Upload
others
View
7
Download
0
Embed Size (px)
Citation preview
Checked Version Release date QA V4.2.9 F1-F2 EN 18.02.2013 2011
S/601 Controller
Installation Manual
FLOW CONTROL
F1 - F2 Flow controller
Equflow BV Manual Controller S/601 F1 - F2 www.equflow.com Revision V4.2.9 18.02.2013 page 2
Introduction Thank you for using the S/601 flow, batch and pump control series. This manual was prepared to provide instructions for the operation of the S/601 F1 – F2 Flow controller We advise you to read this manual entirely before operating this instrument.
Despite effort to avoid errors in the preparation of this manual, Equflow cannot be held liable for any mistakes or consequences related to mistakes that may be present.
Copyright: Equflow BV
Equflow BV Manual Controller S/601 F1 - F2 www.equflow.com Revision V4.2.9 18.02.2013 page 3
Index:
INTRODUCTION ........................................................................................................................................ 2
INDEX: ....................................................................................................................................................... 3
PART I: SYSTEM DESCRIPTION ............................................................................................................. 4
GENERAL FUNCTION DESCRIPTION: ........................................................................................................... 4 OPTIONAL DATA ACQUISITION: .................................................................................................................. 4 MOUNTING AND CONNECTION: .................................................................................................................. 4 PARAMETERS: .......................................................................................................................................... 4
PART II : QUICK SET UP .......................................................................................................................... 5
1. CONNECT (BEFORE SWITCHING ON POWER!) .......................................................................................... 5 2. SET PARAMETERS ................................................................................................................................ 6
Approximate K-factor (impulses/liter) per model: .............................................................................. 7 3. CALIBRATE FLOW METER(S) .................................................................................................................. 8
Procedure for Automatic calibration: ................................................................................................. 8
PART III : PROGRAMMING AND OPERATING....................................................................................... 9
PROGRAMMING INSTRUCTIONS S/601 F1 – F2 FLOW CONTROLLER ............................................................ 9 HOW TO PROGRAM: .................................................................................................................................. 9
PART IV. ALARM MESSAGES............................................................................................................... 10
ALARM AND ALARM MESSAGES ............................................................................................................... 10 WHAT TO DO IN CASE OF AN ALARM ......................................................................................................... 10 ALARM MESSAGES AND POSSIBLE CAUSES ............................................................................................... 10
PART V. APPENDIX – TECHNICAL SPECIFICATIONS ....................................................................... 11
TECHNICAL SPECIFICATIONS ................................................................................................................... 11 CONNECTION AT THE CIRCUIT BOARD ...................................................................................................... 11 PRINT LAYOUT........................................................................................................................................ 12
Equflow BV Manual Controller S/601 F1 - F2 www.equflow.com Revision V4.2.9 18.02.2013 page 4
PART I: SYSTEM DESCRIPTION
General Function description:
The Equflow S/601 F1 – F2 Flow controller enables measuring flow-velocity and totalizing transferred liquids, by measuring the flow with a flow meter. Key functions (F1 version):
Measuring 1 flow velocity, including totalizing transferred liquid volume.
Monitoring flow process parameters like minimum and maximum flow rates.
Controlling leak detection with programmable setpoints.
Generating an internal or/and external alarm if a setpoint exceeds.
Data logging (only if provided with a communication X-port and software)
Displaying actual flow and totalized volume F2 version: Like the F1 version but for 2 channels
Optional Data acquisition:
Flow velocity versus time and totalized volumes are stored in the S/601 memory. By adding an optional X-communication port, data can be exported to a network or PC and the S/601 unit will have its own IP address. The standard S/601 is not provided with an X-port connection. This should be ordered together with the S/601 controller and will be integrated on request. Ask your supplier for extra information or send an email to [email protected].
Mounting and connection:
If possible, mount the controller in a dry and clean location. Avoid direct sunlight on the flow meter as it may affect the readings.
Check all electrical connections (see part II, page 5 of this manual) before switching on the power. Power supply = 24VDC.
Use the appropriate cable connections to connect flow meter to the S/601 Flow controller. Cable connections can be found in part II, page 5.
Parameters:
Because the S/601 F1 - F2 Flow controller can be used in multiple applications and modes of operation, the appropriate parameters (K-factor, display functions, alarm settings, etc..) must be programmed prior to use.
mailto:[email protected]
Equflow BV Manual Controller S/601 F1 - F2 www.equflow.com Revision V4.2.9 18.02.2013 page 5
PART II : QUICK SET UP 2-line Digital Display 4-Button control panel On/Off button 4 Alarm/Operation lights Connections at the rear
1. Connect (before switching on power!)
I. Connect Power
a. Insert plug of the 24 VDC Adapter to P.
