COORDINATE LETTERING COLOR OF THE EXIT SIGN WITH AUTHORITY HAVING JURISDICTION.
PROVIDE MOUNTING TYPES, DIRECTIONAL ARROWS AND FACE QUANTITIES (SINGLE / DOUBLE) AS INDICATED ON DRAWING.
LIGHTING FIXTURE NOTES:
1
LENS/
LOUVER
- 28W T8
NOTES
& CATALOG NO.
MANUFACTURER
2 28A
WATTSNO.
LAMP DATA
DESCRIPTIONTYPE
LIGHTING FIXTURE SCHEDULE
CODE
VOLTS
120
1' X 4 DIRECT/INDIRECT CENTER MOUNT LOUVERED
BASKET W/ DIMMING BALLAST (OR APPROVED
EQUAL) MOUNTED IN GYPSUM BOARD
MOUNTING
CG - CEILING, RECESSED, GYPSUM BD.CR - CEILING, RECESSED, ACTWR# - WALL, RECESSED, # FEET A.F.F.
WS# - WALL MTD., SURFACE, # FEET A.F.F.CC# - CEILING, SUSPENDED, # FEET A.F.F.
CS - CEILING, SURFACE
MOUNTING:
UC - UNDER CABINET
- - -UNV
EXIT SIGN
LED-
COLUMBIA OR APPROVED EQUAL
# STE14-228G-MPO-ED-U-FK14
CR
ACRYLIC 28WT81 28C 120
4' OVER HEADBOARD HOSPITAL FIXTURE WITH
UPLIGHT, DOWNLIGHT, AND NIGHT LIGHT SETTINGS
WS
-E 120
2' WALL MOUNT OVER SINK FLUORESCENT WRAP
FIXTURE
WS
- LED- -H 120
WET LOCATION EXTERIOR OVER DOOR LIGHTING W/
BATTERY PACK
WS
- 28W T82 28F 120
4' INDUSTRIAL FIXTURE
CS
- -- -G 120
WET LOCATION SURFACE MOUNT COMPACT
FLUORESCENT DOWNLIGHT
CS
ACRYLIC 28W T82 28B 120
4' WALL MOUNT OVER SINK FLUORESCENT WRAP
FIXTURE
WS
- 26WTT1 26D 120
7" COMPACT FLUORESCENT DOWNLIGHT W/ DIMMING
BALLAST (OR APPROVED EQUAL)
CR
1
COLUMBIA OR APPROVED EQUAL
# W4-228-E120
COLUMBIA OR APPROVED EQUAL
# WM4-1U2D28-EU-NL
KURT VERSEN OR APPROVED EQUAL
# P921 DM
COLUMBIA OR APPROVED EQUAL
# CSR4-2-28-ST-EU
HUBBELL OR APPROVED EQUAL
# BRLU-01
LITHONIA OR APPROVED EQUAL
# WSR LED-2-10A700/40K-SR3-120-ELCW-DDBXD
LOW VOLTAGE MOLDED CASE CIRCUIT BREAKER,
METER
T
SMOKE DETECTOR
FIRE ALARM MANUAL STATION, 48" A.F.F., U.O.N.
OUTLET BOX, 18" A.F.F., U.O.N.
FAAP FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANELFACP
FLUSH MOUNTED FLOOR OUTLET BOX
DUPLEX RECEPTACLE - 2P, 3W, 2OA, 125V, NEMA 5-2OR IN
2P, 3W, 2OA, 125V, NEMA 5-2OR IN RECESSED TWO-GANG
TWO DUPLEX RECEPTACLES WITH COMMON FACEPLATE
FIRE ALARM HORN WITH VISUAL DEVICE,
GFCI
WP
INDICATES TWO SWITCHED LEVELS OF ILLUMINATION
PROVIDED BY THIS FIXTURE
CONNECT TWO OUTBOARD LAMPS TO ONE SWITCH
CONNECT REMAINING LAMP(S) TO SECOND SWITCH
LIGHTING FIXTURE ON EMERGENCY CIRCUIT /
UPPER CASE - FIXTURE TYPE (TYPICAL FOR ALL
LIGHTING FIXTURES) - SEE LIGHTING FIXTURE SCHEDULE
LIGHTING FIXTURE: DOWNLIGHT, 2' x 4' & 2' x 2'
LOWER CASE - INDICATES CONTROLLING SWITCH(ES)
(TYPICAL FOR ALL LIGHTING FIXTURES)
A
a
REVISION NUMBER - CLOUDED AREA ON DRAWING
CONTAINS REVISION
DETAIL, SECTION OR ELEVATION NUMBER
DRAWING NUMBER
DRAWING NOTE (APPLIES TO THIS DRAWING ONLY)#
LIGHTING FIXTURE, WALL MOUNTED - SEE LIGHTING
FIXTURE SCHEDULE
EXIT LIGHT - DARKENED SECTION INDICATES FACE
WITH DIRECTIONAL ARROWS AS INDICATED.
SEE LIGHTING FIXTURE SCHEDULE
RACEWAY - 2 #12, 1 #12 GW IN 3/4" CONDUIT, U.O.N.
HOMERUN TO PANELBOARD - ARROWS INDICATE NUMBER
OF CIRCUITS SLASHES INDICATE CIRCUIT CONDUCTORS
NO SLASH INDICATES TWO CIRCUIT CONDUCTORS
JUNCTION BOX: CEILING, WALL OR FLUSH-FLOOR MOUNTED
DUPLEX RECEPTACLE - 2P, 3W, 2OA, 125V, NEMA 5-2OR IN
RECESSED OUTLET BOX, 18" A.F.F., U.O.N.:
#
PANELBOARD, RECESSED OR SURFACE MOUNTED
ELECTRICAL MOTOR
MOTOR SWITCH WITH THERMAL OVERLOAD
NONFUSED DISCONNECT SWITCH, NUMERAL INDICATES SIZE
FIRE ALARM VISUAL DEVICE, SUBSCRIPT DENOTES
ELECTRICAL LEGEND
PROVIDE GROUNDING CONDUCTOR, NOT SHOWN
#
(DARKENED AREA INDICATES CONNECTION TO
EMERGENCY LIGHTING CIRCUIT)
AND ACCESSORIES
RATING AS INDICATED, SEE SCHEDULE FOR TYPE
CANDELA RATING, 8O" A.F.F. OR 6" BELOW CEILING,
SUBSCRIPT DENOTES CANDELA RATING, 8O" A.F.F.
DUPLEX RECEPTACLE, MOUNTED 6" ABOVE COUNTERTOP
BACK SPLASH UNLESS OTHERWISE NOTED
FLUORESCENT LIGHTING FIXTURE
FLUORESCENT LIGHTING FIXTURE, INDUSTRIAL TYPE
DUPLEX RECEPTACLE - 2P, 3W, 2OA, 125V, NEMA 5-2OR IN
SURFACE OUTLET BOX, SURFACE MOUNTED, 18" A.F.F., U.O.N.
