EET 3390

COURSE OVERVIEW

Page 2: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

The Power System

The power network consists of several stages:1. Power must be generated 2. Transformation (voltage must be stepped up for transmission )3. Transmitting power4. Transformation (voltage must be stepped down before distribution)5. Distribution of the power. 2

Page 3: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

On-line diagram of the power system

Standard voltage classes and typical operating voltages for the U.S. Power System:

Low voltage (LV) Consumer

120/240,208,240, 277/480,600 (in volts)

Medium voltage (MV) Distribution

2.4, 4.16, 4.8, 6.9, 12.47,13.2, 13.8, 23.0, 24.94, 34.5, 46.0, 69.0 (in kV)

High voltage (HV) Subtransmission

115, 138, 161, 230 (in kV)

Extra high voltage (EHV) Transmission

345, 500, 765 (in kV)

3

Page 4: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

AC power versus DC power

Case 1: Case 2:

DC system:

- Power delivered to theload does not fluctuate.

- If the transmission lineis long power is lost in the line.

4

Page 5: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

AC system:

Power is the product of voltage and current, increasing the voltage woulddecrease the current for a given amount of power. The line loss and voltagedrop would both decrease as well. Difficult to change the voltage in a DC system.

AC systems: alternate the current and voltage

Power has an average value but pulsates around the average value at twice the system frequency. We can use transformer to step up the voltage for the transmission. DC system delivers constant power but to change the voltage is difficult therefore linelosses are more significant.

Advantages of AC systems:Voltage can be changed using transformers.AC generators are cheaper to build and maintain than DC generatorsThe ability to transmit over longer distances with lower losses by using transformersPolyphase AC system can deliver constant power (discussed later)

5

Page 6: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Phasors

Convenient way to represent voltages and currents using phasor form (work in phasor domain)

In its simplest form, a phasor can be thought as a complex number that has magnitude and phase of a sinusoidal function and can be represented partially as a vector in the complex plane.

IMPORTANT: The magnitude of a phasor will always be RMS value of the sinusoid it is representing.

Voltage phasor magnitude

Current phasor magnitude; current is lagging the voltage by 30 degrees

6

Page 7: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Impedance in AC Circuits

Impedance of the inductor:

NOTE: 1. There is a phase shift between the voltage and the

current. The current is lagging the voltage by 90 degrees for the inductor.2. The RMS of the current is the RMS of the voltage

divided by (wL)

Use Ohm’s low in the phasor domain for the inductor by defining the inductive reactance

Current in the inductor:

Impedance of the inductor:

7

Page 8: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Impedance of the capacitor:

NOTE: 1. The current is a negative sine wave, which leads the voltage (cosine wave) by 90 degrees.2. The RMS of the current is related to the RMS of the voltage by (wC).

Capacitance reactance:

Impedance:

Current in the capacitor:

The current in the capacitor will lead the voltage by 90 degrees.example

8

Page 9: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Power in Single-Phase AC Circuits

Real Power (Active Power) energy consumed by the load that is converted to heat and is not be returnedto its initial stage.Real power used by the resistor:

Reactive power (Inductor)Instantaneous current through the inductor variessinusoidally.Inductor stores energy as a function of the current, thus magnetic field varies with time.As current increases the inductor stores more energyin its magnetic field and the power flows from the source to the inductor.As current decreases the inductor releases energy backto the source.The inductor does not use any power on average, there is energy moving back and forth between the source and the Inductor. This is called REACTIVE POWER.

Reactive power (Capacitor)Voltage across the capacitor varies sinusoidally.Capacitor stores energy as a function of the voltage, thus capacitor’s electric field varies with time.Capacitor draws energy from the source as it charges, and returns energy as it discharges.The voltage across the capacitor and the current through the inductor are 90 degrees out of phase, thus when inductor ischarging the capacitor discharges.

9example

Page 10: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Complex Power

Real power

Reactive power

Magnitude of the complex (apparent )power

Relationship between the real and apparentpower.

Power factorAngle theta is the angle of the current with respect to the voltage.If the current lags the voltage (inductive load)then theta is negative.If the current leads the voltage (capacitive load)then theta is positive.Power factor is always positive and less than 1.

Relationship between the reactive and apparentpower.

10

example

Page 11: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Three-Phase WYE Configuration

11

Wye: Consists of three load components connected with a common point called neutral.

Page 12: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Three-Phase DELTA Configuration

Delta:Consists of three load components connected end-to-end way and has no neutral point. Phases are connected in a triangle.

12

Page 13: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Balanced and unbalanced 3-Phase systems

A balanced system is one in which the line and phase currents and voltages in all three phasesare equal in magnitude and separated by 120 degrees, and the impedances in all three phasesare identical.An unbalanced system is one in which any of the foregoing requirements are not met.

