Details Technical Advice 1300 724 505 knaufmetal.com.au External Steel Stud and Top Hat Walls External steel framed plasterboard walls protect the inside from weather, noise and when applicable, fire. They must also comply with local energy efficiency provisions. Fire rated systems in this section can satisfy NCC FRL requirements for spandrel walls and walls built close to a fire source feature such as a property boundary. These walls are often required to be fire rated from the outside only. TruRock forms part of the outer wall and is covered by a moisture barrier and external cladding which provide the weather protection. This section contains systems, installation instructions and construction details for fire rated and non-fire rated external steel framed walls. SYSTEMS 176 NON-FIRE RATED SYSTEMS 176 FIRE RATED SYSTEMS 178 BRICK VENEER SYSTEMS 183 INSTALLATION 185 GENERAL REQUIREMENTS 185 FRAMING 185 PLASTERBOARD LAYOUT 189 PLASTERBOARD FIXING 190 EXTERIOR CLADDING 191 CONSTRUCTION DETAILS 193 176

External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

Details

Technical Advice 1300 724 505 knaufmetal.com.au

External Steel Stud and Top Hat WallsExternal steel framed plasterboard walls protect the inside from weather, noise and when applicable, fire. They must also comply with local energy efficiency provisions.

Fire rated systems in this section can satisfy NCC FRL requirements for spandrel walls and walls built close to a fire source feature such as a property boundary. These walls are often required to be fire rated from the outside only.

TruRock forms part of the outer wall and is covered by a moisture barrier and external cladding which provide the weather protection.

This section contains systems, installation instructions and construction details for fire rated and non-fire rated external steel framed walls.

SYSTEMS 176

NON-FIRE RATED SYSTEMS 176

FIRE RATED SYSTEMS 178

BRICK VENEER SYSTEMS 183

INSTALLATION 185

GENERAL REQUIREMENTS 185

FRAMING 185

PLASTERBOARD LAYOUT 189

PLASTERBOARD FIXING 190

EXTERIOR CLADDING 191

CONSTRUCTION DETAILS 193

176

Page 2: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

3.2.1

Technical Advice 1300 724 505 knaufplasterboard.com.au 177

EXTERNAL STEEL STUD AND TOP HAT WALLSNon-Fire Rated Systems

* R-Value based on anti-glare foil and minimum 13mm gap created by thermal break.

KSW274EXTERNAL WALL CLADDING: 1 layer of minimum 7.5mm HardieTexMOISTURE BARRIER: Wall wrapFRAME: Minimum 70mm steel studs at maximum 600mm centresWALL INSULATION: As specified in table belowINTERNAL WALL LINING: 2 layers of 10mm OPAL

FRL – / – / –

Stud Size (mm)

Estimated Total R-Value (m2.K/W)

Width (mm)

Sound Insulation Rw (Rw + Ctr)

No Insulation R1.5 EarthWool

R1.5 Polyester

Acoustic Report Insul

70 0.7*+ Insulation R Value

110 approximate 43 (31) 47 (35) 46 (34)

KSW73EXTERNAL WALL CLADDING: 1 layer of minimum 7.5mm HardieTexMOISTURE BARRIER: Wall wrapFRAME: Minimum 70mm steel studs at maximum 600mm centresWALL INSULATION: OptionalINTERNAL WALL LINING: 1 layer of 10mm MastaShield or10mm WaterShield

FRL – / – / –

Stud Size (mm)

Estimated Total R-Value (m2.K/W)

Width (mm)

Sound Insulation Rw (Rw + Ctr)

No Insulation R2.0 EarthWool

R1.5 Polyester

Acoustic Report Insul

70 0.6*+ Insulation R Value

100 approximate 38 (29) 42 (31) 40 (30)

KSW378EXTERNAL WALL CLADDING: 1 layer of minimum 7.5mm HardieTexMOISTURE BARRIER: Wall wrapFRAME: Minimum 70mm steel studs at maximum 600mm centresWALL INSULATION: As specified in table belowINTERNAL WALL LINING: 3 layers of 13mm FireShield

FRL – / – / –

Stud Size (mm)

Estimated Total R-Value (m2.K/W)

Width (mm)

Sound Insulation Rw (Rw + Ctr)

No Insulation R1.5 EarthWool

R1.5 Polyester

Acoustic Report Insul

70 0.8*+ Insulation R Value

130 approximate 48 (36) 52 (39) 51 (38)

Page 3: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

3.2.1

Technical Advice 1300 724 505 knaufmetal.com.au178

EXTERNAL STEEL STUD AND TOP HAT WALLSFire RatedSystems

* R-Value based on anti-glare foil, minimum 20mm air gap and 6mm fibre cement.

KSW473EXTERNAL WALL CLADDING: Any claddingMOISTURE BARRIER: Wall wrapEXTERNAL WALL LINING: 1 layer of 16mm TruRock FRAME: Minimum 70mm steel studs at maximum 600mm centresWALL INSULATION: OptionalINTERNAL WALL LINING: 1 layer of 10mm MastaShield or 10mm WaterShield[Use approved fire rated penetration details in the non-fire rated internal lining to maintain FRL]

FRL 60/60/60rated from the outside onlyFire Report FAR 3371

Stud Size (mm)

Estimated Total R-Value (m2.K/W)

Width (mm)

Sound Insulation Rw (Rw + Ctr)

No Insulation R1.5 EarthWool

R1.5 Polyester

Acoustic Report Insul

70 0.8*+ Insulation R Value

155 approximate 38 (30) 42 (32) 41 (30)

KSW470EXTERNAL WALL CLADDING: Any claddingMOISTURE BARRIER: Wall wrapEXTERNAL WALL LINING: 1 layer of 13mm TruRockFRAME: Minimum 70mm steel studs at maximum 600mm centresWALL INSULATION: OptionalINTERNAL WALL LINING: 1 layer of 10mm MastaShield or 10mm WaterShield[Use approved fire rated penetration details in the non-fire rated internal lining to maintain FRL]

FRL 30/30/30rated from the outside onlyFire Report FAR 3371

Stud Size (mm)

Estimated Total R-Value (m2.K/W)

Width (mm)

Sound Insulation Rw (Rw + Ctr)

