Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e [email protected] www.electricaltestmidlands.com COMPANY REGISTRATION No. 5126996 V.A.T. No. 851 3359 29 Report No. IPN4/0506760 Client: East Park Primary School Date: 17/8/2017 Address: East Park Primary School, Hollington Road, Wolverhampton, WV1 2DS Electrical Installation Condition Report

Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e [email protected]

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Electrical Test Midlands

110B Walsall Road, Cannock,

West Midlands, WS11 OJB

t 01922 710014

e [email protected]

www.electricaltestmidlands.com

COMPANY REGISTRATION No. 5126996 V.A.T. No. 851 3359 29

Report No. IPN4/0506760

Client: East Park Primary School

Date: 17/8/2017

Address: East Park

Primary School, Hollington

Road, Wolverhampton,

WV1 2DS

Electrical InstallationCondition Report

Page 2: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

ELECTRICAL INSTALLATIONCONDITION REPORT

Issued in accordance with British Standard 7671 - Requirements for Electrical Installations by an Approved Contractor orConforming Body enrolled with NICEIC, Warwick House,Houghton Hall Park, Houghton Regis,Dunstable,LU5 5ZX

Contractor's Reference Number

035056

A. DETAILS OF THE CLIENT

Client: Address:East Park Primary School Hollington RoadWolverhampton

Postcode: WV1 2DS

B. PURPOSE OF THE REPORT This report must be used only for reporting on the condition of an existing installation.

Purpose for whichthis report is required:

Electrical Installation Condition Report

Date(s) on which inspection and testing were carried out: 7th - 11th Aug 2017

C. DETAILS OF THE INSTALLATION

Occupier East Park Primary School Address Hollington RoadWolverhampton

Postcode: WV1 2DS

Estimated age of theelectrical installation: 40 + years Description of premises:

domestic, commercial,industrial, other(Please state)

CommercialEvidence of alterations

or additions á If yes,estimatedage

5 + years

Date of previousinspection:

N/A Electrical Installation Certificate No or previousPeriodic Inspection or Condition Report No:

N/A

Records of installation available: No Records held by: N/A

D. EXTENT OF THE INSTALLATION AND LIMITATIONS ON THE INSPECTION AND TESTING

Extent of the electrical installation covered by this report:

Whole Site

Agreed limitations (including the reasons), if any, on the inspection and testing:

10% Fittings Removed. 100% Visual. Visual & Accessible Items Tested Only.

Agreed with: Client

Operational limitations including the reasons (see page No. )

No Access To Main Supply Protective Device

The inspection and testing have been carried out in accordance with BS 7671, as amended. Cables concealed within trunking and conduits, or cables and conduitsconcealed under floors, in inaccessible roof spaces and generally within the fabric of the building or underground, have not been visually inspected unlessspecifically agreed between the client and inspector prior to the inspection.

E. SUMMARY OF THE CONDITION OF THE INSTALLATION

General condition of the installation (in terms of electrical safety):

See Observations (Page 2)

Summary of the condition of the installation continued on additional pages? No Yes Specify page No(s):áOverall assessmentof the installation: SATISFACTORY / UNSATISFACTORY

An ‘Unsatisfactory’ assessment indicates that dangerous (CODE C1) and/or potentiallydangerous (CODE C2) conditions have been identified, or that Further investigation withoutdelay (FI) is required

This report should have been reviewed and confirmed by the registered Qualified Supervisorof the Approved Contractor responsible for issuing it. (See declaration on page 2)

This report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

Page 1 of 65

Please see the 'Notes for Recipients'

Page 3: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

ELECTRICAL INSTALLATIONCONDITION REPORT

Please see the 'Guidance for Recipients on theclassification codes' in the 'Notes for Recipients'

F. OBSERVATIONS AND RECOMMENDATIONS FOR ACTIONS TO BE TAKEN

Referring to the attached schedules of inspection and test results, and subject to the limitations at D:

Item No Code Ú

There are no items adversely affecting electrical safety. N/A or The following observations and recommendations forare made

á

Additional Pages? No Yes á Specify page 9

ÚOne of the following codes, as appropriate, has been allocated to each of theobservations made above to indicate to the person(s) responsible for the installationthe degree of urgency for remedial action:

Code C1 "Danger Present". Risk of injury. Immediate remedial action required.

Code C2 "Potentially dangerous". Urgent remedial action required.

Code C3 "Improvement recommended".

Code FI "Further investigation required without delay".

Please see the notes for recipient for guidance regarding the Classification codes.

1 DB R - CIRCUIT 11L3 - SWITCHED OFF AT TIME OF TEST C3

2 DB R - UNABLE TO OBTAIN Z'S DUE TO HEIGHT (OVER 3METRES) - CIRCUITS 5L1, 8L2, 12L1, 12L2, 12L3 C3

3 DB R - CIRCUIT 1L1 - HIGH EARTH LOOP READING C2

4 DB R- CCT 2 - NO RCD PROTECTION FOR SKTS WITHOUT OUTSIDE USE C3

6 DB R 2 - CIRCUIT 2L3 - NO RCD PROTECTION TO SKT WITHOUT OUTDOOR USE C3

8 DB K - CIRCUIT 8L2 - SINGLE SOCKET SHOWING SIGNS OF THERMAL AFFECTS C3

9 DB K - CIRCUIT 7L2 - NO RCD PROTECTION TO SOCKET WITHOUT OUTDOOR USE C3

10 DB 2B (EX) - 1 X 20MM HOLE IN BOTTOM OF DB C2

11 DB 2B (EX) - CIRCUIT 6L2 - UNKNOWN - FURTHER INVESTIGATION IS REQUIRED TO LOCATE FINAL TERMINATION OF

CIRCUITC2

12 DB 2A (EX) - CIRCUIT 1L3 - NO RCD PROTECTION TO SOCKET WITH OUTDOOR USE C2

13 DB 2D (EX) - CIRCUIT 4L2 - NO RCD PROTECTION TO SOCKETS FOR SUPPLYING OUTDOOR USE C2

14 DB 2D (EX) - CIRCUIT 7L2 - SPUR FOR WINDOWS OVER 3 METRES NO ACCESS C3

15 DB 2C (EX) - CIRCUIT 10 - DAMAGED SOCKET ON DADO REAR OF RECEPTION BY CCTV SYSTEM C2

16 DB 2C (EX) - CIRCUIT 6L3 - NO RCD PROTECTION TO SOCKET C3

17 DB 2C (EX) - CIRCUIT 12L3 - SPUR OVER 3 METRES NO ACCESS TO OBTAIN Z'S C3

18 DB1 (N) - CIRCUITS 8L2, 9L1, 9L2, 3L3 - HIGH EARTH LOOP READINGS C2

19 DB1 (N) - CIRCUITS 7L3 - HIGH EARTH LOOP READING C2

20 DB1 (N) - CIRCUITS 8L3 + 9L3 - SOCKET + COOKER SWITCH ABOVE COOKER C2

21 DB1 (EX) - 1 X PIN MISSING FROM DB C3

22 DB 1D (EX) - CIRCUIT 7 - SPUR FOR CCTV OVER 3METERS C3

23 DB 1B (EX) - CIRCUIT 1L1 - NO RCD PROTECTION FOR SOCKETS WITH OUTSIDE USE C2

Immediate remedial actionrequired for items:

Urgent remedial actionrequired for items: 3, 10, 11, 12, 19, 13, 15, 18, 20, 23, 25, 29, 36,

Further investigation requiredwithout delay for items:

Improvementrecommended for items: 1, 2, 4, 6, 8, 9, 14, 16, 17, 21, 22, 24, 31, 32, 33,

G. DECLARATION

I/We, being the person(s) responsible for the inspection and testing of the electrical installation (as indicated by my/our signatures below), particulars of whichare described in page 1 (see C), having exercised reasonable skill and care when carrying out the inspection and testing, hereby declare that the informationin this report, including the observations (see F) and the attached schedules (see H), provides an accurate assessment of the condition of the electricali ns ta l l a t ion tak ing into account the s tated extent o f the ins ta l l a t ion and the l im i ta t ions of the inspect ion and tes t ing ( see D ) .I/We further declare that in my/our judgement, the overall assessment of the installation in terms of its suitability for continued use is

SATISFACTORY / UNSATISFACTORY* (see F) at the time the inspection was carried out, and that it should be further inspected as recommended (see I).

*An ‘Unsatisfactory’ assessment indicates that dangerous (CODE C1) and/or potentially dangerous (CODE C2) conditions have been identified, or that Further investigationwithout delay (FI) is required.

INSPECTION, TESTING AND ASSESSMENT BY:

Signature

Name(CAPITALS) RICHARD BLOCKSIDGE

Position TEST ENGINEER

Date: 11/08/2017

REPORT REVIEWED AND CONFIRMED BY:

Signature

Name(CAPITALS) MICHAEL BRYAN

(Registered Qualified Supervisor for the Approved Contractor at J)

Date: 16/08/2017

Page 2 of 65

This report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

Page 4: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

ELECTRICAL INSTALLATIONCONDITION REPORT

Page 3 of 65

H. SCHEDULES AND ADDITIONAL PAGES

Inspection Schedule: Page(s) No 4,5,6 Additional pages, including additionalsource(s) data sheets: Page No(s)

Schedule of Test Results for the Installation: Page No(s) Even, 8 - 64Schedule of Circuit Details for the Installation: Page No(s) Odd, 7 - 63

The pages identified are an essential part of this report. The report is valid only if accompanied by all the schedules and additional pages identified above.

I. NEXT INSPECTION

I/We recommend that this installation is furtherinspected and tested after an interval of not more than 5 Years (Enter interval in terms of

years, months or weeks, as appropriate)

provided that any items at F which have been attributed a Classification code C1 (danger present) are remedied immediately and that any itemswhich have been attributed a code C2 (potentially dangerous) or FI (further investigation required without delay) are remedied or investigatedrespectively as a matter of urgency. Items which have been attributed a Classification code C3 should be improved as soon aspracticable (see F).

J. DETAILS OF NICEIC APPROVED CONTRACTOR

Trading Title: Electrical Test (Midlands) Ltd

Address: 110B Walsall RoadCannock

Postcode:WS11 0JB

Telephone number: 01922 710014

Email Address: [email protected]

Enrolment number:(Essential information)

035056

Branch number:(if applicable)

N/A

K. SUPPLY CHARACTERISTICS AND EARTHING ARRANGEMENTS

System Type(s) Number and Type of Live Conductors Nature of Supply Parameters

Characteristics of Primary SupplyOvercurrent Protective Device(s)

TN-S á

TN-C-S N/A

TN-C N/A

TT N/A

IT N/A

1-phase(2 wire) N/A

2-phase(3 wire) N/A

3-phase(3 wire) N/A

1-phase(3 wire) N/A

3-phase(4 wire) á

a.c. á d.c. N/A

2 pole N/A

3 pole N/A

otherN/A

N/AOther

NominalVoltage(s): Uþ 415

VN/A

UÒþ V

Nominalfrequency, fþ

50Hz

Prospective faultcurrent, IÙÄÅ

4.2kA

External earth faultloop impendance, Ñ Å Ç

0.11É

1Number ofsources

Notes:(1) by enquiry

(2) by enquiry or bymeasurement

(3) where more thanone supply, recordthe higher or highestvalues

(4) by measurement

BS(EN) LIM

Type LIM

Rated current LIM A

LIM kAShort-circuitcapacity

Confirmation ofsupply polarity á (á)

L. PARTICULARS OF INSTALLATION AT THE ORIGINMeans of Earthing Details of Installation Earth Electrode (where applicable)

Main Switch/Switch-Fuse/Circuit-Breaker/RCD

Distributor'sfacility: á

Installationearth electrode: N/A

Type:(eg rod(s),tape(s))

N/A

Electroderesistance, RÕ:

N/A (É)

Location: N/A

Method ofmeasurement:

N/A

* (applicable only where an RCD is suitable and is used as a main circuit-breaker)

BS 88 Fuse HType:BS(EN)

3No ofPoles

CopperPrimary supplyconductorsmaterial

70.0Primary supplyconductorscsa

mmâ

Voltagerating

415

Ratedcurrent,IÐ

160

RCD operatingcurrent, IÜ *

N/A

Rated timedelay*

N/A

RCD operatingtime (at IÜ )*

N/A

V

A

mA

ms

ms

Earthing conductor Main protective bonding conductors Bonding of extraneous-conductive-parts (á)

Earthing and protective bonding conductors

Conductormaterial

Copper Conductormaterial

Copper

Conductorcsa

35.0 mmâConductor

csa16.0 mmâ

Connection/ ácontinuityverified

Connection/ ácontinuityverified

(á) (á)

Waterinstallation pipes á

Oilinstallation pipes N/A

Gasinstallation pipes á

Lightningprotection N/A

Structuralsteel á

OtherN/A

This report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

Please see the 'Notes for Recipients'

Page 5: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

ELECTRICAL INSTALLATION CONDITION REPORT

This report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

INSPECTION SCHEDULE FOR DISTRIBUTION BOARDS AND CIRCUITS

Item Description Outcome* Location reference

* All Outcome boxes must be completed'á' indicates Acceptable condition'LIM' indicates a Limitation'N/A' indicates Not applicable

Unacceptable condition state C1 or C2Improvement recommended state C3Further investigation required without delaystate FI(to determine whether danger or potential danger exists)

OutcomeProvide additional comment where appropriate onattached numbered sheets. C1, C2, C3 and FI codeditems to be recorded in Section F of the report.

