24
11/11/2016 K:\279\27946.03 Palafox Demolition\Bidding and Bonds\Addendum 5\Addendum 5 ltr.docx 27946.03 ADDENDUM 5 Page 1 of 3 EMERALD COAST UTILITIES AUTHORITY CONSTRUCTION PLANS FOR THE GUILLEMARD STREET EMERGENCY STORAGE TANKS AND SITE DEMOLITION FOR CWRF TRANSMISSION MAIN INTERRUPTION RESPONSE PLAN FOR THE EMERALD COAST UTILITIES AUTHORITY ECUA CIP Project CS-415E BID No. CC2017-08 ADDENDUM NO. 5 November 11, 2016 This addendum forms a part of the Contract Documents and modifies the original Specifications and Drawings, dated September 2016, as noted below. Bidders must acknowledge receipt of this Addendum by indication of its receipt in the indicated location within the Bid Form. Failure to do so may subject Bidder to disqualification. This addendum consists of twenty-four (24) pages. The Contract Documents are modified or supplemented as follows: General: 1. The Bid Opening date has been changed to December 1, 2016 at 2:00 PM. The location remains unchanged. 2. Special Conditions 00850, paragraph 10, requirement to use the E-Builder software for this project is herewith deleted from the Contract Documents. 3. The sump pump shall be Dayton Model 3BB74 or engineer approved equal; ½ hp sump pump without integral float. 4. What is the dimension and material of the blower duct work? The blower duct shall be 18” 304 stainless steel connected to the dome with a 24” x 18” stainless steel fitting. 5. Appendices: Add Appendix F “Sherwin-Williams Protective Coats Product Information and Application Bulletins” with published information for Sherwin Williams Products referenced for Tank Interior Coatings. All information has been downloaded from available on-line website and is reproduced within the Appendix without copyright infringement.

EMERALD COAST UTILITIES AUTHORITY CONSTRUCTION … · Material: 50°F (10°C) minimum, 95°F (35°C) maximum At least 5°F (2.8°C) above dew point Relative humidity: 85% maximum

Embed Size (px)

Citation preview

11/11/2016

K:\279\27946.03 Palafox Demolition\Bidding and Bonds\Addendum 5\Addendum 5 ltr.docx

27946.03 ADDENDUM 5 Page 1 of 3

EMERALD COAST UTILITIES AUTHORITY

CONSTRUCTION PLANS FOR THE GUILLEMARD STREET EMERGENCY

STORAGE TANKS AND SITE DEMOLITION FOR CWRF TRANSMISSION MAIN

INTERRUPTION RESPONSE PLAN FOR THE EMERALD COAST UTILITIES

AUTHORITY

ECUA CIP Project CS-415E BID No. CC2017-08

ADDENDUM NO. 5

November 11, 2016

This addendum forms a part of the Contract Documents and modifies the original Specifications

and Drawings, dated September 2016, as noted below.

Bidders must acknowledge receipt of this Addendum by indication of its receipt in the indicated

location within the Bid Form. Failure to do so may subject Bidder to disqualification. This

addendum consists of twenty-four (24) pages.

The Contract Documents are modified or supplemented as follows:

General:

1. The Bid Opening date has been changed to December 1, 2016 at 2:00 PM. The location

remains unchanged.

2. Special Conditions 00850, paragraph 10, requirement to use the E-Builder software for this

project is herewith deleted from the Contract Documents.

3. The sump pump shall be Dayton Model 3BB74 or engineer approved equal; ½ hp sump

pump without integral float.

4. What is the dimension and material of the blower duct work?

The blower duct shall be 18” 304 stainless steel connected to the dome with a 24” x

18” stainless steel fitting.

5. Appendices: Add Appendix F “Sherwin-Williams Protective Coats Product Information

and Application Bulletins” with published information for Sherwin Williams Products

referenced for Tank Interior Coatings. All information has been downloaded from available

on-line website and is reproduced within the Appendix without copyright infringement.

11/11/2016

K:\279\27946.03 Palafox Demolition\Bidding and Bonds\Addendum 5\Addendum 5 ltr.docx

27946.03 ADDENDUM 5 Page 2 of 3

Specifications:

1. A revision to Specification 13 20 20 “Prestressed Concrete Storage Tank Section 2.11 C

was incorrectly stated in item 10 of the specification section in Addendum 3; revise to

read “Basis of Bid Exterior Coating System including exposed walls and top of dome

shall consist of the following…..”

2. Spec. 13 20 20 “Prestressed Concrete Storage Tank, Section 3.2-A-7; revise to read “The

floor shall receive a light broom finish or as required for an ICRI Profile CSP 3-5 for

coating application.”

3. Spec. 13 20 20 “Prestressed Concrete Storage Tank, Section 3.2-B-1-b-(6); revise to read

“The interior receives a light broom finish or as required for an ICRI Profile CSP 3-5

for coating application.”

4. Spec. 13 20 20 “Prestressed Concrete Storage Tank, Section 3.2-D-8; add to read “8. The

underside of the dome shall be finished to an ICRI Profile CSP 3-5 for coating

application.”

5. Spec. 13 20 20 “Prestressed Concrete Storage Tank, Section 2.11-B; revise the listed

subparts to read as follows:

1. Epoxy Patching and Surfacing Compound – Sherwin Williams STEEL SEAM

FT910, use as a filler and surfacer for uneven concrete surfaces, bugholes, cavities,

and other surface defects. Apply to concrete surfaces following a minimum 28-day

cure period. All concrete surfaces shall receive water blasting cleanse. Meet all

environmental conditions for application including temperature and humidity.

2. Primer Coat Sherwin Williams SW Corobond 100 at 4.0 to 6.0 mils dft.. Apply to

concrete surfaces following a minimum 28-day cure period. All concrete surfaces

shall be clean and dry and bare concrete shall be water blasted clean. Meet all

environmental conditions for application including temperature and humidity.

3. Two coats Sherwin Williams SW Dura-Plate 5900 at 20.0 mils dft each coat. Each of

the two coats will be contrasting, first coat white, second and final coat gray. Meet all

environmental conditions for application including temperature and humidity. All

time windows between successive applications shall comply with the Manufacturers

Application Requirements.

Drawing Sheets:

1. Dwg. C-100, is hereby reissued in its entirety to indicate the building and site

improvements that shall remain in place on the south portion of the property adjacent

to Palafox Street.

2. Dwg. C-103, is hereby reissued in its entirety to indicate the building and site

improvements that shall remain in place on the south portion of the property adjacent

11/11/2016

K:\279\27946.03 Palafox Demolition\Bidding and Bonds\Addendum 5\Addendum 5 ltr.docx

27946.03 ADDENDUM 5 Page 3 of 3

to Palafox Street. A note has also been added to clarify relocation of an existing fire

hydrant.

3. Dwg. C-104, is hereby reissued in its entirety to indicate the building and site

improvements that shall remain in place on the south portion of the property adjacent

to Palafox Street.

