Asbestos Register (Hazardous Materials and Risk Assessment) School: Erina High School (8405) Region: Hunter/Central Coast AMU State Electorate: Terrigal Local Government Area: Central Coast Last Reviewed By: Greencap 20-MAR-2015 Last Revised By: Greencap 25-JUL-2020 Historical Fibro In Grounds Investigations/Events Yes Please refer to the latest site specific Asbestos Management Plans available from the Department's website (Refer to Note 2). Erina High School (8405) 9/09/2020 1/25

Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

Asbestos Register(Hazardous Materials and Risk Assessment)

School: Erina High School (8405)

Region: Hunter/Central Coast AMU

State Electorate: Terrigal

Local Government Area: Central Coast

Last Reviewed By: Greencap 20-MAR-2015

Last Revised By: Greencap 25-JUL-2020

Historical Fibro In Grounds Investigations/Events Yes

Please refer to the latest site specific Asbestos Management Plans available from the Department's website(Refer to Note 2).

Erina High School (8405) 9/09/2020 1/25

Page 2: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

Preface to Asbestos RegisterLimitationsAsbestos Registers established (first surveyed 2007/08) and maintained for the Department of Education (DoE) are limited in extent, in that:

1. All inspections and surveys of materials and finishes in DoE facilities are non-disturbance, with2. Samples undertaken by hygienist to determine whether a sample is an Asbestos Containing Material (ACM),3. The hygienist may apply a single sample to like materials within a space and adjoining spaces, but not normally between buildings,4. Successive inspections have reduced any inconclusive records such as ‘assumed asbestos’ in difficult to access areas, by undertaking additional sampling

with lifting devices.5. In compliance with WHS Act 2011 and WHS Regulations 2017, additional inspections have been undertaken in ceiling spaces and sub-floor areas where

access is possible.Where the ground floor is slab on ground, no inspection is made beneath the slab.Where fibro fragments (ACM taken for sampling) are located in ceiling spaces or sub floor voids air monitoring is normally undertaken at time ofsampling, and clearance undertaken as soon as practicable.

6. No attempt has been made to identify any ACM that is hidden from view or encapsulated withinAny wall cavitySub floor area, particularly formwork for slabs in/on ground,Services (that may use ACM) such as: pipe lagging, asbestos cement pipes, flues.

7. All known ACM in Grounds (Fibro in Grounds) is made available in associated site specific asbestos management plans in DoE electronic files.Notwithstanding information provided, ACM may be present in grounds from time to time and caution must be exercised prior to any grounds disturbance.

Use of the Asbestos RegisterPrior to any disturbance works being undertaken in a building to which this asbestos register applies it will be necessary to confirm the extent of any ACM by adisturbance investigation:

If the building was built prior to 2003If any ACM has been identified in the Asbestos Register for the building.

Update of Asbestos RegistersAsbestos Register Data is updated regularly by the DoE Hygienist Panel via the Online Asbestos Register Tool (Managed by Business Systems, SchoolInfrastructure NSW). Internal users can view the latest edition of the Asbestos Register in the AMS.

Please note: The Department's external website may not contain the latest revision of the Asbestos Register.

Notes 1: VermiculiteDuring 2018/19, all vermiculite occurrences in DoE schools identified in 2007/08, were ‘composite tested’ in accordance with a safe work NSW agreedprocedure. This required multiple testing of all vermiculite occurrences.During the period 2007/08 to 2018/19, some vermiculite has been over sheeted and a warning is indicated for schools where this has happened.

Note 2: DoE website link for information is here:https://www.schoolinfrastructure.nsw.gov.au/about-us/workingwithus/schools-asbestos-register.html https://education.nsw.gov.au/about-us/strategies-and-reports/our-reports-and-reviews/schools-asbestos-register

Note 3: Material Condition AssessmentThe material condition assessment descriptors from Section 3 of the Asbestos Management Plan (AMP) is extracted below. Please read the AMP in its entirety forfurther information.

3.3.2.1 Material condition assessment

The OART records the material condition of identified ACM in the following format:

Rating Description

Good condition (1) For non-friable asbestos that is sealed and has no visible damage. This primarily related to asbestos cement (AC) sheet and vinyl tiles

Minimal damage (2) For non-friable asbestos that has a very small amount of damage, eg hairline cracks.

Some damage /unsealed (3)

For non-friable asbestos with significant breakage or several small areas where material has been damaged, revealing loose asbestosfibres. Non-friable asbestos that is unsealed.

Poor condition (4) For non-friable asbestos that has extensive damage. Visible asbestos debris

Friable asbestos (5) Any occurrence of friable asbestos

Erina High School (8405) 9/09/2020 2/25

Page 3: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

Note: No inspection of live electrical installation

Product Material Description Extent Location MaterialCondition

RiskStatus

RemediationPriority

Result

B00A - General Learning - 1964 - Brick/BlockExterior

Eaves Linings Flat AC Sheeting 96m2 Throughout, Upper portion,Middle portion

GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Expansion Joint Mastic 200 Variable positions MinimalDamage (2)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Ceiling Voids No Asbestos Found

Underfloor Voids AC Fragments/Debris 5 Variable positions SomeDamage -Unsealed (3)

Low (1) MediumPriority (4-5)

Chrysotile (white asbestos) ,Amosite (brown asbestos) ,Crocidolite (blue asbestos)

Interior

B00A - R0006 - Distribution Board Cupboard - .58 m2

Wall Linings Internal Flat AC Sheeting 2m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

Wall Linings Internal- Electrical Box /Cabinet

Flat AC Sheeting - Profiled 2.00m2 Throughout MinimalDamage (2)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00A - R0010 - Senior Study - 85.41 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 70 - 120 m2) - (X8 )

B00A - R0011 - Seminar - 27.38 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 10 - 40 m2) - (X3 )

Floor CoveringsRes/Textile

Vinyl Tiles 28m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Tiles - Adhesive

B00A - R0012 - Staff - Toilet - 4.14 m2

No Asbestos

B00A - R0013 - Cleaning Store - Distributed - 1.85 m2

No Asbestos

B00A - R0014 - Sport Equipment Store - 26.21 m2

CeilingStructures/Linings

Flat AC Sheeting 27m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Wall Linings Internal Flat AC Sheeting 28m2 East GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00A - R0015 - Main Switchroom - 6.84 m2

CeilingStructures/Linings

Flat AC Sheeting 7m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Electrical - BackingBoard

Resinous Membrane 1 North GoodCondition (1)

Medium(2)

Low Priority(2-3)

Assumed Asbestos

B00A - R0016 - Movement - 95.44 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 70 - 120 m2) - (X8 )

