To view Product Specification Page(s), choose a product by clicking directly on the product number in the table on the Product Number Page. To view Instruction Sheet, click on the Instruction Sheet button in the upper right-hand corner. To view Crimp Chart click on the Crimp Chart button. CD-ROM CATALOG V10-99A Links To Catalog 2001 ELASTIMOLD ® 5kV-35kV Distribution Products  SEPARABLE CONNECTORS CABLE JOINTS TERMINATIONS SURGE ARRESTERS FUSES LOADBREAK SWITCHES Overview Page Product Number Page Product Specification Page Product Instruction Sheet This is the Home Page (page 1). Use this as the starting point to access product information. You may also search by product number using the viewer. If you need help, scroll down for diagram and additional instructions. Scroll list and select pages by clicking O or P Introductory Product Information .......... Component Application & Selection Help .. Certified Tests & Performance ............ Separable Connector Interfaces ............. • 200 Amp Loadbreak Connectors ........... • 200 Amp Deadbreak Connector s ........... • 600 Series Deadbreak Connect ors ......... • 600 Series Deadbreak Connectors  Cam-Op, Link-Op .......... ............... • 600 Series Deadbreak Connectors  Stick- Op, Window-Op .................... • 600 Series Deadbreak Cabl e Joints ....... • PCJ Cable Joints ........................... Cable Terminations ........................... Surge Arrester s ................................ • Shield Adapters, Grounding Kits & Jacket Seals............... .......... ........  How to specify size-sensitive products .....  WX Size Tables.................................  AEIC Cable Insulation Diameter Reference..  Cable Conductor Diameter Reference ....... Equipment Bushings ...................... .... • Loadbreak Switches, Molded Current Limiting Fuses, Molded Power Fuses & Transmissi on Cl ass pr oducts ............. O for Overview Page P for Product Number Page 166LR- Use Tables W1 274LR-W Use Tables NUMBER O O O O O O O O O O O O O O O O O O P P P P P P O O O O O O O O O O O O O O O O P P P P P P O O O O O O P P P P P P P P

Elastimold Viejo

Embed Size (px)

Citation preview

  • To view Product Specification Page(s), choose a product by clicking directly on the product number in the table on the Product Number Page. To view Instruction Sheet, click on the Instruction Sheet button in the upper right-hand corner. To view Crimp Chart click on the Crimp Chart button.

    CD-ROM CATALOG V10-99ALinks To Catalog 2001ELASTIMOLD

    5kV-35kV Distribution Productsn SEPARABLE CONNECTORSn CABLE JOINTSn TERMINATIONSn SURGE ARRESTERSn FUSESn LOADBREAK SWITCHES

    OverviewPage

    ProductNumber Page

    ProductSpecification Page

    ProductInstruction Sheet

    This is the Home Page (page 1). Use this as the starting point to access product information. You may also search by product number using the viewer. If you need help, scroll down for diagram and additional instructions.

    Scroll list and select pages by clicking O or P

    Introductory Product Information ..........

    Component Application & Selection Help ..

    Certified Tests & Performance ............

    Separable Connector Interfaces .............

    200 Amp Loadbreak Connectors ...........

    200 Amp Deadbreak Connectors ...........

    600 Series Deadbreak Connectors .........

    600 Series Deadbreak Connectors Cam-Op, Link-Op .........................

    600 Series Deadbreak Connectors Stick-Op, Window-Op ....................

    600 Series Deadbreak Cable Joints .......

    PCJ Cable Joints ...........................

    Cable Terminations ...........................

    Surge Arresters................................

    Shield Adapters, Grounding Kits & Jacket Seals.................................

    How to specify size-sensitive products .....

    WX Size Tables.................................

    AEIC Cable Insulation Diameter Reference..

    Cable Conductor Diameter Reference .......

    Equipment Bushings ..........................

    Loadbreak Switches, Molded CurrentLimiting Fuses, Molded Power Fuses& Transmission Class products .............

    O for Overview PageP for Product Number Page

    166LR-WXUse Tables W1

    274LR-WXUse Tables W1

    NUMBER

    OOOO

    OOOOOOOOOOOO

    OO

    PP

    PPPP

    OOOOOOOOOOOOOO

    OO

    PP

    PPPP

    OOOOOO

    PP

    PP

    PPPP

  • ELASTIMOLD CATALOG 2001 Page 2 ID: 0198ELASTIMOLD

    CERTIFIED TESTS AND PERFORMANCE

    TABLE 1 15kV Class Ratings 25kV Class Ratings 35kV Class Ratings

    OPERATING VOLTAGE 8.3kV 15.2kV 21.1kVMaximum line-to-ground (See Application Info Note 1)

    BIL Impulse withstand 1.2 x 50 microsecond wave 95kV 125kV 150kV

    WITHSTAND VOLTAGEAC One Minute 34kV 40kV 50kVDC Fifteen Minute 53kV 78kV 103kV

    CORONA EXTINCTION LEVEL @ 3pC Sensitivity 11kV 19kV 26kV

    200 AMP ProductsContinuous Current: 200 AMP*Symmetrical Momentary Current: 10kA sym, 10 cycle duration

    600 Series ProductsContinuous Current: 600 and 900 AMP*Symmetrical Momentary Current: 25kA sym, 10 cycle duration

    * Designed for 90C maximum continuous operating temperature

    Elastimold Separable Connectors, Cable Joints, CableTerminators, Surge Arresters, Fused Elbows and other cableaccessory products have been designed and tested perapplicable portions of IEEE, ANSI, NEMA and other industrystandards including: IEEE 386 Standard For Separable Connectors IEEE 404 Standard For Cable Joints and Splices IEEE 48 Standard For Cable Terminations

    IEEE C62.11 Standard For Metal Oxide Surge Arresters ANSI C37.41 Standard For Current Limiting Fuses IEEE 592 Standard For Exposed Semiconducting Shields ANSI C119.4 Standard For Copper and AluminumConductor Connectors

    AEIC CS5 and CS6 Standards For XLP and EPRInsulated Cables

    Application Information: 1. Loadbreak connectors are designed and rated for use on grounded WYE systems. For application on ungrounded WYE or delta systems, the next higher voltage class product is recommended. Examples: 5kV ungrounded: use 15kV class products; 15kV ungrounded: use 25kV class products;25kV ungrounded: use 35kV class products; 35kV ungrounded: contact factory.

    2. Products are designed and constructed for all applications including padmount, subsurface, vault, indoor, outdoor, direct sunlight, direct buried andcontinuously submerged in water.

    3. Products are designed and rated for ambient temperatures of -40C to +65C. It is recommended that loadbreak connectors be hotstick operated at-20C to +65C ambient temperature range and at altitudes not exceeding 6000 feet.

    CABLE JOINTS, TERMINATIONS AND ARRESTER RATINGSRefer to the pages listed below for rating information:

    PCJ Cable Joints, page 20. Surge Arresters, page 26. Cable Terminations, page 22

    SEPARABLE CONNECTOR RATINGSTable 1 shows voltage and current ratings which apply to all Separable Connectors including 200 AMP Loadbreak, 200 AMPDeadbreak and 600 Series Deadbreak products. Table 2 shows switching and fault close ratings which only apply to 200 AMPLoadbreak Connectors.

    TABLE 2 LOADMAKE/LOADBREAK SWITCHING FAULT CLOSE

    1 and 3 circuits 8.3kV line to ground, 14.4kVmax. across open contacts.

    10 loadmake/break operations at 200 Amps max.with 70 to 80% lagging power factor.

    1 and 3 circuits 15.2kV line to ground, 26.3kVmax. across open contacts.

    10 loadmake/break operations at 200 Amps max.with 70 to 80% lagging power factor.

    1 and 3 circuits 21.1kV line to ground, 36.6kVmax. across open contacts.

    10 loadmake/break operations at 200 Amps max.with 70 to 80% lagging power factor.

    1 fault close operation at 8.3kV or 14.4kV; 10,000Amps, rms, sym. 10 cycles (0.17 sec.) 1.3 max. asymfactor applies to new or used mating parts (up tomaximum designated switching operations.)

    1 fault close operation at 15.2kV or 26.3kV; 10,000Amps, rms, sym. 10 cycles (0.17 sec.) 1.3 max. asymfactor applies to new or used mating parts (up tomaximum designated switching operations.)

    1 fault close operation at 21.1kV or 36.6kV; 10,000Amps, rms, sym. 10 cycles (0.17 sec.) 1.3 max. asymfactor applies to new or used mating parts (up tomaximum designated switching operations.)

    15kVClass Ratings

    25kVClass Ratings

    35kVClass Ratings

  • SEPARABLE CONNECTOR INTERFACES

    Bushing Interface Voltage Interface Standard NoClass Description Figure No.

    200 AMP DEEPWELL 15kV, 25kV 200 AMP Bushing IEEEEQUIPMENT BUSHING and 35kV Well Interface 386-1995

    8.3kV, 15.2kV, Fig. 321.1kV

    200 AMP LOADBREAK INSERT 15kV 200 AMP Loadbreak IEEE8.3kV and 386-1995

    8.3kV/14.4kV Fig. 5

    200 AMP LOADBREAK INSERT 25kV 200 AMP Loadbreak IEEE15.2kV and 386-1995

    15.2kV/26.3kV Fig. 7, Note 3

    200 AMP LOADBREAK INSERT 35kV 200 AMP Loadbreak IEEEInterface No. 2 386-1995

    21.1kV and Fig. 7, Note 321.1kV/36.6kV

    200 AMP DEADBREAK INSERT 15kV and 25kV 200 AMP Deadbreak IEEE8.3kV and 15.2kV 386-1985

    Fig. 4

    600 SERIES EQUIPMENT BUSHING 15kV and 25kV 600 AMP Deadbreak IEEEInterface No.1 386-1995

    8.3kV and 15.2kV Fig.11, Note 1

    600 SERIES EQUIPMENT BUSHING 35kV 600 AMP Deadbreak IEEEInterface No.1 386-1995

    21.1kV Fig.13, Note 2

    A

    B

    C

    D

    E

    F

    G

    ANSI/IEEE Standard 386 defines the specific interface dimensions that 200 Amp and 600 Series elbows, inserts,junctions, equipment bushings and any mating compo-nents must conform to insure interchangeability. The table

    below provides information concerning the types of inter-faces supplied by Elastimold for various applications and is useful to assure proper matching of components.

    CATALOG 2001 Page 3 ID: 0198

    NOTES: 1. Was Fig. 10 in previous IEEE 386-1985 publication.2. Was Fig. 11 in previous IEEE 386-1985 publication.3. Elastimold uses Fig. 7 interface for both 25 and 35kV applications.

    STANDARD INTERFACES FOR SEPARABLE CONNECTORS, COMPONENTS AND EQUIPMENT BUSHINGS

    A

    B

    C

    D

    E

    F

    G

  • SEPARABLE CONNECTORS

    200 AMP LOADBREAK

    ELASTIMOLD

    200 Amp loadbreak connectors and accessories provide a convenientmethod to connect/disconnect cable and equipment on power distribution systems. Loadbreak elbows include pro-visions for energized operation usingstandard hotstick tools, allowing load-make/break operation and a visible dis-connect. Components can be isolatedwith insulated caps, plugs and parkingbushings.

    Optional accessories allow systemgrounding, testing, bypass, lightningsurge protection and current limiting fus-ing. Additional connecting points andtaps can be provided by use of junctionsor feed-thrus.

    RATINGS OVERVIEWSee page 2 for complete informationincluding switching and fault closeratings.

    CURRENT RATINGS200A Continuous10kA sym. 10 Cycles

    VOLTAGE RATINGS15kV Class 8.3kV Phase-to-Ground14.4kV Phase-to-Phase95kV BIL34kV AC Withstand53kV DC Withstand11kV Corona Extinction

    25kV Class15.2kV Phase-to-Ground26.3kV Phase-to Phase125kV BIL40kV AC Withstand78kV DC Withstand19kV Corona Extinction

    35kV Class21.1kV Phase-to-Ground36.6kV Phase-to-Phase150kV BIL50kV AC Withstand103kV DC Withstand26kV Corona Extinction

    BUSHING WELLPLUG

    FUSED ELBOW

    LOADBREAKFEED-THRU INSERT

    FEED THRU

    CABLE TO EQUIPMENTCONNECTIONS

    PARKINGSTAND

    SEE CABLE NOTES

    INSULATED CAPWITH GROUND

    ELBOWGROUNDING

    OPERATING ACCESSORIES

    REPLACEMENTELBOW

    INSULATED PARKINGBUSHING

    LOADBREAK ELBOW CONNECTORWITH OR WITHOUT TEST POINT

    BUSHINGWELL

    ASSEMBLY TOOL

    SEE CABLE NOTES

    INSULATED CAP

    SEE PAGE 6

    BOLTEDELBOWW/TAP

    GROUNDINGPLUG

    REPAIRELBOW

    SEE CABLE NOTES

    LOADBREAKBUSHING INSERT

    TEST ROD

    SURGE ARRESTERAPPLICATIONS

    SEE PAGE 26 FOR

    EXTENDEDBUSHING INSERT

    CATALOG 2001 Page 4 ID: 0198

    200 AMP LOADBREAK SEPARABLE CONNECTOR COMPONENTS

  • DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #

    N1. Copper lug for use on COPPER CONDUCTOR ONLY.N2. Incudes 02500X long bi-metal compression lug as standard.N3. Also available as housing only. Specify: 165BLR-W; 273BLR-W;

    375BLR-W; 166BLR-W; 274BLR-W; 376BLR-W.N4. Also available as elbow/insert combination. Specify: 165A4-WX;

    273A4-WX; 166A4-WX; 274A4-WX; 274A4-WX.N5. Also available with jacket seal included. Add - S suffix to part number.