Power calculation in balanced 3-phase systems:

WYE system Delta system

For a single-phase system, the apparent power is the product of the phase voltage and phase current

For a balanced 3-phase system , the total 3-phase apparent power is three times the power consumed by one phase

13examples

Page 14: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

The Per Unit Concept

A convenient method of calculating electrical power quantities.

A shorthand method of solving power system problems has been developed to

eliminate many of the manipulations required in systems with more than one voltage.

14

examples

Page 15: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

The Per Unit Concept (cont.)

15

Page 16: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Major Distribution Layout Classifications

1. A Radial subtransmission and distribution.

The distribution lines extend from

the substation to the last load with

service drops to customers along

the way.

The major advantages of the radial

layout are that it is simpler and more

economical to install than other types

of layouts.

The major disadvantage is that any

problem usually leaves a number of

customers out of service until the

problem is solved.

A modified radial subtransmission

layout is more often used in which

two parallel radial subtransmission

line have a provision for switching

the load to the good line in the event

of a failure.

16

Page 17: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

2. The Loop subtransmission and distribution

The loop connection is more expensive

than the radial because it requires more

equipment, but any point the line has

service from two directions.

If one is out, the customer can be fed

from the other direction. Switches are

placed periodically around the loop so

the malfunctioning section can be

repaired without removing much of the

line from service.

The loop layout is very reliable but

expensive.

17

Page 18: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

3. A combination of radial and loop

Is often used to provide the most

reliable service to critical customers,

such as business and industrial, by a

loop, and reasonably economical

service to residential neighborhoods.

Radial part of the system is arranged

so that only a few residential

customers will be out of service at

one time for any fault condition.

18

Page 19: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

4. Networks

Networks are designed to provide very reliable service to areas with dense loads such as

downtown and suburban business districts containing many multi buildings.

The network consists of underground secondary lines connected at corners with transformers

feeding the network every one to two blocks.

The network equipment is contained in underground vaults with access through main holes

in streets and alleys. Although networks can be very large, network sections are seldom

larger than four square blocks.

Networks are reliable but expensive.

19

Page 20: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Overhead and Underground

Overhead distribution is used because the low initial

cost and good reliability.

The equipment for overhead distribution costs less

than the equipment required for underground

distribution, and it is less costly to maintain.

Overhead distribution lines are more subject to

storm, lightning, and wind damage than underground

lines, but they are more easily and cheaply repaired

when damage occurs.

Underground lines are not as vulnerable to weather

conditions, and they are out of sight so the

neighborhood sky lines is less cluttered.

Underground distribution lines require waterproof

Insulation of high quality and cost.

Underground lines are higher in electrical loss than

overhead lines. The price of equipment for

underground distribution decreasing as more

underground service is installed.

20

Page 21: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

1/1 Transformer

When the primary winding and the secondary winding have the same amount of turns there is no change voltage, the ratio is 1/1 unity.

Step-Down Transformer

If there are fewer turns in the secondary winding than in the primary winding, the secondary voltage will be lower than the primary.

Step Up Transformers

If there are fewer turns in the primary winding than in the secondary winding, the secondary voltage will be higher than the secondary circuit.

21

Page 22: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Transformer classification by cooling:

1. Dry transformers.

2. Oil immersed transformers

Dry types are air cooled, primarily by convection.

Oil immersed transformers in which the windings and core are immersed in oil,

are both cooIed and helped in insulation by the oil.

Almost all utility power and distribution transformers are oil.

Dry types are used primarily where minimum cost is a factor and the transformer is

supplied by the customer such as in apartment house and a building distribution systems.

Because the cooling of dry transformers is by convection they are very intolerant of overloads.

Dry types must be in an enclosure for safety.

22

Page 23: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Voltage and Current

For the ideal transformer, all the flux is confined to theiron core and thus links the primary and secondary.

Turns ratio

For step-down transformer, the primary side has moreturns than secondary, therefore a >1;

For step-up transformer, the primary side has fewerturns than secondary, therefore a <1;

Because the losses are zero in the ideal transformer, the apparent power in and out of the transformer must be the same:

Ratio of the currents is inverse of the voltage ratio or the inverse of the turns ratio.It makes sense: if we raise the voltage level to a load with a step-up transformer , then the secondary current drawn by the load would have to be less than the primary current, science the apparent power is constant

23

Page 24: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Impedance

Due to the fact that the transformer changes the voltage and current levels in opposite directions, it also changes the apparent impedance as seen from the two sides of the transformer.

Ohm’s law applied at the load:

Recollect:

The Reflected (referred) impedance(the impedance looking into

the primary side of the transformer)

When we move an impedance from the secondary to the primary side of the transformerwe multiply by the turns ratio squared.When moving the impedance from the primary to the secondary, we divide it by the turns ratio squared.

