    ELECTRICAL SAFETY

    DESIGN

    General Requirements

    Wiring Design and Protection

    Wiring Methods and Components

    Equipment for General Use.

  • 7/31/2019 Electrical Safety Design

    2/110

    Introduction

    This module deals with

    Occupational Safety andHealth Administration (OSHA)standards for electrical safetydesign.

    These standards cover only

    electrical system parts that anemployee would use or withwhich she/he could makecontact.

    The modules purpose is tominimize potential workplacehazards by specifyingelectrical equipment andsystems designcharacteristics.

  • 7/31/2019 Electrical Safety Design

    3/110

    Development of The Code

    The OSHA electrical standards were based on the National

    Fire Protection Association's standard NFPA 70E, "ElectricalSafety Requirements for Employee Workplaces." The NFPA70 Committee derived Part I of their document from the 1978edition of the National Electrical Code (NEC).

    The standards extracted from the NEC were those consideredthe most applicable to employee safety and least likely tochange with each new edition of the NEC.

    OSHA's electrical standards are performance oriented;therefore they contain few direct references to the NEC.However, the NEC contains specific information as to how therequired performance can be obtained.

  • 7/31/2019 Electrical Safety Design

    4/110

    Introduction - Objectives

    At the end of this module, you should beable to:

    Identify the general requirements for electricalsafety design

    Define proper wiring design and methods

    Define proper installation and protection of

    electrical equipment and components Identify unsafe wiring design, methods,

    equipment, protection, and components.

  • 7/31/2019 Electrical Safety Design

    5/110

    General Requirements -

    Introduction

    The General Requirements

    section, based on standard1910.303, describes the generalrequirements for electrical safetydesign.

    The topics for this section arelisted on the left.

    The conductors and equipmentrequired or permitted by 1910.303shall be acceptable only ifapproved.

    Electrical equipment shall be safefrom recognized hazards that are

    likely to cause death or seriousphysical harm to employees.

    Examination and properinstallation are important methodsfor ensuring safety from hazards.

  • 7/31/2019 Electrical Safety Design

    6/110

    Equipment Examination,

    Installation, and Use The following considerations are

    examined to determine ifequipment is safe:

    Suitability for installation and use,in conformity with electricalstandard provisions. Suitability ofequipment for an identified

    purpose may be evidenced bylisting or labeling for that identifiedpurpose

    Mechanical strength anddurability, including the adequacy

    of the protection by partsdesigned to enclose and protectother equipment

    Electrical insulation

  • 7/31/2019 Electrical Safety Design

    7/110

    Equipment Examination,

    Installation, and Use Heating effects under conditions

    of use

    Arcing effects Classification by type, size,

    voltage, current capacity, andspecific use

    Other factors which contribute tothe practical safeguarding of

    employees using or likely to comein contact with the equipment.

    Listed or labeled equipment shallbe used or installed in accordancewith any instructions included in

    the listing or labeling and with therequirements on the followingpages.

  • 7/31/2019 Electrical Safety Design

    8/110

    Splices and Arcing Parts Conductors shall be spliced or joined

    with suitable splicing devices.

    Another option is for conductors to bespliced by brazing, welding, orsoldering with a fusible metal or alloy.

    Soldered splices should bemechanically and electrically securebefore soldering.

    All splices, joints, and the free ends ofconductors shall be covered with aninsulation equivalent to that of theconductors, or covered with aninsulating device suitable for thepurpose.

    Parts of electric equipment which in

    ordinary operation produce arcs,sparks, flames, or molten metal shall beenclosed or separated and isolatedfrom all combustible material.

  • 7/31/2019 Electrical Safety Design

    9/110

    Marking Electrical equipment may not be used

    unless the manufacturer's name,

    trademark, or other descriptive markingby which the organization responsiblefor the product may be identified isplaced on the equipment.

    Other markings indicating voltage,current, wattage, or other ratings shallbe provided as necessary.

    Marking is almost always provided onthe name-plate of reputablemanufacturers equipment.

    The markings shall be of sufficientdurability to withstand the operatingenvironment.

    Violations usually occur when thenameplate is covered, removed, orobliterated by painting or other abuse.

    One example of abuse is shown to theleft. Importance of Marking

  • 7/31/2019 Electrical Safety Design

    10/110

    Importance of Marking Marking is very important.

    If a piece of equipment is connected to a voltage higher than its rating, a violent failurecould occur.

    If it is connected to a voltage below its rating, it may attempt to perform its intendedfunction and overheat badly, leading to failure.

    If AC equipment is energized with the wrong frequency, or with direct current, it willprobably fail violently. These occurrences can cause fires and burns to employees.

    If equipment is connected to a circuit not adequate for the load, conductors may overheat

    and deteriorate. Over current protective devices should prevent serious damage in such a case. However,

    these devices may have been tampered with, reducing protection capability.

    If the manufacturer's name is not marked on the nameplate, there will be difficulty intracing the reasons for faulty performance and in preventing future failures.

    Sometimes it is necessary to know the identity of the manufacturer in order to determine

    if equipment is approved for a particular purpose. The manufacturer's name may also be necessary so that the user can obtain information

    or replacement parts.

  • 7/31/2019 Electrical Safety Design

    11/110

    Disconnecting Means and

    Circuit Identification Identification (as used in OSHA standards) means equipment is

    labeled to indicate its purpose. Required disconnecting means for motors and appliances shall give

    legible indication of its purpose.

    If the purpose of the circuit is obvious, no identification of thedisconnect is required.

    A disconnecting means is a switch used to disconnect the circuitconductors from the electric current source.

    Disconnect switches protect workers and equipment by enabling acircuit to be opened to stop the flow of electricity.

    Each service, feeder, and branch circuit shall have its purpose legibly

    identified (unless clearly evident) at its disconnecting means or overcurrent device.

    Identification should be located at the circuit origination point. Identification Example

  • 7/31/2019 Electrical Safety Design

    12/110

    Identification Example On a panel that controls several

    motors or on a motor controlcenter, each disconnect must beclearly marked to indicate themotor to which each circuit isconnected.

    In this figure, the Number 2 circuitbreaker in the panel box suppliescurrent only to disconnect Number2, which in turn controls thecurrent to motor Number 2.

    This current to motor Number 2can be shut off by the Number 2circuit breaker or the Number 2disconnect.

  • 7/31/2019 Electrical Safety Design

    13/110

    600 Volts, Nominal or Less 1910.303 also addresses the safety of

    persons qualified to work on the

    equipment, but who do not removeguards and enclosures in order to workon live parts.

    Table S-1 of 1910.303(g)(1)(i) lists theminimum dimensions for working spacein the direction of access to live partsoperating at 600 volts or less and likelyto require examination, adjustment,servicing, or maintenance whileenergized except where required orpermitted in Subpart S.

    In addition, work space may not be lessthan 30 inches wide in front of theelectrical equipment measured fromexposed live parts, or from theenclosure front or opening if the liveparts are enclosed.

