Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
WRc Ref: Defra 10459.04
March 2015
Effect of UV on the Chemical Composition of
Water including DBP Formation: Final Report
RESTRICTION: This report has the following limited distribution:
External: DWI
© WRc plc 2015 The contents of this document are subject to copyright and all rights are reserved. No part of this document may be reproduced, stored in a retrieval system or transmitted, in any form or by any means electronic, mechanical, photocopying, recording or otherwise, without the prior written consent of WRc plc.
This document has been produced by WRc plc.
Any enquiries relating to this report should be referred to the Project Manager at the following address:
WRc plc,
Frankland Road, Blagrove,
Swindon, Wiltshire, SN5 8YF
Telephone: + 44 (0) 1793 865000
Fax: + 44 (0) 1793 865001
Website: www.wrcplc.co.uk
Effect of UV on the Chemical Composition of
Water including DBP Formation: Final Report
Report No.: Defra 10459.04
Date: March 2015
Authors: David Shepherd, Rowena Gee, Tom Hall, Paul Rumsby, Glenn Dillon
Project Manager: Glenn Dillon
Project No.: 16164-0
Client: DWI
Client Manager: Annabelle May
Version Control Table
Version
number Purpose Issued by
Quality Checks
Approved by Date
V.01 Draft final report issued to DWI Representative for PSG meeting.
Glenn Dillon, Project Manager
Glenn Dillon 21/11/2014
V.02 Draft final report issued to DWI Representative for review.
Glenn Dillon, Project Manager
Tom Hall 29/12/2014
V.03 Revised final report issued to DWI Representative for review
Glenn Dillon, Project Manager
Tom Hall 03/02/2015
V.04 Final report issued. Glenn Dillon, Project Manager
Simon Blake 04/03/2015
Acknowledgement
This project was funded by Defra and managed by DWI.
The authors gratefully acknowledge the assistance given by water companies in England and Wales in
providing data and other information.
Disclaimer
Defra and DWI assume no responsibility for the content of this report. Any views expressed are those
of the authors and not necessarily those of Defra or DWI.
Contents
Summary .................................................................................................................................. 1
1. Introduction .................................................................................................................. 3
1.1 Objectives .................................................................................................................... 3
1.2 Background ................................................................................................................. 3
1.3 Résumé of contents .................................................................................................... 4
2. Literature Review ........................................................................................................ 5
2.1 Introduction .................................................................................................................. 5
2.2 Effect of UV used for disinfection ................................................................................ 5
2.3 Effect of UV in advanced oxidation processes .......................................................... 11
2.4 Conclusions ............................................................................................................... 24
3. UV Treatment in Public Supplies .............................................................................. 26
3.1 Introduction ................................................................................................................ 26
3.2 Results ...................................................................................................................... 26
3.3 Conclusions ............................................................................................................... 26
4. Effect of UV Dosage and/or Pre-oxidation on Chemical Composition and DBP Formation ................................................................................................... 31
4.1 Introduction ................................................................................................................ 31
4.2 Selected works and results ....................................................................................... 31
4.3 Conclusions ............................................................................................................... 34
5. UV Treatment in Private Supplies ............................................................................. 35
5.1 Introduction ................................................................................................................ 35
5.2 2011 data .................................................................................................................. 35
5.3 2012 data .................................................................................................................. 36
5.4 2013 data .................................................................................................................. 38
5.5 Nitrate and bromate .................................................................................................. 38
5.6 Conclusions ............................................................................................................... 43
6. Health Significance.................................................................................................... 44
6.1 Introduction ................................................................................................................ 44
6.2 Cytotoxicity and genotoxicity studies ........................................................................ 44
6.3 Derivation of guidance values ................................................................................... 54
6.4 Conclusions ............................................................................................................... 55
7. Future Research........................................................................................................ 57
7.1 Public supplies .......................................................................................................... 57
7.2 Private supplies ......................................................................................................... 62
8. Conclusions ............................................................................................................... 63
8.1 Literature review ........................................................................................................ 63
8.2 Public supplies .......................................................................................................... 63
8.3 Private supplies ......................................................................................................... 64
8.4 Health effects ............................................................................................................ 64
References ............................................................................................................................. 65
Glossary of Terms .................................................................................................................. 69
Appendices
Appendix A Literature Review ..................................................................................... 71
Appendix B UV Treatment in Public Supplies: Returned Questionnaires .................. 85
Appendix C Site Visit Data ........................................................................................ 107
List of Tables
Table 2.1 Summary of UV effects ........................................................................... 14
Table 3.1 Summary of UV treatment by function and source ................................. 28
Table 3.2 Summary of UV treatment by upstream treatment, dose and DBPs detected ......................................................................................... 30
Table 5.1 Summary of UV treated private supplies by water source (2011) ...................................................................................................... 35
Table 5.2 Summary of UV treated private supplies by water use (2011) ................ 36
Table 5.3 Summary of UV treated private supplies by water source (2012) ...................................................................................................... 37
Table 5.4 Summary of UV treated private supplies by water use (2012) ................ 37
Table 5.5 Private supplies: Nitrate (mg/l) ................................................................ 39
Table 5.6 Private supplies: Bromate (µg/l) .............................................................. 42
Table 6.1 Toxicity for different treatment processes ............................................... 47
Table 6.2 Summary of cytotoxicity and genotoxicity studies ................................... 50
Table 6.3 Guideline values for DBPs identified in the literature review .................. 54
Table 7.1 Summary of proposed small-scale investigations ................................... 61
Table C.1 Works A5: Effect of prechlorination on bromate formation ................... 114
List of Figures
Figure 7.1 Upland surface waters and treatment ..................................................... 58
Figure 7.2 Lowland surface waters and treatments.................................................. 59
Figure 7.3 Groundwater and treatment .................................................................... 60
Figure C.1 Works A2: Schematic ............................................................................ 109
Figure C.2 Works A2: Final water THMs ................................................................. 110
Figure C.3 Works A2: UV254 absorbance after preozonation .................................. 111
Figure C.4 Works A2: UV254 absorbance after GAC ............................................... 111
Figure C.5 Works A2: Final water bromate and bromide ........................................ 112
Figure C.6 Works A5: Schematic ............................................................................ 113
Figure C.7 Works A5: Final water THMs ................................................................. 114
Figure C.8 Works A5: Bromate formation due to sunlight ....................................... 115
Figure C.9 Works B1: Schematic ............................................................................ 117
Figure C.10 Works B1: Final water THMs ................................................................. 119
Figure C.11 Works B1: SR1 THMs ........................................................................... 119
Figure C.12 Works B1:SR2 THMs ............................................................................ 120
Figure C.13 Works B1: Filtered water THMs ............................................................ 120
Figure C.14 Works B1: Raw water algal counts ........................................................ 121
Figure C.15 Works B1: Raw and final water TOC..................................................... 121
Figure C.16 Works B1: SR1 THMs (2010-12) ........................................................... 122
Figure C.17 Works B2: Schematic ............................................................................ 123
Figure C.18 Works B2: Final water THMs (April-September 2013) .......................... 125
Figure C.19 Works B2: Final water THMs (April-September 2014) .......................... 125
Figure C.20 Works B2: SR1 THMs (2013) ................................................................ 126
Figure C.21 Works B2: SR1 THMs (2014) ................................................................ 126
Figure C.22 Works B2: TOC (2013) .......................................................................... 127
Figure C.23 Works B2: TOC (2014) .......................................................................... 127
Figure C.24 Works B2: Raw water colour (2013) ...................................................... 128
Figure C.25 Works B2: Raw water colour (2014) ...................................................... 128
Figure C.26 Works D2: Schematic ............................................................................ 129
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 1
Summary
i Reasons
Ultraviolet (UV) disinfection has been used in water treatment for many years and its
implementation in the UK is increasing for general disinfection or specifically to deal with
Cryptosporidium. In addition, advanced oxidation processes (AOPs) incorporating UV at much
higher doses than used for disinfection have been developed over recent years for destruction
of organic micropollutants such as pesticides and algal metabolic products.
Whilst the risk of formation of disinfection by-products (DBPs) from the use of UV is believed
to be low, this work will identify the implications of UV treatment for changing water chemistry,
particularly in relation to DBP formation.
The results of this work will be used to further inform the use of UV in water treatment.
ii Objectives
The aim of this project was to increase DWI‟s understanding of the impact of UV disinfection
on the chemical composition of water, with specific reference to potential formation or removal
of DBPs.
iii Résumé of Contents
This report presents a review of the literature on the effects of UV disinfection on the chemical
composition of water (Section 2), a review of UV treatment in public supplies (Section 3), the
effect of UV dosage and/or pre-oxidation as evidenced from selected treatment works
(Section 4), a review of UV treatment in private supplies (Section 5), a review of the health
significance of DBPs identified as being formed by UV (Section 6), and suggested areas for
future research to fill knowledge gaps regarding DBP formation as a result of UV treatment
(Section 7). Conclusions are presented in Section 8.
iv Conclusions
The potential formation of DBPs as a result of treatment by appropriately designed and
maintained UV systems is low. The most significant DBPs are nitrite (formed from nitrate) and
bromate (formed from prechlorinated supplies containing bromide); the formation of both can
be minimised by appropriate water treatment and UV system design.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 2
A survey of water companies in England and Wales (73% response) identified 89 UV plants
(existing and proposed) with a total treatment capacity of 1,492 Ml/d used mostly at small
groundwater sites for general disinfection and where there is a Cryptosporidium risk.
The full extent of UV treatment of private supplies is unclear from Local Authority (LA) returns
to DWI. UV treated private supplies used for commercial purposes appear to account for
around 90% of persons served and 97-98% of water capacity. Whilst it is unlikely that
formation of DBPs is a significant risk for private supplies, the risk might be greater for
supplies used for commercial purposes where water treatment might include prechlorination
or the UV system might incorporate medium pressure (MP) lamps.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 3
1. Introduction
1.1 Objectives
The aim of this project was to increase DWI‟s understanding of the impact of ultraviolet (UV)
disinfection on the chemical composition of water, with specific reference to potential
formation or removal of disinfection by-products (DBPs).
1.2 Background
Whilst UV disinfection has been used in water treatment for many years, its implementation in
the UK is increasing for general disinfection or specifically to deal with Cryptosporidium. In
addition, advanced oxidation processes (AOPs) incorporating UV at much higher doses than
used for disinfection have been developed over recent years for destruction of organic
micropollutants such as pesticides and algal metabolic products. Disinfection doses for UV
are typically about 40 mJ/cm2, whereas AOP doses are at least an order of magnitude higher.
The risk of formation of DBPs from the use of UV is believed to be low. Two basic types of UV
lamp are used: low pressure (LP) and medium pressure (MP). LP lamps emit UV almost
entirely at the germicidal wavelength of 254 nm, whereas MP lamps emit UV at a wider range
of wavelengths, e.g. 200-300 nm. The DBP most associated with the use of UV is nitrite,
which is formed from reduction of nitrate at a wavelength of less than 230 nm. The formation
of nitrite by MP lamps is minimised by the incorporation of quartz sleeves to remove the lower
wavelength UV. Similarly, absorption of UV by natural organic compounds in water may also
occur at lower wavelength, and any changes to water chemistry from this mechanism may
influence DBP formation. There have been recent reports in the UK of bromate formation
when prechlorinated water is dosed with UV at doses of above 100 mJ/cm2 or when exposed
to natural sunlight. Bromate had not previously been identified as significant from the use of
UV.
The overall objective of this work was to identify the implications of UV treatment for changing
water chemistry, particularly in relation to DBP formation, through its use on public and private
water supplies. The implications for DBPs should include not only those for which standards
exist, specifically the trihalomethanes (THMs), chlorate/chlorite, nitrite and bromate, but also
those without current standards which need to be minimised without compromising
disinfection. These would include haloacetic acids (HAAs), nitrogen-containing DBPs,
iodinated THMs/HAAs and nitrosamines.
The overall objective was met through the sub-objectives:
Identification of the possible mechanisms for changes in water chemistry and DBP
formation from UV use, through a review of published information, and the impact of UV
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 4
type, dose, water quality and other treatments, particularly oxidation, upstream and
downstream to UV.
The implications of these changes for drinking water quality, health or aesthetic
considerations.
The potential scope and impact of these changes based on current UV implementation
for both public and private water supplies.
Evidence of whether or not these changes are significant for public supplies based on a
review of existing data from water treatment works monitoring.
A programme of further work needed to clarify the findings and fill knowledge gaps.
The results of this work will be used to further inform the use of UV in water treatment.
1.3 Résumé of contents
This report presents a review of the literature on the effects of UV disinfection on the chemical
composition of water (Section 2), a review of UV treatment in public supplies (Section 3), the
effect of UV dosage and/or pre-oxidation as evidenced from selected treatment works
(Section 4), a review of UV treatment in private supplies (Section 5), a review of the health
significance of DBPs identified as being formed by UV (Section 6), and suggested areas for
future research to fill knowledge gaps regarding DBP formation as a result of UV treatment
(Section 7). Conclusions are presented in Section 8.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 5
2. Literature Review
2.1 Introduction
The results of the literature review are summarised below; the detailed review is presented in
Appendix A.
The literature review has considered the use of UV irradiation in water treatment for
disinfection and in AOPs. Findings most relevant to conditions used for drinking water
treatment are summarised below for UV disinfection (Section 2.2) and for UV used in AOPs
(Section 2.3). A tabulated summary of the findings is given in Table 2.1.
2.2 Effect of UV used for disinfection
UV disinfection typically uses LP or MP lamps. LP lamps emit essentially monochromatic UV
at 254 nm, whereas MP lamps emit within the range 200-400 nm1. The UV dose for primary
disinfection will typically2 be 40 mJ/cm
2.
2.2.1 Effect of UV on organics
LP UV
Various investigations applying LP UV at doses of 40-200 mJ/cm2 reported no change in the
nature of dissolved organic carbon (DOC) as indicated by DOC concentration, UV254
absorbance and/or specific UV absorbance (SUVA) (Malley et al., 1995; Kashinkunti et al.,
2004; Chin and Berube, 2005; Ijpelaar et al., 2005; Choi and Choi, 2010). An increase in the
fraction of hydrophilic DOC was observed in some (generally low-coloured) waters but not
others (generally high-coloured) by Malley et al. (1995); however, Choi and Choi (2010) found
no change in this metric for the treated surface water used in their tests.
Choi and Choi (2010) investigated dual wavelength (185/254 nm) LP UV. At 40 mJ/cm2, there
was no change in the nature of the DOC, but at 150 mJ/cm2 the average molecular weight
was reduced, consistent with breakage of organic bonds at lower (<200 nm) wavelengths.
1 German (DVGW) and Austrian (ÖNORM) standards for validating performance of MP lamps for
disinfection require wavelengths below 240 nm to be blocked, but the equivalent American (USEPA)
validation protocol does not.
2 German (DVGW) and Austrian (ÖNORM) standards for validating performance of UV for disinfection
stipulate 40 mJ/cm2, but the equivalent American (USEPA) protocol validates performance in terms
of log inactivation of target pathogens (Cryptosporidium, Giardia and/or viruses). The dose applied
by a USEPA validated UV plant may therefore be less than or greater than 40 mJ/cm2.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 6
Various investigations applying LP UV at doses of 40–200 mJ/cm2 reported no change in
regrowth potential as indicated by assimilable organic carbon (AOC) concentration (Malley et
al., 1995; Kashinkunti et al., 2004; Chin and Berube, 2005; Ijpelaar et al., 2005; Choi and
Choi, 2010). An increase in biodegradable dissolved organic carbon (BDOC) was observed in
some (untreated surface) waters but not others (treated surface, ground) by Malley et al.
(1995).
MP UV
MP UV applied at 40 mJ/cm2 resulted in no change in the nature of DOC as indicated by DOC
concentration, UV254 absorbance, fraction of hydrophilic DOC or SUVA (Choi and Choi, 2010).
Over the course of a year, the average molecular weight was decreased for one season but
unchanged for the remainder. Choi and Choi noted that breakage of organic bonds by UV is
more likely at higher (>280 nm) wavelengths as well as lower (<200 nm).
Neither Kashinkunti et al. (2004), (doses 40-140 mJ/cm2) nor Choi and Choi (2010)
(40 mJ/cm2) observed any change in regrowth potential as indicated by AOC concentration.
However, Ijpelaar et al., (2005) reported that AOC increased with increasing UV dose (47-
91 mJ/cm2) and suggested that GAC should be installed after MP UV. Ijpelaar et al. (2007)
concluded that AOC formation is favoured by MP UV, although any increase is unlikely to
exceed 10 g/l for doses <100 mJ/cm2.
2.2.2 Formation of DBPs: Direct formation
Nitrogenated by-products
LP UV
No nitrophenols or nitrosamines were detected following UV irradiation of treated municipal
wastewater effluent (100-160 mJ/cm2) (Liberti et al., 2002). Mole et al. (1997) found some
evidence of the formation of unidentified N-containing compounds after applying a dose of
6,600 mJ/cm2 to an untreated surface water.
Aldehydes and carboxylic acids
LP UV
Formaldehyde (up to 10 μg/l) was formed in various water samples (treated and untreated
surface waters; coloured groundwaters) after a dose of 130 mJ/cm2; concentrations were
highest in coloured surface water and highly-coloured (50 ºH) groundwater, whereas no
formaldehyde was detected in low-coloured groundwater samples (Malley et al., 1995). Mole
et al. (1997) detected formaldehyde and acetaldehyde at concentrations <10 μg/l in untreated
surface water (110 mJ/cm2) and groundwater with added humic acid (220 mJ/cm
2); in both
cases the aldehyde concentration increased at higher UV doses. Liu et al. (2002) observed no
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 7
aldehyde formation in synthetic drinking waters at doses 40-500 mJ/cm2, but some formation
(maximum 13 μg/l) as dose increased to 6,360 mJ/cm2.
Carboxylic acids were not formed as a result of UV irradiation of synthetic drinking water at
doses less than 1,000 mJ/cm2 (Liu et al., 2002).
MP UV
Aldehydes were not formed as a result of UV irradiation of synthetic drinking water at doses
less than 1,000 mJ/cm2 (Liu et al., 2002). However, formation was evident at higher doses
(maximum 37 μg/l at 6,360 mJ/cm2).
Carboxylic acids were not formed as a result of UV irradiation of synthetic drinking water at
doses less than 1,000 mJ/cm2 (Liu et al., 2002). However, 100-240 μg/l were formed
(primarily formic, acetic and oxalic acids) at 6,360 mJ/cm2.
Nitrite
LP UV
Malley et al. (2005), Mole et al. (1997) and Ijpelaar et al. (2005) did not detect nitrite after
applying doses up to 120 mJ/cm2 variously to groundwater, nitrate-spiked deionised water
and treated surface water samples. Ijpellar et al. (2007), however, detected nitrite following
irradiation of nitrate-containing waters: 2 μg/l nitrite at 25 mJ/cm2 with 50 mg/l NO3; and 7 μg/l
nitrite at 120 mJ/cm2 with 14 mg/l NO3. Mole et al. (1997) also observed nitrite after higher
doses (1,100-22,850 mJ/cm2), with formation increasing with UV dose and nitrate
concentration.
MP UV
Ijpellar et al. (2005) detected c. 40 μg/l nitrite following irradiation of a treated surface water at
100 mJ/cm2. Ijpellar et al. (2007) detected 20-40 μg/l nitrite following irradiation at 70 mJ/cm
2;
the lower formation corresponded to an initial nitrate concentration of 8 mg/l, and the higher to
15 mg/l. Ijpellar et al. (2007) also reported that fitting MP lamps with sleeves to block
wavelengths below 235 nm reduced nitrite formation from 150 μg/l to 30 μg/l (50 mJ/cm2,
50 mg/l nitrate). They noted that nitrate absorbs UV predominantly in the 200-240 nm
wavelength range3.
3 Hence it is expected that nitrite formation should not be an issue with MP UV units validated to the
DVGW or ÖNORM standards.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 8
Bromate
Ijpelaar et al. (2007) stated that neither UV nor UV/H2O2 are able to convert bromide to
bromate.
LP UV
Neither Malley et al. (1995) nor Kishimoto and Nakamura (2012) detected bromate formation
after UV irradiation of bromide-containing waters.
Benzene and toluene
LP UV
Zoeteman et al. (1982) detected benzene (0.9 g/l) and toluene (3 g/l) after UV irradiation of
stored River Rhine water at 120 mJ/cm2.
2.2.3 Formation of DBPs: Effect of UV upstream of chlorination
LP UV
Upstream UV irradiation at doses used for disinfection has little, if any, effect on subsequent
formation of THMs (Malley et al., 1995; Liu et al., 2002; Kashinkunti et al., 2004; Chin and
Berube, 2005; Reckhow et al., 2010; Lyon et al., 2012; Linden et al., 2012). However, Liu et
al. (2006) dosed 7 mg/l free chlorine to various waters after UV irradiation at 60 mJ/cm2;
chloroform formation increased by 20-100% in 3 waters but was unchanged in one. Choi and
Choi (2010) found 40 mJ/cm2 had no effect on chlorine demand of a treated surface water at
4°C but increased short-term chlorine demand at 15°C. They also observed that this UV dose
increased THM formation by c. 5-10% in summer and autumn but not in winter and spring.
Dotson et al. (2010) reported an increase in THMFP of c. 15% after applying a UV dose of
1,000 mJ/cm2 to treated river water. The 24-hour chlorine demand increased by c. 40%.
Generally, upstream UV irradiation at doses used for disinfection has little effect on
subsequent formation of HAAs (Malley et al., 1995; Kashinkunti et al., 2004; Chin and Berube,
2005; Reckhow et al., 2010; Lyon et al., 2012). However, Liu et al. (2006) reported 60 mJ/cm2
increased dichloroacetic acid (DCAA) and trichloroacetic acid (TCAA) by 10-50% in 3 waters
but had no impact on one.
Malley et al. (1995) reported UV dosed at 60–200 mJ/cm2 did not affect subsequent formation
of cyanogen chloride (CNCl). Conversely, Liu et al. (2006) reported increased (40-130%)
CNCl concentrations in chlorinated waters dosed upstream at 60 mJ/cm2 in three out of four
waters tested, but no change in the other one.
In a US study (Reckhow et al., 2010), LP UV dosed at 40–140 mJ/cm2
to raw and treated
water had no impact on formation of haloacetonitriles (HANs) and trichloropropanone (TCP).
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 9
Shah et al. (2011) found that UV doses up to 1,000 mJ/cm2 had no effect on
halonitromethane formation after subsequent chlorination. Linden et al. (2012) observed some
additional formation of halonitromethane, at the single g/l level, after UV doses up to
186 mJ/cm2; greater increases were apparent at higher doses (186-1,000 mJ/cm
2).
Lyon et al. (2012) reported increased bromopicrin formation (40-186 mJ/cm2 in the presence
of nitrate and bromide). At a higher dose of 1,000 mJ/cm2, chloral hydrate formation
increased. Linden et al. (2012) observed some additional formation of chloral hydrate, at the
single g/l level, after UV doses up to 186 mJ/cm2; greater increases were apparent at higher
doses (186-1,000 mJ/cm2).
Chu et al. (2014) found doses of 19.5–585 mJ/cm2 did not influence haloacetamide formation.
Linden et al. (2012) concluded that nitrosamine formation after subsequent chloramination is
likely to be reduced to a small degree after UV doses of up to 186 mJ/cm2, with greater
reductions expected at higher doses (186-1,000 mJ/cm2).
MP UV
Upstream UV irradiation at doses used for disinfection has little, if any, effect on subsequent
formation of THMs (Liu et al., 2002; Kashinkunti et al., 2004; Reckhow et al., 2010; Lyon et
al., 2012). However, Liu et al. (2006) dosed 7 mg/l free chlorine to various waters dosed with
at 60 mJ/cm2; chloroform formation increased by 40-110% in 3 waters but was unchanged in
one. Choi and Choi (2010) found 40 mJ/cm2 had no effect on chlorine demand of a treated
surface water at 4°C but increased short-term chlorine demand at 15°C. They also observed
that this UV dose increased THM formation by c. 5-10% in summer and autumn but not in
winter and spring. Liu et al. (2002) observed a decrease of 9-29% in THM formation when
dose was increased to 5,000 mJ/cm2, whereas Lyon et al. (2012) reported THM formation
increased by 30-40% when dose was increased to 1,000 mJ/cm2. Dotson et al. (2010)
reported an increase in THMFP of c. 30-50% after applying a UV dose of 1,000 mJ/cm2 to
treated river water. The 24-hour chlorine demand increased by c. 60%.
Generally, upstream UV irradiation at doses used for disinfection has little effect on
subsequent formation of HAAs (Liu et al., 2002; Kashinkunti et al., 2004; Reckhow et al.,
2010; Lyon et al., 2012; Linden et al., 2012). However, Liu et al. (2006) reported 60 mJ/cm2.
increased formation of dichloroacetic acid (DCAA) and trichloroacetic acid (TCAA) by c. 10-
90% in two waters tested but reduced it by 10-30% in two other waters. Liu et al. (2002)
observed a decrease of 15-44% in HAA formation when dose was increased to 5,000 mJ/cm2.
Liu et al. (2006) reported increased CNCl concentrations by 10-100% in four chlorinated
waters dosed upstream with 60 mJ/cm2. Lyon et al. (2012) reported the formation of CNCl
after subsequent chloramination doubled when UV was dosed at 186 mJ/cm2 in the presence
of nitrate.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 10
Reckhow et al. (2010) reported that UV dosed at 40–140 mJ/cm2
to raw and treated water
increased chloropicrin formation. Shah et al. (2011) found that doses <300 mJ/cm2 increased
chloropicrin formation by as much as an order of magnitude after chlorination. Similarly, Lyon
et al. (2012) reported chloropicrin formation increased by 3 to 6 times after UV doses of 40-
186 mJ/cm2, in the presence of nitrate; and bromopicrin formation increased by 4 to 10 times
after a UV dose of 40 mJ/cm2 in the presence of nitrate and bromide.
Reckhow et al. (2010) reported that UV dosed at 40–140 mJ/cm2
to raw and treated water
increased chloral hydrate formation. Lyon et al. (2012) reported chloral hydrate formation
increased by 20–40% after a UV dose of 40 mJ/cm2. Linden et al. (2012) observed some
additional formation of chloral hydrate, at the single g/l level, after UV doses up to
186 mJ/cm2; greater increases were apparent at higher doses (186-1000 mJ/cm
2).
Linden et al. (2012) observed some additional formation of halonitromethane, at the single
g/l level, after UV doses up to 186 mJ/cm2; greater increases were apparent at higher doses
(186-1,000 mJ/cm2).
Linden et al. (2012) concluded that nitrosamine formation after subsequent chloramination is
likely to be reduced to a small degree after UV doses of up to 186 mJ/cm2, with greater
reductions expected at higher doses (186-1,000 mJ/cm2).
2.2.4 Formation of DBPs: Effect of UV downstream of chlorination
Linden et al. (2012) concluded that UV doses <186 mJ/cm2 did not alter chlorine (or
chloramine) demand nor regulated DBP formation to any practical extent. However, they
noted that photolysis of chlorine species formed hydroxyl and chloride radicals, and
recommended that UV disinfection be installed upstream of secondary disinfection.
LP UV
Huang et al. (2008) reported formation of 10-15 ug/l bromate in chlorinated bromide-spiked
deionised water exposed to LP UV (200-1,000 mJ/cm2 for 5-25 minutes). Bromate formation
was greater at acidic pH (<6).
MP UV
Campbell (2011) reported elevated bromate concentrations at two groundwater sites
containing >100 ug/l bromide where UV >100 mJ/cm2 was dosed post chlorination.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 11
2.2.5 Effect of UV on pre-formed DBPs
Bromate
LP UV
Siddiqui et al. (1996) reported 3-38% decomposition of bromate to bromide (via bromite and
hypobromite) at doses of 22-228 mJ/cm2 using „tailored‟ LP UV at <200 nm. Smaller
conversions of bromate were measured at higher UV doses using standard LP UV.
MP UV
Siddiqui et al. (1996) reported 7-46% decomposition of bromate to bromide (via bromite and
hypobromite) at doses of 60-550 mJ/cm2.
Bensalah et al. (2013) reported 90% decomposition of bromate to at a dose of 1,000 mJ/cm2.
THMs
LP UV
Mole et al. (1997) reported removals of the regulated THMs (bromoform, chlorodibromoform
and bromodichloroform) from spiked groundwaters at LP UV doses of 1,100 and 6,600
mJ/cm2. Chloroform was not removed, indicating that photolysis of the Br-C bond occurs more
readily than the Cl-C bond.
Chang (2008) observed for UV doses of 0-2,200 mJ/cm2 minimal removal of chloroform but
removals of brominated THMs at rates which increased with bromine content.