9OA
BATTERY BACKUP
WHICHEVER IS LOWER.
OR 6" BELOW CEILING, WHICHEVER IS LOWER.
TRANSFORMER, TYPE AS NOTED ON DRAWING
SPECIAL RECEPTACLE, 18" A.F.F. U.O.N. (TYPE AS NOTED)
1 - RANGE: NEMA '14-5O' RECEPTACLE, 3O" A.F.F.
2 - DRYER: NEMA '14-3O' RECEPTACLE, 3O" A.F.F.
R - REFRIGERATOR, CM - COFFEE MAKER,
GFCI - GROUND FAULT CIRCUIT INTERRUPTER,
WP - WEATHERPROOF, MW - MICROWAVE,
TC - TELECOM, DW - DISHWASHER,
"x" NUMERIC DENOTES MOUNTING HEIGHT.
IG - ISOLATED GROUND
3 - SERVER RACK: NEMA 'L5-3OR' RECEPTACLE, 3O" A.F.F.
COMBINATION TELEPHONE/DATA OUTLET. PROVIDE EMPTY
JUNCTION BOX WITH SINGLE GANG EXTENSION WITH 1" CONDUIT
FROM BOX TO ACCESSIBLE CEILING SPACE WITH PULL STRING.
CABLE, JACKS AND FACEPLATES PROVIDED BY OTHERS. SEE I.T.
FOR ADDITIONAL WORK.
J JJ
60
S
M
15
15
M
SINGLE POLE TOGGLE SWITCH - SUBSCRIPT INDICATES
FIXTURES CONTROLLED BY THE SWITCH (TYPICAL FOR
ALL LIGHTING SWITCHES), 48" A.F.F., U.O.N.:
3 - THREE WAY TOGGLE SWITCH,
4 - FOUR WAY TOGGLE SWITCH,
S
a
D - DIMMER SWITCH,
O - WALL MTD. OCCUPANCY SENSOR,
WP - WEATHERPROOF
FLUSH MOUNTED CEILING OUTLET BOX
DUPLEX RECEPTACLE - 2P, 3W, 2OA, 125V, NEMA 5-2OR IN
ELECTRICAL LEGEND
TRANSFORMER
WEATHERPROOF
WIRE
VOLT
UNLESS OTHERWISE NOTED
UNIT HEATER
TYPICAL
TELEPHONE TERMINAL BOARD
SWITCH
ROOM
PANEL
PUSH BUTTON
POLE
PHASE
NOT TO SCALE
NOT IN CONTRACT
NON-FUSED SAFETY SWITCH
NON-FUSED
NATIONAL ELECTRICAL MANUF. ASSOC.
NATIONAL ELECTRICAL CODE
MOUNTING HEIGHT
MOUNTED
MAIN LUGS ONLY
MECHANICAL
MAIN CIRCUIT BREAKER
LIGHTING
KILOWATT
KILOVOLT-AMPERE
THOUSAND CIRCULAR MILS
JUNCTION BOX
HORSEPOWER
GROUND FAULT CIRCUIT INTERRUPTER
GROUND
FUSED SAFETY SWITCH
FULL LOAD AMPERES
FEEDER
FAN COIL UNIT
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM
FUSED OR FUSIBLE
EXISTING
EXISTING TO REMAIN
EQUIPMENT
ELECTRIC / ELECTRICAL
EXHAUST FAN
ENCLOSED CIRCUIT BREAKER
DRAWING
COPPER
CENTER
CEILING
CIRCUIT
CIRCUIT BREAKER
CONDUIT
BUILDING
AMERICAN WIRE GAUGE
AMERICAN NAT'L STANDARDS INSTIT.
AMPERE INTERRUPTING CAPACITY
AIR HANDLING UNIT
ABOVE FINISHED FLOOR
AMPERE
ELECTRICAL ABBREVIATIONS
A
AFF
AHU
AIC
ANSI
AWG
BLDG
C
CB
CKT
CLG
CTR
CU
DWG
ECB
EF
ELEC
EQUIP
ETR
EX
F
FA
FAAP
FACP
FCU
FDR
FLA
FSS
GND
GFCI
HP
JB
KCMIL
KVA
KW
LTG
MCB
MECH
MLO
MTD
MT HT
NEC
NEMA
NF
NFSS
NIC
NTS
PH or
P
PB
PNL
RM
SW
TTB
TYP
UH
UON
V
W
WP
XFMR
AFC ABOVE FINISHED COUNTER
- 28W T82 28A1 120
1' X 4 DIRECT/INDIRECT CENTER MOUNT LOUVERED
BASKET W/ BATTERY PACK W/ DIMMING BALLAST (OR
APPROVED EQUAL) MOUNTED IN GYPSUM BOARD
CR
ACRYLIC -J 120
WET LOCATION EXTERIOR ENTRY LIGHTING W/
BATTERY PACK
WS EVERGREEN OR APPROVED EQUAL
# EVOL22-WALL-44-(3)15WLED-BA-WDA-EMR,900 LUMEN
- 26WTT1 26D1 120
7" COMPACT FLUORESCENT DOWNLIGHT W/
BATTERY PACK W/ DIMMING BALLAST (OR APPROVED
EQUAL)
CR
COLUMBIA OR APPROVED EQUAL
# STE14-228G-MPO-ED-U-EL-FK14
28WT82 28
COLUMBIA OR APPROVED EQUAL
# W2-217-E120
17W T82 17
KURT VERSEN OR APPROVED EQUAL
# P921 DM EM
CEILING MOUNTED OCCUPANCY SENSOR, DUAL TECHNOLOGYO SENSOR AS MANUFACTURED BY WATTSTOPPER OR
APPROVED EQUAL.
