31
EQUIP equipment perimeter PERIM janitor JAN basement BSMT galvanized GALV CPT carpet glass GL gypsum board GYP.BD. CY cubic yard CTC center to center general contractor gypsum board ceiling gypsum board soffit gypsum board bulkhead GC GBS GBC GBB crash rail CRB CR ceramic tile course(s,ing) CT CRS coved resilient base future FUT footing FTG FA fasten, fastener existing EXIST CONST construction CLS closure CL centerline of CH channel gage, gauge GA caulk(ing) CLK CLO closet BUL bulletin BUR built-up roof frame fireproof(ing) FR FP ceramic mosaic tile clear CMT CLR furred(ing) feet or foot FUR FT continuous concrete CONT CONC COL contractor CORR CONTR corridor column FRT fire retardant concrete masonry unit CMU each way EW exterior EXP EXT exhaust EXH expansion face brick FB FD FE fire extinguisher cabinet finish floor elevation FFE FFL FGL FEC cabinet carpet base cubicle curtain cubicle curtain track cubic feet foundation FHC FIN FLR FND face of concrete face of masonry FOC FOM contr. furnished, contr. installed corner guard chamfer circumference control joint ceiling contract limit line floor drain fire extinguisher finish floor line fiberglass fire hose cabinet finish(ed) floor(ing) CAB CB CC CCT CF CFCI CG CHAM CIRC CJ CLG CLL moulding MLD marker board MRKBD movable MOV masonry opening MO mount(ed),(ing) metal MP MT MTL multi-paint medium MED LTWT lightweight LTG lighting light low point LT LP LAM laminated KO knock out PTD paper towel dispenser LVR louver PL PG plastic laminate plate glass plaster PNL PLWD PLSTR PLC pounds per square foot PSF PR PP panel pair push plate plywood plastic laminate clad PSI pounds per square inch joint JT kitchen kick plate length, long lavatory KIT KPL L LAV LBL linear foot long leg horizontal long leg vertical level masonry lintel LF LLH LLV LVL MAS LTL label mechanical manufacturer maximum miscellaneous minimum MAX MECH MFR MISC MIN MAT material EIFS ext. insulation & finish sys. BC bottom of curb ASPH asphalt depth, deep D detail demolition double DET DEMO DBL dimension diagonal diameter DIM DIAG DIA drinking fountain DF anchor bolt door opening DO DN drawer downspout door DWR DWG DS DR acoustical addendum adjustable above finish floor alternate aluminum anodized above drawing down expansion bolt each east EB EA E electric(al) elevation expansion joint each face ELEC EL EJ EF access panel architectural board bumper guard bituminous equal elevator EQ ELEV blocking bench mark bearing plate bearing brick bottom building both sides AB ABV ACOUS ADD ADJ AFF ALT ALUM ANOD AP ARCH BD BG BITUM BLDG BLKG BM BOT BPL BRG BRK BS pre-formed composite metal panel owner furnished, owner installed owner furnished, contr. installed NC no ceiling PCMP PCC pre-cast concrete MTLFUR metal furring MUL mullion HT height high point HP GMU glazed masonry units ounce OZ NOM NO nominal number on center OC OA outside diameter OH OFOI OFCI OD overhead overall opening OPG P OPP particle board PBD paint opposite gravel grab bar grade hardboard height, high grout GRVL GRB GR HDBD H GT hardwood hollow core heating, ventilating, air-conditioning horizontal hollow metal HDWD HDW HC HVAC HORZ HM interior insulation include(d),(ing) invert INT INSUL INCL INV inside diameter ID hardware not to scale NTS millwork north not in contract MWK N NIC A-0 A-1 A2-1 A3-0 A5-1 A6-1 A11-1 CODE COMPLIANCE PLAN DEMOLITION PLAN PHARMACY CLEAN RM. PLAN DOOR SCHEDULE, WALL/FRAME TYPE, DETAILS REFLECTED CEILING PLAN - ROOF PLAN INTERIOR ELEVATIONS FINISHES AND FINISH PLAN GRAVEL NOTE REFERENCE LINTEL TYPE METAL BRICK CONCRETE CEILING HEIGHT CONCRETE MASONRY UNIT REFERENCE DRAWING NUMBER DETAIL NUMBER COLUMN REFERENCE TEST BORING WALL TYPE DOOR NUMBER WINDOW NUMBER L-1 PLASTIC LAMINATE SHIM WOOD, FRAMING WOOD, FINISH PLYWOOD LOUVER TYPE ELEVATION LETTER REFERENCE DRAWING NUMBER REFERENCE DRAWING NUMBER SECTION NUMBER EXISTING POINT ELEVATION NEW CONTOUR NEW POINT ELEVATION EXISTING CONTOUR INSULATION, BATT INSULATION, RIGID GRID LINES PROJECT TITLE: ABBREVIATIONS: SYMBOLS LEGEND: PROJECT TEAM: DRAWING INDEX: CARD READER COVER ELEVATION MTL STUD ARCHITECTURAL EARTH GYPSUM BOARD/ PLASTER SVGC suspended vinyl gypsum ceiling rough opening RO ROW RUB right of way rubber window wood weight waterproof(ing) waterstop wainscot welded wire mesh wall to wall WIN WD WT WSCT WP WS WWM WTW quantity QTY PTN partition polyvinyl chloride PVC QT QTR RD quarry tile quarter round radius reference RAD RD REF REINF required resilient revision REQ'D RESIL RET REV roof drain reinforcing return reflected RFL RM riser R room TMPRD tempered TEL telephone top of curb temporary tongue and groove thick(ness) top of pavement top of slab tread toilet paper dispenser TC TEMP T&G THK TP TST TSL T TPD typical top of wall vertical vinyl composition tile vapor barrier west, width, wide vinyl wall covering veneer TW TYP VERT VCT VB W VWC VNR top of steel water closet wood base WC WB sanitary napkin dispenser SND STRUC structural STD standard STL STOR storage steel SSTL stainless steel SS solid surfacing SQ square SGC suspended gypsum ceiling suspended sheet vinyl SUSP SV south suspended acoustical ceiling sanitary S SAC SAN soap dispenser SCH SD SEC solid core SC schedule section sheet similar space SHT SIM SP special SPEC SPL SPM square foot specification single-ply membrane SF unit dimension underwriters laboratories unfinished unless noted otherwise UD UL UNF UNO verify in field VIF SET NO. SEAL field verify FV gypsum wall board GWB GLBLK glass block gypsum board GB ROOM NUMBER ROOM NAME WAITING 107 3 REVISION NUMBER & TYPE 405 GRAND AVE. DAYTON, OHIO 45409 JULY 24, 2019 - FIT OUT AND MEP GRANDVIEW MEDICAL CENTER USE GROUP: I-2 (HOSPITAL) CONSTRUCTION TYPE: 1-A (UNLIMITED AREA) RENOVATED AREAS: PHARMACY CLEAN RM - 3,358 SQ. FT. FIRE SUPPRESSION: FULLY SUPPRESSED IN AREAS OF RENOVATION NUMBER OF STORIES: 5 OCCUPANT LOAD REMAINS UNCHANGED AND NO NEW AREA WILL BE ADDED TO THE BUILDING. * N.F.P.A. 101 - LIFE SAFETY CODE, 2012 EDITION. * THE OHIO BUILDING CODE, INCLUDING THE MECHANICAL, ELECTRICAL EXISTING CONSTRUCTION IS SHOWN TO DEMONSTRATE INTEGRATION OF THE NEW WORK WITH THE EXISTING SYSTEM OF FIRE AND SMOKE BARRIERS. THE EXISTING CONSTRUCTION SHOWN IS PRESUMED TO BE IN COMPLIANCE WITH APPLICABLE CODES. CODE COMPLIANCE PLANS INDICATE RATED WALL CONSTRUCTION, FIRE SEPARATION AND SMOKE PARTITIONS IN CONFORMANCE WITH APPLICABLE CODES FOR NEW AND REMODELED CONSTRUCTION. THE DRAWINGS HAVE BEEN REVIEWED FOR CONFORMANCE TO: 1. AND PLUMBING CODES, 2017 EDITION. 2. 3. CODE AND STANDARDS: CODE DATA: 480 VANTAGE POINT, SUITE 201 PROJECT ARCHITECTS PINNACLE ARCHITECTS DAYTON, OHIO 45342 DAYTON, OHIO 45409 MECHANICAL ELECTRICAL CONSULTANTS 1400 WEST DOROTHY LANE HEAPY ENGINEERING AREA OF WORK O MICHAEL 7744 TAYLOR T. O T S T A O E F I H E S T E I G R T H I R D R E A C C T E PHARMACY CLEAN RM.(USP 800 COMPLIANCE) RENOVATION VICINITY MAP: N SHOP DRAWINGS SHOWING MORE DETAIL ON PRODUCT SPECIFICATIONS & INTERIOR ELEVATIONS & STOREFRONT WALLS & MOVEABLE & FIXED EQUIPMENT. CARTER HEALTH/ MIDWEST MEDICAL SYSTEMS CHP 101 GENERAL INFORMATION, CALCULATIONS CHP 201-202 FLOOR PLANS CHP 301-305 SECTIONS CHP 401-404 WALL ELEVATIONS CHP 501 CEILING PLANS CHP 601-603 CUT SHEETS AND SPECIFICATIONS CHP 701 NOT USED LEGEND, SPECS AND SHEET INDEX ELECTRICAL SCHEDULES SINGLE LINE DIAGRAM BASEMENT AND ROOF PLANS FIRST FLOOR - ELEC. DEMOLITION PLAN FIRST FLOOR - LIGHTING PLAN FIRST FLOOR - POWER & SYSTEMS PLAN E001 E002 E003 E004 E101 E201 E301 M001 M002 M003 M004 M005 M007 M008 M101 M201 M301 MECHANICAL LEGEND, GENERAL NOTES, INDEX OF DRAWINGS MECHANICAL SCHEDULES MECHANICAL DETAILS MECHANICAL DETAILS MECHANICAL DETAILS MECHANICAL CONTROL SCHEMATICS MECHANICAL CONTROL SCHEMATICS PARTIAL FIRST FLOOR PLAN - DEMOLITION PARTIAL FIRST FLOOR PLAN - NEW WORK HVAC ROOF PLUMBING LEGEND AND SHEET INDEX SCHEDULES AND SPECIFICATIONS PARTIAL BASEMENT PLAN - DEMOLITION PARTIAL FIRST FLOOR PLAN - DEMOLITION PARTIAL BASEMENT PLAN - NEW WORK PARTIAL FIRST FLOOR PLAN - NEW WORK P001 P002 P100 P101 P200 P201 PLUMBING MECHANICAL ELECTRICAL 1 1 A1 - FLOOR PLAN A2 - ELEVATIONS A3 - ELEVATIONS AND DETAILS A4 - SECTIONS AND DETAILS E1 - ELECTRICAL, DATA, PLUMBING PLAN C1 - REFLECTED CEILING PLAN MIDWEST MEDICAL SYSTEMS

 · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

EQUIP equipment

perimeterPERIM

janitorJANbasementBSMTgalvanizedGALV

CPT carpet

glassGL

gypsum boardGYP.BD.

CY cubic yardCTC center to center

general contractor

gypsum board ceilinggypsum board soffit

gypsum board bulkhead

GCGBSGBCGBBcrash rail

CRBCR

ceramic tilecourse(s,ing)

CTCRS

coved resilient base

futureFUT

footingFTG

FA fasten, fastener

existingEXIST

CONST construction

CLS closure

CL centerline of

CH channel

gage, gaugeGA

caulk(ing)CLK

CLO closet

BUL bulletinBUR built-up roof

framefireproof(ing)

FRFP

ceramic mosaic tile

clear

CMT

CLR

furred(ing)

feet or foot

FUR

FT

continuousconcrete

CONTCONCCOL

contractorCORRCONTR

corridor

column

FRT fire retardant

concrete masonry unitCMU

each wayEW

exterior

EXP

EXT

exhaustEXHexpansion

face brickFBFDFE

fire extinguisher cabinetfinish floor elevationFFE

FFLFGL

FEC

cabinetcarpet basecubicle curtaincubicle curtain trackcubic feet

foundation

FHCFINFLRFND

face of concreteface of masonry

FOCFOM

contr. furnished, contr. installedcorner guard

chamfercircumferencecontrol joint

ceiling

contract limit line

floor drainfire extinguisher

finish floor linefiberglassfire hose cabinetfinish(ed)floor(ing)

CABCBCCCCTCFCFCICG

CHAMCIRCCJ

CLG

CLL

mouldingMLD

marker boardMRKBD

movableMOVmasonry openingMO

mount(ed),(ing)metal

MP

MTMTL

multi-paint

mediumMED

LTWT lightweight

LTG lightinglightlow point

LTLP

LAM laminated

KO knock out

PTD paper towel dispenser

LVR louver

PLPG

plastic laminateplate glass

plaster

PNLPLWDPLSTRPLC

pounds per square footPSFPRPP

panel

pairpush plate

plywood

plastic laminate clad

PSI pounds per square inch

jointJT

kitchen

kick plate

length, long

lavatory

KIT

KPL

L

LAVLBL

linear footlong leg horizontallong leg vertical

level

masonry

lintel

LFLLHLLV

LVL

MAS

LTL

label

mechanical

manufacturer

maximum

miscellaneousminimum

MAXMECH

MFR

MISCMIN

MAT material

EIFS ext. insulation & finish sys.

BC bottom of curb

ASPH asphalt

depth, deepD

detaildemolitiondouble

DETDEMODBL

dimensiondiagonaldiameter

DIMDIAGDIA

drinking fountainDF

anchor bolt

door openingDODN

drawer

downspoutdoor

DWRDWGDSDR

acousticaladdendumadjustableabove finish flooralternatealuminumanodized

above

drawing

down

expansion bolteacheast

EBEAE

electric(al)elevationexpansion joint

each face

ELECELEJ

EF

access panelarchitectural

boardbumper guardbituminous

equalelevator

EQELEV

blockingbench mark

bearing platebearingbrick

bottom

building

both sides

ABABVACOUSADDADJAFFALTALUMANODAPARCH

BDBGBITUMBLDGBLKGBMBOTBPLBRGBRKBS

pre-formed composite metal panel

owner furnished, owner installedowner furnished, contr. installed

NC no ceiling

PCMPPCC pre-cast concrete

MTLFUR metal furringMUL mullion

HT heighthigh pointHP

GMU glazed masonry units

ounceOZ

NOMNO

nominalnumber

on centerOCOA

outside diameter

OHOFOIOFCIOD

overhead

overall

openingOPG

P

OPP

particle boardPBDpaint

opposite

gravelgrab bargrade

hardboard

height, high

groutGRVLGRBGR

HDBD

H

GT

hardwood

hollow core

heating, ventilating, air-conditioninghorizontal

hollow metalHDWDHDW

HC

HVACHORZ

HM

interiorinsulationinclude(d),(ing)

invertINTINSULINCL

INV

inside diameterID

hardware

not to scaleNTS

millwork

north

not in contract

MWK

N

NIC

A-0A-1A2-1A3-0A5-1A6-1A11-1

CODE COMPLIANCE PLANDEMOLITION PLANPHARMACY CLEAN RM. PLANDOOR SCHEDULE, WALL/FRAME TYPE, DETAILSREFLECTED CEILING PLAN - ROOF PLANINTERIOR ELEVATIONSFINISHES AND FINISH PLAN

GRAVEL

NOTE REFERENCE

LINTEL TYPE

METAL

BRICK

CONCRETE

CEILING HEIGHT

CONCRETE MASONRY UNIT

REFERENCE DRAWING NUMBERDETAIL NUMBER

COLUMN REFERENCE

TEST BORING WALL TYPE

DOOR NUMBER

WINDOW NUMBER

L-1

PLASTIC LAMINATE

SHIM

WOOD, FRAMING

WOOD, FINISH

PLYWOOD

LOUVER TYPE

ELEVATION LETTER

REFERENCE DRAWING NUMBER

REFERENCE DRAWING NUMBERSECTION NUMBER

EXISTING POINT ELEVATION

NEW CONTOUR

NEW POINT ELEVATION

EXISTING CONTOUR

INSULATION, BATT

INSULATION, RIGID

GRID LINES

PROJECT TITLE:

ABBREVIATIONS:

SYMBOLS LEGEND:

PROJECT TEAM: DRAWING INDEX:

CARD READER

COVER

ELEVATION

MTL STUD

ARCHITECTURAL

EARTH

GYPSUM BOARD/PLASTER

SVGC suspended vinyl gypsum ceilingrough openingROROWRUB

right of wayrubber

windowwood

weight

waterproof(ing)waterstopwainscot

welded wire meshwall to wall

WINWD

WTWSCT

WPWS

WWMWTW

quantityQTY

PTN partitionpolyvinyl chloridePVC

QTQTR RD

quarry tilequarter round

radius

reference

RADRDREFREINF

requiredresilient

revision

REQ'DRESILRETREV

roof drain

reinforcing

return

reflectedRFLRM

riserR

room

TMPRD tempered

TEL telephonetop of curb

temporarytongue and groovethick(ness)

top of pavement

top of slab

tread

toilet paper dispenser

TC

TEMPT&GTHK

TP

TSTTSL

T

TPD

typicaltop of wall

verticalvinyl composition tilevapor barrier

west, width, wide

vinyl wall coveringveneer

TWTYP

VERTVCTVB

W

VWCVNR

top of steel

water closetwood base

WCWB

sanitary napkin dispenserSND

STRUC structural

STD standardSTLSTOR storage

steel

SSTL stainless steelSS solid surfacingSQ square

SGC suspended gypsum ceiling

suspendedsheet vinyl

SUSPSV

southsuspended acoustical ceilingsanitary

SSACSAN

soap dispenserSCHSDSEC

solid coreSCschedule

section

sheetsimilar

space

SHTSIM

SP

specialSPECSPLSPM

square foot

specification

single-ply membrane

SF

unit dimensionunderwriters laboratoriesunfinishedunless noted otherwise

UDULUNFUNO

verify in fieldVIF SET NO. SEALfield verifyFV

gypsum wall boardGWB

GLBLK glass block

gypsum boardGB

ROOM NUMBERROOM NAMEWAITING

107

3 REVISION NUMBER& TYPE

405 GRAND AVE. DAYTON, OHIO 45409JULY 24, 2019 - FIT OUT AND MEP

GRANDVIEW MEDICAL CENTER

USE GROUP: I-2 (HOSPITAL)

CONSTRUCTION TYPE: 1-A (UNLIMITED AREA)

RENOVATED AREAS: PHARMACY CLEAN RM - 3,358 SQ. FT.

FIRE SUPPRESSION: FULLY SUPPRESSED IN AREAS OFRENOVATION

NUMBER OF STORIES: 5

OCCUPANT LOAD REMAINS UNCHANGED AND NO NEW AREAWILL BE ADDED TO THE BUILDING.

* N.F.P.A. 101 - LIFE SAFETY CODE, 2012 EDITION.

* THE OHIO BUILDING CODE, INCLUDING THE MECHANICAL,ELECTRICAL

EXISTING CONSTRUCTION IS SHOWN TO DEMONSTRATEINTEGRATION OF THE NEW WORK WITH THE EXISTINGSYSTEM OF FIRE AND SMOKE BARRIERS. THE EXISTINGCONSTRUCTION SHOWN IS PRESUMED TO BE INCOMPLIANCE WITH APPLICABLE CODES.

CODE COMPLIANCE PLANS INDICATE RATED WALLCONSTRUCTION, FIRE SEPARATION AND SMOKEPARTITIONS IN CONFORMANCE WITH APPLICABLE CODESFOR NEW AND REMODELED CONSTRUCTION.

THE DRAWINGS HAVE BEEN REVIEWED FOR CONFORMANCE TO:1.

AND PLUMBING CODES, 2017 EDITION.

2.

3.

CODE AND STANDARDS:

CODE DATA:

480 VANTAGE POINT, SUITE 201PROJECT ARCHITECTSPINNACLE ARCHITECTS

DAYTON, OHIO 45342

DAYTON, OHIO 45409MECHANICAL ELECTRICAL CONSULTANTS1400 WEST DOROTHY LANE

HEAPY ENGINEERING

AREA OF WORK

O

MICHAEL

7744TAYLOR

T.

OTSTA

OE FIH

EST

E

I

GR

T

H IRDRE A C

C

TE

PHARMACY CLEAN RM.(USP 800 COMPLIANCE) RENOVATION

VICINITY MAP: N

SHOP DRAWINGS SHOWING MORE DETAIL ONPRODUCT SPECIFICATIONS & INTERIORELEVATIONS & STOREFRONT WALLS &MOVEABLE & FIXED EQUIPMENT.

CARTER HEALTH/ MIDWEST MEDICAL SYSTEMS

CHP 101 GENERAL INFORMATION, CALCULATIONSCHP 201-202 FLOOR PLANSCHP 301-305 SECTIONSCHP 401-404 WALL ELEVATIONSCHP 501 CEILING PLANSCHP 601-603 CUT SHEETS AND SPECIFICATIONSCHP 701 NOT USED

LEGEND, SPECS AND SHEET INDEXELECTRICAL SCHEDULESSINGLE LINE DIAGRAMBASEMENT AND ROOF PLANSFIRST FLOOR - ELEC. DEMOLITION PLANFIRST FLOOR - LIGHTING PLANFIRST FLOOR - POWER & SYSTEMS PLAN

E001E002E003E004E101E201E301

M001

M002M003M004M005M007M008M101M201M301

MECHANICAL LEGEND, GENERAL NOTES, INDEXOF DRAWINGSMECHANICAL SCHEDULESMECHANICAL DETAILSMECHANICAL DETAILSMECHANICAL DETAILSMECHANICAL CONTROL SCHEMATICSMECHANICAL CONTROL SCHEMATICSPARTIAL FIRST FLOOR PLAN - DEMOLITIONPARTIAL FIRST FLOOR PLAN - NEW WORKHVAC ROOF

PLUMBING LEGEND AND SHEET INDEXSCHEDULES AND SPECIFICATIONSPARTIAL BASEMENT PLAN - DEMOLITIONPARTIAL FIRST FLOOR PLAN - DEMOLITIONPARTIAL BASEMENT PLAN - NEW WORKPARTIAL FIRST FLOOR PLAN - NEW WORK

P001P002P100P101P200P201

PLUMBING

MECHANICAL

ELECTRICAL

1

1

A1 - FLOOR PLANA2 - ELEVATIONSA3 - ELEVATIONS AND DETAILSA4 - SECTIONS AND DETAILSE1 - ELECTRICAL, DATA, PLUMBING PLANC1 - REFLECTED CEILING PLAN

MIDWEST MEDICAL SYSTEMS

Page 2:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

UP 8R

5

3

4

8

13

14

CARDIOLOGY SUITENON-SLEEPING SUITE - 5,205 SQ. FT.

SUITE - 834 SQ. FT.

PHARMACY STAFF SUITENON-SLEEPING SUITE -2,483 SQ. FT.

CORRIDOR1526

MGR. OFC1545

ORDER ENTRY OFC1544

BULK STORAGE1537A

ADA STAFF TOILET1547

RECEIVING1548

CORRIDOR1527

PACKAGING1550 JAN

1533

POP1538

NARC RM1539

ORDER ENTRY1537

CHEMO RM1541

ANTI RM1542

IV RM1543

OFC1546

HD NON-STERILE1540

CORR.1535

1539

HVAC1542A

PHARMACY SUITENON-SLEEPING SUITE - 3,358 SQ. FT.CR

CR

CR

CODE LEGENDNON-COMBUSTIBLESMOKE RESISTANTWALL PARTITION

1-HR RATEDSMOKE BARRIER

1-HR. RATED WALL

2-HR. RATED WALL

3-HR. RATED WALL

O

MICHAEL

7744TAYLOR

T.

OTSTA

OE FIH

EST

E

I

GR

T

H IRDRE A C

C

TE

CODE COMPLIANCE PLAN

Page 3:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

REMOVE EXIST. WALL PARTITIONREMOVE EXIST. DOOR, FRAME & HARDWAREREMOVE EXIST. CASEWORKREMOVE EXIST. PLUMBING FIXT. & CAP UTILITIESREMOVE EXIST. FLOORING & BASE & PREP FLOORSLAB FOR NEW FINISH MATERIAL SPECIFIED.EXISTING WALL PARTITION TO REMAINEXISTING DOOR, FRAME & HARDWARE TO REMAINEXISTING PTS TO REMAINREMOVE WINDOW.CUT STRAIGHT LINE WHERE FLOORING IS TOREMAINREMOVE PORTION OF WALL FOR NEW DOORINSTALLATIONSHORE EXISTING 2ND FLOOR STRUCTURE & WALLBEFORE REMOVING SECTION OF WALL FOR NEWOPENING -PROVIDE LINTEL ANGLES/BEAM OVERNEW OPENING IN THE BEARING WALL.REMOVE EXISTING LOCKERSDUST PARTITION & TEMPORARY CONST. ACCESSDOOR. PROVIDE STICKY MATS AND HEPAFILTRATION SYSTEM. ADJACENT PHARMACY"CLEAN SPACE" SHALL NOT BE COMPROMISED.REMOVE PORTION OF WALL FOR NEW ACCESSDOOR/FRAME INSTALLATION.USE CAUTION WHEN DEMOLISHING WALLS INTHESE MAIN POWER CONDUIT LOCATIONS.COORDINATE SAW CUTS/REMOVALS IN EXIST.CONCRETE WALL W/ ARCHITECT & STRUCTURALENGINEER.REMOVE ORIGINAL WINDOWS & FRAMES.

INFILL OLD WINDOW OPENINGS WITH FULL WYTHCMU'S - BEFORE CUTTING NEW RAMP OPENING &INSTALLATION OF NEW LINTEL.

1.2.3.4.5.

6.7.8.9.

10.

11.

12.

13.14.

15.

16.

17.

18.

19.

GENERAL DEMOLITION NOTES:ALL OBJECTS TO BE DEMOLISHED ARE SHOWN DASHED.

IF THE CONTRACTOR SUSPECTS OR DISCOVERSEXISTING PRODUCTS CONTAINING ASBESTOS/HAZARDOUS MATERIALS DURING THE COURSE OF THEWORK, HE IS EXPECTED TO STOP WORK AND ISOLATETHAT PRODUCT, NOTIFY THE OWNER OF ITS PRESENCEAND PROVIDE CLEAR ACCESS TO THE OWNER FOR ITSREMOVAL AND DISPOSAL.

THE GENERAL CONTRACTOR WILL BE RESPONSIBLE FORTHE COORDINATION BETWEEN THE PLUMBING,ELECTRICAL AND MECHANICAL CONTRACTORS BEFOREAND DURING DEMOLITION.

ALL PLUMBING AND ELECTRICAL DISCONNECTIONS ARETO BE TERMINATED AT THE NEAREST BRANCH. SEEPLUMBING & ELECTRICAL DWGS AND SPECS.

PROTECT ALL EXISTING TO REMAIN WALLS,CASEWORK, DOORS, WINDOWS, CEILINGS, FURNITURE& EQUIPMENT DURING DEMOLITION. REPAIR ORREPLACE ANY ITEMS DAMAGED DURINGCONSTRUCTION.

MAINTAIN ALL EGRESS PATHS AND FIRE RATEDASSEMBLIES THROUGHOUT CONSTRUCTION,INCLUDING PATCHING OF ALL HOLES EXPOSED INFLOOR CONSTRUCTION WITH 2 HOUR RATED FIRESAFING. BRACE & SHORE UP WALL ABOVE UNTIL NEWLINTEL CAN BE INSTALLED.

REMOVE ALL EXISTING FIXED MEDICAL EQUIPMENTAND RETURN TO OWNER.

PROVIDE HEPA FILTERS AND PROPER INFECTIONCONTROL DEVICES AND SYSTEMS THROUGHOUTCONSTRUCTION. THE PHARMACY IS A CLEAN SPACEAND IN SOME AREAS STERILE AND MUST BEPROTECTED AT ALL TIMES.

A.

B.

C.

D.

E.

F.

G.

H.

O

MICHAEL

7744TAYLOR

T.

OTSTA

OE FIH

EST

E

I

GR

T

H IRDRE A C

C

TE

DEMOLITION PLAN

Page 4:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

RAMP

CORRIDOR1526

MGR. OFC1545

ORDER ENTRY OFC1544

BULK STORAGE1537A

ADA STAFF TOILET1547

RECEIVING1548

CORRIDOR1527

PACKAGING1550

JAN1533

POP1538

NARC RM1539

ORDER ENTRY1537

CHEMO RM1541

ANTI RM1542

IV RM1543

OFC1546OFC1546

HD NON-STERILE1540

24'-6

"

13'-8"

5"

16'-318" 47

8" 3'-6"

478"

8'-8

"47 8"

7'-0

"

6"

8'-8

"

7'-11"

6'-6

"47 8"

7'-5

1 8"

6"

CG-1

CG-1CORR.

1535

47 8"11

'-2"

47 8"

13'-0"478"1'-6"

618"

7'-3

"

47 8"

CG-1

CG-1

CG-1

CG-1

CG-1

8'-0"

478"

478"

4'-1034"

16'-0

"1'

-0"

1'-0

"

1539

9'-334" 47

8"

5'-4

3 4"

47 8"

CG-2CG-2

CG-1

CG-1CG-1 CG-1

CG-1

CG-1

CG-1

CG-1

4'-2

7 8"

4'-0"5'-6"

2'-4

"1'

-0"

CG-1

HVAC1542A

CG-1

9'-1

3 8"47 8"

10'-0

"47 8"

5'-9

"

11'-1118"

478"

9'-758"

478"9'-75

8"478"20'-01

8"

12'-1

11 4"5'

-111 2"

47 8"

4'-0

"

9'-5

1 8"

90 MIN FIRE RATED.PAINTED STEELACCESS PANEL ANDFRAME -3'-0" X 5'-6" DOORIN EXISTING OPENING

CG-1CG-1

CG-1

5'-4

3 8"

4'-6

"

5'-358"

CR

CR

SIM

41 4"

MH

CG-1

CR

NEW BIO CLEAN ROOM WALL PARTITION SYSTEMW/ INTEGRAL GLASS WINDOW LIGHTS. YKKAP, YES45 FS/F1 ALUM. STOREFRONT SYSTEM OR EQUALWITH 14" CLEAR TEMPERED GLAZING (MW)NEW 7' WIDE AUTO SLIDING ALUMINUM & GLASSDOORS WITH INTERLOCK BESAM SL500 CLEANROOM AUTO ALUM. SLIDER W/ 14" CLEARTEMPERED GLAZING PANELS (MW)LOW WALL RETURNS & WALL ENCLOSURES -SEEMECH DWGS.PASS THRU BOX (MW)BENCH SEAT (MW)SINK W/ EYEWASH (MW) - SEE PLUMB'G DWGSSUSP. GWB CEILING SYSTEM 58" TYP 'X' GWB ON 12"METAL SUSP. SYSTEM HUNG FROM STRUC.ABOVE(BY OWNER)NEW SHEET VINYL FLOORING W/ FLASH COVE BASAND HEAT WELDED SEAMS.NEW VAV ABOVE CEILING - SEE MECH DWGS.NEW COUNTER & BASE CABINETSNEW SINK - SEE PLUMBING DWGS.NEW EXHAUST DUCTWORK ABOVE CEILING - SEEMECH DWGS.NEW EXHAUST DUCT THRU WALL & EXTEND UPABOVE ROOF OF BUILDINGNEW DOOR, FRAME AND HARDWARERELOCATED DOOR, FRAME AND HARDWARERELOCATED CASEWORK AND/OR EQUIPMENTNEW ABOVE CEILING MECHANICAL UNIT - SEEMECH DWGS.SEALED CLEAN ROOM LED LIGHT FIXTURES (MC) -SEE ELECT. DWGS.LAMINAR FLOW HOOD UNIT (MC)CLEAN ROOM MOBILE STORAGE UNITS (MC)EXISTING DOOR TO REMAINPASS THRU REFRIGERATOR (MW)IV PASS THRU (MW)NEW MECHANICAL UNIT - SEE MECH. DWGSNEW PNUEMATIC TUBE STATION - BY OWNER -ENCLOSURE BY G.C. - COORD. W/ OWNER'SSUPPLIERPHARMACY SHELVING & EQUIPMENT (MW)WORK TABLE (MC)ADA RAMP UP TO OLD PHARMACY SPACENEW TOILET - SEE PLUMB'G DWGSNEW WALL PARTITIONNEW DOUBLE TIER LOCKERSNEW ALUMINUM STOREFRONT SYSTEMNEW DOOR, FRAME AND HARDWARENEW FFE (BY OWNER)NEW FLOORING & BASEPAINT ALL WALLS. NEW WALLS: 1 PRIME COAT & 2FINISH COATS, EXISTING WALLS: 1 FINISH COATNEW COUNTER MOUNTED SINK (MW)EXISTING WALL TO REMAINSET NEW FURRED OUT WALL AS TIGHT TO EXISTINCONDUIT AS POSSIBLE.CLEAN UP MASONRY JAMBS & COVER W/ FURRINGAND GWB. ALSO ADD A PAIR OF STEEL ANGLELINTELS WHERE HOLE HAS BEEN CUT THRUMASONRY WALL BEFORE INSTALLING NEW ACCESSDOOR AND FRAME.NEW METAL DIAMOND PLATE STEPS. 11" WIDE XMAX 7" TALL DOWN INTO HVAC ROOM. PROVIDEGALV. STEEL ANGLE AT TOP STEP TO HOLDSTRINGERS.ADD WATERPROOF PAINT" ZINSSER WATERTITE - LLOW VOC 7 MILDEW PROOF TO EXTERIORCONCRETE WALL FROM FLOOR TO DECK BEFOREINSTALLATION OF PVC MEMBRANE.TEMPORARY WALL - REMOVE ONCE NEWPHARMACY HAS BEEN CONSTRUCTED AND CAN BESECURED.COPIER BY OWNERRECESSED ELECTRIC PANEL - SEE ELEC. DWGS.

1.

2.

3.

4.5.6.7.

8.

9.10.11.12.

13.

14.15.16.17.

18.

19.20.21.22.23.24.25.

26.27.28.29.30.31.32.33.34.35.36.

37.38.39.

40.

41.

42.

43.

44.45.

NEW CONSTRUCTION NOTES:*

GENERAL NOTES:GENERAL CONTRACTOR TO PATCH/REPAIR ANYAND ALL WALLS AND FLOORS DAMAGED BYCONSTRUCTION BEFORE APPLYING FINISHES.

CONTRACTOR SHALL INSTALL F.R.T. BLOCKING INWALLS OR CEILINGS TO SUPPORT ALL MOUNTEDFIXTURES / EQUIPMENT.

C.P.U.'s ARE TO BE LOCATED OFF THE FLOOR.C.P.U. BRACKETS ARE TO BE O.F.O.I.

ALL MOUNTING BRACKETS FOR TV's / MONITORSTO BE O.F.C.I.

ADJUSTABLE MONITOR BRACKETS ARE TO BEO.F.O.I.

TAKE SPECIAL CARE TO PROTECT HIGH POWERVERTICAL & HORIZ. CONDUIT LINES THAT AREEXISTING THROUGHOUT THIS SPACE.

FIRE CAULK - SEAL ALL HOLES IN EXISTING WEST &NORTH WALLS TO PROVIDE A CONTINUOUS 2HOUR FIRE BARRIER SYSTEM.

A.

B.

C.

D.

E.

F.

G.

O

MICHAEL

7744TAYLOR

T.

OTSTA

OE FIH

EST

E

I

GR

T

H IRDRE A C

C

TE

NEW WORK PLAN

Page 5:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

1-1/2 PR. BB HINGES - HEAVY DUTY - US26D1 EA. ADA LEVER LOCKSET (STOREROOM) US26D1 EA. ELECTRIC STRIKE1 EA. OWNER'S CARD READER1 EA. SILL SWEEP1 EA. WALL STOP

HARDWARE SET 3

1-1/2 PR. BB HINGES - HEAVY DUTY - US26D1 EA. ADA LEVER LATCHSET (PASSAGE FUNCTION) US26D3 EA. DOOR FRAME SILENCERS1 EA. WALL STOP

HARDWARE SET 4

1-1/2 PR. BB HINGES - HEAVY DUTY - US26D1 EA. ADA LEVER LOCKSET (OFFICE FUNCTION) US26D3 EA. DOOR FRAME SILENCERS1 EA. WALL STOP

HARDWARE SET 2 1-1/2 PR. BB HINGES - HEAVY DUTY - US26D1 EA. ADA LEVER LATCHSET (PRIVACY FUNCTION) US26D1 EA. ADA PARALLEL ARM CLOSER3 EA. DOOR FRAME SILENCERS1 EA. WALL STOP1 EA. SIGNAGE "ADA" ACCESSIBLE RESTROOM

HARDWARE SET 5

1-1/2 PR. BB HINGES - HEAVY DUTY - US26D1 EA. ADA LEVER LOCKSET (OFFICE FUNCTION) US26D1 EA. ADA PARALLEL ARM CLOSER1 EA. WALL MOUNTED MAGNETIC HOLD OPEN TIED TO FIRE ALARM.3 EA. DOOR FRAME SILENCERS1 EA. WALL STOP

HARDWARE SET 1

G.C. TO PROVIDE

NOTES:1. MODIFY DOOR/ HARDWARE TO BE CONTROLLED BY OWNER SUPPLIED CARD READER. ADD NEW ELECTRIC STRIKE & POWER. COORDINATE WITH CARD READER CONSULTANT.2. REPAINT DOOR & FRAME.3. PROVIDE MFRS. STD. ADA HARDWARE, CLOSER, HINGES, WALL STOP ETC.4. AUTOMATIC ALUMINUM SLIDING DOOR WITH FULL BREAK OUT CAPABILITY. ISO3(CLASS 1) CLEAN ROOM RATED W/ WEATHERSTRIPPING. (MW)5. PROVIDE WALL MTD. MAGNETIC HOLD OPEN - TO RELEASE. ON ACTIVATION OF THE FIRE ALARM SYSTEM. DOOR SHALL HAVE ADA CLOSER.6. FIRE CAULK AROUND FRAME & PROVIDE 2 HOUR FIRE RATED CAULKING/ FIRESAFING SYSTEM AT DOOR/WALL INTERSECTION.7. ADD AN ADA PARALLEL CLOSER TO THIS DOOR IF NONE EXISTS.