HAAs
LP UV
Chang (2008) observed for UV doses of 0-4,400 mJ/cm2 negligible removal of chlorinated
HAAs (monochloroacetic acid (MCAA), dichloroacetic acid (DCAA), trichloroacetic acid
(TCAA)) and monobromoacetic acid (MBAA) but greater removals of brominated HAAs
(dibromoacetic acid (DBAA), tribromoacetic acid (TBAA)) at rates which increased with
bromine content.
2.3 Effect of UV in advanced oxidation processes
UV may be used in conjunction with ozone (O3), hydrogen peroxide (H2O2) or titanium dioxide
(TiO2) in AOPs, with subsequent reactions strongly influenced by the presence of highly
reactive hydroxyl radicals. UV doses used in AOPs are typically an order of magnitude or
more greater than used for disinfection.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 12
2.3.1 Effect of UV on organics
A reduction in TOC was reported after UV/TiO2 photocatalytic treatment (Richardson et al.,
1996), but the magnitude of the reduction (40%) was likely have been enhanced by the
configuration of the experiment (the samples were recirculated for 24 hours).
Mineralisation of TOC by UV/O3 was observed by Chin and Berube (2005).
Increases in AOC in the range 27-131 mg/l have been reported following UV/H2O2 (MP UV
dose 540 mJ/cm2, H2O2 dose 4.0-6.9 mg/l). AOC formation was inversely related to nitrate
concentration; nitrate strongly absorbs UV at the wavelengths absorbed by natural organic
matter (NOM).
2.3.2 Formation of DBPs: Direct formation
Nitrite
Nitrite may be formed by photolysis of nitrate and is potentially greater at the higher UV doses
used for AOPs (Ijpelaar et al., 2007), for example 40-330 μg/l NO2- formed following UV/H2O2
(MP UV 540 mJ/cm2, H2O2 3.4-6.9 mg/l).
Bromate
Ozone reacts readily with bromide to from bromate. Collivignarelli and Sorlini (2004) reported
that LP UV/O3, with UV dose in the range 270-1,400 mJ/cm2 and ozone dose in the range 0.3
to 10 mg/l, reduced bromate formation by 40-50% relative to ozone alone provided UV dose
was less than 800 mJ/cm2 and/or CT (the product of ozone dose and contact time) was less
than 10 mg.min/l; above these thresholds UV did not reduce bromate formation. However,
Hofman et al. (2010) found that MP UV/O3 (600 mJ/cm2, 2 mg/l) did not reduce formation of
bromate relative to ozone alone.
Hydroxyl radicals can convert bromide to bromate via hypobromous acid (HOBr/OBr-), but in
the presence of H2O2 hypobromous acid is reduced to bromide. Hence bromate formation
from bromide is not expected from the UV/H2O2 process (Ijpelaar et al., 2007). Kishimoto and
Nakamura (2012) observed no bromate formation in experiments with UV/H2O2.
2.3.3 Formation of DBPs: Effect of UV upstream of chlorination
THMs and HAAs
Richardson et al. (1996) reported the formation of many halogenated DBPs after UV/TiO2 and
chlorination, but the number and concentrations were lower than when chlorine was used
alone.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 13
Kleiser and Frimmel (2000) reported an initial increase in THM formation potential following
UV/H2O2 (H2O2 8 mg/l) before declining at increased UV doses. DOC and UV254 absorbance
declined with UV dose. They concluded that molecular ozone is more effective than hydroxyl
radicals for decreasing halogenated organic DBP formation and that an ozone-based AOP is
advantageous if wanting to simultaneously remove micropollutants and reduce DBP
formation.
Collivignarelli and Sorlini (2004) performed bench-scale tests to determine performance of LP
UV/O3. The UV dose was in the range 270-1,400 mJ/cm2 and ozone dose 0.3-10 mg/l. THM
formation was typically 10-30% lower than ozone alone but there was considerable scatter in
their results, with some samples showing increased formation.
Chin and Berube (2005) compared UV/O3 with UV and O3 individually on precursors of
chlorinated DBPs. UV/O3 (130 mJ/cm2; 3 mg/l O3) reduced formation of chloroform and
chlorinated HAAs to a similar extent to that of O3 alone; increasing doses resulted in greater
reductions. UV alone had no impact on DBP formation.
Dotson et al. (2010) investigated DBP formation following UV/H2O2 treatment. Bench-scale
tests using LP and MP UV, with and without H2O2 addition, were carried out on treated water
sampled from a treatment works (river water source). Mean bromide in the treated water
measured 49 µg/l; mean TOC measured 1.51 mg/l in sand filtered water and 0.86 mg/l in
GAC filtered water. A UV dose of 1,000 mJ/cm2 with 10 mg/l H2O2 increased THMFP c. 100%
for both LP and MP UV. The 24-hour chlorine demand was approximately 0.6 mg/l higher
when the 10 mg/l H2O2 was used in combination with 1,000 mJ/cm2 UV, relative to
1,000 mJ/cm2 UV alone.
2.3.4 Effect of UV on pre-formed DBPs
THMs and HAAs
LP UV
Chang (2008) compared UV doses of 0-2,200 mJ/cm2 with and without 6 mg/l H2O2 for THM
removal. The addition of H2O2 did not affect reaction rates. Removal of chloroform was
minimal but removals of brominated THMs increased with bromine content.
Chang (2008) compared UV doses of 0-4,400 mJ/cm2 with and without 6 mg/l H2O2 for HAA
removal. The addition of H2O2 did not affect reaction rates. Removal of chlorinated HAAs
(MCAA, DCAA, TCAA) and MBAA was negligible but removals of brominated HAAs (DBAA,
TBAA) increased with bromine content.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 14
Table 2.1 Summary of UV effects
UV lamp type /
Wavelength (nm)
UV dose
(mJ/cm2)
Medium Observed effect(s) Reference
Effect of UV used for disinfection
Effect of UV on organics
LP 40 Treated SW No change in DOC / hydrophilic DOC, UV254, SUVA or
AOC.
Choi and Choi, 2010
LP 40-140 Treated SW (clarified, filtered, GAC) No change in AOC. Kashinkunti et al., 2004
LP 47-91 Treated SW No significant change in AOC. Ijpelaar et al., 2005
LP 60-200 GWs, untreated SWs, treated (clarified or
filtered) SWs
No change in DOC or UV254 absorbance; AOC was
unchanged; BDOC increased in untreated SWs but
was unchanged in treated SWs and GWs; hydrophilic
DOC increased in treated SWs and low-coloured GWs
but was unchanged in high-coloured untreated SWs
and GWs.
Malley et al., 1995
LP 130-1,600 SW (untreated lake water) No effect on TOC at any dose. No effect on UV254
absorbance at 130 mJ/cm2; marginal reduction at 1600
mJ/cm2.
Chin and Berube, 2005
Dual LP (185/254 nm) 40 Treated SW No change in DOC / hydrophilic DOC, UV254, SUVA or
AOC.
Choi and Choi, 2010
150 No change in DOC / hydrophilic DOC, UV254, SUVA or
AOC. DOM molecular weight decreased in the “dry
season”, unchanged rest of the year.
MP (200-400 nm)
40 Treated SW No change in DOC / hydrophilic DOC, UV254, SUVA or
AOC. DOM molecular weight decreased in the “dry
season”, unchanged rest of the year.
MP (185-400 nm) 40 No change in DOC / hydrophilic DOC, UV254, SUVA or
AOC. DOM molecular weight decreased in the “dry
season”, unchanged rest of the year.
MP 40-140 Treated SW (clarified, filtered, GAC) No change in AOC. Kashinkunti et al., 2004
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 15
UV lamp type /
Wavelength (nm)
UV dose
(mJ/cm2)
Medium Observed effect(s) Reference
MP 47-91 Treated SW AOC increased approximately in proportion to dose (c.
400% at 91 mJ/cm2).
Ijpelaar et al., 2005
Formation of DBPs: Direct formation - Mutagenicity
LP 47-91 Treated SW No significant change in mutagenicity. Ijpelaar et al., 2005
LP 120 Stored SW (River Rhine) No significant change to mutagenicity. Zoeteman et al., 1982
MP 47-91 Treated SW Mutagenicity increased. Ijpelaar et al., 2005
Formation of DBPs: Direct formation - Nitrogenated by-products
LP 100-160 Effluent from municipal wastewater plant No nitrophenols or nitrosamines detected. Liberti et al., 2002
LP 6,600 SW (with/without 50 mg/l added NO3-) Possible formation of unidentified N-containing
compounds.
Mole et al., 1997
Formation of DBPs: Direct formation - Aldehydes and carboxylic acids
LP 130 GWs, untreated SWs, treated (clarified or
filtered) SWs
Formation of formaldehyde in untreated, coloured
SWs, treated SWs and a highly-coloured GW; no
formaldehyde detected in other GWs.
Malley et al., 1995
LP 40-500 Synthetic drinking water (c. 3 mg/l TOC) No significant formation of aldehydes (formaldehyde
and acetaldehyde) or carboxylic acids (formic, acetic
and oxalic acids.
Liu et al., 2002
1,000-6,360 Formation of aldehyde (formaldehyde and
acetaldehyde) increased at doses above 500 mJ/cm2
to 13 μg/l at 6360 mJ/cm2.
LP 110-16,500 Untreated River Thames water Formation of aldehyde (formaldehyde and
acetaldehyde) increased from 9.7 μg/l at 110 mJ/cm2 to
85 μg/l at 16500 mJ/cm2.
Mole et al., 1997
220-16,500 10 mg/l humic acid dissolved in borehole
water
Formation of aldehyde (formaldehyde and
acetaldehyde) increased from 2.9 μg/l at 220 mJ/cm2 to
48.8 μg/l at 16500 mJ/cm2.
MP 40-500 Synthetic drinking water (c. 3 mg/l TOC) No significant formation of aldehydes (formaldehyde
and acetaldehyde) or carboxylic acids (formic, acetic
and oxalic acids).
Liu et al., 2002
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 16
UV lamp type /
Wavelength (nm)
UV dose
(mJ/cm2)
Medium Observed effect(s) Reference
1,000-6,360 Formation of aldehyde (formaldehyde and
acetaldehyde) increased at doses above 500 mJ/cm2
to 37 μg/l at 6,360 mJ/cm2; carboxylic acids (formic,
acetic and oxalic acids) increased to 100-240 μg/l at
6,360 mJ/cm2.
Formation of DBPs: Direct formation - Nitrite
LP 130 GWs (nitrate 0.16-8.1 mg/l) No change in nitrate concentration and nitrite not
detected.
Malley et al., 1995
LP 60-120 Spiked deionised water (nitrate 10 & 50
mg/l)
Nitrite not detected (pH5-8) Mole et al., 1997
2,850-
22,850
At 2,850 mJ/cm2: 90 μg/l nitrite formed with 10 mg/l
nitrate; 290 μg/l nitrite formed with 50 mg/l nitrate
(pH7). At 22,850 mJ/cm2: 570 μg/l nitrite formed with
10 mg/l nitrate; 1,900 μg/l nitrite formed with 50 mg/l
nitrate (pH7).
1,100-6,600 Spiked deionised water (nitrate 50 mg/l) 161 μg/l nitrite formed at 1,100 mJ/cm2, pH8.1 but
<100 μg/l at pH5.1-7.2 (minimum formation at pH6.1).
Formation increased proportionately to dose to 6,600
mJ/cm2.
LP 47-91 Treated SW No significant formation of nitrite. Ijpelaar et al., 2005
LP 25-120
Not stated 2 μg/l nitrite at 25 mJ/cm2 (50 mg/l nitrate); 7 μg/l nitrite
at 120 mJ/cm2 (14 mg/l nitrate).
Ijpelaar et al., 2007
MP 70 Not stated 40 μg/l nitrite at 70 mJ/cm2 (15 mg/l nitrate); 20 μg/l
nitrite at 70 mJ/cm2 (8 mg/l nitrate).
MP 50 Not stated. 50 mg/l nitrate. 30 μg/l nitrite with sleeves to block wavelengths below
235 nm; 150 μg/l nitrite without sleeves.
MP 25-200 Treated SW c. 40 g/l nitrite formed at 100 mJ/cm2 (pilot scale);
BUT c. 800 g/l formed at 91 mJ/cm2 (bench scale).
Authors unable to explain discrepancy.
Ijpelaar et al., 2005
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 17
UV lamp type /
Wavelength (nm)
UV dose
(mJ/cm2)
Medium Observed effect(s) Reference
Formation of DBPs: Direct-formation - Bromate
LP 130 GWs (bromide 50-250 μg/l) No change in bromide concentration and bromate not
detected.
Malley et al., 1995
LP Not stated Not stated (bromide 150 μg/l) No bromate formation after 30 minutes irradiation. Kishimoto & Nakamura, 2012
Formation of DBPs: Direct formation - Other
LP 120 Stored SW (River Rhine) Benzene increased to 1 μg/l; toluene increased to 3
μg/l.
Zoeteman et al., 1982
Not stated Not stated SW (reservoirs) Copper released into solution from copper-bound NOM
(copper sulphate used to control algae).
Parkinson et al., 2001
Formation of DBPs: Effect of UV upstream of chlorination
LP 19.5-585 Various No effect on haloacetamide formation. Chu et al., 2014
LP 40 Treated SW No effect on chlorine demand at 4°C but increased
chlorine decay rate at 15°C. THM formation increased
by c. 5-10% in summer and autumn, no change in
winter or spring.
Choi and Choi, 2010
LP 40-140 Treated SW (clarified, filtered, GAC) Sequential UV and chlorine (2 mg/l dose, 24 hr contact
time): no effect on chlorine demand or formation of
THMs, HAAs, TOX, carboxylic acids and aldehydes.
Kashinkunti et al., 2004
LP 40-140 Raw and treated water No effect on formation of THMs, HAAs, HANs or TCP. Reckhow et al., 2010
LP 60-200 Not stated No effect of UV prior to chlorination or chloramination
on formation of THM, HAA or CNCl.
Malley et al., 1995
LP 40-500 Synthetic drinking water (c. 3 mg/l TOC) No effect on THM or HAA formation. Liu et al., 2002
1,000-6,360 THM formation increased by 15% at 5,000 mJ/cm2. No
effect on HAA formation.
LP 60 Three synthetic waters (each 5 mg/l DOC)
and a raw SW (1.8 mg/l DOC)
Sequential UV and chlorine (7 mg/l free chlorine dose,
3 day contact time): Chloroform formation increased in
3 waters by c. 20-100%, unchanged in 1 water; DCAA
and TCAA formation increased in 3 waters by c. 10-
50%, unchanged in 1 water. Sequential UV and
Liu et al., 2006
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 18
UV lamp type /
Wavelength (nm)
UV dose
(mJ/cm2)
Medium Observed effect(s) Reference
chlorine (7 mg/l free chlorine dose, 7 day contact time):
CNCl formation increased in 3 waters by c. 40-130%,
unchanged in 1 water.
LP Up to 1,500 Humic acid solution and “water samples” No effect of LP on halonitromethane formation. Shah et al., 2011
LP 40-186 “Water samples” spiked with bromide and
nitrate
No effect on THM and HAA formation. Bromopicrin
formation increased by 30-60% when both bromide
and nitrate spiked.
Lyon et al., 2012
1,000 THM formation increased by 30-40%. Chloral hydrate
formation increased.
LP <186 Not stated (various) Chlorine demand, THM and HAA formation unaffected.
Halonitromethane and chloral hydrate formation may
be increased, at single g/l level. Nitrosamine
formation likely reduced to small degree where
chloramination follows UV.
Linden et al., 2012
186-1,000 Chlorine/chloramine demand and corresponding DBP
concentrations increased. Halonitromethane and
chloral hydrate formation may be increased, at g/l
level. Nitrosamine formation likely reduced by
appreciable extent where chloramination follows UV.
LP 130-1,600 SW (untreated lake water ) Negligible reduction in formation potentials of
chloroform and chlorinated HAAs during subsequent
chlorination.
Chin and Berube, 2005
LP 500-1,000 Sand filtered river water (1.51 mg/l TOC);
GAC filtered river water (0.86 mg/l TOC)
c.15% increase in THM formation potential. Dotson et al., 2010
LP Not stated Filtered SW (River Ruhr) 7-13% reduction in THM formation potential after 30-
240 minutes; 13-24% reduction in AOX formation
potential in 30-240 minutes.
Kleiser and Frimmel, 2000
Dual LP (185/254 nm) 40 Treated SW No effect on chlorine demand at 4°C but increased
chlorine decay rate at 15°C. THM formation increased
by c. 5-10% in summer and autumn, no change in
winter or spring.
Choi and Choi, 2010
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 19
UV lamp type /
Wavelength (nm)
UV dose
(mJ/cm2)
Medium Observed effect(s) Reference
150 Increased chlorine decay rate at 4°C and 15°C. THM
formation increased by c. 5-15% in spring through
autumn, no change in winter.
MP 40-140 Treated SW (clarified, filtered, GAC) Sequential UV and chlorine (2 mg/l dose, 24 hr contact
time): no effect on chlorine demand or formation of
THMs, HAAs, TOX, carboxylic acids and aldehydes.
Kashinkunti et al., 2004
MP 40-140 Raw and treated water No effect on formation of THMs, HAAs, HANs or TCP;
chloral hydrate and chloropicrin increased with
increasing dose (chloropicrin also increased with
increasing nitrate).
Reckhow et al., 2010
MP <300 Humic acid solution and “water samples” Increased chloropicrin by an order of magnitude
(greater after chlorination than chloramination); MP
UV/chloramination increased HAN formation in the
humic acid solution but not in the water samples.
Shah et al., 2011
MP 40-500 Synthetic drinking water (c. 3 mg/l TOC) No effect on THM or HAA formation. Liu et al., 2002
1,000-6,360 THM formation decreased by 9- 29% at 5,000 mJ/cm2;
HAA formation decreased by 15-44% at >5,000
mJ/cm2.
MP 60 Three synthetic waters (each 5 mg/l DOC)
and a raw SW (1.8 mg/l DOC)
Sequential UV and chlorine (7 mg/l free chlorine dose,
3 day contact time): Chloroform formation increased in
3 waters by c. 40-110%, unchanged in 1 water; DCAA
and TCAA formation increased in 2 waters by c. 10-
90%, decreased in 2 waters by c. 10-30%. Sequential
UV and chlorine (7 mg/l free chlorine dose, 7 day
contact time): CNCl formation increased by c. 10-
100%.
Liu et al., 2006
MP 40 Treated SW No effect on chlorine demand at 4°C but increased
chlorine decay rate at 15°C. THM formation increased
by c. 5-10% in summer and autumn, no change in
winter or spring.
Choi and Choi, 2010
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 20
UV lamp type /
Wavelength (nm)
UV dose
(mJ/cm2)
Medium Observed effect(s) Reference
MP (185-400 nm) 40 Treated SW Increased chlorine decay rate at 4°C and 15°C. THM
formation increased by c. 5-16% in summer and
autumn, no change in winter or spring.
Choi and Choi, 2010
MP 40-186 “Water samples” spiked with bromide and
nitrate
No effect on THM and HAA formation. Chloropicrin
formation increased by a factor of 2 after
chloramination and by 3-6x after chlorination (nitrate 1-
10 mg/l N). Bromopicrin formation increased by 4-10x
at 40 mJ/cm2 in the presence of both bromide and
nitrate. Cyanogen chloride formation doubled at 186
mJ/cm2 after chloramination. Chloral hydrate formation
increased by 20-40% at 40 mJ/cm2.
Lyon et al., 2012
1,000 THM formation increased by 30-40%.
MP 500-1,000 Sand filtered river water (1.51 mg/l TOC);
GAC filtered river water (0.86 mg/l TOC)
c. 30-50% increase in THM formation potential. Dotson et al., 2010
MP <186 Not stated (various) Chlorine demand, THM and HAA formation unaffected.
Halonitromethane and chloral hydrate formation likely
to be increased, at single g/l level. Nitrosamine
formation likely reduced to small degree where
chloramination follows UV.
Linden et al., 2012
186-1,000 Chlorine/chloramine demand and corresponding DBP
concentrations increased. Halonitromethane and
chloral hydrate formation likely to be increased, at g/l
level. Nitrosamine formation likely reduced by
appreciable extent where chloramination follows UV.
Formation of DBPs: Effect of UV downstream of chlorination
Sunlight Sunlight Chlorinated sea water Increased chlorine decay rate and formation of
bromate (from hypobromite produced by the oxidation
of bromide ions by hypochlorite).
Wong, 1980
LP 40-2,000 Spiked (88 μg/l Br-) deionised water &
clarified/filtered river water (DOC=1.7 mg/l,
Br- = 53-151 μg/l)
Exposure to UV accelerated chlorine decay and
formation of bromate (10-15 μg/l in 5-25 min, and
greater at acidic pH (<6)).
Huang et al., 2008
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 21
UV lamp type /
Wavelength (nm)
UV dose
(mJ/cm2)
Medium Observed effect(s) Reference
Not stated 186 Not stated (various) UV doses <186 mJ/cm2 did not affect chlorine or
chloramine demand nor regulated DBP formation; UV
able to photolyse chlorine and chloramine (producing
hydroxyl and chloride radicals); recommended UV
disinfection be installed upstream of secondary
disinfection.
Linden et al., 2012
Effect of UV on pre-formed DBPs: Bromate
LP (<200 nm) 23-228 3-38% decomposition of bromate to bromide (via
bromite and hypobromite).
Siddiqui et al., 1996
MP 60-550 7-46% decomposition of bromate to bromide (via
bromite and hypobromite).
MP 1,000 90% decomposition of bromate. Presence of DOC,
inorganic carbon or nitrate reduced reaction rate.
Bensalah et al., (2013)
Effect of UV on pre-formed DBPs: THMs
LP 0-2,200 Deionised water Minimal removal of chloroform. Removal of brominated
THMs increased with increasing bromine content.
Reaction rates first order with respect to UV dose.
Chang, 2008
LP 1,100 /
6,600
THM (50 mg/l) spiked GW At 1,100 mJ/cm2, 80% removal of bromoform, 50% of
chlorodibromoform, 20% of bromodichloroform.
At 6,600 mJ/cm2, 100% removal of bromoform and
chlorodibromoform, 50% of bromodichloroform.
No removal of chloroform.
Mole et al., 1997
Effect of UV on pre-formed DBPs: HAAs
LP 0-4,400 Deionised water Negligible removal of chlorinated HAAs (MCAA, DCAA,
TCAA) and MBAA. Removal of more brominated HAAs
(DBAA, TBAA) increased with increasing bromine
content. Reaction rates first order with respect to UV
dose.
Chang, 2008
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 22
UV lamp type /
Wavelength (nm)
UV dose
(mJ/cm2)
Medium Observed effect(s) Reference
Effect of UV used in advanced oxidation processes
Effect of UV on organics
LP 130-1,610 SW (untreated lake water) UV/O3 oxidised organic material and to lesser extent
mineralised TOC.
Chin and Berube, 2005
MP 540 - AOC formation increased (by 27-131 mg/l) after
UV/H2O2 compared with UV disinfection alone; AOC
formation inversely related to nitrate (strongly absorbs
UV at wavelengths absorbed by NOM).
Ijpelaar et al., 2007
Not specified - Raw and ultrafiltered water 40% reduction in TOC after UV/TiO2 photocatalytic
treatment (recirculated in batch reactor for 24 hr).
Richardson et al., 1996
Formation of DBPs: Direct formation – Nitrite
MP 540 - UV/H2O2 plant 40-330 μg/l nitrite (nitrate 4.4-12.5 mg/l
NO3-.).
Ijpelaar et al., 2007
Formation of DBPs: Direct formation – Bromate
LP 270-1,400 SW (1.8 mg/l TOC) UV/O3: UV reduced bromate formation by 40-50%
relative to ozone alone provide UV dose <800 mJ/cm2
and ozone CT <10 mg.min/l.
Collivignarelli and Sorlini, 2004
LP Not stated Not stated (bromide 150 μg/l) UV/H2O2: No bromate formation after 30 minutes
irradiation.
Kishimoto & Nakamura, 2012
MP 600 Part-treated surface waters (0.24 and 1.75
mg/l DOC; bromide 170 μg/l)
UV/O3: After an O3 dose of 2 mg/l, UV increased
bromate formation from 28 to c. 55 g/l in the lower
DOC water but did not change formation in the higher
DOC water.
Hofman et al., 2010
Formation of DBPs: Effect of UV upstream of chlorination
LP 585 Various UV/H2O2 (10 mg/l H2O2): reduced formation of N-DBPs
(haloacetamides, haloacetonitriles, halonitromethanes).
Chu et al., 2014
LP 1,000 Sand filtered river water (1.51 mg/l TOC);
GAC filtered river water (0.86 mg/l TOC)
THMFP increased by c.15% as a result of UV alone,
and by c.100% as a result of UV/H2O2 (10 mg/l).
Dotson et al., 2010
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 23
UV lamp type /
Wavelength (nm)
UV dose
(mJ/cm2)
Medium Observed effect(s) Reference
LP 130-1,610 SW (untreated lake water) UV/O3 reduced formation of chloroform and chlorinated
HAAs by c. 40% at 3 mg/l O3/130 mJ/cm2.
Chin and Berube, 2005
LP 270-1,400 SW (1.8 mg/l TOC) UV/O3: UV typically reduced THM formation by 10-30%
relative to ozone alone but some samples showed an
increase.
Collivignarelli and Sorlini, 2004
MP 1,000 Sand filtered river water (1.51 mg/l TOC);
GAC filtered river water (0.86 mg/l TOC)
THMFP increased by c. 30-50% as a result of UV
alone, and by c.100% as a result of UV/H2O2 (10 mg/l).
Dotson et al., 2010
Not specified - Ultrafiltered water (with and without
secondary chlorination)
Many halogenated DBPs formed after UV/TiO2 and
chlorination, but less than when chlorine used alone;
possible formation of 3-methyl-2,4-hexanedione and
dihydro-4,5-dichloro-2(3H)furanone (recirculated in
batch reactor for 24 hr).
Richardson et al., 1996
- - Filtered river water (River Ruhr) UV/H202 initially increased THM formation before
decreasing with further increase in UV dose; small
reduction in DOC and UV254 absorbance.
Kleiser and Frimmel, 2000
Effect of UV on pre-formed DBPs: THMs
LP 0-2,200 Deionised water UV/H202: UV + 6 mg/l H2O2 did not change reaction
rates relative to UV alone. Minimal removal of
chloroform. Removal of brominated THMs increased
with increasing bromine content. Reaction rates first
order with respect to UV dose.
Chang, 2008
Effect of UV on pre-formed DBPs: HAAs
LP 0-4,400 Deionised water UV/H202: UV + 6 mg/l H2O2 did not change reaction
rates relative to UV alone. Negligible removal of
chlorinated HAAs (MCAA, DCAA, TCAA) and MBAA.
Removal of more brominated HAAs (DBAA, TBAA)
increased with increasing bromine content. Reaction
rates first order with respect to UV dose.
Chang, 2008
Note:
1. GW = groundwater, SW = surface water.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 24
2.4 Conclusions
UV is used in water treatment for disinfection at doses around 40 mJ/cm2 and in AOPs at
doses typically an order of magnitude greater.
At UV doses typically used for disinfection:
Organic DBPs (THMs, HAAs, aldehydes, carboxylic acids) do not appear to be formed
directly.
Nitrite formation may occur if nitrate is present. The likelihood, and extent of formation,
depend on the type of UV lamp, being greatest for MP lamps where wavelengths below
240 nm are not blocked and lowest for LP lamps.
Bromate is not formed by UV directly.
When UV at doses typically used for disinfection is followed by chlorination:
The formation of THMs and HAAs is unlikely to be affected but potentially may increase
by c. 10% (LP or MP).
The formation of aldehydes, carboxylic acids, TCP or HANs is unlikely to be affected.
The formation of chloropicrin and bromopicrin is likely to increase. The formation of
both is promoted by higher concentration of nitrate, while the formation of bromopicrin
is promoted by higher concentration of bromide.
The formation of cyanogen chloride is likely to increase.
The formation of chloral hydrate and halonitromethanes is likely to increase, at the
single g/l level (LP UV) or g/l level (MP UV).
The formation of nitrosamines is likely to be reduced.
When chlorination is followed by UV at doses typically used for disinfection:
There is potential for bromate formation if bromide is present.
Chlorine decay rate may increase but this effect is unlikely to be of practical
significance.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 25
When UV is applied as part of an AOP:
Some mineralisation of DOC may occur.
AOC is likely to increase.
Nitrite formation is likely to occur in the presence of nitrate.
Bromate formation will not occur with UV/H2O2 but will occur with UV/O3.
Conflicting results indicated an increase in THMFP following UV and UV/H2O2 - but also
a reduction in the formation of halogenated organic DBPs - after subsequent
chlorination.