4. Dwg. C-105, is hereby reissued in its entirety to indicate the building and site

improvements that shall remain in place on the south portion of the property adjacent

to Palafox Street. Several drainage revisions will be required and are depicted.

5. Dwg. C-106, is hereby reissued in its entirety with a note that the sheet will be removed

from the set. All drainage improvements are shown on sheet C-105.

6. Dwg. C-203, is hereby reissued in its entirety to correctly identify the 20” x 16” tee to

require MJ fittings with solid sleeves and to show the fittings in the horizontal section

of the existing pipe.

7. Dwg. C-900 is herewith reissued in its entirety to incorporate a driveway detail.

 

 

 

 

 

 

 

 

 

 

APPENDIX F

SHERWIN-WILLIAMS PROTECTIVE COATINGS

PRODUCT INFORMATION AND APPLICATION BULLETINS

STEEL-SEAM FT910

COROBOND 100

DURA-PLATE 5900

NOVEMBER 11, 2016

STEEL-SEAM FT910EPOXY PATCHING AND

SURFACING COMPOUND PART A B58W910 RESIN (WHITE) PART B B58V910 HARDENER(BLACK)

Protective &

MarineCoatings

TRM.67Revised 9/11

www.sherwin-williams.com/protective

PRODUCT DESCRIPTION

STEEL-SEAM FT910 EPOXY PATCHING AND SURFACING COMPOUND is a 100% solids epoxy surfacing compound for steel or patching compound for concrete. It is formulated for ease of application with squeegee, trowel, or airless spray on horizontal, vertical or overhead applications. Cures down to 35°F/1.7°C.

• 100% solids, zero VOC • Tolerates moisture during cure• Outstanding workability• Easy to use• May be applied from 5 mils to 1/2" wft/dft vertically• May be applied up to 1" thick with aggregate addition• Cured down to 35°F/1.7°C

PRODUCT CHARACTERISTICSColor: Gray

Volume Solids: 100%, mixed

VOC (calculated): <100 g/l; 1.67 lb/gal, mixed

Mix Ratio: 3:1 by weight (premeasured kits)

Recommended Spreading Rate:Coverage: 1" cove ~ 38 lf/gal

3" cove ~ 10 lf/gal1 mil wft/dft ~ 1604 sf/gal

Drying Schedule @ 40.0 mils wet (1000 microns):@ 35°F/1.7°C @ 73°F/23°C

50% RHTo touch: 6 hours 4 hoursTo recoat:

minimum: 12 hours 6 hoursmaximum: 4 days 2 days

To cure: 7 days 7 daysIf maximum recoat time is exceeded, abrade surface before recoating.Maximum recoat time is shorter when using polyurea topcoat, refer to topcoat data page.Hardening time is temperature, humidity, and fi lm thickness dependent.Pot Life*: 50 minutes 30 minutes*@ 90°F/32°C, Pot Life is 20 minutes

Sweat-in-Time: None

Shelf Life: 36 months, unopenedStore indoors at 40°F (4.5°C) to 100°F (38°C)

Reduction: Not recommendedClean Up: Reducer R7K54

continued on back

RECOMMENDED USESMay be used as a versatile fi ller/surfacer for uneven surfaces found in formed, open or corroded concrete and masonry surfaces. May also be used as a fairing compound for weld seams, riveted con-nections, lap seams and chine angels in steel tanks prior to epoxy coating and lining applications.

Concrete Uses:• To smooth rough concrete• To fi ll bugholes, tie rod holes, cavities, honeycombs and other

surface defects on horizontal, vertical, or overhead surfaces• To form transition coves at vertical and horizontal coves

Steel Uses:• To smooth riveted, lapped or welded seams• To fi ll corrosion pits on steel surfaces• To form chine coves and fi ll sharp angles

PERFORMANCE CHARACTERISTICS

Test Name Test Method ResultsAbrasion Resistance ASTM D4060 69 mg lost

AdhesionConcrete, ASTM D4541; Steel, ASTM D1002

350 psi, 100% con-crete failure (ASTM D4541); 1,400 psi (ASTM D1002)

Elongation ASTM D412 17.9%Flammability ASTM D635 Self-extinguishingHardness, Shore D ASTM D2240 55-60Tensile Strength ASTM D412 2,672 psi

Thermal Cycling ASTM C884, 5 cycles No cracking

Page F-1

TRM.67

STEEL-SEAM FT910EPOXY PATCHING AND

SURFACING COMPOUND PART A B58W910 RESIN (WHITE) PART B B58V910 HARDENER(BLACK)

Protective &

MarineCoatings

www.sherwin-williams.com/protective

SURFACE PREPARATION

Surface must be clean, dry, and in sound condition. Remove all oil, dust, grease, dirt, loose rust, and other foreign material to ensure adequate adhesion.

Refer to product Application Bulletin for detailed surface prepara-tion information.

Minimum recommended surface preparation: Iron & Steel: SSPC SP-10/NACE2, 3 mils (75 microns) profi le Concrete: SSPC-SP13/NACE 6, or ICRI No. 310.2, CSP 4-6

Surface Preparation StandardsCondition of Surface

ISO 8501-1BS7079:A1

Swedish Std.SIS055900 SSPC NACE

White Metal Sa 3 Sa 3 SP 5 1Near White Metal Sa 2.5 Sa 2.5 SP 10 2Commercial Blast Sa 2 Sa 2 SP 6 3Brush-Off Blast Sa 1 Sa 1 SP 7 4Hand Tool Cleaning Rusted C St 2 C St 2 SP 2 -

Pitted & Rusted D St 2 D St 2 SP 2 -Power Tool Cleaning Rusted C St 3 C St 3 SP 3 -

Pitted & Rusted D St 3 D St 3 SP 3 -

TINTINGDo not tint.

APPLICATION CONDITIONSTemperature: Air and Surface: 35°F (1.7°C) minimum, 120°F (49°C) maximum Material: 50°F (10°C) minimum, 95°F (35°C) maximum At least 5°F (2.8°C) above dew pointRelative humidity: 85% maximumRefer to product Application Bulletin for detailed application information.

ORDERING INFORMATIONPackaging: Part A: 13.2 lb / 1.6 Kg/L (~1.5 gal / 5.6L) in a 3 gallon (11.3L) pail Part B: 4.4 lb / 0.53 Kg/L (~.5 gal / 1.9L) in a 1 gallon (3.78L) pailWeight per mixed unit: 17.5 lbs. ; 2.1 Kg/L (462 cu. in.)

SAFETY PRECAUTIONSRefer to the MSDS sheet before use.

Published technical data and instructions are subject to change without notice. Contact your Sherwin-Williams representative for additional technical data and instructions.

