Document Number: EDS 05-2011 Version: 4.1 Date: 13/05/2015 THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE ENGINEERING DESIGN STANDARD EDS 05-2011 AIR CIRCUIT BREAKER PROTECTION SETTINGS Network(s): EPN, LPN, SPN Summary: This standard details the current and previous protection settings used on LV air circuit breakers used on the EPN, LPN and SPN networks. Owner: Paul Williams Date: 13/05/2015 Approved By: Steve Mockford Approved Date: 03/06/2015 This document forms part of the Company’s Integrated Business System and its requirements are mandatory throughout UK Power Networks. Departure from these requirements may only be taken with the written approval of the Director of Asset Management. If you have any queries about this document please contact the author or owner of the current issue. Applicable To UK Power Networks External All UK Power Networks G81 Website Asset Management Contractors Capital Programme ICPs/IDNOs Connections Meter Operators HSS&TT Network Operations UK Power Networks Services Other

EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

  • Upload
    vodiep

  • View
    294

  • Download
    11

Embed Size (px)

Citation preview

Page 1: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

TH

IS IS

AN

UN

CO

NT

RO

LL

ED

DO

CU

ME

NT

, T

HE

RE

AD

ER

MU

ST

CO

NF

IRM

IT

S V

AL

IDIT

Y B

EF

OR

E U

SE

ENGINEERING DESIGN STANDARD

EDS 05-2011

AIR CIRCUIT BREAKER PROTECTION SETTINGS

Network(s): EPN, LPN, SPN

Summary: This standard details the current and previous protection settings used on LV air circuit breakers used on the EPN, LPN and SPN networks.

Owner: Paul Williams Date: 13/05/2015

Approved By: Steve Mockford Approved Date: 03/06/2015

This document forms part of the Company’s Integrated Business System and its requirements are mandatory throughout UK Power Networks. Departure from these requirements may only be taken with the written approval of the Director of Asset Management. If you have any queries about this document please contact the author or owner of the current issue.

Applicable To

UK Power Networks External

All UK Power Networks G81 Website

Asset Management Contractors

Capital Programme ICPs/IDNOs

Connections Meter Operators

HSS&TT

Network Operations

UK Power Networks Services

Other

Page 2: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 2 of 26

Revision Record

Version 4.1 Review Date 03/06/2018

Date 07/09/2016 Author Lee Strachan

Why has the document been updated: minor version update – publish onto G81

What has changed – No content changes, document to be published on G81

Version 4.0 Review Date 03/06/2018

Date 13/05/2015 Author Jesse Garcia

Why has the document been updated: Periodic review

What has changed – Section 3.1 updated to include 10A tagged TLF, Section 3.2 title updated to include EPN and SPN, Sections 3.2.2, 3.2.3 and 3.2.4 - tables referencing RMU TLF Fuse (A) updated, Section 5 reference list updated.

Version 3.1 Review Date 24/04/2015

Date 28/07/2012 Author Lee Strachan

Document reviewed for publishing on G81 website

Version 3.0 Review Date 24/04/2015

Date 19/03/2012 Author Damien Delea

Reclassification of document from EI 05-2011. Document reviewed. All protection settings revised, customer discrimination and grading curves added

Version 2.0 Review Date

Date 07/08/2007 Author D J Collis

Update to current protection settings – Section 6

Version 1.1 Review Date

Date 16/07/2007 Author D J Collis

Section 6.1.1 Iinst = 6 changed to Iinst = 15.

Section 6.1.2 Iinst = 8 changed to Iinst = 15

Version 1.0 Review Date

Date 12/06/2005 Author D J Collis

Original

Page 3: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 3 of 26

Contents

1 Introduction ............................................................................................................. 5

2 Scope ....................................................................................................................... 5

3 Protection Settings for New ACBs ......................................................................... 5

3.1 General ..................................................................................................................... 5

3.2 Large Supplies to LV Customers Outside Central London and SPN and EPN ........... 6

3.2.1 Legacy Schneider Electric NS1250 ........................................................................... 6

3.2.2 Schneider Electric NT16H1/H2 .................................................................................. 6

3.2.3 Schneider Electric NW16H1 ...................................................................................... 7

3.2.4 Schneider Electric NW20H1 ...................................................................................... 7

3.3 Large Supplies to LV Customers Inside Central London ............................................ 8

3.3.1 Schneider Electric NW20H1 and NW16H1 in Series ................................................. 8

3.4 Reverse Power Relays .............................................................................................. 9

