Energy Stress on Surge Arrester

Embed Size (px)

Citation preview

  • 8/12/2019 Energy Stress on Surge Arrester

    1/6

    CALCULATION OF ENERGY STRESS ON SURGE ARRESTERS IN

    275kV TRANSMISSION LINES

    R. Bhattarai*, H. Griffiths, N. Harid and A. Haddad

    High Voltage Energy Systems Group, School of Engineering, Cardiff University, UK

    *Email: [email protected]

    Abstract: Application of line surge arresters is found to be an efficient tool to improve the

    lightning performance of transmission lines. Suitable selection of arrester rating and configurationalong the line are crucial for achieving improved reliability of the line. This paper presents a

    systematic calculation of energy stress carried out on gapless Zinc-Oxide surge arresters applied to

    a 275 kV double circuit shielded transmission line. An operational line was modelled in TFlash,

    and simulations were carried out under conditions of lightning strokes hitting the phase conductor

    and the shield wire. To determine arrester characteristics, a number of important parameters that

    influence energy stress calculations were evaluated. The arrester failure performance analysis wascarried out to estimate the overall reliability of the transmission line. Stroke to phase conductor

    was found to be the main source of arrester failure in the line.

    1. INTRODUCTION

    Faults caused by lightning are the main source of line

    outages especially in areas with high ground flash

    density, high earth resistivity and poor shielding.

    Previous studies [1-3] have shown that lightning

    performance can be guaranteed by careful selection and

    location of zinc-oxide (ZnO) surge arresters. These linearresters are exposed to high-magnitude lightning

    strikes and have to survive higher energy discharge duty

    imposed by the lightning current.

    In comparison to the substation arrester, the line arrester

    may experience more energy stress. This is because the

    incoming surge to a station is limited either by lineinsulator flashover or by the discharge to earth through

    shield wire. Therefore, adequate selection of a line

    arrester also depends upon assessing its energy

    absorption capability so that it does not fail under

    conditions of lightning striking either the phase

    conductor or the shield wire.

    In this study, a systematic calculation of energy stress

    was carried out on gapless ZnO surge arresters installed

    on a 275 kV double circuit shielded transmission line.The line was modelled in EPRIs TFLASH program

    which is designed to examine all arrester options andtheir potential benefits to improving line performance

    [4]. The simulation was carried out under conditions of

    lightning stroke hitting the phase conductor (shielding

    failure) and the shield wire (which may lead to

    backflashover). In both cases, the energy stress in the

    arrester depends on the line and lightning strokeparameters. A parametric analysis was carried out to

    select the appropriate arrester, considering different

    parameters that affect its energy calculation. Using these

    studies, it is possible to determine an optimum

    application of surge arresters, and make a more accurateselection of arrester rating in terms of protective level

    and energy stress. Furthermore, arrester failure

    performance analysis was carried out to assess the risk

    of failure due to lightning strikes onto the phase

    conductor and shield wire of surge arresters installed on

    the line. A statistical simulation was performed to

    calculate the risk of arrester failure on the line.

    2. SIMULATED DATA

    2.1. 275kV transmission line

    An existing 35 km long, 275 kV double circuit shielded

    line was considered in this study. The line with 300 m

    span length was assumed to be located on flat terrain

    with ground flat density of 0.5 flashes per kilometre

    square per year (flashes/km2/year). Figure 1 show thetower structure and conductor geometry in each tower

    of the line.

    Twin 175 mm2 Lynx type ACSR conductors wereused in phase conductors and a single Lynx ACSR

    conductor was used as shield wire. The diameter of each

    conductor is 19.53 mm, and the bundle spacing of 30.48

    cm was used for the twin phase conductors.

    A 3.31 m long line insulator string composed of 16

    individual glass insulator disc producing an overallcritical flashover voltage (CFO) of 1646 kV was used.

    2.2. Surge arrester

    The following specifications of zinc-oxide surge

    arresters were used.

    Nominal discharge current : 10 kAMax. continuous operating voltage (MCOV) : 220 kV

    Energy capability : 7.8 kJ/kV of MCOV

    Table 1 summarises the arrester V-I curve under an 8/20

    impulse.

    Table 1: Arrester discharge voltage for 8/20 impulsecurrent.