Page 4 of 65

1.0 Condition/adequacy of distributor's/supply intake equipmentÚ

1.1 Service cable LIM

1.2 Service head LIM

1.3 Distributor's earthing arrangement(s) LIM

1.4 Meter tails - Distributor/ Consumer LIM

1.5 Metering equipment LIM

1.6 Means of main isolation (where present) LIM

2.0 Presence of adequate arrangements for parallel or switched alternative sources

2.1 Adequate arrangements where a generating set operates as a switched alternative to the public supply N/A

2.2 Adequate arrangements where a generating set operates in parallel with the public supply N/A

3.0 Automatic disconnection of supply

3.1 Main earthing and bonding arrangements

Presence and condition of distributor's earthing arrangement áPresence and condition of earth electrode arrangement N/A

Adequacy of earthing conductor size áAdequacy of earthing conductor connections áAccessibility of earthing conductor connections áAdequacy of main protective bonding conductor size(s) áAdequacy of main protective bonding conductor connections áAccessibility of main protective bonding connections áAccessibility and condition of other protective bonding connections áProvision of earthing/bonding labels at all appropriate locations á

3.2 FELV

Source providing at least simple separation N/A

Plugs, socket-outlets and the like not interchangeable with those of other systems within the premises N/A

3.3 Reduced low voltage

Adequacy of source N/A

Plugs, socket-outlets and the like not interchangeable with those of other systems within the premises N/A

4.0 Other methods of protection (where the methods of protection listed below are employed, details should be provided on separate sheets)

4.1 Double insulation á4.2 Reinforced insulation á4.3 Use of obstacles á4.4 Placing out of reach á4.5 Non-conducting location á4.6 Earth-free local equipotential bonding á4.7 Electrical separation for more than one item of equipment á

5.0 Distribution equipment

5.1 Adequacy of working space/accessibility of equipment á5.2 Security of fixing á5.3 Condition of insulation of live parts á5.4 Adequacy/security of barriers á5.5 Condition of enclosure(s) in terms of IP rating C2

5.6 Condition of enclosure(s) in terms of fire rating C2

5.7 Enclosure not damaged/deteriorated so as to impair safety C2

5.8 Presence of main switch(es), linked where required á5.9 Operation of main switch(es) (functional check) á5.10 Correct identification of circuit protective devices á5.11 Adequacy of protective devices for prospective fault current á5.12 RCD(s) provided for fault protection - includes RCBOs á5.13 RCD(s) provided for additional protection - includes RCBOs C2

Page 6: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

ELECTRICAL INSTALLATION CONDITION REPORT

This report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

INSPECTION SCHEDULE FOR DISTRIBUTION BOARDS AND CIRCUITS

Item Description Outcome* Location reference

* All Outcome boxes must be completed'á' indicates Acceptable condition'LIM' indicates a Limitation'N/A' indicates Not applicable

Unacceptable condition state C1 or C2Improvement recommended state C3Further investigation required without delaystate FI(to determine whether danger or potential danger exists)

OutcomeProvide additional comment where appropriate onattached numbered sheets. C1, C2, C3 and FI codeditems to be recorded in Section F of the report.

Page 5 of 65

5.14 RCD(s) provided for protection against fire - includes RCBOs N/A

5.15 Manual operation of circuit-breakers and RCDs to prove disconnection á5.16 Presence of RCD retest notice at or near equipment where required á5.17 Presence of diagrams, charts or schedules at or near equipment, where required á5.18 Presence of non-standard (mixed) cable colour warning notice at or near equipment where required á5.19 Presence of alternative/additional supply arrangement warning notice(s) at or near equipment where required N/A

5.20 Presence of replacement next inspection recommendation label á5.21 Presence of other required labelling (specify) N/A

5.22 Examination of protective device(s) and base(s); correct type and rating (no signs of unacceptable thermal damage, arcing or overheating)

á5.23 Single-pole switching or protective devices in line conductors only á5.24 Protection against mechanical damage where cables enter equipment á5.25 Protection against electromagnetic effects where cables enter metallic enclosures á

6.0 Distribution/final circuits

6.1 Identification of conductors á6.2 Cables correctly supported throughout their length C3

6.3 Condition of insulation of live parts á6.4 Non-sheathed cables protected by enclosure in conduit, ducting or trunking á6.5 Suitability of containment systems for continued use (including flexible conduit) á6.6 Cables correctly terminated in enclosures (indicate extent of sampling in Section D of report) á6.7 Confirmation of indication that SPD(s) are functional á6.8 Confirmation that ALL conductor connections, including connections to busbars are correctly located in terminals and

are tight and secureá

6.9 Examination of cables for signs of unacceptable thermal and mechanical damage/deterioration á6.10 Adequacy of cables for current-carrying capacity with regard to the type and nature of installation C3

6.11 Adequacy of protective devices; type and rated current for fault protection á6.12 Presence and adequacy of circuit protective conductors á6.13 Co-ordination between conductors and overload protective devices N/A

6.14 Cable installation methods/practices appropriate to the type and nature of installation and external influences LIM

6.15 Cables where exposed to direct sunlight, of a suitable type N/A

6.16 Cables installed under floors, above ceilings, in walls / partitions, adequately protected against damage

installed in prescribed zones (see Section D. Extent and limitations) N/A

incorporating earthed armour or sheath, or installed within earthed wiring system, or otherwise protected against mechanical damage by nails, screws and the like (see Section D. Extent and limitations)

N/A

6.17 Provision of additional protection by 30 mA RCD

Ú for mobile equipment not exceeding a rating of 32 A for use outdoors C2

Ú for all socket-outlets of rating 20 A or less, unless exempt C3

Ú for cables installed in walls / partitions at a depth of less than 50 mm C3

Ú for cables installed in walls / partitions containing metal parts regardless of depth C3

6.18 Provision of fire barriers, sealing arrangements and protection against thermal effects á6.19 Band II cables segregated/separated from Band I cables á6.20 Cables segregated/separated from non-electrical services á6.21 Termination of cables at enclosures (identify numbers and locations of items inspected in Section D)

Connections under no undue strain áNo basic insulation of a conductor visible outside an enclosure áConnections of live conductors adequately enclosed áAdequacy of connection at point of entry to enclosure (gland, bush or similar) á

6.22 General condition of wiring systems á6.23 Temperature rating of cable insulation á6.24 Condition of accessories including socket-outlets, switches and joint boxes C3

6.25 Suitability of accessories for external influences á6.26 Single-pole switching or protective devices in line conductors only N/A

6.27 Adequacy of connections, including cpcs, within accessories and to fixed and stationary equipment - identify /record numbers and locations of items inspected

N/A

Page 7: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

ELECTRICAL INSTALLATION CONDITION REPORT

This report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

INSPECTION SCHEDULE FOR DISTRIBUTION BOARDS AND CIRCUITS

Item Description Outcome* Location reference

* All Outcome boxes must be completed'á' indicates Acceptable condition'LIM' indicates a Limitation'N/A' indicates Not applicable

Unacceptable condition state C1 or C2Improvement recommended state C3Further investigation required without delaystate FI(to determine whether danger or potential danger exists)

OutcomeProvide additional comment where appropriate onattached numbered sheets. C1, C2, C3 and FI codeditems to be recorded in Section F of the report.

Page 6 of 65

7.0 Isolation and switching

7.1 Isolators

presence and condition of appropriate devices áacceptable location (state if local or remote) ácapable of being secured in the OFF position ácorrect operation verified áclearly identified by position and/or durable marking(s) áWarning label posted in situations where live parts cannot be isolated by the operation of a single device á

7.2 Switching off for mechanical maintenance

presence and condition of appropriate devices áacceptable location ácapable of being secured in the OFF position ácorrect operation verified áclearly identified by position and/or durable marking(s) á

7.3 Emergency switching/stopping

presence and condition of appropriate devices áreadily accessible for operation where danger might occur ácorrect operation verified áclearly identified by position and/or durable marking(s) á

7.4 Functional switching

presence and condition of appropriate devices ácorrect operation verified á

8.0 Current-using equipment (permanently connected)

8.1 Condition of equipment in terms of IP rating á8.2 Equipment does not constitute a fire hazard á8.3 Enclosure not damaged/deteriorated so as to impair safety á8.4 Suitability for the environment and external influences á8.5 Security of fixing á8.6 Cable entry holes in ceiling above luminaires, sized or sealed so as to restrict the spread of fire (indicate extent of

sampling in Section D of report)LIM

8.7 Recessed luminaires (e.g. downlighters)

correct type of lamps fitted N/A

installed to minimise build-up of heat by use of "fire rated" fittings, insulation displacement box or similar N/A

no signs of overheating to surrounding building fabric N/A

no signs of overheating to conductors/terminations N/A

9.0 Location(s) containing a bath or shower

9.1 Additional protection by RCD not exceeding 30 mA

for low voltage circuits serving the location N/A

for low voltage circuits passing through Zone 1 and Zone 2 not serving the location N/A

9.2 Where used as a protective measure, requirements for SELV or PELV are met N/A

9.3 Shaver sockets comply with BS EN 61558-2-5 or BS 3535 N/A

9.4 Presence of supplementary bonding conductors unless not required by BS 7671: 2008 N/A

9.5 Low voltage (e.g. 230 volts) socket-outlets sited at least 3 m from zone 1 N/A

9.6 Suitability of equipment for external influences for installed location in terms of IP rating N/A

9.7 Suitability of equipment for installation in a particular zone N/A

9.8 Suitability of current-using equipment for a particular position within the location N/A

10.0 Other special installations or locations

List special locations present, if any. List the results of particular inspections applied (a separate page is required for each location). N/A

N/A

N/A

N/A

N/A

N/A

Page 8: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 7 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

TOWER

Distributionboard designation: MAIN SWITCH

Supply to distributionboard is from: ORIGIN No of

phases: 3 Nominalvoltage: 415 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) LIM Rating: LIM A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L123 Supply to: DB MP D B 1 70.0 35.0 0.1 88 Fuse HRC 2 160 80 - 0.27

Page 9: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 8 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.11 É

IÙ 4.2 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 11/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L123 - - - 0.02 - 200 200 200 200 á 0.13 - -

Page 10: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 9 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

TOWER

Distributionboard designation: DB MP

Supply to distributionboard is from: MAIN SWITCH No of

phases: 3 Nominalvoltage: 415 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 88 Rating: 160 A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

FP200

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L123 Spare F E 1 35.0 25.0 C.S 5 60947-2 MCCB 2 100 36 - N/A

