Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
TH
IS IS
AN
UN
CO
NT
RO
LL
ED
DO
CU
ME
NT
, T
HE
RE
AD
ER
MU
ST
CO
NF
IRM
IT
S V
AL
IDIT
Y B
EF
OR
E U
SE
ENGINEERING DESIGN STANDARD
EDS 05-2011
AIR CIRCUIT BREAKER PROTECTION SETTINGS
Network(s): EPN, LPN, SPN
Summary: This standard details the current and previous protection settings used on LV air circuit breakers used on the EPN, LPN and SPN networks.
Owner: Paul Williams Date: 13/05/2015
Approved By: Steve Mockford Approved Date: 03/06/2015
This document forms part of the Company’s Integrated Business System and its requirements are mandatory throughout UK Power Networks. Departure from these requirements may only be taken with the written approval of the Director of Asset Management. If you have any queries about this document please contact the author or owner of the current issue.
Applicable To
UK Power Networks External
All UK Power Networks G81 Website
Asset Management Contractors
Capital Programme ICPs/IDNOs
Connections Meter Operators
HSS&TT
Network Operations
UK Power Networks Services
Other
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 2 of 26
Revision Record
Version 4.1 Review Date 03/06/2018
Date 07/09/2016 Author Lee Strachan
Why has the document been updated: minor version update – publish onto G81
What has changed – No content changes, document to be published on G81
Version 4.0 Review Date 03/06/2018
Date 13/05/2015 Author Jesse Garcia
Why has the document been updated: Periodic review
What has changed – Section 3.1 updated to include 10A tagged TLF, Section 3.2 title updated to include EPN and SPN, Sections 3.2.2, 3.2.3 and 3.2.4 - tables referencing RMU TLF Fuse (A) updated, Section 5 reference list updated.
Version 3.1 Review Date 24/04/2015
Date 28/07/2012 Author Lee Strachan
Document reviewed for publishing on G81 website
Version 3.0 Review Date 24/04/2015
Date 19/03/2012 Author Damien Delea
Reclassification of document from EI 05-2011. Document reviewed. All protection settings revised, customer discrimination and grading curves added
Version 2.0 Review Date
Date 07/08/2007 Author D J Collis
Update to current protection settings – Section 6
Version 1.1 Review Date
Date 16/07/2007 Author D J Collis
Section 6.1.1 Iinst = 6 changed to Iinst = 15.
Section 6.1.2 Iinst = 8 changed to Iinst = 15
Version 1.0 Review Date
Date 12/06/2005 Author D J Collis
Original
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 3 of 26
Contents
1 Introduction ............................................................................................................. 5
2 Scope ....................................................................................................................... 5
3 Protection Settings for New ACBs ......................................................................... 5
3.1 General ..................................................................................................................... 5
3.2 Large Supplies to LV Customers Outside Central London and SPN and EPN ........... 6
3.2.1 Legacy Schneider Electric NS1250 ........................................................................... 6
3.2.2 Schneider Electric NT16H1/H2 .................................................................................. 6
3.2.3 Schneider Electric NW16H1 ...................................................................................... 7
3.2.4 Schneider Electric NW20H1 ...................................................................................... 7
3.3 Large Supplies to LV Customers Inside Central London ............................................ 8
3.3.1 Schneider Electric NW20H1 and NW16H1 in Series ................................................. 8
3.4 Reverse Power Relays .............................................................................................. 9
4 Protection Settings for Legacy ACBs .................................................................... 9
4.1 Schneider Electric NW20H1 (2007-2011) .................................................................. 9
4.2 Merlin Gerin NW25H1 and NT16H1 (EPN 2003 to 2007) ........................................ 10
4.3 Merlin Gerin NW16H1 and NW20H1 (LPN 2003 to 2007)........................................ 10
4.4 Merlin Gerin NS1250 (EPN 2003 onwards) ............................................................. 11
4.5 Merlin Gerin M16H1 (EPN 1993 to 2003) ................................................................ 11
4.6 Merlin Gerin M25 (EPN 1993 to 2003) ..................................................................... 12