    I (kA) 3 5 10 15 20 40

    V(kV) 581 601 635 666 690 762

    ISBN 978-0-620-44584-9

    Proceedings of the 16th International Symposium on High Voltage Engineering

    Copyright c 2009 SAIEE, Innes House, Johannesburg

    Pg. 1 Paper G-11

  • 8/12/2019 Energy Stress on Surge Arrester

    2/6

    3. TFLASH MODEL

    Modelling transmission line components in TFLASH is

    facilitated with its existing database of towers, earth

    types, insulators, conductors and arresters [5]. Facilities

    are provided within the program to allow further input

    and modifications of the above components if required.

    A brief description of the line model used in this study

    is given in the following sections.

    3.1. Line model

    Each span on the transmission line is represented as a

    multiphase untransposed distributed parameter line

    section. In order to avoid reflections in the line,matching impedances were used at both terminations of

    the line. Each span section is further divided into

    smaller sub sections to enable stroke simulation at anumber of points along the spans. In this model, 8

    towers from the middle of the line were used in each

    direction with lightning surge striking at a mid tower

    position.

    A high-voltage transmission tower can be considered as

    a network of short transmission lines carrying transientcurrent from its top to the earth and its reflection back

    towards the top [5]. Therefore, in this study, the tower

    itself is modelled as a short vertical transmission line

    section with constant surge impedance describing the

    voltage produced on the tower, per unit current flowing

    through it. The steel lattice tower has surge impedance

    of 173.1 calculated using Equation (1) [6].

    +=

    21

    avg1

    Thh

    rtan5.0cotln60Z (1)

    where, h1 and h2 are the tower heights from base to

    midsection and midsection to the tower top respectively

    and ravg is the weighted average tower radius given byEquation (2).

    ( )

    )hh(

    hrhhrhrr

    21

    1321221avg

    +

    +++= (2)

    where, r1, r2 and r3 are the radii at the top, midsection

    and base of the tower respectively.

    The tower footing resistance plays an important role in

    calculating the arrester energy. A non-linear tower

    footing resistance model as shown in Figure 2 was used.

    The resistance is calculated using Equation (3) [7].

    g

    lci

    I

    I1

    RR

    +

    = (3)

    With;2lc

    g

    gR2

    EI

    = (4)

    where, Rlcis the low-current tower footing resistance,

    is the soil resistivity, I is the stroke current through the

    tower footing and, Eg the soil ionisation criticalelectrical field (4 kV/cm).

    In this study, a low current tower footing resistance of

    10 with soil resistivity of 200 m was used in case of

    a stroke hitting the phase conductor, and a resistance

    value of 80 with soil resistivity of 1600 m was used

    for the case of a stroke hitting the shield wire at the

    tower top.

    3.2. Arrester model

    In TFLASH, arresters are modelled as nonlinear

    voltage-controlled current sources, and the arrestercurrent is calculated based on the applied voltage across

    the arrester [5]. Therefore, the resulting equivalent

    circuit of an arrester installed between a tower structure

    and a line conductor is shown in Figure 3.

    The tower and line conductor node voltages are given

    by Equations (5) and (6) respectively.

    30.48 cm

    19.24 m(12.19) m

    25.33 m(18.26) m

    31.42 m(24.37) m

    36.88 m(30.22) m

    4.57m

    4.26m

    4.03m

    22.55 m

    6.09 m

    6.09 m

    2.15 m

    A1

    A2

    B1 B2

    C1

    C2

    E

    Figure 1: 275kV shielded double circuit transmission

    line tower. Values in brackets are mid-span heights.

    I

    Rlc

    Figure 2:Non-linear tower footing resistance model.

    ISBN 978-0-620-44584-9

    Proceedings of the 16th International Symposium on High Voltage Engineering

    Copyright c 2009 SAIEE, Innes House, Johannesburg

    Pg. 2 Paper G-11

  • 8/12/2019 Energy Stress on Surge Arrester

    3/6

    TA

    ST Z2

    IIV

    = (5)

    LA

    L Z2

    IV

    = (6)

    3.3. Lightning stroke parameter model

    A range of different lightning impulse shapes were used

    in simulating lightning strikes to the transmission line.

    In this study, a double exponential, 4/77.5 impulse

    current wave as recommended by CIGRE [6] was used.

