EF LD Software All of the equipment in the INGEPAC family can be accessed using powerful software tools developed by Ingeteam and which run on Windows ® . The application software is specifically designed for simple and user-friendly access to the equipment. INGEPAC ® EF LD equipment is the perfect solution for completely protecting and controlling high- voltage overhead transmission or undertransmission lines. INGEPAC EF LD includes complete remote protection functions, making it possible to combine differential / distance protection functions with different configurations (main and backup), in one single device, facilitating purchasing and reducing associated maintenance costs. Its design is compliant with all the requirements of standards in the electrical sector, including IEC 61850.Besides having powerful logging features, it provides comprehensive, detailed information, making it possible to monitor and analyse events, these being fundamental elements in an electrical grid’s improvement process. Line Differential Control & Protection Relay Differential Functions 87: Differential line protection (instantaneous and percentual) 2nd harmonic braking and blocking (cross blocking) 87R: Restrained earth V/f Overexcitation and 5th harmonic Directional supervision CT error Saturation detector Load compensation Function 86 Distance Functions Quadrilateral and MHO (5 areas) 21 High speed Zone 1 extension Double line adaptation Serial compensation line adaptation Line adaptation with CVT (Capacitive Voltage Transformers) General Protection Functions SOTF Switch onto fault 27 Undervoltage 59 Overvoltage 59N Neutral overvoltage 47 V2 overvoltage Frequency (81M/m) Frequency rate of change (81R) 32 power units 3x50/51 (67) 50N/51N (67N) 50G/51G. Earthing overcurrent 46TOC (67Q), 46IOC(67Q) 46BC Open phase 50CSC Second harmonic breaking 50CSC Second and fifth harmonic blocking 37 Undercurrent 49 Thermal image Stub bus Teleprotection (21) Teleprotection (67/67Q) Monitoring Units 68LE Load encroachment 68FF Fuse failure 78 Power swing Fault locator Breaker Monitoring kI2 breaker monitoring per pole Closing and trip circuit monitoring Excessive number of trips Dead line / open pole detector Breaker status logic Pole discordance Breaker failure (50BF) Automatic Operations Synchronism Single-pole/three-pole recloser Coupling Data Acquisition Functions Phase and neutral current metering Phase and synchronism voltage metering Active and reactive power Active and reactive energy Chronological historical event, incident and fault recording Breaker monitoring Oscillography Metering logs 74TC CC OPTIONAL BASIC FUNCTIONS 52 50/51G 49 50 STUB 50BF BC 87L 21P 21N 87N 25 79 27/59 47 81 81R 68LE 78 68FF SOF FL 67 59N 24 37 32 67N 67Q 85

EFLD - adaptaust.com.auadaptaust.com.au/wp-content/uploads/2017/11/... · Line Differential Control & Protection Relay ... Line adaptation with CVT (Capacitive Voltage ... ∙ Leakage

  • Upload
    vophuc

  • View
    232

  • Download
    0

Embed Size (px)

Citation preview

Page 1: EFLD - adaptaust.com.auadaptaust.com.au/wp-content/uploads/2017/11/... · Line Differential Control & Protection Relay ... Line adaptation with CVT (Capacitive Voltage ... ∙ Leakage

EF LD

SoftwareAll of the equipment in the INGEPAC family can be accessed using powerful software tools developed by Ingeteam and which run on Windows®.The application software is specifically designed for simple and user-friendly access to the equipment.

INGEPAC® EF LD equipment is the perfect solution for completely protecting and controlling high-voltage overhead transmission or undertransmission lines. INGEPAC EF LD includes complete remote protection functions, making it possible to combine differential / distance protection functions with different configurations (main and backup), in one single device, facilitating purchasing and reducing associated maintenance costs. Its design is compliant with all the requirements of standards in the electrical sector, including IEC 61850.Besides having powerful logging features, it provides comprehensive, detailed information, making it possible to monitor and analyse events, these being fundamental elements in an electrical grid’s improvement process.

