S S S S S S S S S S S NO SCALE SEISMIC RESTRAINTS FOR ELECTRICAL SYSTEM COMPONENTS 5,6,7 1,4 3,8,9 X X X X X X X X 1. LIGHT FIXTURES LESS THAN 20 POUNDS POWERED WITH FLEXIBLE CABLE LESS THAN 3 FEET, FIXTURE SHALL BE MECHANICALLY ATTATCHED TO CEILING GRID. 2. PENDANT TYPE FIXTURES DO NOT REQUIRE SWAY BRACING WHEN IT CAN SWING AT AN ANGLE OF 45° FROM VERTICAL WITHOUT IMPACTING OTHER COMPONENTS. 3. TABLE 4.4, EXCEPTION FOR IP=1.0, WEIGHT LESS THAN 400 POUNDS. 4. TABLE 4.4, EXCEPTION FOR IP=1.0, WEIGHT LESS THAN 20 POUNDS. 5. TABLE 4.4, EXCEPTION FOR IP=1.0, WEIGHT 5LBS/FT OR LESS. 6. FLEXIBLE CONNECTION REQUIRED BETWEEN EQUIPMENT AND COMPONENTS IF INSTALLATION OTHER THAN MOUNTED TO WALLS AND FLOORS. 7. TABLE 4.4, ITEM 2, D, RIGID STEEL IMC CONDUIT < 1-1/2 INCHES IN DIAMETER, AND EMT OR ALUMINUM CONDUIT < 2 INCHES IN DIAMETER. 8. TYPICAL SEISMIC DETAILS ARE PROVIDED ON THE DRAWINGS FOR REFERENCE ONLY. SHOP DRAWINGS ARE REQUIRED. 9. CONTRACTOR SHALL PROVIDE SHOP DRAWINGS TO THE ENGINEER OF RECORD FOR REVIEW AND APPROVAL PRIOR TO SUBMITTAL TO THE PLAN REVIEWER. 10. ELECTRICAL EQUIPMENT AND COMPONENTS IN SEISMIC DESIGN CATEGORY 'C' WITH Ip = 1.0 ARE EXEMPT FROM SEISMIC RESTRAINTS PER ASCE-7,13.1.4. SEISMIC RESTRAINTS FOR ELECTRICAL SYSTEM COMPONENTS (EARTHQUAKE LOAD RESISTANCE) SEISMIC DESIGN CATEGORY ( D ) SEISMIC USE GROUP ( II ) COMMENTS SEPARATE PERMIT & PLANS SHOP DRAWINGS SUBSEQUENT SUBMITTAL LOCATION OF PROFESSIONALLY SEALED ANCHORAGE AND SWAY BRACING DETAILS DRAWING NO. OR SPEC. SECTION ON CONST. DOCUMENTS SWAY BRACING PROVIDED NOT PROVIDED PROVIDED NOT PROVIDED ANCHORAGE TO FLOORS, ROOFS, ETC. LISTING OF EQUIPMENT & SYSTEM COMPONENTS FIRE ALARM WIRING PANEL BOARD LIGHTING FIXTURES CONDUIT AND WIRING SHOP DRAWINGS NEED TO BE SUBMITTED TO THE COUNTY A MINIMUM OF TWO WEEKS PRIOR TO THE PLANNED INSTALLATION TO ALLOW FOR PLAN REVIEW AND DISTRIBUTION TO THE INSPECTOR. ADDITIONAL TIME MAY BE NEEDED IF SUCH SUBMISSIONS ARE DEFICIENT. IT IS THE BASIC INTENET OF THIS CODE BLOCK TO DECLARE WHETHER OR NOT ANCHORAGE AND SWAY BRACING IS REQUIRED ON THE PROJECT. IF SO, TO DECLARE WHETHER OR NOT THE DETAILS ARE SHOWN ON THE PLANS OR WILL BE SHOWN ON A SUBSEQUENT SUBMISSION. IF SEISMIC RESTRAINT OF A COMPONENT IS NOT REQUIRED BY CODE THIS SHOULD BE STATED IN COMMENTS. IF SEISMIC RESTRAINT, WHICH IS NOT REQUIRED BY CODE, IS BEING PROVIDED DUE TO OWNER/DESIGNER REQUIREMENTS THIS SHOULD ALSO BE STATED IN THE COMMENTS. OTHER GENERAL EQUIPMENT & SYSTEM COMPONENTS; OTHER EQUIPMENT & SYSTEM COMPONENTS NEEDED FOR CONTINUED OPERATION OF SEISMIC USE GROUP III FACILITIES OR WHOSE FAILURE COULD IMPAIR THEIR CONTINUED OPERATION; EMERGENCY OR STANDBY EQUIPMENT & SYSTEM COMPONENTS; FIRE PROTECTION, DETECTION & ALARM EQUIPMENT & SYSTEM COMPONENTS; N/A, NO SEISMIC USE GROUP III OR IV IN THE PROJECT N/A, NO EMERGENCY OR STANBY EQUIPMENT IN THE PROJECT 5 EMERGENCY LIGHTING FIXTURES EXIT SIGNS X X X X 1,2,8,9 1 X X TS PC LC T F M M M IC AA3 BB2 C1 D1 LIGHT POLE WITH MULTIPLE HEADS (AS INDICATED). LIGHT POLE WITH SINGLE HEAD LUMINAIRE. SHADING DENOTES EMERGENCY FIXTURE. FACE; WITH DIRECTIONAL ARROW(S) AS INDICATED. FIXTURE TYPE "X" (U.N.O.). EMERGENCY LIGHT - BATTERY OPERATED - WALL MOUNTED 84" AFF (U.N.O.). FIXTURE TYPE "Y" (U.N.O.). EXIT LIGHT - CEILING MOUNTED; WALL MOUNT 7'-6" AFF OR ABOVE DOOR SHADED PORTION INDICATES WALL MOUNTED FIXTURE - AS ABOVE - MOUNTING HEIGHT AS PER PLANS. LUMINAIRE - AS ABOVE - WALL MOUNTED 84" AFF (U.N.O). LIGHTING FIXTURES FIXTURE CIRCUITRY NOTATION: FOUR-WAY SWITCH - AS ABOVE. THREE-WAY SWITCH - AS ABOVE. TIME SWITCH - MOUNT 60" AFF. DIMMER SWITCH - AS ABOVE, 1000 WATT RATING OR 0-10V AS REQUIRED. MOUNT 46" A.F.F. SWITCH WITH PILOT LIGHT - AS ABOVE. SINGLE POLE SWITCH - "a" INDICATES SWITCH LEG - MOUNT 46" AFF. DOUBLE POLE WALL SWITCH - AS ABOVE. NL - NIGHT LIGHT (UNSWITCHED CIRCUIT) a,b - LETTER(S) OF SWITCH(ES) CONTROLLING FIXTURE 1 - CIRCUIT NUMBER TO WHICH FIXTURE IS CONNECTED WIRING DEVICES KEY OPERATED SWITCH - AS ABOVE. CEILING MOUNTED DUPLEX RECEPTACLE, FLUSH IN CEILING (U.N.O.). FLOOR MOUNTED DUPLEX RECEPTACLE WITH BRASS PLATE AND CARPET FLANGE. DUPLEX 8" ABOVE COUNTER OR WALL HUNG LAVATORY. SWITCH AMPS/FUSE AMPS/POLES. DISCONNECT SWITCH (FUSED OR NON-FUSED AS INDICATED) - MOUNT 60" AFF. 30/20/3 INDICATES DUPLEX RECEPTACLE AS ABOVE - SPLIT WIRED, TOP HALF SWITCHED. MOTORS AND EQUIPMENT DUPLEX RECEPTACLE - MOUNT 18" AFF. SINGLE CONVENIENCE RECEPTACLE - AS ABOVE. DRY-TYPE TRANSFORMER. ELECTRIC MOTOR. HEAT DETECTOR - CEILING MOUNTED (U.N.O.). NEW BRANCH CIRCUIT PANELBOARD - MOUNT TOP 78" AFF. NL 1a,b 3 2 a 4 K P 30/20/3 FIRE ALARM MAGNETIC DOOR HOLDER. EXTERIOR FA BELL - MOUNT 90" AFF. FIRE ALARM CONTROL PANEL - MOUNT TOP 72" AFF. SPRINKLER PRESSURE SWITCH (FURNISHED BY FPC). SPRINKLER FLOW SWITCH (FURNISHED BY FPC). SPRINKLER TAMPER SWITCH (FURNISHED BY FPC). HORN OR SPEAKER - MOUNT 80" AFF; V DENOTES COMBINATION AUDIBLE/VISUAL APPLIANCE. MANUAL PULL STATION - MOUNT 46" AFF. 15 FACP FAAP ELECTRICAL SYMBOLS LEGEND SMOKE DETECTOR - CEILING MOUNTED. DUCT MOUNTED SMOKE DETECTOR WITH SAMPLING TUBES. SEE LIGHTING FIXTURE SCHEDULE FOR DESCRIPTION. LUMINAIRE - CEILING MOUNTED. ALPHA-NUMERIC DESIGNATION DENOTES TYPE; TO HEIGHT INDICATED. LED,FLUORESCENT OR H.I.D. FIXTURE - AS ABOVE - CEILING MOUNTED OR PENDANT MOUNTED COMBINATION EXIT LIGHT WITH EMERGENCY LIGHTING HEADS. FIXTURE TYPE "X1" (U.N.O.). M PHOTOCELL MOUNTED IN WP OUTLET BOX LOCATED ON ROOF, FACING NORTH, (U.N.O.). LIGHTING CONTACTOR FOR NUMBER OF CIRCUITS AS INDICATED ON PLAN. JUNCTION BOX OR POINT OF CONNECTION - MOUNT 18" AFF OR AT HEIGHT REQUIRED BY RESPECTIVE EQUIPMENT ITEM MANUFACTURER. DOUBLE DUPLEX RECEPTACLE - AS ABOVE. SPECIAL PURPOSE OUTLET - MOUNT 18" AFF. TYPE AS REQUIRED BY RESPECTIVE EQUIPMENT MFR. KILOWATT HOUR METER BASE. FIRE ALARM SYSTEM FIRE ALARM ANNUNCIATOR PANEL - MOUNT TOP 72" AFF. (U.N.O.). DUCT MOUNTED SMOKE DETECTOR'S REMOTE ANNUNCIATOR LAMP AND TEST SWITCH-MOUNT ON CEILING, A VISUAL FLASHER - MOUNT 80" AFF TO BOTTOM OF FLASHER; (NUMERALS INDICATE CANDELA). V DH R INTERFACE RELAY FOR CODE REQUIRED ACTION, OR AS NOTED ON PLANS; SEE SPECIFICATION. CM MM CONTROL MODULE FOR CODE REQUIRED ACTION; SEE SPECIFICATION. MONITOR MODULE FOR CODE REQUIRED ACTION, OR AS NOTED ON PLANS; SEE SPECIFICATION. EXISTING BRANCH CIRCUIT PANELBOARD. MANUAL MOTOR STARTER WITH OVERLOAD PROTECTION - MOUNT ON SIDE OF UNIT OR AT 46" AFF. OCCUPANCY SENSOR, CEILING MOUNTED, "2" INDICATES 2 POLE. DOUBLE DUPLEX RECEPTACLE 8" ABOVE COUNTER 30 ARC FAULT CIRCUIT INTERRUPTER TYPE DEVICE, (U.N.O.) AFI/AFCI TYPICAL TYP TCC TEMPERATURE CONTROL CONTRACTOR TIME CLOCK EWC NF ELECTRIC WATER COOLER; ROUGH-IN RECEPTACLE INCONSPICUOUSLY; COORDINATE WITH PC WP WEATHERPROOF U.N.O. UNLESS NOTED OTHERWISE PC PLUMBING CONTRACTOR NON-FUSED SWITCH MIN MINIMUM MFR MANUFACTURER MC MECHANICAL CONTRACTOR MAX MAXIMUM HINGED DOOR WITH KEY LOCK. TELEPHONE TERMINAL CABINET 24" x 36" x 6" (U.N.O.) WITH FIRE RETARDANT PLYWOOD BACK AND TTC COMBINATION VOICE & DATA OUTLET - 8" ABOVE COUNTER. FLOOR MOUNTED DATA OUTLET. DATA OUTLET - 8" ABOVE COUNTER. VOICE OUTLET - MOUNT 18" AFF; W INDICATES WALL MOUNT 46" AFF, MICROPHONE OUTLET - CEILING MOUNTED FOR CORD HUNG DEVICE. DUPLEX MICROPHONE OUTLET - FLOOR MOUNTED. SPEAKER - WALL MOUNT 84" AFF. FSS GC GFI/GFCI EWH FLA EX EM AFF EC TTB FULL LOAD AMPS FUSIBLE SAFETY SWITCH GROUND FAULT CIRCUIT INTERRUPTER TYPE DEVICE, (U.N.O.) EXISTING GENERAL CONTRACTOR ELECTRIC WATER HEATER INTERCOM STATION - MOUNT 46" AFF. TELEPHONE TERMINAL BOARD - 3/4" FIRE RETARDANT PLYWOOD, 4' x 8' (U.N.O.). PUSHBUTTON - MOUNT 46" AFF. ABBREVIATIONS ABOVE FINISHED FLOOR. ELECTRICAL CONTRACTOR COMBINATION VOICE & DATA OUTLET - MOUNT 18" AFF. T.V. OUTLET - MOUNT 18" AFF U.N.O. EMERGENCY DUPLEX MICROPHONE OUTLET - MOUNT 18" AFF. VOLUME CONTROL - MOUNT 46" AFF. BELL - MOUNT 84" AFF. DATA OUTLET - MOUNT 18" AFF. AUXILIARY SYSTEMS SPEAKER - CEILING MOUNTED. FAN CONTROL SWITCH. FC DACT DIGITAL ALARM COMMUNICATOR TRANSMITTER RT RAINTIGHT OCCUPANCY SENSOR WALL MOUNTED, MOUNT 46" AFF. "2" INDICATES DUAL RELAY. OS D T WALL BOX TIMER SWITCH. ABOVE COUNTER AC AMP INTERRUPTING CURRENT AIC AFC AVAILABLE FAULT CURRENT ATS AUTOMATIC TRANSFER SWITCH CABLE TELEVISION CATV MOUNTING HEIGHT MH NTS NOT TO SCALE UNINTERRUPTABLE POWER SUPPLY UPS FPC FIRE PROTECTION CONTRACTOR FIRE ALARM POWER SUPPLY - MOUNTED 72" A.F.F. FAPS (NUMERALS INDICATE CANDELA). COMBINATION POWER & DATA/VOICE FLOOR BOX OR POKE THRU - "FF" INDICATES FURNITURE FEED. WIRELESS ACCESS POINT - CEILING MOUNTED, U.N.O. FLOOR MOUNTED COMBINATION VOICE & DATA OUTLET. OS J F SD SD F H F F F F F F T F P S S V TC TV MD C CR RQE ES EH ML GB INTRUSION ALARM SYSTEM INTRUSION ALARM PANEL IAP KEY PAD MOTION DETECTOR DOOR CONTACT K REQUEST TO EXIT CARD READER/PROX READER ELECTRIC STRIKE (FURNISHED BY DIVISION 8) ELECTRIFIED HARDWARE (FURNISHED BY DIVISION 8) MAGNETIC LOCK (FURNISHED BY DIVISION 8) GLASS BREAK SENSOR VIDEO SURVEILLANCE CAMERA DURESS/HOLD UP ALARM A CIRCUITRY UP - CIRCUITRY DOWN. BRANCH CIRCUITRY AS ABOVE, EXPOSED ON WALLS OR STRUCTURE. BRANCH CIRCUITRY AS ABOVE, CONCEALED IN FLOOR SLAB OR UNDERGROUND. BRANCH CIRCUITRY. CONCEALED IN WALLS OR ABOVE CEILINGS. ARROW INDICATES HOME RUN TO PANEL. SHORT SLASH MARKS INDICATE "HOT" WIRES, LONG SLASH MARK INDICATES "NEUTRAL" WIRE, LONG SLASH WITH SOLID CIRCLE INDICATES GREEN GROUNDING CONDUCTOR. CIRCUITRY DESIGNATIONS MECHANICAL EQUIPMENT ITEM IDENTIFICATION PER EQUIPMENT SCHEDULE ON MECHANICAL DRAWINGS. X-X XXX MISCELLANEOUS SSC JOB# 2016123_BID SET - NOT FOR CONSTRUCTION The Seal and Signature apply only to the Document to which they are Affixed, and Expressly Disclaim any Responsibility for all other Plans, Specifications, Estimates, Reports, or other Documents or Instruments relating to or intended to be used for any part or parts of the Architectural or Engineering Project. Copyright © 2016 by SSC Engineering, Inc. MISSOURI 5017 Washington Place Suite 200 St. Louis, M0 63108 314.361.0000 ph 314.361.9191 fax Copyright 2016 HKW Architects IOWA 1000 Melrose Avenue Iowa City, IA 52246 319.343.7055 ph hkwarchitects.com 18207 Edison Avenue Chesterfield, M0 63005 636.530.7770 ph 636.530.7877 fax PNC Bank Bid Set E0.1 PNC Valley Park 16.008.00 April 11, 2016 ELECTRICAL SYMBOLS, ABBREVIATIONS & GENERAL NOTES 912 Meramec Station Road, Valley Park, MO 63021 GENERAL CONSTRUCTION NOTES: 1. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR NECESSARY PERMITS, LICENSES, INSPECTIONS AND FEES FROM THE LOCAL AUTHORITIES. CONTRACTOR SHALL BE LICENSED BY LOCAL AND/OR STATE AUTHORITIES HAVING JURISDICTION.. 2. ALL MATERIAL AND WORKMANSHIP SHALL CONFORM TO THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), NATIONAL ELECTRICAL CODE (NEC), INTERNATIONAL BUILDING CODE (IBC) AND OTHER APPLICABLE LOCAL, STATE AND NATIONAL CODES. 3. ALL ELECTRICAL MATERIAL USED ON THIS PROJECT SHALL BE "UL" LISTED AND LABELED. 4. THE ENTIRE ELECTRICAL SYSTEM AND ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED IN STRICT ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND AS SHOWN ON THE DRAWINGS. PROVIDE A GROUND WIRE IN EACH POWER CONDUIT, SIZED PER THE NEC. 5. CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING A COMPLETE SYSTEM PER CONTRACT DRAWINGS AND ENSURING THAT THE SYSTEM IS OPERATIONAL UPON JOB COMPLETION. 6. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WITH ALL OTHER TRADES AND DISCIPLINES TO AVOID CONFLICTS AND TO VERIFY ALL EQUIPMENT CONNECTIONS. COORDINATE ALL WIRING DEVICE LOCATIONS AND ELEVATIONS INDICATED ON THE PLANS WITH THE OWNER, ARCHITECT AND FINAL FURNITURE/EQUIPMENT LAYOUTS. 7. CONTRACTOR SHALL GUARANTEE ALL LABOR AND MATERIAL INSTALLED OR FURNISHED UNDER THIS CONTRACT FOR A PERIOD OF NOT LESS THAN ONE YEAR AFTER FINAL ACCEPTANCE OF THE BUILDING. 8. MAINTAIN AND VERIFY ELECTRICAL EQUIPMENT CLEARANCES AND WORKING SPACE PER NEC. 9. PROVIDE ELECTRICAL SYSTEMS IDENTIFICATION AS INDICATED IN THE SPECIFICATIONS AND REQUIRED BY THE NEC OR NFPA 70E. 10. IF ANYTHING ON THE PLANS IS NOT IN COMPLIANCE WITH NATIONAL, STATE OR LOCAL CODES, THE ENGINEER SHALL BE ADVISED BY THE ELECTRICAL CONTRACTOR DURING THE BIDDING PROCESS. THERE ARE TO BE NO CHANGES TO THE CONTRACT DOCUMENTS WITHOUT WRITTEN PERMISSION FROM THE ENGINEER. 11. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL MEANS AND METHODS FOR NEW WORK, SAFETY, ETC., IN ACCORDANCE WITH ALL AUTHORITIES HAVING JURISDICTION. (I.E. OSHA, NEC, ETC.) 12. THE CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR PHASING AND SCHEDULING OF THIS PROJECT. COORDINATE WITH OWNER'S FIELD REPRESENTATIVE. 13. VERIFY ALL INDICATED DIMENSIONS BY FIELD MEASUREMENTS. NOTIFY ENGINEER OF ANY DISCREPANCIES. 14. PROVIDE ACCESS PANELS OR DOORS WHERE EQUIPMENT OR DEVICES REQUIRED TO BE ACCESSIBLE ARE CONCEALED BEHIND INACCESSIBLE SURFACES. 15. PRIOR TO TURNOVER, THIS CONTRACTOR SHALL REMOVE ALL RUBBISH, DIRT, DEBRIS AND STAINS ON THEIR WORK OR CAUSED BY THEIR WORK AND SHALL THOROUGHLY CLEAN ALL EQUIPMENT, FIXTURES, DEVICES, ETC. CONTRACTOR SHALL REPLACE, TOUCH-UP OR REFINISH THE FACTORY FINISH ON EQUIPMENT, FIXTURES, DEVICES, ETC. MARRED DURING SHIPMENT, INSTALLATION OR CONSTRUCTION. 16. PANELBOARD CIRCUIT BREAKERS SHALL BE EQUIPPED WITH BOLT-ON TYPE BREAKERS, PHENOLIC NAME TAGS AND KEYED LOCK AND LATCH. EACH PANEL SHALL BE PROVIDED WITH TWO KEYS WITH ALL PANELS KEYED ALIKE. ALL CIRCUIT BREAKERS USED TO SWITCH LIGHT FIXTURES SHALL BE TYPE SWD SHALL BE APPROVED FOR THE PURPOSE. ALL CIRCUIT BREAKERS SERVING HVAC EQUIPMENT SHALL BE HACR TYPE. 17. ALL CIRCUITS INDICATED ON THESE DRAWINGS ARE 20A, 1P CIRCUIT BREAKERS IN PANELS UNLESS NOTED OTHERWISE. 18. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER IDENTIFICATION AND LABELING OF ALL CIRCUIT BREAKERS. EACH PANELBOARD SHALL BE EQUIPPED WITH A TYPE WRITTEN CIRCUIT DIRECTORY. ALL EXISTING PANELBOARDS THAT HAVE CIRCUITS ALTERED SHALL HAVE A NEW TYPE WRITTEN CIRCUIT DIRECTORY SHOWING CIRCUIT REVISIONS AND EXISTING CIRCUIT CONDITIONS ON THE NEW DIRECTORY. 19. MINIMUM WIRE SIZE SHALL BE #12 AWG UNLESS OTHERWISE NOTED. MINIMUM CONDUIT SIZE SHALL BE 1/2" UNLESS OTHERWISE NOTED. ALL CONDUIT IN SLABS OR EXTERIOR TO BUILDING SHALL BE MINIMUM 1". PROVIDE A NYLON/POLY PULL CORD IN ALL EMPTY CONDUITS. 20. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL COPPER CONDUCTORS TYPE THHN OR THWN FOR ALL INTERIOR BUILDING WIRE. FOR EXTERIOR FEEDERS AND BRANCH CIRCUITS PROVIDE ALL COPPER CONDUCTORS TYPE XHHW-2. 21. VOLTAGE DROP MINIMUM WIRE SIZING (20A CIRCUIT) USE: 120V CIRCUIT OVER 100' SHALL BE #10 MINIMUM; 120V CIRCUIT OVER 175' SHALL BE #8 MINIMUM; 208V CIRCUIT OVER 200' SHALL BE #10 MINIMUM; 277V CIRCUIT OVER 200' SHALL BE #10 MINIMUM. MINIMUM WIRE SIZE FOR ANY 20A BRANCH CIRCUIT SHALL BE #12. FURTHERMORE, CONSIDER ALL DERATING OF CONDUCTORS AS REQUIRED IN ACCORDANCE WITH THE APPLICABLE NEC. 22. ELECTRICAL CONTRACTOR SHALL HAVE THE OPTION OF GROUPING HOME RUNS IN ONE CONDUIT, PER THE REQUIREMENTS OF SECTION 310 OF THE NATIONAL ELECTRICAL CODE. NO MORE THAN FOUR (4) CIRCUITS SHALL BE ALLOWED TO BE GROUPED AND INSTALLED IN A SINGLE JUNCTION BOX. EC SHALL BE RESPONSIBLE FOR INCREASING CONDUCTOR SIZE AND DERATING. HOME RUNS WITH MORE THAN THREE CIRCUITS SHALL BE #10 AWG. CONDUCTOR MINIMUM. PROVIDE DEDICATED NEUTRALS FOR EACH PHASE CONDUCTOR AND CONSIDER THEM AS A CURRENT CARRYING CONDUCTOR FOR DERATING. 23. ALL HOME RUNS SHALL BE IN EMT CONDUIT. MC CABLE IS PERMITTED ABOVE CEILINGS FROM HOMERUNS TO FIXTURES AND WIRING DEVICES WITHIN WALLS AND FURRED COLUMNS. REFER TO ELECTRICAL SPECIFICATIONS FOR MORE DETAILED INFORMATION. 24. ONLY PVC CONDUIT SHALL BE PERMITTED IN CONCRETE SLAB, EXCEPT FOR GRS ELLS. 25. WHEN SAW CUTTING FLOOR IS REQUIRED, CONTRACTOR SHALL LIMIT DEPTH TO A MINIMUM. ROUTE NEW CONDUITS BELOW OR ABOVE EXISTING CONDUITS, WATER PIPES, ETC. CONDUIT SHALL HAVE A MINIMUM OF 1'' OF CONCRETE COVER. CONTRACTOR SHALL XRAY FLOOR SLAB PRIOR TO ANY SAW CUTTING. 26. ELECTRICAL CONTRACTOR SHALL ARRANGE WITH THE ELECTRIC, CATV AND TELEPHONE UTILITY COMPANIES FOR INCOMING SERVICE REQUIREMENTS FROM LANDLORD DEMARC AND INCLUDE ALL COSTS IN BASE BID. 27. HEATING, VENTILATING, AIR CONDITIONING EQUIPMENT AND PLUMBING EQUIPMENT ALONG WITH ALL OTHER MISCELLANEOUS EQUIPMENT, MOTORS, AND KITCHEN EQUIPMENT SHALL BE POWERED AS CALLED OUT ON EQUIPMENT PROVIDER'S SCHEDULES UNLESS OTHERWISE NOTED. EC SHALL PROVIDE DISCONNECTING MEANS UNLESS SPECIFICALLY NOTED ON EQUIPMENT PROVIDER'S SCHEDULE. 28. SUPPORT ALL CONDUITS FROM STRUCTURAL WALLS, SLABS, MEMBERS AND ROOF JOISTS. DO NOT SUPPORT CONDUITS FROM CEILING TIE WIRES, DUCTWORK, PIPING, ROOF DECK OR OTHER NON-STRUCTURAL MEMBERS. 29. SUPPORTING OF ELECTRICAL CONDUITS: THE INDIVIDUAL BRANCH CIRCUIT CONDUIT AND ASSOCIATED 4'' X 4'' JUNCTION BOXES MAY BE SUPPORTED FROM FLOOR/ROOF JOISTS. ALL LARGER FEEDER CONDUITS AND/OR CLUSTER OR GROUPS OF BRANCH CIRCUIT CONDUITS SHALL BE SUPPORTED ON STEEL TRAPEZE WITH STEEL CHANNEL ATTACHED TO STEEL OR WOOD JOIST/BEAMS WITH PROPER ATTACHMENTS. NO SUPPORT SHALL BE ATTACHED TO THE ROOF DECK (NO EXCEPTIONS) . HANG CONDUIT FROM TOP CHORD OF BAR JOIST WHEN ATTACHING HOME RUNS TO JOIST. 30. INTERIOR AND EXTERIOR LIGHT FIXTURES SHALL BE FURNISHED AND INSTALLED AS SHOWN ON THE DRAWINGS AND AS CALLED OUT IN THE LIGHTING FIXTURE SCHEDULE. 31. ALL WIRING DEVICES SHALL BE FLUSH MOUNTED, UNLESS NOTED OTHERWISE. ALL CONDUIT SHALL BE RUN WITHIN WALL CAVITIES, BELOW FLOOR AND ABOVE CEILINGS. SURFACE MOUNTED ELECTRICAL WORK SHALL NOT BE USED UNLESS SPECIFICALLY NOTED ON THE PLANS. 32. ALL WALL AND CEILING FIXTURES AND DEVICES SHALL BE INDEPENDENTLY AND SECURELY MOUNTED SO THEY ARE NOT DEPENDENT ON CEILING FINISH FOR SUPPORT AND CAN NOT BE ROTATED OR DISPLACED. FIXTURES AND DEVICES MOUNTED IN SUSPENDED ACOUSTICAL CEILING TILE SHALL HAVE CHANNEL SUPPORTS ACROSS THE MAIN GRID RUNNERS OR GRID SUPPORTS SECURELY ANCHORED SO AS NOT TO CAUSE TILE TO SAG OR SO FIXTURE OR DEVICE CAN NOT BE LIFTED, ROTATED OR DISPLACED. 33. ELECTRICAL LIGHT FIXTURES, MECHANICAL AIR DEVICES, FIRE SPRINKLERS, AND SMOKE DETECTORS IN CEILING: ALL SUBS NEED TO TAKE OTHER DISCIPLINES INTO CONSIDERATION BEFORE STARTING THEIR WORK. ALL ITEMS THAT NEED TO BE MOVED WILL BE MOVED AT THE SUB'S EXPENSE. FIRE SPRINKLERS MUST BE LOCATED A MINIMUM OF 30 INCHES FROM ANY SURFACE MOUNTED LIGHT. SMOKE DETECTORS MUST BE MOUNTED NO CLOSER THAN 3 FEET OF AN AIR DEVICE OR CEILING FAN. FIRE SPRINKLERS, LIGHT FIXTURES, SMOKE DETECTORS, AND AIR DEVICES ALL TO BE CENTERED DOWN THE HALLWAYS. ELECTRICAL, MECHANICAL, FIRE SPRINKLER, AND LOW VOLTAGE SUB CONTRACTOR MUST MEET AND DECIDE BEFORE ANYONE STARTS, WHERE LOCATION OF THESE ITEMS WILL BE LOCATED. IF ITEM NEEDS TO BE MOVED, IT WILL BE AT THE EXPENSE OF THE SUB CONTRACTOR. COORDINATE WITH ARCHITECT'S REFLECTED CEILING PLAN. 34. ALL OPENINGS IN FIRE AND/OR SMOKE RATED WALLS, FLOORS, AND PARTITIONS FOR CONDUITS SHALL BE SEALED WITH RED FIRE RESISTANT FOAM OR PUTTY TO MAINTAIN THE FIRE AND/OR SMOKE RATING. ALL OPENINGS IN FIRE RATED AND/OR SMOKE WALLS, FLOORS, AND PARTITIONS FOR CABLING SHALL BE SEALED WITH WIREMOLD FLAMESTOPPER, STI EZ-PATH, HILTI SPEED SLEEVE OR EQUIVALENT. 35. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF LIGHT FIXTURES, DIMENSIONAL LOCATION OF FIXTURES IN DRYWALL CEILING, ETC. LOCATION OF FLOOR BOXES AND RECEPTACLES, INCLUDING MOUNTING HEIGHTS. ALL RECEPTACLES AND COVER PLATE COLORS SHALL BE APPROVED BY ARCHITECT 36. OWNER RESERVES THE RIGHT TO RELOCATE ANY LIGHT FIXTURE, RECEPTACLE, ETC., BEFORE BEING INSTALLED 10'-0'' FROM LOCATION AS SHOWN ON PLANS AT NO ADDITIONAL EXPENSE TO THE OWNER. 37. OUTLETS IN OFFICES SHALL HAVE THEIR WALL LOCATIONS COORDINATED WITH FINAL FURNITURE LAYOUT. GROUP POWER AND COMMUNICATION OUTLETS SIDE BY SIDE AT SAME HEIGHT. 38. NO CONDUIT OR CABLES SHALL BE INSTALLED EXPOSED IN FINISHED AREA. NON-CEILING AREA CONDUITS SHALL BE INSTALLED EXPOSED IN A NEAT WORKMAN LIKE MANNER AND BE PAINTED TO MATCH ADJACENT FINISHES. 39. ALL MATERIALS, DEVICES, FIXTURES, ETC., THAT ARE REQUIRED FOR THIS PROJECT ARE TO BE FURNISHED AND INSTALLED BY THE EC, UNLESS SPECIFICALLY INDICATED TO BE FURNISHED AND OR INSTALLED BY OTHERS. 40. TELEPHONE, IT, AUDIO, VIDEO AND SECURITY CABLE WIRING WILL BE PROVIDED BY OWNERS VENDOR. EC SHALL COORDINATE AND PROVIDE ALL ROUGH-IN'S AS REQUIRED. LOW VOLTAGE DEVICES HAVE BEEN SHOWN ON THE PLANS FOR REFERENCE PURPOSES ONLY. ALL LOW VOLTAGE CABLING SHALL BE ROUTED IN CONDUIT FROM DEVICE/JUNCTION BOX TO ABOVE AN ACCESSIBLE CEILING OR IN ATTIC SPACE; 1" EMT MINIMUM. EC SHALL PROVIDE J-HOOKS AS REQUIRED, NO MORE THAN 60" O.C. 41. ALL SIGNAL AND CONTROL CABLES SHALL BE MINIMUM #18 STRANDED COPPER, UNLESS NOTED OTHERWISE. ALL CONNECTIONS AND SPLICES TO BE MADE BY USE OF ''STA-KON'' CONNECTORS AND TERMINAL STRIPS. 42. TYPICAL SEISMIC DETAILS ARE PROVIDED ON THE DRAWINGS FOR REFERENCE ONLY. CONTRACTOR SHALL PROVIDE SHOP DRAWINGS TO THE OWNER'S ENGINEER FOR REVIEW AND APPROVAL PRIOR TO SUBMITTAL TO THE PLAN REVIEWER. SHOP DRAWINGS SHALL SHOW ALL EQUIPMENT ANCHORAGE TO WALLS/CEILINGS/FLOORS AND SHALL INCLUDE SIZE OF SEISMIC ANCHOR BOLTS USED FOR EACH SYSTEM. CONTRACTOR SHALL PROVIDE CALCULATIONS, DETAILS, ETC. - PREPARED BY, SIGNED AND SEALED BY A LICENSED STRUCTURAL ENGINEER. REFER TO SPECIFICATIONS. GENERAL DEMOLITION NOTES: 1. THE OWNER INTENDS TO VACATE SPECIFIC AREAS OF WORK BEFORE DEMOLITION BEGINS. ALL OTHER AREAS SHALL REMAIN OCCUPIED AND IN ACTIVE USE. UTILITIES AND SERVICES TO EXISTING ACTIVE AREAS SHALL NOT BE INTERRUPTED WITHOUT THE OWNER'S APPROVAL AS TO THE TIME AND DURATION. THE OWNER WILL CONTINUE TO OCCUPY THE REST OF THE EXISTING FACILITIES THROUGHOUT THE CONSTRUCTION OPERATIONS. THE ELECTRICAL CONTRACTOR SHALL SO ORGANIZE HIS WORK AS TO CAUSE A MINIMUM OF UTILITY INTERRUPTIONS, WHICH SHALL BE SCHEDULED AT THE CONVENIENCE OF THE OWNER. 2. ALL ELECTRICAL EQUIPMENT, LIGHTING FIXTURES, SWITCHES, RECEPTACLES, SPECIAL OUTLETS, ETC., WHICH ARE NOTED TO BE DEMOLISHED, OR ARE SHOWN WITH DASHED LINE SYMBOLS ON THE DEMOLITION PLANS, SHALL BE REMOVED. ASSOCIATED WIRING AND CONDUIT SHALL BE REMOVED BACK TO THE SOURCE OR EXISTING UPSTREAM DEVICE TO REMAIN AND MADE SAFE. 3. REMOVE EQUIPMENT, FIXTURES, DEVICES AND OUTLETS AS SPECIFIED AND SHOWN ON DRAWINGS, AND AS MAY BECOME NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS. EXAMINE ALL EXISTING WALLS AND CEILING DESIGNATED FOR REMOVAL TO DETERMINE THE CONDUIT AND WIRING THAT WILL REQUIRE REMOVAL. 4. FOR EXISTING ELECTRICAL DEVICES IN WALLS TO BE REMOVED, DISCONNECT POWER, REMOVE CONDUCTORS AND CAP CONDUIT BELOW FLOOR OR ABOVE CEILING AS REQUIRED. DEVICES ARE TO BE REMOVED ALONG WITH WALL BY GENERAL CONTRACTOR. 5. FOR EXISTING ELECTRICAL EQUIPMENT, FIXTURES AND DEVICES TO BE REMOVED FROM WALLS WHICH REMAIN, DISCONNECT POWER, REMOVE CONDUCTORS, REMOVE THE ELECTRICAL ITEM, AND PATCH AND FINISH THE SURFACE AS REQUIRED TO MATCH THE EXISTING, OR MAKE READY FOR NEW WALL FINISH. PROVIDE BLANK PLATES WHERE NOTED OR REQUIRED. 6. EXISTING RECEPTACLES, DEVICES, ETC. TO REMAIN ARE DENOTED BY THIN SOLID LINE OR MAY NOT BE INDICATED AT ALL. THESE DEVICES SHALL BE EXTENDED TO BE FLUSH WITH NEW FINISH ON EXISTING WALL WHERE REQUIRED. 7. MAINTAIN CIRCUIT CONTINUITY TO ALL EQUIPMENT, FIXTURES, DEVICES, ETC., TO REMAIN IN USE WHETHER NOTED ON THE PLANS OR NOT. FIELD VERIFY EXISTING ITEMS TO REMAIN IN USE. WIRING FOR EXISTING CIRCUITS WHICH ARE PARTIALLY ABANDONED SHALL BE RECONNECTED BY THE ELECTRICAL CONTRACTOR TO SERVICE THE REMAINING OUTLETS ON THE CIRCUIT. 8. ALL WIRING FOR A CIRCUIT WHICH IS TO BE REMOVED SHALL BE REMOVED BACK TO THE PANEL WHICH SUPPLIED THE CIRCUIT. 9. EXISTING CONDUIT & CONDUCTORS MAY BE REUSED WHERE FEASIBLE. ALL UNUSED CONDUIT MADE EMPTY BY THIS DEMOLITION SHALL BE REMOVED BY THE ELECTRICAL CONTRACTOR. WHERE CONDUITS EXTENDING OUT OF THE FLOOR ARE TO BE REMOVED, CUT THE CONDUIT OFF 1/2" BELOW THE FLOOR LINE AND PATCH. 10. ALL ACTIVE CIRCUITING THAT RUNS THROUGH THIS SPACE, ORIGINATING AND/OR TERMINATING IN OTHER SPACES, SHALL REMAIN IN PLACE. COORDINATE WITH NEW CEILING WORK FOR RAISED CEILING WHICH MAY REQUIRE CIRCUITING RELOCATION. 11. ALL UNUSED TELEPHONE AND DATA CABLES SHALL BE REMOVED. ANY OTHER UNUSED LOW VOLTAGE SYSTEMS CABLES SHALL ALSO BE REMOVED. 12. ALL EXISTING EQUIPMENT, LIGHTING FIXTURES, WIRING DEVICES, AND MATERIALS TO BE REMOVED SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE PREMISES AND PROPERLY DISPOSED OF IN ACCORDANCE WITH AUTHORITIES HAVING JURISDICTION, UNLESS OTHERWISE NOTED. ALL ITEMS NOTED THAT THE OWNER CHOOSES TO KEEP SHALL BE TRANSFERRED TO THEIR STORAGE AREA BY THE ELECTRICAL CONTRACTOR. 13. FOR ALL EXISTING ELECTRICAL WIRING DEVICES, TELEPHONE, DATA ETC., CONTRACTOR SHALL REMOVE/REINSTALL COVERPLATES AS REQUIRED TO ALLOW FOR NEW FINISHES. 14. INFORMATION ON THE EXISTING CONDITIONS PLANS ARE COMPILED FROM EXISTING DRAWINGS AND CASUAL FIELD OBSERVATIONS AND SHALL BE CONSIDERED APPROXIMATE ONLY. VERIFICATION OF ALL EQUIPMENT, WIRING DEVICES AND FIXTURES, EITHER SHOWN OR NOT SHOWN ON THESE PLANS, SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. NOTIFY ENGINEER IMMEDIATELY IF DISCREPANCIES EXIST. ELECTRICAL SHEET LIST Sheet Number Sheet Name E0.1 ELECTRICAL SYMBOLS, ABBREVIATIONS & GENERAL NOTES E0.2 ELECTRICAL PANEL SCHEDULES E0.3 ELECTRICAL DETAILS E1.1 ELECTRICAL LIGHTING PLAN E2.1 ELECTRICAL POWER & SYSTEMS PLAN ELECTRICAL ALTERNATE #1: PROVIDE AN ALTERNATE PRICE ADDER FOR THE FOLLOWING: - REPLACE EXISTING PANEL 102B WITH A NEW 60 POLE, 1 SECTION, 120/208V, 3 PHASE, 4 WIRE, 225A, 10KAIC, MLO PANELBOARD. - PROVIDE TEN (10) ADDITIONAL 20A/1 POLE CIRCUIT BREAKERS AS SPARES. - PROVIDE A 120/208V, 3 PHASE SURGE PROTECTIVE DEVICE AND AN ASSOCIATED 30A/3 POLE CIRCUIT BREAKER FOR THE SPD. - PROVIDE ALL ASSOCIATED INSTALLATION, LABOR AND COORDINATEION FOR THE ABOVE WORK. Revision Schedule No Date Description