II. Connect flow meter(s)
a. When using a 3,5mm stereo jack plug:
Insert the jackplug flow meter(s) 1 (and 2) into F1 (and F2).
b. When NOT using a plug: connect wires of the flow meter(s) 1 (and 2) to the screw connectors.
Black 0V to GND White Signal (A):
- Flow meter 1 to SIG1 - Flow meter 2 to SIG2
Red 5-24V to V-S
P
V-S GND SIG1
F1 F2
SIG2
Equflow BV Manual Controller S/601 F1 - F2 www.equflow.com Revision V4.2.9 18.02.2013 page 6
III. Connect Network connection (Ethernet) In case this option is selected, you will have a network connection on your S/601 controller to store data on your PC.
Caution: Always check wiring instructions provided with the S/601 controller. Changes may occur without notice.
2. Set parameters Switch the unit on, Idle screen shows: Controller set for 1 flow: Controller set for 2 flows:
Navigate through menu with keys: [prog]: Select/Save parameter digit/value [up/down]: Change parameter values [Start/Stop]: Exit to previous level.
Press [prog] to enter menuoptions:
Menu option Key Description Digital display
Totals flow 1 (2) [prog] Read display; Total amount of starts and total volume per channel
[↓]
Cal. Sensor 1 (2) [prog] Display: last measurem. Enter the right volume (see “3. Calibrate”)
[↓]
Login with Pin [prog] Input PIN-code machine operator/technician
[↓]
Units flow 1 (2) [prog] Select liter/milliliter/ pounds(US)/...
[↓]
Time units flow 1 (2) [prog] Select volume per min/sec/hour.
[↓]
Decimals flow 1 (2) [prog] Select 0-5 decimals for higher resolution
[↓]
Bro
wse
th
rou
gh
pa
ram
ete
rs u
sin
g U
P a
nd
DO
WN
arr
ow
s
Equflow BV Manual Controller S/601 F1 - F2 www.equflow.com Revision V4.2.9 18.02.2013 page 7
Approximate K-factor (impulses/liter) per model:
PFA models PVDF models
0045 110.000 100.000
0085 6.350 4.500
0125 2.050 N/A
Alarm delay 1 (2) [prog] After the controller is started it expects a flow. Input in seconds
[↓]
Max. flow 1 (2) alarm level
[prog] Max. flowrate setpoint for an alarm. Input: volume
[↓]
Min. flow 1 (2) alarm level
[prog] Min. flowrate setpoint for an alarm. Input: volume
[↓]
K-factor sensor 1 (2) [prog] Input pulses/liter
[↓]
Language [prog] Select English or Dutch
[↓]
Firmware version [prog] Read display
[↓]
Logout user [prog] Back to basic operator
Bro
wse
th
rou
gh
pa
ram
ete
rs u
sin
g U
P a
nd
DO
WN
arr
ow
s
Equflow BV Manual Controller S/601 F1 - F2 www.equflow.com Revision V4.2.9 18.02.2013 page 8
3. Calibrate Flow meter(s)
Complete parameter set-up before calibration. Calibration liquid should be the same liquid intended for use.
Procedure for Automatic calibration:
1. Set up flow meter as shown in figure 1; 2. Press start on S601 controller; 3. Start pump at calibration flow rate and wait until the flow is stable; 4. Collect liquid in graduated cylinder for < 1 minute; 5. Stop the pump; 6. Press stop on S601 controller; 7. Press prog to enter programming mode and browse to “calibrate sensor” (1 or 2); 8. Change the volume shown into the actual measured volume and press prog; 9. Press stop until back at idle screen;
a. Liquid reservoir
b. Pump c. Flow meter (connected to the S601 controller) d. Graduated cylinder
Typical parameter value table
Units flow Milliliter
Decimals flow 0,0
Time units flow Volume/Minutes
K-factor Sensor See Defaults
Text Idle Line 1 Flow rate 1
Text Idle Line 2 Total Volume 1
Text Dose Line 1 Flow rate 1
Text Dose Line 2 Total Volume 1
b.
c.
a. d.
Equflow BV Manual Controller S/601 F1 - F2 www.equflow.com Revision V4.2.9 18.02.2013 page 9
PART III : PROGRAMMING AND OPERATING
Programming instructions S/601 F1 – F2 Flow controller
Activate the controller by switching on the on/off button on the right-side of the housing.