POWER PACK FOR OCCUPANCY SENSORPP
LITHONIA OR APPROVED EQUAL
# LQM-S-W-3-G-120/277-EL N
LED-
FULL VOLTAGE NON REVERSINGFVNR
COMBINATION MAGNETIC MOTOR STARTER WITH DISCONNECT
SWITCH. SIZE FVNR NEMA STARTER AS REQUIRED. NUMERIAL
INDICATES SIZE OF DISCONNECT
60
TELEPHONE TERMINAL BOARD
SPRINKLER VALVE POSITION (TAMPER) SWITCH
SPRINKLER FLOW SWITCH
VARIABLE FREQUENCY DRIVE
VFD
SPRINKLER PRESSURE SWITCH
FIRE ALARM SPEAKER, CEILING OR WALL MOUNTEDS S
REFER TO DETAIL ON SHEET E4.01
FIRE ALARM ADDRESSABLE MODULEMM
SPRINKLER LOW AIR ALARM SWITCHLA
FIRE ALARM BELL / GONG
DOMESTIC WATER HEATERDWH
CONDENSER WATER PUMPCWP
DOMESTIC HOT WATER CIRCULATOR PUMPCP
HEATING WATER PUMPHWP
G:\070360.050 <
<>
> P
RO
X
XX
.D
WG
07/20/11 13:29 X
RE
F: ..\070360.050T
B.D
WG
-->
A
BA
BKM# 070360.050
1. REFER TO ARCHITECTURAL DRAWINGS FOR ROOM NAME LIST.
2. THE ELECTRICAL CONTRACT DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO INDICATE SCOPE
AND THE GENERAL ARRANGEMENT OF THE SYSTEMS. WHERE APPLICABLE THE FOLLOWING NOTES SHALL
APPLY TO ALL ELECTRICAL SYSTEMS.
3. REFER TO MECHANICAL PLANS FOR EXACT MECHANICAL EQUIPMENT LOCATION & ELECTRICAL
CONNECTION REQUIREMENTS.
4. ALL EQUIPMENT SHOWN ON DEMOLITION PLAN IS EXISTING. ELECTRICAL EQUIPMENT SHOWN SOLID AND
LIGHT SHALL REMAIN ALONG WITH ASSOCIATED WORK UNLESS OTHERWISE NOTED. ELECTRICAL
EQUIPMENT SHOWN DASHED AND DARK SHALL BE REMOVED AND DISPOSED OF.
5. PROVIDE APPROVED FIRE STOPPING MATERIAL AROUND ALL CONDUIT AND WIRE PENETRATIONS
THROUGH FIRE RATED FLOORS AND WALLS. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF
FIRE RATED FLOORS AND WALLS.
6. AS AN INTEGRAL PART OF THESE DOCUMENTS, THE CONTRACTOR SHALL REFER TO THE SPECIFICATIONS
FOR ADDITIONAL INFORMATION.
7. CONTRACTOR SHALL VISIT THE SITE AND VERIFY EXISTING CONDITIONS PRIOR TO THE BEGINNING OF ANY
WORK. FAILURE TO VISIT THE SITE SHALL IN NO WAY RELIEVE THE CONTRACTOR FROM ANY
RESPONSIBILITY.
8. RETURN TO OWNER, AT THEIR DISCRETION, ALL UNUSED ELECTRICAL EQUIPMENT (I.E. FIXTURES, PANELS,
ETC).
9. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATIONS OF LIGHTING FIXTURES.
10. CIRCUIT NUMBERS INDICATED ARE FOR CLARIFICATION OF GROUPING ONLY. ADJUST CIRCUIT NUMBERS
TO COORDINATE WITH ACTUAL CIRCUIT BREAKERS USED.
11. ELECTRICAL CONTRACTOR SHALL PROVIDE RACEWAYS, JUNCTION BOXES, AND DEVICE BOXES AS
NEEDED FOR CABLE PATHWAYS AND DEVICE INSTALLATION FOR ALL WORK SHOWN ON THE T SHEETS.
COORDINATE ALL WORK ON T SHEETS WITH OTHER TRADES.
ELECTRICAL GENERAL NOTES:
EC
B
EC
B
EX. PANEL (30 POLE)
EX. PANEL (42 POLE)
ABANDONED ECB
EX. METER
STACK
PNL BPNL D
ENCLOSURE
PUMP DISCONNECT
PUMP DISCONNECT
(4)
(2)
SCALE: 1/4 " = 1'-0"
1
E1.01
BASEMENT PLAN - ELECTRICAL - DEMOLITION
G:\B
KM
<
<>
> P
RO
-T
YP
.D
WG
08/04/08 14:20 X
RE
F: G
:\B
KM
\P
LO
TT
IN
G S
ET
UP
G
UID
E\T
B.D
WG
-->
A
BA
GENERAL NOTES:
1. REFER TO E0.01 FOR ELECTRICAL LEGEND, ABBREVIATIONS AND GENERAL NOTES.
2. ALL EQUIPMENT SHOWN ON THIS DEMOLITION PLAN IS EXISTING. ELECTRICAL
EQUIPMENT SHOWN SOLID AND LIGHT SHALL REMAIN ALONG WITH ASSOCIATED
WORK UNLESS OTHERWISE NOTED. ELECTRICAL EQUIPMENT SHOWN DASHED AND
DARK SHALL BE DISPOSED OF UNLESS OTHERWISE NOTED.
BKM# 070360.050
N
DRAWING NOTES:
1 REMOVE EXISTING FIRE ALARM DEVICES.
FACP
1
PNL C
S S S
S
S
S
S
S
2
222
2
2
2
2
3 3
SCALE: 1/4 " = 1'-0"
1
E1.02
FIRST FLOOR PLAN - ELECTRICAL - DEMOLITION
G:\B
KM
<
<>
> P
RO
-T
YP
.D
WG
08/04/08 14:20 X
RE
F: G
:\B
KM
\P
LO
TT
IN
G S
ET
UP
G
UID
E\T
B.D
WG
-->
A
BA
DRAWING NOTES:
1
GENERAL NOTES:
1. REFER TO E0.01 FOR ELECTRICAL LEGEND, ABBREVIATIONS AND GENERAL NOTES.
2. ALL POWER, LIGHTING, FIRE ALARM, COMMUNICATION, DATA, AND ADDITIONAL
ELECTRICAL EQUIPMENT IS TO BE REMOVED, UNLESS OTHERWISE NOTED. ALL
CONDUIT AND WIRING TO BE REMOVED BACK TO SOURCE. THIS FLOOR WILL BE
GUTTED.
EXISTING FIRE ALARM CONTROL PANEL TO BE REMOVED CLEANED AND SAVED
FOR REUSE IN NEW WORK. REMOVE ALL ASSOCIATED WIRE, CONDUIT, AND FIRE
ALARM CONTROL WIRING BACK TO SOURCE.
REMOVE EXISTING FIRE ALARM SPEAKER. PROTECT DURING DEMOLITION FOR
REUSE IN NEW WORK. SEE DRAWING E2.02 FOR NEW WORK.
REMOVE EXISTING FIRE ALARM DEVICES LOCATED IN ATTIC SPACE.