  • 7/31/2019 Electrical Safety Design

    14/110

    600 Volts, Nominal or Less Concrete, brick, or tile walls are

    considered to be grounded.

    Working space is not required in backof assemblies such as dead-frontswitchboards or motor control centerswhere there are no renewable oradjustable parts such as fuses orswitches on the back and where allconnections are accessible fromlocations other than the back.

    Working space shall not be used forstorage.

    In addition the working space access,illumination, and headroom shall beadequately maintained.

  • 7/31/2019 Electrical Safety Design

    15/110

    600 Volts, Nominal or Less Except as required or permitted elsewhere in this standard, live parts of

    electric equipment operating at 50 volts or more shall be guarded againstaccidental contact by approved cabinets, enclosures, or by:

    Location in a room, vault, or similar enclosure only accessible to qualified persons

    Suitable permanent, substantial partitions or screens so arranged that only qualifiedpersons will have access to the space within reach of the live parts and that anyopenings shall be so sized and located to prevent accidental contact with the live

    parts or to bring conducting objects into contact with them Location on a suitable balcony, gallery, orplatform

    Elevation of 8 feet or more above the floor or other working surface.

    In locations where electric equipment would be exposed to physical damage,

    enclosures or guards shall be so arranged and of such strength as to preventsuch damage.

    The purpose of guarding equipment is to protect any person, not just qualifiedelectricians, against accidental electrical equipment contact.

    http://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppt
  • 7/31/2019 Electrical Safety Design

    16/110

    Over 600 Volts, Nominal Electrical equipment operating

    above 600 volts, nominalcreates extremely dangerousworking environments.Therefore, it is important toheed the followingrequirements.

    The entrances to all buildings,rooms, or enclosurescontaining exposed live partsor exposed conductors

    operating at over 600 volts,nominal shall be under theobservation of a qualifiedperson or locked at all times.

  • 7/31/2019 Electrical Safety Design

    17/110

    Over 600 Volts, Nominal Electrical installations in the

    following areas where accessis controlled by lock and keyor other approved means areconsidered sufficient toprevent unqualified access:

    Area surrounded by a wall,screen, or fence 8 feet orhigher unless other featuresprovide a degree of isolationequivalent to an 8 foot fence

    Vault Room

    Closet

  • 7/31/2019 Electrical Safety Design

    18/110

    Over 600 Volts, Nominal Electrical installations operating

    over 600 volts, nominal havingexposed live parts shall beaccessible to qualified personsonly.

    Sufficient space shall be provided

    and maintained about electricequipment to permit ready andsafe operation and maintenanceof such equipment.

    Where energized parts are

    exposed, the minimum clear workspace may not be less than 6 feet6 inches high (measured verticallyfrom the floor orplatform), or lessthan 3 feet wide (measuredparallel to the equipment).

    http://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppt
  • 7/31/2019 Electrical Safety Design

    19/110

    Over 600 Volts, Nominal The minimum depth of clear

    working space in front of electricequipment is given in Table S-2 of1910.303(h)(3)(i).

    Unguarded live parts aboveworking spaces shall be

    maintained at elevations not lessthan specified in Table S-3 of1910.303(h)(3)(iii).

  • 7/31/2019 Electrical Safety Design

    20/110

    Over 600 Volts, Nominal At least one entrance not less than 24 inches wide and 6 feet 6 inches high

    shall be provided to give access to the working space about electricequipment.

    On switchboard and control panels exceeding 48 inches in width, there shallbe one entrance at each end of such board where practicable. Where bareenergized parts at any voltage or insulated energized parts above 600 voltsare located adjacent to such entrance, they shall be suitably guarded.

    Adequate illumination shall be provided for all working spaces about electricequipment operating over 600 volts, nominal.

    The lighting outlets shall be arranged so persons changing lamps or makingrepairs on the lighting system will not be endangered by live parts or otherequipment.

    The points of control shall be so located that persons are not likely to come in

    contact with any live part or moving part of the equipment while turning on thelights.

    Permanent ladders or stairways shall be provided to give safe access to theworking space around electric equipment installed on platforms, balconies,mezzanine floors, or in attic or roof spaces.

  • 7/31/2019 Electrical Safety Design

    21/110

    Quiz Question:

    One of the primary purposes ofsoldering is to mechanically and

    electrically secure two conductors.

    True

    False

  • 7/31/2019 Electrical Safety Design

    22/110

    Quiz Question:

    Identification of "disconnecting means" is

    used to:

    Mark the power rating of the device

    Mark the purpose of the device Mark the manufacturer of the device

    Mark the current and voltage rating of a device

  • 7/31/2019 Electrical Safety Design

    23/110

    Quiz Question:

    A wall, screen, or fence less than 8 feet in

    height is not considered sufficient to prevent

    access to electrical equipment operating at

    over 600 volts, nominal.

    True

    False

    Wi i D i d

  • 7/31/2019 Electrical Safety Design

    24/110

    Wiring Design and

    Protection Circuits connected

    improperly can poseserious shock or burnhazards.

    The Wiring Design andProtection section, based

    on standard 1910.304,describes the requirementsfor proper wiring designand protection for workerand equipment safety.

    The topics covered in thissection are listed on theleft.

    G d d d G di

  • 7/31/2019 Electrical Safety Design

    25/110

    Grounded and Grounding

    Conductors Grounded/grounding

    conductors of an electricalcircuit must be marked orcolor coded in a way thatallows employees to identifyand distinguish them fromeach other and from the other

    conductors in the circuit. This section describes

    identification procedures fortwo such conductors.

    Circuit Grounded Conductors Equipment Grounding

    Conductors

    G d d d G di

    http://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppt
  • 7/31/2019 Electrical Safety Design

    26/110

    Grounded and Grounding

    Conductors Color coding is one means by

    which conductors areidentified from other circuitconductors.

    Acceptable color codingincludes the method requiredby the National ElectricalCode, Section 210-5.

    Color Coding Example

  • 7/31/2019 Electrical Safety Design

    27/110

    Color Coding Example The graphic illustrates color

    coding on a distribution panelboard.

    The National Electric Code,Section 210-5 states:

    "The circuit groundedconductor of a branch circuitshall be identified by acontinuous white or naturalgray color. The equipmentgrounding conductor of abranch circuit shall be

    identified by a continuousgreen color or a continuousgreen color with one or moreyellow stripes unless it isbare."

  • 7/31/2019 Electrical Safety Design

    28/110

    Color Coding Example Bare copper or aluminum wire

    is permitted for use as agrounding conductor.

    Distinct identification isimportant to maintain correctpolarity between theungrounded (hot) and

    grounded (neutral) conductorwhen plugs, receptacles, andconnectors are used in anelectrical branch circuit.

