Universal Measuring Device UMG96S Operating instructions Brief instructions see last page Min. value low rate/supply L1-N / L1-L2 L2-N / L2-L3 L3-N / L3-L1 Programming mode Sum measurement L - L Password Voltage transformer Current transformer Output 1 Output 2 Key1 Key 2 Mean value Supply D o k N r . 1 . 0 2 8 . 0 2 7 . 2 Janitza electronics GmbH Vor dem Polstück 1 D-35633 Lahnau Support Tel. (0 64 41) 9642-22 Fax (0 64 41) 9642-30 e-mail: [email protected] Internet: http://www.janitza.de Peak value high rate/Con- sumption

Electrical Power Meter UMG96S OM

Embed Size (px)

Citation preview

Page 1: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 1/96

Universal Measuring DeviceUMG96S

Operating instructions

Brief instructions see last page

Min. valuelow rate/supply

L1-N / L1-L2L2-N / L2-L3

L3-N / L3-L1

Programming modeSum measurementL - L

Password

Voltage transformerCurrent transformer

Output 1Output 2

Key1 Key 2

Mean value

Supply

Dok Nr.1.028.027.2

Janitza electronics GmbHVor dem Polstück 1D-35633 LahnauSupport Tel. (0 64 41) 9642-22

Fax (0 64 41) 9642-30e-mail: [email protected]: http://www.janitza.de

Peak valuehigh rate/Con-

sumption

Page 2: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 2/96

Page 2

ContentsDeclaration of conformity 4

Meaning of the symbols 4Hints for usage 5Receipt control 5Hints for maintenance 6

Repairing and calibration 6Face plate 6Battery 6Waste management 6

Service 6Product description 7

Intended use 7Functional description 8Voltage versions 9Device versions 10

Installation 18Mounting 18Measurement and operation voltage 18Current measurement 19Sum current measurement 19Inputs and outputs 20Serial interfaces 21Connection 22

Putting into service 24Insert device 24Connect measurement and operatingvoltage 24Connect measurement current 25Check phase assignment 25Check current direction 25Check measurement 25Check single phase power 25Check sum power 25

Removal of errors 26Error messages 28

Warnings 29Heavy errors 29Exceeding of measuring range 29

Usage and display 30Indication mode 30Programming mode 30Key functions 31

Parameters and measured values 32Parameter indication at UMG96S 32Measured value indication at UMG96S 32

Program parameters 33

Mean values 34Averaging time current (Adr.057) 34Averaging time power (Adr.058) 34Minimum and maximum values 34Net frequency (Adr.063) 35Real energy 35Current transformer (Addr. 600) 36Voltage transformer (Addr. 602) 37Harmonics (Addr.221) 38Measured value rotation 39Measured value indications 42Indication profile (Addr. 060) 42Indication profile (Addr. 604) 43User password (Addr.011) 44Delete energy (Addr.009) 44Field rotation (Addr. 277) 45LCD Contrast (Addr. 012) 45Time detection 46Serial number (Addr. 911) 46Software Release (Addr. 913) 47Hardware expansion (Addr. 914) 47

Serial interfaces 48Interface selection (Addr. 062) 48Modem operation (Addr. 070) 48

MODBUS RTU 49Realised functions 49

RS232 interface (Option) 50RS485 interface 52Profibus DP (Option) 54

Profibus profiles 56Inputs and outputs 60

Pulse output 62Pulse valence 63Digital output 66

Limit supervision 68Analogue output (Option) 70Digital input (Option) 72

Memory 74Data memory (Option) 74Data memory (056) 74

Tables 76Parameter list 77Measured value list 80

Measured value displays, overview 86Indication range and accuracy 90

Page 3: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 3/96

Page 3

Technical data 91Ambient conditions 91Safety regulations 91Requirements of electromagnetical

compatibility 91Testing voltage (piece test) 92Inputs and outputs 92Measurement 93Serial interfaces 93Connectable wires 93Dimension sketch 94Connection diagrams 95

Brief instructions 96Change current transformer 96Call up measured values 96

Page 4: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 4/96

Page 4

Issue note22.04.2003 First edition.08.11.2004 Completions.

All rights reserved. No part of this manual maybe reproduced or duplicated without the writtenpermission of the author. Any contraventionsare punishable and will be prosecuted with alllegal means.

No liability can be taken for the faultless condi-tion of the manual or damage caused by theuse of it. As failures cannot be avoided com-pletely, we shall be very grateful for any advice.We will try to remove any failures as soon aspossible. The mentioned software and hard-ware descriptions are registered trademarks inthe most cases and are subjected to the regu-lations by law. All registered trademarks areproperty of the corresponding companies andare fully recognized by us.

Beware dangerous electrical voltage.

This symbol shall warn you about possi-ble danger, that can occur while mount-ing, putting into service or the use of thisinstrument.

Meaning of the symbolsThe symbols, that were used in this manualhave the following meaning:

Declaration of conformityThe UMG96S fulfills the safety guidelines ofGuideline 89/336/EWG related to DIN EN61326 (2002-03) as well asGuideline 73/23/EWG and 93/68/EWG related to EN 61010-1 (1993)

Page 5: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 5/96

Page 5

Receipt controlIn order to ensure a perfect and safe use of thedevice, a proper transport, expert storage, erec-tion and mounting and careful usage and main-tenance are required. When it may be sup-

posed, that a safe operation is no longer possi-ble, the device has to be put out of service andbe protected against unintentional putting intoservice.A safe operation can no longer be assumed,when the device• shows visible damage,• does not work in spite of intact net supply,• has been exposed to disadvantageous condi-tions for a longer time (e.g. storage out of theallowed climate without adaption to the room

climate, dew etc.) or transport use (e.g. fallingfrom great height, even without visible dam-age).

Please test the contents of delivery for comple-tion, before starting the installation of the de-vice. All delivered options are listed on the de-livery papers.

Contents of delivery

1 pc. UMG96S,2 pcs. mounting clamps,1 pc. operating instructions,1 pc. PC-Software "PSWbasic" on CD-ROM.For devices with RS232 interface, a PC cable(2m), part no. 08.01.501 belongs to the con-tents of delivery.

All delivered options and versions are describedon the delivery papers.

Hints for usageThis device may be put into service and usedby qualified personnel according to the safetyregulations and instructions only. Please mindthe additional legal and safety regulations for

the respective application.Qualified personnel are persons, familiar witherection, mounting, putting into service and us-age of the product and having the qualificationssuch as:

• education or instruction / entitlement to switch,release, ground or characterize current circuitsand devices according to the standards ofsafety techniques.• education or instruction in care and usage of

suitable safety equipment according to thestandards of safety techniques.

Attention!If the instrument is not used according tothe operating instructions, a safe use can-not be granted, and certain danger canbe effected by the instrument.

This manual also describes options,which have not been delivered and,hence, do not belong to the contents ofdelivery.

Page 6: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 6/96

Page 6

ServiceIf you have problems, which are not describedin this manual, please ask our technical sup-port.For further handling of your questions, please

have the following on hand:- Device description (see type plate),- Serial number (see type plate),- Software Release,- Measurement and auxiliary voltage and- Exact description of the problem.

You can contact us:Monday to Thursday

between 07:00h and 15:00hand Friday

between 07:00h and 12:00h

Janitza electronic GmbHVor dem Polstück 1D-35633 LahnauSupport: Tel. (0 64 41) 9642-22

Fax (0 64 41) 9642-30e-mail: [email protected]

Hints for maintenanceBefore delivery the device is tested in varioussafety checks and marked with a seal. If thedevice is opened, these checks must be re-peated.

There is no guarantee for devices, which areopened out of the manufacturing works.

Repairing and calibrationMaintenance and calibration can only be carriedout at manufacturer's end.

Face plateThe cleaning of the front foil must be done witha soft cloth using a common cleansing agent.

Acid or acidic agents may not be used forcleaning.

BatteryOn the additional PCB 1 (option), there is aLithium battery. The life expectance of the bat-tery at storage temperature +45°C is a mini-mum of 5 years. The typical life expectance isbetween 8 and 10 years.For safety reasons, the battery should be ex-changed in the manufacturing works only!

Waste managementThe UMG96S can be disposed and recycledas electronical waste according to the legalregulations. Please note, that the input Lithiumbattery must be disposed separately.

Page 7: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 7/96

Page 7

Product descriptionIntended useThe UMG96S has been designed for a fixed in-stallation in panels, measuring voltage, current,power etc. in low voltage switchgear. The meas-urement is laid out for three phase systems withneutral conductor (TN and TT networks).The UMG96S gets its operating voltage fromthe measuring voltage and can be delivered foroperating voltage of 150V and 300V. The 300Vstandard version, measurement and operationvoltage (50Hz/60Hz) up to 300VAC againstground and 520VAC phase to phase can beconnected directly. The 150V special version,measurement and operating voltage (50Hz/ 60Hz) up to 150VAC against ground and240VAC phase to phase can be connected di-rectly.The measurement and operational voltagemust be connected to the UMG96S via a sepa-ration (circuit breaker or power switch) and afuse (2-10A) within the installation. The separa-tion (circuit breaker or power switch) must benear to the instrument and easy to reach.The connection of the measurement and oper-ating voltage is carried out on the backside ofthe UMG96S via touch proof spring terminal. Tothe current inputs, either .../5A or .../1A trans-formers can be connected.

Attention!Measurement in systems with pulse loadis not possible, because no continuousscanning of the measuring signals is car-ried out.

Attention!The inputs, outputs and serial interfacesmust be shielded.

Attention!The connection of the neutral conductorN is absolutely neccessary.

Page 8: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 8/96

Page 9: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 9/96

Page 9

Voltage versionsThe UMG96S takes the measurement voltageas operating voltage and can be delivered inthe versions 150V and 300V. The delivered ver-sion is indicated on the type plate of UMG96S.Please ensure, that the local net conditionsmatch the numbers on type plate before con-nection.

300V standard versionIn 300V standard version , the UMG96S canmeasure voltage up to 300VAC against ground.At leats one phase (L) of the UMG96S and theneutral N must be connected and the con-nected voltage must be within the measure-ment and operation voltage range.The measurement and operation voltagerange of devices without additional PCB and fordevices with additional PCB 1 (analogue out-put) are:Measuring range L-N : 30 .. 300V ACMeasuring range L-L : 50 .. 520V ACOperating voltage range L-N : 85 .. 300V AC

The measurement and operating voltage rangefor devices with additional PCB 2 (Profibus) are:Measuring range L-N : 30 .. 300V ACMeasuring range L-L : 50 .. 520V ACOperating voltage range L-N :140.. 300V AC

150V special versionIn 150V special version, the UMG96S canmeasure voltage up to 300VAC against ground.At least 2 phases (L) of the UMG96S must beconnected, and the connected voltage must bewithin the measurement and operation voltagerange.

Measuring range L-N : 25 .. 140V ACMeasuring range L-L : 40 .. 240V ACOperating voltage range L-L : 85 .. 260V AC

Attention!Voltage, which is above the allowedrange can damage the device.

Page 10: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 10/96

Page 10

Device versionsThe UMG96S can be delivered in different ver-sions. The customer can assign a function tothe clamps 11, 12 and 13 of UMG96S.Version 1Version 1 contains the following functionalgroups: RS485 (MODBUS RTU) Input/Output

Pulse output 1 (Wp=real energy)Pulse output 2 (Wq=reactive energy)Digital output 1Digital output 2

UMG96S

12

13

11

14

15TXD

RXD

Input/Output 2 (003)

Pulse output Wq (003 = 0)

Digital output (003 = 1)

Analogue output (003 = 2)

Digital input (003 = 3,5)

Profibus-Remote (003 = 4)

Input/Output 1 (002)

Pulse output Wp (002 = 0)

Digital output (002 = 1)

Analogue output(002 = 2)

Digital input (002 = 3,5)Profibus-Remote (002 = 4)

C o m p a r a

t o r g r o u p

1

C

o m p a r a

t o r g r o u p

2

RS485 (MODBUS RTU)Interface

S e r i a

l I n t e r f a c e

Basic PCB

R S 4 8 5

Current measurement

1 5

1 4

1 3

1 2 1 1

1 0 8 7 9

1 3 2 4

6 5

I / OMeasurementand operating

voltage

Art.Nr.52.13.00152.13.00252.13.00352.13.004

Page 11: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 11/96

Page 12: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 12/96

Page 12

Version 3Version 3 contains the following functionalgroups: RS232 (MODBUS RTU) RS485 (MODBUS RTU) Input/Output

Pulse output 1 (Wp=real energy)Pulse output 2 (Wq=reactive energy)Digital output 1Digital output 2Clock with batteryData memory

UMG96S

12

13

11

R J 1 1

S l e e v e

14

15

TXD

GNDRXD

TXD

RXD

Input/Output 2 (003)

Pulse output Wq (003 = 0)

Digital output (003 = 1)

Analogue output (003 = 2)

Digital input (003 = 3,5)

Profibus-Remote (003 = 4)

Input/Output 1 (002)

Pulse output Wp (002 = 0)

Digital output (002 = 1)