    CIGRE also recommends specific peak values of

    lightning current for the different simulations: a peak

    current magnitude of less than 20 kA under shieldingfailure scenario and currents above 20 kA for

    backflashover scenarios [6]. In order to evaluate the

    maximum energy absorbed by surge arresters, unless

    otherwise specified, a 20 kA lightning stroke hitting the

    phase conductor A1 was used for the shielding failure

    case and a 200 kA stroke hitting the tower-top was usedin the backflashover case.

    4. ENERGY STRESS ON SURGE ARRESTERS

    Based on the line lightning performance analysis carried

    out in a previous study [1], the maximum energy

    absorbed by a line surge arrester was calculated usingthe product of voltage and current traces computed by a

    travelling wave simulation technique [5]. In this

    investigation, the insulator flashover was neglected

    since the voltage measured across the line insulator

    which is protected by the surge arrester was found to be

    much lower than the CFO of the insulator string evenunder high magnitude lightning strike. Therefore, it is

    assumed that the insulator does not flashover when it is

    protected by a surge arrester.

    Figure 4 shows energy stress distribution in surge

    arresters installed in all phases in the case when a

    lightning strike hits a phase conductor or a shield wire.When a low current lightning strike hits a phase

    conductor, the energy absorbed by arresters at any tower

    is different. As expected, the arrester installed on a

    stricken phase absorbs excessively high energy

    compared with arresters on other phases. However,when high current lightning hits the shield wire, it was

    shown that any two arresters installed at the same height

    absorb equal energy. The arresters installed on the

    bottom phases absorb more energy than the arresters

    installed on the other four phases above.

    In a previous study [1], it was shown that the top phase

    conductors are more vulnerable to shielding failure

    while those at the bottom phases are more vulnerable to

    backflashover. Considering this case and the results

    shown in Figure 4, arrester energy requirements can be

    such that the top arresters are more likely to experience

    direct strikes of lower magnitudes while the lower ones

    can be subjected to stresses equivalent to those causing

    backflashover.

    4.1. Parametric analysis

    Appropriate selection of an arrester as a function of its

    energy stress depends upon different parameters. These

    parameters can be classified as line parameters and

    lightning stroke parameters. Parameters such as

    arresters in adjacent towers, tower footing resistance

    and angle of power frequency voltage are considered as

    line parameters whereas stroke peak current magnitude,

    front time and tail time are considered as lightningstroke parameters. Influence of each of these parameters

    on arresters energy stress was analysed in this

    investigation.

    Influence of line parametersIn practice, the energy shared by arresters at a tower is

    highly influenced by the presence of arresters at

    neighbouring towers. The nature of influence of these

    adjacent arresters on the struck arresters energy

    stress depends upon the position of the lightning stroke

    hitting the line. Figure 5 shows the energy discharged

    by an arrester as a function of number of arresters in

    neighbouring towers. It is clearly understood that, whenstroke hits the phase conductor, the neighbouring

    arresters help in sharing some of the duty and, hence,

    this reduces the energy stress on the arrester at the

    struck tower. However, the case is different when high

    current lightning stroke hits the shield wire or the towertop. In this case, the energy absorbed by the arresters atthe tower increases with increasing number of arresters

    at the adjacent towers. This is explained by the current

    passing through the adjacent arresters being of opposite

    IA ZLZL

    ZTZT

    IS

    IA/2IA/2

    IA/2IA/2

    VT

    VL

    Surge

    Arrester

    Figure 3: Equivalent circuit of an arrester installed

    between a line conductor and a tower structure. ZT =

    Tower surge impedance, ZL= Line surge impedance, IS

    = Stroke current, and IA= Arrester current

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    A1-C2 B1-B2 C1-A2 A1-C2 B1-B2 C1-A2

    Arrester Position in Phase

    Arre

    sterEnergy[kJ] 20 kA

    10

    Stroke to shield wireStroke to phase conductor

    200 kA

    80

    Figure 4:Distribution of energy stress in surge arresters

    installed at a stricken tower.

    ISBN 978-0-620-44584-9

    Proceedings of the 16th International Symposium on High Voltage Engineering

    Copyright c 2009 SAIEE, Innes House, Johannesburg

    Pg. 3 Paper G-11

  • 8/12/2019 Energy Stress on Surge Arrester

    4/6

    polarity, and hence flows back to the striking point

    resulting into the increase of energy absorbed by the

    arrester at the struck tower [8].