4 Protection Settings for Legacy ACBs .................................................................... 9

4.1 Schneider Electric NW20H1 (2007-2011) .................................................................. 9

4.2 Merlin Gerin NW25H1 and NT16H1 (EPN 2003 to 2007) ........................................ 10

4.3 Merlin Gerin NW16H1 and NW20H1 (LPN 2003 to 2007)........................................ 10

4.4 Merlin Gerin NS1250 (EPN 2003 onwards) ............................................................. 11

4.5 Merlin Gerin M16H1 (EPN 1993 to 2003) ................................................................ 11

4.6 Merlin Gerin M25 (EPN 1993 to 2003) ..................................................................... 12

4.7 Merlin Gerin M16 and M25 (EPN 1991 to 1993) ...................................................... 12

4.8 Merlin Gerin M16 and M25 (EPN 1991 to 1993) ...................................................... 13

4.9 Merlin Gerin C1250N and C1251N (EPN 1988 to 1992) .......................................... 13

4.10 Dorman Smith 600A and 1250A MCCB (before 1988) ............................................. 14

5 Reference Documents ........................................................................................... 14

Appendix A – Protection Settings Explained .................................................................. 15

A.1 Schneider Electric Micrologic Protection Modules ................................................... 15

A.2 Merlin Gerin (or Schneider Electric) STR38ST Trip Unit Settings ............................ 15

A.3 Dorman Smith Trip Units ......................................................................................... 15

Appendix B – AMTECH Protection Curves...................................................................... 16

B.1 Schneider Electric NS1250 – 11kV 750/700kVA Transformer ................................. 16

B.2 Schneider Electric NS1250 – 11kV 500kVA Transformer ........................................ 17

B.3 Schneider Electric NT16H1/H2 – 11kV 800/750kVA Transformer ............................ 18

B.4 NT16H1/H2 – 11kV 500kVA Transformer ................................................................ 19

B.5 Schneider Electric NW16H1 – 11kV 800/750kVA Transformer ................................ 20

B.6 Schneider Electric NW16H1 – 6.6kV 500kVA Transformer ...................................... 21

Page 4: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 4 of 26

B.7 Schneider Electric NW20H1 – 11kV 1000/800/750kVA Transformer ....................... 22

B.8 Schneider Electric NW20H1 – 11kV 500kVA Transformer ....................................... 23

B.9 NW20H1 – 6.6kV 1000/800/750/500kVA Transformer ............................................. 24

B.10 NW16H1 and NW20H1 – 11kV 1000/800kVA Transformer ..................................... 25

Appendix C – Central London and the High Load Density Load Zone .......................... 26

Page 5: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 5 of 26

1 Introduction

This standard details the protection settings for LV Air Circuit Breakers (ACB) and includes settings for new and legacy ACBs.

This standard has been updated to meet the requirements for large customer LV supplies detailed in UK Power Networks EDS 08-0143.

2 Scope

This standard applies to all ACBs on UK Power Networks EPN, LPN and SPN networks.

3 Protection Settings for New ACBs

3.1 General

A common range of ACBs are available and are used to provide large supplies to LV customers or supply the LPN interconnected network (with reverse power relays). Refer to UK Power Networks EDS 08-0803 for further information on their application.

The approved ranges of ACBs are supplied by Schneider Electric and are fitted with a Micrologic 5.0A protection module to provide overcurrent protection. Refer to the relevant Engineering Approval Standard for the current range of approved ACBs.

The ACB protection settings have been selected to provide the best discrimination between the network LV board on which there are large BS88 J type fuses to customers.

The protection settings for various ACBs and various sizes of transformer to discriminate with a 15A or 10A tagged TLF, used for transformer HV overcurrent protection, are given in the sections that follow. The tagged type TLFs shall be used in conjunction with LV ACBs to allow for discrimination in settings. An explanation of the various settings is given in Appendix A and the associated AMTECH curves are included in Appendix B.

If the standard settings are not suitable due to network variations please contact UK Power Networks Asset Management for site specific settings.

Note:

The Micrologic protection module is pre-set with the protection settings for a 750/800/1000kVA transformer by the supplier.

The Micrologic 6.0A is not suitable for use on the LPN network and care should be taken when it is used on the other networks as the earth fault settings may not provide sufficient discrimination or co-ordination with downstream fusing.

