ELECTRA-flo G5 TransmitterVersion 1.0X

Thermal Airflow & Temperature Measurement System

www.airmonitor.com • (800) AIRFLOW

Installation, Operation and Maintenance Manual

Page 2: ELECTRA-flo G5 Transmitter...The transmitter and probes or flow station are tagged with matching ESID and/or customer specific identification. Matching the systems as configured by

1050 Hopper Avenue, Santa Rosa, CA • Tel (800) AIRFLOW • www.airmonitor.com [email protected] 1015-1 - 03/17 2

Regarding this Manual

• This manual should be passed on to the end user.• Before use, read this manual thoroughly to comprehend its contents.• The contents of this manual may be changed without prior notice.• All rights reserved. No part of this manual may be reproduced in any form without

Air Monitor’s written permission.• Air Monitor makes no warranty of any kind with regard to this material, including,

but not limited to, implied warranties of merchantability and suitability for a particular purpose.

• All reasonable effort has been made to ensure the accuracy of the contents of this manual. However, if any errors are found, please inform Air Monitor.

• Air Monitor assumes no responsibilities for this product except as stated in the warranty. If the customer or any third party is harmed by the use of this product, Air Monitor assumes no responsibility for any such harm owing to any defects in the product which were not predictable, or for any indirect damages.

Safety Precautions

The following general safety precautions must be observed during all phases of installation, operation, service, and repair of this product. Failure to comply with these precautions or with specific WARNINGS given elsewhere in this manual violates safety standards of design, manufacture, and intended use of the product. Air Monitor Corporation assumes no liability for the customer’s failure to comply with these requirements. If this product is used in a manner not specified in this manual, the protection provided by this product may be impaired.

Page 3: ELECTRA-flo G5 Transmitter...The transmitter and probes or flow station are tagged with matching ESID and/or customer specific identification. Matching the systems as configured by

1050 Hopper Avenue, Santa Rosa, CA • Tel (800) AIRFLOW • www.airmonitor.com [email protected] 1015-1 - 03/17 3

TABLE OF CONTENTS

1.0 GENERAL INFORMATION ...................................................................................4 1.1 PURPOSE OF THIS GUIDE ........................................................................4 1.2 TYPICAL METER INSTALLATION ...........................................................4

2.0 SPECIFICATIONS ..................................................................................................5 2.1 PROBE ASSEMBLY .....................................................................................5 2.2 ELECTRA-flo G5 TRANSMITTER .............................................................5 3.0 INSTALLATION 3.1 INSPECTION ...............................................................................................6 3.2 INSTALLATION LOCATION GUIDELINES ..............................................6 3.3 TRANSMITTER PLACEMENT GUIDELINES ...........................................6 3.4 TRANSMITTER MOUNTING INSTRUCTIONS .......................................6 3.5 POWER AND SIGNAL CONNECTIONS ....................................................7 3.6 CONFIGURATION ......................................................................................9 3.7 START-UP AND OPERATION ...................................................................18 3.8 ANALOG OUTPUT SIGNALS ...................................................................19

4.0 MAINTENANCE / INSPECTIONS .........................................................................19 4.1 MAINTENANCE / INSPECTIONS ..............................................................19 4.2 TROUBLESHOOTING ................................................................................19

5.0 WARRANTY .........................................................................................................20

Page 4: ELECTRA-flo G5 Transmitter...The transmitter and probes or flow station are tagged with matching ESID and/or customer specific identification. Matching the systems as configured by

1050 Hopper Avenue, Santa Rosa, CA • Tel (800) AIRFLOW • www.airmonitor.com [email protected] 1015-1 - 03/17 4

SECTION 1.0: GENERAL INFORMATION

Thank you for purchasing the ELECTRA-flo Thermal Airflow & Temperature Measurement System. As our valued customer, Air Monitor’s commitment to you is to provide fast, reliable service and assistance while continuing to offer you the most accurate and reliable products to meet your flow measurement needs.

1.1: PURPOSE OF THIS MANUAL

This manual provides information regarding the installation, operation and maintenance of your thermal airflow measurement system. This is NOT, nor is it intended to be an electrical or HVAC trade manual.

This manual is the basic reference tool for the ELECTRA-flo G5 Transmitter, including its mains power connection and associated outputs. The complete system consists of the transmitter and associated probe array or stations. Refer to supplemental documents for additional information.

1.2: TYPICAL THERMAL AIRFLOW MEASUREMENT SYSTEM INSTALLATION

Air Monitor’s ELECTRA-flo system accurately measures the average velocity of flowing air by means of thermal dispersion at the sensor locations in the duct. Temperature is also measured via these sensors. The G5 transmitter can receive up to 32 individual flow sensors measuring airflow in a single duct or fan, and it generates the outputs, including network and analog signals, which are conveyed to a local controller or BMS.

Physical installation details for the ELECTRA-flo probe array or flow stations can be found in the ELECTRA-flo Installation Procedures guide.

