25.10.2017 Enervent Pinion Maintenance, Repair and Recycling manual

Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

25.10.2017

Enervent PinionMaintenance, Repair and Recycling manual

Page 2: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

2

Copyright © Enervent 2017.

Unauthorised copying and distribution is forbidden.

Page 3: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

3Maintenance , Repair and Recycling manual

CONTENTSREAD FIRST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

TYPE PLATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Electrical safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

DISMANTLING OF THE UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

FANS AND HEAT EXCHANGER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Fans. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Heat exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Taking the spare belt into use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Changing the belt of the heat exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

RECYCLING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

APPENDICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Technical dimensional drawing, left-handed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Technical dimensional drawing, right-handed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

ELECTRICAL DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Internal connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

External connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

SPARE PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Page 4: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

4

READ FIRST

This instruction manual is intended for all people involved in maintenance and repairing of the Enervent ventilation units. Only professionally skilled persons may maintain and repair the equipment described in this manual, according to the instructions provided in this manual and to the local laws and regulations. Failure to comply with the instructions provided in this manual will result in cancellation of the warranty for the equipment and may result in harm to people or property.

The equipment described in this manual may not be used by persons (including children) with reduced physical, sensory or mental capacity or without sufficient experience or knowledge, unless a person responsible for their safety is supervising and advising in the use of the equipment.

Page 5: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

5Maintenance , Repair and Recycling manual

Should you need any technical support, refer to the type plate for the equipment type and serial number before contacting support.

Technical support: www.enervent.com/contact-information/

Webshop for supplies and spareparts: webshop.enervent.com

Service instructions and service requests: www.enervent.com/help-center/

TYPE PLATE

ilmanvaihtolaiteventilation unit

TYYPPI/TYPE:

W/ V/ HZ / A:

www.enervent.com

SRJ. NRO/SERIAL NO:

IP 20

Page 6: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

6

SAFETY

General Electrical safety

Always check that the equipment supply voltage is switched off before opening the service hatch.

Only an authorised electrician may perform any actions in the electrical box.

Follow the local regulations on electrical installations.

In case of malfunction, always find out the reason for the malfunction before starting the unit again.

Wait for two (2) minutes after switching off the power of the unit before commencing the maintenance. Although the power is switched off, the fans continue running and the heating element stays hot for a while.

Check that the unit is entirely isolated from the mains before conducting any voltage tests, insulation resistance measurements or other electrical work or measurements. Such work may damage the sensitive electrical devices.

Control devices used in the ventilation units may cause leakage current. It may affect the operation of the residual current devices.

All ventilation units with a control system must be equipped with an over-voltage arrester.

DANGER DANGER

DANGERWARNING

WARNING CAUTION

CAUTION

CAUTION

Page 7: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

7Maintenance , Repair and Recycling manual

11kg

!HEX 4

1 2

Always check that the equipment supply voltage is switched off before opening the service hatch.

DANGER

DISMANTLING OF THE UNIT

Only an authorized service provider may dismantle the unit.

Page 8: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

8

FANS AND HEAT EXCHANGER

FansCleaning

1

5

3 4

2

6

Before cleaning the fans, see "DISMANTLING OF THE UNIT" on page 7. Perform the cleaning simultaneously with cleaning of the ducts. The fans and heat exchanger are cleaned at the same time as the ventilation ducts of the house are cleaned. The cleaning is to be performed by an authorized service provider.

Care must be taken not to disturb the balancing weights on the fan blades.

WARNING

Page 9: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

9Maintenance , Repair and Recycling manual

Cleaning

5 6

7

4

Check the cleanliness of the rotating heat exchanger visually when changing filters, and clean it if it looks dirty. Before cleaning the heat exchanger, see "DISMANTLING OF THE UNIT" on page 7. The cleaning is to be performed by an authorized service provider.

Heat exchanger

Do not submerge the heat exchanger in water.The electric motor inside the heat exchanger must not get wet.

WARNING

The use of a pressure washer is strictly forbidden.

Use a neutral grease dissolving detergent that does not leave any residue.

1 2

3

Page 10: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

10

Taking the spare belt into use

1 2

43

Before taking the spare belt into use, see "DISMANTLING OF THE UNIT" on page 7.

Page 11: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

11Maintenance , Repair and Recycling manual

3

5

7

4

6

Before changing the belt, see "DISMANTLING OF THE UNIT" on page 7.