BKM# 070360.050
N
2
3
EC
B
30
15
15
HWP-1
HWP-2
PNL-3
EX. METER
STACK
H
F
EX. PANEL (30P)
EX. PANEL (42P)
000
001
002
003
7(42P)
7(42P) 7(42P)
VFD
VFD
8(PNL 3)
2(PNL 3)
3(PNL 3)
1(PNL 3)
J
6
19(PNL 1)
J
CWP-1
5(PNL 3)
CP-1
SM
DWH-1
30
7(PNL 3)
CWP-2
17(PNL 3)
14(PNL 3)
J
12
(2)
LA
16(PNL 3)
SCALE: 1/4 " = 1'-0"
1
E2.01
BASEMENT PLAN - ELECTRICAL - NEW WORK
G:\B
KM
<
<>
> P
RO
-T
YP
.D
WG
08/04/08 14:20 X
RE
F: G
:\B
KM
\P
LO
TT
IN
G S
ET
UP
G
UID
E\T
B.D
WG
-->
A
BA
DRAWING NOTES:
1
2
GENERAL NOTES:
1. REFER TO E0.01 FOR ELECTRICAL LEGEND, ABBREVIATIONS AND GENERAL NOTES.
2. REFER TO MECHANICAL DRAWINGS FOR EXACT EQUIPMENT LOCATIONS AND
ABBREVIATIONS.
3. REFER TO DRAWING E4.01, M5.01 AND M5.02 FOR MORE INFORMATION REGARDING
FIRE ALARM CONNECTIONS TO SPRINKLER PIPE SYSTEM.
CIRCUIT CONTINUES ON SHEET E3.01.
CONNECT TO EXISTING BASEMENT LIGHTING CIRCUIT.
PROVIDE 3 PHASE, 3 HP, 208 V VARIABLE FREQUENCY DRIVE WITH INTEGRAL
DISCONNECT SWITCH.
PROVIDE 4 # 10 + 1 # 10 GND IN 3/4" C.
PROVIDE 4 # 12 + 1 #12 GND IN 3/4" C.
JUNCTION BOX FOR POWER DOOR CONNECTION. SEE DETAILS ON SHEET T-402.
PROVIDE 3/4" RIGID GALVANIZED THREADED CONDUIT.
PROVIDE SURFACE MOUNTED WATER TIGHT RECEPTACLE AND ENCLOSURE
(LEVITON WETGUARD SERIES OR APPROVED EQUAL) IN NEW MANHOLE. ENTEND
WIRE AND CONDUIT AS REQUIRED. REFER TO DRAWING D-6 FOR MORE DETAILS.
CORE DRILL AS REQUIRED.
CONNECT TO SUMP PUMP CONTROLLER.
CONNECT TO EXISTING LIGHTING CIRCUIT SERVING AREA AHEAD OF LOCAL TOGGLE
SWITCH.
CONNECT TO AIR COMPRESSOR.
N
3
4
5
6
BKM# 070360.050
ELECTRICAL ROOM
MECHANICAL ROOM
CRAWL SPACE
ROOM NAME LIST
000
002
003
ELECTRICAL ROOM
001
7
8
9
10
11
12
GFCI
GFCI
GFCI
WP
GFCI
WP
GFCI
WP
GFCI
WP
15 15
15
15
15
15
30
15
15
15
15
30
15
15
15
GFCI
WP
GFCI
WP
GFCI
WP
GFCI
WP
GFCI
WP
FA
AP
PNL 2
PNL 1
9
2
1
2
9
2
2
SM
SM
SM
SM
15
3
118
102
119
123
117
121
122
120
114
115116
100a
100
101
124
113 112
103 104 105 106 107 108 109 110
111
2(PNL 1)
1(PNL 3A)
4(PNL 1)
6(PNL 1)
5(PNL 1)17(PNL 1)
10(PNL 1)
9(PNL 3A)
13(PNL 3A)
26(PNL 3A)
2(42P)
11(PNL 1)
13(PNL 1)
15(PNL 1)
16(PNL 1)
17(PNL 3A)
12(PNL 2)
6(PNL 3A)
7(PNL 2)
10(PNL 3A)
14(PNL 3A)
6(PNL 2)
1(PNL 2)
22(PNL 3A)
15(PNL 3)
4(PNL 2)
18(PNL 3A)
5(PNL 2)
8(PNL 2)
13, 15(PNL 2) 14, 16(PNL 2)
17, 19(PNL 2)
2(PNL 3A)
21(PNL 2) 23(PNL 2)
25(PNL 3A)
5(PNL 3A)
5
5
5
5
5
5
20(PNL 2)
20(PNL 2)
20(PNL 2)
5
30
18(PNL 1)
18(PNL 1)
18(PNL 1)
PNL 3A
30
2
SM
1913
PNL DIM
ERU-1
J
19(PNL 1)
J
7
8
11(PNL 2)
60
60
6
21(PNL 3A)
J
19(PNL 1)
6
3(PNL 1)
7(PNL 1)
9(PNL 1)
8(PNL 1)
SM
21(PNL 1)
J
19(PNL 1)
6
J
19(PNL 1)
6
J
19(PNL 1)
6
J
11
11
11
SM
25(PNL 1)
10
SM
23(PNL 1)
10
SM
27(PNL 1)
10
29(PNL 1)
12
1(PNL 1)
31(PNL 1)
30(PNL 1)
25(PNL 2)
13
13
13
13
13
13
11(PNL 2)
3
26(PNL 2)
14(PNL 1)
3/4" PLYWOOD
27(PNL 2) 29(PNL 2)
30(PNL 2)
J
8
GFCI
7
SM
3(PNL 2)
SS SS
S
S
S
S
S
S
S
14
14
1414
14
14
14
14
FACP
4
9(42P)
J
15
2
SM
J
15
2
SM
J
15
J
15 2
SM
J
15 2
SM
J
15
2
SM
J
15
J
15
J
15
2
SM
J
15 2
SM
J
15
J
16
29(PNL 3A)
J
16
30(PNL 3A)
J J J
32(PNL 1)
17
17
17
J J J
18
34(PNL 1)
J J J
18
34(PNL 1)
J J J
32(PNL 1)
1717
J
J
SCALE: 1/4 " = 1'-0"
1
E2.02
FIRST FLOOR PLAN - POWER - NEW WORK
G:\B
KM
<
<>
> P
RO
-T
YP
.D
WG
08/04/08 14:20 X
RE
F: G
:\B
KM
\P
LO
TT
IN
G S
ET
UP
G
UID
E\T
B.D
WG
-->
A
BA
DRAWING NOTES:
1
2
GENERAL NOTES:
1. REFER TO E001 FOR ELECTRICAL LEGEND, ABBREVIATIONS AND GENERAL NOTES.
2. ALL FIRE ALARM WORK MUST BE COMPATIBLE WITH EXISTING NOTIFIER FIRE ALARM
CONTROL PANEL.
PROVIDE DISCONNECT FOR ERU-1 LOCATED IN ATTIC SPACE.
PROVIDE MOTOR RATED SWITCH FOR CONCEALED DUCTED TYPE GEOTHERMAL HEAT PUMP
LOCATED IN ATTIC SPACE.