This process is called referring the impedance to the side we move it, and allows us to use transformers to match impedances between a source and a load

24

Page 25: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Exciting Current

In real live we deal with real transformers which require current in the primary winding to establish the flux in the core. The current that establishes the flux is called the exiting current. Magnitude of the exciting current is usually about 1%-5% of the rated current of the primary for power transformers but may be much higher for small transformers.

According to Faraday’s law if we apply a sinusoidal voltage to the transformer, then the flux will also be sinusoidal, but due to the non-linearity of B-H curve for the iron curve, the current will not be sinusoidal even if the flux is sinusoidal and the current will be

out of phase with flux.

25

Page 26: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Equivalent T-circuit

Third order circuit. It takes third order differential equation to solve it.

26

Page 27: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

We can refer the impedances of the secondary to the primary side (or vise versa) yielding the equivalent circuits

All resistances and reactances have been referred to the primary side

All resistances and reactances have been referred to the secondary side

27

Page 28: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Series Equivalent Circuit

Note: In large-scale system studies, even cantilever model becomes too complex, so one final simplification is made.

We completely neglect the magnetizing branch of the transformer model. Only combined winding resistance and leakage reactance are included, resulting in the first order model (takes first order differential equation to solve it).

Series equivalent circuit.

Science there are no shunt elements, the primary and secondary currents are equal to each other.

28

Page 29: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Determining Circuit ParametersFor developed model to be useful, there must be a way to determine the values of the model parameters.We use two test to determine this parameters:

Short-circuit test One side of the transformer is shorted, and voltage is applied on the other side until rated current flows in the winding. The applied voltage, winding current, and input power are measured.

Technique: the low-voltage side of the transformer is shorted and voltage is applied to the high-voltage side, because it only takes about 4%-7% of rated voltage to cause rated current to flow in the winding.The measurements are used to calculate value of Req and jXeq.

Input impedance to the transformer is the primary winding in series with the parallel combination of the secondary winding and the exciting branch:

The core branch elements are much larger that the winding impedance:

29

Page 30: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

To conduct the short-circuit test: - Measure the voltage applied to the transformer high side Vsc

- Measure the short-circuit current in the high-side winding Isc

- Measure the power into the transformer Psc.- Having these parameters we calculate the magnitude of input impedance:

Once we have values for the equivalent winding resistance and reactance we can apportion them to the two sides by assuming the windings have equal resistance and reactance when referred to the same side:

30

Page 31: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Open-circuit test

High-voltage side is opened and rated voltage is applied to the low-voltage side (primary side).

The low-voltage side is used to avoid high-voltage measurements.

With no load current, only exciting current Io flows and because the impedance of the primary side is small, the voltage across the magnetizing branch is approximately equal to the applied voltage.

Procedure: - Measure the voltage applied to the transformer low side Voc, the open-circuit current in the low-side winding Ioc and the power into the transformer during open circuit test Poc.

- Calculate resistance and reactance.

31

Page 32: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Now we have the voltage applied to and the power dissipated, so we can calculate:

Because the magnetizing reactance is in parallel with we first need to find the reactive power to find reactance:

The input impedance during open-circuit test is the primary winding in series with the exciting branch:

32

Page 33: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Transformer Efficiency

Efficiency is defined as:

Input is the output plus losses:

LOSSES

Copper losses (the energy dissipated in the resistance of the windings )

Core losses (hysteresis and eddy current losses in ferromagnetic core of the transformer)

33

Page 34: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Losses in the transformer

Winding resistance

Current flowing through the windings causes resistive heating of the conductors.

Eddy currents

Ferromagnetic materials are also good conductors, and a solid core made from

such a material also constitutes a single short-circuited turn throughout its entire length.

Induced eddy currents therefore circulate within the core in a plane normal to the flux,

and are responsible for resistive heating of the core material.

Hysteresis losses

Each time the magnetic field is reversed, a small amount of energy is lost to hysteresis

within the magnetic core, the amount being dependant on the particular core material.

Mechanical losses

The alternating magnetic field causes fluctuating electromagnetic forces between the

primary and secondary windings, that induce vibrations.

34

Page 35: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Stray losses

Not all the magnetic field produced by the primary is intercepted by the secondary.

A portion of the leakage flux may induce eddy currents within nearby conductive

objects, such as the transformer's support structure, and be converted to heat.

Cooling system

Large power transformers may be equipped with cooling fans, oil pumps or water-

cooled heat exchangers designed to remove heat.

The power used to operate the cooling system is typically considered part of the losses

of the transformer.

35

Page 36: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Voltage Regulation

The transformer windings have impedance so there will be a voltage drop across them that changes with current. The secondary voltage will vary as the load changes.

Voltage regulation is a measure of the change in secondary voltage from no-load to full-load and is usually expressed as a percentage of the full-load voltage.

If there were no load on the transformer, the current would be zero and the referred secondary voltage would be equal to the primary voltage.

The no-load voltage (referred to the primary) of the transformer is the primary voltage.