    See 200ECS page 28.N6. Rated for single-phase applications only.N7. Equipped with insulated cuff.N8. Includes internal torquing feature using 200AT Assembly Tool.N9. Rated for 15kV thru 35kV applications.

    N10. Repair elbow has extended length (3-1/4) contact and elbow housing. N11. Replacement elbow has extended length (9-7/8) contact and elbow

    housing.N12. Rated for 25kV thru 35kV applications.N13. Includes long bi-metal contact 00400X.N14. 160CA Cable Size Adapter can only be used with elbow part

    numbers 165LR/166LR C size only.N15. See page 6 for WX size tables and for fuse sizes.N16. Fully rotatable for 360positioning. Includes bail assembly to secure

    feed-thru insert to bushing well.N17. Incudes 02800X long bi-metal contact.N18. Incudes 02509X long bi-metal contact.

    CATALOG 2001 Page 5 ID:0198

    Illustration Description Voltage ELASTIMOLD Notes(not to scale) Class Part Number

    Elbow 15kV 165LR-WX N2,3,4,5Connector

    Use Tables W1 and X125kV 273LR-WX N2,3,4,5

    Use Tables W2 and X135kV 375LR-WX N2,3, 5

    Use Tables W3 and X2

    Elbow 15kV 166LR-WX N2,3,4,5Connector Use Tables W1 and X1

    w/ Test Point 25kV 274LR-WX N2,3,4,5Use Tables W2 and X1

    35kV 376LR-WX N2,3, 5Use Tables W3 and X2

    Repair Elbow 15kV 167ELR-WX N5,10,18Connector Use Tables W5 and X1

    25kV 273ELR-WX N5,10,18Use Tables W5 and X1

    Repair Elbow 15kV 168ELR-WX N5,10,18Connector Use Tables W5 and X1

    w/ Test Point 25kV 274ELR-WX N5,10,18Use Tables W5 and X1

    Replacement 15kV 167RLR-WX N5,11,13Elbow Use Tables W4 and X1

    25kV 273RLR-WX N5,11,13Use Tables W2 and X1

    Replacement 15kV 168RLR-WX N5,11,13Elbow Use Tables W4 and X1

    w/ Test Point 25kV 274RLR-WX N5,11,13Use Tables W2 and X1

    Fused Elbow 15kV 166FLR-WX N5,15(General Purpose Use W and X Tables Current Limiting) on Page 6

    Bolted Elbow 15kV 167LRT-WX N17w/ Tap Use Tables W4 and X1

    Bushing Insert 15kV 1601A4 N4,825kV 2701A4 N4,835kV 3701A4 N635kV 3701A3 N8

    Extended 15kV 1601EA4 N8Bushing 25kV 2701EA4 N8

    InsertFeed-Thru 15kV 1602A3R N16

    Insert 25kV 2702A1 N1635kV 3702A1 N6,16

    Insulated Cap 15kV 160DR

    Insulated Cap 15kV 160DRGw/ Ground 15kV 167DRG N7

    25kV 273DRG N735kV 375DRG N7

    Insulated Cap 15kV 168DRG N7w/ Ground and 25kV 274DRG N7

    Test Point 35kV 376DRG N7Grounding 15kV 161GP

    Plug 25kV 272GP(1/0 AWG x 6'Ground Lead)

    Grounding 15kV 160GLRElbow 25/35kV 370GLR N12

    (1/0 AWG x 6'Ground Lead)

    Feed-Thru 15kV 164FT25kV 274FT35kV 373FT

    Feed-Thru 15kV 164FTVVertical 25kV 274FTV

    35kV 373FTV

    200 AMP LOADBREAK

    Feed-Thru 15/25kV K1601WFTWell

    Feed-Thru 15/25kV K1601WFTVWell Vertical

    Insulated 15kV 161SOPParking Bushing 25kV 272SOP

    35kV 372SOPTest Rod ALL 370TR N9

    Bushing Well 15/25kV 276BWPPlug 35kV M276BWP

    Assembly Tool ALL 200AT N8,9

    Contacts: Use Table X1Long Bi-Metal ALL 02500X N9ELR Bi-Metal 15/25kV 02509X N10

    Copper ALL 02702X N1,9LRT Contact 15kV 02800XRLR Contact 15/25kV 00400X N11Elbow Probe 15kV 166LRF

    25kV 274LRF35kV 376LRF

    Elbow ALL 10EP-W N9Cable Entrance Use Table W6Insulating Plug

    Cable Size 15kV 160CA-W N14Adapter Use Table W6

    EB-FA Only

    Refer to the W and X tables on pages 32 and 33 for sizing to cable insulation diameter and conductor size.

    For cable shield adapters and jacket seals, see page 28.

    Illustration Description Voltage ELASTIMOLD Notes(not to scale) Class Part Number

    JUNCTIONS CONTINUED ON PAGE 6.

    Part numbers that containthe letters W or X are sizesensitive. To complete thepart number, refer to the W or X tables indicated.

  • ELASTIMOLD

    SEPARABLE CONNECTORS

    200 AMP LOADBREAK Contd from Pg. 5

    CATALOG 2001 Page 6 ID: 0198

    RATINGS OVERVIEWSee page 2 for complete informationincluding switching and fault closeratings.

    CURRENT RATINGS200A Continuous10kA sym. 10 Cycles

    VOLTAGE RATINGS15kV Class 8.3kV Phase-to-Ground14.4kV Phase-to-Phase95kV BIL34kV AC Withstand53kV DC Withstand11kV Corona Extinction

    25kV Class15.2kV Phase-to-Ground26.3kV Phase-to Phase125kV BIL40kV AC Withstand78kV DC Withstand19kV Corona Extinction

    35kV Class21.1kV Phase-to-Ground36.6kV Phase-to-Phase150kV BIL50kV AC Withstand103kV DC Withstand26kV Corona Extinction

    CABLE TO CABLECONNECTIONS 3-POINT

    JUNCTION4-POINT

    JUNCTION2-POINT

    JUNCTION

    LOADBREAKBUSHING INSERT

    LOADBREAKBUSHING INSERT

    LOADBREAKBUSHING INSERT

    4 POINT WELL JUNCTION

    3 POINT WELL JUNCTION

    2 POINT WELL JUNCTION

    SURGE ARRESTERAPPLICATIONS

    SEE PAGE 26 FOR

    200 AMP LOADBREAK SEPARABLE CONNECTOR COMPONENTS

    FUSED ELBOW ORDERING INSTRUCTIONSStep 1 (W) Determine the insulation diameter of the cable. Select the insulation letter code that best straddles the insulation diameter. Insert code into catalog number.Step 2 (X) Choose the proper connector code according to the conductor size. Insert code into the catalog number after the insulation code.

    Step 1 (W) Step 2 (X)

    166FLR

    The Fused Elbow kit contains the following:1 - Upper elbow half1 - Lower elbow half1 - Upper connector1 - Lower connector1 - Probe1 - Torque-limiting wrench1 - Lubricant1 - Instruction sheet

    The Fuse Kit includes the following: 1 - Current limiting fuse1 - Allen wrench1 - Air vent rod1 - Instruction sheet

    To order replacement parts, specify the following: For an upper elbow half, specify 166BFLR-T For a lower elbow half, specify 166BFLR-W For an upper connector, specify 166-88 For a lower connector, specify 02600X For a probe, specify 166LRF

    ORDERING INSTRUCTIONS FOR FUSE KIT (to be ordered separately) Determine the ampere rating required. Insert rating into the catalog number below.

    166PF8 -

    Voltage(kV)

    8.3

    AmpereRating

    58

    121830

    ConductorSize*(AWG)

    2

    1

    1/0

    2/0

    3/0

    Symbol For X

    Stranded/ Solid/Compr. Compact

    0220 0210

    0230 0220

    0240 0230

    0250 0240

    0250

    *Cu or AI Conductor

    Cable Insulation Diameter Range SymbolInches For W

    .610 -.735 FAB

    .675 - .785 FB

    .725 - .835 FG

    .775 - .885 GA

    .825 - .935 GAB

  • DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #

    CATALOG 2001 Page 7 ID: 0198

    N1. Also available without straps. Specify suffix -4 in place of -5 in the part number.

    N2. Supplied with replaceable stud. Replacement stud available separately.Specify 1601RS.

    Illustration Description Voltage ELASTIMOLD Notes(not to scale) Class Part Number

    2-Way Well 15/25kV K1601WJ2 N2Junction w/s.s. Bracket

    2-Way Well 15/25kV K1601WJ2-5 N1, N2Junction w/U Straps

    3-Way Well 15/25kV K1601WJ3 N2Junction w/s.s. Bracket

    3-Way Well 15/25kV K1601WJ3-5 N1, N2Junction w/U Straps

    4-Way Well 15/25kV K1601WJ4 N2Junction w/s.s. Bracket

    4-Way Well 15/25kV K1601WJ4-5 N1, N2Junction w/U Straps

    2-Point Junction 15kV 164J2with/stainless 25kV 274J2steel bracket 35kV 373J2

    2-Point Junction 15kV 164J2-5 N1w/U-straps 25kV 274J2-5 N1

    35kV 373J2-5 N1

    3-Point Junction 15kV 164J3with/stainless 25kV 274J3steel bracket 35kV 373J3

    3-Point Junction 15kV 164J3-5 N1w/U-straps 25kV 274J3-5 N1

    35kV 373J3-5 N1

    4-Point Junction 15kV 164J4with/stainless 25kV 274J4steel bracket 35kV 373J4

    4-Point Junction 15kV 164J4-5 N1w/U-straps 25kV 274J4-5 N1

    35kV 373J4-5 N1

    200 AMP LOADBREAK

    Part numbers that containthe letters W or X are sizesensitive. To complete thepart number, refer to the W or X tables indicated.

  • SEPARABLE CONNECTORS

    200 AMP DEADBREAK

    ELASTIMOLD

    200 Amp deadbreak connectors and accessories provide a quick disconnectfeature for cable and equipment connec-tions on power distribution systems. All deadbreak connectors must be DE-ENERGIZED before operating and mustbe mechanically secured with bails whenconnected. Components can be isolatedwith insulated caps, plugs and parkingbushings.

    All deadbreak elbows are equipped with test points as standard. Optionalaccessories allow system grounding,bypass and lightning surge protection.Additional connecting points and taps can be provided by use of junctions orfeed-thrus.

    RATINGS OVERVIEWSee page 2 for complete information.

    CURRENT RATINGS200A Continuous10kA sym. 10 Cycles

    VOLTAGE RATINGS15kV Class 8.3kV Phase-to-Ground14.4kV Phase-to-Phase95kV BIL34kV AC Withstand53kV DC Withstand11kV Corona Extinction

    25kV Class15.2kV Phase-to-Ground26.3kV Phase-to-Ground125kV BIL40kV AC Withstand78kV DC Withstand19kV Corona Extinction

    CATALOG 2001 Page 8 ID: 0198

    200 AMP DEADBREAK SEPARABLE CONNECTOR COMPONENTS

    ALL 200 A DEADBREAKCONNECTIONS MUST BE

    MECHANICALLY SECURED WITH

    SEE PAGE 26 FOR SURGEARRESTERS APPLICATIONS

    INTEGRAL BUSHING

  • DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #

    Illustration Description Voltage ELASTIMOLD Notes(not to scale) Class Part Number

    Elbow Connector 15/25kV 156LR-WX N1,2w/ Test Point Use Tables W4 and X1

    Bail Assembly 15/25kV 150BAfor 156LR Elbow

    Bushing Insert 15/25kV K1501A1 N3

    Feed-thru Insert 15/25kV K1502A1 N3,4

    Insulated Plug 15/25kV K150DP N3

    Insulated Cap 15/25kV K150DR N3

    Insulated Parking 15/25kV K150SOP N3Bushing

    Grounding Plug 15/25kV 151GP N3

    Feed-Thru 15/25kV K1501FT N3,6

    2-Point Junction 15/25kV K1501J2-U N3,6

    3-Point Junction 15/25kV K1501J3-U N3,6,7

    4-Point Junction 15/25kV K1501J4-U N3,6,7

    Elbow Probe 15/25kV 156LRF

    Straight 15/25kV K151SR-WX N3,12Receptacle Use Tables W6 and X5

    Straight Plug 15/25kV K151SP-WX N3,12Use Tables W6 and X5

    Tee Splice 15/25kV K150T N3

    In-Line Junction 15/25kV K150S N3

    Locking Splice 15/25kV K151LS-WX N8,9Use Tables W6 and X8

    Locking Y 15/25kV K151LY-WX N8,9Splice Use Tables W6 and X8

    BAIL 15/25kV 150TB1 N5

    BAIL 15/25kV 150TB2 N5

    BAIL 15/25kV 150TB3 N5

    N1. Includes bail assembly.N2. Includes 02500X long, bi-metal compression lug as standard.N3. Bails are required but not included. Order separately. Consult factory

    for bails not listed for a specific application.N4. Fully rotatable for 360 positioning. Includes bail assembly to secure

    feed-thru insert to bushing well.N5. Refer to general catalog for application details.N6. Center-to-center spacing equals 4 inches.N7. Copper lug for copper cable only.N8. To order cable legs for different cable sizes, list each leg size W and X.