  • 7/31/2019 Electrical Safety Design

    29/110

    Wiring Design and Protection -

    Grounded and Grounding Conductors

    The correct polarity between the ungrounded(hot) and grounded (neutral) conductors whenusing plugs, receptacles, and connectors isimportant because incorrect polarity cancreate dangerous situations. There are twobasic guidelines:

    No grounded conductor may be attached toany terminal or lead which would reversedesignated polarity

    A grounding terminal or grounding-type device

    on a receptacle, cord connector, orattachment plug may not be used forpurposes other than grounding.

    Many pieces of equipment will operateproperly even though the supply wires are notconnected in the order designated by designor the manufacturer. Improper connection ismost prevalent on the smaller branch circuit

    typically associated with standard 120 voltreceptacle outlets, lighting fixtures, and cord-and plug-connected equipment.

  • 7/31/2019 Electrical Safety Design

    30/110

    Wiring Design and Protection -

    Grounded and Grounding Conductors

    In a common 120-volt outletwith a portable hand toolattached, the black conductorsupplies power to the motor.

    The grey (or white) conductoris used as a circuit groundedconductor for the motor.

    This ground is needed totrigger the circuit breaker, thusstopping the motor if a faultoccurs.

    The green wire is used as the

    equipment groundingconductor to protectemployees handling metalenclosures that may beenergized by an internal fault.

  • 7/31/2019 Electrical Safety Design

    31/110

    Wiring Design and Protection -

    Grounded and Grounding Conductors

    The graphic at the leftillustrates the propergrounding for a hand tool.

    An incorrectly connectedcircuit can cause dangeroussituations.

    You can inspect threeexamples and their outcomesby clicking on the examplesbelow. Reversed Polarity with Circuit

    Ground

    Reversed Polarity withEquipment Ground

    Reversed Circuit andEquipment Ground

    Reversed Polarity with

  • 7/31/2019 Electrical Safety Design

    32/110

    Reversed Polarity with

    Circuit Ground In reversed polarity the black (ungrounded) and white (circuit

    grounded) conductors are reversed.

    Although a shock hazard may not exist in this situation, othermechanical hazards can occur.

    For example, if an internal fault occurs in the wiring, the equipmentwould not stop when the switch is released or would start as soon asthe supply cord is plugged into the improperly wired outlet. This couldresult in serious injury.

    Reversed Polarity with

  • 7/31/2019 Electrical Safety Design

    33/110

    Reversed Polarity with

    Equipment Ground It is extremely dangerous when the black (ungrounded) and green

    (equipment grounding) conductors are reversed.

    The metal case of the equipment is at 120 volts with reference to thesurroundings. The equipment will not work with this wiring, however,it is possible for a person to attempt to troubleshoot the problembefore unplugging the power cord.

    Physical contact with a conductive equipment surface will result in aserious, or even deadly, shock.

    Reversed Circuit &

  • 7/31/2019 Electrical Safety Design

    34/110

    Reversed Circuit &

    Equipment The figure below shows the white (circuit grounded) and green

    (equipment grounding) conductors reversed. Although it is not considered by OSHA or code terminology to

    be reversed polarity, a hazard can still exist. In this case, dueto the wiring error, the white wire is being used to provideequipment grounding. Under certain conditions, this could be

    dangerous

    Wiring Design and

  • 7/31/2019 Electrical Safety Design

    35/110

    Wiring Design and

    Protection - Service Entrance The service entrance is where

    the serving conductors enter abuilding.

    Means shall be provided todisconnect all conductors in abuilding or other structure fromthe service entrance

    conductors. One disconnecting means for

    conductors is required to belocated at a point near theservice entrance.

    The disconnecting means canbe a switch or circuit breaker,and must be capable ofinterrupting the circuit from thesource of supply.

    Wiring Design and

  • 7/31/2019 Electrical Safety Design

    36/110

    Wiring Design and

    Protection - Service Entrance The disconnecting means

    shall plainly indicate whether itis in the open or closedposition.

    Additional service entrancerequirements exist for servicesover 600 volts, nominal:

    Service-entrance conductorsinstalled as open wires shallbe guarded to make themaccessible only to qualifiedpersons

    Signs warning of high voltageshall be posted where otherthan qualified employeesmight come in contact withlive parts.

    Wiring Design and Protection

  • 7/31/2019 Electrical Safety Design

    37/110

    Wiring Design and Protection -

    Overcurrent Protection Conductors and equipment shall

    be protected from overcurrent in

    accordance with their ability tosafely conduct current.

    Feeders and branch circuits over600 volts, nominal shall also haveshort-circuit protection.

    The requirements described onthe following screens apply toovercurrent protection of circuitsrated 600 volts, nominal or less.

    An important, basic requirementfor all overcurrent devices is toensure they have adequateinterrupt ratings for the circuit inwhich they will be installed. Conductors and Overcurrent

    Devices

    Conductors and Overcurrent

  • 7/31/2019 Electrical Safety Design

    38/110

    Conductors and Overcurrent

    Devices Electric current is the flow of electrons through a conductor.

    The size of the wire is the main determinate in deciding how much current can safely flow

    through a conductor. A larger wire can carry more current safely. If too much current flows through a

    conductor, excess heat is produced.

    If the circuit is not protected, the heat may continue to build until it reaches a temperaturehigh enough to destroy the insulation and cause a fire.

    The National Electrical Code specifies the allowable current flow permitted in certain-

    sized conductors. Ampacity is the term used to describe the current-carrying capacity of a conductor. The

    size of the fuse or circuit breaker required to provide protection is determined by theampacity of the conductor in the circuit to be protected and the type of load that is on thecircuit.

    Fuses and circuit breakers are designed to protect equipment and facilities againstovercurrent and overheating, but they also provide considerable protection against shock

    in most situations. The basic idea of a protective device is to make a weak link in the circuit. A fuse acts as a

    weak link that is the first piece of the system to be destroyed.

    In the case of a circuit breaker, a set of contacts open the circuit and stops the flow ofcurrent. Unlike a fuse, a circuit breaker can be re-used by re-closing the contacts.

    Wiring Design and Protection

  • 7/31/2019 Electrical Safety Design

    39/110

    Wiring Design and Protection -

    Overcurrent Protection

    Except for motors runningoverload protection,overcurrent devices may notinterrupt the continuity of thegrounded conductor unless allconductors of the circuit areopened simultaneously.

    Unless excepted, overcurrentdevices are always placed inthe "hot" side of a circuit(usually a black wire) and inseries with the load, so that all

    the current in the circuit mustflow through overcurrentdevices.

    Wiring Design and Protection -

  • 7/31/2019 Electrical Safety Design

    40/110

    Wiring Design and Protection -

    Overcurrent Protection

    Except for service fuses, allcartridge fuses which are

    accessible to other thanqualified persons and all fusesand thermal cutouts on circuitsover 150 volts to ground shallbe provided with

    disconnecting means. This disconnecting means

    shall be installed so that thefuse or thermal cutout can bedisconnected from its supply

    without disrupting service toequipment and circuitsunrelated to those protectedby the overcurrent device.