B00A - R0017 - Cleaning Store - Distributed - 2.82 m2

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

3.00m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00A - R0018 - Staff - Toilet - 3.29 m2

No Asbestos

B00A - R0019 - Movement - 21.46 m2

No Asbestos

B00A - R0020 - Movement - 39.85 m2

Erina High School (8405) 9/09/2020 3/25

Page 4: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

CeilingStructures/Linings

Flat AC Sheeting 40m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00A - R0021 - Stairs - 4.39 m2

No Asbestos

B00A - R0022 - Pantry - 4.22 m2

No Asbestos

B00A - R0023 - Laundry - 2.77 m2

No Asbestos

B00A - R0024 - Food/Research Space - 18.97 m2

No Asbestos

B00A - R0025 - Food Technology L.S. - 75.42 m2

No Asbestos

B00A - R0026 - Seminar/Technology Space - 38.47 m2

No Asbestos

B00A - R0027 - General Learning Space - Type 13 - 72.56 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 70 - 120 m2) - (X8 )

B00A - R0028 - Staff Study - 39.2 m2

CeilingStructures/Linings

No Asbestos Found

B00A - R0029 - Stairs - 4.46 m2

No Asbestos

B00A - R1001 - Cleaning Store - Distributed - 1.87 m2

CeilingStructures/Linings

Flat AC Sheeting 1.87m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00A - R1002 - General Storeroom - 4.13 m2

CeilingStructures/Linings

Flat AC Sheeting 5m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Tiles - Adhesive

Floor CoveringsRes/Textile

Vinyl Tiles 4.13m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00A - R1003 - General Learning Space - 66.87 m2

Floor CoveringsRes/Textile

Vinyl Sheet

Floor CoveringsRes/Textile

Vinyl Sheet - Adhesive

B00A - R1004 - General Storeroom - 8.4 m2

CeilingStructures/Linings

Flat AC Sheeting 9m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Sheet

Floor CoveringsRes/Textile

Vinyl Sheet - Adhesive

B00A - R1005 - General Learning Space - 52.49 m2

Floor CoveringsRes/Textile

Vinyl Sheet

Floor CoveringsRes/Textile

Vinyl Sheet - Adhesive

B00A - R1006 - General Storeroom - 3.83 m2

CeilingStructures/Linings

Flat AC Sheeting 4m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Sheet

Floor CoveringsRes/Textile

Vinyl Sheet - Adhesive

Erina High School (8405) 9/09/2020 4/25

Page 5: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

Note: No inspection of live electrical installation

B00A - R1007 - General Learning Space - 52.56 m2

Floor CoveringsRes/Textile

Vinyl Sheet

Floor CoveringsRes/Textile

Vinyl Sheet - Adhesive

B00A - R1008 - Distribution Board Cupboard - .21 m2

Wall Linings Internal Flat AC Sheeting 2m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

Electrical - BackingBoard

Resinous Board 1 North GoodCondition (1)

Low (1) Low Priority(2-3)

Assumed Asbestos

B00A - R1009 - General Storeroom - 5.47 m2

CeilingStructures/Linings

Flat AC Sheeting 6m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Sheet

Floor CoveringsRes/Textile

Vinyl Sheet - Adhesive

B00A - R1010 - General Learning Space - 52.63 m2

Floor CoveringsRes/Textile

Vinyl Sheet

Floor CoveringsRes/Textile

Vinyl Sheet - Adhesive

B00A - R1011 - General Storeroom - 6.22 m2

CeilingStructures/Linings

Flat AC Sheeting 7m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Sheet

Floor CoveringsRes/Textile

Vinyl Sheet - Adhesive

B00A - R1012 - General Learning Space - 52.78 m2

Floor CoveringsRes/Textile

Vinyl Sheet

Floor CoveringsRes/Textile

Vinyl Sheet - Adhesive

B00A - R1013 - General Storeroom - 12.48 m2

CeilingStructures/Linings

Flat AC Sheeting 13m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Sheet

Floor CoveringsRes/Textile

Vinyl Sheet - Adhesive

B00A - R1014 - Seminar - 26.13 m2

No Asbestos

B00A - R1015 - Staff Study - 27.23 m2

Floor CoveringsRes/Textile

Vinyl Sheet

Floor CoveringsRes/Textile

Vinyl Sheet - Adhesive

B00A - R1016 - Cleaning Store - Distributed - 6.28 m2

CeilingStructures/Linings

Flat AC Sheeting 7m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00A - R1017 - External Movement - 132.55 m2

CeilingStructures/Linings

Flat AC Sheeting 133m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00A - R1018 - External Stairs - 6.32 m2

CeilingStructures/Linings

Flat AC Sheeting 6.32m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00A - R1019 - External Stairs - 6.35 m2

Erina High School (8405) 9/09/2020 5/25

Page 6: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

CeilingStructures/Linings

Flat AC Sheeting 7m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00B - Pupil Facilities - 1983 - Brick/BlockExterior

Ceiling Voids - FlatRoof

No Asbestos Found

Underfloor Voids -Slab on Ground

No Asbestos Found

Eaves Linings Flat AC Sheeting 50m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Interior

B00B - R0002 - General Storeroom - 6.39 m2

CeilingStructures/Linings

Flat AC Sheeting 7m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00B - R0003 - Shower/Change - 42.75 m2

No Asbestos

B00B - R0004 - Maintenance Bulk Store - 21.93 m2

No Asbestos

B00B - R0005 - Cleaning Store - Distributed - 3.56 m2

No Asbestos

B00B - R0009 - Shower/Change - 43.23 m2

Partition Walls(Cubicles)

Compressed AC Sheet 24m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00B - R0010 - General Storeroom - 4.11 m2

Floor CoveringsRes/Textile

Vinyl Tiles 5m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

CeilingStructures/Linings

Flat AC Sheeting 5m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00B - R0011 - Staff Shower - 1.96 m2

No Asbestos

B00B - R0013 - Movement - 354.79 m2

CeilingStructures/Linings

Flat AC Sheeting 20m2 East and West GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00B - R0014 - Sport Equipment Store - 7.78 m2

No Asbestos

B00B - R0015 - Garden Store Room - 10.42 m2

No Asbestos

B00B - R0016 - Staff - Toilet - 2.36 m2

CeilingStructures/Linings

Flat AC Sheeting 3m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00B - R0017 - Sport Equipment Store - 15.25 m2

No Asbestos

B00B - R0020 - External Movement - 5.57 m2

CeilingStructures/Linings

Flat AC Sheeting 6m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00B - R0022 - Toilets-Girls - 23.84 m2

