EQUIP equipment
perimeterPERIM
janitorJANbasementBSMTgalvanizedGALV
CPT carpet
glassGL
gypsum boardGYP.BD.
CY cubic yardCTC center to center
general contractor
gypsum board ceilinggypsum board soffit
gypsum board bulkhead
GCGBSGBCGBBcrash rail
CRBCR
ceramic tilecourse(s,ing)
CTCRS
coved resilient base
futureFUT
footingFTG
FA fasten, fastener
existingEXIST
CONST construction
CLS closure
CL centerline of
CH channel
gage, gaugeGA
caulk(ing)CLK
CLO closet
BUL bulletinBUR built-up roof
framefireproof(ing)
FRFP
ceramic mosaic tile
clear
CMT
CLR
furred(ing)
feet or foot
FUR
FT
continuousconcrete
CONTCONCCOL
contractorCORRCONTR
corridor
column
FRT fire retardant
concrete masonry unitCMU
each wayEW
exterior
EXP
EXT
exhaustEXHexpansion
face brickFBFDFE
fire extinguisher cabinetfinish floor elevationFFE
FFLFGL
FEC
cabinetcarpet basecubicle curtaincubicle curtain trackcubic feet
foundation
FHCFINFLRFND
face of concreteface of masonry
FOCFOM
contr. furnished, contr. installedcorner guard
chamfercircumferencecontrol joint
ceiling
contract limit line
floor drainfire extinguisher
finish floor linefiberglassfire hose cabinetfinish(ed)floor(ing)
CABCBCCCCTCFCFCICG
CHAMCIRCCJ
CLG
CLL
mouldingMLD
marker boardMRKBD
movableMOVmasonry openingMO
mount(ed),(ing)metal
MP
MTMTL
multi-paint
mediumMED
LTWT lightweight
LTG lightinglightlow point
LTLP
LAM laminated
KO knock out
PTD paper towel dispenser
LVR louver
PLPG
plastic laminateplate glass
plaster
PNLPLWDPLSTRPLC
pounds per square footPSFPRPP
panel
pairpush plate
plywood
plastic laminate clad
PSI pounds per square inch
jointJT
kitchen
kick plate
length, long
lavatory
KIT
KPL
L
LAVLBL
linear footlong leg horizontallong leg vertical
level
masonry
lintel
LFLLHLLV
LVL
MAS
LTL
label
mechanical
manufacturer
maximum
miscellaneousminimum
MAXMECH
MFR
MISCMIN
MAT material
EIFS ext. insulation & finish sys.
BC bottom of curb
ASPH asphalt
depth, deepD
detaildemolitiondouble
DETDEMODBL
dimensiondiagonaldiameter
DIMDIAGDIA
drinking fountainDF
anchor bolt
door openingDODN
drawer
downspoutdoor
DWRDWGDSDR
acousticaladdendumadjustableabove finish flooralternatealuminumanodized
above
drawing
down
expansion bolteacheast
EBEAE
electric(al)elevationexpansion joint
each face
ELECELEJ
EF
access panelarchitectural
boardbumper guardbituminous
equalelevator
EQELEV
blockingbench mark
bearing platebearingbrick
bottom
building
both sides
ABABVACOUSADDADJAFFALTALUMANODAPARCH
BDBGBITUMBLDGBLKGBMBOTBPLBRGBRKBS
pre-formed composite metal panel
owner furnished, owner installedowner furnished, contr. installed
NC no ceiling
PCMPPCC pre-cast concrete
MTLFUR metal furringMUL mullion
HT heighthigh pointHP
GMU glazed masonry units
ounceOZ
NOMNO
nominalnumber
on centerOCOA
outside diameter
OHOFOIOFCIOD
overhead
overall
openingOPG
P
OPP
particle boardPBDpaint
opposite
gravelgrab bargrade
hardboard
height, high
groutGRVLGRBGR
HDBD
H
GT
hardwood
hollow core
heating, ventilating, air-conditioninghorizontal
hollow metalHDWDHDW
HC
HVACHORZ
HM
interiorinsulationinclude(d),(ing)
invertINTINSULINCL
INV
inside diameterID
hardware
not to scaleNTS
millwork
north
not in contract
MWK
N
NIC
A-0A-1A2-1A3-0A5-1A6-1A11-1
CODE COMPLIANCE PLANDEMOLITION PLANPHARMACY CLEAN RM. PLANDOOR SCHEDULE, WALL/FRAME TYPE, DETAILSREFLECTED CEILING PLAN - ROOF PLANINTERIOR ELEVATIONSFINISHES AND FINISH PLAN
GRAVEL
NOTE REFERENCE
LINTEL TYPE
METAL
BRICK
CONCRETE
CEILING HEIGHT
CONCRETE MASONRY UNIT
REFERENCE DRAWING NUMBERDETAIL NUMBER
COLUMN REFERENCE
TEST BORING WALL TYPE
DOOR NUMBER
WINDOW NUMBER
L-1
PLASTIC LAMINATE
SHIM
WOOD, FRAMING
WOOD, FINISH
PLYWOOD
LOUVER TYPE
ELEVATION LETTER
REFERENCE DRAWING NUMBER
REFERENCE DRAWING NUMBERSECTION NUMBER
EXISTING POINT ELEVATION
NEW CONTOUR
NEW POINT ELEVATION
EXISTING CONTOUR
INSULATION, BATT
INSULATION, RIGID
GRID LINES
PROJECT TITLE:
ABBREVIATIONS:
SYMBOLS LEGEND:
PROJECT TEAM: DRAWING INDEX:
CARD READER
COVER
ELEVATION
MTL STUD
ARCHITECTURAL
EARTH
GYPSUM BOARD/PLASTER
SVGC suspended vinyl gypsum ceilingrough openingROROWRUB
right of wayrubber
windowwood
weight
waterproof(ing)waterstopwainscot
welded wire meshwall to wall
WINWD
WTWSCT
WPWS
WWMWTW
quantityQTY
PTN partitionpolyvinyl chloridePVC
QTQTR RD
quarry tilequarter round
radius
reference
RADRDREFREINF
requiredresilient
revision
REQ'DRESILRETREV
roof drain
reinforcing
return
reflectedRFLRM
riserR
room
TMPRD tempered
TEL telephonetop of curb
temporarytongue and groovethick(ness)
top of pavement
top of slab
tread
toilet paper dispenser
TC
TEMPT>HK
TP
TSTTSL
T
TPD
typicaltop of wall
verticalvinyl composition tilevapor barrier
west, width, wide
vinyl wall coveringveneer
TWTYP
VERTVCTVB
W
VWCVNR
top of steel
water closetwood base
WCWB
sanitary napkin dispenserSND
STRUC structural
STD standardSTLSTOR storage
steel
SSTL stainless steelSS solid surfacingSQ square
SGC suspended gypsum ceiling
suspendedsheet vinyl
SUSPSV
southsuspended acoustical ceilingsanitary
SSACSAN
soap dispenserSCHSDSEC
solid coreSCschedule
section
sheetsimilar
space
SHTSIM
SP
specialSPECSPLSPM
square foot
specification
single-ply membrane
SF
unit dimensionunderwriters laboratoriesunfinishedunless noted otherwise
UDULUNFUNO
verify in fieldVIF SET NO. SEALfield verifyFV
gypsum wall boardGWB
GLBLK glass block
gypsum boardGB
ROOM NUMBERROOM NAMEWAITING
107
3 REVISION NUMBER& TYPE
405 GRAND AVE. DAYTON, OHIO 45409JULY 24, 2019 - FIT OUT AND MEP
GRANDVIEW MEDICAL CENTER
USE GROUP: I-2 (HOSPITAL)
CONSTRUCTION TYPE: 1-A (UNLIMITED AREA)
RENOVATED AREAS: PHARMACY CLEAN RM - 3,358 SQ. FT.
FIRE SUPPRESSION: FULLY SUPPRESSED IN AREAS OFRENOVATION
NUMBER OF STORIES: 5
OCCUPANT LOAD REMAINS UNCHANGED AND NO NEW AREAWILL BE ADDED TO THE BUILDING.
* N.F.P.A. 101 - LIFE SAFETY CODE, 2012 EDITION.
* THE OHIO BUILDING CODE, INCLUDING THE MECHANICAL,ELECTRICAL
EXISTING CONSTRUCTION IS SHOWN TO DEMONSTRATEINTEGRATION OF THE NEW WORK WITH THE EXISTINGSYSTEM OF FIRE AND SMOKE BARRIERS. THE EXISTINGCONSTRUCTION SHOWN IS PRESUMED TO BE INCOMPLIANCE WITH APPLICABLE CODES.
CODE COMPLIANCE PLANS INDICATE RATED WALLCONSTRUCTION, FIRE SEPARATION AND SMOKEPARTITIONS IN CONFORMANCE WITH APPLICABLE CODESFOR NEW AND REMODELED CONSTRUCTION.
THE DRAWINGS HAVE BEEN REVIEWED FOR CONFORMANCE TO:1.
AND PLUMBING CODES, 2017 EDITION.
2.
3.
CODE AND STANDARDS:
CODE DATA:
480 VANTAGE POINT, SUITE 201PROJECT ARCHITECTSPINNACLE ARCHITECTS
DAYTON, OHIO 45342
DAYTON, OHIO 45409MECHANICAL ELECTRICAL CONSULTANTS1400 WEST DOROTHY LANE
HEAPY ENGINEERING
AREA OF WORK
O
MICHAEL
7744TAYLOR
T.
OTSTA
OE FIH
EST
E
I
GR
T
H IRDRE A C
C
TE
PHARMACY CLEAN RM.(USP 800 COMPLIANCE) RENOVATION
VICINITY MAP: N
SHOP DRAWINGS SHOWING MORE DETAIL ONPRODUCT SPECIFICATIONS & INTERIORELEVATIONS & STOREFRONT WALLS &MOVEABLE & FIXED EQUIPMENT.
CARTER HEALTH/ MIDWEST MEDICAL SYSTEMS
CHP 101 GENERAL INFORMATION, CALCULATIONSCHP 201-202 FLOOR PLANSCHP 301-305 SECTIONSCHP 401-404 WALL ELEVATIONSCHP 501 CEILING PLANSCHP 601-603 CUT SHEETS AND SPECIFICATIONSCHP 701 NOT USED
LEGEND, SPECS AND SHEET INDEXELECTRICAL SCHEDULESSINGLE LINE DIAGRAMBASEMENT AND ROOF PLANSFIRST FLOOR - ELEC. DEMOLITION PLANFIRST FLOOR - LIGHTING PLANFIRST FLOOR - POWER & SYSTEMS PLAN
E001E002E003E004E101E201E301
M001
M002M003M004M005M007M008M101M201M301
MECHANICAL LEGEND, GENERAL NOTES, INDEXOF DRAWINGSMECHANICAL SCHEDULESMECHANICAL DETAILSMECHANICAL DETAILSMECHANICAL DETAILSMECHANICAL CONTROL SCHEMATICSMECHANICAL CONTROL SCHEMATICSPARTIAL FIRST FLOOR PLAN - DEMOLITIONPARTIAL FIRST FLOOR PLAN - NEW WORKHVAC ROOF
PLUMBING LEGEND AND SHEET INDEXSCHEDULES AND SPECIFICATIONSPARTIAL BASEMENT PLAN - DEMOLITIONPARTIAL FIRST FLOOR PLAN - DEMOLITIONPARTIAL BASEMENT PLAN - NEW WORKPARTIAL FIRST FLOOR PLAN - NEW WORK
P001P002P100P101P200P201
PLUMBING
MECHANICAL
ELECTRICAL
1
1
A1 - FLOOR PLANA2 - ELEVATIONSA3 - ELEVATIONS AND DETAILSA4 - SECTIONS AND DETAILSE1 - ELECTRICAL, DATA, PLUMBING PLANC1 - REFLECTED CEILING PLAN
MIDWEST MEDICAL SYSTEMS
UP 8R
5
3
4
8
13
14
CARDIOLOGY SUITENON-SLEEPING SUITE - 5,205 SQ. FT.
SUITE - 834 SQ. FT.
PHARMACY STAFF SUITENON-SLEEPING SUITE -2,483 SQ. FT.
CORRIDOR1526
MGR. OFC1545
ORDER ENTRY OFC1544
BULK STORAGE1537A
ADA STAFF TOILET1547
RECEIVING1548
CORRIDOR1527
PACKAGING1550 JAN
1533
POP1538
NARC RM1539
ORDER ENTRY1537
CHEMO RM1541
ANTI RM1542
IV RM1543
OFC1546
HD NON-STERILE1540
CORR.1535
1539
HVAC1542A
PHARMACY SUITENON-SLEEPING SUITE - 3,358 SQ. FT.CR
CR
CR
CODE LEGENDNON-COMBUSTIBLESMOKE RESISTANTWALL PARTITION
1-HR RATEDSMOKE BARRIER
1-HR. RATED WALL
2-HR. RATED WALL
3-HR. RATED WALL
O
MICHAEL
7744TAYLOR
T.
OTSTA
OE FIH
EST
E
I
GR
T
H IRDRE A C
C
TE
CODE COMPLIANCE PLAN
REMOVE EXIST. WALL PARTITIONREMOVE EXIST. DOOR, FRAME & HARDWAREREMOVE EXIST. CASEWORKREMOVE EXIST. PLUMBING FIXT. & CAP UTILITIESREMOVE EXIST. FLOORING & BASE & PREP FLOORSLAB FOR NEW FINISH MATERIAL SPECIFIED.EXISTING WALL PARTITION TO REMAINEXISTING DOOR, FRAME & HARDWARE TO REMAINEXISTING PTS TO REMAINREMOVE WINDOW.CUT STRAIGHT LINE WHERE FLOORING IS TOREMAINREMOVE PORTION OF WALL FOR NEW DOORINSTALLATIONSHORE EXISTING 2ND FLOOR STRUCTURE & WALLBEFORE REMOVING SECTION OF WALL FOR NEWOPENING -PROVIDE LINTEL ANGLES/BEAM OVERNEW OPENING IN THE BEARING WALL.REMOVE EXISTING LOCKERSDUST PARTITION & TEMPORARY CONST. ACCESSDOOR. PROVIDE STICKY MATS AND HEPAFILTRATION SYSTEM. ADJACENT PHARMACY"CLEAN SPACE" SHALL NOT BE COMPROMISED.REMOVE PORTION OF WALL FOR NEW ACCESSDOOR/FRAME INSTALLATION.USE CAUTION WHEN DEMOLISHING WALLS INTHESE MAIN POWER CONDUIT LOCATIONS.COORDINATE SAW CUTS/REMOVALS IN EXIST.CONCRETE WALL W/ ARCHITECT & STRUCTURALENGINEER.REMOVE ORIGINAL WINDOWS & FRAMES.
INFILL OLD WINDOW OPENINGS WITH FULL WYTHCMU'S - BEFORE CUTTING NEW RAMP OPENING &INSTALLATION OF NEW LINTEL.
1.2.3.4.5.
6.7.8.9.
10.
11.
12.
13.14.
15.
16.
17.
18.
19.
GENERAL DEMOLITION NOTES:ALL OBJECTS TO BE DEMOLISHED ARE SHOWN DASHED.
IF THE CONTRACTOR SUSPECTS OR DISCOVERSEXISTING PRODUCTS CONTAINING ASBESTOS/HAZARDOUS MATERIALS DURING THE COURSE OF THEWORK, HE IS EXPECTED TO STOP WORK AND ISOLATETHAT PRODUCT, NOTIFY THE OWNER OF ITS PRESENCEAND PROVIDE CLEAR ACCESS TO THE OWNER FOR ITSREMOVAL AND DISPOSAL.
THE GENERAL CONTRACTOR WILL BE RESPONSIBLE FORTHE COORDINATION BETWEEN THE PLUMBING,ELECTRICAL AND MECHANICAL CONTRACTORS BEFOREAND DURING DEMOLITION.
ALL PLUMBING AND ELECTRICAL DISCONNECTIONS ARETO BE TERMINATED AT THE NEAREST BRANCH. SEEPLUMBING & ELECTRICAL DWGS AND SPECS.
PROTECT ALL EXISTING TO REMAIN WALLS,CASEWORK, DOORS, WINDOWS, CEILINGS, FURNITURE& EQUIPMENT DURING DEMOLITION. REPAIR ORREPLACE ANY ITEMS DAMAGED DURINGCONSTRUCTION.
MAINTAIN ALL EGRESS PATHS AND FIRE RATEDASSEMBLIES THROUGHOUT CONSTRUCTION,INCLUDING PATCHING OF ALL HOLES EXPOSED INFLOOR CONSTRUCTION WITH 2 HOUR RATED FIRESAFING. BRACE & SHORE UP WALL ABOVE UNTIL NEWLINTEL CAN BE INSTALLED.
REMOVE ALL EXISTING FIXED MEDICAL EQUIPMENTAND RETURN TO OWNER.
PROVIDE HEPA FILTERS AND PROPER INFECTIONCONTROL DEVICES AND SYSTEMS THROUGHOUTCONSTRUCTION. THE PHARMACY IS A CLEAN SPACEAND IN SOME AREAS STERILE AND MUST BEPROTECTED AT ALL TIMES.
A.
B.
C.
D.
E.
F.
G.
H.
O
MICHAEL
7744TAYLOR
T.
OTSTA
OE FIH
EST
E
I
GR
T
H IRDRE A C
C
TE
DEMOLITION PLAN
RAMP
CORRIDOR1526
MGR. OFC1545
ORDER ENTRY OFC1544
BULK STORAGE1537A
ADA STAFF TOILET1547
RECEIVING1548
CORRIDOR1527
PACKAGING1550
JAN1533
POP1538
NARC RM1539
ORDER ENTRY1537
CHEMO RM1541
ANTI RM1542
IV RM1543
OFC1546OFC1546
HD NON-STERILE1540
24'-6
"
13'-8"
5"
16'-318" 47
8" 3'-6"
478"
8'-8
"47 8"
7'-0
"
6"
8'-8
"
7'-11"
6'-6
"47 8"
7'-5
1 8"
6"
CG-1
CG-1CORR.
1535
47 8"11
'-2"
47 8"
13'-0"478"1'-6"
618"
7'-3
"
47 8"
CG-1
CG-1
CG-1
CG-1
CG-1
8'-0"
478"
478"
4'-1034"
16'-0
"1'
-0"
1'-0
"
1539
9'-334" 47
8"
5'-4
3 4"
47 8"
CG-2CG-2
CG-1
CG-1CG-1 CG-1
CG-1
CG-1
CG-1
CG-1
4'-2
7 8"
4'-0"5'-6"
2'-4
"1'
-0"
CG-1
HVAC1542A
CG-1
9'-1
3 8"47 8"
10'-0
"47 8"
5'-9
"
11'-1118"
478"
9'-758"
478"9'-75
8"478"20'-01
8"
12'-1
11 4"5'
-111 2"
47 8"
4'-0
"
9'-5
1 8"
90 MIN FIRE RATED.PAINTED STEELACCESS PANEL ANDFRAME -3'-0" X 5'-6" DOORIN EXISTING OPENING
CG-1CG-1
CG-1
5'-4
3 8"
4'-6
"
5'-358"
CR
CR
SIM
41 4"
MH
CG-1
CR
NEW BIO CLEAN ROOM WALL PARTITION SYSTEMW/ INTEGRAL GLASS WINDOW LIGHTS. YKKAP, YES45 FS/F1 ALUM. STOREFRONT SYSTEM OR EQUALWITH 14" CLEAR TEMPERED GLAZING (MW)NEW 7' WIDE AUTO SLIDING ALUMINUM & GLASSDOORS WITH INTERLOCK BESAM SL500 CLEANROOM AUTO ALUM. SLIDER W/ 14" CLEARTEMPERED GLAZING PANELS (MW)LOW WALL RETURNS & WALL ENCLOSURES -SEEMECH DWGS.PASS THRU BOX (MW)BENCH SEAT (MW)SINK W/ EYEWASH (MW) - SEE PLUMB'G DWGSSUSP. GWB CEILING SYSTEM 58" TYP 'X' GWB ON 12"METAL SUSP. SYSTEM HUNG FROM STRUC.ABOVE(BY OWNER)NEW SHEET VINYL FLOORING W/ FLASH COVE BASAND HEAT WELDED SEAMS.NEW VAV ABOVE CEILING - SEE MECH DWGS.NEW COUNTER & BASE CABINETSNEW SINK - SEE PLUMBING DWGS.NEW EXHAUST DUCTWORK ABOVE CEILING - SEEMECH DWGS.NEW EXHAUST DUCT THRU WALL & EXTEND UPABOVE ROOF OF BUILDINGNEW DOOR, FRAME AND HARDWARERELOCATED DOOR, FRAME AND HARDWARERELOCATED CASEWORK AND/OR EQUIPMENTNEW ABOVE CEILING MECHANICAL UNIT - SEEMECH DWGS.SEALED CLEAN ROOM LED LIGHT FIXTURES (MC) -SEE ELECT. DWGS.LAMINAR FLOW HOOD UNIT (MC)CLEAN ROOM MOBILE STORAGE UNITS (MC)EXISTING DOOR TO REMAINPASS THRU REFRIGERATOR (MW)IV PASS THRU (MW)NEW MECHANICAL UNIT - SEE MECH. DWGSNEW PNUEMATIC TUBE STATION - BY OWNER -ENCLOSURE BY G.C. - COORD. W/ OWNER'SSUPPLIERPHARMACY SHELVING & EQUIPMENT (MW)WORK TABLE (MC)ADA RAMP UP TO OLD PHARMACY SPACENEW TOILET - SEE PLUMB'G DWGSNEW WALL PARTITIONNEW DOUBLE TIER LOCKERSNEW ALUMINUM STOREFRONT SYSTEMNEW DOOR, FRAME AND HARDWARENEW FFE (BY OWNER)NEW FLOORING & BASEPAINT ALL WALLS. NEW WALLS: 1 PRIME COAT & 2FINISH COATS, EXISTING WALLS: 1 FINISH COATNEW COUNTER MOUNTED SINK (MW)EXISTING WALL TO REMAINSET NEW FURRED OUT WALL AS TIGHT TO EXISTINCONDUIT AS POSSIBLE.CLEAN UP MASONRY JAMBS & COVER W/ FURRINGAND GWB. ALSO ADD A PAIR OF STEEL ANGLELINTELS WHERE HOLE HAS BEEN CUT THRUMASONRY WALL BEFORE INSTALLING NEW ACCESSDOOR AND FRAME.NEW METAL DIAMOND PLATE STEPS. 11" WIDE XMAX 7" TALL DOWN INTO HVAC ROOM. PROVIDEGALV. STEEL ANGLE AT TOP STEP TO HOLDSTRINGERS.ADD WATERPROOF PAINT" ZINSSER WATERTITE - LLOW VOC 7 MILDEW PROOF TO EXTERIORCONCRETE WALL FROM FLOOR TO DECK BEFOREINSTALLATION OF PVC MEMBRANE.TEMPORARY WALL - REMOVE ONCE NEWPHARMACY HAS BEEN CONSTRUCTED AND CAN BESECURED.COPIER BY OWNERRECESSED ELECTRIC PANEL - SEE ELEC. DWGS.
1.
2.
3.
4.5.6.7.
8.
9.10.11.12.
13.
14.15.16.17.
18.
19.20.21.22.23.24.25.
26.27.28.29.30.31.32.33.34.35.36.
37.38.39.
40.
41.
42.
43.
44.45.
NEW CONSTRUCTION NOTES:*
GENERAL NOTES:GENERAL CONTRACTOR TO PATCH/REPAIR ANYAND ALL WALLS AND FLOORS DAMAGED BYCONSTRUCTION BEFORE APPLYING FINISHES.
CONTRACTOR SHALL INSTALL F.R.T. BLOCKING INWALLS OR CEILINGS TO SUPPORT ALL MOUNTEDFIXTURES / EQUIPMENT.
C.P.U.'s ARE TO BE LOCATED OFF THE FLOOR.C.P.U. BRACKETS ARE TO BE O.F.O.I.
ALL MOUNTING BRACKETS FOR TV's / MONITORSTO BE O.F.C.I.
ADJUSTABLE MONITOR BRACKETS ARE TO BEO.F.O.I.
TAKE SPECIAL CARE TO PROTECT HIGH POWERVERTICAL & HORIZ. CONDUIT LINES THAT AREEXISTING THROUGHOUT THIS SPACE.
FIRE CAULK - SEAL ALL HOLES IN EXISTING WEST &NORTH WALLS TO PROVIDE A CONTINUOUS 2HOUR FIRE BARRIER SYSTEM.
A.
B.
C.
D.
E.
F.
G.
O
MICHAEL
7744TAYLOR
T.
OTSTA
OE FIH
EST
E
I
GR
T
H IRDRE A C
C
TE
NEW WORK PLAN
1-1/2 PR. BB HINGES - HEAVY DUTY - US26D1 EA. ADA LEVER LOCKSET (STOREROOM) US26D1 EA. ELECTRIC STRIKE1 EA. OWNER'S CARD READER1 EA. SILL SWEEP1 EA. WALL STOP
HARDWARE SET 3
1-1/2 PR. BB HINGES - HEAVY DUTY - US26D1 EA. ADA LEVER LATCHSET (PASSAGE FUNCTION) US26D3 EA. DOOR FRAME SILENCERS1 EA. WALL STOP
HARDWARE SET 4
1-1/2 PR. BB HINGES - HEAVY DUTY - US26D1 EA. ADA LEVER LOCKSET (OFFICE FUNCTION) US26D3 EA. DOOR FRAME SILENCERS1 EA. WALL STOP
HARDWARE SET 2 1-1/2 PR. BB HINGES - HEAVY DUTY - US26D1 EA. ADA LEVER LATCHSET (PRIVACY FUNCTION) US26D1 EA. ADA PARALLEL ARM CLOSER3 EA. DOOR FRAME SILENCERS1 EA. WALL STOP1 EA. SIGNAGE "ADA" ACCESSIBLE RESTROOM
HARDWARE SET 5
1-1/2 PR. BB HINGES - HEAVY DUTY - US26D1 EA. ADA LEVER LOCKSET (OFFICE FUNCTION) US26D1 EA. ADA PARALLEL ARM CLOSER1 EA. WALL MOUNTED MAGNETIC HOLD OPEN TIED TO FIRE ALARM.3 EA. DOOR FRAME SILENCERS1 EA. WALL STOP
HARDWARE SET 1
G.C. TO PROVIDE
NOTES:1. MODIFY DOOR/ HARDWARE TO BE CONTROLLED BY OWNER SUPPLIED CARD READER. ADD NEW ELECTRIC STRIKE & POWER. COORDINATE WITH CARD READER CONSULTANT.2. REPAINT DOOR & FRAME.3. PROVIDE MFRS. STD. ADA HARDWARE, CLOSER, HINGES, WALL STOP ETC.4. AUTOMATIC ALUMINUM SLIDING DOOR WITH FULL BREAK OUT CAPABILITY. ISO3(CLASS 1) CLEAN ROOM RATED W/ WEATHERSTRIPPING. (MW)5. PROVIDE WALL MTD. MAGNETIC HOLD OPEN - TO RELEASE. ON ACTIVATION OF THE FIRE ALARM SYSTEM. DOOR SHALL HAVE ADA CLOSER.6. FIRE CAULK AROUND FRAME & PROVIDE 2 HOUR FIRE RATED CAULKING/ FIRESAFING SYSTEM AT DOOR/WALL INTERSECTION.7. ADD AN ADA PARALLEL CLOSER TO THIS DOOR IF NONE EXISTS.
DOOR TYPES
8"
8"1'-0"
2'-1
"
FLASH COVED VINYLFLOORING ON CLEAN
RM. SIDE-TYP.
412" W
5"5"
412" W
EXTEND STUDS & ONESIDE GWB TO DECK
ABOVE & SEAL
FRT WOOD BLOCKINGAT STOREFRONT HEAD W/
CONT. BEAD OF CAULKBOTH SIDES
AT CEILING TO CREATE ASEALED CLEAN RM.
ENCLOSURE
58" TYPE 'X' GWBFASTENED TO MTL.FRAMING SUSPENSIONSYSTEM
YKKAP ALUM.STOREFRONTFRAMING W/1/4"CLEAR TEMPEREDGLAZING (MW)
FLASH COVED VINYLFLOORING ON CLEAN
RM. SIDE-TYP.
YKKAP ALUM.STOREFRONTFRAMING W/1/4"CLEAR TEMPEREDGLAZING (MW)
58" TYPE 'X' GWBFASTENED TO MTL.FRAMING SUSPENSIONSYSTEM
1-1/2" MTL FRAMINGSYSTEM SUSP. FROMSTRUC. ABOVE
1"
FRT WOODBLOCKING ATSTOREFRONT
HEAD.
8'-0
"
8'-0
"
VINYL-FACEDDRYWALL PANELS
OR GWB SYSTEM. SEE PLAN.
G.C. TO PROVIDEGWB SOFFITS
7'-9
"
7'-2
"SINGLE
DOOR WIDTH
DOUBLE ENTRY
PAIR WIDTH
FRAME TYPES
BY ALUM.SLIDING DMANUF.
OR SLIDER
3-5/8" MT'L STUDS
FIRECODE 'X' EA. SIDE5/8" GYP. BD.
@ 16" O.C.
3-5/8" MT'L STUDS
5/8" GYP. BD.
@ 16" O.C.
FIRECODE 'X' EA. SIDE
BLANKET (S.A.B.)2" SOUND ATTENUATION
2 LAYERS -5/8" GYP. BD.
3-5/8 MT'L STUDS
FIRECODE "X" EA. SIDE.
@ 16" O.C.2" SOUND ATTENUATIONBLANKET (S.A.B.)
FIRECODE "X" EA. SIDE. 2 LAYERS -5/8" GYP. BD.
@ 16" O.C.3-5/8 MT'L STUDS
3-5/8 MT'L STUDS@ 16" O.C.
FIRECODE "X"5/8" GYP. BD. 5/8" GYP. BD.
FIRECODE "X"
@ 16" O.C.3-5/8 MT'L STUDS
BLANKET (S.A.B.)2" SOUND ATTENUATION
3-58" 58"
4-14"
3-58" 58"
4-14"
58"
3-58" 58"
6-18"
58"
3-58" 58"
6-18"
58"
3-58" 58"
4-78"
58"
3-58" 58"
4-78"
5/8" GYP. BD. FIRECODE TYPE 'X'
6 " BATT. INSULATION
ANTIMICROBIAL WATER RESISTANT GWB
6 MT'L STUDS@ 16" O.C.
918"
2" RIGID INSUL. W/ EIFS RAIN SCREENFINISH SYSTEM
5/8" GLASS FIBER FACED GWB EXT. SHEATHING
478"
2"
JAMB DETAIL
534"
5 8" 2"
HEAD DETAIL
534"5 8"
2"
478"
FRAME DETAILS
(2) 20 GA. 358" METAL STUDS
58" GYP. BD. EACH SIDE35
8" METAL STUDS @ 16" o.c.
CAULK PERIMITER(BOTH SIDES)
58" GYP. BD. EACH SIDE
358" METAL STUDS @ 16" o.c.
CAULK PERIMITER(BOTH SIDES)
FLASH COVED VINYLFLOORING ON CLEAN
RM. SIDE-TYP.
YKKAP ALUM.STOREFRONTFRAMING W/1/4"CLEAR TEMPEREDGLAZING (MW)
58" TYPE 'X' GWBFASTENED TO MTL.FRAMING SUSPENSIONSYSTEM
1-1/2" MTL FRAMINGSYSTEM SUSP. FROMSTRUC. ABOVE
FRT WOODBLOCKING ATSTOREFRONT
HEAD.
8'-0
" 8'-6
"
G.C. TO PROVIDEGWB SOFFITS
(7'-9
") IN
RM
. 154
0)BLANKET (S.A.B.)3" SOUND ATTENUATION
O
MICHAEL
7744TAYLOR
T.
OTSTA
OE FIH
EST
E
I
GR
T
H IRDRE A C
C
TE
STOREFRONT @ PERIMETER WALL STOREFRONT @ INTERIOR WALL
WALL TYPES
STOREFRONT @ INTERIOR WALL
EXISTINGCEILING
N.C.
GBS @7'-81
2"
1.
2.
3.
4.
5.
NEW SUSP. GWB CEILING SYSTEM. 58" TYPE 'X' GWBON 1-1/2" METAL HANGING GRID SUPPORTED BYSTRUCTURE ABOVE.CUT/ MODIFY EXIST. SUSP. CEILING SYSTEM TOACHIEVE NEW DESIGN SHOWN. ATTACH MODIFIEDEXISTING CLG. TO NEW WALL.NEW STORE FRONT WALL SYSTEM TO ATTACH TOGWB CLG. & BE CAULKED ON BOTH SIDES ASDETAILED.NEW SEALED LIGHT FIXTURES & HVAC DIFFUSERS.(MC) SEE ELECT. & MECH DWGS.EXISTING SUSP. CLG - TO REMAIN. SEE ELECT. &MECH DWGS FOR MODIFICATIONS.
NEW CEILING NOTES:
- CUBICAL CURTAIN TRACKC.C.T.
ABBREVIATIONS
- NO CEILING- GYP. BD. BULKHEAD
- GYP. BD. SOFFIT
- GYP. BD. CEILING- GYP. BD. LIGHT COVE
G.B.B.
G.B.L.C.G.B.S.
G.B.C.
N.C.
LEGEND
SUPPLY DIFFUSERS
RETURN-AIR GRILLE
CEILING HEIGHT
LIGHT FIXTURES
GYP. BD. HEADER
NEW C.C.T.
ACCESS PANELS
EXIT SIGNS
COURTYARDEXTERIOR
NEW DUCT WORKFROM UNIT OVER ROOF & DOWN
INTO NEW PHARMACY
NEW AHU-24 (SEE HVAC DWGS)SET ON EXISTING STEEL FRAMEPLUS NEW INFILL STEEL - SEESTRUCTURAL DWGS. PROVIDESTEEL ACCESS LADDER ALSOSHOWN ON STRUCTURAL DWGS.
COURTYARDEXTERIOR
REMOVE EXISTING WINDOW& WALL BELOW & REPLACEW/ NEW 3' X 7' INSULATEDPTD H.M. DOOR & FRAME.W/ ADA CUSH TYPE PARALLELARM CLOSER. PROVIDETHERMALLY BROKEN ADATHRESHOLDWEATHERSTRIPPING PKGINCLUDING SILL SWEEP.
VARI
ES
SAC
EXISTING 10" CONC.STRUCTURAL FLOOR SLAB
714" 5'-61
4"
1ST FLR. 46' BLDG.
1ST FLR. 71' BLDG.
2ND FLR. 71 BLDG.
GRANULAR FILL@ GRADE INCOURTYARD
MEP SUB-CONTR. COORDALL NEW OPENG'S INCONC. WALL W/ STRUC. -ENG.& PROVIDEWATERTIGHT SEALANTSYSTEM AROUND ALLOPNGS.
EXISTING EXTERIORCOURTYARD
O
MICHAEL
7744TAYLOR
T.
OTSTA
OE FIH
EST
E
I
GR
T
H IRDRE A C
C
TE
NEW REFLECTED CEILING PLAN
ROOF PLAN
SECTION THRU MECH RM. 1542A
ADA STAFF TOILET 1547 ADA STAFF TOILET 1547 ADA STAFF TOILET 1547 TUBE STATION
GB-30
TPGB-42
2'-9
"
1'-0"
2'-9"
GB-42
GB-30
2'-9
"
6"CL
MR1
3'-4
"
1'-6" 1'-9"±
2'-1
0"
SD(OFCI)
PTD(OFCI)
PTD(OFCI)
MR1
PTSPTS
7'-9
"
7'-9
"
CR-1 CR-1
7'-9
"
7'-9
"
UNIT BY OWNERSSUPPLIER - COORD.OPENINGS IN NEW GWBPARTITION W/ PTS SUPPLIER.
O
MICHAEL
7744TAYLOR
T.