WARRANTYThe Sherwin-Williams Company warrants our products to be free of manufactur-ing defects in accord with applicable Sherwin-Williams quality control procedures. Liability for products proven defective, if any, is limited to replacement of the defec-tive product or the refund of the purchase price paid for the defective product as determined by Sherwin-Williams. NO OTHER WARRANTY OR GUARANTEE OF ANY KIND IS MADE BY SHERWIN-WILLIAMS, EXPRESSED OR IMPLIED, STATUTORY, BY OPERATION OF LAW OR OTHERWISE, INCLUDING MER-CHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.

PRODUCT INFORMATION

RECOMMENDED SYSTEMS

May be applied directly to prepared concrete or steel.

May be applied over 100% solids primers to include:• Cor-Cote HCR• Corobond 100• Dura-Plate UHS Primer• Macropoxy 920 PrePrime• Corobond LT• EnviroLastic LT

May be topcoated with a variety of coatings to include:• Acrolon 218 HS• Cor-Cote HCR, HCR FF• Cor-Cote E.N. 7000• Cor-Cote HP, HP FF• Cor-Cote SC-Sewer-Cote• Dura-Plate 235• Dura-Plate UHS Laminate• Dura-Plate UHS Epoxy• EnviroLastic Polyurea• Macropoxy 646 Epoxy• Phenicon HS Epoxy• SherFlex• ExpressCote HCR

The systems listed above are representative of the product's use, other systems may be appropriate.

DISCLAIMERThe information and recommendations set forth in this Product Data Sheet are based upon tests conducted by or on behalf of The Sherwin-Williams Company. Such information and recommendations set forth herein are subject to change and pertain to the product offered at the time of publication. Consult your Sherwin-Williams representative to obtain the most recent Product Data Information and Application Bulletin.

Page F-2

STEEL-SEAM FT910EPOXY PATCHING AND

SURFACING COMPOUND PART A B58W910 RESIN (WHITE) PART B B58V910 HARDENER(BLACK)

Protective &

MarineCoatings

TRM.67Revised 9/11

www.sherwin-williams.com/protective

SURFACE PREPARATIONS

Surface must be clean, dry, and in sound condition. Remove all oil, dust, grease, dirt, loose rust, and other foreign material to ensure adequate adhesion.

Iron & Steel (immersion service)Remove all oil and grease from surface by Solvent Cleaning per SSPC-SP1. Minimum surface preparation is Near White Metal Blast Cleaning per SSPC-SP10/NACE 2. Blast clean all surfaces using a sharp, angular abrasive for optimum surface profi le (3 mils / 75 microns). Remove all weld spatter and round all sharp edges by grinding. Prime any bare steel the same day as it is cleaned or before fl ash rusting occurs.Iron & Steel (atmospheric service)Remove all oil and grease from surface by Solvent Cleaning per SSPC-SP1. Minimum surface preparation is Near White Metal Blast Cleaning per SSPC-SP10/NACE 2. Blast clean all surfaces using a sharp, angular abrasive for optimum surface profi le (2 mils / 50 microns).Prime any bare steel the same day as it is cleaned or before fl ash rusting occurs.

Concrete and MasonryFor surface preparation, refer to SSPC-SP13/NACE 6, or ICRI No. 310.2, CSP 4-6. Surfaces should be thoroughly clean and dry. Concrete and mortar must be cured at least 28 days @ 75°F (24°C). Remove all loose mortar and foreign material. Surface must be free of laitance, concrete dust, dirt, form release agents, moisture curing membranes, loose cement and hardeners. Fill bug holes, air pockets and other voids with Steel-Seam FT910.

Follow the standard methods listed below when applicable:ASTM D4258 Standard Practice for Cleaning Concrete.ASTM D4259 Standard Practice for Abrading Concrete.ASTM D4260 Standard Practice for Etching Concrete.ASTM F1869 Standard Test Method for Measuring Moisture Vapor Emission Rate of Concrete.SSPC-SP 13/Nace 6 Surface Preparation of Concrete.ICRI No. 310.2 Concrete Surface Preparation.

Concrete, Immersion Service:For surface preparation, refer to SSPC-SP13/NACE 6, Section 4.3.1 or 1.3.2 or ICRI No. 310.2, CSP 2-3.

Surface Preparation StandardsCondition of Surface

ISO 8501-1BS7079:A1

Swedish Std.SIS055900 SSPC NACE

White Metal Sa 3 Sa 3 SP 5 1Near White Metal Sa 2.5 Sa 2.5 SP 10 2Commercial Blast Sa 2 Sa 2 SP 6 3Brush-Off Blast Sa 1 Sa 1 SP 7 4Hand Tool Cleaning Rusted C St 2 C St 2 SP 2 -

Pitted & Rusted D St 2 D St 2 SP 2 -Power Tool Cleaning Rusted C St 3 C St 3 SP 3 -

Pitted & Rusted D St 3 D St 3 SP 3 -

APPLICATION BULLETIN

APPLICATION CONDITIONS

Temperature: Air and Surface: 35°F (1.7°C) minimum, 120°F (49°C) maximum Material: 50°F (10°C) minimum, 95°F (35°C) maximum At least 5°F (2.8°C) above dew point

Relative humidity: 85% maximum

APPLICATION EQUIPMENT

The following is a guide. Changes in pressures and tip sizes may be needed for proper spray characteristics. Always purge spray equipment before use with listed reducer. Any reduction must be compliant with existing VOC regulations and compatible with the existing environmental and application conditions.

Reduction ........................Not recommended

Cleanup ...........................Reducer R7K54

Squeegee: Squeegee.......................Flat

Trowel: Trowel ............................Flat blade For applications over severely damaged or eroded concrete, use a rubber faced grout fl oat trowel.

Putty Knife .......................Acceptable

Airless Spray Pump ..............................45:1 (minimum) with gravity feed

hopper connected to a high volume lower unit (minimum 220 cc/cycle)

Pressure .........................2400-3000 psi Hose ...............................3/8" ID, with ¼” whip hose

acceptable Tip ....................................019 - .031 Gun .................................Graco Silver Plus, XTR, or Pistol

Grip Mastic Filter(s) ...........................remove Reduction .......................not recommended Have material agitated with lids open to ensure rapid mixing. Multiple passes will allow fi lm thickness up to 250 mils. An orange peel appearance is normal. If a smoother fi nished is desired, 1-2 hours after application use a 1/8" nap roller dampened with R7K54 to smooth the surface. Use a large spatula to continually wipe the material down into the hopper.

If specifi c application equipment is not listed above, equivalent equipment may be substituted.

continued on back

Page F-3

TRM.67

STEEL-SEAM FT910EPOXY PATCHING AND

SURFACING COMPOUND PART A B58W910 RESIN (WHITE) PART B B58V910 HARDENER(BLACK)

Protective &

MarineCoatings

www.sherwin-williams.com/protective

APPLICATION BULLETIN

APPLICATION PROCEDURES

Surface preparation must be completed as indicated.

Mixing Instructions: Stir each component with low speed power agitation prior to mixing. Mix 3 parts Part A (white) to 1 part Part B (black) by weight (premeasured components). Mix with low speed drill and Jiffy Mixer for approximately three minutes until uniform gray with no white or black streaks.