Typical ELECTRA-flo Installation

Thermal Airflow Transmitter

MIA R TORNO I

ELECTRA-flo

Page 5: ELECTRA-flo G5 Transmitter...The transmitter and probes or flow station are tagged with matching ESID and/or customer specific identification. Matching the systems as configured by

1050 Hopper Avenue, Santa Rosa, CA • Tel (800) AIRFLOW • www.airmonitor.com [email protected] 1015-1 - 03/17 5

SECTION 2.0: SPECIFICATIONS

2.2 ELECTRA-flo G5 TRANSMITTER SERIES

SENSOR DENSITYMaximum number of sensors per transmitter is

32 total sensors per probe array or measurement station

DISPLAYBacklit ¼ VGA Color TFT LCD display, 2.75” X 2.0” Configuration Access:

Field programmable menu driven user interface accessed via four button membrane keypad. Field selectable in U.S. or S.I. units for flow, velocity and temperature.

POWER SUPPLY24 VAC (20-28 VAC) or 24 VDC (20-40 VDC),

isolated and fused with reverse polarity protection16-50 VA, varies based on the quantity of sensors

(1-32) in the probe array or station

OUTPUT SIGNALS PROVIDEDDual analog outputs, field selectable via menu for

0-5 VDC, 0-10 VDC, or 4-20 mADCField adjustable analog output scaling of airflow

velocity and temperatureVelocity Range:

0 to 5,000 FPM in Ducted Applications 0 to 10,000 FPM in Fan Inlet Applications

Temperature Range: -20° to 140° FNetwork Output Communication: BACnet® MS/TP

or MODBUS®

AMBIENT CONDITIONSTemperature Limits: –20° F to 180° F Storage, -20° to

+140° F OperatingHumidity: 0 to 99.9% RH, non-condensing

ENCLOSURENEMA 1 aluminum with hinged cover

Optional: NEMA 4 or NEMA 4X

APPROVALSUL 60730 PENDINGBTLFCC Part 15 Subpart B, Class A Device

2.1 PROBE ASSEMBLY

INDIVIDUAL SENSOR ACCURACYVelocity: ±2% of reading from 0-5000 FPMTemperature: ±0.1° FMulti-point NIST traceable calibration of both temperature and velocity

SENSOR TYPEHermetically sealed, precision matched thermistors

with laser trimmed resistive heating element mounted in flow conditioning aperture.

Max number of sensors per probe: 8Max number of sensors per transmitter: 32

SENSOR SIGNAL PROCESSINGSensor signal processing at the probe with RS-485

communication to the transmitter

MOUNTING CONFIGURATIONSInsertion probe mounting via 4” x 4” aluminum

plate, 1/4” closed cell neoprene gasket and end support stud for probes longer than 18”Optional: Internal mounted probesOptional: Airflow station with factory-mounted probes in a 14 gauge (minimum) galvanized sheet metal casing, available with and without honeycomb airflow straightening cell

Fan inlet mounting with adjustable stainless steel brackets

MATERIALS OF CONSTRUCTION 1.125” diameter anodized aluminum probe with

aluminum probe connection boxOptional: 316 stainless steel probe with 316 stainless steel or polycarbonate probe connection box

ELECTRICAL CONNECTIONSProbe-to-probe connection via plenum rated cable

with mini-DIN Snap & Lock connector for signal and power

Probe-to-transmitter connection via a single plenum rated cable with mini-DIN Snap & Lock connectorOptional: Conduit connection capability between

individual probe-to-probe cables and probe-to-transmitter cable

Cable Length: 10’ typical, up to 100’ optional (cables can be field terminated to length)

PROBE SIZE RANGE6” to 144” dimension length

Page 6: ELECTRA-flo G5 Transmitter...The transmitter and probes or flow station are tagged with matching ESID and/or customer specific identification. Matching the systems as configured by

1050 Hopper Avenue, Santa Rosa, CA • Tel (800) AIRFLOW • www.airmonitor.com [email protected] 1015-1 - 03/17 6

SECTION 3.0: INSTALLATION

3.1 INSPECTION

Carefully remove the ELECTRA-flo probe(s) or station and transmitter from the shipping container and inspect for any damage.

IMPORTANT: All ELECTRA-flo G5 transmitters are factory configured with the application specific duct size and flow rate information. The transmitter and probes or flow station are tagged with matching ESID and/or customer specific identification. Matching the systems as configured by the factory will reduce the installation and start-up labor required. Review the Factory Set-Up Information Sheet provided separately and verify that the W.O. # and serial # match those on the ELECTRA-flo system. Verify that the configuration recorded on the Factory Set-Up Information Sheet is correct for your application. If any damage has occurred in transit or the factory set-up configuration is incorrect for your application, please contact Air Monitor’s Customer Service Department at 1-800-AIRFLOW for assistance.

3.2 INSTALLATION LOCATION GUIDELINES

• The standard version of the ELECTRA-flo G5 transmitter and probe connection heads have a NEMA 1 enclosure rating suitable for clean and dry indoor locations. For additional protection, an enclosure with an adequate NEMA rating may be required. Please contact your Air Monitor representative for enclosure options.

• The ambient temperature of the selected mounting location must be between -20°F and 140°F. Consideration should be given to units exposed to direct sunlight.

• The selected mounting location should be rigid and free of vibration.

3.3 TRANSMITTER PLACEMENT GUIDELINES

The transmitter must be located so that the probe-to-transmitter cable from the probe array or station will reach the mini-DIN receptacle in the bottom of the transmitter. Standard probe-to-transmitter cable length is 10’ with optional 25’, 50’ and 100’ cables available. Terminal connections inside each probe connection box allow for custom sizing of the cable lengths for a clean installation. Do not cut off the mini-DIN connectors.