    Example: K151LY-FB240-FB240-FAB220. See Tables W6 and X8 for sizes.

    N9. To order locking contacts for K151LS and K151LY, order 01401X (Al) or 01402X (Cu) for plug contact. Order 01301X (Al) or 01302X (Cu) for receptacle. See Table X8 for sizes.

    N10. For use with 156LR elbows.N11. For use with K151SR, K151SP, K151LS, K151LY receptacles, plugs and

    splices.N12. Also available as housing only. Specify K151SPH-W or K151SRH-W.

    CATALOG 2001 Page 9 ID: 0198

    Illustration Description Voltage ELASTIMOLD Notes(not to scale) Class Part Number

    BAIL 15/25kV 150TB4 N5

    BAIL 15/25kV 150TB5 N5

    Contacts:Long Bi-Metal 15/25kV 02500X

    Copper 15/25kV 02702X N7Elbow 15/25kV 10EP-W N10

    Cable Entrance Use Table W6Insulating PlugCable Entrance 15/25kV 152EA-W N11Insulating Plug Use Table W6

    200 AMP DEADBREAK

    Refer to the W and X tables on pages 32 and 33 for sizing to cable insulation diameter and conductor size.

    For cable shield adapters and jacket seals, see page 28.

    Part numbers that containthe letters W or X are sizesensitive. To complete thepart number, refer to the W or X tables indicated.

  • SEPARABLE CONNECTORS

    600 SERIES DEADBREAK

    ELASTIMOLD

    600 Series deadbreak elbows, straight recepta-cles, junctions, vault stretchers and accessoriesare used to connect equipment and cable onprimary feeder and network circuits. Designsaccommodate large conductors and featurebolted connections and deadfront modularconstruction for maximum reliability, perfor-mance and versatility.DE-ENERGIZED connectors can be quicklyand easily connected and disconnectedusing standard hand tools and equipment in accordance with accepted operating practices. Optional accessories allow visibleexternal separation, by-pass, isolation, dead-ending, grounding, and testing as well asadding taps, surge arresters and circuit protection.Hot-stick operable and separable joint systemsare shown on pages 14 thru 19.

    RATINGS OVERVIEWSee page 2 for complete information.

    CURRENT RATINGS(Prefixes: 650, K650, K655, K656,750, 755, 756 & 03700)600 Amp Continuous25kA sym.,10 cycles(Prefixes 675,K675,K676,775,776 & 03702)900 Amp Continuous25kA sym.,10 cyclesNOTE: 900 Amp ratings require copper cable and copper current-carrying components.

    VOLTAGE RATINGS15/25kV Class (5kV thru 28kV)16.2kV Phase-to-Ground28kV Phase-to Phase140kV BIL45kV AC Withstand84kV DC Withstand21.5kV Corona Extinction35kV Class21.1kV Phase-to-Ground36.6kV Phase-to-Phase150kV BIL50kV AC Withstand103kV DC Withstand26kV Corona ExtinctionNote: Elastimold has increased the IEEE StandardProduction and Design Test levels for 25kV Classproducts to include 27kV and 28kV systems.

    INTEGRAL BUSHING

    RETAININGRING

    CABLE TO EQUIPMENT

    COMPRESSIONLUG

    CABLEADAPTER

    CABLE TO CABLE

    STRAIGHT RECEPTACLEHOUSING

    LOADBREAKREDUCINGTAP PLUG

    200A LOADBREAKSEE PAGES 4 & 5

    200A DEADBREAKSEE PAGES 8 & 9

    LINK-OPLINK CONNECTOR

    SPANNER WRENCH

    OPERATINGACCESSORIES

    4 PT JUNCTION

    3 PT JUNCTION

    2 PT JUNCTION

    (UTILIZING JUNCTIONS)

    HOTSTICK OPERABLE 600 SERIESCONNECTORS - SEE PAGES 14 - 17

    STICK-OP

    LINK-OP

    COMPRESSIONLUG

    CABLEADAPTER

    VAULTSTRETCHER

    CONNECTOR

    CABLE TO CABLE

    L-1

    UTILIZING L-KITS

    L-2

    ELBOW CONNECTOR

    STICK-OPLOADBREAK REDUCING

    TAP PLUG

    BOLT &WASHERS

    STRAIGHTRECEPTACLE ADAPTER

    L-3

    L-4

    THREADEDSTUD

    LINK-OPRETAINERSLEEVES

    200A TAPS

    INSULATINGPLUG

    INSULATEDPARKING BUSHING

    BUSHINGEXTENDER

    THREADEDCOMPRESSION

    LUG

    600 SERIESELBOW

    CABLEADAPTER

    COMPRESSIONLUG

    CONNECTINGPLUG

    STRAIGHT RECEPTACLE

    REDUCING TAPWELL

    THREADEDSTUD VOLTAGE

    DETECTIONCAP

    INSULATED CAPWITH TEST POINT

    GROUNDINGPLUG

    DEADBREAKREDUCINGTAP PLUG600 SERIES

    TAPS

    CAM-OPRETAINERSLEEVES

    CONNECTINGPLUG

    VAULTSTRETCHER

    BUSHINGEXTENDER

    THREADEDSTUD

    THREADEDSTUD

    WINDOW-OPSEE PGS 16 &17

    CAM-OPCABLE

    ADAPTER

    COMPRESSIONLUG

    SEE PGS 12 & 13

    SEE PGS 12 & 13

    CAM-OPLINK CONNECTOR

    SEE PGS 14 & 15

    SEE PGS 14 & 15

    SEE PGS 16 & 17VS2

    VS3

    VS4VAULT STRETCHERS

    CABLE TO CABLE UTILIZING

    CATALOG 2001 Page 10 ID: 0198

    SEPARABLE CONNECTORS 600 SERIES DEADBREAK

    SEE PAGE 26 FORSURGE ARRESTER

    APPLICATIONS

  • DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #

    Illustration Description Voltage ELASTIMOLD Notes(not to scale) Class Part Number

    600 Series Elbow 15/25kV K655LR-W0X N1,2(w/ Insul. Plug, Use Tables W7 and X6

    Cap, Stud, Lug & 35kV 755LR-W0X N1,2Cable Adapter) Use Tables W9 and X6

    600 Series Elbow 15/25kV K656LR-W0X N1,2w/ Test Point Use Tables W7 and X6

    (w/ Insul. Plug, 35kV 756LR-W0X N1,2Cap, Stud, Lug & Use Tables W9 and X6

    Cable Adapter)600 Series Elbow 15/25kV K655BLR N1,3

    Housing only 35kV 755BLR N1,3(w/ Stud)

    600 Series Elbow 15/25kV K656BLR N1,3w/ Test Point 35kV 756BLR N1,3

    (Housing onlyw/ Stud)

    600 Series Straight 15/25kV K655SR-W0X N1,2,12Receptacle Use Tables W7 and X6

    (w/Cable Adapter, Lug &

    Retaining Ring)600 Series Straight 15/25kV K655BSR N1,12

    Receptacle Housing (Lug

    & Cable Adapter not included)

    Straight Receptacle 15/25kV K650SRA N1,4Adapter

    600 Series 15/25kV K655BVS N1,9Vault Stretcher(Housing only

    w/ Stud)Cable Size 15/25kV 655CA-W

    Adapter Use Table W735kV 755CA-W

    Use Table W9

    Compression ALL 03700X N5Lug Use Table X6

    ALL 03702X N6Use Table X6

    600 Series Elbow 15/25kV 655CK-W0X N2Size Sensitive Kit Use Tables W7 and X6(Cable Adapter 35kV 755CK-W0X N2

    & Lug) Use Tables W9 and X6Adapter ALL 650ARR-X

    Retaining Ring Use Table X6

    600 Series Straight 15/25kV 655CK-W0X-ARR N2Receptacle Size Use Tables W7 and X6

    Sensitive Kit (Cable 35kV 755CK-W0X-ARR N2Adapter, Retaining Use Tables W9 and X6

    Ring & Lug)Bushing 15/25kV K655BE N1,3Extender 35kV 755BE N1,3(w/ Stud)

    Insulated Cap 15/25kV K656DR N3,7w/ Test Point

    (w/ Stud)Insulating Plug 15/25kV K650BIP N1,7,8

    (w/ Cap) 35kV 750BIP N1,7,8Grounding Plug 15/25kV 650GP N1,7,8(Ground Lead 35kV 750GP N1,7,8

    2/0 AWG x 30")Insulated 15/25kV K650SOP N7,8

    Parking Bushing 35kV 750SOP N7,8Connecting Plug 15/25kV K650CP N1,7,8,9

    35kV 750CP N1,7,8,9

    CATALOG 2001 Page 11 ID: 0198

    600 SERIES DEADBREAK

    N1. For 900 Amp ratings, substitute 675 for 650 and 655; 676 for 656; K675for K650 and K655; K676 for K656; 775 for 750 and 755; 776 for 756and 2X for 0X in the part number. The 900 Amp rating requires coppercurrent-carrying connector components and copper conductor cable.

    N2. Add suffix symbol from page 29 to include cable shield grounding kitand/or cable jacket sealing kit.

    N3. Available without the stud by adding N to the part number.N4. Straight Receptacle Adapter is used to connect Straight Receptacles

    K655YBSR and K655YSR-W0X (Pg.14) to equipment bushings.N5. Aluminum lug for use on aluminum or copper conductors. DO NOT

    substitute threaded 03600X lug.N6. Copper lug for use on COPPER CONDUCTOR ONLY. DO NOT substitute

    threaded 03602X lug.N7. Available with the stud factory-assembled by adding SP to the part

    number.N8. Available with a loose stud by adding suffix S to the part number.N9. 600SW spanner wrench is recommended for installation of connecting

    plugs, deadbreak reducing tap plugs and reducing tap wells..N10. 600AT assembly tool is required for installation of loadbreak reducing

    tap plugs.N11. Rubber junction with stainless steel mounting plate and back plate.

    Add -U for rubber junction with stainless steel mounting plate, backplate and adjustable bracket.Add -4 for rubber junction only.Add -5 for rubber junction, stainless steel U-straps and back plate.

    N12. 600 Series Elbows and Straight Receptacles with IEEE Std. 386capacitive test points are available by substituting 656 for 655; K656 forK655; K676 for K675; 756 for 755; 676 for 675; K676 for K675 and 776for 775 in the part number.

    N13. See page 17 for Window-Op Connector Kit.

    Illustration Description Voltage ELASTIMOLD Notes(not to scale) Class Part Number

    Deadbreak 15/25kV K650RTP N1,7,8,9ReducingTap Plug

    Reducing Tap 15/25kV K650RTW N1,7,8,9Well

    Loadbreak 15kV 650ETP N1,7,8,10,13Reducing 25kV K650ETP N1,7,8,10,13Tap Plug 35kV 750ETP N1,7,8,10,13

    Vault Stretcher 15/25kV 650VSA N1Threaded Stud

    600 Series Elbow 15/25kV 650SA N1Threaded Stud 35kV 750SA N1Assembly Tool ALL 600AT N10

    Spanner Wrench ALL 600SW N9

    2-Point Junction 15/25kV K650J2 N1,1135kV 750J2 N1,11

    3-Point Junction 15/25kV K650J3 N1,1135kV 750J3 N1,11

    4-Point Junction 15/25kV K650J4 N1,1135kV 750J4 N1,11

    Refer to the W and X tables on pages 32 and 33 for sizing to cable insulation diameter and conductor size.

    For cable shield adapters and jacket seals, see page 28.

    Part numbers that containthe letters W or X are sizesensitive. To complete thepart number, refer to the W or X tables indicated.

  • CATALOG 2001 Page 12 ID: 0198ELASTIMOLD

    SEPARABLE CONNECTORS

    600 SERIES DEADBREAK Contd from Pg. 11

    600 Series deadbreak elbows, straight recepta-cles, junctions, vault stretchers and accessoriesare used to connect equipment and cable onprimary feeder and network circuits. Designsaccommodate large conductors and featurebolted connections and deadfront modularconstruction for maximum reliability, perfor-mance and versatility.DE-ENERGIZED connectors can be quicklyand easily connected and disconnectedusing standard hand tools and equipment in accordance with accepted operating practices. Optional accessories allow visibleexternal separation, by-pass, isolation, dead-ending, grounding, and testing as well asadding taps, surge arresters and circuit protection.Hot-stick operable and separable joint systemsare shown on pages 14 thru 19.