No Asbestos

B00B - R0023 - Cleaning Store - Distributed - 4.44 m2

No Asbestos

B00B - R0024 - Toilets-Girls - 48.14 m2

No Asbestos

B00B - R0025 - Toilets-Boys - 54.57 m2

No Asbestos

B00B - R0026 - Toilets-Boys - 33.44 m2

No Asbestos

Erina High School (8405) 9/09/2020 6/25

Page 7: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

Note: No inspection of live electrical installation

B00B - R0027 - Bulk Store - 4.84 m2

No Asbestos

B00B - R0028 - Student Canteen - 52.76 m2

No Asbestos

B00B - R0029 - Pantry - 14.04 m2

No Asbestos

B00B - R0030 - Plant - 22.16 m2

No Asbestos

B00B - R0031 - Plant - 7.19 m2

No Asbestos

B00B - R0032 - External Movement - 103.45 m2

No Asbestos

B00B - R0033 - Gymnasium - 131.93 m2

No Asbestos

B00C - Art/Technological & Applied Studies - 1964 - Brick/BlockExterior

Eaves Linings Flat AC Sheeting

Ceiling Voids No Asbestos Found

Underfloor Voids -Slab on Ground

No Asbestos Found

Interior

B00C - R0001 - Materials Store - 19.26 m2

No Asbestos

B00C - R0004 - Staff - Toilet - 4.12 m2

No Asbestos

B00C - R0007 - Distribution Board Cupboard - .33 m2

No Asbestos

B00C - R0008 - Materials Technology L.S. - 93.42 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 70 - 120 m2) - (X8 )

B00C - R0011 - Movement - 20.67 m2

No Asbestos

B00C - R0012 - Resources Store - 2.23 m2

No Asbestos

B00C - R0013 - Staff - Toilet - 3.65 m2

No Asbestos

B00C - R0014 - Stairs - 3.84 m2

No Asbestos

B00C - R0016 - Stairs - .87 m2

No Asbestos

B00C - R0018 - Materials Store - 7.98 m2

No Asbestos

B00C - R0019 - Darkroom Space - 18.49 m2

No Asbestos

B00C - R0020 - External Movement - 7.97 m2

No Asbestos

B00C - R0021 - Movement - 25.45 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 10 - 40 m2) - (X3 )

B00C - R0022 - Wood Technology L.S. - 128.26 m2

No Asbestos

Erina High School (8405) 9/09/2020 7/25

Page 8: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

B00C - R0023 - Project Store - Type 1 - 24.82 m2

No Asbestos

B00C - R0024 - Outdoor Workshop - 77.19 m2

No Asbestos

B00C - R0025 - Materials Store - Type 1 - 10.44 m2

No Asbestos

B00C - R1001 - Resources Store - 1.8 m2

CeilingStructures/Linings

Flat AC Sheeting 2m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Tiles 2m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00C - R1003 - Resources Store - 4.14 m2

CeilingStructures/Linings

Flat AC Sheeting 5.00m2 Throughout MinimalDamage (2)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00C - R1005 - Kiln Space - 19.06 m2

No Asbestos

B00C - R1006 - Resources Store - 6.25 m2

CeilingStructures/Linings

Flat AC Sheeting 7m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00C - R1007 - Staff Study - 27.08 m2

No Asbestos

B00C - R1008 - External Movement - 89.94 m2

CeilingStructures/Linings

Flat AC Sheeting 90m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Wall Linings Internal- Infill

Flat AC Sheeting 2m2 West, Upper portion GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00C - R1009 - General Storeroom - 4.16 m2

CeilingStructures/Linings

Flat AC Sheeting 5.00m2 Throughout MinimalDamage (2)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00C - R1010 - Cleaning Store - Distributed - 1.84 m2

CeilingStructures/Linings

Flat AC Sheeting 2m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00C - R1011 - External Stairs - 7.91 m2

CeilingStructures/Linings

Flat AC Sheeting 8m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00C - R1012 - External Stairs - 7.9 m2

CeilingStructures/Linings

Flat AC Sheeting 8m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00C - R1013 - General Learning Space - 66.18 m2

No Asbestos

B00C - R1014 - Dark Room - 23.41 m2

No Asbestos

B00C - R1015 - General Learning Space - 68.85 m2

No Asbestos

B00D - Various - 1964 - Brick/BlockExterior

Eaves Linings Flat AC Sheeting 96m2 Throughout, Upper portion,Middle portion

GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

Ceiling Voids No Asbestos Found

Underfloor Voids -Slab on Ground

No Asbestos Found

Interior

B00D - R0001 - Cleaning Store - Distributed - 1.84 m2

No Asbestos

B00D - R0002 - Staff - Toilet - 4.14 m2

Erina High School (8405) 9/09/2020 8/25

Page 9: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

Note: No inspection of live electrical installation

No Asbestos

B00D - R0003 - Movement - 20.85 m2

No Asbestos

B00D - R0004 - General Learning Space - 53.66 m2

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

54m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 40 - 70 m2) - (X5 )

B00D - R0005 - General Learning Space - 65.94 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 40 - 70 m2) - (X5 )

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

66m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00D - R0006 - Commonroom - 139.14 m2

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

139m2 West GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 120 - 250 m2) - (X15 )

B00D - R0007 - Distribution Board Cupboard - .24 m2

Wall Linings Internal Flat AC Sheeting 4.00m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

Electrical - BackingBoard

Resinous Board 1.00 North GoodCondition (1)

Low (1) Low Priority(2-3)

Assumed Asbestos

B00D - R0008 - Duplicating Workroom - 31.29 m2

Floor CoveringsRes/Textile

Vinyl Tiles 32m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 10 - 40 m2) - (X3 )

B00D - R0009 - Staff Study - 26.9 m2

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

27m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 10 - 40 m2) - (X3 )

B00D - R0010 - Movement - 81.51 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 70 - 120 m2) - (X8 )

B00D - R0011 - Movement - 40.88 m2

CeilingStructures/Linings

Flat AC Sheeting 20m2 West GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00D - R0012 - Staff - Toilet - 4.05 m2

No Asbestos

B00D - R0013 - Cleaning Store - Distributed - 1.87 m2

No Asbestos

B00D - R0014 - General Storeroom - 33.85 m2

CeilingStructures/Linings

Flat AC Sheeting 34m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00D - R0015 - Movement - 4.26 m2