ELECTRICAL SYMBOLS LEGEND - REiCON Constructors · 2016-04-12 · pnc bank bid set e0.1 pnc valley park 16.008.00 april 11, 2016 electrical symbols, abbreviations & general notes

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

Page 1: ELECTRICAL SYMBOLS LEGEND - REiCON Constructors · 2016-04-12 · pnc bank bid set e0.1 pnc valley park 16.008.00 april 11, 2016 electrical symbols, abbreviations & general notes

S

S

S

S

S

S

S

S

S

S

S

NO SCALE

SEISMIC RESTRAINTS FOR ELECTRICAL SYSTEM COMPONENTS

5,6,71,43,8,9

X

X

X

XXXX

X

1. LIGHT FIXTURES LESS THAN 20 POUNDS POWERED WITH FLEXIBLE CABLE LESS THAN 3 FEET, FIXTURE SHALL BE MECHANICALLY ATTATCHED TO CEILING GRID.

2. PENDANT TYPE FIXTURES DO NOT REQUIRE SWAY BRACING WHEN IT CAN SWING AT AN ANGLE OF 45° FROM VERTICAL WITHOUT IMPACTING OTHER COMPONENTS.3. TABLE 4.4, EXCEPTION FOR IP=1.0, WEIGHT LESS THAN 400 POUNDS.4. TABLE 4.4, EXCEPTION FOR IP=1.0, WEIGHT LESS THAN 20 POUNDS.

5. TABLE 4.4, EXCEPTION FOR IP=1.0, WEIGHT 5LBS/FT OR LESS.6. FLEXIBLE CONNECTION REQUIRED BETWEEN EQUIPMENT AND COMPONENTS IF INSTALLATION OTHER THAN MOUNTED TO WALLS AND FLOORS.7. TABLE 4.4, ITEM 2, D, RIGID STEEL IMC CONDUIT < 1-1/2 INCHES IN DIAMETER, AND EMT OR ALUMINUM CONDUIT < 2 INCHES IN DIAMETER.

8. TYPICAL SEISMIC DETAILS ARE PROVIDED ON THE DRAWINGS FOR REFERENCE ONLY. SHOP DRAWINGS ARE REQUIRED.9. CONTRACTOR SHALL PROVIDE SHOP DRAWINGS TO THE ENGINEER OF RECORD FOR REVIEW AND APPROVAL PRIOR TO SUBMITTAL TO THE PLAN REVIEWER.

10. ELECTRICAL EQUIPMENT AND COMPONENTS IN SEISMIC DESIGN CATEGORY 'C' WITH Ip = 1.0 ARE EXEMPT FROM SEISMIC RESTRAINTS PER ASCE-7,13.1.4.

SEISMIC RESTRAINTS FOR ELECTRICAL SYSTEM COMPONENTS (EARTHQUAKE LOAD RESISTANCE)

SEISMIC DESIGN CATEGORY ( D )SEISMIC USE GROUP ( II )

COMMENTS

SEPARATEPERMIT & PLANS

SHOP DRAWINGS

SUBSEQUENT SUBMITTAL

LOCATION OF PROFESSIONALLY SEALEDANCHORAGE AND SWAY BRACING DETAILS

DRAWING NO. ORSPEC. SECTION

ON CONST.DOCUMENTS

SWAY BRACING

PROVIDEDNOT

PROVIDEDPROVIDED

NOTPROVIDED

ANCHORAGE TOFLOORS, ROOFS, ETC.LISTING OF EQUIPMENT &

SYSTEM COMPONENTS

FIRE ALARM WIRING

PANEL BOARDLIGHTING FIXTURESCONDUIT AND WIRING

SHOP DRAWINGS NEED TO BE SUBMITTED TO THE COUNTY A MINIMUM OF TWO WEEKS PRIOR TO THE PLANNED INSTALLATION TO ALLOW FOR PLAN REVIEW AND DISTRIBUTION TO THE INSPECTOR. ADDITIONAL TIMEMAY BE NEEDED IF SUCH SUBMISSIONS ARE DEFICIENT.

IT IS THE BASIC INTENET OF THIS CODE BLOCK TO DECLARE WHETHER OR NOT ANCHORAGE AND SWAY BRACING IS REQUIRED ON THE PROJECT. IF SO, TO DECLARE WHETHER OR NOT THE DETAILS ARE SHOWN ON THEPLANS OR WILL BE SHOWN ON A SUBSEQUENT SUBMISSION. IF SEISMIC RESTRAINT OF A COMPONENT IS NOT REQUIRED BY CODE THIS SHOULD BE STATED IN COMMENTS. IF SEISMIC RESTRAINT, WHICH IS NOT REQUIREDBY CODE, IS BEING PROVIDED DUE TO OWNER/DESIGNER REQUIREMENTS THIS SHOULD ALSO BE STATED IN THE COMMENTS.

OTHER GENERAL EQUIPMENT & SYSTEMCOMPONENTS;

OTHER EQUIPMENT & SYSTEM COMPONENTSNEEDED FOR CONTINUED OPERATION OFSEISMIC USE GROUP III FACILITIES OR WHOSEFAILURE COULD IMPAIR THEIR CONTINUEDOPERATION;

EMERGENCY OR STANDBY EQUIPMENT & SYSTEMCOMPONENTS;

FIRE PROTECTION, DETECTION & ALARMEQUIPMENT & SYSTEM COMPONENTS;

N/A, NO SEISMIC USE GROUP III ORIV IN THE PROJECT

N/A, NO EMERGENCY OR STANBYEQUIPMENT IN THE PROJECT

5

EMERGENCY LIGHTING FIXTURESEXIT SIGNS

XX X

X 1,2,8,91

X

X

TS

PC

LC

T

F

M

M

M

IC

AA3

BB2

C1

D1

LIGHT POLE WITH MULTIPLE HEADS (AS INDICATED).

LIGHT POLE WITH SINGLE HEAD LUMINAIRE.

SHADING DENOTES EMERGENCY FIXTURE.

FACE; WITH DIRECTIONAL ARROW(S) AS INDICATED. FIXTURE TYPE "X" (U.N.O.).

EMERGENCY LIGHT - BATTERY OPERATED - WALL MOUNTED 84" AFF (U.N.O.). FIXTURE TYPE "Y" (U.N.O.).

EXIT LIGHT - CEILING MOUNTED; WALL MOUNT 7'-6" AFF OR ABOVE DOOR SHADED PORTION INDICATES

WALL MOUNTED FIXTURE - AS ABOVE - MOUNTING HEIGHT AS PER PLANS.

LUMINAIRE - AS ABOVE - WALL MOUNTED 84" AFF (U.N.O).

LIGHTING FIXTURES

FIXTURE CIRCUITRY NOTATION:

FOUR-WAY SWITCH - AS ABOVE.

THREE-WAY SWITCH - AS ABOVE.

TIME SWITCH - MOUNT 60" AFF.

DIMMER SWITCH - AS ABOVE, 1000 WATT RATING OR 0-10V AS REQUIRED. MOUNT 46" A.F.F.

SWITCH WITH PILOT LIGHT - AS ABOVE.

SINGLE POLE SWITCH - "a" INDICATES SWITCH LEG - MOUNT 46" AFF.

DOUBLE POLE WALL SWITCH - AS ABOVE.

NL - NIGHT LIGHT (UNSWITCHED CIRCUIT)a,b - LETTER(S) OF SWITCH(ES) CONTROLLING FIXTURE1 - CIRCUIT NUMBER TO WHICH FIXTURE IS CONNECTED

WIRING DEVICES

KEY OPERATED SWITCH - AS ABOVE.

CEILING MOUNTED DUPLEX RECEPTACLE, FLUSH IN CEILING (U.N.O.).

FLOOR MOUNTED DUPLEX RECEPTACLE WITH BRASS PLATE AND CARPET FLANGE.

DUPLEX 8" ABOVE COUNTER OR WALL HUNG LAVATORY.

SWITCH AMPS/FUSE AMPS/POLES.DISCONNECT SWITCH (FUSED OR NON-FUSED AS INDICATED) - MOUNT 60" AFF. 30/20/3 INDICATES

DUPLEX RECEPTACLE AS ABOVE - SPLIT WIRED, TOP HALF SWITCHED.

MOTORS AND EQUIPMENT

DUPLEX RECEPTACLE - MOUNT 18" AFF.

SINGLE CONVENIENCE RECEPTACLE - AS ABOVE.

DRY-TYPE TRANSFORMER.

ELECTRIC MOTOR.

HEAT DETECTOR - CEILING MOUNTED (U.N.O.).

NEW BRANCH CIRCUIT PANELBOARD - MOUNT TOP 78" AFF.

NL

1a,b

3

2

a

4

K

P

30/20/3

FIRE ALARM MAGNETIC DOOR HOLDER.

EXTERIOR FA BELL - MOUNT 90" AFF.

FIRE ALARM CONTROL PANEL - MOUNT TOP 72" AFF.

SPRINKLER PRESSURE SWITCH (FURNISHED BY FPC).

SPRINKLER FLOW SWITCH (FURNISHED BY FPC).

SPRINKLER TAMPER SWITCH (FURNISHED BY FPC).

HORN OR SPEAKER - MOUNT 80" AFF; V DENOTES COMBINATION AUDIBLE/VISUAL APPLIANCE.

MANUAL PULL STATION - MOUNT 46" AFF.

15

FACP

FAAP

ELECTRICAL SYMBOLS LEGEND

SMOKE DETECTOR - CEILING MOUNTED.

DUCT MOUNTED SMOKE DETECTOR WITH SAMPLING TUBES.

SEE LIGHTING FIXTURE SCHEDULE FOR DESCRIPTION.LUMINAIRE - CEILING MOUNTED. ALPHA-NUMERIC DESIGNATION DENOTES TYPE;

TO HEIGHT INDICATED.LED,FLUORESCENT OR H.I.D. FIXTURE - AS ABOVE - CEILING MOUNTED OR PENDANT MOUNTED

COMBINATION EXIT LIGHT WITH EMERGENCY LIGHTING HEADS. FIXTURE TYPE "X1" (U.N.O.).

M

PHOTOCELL MOUNTED IN WP OUTLET BOX LOCATED ON ROOF, FACING NORTH, (U.N.O.).

LIGHTING CONTACTOR FOR NUMBER OF CIRCUITS AS INDICATED ON PLAN.

JUNCTION BOX OR POINT OF CONNECTION - MOUNT 18" AFF OR AT HEIGHT REQUIRED BY RESPECTIVEEQUIPMENT ITEM MANUFACTURER.

DOUBLE DUPLEX RECEPTACLE - AS ABOVE.

SPECIAL PURPOSE OUTLET - MOUNT 18" AFF. TYPE AS REQUIRED BY RESPECTIVE EQUIPMENT MFR.

KILOWATT HOUR METER BASE.

FIRE ALARM SYSTEM

FIRE ALARM ANNUNCIATOR PANEL - MOUNT TOP 72" AFF.

(U.N.O.).DUCT MOUNTED SMOKE DETECTOR'S REMOTE ANNUNCIATOR LAMP AND TEST SWITCH-MOUNT ON CEILING,A

VISUAL FLASHER - MOUNT 80" AFF TO BOTTOM OF FLASHER; (NUMERALS INDICATE CANDELA).

V

DH

R INTERFACE RELAY FOR CODE REQUIRED ACTION, OR AS NOTED ON PLANS; SEE SPECIFICATION.

CM

MM

CONTROL MODULE FOR CODE REQUIRED ACTION; SEE SPECIFICATION.

MONITOR MODULE FOR CODE REQUIRED ACTION, OR AS NOTED ON PLANS; SEE SPECIFICATION.

EXISTING BRANCH CIRCUIT PANELBOARD.

MANUAL MOTOR STARTER WITH OVERLOAD PROTECTION - MOUNT ON SIDE OF UNIT OR AT 46" AFF.

OCCUPANCY SENSOR, CEILING MOUNTED, "2" INDICATES 2 POLE.