3.4 TRANSMITTER MOUNTING INSTRUCTIONS

For mounting of flow probes and stations, please reference the appropriate ELECTRA-flo Installation Procedures Guide.

This section may be skipped if the unit is an ELECTRA-flo/CM or ELECTRA-flo/M, and the transmitter was ordered factory mounted to the station.

Page 7: ELECTRA-flo G5 Transmitter...The transmitter and probes or flow station are tagged with matching ESID and/or customer specific identification. Matching the systems as configured by

1050 Hopper Avenue, Santa Rosa, CA • Tel (800) AIRFLOW • www.airmonitor.com [email protected] 1015-1 - 03/17 7

• Tools Required: Electric drill; #25 (0.1495”) drill bit; screwdriver or nut driver (as required for customer supplied mounting screws); and four #8-32 self-tapping machine screws.

• The ELECTRA-flo G5 transmitter can be mounted in any position provided it is secured using all four mounting holes.

• Reasonable consideration should be given to clearances for electrical connections.• Once a suitable location is found, use the transmitter as a template to mark the

centers of the four mounting holes.• Drill four pilot holes at the marked locations. With the unit in position, install the

four #8-32 screws.

3.5 POWER and SIGNAL CONNECTIONS

NOTE: The ELECTRA-flo G5 transmitter terminal connections for power and signal wire are labeled on the board for installation convenience. Power wiring is located at terminal strip J2. Signal wiring is located at terminal strip J1.

The REMOVABLE* terminal strips for power and signal are located in the lower portion of the transmitter and are accessible by opening the hinged cover. (See figure on next page for the exact location of the terminal strips.) Two conduit openings are provided in the bottom of the transmitter enclosure; one for power and one for signal wiring.

Recommended wire gauge (14 AWG is the maximum wire gauge - no more than two wires recommended per terminal):

Power wire = 14 AWG to 18 AWGSignal wire = 14 AWG to 22 AWG

* To aid in the wiring of both power and signal wires, J1 and J2 are removable by pulling the terminal strip straight up and off the circuit board. Once wiring has been completed, replace the terminal strip by aligning it with the receptacle and inserting firmly.

Page 8: ELECTRA-flo G5 Transmitter...The transmitter and probes or flow station are tagged with matching ESID and/or customer specific identification. Matching the systems as configured by

1050 Hopper Avenue, Santa Rosa, CA • Tel (800) AIRFLOW • www.airmonitor.com [email protected] 1015-1 - 03/17 8

WARNING: The ELECTRA-flo G5 transmitter is a low voltage device (24V AC/DC). Connecting the transmitter to high voltage power (e.g. 110 VAC) may cause damage and will void the warranty.

Power Connections: Terminal J2, pin 1 for Line, pin 2 for Neutral and pin 3 for Ground. See figure below for details. The ELECTRA-flo G5 can be powered by either 24VAC providing 20-28VAC or 24VDC providing 20-40VDC.

CAUTION: The earth ground is required on all ELECTRA-flo G5 transmitter installations. Omitting the connection to earth ground could result in poor performance and may void the warranty.

Analog Outputs: Terminal J1; AO1 pins 1 and 2; AO2 pins 3 and 4. Pins 2 and 4 are for the common wire of the respective output. See figure below for details.

Network Connections: Terminal J1; BACnet, pins 5 through 8. A is for the positive signal wire, B for the negative, G for the ground, SH for the shield. See figure below for details.

POWERLINE NEUTRAL GROUND

ANALOG OUTPUTAO1 AO2+ - + -

NETWORK CONNECTIONS

A B GND SHLD

J2J1

Page 9: ELECTRA-flo G5 Transmitter...The transmitter and probes or flow station are tagged with matching ESID and/or customer specific identification. Matching the systems as configured by

1050 Hopper Avenue, Santa Rosa, CA • Tel (800) AIRFLOW • www.airmonitor.com [email protected] 1015-1 - 03/17 9

3.6 CONFIGURATION

All device configuration is done using the four button membrane keypad on the transmitter cover. Individual key functions depend on specific menu selection. The basic key functions include:

ENT: Enters menu item from main or service menu; moves cursor to next item below when in submenuESC: Exits current page or submenu itemUP Arrow: Moves cursor “up” through main and service menu; changes character in submenu itemsDOWN Arrow: Moves cursor “down” through main and service menu; changes character in submenu items

MAIN MENU OR SERVICE MENU: ENT opens the highlighted submenu. UP and DOWN move the selection cursor between submenus.

Submenu: ENT moves selection cursor to the next item. UP and DOWN change state of item or change characters in writable fields.