OTSTA
OE FIH
EST
E
I
GR
T
H IRDRE A C
C
TE
RAMP DETAILRAMP DETAIL CAP DETAIL
MGR. OFC1545
ORDER ENTRY OFC1544
BULK STORAGE1537A
ADA STAFF TOILET1547
RECEIVING1548
CORRIDOR1527
PACKAGING1550
JAN1533
POP1538
NARC RM1539
ORDER ENTRY1537
CHEMO RM1541
ANTI RM1542
IV RM1543
OFC1546OFC1546
HD NON-STERILE1540
CORR.1535
HVAC1542A
SV-2/FLASH COVESAC-2P-3
SV-1/ FLASH COVESAC-2P-3
SV-1/ FLASH COVE
SV-1/ FLASH COVE
SV-1/ FLASH COVE
SV-1/ FLASH COVE
SV-1/ FLASH COVE
CPT-1SAC-1P-1
SV-2/FLASH COVESAC-2P-3
SV-2/FLASH COVESAC-2P-3
SV-1/ FLASH COVESAC-2P-3
CPT-1SAC-1P-1
CPT-1SAC-1P-1
EXIS.EXIS.
SAC-2P-1
SAC-2P-1
SAC-2P-1
SAC-2P-1
SAC-2P-1
SV-1/ FLASH COVESAC-2P-1
CPT-1SAC-1P-1
SV-1/ FLASH COVESAC-2P-3
EXIS.
SEALED CONCRETE
CPT-1SAC-2P-1
EXIS.
6'-0
"
FLOORINGSV-1, GERFLOR, SYMBIOZ, COLOR MOLE. OWNER PROVIDED,CONTRACTOR INSTALLEDSV-2, GERFLOR, SYMBIOZ, COLOR COTTONCPT-1, EF CONTRACT, GEO ACCENTS II, GAC44 CITY THREADS
WALL BASECRB-1 JOHNSONITE, 4" COVE, COLOR 49 BEIGE
PAINTP-1 SW6386 NAPERYP-2 SW6106 KILIM BEIGE, METAL DOORS, DOOR FRAMESP-3 SW7010, WHITE DUCK
CEILING TILESAC-1 ARMSTRONG, OPTIMA, 3150 (24 X 24 X 34") SQUARE, WHITESAC-2 GRIDSTONE, CLEAN ROOM GYPSUM CEILING PANELS 2X2
FINISH LEGEND
O
MICHAEL
7744TAYLOR
T.
OTSTA
OE FIH
EST
E
I
GR
T
H IRDRE A C
C
TE
FINISH PLAN
A1
P1 P1OR
A1
OH1
2
1
P2
B
P2
GENERAL FLOOR PLAN NOTES
RISER OR STACK NUMBER
DETAIL: B = DETAIL DESIGNATION P2 = SHEET W HERE DETAIL IS LOCATED
FIRE SUPPRESSION HAZARD CLASSIFICATION AND HAZARD CLASSIFICATION GROUP
SECTION: 1 = SECTION DESIGNATION P2 = SHEET W HERE DETAIL IS LOCATED
EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TO SCHEDULES.
EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK. LETTER DESIGNATIONS REFER TO SCHEDULES.
CONNECT TO EXISTING
PLAN NOTE. APPLIES ONLY TO THE SHEET W HICH IT IS SHOW N UNLESS NOTED OTHERW ISE.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
"UP TO" SYMBOL (ITEM ON FLOOR ABOVE)
10" 10"
ELEV: 8' - 0"ELEV: 8' - 0"
TOE: 3' - 0"
BOE: 0' - 6"
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR BOTTOM OF EQUIPMENT, UNLESS NOTED OTHERW ISE
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO CENTERLINE OF PIPE, UNLESS NOTED OTHERW ISE
FIRE SUPPRESSION SYMBOLSDOUBLE LINE SINGLE LINE
CONCEALED PENDENT SPRINKLER
FS
PIV
S
FIRE HYDRANT
FLOW SW ITCH
GATE VALVE OS&Y
INSTITUTIONAL PENDENT SPRINKLER
PENDENT SPRINKLER
POST INDICATOR VALVE
RECESSED PENDENT SPRINKLER
SIDE W ALL SPRINKLER
SUPERVISED VALVE
UPRIGHT SPRINKLER
PIPING SYMBOLSDOUBLE LINE SINGLE LINE
BOTTOM CONNECTION (45°)
BRANCH TEE CONNECTION (NOTE: BULLHEAD TEE'S ARE NOT PERMITTED)
DIRECTION OF PITCH
DROP
ELBOW DOW N
ELBOW UP
EXISTING PIPE TO BE REMOVED
EXISTING PIPE TO REMAIN
FLOW DIRECTION DESIGNATION
PUMP
RISE
TOP CONNECTION (45°)
TOP CONNECTION (90°)
BOTTOM CONNECTION (90°)
DD
RR
SPECIALTY GAS SYMBOLS
AIR OUTLET - LAB TYPE
VC
VC
CAR BON DIOXIDE OUTLET - H OSPITAL TYPE
M EDICAL AIR OUTLET - HOSPITAL TYPE
M EDICAL VACU UM INLET - HOSPITAL TYPE
NITROGEN OUTLET - H OSPITAL TYPE
NITROUS OXIDE OUTLET - HOSPITAL TYPE
OXYGEN OU TLET - HOSPITAL TYPE
W AGD INLET - HOSPITAL TYPE
NATURAL GAS OUTLET - LAB TYPE
VACUUM OU TLET - LAB TYPE
VAC UUM C LEAN ING STATION - W ALL
VACUUM CLEANING STATION - FLOOR
PLUMBING AND FIRE SUPPRESSION
PIPING DESIGNATIONS
DOM ESTIC COLD W ATER
DOM ESTIC HOT W ATER
DOM ESTIC HOT W ATER RETURN
EXISTING PIPE TO REMAIN
EXISTING PIPE TO BE REMOVED
HOT W ATER PIPE (140 DEGS. F.)
HOT W ATER PIPE (180 DEGS. F.)
HOT W ATER RETURN PIPE (140 DEGS. F.)
HOT W ATER RETURN PIPE (180 DEGS. F.)
ARGO N PIPE
COMPRESSED AIR PIPE
MEDICAL CARBON DIOXIDE PIPE
COMBINATION FIRE SUPPRESSION AND DOMESTIC W ATER SERVICE
DIESEL FUEL PIPE
SPRINKLER PIPE (DRY)
FIRE SUPPRESSION (STANDPIPE / SPRINKLER MAIN)
FIRE SERVICE
FUEL OIL FLOW LINE
FUEL OIL GAUGE LINE
FUEL OIL RETURN LINE
FUEL OIL SUPPLY LINE
NATURAL GAS PIPE
GARAGE DRAINAGE PIPE
GAS SERVICE
HYDROGEN PIPE
HELIUM PIPE
MEDICAL INSTRUMENT AIR PIPE
KITCHEN W ASTE PIPE
LABORATORY COMPRESSED AIR PIPE
LABORATORY VENT PIPE
LABORATORY VACUUM PIPE
LABORATORY W ASTE PIPE
MEDICAL NITROGEN PIPE
MEDICAL COMPRESSED AIR PIPE
MEDICAL-SURGICAL VACUUM PIPE
GASOLINE PIPE (NON-LEAD)
MEDICAL NITROUS OXIDE PIPE
NON-POTABLE
MEDICAL OXYGEN PIPE
(OVERFLOW ) SECONDARY STORM DRAINAGE PIPE
PROPANE GAS PIPE
PUMP DISCHARGE PIPE
PRE-ACTION / DELUGE SPRINKLER PIPE
PURE W ATER PIPE
SPRINKLER PIPE (W ET)
SANITARY DRAINAGE PIPE
SOFT COLD W ATER
SPRINKLER DRAIN PIPE
STORM DRAINAGE PIPE
FUEL TANK VENT PIPE
TRAP PRIMER DISCHARG E PIPE
TEMPERED W ATER PIPE
SANITARY SEW ER VENT
W ASTE ANESTHESIA GAS DISPOSAL PIPE
W ATER SERVICE
140
LV
180
140R
180R
AR
CA
CO2
CW S
DF
DS
F
FS
FOF
FOG
FOR
FOS
G
GD
GS
H2
HE
IA
IV
IW
LA
LV
LW
N2
MA
MV
NG
NO
NPW
O2
OD
P
PD
PS
PW
S
SAN
SCW
SD
STM
T
TP
TW
V
W AGD
W S
INDIR ECT VEN T PIPE
INDIRECT W ASTE PIPE
K
3
3
CHECK VALVE
T
P
FOB
FOT
SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR REQUIRED TYPE BASED ON APPLICATIONS)
CONCEN TRIC PIPE R EDUCER
ECCENTRIC PIPE REDUCER
PRESSURE GAUGE
TEMPERATURE GAUGE OR THERMOMETER
UNION
CLEANOUT
STRAINER
STRAINER W ITH A BLOW DOW N VALVE AND HOSE CONNECTION
DRAIN VALVE W ITH HOSE END CONNECTION
AUTOMATIC FLOW CONTROLLER W ITH P/T PLUG IN AND OUT
EXPANSION JOINT
PRESSURE REGULATING VALVE
SAFETY RELIEF VALVE. PIPE DISCHARGE AIR GAPPED TO FLOOR DRAIN UNLESS NOTED OTHERW ISE.
PRESSURE AND TEMPERATURE TEST PLUG
TRAP PRIMER
VACUUM GAUGE W ITH STOP
CLEANOUT TO GRADE OR FINISHED FLOOR
END CAP
MIXING FAU CET
PLUG
HOSE BIB
W ALL HYDRANT
PLUG VALVE
SHUTOFF VALVE AND BOX
SHUTOFF VALVE ON RISER
V
VB
TP
CO
COMBINATION SHUTOFF AND BALANCING VALVE (REFER TO SPECIFICATIONS FOR REQUIRED TYPE BASED ON APPLICATIONS)
BALL VALVE
BUTTERFLY VALVE
GATE VALVE
VALVES AND FITTINGSDOUBLE LINE SINGLE LINE
SOLENOID VALVES
P/T PRESSURE AND TEMPERATURE SAFETY RELIEF VALVE. PIPE DISCHARGE AIR GAPPED TO FLOOR DRAIN UNLESS NOTED OTHERW ISE.
FIRE DEPARTMENT VALVE
W ATER METERM
ACID VENT PIPEAV
ACID W ASTE PIPEAW
ABBREVIATIONS
AAP - AREA ALARM PANEL (MEDICAL GAS)AC - AIR COMPRESSOR OR AIR CONDITIONERACC - ACCESSACCU - AIR COOLED CONDENSING UNITAD - ACCESS DOOR OR AREA DRAINADB - ACID DILUTION BASINADJ - ADJUSTABLEAFF - ABOVE FINISHED FLOORAFG - ABOVE FINISHED GRADEALT - ALTERNATEAP - ACCESS PANELAPPROX - APPROXIMATEAR - AIR RECEIVER OR ARGONARCH - ARCHITECT OR ARCHITECTURALASSY - ASSEMBLYAV - ACID VENTAW - ACID W ASTE
BDD - BACK DRAFT DAMPERBFP - BACKFLOW PREVENTERBLDG - BUILDINGBOB - BOTTOM OF BEAMBOD - BOTTOM OF DUCTBOE - BOTTOM OF EQUIPMENTBOF - BOTTOM OF FOOTINGBOG - BOTTOM OF GRILLEBOP - BOTTOM OF PIPEBOT - BOTTOMBT - BATHTUBBTU - BRITISH THERMAL UNITBTUH - BRITISH THERMAL UNIT PER HOURBTW N - BETW EEN
CA - COMPRESSED AIRCB - CATCH BASINCBD - COUNTER BALANCED BACKDRAFT DAMPERCFCI - CONTRACTOR FURNISHED CONTRACTOR
INSTALLEDCFM - CUBIC FEET PER MINUTECHS - CHILLED W ATER SUPPLYCHR - CHILLED W ATER RETURNCI - CAST IRONCK - CLINICAL SINKCLG - CEILINGCMU - CONCRETE MASONRY UNITCO - CLEAN OUTCO2 - MEDICAL CARBON DIOXIDECONN - CONNECT OR CONNECTIONCONTR - CONTRACTORCORR - CORRIDORCS - CLINICAL SINK OR COLD SOFT W ATERCTR - CENTERCU - COPPERCW - COLD W ATERCW S - COMBINATION W ATER SERVICE
OR CONDENSER W ATER SUPPLYCW R - CONDENSER W ATER RETURN
D - DEPTH OR DRAIN LINEDD - DECK DRAINDET - DETAILDF - DRINKING FOUNTAIN OR W ATER COOLER
OR DIESEL FUELDFU - DRAINAGE FIXTURE UNITDI - DEIONIZED W ATERDIA - DIAMETERDIM - DIMENSIONDN - DOW NDS - DOW N SPOUT OR SPRINKLER (DRY)DT - PERFORATED DRAIN TILEDW G - DRAW ING
EA - EACHEC - ELECTRICAL CONTRACTOR (DIVISION 26)EEW - EMERGENCY EYE W ASHEJ - EXPANSION JOINTELEC - ELECTRICALELEV - ELEVATOREQ - EQUALEQUIP - EQUIPMENTET - EXPANSION TANKETR - EXISTING TO REMAINES - EMERGENCY SHOW EREQS - EQUIPMENT SUPPLIEREW C - ELECTRICAL W ATER COOLEREXH - EXHAUST AIREXP - EXPANSIONEXT - EXTERIOREX - EXISTING
F - FIRE SUPPRESSION (STANDPIPE/SPRINKLER MAIN)FCE - FIRE CONTROL EQUIPMENTFCO - FLOOR CLEANOUTFD - FLOOR DRAINFDC - FIRE DEPARTMENT CONNECTIONFDV - FIRE DEPARTMENT VALVEFF - FINISHED FLOOR ELEVATIONFHC - FIRE HOSE CABINETFLR - FLOORFM - FORCE MAINFOB - FLAT ON BOTTOM
FOF - FUEL OIL FLOWFOG - FUEL OIL GAUGEFOR - FUEL OIL RETURNFOS - FUEL OIL SUPPLYFOT - FLAT ON TOPFPM - FEET PER MINUTEFR - FIRE RISERFS - FLOOR SINK OR FIRE SERVICEFSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)FT - FEETFTG - FOOTING
G - GAS OR NATURAL GASGA - GAUGEGAL - GALLONGALV - GALVANIZEDGC - GENERAL TRADES CONTRACTORGD - GARAGE DRAINAGEGPM - GALLONS PER MINUTEGS - GAS SERVICEGW - GREASE W ASTE
H2 - HYDROGENHB - HOSE BIBBHC - HVAC CONTRACTOR (DIVISION 23)HD - HUB DRAINHE - HELIUMHG - REFRIGERANT HOT GASHP - HORSEPOW ER OR HIGH POINTHPC - HIGH PRESSURE CONDENSATE RETURNHPS - HIGH PRESSURE STEAM SUPPLYHPW - HIGH PURITY W ATERHPW R - HIGH PURITY W ATER RETURNHR - HOSE REELHT - HEAT TRACEHTR - HEATERHVAC - HEATING, VENTILATING, AND AIR CONDITIONINGHW - HOT W ATERHW R - HEATING HOT W ATER RETURNHW S - HEATING HOT W ATER SUPPLY
IA - MEDICAL INSTRUMENT AIRID - INSIDE DIAMETERINV - INVERT ELEVATIONIN - INCHESIV - INDIRECT VENTIW - INDIRECT W ASTE
JS - JANITOR SINK
K - KITCHEN W ASTEKEC - KITCHEN EQUIPMENT CONTRACTOR
L - LENGTHLA - LABORATORY COMPRESSED AIRLAV - LAVATORYLBS - POUNDSLCW - LABORATORY COLD W ATERLEC - LABORATORY EQUIPMENT CONTRACTORLHW - LABORATORY HOT W ATERLHW R - LABORATORY HOT W ATER RETURNLPC - LOW PRESSURE CONDENSATE RETURNLPS - LOW PRESSURE STEAM SUPPLYLV - LABORATORY VACUUM OR LABORATORY VENTLW - LABORATORY W ASTE
MA - MEDICAL COMPRESSED AIRMAP - MASTER ALARM PANEL (MEDICAL GAS)MAX - MAXIMUMMB - MOP BASINMC - MECHANICAL CONTRACTOR (DIVISION 23)MEZZ - MEZZANINEMFR - MANUFACTURERMH - MANHOLEMIN - MINIMUM OR MINUTEMISC - MISCELLANEOUSMTD - MOUNTEDMTG - MOUNTINGMPC - MEDIUM PRESSURE CONDENSATE RETURNMPS - MEDIUM PRESSURE STEAM SUPPLYMU - W ATER MAKE-UPMV - MEDICAL SURGICAL VACUUM
N2 - MEDICAL NITROGENN/C - NORMALLY CLOSEDNG - GASOLINE (NON-LEAD)NIC - NOT IN CONTRACTN/O - NORMALLY OPENNO - MEDICAL NITROUS OXIDENOM - NOMINALNPW - NON-POTABLE W ATERNPT - NATIONAL PIPE THREADNTS - NOT TO SCALE
02 - MEDICAL OXYGENOA - OUTDOOR AIROD - OUTSIDE DIAMETER OR OVERFLOW DRAINOFCI - OW NER FURNISHED CONTRACTOR
INSTALLEDOFOI - OW NER FURNISHED OW NER INSTALLED
P - PROPANE GASPC - PLUMBING CONTRACTOR (DIVISION 22)
OR PUMPED CONDENSATE RETURNPD - PUMP D ISCHARGE OR PARAPET DRAINPIV - POST INDICATOR VALVEPLBG - PLUMBINGPS - PRE-ACTION/DELUGE SPRINKLER PRESS - PRESSUREPRV - PRESSURE REGULATING VALVEPSF - POUNDS PER SQUARE FOOTPSI - POUNDS PER SQUARE INCHPSV - PRESSURE SUSTAINING VALVEPSIG - POUNDS PER SQUARE INCH GAUGEPW - PURE W ATER
RA - RETURN AIRRAD - RADIUSRCP - REINFORCED CONCRETE PIPERD - ROOF DRAINREC - RECESSEDREQD - REQUIREDRI - ROUGH INRL - REFRIGERANT LIQUIDROS - REVERSE OSMOSIS W ATER SUPPLYROR - REVERSE OSMOSIS W ATER RETURNRPM - REVOLUTIONS PER MINUTERS - REFRIGERANT SUCTIONRV - RELIEF VALVE
S - SPRINKLER (W ET)SA - SHOCK ARRESTOR OR SUPPLY AIRSAN - SANITARY OR SANITARY DRAINSCH - SCHEDULESCW - SOFT COLD W ATERSD - SPRINKLER DRAIN OR SUBSOIL DRAINSH - SHOW ERSHT - SHEETSK - SINKSPEC - SPECIFICATIONSSQ - SQUARESR - SUPPLY RISERSS - SANITARY STACK (SOIL OR W ASTE) OR
STAINLESS STEELSTD - STANDARDSTM - STORM OR STORM DRAINAGESTRUC - STRUCTURAL OR STRUCTURESUC - SITE UTILITY CONTRACTOR
T - FUEL TANK VENTTD - TRENCH DRAINTEMP - TEMPERATURETOB - TOP OF BEAMTOD - TOP OF DUCTTOE - TOP OF EQUIPMENTTOF - TOP OF FOOTINGTOJ - TOP OF JOISTTOP - TOP OF PIPETOS - TOP OF SLAB OR TOP OF STEELTF - TRAP FILLERTP - TRAP PRIMER OR TRAP PRIMER DISCHARGETW - TEMPERED W ATERTYP - TYPICAL
UR - URINALUNO - UNLESS NOTED OTHERW ISE
V - VENT OR SANITARY SEW ER VENTVAC - VACUUMVC - VACUUM CLEANINGVCV - VACUUM CLEANING VALVEVE - VACUUM EXHAUSTVEL - VELOCITYVIB - VALVE IN BOXVOL - VOLUMEVP - VACUUM PUMPVS - VENT STACKVTR - VENT THROUGH ROOFVR - VENT RISER
W / - W ITHW /O - W ITHOUTW - W ASTEW AGD - W ASTE ANESTHESIA GAS DISPOSALW C - W ATER CLOSETW CO - W ALL CLEANOUTW H - W ALL HYDRANT OR W ATER HEATERW IV - W ALL INDICATOR VALVEW S - W ATER SERVICE
YCO - YARD CLEANOUT
ZVC - ZONE VALVE CABINET
PIPE RISER
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT
TO MODIFICATIONS ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT
NECESSARILY BE USED ON THIS PROJECT. Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
5/2
01
9 7
:03
:44
AM
C:\
BIM
\Mod
el\20
19
-05
07
8-M
EP
-Ce
ntr
al_
WS
McC
am
ey.r
vt
2019-05078
ABN
W SM
July 24, 2019
P001
PLUMBING LEGENDAND SHEET INDEX
1 2019.07.24 ADDENDUM 1
SHEET INDEX - PLUMBING
SHEET NUMBER SHEET NAME
P001 PLUMBING LEGEND AND SHEET INDEX
P002 SCHEDULES AND SPECIFICATIONS
P100 PARTIAL BASEMENT PLAN - DEMOLITION
P101 PARTIAL FIRST FLOOR PLAN - DEMOLITION
P200 PARTIAL BASEMENT PLAN - NEW WORK
P201 PARTIAL FIRST FLOOR PLAN - NEW WORK
DIVISION 21 & 22 SPECIFICATIONS
1. PROVIDE A COMPLETE RENOVATED PLUMBING AND FIRE SUPPRESSION SYSTEM AS SHOW N ON THE DRAW INGS AND AS SPECIFIED HEREIN. W ORK INCLUDES, BUT IS NOT NECESSARILY LIMITED TO THE FOLLOW ING PRINCIPAL CATEGORIES.
A. COMPLETE PLUMBING SYSTEMS CONSISTING OF MEDICAL GAS, DOMESTIC W ATER, SANITARY AND VENT SYSTEMS.
B. NEW "W ET PIPE" FIRE SUPPRESSION SYSTEM THROUGHOUT EXISTING SPACE.
C. ALTERATION W ORK IN THE EXISTING BUILDING.
D. SPACE IS EXTREMELY TIGHT. ELECTRONIC COORDINATION DRAW INGS ARE REQUIRED. COORDINATE REQUIREMENTS CLOSELY W ITH DIVISION 23.
2. W ORK SHALL BE PERFORMED BY CONTRACTORS THAT ARE FULLY CERTIFIED BY THE STATE OR AUTHORITY HAVING JURISDICTION.
3. OBTAIN AND PAY FOR ALL PERMITS, UPON COMPLETION. PROVIDE A CERTIFICATE OF APPROVAL FROM THE GOVERNING INSPECTION AUTHORITY.
4. DURING THE BIDDING PERIOD INSPECT THE SITE AND PREMISES OF THE PROPOSED W ORK. REPORT IMMEDIATELY ANY SIGNIFICANT OBSERVED DISCREPANCIES AS RELATED TO THE PLANS OR THE REQUIRED W ORK. ALL W ORK SHALL COMPLY W ITH OHIO PLUMBING CODE, OHIO BUILDING CODE,AND ALL OTHER APPLICABLE CODES, LAW S AND ORDINANCES.
5. TH IS CONTRACTOR SHALL GUARANTEE ALL W ORKMANSHIP, EQUIPMENT, AND MATERIAL ENTERING INTO THIS CONTRACT FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF ACCEPTANCE. ANY W ORK PROVEN TO BE DEFECTIVE DURING THIS PERIOD SHALL BE MADE GOOD BY THIS CONTRACTORW ITHOUT EXPENSE TO THE OW NER.
6. W HERE TRADE NAMES, BRANDS OR MANUFACTURERS ARE LISTED, ANY ONE OF THE SEVERAL NAMED ARE CONSIDERED EQUALLY ACCEPTABLE. NO UNNAMED PRODUCT OR MATERIAL SHALL BE USED UNLESS APPROVED IN W RITING BY THE ENGINEER. SUBMIT ELECTRONIC SHOP DRAW INGS ON MAJOR ITEMS OF EQUIPMENT AND MATERIALS.
A. PIPE, FITTINGS AND JOINING METHODS FOR THE VARIOUS SYSTEMS.
B. PIPE HANGERS.
C. PIPE INSULATION.
D. PLUMBING FIXTURES.
E. FIRESTOPPING.
F. SPRINKLERS, ACCESSORIES AND INSTALLATION DRAW INGS PER NFPA 13.
7. PLAN W ORK AS TO PROVIDE REASONABLE CONTINUOUS SERVICE OF EXISTING SYSTEMS. SHUTDOW N OF SYSTEMS AND W ORK UNDERTAKEN DURING SHUTDOW NS SHALL BE BID AS BEING DONE DURING NORMAL W ORKING HOURS. IF THE OW NER SHOULD REQUIRE SUCH W ORK BE PERFORMED OUTSIDE OF NORMAL W ORKING HOURS, REIMBURSEMENT SHALL BE MADE FOR PREMIUM TIME EXPENSES ONLY, W ITHOUT MARK-UP.
8. ALL PIPING PROVIDED IN THIS W ORK SHALL BE PRESSURE TESTED AS SPECIFIED BELOW .
A. DOMESTIC COLD AND HOT W ATER PIPING – HYDROSTATIC AT 125 PSI OR 1.5 TIME THE MAXIMUM SYSTEM OPERATING PRESSURE, W HICHEVER IS HIGHER, FOR 6 HOURS AT THE LOW POINT OF THE SYSTEM.
B. SOIL W ASTE AND VENT PIPING AND STORM PIPING – ROUGH TEST AND FINAL TEST IN CONFORMANCE TO THE PLUMBING CODE REQUIREMENTS.
C. FIRE SUPPRESSION PIPING – HYDROSTATIC AT 200 PSI M INIMUM, AND NOT LESS THAN 50 PSI ABOVE THE MAXIMUM SYSTEM PRESSURE, FOR A PERIOD NOT LESS THAN 2 HOURS.
9. DISINFECTION OF PIPING
A. ALL NEW DOMESTIC W ATER SYSTEMS INCLUDING ANY EXISTING DOMESTIC W ATER PIPING, TANKS AND EQUIPMENT OUT OF SERVICE FOR MORE THAN 30 DAYS SHALL BE DISINFECTED BY A COMPANY OR PERSONNEL REGULARLY ENGAGED IN THE PERFORMANCE OF TH IS SERVICE.
B. KEEP NEW SYSTEMS ISOLATED FROM THE EXISTING SYSTEMS UNTIL AFTER DISINFECTION IS COMPLETED AND PROVEN ACCEPTABLE BY BACTERIOLOGICAL TEST RESULTS. PROVIDE A SERVICE COCK AT THE POINT OF CONNECTION FOR INJECTION OF THE DISINFECTING AGENT. IF IT IS NECESSARY TO USE A POTABLE W ATER SUPPLY IN THE PERFORMANCE OF THE DISINFECTION PROCEDURES, PROVIDE TEMPORARY REDUCED PRESSURE ZONE BACK FLOW PREVENTION UNTIL DISINFECTION AND ANALYSIS RESULTS ARE COMPLETE.
C. THOROUGHLY FLUSH THE SYSTEM, AS PREVIOUSLY DESCRIBED, PRIOR TO DISINFECTION. DISINFECTION SHALL BE PERFORMED IN ACCORDANCE W ITH THE LOCAL AUTHORITIES PRESCRIBED METHOD, OR W HEN A LOCAL AUTHORITY PRESCRIBED METHOD IS NOT AVAILABLE, IN ACCORDANCE W ITH AW W A C651 OR AW W A C652 STANDARDS. D ISINFECTION SHALL BE BY MEANS OF A CHLORINE SOLUTION INJECTED INTO THE W ATER SYSTEM NEAR THE SOURCE. EACH OUTLET SHALL BE TESTED TO PROVE PRESENCE OF MINIMUM CHLORINE CONCENTRATION. DOCUMENT THAT ADEQUATE LEVELS OF CHLORINE ARE PRESENT IN ALL PARTS OF THE SYSTEM. FOLLOW ING THE APPROPRIATE RETENTION PERIOD, FLUSH OUT THE SYSTEM W ITH CLEAN W ATER UNTIL THE RESIDUAL FREE CHLORINE CONTENT IS EQUAL TO THE LEVEL OF THE INCOMING W ATER, BUT NOT GREATER THAN 1.5 PARTS PER MILLION OR UNTIL APPROVED BY THE HEALTH DEPARTMENT.
D. PERFORM A BACTERIOLOGICAL ANALYSIS OF THE POTABLE W ATER SYSTEM. ONE TEST SAMPLE SHALL BE COLLECTED FROM THE END OF THE MAIN AND ONE FROM EACH BRANCH. PROVIDE CERTIFICATION STATING THE NAME OF THE LAB PERFORMING THE TESTING, THE JOB NAME, THE DATE OF THE SAMPLE AND RESULTS OF THE TESTING.
E. DISINFECTION PROCEDURES SHALL BE W ITNESSED OR APPROVED BY THE ARCHITECT, ENGINEER OR OTHER QUALIFIED REPRESENTATIVE, W HO SHALL PRESENT THE CONTRACTOR W ITH A LETTER OR CERTIFICATE OF COMPLETION. COPIES OF THE CERTIFICATE OF COMPLETION AND BACTERIOLOGICAL ANALYSIS REPORTS SHALL BE INCLUDED IN THE OPERATIONS AND MAINTENANCE MANUALS.
F. LEGIONELLA TESTING1. PROVIDE A LEGIONELLA SAMPLING PLAN AND ANALYSIS REPORT FROM A CERTIFIED LABORATORY.
THE SAMPLING PLAN SHALL BE AS DIRECTED BY THE CERTIFIED LABORATORY, AND SHALL BE BASED ON THE PROJECT SCOPE IDENTIFIED IN THE CONSTRUCTION DOCUMENTS. THE SAMPLING PLAN SHALL IDENTIFY THE NUMBER AND LOCATION OF SAMPLES TO BE COLLECTED. W ATER AND SW AB SAMPLING SHALL BE USED, CONSISTENT W ITH THE LABORATORY’S SUBMITTED PLAN. SAMPLING SHALL BE COLLECTED W ITHIN 48 HOURS AFTER THE FLUSHING AND CHLORINE PIPING DISINFECTION PROCEDURES.
2. LEGIONELLA TESTING SHALL BE BY CULTURE ANALYSIS. ANALYSIS SHALL INCLUDE TOTAL VIABLE LEGIONELLA COUNT AND DETERMINATION AS LEGIONELLA PNEUMOPHILIA SEROGROUP 1, LEGIONELLA PNEUMOPHILIA SEROGROUP 2 - 14, OR LEGIONELLA NON-PNEUMOPHILIA SPECIES. ALL LEGIONELLA REPORTS SHALL INCLUDE INTERPRETATIONS AND RECOMMENDATIONS BASED ON SAMPLE LOCATION. INDIVIDUAL SAMPLE SITES SHALL BE ASSIGNED A RISK FOR LEGIONNAIRES DISEASE. LIM ITS OF DETECTION SHALL BE <1 CFU/ML FOR W ATER SAMPLES AND 20 CFU/SW AB FOR SW AB SAMPLES.
3. THE LABORATORY SHALL BE CERTIFIED BY THE CENTERS FOR DISEASE CONTROL AND PREVENTION (CDC) TO BE PROFIC IENT IN PERFORMING LEGIONELLA ANALYSIS BY THE ELITE (ENVIRONMENTAL LEGIONELLA ISOLATION TECHNIQUES EVALUATION) PROGRAM. THE LABORATORY SHALL BE ACCREDITED AS COMPETENT TO PERFORM MICROBIAL AND LEGIONELLA TESTING AS PROVEN BY PROFICIENCY TESTING AND THROUGH COMPLIANCE TO ISO 17025:2005 POLICIES AND REQUIREMENTS.
4. SUBMIT SAMPLING PLAN TO CONSTRUCTION MANAGER AND ENGINEER FOR REVIEW PRIOR TO IMPLEMENTATION. DISINFECTION, FLUSHING, AND LEGIONELLA TESTING AND ANALYSIS SHALL BE REPEATED UNTIL LABORATORY RESULTS DETECT NO VIABLE LEGIONELLA.
5. IF THE BUILDING IS NOT TO BE IMMEDIATELY “SUBSTANTIALLY” OCCUPIED, A FLUSHING PROCEDURE RECOMMENDED BY THE TESTING LABORATORY AND/OR A W ATER TREATMENT CONSULTANT (CERTIFIED W ATER TECHNOLOGIST) SHALL BE INITIATED. THESE FLUSHING PROCEDURES SHALL CONTINUE UNTIL BUILDING IS SUBSTANTIALLY OCCUPIED. PERIODICALLY, AS DETERMINED BY THE TESTING LABORATORY AND THE W ATER TREATMENT CONSULTANT, LEGIONELLA CULTURE SAMPLES SHALL BE OBTAINED. IF POSITIVELY IS DETECTED AT A LEVEL DEEMED AT RISK, THEN THE PIPING SHALL BE RE-FLUSHED, AND SANITIZED PER SPECIFICATION.
6. THE LEGIONELLA SAMPLING REPORT SHALL INCLUDE DESCRIPTION OF THE SAMPLING PLAN USED, CERTIFICATION STATING THE NAME OF THE LAB PERFORMING THE TESTING, THE JOB NAME, THE DATES OF THE SAMPLES AND RESULTS OF THE TESTING.
10. W ORKMANSHIP SHALL BE FIRST CLASS. THE ARCHITECT'S OR ENGINEER’S JUDGMENT SHALL PREVAIL IF THE QUALITY IS SUSPECT.
11. PROTECT MATERIALS AND EQUIPMENT AFTER DELIVERY TO THE JOB SITE. RESPECT OTHER TRADES AS RELATED TO PROTECTING THEIR W ORK AND TO AVOID CONSTRUCTION INTERFERENCES. CALL ATTENTION TO PROBLEMS RELATING TO SPACE REQUIREMENTS SO EARLY RESOLUTION MAY BE OBTAINED. RESPECT OW NER'S PROPERTY AT ALL TIMES. TEMPORARILY REMOVE, STORE AND RE-INSTALL CEILINGS W HEN REQUIRED TO PERFORM W ORK.
E. INSTALLERS SHALL BE CERTIFIED TO THE REQUIREMENTS OF THE AMERICAN SOCIETY OF SANITARY ENGINEERS (ASSE) 6010 PROFESSIONAL QUALIFICATION STANDARDS FOR MEDICAL GAS SYSTEM INSTALLERS. VERIFIERS SHALL BE CERTIFIED TO THE REQUIREMENTSOF THE AMERICAN SOCIETY OF SANITARY ENGINEERS (ASSE) 6030 PROFESSIONAL QUALIFICATION STANDARDS FOR MEDICAL GAS SYSTEM VERIFIERS.
F. TUBING FOR PRESSURIZED MEDICAL GASES SHALL BE TYPE "L", OR TYPE “K” FOR SYSTEMS W ITH W ORKING PRESSURE EXCEEDING 185 PSI, HARD-DRAW N SEAMLESS COPPER (ASTM B-819). FITTINGS SHALL BE W ROUGHT COPPER, BRASS OR BRONZE DESIGNED EXPRESSLY FORBRAZED CONNECTIONS (ANSI B16.22 OR MSS SP-73). JOINTS SHALL BE BRAZED IN COMPLIANCE W ITH ANSI / AW S A5.8. JOINTS SHALL BE MADE USING A COPPER-PHOSPHORUS BRAZING FILLER ALLOY W ITH A MELTING TEMPERATURE IN EXCESS OF 1,000 DEGREES F. (BCUP-5) W ITHOUT FLUX.ALL TUBING AND FITTINGS SHALL BE LABELED "OXY", “MED”, “OXY/MED”, “OXY/ACR” OR “ACR/MED”. TUBING AND FITTINGS SHALL BE SPECIALLY CLEANED FOR OXYGEN SERVICE IN A FACILITY EQUIPPED TO CLEAN, RINSE AND PURGE THE MATERIAL IN ACCORDANCE W ITH THE REQUIREMENTS OF NFPA 99. TUBING AND FITTINGS SHALL BE DELIVERED TO THE PROJECT SITE CLEANED AND CAPPED/BAGGED.