2L123 Supply to: DB K F C 1 35.0 16.0 C.S 5 60947-2 MCCB 2 63 36 - N/A

3L123 Supply to: DB 2 (EX) B B 1 16.0 M/F 5 60947-2 MCCB 2 63 36 - N/A

4L123 Supply to: DB1 (N) F C 1 35.0 C.S 5 60947-2 MCCB 2 63 36 - N/A

5L123 Supply to: DB1 (EX) B B 1 16.0 6.0 5 60947-2 MCCB 2 63 36 - N/A

6L123 Supply to: DB BH F E 1 25.0 C.S 5 60947-2 MCCB 2 50 36 - N/A

7L1 Supply to: DB 1A (N) F E 1 35.0 35.0 5 60947-2 MCCB 2 63 25 - N/A

7L2 Supply to: DB 1D (N) F E 1 35.0 35.0 5 60947-2 MCCB 2 63 25 - N/A

7L3 Supply to: DB 3 F E 1 35.0 C.S 5 60947-2 MCCB 2 63 25 - N/A

8L1 Supply to: DB 1C (N) F E 1 35.0 35.0 5 60947-2 MCCB 2 63 25 - N/A

8L2 Supply to: DB 1B (N) F E 1 35.0 35.0 5 60947-2 MCCB 2 63 25 - N/A

8L3 SPARE - - - - - - - - - - - -

9L1 FIRE ALARM JUNIOR O E 1 2.5 2.5 0.4 60947-2 MCCB 2 20 65 - N/A

9L2 SPARE - - - - - - - - - - - -

9L3 SPARE - - - - - - - - - - - -

10L1 FIRE ALARM INFANTS O E 1 2.5 2.5 0.4 60947-2 MCCB 2 20 65 - N/A

10L2 Spare - - - - - - - - - - - -

10L3 Spare - - - - - - - - - - - -

11L123 Spare - - - - - - - - - - - -

12L123 Spare - - - - - - - - - - - -

Page 11: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 10 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.13 É

IÙ 3.54 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 11/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L123 - - - 0.05 - 200 200 200 200 á 0.18 - -

2L123 - - - 0.03 - 200 200 200 200 á 0.16 - -

3L123 - - - 0.11 - 200 200 200 200 á 0.24 - -

4L123 - - - 0.11 - 200 200 200 200 á 0.24 - -

5L123 - - - 0.10 - 200 200 200 200 á 0.23 - -

6L123 - - - 0.06 - 200 200 200 200 á 0.19 - -

7L1 - - - 0.07 - - 200 200 200 á 0.20 - -

7L2 - - - 0.06 - - 200 200 200 á 0.19 - -

7L3 - - - 0.16 - - 200 200 200 á 0.29 - -

8L1 - - - 0.04 - - 200 200 200 á 0.17 - -

8L2 - - - 0.08 - - 200 200 200 á 0.21 - -

8L3 - - - - - - - - - - - -

9L1 - - - 0.30 - - - 200 200 á 0.43 - -

9L2 - - - - - - - - - - - -

9L3 - - - - - - - - - - - -

10L1 - - - 0.49 - - - 200 200 á 0.62 - -

10L2 - - - - - - - - - - - -

10L3 - - - - - - - - - - - -

11L123 - - - - - - - - - - - -

12L123 - - - - - - - - - - - -

Page 12: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 11 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

ROOM 002

Distributionboard designation: DB R

Supply to distributionboard is from: DB MP No of

phases: 3 Nominalvoltage: 415 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60947 - 2 Rating: - A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L1 Spare A B 8 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

1L2 SPUR ADJ DB A B 1 2.5 1.5 0.4 60898 MCB B 10 10 - 4.37

1L3 LTS 013 A C 6 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

2L1 SKTS + SPUR 005 + 008 A B 3 2.5 1.5 0 61009 RCD/RCBO C 20 10 30 1.09

2L2 SKTS 007 + 008 A B 6 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 20 10 30 1.09

2L3 SKTS 002 + 003 A B 2 2.5 1.5 0.4 61009 RCD/RCBO C 20 10 30 1.09

3L1 SPUR 009 A B 1 2.5 1.5 0.4 60898 MCB B 16 10 - 2.73

3L2 AUTO DOOR A C 1 2.5 1.5 0 60898 MCB B 20 10 - 2.19

3L3 BLANK PLATE ABOVE SINK 010 A C 1 2.5 1.5 0.4 60898 MCB B 16 10 - 2.73

4L1 SPUR 006 A C 1 2X 2.5 2X 1.5 0.4 60898 MCB B 16 10 - 2.73

4L2 Spare - - - - - - - - - - - -

4L3 Supply to: DB R2 A C 1 6.0 2.5 5 60898 MCB B 32 10 - 1.37

5L1 HALL BLINDS A C 2 2X 2.5 2X 1.5 0.4 60898 MCB B 32 10 - 1.37

5L2 SPUR FOR DOOR MASS A B 1 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

5L3 Supply to: DB R1 A C 1 16.0 6.0 5 60898 MCB B 63 10 - 0.69

6L123 Spare - - - - - - - - - - - -

7L1 LTS 030A A B 20 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

7L2 LTS 002, 003, 004 A B 12 3X 1.5 3X 1.0 0.4 60898 MCB B 10 10 - 4.37

7L3 LTS 030A A B 7 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

8L1 LTS 005+006 A B 4 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

8L2 LTS CORRIDOR A C 9 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

8L3 LTS 007, 008, 009 A C 11 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

9L1 HALL WINDOWS 030 A B 1 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

9L2 COTU SPUR 005 A B 1 2.5 1.5 0.4 60898 MCB B 10 10 - 4.37

9L3 Spare - - - - - - - - - - - -

10L1 DADO SKTS 002 + CORRIDOR C B 7 2X 2.5 2X 2.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

10L2 ALARM SPUR 003 A B 1 2.5 1.5 0.4 60898 MCB B 16 10 - 2.73

10L3 WATER HTR STAFFROOM A B 1 2.5 1.5 0 61009 RCD/RCBO C 16 10 30 1.37

11L1 Spare - - - - - - - - - - - -

Page 13: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 12 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.18 É

IÙ 2.56 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 11/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L1 0.94 0.95 1.52 0.84 - - - 200 200 á 1.02 31.4 30.2 á

1L2 - - - 0.09 - - - 200 200 á 0.27 - -

1L3 - - - 1.24 - - - 200 200 á 1.42 - -

2L1 - - - 0.41 - - - 200 200 á 0.59 33.3 31.7 á

2L2 - - - 0.36 - - - 200 200 á 0.54 34.5 30.9 á

2L3 - - - 0.80 - - - 200 200 á 0.98 28.8 28.6 á

3L1 - - - 0.41 - - - 200 200 á 0.59 - -

3L2 - - - 0.25 - - - 200 200 á 0.43 - -

3L3 - - - 0.39 - - - 200 200 á 0.57 - -

4L1 - - - 0.42 - - - 200 200 á 0.60 - -

4L2 - - - - - - - - - - - -

4L3 - - - 0.14 200 200 200 á 0.32 - -

5L1 0.50 0.53 0.88 LIM - - - 200 200 LIM - -

5L2 - - - 0.13 - - - 200 200 á 0.31 - -

5L3 - - - 0.02 - - 200 200 200 á 0.20 - -

6L123 - - - - - - - - - - - -

7L1 - - - 0.66 - - - 200 200 á 0.84 - -

7L2 - - - 0.54 - - - 200 200 á 0.72 - -

7L3 - - - 0.75 - - - 200 200 á 0.93 - -

8L1 - - - 0.86 - - - 200 200 á 1.04 - -

8L2 - - - LIM - - - 200 200 LIM - -

8L3 - - - 0.94 - - - 200 200 á 1.12 - -

9L1 - - - 0.56 - - - 200 200 á 0.74 - -

9L2 - - - 0.63 - - - 200 200 á 0.81 - -

9L3 - - - - - - - - - - - -

10L1 0.38 0.38 0.40 0.29 - - - 200 200 á 0.47 28.6 28.6 á

10L2 - - - 0.71 - - - 200 200 á 0.89 - -

10L3 - - - 0.37 - - - 200 200 á 0.55 28.6 28.6 á

11L1 - - - - - - - - - - - -

Page 14: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 13 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

ROOM 002

Distributionboard designation: DB R

Supply to distributionboard is from: DB MP No of

phases: 3 Nominalvoltage: 415 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60947 - 2 Rating: - A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

11L2 SKSTS + SPURS 014 A C 5 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

11L3 SWITCHED OFF A B LIM 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

12L1 LTS CORRIDOR 029 A C 5 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

12L2 LTS CORRIDOR 012, 001 A C 13 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

12L3 LTS CORRIDOR 015 A C 9 1.5 1.0 0 60898 MCB B 10 10 - 4.37

13 - 16 Spare - - - - - - - - - - - -

Page 15: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 14 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.18 É

IÙ 2.56 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 11/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

11L2 0.44 0.44 0.76 0.45 - - - 200 200 á 0.63 28.9 28.4 á

11L3 LIM LIM LIM LIM - - - - - LIM LIM LIM

12L1 - - - LIM - - - 200 200 LIM - -

12L2 - - - LIM - - - 200 200 LIM - -

12L3 - - - LIM - - - 200 200 LIM - -

13 - 16 - - - - - - - - - - - -

Page 16: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 15 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

ROOM 13

Distributionboard designation: DB R2

Supply to distributionboard is from: DB R No of

phases: 1 Nominalvoltage: 230 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60898 Rating: 32 A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L3 SPARE - - - - - - - - - - - -

2L3 SKTS BY DOOR A B 2 4.0 1.5 0.4 60898 MCB B 32 6 - 1.37

3L3 SPARE - - - - - - - - - - - -

4L3 DATA CAB A B 1 4.0 1.5 0.4 60898 MCB B 32 6 - 1.37

5L3 SPARE - - - - - - - - - - - -

6L3 WINDOWS SPUR A B 1 2.5 1.5 0.4 60898 MCB B 16 6 - 2.73

Page 17: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 16 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.32 É

IÙ 0.72 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 11/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L3 - - - - - - - - - - - -

2L3 - - - 0.30 - - - 200 200 á 0.62 - -

3L3 - - - - - - - - - - - -

4L3 - - - 0.27 - - - 200 200 á 0.59 - -

5L3 - - - - - - - - - - - -

6L3 - - - 0.10 - - - 200 200 á 0.42 - -

Page 18: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 17 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

ROOM 002

Distributionboard designation: DB R1

Supply to distributionboard is from: DB R No of

phases: 1 Nominalvoltage: 230 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60898 Rating: 63 A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L3 COOKER ROOM 010 A C 1 10.0 4.0 0.4 61009 RCD/RCBO C 32 10 30 0.68

2L3 HOB ROOM 010 A C 1 6.0 2.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

3L3 SKTS + SPUR RMS 009+010 A C 6 2 X 2.5 2 X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

4L3 WATER HTR ROOM 010 A C 1 2.5 1.5 0.4 61009 RCD/RCBO C 16 10 30 1.37

5L3 LTS ROOM 010 A C 2 1.5 1.0 0.4 61009 RCD/RCBO C 6 10 30 3.64

6L3 SKTS STAFFROOM KITCHEN A C 5 2 X 2.5 2 X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

Page 19: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 18 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.20 É

IÙ 1.15 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 11/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L3 - - - 0.29 - - - 200 200 á 0.49 30.2 15.5 á

2L3 - - - 0.33 - - - 200 200 á 0.53 30.2 15.6 á

3L3 0.24 0.24 0.42 0.36 - - - 200 200 á 0.56 33.6 20.2 á

4L3 - - - 0.51 - - - 200 200 á 0.71 30.8 16.1 á

5L3 - - - 0.85 - - - 200 200 á 1.05 30.9 16.3 á

6L3 0.33 0.33 0.53 0.25 - - - 200 200 á 0.45 28.8 28.8 á

Page 20: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 19 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

KITCHEN ROOM STORE

Distributionboard designation: DB K

Supply to distributionboard is from: DB MP No of

phases: 3 Nominalvoltage: 415 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) -

Type:BS(EN) 60947-2 Rating: 63 A RCD No

of poles: - IÜ - mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

FP200

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L123 Spare - - - - - - - - - - - -

