Facility Management – Facility Operations Business Rules Manual

Page 2: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

1

Contents Weekly Schedules for Anschutz and Denver Campuses ....................................................................... 1

CSC Work Order Routing Schedule ....................................................................................................... 2

Integrating the Maximo Program into CU Denver Processes ....................................................................... 3

Guidelines ................................................................................................................................................. 3

Responsibilities ......................................................................................................................................... 4

Processes ................................................................................................................................................... 6

Flow Chart Definitions ........................................................................................................................... 6

Anschutz Medical Campus Emergency Response Process .................................................................... 8

Denver Campus Emergency Response Process .................................................................................... 9

After Hours Anschutz Medical Campus Non-Emergent Assistance Process ....................................... 14

Elevator Service Call ............................................................................................................................ 15

Shift CM WO Evolution ....................................................................................................................... 17

Zone CM WO Evolution ....................................................................................................................... 18

Trades CM WO Evolution .................................................................................................................... 19

CSC Service Request Evolution ............................................................................................................ 20

Maximo Service Request Evolution .................................................................................................... 21

Emergency Freezer Service Request Evolution ................................................................................... 22

Time Recording ................................................................................................................................... 23

Expense Allocation Process ................................................................................................................. 24

Work Order Escalation Process ........................................................................................................... 26

Training and Event Resource Request Process ................................................................................... 27

Work Permit Process ........................................................................................................................... 29

WO Creation and Work Management Processes ............................................................................... 30

Defined Maximo Actions .............................................................................................................................. 34

How to Create Work Orders in Maximo CSC\Shift ................................................................................ 34

How to Classify Work Orders In Maximo .............................................................................................. 38

CSC Will Record Items, Materials and Services Transactions on Work Order’s ..................................... 42

How to Complete a Work Order ........................................................................................................... 44

How to Make Work Order GL Account, Classification, and Time Entry Corrections .............................. 44

Using Non-Building Speed Types on Work Orders ................................................................................ 45

How to Create a New Maximo Purchase Order .................................................................................... 46

How to Change a Maximo Purchase Order after Approval ................................................................... 47

Page 3: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

2

Matching Kronos Pay Codes with Maximo Labor Work Types .............................................................. 48

Modifying Maximo Person Groups by CSC ........................................................................................... 49

Recording Time in Maximo................................................................................................................... 51

CU Denver Policies and Procedures ............................................................................................................ 52

Policy Links .............................................................................................................................................. 52

Fire Watch Protocols ............................................................................................................................... 54

OOM and SOM Assignments .................................................................................................................. 57

BMO Project Rep Responsibilities for Capital Projects ........................................................................... 58

Using the CU Denver Daily Log ............................................................................................................... 60

On Going Issues ................................................................................................................................... 60

Out of Service Equipment ................................................................................................................... 60

Daily Issues .......................................................................................................................................... 61

Work Group Accountability ................................................................................................................ 62

Searching and Printing ........................................................................................................................ 62

Searching the Daily Log ....................................................................................................................... 62

BMO Emergency Response Manual .................................................................................................... 64

Responsibilities: ................................................................................................................................ 65

Flood Procedure (Interior) .................................................................................................................. 66

Definitions: ......................................................................................................................................... 66

First Responder ................................................................................................................................ 66

SOM Checklist .................................................................................................................................. 67

Major Water Main or Sewer Line Break Emergency Procedure (Exterior) ......................................... 68

Definition ............................................................................................................................................ 68

First Responder ................................................................................................................................ 68

SOM Checklist .................................................................................................................................. 68

Electrical Reset for Power Loss & Power Bumps ................................................................................ 69

Definition ............................................................................................................................................ 69

First Responder ................................................................................................................................ 69

Zone 1 ................................................................................................................................................ 70

Zone 2 ................................................................................................................................................ 70

Zone 3 ................................................................................................................................................ 71

Zone 4 ................................................................................................................................................ 72

Zone 5 ................................................................................................................................................ 73

Page 4: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

3

Zone 6 ................................................................................................................................................ 75

Zone 7 ................................................................................................................................................ 77

Zone 8 ................................................................................................................................................ 79

SOM Checklist .................................................................................................................................. 79

Loss of Chilled Water .......................................................................................................................... 80

First Responder ................................................................................................................................ 80

Zone 1 ................................................................................................................................................ 81

Zone 2 ................................................................................................................................................ 82

Zone 3 ................................................................................................................................................ 83

Zone 4 ................................................................................................................................................ 84

Zone 5 ................................................................................................................................................ 86

Zone 6 ................................................................................................................................................ 87

Zone 7 ................................................................................................................................................ 91

Zone 8 ................................................................................................................................................ 96

Elevator Emergencies .......................................................................................................................... 98

Definition ............................................................................................................................................ 98

First Responder ................................................................................................................................ 98

SOM Checklist .................................................................................................................................. 98

Fire Alarm Response ........................................................................................................................... 99

Definition ............................................................................................................................................ 99

First Responder ................................................................................................................................ 99

SOM Checklist .................................................................................................................................. 99

Loss of Building HVAC ......................................................................................................................... 99

Definition .......................................................................................................................................... 100

First Responder .............................................................................................................................. 100

Zone 1 .............................................................................................................................................. 101

Zone 2 .............................................................................................................................................. 102

Zone 3 .............................................................................................................................................. 103

Zone 4 .............................................................................................................................................. 103

Zone 5 .............................................................................................................................................. 105

Zone 6 .............................................................................................................................................. 105

Zone 7 .............................................................................................................................................. 110

Zone 8 .............................................................................................................................................. 116

Page 5: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

4

SOM Checklist ................................................................................................................................ 117

Natural Gas Line Leak ........................................................................................................................ 118

Definition .......................................................................................................................................... 118

First Responder .............................................................................................................................. 118

SOM Checklist ................................................................................................................................ 118

Storm Water/Sewer Line Break (Interior) ......................................................................................... 118

Definition .......................................................................................................................................... 119

First Responder .............................................................................................................................. 119

SOM Checklist ................................................................................................................................ 119

Cold Room Notification Process ........................................................................................................ 120

First Responder .............................................................................................................................. 120

SOM Checklist ................................................................................................................................ 121

Emergency Steam Outage ................................................................................................................. 122

First Responder .............................................................................................................................. 122

-80 C Freezers .................................................................................................................................... 123

Definition .......................................................................................................................................... 123

SOM Checklist ................................................................................................................................ 124

Appendix 1: Continuity of operations (COOP) (Currently undergoing revision) .............................. 126

Appendix 2: Environmental Health and Safety Emergency Procedure/Policy ................................ 126

Appendix 3: Gasoline Spill and SPCC Response Procedure ............................................................... 126

Appendix 4: Zone building emergency manual locations ................................................................ 129

Appendix 5: Move-N-Cooler locations ............................................................................................. 130

Appendix 6: New Employee check-in procedures ........................................................................... 131

Appendix 7: Load Shed Procedures ................................................................................................. 137

Appendix 8: Anschutz Medical Campus Chilled Water Load Shedding: .......................................... 139

Appendix 9: OOM procedures and sign off sheets: (Currently undergoing revision) ................. 141

Appendix 10: Trauma cleanup procedures: (Currently undergoing revision) ............................. 142

Appendix 11: RAVE Communication: ............................................................................................... 143

Appendix 12: Employee phone list: ................................................................................................. 150

Appendix 13: Company Contact numbers: ...................................................................................... 150

Appendix 14: Emergency Contact numbers for Bioscience 2 Building: ........................................... 153

Page 6: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

5

Date Page Change Description Approved

by:

10/19/15 9 - 13 Updated Denver Campus procedures VM & JN

10/19/15 34 – 51 Updated Maximo procedure: work orders and time entry VM

11/18/15 125 Updated Gasoline and SPCC spill response procedures VM

12/10/15 152 Added Emergency contact for BioSience 2 building VM

12/11/15 142 Changed RAVE regisitration procedures VM

3/21/16 1,54,

124

Updated Shift Schedule, Updated Freezer Procedures and added New Fire

Watch Protocols. Added contact info for Servpro

VM

5/2/16 1, 24,

57

Updated Shift Schedule, Expense Process and updated SOM\OOM

Schedule

VM

8/2/16 1 & 57 Updated Shift Schedule and SOM\OOM Schedule VM

Page 7: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

1

Weekly Schedules for Anschutz and Denver Campuses

Normal Week Schedule

AMC Shift

1st

a

b

a

b

DC 1st

2nd

Holiday Week Schedule (Monday Holiday)

AMC Shift

1st

a

b

a

b

DC 1st

2nd

AMC Assignments - Starting on August 14, 2016 AMC OOM Floater Phones DC Assignments

2nd a Anthony Arge-2A1-(720-641-8110)/Brandon Solomon-2A2-(720-355-5025) 720-951-1335 2nd Steven Trujillo

2nd b Paul Patterson-2B1-(303-591-9699)/Glen Troseth-2B2-(303-668-5280) 303-328-5763 2nd Vacant

3rd a Garrett Owens-3A1-(303-668-5269)/Ken Uhrich-3A2-(720-951-6015)

3rd b David Hurtado-3B1-(303-241-7913)/Carlos Jurado-3A2-(303-842-3359)

1400-2200

730-1600

Friday

1400-2200 1400-2200 1400-2200 1400-2200

1400-2400

730-1600

2330-730

730-1600 730-1600 730-1600 730-1600

1400-2200

730-1600 730-1600 730-1600

730-1600

2330-730

0000-1200

Saturday

0000-12002330-9302330-930

730-1600

1400-2200

730-1600

Thursday

1400-2400

1200-2400

730-1600 730-1600

0000-1200

1600-2400 1400-2400 1400-2400

2330-9302330-930

1400-2200

Sunday Monday

1200-2400

0000-1200

1200-2400

1600-2400 1400-2400 1400-2400

1400-2400

Friday

1600-2400

2330-730 2330-9302330-930

Tuesday Wednesday

2330-7302330-930

1400-2200

2330-930

Saturday

730-1600 730-1600 730-1600 730-1600 730-1600

Tuesday Wednesday Thursday

1400-2200

2nd

3rd

2nd

3rd

Sunday Monday

930-1400

1200-2400 1400-2400

Page 8: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

2

CSC Work Order Routing Schedule

AMC: Monday, Tuesday, Thursday, Friday

Normal Service Requests Shift Zone

AMC: Wednesday

DC: Monday

DC: Tuesday, Wednesday, Thursday, Friday

Defenitions: VM = Voice Mail

12a

Shift via VM

7a

CM to Zone &

child to ShiftZone

7:30 3:30

Shift via VM

12a

Shift via VM

Shift via VM

7:30 3:30

CM to Zone &

child to Shift

Shift

CM to Aut Group

(next bus day)

ShiftZone

CM to Aut

Group

7a

Shift via VMCM to Aut

Group

12p5p

Shift via VM

4:00

Shift via VM

CM to Aut Group

(next bus day)

Emergency Service Requests

Autoclave & Glass Washer

Shift via VM

5p

CM to Zone &

child to Shift

CM to Zone &

child to Shift

12p

Shift via VMShift via VM

Shift

ShiftShift via VM

5p 12p7:30

Zone

Zone

Shift via VM

Normal Service Requests

Emergency Service Requests

Autoclave & Glass WasherCM to Aut

Group

CM to Aut

Group

Hold to 4:00

for ShiftShift via VM

12a 7a

Emergency Service Requests Shift via VM Zone Zone

Normal Service Requests Shift via VM Zone Zone

SOM

Shift via VM

12a 7a 7:30 3:30 4p 5p 12p

Shift via VMNormal Service Requests Shift via VM Zone Zone

DC Shift DC Shift

DC Shift DC Shift

3:30 4p

Shift via VMEmergency Service Requests Shift via VM Zone Zone Zone SOM

Page 9: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

3 3/21/2016

Integrating the Maximo Program into CU Denver Processes

Guidelines

1. The desired outcomes of utilizing the Maximo Asset Management System is to accurately

account for all time, record work, and allocate charges to assets.