    Wiring Design and Protection -

    http://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppt
  • 7/31/2019 Electrical Safety Design

    41/110

    Wiring Design and Protection -

    Overcurrent Protection Overcurrent devices require

    proper operation and maintenance

    due to the tremendous amounts ofenergy they are likely to handleduring a fault.

    Device location must allow forimmediate access by all employeeor authorized building

    management personnel whentrouble occurs.

    Overcurrent devices may not belocated where they will beexposed to physical damage.

    Physical damage often resultswhen they are located where theycan be struck by lift trucks or othervehicles, by crane hooks, bymaterials being handled, etc.

    Wiring Design and Protection -

  • 7/31/2019 Electrical Safety Design

    42/110

    Wiring Design and Protection -

    Overcurrent Protection Most fuses and circuit breakers

    have the potential to emit flashes

    or sparks. As a result, easily ignitable

    material should not be storednearby.

    Since fuses and overcurrentdevices can sometimes operate atelevated temperatures, they shallbe located or shielded so thatemployees will not be burned orotherwise injured by theiroperation.

    Wiring Design and Protection -

  • 7/31/2019 Electrical Safety Design

    43/110

    Wiring Design and Protection -

    Overcurrent Protection Circuit breakers shall clearly

    indicate whether they are in

    the open (off) or closed (on)position.

    Where circuit breaker handleson switchboards are operatedvertically rather than

    horizontally or rotationally, theup position of the handle shallbe the closed (on) position.

    If used as switches in 120-volt,fluorescent lighting circuits,

    circuit breakers shall beapproved for the purpose andmarked "SWD."

    http://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppt
  • 7/31/2019 Electrical Safety Design

    44/110

    Quiz Question:

    The circuit grounded conductor shouldbe colored :

    Green with yellow stripes Blue

    White

    Green

  • 7/31/2019 Electrical Safety Design

    45/110

    Quiz Question:

    Most equipment will NOT operate if the

    supply and grounding wires are not

    connected correctly.

    True

    False

    Wiring Design and Protection -

  • 7/31/2019 Electrical Safety Design

    46/110

    Wiring Design and Protection

    Grounding Requirements Grounding electrical circuits and

    electrical equipment is required to

    protect employees againstelectrical shock, safeguard againstfire, and protect against damageto electrical equipment.

    There are two kinds of groundingwhich correspond to the two types

    of grounding conductors (circuitgrounding conductors andequipment grounding conductors)described earlier in this module. Electrical Circuit or System

    Grounding

    Electrical Equipment Grounding

    Circuit and Equipment GroundingSchematic

    Schematic of Circuit and

    http://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppt
  • 7/31/2019 Electrical Safety Design

    47/110

    Equipment Grounding

    This is an example of circuit and equipment grounding.

    Wiring Design and

  • 7/31/2019 Electrical Safety Design

    48/110

    g g

    Protection - Grounding Path The path for electrical circuit and

    equipment grounding shall be

    permanent and continuous.

    This requirement was extractedfrom NEC 250-51, EffectiveGrounding Path.

    NEC 250-51, Effective GroundingPath

    Wiring Design and

    http://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppt
  • 7/31/2019 Electrical Safety Design

    49/110

    g g

    Protection - Grounding Path Remember the following items

    regarding safe grounding paths.

    The fault current in AC circuits willbe limited by the sum ofresistance and reactance. Theonly low- reactance path is thatwhich closely follows the circuitconductors.

    If a metallic raceway system isused, make sure that the metallicsystem is continuous andpermanent.

    In cases where a metallicraceway system is not used,

    provide a green or bareequipment grounding conductorclose to the supply conductors toassure that all enclosures arebonded together and to thesource.

    Support, Enclosure, and

  • 7/31/2019 Electrical Safety Design

    50/110

    Equipment Grounding Proper grounding is important

    to prevent shock, stabilize

    voltage, and channel faultcurrents.

    Metal enclosures for serviceequipment shall be grounded.

    Metal cable trays, metalraceways, and metalenclosures for conductorsshall be grounded, except for:

    Metal enclosures such assleeves that are used toprotect cable assembliesfrom physical damage

    Support, Enclosure, and

  • 7/31/2019 Electrical Safety Design

    51/110

    Equipment Grounding Metal enclosures for

    conductors added to existing

    installations of open wire,knob-and-tube wiring, andnon-metallic-sheathed cablewhich meet the followingconditions: Runs are less than 25 feet

    Enclosures are free fromprobable contact withground, grounded metal,metal laths, or otherconductive materials

    Enclosures are guardedagainst employee contact.

    Support, Enclosure, and

  • 7/31/2019 Electrical Safety Design

    52/110

    Equipment Grounding Frames of electric ranges, wall-

    mounted ovens, counter-mountedcooking units, clothes dryers, and metaloutlet or junction boxes which are partof the circuit for these appliances shallbe grounded.

    Exposed non-current carrying metalparts of fixed equipment which maybecome energized and meet the

    following conditions shall be groundedif: Within 8 feet vertically or 5 feet

    horizontally of ground or groundedmetal objects and subject to employeecontact

    Located in a wet or damp location andnot isolated

    In electrical contact with metal In a hazardous (classified) location

    Supplied by a metal-clad, metal-sheathed, or grounded metal racewaywiring method.

    Support, Enclosure, and

  • 7/31/2019 Electrical Safety Design

    53/110

    Equipment Grounding If exposed non-current carrying metal

    parts of fixed equipment operates withany terminal at over 150 volts to groundwhich may become energized it mustbe grounded.

    However, there are exceptions to thissituation. These exceptions are:

    Enclosures for switches or circuit

    breakers used for other than serviceequipment and only accessible byqualified person

    Metal frames of electrically heatedappliances which are permanently andeffectively insulated from ground

    The cases of distribution apparatussuch as transformers and capacitors

    mounted on wooden poles at a heightexceeding 8 feet above ground orgrade level.

    Support, Enclosure, and

  • 7/31/2019 Electrical Safety Design

    54/110

    Equipment Grounding Exposed non-current-carrying metal parts of cord- and plug-connected

    equipment which may become energized shall be grounded:

    If in a hazardous (classified) location If operated at over 150 volts to ground, except for guarded motors and metal

    frames of electrically heated appliances when the appliance frames arepermanently and effectively insulated from ground

    If the equipment is of the following types: Refrigerators, freezers, and air conditioners

    Clothes-washing, clothes-drying, dishwashing machines, sump pumps, andelectrical aquarium equipment

    Hand-held motor-operated tools

    Motor-operated appliances of the following types: hedge clippers, lawn mowers,snow blowers, and wet scrubbers

    Cord- and plug-connected appliances used in damp or wet locations or byemployees standing on the ground or on metal floors or working inside of metaltanks or boilers

    Portable and mobile X-ray and associated equipment

    Tools likely to be used in wet and conductive locations

    Portable hand lamps.