2L1 CCTV SPUR ADJ DB A B 1 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

2L2 OVEN+WATER CARE SPUR O C 2 2.5 2.5 0.4 60898 MCB C 20 10 - 1.09

2L3 BAIN MARIE No1 O C 1 4.0 4.0 0.4 61009 RCD/RCBO B 32 6 30 1.37

3L1 BAIN MARIE No2 O C 1 4.0 4.0 0.4 61009 RCD/RCBO B 32 6 30 1.37

3L2 SAS VALVE B B 1 2.5 2.5 0.4 60898 MCB B 16 10 - 2.73

3L3 RCD SKTS L/H/S + WINDOW B B 4 2.5 M.F 0.4 60898 MCB B 20 10 - 2.19

4L123 DISHWASHER F C 1 6.0 C.S 0.4 60898 MCB C 32 10 - 0.68

5L123 MAIN EXTRACT B B 1 4.0 M.F 0.4 60898 MCB C 10 10 - 2.19

6L123 SMALL EXTRACT B B 1 4.0 M.F 0.4 60898 MCB C 10 10 - 2.19

7L1 LTS KITCHEN +TOWIN B B 22 3X 1.5 M.F 0.4 60898 MCB B 20 10 - 2.19

7L2 SKT ROOM 078D A B 1 2.5 1.5 0.4 60898 MCB B 20 10 - 2.19

7L3 Spare - - - - - - - - - - - -

8L1 OVEN FAN SPURS 0 B 3 2.5 2.5 0.4 60898 MCB B 16 10 - 2.73

8L2 SKTS ADJ 078D A C 3 2.5 1.5 0.4 61009 RCD/RCBO B 20 10 30 2.19

8L3 Spare - - - - - - - - - - - -

9L123 Spare - - - - - - - - - - - -

10L1 Spare - - - - - - - - - - - -

10L2 WINDOW SPUR A B 1 1.5 1.0 0.4 60898 MCB C 10 10 - 2.19

10L3 MIXER O C 1 2.5 2.5 0.4 60898 MCB B 20 10 - 2.19

11L1 RCD SKTS L/H/S 078E O C 2 4.0 4.0 0.4 60898 MCB B 32 10 - 1.37

11L2 RCD SKTS R/H/S 078E O C 2 4.0 4.0 0.4 60898 MCB B 20 10 - 2.19

11L3 OLD CONTROLLER B B 1 2.5 M.F 0.4 61009 RCD/RCBO C 16 10 30 1.37

12L1 ISOLATER L/H/S 078 B B 1 4.0 M.F 0.4 60898 MCB B 20 10 - 2.19

12L2 Spare - - - - - - - - - - - -

12L3 FIRDGE + STAFFROOM SKTS B B 6 2.5 M.F 0.4 60898 MCB B 20 10 - 2.19

Page 21: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 20 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.16 É

IÙ 2.88 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 09/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L123 - - - - - - - - - - - -

2L1 - - - 0.11 - - - 200 200 á 0.27 - -

2L2 - - - 0.19 - - - 200 200 á 0.35 - -

2L3 - - - 0.26 - - - 200 200 á 0.42 38.4 10.2 á

3L1 - - - 0.31 - - - 200 200 á 0.47 38.4 10.2 á

3L2 - - - 0.14 - - - 200 200 á 0.30 - -

3L3 - - - 0.29 - - - 200 200 á 0.45 - -

4L123 - - - 0.07 - 200 - 200 200 á 0.23 - -

5L123 - - - 0.20 - 200 - 200 200 á 0.36 - -

6L123 - - - 0.15 - 200 - 200 200 á 0.31 - -

7L1 - - - 0.79 - - - 200 200 á 0.94 - -

7L2 - - - 0.35 - - - 200 200 á 0.51 - -

7L3 - - - - - - - - - - - -

8L1 - - - 0.28 - - - 200 200 á 0.43 - -

8L2 - - - 0.26 - - - 200 200 á 0.42 28.6 28.3 á

8L3 - - - - - - - - - - - -

9L123 - - - - - - - - - - - -

10L1 - - - - - - - - - - - -

10L2 - - - 0.32 - - - 200 200 á 0.48 - -

10L3 - - - 0.39 - - - 200 200 á 0.55 - -

11L1 - - - 0.67 - - - 200 200 á 0.83 - -

11L2 - - - 0.34 - - - 200 200 á 0.50 - -

11L3 - - - 0.15 - - - 200 200 á 0.31 38.3 10.2 á

12L1 - - - 0.19 - - - 200 200 á 0.34 - -

12L2 - - - - - - - - - - - -

12L3 - - - 0.25 - - - 200 200 á 0.41 - -

Page 22: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 21 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

ROOM 089

Distributionboard designation: DB 2 (EX)

Supply to distributionboard is from: DB MP No of

phases: 3 Nominalvoltage: 415 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60947-2 Rating: 63 A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L123 Spare - - - - - - - - - - - -

2L1 SKT ROOM 1388 VIA RCD A B 4 2 X 2.5 2 X 1.5 0.4 60898 MCB B 32 10 30 1.37

2L2 Supply to: DB 2B (EX) B B 1 10.0 M.F 5 60898 MCB B 50 10 - 0.87

2L3 Supply to: DB 2A (EX) B B 1 10.0 M.F 5 60898 MCB B 50 10 30 0.87

3L1 SPARE - - - - - - - - - - - -

3L2 SPARE - - - - - - - - - - - -

3L3 LTS ROOM 13813 A B 9 2 X 1.0 2 X 1.0 0.4 60898 MCB B 10 10 - 4.37

4L1 Supply to: DB 2E (EX) B B 1 6.0 M.F 5 60898 MCB B 32 10 - 1.37

4L2 Supply to: DB 2D (EX) B B 1 10.0 M.F 5 60898 MCB B 50 10 - 0.87

4L3 Supply to: DB 2C (EX) B B 1 10.0 M.F 5 60898 MCB B 50 10 - 0.87

Page 23: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 22 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.24 É

IÙ 1.92 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 07/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L123 - - - - - - - - - - - -

2L1 0.36 0.37 0.57 0.27 - - - 200 200 á 0.51 36.4 28.8 á

2L2 - - - 0.04 - - 200 200 200 á 0.28 - -

2L3 - - - 0.28 - - 200 200 200 á 0.52 - -

3L1 - - - - - - - - - - - -

3L2 - - - - - - - - - - - -

3L3 - - - 0.67 - - - 200 200 á 0.91 - -

4L1 - - - 0.09 - - 200 200 200 á 0.33 - -

4L2 - - - 0.11 - - - 200 200 0.35 - -

4L3 - - - 0.08 - - 200 200 200 á 0.32 - -

Page 24: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 23 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

ROOM 89

Distributionboard designation: DB 2B (EX)

Supply to distributionboard is from: DB 2 (EX) No of

phases: 1 Nominalvoltage: 230 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60898 Rating: 50 A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L2 SKTS ROOMS 085 + 087 B B 4 2 X 2.5 M/F 0.4 61009 RCD/RCBO B 32 10 30 -

2L2 Spare - - - - - - - - - - - -

3L2 Spare - - - - - - - - - - - -

4L2 TRANSFORMER ADJ OB A C 1 1.5 1.0 0.4 60898 MCB B 6 10 - 7.28

5L2 A.C COMMS ROOM F C 1 6.0 6.0 0.4 60898 MCB C 6 10 - 3.64

6L2 UNKNOWN O C L 2.5 2.5 0.4 60898 MCB B 10 10 - 4.37

7L2 Spare - - - - - - - - - - - -

8L2 Spare - - - - - - - - - - - -

Page 25: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 24 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.28 É

IÙ 0.82 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction 101266722

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 07/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L2 0.66 0.66 - 0.64 - - - 200 200 á 0.92 28.7 28.5 á

2L2 - - - - - - - - - - - -

3L2 - - - - - - - - - - - -

4L2 - - - 0.06 - - - 200 200 á 0.34 - -

5L2 - - - 0.23 - - - 200 200 á 0.51 - -

6L2 - - - LIM - - - 200 200 LIM - -

7L2 - - - - - - - - - - - -

8L2 - - - - - - - - - - - -

Page 26: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 25 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

STORE ROOM 084

Distributionboard designation: DB 2A (EX)

Supply to distributionboard is from: DB 2 (EX) No of

phases: 1 Nominalvoltage: 230 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60898 Rating: 50 A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L3 Spare B B 10 2X 2.5 2X 1.0 0.4 60898 MCB B 32 10 - 1.37

2L3 SKTS ROOMS 079, 081, 083 C B 12 2X 2.5 2X 2.5 0.4 61009 RCD/RCBO B 32 10 30 1.37

3L3 SKTS ROOMS 085 + 087 C B 8 2X 2.5 2X 2.5 0.4 61009 RCD/RCBO B 16 10 30 2.73

4L3 SKT BELOW DB H C 1 2.5 C.S 0.4 61009 RCD/RCBO B 16 10 30 2.73

5L3 Supply to: DB 2A-1 A B 1 10.0 4.0 5 60898 MCB B 50 10 - 0.87

6L123 Spare - - - - - - - - - - - -

Page 27: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 26 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.52 É

IÙ 0.44 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 08/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L3 0.97 0.96 1.67 0.46 - - - 200 200 á 0.98 - -

2L3 0.95 0.95 1.56 0.83 - - - 200 200 á 1.35 30.2 30.2 á

3L3 0.91 0.91 1.49 0.54 - - - 200 200 á 1.06 28.7 28.8 á

4L3 - - - 0.08 - - - 200 200 á 0.60 28.5 28.4 á

5L3 - - - 0.06 - - 200 200 200 á 0.58 - -

6L123 - - - - - - - - - - - -

Page 28: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 27 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

CORRIDOR 089

Distributionboard designation: DB 2A-1

Supply to distributionboard is from: DB 2A (EX) No of

phases: 1 Nominalvoltage: 230 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60898 Rating: 50 A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L3 DADO SKS 099 + CORRIDOR A B 13 3 X 2.5 3 X 1.5 0.4 61009 RCD/RCBO B 32 10 30 1.37

2L3 DADO SKTS 099A A B 5 4.0 1.5 0.4 61009 RCD/RCBO B 20 10 30 2.19

3L3 DOOR CLOSURES SKT IN LINK CORRIDOR A B 3 2.5 1.5 0.4 61009 RCD/RCBO C 20 10 30 1.09

4L3 LTS LINK CORRIDOR + TIME CLOCK A B 9 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

5L3 LTS CORRIDOR NEAR END C B 11 1.5 1.5 0.4 60898 MCB C 6 10 - 3.64

6L3 LTS CORRIDOR FAR END C B 13 1.5 1.5 0.4 60898 MCB C 6 10 - 3.64

Page 29: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 28 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.58 É

IÙ 0.40 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 09/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L3 0.13 0.14 0.27 0.40 - - - 200 200 á 0.98 28.3 30.2 á

2L3 - - - 0.47 - - - 200 200 á 1.05 28.8 28.7 á

3L3 - - - 0.79 - - - 200 200 á 1.37 28.2 15.2 á

4L3 - - - 0.55 - - - 200 200 á 1.13 - -

5L3 - - - 0.43 - - - 200 200 á 1.01 - -

6L3 - - - 0.76 - - - 200 200 á 1.34 - -

Page 30: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 29 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

ROOM 137

Distributionboard designation: DB 2E (EX)

Supply to distributionboard is from: DB 2 (EX) No of

phases: 1 Nominalvoltage: 230 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60898 Rating: 32 A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

FP200

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L1 SKTS THIS ROOM + CORRIDOR C/O B 3 3X 2.5 3X 2.5 0.4 61009 RCD/RCBO B 32 6 30 1.37

2L1 STERILISER A B 1 6.0 2.5 0.4 61009 RCD/RCBO B 32 6 30 1.37

3L1 EXTERNAL FAN A B 1 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

4L1 LTS THIS ROOM A B 2 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

5L1 DOOR MASS A B 1 2.5 1.5 0.4 60898 MCB B 6 10 - 7.28

6L1 SPARE - - - - - - - - - - - -

Page 31: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 30 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.33 É

IÙ 0.70 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 07/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L1 0.39 0.38 0.40 0.66 - - - 200 200 á 0.99 37.8 10.2 á

2L1 - - - 0.15 - - - 200 200 á 0.48 37.9 10.2 á

3L1 - - - 0.08 - - - 200 200 á 0.41 - -

4L1 - - - 0.41 - - - 200 200 á 0.74 - -

5L1 - - - 0.30 - - - 200 200 á 0.63 - -

6L1 - - - - - - - - - - - -

Page 32: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 31 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

STOREROOM

Distributionboard designation: DB 2D (EX)

Supply to distributionboard is from: DB 2 (EX) No of

phases: 1 Nominalvoltage: 230 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60898 Rating: 50 A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L1 SOCKETS IN 116,118 + 133 L/H/S B B 4 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO B 32 10 30 1.37

2L1 SKTS IN 114+116 R/H/S B B 3 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO B 32 10 30 1.37

