Document Number: ECP 11-0512c
Version: 4.0
Date: 04/12/2015
SCHNEIDER RN2, RN6, RN2C AND RN6C WITH VIP 300 RELAY TEST FORM
Substation Name
Substation Number
Voltage
Switchgear
Installed Mode Free-standing () Transformer-mounted ()
Switchboard Number Manufacturer Schneider
Serial Number Type (RN2c/RN6c)
Protection CTs
CT Ratio (400/1 or 800/1)
Relay
Serial Number Setting Range (x2 or x4)
Shunt Trip Coil (if fitted)
20-48V DC () 110-240V AC/DC ()
Protection Settings (specified by planner/designer)
Overcurrent Settings Earth Fault Settings
Setting Current Setting Current
Curve Curve
Time Multiplier Time Multiplier
Highset Setting Current Highset (or SEF) Setting Current
Highset Time Highset (or SEF) Time
Preliminary Checks ()
Disconnect the umbilical cable from the RTU (if fitted)
Visual inspection satisfactory (no visible signs of damage etc)
Earthing satisfactory
SF6 gas pressure satisfactory
Functional/Interlock Checks ()
Open and close switches
Earth switches cannot be operated when service selected
Switch/circuit-breaker cannot be operated when earth selected
Open and close earth switches
Test access cannot be opened when switch/circuit-breaker in On and Off position
Test access can be opened when earth switch closed
Switch/circuit-breaker cannot be operated when test access open
Actuator operation satisfactory using an RTU simulator (LPN Remsdaq RTU only)
THIS
IS A
N U
NC
ON
TRO
LLED
DO
CU
MEN
T, T
HE
REA
DER
MU
ST C
ON
FIR
M IT
S VA
LID
ITY
BEF
OR
E U
SE
Document Number: ECP 11-0512c
Version: 4.0
Date: 04/12/2015
Transformer Winding Insulation Resistance using Test Voltage from ECS 11-0006 (transformer-mounted units only)
HV windings to earth (LV windings connected together and to earth) M
LV windings to earth (HV windings connected together and to earth) M
Switchgear Continuity Test
RSW1 RSW2 CB Terminals Under Test Continuity
TM* FS* TM* FS*
RSW1 to RSW2 RSW1 to RSW2 to CB
Closed Closed Open Closed L1 - L1 L1 - L1 - L1
Closed Closed Open Closed L2 - L2 L2 - L2 - L2
Closed Closed Open Closed L3 - L3 L3 - L3 - L3
Closed Open Closed L1 - L2 (RSW1)
Closed Open Closed L2 - L3 (RSW1)
RSW1 RSW2 CB Terminals Under Test Continuity
Earthed Open Open RSW1 L1 - E
L2 - E
L3 - E
Open Earthed Open RSW2 L1 - E
L2 - E
L3 - E
HV Insulation Tests using Test Voltage from ECS 11-0006
RSW1 RSW2 CB Terminal Voltage (kV)
Duration (min)
IR (M)
Under Test
Earthed
TM* FS* RSW1 RSW2 CB(FS* only)
Closed Closed Open Closed L1 L2, L3
Closed Closed Open Closed L2 L1, L3
Closed Closed Open Closed L3 L1, L2
Open Closed Open Closed L1, L2, L3
L1, L2, L3
L1, L2, L3
Closed Open Open Open L1, L2, L3
L1, L2, L3
* TM - transformer-mounted and FS - free-standing.