DOUBLE DUPLEX RECEPTACLE 8" ABOVE COUNTER

30

ARC FAULT CIRCUIT INTERRUPTER TYPE DEVICE, (U.N.O.)AFI/AFCI

TYPICALTYP

TCC TEMPERATURE CONTROL CONTRACTOR

TIME CLOCK

EWC

NF

ELECTRIC WATER COOLER; ROUGH-IN RECEPTACLE INCONSPICUOUSLY; COORDINATE WITH PC

WP WEATHERPROOF

U.N.O. UNLESS NOTED OTHERWISE

PC PLUMBING CONTRACTOR

NON-FUSED SWITCH

MIN MINIMUM

MFR MANUFACTURER

MC MECHANICAL CONTRACTOR

MAX MAXIMUM

HINGED DOOR WITH KEY LOCK.TELEPHONE TERMINAL CABINET 24" x 36" x 6" (U.N.O.) WITH FIRE RETARDANT PLYWOOD BACK ANDTTC

COMBINATION VOICE & DATA OUTLET - 8" ABOVE COUNTER.

FLOOR MOUNTED DATA OUTLET.

DATA OUTLET - 8" ABOVE COUNTER.

VOICE OUTLET - MOUNT 18" AFF; W INDICATES WALL MOUNT 46" AFF,

MICROPHONE OUTLET - CEILING MOUNTED FOR CORD HUNG DEVICE.

DUPLEX MICROPHONE OUTLET - FLOOR MOUNTED.

SPEAKER - WALL MOUNT 84" AFF.

FSS

GC

GFI/GFCI

EWH

FLA

EX

EM

AFF

EC

TTB

FULL LOAD AMPS

FUSIBLE SAFETY SWITCH

GROUND FAULT CIRCUIT INTERRUPTER TYPE DEVICE, (U.N.O.)

EXISTING

GENERAL CONTRACTOR

ELECTRIC WATER HEATER

INTERCOM STATION - MOUNT 46" AFF.

TELEPHONE TERMINAL BOARD - 3/4" FIRE RETARDANT PLYWOOD, 4' x 8' (U.N.O.).

PUSHBUTTON - MOUNT 46" AFF.

ABBREVIATIONS

ABOVE FINISHED FLOOR.

ELECTRICAL CONTRACTOR

COMBINATION VOICE & DATA OUTLET - MOUNT 18" AFF.

T.V. OUTLET - MOUNT 18" AFF U.N.O.

EMERGENCY

DUPLEX MICROPHONE OUTLET - MOUNT 18" AFF.

VOLUME CONTROL - MOUNT 46" AFF.

BELL - MOUNT 84" AFF.

DATA OUTLET - MOUNT 18" AFF.

AUXILIARY SYSTEMS

SPEAKER - CEILING MOUNTED.

FAN CONTROL SWITCH.FC

DACT DIGITAL ALARM COMMUNICATOR TRANSMITTER

RT RAINTIGHT

OCCUPANCY SENSOR WALL MOUNTED, MOUNT 46" AFF. "2" INDICATES DUAL RELAY.OS

D

T WALL BOX TIMER SWITCH.

ABOVE COUNTERAC

AMP INTERRUPTING CURRENTAIC

AFC AVAILABLE FAULT CURRENT

ATS AUTOMATIC TRANSFER SWITCH

CABLE TELEVISIONCATV

MOUNTING HEIGHTMH

NTS NOT TO SCALE

UNINTERRUPTABLE POWER SUPPLYUPS

FPC FIRE PROTECTION CONTRACTOR

FIRE ALARM POWER SUPPLY - MOUNTED 72" A.F.F.FAPS

(NUMERALS INDICATE CANDELA).

COMBINATION POWER & DATA/VOICE FLOOR BOX OR POKE THRU - "FF" INDICATES FURNITURE FEED.

WIRELESS ACCESS POINT - CEILING MOUNTED, U.N.O.

FLOOR MOUNTED COMBINATION VOICE & DATA OUTLET.

OS

J

F

SD

SD

F

H

F

F

F

F

F

F

T

F

P

S

S

V

TC

TV

MD

C

CR

RQE

ES

EH

ML

GB

INTRUSION ALARM SYSTEM

INTRUSION ALARM PANELIAP

KEY PAD

MOTION DETECTOR

DOOR CONTACT

K

REQUEST TO EXIT

CARD READER/PROX READER

ELECTRIC STRIKE (FURNISHED BY DIVISION 8)

ELECTRIFIED HARDWARE (FURNISHED BY DIVISION 8)

MAGNETIC LOCK (FURNISHED BY DIVISION 8)

GLASS BREAK SENSOR

VIDEO SURVEILLANCE CAMERA

DURESS/HOLD UP ALARMA

CIRCUITRY UP - CIRCUITRY DOWN.

BRANCH CIRCUITRY AS ABOVE, EXPOSED ON WALLS OR STRUCTURE.

BRANCH CIRCUITRY AS ABOVE, CONCEALED IN FLOOR SLAB OR UNDERGROUND.

BRANCH CIRCUITRY. CONCEALED IN WALLS OR ABOVE CEILINGS. ARROW INDICATES HOME RUN TO PANEL.SHORT SLASH MARKS INDICATE "HOT" WIRES, LONG SLASH MARK INDICATES "NEUTRAL" WIRE, LONG SLASHWITH SOLID CIRCLE INDICATES GREEN GROUNDING CONDUCTOR.

CIRCUITRY DESIGNATIONS

MECHANICAL EQUIPMENT ITEM IDENTIFICATION PER EQUIPMENT SCHEDULE ON MECHANICAL DRAWINGS.X-X

XXX

MISCELLANEOUS

SS

C J

OB

# 2

016123_B

ID S

ET

- N

OT

FO

R C

ON

ST

RU

CT

ION

Th

e S

ea

l and

Sig

na

ture

app

ly o

nly

to t

he

Do

cum

en

t to

wh

ich t

he

y a

re A

ffix

ed

, an

d E

xpre

ssl

y D

iscla

im a

ny

Re

spo

nsib

ility

fo

r all

oth

er

Pla

ns, S

pe

cifica

tion

s,

Estim

ate

s, R

ep

ort

s, o

r o

the

r D

ocu

men

ts o

r In

str

um

en

tsre

latin

g t

o o

r in

ten

de

d t

o b

e u

se

d f

or

any p

art

or

pa

rts

of

the

Arc

hite

ctu

ral o

r E

ng

ine

erin

g P

roje

ct.

Co

pyrig

ht ©

20

16

by S

SC

En

gin

ee

ring

, In

c.

MISSOURI

5017 Washington Place Suite 200

St. Louis, M0 63108

314.361.0000 ph

314.361.9191 fax

Copyright 2016 HKW Architects

IOWA

1000 Melrose Avenue

Iowa City, IA 52246

319.343.7055 ph

hkwarchitects.com

18207 Edison Avenue

Chesterfield, M0 63005

636.530.7770 ph

636.530.7877 fax

PN

C B

ank

Bid Set

E0.1

PN

C V

alle

y P

ark

16.008.00

April 11, 2016

ELECTRICALSYMBOLS,

ABBREVIATIONS& GENERALNOTES

912 Meramec Station Road, Valley Park, MO 63021

GENERAL CONSTRUCTION NOTES:

1. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR NECESSARY PERMITS, LICENSES, INSPECTIONS ANDFEES FROM THE LOCAL AUTHORITIES. CONTRACTOR SHALL BE LICENSED BY LOCAL AND/OR STATE AUTHORITIESHAVING JURISDICTION..

2. ALL MATERIAL AND WORKMANSHIP SHALL CONFORM TO THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA),NATIONAL ELECTRICAL CODE (NEC), INTERNATIONAL BUILDING CODE (IBC) AND OTHER APPLICABLE LOCAL, STATEAND NATIONAL CODES.

3. ALL ELECTRICAL MATERIAL USED ON THIS PROJECT SHALL BE "UL" LISTED AND LABELED.4. THE ENTIRE ELECTRICAL SYSTEM AND ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED IN STRICT

ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND AS SHOWN ON THE DRAWINGS. PROVIDE A GROUNDWIRE IN EACH POWER CONDUIT, SIZED PER THE NEC.

5. CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING A COMPLETE SYSTEM PER CONTRACT DRAWINGS ANDENSURING THAT THE SYSTEM IS OPERATIONAL UPON JOB COMPLETION.

6. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WITH ALL OTHER TRADES AND DISCIPLINES TO AVOIDCONFLICTS AND TO VERIFY ALL EQUIPMENT CONNECTIONS. COORDINATE ALL WIRING DEVICE LOCATIONS ANDELEVATIONS INDICATED ON THE PLANS WITH THE OWNER, ARCHITECT AND FINAL FURNITURE/EQUIPMENTLAYOUTS.

7. CONTRACTOR SHALL GUARANTEE ALL LABOR AND MATERIAL INSTALLED OR FURNISHED UNDER THIS CONTRACTFOR A PERIOD OF NOT LESS THAN ONE YEAR AFTER FINAL ACCEPTANCE OF THE BUILDING.

8. MAINTAIN AND VERIFY ELECTRICAL EQUIPMENT CLEARANCES AND WORKING SPACE PER NEC.9. PROVIDE ELECTRICAL SYSTEMS IDENTIFICATION AS INDICATED IN THE SPECIFICATIONS AND REQUIRED BY THE

NEC OR NFPA 70E.10. IF ANYTHING ON THE PLANS IS NOT IN COMPLIANCE WITH NATIONAL, STATE OR LOCAL CODES, THE ENGINEER

SHALL BE ADVISED BY THE ELECTRICAL CONTRACTOR DURING THE BIDDING PROCESS. THERE ARE TO BE NOCHANGES TO THE CONTRACT DOCUMENTS WITHOUT WRITTEN PERMISSION FROM THE ENGINEER.

11. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL MEANS AND METHODS FOR NEW WORK, SAFETY, ETC., INACCORDANCE WITH ALL AUTHORITIES HAVING JURISDICTION. (I.E. OSHA, NEC, ETC.)

12. THE CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR PHASING AND SCHEDULING OF THISPROJECT. COORDINATE WITH OWNER'S FIELD REPRESENTATIVE.

13. VERIFY ALL INDICATED DIMENSIONS BY FIELD MEASUREMENTS. NOTIFY ENGINEER OF ANY DISCREPANCIES.14. PROVIDE ACCESS PANELS OR DOORS WHERE EQUIPMENT OR DEVICES REQUIRED TO BE ACCESSIBLE ARE

CONCEALED BEHIND INACCESSIBLE SURFACES.15. PRIOR TO TURNOVER, THIS CONTRACTOR SHALL REMOVE ALL RUBBISH, DIRT, DEBRIS AND STAINS ON THEIR

WORK OR CAUSED BY THEIR WORK AND SHALL THOROUGHLY CLEAN ALL EQUIPMENT, FIXTURES, DEVICES, ETC.CONTRACTOR SHALL REPLACE, TOUCH-UP OR REFINISH THE FACTORY FINISH ON EQUIPMENT, FIXTURES,DEVICES, ETC. MARRED DURING SHIPMENT, INSTALLATION OR CONSTRUCTION.

16. PANELBOARD CIRCUIT BREAKERS SHALL BE EQUIPPED WITH BOLT-ON TYPE BREAKERS, PHENOLIC NAME TAGSAND KEYED LOCK AND LATCH. EACH PANEL SHALL BE PROVIDED WITH TWO KEYS WITH ALL PANELS KEYEDALIKE. ALL CIRCUIT BREAKERS USED TO SWITCH LIGHT FIXTURES SHALL BE TYPE SWD SHALL BE APPROVED FORTHE PURPOSE. ALL CIRCUIT BREAKERS SERVING HVAC EQUIPMENT SHALL BE HACR TYPE.

17. ALL CIRCUITS INDICATED ON THESE DRAWINGS ARE 20A, 1P CIRCUIT BREAKERS IN PANELS UNLESS NOTEDOTHERWISE.

18. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER IDENTIFICATION AND LABELING OF ALLCIRCUIT BREAKERS. EACH PANELBOARD SHALL BE EQUIPPED WITH A TYPE WRITTEN CIRCUIT DIRECTORY. ALLEXISTING PANELBOARDS THAT HAVE CIRCUITS ALTERED SHALL HAVE A NEW TYPE WRITTEN CIRCUIT DIRECTORYSHOWING CIRCUIT REVISIONS AND EXISTING CIRCUIT CONDITIONS ON THE NEW DIRECTORY.

19. MINIMUM WIRE SIZE SHALL BE #12 AWG UNLESS OTHERWISE NOTED. MINIMUM CONDUIT SIZE SHALL BE 1/2"UNLESS OTHERWISE NOTED. ALL CONDUIT IN SLABS OR EXTERIOR TO BUILDING SHALL BE MINIMUM 1". PROVIDE ANYLON/POLY PULL CORD IN ALL EMPTY CONDUITS.

20. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL COPPER CONDUCTORS TYPE THHN OR THWN FOR ALL INTERIORBUILDING WIRE. FOR EXTERIOR FEEDERS AND BRANCH CIRCUITS PROVIDE ALL COPPER CONDUCTORS TYPEXHHW-2.

21. VOLTAGE DROP MINIMUM WIRE SIZING (20A CIRCUIT) USE: 120V CIRCUIT OVER 100' SHALL BE #10 MINIMUM; 120VCIRCUIT OVER 175' SHALL BE #8 MINIMUM; 208V CIRCUIT OVER 200' SHALL BE #10 MINIMUM; 277V CIRCUIT OVER200' SHALL BE #10 MINIMUM. MINIMUM WIRE SIZE FOR ANY 20A BRANCH CIRCUIT SHALL BE #12. FURTHERMORE,CONSIDER ALL DERATING OF CONDUCTORS AS REQUIRED IN ACCORDANCE WITH THE APPLICABLE NEC.

22. ELECTRICAL CONTRACTOR SHALL HAVE THE OPTION OF GROUPING HOME RUNS IN ONE CONDUIT, PER THEREQUIREMENTS OF SECTION 310 OF THE NATIONAL ELECTRICAL CODE. NO MORE THAN FOUR (4) CIRCUITS SHALLBE ALLOWED TO BE GROUPED AND INSTALLED IN A SINGLE JUNCTION BOX. EC SHALL BE RESPONSIBLE FORINCREASING CONDUCTOR SIZE AND DERATING. HOME RUNS WITH MORE THAN THREE CIRCUITS SHALL BE #10AWG. CONDUCTOR MINIMUM. PROVIDE DEDICATED NEUTRALS FOR EACH PHASE CONDUCTOR AND CONSIDERTHEM AS A CURRENT CARRYING CONDUCTOR FOR DERATING.

23. ALL HOME RUNS SHALL BE IN EMT CONDUIT. MC CABLE IS PERMITTED ABOVE CEILINGS FROM HOMERUNS TOFIXTURES AND WIRING DEVICES WITHIN WALLS AND FURRED COLUMNS. REFER TO ELECTRICAL SPECIFICATIONSFOR MORE DETAILED INFORMATION.

24. ONLY PVC CONDUIT SHALL BE PERMITTED IN CONCRETE SLAB, EXCEPT FOR GRS ELLS.25. WHEN SAW CUTTING FLOOR IS REQUIRED, CONTRACTOR SHALL LIMIT DEPTH TO A MINIMUM. ROUTE NEW

CONDUITS BELOW OR ABOVE EXISTING CONDUITS, WATER PIPES, ETC. CONDUIT SHALL HAVE A MINIMUM OF 1'' OFCONCRETE COVER. CONTRACTOR SHALL XRAY FLOOR SLAB PRIOR TO ANY SAW CUTTING.

26. ELECTRICAL CONTRACTOR SHALL ARRANGE WITH THE ELECTRIC, CATV AND TELEPHONE UTILITY COMPANIES FORINCOMING SERVICE REQUIREMENTS FROM LANDLORD DEMARC AND INCLUDE ALL COSTS IN BASE BID.

27. HEATING, VENTILATING, AIR CONDITIONING EQUIPMENT AND PLUMBING EQUIPMENT ALONG WITH ALL OTHERMISCELLANEOUS EQUIPMENT, MOTORS, AND KITCHEN EQUIPMENT SHALL BE POWERED AS CALLED OUT ONEQUIPMENT PROVIDER'S SCHEDULES UNLESS OTHERWISE NOTED. EC SHALL PROVIDE DISCONNECTING MEANSUNLESS SPECIFICALLY NOTED ON EQUIPMENT PROVIDER'S SCHEDULE.

28. SUPPORT ALL CONDUITS FROM STRUCTURAL WALLS, SLABS, MEMBERS AND ROOF JOISTS. DO NOT SUPPORTCONDUITS FROM CEILING TIE WIRES, DUCTWORK, PIPING, ROOF DECK OR OTHER NON-STRUCTURAL MEMBERS.

29. SUPPORTING OF ELECTRICAL CONDUITS: THE INDIVIDUAL BRANCH CIRCUIT CONDUIT AND ASSOCIATED 4'' X 4''JUNCTION BOXES MAY BE SUPPORTED FROM FLOOR/ROOF JOISTS. ALL LARGER FEEDER CONDUITS AND/ORCLUSTER OR GROUPS OF BRANCH CIRCUIT CONDUITS SHALL BE SUPPORTED ON STEEL TRAPEZE WITH STEELCHANNEL ATTACHED TO STEEL OR WOOD JOIST/BEAMS WITH PROPER ATTACHMENTS. NO SUPPORT SHALL BEATTACHED TO THE ROOF DECK (NO EXCEPTIONS). HANG CONDUIT FROM TOP CHORD OF BAR JOIST WHENATTACHING HOME RUNS TO JOIST.

30. INTERIOR AND EXTERIOR LIGHT FIXTURES SHALL BE FURNISHED AND INSTALLED AS SHOWN ON THE DRAWINGSAND AS CALLED OUT IN THE LIGHTING FIXTURE SCHEDULE.

31. ALL WIRING DEVICES SHALL BE FLUSH MOUNTED, UNLESS NOTED OTHERWISE. ALL CONDUIT SHALL BE RUNWITHIN WALL CAVITIES, BELOW FLOOR AND ABOVE CEILINGS. SURFACE MOUNTED ELECTRICAL WORK SHALL NOTBE USED UNLESS SPECIFICALLY NOTED ON THE PLANS.

32. ALL WALL AND CEILING FIXTURES AND DEVICES SHALL BE INDEPENDENTLY AND SECURELY MOUNTED SO THEYARE NOT DEPENDENT ON CEILING FINISH FOR SUPPORT AND CAN NOT BE ROTATED OR DISPLACED. FIXTURESAND DEVICES MOUNTED IN SUSPENDED ACOUSTICAL CEILING TILE SHALL HAVE CHANNEL SUPPORTS ACROSSTHE MAIN GRID RUNNERS OR GRID SUPPORTS SECURELY ANCHORED SO AS NOT TO CAUSE TILE TO SAG OR SOFIXTURE OR DEVICE CAN NOT BE LIFTED, ROTATED OR DISPLACED.

33. ELECTRICAL LIGHT FIXTURES, MECHANICAL AIR DEVICES, FIRE SPRINKLERS, AND SMOKE DETECTORS IN CEILING:ALL SUBS NEED TO TAKE OTHER DISCIPLINES INTO CONSIDERATION BEFORE STARTING THEIR WORK. ALL ITEMSTHAT NEED TO BE MOVED WILL BE MOVED AT THE SUB'S EXPENSE. FIRE SPRINKLERS MUST BE LOCATED AMINIMUM OF 30 INCHES FROM ANY SURFACE MOUNTED LIGHT. SMOKE DETECTORS MUST BE MOUNTED NOCLOSER THAN 3 FEET OF AN AIR DEVICE OR CEILING FAN. FIRE SPRINKLERS, LIGHT FIXTURES, SMOKEDETECTORS, AND AIR DEVICES ALL TO BE CENTERED DOWN THE HALLWAYS. ELECTRICAL, MECHANICAL, FIRESPRINKLER, AND LOW VOLTAGE SUB CONTRACTOR MUST MEET AND DECIDE BEFORE ANYONE STARTS, WHERELOCATION OF THESE ITEMS WILL BE LOCATED. IF ITEM NEEDS TO BE MOVED, IT WILL BE AT THE EXPENSE OF THESUB CONTRACTOR. COORDINATE WITH ARCHITECT'S REFLECTED CEILING PLAN.

34. ALL OPENINGS IN FIRE AND/OR SMOKE RATED WALLS, FLOORS, AND PARTITIONS FOR CONDUITS SHALL BESEALED WITH RED FIRE RESISTANT FOAM OR PUTTY TO MAINTAIN THE FIRE AND/OR SMOKE RATING. ALLOPENINGS IN FIRE RATED AND/OR SMOKE WALLS, FLOORS, AND PARTITIONS FOR CABLING SHALL BE SEALEDWITH WIREMOLD FLAMESTOPPER, STI EZ-PATH, HILTI SPEED SLEEVE OR EQUIVALENT.

35. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF LIGHT FIXTURES, DIMENSIONAL LOCATION OFFIXTURES IN DRYWALL CEILING, ETC. LOCATION OF FLOOR BOXES AND RECEPTACLES, INCLUDING MOUNTINGHEIGHTS. ALL RECEPTACLES AND COVER PLATE COLORS SHALL BE APPROVED BY ARCHITECT

36. OWNER RESERVES THE RIGHT TO RELOCATE ANY LIGHT FIXTURE, RECEPTACLE, ETC., BEFORE BEING INSTALLED10'-0'' FROM LOCATION AS SHOWN ON PLANS AT NO ADDITIONAL EXPENSE TO THE OWNER.

37. OUTLETS IN OFFICES SHALL HAVE THEIR WALL LOCATIONS COORDINATED WITH FINAL FURNITURE LAYOUT. GROUPPOWER AND COMMUNICATION OUTLETS SIDE BY SIDE AT SAME HEIGHT.

38. NO CONDUIT OR CABLES SHALL BE INSTALLED EXPOSED IN FINISHED AREA. NON-CEILING AREA CONDUITS SHALLBE INSTALLED EXPOSED IN A NEAT WORKMAN LIKE MANNER AND BE PAINTED TO MATCH ADJACENT FINISHES.

39. ALL MATERIALS, DEVICES, FIXTURES, ETC., THAT ARE REQUIRED FOR THIS PROJECT ARE TO BE FURNISHED ANDINSTALLED BY THE EC, UNLESS SPECIFICALLY INDICATED TO BE FURNISHED AND OR INSTALLED BY OTHERS.

40. TELEPHONE, IT, AUDIO, VIDEO AND SECURITY CABLE WIRING WILL BE PROVIDED BY OWNERS VENDOR. EC SHALLCOORDINATE AND PROVIDE ALL ROUGH-IN'S AS REQUIRED. LOW VOLTAGE DEVICES HAVE BEEN SHOWN ON THEPLANS FOR REFERENCE PURPOSES ONLY. ALL LOW VOLTAGE CABLING SHALL BE ROUTED IN CONDUIT FROMDEVICE/JUNCTION BOX TO ABOVE AN ACCESSIBLE CEILING OR IN ATTIC SPACE; 1" EMT MINIMUM. EC SHALLPROVIDE J-HOOKS AS REQUIRED, NO MORE THAN 60" O.C.

41. ALL SIGNAL AND CONTROL CABLES SHALL BE MINIMUM #18 STRANDED COPPER, UNLESS NOTED OTHERWISE. ALLCONNECTIONS AND SPLICES TO BE MADE BY USE OF ''STA-KON'' CONNECTORS AND TERMINAL STRIPS.

42. TYPICAL SEISMIC DETAILS ARE PROVIDED ON THE DRAWINGS FOR REFERENCE ONLY. CONTRACTOR SHALLPROVIDE SHOP DRAWINGS TO THE OWNER'S ENGINEER FOR REVIEW AND APPROVAL PRIOR TO SUBMITTAL TOTHE PLAN REVIEWER. SHOP DRAWINGS SHALL SHOW ALL EQUIPMENT ANCHORAGE TO WALLS/CEILINGS/FLOORSAND SHALL INCLUDE SIZE OF SEISMIC ANCHOR BOLTS USED FOR EACH SYSTEM. CONTRACTOR SHALL PROVIDECALCULATIONS, DETAILS, ETC. - PREPARED BY, SIGNED AND SEALED BY A LICENSED STRUCTURAL ENGINEER.REFER TO SPECIFICATIONS.

GENERAL DEMOLITION NOTES:

1. THE OWNER INTENDS TO VACATE SPECIFIC AREAS OF WORK BEFORE DEMOLITION BEGINS. ALL OTHER AREAS SHALLREMAIN OCCUPIED AND IN ACTIVE USE. UTILITIES AND SERVICES TO EXISTING ACTIVE AREAS SHALL NOT BE INTERRUPTEDWITHOUT THE OWNER'S APPROVAL AS TO THE TIME AND DURATION. THE OWNER WILL CONTINUE TO OCCUPY THE RESTOF THE EXISTING FACILITIES THROUGHOUT THE CONSTRUCTION OPERATIONS. THE ELECTRICAL CONTRACTOR SHALL SOORGANIZE HIS WORK AS TO CAUSE A MINIMUM OF UTILITY INTERRUPTIONS, WHICH SHALL BE SCHEDULED AT THECONVENIENCE OF THE OWNER.

2. ALL ELECTRICAL EQUIPMENT, LIGHTING FIXTURES, SWITCHES, RECEPTACLES, SPECIAL OUTLETS, ETC., WHICH ARE NOTEDTO BE DEMOLISHED, OR ARE SHOWN WITH DASHED LINE SYMBOLS ON THE DEMOLITION PLANS, SHALL BE REMOVED.ASSOCIATED WIRING AND CONDUIT SHALL BE REMOVED BACK TO THE SOURCE OR EXISTING UPSTREAM DEVICE TOREMAIN AND MADE SAFE.

3. REMOVE EQUIPMENT, FIXTURES, DEVICES AND OUTLETS AS SPECIFIED AND SHOWN ON DRAWINGS, AND AS MAYBECOME NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS. EXAMINE ALL EXISTING WALLS AND CEILING DESIGNATEDFOR REMOVAL TO DETERMINE THE CONDUIT AND WIRING THAT WILL REQUIRE REMOVAL.

4. FOR EXISTING ELECTRICAL DEVICES IN WALLS TO BE REMOVED, DISCONNECT POWER, REMOVE CONDUCTORS AND CAPCONDUIT BELOW FLOOR OR ABOVE CEILING AS REQUIRED. DEVICES ARE TO BE REMOVED ALONG WITH WALL BYGENERAL CONTRACTOR.

5. FOR EXISTING ELECTRICAL EQUIPMENT, FIXTURES AND DEVICES TO BE REMOVED FROM WALLS WHICH REMAIN,DISCONNECT POWER, REMOVE CONDUCTORS, REMOVE THE ELECTRICAL ITEM, AND PATCH AND FINISH THE SURFACE ASREQUIRED TO MATCH THE EXISTING, OR MAKE READY FOR NEW WALL FINISH. PROVIDE BLANK PLATES WHERE NOTED ORREQUIRED.