As the load increases to full load, current flows in the windings of the transformer and there is a voltage drop across the transformer, and the referred value of the secondary voltage is no longer equal to the primary voltage.

Voltage regulation:

36

Page 37: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Methods for Voltage Regulation

Capacitors for voltage regulation

Switch shunt capacitors used across the line to increase the voltage by reducing the inductive VARs drawn

as in power factor correction.

Shunt capacitors are only used for lagging load power factors and their main goal is to correct for load

power factor, and their only current is from the VARs.

Switched capacitor banks are expansive because they must have sensing equipment to monitor the line

voltage and control equipment activate the proper switching.

All capacitor banks require protection: fuses, circuit breakers etc.

Series capacitors are connected in series with the line and carry full line current.

The capacitive reactance of the series capacitance is used to cancel the inductive reactance of the line to

reduce the voltage drop along the line.

37

Page 38: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Series capacitors operation

Figure 4.35 page 143

“a”: line equivalent circuit

“b”: phasor diagram with lagging

power factor load

“c”: the capacitive reactance cancels

a portion of the line inductive

reactance causing the receiving

voltage to rise

Series capacitors can be switched or

fixed and are protected the same way

as are shunt capacitors

38

Page 39: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Three-phase transformer connections

There are four major three-phase transformer connections :

1. WYE-WYE2. Delta-Delta3. WYE-Delta4. Delta-WYE

Three-phase transformers are less expensive than 3-single-phase transformers because less total core material is needed for the three-phase transformer and the packaging cost is reduced.

Additionally they take up less space, are lighter, require less on site external wiring

for installation, and more efficient than three single-phase transformers.

Single phase transformer has one voltage ratio which agrees with the turns ratio.

For 3-phase transformer:

1. Bank Ratio = BR = the ratio of line-to-line voltages.2. Phase Ratio = PR = the ratio of the voltages in the coils of the transformer and thus

agrees with the turns ratio.

39

Page 40: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

The WYE-WYE connection has significant third harmonic content on the secondary lines (unless the neutral point is grounded)

There is no phase shift between the primary and secondary of a Y- Y connected transformer.

The Delta-Delta connection has no harmonic problem and no phase shift from primary to secondary. The only disadvantage with respect to a WYE connection is that the delta insulation class must be for the line to line instead of line to neutral voltage.

40

Page 41: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Figure 4.16 page 120

There is a 30 degrees phase shift in both connections. United States industry convention is to connect the secondary so it lags the high voltage primary by 30 degrees.

When possible the Y is connected to the high voltage side because the insulation requirements are lower (recall that Y phase voltage is 1/sqrt(3) that of the line voltage).

The Y may be necessary on the low voltage side because of the distribution system requirements as in 480/277 V and 208/120 V installations.

41

Page 42: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Transformer protection

Picture 4.18 page 123

Transformers, especially power transformers, are expensive. The transformer must be protected from

overcurrent due to faults on its secondary circuit, and from over voltage, which is usually caused by lightning.

The protective devices:

Lightning protection is provided by lightning arresters. Zinc oxide lightning arresters are the most popular now.

The voltage at which the lightning arresters begins conducting, absorbing power, and preventing further voltage

rise on the line is set at a voltage below the maximum insulating voltage of the transformer and above the

maximum operating voltage of the transformer. Lightning arresters are used on both the primary and secondary

side of the power transformers because lightning can strike on either side.

Overcurrent protection is provided by circuit breakers and their associated protective relays, and fuses.

A fuse opens on overcurrent. Circuit breakers open electrical contacts when they receive a trip signal from one

of their associated relays The opening is done by driving the contacts apart with powerful springs. Circuit

breakers are used on the secondary side of the transformer with a fuse back up on the primary side. 42

Page 43: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Circuit Breakers

Circuit breakers for electrical power distribution include both medium (between 600 V

and 34.5 kV) and high voltage (above 34.5 kV), high current devices that must

automatically disconnect faulted equipment to protect people, prevent damage to

upstream equipment, and minimize damage to downstream equipment in two to

five cycles.

The circuit breaker should not damage itself when it operates.

Breakers are classified by:

1) Voltage

2) Continuous current

3) Interrupting capacity (maximum fault current the breaker can interrupt without

becoming dangerous themselves), and methods of extinguishing the arc.

Example

43

Page 44: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

The Arc

When current carrying contacts open, the initial electric field between the just parted

contacts is very high.

The high electric field causes any gas between the contacts to ionize and support

current flow through it, or arc.

The higher the voltage that the contacts are breaking the more severe the arcing.

The arc must be extinguished to interrupt the current.

Many methods are used to extinguish an arc.

They use one or both of the following two principles:

1. To lengthen the arc until it is long and thin. This causes the arc resistance

to rise, thus the arc current to drop, the arc temperature to decrease, and

ultimately results in insufficient energy in the arc to keep it ionized.

