NEMA Definition Of Motor Full Load Nominal Efficency (Standard MG1-12.54.2) - On photo SIEMENS's new Simogear geared motors NEM A s t a ndard M G1-12.54.2 electrical-engineering-portal.com/nema-definition-of-motor-full-load-nominal-efficency-standard-mg1- 12-54-2 Edvard Translat e » Get PDF » Eff iciency is de fi ned as the ratio o f t he p ower output divid ed by th e p ower input . Machine losses are in the form of heat, and include: 1. Stat or winding los s, 2. Ro tor los s, 3. Core loss (hysteresis and eddy curren t ), 4. Friction and w indag e, and 5. Str ay load loss. NEMA standard MG1-12.54.2 provides instructions for establishing the value of efficiency. The standard states that the nominal efficiency shown on the motor nameplate shall not be greater than the average efficiency of a large population of motors of the same design.  Also , the full loa d efficiency, when o pe rating a t rated v oltag e and fr eq uency, will not b e les s than the minimum v alue ass ocia ted wit h the nominal value. Care should be take n in compa rin g e ff iciencies fr om o ne motor manuf actur er to

Electrical Engineering Portal.com NEMA Standard MG112542

Embed Size (px)

Citation preview

Page 1: Electrical Engineering Portal.com NEMA Standard MG112542

7/27/2019 Electrical Engineering Portal.com NEMA Standard MG112542

http://slidepdf.com/reader/full/electrical-engineering-portalcom-nema-standard-mg112542 1/2

NEMA Definition Of Motor Full Load Nominal Efficency (Standard MG1-12.54.2) - On photo SIEMENS's new Simogear geared motors

NEMA standard MG1-12.54.2

electrical-engineering-portal.com /nema-definition-of-motor-full-load-nominal-efficency-standard-mg112-54-2

Edvard

Translate »

Get PDF »

Efficiency is defined as the ratio of the power output divided by the power input. Machine losses are in the form of heat,

and include:

1. Stator winding loss,

2. Rotor loss,

3. Core loss (hysteresis and eddy current ),

4. Friction and windage, and

5. Stray load loss.

NEMA standard MG1-12.54.2 provides instructions for establishing the value of efficiency.

The standard states that the nominal efficiency shown on the motor nameplate shall not be greater than the average

efficiency of a large population of motors of the same design.

 Also, the full load efficiency, when operating at rated voltage and frequency, will not be less than the minimum value

associated with the nominal va lue. Care should be taken in comparing e fficiencies from one motor manufacturer to

Page 2: Electrical Engineering Portal.com NEMA Standard MG112542

7/27/2019 Electrical Engineering Portal.com NEMA Standard MG112542

http://slidepdf.com/reader/full/electrical-engineering-portalcom-nema-standard-mg112542 2/2

GE motor 250H 4P 460V TEBC nameplate

another. It is difficult to compare e fficiencies based on published, quoted or test data, due to the fact that there is no

single standard method which is used throughout the industry.

The most common referred to standards are IEEE 112 (U.S.), IEC (International), JEC-27 (Japanese), BS-269 (British)

and  ANSI C50.20 (same as IEEE 112).

IEEE 112 is used more than any of the others in the United States, while allowing for a variety of test methods to be

used. The preferred procedure is IEEE method B, where the motor is operated at full load, and the power is directly

measured.

Generally, larger motors will be more efficient than smaller motors.

Today’s premium efficiency 3-phase motors have efficiencies ranging from 86.5% at 1 hp to 95.8% at 300 hp. The

efficiency value that appears on the nameplate is the “nominal full-load efficiency” as determined using a very accurate

dynamometer and a procedure described by IEEE Standard 112, Method B.

The nominal value is what the

average would be if a substantial

number of identical motors were

tested and the averages of the batch

were determined. Some motors mighthave a higher value and others might

be lower, but the average o f all units

tested is shown as the nominal

nameplate value. Thus, essentially 

the rating Nom Eff.

92.1 means this is an average

efficiency of this motor model, but

actual efficiency may vary. The

efficiency is reduced by any form of 

heat, including friction, stator winding

loss, rotor loss, core loss (hysteresisand eddy current ), etc.

The actual motor efficiency is

guaranteed to be within a band of this

nominal efficiency by the manufacturer. The efficiency band varies from manufacturer to manufacturer.

The maximum allowable “band” is 20% set by NEMA.

This is a large range; therefore pay close attention to the manufacturer’s actual minimum guarantee!

Reference: Understanding Motor Nameplate Information: NEMA vs. IEC Standards – Continuing Education and 

Development, Inc.