RUN CONDUIT UNDERGROUND TO BASEMENT. CONNECT TO EXISTING 42 POLE PANEL IN
BASEMENT.
NEW LOCATION FOR EXISTING NOTIFIER FIRE ALARM CONTROL PANEL THAT WAS REMOVED
DURING DEMOLITION.
PROVIDE SURFACE MOUNT RECEPTACLE IN ATTIC. ATTACH TO NEARBY STRUCTURE AS
REQUIRED.
JUNCTION BOX FOR POWER DOOR CONNECTION. SEE DETAILS ON SHEET T-402.
CONNECT TO AUTOMATIC DOOR OPERATOR. EXTEND WIRE AND CONDUIT TO DOOR OPERATOR
AND CIRCUIT INDICATED.
PROVIDE FLOOR MOUNTED JUNCTION BOX. COORDINATE EXACT LOCATION WITH ARCHITECT/
OWNER. CONNECT PEDESTAL MOUNTED PUSH BUTTON TO AUTOMATIC DOOR OPERATOR.
PROVIDE WIRE AND CONDUIT AS REQUIRED.
PROVIDE A NEW 2P 60A NON-FUSED DISCONNECT SWITCH FOR CONCEALED DUCTED TYPE
GEOTHERMAL HEAT PUMP LOCATED IN ATTIC SPACE.
CONNECT TO MOTORIZED PARTITION OPERATOR. EXTEND WIRE AND CONDUIT TO PARTITION
OPERATOR AND CIRCUIT INDICATED.
CONNECT PARTITION CONTROL STATION TO MOTORIZED PARTITION OPERATOR. EXTEND WIRE
AND CONDUIT AS REQUIRED.
MOUNT RECEPTACLE 6" BELOW GYPSUM BOARD CEILING TO CENTER OF FACE PLATE FOR CORD
AND PLUG PATIENT LIFT CHARGER.
COORDINATE EXACT MOUNTING HEIGHT OF RECEPTACLE WITH SMART BOARD MANUFACTURER
REINSTALL EXISTING FIRE ALARM SPEAKER THAT WAS PROTECTED DURING DEMOLITION.
PROVIDE 2 #12 + 1 #12 NEUTRAL + 1 #12 GRD IN 3/4" C. COORDINATE AS REQUIRED FOR
CONNECTION TO 120V CONDENSATE PUMP.
CONNECT TO CONDENSATE PUMP.
CONNECT TO UNDER COUNTER FAUCET SENSOR. COORDINATE WITH PLUMBING WORK AS
REQUIRED
CONNECT TO AUTOMATIC FLUSH VALVE. COORDINATE WITH PLUMBING WORK AS REQUIRED.
BKM# 070360.050
N
3
4
5
HOUSEKEEPING
PATIENT TRAINING ROOM
CORRIDOR
EDUCATION PLATFORM
CORRIDOR
TRAINING ROOM
INSTRUCTOR120
119
124
125
123
122
121
STAFF TOILET
OFFICE #8
OFFICE #9
RECEPTION
RECEPTION
PC TRAINING
WOMEN'S TOILET
MEN'S TOILET
BREAK ROOM
OFFICE #5
DIRECTOR OFFICE #6
OFFICE #7
OFFICE #1
OFFICE #2
OFFICE #4
111
117
118
114
115
116
113
112
106
105
104
109
108
107
110
STORAGE
VENDING
VESTIBULE
ROOM NAME LIST
100
101
102
IT
100a
OFFICE #3
103
6
7
8
9
10
11
12
13
14
15
16
17
18
S
D
S
3D
3D
S
3
3
S
O
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
S
S
D
S
D
OPP
A
A1
A
A
A
A
A
A
A
A1
B B
C
F
G G G
GGG
G G G
J
H
H
H
H
3
S
4
S
4
S
3
A
DDDD D D D
D
D
D
D
D
DDDDD D D
D
D
D
A1 A1
AA A
AA A
AA1 A
AA
AA1AAAA1
AA A
A
A1
A A A A A A A A
A A A A A A A A
A A
A A
A A
A A
A A
A A
OPP
OPP
OPP
OPP
OPP
OPP
OPP
OPP
O
O
PP
O
PP
A
A
A
A
A
A
A
A
OPP O
PP
A
A
A1
O
PP
A
A1
A
A
D
D
D1
D D
A
AA
D
D D
D1
D
J
J J
J
1
11
J
J
J
J
J
22
2
2
2
J
3
3
4
5
118
102
119
123
117
121
122
120
114
115116
100a
100
101
124
113
112
103 104 105 106 107 108 109
110
111
O
A1
22(PNL 2)
24(PNL 2)
26(PNL 1)
6
2(DIM)
1(DIM)
4(DIM)
5(DIM)
6(DIM)
3(DIM)
7(DIM)
8(DIM)
20(PNL-1)
28(PNL 1)
LIGHTING
DIMMING
PANEL
(DIM)
PNL 1
PNL 3A
8(42P)
F
PNL 2
SCALE: 1/4 " = 1'-0"
1
E3.01
FIRST FLOOR PLAN - LIGHTING - NEW WORK
G:\B
KM
<
<>
> P
RO
-T
YP
.D
WG
08/04/08 14:20 X
RE
F: G
:\B
KM
\P
LO
TT
IN
G S
ET
UP
G
UID
E\T
B.D
WG
-->
A
BA
DRAWING NOTES:
1
2
GENERAL NOTES:
1. REFER TO E0.01 FOR ELECTRICAL LEGEND, ABBREVIATIONS AND GENERAL NOTES.
PROVIDE LUTRON PARTITION SENSOR GRX-10 OR APPROVED EQUAL. SEE DRAWING 1
ON SHEET E4.01 FOR MORE INFORMATION.
PROVIDE LIGHTING CONTROL, LUTRON SG-4BN-WH-EGN, OR APPROVED EQUAL. SEE
DRAWING 1 ON SHEET E4.01 FOR MORE INFORMATION.
STACKED LUTRON GRAPHIC EYE MASTER CONTROLS, GRX-4103-WH, OR APPROVED
EQUAL. SEE DRAWING 1 ON SHEET E4.01 FOR MORE INFORMATION.
CIRCUIT CONTINUES ON SHEET E2.01.
RUN CONDUIT UNDERGROUND TO BASEMENT. CONNECT TO EXISTING PANEL 42P IN
BASEMENT.
PANEL UNIT 1, 12 CIRCUIT, 120V LIGHTING DIMMING PANEL, LUTRON GP12-120ML-20.
SEE DRAWING 1 ON SHEET E4.01 FOR MORE INFORMATION.