Removal of pre-formed brominated THMs and HAAs is likely, the extent increasing with
UV dose and with bromine content. Removal of chloroform and HAAs containing only
chlorine will not occur to any appreciable extent at practicable UV doses.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 26
3. UV Treatment in Public Supplies
3.1 Introduction
Information on UV treatment in public supplies was collected by a focussed questionnaire
survey of 22 water companies in England and Wales. The questionnaire was designed to
identify the main features of existing and proposed UV treatment plants, including details of
the plant, main function, upstream and downstream treatment, and any related DBP formation
(or degradation). The survey built on a previous survey carried out by WRc in 2007.
Questionnaires were returned by 16 water companies (73% response), including nil returns
from 6 water companies that reported not using UV treatment.
Six water companies failed to respond to the questionnaire and subsequent requests,
although one company confirmed having about 45 UV units (all on groundwater sites).
3.2 Results
Results of the survey are summarised in Tables 3.1 and 3.2; returned questionnaires are
presented in Appendix B. All details of water companies and treatment works have been
anonymised.
3.3 Conclusions
The questionnaire survey identified 894 UV plants (existing and proposed) from returns from
16 water companies (including 6 nil returns) with a total UV treatment capacity of 1,492 Ml/d.
The UV treatment capacity represents approximately 23% of the production capacity of the
ten companies utilising UV (between 3-100% of capacity) and approximately 17% of the
production capacity of all 16 companies.
The UV dose used for general disinfection is typically around 40 mJ/cm2. The UV dose used
in AOPs is typically around 500-600 mJ/cm2.
UV treatment is used mostly where there is a Cryptosporidium risk and for general
disinfection, with a much smaller usage in AOPs.
UV is used most widely at small groundwater sites, although a greater water volume is treated
by fewer large UV plants at lowland surface water sites. There is little implementation of UV
for upland water sources.
4 Excluding the c. 45 UV units reported by one company that failed to respond to the questionnaire.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 27
Several DBPs were detected at sites incorporating UV: THMs, HAAs, bromate, nitrite,
chlorate, chlorite, and NDMA. Of these, only bromate (at Works A5) was directly attributed to
the use of UV.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 28
Table 3.1 Summary of UV treatment by function and source
Water
company
No. UV
plants
Volume
treated
(Ml/d)
UV treatment by function1 (Ml/d)
(No. sites in brackets)
UV treatment by source2 (Ml/d)
(No. sites in brackets) Notes
D C M GW LSW USW
A 6 354 354
a
(6)
354a
(6) -
42b
(2)
342b
(5) -
a) Includes UV treatment at 6 sites for general
disinfection & Cryptosporidium risk.
b) Includes UV treatment at one site (30 Ml/d)
supplied by GW & LSW.
B 4 28.6 28.6
a
(4) -
12.2a
(1)
2.7
(2)
12.2
(1)
13.7
(1)
a) Includes UV treatment at one site (12.2 Ml/d) for
general disinfection and advanced oxidation.
C 2 134 - 134
(2) -
84
(1)
50
(1) -
D 8 187 47.4
a,b
(3)
148.4a
(4)
27.6b
(2)
101.3c
(6)
102.1c
(3) -
a) Includes UV treatment at one site (16.4 Ml/d) for
general disinfection & Cryptosporidium risk.
b) Includes UV treatment at one site (20 Ml/d) for
general disinfection & advanced oxidation.
c) Includes UV treatment at one site (16.4 Ml/d)
supplied by GW & LSW.
E 8 52.9 52.9
(8) - -
52.9
(8) - -
F 2 4.2 4.2
(2) - -
4.2
(2) - -
G 38 98.6a
74.8b
(28)
98.6b
(23) -
98.6
(38) - -
a) Total for 14 works.
b) Includes UV treatment at 10 sites (74.8 Ml/d) for
general disinfection & Cryptosporidium risk.
H 2 107.5 - 107.5
(2) -
17.5
(1)
90
(1) -
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 29
Water
company
No. UV
plants
Volume
treated
(Ml/d)
UV treatment by function1 (Ml/d)
(No. sites in brackets)
UV treatment by source2 (Ml/d)
(No. sites in brackets) Notes
D C M GW LSW USW
J 4 49.0 46.1
(3)
2.9
(1) -
49.0
(4) - -
K 15 476.4 476.4
a
(15)
151a
(4) -
161.4
(9)
300
(5)
15
(1)
a) Includes UV treatment at 3 sites (151 Ml/d) for
general disinfection & Cryptosporidium risk.
Totals 89 1,492 1,084
(69)
996.4
(42)
39.8
(3)
613.6
(73)
896.3
(16)
28.7
(2)
Notes:
1. D = General Disinfection; C = Cryptosporidium risk; M = Micropollutants (e.g. pesticide, with UV as part of an Advanced Oxidation Process (AOP)).
2. GW = Ground Water; LSW = Lowland Surface Water; USW = Upland Surface Water.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 30
Table 3.2 Summary of UV treatment by upstream treatment, dose and DBPs detected
Water
company
Upstream pre-oxidation by source UV dose by source (mJ/cm2) DBPs
1 detected by source
GW LSW USW GW LSW USW GW LSW USW
A Pre-chlorine Pre-chlorine
Pre-ozone - 40 (min) 40 (min) -
TTHMs
Bromate2
TTHMs
Bromate
Chlorate
Chlorite
-
B Nil Nil Nil 40 40 / 500 40
THMs
Bromate
HAAs
THMs
NDMA
THMs
HAAs
C Pre-chlorine Pre-chlorine - 60 40 - THMs THMs -
D Pre-chlorine Pre-ozone - 25 / 600 40 / 500 -
THMs
Bromate
Nitrite
Chlorate
NDMA
THMs
Bromate
Nitrite
Chlorate
NDMA
-
E Nil - - 40 - -
TTHMs
Bromate
Nitrite
- -
F Nil - - 40 - - THMs - -
G Pre-chlorine - - 40 - >42 - - -
THMs
Bromate
Nitrite
Chlorate
THMs
Bromate
Nitrite
Chlorate
H Nil Nil - 45 40 - THMs THMs
J ? - - 40 - - ? - -
K Nil Pre-chlorine Nil 40 / 48 40 / 48 48 Bromate Nil Nil
Notes: 1. DBPs detected in treatment, distribution or at customers‟ taps, by regulatory or operational monitoring. 2. DBP specifically associated with UV treatment.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 31
4. Effect of UV Dosage and/or Pre-oxidation on Chemical Composition and DBP Formation
4.1 Introduction
Operating and monitoring data from a small number of water treatment works were analysed
to evaluate the effect of UV dosage and/or pre-oxidation on chemical composition and DBP
formation. Appropriate works were selected from the survey of public supplies taking into
account risk factors identified from the literature review and including:
Raw water quality (to include groundwaters and surface waters particularly containing
high levels of bromide).
Different UV sources (LP, MP, LPHO lamps) and location in the treatment stream.
Upstream and downstream treatment (particularly pre-oxidation (e.g. prechlorination)
which is likely to have the greatest impact on DBP formation).
Works were selected where data were available to evaluate effects of changes in UV dosage,
including:
Treatment streams before and after the installation of UV.
Treatment streams where UV is switched on and off.
Treatment streams where UV dose has been changed, e.g. from low dose to high dose
reflecting the installation of AOPs to remove micropollutants.
Parallel treatment streams with and without UV.
Whilst available DBP data was mostly for THMs, the following features were also sought:
Works where a more rigorous monitoring programme has been associated with the
implementation of UV (e.g. higher sampling frequencies, sampling for other DBPs such
as HAAs and bromate, etc.)
Works were UV absorbance and/or colour data (surrogate measures for chlorine
demand) are available before and after UV.
Chlorine dose/demand data are available.
A high frequency of total and individual THM data are available.
4.2 Selected works and results
Five water treatment works were visited to inspect installed UV plant and collect operating
data, to elucidate the formation of DBPs. Full reports of the site visits are included in Appendix
C; summaries of the findings are presented below.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 32
4.2.1 Works A2
Works A2 (design capacity 165 Ml/d) treats a high alkalinity canal water with moderate colour
(typically 30°H) and occasional high turbidity at around 100-110 Ml/d.
Raw water is stored prior to treatment and dosed with chlorine during April to September to
prevent zebra mussel growth; the storage tanks are aerated for THM removal. Further
treatment incorporates preozonation, coagulation (with polyaluminium chloride (PACl)),
sedimentation, RGF, ozonation, GAC, MP UV (typical dose 60-120 mJ/cm2), phosphate
dosing and final chlorination.
Precautions are taken to reduce DBP formation: sulphuric acid can be dosed upstream of
ozonation to reduce bromate formation; MP UV lamps are sleeved to reduce bromate
formation; on-site electrolytic generation of chlorine (OSEGC) uses low-bromide salt, and the
hypochlorite product is stored for no longer than 4 days.
THMs in final water show a seasonal variation, with highest concentrations in the summer –
possibly affected by changes in the nature of raw water DOC, temperature and
prechlorination. Generally, THM concentrations (<30 µg/l) have reduced since the installation
of UV in 2012, but this may reflect reduced chlorine use rather than an effect of UV.
Concentrations of bromate (up to 8 µg/l) are likely to be due to ozonation rather than UV, and
nitrite levels after UV are always low or non-detectable.
4.2.2 Works A5
Works A5 (design capacity 12 Ml/d) treats a high alkalinity, iron-rich groundwater at around 4
Ml/d. The raw water organic content is low (mean TOC 0.5 mg/l). Prior to 2013, treatment
incorporated prechlorination (for iron precipitation), contact tanks, RGF, LP UV, chlorination
and phosphate dosing. The design UV dose at 12 Ml/d is 48 mJ/cm2, but at the lower works
throughput is usually over 100 mJ/cm2.
Prior to 2013, bromate formation was an issue as a result of high-dose UV treatment of
prechlorinated water containing greater than 100 µg/l bromide. Small-scale tests showed
bromate concentrations up to 26 µg/l in post-UV treated water (raw water bromide 154 µg/l,
pre-chlorine dose 2 mg/l). Bromate in RGF filtered water measured 17 µg/l, formed as a result
of sunlight on the supernatant water. Prechlorination ceased in 2013 because of concerns
over bromate formation.
THM formation is low (typical TTHMs in final water <8 µg/l).
4.2.3 Works B1
Works B1 (design capacity 12 Ml/d) treats a low-coloured lowland reservoir water at around
8 Ml/d. The catchment is agricultural and nutrient levels in the reservoir are sufficient to cause
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 33
high algal levels during summer. Treatment incorporates pH adjustment, coagulation (ferric
sulphate), polyelectrolyte-aided sedimentation (LT22S), pH adjustment/chlorination (for
manganese removal), pressure filtration, H2O2/LP UV (for pesticide removal; typical UV dose
400 mJ/cm2), GAC, chlorination/dechlorination.
The raw water TOC shows seasonal variation up to 8 mg/l in the summer/autumn. Final water
THMs similarly show seasonal variation up to 55 µg/l, probably related to water temperature
rather than treated water TOC (which is relatively constant throughout the year). THMs
increased in distribution up to 75-85 µg/l.
A notable feature of the THM data is the very high proportion of brominated THMs in the final
water following peroxide/UV. For filtered water - and for final water prior to implementation of
peroxide/UV - trichloromethane is a higher proportion of the total THMs. Whilst the data
suggest peroxide/UV is enhancing the formation of brominated species, this cannot be stated
definitively because of the quality of the data (variation in operation and sample types).
Bromate concentrations in 2014 measured up to 3.1 µg/l at the GAC inlet, reducing to 1 µg/l in
the final water.
Single measurements for total HAAs in 2014 showed 13 µg/l leaving the works and 19 µg/l in
distribution.
4.2.4 Works B2
Works B2 treats a low-alkalinity, highly-coloured reservoir water at around 13 Ml/d. Treatment
incorporates pH adjustment, coagulation (PACl), polyelectrolyte-aided sedimentation (LT22S),
pH adjustment/chlorination (for manganese removal), RGF, chlorination. UV was installed in
2014 for general disinfection with a design dose of 40 mJ/cm2.
Comparison of DBP formation before and after the installation of UV suggests that THMs
have not increased since the installation. A single HAA measurement (55 µg/l) in 2014 was
higher than pre-UV values; bromate remained low (1.9-3.3 µg/l); and nitrite was not detected.
4.2.5 Works D2
Works D2 (design capacity 7.4 Ml/d) treats a groundwater from three borehole sources at
around 2.3-6.9 Ml/d. Water from Borehole 3 (maximum flow 3.0 Ml/d) contains pesticides and
is treated with high dose LP UV. UV treated water is blended with water from Boreholes 4 and
5 (combined maximum flow 6.2 Ml/d). A proportion of blended water is treated by ion
exchange for nitrate removal, before being blended back prior to chlorination.
Since implementation of UV, THM concentrations in distribution have been low (<20 µg/l) and
nitrite concentrations in the final water have been non-detectable (although any nitrite formed
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 34
by UV would be removed by chlorine). Initial pilot trials at the site highlighted potential
problems with nitrite from MP UV because of the high nitrate in the raw water.
No bromate data are available, but bromide in the raw water is very low and potential for
bromate formation would be expected to be negligible.
4.3 Conclusions
Operating and monitoring data from five water treatment works were analysed to evaluate any
effects of UV dosage and/or pre-oxidation. Generally, available data were limited and few
conclusions regarding effect on DBP formation can be made.
Works A2, A5 (historically) and B2 all dosed chlorine prior to UV. Bromate in excess of the
drinking water standard (10 µg/l) had been detected at Works A5 due to treatment of
prechlorinated water containing greater than 100 µg/l bromide with UV at over 100 mJ/cm2;
the high UV dose resulted from operation at less than the design flow rate. At Works B2, a
single HAA measurement (55 µg/l) exceeded values detected prior to installation of UV in
2014.
Works B1 and D2 both incorporated high-dose UV. No significant effects on DBP formation
were observed, although possible enhanced formation of brominated THMs was noted at
Works B1 (UV dose 400 mJ/cm2).
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 35
5. UV Treatment in Private Supplies
5.1 Introduction
Data on UV treatment in private supplies are collated by DWI based on returns from local
authorities (LAs). Data from 2011-2013 have been summarised below.
5.2 2011 data
In 2011, 261 LAs in England and Wales submitted data to DWI with regard to private water
supplies. In total, 22,503 regulated private supplies were identified, with the capacity to supply
247,155 Ml/yr (approximately 677 Ml/d) (DWI, 2012).
One-hundred-and-thirty-three LAs reported 2,472 private supplies incorporating UV treatment
(UVA and UVP), with the capacity to supply up to 111,474 persons with up to 143 Ml/d of
drinking water. Tables 5.1 and 5.2 provide a summary of these supplies based on the source
type and main activities for which the water is used, respectively.
Table 5.1 Summary of UV treated private supplies by water source (2011)
Water Source1,2
No. of Supplies Persons Served Capacity (m3/d)
BHW 850 (34.4%) 69,545 (62.4%) 37,099 (26.0%)
MMS 33 (1.3%) 3,391 (3.0%) 6,692 (4.7%)
MXW 130 (5.3%) 7,039 (6.3%) 86,699 (60.7%)
RNW 5 (0.20%) 75 (0.07%) 14 (0.01%)
SFW 115 (4.7%) 13,073 (11.7%) 3,371 (2.4%)
SPW 1,053 (42.6%) 15,239 (13.7%) 8,259 (5.8%)
UNK 87 (3.5%) 441 (0.40%) 128 (0.01%)
WEL 199 (8.1%) 2,671 (2.4%) 678 (0.47%)
Totals 2,472 111,474 142,940
Notes:
1. BHW = borehole; MMS = multiple sources which are a combination of borehole and spring (but not influenced by
surface water); MXW = borehole influenced by surface water; RNW = rainwater; SFW = surface water; SPW =
spring; UNK = unknown; WEL = well.
2. Not reported: EBW (estuarine or brackish water) or PMW (public supply (Regulation 8 supplies)).
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 36
Table 5.2 Summary of UV treated private supplies by water use (2011)
Main Activity for
Water Use1
No. of Supplies Persons Served Capacity (m3/d)
COMM 1,195 (48.3%) 100,212 (89.9%) 139,630 (97.7%)
DOMS 1,062 (43.0%) 10,399 (9.3%) 3,015 (2.1%)
SDDW 193 (7.8%) 572 (0.51%) 233 (0.16%)
UNKN 22 (0.89%) 290 (0.26%) 61 (0.04%)
Totals 2,472 111,474 142,940
Note:
1. COMM = commercial purposes; DOMS = domestic purposes; SDDW = single domestic dwelling with no
commercial activity; UNKN = unknown.
Table 5.1 shows that the majority of private supplies incorporating UV treatment are sourced
from springs (42.6%; 1,053) and boreholes (34.4%; 850). Boreholes account for the largest
percentage of persons served (62.4%; 69,545) and the second largest percentage of water
capacity (26.0%; 37,099 m3/d), whereas springs account for 13.7% of persons served
(15,239) and 5.8% of water capacity (8,259 m3/d). Boreholes influenced by surface water
account for the largest percentage of water capacity (60.7%, 86,699 m3/d) supplied from 130
sources.
Table 5.2 shows that approximately equal numbers of private supplies incorporating UV
treatment are used for commercial purposes (48.3%; 1,195) and domestic purposes (43.0%;
1,062). However, private supplies used for commercial purposes account for substantial
percentages of persons served (89.9%; 100,212) and water capacity (97.7%; 139,630 m3/d).
5.3 2012 data
In 2012, 272 LAs in England and Wales submitted data to DWI with regard to private water
supplies. In total, 22,984 regulated private supplies were identified, with the capacity to supply
a permanent population of 1,022,209 (DWI, 2013).
One-hundred-and-forty-nine LAs reported 2,640 private supplies incorporating UV treatment
(UVA and UVP), with the capacity to supply up to 132,953 persons with up to 707 Ml/d of
drinking water. Tables 5.3 and 5.4 provide a summary of these supplies based on the source
type and main activities for which the water is used, respectively.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 37
Table 5.3 Summary of UV treated private supplies by water source (2012)
Water Source1,2
No. of Supplies Persons Served Capacity (m3/d)
BHW 1027 (38.9%) 84,367 (63.5%) 40,375 (25.6%)
MMS 39 (1.5%) 1,793 (1.3%) 6,665 (4.2%)
MXW 136 (5.2%) 7699 (5.8%) 86,791 (55.0%)
RNW 6 (0.23%) 75 (0.06%) 15 (0.01%)
SFW 161 (6.1%) 17,454 (13.1%) 17,236 (10.9%)
SPW 1033 (39.1%) 18,806 (14.1%) 5,968 (3.8%)
UNK 86 (3.3%) 521 (0.4%) 110 (0.07%)
WEL 152 (5.8%) 2,238 (1.7%) 601 (0.38%)
Totals 2,640 132,953 157,761
Notes:
1. BHW = borehole; MMS = multiple sources which are a combination of borehole and spring (but not influenced by
surface water); MXW = borehole influenced by surface water; RNW = rainwater; SFW = surface water; SPW =
spring; UNK = unknown; WEL = well.
2. Not reported: EBW (estuarine or brackish water) or PMW (public supply (Regulation 8 supplies)).
Table 5.4 Summary of UV treated private supplies by water use (2012)
Main Activity for
Water Use1
No. of Supplies Persons Served Capacity (m3/d)
COMM 1,205 (45.6%) 119,443 (89.8%) 152,334 (96.6%)
DOMS 1,198 (45.4%) 12,719 (9.6%) 4,727 (3.0%)
SDDW 205 (7.8%) 412 (0.3%) 386 (0.24%)
UNKN 32 (1.2%) 379 (0.3%) 314 (0.20%)
Totals 2,640 132,953 157,761
Note:
1. COMM = commercial purposes; DOMS = domestic purposes; SDDW = single domestic dwelling with no
commercial activity; UNKN = unknown.
Table 5.3 shows that the majority of private supplies incorporating UV treatment are sourced
from springs (39.1%; 1,033) and boreholes (38.9%; 1,027). Boreholes account for the largest
percentage of persons served (63.5%; 84,367) and the second largest percentage of water
capacity (25.6%; 40,375 m3/d), whereas springs account for 14.1% of persons served
(18,806) and 3.8% of water capacity (5,968 m3/d). Boreholes influenced by surface water
account for the largest percentage of water capacity (55.0%; 86,791 m3/d) supplied from 136
sources.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 38
Table 5.4 shows that approximately equal numbers of private supplies incorporating UV
treatment are used for commercial purposes (45.6%; 1,205) and domestic purposes (45.4%;
1,198). However, private supplies used for commercial purposes account for substantial
percentages of persons served (89.8%; 119,443) and water capacity (96.6%; 152,334 m3/d).
5.4 2013 data
In 2013, 279 LAs in England and Wales submitted data to DWI with regard to private water
supplies5; three LAs failed to respond. Subsequently, the 2013 dataset was supplemented
with data from 2011 or 2012 for these three LAs to provide a „complete‟ picture of the nature
and type of private supplies in the UK6 (DWI, 2014).
In total for England and Wales, 48,274 private supplies were identified [England 34,221;
Wales 14,053]. A large number of these private supplies served single domestic dwellings
(SDDWs) [England 18,976 (55%); Wales 11,571 (82%)].
Local authorities are not generally required to risk assess or monitor SDDWs, and so less is
known about these supplies. The remaining 17,035 supplies [England 14,553; Wales 2,482]
require risk assessment and monitoring. Data for these monitored supplies show that 567,007
people [England 494,759; Wales 72,248] were reliant on private supplies. Upwards of 8
million people [England 7,759,937; Wales 270,398] were exposed to temporary private
supplies when attending leisure events, such as shows, concerts, etc.
The private supplies data submitted to DWI for 2013 did not include details of treatment so it
was not possible to identify supplies using UV treatment.
5.5 Nitrate and bromate
Data were provided for 2011, 2012 and 2013 identifying private supplies containing nitrate
and bromate. Summaries of supplies where nitrate and bromate equalled or exceeded
regulatory standards7 are given in Tables 5.5 and 5.6.
5 Sixty-nine councils reported no private water supplies.
6 In total, 72,312 private supplies were identified for the UK including those serving single domestic
dwellings (SDDWs).
7 Nitrate 50 mg/l; bromate 10 µg/l (DWI, 2009).
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 39
Table 5.5 Private supplies: Nitrate (mg/l)
Local Authority 2011 2012 2013
Max Mean Max Mean Max Mean
Amber Valley 75.3 52.1 51.4 35.0 - -
Anglesey 123 24.7 80.5 22.3 80.9 17.6
Arun 85.1 55.2 77.1 31.1 - -
Babergh 113 11.3 52.9 5.96 68.2 10.5
Basingstoke & Deane - - 55.6 34.0 78.8 47.2
Braintree 83.0 27.1 150 37.5 84.0 29.3
Breckland 248 23.8 - - - -
Broadland 135 21.2 - - 86.9 18.5
Calderdale - - 65.6 7.55 73.1 6.70
Carmarthenshire 81.0 14.4 - - - -
Ceredigion 76.0 11.8 90.0 10.5 207 10.6
Cherwell 82.0 24.7 70.8 64.6 76.3 32.6
Cheshire East 78.7 13.5 108 15.6 70.4 12.7
Chichester 61.2 35.66 - - - -
Colchester - - 97.5 48.5 139 64.5
Cornwall 65.4 19.3 141 25.3 169 17.5
Cotswold 99.4 43.5 - - 104 30.4
Dacorum - - - - 63.4 36.3
Daventry 67.3 36.6 - - - -
Denbighshire 128 9.76 64.1 12.9 81.5 13.5
Derbyshire Dales 59.9 19.5 68.7 16.2 67.1 20.5
Doncaster - - 55.5 37.0 89.7 44.8
Durham 58.0 5.64 - - - -
East Devon 122 26.4 311 15.5 85.0 28.5
East Dorset - - - - 65.8 38.4
East Hampshire 54.2 27.0 62.0 22.6 129 32.6
East Hertfordshire - - 108 24.2 - -
East Lindsey 93.7 15.36 60.7 21.4 90.0 14.9
East Northamptonshire - - 56.9 21.2 - -
East Riding of Yorkshire 61.2 23.1 74.3 29.6 80.0 25.9
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 40
Local Authority 2011 2012 2013
Max Mean Max Mean Max Mean
Eden 53.0 5.68 - - - -
Fareham - - 50.3 50.3 - -
Forest Heath - - 50.0 35.9 134 45.9
Gedling 72.2 24.3 - - 76.8 37.0
Guildford 67.0 67.0 65.4 63.9 67.1 49.9
Hambleton 53.2 9.55 - - - -
Harrogate 110 19.5 62.0 30.8 110 29.1
Herefordshire 176 33.0 177 35.2 168 35.5
Hertsmere 62.8 45.9 56.0 41.0 52.8 50.8
Horsham 55.0 31.3 - - 51.3 23.4
Kings Lynn & West
Norfolk
81.7 56.5 74.0 47.4 86.1 56.7
Leeds City - - 50.7 8.92 - -
Liverpool 66.8 54.7 - - - -
Malvern Hills 108 26.5 73.0 18.1 53.2 16.0
Melton - - - - 97.0 49.9
Mendip 61.0 23.0 51.0 22.4 54.0 23.9
Mid Sussex 62.9 56.4 53.5 53.5 - -
Neath & Port Talbot - - - - 150 20.6
Newcastle under Lyme - - 160 70.0 - -
New Forest - - - - 58.0 30.4
North Devon 63.9 12.3 55.4 13.9 53.2 12.4
North East Derbyshire 57.6 10.9 - - 51.0 10.1
North East Lincolnshire 55.6 22.2 - - 52.2 19.4
North Hertfordshire - - 80.4 31.0 - -
North Kesteven 64.6 10.9 - - - -
North Norfolk 129 18.6 121 19.0 130 18.7
North Somerset 64.0 23.8 - - - -
North Warwickshire - - - - 93.4 47.9
Northumberland - - - - 79.0 15.3
Norwich City 50.5 24.9 - - 53.2 25.8
NW Leicestershire 68.4 48.9 - - - -
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 41
Local Authority 2011 2012 2013
Max Mean Max Mean Max Mean
Pembrokeshire 264 23.6 - - - -
Peterborough City 125 45.3 - - - -
Purbeck - - - - 83.4 25.6
Richmondshire - - 65.4 15.6 53.3 18.5
Rutland - - - - 89.1 59.3
Ryedale 60.9 30.5 81.2 38.8 54.2 36.4
Scarborough - - 64.0 11.2 51.0 6.62
Sedgemoor 64.3 21.3 198 46.3 80.6 33.4
Selby - - - - 98.0 11.1
South Cambridgeshire 53.0 40.1 51.7 39.5 50.8 41.6
South Derbyshire 80.0 55.0 - - - -
South Gloucestershire 75.0 33.5 - - - -
South Hams 76.5 28.4 81.0 29.2 87.3 25.9
South Norfolk 103 14.1 172 22.4 120 26.1
South
Northamptonshire
71.9 44.7 60.7 29.9 74.2 34.9
South Oxfordshire - - 116 30.1 123 34.8
South Somerset 160 50.2 140 45.4 120 52.5
St Edmundsbury 80.4 38.1 97.0 14.7 109 39.4
Stafford - - - - 92.0 48.5
Staffordshire Moorlands 85.0 19.8 - - - -
Stratford-on-Avon - - 75.1 34.7 75.1 25.4
Suffolk Coastal 150 42.3 240 56.1 110 27.3
Taunton Deane 108 28.9 54.0 17.2 157 28.7
Teignbridge - - 86.8 11.1 - -
Telford & Wrekin 127 82.9 145 42.6 192 40.4
Test Valley 93.6 39.9 89.0 39.8 100 43.5
Tewkesbury 74.7 20.1 82.7 28.0 70.5 32.0
Uttlesford - - 72.0 35.1 76.0 29.9
Vale of White Horse 120 47.5 68.4 26.7 86.7 28.4
Welwyn Hatfield 57.6 38.6 66.4 57.9 81.2 70.3
West Devon - - 120 12.9 70.5 9.27
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 42
Local Authority 2011 2012 2013
Max Mean Max Mean Max Mean
West Oxfordshire 70.0 47.5 51.0 37.8 108 34.4
West Somerset 58.0 27.0 59.0 32.9 - -
Wiltshire 65.9 17.4 131 23.0 169 25.0
Winchester City 77.5 38.1 75.7 33.6 79.7 39.9
Wolverhampton 98.1 84.2 99.2 98.9 99.0 89.7
Wychavon 65.5 43.6 50.4 28.6 - -
Wyre Forest 60.2 52.9 - - - -
Table 5.5 shows that over the period 2011 to 2013, ninety-nine LAs reported concentrations
of nitrate in private supplies above the drinking water standard. Whilst this in itself is a
concern, the number of these supplies that use UV treatment is unknown. There is a
possibility that nitrate in source waters could be converted to nitrite by MP UV, but MP lamps
are typically shrouded to avoid formation of nitrite, and MP UV is probably used rarely on
private supplies other than possibly on some larger commercial supplies.