G. TUBING FOR MEDICAL VACUUM SHALL BE TYPE “L” HARD-DRAW N COPPER (ASTM B-88 OR B-819) OR ASTM B-280 ACR COPPER. FITTINGS SHALL BE W ROUGHT COPPER, BRASS OR BRONZE DESIGNED EXPRESSLY FOR BRAZED CONNECTIONS (ANSI B16.22 OR MSS SP-73). JOINTS SHALL BE BRAZED IN COMPLIANCE W ITH ANSI / AW S A5.8. JOINTS SHALL BE MADE USING A COPPER-PHOSPHORUS BRAZING FILLER ALLOY W ITH A MELTING TEMPERATURE IN EXCESS OF 1,000 DEGREES F. (BCUP-5 SERIES) W ITHOUT FLUX.
H. FITTINGS AT TIE-IN LOCATIONS TO EXISTING SYSTEMS SHALL BE, AT THE CONTRACTOR’S OPTION, IN SIZES 0.5 INCH THRU 2 INCHES, AXIALLY SW AGED, ELASTIC STRAIN PRELOAD FITTINGS PROVIDING METAL TO METAL SEAL HAVING PRESSURE AND TEMPERATURE RATINGS NOT LESS THAN THAT OF A BRAZED JOINT. W HEN COMPLETE, FITTINGS SHALL BE PERMANENT AND NON-SEPARABLE. FITTINGS MATERIAL SHALL BE 360 BRASS AS PER ASTM B16, FACTORY CLEANED AND SEALED FOR OXYGENSERVICE PER CGA G-4.1. FITTINGS SHALL BE INSTALLED BY FACTORY TRAINED AND QUALIFIED INSTALLERS, IN STRICT CONFORMANCE W ITH THE FITTING MANUFACTURER’S INSTALLATION REQUIREMENTS,INCLUDING MAINTAINING THE MINIMUM INSTALLATION DISTANCE FROM BRAZED JOINTS. FITTINGS SHALL BE MANUFACTURED BY LOKRING TECHNOLOGY, LLC.
I. COPPER, TUBING, VALVES AND FITTINGS SHALL BE PRE-CLEANED AND PREPARED FOR OXYGEN SERVICE BY THE MANUFACTURER AND RECEIVED SEALED ON THE JOB. CERTIFICATES OF ORIGIN AND OF PROPERPREPARATION SHALL BE MAINTAINED ON THE JOB SITE ATTESTING THE ABOVE. KEEP OPEN ENDS OF TUBE CAPPED OR PLUGGED AT ALL TIMES. DISCARD PIPING, VALVES AND FITTINGS W HICH BECOME CONTAMINATED.CLEANING OF PIPING, VALVES AND FITTINGS ON-SITE IS PROHIBITED.
J. RIGIDLY SUPPORT VALVES AND OTHER EQUIPMENT TO PREVENT STRAIN ON TUBE OR JOINTS.
K. TAKE CARE NOT TO ANNEAL COPPER TUBE W HILE BRAZING. BRAZE ONLY W HILE PURGING THE INTERIOR OF TUBE W ITH OIL FREE DRY NITROGEN NF, M INIMUM U.S.P. OR GRADE B AS SPECIFIED IN CGA G-10.1. AT THECOMPLETION OF ANY SECTION, ALL OPEN PIPE ENDS SHALL BE CAPPED USING AN EXTERNAL CAP. AFTER INSTALLATION OF THE PIPING, BUT BEFORE INSTALLATION OF THE OUTLET VALVES, BLOW LINES CLEAR USINGNITROGEN NF.
L. DO NOT BEND TUBING. USE FITTINGS.
M. APPLY PIPE LABELING DURING INSTALLATION PROCESS AND NOT AFTER INSTALLATION IS COMPLETED. LABEL PIPING W ITH NAME OF GAS SERVICE, IDENTIFICATION COLOR AND DIRECTION OF FLOW . W HERE NON-STANDARD PRESSURES ARE PIPED, LABEL FOR PRESSURE. LABELS SHALL BE PLACED AT LEAST ONCE EVERY 20 FEET OF LINEAR RUN OR ONCE IN EACH STORY (W HICHEVER IS MORE FREQUENT). A LABEL SHALL ADDITIONALLY BE PLACED IMMEDIATELY ON EACH SIDE OF EACH W ALL OR FLOOR PENETRATION. PIPE LABEL COLORS IN ACCORDANCE W ITH NFPA 99.
N. PRIOR TO DECLARING THE SYSTEM READY FOR SYSTEM VERIFICATION, PERFORM AND DOCUMENT ALL INSTALLER TESTS AS REQUIRED BY NFPA 99. PRESSURE TESTS SHALL BE W ITNESSED OR MONITORED BYA RECORDER. FURNISH A W RITTEN RECORD OF EACH PIPING SYSTEM TEST INDICATING DATE, SYSTEM, PRESSURE, DURATION AND RESULTS OF TESTS. SIGNED COPIES OF TEST REPORTS SHALL BE DISTRIBUTEDTO THE ARCHITECT OR ENGINEER, THE AUTHORITY HAVING JURISDICTION, THE VERIFIER AND INCLUDED IN THE O&M MANUALS.
O. INITIAL PRESSURE TEST, CROSS CONNECTION TEST, PIPING PURGE TEST AND STANDING PRESSURE TEST SHALL BE DONE PRIOR TO CLOSING OF W ALLS. TESTING OF EACH SYSTEM SHALL BE DONE ONE AT A TIME, NOTSIMULTANEOUSLY.
P. ALL PIPING SHALL BE INITIALLY TESTED AT 1.50 TIMES THE MAXIMUM W ORKING PRESSURE BUT NOT LESS THAN 150 PSI, EXCEPT NITROGEN W HICH SHALL BE TESTED AT 250 PSI. EACH JOINT SHALL BE INSPECTED AND REPAIRED IF NECESSARY. THE COMPLETELY ASSEMBLED SYSTEM SHALL BE SUBJECTED TO A 24-HOUR STANDING PRESSURE TEST AT 20 PERCENT ABOVE THE NORMAL OPERATING LINE PRESSURE. VACUUMSYSTEMS SHALL BE SUBJECTED TO A 24-HOUR STANDING PRESSURE TEST AT 50 PSIG W ITH NO MORE THAN A 5 PSIG LOSS. THE TEST GAS SHALL BE OIL-FREE, DRY AIR OR NITROGEN.
Q. AFTER INITIAL LEAKAGE TESTING IS COMPLETED, ALLOW PIPING TO REMAIN PRESSURIZED W ITH TESTING GAS UNTIL TESTING AGENCY PERFORMS FINAL TESTS.
R. VERIFICATION OF MEDICAL GAS SYSTEMS
i.) THE MEDICAL AIR SYSTEM SHALL BE TESTED BY AN APPROVED TESTING AGENCY AFTER INSTALLATION OF THE SYSTEM HAS BEEN COMPLETED. THE REPRESENTATIVE SHALL DETERMINE THAT ALL TESTING, VERIFICATION AND REPORTING IS IN COMPLIANCE W ITH ASSE STANDARD #6030.
28. ALL NEW SYSTEMS SHALL BE SEISMICALLY RESTRAINED IN ACCORDANCE W ITH THE OHIO BUILDING CODE.
PARAMETERS FOR SEISMIC DESIGN ARE:
SEISMIC OCCUPANCY CATEGORY IV
SITE CLASS D
DESIGN SPECTRAL RESPONSE ACCELERATION AT SHORT PERIOD (0.2 SECOND), SDS OF 0.165G.
SEISMIC DESIGN CATEGORY C
ALL NEW SYSTEMS AND ASSOCIATED EQUIPMENT, PIPING AND APPURTENANCES SHALL BE DESIGNATED AS HAVING A COMPONENT IMPORTANCE FACTOR, IP, OF 1.5.
SEISMIC RESTRAINTS SHALL BE ENGINEERED, SEALED, AND FURNISHED BY MASON INDUSTRIES, KINETICS OR AMBER/ BOOTH.
12. CUT AND PATCH TO INSTALL W ORK OR PAY OTHERS TO PERFORM SUCH W ORK. W ORKMANSHIP SHALL BE FIRST CLASS. THE ARCHITECT’S OR ENGINEER’S JUDGMENT SHALL PREVAIL IF THE QUALITY IS SUSPECT.
13. IN ALTERATION AND REMODELING W ORK, PERFORM ALL REMOVAL AND RELOCATION W ORK KINDRED TO THE PLUMBING W ORK. LEAVE ALL EXISTING SYSTEMS CONTINUOUS AND FUNCTIONAL. REMOVE EXTRANEOUS PIPING AND EQUIPMENT. NO REMOVED MATERIAL SHALL BE REUSED UNLESS EXPRESSLY SHOW N. W HERE NECESSARY TO DISRUPT SERVICES FOR SHORT PERIODS OF TIME, COORDINATE AND SCHEDULE OUTAGES W ITH THE OW NER.
14. PROVIDE CEILING AND W ALL ACCESS PANELS W HERE INDICATED ON THE DRAW INGS, OR W HERE REQUIRED FOR ACCESS TO CONCEALED VALVES, TRAPS, DEVICES OR SERVICEABLE EQUIPMENT. ACCESS PANELS SHALL BE MINIMUM 18” X 18”, OR LARGER IF REQUIRED, AND SHALL BE COMPATIBLE W ITH THE MATERIALS IN W HICH THEY ARE INSTALLED. ACCESS PANELS IN FIRE RATED BUILDING ELEMENTS SHALL BE LABELED IN COMPLIANCE W ITH THE RATING OF THE BUILD ING ELEMENT.
15. EACH CONTRACTOR SHALL MAINTAIN A SEPARATE SET OF AS-BUILT PRINTS OF THE CONTRACT DOCUMENTS AND SHALL SHOW ANY SIGNIFICANT CHANGES OR VARIATIONS W HICH ARE MADE DURING CONSTRUCTION. UPON COMPLETION OF THE W ORK, THESE DRAW INGS SHALL BE TURNED OVER TO THE ARCHITECT.
16. PAINT FERROUS METAL W HICH IS NOT FACTORY OR SHOP PAINTED OR GALVANIZED AND W HICH REMAINS EXPOSED TO VIEW IN FINISHED AREAS OF THE BUILDING. FERROUS METAL INSTALLED OUTSIDE THE BUILDING W HICH IS NOT FACTORY OR SHOP PAINTED OR GALVANIZED SHALL BE GIVEN A PRIME COAT OF PAINT.
17. MARK ALL PIPING SYSTEMS AND TAG ALL VALVES. ANY EXISTING PIPING ENCOUNTERED SHALL ALSO BE MARKED. PIPE MARKERS SHALL BE 1” HIGH LETTERS W ITH COLOR BAND AND ARROW . MARKERS SHALL BE AT LEAST ONE IN EACH ROOM, BUT NO MORE THAN 20 FT. INTERVALS. COLOR BAND SHALL MATCH EXISTING OR AS DICTATED BY OW NER. TURN OVER VALVE TAG SCHEDULE TO ARCHITECT.
18. FIRESTOPPING ASSEMBLIES SHALL BE PROVIDED AT PENETRATIONS OF PIPING THRU FIRE RATED FLOORS, FIRE RATED FLOOR-CEILING AND ROOF CEILING ASSEMBLIES, FIRE & SMOKE RATED W ALLS AND PARTITIONS AND FIRE & SMOKE RATED SHAFT W ALLS AND PARTITIONS. IN ADDITION, FIRESTOPPING ASSEMBLIES SHALL BE PROVIDED AT PENETRATIONS THRU 0-HOUR RATED FLOORS. REFER TO THE ARCHITECTURAL DRAW INGS FOR FIRE AND SMOKE RATED BUILDING ELEMENTS AND PLUMBING/FIRE SUPPRESSION DRAW INGS FOR PIPE LAYOUTS. FIRESTOPPING SHALL BE AS MANUFACTURED BY SPECIFIED TECHNOLOGIES, INC.
19. ALL PIPING SHALL BE INSTALLED PER ACCEPTED INDUSTRY STANDARDS AND/OR PER MANUFACTURER’S RECOMMENDATIONS. ALL INTERIOR ABOVE GRADE PIPING SHALL BE SUPPORTED BY ATTACHMENT TO BUILDING STRUCTURAL ELEMENTS. DO NOT SUPPORT PIPING FROM NON-STRUCTURAL BUILDING ELEMENTS, DUCTW ORK, OTHER PIPING, ETC. HANGER ROD SIZES AND HANGER/SUPPORT SPACING SHALL BE PER THE FOLLOW ING SCHEDULES. HANGERS FOR PLUMBING PIPING SHALL BE LIGHT DUTY CLEVIS TYPE, COPPER CLAD OR PLASTIC COATED FOR UNINSULATED COPPER PIPING, W ITH LOCK NUT AT EACH HANGER. FIRE SUPPRESSION HANGER AND SUPPORT REQUIREMENTS SHALL BE PER FM GLOBAL AND NFPA STANDARDS. PROVIDE A LOCK NUT AT HANGER ROD ATTACHMENT TO STRUCTURE.
PIPE SIZE MINIMUM HANGER ROD DIAMETER2” AND SMALLER 0.375”2.5" TO 3" 0.5"4" TO 5" 0.625"
PIPE MATERIAL/SIZE MAXIMUM HANGER/SUPPORT SPACINGVERTICAL:COPPER BASE AND 10 FT.CAST IRON BASE AND EACH FLOOR LEVELSTEEL BASE AND 15 FT. HORIZONTAL:COPPER / <=1.25” 6 FT.CAST IRON 10 FT. AND EACH FITTING/JOINTSTEEL / <=1.5 7 FT.STEEL / 2" - 6" 10 FT
20. INSULATE ALL NEW ABOVE GROUND DOMESTIC W ITH FIBERGLASS PIPE INSULATION IN COMPLIANCE W ITH ASHRAE 90.1. FIBERGLASS INSULATION SHALL BE FACTORY MOLDED TUBULAR FIBERGLASS W ITH ALL SERVICE JACKET, INTEGRAL VAPOR BARRIER AND FACTORY ADHESIVE OVERLAPPING JOINTS. PROVIDE FACTORY MOLDED PVC COVERS AND INSULATION FOR FITTINGS, VALVES AND DEVICES. ON COLD SERVICE PIPING, SEAL ALL JOINTS AND TERMINATIONS TO MAINTAIN THE VAPOR BARRIER. COMPOSITE INSULATING SYSTEMS SHALL NOT EXCEED A MAXIMUM FLAME SPREAD OF 25 AND SMOKE DEVELOPMENT OF 50 AS ESTABLISHED BY ASTM E84 TEST METHODS. FIBERGLASS INSULATION MANUFACTURERS - OW ENS-CORNING, JOHNS MANVILLE, MASON OR KNAUFF.
1.25” ANDPIPE SYSTEM SMALLER 1.5” TO 3”DOM. COLD & NON-POTABLE W ATER 0.5” 1.0”DOM. HOT W ATER 1.0” 1.5”DOM. HOT RETURN 1.0” 1.5”
21. FIRE SUPPRESSION PIPING SHALL BE SCHEDULE 40 BLACK STEEL, ASTM A-53, TYPE E OR F OR ASTM A135. FITTING AND JOINTS SHALL BE MALLEABLE OR CAST IRON SCREW ED TYPE FOR PIPING 2” AND SMALLER, AND MECHANICALLY ROLLED GROOVE TYPE FOR SIZES 2” AND LARGER. FITTINGS FOR MECHANICALLY ROLLED GROOVE SYSTEMS SHALL BE MALLEABLE OR DUCTILE IRON BODY W ITH N ITRILE OR EPDM GASKETS, EQUAL TO VICTAULIC “FIRELOCK” STYLE 005 AND 009.
22. ALL MATERIALS AND DEVICES, AS APPROPRIATE, SHALL BE UL LISTED AND/OR FM GLOBAL APPROVED, AND ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. THE FIRE SUPPRESSION SYSTEM(S) SHALL CONFORM TO NFPA STANDARDS, THE GOVERNING BUILD ING CODE, AND OTHER REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION AND THE OW NER’S INSURER.
23. INTERIOR DOMESTIC W ATER PIPING SHALL BE TYPE “L” SEAMLESS HARD DRAW N COPPER TUBING ASTM B88 W ITH W ROUGHT COPPER OR CAST BRONZE FITTINGS ASME B16.22 AND SOLDERED JOINTS. SOLDER SHALL BE LEAD-FREE TIN ALLOY, 95-5 TIN-ANTIMONY OR SILVER BEARING TIN. PIPE NIPPLES EXTENDING OUT OF THE W ALL TO SERVE FIXTURES SHALL BE CHROME PLATED BRASS W ITH SCREW ED ENDS. SHUTOFF VALVES SHALL BE TW O-PIECE, BRONZE BODY, BALL TYPE, 150 W .S.P. ASTM B584, EQUAL TO NIBCO T-585-66-LF. PROVIDE FULL OPEN VALVES AT LOCATIONS REQUIRED BY THE GOVERNING PLUMBING CODE.
24. INTERIOR ABOVE GRADE SOIL, W ASTE AND VENT PIPING SHALL BE CENTRIFUGALLY CAST COATED CAST IRON W ITH HUBLESS ENDS, ASTM A-888 AND CISPI 301. FITTINGS SHALL BE DRAINAGE TYPE. JOINTS SHALL CONSIST OF A NEOPRENE GASKET, ASTM C564, STAINLESS STEEL SHIELD AND STAINLESS STEEL BAND. FLOOR DRAIN TRAPS SHALL BE THE SAME MATERIAL AS THE CONNECTING PIPING. PROVIDE CLEANOUTS W HERE SHOW N ON THE DRAW INGS AND W HERE REQUIRED BY THE GOVERNING PLUMBING CODE.
25. PROVIDE PLUMBING FIXTURES, AS INDICATED ON THE DRAW INGS, INSTALLED IN PLACE COMPLETE W ITH SUPPORTS, CARRIERS AND SUPPLY AND W ASTE TRIM. SUPPLIES TO EACH FIXTURE SHALL BE INDIVIDUALLY VALVED. VALVES, SUPPLIES AND ESCUTCHEONS SHALL BE FURNISHED W ITH FIXTURE SUPPLY TRIM. ALL W ASTE AND SUPPLY TRIM SHALL BE CHROME PLATED BRASS. FIXTURES SHALL BE W HITE UNLESS OTHERW ISE SPECIFIED. SEAL JOINTS AROUND EACH FIXTURE AT THE W ALL, FLOOR AND ANY ADJACENT CONSTRUCTION. JOINT SEALANT SHALL BE ONE PART, M ILDEW RESISTANT SILICONE, ASTM C-920, TYPE S, GRADE NS, CLASS 25 W ITH FUNGICIDE, EQUAL TO PECORA 898. AFTER INSTALLATION OF THE FIXTURES IS COMPLETED, ALL CONNECTING PIPES SHALL BE FLUSHED OUT THROUGH THE FIXTURES TO ELIMINATE SCALE, AND ALL VALVES SHALL BE PROPERLY ADJUSTED AND FIXTURES LEFT COMPLETE AND READY FOR USE. ALL FIXTURES SHALL BE CLEANED, IMMEDIATELY PRIOR TO ACCEPTANCE BY THE OW NER.
26. ALL PLUMBING FIXTURES, EQUIPMENT AND TRIM SHALL MEET THE DIMENSIONAL AND PERFORMANCE REQUIREMENTS OF ANSI, ARI, ASME, AND ASSE AND/OR CSA STANDARDS LISTED IN THE CURRENT JURISDICTIONAL PLUMBING CODE. ALL FAUCETS AND FITTINGS SUPPLYING DRINKING W ATER FOR HUMAN CONSUMPTION SHALL CONFORM TO THE REQUIREMENTS OF NSF 61, SECTION 9.
27. MEDICAL GAS AND VACUUM SYSTEMS SHALL BE PROVIDED AS SHOW N ON THE DRAW INGS, AND AS SPECIFIED.
A. MATERIALS AND INSTALLATION SHALL CONFORM TO REQUIREMENTS OF NFPA 99, COMPRESSED GAS ASSOCIATION P-2 CHARACTERISTICSAND SAFE HANDLING OF MEDICAL GASES AND OHIO BUILDING CODE.
B. A SEPARATE PIPING PERMIT SHALL BE OBTAINED. SPECIAL NOTE SHALL BE TAKEN TO COMPLY W ITH “MEDICAL GAS INSPECTION PROCEDURE FOR PIPING SYSTEMS” ISSUED BY THE STATE OF OHIO.
C. BRAZERS SHALL BE QUALIFIED IN ACCORDANCE W ITH THE REQUIREMENTS OF ASTM BOILER AND PRESSURE VESSEL CODE, SECTION IX OR AW S B2.2 STANDARD FOR BRAZING AND PERFORMANCE QUALIFICATION, AS MODIFIED BY NFPA 99.
D. RETAIN A QUALIFIED THIRD PARTY VERIFIER ACCEPTABLE TO THE ENGINEER AND OW NER TO PERFORM AND ATTEST TO FINAL VERIFICATION OF THE SYSTEMS. MAKE CORRECTIONS AS REQUIRED, INCLUDING ADDITIONAL TESTING IF NECESSARY TO ATTAIN FULL AND UNQUALIFIED CERTIFICATION.
A. ALL PIPING IS ABOVE THE CEILING (AT THE UNDERSIDE OF STRUCTURE IN EXPOSED STRUCTURE AREAS), UNLESS OTHERW ISE NOTED.
B. REFER TO SCHEDULES, DETAILS AND DIAGRAMS FOR PIPING, PIPE SIZES ANDPIPELINE DEVICES NOT INDICATED ON THE FLOOR PLAN.
C. ABOVE CEILING UTILITY SPACE IS LIM ITED. COORDINATION W ITH ALL TRADESIS CRITICAL, PR IOR TO INSTALLATION OF ANY W ORK.
D. LOCATIONS AND SIZES OF EXISTING PIPING HAVE BEEN DETERMINED FROM AREVIEW OF EXISTING DRAW INGS AND/OR SITE INSPECTION, W HERE POSSIBLE.FIELD VERIFICATION OF EXACT LOCATIONS, ELEVATIONS, INVERTS, SIZES,DIRECTION OF FLOW , ETC. SHALL BE REQUIRED PRIOR TO BEGINNINGNEW W ORK.
E. ALL PIPING SHALL BE REMOVED BACK TO ACTIVE MAINS AND CAPPED, ORREMOVED BACK TO POINTS OF CONNECTION IN NEW W ORK. INACCESSIBLEPIPING, W HERE SO NOTED, TO BE ABANDONED SHALL BE DISCONNECTEDFROM ACTIVE SYSTEMS AND CAPPED OR PLUGGED IN CONCEALED LOCATIONS.
F. ALL ABANDONED PIPING SHALL BE CAPPED AT INLET AND OUTLET. DOMESTICW ATER PIPING SHALL BE CAPPED W ITHIN TW O (2) P IPE DIAMETERS OF ACTIVEBRANCH/ MAIN. NO DEAD LEGS W ILL BE PERMITTED.
G. NEW CONNECTIONS TO EXISTING PIPING SHALL BE W ITH THE SAME SIZE ASTHE EXISTING PIPING, UNLESS OTHERW ISE NOTED.
H. ALL REMOVED MATERIAL AND EQUIPMENT, SO DESIGNATED BY THE OW NER,SHALL BE TURNED OVER AND PLACED W HERE DIRECTED. ALL MATERIALAND EQUIPMENT, W HICH THE OW NER DOES NOT W ISH TO RETAIN, SHALLBECOME THE PROPERTY OF THE CONTRACTOR RESPONSIBLE FOR THEREMOVAL.
I. REFER TO THE ARCHITECTURAL PLANS FOR PROJECT PHASING REQUIREMENTS.
J. ANNULAR SPACE OF PIPE, CONDUIT AND OTHER SIMILAR PENETRATIONS OFFIRE RATED ASSEMBLIES SHALL BE FIRESTOPPED. IN ADDITION,PENETRATIONS THRU RATED FLOORS SHALL ALSO BE FIRESTOPPED TORETARD PASSAGE OF FIRE AND SMOKE. REFER TO SPECIFICATIONS. REFER TO ARCHITECTURAL DRAW ING(S) FOR CONSTRUCTION, LAYOUT AND FIRE RATINGS OF FLOORS, W ALLS, PARTITIONS AND OTHER BUILDING ELEMENTS. REFER TO ARCHITECTURAL DRAW INGS FOR PENETRATION DETAILS.
GENERAL NOTES
A. REFER TO ARCHITECTURAL DRAW INGS FOR REFLECTED CEILING PLANS ANDGENERAL TRADES CONSTRUCTION INFORMATION. COORDINATE SPRINKLERLOCATIONS W ITH CEILING DEVICES (LIGHTING, GRILLES, ETC.) OBTAINARCHITECTS APPROVAL OF SPRINKLER LAYOUT PRIOR TO INSTALLATION.FINAL FINISHED APPEARANCE OF W ORK MUST BE APPROVED BY THEARCHITECT.
B. CONTRACTOR SHALL MAKE REQUIRED FLOW TESTS, LAY OUT SYSTEMS, OBTAINAPPROVALS FROM THE AUTHORITY HAVING JURISDICTION AND THE OW NER’SINSURER PRIOR TO BEGINNING ANY FABRICATION OR INSTALLATION W ORK.
C. FIRE SUPPRESSION SPRINKLER SYSTEMS. REFER TO DRAW INGS ANDSPECIFICATIONS FOR COMPLETE SCOPE OF W ORK.
1. RENOVATION AREA(S) TO BE TOTALLY SPRINKLERED. EXISTING SPRINKLERSYSTEMS TO BE MODIFIED TO CONFORM TO THE NEW LAYOUT. NEWSPRINKLERS ARE TO BE INTEGRATED INTO THE EXISTING SPRINKLERSYSTEM. ALL EXISTING SPRINKLERS, REMOVED OR DISTURBED INRENOVATION AREAS, SHALL BE DISPOSED OF AND REPLACED W ITH NEWSPRINKLERS, AS INDICATED ON THE DRAW INGS.
D. BASIS FOR DESIGN OF FIRE SUPPRESSION SYSTEM(S) TO BE:
1. LIGHT HAZARD 1500 SQUARE FEET, 0.10 GPM/ SQ.FT., 225 SQUARE FEETMAXIMUM PER SPRINKLER. 100 GPM HOSE STREAM ALLOW ANCE.
2. ORDINARY HAZARD, (GROUP 1) 1500 SQUARE FEET, 0.15 GPM/ SQ. FT.,130 SQUARE FEET MAXIMUM PER SPRINKLER. 250 GPM HOSE STREAMALLOW ANCE.
FIRE SUPPRESSION DESIGN NOTESE. AREA OF OPERATION REDUCTIONS AND INCREASES SHALL BE CALCULATED
PER NFPA STANDARDS. VERIFY DENSITIES W ITH GOVERNING AUTHORITIESAND OW NER’S INSURER BEFORE PROCEEDING W ITH DESIGN OF SYSTEM(S).IF GOVERNING AUTHORITIES OR OW NER’S INSURER REQUIREMENTS ARE MORESTRINGENT THOSE REQUIREMENTS SHALL PREVAIL. ALL AREAS ARE TO BELIGHT HAZARD CLASSIFICATION, UNLESS OTHERW ISE INDICATED ON THE PLANSOR REQUIRED BY THE GOVERNING AUTHORITY.
F. PROVIDE THE FOLLOW ING SPRINKLER TYPES, UNLESS OTHERW ISE NOTED ONTHE DRAW INGS. PENDENT TYPE SPRINKLERS SHALL BE LOCATED IN THECENTER OF SQUARE PADS AND AT THE CENTER OR AT QUARTERPOINTS OF THELONG AXIS OF RECTANGULAR PADS.
1. SPRINKLERS IN AREAS W ITH CEILINGS SHALL BE CONCEALED TW O PIECEADJUSTABLE PENDENT QUICK RESPONSE TYPE W ITH W HITE FINISH COVERPLATE. PROVIDE GASKETED COVERPLATE INSIDE IV ROOM, ANTI ROOM, CHEMO ROOM & HD NON-STERILE ROOM
2. SPRINKLERS IN EXPOSED AREAS SHALL BE QUICK RESPONSE BRASSUPRIGHT TYPE.
G. EXERCISE SPECIAL CARE TO COORDINATE PIPING AND EQUIPMENT LOCATIONSW ITH ALL OTHER TRADES.
H. ALL NEW W ORK SHALL BE COMPLIANT W ITH RULES AND REGULATIONS OF NFPA-13OR THE GOVERNING AUTHORITY, IF MORE STRINGENT.
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
5/2
01
9 7
:03
:50
AM
C:\
BIM
\Mod
el\20
19
-05
07
8-M
EP
-Ce
ntr
al_
WS
McC
am
ey.r
vt
2019-05078
ABN
W SM
July 24, 2019
P002
SCHEDULES ANDSPECIFICATIONS
1 2019.07.24 ADDENDUM 1
NOTES:1. INSTALL FLUSH VALVE HANDLE ON WIDE SIDE OF STALL PER ADA GUIDELINES.2. PROVIDE STEEL FOOT SUPPORT CARRIER.3. PROVIDE ADA INSULATION KIT ON EXPOSED TRAPS ANDSUPPLIES...
4. COORDINATE INSTALLATION OF SINK AND ALL ACCESSORIES WITH PHARMACY CONTRACTOR.5. SCRUB SINK INCLUDING FAUCET AND WASTE TRIM FURNISHED BY PHARMACY CONTRACTOR. PC TO PROVIDE SUPPLYSTOPS,...
6. INSTALL EYEWASH/DRENCH HOSE ON SINK DECK BESIDE FAUCET. PC TO PROVIDE ASSE 1071 THERMOSTATIC MIXING VALVE INSIDE SINK ENCLOSURE FOR EYEWASH DRENCHHOSE. EXTEND 0.5" TEPID WATER TO EYEWASH/DRENCH HOSE....
7. EXTEND DCW AND DHW PIPING FROM SINK SUPPLIES TOSERVE EYEWASH. PROVIDE BALL AND CHECK VALVES ON SUPPLIESTO THERMOSTATIC MIXING VALVE.
ADA HANDICAP ACCESSIBLE FS FLOOR SET FT FLUSH TANK FV FLUSH VALVE GN GOOSENECK HS HAND SHOWER QD QUICK DISCONNECT
SB SINGLE BOWLSST STAINLESS STEELVB VACUUM BREAKERVR VANDAL RESISTANTWB WRIST BLADEWH WALL HUNG
SCHEDULE ABBREVIATIONS: GENERAL NOTE:1. SUPPLY PIPE SIZES IN THIS SCHEDULE ARE FIXTURE OR SUPPLY STOP CONNECTION SIZES. DOMESTIC COLD AND HOT WATER SUPPLY PIPE SIZES SERVING FIXTURES SHALL BE, AT AMINIMUM, THE SIZES LISTED UNLESS NOTED OTHERWISE OR LABELED ON THE FLOOR PLANS. DOMESTIC COLD WATER SUPPLY PIPE SIZES SERVING FLUSH VALVES SHALL BE AT MINIMUM ONE PIPE SIZE LARGER THAN THE INDICATED CONNECTION SIZE, OR SIZED AS SHOWN ON THE FLOOR PLANS. PIPING AT THE FLUSH VALVE CONNECTION OF A SIZE EQUAL TO THE CONNECTIONSIZE SHALL BE LIMITED TO A MAXIMUM 2 FEET IN DEVELOPED LENGTH AND INCLUDE A MAXIMUM OF ONE 90 DEGREE ELBOW FITTING. FULL SIZE MANIFOLDS, WHERE INDICATED ON THE FLOOR...
A. AMERICAN STANDARD (KOHLER, CRANE, ZURN, TOTO) _
B. SLOAN (DELANY, ZURN) _
C. BEMIS (BENEKE, CHURCH, OLSONITE) _
D. SMITH (WADE, ZURN, JOSAM, WATTS) _
E. CHICAGO (TOTO, T&S BRASS, ZURN) _
F. GUY GRAY (OATEY, PLASTIC ODDITIES) _
G. McGUIRE (EBC, DEARBORN BRASS) _
H. ELKAY (FURNISHED BY OTHERS) _
J. ELKAY (JUST WITH LUG AND SCREW) _
K. GUARDIAN (FURNISHED BY OTHERS) _
L. LEONARD (POWERS, SYMMONS) _
M. AQUARIUS (AQUA-BATH, KOHLER, CRANE) _
N. IN-SINK ERATOR (OR APPROVED EQUAL) _
_
_
_
CATALOG NUMBERS INDICATED ARE THOSE OF THE FIRST NAMED MANUFACTURER IN EACH CATEGORY LISTED BELOW - ADDITIONAL MANUFACTURERS ARE LISTED IN PARENTHESIS
PLUMBING FIXTURES
MARK DESCRIPTION MO
UN
TIN
G H
EIG
HT
FLOW CONTROL SUPPLY WASTE & VENT FIXTURE SUPPLY TRIM SUPPLY / STOP WASTE TRIM TRAP / FIX. DR. MISC.
SE
E N
OT
E
GP
M
GP
F
MA
NU
AL
ME
TE
RIN
G
SENSOR
CO
LD
WA
TE
R
HO
T W
AT
ER
TE
MP
ER
ED
NA
T.
GA
S
FIX
. O
UT
LE
T
TR
AP
FIX
. D
RA
IN
WA
ST
E-M
IN.
VE
NT
-MIN
.
MF
R.
CAT. NO. MF
R.
CAT. NO. MF
R.
CAT. NO. MF
R.
CAT. NO. MF
R.
CAT. NO. MF
R.
CAT. NO. EL
EC
TR
IC
BA
TT
ER
Y
A1 WATER CLOSET/ FS/ FV/ ADA 16.5"TORIM
1.6 ● 1" 3" INT 3" 3" 2" A 3043.001 B 111-1.6-YO-SG
B UNIT A UNIT A INTEGRAL C 1655SSCT 1
B1 LAVATORY/ WH/ GN/ WB/ ADA 34" TORIM
1.5 ● 0.5" 0.5" 1.25"
1.5" 1.5" 1.5" 1.5" A 0356.015 E 786-GN2FCXKABCP
G LFBV2165 G 155WC G 8912 2, 3
D1 SCRUB SINK/ SST/ FURNISHED BY PHARMACYCONTRACTOR
30" TORIM
1.5 ● 0.5" 0.5" 1.5" 1.5" 1.5" 1.5" 1.5" H EWSF13026 H LKB721C G LFBV2165 H LK18B G 8912 2, 4, 5
E1 EYEWASH/DRENCH HOSE/ FURNISHED BYPHARMACY CONTRACTOR
- ● 0.5" K G5022 K UNIT - BALLVALVES
K G3600 6, 7
F1 SINK/ SST/ DROP-IN/ GN/ WB/ ADA/ 6" DEEP - 1.5 ● 0.5" 0.5" 1.5" 1.5" 1.5" 1.5" 1.5" J LRAD191860 E 786-GN8FCXKABCP
G LFBV2165 J LK18B G 8912
SMOKE ZONE
5" SS FROM ABOVE
4" SS FROM ABOVE
SS
SS
SK
SK
SS
SK
VR SK
VR
4" -
SA
N
4" - SAN
4" -
SA
N
2" -
SA
N
4" -
SA
N
5" -
SA
N2"
-S
AN
1
1 1
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
5/2
01
9 7
:03
:54
AM
C:\
BIM
\Mod
el\20
19
-05
07
8-M
EP
-Ce
ntr
al_
WS
McC
am
ey.r
vt
2019-05078
ABN
W SM
July 24, 2019
P100
PARTIAL BASEMENTPLAN - DEMOLITION
1 2019.07.24 ADDENDUM 1
SCALE: 1/4" = 1'-0"
PARTIAL BASEMENT PLAN - DEMOLITION1
NOTES
1 DISCONNECT AND REMOVE EXISTING SANITARY PIPING FROMDEMOLISHED FIXTURES ABOVE BACK TO ACTIVE MAIN AND CAP OR TOPOINT OF RECONNECTION.