CeilingStructures/Linings

Flat AC Sheeting

B00D - R0016 - Stairs - 4.93 m2

No Asbestos

B00D - R0017 - Stairs - 4.83 m2

No AsbestosErina High School (8405) 9/09/2020 9/25

Page 10: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

Note: No inspection of live electrical installation

B00D - R1001 - Cleaning Supplies Store - 1.84 m2

CeilingStructures/Linings

Flat AC Sheeting 2m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

Floor CoveringsRes/Textile

Vinyl Tiles 2m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00D - R1002 - Cleaning Supplies Store - 4.16 m2

CeilingStructures/Linings

Flat AC Sheeting 5m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00D - R1003 - General Learning Space - 53.66 m2

No Asbestos

B00D - R1004 - General Storeroom - 6.04 m2

CeilingStructures/Linings

Flat AC Sheeting 7m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00D - R1005 - General Learning Space - 53.22 m2

No Asbestos

B00D - R1006 - General Storeroom - 6.26 m2

CeilingStructures/Linings

Flat AC Sheeting 7m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00D - R1007 - General Learning Space - 65.79 m2

No Asbestos

B00D - R1008 - General Storeroom - 6.21 m2

No Asbestos

B00D - R1009 - Distribution Board Cupboard - .22 m2

Wall Linings Internal Flat AC Sheeting 2m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

Electrical - BackingBoard

Resinous Board 1 North GoodCondition (1)

Low (1) Low Priority(2-3)

Assumed Asbestos

B00D - R1010 - General Storeroom - 2.61 m2

CeilingStructures/Linings

Flat AC Sheeting

B00D - R1011 - General Learning Space - 65.79 m2

No Asbestos

B00D - R1012 - General Storeroom - 3.03 m2

CeilingStructures/Linings

Flat AC Sheeting

B00D - R1013 - General Learning Space - 53.87 m2

No Asbestos

B00D - R1014 - Cleaning Supplies Store - 6.26 m2

CeilingStructures/Linings

Flat AC Sheeting 7m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00D - R1015 - External Movement - 117.91 m2

CeilingStructures/Linings

Flat AC Sheeting 118m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00D - R1016 - External Stairs - 7.87 m2

CeilingStructures/Linings

Flat AC Sheeting 8m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00D - R1017 - External Stairs - 7.87 m2

CeilingStructures/Linings

Flat AC Sheeting 8m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00E - Administration - 1964 - Brick/BlockExterior

Ceiling Voids No Asbestos Found

Wall Linings Internal- Mastic

Mastic 100 East and West MinimalDamage (2)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Erina High School (8405) 9/09/2020 10/25

Page 11: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

Note: No inspection of live electrical installation

Underfloor Voids AC Fragments/Debris 2 Variable positions SomeDamage -Unsealed (3)

Low (1) MediumPriority (4-5)

Chrysotile (white asbestos) ,Amosite (brown asbestos) ,Crocidolite (blue asbestos)

Eaves Linings Flat AC Sheeting 200m2 Throughout MinimalDamage (2)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

External RoofStructure

Corrugated AC Sheeting 200 Throughout MinimalDamage (2)

Low (1) Low Priority(2-3)

Assumed Asbestos

Interior

B00E - R0001 - Ancillary Staff - 18.73 m2

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

19m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Tiles - Adhesive

B00E - R0002 - Staff - Toilet - 8.35 m2

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

5m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

9m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Tiles - null

Floor CoveringsRes/Textile

Vinyl Tiles - null

B00E - R0003 - Distribution Board Cupboard - .2 m2

Electrical - MountingBoard

Resinous Board 1 North GoodCondition (1)

Low (1) Low Priority(2-3)

Assumed Asbestos

Electrical - Capacitor Insulation Material

B00E - R0004 - Staff - Toilet - 8.68 m2

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

5.00m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Tiles - Adhesive

B00E - R0005 - Principal Office - 18.22 m2

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

19m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Tiles - Adhesive

B00E - R0006 - Staff - Toilet - 5.36 m2

No Asbestos

B00E - R0007 - Cleaning Store - Distributed - 3.16 m2

CeilingStructures/Linings

Flat AC Sheeting

B00E - R0008 - General Storeroom - 8.77 m2

CeilingStructures/Linings

Flat AC Sheeting

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

9.00m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Tiles - Adhesive

B00E - R0009 - Deputy Principal Office - 18.73 m2

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

19m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Tiles - Adhesive

Floor CoveringsRes/Textile

Vinyl Tiles - Adhesive

B00E - R0010 - Interview/Office - Type 1 - 10.32 m2

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

11m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Erina High School (8405) 9/09/2020 11/25

Page 12: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

Floor CoveringsRes/Textile

Vinyl Tiles - Adhesive

CeilingStructures/Linings

No Asbestos Found

Floor CoveringsRes/Textile

Vinyl Tiles - Adhesive

B00E - R0011 - Clinic - Boys - 10.28 m2

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

11m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Tiles - Adhesive

CeilingStructures/Linings

No Asbestos Found

B00E - R0013 - Administration - Clerical - 9.3 m2

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

10m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Tiles - Adhesive

B00E - R0014 - Administration - Clerical - 19.5 m2

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

20m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Tiles - Adhesive

B00E - R0015 - Administration - Clerical - 13.78 m2

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

14m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Tiles - Adhesive

B00E - R0016 - Leading Teacher - 23.8 m2

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

24m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Tiles - Adhesive

B00E - R0017 - Interview/Office - Type 1 - 14.19 m2

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

15m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Tiles - Adhesive

B00E - R0018 - Interview/Office - Type 1 - 14.67 m2

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

15m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Floor CoveringsRes/Textile

Vinyl Tiles - Adhesive

B00E - R0021 - Movement - 6.81 m2

CeilingStructures/Linings

Flat AC Sheeting

B00E - R0022 - Movement - 13.88 m2

No Asbestos

B00E - R0023 - Public Entry - 10.4 m2

No Asbestos

B00E - R0024 - Movement - 33.79 m2

No Asbestos

B00E - R0025 - Interview/Meeting - 9.43 m2

No Asbestos

B00E - R0026 - Movement - 30.8 m2

No Asbestos

B00E - R0027 - Toilets-Disabled - 8.35 m2

Erina High School (8405) 9/09/2020 12/25

Page 13: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

Note: No inspection of live electrical installation

No Asbestos

B00E - R0028 - External Movement - 16.3 m2

CeilingStructures/Linings

Flat AC Sheeting 17m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos) ,Crocidolite (blue asbestos)

B00F - Various - 1964 - Brick/BlockExterior

Eaves Linings Flat AC Sheeting

Ceiling Voids No Asbestos Found

Underfloor Voids -Slab on Ground

No Asbestos Found

Interior

B00F - R0001 - Cleaning Store - Distributed - 1.85 m2

Floor CoveringsRes/Textile

Vinyl Tiles 2.00m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00F - R0002 - Staff - Toilet - 4.12 m2