2. All work is recorded on a work order (WO). Non-work is recorded in Labor Reporting.

3. All expenses are associated with an asset or location.

a. Purchases of services and materials are recorded in Work Order Actuals when

associated with recorded work.

b. Purchases for materials or services recorded on a Maximo Purchase Order (MPO)

must be associated with a work order.

c. Standard Services, services or materials purchased via CU Denver PO or SPO, have a

WO for cost reporting.

4. Zones or Trades own all parent WOs and act as the customer’s point of contact on single-

trade projects. CSC will issue all WO’s on all Multi-trade projects, but will not coordinate the

work.

5. Work orders are made current monthly.

a. WOs are placed in COMP status on completion of labor.

b. WOs are placed in FINCOMP status on completion of financial recording.

6. Work Order Short Description Standard

a. Parent WO: Bldg\Room\Request

b. Child WO: Work Group\Bldg\Room\Request

7. Outages (OUT) are child work orders, to the parent work orders for the project, covering the

isolation and restoration of energy sources.

8. Work orders must stay with the originally assigned group. Support work performed by other

groups must be recorded on subsequent work orders.

a. CSC will transfer originally assigned group only on shift WO’s that have been

requested by shift.

9. Work orders generated as follow-up work must remain the same type, i.e. PM, CM, AAM as

the parent work order.

10. Do not use the browser back arrow or the browser red X. Click Sign Out to exit Maximo.

Page 10: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

4 3/21/2016

Responsibilities

All:

1. Allocate all work and work related expenses on a Work Order (WO).

2. Record time in Maximo application.

3. Record significant events in the Daily Log to inform future shifts.

4. Complete all labor and financial records through the 24th of the month by end of day on the

25th.

Shift:

1. Represent the Zones, Trades and the Customer Service Center during non-business hours.

2. Provide (NIMS) Incident Commander Services for non-business hours incidents.

Zone:

1. Own all parent WOs in area of responsibility and act as the customer’s point of contact.

Trades:

1. Own all parent WOs in area of responsibility and act as the customer’s point of contact.

CSC:

1. Provide communication interface between customers and Facilities Management Staff.

2. Route work requests to the proper work groups.

3. Provide project WO coordination on multi-trade projects.

4. Provide data entry services for Facilities Management.

5. Provide time and expense entries in Maximo for Facilities Management staff.

6. Conduct Quality Assurance (QA) on all expense entries.

7. Ensure all expenditures are on WO’s prior to FINCOMP.

8. Provide feedback to requester on all expense entries.

Leads:

1. Conduct QA checks on work.

2. Serve as SME for area of responsibility.

3. Assign and complete WOs as delegated by the Supervisor.

Supervisors:

1. Approve WOs

2. Approve purchases for their work group.

3. Complete WOs in work groups; COMP on labor, FINCOMP on financial.

4. Reconcile Kronos and Maximo hours.

5. Ensure all expenditures are on WO’s prior to FINCOMP.

Page 11: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

5 3/21/2016

6. Work Group in Labor Reporting: When entering labor for admin time (ex: vacation, sick, holiday etc.) you will be required to enter the work group as well now. This is to help with reporting on admin labor hours.

Supervisor of the Month (SOM):

1. Provides supervisory support to Shift

2. Assigns coverage for Shift absence

3. Provide (NIMS) Incident Commander Services during floods and other emergencies.

4. When the SOM is the Incident Commander they will contact another supervisor to be the

Communication Officer.

Managers:

1. Analyze time and material expenditures for projects and work groups.

2. Confirm reconciliation between Kronos and Maximo.

3. Monitor work orders for compliance with business processes.

Assistant Directors and Directors:

1. Analyze time and material expenditures for projects and work groups.

2. Confirm reconciliation between Kronos and Maximo.

3. Monitor work orders for compliance with business processes.

Page 12: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

6 3/21/2016

Processes

Flow Chart Definitions

Each shape in the flowchart represents a different step in a process.

Terminator This shape indicates the beginning and ending steps of the process.

Process This shape represents a step in the process.

Predefined action This shape for a set of steps that combine to create a sub-process that is defined elsewhere.

Decision This shape indicates a point where the outcome of a decision dictates the next step. There can be

multiple outcomes, but often there are just two — yes and no.

1. Document This shape represents a step that results in a document.

Data This shape indicates that information is coming into the process from outside, or leaving the process. This

shape can also be used to represent materials and is sometimes called an input/output shape.

Page 13: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

7 3/21/2016

Line This shape indicates communication and transfer of responsibility in the direction of the arrow.

Dashed Line This shape indicates informal communication and information transfer.

Dash-Dot Line This shape indicates an alternative option in the flow chart

Page 14: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

8 3/21/2016

Anschutz Medical Campus Emergency Response Process

Anschutz Campus Emergency Management Process 2/2/15

University PoliceBMO Customer

Service CenterShift Staff SOM Comm. Officer EOC

No

Yes

No

No

Yes

No

Yes

Shift

Investigates

and Informs

SOM

Emergency? Create WO

Business

Hours?

Create WO

Escalate

NIMS?

Manage Work

and

Communication

Manage Event

On-site

Incident

Command

Need for BMO

Assistance

Support

Required?

Escalate

NIMS?

Manage Work

and

Communication

Provide

Communication

Officer Services

Page

Emergency

Group

Create WOs

Send DISPO

Page to

Stakeholders.

Create WOs

Send DISPO

Page to

Stakeholders.

No

Yes

Identify

Problem

Can

Resolve?

Yes

No

Page Fac Ops

Stakeholders

Group and

another SOM to

act as

Communication

Officer

Call AVC &

Director

Yes

Shift

Investigates

and Informs

SOM

This line represents a

Rave emergency

notification from

University Police

1. Emergencies occurring during non-business hours are defined as events paged group

notification by the UP.

2. Shift will investigate and immediately inform the Supervisor of the Month (SOM). SOM will call

and inform Director and Associate Vice Chancellor for Facilities. (Director and AVC receive the

emergency group pages from UP and will be expecting a call.)

3. In the case of a flood the SOM is required to report to the campus as Incident Commander.

4. When the SOM is the Incident Commander they will contact another supervisor to be the

Communication Officer.

5. Leaks originating in lab hoods or areas controlled due to contagions require EH&S clearance

prior to clean-up.

Page 15: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

9 3/21/2016

Denver Campus Emergency Response Process

Denver Campus Emergency Response Process 2/2/15

University Police DC Security DC DispatchFire Alarm

ServicesAMC Dispatch AMC Shift

Need for BMO

Assistance

Need for BMO

Assistance

Business

Hours?

Criminal

Offense

Call Auraria Police

or Denver Police

Contact DC

Dispatch or Zone

No

YesYes

Phone or Email

Request

Call Down:

DC OOM Pager

(15 min)

No

Generate WO

and Call Staff

AMC Dispatch

System Alarm

Call AMC Dispatch

Business

Hours?Page Zone

Page DC OOM

Yes

No

Call Down:

DC SOM

These directives are intended to enhance your understanding of the Denver Campus operating norms.

Emergency Contact:

Law enforcement at SC (AB-1), NC or Auraria Campus - 303-556-5000 (Auraria Police)

Law enforcement at LSC, CU, or BUS - 911 (Denver Police emergency), 303-913-2000 (Denver Police non-

emergency)

UCD Security 303-315-6000

UCD Facilities assistance 303-315-7777

Page 16: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

10 3/21/2016

Building Hours:

Lawrence Street Center-1380 Lawrence Street

Building hours: Monday-Friday 6:00 am - 8:00 pm, Saturday 7:30 am - 5:00 pm, closed on Sundays &

holidays (ID access only)

Construction hours: Monday-Friday 7:00 am - 7:00 pm

CU Building- 1250 14th Street

Building hours: Monday-Friday 6:00 am - 8:00 pm, Saturday 7:30 am - 5:00 pm, closed on Sundays &

holidays (ID access only)

Construction hours: Monday-Friday 7:00 am - 7:00 pm

Business School Building- 1475 Lawrence Street

Building hours: Monday-Thursday 7:00 am - 9:30 pm, Friday 7:00 am - 7:00 pm, Saturday 7:30 am - 5:00

pm, Sunday 9:00 am - 5:00 pm, closed on holidays (ID access only)

Construction hours: Monday-Friday 7:00 am - 7:00 pm

Student Commons (AB-1) 1201 Larimer Street

Building hours: Monday - Friday 6:00 am - 8:00 pm, Saturday 7:30 am - 5:00 pm, closed on Sundays &

holidays (ID access only)

Construction hours: Monday-Friday 7:00 am - 7:00 pm

Projects:

Authorizing work: All project access and work must be approved by Facilities Management (FM) and

forwarded from FM to Security. Access requests must be made at least 24 hours in advance. UCD project

managers (PM) and project coordinators (PC) will forward SOW, schedule requests, access requests, hot

work permits, and outage requests to Jim Nelson, Newman Forrester, and Keith Lemieux. Approvals will

be forwarded to security to authorize work.

Work outside of building hours must be approved by Facilities Management (FM) and forwarded from

FM to Security. UCD project managers and project coordinators will forward SOW, schedule requests,

access requests, hot work permits, and outage requests to Jim Nelson, Newman Forrester, and Keith

Lemieux. Approvals will be forwarded from FM to security to authorize work.

Access: Access will be managed by the PM for capital projects or PC for maintenance projects.

PM may designate a General Contractor (GC) staff to provide on-site coordination. Designated GC staff

must be vetted through Projects and badged, with required access programmed and/or keys issued

prior to the work start date. For capital projects building and door access will be provided by PM or GC

staff.