FPI CTs Insulation Resistance using 1kV Test Voltage(test from CT wiring terminal block)
Disconnect FPI (if fitted) ()
Schneider RN2, RN6, RN2c and RN6c with Vip 300 Relay Test Form
Document Number: ECP 11-0512c
Version: 4.0
Date: 04/12/2015
RSW1 RSW2 (if fitted)
Remove CT wiring earth link D190 - D170 () D190 - D270 ()
L1, L2, L3 D111, D131, D151 - Earth
M D111/2, D131/2, D151/2 - earth
M
Replace CT wiring earth link D190 - D170 () D190 - D270 ()
FPI CTs Loop Continuity(test from CT wiring terminal block)
RSW1 RSW2 (if fitted)
L1 D111 - D170 D111/2 - D170/2
L2 D131 - D170 D131/2 - D170/2
L3 D151 - D170 D151/2 - D170/2
Reconnect FPI (if fitted) ()
Protection CTs Insulation Resistance using 1kV Test Voltage
Disconnect CT wiring from relay C11, C31, C51, C71 ()
Remove CT wiring earth link C70 - C90 ()
Measure the insulation resistance C70 - Earth M
Replace CT wiring earth link C70 - C90 ()
Protection CTs Loop Continuity(from CT wiring terminal block)
Measure L1 CT continuity C11 - C70
Measure L3 CT continuity C31 - C70
Measure L3 CT continuity C51 - C70
© UK Power Networks 2016 All rights reserved 3 of 8
Schneider RN2, RN6, RN2c and RN6c with Vip 300 Relay Test Form
Document Number: ECP 11-0512c
Version: 4.0
Date: 04/12/2015
Dual Ratio Protection CTs
For switchgear with dual ratio protection CTs select the appropriate ratio (see appendix A.4) to give the required protection settings and record CT ratio on the front of the form
()
CT Ratio Terminal Block Connections
400/1C112 - 2C132 - 6C152 - 10
()
800/1C112 - 3C132 - 7C152 - 11
()
Relay CT Connections
Reconnect the CT wiring to the relay - use the x2 range unless the required setting current is greater than that available within the range (Appendix A.5) and record the range on the front of the form
Range Relay Connections 200/1 CTs 400/1 CTs 800/1 CTs
x2
C11 - 8C31 - 6C51 - 4C71 - 2&9
20-100A 40-200A 80-400A ()
x4
C11 - 7C31 - 5C51 - 3C71 - 1&9
40-200A 80-400A 160A-800A ()
Ensure the reversible scale label matches the CT ratio and selected range ()
Measure the earth resistance between the relay case and the switchgear earth
© UK Power Networks 2016 All rights reserved 4 of 8
Schneider RN2, RN6, RN2c and RN6c with Vip 300 Relay Test Form
Document Number: ECP 11-0512c
Version: 4.0
Date: 04/12/2015
Test Protection Settings
Apply the following temporary settings to the relay (refer to Appendix A for guidance) ()
Overcurrent Settings Earth Fault Settings
Is 72A or 80A* Ios 60A or 64A*
I> curve SI Io> curve SI
DT only 3 DT only 3
t> 0.6 x10 to> 0.6 x10
I>> off Io>> off
t>> 0.03 to>> 0.03
* Available setting will depend on the CT ratio and the range being used. Note: It is not possible to carry out the pickup test below for 800/1 CTs on the x4 range.
Relay Operation - Primary Injection Test
Increase current until the LED starts to flash and record the current value. Reset the relay and, if necessary, close the circuit breaker before each test
Overcurrent Pickup Test
RSW1 RSW2 CB Conductors Under Test
Short Conductors
Is Setting
Calculated Pickup Current (Is + 20%)
Actual Pickup Current
RSW1 CB
Closed Open Closed L1 - L2 L1, L2, L3 72/80A 87/96A A
Closed Open Closed L2 - L3 L1, L2, L3 72/80A 87/96A A
Earth Fault Pickup Test
RSW1 RSW2 CB Conductors Under Test Ios Setting
Calculated Pickup Current (Ios + 20%)
Actual Pickup Current
RSW1 CB
Closed Open Closed L1 L1 60/64A 72/77A A
Closed Open Closed L2 L2 60/64A 72/77A A
Closed Open Closed L3 L3 60/64A 72/77A A
© UK Power Networks 2016 All rights reserved 5 of 8
Schneider RN2, RN6, RN2c and RN6c with Vip 300 Relay Test Form
Document Number: ECP 11-0512c
Version: 4.0
Date: 04/12/2015
In-service Protection Settings
Apply the in-service protection settings as specified by the planner/designer to the relay and record them below (refer to Appendix A for guidance) ()
Overcurrent Settings Earth Fault Settings
Is Ios
I> curve Io> curve
DT only DT only
t> Select from table on relay
to> Select from table on relayx10 / x1 x10 / x1
I>> (Highset Current ÷Is) Io>> (Highset Current ÷Is)
t>> to>>
Table A - Calculate Injection Currents Overcurrent Setting Earth Fault Setting
CT Ratio
Primary Setting Current (Is) (Ios)
Secondary Setting Current (Primary Setting Current ÷ CT Ratio)
2 x Secondary Setting Current
5 x Secondary Setting Current
I>> or Io>> x Secondary Setting Current (highset)*
DT x Secondary Setting Current (SEF)*
Table B - Calculate Operating Times Overcurrent Setting Earth Fault Setting
Curve (I>) (Io>)
Time Setting on relay
(if x10 is selected multiply t> or to> setting by 10)
(t>) (to>)
(t>>) (to>>)
Tripping time at 2 x secondary current
Curve SI (t> or to> x 3.38) +0.09s s s
Curve VI (t> or to> x 9) + 0.09s s s
Curve EI (t> or to> x 33) + 0.09s s s
Tripping time at 5 x secondary current
Curve SI (t> or to> x 1.44) + 0.09s s s
Curve VI (t> or to> x 2.25) + 0.09s s s
Curve EI (t> or to> x 4.1) + 0.09s s s
Tripping time at I>> or Io>> or DT x Secondary Setting Current
Highset/Instantaneous t>> or to>> + 0.09s s s
SEF* to> + 0.09s s
* Only calculate highset, instantaneous or SEF settings if used.
