Upload
truongthuy
View
247
Download
12
Embed Size (px)
Citation preview
EEEN 4372
Electrical Power Transmission and Distribution
Distribution Transformers
1
Three Phase Transformers
Applications
Construction
Transformer connections
Parallel operation
Three-phase connections
Special problems in transformers
Autotransformers
2
Applications
Power stations: To step-up generator output voltage, from (11kV~25kV)
to transmission voltage (132kV, 275kV, 400kV).
Transmission:
To interconnect lines operating at different voltages (for example 132kV
and 275kV lines).
To interface between transmission network and distribution network (
132kV to 33kV).
Distribution:
To step down system voltages (US 2.4-34.5kV UK 3.3-33kV) to
utilization voltages (US 120-600V, UK 230-415V), located at urban
substations,factories, rural areas (pole mounted), large buildings.
Input transformers for electrical equipment:
arc furnaces,
large power electronic drive systems (>5kW),
large dc power supply units (labs, body scanners, physics rigs..)
rectifier sets for dc traction.3
Construction
4
Three single-phase units One 3-phase unit
Three single phase units are more
flexible,
they can be rated individually to met
unbalanced loads,
in the case of a phase failure: only
one unit need be replaced
but,
heavier,
require more external wiring
A phase failure requires the
replacement of a complete unit,
lighter (15% less weight for the same
rating)
Cheaper
Requires less external wiring
Standard kVA and voltages
5
ANSI standard C57.12.20 gives standard transformer capacity and
voltage ratings for single-phase distribution transformers.
Designation of voltage ratings
6
Types of distribution transformers
(i) dry-type: air cooled and air insulated
(ii) liquid-filled type: oil-filled and inerteen-filled
In overhead distribution systems:
– Conventional transformers : no integral protection
devices provided as part of the transformer
– Completely self-protecting transformers (CSP): from
lightning/surges, overloads and short circuits
– Completely self-protecting for secondary banking
(CSPB): similar to CSPs, but provided with two sets
of circuit breakers. The second set is used to
sectionalize the secondary when it is needed.
7
8
In underground distribution systems:
– Subway transformers
– Low-cost residential transformers
– Network transformers
Transformer polarity
Transformer winding terminals are marked to
show polarity, to indicate the high-voltage
(HV) from the low-voltage (LV) side.
It is an indication of the direction of current
flow through the HV leads with respect to the
direction of current in the LV leads at any
given instant.
9
Transformer polarity
10
•With standard markings, the voltage from
H1 to H2 is always in phase with the
voltage from x1 to x2
•(a) Subtractive polarity : when H1 and x1
terminals are adjacent
•(b) additive polarity: when H1 and x1
terminals are diagonally opposite.
•To test the transformer polarity, two
adjacent terminals of the HV and LV
windings are connected together and a
moderate voltage is applied to the HV
winding, then the voltage between the HV
and LV terminals that are not connected
together is measured: The polarity is
subtractive if the voltage reading is less
than the applied voltage, and is additive if
the voltage reading is greater than the
supply voltage.
Single-phase transformer connections
Single-phase distribution transformers have one HV primary winding
and two LV secondary windings which are rated at 120V: these can be
connected in parallel to supply a two-wire 120V circuit, or in series to
supply a three-wire 120/240V single circuit.
11
12
Single-phase transformer connections (cont’d)
LV windings in series
Single-phase transformer connections (cont’d)
13
Single phase transformer connections for single and two-bushing
transformers to provide customers who require only 240-V single-
phase power. Used for small industrial applications.