4.7 Merlin Gerin M16 and M25 (EPN 1991 to 1993) ...................................................... 12
4.8 Merlin Gerin M16 and M25 (EPN 1991 to 1993) ...................................................... 13
4.9 Merlin Gerin C1250N and C1251N (EPN 1988 to 1992) .......................................... 13
4.10 Dorman Smith 600A and 1250A MCCB (before 1988) ............................................. 14
5 Reference Documents ........................................................................................... 14
Appendix A – Protection Settings Explained .................................................................. 15
A.1 Schneider Electric Micrologic Protection Modules ................................................... 15
A.2 Merlin Gerin (or Schneider Electric) STR38ST Trip Unit Settings ............................ 15
A.3 Dorman Smith Trip Units ......................................................................................... 15
Appendix B – AMTECH Protection Curves...................................................................... 16
B.1 Schneider Electric NS1250 – 11kV 750/700kVA Transformer ................................. 16
B.2 Schneider Electric NS1250 – 11kV 500kVA Transformer ........................................ 17
B.3 Schneider Electric NT16H1/H2 – 11kV 800/750kVA Transformer ............................ 18
B.4 NT16H1/H2 – 11kV 500kVA Transformer ................................................................ 19
B.5 Schneider Electric NW16H1 – 11kV 800/750kVA Transformer ................................ 20
B.6 Schneider Electric NW16H1 – 6.6kV 500kVA Transformer ...................................... 21
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 4 of 26
B.7 Schneider Electric NW20H1 – 11kV 1000/800/750kVA Transformer ....................... 22
B.8 Schneider Electric NW20H1 – 11kV 500kVA Transformer ....................................... 23
B.9 NW20H1 – 6.6kV 1000/800/750/500kVA Transformer ............................................. 24
B.10 NW16H1 and NW20H1 – 11kV 1000/800kVA Transformer ..................................... 25
Appendix C – Central London and the High Load Density Load Zone .......................... 26
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 5 of 26
1 Introduction
This standard details the protection settings for LV Air Circuit Breakers (ACB) and includes settings for new and legacy ACBs.
This standard has been updated to meet the requirements for large customer LV supplies detailed in UK Power Networks EDS 08-0143.
2 Scope
This standard applies to all ACBs on UK Power Networks EPN, LPN and SPN networks.
3 Protection Settings for New ACBs
3.1 General
A common range of ACBs are available and are used to provide large supplies to LV customers or supply the LPN interconnected network (with reverse power relays). Refer to UK Power Networks EDS 08-0803 for further information on their application.
The approved ranges of ACBs are supplied by Schneider Electric and are fitted with a Micrologic 5.0A protection module to provide overcurrent protection. Refer to the relevant Engineering Approval Standard for the current range of approved ACBs.
The ACB protection settings have been selected to provide the best discrimination between the network LV board on which there are large BS88 J type fuses to customers.
The protection settings for various ACBs and various sizes of transformer to discriminate with a 15A or 10A tagged TLF, used for transformer HV overcurrent protection, are given in the sections that follow. The tagged type TLFs shall be used in conjunction with LV ACBs to allow for discrimination in settings. An explanation of the various settings is given in Appendix A and the associated AMTECH curves are included in Appendix B.
If the standard settings are not suitable due to network variations please contact UK Power Networks Asset Management for site specific settings.
Note:
The Micrologic protection module is pre-set with the protection settings for a 750/800/1000kVA transformer by the supplier.
The Micrologic 6.0A is not suitable for use on the LPN network and care should be taken when it is used on the other networks as the earth fault settings may not provide sufficient discrimination or co-ordination with downstream fusing.
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 6 of 26
3.2 Large Supplies to LV Customers Outside Central London and SPN and EPN
Refer to Appendix C for the definition of Central London and the Central High Load Density Zone.
3.2.1 Legacy Schneider Electric NS1250
Large supplies (above 400A three-phase) to LV customers.