6. EXISTING RECEPTACLES, DEVICES, ETC. TO REMAIN ARE DENOTED BY THIN SOLID LINE OR MAY NOT BE INDICATED AT ALL.THESE DEVICES SHALL BE EXTENDED TO BE FLUSH WITH NEW FINISH ON EXISTING WALL WHERE REQUIRED.

7. MAINTAIN CIRCUIT CONTINUITY TO ALL EQUIPMENT, FIXTURES, DEVICES, ETC., TO REMAIN IN USE WHETHER NOTED ON THEPLANS OR NOT. FIELD VERIFY EXISTING ITEMS TO REMAIN IN USE. WIRING FOR EXISTING CIRCUITS WHICH ARE PARTIALLYABANDONED SHALL BE RECONNECTED BY THE ELECTRICAL CONTRACTOR TO SERVICE THE REMAINING OUTLETS ON THECIRCUIT.

8. ALL WIRING FOR A CIRCUIT WHICH IS TO BE REMOVED SHALL BE REMOVED BACK TO THE PANEL WHICH SUPPLIED THECIRCUIT.

9. EXISTING CONDUIT & CONDUCTORS MAY BE REUSED WHERE FEASIBLE. ALL UNUSED CONDUIT MADE EMPTY BY THISDEMOLITION SHALL BE REMOVED BY THE ELECTRICAL CONTRACTOR. WHERE CONDUITS EXTENDING OUT OF THE FLOORARE TO BE REMOVED, CUT THE CONDUIT OFF 1/2" BELOW THE FLOOR LINE AND PATCH.

10. ALL ACTIVE CIRCUITING THAT RUNS THROUGH THIS SPACE, ORIGINATING AND/OR TERMINATING IN OTHER SPACES, SHALLREMAIN IN PLACE. COORDINATE WITH NEW CEILING WORK FOR RAISED CEILING WHICH MAY REQUIRE CIRCUITINGRELOCATION.

11. ALL UNUSED TELEPHONE AND DATA CABLES SHALL BE REMOVED. ANY OTHER UNUSED LOW VOLTAGE SYSTEMS CABLESSHALL ALSO BE REMOVED.

12. ALL EXISTING EQUIPMENT, LIGHTING FIXTURES, WIRING DEVICES, AND MATERIALS TO BE REMOVED SHALL BECOME THEPROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE PREMISES AND PROPERLY DISPOSED OF INACCORDANCE WITH AUTHORITIES HAVING JURISDICTION, UNLESS OTHERWISE NOTED. ALL ITEMS NOTED THAT THE OWNERCHOOSES TO KEEP SHALL BE TRANSFERRED TO THEIR STORAGE AREA BY THE ELECTRICAL CONTRACTOR.

13. FOR ALL EXISTING ELECTRICAL WIRING DEVICES, TELEPHONE, DATA ETC., CONTRACTOR SHALL REMOVE/REINSTALLCOVERPLATES AS REQUIRED TO ALLOW FOR NEW FINISHES.

14. INFORMATION ON THE EXISTING CONDITIONS PLANS ARE COMPILED FROM EXISTING DRAWINGS AND CASUAL FIELDOBSERVATIONS AND SHALL BE CONSIDERED APPROXIMATE ONLY. VERIFICATION OF ALL EQUIPMENT, WIRING DEVICESAND FIXTURES, EITHER SHOWN OR NOT SHOWN ON THESE PLANS, SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.NOTIFY ENGINEER IMMEDIATELY IF DISCREPANCIES EXIST.

ELECTRICAL SHEET LIST

Sheet Number Sheet Name

E0.1 ELECTRICAL SYMBOLS, ABBREVIATIONS & GENERAL NOTES

E0.2 ELECTRICAL PANEL SCHEDULES

E0.3 ELECTRICAL DETAILS

E1.1 ELECTRICAL LIGHTING PLAN

E2.1 ELECTRICAL POWER & SYSTEMS PLAN

ELECTRICAL ALTERNATE #1:PROVIDE AN ALTERNATE PRICE ADDER FOR THE FOLLOWING:- REPLACE EXISTING PANEL 102B WITH A NEW 60 POLE, 1 SECTION, 120/208V, 3 PHASE, 4 WIRE, 225A, 10KAIC, MLO PANELBOARD.- PROVIDE TEN (10) ADDITIONAL 20A/1 POLE CIRCUIT BREAKERS AS SPARES.- PROVIDE A 120/208V, 3 PHASE SURGE PROTECTIVE DEVICE AND AN ASSOCIATED 30A/3 POLE CIRCUIT BREAKER FOR THE SPD.- PROVIDE ALL ASSOCIATED INSTALLATION, LABOR AND COORDINATEION FOR THE ABOVE WORK.

Revision Schedule

No Date Description

Page 2: ELECTRICAL SYMBOLS LEGEND - REiCON Constructors · 2016-04-12 · pnc bank bid set e0.1 pnc valley park 16.008.00 april 11, 2016 electrical symbols, abbreviations & general notes

SS

C J

OB

# 2

016123_B

ID S

ET

- N

OT

FO

R C

ON

ST

RU

CT

ION

Th

e S

ea

l and

Sig

na

ture

app

ly o

nly

to t

he

Do

cum

en

t to

wh

ich t

he

y a

re A

ffix

ed

, an

d E

xpre

ssl

y D

iscla

im a

ny

Re

spo

nsib

ility

fo

r all

oth

er

Pla

ns, S

pe

cifica

tion

s,

Estim

ate

s, R

ep

ort

s, o

r o

the

r D

ocu

men

ts o

r In

str

um

en

tsre

latin

g t

o o

r in

ten

de

d t

o b

e u

se

d f

or

any p

art

or

pa

rts

of

the

Arc

hite

ctu

ral o

r E

ng

ine

erin

g P

roje

ct.

Co

pyrig

ht ©

20

16

by S

SC

En

gin

ee

ring

, In

c.

MISSOURI

5017 Washington Place Suite 200

St. Louis, M0 63108

314.361.0000 ph

314.361.9191 fax

Copyright 2016 HKW Architects

IOWA

1000 Melrose Avenue

Iowa City, IA 52246

319.343.7055 ph

hkwarchitects.com

18207 Edison Avenue

Chesterfield, M0 63005

636.530.7770 ph

636.530.7877 fax

PN

C B

ank

Bid Set

E0.2

PN

C V

alle

y P

ark

16.008.00

April 11, 2016

ELECTRICALPANEL

SCHEDULES

912 Meramec Station Road, Valley Park, MO 63021

Notes:

Receptacle 19420 VA 75.75% 14710 VA Total Est. Demand Current: 105 A

Other 2900 VA 100.00% 2900 VA Total Conn. Current: 118 A

Electric Heat 4000 VA 100.00% 4000 VA Total Est. Demand: 37855 VA

Power 180 VA 100.00% 180 VA Total Conn. Load: 42565 VA

Lighting 2145 VA 100.00% 2145 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 125 A 111 A 121 A

Total Load: 14835 VA 13374 VA 14350 VA

3 41 Receptacle - CASH ROOM 20 A 1 860 VA 0 VA 1 20 A Spare 42 3

3 39 Receptacle - CASH ROOM 20 A 1 360 VA 2100 VA 1 30 A Water Heater 40 3,5

3 37 Receptacle - CASH ROOM 20 A 1 360 VA 2000 VA -- -- -- 38 --

3 35 Receptacle - TELLER/CONCIERGE 20 A 1 360 VA 2000 VA 2 25 A EH-1 36 3,5

3 33 Receptacle - TELLER/CONCIERGE 20 A 1 180 VA 180 VA 1 20 A IT RACK Receptacle 34 3,4

3 31 Receptacle - TELLER/CONCIERGE 20 A 1 360 VA 360 VA 1 20 A IT RACK Receptacle 32 3,4

3 29 Receptacle - TELLER/CONCIERGE 20 A 1 180 VA 2500 VA 1 20 A Receptacle - CASH/SECURITY 30 3

3 27 RECEPTACLE - ICI PRINTER 20 A 1 360 VA 180 VA 1 20 A MICR Printer - CONCIERGE Counter 28 2

3 25 MDF Printer - CONCIERGE 20 A 1 500 VA 720 VA 1 20 A Receptacle - OFF STAGE & DISCOVER 26 2

3 23 Receptacle - CONCIERGE 20 A 1 720 VA 1000 VA 1 20 A Refrigerator - BREAKROOM 24 2

2 21 Receptacle - OFF STAGE 20 A 1 720 VA 1200 VA 1 20 A Microwave - BREAKROOM Counter 22 2

2 19 Receptacle - VESTIBULE 20 A 1 360 VA 1740 VA 1 20 A Receptacle - BREAKROOM/JANITOR 20 2

2 17 Exterior PNC Sign 20 A 1 200 VA 900 VA 1 20 A Receptacle - OFFICE 18 2

2 15 General Receptacles 20 A 1 900 VA 1440 VA 1 20 A Receptacle - OFFICE 16 2

2 13 Emergency Lighting 20 A 1 501 VA 500 VA 1 20 A Receptacle for Diebold 14 2

2 11 Off-Stage, Offices, Break, and Cash... 20 A 1 630 VA 360 VA 1 20 A Receptacle - IT 12 2

2 9 Corridor, Janitor, Restrooms Lighting,... 20 A 1 714 VA 400 VA 1 20 A Receptacle - EWC 10 2

2 7 Vestibule, Lobby, and Concierge Lighting 20 A 1 894 VA 1900 VA 1 20 A Receptacle TOILET/COUPON 8 2

-- 5 -- -- -- 3360 VA 1280 VA -- -- -- 6 --

-- 3 -- -- -- 3360 VA 1280 VA -- -- -- 4 --

1 1 RTU 35 A 3 3360 VA 1280 VA 3 40 A RTU 2 1

CKTNOTES

CKT

Circuit Description Trip Poles

A B C A B C

Poles Trip Circuit Description

CKT CKTNOTES

Notes:

Enclosure: Type 1 MCB Rating:

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: Phases: 3 Mains Type: MLO

Location: Elec/Data 105 Volts: 120/208 Wye A.I.C. Rating:

Branch Panel: 102B

ELECTRICAL PANELBOARD NOTES:

1. EXISTING LOAD TO REMAIN. FIELD VERIFY PANEL LABELING IS ACCURATE PRIOR TO WORK.2. EXISTING LOAD TO BE REMOVED. FIELD VERIFY LOAD IS DEMOLISHED AND RE-USE CIRCUIT BREAKER.3. NEW BREAKER IN EXISTING SPACE.4. VERIFY WITH OWNER'S IT REP PRIOR TO ORDERING.5. VERIFY SIZE WITH MC/PC PRIOR TO ORDERING.

NOTE: EXISTING PANEL SCHEDULE IS NOT LABELED WELL AND ASSUMPTIONS HAVE BEEN MADE FOR RE-USE OFCIRCUITS. FIELD VERIFY ALL AVAILABLE CIRCUITS AFTER DEMOLITION AND MODIFY CIRCUITING AS REQUIRED.NOTE CHANGES ON AS BUILT DRAWINGS.

Revision Schedule

No Date Description

Page 3: ELECTRICAL SYMBOLS LEGEND - REiCON Constructors · 2016-04-12 · pnc bank bid set e0.1 pnc valley park 16.008.00 april 11, 2016 electrical symbols, abbreviations & general notes

NO SCALE

ATTACHMENT - LATERAL BRACING TO MASONRY ORCONCRETE

5/8" BOLT B-LINE, B22 CHANNELLONGITUDINAL ORTRANSVERSE BRACE(9'-4" MAX LENGTH)

1/2"x1-1/4" HEXHEAD CAP SCREWSAND N225WO NUTS

EXPANSION ANCHOR

1

1

NO SCALE

CONCRETE WALL MOUNTED EQUIPMENT SEISMICANCHORAGE

NOTES:1. BASED ON MASON INDUSTRIES INC. TYPE "PB" NEOPRENE BUSHING.

ELONGATED INNERSTEEL SLEEVE

STEEL DISK

INNER NEOPRENEBUSHING

TYPE "PB"

OUTSIDENEOPRENEELEMENT

OUTERSTEEL SLEEVE

SEISMICANCHOR BOLTTYPE "SAB"

INSIDE NEOPRENEELEMENT

BACK OFSTEEL PANEL

NO SCALE

RECESSED MOUNTED FIXTURE SEISMIC SUPPORT"SS3B"

INSERT #2 TAPPING SCREWSTHRU CLAMP AND TEE BAR(2 PER CLAMP)

CADDY SFCLT SEISMICFIXTURE CLAMP WITH

SELF TAPPING SCREWSONE (1) AT EACH

CORNER (TYP. OF 4)

RECESSEDTROFFER

FASTENED TOSTRUCTURE

ABOVE

SEISMIC SUPPORTEDTEE BAR CEILING

CEILING GRIDSUPPORT BY G.C.

CEILING GRIDSUPPORT BY G.C.

12GA. SLACK WIREOR PENCIL ROD

UP TO STRUCTURE

NO SCALE

RECESSED MOUNTED FIXTURE SEISMIC SUPPORT"SS4"

MOUNT ADJUSTABLEMOUNTING BRACKETS

TO LIGHT FIXTUREAND C-CHANNEL

MOUNT C-BAR LIGHTFIXTURE SUPPORT

CHANNEL ON T-BAR SHEET METALSCREWC-BARTO T-BAR PLUSSAME ON DIAGONAL

T-BARCEILINGGRID

ADJUSTABLEMOUNTINGBRACKET

NO SCALE

SEISMIC ISOLATOR TYPE "Z1"

OVERSIZED HOLE

SEISMIC ANCHOR

CONCRETEFLOOR

EQUIPMENTSUPPORT LEG

SEISMIC ANCHORBOLT

STEEL WASHER

NEOPRENEBUSHING"TYPE Z"

FIELD TRIM BUSHINGTO MATCH HOLE DEPTH

DESIGNER NOTES:1. REFERENCE SPECIFICATION SECTION 260025, "SEISMIC

RESTRAINTS" ARTICLE FOR ADDITIONAL INFORMATION.

2. THIS IS BASED ON MASON INDUSTRIES INC. TYPE "SG" NEOPRENE ISOLATOR.

3. NORMALLY USED ON FLOOR MOUNTED EQUIPMENT WHICH DOES NOT GENERATE IT'S OWN VIBRATION.

NO SCALE

SEISMIC SWAY BRACING CABLE ANCHOR

NO SCALE

NOTES FOR SEISMIC BRACING

GENERAL

1. NO BRACING IS REQUIRED IF THE TOP OF THE CONDUIT IS SUSPENDED

12" OR LESS FROM THE SUPPORTING STRUCTURAL MEMBER.2. ATTACHMENT TO STRUCTURAL MEMBERS SHALL USE DEVICES INCLUDED IN FEDERAL SPECIFICATION WW--H-171 (MSS SP-58) OR BE BOLTED/WELDED AS APPROVED BY THE ENGINEER. BRACES SHALL BE CONNECTED TO THE HANGERS/SUPPORTS FOR CONDUIT.3. SEE THE SPECIFICATIONS FOR REQUIRED STRENGTH OF BRACING.4. LATERAL SEISMIC FORCE SHALL BE CONSIDERED TO ACT CONCURRENTLY WITH THE DEAD LOAD. THE SLENDERNESS RATIO (l/r) OF BRACES SHALL NOT EXCEED 200, WHERE (l) IS THE LENGTH OF THE BRACE AND (r) IS THE LEAST RADIUS OF GYRATION, BOTH IN INCHES.

CONDUITS:

1. BRACE ALL 2"� AND LARGER.2. TRANSVERSE AND VERTICAL BRACING SHALL OCCUR AT 40' INTERVALS, MAXIMUM. LONGITUDINAL BRACING SHALL OCCUR AT 80' INTERVALS, MAXIMUM.3. AT RISERS, WHEREVER POSSIBLE, SUPPORT THE WEIGHT OF THE RISER AT A POINT OR POINTS ABOVE THE CENTER OF GRAVITY OF THE RISER.

SLACK 1/8"GAL. STEELAIRCRAFT CABLE

SWIVELCONNECTION

ANCHORED TOSTRUCTURE ABOVE

SEISMIC ANCHOR ANDANCHOR BOLT

(2) SEISMICCABLE BRACES

PER CABLE

2

5 3 17

DESIGNER NOTES:

1. THIS IS BASED ON MASON INDUSTRIES INC. TYPE "SCB" BRACE.

2. REFERENCE SPECIFICATIONS 260025, "VIBRATION AND SEISMIC

CONTROL" FOR ADDITIONAL INFORMATION.

3. USE THIS DETAIL IN CONJUNCTION WITH TRAPEZE MOUNTED

SEISMIC SUPPORT.

46

SS

C J

OB

# 2

016123_B

ID S

ET

- N

OT

FO

R C

ON

ST

RU

CT

ION

Th

e S

ea

l and

Sig

na

ture

app

ly o

nly

to t

he

Do

cum

en

t to

wh

ich t

he

y a

re A

ffix

ed

, an

d E

xpre

ssl

y D

iscla

im a

ny

Re

spo

nsib

ility

fo

r all

oth

er

Pla

ns, S

pe

cifica

tion

s,

Estim

ate

s, R

ep

ort

s, o

r o

the

r D

ocu

men

ts o

r In

str

um

en

tsre

latin

g t

o o

r in

ten

de

d t

o b

e u

se

d f

or

any p

art

or

pa

rts

of

the

Arc

hite

ctu

ral o

r E

ng

ine

erin

g P

roje

ct.

Co

pyrig

ht ©

20

16

by S

SC

En

gin

ee

ring

, In

c.

MISSOURI

5017 Washington Place Suite 200

St. Louis, M0 63108

314.361.0000 ph

314.361.9191 fax

Copyright 2016 HKW Architects

IOWA

1000 Melrose Avenue

Iowa City, IA 52246

319.343.7055 ph

hkwarchitects.com

18207 Edison Avenue

Chesterfield, M0 63005

636.530.7770 ph

636.530.7877 fax

PN

C B

ank

Bid Set

E0.3

PN

C V

alle

y P

ark

16.008.00

April 11, 2016

ELECTRICALDETAILS

912 Meramec Station Road, Valley Park, MO 63021

Revision Schedule

No Date Description

Page 4: ELECTRICAL SYMBOLS LEGEND - REiCON Constructors · 2016-04-12 · pnc bank bid set e0.1 pnc valley park 16.008.00 april 11, 2016 electrical symbols, abbreviations & general notes

D

DDD

OS

OSOS

iO

S

OSOS

jO

S

LV

LCP

J

LV

OS OS OS OS

V

V V V V

SSSS

S ST

S

J

J

J

J

13NL

AE

13NL

AE

13NL

AE

13NL

AE

13NL

AE

13NL

AE

7LCb

A

7LCb

A

7LCb

A

7LCb

A

7LCb

A

7LCb

A

7LCb

A

7LCb

A

9

C

13

CE

11j

B

11j

B

13NL

BE

11j

B

7LCa

B

13NL

BE

7LCa

B

7LCa

B

11i

B

11i

B

7LCa

B

7LCb

B

13NL

BE

7LCa

B

7LCa

B

7LCb

B

13NL

BE

7LCb

B

7LCa

B

13NL

BE

7LCa

B

7LCa

B

13NL

BE

7LCb

B

11

B

11

B

13NL

BE

11

B

7LCa

B

13NL

BE

7LCa

B

9

BE

13NL

BE

7LCa

B

11

B

11

B

11

B

11

B

11

B

11

B

11

B

11

B

7LCb

B

7LCb

B

ATM Vestibule100

13NL

BE

11j

B

11j

B

9

BE

9

BE

13

X1

Concierge102

Off-Stage103

Maintenance104

Elec/Data105

Janitor107

Break Room109

Lobby119

CustomerPantry

113

Self-ServeBoxes

114Coupon Booth

112Toilet108

Toilet106

Office115

Office116

Office117

Office118

1

13

X1

X1 13

2

13

X1

17

3

X2

13

7LCb

DLCc

5

6 6

102B

13

X1

7

8

(TYP.)

8 (TYP.) 8 (TYP.)

4

102B

102A

SS

C J

OB

# 2

016123_B

ID S

ET

- N

OT

FO

R C

ON

ST

RU

CT

ION

Th

e S

ea

l and

Sig

na

ture

app

ly o

nly

to t

he

Do

cum

en

t to

wh

ich t

he

y a

re A

ffix

ed

, an

d E

xpre

ssl

y D

iscla

im a

ny

Re

spo

nsib

ility

fo

r all

oth

er

Pla

ns, S

pe

cifica

tion

s,

Estim

ate

s, R

ep

ort

s, o

r o

the

r D

ocu

men

ts o

r In

str

um

en

tsre

latin

g t

o o

r in

ten

de

d t

o b

e u

se

d f

or

any p

art

or

pa

rts

of

the

Arc

hite

ctu

ral o

r E

ng

ine

erin

g P

roje

ct.

Co

pyrig

ht ©

20

16

by S

SC

En

gin

ee

ring

, In

c.

MISSOURI

5017 Washington Place Suite 200

St. Louis, M0 63108

314.361.0000 ph

314.361.9191 fax

Copyright 2016 HKW Architects

IOWA

1000 Melrose Avenue

Iowa City, IA 52246

319.343.7055 ph

hkwarchitects.com

18207 Edison Avenue

Chesterfield, M0 63005

636.530.7770 ph

636.530.7877 fax

PN

C B

ank

Bid Set

E1.1

PN

C V

alle

y P

ark

16.008.00

April 11, 2016

ELECTRICALLIGHTING PLAN

912 Meramec Station Road, Valley Park, MO 63021

Lighting Fixture Schedule

TypeMark Manufacturer Catalog No. Voltage

Lamp Details

MountingFixtureFinish Remarks (Type) DescriptionLamp Type Lamp

A CREE KR6-13L-35K-120V-10V-RBH*-KR6TA &KR6T-SSGC-WF

120V LED, 3500K INCLUDED RECESSED CLG WHITE GENERAL LTG 6" LED DOWNLIGHT WITH 1100 DELIVERED LUMENS, 0-10V DIMMING, SOFT SATINGLOW REFLECTOR AND WHITE FLANGE/TRIM; C CHANNEL MOUNTINGACCESSORY.

AE CREE KR6-13L-35K-120V-10V-EB7-RBH*-KR6TA &KR6T-SSGC-WF

120V LED, 3500K INCLUDED RECESSED CLG WHITE GENERAL LTG 6" LED DOWNLIGHT WITH 1100 DELIVERED LUMENS, 0-10V DIMMING, SOFT SATINGLOW REFLECTOR AND WHITE FLANGE/TRIM, C-CHANNEL MOUNTING &EMERGNECY BATTERY BALLAST.

B CREE CR22-32L-35K-10V 120V LED, 3500K INCLUDED LAY-IN CLG WHITE GENERAL LTG 2' X 2' RECESSED LED FIXTURE WITH 3200 DELIVERED LUMENS.

BE CREE CR22-32L-35K-10V-EB14 120V LED, 3500K INCLUDED LAY-IN CLG WHITE GENERAL LTG 2' X 2' RECESSED LED FIXTURE WITH 3022 DELIVERED LUMENS AND 1400 LUMENEMERGENCY BATTERY BALLAST

C COOPER 4SNLED-LD4-32HL-LN-UNV-L835-CD-1-U-AYC-CHAIN/SET

120V LED, 3500K INCLUDED SUSPENDED WHITE JANITOR 4' LED STRIP LIGHT WITH 3200 LUMENS AND SEMI-FROST LENS.

CE COOPER 4SNLED-LD4-32HL-LN-UNV-EL14W-L835-CD-1-U-AYC-CHAIN/SET

120V LED, 3500K INCLUDED SUSPENDED WHITE IT/ELEC 4' LED STRIP LIGHT WITH 3200 LUMENS AND SEMI-FROST LENS AND 14WEMERGENCY BATTERY BALLAST.

D SLOAN LED 701269-WWLPY-MB & MULTIPLE POWERSUPPLIES & ALL ACCESSOREIS

120V LED, 4200K INCLUDED MECHANICALFASTNER

WHITE COVE LED MODULES TO BE INSTALLED IN COVE; COORDINATE WITH ARCHITECTURALPLANS AND DETAILS. PROVIDE ONE 60W POWER SUPPLY PER 25' RUN OR ASOTHERWISE REQUIRED BY MFR; PROVIDE ALL REQUIRED MOUNTING ANDCONNECTION ACCESSOREIS; MOUNT POWER SUPPLY ABOVE ACCESSIBALECEILING.

X1 EELP EDGU-1RC-BA-RC-EM-SD 120V LED INCLUDED CEILING - - CEILING MOUNTED SINGLE FACE LED EDGE LIT EXIT SIGN WITH WHITE HOUSING,RED PANEL, BATTERY PACK, AND ARROWS AS INDICATED ON DRAWING.

X2 EELP EDGU-2RW-BA-RC-EM-SD 120V LED INCLUDED CEILING - - CEILING MOUNTED DOUBLE FACE LED EDGE LIT EXIT SIGN WITH WHITEHOUSING, RED PANEL, BATTERY PACK, AND ARROWS AS INDICATED ONDRAWING.

ELECTRICAL KEYED NOTES:

ELECTRICAL GENERAL NOTES:

1. REFER TO SHEET E0.1 FOR SYMBOLS, ABBREVIATIONS AND GENERAL CONSTRUCTION NOTES.2. REFER TO THE ELECTRICAL DETAILS SHEET(S) FOR SEISMIC SUPPORTS OF LIGHTING FIXTURES.3. SUSPENDED CEILING SYSTEMS ARE DESIGNED TO SUPPORT THE WEIGHT OF ALL LIGHTING

FIXTURES. THE STRUCTURAL FRAMING SHALL SUPPORT ALL CONDUITS, JUNCTION BOXES, ETCABOVE CEILINGS.

4. EMERGENCY LIGHTING THAT IS SHOWN TO BE SWITCHED, CONNECT EMERGENCY BALLASTVOLTAGE SENSING LEAD AHEAD OF SWITCH LEG OR OTHER CONTROL DEVICE.

5. INFORMATION ON THIS SHEET IS COMPILED FROM EXISTING DRAWINGS AND CASUAL FIELDOBSERVATIONS AND SHALL BE CONSIDERED APPROXIMATE ONLY. VERIFICATION OF ALLEQUIPMENT AND FIXTURES, EITHER SHOWN OR NOT SHOWN ON THESE PLANS, SHALL BE THERESPONSIBILITY OF THE CONTRACTOR.

6. CONTRACTOR SHALL FIELD VERIFY EXISTING EQUIPMENT AND FIXTURES PRIOR TO STARTINGWORK. NOTIFY ENGINEER IMMEDIATELY IF DISCREPANCIES EXIST.

