Process ESD systems
Valve Automation
ESD Systems
In an emergency, the ability to rapidly shut off fluid and/or gas flow can mean the difference between a manageable situation and a potential disaster
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 2
ESD SystemsNPS 24 Failure USA July 2003 Operating pressure: 1040psi
Pipe Blow out , No fire.
A well designed ESD system utilized to section off the pipeline, coupled with the absence of fire, made this one a non event!
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 3
ESD control solutions
20 years ago, a liquid spill or gas released was not a major event. Historically, sectioning valves on tank farms, liquids lines , aggressive pressurized gases etc.. have been electrically actuated due to their remote location. With today's environmental standards and required practices, the need to have ESD capabilities becomes prevalent and changes the operational function of sectioning valves. The lack of spring return capabilities from the different electric actuators designs on the market and its dependence on the supply source to operate and react to any given situation know makes the users vulnerable to dangerous situations and potential environmental catastrophes.
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 4
ESD Systems
How can we define an ESD valve/damper system? A packaged solution or sets of controls configured to make a rotary or linear actuator go to a desired position upon detection of a set or sets of event(s), autonomously or by dedicated signal. Emergency Shutdown (ESD) Valves and other failsafe valves and dampers assemblies, typically incorporate a spring-to-fail actuator to stroke the valve or damper in the event of an upset process condition.
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 5
ESD SystemsSupply
Open Side
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 6
ESD Systems
An actuator using either stored energy or reserved energy and configured to answer to the designation of Emergency Shut Down (ESD) valve will provide protection on; Pipelines Storage facilities in refineries LPG Chemical Tank farm Loading and unloading facilities Process Wellheads Liquids lines
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 7
ESD Systems
Such protection is indispensable on process medias such as; Ammonia Butane Propane Pentane Polypropylene, LNG NGL Mild acids
Diesel fuels Thermal oils Liquefied gasesValve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 8
ESD systems
Typically used on on/off isolation or sectioning valves, controls can be devised to incorporate ESD logic into control valves packages. Most often installed on ball, plug, butterfly, gate and globe valves, solutions can be self contained or integrated into a ESD system. From local to remote triggering, we must first determined the parameter and means by which we will trip the actuator to fail close or open on each applications.
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 9
ESD triggers
Pressure sensing High & Low
All Pressurematic pilot valves provide high and low pressure sensing on gas or liquids and can be fitted with either an automatic or manual reset..
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 10
ESD triggers
Pressure sensing High & Low Pressure sensing High or Low
low (falling) pressure
high (rising) pressure
SP Pressure Pilot valves provide either high or low pressure sensing on gas or liquid and can be fitted with either an automatic or manual reset facility.high (rising) pressure c/w manual reset valve
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 11
ESD triggers
Pressure sensing High & Low Pressure sensing High or Low Fusible link
Fusible links are set to melt and activate an ESD system in the event of fire.
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 12
ESD triggers
Pressure sensing High & Low Pressure sensing High or Low Fusible link ROD (Rate of Drop)
The Bettis Deltamatic linebreak detection system is designed to automatically monitor pressure and send instrument pressure signal if a predetermined rate of pressure drop is exceeded
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 13
ESD triggers
Pressure sensing High & Low Pressure sensing High or Low Fusible link ROD (Rate of Drop) Linebreak system
In anticipation of customer requirements to provide a system that will not only provide linebreak protection but also monitoring and analyses of pressure characteristics, Bettis has designed our next generation electronic linebreak system. The LineGuard system incorporates everything Bettis has learned about pipeline protection which iswell, a lot. Again, Bettis leads the World in valve actuation systems.