Badging GC staff: PMs must notify DC Facilities Dispatch of GC Staff to be badged and the areas

where access is required and provide the GC staff with an Auraria badge request form. GC must

Page 17: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

11 3/21/2016

purchase a LYNX badge at Auraria Campus ID Office located at the Tivoli Student Union Suite

269, (call 303-556-6346 for hours). GC can then report with their badge to Facilities Dispatch at

LSC Suite 360 to have the badge enabled and pick up needed keys.

For capital and maintenance projects each contractor must have a designated lead sign in with building

security and must record; their cell phone number, work location, company, and number of employees

on site. The contractor lead must remain on-site and will be the primary contact for security and

Facilities.

Permitting:

LSC, CU, and BUS construction permits are requested by the PM, PC, or UCD trades person from the UCD

code official.

SC (AB-1) construction permits are requested by a licensed contractor from the State of Colorado DORA

and by the project coordinator from the UCD Code Official. DC trades staff or zone supervisor will serve

as project coordinator.

To request UCD permits complete the following form G:\Permit Process\FORMS\PERMIT REQUEST -

2015.docm and email it to Chris Jarecki. If the form is not filled out properly or completely, it will be sent

back for follow-up information. Please remember to be as detailed as possible in the “scope” section.

To request UCD inspections use the online website at

https://buildinginspections.ucdenver.edu/UCD/SitePages/Home.aspx . To gain access to the UCD permit

and inspection web site, send an email requesting access to Brett Overby

here: [email protected] . If, for some reason, the website is down or not functioning, you can

request inspections by leaving a voicemail at 303-724-0676. Incomplete messages will not be scheduled,

so please have the permit number and all pertinent information ready when leaving your voicemail.

Dispatch:

Normal hours: M-F 7:30 am – 5:00 pm holidays excluded

The DC Administrative Office is located at LSC 360.

The DC Dispatch phone number is 303-315-7777.

Work order requests can be made on the Maximo start page, or by calling 303-315-7777, or by email to

[email protected].

All requests for assistance or information should be made through the DC Customer Service Center.

Off-normal hours: All work, project support, and service requests are managed by the SOM. All requests

should be via 303-315-7777. The line records off-hours messages to a voice mail box and calls the SOM

and OOM cell phones every 5 minutes until it is answered.

Page 18: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

12 3/21/2016

Keys:

BMO staff who are working on the AMC campus may obtain keys from the key watchers in LSC or

Student Commons (AB-1). Your key watcher account at AMC will work at DC. Please contact Phillip Petty

if key watcher does not allow you to take out keys.

Computing:

We have a landing zone with a Surface Pro 3 docking station and another station for laptops. We also

have five desktop workstations available.

Kronos time clock:

We have Kronos clocks available in LSC and Student Commons.

Deliveries:

All deliveries should be made from the dock and are strictly limited to 20 minutes.

Delivery agents must sign in at the guard desk.

Only personal luggage carts with dimensions not exceeding 12” X 18” may enter through the LSC

Lawrence Street doors.

Parking: (Parking on the docks is not allowed.)

Parking options for construction contractors are:

1. Parking on surface lots in the downtown area 2. Parking at street pay meters 3. Parking in project provided parking areas

Parking options for maintenance contractors are:

1. Parking on the CU Drive. Contractors must be signed in at CU security desk by Facilities staff. ThyssenKrupp, FAS, HSS, and CO HVAC may self-sign.

2. At SC (AB-1) park West of SC on 21st street in the “service vehicle” spot. 3. Parking on the DAP structure (validated by BMO) 4. Parking in local surface lots

Parking options for BMO & FCS vehicles are:

1. Parking on the CU drive. Must sign in with CU Security 2. At SC (AB-1) park West of SC on 21st street in the “service vehicle” spot. 3. Parking in the Performing Arts Center parking structure may be paid with validations from DC

Facilities Dispatch. 4. Parking in the BUS garage. This applies to University business only whether driving their

personal vehicle or a university vehicle.

Prior to parking in the BUS garage:

1. Request an Auraria badge request form from DC Facilities Dispatch [email protected].

2. Call Claudette or Anna to request an available spot prior to driving to the campus.

Page 19: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

13 3/21/2016

3. Clearance at the Business School is 6’2”. BMO vehicles that exceed this height and BMO vendors may park on the CU generator drive. Check in with CU Security is required.

4. Use your badge to enter the BUS parking garage. Parking is available from 7:00 am to 5:00 pm. Monday – Friday.

5. Use of the Business School garage is only allowed while assigned downtown on University business/work purposes.

When arriving: The Business School garage is set up on an anti-pass back system. There must be

one entrance for every one exit on the badge. If you should pull up and the garage door is open,

you will need to wait until the door closes and then scan your card. If you fail to swipe upon

entering, the system will deactivate your card and not allow you to exit.

When leaving: Your badge will be enable you can take the elevators from the 1st floor down to

the parking level. Do not attempt to enter the garage by walking down through the vehicle

entrance.

This parking option will be available as long as there are vacant spaces. Please utilize this option as it

will simplify their trip and reduce the time spent on obtaining parking validations. This will also help to

reduce costs as currently each validation at the Performing Arts Center is costing between $6-$13 per

vehicle depending on their arrival and length of stay. If you have any questions please don’t hesitate to

contact Kerrie Bathje.

Page 20: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

14 3/21/2016

After Hours Anschutz Medical Campus Non-Emergent Assistance Process

After Hours Non Emergent Assistance Process 6/20/12

SMESOMShift

Call SOM SME

Needed?Call Shift?

Advise ShiftTake Action

Log in

Daily Log

Take Action

Log in SOM

Log

Gen WO &

Log in Daily

Log

Yes

No

No

Yes

Send Info to

SOM & Rec

Time on WO

Log in SOM

Log

1. Compensation for SOM time for after-hours assistance is awarded as OT at the end of the

month.

2. Compensation for SME time for after-hours assistance is awarded on the following basis:

a. No pay for simple status confirmation of information passed to SME in initial call.

b. Time spent directing staff is compensated in 15 min increments and recorded on the

WO with “After Hours SOM Assistance” in the comment field.

c. SME Compensation time is flexed if possible.

Page 21: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

15 3/21/2016

Elevator Service Call

Elevator Service Call 2/2/15

CSC CSC Zone Contractor Shift SOM

Problem

Reported

Business

Hours?

Entrapment?

No

Yes

Alert Zone and

Create P1 WO

Yes

Call Contractor for

Emergency

Service & Get ETA

Call UP with

Update

Establish

Communication

with Passenger

and CSC

Create P2 WO for

Zone

Call Contractor for

Normal Service

Repair Elevator &

Report Status to

CSC, Zone or Shift

Establish

Communication

with Passenger

Contact SOM

Call Contractor for

Emergency

Service & Get ETA

Inform Shift and

Sakeholders

Emergency

Service

Required?

Yes

No

Call Contractor for

Normal Service

Next Business Day

No

Update Log

Check Security,

Fire Service and

Doors for Reset

Elevator Reset

Needed?

Tag Elevator

Out of Service

& Update Log

Yes

Entrapment?

Yes

No

Update Log

1. Entrapments: Elevator phones call the UP Dispatch. UP will call Facilities Dispatch when they

receive an entrapment call during business hours and Shift during non-business hours. In either

event the UP starts a 30 minute call-Aurora-Fire timer.

2. Dispatch will send a page to Zone and call ThyssenKrupp for extraction.

3. Shift’s or Zone’s primary responsibility is to establish and maintain communication with the

passengers and UP. This requires going from floor to floor to find the car by yelling through the

door. Once the car is located the responders must calm and assure the passengers. If the

passengers are experiencing a medical emergency ask the UP to call Aurora Fire immediately.

4. During non-business hours Shift is approved to use fire recall to attempt to release the

passengers.

5. Elevator Failures: CSC Dispatch will page the Zone for a confirmation that all doors are checked

for complete closure. Upon receipt of confirmation CSC will call ThyssenKrupp for service.

6. Service is provided by ThyssenKrupp Elevator Co. 303-790-8566.

a. Calls during business hours are answered by the local dispatch.

b. Calls during non-business hours are answered by the regional dispatch in Dallas TX.

c. The dispatchers need address and elevator number to process the call

Page 22: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

16 3/21/2016

Building Addresses with Elevators

Name Address

CU 1250 14th St., Denver, CO 80202

LSC 1380 Lawrence St., Denver, CO 80204

BUS 1475 Lawrence St., Denver, CO 80204

AB1 1201 Larimer Street, Denver, CO 80202

L18.RC1S 12801 E 17th Ave., Aurora, CO 80045

P18.RC1N 12800 E. 19th Ave., Aurora, CO 80045

Q20.500 13001 E. 17th Pl., Aurora, CO 80045

M20. BDC 1775 N. Ursula St., Aurora, CO 80045

M24.NAC 13055 E. 17th Ave., Aurora, CO 80045

S34.CUP 13350 E. 19th Ave., Aurora, CO 80045

L26.SDM 13065 E 17th Ave., Aurora, CO 80045

T36.CSB 1945 N. Wheeling St., Aurora CO 80045

P26.ED1 13070 East 19th Ave., Aurora CO 80045

L15.AO1 12631 E 17th Ave., Aurora, CO 80045

V23.HSL 12950 East Montview Blvd., Aurora, CO 80045

P28.Ed2N 13120 East 19th Ave., Aurora, CO 80045

L28.ED2S 13121 East 17th Ave., Aurora, CO 80045

V17.PSH 12706 East Montview Blvd., Aurora, CO 80045

P15.R2 12700 East 19th Ave., Aurora, CO 80045

V20.PPS 12850 East Montview Blvd., Aurora, CO 80045

V08.HWC 12348 E. Montview Blvd., Aurora, CO 80045

R27.FPEH 13080 East 19th Ave., Aurora, CO 80045

Page 23: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

17 3/21/2016

Shift CM WO Evolution

Shift CM WO Evolution 2/15/15

Shift CSC Zone Trade

Yes

Close CM if

no longer

needed

Initiate CM

Shift transfer

Parent to

CSC

Can Complete?

No

Yes Request

Child WO

from CSC to

Trade Group

Close Parent

Can Complete?

No

Yes

Can Complete?

Close Parent

Close Child

Request

outside

contractor or

projects to

complete WO

CSC create

duplicate WO and

make it the parent.

Send to Zone or

Trade group

No

CSC send

feedback to

Shift that

WO’s have

been

transferred to

appropriate

work groups

1. Shift represents zones and trades during non-business hours.

2. Shift completes CM work orders initiated during non-business hours if possible.

3. Parent Work Orders not completed are transferred to zones or trades by CSC.

4. CSC to send feedback to shift that WO has been transferred.

Page 24: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

18 3/21/2016

Zone CM WO Evolution

Zone CM WO Evolution 2/17/15

Shift Zone Trade FCS or Vendor

Yes

Close Child

Initiate CM

With CSC

Can Complete?

