EGR 360 design.doc

Embed Size (px)

Citation preview

  • 7/28/2019 EGR 360 design.doc

    1/18

    Thermodynamics Design Project:

    Automotive Air-Conditioning System

    by

    Brad Hazard

    EGR 312: Thermodynamics

    Grand Valley State University

  • 7/28/2019 EGR 360 design.doc

    2/18

    Instructor: Dr. Mehmet Sozen

    November 30, 2007

    Introduction:

    The Montreal Protocol has ceased production on R-12 (Freon). As a result, new

    automotive air conditioning systems have been switched to R-134a. R-134a is a highpressure refrigerant with zero ozone depleting potential but with a global warming

    potential that is not acceptable. As a result, new compressor designs along with

    substitute refrigerants are being investigated. The purpose of this project is to evaluatethe feasibility of a new compressor design; a constrained rotary vain design for use in an

    automotive air-conditioning system. The new constrained rotary vane compressor will be

    placed in the vapor compression refrigeration cycle for the purposes of this project. The

    proposed compressor has a compression ratio of 3.6, but the ratio can be adjusted up to6.0 if justification is given. The compressor utilizes four vanes as shown in Figure 1.

    This allows four inlet volumes to be compressed each rotation. The compressor body,

    vanes, and rotor can be produced for various compressor widths depending on the density

    of the refrigerant chosen by the designer.

    Figure 1: Emerald Model 414 Compressor

    The engine speed has a direct effect on the compressor speed, and the refrigerant flow

    rate depends on compressor speed. The system for this project is to be designed to

    deliver 20,000 Btu/hr of cooling at an engine speed of 2,000 rpm. The volumetricefficiency is 90% and the compressor isentropic efficiency is 70%. The refrigerant can

    be assumed to enter the compressor as saturated vapor and leave the condenser as

    saturated liquid. The expansion valve in the system can be treated as an isenthalpicdevice. The refrigerant enters the evaporator at a speed of 100 ft/sec. A 15 F to 25 F

    temperature difference is needed between the refrigerant and the relevant thermal

    reservoir. The thermal reservoirs for the system are going to be assumed to be 180 F forthe hot reservoir and 65 F for the cold reservoir in the worst case scenario. A schematic

    of the system is shown in Figure 2, with all relevant data shown.

    2

  • 7/28/2019 EGR 360 design.doc

    3/18

    Figure 2: Schematic of the Vapor Compression refrigeration System

    System Analysis:

    Choice of Refrigerant:

    The choices of possible refrigerants for the system include R-134a, R-124, or R-152a.The refrigerant that is being replaced is R-12, therefore, a saturation curve that is

    relatively close to the saturation curve of R-12 is desirable. The saturation curves for the

    four refrigerants under investigation are shown in Figure 3.

    3

    Saturated

    Vapor

    FTC

    65=

    sec

    ft100V =

    FTH

    180=

    Saturated

    Liquid

    1

    2

    3

    Condenser

    Evaporator

    Compressor

    Expansion

    Valve

    cW

    %70=c

    outQ

    h

    Btu000,20=inQ

    4

  • 7/28/2019 EGR 360 design.doc

    4/18

    0

    100

    200

    300

    400

    500

    600

    700

    40 90 140 190 240 290

    Temperature (F)

    Pressure(lbf/in

    ^2)

    R-152a R-124 R-134a R-12

    Figure 3: Saturation Curves for R-152a, R-134a, R-124, and R-12 [1]

    Based on the saturation curve, R-152a, is the best choice since it has the closest curve toR-12. R-134a is also very close however, and is a possibility. The saturation curve for

    R-124 differs from the curve for R-12, but it has lower operating pressures at the desired

    operating temperatures, making it a good choice.

    Properties of the refrigerants should also be considered for the selection of refrigerant.