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 14
ESD triggers Initiates valve shutdown on set high and low pipeline pressures. Initiates valve shutdown on a set rate of pipeline pressure fall. Monitors (every 5 seconds) and records pipeline pressure to provide a detailed insight into the pipelines operating characteristics prior and post to valve shutdown. Allows optimizing of setpoints for effective linebreak control. Remote communication and control using industry standard MODBUS protocol.LineGuard 2100
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 15
ESD triggers
Pressure sensing High & Low Pressure sensing High or Low Fusible link ROD (Rate of Drop) Linebreak system Hard wired Cellular communication Radio Communication Scada systems
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 16
ESD triggers
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 17
ESD triggers
Pressure sensing High & Low Pressure sensing High or Low Fusible link ROD (Rate of Drop) Linebreak system Hard wired Cellular communication Radio Communication Scada systems Where an independent monitoring systems from the main process system will send the selected valves into ESD mode.
ESD systems
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 18
ESD control solutions
With controls modification we can turn your control valve package into and ESD solution using both spring return actuators and double acting where we can use the line pack as the source of energy when available
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 19
ESD control solutions
ESD
120/60AC
4-20 ma inSupply80psi min 120 psi max
R
F
P4-20 ma out
ESD signal on Linear control valve ESD process & ESD hand pump
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 20
ESD control solutions
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 21
ESD On/Off solutionsThe Valve Automation division offers a complete array of solution with products such as;
Scotch Yoke & Linear DesignsValve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 22
ESD On/Off solutions
SO
Low/high pressure ESD shut off Spring Return Actuator
OPEN
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 23
ESD On/Off solutionsThe Valve Automation division offers a complete array of solution with products such as;
Hydraulic Vane DesignsValve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 24
ESD On/Off solutionsLow/high pressure ESD shut off Double Acting Actuator
SC
SO
CLOSE
OPEN
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 25
ESD On/Off solutionsThe Valve Automation division offers a complete array of solution with products such as;
Helical Spline subsea DesignsValve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 26
ESD On/Off solutionsThe Valve Automation division offers a complete array of solution with products such as;
Rack & Pinion DesignsValve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 27
ESD On/Off solutionsThe Valve Automation division offers a complete array of solution with products such as;
Rack & Pinion DesignsValve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 28
ESD On/Off solutionsThe Valve Automation division offers a complete array of solution with products such as;
Rack & Pinion intelligent solutionsValve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 29
ESD Self contained solutionThe standard SCH control system always requires at least one additional control component to initiate valve shutdown. This type of component is used to initiate the depressurization of the system allowing the actuators spring to move the mainline valve to its failed position. Most common of these shutdown devices are pressure pilot valves, solenoid valves and manual ball valves.The picture shows a Pressurematic Pilot fitted with a manual reset valve (PMR type) being used as the shutdown device.
PressureMatic Pilot Valve c/w Manual Rest
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 30
ESD Self contained solution
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 31
ESD Gas over Oil solutionWhen line pressure exceeds 400 psi, we can look at using the line pressure as the source of energy to drive the actuator
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 32
ESD Gas over Oil solution10 SUPPLYOA U T
12
13
MA
N
UA L
16
25
15 4 CLO SE4
4 OPE N
4
3
3
3
3
7 14 1 6 88 6 1
7
6 88
1234678910141516253537-
OPERA TOR LIN E VA LVE GA S / HYDR AULIC T ANK 3 -W AY VAL VE (MANU AL) SELECTOR VA LVE SPEED CONTROL VALVE C HECK VALVE H AND PUMP FILTER PR ESSU RE PILOT / MAN RESET EN D OF STROKE VALVE M AN UAL SEL ECTO R VALVE R EVER SING RELAY SH UTT LE VA LVE H AND PUMP SAF ETY VA LVE
37
9
OPER AT IO N: - SH OW N W IT H LINE VA LVE O PEN - TW O-WAY MANU AL - PR ESSU RE PILOT - MA NUA L RESET
PIPELINE 22
Valve Automation[File Name or Event] Emerson Confidential 27-Jun-01, Slide 33
Valve Automation division
The most complete offering of actuation concepts and solutions. Torques up to 6,000,000 lb/in From 3,000 meters below sea to the top of your stack, we offer proven and reliable products for all you automation needs!