No

Yes

Can Complete?

Transfer

Child WO to

Other

Close Parent

No

Yes

Can Complete?

Close Child

Complete Work

Close Child

Transfer work

to Contractor

Transfer

Child WO to

Other

No

1. Zones own all work orders in their area of responsibility.

2. Zones provide point-of- contact service for customers

a. Exceptions: trade supervisors will provide point-of-contact service for customers on

work not requiring logistics or assistance from the zones.

3. All work orders will be generated by the CSC.

Page 25: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

19 3/21/2016

Trades CM WO Evolution

Trade CM WO Evolution 2/17/15

Shift Zone Trade FCS or Vendor

Yes

Can Complete?

No

Yes

Close Child

Initiate CM

With CSC

Can Complete?

Request

Child WO be

sent to Other

Close Child

No

Yes

Close Parent

Request

Child WO be

sent to Other

Can Complete?

Close Child

Complete Work

Request

Child WO be

sent to Other

No

1. Trades own all Work Orders in their area of responsibility.

2. Trades provide point-of- contact service for customers

3. All work orders will be generated by the CSC.

Page 26: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

20 3/21/2016

CSC Service Request Evolution

CSC Service Request Evolution 9/17/15

CSC CSCCSC

(Full Maximo)

CSC

(Part Maximo)

CSC

(No Maximo)

New Service

Request

FLS, Custodial,

Printing, Postal,

Book Store or

Code?

Maximo

Service

Request,

Phone,

Email or

Daily Log

Facility

Services?

BMO

Maintenance?

AAM <5 Man-

Days + Materials

Facilities

Projects?

Event Setup?

Grounds,

Parking, or Pest

Control?

Billable

Creat WO

and forward

WO # to

Event

Coordinator

Phone or

Email

Information

Phone or

Email

Information

Creat Billable

WO and

notify Trade,

Zone or FCS

Creat billable

WO and

notify FCS

Creat WO

and forward

WO # to

Projects

No

No

No

Create WO

and notify

Zone or

Trade

Yes

Yes

No

Yes

No

Yes

Yes

No

Yes

Yes

1. CSC routes work to the appropriate group

a. Facilities Services; Event Set-Up, Grounds, Parking, Pest Control, Fire Life Safety,

Custodial, Printing, Postal, Book Store, Code Official.

b. BMO Maintenance; Zones, Trades, Facilities Construction Services, Shift, Circuit

Management.

c. Facilities Projects

Page 27: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

21 3/21/2016

Maximo Service Request Evolution

Service Request Evolution 10/19/15

Requestor CSC Supervisor\Lead Staff

Submit Service

Request

Maximo will

automatically

change Service

Request to Work

Order and CSC

will review and

then forward to

Work Group

Complete and

Close WO

Status change

available on

Maximo

Assign WO to

Staff

Materials

required

Order

Materials/

Parts. Send

invoices to

CSC for entry

onto WO

Identify Materials/

Parts needed

Yes

Complete WO and

update comment

area on WO

No

Enter Materials/

Parts onto WO

and then notify

Supervisor\Lead of

entries made.

1. Customers log on to Maximo to make service requests.

2. CSC reviews and changes service request to WO and pages to the work group.

3. WO status is updated in Maximo for customer review.

4. When the Work Order is closed the customer is sent a survey via email.

Page 28: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

22 3/21/2016

Emergency Freezer Service Request Evolution

Emergency Freezer Service Request Evolution 7/27/12

Shift Refrig GroupFreezer TechCSC

Freezer

Support

Request

Business

Hours

Contact Customer

& Provide Access

Yes

Requesting

Spare

Freezer?

No

NO

Yes

No

Requesting

Spare

Freezer?

Yes

Respond to WO

Contact Customer,

Provide Access &

Report Event to

Freezer Tech

Record Emerg

Freezer

Availability

Change

1. A business-hours freezer support request is routed through the freezer tech, for storage space,

and the refrigeration group for repair.

2. Non business-hours freezer support request is handled by shift.

3. Freezer inventory owners are contacted by UP and must move freezer contents to spare units.

4. Spare freezer capacity is updated in the zone operations manual.

Page 29: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

23 3/21/2016

Time Recording

Time Recording 9/15/15

Staff Supervisor Manager Director

Accountable

Time

On-site

Record Time in

Maximo

Record Time in

Kronos and

Maximo

Reconcile Kronos

and Maximo Time

Review

Organization Time

Accounability

Review

Organization Time

Accounability

No

Yes

1. Time is recorded at the end of the business day.

2. Supervisors reconcile Maximo time to Kronos.

3. Managers and directors review time reports.

Page 30: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

24 3/21/2016

Expense Allocation Process

Expense Allocation Process 3/21/16

Purchaser CSC Supervisor\Lead Accountant

New Purchase

When approval to

pay has been

authorized pay

invoice

Allocate to proper GL

Account in Concur

Enter all expenses on

proper WO or WO’s

File purchase in EZA\

SPO books

Work

complete?

All Labor on

WO, change

to COMP

Change WO

to FINCOMP

when all

financials

have been

entered and

Verified

Yes

Marketplace PO forward

invoice to CSC with WO

number and Time Stamp on

Receipt

Storeroom item

forward information to CSC

with WO number and Time

Stamp

PO or SPO forward invoice

to CSC with WO number and

Time Stamp on Receipt, also

forward to accountant with

approval to pay

EZA purchase

forward invoice to CSC with

WO number and Time

Stamp

No

No

No

Send feedback to

purchaser that items

have been entered

and QA’d

Yes

Yes

Yes

Yes

Yes

Yes

1. PO, CU Marketplace, and PROCUREMENT purchases with or without labor are allocated on WO’s

by the CSC.

2. Purchases from storerooms are accounted for on MPO’s by CSC.

3. Labor related PROCUREMENT and PO purchases are allocated on WO actuals. Receipts are

forwarded to CSC for recording.

4. Documenting Transactions please follow the requirements below:

Valid source documentation from the merchant is required for the following transactions:

Every transaction totaling more than $25; and, Every transaction for an official function meal, regardless of dollar amount.

Page 31: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

25 3/21/2016

Source documents must include the following information:

Vendor identification (Merchant Name); Date of purchase; Description and quantity of each item purchased (this information may be handwritten on

the receipt); Cost per item (if available); Total cost of order; Cardholder name and/or card number; and, Explanation of purchase (if this is an unusual purchase for the specific department).

Other applicable required documentation for a transaction may include: Official Function form,

furniture waiver, etc.

Examples of source documents may include any of the following or any combination of the

following:

A receipt and card transaction slip from the merchant; A packing slip showing total cost of order and/or item cost; Order forms for dues, subscriptions, registrations or similar items; Vendor invoice (cannot be issued in the name of an individual, e.g., "University of Colorado,

Jane Doe" is acceptable, but "Jane Doe, University of Colorado" is not acceptable): this does not require that the legal name of the University be used; or,

An email confirmation from the merchant.

Note:

Combinations of documentation are allowed in order to complete the requirements of valid source documentation as discussed in the previous paragraph. Please note that the transaction notification emails generated by the Expense System are not valid source documentation, nor are the popup windows that appear next to some transactions in the Expense System.

Please refer to Procurement web site if you have any questions, use link below:

http://www.cu.edu/psc/procurement-card-handbook/ordering-process

Page 32: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

26 3/21/2016

Work Order Escalation Process

WO Resource Escalation Process 2/17/15

CSC or Maximo

AdministratorStaff Lead Supervisor Trades

Create WO

Schedule

Repairs

Forward Child WO

to Trades

Additional

Resources?

Complete WO

No

Additional

Resources?Yes

Additional

Resources?

Complete WO

Complete WONo

No

Yes

Resources in-

house?

Request child

WO for trades

group

Yes

Create child

WO

Procure

outside

vendor.

No

Complete WOComplete

Parent WO

1. Work Orders are generated in the Maximo system and assigned to work groups.

2. The work group’s goal is to complete the work order with the minimal resource demand.

3. Individual staff may escalate work to the lead (SME) if unable to complete.

4. The lead may escalate the work to other members or the supervisor.

5. The supervisor may escalate the work to trades or a vendor.

Page 33: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

27 3/21/2016

Training and Event Resource Request Process

Training Request Process 10/19/15

Requester AVC Admin Training Manager Safety Trainer CSC

Identified Need

Safety

Training?

Yes

Review

Resource

Reservations

Training Request

Form

Training Request

Form

Technical,

Skills or Policy

No

Forward:

Time

Date

Duration

Attendees

Room

Req’mts

Food

Create PO

Make Travel

Arrang.

Add Event to

Train Cal.

Reserve Rm.

Order Food

Invite non-FM

Forward:

Time

Date

Duration

Attendees

Room

Req’mts

Food

Non-FM

Antendee’s

Make Travel

Arrangements

Forward:

Time

Date

Duration

Attendees

Room

Req’mts

Food

Non-FM

Attendee’s

Create WO’s

Send out FM

Invitations

Schedule

Mod’s

Update

Invites

Creates

roster for

Skilsoft

Yes

Yes

No

No

Yes

Training requests must be submitted on the training request form.

o http://www.ucdenver.edu/about/departments/FacilitiesManagement/Documents/FM_

Forms/FacilitiesManagementTrainingRequestForm.pdf

Training requests must be received no later than 10 working days prior to actual training date.

Travel requests require 4 weeks prior notice.

Safety training is scheduled through safety trainer, all other through training manager.

Once approved the training manager or safety trainer will complete the reverse side of the

training form.

CSC will back-up AVC administrative assistant.

Individual responsibilities:

o Requestor: Send event time, date, duration, attendees, room requirements and food

request to Layna.

o Requestor: Send safety training request to Nancy.

o Requestor: Send tech, skills or policy training request to Scott.

Page 34: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

28 3/21/2016

o Requestor: Review training/event information in training calendar event and notify CSC

of any necessary changes.

o AVC Admin Asst.: Create PO, make travel arrangements, add event to training calendar,

reserve room, order food, invite non-FM attendees, and send info to CSC.

o Training Manager: Process training form forward info to Layna for non-FM employees,

make travel arrangements, and send info to CSC.

o Safety trainer: Process training form forward info to Layna for non-FM employees, make

travel arrangements, and send info to CSC.

o CSC: Creates WO’s, sends invites to FM staff, and creates roster for Skill Soft.

o CSC: Make schedule modifications and update invites as required.

Page 35: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

29 3/21/2016

Work Permit Process

Page 36: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

30 3/21/2016

WO Creation and Work Management Processes

CSC Decision Tree for Tenant Work Requests

Work Type Guidelines

AAM: Add Alter Modify – addition to, altering of or modifications to Facilities Management’s or user-owned assets.