3L1 SKTS + SPUR 131 B B 2 2X 2.5 H.F 0.4 61009 RCD/RCBO B 32 10 30 1.37

4L1 SKTS IN 116+118 C B 6 2X 2.5 2X 2.5 0.4 60898 MCB B 32 10 - -

5L1 SKT IN CORRIDOR H C 1 1.5 C/S 0.4 61009 RCD/RCBO B 16 10 30 2.73

6L1 SKTS IN 114 C B 3 2.5 2.5 0.4 61009 RCD/RCBO B 16 10 30 2.73

7L1 SPUR FOR WINDOWS 114 O C 1 2.5 2.5 0.4 60898 MCB B 16 10 - 2.73

8L1 SPUR FOR WINDOWS 116 O C 1 2.5 2.5 0.4 60898 MCB B 16 10 - 2.73

Page 33: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 32 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.35 É

IÙ 0.66 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266727

Insulationresistance 101266722

Continuity 101266722

RCD 101266727

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 07/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L1 0.68 0.68 1.12 0.62 - - - 200 200 á 0.97 31.4 30.2 á

2L1 0.62 0.63 1.01 0.61 200 200 á 0.96 28.5 28.7 á

3L1 0.67 0.67 - 0.54 - - - 200 200 á 0.89 30.2 28.5 á

4L1 0.73 0.72 0.71 0.48 - - - 200 200 á 0.83 - -

5L1 - - - 0.19 - - - 200 200 á 0.54 28.8 28.4 á

6L1 - - - 0.42 - - - 200 200 á 0.77 28.4 28.6 á

7L1 - - - LIM - - - 200 200 LIM - -

8L1 - - - 0.28 - - - 200 200 á 0.63 - -

Page 34: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 33 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

VISITOR W.C

Distributionboard designation: DB 2C (EX)

Supply to distributionboard is from: DB 2 (EX) No of

phases: 1 Nominalvoltage: 230 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60898 Rating: 50 A RCD No

of poles: N/A IÜ mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

FP200

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L3 SKT CORRIDOR + MAG LOCK C B/C 2 2.5 2.5 0.4 61009 RCD/RCBO C 20 10 30 1.09

2L3 SKTS OFFICE B/H B/C 3 2X 2.5 M.F 0.4 61009 RCD/RCBO B 32 10 30 1.37

3L3 DADO SKTS 104 E B 8 2X 4.0 2X 4.0 0.4 61009 RCD/RCBO B 32 10 30 1.37

4L3 SKTS HALL B 13 13 2X 2.5 M.F 0.4 61009 RCD/RCBO B 32 10 30 1.37

5L3 SKTS 104 L/H/S H C 1 1.5 C.S 0.4 61009 RCD/RCBO B 20 10 30 2.19

6L3 SKT BELOW DB B B 1 2.5 1.5 0.4 60898 MCB B 20 10 - 2.19

7L3 SKTS COILER ROOM A B 1 2.5 1.5 0.4 61009 RCD/RCBO B 20 10 30 2.19

8L3 SKTS 108 UNDER DESK O C 2 2.5 1.5 0.4 61009 RCD/RCBO B 20 10 30 2.19

9L3 32A SKT IN HALL F C 1 6.0 6.0 0.4 61009 RCD/RCBO B 32 10 30 1.37

10L3 DADO SKTS 110 + AUTO DOOR E B 9 2X 2.5 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

11L3 DADO SKTS 110 E B 6 2X 2.5 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

12L3 CCTV F.L.U IN HALL A C 1 2.5 1.5 0.4 60898 MCB B 10 10 30 4.37

Page 35: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 34 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.32 É

IÙ 0.72 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 08/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L3 - - - 0.17 - - - 200 200 á 0.49 30.3 10.3 á

2L3 0.53 0.54 - 0.47 - - - 200 200 á 0.79 23.7 30.2 á

3L3 - - - 0.19 - - - 200 200 á 0.51 28.3 28.4 á

4L3 0.39 0.39 - 0.40 - - - 200 200 á 0.72 31.4 28.2 á

5L3 - - - 0.36 - - - 200 200 á 0.68 28.7 28.3 á

6L3 - - - 0.05 - - - 200 200 á 0.37 - -

7L3 - - - 0.28 - - - 200 200 á 0.60 30.1 28.6 á

8L3 - - - 0.51 - - - 200 200 á 0.83 28.4 24.9 á

9L3 - - - 0.25 - - - 200 200 á 0.57 28.7 31.6 á

10L3 0.48 0.49 0.82 0.23 - - - 200 200 á 0.55 40.1 28.8 á

11L3 0.45 0.45 0.73 0.26 - - - 200 200 á 0.58 34.9 19.2 á

12L3 - - - LIM - - - 200 200 LIM - -

Page 36: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 35 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

ROOM 152 NURSERY

Distributionboard designation: DB1 (N)

Supply to distributionboard is from: DB MP No of

phases: 3 Nominalvoltage: 415 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60947-2 Rating: 63 A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

FP200

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L1 LTS ROOM 153 A C 6 1.5 1.0 0.4 60898 MCB C 10 10 - 2.19

1L2 LTS + FANS 154, 155, 156 A C 4 1.5 1.0 0.4 60898 MCB C 10 10 - 2.19

1L3 LTS 145, 146, 151A A C 7 1.5 1.0 0.4 60898 MCB C 10 10 - 2.19

2L1 LTS 144 A C 8 1.5 1.0 0.4 60898 MCB C 10 10 - 2.19

2L2 LTS ROW 5 1+2 ROOM 151 A C 8 1.5 1.0 0.4 60898 MCB C 10 10 - 2.19

2L3 LTS ROW 3 + HANGING ROOM 151 A C 6 1.5 1.0 0.4 60898 MCB C 10 10 - 2.19

3L1 LTS 149 + 150 A C 9 1.5 1.0 0.4 60898 MCB C 10 10 - 2.19

3L2 LTS 147, 148, + 151 A C 7 1.5 1.0 0.4 60898 MCB C 10 10 - 2.19

3L3 SPUR FAIR SIDE 151 A C 1 2.5 1.5 0.4 61009 RCD/RCBO C 20 10 30 1.09

4L1 SKT 140A A C 1 2.5 1.5 0.4 61009 RCD/RCBO C 20 10 30 1.09

4L2 HTR SPUR 140A NEAR A C 1 2.5 1.5 0.4 61009 RCD/RCBO C 20 10 30 1.09

4L3 WINDOW SPURS A C 11 2 X 2.5 2 X 1.5 0.4 60898 MCB B 32 10 - 1.37

5L1 KILN SUPPLY B B 1 6.0 M.F 0.4 61009 RCD/RCBO C 20 10 30 1.09

5L2 WATER HEATER 154 B B 1 2.5 M.F 0.4 61009 RCD/RCBO C 20 10 30 1.09

5L3 SKT THIS ROOM O C 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37

6L123 SPARE - - - - - - - - - - - -

7L1 LTS OFFICE, WC, LINK A C 9 1.5 1.0 0.4 60898 MCB C 10 10 - -

7L2 LTS 152 + OUTSIDE B B 4 1.5 M.F 0.4 60898 MCB B 10 10 - -

7L3 SKTS 141, 142, 143 B B 3 2X 2.5 M.F 0.4 61009 RCD/RCBO C 32 10 30 -

8L1 SPARE - - - - - - - - - - - -

8L2 SKTS 144 + 146 B B 6 2X 2.5 M.F 0.4 61009 RCD/RCBO C 32 10 30 -

8L3 SKTS + SPURS 153 B B 2 2X 2.5 M.F 0.4 61009 RCD/RCBO C 32 10 30 -

9L1 SKTS 151 A B 7 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 -

9L2 RCD SKT 153 O B 2 2X 2.5 2X 2.5 0.4 61009 RCD/RCBO C 32 10 30 -

9L3 COOKER 153 A C 1 6.0 2.5 0.4 61009 RCD/RCBO C 32 10 30 -

10L1 HTR SPUR 153 A C 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 -

10L2 WINDOW SPUR 143+153 A C 3 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 -

10L3 CCTV SPURS A C 2 2.5 2.5 0.4 60898 MCB B 10 10 30 -

11L123 SPARE - - - - - - - - - - - -

Page 37: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 36 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.24 É

IÙ 1.42 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 10/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L1 - - - 0.29 - - - 200 200 á 0.53 - -

1L2 - - - 0.40 - - - 200 200 á 0.64 - -

1L3 - - - 0.77 - - - 200 200 á 1.01 - -

2L1 - - - 0.70 - - - 200 200 á 0.94 - -

2L2 - - - 0.78 - - - 200 200 á 1.02 - -

2L3 - - - 0.81 - - - 200 200 á 1.05 - -

3L1 - - - 0.64 - - - 200 200 á 0.88 - -

3L2 - - - 0.68 - - - 200 200 á 0.92 - -

3L3 - - - 0.88 - - - 200 200 á 1.12 30.9 16.3 á

4L1 - - - 0.38 - - - 200 200 á 0.62 31.3 16.7 á

4L2 - - - 0.48 - - - 200 200 á 0.72 28.1 15.8 á

4L3 0.99 1.02 1.62 0.60 - - - 200 200 á 0.84 - -

5L1 - - - 0.14 - - - 200 200 á 0.38 30.2 15.9 á

5L2 - - - 0.22 - - - 200 200 á 0.46 38.6 10.3 á

5L3 - - - 0.08 - - - 200 200 á 0.32 51.1 18.7 á

6L123 - - - - - - - - - - - -

7L1 - - - 0.56 - - - 200 200 á 0.80 - -

7L2 - - - 0.60 - - - 200 200 á 0.84 - -

7L3 0.49 0.48 - 0.48 - - - 200 200 á 0.72 24.5 20.5 á

8L1 - - - - - - - - - - - -

8L2 0.77 0.77 - 0.82 - - - 200 200 á 1.06 38.7 18.1 á

8L3 0.21 0.22 - 0.40 - - - 200 200 á 0.64 31.6 16.4 á

9L1 0.62 0.63 1.01 0.45 - - - 200 200 á 0.69 40.3 35.2 á

9L2 0.11 0.11 0.08 0.58 - - - 200 200 á 0.82 34.3 16.9 á

9L3 - - - 0.26 - - - 200 200 á 0.50 37.1 16.2 á

10L1 - - - 0.11 - - - 200 200 á 35 28.7 16 á

10L2 - - - 0.28 - - - 200 200 á 0.52 30.7 16 á

10L3 - - - 0.47 - - - 200 200 á 0.71 - -

11L123 - - - - - - - - - - - -

Page 38: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 37 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

ROOM 152 NURSERY

Distributionboard designation: DB1 (N)

Supply to distributionboard is from: DB MP No of

phases: 3 Nominalvoltage: 415 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60947-2 Rating: 63 A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

FP200

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

12L123 SPARE - - - - - - - - - - - -

Page 39: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 38 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.24 É

IÙ 1.42 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 10/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

12L123 - - - - - - - - - - - -

Page 40: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 39 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

ROOM 090

Distributionboard designation: DB1 (EX)

Supply to distributionboard is from: DB MP No of

phases: 3 Nominalvoltage: 415 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60942 Rating: 63 A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L1 Spare - - - - - - - - - - - -

1L2 DATA CAB A B 1 4.0 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

1L3 SKT COMMS ROOM A C 1 2.5 1.5 0.4 61009 RCD/RCBO C 20 10 30 1.09

2L1 DADO SKTS THIS ROOM A B 10 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

2L2 Supply to: DB 1D (EX) F B 1 10.0 10.0 5 60898 MCB B 32 10 - 1.37

2L3 Supply to: DB 1E (EX) D B 1 10.0 M.F 5 60898 MCB B 40 10 - 1.09

3L1 DOOR MAG A B 1 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

3L2 SKT CLOAK ALARM + SPUR H C 2 1.5 C.S 0.4 61009 RCD/RCBO C 20 10 30 1.09

3L3 DESK SKT COMP ROOM A C 1 2.5 1.5 0.4 61009 RCD/RCBO C 20 10 30 1.09

4L1 Supply to: DB 1B (EX) D B 1 10.0 M.F 5 60898 MCB B 40 10 - 1.09

4L2 Supply to: DB1 C (EX) D B 1 10.0 M.F 5 60898 MCB B 40 10 - 1.09

4L3 Supply to: DB1A (EX) D B 1 10.0 M.F 5 60898 MCB B 40 10 - 1.09

Page 41: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 40 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.23 É