    Figure 6 shows the percentage of energy shared by

    arresters at adjacent towers, when lightning strikes aphase conductor and shield wire. Therefore, it can be

    said that when lightning hits the phase conductor, the

    nearest arresters to the strike absorb almost 40% of

    energy, and the arresters on immediate adjacent towers

    absorb 28%. This value decreases to only 19% for the

    arresters at far end on the line section considered in this

    study. However, when lightning hits the shield wire, the

    nearest arresters absorb only 10%, while the arresters at

    the far end does not absorb any energy.

    The energy discharge duty of surge arresters depends on

    tower footing resistance. Figure 7a shows this effectwhen lightning strikes of different current magnitude hit

    the phase conductor. Figure 7b shows the case when

    200 kA lightning strike hits the shield wire. The tower

    footing resistance was varied from 10 to 80 . For

    stroke to a phase, the energy absorbed by the arrester on

    the phase decreases with increasing footing resistance.

    For a stroke to shield wire, however, high value of

    footing resistance increases the arrester energy

    discharge. In this case, arresters installed on the top

    phases are more stressed with low tower footing

    resistance value whereas bottom phase arresters are

    more stressed in the case of high footing resistance

    value.

    Figure 8 shows the effect of power frequency voltage

    angle on arrester energy stress. Significant influence of

    this angle is seen on both the case of lightning hitting

    the phase conductor and shield wire. When stroke hits

    the phase conductor, the maximum energy in struck

    arrester is obtained at voltage angle of 0

    o

    . In case ofstroke hitting the shield wire, the maximum energy is

    found at voltage angle of 180o. With change in voltage

    angle, the energy stress in arrester increases when stroke

    hits the shield wire, but the energy discharge in this case

    is rather low and is unlikely to exceed the maximum

    energy absorption capability of the arrester.

    Influence of lightning stroke parameters

    Lightning stroke parameters have significant influence

    on energy stress in line surge arresters. This can be

    considered as one of the key factor for selection of the

    arrester. The oscillographic simulation was carried out

    to understand the effect of these parameters for both thecase of stroke hitting a phase conductor and the shield

    wire.

    0%

    10%

    20%

    30%

    40%

    50%

    60%

    70%

    80%

    90%

    100%

    -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8

    Tower Number

    ArresterEnergy[%]

    20 kA

    10

    200 kA

    80

    Figure 6:Percentage (with respect to energy absorbed

    by arrester at tower hit by lightning) of energy shared by

    adjacent arresters at towers along the line.

    Figure 5: Arrester energy as a function of adjacent

    arresters.

    0

    100

    200

    300

    400

    500

    600

    700

    800

    900

    1000

    1 3 5 7 9 11 1 3 1 5 1 7

    Number of Towers with Arresters

    ArresterEnergy[kJ]

    0

    5

    10

    15

    20

    25

    30

    35

    40

    45

    50

    ArresterEnergy[kJ]

    200 kA

    10

    10 kA20 kA

    10

    0

    5

    10

    15

    20

    25

    30

    35

    0 10 20 30 40 50 60 70 80

    Tower Footing Resistance [ ]

    ArresterEnergy[kJ]

    Arr A1-C2

    Arr B1-B2

    Arr C1-A2

    200 kA

    80

    200 kA

    80

    200 kA

    80

    b:Stroke to shield wire

    Figure 7:Arrester energy dependence on tower footing

    resistance

    0

    20

    40

    60

    80

    100

    120

    140

    160

    180

    0 10 20 30 40 50 60 70 80

    Tower Footing Resistance [ ] ] ] ]

    Ar

    resterenergy[kJ]

    10

    20 kA

    10 kA

    a:Stroke to phase conductor

    Figure 8: Arrester energy dependence on power

    frequency voltage angle at lightning strike.

    0

    20

    40

    60

    80

    100

    120

    140

    160

    180

    200

    0 60 120 180 240 300 360

    Power Frequency Voltage Angle in A1 []]]]

    ArresterEnergy[kJ]

    200 kA

    80

    20 kA

    10

    ISBN 978-0-620-44584-9

    Proceedings of the 16th International Symposium on High Voltage Engineering

    Copyright c 2009 SAIEE, Innes House, Johannesburg

    Pg. 4 Paper G-11

  • 8/12/2019 Energy Stress on Surge Arrester

    5/6

    Figure 9 shows the effect of stroke peak current

    magnitude on arrester energy. This effect was examined

    for different tower footing resistances. The energy

    absorbed by the arrester increases with increasing peak

    current magnitude, and this is obtained for all cases of

    impact point and tower footing resistance.