Analogue output(002 = 2)

Digital input (002 = 3,5)Profibus-Remote (002 = 4)

Data memory

Additional PCB 1

C o

m p a r a

t o r g r o u p

1

C o m p a r a

t o r g r o u p

2

Basic PCB

RS485 (MODBUS RTU)Interface

RS232 (MODBUS RTU)Interface

S e r i a

l i n t e r f a c e

Clock with battery

A d d i t i o n a

l P C B

1 M e m o r y

1 3

1 2 1 1

RS232

Measurementand operating

voltage

Current measurement

1 5

1 4

1 0 8 7 9

1 3 2 4

6 5

Art.Nr.52.13.00952.13.01052.13.01152.13.012

Page 13: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 13/96

Page 13

Version 4Version 4 contains the following functionalgroups: RS232 (MODBUS RTU) RS485 (MODBUS RTU) Input/Output

Pulse output 1 (Wp=real energy)Pulse output 2 (Wq=reactive energy)Digital output 1Digital output 2Analogue output 1Analogue output 2

UMG96S

12

13

11

R J 1 1

S l e e v e

14

15

TXD

GNDRXD

TXD

RXD

Input/Output 2 (003)

Pulse output Wq (003 = 0)

Digital output (003 = 1)

Analogue output (003 = 2)

Digital input (003 = 3,5)

Profibus-Remote (003 = 4)

Input/Output 1 (002)

Pulse output Wp (002 = 0)

Digital output (002 = 1)

Analogue output(002 = 2)

Digital input (002 = 3,5)Profibus-Remote (002 = 4)

Analogue output 2

Additional PCB 1

C o

m p a r a

t o r g r o u p

1

C o m p a r a

t o r g r o u p

2

Basic PCB

RS485 (MODBUS RTU)Interface

RS232 (MODBUS RTU)Interface

S e r i a

l i n t e r f a c e

Analogue output 1

A d d i t i o n a

l P C B

1

A n a

l o g u e o u

t p u

t s

1 3

1 2 1 1

RS232

Measurementand operating

voltage

Current measurement

1 5

1 4

1 0 8 7 9

1 3 2 4

6 5

Art.Nr.52.13.01352.13.01452.13.01552.13.016

Page 14: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 14/96

Page 14

Version 5Version 5 contains the following functionalgroups: RS232 (MODBUS RTU) RS485 (MODBUS RTU) Input/Output

Pulse output 1 (Wp=real energy)Pulse output 2 (Wq=reactive energy)Digital output 1Digital output 2Analogue output 1Analogue output 2

Clock with battery Data memory

UMG96S

12

13

11

R J 1 1

S l e e v e

14

15

TXD

GNDRXD

TXD

RXD

Input/Output 2 (003)

Pulse output Wq (003 = 0)

Digital output (003 = 1)

Analogue output (003 = 2)

Digital input (003 = 3,5)

Profibus-Remote (003 = 4)

Input/Output 1 (002)

Pulse output Wp (002 = 0)

Digital output (002 = 1)

Analogue output(002 = 2)

Digital input (002 = 3,5)Profibus-Remote (002 = 4)

Analogue output 2

Additional PCB 1

C o

m p a r a

t o r g r o u p

1

C o m p a r a

t o r g r o u p

2

Basic PCB

RS485 (MODBUS RTU)Interface

RS232 (MODBUS RTU)Interface

S e r i a

l i n t e r f a c e

Analogue output 1

Data memory

Clock with battery

A d d i t i o n a

l P C B

1

A n a

l o g u e o u

t p u

t s

C l o c

k w

i t h b a

t t e r y

D a

t a m e m o r y

1 3

1 2 1 1

RS232

Measurementand operating

voltage

Current measurement

1 5

1 4

1 0 8 7 9

1 3 2 4

6 5

Art.Nr.52.13.01752.13.01852.13.01952.13.020

Page 15: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 15/96

Page 15

Version 6Version 6 contains the following functionalgroups: RS232 (MODBUS RTU) RS485 (MODBUS RTU) Input/Output

Pulse output 1 (Wp=real energy)Pulse output 2 (Wq=reactive energy)Digital output 1Digital output 2Digital input 1Digital input 2

C o m p a r a

t o r g r o u p

1

C o m p a r a

t o r g r o u p

2

UMG96S

12

Additional PCB 2

13

11

R J 1 1

S l e e v e

14

15

Digital input 1

TXD

GNDRXD

TXD

RXD

Input/Output 2 (003)

Pulse output Wq (003 = 0)

Digital output (003 = 1)

Analogue output (003 = 2)

Digital input (003 = 3,5)

Profibus-Remote (003 = 4)

Input/Output 1 (002)

Pulse output Wp (002 = 0)

Digital output (002 = 1)

Analogue output(002 = 2)

Digital input (002 = 3,5)Profibus-Remote (002 = 4)

RS485 (MODBUS RTU)Interface

RS232 (MODBUS RTU)Interface

S e r i a

l i n t e r f a c e

Basic PCB

Digital input 2

A d d i t i o n a

l P C B

2

D i g i t a l i n p u

t s

1 3

1 2 1 1

RS232

Measurementand operating

voltage

Current measurement

1 5

1 4

1 0 8 7 9

1 3 2 4

6 5

Art.Nr.52.13.02152.13.02252.13.02352.13.024

Page 16: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 16/96

Page 16

Version 7Version 7 contains the following functionalgroups: RS232 (MODBUS RTU) (Option) RS485 (MODBUS RTU) Profibus DP

Input/OutputPulse output 1 (Wp=real energy)Pulse output 2 (Wq=reactive energy)Digital output 1Digital output 2Digital input 1 (Option)Digital input 2 (Option)

C o m p a r a

t o r g r o u p

1

C o m p a r a

t o r g r o u p

2

Digital input 2

(Option)

UMG96S

12

Additional PCB 2

13

11

R J 1 1

B u c h s e

14

15

Digital input 1(Option)

DSUB 9

Profibus DP(Option)

A B- + TXD

GNDRXD

TXD

RXD

8 35 6

Input/Output 2 (003)

Pulse output Wq (003 = 0)

Digital output (003 = 1)

Analogue output (003 = 2)

Digital input (003 = 3,5)

Profibus-Remote (003 = 4)

Input/Output 1 (002)

Pulse output Wp (002 = 0)

Digital output (002 = 1)

Analogue output(002 = 2)

Digital input (002 = 3,5)Profibus-Remote (002 = 4)

RS485 (MODBUS RTU)Interface

RS232 (MODBUS RTU)Interface

S e r i a

l i n t e r f a c e

Basic PCB

A d d i t i o n a

l P C B

2

P r o

f i b u s

D P

D i g i t a i n p u

t

ProfibusDP

1 3

1 2 1 1

RS232

Measurementand operating

voltage

Current measurement

1 5

1 4

1 0 8 7 9

1 3 2 4

6 5

Art.Nr.52.13.02552.13.02652.13.02752.13.028

Page 17: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 17/96

Page 17

Page 18: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 18/96

Page 18

InstallationMountingThe UMG96S is designed for a fix installationin low and medium voltage systems. Themounting position is random.

Measurement and operationvoltageThe UMG96S gets its operating voltage fromthe measuring voltage. The measurement isdesigned for three phase systems with neutralconductor (TN and TT networks). The meas-urement and operational voltage must be con-nected to the UMG96S via a separation (circuitbreaker or power switch) and a fuse (2-10A)within the installation. The connection of themeasurement and operating voltage is carriedout on the backside of the UMG96S via touchproof spring terminal.

300V standard versionAt least one phase (L) of the UMG96S and theneutral N must be connected and the con-nected voltage must be within the measure-ment and operation voltage range.The measurement and operation voltagerange of devices without additional PCB and fordevices with additional PCB 1 (analogue out-put) are:

L-N 85 .. 300VL-L 148 .. 520V

The measurement and operating voltagerange for devices with additional PCB 2(Profibus) are:

L-N 140 .. 300VL-L 242 .. 520V

150V special versionAt least 2 phases (L) of the UMG96S must beconnected, and the connected voltage must bewithin the measurement and operation voltagerange.The measurement and operating voltagerange is:

L-N 50 .. 150VL-L 85 .. 260V Attention!

Before connecting voltage, the deviceshould be deposited in the preposed in-stallation room for at least 2 hours, inorder to create a temperature equaliza-tion and avoid humidity or dew within theinstrument.

Attention!The limits, mentioned under "technicaldata" may not be exceeded, even notduring checking or putting into service ofUMG96S.

- The used cables must be suitable for a ratedvoltage of 300VAC against ground.

- The measurement and operating voltage mustbe protected by a fuse. The fuse must be in therange of 2A to 10A .

- Please provide a circuit breaker or powerswitch for the operating voltage.

- The switch must be near the UMG96S andeasy to reach.

- The switch must be marked as a separationfor this instrument.

Page 19: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 19/96

Page 19

Sum current measurementIf the current measurement is carried out viatwo current transformers and a sum currenttransformer, the total transformer ratio must beprogrammed at UMG96S.

Example: Sum current transformer A current measurement is carried out via one ct with a ratio of 1000/5A and one ct with a ratio of 200/5A. The current measurement is carried out via a sum current transformer 5+5/5A.The UMG96S must be programmed as follows: Primary current: 1000A + 200A = 1200ASecondary current: 5A

Verbraucher 1 Consumer 1

Verbraucher 1 Consumer 1

Einspeisung 1 Supply 1

Einspeisung 1 Supply 1

UMG96S

L l

K k

L l

K kAK AL

K l

k l

BK Bl

Current measurementThe current measurement is carried out via cur-rent transformers of either ../5A or ../1A. If thecurrent must be measured by an Amperemeteradditionally, it must be connected in series tothe UMG96S.In networks with voltage up to 150VAC againstground, currents up to 5A can be connected di-rectly to the UMG96S.

L l

K kA

l

kUMG96S

VerbraucherConsumer

EinspeisungSupply

Attention!The secondary connections of the currenttransformer must be short-circuited, be-fore the wires that lead to the device areinterrupted!If a testing switch is available, whichshort-circuits the secondaries of the ctsautomatically, it is sufficient to set it intoposition "check", provided that the short-circuiters have been checked before.

Page 20: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 20/96

Page 20

Inputs and outputsThe UMG96S offers the possibility of assigningdifferent functions to the outputs of the differentversions (options).Terminal 12, for example, can have the function"pulse output" and terminal 13 can have thefunction "digital input". Please note, that bothcircuits have a common supply +24VDC, termi-nal 11.Only one function can be assigned to each ter-minal 12 and 13.

12

13

11

Input/Output 2

Pulse output Wq (003 =0)

Digital output (003 = 1)Analogue output(003 = 2)

Digital input (003 = 3,5)

Profibus-Remote (003 = 4)

Input/Output 1

Pulse output Wp (002 =0)

Digital output (002 = 1)Analogue output (002 = 2)

Digital input (002 = 3,5)

Profibus-Remote (002 = 4)

The wires of the inputs and outputs mustbe shielded.

Connection example: UMG96S with one ana- logue output and one digital output.

UMG96S

13

+ -

ExternalSupply voltage

Digitaloutput1,5k

m a x .

3 6 0 O h m

Analogueoutput

12+

+24V= 11 +

230V AC

24V DC

Diagr.: Connection example for the digital in- puts.

ExternalSupply voltage

S1

0V

12

UMG96SDigital inputs

Digital input 1

13

+ -

230V AC

24V DC

11

Digital input 2S2

5k

5k

Attention!Real energy Wp is firmly assigned topuls output 1.Reactive energy Wq is firmly assignedto puls output 2.

Page 21: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 21/96

Page 21

Serial interfacesDepending on the version the UMG96S mayhave up to three serial interfaces. The serial in-terfaces are not separated galvanically.The RS232 and RS485 cannot be operated atthe same time!If both interfaces are connected, the device rec-ognizes by the signal level, if an instrument isconnected to the RS232. The data transmissionis carried out via RS232 only.If no device is recognized at RS232, datatransmission is active on RS485 interface.

The wires of the serial data transmissionmust be shielded.

Page 22: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 22/96

Page 22

Connection

Diagr.: Connection example 1Four wire measurement with three current transformers.

UMG96SVoltage measure-

mentsee type plate

Current

measurement0,005 .. 5A

L1 L2 L3 N

V e r b r a u c

h e r

C o n s u m e r

k lk l

k l../5(1)A

../5(1)A../5(1)A

L1L2L3PEN

1k 1l 2k 2l 3k 3l

1 2 3 4 5 6 7 8 9 10

UMG96SVoltage measure-

mentsee type plate

Current

measurement0,005 .. 5A

L1 L2 L3 N

V e r b r a u c h e r

C o n s u m e r

k l

k l../5(1)A

../5(1)A

L1L2L3PEN

1k 1l 2k 2l 3k 3l

1 2 3 4 5 6 7 8 9 10

Diagr.: Connection example 2 Four wire measurement with two current trans- formers.

Diagr.: Connection example 3 Measurement with three voltage transformers and three current transformers.