IÙ 2.00 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 07/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L1 - - - - - - - - - - - -

1L2 - - - 0.23 - - - 200 200 á 0.46 28.8 28.8 á

1L3 - - - 0.30 - - - 200 200 á 0.53 28.5 28.4 á

2L1 0.21 0.21 0.29 0.37 - - - 200 200 á 0.59 28.4 28.7 á

2L2 - - - 0.11 - - 200 200 200 á 0.34 - -

2L3 - - - 0.31 - - 200 200 200 á 0.54 - -

3L1 - - - 0.06 - - - 200 200 á 0.29 - -

3L2 - - - 0.32 - - - 200 200 á 0.55 28.8 28.8 á

3L3 - - - 0.42 - - - 200 200 á 0.64 31.9 30.4 á

4L1 - - - 0.12 - - 200 200 200 á 0.35 - -

4L2 - - - 0.15 - - 200 200 200 á 0.38 - -

4L3 - - - 0.22 - - 200 200 200 á 0.45 - -

Page 42: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 41 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

STOREROOM

Distributionboard designation: DB 1D (EX)

Supply to distributionboard is from: DB1 (EX) No of

phases: 1 Nominalvoltage: 230 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60898 Rating: 32 A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L2 LTS STOKE 115 B B 2 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

2L2 LTS 114 FAR B B 6 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

3L2 LTS 114 NEAR B B 6 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

4L2 LTS 116 B B 9 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

5L2 LTS 118 B B 9 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

6L2 AUTO DOOR O C 1 2.5 2.5 0.4 60898 MCB B 16 10 - 2.73

7L2 CCTV O C 1 2.5 2.5 0.4 60898 MCB B 10 10 - 4.37

8L2 Spare - - - - - - - - - - - -

Page 43: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 42 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.34 É

IÙ 0.68 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101260727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 07/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L2 - - - 0.09 - - - 200 200 á 0.43 - -

2L2 - - - 0.21 - - - 200 200 á 0.55 - -

3L2 - - - 0.23 - - - 200 200 á 0.57 - -

4L2 - - - 0.27 - - - 200 200 á 0.61 - -

5L2 - - - 0.48 - - - 200 200 á 0.82 - -

6L2 - - - 0.16 - - - 200 200 á 0.50 - -

7L2 - - - LIM - - - 200 200 á LIM - -

8L2

Page 44: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 43 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

ROOM 136

Distributionboard designation: DB 1E (EX)

Supply to distributionboard is from: DB1 (EX) No of

phases: 1 Nominalvoltage: 230 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60898 Rating: 40 A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

FP200

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L3 SKT + SPUR 131 O C 3 2.5 2.5 0.4 61009 RCD/RCBO B 16 10 30 2.73

2L3 RCD SPUR BEOW DB B B 1 2.5 2.5 0.4 60898 MCB B 16 10 30 2.73

3L3 SKT 133 O C 2 2.5 2.5 0.4 61009 RCD/RCBO B 16 10 30 2.73

4L3 LTS 135,135B,136 B B 6 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

5L3 LTS 131,131A + LOBBY B B 3 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

6L3 LTS 131 BCD, 132 , 133 , 134 , + 134A B B 9 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

7L3 Spare - - - - - - - - - - - -

8L3 Spare - - - - - - - - - - - -

9L3 Spare - - - - - - - - - - - -

10L3 LTS CORRIDOR C B 10 1.0 1.0 0.4 60898 MCB C 6 10 - 3.64

11L3 LTS CORRIDOR C B 6 1.0 1.0 0.4 60898 MCB C 6 10 - 3.64

12L3 Spare - - - - - - - - - - - -

Page 45: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 44 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.54 É

IÙ 0.43 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 07/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L3 - - - 0.69 - - - 200 200 á 1.23 27.1 27.2 á

2L3 - - - 0.08 - - - 200 200 á 0.62 24.1 16.3 á

3L3 - - - 0.57 - - - 200 200 á 1.11 28.7 28.6 á

4L3 - - - 0.37 - - - 200 200 á 0.91 - -

5L3 - - - 0.30 - - - 200 200 á 0.84 - -

6L3 - - - 0.50 - - - 200 200 á 1.04 - -

7L3 - - - - - - - - - - - -

8L3 - - - - - - - - - - - -

9L3 - - - - - - - - - - - -

10L3 - - - 0.20 - - - 200 200 á 0.74 - -

11L3 - - - 0.21 - - - 200 200 á 0.75 - -

12L3 - - - - - - - - - - - -

Page 46: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 45 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

VISITOR W.C

Distributionboard designation: DB 1B (EX)

Supply to distributionboard is from: DB1 (EX) No of

phases: 1 Nominalvoltage: 230 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) -

Type:BS(EN) 60898 Rating: 40 A RCD No

of poles: - IÜ - mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

VIR + FP200

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L1 Spare H C 4 4.0 C.S 0.4 60898 MCB B 32 10 - 1.37

2L1 ZIP BOILER ROOM 110 O C 1 2.5 2.5 0.4 60898 MCB B 16 10 - 2.73

3L1 LTS 098, 9613, 98, 98A, B B 5 1.5 M.F 0.4 60898 MCB B 10 10 - 4.37

4L1 LTS 097, 99, 99A, 100 B B 9 1.5 M.F 0.4 60898 MCB B 10 10 - 4.37

5L1 LTS 93, 93A, 95, 95A, 95B B B 6 1.5 M.F 0.4 60898 MCB B 10 10 - 4.37

6L1 LTS 090, 91 B B 4 1.5 M.F 0.4 60898 MCB B 10 10 - 4.37

7L1 LTS 091A, 92 B B 4 1.5 M.F 0.4 60898 MCB B 10 10 - 4.37

8L1 LTS 102, 112 + CANOPY B B 7 1.5 M.F 0.4 60898 MCB B 10 10 - 4.37

9L1 UNKNOWN O B L 2.5 M.F 0.4 60898 MCB B 10 10 - 4.37

10L1 CORRIDOR LTS OFFICE END C B 12 1.5 1.5 0.4 60898 MCB C 6 10 - 3.64

11L1 SANIFO THIS W.C O C 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 - 1.37

12L1 Spare - - - - - - - - - - - -

Page 47: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 46 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.35 É

IÙ 0.66 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 08/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L1 - - - 0.24 - - - 200 200 á 0.59 - -

2L1 - - - 0.28 - - - 200 200 á 0.63 - -

3L1 - - - 0.77 - - - 200 200 á 1.12 - -

4L1 - - - 0.99 - - - 200 200 á 1.34 - -

5L1 - - - 0.79 - - - 200 200 á 1.14 - -

6L1 - - - 0.48 - - - 200 200 á 0.83 - -

7L1 - - - 0.61 - - - 200 200 á 0.96 - -

8L1 - - - 0.62 - - - 200 200 á 0.97 - -

9L1 - - - LIM - - - 200 200 LIM - -

10L1 - - - 0.55 - - - 200 200 á 0.90 - -

11L1 - - - 0.07 - - - -200 200 á 0.42 28.5 28.6 á

12L1 - - - - - - - - - - - -

Page 48: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 47 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

VISITORS W.C

Distributionboard designation: DB1 C (EX)

Supply to distributionboard is from: DB1 (EX) No of

phases: 1 Nominalvoltage: 230 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60898 Rating: 40 A RCD No

of poles: N/A IÜ - mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L2 Spare - - - - - - - - - - - -

2L2 Spare - - - - - - - - - - - -

3L2 LTS IN HALL B B 6 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37

4L2 LTS IN HALL B B 6 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37

5L2 LTS STAFF W.C MEETING ROOM + OFFICE B B 9 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37

6L2 THIS W.C + INCLUSION OFFICE B B 6 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37

7L2 LTS RECEPTION B B 10 1.5 1.6 0.4 60898 MCB B 10 10 - 4.37

8L2 Spare - - - - - - - - - - - -

9L2 SECURITY ALARM A C 1 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

10L2 LTS HALL STORE O C 3 1.0 1.0 0.4 60898 MCB B 10 10 - 4.37

11L2 SKTS FINANCE OFFICE O C 7 2.5 2.5 0.4 61009 RCD/RCBO B 16 10 30 2.73

12L2 CCTV POWER RECEPTION A C 5 2.5 1.5 0.4 60898 MCB B 20 10 - 2.19

Page 49: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 48 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.38 É

IÙ 0.61 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 08/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L2 - - - - - - - - - - - -

2L2 - - - - - - - - - - - -

3L2 - - - 0.23 - - - 200 200 á 0.61 - -

4L2 - - - 0.27 - - - 200 200 á 0.65 - -

5L2 - - - 0.43 - - - 200 200 á 0.81 - -

6L2 - - - 0.35 - - - 200 200 á 0.73 - -

7L2 - - - 0.44 - - - 200 200 á 0.82 - -

8L2 - - - - - - - - - - - -

9L2 - - - 0.27 - - - 200 200 á 0.65 - -

10L2 - - - 0.39 - - - 200 200 á 0.77 - -

11L2 - - - 0.23 - - - 200 200 á 0.61 28.7 31.5

12L2 - - - 0.25 - - - 200 200 á 0.63 - -

Page 50: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 49 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

STORE ROOM 084

Distributionboard designation: DB1A (EX)

Supply to distributionboard is from: DB1 (EX) No of

phases: 1 Nominalvoltage: 230 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60898 Rating: 40 A RCD No

of poles: N/A IÜ - mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

FP200

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L3 LTS 079 + 080 B B 4 1.5 M.F 0.4 60898 MCB B 10 10 - 4.37

2L3 LTS CENTRE 075 B B 6 1.5 M.F 0.4 60898 MCB B 10 10 - 4.37

3L3 LTS 080+081 B B 4 1.5 M.F 0.4 60898 MCB B 10 10 - 4.37

4L3 LTS CENTRE 081 B B 6 1.5 M.F 0.4 60898 MCB B 10 10 - 4.37

5L3 LTS CENTRE 083 B B 6 1.5 M.F 0.4 60898 MCB B 10 10 - 4.37

6L3 LTS 083+084 B B 4 1.5 M.F 0.4 60898 MCB B 10 10 - 4.37

7L3 LTS 084 + 085 B B 4 1.5 M.F 0.4 60898 MCB B 10 10 - 4.37

8L3 LTS CENTRE 085 B B 6 1.5 M.F 0.4 60898 MCB B 10 10 - 4.37

9L3 SPARE - - - - - - - - - - - -

10L3 LTS CENTRE 087 B B 6 1.5 M.F 0.4 60898 MCB B 10 10 - 4.37

11L3 LTS 087, 088, 089 B B 5 1.5 M.F 0.4 60898 MCB B 10 10 - 4.37

12L3 WATER COOLER +OZONE SPURS O C 2 2.5 2.5 0.4 60898 MCB B 6 10 - 7.28

Page 51: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 50 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.45 É

IÙ 0.51 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 09/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L3 - - - 0.52 - - - 200 200 á 0.97 - -

2L3 - - - 0.42 - - - 200 200 á 0.87 - -

3L3 - - - 0.40 - - - 200 200 á 0.85 - -

4L3 - - - 0.44 - - - 200 200 á 0.89 - -

5L3 - - - 0.33 - - - 200 200 á 0.78 - -

6L3 - - - 0.23 - - - 200 200 á 0.68 - -

7L3 - - - 0.27 - - - 200 200 á 0.72 - -

8L3 - - - 0.41 - - - 200 200 á 0.86 - -

9L3 - - - - - - - - - - - -

10L3 - - - 0.24 - - - 200 200 á 0.69 - -

11L3 - - - 0.22 - - - 200 200 á 0.67 - -

12L3 - - - 0.59 - - - 200 200 á 1.04 - -

Page 52: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 51 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

BOILER HOUSE

Distributionboard designation: DB BH

Supply to distributionboard is from: DB MP No of

phases: 3 Nominalvoltage: 415 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60947 Rating: 50 A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L1 LIGHTS THIS ROOM D B 6 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37