CM: Corrective Maintenance – restoring an asset to like new condition after failure.

/BIL = Billable – work by Auxiliary

/FF = Facilities Funded – work by BMO

Work Group Guidelines (Scope) Coordinator

Single Trade: FCS, BMO Trades (aux) Trade Supervisor

Permit required (limited)

2 persons / 2 days or schedule driven

Architect / engineer not required

Cost opinion

Site visit by trade

Web page price list

Limited material purchases

Specialty vendor services required

Multi Trade Trade or Zone Supervisor

Permit required (limited)

Architect / engineer not required

Cost opinion

Site visit by trade

Web page price list

Limited material purchases

Work request via phone, email or Maximo Link

Create CM/FF

for Zone

Maintenance?

Projects?

Billable? Create CM/BIL

for FCS, Trades

or Zone

Create AAM/BIL

for Facilities

Projects

Estimate?

No

Yes

Web Link or

Create AAM/BIL

for Cost Opinion

Cost Opinion?

Yes

No

Yes

Yes No

No

No Yes

Create AAM/BIL

for FCS

Cost

Page 37: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

31 3/21/2016

Work Group Guidelines (Scope)

Facilities Projects

Permit required

Architect / engineer required

Written cost estimate

State Buildings’ process

Multi-trade work

Contractor required

Includes moving

Coordinator

Project Manager

HVAC work

For any work that is not considered routine maintenance, departments must submit a work request that includes a valid speed type. Billable work performed by

Facilities Management staff is billed on an at-cost basis. Work Requests are prioritized in the order they are received and processed.

Details

1. Cost Opinion vs. Cost Estimate

When a tenant requests a cost estimate the CSC will encourage them to review the Facilities web site stating typical costs. They can calculate an

approximation of the charge from this information. CSC will issue WO’s to trades for cost opinion. A cost opinion is developed by an experienced trade

person who, after surveying the job, offers a best guess of the project cost. If this is unacceptable CSC will forward the WO to Facilities Projects for a cost

estimate.

2. Facilities Projects and FCS may transfer project between the groups based on work load and project scope. Facilities Projects may hire FCS as a

contractor for project work.

Work Coordination

1. Single-trade work – supervisor will coordinate.

2. Multi-trade work – Trade or Zone Supervisor will provide administrative coordination.

3. Projects – project manager will coordinate.

Page 38: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

32 3/21/2016

Definitions

1. Cost Estimate: formal proposal for project charges.

2. Cost Opinion – Non-binding, best-guess cost statement by experienced trade’s person, charged against tenant’s speed type and covers one hour on-site.

3. CSC – Customer Service Center

4. Billable – expenses that are not the responsibility of Facilities Management.

5. Maintenance – efforts to restore assets to like new condition.

6. Coordination – collecting and ensuring proper allocation of expenses for time and materials. Organizing work schedules and space access.

Communicating project status to the customer.

7. FCS – Facilities Construction Services (small projects group)

8. Primary work group – trade group or contractor with responsibility for a major, or initial, part of a project.

9. Secondary work group – trade group or contractor with responsibility for an incremental part of a project and supports the work of a primary work

group.

Page 39: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

33 3/21/2016

Work Coordination Model

Multiple work group WO

Primary Work Group

Work Coordination Model

Multiple work group WO

Primary Work Group

Secondary Work Group

CSC is the work coordinator multi-trade small projects.

Create the project WO structure with the assigned

parent and child WOs

Track work progress and ensure completion

Communicate project status with the customer

Ensure all labor and material costs are allocated

Secondary work group communicates project status to

work coordinator and primary work group.

Parent WO

held by Trade

or Zone

Supervisor

Parent WO

held by CSC

Child WO

Work Group 1

Child WO

Work Group 2

Child WO

Work Group 3

Page 40: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

34 3/21/2016

1.

Click the New Work Order button

In the application toolbar.

2. Enter a description of the work.

Defined Maximo Actions

How to Create Work Orders in Maximo CSC\Shift

2.1. Use the following format: ZONE\BLDG\ROOM\DESCRIPTION or WORK

GROUP\BLDG\ROOM\DESCRIPTION 2.2. Designate if Work Orders are Parent or Child in Description block

2.3. If additional detail is required, click the long description button to open the Long

Description dialog. Click when complete.

(Tip) Entering a specific Location will limit the number of assets in the asset drop down List.

3. Enter/Select an Asset. This should auto-populate the Location and GL Account. 3.1. If no asset is defined, enter/select a Location and enter a 0 (zero) in the asset field. 3.2. Ensure the GL Account is populated and correct.

GL Account/Classification/G.L. Craft Type – Agreement Matrix GL Account WO Class BMO Labor Code AUX Labor Code

BMO… …FF… BMO…

BMO… …BIL… CSA… CSA…

Non-BMO …BIL… CSA… CSA…

Selecting a Billable Classification enables the Billable Flag for that Work Order. Facilities Funded (FF) GL Accounts descriptions always start with BMO.

Page 41: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

35 3/21/2016

The Work Order block on Maximo Time entry will turn red to indicate a billable Work Order.

3.3. Enter/Select the Work Type.

(Tip) Work Type Meanings

AAM: Add Alter Modify – addition to, altering of or modifications to Facilities Management’s or user-owned assets. CM: Corrective Maintenance – restoring an asset to like new condition after failure. PM: Preventive Maintenance – planned and scheduled work to prevent asset failure. Must have a job plan and be scheduled for recurring events. OUT: Outage – isolation of energy sources to safely secure assets for work. ADM: Administrative – training, meetings and all work not directly improving an asset or location. EV: Event – one-time occasion requiring labor or expense and not directly improving an asset or location.

3.4. Click the Detail Menu button to the right of the Classification field and click Classify.

3.4.1. The Classify drill-down tree will open: 3.4.1.1. Navigate to and select the appropriate work classification.

(Tip) Find the Work Type in the first level of the classification drop-down and navigate to level that describes the work. (See “How to Classify Work Orders in Maximo”.)

3.5. Enter/Select the appropriate Work Group 3.5.1. The Lead field will be auto-filled – adjust as necessary. 3.5.2. If a Supervisor is defined for the work group, this field will also be auto-filled – adjust as necessary. 3.6. Check the Filter on Lead only? Box if this work order should only show in the Lead’s time entry work order list. When left unchecked (the default), the work order will appear in the time entry work order list of each person in the work group. 3.7. If the work order was called in, enter the requestor’s name in the Requestor field. 3.7.1. Enter the Requestor’s Phone number and Email address. 3.8. Populate remaining fields as needed. Note: If a Job Plan is designated, the work plan will be copied to the Plans tab as soon as the job plan is entered.

4. Click Save Work Oder In the application toolbar.

4.1. To Initiate (INPRG), click the Initiate Work Order button in the application toolbar and click (Tip) All Works Orders are created INPRG

Page 42: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

36 3/21/2016

Other Status Options: WAPPR – Waiting on Approval ESTIMATE – Being Estimated (WAPPR) ONHOLD – ON Hold (WAPPR) WSCH – Waiting to be scheduled (WAPPR) WMATL – Waiting on Material (WAPPR) TRAN – Transfer to Trade (WAPPR) APPR – Approved INPRG – In Progress CAN – Canceled PM-CNCL – PM Canceled FINCOMP – Financials Complete COMP – Labor Complete

Maximo Work Order Status Attribute Matrix

Pseudonym Available

to Users

Can

Change

Status

Add

Labor

Add

Costs

Can

Change

Status

View in

Maximo

Link

Auto

Close

After

X

Days

Rec.

WO

Actual

Start

WAPPR Yes Yes Yes Yes Yes No No No

ESTIMATE WAPPR Yes Yes Yes Yes Yes No No No

ONHOLD WAPPR Yes Yes Yes Yes Yes No No No

PRCSD WAPPR Yes Yes Yes Yes Yes No No No

TRAN WAPPR Yes Yes Yes Yes Yes No No No

WSCH WAPPR No No No No No No No No

WMATL WAPPR Yes Yes Yes Yes Yes No No No

WPCOND WAPPR Yes Yes Yes Yes Yes No No No

INPRG Yes Yes Yes Yes Yes Yes No Yes

APPR Yes Yes Yes Yes Yes Yes No No

CAN CLOSE Yes No No No No No 0 No

DUP CAN Yes No No No No No 0 No

CLOSE No No No No No No No No

PM-CNCL CLOSE Yes No Yes Yes Yes No 1 No

FINCOMP Yes No Yes Yes No No 0 No

COMP Yes Yes Yes Yes Yes No No No

Maximo WO Status Application

Approved Use

WAPPR Status used on preventive maintenance work orders as initial generation status

ESTIMATE Status used when staff is providing estimation on cost (labor hours and materials)

These statuses place the Work Order on-hold.

These statuses enable recording time and material

expenses associated with the work order.

These statuses are for recording work order

completion.

Page 43: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

37 3/21/2016

ONHOLD Used for WOs delayed by non-departmental influences

TRAN Used on parent WO when a child WO is transferred to another work group

WMATL Status used when waiting on material orders, delivery, or data entry

INPRG Status used as initial status on all non-preventive work orders

APPR Used on PM WOs for initiation of assigned work

CAN Status used on preventive maintenance work orders when work is ready to begin

CLOSE Status used by Maximo for all work orders in FINCOMP (status change nightly)

PM-CNCL Status used on work orders when labor or others hinder work from being performed /

PM will generate again using the PM's scheduled frequency FINCOMP Status used by supervisor when all financials are complete for the work order

COMP Status used by supervisor when all labor is complete

Page 44: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

38 3/21/2016

How to Classify Work Orders In Maximo

WO Classification Tree

AAM: Add Alter Modify CM: Corrective Maintenance PM: Preventive Maintenance OUT: Outage ADM: Administrative EV: Event

(Tip) Classifying AAM, CM, PM, OUT, and EV requires navigating to at least the second level of the classification tree. Level 1 = Work Type. Level 2 = Craft Type - Determines the Craft selection in Maximo. Level 3 = Compliance Level 4 =Follow-up

(Tip) Classifying ADM requires navigating to at least the third level of the classification tree for OH and PS. Classifying TRN requires navigating to the 5th level. Level 1 = Work Type. Level 2 = Craft Type - Determines the Craft selection in Maximo. Level 3 = Work Sub-Type Level 4 = Training Type Level 5 = Training Sub-Type AAM Drop-Down List Work Type\Craft Type\Compliance

AAM: Add Alter Modify FF: Facilities Funded AAM \FF CMP: Compliance AAM \FF\CMP BIL: Billable AAM \BIL CMP: Compliance AAM \BIL\CMP CM: Corrective Maintenance PM: Preventive Maintenance OUT: Outage ADM: Administrative EV: Event

