Christian Breuer
12. – 13. November 2014
Einsatz von biobasierten Isolierölen in Transformatoren
Bioschmierstoff-Kongress Hagen
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 2
Agenda – Biobasierte Isolieröle in Transformatoren
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 3
AlstomVier Geschäftsbereiche
Ausrüstung und Dienstleistungen für die Stromerzeugung
ALSTOM THERMAL POWER
Ausrüstung und Dienstleistungen für den Schienenverkehr
Ausrüstung und Dienstleistungen für die Energieübertragung
ALSTOM TRANSPORT
ALSTOM GRIDALSTOM RENEWABLE POWER
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 4
Umspannwerke,schlüsselfertige Lösungen
& Service
Super Grid Technologien
Smart Grid Technologien
NetzwerkManagement
Systeme
Luftisolierte Schaltanlagen
Gasisolierte Schaltanlagen
Transformatoren
Schutz- und Leittechnik für Umspannwerke
Leistungs-elektronik
Produkte
Leistungselektronik, NMS & Automatisierung
Lösungen
Alstom GridUmfassende Lösungen und Produkte
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 5
Alstom in Deutschland
9.000 Beschäftigte an 24 Standorten
• Power4.600 Beschäftigte an 11 Standorten
• Transport2.800 Beschäftigte an 6 Standorten
• Grid 1.400 Beschäftigte an 7 Standorten
• Vertriebsniederlassungen Grid
Alstom Deutschland hat eine großeindustrielle Präsenz mit einem breitgefächerten und technologischhochwertigen Produktportfolio und Service-Angebot in allenGeschäftsbereichen des Konzerns.
Alstom in DeutschlandStandorte
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 6
Baltic 2 (2010)
Selbst-schwimmendes und –errichtendes Umspannwerk
288 MW
2x 150 MVA
Veja Mate (2009)
Umspannwerk und Ausrüstungen
400 MW
2x 240 MVA
Alstom in DeutschlandProjekte Grid: Pionier in Offshore-Anbindungen
Meerwind (2011)
Umspannwerk und Plattform
288 MW
2x 280 MVA
MEG 1 (2011)
Selbst-schwimmendes und –errichtendes Umspannwerk
400 MW
4x 120 MVA
Global Tech I (2009)
Selbst-schwimmendes und –errichtendes Umspannwerk
400 MW
4x 120 MVA
Alpha Ventus (2007)
Umspannwerk und Ausrüstungen
60 MW
1x 75 MVA
Borkum West II (2009)
Plattform und Schutzmantel
400 MW
2x 225 MVA
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 7
Projektumfang: 60 MW Offshore Umspannwerk für 12 Windturbinen
Anteil von Alstom Grid:Schlüsselfertige Übergabe der elektrischen Ausrüstungen für die Plattform einschließlich
• 110/30 kV Transformator• Schutz- & Kontrollausrüstung• 110 kV & 30 kV GIS Schaltanlage• Verkabelung der Plattform• AC/DC Ausrüstung• Dieselgeneratoren• Meeresausrüstung• Feuerschutzausrüstung• Inbetriebnahme
2011 hat alpha ventus 267 Mio. kWh Strom produziert.
Das ist 15 % mehr als erwartet und schließt 4.400 Betriebsstunden bei voller Leistung ein.
Alstom in DeutschlandReferenzen Grid: Umspannplattform für Alpha Ventus
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 8
Leistungsstärkster und schwerster
bisher in Deutschland gebauter
Transformator:
• 1100 MVA, 410/27 kV
• Transportgewicht 450 t
• Gesamtgewicht 600 t
Alstom in DeutschlandReferenzen Grid: Transformator für Kraftwerk Boxberg
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 9
Vorteile:
� Mit natürlichem Esteröl befüllt: biologisch abbaubar und mit erhöhter Sicherheit vor Entflammung
� Hermetisch abgeschlossener Tank, speziell für die Konservierung von Esteröl ausgelegt
� Optimierte Verlustlevel� Geringe Geräuschentwicklung � Online Monitoring-System (optional)
Ein umweltfreundlicher und effizienter Transformator für eine grünere Zukunft von 10 bis 250 MVA und bis zu 245 kV
Alstom in DeutschlandProdukte Grid: umweltfreundlicher Transformator
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 10
Alstom in DeutschlandReferenzen Grid: Hermetiktransformator für die Deutsche Bahn
Leistung: 10 MVA Spannung: 120 kV / 17,25 kV
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 11
Aufgaben eines Transformators
Motivation
• Anforderungen an Transformatoren−Betrieb
• Lange Lebensdauer robust
• Sicherer Betrieb sicher
−Design• Geringes Gewicht leicht
• Geringe Abmessungen klein
• Geringe Verluste effizient
• Geringe Geräusche leise
−Kosten• Kostengünstig günstig
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 12
Aufgaben eines Transformators
• Der Energietransport über größere Entfernungen vom Energieerzeuger zum Verbraucher erfordert hohe Spannungen mit entsprechend kleinen Strömen.
• Der Transformator dient zur Umwandlung der elektrischen Energie auf beliebige Spannungsebenen.