BKM# 070360.050
N
3
4
5
6
6O
OA
2O
OA
2O
OA
2O
OA
2O
OA
2O
OA
2O
OA
3 PH, 4W.
3 PH, 4W.
3 PH, 4W.
208Y/120V,
3 PH, 4W. 3 PH, 4W.
3 PH, 4W. 3 PH, 4W.
3 PH, 4W.
100A 100A
225A
208Y/120V, 3Ø, 4W
116
001 115 124 123 119 002 003 119 119 119
102122 120 117 118114100 110 111 114101
AREA SMOKE DETECTOR
MANUAL PULL STATION
SPRINKLER WATERFLOW / PRESSURE SWITCH
WATER CONTROL VALVE TAMPER
1. S
OU
ND
G
EN
ER
AL B
UILD
IN
G
ALA
RM
2. N
OT
IF
Y F
IR
E D
EP
AR
TM
EN
T.
3. IN
IT
IA
TE
S
UP
ER
VIS
OR
Y
SIG
NA
L T
O A
24-H
OU
R M
AN
NE
D
PO
IN
T F
OR
IM
ME
DIA
TE
RE
SP
ON
SE
.
4. O
PE
N LO
CK
ED
E
GR
ES
S
DO
OR
S.
X
X
X
X
X
X
X
X
X
X
INPUT DEVICE
OUTPUT DEVICE
9(42P)
20(PNL 1)
METER STACK
OUTDOOR
EX. PAD MOUNT
TRANSFORMER
TYPICAL WIRING DIAGRAM FOR CEILING
NO SCALE
Red
Blk
Blu
Wht
Hot
Neutral
Blk
Power
Pack
Control Output
Common
+24VDC
Sensor
24VDC
3-Wire
Any
Red
Red
Local
Switch
Off
d
a
L
o
MOUNTED OCCUPANCY SENSORS
Red
Blk
Blu
Wht
Hot
Neutral
Blk
Power
Pack
Control Output
Common
+24VDC
Sensor
24VDC
3-Wire
Any
Red
Red
Local
Switch
Off
d
a
L
o
Control Output
Common
+24VDC
Sensor
24VDC
3-Wire
Any
TYPICAL WIRING DIAGRAM FOR MULTIPLE
NO SCALE
CEILING MOUNTED OCCUPANCY SENSORS
3 PH, 4W.
100A
3 PH, 4W.
PANEL DIM
GP12-1204ML-15
12 CIRCUIT GP DIMMING
PANEL FEED TYPE:
NORMAL PANEL
STORAGE ROOM 102
Main Unit 2
Main Unit 3
Main Unit 4
GRX-4103-T-WH
3 ZONE CONTROL UNIT
3 GANG US DEEP BACKBOX
SCENES 1 - 4
STORAGE ROOM 102
GRX-4103-T-WH
3 ZONE CONTROL UNIT
3 GANG US DEEP BACKBOX
SCENES 1 - 4
TRAINING ROOM 119
GRX-4103-T-WH
3 ZONE CONTROL UNIT
3 GANG US DEEP BACKBOX
SCENES 1 - 4
STORAGE ROOM 102
GRX-4103-T-WH
3 ZONE CONTROL UNIT
3 GANG US DEEP BACKBOX
SCENES 1 - 4
STORAGE ROOM 102
SG-4BN-WH-EGN
1 GANG US BACKBOX
SCENES 1 - 4
TRAINING ROOM 119
SG-4BN-WH-EGN
1 GANG US BACKBOX
SCENES 1 - 4
TRAINING ROOM 119
SG-4BN-WH-EGN
1 GANG US BACKBOX
SCENES 1 - 4
TRAINING ROOM 119
SG-4BN-WH-EGN
1 GANG US BACKBOX
SCENES 1 - 4
TRAINING ROOM 119
GRX-12VDC
GRX-IO CONTACT CLOSURE
INTERFACE 4" SQUARE BOX
PARTITION STATUS MAINT.
IN. TRAINING ROOM 119
GRX-12VDC
GRX-IO CONTACT CLOSURE
INTERFACE 4" SQUARE BOX
PARTITION STATUS MAINT.
IN. TRAINING ROOM 119
GRX-12VDC
GRX-IRPS
GRX-IO CONTACT CLOSURE
INTERFACE 4" SQUARE BOX
PARTITION STATUS MAINT.
IN. TRAINING ROOM 119
GRX-IRPS
GRX-IRPS
4
4
4
4
4
4
4
4
4
4
4
5
6 6
6
7
30A
SG-4BN-WH-EGN
1 GANG US BACKBOX
SCENES 1 - 4
TRAINING ROOM 119
4
MAIN UNIT 1
208Y/120V, 208Y/120V, 208Y/120V,
208Y/120V,
208Y/120V,
208Y/120V,208Y/120V,208Y/120V,
208Y/120V,
124
119
TO ACCESS
CONTROL SYSTEM
FAAP
001
001 119 119 119 124 100
101 001 001 001
S
124
S
124
S
124
S
124
S
123
S
123
S
119
S
119
S
119
S
119
S
8
5
9
TYPICAL DETAIL OF
NO SCALE
FLOOR BOX INSTALLATION
LA
MM
001001
MM MM MM MM MM MM
001
MM
001001
MM
001
MM
001
MM
001
MM
11
G:\070360.050 <
<>
> P
RO
X
XX
.D
WG
07/20/11 13:29 X
RE
F: ..\070360.050T
B.D
WG
-->
A
BA
BKM# 070360.050
SCALE: N.T.S.
2
E4.01
SINGLE LINE DIAGRAM
SCALE: N.T.S.
1
E4.01
LIGHTING CONTROL DIAGRAM
DRAWING NOTES:
1 PROVIDE LUTRON EQUIPMENT AS SPECIFIED, OR APPROVED EQUAL.
ALL FIRE ALARM DEVICES LOCATED IN ATTIC SPACE SHALL BE EXISTING TO REMAIN
UNLESS OTHERWISE NOTED.
PROVIDE INTERFACE WITH ACCESS CONTROL SYSTEM AS REQUIRED TO RELEASE
DOORS UPON ISSUANCE OF A FIRE ALARM.
PROVIDE LUTRON CABLE GRX-PCBL-46L (PLENUM RATED) OR APPROVED EQUAL.
PROVIDE 4 # 4/0 + 1 # 4 GND IN 2-1/2" C.
PROVIDE 4 # 2 + 1 # 8 GND IN 1-1/2" C.
PROVIDE 4 # 10 + 1 # 10 GND IN 3/4" C.
PROVIDE NETWORK CABLE FOR VA CENTRAL MONITORING. (ASSUME FIBER OPTIC
CABLE FOR BID PURPOSES.)
PROVIDE 4 # 4/0 + 1 # 4 GND IN 2-1/2" C (REUSE EXISTING CONDUIT TO THE EXTENT
POSSIBLE.).
COORDINATE WITH THE VA/ USER TO IDENTIFY THE REQUIRED LIGHTING SCENES.