1 2

Changing the belt of the heat exchanger

8

Page 12: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

12

9

11

13

15

10

12

14

16

Page 13: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

13Maintenance , Repair and Recycling manual

18

19

17

Page 14: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

14

TROUBLESHOOTING

Alarm Description Alarmlimit Symptoms Possible cause Action Notes

FILS Service reminder.

4 or 6

months

It is time for regular maintenance. Replace the filters.

Inspect the ventilation unit.

Clean as necessary.

See if there are any damages visible.

Acknowledge by pressing any button for 5 seconds.

Err Sensor malfunction.

The sensor is in short circuit or there is an interruption in the circuit.

Check the connections and cables of the sensors.

- - - - Downloading. The eWind panel downloads data from the motherboard.

Normal during start-up. In other situations, check the eWind connection cable.

oFFE Stop mode. Ventilation off. External control system has switched the ventilation unit to stop mode.

AL1 Water heat-ing coil is in danger of freezing.

+8 °C Cold supply air. The water coil is frozen/about to freeze:

• The circulation pump has stopped.

• The heat exchanger does not rotate.

• The control valve actuator of the water coil is faulty.

• The extract fan has stopped.

Restart the pump. Replace the motor or the belt. Replace the actuator.

Find out the reason/replace the fan.

The unit will not start until the alarm mode is cleared and the alarm reset by pressing a button in the operation panel.

AL2 The supply air is cold after the rotating heat exchanger.

+5 °C Cold supply air. The heat exchanger does not rotate:

• The drive belt is damaged.

• The drive belt skids.

• The heat exchanger motor is damaged.

Replace the drive belt.

Clean or replace the belt or the heat exchanger.

Replace the heat exchanger motor.

The ventilation unit switches to malfunction mode, in which the fans operate with mini-mum power.

The alarm is auto-matically reset when the fault is cleared.

AL3 Cold supply air.

+10 °C Cold supply air. The extract fan has stopped. Replace the fan.The extract filter is clogged. Replace the filter.

The ventilation is adjusted incor-rectly/not adjusted at all.

Adjust the ventilation as per the ventilation system plan with appropriate measure-ment tools.

The heat insulation of the ducts is insufficient.

Check the insulation thick-ness of the supply and extract air ducts and add insulation as necessary.

The fan speed of the ventilation unit is incorrect.

Always use a fan speed specified by the ventila-tion unit designer (also in winter).

AL4 Supply fan malfunction.

No ventilation. The supply fan has stopped. Repair or replace the supply fan.

The unit will not start until the alarm mode is cleared and the alarm is reset by pressing a button in the operation panel.

AL5 Extract fan malfunction.

No ventilation The extract fan has stopped. Repair or replace the extract fan.

Page 15: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

15Maintenance , Repair and Recycling manual

RECYCLING INSTRUCTIONS

Check the recycling instructions regarding the end-of-life of the unit on the webpage www.enervent.com.

Alarm Description Alarmlimit Symptoms Possible cause Action Notes

AL6 Cold extract air.

+10 °C Cold supply air. Low indoor temperature. Raise the indoor temperature.

Acknowledge by pressing any button for 5 seconds.

Insufficient heat insulation of the extract air duct.

Check the insulation of the ducts and add insulation as necessary.

The ventilation unit’s service hatch is open.

Close the service hatch

Temperature sensor TE30 is faulty. Repair or replace the sensor.

AL7 Hot supply air.

Fire hazard.

+55 °C Hot supply air. Fire hazard. Check if there are any heat sources.

The device will not start until the alarm mode is cleared and the ventilation unit started again.

There is a malfunction in the electric after-heating coil.

Repair or replace the electric after-heating coil.

There is a malfunction in the actuator of the water-based after-heating coil’s valve.

Repair or replace the valve’s actuator.

Temperature sensor TE10 is faulty. Repair or replace the tem-perature sensor.

AL8 Overheating of the electric after-heating or preheat coil.

Hot supply air. Electric preheat or after-heating coil does not work:

• Overheating protector has tripped.

• The supply fan has stopped.

• The supply air filter is clogged.

• The outside air grille is clogged.

• The heater controller board is damaged.

• The heater is damaged.

Find out the reason for overheating and reset the error message.

Find out the reason/replace the fan.

Replace the filter.

Clean the grille. Remove any mosquito net.

Replace the controller board.