Temperature:Do not apply product when ambient or surface temperatures are below 35°F (1.7°C). Surface temperature must be at least 5°F (2.8°C) above dew point.

Apply paint at the recommended fi lm thickness and spreading rate as indicated below:

Recommended Spreading Rate:Coverage: 1" cove ~ 38 lf/gal

3" cove ~ 10 lf/gal1 mil wft/dft ~ 1604 sf/gal

Drying Schedule @ 40.0 mils wet (1000 microns):@ 35°F/1.7°C @ 73°F/23°C

50% RHTo touch: 6 hours 4 hoursTo recoat:

minimum: 12 hours 6 hoursmaximum: 4 days 2 days

To cure: 7 days 7 daysIf maximum recoat time is exceeded, abrade surface before recoating.Maximum recoat time is shorter when using polyurea topcoat, refer to topcoat data page.Hardening time is temperature, humidity, and fi lm thickness dependent.Pot Life*: 50 minutes 30 minutes*@ 90°F/32°C, Pot Life is 20 minutes

Sweat-in-Time: None

Application of coating above maximum or below minimum recommended spreading rate may adversely affect coating performance.

CLEAN UP INSTRUCTIONS

Clean spills and spatters immediately with Reducer R7K54. Clean tools immediately after use with Reducer R7K54. Follow manufac-turer's safety recommendations when using any solvent.

DISCLAIMERThe information and recommendations set forth in this Product Data Sheet are based upon tests conducted by or on behalf of The Sherwin-Williams Company. Such information and recommendations set forth herein are subject to change and pertain to the product offered at the time of publication. Consult your Sherwin-Williams representative to obtain the most recent Product Data Information and Application Bulletin.

PERFORMANCE TIPS

Spreading rates are calculated on volume solids and do not include an application loss factor due to surface profi le, roughness or po-rosity of the surface, skill and technique of the applicator, method of application, various surface irregularities, material lost during mixing, spillage, overthinning, climatic conditions, and excessive fi lm build. No reduction of material is recommended as it can affect fi lm build, appearance, and adhesion.

Do not mix previously catalyzed material with new.

Do not apply the material beyond recommended pot life.

Check surfaces of primer, FT910, and subsequent coats for amine blush (oily fi lm). If detected, remove before applying the next layer or coat.

For fi lling larger defects in concrete, one to four quarts of 30 to 100 mesh aggregate may be added per gallon of mixed FT910, depending on the size of hole and slump required.

Ambient air cured FT910 is acceptable for use on interior of potable water storage tanks and reservoirs when overcoated with an ANSI / NSF Std. 61 certifi ed Sherwin-Williams coating.

Refer to Product Information sheet for additional performance characteristics and properties.

SAFETY PRECAUTIONSRefer to the MSDS sheet before use.

Published technical data and instructions are subject to change without notice. Contact your Sherwin-Williams representative for additional technical data and instructions.

WARRANTYThe Sherwin-Williams Company warrants our products to be free of manufacturing defects in accord with applicable Sherwin-Williams quality control procedures. Liability for products proven defective, if any, is limited to replacement of the de-fective product or the refund of the purchase price paid for the defective product as determined by Sherwin-Williams. NO OTHER WARRANTY OR GUARANTEE OF ANY KIND IS MADE BY SHERWIN-WILLIAMS, EXPRESSED OR IMPLIED, STATUTORY, BY OPERATION OF LAW OR OTHERWISE, INCLUDING MER-CHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.

Page F-4

COROBOND™ 100EPOXY PRIMER/SEALER

PART A B58-5100 SERIES PART B B58V5100 HARDENER

Protective &

MarineCoatings

TRM.73Revised: July 23, 2013

www.sherwin-williams.com/protective

PRODUCT DESCRIPTIONCOROBOND 100 EPOXY PRIMER/SEALER is a high solids, low VOC, low viscosity, penetrating epoxy primer/sealer formulated specifi cally for use over concrete surfaces in secondary contain-ment environments.• Helps prevent "blow-back" and "outgassing"• Low viscosity• Low VOC• Fast dry• Superior penetrating characteristics• Improved visibility during application

PRODUCT CHARACTERISTICS

Finish: Flat sheen

Color: Off White, Haze Gray

Volume Solids: 98%, calculated, mixed

VOC (calculated): <100 g/l; .83 lb/gal, mixed

Mix Ratio: 2:1 by volume, premeasured

Recommended Spreading Rate per coat:Minimum Maximum

Wet mils (microns) 4.0 (100) 6.0 (150)Dry mils (microns) 4.0 (100) 6.0 (150)~Coverage sq ft/gal (m2/L) 265 (6.5) 400 (9.8)Theoretical coverage sq ft/gal (m2/L) @ 1 mil / 25 microns dft 1600 (39.2)

Apply primer to achieve uniform hiding, appearance, and com-plete wetting of the concrete surface, approximately 4.0-6.0 mils (100-150 microns) wft. Coating will be partially absorbed into the concrete. Roll out any puddles.

Drying Schedule @ 5.0 mils wet (125 microns):@ 77°F/25°C

50% RHTo touch: 2 hoursTo recoat:

minimum: 3 hoursmaximum: 24 hours*

To cure: 7 days*Can be topcoated up to 30 days after application with Phenicon HS, Phenicon HS FF, Cor-Cote HCR, Cor-Cote RPP, Macropoxy 646, Sher-Glass FF, or Steel-Seam FT910. 30 day recoat acceptable for non-immersion or secondary containment applications. Check adhesion as necessary.Primer can be topcoated even if the surface is still tacky.If maximum recoat time is exceeded, abrade surface before recoating.

Drying time is temperature, humidity, and fi lm thickness dependent.Pot Life: 45 minutesSweat-in-time: None required

Shelf Life: 36 months, unopenedStore indoors at 40°F (4.5°C) to 100°F (38°C).

Flash Point: 100°F (38°C), PMCC, mixedReduction: Not recommendedClean Up: Reducer #54, R7K54

continued on back

RECOMMENDED USES

• Corobond 100 can be used on all bare concrete surfaces where a 2 part epoxy, penetrating primer is recommended. Its low viscosity and quick recoat time allow it to be used for areas that need a fast turnaround.

• Secondary Containment

• Designed specifi cally as a high performance primer sealer for secondary containment applications

• Suitable for use in the Mining & Minerals Industry

PERFORMANCE CHARACTERISTICS

A high performance primer/sealer for new or existing bare concrete surfaces

Helps prevent "blow-back" and "outgassing" of topcoats superior penetrating characteristics

Superior penetrating characteristics

Refer to applicable topcoat for additional performance information

White in color to provide contrast with concrete

Excellent penetrating properties to provide a "tight and sound" substrate prior to subsequent topcoats

Can recoat while primer is still tacky

Designed to be topcoated

Page F-5

TRM.73

COROBOND™ 100EPOXY PRIMER/SEALER

PART A B58-5100 SERIES PART B B58V5100 HARDENER

Protective &

MarineCoatings

www.sherwin-williams.com/protective

SURFACE PREPARATION

Surface must be clean, dry, and in sound condition. Remove all oil, dust, grease, dirt, loose rust, and other foreign material to ensure adequate adhesion.