    Support, Enclosure, and

  • 7/31/2019 Electrical Safety Design

    55/110

    Equipment Grounding If metal parts or tools are likely to

    be used in wet or conductive

    locations, they do not have to begrounded if their power is suppliedthrough an isolating transformerwith an ungrounded secondarywinding of not over 50 volts.

    Listed or labeled portable toolsand appliances protected by anapproved system of doubleinsulation, or its equivalent, neednot be grounded.

    The equipment shall bedistinctively marked to indicatethat the tool or appliance uses anapproved system of doubleinsulation.

    Support, Enclosure, and

  • 7/31/2019 Electrical Safety Design

    56/110

    Equipment Grounding The metal parts of the following

    non-electrical equipment shall be

    grounded:

    Frames and tracks of electricallyoperated cranes

    Frames of non-electrically drivenelevator cars to which electricconductors are attached

    Hand operated metal shiftingropes or cables of electricelevators

    Metal partitions, grill work, andsimilar metal enclosures aroundequipment of over 750 volts

    between conductors.

    Wiring Design and Protection -

  • 7/31/2019 Electrical Safety Design

    57/110

    Grounding Methods "Non-current-carrying metal

    parts of fixed equipment shall

    be grounded by an equipmentgrounding conductorwhichruns with or encloses thecircuit conductors, if required.

    One option for grounding is to

    contain the equipmentgrounding conductor known asa third wire.

    For D-C circuits only, theequipment grounding

    conductor may be runseparately from the circuitconductors. Third Wire Example

    http://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppt
  • 7/31/2019 Electrical Safety Design

    58/110

    Third Wire Example A third wire and prong are commonly

    provided in the cord set to ground cord-connected equipment.

    The third wire serves as an equipmentgrounding conductor which isconnected to the metal housing of aportable tool and a metal grounding businside the service entrance equipment.

    The third wire provides a path for fault

    current should an insulation failureoccur.

    In this manner, dangerous fault currentwill be directed back to the source (theservice entrance) and will enable circuitbreakers or fuses to operate.

    This opens the circuit and stops the

    current flow. Click here to see the potential danger

    and benefit of a third wire systemcontrol.

  • 7/31/2019 Electrical Safety Design

    59/110

    Third Wire ExamplePotential shock hazards exist when an equipment grounding conductor is not used. If a

    fault occurs, most of the current will follow the path of least resistance. The worker can

    provide that path to ground as an alternate to the white circuit grounded conductor

    (neutral) for some portion of the current. The shock severity will depend on the amount ofcurrent that flows through the worker.

    Cord- and Plug-Connected Equipment Without Equipment GroundingConductor (Short circuit flows through worker)

  • 7/31/2019 Electrical Safety Design

    60/110

    Third Wire ExampleIf there is a properly connected grounded conductor the current in a fault is not sent

    through the worker. It should be noted that properly bonded conduit and associated metal

    enclosures can also serve as a grounding conductor.

    Cord- and Plug-Connected Equipment With Equipment GroundingConductor (Short circuit flows through equipment ground)

    Wiring Design and

  • 7/31/2019 Electrical Safety Design

    61/110

    Protection - HigVoltage High voltage refers to circuits

    of 1000 volts and over. If high

    voltage systems aregrounded, they shall complywith all applicable provisionspreviously discussed in thismodule as well as additionalrequirements andmodifications contained in theWiring Design and Methodssection.

  • 7/31/2019 Electrical Safety Design

    62/110

    Quiz Question:

    Reactance is not considered when

    calculating AC fault current for

    conductors.

    True

    False

  • 7/31/2019 Electrical Safety Design

    63/110

    Quiz Question:

    The third wire in a cord is used for

    equipment grounding.

    True False

    Wiring Methods and

  • 7/31/2019 Electrical Safety Design

    64/110

    Components The Wiring Methods and Components section is based on standard

    1910.305. This section describes general and specific requirements

    for various wiring methods and components. The topics included inthis section are listed below.

    The wiring method provisions described on the following pages donot apply to the conductors that are an integral part of factory-assembled equipment.

    Wiring Methods and Components -

  • 7/31/2019 Electrical Safety Design

    65/110

    General Requirements

    Wiring methods must adhere tocertain general requirements:

    Metal raceways, cable, armor,and other metal enclosures forconductors shall be metallically

    joined together into a continuouselectric conductor and shall be soconnected to all boxes, fittings,and cabinets to provide effective

    electrical continuity No wiring systems of any type

    shall be installed in ducts used totransport dust, loose stock, orflammable vapors

    No temporary or permanentwiring system may be installed in

    any duct used for vapor removalor for ventilation of commercial-type cooking equipment, or in anyshaft containing only such ducts.

    Wiring Methods and Components -

  • 7/31/2019 Electrical Safety Design

    66/110

    Temporary Wiring

    Temporary wiring can be an easysolution to wiring problems.

    However, the use of temporarywiring for electrical power andlighting installations of 600 volts,nominal or less is restricted to thesituations listed here.

    During remodeling, maintenance,repair or demolition of buildings,structures, or equipment andsimilar activities.

    For experimental or developmentwork.

    For a period not to exceed 90days for Christmas decorativelighting, carnivals, and similarpurposes.

    Wiring Methods and Components -

  • 7/31/2019 Electrical Safety Design

    67/110

    Temporary Wiring

    Temporary wiring over 600 volts,nominal may be used only during

    periods of tests, experiments, oremergencies.

    Temporary electrical power andlighting wiring methods may be ofa class less than would berequired for a permanent

    installation. However, all other requirements in

    this module for permanent wiringshall apply to temporary wiringinstallations.

    Wiring Methods and Components -

  • 7/31/2019 Electrical Safety Design

    68/110

    Temporary Wiring

    This page and the next one describe general requirements fortemporary wiring conditions.

    Feeders shall originate in an approved distribution center. Theconductors shall be run as multi-conductor cord or cable assemblies, orthey may be run as open conductors or insulators not more than 10 feetapart if they will not be subject to physical damage.

    Branch circuits shall originate in an approved power outlet or panelboard.Conductors shall be open conductors or multi-conductor cord or cable

    assemblies. If run as open conductors, branch circuits shall be fastenedat ceiling height every 10 feet. No branch- circuit conductor may be laidon the floor, and each branch circuit that supplies receptacles or fixedequipment shall contain a separate equipment grounding conductor.

    Receptacles used in temporary wiring circuits must provide a connectionfor an equipment grounding conductor. Unless the receptacle is supplied

    by a metallic raceway that provides a continuous grounding path back tothe source, a separate equipment grounding conductor must be placed inthe branch circuit. There must be good electrical connection between thereceptacle grounding terminal and the equipment grounding conductor. Receptacle Temporary Wiring Schematic

    Receptacle Temporary

    http://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppt
  • 7/31/2019 Electrical Safety Design

    69/110

    Wiring Schematic This figure illustrates the proper wiring of receptacles used with a temporary

    wiring system.