DOOR TYPES

8"

8"1'-0"

2'-1

"

FLASH COVED VINYLFLOORING ON CLEAN

RM. SIDE-TYP.

412" W

5"5"

412" W

EXTEND STUDS & ONESIDE GWB TO DECK

ABOVE & SEAL

FRT WOOD BLOCKINGAT STOREFRONT HEAD W/

CONT. BEAD OF CAULKBOTH SIDES

AT CEILING TO CREATE ASEALED CLEAN RM.

ENCLOSURE

58" TYPE 'X' GWBFASTENED TO MTL.FRAMING SUSPENSIONSYSTEM

YKKAP ALUM.STOREFRONTFRAMING W/1/4"CLEAR TEMPEREDGLAZING (MW)

FLASH COVED VINYLFLOORING ON CLEAN

RM. SIDE-TYP.

YKKAP ALUM.STOREFRONTFRAMING W/1/4"CLEAR TEMPEREDGLAZING (MW)

58" TYPE 'X' GWBFASTENED TO MTL.FRAMING SUSPENSIONSYSTEM

1-1/2" MTL FRAMINGSYSTEM SUSP. FROMSTRUC. ABOVE

1"

FRT WOODBLOCKING ATSTOREFRONT

HEAD.

8'-0

"

8'-0

"

VINYL-FACEDDRYWALL PANELS

OR GWB SYSTEM. SEE PLAN.

G.C. TO PROVIDEGWB SOFFITS

7'-9

"

7'-2

"SINGLE

DOOR WIDTH

DOUBLE ENTRY

PAIR WIDTH

FRAME TYPES

BY ALUM.SLIDING DMANUF.

OR SLIDER

3-5/8" MT'L STUDS

FIRECODE 'X' EA. SIDE5/8" GYP. BD.

@ 16" O.C.

3-5/8" MT'L STUDS

5/8" GYP. BD.

@ 16" O.C.

FIRECODE 'X' EA. SIDE

BLANKET (S.A.B.)2" SOUND ATTENUATION

2 LAYERS -5/8" GYP. BD.

3-5/8 MT'L STUDS

FIRECODE "X" EA. SIDE.

@ 16" O.C.2" SOUND ATTENUATIONBLANKET (S.A.B.)

FIRECODE "X" EA. SIDE. 2 LAYERS -5/8" GYP. BD.

@ 16" O.C.3-5/8 MT'L STUDS

3-5/8 MT'L STUDS@ 16" O.C.

FIRECODE "X"5/8" GYP. BD. 5/8" GYP. BD.

FIRECODE "X"

@ 16" O.C.3-5/8 MT'L STUDS

BLANKET (S.A.B.)2" SOUND ATTENUATION

3-58" 58"

4-14"

3-58" 58"

4-14"

58"

3-58" 58"

6-18"

58"

3-58" 58"

6-18"

58"

3-58" 58"

4-78"

58"

3-58" 58"

4-78"

5/8" GYP. BD. FIRECODE TYPE 'X'

6 " BATT. INSULATION

ANTIMICROBIAL WATER RESISTANT GWB

6 MT'L STUDS@ 16" O.C.

918"

2" RIGID INSUL. W/ EIFS RAIN SCREENFINISH SYSTEM

5/8" GLASS FIBER FACED GWB EXT. SHEATHING

478"

2"

JAMB DETAIL

534"

5 8" 2"

HEAD DETAIL

534"5 8"

2"

478"

FRAME DETAILS

(2) 20 GA. 358" METAL STUDS

58" GYP. BD. EACH SIDE35

8" METAL STUDS @ 16" o.c.

CAULK PERIMITER(BOTH SIDES)

58" GYP. BD. EACH SIDE

358" METAL STUDS @ 16" o.c.

CAULK PERIMITER(BOTH SIDES)

FLASH COVED VINYLFLOORING ON CLEAN

RM. SIDE-TYP.

YKKAP ALUM.STOREFRONTFRAMING W/1/4"CLEAR TEMPEREDGLAZING (MW)

58" TYPE 'X' GWBFASTENED TO MTL.FRAMING SUSPENSIONSYSTEM

1-1/2" MTL FRAMINGSYSTEM SUSP. FROMSTRUC. ABOVE

FRT WOODBLOCKING ATSTOREFRONT

HEAD.

8'-0

" 8'-6

"

G.C. TO PROVIDEGWB SOFFITS

(7'-9

") IN

RM

. 154

0)BLANKET (S.A.B.)3" SOUND ATTENUATION

O

MICHAEL

7744TAYLOR

T.

OTSTA

OE FIH

EST

E

I

GR

T

H IRDRE A C

C

TE

STOREFRONT @ PERIMETER WALL STOREFRONT @ INTERIOR WALL

WALL TYPES

STOREFRONT @ INTERIOR WALL

Page 6:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

EXISTINGCEILING

N.C.

GBS @7'-81

2"

1.

2.

3.

4.

5.

NEW SUSP. GWB CEILING SYSTEM. 58" TYPE 'X' GWBON 1-1/2" METAL HANGING GRID SUPPORTED BYSTRUCTURE ABOVE.CUT/ MODIFY EXIST. SUSP. CEILING SYSTEM TOACHIEVE NEW DESIGN SHOWN. ATTACH MODIFIEDEXISTING CLG. TO NEW WALL.NEW STORE FRONT WALL SYSTEM TO ATTACH TOGWB CLG. & BE CAULKED ON BOTH SIDES ASDETAILED.NEW SEALED LIGHT FIXTURES & HVAC DIFFUSERS.(MC) SEE ELECT. & MECH DWGS.EXISTING SUSP. CLG - TO REMAIN. SEE ELECT. &MECH DWGS FOR MODIFICATIONS.

NEW CEILING NOTES:

- CUBICAL CURTAIN TRACKC.C.T.

ABBREVIATIONS

- NO CEILING- GYP. BD. BULKHEAD

- GYP. BD. SOFFIT

- GYP. BD. CEILING- GYP. BD. LIGHT COVE

G.B.B.

G.B.L.C.G.B.S.

G.B.C.

N.C.

LEGEND

SUPPLY DIFFUSERS

RETURN-AIR GRILLE

CEILING HEIGHT

LIGHT FIXTURES

GYP. BD. HEADER

NEW C.C.T.

ACCESS PANELS

EXIT SIGNS

COURTYARDEXTERIOR

NEW DUCT WORKFROM UNIT OVER ROOF & DOWN

INTO NEW PHARMACY

NEW AHU-24 (SEE HVAC DWGS)SET ON EXISTING STEEL FRAMEPLUS NEW INFILL STEEL - SEESTRUCTURAL DWGS. PROVIDESTEEL ACCESS LADDER ALSOSHOWN ON STRUCTURAL DWGS.

COURTYARDEXTERIOR

REMOVE EXISTING WINDOW& WALL BELOW & REPLACEW/ NEW 3' X 7' INSULATEDPTD H.M. DOOR & FRAME.W/ ADA CUSH TYPE PARALLELARM CLOSER. PROVIDETHERMALLY BROKEN ADATHRESHOLDWEATHERSTRIPPING PKGINCLUDING SILL SWEEP.

VARI

ES

SAC

EXISTING 10" CONC.STRUCTURAL FLOOR SLAB

714" 5'-61

4"

1ST FLR. 46' BLDG.

1ST FLR. 71' BLDG.

2ND FLR. 71 BLDG.

GRANULAR FILL@ GRADE INCOURTYARD

MEP SUB-CONTR. COORDALL NEW OPENG'S INCONC. WALL W/ STRUC. -ENG.& PROVIDEWATERTIGHT SEALANTSYSTEM AROUND ALLOPNGS.

EXISTING EXTERIORCOURTYARD

O

MICHAEL

7744TAYLOR

T.

OTSTA

OE FIH

EST

E

I

GR

T

H IRDRE A C

C

TE

NEW REFLECTED CEILING PLAN

ROOF PLAN

SECTION THRU MECH RM. 1542A

Page 7:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

ADA STAFF TOILET 1547 ADA STAFF TOILET 1547 ADA STAFF TOILET 1547 TUBE STATION

GB-30

TPGB-42

2'-9

"

1'-0"

2'-9"

GB-42

GB-30

2'-9

"

6"CL

MR1

3'-4

"

1'-6" 1'-9"±

2'-1

0"

SD(OFCI)

PTD(OFCI)

PTD(OFCI)

MR1

PTSPTS

7'-9

"

7'-9

"

CR-1 CR-1

7'-9

"

7'-9

"

UNIT BY OWNERSSUPPLIER - COORD.OPENINGS IN NEW GWBPARTITION W/ PTS SUPPLIER.

O

MICHAEL

7744TAYLOR

T.

OTSTA

OE FIH

EST

E

I

GR

T

H IRDRE A C

C

TE

RAMP DETAILRAMP DETAIL CAP DETAIL

Page 8:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

MGR. OFC1545

ORDER ENTRY OFC1544

BULK STORAGE1537A

ADA STAFF TOILET1547

RECEIVING1548

CORRIDOR1527

PACKAGING1550

JAN1533

POP1538

NARC RM1539

ORDER ENTRY1537

CHEMO RM1541

ANTI RM1542

IV RM1543

OFC1546OFC1546

HD NON-STERILE1540

CORR.1535

HVAC1542A

SV-2/FLASH COVESAC-2P-3

SV-1/ FLASH COVESAC-2P-3

SV-1/ FLASH COVE

SV-1/ FLASH COVE

SV-1/ FLASH COVE

SV-1/ FLASH COVE

SV-1/ FLASH COVE

CPT-1SAC-1P-1

SV-2/FLASH COVESAC-2P-3

SV-2/FLASH COVESAC-2P-3

SV-1/ FLASH COVESAC-2P-3

CPT-1SAC-1P-1

CPT-1SAC-1P-1

EXIS.EXIS.

SAC-2P-1

SAC-2P-1

SAC-2P-1

SAC-2P-1

SAC-2P-1

SV-1/ FLASH COVESAC-2P-1

CPT-1SAC-1P-1

SV-1/ FLASH COVESAC-2P-3

EXIS.

SEALED CONCRETE

CPT-1SAC-2P-1

EXIS.

6'-0

"

FLOORINGSV-1, GERFLOR, SYMBIOZ, COLOR MOLE. OWNER PROVIDED,CONTRACTOR INSTALLEDSV-2, GERFLOR, SYMBIOZ, COLOR COTTONCPT-1, EF CONTRACT, GEO ACCENTS II, GAC44 CITY THREADS

WALL BASECRB-1 JOHNSONITE, 4" COVE, COLOR 49 BEIGE

PAINTP-1 SW6386 NAPERYP-2 SW6106 KILIM BEIGE, METAL DOORS, DOOR FRAMESP-3 SW7010, WHITE DUCK

CEILING TILESAC-1 ARMSTRONG, OPTIMA, 3150 (24 X 24 X 34") SQUARE, WHITESAC-2 GRIDSTONE, CLEAN ROOM GYPSUM CEILING PANELS 2X2

FINISH LEGEND

O

MICHAEL

7744TAYLOR

T.

OTSTA

OE FIH

EST

E

I

GR

T

H IRDRE A C

C

TE

FINISH PLAN

Page 9:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

A1

P1 P1OR

A1

OH1

2

1

P2

B

P2

GENERAL FLOOR PLAN NOTES

RISER OR STACK NUMBER

DETAIL: B = DETAIL DESIGNATION P2 = SHEET W HERE DETAIL IS LOCATED

FIRE SUPPRESSION HAZARD CLASSIFICATION AND HAZARD CLASSIFICATION GROUP

SECTION: 1 = SECTION DESIGNATION P2 = SHEET W HERE DETAIL IS LOCATED

EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TO SCHEDULES.

EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK. LETTER DESIGNATIONS REFER TO SCHEDULES.

CONNECT TO EXISTING

PLAN NOTE. APPLIES ONLY TO THE SHEET W HICH IT IS SHOW N UNLESS NOTED OTHERW ISE.

DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

"UP TO" SYMBOL (ITEM ON FLOOR ABOVE)

10" 10"

ELEV: 8' - 0"ELEV: 8' - 0"

TOE: 3' - 0"

BOE: 0' - 6"

APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR BOTTOM OF EQUIPMENT, UNLESS NOTED OTHERW ISE

APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO CENTERLINE OF PIPE, UNLESS NOTED OTHERW ISE

FIRE SUPPRESSION SYMBOLSDOUBLE LINE SINGLE LINE

CONCEALED PENDENT SPRINKLER

FS

PIV

S

FIRE HYDRANT

FLOW SW ITCH

GATE VALVE OS&Y

INSTITUTIONAL PENDENT SPRINKLER

PENDENT SPRINKLER

POST INDICATOR VALVE

RECESSED PENDENT SPRINKLER

SIDE W ALL SPRINKLER

SUPERVISED VALVE

UPRIGHT SPRINKLER

PIPING SYMBOLSDOUBLE LINE SINGLE LINE

BOTTOM CONNECTION (45°)

BRANCH TEE CONNECTION (NOTE: BULLHEAD TEE'S ARE NOT PERMITTED)

DIRECTION OF PITCH

DROP

ELBOW DOW N

ELBOW UP

EXISTING PIPE TO BE REMOVED

EXISTING PIPE TO REMAIN

FLOW DIRECTION DESIGNATION

PUMP

RISE

TOP CONNECTION (45°)

TOP CONNECTION (90°)

BOTTOM CONNECTION (90°)

DD

RR

SPECIALTY GAS SYMBOLS

AIR OUTLET - LAB TYPE

VC

VC

CAR BON DIOXIDE OUTLET - H OSPITAL TYPE

M EDICAL AIR OUTLET - HOSPITAL TYPE

M EDICAL VACU UM INLET - HOSPITAL TYPE

NITROGEN OUTLET - H OSPITAL TYPE

NITROUS OXIDE OUTLET - HOSPITAL TYPE

OXYGEN OU TLET - HOSPITAL TYPE

W AGD INLET - HOSPITAL TYPE

NATURAL GAS OUTLET - LAB TYPE

VACUUM OU TLET - LAB TYPE

VAC UUM C LEAN ING STATION - W ALL

VACUUM CLEANING STATION - FLOOR

PLUMBING AND FIRE SUPPRESSION

PIPING DESIGNATIONS

DOM ESTIC COLD W ATER

DOM ESTIC HOT W ATER

DOM ESTIC HOT W ATER RETURN

EXISTING PIPE TO REMAIN

EXISTING PIPE TO BE REMOVED

HOT W ATER PIPE (140 DEGS. F.)

HOT W ATER PIPE (180 DEGS. F.)

HOT W ATER RETURN PIPE (140 DEGS. F.)

HOT W ATER RETURN PIPE (180 DEGS. F.)

ARGO N PIPE

COMPRESSED AIR PIPE

MEDICAL CARBON DIOXIDE PIPE

COMBINATION FIRE SUPPRESSION AND DOMESTIC W ATER SERVICE

DIESEL FUEL PIPE

SPRINKLER PIPE (DRY)

FIRE SUPPRESSION (STANDPIPE / SPRINKLER MAIN)

FIRE SERVICE

FUEL OIL FLOW LINE

FUEL OIL GAUGE LINE

FUEL OIL RETURN LINE

FUEL OIL SUPPLY LINE

NATURAL GAS PIPE

GARAGE DRAINAGE PIPE

GAS SERVICE

HYDROGEN PIPE

HELIUM PIPE

MEDICAL INSTRUMENT AIR PIPE

KITCHEN W ASTE PIPE

LABORATORY COMPRESSED AIR PIPE

LABORATORY VENT PIPE

LABORATORY VACUUM PIPE

LABORATORY W ASTE PIPE

MEDICAL NITROGEN PIPE

MEDICAL COMPRESSED AIR PIPE

MEDICAL-SURGICAL VACUUM PIPE

GASOLINE PIPE (NON-LEAD)

MEDICAL NITROUS OXIDE PIPE

NON-POTABLE

MEDICAL OXYGEN PIPE

(OVERFLOW ) SECONDARY STORM DRAINAGE PIPE

PROPANE GAS PIPE

PUMP DISCHARGE PIPE

PRE-ACTION / DELUGE SPRINKLER PIPE

PURE W ATER PIPE

SPRINKLER PIPE (W ET)

SANITARY DRAINAGE PIPE

SOFT COLD W ATER

SPRINKLER DRAIN PIPE

STORM DRAINAGE PIPE

FUEL TANK VENT PIPE

TRAP PRIMER DISCHARG E PIPE

TEMPERED W ATER PIPE

SANITARY SEW ER VENT

W ASTE ANESTHESIA GAS DISPOSAL PIPE

W ATER SERVICE

140

LV

180

140R

180R

AR

CA

CO2

CW S

DF

DS

F

FS

FOF

FOG

FOR

FOS

G

GD

GS

H2

HE

IA

IV

IW

LA

LV

LW

N2

MA

MV

NG

NO

NPW

O2

OD

P

PD

PS

PW

S

SAN

SCW

SD

STM

T

TP

TW

V

W AGD

W S

INDIR ECT VEN T PIPE

INDIRECT W ASTE PIPE

K

3

3

CHECK VALVE

T

P

FOB

FOT

SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR REQUIRED TYPE BASED ON APPLICATIONS)

CONCEN TRIC PIPE R EDUCER

ECCENTRIC PIPE REDUCER

PRESSURE GAUGE

TEMPERATURE GAUGE OR THERMOMETER

UNION

CLEANOUT

STRAINER

STRAINER W ITH A BLOW DOW N VALVE AND HOSE CONNECTION

DRAIN VALVE W ITH HOSE END CONNECTION

AUTOMATIC FLOW CONTROLLER W ITH P/T PLUG IN AND OUT

EXPANSION JOINT

PRESSURE REGULATING VALVE

SAFETY RELIEF VALVE. PIPE DISCHARGE AIR GAPPED TO FLOOR DRAIN UNLESS NOTED OTHERW ISE.

PRESSURE AND TEMPERATURE TEST PLUG

TRAP PRIMER

VACUUM GAUGE W ITH STOP

CLEANOUT TO GRADE OR FINISHED FLOOR

END CAP

MIXING FAU CET

PLUG

HOSE BIB

W ALL HYDRANT

PLUG VALVE

SHUTOFF VALVE AND BOX

SHUTOFF VALVE ON RISER

V

VB

TP

CO

COMBINATION SHUTOFF AND BALANCING VALVE (REFER TO SPECIFICATIONS FOR REQUIRED TYPE BASED ON APPLICATIONS)

BALL VALVE

BUTTERFLY VALVE

GATE VALVE

VALVES AND FITTINGSDOUBLE LINE SINGLE LINE

SOLENOID VALVES

P/T PRESSURE AND TEMPERATURE SAFETY RELIEF VALVE. PIPE DISCHARGE AIR GAPPED TO FLOOR DRAIN UNLESS NOTED OTHERW ISE.

FIRE DEPARTMENT VALVE

W ATER METERM

ACID VENT PIPEAV

ACID W ASTE PIPEAW

ABBREVIATIONS

AAP - AREA ALARM PANEL (MEDICAL GAS)AC - AIR COMPRESSOR OR AIR CONDITIONERACC - ACCESSACCU - AIR COOLED CONDENSING UNITAD - ACCESS DOOR OR AREA DRAINADB - ACID DILUTION BASINADJ - ADJUSTABLEAFF - ABOVE FINISHED FLOORAFG - ABOVE FINISHED GRADEALT - ALTERNATEAP - ACCESS PANELAPPROX - APPROXIMATEAR - AIR RECEIVER OR ARGONARCH - ARCHITECT OR ARCHITECTURALASSY - ASSEMBLYAV - ACID VENTAW - ACID W ASTE

BDD - BACK DRAFT DAMPERBFP - BACKFLOW PREVENTERBLDG - BUILDINGBOB - BOTTOM OF BEAMBOD - BOTTOM OF DUCTBOE - BOTTOM OF EQUIPMENTBOF - BOTTOM OF FOOTINGBOG - BOTTOM OF GRILLEBOP - BOTTOM OF PIPEBOT - BOTTOMBT - BATHTUBBTU - BRITISH THERMAL UNITBTUH - BRITISH THERMAL UNIT PER HOURBTW N - BETW EEN

CA - COMPRESSED AIRCB - CATCH BASINCBD - COUNTER BALANCED BACKDRAFT DAMPERCFCI - CONTRACTOR FURNISHED CONTRACTOR

INSTALLEDCFM - CUBIC FEET PER MINUTECHS - CHILLED W ATER SUPPLYCHR - CHILLED W ATER RETURNCI - CAST IRONCK - CLINICAL SINKCLG - CEILINGCMU - CONCRETE MASONRY UNITCO - CLEAN OUTCO2 - MEDICAL CARBON DIOXIDECONN - CONNECT OR CONNECTIONCONTR - CONTRACTORCORR - CORRIDORCS - CLINICAL SINK OR COLD SOFT W ATERCTR - CENTERCU - COPPERCW - COLD W ATERCW S - COMBINATION W ATER SERVICE

OR CONDENSER W ATER SUPPLYCW R - CONDENSER W ATER RETURN

D - DEPTH OR DRAIN LINEDD - DECK DRAINDET - DETAILDF - DRINKING FOUNTAIN OR W ATER COOLER

OR DIESEL FUELDFU - DRAINAGE FIXTURE UNITDI - DEIONIZED W ATERDIA - DIAMETERDIM - DIMENSIONDN - DOW NDS - DOW N SPOUT OR SPRINKLER (DRY)DT - PERFORATED DRAIN TILEDW G - DRAW ING

EA - EACHEC - ELECTRICAL CONTRACTOR (DIVISION 26)EEW - EMERGENCY EYE W ASHEJ - EXPANSION JOINTELEC - ELECTRICALELEV - ELEVATOREQ - EQUALEQUIP - EQUIPMENTET - EXPANSION TANKETR - EXISTING TO REMAINES - EMERGENCY SHOW EREQS - EQUIPMENT SUPPLIEREW C - ELECTRICAL W ATER COOLEREXH - EXHAUST AIREXP - EXPANSIONEXT - EXTERIOREX - EXISTING

F - FIRE SUPPRESSION (STANDPIPE/SPRINKLER MAIN)FCE - FIRE CONTROL EQUIPMENTFCO - FLOOR CLEANOUTFD - FLOOR DRAINFDC - FIRE DEPARTMENT CONNECTIONFDV - FIRE DEPARTMENT VALVEFF - FINISHED FLOOR ELEVATIONFHC - FIRE HOSE CABINETFLR - FLOORFM - FORCE MAINFOB - FLAT ON BOTTOM

FOF - FUEL OIL FLOWFOG - FUEL OIL GAUGEFOR - FUEL OIL RETURNFOS - FUEL OIL SUPPLYFOT - FLAT ON TOPFPM - FEET PER MINUTEFR - FIRE RISERFS - FLOOR SINK OR FIRE SERVICEFSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)FT - FEETFTG - FOOTING

G - GAS OR NATURAL GASGA - GAUGEGAL - GALLONGALV - GALVANIZEDGC - GENERAL TRADES CONTRACTORGD - GARAGE DRAINAGEGPM - GALLONS PER MINUTEGS - GAS SERVICEGW - GREASE W ASTE

H2 - HYDROGENHB - HOSE BIBBHC - HVAC CONTRACTOR (DIVISION 23)HD - HUB DRAINHE - HELIUMHG - REFRIGERANT HOT GASHP - HORSEPOW ER OR HIGH POINTHPC - HIGH PRESSURE CONDENSATE RETURNHPS - HIGH PRESSURE STEAM SUPPLYHPW - HIGH PURITY W ATERHPW R - HIGH PURITY W ATER RETURNHR - HOSE REELHT - HEAT TRACEHTR - HEATERHVAC - HEATING, VENTILATING, AND AIR CONDITIONINGHW - HOT W ATERHW R - HEATING HOT W ATER RETURNHW S - HEATING HOT W ATER SUPPLY

IA - MEDICAL INSTRUMENT AIRID - INSIDE DIAMETERINV - INVERT ELEVATIONIN - INCHESIV - INDIRECT VENTIW - INDIRECT W ASTE

JS - JANITOR SINK

K - KITCHEN W ASTEKEC - KITCHEN EQUIPMENT CONTRACTOR

L - LENGTHLA - LABORATORY COMPRESSED AIRLAV - LAVATORYLBS - POUNDSLCW - LABORATORY COLD W ATERLEC - LABORATORY EQUIPMENT CONTRACTORLHW - LABORATORY HOT W ATERLHW R - LABORATORY HOT W ATER RETURNLPC - LOW PRESSURE CONDENSATE RETURNLPS - LOW PRESSURE STEAM SUPPLYLV - LABORATORY VACUUM OR LABORATORY VENTLW - LABORATORY W ASTE

MA - MEDICAL COMPRESSED AIRMAP - MASTER ALARM PANEL (MEDICAL GAS)MAX - MAXIMUMMB - MOP BASINMC - MECHANICAL CONTRACTOR (DIVISION 23)MEZZ - MEZZANINEMFR - MANUFACTURERMH - MANHOLEMIN - MINIMUM OR MINUTEMISC - MISCELLANEOUSMTD - MOUNTEDMTG - MOUNTINGMPC - MEDIUM PRESSURE CONDENSATE RETURNMPS - MEDIUM PRESSURE STEAM SUPPLYMU - W ATER MAKE-UPMV - MEDICAL SURGICAL VACUUM

N2 - MEDICAL NITROGENN/C - NORMALLY CLOSEDNG - GASOLINE (NON-LEAD)NIC - NOT IN CONTRACTN/O - NORMALLY OPENNO - MEDICAL NITROUS OXIDENOM - NOMINALNPW - NON-POTABLE W ATERNPT - NATIONAL PIPE THREADNTS - NOT TO SCALE

02 - MEDICAL OXYGENOA - OUTDOOR AIROD - OUTSIDE DIAMETER OR OVERFLOW DRAINOFCI - OW NER FURNISHED CONTRACTOR

INSTALLEDOFOI - OW NER FURNISHED OW NER INSTALLED

P - PROPANE GASPC - PLUMBING CONTRACTOR (DIVISION 22)

OR PUMPED CONDENSATE RETURNPD - PUMP D ISCHARGE OR PARAPET DRAINPIV - POST INDICATOR VALVEPLBG - PLUMBINGPS - PRE-ACTION/DELUGE SPRINKLER PRESS - PRESSUREPRV - PRESSURE REGULATING VALVEPSF - POUNDS PER SQUARE FOOTPSI - POUNDS PER SQUARE INCHPSV - PRESSURE SUSTAINING VALVEPSIG - POUNDS PER SQUARE INCH GAUGEPW - PURE W ATER

RA - RETURN AIRRAD - RADIUSRCP - REINFORCED CONCRETE PIPERD - ROOF DRAINREC - RECESSEDREQD - REQUIREDRI - ROUGH INRL - REFRIGERANT LIQUIDROS - REVERSE OSMOSIS W ATER SUPPLYROR - REVERSE OSMOSIS W ATER RETURNRPM - REVOLUTIONS PER MINUTERS - REFRIGERANT SUCTIONRV - RELIEF VALVE

S - SPRINKLER (W ET)SA - SHOCK ARRESTOR OR SUPPLY AIRSAN - SANITARY OR SANITARY DRAINSCH - SCHEDULESCW - SOFT COLD W ATERSD - SPRINKLER DRAIN OR SUBSOIL DRAINSH - SHOW ERSHT - SHEETSK - SINKSPEC - SPECIFICATIONSSQ - SQUARESR - SUPPLY RISERSS - SANITARY STACK (SOIL OR W ASTE) OR

STAINLESS STEELSTD - STANDARDSTM - STORM OR STORM DRAINAGESTRUC - STRUCTURAL OR STRUCTURESUC - SITE UTILITY CONTRACTOR

T - FUEL TANK VENTTD - TRENCH DRAINTEMP - TEMPERATURETOB - TOP OF BEAMTOD - TOP OF DUCTTOE - TOP OF EQUIPMENTTOF - TOP OF FOOTINGTOJ - TOP OF JOISTTOP - TOP OF PIPETOS - TOP OF SLAB OR TOP OF STEELTF - TRAP FILLERTP - TRAP PRIMER OR TRAP PRIMER DISCHARGETW - TEMPERED W ATERTYP - TYPICAL

UR - URINALUNO - UNLESS NOTED OTHERW ISE

V - VENT OR SANITARY SEW ER VENTVAC - VACUUMVC - VACUUM CLEANINGVCV - VACUUM CLEANING VALVEVE - VACUUM EXHAUSTVEL - VELOCITYVIB - VALVE IN BOXVOL - VOLUMEVP - VACUUM PUMPVS - VENT STACKVTR - VENT THROUGH ROOFVR - VENT RISER

W / - W ITHW /O - W ITHOUTW - W ASTEW AGD - W ASTE ANESTHESIA GAS DISPOSALW C - W ATER CLOSETW CO - W ALL CLEANOUTW H - W ALL HYDRANT OR W ATER HEATERW IV - W ALL INDICATOR VALVEW S - W ATER SERVICE

YCO - YARD CLEANOUT

ZVC - ZONE VALVE CABINET

PIPE RISER

NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT

TO MODIFICATIONS ON OTHER DRAWINGS.

ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT

NECESSARILY BE USED ON THIS PROJECT. Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

5/2

01

9 7

:03

:44

AM

C:\

BIM

\Mod

el\20

19

-05

07

8-M

EP

-Ce

ntr

al_

WS

McC

am

ey.r

vt

2019-05078

ABN

W SM

July 24, 2019

P001

PLUMBING LEGENDAND SHEET INDEX

1 2019.07.24 ADDENDUM 1

SHEET INDEX - PLUMBING

SHEET NUMBER SHEET NAME

P001 PLUMBING LEGEND AND SHEET INDEX

P002 SCHEDULES AND SPECIFICATIONS

P100 PARTIAL BASEMENT PLAN - DEMOLITION

P101 PARTIAL FIRST FLOOR PLAN - DEMOLITION

P200 PARTIAL BASEMENT PLAN - NEW WORK

P201 PARTIAL FIRST FLOOR PLAN - NEW WORK

Page 10:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

DIVISION 21 & 22 SPECIFICATIONS

1. PROVIDE A COMPLETE RENOVATED PLUMBING AND FIRE SUPPRESSION SYSTEM AS SHOW N ON THE DRAW INGS AND AS SPECIFIED HEREIN. W ORK INCLUDES, BUT IS NOT NECESSARILY LIMITED TO THE FOLLOW ING PRINCIPAL CATEGORIES.

A. COMPLETE PLUMBING SYSTEMS CONSISTING OF MEDICAL GAS, DOMESTIC W ATER, SANITARY AND VENT SYSTEMS.

B. NEW "W ET PIPE" FIRE SUPPRESSION SYSTEM THROUGHOUT EXISTING SPACE.

C. ALTERATION W ORK IN THE EXISTING BUILDING.

D. SPACE IS EXTREMELY TIGHT. ELECTRONIC COORDINATION DRAW INGS ARE REQUIRED. COORDINATE REQUIREMENTS CLOSELY W ITH DIVISION 23.

2. W ORK SHALL BE PERFORMED BY CONTRACTORS THAT ARE FULLY CERTIFIED BY THE STATE OR AUTHORITY HAVING JURISDICTION.

3. OBTAIN AND PAY FOR ALL PERMITS, UPON COMPLETION. PROVIDE A CERTIFICATE OF APPROVAL FROM THE GOVERNING INSPECTION AUTHORITY.

4. DURING THE BIDDING PERIOD INSPECT THE SITE AND PREMISES OF THE PROPOSED W ORK. REPORT IMMEDIATELY ANY SIGNIFICANT OBSERVED DISCREPANCIES AS RELATED TO THE PLANS OR THE REQUIRED W ORK. ALL W ORK SHALL COMPLY W ITH OHIO PLUMBING CODE, OHIO BUILDING CODE,AND ALL OTHER APPLICABLE CODES, LAW S AND ORDINANCES.

5. TH IS CONTRACTOR SHALL GUARANTEE ALL W ORKMANSHIP, EQUIPMENT, AND MATERIAL ENTERING INTO THIS CONTRACT FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF ACCEPTANCE. ANY W ORK PROVEN TO BE DEFECTIVE DURING THIS PERIOD SHALL BE MADE GOOD BY THIS CONTRACTORW ITHOUT EXPENSE TO THE OW NER.

6. W HERE TRADE NAMES, BRANDS OR MANUFACTURERS ARE LISTED, ANY ONE OF THE SEVERAL NAMED ARE CONSIDERED EQUALLY ACCEPTABLE. NO UNNAMED PRODUCT OR MATERIAL SHALL BE USED UNLESS APPROVED IN W RITING BY THE ENGINEER. SUBMIT ELECTRONIC SHOP DRAW INGS ON MAJOR ITEMS OF EQUIPMENT AND MATERIALS.

A. PIPE, FITTINGS AND JOINING METHODS FOR THE VARIOUS SYSTEMS.

B. PIPE HANGERS.

C. PIPE INSULATION.

D. PLUMBING FIXTURES.

E. FIRESTOPPING.

F. SPRINKLERS, ACCESSORIES AND INSTALLATION DRAW INGS PER NFPA 13.

7. PLAN W ORK AS TO PROVIDE REASONABLE CONTINUOUS SERVICE OF EXISTING SYSTEMS. SHUTDOW N OF SYSTEMS AND W ORK UNDERTAKEN DURING SHUTDOW NS SHALL BE BID AS BEING DONE DURING NORMAL W ORKING HOURS. IF THE OW NER SHOULD REQUIRE SUCH W ORK BE PERFORMED OUTSIDE OF NORMAL W ORKING HOURS, REIMBURSEMENT SHALL BE MADE FOR PREMIUM TIME EXPENSES ONLY, W ITHOUT MARK-UP.

8. ALL PIPING PROVIDED IN THIS W ORK SHALL BE PRESSURE TESTED AS SPECIFIED BELOW .

A. DOMESTIC COLD AND HOT W ATER PIPING – HYDROSTATIC AT 125 PSI OR 1.5 TIME THE MAXIMUM SYSTEM OPERATING PRESSURE, W HICHEVER IS HIGHER, FOR 6 HOURS AT THE LOW POINT OF THE SYSTEM.

B. SOIL W ASTE AND VENT PIPING AND STORM PIPING – ROUGH TEST AND FINAL TEST IN CONFORMANCE TO THE PLUMBING CODE REQUIREMENTS.

C. FIRE SUPPRESSION PIPING – HYDROSTATIC AT 200 PSI M INIMUM, AND NOT LESS THAN 50 PSI ABOVE THE MAXIMUM SYSTEM PRESSURE, FOR A PERIOD NOT LESS THAN 2 HOURS.

9. DISINFECTION OF PIPING

A. ALL NEW DOMESTIC W ATER SYSTEMS INCLUDING ANY EXISTING DOMESTIC W ATER PIPING, TANKS AND EQUIPMENT OUT OF SERVICE FOR MORE THAN 30 DAYS SHALL BE DISINFECTED BY A COMPANY OR PERSONNEL REGULARLY ENGAGED IN THE PERFORMANCE OF TH IS SERVICE.

B. KEEP NEW SYSTEMS ISOLATED FROM THE EXISTING SYSTEMS UNTIL AFTER DISINFECTION IS COMPLETED AND PROVEN ACCEPTABLE BY BACTERIOLOGICAL TEST RESULTS. PROVIDE A SERVICE COCK AT THE POINT OF CONNECTION FOR INJECTION OF THE DISINFECTING AGENT. IF IT IS NECESSARY TO USE A POTABLE W ATER SUPPLY IN THE PERFORMANCE OF THE DISINFECTION PROCEDURES, PROVIDE TEMPORARY REDUCED PRESSURE ZONE BACK FLOW PREVENTION UNTIL DISINFECTION AND ANALYSIS RESULTS ARE COMPLETE.

C. THOROUGHLY FLUSH THE SYSTEM, AS PREVIOUSLY DESCRIBED, PRIOR TO DISINFECTION. DISINFECTION SHALL BE PERFORMED IN ACCORDANCE W ITH THE LOCAL AUTHORITIES PRESCRIBED METHOD, OR W HEN A LOCAL AUTHORITY PRESCRIBED METHOD IS NOT AVAILABLE, IN ACCORDANCE W ITH AW W A C651 OR AW W A C652 STANDARDS. D ISINFECTION SHALL BE BY MEANS OF A CHLORINE SOLUTION INJECTED INTO THE W ATER SYSTEM NEAR THE SOURCE. EACH OUTLET SHALL BE TESTED TO PROVE PRESENCE OF MINIMUM CHLORINE CONCENTRATION. DOCUMENT THAT ADEQUATE LEVELS OF CHLORINE ARE PRESENT IN ALL PARTS OF THE SYSTEM. FOLLOW ING THE APPROPRIATE RETENTION PERIOD, FLUSH OUT THE SYSTEM W ITH CLEAN W ATER UNTIL THE RESIDUAL FREE CHLORINE CONTENT IS EQUAL TO THE LEVEL OF THE INCOMING W ATER, BUT NOT GREATER THAN 1.5 PARTS PER MILLION OR UNTIL APPROVED BY THE HEALTH DEPARTMENT.