UMG96SVoltage measure-

mentsee type plate

Currentmeasurement

0,005 .. 5A

L1 L2 L3 N

u u u

U U U

x x xX X X

V e r b r a u c

h e r

C o n s u m e r

k lk l

k l../5(1)A

../5(1)A../5(1)A

L1L2L3PEN

1k 1l 2k 2l 3k 3l

1 2 3 4 5 6 7 8 9 10

UMG96SVoltage measure-

mentsee type plate

Currentmeasurement

0,005 .. 5A

L1 L2 L3 N

u u u

U U U

x x xX X X

V e r b r a u c

h e r

C o n s u m e r

k l

k l../5(1)A

../5(1)A

L1L2L3PEN

1k 1l 2k 2l 3k 3l

1 2 3 4 5 6 7 8 9 10

Diagr.: Connection example 4 Measurement with three voltage transformers and two current transformers.

Page 23: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 23/96

Page 24: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 24/96

Page 24

Putting into serviceThe installation of the UMG96S should be car-ried out as follows:

Insert device

The UMG96S is designed for mounting in lowvoltage distributions, which can lead overvolt-age of the class III at maximum.The mounting position is random. For the instal-lation in face plates or panel doors, the deliv-ered fixing brackets must be used.

Programm current and voltage transformerWhen the device is delivered, a current trans-former of 5/5A is set.The voltage transformer ratio may only bechanged, when a voltage transformer is con-nected.While using voltage transformers, the givenmeasurement and operating voltage mustmatch the type plate of the UMG96S!

Connect measurement and operating voltageThe dimension of the measurement and oper-ating voltage is indicated on the type plate.

Measurement and operating voltage,which do not correspond to the numberson type plate can lead to malfunctionsor damage of the instrument.

The wires for the measuring voltage of theUMG96S must be suitable for voltage up to300VAC against ground or 520VAC phase tophase.After connection of the mentioned measure-ment and operating voltage to the UMG96S, allsegments of the display appear. About two sec-onds later, the UMG96S changes to the firstmeasured value indication.If no indication appears, please check, if theoperating voltage is within the rated range.

panel max. 6

9 0 9

6

49

D S U B - 9

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

42 6

2,5

R J 1 1

Fixing bracket

RS 232

RS 485 I / O

UMG96 S45-65Hz 3VAMade in GermanyS V J M A D E P

Strommessung/Current Measurement

k lL2 L3L1

k lk l

5 7 108 9

N L3 L2 L1

6

SpannungsmessungVoltage Measurement

15 14 13 12 11 4 3 2 1

Profibus

Cut out: 92 +0,8 x 92 +0,8 mm

Page 25: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 25/96

Page 26: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 26/96

Page 26

Removal of errors

Fault

Display dark.

A measured valuedisplay cannot beretrieved.

No current indicated.

Current too small.

Wrong current.

Wrong voltage L-N.

Voltage L-L toosmall / too big.

Possible reason

Fuse may have released.Device defective.

The display has been deletedfrom measured value selec-tion.

The corresponding measuringvoltage has not been con-nected.

Current measurement inwrong phase.

Current measurement inwrong phase.Current transformer ratiobadly programmed.

Exceeding of measuringrange.

The maximum current input isexceeded by harmonics.

The current at measuring in-put has been underscored.

Measurement in wrong phase

Voltage transformer wronglyprogrammed.

Outer conductors exchanged.

Wrong connection.

Remedy

Renew fuse.Send device to the manufacturer for re-

pair.

The desired display must be added intothe measured value selection.

Connect the corresponding measuredvoltage.

Check and correct connection.

Check and correct connection.

Read CT ratio on CT and program cor-rectly.

Select and program CT with higher ratio.

Select and program CT with higher ratio.Attention! Please ensure, that the meas-uring inputs are not overloaded.

Select and program CT with lower ratio.

Check and correct connection.

Read voltage transformer ratio at voltagetransformer and program accordingly.

Check and correct connection.Attention! Please ensure, that the meas-uring inputs are not overloaded.

Check and correct connection.

Page 27: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 27/96

Page 28: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 28/96

Page 28

Error messagesThe UMG96S shows three different error mes-sages: - Warnings , - Heavy errors and

- Exceeding of measuring range .For warnings and heavy errors, the symbol"EEE " and a corresponding error number is in-dicated.

L1

L2

L3

Error number

Symbol for error messageThe error number is assembled by the heavy error 910 and the internal reason of error 0x0 1 .In this example an error occured while reading

the calibration data from EEPROM. The device must be sent to the manufacturer.

L1

L2

L3

Example: Error num ber 911 The UMG96S displays error number 911 .

The three digit error number consists of the de-scription of the error and a possible reason forthe error, provided that UMG96S can detect it.

L1

L2

L3

Reason of error Error description

Symbol for error message

Page 29: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 29/96

Page 29

Exceeding of measuring rangeExceedings of measuring range are indicatedas long as they occur and cannot be confirmed.An exceeding occurs, when one or more cur-

rent or voltage input is outside the specifiedrange.With the keys "upwards" the phase, in which theexceeding occured, is marked. The symbols "V"and "A" indicate, if the exceeding was causedby voltage or current.

Internal reasons of errorsIn some cases, the UMG96S can detect an in-ternal error and indicate the following errorcodes. The device must be sent to the manu-facturer for checking.

Error Reason for Error

0x01 EEPROM does not answer0x02 Exceeding of address range.0x04 Checksum error.0x08 Error in internal I2C-Bus.

Attention!Voltage and current out of the specifiedrange can damage the instrument.

Exceeding of measuring rangein phase L1/L2/L3

A = Current path

V = Voltage path

WarningsWarnings are not heavy errors and can be con-firmed by the keys 1 or 2. The retrieving andindication of measured values continues. Thiserror will be displayed with every voltage return.The instrument should be sent to the manufac-turer for checking.

Error Description

100 Error while writing programming data.110 Error while writing a counter.120 Error while writing maximum values.220 Error while reading counters.230 Error while reading maximum values.300 Error of clock.310 Data memory not found.400 Profibus not found.500 No voltage higher 50V with frequency

in the range 45...65Hz in phase L1found.

Heavy errorsThe device must be sent to the manufacturerfor checking.

Error Description

800 Error while writing a block.810 Error while writing calibration.900 Error while reading a block.910 Error while reading calibration.

L1

L2

L3

VA

Hz

Page 30: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 30/96

Page 30

Usage and displayThe usage of the UMG96S is carried out via thekeys 1 and 2. Measured values and program-ming data are indicated on a LCD display. Theindication mode and programming mode can be

distinguished. It is possible to avoid an uninten-tional changing of programming data by enter-ing a password.

Indication modeIn indication mode, please scroll through theprogrammed measured values by using thekeys 1 and 2. When the device is delivered, allmeasured value indications of profile 1 can beretrieved. For each measured value, up to threemeasured values are indicated. The measuredvalue rotation can display selected measuredvalue indications one after the other with aselectable changing time.

Programming modeIn programming mode the neccessary settingsof the UMG96S can be indicated and changed.Pressing key 1 and 2 simultaneously for about1 second, you reach programming mode viapassword request. If no password was entered,you directly reach programming mode. Pro-gramming mode is marked by the text „ PRG “ inthe display.Using key 2, you can change over between thefollowing menues:

- Current transformer,- Voltage transformer,- Parameter list.

If you are in programming mode, and no keywas pressed for about 60 seconds, or key 1 and2 are pressed simultaneously, the UMG96S re-turns to indication mode.

Programming mode

Key 2Key 1

1 2

capcosind

ϕϕϕϕϕ

capcosind

ϕϕϕϕϕ

capcosind

ϕϕϕϕϕ

L1

L2

L3

Hz S

CT VT K1 K2

L-L

PRGMkWhMkVArh

Page 31: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 31/96

Page 31

Key functions

21

2

21

simultaneously

long short1

simultaneously

l o n g

s h o r t

Measuredvalues

Program-ming Menue

Measuredvalues

Measuredvalues

Measuredvalues

Program-ming Menue

2

1Confirm selection

Short number +1Long number -1

Program-ming Menue

2 short value *10(move decimal point to the right) long value /10(move decimal point to the left)

Indication mode Password Programming mode

S c r o

l l

P r o g r a m m

i n g

C h a n g e m o

d e

l o n g

s h o r t

Program-ming Menue

2flashing

2

Page 32: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 32/96

Page 33: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 33/96

Page 33

Program parametersPress both keys simultaneously for about 1 sec-ond.If a user password was programmed, the pass-word request appears with "000".The first number of the user password flashesand can be changed with key 2. Pressing key1, the next number is selected and flashes.If the right combination was entered or no userpassword was programmed, you reach pro-gramming mode.

In programming mode the menue for the cur-rent transformer appears first.With key 2, move to programming menue forvoltage transformer and parameter list.

The parameters for current and voltage trans-former can only be read at UMG96S.

PRG

k AL1

L2

L3 CT

PRG

VL1

L2

L3 VT

L-L

Change a parameter at parameter list.Confirm selection with key 1.The last selected address and the correspond-ing value is indicated.The first number of the address is flashing.

Select address.Select address with key 1 and change with key2.

Change value.The desired address is set.Select a number of the value with key 1 andchange with key 2.

Leave programmingPress both keys simultaneously for about 1 sec-ond.

L1

L2

L3

PRG

value

L1

L2

L3

PRG

Address

L1

L2

L3

Page 34: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 34/96

Page 35: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 35/96

Page 35

Net frequency (Adr.063)The net frequency is detected from the meas-uring voltage of phase 1. The scanning fre-quency for the voltage and current inputs is cal-culated from the net frequency.At measurements with very disturbed voltage,

the frequency cannot be detected accurateenough. Voltage disturbances occur at consum-ers, which are operated with phase anglemodulated power.For measurements, which show strong distor-tion, the corresponding net frequency should befixed. Distortion of the current have no influenceon frequency detection.

If the measuring voltage is missing, no net fre-quency can be detected, and no scanning fre-

quency can be calculated. The error message"500" is displayed and can be confirmed. Volt-age, current and all resulting values are not cal-culated and indicated by zero.If the current shall be measured without meas-uring frequency, the net frequency must be se-lected as a fix frequency at UMG96S.

The determination of the net frequency can becarried out automatically or programmed fixely.The following settings for the destination of thenet frequency are at your disposal: 0 - Automatical frequency detection 1 - Fix frequency 50Hz 2 - Fix frequency 60Hz

Real energyThe UMG96S has four energy meters: Threereal energy meters and one reactive energymeter.

Sum real en-ergyHT/consump-tion

Sum real en-ergy

The real energy meter on address 422 andaddress 424 measures either consumption orhigh and low tariff (HT and NT).The changeover between consumption/supplyand HT/NT is carried out by a digital input (Op-tion). When the device is delivered, the energymeters measure the consumed and suppliedenergy.If one of the digital inputs is programmed forHT/NT changeover, the energy meters do nolonger measure the consumed and suppliedreal energy, but real energy during HT and NTtime. The HT/NT changeover is effected in ad-dress 071.Addr. 071 = 0 => real energy meter NT active.

Addr. 071 = 1 => real energy meter HT active.

Addr. Description

416 Sum real energy (without reverse running stop)418 Sum reactive energy (inductive)422 Sum real energy (Consumption or HT)424 Sum real energy (Supply or NT)

L1

L2

L3 K1 K2

kWh

L1

L2

L3 K1 K2

kWh

Psum = 12 345 678 kWh

Psum (HT) = 134 192 kWh

Page 36: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 36/96

Page 37: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 37/96

Page 37

Voltage transformer (Addr. 602)As secondary and primary voltage, the numbersin the display are given in line to line voltage(L-L). The transformer ratio is calculated by theprimary and secondary voltage.When the device is delivered, a ratio of 1:1 is

set.300V Standard version: 400V/400V (148..520V)150V Special version: 100V/100V (85..260V)

For the 300V standard version, voltage trans-formers with a secondary in the range of 148Vto 520V can be connected.

In programming mode, the VT ratio is indicatedby the symbol „ VT“.

Secondary in Volt

PRG

kVL1

L2

L3 VT

L-L

Primary voltage in kV

ProgrammingIn programming mode, please scroll to the set-ting of the voltage transformer with key 2. Con-firm with key 1.

The first number of the primary is flashing andcan be changed with key 2. Confirming with key1, the next number is selected and flashes.If the complete number is flashing, the decimalpoint can be moved.If no number is flashing, scroll to the indicationof the programming of outputs with key 2.

VT, primary (Addr.602)

Voltage transformer,secondary (Addr.603)

Line to line

Symbol for VT ratio

PRG

VL1

L2

L3 VT

L-L

Page 38: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 38/96

Page 38

Harmonics (Addr.221)Harmonics are the integer multiple of the fun-damental wave. The UMG96S measures thefundamental of voltage in the range of 45 to 65Hz. The calculated harmonic voltage and cur-rent is related to this fundamental. For strongly

distorted voltage, the fundamental cannot bedetermined accurate enough. In order to beable to calculate the harmonics nevertheless, afix fundamental of 50 or 60Hz can be selected.Please see chapter "scanning frequency".The UMG96S calculates harmonics up to the15th multiple of the fundamental.