    Wiring Methods and Components -

  • 7/31/2019 Electrical Safety Design

    70/110

    Temporary Wiring More general requirements for temporary wiring conditions are shown here.

    No bare conductors nor earth returns may be used for the wiring of anytemporary circuit. Earth returns are prohibited because they are not alwayseffective and may present a serious hazard on temporary work sites.

    Description of Earth Returns

    Suitable disconnecting switches or plug connectors shall be installed to permit thedisconnection of all ungrounded conductors of each temporary circuit.

    Lamps for general illumination shall be protected from accidental contact orbreakage. To be adequately protected, lamps shall be elevated at least 7 feet fromnormal working surfaces or by a suitable fixture or lampholder with a guard.

    Flexible cords and cables shall be protected from accidental damage. Sharp

    corners and projections shall be avoided. Flexible cords and cables shall beprovided with protection to avoid damage when passing through doorways or otherpinch points.

    http://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppt
  • 7/31/2019 Electrical Safety Design

    71/110

    Description of Earth Returns Earth returns use the earth to provide a current path back to the supply source. This is

    done by implanting a grounding electrode at the equipment being served and connectingthe equipment to the ungrounded conductor and to the grounding electrode.

    Since one side of the supply source is also connected to ground through a groundingelectrode, a return path exists; however, its effectiveness is dependent on varying soilconditions.

    The graphic to below shows an earth return, which is not allowed, in contrast to a properreturn system

  • 7/31/2019 Electrical Safety Design

    72/110

    Conductors for General Wiring Temporary or permanent

    conductors can create shock andfire hazards that usually can beprevented through insulation.Insulating material should be theappropriate composition andthickness as rated for:

    Voltage the conductor will carry

    Current the conductor will carry

    Temperature extremes and otherenvironmental factors

    Location of the conductor.

    Insulated conductors must also beeasily identifiable, color coding ismost often used.

  • 7/31/2019 Electrical Safety Design

    73/110

    Conductors for General Wiring The colors to be used are:

    White or natural gray forneutralconductors

    Green or green with yellow stripesforequipment groundingconductors unless bare wires areused.

    Other types of circuit wires may beany color except those listedabove.

    http://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppt
  • 7/31/2019 Electrical Safety Design

    74/110

    Cabinets, Boxes, and Fittings In addition to shock and fire hazards,

    conductors could be damaged if theyrub against the sharp edges where they

    enter cabinets, boxes, or fittings. To protect them some type of clamp or

    rubber grommet must be used.

    The device used must close the holethrough which the conductor passes aswell as provide protection fromabrasion.

    If the conductor is in a conduit and theconduit fits tightly in the opening,additional sealing is not required.

    The knockouts in cabinets, boxes, andfittings should be removed only ifconductors are to be run through them.

    However, if a knockout is missing or ifthere is another hole in the box, thehole or opening must be closed.

    http://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppt
  • 7/31/2019 Electrical Safety Design

    75/110

    Cabinets, Boxes, and Fittings All pull boxes, junction boxes, and

    fittings shall be provided withapproved covers. If metal coversare used, they shall be grounded.

    In completed installations, eachoutlet box shall have a cover,faceplate, or fixture canopy. Outlet

    box covers having holes throughwhich flexible cord pendants pass,shall be provided with bushings orshall have smooth, well-roundedsurfaces on which the cords maybear.

    Boxes shall provide a completeenclosure for the containedconductors or cables.

    http://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppt
  • 7/31/2019 Electrical Safety Design

    76/110

    Cabinets, Boxes, and Fittings Boxes shall be closed by suitable

    and securely fastened covers.

    Underground box covers thatweigh over 100 pounds meet thisrequirement.

    Box covers shall be permanentlymarked "HIGH VOLTAGE" on theoutside of the box cover and shallbe readily visible and legible.

    If cabinets, boxes, fittings, cutout

    boxes, and panelboard enclosuresmust be located in a damp or wetlocation, they shall be installed soas to prevent moisture or waterfrom entering and accumulatingwithin the enclosures.

  • 7/31/2019 Electrical Safety Design

    77/110

    Switchboards and Panelboards Switches, switchboards, and circuit

    breakers shall be weatherproof in wetlocations.

    A switchboard that has exposed liveparts must be located in an area that isnot subject to wetness or dampness.

    One purpose of 1910.305 is to lessenthe chance of severe shock if a workeraccidentally comes into contact with thelive parts.

    Additionally, only qualified persons mayhave access to switchboards withexposed live parts.

    To limit access, the switchboard shouldbe located in a locked room or within alocked cage or fenced area.

    Keys to the locks should be controlledto ensure that only properly trainedpersonnel are allowed to enter thearea.

  • 7/31/2019 Electrical Safety Design

    78/110

    Switches Switches provide a means

    for turning power on and off

    to equipment or circuits.

    Three type of switches arecovered in the WiringMethods and Components

    section.

    Single-Throw Knife Switch

    Double-Throw Knife

    Switch Flush Snap Switch

  • 7/31/2019 Electrical Safety Design

    79/110

    Single-Throw Knife Switch Switches provide a means for turning power on and off to equipment or circuits.

    Single-throw knife switches have one energized (closed or "ON") position and one open(dead or "OFF") position. The switch must be designed so that when it is in the open

    position, the blades are not energized (connected to the load side, not the supply side ofthe circuit).

    Switches must also be installed so that if the switch falls downward, it will not fall into itsenergized position. However, some single-throw knife switches are designed to beinstalled so that they open upward, but these must have a latch or other locking deviceused to secure the switch in the open position.

  • 7/31/2019 Electrical Safety Design

    80/110

    Double-Throw Knife Switch Double-throw knife switches

    are knife switches that have

    two energized (closed or"ON") positions and one open(dead or "OFF") position.

    These switches can bemounted vertically so that theyare moved up and down, orhorizontally so that they aremoved left and right. Ifswitches are mountedvertically, they must have alocking device (such as a

    spring-loaded device) that willhold the switch blades in theopen position.

  • 7/31/2019 Electrical Safety Design

    81/110

    Flush Snap Switch Flush Snap switches that

    are mounted in ungrounded

    metal boxes and locatedwithin reach of conductingfloors or other conductingsurfaces shall be provided

    with faceplates of non-conducting, non-combustible material.

    Motor Protection

  • 7/31/2019 Electrical Safety Design

    82/110

    Switches are used as disconnecting means for motors.Specific motor disconnection requirements are listed here:

    A disconnecting means shall be located in sight from thecontroller (within 50 feet of the controller). However, a singledisconnecting means may be located adjacent to a group ofcoordinated controllers that are mounted adjacent to each other

    on a multi-motor continuous process machine.