ACB NS1250
System Voltage (kV) 11(6.6) 11(6.6)
Transformer (kVA) 750, 700 500
RMU CT Ratio 100/5 100/5
RMU TLF Fuse (A) 15 15
ACB Protection Module Micrologic 5.0A Micrologic 5.0A
ACB Protection Settings Ir = 1.0 Ir = 0.9
tr = 4 tr = 4
Isd = 4 Isd = 4
tsd = 0.2+ I2t tsd = 0.2+ I
2t
Iinst = 15 Iinst = 15
3.2.2 Schneider Electric NT16H1/H2
Large supplies (above 400A three-phase) to LV customers.
ACB NT16H1/H2
System Voltage (kV) 11/6.6 11/6.6
Transformer (kVA) 800, 750 500
RMU CT Ratio 100/5 100/5
RMU TLF Fuse (A) 15; 10 depending on load for SPN, EPN
15; 10 depending on load for SPN, EPN
ACB Protection Module Micrologic 5.0A Micrologic 5.0A
ACB Protection Settings Ir = 1 Ir = 0.8
tr = 4 tr = 4
Isd = 4 Isd = 4
tsd = 0.1+ I2t tsd = 0.1+ I
2t
Iinst = 12 Iinst = 12
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 7 of 26
3.2.3 Schneider Electric NW16H1
Large supplies above 400A three-phase to LV customers.
ACB NW16H1
System Voltage (kV) 11/6.6 11/6.6
Transformer (kVA) 800, 750 500
RMU CT Ratio 100/5 100/5
RMU TLF Fuse (A) 15; 10 depending on load for SPN, EPN
15; 10 depending on load for SPN, EPN
ACB Protection Module Micrologic 5.0A Micrologic 5.0A
ACB Protection Settings Ir = 1 Ir = 0.8
tr = 4 tr = 4
Isd = 4 Isd = 4
tsd = 0.1+ I2t tsd = 0.1+ I
2t
Iinst = 15 Iinst = 15
3.2.4 Schneider Electric NW20H1
Large supplies (above 400A three-phase) to LV customers.
ACB NW20H1
System Voltage (kV) 11 11 6.6
Transformer (kVA) 1000, 800, 750 500 1000, 800, 750, 500
RMU CT Ratio 100/5 50/5 100/5
RMU TLF Fuse (A) 15; 10 depending on load for SPN, EPN
15; 10 depending on load for SPN, EPN
15; 10 depending on load for SPN, EPN
ACB Protection Module Micrologic 5.0A Micrologic 5.0A Micrologic 5.0A
ACB Protection Settings Ir = 1 Ir = 0.6 Ir = 0.7
tr = 4 tr = 4 tr = 4
Isd = 4 Isd = 4 Isd = 4
tsd = 0.1+ I
2t
tsd = 0.1+ I
2t
tsd = 0.1+ I
2t
Iinst = 15 Iinst = 10 Iinst = 12
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 8 of 26
3.3 Large Supplies to LV Customers Inside Central London
Refer to Appendix C for the definition of Central London and the Central High Load Density Zone.
3.3.1 Schneider Electric NW20H1 and NW16H1 in Series
Large supplies (above 400A three-phase) to LV customers in the central high load density zone in Central London. These settings have been selected to provide protection discrimination between the 2000A network ACB and the 1600A customer ACB. The over-current facility on the 2000A ACB is required to grade for both the 1600A customer ACB and the other LV customer connections.
ACB NW20H1 NW16H1
System Voltage (kV) 11/6.6 11/6.6
Transformer (kVA) 1000,800 1000, 800
RMU CT Ratio 100/5 100/5
RMU TLF Fuse (A) 15 15
ACB Protection Module Micrologic 5.0A Micrologic 5.0A
ACB Protection Settings Ir = 0.8 Ir = 1
tr = 4 tr = 8
Isd = 4 Isd = 5
tsd = 0.1+ I2t tsd = 0.2+ I2t
Iinst = 10 Iinst = 12
LV Network
11kV
400V
Secondary Substation
2000A ACB
1600A ACB
Large LV
Customer
1000kVA/
800kVA
Figure 1 – Large Supplies to Customers in Central London
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 9 of 26
3.4 Reverse Power Relays
On the LV interconnected network in the LPN area, reverse power relays are used to detect reverse power flow caused by a fault on the HV side of the transformer and trip the ACB to prevent back feed from the LV side. Over-current protection is not required on these ACBs.