    RATINGS OVERVIEWSee page 2 for complete information.

    CURRENT RATINGS(Prefixes: 650, K650, K655, K656,750, 755, 756 & 03700)600 Amp Continuous25kA sym.,10 cycles(Prefixes 675,K675,K676,775,776 & 03702)900 Amp Continuous25kA sym.,10 cyclesNOTE: 900 Amp ratings require copper cable and copper current-carrying components.

    VOLTAGE RATINGS15/25kV Class (5kV thru 28kV)16.2kV Phase-to-Ground28kV Phase-to Phase140kV BIL45kV AC Withstand84kV DC Withstand21.5kV Corona Extinction35kV Class21.1kV Phase-to-Ground36.6kV Phase-to-Phase150kV BIL50kV AC Withstand103kV DC Withstand26kV Corona ExtinctionNote: Elastimold has increased the IEEE StandardProduction and Design Test levels for 25kV Classproducts to include 27kV and 28kV systems.

    INTEGRAL BUSHING

    RETAININGRING

    CABLE TO EQUIPMENT

    COMPRESSIONLUG

    CABLEADAPTER

    CABLE TO CABLE

    STRAIGHT RECEPTACLEHOUSING

    LOADBREAKREDUCINGTAP PLUG

    200A LOADBREAKSEE PAGES 4, & 5

    200A DEADBREAKSEE PAGES 8 & 9

    LINK-OPLINK CONNECTOR

    SPANNER WRENCH

    OPERATINGACCESSORIES

    4 PT JUNCTION

    3 PT JUNCTION

    2 PT JUNCTION

    (UTILIZING JUNCTIONS)

    HOTSTICK OPERABLE 600 SERIESCONNECTORS - SEE PAGES 14 - 17

    STICK-OP

    LINK-OP

    COMPRESSIONLUG

    CABLEADAPTER

    VAULTSTRETCHER

    CONNECTOR

    CABLE TO CABLE

    L-1

    UTILIZING L-KITS

    L-2

    ELBOW CONNECTOR

    STICK-OPLOADBREAK REDUCING

    TAP PLUG

    BOLT &WASHERS

    STRAIGHTRECEPTACLE ADAPTER

    L-3

    L-4

    THREADEDSTUD

    LINK-OPRETAINERSLEEVES

    200A TAPS

    INSULATINGPLUG

    INSULATEDPARKING BUSHING

    BUSHINGEXTENDER

    THREADEDCOMPRESSION

    LUG

    600 SERIESELBOW

    CABLEADAPTER

    COMPRESSIONLUG

    CONNECTINGPLUG

    STRAIGHT RECEPTACLE

    REDUCING TAPWELL

    THREADEDSTUD VOLTAGE

    DETECTIONCAP

    INSULATED CAPWITH TEST POINT

    GROUNDINGPLUG

    DEADBREAKREDUCINGTAP PLUG600 SERIES

    TAPS

    CAM-OPRETAINERSLEEVES

    CONNECTINGPLUG

    VAULTSTRETCHER

    BUSHINGEXTENDER

    THREADEDSTUD

    THREADEDSTUD

    WINDOW-OPSEE PGS 16 &17

    CAM-OPCABLE

    ADAPTER

    COMPRESSIONLUG

    CAM-OPLINK CONNECTOR

    SEE PGS 14 & 15

    SEE PGS 14 & 15

    SEE PGS 16 & 17VS2

    VS3

    VS4VAULT STRETCHERS

    CABLE TO CABLE UTILIZING

    SEPARABLE CONNECTORS 600 SERIES DEADBREAK

    SEE PAGE 26 FORSURGE ARRESTER

    APPLICATIONS

  • DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #

    CATALOG 2001 Page 13 ID: 0198

    Illustration Description Voltage ELASTIMOLD Notes(not to scale) Class Part Number

    1-way 15/25kV K655L1 N1,2,3,4L-Kit 35kV 755L1 N1,2,3,4

    2-way 15/25kV K655L2 N1,2,3,4L-Kit 35kV 755L2 N1,2,3,4

    2-way 15/25kV K655VS2 N1,2,3VS-Kit

    3-way 15/25kV K655L3 N1,2,3,4L-Kit 35kV 755L3 N1,2,3,4

    3-Way 15/25kV K655VS3 N1,2,3VS Kit

    4-Way 15/25kV K655L4 N1,2,3,4L-Kit 35kV 755L4 N1,2,3,4

    4-Way 15/25kV K655VS4 N1,2,3VS-Kit

    Spanner Wrench ALL 600SW N2

    600 SERIES DEADBREAKN1. For 900 Amp ratings, substitute 675 for 650 and 655; 676 for 656; K675

    for K650 and K655; K676 for K656; 775 for 750 and 755; 776 for 756 and2X for 0X in the part number. The 900 Amp rating requires copper current-carrying connector components and copper conductor cable.

    N2. 600SW spanner wrench is recommended for installation of connectingplugs, deadbreak reducing tap plugs and reducing tap wells.

    N3. L-Kits and VS-Kits do not include cable adapters, compression lugs oradapter retaining rings. These items must be ordered separately.

    N4. 600 Series Elbows and Straight Receptacles with IEEE Std. 386 capacitivetest points are available by substituting 656 for 655; K656 for K655; K676for K675; 756 for 755; 676 for 675; K676 for K675 and 776 for 775 in thepart number.

    Refer to the W and X tables on pages 32 and 33 for sizing to cable insulation diameter and conductor size.

    For cable shield adapters and jacket seals, see page 28.

    VAULT STRETCHER

    Provides an alternate method of splicing and joiningvarious types and styles of cables using standard 600 Series components.

    Part numbers that containthe letters W or X are sizesensitive. To complete thepart number, refer to the W or X tables indicated.

  • SEPARABLE CONNECTORS CAM-OP, LINK-OP

    600 SERIES DEADBREAK

    CATALOG 2001 Page 14 ID: 0198ELASTIMOLD

    Elastimolds 600 Series Cam-Op

    ~, andLink-Op~ deadbreak connector systemsincorporate provisions for hotstick opera-tion of DE-ENERGIZED primary feederor network circuits. Configurations allowexternal visible break, testing, groundingand isolation. Retrofit kits allow upgrad-ing existing equipment.

    Cam-Op systems utilize pin and socketconnectors. Link-Op connectors arebolted and installed using torque con-trolled tools. Either system can be retro-fitted to existing equipment.

    The Cam-Op and Link-Op connectorsare unique, allowing all hotstick opera-tions to be completed without movingthe cable, an important considerationwhen large, stiff cables prohibit move-ment.

    The Cam-Op connector is easily in-stalled or removed by hotstick operationof the cam action disconnect lever.

    LOADBREAKELBOW CONNECTOR

    INSULATEDCAP ELBOW

    ARRESTER

    LINKCONNECTOR

    LINK-OP

    LINK-OP

    CAM-OP

    CAM-OP

    RETAINERSLEEVES

    OR2-POINT INSULATED

    BUSHINGS

    OR

    OROR

    OR

    OR

    OR

    600 SERIESELBOW

    600 SERIESELBOW

    COMPRESSIONLUG

    COMPRESSIONLUG

    SEECABLENOTES

    SEECABLENOTES

    CABLEADAPTER

    600 SERIESELBOW

    COMPRESSIONLUG

    SEE CABLE NOTES

    CABLEADAPTER

    CABLEADAPTER

    LOADBREAKELBOW CONNECTOR

    INSULATEDCAP

    ELBOWARRESTER

    LINK CONNECTOR

    BUSINGEXTENDER

    ALIGNMENTBRACKET

    ALIGNMENTBRACKET

    LINK-OP

    CAM-OP

    LINK-OPLINK-OP

    CAM-OPCAM-OP

    RETAINERSLEEVES

    INSULATEDPARKINGBUSHING

    EQUIPMENTBUSHING

    EQUIPMENTBUSHING

    MOUNTABLE INSULATEDPARKING BUSHING

    OR

    LINK-OP

    CAM-OP

    LOADBREEAKREDUCING TAP PLUG

    OPERATING TOOL

    TEST ROD

    GROUNDINGELBOW

    RETROFIT COMPONENTS FOREXISTING EQUIPMENT W/O PROVISIONS FOR MOUNTABLE INSULATED BUSHING

    CABLE TO EQUIPMENT

    CABLE TO CABLE CONNECTION

    CAM-OP & LINK-OP SYSTEM 600 SERIES DEADBREAKRATINGS OVERVIEWSee page 2 for complete information.

    CURRENT RATINGS600 & 900 Amp Continuous25kA sym.,10 cycles

    NOTE: 900 Amp ratings require copper cable and copper current-carrying components.

    CONTINUOUS VOLTAGE RATINGS15kV Class8.3kV Phase-to-Ground14.4kV Phase-to Phase95kV BIL34kV AC Withstand53kV DC Withstand11kV Corona Extinction25kV Class15.2kV Phase-to-Ground26.3kV Phase-to Phase125kV BIL40kV AC Withstand78kV DC Withstand19kV Corona Extinction35kV Class21.1kV Phase-to-Ground36.6kV Phase-to-Phase150kV BIL50kV AC Withstand103kV DC Withstand26kV Corona Extinction

    SEE PAGE 26 FORSURGE ARRESTER

    APPLICATIONS

  • DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #

    CATALOG 2001 Page 15 ID: 0198

    Illustration Description Voltage ELASTIMOLD Notes(not to scale) Class Part Number

    CAM-OP 15kV 655LINK-C-LR-W0X-B-DRG N1,3,11,CONNECTOR Use Tables W7 and X6 13,14,18

    KIT 25kV K655LINK-C-LR-W0X-B-DRG N1,3,11,Use Tables W7 and X6 13,14,18

    35kV 755LINK-C-LR-W0X-B-DRG N1,3,11,Use Tables W9 and X6 13,14,18

    LINK-OP 15kV 655LINK-B-LR-W0X-B-DRG N2,3,11,12CONNECTOR Use Tables W7 and X6 13,14,18

    KIT 25kV K655LINK-B-LR-W0X-B-DRG N2,3,11,Use Tables W7 and X6 13,14,18

    35kV 755LINK-B-LR-W0X-B-DRG N2,3,11,Use Tables W9 and X6 13,14,18

    Mountable 25kV K650LBM-3 N3Insulated 35kV 750LBM-3 N3Bushing

    RETROFIT 15kV 655LINK-C-LR-W0X-A-DRG N5,11,13CAM-OP Use Tables W7 and X6 14,18

    CONNECTOR 25kV K655LINK-C-LR-W0X-A-DRG N5,11,13KIT Use Tables W7 and X6 14,18

    35kV 755LINK-C-LR-W0X-A-DRG N5,11,13Use Tables W9 and X6 14,18

    RETROFIT 15kV 655LINK-B-LR-W0X-A-DRG N6,11,12,LINK-OP Use Tables W7 and X6 13,14,18

    CONNECTOR 25kV K655LINK-B-LR-W0X-A-DRG N6,11,12,KIT Use Tables W7 and X6 13,14,18

    35kV 755LINK-B-LR-W0X-A-DRG N6,11,12,Use Tables W9 and X6 13,14,18

    Insulating 25kV K650LB N4Plug 35kV 750LB N4

    CAM-OP 15kV 650CABAlignment 25kV K650CAB

    Bracket 35kV 750CABLINK-OP ALL 650AB N15

    Alignment ALL 650ABV N15Bracket (RetrofitLINK-OP Only)Compression ALL 03700X N7

    Lug Use Table X6 N8ALL 03702X

    Use Table X6

    CAM-OP & 15/25kV 655CK-W0X N13LINK-OP Size Use Tables W7 and X6Sensitive Kit 35kV 755CK-W0X N13

    (Cable Adapter Use Tables W9 and X6& Lug)

    CAM-OP Re- ALL 650RSC N11taining Sleeve

    LINK-OP ALL 650RS N11Retaining

    SleeveCAM-OP 15kV 655BI-LINK-C-LR-WOX-DRG N9,11,13

    CABLE JOINT Use Tables W7 and X6 14,18KIT 25kV K655BI-LINK-C-LR-WOX-DRG N9,11,13

    Use Tables W7 and X6 14,1835kV 755BI-LINK-C-LR-WOX-DRG N9,11,13

    Use Tables W9 and X6 14,18LINK-OP 15kV 655BI-LINK-B-LR-WOX-DRG N10,11,12,

    CABLE JOINT Use Tables W7 and X6 13,14,18KIT 25kV K655BI-LINK-B-LR-WOX-DRG N10,11,12,

    Use Tables W7 and X6 13,14,1835kV 755BI-LINK-B-LR-WOX-DRG N10,11,12,

    Use Tables W9 and X6 13,14,18CAM-OP 15kV 650LK-C-VB

    Loadbreak 25kV K650LK-C-VBReducing 35kV 750LK-C-VBTap Plugs

    (Visi-Break)LINK-OP 15kV 650LT-B N11

    Loadbreak 25kV K650LT-BReducing 35kV 750LT-BTap Plug

    CAM-OP & LINK-OPIllustration Description Voltage ELASTIMOLD Notes

    (not to scale) Class Part NumberGrounding 15kV 160GLR

    Elbow 25kV 370GLR N19(1/0 AWG x 6' 35kV 370GLR N19Ground Lead)

    Test Rod ALL 370TR

    Assembly Tool ALL 600AT N11

    CAM-OP 15kV 650CAM-OK N16OPERATING 25kV K650CAM-OK N16

    KIT 35kV 750CAM-OK N16

    LINK-OP 15kV 650LINK-OK N17OPERATING 25kV K650LINK-OK N17

    KIT 35kV 750LINK-OK N17

    AB ABV

    N1. Cam-Op connector kit includes: 1- Cam-Op link; 1- elbow housing; 1-cable adapter; 1-0370 style lug; 1- bushing extender; 2- retainer sleeves;1- insulated cap; 1- mountable insulated bushing and 1- alignmentbracket.