MAIN MENU

MAIN MENU SELECTION DESCRIPTIONDensity Compensation Select density compensation type for flow output (Actual or Standard CFM)Select System of Units Select system of units (US or SI)Flow Configuration Select and configure flow and application parameter (ducted or fan inlet, duct size,

fan inlet diameter, etc.)Display Configuration Select parameters of display screenAnalog Output Configuration Configure analog output type, value and averaging filterDisplay Averaging Filter Configure display averaging filterZero Lockdown Adjust zero lockdown (below a FPM set point, drives display and output to zero)Alarm/Alert Configuration Configure alarm type, upper and lower limitsNetwork Configuration Configure network type, baud rate and address informationField Characterization For information on field characterization, please see section 3.6.1 below

SERVICE MENU SELECTION DESCRIPTIONPassword Configuration Enable/disable and change passwordTotal System Scan Displays sensor enabled/disabled statusSensor Control Enable or disable system sensorsSensor Data Scan Displays individual sensor dataSensor Alert Scan Displays alert codes for each sensor Custom ID Configure ID (tag) of unit (also device name displayed in BACnet)Restore Factory Setting Restores display settings to original factory setupProduct Information Displays product information (Serial number, Work Order #, etc.)

Page 10: ELECTRA-flo G5 Transmitter...The transmitter and probes or flow station are tagged with matching ESID and/or customer specific identification. Matching the systems as configured by

1050 Hopper Avenue, Santa Rosa, CA • Tel (800) AIRFLOW • www.airmonitor.com [email protected] 1015-1 - 03/17 10

Density Compensation - Density compensation can be selected to be actual flow or corrected to standard conditions. Default factory setting is for actual conditions. The ELECTRA-flo G5 also allows for inputting the site elevation, which will add density compensation for average atmospheric pressure based upon elevation above sea level.

Select System of Units - US or SI units can be selected. US units will display in CFM and degrees Fahrenheit. SI units will display in L/S and degrees Celsius.

NOTE: When changing between US and SI units, the flow configuration information will need to be converted and updated. This is not done by the transmitter. The user must convert and input.

Flow Configuration - The flow configuration menu provides access to modify the application specific parameters.

NOTE: All transmitters are factory configured for the intended application – Changes to the factory configuration should not be required. A Factory Set-Up Sheet is provided with each transmitter and provides the details for all factory configured parameters.

Measurement type indicates whether the probes are installed in a ducted or a fan inlet application. Ducted applications can be rectangular, circular or flat oval. For fan inlet applications, the transmitter can be used with single, double fan inlets or multiple inlet (same size) fan walls. One transmitter accepts up to 32 sensors; typically, there are two sensors per fan inlet, optional construction uses one sensor per inlet (for fan walls).

Ducted: Select the proper duct shape

(Rectangular, Flat Oval or Circular). Enter the duct dimensions (inches or millimeters). Area (cross-sectional duct area) is automatically calculated. Enter the Max Flow (maximum airflow) in CFM or L/s.

Fan Inlet: Select the number of fan inlets being measured (max = 32) Shape is automatically set to Circular. Enter the diameter of the fan inlet(s). Cross-sectional Area is automatically calculated. Enter the Max Flow (maximum airflow) in CFM

Flow Configuration

ENT - Accept ESC - Leave UP/DN - Change

Measurement Type: Ducted

Rectangular

6.0

30.0

1.25

Shape

Height (In):

Width (In):

Area (ft2):

2000.0 Mass Flow (CFM):

Flow Configuration

ENT - Accept ESC - Leave UP/DN - Change

Measurement Type: Fan Inlet

Circular

6.0

1.25

Fan Inlets:

Shape:

Diameter:

Area (ft2):

2000.0 Max Flow (CFM):

Page 11: ELECTRA-flo G5 Transmitter...The transmitter and probes or flow station are tagged with matching ESID and/or customer specific identification. Matching the systems as configured by

1050 Hopper Avenue, Santa Rosa, CA • Tel (800) AIRFLOW • www.airmonitor.com [email protected] 1015-1 - 03/17 11

Display Configuration

This screen allows the user to set parameters on various lines of the display. There are four display lines on the ELECTRA-flo G5. Line 1 - Flow (typical), Velocity or Temperature. Line 2 - Velocity, Flow or None. Line 3 - Temperature, Flow or None. Line 4 - Custom ID or None. This field is settable over BACnet or through the Service Menu. It is typically used to describe the transmitter location in the building. Brightness - Allows the user to set the brightness of the display in real time. Inactivity Timeout - The time period which holds the display in menu mode. When the timer expires, the display is returned to the main display screen showing the process values.

Analog Output Configuration

The ELECTRA-flo G-5 transmitter is equipped with dual analog outputs. The Analog Output Configuration menu configures the analog output type, parameter and filter.

Output Type: 4-20 mADC, 0-5 VDC or 0-10 VDC Output 1 and 2: Flow, Velocity or TemperatureThe Filter has a minimum setting of 0 to a maximum setting of 10. To disable the Filter, select Off.

Display Average Filter

The Display Averaging Filter filters the data shown on the display. It affects all elements of the display. The Filter has 1-10 settings - 1 is the lightest filter, and 10 represents the heaviest filter. It also has an ‘Off’ setting.

Zero Lockdown

Zero Lockdown will drive the displayed flow and velocity, as well as the associated outputs to zero when the velocity is below the set point. As very low air velocities tend to be noisy and unstable, it may be best for control purposes to raise the zero lockdown velocity to an appropriate threshold above that which the velocity is steady and reliable.