Parallel operation of single-phase transformers
Conditions:
– All transformers have the same turns ratio
– All transformers are connected to the same primary
phase
– All transformers have identical frequency ratings
– All transformers have identical voltage ratings
– All transformers have identical tap settings
– The per unit impedance of one transformer is between
0.925 and 1.075 of the other in order to maximize
capability
14
Parallel operation of single-phase transformers
15
Additive
polarity
Additive
polarity
H1 H2
H1 H2 H1 H2
x2 x1x2 x1
x1 x2
Subtractive
polaritySubtractive
polarity
H1 H2
H1 H2 H1 H2
x1 x2x1 x2
x1 x2
Additive
polarity
Subtractive
polarity
H1 H2
H1 H2 H1 H2
x2 x1x1 x2
x1x2
Load sharing of single-phase transformers in parallel
16
The equivalent circuit of the low-voltage side is, with VH the voltage at the HV
side, „a‟ the transformer ratio and Zeq the equivalent transformer impedance:
Zeq1
LoadVH /a
Zeq2
I1
I2
VL
ILVoltage drop through each
transformer must be equal:
1
2
2
1
2211
eq
eq
eqeq
Z
Z
I
I
ZIZI
Using the percent impedances:
rating Voltage : and r,transforme
of rating : , 100)(%2
V
kVASSV
ZZ TT
TT
22
11
2
1
1
2
2
1
Ter transformof ratingkVA :
Ter transformof ratingkVA :
)(%
)(%
T
T
T
T
T
T
S
S
S
S
Z
Z
I
I
22
11
2
1
1
2
2
1
Trmer by transfo suppliedkVA :
Trmer by transfo suppliedkVA :
)(%
)(%
L
L
T
T
T
T
L
L
S
S
S
S
Z
Z
S
S
Example
A 250-kVA transformer with 2.4% impedance
is paralleled with a 500-kVA transformer with
3.1% impedance. Determine the maximum
load that can be carried without overloading
either transformer. Assume that the
maximum allowable transformer loading is
100% of the rating.
17
Three-phase connections
18
D-D connection formed by connecting three single phase transformers to
provide 240-V service at 0o angular displacement
D-D connection : 0o angular displacement
D-D connection: 180o angular displacement
19
D-D connection formed by connecting three single phase transformers to
provide 240-V service at 180o angular displacement
D-D connection
Often used to supply a small single-phase lighting load and three-phase power load simultaneously.
The mid-tap secondary winding of one of the transformers is grounded and connected to the secondary neutral conductor.
The single-phase loads are connected between the phase and neutral conductors
The transformer with the mid-tap carries two thirds of the 120/240-V single-phase load and one third of the 240-V three-phase load.
The other two units each carry one third of both the 120/240-V and 240-V loads.
20 D-D connection to provide 120/208/240 V 3-phase four-wire service
D-D connection (cont’d)
No problem from third-harmonic overvoltage
High-circulating currents will flow unless all three
single-phase transformers are connected on the same
regulating taps and have the same voltage ratios.
The transformer bank rating is decreased unless all
transformers have identical impedance values.
The secondary neutral bushing can be grounded on
only one of the three single-phase transformers.
Therefore to get balanced loading:
1. All transformer have identical voltage ratios.
2. All transformers have identical impedance values.
3. All transformers are connected on identical taps
21
Equivalent circuit of a D-Dconnected transformer bank
22Equivalent circuit referred to the LV side
Equivalent circuit of a D-D connected transformer bank
23
Voltage drop equation for the low-voltage winding:
0
cbacba
bccbcaacabbacbacba
VVV
where
ZIZIZIVVV
We have, for the D-connected secondary:
cbacc
bacbb
acbaa
III
III
III
-
-
-
0 bccbcaacabba ZIZIZIbut
hence:bccbcaacabba ZIZIZI --
cabcab
bcbcaaba
cababcba
ZZZ
ZIZII
ZIZI
-
: ngsubstituti and side, either to and adding
Equivalent circuit of a D-Dconnected transformer bank
24
similarly:
cabcab
cacabbcb
cabcab
ababccac
ZZZ
ZIZII
and
ZZZ
ZIZII
-
-
For equal percent impedance and equal ratios of
percent reactance to percent resistance (X/R ratio) :
caTbcTabT
bcT
b
caT
a
ba
SSS
S
I
S
I
I
,,,
,,
111
-
caTbcTabT
abT
a
bcT
c
ac
SSS
S
I
S
I
I
,,,
,,
111
-
caTbcTabT
caT
c
abT
b
cb
SSS
S
I
S
I
I
,,,
,,
111
-
ST,ab : kVA rating of the single-phase between phases a and b
ST,bc : kVA rating of the single-phase between phases b and c
ST,ca : kVA rating of the single-phase between phases c and a
Example:
25
Three single-phase transformers are connected D-D to provide power for a
three-phase Y-connected 200-kVA load with 0.8 lagging power factor and
80-kVA single-phase light load with a 0.9 lagging power factor.