Refer to product Application Bulletin for detailed surface prepara-tion information.

Minimum recommended surface preparation: Concrete & Masonry: SSPC-SP13/NACE 6, or ICRI No. 310.2, CSP 3-6**Refer to System Selection Guide

Surface Preparation StandardsCondition of Surface

ISO 8501-1BS7079:A1

Swedish Std.SIS055900 SSPC NACE

White Metal Sa 3 Sa 3 SP 5 1Near White Metal Sa 2.5 Sa 2.5 SP 10 2Commercial Blast Sa 2 Sa 2 SP 6 3Brush-Off Blast Sa 1 Sa 1 SP 7 4Hand Tool Cleaning Rusted C St 2 C St 2 SP 2 -

Pitted & Rusted D St 2 D St 2 SP 2 -Power Tool Cleaning Rusted C St 3 C St 3 SP 3 -

Pitted & Rusted D St 3 D St 3 SP 3 -

TINTING

Do not tint.

APPLICATION CONDITIONSTemperature: 55°F (13°C) minimum, 100°F (38°C) maximum (air, surface, and material) At least 5°F (2.8°C) above dew pointRelative humidity: 85% maximum

Refer to product Application Bulletin for detailed application information.

ORDERING INFORMATIONPackaging: 3 gallon (11.3L) mix Part A: 2 gallons (7.56L) Part B: 1 gallon (3.78L) 15 gallon (75L) mix Part A: Two 5 gallon (18.9L) containers Part B: One 5 gallon (18.9L) container

Weight: 9.5 ± 0.2 lb/gal ; 1.15 Kg/L, mixed

SAFETY PRECAUTIONSRefer to the MSDS sheet before use.

Published technical data and instructions are subject to change without notice. Contact your Sherwin-Williams representative for additional technical data and instructions.

WARRANTYThe Sherwin-Williams Company warrants our products to be free of manufactur-ing defects in accord with applicable Sherwin-Williams quality control procedures. Liability for products proven defective, if any, is limited to replacement of the defec-tive product or the refund of the purchase price paid for the defective product as determined by Sherwin-Williams. NO OTHER WARRANTY OR GUARANTEE OF ANY KIND IS MADE BY SHERWIN-WILLIAMS, EXPRESSED OR IMPLIED, STATUTORY, BY OPERATION OF LAW OR OTHERWISE, INCLUDING MER-CHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.

PRODUCT INFORMATION

RECOMMENDED SYSTEMS

Dry Film Thickness / ct. Mils (Microns)Concrete, Secondary Containment:Concrete & Masonry:1 ct. Corobond 100 Epoxy 4.0-6.0 (100-150) Primer/Sealer Apply primer to achieve uniform hiding, appearance, and complete wetting of the concrete surface. Coating will be partially absorbed into the concrete. Roll out any puddles.1-2 cts. Kem Cati-Coat HS Epoxy 10.0-20.0 (250-500) Filler/Sealer, as required to fi ll voids and bugholes to provide a continuous substrate.1-2 cts. Cor-Cote E.N. 7000 Epoxy 10.0-14.0* (250-350)* Novolac Coating

*Dependent on the severity of the environment, other acceptable topcoats may include Cor-Cote HCR FF, PheniconHS, or Shelcote II.

Mortar System:1 ct. Corobond 100 Epoxy 4.0-6.0 (100-150) Primer/Sealer 1 ct. Cor-Cote HCR Epoxy with 70 lbs Type T Aggregate per 1.25 gallons3/16" dft yields 44 sq. ft.1 ct. Cor-Cote HCR Epoxy 15.0-20.0 (375-500)1 ct. Cor-Cote HCR FF Flake Filled 15.0-20.0 (375-500) Epoxy

The systems listed above are representative of the product's use, other systems may be appropriate.

DISCLAIMERThe information and recommendations set forth in this Product Data Sheet are based upon tests conducted by or on behalf of The Sherwin-Williams Company. Such information and recommendations set forth herein are subject to change and pertain to the product offered at the time of publication. Consult your Sherwin-Williams representative to obtain the most recent Product Data Information and Application Bulletin.

Page F-6

COROBOND™ 100EPOXY PRIMER/SEALER

PART A B58-5100 SERIES PART B B58V5100 HARDENER

Protective &

MarineCoatings

TRM.73Revised: July 23, 2013

www.sherwin-williams.com/protective

SURFACE PREPARATIONS

Surface must be clean, dry, and in sound condition. Remove all oil, dust, grease, dirt, loose rust, and other foreign material to ensure adequate adhesion.

Concrete and MasonryFor surface preparation, refer to SSPC-SP13/NACE 6, or ICRI No. 310.2, CSP 3-6*. Surfaces should be thoroughly clean and dry. Concrete and mortar must be cured at least 28 days @ 75°F (24°C). Remove all loose mortar and foreign material. Surface must be free of laitance, concrete dust, dirt, form release agents, moisture curing membranes, loose cement and hardeners. Fill bug holes, air pockets and other voids with Steel-Seam FT910.

Follow the standard methods listed below when applicable:ASTM D4258 Standard Practice for Cleaning Concrete.ASTM D4259 Standard Practice for Abrading Concrete.ASTM D4260 Standard Practice for Etching Concrete.ASTM F1869 Standard Test Method for Measuring Moisture Vapor Emission Rate of Concrete.SSPC-SP 13/Nace 6 Surface Preparation of Concrete.ICRI No. 310.2 Concrete Surface Preparation.

*Refer to System Selection Guide

Surface Preparation StandardsCondition of Surface

ISO 8501-1BS7079:A1

Swedish Std.SIS055900 SSPC NACE

White Metal Sa 3 Sa 3 SP 5 1Near White Metal Sa 2.5 Sa 2.5 SP 10 2Commercial Blast Sa 2 Sa 2 SP 6 3Brush-Off Blast Sa 1 Sa 1 SP 7 4Hand Tool Cleaning Rusted C St 2 C St 2 SP 2 -

Pitted & Rusted D St 2 D St 2 SP 2 -Power Tool Cleaning Rusted C St 3 C St 3 SP 3 -

Pitted & Rusted D St 3 D St 3 SP 3 -

APPLICATION BULLETIN

APPLICATION CONDITIONS

Temperature: 55°F (13°C) minimum, 100°F (38°C) maximum (air, surface, and material) At least 5°F (2.8°C) above dew point

Relative humidity: 85% maximum

APPLICATION EQUIPMENT

The following is a guide. Changes in pressures and tip sizes may be needed for proper spray characteristics. Always purge spray equipment before use with listed reducer. Any reduction must be compliant with existing VOC regulations and compatible with the existing environmental and application conditions.