Display Configuration

ENT - Accept ESC - Del/Leave UP/DN - Change

Line 1: Flow

Velocity

Temperature

ID

100%

60 min

Line 2:

Line 3:

Line 4:

Brightness:

Inactivity Timeout:

Display Averaging Filter

ENT - Accept ESC - Del/Leave UP/DN - Change

Filter: 4

Analog Output Configuration

ENT - Accept ESC - Leave UP/DN - Change

Output Type: 4-20 mA

Flow

Temperature

4

Output 1:

Output 2:

Filter:

Zero Lockdown

ENT - Accept ESC - Leave UP/DN - Change

Lockdown ON

30 Velocity (FPM):

Page 12: ELECTRA-flo G5 Transmitter...The transmitter and probes or flow station are tagged with matching ESID and/or customer specific identification. Matching the systems as configured by

1050 Hopper Avenue, Santa Rosa, CA • Tel (800) AIRFLOW • www.airmonitor.com [email protected] 1015-1 - 03/17 12

Alarm/Alert Configuration

The Alarm/Alert Configuration menu provides access to select and configure the transmitter alarm and alerts. Alarm type can be either flow or temperature with Upper and Lower limits. The transmitter alarm controls an onboard relay (see the wiring diagram for Normally Open and Normally Closed configurations). Alerts are messages possibly indicating issues with sensors or the transmitter.

Alarm Operation: If the process value (Type) exceeds the Upper or Lower Limit, the relay will change state from the default of NO or NC and the Type will change to red. When the process value recovers to be within the Upper and Lower Limits, the relay will return to the default state and the Type will return to black. The Limits Units are shown in parentheses. These units are controlled by the System of Units and the Units of Measure. If the units are US and the flow is CFH, CFH will be the units used in Limits.

Alert Operation: Enable Reg. Alerts will turn ON / OFF Enable Global Alerts will turn ON / OFF

Network Configuration

Type is BACnet® MS/TP Select appropriate Baud Rate, address, ID and Max Masters.

BACnet MS/TP

BACnet MS/TP serial interface connections are connected at the J2 terminals labeled “BACnet: D+, D-, G, and SH”. The positive RS-485 connection is made to “D+”, the negative connection is made to “D-”, the common ground connection for a 3-wire network is made to “G”, and the shield drain can be connected to “SH”.

WARNING: Do not connect shield drains to the “G” terminal.

Transceiver: 2-wire, half-duplexBaud Rate(s): 9600, 19200, 38400, 56700, 76800, 115200 (Default: 38400) unless

specified by the end userMS/TP MAC Address (“Address” in menu) range: 1 – 255. Starts at 1, incremented

for each transmitter in the system, unless specified by the end userBACnet Device ID (“ID” in menu) range: 0 – 4,194,303. Same as the Device Address,

unless specified by the end userMax Masters: 1 – 127 (Default: 127) unless specified by the end userTermination: 120 Ohms or none (Default: None)Biasing: 549 Ohms or none (Default: None)Flow control: None

Alarm/Alert Configuration

ENT - Accept ESC - Leave UP/DN - Change

Type: Flow

750

100

OFF

ON

Upper Limit (CFM):

Lower Limit (CFM):

Enable Reg. Alerts:

Enable Global Alerts:

Network Configuration

ENT - Accept ESC - Leave UP/DN - Change

Type: BACnet

38400

3

5

127

Baud Rate:

Address:

ID:

Max Masters:

Page 13: ELECTRA-flo G5 Transmitter...The transmitter and probes or flow station are tagged with matching ESID and/or customer specific identification. Matching the systems as configured by

1050 Hopper Avenue, Santa Rosa, CA • Tel (800) AIRFLOW • www.airmonitor.com [email protected] 1015-1 - 03/17 13

The Custom ID field provides the Device Description property over BACnet and on the display. To change the Device Description, either go to the Service Menu - > Custom ID and modify the field or do this remotely over BACnet.

BACnet OBJECT TYPES

BACnet Object Type and number of Objects implemented:

Device 1Analog Input - Reports the average temperature or average flow. Also, reports

individual sensor velocity or sensor temperature. See below for more details.

PROTOCOL IMPLEMENTATION STATEMENT

BACnet Protocol Revision: 9Device Profile (Annex L): BACnet Application Specific Controller (B-ASC)MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 56700, 76800, 115200Device Address Binding: NoBBMD support registration by Foreign Devices: NoCharacter Set Supported: ANSI X3.4

BACnet Interoperability Building Blocks Supported (Annex K):Data Sharing – Read Property-B (DS-RP-B)Data Sharing – Read Property Multiple-B (DS-RPM-B)Data Sharing – Write Property-B (DS-WP-B)Device Management – Dynamic Device Binding-B (DM-DDB-B)Device Management – Dynamic Object Binding-B (DM-DOB-B)Device Management – Device Communication Control-B (DM-DCC-B)Device Management – Reinitialize Device-B (DM-RD-B)

Page 14: ELECTRA-flo G5 Transmitter...The transmitter and probes or flow station are tagged with matching ESID and/or customer specific identification. Matching the systems as configured by

1050 Hopper Avenue, Santa Rosa, CA • Tel (800) AIRFLOW • www.airmonitor.com [email protected] 1015-1 - 03/17 14

STANDARD OBJECT TYPES SUPPORTED

Device Object

Property Default Value Read-Only or Writeable

Comment

Object Identifier 1 Writeable 0 – 4,194,303Object Name ELECTRA-flo Writeable Alpha-numeric; 16 char limit.