No Asbestos

B00F - R0003 - Movement - 21.3 m2

No Asbestos

B00F - R0004 - Laboratory L.S. - 93.29 m2

No Asbestos

B00F - R0007 - Laboratory L.S. - 92.27 m2

No Asbestos

B00F - R0008 - Distribution Board Cupboard - .46 m2

Wall Linings Internal Flat AC Sheeting 3.00m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

Electrical - BackingBoard

Resinous Board 1.00 North GoodCondition (1)

Low (1) Low Priority(2-3)

Assumed Asbestos

B00F - R0009 - Computer Learning Space - 65.24 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 40 - 70 m2) - (X5 )

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

66m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00F - R0010 - Staff Study - 26.86 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 10 - 40 m2) - (X3 )

B00F - R0011 - External Movement - 83.72 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 70 - 120 m2) - (X8 )

B00F - R0012 - Staff - Toilet - 4.14 m2

No Asbestos

B00F - R0013 - Cleaning Store - Distributed - 1.84 m2

Floor CoveringsRes/Textile

Vinyl Tiles 2.00m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00F - R0014 - General Assistants - 29.78 m2

CeilingStructures/Linings

Flat AC Sheeting 30m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00F - R0015 - Movement - 44.73 m2

CeilingStructures/Linings

Flat AC Sheeting 45m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00F - R0016 - Stairs - 4.95 m2

No Asbestos

B00F - R0017 - Stairs - 4.39 m2

Erina High School (8405) 9/09/2020 13/25

Page 14: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

Note: No inspection of live electrical installation

No Asbestos

B00F - R0018 - Preparation - Science - 39.02 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 40 - 70 m2) - (X5 )

B00F - R1001 - Cleaning Store - Distributed - 1.8 m2

CeilingStructures/Linings

Flat AC Sheeting 2m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00F - R1002 - General Storeroom - 4.14 m2

CeilingStructures/Linings

Flat AC Sheeting 5m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00F - R1003 - Art Learning Space - 60.08 m2

Floor CoveringsRes/Textile

Vinyl Tiles 61.00m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00F - R1004 - Kiln Space - 21.36 m2

Floor CoveringsRes/Textile

Vinyl Tiles 22.00m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00F - R1005 - Resources Store - 10.52 m2

CeilingStructures/Linings

Flat AC Sheeting 11m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00F - R1006 - General Learning Space - 65.85 m2

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

66.00m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00F - R1007 - General Learning Space - 65.99 m2

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

66.00m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00F - R1008 - General Storeroom - 5.41 m2

CeilingStructures/Linings

Flat AC Sheeting 6m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00F - R1009 - Distribution Board Cupboard - .51 m2

Wall Linings Internal Flat AC Sheeting 3.00m2 Throughout SomeDamage -Unsealed (3)

Low (1) MediumPriority (4-5)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

Electrical - BackingBoard

Resinous Board 1.00 North GoodCondition (1)

Low (1) Low Priority(2-3)

Assumed Asbestos

B00F - R1010 - Computer Learning Space - 52.85 m2

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

53m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00F - R1011 - Computer Store - 6.02 m2

CeilingStructures/Linings

Flat AC Sheeting 7m2 Throughout MinimalDamage (2)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00F - R1012 - Staff Study - 26.72 m2

Floor CoveringsRes/Textile

Vinyl Tiles (Under FloorCovering/Carpet)

27m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00F - R1013 - Cleaning Supplies Store - 6.25 m2

CeilingStructures/Linings

Flat AC Sheeting 7m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00F - R1014 - External Movement - 118.55 m2

CeilingStructures/Linings

Flat AC Sheeting 119m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

Wall Linings Internal- Infill

Flat AC Sheeting 2m2 East GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00F - R1015 - External Movement - 17.46 m2

Wall Linings Internal Flat AC Sheeting

B00F - R1016 - External Stairs - 7.88 m2

CeilingStructures/Linings

Flat AC Sheeting 8m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00F - R1017 - External Stairs - 7.88 m2Erina High School (8405) 9/09/2020 14/25

Page 15: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

Note: No inspection of live electrical installation

CeilingStructures/Linings

Flat AC Sheeting 8m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00G - Multi Purpose Facilities - 1954 - Brick/BlockExterior

Wall Linings Internal- Infill

Flat AC Sheeting

Ceiling Voids - FlatRoof

No Asbestos Found

Underfloor Voids -Slab on Ground

No Asbestos Found

Interior

B00G - M0001 - Control Room - 5.48 m2

Door - Insulation Insulation Material 1 East SomeDamage -Unsealed (3)

Medium(2)

MediumPriority (4-5)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00G - M0002 - Shower/Change - 45.67 m2

Wall Linings Internal Flat AC Sheeting

Partition Walls(Cubicles)

Compressed AC Sheet

B00G - M0003 - Shower/Change - 45.67 m2

Wall Linings Internal Flat AC Sheeting

Partition Walls(Cubicles)

Compressed AC Sheet

B00G - M0004 - Cleaning Store - Distributed - 5.48 m2

No Asbestos

B00G - M0005 - Movement - 2.19 m2

No Asbestos

B00G - M0006 - Movement - 2.19 m2

No Asbestos

B00G - M0007 - Multi-Purpose Space - 77.08 m2

No Asbestos

B00G - M0008 - Control Room - 7.78 m2

No Asbestos

B00G - M0009 - Stairs - 8.1 m2

No Asbestos

B00G - M0010 - Stairs - 8.26 m2

No Asbestos

B00G - M0011 - Stairs - 1.46 m2

No Asbestos

B00G - M0012 - Stairs - 1.53 m2

No Asbestos

B00G - R0001 - Chair Store - 30.6 m2

No Asbestos

B00G - R0002 - Toilets-Girls - 20.3 m2

Partition Walls(Cubicles)

Compressed AC Sheet

B00G - R0003 - Stage - 94.25 m2

Door - Insulation Insulation Material 2 East SomeDamage -Unsealed (3)

Medium(2)

MediumPriority (4-5)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00G - R0004 - Movement - 17.89 m2

Wall Linings Internal Flat AC Sheeting

B00G - R0005 - Distribution Board Cupboard - .33 m2

Electrical - BackingBoard

Resinous Board 1 North GoodCondition (1)

Low (1) Low Priority(2-3)

Assumed Asbestos

Erina High School (8405) 9/09/2020 15/25

Page 16: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

B00G - R0006 - Toilets-Boys - 19.35 m2

Partition Walls(Cubicles)