Table 5.6 Private supplies: Bromate (µg/l)
Local Authority 2011 2012 2013
Max Mean Max Mean Max Mean
Babergh 16.1 1.97 - - - -
East Hampshire - - - - 15.0 1.31
Horsham - - 17.7 2.70 11.4 1.91
Northumberland - - 12.0 2.07 - -
Powys - - 10.5 10.5 - -
South Oxfordshire - - 23.1 4.02 - -
Tunbridge Wells - - - - 14.7 7.45
Vale of White Horse - - - - 10.0 3.63
West Devon - - - - 10.7 10.0
Westminster 10.0 10.0 - - - -
Table 5.6 shows that over the period 2011 to 2013, ten LAs reported concentrations of
bromate in private supplies above the drinking water standard. Bromate is not generally found
in source waters but is formed by the oxidation of bromide. The literature shows that bromate
has been formed in chlorinated waters exposed to UV (either from UV lamps or natural
sunlight). It is unlikely that chlorine–UV is used on private supplies other than possibly on
some larger commercial supplies.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 43
5.6 Conclusions
UV treatment
In 2011 and 2012, less than 100% of LAs reported private supplies data to DWI. As a result -
and as identification of UV treatment was not compulsory - the data for this period
underestimates the full extent of UV treatment of private supplies.
The LA response to DWI gave no indication as to the design or performance of installed UV
treatment. If inadequately designed or maintained, UV units may be providing greater or
lesser than design doses. If UV doses lower than typical disinfection doses are applied
(including no dose), disinfection could be compromised which would be a greater concern
than the small risk of formation of DBPs.
In 2011 and 2012, around 55-60% of drinking water from UV treated private supplies was
sourced from boreholes influenced by surface water accounted for. Boreholes influenced by
surface water - and surface waters - are more susceptible to contamination, particularly from
microorganisms, organic precursors, nitrate and bromide (the latter two are also possible
contaminants of groundwaters). No respondents reported the use of estuarine or brackish
water sources.
Private supplies used for commercial purposes account for substantial percentages of
persons served and water capacity. In 2011 and 2012, UV treated private supplies for
commercial purposes accounted for 90% of persons served and 97-98% of water capacity.
In 2013, private supplies data submitted to DWI did not include details of treatment so it was
not possible to identify supplies using UV treatment.
Nitrate and bromate
Nitrate data for private supplies show that over the period 2011 to 2013, ninety-nine LAs
reported nitrate exceeding the drinking water standard (50 mg/l). These data were not
correlated to supplies treated by UV. Whilst exceedance of the nitrate standard is of concern,
it is unlikely that formation of nitrite (from nitrate) is a significant risk for private supplies
treated by UV.
Bromate data for private supplies show that over the period 2011 to 2013, ten LAs reported
bromate exceeding the drinking water standard (10 µg/l). These data were not correlated to
supplies treated by UV. Whilst exceedance of the bromate standard is of concern, it is unlikely
that formation of bromate (from bromide) is a significant risk for private supplies treated by
UV.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 44
6. Health Significance
6.1 Introduction
Toxicological implications for the DBPs identified in the literature review have been identified
and used to provide a measure of impact for UV treatment in public supplies and private
supplies.
There is, at present, little toxicological information on the vast majority of DBPs that have
been identified. However, the in vitro cytotoxicity and genotoxicity studies of Plewa et al.
(2012) and others have investigated the DBPs which have the potential to be formed by
reaction of chlorine and organic material with UV and these studies give an indication of
cytotoxic and genotoxic potential; increased cytotoxicity was demonstrated by the observation
of cell death in the cultured cells used in the in vitro assays, and increased genotoxicity was
demonstrated by the observation of DNA/genetic damage. These studies are described
below.
In addition, sufficient toxicological data have been located for the specific DBPs identified
through the literature review to be formed under conditions relevant for treatment in the UK,
enabling the derivation of guidance values.
6.2 Cytotoxicity and genotoxicity studies
Plewa et al. (2012) investigated whether mammalian toxicity varied in response to different
chlorination protocols, with and without LP UV (monochromatic low pressure UV) or MP UV
(polychromatic medium pressure UV) radiation (average dose 300 mJ/cm2 for both). Samples
were obtained from a pilot unit at the Ohio River Plant of the Greater Cincinnati Water Works
in the USA, and the transgenic Chinese Hamster Ovary (CHO) cell line AS52 was used for
both cytotoxicity and genotoxicity assays.
First the water quality of the samples was examined. Some nitrite formation occurred through
the MP UV unit. No difference was observed in the simulated distribution total organic
halogens (SD-TOX) between pilot influent and LP UV treated effluent (with or without
chlorine). SD-TOX of MP UV treated effluent was 30% higher than the pilot influent, where
this was increased by a further 19% when chlorine was added prior to MP UV treatment.
Cytotoxicity assays showed that, after chlorination, water samples were twice as cytotoxic as
those treated with GAC alone. Treatment with MP UV or LP UV alone reduced the cytotoxicity
(by 42 and 65%, respectively) and the authors concluded that the UV radiation degraded
some of the cytotoxic agents in the GAC-treated source water. Subsequent chlorination of UV
treated samples increased the cytotoxicity. The most cytotoxic sample of the entire study was
formed by the combination of LP UV followed by chlorination.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 45
There was a significant correlation (P<0.001) between cytotoxicity and genotoxicity. As with
cytotoxicity, chlorination of GAC-treated source water increased the genotoxicity and the
genotoxicity of the source water was reduced or eliminated with MP UV or LP UV,
respectively. Also as with cytotoxicity, chlorination in addition to UV treatment increased the
genotoxicity to above that of the GAC-treated source water. The highest level of genotoxicity
was observed with LP UV treatment and subsequent chlorination, where this level was higher
than that of chlorination alone. The authors concluded that UV plus chlorination-mediated
generation of specific classes of DBPs was the basis for the distribution of genotoxicity rather
than a general increase of TOX.
In conclusion, the lowest levels of cytotoxicity and genotoxicity were observed with
GAC-treated water exposed to UV treatment alone. With combined chlorination and UV
treatment, the lowest levels of cytotoxicity and genotoxicity were observed with
chlorination followed by MP UV radiation (Plewa et al., 2012).
In a study conducted by Lyon et al. (2014), the formation and cytotoxicity of DBPs in water
was investigated following treatment of natural organic matter (NOM) concentrates. The use
of concentrated NOM conserved volatile DBPs and allowed for direct analysis of the treated
water. Samples were treated with either MP UV radiation (dose 500 mJ/cm2; 550 W lamp)
followed by chlorine or chloramination, or with chlorination or chloramination alone, either with
or without nitrate or iodide spiking. Cytotoxicity assays were carried out using an in vitro
normal human colon cell (NCM460) assay. UV treatment prior to chlorination (unspiked
samples) did not affect cytotoxicity compared to chlorination alone, when toxicity was
expressed on the basis of dissolved organic carbon (DOC); this is contrary to the effects
observed by Plewa et al. (2012). However, nitrate-spiked UV and chlorination treated samples
were of greater cytotoxicity than nitrate-spiked samples treated with chlorine alone or
unspiked samples treated with UV and chlorine, on both a DOC and total organic halogen
basis. Cytotoxicity was also greater using samples treated with UV and chloramination
compared to chloramination alone, where the presence of iodide increased this further, using
either dose metric.
The authors concluded that the increased cytotoxicity observed was likely to be due to
a combination of factors, rather than a single DBP or class of DBPs. They also stated it
was likely that trichloronitromethane contributed to the increased cytotoxicity on the
basis of the DBPs analysed (Lyon et al., 2014).
Buchanan et al. (2006), investigated DBP formation, as well as the cytotoxicity and
mutagenicity of samples treated with UV or VUV (vacuum ultraviolet) photo-oxidation. Raw
surface water (SW) samples were collected from a reservoir system in Victoria, Australia.
Cytotoxicity assays were conducted using African green monkey kidney cells and
mutagenicity was examined using Ames assays in Salmonella typhimurium strains TA98,
TA100 and TA102. Cytotoxicity was not observed using samples treated with UV doses of
23-138 J/cm2 or with VUV doses of 16-160 J/cm
2, whilst cell death was reported in positive
controls. Similarly, mutagenicity was observed only in positive controls, other than one
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 46
positive result in strain TA98 at a VUV dose of 16 J/cm2. This result was further investigated,
and various low doses of VUV (5, 11 and 16 J/cm2) did not lead to a mutagenic response. The
authors highlighted the fact that the radiation doses used in this study are much larger than
typical UV disinfection doses (40-100 mJ/cm2). In agreement with the results from this study,
Backlund (1992) reported that treatment of lake water (natural humic water) from Finland with
UV irradiation (254 nM) alone or in combination with hydrogen peroxide (H2O2) did not result
in mutagenic activity in Salmonella typhimurium strains TA97, TA98 and TA100 (Backlund,
1992; Buchanan et al., 2006).
In summary, no significant cytotoxicity or genotoxicity was observed with samples of
raw reservoir surface water treated with UV or VUV at doses of 23-138 and
16-160 J/cm2, respectively. The authors noted that the doses used in this study are
significantly higher than typical UV disinfection doses In a separate study, no
mutagenicity was observed with samples of lake water (natural humic water) treated
with UV or UV in combination with H2O2.
Martijn et al. (2014) attempted to trace nitrogenous DBPs (N-DBPs) formed after MP UV
treatment. Positive results were reported in an Ames test using strain TA98 without metabolic
activation, after MP UV/H2O2 treatment at a water treatment plant (WTP) in Heemskerk, The
Netherlands (doses not reported). Effluent from the first reactor showed a genotoxic response
2.5 times higher than influent treated with H2O2 alone. Effluent from subsequent reactors
(second to fifth) showed increasing positive responses, at levels slightly above those of the
positive control. A positive correlation was observed between the number of positive wells in
the Ames test and nitrite formation (due to photolysis of nitrate).
In a second study, bench-scale MP UV experiments were conducted using commercially
available artificial water (IHSS Pony Lake NOM) containing 2.5 mg C/l, either with or without
nitrate at a practical concentration of 10 mg NO3/l. In these experiments, UV doses of
40 mJ/cm2 (disinfection) or 600 mJ/cm
2 (UV/H2O2 treatment, with 6 ppm H2O2) were used,
and Ames tests were similarly carried out using strain TA98 without metabolic activation. The
response of MP UV treated water was similar to that of the blank, regardless of the treatment
protocol. However, the addition of nitrate led to an increase in the Ames response, where this
increase was greater with the UV AOP treatment (approximately 4-fold increase in response)
compared to the UV disinfection treatment (approximately 3-fold increase), although these
responses were still below that of the positive control.
In subsequent experiments, using the same artificial water (2.5 mg C/l) with 10 mg NO3/l
treated with MP UV at a dose of 600 mJ/cm2, many nitrogen-containing by-products were
detected following analysis by mass spectroscopy. The identities of three of these by-products
were confirmed to be 2-methyoxy-4,6-dinitrophenol, 4-nitrocatechol and 4-nitrophenol. Three
additional unconfirmed by-products were reported as 3-hydroxy-4-nitrobenzoic acid,
5-nitrovanillin and 2,4-dinitrophenol. Additional data showed that Ames response is increased
(both with and without metabolic activation) after MP UV treatment, but that after
“conventional” post-treatment the Ames response is reduced to below the level of that
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 47
observed before MP UV treatment. This corresponds with an observed increase of nitrogen-
containing by-products after MP UV treatment, but a reduction in the level of by-products after
post-treatment (no further details available).
The data from this study indicate that the genotoxic responses observed in Ames
assays may be due to the sum of multiple nitrogen-containing by-products formed at
low concentrations after MP UV treatment of nitrate-containing waters. However,
conventional post-treatment appears to remove these genotoxic compounds that are
formed. Note that these results were reported at a conference presentation, and are not
yet available as a peer-reviewed publication, and therefore only limited details were
available.
Schmalz et al. (2014) investigated the effect of different treatment processes on DBP
formation, cytotoxicity and genotoxicity. Pilot swimming pool water (with added humic acid in
order to better simulate swimming pool conditions) was subjected to seven different treatment
protocols. These protocols and the results of the cytotoxicity and genotoxicity assays (assay
details not available) are shown in Table 6.1 (details of the assays used not reported).
Table 6.1 Toxicity for different treatment processes
Number Treatment protocol Cytotoxicity Genotoxicity
1 Coagulation (0.07 g/m
3 alum); Sand filtration;
GAC filtration; Chlorination (0.5 mg/l) - -
2 Coagulation; Sand filtration; LP UV (340 W/m
2);
Chlorination - +
3 Coagulation; Sand filtration; MP UV
(4,200 W/m2); Chlorination
(+) +
4 Coagulation; Ultrafiltration; LP UV; Chlorination + -
5 Coagulation; Ultrafiltration; MP UV; Chlorination + +
6 Coagulation; PAC (1.5 g/m
3, 40 seconds);
Ultrafiltration; Chlorination - -
7 Coagulation; PAC; Sand filtration; Chlorination - -
Notes:
- Negative; (+) Induction factor between 1.2 and 1.3; + Induction factor > 1.3
(control: tap water from Bad Elster, Germany).
No cytotoxicity or genotoxicity was observed with any of the control treatments, without UV.
Both cytotoxicity and genotoxicity were observed with the two protocols using MP UV (3 and
5; 4,200 W/m2) in combination with either sand filtration or ultrafiltration. With LP UV
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 48
(340 W/m2), genotoxicity only was observed with protocol 2 (in combination with sand
filtration) and only cytotoxicity was observed with protocol 4 (in combination with
ultrafiltration). Levels of the DBP trichloramine were significantly increased using protocols 3
and 5, with MP UV (approximately 4-fold increase). Levels were also increased with
protocols 2 and 4, with LP UV treatment, but by a lower amount (approximately 3- and 1.5-
fold increases, respectively).
In summary, the use of UV treatment (particularly MP UV) led to an increase in the
cytotoxicity and genotoxicity of pilot swimming pool water, and in levels of the DBP
trichloramine. These results further elucidate the effects observed by Plewa et al.
(2012) with UV treatment and chlorination. Note that these results were reported at a
conference presentation, and are not yet available as a peer-reviewed publication, and
therefore only limited details were available.
Zoeteman et al. (1982) compared alternatives to chlorine for the disinfection of stored River
Rhine water in a pilot-plant study. Using the Ames assay and Salmonella typhimurium strain
TA98 (with and without metabolic activation), increased mutagenicity was observed after
treatment with either chlorine dioxide or chlorine, but ozonation reduced the mutagenic
activity. When UV was applied at a dose of 120 mJ/cm2, no significant change to mutagenicity
was observed relative to the untreated raw water, and no significant mutagenicity was
observed with any treatment using strain TA100.
A study by Heringa et al. (2011) aimed to investigate the genotoxicity of water following
UV/H2O2 treatment and GAC filtration. Pre-treated surface water from three locations (two in
The Netherlands and one in Ohio, USA) was treated with MP UV/H2O2 followed by GAC
treatment. Samples were taken before and after each treatment step, and genotoxicity was
examined (with and without metabolic activation) using the Comet assay in HepG2 human
liver cells and in the Ames II assay (a modified version of the classic Ames assay).
Pre-treatment protocols varied between locations: At the US site, pre-treatment consisted of
coagulation (aluminium sulphate and polyDADMAC8), sedimentation, pH correction (calcium
oxide) and rapid sand filtration; the first site in The Netherlands used coagulation (iron
sulphate), sedimentation, microsieves and rapid sand filtration, and the second site used a
2-6 day reservoir residence time followed by coagulation (iron chloride sulphate),
sedimentation and rapid sand filtration.
No genotoxicity was observed in any water sample following MP UV/H2O2 treatment in either
the Comet assay or the Ames II assay using the strain TAMix, which is a combination of six
different strains. However, significant increases in mutations (described as “low genotoxicity”)
were observed with the TA98 strain both with (one location) and without (all three locations)
metabolic activation. Genotoxicity was also observed using samples treated only with MP UV,
8 Cationic polymer (poly-diallyldimethylammonium chloride).
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 49
to a higher level than those treated also with H2O2. The authors indicated that the observed
response in strain TA98 but not TAMix indicated that the compounds in the samples were
generating frame-shift mutations, rather than base-pair substitutions. Subsequent GAC
treatment of MP UV/H2O2 treated water reduced genotoxic activity to the level of the negative
control in samples from two of the three locations. Whilst a slight genotoxic response was still
observed in strain TA98 (with metabolic activation) using the sample from the third location,
this response was less than was observed in the sample which did not undergo GAC
treatment. Preliminary results using samples from two of the locations showed a much lower
or no genotoxic response following LP UV/H2O2 treatment, compared to MP UV/H2O2
treatment.
The authors concluded that the observed genotoxic response in water samples from
three different locations indicated that the genotoxic compounds were formed from
ubiquitous water components, such as NOM. It was also concluded that no health risks
are expected provided that UV/H2O2 treatment is followed by GAC filtration. The
authors also noted that the UV dose usually applied during disinfection is typically 10-
15 times lower than the dose used in this study (Heringa et al., 2011).
Micronucleus assays have also been used to characterise the mutagenic response following
UV treatment, although, mixed results have been reported. Helma et al. (1994) reported a
dose-dependent increase in micronuclei in the Tradescantia plant using groundwater exposed
to UV under laboratory conditions (highest dose, 1500 J/m2 (150 mJ/cm
2)), where this
clastogenic response was only observed transiently with a reported half-life of approximately
1 day. However, following treatment of groundwater samples (from different locations in
Austria) with LP UV radiation (254 nm; 800 J/m2 (80 mJ/cm
2)), no genotoxic effects were
observed in micronucleus assays with the Tradescantia plant or primary rat hepatocytes. Only
one weak positive result was reported in an Ames assay with strain TA98 without metabolic
activation (negative in strains TA100 and TA102) (Haider et al., 2002).
The results discussed above are summarised in Table 6.2.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 50
Table 6.2 Summary of cytotoxicity and genotoxicity studies
Treatment protocol UV dose
(mJ/cm2)
Sample details Assay(s) Results Reference
UV 23-138 Raw SW from a
reservoir system in
Victoria, Australia
African green monkey
cells (cytotoxicity)
Ames assays in
Salmonella
typhimurium strains
TA98, TA100 and
TA102 (genotoxicity)
No cytotoxicity or genotoxicity in
treated samples.
Buchanan et al.,
2006
VUV 16-160 No cytotoxicity in treated samples.
One positive genotoxicity result in
strain TA98. When investigated
further, no positive results
observed at various low doses (5,
11, 16)
UV 120 Stored River Rhine
water
not reported No significant change in
mutagenicity, compared to
untreated water
Zoeteman et al.,
1982
GAC + MP UV or LP
UV
300 (average) From a pilot unit at the
Ohio River Plant
(Greater Cincinnati
Water Works, USA)
Chinese Hamster
Ovary cell line AS52
(cytotoxicity and
genotoxicity)
Reduced cytotoxicity and
genotoxicity compared to GAC
treatment alone
Plewa et al., 2012
GAC + Cl2
GAC + MP UV + Cl2
GAC + LP UV + Cl2
Increased cytotoxicity and
genotoxicity compared to GAC
treatment alone
Most cytotoxic sample:
GAC + LP UV + Cl2
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 51
Treatment protocol UV dose
(mJ/cm2)
Sample details Assay(s) Results Reference
MP UV + Cl2
(unspiked)
500 NOM concentrates normal human colon
cell (NCM460) assay
(cytotoxicity only)
No effect on cytotoxicity compared
to Cl2 alonea.
Lyon et al., 2014
MP UV + Cl2
(nitrate-spiked)
Greater cytotoxicity than unspiked
samples, or nitrate-spiked
samples with Cl2 aloneb.
MP UV + chloramine Greater cytotoxicity compared to
chloramine alone; further
increased by iodide spiking.
UV (254 nm)
UV + H2O2
not reported Lake water (natural
humic water) from
Finland
Ames assays in
Salmonella
typhimurium strains
TA97, TA98 and
TA100
No mutagenic activity with either
treatment condition
Backlund, 1992;
cited in Buchanan
et al., 2006
MP UV + H2O2 not reported WTP in Heemskerk,
The Netherlands
Ames assays in
Salmonella
typhimurium strain
TA98 (without
metabolic activation)
Increasing genotoxic response
with effluent from 1st-5th reactors;
greater than influent treated only
with H2O2
Martijn et al., 2014
MP UV
MP UV + H2O2
40
600
Artificial water (IHSS
Pony Lake NOM)
Genotoxic response on the
addition of nitrate
MP UV 600 Genotoxic response reduced
following post-treatment
Coagulation + sand
filtration + LP UV +
chlorination
340 W/m2 Pilot swimming pool
water (with added
humic acid)
No details reported Increased genotoxicity
Negative for cytotoxicity
Schmalz et al.,
2014
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 52
Treatment protocol UV dose
(mJ/cm2)
Sample details Assay(s) Results Reference
Coagulation +
ultrafiltration + LP UV
+ chlorination
Increased cytotoxicity
Negative for genotoxicity
Coagulation + sand
filtration/ultrafiltration
+ MP UV +
chlorination
4,200 W/m2 Increased genotoxicity and
cytotoxicity
No cytotoxicity or genotoxicity
when using the three protocols
without UV
MP UV/H2O2 400 (Ohio site);
550 or 560 (two
sites in The
Netherlands,
respectively)
Pre-treated SW from
three locations (two in
The Netherlands and
one in Ohio, USA)
Comet assay in
HepG2 human liver
cells and Ames II
assay using strains
TA98 and TAMix
(genotoxicity)
No genotoxicity in comet assay or
TAMix. Low genotoxicity in TA98
Heringa et al.,
2011
MP UV only Genotoxicity observed, to a higher
level than with H2O2 treatment
MP UV/H2O2 + GAC Reduced genotoxicity compared
to samples without GAC treatment
LP UV/H2O2 (two
locations only)
Lower or no genotoxic response
compared to MP UV/H2O2
treatment.
UV (laboratory
conditions)
1,500 (highest
dose)
GW Micronucleus assay in
the Tradescantia
plant.
Transient dose-dependent
increase in micronuclei (half-life of
approximately 1-day).
Helma et al., 1994
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 53
Treatment protocol UV dose
(mJ/cm2)
Sample details Assay(s) Results Reference
LP UV (254 nm) 800 GW from various
locations in Austria
Micronucleus assay in
the Tradescantia plant
and primary rat
hepatocytes; Ames
assay in strains TA98,
TA100 and TA102
No micronuclei formation
observed.
Weak positive genotoxic response
in strain TA98 without metabolic
activation (negative in strains
TA100 and TA102).
Haider et al., 2002
UV 23-138 J/cm2 Raw SW from a
reservoir system in
Victoria, Australia
African green monkey
cells (cytotoxicity)
Ames assays in
Salmonella
typhimurium strains
TA98, TA100 and
TA102 (genotoxicity)
No cytotoxicity or genotoxicity in
treated samples.
Buchanan et al.,
2006
VUV 16-160 J/cm2 No cytotoxicity in treated samples.
One positive genotoxicity result in
strain TA98. When investigated
further, no positive results
observed at various lower doses
(5, 11 and 16 J/cm2)
Notes:
a: When expressed on the basis of dissolved organic carbon (DOC).
b: On both a DOC and total organic halogen basis.
NOM: Natural organic matter.
VUV: Vacuum ultraviolet.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 54
6.3 Derivation of guidance values
In addition to searching for studies investigating the changes in cytotoxicity and mutagenicity
upon using different UV treatment protocols, guidance values have also been derived for
specific DBPs of concern that were identified through the literature review (Task 1) to be
formed under conditions relevant for treatment in the UK (Table 6.3). The specific DBPs
identified were bromate, chloral hydrate, chloropicrin, cyanogen chloride and nitrite.
Standards are available in the UK for bromate and nitrite, and so these have been used as
the respective guideline values. The World Health Organization (WHO) has set health-based
values for both chloral hydrate and cyanogen chloride. These are not formal guidelines, but
can nevertheless be used for guidance purposes, to give an indication of the levels below
which adverse health effects are not anticipated.
There are currently no drinking water standards available for chloropicrin in the UK, and WHO
has not derived a Guideline for Drinking-water Quality (GDWQ) or any health-based values.
However, in 2011 the European Food Safety Authority (EFSA) derived an Acceptable Daily
Intake (ADI) for chloropicrin in food. Using this ADI as a Tolerable Daily Intake (TDI), a
guidance value for chloropicrin can be derived, assuming a 60 kg adult drinking 2 litres of
water per day and allocating 20% of the TDI to water. The use of 20% allocation is similar to
the lifetime exposure usually used in standards and guideline values derived by authoritative
bodies such as WHO.
Table 6.3 Guideline values for DBPs identified in the literature review
DBP Reference value TDI Guidance value
(µg/l)
Bromate - - 10 (UK standard;
DWI, 2012)
Chloral hydrate LOAEL
13.5 mg/kg bw/day
Based on a 2-year
drinking water study in
mice
0.0045 mg/kg bw/day
Derived by WHO
100 (WHO health-
based value but not
a formal guideline)a
Chloropicrin NOAEL
0.1 mg/kg bw/day
(EFSA, 2011)
Based on a 2-year
(chronic) rat study
0.001 mg/kg bw/day
(1 µg/kg bw/day)
(EFSA, 2011)
ADI derived by EFSA
6
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 55
DBP Reference value TDI Guidance value
(µg/l)
Cyanogen chloride NOAEL
4.5 mg/kg bw/day
(cyanide)
Based on a 13-week
drinking water study in
rats
0.045 mg/kg bw/day
(as cyanide)
reported to correspond
to 0.11 mg/kg bw/day
as cyanogen chloride
600 (as cyanogen
chloride; WHO
health-based value
but not a formal
guideline)b
Nitrite - - 500 (UK standard;
DWI, 2012)c
Notes:
a: In 2005, WHO calculated a health-based value of 100 µg/l for chloral hydrate based on 80% allocation of the TDI
to water (since most exposure to chloral hydrate is from drinking water). However, since they reported that chloral
hydrate usually occurs in drinking water at concentrations well below those of health concern, they did not set a
formal guideline value (WHO, 2005; 2011).
b: In 2009, WHO reported that cyanogen chloride occurs in drinking-water at concentrations well below those of
health concern. Therefore, WHO did not derive a formal guideline value, but instead they derived a health-based
value based on cyanide, for guidance purposes (WHO, 2011).
c: 100 µg/l at the treatment works.
ADI: Acceptable Daily Intake.
EFSA: European Food Safety Authority.
NOAEL: No Observed Adverse Effect Level.
WHO: World Health Organization.
6.4 Conclusions
A number of in vitro studies have been conducted investigating changes in cytotoxicity and
genotoxicity following treatment with UV at a range of doses. Note that in vitro studies are
frequently used as useful screening tools where there is a lack of data from other sources.
However, as such, effects observed may not necessarily translate to in vivo effects, and
results should be interpreted with caution. In these particular studies, there has also been no
comprehensive identification of the chemicals formed which give rise to the observed effects
with UV, chlorination and/or NOM.
Conflicting results have been reported regarding the effect of UV treatment. In many cases,
no significant increase in genotoxicity or mutagenicity was observed. However, positive
responses have been demonstrated under certain conditions, for example with the use of high
doses (frequently higher than those typically used at treatment works), in the presence of
nitrate, and where UV treatment is used in combination with other treatment processes such
as chlorination. For example, the studies of Plewa et al. (2012) indicate the possibility of an
increase in cytotoxicity and genotoxicity where UV treatment is followed by chlorination, but
also show that reversing the order of these processes, i.e. chlorination followed by UV
treatment, reduces the cytotoxicity and genotoxicity observed with chlorination alone. Several
studies have also reported that post-treatment, for example with GAC, appears to reduce
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 56
genotoxic compounds which may be formed during UV treatment and that no health risks are
expected provided that UV/H2O2 treatment is followed by GAC.
In addition, guidance values have been derived for specific DBPs identified through the
literature review to be formed under conditions relevant for treatment in the UK. UK standards
currently exist for bromate and nitrite, and the World Health Organization have derived health-
based values for chloral hydrate and cyanogen chloride which, whilst not formal guidelines,
give an indication of the concentrations below which adverse health effects are not
anticipated. A guidance value has also been derived for chloropicrin based on an Acceptable
Daily Intake (ADI) derived by the European Food Safety Authority (EFSA).
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 57
7. Future Research
7.1 Public supplies
Existing operating and monitoring data from water treatment works with regard to UV
treatment and DBP formation is limited. In order to collate a more extensive dataset, a series
of laboratory- and/or pilot-scale tests is proposed that will provide a structured approach for
investigating UV-related DBPs formed under typical UK water treatment conditions.