The display shows the name and version-number of the controller. After a few seconds the display shows:
o F1 version: actual flow (F1) and the total flow (T1) 1
o F2 version: actual flow (F1) and actual flow (F2)
How to program:
Press prog to enter programming-mode.
Select the preferred function to adjust, by scrolling the menu using V or Ʌ, followed by prog. Now each digit can be adjusted by using V or Ʌ, directly followed by pressing prog to save the
digit (after adjusting each digit).
To cancel an adjustment or go back to the previous menu; press start/stop
In order to protect your adjustments and store data always press prog to save settings after making an adjustment in PIN mode.
Adjusting some higher level settings a PIN code must be used at the function ”Login with pin” PIN codes: 0001 = access to Machine Operator mode 0022 = access to Technician mode
Nbr
Functions at user-mode
Function Basic
Operator Machine Operator
Technician
1 Totals flow 1 (2) v v v
2 Cal. Sensor 1 (2) v v v
3 Login with pin v v v
4 Units flow 1 (2) v v
5 Time units flow 1 (2) v v
6 Decimals flow 1 (2) v v
7 Alarm delay 1 (2) v v
8 Firmware version v v
9 Logout user v v
10 Max flow 1 (2) alarm level v
11 Min flow 1 (2) alarm level v
12 K factor sensor 1 (2) v
13 Language v
1 The information showed in the display can (within ranges) be adjusted by equflow to the demands of
the user.
Equflow BV Manual Controller S/601 F1 - F2 www.equflow.com Revision V4.2.9 18.02.2013 page 10
PART IV. ALARM MESSAGES
Alarm and Alarm messages
In case of an alarm, the controller will respond as follows:
1 Display text will show the alarm message. 2 The red alarm-led F1 or F2 will light. 3 The system buzzer will beep. 4 The alarm output [4] will trigger (NPN).
An alarm will only be generated if the controller is in start mode by pressing [Start]. An alarm will be turned off if the value programmed is 0 (zero).
What to do in case of an alarm
1 Write down the text displayed. 2 Press Stop button to release alarm. 3 Solve the problem.
Alarm messages and possible causes
Alarm messages
Alarm Text Possible cause Solution
Min or max flow
The controller is expecting a flow but does not measure one; or The flow is too high (max flow); or The flow is too low (min flow);
Valve does not open, pump start
Sensor gives no signal
Pump not running (Air pressure?)
Tank empty
Filter blocked?
Depends on what caused the alarm. Solve problem depending alarm cause.
External alarm Controller received a stop command from the external input. Solve external issue.
Equflow BV Manual Controller S/601 F1 - F2 www.equflow.com Revision V4.2.9 18.02.2013 page 11
PART V. APPENDIX – TECHNICAL SPECIFICATIONS
Technical specifications
Supply : 24 VDC Power consumption : ca 200 mA Fuse : F 2 Amp at pcb Max. Pulse freq. : 6000 Hz Display : 2 lines / 16 digits Ambient temp. : -10 - +60 C° Dimensions encl. : 130 x 105 x 195 (Br x H x D) Waterproof : IP65
Connection at the circuit board
Nr. Connection: Remark:
1 Zero 24 VDC Supply
2 + 24 VDC Supply
3 Zero 24 VDC
4 + 24 VDC
5 Sensor + Flow sensor 2
6 Sensor pulse Flow sensor 2
7 Sensor - Flow sensor 2
8 Sensor + Flow sensor 1
9 Sensor pulse Flow sensor 1
10 Sensor - Flow sensor 1
11 Plus 24 volt DC
12 External input 4 connect to +24 volt Reserve
13 External input 3 connect to +24 volt Stop flow 1 and 2
14 External input 2 connect to +24 volt Start flow 2
15 External input 1 connect to +24 volt Start flow 1
16 Zero of 24 VDC
17 N.C.
18 N.C.
19 N.C.
20 Spare
21 Output 4 (switching to zero volt) Attention 24 DC Alarm output
22 Output 3 (switching to zero volt) Reject pulse max or min overdose
23 Output 2 (switching to zero volt) Valve and or pump start 2
24 Output 1 (switching to zero volt) Valve and or pump start 1
25 + 24 VDC
Equflow BV Manual Controller S/601 F1 - F2 www.equflow.com Revision V4.2.9 18.02.2013 page 12
Print layout