Replace the heater

Page 16: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

16

Dimensional drawingsTechnical dimensional drawing, left-handed

APPENDICES

Page 17: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

17Maintenance , Repair and Recycling manual

Technical dimensional drawing, right-handed

Page 18: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

18

Electrical diagramsInternal connections

Page 19: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

19Maintenance , Repair and Recycling manual

WIR

E CO

LOU

RSBK

BL

ACK

BN

BRO

WN

RD

RED

OG

O

RAN

GE

YE

YELL

OW

GN

G

REEN

BU

BLU

EG

Y G

REY

WH

W

HIT

E

Nam

eEx

plan

atio

nM

arki

ng o

n ci

rcui

t boa

rdTE

45RE

TURN

WAT

ER S

ENSO

R eW

ind

W U

NIT

STE

45TE

46RE

TURN

WAT

ER S

ENSO

R eW

ind

CG U

NIT

STE

45TE

02PR

EHEA

TED

OU

TSID

E AI

R SE

NSO

RTE

02TE

20RE

TURN

AIR

TEM

PERA

TURE

(KO

TILÄ

MPÖ

eW

ind

UN

ITS)

TE02

TE32

EXH

AUST

AIR

TEM

PERA

TURE

SEN

SOR

TE32

TE10

SUPP

LY A

IR T

EMPE

RATU

RE S

ENSO

RTE

10TE

05AI

R TE

MPE

RATU

RE A

FTER

TH

E H

EAT

RECO

VERY

HEA

T EX

CHAN

GER

TE05

TE01

OU

TSID

E AI

R TE

MPE

RATU

RE S

ENSO

RTE

01RH

T30

EXTR

ACT

AIR

TEM

PERA

TURE

AN

D H

UM

IDIT

Y SE

NSO

R(RH

0-1

00%

)RH

T30

SF10

SUPP

LY A

IR FA

NAO

1,D

I11

EF30

EXTR

ACT

AIR

FAN

AO2,

DI1

2CF

20RE

TURN

AIR

FAN

(KO

TILÄ

MPÖ

UN

ITS

ON

LY)

AO6

M75

HEA

T RE

COVE

RY H

EAT

EXCH

ANG

ER M

OTO

RAO

4

Page 20: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

20

Electrical heating element and pre-heater connections.

Page 21: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

21Maintenance , Repair and Recycling manual

WIR

E CO

LOU

RSBK

BL

ACK

BN

BRO

WN

RD

RED

OG

O

RAN

GE

YE

YELL

OW

GN

G

REEN

BU

BLU

EG

Y G

REY

WH

W

HIT

E

Nam

eEx

plan

atio

nM

arki

ng o

n ci

rcui

t boa

rdTZ

+O

VERH

EAT

PRO

TECT

ION

AU

TOM

ATIC

RES

ETTZ

AO

VERH

EAT

PRO

TECT

ION

MAN

UAL

RESE

TTS

02CA

PILL

ARY

THER

MO

STAT

Page 22: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

22

External connections

Page 23: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

23Maintenance , Repair and Recycling manual

WIR

E CO

LOU

RSBK

BL

ACK

BN

BRO

WN

RD

RED

OG

O

RAN

GE

YE

YELL

OW

GN

G

REEN

BU

BLU

EG

Y G

REY

WH

W

HIT

E

Nam

eEx

plan

atio

nM

arki

ng o

n ci

rcui

t boa

rdFP

/EX

FIRE

PLAC

E/EX

TRAC

TOR

HO

OD

MO

DE

DI6

AWAY

AWAY

MO

DE

DI5

BOO

STM

ANUA

L BO

OST

DI4

ESTO

PEX

TERN

AL S

TOP

DI1

TE45

RETU

RNW

ATER

TEM

PERA

TURE

SEN

SOR

eWin

d W

UN

ITS

TE45

TE46

RETU

RNW

ATER

TEM

PERA

TURE

SEN

SOR

eWin

d CG

UN

ITS

TE45

TE02

PREH

EATE

D O

UTS

IDE

AIR

TEM

PERA

TURE

, EXT

ERN

AL P

REH

EATE

RTE

02TE

20RE

CIRC

ULA

TIO

N A

IR T

EMPE

RATU

RE (K

OTI

LÄM

PÖ e

Win

d)TE

02TE

10SU

PPLY

AIR

TEM

PERA

TURE

TE10

TE01

OU

TSID

E AI

R TE

MPE

RATU

RETE

01RH

CO

²EX

TERN

AL H

UM

IDIT

Y SE

NSO

R (R

H 0

-100

%) B

Y D

EFAU

LT IF

PARA

MET

ER c

27 IS

ACT

IVE,

CO

² SE

NSO

R (2

00-2

000p

pm) (

ACCE

SSO

RY)