    R-124 is known to be ozone depleting and dangerous for the environment, making it a

    bad choice. R-152a is known to be extremely flammable, which is problematic for usenear an internal combustion engine. R-134a is not known to have any effects on the

    ozone, it is not flammable, and it actually has a slightly lower pressure at given

    temperatures compared to the other refrigerants. It is also known to be compatible withthe materials that will need to be used in the system [2]. Therefore, R-134a is the best

    choice of refrigerant based on its saturation curve and known properties.

    Since R-134a was chosen, U factors for the heat exchangers are given in the project to be

    U (evaporator to air) =Rfth

    Btu

    ft

    m

    W

    hBtu

    R

    K

    Km

    W 2

    2

    28326.527

    2808.3

    1

    1

    413.3

    8.1

    13000 =

    U (condenser to air) =Rfth

    Btu

    ft

    m

    W

    hBtu

    R

    K

    Km

    W 2

    2

    23969.440

    2808.3

    1

    1

    413.3

    8.1

    12500 =

    State Calculations:

    Since the refrigerant has been chosen, the high and low pressures and the corresponding

    temperatures need to be chosen for the system. It is known that the temperatures for thehot and cold reservoirs in the worst case scenario are 180F and 65F respectively. For

    4

  • 7/28/2019 EGR 360 design.doc

    5/18

    design purposes, the high and low temperatures of the refrigerant should be about 15F to

    25F different from the corresponding thermal reservoir. The high pressure chosen is

    480 psi with a corresponding saturation temperature of 195.75F. The low pressurechosen is 60 psi with a corresponding saturation temperature of 49.89F. Therefore, the

    last requirement to be checked is that the compression ratio is under 6.0.

    The properties of the given states shown in Figure 2 can now be evaluated in a state chart.

    The following properties of the states were found using tables given for R-134a [3].

    State 1: Saturated Vapor, Pressure = 60 psi.

    Therefore, v1 = vg (60 psi) = 0.7887 ft3/lb

    h1 = hg(60 psi) = 108.72 Btu/lb

    s1 = sg (60 psi) = 0.2183 Btu/lbR

    State 2: Pressure = 480 psi, Superheated Vapor,

    s2s = s1 = 0.2183 Btu/lbR

    With interpolation in excel, (Figure 1A, Appendix A) h2s = 127.35 Btu/lb

    ( )

    ( ) lbBtu

    33.135h70.0

    lb

    Btu72.108h

    lb

    Btu72.10835.127

    hh

    hh2

    212

    12scompressor ==

    =

    =

    With interpolation,

    v2 = 0.08187 ft3/lb

    s2 = 0.23013 Btu/lbR

    State 3: Saturated Liquid, Pressure = 480 psi , with interpolation v3= vf (480psi) = 0.01964 ft3/lb

    h3 = hf(480psi)= 84.306 Btu/lb

    s3 = sf (480psi) = 0.1539 Btu/lbR

    State 4: Throttling Process, h4 = h3 = 84.306 Btu/lb

    The compressor ratio can now be found very simply by dividing the inlet volume by the

    exit volume. Since the mass flow rates are the same on both sides of the compressor, the

    specific volume can be used and

    63.9

    08187.0

    7887.0

    ratioCompressor 3

    3

    2

    1 ===

    lb

    ftlb

    ft

    vv .

    The compression ratio is constrained however and therefore the design needs to change.

    The lower temperature needs to stay the same, about 50F so the passengers in the car can

    remain comfortable at 65F. The worst case scenario of 180F can no longer be plannedfor however. The given compression ratio of 3.6 is also not feasible because it would not

    5

  • 7/28/2019 EGR 360 design.doc

    6/18

    work at higher temperatures. The high temperature of the refrigerant needs to be lowered

    so the design requirements of the project are met. Since the max compression ratio is 6,

    the minimum v2 is

    lbftlb

    ft

    vv

    3

    3

    21 13145.0

    6

    7887.0

    RatioonCompresssi ===

    For this to occur the high pressure becomes 375 psi and the high temperature of the R-134a becomes 174.46F as shown in the following calculation for the states.