There are two types of relay used:
The English Electric CAG with a PCD directional element;
The Reyrolle TGG relay.
Both relays have fixed settings that are set to trip at roughly three times the LV current with the secondary set at 10A.
4 Protection Settings for Legacy ACBs
This section details the protection settings for legacy ACBs used on the EPN, LPN and SPN networks between 1st July 2007 and 31st December 2011.
Note: ACBs were introduced in SPN in 2007.
4.1 Schneider Electric NW20H1 (2007-2011)
ACB NW20H1
System Voltage (kV) 11 11 6.6
Transformer (kVA) 1000, 800, 750 500
RMU CT Ratio 100/5 50/5
RMU TLF Fuse (A) 15 15
ACB Protection Module Micrologic 6.0A/6.0P Micrologic 6.0A/6.0P Micrologic 6.0A/6.0P
ACB Protection Settings Ir = 1 Ir = 0.6 Ir = 0.7
tr = 4 tr = 4 tr = 4
Isd = 4 Isd = 4 Isd = 4
tsd = 0.1+ I2t tsd = 0.1+ I
2t tsd = 0.1+ I
2t
Iinst = 15 Iinst = 15 Iinst = 15
Ig = Ig = Ig =
tg = tg = tg =
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 10 of 26
4.2 Merlin Gerin NW25H1 and NT16H1 (EPN 2003 to 2007)
The Merlin Gerin NW25H1 was used with 1500kVA and 1000kVA transformers. The Merlin Gerin NT16H1 is only used with 1000kVA transformers. Note: These units have been selected to cope with 130% overload conditions.
Application Large supplies to LV customers
ACB NW25H1 NW25H1 NT16H1
Transformer 1500kVA 1000kVA 1000kVA
Protection Module Micrologic 6.0A Micrologic 6.0A Micrologic 6.0A
Protection Settings Ir = 0.9 Ir = 0.7 Ir = 1
tr = 8 tr = 8 tr = 8
Isd = 2 Isd = 2 Isd = 3
tsd = 0.2 + I2t tsd = 0.2+ I
2t tsd = 0.3 + I
2t
Ii= 12 Ii = 12 Ii = 12
tg = 0.4+ I2t ON tg = 0.4+ I
2t ON tg = 0.4+ I
2t ON
4.3 Merlin Gerin NW16H1 and NW20H1 (LPN 2003 to 2007)
The Merlin Gerin NW16H1 was used with 800kVA transformers and below. The Merlin Gerin NW20H1 was used with 1000kVA transformers. Note: These units have been selected to cope with 160% overload conditions.
Application Large supplies to LV customers or network support for the interconnected network
ACB NW16H1 NW20H1
Transformer 800kVA and below 1000kVA
Protection Module Micrologic 5.0A Micrologic 5.0A
Protection Settings Ir = 1 Ir = 1
tr = 4 tr = 4
Isd = 6 Isd = 8
tsd = 0.1+I2t tsd = 0.1+I
2t
Iinst = 15 Iinst = 15
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 11 of 26
4.4 Merlin Gerin NS1250 (EPN 2003 onwards)
The Merlin Gerin NS1250 was used with 500kVA and 700 kVA transformers. Note: This unit has been selected to cope with 130% overload conditions.
Application Large supplies to LV customers
ACB NS1250 NS1250
Transformer 500kVA 700kVA
Protection Module Micrologic 5.0A Micrologic 5.0A
Protection Settings Ir = 0.9 Ir = 1
tr = 8 tr = 8
Isd = 2.5 Isd = 5
tsd = 0.3 + I2t tsd = 0.3 + I
2t
Ii = 15 Ii = 15
4.5 Merlin Gerin M16H1 (EPN 1993 to 2003)
The Merlin Gerin M16H1 was used with 1000kVA transformers. Note: This unit has been selected to cope with 130% overload conditions.
Application Large supplies to LV customers
ACB M16H1
Transformer 1000kVA
Protection Module STR38ST
Protection Settings Io = 1
Ir = 1
Im = 3
tm = 0.3 + I2t ON
Ii = max/ON (any position in shaded area)
Ih = 500
th = 0.4 + I2t ON
Minimum tripping current 1680A
Note:
Current in excess of the minimum tripping currents may trip the circuit-breaker after 200s.