1314
LOCK.
38
PTD
SD
1SK
5
5
4
1" - MA
1" - MV
1" -
MA
1" -
MV
2
2
5
3" - F
3" -
F
3" -
F
1.5" - O23" - DCW
2" - DHW0.75" - DHW R
1" - MV1" - MA
3" - DCW2" - DHW
0.75" - DHW R
1" - MV1" - MA
1.5" - O2
4" - DCW3" - DHW1" - MV1" - MA
1.5" - O21.25" - DHW R
4" - DCW4" - DHW
1.25" - DHW R
1" - MA
1.25" - MV
1" - DHW R3" - DHW
3" - DCW1.25" - O2
1" - MV1" - MA
6
4
6
1" -
DH
W
1" -
DC
W
0.75
" -
G
0.75
" -
MA
0.75
" -
DH
W
0.75
" -
DC
W
3
3
4
1LAV1W C
1.25" - G
1.25" - G
7
4" SS DN 2" V UP
4" SS DN
W C
LAV
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
5/2
01
9 7
:04
:00
AM
C:\
BIM
\Mod
el\20
19
-05
07
8-M
EP
-Ce
ntr
al_
WS
McC
am
ey.r
vt
2019-05078
ABN
W SM
July 24, 2019
P101
PARTIAL FIRST FLOORPLAN - DEMOLITION
1 2019.07.24 ADDENDUM 1
SCALE: 1/4" = 1'-0"
PARTIAL FIRST FLOOR PLAN - DEMOLITION1
NOTES
4 DISCONNECT AND REMOVE EXISTING MEDICAL AIR, VACUUM AND/ORGAS PIPING INCLUDING ALL HANGERS AND SUPPORTS BACK TOACTIVE BRANCH/MAIN AND CAP.
5 REMOVE EXISTING DOMESTIC WATER, SANITARY AND VENT PIPINGBACK TO ACTIVE BRANCH/MAIN AND CAP.
6 DISCONNECT, REMOVE AND REROUTE EXISTING FIRE MAIN PIPINGINCLUDING ALL HANGERS AND SUPPORTS. COORDINATE NEWROUTING CLOSELY WITH ALL TRADES TO MAXIMIZE CEILING HEIGHT.
7 DISCONNECT, REMOVE AND REROUTE EXISTING SANITARY PIPINGINCLUDING ALL HANGERS AND SUPPORTS. COORDINATE NEWROUTING CLOSELY WITH HC.
NOTES
1 DISCONNECT AND REMOVE EXISTING PLUMBING FIXTURE INCLUDINGALL ACCESSORIES (TYPE AS INDICATED). REMOVE EXISTINGDOMESTIC WATER PIPING BACK TO WITHIN TWO (2) PIPE DIAMETERSOF ACTIVE BRANCH/MAIN AND CAP. REMOVE SANITARY PIPING TOBEYOND FINISHED WALL AND CAP. NO PIPE STUBS SHALL REMAINVISIBLE IN FINISHED SPACE.
2 REMOVE ABANDONED SANITARY AND/OR VENT PIPING BACK TOACTIVE BRANCH/MAIN AND CAP OR TO POINT OF RECONNECTION.REFER TO NEW WORK PLAN.
3 REMOVE ALL ABANDONED DOMESTIC WATER PIPING BACK TO WITHINTWO (2) PIPE DIAMETERS OF ACTIVE BRANCH/MAIN AND CAP OR TOPOINT OF RECONNECTION. REFER TO NEW WORK PLAN.
SMOKE ZONE
F1
D1
B1
A1
4" -
SA
N
4" - SAN
4" -
SA
N
2" -
SA
N
4" -
SA
N
5" -
SA
N
5" SS FROM ABOVE
4" SS FROM ABOVE
NEW CAP
NEW CAP
CO
VRVR
3" -
SA
N
1.5" - SAN
3" -
SA
N
FD1
D1
FD1
NEW CAP
2" -V
3" -SAN
4" -SAN
4" - SAN2" - SAN
4" - SAN
1.5"
1.5"
2"2"
3"
1.5"
4" -SAN
1.5"2" -V
F1
3" -SAN
1.5"
2"
2" -V
CO
3"
A1B1
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
5/2
01
9 7
:04
:06
AM
C:\
BIM
\Mod
el\20
19
-05
07
8-M
EP
-Ce
ntr
al_
WS
McC
am
ey.r
vt
2019-05078
ABN
W SM
July 24, 2019
P200
PARTIAL BASEMENTPLAN - NEW WORK
1 2019.07.24 ADDENDUM 1
SCALE: 1/4" = 1'-0"
PARTIAL BASEMENT PLAN - NEW WORK1
SCALE: NONE
SANITARY WASTE AND VENT DIAGRAM - ANTI ROOM & MECH ROOM2
SCALE: NONE
SANITARY WASTE AND VENT DIAGRAM - PHARMACY3
SCALE: NONE
SANITARY WASTE AND VENT DIAGRAM - TOILET ROOM4
PTD
SD
TP
1.25
" -
DH
W
1.25
" -
DC
W
1.5" - O23" - DCW
2" - DHW0.75" - DHW R
1" - MV1" - MA
3" - DCW2" - DHW
0.75" - DHW R
1" - MV1" - MA
1.5" - O2
4" - DCW3" - DHW1" - MV1" - MA
1.5" - O21.25" - DHW R
4" - DCW4" - DHW
1.25" - DHW R
1" - MA
1.25" - MV
1" - DHW R3" - DHW
3" - DCW1.25" - O2
1" - MV1" - MA
1" -
DH
W
1" -
DC
W
1.25" - G
1.25" - G
A1 B1
4" SS DN
4" SS DN
LAV
NEW CAP
CO
2
1
D1
F1
NEW CAPSNEW CAPS
0.5"1"
3" -
F
3" - F
3" -
F
1.5"
-O
2
1.5"
-O
2
1"
2" -
V
2 " V U P
W C
1" - MV
1542AHVAC
1535CORR.
1527CORRIDOR
1544
ORDER
ENTRY
OFC
1542ANTI RM
1541CHEMO RM
1540
HD
NON-STERILE
1539NARC RM
1538POP
1533JAN
1550PACKAGING
1548RECEIVING
1547
ADA STAFF
TOILET
1546OFC
1545MGR. OFC
1543IV RM
1537A
BULK
STORAGE
1537
ORDER
ENTRY
OH1
OH1
NEW C APS
NEW C APS
7
5
5
7
7
5
5
OH1
E1
FD1 3
4
6
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
5/2
01
9 7
:04
:13
AM
C:\
BIM
\Mod
el\20
19
-05
07
8-M
EP
-Ce
ntr
al_
WS
McC
am
ey.r
vt
2019-05078
ABN
W SM
July 24, 2019
P201
PARTIAL FIRST FLOORPLAN - NEW W ORK
1 2019.07.24 ADDENDUM 1
SCALE: 1/4" = 1'-0"
PARTIAL FIRST FLOOR PLAN - NEW WORK1
NOTES
7 ROUTING OF FIRE MAIN SHALL FOLLOW THE HOT AND CHILLED WATERPIPING. COORDINATE ROUTING AND HANGERS CLOSELY WITH HC.
NOTES
1 ROUTE SANITARY PIPING THROUGH WALL AND DROP BEYONDELECTRICAL EQUIPMENT BELOW.
2 REROUTE EXISTING SANITARY PIPING AND CONNECT TO EXISTINGSANITARY STACK. COORDINATE NEW ROUTING CLOSELY WITH HC.
3 PROVIDE 3" FLOOR DRAIN WITH 12" STRAINER AND SEDIMENT BUCKET,JR SMITH #2130-B.
4 PROVIDE TRAP PRIMER, PPP INC. #PR-500. EXTEND TRAP PRIMERDISCHARGE AND TERMINATE ABOVE FLOOR DRAIN.
5 PROVIDE NEW FIRE SUPPRESSION COVERAGE THROUGHOUTRENOVATED AREA PER NFPA 13 REQUIREMENTS.
6 PROVIDE GASKETED COVERPLATES IN THESE FOUR (4) ROOMS.
A. ELECTRONIC COORDINATION DRAW INGS ARE REQUIRED AND MUST BE SUBMITTED TO THE ENGINEER FOR REVIEW PRIOR TO BEGINNING NEW W ORK. REFER TO 23 05 01.
GENERAL NOTES
NOTE: ALL SYMBOLS AND ABBREVIATIONS
ARE SUBJECT TO MODIFICATIONS
ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS
MIGHT NOT NECESSARILY BE USED ON
THIS PROJECT.
ABBREVIATIONS
AC - AIR COMPRESSOR OR AIR CONDITIONERACCU - AIR COOLED CONDENSING UNITAD - ACCESS DOOR OR AREA DRAINADJ - ADJUSTABLEAFF - ABOVE FIN ISHED FLOORAFG - ABOVE FIN ISHED GRADEAFMS - AIR FLOW MEASURING STATIONALT - ALTERNATEAP - ACCESS PANELAPPROX - APPROXIMATEARCH - ARCHITECT OR ARCHITECTURALASSY - ASSEMBLYATC - AUTOMATIC TEMPERATURE CONTROL
BDD - BACK DRAFT DAMPERBFP - BACKFLOW PREVENTERBLDG - BUILDINGBOB - BOTTOM OF BEAMBOD - BOTTOM OF DUCTBOE - BOTTOM OF EQUIPMENTBOF - BOTTOM OF FOOTINGBOG - BOTTOM OF GRILLEBOP - BOTTOM OF PIPEBOT - BOTTOMBTU - BRITISH THERMAL UNITBTUH - BRITISH THERMAL UNIT PER HOUR
CBD - COUNTER BALANCED BACKDRAFT DAMPERCFCI - CONTRACTOR FURNISHED CONTRACTOR
INSTALLEDCFM - CUBIC FEET PER MINUTECHS - CHILLED W ATER SUPPLYCHR - CHILLED W ATER RETURNCHGR - CHILLED W ATER GLYCOL SOLUTION RETURNCHGS - CHILLED W ATER GLYCOL SOLUTION SUPPLYCLG - CEILINGCMU - CONCRETE MASONRY UNITCO - CLEAN OUTCO2 - CARBON DIOXIDECONN - CONNECT OR CONNECTIONCONTR - CONTRACTORCTR - CENTERCU - COPPERCW - COLD W ATERCW R - CONDENSER W ATER RETURNCW S - CONDENSER W ATER SUPPLY
D - DRAIN LINEDB - DRY BULBDDC - DIRECT DIGITAL CONTROLSDI - DEIONIZED W ATERDIA - DIAMETERDIM - DIMENSIONDN - DOW NDW G - DRAW ING
EA - EACH OR EXHAUST AIREAT - ENTERING AIR TEMPERATUREEC - ELECTRICAL CONTRACTOR (DIVISION 26)EJ - EXPANSION JOINTELEC - ELECTRICALELEV - ELEVATOREQUIP - EQUIPMENTET - EXPANSION TANKETR - EXISTING TO REMAINEQS - EQUIPMENT SUPPLIEREW T - ENTERING W ATER TEMPERATUREEXH - EXHAUSTEXP - EXPANSIONEXT - EXTERIOREX - EXISTING
FD - FLOOR DRAINFF - FINISHED FLOOR ELEVATIONFLR - FLOORFOB - FLAT ON BOTTOMFOF - FUEL OIL FLOWFOG - FUEL OIL GAUGEFOR - FUEL OIL RETURNFOS - FUEL OIL SUPPLYFOT - FLAT ON TOPFPM - FEET PER MINUTEFSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)FT - FEETFTG - FOOTING
G - GAS OR NATURAL GASGA - GAUGEGAL - GALLONGALV - GALVANIZEDGC - GENERAL TRADES CONTRACTORGPM - GALLONS PER MINUTE
HB - HOSE BIBBHC - HVAC CONTRACTOR (DIVISION 23)HD - HUB DRAINHG - REFRIGERANT HOT GASHP - HORSEPOW ERHPC - HIGH PRESSURE CONDENSATE RETURNHPS - HIGH PRESSURE STEAM SUPPLYHR - HOURHT - HEAT TRACEHTR - HEATERHVAC - HEATING, VENTILATING, AND AIR CONDITIONINGHW - HOT W ATERHW R - HEATING HOT W ATER RETURNHW S - HEATING HOT W ATER SUPPLY
ID - INSIDE DIAMETERINV - INVERT ELEVATIONIN - INCHES
KEC - KITCHEN EQUIPMENT CONTRACTOR
L - LENGTHLAT - LEAVING AIR TEMPERATURELAV - LAVATORYLBS - POUNDSLPC - LOW PRESSURE CONDENSATE RETURNLPS - LOW PRESSURE STEAM SUPPLYLW T - LEAVING W ATER TEMPERATURE
MAX - MAXIMUMMDD - MOTORIZED DAMPERMEZZ - MEZZANINEMFR - MANUFACTURERMH - MANHOLEMIN - MINIMUM OR MINUTEMISC - MISCELLANEOUSMTD - MOUNTEDMTG - MOUNTINGMPC - MEDIUM PRESSURE CONDENSATE
RETURNMPS - MEDIUM PRESSURE STEAM SUPPLYMU - W ATER MAKE-UP
N/C - NORMALLY CLOSEDNIC - NOT IN CONTRACTN/O - NORMALLY OPENNOM - NOMINALNPT - NATIONAL PIPE THREADNTS - NOT TO SCALE
OA - OUTDOOR AIROBD - OPPOSED BLADE DAMPEROD - OUTSIDE DIAMETEROFCI - OW NER FURNISHED CONTRACTOR
INSTALLEDOFOI - OW NER FURNISHED OW NER INSTALLED
P - PROPANE GASPC - PLUMBING CONTRACTOR (DIVISION 22)
OR PUMPED CONDENSATE RETURNPLBG - PLUMBINGPRESS - PRESSUREPRV - PRESSURE REGULATING VALVEPSF - POUNDS PER SQUARE FOOTPSI - POUNDS PER SQUARE INCHPSIG - POUNDS PER SQUARE INCH GAUGE
RA - RETURN AIRRAD - RADIUSRCP - REFLECTED CEILING PLANRD - ROOF DRAINREC - RECESSEDREQD - REQUIREDRI - ROUGH INRL - REFRIGERANT LIQUIDROS - REVERSE OSMOSIS W ATER SUPPLYROR - REVERSE OSMOSIS W ATER RETURNRPM - REVOLUTIONS PER MINUTERS - REFRIGERANT SUCTION
S - SPRINKLER (W ET)SA - SUPPLY AIRSAN - SANITARY OR SANITARY DRAINSCH - SCHEDULESCW - SOFT COLD W ATERSHT - SHEETSPEC - SPECIFICATIONSSQ - SQUARESR - SUPPLY RISERSRV - SAFETY RELIEF VALVESS - STAINLESS STEELSTD - STANDARDSTM - STORM OR STORM DRAINAGESTRUC - STRUCTURAL OR STRUCTURESUC - SITE UTILITY CONTRACTOR
TEMP - TEMPERATURETOB - TOP OF BEAMTOD - TOP OF DUCTTOE - TOP OF EQUIPMENTTOF - TOP OF FOOTINGTOJ - TOP OF JOISTTOP - TOP OF PIPETOS - TOP OF SLAB OR TOP OF STEELTYP - TYPICAL
UNO - UNLESS NOTED OTHERW ISE
V - VENTVAC - VACUUMVEL - VELOCITYVIB - VALVE IN BOXVOL - VOLUMEVTR - VENT THROUGH ROOFVR - VENT RISER
W / - W ITHW /O - W ITHOUTW B - W ET BULBW CO - W ALL CLEANOUT
GENERAL FLOOR PLAN NOTES
PLAN NOTE. APPLIES ONLY TO THE SHEET W HICH IT IS SHOW N UNLESS NOTED OTHERW ISE.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
3
3
A1EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK. LETTER DESIGNATIONS REFER TO SCHEDULES.
H1 H1OREQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TO SCHEDULES.
2
1
H2
B
H2
RISER OR STACK NUMBER
DETAIL: B = DETAIL DESIGNATION H2 = SHEET W HERE DETAIL IS LOCATED
SECTION: 1 = SECTION DESIGNATION H2 = SHEET W HERE DETAIL IS LOCATED
A1 "UP TO" SYMBOL (ITEM ON FLOOR ABOVE)
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR BOTTOM OF EQUIPMENT, UNLESS NOTED OTHERW ISE
10"
ELEV: 8' - 0"ELEV: 8' - 0"
TOD: 8' - 10"
BOD: 7' - 2"
20x20
20x20
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR BOTTOM OF DUCTW ORK, UNLESS NOTED OTHERW ISE
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO CENTERLINE OF PIPE, UNLESS NOTED OTHERW ISE
DL-1
UC-X DOOR UNDERCUT. X = HEIGHT OF UNDERCUT IN INCHES; 0.75 INCH UNDERCUT IF NO HEIGHT IS NOTED. COORDINATE W ITH GC.
DOOR LOUVER. 1 = SQUARE FEET OF LOUVER.
CONNECT TO EXISTING
HVAC PIPING DESIGNATIONS
CHILLED W ATER SUPPLY PIPECHS
CONDENSER W ATER SUPPLY PIPECW S
CONDENSER W ATER RETURN PIPECW R
DRAIN LINE. PITCH IN DIRECTION INDICATEDD
HEATING HOT W ATER SUPPLY PIPEHW S
HEATING HOT W ATER RETURN PIPEHW R
W ATER MAKE-UP PIPEMU
VENT PIPEV
REFRIGERANT LIQUID LINERL
REFRIGERANT SUCTION LINERS
EXPANSION TANK PIPEET
REFRIGERANT HOT GAS LINEHG
LOW PRESSURE CONDENSATE RETURN PIPELPC
LOW PRESSUR E STEAM SUPPLY PIPELPS
M EDIUM PRESSURE CON DENSATE RETURN PIPEMPC
M EDIUM PRESSURE STEAM SUPPLY PIPEM PS
PUMPED CONDENSATE RETURN PIPEPC
HIGH PRESSURE CONDENSATE RETURN PIPEHPC
HIGH PRESSURE STEAM SUPPLY PIPEHPS
STEAM SUPPLY PIPE - NUMBER INDICATES P.S.I.G.10
MISC SYMBOLS
DUCTWORK SYMBOLS
ROUND BRANCH DUCTW ORKCONICALFITTING
ACOUSTICFITTING
ACOUSTICFITTING
ADAD
D
R R
D
RECTANGULAR BRANCH DUC TW ORK
SQUARE TEE W ITH TURNING VANES
NOTE: ALL SQUARE ELBOW S IN RECTANGULAR AND ROUND / OVAL DUCTW ORK SHALL BE PROVIDED W ITH TURNING VANES. REFER TO SPECIFICATIONS FOR ADDITIONAL DETAILS.
EXISTING DUCTW ORK TO REMOVED
RETURN AIR, RELIEF AIR, OR TRANSFER AIR DUCTW ORK. (UP AND DOW N) RADIUSED OR SQUARE W ITH TURNING VANES.SUPPLY AIR OR OUTDOOR AIR DUCTW ORK.(UP AND DOW N) RADIUSED OR SQUARE W ITH TURNING VANES.
EXHAUST AIR DUCTW ORK. (UP AND DOW N) RADIUSED OR SQUARE W ITH TURNING VANES.
RECTANGULAR AND ROUND / OVAL DUCTW ORK RISE / DROP W ITH 90° RADIUSED OR SQUARE ELBOW S AND TURNING VANES.
RADIUS ELBOW
90° SQUARE ELBOW (W ITH TURNING VANES)NOTE: ALL SQUARE ELBOW S IN RECTANGULAR AND ROUND DUCTW ORK SHALL BE PROVIDED W ITH TURNING VANES.
ACCESS DOOR OR PANEL
DUCTW ORK RISE IN DIRECTION OF AIR FLOW
DUCTW ORK DROP IN DIRECTION OF AIR FLOW
DUCTW ORK W ITH ACOUSTICAL LINER. LISTED DUCT SIZES ARE INSIDE CLEAR DIMENSIONS.
RECTANGULAR ROUND / OVAL
FLEXIBLE DUCTW ORK
FLEXIBLE CONNECTION
DUCTW ORK CONSTRUCTED OF SPECIAL MATERIAL AS NOTED
DIRECTION OF PITCH
RECTANGULAR DUCTW ORK DIMENSIONS(W x H)26x20
ROUND DUCTW ORK DIMENSIONS (DIA)26ø
OVAL DUCTW ORK DIMENSIONS (W x H)26x20 OV
DUCTWORK DEVICE SYMBOLS
W ALL OR DUCTW ORK MOUNTED AIR DEVICE. SG1 = DESIGNATION (REFER TO AIR DEVICE SCHEDULE). 20x12 = DUCT CONNECTION SIZE (IN INCHES).300 = REQUIRED CFM. 9'-0" = MOUNTING HEIGHT FROM FLOOR TO BOTTOM OF GRILLE.
A310ø300
MANUAL BALANCING VALVE DAMPER W ITH LOCKING DEVICE
BDD = BACK DRAFT DAMPERCBD = COUNTER-BALANCED BACK DRAFT DAMPER
SD = SMOKE DAMPERFS = COMBINATION FIRE - SMOKE DAMPERMDD = MOTORIZED DAMPERAFMS = AIR FLOW MEASURING STATION
DUCT MOUNTED SMOKE DETECTOR. COORDINATE LOCATION.
HUMIDITY SENSOR - DUCT MOUNTED
SG120x12
300BOG: 9'-0"
XXX
A-D
XX
H
SD
SP
AIR DEVICE. A3 = DESIGNATION (REFER TO FLOOR PLANS AND AIR DEVICE SCHEDULE FOR VARIOUS DESIGNATIONS).10ø = NECK SIZE (IN INCHES). 300 = REQUIRED CFM. ALL AIR DEVICE DISCHARGE 4-W AY UNLESS NOTED W ITH FLOW ARROW S. AIR DEVICE SHOW N IS 2-W AY SIDE THROW . METHOD OF IDENTIFICATION ALSO APPLIES TO OTHER CEILING MOUNTED AIR DEVICES.
FIRE DAMPERA = TYPE (REFER TO FLOOR PLANS FOR VARIOUS TYPES)D OR S = DYNAMIC OR STATIC
STATIC PRESSURE SENSOR - DUCT MOUNTED
CCARBON D IOXIDE SENSOR - DUCT MOUNTED
STEMPERATURE SENSOR - DUCT MOUNTED
CHECK VALVE
T
P
FOB
FOT
SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR REQUIRED TYPE BASED ON APPLICATIONS)
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
PRESSURE GAUGE
TEMPERATURE GAUGE OR THERMOMETER
COMBINATION SHUTOFF AND BALANCING VALVE (REFER TO SPECIFICATIONS FOR REQUIRED TYPE BASED ON APPLICATIONS)
BALL VALVE
BUTTERFLY VALVE
GATE VALVE
VALVES AND FITTINGSDOUBLE LINE SINGLE LINE
10"
TOE: 3' - 0"
BOE: 0' - 6"
CHILLED W ATER GLYCOL SOLUTION RETURN PIPECHGR
CHILLED W ATER GLYCOL SOLUTION SUPPLY PIPECHGS
CHILLED W ATER RETURN PIPECHR
SQUARE THROAT / RADIUS HEEL FITTINGS NOT ACCEPTABLE
PIPING SYMBOLSDOUBLE LINE SINGLE LINE
BOTTOM CONNECTION (45°)
BRANCH TEE CONNECTION (NOTE: BULLHEAD TEE'S ARE NOT PERMITTED)
DIRECTION OF PITCH
DROP
ELBOW DOW N
ELBOW UP
EXISTING PIPE TO BE REMOVED
EXISTING PIPE TO REMAIN
FLOW DIRECTION DESIGNATION
PUMP
RISE
TOP CONNECTION (45°)
TOP CONNECTION (90°)
BOTTOM CONNECTION (90°)
DD
RR
PIPE RISER
RADIUS'D BRANCH
RADIUS'D TEE
EXISTING DUCTW ORK TO REMAIN
UNLESS NOTED OTHERW ISE ON DRAW INGS, 15° MAX FOR DIVERGING, 30° MAX FOR CONVERGING TRANSITION
EMERGENCY SHUTOFF STATION. 46" MOUNTING HEIGHT UNLESS NOTED OTHERW ISE.
SPACE TEMPERATURE SENSOR / THERMOSTAT. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.
T
DPDIFFERENTIAL PRESSURE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.
HHUMIDITY SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.
CARBON DIOXIDE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.
C
COCARBON MONOXIDE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.
TEMPERATURE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.
S
S TEMPERATURE SENSOR MOUNTED IN CEILING PLENUM.
STATIC PRESSURE SENSOR.SP
STRAINER W ITH A BLOW DOW N VALVE AND HOSE CONNECTION
DRAIN VALVE W ITH HOSE END CONNECTION
AUTOMATIC FLOW CONTROLLER W ITH P/T PLUG IN AND OUT
EXPANSION JOINT
MANUAL AIR VENT
AUTOMATIC AIR VENT
PRESSURE REDUCING VALVE
2 PORT AUTOMATIC CONTROL VALVE
3 PORT AUTOMATIC CONTROL VALVE
QUICK OPENING MANUAL VALVE
VACUUM BREAKER
NEEDLE VALVE
PRESSURE AND TEMPERATURE TEST PLUG
VACUUM GAUGE W ITH STOP
END CAP
GLOBE VALVE
SHUTOFF VALVE AND BOX
SHUTOFF VALVE ON RISER
A
M
M
N
V
VB
SOLENOID VALVES
SAFETY RELIEF VALVE. FOR HYDRONIC SYSTEMS PIPE DISCHARGE AIR GAPPED TO FLOOR DRAIN UNLESS NOTED OTHERW ISE. FOR STEAM SYSTEMS PIPE DISCHARGE TO OUTDOORS.
W ATER METERM
PRESSURE GAU GE W ITH COCK AND SIPHON LOOP
BI-M ETALIC STEAM TRAP AND DRIP ASSEM BLY
THERMODYNAMIC STEAM TRAP AND DRIP ASSEMBLY
INVERTED BUCKET STEAM TRAP AND DRIP ASSEMBLY
FLOAT AND THERMOSTATIC STEAM TRAP AND DRIP ASSEMBLY
THERM OSTATIC STEAM TRAP AND DRIP ASSEM BLY
BM
TD
IB
FT
TS
FLOW M ETERF
UNION
CLEANOUT
STRAINER
AUTOMATIC PRESSURE INDEPENDENT CONTROL VALVE
M
HVAC GENERAL NOTES
A. THESE NOTES APPLY EQUALLY TO THE FULL SET OF DOCUMENTS.
B. INCLUDE ALL W ORK NECESSARY TO ACCOMMODATE PHASING. REFER TO ARCHITECTURAL DRAW INGS AND GENERAL REQUIREMENTS SECTION 01 00 00.
C. INSULATE DUCTW ORK AND PIPING W HERE EXISTING INSULATION HAS BEEN DAMAGED AND/OR REMOVED IN THE PERFORMANCE OF W ORK IN THIS PROJECT.
D. PROVIDE ALL ROOFING PENETRATION, REPAIR & REINFORCEMENT IN THE EXISTING BUILD ING FOR W ORK INDICATED. ENGAGE A ROOFING SUBCONTRACTOR TO PERFORM THE ROOFING W ORK. W HERE ROOFING W ORK IS REQUIRED, THE EXISTING ROOFING MEMBRANE AND INSULATION SHALL BE CUT, REMOVED AND RESTORED AS REQUIRED TO ATTAIN A W ATERTIGHT CONDITION. THE ROOFING SUB-CONTRACTOR SHALL BE A CERTIFIED INSTALLER FOR SUCH INSTALLATION TO MAINTAIN THE EXISTING W ARRANTY ON THE ROOF.
E. THE CONTRACTOR SHALL REFER TO ALL SPECIFICATION SECTIONS AND THESE DRAW INGS FOR DETAILS OF BUILDING CONSTRUCTION TO ENSURE SPACE AND SATISFACTORY ARRANGEMENT FOR THEIR W ORK. THE VARIOUS DRAW INGS COMPRISING THE SET ARE INTERDEPENDENT AND MUST BE USED JOINTLY AT ALL TIMES. THE CONTRACTOR SHALL REFER TO THE GENERAL REQUIREMENTS OF THE CONTRACT. THE NOTES AND SYMBOLS INDICATED ON THE DRAW INGS ARE FOR THE GUIDANCE OF ALL TRADES INVOLVED IN THE PROJECT AND MUST BE FOLLOW ED TO EXECUTE THE W ORK AS INTENDED. IF DISCREPANCIES OCCUR, CONTACT THE COR THRU THE CONTRACTING OFFICER FOR CLARIFICATION BEFORE PROCEEDING.
F. IN ACCORDANCE W ITH GENERALLY ACCEPTED CONSTRUCTION PRACTICES, THE CONTRACTOR W ILL BE SOLELY AND COMPLETELY RESPONSIBLE FOR THE CONDITIONS ON THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY DURING PERFORMANCE OF THE W ORK. THIS W ILL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL W ORKING HOURS. SEE SPECIFICATIONS FOR MORE SPECIFIC DETAILS ON RESPONSIBILITIES.
G. ALL W ORK MUST BE COORDINATED W ITH THE CONTRACTING OFFICER AND COR TO MAINTAIN OPERATION OF THE EXISTING FACILITY.
H. EACH CONTRACTOR SHALL COORDINATE HIS W ORK W ITH THE W ORK OF OTHERS. HE SHALL KEEP HIMSELF INFORMED OF THE PROGRESS AND DETAIL DEVELOPMENT OF THE W ORK OF OTHERS AND SHALL BE RESPONSIBLE FOR COORDINATING AND EXPEDITING HIS W ORK W ITH OTHERS SO THAT THE PROGRESS OF THE TOTAL W ORK SHALL BE KEPT ON SCHEDULE.
I. ALL W ORK SHALL BE PERFORMED IN COMPLETE COMPLIANCE W ITH ALL GOVERNING CODES AND STANDARDS.
J. EXISTING CONDITIONS SHOW N HAVE BEEN BASED UPON AVAILABLE DRAW ING INFORMATION, AND MAY BE AT VARIANCE W ITH ACTUAL W ORK IN PLACE. THE CONTRACTOR SHALL TAKE ALL NECESSARY FIELD MEASUREMENTS AND FIELD VERIFY ALL CONDITIONS AFFECTING THE EXECUTION OF THE W ORK. ANY DISCREPANCIES BETW EEN EXISTING CONDITIONS AND THE W ORK SHOW N ON THE CONTRACT DOCUMENTS W HICH MAY IMPACT THE PROGRESS OF THE W ORK SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER IN W RITING FOR RESOLUTION BEFORE PROCEEDING W ITH THE W ORK.
K. EACH CONTRACTOR AND/OR TRADE, FITTING OR PLACING HIS W ORK INTO OR ON THE W ORK OF OTHERS DOES SO W ITH THE UNDERSTANDING THAT THE INSTALLATION OF H IS W ORK CONSTITUTES HIS ACCEPTANCE OF THE SUITABILITY OF THE W ORK IN PLACE. IF THE W ORK OF OTHERS IS NOT ACCEPTABLE, HE SHALL NOTIFY THE COR AND SUCH W ORK SHALL BE CORRECTED. ANY NEW W ORK INSTALLED IN UNSUITABLE EXISTING W ORK SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR OR TRADE INSTALLING THE NEW W ORK. NO CLAIMS FOR ADDITIONAL COMPENSATION FOR CORRECTING W ORK INSTALLED IN UNSUITABLE EXISTING CONDITIONS W ILL BE CONSIDERED.
L. IF, IN THE PERFORMANCE OF THIS W ORK, MATERIALS ARE OBSERVED W HICH ARE SUSPECTED TO CONTAIN ASBESTOS, THE CONTRACTOR SHALL IMMEDIATELY INFORM THE COR. W ORK THAT W OULD EXPOSE W ORKERS TO THE INHALATION OF ASBESTOS PARTICLES SHALL BE TERMINATED. W ORK MAY BE RESUMED ONLY AFTER A DETERMINATION HAS BEEN MADE AND UNSAFE MATERIALS HAVE BEEN REMOVED OR ENCAPSULATED AND THE AREA DECLARED SAFE.
M . CONTRACTORS SHALL TAKE SPECIAL CARE W HILE W ORKING ADJACENT TO ASBESTOS MATERIALS AND MUST BE PROPERLY PROTECTED W ITH CLOTHING, BREATHING APPARATUS, ETC. VERIFY REQUIREMENTS OF VAMC'S INFECTION CONTROL RISK ASSESSMENT TEAM (ICRA).
N. THE FIRST FIGURE OF DUCT SIZE INDICATES D IMENSION OF FACE SHOW N OR INDICATED. DUCT SIZES ARE NET INSIDE DIMENSIONS.
O. PROVIDE DUCT ACCESS PANELS AS REQUIRED BY 23 31 00 FOR ACCESS TO FIRE DAMPERS, SMOKE DAMPERS, SMOKE DETECTORS, AUTOMATIC CONTROL DAMPERS, AND HUMIDIFIER DISPERSION TUBES. REFER TO DETAIL ON SHEET M0.3. COORDINATE SIZES AND LOCATIONS W ITH ACCESSORIES PROVIDED BY OTHER TRADES.
P. ALL PRESSURES LISTED ARE GAGE PRESSURE UNLESS OTHERW ISE NOTED.
Q. ALL CUTTING AND PATCHING REQUIRED FOR THIS PROJECT SHALL BE INCLUDED IN THE CONTRACT. REFINISH ANY SURFACE DISTURBED UNDER THIS W ORK TO MATCH EXISTING.
R. THE CONTRACT DRAW INGS ARE NOT INTENDED TO SHOW EVERY VERTICAL OR HORIZONTAL OFFSET W HICH MAY BE NECESSARY TO COMPLETE THE SYSTEMS. COORDINATE W ORK IN ADVANCE W ITH ALL OTHER TRADES AND REPORT IMMEDIATELY ANY DIFFICULTIES W HICH CAN BE ANTICIPATED.
S. FIELD VERIFY EXISTING CONDITIONS, INCLUDING DUCT, PIPE AND EQUIPMENT SIZES, SERVICES AND LOCATIONS PRIOR TO PERFORMING W ORK.
T. ALL ABANDONED EXTRANEOUS PIPING, DUCTW ORK, SUPPORTS, CONTROLS, ETC. SHALL BE REMOVED.
U. W HERE CONTROL DEVICES ARE REMOVED, PNEUMATIC LINES SHALL BE REMOVED BACK TO MAIN AND CAPPED; AND CONTROL W IRING AND CONDUIT SHALL BE REMOVED BACK TO SOURCE.
V. ALL EXISTING DUCTW ORK, PIPING, EQUIPMENT, CONTROLS, ETC. SHOW N DASHED SHALL BE REMOVED. THE MAJORITY OF W ORK TO BE REMOVED IS SHOW N. REMOVE ALL INC IDENTAL AND/OR ABANDONED DUCTW ORK, PIPING, ETC. THAT MAY NOT BE SHOW N BUT IS ASSOCIATED W ITH THE REMOVAL W ORK.
W . ALL ITEMS THAT REQUIRE ACCESS, SUCH AS FOR OPERATING, CLEANING, SERVICING, MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE BY PERSONS STANDING AT FLOOR LEVEL, OR STANDING ON PERMANENT PLATFORMS, W ITHOUT THE USE OF PORTABLE LADDERS. EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF VALVES, FILTERS AND STRAINER, TRANSMITTERS, CONTROL DEVICES, ETC.
