Page 1: ELEC300_lecture7_2011_bw

18:26:52 1

Tao LuDept. Electrical and Computer Engineering

University of Victoria10 February 2011

Page 2: ELEC300_lecture7_2011_bw

Midterm 1 available at EOW 321. Midterm 2: Mar. 8, 13:00-14:20??? Pspice is available at ELW B324

Talk to Rob Fichtner, ELW B320, 721-8669, [email protected] you still don’t have card access to that lab.

18:26:53 2

Page 3: ELEC300_lecture7_2011_bw

11.2 Instantaneous and Average Power Instantaneous power is the power at any instant of time

Average Power The average of the instantaneous power over one period.

Under sinusoidal excitation

18:26:53 3

( ) ( ) ( )titvtp =

( ) ( ) ( ) ( )( ) ( ) ( )

( )ivmm

ivmmivmm

imvm

IVP

tIVIVtp

tItitVtv

θθ

θθωθθ

θωθω

−=

+++−=

+=+=

cos21

2cos21cos

21

cos,cos

( )dttpT

PT

∫=0

1

Page 4: ELEC300_lecture7_2011_bw

Phasor representation

When , When ,

A resistive load (R) absorbs power at all times, while a reactive load (L or C) absorbs zero average power.

18:26:53 4

[ ] ( )ivmmIVVIP θθ −== cos21Re

21 *

iv θθ = RIRIIVP mmm22

21

21

21

===

90±=− iv θθ 0=P

Page 5: ELEC300_lecture7_2011_bw

Calculate the instantaneous power and average power absorbed by the passive linear network of Fig. 11.1 if and

18:26:53 5

( ) ( )Vttv 2010cos165 +=

( ) ( )Vtti 6010cos20 +=

Page 6: ELEC300_lecture7_2011_bw

Deternube tge average oiwer generated by each source and the average power absorbed by each passive element in the circuit of Fig. 11.5(a).

18:26:53 6

Page 7: ELEC300_lecture7_2011_bw

For maximum average power transfer, the load impedance ZL must be equal to the complex conjugate of the Thevenin impedance ZTh.

18:26:53 7

Th

Th

ThL

RV

P

ZZ

8

2

max =

= ∗

Page 8: ELEC300_lecture7_2011_bw

In the circuit in Fig. 11.11, find the value of RLthat will absorb the maximum average power. Calculate the power.

18:26:53 8

Page 9: ELEC300_lecture7_2011_bw

The effective value of a period current is the dc current that delivers the same average power to a resistor as the periodic current.

The effective value of a period signal is its root mean square (rms) value.

18:26:53 9

∫=

==T

rms

rmseffrmseff

dtxT

X

VVII

0

21

,

Page 10: ELEC300_lecture7_2011_bw

Find the rms value of the full-wave rectified sine wave in Fig. 11.17. Calculate the average power dissipated in a 6-Ω resistor.

18:26:56 10

Page 11: ELEC300_lecture7_2011_bw

The apparent power (S) is the product of the rms values of voltage and current.

The power factor (pf) is the cosine of the phase difference between voltage and current. It is also the cosine of the angle of the load impedance.

18:26:56 11

( )

( )iv

rmsrmsmm

ivmm

pf

IVIVS

pfSIVP

θθ

θθ

−=

==

•=−=

cos21

cos21

Page 12: ELEC300_lecture7_2011_bw

Determine the power factor of the entire circuit of Fig. 11.18 as seen by the source. Calculate the average power delivered by the source.

18:26:56 12

Page 13: ELEC300_lecture7_2011_bw

Adopting phasor representation

P: real power or average power Q: the reactive power in volt-ampere reactive (VAR)

18:26:56 13

jQPIVZ

VZIS rmsrmsrms

rms +==== ∗2

2

Page 14: ELEC300_lecture7_2011_bw

For a load, V, A. Determine: (a) the complex and apparent powers, (b) the real and reactive powers, and (c) the power factor and the load impedance.

18:26:57 14

85110∠=rmsV 154.0 ∠=rmsI

Page 15: ELEC300_lecture7_2011_bw

The power process of increasing the power factor without altering the voltage or current to the original load is known as power factor correction.

18:26:57 15

Page 16: ELEC300_lecture7_2011_bw

When connected to a 120-V (rms), 60 –Hz power line, a load absorbs 4 kW at a lagging power factor of 0.8. Find the value of capacitance necessary to raise the pf to 0.95.

18:26:57 16

Page 17: ELEC300_lecture7_2011_bw

Example 11.17: A manufacturing industry consumes 200MWh in one month. If the maximum demand is 1600kW, calculate the electricity bill based on the following tow-part rate: Demand charge: $5.00 per month per kW of billing

demand. Energy charge: 8 cents per kWh for the first 50,000

kWh, 5 cents per kWh for the remain energy.

18:26:57 17