PROVIDE PROGRAMMING OF THE SYSTEM AS NEEDED. PROVIDE A MINIMUM 8 HOURS
OF TRAINING FOR VA PERSONNEL ON USE AND PROGRAMMING OF SYSTEM.
COORDINATE WITH FIRE PROTECTION WORK FOR CONNECTION OF 24V. WET PIPE
WATER GONG.
1
SCALE: N.T.S.
4
E4.01
FIRE ALARM DIAGRAM
2
3
2
3
SCALE: N.T.S.
5
E4.01
FIRE ALARM MATRIX
4
5
6
7
8
9
10
10
11
CONNECTED LOAD:
19
25
29
27
23
21
17
15
13
11
2O
26
3O
28
24
22
18
16
14
12
CØ: KVA= A
AØ:
BØ:
KVA=
KVA=
A
A
SUB-TOTALS
65
9
7
1O
8
CØ
LOAD (KVA)
EQUIPMENT
3
1
CKT
BØAØSERVED
LOAD (KVA)
BØAØ
BA C
CB BUS CB
SERVED
EQUIPMENT
CØ
4
2
CKT
SPACE
EXISTING LOAD
- - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - -
PNL-1
20
-
-
- -
-
-
-
-
20
-
-
-
-
-
-
20
20
20
20
20
20
20
20
20
20
20
- -
-
-
-
20
20
20
20
20
20
-
-
-
-
-
-
SPARE
SPARE
-
SPARE
-
-
9.2
-
9.3
7.3
20
100
20
20
20
20
-
-
-
-
EXISTING LOAD
SURFACE
3O29
CONNECTED LOAD:
41
35
37
39
33
31
42
36
38
4O
34
32
17
23
27
25
21
19
15
13
11
18
24
28
26
22
2O
16
14
12
CØ: KVA= A
AØ:
BØ:
KVA=
KVA=
A
A
SUB-TOTALS
65
9
7
1O
8
CØ
LOAD (KVA)
EQUIPMENT
3
1
CKT
BØAØSERVED
LOAD (KVA)
BØAØ
BA C
CB BUS CB
SERVED
EQUIPMENT
CØ
4
2
CKT
PNL-2
- - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - -
EXISTING LOAD
FACP
BASEMENT RECEPTACLES
SPACE
12.9
11.7
10.5
108
98
88
SPARE
SPARE
SPARE
LIGHTING
- - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - -
ERU-1
0.5
-
-
-
-
-
10.3
10.0
0.1
-
-
-
-
-
10.1
8.9
-
-
-
-
-
-
8.9
1.6
1.0
-
-
-
-
-
2.6
1.6
-
-
-
-
-
-
1.6
1.6
-
-
-
-
-
-
1.6
100 20
20 20
20
20
20 20
20 20
20 20
20 20
20 20
20 20
20 20
20 20
20 20
20 20
20 20
20 20
20
20
20
SURFACE
3O29
CONNECTED LOAD:
41
35
37
39
33
31
42
36
38
4O
34
32
17
23
27
25
21
19
15
13
11
18
24
28
26
22
2O
16
14
12
CØ: KVA= A
AØ:
BØ:
KVA=
KVA=
A
A
SUB-TOTALS
65
9
7
1O
8
CØ
LOAD (KVA)
EQUIPMENT
3
1
CKT
BØAØSERVED
LOAD (KVA)
BØAØ
BA C
CB BUS CB
SERVED
EQUIPMENT
CØ
4
2
CKT
HWP-1
HWP-2*
13.4
14.7
9.7
110
121
81
PANEL 3A
CWP-2*
CWP-10.6
0.3
2.9
0.6
2
3.3
0.2
2.7
1.3
-
10.5
1.3
-
11.4
1.3
7
9.8
20 20
SURFACE
3O29
CONNECTED LOAD:
41
35
37
39
33
31
42
36
38
4O
34
32
17
23
27
25
21
19
15
13
11
18
24
28
26
22
2O
16
14
12
CØ: KVA= A
AØ:
BØ:
KVA=
KVA=
A
A
SUB-TOTALS
65
9
7
1O
8
CØ
LOAD (KVA)
EQUIPMENT
3
1
CKT
BØAØSERVED
LOAD (KVA)
BØAØ
BA C
CB BUS CB
SERVED
EQUIPMENT
CØ
4
2
CKT
RECEPTACLES
AUTOMATIC DOOR OPERATOR
RECEPTALCES
RECEPTACLES
RECEPTACLES
RECEPTACLES
COMPUTER TRAINING
COMPUTER TRAINING
COMPUTER TRAINING
VENDING MACHINE
VENDING MACHINE
COMPUTER TRAINING
SMART BOARD PROJECTOR
SPACE
9.8
10.0
8.9
82
83
75
SPARE
SPARE
SPARE
ATTIC RECEPTACLES
LIGHTING
LIGHTING
COMPUTER TRAINING
COMPUTER TRAINING
SPARE
RECEPTACLES
RECEPTACLES
RECEPTACLES
RECEPTACLES
REFRIGERATOR
RECEPTACLES2.0
2.0
0.7
0.7
0.6
-
-
6.0
0.3
2.0
0.7
1.3
1.5
-
-
5.8
0.9
0.5
0.7
1.3
1.1
-
-
4.5
0.5
1.3
0.7
0.7
0.4
0.2
-
3.8
0.3
1.1
0.7
1.7
0.4
-
-
4.2
1.1
1.1
-
1.5
0.7
-
-
4.4
20 20
20 20
20 20
20 20
20 20
20 20
20 20
20 20
20 20
20 20
20 20
20 20
20 20
20 20
20 20
20 20
20 20
20 20
20
20
20
RECESSED
3O29
CONNECTED LOAD:
41
35
37
39
33
31
42
36
38
4O
34
32
17
23
27
25
21
19
15
13
11
18
24
28
26
22
2O
16
14
12
CØ: KVA= A
AØ:
BØ:
KVA=
KVA=
A
A
SUB-TOTALS
65
9
7
1O
8
CØ
LOAD (KVA)
EQUIPMENT
3
1
CKT
BØAØSERVED
LOAD (KVA)
BØAØ
BA C
CB BUS CB
SERVED
EQUIPMENT
CØ
4
2
CKT
RECEPTACLES
SMART BOARD PROJECTOR
FLOOR RECEPTACLES
RECEPTACLES
FLOOR RECEPTACLES
RECEPTACLES
RECEPTACLES
POWER DOOR
SPACE
9.3
9.2
7.3
78
77
61
SPARE
SPARE
SPARE
LIGHTING DIMMING PANEL
LIGHTING
RECEPTACLES
DATA RACK
ATTIC RECEPTACLES
SMART BOARD PROJECTOR
RECEPTACLES
RECEPTACLES
FLOOR RECEPTACLES
FLOOR RECEPTACLES
FLOOR RECEPTACLES1.1
0.6
1.1
1.2
1.2
0.6
-
5.8
0.6
0.6
0.5
0.5
1.2
-
-
3.4
0.4
0.7
0.4
1.2
0.8
-
-
3.5
0.2
0.6
0.5
0.4
-
3.5
0.7
0.7
2.2
0.4
-
5.9
0.7
1.1
0.5
-
-
3.8
20 20
20 20
20 20
20 20
20 20
20 20
20 20
20 30
20 20
20 30
20
20
20 20
20 20
20 20
20 20
20 20
20 20
20
20
20
SURFACE
PAVILION RECEPTACLES
- - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - -
CC = COLD CATHODE
NE = NEON
LV = LOW VOLTAGE
FL = FLUORESCNET
IN = INCANDESCENT
SUB-TOTAL
DIMMER PANEL SCHEDULE
DIMMER
ROOM NAME AND NUMBER FIXTURE
TYPE
LIGHTING
AMPS POLES
CKT. BREAKER
TYPE KVA
LOAD
NOTES
CIRCUIT
NO. (DM)
ZONE
NO.