Laboratory-scale tests should be adequate to investigate the formation of DBPs; pilot-scale
tests would provide more realistic results but would be much more expensive.
Three types of water should be investigated:
Upland surface water with moderate-high colour, including both high and low
manganese.
Lowland surface water, both river (with upstream sewage discharges) and reservoir
(high algae) derived.
Low TOC groundwater, with and without high manganese.
The reason for the inclusion of high manganese waters is to investigate the impact of
additional chlorination and pH increase for manganese removal.
For the surface waters, both organic DBPs and bromate should be investigated. For the
groundwaters, only bromate is of interest. Nitrite formation from nitrate by UV is already well
understood, so is not included in the investigations.
The proposed treatment stages and analyses for investigation are illustrated in Figures 7.1,
7.2 and 7.3, and are summarised in Table 7.1. For the lowland surface waters and
groundwater, both AOP UV/peroxide and disinfection UV are included; for the upland surface
water only disinfection UV is included because pesticide removal is rarely a main
consideration for this type of water. For some of the tests coagulation should be carried out at
both an optimal dose (determined from jar tests) and a sub-optimal dose to provide lower
TOC (and DBP precursor) removal. Final chlorination should be carried out with 1-hour and
24-hour contact times to simulate treatment and distribution conditions.
The lowland reservoir water tests include spiking of bromide, to investigate formation of
bromate and brominated THMs/HAAs, and iodide to investigate iodinated THM formation. The
groundwater tests include spiking of bromide to investigate bromate formation.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 58
Figure 7.1 Upland surface waters and treatment
adjustment (sodium hydroxide)(for manganese removal)
Upland surface water withhigh colour
Coagulation (optimal and
sub-optimal dose),clarification and filtration
Upland surface water withhigh colour and manganese
Coagulation (optimal dose)
and clarification
Chlorination and pH
Filtration UV disinfection
Chlorination with
1 hour and 24 hourscontact time
DBP measurement
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 59
Figure 7.2 Lowland surface waters and treatments
Pre-ozonation
Lowland river water withupstream sewage inputs
Lowland reservoir withhigh algae
Lowland reservoir withhigh algae spiked with
bromide / iodide
GACAOP (UV/peroxide)
(* disinfection dose)
Ozonation
Coagulation (optimal and sub-optimal dose), clarification and filtration
*UV
DBP measurement
Chlorination with1 hour and 24 hours
contact time
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 60
Figure 7.3 Groundwater and treatment
Chlorination /
filtration(for Mn removal)
Bromate measurement
Chlorination with1 hour and 24 hours
contact time
AOP (UV/peroxide)
(* disinfection dose)*UV
Bromide spike
Groundwater withlow TOC
Bromide spike
Groundwater withlow TOC and manganese
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 61
Table 7.1 Summary of proposed small-scale investigations
Water type Water treatment DBPs of interest
Upland surface water with high
colour
Chemical coagulation, clarification, filtration, chlorination THMs, HAAs, bromate
Chemical coagulation, clarification, filtration, UV, chlorination
Upland surface water with high
colour and high manganese
Chemical coagulation, clarification, chlorination/pH increase, filtration,
chlorination
THMs, HAAs, bromate
Chemical coagulation, clarification, chlorination/pH increase, filtration,
UV, chlorination
Lowland river water with upstream
sewage inputs
Coagulation, clarification, filtration, chlorination THMs, HAAs, bromate, N-
containing DBPs Coagulation, clarification, filtration, UV, chlorination
Coagulation, clarification, filtration, ozonation, GAC, chlorination
Coagulation, clarification, filtration, ozonation, GAC, UV, chlorination
Lowland reservoir water with high
algae, with and without spiked
bromide and iodide
Coagulation, clarification, filtration, chlorination THMs, HAAs, bromate, N-
containing DBPs, iodinated DPBs Coagulation, clarification, filtration, UV, chlorination
Coagulation, clarification, filtration, ozonation, GAC, chlorination
Coagulation, clarification, filtration, ozonation, GAC, UV, chlorination
Each of the above preceded by preozonation
Low TOC groundwater with and
without spiked bromide
Chlorination Bromate
UV, chlorination
Low TOC groundwater with high
manganese, with and without
spiked bromide
Chlorination/pH increase, filtration, chlorination Bromate
Chlorination/pH increase, filtration, UV, chlorination
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 62
7.2 Private supplies
The data currently collected by LAs and reported to the DWI has little value in terms of
evaluating risks of formation of DBPs as a result of UV treatment.
The DBPs of most concern would be nitrite (from nitrate for MP UV) and bromate (from
bromide in prechlorinated water), although the risk of formation of both would be small for
well-designed systems.
Risk assessments carried out by LAs should aim to identify private supplies most at risk of
failing to meet water quality standards, including potential formation of DBPs. It is proposed
that the information collected by LAs should identify:
Estuarine or brackish water sources9.
UV lamp type (LP or MP).
Supplies that are chlorinated prior to UV.
Concentrations of nitrate and bromate in drinking water9.
9 Data currently collected.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 63
8. Conclusions
8.1 Literature review
UV is dosed for disinfection at around 40 mJ/cm2 and in AOPs at an order of magnitude
greater.
Direct formation of nitrite (from nitrate) may occur at wavelengths below 240 nm, particularly
for MP UV, but lamps can be treated to block these wavelengths.
Where chlorination is followed by UV, there is evidence of bromate formation if bromide is
present in the chlorinated water.
Where UV at doses typically used for disinfection is followed by chlorination, there is some
evidence of increased formation of chloropicrin, bromopicrin, cyanogen chloride, chloral
hydrate, and halonitromethanes.
Where UV at doses typically used for AOPs is followed by chlorination, there is some
evidence of increased THMFP but conflicting research also indicates reduced formation of
halogenated organic DBPs.
8.2 Public supplies
A questionnaire survey identified 89 UV plants (existing and proposed) from returns from 16
water companies (including 6 nil returns) with a total UV treatment capacity of 1,492 Ml/d. The
UV treatment capacity represents approximately 23% of the production capacity of the ten
companies utilising UV (between 3-100% of capacity).
UV treatment is used mostly where there is a Cryptosporidium risk and for general
disinfection, with a much smaller usage in AOPs.
UV is used most widely at small groundwater sites, although a greater water volume is treated
by fewer large UV plants at lowland surface water sites. There is little implementation of UV
for upland water sources.
8.2.1 Effects of UV dosage and/or pre-oxidation
Operating and monitoring data from five water treatment works were analysed to evaluate any
effects of UV dosage and/or pre-oxidation. Generally, available data were limited and few
conclusions regarding effect on DBP formation can be made.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 64
Bromate in excess of the drinking water standard (10 µg/l) had been detected at one works
due to treatment of prechlorinated water containing greater than 100 µg/l bromide with UV at
over 100 mJ/cm2; the high UV dose resulted from operation at less than the design flow rate.
No significant effects on DBP formation were observed as a result of high-dose UV, although
possible enhanced formation of brominated THMs was noted at one works.
8.3 Private supplies
The full extent of UV treatment of private supplies is unclear from LA returns to DWI. In 2013,
private supplies data submitted to DWI did not include details of treatment so it was not
possible to identify supplies using UV treatment.
The LA returns to DWI for 2011 and 2012 gave no indication as to the design or performance
of installed UV treatment. It is unlikely that formation of DBPs is a significant risk for UV
treated private supplies. If UV doses lower than design doses are applied, disinfection could
be compromised which would be of greater concern than the small risk of formation of DBPs.
In 2011 and 2012, boreholes influenced by surface water accounted for the largest
percentage of UV treated water capacity. Boreholes influenced by surface water - and surface
waters - are more susceptible to contamination, particularly from microorganisms, organic
precursors, nitrate and bromide.
UV treated private supplies used for commercial purposes account for substantial
percentages of persons served and water capacity. In 2011 and 2012, UV treated private
supplies for commercial purposes accounted for 90% of persons served and 97-98% of water
capacity.
8.4 Health effects
Conflicting results have been reported regarding the effect of UV in water treatment. In many
cases, no significant increase in genotoxicity or mutagenicity was observed. However,
positive responses have been demonstrated under certain conditions, for example with the
use of high UV doses (frequently higher than those typically used at treatment works), in the
presence of nitrate, and where UV treatment is used in combination with other treatment
processes such as chlorination. Several studies have also reported that post-treatment, for
example with GAC, appears to reduce genotoxic compounds which may be formed during UV
treatment.
Guidance values have been derived for specific DBPs formed under conditions relevant for
water treatment in the UK, giving an indication of the concentrations below which adverse
health effects are not anticipated.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 65
References
Backlund (1992). Degradation of aquatic humic material by ultraviolet light. Chemosphere, 25 (12),
pp1869-1878.
Bensalah, N., Liu, X. and Abdel-Wahab, A. (2013). Bromate reduction by ultraviolet irradiation using
medium pressure lamp. International Journal of Environmental Studies, 70, (4), pp568-582.
Buchanan, W., Roddick, F. and Porter, N. (2006). Formation of hazardous by-products resulting from
the irradiation of natural organic matter: comparison between UV and VUV irradiation. Chemosphere,
63 (7), pp1130-1141.
Campbell, A. (2011). United Utilities Operational Experience with UV Disinfection. Presentation to
IUVA, London.
Chang, H.J. (2008). Oxidation of disinfection by-products and algae-related odorants by UV/H2O2. PhD
Dissertation, Virginia Polytechnic Institute and State University, Blacksburg, Virginia, USA.
Chin, A. and Berube, P.R. (2005). Removal of disinfection by-product precursors with ozone-UV
advanced oxidation process. Water Research, 39, (10), pp2136-2144.
Choi, Y. and Choi, Y-J. (2010). The effects of UV disinfection on drinking water quality in distribution
systems. Water Research, 44, pp115-122.
Collivignarelli, C. and Sorlini, S. (2004). AOPs with ozone and UV radiation in drinking water:
contaminants removal and effects on disinfection by-products formation. Water Science and
technology, 49, (4), pp51-56.
Chu. W., Gao, N., Yin, D., Krasner, S.W. and Mitch, W.A. (2014). Impact of UV/H2O2 pre-oxidation on
the formation of haloacetamides and other nitrogenous disinfection by-products during chlorination.
Environmental Science and Technology, 48, (20), pp12190-12198.
Dotson, A.D., Keen, V.S., Metz, D. and Linden, K.G. (2010). UV/H2O2 treatment of drinking water
increases post-chlorination DBP formation. Water Research, 44, (12), pp3703-3713.
DWI (2009). The Private Water Supplies Regulations 2009, SI 2009 No. 3101. Drinking Water
Inspectorate.
DWI (2012a). Drinking Water 2011. Private Water Supplies in England. Drinking Water Inspectorate.
(http://dwi.defra.gov.uk/about/annual-report/2011/private-england.pdf)
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 66
DWI (2012b). Drinking Water 2011. Private Water Supplies in Wales. Drinking Water Inspectorate.
(http://dwi.defra.gov.uk/about/annual-report/2011/private-wales.pdf)
DWI (2013). Drinking Water 2012. Private Water Supplies in England, Drinking Water Inspectorate.
DWI (2014). Drinking Water 2013. Private Water Supplies in England, Drinking Water Inspectorate.
EFSA (2011) Conclusion on the peer review of the pesticide risk assessment of the active substance
chloropicrin. European Food Safety Authority. EFSA Journal 9 (3), p2084.
Haider, T., Sommer, R., Knasmüller, S., Eckl, P., Pribil, W., Cabaj, A. and Kundi, M. (2002). Genotoxic
response of Austrian groundwater samples treated under standardized UV (254 nm): disinfection
conditions in a combination of three different bioassays. Water Research, 36 (1), pp25-32.
Helma, C., Sommer, R., Schulte-Hermann, R. and Knasmüller, S. (1994). Enhanced clastogenicity of
contaminated groundwater following UV irradiation detected by the Tradescantia micronucleus assay.
Mutat Research, 323 (3), pp93-98.
Heringa, M.B., Harmsen, D.J., Beerendonk, E.F., Reus, A.A., Krul, C.A., Metz, D.H. and Ijpelaar, G.F.
(2011). Formation and removal of genotoxic activity during UV/H2O2-GAC treatment of drinking water.
Water Research, 45 (1), pp366-374.
Hofman, C.H.M., Harmsen, D.J.H. and v. Leerdam, R. (2010). Feasibility study of combined UV and
ozone system (DOPFR-UV). BTO 2010.03. KWR.
Huang, X., Gao, N. and Deng, Y. (2008). Bromate ion formation in dark chlorination and
ultraviolet/chlorination processes for bromide-containing water. Journal of Environmental Sciences, 20,
pp246-251.
Ijpelaar, G.F., van der Veer, B., Medema, G.J. and Kruithof, J.C. (2005). By-product formation during
UV disinfection of a pre-treated surface water. Journal of Environmental Engineering and Science, 4,
(S1), ppS51-S56.
Ijpelaar, G.F., Harmsen, J.H. and Heringa, M. (2007). UV disinfection and UV/H2O2 oxidation: by-
product formation and control. TECHNEAU Report D2.4.1.1.
Kashinkunti, R.D., Linden, K.G., Shin, G-A., Metz, D.H., Sobsey, M.D., Moran, M.C. and Samuelson,
A.M. (2004). Investigating multibarrier inactivation for Cincinnati – UV, By-products, and biostability.
Journal American Water Works Association, 96, (6), pp114-127.
Kishimoto, N. and Nakamura, E. (2012). Bromate formation characteristics of UV irradiation, hydrogen
peroxide addition, ozonation, and their combined processes. International Journal of Photoenergy,
2012, Article ID 107293.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 67
Kleiser, G. and Frimmel, F.H. (2000). Removal of precursors for disinfection by-products (DBPs) –
differences between ozone- and OH-radical-induced oxidation. Science of the Total Environment, 256,
(1), pp1-9.
Liberti, L., Notarnicola, M. and Petruzzelli, D. (2002). Advanced treatment for municipal wastewater
reuse in agriculture. UV disinfection: parasite removal and by-product formation. Desalination, 152,
pp315-324.
Linden, K.G., Dotson, A.D., Weinberg, H.S., Lyon, B., Mitch, W.A. and Shah, A. (2012). Impact of UV
location and sequence on by-product formation. Water Research Foundation, Denver, Colorado.
Liu, W., Andrews, S.S., Bolton, J.R., Linden, K.G., Sharpless, C. and Stefan, M. (2002). Comparison of
disinfection by-product (DBP) formation from different UV technologies at bench scale. Water Science
and Technology: Water Supply, 2, (5-6), pp515-521.
Liu, W., Cheung, L-M., Yang, X. and Shang, C. (2006). THM, HAA and CNCl formation from UV
irradiation and chlor(am)ination of selected organic waters. Water Research, 40, (10), pp2033-2043.
Lyon, B.A., Dotson, A.D., Linden, K.G. and Weinberg, H.S. (2012). The effect of inorganic precursors
on disinfection by-product formation during UV-chlorine/chloramine drinking water treatment. Water
Research, 46, (15), pp4653-4664.
Lyon, B.A., Milsk, R.Y., DeAngelo, A.B., Simmons, J.E., Moyer, M.P. and Weinberg, H.S. (2014).
Integrated chemical and toxicological investigation of UV-chlorine/chloramine drinking water treatment.
Environ. Science and Technology, 48 (12), pp6743-6753.
Malley, J.P., Shaw, J.P. and Ropp, J.R. (1995). Evaluation of by-products produced by the treatment of
groundwaters with ultraviolet irradiation. AWWARF, Denver, Colorado.
Martijn, B., Kolkman, A., Aljammaz, M., Vughs, D. and Baken, K. (2014) Tracing genotoxic N-DBPs
after medium pressure UV water treatment by nitrogen labelling. Keynote presentation. Presented by
Bram Martijn (PWN Technologies, NL) at DBP 2014: Disinfection By-products in Drinking Water, 27-
29th October 2014. Municipal Hall, Mülheim an der Ruhr, Germany.
Mole, N., Lunt, D. and Fielding, M. (1997). Influence of UV disinfection on by-product formation and the
operational implications. DWI 4237/1, Drinking Water Inspectorate.
Parkinson, A., Barry, M.J., Roddick, F.A. and Hobday, M.D. (2001). Preliminary toxicity assessment of
water after treatment with UV-irradiation and UVC/H2O2. Water Research, 35, (15), pp3656-3664.
Plewa, M.J., Wagner, E.D., Metz, D.H., Kashinkunti, R., Jamriska, K.J. and Meyer, M. (2012).
Differential Toxicity of Drinking Water Disinfected with Combinations of Ultraviolet Radiation and
Chlorine. Environmental Science and Technology, 46 (14), pp7811-1.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 68
Reckhow, D.A., Linden, K.G., Kim, J., Shemer, H. and Makdissy, G. (2010). Effect of UV treatment on
DBP formation. Journal American Water Works Association, 102, (6), pp100-113.
Richardson, S.D., Thruston Jr, A.D., Collette, T.W., Patterson, K.S., Lykins, B.W. and Ireland, J.C.
(1996). Identification of TiO2/UV disinfection by-products in drinking water. Environmental Science and
Technology, 30, (11), pp3327-3334.
Shah, A.D., Dotson, A.D., Linden, K.G. and Mitch, W.A. (2011). Impact of UV disinfection combined
with chlorination/chloramination on the formation of halonitromethanes and haloacetonitriles in drinking
water. Environmental Science and Technology, 45, (8), pp3657-3664.
Schmalz, C., Grummt, T. and Zwiener, C. (2014) Pool water DBPs – Drowning in disinfection by-
products? Presented by Christian Zwiener (University of Tübingen, DE) at DBP 2014: Disinfection By-
products in Drinking Water, 27-29th October 2014. Municipal Hall, Mülheim an der Ruhr, Germany.
Siddiqui, M.S., Amy, G.L. and McCollum, L.J. (1996). Bromate destruction by UV irradiation and electric
arc discharge. Ozone Science and Engineering, 18, (3), pp271-290.
WHO (2005) Chloral Hydrate in Drinking-water. Background document for development of WHO
Guidelines for Drinking-water Quality. World Health Organization.
WHO (2011) Guidelines for Drinking-water Quality. Fourth Edition. World Health Organization.
Wong, G.T.F. (1980). The effects of light on the dissipation of chlorine in sea-water. Water Research,
14, (9), pp1263-1268.
Zoeteman, B.C.J., Hrubec, J., de Greef, E. and Kool, H.J. (1982). Mutagenic activity associated with by-
products of drinking water disinfection by chlorine, chlorine dioxide, ozone and UV-irradiation.
Environmental Health Perspectives, 46, pp197-205.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 69
Glossary of Terms
ADI Acceptable daily intake
AOC Assimilable organic carbon
AOP Advanced oxidation process
AOX Adsorbable organic halide
BDOC Biodegradable dissolved organic carbon
CNCl Cyanogen chloride
DBP Disinfection by-product
DBAA Dibromoacetic acid
DCAA Dichloroacetic acid
DOC Dissolved organic carbon
DOM Dissolved organic matter
DWI Drinking Water Inspectorate
EFSA European Food Safety Authority
GC-NPD Gas chromatograph – nitrogen phosphorus detector
GC-MS Gas chromatograph – mass spectrometer
H2O2 Hydrogen peroxide
HAA Haloacetic acid
HAN Haloacetonitrile
LC-MS Liquid chromatograph – mass spectrometer
LP Low pressure (UV lamp)
MBAA Monobromoacetic acid
MCAA Monochloroacetic acid
MP Medium pressure (UV lamp)
N-DBP Nitrogenous disinfection by-product
NOAEL No observed adverse effect level
NOM Natural organic matter
O3 Ozone
OSEGC On-site electrolytic generation of chlorine
PACl Polyaluminium chloride
SUVA Specific UV absorbance (UV254/DOC)
TBAA Tribromoacetic acid
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 70
TCAA Trichloroacetic acid
TCP Trichlorpropanone
THM Trihalomethane
THMFP THM formation potential
TiO2 Titanium dioxide
TTHMs Total THMs (regulated)
UV Ultraviolet
UV254 UV with a wavelength of 254 nm
VUV Vacuum ultraviolet
WHO World Health Organization
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 71
Appendix A Literature Review
A1 Effect of UV used for disinfection
A1.1 UV lamps
Unless stated otherwise, the literature citations refer to UV reactors with germicidal lamps.
Low pressure (LP) germicidal lamps emit essentially monochromatic UV at 254 nm. Medium
pressure (MP) germicidal lamps normally emit within the range 200–400 nm.
A1.2 Effect of UV on organics
Photolysis of natural organic matter (NOM) can break bonds, resulting in smaller molecules
that are more assimilable for bacteria. The potential therefore exists for UV irradiation to
increase the biodegradability of the NOM, and thus potential for regrowth. UV absorbance is
greater in the 200–230 nm wavelength range than at 254 nm, so this is potentially a greater
issue with MP than LP (Ijpelaar et al., 2007).
Malley et al. (1995) applied LP UV doses of 60–200 mJ/cm2
to a range of groundwaters,
untreated surface waters and treated (clarified or filtered) surface waters. No changes in
dissolved organic carbon (DOC) concentration or UV254 absorbance were observed. Three
techniques were used to assess the potential impact on regrowth potential: assimilable
organic carbon (AOC), biodegradable dissolved organic carbon (BDOC), and the proportion of
hydrophilic DOC – increases in any one of which might indicate increased regrowth potential.
AOC was analysed as two components, P17 and NOX; P17 AOC increased but NOX AOC
was unchanged; total AOC was unchanged because P17 AOC concentrations were much
lower than NOX AOC. BDOC increased in untreated surface waters but remained unchanged
in treated surface waters and groundwaters. The proportion of hydrophilic DOC increased in
treated surface waters and low-colour groundwaters but remained unchanged in high-
coloured waters (whether untreated surface water or groundwater).
Kashinkunti et al. (2004) investigated at bench scale the application of UV followed by
chlorination as a barrier against Cryptosporidium and viruses for a direct river abstraction
water treatment plant and as part of this study evaluated the impact of UV on AOC. At the
proposed point of application of UV at the treatment works the water had been subject to
coagulation, two stages of sedimentation, sand filtration and GAC filtration. LP and MP
collimated beam apparatus were used to apply doses of 40 to 140 mJ/cm2. No well-defined
trend in AOC formation was observed with respect to UV dose, and it was concluded that UV
„does not systematically alter the potential for microbial regrowth following treatment for the
limited conditions investigated‟.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 72
Ijpelaar et al. (2005) compared LP and MP UV at bench scale applied to a treated surface
water. For the same range of doses, 47–91 mJ/cm2, no significant increase in AOC was
observed for LP whereas for MP the AOC increased approximately in proportion to dose (c.
400% at 91 mJ/cm2). As a control measure for any such increase in AOC they suggested
installing GAC downstream of MP UV.
Ijpelaar et al. (2007) reviewed published data for evidence of AOC formation by UV. They
concluded that AOC formation is lower in LP reactors than MP, and that for MP doses
<100 mJ/cm2 the increase in AOC is unlikely to exceed 10 g/l.
Choi and Choi (2010) investigated the effects of UV on the characteristics of dissolved
organic matter (DOM), chlorine demand and THM formation. Samples were taken from a pilot
plant comprising 4 parallel UV reactors: germicidal MP and LP, each applying a dose of
40 mJ/cm2; dual-wavelength (185/254 nm) LP, applying (at different times) doses of 40 and
150 mJ/cm2; and broader spectrum MP (185–400 nm) applying a dose of 40 mJ/cm
2. The
feed water was filtrate from sand filters at a water treatment plant. Feed water DOC was in the
range 0.96–1.27 mg/l, UV254 1.4–2.2 m-1
, and SUVA (UV254/DOC) 1.45–1.73 l/mg.m. The
duration of the trials included dry and rainy seasons and „normal times‟; the authors noted that
in the rainy season the DOM tended to be of terrestrial origin, higher molecular weight, more
refactory and more hydrophobic; whereas in the dry season it tended to of algal and bacterial
origin, lower molecular weight relatively labile, and more hydrophilic.
DOC, UV254 and SUVA were unchanged after UV. AOC and the proportion of hydrophilic
DOC were also unchanged. Average DOM molecular weight was unaffected during the rainy
season and „normal times‟. However, in the dry season molecular weight was unaffected by
germicidal LP but decreased after the other reactors, in order (largest decrease to smallest):
dual LP (150 mJ/cm2) > broad spectrum MP > germicidal MP > dual LP (40 mJ/cm
2)
Citing other literature, the authors concluded that these observations were consistent with
lower wavelength (<200 nm) and higher wavelength (>280 nm) being able to break organic
bonds, in conjunction with the relatively UV-reactive dry season DOM.
A1.3 Formation of DBPs: Direct formation
A1.3.1 Mutagenicity
Zoeteman et al. (1982) compared alternatives to chlorine for the disinfection of stored River
Rhine water. LP UV was applied at a dose of 120 mJ/cm2. No significant change to
mutagenicity was observed relative to the untreated raw water.
Ijpelaar et al. (2005) compared LP and MP UV at bench scale applied to a treated surface
water. For the same range of doses, 47–91 mJ/cm2, no change in mutagenicity was observed
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 73
for LP whereas for MP it increased by c. 600% at the highest dose. However, at pilot scale,
MP UV applied to the same water over a similar dose range increased mutagenicity by c.
100%, a discrepancy which the authors were unable to explain.
A1.3.2 Nitrogenated by-products
Mole et al. (1997) used GC-NPD (nitrogen-phosphorus detector) and GC-MS scans to
investigate if UV can cause formation of nitrogen-containing organics. A LP dose of 6,600
mJ/cm2 was applied to river water samples with and without 50 mg/l NO3
- added nitrate. The
GC-NPD scans suggested some formation of nitrogen-containing compounds, but no specific
compounds were identified by GC-MS. They concluded that, overall, the results provided no
firm evidence of UV generating nitrogen-containing compounds.
Liberti et al. (2002) investigated the potential formation of nitro-phenols and nitroso-amines in
secondary- (clarified) and tertiary- (sand filtered) treated wastewater by UV disinfection. The
secondary effluent received a UV dose of 160 mJ/cm2, and the tertiary effluent a dose of
100 mJ/cm2. Comparisons of GC-MS spectra from samples before and after UV irradiation
showed no evidence of volatile DBP formation. In a further test, comparisons of LC-MS
spectra of a secondary-effluent sample before and after a UV dose of 25,000 mJ/cm2 showed
no evidence of non-volatile DBP formation. It was concluded that UV doses much higher than
the 100-160 mJ/cm2 are necessary to promote formation of the target by-products.
A1.3.3 Aldehydes and carboxylic acids
Malley et al. (1995) applied a LP UV dose of 130 mJ/cm2 to a range of groundwaters,
untreated surface waters and treated surface waters. The formation of up to 10 g/l
formaldehyde was observed in untreated, coloured surface waters and a highly-coloured
groundwater (50 oH). In treated surface waters, formaldehyde formation was in the range 1 - 2
g/l, and was below the detection limit in all other groundwaters. They commented that in
practice UV disinfection would not be appropriate for either untreated surface water or highly-
coloured groundwater.
Liu et al. (2002) applied a wide range of UV doses (0–6,360 mJ/cm2) using LP and MP lamps
to a synthetic drinking water containing c. 3 mg/l TOC. The possible production of two groups
of compounds known to affect biostability, aldehydes and carboxylic acids, was investigated.
No change to background concentration of aldehyde was observed at doses less than 500
mJ/cm2. Aldehyde concentrations were observed to increase at UV doses above 500 mJ/cm
2,
to a greater extent for MP than LP (concentrations approximately double). At the maximum
dose, 6,360 mJ/cm2, average aldehyde formation was 13 g/l for LP and 37 g/l for MP
(primarily formaldehyde and acetaldehyde). Neither LP nor MP UV was observed to increase
carboxylic acid concentration at doses less than 1,000 mJ/cm2. For higher LP doses, an
increase in carboxylic acid concentration was apparent but, because of scatter in the data, not
statistically significant. At the maximum dose, 6,360 mJ/cm2, MP UV generated between 100
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 74
and 240 g/l carboxylic acids (primarily formic, acetic and oxalic). The authors noted that no
reduction in TOC had been observed during the tests.
A1.3.4 Nitrite
Nitrite is a photolysis product of nitrate. Nitrate absorbs UV mainly in the 200–240 nm
wavelength range, so nitrite formation is expected to be very limited in LP reactors but
potentially greater in MP reactors (Ijpelaar et al., 2007).
Malley et al. (1995) applied a LP UV dose of 130 mJ/cm2 to a range of groundwaters with
nitrate concentrations in the range 0.16–8.1 mg/l. They observed no change in nitrate
concentration and did not detect nitrite.