Reduction ........................Not recommended

Clean Up ..........................Reducer #54, R7K54

Airless Spray Pump..............................30:1 minimum Hose...............................3/8" ID Tip ...................................019" Filter ...............................60 mesh

Brush Brush..............................Natural Bristle

Roller Cover .............................3/8" woven with solvent resistant core

If specifi c application equipment is not listed above, equivalent equipment may be substituted.

continued on back

Page F-7

TRM.73

COROBOND™ 100EPOXY PRIMER/SEALER

PART A B58-5100 SERIES PART B B58V5100 HARDENER

Protective &

MarineCoatings

www.sherwin-williams.com/protective

APPLICATION BULLETIN

APPLICATION PROCEDURESSurface preparation must be completed as indicated.Mixing Instructions: Mix components only after all surfaces are completely prepared and ready to be coated. Thoroughly agitate each component using low speed mechanical agitation, i.e., Jiffy Blade model ES. Then combine 2 parts by volume of Part A with 1 part by volume Part B. Using mechanical agitation, Jiffy Blade ES, thoroughly mix material for three minutes at 250 rpm. Only mix full units. Be sure to mix material from the bottom and sides of the containers. Apply paint at the recommended fi lm thickness and spreading rate as indicated below:

Recommended Spreading Rate per coat:Minimum Maximum

Wet mils (microns) 4.0 (100) 6.0 (150)Dry mils (microns) 4.0 (100) 6.0 (150)~Coverage sq ft/gal (m2/L) 265 (6.5) 400 (9.8)Theoretical coverage sq ft/gal (m2/L) @ 1 mil / 25 microns dft 1600 (39.2)

Apply primer to achieve uniform hiding, appearance, and com-plete wetting of the concrete surface, approximately 4.0-6.0 mils (100-150 microns) wft. Coating will be partially absorbed into the concrete. Roll out any puddles.

Drying Schedule @ 5.0 mils wet (125 microns):@ 77°F/25°C

50% RHTo touch: 2 hoursTo recoat:

minimum: 3 hoursmaximum: 24 hours*

To cure: 7 days*Can be topcoated up to 30 days after application with Phenicon HS, Phenicon HS FF, Cor-Cote HCR, Cor-Cote RPP, Macropoxy 646, Sher-Glass FF, or Steel-Seam FT910. 30 day recoat acceptable for non-immersion or secondary containment applications. Check adhesion as necessary.Primer can be topcoated even if the surface is still tacky.If maximum recoat time is exceeded, abrade surface before recoating.

Drying time is temperature, humidity, and fi lm thickness dependent.Pot Life: 45 minutesSweat-in-time: None required

Application of coating above maximum or below minimum recommended spreading rate may adversely affect coating performance.

CLEAN UP INSTRUCTIONSClean spills and spatters immediately with Reducer #54, R7K54. Clean tools immediately after use with Reducer #54, R7K54. Follow manufacturer's safety recommendations when using any solvent.

DISCLAIMERThe information and recommendations set forth in this Product Data Sheet are based upon tests conducted by or on behalf of The Sherwin-Williams Company. Such information and recommendations set forth herein are subject to change and pertain to the product offered at the time of publication. Consult your Sherwin-Williams representative to obtain the most recent Product Data Information and Application Bulletin.

PERFORMANCE TIPS

When using spray application, use a 50% overlap with each pass of the gun to avoid holidays, bare areas, and pinholes. If necessary, cross spray at a right angle

Spreading rates are calculated on volume solids and do not include an application loss factor due to surface profi le, roughness or po-rosity of the surface, skill and technique of the applicator, method of application, various surface irregularities, material lost during mixing, spillage, overthinning, climatic conditions, and excessive fi lm build.

No reduction of material is recommended as it can affect fi lm build, appearance, and adhesion.

Do not apply the material beyond recommended pot life.

Do not mix previously catalyzed material with new.

In order to avoid blockage of spray equipment, clean equipment before use or before periods of extended downtime with Reducer #54, R7K54.

Refer to Product Information sheet for additional performance characteristics and properties.

SAFETY PRECAUTIONSRefer to the MSDS sheet before use.

Published technical data and instructions are subject to change without notice. Contact your Sherwin-Williams representative for additional technical data and instructions.

WARRANTYThe Sherwin-Williams Company warrants our products to be free of manufacturing defects in accord with applicable Sherwin-Williams quality control procedures. Liability for products proven defective, if any, is limited to replacement of the de-fective product or the refund of the purchase price paid for the defective product as determined by Sherwin-Williams. NO OTHER WARRANTY OR GUARANTEE OF ANY KIND IS MADE BY SHERWIN-WILLIAMS, EXPRESSED OR IMPLIED, STATUTORY, BY OPERATION OF LAW OR OTHERWISE, INCLUDING MER-CHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.

Page F-8

Revised: Sept 8, 2015

DURA-PLATE® 5900(FORMERLY COR-COTE SC PLUS)

HigH Build Epoxy

part a B62W465 WHitE part a B62a465 gray part B B62V465 HardEnEr

Protective &

MarineCoatings

www.sherwin-williams.com/protective

Product descriPtion

DURA-PLATE 5900 is a high build, 100% solids epoxy designed for corrosion protection of concrete and steel in municipal and industrial wastewater treatment facilities, especially where a high build coating is required.

• 100%solids• LowVOC• Resistanttowaterandwastewatertreatmentimmersion• MaybeappliedtoanSSD(SaturatedSurfaceDry)substrate• MaybeappliedasMortarSystemutilizingTypeDPAggregate

Product characteristics

Finish: Matte

Color: White, Gray

Volume Solids: 100%

VOC (measured): 160g/L(EPAMethod24)

Weight Solids: 100%, calculated mixed

Mix Ratio: 1:1, mix by volume

Recommended Spreading Rate per coat:Minimum Maximum

Wet mils(microns) 15.0 (375) 125.0 (3125)Dry mils(microns) 15.0 (375) 125.0 (3125)~Coverage sq ft/gal(m2/L) 12.8 (0.3) 106.9 (7.1)

Drying Schedule @ 120.0 mils wet (3000 microns):@ 77°F/25°C

50% RHTo touch: 2 hoursTo handle: 8 hoursTo recoat:

Minimum: 8 hoursMaximum: 2 weeks

Cure to service: 2 daysIf maximum recoat time is exceeded, scarify surface before recoating.Drying time is temperature, humidity, and film thickness dependent.Pot Life: 30minutesSweat-in-Time: None

Shelf Life: 9 months, unopened Store indoorsat40°F (4.5°C)to100°F(38°C).

Flash Point: 204°F(95°C),PMCCASTMD93

Clean Up/Reducer: R2KT4orMEK.Donotthinmaterial.

continued on back

recommended uses

Protectsconcreteandsteelsurfacesinimmersionandatmosphericexposure.