The STR38ST trip units used on Masterpact ACBs from 1993 may be unstable and may give nuisance tripping on low loads if Ih is set to less than 500A.
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 12 of 26
4.6 Merlin Gerin M25 (EPN 1993 to 2003)
The Merlin Gerin M25 was used with 1500kVA and 1000kVA transformers. Note: This unit has been selected to cope with 130% overload conditions.
Application Large supplies to LV customers
ACB M25 M25
Transformer 1500kVA 1000kVA
Protection Module STR38ST STR38ST
Protection Settings Io = 1 Io = 0.63
Ir = 0.9 Ir = 1
Im = 2 Im = 2
tm = 0.2 + I2t ON tm = 0.2 + I
2t ON
I = max/ON (any position in shaded area)
I = max/ON (any position in shaded area)
Minimum tripping current 2360A Minimum tripping current 2360A
Note:
Current in excess of the minimum tripping current may trip the circuit-breaker after 200s.
The STR38ST trip units used on Masterpact ACBs from 1993 may be unstable and may give nuisance tripping on low loads if Ih is set to less than 500A.
4.7 Merlin Gerin M16 and M25 (EPN 1991 to 1993)
The Merlin Gerin M16 was used with 1000kVA transformers and the Merlin Gerin M25 was used with 1500kVA and 1000kVA transformers. Note: These units have been selected to cope with 130% overload conditions.
Application Large supplies to LV customers
ACB M16 M25 M25
Transformer 1000kVA 1500kVA 1000kVA
Protection Module STR308ST STR38ST STR38ST
Protection Settings Ir = 1 Ir = 0.9 Ir = 0.63
Im = 3 Im = 2.5 Im = 2.5
tm = 0.3 tm = 0.3 tm = 0.3
Ih = 0.2 Ih = 0.2 Ih = 0.2
Minimum tripping current 1680A
Minimum tripping current 2360A
Minimum tripping current 2360A
Note: Current in excess of the minimum tripping currents may trip the breaker after 200s.
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 13 of 26
4.8 Merlin Gerin M16 and M25 (EPN 1991 to 1993)
The Merlin Gerin M16 was used with 1000kVA transformers and the Merlin Gerin M25 was used with 1500kVA and 1000kVA transformers. Note: These units have been selected to cope with 130% overload conditions.
Application Large supplies to LV customers
ACB M16 M25 M25
Transformer 1000kVA 1500kVA 1000kVA
Protection Module STR308ST STR38ST STR38ST
Protection Settings Ir = 1 Ir = 0.9 Ir = 0.63
Im = 3 Im = 2.5 Im = 2.5
tm = 0.3 tm = 0.3 tm = 0.3
Ih = 0.2 Ih = 0.2 Ih = 0.2
Minimum tripping current 1680A
Minimum tripping current 2360A
Minimum tripping current 2360A
Note: Current in excess of the minimum tripping currents may trip the breaker after 200s.
4.9 Merlin Gerin C1250N and C1251N (EPN 1988 to 1992)
The Merlin Gerin C1250N and C1251N were used with 500kVA and 700kVA transformers. Note: These units have been selected to cope with 130% overload conditions.
Application Large supplies to LV customers
ACB C1250N C1250N C1251N C1251N
Transformer 500kVA 700kVA 500kVA 700kVA
Protection Settings Io = 1 Io = 1
Protection Settings Ir = 0.8 Ir = 1 Ir = 0.9 Ir = 1
Im = 4 Im = 5 Im = 2.5 Im = 6
tm = 0.3 tm = 0.3 + I2t
ON
tm = 0.3 + I2t ON tm = 0.3
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 14 of 26
4.10 Dorman Smith 600A and 1250A MCCB (before 1988)
The Dorman Smith 600A and 1200A MCCBs were used with 500kVA and 700kVA transformers respectively.