Mole et al. (1997) applied high (1,100–6,600 mJ/cm2) and low (60–120 mJ/cm
2) LP UV doses
to deionised water spiked with 50 mg/l NO3- across a pH range 5–8. At 1,100 mJ/cm
2,
maximum nitrite formation occurred at pH 8.1 (161 g/l NO2-) and was <100 μg/l at lower pH
(5.1 to 7.2), with an apparent minimum at pH 6.1 (59 g/l NO2-). Increasing the dose to 6,600
mJ/cm2 increased nitrite formation approximately in proportion to dose. At the low UV doses,
nitrite formation was below the limit of detection (which was relatively high for the analytical
method used, 33 g/l).
Ijpelaar et al. (2005) compared LP and MP UV at bench scale applied to a treated surface
water. For the same range of doses, 47–91 mJ/cm2, and nitrate concentration in the range
13–15 mg/l NO3, no nitrite formation was observed for LP whereas for MP appreciable nitrite
was formed, approximately in proportion to dose (c. 0.8 mg/l at 91 mJ/cm2). However, at pilot
scale, MP UV applied to the same water over the dose range 25–200 mJ/cm2
generated only
about 5% of the nitrite reported at bench scale (c. 0.04 mg/l at 100 mJ/cm2), a discrepancy
which the authors were unable to explain.
Ijpelaar et al. (2007) cited examples of nitrite formation after LP and MP UV exposure. For LP
UV, 2 g/l NO2- after a dose of 25 mJ/cm
2, where nitrate concentration was 50 mg/l NO3
-; and
7 g/l NO2- after a dose of 120 mJ/cm
2, where nitrate concentration was 14 mg/l NO3
-. For MP
UV, 40 g/l NO2- after a dose of 70 mJ/cm
2, where nitrate concentration was 15 mg/l NO3
-;
and 20 g/l NO2- after a dose of 70 mJ/cm
2, where nitrate concentration was 8 mg/l NO3
-.
They noted that nitrite formation from MP UV can be appreciably reduced by providing the
lamps with quartz sleeves to block lower wavelengths. With a water containing 50 mg/l NO3-,
30 g/l NO2- formed after a dose of 50 mJ/cm
2 with lamps sleeved to block wavelengths below
235 nm, whereas 150 g/l NO2- formed with lamps that weren‟t sleeved. They further noted
that, for a given water, nitrite formation is approximately linear with increasing nitrate
concentration and increasing UV dose, and increases with increasing pH (from tests in the
range pH 7–9).
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 75
A1.3.5 Bromate
Malley et al. (1995) applied a LP UV dose of 130 mJ/cm2 to a range of groundwaters with
bromide concentrations in the range 50–250 g/l. They observed no change in bromide
concentration and did not detect bromate.
Ijpelaar et al. (2007) stated that neither UV nor UV/H2O2 are able to convert bromide to
bromate.
Kishimoto and Nakamura (2012) investigated the formation of bromate by LP UV, hydrogen
peroxide and ozone individually and in combination. They observed no bromate formation
after irradiating a 150 g/l Br- solution for 30 minutes (UV dose not specified).
A1.3.6 Other
Zoeteman et al. (1982) compared GC-MS spectra before and after application of LP UV (dose
120 mJ/cm2) to stored River Rhine water and observed some formation of benzene (0.1 g/l
before UV, 1 g/l after) and toluene (not detected before UV, 3 g/l after).
Parkinson et al. (2001) assessed toxicity of water samples from two Australian reservoirs after
treatment by UV and UV/H2O2. UV and UV/H2O2 treated samples were found to be toxic to
Daphnia carinata, which was attributed to the release into solution of copper bound to NOM,
as evidenced by increases in concentrations of copper ions (the origin of the organically-
bound copper likely being the use of copper sulphate to control algae). The concentrations of
copper were well below the applicable water quality standard.
A1.4 Formation of DBPs: Effect of UV upstream of chlorination
Malley et al. (1995) compared DBP formation arising from chlorination and chloramination,
with and without prior exposure to LP UV doses of 60–200 mJ/cm2. The application of UV did
not affect subsequent THM, HAA or cyanogen chloride (CNCl) formation.
Kleiser and Frimmel (2000) reported a decrease of 7% in THM formation potential in filtered
River Ruhr water after exposure to LP UV in a recirculating apparatus after 30 minutes, and a
13% decrease after 240 minutes; no estimate of UV dose was given. Adsorbable organic
halide (AOX) formation potential decreased by 13% and 24%, respectively.
Liu et al. (2002) applied a wide range of UV doses (0–6,360 mJ/cm2) using LP and MP lamps
to a synthetic drinking water containing c. 3 mg/l TOC, and investigated THM and HAA
formation after subsequent chlorination. The synthetic water contained little bromide so
chlorinated species dominated the DBPs formed. No impact on THM formation was observed
at doses below 1,000 mJ/cm2, whether LP or MP. At a LP dose of 5,000 mJ/cm
2, THM
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 76
formation increased by 15%, whereas with MP at the same dose THM formation decreased
by 29%; the authors, however, reported the presence of hydrogen peroxide in the MP test
(without commenting on why), so this decrease was influenced to an unknown extent by an
AOP effect. LP UV did not affect HAA formation at any dose. MP UV did not affect HAA
formation at doses below 1,000 mJ/cm2, but at c. 5,000 mJ/cm
2 reduced formation by
between 15 and 44%.
Kashinkunti et al. (2004) investigated at bench scale the application of UV followed by
chlorination as a barrier against Cryptosporidium and viruses for a direct river abstraction
water treatment plant and as part of this study evaluated the impact of UV on DBPs. At the
proposed point of application of UV at the treatment works the water had been subject to
coagulation, two stages of sedimentation, sand filtration and GAC filtration. LP and MP
collimated beam apparatus were used to apply doses of 40 and 140 mJ/cm2, then 2 mg/l
chlorine was dosed and left for 24 hours before sampling for chlorine residual, THMs, HAAs,
carboxylic acids, aldehydes and TOX. UV was found to have no effect on chlorine demand or
DBP formation, irrespective of UV dose or lamp type.
Chin and Berube (2005) applied UV doses in the range 130–1,600 mJ/cm2 to untreated lake
water (1.8 mg/l TOC; 3.7 mg/l CaCO3 alkalinity; pH 6.6) and observed no reduction in TOC,
and negligible reduction in formation potentials of chloroform and chlorinated HAAs during
subsequent chlorination. They cited other literature reporting results consistent with their own,
but also noted that other studies had observed UV to remove TOC or reduce THM formation
potential; these latter studies, however, had applied UV doses of 13,000 to 288,000 mJ/cm2,
and were, therefore, not at all representative of the typical potable water UV disinfection dose
of 40 mJ/cm2. They concluded that at practical doses UV has very little impact on the organic
constituents in raw water.
Liu et al. (2006) compared the effects of sequential combinations of UV and chlorine on
subsequent DBP formation. UV dose was 60 mJ/cm2, and chlorine was dosed at 7 mg/l free
chlorine. Contact times extended to 7 days to simulate time in distribution. The test matrix
included LP and MP lamps. The impact of UV was determined by comparing against control
tests which dosed only chlorine. Four waters were tested: three were synthetic – buffered
solutions of two commercially available humic acids and one natural organic matter (NOM)
concentrate in ultrapure water, each equivalent to 5 mg/l DOC - and one was a raw river
water (1.8 mg/l DOC). For three out of the four waters, chloroform formation increased when
UV was dosed, with (marginally) greater increases with MP than LP; for the other water,
formation was the same with and without UV. Chloroform formation with chlorine alone was
lowest in the only real water tested (c. 25 g/l after 72 hours) but UV had the greatest impact
in both proportional and absolute terms – the concentration was approximately doubled. In
two waters, UV increased both dichloroacetic acid (DCAA) and trichloroacetic acid (TCAA),
again with greater increases observed with MP than LP; whereas for the other two waters,
DCAA and TCAA were increased by LP but decreased by MP. Chlorine without UV produced
4 to 6 g/l of cyanogen chloride (CNCl) after 7 days contact; in 6 out of 8 tests UV increased
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 77
CNCl concentration, by between 2 and 8 g/l, while in the other 2 tests UV did not change the
concentration.
Choi and Choi (2010) investigated the effects of UV on the characteristics of dissolved
organic matter (DOM), chlorine demand and THM formation. Samples were taken from a pilot
plant comprising 4 parallel UV reactors: germicidal MP and LP, each applying a dose of
40 mJ/cm2; dual-wavelength (185/254 nm) LP, applying (at different times) doses of 40 and
150 mJ/cm2; and broader spectrum MP (185–400 nm) applying a dose of 40 mJ/cm
2. The
feed water was filtrate from sand filters at a water treatment plant. Feed water DOC was in the
range 0.96–1.27 mg/l, UV254 1.4–2.2 m-1
, and SUVA (UV254/DOC) 1.45–1.73 l/mg.m.
Germicidal UV had no effect on chlorine demand or THM formation at 4oC, but at 15
oC it
resulted in an increase in short-term chlorine demand (chlorine decay rate over the first
4 hours contact time increased by a factor of 2.5, but decay rate beyond 4 hours was
unchanged) and increased THM formation (up to 16.5%).
Reckhow et al. (2010) applied LP and MP doses of 40–140 mJ/cm2 to samples of treated and
raw water to determine the impact on DBP formation after subsequent chlorination. Neither
LP nor MP UV affected regulated (US) DBP formation (THM, HAA). Similarly, neither LP nor
MP UV affected formation of haloacetonitriles (HAN), trichlorpropanone (TCP). However,
whereas chloropicrin formation was unaffected by LP UV, it increased with increasing MP
dose; chloral hydrate formation also increased with increasing MP UV dose. Increasing nitrate
concentration was observed to increase formation of chloropicrin when MP UV was applied,
but not LP UV.
Shah et al. (2011) observed that LP UV at doses up to 1,500 mJ/cm2 did not enhance
halonitromethane formation after subsequent chlorination or chloramination, whereas MP UV
doses <300 mJ/cm2 increased chloropicrin formation by as much as an order of magnitude,
formation being greater after chlorination than chloraminaton. The combination MP
UV/chloramination enhanced haloacetonitrile (HAN) formation in a humic acid solution but not
in water samples collected from the field.
Lyon et al. (2012) subjected samples of water collected from a number of water treatment
works to a range of UV doses (LP and MP) followed by chlorination or chloramination. The
impact of the addition of bromide and nitrate was examined. THM and HAA formation were
not affected by disinfection UV doses of 40–186 mJ/cm2, but THM formation increased by 30–
40% at the higher UV dose of 1,000 mJ/cm2. Formation of some non-regulated DBPs
increased at disinfection UV doses. In the presence of nitrate (1–10 mg/l N), 40 mJ/cm2 MP
UV increased chloropicrin formation after chloramination by a factor of 2, and after
chlorination by a factor of 3–6; and in the presence of both bromide and nitrate, bromopicrin
formation after chlorination was increased by c.50 % by 40 mJ/cm2 LP UV and by a factor of
4–10 by 40 mJ/cm2 MP UV. In the presence of nitrate, MP UV doses of 186 and
1,000 mJ/cm2 increased cyanogen chloride formation after chloramination by factors of 2 and
3 respectively, although the concentration never exceeded the World Health Organization
guideline value of 70 g/l.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 78
Linden et al. (2012) investigated the impact of UV disinfection on the formation of regulated
and non-regulated DBPs. The project included a survey of full-scale UV installations across
North America, and experimental evaluation of DBP formation at bench-, pilot- and full-scale.
Elements of the project were reported by Shah et al. (2011) and Lyon et al. (2012). Overall
conclusions were, that UV doses <186 mJ/cm2:
do not alter chlorine demand (free or combined) to any practical extent;
do not alter THM and HAA formation to any practical extent;
are likely to increase halonitromethane formation, particularly when MP UV is applied,
and chloral hydrate formation (LP or MP), at the single g/l level;
will likely reduce to a small degree nitrosamine formation where chloramination follows
the UV.
and UV doses in the range 186–1,000 mJ/cm2:
increase subsequent chlorine/chloramine demand by up to 1 mg/Cl2/l (higher UV dose
corresponding to greater increase in demand) and correspondingly DBP concentrations
will generally be greater;
are likely to increase halonitromethane and chloral hydrate formation by a few g/l,
particularly when MP UV is applied;
will likely appreciably reduce nitrosamine formation where chloramination follows the
UV.
Chu et al. (2014) investigated the impact of pre-oxidation by LP UV, H2O2 and UV/H2O2 on the
formation of haloacetamides by subsequent chlorination. LP UV at doses in the range 19.5-
585 mJ/cm2 did not change formation relative to no pre-oxidation.
A1.5 Formation of DBPs: Effect of UV downstream of chlorination
Wong (1980) demonstrated that exposure of chlorinated sea water to sunlight increased the
chlorine decay rate and resulted in the formation of bromate. The bromate was formed from
hypobromite, itself the product of the oxidation of bromide ions by hypochlorite. Bromate
formation was not observed in the dark, and increased as light intensity increased.
Huang et al. (2008) investigated bromate formation in chlorinated samples of deionised and
clarified/filtered river water (DOC 1.7 mg/l), in darkness and after exposure to LP UV. The
deionised water was spiked with 88 g/l Br-. The natural bromide concentration in the treated
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 79
river water was 53 g/l Br-, which was increased by spiking to 151 g/l for some experiments.
UV dose was in the range 40–2,000 mJ/cm2. Chlorine doses were in the range 1–5 mg/l, and
bromate concentrations were measured in the sodium hypochlorite stock solutions and
accounted for in the subsequent experiments (typically 0.5–1.0 g/l BrO3-/mg Cl2).
Some bromate formation occurred in darkness, but at low rate. After c. 4 days contact time at
pH 7.4 and chlorine dose 1.2 mg/l, bromate concentrations in treated river water samples
were c. 3 g/l, increasing to c. 4 g/l after a further 20 days; chlorine decay rates and bromate
concentrations were marginally greater in the bromide-spiked samples.
Exposure to UV greatly accelerated chlorine decay; in darkness, 5.1 mg/l Cl2 dosed to
deionised water decayed by 15% in 600 hours but by 25% in 5 minutes when exposed to UV
(cumulative UV dose c. 200 mJ/cm2). Approximately 10 g/l BrO3
- formed in this time,
increasing to c. 15 g/l after 25 minutes (cumulative dose 1,000 mJ/cm2). The authors noted
the capability of UV to reduce bromate but did not attempt to quantify the impact this might
have had on the observed bromate formation. Bromate formation was greater at acidic pH,
particularly at pH <6, than at pH 7.8; raising pH from 7.8 to 11 made little difference to
formation.
Campbell (2011) reported elevated bromate concentrations at two groundwater sites
containing >100 ug/l bromide where UV >100 mJ/cm2 was dosed post chlorination. The UV
dose was substantially greater than the target dose of 48 mJ/cm2 due to the reactor design.
Bromate formation was reduced as a result of a reduction in free chlorine concentration and a
reduction of the UV dose.
Linden et al. (2012) concluded that the point of application of UV doses <186 mJ/cm2,
whether upstream or downstream of secondary disinfection by chlorine or chloramine, does
not alter chlorine or chloramine demand nor regulated DBP formation to any practical extent.
However, they noted the capability of UV to photolyse chlorine and chloramine, for example
hypochlorous acid cleaved into hydroxyl and chloride radicals:
→
and recommended that where possible UV disinfection be installed upstream of secondary
disinfection.
A1.6 Effect of UV on pre-formed DBPs
A1.6.1 Bromate
Siddiqui et al. (1996) compared the effectiveness of LP and MP UV for decomposing bromate
to bromide via the intermediates bromite and hypobromite. Peak UV absorption of bromate is
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 80
195 nm, so LP lamp tailored to transmit mostly in the <200 nm range was found to be the
most efficient of the options tested, achieving 40% destruction of bromate at a dose of
250 mJ/cm2, compared with 550 mJ/cm
2 using a MP lamp and c. 800 mJ/cm
2 using a
standard germicidal LP lamp.
Bensalah et al. (2013) investigated bromate reduction by MP UV (200-600 nm). A dose of
1,000 mJ/cm2 reduced bromate by >90%. Observed reaction rate increased with increasing
UV intensity, and decreased in the presence of DOC, inorganic carbon and nitrate.
A1.6.2 THMs
Mole et al. (1997) applied LP UV doses of 1,100 and 6,600 mJ/cm2 to samples of
groundwater spiked with nominally 50 mg/l of individual regulated THMs and with a mixture of
the four regulated THMs each at nominally 50 mg/l. At 1,100 mJ/cm2, removals of
approximately 80% of bromoform, 50% of chlorodibromoform and 20% bromodichloroform
were observed; at 6,600 mJ/cm2, practically all bromoform and chlorodibromoform was
removed and approximately 50% bromodichloroform. Chloroform was not removed, indicating
that photolysis of the Br-C bond occurs more readily than the Cl-C bond.
Chang (2008), using bench-scale LP UV apparatus, observed removal of THMs to be first
order with respect to UV dose (0–2,200 mJ/cm2). Removal of trichloromethane was low
(c. 20% at 2,000 mJ/cm2) but removal rate increased with increasing bromine content.
A1.6.3 HAAs
Chang (2008), using bench-scale LP UV apparatus, observed removal of chlorinated and
brominated HAAs to be first order with respect to UV dose (0–4,400 mJ/cm2). Removal of
chlorinated HAAs (MCAA, DCAA, TCAA) was negligible, and of MBAA very low, but reaction
rate increased appreciably with increasing bromine content (DBAA, TBAA).
A2 Effect of UV in Advanced Oxidation Processes
When UV is applied as a component of an advanced oxidation process (AOP), in conjunction
with ozone (O3), hydrogen peroxide (H2O2) or titanium dioxide (TiO2), the impact on DBPs
may be different than when UV is applied alone because of the hydroxyl radical reaction
pathway.
A2.1 Effect of UV on organics
Richardson et al. (1996) investigated organic DBPs after ultrafiltration and UV/TiO2
photocatalytic treatment, with and without secondary chlorination. For comparison, raw and
ultrafiltered water were also chlorinated. They observed a 40% reduction in TOC (evidence of
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 81
mineralisation) after UV/TiO2 photocatalytic treatment. Although they were considering
UV/TiO2 in the context of potential use for treating small community supplies, in their
experimental method the water was recirculated through the reactor for 24 hours; whether the
quantitative results from this study, notably the magnitude of reduction in TOC achieved by
UV/TiO2 photocatalytic treatment, are representative is questionable.
Ijpelaar et al. (2007) reported that AOC formation to be much higher after the UV/H2O2 AOP
than UV disinfection, in part because of the greater UV dose but also because of hydroxyl
radical reaction pathways. They reported increases in AOC concentration in the range 27–131
µg/l after an MP UV dose of 540 mJ/cm2 (H2O2 dose in the range 4.0–6.9 mg/l); AOC
formation was inversely related to nitrate concentration, because nitrate strongly absorbs UV
at the wavelengths absorbed by NOM.
A2.2 Formation of DBPs: Direct formation
A2.2.1 Nitrite
Ijpelaar et al. (2007) noted that nitrite formation only occurs through photolysis and is related
to UV dose. Since the UV dose applied for AOPs is typically an order of magnitude greater
than for disinfection, nitrite formation is potentially similarly greater (MP lamps being generally
used for AOP applications). They cited an example of a UV/H2O2 plant for which nitrite
formation was in the range 40–330 g/l NO2- at 540 mJ/cm
2 MP UV dose, where
corresponding nitrate concentration was in the range 4.4–12.5 mg/l NO3- and H2O2 dose was
in the range 3.4–6.9 mg/l.
A2.2.2 Bromate
Collivignarelli and Sorlini (2004) performed bench-scale tests to determine performance of LP
UV/O3, which included by-product formation. Their batch apparatus incorporated a recycle,
with ozone and UV doses increased by recirculating for longer. The UV dose was in the range
270-1,400 mJ/cm2 and ozone dose 0.3–10 mg/l. Bromate formation was 40–50% lower than
ozone alone provided UV dose was less than 800 mJ/cm2 and/or CT (the product of ozone
dose and contact time) was less than 10 mg.min/l; above these thresholds UV did not reduce
bromate formation.
Hofman et al. (2010) investigated the impact of combining UV with ozone on bromate
formation. At an ozone dose of 2 mg/l they observed that the application of an MP UV dose of
600 mJ/cm2 approximately doubled bromate formation (from 28 g/l with no UV) in one water
(very low DOC 0.24 mg/l; bromide 170 g/l) while using a different water (moderate DOC
1.75 mg/l; bromide 170 g/l) bromate formation increased from c. 85 to c. 125 g/l at
600 mJ/cm2 in one test but was unchanged in a repeat test.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 82
Kishimoto and Nakamura (2012) investigated the formation of bromate by LP UV, hydrogen
peroxide and ozone individually and in combination. They observed no bromate formation
after irradiating a 150 g/l Br- solution for 30 minutes in the presence of hydrogen peroxide
(UV dose not specified).
A2.3 Formation of DBPs: Effect of UV upstream of chlorination
Richardson et al. (1996) investigated organic DBPs after ultrafiltration and UV/TiO2
photocatalytic treatment, with and without secondary chlorination. For comparison, raw and
ultrafiltered water were also chlorinated. Their results showed that, while many halogenated
DBPs were formed after the combination of UV/TiO2 and chlorination, the number and
concentrations of these DBPs were lower than when chlorine was used alone. They also
observed:
a single DBP formed by UV/TiO2 photocatalytic treatment, tentatively identified as 3-
methyl-2,4-hexanedione;
a single DBP formed only by the combination of UV/TiO2 and chlorination, tentatively
identified as dihydro-4,5-dichloro-2(3H)furanone. It was suggested that this compound
had actually been formed during the analytical process, and hence was initially present
(in the treated water) in a different form, possibly a straight-chain chlorinated hydroxyl
acid.
Kleiser and Frimmel (2000) compared the effect of UV/H2O2 with O3 on DBP formation
potential using filtered River Ruhr water. A transferred O3 dose of 2.3 mg/l reduced THM
formation potential by 24% and AOX formation potential by 26%. Smaller reductions were
observed when LP UV was applied (doses not quantified). UV/H2O2 with 8 mg/l H2O2 dose
initially increased THM formation potential as UV dose was increased, reaching a maximum
of c. 20% greater than the control before declining with further increase in UV dose. There
was a small but statistically significant reduction in DOC, proportional to UV dose. UV254
absorbance also declined with UV dose, initially at a much greater rate than DOC. Both lower
(4 mg/l) and higher (16 mg/l) H2O2 doses reduced the extents to which THM formation
potential increased, and DOC and UV254 absorbance were decreased, relative to the 8 mg/l
dose; this was explained by, on the one hand fewer hydroxyl radicals being formed at the
lower H2O2 dose, and on the other hand more scavenging of hydroxyl radicals by excess
H2O2 at the higher H2O2 dose. They concluded that molecular ozone is more effective than
hydroxyl radicals for decreasing halogenated organic DBP formation and that an ozone-based
AOP is advantageous if wanting to simultaneously remove micropollutants and reduce DBP
formation.
Collivignarelli and Sorlini (2004) performed bench-scale tests to determine performance of LP
UV/O3, which included by-product formation. Their batch apparatus incorporated a recycle,
with ozone and UV doses increased by recirculating for longer. The UV dose was in the range
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 83
270-1,400 mJ/cm2 and ozone dose 0.3–10 mg/l. THM formation was typically 10–30% lower
than ozone alone but there was considerable scatter in their results, with some samples
showing increased formation.
Chin and Berube (2005) compared the effect of the combination of UV/O3 with UV and O3
individually on precursors of chlorinated DBPs (chloroform, chlorinated HAAs). The UV dose
range (130–1,610 mJ/cm2) was above that which would normally be applied for disinfection
but encompassed the range for an AOP application, while only the lowest O3 consumption in
the experimental range (3–24 mg/l) was representative of what might be expected in water
treatment practice. Their apparatus was operated in a batch recirculation mode for set periods
of time; increasing the time increased both UV and O3 doses. They observed that:
UV alone had no impact on DBP formation.
O3 alone at 3 mg/l oxidised organic material but not to the extent of mineralisation
(UV254 absorption was reduced but not TOC) and reduced chloroform formation by
c. 45% and chlorinated HAA formation by c. 35%. No additional benefit was observed
by increasing O3 dose.
UV/O3 oxidised organic material and mineralised TOC. At 130 mJ/cm2 + 3 mg/l O3, the
reduction in formation of chloroform and chlorinated HAAs was similar to that of O3
alone, but increasing doses resulted in greater reduction. However, there was a point of
diminishing return between 270 mJ/cm2 + 8 mg/l O3 and 810 mJ/cm
2 + 16 mg/l O3.
Dotson et al. (2010) investigated DBP formation following UV/H2O2 treatment. Bench-scale
tests using LP and MP UV, with and without H2O2 addition, were carried out on treated water
sampled from a treatment works (river water source). Mean bromide in the treated water
measured 49 µg/l; mean TOC measured 1.51 mg/l in sand filtered water and 0.86 mg/l in
GAC filtered water. THMFP increased by c. 15% (LP) and c. 30-50% (MP) as a result of UV
dosed at 1,000 mJ/cm2. When the UV dose was supplemented with 10 mg/l H2O2, THMFP
increased by c. 100% for both LP and MP UV. For the main tests with UV/H2O2, sufficient
chlorine was dosed to quench the residual H2O2 and provide a chlorine residual of 1 mg/l after
24 hours. The effect of only partially quenching the H2O2 was also explored, by dosing less
than the stoichiometric amount of chlorine required for quenching. It was observed that some
THM formation still occurred, the amount increasing as the chlorine dose approached the
stoichiometric amount, despite the rapid rate of the quenching reaction.
Chu et al. (2014) investigated the impact of pre-oxidation by LP UV, H2O2 and UV/H2O2 on the
formation of haloacetamides and other N-DBPs by subsequent chlorination. UV/H2O2
(585 mJ/cm2, 10 mg/l H2O2) reduced N-DBP formation relative to no pre-oxidation.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 84
A2.4 Effect of UV on pre-formed DBPs
A2.4.1 THMs
Chang (2008), using bench-scale LP UV apparatus, compared removal of THMs by UV and
UV/H2O2. Reaction rates were similar with or without 6 mg/l H2O2, and first order with respect
to UV dose (0–2,200 mJ/cm2), resulting in the conclusion that the reactions were primarily by
UV photolysis rather than with hydroxyl radicals. Removal of trichloromethane was low
(c. 20% at 2,000 mJ/cm2) but removal rate increased with increasing bromine content.
A2.4.2 HAAs
Chang (2008), using bench-scale LP UV apparatus, compared removal of chlorinated and
brominated HAAs by UV and UV/H2O2. Reaction rates were similar with or without 6 mg/l
H2O2, and first order with respect to UV dose (0–4,400 mJ/cm2), resulting in the conclusion
that the reactions were primarily by UV photolysis rather than with hydroxyl radicals. Removal
of chlorinated HAAs (MCAA, DCAA, TCAA) was negligible, and of MBAA very low, but
reaction rate increased appreciably with increasing bromine content (DBAA, TBAA).
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 85
Appendix B UV Treatment in Public Supplies: Returned Questionnaires
B1 Introduction
Information on UV treatment in public supplies was collected by a focussed questionnaire
survey of 22 water companies in England and Wales. The questionnaire was designed to
identify the main features of existing and proposed UV treatment plants, including details of
the plant, main function, upstream and downstream treatment, and any related DBP formation
(or degradation). The survey built on a previous survey carried out by WRc in 2007.
Questionnaires were returned by 16 water companies (73% response), including nil returns
from 6 water companies that reported not using UV.
Six water companies failed to respond to the questionnaire and subsequent requests,
although one company confirmed having about 45 UV units (all on groundwater sites).