CONTROL
STATION
DESIGN.
WAMPS
LOCATION:
PANEL:
AIC: MOUNTING:
RATING: VOLTAGE:MAIN:
NOTE:
VY/ PH,
LED = LIGHT EMITTING DIODE
15 1 - 0.3
- 0.4
- 0.2
- 0.2
- 0.2
5
4
3
2
1
1.8
GEMC
SURFACE
8
7
6 - 0.1
- 0.2
- 0.2
1
1
1
1
1
1
1
5
4
3
2
1
8
7
6
GEMC
GEMC
GEMC
GEMC
GEMC
GEMC
GEMC
GEMC = GRAFIK EYE MASTER CONTROL
CFL = COMPACT FLUORESCENT
- -
- -
- -
- -
LIGHTING
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
20
20
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
1.2
1.2
0.6
0.6
0.6- - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - -
AUTOMATIC FLUSH
SPARE
RECEPTACLES
FAUCET SENSOR
AUTOMATIC DOOR OPERATOR
MOTORIZED PARTITION
POWERED LIFT
SMART BOARD PROJECTOR
SPARE
SPARE
RECEPTACLES
RECEPTACLES
RECEPTACLES
FAUCET AND FLUSH SENSOR
SPARE
SPARE
RECEPTACLES
SPARE
SPARE
SPARE
1
1
1
1
3O29
CONNECTED LOAD:
41
35
37
39
33
31
42
36
38
4O
34
32
17
23
27
25
21
19
15
13
11
18
24
28
26
22
2O
16
14
12
CØ: KVA= A
AØ:
BØ:
KVA=
KVA=
A
A
SUB-TOTALS
65
9
7
1O
8
CØ
LOAD (KVA)
EQUIPMENT
3
1
CKT
BØAØSERVED
LOAD (KVA)
BØAØ
BA C
CB BUS CB
SERVED
EQUIPMENT
CØ
4
2
CKT
GEOTHERMAL HEAT PUMP-1
- - - - - - - - - - - - - - - - - - - - - - - - -
9
9.9
5.7
75
82.5
47.5
SPARE
2.0
0.7
0.5
0.5
0.5
4.2
2.0
0.7
0.5
1.0
0.5
4.7
0.7
0.7
0.5
1.0
2.9
2.0
0.7
0.7
0.5
0.9
4.8
2.0
0.9
0.7
0.7
0.9
5.2
0.7
0.9
0.5
0.7
-
2.8
35 35
15 15
15 15
15 15
15 15
15 15
15 15
20
SURFACE
GEOTHERMAL HEAT PUMP-2
- - - - - - - - - - - - - - - - - - - - - - - - -
GEOTHERMAL HEAT PUMP-3
- - - - - - - - - - - - - - - - - - - - - - - - -
GEOTHERMAL HEAT PUMP-4
- - - - - - - - - - - - - - - - - - - - - - - - -
GEOTHERMAL HEAT PUMP-5
- - - - - - - - - - - - - - - - - - - - - - - - -
GEOTHERMAL HEAT PUMP-6
- - - - - - - - - - - - - - - - - - - - - - - - -
GEOTHERMAL HEAT PUMP-7
- - - - - - - - - - - - - - - - - - - - - - - - -
GEOTHERMAL HEAT PUMP-8
- - - - - - - - - - - - - - - - - - - - - - - - -
GEOTHERMAL HEAT PUMP-9
- - - - - - - - - - - - - - - - - - - - - - - - -
GEOTHERMAL HEAT PUMP-10
- - - - - - - - - - - - - - - - - - - - - - - - -
GEOTHERMAL HEAT PUMP-11
- - - - - - - - - - - - - - - - - - - - - - - - -
GEOTHERMAL HEAT PUMP-12
- - - - - - - - - - - - - - - - - - - - - - - - -
GEOTHERMAL HEAT PUMP-13
- - - - - - - - - - - - - - - - - - - - - - - - -
GEOTHERMAL HEAT PUMP-14
- - - - - - - - - - - - - - - - - - - - - - - - -
2
-
20
20
20
20
20
20
2020
20
20
20
20
20
20
SPARE
SPARE
SPARE
SPARE
SPARE
CONDENSATE PUMP
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
CONDENSATE PUMP
-
-
-
-
-
-
-
-
-
-
-
-
0.20.2
- - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - -
100
SUMP PUMP
SPARE SPARE
SPARE
AIR COMPRESSOR
SUMP PUMP CONTROLLER0.2
0.2
-
-
2
0.7
0.5
-
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
20
20
20
20
30
20
20
20
* PUMP IS STAND-BY
15
15
15
15
15
15
15
15
15
15
15
SMART BOARD PROJECTOR
SMART BOARD PROJECTOR
MOTORIZED PARTITION
MOTORIZED PARTITION
0.9
CP-1
EF-1
DWH-1
20
20
20
1
1
1
9
9.9
5.7
9.3
9.2
7.3
78
77
61
RECEPTACLES
G:\070360.050 <
<>
> P
RO
X
XX
.D
WG
07/20/11 13:29 X
RE
F: ..\070360.050T
B.D
WG
-->
A
BA
BKM# 070360.050
DRAWING NOTES:
1
GENERAL NOTES:
1. BRANCH CIRCUIT BREAKERS MADE AVAILABLE DUE TO DEMOLITION SHALL BECOME
SPARES IN EXISTING PANELS.
PROVIDE NEW CIRCUIT BREAKER IN EXISTING SPACE. MATCH AIC OF EXISTING
CIRCUIT BREAKERS IN PANEL.