Application Large supplies to LV customers
ACB 600A 1250A
Transformer 500kVA 700kVA
Protection Module 600A Tripping Unit Type A 1250A Tripping Unit Type B
Thermal Over Load Setting No. 5 No. 4
Instantaneous Magnetic Release High High
5 Reference Documents
EAS 00-0008 LV Plant and Equipment Materials List
EDS 08-0143 Customer LV Supplies Above 100A
EDS 08-0803 LV Air Circuit Breaker Specification
EAS 13-0031 Schneider Electrical NT16 H2, NW16 H1 and NW20 H1 Air Circuit Breakers
EAS 13-0032 Schneider Electrical NT16 Air Circuit Breaker Transformer Mounted
Legacy breaker Schneider Electric NS1250 Air Circuit Breaker Supply Cubicle
Legacy breaker Schneider master pack NW25H1
Legacy EPN breaker NW 2500AH1 ACB 1 - Schneider Electric
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 15 of 26
Appendix A – Protection Settings Explained
This appendix provides a brief explanation of the protection settings used on the various protection modules.
A.1 Schneider Electric Micrologic Protection Modules
Protection Element
Description Function
Ir Long time current setting Adjusts pickup current
tr Long time tripping delay Adjusts time to trip the long time current setting
Isd Short time pickup (multiple of Ir) Adjusts current setting of intermediate vertical lines
tsd Short time tripping delay Adjusts time setting of high current trip (2nd horizontal/ slope from left)
Iinst or Ii Instantaneous pickup Sets high current instantaneous pickup
Ig Earth fault pickup Adjusts earth fault current
tg Earth fault time delay Adjusts earth fault time delay
A.2 Merlin Gerin (or Schneider Electric) STR38ST Trip Unit Settings
Protection Element
Description Function
Io Long time current setting Provides a wider range of pickup current
Ir Long time current setting (on STR38ST or C1251N = Io x Ir)
Adjusts pickup current
Im Short time pickup (multiple of Ir) Adjusts current setting of intermediate vertical lines
tm Short time tripping delay Adjusts time setting of high current trip (2nd horizontal/ slope from left)
Ii Instantaneous pickup (STR38ST has 2 settings only - MAX and OFF)
Sets high current instantaneous pickup
Ih Earth fault pickup Adjusts earth fault current
th Earth fault time delay Adjusts earth fault time delay
A.3 Dorman Smith Trip Units
The trip unit size is not visible unless the MCCB (Moulded Case Circuit Breaker) front panel is removed. Note: That the 600A trip unit is rated at 700A when fitted in the standard (1250A) MCCB and cubicle.
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 16 of 26
Appendix B – AMTECH Protection Curves
This appendix contains the AMTECH plots for each of the settings in Section 3. Key:
Top (red) curve – ring main unit (HV AC Series Tripping) 15A tagged TLF fuse.
Middle (green) (green or blue in B10) curve – ACB.
Bottom (blue) (orange in B10) curve – 400A BS88 J type supply fuse.
B.1 Schneider Electric NS1250 – 11kV 750/700kVA Transformer
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 17 of 26
B.2 Schneider Electric NS1250 – 11kV 500kVA Transformer
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 18 of 26
B.3 Schneider Electric NT16H1/H2 – 11kV 800/750kVA Transformer
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 19 of 26
B.4 NT16H1/H2 – 11kV 500kVA Transformer
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 20 of 26
B.5 Schneider Electric NW16H1 – 11kV 800/750kVA Transformer
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 21 of 26
B.6 Schneider Electric NW16H1 – 6.6kV 500kVA Transformer
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 22 of 26
B.7 Schneider Electric NW20H1 – 11kV 1000/800/750kVA Transformer
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 23 of 26
B.8 Schneider Electric NW20H1 – 11kV 500kVA Transformer
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 24 of 26
B.9 NW20H1 – 6.6kV 1000/800/750/500kVA Transformer
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 25 of 26
B.10 NW16H1 and NW20H1 – 11kV 1000/800kVA Transformer
Air Circuit Breaker Protection Settings Document Number: EDS 05-2011
Version: 4.1
Date: 13/05/2015
© UK Power Networks 2016 All rights reserved 26 of 26
Appendix C – Central London and the High Load Density Load Zone
> 300 MW / km2 by 2015 kw / km
2 x
105
West End
City of London
Docklands