EFT3 SERIES
Series Voltage In
EFT3
Office: 718-418-5600 • Fax: 718-418-561857-10 49th Place • Maspeth, N.Y. 11378www.encorelighting.com P/N75-1036 (02/07)
Wattage (VA)
Description:The series EFT3 is a central inverter system for emergency lighting applications. The series EFT3 is FAST TRANSFER, achieving transfer from normal AC input to battery output within 2 milliseconds and will power both normally on and off lighting loads including incandescent, fluorescent, and HID.
Electrical:Input and output voltage is 120/208 VAC or 277/480VAC 3 phase, 4 wire, +/- 10 %.All units have an input circuit breaker. Harmonic distortion is < 10 %. Power factor is .5 lag/lead.
Compatible Lamp Sources:Incandescent, fluorescent, and HID. Normally ON and OFF loads, including cold starts.
ORDERING INFORMATIONSAMPLE CAT#: EFT3-120/208-6000-120/208-LC-**
120/208277/480
Metering:The control panel is a micropro-cessor controlled 2X20 LCD display with touchpad. Display shows input/output voltage, battery voltage, battery & output current, output VA and temperature. Unit includes an RS232 port (DB9) and is programmable for monthly and yearly testing. Display maintains a memory record of the 50 most recent failure events.
Listing/Code Compliances:UL924 listedNFPA101
Fast Transfer Inverter3 Phase, 4 Wire4.8 kva - 50 kvaIncandescentFluorescent HID
Construction:Enclosure is NEMA Type 1, 14 gauge steel, powder coated finish. Unit has 2 front hinged doors with security locks.
Battery:Sealed maintenance free Lead Calcium is standard. NICAD and Long Life Lead are also available. Lead Calcium batteries are front access style for easy installation and maintenance. Automatic low voltage disconnect is standard.Environmental:< 10,000 feet above sea level, without derating. Less than 95% non-condensing humidity. Ambient operating temperatures range from 32 F to 95 F.Performance:Inverter unit is a standby UPS type, pulse width modulation achieving transfer to emergency in 2 ms, fast enough to power incandescent, fluorescent, or HID lamp sources. Unit run time is 90 minutes standard, other run times are available, consult factory. Unit includes a maintenance bypass switch.
Warranty:1 year standard warranty includes parts & labor. Batteries are covered by a 10 year pro-rated warranty.
4,800 16,700 6,000 24,000 8,000 33,00010,000 40,00012,500 50,000
Voltage Out
120/208277/480
Battery Type
LC Lead CalciumLL Long Life LeadNC Nickel Cadmium
Options
Commercial Pi BT Shift & B
Model Number
VA Rating
# of Electrical Cabinets
# of Battery
Cabinets
Inverter Cabinet
Weight (lb)
Battery Cabinet
Weight (lb)
Total System
Weight (lb)# of
Batteries
*Max Util. Input Amps
*Heat Loss % BTUs
EFT3-** 4800 1 1 30 46 22 30 46 22 440 1038 1478 12 55 245
EFT3-** 6000 1 1 30 46 22 30 46 22 440 1260 1700 15 68 300EFT3-** 8000 1 2 30 46 22 30 46 22 440 890 2220 20 91 400
EFT3-** 10000 1 2 30 46 22 30 46 22 520 1038 2596 24 114 500EFT3-** 12500 1 2 30 46 22 30 46 22 520 1260 3040 30 142 660
EFT3-** 16700 1 3 30 46 22 30 46 22 520 1137 3930 40 190 840EFT3-** 24000 1 2 44 72 31 48 72 31 665 2400 5465 60 273 1200
EFT3-** 33000 1 2 44 72 31 48 72 31 775 3150 7075 40 375 1500EFT3-** 40000 1 3 44 72 31 48 72 31 855 2650 8805 100 455 1960
EFT3-** 50000 1 3 44 72 31 48 72 31 975 3150 10425 60 568 2520