Compressed AC Sheet

B00G - R0007 - Sport Equipment Store - 31.59 m2

No Asbestos

B00G - R0008 - Self Help Toilet - 4.39 m2

No Asbestos

B00G - R0009 - Staff Shower - 6.95 m2

No Asbestos

B00G - R0010 - Student Canteen - 11.19 m2

No Asbestos

B00G - R0011 - Performing Arts Store - 22.07 m2

No Asbestos

B00G - R0012 - Multi-Purpose Space - 469.81 m2

No Asbestos

B00G - R0014 - Stairs - 1.03 m2

No Asbestos

B00G - R0015 - Stairs - 1.04 m2

No Asbestos

B00G - R0016 - Plant - .39 m2

No Asbestos

B00G - R0017 - External Movement - 44.78 m2

CeilingStructures/Linings

Flat AC Sheeting

B00G - R0018 - Stairs - .87 m2

No Asbestos

B00G - R0019 - Stairs - .87 m2

No Asbestos

B00H - Various - 1964 - Brick/BlockExterior

Wall Linings Internal- Infill

Flat AC Sheeting 2 East, Upper portion, Middleportion

GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Ceiling Voids No Asbestos Found

Underfloor Voids No Asbestos Found

Eaves Linings Flat AC Sheeting

Interior

B00H - R0001 - Cleaning Store - Distributed - 1.84 m2

Floor CoveringsRes/Textile

Vinyl Tiles 2.00m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00H - R0002 - Staff - Toilet - 4.14 m2

No Asbestos

B00H - R0003 - Movement - 20.65 m2

No Asbestos

B00H - R0004 - General Storeroom - 8.9 m2

No Asbestos

B00H - R0005 - Staff Study - 39.71 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 40 - 70 m2) - (X5 )

B00H - R0006 - Food Technology L.S. - 65.35 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 40 - 70 m2) - (X5 )

B00H - R0007 - Seminar - 12.67 m2

Erina High School (8405) 9/09/2020 16/25

Page 17: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

Note: No inspection of live electrical installation

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 10 - 40 m2) - (X3 )

B00H - R0008 - Laundry - 25.8 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 10 - 40 m2) - (X3 )

B00H - R0009 - Food/Research Space - 12.67 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 10 - 40 m2) - (X3 )

B00H - R0010 - Study Space - 6.23 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( < 10 m2) - ( X2 )

B00H - R0011 - General Storeroom - 5.62 m2

No Asbestos

B00H - R0012 - Distribution Board Cupboard - .52 m2

Wall Linings Internal Flat AC Sheeting 3.00m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

Electrical - BackingBoard

Resinous Board 1.00 South GoodCondition (1)

Low (1) Low Priority(2-3)

Assumed Asbestos

B00H - R0013 - Design L.S. - 65.94 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 40 - 70 m2) - (X5 )

B00H - R0014 - General Storeroom - 6.79 m2

No Asbestos

B00H - R0015 - General Learning Space - 54.02 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 40 - 70 m2) - (X5 )

B00H - R0016 - General Storeroom - 5.52 m2

No Asbestos

B00H - R0017 - Movement - 84.99 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 70 - 120 m2) - (X8 )

B00H - R0018 - Staff - Toilet - 4.14 m2

No Asbestos

B00H - R0019 - Cleaning Store - Distributed - 1.84 m2

No Asbestos

B00H - R0020 - Maintenance Bulk Store - 29.78 m2

CeilingStructures/Linings

Flat AC Sheeting 30m2 West GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00H - R0021 - Movement - 44.68 m2

CeilingStructures/Linings

Flat AC Sheeting 20m2 West GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00H - R0022 - Stairs - 5 m2

No Asbestos

B00H - R0023 - Stairs - 5.02 m2

No Asbestos

B00H - R1001 - Cleaning Store - Distributed - 1.84 m2

No Asbestos

B00H - R1002 - General Storeroom - 4.14 m2

No Asbestos

B00H - R1003 - Staff Study - 26.9 m2

Erina High School (8405) 9/09/2020 17/25

Page 18: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

Note: No inspection of live electrical installation

Floor CoveringsRes/Textile

Vinyl Sheet

Floor CoveringsRes/Textile

Vinyl Sheet - Adhesive

B00H - R1004 - General Learning Space - 52.56 m2

Floor CoveringsRes/Textile

Vinyl Sheet

Floor CoveringsRes/Textile

Vinyl Sheet - Adhesive

B00H - R1005 - General Learning Space - 52.56 m2

Floor CoveringsRes/Textile

Vinyl Sheet

Floor CoveringsRes/Textile

Vinyl Sheet - Adhesive

B00H - R1006 - General Learning Space - 52.62 m2

Floor CoveringsRes/Textile

Vinyl Sheet

Floor CoveringsRes/Textile

Vinyl Sheet - Adhesive

B00H - R1007 - Distribution Board Cupboard - .51 m2

Wall Linings Internal Flat AC Sheeting 3.00m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

Electrical - BackingBoard

Resinous Board 1.00 South GoodCondition (1)

Low (1) Low Priority(2-3)

Assumed Asbestos

B00H - R1008 - General Learning Space - 52.56 m2

Floor CoveringsRes/Textile

Vinyl Sheet

Floor CoveringsRes/Textile

Vinyl Sheet - Adhesive

B00H - R1009 - General Learning Space - 52.56 m2

Floor CoveringsRes/Textile

Vinyl Sheet

Floor CoveringsRes/Textile

Vinyl Sheet - Adhesive

B00H - R1010 - General Storeroom - 7.82 m2

CeilingStructures/Linings

Flat AC Sheeting 8m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00H - R1011 - Staff Study - 13.36 m2

Floor CoveringsRes/Textile

Vinyl Sheet

Floor CoveringsRes/Textile

Vinyl Sheet - Adhesive

B00H - R1012 - Cleaning Supplies Store - 6.32 m2

CeilingStructures/Linings

Flat AC Sheeting 7m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00H - R1013 - External Movement - 120.49 m2

CeilingStructures/Linings

Flat AC Sheeting 121m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00H - R1014 - External Movement - 20.04 m2

Wall Linings Internal Flat AC Sheeting

B00H - R1015 - External Stairs - 7.66 m2

CeilingStructures/Linings

Flat AC Sheeting 8m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00H - R1016 - External Stairs - 7.88 m2

CeilingStructures/Linings

Flat AC Sheeting 8m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00J - Various - 1964 - Brick/BlockExterior