Page 6: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 6 of 26

3.2 Large Supplies to LV Customers Outside Central London and SPN and EPN

Refer to Appendix C for the definition of Central London and the Central High Load Density Zone.

3.2.1 Legacy Schneider Electric NS1250

Large supplies (above 400A three-phase) to LV customers.

ACB NS1250

System Voltage (kV) 11(6.6) 11(6.6)

Transformer (kVA) 750, 700 500

RMU CT Ratio 100/5 100/5

RMU TLF Fuse (A) 15 15

ACB Protection Module Micrologic 5.0A Micrologic 5.0A

ACB Protection Settings Ir = 1.0 Ir = 0.9

tr = 4 tr = 4

Isd = 4 Isd = 4

tsd = 0.2+ I2t tsd = 0.2+ I

2t

Iinst = 15 Iinst = 15

3.2.2 Schneider Electric NT16H1/H2

Large supplies (above 400A three-phase) to LV customers.

ACB NT16H1/H2

System Voltage (kV) 11/6.6 11/6.6

Transformer (kVA) 800, 750 500

RMU CT Ratio 100/5 100/5

RMU TLF Fuse (A) 15; 10 depending on load for SPN, EPN

15; 10 depending on load for SPN, EPN

ACB Protection Module Micrologic 5.0A Micrologic 5.0A

ACB Protection Settings Ir = 1 Ir = 0.8

tr = 4 tr = 4

Isd = 4 Isd = 4

tsd = 0.1+ I2t tsd = 0.1+ I

2t

Iinst = 12 Iinst = 12

Page 7: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 7 of 26

3.2.3 Schneider Electric NW16H1

Large supplies above 400A three-phase to LV customers.

ACB NW16H1

System Voltage (kV) 11/6.6 11/6.6

Transformer (kVA) 800, 750 500

RMU CT Ratio 100/5 100/5

RMU TLF Fuse (A) 15; 10 depending on load for SPN, EPN

15; 10 depending on load for SPN, EPN

ACB Protection Module Micrologic 5.0A Micrologic 5.0A

ACB Protection Settings Ir = 1 Ir = 0.8

tr = 4 tr = 4

Isd = 4 Isd = 4

tsd = 0.1+ I2t tsd = 0.1+ I

2t

Iinst = 15 Iinst = 15

3.2.4 Schneider Electric NW20H1

Large supplies (above 400A three-phase) to LV customers.

ACB NW20H1

System Voltage (kV) 11 11 6.6

Transformer (kVA) 1000, 800, 750 500 1000, 800, 750, 500

RMU CT Ratio 100/5 50/5 100/5

RMU TLF Fuse (A) 15; 10 depending on load for SPN, EPN

15; 10 depending on load for SPN, EPN

15; 10 depending on load for SPN, EPN

ACB Protection Module Micrologic 5.0A Micrologic 5.0A Micrologic 5.0A

ACB Protection Settings Ir = 1 Ir = 0.6 Ir = 0.7

tr = 4 tr = 4 tr = 4

Isd = 4 Isd = 4 Isd = 4

tsd = 0.1+ I

2t

tsd = 0.1+ I

2t

tsd = 0.1+ I

2t

Iinst = 15 Iinst = 10 Iinst = 12

Page 8: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 8 of 26

3.3 Large Supplies to LV Customers Inside Central London

Refer to Appendix C for the definition of Central London and the Central High Load Density Zone.

3.3.1 Schneider Electric NW20H1 and NW16H1 in Series

Large supplies (above 400A three-phase) to LV customers in the central high load density zone in Central London. These settings have been selected to provide protection discrimination between the 2000A network ACB and the 1600A customer ACB. The over-current facility on the 2000A ACB is required to grade for both the 1600A customer ACB and the other LV customer connections.

ACB NW20H1 NW16H1

System Voltage (kV) 11/6.6 11/6.6

Transformer (kVA) 1000,800 1000, 800

RMU CT Ratio 100/5 100/5

RMU TLF Fuse (A) 15 15

ACB Protection Module Micrologic 5.0A Micrologic 5.0A

ACB Protection Settings Ir = 0.8 Ir = 1

tr = 4 tr = 8

Isd = 4 Isd = 5

tsd = 0.1+ I2t tsd = 0.2+ I2t

Iinst = 10 Iinst = 12

LV Network

11kV

400V

Secondary Substation

2000A ACB

1600A ACB

Large LV

Customer

1000kVA/

800kVA

Figure 1 – Large Supplies to Customers in Central London

Page 9: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 9 of 26

3.4 Reverse Power Relays

On the LV interconnected network in the LPN area, reverse power relays are used to detect reverse power flow caused by a fault on the HV side of the transformer and trip the ACB to prevent back feed from the LV side. Over-current protection is not required on these ACBs.