    N2. Link-Op connector kit includes: 1- Link-Op link; 1- elbow housing; 1-cable adapter; 1-0370 style lug; 1- bushing extender; 2- retainer sleeves;2- insulated caps; and 1- mountable insulated bushing.

    N3. Mountable insulated bushing included with Cam-Op and Link-Op connec-tor kit. Requires 3 threaded studs on equipment faceplate for installation.

    N4. Use with the Retrofit Cam-Op and Retrofit Link-Op connector kit.N5. Retrofit Cam-Op connector kit includes: 1- link; 1- elbow housing; 1-

    cable adapter; 1-0370 style lug; 1- bushing extender; 2- retainer sleeves;1- insulated cap; 1- insulating plug; and 1- alignment bracket.

    N6. Retrofit Link-Op connector kit includes: 1- link; 1- elbow housing; 1-cable adapter; 1-0370 style lug; 1- bushing extender; 2- retainer sleeves;2- insulated caps; 1- insulating plug; and 1- alignment bracket.

    N7. Aluminum lug for use on aluminum or copper conductors. DO NOT sub-stitute threaded 03600X lug.

    N8. Copper lug for use on COPPER CONDUCTOR ONLY. DO NOT substi-tute 03602X threaded lug.

    N9. Cam-Op Cable Joint Kit includes: 1- Cam-Op link; 1- Cam-Op BI-SOP; 2-elbow housings; 2- cable adapters; 2- 0370 style lugs; 2- retainersleeves; 1- insulated cap.

    N10. Link-Op Cable Joint Kit includes: 1- Link-Op link; 1- Link-Op BI-SOP; 2-elbow housings; 2- cable adapters; 2- 0370 style lugs; 2- retainersleeves; 2- insulated caps.

    N11. 600AT assembly tool required for operation and/or installation. N12. For 900 Amp ratings, substitute 675 for 650 and 655; 676 for 656; K675

    for K650 and K655; K676 for K656; 775 for 750 and 755; 776 for 756and 2X for 0X in the part number. The 900 Amp rating requires coppercurrent-carrying connector components and copper conductor cable.

    N13. Add suffix symbol from page 29 to include cable shield grounding kitand/or cable jacket sealing kit.

    N14. To add elbows or arresters instead of insulating caps, replace the DRGwith LR-WX for elbows (with test point) or ESA for elbow arresters.

    N15. The 650ABV is required when the bushing horizontal spacing on theequipment or junctions is less than 5".

    N16. Cam-Op operating kit includes accessories that enable visible break,testing, isolation and grounding functions to be performed. Kit includes:3- Cam-Op loadbreak reducing tap plugs; 3- grounding elbows; 1- as-sembly tool; 1- test rod; 1- carry case; 1- lubricant; 1- instructions.

    N17. Link-Op operating kit includes accessories that enable visible break,testing, isolation and grounding functions to be performed. Kit includes:6- Link-Op loadbreak reducing tap plugs; 3- grounding elbows; 1- as-sembly tool; 1- test rod; 1- carry case; 1- lubricant; 1- instructions.

    N18. 600 Series Elbows and Straight Receptacles with IEEE Std. 386 capaci-tive test points are available by substituting 656 for 655; K656 for K655;K676 for K675; 756 for 755; 676 for 675; K676 for K675 and 776 for 775in the part number.

    N19. Rated for both 25kV and 35kV applications.

    Refer to the W and X tables on pages 32 and 33 for sizing to cable insulation diameter and conductor size.

    For cable shield adapters and jacket seals, see page 28.

    Part numbers that containthe letters W or X are sizesensitive. To complete thepart number, refer to the W or X tables indicated.

  • ELASTIMOLD

    SEPARABLE CONNECTORS STICK-OP, WINDOW-OP

    600 SERIES DEADBREAK

    CATALOG 2001 Page 16 ID: 0198

    Elastimolds 600 Series Window-Op~and Stick-Op~ deadbreak connectorsystems incorporate provisions for hotstick operation of DE-ENERGIZEDprimary feeder or network circuits.

    The Window-Op and Stick-Op connec-tors allow direct testing and groundingwith no required cable movement.

    Window-Op is ideal for equipment applications which include viewing windows to provide an internal visiblebreak that does not require hot stick removal of the elbows.

    Stick-Op provides an external visiblebreak by hot stick removal of the elbow.

    Window-Op and Stick-Op connectorsare bolted and installed using torquecontrolled tools.

    600 SERIESELBOW

    CABLE ADAPTER

    TEST ROD

    OPERATING ACCESSORIES

    INTEGRALBUSHING

    ASSEMBLY TOOL(STICK-OP)

    ASSEMBLY TOOL(WINDOW-OP)

    GROUNDINGELBOW

    STAND-OFFPLUG

    SEE CABLE NOTES

    LOADBREAKREDUCINGTAP PLUG

    STICK-OP600DB/200LB

    BUSHING/ELBOWADAPTER

    THREADEDCOMPRESSION LUG

    STICK-OP

    GROUNDINGPLUG

    INSULATED CAP

    STICK-OP

    WINDOW-OP

    COMPRESSION LUGWINDOW-OP

    OR

    STICK-OP & WINDOW-OP SYSTEM 600 SERIES DEADBREAK

    BOLTED CONNECTIONLOADBREAK REDUCINGTAP PLUG

    INSULATEDCAP

    STICK-OPERABLE

    RATINGS OVERVIEWSee page 2 for complete information.

    CURRENT RATINGS600 & 900 Amp Continuous25kA sym.,10 cycles

    NOTE: 900 Amp ratings require copper cable and copper current-carrying components.

    CONTINUOUS VOLTAGE RATINGS15kV Class8.3kV Phase-to-Ground14.4kV Phase-to Phase95kV BIL34kV AC Withstand53kV DC Withstand11kV Corona Extinction25kV Class15.2kV Phase-to-Ground26.3kV Phase-to Phase125kV BIL40kV AC Withstand78kV DC Withstand19kV Corona Extinction35kV Class21.1kV Phase-to-Ground36.6kV Phase-to-Phase150kV BIL50kV AC Withstand103kV DC Withstand26kV Corona Extinction

    SEE PAGE 26 FORSURGE ARRESTER

    APPLICATIONS

  • DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #

    CATALOG 2001 Page 17 ID: 0198

    Illustration Description Voltage ELASTIMOLD Notes(not to scale) Class Part Number

    WINDOW-OP 15kV 655ETP-W0X-DRG N1,3,4,5,CONNECTOR Use Tables W7 and X6 6,13

    KIT 25kV K655ETP-W0X-DRGUse Tables W7 and X6

    35kV 755ETP-W0X-DRGUse Tables W9 and X6

    STICK-OP 15kV 655LRTP-W0X-DRG N2,3,4,5,CONNECTOR Use Tables W7 and X6 8,13

    KIT 25kV K655LRTP-W0X-DRGUse Tables W7 and X6

    35kV 755LRTP-W0X-DRGUse Tables W9 and X6

    WINDOW-OP 15kV 650ETP N4,15Loadbreak 25kV K650ETP N4,15Reducing 35kV 750ETP N4,15Tap Plug

    STICK-OP 15kV 650LRTPA3 N3,4Loadbreak 25kV K650LRTPA2Reducing 35kV 750LRTPA2Tap Plug

    STICK-OP 15kV 650BEA3 N3,4Bushing 25kV K650BEA2Adapter 35kV 750BEA2

    Compression ALL 03700X N6Lug Use Tables X6

    WINDOW-OP ALL 03702X N7Use Tables X6

    Threaded ALL 03600X N8Compression Use Tables X6

    Lug ALL 03602X N9STICK-OP Use Tables X6

    WINDOW-OP 15/25kV 655CK-W0X N5Size Sensitive Kit Use Tables W7 and X6(Cable Adapter 35kV 755CK-W0X N5

    & Lug) Use Tables W9 and X6

    STICK-OP 15/25kV 655TCK-W0X N5Size Sensitive Kit Use Tables W7 and X6(Cable Adapter 35kV 755TCK-W0X N5

    & Threaded Lug) Use Tables W9 and X6

    Extraction Tool ALL 600ET N3,10

    Grounding 15kV 160GLRElbow 25kV 370GLR N14

    (1/0 AWG x 6' 35kV 370GLR N14Ground Lead)

    Test Rod ALL 370TR

    Assembly Tool ALL 600AT N3(Stick-Op)

    Assembly Tool ALL 600ATM N15(Window-Op)

    STICK-OP 15kV 650STICK-OK N11OPERATING 25kV K650STICK-OK N11

    KIT 35kV 750STICK-OK N11

    WINDOW-OP 15kV 650WINDOW-OK N12OPERATING 25kV K650WINDOW-OK N12

    KIT 35kV 750WINDOW-OK N12

    N1. Window-Op Kit includes: insulated cap; Window-Op reducing tap plug;600 Series elbow housing; cable adapter; and 0370 style compressionlug.

    N2. Stick-Op Kit includes insulated cap; Stick-Op Loadbreak reducing tapplug; 600A Elbow Housing; cable adapter; and threaded 0360 stylecompression lug.

    N3. 600AT assembly tool required for operation and/or installation.N4. For 900 Amp ratings, substitute 675 for 650 and 655; 676 for 656; K675

    for K650 and K655; K676 for K656; 775 for 750 and 755; 776 for 756and 2X for 0X in the part number. The 900 Amp rating requires coppercurrent-carrying connector components and copper conductor cable.

    N5. Add suffix symbol from page 29 to include cable shield grounding kitand/or cable jacket sealing kit.

    N6. Aluminum lug for use on aluminum or copper conductors. DO NOTsubstitute threaded 03600X lug.

    N7. Copper lug for use on COPPER CONDUCTOR ONLY. DO NOTsubstitute 03602X threaded lug.

    N8. Threaded aluminum lug (Stick-Op only) for use on copper or aluminumconductors. DO NOT substitute unthreaded 03700X lugs. DO NOT usewith 675, 676, K675, K676, 775 or 776 part numbers.

    N9. Threaded copper lug (Stick-Op only) for use on copper conductors only.DO NOT substitute unthreaded 03702X lugs.

    N10. Required to disassemble Stick-Op loadbreak reducing tap plug from thethreaded compression lug and 600 Series elbow after the shear-pin isbroken during assembly.

    N11. Stick-Op Operating Kit includes accessories that enable visible breakdirect testing, isolation, and grounding functions to be performed. Kitincludes: 3-insulated parking bushings; 3-grounding elbows; 3-600DB/200LB bushing/elbow adapters; 1-assembly tool; 1-test rod; 1-carry case; l-lubricant; 1-instructions.

    N12. Window-Op Operating Kit includes accessories that enable visiblegrounding and direct testing functions to be performed. Kit includes: 3-grounding elbows; 1-test rod; 1-carry case; 1-lubricant; 1-instructions.

    N13. 600 Series Elbows and Straight Receptacles with IEEE Std. 386capacitive test points are available by substituting 656 for 655; K656 forK655; K676 for K675; 756 for 755; 676 for 675; K676 for K675 and 776for 775 in the part number.

    N14. Rated for both 25kV and 35kV applications.N15. 600ATM assembly tool required for Window-Op assembly.

    STICK-OP & WINDOW-OP

    Refer to the W and X tables on pages 32 and 33 for sizing to cable insulation diameter and conductor size.

    For cable shield adapters and jacket seals, see page 28.

    Part numbers that containthe letters W or X are sizesensitive. To complete thepart number, refer to the W or X tables indicated.

  • SEPARABLE CONNECTORS CABLE JOINTS

    600 SERIES DEADBREAK

    CATALOG 2001 Page 18 ID: 0198ELASTIMOLD

    600 Series Separable Cable Joints are available in 2, 3 and 4-way versions and include a capaci-tive test point as standard. Units are interchange-able, featuring bolted connections. Designs arecompact and ideally suited for small vaults andmanholes.DE-ENERGIZED joints can be quickly and easilyconnected and disconnected using standardhand tools and equipment in accordance with accepted operating practices. Bus bars can bechanged to add or remove cables from the joint.Optional accessories include insulating andgrounding caps and plugs which allow visible ex-ternal separation, by-pass, isolation, dead-ending,grounding and testing.