Linked to “Custom ID” setting in the Service Menu.Also displays on the bottom of the LCD display on transmitter.

Object Type Device Read-onlySystem Status Operational Read-onlyVendor Name Ari Monitor Corporation Read-onlyModel Name ELECTRA-flo Read-onlyLocation Default Location Read-onlyDescription Thermal Read-onlyProtocol Version 1 Read-onlyProtocol Revision 9 Read-onlyServices Supported readProperty,

readPropertyMultiple,writeProperty,deviceCommunicationControl,reinitilizeDevide, who-Has,who-is

Read-only

Object Types Supported

Analog-input, Device Read-only

Object List Varies: (device, 1), (analog input, 0 - X) where X = 1 + (No. of sensors *2)

Read-only

Max ADPU Length 128 Read-onlySegmentation Supported

No Segmentation Read-only

APDU Time-out 3000 Read-only# of APDU Retries 3 Read-onlyMax Master 127 WriteableDevice Address Binding

{} Read-only

Database Revision 3 Read-only

Page 15: ELECTRA-flo G5 Transmitter...The transmitter and probes or flow station are tagged with matching ESID and/or customer specific identification. Matching the systems as configured by

1050 Hopper Avenue, Santa Rosa, CA • Tel (800) AIRFLOW • www.airmonitor.com [email protected] 1015-1 - 03/17 15

Analog Inputs

Property Default Value Read-only or WriteableObject Identifier Analog Input-0 to Analog Input-X1 Read-onlyObject Name Various Read-onlyObject Type Analog-input Read-onlyPresent Value REAL Read-onlyStatus Flags F2, F, F, F3 Read-onlyEvent State Normal Read-onlyOut of Service FALSE Read-onlyDescription Various Read-onlyUnits Various Read-only

The Air Monitor BACnet stack supports the optional property “DESCRIPTION”. This is used to indicate the type of information in the object. For example, for an ELECTRA-flo system, the description will indicate as “Avg Flow” for average flow, or “Avg Temp” for average temperature. If the object belongs to a sensor in the system, it will be indicated as “SensorN Temp” or “SensorN Flow”, where N is the sensor address. The amount of AI objects is determined by the total number of sensors in the system x 2 with an additional 2 AI objects for system average flow and system average temperature. For example, an ELECTRA-flo system with 8 sensors will have a total of 18 AI objects.

Usage of the Status Field

• Each object supports status bits IN_ALARM, FAULT, and OUT_OF_SERVICE.• The OOS property indicates the physical input to the object is not in service. This

will be set by the transmitter if someone intentionally removes the sensor from the network. If the transmitter determines there is a problem with any sensor in question, the OOS bit is set along with the FAULT bit. If the OOS property is set, data from the physical device will not be used in any calculation.

• IN_ALARM is set for values which exceed the predetermined values set in the transmitter memory. This field only affects the Avg Temp and Avg Flow Analog Input objects

BACnet® Engineering Units for Analog Inputs (Defaults)Flow Rates: Cubic feet per minute, Liters per minuteTemperatures: Degrees Fahrenheit, Degrees Celsius

Analog Input ObjectsObject Identifier FunctionAnalog Input 1 Average Flow RateAnalog Input 2 Average TemperatureAnalog Input (2 + X) Sensor X Flow RateAnalog Input (3 + X) Sensor X Temperature

Page 16: ELECTRA-flo G5 Transmitter...The transmitter and probes or flow station are tagged with matching ESID and/or customer specific identification. Matching the systems as configured by

1050 Hopper Avenue, Santa Rosa, CA • Tel (800) AIRFLOW • www.airmonitor.com [email protected] 1015-1 - 03/17 16

Field Characterization

Field characterization (K-factoring) of a flow element is the adjustment of the flow measurement system to match a known reference measurement, (for our reference - most commonly airflow traverse testing.) Field characterization is typically done when there is insufficient straight duct run or another issue that creates questionable output from the installed measurement system.

A Field Characterization can be developed from one, two or three references flow rates – more could be used, but are not necessary. One traverse test is required for each flow rate. It is recommended that a minimum of a low and a high flow rate are used to determine a Field Characterization. If there is little to no variance in the normal flow rate, it is feasible to use a Field Characterization developed from a single flow rate test. If a high and low flow rate test are performed and it is found that these readings are substantially different, then a medium flow rate should be considered to ensure a more accurate Field Characterization. For any questions or concerns regarding Field Characterization implementation, please contact Air Monitor.

Field Characterization: On enables the Field Characterization and the selection of Calculate or Manual. The Calculate selection will display the on-board calculator that will determine the K-factor (device and reference data must be in-hand and ready to input). Manual displays the Exponent and Gain value forms for inputting externally determined Exponent and Gain values.

Calculate

Number of Points is the number of flow reference points. Each point is one reference flow rate (determined by traverse testing or other) and the associated ELECTRA-flo system flow rate. The traverse testing flow rate for these reference points is performed before entering this screen and is written down with the associated ELECTRA-flo point (flow rate). For most applications, a minimum of two points (low and high flow rates) are recommended for an accurate Field Characterization. Three points may be required.

Electra Point 1 and Reference Point 1 will be the flow rates for the first test, Points 2 for the second test and Points 3 for the third test. Best practice will be to go from the lowest to highest flow rates when inputting this data. Once all data has been entered and the ENT button is pushed for the final Reference Point, the Calculator will display the calculated gain and exponent values.