There are two types of relay used:

The English Electric CAG with a PCD directional element;

The Reyrolle TGG relay.

Both relays have fixed settings that are set to trip at roughly three times the LV current with the secondary set at 10A.

4 Protection Settings for Legacy ACBs

This section details the protection settings for legacy ACBs used on the EPN, LPN and SPN networks between 1st July 2007 and 31st December 2011.

Note: ACBs were introduced in SPN in 2007.

4.1 Schneider Electric NW20H1 (2007-2011)

ACB NW20H1

System Voltage (kV) 11 11 6.6

Transformer (kVA) 1000, 800, 750 500

RMU CT Ratio 100/5 50/5

RMU TLF Fuse (A) 15 15

ACB Protection Module Micrologic 6.0A/6.0P Micrologic 6.0A/6.0P Micrologic 6.0A/6.0P

ACB Protection Settings Ir = 1 Ir = 0.6 Ir = 0.7

tr = 4 tr = 4 tr = 4

Isd = 4 Isd = 4 Isd = 4

tsd = 0.1+ I2t tsd = 0.1+ I

2t tsd = 0.1+ I

2t

Iinst = 15 Iinst = 15 Iinst = 15

Ig = Ig = Ig =

tg = tg = tg =

Page 10: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 10 of 26

4.2 Merlin Gerin NW25H1 and NT16H1 (EPN 2003 to 2007)

The Merlin Gerin NW25H1 was used with 1500kVA and 1000kVA transformers. The Merlin Gerin NT16H1 is only used with 1000kVA transformers. Note: These units have been selected to cope with 130% overload conditions.

Application Large supplies to LV customers

ACB NW25H1 NW25H1 NT16H1

Transformer 1500kVA 1000kVA 1000kVA

Protection Module Micrologic 6.0A Micrologic 6.0A Micrologic 6.0A

Protection Settings Ir = 0.9 Ir = 0.7 Ir = 1

tr = 8 tr = 8 tr = 8

Isd = 2 Isd = 2 Isd = 3

tsd = 0.2 + I2t tsd = 0.2+ I

2t tsd = 0.3 + I

2t

Ii= 12 Ii = 12 Ii = 12

tg = 0.4+ I2t ON tg = 0.4+ I

2t ON tg = 0.4+ I

2t ON

4.3 Merlin Gerin NW16H1 and NW20H1 (LPN 2003 to 2007)

The Merlin Gerin NW16H1 was used with 800kVA transformers and below. The Merlin Gerin NW20H1 was used with 1000kVA transformers. Note: These units have been selected to cope with 160% overload conditions.

Application Large supplies to LV customers or network support for the interconnected network

ACB NW16H1 NW20H1

Transformer 800kVA and below 1000kVA

Protection Module Micrologic 5.0A Micrologic 5.0A

Protection Settings Ir = 1 Ir = 1

tr = 4 tr = 4

Isd = 6 Isd = 8

tsd = 0.1+I2t tsd = 0.1+I

2t

Iinst = 15 Iinst = 15

Page 11: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 11 of 26

4.4 Merlin Gerin NS1250 (EPN 2003 onwards)

The Merlin Gerin NS1250 was used with 500kVA and 700 kVA transformers. Note: This unit has been selected to cope with 130% overload conditions.

Application Large supplies to LV customers

ACB NS1250 NS1250

Transformer 500kVA 700kVA

Protection Module Micrologic 5.0A Micrologic 5.0A

Protection Settings Ir = 0.9 Ir = 1

tr = 8 tr = 8

Isd = 2.5 Isd = 5

tsd = 0.3 + I2t tsd = 0.3 + I

2t

Ii = 15 Ii = 15

4.5 Merlin Gerin M16H1 (EPN 1993 to 2003)

The Merlin Gerin M16H1 was used with 1000kVA transformers. Note: This unit has been selected to cope with 130% overload conditions.