    States 2, 3, and 4 now become:

    State 2: Pressure = 375 psi, Superheated Vapor,

    s2s = s1 = 0.2183 Btu/lbR

    With interpolation done in excel (Figure 2A, Appendix A)

    h2s = 124.5674 Btu/lb (Appendix A)

    ( )

    ( ) lb

    Btu3591.131h70.0

    lb

    Btu72.108h

    lb

    Btu72.1085674.124

    hh

    hh2

    212

    12scompressor ==

    =

    =

    With interpolation,

    v2 = 0.13266 ft3/lb

    s2 = 0.2287 Btu/lbR

    State 3: Saturated Liquid, Pressure = 375 psi

    Therefore, v3= vf (375psi) = 0.01715 ft3

    /lb h3 = hf(375psi) = 73.54 Btu/lb

    s3 = sf (375psi) = 0.13775 Btu/lbR

    State 4: Throttling Process, h4 = h3 = 73.54 Btu/lb, Pressure = 60 psi

    The specific volume can then be determined based on the quality.

    ( ) 557.014.2443.10714.2754.73 == xlb

    Btux

    lb

    Btu

    lb

    Btu

    lb

    ft

    lb

    ft

    lb

    ftv

    333

    4 445.0)01270.07887.0)(557.0(01270.0 =+=

    The compressor ratio is therefore,

    95.5

    13266.0

    7887.0

    ratioCompressor3

    3

    2

    1 ===

    lb

    ft

    lb

    ft

    v

    v

    6

  • 7/28/2019 EGR 360 design.doc

    7/18

    The four states were put into a state chart to show all relevant data. The state chart is

    shown in Table 1.

    Table 1: State Chart

    StatePressure

    (psi)

    Temperature

    (F)Composition v (ft3/lb) h (Btu/lb) s (Btu/lb)

    1 60 49.89 SaturatedVapor

    0.7887 108.72 0.2183

    2 375 203.31Superheated

    Vapor0.1327 131.36 0.2287

    3 375 174.46Saturated

    Liquid0.0172 73.54 0.1378

    4 60 49.89

    Mixture of

    vapor and

    liquid

    0.445 73.54 -

    The T-s diagram is shown below with the four states indicated is shown in Figure 4 andthe p-h Diagram is shown in Figure 5.

    0

    1020

    30

    40

    5060

    70

    80

    90100

    110

    120130

    140

    150

    160

    170180

    190

    200

    210220

    230

    20 25 30 35 40 45

    Entropy (Btu/lb*R)

    Temp.

    (deg.F

    )

    375 psi

    60 psi

    14

    3

    22s

    Tlow=49.89 Deg. F

    Thigh=174.46 Deg. F

    Figure 4: T-s Diagram

    7

  • 7/28/2019 EGR 360 design.doc

    8/18

    Figure 5: P-h Diagram

    Mass Flow Rate:

    The required mass flow rate to provide 20,000 Btu/hr of cooling at 2000 rpm can becalculated by doing an energy balance on the evaporator. It can be assumed that there is

    no work done on or by the evaporator and there is no Kinetic or Potential Energy change.

    Therefore, the mass flow rate can be determined knowing the properties at state 4 andstate1:

    ( ) ( )min

    47.950.56854.7372.108000,2041lb

    h

    lbm

    lb

    Btum

    h

    BtuhhmQin ===== .

    Compressor Calculations:

    8

    1

    2s

    1 23

    4

  • 7/28/2019 EGR 360 design.doc

    9/18

    The width of the compressor can be determined for a given cross sectional area of the

    inlet chamber of 1.50 in2. The volumetric flow rate for the compressor with the engineturning at 2000 rpm is known to be

    ( ) 14min

    2000 vmVEchamber

    Vrev

    chambersrevV ==

    where V is the volume of the chamber and is the cross sectional area times the width of

    the compressor and VE is the volumetric efficiency.

    The width of the compressor is therefore

    ( )

    inft

    in

    inrev

    rev

    lb

    ftlb

    w 195.11

    12

    )9.0(5.14

    min2000

    7887.0min

    47.9 3

    2

    3

    =

    = .

    The diameters of the inlet and exit hoses to the compressor can be determined with the

    known mass flow rate throughout the system and the known velocity into the evaporator.