AI1

TL01

TL

50PR

EHEA

TER

VALV

E AC

TUAT

OR

-CH

G M

OD

ELS

COO

LIN

G V

ALVE

ACT

UATO

R -C

G M

OD

ELS

AO6

TL45

HEA

TIN

G V

ALVE

ACT

UATO

R -W

MO

DEL

SAO

5D

O8

ALAR

M A

OU

TPU

T BY

DEF

AULT

PRE

HEA

TER

ON

/OFF

CO

NTR

OL

IN -C

HG

-AG

H -E

LEC

TRIC

AL

PREH

EATE

R M

OD

ELS

COO

LIN

G O

N/O

FF C

ON

TRO

L IN

-CG

MO

DEL

S D

O8

DO

5O

UTS

IDE

AIR

AND

EXH

AUST

AIR

DAM

PER

CON

TRO

L (A

CCES

SORY

)D

O5

DO

2H

EATI

NG

ON

/OFF

CO

NTR

OL

eWin

d W

MO

DEL

S

M

AX 5

00W

PU

MP

DO

2O

P1U

SERP

ANEL

1pc

s. IN

CLU

DED

IN D

ELIV

ERY,

10m

CAB

LE IN

CLU

DED

IF N

OT

MO

UN

TED

ON

U

NIT

OP1

OP2

USE

RPAN

EL (A

CCES

SORY

) 10

m C

ABLE

INCL

UD

ED IN

DEL

IVER

YO

P2

Page 24: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

24

Product number Model Product nameK100130002 Pinion eWind Rotating heat exchanger, stepless control PinionK120090003O Pinion eWind Heat exchanger motor package stepless DC Piccolo,Plaza, Liggolo, LTR-2K140130001 Pinion right handed Supply air fan 119W, PinionK140130002 Pinion right handed Extract air fan119W, PinionK140130003 Pinion left handed Supply air fan 119W, PinionK140130004 Pinion left handed Extract air fan119W, PinionK160130001 Pinion eco ECE right/left Electrical after heater 0,8kW ECE PinionK160130002 Pinion eWind E right /left Electrical after heater 0,8kW eAir PinionK160130011 Pinion right handed Arctic Electrical pre heater 0,8kW right handed PinionK160130011v Pinion left handed Arctic Electrical pre heater 0,8kW left handed PinionK580040001 Pinion eWind eWind control panel Packet includes panel, surface mounting box and 10m cableK930020024 Pinion eco ECE ECC05E control panel+frame+cable (10m) +surface mounting boxM070010001 Pinion Brush sealing set 23/12mm DX 1175-0004-0001 PB048,1300-CF grM120200007 Pinion Control circuit board EM-240-M1 DC-motor M140030008 Pinion Belt, PUW green, diam. 6mm 845 mm Piccolo, PlazaM150300101 Pinion Belt wheel diam. 54mm T081839.1 BELT WHEEL (P010010503 D)M210130242 Pinion Spare filters F7/F5 PinionM230120511 Pinion eco ECE Temperature sensor TS-EV-L500 M230120514 Pinion eco ECE Temperature sensor TS-EV-L850 M620200003 Pinion MeanWell switch-mode power supply RS-15-24 M620200011 Pinion Tufvassons switch-mode power supplyPSLR 24 M710400002 Pinion eco ECE ECC electrical heater triac circuit boardM710600007 Pinion eWind E EDA electrical heater triac circuit board Enerpoint

Spare parts list

Page 25: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

25Maintenance , Repair and Recycling manual

Page 26: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

26

Page 27: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

27Maintenance , Repair and Recycling manual

Page 28: Enervent Pinion · The use of a pressure washer is strictly forbidden. Use a neutral grease dissolving detergent that ... EXTERNAL HUMIDITY SENSOR (RH 0-100%) BY DEFAULT IF PARAMETER

Enervent OyKipinätie 1FIN-06150 Porvoo, FinlandTel. +358 207 528 800Fax. +358 207 528 [email protected]