Application Large supplies to LV customers

ACB M16H1

Transformer 1000kVA

Protection Module STR38ST

Protection Settings Io = 1

Ir = 1

Im = 3

tm = 0.3 + I2t ON

Ii = max/ON (any position in shaded area)

Ih = 500

th = 0.4 + I2t ON

Minimum tripping current 1680A

Note:

Current in excess of the minimum tripping currents may trip the circuit-breaker after 200s.

The STR38ST trip units used on Masterpact ACBs from 1993 may be unstable and may give nuisance tripping on low loads if Ih is set to less than 500A.

Page 12: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 12 of 26

4.6 Merlin Gerin M25 (EPN 1993 to 2003)

The Merlin Gerin M25 was used with 1500kVA and 1000kVA transformers. Note: This unit has been selected to cope with 130% overload conditions.

Application Large supplies to LV customers

ACB M25 M25

Transformer 1500kVA 1000kVA

Protection Module STR38ST STR38ST

Protection Settings Io = 1 Io = 0.63

Ir = 0.9 Ir = 1

Im = 2 Im = 2

tm = 0.2 + I2t ON tm = 0.2 + I

2t ON

I = max/ON (any position in shaded area)

I = max/ON (any position in shaded area)

Minimum tripping current 2360A Minimum tripping current 2360A

Note:

Current in excess of the minimum tripping current may trip the circuit-breaker after 200s.

The STR38ST trip units used on Masterpact ACBs from 1993 may be unstable and may give nuisance tripping on low loads if Ih is set to less than 500A.

4.7 Merlin Gerin M16 and M25 (EPN 1991 to 1993)

The Merlin Gerin M16 was used with 1000kVA transformers and the Merlin Gerin M25 was used with 1500kVA and 1000kVA transformers. Note: These units have been selected to cope with 130% overload conditions.

Application Large supplies to LV customers

ACB M16 M25 M25

Transformer 1000kVA 1500kVA 1000kVA

Protection Module STR308ST STR38ST STR38ST

Protection Settings Ir = 1 Ir = 0.9 Ir = 0.63

Im = 3 Im = 2.5 Im = 2.5

tm = 0.3 tm = 0.3 tm = 0.3

Ih = 0.2 Ih = 0.2 Ih = 0.2

Minimum tripping current 1680A

Minimum tripping current 2360A

Minimum tripping current 2360A

Note: Current in excess of the minimum tripping currents may trip the breaker after 200s.

Page 13: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 13 of 26

4.8 Merlin Gerin M16 and M25 (EPN 1991 to 1993)

The Merlin Gerin M16 was used with 1000kVA transformers and the Merlin Gerin M25 was used with 1500kVA and 1000kVA transformers. Note: These units have been selected to cope with 130% overload conditions.

Application Large supplies to LV customers

ACB M16 M25 M25

Transformer 1000kVA 1500kVA 1000kVA

Protection Module STR308ST STR38ST STR38ST

Protection Settings Ir = 1 Ir = 0.9 Ir = 0.63

Im = 3 Im = 2.5 Im = 2.5

tm = 0.3 tm = 0.3 tm = 0.3

Ih = 0.2 Ih = 0.2 Ih = 0.2

Minimum tripping current 1680A

Minimum tripping current 2360A

Minimum tripping current 2360A

Note: Current in excess of the minimum tripping currents may trip the breaker after 200s.

4.9 Merlin Gerin C1250N and C1251N (EPN 1988 to 1992)

The Merlin Gerin C1250N and C1251N were used with 500kVA and 700kVA transformers. Note: These units have been selected to cope with 130% overload conditions.

Application Large supplies to LV customers

ACB C1250N C1250N C1251N C1251N

Transformer 500kVA 700kVA 500kVA 700kVA

Protection Settings Io = 1 Io = 1

Protection Settings Ir = 0.8 Ir = 1 Ir = 0.9 Ir = 1

Im = 4 Im = 5 Im = 2.5 Im = 6

tm = 0.3 tm = 0.3 + I2t

ON

tm = 0.3 + I2t ON tm = 0.3

Page 14: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 14 of 26

4.10 Dorman Smith 600A and 1250A MCCB (before 1988)

The Dorman Smith 600A and 1200A MCCBs were used with 500kVA and 700kVA transformers respectively.