2. To open the arc in a medium that absorbs energy from the arc causing it to

cool and quench.

Air, oil, and insulating gas are normally used as the medium.

44

Page 45: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Air Circuit Breakers

Air circuit breakers use air as the arc interrupting medium. Because air at atmospheric pressure ionizes easily

some auxiliary equipment must be used to break the arc except for the very lowest voltage and capacity

breakers.

Figure5.4 page 162

Convection causes an arc, which is hot, to rise

if the contacts are properly oriented. As the rising

arc stretches its resistance increases, its current

drops, and its increased surface area is exposed

to cooler air, causing its temperature to drop

until the arc is finally extinguished. The longer

an arc can be drawn out the easier it is to

extinguish.

Arc tips break after the main contacts break

Arc horns work on the same principle except

convection drives the arc up the spreading

horns causing the arc to leave the load current

carrying contacts and stretch.

Interrupting fins placed in the path of the rising

arc will stretch the arc farther, cool it more, and

aid in extinguishing the arc.

Large low voltage breakers will have interrupting

fins.

45

Page 46: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Figure 5.5 page 163

Magnetic blowout refers to the use of a transverse magnetic field near the contacts to stretch

and drive the arc into the interrupting fins.

The magnetic field interacts with the ions of the arc to provide the driving force.

The magnetic field can come from a permanent magnet in small breakers, but is provided by

a properly positioned coil through which the contact current flows in larger low voltage

breakers.

Circuit breakers with magnetic blowout and interrupting fins can even be used for lower

medium voltages. 46

Page 47: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Air Blast Circuit Breakers

Figure 5.6

And figure 5.7

Page 164

Cross air blast circuit breakers are special purpose

medium voltage circuit breakers used where

noise is an important factor.

A blast of compressed air (to 800 psi) is blown

across the circuit breaker contacts as the contacts

open.

The blast of high pressure air blows the arc into

the interrupting fins, stretches the arc, and cools it.

Axial air blast circuit breakers blow high pressure

air along the axis of the contacts to stretch and

cool the arc.

The air is blown from a port next to the stationary

contact toward the moving contact.

Axial air blast breakers are usually high voltage

breakers. They can be built to interrupt currents

as high as 63 kA at 800 kV.

47

Page 48: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Vacuum circuit break contacts are enclosed in a container with a high vacuum.

No significant arcing can occur because there is no air between the contacts to ionize

Vacuum Circuit Breakers

Oil Circuit Breakers

Oil circuit breakers use oil as the arc interrupting medium.

Oil has a dielectric strength far in excess of air. When contacts open in oil the arc

causes the oil to disassociate which absorbs arc energy.

Sulphur Hexaflouride Circuit Breakers

Sulphur Hexaflouride gas is a popular interrupting medium for high voltage and

extremely big voltage (EHV, above 345 kV) applications. Its voltage withstand

rating is about three times that of air and it is extremely electronegative. That

means its atoms bind for a considerable time to free electrons, thus becoming

negative ions. When free electrons are removed from the arc it is difficult to sustain

because no free electrons are available to accelerate and ionize atoms by collision.

48

Page 49: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

RECLOSERS

Most faults (80-95%) on distribution and transmission lines are temporary, lasting from a few cycles to a few

seconds.

They are caused by such things as tree limbs falling or blowing across the lines and are removed when the

limb burns off or is blown out of the line. Reclosers allow temporary faults to clear and then restore service

quickly, but disconnect a permanent fault.

Reclosers are essentially special purpose, light duty circuit breakers. They can interrupt overloads but not

severe faults. Reclosers sense an overcurrent, open, then after a preprogrammed time, reclose. They can

be programmed to sense an overcurrent, open, and reclose several times (up to five times is typical) and

after the preset number of operations remain open.

FIGURE 5.17 page 177

Two types of reclosures are currently manufactured. In one type the times are controlled by pistons in hydraulic

cylinders, and in the other by electronic circuitry.

Electronic reclosers are more flexible, accurate, and easily tested than hydraulic closers, but are also more

expensive so electronic controls are used primarily on heavy duty three-phase reclosers. 49

Page 50: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

SECTIONALIZERS

A sectionalizer is a device that is used to automatically isolate faulted line segments

from a distribution system.

1. It senses any current above its actuating current followed by a line de-energization

by a recloser.

2. It counts the number of overcurrent allowed by line de-energization sequences

and after a preset number of times it opens and locks out.

The sectionalizer must be manually reset after lock out. If normal line conditions

continue for a preset length of time after an overcurrent, de-energization sequence

below the preset lock out number, the sectionaIizer will reset itself to zero count.

The delay before reset is usually set between 30 and 90 seconds:

Two types of sectionalizers are available:

1. Smaller ones are hydraulically operated in a manner similar to reclosers

2. Higher capacity are electronically operated.

50

Page 51: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

FUSES

Fuses are one-time devices that must be replaced each time they open a fault. They use a metallic element

that melts when an overload current passes through it. The melted element separates breaking the circuit.