    The controller disconnecting means for motor branch circuitsover 600 volts, nominal may be out of sight of the controller, ifthe controller is marked with a warning label giving the location

    and identification of the disconnecting means which is to belocked in the open position

    Motor Protection

  • 7/31/2019 Electrical Safety Design

    83/110

    The disconnecting means shall disconnect the motor and thecontroller from all ungrounded supply conductors and shall be so

    designed that no pole can be operated independently

    If a motor and the driven machinery are not in sight from thecontroller location, the installation shall comply with one of thefollowing conditions:

    The controller disconnecting means shall be capable of being lockedin the open position

    A manually operable switch that will disconnect the motor from itssupply source shall be placed in sight from the motor location.

    Motor Protection

  • 7/31/2019 Electrical Safety Design

    84/110

    Additional motordisconnecting meansrequirements are listed here:

    The disconnecting means shall plainly

    indicate open (off) or closed (on) The disconnecting means shall be

    readily accessible. If more than one isprovided for the same equipment, onlyone must be readily accessible

    An individual disconnecting meansshall be provided for each motor, but asingle disconnecting means may beused for a group of motors under anyone of the following conditions: If a number of motors drive special

    parts of a single machine or piece ofapparatus, such as a metal orwoodworking machine, crane, or hoist

    If a group of motors is under theprotection of one set of branch-circuitprotective devices

    If a group of motors is in a single roomin sight from the location of thedisconnecting means.

    Motor Protection

    http://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppt
  • 7/31/2019 Electrical Safety Design

    85/110

    Motordisconnecting means provideone method for meeting the followingrequirement.

    Motors, motor-control apparatus, andmotor branch-circuit conductors shallbe protected against overheating due tomotor overloads or start failure, andagainst short-circuits or ground faults.

    Overload protection is not required ifstopping a motor could cause additionalor increased hazards.

    An example is where motor operation isnecessary for a safe shutdown of

    equipment or process and motoroverload sensing devices areconnected to a supervised alarm

    Motor Protection

    http://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppt
  • 7/31/2019 Electrical Safety Design

    86/110

    Stationary motors are not required toguard commutators, collectors, andbrush rigging located inside of motor

    end brackets and not conductivelyconnected to supply circuits operatingat more than 150 volts to ground.

    Exposed live parts of motors andcontrollers operating at 50 volts or morebetween terminals shall be guardedagainst accidental contact by:

    Installing live parts in a room orenclosure only accessible to qualifiedpersons

    Installing live parts on a suitablebalcony, gallery, or platform, elevatedand arranged as to exclude unqualifiedpersons

    Elevating live parts 8 feet or moreabove the floor.

    Motor Protection

  • 7/31/2019 Electrical Safety Design

    87/110

    Suitable insulating mats or platformsshall be provided and used byattendants to stand on if they are

    required to work near live controller ormotor parts operating at over 150 voltsto ground where parts are guardedagainst accidental contact only bylocation.

    Transformers

  • 7/31/2019 Electrical Safety Design

    88/110

    Contact with transformers occurs less often then with motors; however,transformers still pose a serious shock and fire hazard. The requirementsbelow apply to most transformers.

    To prevent accidents, follow these requirements: The operating voltage of exposed live parts of transformer installations shall be

    indicated by warning signs or visible markings on the equipment or structure

    Dry-type, high fire point liquid-insulated, and askarel-insulated transformersinstalled indoors and rated over 35 kV shall be in a vault

    Oil-insulated transformers installed indoors shall be in a vault if they present a firehazard to employees

    Combustible material, combustible buildings along with parts of buildings, fireescapes, and door and window openings shall be safeguarded from fires which mayoriginate in attached or adjacent oil-insulated transformers

    Transformer vaults shall be constructed so as to contain fire and combustible liquidswithin the vault and to prevent unauthorized access. Locks and latches shall be so

    arranged that a vault door can be readily opened from the inside Any pipe or duct system foreign to the vault installation may not enter or pass

    through a transformer vault

    Materials may not be stored in transformer vaults.

    Capacitors

  • 7/31/2019 Electrical Safety Design

    89/110

    Capacitors are used in most electricalsystems to store electrical charge;therefore, they can be a source of

    severe shock unless that charge isdrained when the capacitors aredisconnected from the power source.

    Unless some type of automaticdischarge is designed into a system,devices such as resistors must bepermanently attached across the

    terminals of the capacitors to drain thecharge when the circuit is open (de-energized).

    Most capacitors are manufactured withthis type of discharge resistor. Surgecapacitors, which act like lightning rods,do not require an automatic means for

    draining the charge.

    Storage Batteries

  • 7/31/2019 Electrical Safety Design

    90/110

    Storage batteries (which areusually lead-acid or alkali) presentan explosive hazard in addition to

    a shock danger because they canproduce explosive gases,including hydrogen, if they areovercharged.

    These explosive gases must notaccumulate in quantities that mayform an explosive mixture with air.

    A spark or open flame could ignitethe mixture and cause anexplosion.

    To prevent this accumulation,

    good ventilation must be provided.

    Quiz Question:

  • 7/31/2019 Electrical Safety Design

    91/110

    Temporary electric power and lighting

    wiring may be of a class less thanwould be required for permanent

    installations.

    True

    False

    Quiz Question:

  • 7/31/2019 Electrical Safety Design

    92/110

    Temporary wiring over 600 volts,

    nominal may NOT be used for:

    Emergencies Experiments

    Tests Remodeling

  • 7/31/2019 Electrical Safety Design

    93/110

    Flexible Cords and Cables

  • 7/31/2019 Electrical Safety Design

    94/110

    The standard for safe use offlexible cords is one of themost frequently violatedelectrical standards,particularly in smaller plants.

    There is a temptation tomisuse flexible cords becausethey seem to offer a quick andeasy way to carry electricity towhere it is needed.

    The basic problem is thatflexible cords generally aremore vulnerable than the fixed

    wiring of the building.

    Flexible Cords and Cables

  • 7/31/2019 Electrical Safety Design

    95/110

    Flexible cords should not be: Used as a substitute for the

    fixed wiring of the structure

    Run through holes in walls,ceilings, or floors

    Run through doorways,windows, or similar openings

    Attached to building surfaces

    Concealed behind buildingwalls, ceilings, or floors.

    Uses of Flexible Cords andCables

    Uses of Flexible Cords and

    Cables

  • 7/31/2019 Electrical Safety Design

    96/110

    Flexible cords and cables shall be approved and are suitable for thefollowing:

    Pendants Fixtures Wiring

    Portable lamp or appliance connection

    Elevator cables

    Wiring of cranes and hoists (where flexibility is necessary)

    Connection of stationary equipment to facilitate their frequentinterchange

    Prevention of the transmission of noise or vibration. (vibration mightfatigue fixed wiring and result in a situation more hazardous than flexiblecord.)

    Appliances where the fastening means and mechanical connections are

    designed to permit removal for maintenance and repair (e.g. watercoolers, exhaust fans)

    Approved data processing cables.