D. PERFORM A BACTERIOLOGICAL ANALYSIS OF THE POTABLE W ATER SYSTEM. ONE TEST SAMPLE SHALL BE COLLECTED FROM THE END OF THE MAIN AND ONE FROM EACH BRANCH. PROVIDE CERTIFICATION STATING THE NAME OF THE LAB PERFORMING THE TESTING, THE JOB NAME, THE DATE OF THE SAMPLE AND RESULTS OF THE TESTING.

E. DISINFECTION PROCEDURES SHALL BE W ITNESSED OR APPROVED BY THE ARCHITECT, ENGINEER OR OTHER QUALIFIED REPRESENTATIVE, W HO SHALL PRESENT THE CONTRACTOR W ITH A LETTER OR CERTIFICATE OF COMPLETION. COPIES OF THE CERTIFICATE OF COMPLETION AND BACTERIOLOGICAL ANALYSIS REPORTS SHALL BE INCLUDED IN THE OPERATIONS AND MAINTENANCE MANUALS.

F. LEGIONELLA TESTING1. PROVIDE A LEGIONELLA SAMPLING PLAN AND ANALYSIS REPORT FROM A CERTIFIED LABORATORY.

THE SAMPLING PLAN SHALL BE AS DIRECTED BY THE CERTIFIED LABORATORY, AND SHALL BE BASED ON THE PROJECT SCOPE IDENTIFIED IN THE CONSTRUCTION DOCUMENTS. THE SAMPLING PLAN SHALL IDENTIFY THE NUMBER AND LOCATION OF SAMPLES TO BE COLLECTED. W ATER AND SW AB SAMPLING SHALL BE USED, CONSISTENT W ITH THE LABORATORY’S SUBMITTED PLAN. SAMPLING SHALL BE COLLECTED W ITHIN 48 HOURS AFTER THE FLUSHING AND CHLORINE PIPING DISINFECTION PROCEDURES.

2. LEGIONELLA TESTING SHALL BE BY CULTURE ANALYSIS. ANALYSIS SHALL INCLUDE TOTAL VIABLE LEGIONELLA COUNT AND DETERMINATION AS LEGIONELLA PNEUMOPHILIA SEROGROUP 1, LEGIONELLA PNEUMOPHILIA SEROGROUP 2 - 14, OR LEGIONELLA NON-PNEUMOPHILIA SPECIES. ALL LEGIONELLA REPORTS SHALL INCLUDE INTERPRETATIONS AND RECOMMENDATIONS BASED ON SAMPLE LOCATION. INDIVIDUAL SAMPLE SITES SHALL BE ASSIGNED A RISK FOR LEGIONNAIRES DISEASE. LIM ITS OF DETECTION SHALL BE <1 CFU/ML FOR W ATER SAMPLES AND 20 CFU/SW AB FOR SW AB SAMPLES.

3. THE LABORATORY SHALL BE CERTIFIED BY THE CENTERS FOR DISEASE CONTROL AND PREVENTION (CDC) TO BE PROFIC IENT IN PERFORMING LEGIONELLA ANALYSIS BY THE ELITE (ENVIRONMENTAL LEGIONELLA ISOLATION TECHNIQUES EVALUATION) PROGRAM. THE LABORATORY SHALL BE ACCREDITED AS COMPETENT TO PERFORM MICROBIAL AND LEGIONELLA TESTING AS PROVEN BY PROFICIENCY TESTING AND THROUGH COMPLIANCE TO ISO 17025:2005 POLICIES AND REQUIREMENTS.

4. SUBMIT SAMPLING PLAN TO CONSTRUCTION MANAGER AND ENGINEER FOR REVIEW PRIOR TO IMPLEMENTATION. DISINFECTION, FLUSHING, AND LEGIONELLA TESTING AND ANALYSIS SHALL BE REPEATED UNTIL LABORATORY RESULTS DETECT NO VIABLE LEGIONELLA.

5. IF THE BUILDING IS NOT TO BE IMMEDIATELY “SUBSTANTIALLY” OCCUPIED, A FLUSHING PROCEDURE RECOMMENDED BY THE TESTING LABORATORY AND/OR A W ATER TREATMENT CONSULTANT (CERTIFIED W ATER TECHNOLOGIST) SHALL BE INITIATED. THESE FLUSHING PROCEDURES SHALL CONTINUE UNTIL BUILDING IS SUBSTANTIALLY OCCUPIED. PERIODICALLY, AS DETERMINED BY THE TESTING LABORATORY AND THE W ATER TREATMENT CONSULTANT, LEGIONELLA CULTURE SAMPLES SHALL BE OBTAINED. IF POSITIVELY IS DETECTED AT A LEVEL DEEMED AT RISK, THEN THE PIPING SHALL BE RE-FLUSHED, AND SANITIZED PER SPECIFICATION.

6. THE LEGIONELLA SAMPLING REPORT SHALL INCLUDE DESCRIPTION OF THE SAMPLING PLAN USED, CERTIFICATION STATING THE NAME OF THE LAB PERFORMING THE TESTING, THE JOB NAME, THE DATES OF THE SAMPLES AND RESULTS OF THE TESTING.

10. W ORKMANSHIP SHALL BE FIRST CLASS. THE ARCHITECT'S OR ENGINEER’S JUDGMENT SHALL PREVAIL IF THE QUALITY IS SUSPECT.

11. PROTECT MATERIALS AND EQUIPMENT AFTER DELIVERY TO THE JOB SITE. RESPECT OTHER TRADES AS RELATED TO PROTECTING THEIR W ORK AND TO AVOID CONSTRUCTION INTERFERENCES. CALL ATTENTION TO PROBLEMS RELATING TO SPACE REQUIREMENTS SO EARLY RESOLUTION MAY BE OBTAINED. RESPECT OW NER'S PROPERTY AT ALL TIMES. TEMPORARILY REMOVE, STORE AND RE-INSTALL CEILINGS W HEN REQUIRED TO PERFORM W ORK.

E. INSTALLERS SHALL BE CERTIFIED TO THE REQUIREMENTS OF THE AMERICAN SOCIETY OF SANITARY ENGINEERS (ASSE) 6010 PROFESSIONAL QUALIFICATION STANDARDS FOR MEDICAL GAS SYSTEM INSTALLERS. VERIFIERS SHALL BE CERTIFIED TO THE REQUIREMENTSOF THE AMERICAN SOCIETY OF SANITARY ENGINEERS (ASSE) 6030 PROFESSIONAL QUALIFICATION STANDARDS FOR MEDICAL GAS SYSTEM VERIFIERS.

F. TUBING FOR PRESSURIZED MEDICAL GASES SHALL BE TYPE "L", OR TYPE “K” FOR SYSTEMS W ITH W ORKING PRESSURE EXCEEDING 185 PSI, HARD-DRAW N SEAMLESS COPPER (ASTM B-819). FITTINGS SHALL BE W ROUGHT COPPER, BRASS OR BRONZE DESIGNED EXPRESSLY FORBRAZED CONNECTIONS (ANSI B16.22 OR MSS SP-73). JOINTS SHALL BE BRAZED IN COMPLIANCE W ITH ANSI / AW S A5.8. JOINTS SHALL BE MADE USING A COPPER-PHOSPHORUS BRAZING FILLER ALLOY W ITH A MELTING TEMPERATURE IN EXCESS OF 1,000 DEGREES F. (BCUP-5) W ITHOUT FLUX.ALL TUBING AND FITTINGS SHALL BE LABELED "OXY", “MED”, “OXY/MED”, “OXY/ACR” OR “ACR/MED”. TUBING AND FITTINGS SHALL BE SPECIALLY CLEANED FOR OXYGEN SERVICE IN A FACILITY EQUIPPED TO CLEAN, RINSE AND PURGE THE MATERIAL IN ACCORDANCE W ITH THE REQUIREMENTS OF NFPA 99. TUBING AND FITTINGS SHALL BE DELIVERED TO THE PROJECT SITE CLEANED AND CAPPED/BAGGED.

G. TUBING FOR MEDICAL VACUUM SHALL BE TYPE “L” HARD-DRAW N COPPER (ASTM B-88 OR B-819) OR ASTM B-280 ACR COPPER. FITTINGS SHALL BE W ROUGHT COPPER, BRASS OR BRONZE DESIGNED EXPRESSLY FOR BRAZED CONNECTIONS (ANSI B16.22 OR MSS SP-73). JOINTS SHALL BE BRAZED IN COMPLIANCE W ITH ANSI / AW S A5.8. JOINTS SHALL BE MADE USING A COPPER-PHOSPHORUS BRAZING FILLER ALLOY W ITH A MELTING TEMPERATURE IN EXCESS OF 1,000 DEGREES F. (BCUP-5 SERIES) W ITHOUT FLUX.

H. FITTINGS AT TIE-IN LOCATIONS TO EXISTING SYSTEMS SHALL BE, AT THE CONTRACTOR’S OPTION, IN SIZES 0.5 INCH THRU 2 INCHES, AXIALLY SW AGED, ELASTIC STRAIN PRELOAD FITTINGS PROVIDING METAL TO METAL SEAL HAVING PRESSURE AND TEMPERATURE RATINGS NOT LESS THAN THAT OF A BRAZED JOINT. W HEN COMPLETE, FITTINGS SHALL BE PERMANENT AND NON-SEPARABLE. FITTINGS MATERIAL SHALL BE 360 BRASS AS PER ASTM B16, FACTORY CLEANED AND SEALED FOR OXYGENSERVICE PER CGA G-4.1. FITTINGS SHALL BE INSTALLED BY FACTORY TRAINED AND QUALIFIED INSTALLERS, IN STRICT CONFORMANCE W ITH THE FITTING MANUFACTURER’S INSTALLATION REQUIREMENTS,INCLUDING MAINTAINING THE MINIMUM INSTALLATION DISTANCE FROM BRAZED JOINTS. FITTINGS SHALL BE MANUFACTURED BY LOKRING TECHNOLOGY, LLC.

I. COPPER, TUBING, VALVES AND FITTINGS SHALL BE PRE-CLEANED AND PREPARED FOR OXYGEN SERVICE BY THE MANUFACTURER AND RECEIVED SEALED ON THE JOB. CERTIFICATES OF ORIGIN AND OF PROPERPREPARATION SHALL BE MAINTAINED ON THE JOB SITE ATTESTING THE ABOVE. KEEP OPEN ENDS OF TUBE CAPPED OR PLUGGED AT ALL TIMES. DISCARD PIPING, VALVES AND FITTINGS W HICH BECOME CONTAMINATED.CLEANING OF PIPING, VALVES AND FITTINGS ON-SITE IS PROHIBITED.

J. RIGIDLY SUPPORT VALVES AND OTHER EQUIPMENT TO PREVENT STRAIN ON TUBE OR JOINTS.

K. TAKE CARE NOT TO ANNEAL COPPER TUBE W HILE BRAZING. BRAZE ONLY W HILE PURGING THE INTERIOR OF TUBE W ITH OIL FREE DRY NITROGEN NF, M INIMUM U.S.P. OR GRADE B AS SPECIFIED IN CGA G-10.1. AT THECOMPLETION OF ANY SECTION, ALL OPEN PIPE ENDS SHALL BE CAPPED USING AN EXTERNAL CAP. AFTER INSTALLATION OF THE PIPING, BUT BEFORE INSTALLATION OF THE OUTLET VALVES, BLOW LINES CLEAR USINGNITROGEN NF.

L. DO NOT BEND TUBING. USE FITTINGS.

M. APPLY PIPE LABELING DURING INSTALLATION PROCESS AND NOT AFTER INSTALLATION IS COMPLETED. LABEL PIPING W ITH NAME OF GAS SERVICE, IDENTIFICATION COLOR AND DIRECTION OF FLOW . W HERE NON-STANDARD PRESSURES ARE PIPED, LABEL FOR PRESSURE. LABELS SHALL BE PLACED AT LEAST ONCE EVERY 20 FEET OF LINEAR RUN OR ONCE IN EACH STORY (W HICHEVER IS MORE FREQUENT). A LABEL SHALL ADDITIONALLY BE PLACED IMMEDIATELY ON EACH SIDE OF EACH W ALL OR FLOOR PENETRATION. PIPE LABEL COLORS IN ACCORDANCE W ITH NFPA 99.

N. PRIOR TO DECLARING THE SYSTEM READY FOR SYSTEM VERIFICATION, PERFORM AND DOCUMENT ALL INSTALLER TESTS AS REQUIRED BY NFPA 99. PRESSURE TESTS SHALL BE W ITNESSED OR MONITORED BYA RECORDER. FURNISH A W RITTEN RECORD OF EACH PIPING SYSTEM TEST INDICATING DATE, SYSTEM, PRESSURE, DURATION AND RESULTS OF TESTS. SIGNED COPIES OF TEST REPORTS SHALL BE DISTRIBUTEDTO THE ARCHITECT OR ENGINEER, THE AUTHORITY HAVING JURISDICTION, THE VERIFIER AND INCLUDED IN THE O&M MANUALS.

O. INITIAL PRESSURE TEST, CROSS CONNECTION TEST, PIPING PURGE TEST AND STANDING PRESSURE TEST SHALL BE DONE PRIOR TO CLOSING OF W ALLS. TESTING OF EACH SYSTEM SHALL BE DONE ONE AT A TIME, NOTSIMULTANEOUSLY.

P. ALL PIPING SHALL BE INITIALLY TESTED AT 1.50 TIMES THE MAXIMUM W ORKING PRESSURE BUT NOT LESS THAN 150 PSI, EXCEPT NITROGEN W HICH SHALL BE TESTED AT 250 PSI. EACH JOINT SHALL BE INSPECTED AND REPAIRED IF NECESSARY. THE COMPLETELY ASSEMBLED SYSTEM SHALL BE SUBJECTED TO A 24-HOUR STANDING PRESSURE TEST AT 20 PERCENT ABOVE THE NORMAL OPERATING LINE PRESSURE. VACUUMSYSTEMS SHALL BE SUBJECTED TO A 24-HOUR STANDING PRESSURE TEST AT 50 PSIG W ITH NO MORE THAN A 5 PSIG LOSS. THE TEST GAS SHALL BE OIL-FREE, DRY AIR OR NITROGEN.

Q. AFTER INITIAL LEAKAGE TESTING IS COMPLETED, ALLOW PIPING TO REMAIN PRESSURIZED W ITH TESTING GAS UNTIL TESTING AGENCY PERFORMS FINAL TESTS.

R. VERIFICATION OF MEDICAL GAS SYSTEMS

i.) THE MEDICAL AIR SYSTEM SHALL BE TESTED BY AN APPROVED TESTING AGENCY AFTER INSTALLATION OF THE SYSTEM HAS BEEN COMPLETED. THE REPRESENTATIVE SHALL DETERMINE THAT ALL TESTING, VERIFICATION AND REPORTING IS IN COMPLIANCE W ITH ASSE STANDARD #6030.

28. ALL NEW SYSTEMS SHALL BE SEISMICALLY RESTRAINED IN ACCORDANCE W ITH THE OHIO BUILDING CODE.

PARAMETERS FOR SEISMIC DESIGN ARE:

SEISMIC OCCUPANCY CATEGORY IV

SITE CLASS D

DESIGN SPECTRAL RESPONSE ACCELERATION AT SHORT PERIOD (0.2 SECOND), SDS OF 0.165G.

SEISMIC DESIGN CATEGORY C

ALL NEW SYSTEMS AND ASSOCIATED EQUIPMENT, PIPING AND APPURTENANCES SHALL BE DESIGNATED AS HAVING A COMPONENT IMPORTANCE FACTOR, IP, OF 1.5.

SEISMIC RESTRAINTS SHALL BE ENGINEERED, SEALED, AND FURNISHED BY MASON INDUSTRIES, KINETICS OR AMBER/ BOOTH.

12. CUT AND PATCH TO INSTALL W ORK OR PAY OTHERS TO PERFORM SUCH W ORK. W ORKMANSHIP SHALL BE FIRST CLASS. THE ARCHITECT’S OR ENGINEER’S JUDGMENT SHALL PREVAIL IF THE QUALITY IS SUSPECT.

13. IN ALTERATION AND REMODELING W ORK, PERFORM ALL REMOVAL AND RELOCATION W ORK KINDRED TO THE PLUMBING W ORK. LEAVE ALL EXISTING SYSTEMS CONTINUOUS AND FUNCTIONAL. REMOVE EXTRANEOUS PIPING AND EQUIPMENT. NO REMOVED MATERIAL SHALL BE REUSED UNLESS EXPRESSLY SHOW N. W HERE NECESSARY TO DISRUPT SERVICES FOR SHORT PERIODS OF TIME, COORDINATE AND SCHEDULE OUTAGES W ITH THE OW NER.

14. PROVIDE CEILING AND W ALL ACCESS PANELS W HERE INDICATED ON THE DRAW INGS, OR W HERE REQUIRED FOR ACCESS TO CONCEALED VALVES, TRAPS, DEVICES OR SERVICEABLE EQUIPMENT. ACCESS PANELS SHALL BE MINIMUM 18” X 18”, OR LARGER IF REQUIRED, AND SHALL BE COMPATIBLE W ITH THE MATERIALS IN W HICH THEY ARE INSTALLED. ACCESS PANELS IN FIRE RATED BUILDING ELEMENTS SHALL BE LABELED IN COMPLIANCE W ITH THE RATING OF THE BUILD ING ELEMENT.

15. EACH CONTRACTOR SHALL MAINTAIN A SEPARATE SET OF AS-BUILT PRINTS OF THE CONTRACT DOCUMENTS AND SHALL SHOW ANY SIGNIFICANT CHANGES OR VARIATIONS W HICH ARE MADE DURING CONSTRUCTION. UPON COMPLETION OF THE W ORK, THESE DRAW INGS SHALL BE TURNED OVER TO THE ARCHITECT.

16. PAINT FERROUS METAL W HICH IS NOT FACTORY OR SHOP PAINTED OR GALVANIZED AND W HICH REMAINS EXPOSED TO VIEW IN FINISHED AREAS OF THE BUILDING. FERROUS METAL INSTALLED OUTSIDE THE BUILDING W HICH IS NOT FACTORY OR SHOP PAINTED OR GALVANIZED SHALL BE GIVEN A PRIME COAT OF PAINT.

17. MARK ALL PIPING SYSTEMS AND TAG ALL VALVES. ANY EXISTING PIPING ENCOUNTERED SHALL ALSO BE MARKED. PIPE MARKERS SHALL BE 1” HIGH LETTERS W ITH COLOR BAND AND ARROW . MARKERS SHALL BE AT LEAST ONE IN EACH ROOM, BUT NO MORE THAN 20 FT. INTERVALS. COLOR BAND SHALL MATCH EXISTING OR AS DICTATED BY OW NER. TURN OVER VALVE TAG SCHEDULE TO ARCHITECT.

18. FIRESTOPPING ASSEMBLIES SHALL BE PROVIDED AT PENETRATIONS OF PIPING THRU FIRE RATED FLOORS, FIRE RATED FLOOR-CEILING AND ROOF CEILING ASSEMBLIES, FIRE & SMOKE RATED W ALLS AND PARTITIONS AND FIRE & SMOKE RATED SHAFT W ALLS AND PARTITIONS. IN ADDITION, FIRESTOPPING ASSEMBLIES SHALL BE PROVIDED AT PENETRATIONS THRU 0-HOUR RATED FLOORS. REFER TO THE ARCHITECTURAL DRAW INGS FOR FIRE AND SMOKE RATED BUILDING ELEMENTS AND PLUMBING/FIRE SUPPRESSION DRAW INGS FOR PIPE LAYOUTS. FIRESTOPPING SHALL BE AS MANUFACTURED BY SPECIFIED TECHNOLOGIES, INC.

19. ALL PIPING SHALL BE INSTALLED PER ACCEPTED INDUSTRY STANDARDS AND/OR PER MANUFACTURER’S RECOMMENDATIONS. ALL INTERIOR ABOVE GRADE PIPING SHALL BE SUPPORTED BY ATTACHMENT TO BUILDING STRUCTURAL ELEMENTS. DO NOT SUPPORT PIPING FROM NON-STRUCTURAL BUILDING ELEMENTS, DUCTW ORK, OTHER PIPING, ETC. HANGER ROD SIZES AND HANGER/SUPPORT SPACING SHALL BE PER THE FOLLOW ING SCHEDULES. HANGERS FOR PLUMBING PIPING SHALL BE LIGHT DUTY CLEVIS TYPE, COPPER CLAD OR PLASTIC COATED FOR UNINSULATED COPPER PIPING, W ITH LOCK NUT AT EACH HANGER. FIRE SUPPRESSION HANGER AND SUPPORT REQUIREMENTS SHALL BE PER FM GLOBAL AND NFPA STANDARDS. PROVIDE A LOCK NUT AT HANGER ROD ATTACHMENT TO STRUCTURE.

PIPE SIZE MINIMUM HANGER ROD DIAMETER2” AND SMALLER 0.375”2.5" TO 3" 0.5"4" TO 5" 0.625"

PIPE MATERIAL/SIZE MAXIMUM HANGER/SUPPORT SPACINGVERTICAL:COPPER BASE AND 10 FT.CAST IRON BASE AND EACH FLOOR LEVELSTEEL BASE AND 15 FT. HORIZONTAL:COPPER / <=1.25” 6 FT.CAST IRON 10 FT. AND EACH FITTING/JOINTSTEEL / <=1.5 7 FT.STEEL / 2" - 6" 10 FT

20. INSULATE ALL NEW ABOVE GROUND DOMESTIC W ITH FIBERGLASS PIPE INSULATION IN COMPLIANCE W ITH ASHRAE 90.1. FIBERGLASS INSULATION SHALL BE FACTORY MOLDED TUBULAR FIBERGLASS W ITH ALL SERVICE JACKET, INTEGRAL VAPOR BARRIER AND FACTORY ADHESIVE OVERLAPPING JOINTS. PROVIDE FACTORY MOLDED PVC COVERS AND INSULATION FOR FITTINGS, VALVES AND DEVICES. ON COLD SERVICE PIPING, SEAL ALL JOINTS AND TERMINATIONS TO MAINTAIN THE VAPOR BARRIER. COMPOSITE INSULATING SYSTEMS SHALL NOT EXCEED A MAXIMUM FLAME SPREAD OF 25 AND SMOKE DEVELOPMENT OF 50 AS ESTABLISHED BY ASTM E84 TEST METHODS. FIBERGLASS INSULATION MANUFACTURERS - OW ENS-CORNING, JOHNS MANVILLE, MASON OR KNAUFF.

1.25” ANDPIPE SYSTEM SMALLER 1.5” TO 3”DOM. COLD & NON-POTABLE W ATER 0.5” 1.0”DOM. HOT W ATER 1.0” 1.5”DOM. HOT RETURN 1.0” 1.5”

21. FIRE SUPPRESSION PIPING SHALL BE SCHEDULE 40 BLACK STEEL, ASTM A-53, TYPE E OR F OR ASTM A135. FITTING AND JOINTS SHALL BE MALLEABLE OR CAST IRON SCREW ED TYPE FOR PIPING 2” AND SMALLER, AND MECHANICALLY ROLLED GROOVE TYPE FOR SIZES 2” AND LARGER. FITTINGS FOR MECHANICALLY ROLLED GROOVE SYSTEMS SHALL BE MALLEABLE OR DUCTILE IRON BODY W ITH N ITRILE OR EPDM GASKETS, EQUAL TO VICTAULIC “FIRELOCK” STYLE 005 AND 009.

22. ALL MATERIALS AND DEVICES, AS APPROPRIATE, SHALL BE UL LISTED AND/OR FM GLOBAL APPROVED, AND ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. THE FIRE SUPPRESSION SYSTEM(S) SHALL CONFORM TO NFPA STANDARDS, THE GOVERNING BUILD ING CODE, AND OTHER REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION AND THE OW NER’S INSURER.

23. INTERIOR DOMESTIC W ATER PIPING SHALL BE TYPE “L” SEAMLESS HARD DRAW N COPPER TUBING ASTM B88 W ITH W ROUGHT COPPER OR CAST BRONZE FITTINGS ASME B16.22 AND SOLDERED JOINTS. SOLDER SHALL BE LEAD-FREE TIN ALLOY, 95-5 TIN-ANTIMONY OR SILVER BEARING TIN. PIPE NIPPLES EXTENDING OUT OF THE W ALL TO SERVE FIXTURES SHALL BE CHROME PLATED BRASS W ITH SCREW ED ENDS. SHUTOFF VALVES SHALL BE TW O-PIECE, BRONZE BODY, BALL TYPE, 150 W .S.P. ASTM B584, EQUAL TO NIBCO T-585-66-LF. PROVIDE FULL OPEN VALVES AT LOCATIONS REQUIRED BY THE GOVERNING PLUMBING CODE.

24. INTERIOR ABOVE GRADE SOIL, W ASTE AND VENT PIPING SHALL BE CENTRIFUGALLY CAST COATED CAST IRON W ITH HUBLESS ENDS, ASTM A-888 AND CISPI 301. FITTINGS SHALL BE DRAINAGE TYPE. JOINTS SHALL CONSIST OF A NEOPRENE GASKET, ASTM C564, STAINLESS STEEL SHIELD AND STAINLESS STEEL BAND. FLOOR DRAIN TRAPS SHALL BE THE SAME MATERIAL AS THE CONNECTING PIPING. PROVIDE CLEANOUTS W HERE SHOW N ON THE DRAW INGS AND W HERE REQUIRED BY THE GOVERNING PLUMBING CODE.

25. PROVIDE PLUMBING FIXTURES, AS INDICATED ON THE DRAW INGS, INSTALLED IN PLACE COMPLETE W ITH SUPPORTS, CARRIERS AND SUPPLY AND W ASTE TRIM. SUPPLIES TO EACH FIXTURE SHALL BE INDIVIDUALLY VALVED. VALVES, SUPPLIES AND ESCUTCHEONS SHALL BE FURNISHED W ITH FIXTURE SUPPLY TRIM. ALL W ASTE AND SUPPLY TRIM SHALL BE CHROME PLATED BRASS. FIXTURES SHALL BE W HITE UNLESS OTHERW ISE SPECIFIED. SEAL JOINTS AROUND EACH FIXTURE AT THE W ALL, FLOOR AND ANY ADJACENT CONSTRUCTION. JOINT SEALANT SHALL BE ONE PART, M ILDEW RESISTANT SILICONE, ASTM C-920, TYPE S, GRADE NS, CLASS 25 W ITH FUNGICIDE, EQUAL TO PECORA 898. AFTER INSTALLATION OF THE FIXTURES IS COMPLETED, ALL CONNECTING PIPES SHALL BE FLUSHED OUT THROUGH THE FIXTURES TO ELIMINATE SCALE, AND ALL VALVES SHALL BE PROPERLY ADJUSTED AND FIXTURES LEFT COMPLETE AND READY FOR USE. ALL FIXTURES SHALL BE CLEANED, IMMEDIATELY PRIOR TO ACCEPTANCE BY THE OW NER.

26. ALL PLUMBING FIXTURES, EQUIPMENT AND TRIM SHALL MEET THE DIMENSIONAL AND PERFORMANCE REQUIREMENTS OF ANSI, ARI, ASME, AND ASSE AND/OR CSA STANDARDS LISTED IN THE CURRENT JURISDICTIONAL PLUMBING CODE. ALL FAUCETS AND FITTINGS SUPPLYING DRINKING W ATER FOR HUMAN CONSUMPTION SHALL CONFORM TO THE REQUIREMENTS OF NSF 61, SECTION 9.

27. MEDICAL GAS AND VACUUM SYSTEMS SHALL BE PROVIDED AS SHOW N ON THE DRAW INGS, AND AS SPECIFIED.

A. MATERIALS AND INSTALLATION SHALL CONFORM TO REQUIREMENTS OF NFPA 99, COMPRESSED GAS ASSOCIATION P-2 CHARACTERISTICSAND SAFE HANDLING OF MEDICAL GASES AND OHIO BUILDING CODE.

B. A SEPARATE PIPING PERMIT SHALL BE OBTAINED. SPECIAL NOTE SHALL BE TAKEN TO COMPLY W ITH “MEDICAL GAS INSPECTION PROCEDURE FOR PIPING SYSTEMS” ISSUED BY THE STATE OF OHIO.

C. BRAZERS SHALL BE QUALIFIED IN ACCORDANCE W ITH THE REQUIREMENTS OF ASTM BOILER AND PRESSURE VESSEL CODE, SECTION IX OR AW S B2.2 STANDARD FOR BRAZING AND PERFORMANCE QUALIFICATION, AS MODIFIED BY NFPA 99.

D. RETAIN A QUALIFIED THIRD PARTY VERIFIER ACCEPTABLE TO THE ENGINEER AND OW NER TO PERFORM AND ATTEST TO FINAL VERIFICATION OF THE SYSTEMS. MAKE CORRECTIONS AS REQUIRED, INCLUDING ADDITIONAL TESTING IF NECESSARY TO ATTAIN FULL AND UNQUALIFIED CERTIFICATION.

A. ALL PIPING IS ABOVE THE CEILING (AT THE UNDERSIDE OF STRUCTURE IN EXPOSED STRUCTURE AREAS), UNLESS OTHERW ISE NOTED.

B. REFER TO SCHEDULES, DETAILS AND DIAGRAMS FOR PIPING, PIPE SIZES ANDPIPELINE DEVICES NOT INDICATED ON THE FLOOR PLAN.

C. ABOVE CEILING UTILITY SPACE IS LIM ITED. COORDINATION W ITH ALL TRADESIS CRITICAL, PR IOR TO INSTALLATION OF ANY W ORK.

D. LOCATIONS AND SIZES OF EXISTING PIPING HAVE BEEN DETERMINED FROM AREVIEW OF EXISTING DRAW INGS AND/OR SITE INSPECTION, W HERE POSSIBLE.FIELD VERIFICATION OF EXACT LOCATIONS, ELEVATIONS, INVERTS, SIZES,DIRECTION OF FLOW , ETC. SHALL BE REQUIRED PRIOR TO BEGINNINGNEW W ORK.

E. ALL PIPING SHALL BE REMOVED BACK TO ACTIVE MAINS AND CAPPED, ORREMOVED BACK TO POINTS OF CONNECTION IN NEW W ORK. INACCESSIBLEPIPING, W HERE SO NOTED, TO BE ABANDONED SHALL BE DISCONNECTEDFROM ACTIVE SYSTEMS AND CAPPED OR PLUGGED IN CONCEALED LOCATIONS.

F. ALL ABANDONED PIPING SHALL BE CAPPED AT INLET AND OUTLET. DOMESTICW ATER PIPING SHALL BE CAPPED W ITHIN TW O (2) P IPE DIAMETERS OF ACTIVEBRANCH/ MAIN. NO DEAD LEGS W ILL BE PERMITTED.

G. NEW CONNECTIONS TO EXISTING PIPING SHALL BE W ITH THE SAME SIZE ASTHE EXISTING PIPING, UNLESS OTHERW ISE NOTED.

H. ALL REMOVED MATERIAL AND EQUIPMENT, SO DESIGNATED BY THE OW NER,SHALL BE TURNED OVER AND PLACED W HERE DIRECTED. ALL MATERIALAND EQUIPMENT, W HICH THE OW NER DOES NOT W ISH TO RETAIN, SHALLBECOME THE PROPERTY OF THE CONTRACTOR RESPONSIBLE FOR THEREMOVAL.

I. REFER TO THE ARCHITECTURAL PLANS FOR PROJECT PHASING REQUIREMENTS.

J. ANNULAR SPACE OF PIPE, CONDUIT AND OTHER SIMILAR PENETRATIONS OFFIRE RATED ASSEMBLIES SHALL BE FIRESTOPPED. IN ADDITION,PENETRATIONS THRU RATED FLOORS SHALL ALSO BE FIRESTOPPED TORETARD PASSAGE OF FIRE AND SMOKE. REFER TO SPECIFICATIONS. REFER TO ARCHITECTURAL DRAW ING(S) FOR CONSTRUCTION, LAYOUT AND FIRE RATINGS OF FLOORS, W ALLS, PARTITIONS AND OTHER BUILDING ELEMENTS. REFER TO ARCHITECTURAL DRAW INGS FOR PENETRATION DETAILS.

GENERAL NOTES

A. REFER TO ARCHITECTURAL DRAW INGS FOR REFLECTED CEILING PLANS ANDGENERAL TRADES CONSTRUCTION INFORMATION. COORDINATE SPRINKLERLOCATIONS W ITH CEILING DEVICES (LIGHTING, GRILLES, ETC.) OBTAINARCHITECTS APPROVAL OF SPRINKLER LAYOUT PRIOR TO INSTALLATION.FINAL FINISHED APPEARANCE OF W ORK MUST BE APPROVED BY THEARCHITECT.

B. CONTRACTOR SHALL MAKE REQUIRED FLOW TESTS, LAY OUT SYSTEMS, OBTAINAPPROVALS FROM THE AUTHORITY HAVING JURISDICTION AND THE OW NER’SINSURER PRIOR TO BEGINNING ANY FABRICATION OR INSTALLATION W ORK.

C. FIRE SUPPRESSION SPRINKLER SYSTEMS. REFER TO DRAW INGS ANDSPECIFICATIONS FOR COMPLETE SCOPE OF W ORK.

1. RENOVATION AREA(S) TO BE TOTALLY SPRINKLERED. EXISTING SPRINKLERSYSTEMS TO BE MODIFIED TO CONFORM TO THE NEW LAYOUT. NEWSPRINKLERS ARE TO BE INTEGRATED INTO THE EXISTING SPRINKLERSYSTEM. ALL EXISTING SPRINKLERS, REMOVED OR DISTURBED INRENOVATION AREAS, SHALL BE DISPOSED OF AND REPLACED W ITH NEWSPRINKLERS, AS INDICATED ON THE DRAW INGS.

D. BASIS FOR DESIGN OF FIRE SUPPRESSION SYSTEM(S) TO BE:

1. LIGHT HAZARD 1500 SQUARE FEET, 0.10 GPM/ SQ.FT., 225 SQUARE FEETMAXIMUM PER SPRINKLER. 100 GPM HOSE STREAM ALLOW ANCE.

2. ORDINARY HAZARD, (GROUP 1) 1500 SQUARE FEET, 0.15 GPM/ SQ. FT.,130 SQUARE FEET MAXIMUM PER SPRINKLER. 250 GPM HOSE STREAMALLOW ANCE.

FIRE SUPPRESSION DESIGN NOTESE. AREA OF OPERATION REDUCTIONS AND INCREASES SHALL BE CALCULATED

PER NFPA STANDARDS. VERIFY DENSITIES W ITH GOVERNING AUTHORITIESAND OW NER’S INSURER BEFORE PROCEEDING W ITH DESIGN OF SYSTEM(S).IF GOVERNING AUTHORITIES OR OW NER’S INSURER REQUIREMENTS ARE MORESTRINGENT THOSE REQUIREMENTS SHALL PREVAIL. ALL AREAS ARE TO BELIGHT HAZARD CLASSIFICATION, UNLESS OTHERW ISE INDICATED ON THE PLANSOR REQUIRED BY THE GOVERNING AUTHORITY.

F. PROVIDE THE FOLLOW ING SPRINKLER TYPES, UNLESS OTHERW ISE NOTED ONTHE DRAW INGS. PENDENT TYPE SPRINKLERS SHALL BE LOCATED IN THECENTER OF SQUARE PADS AND AT THE CENTER OR AT QUARTERPOINTS OF THELONG AXIS OF RECTANGULAR PADS.

1. SPRINKLERS IN AREAS W ITH CEILINGS SHALL BE CONCEALED TW O PIECEADJUSTABLE PENDENT QUICK RESPONSE TYPE W ITH W HITE FINISH COVERPLATE. PROVIDE GASKETED COVERPLATE INSIDE IV ROOM, ANTI ROOM, CHEMO ROOM & HD NON-STERILE ROOM

2. SPRINKLERS IN EXPOSED AREAS SHALL BE QUICK RESPONSE BRASSUPRIGHT TYPE.

G. EXERCISE SPECIAL CARE TO COORDINATE PIPING AND EQUIPMENT LOCATIONSW ITH ALL OTHER TRADES.

H. ALL NEW W ORK SHALL BE COMPLIANT W ITH RULES AND REGULATIONS OF NFPA-13OR THE GOVERNING AUTHORITY, IF MORE STRINGENT.

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

5/2

01

9 7

:03

:50

AM

C:\

BIM

\Mod

el\20

19

-05

07

8-M

EP

-Ce

ntr

al_

WS

McC

am

ey.r

vt

2019-05078

ABN

W SM

July 24, 2019

P002

SCHEDULES ANDSPECIFICATIONS

1 2019.07.24 ADDENDUM 1

NOTES:1. INSTALL FLUSH VALVE HANDLE ON WIDE SIDE OF STALL PER ADA GUIDELINES.2. PROVIDE STEEL FOOT SUPPORT CARRIER.3. PROVIDE ADA INSULATION KIT ON EXPOSED TRAPS ANDSUPPLIES...