No Insulation R1.5 EarthWool

R1.5 Polyester

Acoustic Report Insul

70 0.8*+ Insulation R Value

150 approximate 37 (29) 41 (31) 40 (31)

KSW471EXTERNAL WALL CLADDING: Any claddingMOISTURE BARRIER: Wall wrapEXTERNAL WALL LINING: 2 layers of 13mm TruRock FRAME: Minimum 70mm steel studs at maximum 600mm centresWALL INSULATION: OptionalINTERNAL WALL LINING: 1 layer of 10mm MastaShield or 10mm WaterShield[Use approved fire rated penetration details in the non-fire rated internal lining to maintain FRL]

FRL 90/90/90rated from the outside onlyFire Report FAR 3371

Stud Size (mm)

Estimated Total R-Value (m2.K/W)

Width (mm)

Sound Insulation Rw (Rw + Ctr)

No Insulation R1.5 EarthWool

R1.5 Polyester

Acoustic Report Insul

70 0.9*+ Insulation R Value

165 approximate 43 (33) 46 (35) 45 (34)

Page 4: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

3.2.1

Technical Advice 1300 724 505 knaufplasterboard.com.au 179

EXTERNAL STEEL STUD AND TOP HAT WALLSFire Rated Systems

* R-Value based on anti-glare foil, minimum 20mm air gap and 6mm fibre cement.

KSW491EXTERNAL WALL CLADDING: Any claddingMOISTURE BARRIER: Wall wrapEXTERNAL WALL LINING: 2 layers of 13mm TruRockFRAME: Minimum 70mm steel studs at maximum 600mm centresWALL INSULATION: OptionalINTERNAL WALL LINING: Optional

FRL 30/30/30rated from the outside onlyFire Report FAR 2827

Stud Size (mm)

Estimated Total R-Value (m2.K/W)

Width (mm)

Sound Insulation Rw (Rw + Ctr)

No Insulation R1.5 EarthWool

R1.5 Polyester Acoustic Report

Day Design 3094-3370 0.8*

+ Insulation R Value155

approximate 34 (30) 34 (30) 34 (30)

KSW472EXTERNAL WALL CLADDING: Any claddingMOISTURE BARRIER: Wall wrapEXTERNAL WALL LINING: 3 layers of 13mm TruRockFRAME: Minimum 70mm steel studs at maximum 600mm centresWALL INSULATION: OptionalINTERNAL WALL LINING: 1 layer of 10mm MastaShield or 10mm WaterShield[Use approved fire rated penetration details in the non-fire rated internal lining to maintain FRL]

FRL 120/120/120

rated from the outside onlyFire Report FAR 3371

Stud Size (mm)

Estimated Total R-Value (m2.K/W)

Width (mm)

Sound Insulation Rw (Rw + Ctr)

No Insulation R1.5 EarthWool

R1.5 Polyester

Acoustic Report Insul

70 1.0*+ Insulation R Value

175 approximate 46 (36) 50 (38) 49 (38)

KSW494EXTERNAL WALL CLADDING: Any claddingMOISTURE BARRIER: Wall wrapEXTERNAL WALL LINING: 2 layers of 16mm TruRock FRAME: Minimum 70mm steel studs at maximum 600mm centresWALL INSULATION: OptionalINTERNAL WALL LINING: Optional

FRL 60/60/60rated from the outside onlyFire Report FAR 2827

Stud Size (mm)

Estimated Total R-Value (m2.K/W)

Width (mm)

Sound Insulation Rw (Rw + Ctr)

No Insulation R1.5 EarthWool

R1.5 Polyester Acoustic Report

Day Design 3094-3370 0.9*

+ Insulation R Value160

approximate 35 (31) 35 (31) 35 (31)

Page 5: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

3.2.1

Technical Advice 1300 724 505 knaufmetal.com.au180

EXTERNAL STEEL STUD AND TOP HAT WALLSFire RatedSystems

* R-Value based on anti-glare foil, minimum 20mm air gap and 6mm fibre cement.

KSW495EXTERNAL WALL CLADDING: Any claddingMOISTURE BARRIER: Wall wrapEXTERNAL WALL LINING: 3 layers of 16mm TruRock FRAME: Minimum 70mm steel studs at maximum 600mm centresWALL INSULATION: OptionalINTERNAL WALL LINING: Optional

FRL 120/120/120

rated from the outside onlyFire Report FAR 2827

Stud Size (mm)

Estimated Total R-Value (m2.K/W)

Width (mm)

Sound Insulation Rw (Rw + Ctr)

No Insulation R1.5 EarthWool

R1.5 Polyester Acoustic Report

Day Design 3094-3370 1.0*

+ Insulation R Value175

approximate 38 (35) 38 (35) 38 (35)

KSW492EXTERNAL WALL CLADDING: Any claddingMOISTURE BARRIER: Wall wrapEXTERNAL WALL LINING: 3 layers of 13mm TruRockFRAME: Minimum 70mm steel studs at maximum 600mm centresWALL INSULATION: OptionalINTERNAL WALL LINING: Optional

FRL 90/90/90rated from the outside onlyFire Report FAR 2827

Stud Size (mm)

Estimated Total R-Value (m2.K/W)

Width (mm)

Sound Insulation Rw (Rw + Ctr)

No Insulation R1.5 EarthWool

R1.5 Polyester Acoustic Report

Day Design 3094-3370 0.9*

+ Insulation R Value165

approximate 37 (34) 37 (34) 37 (34)

KSW496EXTERNAL WALL CLADDING: Any claddingMOISTURE BARRIER: Wall wrapEXTERNAL WALL LINING: 1 layer of 13mm TruRock FRAME: Minimum 70mm steel studs at maximum 600mm centresWALL INSULATION: OptionalINTERNAL WALL LINING: 1 layer of 13mm FireShield or 13mm TruRock

FRL – /60/60

rated from both sidesFire Report FAR 3210

Stud Size (mm)

Estimated Total R-Value (m2.K/W)

Width (mm)

Sound Insulation Rw (Rw + Ctr)

No Insulation R1.5 EarthWool

R1.5 Polyester

Acoustic Report Insul

70 0.8*+ Insulation R Value

155 approximate 39 (30) 43 (32) 42 (31)

Page 6: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

3.2.1

Technical Advice 1300 724 505 knaufplasterboard.com.au 181

EXTERNAL STEEL STUD AND TOP HAT WALLSFire Rated Systems

* R-Value based on anti-glare foil, minimum 20mm air gap and 6mm fibre cement.

KSW478EXTERNAL WALL CLADDING: Any claddingMOISTURE BARRIER: Wall wrapEXTERNAL WALL LINING: 2 layers of 13mm TruRockFRAME: Minimum 70mm steel studs at maximum 600mm centresWALL INSULATION: OptionalINTERNAL WALL LINING: 2 layers of 13mm FireShield or 13mm TruRock

FRL 90/90/90

rated from both sidesFire Report FAR 3371

Stud Size (mm)

Estimated Total R-Value (m2.K/W)

Width (mm)

Sound Insulation Rw (Rw + Ctr)

No Insulation R1.5 EarthWool

R1.5 Polyester

Acoustic Report Insul

70 1.0*+ Insulation R Value

180 approximate 50 (41) 53 (45) 52 (43)

KSW477EXTERNAL WALL CLADDING: Any claddingMOISTURE BARRIER: Wall wrapEXTERNAL WALL LINING: 2 layers of 13mm TruRockFRAME: Minimum 70mm steel studs at maximum 600mm centresWALL INSULATION: OptionalINTERNAL WALL LINING: 1 layer of 16mm FireShield or 16mm TruRock

FRL 90/90/90

rated from the outside60/60/60

rated from the inside Fire Report FAR 3371

Stud Size (mm)

Estimated Total R-Value (m2.K/W)

Width (mm)

Sound Insulation Rw (Rw + Ctr)

No Insulation R1.5 EarthWool

R1.5 Polyester

Acoustic Report Insul

70 0.9*+ Insulation R Value

170 approximate 45 (36) 48 (39) 47 (38)

KSW476EXTERNAL WALL CLADDING: Any claddingMOISTURE BARRIER: Wall wrapEXTERNAL WALL LINING: 1 layer of 16mm TruRockFRAME: Minimum 70mm steel studs at maximum 600mm centresWALL INSULATION: OptionalINTERNAL WALL LINING: 1 layer of 16mm FireShield or 16mm TruRock

FRL 60/60/60

rated from both sidesFire Report FAR 3371

-/90/90with EarthWool

Fire Report FAR 3210

Stud Size (mm)

Estimated Total R-Value (m2.K/W)

Width (mm)

Sound Insulation Rw (Rw + Ctr)

No Insulation R1.5 EarthWool

R1.5 Polyester

Acoustic Report Insul

70 0.9*+ Insulation R Value

160 approximate 40 (31) 44 (35) 43 (33)

Page 7: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

* R-Value based on anti-glare foil, minimum 20mm air gap and 6mm fibre cement.

3.2.1

Technical Advice 1300 724 505 knaufmetal.com.au182

EXTERNAL STEEL STUD AND TOP HAT WALLSFire RatedSystems

KSW479EXTERNAL WALL CLADDING: Any claddingMOISTURE BARRIER: Wall wrapEXTERNAL WALL LINING: 2 layers of 16mm TruRockFRAME: Minimum 70mm steel studs at maximum 600mm centresWALL INSULATION: OptionalINTERNAL WALL LINING: 2 layers of 16mm FireShield or 16mm TruRock

FRL 120/120/120

rated from both sidesFire Report FAR 3371

Stud Size (mm)

Estimated Total R-Value (m2.K/W)

Width (mm)

Sound Insulation Rw (Rw + Ctr)

No Insulation R1.5 EarthWool

R1.5 Polyester

Acoustic Report Insul

70 1.1*+ Insulation R Value

190 approximate 51 (43) 54 (37) 53 (45)

Page 8: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

3.2.1

Technical Advice 1300 724 505 knaufplasterboard.com.au 183

EXTERNAL STEEL STUD AND TOP HAT WALLSBrick Veneer Systems

KSW70EXTERNAL MASONRY: Minimum 90mm masonry with FRL 60/60/60

(Minimum laid weight 130 kg/m²)FRAME: Minimum 70mm steel studs at maximum 600mm centres

with a minimum 40mm air gapWALL INSULATION: OptionalINTERNAL WALL LINING: 1 layer of 10mm MastaShield or10mm WaterShield

FRL 60/60/60rated from the outside onlyFire Report FAR 3586

Stud Size (mm)

Estimated Total R-Value (m2.K/W)

Width (mm)

Sound Insulation Rw (Rw + Ctr)

No Insulation R1.5 EarthWool

R1.5 Polyester

Acoustic Report Insul

70 0.5+ Insulation R Value

210 approximate 47 (41) 58 (47) 57 (46)

KSW371EXTERNAL MASONRY: Minimum 90mm masonry with FRL 90/90/90

(Minimum laid weight 130 kg/m²)FRAME: Minimum 70mm steel studs at maximum 600mm centres

with a minimum 40mm air gapWALL INSULATION: OptionalINTERNAL WALL LINING: 2 layers of 13mm FireShield or 13mm TruRock

FRL 90/90/90

rated from both sidesFire Report FAR 3586

Stud Size (mm)

Estimated Total R-Value (m2.K/W)

Width (mm)

Sound Insulation Rw (Rw + Ctr)

No Insulation R1.5 EarthWool

R1.5 Polyester

Acoustic Report Insul

70 0.6+ Insulation R Value

226 approximate 51 (47) 62 (53) 61 (52)

KSW373EXTERNAL MASONRY: Minimum 90mm masonry with FRL 60/60/60

(Minimum laid weight 130 kg/m²)FRAME: Minimum 70mm steel studs at maximum 600mm centres

with a minimum 40mm air gapWALL INSULATION: OptionalINTERNAL WALL LINING: 1 layer of 16mm FireShield or 16mm TruRock

FRL 60/60/60

rated from both sidesFire Report FAR 3586

Stud Size (mm)

Estimated Total R-Value (m2.K/W)

Width (mm)

Sound Insulation Rw (Rw + Ctr)

No Insulation R1.5 EarthWool

R1.5 Polyester

Acoustic Report Insul

70 0.5+ Insulation R Value

216 approximate 48 (43) 59 (49) 58 (48)

Page 9: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

3.2.1

Technical Advice 1300 724 505 knaufmetal.com.au184

EXTERNAL STEEL STUD AND TOP HAT WALLSBrick VeneerSystems

KSW374EXTERNAL MASONRY: Minimum 90mm masonry with FRL 120/120/120

(Minimum laid weight 130 kg/m²)FRAME: Minimum 70mm steel studs at maximum 600mm centres

with a minimum 40mm air gapWALL INSULATION: OptionalINTERNAL WALL LINING: 2 layers of 16mm FireShield or 16mm TruRock

FRL 120/120/120

rated from both sidesFire Report FAR 3586

Stud Size (mm)

Estimated Total R-Value (m2.K/W)

Width (mm)

Sound Insulation Rw (Rw + Ctr)

No Insulation R1.5 EarthWool

R1.5 Polyester

Acoustic Report Insul

70 0.6+ Insulation R Value

232 approximate 53 (49) 65 (55) 64 (54)

Page 10: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

3.2.1

Technical Advice 1300 724 505 knaufplasterboard.com.au 185

EXTERNAL STEEL STUD AND TOP HAT WALLSGeneral Requirements and Framing Installation

3.2.1

Technical Advice 1300 724 505 knaufplasterboard.com.au 185

Installation

General Requirements

Non-Fire Rated

Fire Rated

Install control joints in plasterboard walls: At 12m maximum intervals At all control joints in the structure At any change in the substrate material.

✔ ✔

Jointing of the TruRock is not required due to the overlying breathable wall wrap and cladding. ✔

Joint the face layer on the internal side with: Paper tape and two coats of MastaBase / MastaLongset or Paper tape and three coats of MastaLite or Bindex Fire and Acoustic Sealant according to the Technical Data Sheet.

Use approved fire rated penetration details. Fire penetrations may require fire collars or other devices to maintain fire performance. ✔

Use approved fire rated penetration details for systems that use the internal non-fire rated plasterboard wall lining to maintain the FRL. ✔

Pack any gaps between the top of the wall and the underside of the roof covering with mineral fibre or other suitable fire resisting material. ✔

Protect plasterboard from water pooling at ground level. ✔ ✔

Use fire sealant on all gaps and around perimeter, vermiculite plaster is not permitted. ✔

Attach all fixtures to studs or noggings. Wall anchors must not be directly fixed to only the plasterboard of fire rated walls. ✔

For acceptable modifications or variations to fire rated systems [Refer to Section 2.3 Fire Resistance].

FramingNon-Fire

RatedFire

Rated

Framing members must be spaced at 600mm maximum centres. ✔ ✔

Face studs in the same direction if possible, to allow easier fastening of plasterboard. However, installation of some services may require the studs to be positioned in opposite directions.

✔ ✔

Follow a structural design suitable for the intended dead, live and wind loads in accordance with AS/NZS 1170. ✔ ✔

Noggings are permitted to assist the fixing of services. Copper Chromium Arsenate (CCA) treated timber must not be used.

Page 11: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

3.2.1

Technical Advice 1300 724 505 knaufmetal.com.au186

EXTERNAL STEEL STUD AND TOP HAT WALLSFraming Installation

HORIZONTAL 50x15x1.15 TOP HAT SPACING TABLE (mm)

Span type

Stud spacing (mm)

Ultimate Wind Pressure Wu (kPa)

2.0 3.0 4.0 5.0 6.0 7.0

Serviceabilitydefl ection

limit Span / 250

Single span

600 900 640 480 380 320 270450 900 900 900 900 760 650400 900 900 900 900 900 900300 900 900 900 900 900 900

2 or more spans

600 900 800 600 480 400 340450 900 900 800 640 530 460400 900 900 900 720 600 520300 900 900 900 900 800 690

Serviceabilitydefl ection

limitSpan / 360

Single span

600 700 450 330 270 220 190450 900 900 800 640 530 450400 900 900 900 900 760 650300 900 900 900 900 900 900

2 or more spans

600 900 800 600 480 400 340450 900 900 800 640 530 460400 900 900 900 720 600 520300 900 900 900 900 800 690

HORIZONTAL TOP HAT FRAMING

FIGURE 1 Horizontal Steel Top Hat Layout

Horizontal Top Hats

Horizontal Top Hat span(stud spacing)

Horizontal Top Hat spacing

150mm

Wall noggings not shown for clarity

150mm

Steel stud substrate

1. Check maximum cladding span and fastener spacing requirements from the manufacturers literature. Maximum cladding weight 22 kg/m2 or seat cladding on floor.2. Top Hat spacing limited to 900mm to apply an evenly distributed load to stud frame substrate.3. Tables refer to Knauf Top Hats of grade G300 steel with ZincalumeTM AM150 corrosion protection.4. All Top Hats must be supported 150mm maximum from ends.5. Tables are applicable to self weight and uniformly distributed lateral pressures. Point loads and other loads such as shelf loads, or live loads are not considered.6. Calculations based upon either single span or 2-or-more spans, designed in accordance with AS/NZS 4600:2005 Cold Formed Steel Structures.7. Ultimate Load Case 1.2G + Wu8. Serviceability Load Case G + Ws, with deflection limited to either span/250 or span/360. Serviceability pressure taken as 65% of ultimate wind pressure.9. Connections checked using 2 x 12g hex-head screws into minimum 1.15mm thick G300 steel.10. Splicing of Top Hats is not permitted.11. Do not use the tables for vertical top hats over horizontal top hat construction.12. The project engineer must approve the nominated lateral pressures and deflection limits are appropriate for a specific project.

Page 12: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

3.2.1

Technical Advice 1300 724 505 knaufplasterboard.com.au 187

EXTERNAL STEEL STUD AND TOP HAT WALLSFraming Installation

HORIZONTAL 50x25x1.15 OR 50x35x0.75 TOP HAT SPACING TABLE (mm)

Span type

Stud spacing (mm)

Ultimate Wind Pressure Wu (kPa)

2.0 3.0 4.0 5.0 6.0 7.0

Serviceabilitydefl ection

limit Span / 250

Single span

600 900 900 900 900 900 860450 900 900 900 900 900 900400 900 900 900 900 900 900300 900 900 900 900 900 900

2 or more spans

600 900 800 600 480 400 340450 900 900 800 640 530 460400 900 900 900 720 600 520300 900 900 900 900 800 690

Serviceabilitydefl ection

limitSpan / 360

Single span

600 900 900 900 900 820 700450 900 900 900 900 900 900400 900 900 900 900 900 900300 900 900 900 900 900 900

2 or more spans

600 900 800 600 480 400 340450 900 900 800 640 530 460400 900 900 900 720 600 520300 900 900 900 900 800 690

1. Check maximum cladding span and fastener spacing requirements from the manufacturers literature. Maximum cladding weight 22 kg/m2 or seat cladding on floor.2. Top Hat spacing limited to 900mm to apply an evenly distributed load to stud frame substrate.3. Tables refer to Knauf Top Hats of grade G300 steel with ZincalumeTM AM150 corrosion protection.4. All Top Hats must be supported 150mm maximum from ends.5. Tables are applicable to self weight and uniformly distributed lateral pressures. Point loads and other loads such as shelf loads, or live loads are not considered.6. Calculations based upon either single span or 2-or-more spans, designed in accordance with AS/NZS 4600:2005 Cold Formed Steel Structures.7. Ultimate Load Case 1.2G + Wu8. Serviceability Load Case G + Ws, with deflection limited to either span/250 or span/360. Serviceability pressure taken as 65% of ultimate wind pressure.9. Connections checked using 2 x 12g hex-head screws into minimum 1.15mm thick G300 steel.10. Splicing of Top Hats is not permitted.11. Do not use the tables for vertical top hats over horizontal top hat construction.12. The project engineer must approve the nominated lateral pressures and deflection limits are appropriate for a specific project.

Page 13: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

3.2.1

Technical Advice 1300 724 505 knaufmetal.com.au188

EXTERNAL STEEL STUD AND TOP HAT WALLSFraming Installation

Many types of modern external cladding products require vertical top hat framing as the substrate. For structural and practical installation reasons, vertical top hats are not permitted to be installed directly over the vertical stud framing, therefore a layer of horizontal top hats directly fixed to the stud framing, then an additional layer of vertical top hats is the typical construction used [Refer to Figure 2]. If this type of construction is required for your project, please contact Knauf’s Technical Services for a framing solution.

When horizontal top hats (under) with vertical top hats (over) framing is used over wall stud framing, no thermal break is required.

Steel stud substrate

FIGURE 2 Vertical Top Hats over Horizontal Top Hats

VerticalTop Hat spacing

HorizontalTop Hat spacing

and VerticalTop Hat span

150mm

Wall noggings not shown for clarity

150mm

Horizontal Top Hats

Vertical Top Hats

VERTICAL TOP HATS OVER HORIZONTAL TOP HAT FRAMING

Page 14: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

3.2.1

Technical Advice 1300 724 505 knaufplasterboard.com.au 189

EXTERNAL STEEL STUD AND TOP HAT WALLSPlasterboard Layout Installation

Plasterboard LayoutNon-Fire

RatedFire

Rated

For single layer systems vertical joints must be 200mm minimum from the edge of any opening such as windows and doorways to minimise cracking at the joints. ✔ ✔

Horizontal Layout

Stagger butt joints in single layer systems by 300mm minimum on adjoining sheets and on opposite sides of the wall. ✔ ✔

Stagger butt joints in multi layer systems by 300mm minimum on adjoining sheets and between layers. ✔ ✔

First layer butt joints must be backed by a stud or back-blocked. [Refer to installation diagrams] ✔ ✔

Stagger recessed edges by 300mm minimum between layers. ✔ ✔

Stagger recessed edges in single layer systems by 300mm minimum on opposite sides of the wall or alternatively, back by a nogging. ✔

Vertical Layout

Stagger butt joints in single layer systems by 300mm minimum on adjoining sheets and on opposite sides of the wall. ✔ ✔

Stagger butt joints by 300mm minimum on adjoining sheets and between layers. ✔ ✔

First layer butt joints must be backed by a nogging or back-blocked. ✔

First layer butt joints must be backed by a nogging. ✔

Stagger recessed edges by 300mm minimum between layers and on opposite sides of the wall. ✔ ✔

Install plasterboard sheets horizontally when practical to minimise stud twisting and reduce the effect of glancing light.

Minimise butt joints by using long sheets.

Page 15: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

3.2.1

Technical Advice 1300 724 505 knaufmetal.com.au190

EXTERNAL STEEL STUD AND TOP HAT WALLSPlasterboard Fixing Installation

Plasterboard FixingNon-Fire

RatedFire

Rated

Drive screws to just below the sheet surface, taking care not to break the paper linerboard.

Laminating screws can be used to fix butt joints in the second and third layer.

Screw and Adhesive Method

Apply MastaGrip Stud Adhesive after the frame is clean, dry, and free from grease, dust and other contaminants.

Apply MastaGrip daubs 200mm minimum from screws and plasterboard edges.

Screw Only Method

Use the ‘Screw Only Method’ in tiled or fire rated areas. Stud adhesive is not permitted.

The ‘Screw and Adhesive Method’ is recommended for non-fire rated applications. MastaGrip will:

Minimise screw popping

Reduce the number of screw heads that may show in glancing light

SCREW TYPE AND MINIMUM LENGTH FOR THE INSTALLATION OF PLASTERBOARD TO STEEL

Plasterboard Thickness 1st Layer 2nd Layer 3rd Layer

10mm 25mm screw 40mm screw* –

13mm 25mm screw 40mm screw* 60mm screw*

16mm 30mm screw 45mm screw* 65mm screw*

For steel ≤ 0.75mm BMT minimum 6g fine thread needle point screws. For steel ≥ 0.75mm BMT minimum 6g fine thread drill point screws. *38mm – 10g Laminating screws may be used as detailed in installation diagrams.

Page 16: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

3.2.1

Technical Advice 1300 724 505 knaufplasterboard.com.au 191

EXTERNAL STEEL STUD AND TOP HAT WALLSExterior Cladding Installation

Exterior CladdingNon-Fire

RatedFire

Rated

The following cladding sheets or planks are not considered detrimental to the FRL of the wall: PERMAROCK Outdoor Fibre cement Wood or timber Steel Aluminium PVC Rendered polystyrene Cladding fixed and supported independently of the wall

Fix cladding or cladding top hats to the steel frame through the TruRock.

Extend the external fire rated wall up to the non-combustible roof covering or non-combustible eaves lining. [Refer to Construction Details]

Exterior cladding and moisture barrier must provide protection from the weather.

Use construction techniques that direct condensation and rain away from plasterboard.

Knauf recommends a drained cavity between the external cladding and the TruRock for weathertightness.

Top hats between external cladding and external plasterboard do not change the FRL of the system.

Plasterboard must not be fixed to head track

Fix on each stud 60 - 100mm

Fix on each stud 50mm

Fix on each stud 50mm

300mm max

300mm max

200mm min

10 - 50mm

200mm max

Recessed Edges Stagger recessed edges by 300mm

min on opposite sides of the wall or back by a nogging

Sealant Use Knauf Bindex Fire and Acoustic Sealant on all gaps and around perimeter to maintain fire and acoustic integrity

Butt Joints Fix at 200mm max centres. Stagger by 600mm min

on adjoining sheets and on opposite sides of the wall

150mm min

Field 300mm max

Butt Joints Fix on a stud or alternatively, float between

studs using 51mm min track

Floating butt joint backed with 51mm min track

Web of track

Sheet Edges Fix screws 10 - 50mm from sheet edges except at head and base tracks

Openings 300mm maxvertical screw spacing

Corners 300mm max

FIGURE 4 Fire Rated 2 Layers - Horizontal + HorizontalScrew Only Method

Corners2nd layer300mm max

Fix on each stud 60 - 100mm

Sealant Use Knauf Bindex Fire and Acoustic Sealant on all gaps and around perimeter to maintain fire and acoustic integrity

Plasterboard must not be fixed to head trackRecessed Edges Fix 1st and

2nd layer recessed edges on each stud. Stagger recessed edges by

300mm min between layers.

Field1st layer 600mm max

Corners1st layer 600mm

max1st layer 600mm max

Field2nd layer 300mm max

Stagger recessed edges by 300mm min between layers

2nd layer 300mm max

Openings1st layer 600mm max vertical screw spacing

Butt Joints1st layer butt joints

must be fixed at 600mm max

centres and backed by a stud, or

alternatively back with 51mm min

track

Sheet EdgesFix screws

10 - 50mm from sheet edges

except at head and base tracks

Stagger butt joints by 300mm min between layers

2nd layer floating butt joint

Openings2nd layer300mm maxvertical screw spacing

10 - 50mm

Sheet Edges Fix screws 10 - 50mm from sheet edges except at head and base tracks

FIGURE 3 Fire Rated 1 Layer - HorizontalScrew Only Method

1st layer

2nd layer

Butt Joints 2nd layer. Fix on a stud at 200mm max centres. Alternatively, float butt joints and laminate to 1st layer using laminating screws at 200mm max centres.

Sheet Width Fixing Pattern600mm S S S900mm S S S S

1200mm S S S S S1350mm S S S S S S

Page 17: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

3.2.1

Technical Advice 1300 724 505 knaufmetal.com.au192

EXTERNAL STEEL STUD AND TOP HAT WALLSExterior Cladding Installation

Plasterboard must not be fixed to head track

Fix on each stud 60 - 100mm

Fix on each stud 50mm

Fix on each stud 50mm

300mm max

300mm max

200mm min

10 - 50mm

200mm max

Recessed EdgesStagger recessed edges by 300mm

min on opposite sides of the wall or back by a nogging

Sealant Use Knauf Bindex Fire and Acoustic Sealant on all gaps and around perimeter to maintain fire and acoustic integrity

Butt Joints Fix at 200mm max centres. Stagger by 600mm min

on adjoining sheets and on opposite sides of the wall

150mm min

Field300mm max

Butt Joints Fix on a stud or alternatively, float between

studs using 51mm min track

Floating butt joint backed with 51mm min track

Web of track

Sheet Edges Fix screws 10 - 50mm from sheet edges except at head and base tracks

Openings300mm maxvertical screw spacing

Corners300mm max

FIGURE 4 Fire Rated 2 Layers - Horizontal + HorizontalScrew Only Method

Corners2nd layer300mm max

Fix on each stud 60 - 100mm

Sealant Use Knauf Bindex Fire and Acoustic Sealant on all gaps and around perimeter to maintain fire and acoustic integrity

Plasterboard must not be fixed to head trackRecessed Edges Fix 1st and

2nd layer recessed edges on each stud. Stagger recessed edges by

300mm min between layers.

Field 1st layer 600mm max

Corners1st layer 600mm

max1st layer 600mm max

Field 2nd layer 300mm max

Stagger recessed edges by 300mm min between layers

2nd layer 300mm max

Openings1st layer 600mm max vertical screw spacing

Butt Joints1st layer butt joints

must be fixed at 600mm max

centres and backed by a stud, or

alternatively back with 51mm min

track

Sheet EdgesFix screws

10 - 50mm from sheet edges

except at head and base tracks

Stagger butt joints by 300mm min between layers

2nd layer floating butt joint

Openings 2nd layer300mm maxvertical screw spacing

10 - 50mm

Sheet Edges Fix screws 10 - 50mm from sheet edges except at head and base tracks

FIGURE 3 Fire Rated 1 Layer - HorizontalScrew Only Method

1st layer

2nd layer

Butt Joints 2nd layer. Fix on a stud at 200mm max centres. Alternatively, float butt joints and laminate to 1st layer using laminating screws at 200mm max centres.

Sheet Width Fixing Pattern600mm S S S900mm S S S S

1200mm S S S S S1350mm S S S S S S

FIGURE 5 Fire Rated 3 Layers - Horizontal + Horizontal + HorizontalScrew Only Method

Fix on each stud 60 - 100mm

Sealant Use Knauf Bindex Fire and Acoustic Sealant on all gaps and around perimeter to maintain fire and acoustic integrity

Openings1st layer 600mm max2nd layer300mm max 3rd layer400mm max

Plasterboard must not be fixed to head track

Butt Joints 1st layer butt joints must be fixed at 600mm

max centres and be backed by a stud, or alternatively with

51mm min track2nd layer butt joint fixed to a stud

Butt Joints Stagger butt joints

by 300mm min between all layers

Field 3rd layer

laminate at 400mm max

Fix on each stud 50mm

Field 1st layer 600mmmax

Butt Joints 2nd layer.Fix on a stud at 200mm max centres. Alternatively, float butt joints and laminate to 1st layer using laminating screws at 200mm max centres.

3rd layer 400mm max

Field 2nd layer 300mm max

Corners1st layer 600mm max2nd layer 300mm max3rd layer 400mm max

Sheet Edges Fix screws 10 - 50mm from sheet edges except at head and base tracks

10 - 50mm

Recessed Edges Fix 1st and 2nd layer recessed edges on each stud. Stagger recessed edges by 300mm min between all layers.

1st layer

2nd layer

3rd layer

Recessed Edges 3rd layer

Laminate to previous layer

using laminating screws at 400mm

max centres Stagger butt joints by 300mm min on

adjoining sheets

Butt Joints 3rd layerLaminate to previous layer using laminating screws at

200mm max centres

Page 18: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

3.2.1

193Technical Advice 1

DetailsEXTERNAL STEEL STUD AND TOP HAT WALLS

Construction Details

3.2.1

Technical Advice 1300 724 505 knaufplasterboard.com.au 193

Details

NON-FIRE RATED HEAD AND BASE DETAILS FOR EXTERNAL STUD WALLS

100mm between soffit and nogging

Fix 60-100mm from sheet top. Do not fix through track

Fix stud through slotted deflection head track using 10g screws (additional nogging 100mm below is not required)

Fix nogging to both sides of stud using 10g screws

20mm clearance to stud and plasterboard

Fix 60-100mm from sheet top. Do not fix through track

20mm clearance to stud and plasterboard

FIGURE 6 Wall HeadDeflection Head TrackSection

FIGURE 8 Wall HeadSlotted Deflection Head TrackSection

FIGURE 9 Wall HeadSlotted Deflection Head TrackElevation

NON-FIRE RATEDHEAD AND BASE DETAILS FOR EXTERNAL STUD WALLS

FIGURE 7

Fix 60-100mm from sheet top. Do not fix through track

Accujamb Connector Bracket (AJCB) to reinforce stud to top track connec-tion. Use 12g Hex-head screws through slots to accommodate slab deflection.

20mm clearance to stud and plasterboard

FIGURE 7 Wall HeadWith Accujamb Connector BracketSection

Sealant, if required to maintain acoustic, thermal integrity

5-10mmclearance toplasterboard

Fix 50mm from sheet bottom. Do not fix through track Fix track to both

sides of stud using 10g screws

Fix nogging to both sides of stud using 10g screws. Refer to engineer’s design for number of noggings required

Fix nogging to both sides of stud using 10g screws. Refer to engineer’s design for number of noggings required

Sealant, if required to maintain acoustic, thermal integrity

Sealant, if required to maintain acoustic, thermal integrity

5-10mmclearance toplasterboard

Fix 50mm from sheet bottom. Do not fix through track

Sealant, if required to maintain acoustic, thermal integrity

Sealant, if required to maintain acoustic, thermal integrity

FIGURE 10 Wall BaseSection

FIGURE 11 Wall BaseSection

Accujamb Connector Bracket (AJCB) to reinforce stud to bottom track connection. Use 12g Hex-head screws through outer holes

Insulation not shown for clarity. Refer to

System tables for lining and insulation requried.

Slotted DHT are not suitable where

inter-storey drift required

Head brackets are not suitable where

inter-storey drift required

Knauf plasterboard

Knauf plasterboard

Knauf plasterboard

When fixed 8mm from the bottom of the slot, the Slotted Deflection Head allows for 15mm downward, and 5mm upwards slab movement.

Stud

Single anchor for 92mm studs into concrete, or 2 anchors across width if using 150mm studs

Single anchor for 92mm studs into concrete, or 2 anchors across width if using 150mm studs. Check anchor’s minimum edge distance with anchor manufacturer.

Page 19: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

3.2.1 EXTERNAL STEEL STUD AND TOP HAT WALLSConstruction DetailsDetails

194 Technical Advice 1300 724 505 knaufmetal.com.au

3.2.1

194

Details

NON-FIRE RATED TYPICAL DETAILS FOR NON-LOAD BEARING EXTERNAL STEEL STUD WALLS

NON-FIRE RATEDTYPICAL DETAILS FOR NON-LOAD BEARING EXTERNAL STEEL STUD WALLS

FIGURE 12 External Steel Stud Wall HeadWall with cladding over thermal breakSection

FIGURE 14 External Steel Stud Wall BaseWall with cladding over thermal breakSection

Thermal break

Base track

Knauf Earthwool insulation

Wall wrap

External cladding

Single anchor for 92mm studs into concrete, or 2 anchors across width if using 150mm studs

Knauf steel stud

Knauf steel stud

FIGURE 13 External Steel Stud Wall HeadWall with cladding over horizontal top-hatsSection

FIGURE 15 External Steel Stud Wall BaseWall with cladding over horizontal top-hatsSection

Nogging

Horizontal top hat supporting external cladding

Horizontal top hat supporting external cladding

Damp proof course, if required

Fix top hat to studs using minimum 12g hex-head screws

Damp proof course, if required

External cladding

Knauf plasterboard

Refer to Figures 4, 5 and 6 for typical stud wall head details

Refer to Figures 4, 5 and 6 for typical stud wall head details

Non-load bearing walls are unsuitable

for bracing wall applications

Top hats must not be

fixed to noggings or deflection head tracks

Slotted DHT are not suitable where

inter-storey drift required

Refer to cladding manufacturer for

specific installation detail

Refer to Figures 8 and 9 for typical stud wall base details

Page 20: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

3.2.1

195Technical Advice 1

DetailsEXTERNAL STEEL STUD AND TOP HAT WALLS

Construction Details

NON-FIRE RATEDTYPICAL DETAILS FOR NON-LOAD BEARING EXTERNAL STEEL STUD WALLS

FIGURE 16 External Steel Stud Wall HeadStud with cladding over horizontal + vertical Top HatsSection

Horizontaltop hats

FIGURE 18 External Steel Stud Wall BaseStud with cladding over horizontal + vertical Top HatsSection

Horizontaltop hats

Vertical top hats supporting external cladding

External cladding

Vertical top hats supporting external cladding

Nogging

Earthwool insulation

Horizontaltop hats

Vertical top hats supporting external cladding

External cladding

External cladding

Non-load bearing walls are unsuitable

for bracing wall applications

Knauf steel stud

Base track

FIGURE 17 External Steel Stud Wall HeadStud with cladding over horizontal + vertical Top HatsSection

Knauf plasterboard

Slotted DHT are not suitable where

inter-storey drift required

Refer to cladding manufacturer for

specific installation detail

Fix top hat to studs using minimum 12g hex-head screws

Fix top hat to studs using minimum 12ghex-head screws

Refer to Figures 4, 5 and 6 for typical stud wall head details

Refer to Figures 4, 5 and 6 for typical stud wall head details

Refer to Figures 8 and 9 for typical stud wall base details

NON-FIRE RATED TYPICAL DETAILS FOR NON-LOAD BEARING EXTERNAL STEEL STUD WALLS

Page 21: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

3.2.1 EXTERNAL STEEL STUD AND TOP HAT WALLSConstruction DetailsDetails

196 Technical Advice 1300 724 505 knaufmetal.com.au

Earthwool insulation

FIRE RATEDTYPICAL DETAILS FOR NON-LOAD BEARING EXTERNAL STEEL STUD WALLS

FIGURE 20 External Steel Stud Wall HeadStud with cladding over horizontal + vertical Top HatsFire rated from both directions - Section

Horizontaltop hats

FIGURE 22 External Steel Stud Wall BaseStud with cladding over horizontal + vertical Top HatsFire rated from both directions - Section

Horizontaltop hats

Vertical top hats supporting external cladding

External cladding

Vertical top hats supporting external cladding

Sill opening member

Header opening member

External cladding

Knauf fire rated plasterboard

Knauf steel stud

Knauf fire and water resistant plasterboard

Knauf fire and water resistant plasterboard

Non-load bearing walls are unsuitable

for bracing wall applications

Knauf Bindex Fire and Acoustic Sealant required to maintain integrity

Knauf Bindex Fire and Acoustic Sealant required to maintain integrity

Top Hats must not be fixed to noggings or

deflection head tracks

FIGURE 19 External Steel Stud Wall HeadStud with cladding over horizontal + vertical Top HatsFire rated from the outside only - Section

FIGURE 21 External Steel Stud Wall BaseStud with cladding over horizontal + vertical Top HatsFire rated from the outside only - Section

Horizontaltop hats

Vertical top hats supporting external cladding

External cladding

Vertical top hats supporting external cladding

Nogging

Knauf plasterboard

Knauf steel stud

Slotted DHT are not suitable where

inter-storey drift required

Knauf fire and water resistant plasterboard

Knauf fire and water resistant plasterboard

Knauf Bindex Fire and Acoustic Sealant required to maintain integrity

Horizontaltop hats

Knauf Bindex Fire and Acoustic Sealant required to maintain integrity

Refer to cladding manufacturer for

specific installation detail

Fix top hats using minimum 12g hex-head screws

External cladding

Fix top hats using minimum 12g hex-head screws

Refer to Figures 4, 5 and 6 for typical stud wall head details

Refer to Figures 8 and 9 for typical stud wall base details

FIRE RATED TYPICAL DETAILS FOR NON-LOAD BEARING EXTERNAL STEEL STUD WALLS

Page 22: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

3.2.1

197Technical Advice 1

DetailsEXTERNAL STEEL STUD AND TOP HAT WALLS

Construction Details

NON-FIRE RATEDTYPICAL HEAD AND BASE SECTION DETAILS FOR EXTERNAL STUD WALLS

FIGURE 23 External Steel Stud Wall HeadStud with horizontal Top Hats under AACSection

FIGURE 25 External Steel Stud Wall BaseStud with horizontal Top Hats under AACSection

Horizontal top hats supporting AAC panels or other cladding

Nogging

Knaufsteel stud

Knaufsteel stud

Earthwool insulation

Knauf plasterboard

FIGURE 24 External Steel Stud Wall HeadStud with brick veneerSection

FIGURE 26 External Steel Stud Wall BaseStud with brick veneerSection

Nogging

Earthwool insulation

Knauf plasterboard

Brick veneer ties must be compatible with Zincalume steel. Stainless steel

brick ties and other more noble metals must be electrically isolated from the steel studs.

Refer to cladding manufacturer for

specific installation detail

Fix top hat to studs using minimum 12g hex-head screws

Fix top hat to studs using minimum 12g hex-head screws

Horizontal top hats supporting AAC panels or other cladding

Refer to Figures 4, 5 and 6 for typical stud wall head details

Refer to Figures 8 and 9 for typical stud wall base details

NON-FIRE RATED TYPICAL HEAD AND BASE SECTION DETAILS FOR EXTERNAL STUD WALLS

Page 23: External Steel Stud and Top Hat Walls · 2019-06-03 · 3.2.1 178 Technical Advice 1300 724 505 knaufmetal.com.au EXTERNAL STEEL STUD AND TOP HAT WALLS Systems Fire Rated * R-Value

3.2.1 EXTERNAL STEEL STUD AND TOP HAT WALLSConstruction DetailsDetails

198 Technical Advice 1300 724 505 knaufmetal.com.au

FIRE RATEDTYPICAL DETAILS FOR SPANDREL WALLS

Earthwool insulation

FIGURE 27 Spandrel Steel Stud WallSpandrel wall tilted into position near facadeSection

Sill member

Knauf steel stud

Spandrel wall height is limited to 1000mm for a non-load bearing wall (FRL -/60/60). For a load bearing spandrel wall (FRL 60/60/60) the wall can be structurally designed to ambient temperature requirements.

Knauf Bindex Fire and Acoustic Sealant required to maintain integrity

Knauf fire rated plasterboard, installed after wall tilted into position

Knauf fire rated plasterboard, installed after wall tilted into position

Knauf fire and water resistant plasterboard

Knauf fire and water resistant plasterboard

Use masonry fixings at 600mm max centres vertically

Backing rod and Knauf Bindex Fire and Acoustic Sealant required to maintain integrity

Optional stopping angle

600mm max100mm max

10mm clearance to plasterboard

FIGURE 28 Spandrel Steel Stud Wall EndSpandrel wall tilted into position near facadeplan

Facade

Facade

2 layers of Knauf fire and water resistant plasterboard to maintain fire integrity

FIRE RATED TYPICAL DETAILS FOR SPANDREL WALLS