    OPERATING ACCESSORIES

    COMPRESSION LUG

    STRAIGHT RECEPTACLE HOUSING

    BOLT &WASHERSRETAINING

    RING

    CABLE ADAPTER

    GROUNDING PLUGGROUNDING CAP

    INSULATED CAP WITH BAIL

    INSULATING PLUGW/TEST POINT & CAP

    3 7/88 1/8

    37 1/84 1/4

    W/ TEST POINT

    D

    A

    C

    2-WAY INSULATED BUS BAR

    3-WAY INSULATED BUS BAR

    B

    4-WAY INSULATED BUS BAR

    A

    DCBA

    DIMENSION INCHES

    SEPARABLESTRAIGHT JOINT

    (2-WAY)

    SEPARABLEWYE-JOINT(3-WAY)

    SEPARABLEH-JOINT(4-WAY)

    SEPARABLE CABLE JOINTS 600 SERIES DEADBREAK RATINGS OVERVIEWSee page 2 for complete information

    CURRENT RATINGS(Prefixes: 650, K650, K655, K656 & 03700)600 Amp Continuous25kA sym.,10 cycles(Prefixes: 675, K675, K676 & 03702)900 Amp Continuous25kA sym.,10 cyclesNOTE: 900 Amp ratings require copper cable and copper current-carrying components.

    VOLTAGE RATINGS15/25kV Class (5kV thru 28kV)16.2kV Phase-to-Ground28kV Phase-to Phase140kV BIL45kV AC Withstand84kV DC Withstand21.5kV Corona ExtinctionNote: Elastimold has increased the IEEE StandardProduction and Design Test levels for 25kV Classproducts to include 27kV and 28kV systems.

    Note: The separablecable joints shownhere use a special Yinterface that may notbe interchangeablewith other 600 Seriesinterfaces.

  • DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #

    CATALOG 2001 Page 19 ID: 0198

    Illustration Description Voltage ELASTIMOLD Notes(not to scale) Class Part Number

    Separable 15/25kV K656I-W0X N1,6,8Straight Joint Pkg. Use Tables W7 and X6

    (2-way)w/ Test Point

    Basic Housing Pkg. 15/25kV K656I-HP N2,6Straight Jointw/ Test Point

    Separable 15/25kV K656CY-W0X N1,6,8Wye Joint Pkg. Use Tables W7 and X6

    (3-Way)w/ Test Point

    Basic Housing Pkg. 15/25kV K656CY-HP N2,6Wye Joint

    w/ Test point

    Separable 15/25kV K656CH-W0X N1,6,8H Joint Pkg. Use Tables W7 and X6

    (4-Way)w/ Test Point

    Basic Housing Pkg. 15/25kV K656CH-HP N2,6H Joint

    w/ Test Point

    2-Way 15/25kV K656I-BUS N3,6Insulated Bus Bar

    w/Test Point

    3-Way 15/25kV K656CY-BUS N3,6Insulated Bus Bar

    w/Test Point

    4-Way 15/25kV K656CH-BUS N3,6Insulated Bus Bar

    w/Test Point

    Straight 15/25kV K655YSR-W0X N4,6,8Receptacle Use Tables W7 and X6

    Straight 15/25kV K655YBSR N5,6,Receptacle 10

    HousingOnly

    Insulated Cap 15/25kV K655YDRw/ Bail

    Bail 15/25kV 650BAOnly

    Cable Adapter 15/25kV 655CA-WUse Table W7

    Adapter 15/25kV 650ARR-XRetaining Ring Use Table X6

    Compression Lug 15/25kV 03700X N6,715/25kV 03702X N6,9

    Use Table X6

    600 Series 15/25kV 655CK-W0X N8Straight Receptacle Use Tables W7 and X6

    Size Sensitive Kit(Cable Adapter,Retaining Ring

    & Lug)Assembly/ 15/25kV 600YADT

    DisassemblyTool

    N1. Complete Joint Packages consisting of: insulated bus bar; straight receptacle housings, retaining rings, cable size adapters, lugs, bolts andwashers.

    N2. Housing Packages consisting of the following non-size sensitive components of the joint: insulated bus bar, straight receptacle housings, bolts and washers.

    N3. Insulated bus bar only.N4. Straight Receptacle consisting of: straight receptacle housing, retaining

    ring, cable adapter, lug, bolt and washers.N5. Straight receptacle housing consisting of: straight receptacle housing,

    bolt and washers.N6. For 900 Amp ratings, substitute 675 for 650 and 655; 676 for 656; K675

    for K650 and K655; K676 for K656; 775 for 750 and 755; 776 for 756and 2X for 0X in the part number. The 900 Amp rating requires coppercurrent-carrying connector components and copper conductor cable.

    N7. Aluminum lug for use on aluminum or copper conductors. DO NOT substitute threaded 03600X lug.

    N8. Add suffix symbol from page 29 to include cable shield grounding kitand/or cable jacket sealing kit.

    N9. Copper lug for use with COPPER CONDUCTOR ONLY. DO NOTsubstitute threaded 03602X lug.

    N10. Available without the bolt & washers by adding N to the part number.

    Illustration Description Voltage ELASTIMOLD Notes(not to scale) Class Part Number

    Insulating Plug w/ 15/25kV K650YBIPTest Point & Cap

    Grounding Plug 15/25kV 650YGP(4/0 AWG x 6'Ground Lead)

    Grounding Cap 15/25kV 650YGDR(4/0 AWG x 6'Ground Lead)

    Aluminum Bolt 15/25kV 650BAW N6& Washers

    Brass Bolt & 15/25kV 675BAW N6Washers

    600 SERIES DEADBREAK

    Refer to the W and X tables on pages 32 and 33 for sizing to cable insulation diameter and conductor size.

    For cable shield adapters and jacket seals, see page 28.

    Part numbers that containthe letters W or X are sizesensitive. To complete thepart number, refer to the W or X tables indicated.

  • PCJ CABLE JOINTS

    ELASTIMOLD

    PCJ~Power Cable Joints utilize perma-nently crimped connectors. PCJ Housingsare fully insulated, shielded and sealed fordirect buried, vault, submersible and othersevere service applications. Units havebeen designed and tested per IEEEStandard 404 to assure system matchedperformance and ratings equal to the cableto which the splice will be installed.

    PCJ Power Cable Joints are available in 2 styles:

    Style 1 uses a single piece housing that issized to accommodate a specific range ofcable. Style 1 units are ideally suited forstraight splicing of the same or similarcable.

    Style 2 designs incorporate a universalhousing with separate cable adapters toallow transition splices of different types and sizes of cable.

    ELECTRICAL RATINGS SUMMARYThe follow ratings summary is based on IEEE Std. 404 and applies to all Elastimold PCJ Power Cable Joints.

    VOLTAGEA. 15kV Class (8.7kV Phase-to-Ground)B. 25kV Class (14.4kV Phase-to-Ground)C. 35kV Class (20.2kV Phase-to-Ground)

    Impulse Withstand: A=110kV, B=150kV, C=200kV BIL,1.2 x 50microsecond wave.

    Corona Extinction Voltage: A=13kV, B=22kV, C=31kVminimum, 3pC sensitivity.

    DC Withstand: During installation: A=56kV, B=80kV, C=100kV(Reference AEIC CS5 and CS6, Section L.1.)

    DC Withstand:After installation and in service for the first 5 years: A=18kV, B=25kV, C=31kV for XLPE Insulated Cables and A=45kV, B=64kV, C=80kV for EPR Insulated Cables. (Reference AEIC CS5 and CS6, Section L.2.)

    CURRENT Continuous rating equal to the rating of the cable. Short-Time rating equall to the rating of the cable.

    SHIELD DESIGN Meets IEEE standard 592 for Exposed Semiconducting Shields on

    Premolded High Voltage Cable Joints and Separable InsulatedConnectors.

    Production tests include 100% tests of the premolded joints to assure: Corona Extinction Voltage: A=13kV, B=22kV, C=31kV

    minimum, 3pC sensitivity.

    AC Withstand: A=35kV, B=52kV, C=69kV, 60 Hz, 1 minute.

    Design tests on production joints demonstrate compliance with IEEE 404 including: Corona Extinction Voltage: A=13.0kV, B=21.6kV, C=30.3kV

    minimum, 3pC sensitivity.

    AC Withstand: A=35kV, B=52kV, C=69kV, 60 Hz 1 minute.

    DC Withstand: A=70kV, B=100kV, C=125kV negative polarity, 15 minutes.

    Impulse Withstand (BIL): A=110kV, B=150kV, C=200kV, 10positive and 10 negative, 1.2 x 50 microsecond wave, at conductortemperatures of 20 and 130C, nominal.

    Short-Time Current: magnitude equal to cable.

    Cyclic Aging: 30 days at: A=26.1kV, B=43.2kV, C=60.2kV ACcontinuous, load current for 8 hours per day providing 130conductor temperature. Joints then subjected to: A=35kV, B=52kV,C=69kV for 5 hours followed by: A=53kV, B=78kV, C=104kV for1 hour.

    Load Cycle: Connectors meet thermal and mechanical require-ments of ANSI C119.4, Class A heat cycle, Class 2 partial tension.

    CATALOG 2001 Page 20 ID: 0198

  • DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #

    STYLE 1 A BPART NUMBER inches inches

    15PCJ1FX 10 1/4" 1 3/4"15PCJ1GX 10 1/4" 1 3/4"25PCJ1GX 14 3/8" 2 7/16"

    15/25/35PCJ1HX 14 3/8" 2 7/16"15/25/35PCJ1JX 14 3/8" 2 7/16"15/25/35PCJ1KX 14 3/8" 2 25/32"15/25/35PCJ1LX 14 3/8" 2 25/32"15/25/35PCJ1LMX 14 3/8" 2 25/32"15/25/35PCJ1MX 14 3/8" 2 25/32"15/25/35PCJ1NX 15 3/4" 3 3/16"15/25/35PCJ1PX 15 3/4" 3 3/16"15/25/35PCJ1QX 15 3/4" 3 3/16"

    Description Voltage ELASTIMOLD NotesClass Part Number

    Power Cable 15kV 15PCJ1W1X N1Joint 15kV 15PCJ1W2X N2

    25kV 25PCJ1W1X N1Style 1 25kV 25PCJ1W2X N2

    35kV 35PCJ1W1X N135kV 35PCJ1W2X N2

    Power Cable 15kV 15PCJ2W1X N1Joint 15kV 15PCJ2W2X N2

    25kV 25PCJ2W1X N1Style 2 25kV 25PCJ2W2X N2

    35kV 35PCJ2W1X N135kV 35PCJ2W2X N2

    N1. Kit includes aluminum compression connector suitable for splicing aluminum conductor to aluminum conductor or aluminum conductor to copper conductor.

    N2. Kit includes copper compression connector suitable for splicing copper conductor to copper conductor only.

    CATALOG 2001 Page 21 ID: 0198

    STYLE 2 A BPART NUMBER inches inches

    15PCJ2EX 16 3/8" 2 25/32"15PCJ2FX 16 3/8" 2 25/32"

    15/25PCJ2GX 16 3/8" 2 25/32"15/25/35PCJ2HX 16 3/8" 2 25/32"15/25/35PCJ2JX 16 3/8" 2 25/32"15/25/35PCJ2KX 21" 3 3/4"15/25/35PCJ2LX 21" 3 3/4"15/25/35PCJ2MX 21" 3 3/4"15/25/35PCJ2NX 21" 3 3/4"15/25/35PCJ2PX 21" 3 3/4"15/25/35PCJ2QX 21" 3 3/4"

    DIMENSIONAL DATA

    ORDERING INFORMATIONPCJ Style 1with single-piece housing

    PCJ Style 2with universal housing and separate cable adapters

    that can be varied with the cable application.

    DIMENSION AOVERALL LENGTH

    DIMENSION BOUTSIDE DIA.

    Refer to the W and X tables on pages 32 and 33 for sizing to cable insulation diameter and conductor size.

    For cable shield adapters and jacket seals, see page 28.

    Pow

    er

    Cab

    le

    Join

    t

    Sty

    le

    Insu

    lation

    D

    iam

    eter

    Vol

    tage

    C

    lass

    Con

    duct

    or

    Con

    duct

    or

    Siz

    e C

    ode

    1- Aluminum2- Copper1- Style 1

    2- Style 2

    W SIZING INFORMATION AND SELECTION Use Table W8 for 15PCJ Use Table W9 for 25PCJ Use Table W10 for 35PCJ

    X SIZING INFORMATION AND SELECTION Use Table X7 for 15PCJ, 25PCJ and 35PCJ

    Part numbers that containthe letters W or X are sizesensitive. To complete thepart number, refer to the W or X tables indicated.