NORTH

SCALE: 1/8" = 1'-0"

ELECTRICAL LIGHTING PLAN - RENOVATION

NORTH

SCALE: 1/8" = 1'-0"

ELECTRICAL LIGHTING PLAN - DEMOLITION

PROVIDE WATTSTOPPER PEANUT LIGHTING CONTROL PANEL #LP8S-8-115 WITH EIGHT RELAY'S,ASTRONOMICAL TIME CLOCK AND LOW VOLTAGE INPUTS. EC SHALL PROGRAM ACCORDING TOPNC'S REQUEST, ALL LIGHTS SHALL COME ON 1 HOUR PRIOR TO NORMAL BUSINESS HOURS ANDA ALL LIGHTS TO GO OFF 1 HOUR AFTER NORMAL BUSINESS HOURS (OR AS OTHERWISEINDICATED BY PNC.)

PROVIDE LOW VOLTAGE SWITCH EQUAL TO WATTSTOPPER AS-102-W COMPATIBLE WITHLIGHTING CONTROL PANEL. COORDINATE SWITCH FINISH WITH ARCHITECTURAL PLANS. SWITCHSHALL HAVE 2 BUTTONS, TOP BUTTON SHALL TURN ON ALL LIGHTS CONNECTED TOCONTROLLER, BOTTOM BUTTON SHALL TURN OFF ALL LIGHTS CONTROLLED BY CONTROLLER.

PROVIDE CONNECTION TO EXTERIOR SIGN; COORDINATE EXACT LOCATION AND REQUIREMENTSWITH SIGN INSTALLER. CONNECT SIGN WITH DEDICATED CIRCUIT THRU LIGHTING CONTROLLER.PROGRAM WITH ASTRONOMICAL CLOCK TO BE ON AT DUSK AND OFF AT DAWN.

MOUNT POWER SUPPLY TRANSFORMER ABOVE ACCESSIBLE CEILING.

PROVIDE LOW VOLTAGE SWITCH EQUAL TO WATTSTOPPER AS-102-W COMPATIBLE WITHLIGHTING CONTROL PANEL. COORDINATE SWITCH FINISH WITH ARCHITECTURAL PLANS. SWITCHSHALL HAVE 2 BUTTONS, TOP BUTTON SHALL TURN ON ALL EXTERIOR SIGN LIGHTS CONNECTEDTO CONTROLLER, BOTTOM BUTTON SHALL TURN OFF ALL EXTERIOR SIGN LIGHTS CONTROLLEDBY CONTROLLER. PROVIDE PERMANENT LABEL READING 'EXTERIOR SIGN LIGHT OVERRIDE'.

OCCUPANCY SENSOR SHALL ALSO CONTROL EXHAUST FAN IN ROOM.

COORDINATE ROUGH-IN LOCATION WITH T-STAT AND MC.

PROVIDE ROUGH-IN FOR ALL SPEAKERS AND VOLUME CONTROLS. PROVIDE WPW #2524WT OREQUAL #18G/2C TWISTED PLENUM CABLING FOR SPEAKERS. REVIEW EXACT ROUTING ANDCONNECTIONS WITH SPEAKER INSTALLER PRIOR TO WORK.

1

2

3

4

5

6

7

8

Revision Schedule

No Date Description

Page 5: ELECTRICAL SYMBOLS LEGEND - REiCON Constructors · 2016-04-12 · pnc bank bid set e0.1 pnc valley park 16.008.00 april 11, 2016 electrical symbols, abbreviations & general notes

FD

V

F

15

J

J

+46"GFI GFI

GF

I

C

K+6

7"

JJ

J

+67"

AAAA

A

GFI GFI

+4

6"

GFI+24"

GF

IG

FI

+3

4"

+2

6"

LCP

V

F

15

J

T

T

F

DD

DC

DC

K

FD

GFI GFI

V

F

15

V

F

15

J

F

DD

Office115

Office116

Office117

Office118

CustomerPantry

113

Passage111

Self-ServeBoxes

114

Coupon Booth112

Toilet108

Toilet106

Elec/Data105

Janitor107

Maintenance104

Break Room109

Off-Stage103

Concierge102

Lobby119

Cash Room101

ATM Vestibule100

102B

16

18

16

18

16

18

16

20

20

20

2022

26

15

26

15

23

41

39

27

37

8

9

12

12

10

13

14

15

8 8 8

2121

24

102A

8

8

+24" +24"

+67"

+67"+24"

+24"

EF

1

EF

2

EF

3

TV

TV

19

19

25 23 23 2823

10

TGB

18

REQUIRED ELECTRICALCLEARANCE

5

19

41

26

18

9 9

9

22

2240

14

21

EH

1

36,38

23

23

6

FOR ATM; COORDINATE EXACTLOCATIONS WITH ATM INSTALLER.

1135 33 31 29

24

24

24

24

15

15

15

21

2525

25

26TV 41

1

2

2

4

3

27

TV21

28

26

30

8

12

12+46"

+46"

34 32

17

ABV CLG

29

13

30

102B

16

7

19

20

20

20

20

21

6

SS

C J

OB

# 2

016123_B

ID S

ET

- N

OT

FO

R C

ON

ST

RU

CT

ION

Th

e S

ea

l and

Sig

na

ture

app

ly o

nly

to t

he

Do

cum

en

t to

wh

ich t

he

y a

re A

ffix

ed

, an

d E

xpre

ssl

y D

iscla

im a

ny

Re

spo

nsib

ility

fo

r all

oth

er

Pla

ns, S

pe

cifica

tion

s,

Estim

ate

s, R

ep

ort

s, o

r o

the

r D

ocu

men

ts o

r In

str

um

en

tsre

latin

g t

o o

r in

ten

de

d t

o b

e u

se

d f

or

any p

art

or

pa

rts

of

the

Arc

hite

ctu

ral o

r E

ng

ine

erin

g P

roje

ct.

Co

pyrig

ht ©

20

16

by S

SC

En

gin

ee

ring

, In

c.

MISSOURI

5017 Washington Place Suite 200

St. Louis, M0 63108

314.361.0000 ph

314.361.9191 fax

Copyright 2016 HKW Architects

IOWA

1000 Melrose Avenue

Iowa City, IA 52246

319.343.7055 ph

hkwarchitects.com

18207 Edison Avenue

Chesterfield, M0 63005

636.530.7770 ph

636.530.7877 fax

PN

C B

ank

Bid Set

E2.1

PN

C V

alle

y P

ark

16.008.00

April 11, 2016

ELECTRICALPOWER &SYSTEMSPLAN

912 Meramec Station Road, Valley Park, MO 63021

ELECTRICAL GENERAL NOTES:

1. REFER TO SHEET E0.1 FOR SYMBOLS, ABBREVIATIONS AND GENERAL CONSTRUCTION NOTES.2. ALL MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION, AND HVAC WORK SHALL BE

COORDINATED BY THE CONTRACTOR DOING THE WORK. ANY CORRECTIONS TO ANY OF THE ABOVESHALL BE AT THE CONTRACTOR'S EXPENSE.

3. ALL DISCONNECTS REQUIRED SHALL BE PROVIDED BY THE EC, U.N.O. SEE MECHANICAL & PLUMBINGEQUIPMENT SCHEDULE(S) FOR EQUIPMENT DETAILS AND FOR DISCONNECTS FURNISHED BY OTHERS.REFER TO MANUFACTURER'S SPECIFICATIONS FOR MECHANICAL & PLUMBING EQUIPMENTCONNECTION DETAILS. COORDINATE WITH APPLICABLE TRADES.

4. PROVIDE EQUIPMENT GROUNDING CONDUCTOR IN ALL FEEDERS, SIZED IN ACCORDANCE WITH NECARTICLE 250.122, SEE SPECIFICATIONS.

5. REFER TO ELECTRICAL DETAILS SHEET(S) FOR ADDITIONAL PHONE AND DATA REQUIREMENTS.6. INFORMATION ON THIS SHEET IS COMPILED FROM EXISTING DRAWINGS AND CASUAL FIELD

OBSERVATIONS AND SHALL BE CONSIDERED APPROXIMATE ONLY. VERIFICATION OF ALL EQUIPMENTAND DEVICES, EITHER SHOWN OR NOT SHOWN ON THESE PLANS, SHALL BE THE RESPONSIBILITY OFTHE CONTRACTOR.

7. CONTRACTOR SHALL FIELD VERIFY EXISTING EQUIPMENT AND DEVICES PRIOR TO STARTING WORK.NOTIFY ENGINEER IMMEDIATELY IF DISCREPANCIES EXIST.

8. THE FIRE ALARM IS A BUILDING WIDE SYSTEM MAINTAINED BY LANDLORD. EC SHALL PERFORMWORK AS INDICATED. BUT MUST COORDINATE ALL FA WORK WITH LANDLORD.

9. PRIOR TO ANY SAWCUTTING OF THE FLOOR SLAB, CONTRACTOR SHALL XRAY THE FLOOR TO AVOIDHITTING OTHER UTILITIES OR RE-BAR. COORDINATE EXACT ROUTE TO MINIMIZE DISTURBANCE TOFLOOR SLAB. REVIEW AND COORDINATE ALL SAWCUTTING WITH LANDLORD PRIOR TO WORK

ELECTRICAL KEYED NOTES:

NORTH

SCALE: 1/8" = 1'-0"

ELECTRICAL POWER & SYSTEMS PLAN - RENOVATION

NORTH

SCALE: 1/8" = 1'-0"

ELECTRICAL POWER & SYSTEMS PLAN - DEMOLITION

1 CONNECT DOOR CHIME TO BUTTON AT REMOTE ENTRY. PROVIDE NUTONE HARDWIREDDOOR CHIME KIT MODEL BK125WH OR APPROVED EQUAL, (2) DOOR CHIMES, (2)TRANSFORMERS AND LOW VOLTAGE WIRING PER MANUFACTURER'S RECOMMENDATION TOOPERATE BOTH CHIMES FROM A SINGLE BUTTON.

PROVIDE LOW VOLTAGE TRANSFORMER FOR DOOR BELL CHIME SYSTEM AND MOUNTABOVE ACCESSIBLE CEILING.

PROVIDE DUPLEX AND LOW VOLTAGE ROUGH-IN FOR TWO TV'S; TV'S ARE STACKEDVERTICALLY AND OFFSET HORIZONTALLY; REFER TO ARCHITECTURAL DETAILS FOR MOREINFORMATION. IT VENDOR TO PROVIDE DATA CABLES FOR TV AS REQUIRED.

PROVIDE 3/4" CONDUIT TO ALARM PANEL. PROVIDE ADDITIONAL SEALTITE CONDUIT FROMJUNCTION BOX TO SAFE.

IT RACK AND CABLE TRAY BY PNC. COORDINATE WITH PNC DURING CONSTRUCTION TORESERVE ADEQUATE SPACE. PROVIDE #6 COPPER GROUND CONDUCTOR FROM CABLETRAY AND EACH IT RACK TO GROUND BAR.

EXISTING DUCT DETECTOR TO BE PROTECTED AND REMAIN. RE-ROUTE WIRING ASREQUIRED TO ACCOMMODATE NEW WORK.

EXISTING FIRE ALARM DEVICE TO REMAIN. PROTECT DURING CONSTRUCTION.

PROVIDE TWO DEDICATED RECEPTACLES FOR IT RACK; ONE QUAD AND ONE DUPLEX.COORDINATE LOCATION AND TYPE WITH PNC.

PROVIDE DEDICATED RECEPTACLE FOR DIEBOLD. COORDINATE EXACT REQUIREMENTS ANDLOCATION WITH DIEBOLD.

PROVIDE FLOOR BOX EQUAL TO LEGRAND RFB-2-OG WITH COVER; PREPARED WITH DUPLEXRECEPTACLE AND DATA/VOICE OUTLET. SAW CUT FLOOR TO ACCESSIBLE WALL. PROVIDE(1) 1" CONDUIT FOR POWER AND (2) 1-1/4" CONDUIT FOR LOW VOLTAGE, ROUTED TOACCESSIBLE WALL. PROVIDE BRONZE COVER FPBTCBZ. PATCH AND FILL AS REQUIRED.XRAY FLOOR PRIOR TO SAWCUTTING.

PROVIDE (2) CIRCUITS AT EACH NEW TELLER POSITION. FIELD INSTALL TWO RECEPTACLESAND TWO DATA J-BOXES AS SHOWN; COORDINATE EXACT LOCATIONS WITH TELLER STATIONINSTALLER PRIOR TO WORK.

SAW CUT FLOOR AND PROVIDE (1) 1" POWER FEED AND (2) 1-1/4" LOW VOLTAGE FEEDS PERTELLER STATION STUBBED THROUGH WALL CAVITY, BELOW SLAB, AND STUBBED UP ATTELLER CONCIERGE DESK. COORDINATE EXACT LOCATION WITH OWNER'S MILLWORKPROVIDER PRIOR TO SAWCUTTING.

PROVIDE ROUGH-IN FOR SECURITY KEYPAD. KEYPAD TO BE PROVIDED BY OWNER'SSECURITY CONTRACTOR.

DEDICATED RECEPTACLE FOR MFD PRINTER; COORDINATE ELEVATION WITHARCHITECTURAL PLANS.

DEDICATED RECEPTACLE FOR MICR PRINTER; COORDINATE ELEVATION WITHARCHITECTURAL PLANS.

EXISTING ELECTRICAL PANEL TO REMAIN. PANEL IS NOT CONNECTED TO AN ELECTRICALSERVICE; PANEL IS FOR LANDLORDS FUTURE USE ONLY.

PROVIDE CONNECTION TO UNIT HEATER; COORDINATE WITH MC.

PROVIDE 10" X 2" X 1/4" COPPER GROUND BUS FOR GROUNDING OF IT EQUIPMENT. PROVIDEA #6AWG BARE COPPER CONDUCTOR FROM GROUND BUS TO INCOMING ELECTRICALEXISTING GROUNDING SYSTEM.

RELOCATE FIRE ALARM NOTIFICATION APPLIANCE. COORDINATE ALL WORK WITHLANDLORDS FIRE ALARM VENDOR. EXTEND WIRING AS REQUIRED. REMOVE, PROTECT ANDRE-INSTALL AS SHOWN.

REMOVE DEVICE AND WIRING, MAINTAIN ROUGH-IN. RE-CIRCUIT AS INDICATED ONRENOVATION PLAN.

DISCONNECT EXISTING WATER HEATER ABOVE CEILING; MAINTAIN CONDUIT; PROVIDE NEW #10 AWG CONDUCTOR TO PANEL AND NEW BREAKER PER MFR. SPECS., AND CONNECT NEWWATER HEATER.

CONTROL EF WITH LIGHTING OCCUPANCY SENSOR. SEE LIGHTING PLAN.

PROVIDE CONNECTION TO LINE VOLTAGE THERMOSTAT. COORDINATE EXACTREQUIREMENTS WITH TCC & MC.

PROVIDE NEW DEVICE IN EXISTING ROUGH-IN; PROVIDE NEW WIRING AND WALL PLATE;COORDINATE FINISH WITH ARCHITECTURAL PLANS.

COORDINATE ALL ROUGH-IN WORK ALONG PERIMETER WALLS WITH PNC SECURITY ANDWIRE MESH INSTALLER TO MAINTAIN SECURITY OF WIRE MESH BEING INSTALLED.

PROVIDE 4' X 4' FIRE RETARDANT PLYWOOD BACKER BOARD FOR SECURITY CONTRACTOR.LOCATE 5 DUPLEX RECEPTACLES AT BACKER BOARD, COORDINATE EXACT LOCATION OFRECEPTACLES WITH DIEBOLD PRIOR TO WORK.

PROVIDE DUPLEX AND LOW VOLTAGE ROUGH-IN FOR TV ABOVE ATM. ROUGH-IN SHALL BEFROM BEHIND IN CASH ROOM; COORDINATE EXACT ROUGH-IN WITH ARCHITECTURALDETAILS. IT VENDOR TO PROVIDE DATA CABLES FOR TV AS REQUIRED.

PROVIDE DUPLEX AND LOW VOLTAGE ROUGH-IN FOR TV ABOVE TELLER COUNTER;COORDINATE EXACT LOCATION AND ELEVATIONWITH ARCHITECTURAL DETAILS. IT VENDORTO PROVIDE DATA CABLES FOR TV AS REQUIRED.

PROVIDE ALTERNATE PRICING AS OUTLINED ON E0.1.

PROVIDE AND COORDINATE ROUGH-IN IN EXTERIOR WALL FOR EXTERIOR CAMERA.

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

EC SHALL PROVIDE ROUGH-IN'S FOR ALL DATA, VOICE, SOUND, SECURITY, ACCESS CONTROL ANDOTHER LOW VOLTAGE SYSTEMS. LOW VOLTAGE EQUIPMENT HAS BEEN SHOWN FOR REFERENCEONLY; COORDINATE EXACT REQUIREMENTS WITH RESPECTIVE TRADES. REFER TO SECURITASSECURITY DRAWING 'SEC-1' DATED 03/31/16 FOR MORE DETAILS REGARDING SECURITY ROUGH-INREQUIREMENTS. EC SHALL PROVIDE ALL ROUGH-INS; ALL CABLING (OTHER THAN SPEAKER WIRING)WILL BE FURNISHED BY OTHERS. COORDINATE PRIOR TO CEILING AND DRYWALL BEING INSTALLED.

30

Revision Schedule

No Date Description

Page 6: ELECTRICAL SYMBOLS LEGEND - REiCON Constructors · 2016-04-12 · pnc bank bid set e0.1 pnc valley park 16.008.00 april 11, 2016 electrical symbols, abbreviations & general notes

LISTING OFEQUIPMENT AND

SYSTEM COMPONENTS

Not Provided Provided

ANCHORAGE TOFLOORS,

ROOFS, ETC.

ProvidedNot Provided

SWAY BRACING

Drawing No. orSpec. Section

LOCATION OF PROFESSIONALLY SEALEDANCHORAGE

AND SWAY BRACING DETAILS

Shop DrawingsSeparate

Permit & Plans

COMMENTS

ANCHORAGE & SWAY BRACING - MECHANICAL SYSTEM COMPONENTS

Seismic Design Category ( D )Occupancy Category ( II )

PIPING - -BRACE PIPING

AS REQUIRED INNFPA 13 & 14

- -

-

ISOLATORDEFLECTION

YES

SEISMICRESTRAINT

SC

ISOLATIONSPEC.

SPR-PIPING

VIBRATION ISOLATION AND SEISMIC RESTRAINT SCHEDULE

EQUIPMENTTAG

IMPORTANCEFACTOR

MODIFICATIONFACTOR

AMPLIFICATIONFACTOR

COMPONENT

RESPONSE

1.5 2.5 1.0

X X BY FPC

SPR

FIRE PROTECTION SYMBOLS LEGEND

CONNECTION OF NEW TO EXISTING

SPRINKLER PIPING

PENDENT SPRINKLER HEAD

UPRIGHT SPRINKLER HEAD

EXISTING SPRINKLER HEAD

EC ELECTRICAL CONTRACTOR

PC PLUMBING CONTRACTOR

AFF ABOVE FINISHED FLOOR

FIRE PROTECTION CONTRACTORFPC

EXTENDED COVERAGEECV

QUICK RESPONSEQR

STANDARDSTND

UPRIGHTUPR

PENDENTPND

HORIZONTAL SIDEWALLHSW

BRZ BRONZE

GROOVEDGRVD

THREADEDTHR

BOP BOTTOM OF PIPE

GENERAL:NO BRACING IS REQUIRED IF THE TOP OF PIPING IS SUSPENDED 12" OR LESS FROM THESUPPORTING STRUCTURAL MEMBER.

WALLS, INCLUDING DRYWALL PARTITIONS, MAY REPLACE REQUIRED TRANSVERSE ORVERTICAL BRACING FOR PIPING.

ATTACHMENT TO STRUCTURAL MEMBERS SHALL USE DEVICES INCLUDED IN FEDERALSPECIFICATION WW--H-171 (MSS SP-58) OR BE BOLTED/WELDED AS APPROVED BY THEENGINEER. BRACES SHALL BE CONNECTED TO THE HANGERS/SUPPORTS FOR PIPINGAND SUSPENDED EQUIPMENT.

SEE THE SPECIFICATIONS FOR REQUIRED STRENGTH OF BRACING.

LATERAL SEISMIC FORCE SHALL BE CONSIDERED TO ACT CONCURRENTLY WITH THEDEAD LOAD. THE SLENDERNESS RATIO (l/r) OF BRACES SHALL NOT EXCEED 200, WHERE(l) IS THE LENGTH OF THE BRACE AND (r) IS THE LEAST RADIUS OF GYRATION, BOTH ININCHES.

SWAY BRACING METHODS SHOWN IN NFPA 13 (SPRINKLER PIPING) MAY BE USED IN LIEUOF DETAILS SHOWN ON THE DRAWINGS FOR PIPING.

BRACE ALL FIRE SUPPRESSION PIPING.

1.

2.

3.

4.

5.

6.

7.

PIPING:BRACE ALL PIPES 2-1/2"Ø AND LARGER. IN MECHANICAL ROOMS, BRACE ALLPIPING 1-1/4"Ø AND LARGER.

TRANSVERSE AND VERTICAL BRACING SHALL OCCUR AT 40' INTERVALS,MAXIMUM. LONGITUDINAL BRACING SHALL OCCUR AT 80' INTERVALS, MAXIMUM.

AT PIPE RISERS, WHEREVER POSSIBLE, SUPPORT THE WEIGHT OF THE RISERAT A POINT OR POINTS ABOVE THE CENTER OF GRAVITY OF THE RISER.

DO NOT FASTEN ON RIGID PIPING SYSTEM TO TWO DISSIMILAR PARTS OFTHE BUILDING THAT MAY RESPOND IN A DIFFERENT MODE DURING ANEARTHQUAKE; FOR EXAMPLE, A WALL AND A ROOF.

DO NOT USE BRANCH LINES TO BRACE MAIN LINES.

1.

2.

3.

4.

5.

EQUIPMENT:PROVIDE VIBRATION ISOLATORS & SWAY BRACING FOR ALL SUSPENDEDEQUIPMENT.

PROVIDE NEOPRENE WASHER AND PAD FOR ALL PUMPS ANCHORED TOCONCRETE PADS.

1.

2.

LATERAL EARTHQUAKE BRACE FAST CLAMP RISER BRACE

4 WAY EARTHQUAKE BRACE LONGITUDINAL EARTHQUAKE BRACE

NO SCALE NO SCALE

NO SCALE NO SCALE

MIN. 45°-90° TYPICAL

SWIVELSWAYBRACEFITTING (2)

SWAY BRACEATTACHMENT (2)

MIN. 45°-90° TYPICAL

SWIVELSWAYBRACEFITTING

SWAY BRACEATTACHMENT

BRACE PIPE

MIN. 45°-90° TYPICAL

BRACE PIPE

PIPE CLAMP FORSWAY BRACE

NO-THREADSWIVEL SWAYBRACEATTACHMENT

SWAY BRACEATTACHMENT

SWIVELSWAY

BRACEFITTING

MIN. 45°-90°TYPICAL

3" MAX

TOLCO FIGURE 907

ATTACH TO CONCRETE DECK OR STRUCTURAL MEMBERS VIAAPPROVED ATTACHMENT METHOD, ATTACHMENT TO METAL ROOFDECK IS PROHIBITED.

KEYED NOTES:

1

1

LOCK NUT

PROVIDE A SUPPORT ANGLE SPANNING TWO OR MORE JOISTS;3x3x1/4" SUPPORT ANGLE WHERE JOIST SPACING IS OVER 2'-0"BUT NOT MORE THAN 4'-0". PROVIDE 2x2x1/4" SUPPORT ANGLEWHERE JOIST SPACING IS 2'-0" AND UNDER. WHERE LOAD EXCEEDS500 POUNDS PER HANGER, SEE STRUCTURAL DRAWINGS FOR DETAILING.

FIELD WELD STIFFENER TO BAR JOIST TOP AND BOTTOM CHORD.

PROVIDE STIFFENER ANGLE WHERE LOAD BEING HUNG EXCEEDS 250 LBS.

THIS METHOD ALLOWABLE FOR MAX. 150 LB. LOAD WITHIN 6" OF PANELPOINT; BEYOND 6" OF PANEL POINT 50 LB. MAX. LOAD ALLOWABLE.

THIS METHOD ALLOWABLE FOR MAX. 50 LB. LOAD WITHIN 6" OF PANELPOINT; BEYOND 6" OF PANEL POINT THIS METHOD IS NOT ALLOWED.

1

2

3

4

5

1 SUPPORT ANGLE

BOTTOM CHORDOF JOIST

LOCK NUT

LARGEWASHER

BOTTOMCHORD OFJOIST

LARGEWASHER

LOCK NUT

HANGER ROD

4

5

BOTTOM CHORDOF JOIST

RETAININGCLIP

LOCK NUT

"C" CLAMP

LOCK NUT

HANGER ROD

3

1-1/2x1-1/2x3/16"STIFFENER

PANEL POINT

6"6"

B

THIS DETAIL

A

THIS DETAIL

2HANGER ROD

LARGE WASHERLOCK NUT

1/2"Ø BOLT

A

THIS DETAIL

B

THIS DETAIL

SECTION

N.T.S.

SECTION

N.T.S.

1 SUPPORT ANGLE

BOTTOM CHORDOF JOIST

HANGER ROD

LOCK NUT

LARGE WASHER

1/2"Ø BOLT

LOCK NUT

TYPICAL BAR JOIST AND BEAM HANGER ATTACHMENT NOTES:

ADDITIONAL HANGERS SHALL BE REQUIRED TO LIMIT THE LOAD ON EACH STRUCTURALMEMBER BELOW THE MAXIMUM LOAD ALLOWED. COORDINATE WITH STRUCTURAL ENGINEEROF RECORD TO PREVENT OVERLOADING.

WHEN MULTIPLE PIPES/DUCTWORK ARE PERPENDICULAR TO JOISTS, HANGERS SHALL BESTAGGERED SO THAT PIPING/DUCTWORK IS NOT SUPPORTED FROM A SINGLE JOIST.

HANGERS AND SUPPORT COMPONENTS SHALL BE FACTORY FABRICATED OF MATERIALS,DESIGN, AND MANUFACTURER COMPLYING WITH MSS SP-58 AND MSS SP-69 ANDSPECIFICATION 15010. 210010, 220010 OR 230010. COMPLY WITH LOAD RATINGS FOR EACHTYPE.

BEAM CLAMPS SHALL COMPLY WITH MSS TYPE 19-23, 25, 27-34. TYPE 19 AND 23 C-CLAMPSSHALL HAVE LOCKNUTS AND RETAINING DEVICES, FURNISHED BY THE MANUFACTURER.

FOR BUILDINGS WITH JOISTS MADE BEFORE 1985, ALL CLAMPS SHALL BE ATTACHED TO THEUPPER CHORD OF JOISTS.

PROVIDE BEAM CLAMPS WITH RETAINING CLIPS FOR INSTALLATIONS WHERE SEISMICBRACING IS REQUIRED.

HANGERS THAT ARE PART OF A SEISMIC RESTRAINT SHALL BE INSTALLED IN CONTACT WITHTHE PIPE.

SUPPORT ANGLES AND STIFFENERS TO BE SUPPLIED AND INSTALLED BY CONTRACTOR.