4. COORDINATE INSTALLATION OF SINK AND ALL ACCESSORIES WITH PHARMACY CONTRACTOR.5. SCRUB SINK INCLUDING FAUCET AND WASTE TRIM FURNISHED BY PHARMACY CONTRACTOR. PC TO PROVIDE SUPPLYSTOPS,...

6. INSTALL EYEWASH/DRENCH HOSE ON SINK DECK BESIDE FAUCET. PC TO PROVIDE ASSE 1071 THERMOSTATIC MIXING VALVE INSIDE SINK ENCLOSURE FOR EYEWASH DRENCHHOSE. EXTEND 0.5" TEPID WATER TO EYEWASH/DRENCH HOSE....

7. EXTEND DCW AND DHW PIPING FROM SINK SUPPLIES TOSERVE EYEWASH. PROVIDE BALL AND CHECK VALVES ON SUPPLIESTO THERMOSTATIC MIXING VALVE.

ADA HANDICAP ACCESSIBLE FS FLOOR SET FT FLUSH TANK FV FLUSH VALVE GN GOOSENECK HS HAND SHOWER QD QUICK DISCONNECT

SB SINGLE BOWLSST STAINLESS STEELVB VACUUM BREAKERVR VANDAL RESISTANTWB WRIST BLADEWH WALL HUNG

SCHEDULE ABBREVIATIONS: GENERAL NOTE:1. SUPPLY PIPE SIZES IN THIS SCHEDULE ARE FIXTURE OR SUPPLY STOP CONNECTION SIZES. DOMESTIC COLD AND HOT WATER SUPPLY PIPE SIZES SERVING FIXTURES SHALL BE, AT AMINIMUM, THE SIZES LISTED UNLESS NOTED OTHERWISE OR LABELED ON THE FLOOR PLANS. DOMESTIC COLD WATER SUPPLY PIPE SIZES SERVING FLUSH VALVES SHALL BE AT MINIMUM ONE PIPE SIZE LARGER THAN THE INDICATED CONNECTION SIZE, OR SIZED AS SHOWN ON THE FLOOR PLANS. PIPING AT THE FLUSH VALVE CONNECTION OF A SIZE EQUAL TO THE CONNECTIONSIZE SHALL BE LIMITED TO A MAXIMUM 2 FEET IN DEVELOPED LENGTH AND INCLUDE A MAXIMUM OF ONE 90 DEGREE ELBOW FITTING. FULL SIZE MANIFOLDS, WHERE INDICATED ON THE FLOOR...

A. AMERICAN STANDARD (KOHLER, CRANE, ZURN, TOTO) _

B. SLOAN (DELANY, ZURN) _

C. BEMIS (BENEKE, CHURCH, OLSONITE) _

D. SMITH (WADE, ZURN, JOSAM, WATTS) _

E. CHICAGO (TOTO, T&S BRASS, ZURN) _

F. GUY GRAY (OATEY, PLASTIC ODDITIES) _

G. McGUIRE (EBC, DEARBORN BRASS) _

H. ELKAY (FURNISHED BY OTHERS) _

J. ELKAY (JUST WITH LUG AND SCREW) _

K. GUARDIAN (FURNISHED BY OTHERS) _

L. LEONARD (POWERS, SYMMONS) _

M. AQUARIUS (AQUA-BATH, KOHLER, CRANE) _

N. IN-SINK ERATOR (OR APPROVED EQUAL) _

_

_

_

CATALOG NUMBERS INDICATED ARE THOSE OF THE FIRST NAMED MANUFACTURER IN EACH CATEGORY LISTED BELOW - ADDITIONAL MANUFACTURERS ARE LISTED IN PARENTHESIS

PLUMBING FIXTURES

MARK DESCRIPTION MO

UN

TIN

G H

EIG

HT

FLOW CONTROL SUPPLY WASTE & VENT FIXTURE SUPPLY TRIM SUPPLY / STOP WASTE TRIM TRAP / FIX. DR. MISC.

SE

E N

OT

E

GP

M

GP

F

MA

NU

AL

ME

TE

RIN

G

SENSOR

CO

LD

WA

TE

R

HO

T W

AT

ER

TE

MP

ER

ED

NA

T.

GA

S

FIX

. O

UT

LE

T

TR

AP

FIX

. D

RA

IN

WA

ST

E-M

IN.

VE

NT

-MIN

.

MF

R.

CAT. NO. MF

R.

CAT. NO. MF

R.

CAT. NO. MF

R.

CAT. NO. MF

R.

CAT. NO. MF

R.

CAT. NO. EL

EC

TR

IC

BA

TT

ER

Y

A1 WATER CLOSET/ FS/ FV/ ADA 16.5"TORIM

1.6 ● 1" 3" INT 3" 3" 2" A 3043.001 B 111-1.6-YO-SG

B UNIT A UNIT A INTEGRAL C 1655SSCT 1

B1 LAVATORY/ WH/ GN/ WB/ ADA 34" TORIM

1.5 ● 0.5" 0.5" 1.25"

1.5" 1.5" 1.5" 1.5" A 0356.015 E 786-GN2FCXKABCP

G LFBV2165 G 155WC G 8912 2, 3

D1 SCRUB SINK/ SST/ FURNISHED BY PHARMACYCONTRACTOR

30" TORIM

1.5 ● 0.5" 0.5" 1.5" 1.5" 1.5" 1.5" 1.5" H EWSF13026 H LKB721C G LFBV2165 H LK18B G 8912 2, 4, 5

E1 EYEWASH/DRENCH HOSE/ FURNISHED BYPHARMACY CONTRACTOR

- ● 0.5" K G5022 K UNIT - BALLVALVES

K G3600 6, 7

F1 SINK/ SST/ DROP-IN/ GN/ WB/ ADA/ 6" DEEP - 1.5 ● 0.5" 0.5" 1.5" 1.5" 1.5" 1.5" 1.5" J LRAD191860 E 786-GN8FCXKABCP

G LFBV2165 J LK18B G 8912

Page 11:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

SMOKE ZONE

5" SS FROM ABOVE

4" SS FROM ABOVE

SS

SS

SK

SK

SS

SK

VR SK

VR

4" -

SA

N

4" - SAN

4" -

SA

N

2" -

SA

N

4" -

SA

N

5" -

SA

N2"

-S

AN

1

1 1

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

5/2

01

9 7

:03

:54

AM

C:\

BIM

\Mod

el\20

19

-05

07

8-M

EP

-Ce

ntr

al_

WS

McC

am

ey.r

vt

2019-05078

ABN

W SM

July 24, 2019

P100

PARTIAL BASEMENTPLAN - DEMOLITION

1 2019.07.24 ADDENDUM 1

SCALE: 1/4" = 1'-0"

PARTIAL BASEMENT PLAN - DEMOLITION1

NOTES

1 DISCONNECT AND REMOVE EXISTING SANITARY PIPING FROMDEMOLISHED FIXTURES ABOVE BACK TO ACTIVE MAIN AND CAP OR TOPOINT OF RECONNECTION.

Page 12:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

1314

LOCK.

38

PTD

SD

1SK

5

5

4

1" - MA

1" - MV

1" -

MA

1" -

MV

2

2

5

3" - F

3" -

F

3" -

F

1.5" - O23" - DCW

2" - DHW0.75" - DHW R

1" - MV1" - MA

3" - DCW2" - DHW

0.75" - DHW R

1" - MV1" - MA

1.5" - O2

4" - DCW3" - DHW1" - MV1" - MA

1.5" - O21.25" - DHW R

4" - DCW4" - DHW

1.25" - DHW R

1" - MA

1.25" - MV

1" - DHW R3" - DHW

3" - DCW1.25" - O2

1" - MV1" - MA

6

4

6

1" -

DH

W

1" -

DC

W

0.75

" -

G

0.75

" -

MA

0.75

" -

DH

W

0.75

" -

DC

W

3

3

4

1LAV1W C

1.25" - G

1.25" - G

7

4" SS DN 2" V UP

4" SS DN

W C

LAV

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

5/2

01

9 7

:04

:00

AM

C:\

BIM

\Mod

el\20

19

-05

07

8-M

EP

-Ce

ntr

al_

WS

McC

am

ey.r

vt

2019-05078

ABN

W SM

July 24, 2019

P101

PARTIAL FIRST FLOORPLAN - DEMOLITION

1 2019.07.24 ADDENDUM 1

SCALE: 1/4" = 1'-0"

PARTIAL FIRST FLOOR PLAN - DEMOLITION1

NOTES

4 DISCONNECT AND REMOVE EXISTING MEDICAL AIR, VACUUM AND/ORGAS PIPING INCLUDING ALL HANGERS AND SUPPORTS BACK TOACTIVE BRANCH/MAIN AND CAP.

5 REMOVE EXISTING DOMESTIC WATER, SANITARY AND VENT PIPINGBACK TO ACTIVE BRANCH/MAIN AND CAP.

6 DISCONNECT, REMOVE AND REROUTE EXISTING FIRE MAIN PIPINGINCLUDING ALL HANGERS AND SUPPORTS. COORDINATE NEWROUTING CLOSELY WITH ALL TRADES TO MAXIMIZE CEILING HEIGHT.

7 DISCONNECT, REMOVE AND REROUTE EXISTING SANITARY PIPINGINCLUDING ALL HANGERS AND SUPPORTS. COORDINATE NEWROUTING CLOSELY WITH HC.

NOTES

1 DISCONNECT AND REMOVE EXISTING PLUMBING FIXTURE INCLUDINGALL ACCESSORIES (TYPE AS INDICATED). REMOVE EXISTINGDOMESTIC WATER PIPING BACK TO WITHIN TWO (2) PIPE DIAMETERSOF ACTIVE BRANCH/MAIN AND CAP. REMOVE SANITARY PIPING TOBEYOND FINISHED WALL AND CAP. NO PIPE STUBS SHALL REMAINVISIBLE IN FINISHED SPACE.

2 REMOVE ABANDONED SANITARY AND/OR VENT PIPING BACK TOACTIVE BRANCH/MAIN AND CAP OR TO POINT OF RECONNECTION.REFER TO NEW WORK PLAN.

3 REMOVE ALL ABANDONED DOMESTIC WATER PIPING BACK TO WITHINTWO (2) PIPE DIAMETERS OF ACTIVE BRANCH/MAIN AND CAP OR TOPOINT OF RECONNECTION. REFER TO NEW WORK PLAN.

Page 13:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

SMOKE ZONE

F1

D1

B1

A1

4" -

SA

N

4" - SAN

4" -

SA

N

2" -

SA

N

4" -

SA

N

5" -

SA

N

5" SS FROM ABOVE

4" SS FROM ABOVE

NEW CAP

NEW CAP

CO

VRVR

3" -

SA

N

1.5" - SAN

3" -

SA

N

FD1

D1

FD1

NEW CAP

2" -V

3" -SAN

4" -SAN

4" - SAN2" - SAN

4" - SAN

1.5"

1.5"

2"2"

3"

1.5"

4" -SAN

1.5"2" -V

F1

3" -SAN

1.5"

2"

2" -V

CO

3"

A1B1

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

5/2

01

9 7

:04

:06

AM

C:\

BIM

\Mod

el\20

19

-05

07

8-M

EP

-Ce

ntr

al_

WS

McC

am

ey.r

vt

2019-05078

ABN

W SM

July 24, 2019

P200

PARTIAL BASEMENTPLAN - NEW WORK

1 2019.07.24 ADDENDUM 1

SCALE: 1/4" = 1'-0"

PARTIAL BASEMENT PLAN - NEW WORK1

SCALE: NONE

SANITARY WASTE AND VENT DIAGRAM - ANTI ROOM & MECH ROOM2

SCALE: NONE

SANITARY WASTE AND VENT DIAGRAM - PHARMACY3

SCALE: NONE

SANITARY WASTE AND VENT DIAGRAM - TOILET ROOM4

Page 14:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

PTD

SD

TP

1.25

" -

DH

W

1.25

" -

DC

W

1.5" - O23" - DCW

2" - DHW0.75" - DHW R

1" - MV1" - MA

3" - DCW2" - DHW

0.75" - DHW R

1" - MV1" - MA

1.5" - O2

4" - DCW3" - DHW1" - MV1" - MA

1.5" - O21.25" - DHW R

4" - DCW4" - DHW

1.25" - DHW R

1" - MA

1.25" - MV

1" - DHW R3" - DHW

3" - DCW1.25" - O2

1" - MV1" - MA

1" -

DH

W

1" -

DC

W

1.25" - G

1.25" - G

A1 B1

4" SS DN

4" SS DN

LAV

NEW CAP

CO

2

1

D1

F1

NEW CAPSNEW CAPS

0.5"1"

3" -

F

3" - F

3" -

F

1.5"

-O

2

1.5"

-O

2

1"

2" -

V

2 " V U P

W C

1" - MV

1542AHVAC

1535CORR.

1527CORRIDOR

1544

ORDER

ENTRY

OFC

1542ANTI RM

1541CHEMO RM

1540

HD

NON-STERILE

1539NARC RM

1538POP

1533JAN

1550PACKAGING

1548RECEIVING

1547

ADA STAFF

TOILET

1546OFC

1545MGR. OFC

1543IV RM

1537A

BULK

STORAGE

1537

ORDER

ENTRY

OH1

OH1

NEW C APS

NEW C APS

7

5

5

7

7

5

5

OH1

E1

FD1 3

4

6

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

5/2

01

9 7

:04

:13

AM

C:\

BIM

\Mod

el\20

19

-05

07

8-M

EP

-Ce

ntr

al_

WS

McC

am

ey.r

vt

2019-05078

ABN

W SM

July 24, 2019

P201

PARTIAL FIRST FLOORPLAN - NEW W ORK

1 2019.07.24 ADDENDUM 1

SCALE: 1/4" = 1'-0"

PARTIAL FIRST FLOOR PLAN - NEW WORK1

NOTES

7 ROUTING OF FIRE MAIN SHALL FOLLOW THE HOT AND CHILLED WATERPIPING. COORDINATE ROUTING AND HANGERS CLOSELY WITH HC.

NOTES

1 ROUTE SANITARY PIPING THROUGH WALL AND DROP BEYONDELECTRICAL EQUIPMENT BELOW.

2 REROUTE EXISTING SANITARY PIPING AND CONNECT TO EXISTINGSANITARY STACK. COORDINATE NEW ROUTING CLOSELY WITH HC.

3 PROVIDE 3" FLOOR DRAIN WITH 12" STRAINER AND SEDIMENT BUCKET,JR SMITH #2130-B.

4 PROVIDE TRAP PRIMER, PPP INC. #PR-500. EXTEND TRAP PRIMERDISCHARGE AND TERMINATE ABOVE FLOOR DRAIN.

5 PROVIDE NEW FIRE SUPPRESSION COVERAGE THROUGHOUTRENOVATED AREA PER NFPA 13 REQUIREMENTS.

6 PROVIDE GASKETED COVERPLATES IN THESE FOUR (4) ROOMS.

A. ELECTRONIC COORDINATION DRAW INGS ARE REQUIRED AND MUST BE SUBMITTED TO THE ENGINEER FOR REVIEW PRIOR TO BEGINNING NEW W ORK. REFER TO 23 05 01.

GENERAL NOTES

Page 15:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

NOTE: ALL SYMBOLS AND ABBREVIATIONS

ARE SUBJECT TO MODIFICATIONS

ON OTHER DRAWINGS.

ALL SYMBOLS OR ABBREVIATIONS

MIGHT NOT NECESSARILY BE USED ON

THIS PROJECT.

ABBREVIATIONS

AC - AIR COMPRESSOR OR AIR CONDITIONERACCU - AIR COOLED CONDENSING UNITAD - ACCESS DOOR OR AREA DRAINADJ - ADJUSTABLEAFF - ABOVE FIN ISHED FLOORAFG - ABOVE FIN ISHED GRADEAFMS - AIR FLOW MEASURING STATIONALT - ALTERNATEAP - ACCESS PANELAPPROX - APPROXIMATEARCH - ARCHITECT OR ARCHITECTURALASSY - ASSEMBLYATC - AUTOMATIC TEMPERATURE CONTROL

BDD - BACK DRAFT DAMPERBFP - BACKFLOW PREVENTERBLDG - BUILDINGBOB - BOTTOM OF BEAMBOD - BOTTOM OF DUCTBOE - BOTTOM OF EQUIPMENTBOF - BOTTOM OF FOOTINGBOG - BOTTOM OF GRILLEBOP - BOTTOM OF PIPEBOT - BOTTOMBTU - BRITISH THERMAL UNITBTUH - BRITISH THERMAL UNIT PER HOUR

CBD - COUNTER BALANCED BACKDRAFT DAMPERCFCI - CONTRACTOR FURNISHED CONTRACTOR

INSTALLEDCFM - CUBIC FEET PER MINUTECHS - CHILLED W ATER SUPPLYCHR - CHILLED W ATER RETURNCHGR - CHILLED W ATER GLYCOL SOLUTION RETURNCHGS - CHILLED W ATER GLYCOL SOLUTION SUPPLYCLG - CEILINGCMU - CONCRETE MASONRY UNITCO - CLEAN OUTCO2 - CARBON DIOXIDECONN - CONNECT OR CONNECTIONCONTR - CONTRACTORCTR - CENTERCU - COPPERCW - COLD W ATERCW R - CONDENSER W ATER RETURNCW S - CONDENSER W ATER SUPPLY

D - DRAIN LINEDB - DRY BULBDDC - DIRECT DIGITAL CONTROLSDI - DEIONIZED W ATERDIA - DIAMETERDIM - DIMENSIONDN - DOW NDW G - DRAW ING

EA - EACH OR EXHAUST AIREAT - ENTERING AIR TEMPERATUREEC - ELECTRICAL CONTRACTOR (DIVISION 26)EJ - EXPANSION JOINTELEC - ELECTRICALELEV - ELEVATOREQUIP - EQUIPMENTET - EXPANSION TANKETR - EXISTING TO REMAINEQS - EQUIPMENT SUPPLIEREW T - ENTERING W ATER TEMPERATUREEXH - EXHAUSTEXP - EXPANSIONEXT - EXTERIOREX - EXISTING

FD - FLOOR DRAINFF - FINISHED FLOOR ELEVATIONFLR - FLOORFOB - FLAT ON BOTTOMFOF - FUEL OIL FLOWFOG - FUEL OIL GAUGEFOR - FUEL OIL RETURNFOS - FUEL OIL SUPPLYFOT - FLAT ON TOPFPM - FEET PER MINUTEFSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)FT - FEETFTG - FOOTING

G - GAS OR NATURAL GASGA - GAUGEGAL - GALLONGALV - GALVANIZEDGC - GENERAL TRADES CONTRACTORGPM - GALLONS PER MINUTE

HB - HOSE BIBBHC - HVAC CONTRACTOR (DIVISION 23)HD - HUB DRAINHG - REFRIGERANT HOT GASHP - HORSEPOW ERHPC - HIGH PRESSURE CONDENSATE RETURNHPS - HIGH PRESSURE STEAM SUPPLYHR - HOURHT - HEAT TRACEHTR - HEATERHVAC - HEATING, VENTILATING, AND AIR CONDITIONINGHW - HOT W ATERHW R - HEATING HOT W ATER RETURNHW S - HEATING HOT W ATER SUPPLY

ID - INSIDE DIAMETERINV - INVERT ELEVATIONIN - INCHES

KEC - KITCHEN EQUIPMENT CONTRACTOR

L - LENGTHLAT - LEAVING AIR TEMPERATURELAV - LAVATORYLBS - POUNDSLPC - LOW PRESSURE CONDENSATE RETURNLPS - LOW PRESSURE STEAM SUPPLYLW T - LEAVING W ATER TEMPERATURE

MAX - MAXIMUMMDD - MOTORIZED DAMPERMEZZ - MEZZANINEMFR - MANUFACTURERMH - MANHOLEMIN - MINIMUM OR MINUTEMISC - MISCELLANEOUSMTD - MOUNTEDMTG - MOUNTINGMPC - MEDIUM PRESSURE CONDENSATE

RETURNMPS - MEDIUM PRESSURE STEAM SUPPLYMU - W ATER MAKE-UP

N/C - NORMALLY CLOSEDNIC - NOT IN CONTRACTN/O - NORMALLY OPENNOM - NOMINALNPT - NATIONAL PIPE THREADNTS - NOT TO SCALE

OA - OUTDOOR AIROBD - OPPOSED BLADE DAMPEROD - OUTSIDE DIAMETEROFCI - OW NER FURNISHED CONTRACTOR

INSTALLEDOFOI - OW NER FURNISHED OW NER INSTALLED

P - PROPANE GASPC - PLUMBING CONTRACTOR (DIVISION 22)

OR PUMPED CONDENSATE RETURNPLBG - PLUMBINGPRESS - PRESSUREPRV - PRESSURE REGULATING VALVEPSF - POUNDS PER SQUARE FOOTPSI - POUNDS PER SQUARE INCHPSIG - POUNDS PER SQUARE INCH GAUGE

RA - RETURN AIRRAD - RADIUSRCP - REFLECTED CEILING PLANRD - ROOF DRAINREC - RECESSEDREQD - REQUIREDRI - ROUGH INRL - REFRIGERANT LIQUIDROS - REVERSE OSMOSIS W ATER SUPPLYROR - REVERSE OSMOSIS W ATER RETURNRPM - REVOLUTIONS PER MINUTERS - REFRIGERANT SUCTION

S - SPRINKLER (W ET)SA - SUPPLY AIRSAN - SANITARY OR SANITARY DRAINSCH - SCHEDULESCW - SOFT COLD W ATERSHT - SHEETSPEC - SPECIFICATIONSSQ - SQUARESR - SUPPLY RISERSRV - SAFETY RELIEF VALVESS - STAINLESS STEELSTD - STANDARDSTM - STORM OR STORM DRAINAGESTRUC - STRUCTURAL OR STRUCTURESUC - SITE UTILITY CONTRACTOR

TEMP - TEMPERATURETOB - TOP OF BEAMTOD - TOP OF DUCTTOE - TOP OF EQUIPMENTTOF - TOP OF FOOTINGTOJ - TOP OF JOISTTOP - TOP OF PIPETOS - TOP OF SLAB OR TOP OF STEELTYP - TYPICAL

UNO - UNLESS NOTED OTHERW ISE

V - VENTVAC - VACUUMVEL - VELOCITYVIB - VALVE IN BOXVOL - VOLUMEVTR - VENT THROUGH ROOFVR - VENT RISER

W / - W ITHW /O - W ITHOUTW B - W ET BULBW CO - W ALL CLEANOUT

GENERAL FLOOR PLAN NOTES

PLAN NOTE. APPLIES ONLY TO THE SHEET W HICH IT IS SHOW N UNLESS NOTED OTHERW ISE.

DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

3

3

A1EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK. LETTER DESIGNATIONS REFER TO SCHEDULES.

H1 H1OREQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TO SCHEDULES.

2

1

H2

B

H2

RISER OR STACK NUMBER

DETAIL: B = DETAIL DESIGNATION H2 = SHEET W HERE DETAIL IS LOCATED

SECTION: 1 = SECTION DESIGNATION H2 = SHEET W HERE DETAIL IS LOCATED

A1 "UP TO" SYMBOL (ITEM ON FLOOR ABOVE)

APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR BOTTOM OF EQUIPMENT, UNLESS NOTED OTHERW ISE

10"

ELEV: 8' - 0"ELEV: 8' - 0"

TOD: 8' - 10"

BOD: 7' - 2"

20x20

20x20

APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR BOTTOM OF DUCTW ORK, UNLESS NOTED OTHERW ISE

APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO CENTERLINE OF PIPE, UNLESS NOTED OTHERW ISE

DL-1

UC-X DOOR UNDERCUT. X = HEIGHT OF UNDERCUT IN INCHES; 0.75 INCH UNDERCUT IF NO HEIGHT IS NOTED. COORDINATE W ITH GC.

DOOR LOUVER. 1 = SQUARE FEET OF LOUVER.

CONNECT TO EXISTING

HVAC PIPING DESIGNATIONS

CHILLED W ATER SUPPLY PIPECHS

CONDENSER W ATER SUPPLY PIPECW S

CONDENSER W ATER RETURN PIPECW R

DRAIN LINE. PITCH IN DIRECTION INDICATEDD

HEATING HOT W ATER SUPPLY PIPEHW S

HEATING HOT W ATER RETURN PIPEHW R

W ATER MAKE-UP PIPEMU

VENT PIPEV

REFRIGERANT LIQUID LINERL

REFRIGERANT SUCTION LINERS

EXPANSION TANK PIPEET

REFRIGERANT HOT GAS LINEHG

LOW PRESSURE CONDENSATE RETURN PIPELPC

LOW PRESSUR E STEAM SUPPLY PIPELPS

M EDIUM PRESSURE CON DENSATE RETURN PIPEMPC

M EDIUM PRESSURE STEAM SUPPLY PIPEM PS

PUMPED CONDENSATE RETURN PIPEPC

HIGH PRESSURE CONDENSATE RETURN PIPEHPC

HIGH PRESSURE STEAM SUPPLY PIPEHPS

STEAM SUPPLY PIPE - NUMBER INDICATES P.S.I.G.10

MISC SYMBOLS

DUCTWORK SYMBOLS

ROUND BRANCH DUCTW ORKCONICALFITTING

ACOUSTICFITTING

ACOUSTICFITTING

ADAD

D

R R

D

RECTANGULAR BRANCH DUC TW ORK

SQUARE TEE W ITH TURNING VANES

NOTE: ALL SQUARE ELBOW S IN RECTANGULAR AND ROUND / OVAL DUCTW ORK SHALL BE PROVIDED W ITH TURNING VANES. REFER TO SPECIFICATIONS FOR ADDITIONAL DETAILS.

EXISTING DUCTW ORK TO REMOVED

RETURN AIR, RELIEF AIR, OR TRANSFER AIR DUCTW ORK. (UP AND DOW N) RADIUSED OR SQUARE W ITH TURNING VANES.SUPPLY AIR OR OUTDOOR AIR DUCTW ORK.(UP AND DOW N) RADIUSED OR SQUARE W ITH TURNING VANES.

EXHAUST AIR DUCTW ORK. (UP AND DOW N) RADIUSED OR SQUARE W ITH TURNING VANES.

RECTANGULAR AND ROUND / OVAL DUCTW ORK RISE / DROP W ITH 90° RADIUSED OR SQUARE ELBOW S AND TURNING VANES.

RADIUS ELBOW

90° SQUARE ELBOW (W ITH TURNING VANES)NOTE: ALL SQUARE ELBOW S IN RECTANGULAR AND ROUND DUCTW ORK SHALL BE PROVIDED W ITH TURNING VANES.

ACCESS DOOR OR PANEL

DUCTW ORK RISE IN DIRECTION OF AIR FLOW

DUCTW ORK DROP IN DIRECTION OF AIR FLOW

DUCTW ORK W ITH ACOUSTICAL LINER. LISTED DUCT SIZES ARE INSIDE CLEAR DIMENSIONS.

RECTANGULAR ROUND / OVAL

FLEXIBLE DUCTW ORK

FLEXIBLE CONNECTION

DUCTW ORK CONSTRUCTED OF SPECIAL MATERIAL AS NOTED

DIRECTION OF PITCH

RECTANGULAR DUCTW ORK DIMENSIONS(W x H)26x20

ROUND DUCTW ORK DIMENSIONS (DIA)26ø

OVAL DUCTW ORK DIMENSIONS (W x H)26x20 OV

DUCTWORK DEVICE SYMBOLS

W ALL OR DUCTW ORK MOUNTED AIR DEVICE. SG1 = DESIGNATION (REFER TO AIR DEVICE SCHEDULE). 20x12 = DUCT CONNECTION SIZE (IN INCHES).300 = REQUIRED CFM. 9'-0" = MOUNTING HEIGHT FROM FLOOR TO BOTTOM OF GRILLE.

A310ø300

MANUAL BALANCING VALVE DAMPER W ITH LOCKING DEVICE

BDD = BACK DRAFT DAMPERCBD = COUNTER-BALANCED BACK DRAFT DAMPER

SD = SMOKE DAMPERFS = COMBINATION FIRE - SMOKE DAMPERMDD = MOTORIZED DAMPERAFMS = AIR FLOW MEASURING STATION

DUCT MOUNTED SMOKE DETECTOR. COORDINATE LOCATION.

HUMIDITY SENSOR - DUCT MOUNTED

SG120x12

300BOG: 9'-0"

XXX

A-D

XX

H

SD

SP

AIR DEVICE. A3 = DESIGNATION (REFER TO FLOOR PLANS AND AIR DEVICE SCHEDULE FOR VARIOUS DESIGNATIONS).10ø = NECK SIZE (IN INCHES). 300 = REQUIRED CFM. ALL AIR DEVICE DISCHARGE 4-W AY UNLESS NOTED W ITH FLOW ARROW S. AIR DEVICE SHOW N IS 2-W AY SIDE THROW . METHOD OF IDENTIFICATION ALSO APPLIES TO OTHER CEILING MOUNTED AIR DEVICES.

FIRE DAMPERA = TYPE (REFER TO FLOOR PLANS FOR VARIOUS TYPES)D OR S = DYNAMIC OR STATIC

STATIC PRESSURE SENSOR - DUCT MOUNTED

CCARBON D IOXIDE SENSOR - DUCT MOUNTED

STEMPERATURE SENSOR - DUCT MOUNTED

CHECK VALVE

T

P

FOB

FOT

SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR REQUIRED TYPE BASED ON APPLICATIONS)

CONCENTRIC PIPE REDUCER

ECCENTRIC PIPE REDUCER

PRESSURE GAUGE

TEMPERATURE GAUGE OR THERMOMETER

COMBINATION SHUTOFF AND BALANCING VALVE (REFER TO SPECIFICATIONS FOR REQUIRED TYPE BASED ON APPLICATIONS)

BALL VALVE

BUTTERFLY VALVE

GATE VALVE

VALVES AND FITTINGSDOUBLE LINE SINGLE LINE

10"

TOE: 3' - 0"

BOE: 0' - 6"

CHILLED W ATER GLYCOL SOLUTION RETURN PIPECHGR

CHILLED W ATER GLYCOL SOLUTION SUPPLY PIPECHGS

CHILLED W ATER RETURN PIPECHR

SQUARE THROAT / RADIUS HEEL FITTINGS NOT ACCEPTABLE

PIPING SYMBOLSDOUBLE LINE SINGLE LINE

BOTTOM CONNECTION (45°)

BRANCH TEE CONNECTION (NOTE: BULLHEAD TEE'S ARE NOT PERMITTED)

DIRECTION OF PITCH

DROP

ELBOW DOW N

ELBOW UP

EXISTING PIPE TO BE REMOVED

EXISTING PIPE TO REMAIN

FLOW DIRECTION DESIGNATION

PUMP

RISE

TOP CONNECTION (45°)

TOP CONNECTION (90°)

BOTTOM CONNECTION (90°)

DD

RR

PIPE RISER

RADIUS'D BRANCH

RADIUS'D TEE

EXISTING DUCTW ORK TO REMAIN

UNLESS NOTED OTHERW ISE ON DRAW INGS, 15° MAX FOR DIVERGING, 30° MAX FOR CONVERGING TRANSITION

EMERGENCY SHUTOFF STATION. 46" MOUNTING HEIGHT UNLESS NOTED OTHERW ISE.

SPACE TEMPERATURE SENSOR / THERMOSTAT. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.

T

DPDIFFERENTIAL PRESSURE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.

HHUMIDITY SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.

CARBON DIOXIDE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.

C

COCARBON MONOXIDE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.

TEMPERATURE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.

S

S TEMPERATURE SENSOR MOUNTED IN CEILING PLENUM.

STATIC PRESSURE SENSOR.SP

STRAINER W ITH A BLOW DOW N VALVE AND HOSE CONNECTION

DRAIN VALVE W ITH HOSE END CONNECTION

AUTOMATIC FLOW CONTROLLER W ITH P/T PLUG IN AND OUT

EXPANSION JOINT

MANUAL AIR VENT

AUTOMATIC AIR VENT

PRESSURE REDUCING VALVE

2 PORT AUTOMATIC CONTROL VALVE

3 PORT AUTOMATIC CONTROL VALVE

QUICK OPENING MANUAL VALVE

VACUUM BREAKER

NEEDLE VALVE

PRESSURE AND TEMPERATURE TEST PLUG

VACUUM GAUGE W ITH STOP

END CAP

GLOBE VALVE

SHUTOFF VALVE AND BOX

SHUTOFF VALVE ON RISER

A

M

M

N

V

VB

SOLENOID VALVES

SAFETY RELIEF VALVE. FOR HYDRONIC SYSTEMS PIPE DISCHARGE AIR GAPPED TO FLOOR DRAIN UNLESS NOTED OTHERW ISE. FOR STEAM SYSTEMS PIPE DISCHARGE TO OUTDOORS.

W ATER METERM

PRESSURE GAU GE W ITH COCK AND SIPHON LOOP

BI-M ETALIC STEAM TRAP AND DRIP ASSEM BLY

THERMODYNAMIC STEAM TRAP AND DRIP ASSEMBLY

INVERTED BUCKET STEAM TRAP AND DRIP ASSEMBLY

FLOAT AND THERMOSTATIC STEAM TRAP AND DRIP ASSEMBLY

THERM OSTATIC STEAM TRAP AND DRIP ASSEM BLY

BM

TD

IB

FT

TS

FLOW M ETERF

UNION

CLEANOUT

STRAINER

AUTOMATIC PRESSURE INDEPENDENT CONTROL VALVE

M

HVAC GENERAL NOTES

A. THESE NOTES APPLY EQUALLY TO THE FULL SET OF DOCUMENTS.

B. INCLUDE ALL W ORK NECESSARY TO ACCOMMODATE PHASING. REFER TO ARCHITECTURAL DRAW INGS AND GENERAL REQUIREMENTS SECTION 01 00 00.

C. INSULATE DUCTW ORK AND PIPING W HERE EXISTING INSULATION HAS BEEN DAMAGED AND/OR REMOVED IN THE PERFORMANCE OF W ORK IN THIS PROJECT.

D. PROVIDE ALL ROOFING PENETRATION, REPAIR & REINFORCEMENT IN THE EXISTING BUILD ING FOR W ORK INDICATED. ENGAGE A ROOFING SUBCONTRACTOR TO PERFORM THE ROOFING W ORK. W HERE ROOFING W ORK IS REQUIRED, THE EXISTING ROOFING MEMBRANE AND INSULATION SHALL BE CUT, REMOVED AND RESTORED AS REQUIRED TO ATTAIN A W ATERTIGHT CONDITION. THE ROOFING SUB-CONTRACTOR SHALL BE A CERTIFIED INSTALLER FOR SUCH INSTALLATION TO MAINTAIN THE EXISTING W ARRANTY ON THE ROOF.

E. THE CONTRACTOR SHALL REFER TO ALL SPECIFICATION SECTIONS AND THESE DRAW INGS FOR DETAILS OF BUILDING CONSTRUCTION TO ENSURE SPACE AND SATISFACTORY ARRANGEMENT FOR THEIR W ORK. THE VARIOUS DRAW INGS COMPRISING THE SET ARE INTERDEPENDENT AND MUST BE USED JOINTLY AT ALL TIMES. THE CONTRACTOR SHALL REFER TO THE GENERAL REQUIREMENTS OF THE CONTRACT. THE NOTES AND SYMBOLS INDICATED ON THE DRAW INGS ARE FOR THE GUIDANCE OF ALL TRADES INVOLVED IN THE PROJECT AND MUST BE FOLLOW ED TO EXECUTE THE W ORK AS INTENDED. IF DISCREPANCIES OCCUR, CONTACT THE COR THRU THE CONTRACTING OFFICER FOR CLARIFICATION BEFORE PROCEEDING.

F. IN ACCORDANCE W ITH GENERALLY ACCEPTED CONSTRUCTION PRACTICES, THE CONTRACTOR W ILL BE SOLELY AND COMPLETELY RESPONSIBLE FOR THE CONDITIONS ON THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY DURING PERFORMANCE OF THE W ORK. THIS W ILL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL W ORKING HOURS. SEE SPECIFICATIONS FOR MORE SPECIFIC DETAILS ON RESPONSIBILITIES.

G. ALL W ORK MUST BE COORDINATED W ITH THE CONTRACTING OFFICER AND COR TO MAINTAIN OPERATION OF THE EXISTING FACILITY.

H. EACH CONTRACTOR SHALL COORDINATE HIS W ORK W ITH THE W ORK OF OTHERS. HE SHALL KEEP HIMSELF INFORMED OF THE PROGRESS AND DETAIL DEVELOPMENT OF THE W ORK OF OTHERS AND SHALL BE RESPONSIBLE FOR COORDINATING AND EXPEDITING HIS W ORK W ITH OTHERS SO THAT THE PROGRESS OF THE TOTAL W ORK SHALL BE KEPT ON SCHEDULE.

I. ALL W ORK SHALL BE PERFORMED IN COMPLETE COMPLIANCE W ITH ALL GOVERNING CODES AND STANDARDS.

J. EXISTING CONDITIONS SHOW N HAVE BEEN BASED UPON AVAILABLE DRAW ING INFORMATION, AND MAY BE AT VARIANCE W ITH ACTUAL W ORK IN PLACE. THE CONTRACTOR SHALL TAKE ALL NECESSARY FIELD MEASUREMENTS AND FIELD VERIFY ALL CONDITIONS AFFECTING THE EXECUTION OF THE W ORK. ANY DISCREPANCIES BETW EEN EXISTING CONDITIONS AND THE W ORK SHOW N ON THE CONTRACT DOCUMENTS W HICH MAY IMPACT THE PROGRESS OF THE W ORK SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER IN W RITING FOR RESOLUTION BEFORE PROCEEDING W ITH THE W ORK.