PRGMkWhMkVArh

L1

L2

L3

k A

In this example, the 15th harmonic of current inL3 is indicated.

Number of partialharmonic

Current har-monic

Phase L3

Measured value

Total harmonic distortion factor THD(Addr.269)The total harmonic distortion factor, which iscalculated by UMG96S for current and voltage,represents the ratio of the effective value of the

distorted quantity compared to the effectivevalue of the measured quantity. The total har-monic distortion factor is given in per cent:Total harmonic distortion of current THDI:

Partial harmonics (Addr.221)In the further description, the single harmonicsare described as partial harmonics.The partial harmonics of the current are givenin Ampere and the partial harmonics of voltageare given in Volt.

Total harmonic distortion of voltage THDU:

I

2

1

2

THD I II

=-

x 100%

U

2

1

2

THD U UU

=-

x 100%

PRGMkWhMkVArh

L1

L2

L3

Voltage,Phase L3-N

In this example, the total harmonic distortionfactor THD of voltage is indicated for phase L3.

Value

Page 39: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 39/96

Page 39

Measured value rotationAll measured values are calculated once persecond and can be called up on the display.Two methods are available for calling up themeasured values:- The automatic changing of measured values,

which is described as measured value rotation.- The selection of a measured value via thekeys 1 and 2 from a selected indication profile.

Both methods are available simultaneously. Themeasured value rotation is active, if at least onemeasured value indication is selected with achanging time longer than 0 seconds.If a key is pressed, please scroll through themeasured value indications of the selected pro-file. If no key was pressed for about 60 sec-

onds, measured value rotation is started, andthe selected measured values are indicated cy-clically one after the other.

Changing time (Addr.059)Setting range: 0 .. 60 secondsIf 0 seconds are set, no changing of the indica-tions is effected.The changing time is valid for all measuredvalue rotation profiles.

Measured value rotation profiles (Addr.061)Setting range: 0 .. 30 - Rotation profile No.0, fix.1 - Rotation profile No.1, fix.2 - Rotation profile No.2, fix.3 - Rotation profile No.3, specifically. This pro-file can be programmed by the softwarePSWbasic only.

Rotation profile No.0(See page 86 to 89)

A B C D E F G H

01 x x x02 x x x03 x x x x04 x x x x05 x x x06 x x x x07 x x x08 x x x09 x x x10 x x x11 x x x12 x x x13 x x x14 x x x15 x16 x x17 x18 x x x19 x20 x x x x x x x x21 x x x x x x x x x22 x x x x x x x x x23 x x x x x x x x x24 x x x x x x x x x25 x x x x x x x x x26 x x x x x x x x x27 x x x x x x x x x28 x x x x x x x x x29 x x x x x x x x x30 x x x x x x x x x31 x x x x x x x x x32 x x x x x x x x x

Page 40: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 40/96

Page 40

In the overview for the measuredvalue indications, "A01" corre-sponds to the indication of voltageL-N.

Rotation profile No.1(See page 86 to 89)

A B C D E F G H

01 x x x02 x x x03 x x x x04 x x x x05 x x x06 x x x x07 x x x08 x x x09 x x x10 x x x11 x x x12 x x x13 x x x14 x x x15 x16 x x17 x18 x x x19 x20 x x x x x x x x21 x x x x x x x x x22 x x x x x x x x x23 x x x x x x x x x24 x x x x x x x x x25 x x x x x x x x x26 x x x x x x x x x27 x x x x x x x x x28 x x x x x x x x x29 x x x x x x x x x30 x x x x x x x x x31 x x x x x x x x x32 x x x x x x x x x

Rotation profile No.2(See page 86 to 89)

A B C D E F G H

01 x x x02 x x x03 x x x x04 x x x x05 x x x06 x x x x07 x x x08 x x x09 x x x10 x x x11 x x x12 x x x13 x x x14 x x x15 x16 x x17 x18 x x x19 x20 x x x x x x x x21 x x x x x x x x x22 x x x x x x x x x23 x x x x x x x x x24 x x x x x x x x x25 x x x x x x x x x26 x x x x x x x x x27 x x x x x x x x x28 x x x x x x x x x29 x x x x x x x x x30 x x x x x x x x x31 x x x x x x x x x32 x x x x x x x x x

Page 41: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 41/96

Page 41

Rotation profile No.3 (Addr.605)The specific profile No. 3 can only be config-ured by the PC software PSWbasic but not di-rectly at UMG96S. For this profile, a connection

between UMG96S and PC via serial interface(RS232 or RS485) is mandatory.

FormatFormat of the rotation profile:STRING

Byte 1 = row 1,Bit1 = 1. measured value table,Bit2 = 2. measured value table,...Bit8 = 8. measured value table.

Byte 2 = row 2,Bit1 = 1. measured value table,Bit2 = 2. measured value table,...Bit8 = 8. measured value table

....Byte 32 = row 32,

Bit1 = 1.measured value table,Bit2 = 2. measured value table,....Bit8 = 8. measured value table.

Roration profile No.3(Specifically, can only be programmed by PC!)

A B C D E F G H

01 x x x02 x x x03 x x x x04 x x x x05 x x x06 x x x x07 x x x08 x x x09 x x x10 x x x11 x x x12 x x x13 x x x14 x x x15 x16 x x17 x18 x x x19 x20 x x x x x x x x21 x x x x x x x x x22 x x x x x x x x x23 x x x x x x x x x24 x x x x x x x x x25 x x x x x x x x x26 x x x x x x x x x27 x x x x x x x x x28 x x x x x x x x x29 x x x x x x x x x30 x x x x x x x x x31 x x x x x x x x x32 x x x x x x x x x

Page 42: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 42/96

Page 43: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 43/96

Page 44: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 44/96

Page 44

Delete energy (Addr.009)The UMG96S contains 4 energy meters, threereal energy meters and one reactive energymeter.

User password (Addr.011)To avoid unintentional changing of the program-ming data, a password can be programmed.After entering the correct user password, achanging into the following programmingmenue is possible.

When the device is delivered, no password isentered. In this case, the password menue iscancelled, and you reach the current trans-former menue at once.

If a user password was programmed, the pass-word menue appears, indicating „000“.The first number of the password is flashingand can be changed using key 2. Pressing key1, the next number is selected and flashes.If the right number combination was entered,

you reach the programming menue for the cur-rent transformer.

If a changed user password is not knownanymore, the device must be sent to the manu-facturer.

The energy meters can only be deleted simul-taneously.To delete the contents of the energy meters,address 009 must be overwritten by „001“.

Addr. Description

416 Sum real energy (without reverse running stop)418 Sum reactive energy (inductive)422 Sum real energy (consumption or HT)424 Sum real energy (supply or NT)

Page 45: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 45/96

Page 46: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 46/96

Page 46

Serial number (Addr. 911)The serial number, which is indicated by theUMG96S, is a 6 digit part of the serial numberon type plate.The serial number cannot be changed.

Serial number on type plate

Indicated serial number

PRGMkWhMkVArh

L1

L2

L3

PRG

XX00-0000

Time detectionThe UMG96S detects the operating hours ofthe UMG96S, and the total running time of eachcomparator. The time is measured with a solu-tion of 0.1 hours, indicated in hours.For the call up, the time is marked by the num-

bers 0 to 6:0 = Operating hours counter (Addr.394)1 = Total run. time, Comparator 1A (Addr.396)2 = Total run. time, Comparator 2A (Addr.398)3 = Total run. time, Comparator 1A (Addr.400)4 = Total run. time, Comparator 2A (Addr.402)5 = Total run. time, Comparator 1A (Addr.404)6 = Total run. time, Comparator 2A (Addr.406)

In the indication, up to 99999.9 h (=11,4 years)can be indicated.

Operating hours counter (Addr. 394)The operating hours counter measures thetime, in which the UMG96S detects and indi-cates measured data. The operating hourscounter cannot be reset.

Total running time comparatorsThe total running time of a comparator is thesum of all time, in which the comparator result

violates its limit. The total running time of eachcomparator can be reset individually.

L1

L2

L3

h

Working hours counter

Example: Indication of operating hours The UMG96S indicates the operating hours by the number 140,8h . This corresponds to 140 hours and 60 industrial minutes.100 industrial minutes correspond to 60 min- utes.In this example, the 80 industrial minutes refer to 48 minutes.

Page 47: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 47/96

Page 47

Software Release (Addr. 913)The internal software of the UMG96S is im-proved and expanded continuously. The soft-ware release of the device is given by a 3 digitnumber. The software release cannot bechanged by the user.

Hardware expansion (Addr. 914)The available options of the UMG96S can becalled up under the address 914. For eachavailable option, a Bit is set. The result is a bi-nary value, that is indicated in decimal form bythe UMG96S.

Example 1The UMG96S indicates the decimal value 96 under address 914.

OptionHex Binary Description

0x01 0000 0001 Memory (EEPROM)0x02 0000 0010 Clock0x04 0000 0100 Analogue outputs 1/20x08 0000 1000 Digital output or

pulse output 1/20x10 0001 0000 Digital input 1/20x20 0010 0000 Profibus0x40 0100 0000 RS2320x80 1000 0000 RS485

Option Profibus Option RS232

96 = 0x60 = 0110 0000

Example 2 The UMG96S displays the decimal value 248 under address 914.

Digital output 1/2 Digital input 1/2 Profibus RS232 RS485

24 8 = 0xf8 = 1111 1000

Address =914

Value= 96

L1

L2

L3

Page 48: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 48/96

Page 49: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 49/96

Page 50: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 50/96

Page 50

RS232 interface (Option)The possible distance between two RS232 de-vices depends on the used cable and baud rate.As an estimation, for a baud rate of 9600 Baud,a distance of 15m should not be exceeded(maximum 30m).The allowed ohmic load must be higher than3kOhm and the capacitive load effected by thecable must be smaller than 2500pF.With the PC cable (2m) that belongs to the con-tents of delivery of the RS232 interface, themaximum baud rate is 38,4kBit/s.

UMG96S

12

13

11

R J 1 1

S l e e v e

14

15

TXD

GNDRXD

A

B

Input/Output 2 (003)

Pulse output Wq (003 =0)

Digital output (003 = 1)

Analogue output(003 = 2)

Digital input (003 = 3,5)

Profibus-Remote (003 = 4)

Input/Output 1 (002)

Pulse output Wp (002 =0)

Digital output (002 = 1)

Analogue output(002 = 2)

Digital input (002 = 3,5)Profibus-Remote (002 = 4)

C o m p a r a

t o r g r o u p

1

C

o m p a r a

t o r g r o u p

2

Basic PCB

RS485 (MODBUS RTU)Interface

RS232 (MODBUS RTU)Interface

S e r i a

l i n t e r f a c e

Page 51: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 51/96

Page 51

Connection example

PC cable (2m)Part no. 08.01.501

RS232/DSUB-9 RS232/RJ11

UMG96S

PSWbasicProfessional

Diagr. Connect the UMG96S to a PC via PC cable.

ConverterRS485/RS232

RS232RS485RS232 RS485

UMG96SUMG96S

PSWbasicProfessional

Diagr. Connect UMG96S via an interface converter to a PC.

Modem cable (2m)Part no. 08.01.503

PSWbasicProfessional

UMG96S

ModemRxD TxD

ModemRxD TxD

RS232/RJ11

Diagr. Connect the UMG96S to PC via modem.

Diagr. PC cable, part no. 08.01.501 (2m)

PC cable

Pin 9Pin 3Pin 2Pin 5Pin 7Pin 8Pin 1Pin 6Pin 4

DSUB-9Plug/maleRJ11

Pin 4Pin 3Pin 2Pin 1

TxD

RxD

GND

TxD

RxD

GND

Diagr. Modem cable, part no. 08.01.503 (2m)

Modem cable

Pin 9Pin 3Pin 2Pin 5Pin 7Pin 8Pin 1Pin 6Pin 4

DSUB-9Sleeve/femaleRJ11

Pin 4Pin 3Pin 2Pin 1

TxD

RxD

GND

RxD

TxD

GND

Page 52: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 52/96

Page 52

UMG96S

12

13

11

R J 1 1

S l e e v e

14

15

TXD

GNDRXD

A

B

Input/Output 2 (003)

Pulse output Wq (003 =0)

Digital output (003 = 1)

Analogue output (003 = 2)

Digital input (003 = 3,5)

Profibus-Remote (003 = 4)

Input/Output 1 (002)

Pulse output Wp (002 =0)

Digital output (002 = 1)

Analogue output (002 = 2)

Digital input (002 = 3,5)Profibus-Remote (002 = 4)

C o m p a r a

t o r g r o u p

1

C

o m p a r a

t o r g r o u p

2

Basic PCB

RS485 (MODBUS RTU)Interface

RS232 (MODBUS RTU)Interface

S e r i a

l i n t e r f a c e

Fieldbus (RS485)Termination resistorsAll units shall be connected in a single line busstructure. Up to 32 units can be located withinone segment. Use termination resistors at bothends of each segment.Repeaters must be used to connect the seg-ments if more than 32 units or longer lines areneeded. Termination resistor.