1.

2.

3.

4.

5.

6.

7.

8.

THREADED HANGER ROD

CONCENTRICALLY LOADED BAR JOIST - TOP CHORD

CONCENTRICALLY LOADED BAR JOIST - BOTTOM CHORD

NUT

WASHER

TOP CHORD OF JOIST,TYP. 2 MEMBERS

THREADED HANGER ROD

NUT

WASHER

BOTTOM CHORD OF JOIST,TYP. 2 MEMBERS

SPRINKLER HEAD

1'-0"

2'-0"

1'-0

"1

'-0"

2'-0

"

1'-0"

NOTE:ALL PENETRATIONS OF SPRINKLER HEADS IN AN ACCOUSTICAL CEILINGPANEL SHALL BE CENTERED.

4'-0"

1'-0

"1

'-0"

2'-0

"

1'-0" 1'-0" 1'-0" 1'-0"

SPRINKLER HEAD

FIRE PROTECTION BRANCH LINE

RETURNBEND

PENDENTSPRINKLERHEAD

RETURN BENDCONNECTED TOTOP OF BRANCHLINE PIPING, TYP.

DRY PENDENT SPRINKLER HEAD NOTE:DRY BARREL SHALL BE PROVIDED FOR THE ENTIRE LENGTH OF THE DROP PIPINGFROM THE SPRINKLER HEAD TO THE ELBOW AT THE TOP OF THE RETURN BEND.DRY PENDENTS SHALL NOT INCLUDE A DRAIN OUTLET IN DROP PIPING.

SS

C J

OB

# 2

016123_B

ID S

ET

- N

OT

FO

R C

ON

ST

RU

CT

ION

Th

e S

ea

l and

Sig

na

ture

app

ly o

nly

to t

he

Do

cum

en

t to

wh

ich t

he

y a

re A

ffix

ed

, an

d E

xpre

ssl

y D

iscla

im a

ny

Re

spo

nsib

ility

fo

r all

oth

er

Pla

ns, S

pe

cifica

tion

s,

Estim

ate

s, R

ep

ort

s, o

r o

the

r D

ocu

men

ts o

r In

str

um

en

tsre

latin

g t

o o

r in

ten

de

d t

o b

e u

se

d f

or

any p

art

or

pa

rts

of

the

Arc

hite

ctu

ral o

r E

ng

ine

erin

g P

roje

ct.

Co

pyrig

ht ©

20

16

by S

SC

En

gin

ee

ring

, In

c.

MISSOURI

5017 Washington Place Suite 200

St. Louis, M0 63108

314.361.0000 ph

314.361.9191 fax

Copyright 2016 HKW Architects

IOWA

1000 Melrose Avenue

Iowa City, IA 52246

319.343.7055 ph

hkwarchitects.com

18207 Edison Avenue

Chesterfield, M0 63005

636.530.7770 ph

636.530.7877 fax

PN

C B

ank

Bid Set

FP0.1

PN

C V

alle

y P

ark

16.008.00

April 11, 2016

FIREPROTECTIONNOTES &DETAILS

912 Meramec Station Road, Valley Park, MO 63021

FIRE PROTECTION SHEET LIST

Sheet Number Sheet Name

FP0.1 FIRE PROTECTION NOTES & DETAILS

FP1.1 FIRE PROTECTION PLAN

FIRE PROTECTION GENERAL RENOVATION NOTES:1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

THESE DRAWINGS ARE ACCOMPANIED BY SPECIFICATIONS.

THIS CONTRACTOR SHALL COORDINATE WITH OTHER CONTRACTORS IN THE LOCATION OF ALLPIPING AND EQUIPMENT TO PREVENT INTERFERENCE.

PROVIDE ALL NECESSARY OFFSETS IN PIPING TO AVOID STRUCTURE.

IN SPACES WITHOUT CEILINGS PROVIDE ROUGH BRONZE UPRIGHT SPRINKLER HEADS. IN SPACESWITH CEILINGS, REFER TO SPECIFICATIONS FOR SPRINKLER HEAD TYPES. IN DRYWALL CEILINGS,SPRINKLER HEADS SHALL ALIGN WITH LIGHT FIXTURES AND OTHER CEILING MOUNTED DEVICES.CONTRACTOR SHALL COORDINATE SPRINKLER HEAD LOCATIONS WITH ARCHITECT'S REFLECTEDCEILING PLAN, AND PROVIDE ADDITIONAL SPRINKLER HEADS WHERE REQUESTED BY ARCHITECT.

PRIOR TO COMMENCING WORK, APPROVAL SHALL BE RECEIVED FROM THE OWNERS INSURANCECOMPANY, ENGINEER, FIRE MARSHAL AND OWNER.

UPON COMPLETION, THIS CONTRACTOR SHALL PROVIDE A COMPLETE AND FUNCTIONING SYSTEM.

PROVIDE SEISMIC BRACING AS REQUIRED FOR NEW PIPING.

FIRE PROTECTION CONTRACTOR SHALL PERFORM A FLOW TEST. FLOW TEST RESULTS INCLUDINGDATE OF TEST, LOCATION OF TEST HYDRANT, LOCATION OF FLOW HYDRANT, STATIC PRESSURE,RESIDUAL PRESSURE AND TEST FLOW GPM SHALL BE SUBMITTED WITH HYDRAULICCALCULATIONS.

THE FIRE PROTECTION CONTRACTOR SHALL SUBMIT HYDRAULIC CALCULATIONS AND SHOPDRAWINGS SIGNED AND SEALED BY A FIRE PROTECTION ENGINEER REGISTERED IN THE STATEWHERE THE PROJECT IS LOCATED.

CONTRACTOR SHALL PROVIDE ALL DOCUMENTATION AS REQUIRED BY THE AUTHORITY HAVINGJURISDICTION TO DEMONSTRATE COMPLIANCE WITH NFPA 13.

PIPING SHALL BE INSTALLED AS HIGH AS POSSIBLE.

PIPING SHALL BE ROUTED A MINIMUM OF 12" ABOVE CEILING.

WHERE PIPING ELEVATION CONFLICTS WITH DUCTWORK, OFFSETS TO FIRE PROTECTION PIPINGSHALL BE UP AND OVER DUCTWORK. WHERE CONFLICTS OCCUR, PIPING SHALL NOT BE ROUTEDDOWN BELOW DUCTWORK WHERE THIS PIPING WOULD BE WITHIN 12" OF CEILING ELEVATION.

PROVIDE AUXILIARY DRAINS AS REQUIRED FOR DRAINING TRAPPED SECTIONS OF PIPING. FORTRAPPED SECTIONS OF PIPING EXCEEDING 5 GALLONS IN CAPACITY, PROVIDE A HARD-PIPED DRAINCONNECTION AND ROUTE BACK TO DRAIN IN SPRINKLER RISER ROOM.

PIPE ROUTING SHOWN ON DRAWINGS IS FOR REFERENCE ONLY. FIRE PROTECTION CONTRACTORSHALL COORDINATE WITH STRUCTURAL DRAWINGS, ELECTRICAL AND MECHANICAL DRAWINGSFOR LOCATIONS AND ELEVATIONS OF PIPING. NO CHANGE TO THE CONTRACT PRICE WILL BEACCEPTED WHERE ALTERNATE PIPING ROUTES ARE REQUIRED.

CONTRACTOR SHALL PROVIDE A FIRE WATCH DURING CONSTRUCTION HOURS. COORDINATE WITHLOCAL FIRE DEPARTMENT FIRE WATCH REQUIREMENTS. OBTAIN A FIRE WATCH INSPECTIONFORM AND LOG INSPECTION TIME PER FIRE DEPARTMENT'S REQUIREMENTS.

FIRE PROTECTION SYSTEM DELEGATED-DESIGN NOTE:THE FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR DESIGNING ANDPROVIDING AN AUTOMATIC SPRINKLER SYSTEM BASED ON NFPA 13 REQUIREMENTS, THEAVAILABLE WATER FLOW AND PRESSURE AT THE SITE, AND IBC REQUIREMENTS FOR AFULLY SPRINKLERED BUILDING. ALL OCCUPIED AREAS SHALL BE SERVED BY WET-PIPEAUTOMATIC FIRE PROTECTION SYSTEMS. CONTRACTOR SHALL DESIGN ALL PIPE ROUTING,COORDINATE WITH STRUCTURAL ELEMENTS AND DETERMINE SPRINKLER HEADLOCATIONS AND QUANTITIES REQUIRED. SPRINKLER HEAD LOCATIONS AND PIPINGROUTING ARE SHOWN FOR REFERENCE ONLY, AS AN AID TO BIDDING AND ARCHITECTURALCOORDINATION. THE FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FORPERFORMING A FLOW TEST, PROVIDING ENGINEERED SHOP DRAWINGS AND HYDRAULICCALCULATIONS SIGNED AND SEALED BY A REGISTERED PROFESSIONAL ENGINEER IN THESTATE WHERE THE PROJECT IS LOCATED, AND DESIGNING, SIZING AND INSTALLING ALLPIPING, VALVES, SPRINKLERS, ETC. REQUIRED FOR A COMPLETE, FUNCTIONAL AND CODECOMPLIANT SYSTEM.

FIRE PROTECTION GENERAL DEMOLITION NOTES:1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

SEE THIS SHEET FOR SYMBOLS AND ABBREVIATIONS.

THESE GENERAL DEMOLITION NOTES APPLY TO ALL DEMOLITION WORK.

DEMOLISH PIPING AND EQUIPMENT SHOWN CROSS HATCHED.

THESE DRAWINGS MAY NOT FULLY DEPICT ALL AS-BUILT CONDITIONS, CONTRACTOR SHALLFIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING BIDS. NOTIFY THE ENGINEER ATONCE SHOULD A DISCREPANCY OR OMISSION BE FOUND.

CONTRACTOR SHALL USE CAUTION WHEN REMOVING PIPING AND EQUIPMENT TO AVOID DAMAGETO ELECTRICAL WIRING THAT IS TO REMAIN. NOTIFY GC AND EC IF WIRING IS FOUND ATTACHEDTO PIPING.

WHEREVER EXISTING EQUIPMENT, PIPING AND EQUIPMENT, ETC., ARE TO BE REMOVED, SUCHREMOVAL SHALL INCLUDE ALL ANCHORS, HANGERS, FOUNDATIONS, ETC., UNLESS NOTEDOTHERWISE. AFTER REMOVAL; FLOORS, WALLS AND CEILINGS SHALL BE PATCHED ANDFINISHED TO MATCH ADJOINING SURFACES.

WHERE ITEMS ARE REMOVED, UTILITIES AND THE AREA FROM WHICH THE ITEMS HAVE BEENREMOVED SHALL BE LEFT IN SUCH A MANNER THAT IS SAFE FOR BOTH PEOPLE AND PROPERTYON A DAILY BASIS.

SEE ARCHITECTURAL DRAWINGS FOR ARCHITECTURAL DEMOLITION. REFER TO MEP ANDSPRINKLER DEMOLITION PLANS FOR MEP DEMOLITION.

SPRINKLER DEMOLITION WORK: VERIFY EXISTING SERVICES TO REMAIN. ALL NECESSARY CARESHALL BE TAKEN DURING DEMOLITION TO PREVENT DAMAGE TO FIRE PROTECTION, PLUMBING,ELECTRICAL, AND MECHANICAL SYSTEMS TO REMAIN. FIRE PROTECTION SYSTEMS SERVINGOTHER AREAS SHALL PROVIDE FOR UNINTERRUPTED SERVICE TO THOSE AREAS UNLESS PRIORWRITTEN APPROVAL IS RECEIVED FROM THE OWNER. COORDINATE ALL SUCH WORK WITH THEGENERAL CONTRACTOR AND OWNER'S ON SITE REPRESENTATIVE.

THE OWNER WILL BE RESPONSIBLE FOR THE REMOVAL OF ANY ACMs (ASBESTOS CONTAININGMATERIALS, PCBs OR OTHER HAZARDOUS MATERIALS) PRESENTLY EXISTING WITHIN THEAREAS AFFECTED BY THE PROJECT SCOPE, THAT WOULD BE REQUIRED TO BE REMOVED FORTHE WORK. ABATEMENT WORK, IF REQUIRED, IS NOT PART OF THIS CONTRACT.

NOT TO SCALE

SEISMIC BRACING DETAILS AND NOTES

NOT TO SCALE

TYPICAL JOIST HANGER DETAIL FOR PIPING AND EQUIPMENT

NOT TO SCALE

TYPICAL BAR JOIST & BEAM HANGER NOTES

NOT TO SCALE

CONCENTRICALLY LOADED JOIST ATTACHMENT DETAIL

NOT TO SCALE

CEILING PANEL PENETRATION DETAIL

NOT TO SCALE

RETURN BEND PIPING TO WET AND DRY PENDENTS

Revision Schedule

No Date Description

Page 7: ELECTRICAL SYMBOLS LEGEND - REiCON Constructors · 2016-04-12 · pnc bank bid set e0.1 pnc valley park 16.008.00 april 11, 2016 electrical symbols, abbreviations & general notes

4

Lobby

ATM Vestibule Concierge

Office Office Office Office

Self-ServeBoxes

CustomerPantry

Passage

ToiletCoupon Booth

Toilet

Elec/DataJanitor

Maintenance

Break Room

Off-Stage

1 1 1 1

2

2 2

3

2 2

SPRSPRSPR

EXISTING FPSERVICE MAIN

EXISTING 2-1/2" RISER5

MAIN@ 14'-2" AFF

SS

C J

OB

# 2

016123_B

ID S

ET

- N

OT

FO

R C

ON

ST

RU

CT

ION

Th

e S

ea

l and

Sig

na

ture

app

ly o

nly

to t

he

Do

cum

en

t to

wh

ich t

he

y a

re A

ffix

ed

, an

d E

xpre

ssl

y D

iscla

im a

ny

Re

spo

nsib

ility

fo

r all

oth

er

Pla

ns, S

pe

cifica

tion

s,

Estim

ate

s, R

ep

ort

s, o

r o

the

r D

ocu

men

ts o

r In

str

um

en

tsre

latin

g t

o o

r in

ten

de

d t

o b

e u

se

d f

or

any p

art

or

pa

rts

of

the

Arc

hite

ctu

ral o

r E

ng

ine

erin

g P

roje

ct.

Co

pyrig

ht ©

20

16

by S

SC

En

gin

ee

ring

, In

c.

MISSOURI

5017 Washington Place Suite 200

St. Louis, M0 63108

314.361.0000 ph

314.361.9191 fax

Copyright 2016 HKW Architects

IOWA

1000 Melrose Avenue

Iowa City, IA 52246

319.343.7055 ph

hkwarchitects.com

18207 Edison Avenue

Chesterfield, M0 63005

636.530.7770 ph

636.530.7877 fax

PN

C B

ank

Bid Set

FP1.1

PN

C V

alle

y P

ark

16.008.00

April 11, 2016

FIREPROTECTION

PLAN

912 Meramec Station Road, Valley Park, MO 63021

NORTH

SCALE: 1/8" = 1'-0"

FIRE PROTECTION FLOOR PLAN - RENOVATION

1

FIRE PROTECTION GENERAL NOTES:

1.

2.

3.

REFER TO SHEET FP0.1 FOR SYMBOLS, ABBREVIATIONS AND GENERAL CONSTRUCTION NOTES.

ADJACENT TENANT SPACE NOT IN SCOPE.

ITEMS SHOWN CROSS HATCHED TO BE REMOVED.

FIRE PROTECTION KEYED NOTES:

REMOVE SPRINKLER HEADS AND BRANCH PIPING BACK TO MAIN.

REMOVE EXISTING SPRINKLER HEAD WITHIN SPACE AND PLUG OUTLET. BRANCH PIPING TOREMAIN TO SERVE ADJACENT TENANT SPACE.

EXISTING 2 1/2" CROSS-MAIN AT APPROXIMATELY 14'-2" AFF TO REMAIN.

PROVIDE THE DESIGN AND INSTALLATION OF A COMPLETE AND FUNCTIONAL AUTOMATIC FIREPROTECTION SYSTEM IN THE AREA INDICATED. FIRE PROTECTION SYSTEM(S) SHALL BEDESIGNED PER NFPA 13 AND IBC REQUIREMENTS FOR A FULLY SPRINKLER BUILDING. PROVIDEALL SPRINKLER HEADS, PIPING, HANGERS, ETC. AND COORDINATE LOCATIONS, PIPE ROUTING,SCHEDULING, AND ALL OTHER INSTALLATION REQUIREMENTS WITH OTHER TRADES. EXTENDNEW BRANCH LINES FROM EXISTING CROSS-MAIN OUTLETS. WHERE CROSS MAIN OUTLETS ARENOT OF SUFFFICIENT QUANTITY PROVIDE A MECHANICAL TEE, TAP EXISTING SUPPLY MAIN ANDPROVIDE ADDITIONAL BRANCH LINE(S).

TO EXISTING VERTICAL BACKFLOW PREVENTER AND SYSTEM RISER.

NORTH

SCALE: 1/8" = 1'-0"

FIRE PROTECTION FLOOR PLAN - DEMOLITION

2

3

4

5

Revision Schedule

No Date Description

Page 8: ELECTRICAL SYMBOLS LEGEND - REiCON Constructors · 2016-04-12 · pnc bank bid set e0.1 pnc valley park 16.008.00 april 11, 2016 electrical symbols, abbreviations & general notes

LISTING OFEQUIPMENT AND

SYSTEM COMPONENTS

Not Provided Provided

ANCHORAGE TOFLOORS,

ROOFS, ETC.

ProvidedNot Provided

SWAY BRACING

Drawing No. orSpec. Section

LOCATION OF PROFESSIONALLY SEALEDANCHORAGE

AND SWAY BRACING DETAILS

Shop DrawingsSeparate

Permit & Plans

COMMENTS

Anchorage & Sway Bracing - Mechanical & Plumbing System Components

Seismic Design Category ( D )Seismic Use Group ( II )

EH-1

DUCTWORK

X

X

X

X

EF-1 (EXHAUST FAN)

X X

AIR DEVICES

12

4

12

2X

TABLE 4.4, ITEM 1, A, EXCEPTION FOR 3 FEET MINIMUM OF FLEX CONNECTION BETWEEN COMPONENTS, MOUNTED 4 FEET OR LESSABOVE THE FLOOR LEVEL AND WEIGHS 400 POUNDS OR LESS.TABLE 4.4, ITEM 1, B, EXCEPTION FOR 3 FEET MINIMUM OF FLEX CONNECTION BETWEEN COMPONENTS AND WEIGHS 20 POUNDS OR LESS.TABLE 4.4, ITEM 1, B, EXCEPTION FOR LESS THAN 5LB/FT (COPPER PIPING - 2-1/2" OR LESS, SCHEDULE 40 AND 80 CPVC - 3" OR LESS). 3 FOOT FLEXCONNECTIONS FOR SUSPENDED EQUIPMENT.TABLE 4.4, ITEM 3, EXCEPTION FOR DUCTWORK "A" (OR "B"). REFER TO INSTALLATION DETAIL ON DRAWING #__.TABLE 4.4, ITEM 4, EXCEPTION FOR PIPING SUSPENDED FROM HANGERS 12 INCHES OR LESS. REFER TO INSTALLATION DETAIL ON DRAWING #__.TABLE 4.4, ITEM 4, EXCEPTION FOR DUCTILE PIPING 1" OR LESS (SEISMIC DESIGN CATEGORY D).DUCTILE PIPING, STEEL, COPPER PIPING AND TUBING JOINED BY WELDING, BRAZING/SOLDERING OR FLANGES. REFER TO TABLE 4.4, ITEM 4.TABLE 4.4, ITEM 4, EXCEPTION FOR DUCTILE PIPING 3" OR LESS (SEISMIC DESIGN CATEGORY D).TABLE 4.4, ITEM 5, EXCEPTION FOR EXTERIOR GAS PIPING ON ROOF, 2 PSI OR LESS: SEISMIC SHUT-OFF VALVE OR FLEX CONNECTORS WITHIN 5 FEETOF THE BEGINNING OF THE RUN, AT CONNECTIONS TO EQUIPMENT AND AT 42 FOOT OR LESS INTERVALS.COMPONENTS SHALL BE POSITIVELY ATTACHED WITH MECHANICAL FASTENERS.SEISMIC CALCULATIONS ARE ATTACHED TO SET OF DRAWINGS.CONTRACTOR SHALL PROVIDE SHOP DRAWINGS TO THE ENGINEER OF RECORD FOR REVIEW AND APPROVAL PRIOR TO SUBMITTAL TO THE PLANREVIEWER.TYPICAL SEISMIC ANCHORAGE (OR SWAY BRACING) IS PROVIDED ON THE DRAWINGS FOR REFERENCE ONLY. SHOP DRAWINGS ARE REQUIRED.

X X

X

1.

2.

3.

4.

5.6.7.8.

9.

10.11.12.13.

H

T

TDD SD

R

X

EQUIPMENT IDENTIFICATION

S - SUPPLYR - RETURNE - EXHAUST

D

CFM

AIR DEVICE TAG

DRAIN

24 X 12

24 X 12

OR

X' - X"

18x12 12x12

18x12 12x12

M

A

EJ

MECHANICAL SYMBOLS LEGEND

M

RG REFRIGERANT HOT GAS

REFRIGERANT LIQUIDRL

REFRIGERANT SUCTIONRS

HOT WATER HEATING SUPPLYHWS

HWR HOT WATER HEATING RETURN

PIPE ANCHOR

CA COMPRESSED AIR

NATURAL GASG

LIQUID PROPANE GASLPG

CHILLED WATER SUPPLYCWS

CHILLED WATER RETURNCWR

CHILLED WATER SUPPLYCHS

CHILLED WATER RETURNCHR

CONDENSER WATER SUPPLYCS

CONDENSER WATER RETURNCR

LOW PRESSURE STEAMLPS

MEDIUM PRESSURE STEAMMPS

HIGH PRESSURE STEAMHPS

LOW PRESSURE CONDENSATELPC

MEDIUM PRESSURE CONDENSATEMPC

HIGH PRESSURE CONDENSATEHPC

PD STEAM CONDENSATE PUMPED DISCHARGE

LOOP WATER SUPPLYLWS

LWR LOOP WATER RETURN

DEMO PIPE OR EQUIPMENT

POINT OF CONNECTION NEW TO EXISTING

OPPOSED BLADE DAMPER

HUMIDISTAT

THERMOSTAT

SMOKE DETECTOR (DUCT)

FLOW SWITCH

DIFFERENTIAL PRESSURE SWITCH

PRESSURE SWITCH

BOTTOM OF DUCT ELEVATION

RECTANGULAR DUCT (FIRST NUMBER IS SURFACE

SHOWN-DIMENSIONS REPRESENT NET FREE AREA)

OR

12"Ø

12"Ø

ROUND DUCT

RECTANGULAR TO ROUND TRANSITION

TRANSITION

DUCT WITH LINER

INCLINED RISE (R) OR DROP (D) ARROW IN DIRECTION OF CHANGE

FLEXIBLE DUCT CONNECTION

SUPPLY AIR UP OR IN SECTION

RETURN,EXHAUST OR OUTSIDE AIR UP OR IN SECTION

SUPPLY AIR DOWN OR AWAY

RETURN,EXHAUST OR OUTSIDE AIR DOWN OR AWAY

RECTANGULAR ELBOW WITH TURNING VANES

VOLUME DAMPER

MOTORIZED DAMPER

FIRE DAMPER/SMOKE DAMPER/COMB. FIRE SMOKE DAMPER

SPIN-IN FITTING WITH DAMPER (SIDE)

MECHANICAL SYMBOLS LEGEND (CONT.)

ROUND TAP WITH DAMPER (BOTTOM)

AIR DIFFUSER 4-WAY UNLESS OTHERWISE INDICATEDCEILING MOUNTED, SQUARE SUPPLY

(ARROW INDICATES DIRECTION OF THROW)

CEILING MOUNTED RETURN AIR GRILLE

SIDEWALL RETURN GRILLE

SIDEWALL SUPPLY DIFFUSER

FLOW DIRECTION

RECTANGULAR TAP WITH DAMPER (BOTTOM)

ROUND DUCT SUPPLY UP, DN OR IN SECTION

ROUND DUCT RETURN UP, DN OR IN SECTION

PIPE UP

PIPE DOWN

TOP CONNECTION

BOTTOM CONNECTION

SUPPLY AIR SLOT DIFFUSER

MANUAL AIR VENT

AUTOMATIC AIR VENT

THERMOWELL

PRESSURE GAUGE

MANIFOLD GAUGE

THERMOMETER

CAPPED OUTLET (UP)

DIRT LEG (DN)

UNION

PIPE GUIDE

STEAM TRAP

EXPANSION JOINT

REDUCER

BASKET STRAINER

SUCTION DIFFUSER

STRAINER

GATE VALVE

BALL VALVE

TRIPLE DUTY VALVE

BUTTERFLY VALVE

PRESSURE REDUCING VALVE

CHECK VALVE

GAS COCK

BALANCING VALVE (FLOW CONTROL VALVE)

RPBP - REDUCED PRESSURE BACKFLOW PREVENTER

DRAIN VALVE W/HOSE THREADED CONN.

PRESSURE RELIEF VALVE

3-WAY AUTOMATIC CONTROL VALVE

2-WAY AUTOMATIC CONTROL VALVE

MOTORIZED VALVE

ANGLE VALVE

THERMAL EXPANSION VALVE

TEMPERATURE/PRESSURE TEST PLUG

1AHU

#S1

FS

DPS

PS

SVSOLENOID VALVE

PNEUMATIC TUBING

ELECTRICAL WIRING

P

E

SS

C J

OB

# 2

016123_B

ID S

ET

- N

OT

FO

R C

ON

ST

RU

CT

ION

Th

e S

ea

l and

Sig

na

ture

app

ly o

nly

to t

he

Do

cum

en

t to

wh

ich t

he

y a

re A

ffix

ed

, an

d E

xpre

ssl

y D

iscla

im a

ny

Re

spo

nsib

ility

fo

r all

oth

er

Pla

ns, S

pe

cifica

tion

s,

Estim

ate

s, R

ep

ort

s, o

r o

the

r D

ocu

men

ts o

r In

str

um

en

tsre

latin

g t

o o

r in

ten

de

d t

o b

e u

se

d f

or

any p

art

or

pa

rts

of

the

Arc

hite

ctu

ral o

r E

ng

ine

erin

g P

roje

ct.

Co

pyrig

ht ©

20

16

by S

SC

En

gin

ee

ring

, In

c.