K. EACH CONTRACTOR AND/OR TRADE, FITTING OR PLACING HIS W ORK INTO OR ON THE W ORK OF OTHERS DOES SO W ITH THE UNDERSTANDING THAT THE INSTALLATION OF H IS W ORK CONSTITUTES HIS ACCEPTANCE OF THE SUITABILITY OF THE W ORK IN PLACE. IF THE W ORK OF OTHERS IS NOT ACCEPTABLE, HE SHALL NOTIFY THE COR AND SUCH W ORK SHALL BE CORRECTED. ANY NEW W ORK INSTALLED IN UNSUITABLE EXISTING W ORK SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR OR TRADE INSTALLING THE NEW W ORK. NO CLAIMS FOR ADDITIONAL COMPENSATION FOR CORRECTING W ORK INSTALLED IN UNSUITABLE EXISTING CONDITIONS W ILL BE CONSIDERED.

L. IF, IN THE PERFORMANCE OF THIS W ORK, MATERIALS ARE OBSERVED W HICH ARE SUSPECTED TO CONTAIN ASBESTOS, THE CONTRACTOR SHALL IMMEDIATELY INFORM THE COR. W ORK THAT W OULD EXPOSE W ORKERS TO THE INHALATION OF ASBESTOS PARTICLES SHALL BE TERMINATED. W ORK MAY BE RESUMED ONLY AFTER A DETERMINATION HAS BEEN MADE AND UNSAFE MATERIALS HAVE BEEN REMOVED OR ENCAPSULATED AND THE AREA DECLARED SAFE.

M . CONTRACTORS SHALL TAKE SPECIAL CARE W HILE W ORKING ADJACENT TO ASBESTOS MATERIALS AND MUST BE PROPERLY PROTECTED W ITH CLOTHING, BREATHING APPARATUS, ETC. VERIFY REQUIREMENTS OF VAMC'S INFECTION CONTROL RISK ASSESSMENT TEAM (ICRA).

N. THE FIRST FIGURE OF DUCT SIZE INDICATES D IMENSION OF FACE SHOW N OR INDICATED. DUCT SIZES ARE NET INSIDE DIMENSIONS.

O. PROVIDE DUCT ACCESS PANELS AS REQUIRED BY 23 31 00 FOR ACCESS TO FIRE DAMPERS, SMOKE DAMPERS, SMOKE DETECTORS, AUTOMATIC CONTROL DAMPERS, AND HUMIDIFIER DISPERSION TUBES. REFER TO DETAIL ON SHEET M0.3. COORDINATE SIZES AND LOCATIONS W ITH ACCESSORIES PROVIDED BY OTHER TRADES.

P. ALL PRESSURES LISTED ARE GAGE PRESSURE UNLESS OTHERW ISE NOTED.

Q. ALL CUTTING AND PATCHING REQUIRED FOR THIS PROJECT SHALL BE INCLUDED IN THE CONTRACT. REFINISH ANY SURFACE DISTURBED UNDER THIS W ORK TO MATCH EXISTING.

R. THE CONTRACT DRAW INGS ARE NOT INTENDED TO SHOW EVERY VERTICAL OR HORIZONTAL OFFSET W HICH MAY BE NECESSARY TO COMPLETE THE SYSTEMS. COORDINATE W ORK IN ADVANCE W ITH ALL OTHER TRADES AND REPORT IMMEDIATELY ANY DIFFICULTIES W HICH CAN BE ANTICIPATED.

S. FIELD VERIFY EXISTING CONDITIONS, INCLUDING DUCT, PIPE AND EQUIPMENT SIZES, SERVICES AND LOCATIONS PRIOR TO PERFORMING W ORK.

T. ALL ABANDONED EXTRANEOUS PIPING, DUCTW ORK, SUPPORTS, CONTROLS, ETC. SHALL BE REMOVED.

U. W HERE CONTROL DEVICES ARE REMOVED, PNEUMATIC LINES SHALL BE REMOVED BACK TO MAIN AND CAPPED; AND CONTROL W IRING AND CONDUIT SHALL BE REMOVED BACK TO SOURCE.

V. ALL EXISTING DUCTW ORK, PIPING, EQUIPMENT, CONTROLS, ETC. SHOW N DASHED SHALL BE REMOVED. THE MAJORITY OF W ORK TO BE REMOVED IS SHOW N. REMOVE ALL INC IDENTAL AND/OR ABANDONED DUCTW ORK, PIPING, ETC. THAT MAY NOT BE SHOW N BUT IS ASSOCIATED W ITH THE REMOVAL W ORK.

W . ALL ITEMS THAT REQUIRE ACCESS, SUCH AS FOR OPERATING, CLEANING, SERVICING, MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE BY PERSONS STANDING AT FLOOR LEVEL, OR STANDING ON PERMANENT PLATFORMS, W ITHOUT THE USE OF PORTABLE LADDERS. EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF VALVES, FILTERS AND STRAINER, TRANSMITTERS, CONTROL DEVICES, ETC.

X. REFER TO SPECIFICATIONS SECTION 01 00 00 GENERAL REQUIREMENTS AND THESE DRAW INGS FOR DESCRIPTIONS OF THE BID ITEMS INCLUDING DEDUCT ALTERNATES, ADDITIONAL INFORMATION NOTED THROUGHOUT THE DRAW INGS.

Y. SYSTEMS SERVING AREAS OUTSIDE THE CONSTRUCTION ZONE SHALL REMAIN OPERATIONAL DURING CONSTRUCTION. ANY OUTAGES SHALL BE PERFORMED ON W EEKENDS OR W EEK NIGHTS. DOW NTIME SHALL BE KEPT TO A MINIMUM, AND SHALL BE COORDINATED AND SCHEDULED 4 W EEKS (30 CALENDAR DAYS) IN ADVANCE W ITH THE COR.

Z. REFER TO NEW W ORK FLOOR PLANS FOR W ORK THAT MAY BE REQUIRED PRIOR TO ANY REMOVAL W ORK.

AA. READ ALL NOTES THOROUGHLY PRIOR TO STARTING CONSTRUCTION.

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

5/2

01

9 1

2:2

0:4

4 P

MC

:\B

IM\M

ode

l\20

19

-05

07

8-M

EP

-Ce

ntr

al_

ajg

ran

ata

@h

ea

py.c

om

.rvt

2019-05078

DTR

AJG

July 24, 2019

M001

MECHANICAL LEGEND,GENERAL NOTES, ANDINDEX OF DRAW INGS

1 2019.07.24 ADDENDUM 1

SHEET INDEX - MECHANICAL

SHEET NUMBER SHEET NAME

M001 MECHANICAL LEGEND, GENERAL NOTES, AND INDEX OF DRAWINGS

M002 MECHANICAL SCHEDULES

M003 MECHANICAL DETAILS

M004 MECHANICAL DETAILS

M005 MECHANICAL DETAILS

M007 MECHANICAL CONTROL SCHEMATICS

M008 MECHANICAL CONTROL SCHEMATICS

M101 PARTIAL FIRST FLOOR PLAN - DEMOLITION

M201 PARTIAL FIRST FLOOR PLAN - NEW WORK

M301 HVAC ROOF

Total Count: 10

Page 16:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

C.V.R. 300 300 9.8 1.0 0.75" 0.4 3524-03ASUPPLY

V.V. 650 420 - - - - 3524-03B 12"ROOM EX. 7

V.V. - - - - 3524-03C 8"

- - - - -TOTAL CHEMO

930 930

3,4,5,6

-350

4. AIR VALVE TO HAVE EPOXY COATING TO RESIST CORROSION.

6. AIR VALVE SHALL BE ENABLED BY "AUXILIARY" SWITCH ON HOOD.

5. PROVIDE AIR-TIGHT SHUTOFF DAMPER AT BSC EQUIPMENT CONNECTION.

7. PROVIDE BLAST GATE DOWN STREAM OF ROOM EXHAUST AIR VALVE.

1. MINIMUM ROOM SUPPLY SHALL BE THE SCHEDULED "OCCUPIED MINIMUM" AS NOTED.

2. MINIMUM ROOM EXHAUST SHALL BE THE ROOM SUPPLY MINUS CFM OFFSET.

3. AIR VALVE SHALL BE SHUT-OFF TYPE.

C.V.R. 1,520 1,520 49.5 5.0 1.0" 2.3 3524-01A 14"SUPPLY 1

C.V. 1120 1120 - - - - 3524-01B 14"RETURN 7

+400

IV ROOM

2

2-WAY

-

-

-

2-WAY

-

1

TYPES - "V.V." VARIABLE VOLUME;

"V.V.R." VARIABLE VOLUME REHEAT;

"C.V.R." CONSTANT VOLUME REHEAT;

UNIT & COIL AT MAX. CFM (VAV BOX).

0.5" S.P. MAX. PRESS. DROP THRU

"C.V." CONSTANT VOLUME.REHEAT COIL CAPACITY BASED ON

WINTER MIN. CFM, 53° ENT. AIR, 180° ENT.

WATER TEMPERATURE, 160° LVG. WATER

TEMPERATURE, MAX 7 FT. HD. W.P.D.

8"

AIR VALVE 0.3" MAX PRESS.

DROP THRU UNIT AT MAX CFM.

1543

C.V.R. 510 510 15.5 1.6 0.75" 0.7 3524-02A 10"SUPPLY 1

C.V. 235 235 - - - - 3524-02B 8"RETURN 7

+275

ANTE 2-WAY

-

1542

CHEMO

CHEMO

CHEMO

- - - - -TOTAL STORAGE

450 450 2-

1541

HOOD EX.

ROOM EXHAUST

ROOM EXHAUST

C.V.R. 200 200 6.6 0.7 0.75" 0.3 35SUPPLY 1

C.V. 400 400 - - - - 35RETURN 7

-200

HD STOR. 2-WAY

-

1540

8"24-04A

24-04B 10"

650 420

EXHAUST DUCTWORK, NEW EF-92

SUPPLY DUCTWORK DOWNSTREAM OF

RETURN DUCTWORK

VAV BOXESA+1"

-6"

-2"

A

A

X

X

X

16/8

16/8

4/2

2

NOTES:1 DUCTWORK OVER 3" S.P. CLASS REQUIRES LEAK TESTING. REFER TO SPECIFICATIONS.

2 ROUND, SHEET METAL RUN-OUTS TO AIR DEVICES, DOWNSTREAM OF VAV BOXES SHALL BE EXTERNALLY INSULATED.

3 INSULATE FROM 24" UPSTREAM OF CONTROL DAMPER TO PENETRATION OF ROOF.

VAV BOXESSUPPLY DUCTWORK UPSTREAM OF

+3 4/2 XA 1

EF-92 PHARMACY CHEMO EXHAUST 1,300UTILITY SET FAN 1, 2, 3, 4, 5, 6, 7, 8

1 COORDINATE ACTUAL EQUIPMENT NUMBER WITH BUILDING CONTROLS.

2 PROVIDE FAN WITH MOTORIZED DAMPER EQUAL TO TAMCO SERIES 9000. WHEN FAN IS OFF, DAMPER SHALL BE CLOSED. DAMPER ACTUATOR SHALL HAVE END SWITCH TO PREVENT THE

FAN FROM TURNING ON UNTIL THE DAMPER IS PROVEN OPEN. DAMPER SHALL BE LOCATED IN THE DUCTWORK BELOW THE ROOF, REFER TO DETAIL.

3 PROVIDE UTILITY SET FAN WITH 10' STACK ABOVE ROOF, REFER TO DETAIL.

4 PROVIDE FAN WITH 8" DISCHARGE, REFER TO DETAIL.

1 AIR DEVICE USED FOR RETURN AIR SYSTEM.

A1STANDARD SQ. CONE CEILING

DIFFUSER - ROUND NECKTITUS - TMS-AA

J1 EGGCRATE CEILING GRILLE TITUS - 50F 1

5 FAN SHALL BE ON EMERGENCY POWER.

6 3,600 RPM MOTOR.

1

7 FAN SHALL BE PROVIDED WITH A BOTTOM UPWARDS (BAU) DISCHARGE, REFER TO DETAIL.

8 FAN SHALL BE PROVIDED WITH A VARIABLE FREQUENCY DRIVE WITH BYPASS.

HU-5

ELEVATION BASED ON 499 FT.

ULTRA-SORB XV AIR HANDLER AHU-5 2,800 53.3 34 55 71 68 451.0" 0.75" 24" 16" 14" 1, 2

HUMIDIFIER BASED ON 40 PSIG ENTERING STEAM PRESSURE.

45.9

MOTOR - 480V - 3 PHASE UNLESS NOTED OTHERWISE.

COOLING COIL CAPACITY BASED ON 42° EWT.HEATING COIL CAPACITY BASED ON 180° EWT.

AHU-24

COOLING COILS SHALL NOT

1 REFER TO STEAM HUMIDIFIER SCHEDULE ON THIS SHEET.2 PROVIDE UV LIGHTS ON COOLING COIL AND FINAL FILTER.

CAPACITIES BASED ON

7.4" / 2.6"

-

4,534

3,000

29

6.75

117

65

0.07"

12" MERV 14

8

SIDE ACCESS

0.18"

FRONT ACCESS

8

0.3"

1.0"

1.5"

215

7.0

133

30 - (1) 1.5"

86.0 / 70.0

45.7 / 45.7

17

14.5 / 2-WAY

1.18"

1,500 (50.0%)

INTERNAL - 2"

YES

YES

2

INGENIA

2" CARTRIDGE FILTER

3 PROVIDE UNIT WITH SINGLE POINT POWER CONNECTION. PROVIDE 120 VOLT

3

11.8 - (1) 1.5"

17

5.6 / 2-WAY

MERV 8

FIRST FLOOR

ROOF

DRAW THRU

3,000

PHARMACY

1. REFER TO PIPING DETAIL FOR PIPE ACCESSORIES.

2. HUMIDIFIER CONTROL PANEL REQUIRES 120V POWER FEED BY E.C.2,480

P-24 INLINE PUMP HOT WATER COIL - AHU-24 11 25 245 120 1 - - UP 26-99 F

RELIEF AIR DUCTWORK AND PLENUMS

OUTSIDE AIR DUCTWORK AND PLENUMS

+2"

-2"

A

A 16/8

16/8 3X

X

FCU-1

225

0.19

0.13

115 / 1

ECM

1, 2

RECEIVING

RECEIVING

CHILLED WATER

3.8

4.9

71 / 61

51 / 50

3.9

1.4

0.7 / 2-WAY

MERV 8

54

TRANE FCC

BLOW-THRU

0.5

0.1

85

65

3.2

0.2 / 2-WAY

FCU-2 FCU-3 FCU-4A FCU-4B FCU-5

HORIZ. CONC. DUCTED

700

0.19

0.22

115 / 1

ECM

1, 2

BULK STORAGE

BULK STORAGE

CHILLED WATER

9.0

10.0

72 / 61

51 / 50

18.1

6.5

3.0 / 2-WAY

MERV 8

212

TRANE FCC

BLOW-THRU

1.2

0.5

85

65

11.6

0.5 / 2-WAY

BULK STORAGE

1.2 / 2-WAY

MERV 8

106

TRANE FCC

1.2 / 2-WAY

MERV 8

106

TRANE FCC

0.8 / 2-WAY

MERV 8

71

TRANE FCC

CHILLED WATER

0.75

0.2

85

65

5.8

0.4 / 2-WAY

CHILLED WATER

0.75

0.2

85

65

5.8

0.4 / 2-WAY

CHILLED WATER

0.5

0.1

85

65

4.3

0.2 / 2-WAY

115 / 1 115 / 1 115 / 1

3.4

3.9

51 / 50

12.1

2.5

3.4

3.9

51 / 50

12.1

2.5

3.2

3.9

51 / 50

4.8

1.6

300

0.24

0.13

300

0.24

0.13

220

0.22

0.13

ECM ECM ECM

NARCOTICS & POPBULK STORAGEBULK STORAGE

BLOW-THRU BLOW-THRU BLOW-THRU

BULK STORAGE POP

HORIZ. CONC. DUCTED

300

0.19

0.13

115 / 1

ECM

1, 2

OFFICES

BULK STORAGE

CHILLED WATER

4.8

6.2

71 / 61

51 / 50

7.2

2.0

1.0 / 2-WAY

MERV 8

91

TRANE FCC

BLOW-THRU

0.5

0.1

85

65

4.1

0.2 / 2-WAY

72 / 61 72 / 61 72 / 61

1, 2 1, 2 1, 2

HORIZ. CONC. DUCTED HORIZ. CONC. DUCTED HORIZ. CONC. DUCTED HORIZ. CONC. DUCTED

EXCEED 12 FINS PER INCH.

CLEAR WATER.

1.75" / 1.5"

-

705

2,000

1,355

CONNECTION FOR UV LIGHTS, OUTLETS, LIGHTS, AND HEAT TRACE.

VENTILATION SCHEDULE

AIR SUPPLY UNIT

PHARMACY AIR CONTROL UNITS - HOT WATER

GENERAL NOTES

NOTES:

UNIT

NO. DIA.

INLETTYPEMIN. MBH GPM NOTE

SEE

VALVE CVAUTO.RUNOUT

SIZEN.C.

MAX.CFM REHEAT COILROOM

NO.

CFM

OFFSET MAX.

NOTE:

TYPEVALVE

DUCT CONSTRUCTION & SEALING

FANS

AIR DISTRIBUTION DEVICES

STEAM HUMIDIFIER

PUMPS

BLOWER COIL / FAN COIL

ELECTRIC HEATING UNITS

INSULATIONEXTERNAL

DUCTBOARD; ETC.

DUCT SYSTEM

S.M.A.C.N.A. CLASS.

S.P. CON-

STRUCT. CLASS

SEALINTERNALLY

CLASS

LEAKAGELINED

REFER TO SPECIFICATIONS FOR DUCT CONSTRUCTION:

SHEET METAL DUCT; INTERIOR LINING; EXTERIOR INSULATION; FIBERGLASS

GENERAL NOTES

NOTINSULATED

WALLINSULATED

DOUBLE

NOTES

RECT/RD

GENERAL CONTRACTOR.

WALL LINTEL FOR WALL OPENING BY

WHERE REQUIRED FOR DECK SUPPORT AND

STEEL FRAMING AROUND ROOF OPENING.

PHASE

CONSIDERED MINIMUM.

MOTOR HORSEPOWERS LISTED ARE TO BE

300 & 301 MEASURED AT 5 FT. FOR P.R.V.'S.

SONES VALUES BASED ON A.M.C.A. BULLETINS

DESCRIPTIONUNIT

NO.

CONTRACTOR.

VERIFY SIZE & COORDINATE WITH GENERAL

ROOF & WALL OPENINGS ARE APPROXIMATE.

SERVICESONES

MAX.STATIC WHEEL

PRESSCFM

DIA.

MOTOR

H.P. VOLT

ROOF/APPROX.

WALL OPG.

REFER TONOTE NO.

4.25" 12.25" 34 2 -480 3

BASIS OF

DESIGN

GREENHECKUSF-312-BI

GENERAL NOTES

W.B.E.

FINISH KEY: "W.B.E."- WHITE BAKED ENAMEL,

"E.C.L."-ETCHED CLEAR LACQUER OR ANODIZED.

SUPPLY AIR DIFFUSERS SHALL BE 4-WAY

BLOW UNLESS OTHERWISE NOTED ON DWGS.

DESCRIPTION

REFER TO SPECIFICATIONS FOR OTHER

ALL LAY-IN AIR DEVICES SHALL FIT IN

24"X24" LAY-IN CEILING SYSTEM.

SYMBOL

GENERAL NOTES

MANUFACTURERS.

TYPE MOUNTING MATERIAL

LAY-IN SURFACE STEEL

PROVIDE AUX. FRAMES FOR AIR DEVICES IN

CERAMIC TILE SURFACES.

PLASTER, GYPSUM BOARD, GLAZED TILE OR

FINISH CATALOG NUMBERACCESSORIES

O.B.D. - OPPOSED BLADE DAMPER

ALUM. E.C.L.

NOTES:

REFER TO

NOTE NO.SEE NOTE

EXT.

NO.UNIT

DESCRIPTION SERVICELB/HR

RUNOUTSUPPLY

RUNOUTCOND.

CFMRH(%)

ENTERING AIR

DB RH(%)

LEAVING AIR

DB RH(%)

ROOM

DB HEIGHT

FACE SIZE

WIDTHDISTANCE

ABSORPTIONREMARKS

- INCHES

GENERAL NOTES:

(INCLUDINGLOSS)

REMARKS

PR

E-H

EA

T C

OIL

LEAV. AIR

FACE AREA

HOUSING

PRESS. DROP IN. W.G. CLEAN

PR

E-F

ILT

ER

GPM - CONNECTION (QTY) SIZE

SENSIBLE MBH

TOTAL MBH

ENT. AIR DB/WB

LEAV. AIR DB/WB

AUTO. VALVE Cv & TYPE

MAX. WATER P.D.- FT.

MAX. AIR P.D.- INCHES W.G.

TYPE

CO

OLIN

G C

OIL

MIN. FACE AREA

MAX. AIR P.D. INCHES W.G.

WHEEL DIA.

WHEEL TYPE / CLASS

CAPACITY MBH

MOTOR (WATTS)

MIN. FACE AREA

TOTAL / EXT. S.P. - INCHES W.G.

ENT. AIR

SU

PP

LY

FA

N

GENERAL NOTES

UNIT LOCATION

AREA SERVED

UNIT NUMBER

UNIT CONFIGURATION

FACE AREA

HOUSING

PRESS. DROP IN. W.G. CLEAN

OUTSIDE AIR CFM

FIN

AL F

ILT

ER

TYPE

NOTES:

VIBRATION ISOLATORS

TOTAL SUPPLY CFM

PRESS. DROP IN. W.G. DIRTY

PRESS. DROP IN. W.G. DIRTY

UV LIGHTS

WINTER MIN. CFM

AIR SIDE ECONOMIZER

ECM PLENUM

BASIS OF DESIGN

GPM - CONNECTION (QTY) SIZE

AUTO. VALVE Cv & TYPE

MAX. WATER P.D.- FT.

APPROX. CONNECTED CFM

DISCHARGE

SUCTION &DESCRIPTION

UNIT

NO.

PERFORMANCE

GPMSERVICE

MOTOR

VOLTFT. HD. WATTS

MIN.

EFF.%PHASE MODEL NO.

GRUNDFOSSEE NOTE

NOTES:

MAX. WATER P.D.- FT.

AUTO. VALVE CV & TYPE

LEAV. AIR DB/WB

MAX. WATER P.D.- FT.

AUTO. VALVE CV & TYPE

ENT. AIR DB/WB

CO

OL

ING

CO

IL

FILTER

GPM

TOTAL MBH

COOLANT

SENSIBLE MBH

GPM

ENT. AIR

LEAV. AIR

HE

AT

ING

CO

IL

HEATING COIL CAPACITY BASED ON 130° ENT. WATER

COOLING COIL CAPACITY BASED ON 42° ENT. WATER

EXTERNAL S.P.-IN. W.G.

MOTOR H.P.

UNIT CONFIGURATION

SU

PP

LY

FA

N

CAPACITY MBH

CFM

UNIT NUMBER

AREA SERVED

UNIT LOCATION

GENERAL NOTES

VOLTAGE/PHASE

MINIMUM OUTSIDE AIR CFM

BASIS OF DESIGN

ARRANGEMENT

VFD

NOTES

NOTES:

1. PROVIDE WITH CONDENSATE PUMP EQUAL TO LITTLE GIANT MODEL # VCL-45ULS.

2. CONNECT CONDENSATE PUMP TO LOCAL 120V CIRCUIT. PROVIDE TOGGLE SWITCH DISCONNECT.

ELEC. SERVICE TO THREE-PHASE UNITSTOBE THREE-WIRE UNLESSNOTED

APPROX. CABINETDIMENSIONS

DEPTH

VERIFY/COORDINATE CABINET DIMENSIONS,MOUNTING

DESCRIPTION

AND RECESS REQUIREMENTS WITHARCHITECTURALDWGS. PRIOR TOORDERING.RECESSED UNITS TO HAVE FOUR(4) SIDEOVERLAP UNLESS OTHERWISENOTED

UNITNO.

GENERALNOTES:

BY GEN.CONT'R.

HEATING

LINTELS IN MASONRY WALLS FOR FULL&SEMI-RECESSED UNIT WALL OPENINGPROVIDED

THREE(3) PHASE COIL LOADS SHALL BEDIVIDEDEVENLY ACROSS EACHPHASE.

LOCATION CFMM.B.H.

ELEC.SERVICE

VOLTKW(MAX)KW(MIN) AMP LENGTHPHASE

REFERTONOTENO.HEIGHT RECESS

NOTES

1. BASIS OF DESIGN: TRANEUHEC

ELECTRIC UNITHEATER

4.0 3 14" 211.2400EUH-1 3.3 3.3 480 7" 17" -PROPELLERAHU-24

VESTIBULE

WHEEL DIA.

WHEEL TYPE / CLASS

MOTOR (WATTS)

TOTAL / EXT. S.P. - INCHES W.G.

RE

TU

RN

FA

N

TOTAL SUPPLY CFM

ECM PLENUM

APPROX. CONNECTED CFM

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

5/2

01

9 1

2:2

0:4

8 P

MC

:\B

IM\M

ode

l\20

19

-05

07

8-M

EP

-Ce

ntr

al_

ajg

ran

ata

@h

ea

py.c

om

.rvt

2019-05078

DTR

AJG

July 24, 2019

M002

MECHANICALSCHEDULES

1 2019.07.24 ADDENDUM 1

Page 17:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

.

7

8 5

1

8

2 3 6 4 9

610

TO AIR DEVICES

MAIN SUPPLY DUCT

1. CONICAL SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE. INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR TAP FITTING TO MAIN SUPPLY DUCT W ITH INTERNAL INSULATION.

2. ROUND SHEET METAL BRANCH DUCT, SAME SIZE AS AIR TERMINAL UNIT INLET SIZE UNLESS NOTED OTHERW ISE.

3. HARD DUCT CONNECTION TO AIR TERMINAL UNIT. FLEX CONNECTION NOT PERMITTED.

4. AIR TERMINAL UNIT.5. M INIMUM FOUR HANGER RODS FOR UNIT (CORNER

POINTS). ATTACH TO STRUCTURE.

6. TRANSITION W HEN REQUIRED.7. M INIMUM STRAIGHT LENGTH OF DUCT SHALL BE

TERMINAL UNIT MANUFACTURER'S REQUIRED LENGTH, BUT AT LEAST 3 TIMES UNIT INLET DIAMETER.

8. DUCT HANGER. ATTACH TO STRUCTURE.9. DUCT SHALL BE FULL SIZE OF UNIT OUTLET UNLESS

NOTED OTHERW ISE ON FLOOR PLANS.10. REHEAT COIL W HEN SPECIFIED. REFER TO COIL DETAIL.

NOTES

SUPPLY DUCT

6

8

4 3 45 4

6

9

182

10

7

CEILING CEILING DIFFUSER

1. SQUARE-TO-ROUND ADAPTER IF DIFFUSER NECK IS SQUARE. CONNECT ADAPTOR TO DIFFUSER. SEAL TO AIR DEVICE, SEAL CLASS A. INSULATE ADAPTOR AND EXPOSED BACKSIDE SURFACES OF AIR DEVICE.

2. INSULATED FLEXIBLE DUCT SAME DIAMETER AS BRANCH DUCT , 7 FT. MAXIMUM TOTAL LENGTH PER AIR DEVICE. STRETCH FLEXIBLE DUCT TO AT LEAST 90% OF FULLY EXTENDED LENGTH.

3. SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE W ITH MANUAL DAMPER. DAMPER SHAFT IN HORIZONTAL. INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR TAP FITTING TO MAIN DUCT W ITH INTERNAL INSULATION, AND EXTENDED DAMPER SHAFT AND HANDLE W ITH STAND-OFF TO ACCOMMODATE EXTERNAL INSULATION.

4. DUCT STRAP HANGER. ATTACH TO STRUCTURE.5. STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE DUCT IS

LONGER THAN 4 FT.

6. M INIMUM CENTERLINE RADIUS EQUAL TO DUCT DIAMETER.7. ROUND SHEET METAL BRANCH DUCT, SAME SIZE AS

DIFFUSER INLET UNLESS NOTED OTHERW ISE.8. FLEXIBLE DUCT ELBOW SUPPORT, INSTALLED W ITH NYLON

BANDING PER MANUFACTURER'S INSTRUCTIONS.9. A RADIUS'D SHEET METAL ELBOW MAY BE USED IN LIEU OF

A FLEXIBLE ELBOW SUPPORT W HEN CONNECTED DIRECTLY TO AIR DEVICE.

10. CEILING T-BAR SUPPORT (FOR LAY-IN APPLICATIONS). COORDINATE AND VERIFY T-BAR TYPE FOR COMPATIBILITY W ITH DIFFUSER.

7

NOTES

5

CEILING CEILING DIFFUSER

37

5

2 6 4 1

8

SUPPLY DUCT

1. SHEET METAL BOX W ITH SAME INTERNAL OR EXTERNAL INSULATION AS MAIN SUPPLYDUCT, 2" LARGER EACH DIRECTION THAN DIFFUSER NECK, W ITH ADAPTOR CONNECTIONTO DIFFUSER. CONNECT PLENUM TO DIFFUSER. SEAL BOX AND ADAPTOR TO AIRDEVICE, SEAL CLASS A. INSULATE ADAPTOR AND BACKSIDE SURFACES OF AIR DEVICE.

2. INSULATED FLEXIBLE DUCT SAME DIAMETER AS BRANCH DUCT , 7 FT. MAXIMUMTOTAL LENGTH PER AIR DEVICE. STRETCH FLEXIBLE DUCT TO AT LEAST 90% OF FULLYEXTENDED LENGTH.

3. SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE W ITH MANUAL DAMPER. DAMPER SHAFT INHORIZONTAL. INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR TAP FITTING TOMAIN DUCT W ITH INTERNAL INSULATION, AND EXTENDED DAMPER SHAFT AND HANDLEW ITH STAND-OFF TO ACCOMMODATE EXTERNAL INSULATION.

4. SPIN-IN TAP FITTING SIMILAR TO EXCEPT NO DAMPER.

5. DUCT STRAP HANGER. ATTACH TO STRUCTURE.

6. STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE DUCT IS LONGER THAN 4 FT.

7. ROUND SHEET METAL BRANCH DUCT, SAME SIZE AS DIFFUSER INLET UNLESS NOTEDOTHERW ISE.

8. CEILING T-BAR SUPPORT (FOR LAY-IN APPLICATIONS). COORDINATE AND VERIFY T-BARTYPE FOR COMPATIBILITY W ITH DIFFUSER.

7

3

NOTES

ROUND SHEETMETAL BRANCH DUCT

BRANCH CFM RD. DUCT SIZE

0 TO 80 CFM 6"D

81 TO 120 CFM 7"D

121 TO 200 CFM 8"D

401 TO 700 CFM 12"D

701 TO 1000 CFM 14"D

201 TO 400 CFM 10"D

8CEILING RETURN OR EXHAUST GRILLE

55 3 57 6

10

9

119

4

1102RETURN OR EXHAUST DUCT

1. SHEET METAL PLENUM, FULL SIZE OF GRILLE NECK, M INIMUM 6" TALL W ITH SAME INTERNAL OR EXTERNAL INSULATION AS RETURN OR EXHAUST DUCT. CONNECT TO GRILLE. SEAL PLENUM AND CONNECTION TO GRILLE, SEAL CLASS A.

2. FLEXIBLE DUCT, SAME DIAMETER AS BRANCH DUCT , 3. 7 FT. MAXIMUM TOTAL LENGTH PER AIR DEVICE. STRETCH

FLEXIBLE DUCT TO AT LEAST 90% OF FULLY EXTENDED LENGTH.4. SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE W ITH MANUAL

DAMPER. DAMPER SHAFT IN HORIZONTAL. INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR TAP FITTING TO MAIN DUCT W ITH INTERNAL INSULATION. EXTENDED DAMPER SHAFT AND HANDLE W ITH STAND-OFF REQUIRED FOR EXTERNALLY INSULATED DUCTW ORK.

5. SPIN-IN TAP FITTING SIMILAR TO EXCEPT NO DAMPER.6. DUCT STRAP HANGER. ATTACH TO STRUCTURE.

6. STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE DUCT IS LONGER THAN 4 FT.

7. ROUND SHEET METAL BRANCH DUCT, SIZE AS INDICATED IN ADJACENT SCHEDULE UNLESS NOTED OTHERW ISE ON PLANS.

8. CEILING T-BAR SUPPORT (FOR LAY-IN APPLICATIONS). COORDINATE AND VERIFY T-BAR TYPE FOR COMPATIBILITY W ITH GRILLE.

9. M INIMUM CENTERLINE RADIUS EQUAL TO DUCT DIAMETER.10. FLEXIBLE DUCT ELBOW SUPPORT, INSTALLED W ITH NYLON

BANDING PER MANUFACTURER'S INSTRUCTIONS.11. A RADIUS'D SHEET METAL ELBOW MAY BE USED IN LIEU OF

A FLEXIBLE ELBOW SUPPORT W HEN CONNECTED DIRECTLY TO AIR DEVICE.

7

3

NOTES

ROUND SHEETMETAL BRANCH DUCT

BRANCH CFM RD. DUCT SIZE

0 TO 80 CFM 6"D

81 TO 120 CFM 7"D

121 TO 200 CFM 8"D

401 TO 700 CFM 12"D

701 TO 1000 CFM 14"D

201 TO 400 CFM 10"D

RETURN OR EXHAUST DUCT

8CEILING

RETURN OR EXHAUST GRILLE

14

625735

1. SHEET METAL PLENUM, FULL SIZE OF GRILLE NECK, M INIMUM 4" TALLER THAN DUCT RUNOUT SIZE, W ITH SAME INTERNAL OR EXTERNAL INSULATION AS RETURN OR EXHAUST DUCT, CONNECT TO GRILLE. SEAL PLENUM AND CONNECTION TO GRILLE, SEAL CLASS A.

2. FLEXIBLE DUCT, SAME DIAMETER AS BRANCH DUCT , 7 FT. MAXIMUM TOTAL LENGTH PER AIR DEVICE. STRETCH FLEXIBLE DUCT TO AT LEAST 90% OF FULLY EXTENDED LENGTH.

3. SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE W ITH MANUAL DAMPER. DAMPER SHAFT IN HORIZONTAL. INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR TAP FITTING TO MAIN DUCT W ITH INTERNAL INSULATION. EXTENDED DAMPER SHAFT AND HANDLE W ITH STAND-OFF REQUIRED FOR EXTERNALLY INSULATED DUCTW ORK.

4. SPIN-IN TAP FITTING SIMILAR TO EXCEPT NO DAMPER.5. DUCT STRAP HANGER. ATTACH TO STRUCTURE.6. STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE DUCT IS

LONGER THAN 4 FT.7. ROUND SHEET METAL BRANCH DUCT, SIZE AS INDICATED IN

ADJACENT SCHEDULE UNLESS NOTED OTHERW ISE ON PLANS.8. CEILING T-BAR SUPPORT (FOR LAY-IN APPLICATIONS).

COORDINATE AND VERIFY T-BAR TYPE FOR COMPATIBILITY W ITH GRILLE.

7

3

NOTES

6" M

AX

7CEILING RETURN OR EXHAUST GRILLE

3 1 3 2 3

64

5

RETURN OR EXHAUST DUCT

1. 45 DEGREE STATIC BOOT AND MANUAL DAMPER. INTEGRAL INSULATION GUARD SLEEVE REQUIRED W HEN MAIN DUCT HAS INTERNAL INSULATION. EXTENDED DAMPER SHAFT AND HANDLE W ITH STAND-OFF REQUIRED FOR EXTERNALLY INSULATED DUCTW ORK.

2. SHEET METAL DUCT, SIZE AS NOTED ON PLANS.3. DUCT STRAP HANGER.4. STATIC BOOT SIMILAR TO EXCEPT NO DAMPER.5. SHEET METAL DUCT, FULL SIZE OF GRILLE NECK SIZE. CONNECT AND SEAL

DUCT TO GRILLE, SEAL CLASS A.6. FLEXIBLE DUCT CONNECTOR.7. CEILING T-BAR SUPPORT (FOR LAY-IN APPLICATIONS). COORDINATE AND

VERIFY T-BAR TYPE FOR COMPATIBILITY W ITH GRILLE.

1

NOTES

GENERAL NOTES

NOTES

A. FIRE DAMPERS SHALL BE UL LABELED.

B. INSTALLATION OF FIRE DAMPERS AND ACCESSORIES SHALL CONFORM TO NFPA 90A, SMACNA AND MANUFACTURER'S INSTRUCTIONS.

C. DETAILS SHOW INSTALLATION OF FIRE DAMPER IN W ALL. DAMPER INSTALLATION IN FLOOR SIMILAR. COORDINATE REQUIRED ACCESS LOCATIONS.