Application Large supplies to LV customers

ACB 600A 1250A

Transformer 500kVA 700kVA

Protection Module 600A Tripping Unit Type A 1250A Tripping Unit Type B

Thermal Over Load Setting No. 5 No. 4

Instantaneous Magnetic Release High High

5 Reference Documents

EAS 00-0008 LV Plant and Equipment Materials List

EDS 08-0143 Customer LV Supplies Above 100A

EDS 08-0803 LV Air Circuit Breaker Specification

EAS 13-0031 Schneider Electrical NT16 H2, NW16 H1 and NW20 H1 Air Circuit Breakers

EAS 13-0032 Schneider Electrical NT16 Air Circuit Breaker Transformer Mounted

Legacy breaker Schneider Electric NS1250 Air Circuit Breaker Supply Cubicle

Legacy breaker Schneider master pack NW25H1

Legacy EPN breaker NW 2500AH1 ACB 1 - Schneider Electric

Page 15: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 15 of 26

Appendix A – Protection Settings Explained

This appendix provides a brief explanation of the protection settings used on the various protection modules.

A.1 Schneider Electric Micrologic Protection Modules

Protection Element

Description Function

Ir Long time current setting Adjusts pickup current

tr Long time tripping delay Adjusts time to trip the long time current setting

Isd Short time pickup (multiple of Ir) Adjusts current setting of intermediate vertical lines

tsd Short time tripping delay Adjusts time setting of high current trip (2nd horizontal/ slope from left)

Iinst or Ii Instantaneous pickup Sets high current instantaneous pickup

Ig Earth fault pickup Adjusts earth fault current

tg Earth fault time delay Adjusts earth fault time delay

A.2 Merlin Gerin (or Schneider Electric) STR38ST Trip Unit Settings

Protection Element

Description Function

Io Long time current setting Provides a wider range of pickup current

Ir Long time current setting (on STR38ST or C1251N = Io x Ir)

Adjusts pickup current

Im Short time pickup (multiple of Ir) Adjusts current setting of intermediate vertical lines

tm Short time tripping delay Adjusts time setting of high current trip (2nd horizontal/ slope from left)

Ii Instantaneous pickup (STR38ST has 2 settings only - MAX and OFF)

Sets high current instantaneous pickup

Ih Earth fault pickup Adjusts earth fault current

th Earth fault time delay Adjusts earth fault time delay

A.3 Dorman Smith Trip Units

The trip unit size is not visible unless the MCCB (Moulded Case Circuit Breaker) front panel is removed. Note: That the 600A trip unit is rated at 700A when fitted in the standard (1250A) MCCB and cubicle.

Page 16: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 16 of 26

Appendix B – AMTECH Protection Curves

This appendix contains the AMTECH plots for each of the settings in Section 3. Key:

Top (red) curve – ring main unit (HV AC Series Tripping) 15A tagged TLF fuse.

Middle (green) (green or blue in B10) curve – ACB.

Bottom (blue) (orange in B10) curve – 400A BS88 J type supply fuse.

B.1 Schneider Electric NS1250 – 11kV 750/700kVA Transformer

Page 17: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 17 of 26

B.2 Schneider Electric NS1250 – 11kV 500kVA Transformer

Page 18: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 18 of 26

B.3 Schneider Electric NT16H1/H2 – 11kV 800/750kVA Transformer

Page 19: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 19 of 26

B.4 NT16H1/H2 – 11kV 500kVA Transformer

Page 20: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 20 of 26

B.5 Schneider Electric NW16H1 – 11kV 800/750kVA Transformer

Page 21: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 21 of 26

B.6 Schneider Electric NW16H1 – 6.6kV 500kVA Transformer

Page 22: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 22 of 26

B.7 Schneider Electric NW20H1 – 11kV 1000/800/750kVA Transformer

Page 23: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 23 of 26

B.8 Schneider Electric NW20H1 – 11kV 500kVA Transformer

Page 24: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 24 of 26

B.9 NW20H1 – 6.6kV 1000/800/750/500kVA Transformer

Page 25: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 25 of 26

B.10 NW16H1 and NW20H1 – 11kV 1000/800kVA Transformer

Page 26: EDS 05-2011 Air Circuit Breaker Protection Settings · PDF fileVersion 2.0 Review Date ... 4.10 Dorman Smith 600A and 1250A MCCB ... A.1 Schneider Electric Micrologic Protection Modules

Air Circuit Breaker Protection Settings Document Number: EDS 05-2011

Version: 4.1

Date: 13/05/2015

© UK Power Networks 2016 All rights reserved 26 of 26