    The area of the hose required for a given velocity and mass flow rate is known to be

    V

    vmA

    =

    where A is the area of the hose, m is the mass flow rate, v is specific volume, and V is

    the velocity.

    The cross sectional area of the hose entering the evaporator is therefore:

    2

    3

    0007026.0

    100

    sec60

    min1445.0

    min47.9

    ft

    s

    ft

    lb

    ftlb

    A =

    = .

    It can be assumed that the hose exiting the evaporator is the same size as the hose

    entering the evaporator and therefore the same size as the inlet hose to the compressor.

    The diameter of the inlet hose is therefore

    inft 3589.00299.0)6ft4(0.0007024A

    DiameterHoseInlet2

    ====

    .

    The velocity through the compressor is constant so the velocity at state 1 is needed. It

    can be found to be

    9

  • 7/28/2019 EGR 360 design.doc

    10/18

    sec2353.177

    0007026.0

    sec60

    min17887.0

    min47.9

    2

    3

    1 ft

    ft

    lb

    ftlb

    A

    vmV =

    == .

    The area at the exit of the compressor, or state 2, is therefore

    2

    3

    0001181.0

    2353.177

    sec60

    min11327.0

    min47.9

    ft

    s

    ft

    lb

    ftlb

    A =

    = .

    The diameter of the exit hose from the compressor is then found to be

    inft 1471.001226.0

    )1ft4(0.0001184A

    DiameterHoseExit

    2

    ==== .

    Power required to run the system:

    The power required to run the system is the power that is needed for the compressor. It

    can be assumed that there is no heat lost or added in the compressor and that there is no

    change in potential or kinetic energy. An energy balance results in

    .619.52545

    146.12870

    9.0/)72.10836.131(50.586/)( 12

    hp

    hBtuhp

    h

    Btu

    lb

    Btu

    h

    lbhhmW mechc

    =

    =

    ==

    Condenser Calculations:

    The cooling rate in the condenser can be calculated by doing an energy balance. It can be

    assumed that there is no work done on or by the condenser and there is no Kinetic or

    Potential Energy change. Therefore, the cooling rate can be determined knowing theproperties at state 2 and state 3:

    ( ) ( )h

    BtulbBtu

    hlbhhmQout 46.870,3254.7336.13150.56832 ===

    The type of condenser that is given in the project is a cross-flow design with both fluids

    unmixed. A drawing of this type of heat exchanger is shown in Figure 1B of AppendixB. The area that the condenser must be can be calculated knowing

    10

  • 7/28/2019 EGR 360 design.doc

    11/18

    mTUF

    QA

    =

    (1)

    where A is the area, Q is the cooling rate, U is a given Factor, F is a correction factor

    for a cross-flow heat exchanger, and Tm is the log mean temperature difference.

    The log mean temperature difference is given by

    ( )

    =

    1

    2

    12

    lnT

    T

    TTTm

    (2)

    where T1 is the change in high temperature for the refrigerant and the air, and T2 is the

    change in low temperatures for the refrigerant and the air.

    The high and low temperatures for the condenser occur at state 2 and state 3, which is

    shown in Table 1. The high and low temperatures of the air are limited by the saturation

    temperature at 375 psi. The worst case scenario that can be accounted for is therefore15F below the saturation temperature of 174.46F, or 159.46F. Therefore, the high and

    low temperatures for the condenser are known to be:

    TR-134a,1 = 203.31 F = 662.98 RTR-134a,2 = 174.46 F = 634.13 R

    Tair,1 = 174.46 F = 634.13 R

    Tair,2 = 159.46 F = 619.13 R

    The log mean temperature difference is therefore

    ( )

    ( )

    R

    R

    R

    RTm

    17543.21

    13.63498.662

    13.61913.634ln

    ))13.63498.662()13.61913.634(( =

    =.

    The correction factor F can be determined based on the plot shown in Figure 2B of

    Appendix B for an unmixed counter-flow heat exchanger.