1. Low voltage and current limiting fuses

Low voltage fuses use zinc, copper, or silver as

the metallic element, while medium and high

voltage fuses typically use tin, cadmium, or silver.

Current limiting fuses are fuses that limit the peak

fault current to less than it would be without a

current limiting fuse, and break the circuit in less

than one-half cycle.

A current limiting fuse cartridge is filled with sand.

The sand melts but does not disassociate so it

absorbs heat energy cooling the arc, plus the

sand filling leaves little air to support an arc.

Current limiting is valuable because both the

heating and mechanical damage caused by a

fault is proportional to the square of the current.

51

Page 52: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

The job of the lightning arresters is to clip the induced voltage transient caused by a lightning

strike at a level below the BIL, but above the normal operating voltage, of the protected

equipment.

The lightning arrester should be an insulator at any , below the protected voltage, and a good

conductor at any voltage above to pass the energy of the strike to ground.

Lightning Arresters

Shield wires for lightning protection of lines

Shield, or static wires, are conductors strung above the load carrying conductors on

transmission and distribution towers and poles to protect the load carrying conductors

from lightning strikes.

The shield wires provide a place for lightning strokes to terminate instead of the power

carrying conductors, thereby protecting the power conductors.

Almost all lines 34.5 kV and above use shield wires.

52

Page 53: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Shield wires provide a 30°

zone of protection on either

side of a vertical line drawn

from the ground to the wire.

Towers in which the power

carrying conductors do not

fit within the zone of

protection of a single shield

wire use two.

Equipment in station yards

can be protected by placing

it within the 30° protection

zone of a tall mast with a

conductor running from the

tip to ground.

Shield wires must be

grounded to provide a

path for the lightning

current.

Figure 5.35 page 198

53

Page 54: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

PROTECTIVE RELAVS

A relay is an electromechanical- or microprocessor-controlled electronic system .

That senses an abnormal or fault condition, such as an overcurrent, under or over

voltage, or low frequency, and sends a trip signal to a circuit breaker.

They are used to protect generators, transformers, motors, and lines.

Monitoring relays verify conditions in the power system or power system protection system

and send an alarm when the conditions are abnormal.

Monitoring relays often are used in conjunction with protective relays.

Programming relays sequence events or detect sequences of events. They are used to control

and monitor synchronization and reclosing sequences.

Regulatory relays are used to determine if a parameter, such as line voltage, is between

programmed limits and send a control signal to force the parameter to return to within the limits

Auxiliary relays provide miscellaneous functions within other relaying systems. Timers are

an example of an auxiliary relay function.

Relays must operate reliably, and quickly, be economical, and selective, operatmg only on

the desired input

Example

54

Page 55: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Microcomputer Controlled Relays

The use of microprocessors in microcomputer relay systems has allowed relay systems to perform several

relaying functions with a single central relaying package in a very economical manner. The multifunction

capability of microprocessor controlled relay systems has resulted in a drop in the cost per function of such

relays when compared to electromechanical relays.

Figure 5.36 page 199

The current and potential transformers

provide current and voltage information

to the relay from which the relay

microcomputer calculates any

additional parameters needed, such as

impedance, VAR and power quantity and

flow direction, trends over a fixed time,

and running averages of quantities.

The relay can also make use of other

parameters, such as temperature and

vibration sensor outputs, to monitor

more conditions than electromechanical

relays are able to monitor.

A single microcomputer-controlled relay

can monitor and respond to abnormal

conditions while gathering data for use in

control and trend analysis.

The relay will react to out of limit parameters by sending a trip signal to a circuit breaker and an

alarm signal to a central monitoring point via a telecommunication system.

55

Page 56: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

DISCONNECT SWITCHES

Disconnect switches are designed to open and close a circuit at high voltages. The switches

must have a large gap when open. An air gap of about 11 feet is required at 230 kV.

Disconnect switches cannot open a fault.

Non-load Break Disconnect Switch:

High and medium voltage disconnect switches are designed to isolate a section of a circuit

after the protective device has de-energized the circuit.

Disconnect switches can be operated by motors, as most high voltage switches are, by an

insulated lever connected to a actuating arm that moves the switch blade.

Load Break Switches:

Load break disconnect switches can interrupt normal load currents, but not large fault currents.

The wall switch is the most common load break switch.

Most load break switches use motors to open and close the switch blades but the interrupters

are actuated by strong spring pressure.

56

Page 57: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Substations generally have:1. Switching equipment2. Protection equipment3. Control equipment 4. One or more transformers

In a large substation: Circuit breakers are used to interrupt anyshort-circuits or overload currents that mayoccur on the network.

In smaller distribution stations: Recloser circuit breakers or fuses may be usedfor protection of distribution circuits.