Line DifferentialControl & Protection Relay

Differential Functions 87: Differential line protection (instantaneous and percentual) 2nd harmonic braking and blocking (cross blocking) 87R: Restrained earth V/f Overexcitation and 5th harmonicDirectional supervision CT error Saturation detector Load compensation Function 86 Distance Functions Quadrilateral and MHO (5 areas) 21 High speed Zone 1 extension Double line adaptation Serial compensation line adaptation

Line adaptation with CVT (Capacitive Voltage Transformers) General Protection Functions SOTF Switch onto fault 27 Undervoltage 59 Overvoltage 59N Neutral overvoltage 47 V2 overvoltage Frequency (81M/m) Frequency rate of change (81R) 32 power units 3x50/51 (67) 50N/51N (67N) 50G/51G. Earthing overcurrent46TOC (67Q), 46IOC(67Q) 46BC Open phase 50CSC Second harmonic breaking 50CSC Second and fifth

harmonic blocking 37 Undercurrent49 Thermal image Stub busTeleprotection (21) Teleprotection (67/67Q) Monitoring Units 68LE Load encroachment 68FF Fuse failure 78 Power swing Fault locator Breaker Monitoring kI2 breaker monitoring per pole Closing and trip circuit monitoring Excessive number of trips Dead line / open pole detector Breaker status logicPole discordance Breaker failure (50BF)

Automatic Operations Synchronism Single-pole/three-pole recloserCoupling Data Acquisition Functions Phase and neutral current metering Phase and synchronism voltage metering Active and reactive power Active and reactive energy Chronological historical event, incident and fault recording Breaker monitoring OscillographyMetering logs

74TC CC

OPTIONALBASIC FUNCTIONS

52

50/51G49 50STUB50BFBC

87L 21P 21N87N

25 79 27/59 47 81 81R

68LE7868FF SOF

FL67

59N

24

37

32

67N 67Q85

Page 2: EFLD - adaptaust.com.auadaptaust.com.au/wp-content/uploads/2017/11/... · Line Differential Control & Protection Relay ... Line adaptation with CVT (Capacitive Voltage ... ∙ Leakage

The

tech

nica

l dat

a in

this

cat

alog

ue is

sub

ject

to c

hang

e w

ithou

t prio

r not

ice.

FY

48IP

TT01

_A/1

2201

4

Main FeaturesInsulation and Electromagnetic Tests ∙ Dielectric strength IEC 60255-5 ∙ Insulation resistance IEC 60255-5 ∙ Impulse voltage IEC 60255-5 ∙ 1 MHz damped wave

immunity test IEC 60255-22-1 ∙ Immunity to industrial

frequencies IEC 60255-22-7 ∙ Leakage current IEC 60255-27 ∙ Electrostatic discharge

immunity test IEC 61000-4-2 ∙ Immunity to radiofrequency

radiated fields IEC 61000-4-3 ∙ Fast transient burst

immunity IEC61000-4-4 ∙ Surge pulses immunity test IEC 61000-4-5 ∙ Immunity to radiofrequency

induced signals IEC 61000-4-6 ∙ Harmonics IEC 61000-4-7 ∙ Immunity to 50Hz magnetic

fields IEC 61000-4-8 ∙ Immunity to pulsing

magnetic fields IEC61000-4-9 ∙ Immunity to damped

oscillatory magnetic fields IEC 61000-4-10 ∙ Immunity to interruptions

and dips in DC power supply IEC 61000-4-11 ∙ Ripple immunity in DC power

supply IEC 61000-4-17 ∙ Damped oscillatory waves

immunity IEC61000-4-18 ∙ Immunity to interruptions,

dips and variations in DC power supply IEC 61000-4-29

∙ Radioelectrical emissions EN 61000-6-4

∙ Earth continuity IEC 61131-2

Climatic ∙ Cold low temperature test IEC 60068-2-1 ∙ Dry heat test IEC 60068-2-2 ∙ Thermal shock IEC 60068-2-14 ∙ Humid heat, cyclical test IEC 60068-2-30 ∙ Humid heat continuous test IEC 60068-2-78 ∙ External protection level IEC60529