1L2 SUMP PUMP ( RLD VIA MODULE) D B 1 2.5 2.5 0.4 60898 MCB B 10 10 - 4.37

1L3 HEATERS IN HALL + SOCKETS WHITEBOARD D B 6 2.5 2.5 0.4 61009 RCD/RCBO B 16 10 30 2.73

2L1 EXTERNAL LIGHTS D B 2 1.5 1.5 0.4 60898 MCB B 6 10 - 7.28

2L2 PAMEL HEATER SPUR LHS D B 1 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19

2L3 SOCKET BELOW C B 1 2.5 1.5 0.4 60898 MCB B 16 6 - 2.73

3L123 SPARE - - - - - - - - - - - -

4L123 BOILER/HEATING PANEL D B 1 6.0 6.0 5 60898 MCB C 40 10 - 0.55

Page 53: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 52 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.19 É

IÙ 2.42 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101340213

Insulationresistance 101340211

Continuity 101340211

RCD 101340213

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 10/08/2017Name:

(CAPITALS) ANTHONY KNAPP

Position: Test Engineer

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L1 - - - 0.03 - - - 200 200 á 0.22 - -

1L2 - - - 0.07 - - - 200 200 á 0.26 - -

1L3 - - - 1.12 - - - 200 200 á 1.31 28.5 28.5 á

2L1 - - - LIM - - - 200 200 LIM - -

2L2 - - - 0.17 - - - 200 200 á 0.36 - -

2L3 - - - 0.04 - - - 200 200 á 0.23 - -

3L123 - - - - - - - - - - - -

4L123 - - - 0.13 - 200 200 200 200 á 0.32 - -

Page 54: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 53 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

CORRIDOR 027

Distributionboard designation: DB 1A (N)

Supply to distributionboard is from: DB MP No of

phases: 1 Nominalvoltage: 230 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60947-2 Rating: 63 A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L1 SPURS IN W.C A C 2 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 20 10 30 1.09

2L1 LAMP POST F E 1 6.0 C.S 0.4 61009 RCD/RCBO C 16 10 30 1.37

3L1 SPARE - - - - - - - - - - - -

4L1 WATER HEATER GIRLS, WC A C 1 2.5 1.5 0.4 61009 RCD/RCBO C 16 10 30 1.37

5L1 WATER HEATER CORRIDOR A C 1 2.5 1.5 0.4 61009 RCD/RCBO C 16 10 30 1.37

6L1 SKTS CORRIDOR A C 4 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

7L1 SKTS 018 A C 9 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

8L1 SKTS 019 A C 11 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

9L1 SKTS 020 A C 11 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

10L1 SPARE - - - - - - - - - - - -

11L1 CCTV SPURS A C 2 2.5 1.5 0.4 60898 MCB B 10 10 - 4.37

12L1 DOOR MASS 032 A C 2 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO B 16 10 - 2.73

13L1 RCD SPUR FOR STAIR LIFT A C 1 2.5 1.5 0.4 61009 RCD/RCBO B 16 10 30 2.73

14L1 LTS CORRIDOR A C 12 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

15L1 LTS, RAN + WINDOW SPURS 021, 025, 027 A C 14 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

16L1 LTS 018 A C 10 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

17L1 LTS 019 A C 10 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

18L1 LTS 020 + SECURITY SPURS A C 13 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

Page 55: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 54 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.20 É

IÙ 1.15 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 10/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L1 - - - 0.48 - - - 200 200 á 0.68 31.2 17.2 á

2L1 - - - 0.60 - - - 200 200 á 0.80 34 16.5 á

3L1 - - - - - - - - - - - -

4L1 - - - 0.23 - - - 200 200 á 0.43 30.2 15.5 á

5L1 - - - 0.18 - - - 200 200 á 0.38 30.9 16.7 á

6L1 0.42 0.41 0.72 0.60 - - - 200 200 á 0.80 30.2 16.3 á

7L1 0.81 0.81 1.38 0.91 - - - 200 200 á 1.11 23.8 15.7 á

8L1 0.71 0.70 1.17 0.51 - - - 200 200 á 0.71 32 16.2 á

9L1 0.67 0.68 1.11 0.74 - - - 200 200 á 0.94 32.1 16.6 á

10L1 - - - - - - - - - - - -

11L1 - - - 0.67 - - - 200 200 á 0.87 - -

12L1 - - - 0.53 - - - 200 200 á 0.73 - -

13L1 - - - 0.59 - - - 200 200 á 0.79 34.1 28.2 á

14L1 - - - 0.94 - - - 200 200 á 1.14 40.3 15 á

15L1 - - - 1.01 - - - 200 200 á 1.21 30.5 15.7 á

16L1 - - - 0.83 - - - 200 200 á 1.03 31.1 18.4 á

17L1 - - - 0.99 - - - 200 200 á 1.19 31.7 18.5 á

18L1 - - - 1.21 - - - 200 200 á 1.41 32.2 20.2 á

Page 56: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 55 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

ROOM 119

Distributionboard designation: DB 3

Supply to distributionboard is from: DB MP No of

phases: 1 Nominalvoltage: 230 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60947 - 2 Rating: 63 A RCD No

of poles: N/A IÜ - mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

FP200

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L3 Spare A B LIM 6.0 2.5 5 60898 MCB C 40 10 - 0.55

2L3 SKTS + SPURS NURSERY C B 12 2X 2.5 2X 2.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

3L3 SKTS NURSERY C B 5 2X 2.5 2X 2.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

4L3 SKTS NURSERY + TV ROOM + STAFF W.C C B 3 2X 2.5 2X 2.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

5L3 SPARE - - - - - - - - - - - -

6L3 W/HTR STAFF W.C C B 1 2.5 2.5 0.4 60898 MCB B 16 10 - 2.73

7L3 SPUR FOR WINDOWS ROOM 118 O B/C 1 2.5 2.5 0.4 60898 MCB B 16 10 - 2.73

8L3 LTS NURSERY C B 9 2.5 2.5 0.4 60898 MCB B 16 10 - 2.73

9L3 LTS NURSERY W.C TV ROOM + STAFF W.C C B 5 1.0 1.0 0.4 60898 MCB B 16 10 - 2.73

10L3 COOKER C B 1 6.0 6.0 0.4 61009 RCD/RCBO C 32 10 30 0.68

11L3 AIR FRESHER BOYS W.C O C 1 2.5 2.5 0.4 60898 MCB B 6 10 - 7.28

12L3 Supply to: DB 3A H C 1 4.0 C.S 5 60898 MCB C 40 10 - 0.55

Page 57: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 56 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.29 É

IÙ 0.79 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 08/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L3 - - - LIM - - - - - LIM - -

2L3 0.23 0.23 0.24 0.35 - - - 200 200 á 0.64 28.8 17.5 á

3L3 0.41 0.41 0.41 0.34 - - - 200 200 á 0.63 38.7 18.3 á

4L3 0.28 0.29 0.28 0.53 - - - 200 200 á 0.82 38.8 30.3 á

5L3 - - - - - - - - - - - -

6L3 - - - 0.42 - - - 200 200 á 0.71 - -

7L3 - - - 0.20 - - - 200 200 á 0.49 - -

8L3 - - - 0.62 - - - 200 200 á 0.91 - -

9L3 - - - 0.64 - - - 200 200 á 0.93 - -

10L3 - - - 0.04 - - - 200 200 á 0.33 31.6 18.5 á

11L3 - - - 0.40 - - - 200 200 á 0.69 - -

12L3 - - - 0.05 - - 200 200 200 á 0.34 - -

Page 58: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 57 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

ROOM 128

Distributionboard designation: DB 3A

Supply to distributionboard is from: DB 3 No of

phases: 1 Nominalvoltage: 230 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60898 Rating: 40 A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L3 LIGHTS LOBBY, DISABLED W.C + CRECHE A B/C 17 1.5 1.0 0.4 60898 MCB C 6 10 - 3.64

2L3 LTS CRECHE FAR SIDE A B/C 9 1.5 1.0 0.4 60898 MCB C 6 10 - 3.64

3L3 LTS THIS ROOM + BOYS + GIRLS WC'S A B/C 9 1.5 1.0 0.4 60898 MCB C 6 10 - 3.64

4L3 BOILER SUPPLY A B/C 3 2.5 1.5 0.4 60898 MCB C 16 10 - 1.37

5L3 URINAL FLUSH UNIT A B/C 1 2.5 1.5 0.4 60898 MCB B 10 10 - 4.37

6L3 CCTV + DOOR ACCESS A B/C 2 2.5 1.5 0.4 60898 MCB B 20 10 - 2.19

7L3 SKTS CRECHE A B/C 8 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 20 10 30 1.09

8L3 DOOR ENTRY SYSTEM A B/C 1 2.5 1.5 0.4 60898 MCB C 10 10 - 2.19

9L3 CCTV F.C.U IN W.C O C 1 2.5 1.5 0.4 60898 MCB B 10 10 - 4.37

Page 59: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 58 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.34 É

IÙ 0.68 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266727

Insulationresistance 101266722

Continuity 101266722

RCD 101266727

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 08/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L3 - - - 0.79 - - - 200 200 á 1.13 - -

2L3 - - - 0.81 - - - 200 200 á 1.15 - -

3L3 - - - 0.70 - - - 200 200 á 1.04 - -

4L3 - - - 0.12 - - - 200 200 á 0.46 - -

5L3 - - - 0.30 - - - 200 200 á 0.65 - -

6L3 - - - 0.29 - - - 200 200 á 0.63 - -

7L3 - - - 0.57 - - - 200 200 á 0.91 58.7 19 á

8L3 - - - 0.03 - - - 200 200 á 0.37 - -

9L3 - - - LIM - - - 200 200 LIM - -

Page 60: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 59 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

CORRIDOR 057

Distributionboard designation: DB 1C (N)

Supply to distributionboard is from: DB MP No of

phases: 1 Nominalvoltage: 230 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60947-2 Rating: 63 A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L1 WINDOW SPURS 057 + CCTV FLU 075 A C 3 2X 1.5 2X 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

2L1 LTS CORRIDOR 057 A C 17 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

3L1 SPUR IN BOYS W.C 061 A C 1 2.5 1.5 0.4 61009 RCD/RCBO C 16 10 30 1.37

4L1 LTS ROOM 058 A C 10 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

5L1 LTS + FANS 061, 065, 066, 075, 072, 071 +

DISABLED ALARMA C 25 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

6L1 LTS ROOM 060 + OUTSIDE A C 11 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

7L1 SKTS + SPURS ROOM 060 A C 11 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

8L1 SKTS 014 A C 5 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

9L1 SKTS 057 + 065 A C 5 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

10L1 SKTS + SPURS 058 A C 10 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

11L1 WATER HTR 057 A C 1 2.5 1.5 0.4 61009 RCD/RCBO C 16 10 30 1.37

12L1 WATER HTR 065 A C 1 2.5 1.5 0.4 61009 RCD/RCBO C 16 10 30 1.37

13L1 SPUR IN GIRLS W.C 075 A C 1 2.5 1.5 0.4 61009 RCD/RCBO C 16 10 30 1.37

14L1 LTS 014 A C 7 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

15L1 LTS 059 A C 10 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

16L1 SKTS + SPURS 059 A C 10 1.5 1.0 0.4 61009 RCD/RCBO C 32 10 30 0.68

17L1 WINDOW SPURS 057 + 061 A C 4 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

18L1 SKTS 072 A C 4 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

Page 61: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 60 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.17 É

IÙ 1.35 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 09/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L1 - - - 0.45 - - - 200 200 á 0.62 32.2 17.1 á

2L1 - - - 0.72 - - - 200 200 á 0.89 31.3 20.2 á

3L1 - - - 0.47 - - - 200 200 á 0.64 30.4 15.7 á

4L1 - - - 0.80 - - - 200 200 á 0.97 32.2 18.6 á

5L1 - - - 1.26 - - - 200 200 á 1.43 40.2 16.3 á

6L1 - - - 0.76 - - - 200 200 á 0.93 38 20.2 á

7L1 0.77 0.77 1.32 0.50 - - - 200 200 á 0.67 30.9 16.5 á

8L1 0.51 0.51 0.82 0.32 - - - 200 200 á 0.49 30.5 16.3 á

9L1 0.71 0.71 1.18 0.43 - - - 200 200 á 0.60 30.6 17 á

10L1 0.88 0.88 1.43 0.46 - - - 200 200 á 0.63 30.2 16.3 á

11L1 - - - 0.41 - - - 200 200 á 0.58 30.9 16 á

12L1 - - - 0.55 - - - 200 200 á 0.72 30.5 16.5 á

13L1 - - - 0.60 - - - 200 200 á 0.77 30.2 15.9 á

14L1 - - - 1.37 - - - 200 200 á 1.54 38.6 16.9 á

15L1 - - - 0.86 - - - 200 200 á 1.03 38.1 15.9 á

16L1 0.83 0.84 1.40 0.53 - - - 200 200 á 0.70 30.2 15.2 á

17L1 - - - 0.51 - - - 200 200 á 0.68 30.2 16.7 á

18L1 0.37 0.36 0.71 0.21 - - - 200 200 á 0.38 30.2 16.2 á

Page 62: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 61 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