Unit with RS485 port.

Fig. Double terminated bus structure

Page 53: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 53/96

Page 53

Earthing terminal

Panel

Bus cable

Shielding Single wires 120 Ohm 1/4WTermination resistor

UMG96S

1 4

B

1 5

A

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7

1 2 3 4 5 6 7

1 2 3 4 5 6 7

1 2 3 4 5 6 7

UMG96S

1 4

B

1 5

A

ShieldingUse shielded twisted pair cable for the RS485bus. To ensure sufficient shielding the cableshield connection must be short and plane-style. Do not use pigtail shield connection.

KabeltypUnitronic Li2YCY(TP)2x2x0,22 (Lapp Kabel).

Cable length1200m at 38400 baud.

Page 54: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 54/96

Page 54

Profibus DP (Option)The UMG96S has a 9-pole SubD sleeve on theback side. On this sleeve, a RS485 interface iswired, which is operated by Profibus DP proto-col. Via this RS485 interface, up to 32 partici-pants can be connected. If more participantsmust be connected, a repeater must be inter-connected.

GSD fileThe main data of the UMG96S has got the filename „U96S0781.GSD“.

Attention!The RS232/RS485 interface and theProfibus interface are not separated gal-vanically from each other.

C o m p a r a

t o r g r o u p

1

C o m p a r a

t o r g r o u p

2

Digital input 2

UMG96S

12

Additional PCB 2

13

11

R J 1 1

S l e e v e

14

15

Digital input 1

DSUB 9

Profibus DP(Option)

A B- + TXD

GNDRXD

A

B

8 35 6

Input/Output 2 (003)

Pulse output Wq (003 =0)

Digital output (003 = 1)

Analogue output (003 = 2)

Digital input (003 = 3,5)

Profibus-Remote (003 = 4)

Input/Output 1 (002)

Pulse output Wp (002 =0)

Digital output (002 = 1)

Analogue output (002 = 2)

Digital input (002 = 3,5)Profibus-Remote (002 = 4)

RS485 (MODBUS RTU)Interface

RS232 (MODBUS RTU)Interface

S e r i a

l i n t e r f a c e

Basic PCB

Page 55: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 55/96

Page 56: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 56/96

Page 56

Profibus profilesThere are many measured values available fortransmission. To keep the data to be transmit-ted via Profibus small in number, only a selec-tion of the possible measured data will be trans-mitted by UMG96S. The selected measured

values are combined in 14 different profiles.The programming of specific data is not possi-ble. The profiles have the description of profile number 1 to 14.If a certain profile is required by the Profibusmaster, please write the desired profile numberinto the first Byte of the output range of thePLC. The UMG96S supplies the input range ofthe PLC with the first 2 Bytes of the actual pro-file number and the condition of the three com-parators.

If not all values of the selected profile areneeded, you can pick the first measured valuesfrom a profile only.Via the 2nd Byte of the output range of thePLC, the two outputs of the UMG96S can beactivated. The relation is:Output 1 = Input/Output 1 = Terminal 12Output 2 = Input/Output 2 = Terminal 13

Profile formatsThe measured values can be retrieved in 14profiles in integer and floating point format. Ad-ditionally, the formats "high before low byte" or"low before high byte" can be provided. Meas-

ured values in integer format do not containcurrent and voltage transformer ratios.

Profibus profile No. Format

1..14 + 128 Integer format 1..14 + 31 + 128 Float formats (4Byte)

Table: Measured values "high before low byte"

Profibus profile No. Format

1..14 Integer format 1..14 + 31 Float formats (4Byte)

Table: Measured values "low before high byte"

Diagr. Data transmission PLC - UMG96S.

UMG96S

Input range of the PLC

1. Byte Back signal of profile number2. Byte Condition of comparators

Format:2 x 3 Conditions of comparators.Condition of two digital inputs.

3. Byte Contents of the selected profile... .... ..124. Byte

Output range of the PLC

1. Byte Profile number.2. Byte Bit 0 Set Output 1.

Bit 1 Set output 2.0= off = Transistor blocked.1= on = Transistor active.SPS

Page 57: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 57/96

Page 58: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 58/96

Page 58

Profibus profile 8Values Bytesthd_i_L1 2thd_i_L2 2thd_i_L3 2dft_i_1_L1 2

dft_i_1_L2 2dft_i_1_L3 2dft_i_3_L1 2dft_i_3_L2 2dft_i_3_L3 2dft_i_5_L1 2dft_i_5_L2 2dft_i_5_L3 2dft_i_7_L1 2dft_i_7_L2 2dft_i_7_L3 2

dft_i_9_L1 2dft_i_9_L2 2dft_i_9_L3 2dft_i_11_L1 2dft_i_11_L2 2dft_i_11_L3 2dft_i_13_L1 2dft_i_13_L2 2dft_i_13_L3 2dft_i_15_L1 2dft_i_15_L2 2dft_i_15_L3 2Sum 54Bytes

Profibus profile 9Values Bytesthd_u_L1 2thd_u_L2 2thd_u_L3 2dft_u_1_L1 2

dft_u_1_L2 2dft_u_1_L3 2dft_u_3_L1 2dft_u_3_L2 2dft_u_3_L3 2dft_u_5_L1 2dft_u_5_L2 2dft_u_5_L3 2dft_u_7_L1 2dft_u_7_L2 2dft_u_7_L3 2

dft_u_9_L1 2dft_u_9_L2 2dft_u_9_L3 2dft_u_11_L1 2dft_u_11_L2 2dft_u_11_L3 2dft_u_13_L1 2dft_u_13_L2 2dft_u_13_L3 2dft_u_15_L1 2dft_u_15_L2 2dft_u_15_L3 2Sum 54Bytes

Profibus profile 10Values Bytestdh_i_L1 2thd_i_L2 2thd_i_L3 2thd_u_L1 2

thd_u_L2 2thd_u_L3 2dft_i_3_L1 2dft_i_3_L2 2dft_i_3_L3 2dft_u_3_L1 2dft_u_3_L2 2dft_u_3_L3 2dft_i_5_L1 2dft_i_5_L2 2dft_i_5_L3 2

dft_u_5_L1 2dft_u_5_L2 2dft_u_5_L3 2dft_i_7_L1 2dft_i_7_L2 2dft_i_7_L3 2dft_u_7_L1 2dft_u_7_L2 2dft_u_7_L3 2Sum 48Bytes

Profibus profile 11Values Bytesdft_i_9_L1 2dft_i_9_L2 2dft_i_9_L3 2dft_u_9_L1 2

dft_u_9_L2 2dft_u_9_L3 2dft_i_11_L1 2dft_i_11_L2 2dft_i_11_L3 2dft_u_11_L1 2dft_u_11_L2 2dft_u_11_L3 2dft_i_13_L1 2dft_i_13_L2 2dft_i_13_L3 2

dft_u_13_L1 2dft_u_13_L2 2dft_u_13_L3 2dft_i_15_L1 2dft_i_15_L2 2dft_i_15_L3 2dft_u_15_L1 2dft_u_15_L2 2dft_u_15_L3 2Sum 48Bytes

Page 59: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 59/96

Page 59

Profibus profile 13Values Bytesthd_i_L1_max 2thd_i_L2_max 2thd_i_L3_max 2dft_i_1_L1_max 2

dft_i_1_L2_max 2dft_i_1_L3_max 2dft_i_3_L1_ma 2dft_i_3_L2_ma 2dft_i_3_L3_ma 2dft_i_5_L1_ma 2dft_i_5_L2_ma 2dft_i_5_L3_ma 2dft_i_7_L1_ma 2dft_i_7_L2_ma 2dft_i_7_L3_ma 2

dft_i_9_L1_max 2dft_i_9_L2_max 2dft_i_9_L3_max 2dft_i_11_L1_max 2dft_i_11_L2_max 2dft_i_11_L3_max 2dft_i_13_L1_max 2dft_i_13_L2_max 2dft_i_13_L3_max 2dft_i_15_L1_max 2dft_i_15_L2_max 2dft_i_15_L3_max 2Sum 54Bytes

Profibus profile 14Values Bytesthd_u_L1_max 2thd_u_L2_max 2thd_u_L3_max 2dft_u_1_L1_max 2

dft_u_1_L2_max 2dft_u_1_L3_max 2dft_u_3_L1_max 2dft_u_3_L2_max 2dft_u_3_L3_max 2dft_u_5_L1_max 2dft_u_5_L2_max 2dft_u_5_L3_max 2dft_u_7_L1_max 2dft_u_7_L2_max 2dft_u_7_L3_max 2

dft_u_9_L1_max 2dft_u_9_L2_max 2dft_u_9_L3_max 2dft_u_11_L1_max 2dft_u_11_L2_max 2dft_u_11_L3_max 2dft_u_13_L1_max 2dft_u_13_L2_max 2dft_u_13_L3_max 2dft_u_15_L1_max 2dft_u_15_L2_max 2dft_u_15_L3_max 2Sum 54Bytes

Profibus profile 12Values BytesP_sum_max 2P_sum_max_mean 2I_sum_max 2I_sum_max_mean 2

phi_sum_max 2S_sum_max 2Q_sum_max 2Uln L1_max 2Uln L2_max 2Uln L2_max 2Uln L1_min 2Uln L2_min 2Uln L2_min 2UL1-L2_max 2UL2-L3_max 2

UL1-L3_max 2UL1-L2_min 2UL2-L3_min 2UL1-L3_min 2IL1_max 2IL2_max 2IL3_max 2P1_max 2P2_max 2P3_max 2Q1_max 2Q2_max 2Q3_max 2S1_max 2S2_max 2S3_max 2Sum 62Bytes

Page 60: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 60/96

Page 60

Inputs and outputsThe terminals 12 and 13 at UMG96S can beassigned to the following functions: 0 = Pulse output, 1 = Digital output, 2 = Analogue output, 3 = Digital input, 4 = Profibus-Remote output (Option), 5 = HT/NT changeover via digital input , 6 = Synchronization of storage of profile 1

via digital input.

The desired function (0..6) is written into ad-dress 002 related to the terminal 12 or address003 related to terminal 13.

R S

4 8 5

Currentmeasurement

1 5

1 4

1 3

1 2 1 1

1 0 8 7 9

1 3 2 4

6 5

I / OMeasuring and

operating

voltage

Input/Output 2 (003)

Pulse output Wp (003 =0)

Digital output (003= 1)

Analogue output (003 = 2)

Digital input (003 = 3,5)

Profibus-Remote (003 = 4)

Input/Output 1 (002)

Pulse output Wp (002 =0)

Digital output (002 = 1)

Analogue output (002 = 2)

Digital input (002 = 3,5)

Profibus-Remote (002 = 4)

12

13

11

UMG96S

+

A simultaneous use of the various functions onone terminal is not possible. The simultaneoususe of the functions on different terminals ispossible. Please note, that the common refer-ence for the terminals 12 and 13 is on terminal11(+).

combination possibilities of the inputs and out-puts:a) 2 Digital outputs,b) 2 Digital inputs,c) 2 Analogue outputs,d) 1 Digital output and 1 Analogue output,e) 1 Digital output and 1 Digital input.

Page 61: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 61/96

Page 62: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 62/96

Page 63: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 63/96

Page 63

Minimum pulse duration (Addr. 010)The minimum pulse duration can be pro-grammed on 10 ms steps in a range between50ms and 1000ms. The shortest pulse pausecorresponds to the programmed minimumpulse duration.

At a minimum pulse duration of 50ms the maxi-mum pulse frequency is 10Hz. If less pulsesmust be transmitted, the pulse pause becomeslonger. The programmed minimum pulse dura-tion of 50ms remains constantly.

Attention!When the real energy meter with reverserunning stop works, pulses are onlygiven out while consumption of energy.As the reactive energy meter works withreverse running stop, pulses are onlytransmitted at inductive load.

Attention!The pulse pause is not proportional topower.

Diagr. Maximum pulse frequency at minimum pulse duration of 50ms.

Impuls50ms

Pulse pause50ms

100ms => 10Hz

Minimum pulse duration

Pulse pause

Minimum pulse duration

Impuls0.05s

Diagr. Pulse frequency <10Hz at minimum

pulse duration of 50ms.

Pulse valenceThe pulse valence tells you, how much energyis related to one pulse (Wh or kvarh).

The pulse valence may not be confused withthe meter constant. The meter constant is givenin

Meter constant = rotations per kWh

The correspondance between pulse valenceand meter constant can be seen in the follow-ing relations: Meter constant = 1 / pulse valence Pulse valence = 1 / meter constant

Pulse valence =energy

max. pulse frequency 3600s

Pulse fr

eequency in Wh/pulseEnergy at WhMax. puls frequency at Hz

Page 64: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 64/96

Page 64

Diagr. Maximum pulse frequency at minimum pulse duration 50ms.

2.) Determin e min imu m pu lse durat ion The UMG96S can transmit pulses with a fre- quency of up to 10Hz.