  • CABLE TERMINATIONS

    ELASTIMOLD

    ELECTRICAL RATINGSSUMMARYThe following ratings summary is based on IEEE Std. 48 and applies to all the terminations on page 22 thru 25. Elastimoldterminations are designed for use on three-phase systems, either 3-wire or 4-wire and the single-phase laterals of these systems.

    VOLTAGE RATINGS15kV Class 9.5kV Phase-to-Ground110kV BIL 1.2 x 50 microsecond waveAC Withstand:

    50kV 1 min. dry35kV 6 hr. dry45kV 10 sec. wet

    13kV Corona Extinction

    25kV Class16kV Phase-to-Ground150kV BIL 1.2 x 50 microsecond waveAC Withstand:

    65kV 1 min. dry55kV 6 hr. dry60kV 10 sec. wet

    21.5kV Corona Extinction

    35kV Class22kV Phase-to-Ground200kV BIL 1.2 x 50 microsecond waveAC Withstand:

    90kV 1 min. dry75kV 6 hr. dry80kV 10 sec. wet

    30kV Corona Extinction

    MODULAR TERMINATORS

    BRACKETS

    35MSC

    35MTBPB-1 16TB2 1535AFB

    16THGS16THG 35MTGI 35MTG

    STRESS CONE

    35MSCIPCT-1 PCT-2

    SINGLE PIECE TERMINATORS

    CATALOG 2001 Page 22 ID: 0198

    TERMINATIONS

    Elastimold cable terminations are available in single piece or modulardesigns. Terminators allow connectionand transition from shielded, under-ground cable to bare overhead conductors and live-front equipment.Units are designed and rated per IEEEStandard 48 for riser pole, padmount,indoor and outdoor applications.PCT1, PCT2, 16THG and 35MTGterminators provide sufficient creep,strike and weather sealing for class 1outdoor service. PCT1 and PCT2 alsoinclude an integral cable jacket seal.The 35MTGI terminators and 35MSCstress cones are rated for class 2 andclass 3 indoor service respectively.Optional mounting brackets, aerial lugsand equipment connectors are avail-able as required.

  • DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #

    CATALOG 2001 Page 23 ID: 0198

    Illustration Description Voltage ELASTIMOLD Notes(not to scale) Class Part Number

    Single-Piece 15kV PCT1-X-4 N12,14,Terminator Use Table X9 15, 22(Class 1) 25kV PCT2-X-4 N12,14,

    Use Table X9 15, 23

    Housing 15kV PCT1-4 N13, 22only 25kV PCT2-4 N13, 23

    Single-Piece 15/25kV 16THG-WX-4 N2,14Terminator Use Tables W12 and X8 15(Class 1)

    Housing 15/25kV 16THGH-Wonly Use Table W12

    Single-Piece 15/25kV 16THGS-WX N3Terminator Use Tables W12 and X4for solid

    conductor only(Class 1)

    Stress Cone ALL 35MSC-W N17(Class 3) Use Table W11

    w/Grd. Strap ALL 35MSCI-W N17Use Table W11

    Modules ALL 35MG-W N11,16only Use Table W13

    Modular 15kV 35MTG-WX-4-CA N2,11Terminator Use Tables W13 and X3(Class 1) 25kV 35MTG-WX-8-CA N2,5,11

    Use Tables W13 and X335kV 35MTG-WX-10-CA N2,6,11

    Use Tables W13 and X3

    Modular 15kV 35MTGI-W-4 N11Terminator Use Table W13(Class 2) 25kV 35MTGI-W-6 N11w/o Rain Use Table W13

    Cap 35kV 35MTGI-W-8 N7,11Use Table W13

    Rod Contact 15/25kV 0070X N1for PCT Use Table X9

    Rod Contact 15/25kV 16TCA-X N2, 8for 16THG Use Table X8

    Solid Conductor 15/25kV 16CAS-X N3, 9Package Use Table X4

    for 16THGS

    3/4-16 Threaded ALL 35MTGA-WX-1 N2,10,11Rod for MTG Use Tables W13 and X3 18, 25

    1-14 Threaded ALL 35MTGA-WX-2 N2,10,11Rod for MTG Use Tables W13 and X3 19, 25

    Two-Hole Spade ALL 35MTGA-WX-3 N4,10,11for MTG Use Tables W13 and X3 20, 25

    Two-Hole Spade ALL 0100X N1for PCT Use Table X9

    One-Hole Spade ALL 0110X N1for PCT Use Table X9

    Universal Rod ALL 35MTCGA-WX-4 N2,10,11for MTG Use Tables W13 and X3 21, 25

    Aerial Lugs ALL 35AL-A N10, 24for MTG

    Threaded Rod(Two-hole spade

    or bare wire)

    TERMINATIONSN1. Use with PCT1 or PCT2 Terminators.N2. Includes contact rod, ground strap and rain cap.N3. Includes crimp ring, ground strap and rain cap.N4. Includes spade contact, ground strap and rain cap.N5. For KA thru PB sizes use 35MTG-WX-6-CA.N6. For KA thru PB sizes use 35MTG-WX-8-CA.N7. For KA thru PB sizes use 35MTGI-W-6.N8. Use with 16THG Terminators.N9. Use with 16THGS Terminators.

    N10. Use with 35MTG Terminators.N11. Refer to page 24 for detailed ordering instructions.N12. Includes rod contact as standard. Specify suffix -3 in place of -4

    for two-hole spade lug. Specify suffix -5 in place of -4 for one-holespade lug.

    N13. Specify suffix -3 or -5 in place of -4 for two-hole spade lughousing or one- hole spade style housing.

    N14. Use 1X for rod contact for aluminum conductors only.N15. Use 0X for rod contact for aluminum or copper conductors.N16. Available in sizes from GA thru PB.N17. Available in sizes EB thru PB.N18. For conductors from 1/0 thru 350 kcmil.N19. For conductors from 400 kcmil thru 1000 kcmil.N20. For conductors from #2 to 1000 kcmil.N21. For conductors from #6 thru 4/0.N22. Use for insulation dia. range from .640" thru 1.070".N23. Use for insulation dia. range from .830" thru 1.180".N24. Select symbol for A from aerial lug ordering information on page 24.N25. W13 Table provides sizing for rain cap

    X10 Table provides sizing for connectors.

    Refer to the W and X tables on pages 32 and 33 for sizing to cable insulation diameter and conductor size.

    For cable shield adapters and jacket seals, see page 28.

    Part numbers that containthe letters W or X are sizesensitive. To complete thepart number, refer to the W or X tables indicated.

  • ELASTIMOLD

    CABLE TERMINATIONS contd

    ELASTIMOLD CATALOG 2001 Page 24 ID: 0198

    35MTG - - -W X N C A

    QRDERING INSTRUCTIONS FOR MODULAR TERMINATORS

    GA-JB KA-PB15kV 4 425kV 8 635kV 10 8

    Recommended Number of Modules

    Use Table W13, below

    Use Table X3, belowNOTE: Sizes are limited depending

    upon connector style selection. See notes 8 thru 11 on page 25.

    I =IndoorBlank = Outdoor

    Description Available for Symbol NoteConductor

    Sizes3/4"-16 1/0 thru -1 N8

    Threaded 350 kcmilRod1"-14 400 thru -2 N9

    Threaded 1000 kcmilRod

    2-Hole #2 thru -3 N10Spade 1000 kcmil

    Universal #6 thru 4/0 -4 N11Rod

    Type Connector SymbolBare Wire 3/4"-16 -11

    Rod2-Hole Spade 3/4"-16 -12

    RodBare Wire 1"-14 -21

    Rod2-Hole Spade 1"-14 -22

    Rod

    Connector Style Aerial Lugs forThreaded RodConnectors Only

    Cable InsulationTableW13 Diameter in Inches Symbol

    MIN. MAX. for W.775 .885 GA.825 .935 GAB.875 .985 GB.930 1.040 GH.980 1.115 HA

    1.040 1.175 HAB1.095 1.240 HB1.160 1.305 HJ1.220 1.375 JA1.285 1.395 JAB1.355 1.520 JB1.485 1.595 KA1.530 1.640 KAB1.575 1.685 KB1.665 1.785 PA1.755 1.875 PB

    USE FORFOLLOWINGPRODUCTS

    35MTG35MTGI

    Conductor Symbol for XTableX3 SIZE AWG Strand./ Compt./

    or kcmil Compr. Solid.#6 3 #5 3 #4 2 3#3 2 #2 1 2#1 0 11/0 10 02/0 20 103/0 30 204/0 40 30250 250 40300 300 250350 350 300400 400 350450 450 400500 500 450550 550 500600 600 500

    650-700 550 550750 750 600800 800 550900 900 7501000 1000 900

    USE FORFOLLOWINGPRODUCT

    35MTG

  • DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #

    CATALOG 2001 Page 25 ID: 0198

    N1. Use with PCT-1 or PCT-2 Terminators.N2. Fits overall cable O.D. from 1.195" to 1.625".N3. Fits overall cable O.D. from .925" to 1.335".N4. Fits overall cable O.D. from .890" to 1.185".N5. Fits overall cable O.D. from 1.500" to 2.000".N6. Use with 16THG & 16THGS Terminators.N7. Use with MTG, MTG1 & MSC Terminators.N8. For conductors from 1/0 thru 350 kcmil.N9. For conductors from 400 kcmil thru 1000 kcmil.

    N10. For conductors from #2 to 1000 kcmil.N11. For conductors from #6 thru 4/0.N12. Fits overall cable O.D. from .750" to 1.625".

    TERMINATIONS

    Refer to the W and X tables on pages 32 and 33 for sizing to cable insulation diameter and conductor size.

    For cable shield adapters and jacket seals, see page 28.

    Illustration Description Voltage ELASTIMOLD Notes(not to scale) Class Part Number

    PCT ALL PB-1 N1,12Positioning

    Bracket

    16THG Bracket ALL 16TB-2 N6

    Bracket ALL 16TB-3 N6for crossarm

    mounting16THG

    Bracket ALL 16TB-4 N6for riser pole

    mounting16THG

    Bracket ALL 16TB-5 N6for tri-mounting

    16THG

    KELLUMS ALL 35MTB1-A N1,2,6,7GRIP ALL 35MTB1-B N1,3,6,7

    Bracket ALL 35MTB1-C N1,4,6,7ALL 35MTB1-D N1,5,6,7

    KELLUMS ALL 35MTB3-A N1,2,6,7Bracket ALL 35MTB3-B N1,3,6,7

    for crossarm ALL 35MTB3-C N1,4,6,7mounting ALL 35MTB3-D N1,5,6,7Bracket ALL 35MTB4-A N1,2,6,7

    (for riser pole ALL 35MTB4-B N1,3,6,7mounting) ALL 35MTB4-C N1,4,6,7

    ALL 35MTB4-D N1,5,6,7KELLUMS ALL 35MTB5-A N1,2,6,7

    Bracket ALL 35MTB5-B N1,3,6,7for tri-mounting ALL 35MTB5-C N1,4,6,7

    ALL 35MTB5-D N1,5,6,7

    ALUMA FORM ALL 1535AFB-1 N1,6,7Bracket

    ALUMA FORM ALL 1535AFB-3 N1,6,7Bracket

    for Crossarmmounting

    ALUMA FORM ALL 1535AFB-4 N1,6,7Bracket

    for riser-polemounting

    ALUMA FORM ALL 1535AFB-5 N1,6,7Bracket

    for tri-mounting

    Part numbers that containthe letters W or X are sizesensitive. To complete thepart number, refer to the W or X tables indicated.

  • SURGE ARRESTERS

    ELASTIMOLD

    ELECTRICAL RATINGS & PROTECTIVE CHARACTERISTICSPerformance:High Current Short Duration - All MOV Arresters withstand two discharges of 40kA crest.Low Current Long Duration - All MOV Arresters withstand 20 surges

    of 75 amperes/2000 microsecond duration. Duty Cycle Test - All MOV Arresters withstand 22 operations of 5kA crest at 8 x 20 microsecondduration while energized at rated voltage for the initial 20 operations and at maximum continuousoperating voltage (MCOV) for the final two operations.Following each of the preceding tests, MOV Arresters demonstrate thermal recovery at MCOV.

    PROTECTIVE CHARACTERISTICS:

    BUSHINGWELL

    BSA BUSHINGSURGE ARRESTER

    ESA ELBOWSURGE

    ARRESTER

    PSA PARKINGSTAND

    ARRESTER

    LOADBREAKBUSHING INSERT

    LOADBREAKFEED-THRU INSERT

    FEED THRU

    PARKINGSTAND

    CATALOG 2001 Page 26 ID: 0198

    ELASTIMOLD Metal Oxide Varistor (MOV) surge arresters are fully-shielded, fully-submersible and are equipped with IEEE 386 interfaces forconvenient energized connection with other 200 Amp loadbreak compo-nents. Units are compact, allowing installation in existing cabinetry. For application ease, arresters are available in 3 styles: Elbow (ESA), ParkingStand (PSA) and Bushing (BSA). The PSA and BSA arresters permit directconnection eliminating the need for additional accessories.