MISSOURI

5017 Washington Place Suite 200

St. Louis, M0 63108

314.361.0000 ph

314.361.9191 fax

Copyright 2016 HKW Architects

IOWA

1000 Melrose Avenue

Iowa City, IA 52246

319.343.7055 ph

hkwarchitects.com

18207 Edison Avenue

Chesterfield, M0 63005

636.530.7770 ph

636.530.7877 fax

PN

C B

ank

Bid Set

M0.1

PN

C V

alle

y P

ark

16.008.00

April 11, 2016

MECHANICALSYMBOLS,

ABBREVIATIONS& GENERALNOTES

912 Meramec Station Road, Valley Park, MO 63021

MECHANICAL GENERAL RENOVATION NOTES:1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

SEE THIS SHEET FOR SYMBOLS AND ABBREVIATIONS.

THESE GENERAL NOTES APPLY TO ALL WORK.

DUCT SIZES SHOWN ARE SHEET METAL SIZE AND INCLUDE THE DUCT LINER WHERE LINER IS REQUIRED.

ALL SUPPLY, RETURN, EXHAUST, AND TRANSFER REGISTERS IN ROOMS WITHOUT CEILINGS SHALL BE 9'-0"AFF UNLESS NOTED OTHERWISE.

REFER TO THE ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION OF CEILING AIR DEVICES.

MAINTAIN 10'-0" MINIMUM BETWEEN OUTSIDE AIR INTAKES AND ALL EXHAUST FANS, FLUES, PLUMBINGVENTS, ETC.

ALL DUCT RUN OUTS TO AIR DEVICES SHALL HAVE A DAMPER WITH A LOCKING QUADRANT IN ADDITION TOTHE DAMPER IN THE NECK OF THE AIR DEVICE.

CONTRACTOR SHALL COORDINATE WITH OTHER TRADES TO PREVENT THE INSTALLATION OF CONDUITS,PIPING, LIGHTING, OR OTHER OBSTRUCTIONS UNDER OR ADJACENT TO HVAC EQUIPMENT THATOBSTRUCTS ACCESS TO COILS, MOTORS, VALVES, FILTERS, ETC., OR OTHER HVAC COMPONENTS NEEDINGMAINTENANCE OR OPERATIONS ACCESS.

FLEXIBLE DUCT LENGTH SHALL NOT EXCEED 3'-0".

ALL EXPOSED DUCTS SHALL HAVE PAINT GRIP FINISH FOR PAINTING BY GC. COLOR PER ARCHITECT.

THERMOSTATS AND ROOM TEMPERATURE SENSORS SHALL BE MOUNTED AT 4'-0" TO THE TOP OF THEJUNCTION BOX THAT THE DEVICE IS MOUNTED ON.

COORDINATE DUCTWORK WITH ALL SPRINKLER AND PLUMBING PIPING BEFORE COMMENCEMENT OFWORK.

MAINTAIN MINIMUM OF 4'-0" BETWEEN BRANCH TAKE OFFS.

LOCATIONS OF NEW EQUIPMENT, DUCTWORK, PIPING, AND ASSOCIATED ITEMS SHOWN ON THE DRAWINGSARE SCHEMATIC. CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION AND ELEVATION OF ALL WORK.PROVIDE OFFSETS, FITTINGS, TRANSITIONS, EXTENSIONS, ETC., REQUIRED FOR A COMPLETE SYSTEM.

NO CHANGES IN CONTRACT PRICE WILL BE ALLOWED FOR MINOR CHANGES IN LAYOUT OR LOCATIONREQUIRED TO AVOID INTERFERENCES, OBSTRUCTIONS, ETC. CONTRACT PRICE CHANGES WILL BECONSIDERED ONLY FOR CHANGES IN THE SCOPE OF THE PROJECT REQUIREMENTS. ALL SUCH SCOPECHANGES AND PRICE REVISIONS MUST BE AUTHORIZED IN WRITING. NOTIFY THE ENGINEER AT ONCESHOULD A DISCREPANCY OR OMISSION BE FOUND.

ALL UTILITIES SERVING EXISTING AREAS SHALL REMAIN IN SERVICE AT ALL TIMES EXCEPT FOR SHORTPERIODS OF INTERRUPTION FOR TIE IN OF NEW SERVICES TO EXISTING. ALL INTERRUPTIONS SHALL BESCHEDULED WITH OWNER AND SHALL NOT BE SCHEDULED UNTIL NEW SERVICES ARE COMPLETE ANDREADY FOR FINAL CONNECTION.

AIR DEVICES SHALL BE SIZED TO MATCH THE CEILING GRID. FURNISH AIR DEVICES FOR EITHER REGULARGRID CEILINGS OF FOR NARROW GRID CEILINGS OR FOR BOTH TYPES OF GRID; COORDINATE WITH THEARCHITECTURAL REFLECTED CEILING PLANS.

PROVIDE SUPPLEMENTAL "TEES" FOR THE CEILING GRID WHERE DIFFUSERS ARE A DIFFERENT SIZE THANTHE CEILING TILES.

WHERE INSULATION CONTAINING HAZARDOUS MATERIALS HAS BEEN REMOVED FROM DUCTWORK, PIPING,OR EQUIPMENT, REPLACE IT WITH NEW INSULATION. SEE SPECIFICATIONS FOR TYPE AND THICKNESS.

GENERALLY PROVIDE DUCT INSULATION FOR SUPPLY, RETURN AND OUTSIDE AIR DUCTS ABOVE CEILINGS.SEE DETAILS AND DUCT INSULATION SCHEDULE ON PLANS FOR ADDITIONAL REQUIREMENTS. SEE SPECS230900 AND 230200 FOR A MORE DETAILED DESCRIPTION OF LINING AND INSULATION REQUIREMENTS.

ALL DUCTS SHALL BE 2" WG PRESSURE CLASS.

MECHANICAL GENERAL DEMOLITION NOTES:1.

2.

3.

4.

5.

6.

7.

8.

9.

SEE THIS SHEET FOR SYMBOLS AND ABBREVIATIONS.

THESE GENERAL NOTES APPLY TO ALL DEMOLITION WORK.

REMOVE DUCTS AND EQUIPMENT SHOWN CROSS HATCHED OR DASHED.

CONTRACTOR SHALL USE CAUTION WHEN REMOVING DUCTS TO AVOID DAMAGE TO ELECTRICALWIRING THAT IS TO REMAIN. NOTIFY GC AND EC IF WIRING IS FOUND ATTACHED TO DUCTWORK.

WHEREVER EXISTING EQUIPMENT, PIPING, DUCTS, ETC., ARE TO BE REMOVED, SUCH REMOVALSHALL INCLUDE ALL ANCHORS, HANGERS, FOUNDATIONS, ETC., UNLESS NOTED OTHERWISE.AFTER REMOVAL; FLOORS, WALLS AND CEILINGS SHALL BE PATCHED AND FINISHED TO MATCHADJOINING SURFACES.

WHERE ITEMS ARE REMOVED, UTILITIES AND THE AREA FROM WHICH THE ITEMS HAVE BEENREMOVED SHALL BE LEFT IN SUCH A MANNER THAT IS SAFE FOR BOTH PEOPLE AND PROPERTY ONA DAILY BASIS.

THESE DRAWINGS MAY NOT FULLY DEPICT ALL AS-BUILT CONDITIONS, CONTRACTOR SHALL FIELDVERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING BIDS. NOTIFY THE ENGINEER AT ONCESHOULD A DISCREPANCY OR OMISSION BE FOUND.

SEE ARCHITECTURAL DRAWINGS FOR ARCHITECTURAL DEMOLITION. REFER TO MEP ANDSPRINKLER DEMOLITION PLANS FOR MEP AND SPRINKLER DEMOLITION.

THE OWNER WILL BE RESPONSIBLE FOR THE REMOVAL OF ANY ACMs (ASBESTOS CONTAININGMATERIALS, PCBs OR OTHER HAZARDOUS MATERIALS) PRESENTLY EXISTING WITHIN THE AREASAFFECTED BY THE PROJECT SCOPE, THAT WOULD BE REQUIRED TO BE REMOVED FOR THE WORK.ABATEMENT WORK, IF REQUIRED, IS NOT PART OF THIS CONTRACT.

MECHANICAL SHEET LIST

Sheet Number Sheet Name

M0.1 MECHANICAL SYMBOLS, ABBREVIATIONS & GENERAL NOTES

M0.2 MECHANICAL SCHEDULES & DETAILS

M1.1 MECHANICAL DUCTWORK PLAN

INVERT ELEVATIONINCHESINSTALLEDINFRA-RED HEATERLEAVING AIR TEMPERATURELEAVING DRY BULB TEMPERATURELEAVING WET BULB TEMPERATURELEAVING WATER TEMPERATURELOCKED ROTOR AMPSLIQUID PROPANE GASLOW WATER CUT-OFFMAKE-UP AIR UNITMAXIMUM1000 BTU/HRMECHANICAL CONTRACTORMOTOR CONTROL CENTERMOTORIZED DAMPERMINIMUMMOP SERVICE BASINMIXING VALVENORMALLY OPENNORMALLY CLOSEDNUMBERNON-FUSEDNOT TO SCALEOUTSIDE AIROPEN END DUCTOUTLET VELOCITYPUMPPLUMBING CONTRACTORPOINT OF CONNECTIONPOWER INDUCTION BOXPRESSURE DROPPOLYVINYL CHLORIDERETURN AIRRETURN AIR DEVICEROOF DRAINRELIEF FANREVOLUTIONS PER MINUTERECIRCULATING PUMPREDUCED PRESSURE BACK FLOW PREVENTERROOF TOP UNITRELIEF VALVESUPPLY AIR DEVICESUPPLY AIRSMOKE DAMPERSUPPLY FANSWITCHSTEELSIGHT GLASSSTATIC PRESSURESPRINKLER CONTRACTORSOLENOID VALVETEMPERATURE CONTROLLERTRIPLE DUTY VALVETRANSFER GRILLETRANSFER FANTAMPER SWITCHTOTAL STATIC PRESSURETHERMAL EXPANSION VALVEUNIT HEATER (HYDRONIC)URINALVENTVARIABLE AIR VOLUME BOXVOLUME DAMPERVARIABLE FREQUENCY DRIVEVENT THRU ROOFWET BULB TEMPERATUREWATER PRESSURE DROP(FT. H20)WATER COLUMNZONE DAMPER

IEININSTIRHLATLDBLWBLWTLRALPGLWCOMAUMAXMBHMCMCCMDMINMSBMVNONCNO.NFNTSOAOEDOVPPCPOCPIBPDPVCRAR-#RDRFRPMRPRPBPRTURVS-#SASDSFSWSTLSGSPSPCSVTCTDVTTFTSTSPTXVUHURVVAVVDVFDVTRWBWPDW.C.ZD

AIR COOLED CONDENSERAIR CONDITIONING UNITADJUSTABLEABOVE FINISHED FLOORAIR HANDLING UNITACCESS PANELAIR PRESSURE DROP(IN WC)AIR SEPARATORBOILERAIR BLENDERBACKDRAFT DAMPERBRAKE HORSEPOWERBRITISH THERMAL UNITSBOTTOM OF DUCTBOTTOM OF PIPEBOTTOM OF STEELBACKWATER VALVECAPACITYCENTER TO CENTERCUBIC FEET PER MINUTECHILLERCHILLED WATER RETURNCHILLED WATER SUPPLYCAST IRONCENTER LINECEILINGCLEANOUTCONNECTIONCHLORINATED POLYVINYL CHLORIDECONDENSER WATER RETURNCONDENSER WATER SUPPLYCONDENSING UNITCABINET UNIT HEATERCONTROL VALVEDRAINDIAMETERDRY BULB TEMPERATUREDISCONNECTDOWNDOWNSPOUTDISHWASHERDUCT SMOKE DETECTOR SUPPLYDUCT SMOKE DETECTOR RETURNEXHAUST AIR DEVICEEXHAUST AIRENTERING AIR TEMPERATUREENTERING DRY BULB TEMPERATUREENTERING WET BULB TEMPERATUREENTERING WATER TEMPERATUREEFFICIENCYEXPANSION TANKELECTRIC CABINET HEATEREXHAUST FANELECTRICAL CONTRACTORENERGY MANAGEMENT SYSTEMEXTERNAL STATIC PRESSUREEMERGENCY SHUT-OFF VALVEELECTRIC UNIT HEATERELECTRIC WATER HEATEREXISTINGEXHAUSTFRESH AIRFAN COIL UNITFLOOR DRAINFLOOR HYDRANTFILTER DRIERFINISHFLOORFACTORY MOUNTEDFEET PER MINUTEFEETFURNISHEDFULL LOAD AMPSFLAT ON BOTTOMFLAT ON TOPFIRE PROTECTION CONTRACTORFLOOR SINKFAN TERMINAL UNITGALLONSGALVANIZEDGREASE INTERCEPTORGENERAL CONTRACTORGAS UNIT HEATERGAS WATER HEATERCOLD WATERHOSE BIBBHUB DRAINHOURHORSEPOWER

ACCACADJAFFAHUAPAPDASBBBBDDBHPBTUBODBOPBOSBWCAPCCCFMCHCWRCWSCICLCLGCOCONNCPVCCRCSCUCUHCVDDIADBDISCDNDSDWDSDDSRE-#EAEATEDBEWBEWTEFFETECHEFECEMSESPESVEUHEWHEXEXHFAFCUFDFHFDRFINFLRFMFPMFTFURNFLAFOBFOTFPCFSFTUGALGALVGIGCGUHGWHCWHBHDHRHP

MECHANICAL ABBREVIATIONS

X - EXISTING

X - EXISTING

Revision Schedule

No Date Description

Page 9: ELECTRICAL SYMBOLS LEGEND - REiCON Constructors · 2016-04-12 · pnc bank bid set e0.1 pnc valley park 16.008.00 april 11, 2016 electrical symbols, abbreviations & general notes

EXHAUST FAN SCHEDULE

MODEL NO.MANUFACTURERMARK SPCFM RPM REMARKSVOLTS/PH HPLOCATION

1. VERIFY ARRANGEMENT WITH CEILING TYPE2. DAMPERS TO BE RADIAL OPPOSED BLADE3. DROPPED FACE RETURN GRILLE4. PROVIDE NECK ADAPTER MATCHING SIZE ON DRAWING5. VARIABLE VOLUME DIFFUSER. SUPPORTED BY DUCT IN OPEN CEILING.

REMARKSMARKPLAN

AIR DEVICE SCHEDULE

MATL.MANUFACTURER

R1

MODEL

LAY-IN

SIZENECK

TYPEFRAME

SIZEPANEL

24x24 1,2

NC

12x12SURFACE22x22

STEELPLQKRUEGERS1

1,2

S3

SERVICEDRIVE

<30

24x24LAY-IN

10"Ø

1,2,3,4-

24x24LAY-IN8"Ø

S2

1,2<30

ALUMT1

<30

ROOF TOP UNIT SCHEDULE (EXISTING TO REMAIN)

D1NA048N11025C

YORKRTU-1

MODEL NO.MARK MANUFACTURER H2O

29.5 1

V/PH

ELECTRICALREMARKS

MCAINCHES

ESP

RTU-2 25.9

CEILING -120/1 11,7500.350100L150MGBROANEF-2 RESTROOMDIRECT

YORK 4

TONS

5

1,500

CFM

1,850 260

CFM

100

O.A.

0.5

0.5

HEATING INPUT MBH

208/3

208/3

135

135

HP

1.0

1.0 1

EXISTING RTU UNIT. NO MODIFCATION OR UPGRADES REQUIRED TO UNIT OR ASSOCIATED GAS PIPING.

1. SPEED CONTROLLER AND BACKDRAFT DAMPER.

CEILING -120/1 11,7500.350100L150MGBROANEF-3 RESTROOMDIRECT

STEEL

1.

CEILING -120/1 11,7500.350100L150MGBROANEF-1 JANITOR CLOSETDIRECT

D2NA060N11025D

4000 208/1 1,2,3

REMARKSVOLT/PHWATTSLOCATION

QMARK

MARK

EH-1

MANUFACTURER

ELECTRIC HEATER SCHEDULE (CEILING)

1. UNIT MOUNTED DISCONNECT SWITCH.2. CEILING MOUNTED.3. THERMOSTAT TO BE MOUNTED ON WALL. SEE SHEET M1.1 FOR LOCATION.

MODEL NO.

CDF548 ATM / VESTIBULE

PLQKRUEGER

5810KRUEGER

S80HKRUEGER

COLOR

10-ALUMICAN

44-BRITISH WHITE

44-BRITISH WHITE

44-BRITISH WHITE

STEEL

22x22

8"Ø 1,2,524x24 <30ACUTHERM STANDARD WHITELAY-INTF-HC STEELS4

12x12SURFACE22x22 1,2<30ALUM5810KRUEGER 10-ALUMICAN

FLEXIBLE ROUND DUCT,SEE SPECS

VOLUME DAMPER WITHLOCKING QUADRANT ANDINSULATION EXTENSION

DRAWBANDSEE NOTE 2

EXTERNAL DUCTINSULATION

SQUARE TO ROUNDTRANSITION

SEAL FLEX DUCTINSULATION TO

RIGID DUCTINSULATION WITH

DUCT TAPE

NOTES:1. THIS DETAIL IS APPLICABLE FOR FELXIBLE ROUND DUCT TAKE-OFFS FROMBRANCH DUCTS TO DIFFUSERS.2. FLEXIBLE DUCT INSULATION SHALL TERMINATE AT SIDE OF BRANCH DUCTSO NO UNISULATED METAL PARTS ARE EXPOSED.

BRANCHDUCT

SS

C J

OB

# 2

016123_B

ID S

ET

- N

OT

FO

R C

ON

ST

RU

CT

ION

Th

e S

ea

l and

Sig

na

ture

app

ly o

nly

to t

he

Do

cum

en

t to

wh

ich t

he

y a

re A

ffix

ed

, an

d E

xpre

ssl

y D

iscla

im a

ny

Re

spo

nsib

ility

fo

r all

oth

er

Pla

ns, S

pe

cifica

tion

s,

Estim

ate

s, R

ep

ort

s, o

r o

the

r D

ocu

men

ts o

r In

str

um

en

tsre

latin

g t

o o

r in

ten

de

d t

o b

e u

se

d f

or

any p

art

or

pa

rts

of

the

Arc

hite

ctu

ral o

r E

ng

ine

erin

g P

roje

ct.

Co

pyrig

ht ©

20

16

by S

SC

En

gin

ee

ring

, In

c.

MISSOURI

5017 Washington Place Suite 200

St. Louis, M0 63108

314.361.0000 ph

314.361.9191 fax

Copyright 2016 HKW Architects

IOWA

1000 Melrose Avenue

Iowa City, IA 52246

319.343.7055 ph

hkwarchitects.com

18207 Edison Avenue

Chesterfield, M0 63005

636.530.7770 ph

636.530.7877 fax

PN

C B

ank

Bid Set

M0.2

PN

C V

alle

y P

ark

16.008.00

April 11, 2016

MECHANICALSCHEDULES &DETAILS

912 Meramec Station Road, Valley Park, MO 63021

NOT TO SCALE

FLEXIBLE DUCT CONNECTION TO BRANCH - INSULATEDNOT TO SCALE

BRANCH CONNECTION TO DIFFUSER DETAILNOT TO SCALE

BOTTOM TAP DIFFUSER DETAILNOT TO SCALE

SOUND BO0T DETAIL

Revision Schedule

No Date Description

Page 10: ELECTRICAL SYMBOLS LEGEND - REiCON Constructors · 2016-04-12 · pnc bank bid set e0.1 pnc valley park 16.008.00 april 11, 2016 electrical symbols, abbreviations & general notes

FDFD

S1

150

S1

150

S1

150

R1

-

EF

3

S1

150

S1

100

EF

2

S1

150S1

100

R1

-

S1

150

S2

350

R1

-

R1

- R1

-

R1

-

S1

100

S1

100

S3

350

S2

350

S1

100

S2

350

S1

150S1

200S1

200

EF

1

16"ø

14"x16"

Concierge102

Off-Stage103

Maintenance104

Break Room109

Janitor107

Elec/Data105

Passage111

Toilet106

Toilet108

Coupon Booth112

Self-ServeBoxes

114

CustomerPantry

113

Office115

Office116

Office117

Office118

Lobby119

ATM Vestibule100

20"x20"

16"x16"

20

"x20

"

44

4

T1

-

T1

-

RTU-1XT

RTU-2XT

2

RTU

1X

RTU

2X

(ONROOF)

(ONROOF)

10"ø

R1

-

S1

100

10

8"ø

8"ø

8"ø 8"ø

10"ø

10"ø

8"ø

8"ø

8 (TYP)R1

-

8"ø

8"ø

8"ø

8"ø

8"ø

8"ø

8"ø

10"ø

5

T1

-

65

8"ø

EH

1

S1

150

6"ø

S4

150

EH-1T

8"ø 8"ø

R1

-

8"ø

R1

-

12"x12"

12"x12"

12"x12"

12"x12"

12

12

12

RTU

1X

RTU

2X

12"ø 16"ø 12"ø

12"ø 16"ø 12"ø

XT

-

XT

-

XS

-

XS

-

XS

-

XS

-

XS

-

XS

-

XT

- XT

-

XS

-

XS

-

XS

-

XS

-

XS

-

XS

-

XS

-

EF

EX

EF

EX

RTU-2XT

RTU-1XT

(ON ROOF)

(ON ROOF)

2

XS

-

1

1

1

1

1

1

1

1

1

1

1

1

1

1

3 3

9

9

99

11

4

SS

C J

OB

# 2

016123_B

ID S

ET

- N

OT

FO

R C

ON

ST

RU

CT

ION

Th

e S

ea

l and

Sig

na

ture

app

ly o

nly

to t

he

Do

cum

en

t to

wh

ich t

he

y a

re A

ffix

ed

, an

d E

xpre

ssl

y D

iscla

im a

ny

Re

spo

nsib

ility

fo

r all

oth

er

Pla

ns, S

pe

cifica

tion

s,

Estim

ate

s, R

ep

ort

s, o

r o

the

r D

ocu

men

ts o

r In

str

um

en

tsre

latin

g t

o o

r in

ten

de

d t

o b

e u

se

d f

or

any p

art

or

pa

rts

of

the

Arc

hite

ctu

ral o

r E

ng

ine

erin

g P

roje

ct.

Co

pyrig

ht ©

20

16

by S

SC

En

gin

ee

ring

, In

c.

MISSOURI

5017 Washington Place Suite 200

St. Louis, M0 63108

314.361.0000 ph

314.361.9191 fax

Copyright 2016 HKW Architects

IOWA

1000 Melrose Avenue

Iowa City, IA 52246

319.343.7055 ph

hkwarchitects.com

18207 Edison Avenue

Chesterfield, M0 63005

636.530.7770 ph

636.530.7877 fax

PN

C B

ank

Bid Set

M1.1

PN

C V

alle

y P

ark

16.008.00

April 11, 2016

MECHANICALDUCTWORK

PLAN

912 Meramec Station Road, Valley Park, MO 63021

NORTH

SCALE: 1/8" = 1'-0"

MECHANICAL DUCTWORK PLAN - RENOVATION

1

2

MECHANICAL GENERAL NOTES:

1.

2.

3.

4.

REFER TO SHEET M0.1 FOR SYMBOLS, ABBREVIATIONS AND GENERAL CONSTRUCTION NOTES.

ADJACENT TENANT SPACE NOT IN SCOPE.

ITEMS SHOWN DASHED OR CROSS HATCHED TO BE DEMOLISHED.

MC SHALL PROVIDE COMMISIONING FOR THE HVAC SYSTEM BEFORE SUBSTANTIALCOMPLETION. CONFIRM CONTROLS OPERATION; RTU OPERATION - FAN, DAMPERS, COOLINGSTAGING, HEATING STAGING; EF OPERATION; EH OPERATION. SUBMIT REPORT TO OWNER.

MECHANICAL KEYED NOTES:

DEMOLISH EXISTING AIR DEVICE. PATCH DUCT TO REMAIN WHERE APPLICABLE.

RELOCATE EXISTING THERMOSTAT TO NEW LOCATION. SEE RENOVATION PLAN.

DEMOLISH EXISTING EXHAUST FAN AND DUCT TO EXISTING VENT THROUGH ROOF. VENT THROUGHROOF TO REMAIN.

NEW EXHAUST FAN TO CONNECT TO EXISTING CAPPED VENT THROUGH ROOF.

INSTALL SIDE WALL AIR DEVICE 10' AFF.

12" X 12" TRANSFER DUCT SHALL TRANSITION UP AND TERMINATE IN CEILING PLENUM OF LOBBY.

8" TWO-POSITION, 120 VOLT CONTROL DAMPER. LINE VOLTAGE, DUCT MOUNTED THERMOSTAT SHALLCLOSE DAMPER WHEN SUPPLY AIR ABOVE 80° F.

PROVIDE DUCTED SOUND BOOT AT PLENUM RETURN GRILLES, SEE SHEET M0.2.

EXISTING WALL TRANSFER GRILLE AT 12' AFF TO BE REMOVED TO ACCOMMODATE NEW LAY-INCEILING.

NEW WALL TRANSFER GRILLE AT 7' AFF.

EXISTING DUCT DETECTOR TO REMAIN.

12" x 12" TRANSFER DUCT ABOVE CEILING.

NORTH

SCALE: 1/8" = 1'-0"

MECHANICAL DUCTWORK PLAN - DEMOLITION

3

4

5

6

7

8

9

10

11

12

Revision Schedule

No Date Description

Page 11: ELECTRICAL SYMBOLS LEGEND - REiCON Constructors · 2016-04-12 · pnc bank bid set e0.1 pnc valley park 16.008.00 april 11, 2016 electrical symbols, abbreviations & general notes

1.2.

3.

4.

5.

LISTING OFEQUIPMENT AND

SYSTEM COMPONENTS

Not Provided Provided

ANCHORAGE TOFLOORS,

ROOFS, ETC.

ProvidedNot Provided

SWAY BRACING

Drawing No. orSpec. Section

LOCATION OF PROFESSIONALLY SEALEDANCHORAGE

AND SWAY BRACING DETAILS

Shop DrawingsSeparate

Permit & Plans

COMMENTS

Anchorage & Sway Bracing - Plumbing System Components

Seismic Design Category ( D )Seismic Use Group ( II )

VENT PIPING

X

X

X

WASTE PIPING

2a

1

2aX

TABLE 4.4, ITEM 1, A, lp=1.0, COMPONENT DOES NOT WEIGH MORE THAN 400 POUNDS AND FLEXIBLE CONNECTIONS ARE PROVIDED.TABLE 4.4, NOTE 2:a. THE FOLLOWING SANITARY DRAIN, WASTE AND VENT PIPE: SCHEDULE 40 PVC, 6 INCHES OR LESS IN DIAMETER, SCHEDULE 80 PVC, 4 INCHES OR LESS IN DIAMETER, SERVICE WEIGHT AND NO HUB CAST IRON, 2 INCHES OR LESS IN DIAMETER.b. THE FOLLOWING STORM DRAIN PIPE: SCHEDULE 40 AND 80 PVC, 3 INCHES OR LESS IN DIAMETER, SERVICE WEIGHT AND NO HUB CAST IRON, NOT APPLICABLE.c. THE FOLLOWING WATER PIPE: TYPE L AND M COPPER, 2-1/2 INCHES OR LESS IN DIAMETER, SCHEDULE 40 AND 80 CPVC, 3 INCHES OR LESS IN DIAMETER.d. FLEXIBLE CONNECTIONS ARE NOT REQUIRED FOR CONNECTIONS TO APPLIANCES OR PLUMBING FIXTURES THAT ARE MOUNTED TO WALLS OR FLOORS.CONTRACTOR SHALL PROVIDE SHOP DRAWINGS TO THE ENGINEER OF RECORD FOR REVIEW AND APPROVAL PRIOR TO SUBMITTAL TO THE PLANREVIEWER.SEISMIC DETAILS ARE ATTACHED TO THE SET OF DRAWINGS.TYPICAL SEISMIC ANCHORAGE (OR SWAY BRACING) IS PROVIDED ON THE DRAWINGS FOR REFERENCE ONLY. SHOP DRAWINGS ARE REQUIRED.