The data collecting device can retrieve pulses with a frequency of 50Hz in this example. The minimum pulse duration at UMG96S can be set to 50ms.

Minimum pulse duration Addr.010 = 50

Example : Program pu lse output The UMG96S shall measure real energy in a distribution, and transmit it via pulse output to a data collecting device. The distribution provides a real power of 400kW. The data collecting de- vice can retrieve pulse frequencies up to 50Hz.

At UMG96S, the pu l se ou tpu t , the min imum pulse dura t ion and the puls e valence must be programmed.

Input/Output 2 (003)

Pulse output Wp (003 =0)

Digital output (003 = 1)

Analogue output (003 = 2)

Digital input (003 = 3,5)

Profibus-Remote (003 = 4)

Input/Output 1 (002)

Pulse output Wp (002 =0)

Digital output (002 = 1)

Analogue output (002 = 2)

Digital input (002 = 3,5)

Profibus-Remote (002 = 4)

12

13

11

UMG96S

+

1.) Select puls e outp ut Assign terminal 12 to the function pulse output.

Input/Output 1 Addr.002=0

Diagr: Connection example for the connection of the terminals 11 and 13 as pulse output.

+ -

230V AC

24V DC

External

power supply

+24V=11

12

13UMG96SDigital/pulse outputs

1,5k

Data col-lection

Pulse50ms

Pulse pause50ms

100ms => 10Hz

Minimum pulse duration

Page 65: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 65/96

Page 65

3.) Determination of pu lse valence The energy, which is consumed within 1 hour can be calculated as: Energy = Real power * t ime Energy = 400kW *1h Energy = 400kWh

If a pulse valence of 400kWh per pulse is set,the UMG96S transmits one pulse per hour at full load, which corresponds to a pulse fre- quency of

= 1 pulse/h = 1 pulse/3600Sec.= 1/3600 Hz = 0,00028 Hz

With this pulse valence, very few pulses are transmitted. Supervision of energy in the range of minutes is not possible.

But UMG96S can provide up to 10 pulses per second (10Hz), and the data collecting device can detect 50 pulses per second (50Hz). A pos- sible solution is to programm the UMG96S to send a frequency of 10Hz at 400kW (or for safety reasons 500kW).

= 500kWh Energy per hour = 500kWh / 3600 = 0,14kWh = 140Wh Energy per second = 140Wh / 10 = 14Wh Energy in 1/10 sec.

This means, if 10 pulses are sent per second with a valence of 14Wh, this corresponds to the power of 500kW for one hour.

Pulse valence Addr. 004 = 14

Pulse valency =500000Wh

10Hz 3600s

Pulse valency = 14Wh/P

uulse

Pulse valence = energymax. pulse frequency 3600s

Pulse fr

eequency in Wh/pulseEnergy at WhMax. puls frequency at Hz

Page 66: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 66/96

Page 66

Digital outputTwo digital outputs can be assigned to the ter-minals 12 and 13 of UMG96S. For digital out-put 1 a 001 must be written to parameter ad-dress 002 and for digital output 2, a 001 mustbe written to parameter address 003 eine 001.

The result of a limit supervision (388,392) willbe given out by the corresponding digital out-put.

UMG96S

12

13

11

R J 1 1

S l e e v e

14

15

TXD

GNDRXD

A

B

Input/Output 2 (003)

Pulse output Wp (003 =0)

Digital output (003 = 1)

Analogue output (003 = 2)

Digital input (003 = 3,5)

Profibus-Remote (003 = 4)

Input/Output 1 (002)

Pulse output Wp (002 =0)

Digital output (002 = 1)

Analogue output (002 = 2)

Digital input (002 = 3,5)Profibus-Remote (002 = 4)

C o m p a r a

t o r g r o u p

1

C

o m p a r a

t o r g r o u p

2

Basic PCB

RS485 (MODBUS RTU)Interface

RS232 (MODBUS RTU)Interface (Option)

S e r i a

l i n t e r f a c e

Page 67: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 67/96

Page 68: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 68/96

Page 68

Limit supervisionFor limit supervision, two comparator groupswith 3 comparators each are available. The re-sults of the comparators A, B and C can becombined with AND or OR and the result canbe inverted optionally. The total combination re-sult of comparator group 1 can be assigned todigital output 1 and the combination result ofcomparator 2 can be assigned to digital output2.

Diagr. Limit supervision with digital output 1.

Measured value (Addr.015)Limit (Addr.013)Minimum time (Addr.016)Run up time (Addr. 064)Operator ">=", "<" (Addr.017)

TafelComparator AMeasured value (Addr.025)Limit (Addr.023)Minimum time (Addr.026)Run up time (Addr. 066)Operator ">=", "<" (Addr.027)

Comparator CMeasured value(Addr.020)Limit (Addr.018)Minimum time (Addr.021)Run up time (Addr. 065)Operator ">=", "<" (Addr.022)

Comparator B

Comparator group 1

- Combine results of the comparators A, B and C AND or OR (Addr.043).- Invert result (Addr.044).

Combine results of the comparators A, B and C

Total combination result (Addr.389)

Digital output 1 (Addr.002 = 1)

1112

Data memory(Addr.500)

Data memory(Addr.500)

Data memory(Addr.500)

Total run time(Addr.396)

Total run time(Addr.400)

Total run time(Addr.398)

Comparator result (Addr.386) Comparator result (Addr.388)Comparator result (Addr.387)

Attention!At UMG96S only the first three digits ofa parameter can be set.With PSWbasic, all digits of a parametercan be set.Because of the measuring accuracy ofthe UMG96S, only the first three digits ofa parameter are relevant.

Page 69: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 69/96

Page 69

Measured value (Addr. 015)The measured value indicates the address ofthe supervised measured value. The followingvalues can be assigned:000 = Comparator inactive.

001 = the comparator result can be written externally (Modbus RTU).200 .. 400 = Measured values of measured value list.

Limit (Addr. 018)The limit serves a constant of the type LONG.The limit is compared to the correspondingmeasured value.

Minimum time (Addr. 016)

For the duration of the minimum time, the com-parator result remains active (Addr.389). Theminimum time can be programmed in the rangeof 1...900 seconds.

Run up time (Addr. 064)At least for the duration of the run up time, aviolation of the limit must be active to changethe comparator result.The run up time can be programmed in therange of 1...900 seconds.

Diagr. Example, Limit violation.

Minimum time

t

Limit

Measuredvalue

Exceeding

t

Comparator re-sult

t

2 seconds

t

run up time

t

2 Seconds

Operator (Addr. 017)There are two operators available for thecomparsion of measured value and limit.Operator = 0 means higher than (>=)Operator = 1 means smaller than (<)

Comparator result (Addr.386)The result of the comparison of measured valueand limit is the comparator result.The correspondence is:0 = No limit violation.1 = Limit violation.

Data memory (Addr. 500)Changes of the comparator results can bestored in the memory (option), as long as pro-

file 4 for the memory (addr. 056) was activated.

Total running time (Addr. 396)This is the sum of all times, for which the limitwas violated.

Combination (Addr. 044)Combines the results of the comparators A, Band C AND or OR .

Invert result (Addr. 046)

The result of the combination (Addr. 046) canbe inverted or not.

Total combination result (Addr. 389)The combined comparator results of the com-parators A, B and C are in the total combina-tion result.

Page 70: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 70/96

Page 71: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 71/96

Page 71

Diagr. Connection of the analogue outputs to a PLC.

4 - 20mA

4 - 20mA

Analogueoutput 1

Analogueoutput 2

UMG96SAnalogue outputs

ExternalPower Supply

12+

13

+24V=11

+

+ -

230V AC

24V DC

L+

M

SPS

A n a

l o g u e

i n p u

t sM+

M+

M-

M-

Diagr. Connection of an analogue output to an analogue writer.

4 - 20mA

4 - 20mA

Analogueoutput 1

Analogueoutput 2

UMG96SAnalogue outputs

Externalpower supply

12+

13

+24V=11 +

+ -

230V AC

24V DC

Analoguewriter

m a x .

3 6 0 O h m

Page 72: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 72/96

Page 73: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 73/96

Page 73

Diagr.: Connection example for the digital in- puts.

External powersupply

S1

0V

12

UMG96SDigital inputs

Digital input 1

13

+ -

230V AC

24V DC

11

Digital input 2S2

5k

5k

Page 74: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 74/96

Page 75: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 75/96

Page 76: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 76/96

Page 76

TablesParameter listIn the parameter list all necessary settings for correct operation of the UMG96S, such as CT dataor device address, are mentioned. The values in the parameter list can be written and read. Dateand time in address 700 are an exception and can be written only. On address 410 of the meas-

ured value list, date and time can be read in seconds since 1.1.1970.Measured value listThe measured value list contains the measured and calculated measured values, condition data ofthe inputs and outputs as well as the protocolled values for reading out.

FormatsCHAR = 1 ByteINT = 2 Byte; (high before low Byte)LONG = 4 Byte; (high before low Byte)STRING1 = 32 Byte; Byte 1 = row 1, Bit1=1.meas. value table, Bit2=2.meas. value table ...

Byte 2 =row 2, Bit1=1. meas. value table, Bit2=2.meas.value table ...STRING2 = 6 Byte; Hour, minute, second, day, month, yearFDATA = 2 Byte; Data set number

4 Byte; Time since 1.1.1970 10 Byte; Data string 1 Byte; Profile number 1 Byte; Error information

Representation of CosPhi within UMG96S

Measured value indication

measured value list and data memory

Analogue outputs and switching out-puts

capacitive inductive1,00

0,00cap 0,00ind

-100

-1

+100

+0-100 +100

0 0

1,00 1,00

Attention!Only the PC software PSWbasic/professional can use the maximum setting range of someparameters. At UMG96S, values can be entered up to 999999.

Page 77: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 77/96

Page 77

Addr. Description Setting range Type Unit Presetting

000 UMG96S Device address 1 .. 255 CHAR - 1001 Baud rate (RS232 and RS485) 0 .. 2 CHAR 1) kbps 0

002 Input/Output 1, Type 0 .. 5 CHAR2)

- 0003 Input/Output 2, Type 0 .. 5 CHAR 2) - 0004 Pulse valence, Digital output 1 0 .. 100000 PULS Wh 1,00 5)

006 Pulse valence, Digital output 2 0 .. 100000 PULS varh 1,00 5)

008 Delete min. and max. values 0 .. 1 CHAR - 0009 Delete energy 0 .. 1 CHAR - 0010 Min. pulse duration, Digital output 1/2 5 .. 99 CHAR 3) ms 5=50ms011 User password 0 .. 999 INT - 000012 LCD contrast 0 .. 7 CHAR - 3013 Comparator 1A, limit -999999999 ..

999999999 LONG 0

015 Comparator 1A, measured value 0 .. 999 INT 6) 000016 Comparator 1A, Min. on time 1 .. 899 INT Sec. 1017 Comparator 1A, Operator 0, 1 CHAR 4) 0018 Comparator 1B, limit -999999999 ..

999999999 LONG020 Comparator 1B, measured value 0 .. 999 INT 6)

021 Comparator 1B, min. on time 1 .. 899 INT Sec. 1022 Comparator 1B, Operator 0, 1 CHAR 4) 0023 Comparator 1C, limit -999999999 ..

999999999 LONG025 Comparator 1C, measured value 0 .. 999 INT 6)

026 Comparator 1C, min. on time 1 .. 899 INT Sec. 1027 Comparator 1C, Operator 0, 1 CHAR 4) 0028 Comparator 2A, limit -999999999 ..

999999999 LONG030 Comparator 2A, measured value 0 .. 999 INT 6)

031 Comparator 2A, min. on time 1 .. 899 INT Sec. 1032 Comparator 2A, Operator 0, 1 CHAR 4) 0033 Comparator 2B, limit -999999999 ..

999999999 LONG035 Comparator 2B, measured value 0 .. 999 INT 6)

036 Comparator 2B, min. on time 1 .. 899 INT Sec. 1037 Comparator 2B, not/inverted 0, 1 CHAR 4) 0038 Comparator 2C, limit -999999999 ..

999999999 LONG

1) 0 = 9,6kBit/s; 1 = 19,2kBit/s; 2 = 38.4kBit/s2) 0 = Pulse output, 1 = Digital output, 2 = Analogue output, 3 = Digital input, 4 = Profibus-Remote output, 5 = HT/NT changeover via digital input.3) Min. pulse duration = setting range * 10 [ms]4) 0 = higher than, 1 = smaller than5) Reading/writing 100=1,006) 0 = Comparator not used, 1 = remote, 200-424 = measured values

Parameter list

Attention!For some parameters, only software PSWbasic/professional can use the full setting range.At UMG96S, only values up to 999999 can be set.

Page 78: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 78/96

Page 79: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 79/96

Page 79

Addr. Description Setting range Type Unit Presettin.