CORRIDOR 055

Distributionboard designation: DB 1D (N)

Supply to distributionboard is from: DB MP No of

phases: 1 Nominalvoltage: 230 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60947 - 2 Rating: 63 A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L2 LTS CORRIDOR 045 + 055 A C 17 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

2L2 LTS + FAN GIRLS W.C A C 9 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

3L2 LTS 047 A C 10 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

4L2 LTS + SPUR 048 A C 11 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

5L2 LTS + FAN BOYS W.C A C 5 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

6L2 LTS 046 A C 10 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

7L2 WATER HTR 053 A C 1 2.5 1.5 0.4 61009 RCD/RCBO C 16 10 30 1.37

8L2 WATER HTR 055 A C 1 2.5 1.5 0.4 61009 RCD/RCBO C 16 10 30 1.37

9L2 SPUR IN BOYS W.C A C 1 2.5 1.5 0.4 61009 RCD/RCBO C 16 10 30 1.37

10L2 SPUR IN GIRLS W.C A C 1 2.5 1.5 0.4 61009 RCD/RCBO C 16 10 30 1.37

11L2 SKTS + SPUR 047 A C 10 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

12L2 SKTS + SPUR 048 A C 7 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

13L2 SKTS CORRIDOR 055 A C 4 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

14L2 SKTS + SPUR 046 A C 11 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

15L2 ALARM SPUR ABOVE CEILINGS A C 1 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

16L2 WINDOW SPURS GIRLS W.C + CORRIDOR A C 1 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

17L2 WINDOW SPURS CORRIDOR A C 1 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

18L2 CCTV 048 A C 1 2.5 1.5 0.4 60898 MCB B 10 10 30 4.37

Page 63: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 62 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.19 É

IÙ 1.21 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 09/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L2 - - - 0.95 - - - 200 200 á 1.14 30.2 18.2

2L2 - - - 0.65 - - - 200 200 á 0.84 32.4 16.6

3L2 - - - 0.72 - - - 200 200 á 0.91 31.5 16.5

4L2 - - - 0.68 - - - 200 200 á 0.87 31 17

5L2 - - - 0.71 - - - 200 200 á 0.90 40.2 15.1

6L2 - - - 1.10 - - - 200 200 á 1.29 31.8 18.7

7L2 - - - 0.41 - - - 200 200 á 0.60 30.2 15.2

8L2 - - - 0.22 - - - 200 200 á 0.41 30.2 16.9

9L2 - - - 0.47 - - - 200 200 á 0.66 30.8 15.3

10L2 - - - 0.51 - - - 200 200 á 0.70 30.2 16.2

11L2 0.53 0.53 0.91 0.74 - - - 200 200 á 0.93 30.2 16.1

12L2 0.75 0.74 1.28 0.52 - - - 200 200 á 0.71 30.4 15.8

13L2 0.38 0.38 0.64 0.36 - - - 200 200 á 0.55 32.8 16.3

14L2 0.83 0.82 1.35 0.66 - - - 200 200 á 0.85 30.6 15.9

15L2 - - - LIM - - - 200 200 LIM 35.1 15.6

16L2 - - - 0.49 - - - 200 200 á 0.68 31.1 15.9

17L2 - - - 0.40 - - - 200 200 á 0.59 30.4 10.2

18L2 - - - 0.45 - - - 200 200 á 0.64 - -

Page 64: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 63 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

CORRIDOR 044

Distributionboard designation: DB 1B (N)

Supply to distributionboard is from: DB MP No of

phases: 1 Nominalvoltage: 230 V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN) N/A

Type:BS(EN) 60947-2 Rating: 63 A RCD No

of poles: N/A IÜ N/A mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1L2 SPARE - - - - - - - - - - - -

2L2 SWITCHED OFF A C LIM 2.5 1.5 0.4 61009 RCD/RCBO C 16 10 30 1.37

3L2 SKTS CORRIDOR 044 A C 2 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

4L2 WATER HTR 042 A C 1 2.5 1.5 0.4 61009 RCD/RCBO C 16 10 30 1.37

5L2 WATER HTR 037 A C 1 2.5 1.5 0.4 61009 RCD/RCBO C 16 10 30 1.37

6L2 SPURS IN W.'S A C 2 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 20 10 30 1.09

7L2 SKTS + SPUR 35+35A A C 9 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

8L2 SKTS + SPURS 033 + 044 A C 10 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

9L2 SKTS + SPURS 034 + 044 A C 10 2X 2.5 2X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

10L2 SPARE - - - - - - - - - - - -

11L2 SPARE - - - - - - - - - - - -

12L2 SPARE - - - - - - - - - - - -

13L2 CCTV SPUR A C 1 2.5 1.5 0.4 60898 MCB B 10 10 - 4.37

14L2 LTS 038, 042, + 044 A C 13 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

15L2 LTS + SPURS 037 + 043 A C 12 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

16L2 LTS 035+ 043 A C 13 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

17L2 LTS 033 A C 10 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

18L2 LTS 034 A C 10 1.5 1.0 0.4 61009 RCD/RCBO C 10 10 30 2.19

Page 65: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Page 64 of 65

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0506760

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

YES Confirmation of supply polarity* See note below

Ö 0.21 É

IÙ 1.10 kA

*

*

At IÜ N/A ms

At 5IÜ N/A ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate)

Test instruments (serial numbers) used:

Earth fault loopimpedance 101266722

Insulationresistance 101266727

Continuity 101266727

RCD 101266722

Multifunction N/A

Other N/A

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 10/08/2017Name:

(CAPITALS) RICHARD BLOCKSIDGE

Position: TEST ENGINEER

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1L2 - - - - - - - - - - - -

2L2 - - - LIM - - - N/A N/A LIM LIM LIM

3L2 0.40 0.40 0.64 0.44 - - - 200 200 á 0.65 30.2 15.8 á

4L2 - - - 0.40 - - - 200 200 á 0.61 31 16.2 á

5L2 - - - 0.47 - - - 200 200 á 0.68 30.2 15.7 á

6L2 - - - 0.60 - - - 200 200 á 0.81 23.6 15.2 á

7L2 0.80 0.81 1.29 0.83 - - - 200 200 á 1.04 32.5 16.3 á

8L2 0.79 0.78 1.34 0.65 - - - 200 200 á 0.86 30.2 16.1 á

9L2 0.74 0.75 1.24 0.49 - - - 200 200 á 0.70 30.3 16.3 á

10L2 - - - - - - - - - - - -

11L2 - - - - - - - - - - - -

12L2 - - - - - - - - - - - -

13L2 - - - 0.70 - - - 200 200 á 0.91 - -

14L2 - - - 1.13 - - - 200 200 á 1.34 37.2 20.2 á

15L2 - - - 1.30 - - - 200 200 á 1.51 38.7 11.2 á

16L2 - - - 1.11 - - - 200 200 á 1.32 40.2 19.1 á

17L2 - - - 0.98 - - - 200 200 á 1.19 31.5 10.9 á

18L2 - - - 1.03 - - - 200 200 á 1.24 40.2 10.2 á

Page 66: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Please see the 'Guidance for Recipients on theclassification codes' in the 'Notes for Recipients'

F. OBSERVATIONS AND RECOMMENDATIONS FOR ACTIONS TO BE TAKEN

Referring to the attached schedules of inspection and test results, and subject to the limitations at D:

Item No Code Ú

There are no items adversely affecting electrical safety. N/A or The following observations and recommendations forare made

á

Additional Pages? No Yesá Specify page

ÚOne of the following codes, as appropriate, has been allocated to each of theobservations made above to indicate to the person(s) responsible for the installationthe degree of urgency for remedial action:

Code C1 "Danger Present". Risk of injury. Immediate remedial action required.

Code C2 "Potentially dangerous". Urgent remedial action required.

Code C3 "Improvement recommended".

Code FI "Further investigation required without delay".

Please see the notes for recipient for guidance regarding the Classification codes.

24 DB 1B (EX) - CIRCUIT 9L1 - WIRED IN V.I.R CABLE C3

25 DB 1B (EX) - CIRCUIT 9L1 - UNKNOWN - FURTHER INVESTIGATION IS REQUIRED TO LOCATE FINAL TERMINATION OF

CIRCUITC2

26 DB BH - CIRCUIT 2L1 - NO Z'S READING OBTAINED AT EXT LIGHTS DUE TO HEIGHT RESTRICTION LIM

27 DB BH - CIRCUIT 1L2 - RUNS THROUGH RCD MODULE 30MA (X1 - 23.6) (X5 5.5) NOTE

28 DB BH - CIRCUIT 1L1 - Z'S OBTAINED AT SWITCH NOTE

29 DB BH - CIRCUIT - 2L3 - INTEGRAL RCD SOCKET CIRCUIT - FAULTY RCD - (X1 - FAIL) (X5 FAIL) C2

30 DB BH - CIRCUIT 4L123 - INTEGRAL RCD SOCKET FITTED TO BOILER/HEATING PANEL - (X1 28.7) (X5 - 8.5) NOTE

31 DB BH - METALLIC TRUNKING ABOVE DB REQUIRES SECURING C3

32 DB 3 - CIRCUIT 1L3 - CIRCUIT SWITCHED OFF AT TIME OF TEST C3

33 DB 3 - CIRCUIT 7L3 - 1 PIN MISSING FROM SPUR C3

34 DB 3 - CIRCUIT 11L3 - CABLE NOT FIXED/ SUPPORTED IN W.C C3

35 DB 3 - CIRCUIT 2L3 - TRUNKING PASES ABOVE COOKER C3

36 DB 3 - CIRCUIT 10L3 - COOKER SWITCH ABOVE COOKER C2

37 DB 3A - CIRCUIT 9L3 - FCU OVER 3METRES UNABLE TO GAIN ACCESS TO OBTAIN READING C3

38 DB 3A - CIRCUITS 1L3, 2L3 + 4L3 - CABLES BURIED IN WALLS WITHOUT RCD PROTECTION C3

39 DB 1C (N) - CIRCUIT 16L1 - HIGH EARTH LOOP READING C2

40 DB 1D (N) - CIRCUIT 15L2 - SPUR ABOVE CEILING UNABLE TO GAIN LOOP READING C3

41 DB 1D (N) - CIRCUITS 11L2, 12L2 + 14L2 - HIGH EARTH LOOP READINGS C2

42 DB 1B (N) - CIRCUIT 2L2 - SWITCHED OFF AT TIME OF TEST NOTE

43 DB 1B (N) - CIRCUITS 7L2, 8L2 + 9L2 - HIGH EARTH LOOP READINGS C2

Immediate remedial actionrequired for items:

Urgent remedial actionrequired for items: 25,29,36,39,41,43,

Further investigationrequired for items:

Improvementrecommended for items: 24,31,32,33,34,35,37,38,40,

Page 67: Electrical Installation Condition Report Park - 5Yr Fixed Wirin… · Electrical Test Midlands 110B Walsall Road, Cannock, West Midlands, WS11 OJB t 01922 710014 e admin@electricaltestmidlands.com

Thank you for using our services and if you would like to discuss your companies further requirements please get in touch.

www.electricaltestmidlands.com

Electrical Test Midlands Ltd

110B Walsall Road, Cannock,

West Midlands, WS11 OJB

t 01922 710014

t 0800 066 3227

e [email protected]

Call one of the teamon 01922 710014or email [email protected]

• Alarms & Security

• Electrical Inspection & Testing

• Building Services

• Electrical Compliance

• Electrical Installation

• Emergency Lighting

• Energy Monitoring

• Electrical Installation Drawings

• Fire Alarm Installation & Testing

• Gas Installation & Plumbing

• (PAT) Portable Appliance Testing

• Thermal Imaging (Thermography)