Page 45: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

39 3/21/2016

CM Drop-Down List Work Type\Craft Type\Compliance

AAM: Add Alter Modify CM: Corrective Maintenance FF: Facilities Funded CM\FF CMP: Compliance CM\FF\CMP BIL: Billable CM\BIL CMP: Compliance CM\BIL\CMP PM: Preventive Maintenance OUT: Outage

ADM: Administrative

EV: Event

PM Drop-Down List Work Type\Craft Type\Follow-up or Compliance

AAM: Add Alter Modify CM: Corrective Maintenance PM: Preventive Maintenance FF: Facilities Funded FU: Follow Up PM\FF\FU CMP: Compliance PM\FF\CMP FU: Follow Up PM\FF\CMP\FU BIL: Billable FU: Follow Up PM\BIL\FU CMP: Compliance PM\BIL\CMP FU: Follow Up PM\BIL\CMP\FU OUT: Outage

ADM: Administrative

EV: Event

OUT Drop-Down List Work Type\Craft Type

AAM: Add Alter Modify CM: Corrective Maintenance PM: Preventive Maintenance OUT: Outage

FF: Facilities Funded OUT\ FF

BIL: Billable OUT\BIL

ADM: Administrative

EV: Event

Page 46: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

40 3/21/2016

ADM Drop-Down List Work Type\Craft Type\Work Sub-Type\Training Type\Training Sub-Type

AAM: Add Alter Modify CM: Corrective Maintenance PM: Preventive Maintenance OUT: Outage

ADM: Administrative

FF: Facilities Funded

OH: Overhead ADM\FF\OH

PS: Project Support ADM\FF\PS

TRN: Training

EXT: External

CMP: Compliance ADM\FF\TRN\EXT\CMP

ELE: Elective ADM\FF\TRN\EXT\ELE

EH&S: Env. Health & Safety ADM\ ADM\FF\TRN\EXT\EH&S

P&P: Pol & Proc ADM\FF\TRN\EXT\P&P

TCH: Technical ADM\FF\TRN\EXT\TCH

PD: Prof. Development ADM\FF\TRN\EXT\PD

BUS: Business ADM\FF\TRN\EXT\BUS

INT: Internship ADM\FF\TRN\EXT\INT

TSP: Train Sponsored Event ADM\FF\TRN\EXT\TSP

INT: Internal

CMP: Compliance ADM\FF\TRN\INT\CMP

ELE: Elective ADM\FF\TRN\INT\ELE

EH&S: Env. Health & Safety ADM\FF\TRN\INT\EH&S

P&P: Pol & Proc ADM\FF\TRN\INT\P&P

TCH: Technical ADM\FF \TRN\INT\TCH

PD: Prof. Development ADM\FF\TRN\INT\PD

BUS: Business ADM\FF \TRN\INT\BUS

INT: Internship ADM\FF\TRN\INT\INT

TSP: Train Sponsored Event ADM\FF\TRN\INT\TSP

BIL: Billable OH: Overhead ADM\BIL\OH PS: Project Support ADM\BIL\PS TRN: Training EXT: External CMP: Compliance ADM\BIL\TRN\EXT\CMP

ELE: Elective ADM\BIL\TRN\EXT\ELE

EH&S: Env. Health & Safety ADM\BIL\TRN\EXT\EH&S

P&P: Pol & Proc ADM\BIL\TRN\EXT\P&P

TCH: Technical ADM\BIL\TRN\EXT\TCH

PD: Prof. Development ADM\BIL\TRN\EXT\PD

BUS: Business ADM\BIL\TRN\EXT\BUS

Page 47: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

41 3/21/2016

INT: Internship ADM\BIL\TRN\EXT\INT

TSP: Train Sponsored Event ADM\FF\TRN\EXT\TSP

INT: Internal CMP: Compliance ADM\BIL\TRN\INT\CMP

ELE: Elective ADM\BIL\TRN\INT\ELE

EH&S: Env. Health & Safety ADM\BIL\TRN\INT\EH&S

P&P: Pol & Proc ADM\BIL\TRN\INT\P&P

TCH: Technical ADM\BIL\TRN\INT\TCH

PD: Prof. Development ADM\BIL\TRN\INT\PD

BUS: Business ADM\BIL\TRN\INT\BUS

INT: Internship ADM\BIL\TRN\INT\INT

TSP: Train Sponsored Event ADM\BIL\TRN\INT\TSP

EV: Event

Training 4th Level Training Type Definitions

INT: Internal – training provided and delivered by Facilities Management. EXT: External – training provided by a third party, includes other departments (on-sight or off).

Training 5th Level Training Sub-Type Definitions

CMP – regulatory compliance training related to environment, safety or public interaction.

ELE – elective training not required for a position or a task (non-directed).

EH&S – training presented by EH&S.

P&P – training on University or departmental policies and procedures.

TCH – technical training for skills development or operational instruction.

PD – professional development training for soft skills, credentialing and personal development.

BUS – training on business process like Maximo, Kronos, Concur or CU Marketplace.

INT – training for interns, also applies to mentors and supervisors involved in the program.

TSP – training sponsored events like trade shows, lunch-and-learn sessions, and recognition trips.

EV Drop-Down List Work Type\Craft Type

ADM: Administrative

CM: Corrective Maintenance PM: Preventive Maintenance AAM: Add Alter Modify OUT: Outage

EV: Event FF: Facilities Funded EV\FF

BIL: Billable EV\BIL

Page 48: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

42 3/21/2016

CSC Will Record Items, Materials and Services Transactions on Work Order’s

Material and service usage can be recorded on any work order that is Approved, In Progress or Complete.

1. Find and select the work order on which you want to record material or service usage. 2. Click the Actuals tab. 3. Click the Materials sub tab. 4. To record an outside Material or Service purchase:

4.1. Click the button. 4.2. Set the Line Type appropriately. The default is Material, if recording a service, change it to Service. 4.3. Enter: Name (purchaser)\Company\Order or Invoice number\SPO or PO number if applicable\Description of what was purchased. 4.4. Enter the Quantity. 4.5. Enter the Unit Cost 4.6. Enter/Select the Vendor.

(Tip) It is necessary to search the vendor list so you don’t make a second entry for the same vendor.

Select the search icon beside the Vendor field.

Then query the list by entering parts of the vendor name in the Description field of the Select Value box and hit enter.

4.6.1. If the vendor is not in the value list:

Select on the Select Value box. 4.6.1.1. Check the Other? Box. 4.6.1.2. Enter the Vendor Name

4.6.1.3. If known, enter the vendor’s Address, Phone, a Contact name, Number and E-mail address.

4.7. Click Save Work Order in the application toolbar. 5. To record an Item or Standard Service used from inventory:

5.1. Click the button. 5.2. Change the Line Type to Item or Standard Service respectively. 5.3. Enter/Select the appropriate Storeroom. For standard services, always specify the SERVICES Storeroom.

Page 49: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

43 3/21/2016

5.4. Enter/Select the appropriate Item / Standard Service. Note: When a Standard Service is entered, the Line Type will change to Item. This is normal behavior. 5.5. Adjust the Quantity as needed.

(Tip) Enter GL Credit Account according to the Matrix provided by Finance.

(Tip) All Billable Work Orders invoices must be entered line by line.

5.7. Click Save Work Order in the application toolbar.

Note: Once the work order is saved, material transactions cannot be modified or deleted.

Page 50: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

44 3/21/2016

How to Complete a Work Order

When the work has been completed the work order status will be set to COMP (Work Complete). Once all the costs have been recorded on the work order its status will be set to FINCOMP (Financials Complete). Work order status will be changed to CLOSE my Maximo when the status is changed to FINCOMP. Work orders CLOSED cannot be viewed in Maximo time entry.

How to Make Work Order GL Account, Classification, and Time Entry Corrections

Work orders contradicting the GL Account/Classification/G.L. Craft Type – Agreement Matrix must be corrected prior to the month-end charges upload.

GL Account WO Classification BMO Labor Code AUX Labor Code

BMO… …FF… BMO…

BMO… …BIL… CSA… CSA…

Non-BMO …BIL… CSA… CSA…

Incorrect GL Account can be changed on open WOs. For Closed WOs the entire WO, including time

entries, must be reversed and recreated in new WOs. (see Closed WOs below)

Incorrect WO Classification can be changed on open WOs. For Closed WOs the entire WO, including

time entries, must be reversed and recreated in a new WO. (see Closed WOs below)

Incorrect Labor Code must always be reversed and re-entered correctly. The process varies

depending on the WO status, open vs. CLOSE.

Open WOs:

1. Reverse time entries by creating a duplicate line entry with the same Start Date and Labor Code

and apply the opposite sign to the hours (1.5 vs. -1.5) in the open WO.

2. Create another duplicate of the original time entry with the same Start Date and correct Labor

Code.

CLOSED WOs:

Adding charges to a closed work order

1. CSC will notify the work group supervisor when invoices or labor are submitted to CSC

for expensing on a closed WO.

a. If the GL Account is correct CSC can make a WO history revision

b. IF the GL Account is incorrect a new WO must be generated

2. The work group supervisor will notify the work group manager to request a history

revision or generation of a new WO for recording additional labor, material, or service

expenses.

Page 51: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

45 3/21/2016

3. The manager will contact the CSC to authorize the action and get the following

information:

a. Closed WO number

b. Current expenses recorded

c. New WO number

d. New expense to be recorded

e. Name and contact information of the financial administrator for the speed type

4. The manager will forward the information to the supervisor, who will contact the speed

type administrator to explain the additional expense. Work orders with material or

service charges associated should be forwarded to Customer Service Center to correct.

Time labor entries will be corrected by the Supervisor.

Using Non-Building Speed Types on Work Orders

61077896 AMC/DC BMO Clearing – is used to credit all non-auxiliary expenses and to debit labor,

material, and service expenses not assignable to a building. Use as AMC BMO Operating

There can be NO labor on clearing account work orders

61077891 Administrative – is used to debit all administrative overhead expenses, such as IT equipment

and office supplies.

61077890 AMC BMO Campus Wide – is used to credit an expense for materials purchased for and

distributed to all buildings. Due to its impact on ICR calculation caution is required.

Materials must be equally apportioned to all buildings.

Not suitable for labor charges or service charges.

61077897 DC BMO Operating – is used to credit all non-auxiliary expenses and to debit labor, material,

and service expenses not assignable to a specific building.