X. REFER TO SPECIFICATIONS SECTION 01 00 00 GENERAL REQUIREMENTS AND THESE DRAW INGS FOR DESCRIPTIONS OF THE BID ITEMS INCLUDING DEDUCT ALTERNATES, ADDITIONAL INFORMATION NOTED THROUGHOUT THE DRAW INGS.
Y. SYSTEMS SERVING AREAS OUTSIDE THE CONSTRUCTION ZONE SHALL REMAIN OPERATIONAL DURING CONSTRUCTION. ANY OUTAGES SHALL BE PERFORMED ON W EEKENDS OR W EEK NIGHTS. DOW NTIME SHALL BE KEPT TO A MINIMUM, AND SHALL BE COORDINATED AND SCHEDULED 4 W EEKS (30 CALENDAR DAYS) IN ADVANCE W ITH THE COR.
Z. REFER TO NEW W ORK FLOOR PLANS FOR W ORK THAT MAY BE REQUIRED PRIOR TO ANY REMOVAL W ORK.
AA. READ ALL NOTES THOROUGHLY PRIOR TO STARTING CONSTRUCTION.
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
5/2
01
9 1
2:2
0:4
4 P
MC
:\B
IM\M
ode
l\20
19
-05
07
8-M
EP
-Ce
ntr
al_
ajg
ran
ata
@h
ea
py.c
om
.rvt
2019-05078
DTR
AJG
July 24, 2019
M001
MECHANICAL LEGEND,GENERAL NOTES, ANDINDEX OF DRAW INGS
1 2019.07.24 ADDENDUM 1
SHEET INDEX - MECHANICAL
SHEET NUMBER SHEET NAME
M001 MECHANICAL LEGEND, GENERAL NOTES, AND INDEX OF DRAWINGS
M002 MECHANICAL SCHEDULES
M003 MECHANICAL DETAILS
M004 MECHANICAL DETAILS
M005 MECHANICAL DETAILS
M007 MECHANICAL CONTROL SCHEMATICS
M008 MECHANICAL CONTROL SCHEMATICS
M101 PARTIAL FIRST FLOOR PLAN - DEMOLITION
M201 PARTIAL FIRST FLOOR PLAN - NEW WORK
M301 HVAC ROOF
Total Count: 10
C.V.R. 300 300 9.8 1.0 0.75" 0.4 3524-03ASUPPLY
V.V. 650 420 - - - - 3524-03B 12"ROOM EX. 7
V.V. - - - - 3524-03C 8"
- - - - -TOTAL CHEMO
930 930
3,4,5,6
-350
4. AIR VALVE TO HAVE EPOXY COATING TO RESIST CORROSION.
6. AIR VALVE SHALL BE ENABLED BY "AUXILIARY" SWITCH ON HOOD.
5. PROVIDE AIR-TIGHT SHUTOFF DAMPER AT BSC EQUIPMENT CONNECTION.
7. PROVIDE BLAST GATE DOWN STREAM OF ROOM EXHAUST AIR VALVE.
1. MINIMUM ROOM SUPPLY SHALL BE THE SCHEDULED "OCCUPIED MINIMUM" AS NOTED.
2. MINIMUM ROOM EXHAUST SHALL BE THE ROOM SUPPLY MINUS CFM OFFSET.
3. AIR VALVE SHALL BE SHUT-OFF TYPE.
C.V.R. 1,520 1,520 49.5 5.0 1.0" 2.3 3524-01A 14"SUPPLY 1
C.V. 1120 1120 - - - - 3524-01B 14"RETURN 7
+400
IV ROOM
2
2-WAY
-
-
-
2-WAY
-
1
TYPES - "V.V." VARIABLE VOLUME;
"V.V.R." VARIABLE VOLUME REHEAT;
"C.V.R." CONSTANT VOLUME REHEAT;
UNIT & COIL AT MAX. CFM (VAV BOX).
0.5" S.P. MAX. PRESS. DROP THRU
"C.V." CONSTANT VOLUME.REHEAT COIL CAPACITY BASED ON
WINTER MIN. CFM, 53° ENT. AIR, 180° ENT.
WATER TEMPERATURE, 160° LVG. WATER
TEMPERATURE, MAX 7 FT. HD. W.P.D.
8"
AIR VALVE 0.3" MAX PRESS.
DROP THRU UNIT AT MAX CFM.
1543
C.V.R. 510 510 15.5 1.6 0.75" 0.7 3524-02A 10"SUPPLY 1
C.V. 235 235 - - - - 3524-02B 8"RETURN 7
+275
ANTE 2-WAY
-
1542
CHEMO
CHEMO
CHEMO
- - - - -TOTAL STORAGE
450 450 2-
1541
HOOD EX.
ROOM EXHAUST
ROOM EXHAUST
C.V.R. 200 200 6.6 0.7 0.75" 0.3 35SUPPLY 1
C.V. 400 400 - - - - 35RETURN 7
-200
HD STOR. 2-WAY
-
1540
8"24-04A
24-04B 10"
650 420
EXHAUST DUCTWORK, NEW EF-92
SUPPLY DUCTWORK DOWNSTREAM OF
RETURN DUCTWORK
VAV BOXESA+1"
-6"
-2"
A
A
X
X
X
16/8
16/8
4/2
2
NOTES:1 DUCTWORK OVER 3" S.P. CLASS REQUIRES LEAK TESTING. REFER TO SPECIFICATIONS.
2 ROUND, SHEET METAL RUN-OUTS TO AIR DEVICES, DOWNSTREAM OF VAV BOXES SHALL BE EXTERNALLY INSULATED.
3 INSULATE FROM 24" UPSTREAM OF CONTROL DAMPER TO PENETRATION OF ROOF.
VAV BOXESSUPPLY DUCTWORK UPSTREAM OF
+3 4/2 XA 1
EF-92 PHARMACY CHEMO EXHAUST 1,300UTILITY SET FAN 1, 2, 3, 4, 5, 6, 7, 8
1 COORDINATE ACTUAL EQUIPMENT NUMBER WITH BUILDING CONTROLS.
2 PROVIDE FAN WITH MOTORIZED DAMPER EQUAL TO TAMCO SERIES 9000. WHEN FAN IS OFF, DAMPER SHALL BE CLOSED. DAMPER ACTUATOR SHALL HAVE END SWITCH TO PREVENT THE
FAN FROM TURNING ON UNTIL THE DAMPER IS PROVEN OPEN. DAMPER SHALL BE LOCATED IN THE DUCTWORK BELOW THE ROOF, REFER TO DETAIL.
3 PROVIDE UTILITY SET FAN WITH 10' STACK ABOVE ROOF, REFER TO DETAIL.
4 PROVIDE FAN WITH 8" DISCHARGE, REFER TO DETAIL.
1 AIR DEVICE USED FOR RETURN AIR SYSTEM.
A1STANDARD SQ. CONE CEILING
DIFFUSER - ROUND NECKTITUS - TMS-AA
J1 EGGCRATE CEILING GRILLE TITUS - 50F 1
5 FAN SHALL BE ON EMERGENCY POWER.
6 3,600 RPM MOTOR.
1
7 FAN SHALL BE PROVIDED WITH A BOTTOM UPWARDS (BAU) DISCHARGE, REFER TO DETAIL.
8 FAN SHALL BE PROVIDED WITH A VARIABLE FREQUENCY DRIVE WITH BYPASS.
HU-5
ELEVATION BASED ON 499 FT.
ULTRA-SORB XV AIR HANDLER AHU-5 2,800 53.3 34 55 71 68 451.0" 0.75" 24" 16" 14" 1, 2
HUMIDIFIER BASED ON 40 PSIG ENTERING STEAM PRESSURE.
45.9
MOTOR - 480V - 3 PHASE UNLESS NOTED OTHERWISE.
COOLING COIL CAPACITY BASED ON 42° EWT.HEATING COIL CAPACITY BASED ON 180° EWT.
AHU-24
COOLING COILS SHALL NOT
1 REFER TO STEAM HUMIDIFIER SCHEDULE ON THIS SHEET.2 PROVIDE UV LIGHTS ON COOLING COIL AND FINAL FILTER.
CAPACITIES BASED ON
7.4" / 2.6"
-
4,534
3,000
29
6.75
117
65
0.07"
12" MERV 14
8
SIDE ACCESS
0.18"
FRONT ACCESS
8
0.3"
1.0"
1.5"
215
7.0
133
30 - (1) 1.5"
86.0 / 70.0
45.7 / 45.7
17
14.5 / 2-WAY
1.18"
1,500 (50.0%)
INTERNAL - 2"
YES
YES
2
INGENIA
2" CARTRIDGE FILTER
3 PROVIDE UNIT WITH SINGLE POINT POWER CONNECTION. PROVIDE 120 VOLT
3
11.8 - (1) 1.5"
17
5.6 / 2-WAY
MERV 8
FIRST FLOOR
ROOF
DRAW THRU
3,000
PHARMACY
1. REFER TO PIPING DETAIL FOR PIPE ACCESSORIES.
2. HUMIDIFIER CONTROL PANEL REQUIRES 120V POWER FEED BY E.C.2,480
P-24 INLINE PUMP HOT WATER COIL - AHU-24 11 25 245 120 1 - - UP 26-99 F
RELIEF AIR DUCTWORK AND PLENUMS
OUTSIDE AIR DUCTWORK AND PLENUMS
+2"
-2"
A
A 16/8
16/8 3X
X
FCU-1
225
0.19
0.13
115 / 1
ECM
1, 2
RECEIVING
RECEIVING
CHILLED WATER
3.8
4.9
71 / 61
51 / 50
3.9
1.4
0.7 / 2-WAY
MERV 8
54
TRANE FCC
BLOW-THRU
0.5
0.1
85
65
3.2
0.2 / 2-WAY
FCU-2 FCU-3 FCU-4A FCU-4B FCU-5
HORIZ. CONC. DUCTED
700
0.19
0.22
115 / 1
ECM
1, 2
BULK STORAGE
BULK STORAGE
CHILLED WATER
9.0
10.0
72 / 61
51 / 50
18.1
6.5
3.0 / 2-WAY
MERV 8
212
TRANE FCC
BLOW-THRU
1.2
0.5
85
65
11.6
0.5 / 2-WAY
BULK STORAGE
1.2 / 2-WAY
MERV 8
106
TRANE FCC
1.2 / 2-WAY
MERV 8
106
TRANE FCC
0.8 / 2-WAY
MERV 8
71
TRANE FCC
CHILLED WATER
0.75
0.2
85
65
5.8
0.4 / 2-WAY
CHILLED WATER
0.75
0.2
85
65
5.8
0.4 / 2-WAY
CHILLED WATER
0.5
0.1
85
65
4.3
0.2 / 2-WAY
115 / 1 115 / 1 115 / 1
3.4
3.9
51 / 50
12.1
2.5
3.4
3.9
51 / 50
12.1
2.5
3.2
3.9
51 / 50
4.8
1.6
300
0.24
0.13
300
0.24
0.13
220
0.22
0.13
ECM ECM ECM
NARCOTICS & POPBULK STORAGEBULK STORAGE
BLOW-THRU BLOW-THRU BLOW-THRU
BULK STORAGE POP
HORIZ. CONC. DUCTED
300
0.19
0.13
115 / 1
ECM
1, 2
OFFICES
BULK STORAGE
CHILLED WATER
4.8
6.2
71 / 61
51 / 50
7.2
2.0
1.0 / 2-WAY
MERV 8
91
TRANE FCC
BLOW-THRU
0.5
0.1
85
65
4.1
0.2 / 2-WAY
72 / 61 72 / 61 72 / 61
1, 2 1, 2 1, 2
HORIZ. CONC. DUCTED HORIZ. CONC. DUCTED HORIZ. CONC. DUCTED HORIZ. CONC. DUCTED
EXCEED 12 FINS PER INCH.
CLEAR WATER.
1.75" / 1.5"
-
705
2,000
1,355
CONNECTION FOR UV LIGHTS, OUTLETS, LIGHTS, AND HEAT TRACE.
VENTILATION SCHEDULE
AIR SUPPLY UNIT
PHARMACY AIR CONTROL UNITS - HOT WATER
GENERAL NOTES
NOTES:
UNIT
NO. DIA.
INLETTYPEMIN. MBH GPM NOTE
SEE
VALVE CVAUTO.RUNOUT
SIZEN.C.
MAX.CFM REHEAT COILROOM
NO.
CFM
OFFSET MAX.
NOTE:
TYPEVALVE
DUCT CONSTRUCTION & SEALING
FANS
AIR DISTRIBUTION DEVICES
STEAM HUMIDIFIER
PUMPS
BLOWER COIL / FAN COIL
ELECTRIC HEATING UNITS
INSULATIONEXTERNAL
DUCTBOARD; ETC.
DUCT SYSTEM
S.M.A.C.N.A. CLASS.
S.P. CON-
STRUCT. CLASS
SEALINTERNALLY
CLASS
LEAKAGELINED
REFER TO SPECIFICATIONS FOR DUCT CONSTRUCTION:
SHEET METAL DUCT; INTERIOR LINING; EXTERIOR INSULATION; FIBERGLASS
GENERAL NOTES
NOTINSULATED
WALLINSULATED
DOUBLE
NOTES
RECT/RD
GENERAL CONTRACTOR.
WALL LINTEL FOR WALL OPENING BY
WHERE REQUIRED FOR DECK SUPPORT AND
STEEL FRAMING AROUND ROOF OPENING.
PHASE
CONSIDERED MINIMUM.
MOTOR HORSEPOWERS LISTED ARE TO BE
300 & 301 MEASURED AT 5 FT. FOR P.R.V.'S.
SONES VALUES BASED ON A.M.C.A. BULLETINS
DESCRIPTIONUNIT
NO.
CONTRACTOR.
VERIFY SIZE & COORDINATE WITH GENERAL
ROOF & WALL OPENINGS ARE APPROXIMATE.
SERVICESONES
MAX.STATIC WHEEL
PRESSCFM
DIA.
MOTOR
H.P. VOLT
ROOF/APPROX.
WALL OPG.
REFER TONOTE NO.
4.25" 12.25" 34 2 -480 3
BASIS OF
DESIGN
GREENHECKUSF-312-BI
GENERAL NOTES
W.B.E.
FINISH KEY: "W.B.E."- WHITE BAKED ENAMEL,
"E.C.L."-ETCHED CLEAR LACQUER OR ANODIZED.
SUPPLY AIR DIFFUSERS SHALL BE 4-WAY
BLOW UNLESS OTHERWISE NOTED ON DWGS.
DESCRIPTION
REFER TO SPECIFICATIONS FOR OTHER
ALL LAY-IN AIR DEVICES SHALL FIT IN
24"X24" LAY-IN CEILING SYSTEM.
SYMBOL
GENERAL NOTES
MANUFACTURERS.
TYPE MOUNTING MATERIAL
LAY-IN SURFACE STEEL
PROVIDE AUX. FRAMES FOR AIR DEVICES IN
CERAMIC TILE SURFACES.
PLASTER, GYPSUM BOARD, GLAZED TILE OR
FINISH CATALOG NUMBERACCESSORIES
O.B.D. - OPPOSED BLADE DAMPER
ALUM. E.C.L.
NOTES:
REFER TO
NOTE NO.SEE NOTE
EXT.
NO.UNIT
DESCRIPTION SERVICELB/HR
RUNOUTSUPPLY
RUNOUTCOND.
CFMRH(%)
ENTERING AIR
DB RH(%)
LEAVING AIR
DB RH(%)
ROOM
DB HEIGHT
FACE SIZE
WIDTHDISTANCE
ABSORPTIONREMARKS
- INCHES
GENERAL NOTES:
(INCLUDINGLOSS)
REMARKS
PR
E-H
EA
T C
OIL
LEAV. AIR
FACE AREA
HOUSING
PRESS. DROP IN. W.G. CLEAN
PR
E-F
ILT
ER
GPM - CONNECTION (QTY) SIZE
SENSIBLE MBH
TOTAL MBH
ENT. AIR DB/WB
LEAV. AIR DB/WB
AUTO. VALVE Cv & TYPE
MAX. WATER P.D.- FT.
MAX. AIR P.D.- INCHES W.G.
TYPE
CO
OLIN
G C
OIL
MIN. FACE AREA
MAX. AIR P.D. INCHES W.G.
WHEEL DIA.
WHEEL TYPE / CLASS
CAPACITY MBH
MOTOR (WATTS)
MIN. FACE AREA
TOTAL / EXT. S.P. - INCHES W.G.
ENT. AIR
SU
PP
LY
FA
N
GENERAL NOTES
UNIT LOCATION
AREA SERVED
UNIT NUMBER
UNIT CONFIGURATION
FACE AREA
HOUSING
PRESS. DROP IN. W.G. CLEAN
OUTSIDE AIR CFM
FIN
AL F
ILT
ER
TYPE
NOTES:
VIBRATION ISOLATORS
TOTAL SUPPLY CFM
PRESS. DROP IN. W.G. DIRTY
PRESS. DROP IN. W.G. DIRTY
UV LIGHTS
WINTER MIN. CFM
AIR SIDE ECONOMIZER
ECM PLENUM
BASIS OF DESIGN
GPM - CONNECTION (QTY) SIZE
AUTO. VALVE Cv & TYPE
MAX. WATER P.D.- FT.
APPROX. CONNECTED CFM
DISCHARGE
SUCTION &DESCRIPTION
UNIT
NO.
PERFORMANCE
GPMSERVICE
MOTOR
VOLTFT. HD. WATTS
MIN.
EFF.%PHASE MODEL NO.
GRUNDFOSSEE NOTE
NOTES:
MAX. WATER P.D.- FT.
AUTO. VALVE CV & TYPE
LEAV. AIR DB/WB
MAX. WATER P.D.- FT.
AUTO. VALVE CV & TYPE
ENT. AIR DB/WB
CO
OL
ING
CO
IL
FILTER
GPM
TOTAL MBH
COOLANT
SENSIBLE MBH
GPM
ENT. AIR
LEAV. AIR
HE
AT
ING
CO
IL
HEATING COIL CAPACITY BASED ON 130° ENT. WATER
COOLING COIL CAPACITY BASED ON 42° ENT. WATER
EXTERNAL S.P.-IN. W.G.
MOTOR H.P.
UNIT CONFIGURATION
SU
PP
LY
FA
N
CAPACITY MBH
CFM
UNIT NUMBER
AREA SERVED
UNIT LOCATION
GENERAL NOTES
VOLTAGE/PHASE
MINIMUM OUTSIDE AIR CFM
BASIS OF DESIGN
ARRANGEMENT
VFD
NOTES
NOTES:
1. PROVIDE WITH CONDENSATE PUMP EQUAL TO LITTLE GIANT MODEL # VCL-45ULS.
2. CONNECT CONDENSATE PUMP TO LOCAL 120V CIRCUIT. PROVIDE TOGGLE SWITCH DISCONNECT.
ELEC. SERVICE TO THREE-PHASE UNITSTOBE THREE-WIRE UNLESSNOTED
APPROX. CABINETDIMENSIONS
DEPTH
VERIFY/COORDINATE CABINET DIMENSIONS,MOUNTING
DESCRIPTION
AND RECESS REQUIREMENTS WITHARCHITECTURALDWGS. PRIOR TOORDERING.RECESSED UNITS TO HAVE FOUR(4) SIDEOVERLAP UNLESS OTHERWISENOTED
UNITNO.
GENERALNOTES:
BY GEN.CONT'R.
HEATING
LINTELS IN MASONRY WALLS FOR FULL&SEMI-RECESSED UNIT WALL OPENINGPROVIDED
THREE(3) PHASE COIL LOADS SHALL BEDIVIDEDEVENLY ACROSS EACHPHASE.
LOCATION CFMM.B.H.
ELEC.SERVICE
VOLTKW(MAX)KW(MIN) AMP LENGTHPHASE
REFERTONOTENO.HEIGHT RECESS
NOTES
1. BASIS OF DESIGN: TRANEUHEC
ELECTRIC UNITHEATER
4.0 3 14" 211.2400EUH-1 3.3 3.3 480 7" 17" -PROPELLERAHU-24
VESTIBULE
WHEEL DIA.
WHEEL TYPE / CLASS
MOTOR (WATTS)
TOTAL / EXT. S.P. - INCHES W.G.
RE
TU
RN
FA
N
TOTAL SUPPLY CFM
ECM PLENUM
APPROX. CONNECTED CFM
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
5/2
01
9 1
2:2
0:4
8 P
MC
:\B
IM\M
ode
l\20
19
-05
07
8-M
EP
-Ce
ntr
al_
ajg
ran
ata
@h
ea
py.c
om
.rvt
2019-05078
DTR
AJG
July 24, 2019
M002
MECHANICALSCHEDULES
1 2019.07.24 ADDENDUM 1
.
7
8 5
1
8
2 3 6 4 9
610
TO AIR DEVICES
MAIN SUPPLY DUCT
1. CONICAL SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE. INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR TAP FITTING TO MAIN SUPPLY DUCT W ITH INTERNAL INSULATION.
2. ROUND SHEET METAL BRANCH DUCT, SAME SIZE AS AIR TERMINAL UNIT INLET SIZE UNLESS NOTED OTHERW ISE.
3. HARD DUCT CONNECTION TO AIR TERMINAL UNIT. FLEX CONNECTION NOT PERMITTED.
4. AIR TERMINAL UNIT.5. M INIMUM FOUR HANGER RODS FOR UNIT (CORNER
POINTS). ATTACH TO STRUCTURE.
6. TRANSITION W HEN REQUIRED.7. M INIMUM STRAIGHT LENGTH OF DUCT SHALL BE
TERMINAL UNIT MANUFACTURER'S REQUIRED LENGTH, BUT AT LEAST 3 TIMES UNIT INLET DIAMETER.
8. DUCT HANGER. ATTACH TO STRUCTURE.9. DUCT SHALL BE FULL SIZE OF UNIT OUTLET UNLESS
NOTED OTHERW ISE ON FLOOR PLANS.10. REHEAT COIL W HEN SPECIFIED. REFER TO COIL DETAIL.
NOTES
SUPPLY DUCT
6
8
4 3 45 4
6
9
182
10
7
CEILING CEILING DIFFUSER
1. SQUARE-TO-ROUND ADAPTER IF DIFFUSER NECK IS SQUARE. CONNECT ADAPTOR TO DIFFUSER. SEAL TO AIR DEVICE, SEAL CLASS A. INSULATE ADAPTOR AND EXPOSED BACKSIDE SURFACES OF AIR DEVICE.
2. INSULATED FLEXIBLE DUCT SAME DIAMETER AS BRANCH DUCT , 7 FT. MAXIMUM TOTAL LENGTH PER AIR DEVICE. STRETCH FLEXIBLE DUCT TO AT LEAST 90% OF FULLY EXTENDED LENGTH.
3. SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE W ITH MANUAL DAMPER. DAMPER SHAFT IN HORIZONTAL. INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR TAP FITTING TO MAIN DUCT W ITH INTERNAL INSULATION, AND EXTENDED DAMPER SHAFT AND HANDLE W ITH STAND-OFF TO ACCOMMODATE EXTERNAL INSULATION.
4. DUCT STRAP HANGER. ATTACH TO STRUCTURE.5. STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE DUCT IS
LONGER THAN 4 FT.
6. M INIMUM CENTERLINE RADIUS EQUAL TO DUCT DIAMETER.7. ROUND SHEET METAL BRANCH DUCT, SAME SIZE AS
DIFFUSER INLET UNLESS NOTED OTHERW ISE.8. FLEXIBLE DUCT ELBOW SUPPORT, INSTALLED W ITH NYLON
BANDING PER MANUFACTURER'S INSTRUCTIONS.9. A RADIUS'D SHEET METAL ELBOW MAY BE USED IN LIEU OF
A FLEXIBLE ELBOW SUPPORT W HEN CONNECTED DIRECTLY TO AIR DEVICE.
10. CEILING T-BAR SUPPORT (FOR LAY-IN APPLICATIONS). COORDINATE AND VERIFY T-BAR TYPE FOR COMPATIBILITY W ITH DIFFUSER.
7
NOTES
5
CEILING CEILING DIFFUSER
37
5
2 6 4 1
8
SUPPLY DUCT
1. SHEET METAL BOX W ITH SAME INTERNAL OR EXTERNAL INSULATION AS MAIN SUPPLYDUCT, 2" LARGER EACH DIRECTION THAN DIFFUSER NECK, W ITH ADAPTOR CONNECTIONTO DIFFUSER. CONNECT PLENUM TO DIFFUSER. SEAL BOX AND ADAPTOR TO AIRDEVICE, SEAL CLASS A. INSULATE ADAPTOR AND BACKSIDE SURFACES OF AIR DEVICE.
2. INSULATED FLEXIBLE DUCT SAME DIAMETER AS BRANCH DUCT , 7 FT. MAXIMUMTOTAL LENGTH PER AIR DEVICE. STRETCH FLEXIBLE DUCT TO AT LEAST 90% OF FULLYEXTENDED LENGTH.
3. SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE W ITH MANUAL DAMPER. DAMPER SHAFT INHORIZONTAL. INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR TAP FITTING TOMAIN DUCT W ITH INTERNAL INSULATION, AND EXTENDED DAMPER SHAFT AND HANDLEW ITH STAND-OFF TO ACCOMMODATE EXTERNAL INSULATION.
4. SPIN-IN TAP FITTING SIMILAR TO EXCEPT NO DAMPER.
5. DUCT STRAP HANGER. ATTACH TO STRUCTURE.
6. STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE DUCT IS LONGER THAN 4 FT.
7. ROUND SHEET METAL BRANCH DUCT, SAME SIZE AS DIFFUSER INLET UNLESS NOTEDOTHERW ISE.
8. CEILING T-BAR SUPPORT (FOR LAY-IN APPLICATIONS). COORDINATE AND VERIFY T-BARTYPE FOR COMPATIBILITY W ITH DIFFUSER.
7
3
NOTES
ROUND SHEETMETAL BRANCH DUCT
BRANCH CFM RD. DUCT SIZE
0 TO 80 CFM 6"D
81 TO 120 CFM 7"D
121 TO 200 CFM 8"D
401 TO 700 CFM 12"D
701 TO 1000 CFM 14"D
201 TO 400 CFM 10"D
8CEILING RETURN OR EXHAUST GRILLE
55 3 57 6
10
9
119
4
1102RETURN OR EXHAUST DUCT
1. SHEET METAL PLENUM, FULL SIZE OF GRILLE NECK, M INIMUM 6" TALL W ITH SAME INTERNAL OR EXTERNAL INSULATION AS RETURN OR EXHAUST DUCT. CONNECT TO GRILLE. SEAL PLENUM AND CONNECTION TO GRILLE, SEAL CLASS A.
2. FLEXIBLE DUCT, SAME DIAMETER AS BRANCH DUCT , 3. 7 FT. MAXIMUM TOTAL LENGTH PER AIR DEVICE. STRETCH
FLEXIBLE DUCT TO AT LEAST 90% OF FULLY EXTENDED LENGTH.4. SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE W ITH MANUAL
DAMPER. DAMPER SHAFT IN HORIZONTAL. INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR TAP FITTING TO MAIN DUCT W ITH INTERNAL INSULATION. EXTENDED DAMPER SHAFT AND HANDLE W ITH STAND-OFF REQUIRED FOR EXTERNALLY INSULATED DUCTW ORK.
5. SPIN-IN TAP FITTING SIMILAR TO EXCEPT NO DAMPER.6. DUCT STRAP HANGER. ATTACH TO STRUCTURE.
6. STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE DUCT IS LONGER THAN 4 FT.
7. ROUND SHEET METAL BRANCH DUCT, SIZE AS INDICATED IN ADJACENT SCHEDULE UNLESS NOTED OTHERW ISE ON PLANS.
8. CEILING T-BAR SUPPORT (FOR LAY-IN APPLICATIONS). COORDINATE AND VERIFY T-BAR TYPE FOR COMPATIBILITY W ITH GRILLE.
9. M INIMUM CENTERLINE RADIUS EQUAL TO DUCT DIAMETER.10. FLEXIBLE DUCT ELBOW SUPPORT, INSTALLED W ITH NYLON
BANDING PER MANUFACTURER'S INSTRUCTIONS.11. A RADIUS'D SHEET METAL ELBOW MAY BE USED IN LIEU OF
A FLEXIBLE ELBOW SUPPORT W HEN CONNECTED DIRECTLY TO AIR DEVICE.
7
3
NOTES
ROUND SHEETMETAL BRANCH DUCT
BRANCH CFM RD. DUCT SIZE
0 TO 80 CFM 6"D
81 TO 120 CFM 7"D
121 TO 200 CFM 8"D
401 TO 700 CFM 12"D
701 TO 1000 CFM 14"D
201 TO 400 CFM 10"D
RETURN OR EXHAUST DUCT
8CEILING
RETURN OR EXHAUST GRILLE
14
625735
1. SHEET METAL PLENUM, FULL SIZE OF GRILLE NECK, M INIMUM 4" TALLER THAN DUCT RUNOUT SIZE, W ITH SAME INTERNAL OR EXTERNAL INSULATION AS RETURN OR EXHAUST DUCT, CONNECT TO GRILLE. SEAL PLENUM AND CONNECTION TO GRILLE, SEAL CLASS A.
2. FLEXIBLE DUCT, SAME DIAMETER AS BRANCH DUCT , 7 FT. MAXIMUM TOTAL LENGTH PER AIR DEVICE. STRETCH FLEXIBLE DUCT TO AT LEAST 90% OF FULLY EXTENDED LENGTH.
3. SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE W ITH MANUAL DAMPER. DAMPER SHAFT IN HORIZONTAL. INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR TAP FITTING TO MAIN DUCT W ITH INTERNAL INSULATION. EXTENDED DAMPER SHAFT AND HANDLE W ITH STAND-OFF REQUIRED FOR EXTERNALLY INSULATED DUCTW ORK.
4. SPIN-IN TAP FITTING SIMILAR TO EXCEPT NO DAMPER.5. DUCT STRAP HANGER. ATTACH TO STRUCTURE.6. STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE DUCT IS
LONGER THAN 4 FT.7. ROUND SHEET METAL BRANCH DUCT, SIZE AS INDICATED IN
ADJACENT SCHEDULE UNLESS NOTED OTHERW ISE ON PLANS.8. CEILING T-BAR SUPPORT (FOR LAY-IN APPLICATIONS).
COORDINATE AND VERIFY T-BAR TYPE FOR COMPATIBILITY W ITH GRILLE.
7
3
NOTES
6" M
AX
7CEILING RETURN OR EXHAUST GRILLE
3 1 3 2 3
64
5
RETURN OR EXHAUST DUCT
1. 45 DEGREE STATIC BOOT AND MANUAL DAMPER. INTEGRAL INSULATION GUARD SLEEVE REQUIRED W HEN MAIN DUCT HAS INTERNAL INSULATION. EXTENDED DAMPER SHAFT AND HANDLE W ITH STAND-OFF REQUIRED FOR EXTERNALLY INSULATED DUCTW ORK.
2. SHEET METAL DUCT, SIZE AS NOTED ON PLANS.3. DUCT STRAP HANGER.4. STATIC BOOT SIMILAR TO EXCEPT NO DAMPER.5. SHEET METAL DUCT, FULL SIZE OF GRILLE NECK SIZE. CONNECT AND SEAL
DUCT TO GRILLE, SEAL CLASS A.6. FLEXIBLE DUCT CONNECTOR.7. CEILING T-BAR SUPPORT (FOR LAY-IN APPLICATIONS). COORDINATE AND
VERIFY T-BAR TYPE FOR COMPATIBILITY W ITH GRILLE.
1
NOTES
GENERAL NOTES
NOTES
A. FIRE DAMPERS SHALL BE UL LABELED.
B. INSTALLATION OF FIRE DAMPERS AND ACCESSORIES SHALL CONFORM TO NFPA 90A, SMACNA AND MANUFACTURER'S INSTRUCTIONS.
C. DETAILS SHOW INSTALLATION OF FIRE DAMPER IN W ALL. DAMPER INSTALLATION IN FLOOR SIMILAR. COORDINATE REQUIRED ACCESS LOCATIONS.
D. INSULATE RETAINING ANGLES FOR SYSTEMS REQUIRED TO BE INSULATED.
1. FIRE DAMPER, FOLDED BLADE CURTAIN TYPE, EXCEPT AS NOTED. VERTICAL MOUNT, GRAVITY DROP; HORIZONTAL MOUNT,SPRING LOADED TO CLOSE. REFER TO SPECS FOR VELOCITY LIMITATIONS OF EACH TYPE. REFER TO DRAW INGS FOR STATIC OR DYNAMIC REQUIREMENTS.
TYPE "A" - BLADES STORED IN AIR STREAM. RECTANGULAR, ROUND OR OVAL DUCT CONNECTION.TYPE "B" - BLADES STORED OUT OF AIR STREAM. RECTANGULAR, ROUND OR OVAL DUCT CONNECTION.
2. SHEET METAL W ALL SLEEVE, SAME MATERIAL AS DUCT (EXCEPT GALVANIZED SHEET METAL FOR FIBERGLASS DUCT). SHEET METAL GAUGE PER SMACNA. USE EXTENDED HEAVY GAUGE SLEEVES W HEN INSTALLED CONDITION REQUIRES.
3. DUCT/SLEEVE CONNECTION. BREAKAW AY TYPE SHOW N. CONNECTION MAY BE RIGID TYPE IF ALLOW ED BY CODE AUTHORITY.
4. RETAINING ANGLE ALL FOUR SIDES, GAUGE PER SMACNA. 1" MIN IMUM OVERLAP OF W ALL OPENING. LONGER LEG MAY BE REQUIRED TO ATTAIN REQUIRED OVERLAP. BOLT, SCREW OR TACK W ELD TO W ALL SLEEVE. SPACING OF FASTENERS PER SMACNA.
5. DUCT ACCESS PANEL OR DOOR. REFER TO SPECIFICATIONS.
6. CEILING ACCESS PANEL IF CEILING IS NOT ACCESSIBLE.
7. RATED ACCESS PANEL NEAR FLOOR.
AIR FLOW
AIR FLOW
AIR
FL
OW
TURNING VANES
SEE FLOOR PLAN FOR SPLIT DIMENSION
MAIN SUPPLY DUCT
MANUAL VOLUME DAMPER
SUPPLY REGISTER ON BRANCH DUCT
SQUARE ELBOW SHOW N PROVIDE ROUND ELBOW W HEN SHOW N ON PLANS
AIR FLOW
AIR
FL
OW
W /4 OR 4" MIN.
MAIN SUPPLY DUCT
MANUAL VOLUME DAMPER
BRANCH DUCT
W
BRANCH DUCT TAKE-OFF
PLAN VIEW
AIR SPLIT DUCT TAKE-OFF
PLAN VIEW
THE BRANCH DUCT TAKE-OFF MAY BE USED FOR UP TO 15% OF THE MAIN DUCT CFM, AND UP TO 40% W HEN THE MAIN DUCT VELOCITY IS 1000 FPM OR LESS. THE AIR SPLIT DUCT TAKE-OFF SHALL BE USED IN ALL OTHER CASES
AIR FLOW
EQ
UIP
ME
NT
AIR FLOW
TYPICAL DUCTW ORK
TRANSITION W ITH EQUIPMENT
M OUNTED IN DUCT PLAN OR
SIDE VIEW
TYPICAL DUCTW ORK
TRANSITION PLAN OR SIDE
VIEW
NOTE:UNLESS OTHERW ISE INDICATED ON PLANS, MAXIMUM ANGLES SHOW N SHALL APPLY.