    Elastimold arresters provide high voltage lightning and switching surge protection of transformers, cable, equipment and other components typi-cally located on underground power distribution systems. Proper place-ment, voltage selection and coordination with riser pole arresters minimizesdamaging surge voltages by improving protective margins.

    Typical applications include installing an arrester at the end of a radial system or at both ends of an open point on a loop system. Additional arresters can be added at strategic locations upstream from the end pointfor optimum protection. Request Form 2068 (Surge Protection Options ForUnderground Distribution) and Form 2069 (Arrester Applications Underground Electrical Systems) for additional application and margin ofprotection information.

    ESA Elbow Arresters are also available with a 200 Amp Deadbreak inter-face for mating with other Deadbreak accessories.

    MCOV Maximum Discharge Voltage (kV crest) F.O.W.Protective(kVrms) Duty Cycle 8x20 microsecond current wave Level (kV crest)Note 1 Rating (kVrms) 1.5kA 3kA 5kA 10kA 20kA Note 2

    15kV 2.55 3 10.5 11.0 11.5 13.0 14.5 13.0CLASS 5.1 6 20.5 21.5 23.0 25.5 30.0 25.5

    8.4 10 30.5 32.5 34.5 38.5 43.5 38.510.2 12 40.0 42.5 45.0 50.0 56.5 50.012.7 15 48.0 51.0 54.0 60.0 68.0 60.015.3 18 56.5 60.0 64.0 71.0 80.5 71.0

    25kV 8.4 10 30.5 32.5 34.5 38.5 43.5 38.5CLASS 10.2 12 40.0 42.5 45.0 50.0 56.5 50.0

    12.7 15 48.0 51.0 54.0 60.0 68.0 60.015.3 18 56.5 60.0 64.0 71.0 80.5 71.017.0 21 65.5 69.5 74.0 82.5 93.0 82.5

    35kV 19.5 24 78.5 83.5 89.0 99.0 112.0 99.0CLASS 22.0 27 87.5 93.0 99.0 110.0 124.5 110.0

    24.4 30 95.5 101.5 108.0 120.0 136.0 120.0

    NOTES:1. MCOV = Maximum Continuous Operating Voltage.2. The front of wave (FOW) protective level is the maximum discharge for a 5kA impulse current wave

    producing a voltage wave cresting in 0.5 microseconds.

    167ESA

    167PSA167BSA

  • DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    System Line-to-Line MCOV (Max. Continuous Voltage kV rms Operating Voltage) kV rms

    Solidly 3-WireNominal Max. Grounded Ungrounded

    Neutral Circuits Circuits

    15kV 2.40 2.54 2.55 2.55Class 4.16 4.40 2.55 5.10

    4.80 5.08 5.10 5.106.90 7.26 5.10 8.408.32 8.80 5.10 8.40

    12.47 13.20 8.40 15.3013.20 13.97 8.40 15.3013.80 14.50 8.40* 15.3013.80 14.50 10.20 15.30

    25kV 6.90 7.26 5.10 8.40Class 8.32 8.80 5.10 8.40

    12.47 13.20 8.40 15.3013.20 13.97 8.40 15.3013.80 14.50 8.40* 15.3013.80 14.50 10.20 15.3020.78 22.00 12.70 20.78 22.00 15.30* 23.00 24.34 15.30 24.94 26.40 15.30 24.94 26.40 17.00* 28.00 29.80 17.00

    35kV 23.00 24.34 22.00Class 34.50 36.51 22.00*

    34.50 36.51 24.40

    CATALOG 2001 Page 27 ID: 0198

    Illustration Description Voltage Elastimold MCOV(not to scale) Class Part Number kVrms

    BSA 15kV 167BSA-3 2.55Bushing 15kV 167BSA-6 5.10

    Surge Arrester 15kV 167BSA-10 8.40(includes 15kV 167BSA-12 10.20assembly 15kV 167BSA-15 12.70

    tool) 15kV 167BSA-18 15.3025kV 273BSA-10 8.4025kV 273BSA-12 10.20

    See Notes 25kV 273BSA-15 12.70N1, 2, 3,4 25kV 273BSA-18 15.30

    25kV 273BSA-21 17.0035kV 375BSA-24 19.5035kV 375BSA-27 22.0035kV 375BSA-30 24.40

    ESA 15kV 167ESA-3 2.55Elbow 15kV 167ESA-6 5.10

    Surge Arrester 15kV 167ESA-10 8.4015kV 167ESA-12 10.2015kV 167ESA-15 12.70

    See Notes 15kV 167ESA-18 15.30N2, 3, 5 25kV 273ESA-10 8.40

    25kV 273ESA-12 10.2025kV 273ESA-15 12.7025kV 273ESA-18 15.3025kV 273ESA-21 17.0035kV 375ESA-24 19.5035kV 375ESA-27 22.0035kV 375ESA-30 24.40

    PSA 15kV 167PSA-3 2.55Parking Stand 15kV 167PSA-6 5.10

    Arrester 15kV 167PSA-10 8.4015kV 167PSA-12 10.2015kV 167PSA-15 12.70

    See Notes 15kV 167PSA-18 15.30N1, 2, 3 25kV 273PSA-10 8.40

    25kV 273PSA-12 10.2025kV 273PSA-15 12.7025kV 273PSA-18 15.3025kV 273PSA-21 17.0035kV 375PSA-24 19.5035kV 375PSA-27 22.0035kV 375PSA-30 24.40

    ARRESTER APPLICATION TABLE

    * Preferred arrester MCOV for this system voltage

    SELECTION CHART

    N1. Elastimold PSA and BSA Arresters are equipped with a fully rated 200Aswitching and fault close loadbreak bushing.

    N2. Elastimold Arresters use high-strength silver epoxy bonded MOV blocksand shunted spring connections for the best circuit connection.

    N3. A 36 inch #4 AWG ground lead provided with each unit.N4. BSA installed by turning internal hex bolt (accessed thru the 200 Amp

    Bushing Interface) with 5/16" hex wrench supplied with each unit.N5. For 15kV and 25kV Class DEADBREAK system Elbow Arresters, use part

    number 156ESA with the appropriate Duty Cycle rating.ORDERING INSTRUCTIONS:

    (1.) Determine the appropriate Maximum Continuous Operating Voltage (MCOV) for your system voltage by using the ELASTIMOLDARRESTER APPLICATION TABLE.

    (2.) Specify the appropriate ELASTIMOLD part number from the selection chart.

  • SHIELD ADAPTERS, GROUNDING KITS AND JACKET SEALS

    CATALOG 2001 Page 28 ID: 0198ELASTIMOLD

    CONCENTRICNEUTRAL

    URD

    JACKETEDCONCENTRIC

    NEUTRALURD

    DRAINWIRE

    SHIELDED

    COPPERTAPE

    SHIELDED

    LEAD JACKETED

    CABLE

    UNISHIELD

    600/200ECS

    600/200ECSG1-2

    600/200ECSG2-2

    600/200ECS3

    NONEREQUIRED

    21MA 20MA 10TL 10TL

    CONDUCTOR

    INSULATION

    EXTRUDED SHIELD

    CONCENTRIC NEUTRAL WIRES

    OUTER JACKET

    CONDUCTOR

    INSULATION

    EXTRUDED SHIELD OR BEDDING TAPE

    DRAIN WIRES

    OUTER JACKET

    CONDUCTOR

    INSULATION

    EXTRUDED SHIELD OR BEDDING TAPE

    COPPER SHIELD

    OUTER JACKET

    CONDUCTOR

    INSULATION

    SEMI-CON TAPE

    LEAD JACKET

    CONDUCTOR

    INSULATION

    CONDUCTIVE JACKET

    DRAIN WIRES

    CONDUCTOR

    INSULATION

    EXTRUDED SHIELD

    CONCENTRIC NEUTRAL WIRES

    CABLESHIELDTYPES

    CABLE ENTRANCE DETAIL

    INSULATIONEPDM RUBBER

    MOLDED SHIELDCONDUCTIVE EPDM RUBBER

    10TL 20 MA 21MA ECS

    CABLE SHIELD ADAPTERSCable 10TL 20MA 21MA

    Insulation Dia. inches inches inches

    min. .495 .575 .575max. 1.755 1.755 1.755

    JACKET SEALSJacket 200ECS 600ECS

    O.D. inches inches

    min. .80 1.28max. 1.50 2.30

    Elastimold elbows, splices and terminators are designed for application onXLP, EPR and other solid dielectric insulated power cables. As shown in the diagram below, a variety of shielding and jacketing methods are available forthese types of cables. In some cases, the use of cable shield adapters,grounding kits and/or jacket seals are required in order to properly installElastimold components. Refer to the diagram below for recommendations, selection and use of adapters, grounding kits and jacket seals.

  • DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #DEADFRONT

    LIVEFRONT

    SEPARABLE CONNECTORS

    FUSED ELBOWS

    CABLE JOINTS

    SURGE ARRESTERS

    200 AMP DEADBREAK

    200 AMP LOADBREAK

    600 SERIES DEADBREAKTERMINATIONS

    5-15kV

    25kV

    35kV

    PART #

    CATALOG 2001 Page 29 ID: 0198

    Illustration Description ELASTIMOLD Suffix Notes(not to scale) Part Number

    Cold Shrinkable 200ECS -S N1,3Jacket Seal

    Cold Shrinkable 600ECS -S N1,4Jacket Seal

    Metallic Tape 20MA-W -0MA N1,2Shield Adapter Use Table W14

    for sizing

    Wire Shield 21MA-W -1MA N1,2Adapter Use Table W14

    for sizing

    Shield 10TL-W -TL N1,2Adapter Use Table W15

    for sizing

    Cold Shrinkable Seal 200ECSG1-2 -SG1 N1,3w/ Copper Rod &Crimp Connector

    Cold Shrinkable Seal 600ECSG1-2 -SG1 N1,4w/ Copper Rod &Crimp Connector

    Cold Shrinkable Seal 200ECSG2-2 -SG2 N1,3w/ Copper Rod &Constant Force

    Spring

    Cold Shrinkable Seal 600ECSG2-2 -SG2 N1,4w/ Copper Rod &Constant Force

    Spring

    Cold Shrinkable Seal 200ECSG3 -SG3 N1,3w/ Copper Braid &

    Constant ForceSpring

    Cold Shrinkable Seal 600ECSG3 -SG3 N1,4w/ Copper Braid &

    Constant ForceSpring

    N1. To order the kits as separate items, use the part numbers shown in thetable. Example: To order a cold shrinkable tube as a separate item, usethe part number 200ECS.To order the kits as components of other items, add the suffix to the endof the part number. Example: To order a cold shrinkable jacket seal as acomponent of an elbow kit, use the part number 166LR-A520-S.

    N2. Only use this suffix with part numbers that designate a W housing size.Sizing the main component will also size the suffix adapter.

    N3. Size range .80" to 1.50" jacket diameters. Maximum installed diameter isapprox. 2".

    N4. Size range 1.28" to 2.30" jacket diameters. Maximum installed diameteris approx. 2.75".

    InsulationTableW15 Inches Symbol

    MIN. MAX. for W.495 .585 EB.525 .635 EF.575 .585 FA.625 .735 FAB.675 .785 FB.725 .835 FG.775 .885 GA .825 .935 GAB.875 .985 GB.930 1.040 GH.980 1.115 HA1.040 1.175 HAB1.095 1.240 HB1.160 1.305 HJ1.220 1.375 JA1.285 1.395 JAB1.355 1.520 JB1.485 1.595 KA1.530 1.640 KAB1.575 1.685 KB1.755 1.875 PB

    USE FOR

    10TL

    InsulationTableW14 Inches Symbol

    MIN. MAX. for W.530 .680 E.640 .820 F.760 .950 G.850 1.050 H.980 1.180 J1.090 1.310 K1.180 1.465 L1.280 1.430 LM1.370 1.630 M1.515 1.780 N

    USE FOR

    20MA21MA

    Part numbers that containthe letters W or X are sizesensitive. To complete thepart number, refer to the W or X tables indicated.

  • How to specify Size-Sensitive Products

    CATALOG 2001 Page 30 ID: 0198ELASTIMOLD

    INSULATION DIAMETER SELECTION GUIDEElastimold Elbows, splices and terminations are designed for application on XLP,EPR and other solid dielectric insulated power cables. These components are con-structed of molded elastomer and rely on an interference fit with the cable insulationdiameter in order to maintain proper dielectric strength, creep path integrity and awater seal. Elastimold components are available in a wide range of sizes in order toaccommodate a variety of cable insulation diameters.Selection of size-sensitive components requires determining the cable insulation diameter. This can be done in several ways:A. Refer to the cable manufacturers spec sheet for dimensions.B. Measure the cable.C. If the cable conforms to AEIC standards with a 175, 220, 260 or 345 mil wall

    thickness, use the table on page 34.After the cable insulation diameter has been determined:1. Locate the W table indicated in the part number selection chart.2. Complete the ordering information by select