Entergy Gulf States, Inc. (Louisiana) Proposed Transmission Reliability Projects. Entergy Transmission Planning Summit New Orleans, LA July 10, 2003. 2004 EGSI-LA Transmission Reliability Projects. McManus Capacitor Bank Addition. Harelson Substation: 230/69kV Auto Replacement - PowerPoint PPT Presentation

Citation preview

Page 1: Entergy Gulf States, Inc. (Louisiana) Proposed Transmission Reliability Projects

1

Entergy Gulf States, Inc.(Louisiana)

Proposed TransmissionReliability Projects

Entergy Transmission Planning Summit

New Orleans, LA

July 10, 2003

Page 2: Entergy Gulf States, Inc. (Louisiana) Proposed Transmission Reliability Projects

2

2004 EGSI-LA Transmission Reliability Projects

69kV Five Points-ErathLine Upgrade

McManusCapacitor Bank Addition

Harelson Substation:230/69kV Auto ReplacementCarryover – 4-30-2004 ISD

Improve ASI REVISED:Build lineConway-Panama (2004 ISD) CarryoverSEE ELI Presentation

Willow Glen: Breaker Replacement Program 5 – 230 kV breakers

Coly-Hammond:Build 230kV line2006 ISD .

Port Hudson-Crown

Zellerbach Line upgrade

Chlomal-Jennings Line 13 Upgrade

Port Hudson 69 kV Breaker Replacement

Page 3: Entergy Gulf States, Inc. (Louisiana) Proposed Transmission Reliability Projects

3

230kV Harelson Substation:Replace 2nd 230/69kV 200MVA auto with a 300MVA

unit

• Harelson 230/69kV substation, located in eastern Baton Rouge, has two 200MVA autotransformers. This substation, in conjunction with Coly substation, serves an area with one of the highest load growths in south Louisiana.

• Contingency: Under peak loading conditions, loss of one of the existing 230/69kV autotransformers at Harelson can potentially overload the other unit by 19% .

• Recommended Solution: Replace 2nd 200MVA auto with another 300MVA unit. The 1st auto will have been in-service by 12-13-2003 (T#2). Substation space constraints prohibited the installation of a third auto.

• Total Estimated Cost: $4.2M 2004 Cost: $700 K

• Estimated In-service Date: 4-30-2004

2004

Page 4: Entergy Gulf States, Inc. (Louisiana) Proposed Transmission Reliability Projects

4

2004

Harelson

Weiner

230kV Harelson Substation

Page 5: Entergy Gulf States, Inc. (Louisiana) Proposed Transmission Reliability Projects

5

EGSI-LA Circuit Breaker Replacement Program

2004

• Mandatory: Safety Issue– Replace five 230 kV circuit breakers at Willow Glen Substation

– Replace one 69kV circuit breaker at Port Hudson

• Total Estimated Program Cost: $7.3 M – 2004 Cost: ~$2.8 M

• Estimated ISD: 7-30-2004

Page 6: Entergy Gulf States, Inc. (Louisiana) Proposed Transmission Reliability Projects

6

138 kV Line 368 Port Hudson-Crown Zellerbach:

2004

The 138 kV substations in East Baton Rouge and East Feliciana Parishes are served by 2-230/138 kV autos located at Port Hudson substation. This industrial loop serves approximately 237 MVA.

Contingency: Under peak loading conditions, loss of the Repapco-Port Hudson line can potentially overload Line 368 (Port Hudson-Crown Zellerbach) by as much as 36% in 2004, that portion of line composed of 795 AA and rated at 174 MVA.

Recommended Solution: Reconductor 7.5 miles of Line 368 with a conductor capable of at least 301 MVA or 1260 A.

Estimated Cost: $3.81M

Page 7: Entergy Gulf States, Inc. (Louisiana) Proposed Transmission Reliability Projects

7

138kV Line 368 Port Hudson-Crown Zellerbach

Line 368

2004

Page 8: Entergy Gulf States, Inc. (Louisiana) Proposed Transmission Reliability Projects

8

Chlomal-Jennings Loop Upgrade• The 69kV transmission system between Jennings and Chlomal substations will

serve approximately 73MW of load including the radial from Lawtag substation in 2004. The main "trunk" of these systems are the contiguous segments comprising of Line 13 (Jennings-Compton-Elton), Line 16 (Elton-Tupper-Serpent-Carter), and Line 11 (Carter-Lacassine-Chlomal).

• The other main "trunk" is comprised of Line 14 (Jennings-Lawtag) and Line 12 (Lawtag-Welsh-Derouen-Iowa-Chlomal), which span approximately 29 miles and serve approximately 39 MW.

• These lines are over 50 years old. Their age have manifested in reduced reliability and reduced load-serving capacity. Between 1997 and 2001, an average of 19 outages per year occurred on the northern route (Lines 11,13, and 16). In 2002, 13 outages were recorded.

• Splices have been used to make repairs and they are beginning to fail. The

current loading can potentially cause the 69kV lines to sag into the distribution underbuild that is located along most of these lines. Upgrading these lines is needed to avoid safety and reliability concerns.