30 DEG. MAX.
AIR FLOW
15 DEG. MAX
15 DEG. MAX15 DEG. MAX.
30 DEG. MAX.
15 DEG. MAX.
CONCENTRIC TRANSITIONS UNLESSSHOW N OTHERW ISE ON PLANS
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
5/2
01
9 1
2:2
0:5
7 P
MC
:\B
IM\M
ode
l\20
19
-05
07
8-M
EP
-Ce
ntr
al_
ajg
ran
ata
@h
ea
py.c
om
.rvt
2019-05078
DTR
AJG
July 24, 2019
M003
MECHANICAL DETAILS
SCALE: NONE
AIR TERMINAL UNIT HARD DUCT CONNECTION1
SCALE: NONE
CEILING DIFFUSER DUCT CONNECTION4
SCALE: NONE
CEILING DIFFUSER DUCT CONNECTION5
SCALE: NONE
RETURN/EXHAUST GRILLE DUCT CONNECTION6
SCALE: NONE
RETURN/EXHAUST GRILLE DUCT CONNECTION7
SCALE: NONE
RETURN/EXHAUST GRILLE DUCT CONNECTION8
SCALE: NONE
FIRE DAMPER NOTES9
SCALE: NONE
SUPPLY DUCTWORK TAKE-OFFS14
SCALE: NONE
DUCTWORK TRANSITIONS16
1 2019.07.24 ADDENDUM 1
1. LOCATE STRAINER W ITH BLOW -DOW N VALVE AND HOSE CONNECTION AT LOW POINT OF COIL PIPING.
2. PIPE REDUCER IF REQUIRED.3. FULL RUN-OUT PIPE SIZE.4. INSULATE FIRST 6" NEXT TO COIL.5. 18" M INIMUM LONG BRAIDED STAINLESS STEEL FLEXIBLE PIPE
CONNECTOR.6. MAXIMUM DISTANCE FROM SUPPLY AND RETURN SHUT-OFF VALVES TO
COIL IS 48".7. FACTORY ASSEMBLED PIPING PACKAGE (OPTIONAL).8. LINE SIZE START-UP/FLUSHING BYPASS.9. OPTION 2 MAY ONLY BE USED W ITH A FACTORY PIPING PACKAGE THAT
IS FACTORY MOUNTED RIGIDLY TO THE TERMINAL UNIT.10. PIPING SAME SIZE AS AUTO CONTROL VALVE OR COIL CONNECTION,
W HICHEVER IS LARGER.
HW R
HW S
COIL
6
5 23
1
7
M
NOTES
18" MIN
18" MIN
48" MAX
A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT PIPING UNLESS NOTED OTHERW ISE.
B. REFER TO AIR TERMINAL UNIT SCHEDULE FOR AUTOMATIC CONTROL VALVE SIZE.
C. REFER TO SPECIFICATIONS FOR DEVICES NOT TO BE INSULATED. INSULATED DEVICES SHALL INCLUDE EXTENDED NECKS, SHAFTS, ETC... SO THEY ARE ACCESSIBLE ABOVE THE INSULATION.
GENERAL NOTES
N.C.
8
HW R
HW S
COIL
6
4
10
1
7
4
M
6" MIN
6" MIN
48" MAX
2N.C.8
OPTION 1
4
4
5
5
OPTION 2 9
1. AUTOMATIC TW O-PORT CONTROL VALVE. NORMALLY OPEN THRU COIL.
2. 0.5" DRAIN VALVE.3. PIPE REDUCER IF COIL CONNECTION
DIFFERS FROM PIPE SIZE.4. LEAVE W IDE OPEN UNLESS REQUIRED
TO BALANCE PUMP GPM.5. COIL RECIRCULATING PUMP.
A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT PIPING UNLESS NOTED OTHERW ISE.
B. REFER TO AIR HANDLING UNIT SCHEDULE FOR AUTOMATIC CONTROL VALVE SIZE.
HW
S
HW
R
AIR
FLOW
M1
4
3
5
3
2
NOTES
GENERAL NOTES
1. AUTOMATIC TW O-PORT CONTROL VALVE. NORMALLY CLOSED THRU COIL.
2. 0.5" DRAIN VALVE.3. PIPE REDUCER IF COIL CONNECTION DIFFERS
FROM PIPE SIZE.4. DRAIN PAN.5. DRAIN PIPE, SAME SIZE AS PAN CONNECTION,
W ITH DEEP SEAL TRAP. REFER TO CONDENSATE DRAIN PIPING DETAIL.
A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT PIPING UNLESS NOTED OTHERW ISE.
B. REFER TO AIR HANDLING UNIT SCHEDULE FOR AUTOMATIC CONTROL VALVE SIZE.
CH
R
CH
S
AIR
FLOW
D
M1
3
3
2
45
NOTES
GENERAL NOTES
1. STEAM MAIN (ABOVE 30 PSIG).2. COLLECTING POCKET AND DIRT LEG SAME SIZE AS MAIN.3. LENGTH FROM INVERT OF MAIN TO DRIP PIPE, 1.5 x MAIN
DIAMETER, 8" M INIMUM.4. THERMODYNAMIC STEAM TRAP, 0.75" SIZE UNLESS
NOTED OTHERW ISE.5. CONDENSATE RETURN, FULL SIZE OF TRAP DISCHARGE,
0.75" M INIMUM.6. 0.75" BY-PASS W ITH NORMALLY CLOSED GLOBE VALVE.7. 0.75" DRAIN VALVE W ITH HOSE CONNECTION.8. 0.75" TEST VALVE AND DRAIN W ITH HOSE CONNECTION.
6
54
1
3
2
N.C.
NOTES
TD
87
4" M
IN.
.
P
5 1
74
6 3 22
7
1. PUMP W ITH FLANGED CONNECTIONS.2. SPRING HANGER.3. PRESSURE GAUGE W ITH INTERCONNECTING PIPING
AND VALVES.4. BALANCING VALVE, S IZED FOR 3 TO 5 FT. HD. W PD AT
FULL PUMP GPM. PROVIDE REDUCERS IN AND OUT. FOR PUMPS FITTED W ITH AN ADJUSTABLE FREQUENCY MOTOR CONTROLLER LEAVE THE BALANCING VALVE FULL OPEN.
5. REDUCER W HEN PUMP CONNECTION SIZE DIFFERS FROM PIPE SIZE.
6. LEAVE SPACE TO ALLOW MOTOR TO BE PULLED.7. DRAIN VALVE W ITH HOSE CONNECTION.
TYPICAL - - TYPICAL
NOTES
NOTES
"a"
1. STEAM DISTRIBUTORS. SPACING, QUANTITIES, ETC. PER EQUIPMENT DATA.
2. F&T STEAM TRAP W HEN HUMIDIFIER MOUNTED IN DUCTW ORK ABOVE CEILINGS. BUCKET TRAP W HEN MOUNTED IN EXPOSED AREAS SUCH AS MECHANICAL ROOMS.
3. MOUNT STEAM SIDE STRAINER SUCH THAT STRAIN IS ON ITS SIDE IN A HORIZONTAL POSITION.
4. AUTOMATIC MODULATING CONTROL VALVE FURNISHED BY UNIT MANUFACTURER, PROVIDE MULTIPLE VALVE W HEN SPECIFIED.
5. HEAT EXCHANGER SOLENOID VALVE (ON/OFF).6. LINE SIZE AUTOMATIC 2-POSITION CONTROL VALVE
FOR SEASONAL OR SAFETY SHUT-OFF.7. EXTEND CONDENSATE RETURN PER PLANS.8. TEMPERATURE SW ITCH.9. TUBULETS PERPENDICULAR TO AIRFLOW .10. SHUT-OFF VALVE.11. W HEN D IMENSION "A" EXCEEDS 10 LINEAR FEET,
PROVIDE DRIP LEG AND TRAP ASSEMBLY PER ABOVE.
REFER TO TYPICALSTEAM DRIP ASSEMBLY
TO CONDENSATERETURN MAIN
REFER TO BELOW FORHUMIDIFIER PIPING
STEAM SUPPLY MAIN
CONDENSATE RETURN MAIN
STEAM SUPPLY MAIN
9
18
2
756
4
410 3
11
1. PIPE REDUCER IF COIL CONNECTION SIZE DIFFERS FROM PIPE SIZE.
2. MAXIMUM D ISTANCE FROM SHUT-OFF VALVE TO COIL IS 48".3. M INIMUM 18" LONG BRAIDED STAINLESS STEEL FLEXIBLE PIPE
CONNECTOR.4. FACTORY ASSEMBLED PIPING PACKAGE (OPTIONAL).
A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT PIPING UNLESS NOTED OTHERW ISE.
B. REFER TO EQUIPMENT SCHEDULE FOR AUTOMATIC CONTROL VALVE SIZE.
C. REFER TO SPECIFICATIONS FOR DEVICES NOT TO BE INSULATED. INSULATED DEVICES SHALL INCLUDE EXTENDED NECKS, SHAFTS, ETC. SO THEY ARE ACCESSIBLE ABOVE THE INSULATION.
M
COIL
2
4
1
NOTES
GENERAL NOTES48" MAX
3
3
1. PIPE REDUCER IF COIL CONNECTION SIZE DIFFERS FROM PIPE SIZE.2. 0.75" CONDENSATE DRAIN PIPE, CONNECT TO UNIT PAN W ITH
FLEXIBLE POLYETHYLENE TUBING.3. M INIMUM 18" LONG BRAIDED STAINLESS STEEL FLEXIBLE PIPE
CONNECTOR.4. FACTORY ASSEMBLED PIPING PACKAGE (OPTIONAL).
A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT PIPING UNLESS NOTED OTHERW ISE.
B. REFER TO EQUIPMENT SCHEDULE FOR AUTOMATIC CONTROL VALVE SIZE.
M
D UNIT DRAIN PAN
COIL DRAIN PAN
COIL
2
1
4
NOTES
GENERAL NOTES3
3
1. DRAIN PIPE SAME SIZE AS UNIT DRAIN PAN CONNECTION.
2. UNIT ROOF CURB. VERIFY REQUIRED HEIGHT FOR DRAIN PIPE AND TRAP INSTALLATION. PROVIDE CURB OF ADEQUATE HEIGHT TO ATTAIN REQUIRED DIMENSION.
3. TEE W ITH CLEANOUT PLUG.4. 1" CENTERLINE - TO - CENTERLINE
DIMENSION.5. CENTERLINE - TO - CENTERLINE DIMENSION
NOT LESS THAN SUPPLY FAN T.S.P. (INCH W .G.) + 1/2 INCH..
6. CENTERLINE - TO - CENTERLINE DIMENSION NOT LESS THAN SUPPLY FAN T.S.P. (IN W .G.) + 1 INCH.
7. CENTERLINE - TO - CENTERLINE DIMENSION SHALL BE 50% OF DIMENSION FOUND IN ABOVE.
8. SPLASH BLOCK.
3
NOTES
6
BLOW -THRU UNIT
DRAW -THRU UNIT
ROOFTOP UNIT
1
3
4
5
..
TRAP
1
3
6
7
..
28
ROOFTOP UNIT
3
TRAP
28
ROOF
ROOF
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
5/2
01
9 1
2:2
1:0
9 P
MC
:\B
IM\M
ode
l\20
19
-05
07
8-M
EP
-Ce
ntr
al_
ajg
ran
ata
@h
ea
py.c
om
.rvt
2019-05078
DTR
AJG
July 24, 2019
M004
MECHANICAL DETAILS
SCALE: NONE
DUCT HEATING COIL3
SCALE: NONE
A.H. UNIT HOT WATER COIL4
SCALE: NONE
A.H. UNIT CHILLED WATER COIL5
SCALE: NONE
31 TO 125 PSIG STEAM DRIP ASSEMBLY8
SCALE: NONE
PIPE MOUNTED PUMP9
SCALE: NONE
HUMIDIFIER PIPING DETAIL6
1 2019.07.24 ADDENDUM 1
SCALE: NONE
FAN COIL UNIT PIPING-HEATING COIL1
SCALE: NONE
FAN-COIL UNIT PIPING-COOLING COIL2
SCALE: NONE
ROOFTOP UNIT DRAIN PIPING7
NOTES
FAN DISCHARGE VIEW FAN INLET VIEW
1. T-FLANGE FRAME MOTORIZED ISOLATIONDAMPER.
2. ROOF SUPPORT CURBS, MIN. 14" HIGH. FLASH INTO
ROOFING SYSTEM.
3. EXHAUST STACK, SAME MATERIAL AS SYSTEMDUCTWORK. PRIME AND PAINT. SUPPORT DUCT FROM
4. FLEX CONNECTION.
5. BLIND FLANGE CONNECTION, SLOPED TO DRAINOUTLET.
6. 3/4" PVC DRAIN OUTLET TO SPILL ONTO CONCRETESPLASH BLOCK OR NEARBY ROOF DRAIN.
7. SUPPORT DUCT STACK FROM SCREEN WALL.
ROOF ROOF
EXHAUST FAN
DRAIN BAFFLE
EXHAUST FAN
LIGHTNING PROTECTION
3x WHEEL DIA.
22
6
5
3
7
4
2 1
4
2
8. INSULATE DUCT FROM EXHAUST FAN INLET TO 24"
BEYOND THE MOTORIZED DAMPER INSIDE THE BUILDING. EXTERIOR INSULATION SHALL BE JACKETED.
ADJACENT BUILDING WALL.
FASTENCURB
12" HIGHCURB.
FASTEN CURB TODECK
INSULATION
FASTEN TONAILER
METALDECK
TODECK.
STRUCTURAL FRAMING BYG.C.
NEWDUCT
INSULATE DUCT TO BELOWDECK
NEW FLASHING. SEALWATER-TIGHT AROUND DUCTPENETRATION.
PATCH INSULATION & ROOFINGTO SEAL WATERTIGHT FASTEN
CURB
12" HIGHCURB.
FASTEN CURB TODECK
INSULATION
FASTEN TONAILER
CONCRETEDECK
TODECK.
STRUCTURAL FRAMING BYG.C.
PIPING
PIPE INSULATION, REFER TOSPECIFICATION.
NEW FLASHING. SEALWATER-TIGHT AROUND DUCTPENETRATION.
PATCH INSULATION & ROOFINGTO SEAL WATERTIGHT
NOTES
RETURN OREXHAUST DUCT
FROM GENERAL RETURN/EXHAUST
1. CONICAL TEE FITTING.2. ROUND SHEET METAL BRANCH DUCT, SAME SIZE AS AIR
CONTROL VALVE INLET SIZE UNLESS NOTED OTHERW ISE.3. RETURN OR EXHAUST AIR CONTROL VALVE.4. STRAP HANGER. ATTACH TO STRUCTURE.5. TRANSITION W HEN REQUIRED.6. M INIMUM FOUR STRAP HANGERS FOR UNIT (CORNER POINTS).
ATTACH TO STRUCTURE.7. 6" W IDE 22 GAUGE DRAW BAND W ITH 5/16" THICK x 3/4" W IDE
DUCTMATE DM 440 GASKET TAPE (BUTYL RUBBER TAPE) INSTALLED PER VALVE MANUFACTURER'S INSTRUCTIONS.
8. SOUND ATTENUATOR, IF REQUIRED.
1
4 62 4 7 8
5 7 3 6
INTERNAL D IVIDER TOEQUALIZE VELOCITY ACROSS LOUVER
RETURN DUCT R ISER
MIDW AY IN LOUVER AND DUCT
FLOOR
NOTES
MAIN SUPPLY DUCT
TO AIR DEVICES
1. CONICAL TEE FITTING.2. ROUND SHEET METAL BRANCH DUCT, SAME SIZE AS AIR CONTROL VALVE INLET SIZE
UNLESS NOTED OTHERW ISE.3. HARD DUCT CONNECTION TO AIR TERMINAL UNIT. FLEX CONNECTION NOT PERMITTED.4. SUPPLY AIR CONTROL VALVE. EXTERNALLY INSULATE TO PREVENT SW EATING.5. STRAP HANGER. ATTACH TO STRUCTURE.6. TRANSITION W HEN REQUIRED.7. HOT W ATER REHEAT COIL. REFER TO REHEAT COIL PIPING DETAIL. INSULATE COIL.8. 6" W IDE 22 GAUGE DRAW BAND W ITH 5/16" THICK x 3/4" W IDE DUCTMATE DM 440
GASKET TAPE (BUTYL RUBBER TAPE) INSTALLED PER VALVE MANUFACTURER 'S INSTRUCTIONS.
9. SOUND ATTENUATOR, IF REQUIRED.10. PROVIDE 6"x6" LATCH ACCESS PANEL IN BOTTOM OF TRANSITION. REFER TO
SPECIFICATIONS.11. M INIMUM FOUR STRAP HANGERS FOR UNIT (CORNER POINTS). ATTACH TO
STRUCTURE.
1
5112 5 6 93
71084
8
BRANCH DUCT
PLAN VIEW
W
W /4 OR 4" M IN.
PROVID E MANUAL VOLUME DAMPER AT EACH BRANCH DUCT
MAIN EXHAUST OR RETURN AIR FLOW
45 DEG.
AIR
FLO
W
AIR FLOWLAG SCREW
W OOD NAILER
4"x4"x1/4" STEEL PLATE
INSULATION
ROOFING
CONCRETE DECK
1
23
4
1. PROVIDE COUNTER-FLASHING.2. HEAVY GAUGE CONTINUOUS SUPPORT
EXTENDS 6" BEYOND LAST EQUIPMENT LEG. SCREW ATTACHMENT TO DECK.
3. M INIMUM 12 INCHES.4. EXPANSION LAGS TO DECK.5. 18 / 24 / 36 INCH H IGH INSULATED STEEL CURB.
.
NOTES
5
1TYPE "A" -
DUCT
3" MIN3" MIN
FIRE RATED W ALL OR PARTITION
3
44
2
5
3
6
DUCT EXTENSION AT TOP OF DAMPER
DUCT
1TYPE "B" -
FIRE RATED W ALL OR PARTITION
5
3
6
3" MIN3" MIN
3
4 42
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
5/2
01
9 1
2:2
1:1
7 P
MC
:\B
IM\M
ode
l\20
19
-05
07
8-M
EP
-Ce
ntr
al_
ajg
ran
ata
@h
ea
py.c
om
.rvt
2019-05078
DTR
AJG
July 24, 2019
M005
MECHANICAL DETAILS
1 2019.07.24 ADDENDUM 1
SCALE: NONE
RETURN/EXHAUST AIR CONTROL VALVE DUCT CONNECTION1
SCALE: NONE
LOW RETURN AIR GRILLE3
SCALE: NONE
SUPPLY AIR CONTROL VALVE DUCT CONNECTION2
SCALE: NONE
EXHAUST OR RETURN BRANCH DUCTWORK4
SCALE: NONE
ROOF EQUIPMENT SUPPORT5
SCALE: NONE
FIRE DAMPER TYPE "A"6
SCALE: NONE
FIRE DAMPER TYPE "B"7
SCALE: NONE
UTILITY SET FAN8
SCALE: NONE
DUCT UTILITY CURB10
SCALE: NONE
PIPE UTILITY CURB11
ROOM PRESSURECONTROLLER
FLOW COMMAND TO RETURN
FLOW FEEDBACK FROM RETURN
FLOW COMMAND TO SUPPLY
FLOW FEEDBACK FROM SUPPLY
H
C
M
HWS
HWR
SUPPLY AIR
T
DISCHARGE AIR
TEMPERATURE
TERMINAL UNIT
CONTROLLER
M
REHEAT COILVALVE
H L
AIRFLOW
SENSOR
SUPPLY AIR FROM
AIR HANDLER
24 VAC
TERMINAL UNIT
CONTROLLER
24 VAC
24 VAC
24 VAC24 VAC
M
RETURN
24 VAC
NETWORK CABLE
NETWORK CABLE
SPACE SENSOR WITH
TEMPERATURE ADJUSTMENT,
OCCUPANCY OVERRIDE,
AND LCD DISPLAY
T
RPS
RPM
ROOM
PRESSUREMONITOR
PRESSURE
SENSOR
DS
DOOR
SWITCH
NETWORK CABLE
NETWORK CABLE
AIRFLOW
(+)
SA-2
SA-1
SA-3
SA-4
SA-5
SA-6
OS OCCUPANCY
SENSOR
(WHERE APPLICABLE)
(NON H.D. COMPOUNDING + ANTE ROOM)
(BASIS OF DESIGN: PRICE CRITICAL CONTROLS.REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS)
VENTURI AIR VALVE
H
HUMIDITY SENSOR LOCATED BEHIND THE RETURN GRILLES.HUMIDITY SENSORS SHALL BE AVERAGING BETWEEN THE FOUR ROOMS.
VENTURI AIR VALVE
HUMIDIFIER IN
DUCTWORK
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
5/2
01
9 1
2:2
1:2
0 P
MC
:\B
IM\M
ode
l\20
19
-05
07
8-M
EP
-Ce
ntr
al_
ajg
ran
ata
@h
ea
py.c
om
.rvt
2019-05078
DTR
AJG
July 24, 2019
M007
MECHANICALCONTROL
SCHEMATICS
1 2019.07.24 ADDENDUM 1
SCALE: NONE
CRITICAL CONTROL SCHEMATIC1
AIR HANDLING UNIT AHU - 24 POINTS LIST SCHEDULE
POINT NO.
TYPE
NOTES
POINT NAME
ALARM
AH-01 AH-02 AH-03 AH-04 AH-05 AH-06 AH-07 AH-08 AH-09 AH-10
AI
RE
TU
RN
AIR
TE
MP
ER
AT
UR
E
AH-11
HIG
H/L
OW
AIR HANDLING UNIT AHU - 24 ATC DIAGRAM
AI
NOTES:1. CURRENT SENSOR.2. COORDINATE W ITH VFD SUPPLIER.3. COORDINATE SMOKE DETECTION ALARM SIGNAL FROM FIRE ALARM SYSTEM. SMOKE DETECTOR BY DIV 26/28.4. IN ADDITION TO BEING A (BI) SAFETIES SHALL BE W IRED INTO THE FAN STARTERS/VFD(S) STARTER CIRCUIT SUCH THAT THE SAFETY SHALL FUNCTION W HETHER THE SELECTOR SW ITCH IS IN THE "HAND" OR "AUTOMATIC" POSITION.5. COORDINATE INTER-FACE CARD W ITH VFD SUPPLIER.
AI
HIG
H/L
OW
AH-12 AH-13 AH-14 AH-15 AH-16 AH-17
HIG
H/L
OW
AH-18
AI
HIG
H/L
OW
SCALE: NONE
FINAL FILTER
T
AH-28
SUPPLY AIR TEMPERATURE
AH-29
SAFETY SHUTDOW N
SP
AH-30
DUCT STATIC PRESSURE
SUPPLY AIR
SUPPLY FAN
AH-23
AIR FLOW STATION
VFD
AH-25
START/STOP
AH-26
DRIVE SPEED
AH-27
FAN FAULT
AH-24
FAN STATUS
COOLING COIL
AH-22
DRAIN PAN OVERFLOW
T
AH-20
H.C.L.A.T.
AH-19
FREEZE-STAT
PRE-HEAT COIL W L
AH-14
MIXED AIR TEMPERATURE
PR E- FILTER
AH-13
FILTER STATUS
OU TSIDE AIR
DPHL
AH-28
FILTER STATUS
DPHL
AH-12
AIR FLOW STATION
OUTSIDE AIR DAMPER
AH-33
AH-11
MIXED AIR DAMPER
RETURN AIR DAMPER
PSL
SAFETY SHUT-DOW N
AH-05
FIRE ALARM SMOKE
DETECTION
AH-04
H
RETURN AIR HUMIDITY
AH-02
T
AH-01
RETURN AIR TEMPERATURE
RETURN AIRRELIEF AIR
TO SERVICE VESTIBULE
AH-19 AH-20 AH-21 AH-22 AH-23 AH-24 AH-25 AH-26 AH-27 AH-28 AH-29
RE
TU
RN
AIR
HU
MID
ITY
AI BI
ON
TR
IPR
ETU
RN
AIR
F.A
. SM
OK
E
DE
TE
CTI
ON
3,4
BI
LOW
PR
ES
S.
SY
ST
EM
ALA
RM
4
RE
TU
RN
FA
N -
AIR
FLO
W
ME
AS
UR
ING
STA
TIO
N
BI
AD
JUS
TA
BLE
H
IGH
PR
ES
S.
PR
E -
FIL
TE
R S
TA
TU
S
RE
TU
RN
FA
N D
RIV
E S
PE
ED
AO
MIX
ED
AIR
DA
MP
ER
S
OU
TSID
E A
IR -
AIR
FLO
W
ME
AS
UR
ING
STA
TIO
N
MIX
ED
AIR
TE
MP
ER
AT
UR
E
AO BI
1
BI
4
FR
EE
ZE
-ST
AT
BOAO BI
ON
TR
IP
4
DR
AIN
PA
N O
VE
RF
LOW
SU
PP
LY F
AN
-A
IRFL
OW
M
EA
SU
RIN
G S
TATI
ON
BI
1
AI
HIG
H/L
OW
SU
PP
LY D
UC
T S
TA
TIC
PR
ES
SU
RE
UV
SY
ST
EM
-C
C
T T
LL
AFMSAFMS
HU
MID
IFIE
R S
HU
T-O
FF
VA
LVE
AH-33AH-31 AH-32AH-30
BI
PR
ES
SU
RE
SA
FE
TY
SH
UT
-DO
WN
RETURN FAN
AH-06
AIR FLOW STATION
AFMS
VFD AH-07
FAN STATUSAH-08
START/STOP
AH-09
DRIVE SPEED
AH-10
FAN FAULT
AH-31
RELIEF AIR DAMPER
RELIEF AIR DAMPER
AH-34
RE
LIE
F A
IR D
AM
PE
R
AOAI
HIG
H/L
OW
ON
FA
ILU
RE
BI
1
RE
TU
RN
FA
N S
TA
TU
S
RE
TU
RN
FA
N S
TA
RT
/ST
OP
BO
2
AO
RE
TU
RN
FA
N F
AU
LT
BI
ON
TR
IP
2
AI
HIG
H/L
OW
AI
HIG
H/L
OW
ON
FA
ILU
RE
BO
ON
TR
IP
BI
ON
FA
ILU
RE
2
AO
2
ON
TR
IP
AI
HIG
H/L
OW
BI
4
HIG
H P
RE
SS
. S
YS
TEM
ALA
RM
BO BO
H
L
L
H
AH-34
HUMIDIFIER
M
AH-35
HUMIDIFIER CONTROL VALVE
HUMIDIFIER ISOLATION VALVE
M
AH-35
AO
HU
MID
IFIE
R C
ON
TR
OL
VA
LVE
UV
M
AH-21
CHILLED W ATER CONTROL VALVE
MT
MS
AH-17
PUMP STATUS
AH-18
HOT W ATER PUMP START/STOP
AH-16
HOT W ATER CONTROL VALVE
AH-15
RETURN W ATER TEMPERATURE
BO
AH-36
UV
SY
ST
EM
-F
F
AH -36
UV
PSH
H
L
PR
ES
SU
RE
SA
FE
TY
SH
UT
-DO
WN
HO
T W
ATE
R C
OIL
RE
TU
RN
W
AT
ER
TE
MP
ER
AT
UR
E
HO
T W
AT
ER
CO
IL C
ON
TR
OL
VA
LVE
HO
T W
AT
ER
CO
IL P
UM
P S
TA
TU
S
HO
T W
ATE
R C
OIL
PU
MP
S
TAR
T/S
TOP
PR
EH
EA
T C
OIL
-LE
AV
ING
AIR
TE
MP
ER
AT
UR
E
CH
ILLE
D W
ATE
R C
OIL
CO
NT
RO
L V
ALV
E
SU
PP
LY F
AN
-S
TA
TU
S
SU
PP
LY F
AN
-S
TA
RT
/ST
OP
SU
PP
LY F
AN
-D
RIV
E S
PE
ED
SU
PP
LY F
AN
-F
AU
LT
SU
PP
LY A
IR -
TE
MP
ER
AT
UR
E
AH -32
RETURN FAN VFD INTER -
FACE
AH-37
SUPPLY FAN VFD INTER-FACE
AH-37
INTER-FACE
SU
PP
LY F
AN
VF
D IN
TE
R-F
AC
E
5
INTER-FACE
RE
TU
RN
FA
N V
FD
INT
ER
-FA
CE
5
SD
M
M
M
2 2
AI
AO
BI
BO
PI
OAT
MAT
RAT
SAT
CCAT
HCAT
OAHY
RAH
SAH
NC
NO
L
H
C
XX-01
LEGEND-AUTOMATIC
TEMPERATURE CONTROLS
CONTROL POINT - SEE POINTS SCHEDULE
ANALOG INPUT
ANALOG OUTPUT
BINARY INPUT
BINARY OUTPUT
PULSED INPUT
OUTSIDE AIR TEMPERATURE
MIXED AIR TEMPERATURE
RETURN AIR TEMPERATURE
SUPPLY AIR TEMPERATURE
COOLING COIL LEAVING AIR TEMPERATURE
HEATING COIL LEAVING AIR TEMPERATURE
OUTSIDE AIR HUMID ITY
RETURN AIR HUMIDITY
SUPPLY AIR HUMIDITY
NORMALLY CLOSED (CLOSES ON LOSS OF POW ER)
NORMALLY OPEN (OPENS ON LOSS OF POW ER)
LOW
HIGH
COMMON
2-W AY AUTOMATIC 2-POSITION CONTROL VALVE
3-W AY AUTOMATIC 2-POSITION CONTROL VALVE
2-W AY AUTOMATIC MODULATING CONTROL VALVE
3-W AY AUTOMATIC MODULATING CONTROL VALVE
DIFFERENTIAL PRESSURE SENSOR
DIFFERENTIAL PRESSURE SW ITCH
CARBON DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
CURRENT SENSOR TRANSMITTER
ELECTRONIC TO PNEUMATIC TRANSDUCER
FLOW METER TRANSMITTER
HUMIDITY SENSOR
LEVEL CONTROLLER
LEVEL TRANSMITTER
PRESSURE SENSOR
STATIC PRESSURE SENSOR
TEMPERATURE SENSOR
W ATER FLOW SENSOR
W ATER LEVEL SENSOR
CURRENT SW ITCH
END SW ITCH
FLOW SW ITCH
HUMIDISTAT
OCCUPANCY SENSOR
PRESSURE SW ITCH, HIGH LIMIT
PRESSURE SW ITCH, LOW LIMIT
TEMPERATURE LOW LIMIT (FREEZE STAT)
ROOM THERMOSTAT
AIR FLOW MEASURING STATION
VARIABLE FREQUENCY DRIVE (ADJUSTABLE FREQUENCY MOTOR CONTROLLER)
MOTOR STARTER
CONTACTOR
LOCAL TEMPERATURE CONTROL PANEL
PRESSURE SAFETY - H IGH
PRESSURE SAFETY - LOW
SMOKE DETECTOR
DAMPER OR VALVE ACTUATOR - MODULATING
DAMPER OR VALVE ACTUATOR - 2-POSITION
RELAY
UVGI LIGHT
PUMP
FAN
COOLING COIL
HEATING COIL
HUMIDIFIER
FILTER
ENERGY RECOVERY W HEEL
OPPOSED BLADE CONTROL DAMPER
PARALLEL BLADE CONTROL DAMPER
SMOKE DAMPER
MIN OA / ECON DAMPER
DX COIL
W ALL MOUNTED DEVICE
DUCT INSERTION DEVICE
PIPE INSERTION OR IMMERSION DEVICE W ITH W ELL
AVERAGING SENSOR OR DEVICE
OUTDOOR SENSOR OR DEVICE, SHIELDED
GENERAL NOTES-
AUTOMATIC TEMPERATURE CONTROLS
A A COMPLETE SYSTEM OF AUTOMATIC TEMPERATURE CONTROLS SHALL BE INSTALLED AS REQUIRED TO ACCOMPLISH THE SEQUENCE OF CONTROL FOR VARIOUS ITEMS OF EQUIPMENT AND SYSTEMS DESCRIBED HEREINAFTER. THE SYSTEM SHALL BE A DIRECT DIGITAL CONTROL SYSTEM UTILIZING ELECTRIC OR PNEUMATIC ACTUATION AS DEFINED IN THE SPECIFICATIONS.
B THE CONTROL DIAGRAMS AND INFORMATION CONTAINED W ITHIN ARE TO SHOW DESIGN INTENT. IT IS THE CONTROL SYSTEM SUPPLIERS RESPONSIBILITY TO DEVELOP DETAILED AND COMPLETE CONTROL DIAGRAMS AND SHOP DRAW INGS TO ACCOMPLISH THE SPECIFIED SEQUENCES.
C THE POINTS LIST IS SHOW N AS AN AID TO THE CONTRACTOR INDICATING THE MINIMUM POINTS REQUIRED FOR CONTROL, AND MONITORING. ALL INPUT AND OUTPUT POINTS, AND THEIR REQUIRED INTERFACE AND ACCESSORY HARDW ARE, SHALL BE PROVIDED FOR A COMPLETE AND FUNCTIONAL CONTROL SYSTEM. IF OR W HEN ADDITIONAL POINTS ARE REQUIRED TO ACCOMPLISH THE SEQUENCES OF CONTROL SPECIFIED , THESE POINTS, ALONG W ITH ADDITIONAL DIRECT DIGITAL CONTROL PANE(S) (IF REQUIRED), SHALL ALSO BE PROVIDED.
D BULB W ELLS FOR TEMPERATURE SENSING AS INDICATED SHALL BE PROVIDED BY THE HVAC CONTRACT. PIPING W ORK SHALL INCLUDE PROPERLY SIZED W ELDOLET OR THREADOLET FITTINGS PLACED AS DIRECTED BY THE CONTROL SYSTEM SUPPLIER.
E ELECTRICAL W ORK INCLUDES A POW ER SOURCE TO THE MOTOR STARTERS. PROVIDE ALL HVAC POW ER SOURCES REQUIRED BEYOND THESE STARTERS OR BEYOND SOURCES EXPLICITLY SHOW N ON THE ELECTRICAL DRAW INGS. THIS SHALL INCLUDE BUT NOT BE LIMITED TO W IR ING, CONDUIT, TRANSFORMERS, RELAYS AND FUSES.
M
M
M
M
DPHL
DPH
L
C
CO
CS
EPT
FM
H
LC
LT
P
SP
T
W F
W L
CS
ES
FS
H
OS
HLP
LLP
TLL
T
LEGEND-AUTOMATIC
TEMPERATURE CONTROLS
AFMS
VFD
MS
CON
TCP
SD
M
M
SD
X
X
X
X
X
X
X
X
X
X
R
M M
MINECON
R
UV
PSH
PSL
SP
AH-03
H
L
HIG
H/L
OW
RE
TU
RN
DU
CT
ST
AT
IC P
RE
SS
UR
E
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
5/2
01
9 1
2:2
1:3
1 P
MC
:\B
IM\M
ode
l\20
19
-05
07
8-M
EP
-Ce
ntr
al_
ajg
ran
ata
@h
ea
py.c
om
.rvt
2019-05078
DTR
AJG
July 24, 2019
M008
MECHANICALCONTROL
SCHEMATICS
1 2019.07.24 ADDENDUM 1
SCALE: NONE
AIR HANDLING UNIT 24 ATC DIAGRAM1
PTD
SD
T
T
T
T
T
T
T
T
2
M 301
1
1
1
1
1
1
1
3
3
1
3
3
3
3
3
3
2
2
2
2
2
2
2
2
2
2
2
2
2
222
2
2
2
2
2
2
2
4
4
4
4
4
4
4
4
5
5
5
5
5
5
5
5
5
6
6 8
8
8
7
7
7
7
7
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
5/2
01
9 1
2:2
1:4
4 P
MC
:\B
IM\M
ode
l\20
19
-05
07
8-M
EP
-Ce
ntr
al_
ajg
ran
ata
@h
ea
py.c
om
.rvt
2019-05078
DTR
AJG
July 24, 2019
M101
PARTIAL FIRST FLOORPLAN - DEMOLITION
1 2019.07.24 ADDENDUM 1
SCALE: 1/4" = 1'-0"
PARTIAL FIRST FLOOR PLAN - DEMOLITION1
NOTES
1. REMOVE EXISTING FAN COIL UNIT AND ALL ASSOCIATED DUCTW ORK, PIPING,AND CONTROL W IR ING.
2. REMOVE EXISTING AIR DEVICE AND ASSOCIATED DUCTW ORK AS INDICATED.
3. REMOVE EXISTING THERMOSTAT AND ALL ASSIOCIATED CONTROL W IRING.
4. REMOVE EXISITING PIPING AS INDICATED. CAP AND SEAL W ATERTIGHT.
5. REMOVE EXISTING DUCTW ORK AS INDICATED. CAP AND SEAL AIRTIGHT.
6. EXISTING DUCTW ORK TO REMAIN.
7. EXISTING PIPING TO REMAIN.
8. EXISTING AIR DEVICE TO REMAIN. REFER TO NEW W ORK FOR REBALANCING.
1314
LOCK.