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 86
B2 Water Company A
B2.1 Site information
Site name
Works design
capacity (Ml/d)
Raw water
1
Water treatment train identifying location of UV treatment (from works
inlet to distribution)
DBPs monitored
2
DBPs detected
3
A1
30 GW / LSW
Inlet - submerged membranes – slow sand filters – UV – marginal chlorination - phosphate-distribution
Bromate Nitrite
Total THM
No No Yes
A2
165 LSW Inlet - pre chlorine - raw water tanks - pre ozone – clarification – RGFs – post ozone – GAC adsorbers – UV – marginal chlorination (OSEC since Feb 2014) – phosphate - distribution
Bromate Chlorate Chlorite Nitrite
Total THM
Yes-due to O3 Yes Yes No Yes
A3
60 LSW Inlet - pre chlorine - raw water tanks - clarification – pre ozone - RGFs (GAC media)– post ozone – UV – marginal chlorination – phosphate – distribution
Bromate Chlorate Chlorite Nitrite
Total THM
Yes-due to O3 Yes Yes No Yes
A4
27 LSW Inlet – microstrainers – pre ozone – RGFs – slow sand filters – UV – superchlorination/dechlorination – phosphate- distribution
Bromate Nitrite
Total THM
Yes-due to O3 No Yes
A5
12 GW Pre-chlorination – RGFs – UV – marginal chlorination – phosphate – distribution
Bromate Nitrite
Total THM
Yes-due to UV No in final
Yes
A6
60 LSW Inlet – microstrainer – slow sand filters – UV (not installed yet) – marginal chlorination (superchlorination/dechlorination at present) – phosphate – distribution
Bromate Nitrite
Total THM
No No Yes
Works A5 can be supplied from two groundwater sources – GW1 and GW2. Both contain soluble iron but GW2 has more (300 µg/l vs 100 µg/l). Pre-chlorine is used to oxidise the soluble iron and is dosed prior to sand RGFs which include a layer of MnO2 coated sand. GW1 contains typically about 0.2 mg/l NH4. The original design was to dose pre-chlorine at 1.5 mg/l which would carry through the process and SO2 dosed at inlet to CWT to bring residual down to 0.50 mg/l. Pre-chlorine oxidised both the iron and the ammonia. We knew that the UV would lead to a reduction in the chlorine residual but this was accepted. GW2 contains about 150 µg/l Br and GW1 220 µg/l Br. A few weeks after commissioning we detected an increased concentration of bromate (26.6 µg/l) in a compliance sample taken in the Works A5 supply area. The UV dose was 200 mJ/cm
2 . The two UV reactors are Xylem LBX1000 and are
sized to provide the minimum required UV dose of 40 mJ/cm2 at a minimum UV transmission of 70%
and at maximum design flow. The works being on the minimum design flow and the raw water quality being excellent with a UVT >95% led to high UV dose. We have now changed the chlorine dosing point so that we have the facility to dose after the UV as well as before the RGFs (a much reduced dose to oxidise Fe). We have installed a chlorine residual analyser at the inlet to the UV reactors so the site shuts down if chlorine is detected. Since the event we have just been running on GW1 with the pre-chlorine turned off and the MnO2 coated sand has been removing the soluble Fe. However, although we have nitrosomonas bugs in the RGF which convert the ammonia to nitrite we don‟t achieve the oxidation to nitrate (probably no nitrobacter present in the RGFs). So we now have nitrite >0.10 mg/l passing through the works and through the UV reactors but the final chlorine breaks this out. Notes:
1. GW = Ground Water; LSW = Lowland Surface Water; USW = Upland Surface Water.
2. DBPs monitored (regulatory and operational) at the treatment works, within distribution or at customers‟ taps.
3. DBPs detected as a result of regulatory or operational monitoring at the treatment works, within distribution or at customers‟ taps.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 87
B2.2 UV system information
Site name
Year of installation
of UV system
1
Reason for installation
2
Manufacturer & lamp type
3
Number of units & outline of operation
Design dose
(mJ/cm2)
A1
2007 D&C Wedeco, LPHO
2 units, duty/standby 40 (min)
A2
Jan 2012 D&C Trojan 10L30 Swift
Medium Pressure
3 streams. Duty, Assist and standby
40 (min)
A3
Dec 2012 D&C Trojan 10L30 Swift
Medium Pressure
2 streams. Duty, assist/standby.
40 (min)
A4
Feb 2013 D&C Wedeco LBX 1000
Low Pressure High Output
2 streams. Duty/standby.
40 (min)
A5
Nov 2013 D&C Trojan 10L30 Swift
Medium Pressure
2 streams. Duty/standby
40 (min)
A6
June 2014 D&C Trojan 10L30 Swift
Medium Pressure
2 streams. Duty, assist/standby.
40 (min)
Notes:
1. Installation date or date of proposed installation if not an existing system.
2. D = General disinfection; C = Cryptosporidium risk; M = Micropollutant (e.g. pesticide; UV as part of an AOP).
3. LP = Low Pressure; LPHO = Low Pressure High Output; MP = Medium Pressure.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 88
B3 Water Company B
B3.1 Site information
Site name
Works design
capacity (Ml/d)
Raw water
1
Water treatment train identifying location of
UV treatment (from works inlet to distribution)
DBPs monitored
2
DBPs detected3
B1
12.2 LSW Until July 2012: Coagulation/flocculation – HBC – pressure filtration – UV – marginal chlorination - distribution From July 2012: Coagulation/flocculation – HBC – pressure filtration – UV/peroxide – GAC – super chlorination /dechlorination – distribution
THMs (extensive)
HAAs, NDMA, & Bromate
(infrequent/limited data),
Audit & operational monitoring:
THMs 2013 Final Water Avg =
43.6 ug/l 2013 SR Outlet Avg = 62.0
ug/l 2013 WIS Zone (customers
taps) Avg = 65.6 ug/l HAAs
All results from Final Water & SR Outlets in 2013 were
<1.0 ug/l NDMA
Average of 73 analyses of Final Water during 2010 &
2011 = 2.7 ng/l, issues identified with ferric coag
not DBP. Bromate
Limited data during 2009 & 2010. All results from Final Water & SR Outlets <0.6
ug/l
B2
13.7 USW Coagulation/flocculation – FBC – RGF – UV – marginal chlorination (gas) – distribution UV will become operational mid-2014
THMs, HAAs THMs = 45.2 ug/l (avg) HAAs = 5.8 ug/l (avg)
B3
0.55 GW Borehole pump – UV – marginal chlorination with sodium hypochlorite – distribution
THMs, Bromate THMs = 5ug/l Bromate = 1 ug/l
HAAs = 1ug/l
B4
2.1 GW Borehole pump – UV – distribution
THMs, Bromate, HAAs
THMs = 0 ug/l Bromate = 1 ug/l
HAAs = 1 ug/l Notes:
1. GW = Ground Water; LSW = Lowland Surface Water; USW = Upland Surface Water.
2. DBPs monitored (regulatory and operational) at the treatment works, within distribution or at customers‟ taps.
3. DBPs detected as a result of regulatory or operational monitoring at the treatment works, within distribution or at customers‟
taps.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 89
B3.2 UV system information
Site name
Year of installation
of UV system
1
Reason for installation
2
Manufacturer & lamp type
3
Number of units & outline of operation
Design dose
(mJ/cm2)
B1
1992
2013- Advanced
oxidation UV system
D
M
Hanovia, LP
Trojan uvPhox, LP
3 units; 3x duty (2x required to maintain minimum UV dose)
Single unit
40
500
B2
2014 D Trojan, LP 2 units; 1x duty (1x required to maintain minimum UV dose)
40
B3
2011 D Trojan, LP 1 unit 40
B4
2012 D Wedeco, LP 1 unit 40
Notes:
1. Installation date or date of proposed installation if not an existing system.
2. D = General disinfection; C = Cryptosporidium risk; M = Micropollutant (e.g. pesticide; UV as part of an AOP).
3. LP = Low Pressure; LPHO = Low Pressure High Output; MP = Medium Pressure.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 90
B4 Water Company C
B4.1 Site information
Site name
Works design
capacity (Ml/d)
Raw water
1
Water treatment train identifying location of UV
treatment (from works inlet to distribution)
DBPs monitored
2
DBPs detected3
C1
84 GW (Crypto
risk)
Inlet – part flow aeration – part flow pellet reactor softening-other part flow chlorinated – blending of flows – coagulation – RGF – UV –contact tank disinfection-partial dechlorination-chloramination-phos acid - supply
THMs
Nitrite
TTHM levels <20 µg/l leaving WTWs
TTHM levels <30 µg/l at customer taps
<0.01 mg/l detected
at WTWs <0.2 mg/l detected at
customer taps
C2
50 LSW (Crypto
risk)
Storage -inlet – chlorination-coagulation-clarification –filtration-GAC-phos acid -UV-aeration-contact tank disinfection-chloramination-supply
THMs
Nitrite
TTHM levels <50 µg/l leaving WTWs
TTHM levels <60 µg/l at customer taps
<0.01 mg/l detected
at TWorks. <0.3 mg/l detected at
customer taps Notes:
1. GW = Ground Water; LSW = Lowland Surface Water; USW = Upland Surface Water.
2. DBPs monitored (regulatory and operational) at the treatment works, within distribution or at customers‟ taps.
3. DBPs detected as a result of regulatory or operational monitoring at the treatment works, within distribution or at customers‟ taps.
B4.2 UV system information
Site name
Year of installation
of UV system
1
Reason for installation
2
Manufacturer & lamp type
3
Number of units & outline of operation
Design dose (mJ/cm
2)
C1
2005 C Trojan, MP 3 units; 1x duty and 2x assist
60
C2
2010 C ATG, MP 3 units; duty, assist and standby
Minimum 4-log
inactivation of Crypto at 50ML/d with applied dose of 40mJ/cm
2
Notes:
1. Installation date or date of proposed installation if not an existing system.
2. D = General disinfection; C = Cryptosporidium risk; M = Micropollutant (e.g. pesticide; UV as part of an AOP).
3. LP = Low Pressure; LPHO = Low Pressure High Output; MP = Medium Pressure.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 91
B5 Water Company D
B5.1 Site information
Site name
Works design
capacity (Ml/d)
Raw water
1
Water treatment train identifying location of UV treatment (from
works inlet to distribution)
DBPs monitored
2
DBPs detected
3
D1
11.0 GW Calgon Aeration (solvent removal) GAC adsorption Nitrate reduction (ion exchange) UV irradiation Plumbosolvency control Chlorination (gas) Ammoniation
Bromate (Treated) Chlorate (Treated)
NDMA (Treated) Nitrite (Treated
& Cust taps) THM (Cust taps)
TOC (Raw & Treated)
Bromate (Treated) Chlorate (Treated)
NDMA (Treated)
Nitrite (Treated & Cust taps) THM (Cust
taps) TOC (Raw &
Treated)
D2
7.6 GW UV irradiation Filtration (cartridge) – separate source water Nitrate reduction (ion exchange) Plumbosolvency control Chlorination (gas)
Bromate (Treated) Chlorate (Treated)
Nitrite (Treated & Cust taps)
THM (Cust taps) TOC (Raw &
Treated)
Chlorate (Treated)
Nitrite (Treated & Cust taps) THM (Cust
taps) TOC (Raw &
Treated)
D3
16.4 SW&GW
Preozonation Clarification Rapid gravity filtration Post-ozonation De-ozonation GAC adsorption UV irradiation Chlorination (gas) Dechlorination Plumbosolvency control
Bromate (Treated) Chlorate (Treated)
NDMA (Treated) Nitrite (Raw,
Treated & Cust taps)
THM (Treated & Cust taps)
TOC (Raw & Treated)
Bromate (Treated) Chlorate (Treated)
NDMA (Treated)
Nitrite (Raw, Treated & Cust
taps) THM (Treated & Cust taps) TOC (Raw &
Treated)
D4
Included in above
GW UV irradiation Chlorination (gas) Plumbosolvency control
D5
34.3 GW Nitrate reduction (ion exchange) Filtration (cartridge) UV irradiation Chlorination (gas) Fluoridation Dechlorination Plumbosolvency control
Bromate (Treated) Chlorate (Treated)
Nitrite (Treated & Cust taps)
THM (Cust taps) TOC (Raw &
Treated)
Bromate (Treated)
Nitrite (Treated & Cust taps)
Nitrite (Treated)
THM (Cust taps)
TOC (Raw & Treated)
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 92
Site name
Works design
capacity (Ml/d)
Raw water
1
Water treatment train identifying location of UV treatment (from
works inlet to distribution)
DBPs monitored
2
DBPs detected
3
D6
65.7 SW Microstrainers Preozonation Lime dosing Clarification Calgon Rapid gravity filtration UV irradiation Post-ozonation De-ozonation GAC adsorption Chlorination (gas) Plumbosolvency control Dechlorination
Bromate (Treated & Cust
taps) Chlorate (Treated)
NDMA (Treated) Nitrite (Raw,
Treated & Cust taps)
THM (Treated & Cust taps) TOC (Raw,
Treated & Cust taps)
Bromate (Treated & Cust taps) Chlorate (Treated)
NDMA (Treated)
Nitrite (Raw, Treated & Cust
taps) THM (Treated & Cust taps) TOC (Raw,
Treated & Cust taps)
D7
20 SW Rapid gravity filtration (GAC) Submerged membrane UV peroxide UV irradiation GAC adsorption Chlorination (gas) Plumbosolvency control Fluoridation
Bromate (Treated) Chlorate (Treated)
Nitrite (Raw & Treated)
THM (Treated) TOC (Raw &
Treated)
Nitrite (Raw) TOC (Raw)
D8
32 GW Plumbosolvency control Chlorination (gas) UV irradiation
Bromate (Treated) Chlorate (Treated)
Nitrite (Treated & Cust taps)
THM (Cust taps) TOC (Raw &
Treated)
Bromate (Treated) Chlorate (Treated)
Nitrite (Treated & Cust taps) THM (Cust
taps) TOC (Raw &
Treated) Notes:
1. GW = Ground Water; LSW = Lowland Surface Water; USW = Upland Surface Water.
2. DBPs monitored (regulatory and operational) at the treatment works, within distribution or at customers‟ taps.
3. DBPs detected as a result of regulatory or operational monitoring at the treatment works, within distribution or at customers‟
taps.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 93
B5.2 UV system information
Site name
Year of installation
of UV system
1
Reason for installation
2
Manufacturer & lamp type
3
Number of units & outline of operation
Design dose
(mJ/cm2)
D1
1993 D Hanovia, LP 4 units, 3x duty/assist 1x standby,
changeover every 24 hours
25
D2
2006 M (pesticides - trietazine)
Trojan, LP 2 units, duty/standby, changeover every 6
hours
600
D3
2007 C Trojan, LP (Swift SC DC
30)
3 units duty/duty/standby
Min. of 40
D4 2008 D (drought scheme)
Trojan, LP 2 units, duty/standby 40
D5 2011 C Trojan, LP (Swift SC DC
30)
3 units duty/duty/standby
Min. of 40
D6
2012 C Trojan, LP 4 units plus 2 emergency units
containing two reactors each.
6 duty reactors/2 standby
Min. of 40
D7
Not yet in supply –
planned 2014
M
D
Trojan Torrent
Trojan, LP (Swift SC DC
30)
4 UV reactors in conjunction with peroxide dose –
duty/standby arrangement
dependent on flow and raw water metaldehyde
challenge
2 UV reactors as final stage of disinfection act
as duty/duty or duty/standby
dependent on flow
500
40 - 25
D8
2012 C Trojan, LP 4 reactors 2 or 3 duty (dependent
on plant flow) /1 standby
Min. of 40
Notes:
1. Installation date or date of proposed installation if not an existing system.
2. D = General disinfection; C = Cryptosporidium risk; M = Micropollutant (e.g. pesticide; UV as part of an AOP).
3. LP = Low Pressure; LPHO = Low Pressure High Output; MP = Medium Pressure.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 94
B6 Water Company E
B6.1 Site information
Site name
Works design
capacity (Ml/d)
Raw water
1
Water treatment train identifying location of UV treatment (from works
inlet to distribution)
DBPs monitored
2
DBPs detected
3
E1
3.1 GW E1 mains and E1 borehole sites are abstraction sites, each with two boreholes. E1 Mains pumps groundwater to E1 Treatment works. No water from E1 Mains enters into customer supply it all passes forward to E1 treatment works. At E1 treatment works the only treatment is chlorination and UV treatment.
Total THMs and Bromate
in distribution.
Nitrite at Works.
THMs 6.7-10.1 ug/l (2013)
BrO3 <0.3-0.33 ug/l (2013)
NO2 <1.1-18 ug/l (2013)
E2
7.0 GW Chlorination and phosphate dosing. One borehole/well. 4 pumps with duty standby for maximum 2 pump operation. Installed in pumping main prior to distribution.
Total THMs and Bromate
in distribution.
Nitrite at Works.
THMs 1.98-56.6 ug/l (2013)
BrO3 <0.3-1.1 ug/l (2013)
(THMs and BrO3 data
from various
supplies)
NO2 <1.1-8.4 ug/l (2013)
E3
7.5 GW At this works there is one borehole with two pumps (duty/duty). The main treatment processes are chlorination and phosphate dosing. Installed in pumping main prior to distribution.
Total THMs and Bromate
in distribution.
Nitrite at Works.
THMs 1.98-56.6 ug/l (2013)
BrO3 <0.3-1.1 ug/l (2013)
(THMs and BrO3 data
from various
supplies)
NO2 <1.1-8.1 ug/l (2013)
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 95
Site name
Works design
capacity (Ml/d)
Raw water
1
Water treatment train identifying location of UV treatment (from works
inlet to distribution)
DBPs monitored
2
DBPs detected
3
E4
5.4 GW Chlorination and phosphate dosing. One borehole/well. 2 pumps with duty standby. Installed in pumping main prior to distribution.
Total THMs and Bromate
in distribution.
Nitrite at Works.
THMs 1.98-56.6 ug/l (2013)
BrO3 <0.3-1.1 ug/l (2013)
(THMs and BrO3 data
from various
supplies)
NO2 <1.1 ug/l (2013)
E5
4.5 GW Chlorination and phosphate dosing. One borehole/well. 2 pumps with duty standby - with one maximum pump in operation. Installed in pumping main prior to distribution.
Total THMs and Bromate
in distribution.
Nitrite at Works.
THMs 1.98-56.6 ug/l (2013)
BrO3 <0.3-1.1 ug/l (2013)
(THMs and BrO3 data
from various
supplies)
NO2 <1.1-31 ug/l (2013)
E6 (Proposed)
5.0 GW At this works there is one borehole with one pump; treatment consists of chlorination and phosphate dosing.
Total THMs and Bromate
in distribution.
Nitrite at Works.
THMs 1.98-56.6 ug/l (2013)
BrO3 <0.3-1.1 ug/l (2013)
(THMs and BrO3 data
from various
supplies)
NO2 <1.1-2.8 ug/l (2013)
E7 (Proposed)
8.4 GW Disinfected borehole waters combine at E7 WTW site and the water is pH corrected with caustic soda, phosphate is added for lead control and the supply is disinfected with sodium hypochlorite. There is a contact tank at E7 to provide Ct.
Total THMs and Bromate
in distribution.
Nitrite at Works.
THMs 1.98-56.6 ug/l (2013)
BrO3 <0.3-1.1 ug/l (2013)
(THMs and BrO3 data
from
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 96
Site name
Works design
capacity (Ml/d)
Raw water
1
Water treatment train identifying location of UV treatment (from works
inlet to distribution)
DBPs monitored
2
DBPs detected
3
various supplies)
E8 (Proposed)
12.0 GW At this works there are three boreholes with four pumps with variable pump operational combinations possible from one pump to all four. The main treatment processes are chlorination and phosphate dosing.
Total THMs and Bromate
in distribution.
Nitrite at Works.
THMs 1.98-56.6 ug/l (2013)
BrO3 <0.3-1.1 ug/l (2013)
(THMs and BrO3 data
from various
supplies)
NO2 <1.1-15 ug/l (2013)
Notes:
1. GW = Ground Water; LSW = Lowland Surface Water; USW = Upland Surface Water.
2. DBPs monitored (regulatory and operational) at the treatment works, within distribution or at customers‟ taps.
3. DBPs detected as a result of regulatory or operational monitoring at the treatment works, within distribution or at customers‟
taps.
B6.2 UV system information
Site name
Year of installation
of UV system
1
Reason for installation
2
Manufacturer & lamp type
3
Number of units & outline of operation
Design dose
(mJ/cm2)
E1 2009 D Berson UV MP
A single Inline 1000+ unit installed on
pumping main prior to chemical
dosing in constant operation.
40
E2 2012 D Berson UV MP
A single Inline 5000+ DVGW unit
installed on pumping main
prior to chemical dosing in constant
operation.
40
E3
2013 D Berson UV MP
A single inline 5000 + DVGW unit installed on pumping main
prior to chemical dosing in constant
operation.
40
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 97
Site name
Year of installation
of UV system
1
Reason for installation
2
Manufacturer & lamp type
3
Number of units & outline of operation
Design dose
(mJ/cm2)
E4
2012 D Berson UV MP
A single inline 1000 + DVGW unit installed on pumping main
prior to chemical dosing in constant
operation.
40
E5
2012 D Berson UV MP
A single inline 1000 + DVGW unit installed on pumping main
prior to chemical dosing in constant
use.
40
E6 (Proposed)
- D Not yet specified.
E7 (Proposed) - D Not yet specified.
E8 (Proposed) - D Not yet specified.
Notes:
1. Installation date or date of proposed installation if not an existing system.
2. D = General disinfection; C = Cryptosporidium risk; M = Micropollutant (e.g. pesticide; UV as part of an AOP).
3. LP = Low Pressure; LPHO = Low Pressure High Output; MP = Medium Pressure.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 98
B7 Water Company F
B7.1 Site information
Site name
Works design
capacity (Ml/d)
Raw water
1
Water treatment train identifying location of UV treatment (from works
inlet to distribution)
DBPs monitored
2
DBPs detected
3
F1 1.4 GW UV, Chlorination Regulatory THMs at
customers taps
Typically <5ug/l
F2
2.8 GW UV, Chlorination Regulatory THMs at
customers taps
AMP6 project
Notes:
1. GW = Ground Water; LSW = Lowland Surface Water; USW = Upland Surface Water.
2. DBPs monitored (regulatory and operational) at the treatment works, within distribution or at customers‟ taps.
3. DBPs detected as a result of regulatory or operational monitoring at the treatment works, within distribution or at customers‟
taps.
B7.2 UV system information
Site name
Year of installation
of UV system
1
Reason for installation
2
Manufacturer & lamp type
3
Number of units & outline of operation
Design dose
(mJ/cm2)
F1 2004 D ATG MP 2 units operating in duty standby arrangement
25
F2 AMP6 D Unknown, LP 2 units operating in duty standby arrangement
40
F3 (Replacement of F1)
AMP6 D Unknown, LP 2 units operating in duty standby arrangement
40
Notes:
1. Installation date or date of proposed installation if not an existing system.
2. D = General disinfection; C = Cryptosporidium risk; M = Micropollutant (e.g. pesticide; UV as part of an advanced AOP).
3. LP = Low Pressure; LPHO = Low Pressure High Output; MP = Medium Pressure.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 99
B8 Water Company G
B8.1 Site information
Site name
Works design
capacity (Ml/d)
Raw water
1
Water treatment train identifying location of UV treatment (from works
inlet to distribution)
DBPs monitored
2
DBPs detected
3
G1
10.0 GW BH1 inlet – balance tank – UV – treated water reservoir (mixes with surface water works output) – distribution
Bromate Chlorate
Nitrite THMs
Bromate Chlorate
Nitrite THMs
G2
2.2 GW Inlet – UV – marginal chlorination – distribution
Bromate Chlorate
Nitrite THMs
Bromate Chlorate
Nitrite THMs
G3
3.8 GW Inlet – UV – marginal chlorination – phosphate dosing –distribution
Bromate Nitrite THMs
Bromate Nitrite THMs
G4 8.6 GW Inlet – UV – marginal chlorination- phosphate dosing – distribution (incl. blending for pH in DSR)
Bromate Chlorate
Nitrite THMs
Bromate Chlorate
Nitrite THMs
G5 9.1 GW Inlet – UV – marginal chlorination – distribution (incl. blending for arsenic in DSR)
Bromate Chlorate
Nitrite THMs
Bromate Chlorate
Nitrite THMs
G6
15.7 GW Inlet – phosphate dosing – UV – marginal chlorination – distribution
Bromate Chlorate
Nitrite THMs
Bromate Nitrite THMs
G7
7.0 GW Inlet – phosphate dosing – UV – marginal chlorination – distribution (incl. blending for nitrate in DSR)
Bromate Nitrite THMs
Bromate Nitrite THMs
G8
0.87 GW Inlet – UV – marginal chlorination (hypochlorite) – distribution
Bromate Chlorate
Nitrite THMs
Chlorate Nitrite THMs
G9
13.6 GW Inlet – marginal chlorination – phosphate dosing – UV – distribution
Bromate Chlorate
Nitrite THMs
Bromate Chlorate
Nitrite THMs
G10 (Off line)
1.6 GW Inlet – UV – marginal chlorination (hypochlorite) – distribution (incl. blending for pH in DSR)
Bromate Nitrite THMs
Bromate Nitrite THMs
G11 7.7 GW Inlet – prechlorination (oxidant for manganese removal) – manganese removal filters (incl. blending for nitrate) – UV – dechlorination – emergency chlorination – distribution
Bromate Chlorate
Nitrite THMs
Bromate Chlorate
Nitrite THMs
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 100
Site name
Works design
capacity (Ml/d)
Raw water
1
Water treatment train identifying location of UV treatment (from works
inlet to distribution)
DBPs monitored
2
DBPs detected
3
G12
10.0 GW - Bromate Chlorate
Nitrite THMs
Bromate Chlorate
Nitrite THMs
G13
2.9 GW BH3 inlet – cartridge filter – UV – nitrate plant – blending tank (for sodium) – phosphate dosing – distribution
Bromate Chlorate
Nitrite THMs
Bromate Chlorate
Nitrite THMs
G14 (Off line)
5.5 GW - Bromate Chlorate
Nitrite THMs
Nitrite THMs
G15
- GW Due to be commissioned - -
G16
- GW Proposed AMP6 scheme - -
G17
- GW Proposed AMP6 scheme - -
G18
- GW Proposed AMP6 scheme - -
G19
- GW Proposed AMP6 scheme - -
G20
- GW Proposed AMP6 scheme - -
G21
- GW Proposed AMP6 scheme - -
G22
- GW Proposed AMP6 scheme - -
G23
- GW Proposed AMP6 scheme - -
G24
- GW Proposed AMP6 scheme - -
G25
- GW Proposed AMP6 scheme - -
G26
- GW Proposed AMP6 scheme - -
G27
- GW Proposed AMP6 scheme - -
G28
- GW Proposed AMP6 scheme - -
G29
- GW Proposed AMP6 scheme - -
G30
- GW Proposed AMP6 scheme - -
G31
- GW Proposed AMP6 scheme - -
G32
- GW Proposed AMP6 scheme - -
G33
- GW Proposed AMP6 scheme - -
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 101
Site name
Works design
capacity (Ml/d)
Raw water
1
Water treatment train identifying location of UV treatment (from works
inlet to distribution)
DBPs monitored
2
DBPs detected
3
G34
- GW Proposed AMP6 scheme - -
G35
- GW Proposed AMP6 scheme - -
G36
- GW Proposed AMP6 scheme - -
G37
- GW Proposed AMP6 scheme - -
G38
- GW Proposed AMP6 scheme - -
Notes:
1. GW = Ground Water; LSW = Lowland Surface Water; USW = Upland Surface Water.
2. DBPs monitored (regulatory and operational) at the treatment works, within distribution or at customers‟ taps.
3. DBPs detected as a result of regulatory or operational monitoring at the treatment works, within distribution or at customers‟
taps.
B8.2 UV system information
Site name Year of
installation of UV system
1
Reason for installation
2
Manufacturer & lamp type
3
Number of units & outline of operation
Design dose
(mJ/cm2)
G1
2013 C Berson, MP 2 units; duty/standby
40
G2
2006 C, D Hanovia, PMD200D1/6NW
2 units (ARC reactors); duty/duty
-
G3 1990s D Jaybay, MP 2 units; duty/standby
-
G4
2009 C, D Trojan, MP 1 unit; duty only (temporary)
>42
G5
1990s D Jaybay, MP 2 units; duty/standby
-
G6
2012 C, D Berson, MP 2 units; duty/standby
>42
G7
- C, D - - -
G8
1996 D J-Bay 2 units; duty/standby
-
G9
2012 C, D Xylem 1 unit; duty only (temporary)
>42
G10 (Off line)
2013 C, D Berson, MP 2 units; duty/standby
>42
G11
2012 C, D Trojan, MP 2 units; duty/standby
>42
G12
2013 C, D Berson, MP 2 units; duty/standby
>42
G13 2005 C, D Xylem 2 units; duty/standby
40 (min)
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 102
Site name Year of
installation of UV system
1
Reason for installation
2
Manufacturer & lamp type
3
Number of units & outline of operation
Design dose
(mJ/cm2)
G14 (Off line)
2013 C, D Berson, MP 2 units; duty/standby
>42
G15
2014 (Due to
be commissioned)
- - - -
G16
- C - - -
G17
- C - - -
G18
- C - - -
G19
- C - - -
G20
- C - - -
G21
- C - - -
G22
- C - - -
G23
- C - - -
G24
- D - - -
G25
- D - - -
G26
- D - - -
G27
- D - - -
G28
- D - - -
G29
- D - - -
G30
- D - - -
G31
- D - - -
G32
- D - - -
G33
- D - - -
G34
- D - - -
G35
- D - - -
G36
- D - - -
G37
- D - - -
G38
- D - - -
Notes:
1. Installation date or date of proposed installation if not an existing system.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 103
2. D = General disinfection; C = Cryptosporidium risk; M = Micropollutant (e.g. pesticide; UV as part of an AOP).
3. LP = Low Pressure; LPHO = Low Pressure High Output; MP = Medium Pressure.
B9 Water Company H
B9.1 Site information
Site name
Works design
capacity (Ml/d)
Raw water
1
Water treatment train identifying location of UV treatment (from works
inlet to distribution)
DBPs monitored
2
DBPs detected
3
H1
17.5 GW Micro-filtration, UV, aeration, super-de chlorine disinfection
4 regulatory required THMs at
customers taps
All 4
H2
90.0 SW Pressure filtration, slow sand filtration, UV, super-de chlorine disinfection
4 regulatory required THMs at
customers taps
All 4
Notes:
1. GW = Ground Water; LSW = Lowland Surface Water; USW = Upland Surface Water.
2. DBPs monitored (regulatory and operational) at the treatment works, within distribution or at customers‟ taps.
3. DBPs detected as a result of regulatory or operational monitoring at the treatment works, within distribution or at customers‟
taps.