2004

Page 9: Entergy Gulf States, Inc. (Louisiana) Proposed Transmission Reliability Projects

9

Line 11/12/13/15/16 69 kV Upgrade

Page 10: Entergy Gulf States, Inc. (Louisiana) Proposed Transmission Reliability Projects

10

Chlomal-Jennings Loop Upgrade(continued)

For Existing Configuration:

Contingency Overload/UndervoltageLoss of Jennings-Compton Chlomal-Lacassine 13%

Depressed local area voltages (0.78 p.u. at Compton)Loss of Jennings-Elton Chlomal-Lacassine loads to 99%Loss of Chlomal-Lacassine Jennings-Compton 30%

Depressed local area voltages(0.75 p.u. at Lacassine)Elton-Tupper 5%

Loss of Jennings-Lawtag Chlomal-Iowa 6%Depressed local area voltages (0.91 p.u. at Potter)

Possible solution: Upgrade 46 miles of line Chlomal-Serpent and Jennings to Compton rated 33 MVA/ 39 MVA with a conductor capable of 72 MVA or 602 amps. Install breaker at Lacassine.

Estimated cost: $13M ($2.5M for 2004)

Expected In-Service Date: October 2010

Page 11: Entergy Gulf States, Inc. (Louisiana) Proposed Transmission Reliability Projects

11

Existing Configuration of Lines 11, 12, 13, 14 & 16

Station with Breaker

Non-Breaker Station

LEGEND

Station with Proposed Breakers

Radial to Winn/Potter/Thornwell/ TexLake

Chlomal Iowa Derouen

Lacassine

Carter

Serpent Tupper

Elton

Compton

Roanoke

Lawtag

Robbie

Jennings

Welsh

Normally-OpenedL11 L13

L16

L13A

L12L14

Page 12: Entergy Gulf States, Inc. (Louisiana) Proposed Transmission Reliability Projects

12

Chlomal-Jennings Loop Upgrade(continued)

For Modified Proposal:

Contingency Overload/Undervoltage

Loss of Jennings-Lawtag Chlomal-Iowa 119%

Loss of Carter-Lacassine Lawtag-Jennings 32%

Loss of Chlomal-Lacassine Lawtag-Jennings 43%

Loss of Lawtag-Compton Tupper, Serpent,

Compton, Elton < 0.9 p.u.

Possible solution: Upgrade 25.5 miles of line Chlomal to Carter and Jennings to Roanoke pt rated 33 MVA/ 39 MVA with a conductor capable of 93 MVA or 780 amps. Install breaker at Lacassine.

Total Estimated cost: $13M ($3.5M for 2004)

Expected In-Service Date: October 2010

Page 13: Entergy Gulf States, Inc. (Louisiana) Proposed Transmission Reliability Projects

13

Modified Proposed Reconfiguration

Radial to Winn/Potter/Thornwell/ TexLake

Chlomal Iowa

Derouen Lacassine

Carter

Serpent Tupper

Elton

Compton

Roanoke

Lawtag

Robbie

JenningsWelsh

Station with Breaker

Non-Breaker Station

LEGEND

Station with Proposed Breakers

Lines that can be de-energized or taken out of service.

Page 14: Entergy Gulf States, Inc. (Louisiana) Proposed Transmission Reliability Projects

14

McManus 69kV Substation: Replace Cap Bank & Correct Load PF

• McManus 69kV Substation is located north of Baton Rouge in East Feliciana Parish near the end of a 12 mile radial 69kV line. There will be approximately 70 MW of load in the area in 2004.

• Contingency: Loss of Port Hudson to Jackson 69kV will cause voltages less than 0.91 p.u. near the end of this line.

• Recommended Solution: Replace existing 18 MVAr capacitor bank with 1-30 MVAR capacitor bank.

• Estimated Cost: $550K

2004

Page 15: Entergy Gulf States, Inc. (Louisiana) Proposed Transmission Reliability Projects

15

McManus 69kV Substation

Page 16: Entergy Gulf States, Inc. (Louisiana) Proposed Transmission Reliability Projects

16

69kV Line 280 (Five Points -Erath)• The 69kV substations Five Points, Texas Erath, Erath, and LeBlanc in

Vermillion and Iberia Parishes are served by two sources, Meaux and Moril. The load served by the four 69kV substations will be approximately 41 MW in 2004.

• Contingency: Under peak loading conditions, loss of the Moril 138/69kV autotransformer can potentially overload a portion of Line 280 (Five Points to Erath) by 13% in 2004, that portion of line is composed of 4/0 ACSR and rated at 39MVA.

• Recommended Solution: Reconductor 5.01 miles of 69kV Five Points-Erath with a conductor capable of 72 MVA.

• Estimated Cost: $1.3M

2004

Page 17: Entergy Gulf States, Inc. (Louisiana) Proposed Transmission Reliability Projects

17

69kV L280 (Five Points -Erath)

These lines (Line 280 & 649) do not connect. TIGRE

Page 18: Entergy Gulf States, Inc. (Louisiana) Proposed Transmission Reliability Projects

18

2005+ EGSI-LA Transmission Target Areas

69kV Jackson- MarydaleLine Upgrade: ISD 2005

Coly-Hammond:Build 230kV line2006 ISD

69 kV Lafayette-Holiday Line Upgrade: ISD 2006

Winn 69 kV 18MVAR Capacitor Installation: ISD 2005

69 kV Harelson-Flannery Rd Line Upgrade: ISD 2006

138 kV Willow Glen-Alchem Line Upgrade: ISD 2005

Page 19: Entergy Gulf States, Inc. (Louisiana) Proposed Transmission Reliability Projects

19

Questions