61077892 Training – is used for all training.

Page 52: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

46 3/21/2016

How to Create a New Maximo Purchase Order

Go To > Purchasing > Purchase Orders

1. Click the New Purchase Order button in the application toolbar. 2. On the PO tab: 2.1. Press the Tab key to move to the Description field. 2.2. Enter a description for the PO. 2.3. Find the Company field and enter/select the appropriate vendor. 3. Click on the PO Lines tab: 3.1. In the Default Table Data section: 3.1.1. If every item on the PO should be charged to a specific Work Order, Location, Asset, GL Debit Account and/or GL Credit Account – enter or select those values now. 3.2. In the PO Lines section:

3.2.1. Click the button. 3.2.2. Enter/Select an item. 3.2.3. Set the Quantity to the desired amount. 3.2.4. Ensure Conversion Factor is populated appropriately. Value must be greater than zero. 3.2.5. Adjust the Unit Cost as needed. 3.2.6. Select the Storeroom into which the item is to be received. 3.2.7. Fill in Debit and Credit account speed types. 3.2.8. Repeat to add additional items.

4. Click the Save Purchase Order button in the application toolbar.

5. Approve the PO only if all shipping charges have been added and then by clicking the Approve

Purchase Order button in the application toolbar.

5.1. In the Change Status dialog box, click

Page 53: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

47 3/21/2016

How to Change a Maximo Purchase Order after Approval

Once a Purchase Order is approved it becomes read only and cannot be modified. In Maximo, purchase order records are revision controlled; meaning that in order to make changes to an approved PO it must be “revised”.

1. Find and select the purchase order to be revised. 2. From the Select Action menu in the application toolbar, select Revise PO 3. In the Revise PO dialog box: 3.1. Enter the reason for the revision.

3.2. Click 4. The Revision number increments, the Status is set to Pending Revision (PNDREV) and the record becomes editable. The previous revision remains in an approved state.

5. After making the necessary changes, change the PO’s status to Approved. The PO’s previous

revision’s status will be set to Revised (REVISD) and no further action can be performed on it.

Page 54: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

48 3/21/2016

Matching Kronos Pay Codes with Maximo Labor Work Types

Hours sign in Maximo must match the hours sign in Kronos

Kronos Maximo

ADM Administrative Leave (For Training; use RGS or REG)…………………………………………. WORK ATS Additional Time at Straight Pay…………………………………………………………………………..WORK CBS Call Back @Straight WORK CBT Call Back @Overtime…………………………………………………………………………………………. WORK DK2 Unpaid Time (Enter Negative Numbers) NON-WORK (Pos #s) DK3 Furlough Time (Enter Negative Numbers)………………………………………………………….. NON-WORK (Pos #s) FLH Floating Holiday HOL FNL Funeral Leave……………………………………………………………………………………………………. ADMIN FSK Family Sick SICK HOL Holiday………………………………………………………………………………………………………………..HOL JRY Jury Leave………………………………………………………………………………………………………….. ADMIN MLP Paid Military Leave ADMIN OJI On-the-Job Injury…………………………………………………………………………………………….….ADMIN OTM Overtime WORK RGS Regular pay, salaried…………………………………………………………………………………………. ADMIN REG Regular pay, hourly (temp and part time) WORK SCK Sick Leave Taken………………………………………………………………………………………………… SICK STH Student Hourly WORK SOT Student Overtime………………………………………………………………………………………………. WORK VAC Vacation Leave Taken VAC VOL Volunteer Leave……………………………………………………………………………………………….…ADMIN XRG Additional Hours for non-FTE (Need FM HR approval) WORK

Page 55: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

49 3/21/2016

Modifying Maximo Person Groups by CSC

Adding Employees to Person Groups

A person can belong to one or more person groups.

The Person Groups screen is found in the Resources module of the Go To / Administration menu.

1. Go To > Administration > Resources > Person Groups.

2. From the List tab hit enter to show all person groups.

3. At the bottom of the list check Select Records to show the full list of person

groups.

4. Select the person group to which you need to add a member.

5. Click on the Person Group tab to display the group members.

6. Click on New Row to open the New Row Details screen.

7. Select the double chevron beside the Person field box.

8. Click on Select Value.

9. Enter the last name of the person you are adding to the Name field

and hit enter.

10. Select on the Person field to automatically add the person to the

selected work group.

11. Input a number in the sequence field box. This number should be greater

than the numbers of the other members.

Signing out or switching to other Maximo applications will generate the save changes message.

. Click yes to save your work.

Page 56: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

50 3/21/2016

Removing Employees from Person Groups

Go To > Administration > Resources > Person Groups.

From the List tab hit enter to show all person groups.

At the bottom of the list check Select Records to show the full list of person

groups.

Select the person group to which you need to remove a member.

Click on the Person Group tab to display the group members.

Select the Trash Can at the end of the row for the person you want to remove.

Signing out or switching to other Maximo applications will generate the save changes

message. . Click yes to save your work.

Page 57: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

51 3/21/2016

Recording Time in Maximo

Maximo Time Entry

4 6

3 5

8 1 7

2

9

10

1. To locate WO for time entry click on search glass and select WO from drop down

2. Verify status of WO – Time can only be added to OPEN WO’s such as INPRG or APPR, if WO is in

another status please contact your supervisor.

3. Ensure Date is correct time entry (Defaults to current date)

4. Fill in regular hours

5. Ensure craft is correct before final submission

6. Fill out remarks section – All entries should at a minimum begin with either Open or Complete to

signify WO status

7. To email yours remarks to your supervisor check box

8. To add over time to WO click on “Add OT” button

A. Verify OT multiples units is correct, not sure ask your supervisor

9. To add time to another WO click “Add new time entry” button

10. When complete with time entry click “Submit” button

Page 58: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

52 3/21/2016

CU Denver Policies and Procedures

Policy Links CU Denver Facilities Management Policies are located at:

http://www.ucdenver.edu/about/departments/FacilitiesManagement/PoliciesGuidelines/StaffPoliciesG

uidelines/Pages/StaffPoliciesGuidelines.aspx

Administrative Policies

Family Medical Leave

Workers Compensation

Procedure for Reporting and Processing Allegations of Sexual Harassment

Procedures for Assessing the Use of Sick Leave

Leave Request Policy and Procedure

Bereavement Leave Policies and Procedures

Temporary Modified Duty

Job Description (PDQ) and Physical Requirements Checklist Procedure

Essential Personnel

Kronos Time System Policy and Procedures

Fiscal Policies

Computing Resources Procedures

Use of Electronic Mail

Critical Skills Differential Temporary Pay

Referral Award and Signing Bonus

Cellular Phone Policies and Procedures

Scrap Identification and Disposal

Health and Safety Policies

Authority Having Jurisdiction for Fire Prevention and Life Safety

Personal Protective Equipment (PPE)

Department Issued Uniforms and/or Apparel and Safety and Appearance Expectations

Substance Abuse Policy and Procedures

Construction and Modification Code Compliance

Fire Code Policy and Procedures

Campus Construction Fire Safety Policy and Procedures

Tent-Type Structures and Permits Policy and Procedures

Fire Doors Policy

Employee Safety - Fall Protection Procedures

Elevator Emergency Procedures

Fire Systems Testing

Fire Alarm Response Policy and Procedures

Fire Alarm Delayed Evacuation Policy and Procedures

Controlled Energy (Lock Out / Tag Out)

Flammable / Combustible Liquids Policy and Procedures

Flammable Gases Policy and Procedures

Flammable Liquids Cabinets Policy and Procedures

Electrical Safety Policy and Procedures

Attended Heating Policy and Procedures

Page 59: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

53 3/21/2016

Space Heaters Policy and Procedures

Holiday Decorations Policy and Procedures

Candles Policy and Procedures

Gas Cylinder Safeguards Policy and Procedures

Confined Space Entry Policy and Procedures

Hot Work Policy and Procedures

Fire System Outages

Parking Policies

Citation Writing and Processing Policies and Procedures

Electric and Fuel Powered Cart Policy and Procedure

Guidelines

Progressive Discipline Procedure Guidelines

Creating a Positive Work Environment Delegating Appointing Authority

Page 60: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

54 3/21/2016

Fire Watch Protocols

Fire Protection System Impairments

Hot Work

The need for initiating fire watch duties relating to fire protection system impairments in particular, are often times determined on a case-by-case basis (with some exceptions), and will typically include either pre-planned or emergency conditions. Each will consider the building, occupancy type, nature and duration of impairment, building occupancy level during impairment period, active work being conducted on the system during the impairment, condition of other fire protection systems and features, building and system compartmentation, and hazards/assets for areas at risk. In all cases the required impairment (outage) request shall be submitted and the need for fire watch reviewed accordingly. Fire watch duties are also performed in conjunction with hot work activities. University Police will typically provide personnel to perform fire watches in the affected areas which may consist of either certified officers or uniformed security personnel. However, other personnel may act in the same capacity, as long as all criteria for assigned duties can be demonstrated in advance. Appropriate mitigating measures for fire protection system impairments range from simple occupant notification to full-time fire watch duties. Determining factors vary from test-related impairments and maintenance activities during normal business through extensive impairments to high-value, high hazardous or construction-related activities. The following information provides guidance and direction for some of the more common impairments requiring fire watch personnel.

FIRE WATCH. A temporary measure intended to ensure continuous and systematic surveillance of a building or portion thereof by one or more qualified individuals for the purposes of identifying and controlling fire hazards, detecting early signs of unwanted fire, raising an alarm of fire and notifying the fire department (Ref: International Fire Code)

Construction (pre-planned wet-based fire protection systems)

When required by the fire code official for building demolition, or building construction during or after working hours that is hazardous in nature, qualified personnel shall be provided to serve as an on-site fire watch. Fire watch personnel shall be provided with at least one approved means for notification to the fire department and their sole duty shall be to perform constant patrols and watch for the occurrence of fire.

Temporary fire protection is to be provided by installing not less than 4A60:BC fire extinguishers in strategic locations spaced at 50’-75’ intervals-subject to change as construction changes.

The areas involved have been inspected and the increased risks determined (contractor, fire watch personnel, and BMO staff).

The supervisors in the areas to be affected have been notified (by contractor, BMO group).

The fire department has been notified of days, times, areas, and duration of impairment(s) (sprinkler system over 10 hours in a 24 hr. period).

The insurance carrier has been notified of partial or complete system impairment, and FM Global red tag system employed (sprinkler system over 10 hours in a 24-hr. period).

A fire watch as described shall be initiated during all times of fire protection system impairment in the affected areas only-all other fire protection system functions shall remain operational.

Water-flow alarms in areas unaffected by construction shall remain functional at all times.

Page 61: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

55 3/21/2016

Hot work will only be allowed when all combustible materials have been removed from areas under construction. However, if any hot work is essential to complete the work before combustible materials have been removed, please discuss with FLSO well in advance.

Trash and excessive debris (combustible) shall be removed from the premises at the end of each work day; non-combustible material shall be kept neat and orderly as construction activities allow, ensuring egress and ingress have not been obstructed.

Ensure other sprinkler control valves on the affected floor remain open-especially where none are labeled or identified at the ceiling level in any manner, and their location and positional status requires confirmation.