D. INSULATE RETAINING ANGLES FOR SYSTEMS REQUIRED TO BE INSULATED.

1. FIRE DAMPER, FOLDED BLADE CURTAIN TYPE, EXCEPT AS NOTED. VERTICAL MOUNT, GRAVITY DROP; HORIZONTAL MOUNT,SPRING LOADED TO CLOSE. REFER TO SPECS FOR VELOCITY LIMITATIONS OF EACH TYPE. REFER TO DRAW INGS FOR STATIC OR DYNAMIC REQUIREMENTS.

TYPE "A" - BLADES STORED IN AIR STREAM. RECTANGULAR, ROUND OR OVAL DUCT CONNECTION.TYPE "B" - BLADES STORED OUT OF AIR STREAM. RECTANGULAR, ROUND OR OVAL DUCT CONNECTION.

2. SHEET METAL W ALL SLEEVE, SAME MATERIAL AS DUCT (EXCEPT GALVANIZED SHEET METAL FOR FIBERGLASS DUCT). SHEET METAL GAUGE PER SMACNA. USE EXTENDED HEAVY GAUGE SLEEVES W HEN INSTALLED CONDITION REQUIRES.

3. DUCT/SLEEVE CONNECTION. BREAKAW AY TYPE SHOW N. CONNECTION MAY BE RIGID TYPE IF ALLOW ED BY CODE AUTHORITY.

4. RETAINING ANGLE ALL FOUR SIDES, GAUGE PER SMACNA. 1" MIN IMUM OVERLAP OF W ALL OPENING. LONGER LEG MAY BE REQUIRED TO ATTAIN REQUIRED OVERLAP. BOLT, SCREW OR TACK W ELD TO W ALL SLEEVE. SPACING OF FASTENERS PER SMACNA.

5. DUCT ACCESS PANEL OR DOOR. REFER TO SPECIFICATIONS.

6. CEILING ACCESS PANEL IF CEILING IS NOT ACCESSIBLE.

7. RATED ACCESS PANEL NEAR FLOOR.

AIR FLOW

AIR FLOW

AIR

FL

OW

TURNING VANES

SEE FLOOR PLAN FOR SPLIT DIMENSION

MAIN SUPPLY DUCT

MANUAL VOLUME DAMPER

SUPPLY REGISTER ON BRANCH DUCT

SQUARE ELBOW SHOW N PROVIDE ROUND ELBOW W HEN SHOW N ON PLANS

AIR FLOW

AIR

FL

OW

W /4 OR 4" MIN.

MAIN SUPPLY DUCT

MANUAL VOLUME DAMPER

BRANCH DUCT

W

BRANCH DUCT TAKE-OFF

PLAN VIEW

AIR SPLIT DUCT TAKE-OFF

PLAN VIEW

THE BRANCH DUCT TAKE-OFF MAY BE USED FOR UP TO 15% OF THE MAIN DUCT CFM, AND UP TO 40% W HEN THE MAIN DUCT VELOCITY IS 1000 FPM OR LESS. THE AIR SPLIT DUCT TAKE-OFF SHALL BE USED IN ALL OTHER CASES

AIR FLOW

EQ

UIP

ME

NT

AIR FLOW

TYPICAL DUCTW ORK

TRANSITION W ITH EQUIPMENT

M OUNTED IN DUCT PLAN OR

SIDE VIEW

TYPICAL DUCTW ORK

TRANSITION PLAN OR SIDE

VIEW

NOTE:UNLESS OTHERW ISE INDICATED ON PLANS, MAXIMUM ANGLES SHOW N SHALL APPLY.

30 DEG. MAX.

AIR FLOW

15 DEG. MAX

15 DEG. MAX15 DEG. MAX.

30 DEG. MAX.

15 DEG. MAX.

CONCENTRIC TRANSITIONS UNLESSSHOW N OTHERW ISE ON PLANS

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

5/2

01

9 1

2:2

0:5

7 P

MC

:\B

IM\M

ode

l\20

19

-05

07

8-M

EP

-Ce

ntr

al_

ajg

ran

ata

@h

ea

py.c

om

.rvt

2019-05078

DTR

AJG

July 24, 2019

M003

MECHANICAL DETAILS

SCALE: NONE

AIR TERMINAL UNIT HARD DUCT CONNECTION1

SCALE: NONE

CEILING DIFFUSER DUCT CONNECTION4

SCALE: NONE

CEILING DIFFUSER DUCT CONNECTION5

SCALE: NONE

RETURN/EXHAUST GRILLE DUCT CONNECTION6

SCALE: NONE

RETURN/EXHAUST GRILLE DUCT CONNECTION7

SCALE: NONE

RETURN/EXHAUST GRILLE DUCT CONNECTION8

SCALE: NONE

FIRE DAMPER NOTES9

SCALE: NONE

SUPPLY DUCTWORK TAKE-OFFS14

SCALE: NONE

DUCTWORK TRANSITIONS16

1 2019.07.24 ADDENDUM 1

Page 18:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

1. LOCATE STRAINER W ITH BLOW -DOW N VALVE AND HOSE CONNECTION AT LOW POINT OF COIL PIPING.

2. PIPE REDUCER IF REQUIRED.3. FULL RUN-OUT PIPE SIZE.4. INSULATE FIRST 6" NEXT TO COIL.5. 18" M INIMUM LONG BRAIDED STAINLESS STEEL FLEXIBLE PIPE

CONNECTOR.6. MAXIMUM DISTANCE FROM SUPPLY AND RETURN SHUT-OFF VALVES TO

COIL IS 48".7. FACTORY ASSEMBLED PIPING PACKAGE (OPTIONAL).8. LINE SIZE START-UP/FLUSHING BYPASS.9. OPTION 2 MAY ONLY BE USED W ITH A FACTORY PIPING PACKAGE THAT

IS FACTORY MOUNTED RIGIDLY TO THE TERMINAL UNIT.10. PIPING SAME SIZE AS AUTO CONTROL VALVE OR COIL CONNECTION,

W HICHEVER IS LARGER.

HW R

HW S

COIL

6

5 23

1

7

M

NOTES

18" MIN

18" MIN

48" MAX

A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT PIPING UNLESS NOTED OTHERW ISE.

B. REFER TO AIR TERMINAL UNIT SCHEDULE FOR AUTOMATIC CONTROL VALVE SIZE.

C. REFER TO SPECIFICATIONS FOR DEVICES NOT TO BE INSULATED. INSULATED DEVICES SHALL INCLUDE EXTENDED NECKS, SHAFTS, ETC... SO THEY ARE ACCESSIBLE ABOVE THE INSULATION.

GENERAL NOTES

N.C.

8

HW R

HW S

COIL

6

4

10

1

7

4

M

6" MIN

6" MIN

48" MAX

2N.C.8

OPTION 1

4

4

5

5

OPTION 2 9

1. AUTOMATIC TW O-PORT CONTROL VALVE. NORMALLY OPEN THRU COIL.

2. 0.5" DRAIN VALVE.3. PIPE REDUCER IF COIL CONNECTION

DIFFERS FROM PIPE SIZE.4. LEAVE W IDE OPEN UNLESS REQUIRED

TO BALANCE PUMP GPM.5. COIL RECIRCULATING PUMP.

A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT PIPING UNLESS NOTED OTHERW ISE.

B. REFER TO AIR HANDLING UNIT SCHEDULE FOR AUTOMATIC CONTROL VALVE SIZE.

HW

S

HW

R

AIR

FLOW

M1

4

3

5

3

2

NOTES

GENERAL NOTES

1. AUTOMATIC TW O-PORT CONTROL VALVE. NORMALLY CLOSED THRU COIL.

2. 0.5" DRAIN VALVE.3. PIPE REDUCER IF COIL CONNECTION DIFFERS

FROM PIPE SIZE.4. DRAIN PAN.5. DRAIN PIPE, SAME SIZE AS PAN CONNECTION,

W ITH DEEP SEAL TRAP. REFER TO CONDENSATE DRAIN PIPING DETAIL.

A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT PIPING UNLESS NOTED OTHERW ISE.

B. REFER TO AIR HANDLING UNIT SCHEDULE FOR AUTOMATIC CONTROL VALVE SIZE.

CH

R

CH

S

AIR

FLOW

D

M1

3

3

2

45

NOTES

GENERAL NOTES

1. STEAM MAIN (ABOVE 30 PSIG).2. COLLECTING POCKET AND DIRT LEG SAME SIZE AS MAIN.3. LENGTH FROM INVERT OF MAIN TO DRIP PIPE, 1.5 x MAIN

DIAMETER, 8" M INIMUM.4. THERMODYNAMIC STEAM TRAP, 0.75" SIZE UNLESS

NOTED OTHERW ISE.5. CONDENSATE RETURN, FULL SIZE OF TRAP DISCHARGE,

0.75" M INIMUM.6. 0.75" BY-PASS W ITH NORMALLY CLOSED GLOBE VALVE.7. 0.75" DRAIN VALVE W ITH HOSE CONNECTION.8. 0.75" TEST VALVE AND DRAIN W ITH HOSE CONNECTION.

6

54

1

3

2

N.C.

NOTES

TD

87

4" M

IN.

.

P

5 1

74

6 3 22

7

1. PUMP W ITH FLANGED CONNECTIONS.2. SPRING HANGER.3. PRESSURE GAUGE W ITH INTERCONNECTING PIPING

AND VALVES.4. BALANCING VALVE, S IZED FOR 3 TO 5 FT. HD. W PD AT

FULL PUMP GPM. PROVIDE REDUCERS IN AND OUT. FOR PUMPS FITTED W ITH AN ADJUSTABLE FREQUENCY MOTOR CONTROLLER LEAVE THE BALANCING VALVE FULL OPEN.

5. REDUCER W HEN PUMP CONNECTION SIZE DIFFERS FROM PIPE SIZE.

6. LEAVE SPACE TO ALLOW MOTOR TO BE PULLED.7. DRAIN VALVE W ITH HOSE CONNECTION.

TYPICAL - - TYPICAL

NOTES

NOTES

"a"

1. STEAM DISTRIBUTORS. SPACING, QUANTITIES, ETC. PER EQUIPMENT DATA.

2. F&T STEAM TRAP W HEN HUMIDIFIER MOUNTED IN DUCTW ORK ABOVE CEILINGS. BUCKET TRAP W HEN MOUNTED IN EXPOSED AREAS SUCH AS MECHANICAL ROOMS.

3. MOUNT STEAM SIDE STRAINER SUCH THAT STRAIN IS ON ITS SIDE IN A HORIZONTAL POSITION.

4. AUTOMATIC MODULATING CONTROL VALVE FURNISHED BY UNIT MANUFACTURER, PROVIDE MULTIPLE VALVE W HEN SPECIFIED.

5. HEAT EXCHANGER SOLENOID VALVE (ON/OFF).6. LINE SIZE AUTOMATIC 2-POSITION CONTROL VALVE

FOR SEASONAL OR SAFETY SHUT-OFF.7. EXTEND CONDENSATE RETURN PER PLANS.8. TEMPERATURE SW ITCH.9. TUBULETS PERPENDICULAR TO AIRFLOW .10. SHUT-OFF VALVE.11. W HEN D IMENSION "A" EXCEEDS 10 LINEAR FEET,

PROVIDE DRIP LEG AND TRAP ASSEMBLY PER ABOVE.

REFER TO TYPICALSTEAM DRIP ASSEMBLY

TO CONDENSATERETURN MAIN

REFER TO BELOW FORHUMIDIFIER PIPING

STEAM SUPPLY MAIN

CONDENSATE RETURN MAIN

STEAM SUPPLY MAIN

9

18

2

756

4

410 3

11

1. PIPE REDUCER IF COIL CONNECTION SIZE DIFFERS FROM PIPE SIZE.

2. MAXIMUM D ISTANCE FROM SHUT-OFF VALVE TO COIL IS 48".3. M INIMUM 18" LONG BRAIDED STAINLESS STEEL FLEXIBLE PIPE

CONNECTOR.4. FACTORY ASSEMBLED PIPING PACKAGE (OPTIONAL).

A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT PIPING UNLESS NOTED OTHERW ISE.

B. REFER TO EQUIPMENT SCHEDULE FOR AUTOMATIC CONTROL VALVE SIZE.

C. REFER TO SPECIFICATIONS FOR DEVICES NOT TO BE INSULATED. INSULATED DEVICES SHALL INCLUDE EXTENDED NECKS, SHAFTS, ETC. SO THEY ARE ACCESSIBLE ABOVE THE INSULATION.

M

COIL

2

4

1

NOTES

GENERAL NOTES48" MAX

3

3

1. PIPE REDUCER IF COIL CONNECTION SIZE DIFFERS FROM PIPE SIZE.2. 0.75" CONDENSATE DRAIN PIPE, CONNECT TO UNIT PAN W ITH

FLEXIBLE POLYETHYLENE TUBING.3. M INIMUM 18" LONG BRAIDED STAINLESS STEEL FLEXIBLE PIPE

CONNECTOR.4. FACTORY ASSEMBLED PIPING PACKAGE (OPTIONAL).

A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT PIPING UNLESS NOTED OTHERW ISE.

B. REFER TO EQUIPMENT SCHEDULE FOR AUTOMATIC CONTROL VALVE SIZE.

M

D UNIT DRAIN PAN

COIL DRAIN PAN

COIL

2

1

4

NOTES

GENERAL NOTES3

3

1. DRAIN PIPE SAME SIZE AS UNIT DRAIN PAN CONNECTION.

2. UNIT ROOF CURB. VERIFY REQUIRED HEIGHT FOR DRAIN PIPE AND TRAP INSTALLATION. PROVIDE CURB OF ADEQUATE HEIGHT TO ATTAIN REQUIRED DIMENSION.

3. TEE W ITH CLEANOUT PLUG.4. 1" CENTERLINE - TO - CENTERLINE

DIMENSION.5. CENTERLINE - TO - CENTERLINE DIMENSION

NOT LESS THAN SUPPLY FAN T.S.P. (INCH W .G.) + 1/2 INCH..

6. CENTERLINE - TO - CENTERLINE DIMENSION NOT LESS THAN SUPPLY FAN T.S.P. (IN W .G.) + 1 INCH.

7. CENTERLINE - TO - CENTERLINE DIMENSION SHALL BE 50% OF DIMENSION FOUND IN ABOVE.

8. SPLASH BLOCK.

3

NOTES

6

BLOW -THRU UNIT

DRAW -THRU UNIT

ROOFTOP UNIT

1

3

4

5

..

TRAP

1

3

6

7

..

28

ROOFTOP UNIT

3

TRAP

28

ROOF

ROOF

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

5/2

01

9 1

2:2

1:0

9 P

MC

:\B

IM\M

ode

l\20

19

-05

07

8-M

EP

-Ce

ntr

al_

ajg

ran

ata

@h

ea

py.c

om

.rvt

2019-05078

DTR

AJG

July 24, 2019

M004

MECHANICAL DETAILS

SCALE: NONE

DUCT HEATING COIL3

SCALE: NONE

A.H. UNIT HOT WATER COIL4

SCALE: NONE

A.H. UNIT CHILLED WATER COIL5

SCALE: NONE

31 TO 125 PSIG STEAM DRIP ASSEMBLY8

SCALE: NONE

PIPE MOUNTED PUMP9

SCALE: NONE

HUMIDIFIER PIPING DETAIL6

1 2019.07.24 ADDENDUM 1

SCALE: NONE

FAN COIL UNIT PIPING-HEATING COIL1

SCALE: NONE

FAN-COIL UNIT PIPING-COOLING COIL2

SCALE: NONE

ROOFTOP UNIT DRAIN PIPING7

Page 19:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

NOTES

FAN DISCHARGE VIEW FAN INLET VIEW

1. T-FLANGE FRAME MOTORIZED ISOLATIONDAMPER.

2. ROOF SUPPORT CURBS, MIN. 14" HIGH. FLASH INTO

ROOFING SYSTEM.

3. EXHAUST STACK, SAME MATERIAL AS SYSTEMDUCTWORK. PRIME AND PAINT. SUPPORT DUCT FROM

4. FLEX CONNECTION.

5. BLIND FLANGE CONNECTION, SLOPED TO DRAINOUTLET.

6. 3/4" PVC DRAIN OUTLET TO SPILL ONTO CONCRETESPLASH BLOCK OR NEARBY ROOF DRAIN.

7. SUPPORT DUCT STACK FROM SCREEN WALL.

ROOF ROOF

EXHAUST FAN

DRAIN BAFFLE

EXHAUST FAN

LIGHTNING PROTECTION

3x WHEEL DIA.

22

6

5

3

7

4

2 1

4

2

8. INSULATE DUCT FROM EXHAUST FAN INLET TO 24"

BEYOND THE MOTORIZED DAMPER INSIDE THE BUILDING. EXTERIOR INSULATION SHALL BE JACKETED.

ADJACENT BUILDING WALL.

FASTENCURB

12" HIGHCURB.

FASTEN CURB TODECK

INSULATION

FASTEN TONAILER

METALDECK

TODECK.

STRUCTURAL FRAMING BYG.C.

NEWDUCT

INSULATE DUCT TO BELOWDECK

NEW FLASHING. SEALWATER-TIGHT AROUND DUCTPENETRATION.

PATCH INSULATION & ROOFINGTO SEAL WATERTIGHT FASTEN

CURB

12" HIGHCURB.

FASTEN CURB TODECK

INSULATION

FASTEN TONAILER

CONCRETEDECK

TODECK.

STRUCTURAL FRAMING BYG.C.

PIPING

PIPE INSULATION, REFER TOSPECIFICATION.

NEW FLASHING. SEALWATER-TIGHT AROUND DUCTPENETRATION.

PATCH INSULATION & ROOFINGTO SEAL WATERTIGHT

NOTES

RETURN OREXHAUST DUCT

FROM GENERAL RETURN/EXHAUST

1. CONICAL TEE FITTING.2. ROUND SHEET METAL BRANCH DUCT, SAME SIZE AS AIR

CONTROL VALVE INLET SIZE UNLESS NOTED OTHERW ISE.3. RETURN OR EXHAUST AIR CONTROL VALVE.4. STRAP HANGER. ATTACH TO STRUCTURE.5. TRANSITION W HEN REQUIRED.6. M INIMUM FOUR STRAP HANGERS FOR UNIT (CORNER POINTS).

ATTACH TO STRUCTURE.7. 6" W IDE 22 GAUGE DRAW BAND W ITH 5/16" THICK x 3/4" W IDE

DUCTMATE DM 440 GASKET TAPE (BUTYL RUBBER TAPE) INSTALLED PER VALVE MANUFACTURER'S INSTRUCTIONS.

8. SOUND ATTENUATOR, IF REQUIRED.

1

4 62 4 7 8

5 7 3 6

INTERNAL D IVIDER TOEQUALIZE VELOCITY ACROSS LOUVER

RETURN DUCT R ISER

MIDW AY IN LOUVER AND DUCT

FLOOR

NOTES

MAIN SUPPLY DUCT

TO AIR DEVICES

1. CONICAL TEE FITTING.2. ROUND SHEET METAL BRANCH DUCT, SAME SIZE AS AIR CONTROL VALVE INLET SIZE

UNLESS NOTED OTHERW ISE.3. HARD DUCT CONNECTION TO AIR TERMINAL UNIT. FLEX CONNECTION NOT PERMITTED.4. SUPPLY AIR CONTROL VALVE. EXTERNALLY INSULATE TO PREVENT SW EATING.5. STRAP HANGER. ATTACH TO STRUCTURE.6. TRANSITION W HEN REQUIRED.7. HOT W ATER REHEAT COIL. REFER TO REHEAT COIL PIPING DETAIL. INSULATE COIL.8. 6" W IDE 22 GAUGE DRAW BAND W ITH 5/16" THICK x 3/4" W IDE DUCTMATE DM 440

GASKET TAPE (BUTYL RUBBER TAPE) INSTALLED PER VALVE MANUFACTURER 'S INSTRUCTIONS.

9. SOUND ATTENUATOR, IF REQUIRED.10. PROVIDE 6"x6" LATCH ACCESS PANEL IN BOTTOM OF TRANSITION. REFER TO

SPECIFICATIONS.11. M INIMUM FOUR STRAP HANGERS FOR UNIT (CORNER POINTS). ATTACH TO

STRUCTURE.

1

5112 5 6 93

71084

8

BRANCH DUCT

PLAN VIEW

W

W /4 OR 4" M IN.

PROVID E MANUAL VOLUME DAMPER AT EACH BRANCH DUCT

MAIN EXHAUST OR RETURN AIR FLOW

45 DEG.

AIR

FLO

W

AIR FLOWLAG SCREW

W OOD NAILER

4"x4"x1/4" STEEL PLATE

INSULATION

ROOFING

CONCRETE DECK

1

23

4

1. PROVIDE COUNTER-FLASHING.2. HEAVY GAUGE CONTINUOUS SUPPORT

EXTENDS 6" BEYOND LAST EQUIPMENT LEG. SCREW ATTACHMENT TO DECK.

3. M INIMUM 12 INCHES.4. EXPANSION LAGS TO DECK.5. 18 / 24 / 36 INCH H IGH INSULATED STEEL CURB.

.

NOTES

5

1TYPE "A" -

DUCT

3" MIN3" MIN

FIRE RATED W ALL OR PARTITION

3

44

2

5

3

6

DUCT EXTENSION AT TOP OF DAMPER

DUCT

1TYPE "B" -

FIRE RATED W ALL OR PARTITION

5

3

6

3" MIN3" MIN

3

4 42

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

5/2

01

9 1

2:2

1:1

7 P

MC

:\B

IM\M

ode

l\20

19

-05

07

8-M

EP

-Ce

ntr

al_

ajg

ran

ata

@h

ea

py.c

om

.rvt

2019-05078

DTR

AJG

July 24, 2019

M005

MECHANICAL DETAILS

1 2019.07.24 ADDENDUM 1

SCALE: NONE

RETURN/EXHAUST AIR CONTROL VALVE DUCT CONNECTION1

SCALE: NONE

LOW RETURN AIR GRILLE3

SCALE: NONE

SUPPLY AIR CONTROL VALVE DUCT CONNECTION2

SCALE: NONE

EXHAUST OR RETURN BRANCH DUCTWORK4

SCALE: NONE

ROOF EQUIPMENT SUPPORT5

SCALE: NONE

FIRE DAMPER TYPE "A"6

SCALE: NONE

FIRE DAMPER TYPE "B"7

SCALE: NONE

UTILITY SET FAN8

SCALE: NONE

DUCT UTILITY CURB10

SCALE: NONE

PIPE UTILITY CURB11

Page 20:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

ROOM PRESSURECONTROLLER

FLOW COMMAND TO RETURN

FLOW FEEDBACK FROM RETURN

FLOW COMMAND TO SUPPLY

FLOW FEEDBACK FROM SUPPLY

H

C

M

HWS

HWR

SUPPLY AIR

T

DISCHARGE AIR

TEMPERATURE

TERMINAL UNIT

CONTROLLER

M

REHEAT COILVALVE

H L

AIRFLOW

SENSOR

SUPPLY AIR FROM

AIR HANDLER

24 VAC

TERMINAL UNIT

CONTROLLER

24 VAC

24 VAC

24 VAC24 VAC

M

RETURN

24 VAC

NETWORK CABLE

NETWORK CABLE

SPACE SENSOR WITH

TEMPERATURE ADJUSTMENT,

OCCUPANCY OVERRIDE,

AND LCD DISPLAY

T

RPS

RPM

ROOM

PRESSUREMONITOR

PRESSURE

SENSOR

DS

DOOR

SWITCH

NETWORK CABLE

NETWORK CABLE

AIRFLOW

(+)

SA-2

SA-1

SA-3

SA-4

SA-5

SA-6

OS OCCUPANCY

SENSOR

(WHERE APPLICABLE)

(NON H.D. COMPOUNDING + ANTE ROOM)

(BASIS OF DESIGN: PRICE CRITICAL CONTROLS.REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS)

VENTURI AIR VALVE

H

HUMIDITY SENSOR LOCATED BEHIND THE RETURN GRILLES.HUMIDITY SENSORS SHALL BE AVERAGING BETWEEN THE FOUR ROOMS.

VENTURI AIR VALVE

HUMIDIFIER IN

DUCTWORK

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

5/2

01

9 1

2:2

1:2

0 P

MC

:\B

IM\M

ode

l\20

19

-05

07

8-M

EP

-Ce

ntr

al_

ajg

ran

ata

@h

ea

py.c

om

.rvt

2019-05078

DTR

AJG

July 24, 2019

M007

MECHANICALCONTROL

SCHEMATICS

1 2019.07.24 ADDENDUM 1

SCALE: NONE

CRITICAL CONTROL SCHEMATIC1

Page 21:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

AIR HANDLING UNIT AHU - 24 POINTS LIST SCHEDULE

POINT NO.

TYPE

NOTES

POINT NAME

ALARM

AH-01 AH-02 AH-03 AH-04 AH-05 AH-06 AH-07 AH-08 AH-09 AH-10

AI

RE

TU

RN

AIR

TE

MP

ER

AT

UR

E

AH-11

HIG

H/L

OW

AIR HANDLING UNIT AHU - 24 ATC DIAGRAM

AI

NOTES:1. CURRENT SENSOR.2. COORDINATE W ITH VFD SUPPLIER.3. COORDINATE SMOKE DETECTION ALARM SIGNAL FROM FIRE ALARM SYSTEM. SMOKE DETECTOR BY DIV 26/28.4. IN ADDITION TO BEING A (BI) SAFETIES SHALL BE W IRED INTO THE FAN STARTERS/VFD(S) STARTER CIRCUIT SUCH THAT THE SAFETY SHALL FUNCTION W HETHER THE SELECTOR SW ITCH IS IN THE "HAND" OR "AUTOMATIC" POSITION.5. COORDINATE INTER-FACE CARD W ITH VFD SUPPLIER.

AI

HIG

H/L

OW

AH-12 AH-13 AH-14 AH-15 AH-16 AH-17

HIG

H/L

OW

AH-18

AI

HIG

H/L

OW

SCALE: NONE

FINAL FILTER

T

AH-28

SUPPLY AIR TEMPERATURE

AH-29

SAFETY SHUTDOW N

SP

AH-30

DUCT STATIC PRESSURE

SUPPLY AIR

SUPPLY FAN

AH-23

AIR FLOW STATION

VFD

AH-25

START/STOP

AH-26

DRIVE SPEED

AH-27

FAN FAULT

AH-24

FAN STATUS

COOLING COIL

AH-22

DRAIN PAN OVERFLOW

T

AH-20

H.C.L.A.T.

AH-19

FREEZE-STAT

PRE-HEAT COIL W L

AH-14

MIXED AIR TEMPERATURE

PR E- FILTER

AH-13

FILTER STATUS

OU TSIDE AIR

DPHL

AH-28

FILTER STATUS

DPHL

AH-12

AIR FLOW STATION

OUTSIDE AIR DAMPER

AH-33

AH-11

MIXED AIR DAMPER

RETURN AIR DAMPER

PSL

SAFETY SHUT-DOW N

AH-05

FIRE ALARM SMOKE

DETECTION

AH-04

H

RETURN AIR HUMIDITY

AH-02

T

AH-01

RETURN AIR TEMPERATURE

RETURN AIRRELIEF AIR

TO SERVICE VESTIBULE

AH-19 AH-20 AH-21 AH-22 AH-23 AH-24 AH-25 AH-26 AH-27 AH-28 AH-29

RE

TU

RN

AIR

HU

MID

ITY

AI BI

ON

TR

IPR

ETU

RN

AIR

F.A

. SM

OK

E

DE

TE

CTI

ON

3,4

BI

LOW

PR

ES

S.

SY

ST

EM

ALA

RM

4

RE

TU

RN

FA

N -

AIR

FLO

W

ME

AS

UR

ING

STA

TIO

N

BI

AD

JUS

TA

BLE

H

IGH

PR

ES

S.

PR

E -

FIL

TE

R S

TA

TU

S

RE

TU

RN

FA

N D

RIV

E S

PE

ED

AO

MIX

ED

AIR

DA

MP

ER

S

OU

TSID

E A

IR -

AIR

FLO

W

ME

AS

UR

ING

STA

TIO

N

MIX

ED

AIR

TE

MP

ER

AT

UR

E

AO BI

1

BI

4

FR

EE

ZE

-ST

AT

BOAO BI

ON

TR

IP

4

DR

AIN

PA

N O

VE

RF

LOW

SU

PP

LY F

AN

-A

IRFL

OW

M

EA

SU

RIN

G S

TATI

ON

BI

1

AI

HIG

H/L

OW

SU

PP

LY D

UC

T S

TA

TIC

PR

ES

SU

RE

UV

SY

ST

EM

-C

C

T T

LL

AFMSAFMS

HU

MID

IFIE

R S

HU

T-O

FF

VA

LVE

AH-33AH-31 AH-32AH-30

BI

PR

ES

SU

RE

SA

FE

TY

SH

UT

-DO

WN

RETURN FAN

AH-06

AIR FLOW STATION

AFMS

VFD AH-07

FAN STATUSAH-08

START/STOP

AH-09

DRIVE SPEED

AH-10

FAN FAULT

AH-31

RELIEF AIR DAMPER

RELIEF AIR DAMPER

AH-34

RE

LIE

F A

IR D

AM

PE

R

AOAI

HIG

H/L

OW

ON

FA

ILU

RE

BI

1

RE

TU

RN

FA

N S

TA

TU

S

RE

TU

RN

FA

N S

TA

RT

/ST

OP

BO

2

AO

RE

TU

RN

FA

N F

AU

LT

BI

ON

TR

IP

2

AI

HIG

H/L

OW

AI

HIG

H/L

OW

ON

FA

ILU

RE

BO

ON

TR

IP

BI

ON

FA

ILU

RE

2

AO

2

ON

TR

IP

AI

HIG

H/L

OW

BI

4

HIG

H P

RE

SS

. S

YS

TEM

ALA

RM

BO BO

H

L

L

H

AH-34

HUMIDIFIER

M

AH-35

HUMIDIFIER CONTROL VALVE

HUMIDIFIER ISOLATION VALVE

M

AH-35

AO

HU

MID

IFIE

R C

ON

TR

OL

VA

LVE

UV

M

AH-21

CHILLED W ATER CONTROL VALVE

MT

MS

AH-17

PUMP STATUS

AH-18

HOT W ATER PUMP START/STOP

AH-16

HOT W ATER CONTROL VALVE

AH-15

RETURN W ATER TEMPERATURE

BO

AH-36

UV

SY

ST

EM

-F

F

AH -36

UV

PSH

H

L

PR

ES

SU

RE

SA

FE

TY

SH

UT

-DO

WN

HO

T W

ATE

R C

OIL

RE

TU

RN

W

AT

ER

TE

MP

ER

AT

UR

E

HO

T W

AT

ER

CO

IL C

ON

TR

OL

VA

LVE

HO

T W

AT

ER

CO

IL P

UM

P S

TA

TU

S

HO

T W

ATE

R C

OIL

PU

MP

S

TAR

T/S

TOP

PR

EH

EA

T C

OIL

-LE

AV

ING

AIR

TE

MP

ER

AT

UR

E

CH

ILLE

D W

ATE

R C

OIL

CO

NT

RO

L V

ALV

E

SU

PP

LY F

AN

-S

TA

TU

S

SU

PP

LY F

AN

-S

TA

RT

/ST

OP

SU

PP

LY F

AN

-D

RIV

E S

PE

ED

SU

PP

LY F

AN

-F

AU

LT

SU

PP

LY A

IR -

TE

MP

ER

AT

UR

E

AH -32

RETURN FAN VFD INTER -

FACE

AH-37

SUPPLY FAN VFD INTER-FACE

AH-37

INTER-FACE

SU

PP

LY F

AN

VF

D IN

TE

R-F

AC

E

5

INTER-FACE

RE

TU

RN

FA

N V

FD

INT

ER

-FA

CE

5

SD

M

M

M

2 2

AI

AO

BI

BO

PI

OAT

MAT

RAT

SAT

CCAT

HCAT

OAHY

RAH

SAH

NC

NO

L

H

C

XX-01

LEGEND-AUTOMATIC

TEMPERATURE CONTROLS

CONTROL POINT - SEE POINTS SCHEDULE

ANALOG INPUT

ANALOG OUTPUT

BINARY INPUT

BINARY OUTPUT

PULSED INPUT

OUTSIDE AIR TEMPERATURE

MIXED AIR TEMPERATURE

RETURN AIR TEMPERATURE

SUPPLY AIR TEMPERATURE

COOLING COIL LEAVING AIR TEMPERATURE

HEATING COIL LEAVING AIR TEMPERATURE

OUTSIDE AIR HUMID ITY

RETURN AIR HUMIDITY

SUPPLY AIR HUMIDITY

NORMALLY CLOSED (CLOSES ON LOSS OF POW ER)

NORMALLY OPEN (OPENS ON LOSS OF POW ER)

LOW

HIGH

COMMON

2-W AY AUTOMATIC 2-POSITION CONTROL VALVE

3-W AY AUTOMATIC 2-POSITION CONTROL VALVE

2-W AY AUTOMATIC MODULATING CONTROL VALVE

3-W AY AUTOMATIC MODULATING CONTROL VALVE

DIFFERENTIAL PRESSURE SENSOR

DIFFERENTIAL PRESSURE SW ITCH

CARBON DIOXIDE SENSOR

CARBON MONOXIDE SENSOR

CURRENT SENSOR TRANSMITTER

ELECTRONIC TO PNEUMATIC TRANSDUCER

FLOW METER TRANSMITTER

HUMIDITY SENSOR

LEVEL CONTROLLER

LEVEL TRANSMITTER

PRESSURE SENSOR

STATIC PRESSURE SENSOR

TEMPERATURE SENSOR

W ATER FLOW SENSOR

W ATER LEVEL SENSOR

CURRENT SW ITCH

END SW ITCH

FLOW SW ITCH

HUMIDISTAT

OCCUPANCY SENSOR

PRESSURE SW ITCH, HIGH LIMIT

PRESSURE SW ITCH, LOW LIMIT

TEMPERATURE LOW LIMIT (FREEZE STAT)

ROOM THERMOSTAT

AIR FLOW MEASURING STATION

VARIABLE FREQUENCY DRIVE (ADJUSTABLE FREQUENCY MOTOR CONTROLLER)

MOTOR STARTER

CONTACTOR

LOCAL TEMPERATURE CONTROL PANEL

PRESSURE SAFETY - H IGH

PRESSURE SAFETY - LOW

SMOKE DETECTOR

DAMPER OR VALVE ACTUATOR - MODULATING

DAMPER OR VALVE ACTUATOR - 2-POSITION

RELAY

UVGI LIGHT

PUMP

FAN

COOLING COIL

HEATING COIL

HUMIDIFIER

FILTER

ENERGY RECOVERY W HEEL

OPPOSED BLADE CONTROL DAMPER

PARALLEL BLADE CONTROL DAMPER

SMOKE DAMPER

MIN OA / ECON DAMPER

DX COIL

W ALL MOUNTED DEVICE

DUCT INSERTION DEVICE

PIPE INSERTION OR IMMERSION DEVICE W ITH W ELL

AVERAGING SENSOR OR DEVICE

OUTDOOR SENSOR OR DEVICE, SHIELDED

GENERAL NOTES-

AUTOMATIC TEMPERATURE CONTROLS

A A COMPLETE SYSTEM OF AUTOMATIC TEMPERATURE CONTROLS SHALL BE INSTALLED AS REQUIRED TO ACCOMPLISH THE SEQUENCE OF CONTROL FOR VARIOUS ITEMS OF EQUIPMENT AND SYSTEMS DESCRIBED HEREINAFTER. THE SYSTEM SHALL BE A DIRECT DIGITAL CONTROL SYSTEM UTILIZING ELECTRIC OR PNEUMATIC ACTUATION AS DEFINED IN THE SPECIFICATIONS.

B THE CONTROL DIAGRAMS AND INFORMATION CONTAINED W ITHIN ARE TO SHOW DESIGN INTENT. IT IS THE CONTROL SYSTEM SUPPLIERS RESPONSIBILITY TO DEVELOP DETAILED AND COMPLETE CONTROL DIAGRAMS AND SHOP DRAW INGS TO ACCOMPLISH THE SPECIFIED SEQUENCES.

C THE POINTS LIST IS SHOW N AS AN AID TO THE CONTRACTOR INDICATING THE MINIMUM POINTS REQUIRED FOR CONTROL, AND MONITORING. ALL INPUT AND OUTPUT POINTS, AND THEIR REQUIRED INTERFACE AND ACCESSORY HARDW ARE, SHALL BE PROVIDED FOR A COMPLETE AND FUNCTIONAL CONTROL SYSTEM. IF OR W HEN ADDITIONAL POINTS ARE REQUIRED TO ACCOMPLISH THE SEQUENCES OF CONTROL SPECIFIED , THESE POINTS, ALONG W ITH ADDITIONAL DIRECT DIGITAL CONTROL PANE(S) (IF REQUIRED), SHALL ALSO BE PROVIDED.

D BULB W ELLS FOR TEMPERATURE SENSING AS INDICATED SHALL BE PROVIDED BY THE HVAC CONTRACT. PIPING W ORK SHALL INCLUDE PROPERLY SIZED W ELDOLET OR THREADOLET FITTINGS PLACED AS DIRECTED BY THE CONTROL SYSTEM SUPPLIER.

E ELECTRICAL W ORK INCLUDES A POW ER SOURCE TO THE MOTOR STARTERS. PROVIDE ALL HVAC POW ER SOURCES REQUIRED BEYOND THESE STARTERS OR BEYOND SOURCES EXPLICITLY SHOW N ON THE ELECTRICAL DRAW INGS. THIS SHALL INCLUDE BUT NOT BE LIMITED TO W IR ING, CONDUIT, TRANSFORMERS, RELAYS AND FUSES.