    ( )( )342.0

    13.61998.66213.61913.634

    21134

    21 === RR

    TTTTP

    airaR

    airair

    ( )

    ( )923.1

    13.61913.634

    13.63498.662

    21

    21341134 ==

    = R

    R

    TT

    TTR

    airair

    aRaR

    Therefore, F is approximately 0.91.

    11

  • 7/28/2019 EGR 360 design.doc

    12/18

    The area of the condenser must be

    ( )

    2

    2

    87.3

    175.2191.040.440

    46.870,32

    ft

    RRhft

    Btu

    h

    Btu

    A =

    =

    .

    The mass flow rate can be determined based on

    ( ) airairair TcmhhmQ == 32

    where cair is the specific heat, based on pressure, between 174.46F and 159.46F.

    The average temperature for the temperature change of the air is 166.96F. cair can be

    interpolated at this value to get 0.241 Btu/lbR. The mass flow rate of the air is therefore

    ( ) min75.1519105

    13.61913.634241.0

    46.32870lb

    h

    lb

    RRlb

    Btuh

    Btu

    Tc

    Qm

    airair

    air ==

    =

    =

    .

    Evaporator Calculations:

    The air flow rate in the evaporator can be calculated based on the temperature difference

    of the refrigerant R-134a and the temperature difference of the air. In the worst case

    scenario, the ambient air temperature will enter the heat exchanger at around 100F andwill need to drop to 65F to provide the passengers with a comfortable environment. The

    temperatures of the refrigerant are the temperatures of state 4 and state 1. The

    temperatures are therefore:

    TR-134a,1 = 49.89 F = 509.56 R

    TR-134a,2 = 49.89 F = 509.56 RTair,1 = 100 F = 559.67 R

    Tair,2 = 65 F = 524.67 R

    Using Equation (1), the log mean temperature difference is

    ( )

    ( )

    R

    R

    R

    RTm

    1943.29

    56.50967.559

    56.50967.524ln

    )))56.50967.559()56.50967.524(( =

    =.

    Since the temperature difference of the R-134a is zero across the evaporator, the

    correction factor F is 1.

    12

  • 7/28/2019 EGR 360 design.doc

    13/18

    The area of the evaporator must be

    ( )( )

    2

    2

    298.1

    1943.2918326.527

    000,20

    ft

    RRhft

    Btu

    h

    Btu

    A =

    =

    .

    The mass flow rate in the evaporator can be determined based on

    ( ) airairair TcmhhmQ == 41

    where cair is the specific heat of air, based on pressure, between 100F and 65F.

    cair can be found to be 0.240 Btu/lbR. The mass flow rate of the air is therefore

    ( ) min68.3995.2380

    67.52467.559240.0

    000,20 lb

    h

    lb

    RRlb

    Btuh

    Btu

    Tc

    Qm

    airair

    air ==

    =

    =

    .

    Effect of Isentropic Efficiency:

    The effect of the isentropic efficiency on the cooling capacity of the system can be seen ifan energy balance is done on the system. It can be assumed that there is no change in

    potential, kinetic, or internal energy for the system. Therefore, the energy balance results

    in

    inoutcnetnetQQWQW == (3)

    where netW is the net work of the system, netQ is the net heat transfer of the system,

    cW is the work of the compressor, inQ is the heat transfer into the system, or the

    cooling capacity, and outQ is the heat transfer out of the system.

    For the purpose of this analysis, outQ is assumed to be constant at the rate that was

    previously calculated, 32,870.46 Btu/hr. Therefore, the cooling capacity, or inQ , can be

    determined based on how cW changes. The work of the compressor is known to equal

    )(12hhmW

    c = . (4)

    The enthalpy at state 2 is calculated based on the isentropic efficiency,

    13

  • 7/28/2019 EGR 360 design.doc

    14/18

    1

    compressor

    12s2

    hhhh +

    =

    .