600 Current transformer, primary 3) 1 .. 10000 INT A 5601 Current transformer, secondary 3) 1 .. 5 INT A 5

602 Voltage transformer, primary3)

100 .. 60000 INT V 4001)

603 Voltage transformer, secondary 3) 100 .. 400 INT V 400 1)

604 Indication profile, actual 2) STRING1 - -605 Indication rotation profile, actual 2) STRING1 - -700 Date and time 2) STRING2 - -701 Option clock, yes=1, no= 0 read only CHAR - -702 Ring buffer, Data set number, address read only INT - -703 Option Ringpuffer, ja=1, nein= 0 read only CHAR - -800 Write in EEPROM 0 .. 4 CHAR - 0

Bit 1 = 1, Write calibration data.Bit 2 = 1, Write programming data.

Bit 4 = 1, Write counter.Bit 8 = 1, Write min./max. values.911 Serial number read only LONG - ######913 Software Release read only INT - ###914 Hardware Expansion read only INT - ###

1) In 300V standard version: 400V; In 150V special version: 100V.2) These values can only be read and written with PSWbasic/professional.3) The parameters for current and voltage transformer ratios can be read at UMG96S only.

Parameter list Part 3

Attention!For some parameters, only software PSWbasic/professional can use the full setting range.At UMG96S, only values up to 999999 can be set.

Page 80: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 80/96

Page 80

Addr. Description Type Unit Solution

200 Voltage L1-N INT V 0,1201 Voltage L2-N INT V 0,1

202 Voltage L3-N INT V 0,1203 Voltage L1-L2 INT V 0,1204 Voltage L2-L3 INT V 0,1205 Voltage L3-L1 INT V 0,1206 Current in L1 INT mA 1207 Current in L2 INT mA 1208 Current in L3 INT mA 1209 Real power L1 INT W 0,1210 Real power L2 INT W 0,1211 Real power L3 INT W 0,1212 Reactive power L1 INT W 0,1

213 Reactive power L2 INT W 0,1214 Reactive power L3 INT W 0,1215 Apparent power L1 INT W 0,1216 Apparent power L2 INT W 0,1217 Apparent power L3 INT W 0,1218 CosinusPhi in L1 PHI - 0,01219 CosinusPhi in L2 PHI - 0,01220 CosinusPhi in L3 PHI - 0,01221 1. Harmonic U L1-N INT V 0,1222 3. Harmonic U L1-N INT V 0,1223 5. Harmonic U L1-N INT V 0,1

224 7. Harmonic U L1-N INT V 0,1225 9. Harmonic U L1-N INT V 0,1226 11. Harmonic U L1-N INT V 0,1227 13. Harmonic U L1-N INT V 0,1228 15. Harmonic U L1-N INT V 0,1229 1. Harmonic U L2-N INT V 0,1230 3. Harmonic U L2-N INT V 0,1231 5. Harmonic U L2-N INT V 0,1232 7. Harmonic U L2-N INT V 0,1233 9. Harmonic U L2-N INT V 0,1234 11. Harmonic U L2-N INT V 0,1

235 13. Harmonic U L2-N INT V 0,1236 15. Harmonic U L2-N INT V 0,1237 1. Harmonic U L3-N INT V 0,1238 3. HarmonicU L3-N INT V 0,1239 5. Harmonic U L3-N INT V 0,1240 7. HarmonicU L3-N INT V 0,1241 9. Harmonic U L3-N INT V 0,1242 11. Harmonic U L3-N INT V 0,1243 13. Harmonic U L3-N INT V 0,1244 15. Harmonic U L3-N INT V 0,1245 1. Harmonic I L1 INT mA 1

246 3. Harmonic I L1 INT mA 1247 5. Harmonic I L1 INT mA 1248 7. Harmonic I L1 INT mA 1

Measured value list

Page 81: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 81/96

Page 81

Addr. Description Type Unit Solution

249 9. Harmonic I L1 INT mA 1250 11. Harmonic I L1 INT mA 1

251 13. Harmonic I L1 INT mA 1252 15. Harmonic I L1 INT mA 1253 1. Harmonic I L2 INT mA 1254 3. Harmonic I L2 INT mA 1255 5. Harmonic I L2 INT mA 1256 7. Harmonic I L2 INT mA 1257 9. Harmonic I L2 INT mA 1258 11. Harmonic I L2 INT mA 1259 13. Harmonic I L2 INT mA 1260 15. Harmonic I L2 INT mA 1261 1. Harmonic I L3 INT mA 1

262 3. Harmonic I L3 INT mA 1263 5. Harmonic I L3 INT mA 1264 7. Harmonic I L3 INT mA 1265 9. Harmonic I L3 INT mA 1266 11. Harmonic I L3 INT mA 1267 13. Harmonic I L3 INT mA 1268 15. Harmonic I L3 INT mA 1269 THD U L1 INT % 0,1270 THD U L2 INT % 0,1271 THD U L3 INT % 0,1272 THD I L1 INT % 0,1

273 THD I L2 INT % 0,1274 THD I L3 INT % 0,1275 Frequency L1 INT Hz 0,01276 CosinusPhi, Sum INT 0,01 -277 Field rotation INT 1) - -278 Current in N INT mA 1279 Real power, Sum INT W 1280 Reactive power, Sum INT var 1281 Apparent power, Sum INT VA 1282 Mean value I in L1 INT mA 1283 Mean value I in L2 INT mA 1

284 Mean value I in L3 INT mA 1285 Mean value P in L1 INT W 0,1286 Mean value P in L2 INT W 0,1287 Mean value P in L3 INT W 0,1288 Mean value Q in L1 INT var 0,1289 Mean value Q in L2 INT var 0,1290 Mean value Q in L3 INT var 0,1291 Mean value S in L1 INT VA 0,1292 Mean value S in L2 INT VA 0,1293 Mean value S in L3 INT VA 0,1294 Mean value I in N INT mA 1

295 Mean value P, Sum INT W 1296 Mean value Q, Sum INT var 1

1) 0 = no field rotation recognized, 1 = clockwise field, -1 = anticlockwise field

Measured value list, part2

Page 82: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 82/96

Page 82

Addr. Description Type Unit Solution

297 Mean value S, Sum INT VA 1298 Max. value I, Sum INT mA 1

299 Max. value, P mean value, Sum INT W 1300 Max. value I mean value, Sum INT mA 1301 Max. value, P Sum INT W 1302 Max. value, Q Sum INT var 1303 Max. value, S Sum INT VA 1304 Max. value, CosPhi Sum INT - 0,01305 Min. value, U L1-N INT V 0,1306 Min. value, U L2-N INT V 0,1307 Min. value, U L3-N INT V 0,1308 Max. value, U L1-N INT V 0,1309 Max. value, U L2-N INT V 0,1

310 Max. value, U L3-N INT - 0,1311 Min. value, U L1-L2 INT V 0,1312 Min. value, U L2-L3 INT V 0,1313 Min. value, U L3-L1 INT V 0,1314 Max. value, U L1-L2 INT V 0,1315 Max. value, U L2-L3 INT V 0,1316 Max. value, U L3-L1 INT V 0,1317 Max. value, I L1 INT mA 1318 Max. value, I L2 INT mA 1319 Max. value, I L3 INT mA 1320 Max. value, I L1 Mean value INT mA 1

321 Max. value, I L2 Mean value INT mA 1322 Max. value, I L3 Mean value INT mA 1323 Max. value, P L1 INT W 0,1324 Max. value, P L2 INT W 0,1325 Max. value, P L3 INT W 0,1326 Max. value, Q L1 INT var 0,1327 Max. value, Q L2 INT var 0,1328 Max. value, Q L3 INT var 0,1329 Max. value, S L1 INT VA 0,1330 Max. value, S L2 INT VA 0,1331 Max. value, S L3 INT VA 0,1

332 Max. value, 1. Harmonic U L1-N INT V 0,1333 Max. value, 3. Harmonic U L1-N INT V 0,1334 Max. value, 5. Harmonic U L1-N INT V 0,1335 Max. value, 7. Harmonic U L1-N INT V 0,1336 Max. value, 9. Harmonic U L1-N INT V 0,1337 Max. value, 11. Harmonic U L1-N INT V 0,1338 Max. value, 13. Harmonic U L1-N INT V 0,1339 Max. value, 15. Harmonic U L1-N INT V 0,1340 Max. value, 1. Harmonic U L2-N INT V 0,1341 Max. value, 3. Harmonic U L2-N INT V 0,1342 Max. value, 5. Harmonic U L2-N INT V 0,1

343 Max. value, 7. Harmonic U L2-N INT - 0,1344 Max. value, 9. Harmonic U L2-N INT V 0,1

Measured value list part 3

Page 83: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 83/96

Page 83

The minimum and maximum values are stored without date and time.

Addr. Description Type Unit Solution

345 Max. value, 11. Harmonic U L2-N INT V 0,1346 Max. value, 13. Harmonic U L2-N INT V 0,1347 Max. value, 15. Harmonic U L2-N INT V 0,1348 Max. value, 1. Harmonic U L3-N INT V 0,1349 Max. value, 3. Harmonic U L3-N INT V 0,1350 Max. value, 5. Harmonic U L3-N INT V 0,1351 Max. value, 7. Harmonic U L3-N INT V 0,1352 Max. value, 9. Harmonic U L3-N INT V 0,1353 Max. value, 11. Harmonic U L3-N INT V 0,1354 Max. value, 13. Harmonic U L3-N INT V 0,1355 Max. value, 15. Harmonic U L3-N INT V 0,1356 Max. value, 1.Harmonic I L1 INT mA 1357 Max. value, 3.Harmonic I L1 INT mA 1

358 Max. value, 5.Harmonic I L1 INT mA 1359 Max. value, 7.Harmonic I L1 INT mA 1360 Max. value, 9.Harmonic I L1 INT mA 1361 Max. value, 11.Harmonic I L1 INT mA 1362 Max. value, 13.Harmonic I L1 INT mA 1363 Max. value, 15.Harmonic I L1 INT mA 1364 Max. value, 1.Harmonic I L2 INT mA 1365 Max. value, 3.Harmonic I L2 INT mA 1366 Max. value, 5.Harmonic I L2 INT mA 1367 Max. value, 7.Harmonic I L2 INT mA 1368 Max. value, 9.Harmonic I L2 INT mA 1

369 Max. value, 11.Harmonic I L2 INT mA 1370 Max. value, 13.Harmonic I L2 INT mA 1371 Max. value, 15.Harmonic I L2 INT mA 1372 Max. value, 1.Harmonic I L3 INT mA 1373 Max. value, 3.Harmonic I L3 INT mA 1374 Max. value, 5.Harmonic I L3 INT mA 1375 Max. value, 7.Harmonic I L3 INT mA 1376 Max. value, 9.Harmonic I L3 INT mA 1377 Max. value, 11.Harmonic I L3 INT mA 1378 Max. value, 13.Harmonic I L3 INT mA 1379 Max. value, 15.Harmonic I L3 INT mA 1

380 Max. value, THD U L1 INT % 0,1381 Max. value, THD U L2 INT % 0,1382 Max. value, THD U L3 INT % 0,1383 Max. value, THD I L1 INT % 0,1384 Max. value, THD I L2 INT % 0,1385 Max. value, THD I L3 INT % 0,1

Measured value list part 4

Page 84: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 84/96

Page 84

Addr. Description Type Unit Solution

386 Comparator result 1A CHAR - 0/1387 Comparator result 1B CHAR - 0/1

388 Comparator result 1C CHAR - 0/1389 Total result, comparator group 1 CHAR - 0/1390 Comparator result 2A CHAR - 0/1391 Comparator result 2B CHAR - 0/1392 Comparator result 2C CHAR - 0/1393 Total result, comparator group 2 CHAR - 0/1394 Operation hours meter LONG Sec. 0,1h396 Total running time, comparator 1A LONG Sec. 1398 Total running time, comparator 1B LONG Sec. 1400 Total running time, comparator 1C LONG Sec. 1402 Total running time, comparator 2A LONG Sec. 1

404 Total running time, comparator 2B LONG Sec. 1406 Total running time, comparator 2C LONG Sec. 1408 Temperature within device INT [°C] 1409 Internal operation voltage INT V 10mV410 Time since 1.1.1970 LONG Sec. 1412 Mean value, CosPhi, Sum PHI 1) - 0.01413 Exceeding of measuring range CHAR -

Bit 1: Exceeding of 6,5Aeff in phase L1Bit 2: Exceeding of 6,5Aeff in phase L2Bit 3: Exceeding of 6,5Aeff in phase L3Bit 4: Free

Bit 5: Exceeding of 300Veff in phase L1Bit 6: Exceeding of 300Veff in phase L2Bit 7: Exceeding of 300Veff in phase L3Bit 8: Free

414 Analogue output 0 (4-20mA) INT A 10uA415 Analogue output 1 (4-20mA) INT A 10uA416 Sum real energy Wp, without reverse running stop LONG Wh -418 Sum reactive energy Wq, inductive LONG varh -420 Condition, Digital input 1 CHAR - 0/1421 Condition, Digital input 2 CHAR - 0/1422 Sum real energy Wp, Consumption or HT LONG Wh -

424 Sum real energy Wp, supply or NT LONG Wh -

Measured value list part 5

1) PHI = 2 Byte: -100(cap) .. +100(ind); High before Low Byte.