© UK Power Networks 2016 All rights reserved 6 of 8
Schneider RN2, RN6, RN2c and RN6c with Vip 300 Relay Test Form
Document Number: ECP 11-0512c
Version: 4.0
Date: 04/12/2015
Relay Operation - Secondary Injection Test
Connect timer circuit to auxiliary contacts 64 and 65 (contact closed when CB open) ()
Overcurrent Test
SettingCalculated Injection Current(from table A)
Calculated Operating Time (from table B)
Actual Operating Times
C11 - C31 C31 - C51 C51 - C11
2x A s s s s
5x A s s s s
Instantaneous A s s s s
Earth Fault Test
SettingCalculated Injection Current(from table A)
Calculated Operating Time (from table B)
Actual Operating Times
C11 - C70 C31 - C70 C51 - C70
2x A s s s s
5x A s s s s
Instantaneous A s s s s
SEF* A s s s s
* The trip current may have to be increased to operate the circuit breaker if the current is below the minimum operating current.
Shunt Trip and Emergency Trip (if fitted)
Check correct shunt trip coil voltage is selected ()
Test Coil Terminals Test Voltage CB Trips
Apply 70% (dc) or 85% (ac) of coil rated voltage
20-48V DC 47 - 48 V ()
110-240V AC/DC 47 - 49 V ()
Apply 110% Voltage of coil rated voltage
20-48V DC 47 - 48 V ()
110-240V AC/DC 47 - 49 V ()
Check emergency trip button operates circuit-breaker ()
Final Checks ()
Check correct CT and interposing CT ratios selected
Check correct ratio labels have been fitted
Check correct protection settings applied
Check relay reset
Ensure FPI CT shorting-link(s) are replaced if CTs are not used or not connected to FPI or RTU
Reconnect umbilical cable to RTU (if fitted)
Asset data form completed
© UK Power Networks 2016 All rights reserved 7 of 8
Schneider RN2, RN6, RN2c and RN6c with Vip 300 Relay Test Form
Document Number: ECP 11-0512c
Version: 4.0
Date: 04/12/2015
Test Equipment
Make/Type Serial Number Calibration Date
Certification ()
All tests have been completed satisfactorily
Comments
Commissioning Engineer Signature Date
The completed test form shall be left on-site in a plastic wallet and in secure location. A copy of the completed test shall be sent to the relevant ART mailbox.
© UK Power Networks 2016 All rights reserved 8 of 8
Schneider RN2, RN6, RN2c and RN6c with Vip 300 Relay Test Form
Document Number: ECP 11-0512c
Version: 4.0
Date: 04/12/2015
Appendix A – Vip 300
A.1 Introduction
The Vip 300 is a self-powered three phase overcurrent and earth fault protection relay. Protection settings are displayed on the relay front panel (see section A.2) along with manual reset and trip flags.
The CTs are connected to one of two sets of inputs to the relay, to give two different setting current ranges. It is important to ensure that the correct scale label (see section A.3) is in place (either x4 or x2) depending on the inputs and the CT ratio used.
Settings are applied by adjusting the dial selectors to the correct location using a screwdriver. Care should be taken when applying the time settings as the Vip 300 does not use the time multiplier as the time input for IDMT curves (t> or to>). Instead the table on the top right of the front panel should be used to convert the required time multiplier to the Vip 300 setting depending on the IDMT characteristic being applied. For definite time settings (DT, I>>, Io>>) the dials give the relay operating time.
For example, to apply the following typical settings to a Vip 300 relay with 400/1 CTs:
OC 200A VI 0.1TM SEF 32A DT 3s
Looking at the range cards for 400/1 CTs it can be seen that the x2 range provides the option for a phase overcurrent setting (Is) of 200A and an earth fault setting current (Ios) of 32A, the x2 range inputs should be used.