    (5)

    Equation (5) can be substituted into Equation (4) to obtain

    =

    compressor

    s

    c

    hhmW

    12 . (6)

    Equation (6) can be placed into Equation (3) to obtain

    inoutcompressor

    s QQhh

    m =

    12. (7)

    Equation (7) can be rearranged to obtain

    =

    compressor

    soutin

    hhmQQ

    12 . (8)

    Therefore, the cooling capacity is inversely related to the compressor efficiency. Since

    outQ , m , h2s, and h1 are known for the system to be 32,870.46 Btu/h, 568.50 lb/h,

    124.5674 Btu/lb, and 108.72 Btu/lb respectively. A plot of the cooling rate versus the

    isentropic efficiency ranging from 50 to 90% is shown in Figure 6.

    12000

    14000

    16000

    18000

    20000

    22000

    24000

    0.45 0.5 0.55 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95

    Isentropic Efficiency

    CoolingCapacity(Btu/h)

    Figure 6: Plot of Cooling Capacity vs. Isentropic Efficiency

    As shown in Figure 6, the plot of Cooling Capacity vs. Isentropic Efficiency is shown to

    be a decreasing exponential relationship. A lower isentropic efficiency results in a lower

    14

  • 7/28/2019 EGR 360 design.doc

    15/18

    cooling capacity while a higher isentropic efficiency results in a higher cooling capacity,

    though the capacity levels off as the isentropic efficiency increases.

    Discussion and Results:

    The results of the required analysis are shown in Table 2.

    Table 2: Table of Results

    Requirement Result

    Mass Flow Rate 9.47 lb/min

    Width of Compressor 1.195 in

    Compressor Inlet Hose Diameter 0.3589 in

    Compressor Exit Hose Diameter 0.1417 in

    Power Required 5.619 hp

    Cooling Rate of Condenser 32,870.46 Btu/h

    Area of Condenser 3.87 ft2

    Air Flow Rate of Condenser 151.75 lb/minArea of Evaporator 1.298 ft2

    Air Flow Rate of Evaporator 39.68 lb/min

    For the current design of the system, increasing the compressor volumetric efficiency

    would increase the overall performance of the system. A higher volumetric efficiency

    would result in more volume and therefore more mass accepted in each chamber in thecompressor. This would result in less power required to deliver the same mass to the exit

    of the compressor because it would have to spin less.

    The expansion valve is a very important process in the system. Without it, a constant

    high pressure would be held through the whole system. The expansion valve causes alarge temperature drop to occur for the refrigerant. In the current design, the temperature

    of the refrigerant before the expansion valve is 174.46F. If the expansion valve was notthere, the refrigerant could not cool the air because it is at such a high temperature. If the

    cool inside air was being circulated through the evaporator, the system would actually

    heat the air going back into the car.

    Each component in the design is important to the overall performance of the system. The

    compressor is necessary to increase the pressure and therefore the temperature of therefrigerant so that heat transfer to the surroundings is possible. The condenser is

    necessary to transfer heat out of the system and to the surroundings, allowing cooling to

    occur. The expansion valve is necessary to lower the pressure and therefore thetemperature of the refrigerant, allowing a low temperature refrigerant to cool the airgoing into the car. The evaporator is necessary to allow heat transfer to occur between

    the refrigerant and the air going into the vehicle so that the air can be cooled. Therefore,

    all of the components are just as critical to the system as any other. Without any one ofthe components, the system would not be able to operate as intended.

    Non Engineering Explanation

    15

  • 7/28/2019 EGR 360 design.doc

    16/18

    The refrigeration system that was designed is intended to provide cool air to a vehicle

    using Refrigerant 134a in order to maintain a comfortable environment. To accomplish

    the refrigeration process, four separate components are needed. The first component isthe compressor. The compressor takes the low pressure, low temperature refrigerant and

    compresses it to a high pressure, and therefore high temperature state using power added

    by the engine. In the case of this design, the low pressure and temperature is 60 psi and49.89F and the high pressure and temperature is 375 psi and 203.31F respectively. It

    does this so the temperature of the refrigerant is high enough to facilitate heat transfer

    from the refrigerant to the surrounding environment that takes place in the nextcomponent, the condenser. The condenser is designed to exchange heat from the hot