Erina High School (8405) 9/09/2020 18/25

Page 19: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

Note: No inspection of live electrical installation

Eaves Linings Flat AC Sheeting

Wall Cladding Flat AC Sheeting 26m2 Adjacent JR0001 GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Ceiling Voids No Asbestos Found

Underfloor Voids -Slab on Ground

No Asbestos Found

Interior

B00J - R0001 - Materials Store - 14.82 m2

Wall Linings Internal Flat AC Sheeting 26m2 North, South, East GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00J - R0002 - L.P.G. Store - 1.86 m2

Floor CoveringsRes/Textile

Vinyl Tiles 1m2 North GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00J - R0005 - Materials Technology L.S. - 84.72 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 70 - 120 m2) - (X8 )

B00J - R0008 - Seminar/Technology Space - 45.74 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 40 - 70 m2) - (X5 )

B00J - R0009 - Design/Technology L.S. - 52.46 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 10 - 40 m2) - (X3 )

B00J - R0010 - General Storeroom - 10.92 m2

No Asbestos

B00J - R0011 - General Storeroom - 2.21 m2

Floor CoveringsRes/Textile

Vinyl Tiles 3m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00J - R0012 - Staff - Toilet - 3.78 m2

No Asbestos

B00J - R0013 - Distribution Board Cupboard - .57 m2

Wall Linings Internal Flat AC Sheeting 4.00m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

Plant / Equipment -Electric Off PeakHeater

Resinous Board 1.00 South GoodCondition (1)

Low (1) Low Priority(2-3)

Assumed Asbestos

B00J - R0014 - Movement - 55.74 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 40 - 70 m2) - (X5 )

B00J - R0015 - General Storeroom - 17.67 m2

No Asbestos

B00J - R0016 - Movement - 9.99 m2

No Asbestos

B00J - R0017 - Stairs - 5.03 m2

No Asbestos

B00J - R0019 - General Storeroom - 7.09 m2

No Asbestos

B00J - R0020 - Staff - Toilet - 1.65 m2

No Asbestos

B00J - R0021 - Toilet - Lobby - 2.18 m2

No Asbestos

B00J - R0022 - General Storeroom - 26.61 m2

Erina High School (8405) 9/09/2020 19/25

Page 20: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

Note: No inspection of live electrical installation

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 10 - 40 m2) - (X3 )

B00J - R0023 - Metal Technology Bay - 14.23 m2

No Asbestos

B00J - R0024 - Materials Store - 9.55 m2

Wall Linings Internal Flat AC Sheeting 5.00m2 North GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00J - R0025 - External Movement - 6.16 m2

No Asbestos

B00J - R0026 - Stairs - 1.9 m2

Wall Linings Internal Flat AC Sheeting 2m2 South GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00J - R1001 - General Storeroom - 1.81 m2

CeilingStructures/Linings

Flat AC Sheeting 2m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

Floor CoveringsRes/Textile

Vinyl Tiles 2m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00J - R1002 - General Storeroom - 4.16 m2

CeilingStructures/Linings

Flat AC Sheeting 5m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00J - R1003 - Music Learning Space - 66.36 m2

No Asbestos

B00J - R1004 - Music Store - 21.02 m2

No Asbestos

B00J - R1005 - Practice/Seminar - 30.17 m2

No Asbestos

B00J - R1006 - Music Learning Space - 63.09 m2

No Asbestos

B00J - R1007 - Staff Study - 23.67 m2

CeilingStructures/Linings

Flat AC Sheeting 24m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00J - R1008 - Distribution Board Cupboard - .61 m2

Wall Linings Internal Flat AC Sheeting 4.00m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

Electrical - BackingBoard

Resinous Board 1.00 South GoodCondition (1)

Low (1) Low Priority(2-3)

Assumed Asbestos

B00J - R1009 - General Storeroom - 6.26 m2

CeilingStructures/Linings

Flat AC Sheeting 7m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00J - R1010 - External Movement - 91.24 m2

CeilingStructures/Linings

Flat AC Sheeting 92m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00J - R1011 - External Stairs - 7.88 m2

CeilingStructures/Linings

Flat AC Sheeting 8m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00J - R1012 - External Stairs - 7.87 m2

CeilingStructures/Linings

Flat AC Sheeting 8m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00K - Performing Arts - 1964 - TimberExterior

Ceiling Voids Non Accessible Area

Underfloor Voids No Asbestos Found

Interior

B00K - R0001 - Performing Arts Changeroom - 21.34 m2

Erina High School (8405) 9/09/2020 20/25

Page 21: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

CeilingStructures/Linings

Flat AC Sheeting 22m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00K - R0002 - Performance Workspace - 97.27 m2

CeilingStructures/Linings

Flat AC Sheeting 98m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00K - R0003 - Movement - 3.54 m2

CeilingStructures/Linings

Flat AC Sheeting 4m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos) ,Amosite (brown asbestos)

B00L - Agricultural Science - 1964 - Brick/BlockExterior

Ceiling Voids No Asbestos Found

Underfloor Voids -Slab on Ground

No Asbestos Found

Interior

B00L - R0001 - Staff Study - 5.7 m2

No Asbestos

B00L - R0002 - Staff - Toilet - 2.38 m2

No Asbestos

B00L - R0003 - Class Tools Storage - 12.49 m2

No Asbestos

B00L - R0004 - Machine Storage - 20.98 m2

No Asbestos

B00L - R0005 - General Storeroom - 5.57 m2

No Asbestos

B00L - R0006 - Toilets-Boys - 2.16 m2

No Asbestos

B00L - R0007 - External Movement - 26.98 m2

No Asbestos

B00M - Other - 2006 - Brick/BlockExterior

Ceiling Voids No Asbestos Found

Underfloor Voids No Asbestos Found

Interior

B00M - R0001 - Movement - 3.78 m2

No Asbestos

B00M - R0002 - Lift - 2.13 m2

No Asbestos

B00M - R0003 - Movement - 3.8 m2

No Asbestos

B00M - R1001 - Movement - 3.78 m2

No Asbestos

B00M - R1002 - Lift - 2.13 m2

No Asbestos

B00M - R1003 - Movement - 3.8 m2

No Asbestos

B00N - Science/Library - 1973 - Brick/BlockExterior

Eaves Linings Flat AC Sheeting

Wall Linings Internal- Infill

Flat AC Sheeting 5 East, West, Middle portion,Lower portion, Variablepositions

GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

Ceiling Voids -Raked Ceiling

No Asbestos Found

Erina High School (8405) 9/09/2020 21/25

Page 22: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

Note: No inspection of live electrical installation

Underfloor Voids -Slab on Ground

No Asbestos Found

Interior

B00N - M1001 - Main Area - 143.24 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 10 - 40 m2) - (X3 )