Other devices such as capacitors and voltage regulators may also be located at asubstation.

Substations may be on the surface in fenced enclosures, underground, or located in special-purpose buildings.

Page 58: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Distribution substation

A distribution substation transfers power from the transmission system to the distribution system of an area.

The input for a distribution substation is typically at least two transmission or subtransmission lines.

Distribution voltages are typically medium voltage, between 2.4 and 33 kV depending on the size of the area served and the practices of the local utility.

Besides changing the voltage, the job of the distribution substation is to isolate faults in either the transmission or distribution systems.

Distribution substations may also be the points of voltage regulation, although on long distribution circuits (several km/miles), voltage regulation equipment may also be installed along the line.

Complicated distribution substations can be found in the downtown areas of large cities, with high-voltage switching, and switching and backup systems on the low-voltage side.

Page 59: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Collector substation

In distributed generation projects such as a wind farm, a collector substation may be required, which is similar to a distribution substation although power flows in the opposite direction, from many wind turbines up into the transmission grid.

For economy of construction the collector system operates around 35 kV, and the collector substation steps up voltage to a transmission voltage for the grid.

The collector substation can also provide power factor correction if it is needed, metering and control of the wind farm.

Collector substations also exist where multiple thermal or hydroelectric power plants of comparable output power are in proximity.

Page 60: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Switching substation

A switching substation is a substation which does not contain transformers and operates only at a single voltage level.

Switching substations are sometimes used as collector and distribution stations.

Sometimes they are used for switching the current to back-up lines or for paralellizing circuits in case of failure.

Page 61: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Design

The main considerations taking into account during the design process are:

1. Reliability

2. Cost (sufficient reliability without excessive cost)

3. Expansion of the station, if required.

Selection of the location of a substation must consider many factors:

1. Sufficient land area

2. Necessary clearances for electrical safety

3. Access to maintain large apparatus such as transformers.

4. The site must have room for expansion due to load growth or planned

transmission additions.

5. Environmental effects( drainage, noise and road traffic effects.

6. Grounding must be taking into account to protect passers-by during a short-

circuit in the transmission system

7. The substation site must be reasonably central to the distribution area to be

served.

Page 62: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Distribution Substation Protection Needs

Above a minimum protection needed to avoid injury to people and damage to equipment,

the level of protection of a substation is determined by how critical the loss of power is to the

load.

The loss of electrical power to a hospital is very serious while the loss of power to a residence

is inconvenient. In the event of a fault the hospital electricity must be restored in the shortest

amount of time possible while the residence can be without electricity several hours without serious

consequences.

Equipping a substation with automatic

switching to restore power when it is lost

and to assure the least possible damage

and repair time after a fault is expensive.

A small substation at the end of a radial subtransmission line that might be used to serve a small group of

residences. It consists of two dead end poles to terminate the lines, two manual non-load break switches,

and primary fusing.

Page 63: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

DISTRIBUTION SUBSTATION CONSTRUCTION METHODS

Four basic methods exist for substation construction:

1. Wood

2. Steel lattice

3. Steel low profile

4. Unit.

Wood pole substations are inexpensive, and can easily use wire bus structures. Wood is suitable

only for relatively small, simple substations because of the difficulty of building complex bus and

switch gear support structures from wood.

Lattice steel provides structures of low weight and high strength. Complex, lattice steel is

reasonably economical and is the preferred material for substation construction whenever

possible.

Solid steel low profile substations are superior to lattice or wood constructed substations.

However, low profile construction is more expensive than either wood or lattice steel, and requires

more land because multilevel bus structures cannot be used.

The unit substation is a relatively recent development. A unit substation is factory built and tested,

then shipped in modules that are bolted together at the site.

Unit substations usually contain high and low voltage disconnect switches, one or two three-phase

transformers, low voltage breakers, high voltage fusing, bus work, and relays.

Page 64: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

DISTRIBUTION SUBSTATION LAYOUT

1. Single source, single feeder substation

The one-line diagram of a single-source, single-feeder

substation with the minimum equipment used.

A bypass switch is provided so service can continue during

circuit breaker maintenance.

The probability of a fault during circuit breaker maintenance

is small, but still there as a result the transformer is protected

by a primary fuse to back up the breaker, and provide

some protection for internal transformer faults.

The minimum relaying is overcurrent on the secondary side

of the transformer.

The switches can be manually or motor operated.

Page 65: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

2. Single bus substation

This is the one line of a single bus substation

fed by a single radial subtransaission line.

Each feeder must has its own overcurrent

protection.

The primary switch must be able to break the

transformer excitation current.

The transformer may have differential relaying

that trips all of the feeder breakers in the event of

a fault.

Each distribution voltage the substation supplies

must have its own bus.

The possibility of a subtransmission circuit fault is

much higher than a transformer fault. Two sources

allow service to be restored more quickly upon a

subtransmission circuit fault.