B9.2 UV system information
Site name
Year of installation
of UV system
1
Reason for installation
2
Manufacturer & lamp type
3
Number of units & outline of operation
Design dose
(mJ/cm2)
H1
2012 C MP 2 – duty & standby 45.4
H2
2014 C MP 4 – duty & standby 40.0
Notes:
1. Installation date or date of proposed installation if not an existing system.
2. D = General disinfection; C = Cryptosporidium risk; M = Micropollutant (e.g. pesticide; UV as part of an AOP).
3. LP = Low Pressure; LPHO = Low Pressure High Output; MP = Medium Pressure.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 104
B10 Water Company J
B10.1 Site information
Site name
Works design
capacity (Ml/d)
Raw water
1
Water treatment train identifying location of UV treatment (from works
inlet to distribution)
DBPs monitored
2
DBPs detected
3
J1
25 GW (chalk)
J2
8.4 GW (chalk)
J3
2.88 GW (chalk)
J4
12.70 GW (chalk)
Notes:
1. GW = Ground Water; LSW = Lowland Surface Water; USW = Upland Surface Water.
2. DBPs monitored (regulatory and operational) at the treatment works, within distribution or at customers‟ taps.
3. DBPs detected as a result of regulatory or operational monitoring at the treatment works, within distribution or at customers‟
taps.
B10.2 UV system information
Site name
Year of installation
of UV system
1
Reason for installation
2
Manufacturer & lamp type
3
Number of units & outline of operation
Design dose
(mJ/cm2)
J1
2008 D Berson, MP 3 units; <400 m3/h =
1 unit, 400-600 m3/h
= 2 units, >600 m3/h
= 3 units
40
J2
1998 D Hanovia, MP 2 units; duty/standby, 360 m
3/hr
40
J3
2012 C Xylem, LP 116 m3/hr, 2 units,
duty/standby 40
J4
2014 D Xylem, LP 2 units; duty/duty, 666 m
3/hr
40
Notes:
1. Installation date or date of proposed installation if not an existing system.
2. D = General disinfection; C = Cryptosporidium risk; M = Micropollutant (e.g. pesticide; UV as part of an AOP).
3. LP = Low Pressure; LPHO = Low Pressure High Output; MP = Medium Pressure.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 105
B11 Water Company K
B11.1 Site information
Site name
Works design
capacity (Ml/d)
Raw water
1
Water treatment train identifying location of UV treatment (from works inlet to
distribution)
DBPs monitored
2
DBPs detected
3
K1 15 USW Inlet - Coagulation/Flocculation - DAF - RGF1 - RGF2 - UV – Distribution
Nitrites Bromates
No No
K2 18 GW Inlet - Membrane Filtration - Pressure Filtration - UV – Distribution
Nitrites Bromates
No No
K3 27 GW Inlet - Membrane Plant - UV - Chlorine – Distribution
Bromate No
K4 4.5 GW Inlet - Aeration - pH correction - UV - Chlorination – Distribution
Nitrites Bromates
No No
K5 11 GW Inlet - Pressure Filtration - UV – Distribution Bromate Nitrite
1/2 Reg PCV No
K6 45 SW Inlet - Coagulation/Flocculation - Pressure Filters - UV – Distribution
Nitrites Bromates
THMs
No No No
K7 40 SW Inlet - Coagulation/Flocculation - DAF - RGF1 - RGF2 - Chlorination - UV - oPO4 – Distribution
Nitrites Bromates
No No
K8 70 SW Inlet - UV - oPO4 - Chlorination - Distribution Nitrites THMs
No No
K9 11.5 GW Inlet - UV - Chlorination - oPO4 – Distribution No No
K10 25 SW Inlet - UV - oPO4 – Distribution Nitrites Bromates
No No
Notes:
1. GW = Ground Water; LSW = Lowland Surface Water; USW = Upland Surface Water.
2. DBPs monitored (regulatory and operational) at the treatment works, within distribution or at customers‟ taps.
3. DBPs detected as a result of regulatory or operational monitoring at the treatment works, within distribution or at customers‟
taps.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 106
B11.2 UV system information
Site name
Year of installation
of UV system
1
Reason for installation
2
Manufacturer & lamp type
3
Number of units & outline of operation
Design dose
(mJ/cm2)
K1 2007 D C Wedeco, LP 2 x BX3200; Duty/Duty (each capable of 100% flow)
48
K2 2006 D Wedeco, LP 2 x BX1800; Duty/Assist 48
K3 2007 D Wedeco, LP 3 x BX3200; Duty/Assist/Stand-by
48
K4 2007 D Wedeco, LP 2 x BX1000; Duty/Duty (each capable of 100% flow)
48
K5 2007 D Wedeco, LP 2 x BX3200; Duty/Duty 48
K6 2007 D Wedeco, LP 1 x K series; Duty 48
K7 2007 D Wedeco, LP 1 x K series; Duty 48
K8 2008 D Wedeco, LP 1 x K series; Duty 48
K9 2006 D Wedeco, LP 1 x BX1800; Duty 48
K10 2007 D Wedeco, LP 2 x BX3200; Duty/Duty 48 Notes:
1. Installation date or date of proposed installation if not an existing system.
2. D = General disinfection; C = Cryptosporidium risk; M = Micropollutant (e.g. pesticide; UV as part of an AOP).
3. LP = Low Pressure; LPHO = Low Pressure High Output; MP = Medium Pressure.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 107
Appendix C Site Visit Data
C1 Works A2
C1.1 Works Description
The works treats canal water which is of high alkalinity and moderate colour (typically 30°H),
with occasional high turbidity. The maximum design flow is 165 Ml/d, and the treated flow is
typically in the range 100-110 Ml/d.
Raw water is held in two storage tanks (effective capacity for both tanks combined: 108 Ml/d –
approximately 24 hours storage) prior to treatment. When the water temperature is above
15°C (usually April to September) chlorine is dosed to 1 mg/l prior to the storage tanks to
prevent zebra mussel growth. The storage tanks are fitted with aerators for THM removal.
Feed water to the works is dosed with sulphuric acid (to give a coagulation pH of 6.8) prior to
preozonation at a dose of 1 mg/l (capacity of each tank is 0.306 Ml; two streams are always in
service – total capacity of 0.612 Ml). The water is coagulated with polyaluminium chloride and
split between a bank of 12 hopper bottomed clarifiers and 2 superpulsators after dosing with
Magnafloc LT27 polyelectrolyte separately to each of the two streams. The clarified water is
filtered with a bank of 7 rapid gravity sand filters.
The filtered water is repumped to main ozonation, typically with a dose of 0.3-0.4 mg/l to give
a residual of 0.15 mg/l after the contactors. During normal operation, 2 ozone streams are in
service – the capacity of one ozone stream is 0.797 Ml, the capacity of two ozone streams is
1.593 Ml. At a flow of 100 Ml/d, the contact time in one stream is 11.5 minutes, the contact
time in two streams is 22.9 minutes. Sulphuric acid can be dosed upstream of ozonation to
reduce bromate formation.
The water is treated on 8 GAC contactors for pesticide, taste and odour removal prior to UV
disinfection. There are three Trojan units with a minimum design dose of 42 mJ/cm2 at 70%
UVT, but the dose is usually in the range 60-120 mJ/cm2. The MP lamps are sleeved to
prevent nitrite formation. The UV was installed in early 2012.
The water is dosed with NaOH to pH 7.2 and phosphate prior to final chlorination with a dose
typically around 1.2 mg/l to give a residual of 1 mg/l after the clear water tanks (capacity:
27 Ml). On-site electrolytic chlorine generation with low-bromide salt is used for final
chlorination and prechlorination when used, with the hypochlorite product stored for up to 4
days.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 108
Backwash water and clarifier sludge are treated on-site using Magnafloc LT22, with recycling
of supernatants to the works inlet. (Supernatant is pumped to Canal Pump Sump A where it
mixes with the raw water and is then pumped over to the raw water storage tanks).
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 109
Figure C.1 Works A2: Schematic
Canal
Canal (optional by-pass)Sulphuric acid
Polyaluminium chloridePolyelectrolyte (LT27)
Sulphuric acid(seasonal for bromate control)
PhosphateSodium hydroxide (to pH 7.2)
Chlorine residual Chlorine 1.0 mg/l afterfinal tanks
Chlorine(seasonal)
Final watertanks
UV
GAC
Ozonation
Pre-ozonation
Raw waterstorage
Clarification Clarification
Rapid gravityfiltration
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 110
C1.2 DBP Formation
Figure C.2 shows THM concentrations in the final water. A seasonal influence is evident, with
higher levels in the summer. This will be partly a temperature effect, but may also result from
prechlorination used in the summer for zebra mussel control, and changes in the nature of
raw water DOC between summer and winter (although there is no clear indication of these
seasonal changes based on UV absorbance in the water after preozonation, Figure C.3, and
after GAC, Figure C.4).
Figure C.2 Works A2: Final water THMs
Generally, THM levels have been lower since installation of the UV in early 2012 (this may
reflect reduced chlorine use or possibly when THM removal in the raw water tanks with the
aerators was started).
Elevated bromate occurs in the final water, Figure C.5, but this is likely to be from ozonation
rather than any influence from the UV.
Nitrite levels in the water immediately after UV treatment are always very low or non-
detectable.
0
10
20
30
40
50
60
70
80
90
06
/07
/20
09
22
/01
/20
10
10
/08
/20
10
26
/02
/20
11
14
/09
/20
11
01
/04
/20
12
18
/10
/20
12
06
/05
/20
13
22
/11
/20
13
10
/06
/20
14
27
/12
/20
14
tothaloforms (ug/l)
tribromomethane (ug/l)
trichloromethane (ug/l)
dibromochloromethane (ug/l)
dichlorobromomethane (ug/l)
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 111
Figure C.3 Works A2: UV254 absorbance after preozonation
Figure C.4 Works A2: UV254 absorbance after GAC
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
0.4
0.450
6/0
7/2
00
9
22
/01
/20
10
10
/08
/20
10
26
/02
/20
11
14
/09
/20
11
01
/04
/20
12
18
/10
/20
12
06
/05
/20
13
22
/11
/20
13
10
/06
/20
14
27
/12
/20
14
uv254 Abs/cm
0
0.005
0.01
0.015
0.02
0.025
0.03
0.035
0.04
0.045
14/09/2011 01/04/2012 18/10/2012 06/05/2013 22/11/2013 10/06/2014 27/12/2014 15/07/2015
uv254 Abs/cm
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 112
Figure C.5 Works A2: Final water bromate and bromide
C2 Works A5
C2.1 Works Description
The works is fed from groundwater boreholes (GW1) high in iron. There is also a local
groundwater source with wells on site but this is no longer used. The maximum design flow is
12 Ml/d, but the normal flow is around 4 Ml/d. The water is high alkalinity with pH typically
between 7.5 and 8, and the water temperature is usually around 10°C. Turbidity is low and
microbiological quality high.
Up to 2013, chlorine was dosed to the water at 2-3 mg/l for iron precipitation, but this is no
longer used because of concerns over bromate formation. The water then flows through two
contact tanks in parallel to a bank of 5 rapid gravity sand filters for iron removal. The filtered
water then splits between two Wedeco LP UV units, via a common feed tank. The UV dose at
the maximum design flow is 48 mJ/cm2, but the dose is usually over 100 mJ/cm
2.
The water is chlorinated (chlorine gas) to 1 mg/l dose to give a residual of 0.8 mg/l after the
final water tanks. Phosphate dosing is carried out immediately before distribution.
0
2
4
6
8
10
12
14
16
18
200
2/0
3/2
01
4
21
/04
/20
14
10
/06
/20
14
30
/07
/20
14
18
/09
/20
14
07
/11
/20
14
27
/12
/20
14
ug/l Br
ug/l BrO3
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 113
Backwash water is settled after polyelectrolyte dosing, and the supernatant is returned to the
works inlet.
Figure C.6 Works A5: Schematic
C2.2 DBP Formation
The raw water at the works has low TOC. Over 2013 and 2014, the mean TOC was 0.5 mg/l
(standard deviation 0.2 mg/l). As a result, THM formation is very low, Figure C.7.
Chlorine(no longer used)
Chlorine
GW1 boreholes
Final water
Contact tank
Filters
UV
tank
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 114
Figure C.7 Works A5: Final water THMs
One concern identified at the works has been bromate formation when prechlorination was
used before the filters for iron removal. The results of tests carried out to address the problem
are shown in Table C.1. The water was running to waste at the time of the tests (works flow
2.8 Ml/d).
Table C.1 Works A5: Effect of prechlorination on bromate formation
Date Prechlorine
dose (mg/l)
Raw water (µg/l) Filtered water
1
(µg/l)
Post-UV water
(µg/l)
Bromide Bromate Bromide Bromate Bromide Bromate
30/04/13 0 210 <0.1 213 0.1-0.8 213 0.2
30/04/13 1 135 <0.1 33 3.3-3.8 95 11
01/05/13 2 154 <0.1 36 7.5-21.6 33/32 26.1/24.2
Note:
1. Including samples taken from supernatant water above the filters.
Bromate was seen in the filtered water with prechlorination, and it is believed that this was
being formed from UV in sunlight on the supernatant water. The bromate then increases
further after UV treatment. For this reason prechlorination is no longer used at the works.
To further investigate bromate formation from sunlight, tests were carried out using GW1
water chlorinated and left in buckets exposed to sunlight or in the dark. The results shown in
Figure C.8 indicate the potential for bromate formation from chlorination and sunlight.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 115
Figure C.8 Works A5: Bromate formation due to sunlight
C3 Works B1
C3.1 Works Description
The works treats lowland water with generally low colour (20°H). The catchment is
agricultural, so nutrient levels in the reservoir water are high enough to cause high algal levels
during summer. The maximum design flow is 12 Ml/d, but usually the flow is around 8 Ml/d.
Reservoir water is dosed with lime and ferric sulphate to a coagulation pH of between 4.9 and
5.3. Polyelectrolyte (LT22S) is then dosed prior to 7 hopper bottomed clarifiers. Lime is then
dosed to the clarified water to pH 7.2, followed by chlorination for manganese removal on two
banks of 4 pressure filters. The chlorine (gas) dose is controlled automatically to a set point
before the filters; the set point is adjusted manually to give a residual of 0.1-0.2 mg/l after
around 20 minutes retention time in the filters.
Hydrogen peroxide is dosed to the filtered water to 5.3 mg/l (5 mg/l for Advanced Oxidation
plus 0.3 mg/l to remove remaining chlorine), prior to UV treatment with a dose of 400 mJ/cm2
using a Low Pressure Trojan system. GAC is then used to remove any remaining pesticides,
geosmin/MIB and peroxide. There are 4 GAC beds giving 20 minutes EBCT at 142 l/s
0
5
10
15
20
25
30
0 1 2
Bro
mat
e a
s B
rO3
µg/
l
Hours exposed to strong sunlight (UV index 6)
Cl2 dose 0.5mg/l
Cl2 dose 1.0mg/l
Cl2 dose 2.0mg/l
WQ standard
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 116
(12 Ml/d). Regeneration is planned every 4 years (one per year), and a staggered
regeneration cycle is being developed.
Chlorine (gas) is dosed to the water leaving the GAC to give a residual of 0.9 mg/l after the
first 5 minutes in the contact tank. The minimum contact time (T10) is 35 minutes at maximum
design flow. Sulphur dioxide is dosed for dechlorination to a chlorine residual of 0.5 mg/l. The
residual after the contact tank prior to dechlorination is not monitored, and the CT10
calculation assumes a chlorine concentration of 0.5 mg/l to give a conservative measure.
Lime is dosed to pH 8 immediately before dechlorination, and the water is stored in two Final
Water Tanks before distribution. Routine THM monitoring includes in-works samples as well
as at 5 Service Reservoirs in the distribution system.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 117
Figure C.9 Works B1: Schematic
Ferric sulphateCalcium hydroxide (to pH 4.9)Polyelectrolyte (LT22)
Calcium hydroxide (to pH 7.2)Chlorine residual Chlorine0.1-0.2 mg/l afterfiltration
Hydrogen peroxide
Chlorine residual Chlorine 0.9 mg/l after5 minutes incontact tank
Calcium hydroxide (to pH 8.0)Chlorine residual Sulphur dioxidereduced to 0.5 mg/l
Clarification
Filtration
GAC
Contact tank
Final watertanks
UV
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 118
C3.2 DBP formation
Figure C.10 shows THMs in the water leaving the works, and Figures C.11 and C.12 show
THMs at the two Service Reservoirs (SR1 and SR2) furthest from the works. The seasonal
changes in THMs may result from the influence of water temperature on THM formation, but
may also be linked to seasonal changes in algae (Figure C.13) or raw water TOC (Figure
C.14). However, the treated water TOC is relatively consistent throughout the year, and the
large difference in algal levels between 2013 and 2014 is not reflected in the THM differences,
suggesting the THM variations are primarily related to water temperature.
A significant feature of the THM data is the very high proportion of brominated THMs. This
may result largely from the relatively high bromide in the raw water. Six raw water samples for
bromide in 2013/14 showed a range of 45-192 µg/l, with a mean of 149 µg/l. For the final
water and Service Reservoir samples, trichloromethane represents around 10% of the total
THMs. However, for filtered water, trichloromethane is a higher proportion of the total THMs,
Figure C.15, and is in similar proportions to the brominated species. This may suggest that
UV/peroxide is enhancing the formation of brominated THMs, but is it difficult to draw any firm
conclusions because of the differences in chlorination and contact times between the sample
types. THMs for SR1 in 2010-12, prior to UV implementation, are shown in Figure C.16.
During the period the mean bromide concentration in the raw water was 126 µg/l. The
trichloromethane was a higher proportion of the total THMs, but, again, not enough to allow
firm conclusions to be drawn.
Sampling for bromate mainly in 2014 showed between 1–3.1 µg/l at the GAC inlet (11
samples) falling to 1 µg/l in the final water (7 samples).
Single samples for total HAAs in September 2014 shows levels of 13 µg/l leaving the works
and 19 µg/l at SR1.
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 119
Figure C.10 Works B1: Final water THMs
Figure C.11 Works B1: SR1 THMs
0
10
20
30
40
50
60
18/10/2012 26/01/2013 06/05/2013 14/08/2013 22/11/2013 02/03/2014 10/06/2014 18/09/2014 27/12/2014
Tribromomethane (ug/l)
Dibromochloromethane (ug/l)
Bromodichloromethane (ug/l)
Trichloromethane (ug/l)
Total THM (ug/l)
0
10
20
30
40
50
60
70
80
90
18/10/2012 26/01/2013 06/05/2013 14/08/2013 22/11/2013 02/03/2014 10/06/2014 18/09/2014 27/12/2014
Tribromomethane (ug/l)
Dibromochloromethane (ug/l)
Bromodichloromethane (ug/l)
Trichloromethane (ug/l)
THM Total (ug/l)
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 120
Figure C.12 Works B1:SR2 THMs
Figure C.13 Works B1: Filtered water THMs
0
10
20
30
40
50
60
70
80
90
18/10/2012 26/01/2013 06/05/2013 14/08/2013 22/11/2013 02/03/2014 10/06/2014 18/09/2014 27/12/2014
Tribromomethane (ug/l)
Dibromochloromethane (ug/l)
Bromodichloromethane (ug/l)
Trichloromethane (ug/l)
THM Total (ug/l)
0
5
10
15
20
25
30
35
18/10/2012 26/01/2013 06/05/2013 14/08/2013 22/11/2013 02/03/2014 10/06/2014 18/09/2014 27/12/2014
Tribromomethane Total ug/l
Dibromochloromethane Total ug/l
Bromodichloromethane Total ug/l
Trichloromethane Total ug/l
THM Total ug/l
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 121
Figure C.14 Works B1: Raw water algal counts
Figure C.15 Works B1: Raw and final water TOC
0
100000
200000
300000
400000
500000
600000
700000
18/10/2012 26/01/2013 06/05/2013 14/08/2013 22/11/2013 02/03/2014 10/06/2014 18/09/2014 27/12/2014
Total Blue Green
Total Algal Count
0
1
2
3
4
5
6
7
8
9
10
18/10/2012 26/01/2013 06/05/2013 14/08/2013 22/11/2013 02/03/2014 10/06/2014 18/09/2014 27/12/2014
Final Water TOC (mg/l)
Raw water TOC (mg/l)
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 122
Figure C.16 Works B1: SR1 THMs (2010-12)
C4 Works B2
C4.1 Works Description
The raw water from the reservoir is low alkalinity, and often highly coloured (up to 100°H),
from a catchment with little or no agricultural or human activity. The water is therefore of low
risk in terms of pesticides, pathogens and algal growth. The flow through treatment is around
13 M/ld.
Turbines are installed in the raw water feed pipeline to generate electricity. The water is then
dosed with NaOH and PACl before a flash mixer and flocculators for coagulation at pH 6-7.
The flow then splits between older precipitator clarifiers (4 units) and a new flat bottomed
clarifier, with separate polyelectrolyte (LT22S) dosing to each stream. The clarified water is
dosed with chlorine (gas) to 0.7 mg/l, with NaOH to pH 7, for manganese removal across four
rapid gravity sand filters. The chlorine residual in the filtered water after around 20 minutes in
the filters is 0.3 mg/l.
Further chlorine (gas) is added to 1.1 mg/l before a contact channel giving a few minutes
contact time. The water is then treated with UV to a dose of 40 mJ/cm2 (based on a minimum
UVT of 93% at maximum flow) using two Trojan MP units in parallel, with sleeving of the
lamps to prevent nitrite formation.
Further NaOH is added to the UV treated water to pH 9, before two final water tanks giving
around 6 hours storage. The chlorine residual leaving these tanks is typically around 0.8 mg/l,
for distribution.
Sludge thickening is carried out on site, with return of supernatant to the flash mixer.
0
20
40
60
80
100
120
03/12/2009 21/06/2010 07/01/2011 26/07/2011 11/02/2012 29/08/2012
Tribromomethane (ug/l)
Dibromochloromethane (ug/l)
Bromodichloromethane (ug/l)
Trichloromethane (ug/l)
Total THM (ug/l)
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 123
There are plans to relocate the second chlorine dose to a point after the UV disinfection stage
and reduce the free chlorine residual to about 0.5 mg/l in the distributed water.
Figure C.17 Works B2: Schematic
Polyaluminium chlorideSodium hydroxide (to pH 6-7)
Polyelectrolyte
Chlorine (0.7 mg/l dose)Sodium hydroxide (to pH 7.0)
Chlorine residual Chlorine (1.1 mg/l dose)c. 0.3 mg/l
Sodium hydroxide (to pH 9.0)
Chlorine residualc. 0.8 mg/l
Clarification Clarification
Final watertanks
Flocculation
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 124
C4.2 DBP formation
UV was installed in April 2014. A comparison of DBP formation in April–October 2013 with the
same period in 2014 has been used to identify any influence of the UV treatment.
Figures C.18 and C.19 show final water THMs for 2013 and 2014 respectively, and Figures
C.20 and C.21 show the data for the Service Reservoir (SR1) furthest from the works. The
THMs in the works final water samples are predominantly trichloromethane, whereas the
longer contact time at the SR shows an increased proportion of bromodichloromethane.
Raw and treated water TOC were generally similar between 2013 and 2014 (Figures C.22
and C.23), as were raw water colour levels (Figure C.24 and C.25).
Final water HAA sampling on 2 occasions in 2013 showed low levels (<10 µg/l). Sampling on
a single occasion in 2014 showed higher levels of around 55 µg/l. However, there are
insufficient data to draw any firm conclusions from this.
Bromate was measured in 7 samples in 2014, showing a range of 1.9 to 3.3 and an average
of 2.4.
No nitrite was found in any final water samples taken in 2013 or 2014. Raw water nitrate
levels are generally low.
The results suggest that implementation of the UV has not increase the DBPs measured.
THMs were higher in 2013 before the UV installation, which may result partly from slightly
higher chlorine dose in 2013 than 2014 (1 mg/l in the treated water compared with 0.8 mg/l).
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 125
Figure C.18 Works B2: Final water THMs (April-September 2013)
Figure C.19 Works B2: Final water THMs (April-September 2014)
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
17/03/2013 06/05/2013 25/06/2013 14/08/2013 03/10/2013 22/11/2013
Total THMs (ug/l)
Trichloromethane (ug/l)
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
02/03/2014 21/04/2014 10/06/2014 30/07/2014 18/09/2014 07/11/2014
Total THM (ug/l)
Trichloromethane (ug/l)
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 126
Figure C.20 Works B2: SR1 THMs (2013)
Figure C.21 Works B2: SR1 THMs (2014)
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
17/03/2013 06/05/2013 25/06/2013 14/08/2013 03/10/2013 22/11/2013
Total THM (ug/l)
Trichloromethane (ug/l)
Bromodichloromethane ug/l
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
02/03/2014 21/04/2014 10/06/2014 30/07/2014 18/09/2014 07/11/2014
Total THM (ug/l)
Trichloromethane (ug/l)
Bromodichloromethane (ug/l)
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 127
Figure C.22 Works B2: TOC (2013)
Figure C.23 Works B2: TOC (2014)
0.00
2.00
4.00
6.00
8.00
10.00
12.00
14.00
17/03/2013 06/05/2013 25/06/2013 14/08/2013 03/10/2013 22/11/2013
Raw TOC (mg/l)
Final TOC (mg/l)
0.00
2.00
4.00
6.00
8.00
10.00
12.00
02/03/2014 21/04/2014 10/06/2014 30/07/2014 18/09/2014 07/11/2014
Raw TOC (mg/l)
Final TOC (mg/l)
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 128
Figure C.24 Works B2: Raw water colour (2013)
Figure C.25 Works B2: Raw water colour (2014)
0.00
10.00
20.00
30.00
40.00
50.00
60.00
17/03/2013 06/05/2013 25/06/2013 14/08/2013 03/10/2013
Raw water colour (mg/l)
0.00
10.00
20.00
30.00
40.00
50.00
60.00
02/03/2014 21/04/2014 10/06/2014 30/07/2014 18/09/2014 07/11/2014
Raw water colour (mg/l)
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 129
C5 Works D2
C5.1 Works Description
The works is fed by three borehole sources, the number used at any time depending on
demand. Borehole 3 (maximum flow 35 l/s) has high pesticides (trietazine and bentazone),
and is treated with high dose UV (design dose based on power consumption of 0.24 kWh/m3).
There are three Trojan LP units, one as standby. UV treated water is then blended with water
from Boreholes 4 and 5 (maximum flows 45 and 27 l/s, respectively), and a required
proportion of the blended water is treated by ion exchange nitrate removal before being
blended back prior to chlorination. Chlorine (gas) is dosed to typically 0.6 mg/l prior to a
contact tank giving around 1-hour storage. There is very little reduction in chlorine
concentration across the contact tank, and the residual leaving the tank is monitored. The
water is than held in a balance tank for around 30 minutes before distribution. The maximum
design flow is 86 l/s, but actual flows are between 27 and 80 l/s.
Figure C.26 Works D2: Schematic
Borehole 4Borehole 5
Chlorine (0.6 mg/l dose)
Balance tank
Borehole 3
UV (x3)
Ion exchange
Contact tank
DWI
WRc Ref: Defra 10459.04/16164-0 March 2015
© WRc plc 2015 130
C5.2 DBP formation
THM samples taken in distribution since implementation of UV (12 samples over the past 5
years) show very low levels (<20 µg/l total THMs), reflecting the low chlorine demand of the
water. Nitrite concentrations in the final water have been non-detectable over the past three
years, although any nitrite formed by UV would be removed by chlorine. The low chlorine
demand suggests that nitrite formation would not be an issue, consistent with the use of LP
lamps rather than MP. Initial pilot plant trials at the site raised potential problems with nitrite
from MP systems, because of the high nitrate. No bromate data are available, but bromide in
the raw water is very low, so any potential for bromate production would be expected to be
negligible.