38
PTD
SD
T
T
T
T
T
T
T
T
T
T
2
M 301
R
18x10
18x8
20x12
16x6
24x14
12x6
24x10
10ø
10ø
8ø
10x10
14x10
8øA1
150 CFM
8øA1
150 CFM
8øA1
150 CFM
8ø
10øA1
235 CFM
8øA1
150 CFM
7ø
6ø
6øA1
50 CFM
24x1250 CFM
J1
6øA1
100 CFM
24x12150 CFM
J1
3" - CHS
3" - HW S1.25" - CHR
8øA1
150 CFM
7ø
7ø
6ø
6ø
24x12100 CFM
J1
14x14
24-03A
24-03B24-04B24-04A
24-03A
24-02A
24-01A
24-01B
24-02B
18x8
22x6
24x8
1-05
1-04B
1-04A
1-03
1-01
1-02
1
4
3
2
TYP.5
5
5
5
6
6
6
6
6
235
560
560
650
400
7
8
8
8
8
9
9
9
9
10
14x10
8øA1
225 CFM
55
1095
10215
10110
12x8
8x4
10105
8x4
24x6
24x8
8ø
10øA1
235 CFM
10øA1
230 CFM
24x12225 CFM
J1
14x1
0
10x8
12x12
18x8 20x8
16x812x4
10x6
12 10012100
1275
24x6
11
14x6
18x8
14x10
12x12
18x8
1-01
1537A
BULK
STORAGE
1547
ADA STAFF
TOILET
1546OFC
1545MGR. OFC
1544
ORDER
ENTRY
OFC
1543IV RM
1542AHVAC
1541CHEMO RM
1542ANTI RM
1540
HD
NON-STERILE
1539NARC RM
1538POP
1535CORR.
1533JAN
1537
ORDER
ENTRY
1-02
1-03
24x12300 CFM
J1
24x12300 CFM
J1
1-04B
1-04A
6øA1
100 CFM24x12
100 CFM
J1
24x12120 CFM
J1 6øA1
120 CFM
10x8
24x1
0
1-05
12x1285 CFM
K1
24x12200 CFM
K1
10øA2
380 CFM10øA2
380 CFM10øA2
380 CFM10øA2
380 CFM
24-01A 8øA2
255 CFM
8øA2
255 CFM
24-02A
8øA2
200 CFM
24-04A
10øA2
300 CFM
24-03A
20x12 14x14
13 13
COURTYARD
6ø
0.75
" -
D
0.75" - D 1" - D 1.25" - D
1.25
" -
D
0.75" - D
40x12
44x1
0
1.5" -
CHS
1" -HW
S
1.5" -
CHR
1" -HW
R
3" - CHS2" - HW S
1.5" - CHR
1.5" - HW R
3" - CHS3" - HW S
2" - CHR
1.5" - HW R
1.25" - CHS
0.75" - HW S1.25" - CHR
0.75" - HW R
0.75" - HW R
1.25
" -
HW
R
1 .25" - HW S
1.5" - CHR
1070
6ø
8x8
2.5" - HW R2.5" - HW S
0.75" - LPC
0.75" - LPS3" - CHR3" - CHS14
18x10
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
5/2
01
9 1
2:2
2:0
9 P
MC
:\B
IM\M
ode
l\20
19
-05
07
8-M
EP
-Ce
ntr
al_
ajg
ran
ata
@h
ea
py.c
om
.rvt
2019-05078
DTR
AJG
July 24, 2019
M201
PARTIAL FIRST FLOORPLAN - NEW W ORK
1 2019.07.24 ADDENDUM 1
SCALE: 1/4" = 1'-0"
PARTIAL FIRST FLOOR PLAN - NEW WORK1
1. PROVIDE W ALL MOUNTED ROOM PRESSURE MONITOR ON W ALL, PROVIDE LABEL THAT THIS SERVES ANTE ROOM. MONITOR SHALL BE SIEMENS RPM OR APPROVED EQUAL PER SPECIFICATIONS. THRU-THE-W ALL ROOM PRESSURE SENSORS SHALL BE MOUNTED ABOVE THE DOOR. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. ROOM PRESSURE CONTROLS SHALL BE PROVIDED BY ATC TO MAINTAIN THE ANTE ROOM AT A MINIMUM OF +0.02" POSITIVE W ITH RESPECT TO PHARMACY.
2. PROVIDE W ALL MOUNTED ROOM PRESSURE MONITOR ON W ALL, PROVIDE LABEL THAT THIS SERVES IV ROOM. MONITOR SHALL BE SIEMENS RPM OR APPROVED EQUAL PER SPECIFICATIONS. THRU-THE-W ALL ROOM PRESSURE SENSORS SHALL BE MOUNTED ABOVE THE DOOR. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. ROOM PRESSURE CONTROLS SHALL BE PROVIDED BY ATC TO MAINTAIN THE IV ROOM AT A MINIMUM OF +0.02" TO +0.05" POSITIVE W ITH RESPECT TO ANTE ROOM..
3. PPROVIDE W ALL MOUNTED ROOM PRESSURE MONITOR PROVIDE LABEL THAT THIS SERVES CHEMO ROOM. MONITOR SHALL BE SIEMENS RPM OR APPROVED EQUAL PER SPECIFICATIONS. THRU-THE-W ALL ROOM PRESSURE SENSORS SHALL BE MOUNTED ABOVE THE DOOR. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. ROOM PRESSURE CONTROLS SHALL BE PROVIDED BY ATC TO MAINTAIN THE CHEMO ROOM AT A MINIMUM OF -0.01" TO -0.03" NEGATIVE W ITH RESPECT TO ANTE ROOM.
4. PROVIDE W ALL MOUNTED ROOM PRESSURE MONITOR PROVIDE LABEL THAT THIS SERVES NON STERILE ROOM. MONITOR SHALL BE SIEMENS RPM OR APPROVED EQUAL PER SPECIFICATIONS. THRU-THE-W ALL ROOM PRESSURE SENSORS SHALL BE MOUNTED ABOVE THE DOOR. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. ROOM PRESSURE CONTROLS SHALL BE PROVIDED BY ATC TO MAINTAIN THE HD NON STERILE ROOM AT A MINIMUM OF -0.01" TO -0.03" NEGATIVE W ITH RESPECT TO PHARMACY ROOM.
5. CEILING MOUNTED SUPPLY DIFFUSERS SHALL BE FURNISHED BY OTHERS, INSTALLED BY H.C. H.C. SHALL CONNECT AIR DEVICES INTO SUPPLY DUCT SHOW N FROM AIR VALVE AS INDICATED. BALANCE TO CFM INDICATED.
6. LOW EXHAUST/RETURN GRILLE TO BE FURNISHED BY OTHERS, INSTALLED BY H.C. H.C. SHALL EXTEND DUCTW ORK AS NEEDED IN CHASE TO CONNECT TO LOW GRILLE. BALANCE TO CFM INDICATED..
7. DROP 8" EXHAUST DUCT AND CONNECT TO MIC SINGLE HOOD. PER MANUFACTURER, DROP 4" DUCT TO 4-6" PERPENDICULAR FROM THE CEILING AND THE EXHAUST SIDE OF THE MIC FIELD INSTALLATION KIT W ILL ATTACH VIA A FLEX HOSE. BALANCE VALVES (INTAKE AND EXHAUST) AS REQUIRED TO ACHIEVE THE PROPER FLOW , REFER TO MANUFACTURER'S LITERATURE FOR MORE INFORMATION.
8. ROOM SHALL BE SEALED UP TIGHTLY. CAULK ALL PENETRATIONS INTO AND OUT OF W ALLS AND CEILINGS. PROVIDE GASKETED ACCESS DOORS AS REQUIRED IN CEILINGS TO ACCESS JUNCTION BOXES, EQUIPMENT, VALVES, ETC. COORDINATE W ITH OW NER.
9. KEEP ALL NEW EQUIPMENT, VALVES, ETC. ABOVE LAY-IN CEILING AS INDICATED TO REDUCE NUMBER OF ACCESS PANELS REQUIRED IN THE COMPOUNDING ROOMS.
10. OUTSIDE AIR DUCT TO CONNECT TO RETURN DUCT. BALANCE TO CFM INDICATED.
11. CONDENSATE DRAIN SHALL DISCHARGE TO MOP SINK IN JANITOR'S CLOSET.
12. RE-BALANCE EXISTING AIR DEVICE TO CFM INDICATED.
13. DUCT SHALL RISE UP EXTERIOR BUILDING W ALL TO ROOF ABOVE. REFER TO M301 FOR CONTINUATION.
14. PIPING RISE TO AIR HANDLER ON ROOF ABOVE. REFER TO SHEET M301 FOR CONTINUATION.
NOTES
A. ELECTRONIC COORDINATION DRAW INGS ARE REQUIRED AND MUST BE SUBMITTED TO THE ENGINEER FOR REVIEW PRIOR TO BEGINNING NEW W ORK. REFER TO 23 05 01.
GENERAL NOTES
5
8
13
14
20x14
14x14AHU-24
14ø
20x1
4
14ø EF-92
6' - 0"
6' - 0"
5' -
0"
EUH-1
P-24
1
2
3
45
6
77
12
10
10ø
9
TYP.11
8
EX.EF
COURTYARD
13
2.5" - HW S
0.75" - LPS0.75" - LPC
3" - CHS
2.5" - HW R
3" - CHR
Level 10' - 0"
Level 29' - 9"
24x14
8x8
8x8
24-04B 24-03B 24-03A24-02B
24-01A
24-04A24-02A
24-03A
18x10
14x14
IV ROOM
24x1
4
8' -
0"
24-01B
12x1
0
TYP.1
TYP.2
TYP.3
4
1
2
3
4
5 6 7 8 9
10
11
12
1. RETURN FAN SECTION.2. RELIEF AIR DAMPER.3. OUTSIDE AIR DAMPER W ITH HOOD.4. AIR BLENDER SECTION.5. SIDE LOADING FILTER SECTION.6. HOT W ATER COIL SECTION.7. HUMIDIFIER SECTION.8. CHILLED W ATER COIL SECTION.9. ACCESS SECTION.10. SUPPLY FAN SECTION.11. SIDE LOADING FILTER SECTION.12. SERVICE CORRIDOR SECTION.13. ELECTRIC UNIT HEATER LOCATION. REFER TO ROOF PLAN14. COIL CIRCULATING PUMP (P-24) LOCATION. REFER TO ROOF PLAN.15. RELIEF LOUVER W ITH BACKDRAFT DAMPER.16. ACCESS DOOR.17. RETURN DUCT CONNECTION.18. SUPPLY DUCT CONNECTION.19. HEAT TRACE PANEL LOCATION. REFER TO ROOF PLAN.20. UVGI CONTROL PANEL LOCATION. REFER TO ROOF PLAN.
NOTES
1314
1516
TYP.1718
19
20
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
5/2
01
9 1
2:2
2:1
6 P
MC
:\B
IM\M
ode
l\20
19
-05
07
8-M
EP
-Ce
ntr
al_
ajg
ran
ata
@h
ea
py.c
om
.rvt
2019-05078
DTR
AJG
July 24, 2019
M301
HVAC ROOF
1 2019.07.24 ADDENDUM 1
SCALE: 1/8" = 1'-0"
HVAC ROOF PLAN1
NOTES - HVAC ROOF PLAN
1. AIR HANDLING UNIT MOUNTED ON STEEL STRUCTURE. COORDINATE EXACT LOCATION W ITH STRUCTURAL DRAW INGS. OUTSIDE AIR OPENING MUST BE MINIMUM 25'-0" AW AY FROM ANY EXHAUST OR VENTS.
2. PIPING RISES THROUGH ROOF FROM FLOOR BELOW . ALL EXTERIOR PIPING SHALL BE HEAT TRACED. PIPING RISES INTO AHU SERVICE VESTIBULE THROUGH THE FLOOR OF THE UNIT..
3. DASHED LINES INDICATE 25'-0" CLEARANCE FROM EXHAUST FANS ON THE ROOF. DO NOT LOCATE OUTSIDE AIR OPENING FROM AIR HANDLER INSIDE THIS CIRCLE.
4. MECHANICAL SERVICE PLATFORM. REFER TO STRCTURAL AND ARCHITECTURAL DRAW INGS.
5. SUPPLY DUCT SHALL DROP THROUGH SERVICE PLATFORM GRATING SO A 3'-0" W IDE PATH CAN BE MAINTAINED TO GET PAST THE DUCT.
6. PROVIDE EXHAUST STACK, REFER TO UTILITY SET FAN DETAIL.
7. DUCTW ORK DROPS ALONG THE EXTERIOR W ALL INTO THE COURTYARD BELOW . REFER TO SHEET M201 FOR CONTINUATION.
8. ACCESS LADDER TO SERVICE PLATFORM.
9. ROOF ACCESS DOOR, REFER TO ARCHITECTURAL PLANS.
10. RE-W ORK EXISTING 10" ROUND DUCTW ORK TO AVOID CONFLICT W ITH NEW DUCTW ORK. RE-INSULATE TO MATCH EXISTING.
11. DUCT SUPPORT CURBS. SPACE PER MANUFACTURER 'S RECOMMENDATIONS.
12. EXISTING BUILD ING STEEL ABOVE ROOF.
13. EXHAUST FILTER HOUSING CONTAINING 2" MERV 8 FILTER AND 12" HEPA FILTER IN SERIES. FILTERS SHALL BE 20"X20" OR EQUIVALENT SQUARE FOOTAGE. HOUSING SHALL BE EQUAL TO CAMFIL GLIDEPACK.
SCALE: 1/4" = 1'-0"
MECHANICAL ROOM SECTION2
SCALE: 1/4" = 1'-0"
AHU DETAIL3
NOTES - MECHANICAL ROOM SECTION
1. EXHUAST DUCT HIGH.
2. RETURN DUCT HIGH.
3. SUPLLY DUCT LOW .
4. EXHAUST FAN VFD.
FIRE ALARM SYMBOLS
ELECTRICAL SYMBOLS
EXISTING OUTLET OR DEVICE TO REMAIN. MAINTAIN EXISTING CIRCUITING.
DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS W HERE REQUIRED.
ELECTRICAL CONNECTION.
20A-125V HOSPITAL GRADE DUPLEX RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERW ISE).
20A-125V HOSPITAL GRADE SINGLE RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERW ISE).
HOSPITAL GRADE SPECIAL PURPOSE RECEPTACLE. REFER TO NOTE ON PLAN.
20A-125V HOSPITAL GRADE DOUBLE DUPLEX RECEPTACLE. NEMA 5-20R, (18" MH UNLESS NOTED OTHERW ISE) TW O GANG ASSEMBLY.
20A-125V HOSPITAL GRADE DUPLEX RECEPTACLE, NEMA 5-20R W ITH BOTTOM OUTLET CONTROLLED BY W ALL SW ITCH. (18" MH UNLESS NOTED OTHERW ISE).
20A-125V HOSPITAL GRADE DUPLEX RECEPTACLE, NEMA 5-20R, W ITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED OTHERW ISE).
20A-125V W EATHERPROOF HOSPITAL GRADE DUPLEX RECEPTACLE, NEMA 5-20R (HORIZONTAL 18" MH UNLESS NOTED OTHERW ISE) W ITH TAYMAC #10310 STANDARD COVER, VERTICAL MOUNT.20A-125V W EATHERPROOF HOSPITAL GRADE DUPLEX RECEPTACLE, NEMA 5-20R W ITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED OTHERW ISE), W ITH TAYMAC #20310 STANDARD COVER, VERTICAL MOUNT.
POKE-THROUGH W ITH POW ER AND DATA.
JUNCTION BOX. SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POW ER.
MULTI-OUTLET RECEPTACLES ASSEMBLY, NEMA 5-15R (SINGLE OUTLETS ON 18" CENTERS) (46" MH UNLESS NOTED OTHERW ISE).
SPECIFICATION GRADE SINGLE POLE SW ITCH (46" MH UNLESS NOTED OTHERW ISE).
SPECIFICATION GRADE MULTI-W AY W ALL SW ITCH, # INDICATES NUMBER OF W AYS (46" MH UNLESS NOTED OTHERW ISE).
SPECIFICATION GRADE KEY OPERATED W ALL SW ITCH (46" MH UNLESS NOTED OTHERW ISE).
0-10V DC SPECIFICATION GRADE LIGHTING DIMMER SW ITCH (46" MH UNLESS NOTED OTHERW ISE)
DISCONNECT SW ITCH.
MOTOR STARTER.
COMBINATION MOTOR STARTER AND DISCONNECT SW ITCH.
ELECTRIC MOTOR.
ELECTRICAL PANEL OR SW ITCHBOARD PER DRAW INGS.
POW ER POLE.
CEILING MOUNTED OCCUPANCY SENSOR.
W ALL MOUNT SPEAKER & SIGNAL LIGHT (W HITE FINISH), (# W HEN SHOW N INDICATES CANDELA RATING OF STROBE. W HEN A # IS NOT SHOW N, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS & 30 CANDELA FOR ALL OTHER LOCATIONS.
W ALL MOUNT SIGNAL LIGHT (W HITE FINISH), (# W HEN SHOW N INDICATES CANDELA RATING OF STROBE. W HEN A # IS NOT SHOW N, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS & 30 CANDELA FOR ALL OTHER LOCATIONS.
FIRE ALARM MANUAL STATION (46" MH UNLESS NOTED OTHERW ISE).
CEILING MOUNTED SMOKE DETECTOR.
ELECTRO-MAGNETIC DOOR HOLDER.
W ATER FLOW SW ITCH.
VALVE SUPERVISORY SW ITCH.
PUSHBUTTON (46" MH UNLESS NOTED OTHERW ISE) EDW ARDS 852 (120 VOLT).
GF
W P
W P/GF
J
#
K
D
PP
OS
F15
15
F
S
D
FS
V
ADDRESSABLE MODULE. SUBSCRIPT "I" IND ICATES INPUT. SUBSCRIPT "C" INDICATES CONTROL.AMC/I
FIRE ALARM CONTROL PANEL.
20A-125V HOSPITAL GRADE DUPLEX RECEPTACLE, NEMA 5-20R (46" MH UNLESS NOTED OTHERW ISE).
FACP
SPECIFICATION GRADE LOW -VOLTAGE MOMENTARY W ALL SW ITCH (46" MH UNLESS NOTED OTHERW ISE).L
SECURITY SYMBOLS WITH ELECTRICAL REQUIREMENTS
EL ELECTRONIC DOOR LOCK. PROVIDE ROUGH-IN. REFER TO GENERAL NOTE.
ES ELECTRONIC STRIKE. PROVIDE ROUGH-IN. REFER TO GENERAL NOTE.
HD HANDICAP DOOR OPERATOR MOTOR ASSEMBLY. PROVIDE ROUGH-IN. REFER TO GENERAL NOTE.
HA W ALL/PEDESTAL MOUNT HANDICAP DOOR ACTUATOR BUTTON. PROVIDE ROUGH-IN. REFER TO GENERAL NOTE.
CRW ALL MOUNTED PROXIMITY CARD READER (46" MH UNLESS NOTED OTHERW ISE). PROVIDE ROUGH-IN. REFER TO GENERAL NOTE.
KW ALL MOUNTED SECURITY KEYPAD ENTRY STATION (46" MH UNLESS NOTED OTHERW ISE). PROVIDE ROUGH-IN. REFER TO GENERAL NOTE.
PP WW ALL MOUNTED PANIC /DURESS BUTTON (46" MH UNLESS NOTED OTHERW ISE). PROVIDE ROUGH-IN. REFER TO GENERAL NOTE.
TECHNOLOGY SYMBOLS WITH ELEC. REQUIREMENTS
P W ALL MOUNTED PHONE OUTLET (46" MH UNLESS NOTED OTHERW ISE). PROVIDE ROUGH-IN. REFER TO GENERAL NOTE.
CONDUIT SLEEVE / FIRE RATED SLEEVE ASSEMBLY THRU W ALL (1-2" SLEEVE UNLESS NOTED OTHERW ISE) PER DIV 26.
D W ALL MOUNTED VOICE/DATA OUTLET (18" MH UNLESS NOTED OTHERW ISE). PROVIDE ROUGH-IN. REFER TO GENERAL NOTE.
ABBREVIATIONS
AAP - AREA ALARM PANEL - MEDICAL GASALT - ALTERNATEARCH - ARCHITECT OR ARCHITECTURALATS - AUTOMATIC TRANSFER SW ITCH
CM - COFFEE MAKERCORR - CORRIDOR
D - DEPTHDIA - DIAMETERDIM - DIMENSIONDIV - DIVISIONDN - DOW NDW G - DRAW ING
EC - ELECTRICAL CONTRACTOR (DIVISION 26)ELEC - ELECTRICALELEV - ELEVATION OR ELEVATOREM - EMERGENCYEQUIP - EQUIPMENTE - EXISTING TO REMAINE/R - EXISTING TO BE RELOCATED
FSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)FT - FEET
GC - GENERAL CONTRACTORGF - GROUND FAULT CIRCUIT INTERRUPTERGFCI - GROUND FAULT CIRCUIT INTERRUPTER
HC - HVAC CONTRACTOR (D IVISION 23)HP - HORSE POW ERHVAC - HEATING, VENTILATING, AND AIR CONDITIONING
L - LENGTHLBS - POUNDS
MAP - MASTER ALARM PANEL (MEDICAL GAS)MAX - MAXIMUMMH - MOUNTING HEIGHT TO CENTER LINE OF ITEMMIN - MINIMUMMTD - MOUNTEDMW - MICROW AVE
NIC - NOT IN CONTRACTNTS - NOT TO SCALE
PC - PLUMBING CONTRACTOR (DIVISION 22)PLBG - PLUMBINGPR - PRINTER
REF - REFRIGERATOR
S - SURFACE MOUNTEDSH - SHREDDERSPEC - SPECIFICATIONSSQ - SQUARE
TEMP - TEMPERATURETV - TELEVISION/MONITORTYP - TYPICAL
UCR - UNDERCOUNTER REFERIGERATOR
VFD - VARIABLE FREQUENCY DRIVE
W P - W EATHERPROOF
ZVC - ZONE VALVE CABINET
1
E2
B
E2DETAIL: B = DETAIL DESIGNATION
E2 = SHEET W HERE DETAIL IS LOCATED
SECTION: 1 = SECTION DESIGNATION E2 = SHEET W HERE SECTION IS LOCATED
PLAN NOTE. APPLIES ONLY TO THE SHEET W HICH IT IS SHOW N.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
GENERAL FLOOR PLAN NOTES
EACH ARROW HEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL NAME; NUMBER(S) DENOTES CIRCUIT(S).
X - 1,2
3
3
LUMINAIRE SYMBOLS
LIGHTING FIXTURE. CAPITAL LETTER DENOTES FIXTURE TYPE, LOW ER CASE LETTER DENOTES SW ITCHING ARRANGEMENT.
LIGHTING FIXTURE ON CRITICAL CIRCU IT.
EXIT LIGHTING FIXTURE, ARROW S AS INDICATED.
Aa
3
3
20A-125V HOSPITAL GRADE DUPLEX RECEPTACLE, NEMA 5-20R W ITH 2 INTEGRAL USB CHARGERS (18" MH UNLESS NOTED OTHERW ISE).
NOTE:
• ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT
TO MODIFICATIONS ON OTHER DRAWINGS.
• ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT
NECESSARILY BE USED ON THIS PROJECT.
LIGHTING FIXTURE ON LIFE SAFETY AND NIGHT LIGHT.
SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POW ER. SPECIFICATION IS SAME AS RESPECTIVE ROUND DEVICE.
J
• THE ELECTRICAL CONTRACTOR SHALL REMOVE EXISTING W ORK W HICH IS ASSOCIATED W ITH HIS TRADE, AND W HICH W ILL BE SUPERFLUOUS W HEN THE NEW SYSTEM IS INSTALLED AND MADE OPERATIONAL. REMOVE INACTIVE W IRING BACK TO THE LAST ACTIVE JUNCTION BOX, PANELBOARD OR PIECE OF EQUIPMENT. NETW ORK CABLING SHALL BE REMOVED BY OW NER.
• ELECTRICAL DEMOLITION PLAN IS NOT INTENDED TO SHOW THE ENTIRE SCOPE OF DEMOLITION W ORK BUT TO HELP CLARIFY SCOPE OF NEW W ORK. THE EC IS REQUIRED TO FIELD VERIFY EXACT SCOPE OF DEMOLITION W ORK DURING BID PERIOD.
• EC SHALL COORDINATE ALL D IMMER SW ITCHES W ITH LUMINAIRE MANUFACTURER TO ENSURE DIMMER IS COMPATIBLE W ITH LUMINAIRE.
• REFER TO ARCHITECT'S REFLECTED CEILING PLAN FOR EXACT LOCATIONS OF ALL LUMINARIES.
• PROVIDE 120V CONTROL POW ER FOR ALL FIRE SMOKE DAMPERS. REFER TO DIVISION 23 DRAW INGS/DETAILS FOR EXACT QUANTITY AND LOCATIONS. PROVIDE 120V-20A LIFE SAFETY CIRCUIT(S) SERVED FROM PANEL _____. CONNECT NO MORE THAN EIGHT (8) DAMPERS PER CIRCUIT.
• EC SHALL PROVIDE ROUGH-INS FOR ALL NEW THERMOSTATS CONSISTING OF A SINGLE GANG BOX AND 0.75" BUSHED CONDUIT STUBBED ABOVE ACCESSIBLE CEILING TURNED 90 DEGREES W ITH BUSED ENDS. REFER TO DIVISION 23 DRAW INGS FOR EXACT QUANTITY AND LOCATIONS.
• EC SHALL PROVIDE ALL ROUGH-INS REQUIRED FOR MATRIX ACCESS CONTROL SYSTEM. COORDINATE ALL W ORK W ITH OW NER'S VENDOR, MATRIX SYSTEMS. PROVIDE CONDUIT STUBS FOR W ALL ROUGH-INS TURNED 90 DEGREES W ITH BUSHED ENDS.
• COORDINATE EXACT MOUNTING HEIGHTS W ITH ARCHITECTURAL DRAW INGS PRIOR TO ROUGH-IN.
• FIRE ALARM SYSTEM W ORK SHALL BE PROVIDED BY DIVISION 26 CONTRACTOR. COORDINATE ALL FIRE ALARM W ORK W ITH OW NER'S VENDOR. REFER TO SPECS
• VOICE/DATA W ORK INCLUDING HORIZONTAL CABLING, JACKS, FACEPLATES PUNCHDOW N PANELS, ETC. SHALL BE PROVIDED BY OW NER. EC SHALL PROVIDE 4" SQUARE BOX W ITH SINGLE GANG RING AND 1" CONDUIT STUBBED ABOVE ACCESSIBLE CEILING AND TURNED 90 DEGREES W ITH BUSHED ENDS. FOR EXISTING STUD W ALLS, PROVIDE FLANGED OPENING W ITH A STRING.
ELECTRICAL GENERAL NOTES
• W ORK MUST CONFORM TO THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE AND OTHER APPLICABLE LOCAL, STATE AND FEDERAL LAW S, ORDINANCES AND REGULATIONS. W HERE DRAW INGS OR SPECIFICATIONS EXCEED CODE REQUIREMENTS, THE DRAW INGS AND SPECIFICATIONS SHALL GOVERN. INSTALL NO W ORK CONTRARY TO MINIMUM LEGAL STANDARDS.
• ALL ELECTRICAL W ORK SHALL BE INSPECTED AND APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION.
• PROVIDE OFFSETS IN SYSTEM RUNS, ADDITIONAL FITTINGS, NECESSARY CONDUIT, PULL BOXES, CONDUCTORS, SW ITCHES AND DEVICES REQUIRED TO COMPLETE THE INSTALLATION, OR FOR THE PROPER OPERATION OF THE SYSTEM.
• AS EACH W IRING SYSTEM IS COMPLETED, IT SHALL BE TESTED FOR CONTINUITY AND FREEDOM FROM GROUNDS.
• W ORK SHALL BE SO PLANNED AND EXECUTED AS TO PROVIDE REASONABLE CONTINUOUS SERVICE OF EXISTING SYSTEMS THROUGHOUT THE CONSTRUCTION PERIOD. W HERE NECESSARY TO DISRUPT SERVICES FOR SHORT PERIODS OF TIME FOR CONNECTION, ALTERATION OR SW ITCH OVER, THE OW NER SHALL BE NOTIFIED IN ADVANCE AND OUTAGES SCHEDULED AT THE OW NER'S REASONABLE CONVENIENCE.
• ELECTRICAL W ORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN ACCORDANCE W ITH REQUIREMENTS OF THE JURISDICTION.
• W HERE CONDUITS ARE TO PASS THRU, ABOVE OR BEHIND EXISTING W ALLS, PARTITIONS, FLOORS, ROOF OR CEILING, CUTTING, PATCHING, REFINISHING AND PAINTING OF SAME SHALL BE INCLUDED. CORE DRILLING AND SAW CUTTING SHALL BE UTILIZED W HERE PRACTICAL. CONTRACTOR TO EXAMINE W HERE FLOORS AND W ALLS ETC. ARE TO BE CUT FOR PRESENCE OF EXISTING UTILITIES UTILIZING X-RAY TECHNOLOGY IF NECESSARY.
• FIRESTOPPING ASSEMBLIES SHALL BE TESTED AND RATED IN ACCORDANCE W ITH ASTM E814 AND E119 AND LISTED IN ACCORDANCE W ITH UL 1479, AS PUBLISHED IN THE UL FIRE RESISTANCE DIRECTORY. FIRESTOPPING SHALL PROVIDE A FIRE RATING EQUAL TO THAT OF THE CONSTRUCTION BEING PENETRATED AND MANUFACTURED BY SPECIFIED TECHNOLOGIES.
• A COMPLETE ELECTRICAL SYSTEM AS SHOW N ON THE DRAW INGS AND AS SPECIFIED HEREIN. W ORK INCLUDES, BUT IS NOT NECESSARILY LIMITED TO W IRING DEVICES, POW ER W IRING, M ISCELLANEOUS W IRING AND INTERLOCKS, EQUIPMENT CONNECTIONS, LUMINARIES, FIRE ALARM.
• PROVIDE FLUSH W ALL MOUNTED HOSPITAL GRADE W IRING DEVICES AS SHOW N. OUTLETS SERVED BY NORMAL CIRCUITS SHALL BE IVORY COVERED BY A STAINLESS STEEL PLATE. COVERPLATES FOR NORMAL RECEPTACLES SHALL BE ENGRAVED TO IDENTIFY PANELBOARD AND CIRCUIT NUMBER FILLED W ITH BLACK PAINT. MATCH HOSPITAL STANDARD.
• PROVIDE FLUSH W ALL MOUNTED HOSPITAL GRADE W IRING DEVICES AS SHOW N. OUTLETS SERVED BY UPS CIRCUITS SHALL BE W HITE COVERED BY IVORY PLATE. COVERPLATES FOR UPS RECEPTACLES SHALL BE ENGRAVED TO IDENTIFY PANELBOARD AND CIRCUIT NUMBER FILLED W ITH RED PAINT. MATCH HOSPITAL STANDARD.
• PROVIDE A DEVICE PLATE TO SUIT EACH PARTICULAR APPLICATION. COVER ALL EMPTY OUTLET BOXES W ITH A BLANK PLATE.
• IN FIN ISHED SPACES, W ALL PLATES SHALL BE NOMINAL .032 INCH THICK, MADE OF 302 HIGH NICKEL STAINLESS STEEL W ITH BRUSHED SATIN FINISH AND BEVELED EDGES. SCREW S SHALL BE METAL W ITH COUNTERSUNK HEADS AND FINISHED TO MATCH PLATES. SECTIONAL PLATES W ILL NOT BE PERMITTED.
• NONMETALLIC SPRING TYPE INSULATED PRESSURE CONNECTORS AS MADE BY "SCOTCHLOK" OR EQUAL SHALL BE USED FOR SPLICING CONDUCTORS. CONNECTIONS IN NO. 8 AND LARGER SHALL BE SPLICED BY APPROVED PRESSURE TYPE MECHANICAL CONNECTORS AND INSULATED W ITH RUBBER OR VINYL TAPE TO ACHIEVE A RESISTANCE EXCEEDING 150% OF THE CONDUCTOR INSULATION. W IRE SHALL BE PULLED ONLY AFTER THAT SECTION OF THE CONDUIT RUN IS PROVEN TO BE CLEAR OF OBSTRUCTIONS, DIRT, MOISTURE AND GREASE. BRANCH CIRCUIT W IR ING SHALL BE PULLED W ITHOUT THE USE OF LEVERS OR HEAVY PULLING DEVICES.
• CONDUIT SHALL BE USED FOR ALL W IRING (EXCEPT W HERE “HCF” ARMORED IS USED). CONDUIT SHALL BE 3/4" DIAMETER OR LARGER EXCEPT 1/2" SIZE MAY BE USED FOR FLEXIBLE CONDUIT, SW ITCH LEGS OR CONDUIT CARRYING CONTROL W IRING ONLY. TERMINATIONS OF ALL CONDUITS SHALL BE SECURED BY LOCK- NUTS AND APPROVED BUSHINGS TIGHTENED UP TO SECURE ELECTRICAL AND MECHANICAL INTEGRITY OF THE CONDUIT SO TO PROVIDE AN UNBROKEN GROUNDING PATH. A SEPARATE COPPER GROUNDING CONDUCTOR SHALL BE PULLED W ITH ALL BRANCH CIRCUITS.
• CONDUIT SYSTEMS MAY BE ANY ONE OR COMBINATION OF THE FOLLOW ING, W ITHIN RESTRICTING LIMITS INDICATED. CONDUIT TYPES NOT LISTED SHALL NOT BE USED.
1. RIGID GALVANIZED CONDUIT - NO RESTRICTIONS.2. INTERMEDIATE GRADE GALVANIZED THREADED CONDUIT - NO RESTRICTIONS.3. THINW ALL CONDUIT W ITH APPROVED CONNECTOR FITTINGS TO ASSURE GROUNDING CONTINUITY. SHALL NOT BE USED IN POURED
CONCRETE, OUTDOORS, OR UNDERGROUND.4. FLEXIBLE METAL CONDUIT (GREENFIELD TYPE) GALVANIZED. ABOVE CEILING USE RESTRICTED TO CONNECTIONS TO LIGHTING
FIXTURES, MAXIMUM LENGTH 6 FT.5. LIQUID TIGHT FLEXIBLE METAL CONDUIT W ITH W ATER TIGHT OIL RESISTANT OUTER PVC COVERING. USED FOR CONNECTIONS TO
MOTORS OR CONTROLS ON DYNAMIC EQUIPMENT AND CONNECTIONS TO TRANSFORMERS.
• ARMORED/METAL CLAD CABLE, TYPE HCF SHALL ONLY BE USED FOR NORMAL POW ER C IRCUITS IN FULL HEIGHT W ALLS ONLY. HCF CABLE SHALL NOT BE USED IN HALF W ALLS SUCH AS NURSES STATIONS, BELOW W INDOW S OR ABOVE CEILING SPACES. BRANCH CIRCUITS FROM PANELBOARDS SHALL BE RUN IN HOME RUN CONDUITS TO A JUNCTION BOX LOCATED NO MORE THAN FOUR FEET FROM THE FULL HEIGHT W ALL. AT THESE JUNCTION BOXES, THE TRANSITION IS MADE TO TYPE HCF CABLE. THE MULTI-CONDUCTOR ARMORED METAL CLAD CABLE RUNOUTS CONTINUE TO RECEPTACLES, ETC.