Isolation of affected area for future anticipated sprinkler system alterations shall be pre-determined, confirmed, and approved by the FLSO and/or Building Official; subject to change based on future design considerations (as applicable to the sprinkler system impairment).

All personnel conducting fire watch duties shall read, understand, and commit to these requirements.

Written documentation of systematic surveillance conducted by all fire watch personnel is strongly encouraged (dates, times, responsible party, conditions observed, and so on).

Phones or other approved means of communicating emergencies to UCD dispatch and AFD shall be provided by all fire watch personnel.

Number of fire watch personnel-based on square footage, involved area(s), individual circumstances.

Periodic, unscheduled inspections may be conducted by the FLSO at his/her discretion.

Emergency conditions (warranting fire watch)

Emergency impairments shall include, but are not limited to, interruption of water supply, frozen or ruptured piping, and equipment failure, and includes impairments found during testing, inspections, and maintenance (for example: obstructions in sprinkler piping).

Temporary fire protection is to be provided by installing not less than 4A60:BC fire extinguishers in strategic locations spaced at 50-75” intervals.

The areas involved have been inspected and the increased risks determined.

The supervisors in the areas to be affected have been notified.

Recommendations to mitigate any increased risks have been submitted to management, along with corrective action and execution of fire watch.

Establish and implement a program to eliminate potential ignition sources (such as in the lab areas).

Hot Work

When required: A fire watch shall be provided during hot work activities and shall continue for a minimum of 30 minutes after the conclusion of the work. The fire code official, or the responsible manager under a hot work program, is authorized to extend the fire watch based on the hazards or work being performed. Exception: Where the hot work area has no fire hazards or combustible exposures.

Location: The fire watch shall include the entire hot work area. Hot work conducted in areas with vertical or horizontal fire exposures that are not observable by a single individual shall have additional personnel assigned to fire watches to ensure that exposed areas are monitored.

Page 62: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

56 3/21/2016

Duties: Individuals designated to fire watch duty shall have fire-extinguishing equipment readily available and shall be trained in the use of such equipment. Individuals assigned to fire watch duty shall be responsible for extinguishing spot fires and communicating an alarm.

Fire training: The individuals responsible for performing the hot work and individuals responsible for providing the fire watch shall be trained in the use of portable fire extinguishers.

Fire extinguisher: A minimum of one portable fire extinguisher with a minimum 2-A:20-B:C rating shall be readily accessible within 30 feet (9144 mm) of the location where hot work is performed.

Page 63: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

57 3/21/2016

OOM and SOM Assignments

Month SOM OOM 1 OOM 2 OOM 3 OOM 4 OOM 1 OOM 2 OOM 3 SOM

Aug-16 T. Norrison S. Avila R. Decess T. Chapin I. Rodriguez S. Trujillo G. Vergara M. Fernandez K. Lemieux

Sep-16 G.Woods A. Eyre PMT-1 D.Winfrey C. Sanchez G. Vergara M. Fernandez S. Trujillo P. Petty

Oct-16 R. Turner PMT-1 C. Gallegos G. Barrow s J. Allen M. Fernandez S. Trujillo G. Vergara K. Lemieux

Nov-16 D.Tilton B. Waldmann J. Neeper PMT-1 S. Becker S. Trujillo G. Vergara M. Fernandez P. Petty

Dec-16 T. Berry J. Law ton G. Lee J. Radaelli PMT-1 G. Vergara M. Fernandez S. Trujillo K. Lemieux

Jan-17 M. Arge R. Decess T. Chapin I. Rodriguez S. Avila M. Fernandez S. Trujillo G. Vergara P. Petty

Feb-17 N. Sullivan PMT-1 D.Winfrey C. Sanchez A. Eyre S. Trujillo G. Vergara M. Fernandez TBD

Mar-17 S. Roen C. Gallegos G. Barrow s J. Allen PMT-1 G. Vergara M. Fernandez S. Trujillo TBD

Apr-17 J. Walklett J. Neeper PMT-1 S. Becker B. Waldmann M. Fernandez S. Trujillo G. Vergara TBD

May-17 V. Mitchell G. Lee J. Radaelli PMT-1 J. Law ton S. Trujillo G. Vergara M. Fernandez TBD

Jun-17 D. Thorson T. Chapin I. Rodriguez S. Avila R. Decess G. Vergara M. Fernandez S. Trujillo TBD

Jul-17 E. SchroederD.Winfrey C. Sanchez A. Eyre PMT-1 M. Fernandez S. Trujillo G. Vergara TBD

Aug-17 M. Sherman G. Barrow s J. Allen PMT-1 C. Gallegos S. Trujillo G. Vergara M. Fernandez TBD

1. To contact shift please leave a voice mail - AMC shift 303-724-1777 or DDC shift 303-315-7777

2. All staff are required to maintain 24 X 7 phone availability. (FMP: 102-050)

3. OOM responds to emergencies and provides relief on assigned campuses. Additional staff will be called-in as

needed.

4. OOM is required to designate replacement if unavailable.

5. OOM's scheduled training takes priority over shift coverage

6. SOM will rotate calls equitably between the OOMs

7. When forecasted temp is above 32o "lone shift worker" rules may be utilized. LSW requirements:

a. Weather forecast must be above 32o

b. Shift must make contact with CUP operators at the start of the shift and hourly at the top of the hour.

c. SOM must be ready to respond if assistance is required.

8. OOMs are paid overtime for emergency call-ins. Scheduled coverage will be flexed-off.

9. Coverage for non-scheduled times or extenuating circumstances, such as daytime hours on holidays, may be

posted for volunteers.

1) Emergency communication will follow the NIMS model.

2) Shift supervisor, shift lead technician, or SOM, when on site, will serve as Incident Commander.

3) When the SOM is the Incident Commander they will contact another supervisor to be the Communication

Officer.

4) SOM will serve as Communication Officer utilizing the RAVE system to call in staff and disseminate

information to the appropriate entities when there is a shift supervisor or shift lead technician on site.

5) SOM needing coverage will find replacement coverage.

OOMs covering for Shift will work on WOs from their zone. If an emergencies arise Shift can create WOs

Emergency Communication Procedures

Supervisor and Operator of the Month Schedule

Updated 8/1/16

Anschutz OOMs DC OOMs

Page 64: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

58 3/21/2016

BMO Project Rep Responsibilities for Capital Projects

Design

Attend design meetings

o Access lines of communication with the project team

Distribute project call-down list

Organize construction document submittal reviews for Operations

o Involve Operations SMEs

o Generate ADM work orders for all of the applicable trades for construction document

review for each phase of construction document development via WO request through

CSC

o Collect and submit Operations comments to the project team

o Collect and communicate responses from the project team to Operations

Construction

Attend OAC meetings

o Distribute project updates and schedule

Conduct site walks with Operations staff (quality construction, access, and Standards

compliance)

o Collect and submit comments to the project team

Review and distribute product submittals to Operations SMEs

o Collect and submit comments to the project team

o Set-up a rule in Outlook that forwards any division 23 submittals to the fluid and HVAC

group supervisors, any division 26 submittals to the electrical group supervisor, and

division 23 and 26 submittals to the engineering group supervisor

o Generate ADM work orders for all of the applicable trades for submittal review of

proposed products via WO request through CSC

o Collect and submit Operations comments to the project team

o Collect and communicate responses from the project team to Operations

Attend project team job and punch walks (construction, turnover, 6-mo, and 11-mo)

Coordinate equipment training for Operations staff

Coordinate the turnover of all extra materials or spare parts

Accept O&M manual and warranty log

Provide asset info and project documentation to the building archivist, to include BAS As Builts

and network lighting As Builts

Submit asset list for inclusion in Maximo

Coordinate with Zone and Trade Supervisors to schedule to schedule maintenance development

in Maximo

Provide Operations project acceptance sign-off at turnover

Notify Operations staff of turnover and warranty dates

Page 65: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

59 3/21/2016

Occupancy

Follow-up on punch items

Collect and submit warranty claims

Maintain warranty log

o Coordinate repairs

o Review Responses

o Forward responses to group who issued warranty item for verification before closeout

by project

o Update O&Ms and building archive

Page 66: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

60 3/21/2016

Using the CU Denver Daily Log

The CU Denver Daily Log is intended as an on-line secure source for transferring critical information

between shifts and work groups. These records are archived and used to demonstrate code compliance,

equipment failure dates, warranty issues, work done, etc.

The Daily Log is divided into three sections; On Going Issues, Daily Issues, and Work Group

Accountability.

On Going Issues – These are issues that will be resolved in the immediate future and require action from

successive shifts. Items entered should include

1. The problem.

2. The action required by the successive shifts.

3. The name of the person making the entry.

To make an entry in the On Going Issues section, enter your information in the blank text box and click

the button. Once a line is added it can be updated by clicking on the button for that line.

Information can be updated and/or Date Fixed recorded. Select to save or to discard the

changes. Items will not display on the log after the stated Date Fixed.

Out of Service Equipment – This section lists equipment that is out of service for an extended period. The

intent is to provide a location to document long-term out-of-service equipment without unduly

burdening the On Going Issues section.

To access the Out of Service Equipment section click on the button. The On Going

Issues section will become Out of Service Section.

Page 67: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

61 3/21/2016

The process for entering items is identical to Ongoing Issues. To change back to the Ongoing Issues

Section click on the button.

Daily Issues – These are significant items that should be recorded for historical value. Items should

include

1. Occurrence time.

2. Description of the issue.

3. ATTN box checked if follow-up work is required

4. Location (locations are listed by building name in the pull down but display as GIS name,

5. Person making entry (Names are listed by sign-on name but display as full name. Names can be

overwritten in the edit mode.)

To make an entry in the Daily Issues section, complete the Time, Remarks, ATTN, Location, and Person

fields.

Page 68: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

62 3/21/2016

After clicking on the button the information is recorded in the format below.

Once a line is added it can be updated by clicking on the button for that line. Select to save or

to discard the changes.

Work Group Accountability – This section is intended as a tool for the different work groups to record

they are aware of the items entered in the Daily Log.

The person assigned to review the log should make a check in the box for their work group. This

indicates the work group is attending to the pertinent issues in that shift’s log.

To make an entry click on the button to put the form in edit status.

Check the box to the right of your work group. Click on to save or to disregard changes.

Searching and Printing

You can view the daily log sequential shifts by toggling the shift selection chevrons. Or you

can use the calendar to select dates from history.

Searching the Daily Log - You can search for specific information, in the On Going Issues, by selecting

.To search in the Oos Equipment section click on .Search Daily Issues, by

selecting . These open search pages allowing you to search on combinations of various fields.

You can view a printable version of the daily log by clicking on and printing to your

default or selected printer.

Page 69: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

63 3/21/2016

Responsibilities:

1. