Evaluation of Chemical and Non-Chemical Treatment Methods for Condenser Water Ng Wai Lun 1 , Yoon Li Wan 1 and Satesh Narayana Namasivayam 1 , Chen Thiam Leong 2 1 School of Engineering, Faculty of Innovation and Technology, Taylor’s University Lakeside Campus, No. 1, Jalan Taylor’s, 47500 Subang Jaya, Selangor, Malaysia. 2 Green Building Index Sdn Bhd, Level 4, PAM Centre, 99L, Jalan Tandok, Bangsar, 59100, Kuala Lumpur, Malaysia *Corresponding author: [email protected] Abstract. In the Heating, Ventilation and Air Conditioning (HVAC) field, condenser water is used to remove heat from the refrigerant cycle and is cooled at cooling towers. Due to the high operating temperatures of 29°C to 38°C, the condenser water cycle is vulnerable to operating issues such as scaling, corrosion and microbiological proliferation; which can be mitigated through either chemical or non-chemical treatment methods. In this paper, the chemical and non-chemical treatment methods for condenser water treatment in the Heating, Ventilation and Air Conditioning (HVAC) systems are compared in terms of efficiency (scaling, corrosion and microbiological proliferation control) and environmental impact. The efficiency of one chemical treatment system (descalant) and three non-chemical treatment systems (Merus Ring, Power Pulsed and Ultra Low Frequency) are investigated by taking condenser water samples from the cooling tower basins biweekly for three months to characterize for pH, water alkalinity, iron content, chloride content, total dissolved solids (TDS) content, electrical conductivity and water hardness, which are compared to the Japan Refrigeration and Air Conditioning Industry Association Standards (JRA-GL-02-1994) and applied to the Langelier Saturation Index (LSI), Ryznar Stability Index (RSI) and Practical (Puckorious) Scaling Index (PSI) to predict the scale formation in condenser water samples. The temperature differences between chilled waters for all systems investigated are recorded to relate the characterized parameters to chiller efficiency. The environmental impacts for all systems investigated are assessed by focusing on the operational stage of all system where the main source of environmental damage is due to the electrical consumption by the HVAC systems. The results yield that all systems investigated comply to the industrial standards. LSI and RSI proved that all condenser waters are saturated with calcium ions but PSI proved that scale formations in the systems investigated are unlikely as the scales are likely to remain dissolved in the condenser water. Consistent temperature differences of chilled water are observed throughout the research period which show that the performance of chillers in each system are optimal, which proves that non-chemical treatment systems are as efficient (in terms of corrosion, scaling and microbial activity control) as chemical treatment system. Environmental impact analysis concluded that chemical treatment system has the highest annual equivalent CO2 emission per cooling capacity of 868.30 kg CO2 e/year RT. Thus, non-chemical treatment systems have lesser environmental impact than chemical treatment system. Key words: HVAC System, Condenser Water Treatment Systems, Corrosion, Scaling, Microbiological Proliferation

Evaluation of Chemical and Non-Chemical Treatment Methods for Condenser Water · 2021. 1. 22. · Evaluation of Chemical and Non-Chemical Treatment Methods for Condenser Water Ng

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

  • Evaluation of Chemical and Non-Chemical Treatment

    Methods for Condenser Water

    Ng Wai Lun1, Yoon Li Wan1 and Satesh Narayana Namasivayam1, Chen Thiam

    Leong2

    1 School of Engineering, Faculty of Innovation and Technology, Taylor’s University Lakeside Campus, No. 1, Jalan

    Taylor’s, 47500 Subang Jaya, Selangor, Malaysia. 2 Green Building Index Sdn Bhd, Level 4, PAM Centre, 99L, Jalan Tandok, Bangsar, 59100, Kuala Lumpur,

    Malaysia

    *Corresponding author: [email protected]

    Abstract. In the Heating, Ventilation and Air Conditioning (HVAC) field, condenser water is used to remove heat from

    the refrigerant cycle and is cooled at cooling towers. Due to the high operating temperatures of 29°C to 38°C, the condenser

    water cycle is vulnerable to operating issues such as scaling, corrosion and microbiological proliferation; which can be

    mitigated through either chemical or non-chemical treatment methods. In this paper, the chemical and non-chemical

    treatment methods for condenser water treatment in the Heating, Ventilation and Air Conditioning (HVAC) systems are

    compared in terms of efficiency (scaling, corrosion and microbiological proliferation control) and environmental impact.

    The efficiency of one chemical treatment system (descalant) and three non-chemical treatment systems (Merus Ring, Power

    Pulsed and Ultra Low Frequency) are investigated by taking condenser water samples from the cooling tower basins

    biweekly for three months to characterize for pH, water alkalinity, iron content, chloride content, total dissolved solids

    (TDS) content, electrical conductivity and water hardness, which are compared to the Japan Refrigeration and Air

    Conditioning Industry Association Standards (JRA-GL-02-1994) and applied to the Langelier Saturation Index (LSI),

    Ryznar Stability Index (RSI) and Practical (Puckorious) Scaling Index (PSI) to predict the scale formation in condenser

    water samples. The temperature differences between chilled waters for all systems investigated are recorded to relate the

    characterized parameters to chiller efficiency. The environmental impacts for all systems investigated are assessed by

    focusing on the operational stage of all system where the main source of environmental damage is due to the electrical

    consumption by the HVAC systems. The results yield that all systems investigated comply to the industrial standards. LSI

    and RSI proved that all condenser waters are saturated with calcium ions but PSI proved that scale formations in the systems

    investigated are unlikely as the scales are likely to remain dissolved in the condenser water. Consistent temperature

    differences of chilled water are observed throughout the research period which show that the performance of chillers in

    each system are optimal, which proves that non-chemical treatment systems are as efficient (in terms of corrosion, scaling

    and microbial activity control) as chemical treatment system. Environmental impact analysis concluded that chemical

    treatment system has the highest annual equivalent CO2 emission per cooling capacity of 868.30 kg CO2 e/year RT. Thus,

    non-chemical treatment systems have lesser environmental impact than chemical treatment system.

    Key words: HVAC System, Condenser Water Treatment Systems, Corrosion, Scaling, Microbiological Proliferation

    mailto:[email protected]

  • INTRODUCTION

    The typical Heating, Ventilation and Air-conditioning (HVAC) system of a commercial building consists of key

    systems such as the chilled water cycle, refrigerant cycle and the condenser water cycle. As seen in Figure 1, the

    chilled water first enters the Air Handling Unit (AHU) where it exchanges heat with the air in the room or space. The

    air turns cooler and the chilled water temperature increases. The chilled water then flows to an evaporator where it

    exchanges het with the refrigerant to be cooled before repeating the cycle again. The warm refrigerant is then

    compressed to enter the condenser where it exchanges heat with condenser water before passing through an expansion

    valve to be heated up again in the evaporator. The warm condenser water first enters the cooling tower to be cooled

    by using ambient air. After being cooled, the condenser water then repeats the cycle by entering the condenser again

    to exchange heat with the warm refrigerant.

    FIGURE 1: Illustration of a typical HVAC system of a commercial building.

    As illustrated in Figure 1, all three systems are operating in closed loops. Thus, if no proper treatment was done to

    the systems, impurities in the chilled water and condenser water could cause issues such as scaling, corrosion and

    microbiological proliferation, which can decrease the efficiency of the cooling system [1]. The condenser water system is highly vulnerable to these operational issues due to the high operating conditions

    of 29°C to 38°C [2], as compared to chilled water with the operating temperatures of 5°C to 7°C.As temperature

    increases, the possibility of corrosion and scaling increases as soluble solids at low temperatures starts forming at high

    temperatures [1]. In addition to that, microbiological activities typically take place at ambient temperatures.

    Condenser water treatment methods can be separated into chemical methods that include the use of chemicals such

    as biocides, corrosion and scaling inhibitors as well as the non-chemical treatment methods that include the use of

    devices that use physical principles such as interfering and resonance oscillations [3], power-pulsed device [4] and

    ultra-low frequency in the control of scaling, corrosion and microbial activity.

    To catalyze the application of non-chemical treatment methods for condenser water loops in HVAC systems,

    Malaysia’s first green rating tool, Green Building Index (GBI) pledges to award one (1) innovation point for buildings

    that use non-chemical methods for the treatment of condenser water [5].

    Although numerous studies have proven the effectiveness of the non-chemical treatment methods in controlling

    scaling, corrosion and microbiological proliferation [3, 4], these studies are conducted without benchmarking with

    chemical treatment methods. This shows that the efficiency comparison (in terms of scaling, corrosion and microbial

    activity control) between chemical treatment systems and non-chemical treatment systems is yet to be investigated.

    In the cradle to grave lifecycle of both chemical and non-chemical treatment methods for condenser water in the

    HVAC systems, there will certainly be environmental impact such as the production of greenhouse gases (GHG) due

  • to various activities ranging from the manufacture stage to the transportation, construction, maintenance and operation

    as well as the demolition stage [6].

    Quantification of environmental impact requires lifecycle assessments and that there are no known studies

    conducted to compare the environmental impacts between the chemical and non-chemical treatment methods for

    condenser water in HVAC systems.

    In this study, the first objective is to identify the suitable system with effective corrosion and scaling control for

    condenser water treatment among the chemical and non-chemical treatment systems investigated. The second

    objective is to evaluate the environmental impact during the operational stage of the chemical and non-chemical

    treatment systems for condenser water treatment.

    RESEARCH METHODOLOGY

    In this study, three non-chemical treatment methods for condenser water are investigated. The first system uses

    Merus ring magnetic device, denoted as system A, the second system uses ultra-low frequency technology, denoted

    as system B that and the third system uses power pulsed device, denoted as system C. The chemical treatment method

    that is investigated that uses descalant and biocide, denoted by system D.

    Efficiency Analysis

    The efficiency analysis is conducted in two aspects, treatment efficiency and chiller efficiency. Treatment

    efficiency includes the sampling and characterization of condenser water as well as the prediction of scaling and

    corrosion. The chiller efficiency is analyzed by taking the temperature differences of chilled water in the chillers of

    the systems investigated.

    Sampling and Characterization of Condenser Water

    The sampling of the condenser water from systems A to D are conducted biweekly for nine (9) weeks with the

    assistance from engineers responsible for the cooling tower operations of the systems investigated. During each

    sampling trial, three (3) samples are taken at random for all running cooling towers during the time of sampling. The

    condenser water samples are stored at 4°C before further testing and analysis.

    The characterization of condenser water samples is conducted by analyzing for the pH, water alkalinity, water

    hardness, electrical conductivity, total dissolved solids (TDS) content, chloride and iron content. The pH, TDS and

    electrical conductivity can be measured by using the pH meter (Eutech, pH700, Fisher).

    Test kits such as the iron test kit, alkalinity test kit and chloride test kit are purchased from Merck and are used to

    test for the iron content, water alkalinity and chloride content respectively. Spectrophotometer (Prove 300, Merck,

    VSA) is used to measure the absorbance at respective wavelength for different tests.

    The water hardness is evaluated through the colorimetric titration method that uses ethylene diamine tetra acetic

    acid (EDTA) and Solochrome black-T (EBT). In this method, EBT and ammonium buffer solution are added to the

    condenser water samples. EDTA is then used to titrate the water samples until it turns from wine red to steel blue.

    This method requires a calibration curve constructed by using standard hard water in replacement of the condenser

    water in the titration to relate the water hardness to the volume of EDTA required to reach the end point of titration

    where the color change occurs.

    For microbiological proliferation, the heterotrophic plate count (HPC) method is used to characterized the colonies

    of heterotrophic bacteria present in the condenser water samples. In addition, the test for Legionella sp. is conducted.

    The test for microbiological proliferation will be conducted twice throughout the study period.

    The raw data obtained from the characterization is initially compared with Japan Refrigeration and Air

    Conditioning Industry Association Standards (JRA-GL-02-1994) to check if the operating parameters of the condenser

    water are met. Appendix 1 shows a copy of the JRA-GL-02-1994 extracted from the Japan Refrigeration and Air

    Conditioning Industry Association [7].

    The analysis of variance (ANOVA) single factor is used to assess the significance of batch to batch variations in

    readings. The significance is evaluated at p

  • Prediction of Scaling and Corrosion

    The scaling and corrosion potential for the condenser water samples are predicted by using LSI, RSI and PSI as it

    is widely applicable in the study of potentially corrosion and circulating water [8, 9, 10],. The formulae for the calculations of LSI, RSI and PSI are tabulated in Table 1. Table 2 shows the interpretation of the indices calculated.

    TABLE 1: Tabulation of formulae for LSI, RSI and PSI.

    Index Equations

    Langelier Saturation Index

    (LSI)

    𝐿𝑆𝐼 = 𝑝𝐻 − 𝑝𝐻𝑠 Eq. (1) 𝑝𝐻𝑠 =

    𝐴 + 𝐵 − 𝑙𝑜𝑔10(𝐶𝑎2+) − 𝑙𝑜𝑔10(𝐴𝑙𝑘𝑎𝑙𝑖𝑛𝑖𝑡𝑦)

    For pH ≤ 9.3

    Eq. (2)

    𝑝𝐻𝑠 = (9.3 + 𝐴 + 𝐵) − (𝐶 + 𝐷) For pH > 9.3 Eq. (3) 𝐿𝑆𝐼 = 𝑝𝐻 − 𝑝𝐻𝑠 Eq. (4)

    Ryznar Stability Index (RSI) 𝑅𝑆𝐼 = 2𝑝𝐻𝑠 − 𝑝𝐻 Eq. (5)

    Practical (Puckorious) Scaling

    Index (PSI)

    𝑃𝑆𝐼 = 2𝑝𝐻𝑠 − 𝑝𝐻𝑒𝑞 Eq. (6)

    𝐴 = 𝑙𝑜𝑔10[𝑇𝐷𝑆] − 1

    10 Eq. (7)

    𝐵 = −13.2 × 𝑙𝑜𝑔10(°𝐶 + 273) + 34.55 Eq. (8) 𝐶 = 𝑙𝑜𝑔10[𝐶𝑎

    2+𝑎𝑠 𝐶𝑎𝐶𝑂3] − 0.4 Eq. (9) 𝐷 = 𝑙𝑜𝑔10[𝐴𝑙𝑘𝑎𝑙𝑖𝑛𝑖𝑡𝑦] Eq. (10)

    𝑝𝐻𝑒𝑞 = 1.465 × 𝑙𝑜𝑔10[𝐴𝑙𝑘𝑎𝑙𝑖𝑛𝑖𝑡𝑦] + 4.54 Eq. (11)

    [𝐴𝑙𝑘𝑎𝑙𝑖𝑛𝑖𝑡𝑦] = [𝐻𝐶𝑂3−] + 2[𝐶𝑂3

    2−] + [𝑂𝐻−] Eq. (12)

    TABLE 2: Tabulation of index values and the corresponding water condition.

    Index Index Values Water Conditions

    LSI LSI > 0 Super saturated, tend to precipitate calcium carbonate

    LSI = 0 Saturated, calcium carbonate is in equilibrium

    LSI < 0 Under saturated, tend to dissolve solid calcium carbonate

    RSI RSI < 6 Super saturated, tend to precipitate calcium carbonate

    6 < RSI < 7 Saturated, calcium carbonate is in equilibrium

    RSI > 7 Under saturated, tend to dissolve solid calcium carbonate

    PSI PSI < 6 Scaling is unlikely to occur

    6

  • LSI takes the difference between the pH and the saturation pH of the condenser water to determine the potential

    of scaling but does not giving insights on how much scale is expected to form [11], which is why this index is

    commonly used in combination of other indices such as the RSI to accurately describe the scaling potential of the

    given condenser water.

    In the RSI, the saturation term is doubled to increase the sensitivity of the index to the saturation pH of calcium

    carbonate in the water sample, which can approximate the tendency of precipitation of calcium carbonate. RSI is

    proven to be more accurate and sensitive than LSI as proven by Hoseinzadeh et al. [12] where RSI yielded a smaller

    percentage error of corrosion potential of 5.5% when compared to LSI with 18.1%.

    PSI considers the equilibrium pH instead of the actual pH, which minimizes the effect of buffering agents such as

    caustic and ammonia that can result in inaccurate conclusion of scaling tendency calculated by LSI and RSI [13]. All indices are calculated and the interpretations of the condenser water are based on Table 2.

    Chiller Temperature Difference Analysis

    The chiller efficiency can be measured from the temperature difference of the chilled water that enters and leaves

    the chiller. The operational load of the chiller changes with respect to the demand for cold air by the occupants of the

    buildings, which is also dependent on the duration of the day.

    Operational load refers to the demand of cooling required by the building. For instance, in the morning with lesser

    occupants in a building, the cooling demand is lesser than when in the afternoon with more occupants.

    Due to these changes, the temperature difference readings are taken consistently biweekly on site with the sampling

    schedule at the specified time as shown below:

    System A: 11.00 A.M. – 11.30 A.M.

    System B: 12.00 P.M. – 12.30 P.M.

    System C: 10.00 A.M. – 10.30 A.M.

    System D: 2.30 P.M. – 3.00 P.M.

    The readings obtained are plotted in a line graph to monitor the trends of the temperature differences of the systems

    investigated over the study period to investigate the impact of the operational parameters of condenser water

    characterized with the chiller efficiency.

    Environmental Impact Analysis

    Quantification of environmental impact by the HVAC systems can be done through lifecycle assessment (LCA)

    from cradle to grave [6]. This research only focuses on the environmental impact of HVAC systems during the

    operational stage. According to the inventory analysis by Chen et al. [14], the most significant environmental impact

    during the operational stage of the HVAC systems is due to the electricity consumption.

    According to the local energy provider, Tenaga Nasional Berhad (TNB), the emission factor per kWh of power

    produced is 0.55 kg CO2 e/kWh [15]. From this information, the environmental impact analysis for all systems of

    condenser water treatments is carried out by evaluating the annual equivalent carbon dioxide (CO2) released per

    cooling capacity which can be calculated by multiplying the emission factor with the annual power consumption by

    each system investigated.

    The assumptions made for the calculation of environmental impact analysis include:

    1. Chiller as the major power consumer in the HVAC system. 2. 80% average motor operating load. 3. Chiller is operational for 12 hours per day. 4. Chiller is operational for 260 days per year.

    The chiller power consumption is calculated by considering of the rated power input and the total number of

    chillers present at the HVAC systems.

    For comparison of the environmental impact between the systems to be possible, the annual CO2 emission

    calculated must be divided by the respective system capacities.

  • During the operational stage, the biocide and descalant used by system D in the control of scaling, corrosion and

    microbial activity control may have environmental impacts which are not considered while calculating for the annual

    emission of carbon dioxide equivalent.

    However, the SDS for the chemicals used by system D will be analyzed to check for any environmental impacts

    that the chemicals may have.

    RESULTS AND DISCUSSIONS

    Efficiency Analysis

    The efficiency analysis includes the characterization of condenser water samples, the scaling and corrosion

    prediction analysis and the chiller performance analysis.

    Characterization of Condenser Water Samples

    (a) (b)

    (c) (d)

  • (e) (f)

    FIGURE 2: Results from characterization of condenser water samples for (a) pH (b) alkalinity (c) chloride content (d) water

    hardness (e) water conductivity and (f) TDS.

    The red lines in Figure 2(a), (b), (e) and (f) show the limit of the respective operating parameters in accordance to

    JRA-GL-02-1994. Figure 2(c) and (d) does not have red lines because the operating limits are out of range from the

    chart. The limits for chloride content and water hardness are 200 mg/L Cl- and 600 mg/L CaCO3 respectively.

    pH and Alkalinity

    From Figure 2(a) and (b), all systems are by complying the standards except for sampling trial 1 system C and

    sampling trial 4 system A. The exception of these two cases can be explained.

    Firstly, for sampling trial 1 system C, it is reported that there is maintenance conducted not long before the

    sampling of condenser water at system C. This causes residual impurities to be within the condenser water line that

    contributes to the high readings.

    On the other hand, for sampling trial 4 system A, it is reported that the sand filter used on site was offline for

    maintenance for the week where sampling of condenser water is conducted. During this week, only one sand filter

    was online and it is insufficient to maintain condenser water quality. This immediately resulted in the spike of reading

    for all operating parameters except chloride content.

    Chloride Content and Water Hardness

    From Figure 2(c) and (d), it is seen that all systems are operating well below the standards. However, the most

    significant reading found is on sampling trial 4 system A. The reason of the high readings is explained previously due

    to the maintenance of the sand filter on site.

    It is also worth noticing that the readings taken in system D are generally lower and more consistent when

    compared to the non-chemical treatment systems for chloride content, water hardness, conductivity and TDS. At the

    same time, the non-chemical treatment systems can be said that it has lesser consistency and that the readings are

    generally higher than the chemical treatment system.

    Water Conductivity and TDS

    From Figure 2(e) and (f), it is seen that all systems generally operate below the standards. The spike of reading for

    sampling trial 4 system A is explained earlier as the maintenance of sand filter on site. However, it is also worth

    mentioning that system B operates near the standards for water conductivity after the first sampling trial.

    This is due to the faulty TDS sensor on site that resulted in insufficient bleeding of condenser water which leads

    to the high readings of both conductivity and TDS content from sampling trail 2 to sampling trial 5. It is known that

    the faulty TDS sensor was not replaced.

  • Similar to the chloride content and water hardness, system D generally has readings that are lower and more

    consistent when compared to systems A, B and C.

    System A, B and C showed

  • TABLE 5: Tabulation of calculations and implications of LSI, RSI and PSI.

    Index Implication

    Samples LSI RSI PSI LSI RSI PSI

    Trial 1

    A 0.02 7.51 7.85 SSa USa SDa

    B 0.51 6.94 7.47 SS Sa SD

    C 0.70 6.65 7.13 SS S SD

    D 0.18 7.28 7.61 SS US SD

    Trial 2

    A 0.61 6.68 7.19 SS S SD

    B 0.78 6.57 7.37 SS S SD

    C 0.67 6.76 7.42 SS S SD

    D 0.44 7.05 7.55 SS US SD

    Trial 3

    A 0.48 6.94 7.67 SS S SD

    B 0.52 7.03 8.17 SS US SD

    C 0.50 6.98 7.63 SS S SD

    D 0.65 6.89 7.95 SS S SD

    Trial 4

    A 1.00 5.94 6.33 SS SS Sta

    B 0.72 6.59 7.26 SS S SD

    C 0.33 7.31 7.99 SS US SD

    D 0.33 7.32 8.15 SS US SD

    Trial 5

    A 0.75 6.47 7.05 SS S SD

    B 0.72 6.45 6.92 SS S St

    C 0.49 6.84 7.24 SS S SD

    D -0.14 7.72 8.0 US US SD aSS: Super Saturated; US: Under Saturated; SD: Scale Dissolves; S: Saturated; St: Stable

    Contradictory results between LSI and RSI are also published in literature by Kim et al. [16], Al-Huseini [17],

    Shams et al. [18] and Shankar [19]. The contradictory results are often caused by the actual pH values of the water

    samples. By using pH to compare between Table 5 and Figure 2(a), it can be seen that water samples with pH of less

    than 7.8 generally yields ‘US’ result RSI while having ‘SS’ for LSI. Because of the relatively low pH, both LSI and

    RSI values are at the borderlines of the descriptions of water conditions as shown in Table 2. In these cases, the water

    conditions need to be verified by using PSI to check for the scaling condition.

    For condenser water samples that have pH values of more than 7.8, the LSI remains to have ‘SS’ and that the RSI

    gives ‘S’. From the two indices, it is agreeable that calcium ions in these water samples are saturated. However, the

    degree of saturation remains unknown due to the contradicting results from LSI and RSI. Hoseinzadeh et al. [12] proved that RSI is more accurate when compared to LSI as the sensitivity to the saturation pH of calcium carbonate

    is increased. This implies that RSI is a more reliable index to indicate the scaling potential due to the degree of

    saturation of the water samples. Shankar [19] supported this statement by justifying that the range of water condition

    for the LSI is more limited as a solid zero is needed to show that the water is saturated as shown in Table 2. On the

    other hand, RSI provides a range of 6 to 7 for a saturation zone which allows more flexibility in terms of the water

    condition. Therefore, in these cases where the pH values of the condenser water samples are more than 7.8, the water

    condition is concluded from RSI instead of LSI.

    As LSI and RSI only describe the tendencies of the scale formation in water bodies without giving insights on how

    much scale is expected, PSI must be used in addition to LSI and RSI to confirm the condenser water conditions. The

    PSI readings show that all condenser waters are likely to dissolve scale except for sampling trial 4 system A and

    sampling trial 5 system B. This shows that the condenser water samples do not have scale formation tendencies. The

    stable condition of condenser water for sampling trial 4 system A is caused by the maintenance of sand filter on site.

    The stable condition of condenser water for sampling trail 5 system B is caused by the faulty TDS sensor on site that

    leads to insufficient bleeding of condenser water.

  • In summary, although that the condenser water samples are saturated with calcium ions as proven by LSI and RSI,

    the scale formations in the systems investigated are unlikely as the scales will remain dissolved in the condenser water

    as proven by PSI.

    Chiller Performance Analysis

    Figure 3 shows the graph of temperature difference of chilled water for systems A to D across the study period.

    As mentioned, the timings of the registration of readings for the chilled water temperatures from each system are

    different but consistent. Therefore, instead of comparing system by system, the consistencies of each system in terms

    of the temperature difference of chilled water are investigated.

    From Figure 3, it is seen that the temperature differences for systems A, B and D are consistently in the range of

    3.0°C to 5.0°C. For system C, the inconsistent temperature difference readings are due to the different operating loads

    of the chiller on site.

    For systems A, B and D, the consistent temperature differences of chilled water are the results of the operation of

    condenser water that is generally below the industrial standards. Because of this, operational issues such as corrosion,

    scaling and microbiological proliferation are prevented which allows optimal operation of the HVAC systems in

    system A, B and D.

    For system C, the fluctuations in the temperature differences between the chilled water in the chiller does not

    necessarily mean that the operation of condenser water exceeds the industrial standards. This is further reinforced by

    the excellent results obtained by system C in the characterization of condenser water in Figure 2.

    FIGURE 3: Chilled water temperature difference in chillers.

    Therefore, the fluctuations of temperature difference between the chilled water in the chiller in system C is not

    caused by operational issues of condenser water such as corrosion, scaling and microbiological proliferation. The

    fluctuation in the temperature difference of chilled water is however due to the different chiller operating loads.

    In system C, for sampling trials of 1, 2 and 5, the chiller is running at operating loads of 103%, 100% and 98%

    respectively, while for sampling trials of 3 and 4, the chiller is running at operating loads of 58% and 51%, although

    that the readings are taken consistently between 10.00 A.M. to 10.30 A.M.

    It is clear that the temperature difference fluctuations of system C is caused by the operational load of the chiller.

    Therefore, based on the results obtained from the characterization of condenser water samples, it can be concluded

    that the HVAC system in system C operates optimally without issues such as corrosion, scaling and microbiological

    proliferation.

    0.00

    1.00

    2.00

    3.00

    4.00

    5.00

    6.00

    7.00

    8.00

    0 1 2 3 4 5 6

    Chil

    led

    Wat

    er T

    emp

    erat

    ure

    Dif

    fere

    nce

    ,

    °C

    Sampling Trials

    Chilled Water Temperature Difference

    System A

    System B

    System C

    System D

  • Environmental Impact Analysis

    Table 6 shows the tabulation of information required for the calculation. The rated power inputs for the chillers in

    system C are unobtainable. Thus, the calculation of the power input to the chillers in system C is evaluated by using

    the chiller efficiency information as shown in Table 6.

    TABLE 5: Tabulation of system specifications for environmental impact calculations.

    System Number of Chillers Power Input (kW) Chiller Efficiency

    (kW/RT)

    Cooling Capacity

    (RT)

    A 3 342 0.670 2700

    B 3 310 0.670 1650

    C 7 NAa 0.175 8000

    D 4 253 NA 1600 aNA: Not Applicable (For information that are unobtainable)

    By considering the assumptions listed out for the calculations, the annual electricity consumption of the chillers

    for each system can be evaluated, followed by the annual equivalent emission of CO2 per RT. Table 7 shows the

    tabulation of the results calculated for the environmental impact analysis.

    TABLE 6: Tabulation of results for environmental impact analysis.

    System

    Annual

    Electricity Consumption

    (kW/year)

    Annual Equivalent

    CO2 Emission

    (kg CO2 e/year)

    Annual Emission per

    Cooling Capacity

    (kg CO2 e/year RT)

    A 2,560,896 1,408,493 521.66

    B 2,321,280 1,276,704 773.76

    C 3,494,400 1,921,920 240.24

    D 2,525,952 1,389,274 868.30

    As observed in Table 7, the annual emission per cooling capacity for system D is the highest at 868.30 kg CO2

    e/year RT when compared to the non-chemical treatment systems of A to C. This indicates that the non-chemical

    treatment systems for condenser water in the HVAC systems causes lesser environmental impact (in terms of CO2

    emission) when compared to the chemical treatment system.

    From Tables 6 and 7, it is seen that the chiller in system D consumes only 253 kW, but when the comparison of

    the same cooling capacity is made, system D yields the highest annual emission per cooling capacity. This shows that

    the chillers in system D are not as efficient as the chillers in system A, B and C because that it requires more energy

    to produce 1 RT of cooling capacity. Therefore, from the environmental impact analysis, it can be seen that the

    chemical treatment system not only produces more CO2 equivalent annually per RT, it is also shown to have the least

    efficient chillers when compared to the non-chemical treatment systems.

    In addition, there are three (3) chemicals used in the control of scaling, corrosion and microbial activity control in

    system D. The three chemicals are labelled as CL-320, CL-650 and CL-653.

    CL-320 is an organo-phosphonate based corrosion and scale inhibitor that has the combination of calcium

    carbonate inhibitor, dispersant, dual phosphonate and yellow metal inhibitor to control corrosion of mild steel, copper

    and admiralty brass. This chemical also minimizes hardness salt formation in alkaline cooling water.

    CL-650 is a non-oxidizing blend of quaternary ammonium compounds-based biocide that functions to control the

    activity of bacteria, fungi and algae in open re-circulating cooling water systems. It also contains dispersing agents

    that ensure good distribution throughout the system and efficient penetration of slime masses.

    CL-653 is a non-oxidizing mixture of isothiazolin based biocide that is designed specifically for the control of

    bacteria, fungi and algae in open re-circulating cooling water system. This product has low foaming tendency and is

    compatible with most treatment chemicals.

    According to the SDS of the chemicals, CL-320 has no environmental impact during the usage, but CL-650 and

    CL-653 have reported to have category 3 acute aquatic hazard, which means that short term exposure (15 minutes) of

    10 mg/L to 100 mg/L of the chemicals can cause damage to aquatic environment and subsequently to the aquatic

  • organisms. Thus, this concludes that the non-chemical treatment systems might cause lesser environmental impact

    when compared to the chemical treatment system.

    CONCLUSION

    In conclusion, the efficiency analysis proves that the chemical and non-chemical treatment systems are capable in

    maintaining operating parameters such as the pH, water alkalinity, iron content, chloride content, TDS, water electrical

    conductivity and water hardness by complying the industrial standards such as the JRA-GL-02-1994. In addition to

    that, the calculations of LSI, RSI and PSI concluded that all condenser water samples are saturated with calcium ions,

    but scale formations are unlikely as the scales are likely to remain dissolved in the condenser water. Because of the

    adherent to the industrial standards, the chillers in all systems are able to run optimally with consistent temperature

    difference between the chilled water taken at consistent timings.

    Secondly, the environmental impact analysis concluded that the non-chemical treatment systems have lesser

    environmental impact compared to the chemical treatment system with an annual equivalent emission of CO2 of

    868.30 kg CO2 e/year RT which is the most among the systems investigated. Due to the chemicals used, the chemical

    treatment system might have more negative environmental impact when compared to the non-chemical treatment

    systems.

    ACKNOWLEDGMENT

    The authors would like to express gratitude to panels from Green Building Index, EnGreen, Greneco and Taylor’s

    University for the support and cooperation throughout the research project.

    REFERENCES

    [1] J. P. Guyer, P.E., R.A., F. ASCE and F. AEI, "An Introduction to Cooling Tower Water Treatment," Continuing

    Education and Development, Inc., New York, 2014.

    [2] American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE), The ASHRAE

    GreenGuide: The Design, Construction, and Operation of Sustainable Buildings, ASHRAE Press, 2006.

    [3] Hawari, Z. A. Rahman and Yahaya, "Merus Ring Technology for Boiler Feed Water Treatment," Malaysia Palm

    OIl Board, Kuala Lumpur, 2012.

    [4] Y. I. Cho, J. Lane and W. Kim, "Pulsed-power treatment for physical water treatment," International

    Communications in Heat and Mass Transfer, vol. 32, pp. 861-871, 2005.

    [5] Green Building Index Sdn Bhd, GBI Assesment criteria: industrial new construct ion (INC), Kuala Lumpur:

    Green Building Index Sdn Bhd, 2011.

    [6] S. Chen, "System Dynamics Based Models for Selecting HVAC System for Office Buildings: A Life Cycle

    Assessment from Carbon Emission Perspective," School of Civil, Environmental and Chemical Engineering,

    College of Science, Engineering and Health, RMIT Univetsity, Melbourne, 2012.

    [7] Japan Refrigeration and Air Conditioning Industry Association Standards, Water Quality Standard for Cooling

    water, Cold water, Hot water, Makeup water, Japan: Japan Refrigeration and Air Conditioning Industry

    Association, 2011.

    [8] M. Mirzabeygi, M. Naji, N. Yousefi, M. Shams, H. Biglari and A. H. Mahvi, "Evaluation of corrosion and

    scaling tendency indices in water distribution system: a case study of Torbat Heydariye, Iran," Desalination and

    Water Treatment, vol. 10, pp. 1-9, 2016.

    [9] A. Gholizadeh, M. Mokhtari, N. Naimi, B. Shiravand, M. H. Ehrampoush, M. Miri and A. Ebrahimi,

    "Assessment of corrosion and scaling potential in groundwater resources; a case study of Yazd-Ardakan Plain,

    Iran," Groundwater for Sustainable Development, vol. 5, pp. 59-65, 2017.

  • [10] U. M. Etesin1, T. Harry, I. O. Isaac and U. G. Isotuk, "A Study of Potential Corrosivity of Borehole Waters in

    Eket, Nigeria by Saturation Index Measurement," Asian Journal of Environment & Ecology, vol. 7, no. 3, pp.

    1-13, 2018.

    [11] Y. Chen, Y. Cui, A. G. Barrett, F. Chille and S. Lassalle, "Investigation of calcite precipitation in the drainage

    system of railway tunnels," Tunnelling and Underground Space Technology, vol. 84, pp. 45-55, 2019.

    [12] E. Hoseinzadeh, A. Yusefzadeh, N. Rahimi and H. Khorsandi, "Evaluation of Corrosion and Scaling Potential

    of a Water Treatment Plant," Archives of Hygiene Sciences, vol. 2, no. 2, pp. 41-47, 2013.

    [13] A. Takdastan, M. M. (Radfard), A. A. Mahmood Yousefi, R. Khodadadia, H. Soleimani, A. H. Mahvi and D. J.

    Naghan, "Neuro-fuzzy inference system Prediction of stability indices and Sodium absorption ratio in Lordegan

    rural drinking water resources in west Iran," Data in Brief, vol. 18, pp. 255-261, 2018.

    [14] S. Chen, K. Zhang and S. Setunge, "Comparison of Three HVAC Systems in an Office Building from a Life

    Cycle Perspective," School of Civil, Environmental and Chemical Engineering, RMIT University, Melbourne,

    2011.

    [15] Tenaga Nasional Berhad (TNB), "Sustainability Report 2017," Tenaga Nasional Berhad, Kuala Lumpur, 2017.

    [16] J. Kim, S. K. Behera, S. Oh and H. Park, "Reuse potential of municipal wastewater treatment facility effluents

    for sustainable water resource management in Ulsan, Korea," Waater and Environment Journal, vol. 24, no. 4,

    pp. 293-302, 2010.

    [17] A. Al-Husseini, " Study of potential corrosion and scaling for treated water of two water treatment plants in Al-

    Hilla City," Journal of Babylon University, Engineering Sciences, vol. 4, no. 20, pp. 1180-1190, 2012.

    [18] M. Shams, A. Mohammadi and S. A. Sajjadi, "Evaluation of corrosion and scaling potential of water in rural

    water supply distribution networks of Tabas, Iran," World Applied Sciences Journal, vol. 17, no. 11, pp. 1484-

    1489, 2012.

    [19] S. B.S., "Determination of Scaling and corrosion tendencies of water through the use of Langelier and Ryznar

    Indices," Scholars Journal of Engineering and Technology (SJET), vol. 2, no. 2A, pp. 123-127, 2014.

    [20] K. A. KITZMAN, E. F. MAZIARZ, B. PADGETT, C. D. BLUMENSCHEIN and A. SMITH, "Chemical vs.

    Non-chemical Cooling Water Treatments – a Side-by-Side Comparison," Alcoa’s Mt. Holly Works, Pittsburgh

    , 2008.

    [21] G. Tomberlin, J. Dean and M. Deru, "Electrochemical Water Treatment for Cooling Towers," National

    Renewable Energy Laboratory (NREL), Golden, 2019.

    [22] D. Cutler, J. Dean, J. Daw and Dan Howett, "Alternative Water Treatment Technologies for Cooling Tower

    Applications," National Renewable Energy Laboratory (NREL), Golden, 2019.