    The effect of impulse front time for different stroke

    peak current magnitudes is shown in Figure 10. In the

    case of lightning hitting the phase conductor, the change

    in front time does not have any influence on the arrester

    energy. However, the arresters are less stressed with

    high front time when lightning hits the shield wire. Onthe other hand, the stroke current tail time has

    significant influence on the energy absorbed by line

    arresters (Figure 11). The arrester energy increases with

    increasing tail time of the lightning impulse.

    5. ARRESTER FAILURE PERFORMANCE

    The objective of this study is to estimate the failure rate

    of arresters due to excessive energy absorption and to

    guarantee that the arresters installed on the line have

    sufficient energy capability to withstand lightningstrikes to the phase conductors or to the shield wire. To

    determine the arrester failure probability, the integrated

    energy for each arrester is used with the failure

    probability curve from EPRI report 1000461 [9].

    The statistical simulation method was used. To integrate

    the energy through the arresters over most of the strokeduration, the method used in TFLASH software adopts

    different simulation time limits for strokes to phase

    conductor and shield wire. These time limits are much

    longer than the flashover statistics time limit (500 s for

    a stroke to phase conductor and 100 s for a stroke to

    shield wire). Figure 12 shows an example of a typicalwaveform used for energy calculation for a 20 kA

    stroke current. In this case, the insulation flashovers

    were disabled.

    -5

    0

    5

    10

    15

    20

    25

    30

    35

    40

    45

    0 25 50 75 100 125 150 175 200 225

    Stroke Peak Current Ma gnitude [kA]

    ArresterEnergy[kJ]

    50

    20

    80

    Figure 9:Effect of stroke peak current magnitude

    a:Stroke to phase conductor

    b:Stroke to shield wire

    -20

    0

    20

    40

    60

    80

    100

    120

    140

    160

    180

    0 2 4 6 8 10 12 14 16 18 20

    Stroke Peak Current Magnitude [kA]

    ArresterEnergy[kJ]

    80

    10

    40

    0

    20

    40

    60

    80

    100

    120

    140

    0 1 2 3 4 5 6

    Front Time [s]

    ArresterEnergy[kJ]

    150 kA

    200 kA

    250 kA

    80

    Figure 10:Effect of front time (Tail time = 77.5s)

    a:Stroke to phase conductor

    b:Stroke to shield wire

    0

    20

    40

    60

    80

    100

    120

    140

    160

    180

    0 1 2 3 4 5 6

    Front Time [s]]]]

    Arreste

    rEnergy[kJ]

    5 kA10

    20 kA

    10 kA

    0

    50

    100

    150

    200

    250

    0 25 50 75 100 125 150 175

    Tail Time [s]

    A

    rresterEnergy[kJ]

    10

    5 kA

    10 kA

    20 kA

    0

    10

    20

    30

    40

    50

    60

    70

    80

    0 25 50 75 100 125 150 175

    Tail Time [s]

    ArresterEnergy[kJ]

    80

    250 kA

    200 kA

    150 kA

    Figure 11:Effect of tail time (Front time = 4s)

    a:Stroke to phase conductor

    b:Stroke to shield wire

    0

    5

    10

    15

    20

    25

    0 50 100 150 200 250 300 350 400 450 500

    Time [s]

    Current[kA]

    For 20kA stroke current

    Front time = 3.4 s

    Tail time= 56.2 s

    Figure 12:Equal probability waveform (20kA stroke

    current)

    ISBN 978-0-620-44584-9

    Proceedings of the 16th International Symposium on High Voltage Engineering

    Copyright c 2009 SAIEE, Innes House, Johannesburg

    Pg. 5 Paper G-11

  • 8/12/2019 Energy Stress on Surge Arrester

    6/6

    The arrester failure performance was analysed for the

    whole line section (35 km) when arresters are installed

    at each phase and at every tower. Table 2 gives a

    summary of the arrester failures for the 35 km line. It

    can be seen that the phase conductors are expected to be

    hit by 3.704 strokes per year resulting in an arrester

    failure rate of 0.128 failures per year, i.e. one arrestermay fail every 7 to 8 years. Since there are hundreds of

    arresters installed on the line, the chances of the same

    arrester failing again is very low. The table also shows

    the failure rate on each phase. It can be seen that there is

    no risk of arrester failure for stroke terminating on theshield wire or tower top but there is risk associated to

    the arresters at the top phase (installed on phases A1and

    C2) with direct strokes terminating on the phase.