NOTE: Whenever a system is being retested in order to determine a new Field Characterization (K-factor), the existing Field Characterization should be turned off prior to testing.

Field Characterization

ENT - Accept ESC - Leave UP/DN - Change

Calculate

On

Manual

Characterization Calculator

ENT - Accept ESC - Leave UP/DN - Change

Number of Points: 1

300.0

400.0

Electra Point 1:

Electra Point 2:

Electra Point 3:

Reference Point 1:

Reference Point 2:

Reference Point 3:

Page 17: ELECTRA-flo G5 Transmitter...The transmitter and probes or flow station are tagged with matching ESID and/or customer specific identification. Matching the systems as configured by

1050 Hopper Avenue, Santa Rosa, CA • Tel (800) AIRFLOW • www.airmonitor.com [email protected] 1015-1 - 03/17 17

Manual

Selecting Manual will allow inputting of externally determined Gain (K) and Exponent (E) values, where:

Flow (corrected) = K x Flow (uncorrected) ^ E

Note: A Gain (K) only Field Characterization (K-factor) can be achieved with an exponent (E) value = 1.0.

SERVICE MENU

Total System Scan

Displays the current status of all of the system sensors, thus allowing the user to quickly verify all is operating properly. Expected (white) and Enabled (green) sensor values should be the same unless sensors have been intentionally Disabled (red). See below for sensor control. If Missing (yellow) is at a value other than zero, the transmitter is not communicating with the associated node.

Sensor Control / Sensor Data Scan / Sensor Alert Scan

Sensor Control:An enabled sensor will report measurement data to the ELECTRA-flo G5 transmitter. This is the default condition after initially powering the system. A disabled sensor will not report measurement data to the ELECTRA-flo G5 transmitter. Disabled sensors may have a malfunction that causes this condition. It may also be desirable to intentionally disable a sensor for troubleshooting purposes. A known bad or suspect sensor can be disabled to remove it from the flow and temperature averages until it can be evaluated and/or repaired if necessary.

Sensor Data Scan:Displays sensor number (Sen), power input to sensors (PWM), temperature difference between flow and temperature sensors (DELTAt), velocity (FPM), flow temperature sensor (FLOWt) and the reference temperature sensor (REFt).

This data display screen can be used to further evaluate and troubleshoot the system performance and the application characteristics; e.g., the individual sensor velocities and temperatures will provide comprehensive data regarding the flow profile measured.

Total System Scan

ESC - Leave

Expected

Missing

Enabled

Disabled 00

22

1 2 3 4 5 6 7 8

9 10 11 12 13 14 15 16

17 18 19 20 21 22 23 24

25 26 27 28 29 32 31 32

Sensor Control

ENT - Toggle ESC - Leave UP/DN - Select

Sensor 2: Enabled

Sensor 1: Disabled

Sensor Data Scan

ESC - Leave UP/DN - Page Scroll

Sen PWM DELTAt FPM FLOWt REFt

1 8980 31.3 885.0 104.9 73.6

2 6813 35.0 382.0 108.2 73.2

3 0 0.0 0.0 0.0 0.0

4 0 0.0 0.0 0.0 0.0

5 0 0.0 0.0 0.0 0.0

6 0 0.0 0.0 0.0 0.0

7 0 0.0 0.0 0.0 0.0

8 0 0.0 0.0 0.0 0.0

9 0 0.0 0.0 0.0 0.0

10 0 0.0 0.0 0.0 0.0

Page 18: ELECTRA-flo G5 Transmitter...The transmitter and probes or flow station are tagged with matching ESID and/or customer specific identification. Matching the systems as configured by

1050 Hopper Avenue, Santa Rosa, CA • Tel (800) AIRFLOW • www.airmonitor.com [email protected] 1015-1 - 03/17 18

Sensor Alert Scan:Displays alert codes for expected sensors. Sensors operating properly will display NoAlert.

Other Alert Codes

Alert Code Type Description Corrective ActionMissing ALERT Transmitter cannot communicate with Sensor Power cycle system and recheck.SensAOORorSensBOOR

ALERT Sensor fault Replace sensor. Contact Air Monitor.

DeltaOOR ALERT Sensor Delta Temperature out of range Contact Air Monitor.TempOOR RANGE Temperature measurement out of range

(-20 to 140 ³F)Verify application temperature is not outside -20 to 140 ³F. If ELECTRA-flo G5 appears to be reporting incorrectly, contact Air Monitor.

Disabled ALERT Sensor resets abnormally Power cycle system and recheck.VelOOR RANGE Average velocity exceeds 5000 FPM for

ducted and 10,000 FPM for Fan InletVerify factory set-up information is correct. If application velocity exceeds 5000 FPM, contact Air Monitor.

3.7 START-UP / OPERATION

After power and signal wiring has been verified in accordance with section 3.5, activate the external 24 VAC / 24 VDC power source.

Sensor Alert Scan

ESC - Leave UP/DN - Scroll

Sensor 1: DisabledSENSOR ALERT CODE FREQ

1 Disabled 41

2 NoAlLert

1. Press the power button located on the bottom left corner of the front cover to turn the system ON.

2. The display will show a loading bar. After reaching 100%, the display will indicate which sensors have been discovered for approximately 2 seconds. Then the normal operating screen will be displayed.