M

M

M

M

DPHL

DPH

L

C

CO

CS

EPT

FM

H

LC

LT

P

SP

T

W F

W L

CS

ES

FS

H

OS

HLP

LLP

TLL

T

LEGEND-AUTOMATIC

TEMPERATURE CONTROLS

AFMS

VFD

MS

CON

TCP

SD

M

M

SD

X

X

X

X

X

X

X

X

X

X

R

M M

MINECON

R

UV

PSH

PSL

SP

AH-03

H

L

HIG

H/L

OW

RE

TU

RN

DU

CT

ST

AT

IC P

RE

SS

UR

E

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

5/2

01

9 1

2:2

1:3

1 P

MC

:\B

IM\M

ode

l\20

19

-05

07

8-M

EP

-Ce

ntr

al_

ajg

ran

ata

@h

ea

py.c

om

.rvt

2019-05078

DTR

AJG

July 24, 2019

M008

MECHANICALCONTROL

SCHEMATICS

1 2019.07.24 ADDENDUM 1

SCALE: NONE

AIR HANDLING UNIT 24 ATC DIAGRAM1

Page 22:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

PTD

SD

T

T

T

T

T

T

T

T

2

M 301

1

1

1

1

1

1

1

3

3

1

3

3

3

3

3

3

2

2

2

2

2

2

2

2

2

2

2

2

2

222

2

2

2

2

2

2

2

4

4

4

4

4

4

4

4

5

5

5

5

5

5

5

5

5

6

6 8

8

8

7

7

7

7

7

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

5/2

01

9 1

2:2

1:4

4 P

MC

:\B

IM\M

ode

l\20

19

-05

07

8-M

EP

-Ce

ntr

al_

ajg

ran

ata

@h

ea

py.c

om

.rvt

2019-05078

DTR

AJG

July 24, 2019

M101

PARTIAL FIRST FLOORPLAN - DEMOLITION

1 2019.07.24 ADDENDUM 1

SCALE: 1/4" = 1'-0"

PARTIAL FIRST FLOOR PLAN - DEMOLITION1

NOTES

1. REMOVE EXISTING FAN COIL UNIT AND ALL ASSOCIATED DUCTW ORK, PIPING,AND CONTROL W IR ING.

2. REMOVE EXISTING AIR DEVICE AND ASSOCIATED DUCTW ORK AS INDICATED.

3. REMOVE EXISTING THERMOSTAT AND ALL ASSIOCIATED CONTROL W IRING.

4. REMOVE EXISITING PIPING AS INDICATED. CAP AND SEAL W ATERTIGHT.

5. REMOVE EXISTING DUCTW ORK AS INDICATED. CAP AND SEAL AIRTIGHT.

6. EXISTING DUCTW ORK TO REMAIN.

7. EXISTING PIPING TO REMAIN.

8. EXISTING AIR DEVICE TO REMAIN. REFER TO NEW W ORK FOR REBALANCING.

Page 23:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

1314

LOCK.

38

PTD

SD

T

T

T

T

T

T

T

T

T

T

2

M 301

R

18x10

18x8

20x12

16x6

24x14

12x6

24x10

10ø

10ø

10x10

14x10

8øA1

150 CFM

8øA1

150 CFM

8øA1

150 CFM

10øA1

235 CFM

8øA1

150 CFM

6øA1

50 CFM

24x1250 CFM

J1

6øA1

100 CFM

24x12150 CFM

J1

3" - CHS

3" - HW S1.25" - CHR

8øA1

150 CFM

24x12100 CFM

J1

14x14

24-03A

24-03B24-04B24-04A

24-03A

24-02A

24-01A

24-01B

24-02B

18x8

22x6

24x8

1-05

1-04B

1-04A

1-03

1-01

1-02

1

4

3

2

TYP.5

5

5

5

6

6

6

6

6

235

560

560

650

400

7

8

8

8

8

9

9

9

9

10

14x10

8øA1

225 CFM

55

1095

10215

10110

12x8

8x4

10105

8x4

24x6

24x8

10øA1

235 CFM

10øA1

230 CFM

24x12225 CFM

J1

14x1

0

10x8

12x12

18x8 20x8

16x812x4

10x6

12 10012100

1275

24x6

11

14x6

18x8

14x10

12x12

18x8

1-01

1537A

BULK

STORAGE

1547

ADA STAFF

TOILET

1546OFC

1545MGR. OFC

1544

ORDER

ENTRY

OFC

1543IV RM

1542AHVAC

1541CHEMO RM

1542ANTI RM

1540

HD

NON-STERILE

1539NARC RM

1538POP

1535CORR.

1533JAN

1537

ORDER

ENTRY

1-02

1-03

24x12300 CFM

J1

24x12300 CFM

J1

1-04B

1-04A

6øA1

100 CFM24x12

100 CFM

J1

24x12120 CFM

J1 6øA1

120 CFM

10x8

24x1

0

1-05

12x1285 CFM

K1

24x12200 CFM

K1

10øA2

380 CFM10øA2

380 CFM10øA2

380 CFM10øA2

380 CFM

24-01A 8øA2

255 CFM

8øA2

255 CFM

24-02A

8øA2

200 CFM

24-04A

10øA2

300 CFM

24-03A

20x12 14x14

13 13

COURTYARD

0.75

" -

D

0.75" - D 1" - D 1.25" - D

1.25

" -

D

0.75" - D

40x12

44x1

0

1.5" -

CHS

1" -HW

S

1.5" -

CHR

1" -HW

R

3" - CHS2" - HW S

1.5" - CHR

1.5" - HW R

3" - CHS3" - HW S

2" - CHR

1.5" - HW R

1.25" - CHS

0.75" - HW S1.25" - CHR

0.75" - HW R

0.75" - HW R

1.25

" -

HW

R

1 .25" - HW S

1.5" - CHR

1070

8x8

2.5" - HW R2.5" - HW S

0.75" - LPC

0.75" - LPS3" - CHR3" - CHS14

18x10

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

5/2

01

9 1

2:2

2:0

9 P

MC

:\B

IM\M

ode

l\20

19

-05

07

8-M

EP

-Ce

ntr

al_

ajg

ran

ata

@h

ea

py.c

om

.rvt

2019-05078

DTR

AJG

July 24, 2019

M201

PARTIAL FIRST FLOORPLAN - NEW W ORK

1 2019.07.24 ADDENDUM 1

SCALE: 1/4" = 1'-0"

PARTIAL FIRST FLOOR PLAN - NEW WORK1

1. PROVIDE W ALL MOUNTED ROOM PRESSURE MONITOR ON W ALL, PROVIDE LABEL THAT THIS SERVES ANTE ROOM. MONITOR SHALL BE SIEMENS RPM OR APPROVED EQUAL PER SPECIFICATIONS. THRU-THE-W ALL ROOM PRESSURE SENSORS SHALL BE MOUNTED ABOVE THE DOOR. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. ROOM PRESSURE CONTROLS SHALL BE PROVIDED BY ATC TO MAINTAIN THE ANTE ROOM AT A MINIMUM OF +0.02" POSITIVE W ITH RESPECT TO PHARMACY.

2. PROVIDE W ALL MOUNTED ROOM PRESSURE MONITOR ON W ALL, PROVIDE LABEL THAT THIS SERVES IV ROOM. MONITOR SHALL BE SIEMENS RPM OR APPROVED EQUAL PER SPECIFICATIONS. THRU-THE-W ALL ROOM PRESSURE SENSORS SHALL BE MOUNTED ABOVE THE DOOR. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. ROOM PRESSURE CONTROLS SHALL BE PROVIDED BY ATC TO MAINTAIN THE IV ROOM AT A MINIMUM OF +0.02" TO +0.05" POSITIVE W ITH RESPECT TO ANTE ROOM..

3. PPROVIDE W ALL MOUNTED ROOM PRESSURE MONITOR PROVIDE LABEL THAT THIS SERVES CHEMO ROOM. MONITOR SHALL BE SIEMENS RPM OR APPROVED EQUAL PER SPECIFICATIONS. THRU-THE-W ALL ROOM PRESSURE SENSORS SHALL BE MOUNTED ABOVE THE DOOR. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. ROOM PRESSURE CONTROLS SHALL BE PROVIDED BY ATC TO MAINTAIN THE CHEMO ROOM AT A MINIMUM OF -0.01" TO -0.03" NEGATIVE W ITH RESPECT TO ANTE ROOM.

4. PROVIDE W ALL MOUNTED ROOM PRESSURE MONITOR PROVIDE LABEL THAT THIS SERVES NON STERILE ROOM. MONITOR SHALL BE SIEMENS RPM OR APPROVED EQUAL PER SPECIFICATIONS. THRU-THE-W ALL ROOM PRESSURE SENSORS SHALL BE MOUNTED ABOVE THE DOOR. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. ROOM PRESSURE CONTROLS SHALL BE PROVIDED BY ATC TO MAINTAIN THE HD NON STERILE ROOM AT A MINIMUM OF -0.01" TO -0.03" NEGATIVE W ITH RESPECT TO PHARMACY ROOM.

5. CEILING MOUNTED SUPPLY DIFFUSERS SHALL BE FURNISHED BY OTHERS, INSTALLED BY H.C. H.C. SHALL CONNECT AIR DEVICES INTO SUPPLY DUCT SHOW N FROM AIR VALVE AS INDICATED. BALANCE TO CFM INDICATED.

6. LOW EXHAUST/RETURN GRILLE TO BE FURNISHED BY OTHERS, INSTALLED BY H.C. H.C. SHALL EXTEND DUCTW ORK AS NEEDED IN CHASE TO CONNECT TO LOW GRILLE. BALANCE TO CFM INDICATED..

7. DROP 8" EXHAUST DUCT AND CONNECT TO MIC SINGLE HOOD. PER MANUFACTURER, DROP 4" DUCT TO 4-6" PERPENDICULAR FROM THE CEILING AND THE EXHAUST SIDE OF THE MIC FIELD INSTALLATION KIT W ILL ATTACH VIA A FLEX HOSE. BALANCE VALVES (INTAKE AND EXHAUST) AS REQUIRED TO ACHIEVE THE PROPER FLOW , REFER TO MANUFACTURER'S LITERATURE FOR MORE INFORMATION.

8. ROOM SHALL BE SEALED UP TIGHTLY. CAULK ALL PENETRATIONS INTO AND OUT OF W ALLS AND CEILINGS. PROVIDE GASKETED ACCESS DOORS AS REQUIRED IN CEILINGS TO ACCESS JUNCTION BOXES, EQUIPMENT, VALVES, ETC. COORDINATE W ITH OW NER.

9. KEEP ALL NEW EQUIPMENT, VALVES, ETC. ABOVE LAY-IN CEILING AS INDICATED TO REDUCE NUMBER OF ACCESS PANELS REQUIRED IN THE COMPOUNDING ROOMS.

10. OUTSIDE AIR DUCT TO CONNECT TO RETURN DUCT. BALANCE TO CFM INDICATED.

11. CONDENSATE DRAIN SHALL DISCHARGE TO MOP SINK IN JANITOR'S CLOSET.

12. RE-BALANCE EXISTING AIR DEVICE TO CFM INDICATED.

13. DUCT SHALL RISE UP EXTERIOR BUILDING W ALL TO ROOF ABOVE. REFER TO M301 FOR CONTINUATION.

14. PIPING RISE TO AIR HANDLER ON ROOF ABOVE. REFER TO SHEET M301 FOR CONTINUATION.

NOTES

A. ELECTRONIC COORDINATION DRAW INGS ARE REQUIRED AND MUST BE SUBMITTED TO THE ENGINEER FOR REVIEW PRIOR TO BEGINNING NEW W ORK. REFER TO 23 05 01.

GENERAL NOTES

Page 24:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

5

8

13

14

20x14

14x14AHU-24

14ø

20x1

4

14ø EF-92

6' - 0"

6' - 0"

5' -

0"

EUH-1

P-24

1

2

3

45

6

77

12

10

10ø

9

TYP.11

8

EX.EF

COURTYARD

13

2.5" - HW S

0.75" - LPS0.75" - LPC

3" - CHS

2.5" - HW R

3" - CHR

Level 10' - 0"

Level 29' - 9"

24x14

8x8

8x8

24-04B 24-03B 24-03A24-02B

24-01A

24-04A24-02A

24-03A

18x10

14x14

IV ROOM

24x1

4

8' -

0"

24-01B

12x1

0

TYP.1

TYP.2

TYP.3

4

1

2

3

4

5 6 7 8 9

10

11

12

1. RETURN FAN SECTION.2. RELIEF AIR DAMPER.3. OUTSIDE AIR DAMPER W ITH HOOD.4. AIR BLENDER SECTION.5. SIDE LOADING FILTER SECTION.6. HOT W ATER COIL SECTION.7. HUMIDIFIER SECTION.8. CHILLED W ATER COIL SECTION.9. ACCESS SECTION.10. SUPPLY FAN SECTION.11. SIDE LOADING FILTER SECTION.12. SERVICE CORRIDOR SECTION.13. ELECTRIC UNIT HEATER LOCATION. REFER TO ROOF PLAN14. COIL CIRCULATING PUMP (P-24) LOCATION. REFER TO ROOF PLAN.15. RELIEF LOUVER W ITH BACKDRAFT DAMPER.16. ACCESS DOOR.17. RETURN DUCT CONNECTION.18. SUPPLY DUCT CONNECTION.19. HEAT TRACE PANEL LOCATION. REFER TO ROOF PLAN.20. UVGI CONTROL PANEL LOCATION. REFER TO ROOF PLAN.

NOTES

1314

1516

TYP.1718

19

20

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

5/2

01

9 1

2:2

2:1

6 P

MC

:\B

IM\M

ode

l\20

19

-05

07

8-M

EP

-Ce

ntr

al_

ajg

ran

ata

@h

ea

py.c

om

.rvt

2019-05078

DTR

AJG

July 24, 2019

M301

HVAC ROOF

1 2019.07.24 ADDENDUM 1

SCALE: 1/8" = 1'-0"

HVAC ROOF PLAN1

NOTES - HVAC ROOF PLAN

1. AIR HANDLING UNIT MOUNTED ON STEEL STRUCTURE. COORDINATE EXACT LOCATION W ITH STRUCTURAL DRAW INGS. OUTSIDE AIR OPENING MUST BE MINIMUM 25'-0" AW AY FROM ANY EXHAUST OR VENTS.

2. PIPING RISES THROUGH ROOF FROM FLOOR BELOW . ALL EXTERIOR PIPING SHALL BE HEAT TRACED. PIPING RISES INTO AHU SERVICE VESTIBULE THROUGH THE FLOOR OF THE UNIT..

3. DASHED LINES INDICATE 25'-0" CLEARANCE FROM EXHAUST FANS ON THE ROOF. DO NOT LOCATE OUTSIDE AIR OPENING FROM AIR HANDLER INSIDE THIS CIRCLE.

4. MECHANICAL SERVICE PLATFORM. REFER TO STRCTURAL AND ARCHITECTURAL DRAW INGS.

5. SUPPLY DUCT SHALL DROP THROUGH SERVICE PLATFORM GRATING SO A 3'-0" W IDE PATH CAN BE MAINTAINED TO GET PAST THE DUCT.

6. PROVIDE EXHAUST STACK, REFER TO UTILITY SET FAN DETAIL.

7. DUCTW ORK DROPS ALONG THE EXTERIOR W ALL INTO THE COURTYARD BELOW . REFER TO SHEET M201 FOR CONTINUATION.

8. ACCESS LADDER TO SERVICE PLATFORM.

9. ROOF ACCESS DOOR, REFER TO ARCHITECTURAL PLANS.

10. RE-W ORK EXISTING 10" ROUND DUCTW ORK TO AVOID CONFLICT W ITH NEW DUCTW ORK. RE-INSULATE TO MATCH EXISTING.

11. DUCT SUPPORT CURBS. SPACE PER MANUFACTURER 'S RECOMMENDATIONS.

12. EXISTING BUILD ING STEEL ABOVE ROOF.

13. EXHAUST FILTER HOUSING CONTAINING 2" MERV 8 FILTER AND 12" HEPA FILTER IN SERIES. FILTERS SHALL BE 20"X20" OR EQUIVALENT SQUARE FOOTAGE. HOUSING SHALL BE EQUAL TO CAMFIL GLIDEPACK.

SCALE: 1/4" = 1'-0"

MECHANICAL ROOM SECTION2

SCALE: 1/4" = 1'-0"

AHU DETAIL3

NOTES - MECHANICAL ROOM SECTION

1. EXHUAST DUCT HIGH.

2. RETURN DUCT HIGH.

3. SUPLLY DUCT LOW .

4. EXHAUST FAN VFD.

Page 25:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

FIRE ALARM SYMBOLS

ELECTRICAL SYMBOLS

EXISTING OUTLET OR DEVICE TO REMAIN. MAINTAIN EXISTING CIRCUITING.

DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS W HERE REQUIRED.

ELECTRICAL CONNECTION.

20A-125V HOSPITAL GRADE DUPLEX RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERW ISE).

20A-125V HOSPITAL GRADE SINGLE RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERW ISE).

HOSPITAL GRADE SPECIAL PURPOSE RECEPTACLE. REFER TO NOTE ON PLAN.

20A-125V HOSPITAL GRADE DOUBLE DUPLEX RECEPTACLE. NEMA 5-20R, (18" MH UNLESS NOTED OTHERW ISE) TW O GANG ASSEMBLY.

20A-125V HOSPITAL GRADE DUPLEX RECEPTACLE, NEMA 5-20R W ITH BOTTOM OUTLET CONTROLLED BY W ALL SW ITCH. (18" MH UNLESS NOTED OTHERW ISE).

20A-125V HOSPITAL GRADE DUPLEX RECEPTACLE, NEMA 5-20R, W ITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED OTHERW ISE).

20A-125V W EATHERPROOF HOSPITAL GRADE DUPLEX RECEPTACLE, NEMA 5-20R (HORIZONTAL 18" MH UNLESS NOTED OTHERW ISE) W ITH TAYMAC #10310 STANDARD COVER, VERTICAL MOUNT.20A-125V W EATHERPROOF HOSPITAL GRADE DUPLEX RECEPTACLE, NEMA 5-20R W ITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED OTHERW ISE), W ITH TAYMAC #20310 STANDARD COVER, VERTICAL MOUNT.

POKE-THROUGH W ITH POW ER AND DATA.

JUNCTION BOX. SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POW ER.

MULTI-OUTLET RECEPTACLES ASSEMBLY, NEMA 5-15R (SINGLE OUTLETS ON 18" CENTERS) (46" MH UNLESS NOTED OTHERW ISE).

SPECIFICATION GRADE SINGLE POLE SW ITCH (46" MH UNLESS NOTED OTHERW ISE).

SPECIFICATION GRADE MULTI-W AY W ALL SW ITCH, # INDICATES NUMBER OF W AYS (46" MH UNLESS NOTED OTHERW ISE).

SPECIFICATION GRADE KEY OPERATED W ALL SW ITCH (46" MH UNLESS NOTED OTHERW ISE).

0-10V DC SPECIFICATION GRADE LIGHTING DIMMER SW ITCH (46" MH UNLESS NOTED OTHERW ISE)

DISCONNECT SW ITCH.

MOTOR STARTER.

COMBINATION MOTOR STARTER AND DISCONNECT SW ITCH.

ELECTRIC MOTOR.

ELECTRICAL PANEL OR SW ITCHBOARD PER DRAW INGS.

POW ER POLE.

CEILING MOUNTED OCCUPANCY SENSOR.

W ALL MOUNT SPEAKER & SIGNAL LIGHT (W HITE FINISH), (# W HEN SHOW N INDICATES CANDELA RATING OF STROBE. W HEN A # IS NOT SHOW N, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS & 30 CANDELA FOR ALL OTHER LOCATIONS.

W ALL MOUNT SIGNAL LIGHT (W HITE FINISH), (# W HEN SHOW N INDICATES CANDELA RATING OF STROBE. W HEN A # IS NOT SHOW N, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS & 30 CANDELA FOR ALL OTHER LOCATIONS.

FIRE ALARM MANUAL STATION (46" MH UNLESS NOTED OTHERW ISE).

CEILING MOUNTED SMOKE DETECTOR.

ELECTRO-MAGNETIC DOOR HOLDER.

W ATER FLOW SW ITCH.

VALVE SUPERVISORY SW ITCH.

PUSHBUTTON (46" MH UNLESS NOTED OTHERW ISE) EDW ARDS 852 (120 VOLT).

GF

W P

W P/GF

J

#

K

D

PP

OS

F15

15

F

S

D

FS

V

ADDRESSABLE MODULE. SUBSCRIPT "I" IND ICATES INPUT. SUBSCRIPT "C" INDICATES CONTROL.AMC/I

FIRE ALARM CONTROL PANEL.

20A-125V HOSPITAL GRADE DUPLEX RECEPTACLE, NEMA 5-20R (46" MH UNLESS NOTED OTHERW ISE).

FACP

SPECIFICATION GRADE LOW -VOLTAGE MOMENTARY W ALL SW ITCH (46" MH UNLESS NOTED OTHERW ISE).L

SECURITY SYMBOLS WITH ELECTRICAL REQUIREMENTS

EL ELECTRONIC DOOR LOCK. PROVIDE ROUGH-IN. REFER TO GENERAL NOTE.

ES ELECTRONIC STRIKE. PROVIDE ROUGH-IN. REFER TO GENERAL NOTE.

HD HANDICAP DOOR OPERATOR MOTOR ASSEMBLY. PROVIDE ROUGH-IN. REFER TO GENERAL NOTE.

HA W ALL/PEDESTAL MOUNT HANDICAP DOOR ACTUATOR BUTTON. PROVIDE ROUGH-IN. REFER TO GENERAL NOTE.

CRW ALL MOUNTED PROXIMITY CARD READER (46" MH UNLESS NOTED OTHERW ISE). PROVIDE ROUGH-IN. REFER TO GENERAL NOTE.

KW ALL MOUNTED SECURITY KEYPAD ENTRY STATION (46" MH UNLESS NOTED OTHERW ISE). PROVIDE ROUGH-IN. REFER TO GENERAL NOTE.

PP WW ALL MOUNTED PANIC /DURESS BUTTON (46" MH UNLESS NOTED OTHERW ISE). PROVIDE ROUGH-IN. REFER TO GENERAL NOTE.

TECHNOLOGY SYMBOLS WITH ELEC. REQUIREMENTS

P W ALL MOUNTED PHONE OUTLET (46" MH UNLESS NOTED OTHERW ISE). PROVIDE ROUGH-IN. REFER TO GENERAL NOTE.

CONDUIT SLEEVE / FIRE RATED SLEEVE ASSEMBLY THRU W ALL (1-2" SLEEVE UNLESS NOTED OTHERW ISE) PER DIV 26.

D W ALL MOUNTED VOICE/DATA OUTLET (18" MH UNLESS NOTED OTHERW ISE). PROVIDE ROUGH-IN. REFER TO GENERAL NOTE.

ABBREVIATIONS

AAP - AREA ALARM PANEL - MEDICAL GASALT - ALTERNATEARCH - ARCHITECT OR ARCHITECTURALATS - AUTOMATIC TRANSFER SW ITCH

CM - COFFEE MAKERCORR - CORRIDOR

D - DEPTHDIA - DIAMETERDIM - DIMENSIONDIV - DIVISIONDN - DOW NDW G - DRAW ING

EC - ELECTRICAL CONTRACTOR (DIVISION 26)ELEC - ELECTRICALELEV - ELEVATION OR ELEVATOREM - EMERGENCYEQUIP - EQUIPMENTE - EXISTING TO REMAINE/R - EXISTING TO BE RELOCATED

FSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)FT - FEET

GC - GENERAL CONTRACTORGF - GROUND FAULT CIRCUIT INTERRUPTERGFCI - GROUND FAULT CIRCUIT INTERRUPTER

HC - HVAC CONTRACTOR (D IVISION 23)HP - HORSE POW ERHVAC - HEATING, VENTILATING, AND AIR CONDITIONING

L - LENGTHLBS - POUNDS

MAP - MASTER ALARM PANEL (MEDICAL GAS)MAX - MAXIMUMMH - MOUNTING HEIGHT TO CENTER LINE OF ITEMMIN - MINIMUMMTD - MOUNTEDMW - MICROW AVE

NIC - NOT IN CONTRACTNTS - NOT TO SCALE

PC - PLUMBING CONTRACTOR (DIVISION 22)PLBG - PLUMBINGPR - PRINTER

REF - REFRIGERATOR

S - SURFACE MOUNTEDSH - SHREDDERSPEC - SPECIFICATIONSSQ - SQUARE

TEMP - TEMPERATURETV - TELEVISION/MONITORTYP - TYPICAL

UCR - UNDERCOUNTER REFERIGERATOR

VFD - VARIABLE FREQUENCY DRIVE

W P - W EATHERPROOF

ZVC - ZONE VALVE CABINET

1

E2

B

E2DETAIL: B = DETAIL DESIGNATION

E2 = SHEET W HERE DETAIL IS LOCATED

SECTION: 1 = SECTION DESIGNATION E2 = SHEET W HERE SECTION IS LOCATED

PLAN NOTE. APPLIES ONLY TO THE SHEET W HICH IT IS SHOW N.

DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

GENERAL FLOOR PLAN NOTES

EACH ARROW HEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL NAME; NUMBER(S) DENOTES CIRCUIT(S).

X - 1,2

3

3

LUMINAIRE SYMBOLS

LIGHTING FIXTURE. CAPITAL LETTER DENOTES FIXTURE TYPE, LOW ER CASE LETTER DENOTES SW ITCHING ARRANGEMENT.

LIGHTING FIXTURE ON CRITICAL CIRCU IT.

EXIT LIGHTING FIXTURE, ARROW S AS INDICATED.

Aa

3

3

20A-125V HOSPITAL GRADE DUPLEX RECEPTACLE, NEMA 5-20R W ITH 2 INTEGRAL USB CHARGERS (18" MH UNLESS NOTED OTHERW ISE).

NOTE:

• ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT

TO MODIFICATIONS ON OTHER DRAWINGS.

• ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT

NECESSARILY BE USED ON THIS PROJECT.

LIGHTING FIXTURE ON LIFE SAFETY AND NIGHT LIGHT.

SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POW ER. SPECIFICATION IS SAME AS RESPECTIVE ROUND DEVICE.

J

• THE ELECTRICAL CONTRACTOR SHALL REMOVE EXISTING W ORK W HICH IS ASSOCIATED W ITH HIS TRADE, AND W HICH W ILL BE SUPERFLUOUS W HEN THE NEW SYSTEM IS INSTALLED AND MADE OPERATIONAL. REMOVE INACTIVE W IRING BACK TO THE LAST ACTIVE JUNCTION BOX, PANELBOARD OR PIECE OF EQUIPMENT. NETW ORK CABLING SHALL BE REMOVED BY OW NER.

• ELECTRICAL DEMOLITION PLAN IS NOT INTENDED TO SHOW THE ENTIRE SCOPE OF DEMOLITION W ORK BUT TO HELP CLARIFY SCOPE OF NEW W ORK. THE EC IS REQUIRED TO FIELD VERIFY EXACT SCOPE OF DEMOLITION W ORK DURING BID PERIOD.

• EC SHALL COORDINATE ALL D IMMER SW ITCHES W ITH LUMINAIRE MANUFACTURER TO ENSURE DIMMER IS COMPATIBLE W ITH LUMINAIRE.

• REFER TO ARCHITECT'S REFLECTED CEILING PLAN FOR EXACT LOCATIONS OF ALL LUMINARIES.

• PROVIDE 120V CONTROL POW ER FOR ALL FIRE SMOKE DAMPERS. REFER TO DIVISION 23 DRAW INGS/DETAILS FOR EXACT QUANTITY AND LOCATIONS. PROVIDE 120V-20A LIFE SAFETY CIRCUIT(S) SERVED FROM PANEL _____. CONNECT NO MORE THAN EIGHT (8) DAMPERS PER CIRCUIT.

• EC SHALL PROVIDE ROUGH-INS FOR ALL NEW THERMOSTATS CONSISTING OF A SINGLE GANG BOX AND 0.75" BUSHED CONDUIT STUBBED ABOVE ACCESSIBLE CEILING TURNED 90 DEGREES W ITH BUSED ENDS. REFER TO DIVISION 23 DRAW INGS FOR EXACT QUANTITY AND LOCATIONS.

• EC SHALL PROVIDE ALL ROUGH-INS REQUIRED FOR MATRIX ACCESS CONTROL SYSTEM. COORDINATE ALL W ORK W ITH OW NER'S VENDOR, MATRIX SYSTEMS. PROVIDE CONDUIT STUBS FOR W ALL ROUGH-INS TURNED 90 DEGREES W ITH BUSHED ENDS.

• COORDINATE EXACT MOUNTING HEIGHTS W ITH ARCHITECTURAL DRAW INGS PRIOR TO ROUGH-IN.

• FIRE ALARM SYSTEM W ORK SHALL BE PROVIDED BY DIVISION 26 CONTRACTOR. COORDINATE ALL FIRE ALARM W ORK W ITH OW NER'S VENDOR. REFER TO SPECS

• VOICE/DATA W ORK INCLUDING HORIZONTAL CABLING, JACKS, FACEPLATES PUNCHDOW N PANELS, ETC. SHALL BE PROVIDED BY OW NER. EC SHALL PROVIDE 4" SQUARE BOX W ITH SINGLE GANG RING AND 1" CONDUIT STUBBED ABOVE ACCESSIBLE CEILING AND TURNED 90 DEGREES W ITH BUSHED ENDS. FOR EXISTING STUD W ALLS, PROVIDE FLANGED OPENING W ITH A STRING.

ELECTRICAL GENERAL NOTES

• W ORK MUST CONFORM TO THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE AND OTHER APPLICABLE LOCAL, STATE AND FEDERAL LAW S, ORDINANCES AND REGULATIONS. W HERE DRAW INGS OR SPECIFICATIONS EXCEED CODE REQUIREMENTS, THE DRAW INGS AND SPECIFICATIONS SHALL GOVERN. INSTALL NO W ORK CONTRARY TO MINIMUM LEGAL STANDARDS.

• ALL ELECTRICAL W ORK SHALL BE INSPECTED AND APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION.

• PROVIDE OFFSETS IN SYSTEM RUNS, ADDITIONAL FITTINGS, NECESSARY CONDUIT, PULL BOXES, CONDUCTORS, SW ITCHES AND DEVICES REQUIRED TO COMPLETE THE INSTALLATION, OR FOR THE PROPER OPERATION OF THE SYSTEM.

• AS EACH W IRING SYSTEM IS COMPLETED, IT SHALL BE TESTED FOR CONTINUITY AND FREEDOM FROM GROUNDS.

• W ORK SHALL BE SO PLANNED AND EXECUTED AS TO PROVIDE REASONABLE CONTINUOUS SERVICE OF EXISTING SYSTEMS THROUGHOUT THE CONSTRUCTION PERIOD. W HERE NECESSARY TO DISRUPT SERVICES FOR SHORT PERIODS OF TIME FOR CONNECTION, ALTERATION OR SW ITCH OVER, THE OW NER SHALL BE NOTIFIED IN ADVANCE AND OUTAGES SCHEDULED AT THE OW NER'S REASONABLE CONVENIENCE.

• ELECTRICAL W ORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN ACCORDANCE W ITH REQUIREMENTS OF THE JURISDICTION.

• W HERE CONDUITS ARE TO PASS THRU, ABOVE OR BEHIND EXISTING W ALLS, PARTITIONS, FLOORS, ROOF OR CEILING, CUTTING, PATCHING, REFINISHING AND PAINTING OF SAME SHALL BE INCLUDED. CORE DRILLING AND SAW CUTTING SHALL BE UTILIZED W HERE PRACTICAL. CONTRACTOR TO EXAMINE W HERE FLOORS AND W ALLS ETC. ARE TO BE CUT FOR PRESENCE OF EXISTING UTILITIES UTILIZING X-RAY TECHNOLOGY IF NECESSARY.

• FIRESTOPPING ASSEMBLIES SHALL BE TESTED AND RATED IN ACCORDANCE W ITH ASTM E814 AND E119 AND LISTED IN ACCORDANCE W ITH UL 1479, AS PUBLISHED IN THE UL FIRE RESISTANCE DIRECTORY. FIRESTOPPING SHALL PROVIDE A FIRE RATING EQUAL TO THAT OF THE CONSTRUCTION BEING PENETRATED AND MANUFACTURED BY SPECIFIED TECHNOLOGIES.

• A COMPLETE ELECTRICAL SYSTEM AS SHOW N ON THE DRAW INGS AND AS SPECIFIED HEREIN. W ORK INCLUDES, BUT IS NOT NECESSARILY LIMITED TO W IRING DEVICES, POW ER W IRING, M ISCELLANEOUS W IRING AND INTERLOCKS, EQUIPMENT CONNECTIONS, LUMINARIES, FIRE ALARM.

• PROVIDE FLUSH W ALL MOUNTED HOSPITAL GRADE W IRING DEVICES AS SHOW N. OUTLETS SERVED BY NORMAL CIRCUITS SHALL BE IVORY COVERED BY A STAINLESS STEEL PLATE. COVERPLATES FOR NORMAL RECEPTACLES SHALL BE ENGRAVED TO IDENTIFY PANELBOARD AND CIRCUIT NUMBER FILLED W ITH BLACK PAINT. MATCH HOSPITAL STANDARD.

• PROVIDE FLUSH W ALL MOUNTED HOSPITAL GRADE W IRING DEVICES AS SHOW N. OUTLETS SERVED BY UPS CIRCUITS SHALL BE W HITE COVERED BY IVORY PLATE. COVERPLATES FOR UPS RECEPTACLES SHALL BE ENGRAVED TO IDENTIFY PANELBOARD AND CIRCUIT NUMBER FILLED W ITH RED PAINT. MATCH HOSPITAL STANDARD.

• PROVIDE A DEVICE PLATE TO SUIT EACH PARTICULAR APPLICATION. COVER ALL EMPTY OUTLET BOXES W ITH A BLANK PLATE.

• IN FIN ISHED SPACES, W ALL PLATES SHALL BE NOMINAL .032 INCH THICK, MADE OF 302 HIGH NICKEL STAINLESS STEEL W ITH BRUSHED SATIN FINISH AND BEVELED EDGES. SCREW S SHALL BE METAL W ITH COUNTERSUNK HEADS AND FINISHED TO MATCH PLATES. SECTIONAL PLATES W ILL NOT BE PERMITTED.

• NONMETALLIC SPRING TYPE INSULATED PRESSURE CONNECTORS AS MADE BY "SCOTCHLOK" OR EQUAL SHALL BE USED FOR SPLICING CONDUCTORS. CONNECTIONS IN NO. 8 AND LARGER SHALL BE SPLICED BY APPROVED PRESSURE TYPE MECHANICAL CONNECTORS AND INSULATED W ITH RUBBER OR VINYL TAPE TO ACHIEVE A RESISTANCE EXCEEDING 150% OF THE CONDUCTOR INSULATION. W IRE SHALL BE PULLED ONLY AFTER THAT SECTION OF THE CONDUIT RUN IS PROVEN TO BE CLEAR OF OBSTRUCTIONS, DIRT, MOISTURE AND GREASE. BRANCH CIRCUIT W IR ING SHALL BE PULLED W ITHOUT THE USE OF LEVERS OR HEAVY PULLING DEVICES.

• CONDUIT SHALL BE USED FOR ALL W IRING (EXCEPT W HERE “HCF” ARMORED IS USED). CONDUIT SHALL BE 3/4" DIAMETER OR LARGER EXCEPT 1/2" SIZE MAY BE USED FOR FLEXIBLE CONDUIT, SW ITCH LEGS OR CONDUIT CARRYING CONTROL W IRING ONLY. TERMINATIONS OF ALL CONDUITS SHALL BE SECURED BY LOCK- NUTS AND APPROVED BUSHINGS TIGHTENED UP TO SECURE ELECTRICAL AND MECHANICAL INTEGRITY OF THE CONDUIT SO TO PROVIDE AN UNBROKEN GROUNDING PATH. A SEPARATE COPPER GROUNDING CONDUCTOR SHALL BE PULLED W ITH ALL BRANCH CIRCUITS.

• CONDUIT SYSTEMS MAY BE ANY ONE OR COMBINATION OF THE FOLLOW ING, W ITHIN RESTRICTING LIMITS INDICATED. CONDUIT TYPES NOT LISTED SHALL NOT BE USED.

1. RIGID GALVANIZED CONDUIT - NO RESTRICTIONS.2. INTERMEDIATE GRADE GALVANIZED THREADED CONDUIT - NO RESTRICTIONS.3. THINW ALL CONDUIT W ITH APPROVED CONNECTOR FITTINGS TO ASSURE GROUNDING CONTINUITY. SHALL NOT BE USED IN POURED

CONCRETE, OUTDOORS, OR UNDERGROUND.4. FLEXIBLE METAL CONDUIT (GREENFIELD TYPE) GALVANIZED. ABOVE CEILING USE RESTRICTED TO CONNECTIONS TO LIGHTING

FIXTURES, MAXIMUM LENGTH 6 FT.5. LIQUID TIGHT FLEXIBLE METAL CONDUIT W ITH W ATER TIGHT OIL RESISTANT OUTER PVC COVERING. USED FOR CONNECTIONS TO

MOTORS OR CONTROLS ON DYNAMIC EQUIPMENT AND CONNECTIONS TO TRANSFORMERS.