Page 85: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 85/96

Page 85

Addr. Description Type Unit Solution

500 Data memory - data set FDATA - -501 Data memory - data set FDATA - -

502 Data memory - data set FDATA - -503 Data memory - data set FDATA - -504 Data memory - data set FDATA - -505 Data memory - data set FDATA - -

500-505 decr. data memory pointer 702 while reading506 Data memory - data set FDATA - -510 Function INT

0000h = write act. data memory address into addr. 702A55Ah = Delete data memory5AA5h = Set device with presettings.

520 Measured value indications STRING521 measured value indication, indication rotation STRING

Measured value list part 6

Page 86: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 86/96

Page 87: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 87/96

Page 87

Measured valueSum Reactive

power

Mean valueSum Reactive

power

Max. value (ind.)Sum Reactive

power

Measured valueTHDU L1

Measured valueTHDU L2

Measured valueTHDU L3

Measured valueTHD

I L1

Measured valueTHD

I L2

Measured valueTHD

I L3

Measured value L1 cos(phi) L2 cos(phi) L3 cos(phi)

Measured value Sum cos(phi)

Measured valueFrequency L1Field rotation

Measured value Sum Real energy(without reverse running

stop)

Mean value Sum cos(phi)

Max. value THDU L1

Max. value THDU L2

Max. value THDU L3

Max. value THDI L1

Max. value THDI L2

Max. value THDI L3

A10 C10B10

A11 B11 C11

A12 B12 C12

A13 B13 C13

A14 B14 C14

A15

A16 B16

A17

A18

Measured value Sum Real energy

(Consumption or HT)

B18

Measured value Sum Real energy

(Supply or NT)

C18

Page 88: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 88/96

Page 88

Those menues are not displayed with the producer`s presettings.

Operating hourscounter 1

Comparator 1Total running time

Measured value1. Harmonic

U L1

Measured value3. Harmonic

U L1

Measured value15. Harmonic

U L1

Measured value1. Harmonic

U L2

Measured value3. Harmonic

U L2

Measured value15. Harmonic

U L2

Measured value1. Harmonic

U L3

Measured value3. Harmonic

U L3

Measured value15. Harmonic

U L3

Measured value1. Harmonic

I L1

Measured value3. Harmonic

I L1

Measured value15. Harmonic

I L1

Measured value

1. HarmonicI L2

Measured value

3. HarmonicI L2

Measured value

15. HarmonicI L2

Measured Value1. Harmonic

I L3

Measured value3. Harmonic

I L3

Measured value15. Harmonic

I L3

Comparator 6Total running time

Measured value(ind) Sum

Reactive energy

A19

A20 B20 G20

A21 B21 H21

A22 B22 H22

A23 B23 H23

A24 B24 H24

A25 B25 H25

A26 B26 H26

Page 89: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 89/96

Page 89

Max. value1. Harmonic

U L1

Max. value3. Harmonic

U L1

Max. value15. Harmonic

U L1

Max. value1. Harmonic

U L2

Max. value3. Harmonic

U L2

Max. value15. Harmonic

U L2

Max. value1. Harmonic

U L3

Max. value3. Harmonic

U L3

Max. value15. Harmonic

U L3

Max. value1. Harmonic

I L1

Max. value3. Harmonic

I L1

Max. value15. Harmonic

I L1

Max. value1. Harmonic

I L2

Max. value3. Harmonic

I L2

Max. value15. Harmonic

I L2

Max. value1. Harmonic

I L3

Max. value3. Harmonic

I L3

Max. value15. Harmonic

I L3

A27 H27B27

A28 B28 H28

A29 B29 H29

A30 B30 H30

A31 B31 H31

A32 B32 H32

Those menues are not displayed with the producer`s presettings.

Page 90: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 90/96

Page 90

These specifications presuppose a yearly calibration and a warm up time of 10 minutes.Used abbreviations:

rng = of measuring rangerdg = of measured value

Indication range and accuracy

Quantity Indication range Measuring range 1) Accuracy 3)

Voltage L-N 0 .. 34kV 10 .. 300V +-0,5% rng Voltage L-L 0 .. 60kV 10 .. 520V +-1,0% rng Current 0,01 .. 60,0kA 0,01 .. 6A +-0,5% rng Current in N 0,01 .. 180,0kA 0,01 .. 18A +-1,5% rng Real power, per phase 0,1W .. 99,9MW 0,1W .. 1,8kW +-1,0% rng Apparent power, per phase 0,1VA .. 99,9MVA 0,1VA .. 1,8kVA +-1,0% rng Reactive power, (Q0) per phase 0,1var .. 99,9Mvar 0,1var .. 1,8kvar +-1,0% rng Real power, Sum 1W .. 99,9MW 1W .. 5,4kW +-1,0% rng Apparent power, Sum 1VA .. 99,9MVA 1VA .. 5,4kVA+-1,0% rng Reactive power (Q0), Sum 1var .. 99,9Mvar 1var .. 5,4kvar +-1,0% rng Harmonics U, 1-15 0 .. 34kV 0,1V .. 300,0V +-2,0% rng Harmonics I, 1-15 0,01 .. 60,0kA 1mA .. 6000mA +-2,0% rng THD U , I 0,1% .. 100,0% +-2,0% rng cos(phi) 0,00i .. 1.00 .. 0,00c 0,00i ..1.00.. 0,00c +- 1 degree Frequency (of voltage) 45,0 .. 65,0Hz 45,0 .. 65,0Hz +-0,1% rdg Reactive energy Wq, inductive 0 .. 999.999.999kvarh 4) Class 1 2) (../5A)

Class 2 2) (../1A) Real energy Wp, supply 0 .. 999.999.999kWh 4) Class 1 2) (../5A)

Class 2 2) (../1A) Operating hours counter 0 .. 999 999 999h +-2Minutes/day

1) Measuring range with scale factor = 1, (Current transformer = 5/5A, 1/1A)

2) , Accuracy class according to DIN EN61036:2001-01, VDE0418 partl 7, IEC61036:1996 + A1:20003) In the range of -10..18°C and 28..55°C an additional error of +-0,5‰ rng per K must be re-spected.

4) The maximum indication range of real andreactive energy depends on the transformerratio v = vi * vu.vi = Currrent transformer ratio.vu = Voltage transformer ratio.Example: 200/5A -> vi = 40

1000/100V -> vu = 10v = vi * vuv = 40 *10v = 400

1 10 100 400 v

999.999.999

210.000.000

21.000.000,0

2.100.000,00

/kvarh /kWh

Transformer ratio

Indication range

Page 91: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 91/96

Page 91

Weight : 250gCalorific value : 2,2MJ (610Wh)

Ambient conditionsOver voltage class : CATIIIPollution degree : 2Protection class : II = without protective wireAmbient temperature : -10°C .. +55°CStorage temperature : -20°C .. +70°CRelative humidity : 15% to 95% without dewProtection

Front : IP50 according to IEC60529Front with seal (Option) : IP65 according to IEC60529Back side : IP20 according to IEC60529

Mounting position : optionalMounting height : 0 .. 2000m over NN

Declaration of conformityUMG96S fulfills the protection requirements of standard 89/336/EWG in connection to DIN EN61326 (2002-03) as well as of standard 73/23EWG and 93/68/EWG in connection to EN 61010-1(202-08).

Safety regulations: EN61010-1 03.1994 + A2 05.1996

Requirements of electromagnetical compatibility: DIN EN61326:2002-03

Noise emission Basic unit : DIN EN61326:2002-03, table 4 class B, (residential areas) Basic unit with option 1 : DIN EN61326:2002-03, table 4 class B, (residential areas) Basic unit with option 2 : DIN EN61326:2002-03, table 4 class A, (industrial areas)

Noise immunity (industrial areas) Casing : Electrostatic discharge immunity test, IEC61000-4-2 (4kV/8kV)

: Electromagnetically fields, IEC61000-4-3 (10V/m) Voltage and supply : Voltage dips, IEC61000-4-11 (0,5Periode)

: Electrical fast transient/burst, IEC61000-4-4 (2kV): Surge immunity test, IEC61000-4-5 (1kV): Immunity to conducted disturbances, IEC61000-4-6 (3V)

Input/output, serial interfaces: Electrical fast transient/burst, IEC61000-4-4 (1kV): Surge immunity test, IEC61000-4-5 (1kV)

Technical data

Page 92: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 92/96

Page 93: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 93/96

Page 93

MeasurementMeasuring inputs

Measuring rate : 1 measurement/sec.Rated pulse voltage : 4kVSignal frequency : 45Hz .. 1000Hz

Measuring and operating voltage : see type plateFuse : 2A .. 10A (medium type)Frequency of fundamental : 45Hz .. 65Hzpower consumption (basic instrument)

Connecting one phase (L-N) : max. 1,5VA (1,5W)Connecting all 3 phases (L1/L2/L3-N) : max. 0,5VA (0,5W) / Phase

Power consumption (basic device with add. PCB 2)Connecting one phase (L-N) : max. 3VA (3W)Connecting all three phases (L1/L2/L3-N) : max. 1VA (1W) / Phase

300V Standard version : max. 300V AC against groundMeasuring range L-N : 50 .. 300V ACMeasuring range L-L : 87 .. 520V ACOperation voltage L-N : 85 (140)* .. 300V AC

150V Special version : max. 150V AC against groundMeasuring range L-N : 25 .. 150V ACMeasuring range L-L : 40 .. 260V ACOperation voltage L-L : 85 .. 260V AC

Current measurement : max. 150VAC against groundPower consumption : ca. 0,2 VARated current at ../5A (../1A) : 5A (1A)

Minimum working current : 5mALimit at ../1A : 1,2A (sinus shape)Limit at ../5A : 6A (sinus shape)

Overload : 150A for 2 Sec.

Serial interfacesRS232, RJ11-sleeve (Option)

Protocol : MODBUS RTUTransmission rates : 9.6, 19.2, 38.4kBit/s

RS485, Spring terminals (Option)Protocol : MODBUS RTUTransmission rates : 9.6, 19.2, 38.4kBit/s

RS485, DSUB-9 (Option)Protocol : Profibus DP (V0)Transmission rates : 9.6, 19.2, 45.45, 93.75, 187.5, 500,

1500kBit/s

Connectable wiresone wire, more wires,fine wires : 0,08 - 2,5mm 2

Pin cable socket, conductor sleeves : 1,5mm 2

For each terminal, only one wire may be

connected!

Technical data, part 3

* The smallest operation voltage for devices with option Profibus is 140V AC.

Page 94: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 94/96

Page 94

Side view

All dimensions in mm

Dimension sketchCut out: 92 +0,8 x 92 +0,8 mm

Back side

Panelmax. 6

9 0

9 6

49

D S U B - 9

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

42 6

2,5

R J 1 1

Fixing angles

Option

Option

Page 95: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 95/96

Page 95

Connection diagrams

UMG96SMeasurement andoperation voltage

see type plate

Currentmeasurement

0,005 .. 5A

L1 L2 L3 N

V e r b r a u c

h e r

C o n s u m e r

2 .. 10A

k lk l

k l../5(1)A

../5(1)A../5(1)A

L1L2L3PEN

1k 1l 2k 2l 3k 3l

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 RJ11

R S

2 3 2

DC+ -

R

S 4 8 5

M o d

b u s

R T U

Diagr. UMG96S with RS232 and digital outputs.

D i g i t a l o u

t p u t s

RS485 Bus cable

B A(Option)

S1

S2

UMG96SMeasurement andoperation voltage

see type plate

Currentmeasurement

0,01 .. 5A

L1 L2 L3 N

V e r b

r a u c

h e r

C o n s u m e r

2 .. 10A

k lk l

k l../5(1)A

../5(1)A

../5(1)A

L1L2L3PEN

1k 1l 2k 2l 3k 3l

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 RJ11 DSUB-9

Additional PCB 2 (Option)

R S 2 3 2

DC +-SPS

Diagr. UMG96S with digital inputs, RS232 and Profibus.

P r o

f i b u s

Profibus DP

Profibus

D i g i t a l i n p u

t s

RS485 Bus cable

B A (Option)

Page 96: Electrical Power Meter UMG96S OM

8/20/2019 Electrical Power Meter UMG96S OM

http://slidepdf.com/reader/full/electrical-power-meter-umg96s-om 96/96

Brief instructions

Change current transformerChange into programming modeIf you are in indication mode and press key 1 and 2 simulta-neously for about one second, you reach programming mode.The symbol for programming mode PRG and current trans-former CT appears.Confirm selection with key 1.The first number of the primary flashes.

PRG

k AL1

L2

L3 CT

Primary current

Secondary current 1 2

Call up measured valuesChange into indication mode

Change primary currentChange the flashing number with key 2.Select next number using key 1.The selected number flashes.If the complete number is flashing, the decimal point can bemoved.Change secondary currentAs secondary current, only 1A or 5A can be set.Select secondary with key 1.Change flashing number with key 2.

Leave programming modePress both keys for about 1 second.The CT ratio is stored and you return to indication mode.

SCT symbol

Programming mode

PRG

k AL1

L2

L3 CT

1 2