ELECTRAflo

Total Flow

520 ACFM

417.1 AFPM Velocity 72.71 F Temperature

The default normal operating screen will display Total Flow on the first process line, Velocity (average of all enabled sensors) on the second process line and Temperature (average of all enabled sensors) on the third process line. Application tagging information is at the bottom of the screen and is customer configurable.

Page 19: ELECTRA-flo G5 Transmitter...The transmitter and probes or flow station are tagged with matching ESID and/or customer specific identification. Matching the systems as configured by

1050 Hopper Avenue, Santa Rosa, CA • Tel (800) AIRFLOW • www.airmonitor.com [email protected] 1015-1 - 03/17 19

Transmitter communicating normally on BACnet network

Send/Receive arrows flashing indicates the sensor(s) and transmitter are communicating normally

Transmitter processor normal

Field Characterization has been turned on

3.8 ANALOG OUTPUT SIGNALS

Airflow: Available on connector J1, terminals AO1+ and AO1- or AO2+ and AO2-. The full scale output is equal to Max flow as inputted into the ELECTRA-flo G5 transmitter on the Flow Configuration submenu.

Temperature: Available on connector J1, terminals AO1+ and AO1- or AO2+ and AO2-. The temperature analog output has a fixed scale of -20º F to 140º F.

SECTION 4.0: MAINTENANCE / INSPECTIONS / TROUBLESHOOTING

4.1 MAINTENANCE / INSPECTIONS

The ELECTRA-flo system has been designed to operate in most HVAC applications without the need for periodic maintenance or calibration. In some applications, it may be necessary to perform a visual inspection of the probe and sensors, and if necessary clean them using a soft, small brush and/or compressed air to remove any accumulated particulate or debris.

4.2 TROUBLESHOOTING

The ELECTRA-flo system is intended to provide long-term, trouble-free operation. In the event there is an issue with the ELECTRA-flo measurement system, or the BMS or the controller ceases to receive valid airflow and/or temperature signals, make certain the following have been checked and confirmed:

• The power wiring is securely connected to the proper terminals and is providing the intended 24V AC/DC power.

• The signal wiring is securely connected to the proper terminals.• The probe-to-probe and probe-to-transmitter cables and connections are properly

connected and secure.• Power cycles the transmitter.

If after following the above troubleshooting steps, the ELECTRA-flo system continues to operate improperly, contact Air Monitor for technical assistance.

The following icons will always be displayed at the top of the normal operating screen. Press ENT to enter menu screens. Follow instructions in section 3.6 to navigate.

Page 20: ELECTRA-flo G5 Transmitter...The transmitter and probes or flow station are tagged with matching ESID and/or customer specific identification. Matching the systems as configured by

1050 Hopper Avenue, Santa Rosa, CA • Tel (800) AIRFLOW • www.airmonitor.com [email protected] 1015-1 - 03/17 20

SECTION 5.0: WARRANTY INFORMATION

Air Monitor Corporation (hereinafter referred to as “Seller”) warrants that at the time of shipment, products sold pursuant to this contract will be free from defects in materials and workmanship and will conform to the specifications furnished or approved in writing by Seller. No warranty is given that delivered products will conform to catalog sheets, data sheets, and the like, which are subject to change without notice.

Seller will repair or replace, at its option, any product listed under this warranty which is returned freight prepaid to Seller within three (3) years after start-up or thirty-nine (39) months after shipment that upon test and examination, proves defective within the terms of this warranty. The warranty period for the ELECTRA-flo system repaired or replaced shall be for the time remaining on the warranty period of the original components. Purchaser shall notify Seller in writing of such defect within sixty (60) days of discovery of the defect.

This warranty does not extend to any product sold by Seller which has been the subject of misuse, neglect, accident, damage or malfunction caused by interconnection with equipment manufactured by others, improper installation or storage, or used in violation of instructions furnished by Seller, nor does it extend to any product which has been repaired or altered by persons not expressly approved by Seller. Nor does Seller warrant equipment against normal deterioration due to environment; nor items such as lamps, glass, and similar items subject to wear or burnout through usage. Adjustments for items or equipment not manufactured by Seller shall be made to the extent of any warranty of the manufacturer or supplier thereof.

Seller shall not be liable for any special or consequential damages or for loss of damage, directly or indirectly arising from the use of the products. Seller’s warranty shall be limited to replacement of defective equipment and shall not include field removal and installation expenses.

The warranty set forth above is in lieu of all other warranties either express or implied and constitutes the full extent of Air Monitor Corporation’s liability to the customer, or any other party for breach of warranty.

THERE ARE NO EXPRESS WARRANTIES EXCEPT AS SET FORTH HEREIN AND THERE ARE NO IMPLIED WARRANTIES OF MERCHANTABILITY OF FITNESS FOR ANY PARTICULAR PURPOSE, WHICH ARE PARTICULARLY DISCLAIMED.

Copyright © 2016 Air Monitor Corporation. All printed material should not be changed or altered without permission of Air Monitor Corporation. Any published technical data and instructions are subject to change without notice. Contact your Air Monitor Corporation representative for current technical data and instructions. All brand names trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. Visit www.airmonitor.com to view and/or download the most recent version of this and other documents.