Applying the overcurrent setting:
1. Is should be set to 200.2. I> curve selection should be set to VI.3. t> should be set to 0.3 with a multiplier of x1 (from the table provided this corresponds to
a time multiplier of 0.1).4. As no high set overcurrent is required, I>> should be set to OFF.5. As no high set overcurrent is required, t>> should be set to 0.03.
Applying the earth fault setting:
1. Ios should be set to 32.2. Ios> curve selection should be set to DT.3. DT should be set to 1.4. t> should be set to 0.3 with a multiplier of x10.5. As no high set earth fault is required, Io>> should be set to OFF.6. As no high set earth fault is required, to>> should be set to 0.03.
© UK Power Networks 2016 All rights reserved 1
Schneider RN2, RN6, RN2c and RN6c with Vip 300 Relay Test Form
Document Number: ECP 11-0512c
Version: 4.0
Date: 04/12/2015
A.2 Front Panel
VIP 300
VAP6 test plug
EI,VI,SI
DT
RI
DT only
11.2
1.51.8 2.1
2.42.7
3
( x Is)
x 10
x 1
t >>
0.030.05
0.10.2 0.4
0.60.9
1.5(s)
DT
RI
SIVI EI
off
curve selection
I>phase
overcurrent
I>
trip
sensors:800/1 4509169A0VIP 300LH range: x2
34
69 12
1520
( x Is)
I>>
off
DT only
1
1.21.5
1.8 2.12.42.7
3
( x Ios)
x 10
x 1
200
816
3248
64 96 128160
240280
320(A)
Ios
Io>
trip
minimum operatingphase current: 80A
earth fault
0.90.03
0.050.1
0.2 0.40.6
1.5(s)
to >>
reset
34
69 12
1520
( x Ios)
Io>>
off
VIP300Settings
Equivalent TimeMultiplier
t>, to> SI VI EI0.05 x1 0.02 0.03 0.060.07 x1 0.02 0.05 0.090.1 x1 0.03 0.07 0.120.15 x1 0.05 0.1 0.190.2 x1 0.07 0.13 0.250.3 x1 0.1 0.2 0.370.4 x1 0.13 0.27 0.50.05 x10 0.17 0.33 0.620.6 x1 0.2 0.4 0.740.07 x10 0.24 0.47 0.870.1 x10 0.34 0.67 1.240.15 x10 0.5 1 1.860.2 x10 0.67 1.33 2.480.3 x10 1.01 2 3.710.4 x10 1.35 2.67 4.950.6 x10 2.02 4 7.43
Warning
not timemultiplier
see table
Warning
not timemultiplier
see table
288
8096
120144
168192 224256
320360
400(A)
Is
0.40.05
0.070.1
0.15 0.20.3
0.6(s)
to >
DT
RI
SIVI EI
off
curve selection
Io>
t >
0.050.07
0.10.15 0.2
0.3
0.40.6
(s)
A.3 Scale Labels
Reversible scale label for Ringmaster fitted with
200/1CTs
Reversible scale label for Ringmaster fitted with
400/1CTs
Reversible scale label for Ringmaster fitted with
800/1CTs
© UK Power Networks 2016 All rights reserved 2
Schneider RN2, RN6, RN2c and RN6c with Vip 300 Relay Test Form
Document Number: ECP 11-0512c
Version: 4.0
Date: 04/12/2015
A.4 Dual Ratio CT Connections
Note: The orientation of the connections may vary depending on the vintage of the switchgear.
A.5 Relay CT Connections
© UK Power Networks 2016 All rights reserved 3
400/1 Ratio
800/1 Ratio
Schneider RN2, RN6, RN2c and RN6c with Vip 300 Relay Test Form
Document Number: ECP 11-0512c
Version: 4.0
Date: 04/12/2015
This page is intentionally left blank.
© UK Power Networks 2016 All rights reserved 4
Schneider RN2, RN6, RN2c and RN6c with Vip 300 Relay Test Form Document Number: ECP 11-0512c
Version: 4.0
Date: 04/12/2015
Appendix B – Schematic Diagrams
© UK Power Networks 2016 All rights reserved 1
Schneider RN2, RN6, RN2c and RN6c with Vip 300 Relay Test Form Document Number: ECP 11-0512c
Version: 4.0
Date: 04/12/2015
© UK Power Networks 2016 All rights reserved 2