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 13
Design und Material
Kern + Wicklungen
+ Kessel
+ Stufenschalter
+ Öl Dehngefäß
Radiatoren
Durchführung+ Anbaukomponenten = Transformator
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 14
Design und Material
Physikalische Grenzen
• Kernblech− Sättigung des Kernmaterials liegt bei ca. 2 Tesla− Leerlaufverlust und Leerlaufgeräusche
begrenzen häufig die Induktion
• Wicklungen− Maximale Stromdichte (thermische
Belastbarkeit) liegt bei ca. 4 A/mm²− Kurzschlussverluste und Stromgeräusch
bestimmen häufig die Stromdichte
• Transport− Beschränkung durch den
Regellichtraum/Grenzmaß der DB− Allgemeine Bestimmungen für Transporte auf
der Straße, wie z. B. Achslasten, Brückenlasten oder Tunnelabmessungen
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 15
Bioöl
Natürliche Esterflüssigkeiten
• Motivation− Steigende Nachfrage nach
umweltfreundlichen Produkten
• Idee− Transformatoren mit natürlicher
Esterfüllung als Isolierflüssigkeit−Weitreichende Erfahrungen
beim Einsatz von natürlichen Estern in Verteilungstransformatoren
• Aufgabe− Erweiterung des Konzeptes auf
Hochspannungstransformatoren
• Herausforderung− Auslegung, Produktion und
Prüfung regelbarer Leistungstransformatoren mit natürlicher Esterfüllung
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 16
Bioöl – natürliche Ester
Thermische Eigenschaften
• Wärmeleitfähigkeit− Mineralöl ca. 0,14 W/mK− natürlicher Ester ca. 0,17 W/mK− Verbesserte Wärmeabgabe aus dem
Wicklungsmaterial an die Isolierflüssigkeit bei Einsatz von natürlichen Estern
• Alterung− Höheres Wasseraufnahmevermögen
von natürlichen Estern
• Verringerung der Alterung bzw. höhere Belastung des Transformators möglich
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 17
Bioöl – natürliche Ester
Thermische Eigenschaften
Erhöhung der Kühloberfläche bei natürlichen Estern im Vergleich zu Mineralöl
Quelle: Cigre Colloquium Bruges 2007
höhere Viskositätenverringerter Ölfluss
höhere Ölerwärmungerhöhte Heißpunkttemperatur
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 18
Bioöl – natürliche Ester
Elektrische Eigenschaften
• Spannungsuntersuchungen gemäß IEC 60156 mit 2,5 mm Elektrodenabstand und natürlichen Estern
• Vergleichbare Spannungsfestigkeiten zwischen Mineralöl und natürlichen Estern
Quelle: ALSTOM Frankreich
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 19
Bioöl – natürliche Ester
Einfluss der Dielektrizitätszahlen
• Elektrische Vorteile von natürlichen Estern im Vergleich zu Mineralöl− Eine homogenere Feldstärkeverteilung der Gesamtanordnung− Eine Verringerung der Feldstärke in den Ölkanälen
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 20
Bioöl – natürliche Ester
• Einsatz bekannter Materialien aus dem Bau von mineralölgefüllten Transformatoren
• Kaum verlängerte Prozesszeiten
• Einfluss der erhöhten Viskositäten−Dicke Isolationsmaterialien
erhalten zusätzliche Bohrungenzur Verbesserung der Imprägnierung−Verlängerung der Standzeiten
• Ölfüllung übergetrennte Anlage
Einfluss auf die Transformatorenfertigung
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 21
Bioöl – natürliche Ester
• Materialverträglichkeitsuntersuchungen der Hersteller von Esterflüssigkeiten zeigten kaum Auffälligkeiten− Isolationsmaterialien− Dichtungen (Viton)− Eisenteile−Wicklungsmaterial− Kernmaterial
• Umfangreiche Diskussionen mitHerstellern von Komponenten− Durchführungen− Stufenschalter
• Begrenzungen beiTiefsttemperaturen
• Ungeklärte Komponenten− Öl-Luft Kühler
Komponenten
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 22
Neuer Trafotyp für die DB
− Zusammenarbeit zwischen ALSTOM und der DB− Eigenschaften
• Biologisch abbaubares Öl (keine Ölauffangwanne mehr)
• Nomex Isolation
• Hermetisch geschlossener Transformator
• Niedrige Verluste und Geräusche
• Neuer Korrosionsschutz (kathodische Tauchlackierung KTL)
− finanziert durch DBTiefsttemperaturverhalten von Estern.
Versuche durch die Uni Stuttgart
KTL bei DTR-KesselKTL TauchbeckenHermetiktrafoLeiter mit Nomex-Lochband
Grüner Transformator für die Deutsche Bahn
Bioöl – natürliche Ester
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 23
Bioöl – natürliche Ester
Prüfergebnisse/Referenzen
• Prüfanforderungen (Prüfpegel) an Transformatoren mit Esterfüllungsind identisch mit denen an Transformatoren mit Mineralöl
• Keine Auffälligkeiten bei allen durchgeführten Prüfungen(Spannungsprüfungen, Wärmeläufe, Verluste, Geräusche, etc.)
• Störungsfreier Betrieb seit über 5 Jahren
ALSTOM Brasilien245 kV -Drossel
ALSTOM UK60 MVA, 132 kV
ALSTOM Deutschland
31,5 MVA, 110 kV
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Presentation title - 05/11/2014 – P 24
• Steigende Nachfrage nach umweltfreundlichen Produkten bei Leistungstransformatoren
• Entwicklungen der letzten Jahre− Neue, umweltfreundliche Isolierflüssigkeiten− Lebensdaueroptimierung durch hermetischen Abschluss− Optimierter Wartungsaufwand: Gemeinsamer Ölhaushalt
• Erste Referenzen mit Esterfüllungen− Störungsfreier Betrieb seit über 5 Jahren
Zusammenfassung
Einsatz von biobasierten Isolierölen in Transformatoren