    Equipment for General Use -

    Flexible Cords and Cables

    http://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppt
  • 7/31/2019 Electrical Safety Design

    97/110

    There is usually not muchquestion about using the shortflexible cord attached to anapproved appliance or tool.

    Likewise, there is usually noquestion about an extensioncord used temporarily topermit the use of the

    appliance or tool in itsintended manner at somedistance from a fixed outlet.

    However, there are questionswhen the usage is not

    obviously temporary, and aflexible cord is used to avoidproviding a fixed outlet whereneeded.

    Equipment for General Use -

    Flexible Cords and Cables

  • 7/31/2019 Electrical Safety Design

    98/110

    If a flexible cord is usedimproperly, it can be damagedby: Door or window edges

    Staples or fastenings

    Abrasion from adjacentmaterials

    Aging.

    If the conductors becomepartially exposed over time,they will create a danger ofshocks, burns, or fire.

    Equipment for General Use -

    Flexible Cords and Cables

  • 7/31/2019 Electrical Safety Design

    99/110

    Flexible cords shall only beused in continuous lengthswithout splices or taps.

    Hard service flexible cords,No. 12 or larger, may berepaired if the splice retainsthe insulation, outer sheathproperties, and usage

    characteristics of the cord. Flexible cords shall be

    connected to devices andfittings so that strain relief isprovided to prevent pull from

    being directly transmitted tojoints or terminal screws.

    Portable Cables Over 600

    Volts, Nominal

    http://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppt
  • 7/31/2019 Electrical Safety Design

    100/110

    Multi-conductor portable cable foruse in supplying power to portableor mobile equipment at over 600

    volts, nominal shall consist of No.8 or larger conductors employingflexible stranding.

    Cables operated at over 2000volts shall be shielded for thepurpose of confining the voltage

    stresses to the insulation. Grounding conductors shall be

    provided.

    Connectors for these cables shallbe of a locking type with

    provisions to prevent their openingor closing while energized.

    Portable Cables Over 600

    Volts, Nominal

  • 7/31/2019 Electrical Safety Design

    101/110

    Strain relief shall be provided atconnections and terminations.

    Portable cables may not beoperated with splices unless thesplices are of the permanentmolded, vulcanized, or otherapproved type.

    Termination enclosures shall besuitably marked with a highvoltage hazard warning.

    Termination enclosures shall beaccessible only to authorized andqualified personnel.

    Lighting Fixtures, Lampholders,

    Lamps, and Receptacles

    http://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppt
  • 7/31/2019 Electrical Safety Design

    102/110

    Fixtures, lampholders, lamps, rosettes, and receptacles may not have liveparts exposed to employee contact during normal operation. However,rosettes, and cleat-type lampholders and receptacles located at least 8 feet

    above the floor may have exposed parts. Portable type handlamps powered through flexible cords shall be equipped

    with a handle of molded composition or other material approved for thepurpose, and a substantial guard shall be attached to the lampholder or thehandle.

    Screw-shell type lampholders shall be installed for use as lampholders onlyand must not be used with screw-base socket adapters. These adaptersscrew into the existing lamp socket and convert lampholders into receptacles.These adapters are not permitted because equipment grounding connectionscannot be made through the two-blade adapters and because the fixture hasbeen designed only for lighting.

    Only weatherproof lampholders may be installed in wet or damp areas.Unprotected lampholders might allow moisture to enter the lampholder socket,creating an electrical shock hazard.

    Cord Conductors

  • 7/31/2019 Electrical Safety Design

    103/110

    Cord connectors are used to join twosections of electrical cord together.

    Attachment plugs are devices that arefastened onto the end of a cord so thatelectrical contact can be made betweenthe conductors in the cord and theconductors in a receptacle.

    Connectors, plugs, and receptacles areuniquely designed for different voltagesand currents, so that only matching

    plugs will fit into the correct receptacleor cord connector.

    In this way, equipment rated for onevoltage-current combination cannot beplugged into a power system that is of adifferent voltage or current capacity.

    The only exceptions to this are 125-volt

    and 250-volt, 20-Ampere, T-slotreceptacles.

    The 125-Volt, 20-Ampere T-slotreceptacle is illustrated in the graphic tothe left.

    Cord Conductor

  • 7/31/2019 Electrical Safety Design

    104/110

    An electrical appliance that israted for 15 amperes will notoverload a 20-ampere circuit, and

    the 20-ampere breaker will stillprovide overcurrent protection for15-ampere equipment.

    Note that the opposite is notnecessarily true; therefore, a 20-ampere plug is made not to fit into

    a 15-ampere receptacle or cordconnector.

    The National ElectricalManufacturer's Association(NEMA) has established standardplug and receptacle connector

    blade configurations.

    Cord Conductor

    http://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppt
  • 7/31/2019 Electrical Safety Design

    105/110

    Each has been developed tostandardize the use of plugs andreceptacles for different voltages,

    amperages, and phases from 115volts through 600, from 15amperes through 60, and forsingle- and three-phase systems.

    A receptacle installed in a wet ordamp location shall be suitable for

    the location.

    Appliances

  • 7/31/2019 Electrical Safety Design

    106/110

    Along with receptacles and lightfixtures, appliances are found in mostworkplaces.

    Electrical appliances such as portableair conditioning units, coffee-makers,and fans must not have any exposedlive wires or electrical parts that mightcreate an electric shock hazard.

    Exceptions to this are appliances suchas space heaters or toasters that must

    have exposed current-carrying partsthat operate at high temperatures totransfer heat.

    The heat generated by these partsminimizes the possibility of directcontact and resultant electric shock.

    Each appliance shall be marked with itsrating in volts and amperes or volts andwatts.

    All appliances must have adisconnecting means.

    Quiz Question:

    http://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppthttp://c/PPT/Glossary.ppt
  • 7/31/2019 Electrical Safety Design

    107/110

    Appliances may have live parts exposed if:

    The heat produced by the live parts protectsagainst contact

    A proper disconnecting means is installed

    A warning sign is present An insulating material protects against

    accidental contact

    Quiz Question:

  • 7/31/2019 Electrical Safety Design

    108/110

    Flexible cords may be:

    Run through doorways, windows, or similaropenings

    Attached to building surfaces

    Used to prevent transmission of noise orvibration

    Used as a substitute for the wiring of a structure

    Quiz Question:

  • 7/31/2019 Electrical Safety Design

    109/110

    Portable cables may not be operated

    with splices unless the splices are ofthe permanent molded, vulcanized, orother approved type.

    True

    False

    Summary

  • 7/31/2019 Electrical Safety Design

    110/110

    During this module we have discussed the

    scope and philosophy of Subpart S of theOSHA standard and presented specific andgeneral electrical safety design

    requirements for:

    General Requirements

    Wiring Design and Protection Wiring Methods and Components

    Equipment for General Use.