• ARMORED/METAL CLAD CABLE, TYPE HCF SHALL ONLY BE USED FOR NORMAL POW ER C IRCUITS IN FULL HEIGHT W ALLS ONLY. HCF CABLE SHALL NOT BE USED IN HALF W ALLS SUCH AS NURSES STATIONS, BELOW W INDOW S OR ABOVE CEILING SPACES. BRANCH CIRCUITS FROM PANELBOARDS SHALL BE RUN IN HOME RUN CONDUITS TO A JUNCTION BOX LOCATED NO MORE THAN FOUR FEET FROM THE FULL HEIGHT W ALL. AT THESE JUNCTION BOXES, THE TRANSITION IS MADE TO TYPE HCF CABLE. THE MULTI-CONDUCTOR ARMORED METAL CLAD CABLE RUNOUTS CONTINUE TO RECEPTACLES, ETC.

• DEVICE AND JUNCTION BOXES GALVANIZED STEEL, CODE GAUGE AND SIZE BY STEEL CITY, RACO, APPLETON OR R&S. BOXES CONNECTING MORE THAN ONE PAIR OF CONDUCTORS TO BE MINIMUM 4" X 4", OR 4" OCTAGONAL SIZE. USE ADAPTER PLATES FOR DEVICES W HERE NUMBER OF CONNECTIONS OR OTHER CONDITIONS DICTATE. W RITE PANEL AND CIRCUIT NUMBER ON JUNCTION BOX W ITH PERMANENT MARKER.

• FIRE ALARM W ORK SHALL BE AN EXPANSION/MODIFICATION OF THE EXISTING NOTIFIER NFS 3030 INTELLIGENT FIRE ALARM SYSTEM AND SHALL BE INCLUDED IN THE DIVISION 26 CONTRACT. W IRING SHALL BE IN CONDUIT INSTALLED PER DIRECTION OF THE MANUFACTURER. TEST AND DEMONSTRATE SYSTEM. INSTALLER SHALL MEET STATE OF OHIO REQUIREMENTS FOR CERTIFICATION. THE CONTRACTOR OR H IS FIRE ALARM SUPPLIER/INSTALLER SHALL SUBMIT SHOP DRAW INGS TO THE LOCAL FIRE OFFICIAL FOR PERMIT, REVIEW AND APPROVAL. THE FIRE ALARM SUPPLIER SHALL SUBMIT FOR APPROVAL W ITH SHOP DRAW INGS, FLOOR PLANS, SCHEMATIC AND POINT TO POINT W IRING DIAGRAMS SHOW ING ALL MANUAL AND AUTOMATIC DEVICES, CONTROL PANELS, SOUNDING DEVICES, CONDUIT SIZES, NUMBER AND SIZE OF W IRES, ETC. SHOP DRAW INGS SHALL INCLUDE CALCULATIONS FOR SIZING OF SIGNAL POW ER SUPPLIES, VOLTAGE DROP CALCULATIONS FOR AUDIBLE AND VISUAL SIGNAL C IRCUITS, SPEAKER AMPLIFIERS AND STANDBY BATTERIES.

ELECTRICAL SPECIFICATIONS

1

RW ALL MOUNTED TV OUTLET. COORDINATE MOUNTING HEIGHT W ITH OW NER/ARCHITECT. PROVIDE ROUGH-IN . REFER TO GENERAL NOTE.

15

F

FIRE ALARM SIGNAL LIGHT (80" AFF). # W HEN SHOW N INDICATES CANDELA RATING OF STROBE. W HEN A # IS NOT SHOW N, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.

CEILING MOUNTED FIRE ALARM SIGNAL LIGHT. # W HEN SHOW N INDICATES CANDELA RATING OF STROBE. W HEN A # IS NOT SHOW N, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.

15F

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

4/2

01

9 4

:27

:55

PM

\\D

ayd

ata

05

\He

apyD

ocu

men

ts\k

mu

hle

nh

ake\M

y D

ocum

ents

\20

19

-05

078

-ME

P-C

en

tra

l_km

uhle

nha

ke

.rvt

2019-05078

LLC

KMU

July 24, 2019

E001

LEGEND, SPECS ANDSHEET INDEX

1 2019.07.24 ADDENDUM 1

SHEET INDEX - ELECTRICAL

SHEET NUMBER SHEET NAME

E001 LEGEND, SPECS AND SHEET INDEX

E002 ELECTRICAL SCHEDULES

E003 SINGLE LINE DIAGRAM

E004 BASEMENT AND ROOF PLANS

E101 FIRST FLOOR - ELEC. DEMOLITION PLAN

E201 FIRST FLOOR - LIGHTING PLAN

E301 FIRST FLOOR - POWER & SYSTEMS PLAN

Page 26:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

4/2

01

9 4

:28

:04

PM

\\D

ayd

ata

05

\He

apyD

ocu

men

ts\k

mu

hle

nh

ake\M

y D

ocum

ents

\20

19

-05

078

-ME

P-C

en

tra

l_km

uhle

nha

ke

.rvt

2019-05078

LLC

KMU

July 24, 2019

E002

ELECTRICALSCHEDULES

1 2019.07.24 ADDENDUM 1

33.33 kVA 28.04 kVA (78 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: 1. NOTE - THIS IS AN EXISTING PANEL AND SERVED FROM NORMAL POWER. PANEL WAS PREVIOUSLY LABELED CG.

Total Load: 10.88 kVA 10.95 kVA 11.50 kVA

41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42

39 REC 20 A 1 720 VA 180 VA 1 20 A REC 40

37 REC 20 A 1 720 VA 900 VA 1 20 A REC 38

35 REC 20 A 1 720 VA 900 VA 1 20 A REC 36

33 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 34

31 EXISTING 20 A 1 720 VA 1000... 1 20 A REFRIGERATOR 32

29 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 30

27 EXISTING 20 A 1 720 VA 1000... 1 20 A REFRIGERATOR 28

25 HOOD 20 A 1 750 VA 1000... 1 20 A REFRIGERATOR 26

23 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 24

21 HOOD 20 A 1 750 VA 750 VA 1 20 A HOOD 22

19 HOOD 20 A 1 750 VA 720 VA 1 20 A EXISTING 20

17 UC REF 20 A 1 1160... 2400... 1 20 A OMNICELL 18

15 EXISTING 20 A 1 720 VA 720 VA 1 20 A REC 16

13 EXISTING 20 A 1 720 VA 720 VA 1 20 A REC 14

11 REC 20 A 1 720 VA 720 VA 1 20 A REC 12

9 REFRIGERATOR 20 A 1 1000... 1000... 1 20 A REFRIGERATOR 10

7 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 8

5 FREEZER 20 A 1 1000... 1000... 1 20 A FREEZER 6

3 EXISTING 20 A 1 720 VA 1233... 1 20 A LTG PHARMACY 4

1 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 2

CKT Circuit Description Trip PolesA B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W Mains Rating: 200 ASupply From: DP3 Enclosure: Type 1 Mains Type: MLO

Location: CORRIDOR 1527 Mounting: Recessed A.I.C. Rating: EXISTING

Panel: N112

50.06 kVA 45.61 kVA (127 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: 1. NOTE - THIS IS AN EXISTING PANEL AND SERVED FROM THE CRITICAL BRANCH. PANEL WAS PREVIOUSLY LABELEDEM3.

Total Load: 18.01 kVA 16.38 kVA 15.67 kVA

41 -- -- -- 720 VA 6310... -- -- -- 42

39 EXISTING 20 A 2 720 VA 7020... -- -- -- 40

37 EXISTING 20 A 1 720 VA 8653... 3 70 A E127A-CB 38

35 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 36

33 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 34

31 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 32

29 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 30

27 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 28

25 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 26

23 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 24

21 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 22

19 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 20

17 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 18

15 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 16

13 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 14

11 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 12

9 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 10

7 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 8

5 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 6

3 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 4

1 EXISTING 20 A 1 720 VA 720 VA 1 20 A EXISTING 2

CKT Circuit Description Trip PolesA B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W Mains Rating: 200 ASupply From: DP5 Enclosure: Type 1 Mains Type: MLO

Location: CORRIDOR 1527 Mounting: Recessed A.I.C. Rating: EXISTING

Panel: E127-CB

21.98 kVA 17.53 kVA (49 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: 1. NOTE - THIS IS A NEW PANEL AND SERVED FROM THE CRITICAL BRANCH.2. $ REPRESENTS GFCI BREAKER.

Total Load: 8.65 kVA 7.02 kVA 6.31 kVA

41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42

39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40

37 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 38

35 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 36

33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34

31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32

29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30

27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28

25 REC 20 A 1 720 VA 370 VA 1 20 A PHARMACY FAN COILS 26

23 REC 20 A 1 900 VA 720 VA 1 20 A $ REC 24

21 REF 20 A 1 1000... 720 VA 1 20 A REC 22

19 COPIER 20 A 1 750 VA 1000... 1 20 A REF 20

17 UC REF 20 A 1 860 VA 1000... 1 20 A REF 18

15 OMNICELL 20 A 1 1000... 750 VA 1 20 A HOOD 16

13 REC 20 A 1 720 VA 750 VA 1 20 A HOOD 14

11 REC 20 A 1 720 VA 750 VA 1 20 A HOOD 12

9 REC 20 A 1 720 VA 750 VA 1 20 A HOOD 10

7 REFRIGERATOR 20 A 1 1000... 720 VA 1 20 A REC 1550 8

5 REFRIGERATOR 20 A 1 1000... 360 VA 1 20 A P TUBE 6

3 FREEZER 20 A 1 1000... 1080... 1 20 A AUTO DOORS 4

1 FREEZER 20 A 1 1000... 1623... 1 20 A LTG PHARMACY 2

CKT Circuit Description Trip PolesA B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W Mains Rating: 100 ASupply From: E127-CB Enclosure: Type 1 Mains Type: MLO

Location: CORR. 1535 Mounting: Recessed A.I.C. Rating: 10,000

Panel: E127A-CB

NOTES:1.

LUMINAIRES

MARK FIX

TU

RE

VO

LT

AG

E

LO

AD

(V

A)

MANUFACTURER CATALOG NO. DESCRIPTION

OTHER ACCEPTABLEMANUFACTURERS

MOUNTING

SE

E N

OT

E

S-SURFACER-RECESSEDSM-STEM MTDWM-WALL MTDC-CHAIN MTD

UC-UNDER CABCS-CEIL SURFACE

C4 120 41 LITHONIA ZL1D-L48-5000LM-FST-MVOLT-35K-80CRI-WH-HC36 4' LONG LED INDUSTRIAL STRIP COLUMBIA "CSL" C

F6 120 21 LITHONIA LDN6-35/15-LO6-LSS-MVOLT-EZ10 6" LED DOWNLIGHT PRESCOLITE "LC6" R

L22 120 32 LITHONIA EPANL-2x2-4000LM-80CRI-35K-MIN10-ZT-MVOLT 2'x2' LED FLAT PANEL COLUMBIA "CFP" R

L24 120 54 LITHONIA EPANL-2x4-6000LM-80CRI-35K-MIN10-ZT-MVOLT 2'x4' LED FLAT PANEL COLUMBIA "CFP" R

L24L 120 39 LITHONIA EPANL-2x4-4000LM-80CRI-35K-MIN10-ZT-MVOLT 2'x4' LED FLAT PANEL COLUMBIA "CFP" R

W2 120 20 TECH LIGHTING 700BCMLN-24-W-C-LED930 2' LONG LED VANITY LIGHT MODERN FORMS WM

X1 120 1 LITHONIA LQC-W-1-R SINGLE FACE EXIT SIGN DUAL-LITE CS

X2 120 1 LITHONIA LQC-W-2-R DOUBLE FACE EXIT SIGN DUAL-LITE CS

NOTES:1. SINGLE POINT CONNECTION TO AHU BY EC. AHU SHALL HAVE INTERNAL TRANSFORMER TO SERVE MISCELLANEOUS 120V LOADS.2. EC SHALL PROVIDE WEATHERPROOF DISCONNECT ADJACENT TO EXHAUST FAN.

MOTORS, STARTERS, DISCONNECTS & CONTROLS

MARK

MOTOR STARTER DISCONNECT MEANS FEEDER

SE

E N

OT

E

NAMEPLATE

CHARACTERISTICS

NE

MA

SIZ

E

TYPE LOCATION F

UR

NIS

HE

D B

YTYPE LOCATION

FU

RN

ISH

ED

BY

NU

MB

ER

OF

CO

ND

UC

TO

RS

WIR

E S

IZE

GR

OU

ND

SIZ

E

CO

ND

UIT

SIZ

E

HO

RS

EP

OW

ER

(H

P)

LO

AD

(kV

A)

12

0V

-1P

H

20

8V

-1P

H

20

8V

-3P

H

48

0V

-1P

H

48

0V

-3P

H

EC

M

MA

GN

ET

IC

VF

D

SE

E N

OT

E

NE

AR

MO

TO

R

IN

TE

GR

AL

W/

EQ

UIP

.

RO

OM

NU

MB

ER

SE

E N

OT

E

DIS

C S

WIT

CH

NE

MA

TY

PE

DIS

C S

IZE

FU

SE

SIZ

E

NE

AR

MO

TO

R

IN

TE

GR

AL

W/

EQ

UIP

.

SE

E N

OT

E

AHU-24 PHARMACY AHU 12 kVA 12 ● ● ● HC ● ● HC 3 10 10 0.75 1

EF-92 CHEMO EXHAUST 2 2.83 ● ● 1542A 2 HC ● 3R 30 ● EC 3 12 12 0.75 2

14.83 kVA 14.83 kVA (18 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: 1. NOTE - THIS IS A NEW PANEL AND SERVED FROM THE EQUIPMENT BRANCH.

Total Load: 4.94 kVA 4.94 kVA 4.94 kVA

41 Space -- -- 0 VA 0 VA -- -- Space 42

39 Space -- -- 0 VA 0 VA -- -- Space 40

37 Space -- -- 0 VA 0 VA -- -- Space 38

35 Space -- -- 0 VA 0 VA -- -- Space 36

33 Space -- -- 0 VA 0 VA -- -- Space 34

31 Space -- -- 0 VA 0 VA -- -- Space 32

29 Space -- -- 0 VA 0 VA -- -- Space 30

27 Space -- -- 0 VA 0 VA -- -- Space 28

25 Space -- -- 0 VA 0 VA -- -- Space 26

23 Space -- -- 0 VA 0 VA -- -- Space 24

21 Space -- -- 0 VA 0 VA -- -- Space 22

19 Space -- -- 0 VA 0 VA -- -- Space 20

17 -- -- -- 0 VA 0 VA -- -- -- 18

15 -- -- -- 0 VA 0 VA -- -- -- 16

13 Spare 20 A 3 0 VA 0 VA 3 20 A Spare 14

11 -- -- -- 0 VA 0 VA -- -- -- 12

9 -- -- -- 0 VA 0 VA -- -- -- 10

7 Spare 20 A 3 0 VA 0 VA 3 20 A Spare 8

5 -- -- -- 4000... 942 VA -- -- -- 6

3 -- -- -- 4000... 942 VA -- -- -- 4

1 AHU-24S 30 A 3 4000... 942 VA 3 20 A EF-1 2

CKT Circuit Description Trip PolesA B C

Poles Trip Circuit Description CKT

Voltage: 480/277 Wye-3PH-4W Mains Rating: 100 ASupply From: DP4 Enclosure: Type 1 Mains Type: MLO

Location: HVAC 1542A Mounting: Surface A.I.C. Rating: 10,000

Panel: E190-EB

Page 27:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

NE

NONE

EM3AE127A-CB

E190-EB

100

E87A-CB

200A/3P (200A)

N193

E188-CB

E85-CB

E189-CB E87B-CB

CATHLAB #4

UPS

MA

80/3PCB

N80A

150A(NEW)

150A STCB2

SINGLE-LINE DIAGRAM

N

100A/3PMANUALTRANS.

PDU1A PDU1B

480D208Y/120V75KVA

SONETPDU1-LS

3

HV3

LIFE SAFETY

B3

A2

C3A3

1"C

ELEV. ELEV.

ELEV. ELEV.

ELEV. ELEV.

EM43

SECTION #1

EM51ELEC.

SHOP

EM1

EM53EM53A

EM41

SP

AC

E F

OR

200A

SW

ITC

H

SECTION #2

1200AMAIN

CATSCANLEIBERT

AC

SP

AR

E10

0S

PA

RE

100

SP

AR

E10

0

200

200

SP

AR

E20

0

200

EM55

EM42

EM50

EM5

EM3 EM4 EM2

'66 BLDG.

SECTION #3

EM6

SP

AR

E20

0S

PA

RE

200

SP

AR

E20

0S

PA

RE

200

SP

AC

E20

0

SP

AC

E20

0

SECTION #4 SECTION #1

OLD MATERNITY A.C.

BOILER

SECTION #2

200

SP

AR

E10

0

100

SP

AR

E10

0

SP

AR

E10

0

ROOM

OLD AH #1

EM

ER

.

NO

RM

.

O.U. BLDG.

OLD

SP

AC

E20

0

P3

EMX1

SECTION #1 SECTION #2

SP

AR

E60

SP

AR

E20

0

SP

AR

E20

0

SP

AR

E40

0

P2CATHLAB

SP

AR

E60

P4

TO WESTPARKING

LOT LIGHTS

SP

AR

E30

P5

SP

AR

E

CHILLERRM. 21

SP

AR

E20

0

800

SP

AR

E20

0

200A

MED AIRPUMP

PACKAGE #2

100A

MED VACPUMP

PACKAGE #2

800 800 1600

SECT. #1 SECTION #2

TO O.U. BLDG.

200A

SP

AC

E

200A

SP

AC

E

EM9

SHORT

EM9A

STAY

1� 200ATELE.

FRAMEROOM

NUCLEARMEDICINE

ELEC.SHOPCAGE

PLUMB.SHOPHALL

SECTION #1 SECTION #2 SECTION #3 SECTION #4

1600

200

HALLNEARRM. 5

200

HG

200

AAG(AG)

E

SP

AC

E

200

AA12300

2-10

0AS

PA

CE

200

GG12300

EAST

HH12300

WEST

200

BG

200

CG

200

DG

400

GG

2-10

0AS

PA

CE

2-10

0AS

PA

CE

SP

AR

E10

0

SP

AR

E10

0

SP

AR

E20

0

200

200

NG

200

2-10

0AS

PA

CE

2-10

0AS

PA

CE

SP

AR

E10

0S

PA

RE

100

200

NL1

200

NL2

SITE

200

PG

LIGHTING

LPN-150

NUCLEARMEDICINE

COMM. RM.PHARMACY

T16

200

R1

2-10

0AS

PA

CE

SECTION #4 SECTION #3 SECTION #2 SECTION #1

2-10

0AS

PA

CE

SP

AR

E10

0S

PA

RE

100

"N62"(BB)

200

TRANSFERFOR PHONE

SWITCH

200

MG

200

FG

F1

200

200

SP

AC

E

SP

AR

E20

0

B1

200

C1

200

D1

E1

200

200

KG

400

'66 BLDG.NUCLEAR

200

200

TG

SP

AR

E20

0

400

SP

AR

E20

0

200

200

EG

200

SG

400

JG

TO LS SECT. 2

TO TS14

TO SC1

SP

AR

E

SP

AC

E

SP

AC

E

SP

AC

E

SP

AC

E

SP

AC

E

1600 800 800SPACESPACE

J1J1A

SHORTSTAY

TVROOM

SHORTSTAY

CATHLAB

3600

'66EM44B

CATHLAB

TO TS13

SP

AR

E

SP

AR

E

SP

AR

E

SP

AR

E

MORGUE

EM44A

RADIOLOGYCLOSET

QI

RAD.

RAD.CLOSET

BLDG.

K12300

D24600

LAB KITCH.

KITCH.STEAMROOM

LOBBY

ELEV. #7THERAPY

PHYS.

MED.

NUC.

HALLRADIOLOGYTHERAPY

PHYS.

HIMS COMM. ROOM

D1ADOCTOR'S

READING RM.

PHARM.

HALLNEARPBX

PHONESWITCH

REGULATOR

GGELEV. OLD LAB KIT.

MAILROOMWALL

#3 & 4LOBBY

KIT.KIT.

MANHOLE #__

MCC1

EM

ER

.

MCC6

RADIOLOGYQI

TO DP18SECT. 3

SHEET E-5

3600

A15600

TO ELEV. #10

SEE SHEET E-6

B16600

EM13

'66 BLDG.

EM13A

'66 BLDG.EM13B

LAB

RAD.HALL

2300

CHEM.LAB

QIRAD.

RAD.CLOSET

MORGUE

PENTHOUSE

ELEV. #8

SHEET E-4

SHEET E-4

SHEET E-4

SHEET E-4

#3 #4

#5 #6

#7 #8

TA

G 1

2-93

RE

MO

VE

D

CHILLER 3RM. 3

SPACESPACE

TO PSC-2

N177

N178

CB X-RAY CATHLAB

ANGIO

AB

DP6

LABELED C2

3/60

2/60

E133EB

B506

E148CB

B521

E146CB

1342

E131CB

2432

E103CB

2407E102CB

4542E75CB

4545E75ACB

2430

E100CB

1518

E132CB

2316

E109CB

EM422316

E109CB

E128CB

2435E101CB

E127-CB

B415E147CB

1616

E129CB

3617

E78CB

4645

E71CB

6600

E68CB

6642N66

B522E145EB

3403

CTFEEDER

B503E139EB

2407E104EB

3618N76

3419N83

5642N69

B400

N14

3CB

N14

2

B424E140

1725E124

N136B524

N117

1342N110

2316N105

2314N107

N106

N111N112

N113 N115N116

CAPPEDOFF IN

BOILER RM.

B521

N138N137

1616N121

2317N125

1335N120 1313

N114

2606N88

N89 N90

N91A

N91

N92

4653N123B

N70N72 N74 N73

3618N77

N79

2311N123A

N119

N1231631 N122

1728

J1

N62B408

N961500 N95

1500

N1181725

2332N94

2407N93

2314N108

2437N18L

E59CB E182CB

E61CB E67CB

B522

E63CB E64CB

3621E44ALS

2432E44BLS

1342E43LS

B522E60LS

TO SHEETE-4E60LS

CAGE

OLD HIMS

DICTATION

SP

AR

E

TRANSFORMER

NEED'S #

MCC1A

PANEL C2VASCULAR LAB

HALL 3618

6500

7603 7603

TO TS-23

60/3

(40)

100/

3

100/

3

EM44CLS

60A/2P

(40A)

60A/2P

(50A)

WP

60/3

30A/2P

(25A)

480V

10K V A 60A / 3P P MS

240/ 120V

EXISTING PULL BOX

NOTE: DARK LINE WEIGHT REPRESENTS NEW WORK.

"MTS2-LS"

100

"MTS1-LS"

UPSBYPASS

PBXUPS

EM43MORGUE

TO "LS"

E128ACB(LAB)

N96A N95A

EM6A FGA

SHAFTDAMPERS

ELEV.MACHINERM

ELEV.COND.UNIT

A/C

20A/2P

(20A)

T31000 KVA12,470V TO480V - 3PH - 3W

T21500 KVA12,470V TO280Y/120V - 3PH - 4W

T12000KVA12,470V TO480V - 3PH - 3W

T11KVA

V TOV - 3PH - 3W

SB (NE W)

E44-LS(NEW)

60/260/260/3

400/3

(400A)

400/3

(250A)

400/3

(300A)

480Δ TO480/277V500 KVA 6.69%

TRANSFORMERTAP

125/3PE195-CB

TS-1

200/3(200A)

EMX1

EMP1

E82EB

CATHLABUPS

N192

200/3(200A)

MA

EPLABUPS

MA

80/3PCB

80/3PCB

125/3P STCB2

125/3P STCB2

E84-CB (EM8)

N80

E

SB

E87-CB

E233-EB

60/3P

E186-CB

E187-CB

E184-CB

E185-CB

N191

E

1500

42

XX

X

5

HV2

6 2 1

XX

X

U1

UG

U3

C2

C1

HV1

XX

X

TO PSC-2 TO PSC-2

1725

2315

1400

1427

1518

1725

1725

2435

2435

1616

2529

2517

2517

4653

4542

4504

4542

3419

DP3 ()1600A - 208Y/120V-3PH-4W

DP2 ()1600A - 208Y/120V-3PH-4W

DP1 ()1000A - 480V-3PH-4W

DP16 ()A - 480V-3PH-3W

DP4 ()800A - 480V-3PH-3W

DP5 ()800A - 208Y/120V-3PH-4W

DP15 ('71 BLDG. BASEMENT,OFFICE NEAR ROOM 5)A - 480V-3PH-3W

DP6 (RM 3403)800A - 208Y/120V-3PH-4W

US2 ()3000A - 208Y/120V-3PH-4W

US3 ()1600A - 480V-3PH-3W

US1 ()2000A - 480V-3PH-3W

SEVENTH

SIXTH SIXTH

FIFTH FIFTH

FOURTH FOURTH

THIRD THIRD

SECOND SECOND

FIRST FIRST

BSMNT BSMNT

ROOF

SCALE:

12

SCOPE OF W ORK

2 3

SCOPE OF W ORK

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

4/2

01

9 4

:28

:12

PM

\\D

ayd

ata

05

\He

apyD

ocu

men

ts\k

mu

hle

nh

ake\M

y D

ocum

ents

\20

19

-05

078

-ME

P-C

en

tra

l_km

uhle

nha

ke

.rvt

2019-05078

LLC

KMU

July 24, 2019

E003

SINGLE LINE DIAGRAM

1 2019.07.24 ADDENDUM 1

1 EC SHALL PROVIDE NEW 100A/3P BREAKER INEXISTING PANEL.

2 4-#2, 1-#8 GROUND IN 1.25" CONDUIT.

3 UTILIZE SPARE 100A FUSIBLE SWITCH ANDPROVIDE NEW 100A FUSING.

Page 28:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

8

13

14

DP

5

DP

2

DP

3

DP

4

US1 US2

DP

1

ATS1

EM1

PR

IMA

RY

SW

ITC

HG

EA

R #

2

DP15

T11

NL2

NL1

DP

4D

P5

DP

5

DP

5

DP

1

DP

2

DP

3D

P3

DP

2D

P2

DP

3

EF-92

E190-EB - 1,3,5

AHU-24

W P

TO VFD

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

4/2

01

9 4

:28

:19

PM

\\D

ayd

ata

05

\He

apyD

ocu

men

ts\k

mu

hle

nh

ake\M

y D

ocum

ents

\20

19

-05

078

-ME

P-C

en

tra

l_km

uhle

nha

ke

.rvt

2019-05078

LLC

KMU

July 24, 2019

E004

BASEMENT AND ROOFPLANS

1 2019.07.24 ADDENDUM 1

SCALE: 1/8" = 1'-0"

PARTIAL BASEMENT - ELECTRICAL PLAN3

NOTES

SCALE: 1/16" = 1'-0"

PARTIAL THIRD FLOOR (ROOF) - ELECTRICAL PLAN4

Page 29:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

E127-CB N112

1

1

1

1 1 1 1

1

1

11

1

1

1 1

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

4/2

01

9 4

:28

:21

PM

\\D

ayd

ata

05

\He

apyD

ocu

men

ts\k

mu

hle

nh

ake\M

y D

ocum

ents

\20

19

-05

078

-ME

P-C

en

tra

l_km

uhle

nha

ke

.rvt

2019-05078

LLC

KMU

July 24, 2019

E101

FIRST FLOOR - ELEC.DEMOLITION PLAN

1 2019.07.24 ADDENDUM 1

SCALE: 1/4" = 1'-0"

PARTIAL FIRST FLOOR - ELECTRICAL DEMOLITION PLAN1

NOTES

1 REMOVE ALL LUMINAIRES, RECEPTACLES, FIRE ALARM DEVICES,PUBLIC ADDRESS DEVICES, DATA/COMMUNICATION DEVICES, ETC.UNLESS OTHERWISE NOTED. MAINTAIN ALL NORMAL POWERRECEPTACLE CIRCUITS FOR NEW WORK.

GENERAL NOTES

A. ELECTRONIC COORDINATION DRAW INGS ARE REQUIRED AND MUST BE SUBMITTED TO THE ENGINEER FOR REVIEW PRIOR TO BEGINNING NEW W ORK. REFER TO 23 05 01.

Page 30:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

PTD

SD

33

44

33

L

L

OS

OS

L

D D

OS OSOS

OS

D

OS

OS

L

L

OS

J

J J

J

1544

ORDER

ENTRY

OFC

1542AHVAC

1535CORR.

1527CORRIDOR

L24L

N112 - 4

v

L24L

E127A-CB - 2

v

L24L

N112 - 4

z

L24L

E127A-CB - 2

z

L24L

N112 - 4

z

E12

7A-C

B

E127-CB N112

ba

ba

ba

L24L

N112 - 4

a

L24L

E127A-CB - 2

b

L24

E127A-CB - 2

b

L24

N112 - 4

a

L24

E127A-CB - 2

b

L24

N112 - 4

a

L24

E127A-CB - 2

b

L24

N112 - 4

a

L22

E127A-CB - 2

b

L24

N112 - 4

a

L24

N112 - 4

a

L22

N112 - 4

a

L22

E127A-CB - 2

b

L24

E127A-CB - 2

b

L24

N112 - 4

a

L22

N112 - 4

a

L24

N112 - 4

a

L24

E127A-CB - 2

b

L22

N112 - 4

a

L24

N112 - 4

a

L22

N112 - 4

a

L24

N112 - 4

a

L22

E127A-CB - 2

b

L24

E127A-CB - 2

b

L22

N112 - 4

a

L22

E127A-CB - 2

b

L24

E127A-CB - 2

b

L24L

N112 - 4

y

L22

N112 - 4

c

L22

E127A-CB - 2

c

L22

N112 - 4

c

L22

E127A-CB - 2

c

L22

N112 - 4

c

c

c

d

d

d d

d

d

d d

d

d

L22

N112 - 4

e

L22

E127A-CB - 2

e

L22

N112 - 4

e

L22

E127A-CB - 2

e

L24L

E127A-CB - 2

f

L24L

N112 - 4

f

L22

N112 - 4

a

1542ANTI RM

1541CHEMO RM

1540

HD

NON-STERILE

1539NARC RM

1538POP1533

JAN

1550PACKAGING1548

RECEIVING

1547

ADA STAFF

TOILET

1546OFC

1545MGR. OFC

1543IV RM

1537A

BULK

STORAGE

1537

ORDER

ENTRY

C4 C4

E127A-CB - 2E127A-CB - 2

y

v z

F6

W 2

E127A-CB - 2

E127A-CB - 2

e

f

1 1

1

1

1

L24

N112 - 4

a

L24

E127A-CB - 2

b

L24

N112 - 4

a

2 3

E127A-CB - 2

2 3

E127A-CB - 2

2 3

E127A-CB - 2

2 3

E127A-CB - 2

L24

E127A-CB - 2

b

L24

N112 - 4

a

E190-EB

X1

X1

X1

X2

X2

X2

TYP.4

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

4/2

01

9 4

:28

:33

PM

\\D

ayd

ata

05

\He

apyD

ocu

men

ts\k

mu

hle

nh

ake\M

y D

ocum

ents

\20

19

-05

078

-ME

P-C

en

tra

l_km

uhle

nha

ke

.rvt

2019-05078

LLC

KMU

July 24, 2019

E201

FIRST FLOOR -LIGHTING PLAN

1 2019.07.24 ADDENDUM 1

SCALE: 1/4" = 1'-0"

PARTIAL FIRST FLOOR - NEW WORK LIGHTING PLAN1

NOTES

1 PROVIDE TWO POWER PACKS TO CONTROL LIGHTING.

2 ALL JUNCTION BOXES SHALL BE MOUNTED ABOVE ACCESSIBLECEILING.

3 LUMINAIRES IN THIS SPACE SHALL BE FURNISHED BY OWNER'SVENDOR (CARTER HEALTH) AND INSTALLED BY EC. COORDINATEEXACT REQUIREMENTS WITH OWNER'S VENDOR. PROVIDE 120VCONNECTION TO EACH LUMINAIRE.

4 CONNECT EXIT SIGN TO CORRIDOR LIFE SAFETY LIGHTING CIRCUIT.

GENERAL NOTES

A. ELECTRONIC COORDINATION DRAW INGS ARE REQUIRED AND MUST BE SUBMITTED TO THE ENGINEER FOR REVIEW PRIOR TO BEGINNING NEW W ORK. REFER TO 23 05 01.

Page 31:  · EQUIP equipment PERIM perimeter BSMT basement JAN janitor GALV galvanized CPT carpet GL glass GYP.BD. gypsum board CY cubic yard CTC center to center general contractor gypsum

PTD

SD

GF

S

S

S

S

CR

EL

CR

EL

CREL

JJ

SHD

HD

HD

29"MH

D 29"MH

29"M

H

D29

"MH

29"M

H

D29

"MH

29"MH

D29"MH

FREEZER

D 46"MH

FREEZER

FREEZER

D 46"MH

FREEZER

REF

D46"MH

REF

REF

D46"MH

REF

GF

D46"MH

CR

AS

H C

AR

T

CR

AS

H C

AR

T

D D

D

D D

UC

R

D18

"MH

UC

R

OMNICELL

D46"MH

OMNICELL

OMNICELL

D46"MH

OMNICELL

CO

D46

"MH

CRASH CART29"MH

D 29"MH

29"MH

D 29"MH

GF

B/S

INK

HOOD

D 46"MH

HOOD

HO

OD

D46

"MH

HO

OD

HOOD

D46"MH

HOOD

REF

D46"MH

REF

29"M

H

D29

"MH

29"M

H

D29

"MH

HOOD

D46"MH

HOOD

REF

D 46"MH

REF

REF

D46"MH

REF

D

D

29"M

H

D29

"MH

29"M

H

D29

"MH

29"MH

D29"MH

29"MH

D29"MH

29"MH

D 29"MH

29"M

H

D29

"MH

FC 1-01 FC 1-03

FC 1-04A

FC 1-04B

FC 1-05

FC 1-02

CR

EL

E12

7A-C

B

E127-CB N112

1544

ORDER

ENTRY

OFC

1542AHVAC

1535CORR.

1527CORRIDOR

1542ANTI RM

1541CHEMO RM

1540

HD

NON-STERILE

1539NARC RM

1538POP

1533JAN

1550PACKAGING1548

RECEIVING

1547

ADA STAFF

TOILET

1546OFC

1545MGR. OFC

1543IV RM

1537A

BULK

STORAGE

1537

ORDER

ENTRY

E127A-CB - 6 E127A-CB - 6

11

E127A-CB - 4

E127A-CB - 4

E127A-CB - 4

39

37

38

38

39

39

8

11 8

11

1

5

3

6

7

10

5

9

38

23

38

38

23 23

9

12

1114

1114

13 16 13 16

1717

15

18

15

18

19

2412

9

39

24

10

19

1221

16

25

18

26

1717

14

22

20

28

21

32

36

36

36

36

37

3522

35

22

37

40

25

25

E127A-CB - 26

2

E127A-CB - 26

2

E127A-CB - 26

2

E127A-CB - 26

2

E127A-CB - 26

2

E127A-CB - 26

2

E190-EBEF-92VFD

TO DISCONNECT ON ROOF

E190-EB - 2,4,6

3

44

Kettering Health Network

Grandview Medical Center

KEYPLAN:

REVISIONS:

NOTES:

Job No.

Drawn By

Checked By

Date

Sheet No.

No. Date Description

480 VANTAGE POINT, SUITE 201

MIAMISBURG, OH 45342PHONE: 937. 222. 1117 FAX: 937. 222. 4893

www.pinnaclearchitects.com

405 W. GRAND AVE. DAYTON, OHIO 45405

CLEAN ROOM RENOVATION

PHARMACY

PROJECT NO. 2019-05078

7/2

4/2

01

9 4

:28

:44

PM

\\D

ayd

ata

05

\He

apyD

ocu

men

ts\k

mu

hle

nh

ake\M

y D

ocum

ents

\20

19

-05

078

-ME

P-C

en

tra

l_km

uhle

nha

ke

.rvt

2019-05078

LLC

KMU

July 24, 2019

E301

FIRST FLOOR - POW ER& SYSTEMS PLAN

1 2019.07.24 ADDENDUM 1

SCALE: 1/4" = 1'-0"

PARTIAL FIRST FLOOR - NEW WORK POWER & SYSTEMS PLAN1

NOTES

1 PROVIDE 120V CONNECTION TO NEW PNEUMATIC TUBE STATION.

2 PROVIDE SINGLE POINT 120V CONNECTION TO FAN COIL. COORDINATEWITH HC.

3 STACK MOUNT POWER AND DATA ON WALL AT APPROXIMATELY 84".

4 STACK MOUNT POWER AND DATA ON MULLION.

GENERAL NOTES

A. ELECTRONIC COORDINATION DRAW INGS ARE REQUIRED AND MUST BE SUBMITTED TO THE ENGINEER FOR REVIEW PRIOR TO BEGINNING NEW W ORK. REFER TO 23 05 01.

B. UNLESS NOTED OTHERW ISE, ALL NORMAL POW ER RECEPTACLES SHALL BE FED FROM PANEL N112 AND ALL CRITICAL POW ER RECEPTACLES SHALL BE FED FROM E127A-CB.