• DEVICE AND JUNCTION BOXES GALVANIZED STEEL, CODE GAUGE AND SIZE BY STEEL CITY, RACO, APPLETON OR R&S. BOXES CONNECTING MORE THAN ONE PAIR OF CONDUCTORS TO BE MINIMUM 4" X 4", OR 4" OCTAGONAL SIZE. USE ADAPTER PLATES FOR DEVICES W HERE NUMBER OF CONNECTIONS OR OTHER CONDITIONS DICTATE. W RITE PANEL AND CIRCUIT NUMBER ON JUNCTION BOX W ITH PERMANENT MARKER.
• FIRE ALARM W ORK SHALL BE AN EXPANSION/MODIFICATION OF THE EXISTING NOTIFIER NFS 3030 INTELLIGENT FIRE ALARM SYSTEM AND SHALL BE INCLUDED IN THE DIVISION 26 CONTRACT. W IRING SHALL BE IN CONDUIT INSTALLED PER DIRECTION OF THE MANUFACTURER. TEST AND DEMONSTRATE SYSTEM. INSTALLER SHALL MEET STATE OF OHIO REQUIREMENTS FOR CERTIFICATION. THE CONTRACTOR OR H IS FIRE ALARM SUPPLIER/INSTALLER SHALL SUBMIT SHOP DRAW INGS TO THE LOCAL FIRE OFFICIAL FOR PERMIT, REVIEW AND APPROVAL. THE FIRE ALARM SUPPLIER SHALL SUBMIT FOR APPROVAL W ITH SHOP DRAW INGS, FLOOR PLANS, SCHEMATIC AND POINT TO POINT W IRING DIAGRAMS SHOW ING ALL MANUAL AND AUTOMATIC DEVICES, CONTROL PANELS, SOUNDING DEVICES, CONDUIT SIZES, NUMBER AND SIZE OF W IRES, ETC. SHOP DRAW INGS SHALL INCLUDE CALCULATIONS FOR SIZING OF SIGNAL POW ER SUPPLIES, VOLTAGE DROP CALCULATIONS FOR AUDIBLE AND VISUAL SIGNAL C IRCUITS, SPEAKER AMPLIFIERS AND STANDBY BATTERIES.
ELECTRICAL SPECIFICATIONS
1
RW ALL MOUNTED TV OUTLET. COORDINATE MOUNTING HEIGHT W ITH OW NER/ARCHITECT. PROVIDE ROUGH-IN . REFER TO GENERAL NOTE.
15
F
FIRE ALARM SIGNAL LIGHT (80" AFF). # W HEN SHOW N INDICATES CANDELA RATING OF STROBE. W HEN A # IS NOT SHOW N, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
CEILING MOUNTED FIRE ALARM SIGNAL LIGHT. # W HEN SHOW N INDICATES CANDELA RATING OF STROBE. W HEN A # IS NOT SHOW N, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
15F
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
4/2
01
9 4
:27
:55
PM
\\D
ayd
ata
05
\He
apyD
ocu
men
ts\k
mu
hle
nh
ake\M
y D
ocum
ents
\20
19
-05
078
-ME
P-C
en
tra
l_km
uhle
nha
ke
.rvt
2019-05078
LLC
KMU
July 24, 2019
E001
LEGEND, SPECS ANDSHEET INDEX
1 2019.07.24 ADDENDUM 1
SHEET INDEX - ELECTRICAL
SHEET NUMBER SHEET NAME
E001 LEGEND, SPECS AND SHEET INDEX
E002 ELECTRICAL SCHEDULES
E003 SINGLE LINE DIAGRAM
E004 BASEMENT AND ROOF PLANS
E101 FIRST FLOOR - ELEC. DEMOLITION PLAN
E201 FIRST FLOOR - LIGHTING PLAN
E301 FIRST FLOOR - POWER & SYSTEMS PLAN
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
4/2
01
9 4
:28
:04
PM
\\D
ayd
ata
05
\He
apyD
ocu
men
ts\k
mu
hle
nh
ake\M
y D
ocum
ents
\20
19
-05
078
-ME
P-C
en
tra
l_km
uhle
nha
ke
.rvt
2019-05078
LLC
KMU
July 24, 2019
E002
ELECTRICALSCHEDULES
1 2019.07.24 ADDENDUM 1
33.33 kVA 28.04 kVA (78 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: 1. NOTE - THIS IS AN EXISTING PANEL AND SERVED FROM NORMAL POWER. PANEL WAS PREVIOUSLY LABELED CG.
Total Load: 10.88 kVA 10.95 kVA 11.50 kVA
41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42
39 REC 20 A 1 720 VA 180 VA 1 20 A REC 40
37 REC 20 A 1 720 VA 900 VA 1 20 A REC 38
35 REC 20 A 1 720 VA 900 VA 1 20 A REC 36
33 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 34
31 EXISTING 20 A 1 720 VA 1000... 1 20 A REFRIGERATOR 32
29 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 30
27 EXISTING 20 A 1 720 VA 1000... 1 20 A REFRIGERATOR 28
25 HOOD 20 A 1 750 VA 1000... 1 20 A REFRIGERATOR 26
23 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 24
21 HOOD 20 A 1 750 VA 750 VA 1 20 A HOOD 22
19 HOOD 20 A 1 750 VA 720 VA 1 20 A EXISTING 20
17 UC REF 20 A 1 1160... 2400... 1 20 A OMNICELL 18
15 EXISTING 20 A 1 720 VA 720 VA 1 20 A REC 16
13 EXISTING 20 A 1 720 VA 720 VA 1 20 A REC 14
11 REC 20 A 1 720 VA 720 VA 1 20 A REC 12
9 REFRIGERATOR 20 A 1 1000... 1000... 1 20 A REFRIGERATOR 10
7 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 8
5 FREEZER 20 A 1 1000... 1000... 1 20 A FREEZER 6
3 EXISTING 20 A 1 720 VA 1233... 1 20 A LTG PHARMACY 4
1 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 2
CKT Circuit Description Trip PolesA B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 200 ASupply From: DP3 Enclosure: Type 1 Mains Type: MLO
Location: CORRIDOR 1527 Mounting: Recessed A.I.C. Rating: EXISTING
Panel: N112
50.06 kVA 45.61 kVA (127 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: 1. NOTE - THIS IS AN EXISTING PANEL AND SERVED FROM THE CRITICAL BRANCH. PANEL WAS PREVIOUSLY LABELEDEM3.
Total Load: 18.01 kVA 16.38 kVA 15.67 kVA
41 -- -- -- 720 VA 6310... -- -- -- 42
39 EXISTING 20 A 2 720 VA 7020... -- -- -- 40
37 EXISTING 20 A 1 720 VA 8653... 3 70 A E127A-CB 38
35 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 36
33 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 34
31 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 32
29 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 30
27 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 28
25 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 26
23 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 24
21 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 22
19 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 20
17 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 18
15 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 16
13 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 14
11 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 12
9 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 10
7 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 8
5 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 6
3 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 4
1 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 2
CKT Circuit Description Trip PolesA B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 200 ASupply From: DP5 Enclosure: Type 1 Mains Type: MLO
Location: CORRIDOR 1527 Mounting: Recessed A.I.C. Rating: EXISTING
Panel: E127-CB
21.98 kVA 17.53 kVA (49 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: 1. NOTE - THIS IS A NEW PANEL AND SERVED FROM THE CRITICAL BRANCH.2. $ REPRESENTS GFCI BREAKER.
Total Load: 8.65 kVA 7.02 kVA 6.31 kVA
41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42
39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40
37 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 38
35 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 36
33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34
31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32
29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30
27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28
25 REC 20 A 1 720 VA 370 VA 1 20 A PHARMACY FAN COILS 26
23 REC 20 A 1 900 VA 720 VA 1 20 A $ REC 24
21 REF 20 A 1 1000... 720 VA 1 20 A REC 22
19 COPIER 20 A 1 750 VA 1000... 1 20 A REF 20
17 UC REF 20 A 1 860 VA 1000... 1 20 A REF 18
15 OMNICELL 20 A 1 1000... 750 VA 1 20 A HOOD 16
13 REC 20 A 1 720 VA 750 VA 1 20 A HOOD 14
11 REC 20 A 1 720 VA 750 VA 1 20 A HOOD 12
9 REC 20 A 1 720 VA 750 VA 1 20 A HOOD 10
7 REFRIGERATOR 20 A 1 1000... 720 VA 1 20 A REC 1550 8
5 REFRIGERATOR 20 A 1 1000... 360 VA 1 20 A P TUBE 6
3 FREEZER 20 A 1 1000... 1080... 1 20 A AUTO DOORS 4
1 FREEZER 20 A 1 1000... 1623... 1 20 A LTG PHARMACY 2
CKT Circuit Description Trip PolesA B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 100 ASupply From: E127-CB Enclosure: Type 1 Mains Type: MLO
Location: CORR. 1535 Mounting: Recessed A.I.C. Rating: 10,000
Panel: E127A-CB
NOTES:1.
LUMINAIRES
MARK FIX
TU
RE
VO
LT
AG
E
LO
AD
(V
A)
MANUFACTURER CATALOG NO. DESCRIPTION
OTHER ACCEPTABLEMANUFACTURERS
MOUNTING
SE
E N
OT
E
S-SURFACER-RECESSEDSM-STEM MTDWM-WALL MTDC-CHAIN MTD
UC-UNDER CABCS-CEIL SURFACE
C4 120 41 LITHONIA ZL1D-L48-5000LM-FST-MVOLT-35K-80CRI-WH-HC36 4' LONG LED INDUSTRIAL STRIP COLUMBIA "CSL" C
F6 120 21 LITHONIA LDN6-35/15-LO6-LSS-MVOLT-EZ10 6" LED DOWNLIGHT PRESCOLITE "LC6" R
L22 120 32 LITHONIA EPANL-2x2-4000LM-80CRI-35K-MIN10-ZT-MVOLT 2'x2' LED FLAT PANEL COLUMBIA "CFP" R
L24 120 54 LITHONIA EPANL-2x4-6000LM-80CRI-35K-MIN10-ZT-MVOLT 2'x4' LED FLAT PANEL COLUMBIA "CFP" R
L24L 120 39 LITHONIA EPANL-2x4-4000LM-80CRI-35K-MIN10-ZT-MVOLT 2'x4' LED FLAT PANEL COLUMBIA "CFP" R
W2 120 20 TECH LIGHTING 700BCMLN-24-W-C-LED930 2' LONG LED VANITY LIGHT MODERN FORMS WM
X1 120 1 LITHONIA LQC-W-1-R SINGLE FACE EXIT SIGN DUAL-LITE CS
X2 120 1 LITHONIA LQC-W-2-R DOUBLE FACE EXIT SIGN DUAL-LITE CS
NOTES:1. SINGLE POINT CONNECTION TO AHU BY EC. AHU SHALL HAVE INTERNAL TRANSFORMER TO SERVE MISCELLANEOUS 120V LOADS.2. EC SHALL PROVIDE WEATHERPROOF DISCONNECT ADJACENT TO EXHAUST FAN.
MOTORS, STARTERS, DISCONNECTS & CONTROLS
MARK
MOTOR STARTER DISCONNECT MEANS FEEDER
SE
E N
OT
E
NAMEPLATE
CHARACTERISTICS
NE
MA
SIZ
E
TYPE LOCATION F
UR
NIS
HE
D B
YTYPE LOCATION
FU
RN
ISH
ED
BY
NU
MB
ER
OF
CO
ND
UC
TO
RS
WIR
E S
IZE
GR
OU
ND
SIZ
E
CO
ND
UIT
SIZ
E
HO
RS
EP
OW
ER
(H
P)
LO
AD
(kV
A)
12
0V
-1P
H
20
8V
-1P
H
20
8V
-3P
H
48
0V
-1P
H
48
0V
-3P
H
EC
M
MA
GN
ET
IC
VF
D
SE
E N
OT
E
NE
AR
MO
TO
R
IN
TE
GR
AL
W/
EQ
UIP
.
RO
OM
NU
MB
ER
SE
E N
OT
E
DIS
C S
WIT
CH
NE
MA
TY
PE
DIS
C S
IZE
FU
SE
SIZ
E
NE
AR
MO
TO
R
IN
TE
GR
AL
W/
EQ
UIP
.
SE
E N
OT
E
AHU-24 PHARMACY AHU 12 kVA 12 ● ● ● HC ● ● HC 3 10 10 0.75 1
EF-92 CHEMO EXHAUST 2 2.83 ● ● 1542A 2 HC ● 3R 30 ● EC 3 12 12 0.75 2
14.83 kVA 14.83 kVA (18 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: 1. NOTE - THIS IS A NEW PANEL AND SERVED FROM THE EQUIPMENT BRANCH.
Total Load: 4.94 kVA 4.94 kVA 4.94 kVA
41 Space -- -- 0 VA 0 VA -- -- Space 42
39 Space -- -- 0 VA 0 VA -- -- Space 40
37 Space -- -- 0 VA 0 VA -- -- Space 38
35 Space -- -- 0 VA 0 VA -- -- Space 36
33 Space -- -- 0 VA 0 VA -- -- Space 34
31 Space -- -- 0 VA 0 VA -- -- Space 32
29 Space -- -- 0 VA 0 VA -- -- Space 30
27 Space -- -- 0 VA 0 VA -- -- Space 28
25 Space -- -- 0 VA 0 VA -- -- Space 26
23 Space -- -- 0 VA 0 VA -- -- Space 24
21 Space -- -- 0 VA 0 VA -- -- Space 22
19 Space -- -- 0 VA 0 VA -- -- Space 20
17 -- -- -- 0 VA 0 VA -- -- -- 18
15 -- -- -- 0 VA 0 VA -- -- -- 16
13 Spare 20 A 3 0 VA 0 VA 3 20 A Spare 14
11 -- -- -- 0 VA 0 VA -- -- -- 12
9 -- -- -- 0 VA 0 VA -- -- -- 10
7 Spare 20 A 3 0 VA 0 VA 3 20 A Spare 8
5 -- -- -- 4000... 942 VA -- -- -- 6
3 -- -- -- 4000... 942 VA -- -- -- 4
1 AHU-24S 30 A 3 4000... 942 VA 3 20 A EF-1 2
CKT Circuit Description Trip PolesA B C
Poles Trip Circuit Description CKT
Voltage: 480/277 Wye-3PH-4W Mains Rating: 100 ASupply From: DP4 Enclosure: Type 1 Mains Type: MLO
Location: HVAC 1542A Mounting: Surface A.I.C. Rating: 10,000
Panel: E190-EB
NE
NONE
EM3AE127A-CB
E190-EB
100
E87A-CB
200A/3P (200A)
N193
E188-CB
E85-CB
E189-CB E87B-CB
CATHLAB #4
UPS
MA
80/3PCB
N80A
150A(NEW)
150A STCB2
SINGLE-LINE DIAGRAM
N
100A/3PMANUALTRANS.
PDU1A PDU1B
480D208Y/120V75KVA
SONETPDU1-LS
3
HV3
LIFE SAFETY
B3
A2
C3A3
1"C
ELEV. ELEV.
ELEV. ELEV.
ELEV. ELEV.
EM43
SECTION #1
EM51ELEC.
SHOP
EM1
EM53EM53A
EM41
SP
AC
E F
OR
200A
SW
ITC
H
SECTION #2
1200AMAIN
CATSCANLEIBERT
AC
SP
AR
E10
0S
PA
RE
100
SP
AR
E10
0
200
200
SP
AR
E20
0
200
EM55
EM42
EM50
EM5
EM3 EM4 EM2
'66 BLDG.
SECTION #3
EM6
SP
AR
E20
0S
PA
RE
200
SP
AR
E20
0S
PA
RE
200
SP
AC
E20
0
SP
AC
E20
0
SECTION #4 SECTION #1
OLD MATERNITY A.C.
BOILER
SECTION #2
200
SP
AR
E10
0
100
SP
AR
E10
0
SP
AR
E10
0
ROOM
OLD AH #1
EM
ER
.
NO
RM
.
O.U. BLDG.
OLD
SP
AC
E20
0
P3
EMX1
SECTION #1 SECTION #2
SP
AR
E60
SP
AR
E20
0
SP
AR
E20
0
SP
AR
E40
0
P2CATHLAB
SP
AR
E60
P4
TO WESTPARKING
LOT LIGHTS
SP
AR
E30
P5
SP
AR
E
CHILLERRM. 21
SP
AR
E20
0
800
SP
AR
E20
0
200A
MED AIRPUMP
PACKAGE #2
100A
MED VACPUMP
PACKAGE #2
800 800 1600
SECT. #1 SECTION #2
TO O.U. BLDG.
200A
SP
AC
E
200A
SP
AC
E
EM9
SHORT
EM9A
STAY
1� 200ATELE.
FRAMEROOM
NUCLEARMEDICINE
ELEC.SHOPCAGE
PLUMB.SHOPHALL
SECTION #1 SECTION #2 SECTION #3 SECTION #4
1600
200
HALLNEARRM. 5
200
HG
200
AAG(AG)
E
SP
AC
E
200
AA12300
2-10
0AS
PA
CE
200
GG12300
EAST
HH12300
WEST
200
BG
200
CG
200
DG
400
GG
2-10
0AS
PA
CE
2-10
0AS
PA
CE
SP
AR
E10
0
SP
AR
E10
0
SP
AR
E20
0
200
200
NG
200
2-10
0AS
PA
CE
2-10
0AS
PA
CE
SP
AR
E10
0S
PA
RE
100
200
NL1
200
NL2
SITE
200
PG
LIGHTING
LPN-150
NUCLEARMEDICINE
COMM. RM.PHARMACY
T16
200
R1
2-10
0AS
PA
CE
SECTION #4 SECTION #3 SECTION #2 SECTION #1
2-10
0AS
PA
CE
SP
AR
E10
0S
PA
RE
100
"N62"(BB)
200
TRANSFERFOR PHONE
SWITCH
200
MG
200
FG
F1
200
200
SP
AC
E
SP
AR
E20
0
B1
200
C1
200
D1
E1
200
200
KG
400
'66 BLDG.NUCLEAR
200
200
TG
SP
AR
E20
0
400
SP
AR
E20
0
200
200
EG
200
SG
400
JG
TO LS SECT. 2
TO TS14
TO SC1
SP
AR
E
SP
AC
E
SP
AC
E
SP
AC
E
SP
AC
E
SP
AC
E
1600 800 800SPACESPACE
J1J1A
SHORTSTAY
TVROOM
SHORTSTAY
CATHLAB
3600
'66EM44B
CATHLAB
TO TS13
SP
AR
E
SP
AR
E
SP
AR
E
SP
AR
E
MORGUE
EM44A
RADIOLOGYCLOSET
QI
RAD.
RAD.CLOSET
BLDG.
K12300
D24600
LAB KITCH.
KITCH.STEAMROOM
LOBBY
ELEV. #7THERAPY
PHYS.
MED.
NUC.
HALLRADIOLOGYTHERAPY
PHYS.
HIMS COMM. ROOM
D1ADOCTOR'S
READING RM.
PHARM.
HALLNEARPBX
PHONESWITCH
REGULATOR
GGELEV. OLD LAB KIT.
MAILROOMWALL
#3 & 4LOBBY
KIT.KIT.
MANHOLE #__
MCC1
EM
ER
.
MCC6
RADIOLOGYQI
TO DP18SECT. 3
SHEET E-5
3600
A15600
TO ELEV. #10
SEE SHEET E-6
B16600
EM13
'66 BLDG.
EM13A
'66 BLDG.EM13B
LAB
RAD.HALL
2300
CHEM.LAB
QIRAD.
RAD.CLOSET
MORGUE
PENTHOUSE
ELEV. #8
SHEET E-4
SHEET E-4
SHEET E-4
SHEET E-4
#3 #4
#5 #6
#7 #8
TA
G 1
2-93
RE
MO
VE
D
CHILLER 3RM. 3
SPACESPACE
TO PSC-2
N177
N178
CB X-RAY CATHLAB
ANGIO
AB
DP6
LABELED C2
3/60
2/60
E133EB
B506
E148CB
B521
E146CB
1342
E131CB
2432
E103CB
2407E102CB
4542E75CB
4545E75ACB
2430
E100CB
1518
E132CB
2316
E109CB
EM422316
E109CB
E128CB
2435E101CB
E127-CB
B415E147CB
1616
E129CB
3617
E78CB
4645
E71CB
6600
E68CB
6642N66
B522E145EB
3403
CTFEEDER
B503E139EB
2407E104EB
3618N76
3419N83
5642N69
B400
N14
3CB
N14
2
B424E140
1725E124
N136B524
N117
1342N110
2316N105
2314N107
N106
N111N112
N113 N115N116
CAPPEDOFF IN
BOILER RM.
B521
N138N137
1616N121
2317N125
1335N120 1313
N114
2606N88
N89 N90
N91A
N91
N92
4653N123B
N70N72 N74 N73
3618N77
N79
2311N123A
N119
N1231631 N122
1728
J1
N62B408
N961500 N95
1500
N1181725
2332N94
2407N93
2314N108
2437N18L
E59CB E182CB
E61CB E67CB
B522
E63CB E64CB
3621E44ALS
2432E44BLS
1342E43LS
B522E60LS
TO SHEETE-4E60LS
CAGE
OLD HIMS
DICTATION
SP
AR
E
TRANSFORMER
NEED'S #
MCC1A
PANEL C2VASCULAR LAB
HALL 3618
6500
7603 7603
TO TS-23
60/3
(40)
100/
3
100/
3
EM44CLS
60A/2P
(40A)
60A/2P
(50A)
WP
60/3
30A/2P
(25A)
480V
10K V A 60A / 3P P MS
240/ 120V
EXISTING PULL BOX
NOTE: DARK LINE WEIGHT REPRESENTS NEW WORK.
"MTS2-LS"
100
"MTS1-LS"
UPSBYPASS
PBXUPS
EM43MORGUE
TO "LS"
E128ACB(LAB)
N96A N95A
EM6A FGA
SHAFTDAMPERS
ELEV.MACHINERM
ELEV.COND.UNIT
A/C
20A/2P
(20A)
T31000 KVA12,470V TO480V - 3PH - 3W
T21500 KVA12,470V TO280Y/120V - 3PH - 4W
T12000KVA12,470V TO480V - 3PH - 3W
T11KVA
V TOV - 3PH - 3W
SB (NE W)
E44-LS(NEW)
60/260/260/3
400/3
(400A)
400/3
(250A)
400/3
(300A)
480Δ TO480/277V500 KVA 6.69%
TRANSFORMERTAP
125/3PE195-CB
TS-1
200/3(200A)
EMX1
EMP1
E82EB
CATHLABUPS
N192
200/3(200A)
MA
EPLABUPS
MA
80/3PCB
80/3PCB
125/3P STCB2
125/3P STCB2
E84-CB (EM8)
N80
E
SB
E87-CB
E233-EB
60/3P
E186-CB
E187-CB
E184-CB
E185-CB
N191
E
1500
42
XX
X
5
HV2
6 2 1
XX
X
U1
UG
U3
C2
C1
HV1
XX
X
TO PSC-2 TO PSC-2
1725
2315
1400
1427
1518
1725
1725
2435
2435
1616
2529
2517
2517
4653
4542
4504
4542
3419
DP3 ()1600A - 208Y/120V-3PH-4W
DP2 ()1600A - 208Y/120V-3PH-4W
DP1 ()1000A - 480V-3PH-4W
DP16 ()A - 480V-3PH-3W
DP4 ()800A - 480V-3PH-3W
DP5 ()800A - 208Y/120V-3PH-4W
DP15 ('71 BLDG. BASEMENT,OFFICE NEAR ROOM 5)A - 480V-3PH-3W
DP6 (RM 3403)800A - 208Y/120V-3PH-4W
US2 ()3000A - 208Y/120V-3PH-4W
US3 ()1600A - 480V-3PH-3W
US1 ()2000A - 480V-3PH-3W
SEVENTH
SIXTH SIXTH
FIFTH FIFTH
FOURTH FOURTH
THIRD THIRD
SECOND SECOND
FIRST FIRST
BSMNT BSMNT
ROOF
SCALE:
12
SCOPE OF W ORK
2 3
SCOPE OF W ORK
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
4/2
01
9 4
:28
:12
PM
\\D
ayd
ata
05
\He
apyD
ocu
men
ts\k
mu
hle
nh
ake\M
y D
ocum
ents
\20
19
-05
078
-ME
P-C
en
tra
l_km
uhle
nha
ke
.rvt
2019-05078
LLC
KMU
July 24, 2019
E003
SINGLE LINE DIAGRAM
1 2019.07.24 ADDENDUM 1
1 EC SHALL PROVIDE NEW 100A/3P BREAKER INEXISTING PANEL.
2 4-#2, 1-#8 GROUND IN 1.25" CONDUIT.
3 UTILIZE SPARE 100A FUSIBLE SWITCH ANDPROVIDE NEW 100A FUSING.
8
13
14
DP
5
DP
2
DP
3
DP
4
US1 US2
DP
1
ATS1
EM1
PR
IMA
RY
SW
ITC
HG
EA
R #
2
DP15
T11
NL2
NL1
DP
4D
P5
DP
5
DP
5
DP
1
DP
2
DP
3D
P3
DP
2D
P2
DP
3
EF-92
E190-EB - 1,3,5
AHU-24
W P
TO VFD
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
4/2
01
9 4
:28
:19
PM
\\D
ayd
ata
05
\He
apyD
ocu
men
ts\k
mu
hle
nh
ake\M
y D
ocum
ents
\20
19
-05
078
-ME
P-C
en
tra
l_km
uhle
nha
ke
.rvt
2019-05078
LLC
KMU
July 24, 2019
E004
BASEMENT AND ROOFPLANS
1 2019.07.24 ADDENDUM 1
SCALE: 1/8" = 1'-0"
PARTIAL BASEMENT - ELECTRICAL PLAN3
NOTES
SCALE: 1/16" = 1'-0"
PARTIAL THIRD FLOOR (ROOF) - ELECTRICAL PLAN4
E127-CB N112
1
1
1
1 1 1 1
1
1
11
1
1
1 1
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
4/2
01
9 4
:28
:21
PM
\\D
ayd
ata
05
\He
apyD
ocu
men
ts\k
mu
hle
nh
ake\M
y D
ocum
ents
\20
19
-05
078
-ME
P-C
en
tra
l_km
uhle
nha
ke
.rvt
2019-05078
LLC
KMU
July 24, 2019
E101
FIRST FLOOR - ELEC.DEMOLITION PLAN
1 2019.07.24 ADDENDUM 1
SCALE: 1/4" = 1'-0"
PARTIAL FIRST FLOOR - ELECTRICAL DEMOLITION PLAN1
NOTES
1 REMOVE ALL LUMINAIRES, RECEPTACLES, FIRE ALARM DEVICES,PUBLIC ADDRESS DEVICES, DATA/COMMUNICATION DEVICES, ETC.UNLESS OTHERWISE NOTED. MAINTAIN ALL NORMAL POWERRECEPTACLE CIRCUITS FOR NEW WORK.
GENERAL NOTES
A. ELECTRONIC COORDINATION DRAW INGS ARE REQUIRED AND MUST BE SUBMITTED TO THE ENGINEER FOR REVIEW PRIOR TO BEGINNING NEW W ORK. REFER TO 23 05 01.
PTD
SD
33
44
33
L
L
OS
OS
L
D D
OS OSOS
OS
D
OS
OS
L
L
OS
J
J J
J
1544
ORDER
ENTRY
OFC
1542AHVAC
1535CORR.
1527CORRIDOR
L24L
N112 - 4
v
L24L
E127A-CB - 2
v
L24L
N112 - 4
z
L24L
E127A-CB - 2
z
L24L
N112 - 4
z
E12
7A-C
B
E127-CB N112
ba
ba
ba
L24L
N112 - 4
a
L24L
E127A-CB - 2
b
L24
E127A-CB - 2
b
L24
N112 - 4
a
L24
E127A-CB - 2
b
L24
N112 - 4
a
L24
E127A-CB - 2
b
L24
N112 - 4
a
L22
E127A-CB - 2
b
L24
N112 - 4
a
L24
N112 - 4
a
L22
N112 - 4
a
L22
E127A-CB - 2
b
L24
E127A-CB - 2
b
L24
N112 - 4
a
L22
N112 - 4
a
L24
N112 - 4
a
L24
E127A-CB - 2
b
L22
N112 - 4
a
L24
N112 - 4
a
L22
N112 - 4
a
L24
N112 - 4
a
L22
E127A-CB - 2
b
L24
E127A-CB - 2
b
L22
N112 - 4
a
L22
E127A-CB - 2
b
L24
E127A-CB - 2
b
L24L
N112 - 4
y
L22
N112 - 4
c
L22
E127A-CB - 2
c
L22
N112 - 4
c
L22
E127A-CB - 2
c
L22
N112 - 4
c
c
c
d
d
d d
d
d
d d
d
d
L22
N112 - 4
e
L22
E127A-CB - 2
e
L22
N112 - 4
e
L22
E127A-CB - 2
e
L24L
E127A-CB - 2
f
L24L
N112 - 4
f
L22
N112 - 4
a
1542ANTI RM
1541CHEMO RM
1540
HD
NON-STERILE
1539NARC RM
1538POP1533
JAN
1550PACKAGING1548
RECEIVING
1547
ADA STAFF
TOILET
1546OFC
1545MGR. OFC
1543IV RM
1537A
BULK
STORAGE
1537
ORDER
ENTRY
C4 C4
E127A-CB - 2E127A-CB - 2
y
v z
F6
W 2
E127A-CB - 2
E127A-CB - 2
e
f
1 1
1
1
1
L24
N112 - 4
a
L24
E127A-CB - 2
b
L24
N112 - 4
a
2 3
E127A-CB - 2
2 3
E127A-CB - 2
2 3
E127A-CB - 2
2 3
E127A-CB - 2
L24
E127A-CB - 2
b
L24
N112 - 4
a
E190-EB
X1
X1
X1
X2
X2
X2
TYP.4
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
4/2
01
9 4
:28
:33
PM
\\D
ayd
ata
05
\He
apyD
ocu
men
ts\k
mu
hle
nh
ake\M
y D
ocum
ents
\20
19
-05
078
-ME
P-C
en
tra
l_km
uhle
nha
ke
.rvt
2019-05078
LLC
KMU
July 24, 2019
E201
FIRST FLOOR -LIGHTING PLAN
1 2019.07.24 ADDENDUM 1
SCALE: 1/4" = 1'-0"
PARTIAL FIRST FLOOR - NEW WORK LIGHTING PLAN1
NOTES
1 PROVIDE TWO POWER PACKS TO CONTROL LIGHTING.
2 ALL JUNCTION BOXES SHALL BE MOUNTED ABOVE ACCESSIBLECEILING.
3 LUMINAIRES IN THIS SPACE SHALL BE FURNISHED BY OWNER'SVENDOR (CARTER HEALTH) AND INSTALLED BY EC. COORDINATEEXACT REQUIREMENTS WITH OWNER'S VENDOR. PROVIDE 120VCONNECTION TO EACH LUMINAIRE.
4 CONNECT EXIT SIGN TO CORRIDOR LIFE SAFETY LIGHTING CIRCUIT.
GENERAL NOTES
A. ELECTRONIC COORDINATION DRAW INGS ARE REQUIRED AND MUST BE SUBMITTED TO THE ENGINEER FOR REVIEW PRIOR TO BEGINNING NEW W ORK. REFER TO 23 05 01.
PTD
SD
GF
S
S
S
S
CR
EL
CR
EL
CREL
JJ
SHD
HD
HD
29"MH
D 29"MH
29"M
H
D29
"MH
29"M
H
D29
"MH
29"MH
D29"MH
FREEZER
D 46"MH
FREEZER
FREEZER
D 46"MH
FREEZER
REF
D46"MH
REF
REF
D46"MH
REF
GF
D46"MH
CR
AS
H C
AR
T
CR
AS
H C
AR
T
D D
D
D D
UC
R
D18
"MH
UC
R
OMNICELL
D46"MH
OMNICELL
OMNICELL
D46"MH
OMNICELL
CO
D46
"MH
CRASH CART29"MH
D 29"MH
29"MH
D 29"MH
GF
B/S
INK
HOOD
D 46"MH
HOOD
HO
OD
D46
"MH
HO
OD
HOOD
D46"MH
HOOD
REF
D46"MH
REF
29"M
H
D29
"MH
29"M
H
D29
"MH
HOOD
D46"MH
HOOD
REF
D 46"MH
REF
REF
D46"MH
REF
D
D
29"M
H
D29
"MH
29"M
H
D29
"MH
29"MH
D29"MH
29"MH
D29"MH
29"MH
D 29"MH
29"M
H
D29
"MH
FC 1-01 FC 1-03
FC 1-04A
FC 1-04B
FC 1-05
FC 1-02
CR
EL
E12
7A-C
B
E127-CB N112
1544
ORDER
ENTRY
OFC
1542AHVAC
1535CORR.
1527CORRIDOR
1542ANTI RM
1541CHEMO RM
1540
HD
NON-STERILE
1539NARC RM
1538POP
1533JAN
1550PACKAGING1548
RECEIVING
1547
ADA STAFF
TOILET
1546OFC
1545MGR. OFC
1543IV RM
1537A
BULK
STORAGE
1537
ORDER
ENTRY
E127A-CB - 6 E127A-CB - 6
11
E127A-CB - 4
E127A-CB - 4
E127A-CB - 4
39
37
38
38
39
39
8
11 8
11
1
5
3
6
7
10
5
9
38
23
38
38
23 23
9
12
1114
1114
13 16 13 16
1717
15
18
15
18
19
2412
9
39
24
10
19
1221
16
25
18
26
1717
14
22
20
28
21
32
36
36
36
36
37
3522
35
22
37
40
25
25
E127A-CB - 26
2
E127A-CB - 26
2
E127A-CB - 26
2
E127A-CB - 26
2
E127A-CB - 26
2
E127A-CB - 26
2
E190-EBEF-92VFD
TO DISCONNECT ON ROOF
E190-EB - 2,4,6
3
44
Kettering Health Network
Grandview Medical Center
KEYPLAN:
REVISIONS:
NOTES:
Job No.
Drawn By
Checked By
Date
Sheet No.
No. Date Description
480 VANTAGE POINT, SUITE 201
MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893
www.pinnaclearchitects.com
405 W. GRAND AVE. DAYTON, OHIO 45405
CLEAN ROOM RENOVATION
PHARMACY
PROJECT NO. 2019-05078
7/2
4/2
01
9 4
:28
:44
PM
\\D
ayd
ata
05
\He
apyD
ocu
men
ts\k
mu
hle
nh
ake\M
y D
ocum
ents
\20
19
-05
078
-ME
P-C
en
tra
l_km
uhle
nha
ke
.rvt
2019-05078
LLC
KMU
July 24, 2019
E301
FIRST FLOOR - POW ER& SYSTEMS PLAN
1 2019.07.24 ADDENDUM 1
SCALE: 1/4" = 1'-0"
PARTIAL FIRST FLOOR - NEW WORK POWER & SYSTEMS PLAN1
NOTES
1 PROVIDE 120V CONNECTION TO NEW PNEUMATIC TUBE STATION.
2 PROVIDE SINGLE POINT 120V CONNECTION TO FAN COIL. COORDINATEWITH HC.
3 STACK MOUNT POWER AND DATA ON WALL AT APPROXIMATELY 84".
4 STACK MOUNT POWER AND DATA ON MULLION.
GENERAL NOTES
A. ELECTRONIC COORDINATION DRAW INGS ARE REQUIRED AND MUST BE SUBMITTED TO THE ENGINEER FOR REVIEW PRIOR TO BEGINNING NEW W ORK. REFER TO 23 05 01.
B. UNLESS NOTED OTHERW ISE, ALL NORMAL POW ER RECEPTACLES SHALL BE FED FROM PANEL N112 AND ALL CRITICAL POW ER RECEPTACLES SHALL BE FED FROM E127A-CB.