Assume that the three single-
phase transformers have equal
percent impedance and equal
ratios of per-cent reactance to
percent resistance.
The primary side voltage of the
bank is 7620/13200V and the
secondary side voltage is
240V. Assume that the single-
phase transformer connected
between phases b and c is
rated at 100kVA and the other
two are rated at 75 kVA.
Determine:
1. The line current flowing in each secondary-phase wire
2. The current flowing in the secondary winding of each transformer
3. The load on each transformer in kVA
4. The current flowing in each primary winding of each transformer
5. The line current flowing in each primary-phase wire.
Solution:
26
oooan bc
oan bc
obcbc
bc
Lbc
oc
ob
oa
..-VI
VV,.VI
A.V
SI
A..I
A..I
A..I
811590825
90825
3333240
1080
8635198
721905765
9367481
3
--
-
-
-
by lags hence
,by voltage reference the lags butby lags
A...j.
....
SSS
S
I
S
I
I o
oo
ca,Tbc,Tab,T
ab,T
a
bc,T
c
ac 13311129555607116
75
1
100
1
75
175
9367481
100
8635198
111--
--
-
-
1.
2. Current in the secondary winding of the first transformer:
A...j.
SSS
S
I
S
I
I
:similarly
o
ca,Tbc,Tab,T
bc,T
b
ca,T
a
ba 3565301082834300111
-
A...j.
SSS
S
I
S
I
I
and
o
ca,Tbc,Tab,T
ca,T
c
ab,T
b
cb 72043270951126245111
--
-
27
kVA...IVS
kVA...IVS
kVA...IVS
acacca,L
cbcbbc,L
babaab,L
9930111292400
8864332702400
472653012400
A...
..
a
II
A...
..
a
II
A...
..
a
II
.a
oo
cbCB
oo
baBA
oo
acAC
72045187531
72043270
35597531
3565301
1330747531
13311129
7531240
7620
--
:ratio rtransforme
3. The kVA load on each transformer:
4. Currents in the primary windings :
5. Line Currents in the primary phase wires:
A...j.....III
A...j.....III
A...j.....III
oooACCBC
oooCBBAB
oooBAACA
8186221134114111330747204518
5147617444191772045183559
127086130563559133074
-----
--
-----
The Open D- Open D connection
28
•If one of the transformers becomes damaged or removed from service, the other
two can be operated in the open-delta or “V” connection
•The currents in the other two transformers increase by a ratio of 1.73
•The individual transformers now function at a power factor of 0.866
•One of the transformers delivers a leading load and the other a lagging load.
•To operate the openD-openD bank safely, the load has to be decreased by 57.7%.
%7.57577.03
1
:
10003
3
1000
3
or
D-D
-
-
D-D
S
S
hence
kVAVI
S
kVAVI
S
The Y-Y transformer connection
29
Wye-Wye connection to provide a 120/208-V grounded-
wye 3-phase four-wire multigrounded service
•This system provides a 208-V
three-phase power supply for
three-phase motors and 120-V
single-phase supply for small
single-phase loads.
• Advantage: when a system is
changed from D to a 4-wire Wye to
increase system capacity, existing
transformers can be used.
•Creates series disturbances in
communication circuits in the
vicinity.
•Primary neutral should be solidly
grounded and bonded to the
system neutral to avoid excessive
voltages on the secondary side.
• With an isolated neutral point,
third-harmonic voltages appear at
the transformer neutral.
•Possibility of resonance between
the line capacitance to ground and
the magnetizing impedance of the
transformer.