Ideally suited for coating, lining, and containment applications in water and wastewater facilities including:• Liftstations •Concretepipe •Wetwells • Steelpipe •Manholes •Sumps• Digesters •Trenches •Clarifiers• Sluiceways •Basins •Influentchambers

Performance characteristics

Substrate*: SteelSurface Preparation*:SSPC-SP10System Tested*: [email protected](2000microns)to100.0mils(2500microns)dft*unless otherwise noted below

Test Name Test Method ResultsAbrasion ASTMD4060 104.5mglossAbsorption* ASTMC413 0.03%Adhesion (Concrete) ASTMD7234 700psi

Adhesion (Steel) ASTMD4541 2000 psiDry Heat Resistance

D2485Quenchtest only 300°F(149°C)

Hardness, Shore D ASTM2240 75

ImmersionASTMD6943,10 months fresh water

Rating10perASTMD610forrusting;Rating10perASTMD714forblistering

Impact Resistance ASTMD2794 30in.lbs.

*MortarSystem

Epoxycoatingsmaydarkenordiscolorfollowingapplicationandcuring and may chalk when exposed to sunlight.

Page F-9

Revised: Sept 8, 2015

DURA-PLATE® 5900(FORMERLY COR-COTE SC PLUS)

HigH Build Epoxy

part a B62W465 WHitE part a B62a465 gray part B B62V465 HardEnEr

Protective &

MarineCoatings

www.sherwin-williams.com/protective

surface PreParationSurface must be clean, dry, and in sound condition. Remove all oil, dust, grease, dirt, loose rust, and other foreign material to ensure adequate adhesion.

RefertoproductApplicationBulletinfordetailedsurfaceprepara-tion information.Minimumrecommendedsurfacepreparation:* Iron & Steel: Atmospheric: SSPC-SP6/NACE3,2mil(50micron) profile Immersion: SSPC-SP10/NACE2,2-3mil (50-75micron)profile* Concrete&Masonry: Immersion: SSPC-SP13/NACE6-4.3.1or4.3.2,or ICRINo.310.2R,CSP3-5

Surface Preparation StandardsCondition of Surface

ISO 8501-1BS7079:A1

Swedish Std.SIS055900 SSPC NACE

WhiteMetal Sa3 Sa3 SP5 1NearWhiteMetal Sa 2.5 Sa 2.5 SP10 2CommercialBlast Sa 2 Sa 2 SP6 3Brush-OffBlast Sa 1 Sa 1 SP7 4HandToolCleaning Rusted CSt2 CSt2 SP2 -

Pitted&Rusted DSt2 DSt2 SP2 -PowerToolCleaning Rusted CSt3 CSt3 SP3 -

Pitted&Rusted DSt3 DSt3 SP3 -

tintingDonottint.

aPPlication conditionsTemperature: 50°F(10°C)minimum,100°F(38°C) maximum (Air,surface,&material) Atleast5°F(2.8°C)abovedewpoint

Relative humidity: 85% maximum

RefertoproductApplicationBulletinfordetailedapplicationinformation.

ordering informationPackaging: PartA: 5gallon(18.9L)container PartB: 5gallon(18.9L)containerWeight: 12.6±0.2lb/gl 1.5Kg/L

safety PrecautionsRefertotheMSDSsheetbeforeuse.Publishedtechnicaldataandinstructionsaresubjecttochangewithoutnotice.ContactyourSherwin-Williamsrepresentativeforadditionaltechnicaldataandinstructions.

WarrantyTheSherwin-WilliamsCompanywarrantsourproductstobefreeofmanufactur-ing defects in accord with applicable Sherwin-Williams quality control procedures. Liabilityforproductsprovendefective,ifany,islimitedtoreplacementofthedefec-tive product or the refund of the purchase price paid for the defective product as determinedbySherwin-Williams.NOOTHERWARRANTYORGUARANTEEOFANYKINDISMADEBYSHERWIN-WILLIAMS,EXPRESSEDORIMPLIED,STATUTORY,BYOPERATIONOFLAWOROTHERWISE,INCLUDINGMER-CHANTABILITYANDFITNESSFORAPARTICULARPURPOSE.

product information

recommended systems

Dry Film Thickness / ct. Mils (Microns)

Steel (Immersion Service):1ct. Dura-Plate5900 15.0-125.0(375-3125)

Dura-Plate5900canbeappliedupto125mils(3125microns)thick in areas requiring protection from erosion. Concrete (Immersion Service):1ct. Corobond100EpoxyPrimer* 4.0-6.0 (100-150)1ct. Dura-Plate5900 40.0-125.0(1000-3125)

Concrete, Mortar (Lining and Resurfacing):1ct. Dura-Plate5900with28lbs.of TypeDPAggregateper2gallons 125-200 (3125-5000)

*Primerisoptional.OtherAcceptablePrimers:CorobondLTDura-Plate235MPEConsultyourSherwin-WilliamsRepresentativeforotherprimeroptions.

Thesystemslistedabovearerepresentativeoftheproduct'suse,other systems may be appropriate.

disclaimerTheinformationandrecommendationssetforthinthisProductDataSheetarebasedupontestsconductedbyoronbehalfofTheSherwin-WilliamsCompany.Suchinformationandrecommendationssetforthhereinaresubjecttochangeandpertaintotheproductofferedatthetimeofpublication.ConsultyourSherwin-WilliamsrepresentativetoobtainthemostrecentProductDataInformationandApplicationBulletin.

Page F-10

Revised: Sept 8, 2015

DURA-PLATE® 5900(FORMERLY COR-COTE SC PLUS)

HigH Build Epoxy

part a B62W465 WHitE part a B62a465 gray part B B62V465 HardEnEr

Protective &

MarineCoatings

www.sherwin-williams.com/protective

surface PreParations

Surface must be clean, surface dry, and in sound condition. Remove all oil, dust, grease, dirt, loose rust, and other foreign material to ensure adequate adhesion.

Carbon Steel, Immersion Service: Cleananddegrease the surface prior to abrasive blasting perSSPC-SP1SolventCleaning.MethodsdescribedinSSPC-SP1include solvents, alkali, detergent/water, emulsions, and steam. ThesurfaceshallbeabrasiveblastedtoSSPC-SP10/NACENo.2Near-WhiteBlastCleaningwitha2-3milprofile.Theanchorpatternshallbesharpwithnoevidenceofapolishedsurface.Thefinishedsurfaceshallbefreeofallvisibleoil,grease,dust,dirt,millscale, rust, coating, oxides, corrosion products, and other foreign matterwithnomorethan5%staining.Afterblasting,alldustandloose residue should be removed from the surface by acceptable means.Coatsteelthesamedayasitispreparedandpriortotheformation of rust.