Page 66: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

2. Single bus substation

This is the one line of a double throw switch on the primary side which allows the transfer to be

made quickly from one subtransmission circuit to another.

The switch is interlocked with the transformer breaker so it cannot be opened under load.

The switch can be replaced by two manual high voltage breakers that can break the load, and

expected fault current.

The transformer secondary breaker makes possible very effective differential bus protection to

detect faults internal to the bus. The bus relays then trip all of the circuit breakers connected to the

bus upon a bus fault.

Page 67: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

3. Two Transformer Distribution Substations

More critical loads implement a two transformer distribution

substation allowing to significantly decrease the out of service time.

Normally the transformers are rated at 75% capacity when self

cooled and equipped with automatic air cooling that is used when

one transformer must handle the entire substation capacity.

The tie switch between the two transformer connections to the bus

which is in open state when both transformers are in use to prevent

the transformer secondaries from operating in parallel.

Momentary parallel operation during switching is often permissible

but must be avoided for the extended operation time due to the high

secondary currents.

The primary side switching is arranged so that either or both

transformers can be fed by either subtransmission line.

Page 68: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

4. Automatic Switching (Throw-over)

Two source, radial arrangement

Service outage time can be reduced considerably by using

circuit breakers to automatically, or on command from a

central control station, disconnect the faulted source or bus

and connect the substation so that power can reach all of

the feeders.

Figure shows a substation connected for automatic switching,

also called throw-over or roll-over.

Operation:

Assume sources 1 and 2 are connected as radial lines.

1. Source 1 is lost, breaker 1 will open under relay control

disconnecting source 1

2 . Breaker 3 closes connecting transformer 1 to source 2,

and vice versa.

3. If transformer 1 fails, breakers 1, 3, and 4 would open

to disconnect it.

The low voltage bus tie breaker 6 closes to connect all

of the feeders to transformer 2

The low voltage tie breaker is interlocked with

transformer secondary breakers 4 and 5 to prevent

parallel transformer operation.

Page 69: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

TRANSMISSION LINE FAULT CALCULATIONS

Fault Classifications :

1. Line to ground. Line to ground faults are caused by a line touching the ground. Wind, ice loading, tree falling on a line can cause a line to ground fault. This category accounts for about 70% of all line short circuit faults.

A system fault is defined as any abnormal condition.

69

Page 70: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Fault Classifications :

2. Line to line. These faults are caused by high winds blowing one line into another, or by a line breaking and falling on a line below it.These account for about 15% of line faults.

70

Page 71: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Fault Classifications :

3. Double line to ground. This category is caused by the same things that cause single line to ground faults, except two lines are involved instead of one. These account for about 10% of line faults.

71

Page 72: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Fault Classifications :

4. Three-phase faults. If a line condition occurs in which all three phases are shorted together, an equipment failure, or all three lines falling to the ground, it is called a three-phase fault. Accounts for only about 5% of all line faults.

72

Page 73: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

The point at which a conductor touches ground or another conductor during a fault is usually accompanied by an arc.

The arc is resistive, but arc resistance varies widely.

The usual utility practice is to consider the fault resistance zero to calculate the maximum fault current that can occur at a point of interest on a line.

The fault current that flows depends on the source, line, and fault impedances:

73

Page 74: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

Bus Protection

Differential protection is effective for bus faults because the current leaving the bus on

feeders and the current entering the bus from sources should be zero at any instant.

Additionally, differential protection can distinguish between internal bus faults and external

feeder faults. A feeder fault can result in the CTs on the feeder saturating, and the dc offset

of a fault worsens the situation. Thus special care must be taken in bus differential relaying

to prevent external faults from causing a trip on the circuit breakers supplying the bus.

Three major systems are used: .

1. Linear coupler (LC) system, which works by eliminating the iron core of the CTs.

2. Multi-restraint, variable percentage relays (CA-16).

3. High impedance voltage operated differential relays (KAB).

Page 75: EET 3390 - Michigan Tech IT Support Centerpages.mtu.edu/~avsergue/EET3390/Lectures/EET_3390... · 2010-12-08 · EET 3390 COURSE OVERVIEW. The ... 500, 765 (in kV) 3. AC power versus

SUBSTATION GROUNDING

Substation grounding is done safety, and to provide a stable reference voltage for protection systems.

The grounding system of a substation consists of a ground mat made of large size bare conductors,

connected in a grid pattern, and buried beneath the substation.

The perimeter of the grid is connected to metal rods driven about 30 feet into the ground. The grid wires

are about 20 feet apart but the spacing varies with the conductivity of the soil.

Highly conductive soil can use larger grid wire spacing.

All substation structures are to be constructed within the perimeter of the grid.

The fence around a substation has two buried ground wires connected to the fence every few feet.

One runs about 3 feet outside the fence, and one inside the fence.

Both wires are connected to grounding rods every 50 feet.