The Y-D transformer connection
30
Wye-delta connection to provide a 120/208/240-V 3-phase
four-wire secondary service
•Advantage: Transformers with
primary winding of only the voltage
to neutral can be used on a higher
distribution voltage (eg. 2.4-kV
primary single-phase transformers
can be connected in Y on the
primary to a 4.16-kV 3-phase Y-
circuit.
• The transformation ratio of the
bank is 1.73 times the
transformation ratio of the
individual transformers.
•When transformers of different
ratings are used, the maximum
safe bank rating is three times the
rating of the smallest transformers.
•Third-harmonic currents circulate
in the Delta winding, correcting
voltage deformations arising from
isolation of neutral on the primary
side.
The Y-D transformer connection
31
Wye-delta connection to provide a 240-V three-
phase three-wire secondary service at 210o angular
displacement
When the primary-side neutral of the
transformer bank is not isolated but
connected to the primary circuit neutral,
The Y-D transformer bank may burn-out
due to the following reasons:
• The transformer bank may act as a
grounding transformer bank for
unbalanced primary conditions and may
supply fault current to any fault on the
circuit to which it is connected, reducing
its own capacity for connected load.
•The transformer bank may be
overloaded if one of the protective fuses
opens on a line-to-ground fault, leaving
the bank with only the capacity of an
open-Y open-D bank.
•The transformer bank causes
circulating currents in the D in an
attempt to balance any unbalanced load
connected to the primary line.
The D-Y transformer connection
32
Delta-wye connection to provide a 120/208-V three-
phase four-wire grounde-Y service at 30o angular
displacement
The D-Y connection has many uses:
•It eliminates unbalanced primary currents occurring with other connections.
• Single-phase loads can be balanced on three-phases in each bank, and banks may be
paralleled.
•No operation if one of the transformers becomes damaged or is removed from service.
•The line voltages on the secondaries of Y-D and D-Y connections are 30o lagging behind
the line voltages on the primaries.
•The D-Y step-up and Y-D step down connections are suitable for high-voltage transmission
systems. They are economical and provide a stable neutral point for grounding.
Delta-wye connection to provide a 120/208-V three-
phase four-wire grounde-Y service at 210o angular
displacement
The auto-transformer
33
Construction:
•Use a single, tapped winding in each phase
rather than two separate windings
•A common flux passes through all the turns
1
2
1
21
1
21
1
444
444
n
n
n
nnk
V
V
IZIR
knf.
)n(nf.
E
E
x
H
tt
m
m
x
H
:is ratio rtransforme the drops, and neglecting
11
2 - kn
n
V
V
C
S
: is ratio voltage- windingThe
1--
kI
II
I
I
I
I
H
Hx
H
C
S
C
: ratio Current
IC: current in the common winding
IS: current in the series winding
xxHH IVIV rating VA sCircuit'
CCSS IVIV rating VA sWinding'
1-
-
-
k
k
V/)VV(
V/V
I)VV(
IV
IV
IV
xxH
xH
HxH
HH
SS
HH
rtransforme winding-two ascapacirty
ormerautotransf ascapacity
Designation of connections by vector group symbols (British Standard)
Y, D, Z for the star, delta and zigzag high-
voltage winding
y, d, z for the star, delta and zigzag low-
voltage and intermediate windings,
YN, ZN if a neutral connection is made on the
h.v winding,
yn, zn if a neutral connection is made on the
l.v winding.
34
Vector Group
In the British Standard, transformers are
designated according to the phase
displacement between the primary and
secondary winding voltages.
The clock-hour figure is used to express the
phase displacement.
35
Use of vector group symbols
• Use of the clock-hour
figure: The phase
displacement is expressed
as the hour number, shown
on a clock whose large hand
is pointing at 12 and
coincides with vector of the
voltage between the neutral
point and the HV line
terminal, and whose small
hand coincides with the
vector of the voltage
between the neutral and the
corresponding LV or
intermediate terminal.
•The vector relating to the
HV winding is taken as the
vector of origin.
HV transformer
37
38
39