Concrete and Masonry, Immersion Service: Decontaminationoftheconcretesurfacerequirestheremovalofoils, grease, wax, fatty acids and other contaminants and may be accomplished by the use of detergent scrubbing with a Sherwin-Williamscleaneranddegreaser,lowpressurewatercleaning(lessthan5,000psi),steamcleaning,orchemicalcleaning.Thepreferredmethods forcreatingasurfaceprofile, including the removalofdirt, dust, laitance and curing compounds, is abrasive blasting or scarifyingtoachieveanICRIsurfaceequivalenttoCSP3-5.Fillallcracks, voids, and bug holes with cementitious grout, Steel-Seam FT910orDura-Plate5800grout.SeeICRITechnicalGuidelineNo.310.2Rforadditionalinformation.

Surface Preparation StandardsCondition of Surface

ISO 8501-1BS7079:A1

Swedish Std.SIS055900 SSPC NACE

WhiteMetal Sa3 Sa3 SP5 1NearWhiteMetal Sa 2.5 Sa 2.5 SP10 2CommercialBlast Sa 2 Sa 2 SP6 3Brush-OffBlast Sa 1 Sa 1 SP7 4HandToolCleaning Rusted CSt2 CSt2 SP2 -

Pitted&Rusted DSt2 DSt2 SP2 -PowerToolCleaning Rusted CSt3 CSt3 SP3 -

Pitted&Rusted DSt3 DSt3 SP3 -

application BullEtin

aPPlication conditionsTemperature: 50°F (10°C)minimum,100°F (38°C) maximum (Air,surface,&material) Atleast5°F(2.8°C)abovedewpoint

Relative humidity: 85% maximum

aPPlication equiPment

Thefollowingisaguide.Changesinpressuresandtipsizesmaybeneededforproperspraycharacteristics.Alwayspurgesprayequipmentbeforeusewithlistedreducer.AnyreductionmustbecompliantwithexistingVOCregulationsandcompatiblewiththeexisting environmental and application conditions.

Application requiresahopper feeddeliveryofmixedmaterials.Changesinpressuresandtipsizesmaybeneedsforproperspraycharacteristics.

Clean Up Solvent ............ReducerR2KT4orMEK

Airless Spray Pump..............................XtremeMix45:1or50:1 Pressure.........................2,200-2,500 psi Hose...............................1/2"IDhose(25ft) Gun ................................SilverFlexorXTR Tip ..................................21-31 Filter ...............................None Reduction .......................None

Plural Component Equipment: Pump................................GracoXtremeMix50and70,XM7,

XP50and70Pressure............................3500psiHose..................................3/8"IDTip.......................................025"-.031"Pumpheatersetting..........90°F-110°F(32°C-43°C)MaterialTemperatureatguntip............................80°F-110°F

(27°C-43°C),varyasneededBrush Brush..............................Not recommended

Roller Cover .............................Not recommended

Ifspecificapplicationequipmentisnotlistedabove,equivalentequipment may be substituted.

continued on back

Page F-11

Revised: Sept 8, 2015

DURA-PLATE® 5900(FORMERLY COR-COTE SC PLUS)

HigH Build Epoxy

part a B62W465 WHitE part a B62a465 gray part B B62V465 HardEnEr

Protective &

MarineCoatings

www.sherwin-williams.com/protective

application BullEtin

aPPlication Procedures

Surface preparation must be completed as indicated.

Mixing Instructions:Mixcontentsofeachcomponentthoroughlywithlowspeedpoweragitation.Makecertainnopigmentremainsonthebottomofthecan.ThencombineonepartsbyvolumeofPartAwithonepartbyvolumeofPartB.Thoroughlyagitatethemixturewithpoweragitation.Fillhoppercontainerwithmixedcoating.

Applypaintattherecommendedfilmthicknessandspreadingrate as indicated below:

Recommended Spreading Rate per coat:Minimum Maximum

Wet mils(microns) 15.0 (375) 125.0 (3125)Dry mils(microns) 15.0 (375) 125.0 (3125)~Coverage sq ft/gal(m2/L) 12.8 (0.3) 106.9 (7.1)

Drying Schedule @ 120.0 mils wet (3000 microns):@ 77°F/25°C

50% RHTo touch: 2 hoursTo handle: 8 hoursTo recoat:

Minimum: 8 hoursMaximum: 2 weeks

Cure to service: 2 daysIf maximum recoat time is exceeded, scarify surface before recoating.Drying time is temperature, humidity, and film thickness dependent.Pot Life: 30minutesSweat-in-Time: None

Application of coating abovemaximumor belowminimumrecommended spreading rate may adversely affect coating performance.

For Mortar Applications: (lining and resurfacing)RefertoProtective&Marinetechnicalbulletin-Dura-PlateEpoxyMortarsformixinginstructions

clean uP instructionsCleanspillsandspattersimmediatelywithReducer.Cleanpump,hose,andgunbyflushingsystemwithR2KT4.Thenflushtoolsim-mediatelyafterusewithMEK.

disclaimerTheinformationandrecommendationssetforthinthisProductDataSheetarebasedupontestsconductedbyoronbehalfofTheSherwin-WilliamsCompany.Suchinformationandrecommendationssetforthhereinaresubjecttochangeand

Performance tiPs

Stripe coat all crevices, welds, and sharp angles to prevent early failure in these areas.

When using spray application, use a 50% overlap with each pass of the gun to avoid holidays, bare areas, and pinholes. If necessary, cross spray at a right angle

Spreading rates are calculated on volume solids and do not include anapplicationlossfactorduetosurfaceprofile,rough-nessorpo-rosity of the surface, skill and technique of the applicator, method of application, various surface irregularities, material lost during mixing, spillage, over thinning, climatic conditions, and excessive filmbuild.

Donotmixpreviouslycatalyzedmaterialwithnew.

Donotapplythematerialbeyondrecommendedpotlife.

In order to avoid blockage of spray equipment, clean equipment before use or before periods of extended downtime.

Tintingisnotrecommendedforimmersionservice.

For Immersion Service(ifrequired):HolidaytestinaccordancewithASTMD5162forsteel,orASTMD4787forconcrete.

RefertoProductInformationsheetforadditionalperformancecharacteristics and properties.

safety Precautions

RefertotheMSDSsheetbeforeuse.

Publishedtechnicaldataandinstructionsaresubjecttochangewithoutnotice.ContactyourSherwin-Williamsrepresentativeforadditionaltechnicaldataandinstructions.

WarrantyTheSherwin-WilliamsCompanywarrantsourproductstobefreeofmanufacturingdefects in accord with applicable Sherwin-Williams quality control procedures. Liabilityforproductsprovendefective,ifany,islimitedtoreplacementofthede-fective product or the refund of the purchase price paid for the defective product asdeterminedbySherwin-Williams.NOOTHERWARRANTYORGUARANTEEOFANYKINDISMADEBYSHERWIN-WILLIAMS,EXPRESSEDORIMPLIED,STATUTORY,BYOPERATIONOFLAWOROTHERWISE,INCLUDINGMER-CHANTABILITYANDFITNESSFORAPARTICULARPURPOSE.