    refrigerant to the outside environment. It does this to remove heat from the system,

    allowing a cool environment to be maintained. The next step of the process is to take the

    slightly cooler refrigerant and cool it down even further. This is accomplished throughthe use of an expansion valve. The expansion valve takes the high pressure refrigerant

    down to a low pressure, in this design, from 375 psi down to 60 psi. As a result, the

    temperature of the refrigerant drops drastically, down to 49.89F in this design. The

    purpose of cooling down the refrigerant is to facilitate heat transfer in the next process ofthe cycle, the evaporator. The evaporator is a heat exchanger that transfers heat from the

    air to the cool refrigerant so that the air is cooled down when it enters the car. The worstcase scenario for the designed heat exchanger is that the ambient air, up to about 100F,

    will need to be cooled down to the desired temperature of 65F. It accomplishes this by

    transferring heat from the air to the refrigerant that has been cooled down by theexpansion process. The refrigeration process has then been completed. Therefore, the

    overall goal of the system is to transfer heat from the air entering the car to the

    surrounding environment of the vehicle.

    References:

    1. E.W. Lemmon, M.O. McLinden and D.G. Friend, ThermophysicalProperties ofFluid Systems" in NIST Chemistry WebBook, NIST Standard Reference

    Database Number 69, Eds. P.J. Linstrom and W.G. Mallard, June 2005, National

    Institute of Standards and Technology, Gaithersburg MD, 20899(http://webbook.nist.gov).

    2. Gas Encyclopedia in Air Liquide, 2007, Air Liquide

    (http://encyclopedia.airliquide.com).

    3. Moran, Michael J. and Shapiro, Howard N., Fundamentals of Engineering

    Thermodynamics, John Wiley & Sons, Inc., 2008. (pp. 883 887, 901)

    Appendix A: Excel Spreadsheet of Interpolated Data

    16

    http://webbook.nist.gov/http://encyclopedia.airliquide.com/http://webbook.nist.gov/http://encyclopedia.airliquide.com/
  • 7/28/2019 EGR 360 design.doc

    17/18

    Table 1A: Interpolated Data at 480 psi

    T(F) v (ft3/ lb)

    u(Btu/lb)

    h(Btu/lb)

    s(Btu/lb

    R)

    180 0.04306 107.878 113.474 0.1972

    200 0.06358 116.676 124.008 0.2133220 0.0771 123.598 132.134 0.2255

    240 0.0878 129.824 139.316 0.2359

    260 0.09672 135.674 145.992 0.2454

    280 0.10478 141.324 152.392 0.2541

    300 0.11216 146.838 158.582 0.2623

    320 0.11896 152.29 164.69 0.2703

    340 0.1252 157.69 170.708 0.2779

    360 0.13132 163.076 176.684 0.2853

    380 0.13724 168.474 182.626 0.2925

    400 0.14288 173.876 188.58 0.2994

    Table 2A: Interpolated Data at 375 psi

    T(F) v (ft3/ lb)

    u(Btu/lb)

    h(Btu/lb)

    s(Btu/lb

    R)

    180 0.1132 114.325 121.948 0.2143

    200 0.13015 121.223 130.035 0.2267

    220 0.14325 127.21 136.933 0.2371

    240 0.154475 132.838 143.338 0.2463

    260 0.16455 138.268 149.468 0.255

    280 0.173975 143.603 155.448 0.2632

    300 0.182825 148.875 161.323 0.271320 0.1912 154.128 167.158 0.2786

    340 0.199225 159.37 172.955 0.2859

    360 0.207025 164.63 178.753 0.2931

    380 0.214625 169.913 184.548 0.3001

    400 0.22205 175.22 190.365 0.3069

    Appendix B:

    17

  • 7/28/2019 EGR 360 design.doc

    18/18

    Figure 1B: Drawing of a cross-flow, unmixed, heat exchanger.

    Figure 2B: Correction Factor Plots for single pass counter-flow heat exchanger, both

    fluids unmixed.

    18