Mechanical ∙ Vibrations test IEC 60255-21-1 ∙ Shock and bump test IEC 60255-21-2 ∙ Seismic tests IEC 60255-21-3

∙ The equipment is suitable for lines with 2 and 3 ends, or for lines with intermediate transformers. ∙ It allows you to synchronise different ends without the need for GPS, via communications. ∙ 1 or 2 serial channels (RS232, multi-mode OF or single-mode OF), for simple or redundant commu-

nications between devices. ∙ Different hardware configuration variants allowing you to define suitable equipment for the applica-

tion. ∙ Distance protection: 5 separate areas of action with mho and/or quadrangular characteristics in each

of them. Direction can be selected for each area: forward, reverse or non-directional ∙ Analysis per phase combination (AN,BN,CN,AB,BC,CA), characteristics (Quadrangular and Mho)

and area of action. ∙ Single-phase or three-phase triggers and applicable with or without teleprotection schemes. ∙ Backup units; overcurrent, overvoltage, undervoltage, frequency, etc. ∙ Distance units supervision; power oscillation, load area, fuse failure, etc. ∙ Backup functions 21 and 67 can be blocked if the differential is operative and enabled automatically

with communications failure. ∙ Adaptation to lines with capacitive voltage transformers (CVT). ∙ Fault locator for reducing down times. ∙ Automatic operations: recloser, synchronism. ∙ Single protection and control, multi-protocol, native IEC61850 platform ∙ Graphic and textual programming for operation logic based on IEC61131-3. ∙ Chronological logging of events, failure reports, load curves and oscillographs facilitates the complete

analysis of events. ∙ Measurement: Current, voltage, power, power factor, energy, frequency, negative sequence current,

demand maximeter, THD, fundamental values and RMS. ∙ Front panel for setting and display. 4.9” monochromatic graphic display, programmable function keys

with 2 LEDs each, 19 programmable LEDs and 1 fixed two-colour hardware status LED, numerical keypad, menu keys, and 9 programmable graphics pages.

∙ Up to 6 serial and 2 Ethernet rear ports ∙ Ethernet RJ45 and USB port on the front. ∙ Equipment synchronisation through NTP server, demodulated IRIG-B or from global references via

communications protocols. ∙ Web server for monitoring and adjustments without needing in-house tools.

Options

∙ Two housing types: 1/2 x 19’, 5U rack and 19’, 4U rack, which can contain the following modules in different configurations:

11 digital inputs and 9 digital outputs16 digital inputs and 16 digital outputs16 digital inputs and 8 digital outputs32 digital inputs16 digital inputs and 8 analog inputs16 digital inputs and 8 analog inputs (4 isolated)8 digital inputs, 4 digital outputs and 4 high break contact outputs8 digital inputs and 8 digital outputs

∙ Selectable rear port connectivity:Up to 6 serial communicationsUp to 2 Ethernet communications

∙ Serial ports in glass optic fibre (multi-mode or single-mode), plastic optic fibre, RS232 or RS485. ∙ Protocols: IEC 61850, PROCOME, DNP3.0. ∙ HSR, PRP, or link failover redundancy.Ethernet ports in glass optic fibre or RJ45. ∙ 1 or 2 OF single-mode channels for differential protection. ∙ Different models for auxiliary voltages most commonly found in electrical installations. ∙ RIO module capturing (remote inputs and outputs). ∙ Redundant power supply source. ∙ Up to 2 ports for teleprotection that comply with C37.94 or G.703 standards.

Applications

∙ Primary or secondary protection for cables, overhead or mixed lines in transmission and undertrans-mission grids.

∙ Main protection for T lines. ∙ Grid Automation.

General Description