WATER PIPING

X 2c

WATER HEATER (LESS THANOR EQUAL TO 400 POUNDS)

X

X

X

WC-1 FLOOR MOUNTED WATER CLOSET - ADA

EF-21-318 L/R

9500CT

GERBER FLOOR MOUNTED TANK TYP VITREOUS CHINA TOILET. ELONGATED BOWL,ADA COMPLIANT, 1.1 GAL PER FLUSH.

CHURCH COMMERCIAL WHITE SOLID PLASTIC OPEN FRONT SEAT, LESS COVER.

LAV-1 WALL HUNG LAVATORY

0356.137

155A2

EFX-375.100.0000

LFBV2166

AMERICAN STANDARD "LUCERNE", VITREOUS CHINA, 20-1/2"x18-1/4", WALL-HUNG, FRONTOVERFLOW LAVATORY, 2-1/8" DIA. HOLES FOR CONCEALED ARMS. SINGLE CENTERSET.

MCGUIRE OPEN-GRID DRAIN. RUBBER WASHER AND BRASS LOCKNUT. WITH 1-1/2" TAILPIECE.

BASYS IR SERIES FAUCET.ONS SINGLE LEVER LAVATORY FAUCET WITH GRID STRAINER DRAIN ASSEMBLY,SINGLE CENTERSET, 0.5 GPM AERATOR.

MCGUIRE LOOSE KEY CHROME PLATED, COMMERCIAL PATTERN QUARTER TURN BRASS BALL VALVE.

ELECTRIC WATER COOLEREWC-1

LZSTL8WSVRSK

LFBV02

8912

ELKAY BI-LEVEL ELECTRIC WATER COOLER WITH BOTTLE FILLING STATION. VANDAL RESIST STREAMSAVEREZH20 BOTTLE FILLING - WATER COOLER COMBINATION KIT.

MCGUIRE STOP VALVE, CONVERTIBLE LOOSE KEY HANDLE, LEAD FREE, CHROME PLATED.

MCGUIRE CHROME PLATED, BRASS BODY P-TRAP WITH CLEANOUT, 17 GAUGE TUBULAER WALL BEND, CASTBRASS SLIP NUTS.

SINKS-1

201-AGN8AE3-317ABCP

LRADQ2521

LK-18B

SR1912A C

ELKAY, 25"x21.25" STAINLESS STEEL SINGLE BOWL SINK, 6" DEEP, HEAVY DUTY SOUNDGUARD UNDERCOATING. 8" CENTERSET.

ELKAY 3-1/2" DIAMETER WASTE AND 1-1/2" TAILPIECE.

BRASS CRAFT LOOSE KEY, CHROME PLATED ANGLE STOP, WITH 1/2" SWEAT INLET AND 3/8"O.D. COMPRESSION OUTLET WITH 3/8" x 11-1/2" LONG RISER AND SHALLOW CHROMEPLATED WALL ESCUTCHEON.

MOP SERVICE BASINMSB-1

897-RCF

T-35

EB-54

CHICAGO WALL MOUNTED, 8" BODY FAUCET WITH ADJUSTABLE ARMS.

STERN WILLIAMS HOSE AND WALL HOOK.

STERN WILLIAMS ELFIN ONE PIECE, TERRAZO WITH GREY MARBLE CHIPS 24"x24" WITH 6" HIGH SIDES,MOP BASIN. DRAIN BODY SHALL BE STAINLESS STEEL OR CHROME PLATED BRASS, CAST INTEGRAL ANDSHALL PROVIDE FOR A CAULK CONNECTION NOT LESS THAN 1" DEEP TO A 3" PIPE. STRAINER SHALLBE CHROME PLATED BRASS.

WATER SUPPLY BOXWSB-1

MIB1HAAB GUY GRAY WATER SUPPLY BOX, 20 GAUGE STEEL FACEPLATE AND BOX WITH WHITE POWDER COATING,1/4 TURN VALVE, 1/2" SWEAT CONNECTION, WITH LEAD FREE WATER HAMMER ARRESTER.

DESCRIPTIONMARK

PLUMBING FIXTURE SCHEDULE

#103 E-Z LAV GUARD 2 FAST FIT UNDERSINK PIPING COVERS FOR P-TRAP, ANGLE STOPS, AND SUPPLY COVERS. ADA COMPLIANT.

CHICAGO FAUCET DECK MOUNTED WIDESPREAD FAUCET WITH BLADE HANDLES, 8" HIGH ARC SWINGSPOUT WITH 1.0 GPM AERATOR (E3JKABCP).

Z1231-SL-79 CONCEALED ARM SYSTEM FOR WALL LAVATORY.

8912 MCGUIRE CHROME PLATED, BRASS BODY WITH CLEANOUT, 17 GAUGE TUBULAER WALL BEND, CASTBRASS SLIP NUTS.

8912 MCGUIRE CHROME PLATED, BRASS BODY P-TRAP WITH CLEANOUT, 17 GAUGE TUBULAER WALL BEND, CASTBRASS SLIP NUTS.

ELECTRIC WATER HEATER SCHEDULE

°F. RISE

DEL-6

MODEL NO.

EWH-1

MARK

A.O. SMITH

MNFG.

6

STORAGE GAL. RECOVERY

10 GPH 100

HEAT SOURCE

120V

HEAT CAP.

2500 WATTS

REMARKS

1

1. NON-SIMULTANEOUS OPERATION.

WC

1

DRAIND

PLUMBING SYMBOLS LEGEND

FIXTURE TYPE

FIXTURE NUMBER

CONNECTION OF NEW TO EXISTING

COLD WATER (CW)

HOT WATER SUPPLY (HW)

HOT WATER RETURN (REC)

SOFT WATER

HARD WATER

TEMPERED WATER

140 DEGREE HOT WATER

GAS PIPING

GREASE WASTE

SANITARY WASTE ABOVE GRADE

DRAIN TILE

STORM DRAINAGE PIPING ABOVE GRADE

OVERFLOW DRAINAGE PIPING ABOVE GRADE

PIPING BELOW GRADE (SEE PLANS)

PLUMBING TRAP

PIPE TURNING DOWN

PIPE TURNING UP

WATER HAMMER ARRESTER

BALL VALVE

FLOW CONTROL/BALANCE VALVE

PRESSURE RELIEF VALVE

CHECK VALVE

GAS COCK

UNION

PRESSURE GAUGE

STRAINER

REDUCED PRESSURE BACKFLOW PREVENTOR (RPBFP)

TRAP PRIMER

ABOVE FINISHED FLOOR

NOT TO SCALE

CAST IRON

CLEAN OUT

THRU-FLOOR

SANITARY VENT

AFF

NTS

CI

CO

TP

S

H

T

140

G

GW

W

DT

ST

OD

SS

C J

OB

# 2

016123_B

ID S

ET

- N

OT

FO

R C

ON

ST

RU

CT

ION

Th

e S

ea

l and

Sig

na

ture

app

ly o

nly

to t

he

Do

cum

en

t to

wh

ich t

he

y a

re A

ffix

ed

, an

d E

xpre

ssl

y D

iscla

im a

ny

Re

spo

nsib

ility

fo

r all

oth

er

Pla

ns, S

pe

cifica

tion

s,

Estim

ate

s, R

ep

ort

s, o

r o

the

r D

ocu

men

ts o

r In

str

um

en

tsre

latin

g t

o o

r in

ten

de

d t

o b

e u

se

d f

or

any p

art

or

pa

rts

of

the

Arc

hite

ctu

ral o

r E

ng

ine

erin

g P

roje

ct.

Co

pyrig

ht ©

20

16

by S

SC

En

gin

ee

ring

, In

c.

MISSOURI

5017 Washington Place Suite 200

St. Louis, M0 63108

314.361.0000 ph

314.361.9191 fax

Copyright 2016 HKW Architects

IOWA

1000 Melrose Avenue

Iowa City, IA 52246

319.343.7055 ph

hkwarchitects.com

18207 Edison Avenue

Chesterfield, M0 63005

636.530.7770 ph

636.530.7877 fax

PN

C B

ank

Bid Set

P0.1

PN

C V

alle

y P

ark

16.008.00

April 11, 2016

PLUMBINGSYMBOLS,

ABBREVIATIONS& GENERALNOTES

912 Meramec Station Road, Valley Park, MO 63021

PLUMBING GENERAL RENOVATION NOTES:1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

SEE SHEET P0.1 FOR SYMBOLS AND ABBREVIATIONS. THESE GENERAL NOTES APPLY TO ALL WORK.

THESE DRAWINGS MAY NOT FULLY DEPICT ALL AS-BUILT CONDITIONS, CONTRACTOR SHALL FIELDVERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING BIDS. NOTIFY THE ENGINEER AT ONCE SHOULDA DISCREPANCY OR OMISSION BE FOUND.

PIPING ON PLANS IS SHOWN FOR GENERAL ARRANGEMENT. SEE DETAILS FOR CONNECTIONS TO UNITS.

WHERE PIPE SIZES ARE NOT SHOWN ON PLANS, SEE SIZES SHOWN ON ISOMETRICS. IF PIPE SIZES ONPLANS CONFLICT WITH SIZES SHOWN ON ISOMETRIC DIAGRAMS, SIZES ON DIAGRAMS SHALL TAKEPRECEDENCE.

SLOPE ALL SANITARY PIPES SMALLER THAN 4" AT 1/4" PER FT. AND SANITARY PIPES 4" OR LARGER AT1/8" PER FT. UNLESS OTHERWISE INDICATED.

CONTRACTOR SHALL COORDINATE WITH OTHER TRADES TO PREVENT THE INSTALLATION OF CONDUITS,PIPING, LIGHTING, OR OTHER OBSTRUCTIONS UNDER OR ADJACENT TO HVAC EQUIPMENT THATOBSTRUCTS ACCESS TO COILS, MOTORS, VALVES, FILTERS, ETC., OR OTHER HVAC COMPONENTSNEEDING MAINTENANCE OR OPERATIONS ACCESS.

CONTRACTOR SHALL COORDINATE EXACT LOCATION OF FLOOR DRAINS WITH ARCHITECTURAL ANDSTRUCTU PLANS.

COORDINATE PLUMBING WITH ALL MECHANICAL DUCTWORK AND PIPING AND SPRINKLER PIPINGBEFORE COMMENCEMENT OF WORK.

LOCATIONS OF NEW FIXTURES, EQUIPMENT, PIPING, AND ASSOCIATED ITEMS SHOWN ON THEDRAWINGS ARE SCHEMATIC. CONTRACTOR SHALL SEE ARCHITECTURAL PLANS AND FIELD VERIFYEXACT LOCATION AND ELEVATION OF ALL WORK. PROVIDE OFFSETS, FITTINGS, TRANSITIONS,EXTENSIONS, ETC., REQUIRED FOR A COMPLETE SYSTEM.

NO CHANGES IN CONTRACT PRICE WILL BE ALLOWED FOR MINOR CHANGES IN LAYOUT OR LOCATIONREQUIRED TO AVOID INTERFERENCES, OBSTRUCTIONS, ETC. CONTRACT PRICE CHANGES WILL BECONSIDERED ONLY FOR CHANGES IN THE SCOPE OF THE PROJECT REQUIREMENTS. ALL SUCH SCOPECHANGES AND PRICE REVISIONS MUST BE AUTHORIZED IN WRITING. NOTIFY THE ENGINEER AT ONCESHOULD A DISCREPANCY OR OMISSION BE FOUND.

PIPING IN EXPOSED LOCATIONS SHALL BE CHROME PLATED UNLESS OTHERWISE INDICATED.

CHROME PLATED ESCUTCHEONS SHALL BE PROVIDED AT ALL LOCATIONS WHERE PIPES PENETRATEWALLS IN EXPOSED LOCATIONS.

PROVIDE SEISMIC BRACING AS REQUIRED. SEE SCHEDULE FOR SPECIFICATIONS.

ALL UTILITIES SERVING EXISTING AREAS SHALL REMAIN IN SERVICE AT ALL TIMES EXCEPT FOR SHORTPERIODS OF INTERRUPTION FOR TIE IN OF NEW SERVICES TO EXISTING. ALL INTERRUPTIONS SHALL BESCHEDULED WITH OWNER, AND SHALL NOT BE SCHEDULED UNTIL NEW SERVICES ARE COMPLETE ANDREADY FOR FINAL CONNECTION.

SPACES ABOVE CEILINGS ARE RETURN AIR PLENUMS UNLESS OTHERWISE INDICATED ON HVAC PLANS.PIPING AND INSULATION IN CEILING PLENUMS SHALL HAVE A FLAME SPREAD OF 25 OR LESS AND ASMOKE DEVELOPED RATING OF 50 OR LESS AS DETERMINED IN ACCORDANCE WITH ASTM STANDARDE-84.

PLUMBING GENERAL DEMOLITION NOTES:1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

SEE SHEET P0.1 FOR SYMBOLS AND ABBREVIATIONS. SEE RISER DIAGRAMS FORADDITIONAL DEMOLITION DETAILS.

THESE GENERAL DEMOLITION NOTES APPLY TO ALL DEMOLITION WORK.

DEMOLISH PIPING, FIXTURES, AND EQUIPMENT SHOWN CROSS HATCHED OR DASHED.

THESE DRAWINGS MAY NOT FULLY DEPICT ALL AS-BUILT CONDITIONS, CONTRACTORSHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING BIDS. NOTIFY THEENGINEER AT ONCE SHOULD A DISCREPANCY OR OMISSION BE FOUND.

CONTRACTOR SHALL USE CAUTION WHEN REMOVING PIPING, EQUIPMENT AND FIXTURESTO AVOID DAMAGE TO ELECTRICAL WIRING THAT IS TO REMAIN. NOTIFY GC AND EC IFWIRING IS FOUND ATTACHED TO PIPING.

WHEREVER EXISTING EQUIPMENT, PIPING, ETC., ARE TO BE REMOVED, SUCH REMOVALSHALL INCLUDE ALL ANCHORS, HANGERS, FOUNDATIONS, ETC., UNLESS NOTEDOTHERWISE. AFTER REMOVAL, FLOORS, WALLS AND CEILINGS SHALL BE PATCHED ANDFINISHED TO MATCH ADJOINING SURFACES.

WHERE ITEMS ARE REMOVED, UTILITIES AND THE AREA FROM WHICH THE ITEMS HAVEBEEN REMOVED SHALL BE LEFT IN SUCH A MANNER THAT IS SAFE FOR BOTH PEOPLE ANDPROPERTY ON A DAILY BASIS.

SEE ARCHITECTURAL DRAWINGS FOR ARCHITECTURAL DEMOLITION. REFER TO MEP ANDSPRINKLER DEMOLITION PLANS FOR MEP AND SPRINKLER DEMOLITION.

THE OWNER WILL BE RESPONSIBLE FOR THE REMOVAL OF ANY ACMs (ASBESTOSCONTAINING MATERIALS, PCBs OR OTHER HAZARDOUS MATERIALS) PRESENTLY EXISTINGWITHIN THE AREAS AFFECTED BY THE PROJECT SCOPE, THAT WOULD BE REQUIRED TOBE REMOVED FOR THE WORK. ABATEMENT WORK, IF REQUIRED, IS NOT PART OF THISCONTRACT.

MEP DEMOLITION WORK: VERIFY EXISTING SERVICES TO REMAIN. ALL NECESSARY CARESHALL BE TAKEN DURING DEMOLITION TO PREVENT DAMAGE TO PLUMBING, ELECTRICAL,AND MECHANICAL SYSTEMS TO REMAIN. DUCTWORK, PIPING, ELECTRICAL LINES, ANDPLUMBING SERVING OTHER AREAS SHALL PROVIDE FOR UNINTERRUPTED SERVICE TOTHOSE AREAS UNLESS PRIOR WRITTEN APPROVAL IS RECEIVED FROM THE OWNER.COORDINATE ALL SUCH WORK WITH THE GENERAL CONTRACTOR AND OWNER'S ON SITEREPRESENTATIVE.

WASTE PIPING TO BE PVC WITH PLENUM WRAP OR CAST-IRON TO BE INSTALLED INRETURN AIR PLENUM.

PLUMBING SHEET LIST

Sheet Number Sheet Name

P0.1 PLUMBING SYMBOLS, ABBREVIATIONS & GENERAL NOTES

P1.1 PLUMBING WASTE & VENT PLAN

P2.1 PLUMBING DOMESTIC PIPING PLAN

Revision Schedule

No Date Description

Page 12: ELECTRICAL SYMBOLS LEGEND - REiCON Constructors · 2016-04-12 · pnc bank bid set e0.1 pnc valley park 16.008.00 april 11, 2016 electrical symbols, abbreviations & general notes

WC

1

LAV

1

WC

1

LAV

1

FD

EX

FD

EX

MSB

1

6

3

3"

2"

S

1

2"

EWC

12"6

6

Lobby119

Maintenance104

Off-Stage103Concierge

102

ATM Vestibule100

Office118

Office117

Office116

Office115 Self-Serve

Boxes

114

CustomerPantry

113

Toilet108

Toilet106

Passage111

Elec/Data105

Janitor107

Break Room109

FD

EX

FD

EX

FD

EX

1

2

WC

EX

LAV

EX

WC

EX

LAV

EX

MSB

EX

3

4

5

4

5

SS

C J

OB

# 2

016123_B

ID S

ET

- N

OT

FO

R C

ON

ST

RU

CT

ION

Th

e S

ea

l and

Sig

na

ture

app

ly o

nly

to t

he

Do

cum

en

t to

wh

ich t

he

y a

re A

ffix

ed

, an

d E

xpre

ssl

y D

iscla

im a

ny

Re

spo

nsib

ility

fo

r all

oth

er

Pla

ns, S

pe

cifica

tion

s,

Estim

ate

s, R

ep

ort

s, o

r o

the

r D

ocu

men

ts o

r In

str

um

en

tsre

latin

g t

o o

r in

ten

de

d t

o b

e u

se

d f

or

any p

art

or

pa

rts

of

the

Arc

hite

ctu

ral o

r E

ng

ine

erin

g P

roje

ct.

Co

pyrig

ht ©

20

16

by S

SC

En

gin

ee

ring

, In

c.

MISSOURI

5017 Washington Place Suite 200

St. Louis, M0 63108

314.361.0000 ph

314.361.9191 fax

Copyright 2016 HKW Architects

IOWA

1000 Melrose Avenue

Iowa City, IA 52246

319.343.7055 ph

hkwarchitects.com

18207 Edison Avenue

Chesterfield, M0 63005

636.530.7770 ph

636.530.7877 fax

PN

C B

ank

Bid Set

P1.1

PN

C V

alle

y P

ark

16.008.00

April 11, 2016

PLUMBINGWASTE & VENT

PLAN

912 Meramec Station Road, Valley Park, MO 63021

NORTH

SCALE: 1/8" = 1'-0"

PLUMBING WASTE & VENT PLAN - RENOVATION

1

2

PLUMBING GENERAL NOTES:

1.

2.

3.

4.

5.

REFER TO SHEET P0.1 FOR SYMBOLS AND GENERAL NOTES.

PRIOR TO ANY SAWCUTTING OF THE FLOOR SLAB, CONTRACTOR SHALL XRAY THE FLOOR TOAVOID HITTING OTHER UTILITIES OR RE-BAR. COORDINATE EXACT ROUTE TO MINIMIZEDISTURBANCE TO FLOOR SLAB. REVIEW AND COORDINATE ALL SAWCUTTING WITH LANDLORDPRIOR TO WORK.

EXISTING VENT AND WASTE PIPING FROM EXISTING LAV AND WATER CLOSET IN RESTROOMSVENTED TO ROOF THROUGH TENANT WALL TO REMAIN.

ADJACENT TENANT SPACE NOT IN SCOPE.

ITEMS SHOWN CROSS HATCHED TO BE DEMOLISHED.

PLUMBING DEMOLITION KEYED NOTES:

EXISTING FLOOR DRAIN TO BE REMOVED. PLUG AND CAP PIPE. PATCH FLOOR TO MATCHEXISTING FLOOR FINISH.

EXISTING MOP SERVICE BASIN TO BE REMOVED. PLUG AND CAP PIPE. PATCH FLOOR TOMATCH EXISTING FLOOR FINISH.

EXISTING VENT THROUGH ROOF.

NORTH

SCALE: 1/8" = 1'-0"

PLUMBING WASTE & VENT PLAN - DEMOLITION

4

PLUMBING RENOVATION KEYED NOTES:

EXISTING LAVATORY SHALL BE DISCONNECTED AND REMOVED. EXISTING ROUGH-IN SHALLREMAIN FOR NEW FIXTURE CONNECTIONS.

EXISTING WATER CLOSET SHALL BE DISCONNECTED AND REMOVED. EXISTING ROUGH-INSHALL REMAIN FOR NEW FIXTURE CONNECTIONS.

CUT AND REMOVE EXISTING FLOOR TO INSTALL NEW WASTE PIPE BELOW SLAB. CONNECTTO EXISTING WASTE PIPING. PATCH FLOOR TO MATCH EXISTING FLOOR FINISH.

3

5

6

Revision Schedule

No Date Description

Page 13: ELECTRICAL SYMBOLS LEGEND - REiCON Constructors · 2016-04-12 · pnc bank bid set e0.1 pnc valley park 16.008.00 april 11, 2016 electrical symbols, abbreviations & general notes

FDFD

MSB

1EWH

1

WC

1

LAV

1

WC

1

LAV

1

S

1

EWC

1

4

2 1/2"

5

1/2"

1/2"

1/2"

6

WB

1

Lobby119

Maintenance104

Off-Stage103Concierge

102

ATM Vestibule100

Office118

Office117

Office116

Office115 Self-Serve

Boxes

114

CustomerPantry

113

Toilet108

Toilet106

Passage111

Elec/Data105

Janitor107

Break Room109

7

7

7

7

WC

EX

LAV

EX

WC

EX

LAV

EX

2

2

MSB

EX1

3EWH

EX

22

1/2"

1/2"

2 1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"1/2"1/2"

SS

C J

OB

# 2

016123_B

ID S

ET

- N

OT

FO

R C

ON

ST

RU

CT

ION

Th

e S

ea

l and

Sig

na

ture

app

ly o

nly

to t

he

Do

cum

en

t to

wh

ich t

he

y a

re A

ffix

ed

, an

d E

xpre

ssl

y D

iscla

im a

ny

Re

spo

nsib

ility

fo

r all

oth

er

Pla

ns, S

pe

cifica

tion

s,

Estim

ate

s, R

ep

ort

s, o

r o

the

r D

ocu

men

ts o

r In

str

um

en

tsre

latin

g t

o o

r in

ten

de

d t

o b

e u

se

d f

or

any p

art

or

pa

rts

of

the

Arc

hite

ctu

ral o

r E

ng

ine

erin

g P

roje

ct.

Co

pyrig

ht ©

20

16

by S

SC

En

gin

ee

ring

, In

c.

MISSOURI

5017 Washington Place Suite 200

St. Louis, M0 63108

314.361.0000 ph

314.361.9191 fax

Copyright 2016 HKW Architects

IOWA

1000 Melrose Avenue

Iowa City, IA 52246

319.343.7055 ph

hkwarchitects.com

18207 Edison Avenue

Chesterfield, M0 63005

636.530.7770 ph

636.530.7877 fax

PN

C B

ank

Bid Set

P2.1

PN

C V

alle

y P

ark

16.008.00

April 11, 2016

PLUMBINGDOMESTICPIPING PLAN

912 Meramec Station Road, Valley Park, MO 63021

NORTH

SCALE: 1/8" = 1'-0"

PLUMBING DOMESTIC WATER PLAN - RENOVATION

1

2

PLUMBING GENERAL NOTES:

1.

2.

3.

REFER TO SHEET P0.1 FOR SYMBOLS AND GENERAL NOTES.

ADJACENT TENANT SPACE NOT IN SCOPE.

ITEMS SHOWN CROSS HATCHED TO BE DEMOLISHED.

PLUMBING DEMOLITION KEYED NOTES:

DISCONNECT AND REMOVE EXISTING PLUMBING FIXTURE. REMOVE PIPING ROUGH-IN ANDBRANCH PIPE BACK TO SUPPLY MAIN. CAP AT MAIN.

DISCONNECT AND REMOVE EXISTING PLUMBING FIXTURE. EXISTING ROUGH-IN TO REMAINFOR NEW CONNECT TO NEW PLUMBING FIXTURE.

EXISTING ELECTRIC WATER HEATER ABOVE CEILING TO BE REMOVED. CONNECTIONSBRANCHING INTO ADJACENT SPACE TO BE CAPPED AND REMOVED. CONTRACTOR TOCOORDINATE WITH LANDLORD TO VERIFY WATER SERVICE IS AVAILABLE WITH ADJACENTTENANT SPACE.

NORTH

SCALE: 1/8" = 1'-0"

PLUMBING DOMESTIC WATER PLAN - DEMOLITION

3

4

PLUMBING RENOVATION KEYED NOTES:

NOT TO SCALE

PLUMBING DOMESTIC WATER ISOMETRIC

EWH

1

6

EWC

1

MSB

1

S

14

3

OPTIONAL1/2" COLD WATER PIPE TO SERVE TO COFFEE MAKER. CONTRACTOR TO BID ASSEPARATE LINE ITEM. SEE ARCHITECTURAL DRAWING FOR MOUNTING HEIGHT.

EXISTING PRV VALVE / SPACE MAIN WATER SUPPLY. ACCESS THROUGH RESTROOMCEILING ACCESS PANEL.

2-1/2" MAIN WATER SERVICE TO BUILDING WATER SUPPLY CONNECTION.

HOT AND COLD WATER PIPING TO EXISTING WATERCLOSETS AND LAVATORIES TO REMAIN.

EXISTING COLD WATER AND HOT WATER TO ADJACENT TENANT. DISCONNECT EXISTINGWATER HEATER PIPING JOINING WITH THE ADJACENT SPACE WATER HEATER. PLUG / CAPSERVICE TO ADJACENT SPACE.

5

6

WB

1

7 7

8

8

Revision Schedule

No Date Description