B00N - M1002 - Seminar - 19.19 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 10 - 40 m2) - (X3 )

B00N - M1003 - Teachers Aides - 20.59 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 10 - 40 m2) - (X3 )

B00N - M1004 - Stairs - 2.53 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( < 10 m2) - ( X2 )

B00N - M1005 - Stairs - 2.53 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( < 10 m2) - ( X2 )

B00N - R0001 - Laboratory L.S. - 90.73 m2

Wall Linings Internal Flat AC Sheeting

B00N - R0002 - Laboratory L.S. - 91 m2

Wall Linings Internal Flat AC Sheeting

B00N - R0003 - Preparation - 48.47 m2

Wall Linings Internal Flat AC Sheeting

B00N - R0004 - Laboratory L.S. - 90.64 m2

Wall Linings Internal Flat AC Sheeting

B00N - R0005 - Apparatus Store - 12.1 m2

No Asbestos

B00N - R0006 - Laboratory L.S. - 90.46 m2

Wall Linings Internal Flat AC Sheeting

B00N - R0007 - Distribution Board Cupboard - .36 m2

Electrical - BackingBoard

Resinous Board 1 North GoodCondition (1)

Low (1) Low Priority(2-3)

Assumed Asbestos

B00N - R0008 - Preparation - 48.06 m2

Floor CoveringsRes/Textile

Vinyl Tiles 49m2 Throughout GoodCondition (1)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 40 - 70 m2) - (X5 )

B00N - R0009 - Movement - 40.37 m2

No Asbestos

B00N - R0010 - Cleaning Store - Distributed - 8.08 m2

No Asbestos

B00N - R0011 - Movement - 3.53 m2

No Asbestos

B00N - R0012 - Plant - 13.14 m2

No Asbestos

B00N - R0013 - External Stairs - 8.02 m2

No Asbestos

B00N - R1001 - Main Area - 387.59 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( > 250 m2) - (X25 )

B00N - R1002 - Staff - Toilet - 3.5 m2Erina High School (8405) 9/09/2020 22/25

Page 23: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

Note: No inspection of live electrical installation

Note: No inspection of live electrical installation

Wall Linings Internal- Infill

Flat AC Sheeting 0.5m2 East MinimalDamage (2)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00N - R1003 - Seminar - 12.29 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 10 - 40 m2) - (X3 )

Wall Linings Internal- Infill

Flat AC Sheeting 1m2 West MinimalDamage (2)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00N - R1004 - Seminar - 12.29 m2

Wall Linings Internal- Infill

Flat AC Sheeting 1m2 West MinimalDamage (2)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00N - R1005 - Distribution Board Cupboard - .55 m2

No Asbestos

B00N - R1006 - Cleaning Store - Distributed - 1.89 m2

No Asbestos

B00N - R1007 - Teachers Aides - 11.94 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 10 - 40 m2) - (X3 )

Wall Linings Internal- Infill

Flat AC Sheeting 1m2 East MinimalDamage (2)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00N - R1008 - Distribution Board Cupboard - .55 m2

Electrical - MountingBoard

Resinous Board 1 South GoodCondition (1)

Low (1) Low Priority(2-3)

Assumed Asbestos

B00N - R1009 - Seminar - 12.28 m2

Wall Linings Internal- Infill

Flat AC Sheeting 1m2 East MinimalDamage (2)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00N - R1010 - Seminar - 12.28 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 10 - 40 m2) - (X3 )

Wall Linings Internal- Infill

Flat AC Sheeting 1m2 West MinimalDamage (2)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00N - R1011 - Audio Visual Workroom - 29.04 m2

CeilingStructures/Linings

Vermiculite - CompositeSample - ( 10 - 40 m2) - (X3 )

B00N - R1012 - Librarian - 10.56 m2

CeilingStructures/Linings

No Asbestos Found

B00N - R1013 - Workroom - 20.01 m2

CeilingStructures/Linings

No Asbestos Found

B00N - R1014 - General Storeroom - 7.43 m2

CeilingStructures/Linings

Flat AC Sheeting

Wall Linings Internal Flat AC Sheeting

B00N - R1015 - Staff - Toilet - 3.5 m2

Wall Linings Internal- Infill

Flat AC Sheeting 1m2 East MinimalDamage (2)

Low (1) Low Priority(2-3)

Chrysotile (white asbestos)

B00N - R1016 - External Movement - 2.43 m2

No Asbestos

B00N - R1017 - External Stairs - 17.16 m2

No Asbestos

B00N - R1018 - Stairs - .33 m2

No Asbestos

B00N - R1019 - Stairs - .33 m2

No AsbestosErina High School (8405) 9/09/2020 23/25

Page 24: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

B00O - Other-Community Use - 2009 - Brick/VeneerExterior

Ceiling Voids No Asbestos Found

Underfloor Voids -Slab on Ground

No Asbestos Found

Interior

B00O - R0001 - External Movement - 21.68 m2

No Asbestos

B00O - R0002 - Toilets-Boys - 11.26 m2

No Asbestos

B00O - R0003 - Plant - 7.41 m2

No Asbestos

B00O - R0004 - Toilets-Girls - 16.08 m2

No Asbestos

B00O - R0005 - Change - 25.05 m2

No Asbestos

B00O - R0006 - Change - 25.21 m2

No Asbestos

B00O - R0007 - Staff Kitchen - 18 m2

No Asbestos

B00O - R0008 - No Access - 7.98 m2

No Asbestos

B00O - R0009 - Other-Vacant - 21.15 m2

No Asbestos

B00O - R0010 - No Access - 1.2 m2

No Asbestos

B00P - Other-Vacant - 2009 - Brick/BlockExterior

Ceiling Voids No Asbestos Found

Underfloor Voids -Slab on Ground

No Asbestos Found

Interior

B00P - R0001 - Other-Vacant - 4.55 m2

No Asbestos

B00Q - Mechanical Services - 2013 - Metal ShedExterior

Ceiling Voids - FlatRoof

No Asbestos Found

Underfloor Voids -Slab on Ground

No Asbestos Found

Interior

B00Q - R0001 - Plant - 8.3 m2

No Asbestos

Erina High School (8405) 9/09/2020 24/25

Page 25: Erina High School (8405) · 2020. 11. 24. · Erina High School (8405) 9/09/2020 4/25. Note: No inspection of live electrical installation B00A - R1007 - General Learning Space -

DemountablesThere are no Demountable(s) Located at this school as per the AMS records as of 09-Sep-2020

Erina High School (8405) 9/09/2020 25/25