Date: 2-11-2018 Test Reference Number: M021118-02/TAB Place: Waalwijk MR/vs010315 Model (name/type): CWK-H-D-100-3-2,5 Result: Class D Air temperature (ºC) 22 Atmospheric pressure (Pa) 102160 Pressure �me 120 sec. (standard) Correcon factor 1,001 Surface Area: 0,84 m 2 Case width (m) 0,238 Measuring Equipment: Case Height (m) 0,180 Air leakage tester type: Airow HVLT MK4 M (230V) Duct Length (m) 1 Serial No: 125286 Tielenstraat 17, 5145 RC Waalwijk Other Date cer�ficaon: 12-09-2017 Calibraon cert.nr. 21700548 Stac Leakage EN 1751 EN 1751 EN 1751 Reading Pressure Leakage Rig Leakage Duct Surface Corrected Class A Class B Class C (Pa) (N l/s) (l/s) (l/s/m 2 ) (l/s/m 2 ) (l/s/m 2 ) (l/s/m 2 ) 1 400 1,03 1,01 0,024 0,024 1,326 0,442 - 2 1000 1,67 1,65 0,024 0,024 - 0,802 0,267 3 2000 2,39 2,35 0,048 0,048 - - 0,420 From DW/144 Duct Pressure Class Stac pressure limit Posi�ve Nega�ve 1 2 3 4 Pa Pa m/s Low - Class A 500 500 10 Medium - Class B 1000 750 20 High - Class C 2000 750 40 @ Pa: Approved and cer�fied by Cer�ficate nr. : x 5 l/s/m2 0.027 x p 0.65 0.009 x p 0.65 0.003 x p 0.65 0,089 0,140 Maximum Air Velocity Air leakage limits litres per second per square metre of duct surface area Visual deformaon? No - EN 15727 Test Report Casing Air Leakage Rate Tested by: Tom Absil Witness by: Sander v/d Hoven Approximate EN 1751 Class D (l/s/m 2 ) 100 1000 0,03 0,25 2,50 OVERPRESSURE Pa LEAKAGE l/s/m 2 EN 1751 Figure C.2 - Classicaon of Case Leakage A B C D [email protected], www.inatherm.nl

EN 15727 Test Report Casing Air Leakage Rate

  • Upload
    others

  • View
    11

  • Download
    0

Embed Size (px)

Citation preview

Page 1: EN 15727 Test Report Casing Air Leakage Rate

Date: 2-11-2018 Test Reference Number: M021118-02/TABPlace: Waalwijk MR/vs010315

Model (name/type): CWK-H-D-100-3-2,5 Result: Class D

Air temperature (ºC) 22Atmospheric pressure (Pa) 102160 Pressure �me 120 sec. (standard)

Correc�on factor 1,001 Surface Area: 0,84 m2

Case width (m) 0,238 Measuring Equipment:Case Height (m) 0,180 Air leakage tester type: Airflow HVLT MK4 M (230V)Duct Length (m) 1 Serial No: 125286 Tielenstraat 17, 5145 RC WaalwijkOther Date cer�fica�on: 12-09-2017

Calibra�on cert.nr. 21700548

Sta�c Leakage EN 1751 EN 1751 EN 1751Reading Pressure Leakage Rig Leakage Duct Surface Corrected Class A Class B Class C

(Pa) (N l/s) (l/s) (l/s/m2) (l/s/m2) (l/s/m2) (l/s/m2)

1 400 1,03 1,01 0,024 0,024 1,326 0,442 -2 1000 1,67 1,65 0,024 0,024 - 0,802 0,2673 2000 2,39 2,35 0,048 0,048 - - 0,420

From DW/144Duct Pressure Class Sta�c pressure limit

Posi�ve Nega�ve1 2 3 4

Pa Pa m/s

Low - Class A 500 500 10Medium - Class B 1000 750 20High - Class C 2000 750 40

@ Pa:

Approved and cer�fied by Cer�ficate nr. :

x

5l/s/m2

0.027 x p 0.65

0.009 x p 0.65

0.003 x p 0.65

0,0890,140

Maximum Air Velocity

Air leakage limits litres per second per square metre of duct surface area

Visual deforma�on? No

-

EN 15727 Test Report Casing Air Leakage Rate

Tested by: Tom Absil Witness by: Sander v/d Hoven

ApproximateEN 1751Class D(l/s/m2)

100

1000

0,03 0,25 2,50

OVE

RPRE

SSU

RE P

a

LEAKAGE l/s/m2

EN 1751 Figure C.2 - Classifica�on of Case Leakage