    Figure 13 shows the arrester failure rate at towers along

    the section of the line. The maximum failure rate is very

    low; e.g. an arrester at the same tower may fail every

    815 years. This of course depends on the appropriateselection of the arresters.

    Table 2: Arrester failure performance of 35km line.

    (Values in per year basis)

    Direct strikes per year = 3.704

    Arrester failure per year = 0.128

    Arrester Failure by Phase

    Failure From

    PhaseDirect

    StrikesShield

    Strikes

    Phase

    Strikes

    All

    Strikes

    A1 0.269 0.000 0.065 0.065

    B1 0.000 0.000 0.000 0.000

    C1 0.000 0.000 0.000 0.000

    C2 0.269 0.000 0.065 0.065

    B2 0.000 0.000 0.000 0.000

    A2 0.000 0.000 0.000 0.000

    6. CONCLUSIONS

    Energy stress analysis of ZnO surge arresters installed

    on a 275 kV double circuit transmission line was

    investigated. It was found that the energy requirements

    on the line arresters were moderate. The energy

    absorption studies were carried out for the line andstroke parameters which are essential in the selection

    process of line surge arresters.

    Lightning strikes hitting the phase conductors (shielding

    failure) were found to be the main source of the risk of

    failure. In this case, the surge arresters installed on other

    phases on the same tower did not help to share the totalsurge energy. The risk of failure when lightning hits the

    shield wire or tower was found to be zero.

    7. ACKNOWLEDGMENT

    The authors wish to thank the Engineering and PhysicalSciences Research Council (EPSRC) for financial

    support.

    8. REFERENCES

    [1] R. Bhattarai, R. Rashedin, S. Venkatesan, A.Haddad, H. Griffiths and N. Harid, Lightning

    performance of 275kV transmission lines, in Proc.

    of 43rd

    International Universities PowerEngineering Conference, Padova, Italy, Sept. 2008.

    [2] J. A. Tarchini and W. Gimenez, Line surge arresterselection to improve lightning performance of

    transmission lines, in Proc. of IEEE PowerTechConference, vol. 2, Bologna, Italy, June 2003.

    [3] J. A. Martinez and F. Castro-Aranda, Lightningflashover rate of an overhead transmission line

    protected by surge arresters, IEEE Power

    Engineering Society General Meeting, Tampa,

    Florida, USA, June 2007.

    [4] EPRI, Lightning performance analysis of pacificpower company cascade craft substation, Draft

    Report, EPRI, Palo Alto, Exhibit No: WWB-4,

    Nov. 2006.

    [5] EPRI, Handbook for improving overheadtransmission line lightning performance, EPRI,

    Palo Alto, CA:2004. 1002019, Dec. 2004.[6] CIGRE WG 33-01, Guide to procedures for

    estimating the lightning performance of

    transmission lines, CIGRE Brochure 63, Oct.

    1991.

    [7] British Std. BSEN 60071-2, Insulationcoordination, part 2: application guide, 1997.

    [8] A. R. Hileman, Insulation coordination for powersystems, Marcel Dekker, ISBN 0-8247-9957-7,

    1999.

    [9] EPRI, Transmission line surge arrester impulseenergy testing, EPRI, Palo Alto, vol. 1000461.

    Figure 13: Arrester failure rate at each tower along a

    section of the line.

    0

    0.0002

    0.0004

    0.0006

    0.0008

    0.001

    0.0012

    0.0014

    0.0016

    49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65

    Tower Number

    ArresterFailure/Year

    ISBN 978-0-620-44584-9

    Proceedings of the 16th International Symposium on High Voltage Engineering

    Copyright c 2009 SAIEE, Innes House, Johannesburg

    Pg. 6 Paper G-11