BM POWER SUPPLY &
ELECTRICAL SERVICES
BM POWER SUPPLY & ELECTRICAL SERVICES Tel# 563-2946 / 563-2957 / 561-0544 Fax# 563-2969 / 562-4421
Email Address: [email protected]
Customer : JMY ENGINEERING Date: Nov. 30,2013
Location : IM DIGITAL INC. (FPIP Sto. Tomas, Batangas)
Transformer Specifications Capacity 1500KVA
Phase Three (3)
Frequency 60 Hz
Cooling Class ONAN
High Voltage 460V
Low Voltage 380V
Vector Diagram Dyn
HV Tap Position Not applicable
Impedance 5.91%
Temperature Rise 60°C
Insulating Liquid Mineral oil
Brand Shinsoeng Industrial Co., Ltd.
Serial Number 11844
Year Manufactured 2011.10
Certified Test Results
1. Insulation Resistance and Dielectric Adsorption/Polarization Index of Windings
(Megger Test):
Test Voltage Five-Minutes
DC (in KV) (in GIgaohms)
Primary to Ground 1 24.5
Secondary to Ground 1 29.8
Primary to Secondary 1 22.1 Note: 1. The minimum Insulation Resistance two (2) Megaohms/KV or 100 Megaohms for 0 to 600V; 1000 Megaohms for
601-5000V; and 5000 Megaohms for greater than 5000V.
Remarks: PASSED
Test Instrument: MEGGER, MIT520/2
2. Transformer Insulating Oil Dielectric Breakdown Voltage (DBV) test:
Trials As Found DBV
1 41.9 KV
2 39.0 KV
3 30.1 KV
4 30.0 KV
5 32.2 KV
Average 34.6 KV Note: The average Dielectric Breakdown Voltage of transformer insulating oil should be 26KV or higher to be considered
Satisfactorily Good.
Remarks: PASSED
Test Instrument: HIPOTRONICS, DIGITAL OIL TESTER
BM POWER SUPPLY & ELECTRICAL SERVICES Tel# 563-2946 / 563-2957 / 561-0544 Fax# 563-2969 / 562-4421
Email Address: [email protected]
3. Transformer Turns Ratio (TTR) Test:
Tap Primary Voltage Computed As found Ratio
(per phase) ratio U,V/O,U V,W/O,V W,U/O,W
1 460 2.091 2.075 2.075 2.075 Note: As found ratio must not exceed ± 0.5% of computed ratio
Remarks: PASSED
Test Instrument: MEGGER, TTR
4. Winding Resistance Test:
Tap As Found Resistance Test
Test Current 1A
U,W U,V W,V
1 0.002mΩ 0.002mΩ 0.003mΩ
Secondary Side
O,U O,V O,W
0.002mΩ 0.002mΩ 0.003mΩ
Note: Data obtained to be compare for each phases must at least approximately balanced.
Remarks: PASSED
Test Instrument: BIDDLE, DLRO
5. Excitation Current Test (No Load Test):
As Found Excitation Current @ HIGH SIDE
Test Voltage U,V U,W V,W
491 4.22 5.08 3.97 Note: 1. Excitation current, test data pattern for three phase transformer is two (2) similar readings and one (1) lower
reading;
2. Excitation current at rated voltage of transformer should not exceed 3% of full load current
Remarks: PASSED
Test Instrument: NANOVIP (ammeter,voltmeter,wattmeter)
6. Evaluation and Recommendation:
All tests conducted on transformer with the above specifics satisfactorily passed and/or meet
the standards for maintained liquid filled transformers (ANSI/NETA-MTS2011) thus transformer is
ready for energization.
Tested By: Checked by:
ERWIN GARCIA CHRISTIAN AARON AZCUETA
Secondary Voltage
(per phase)
220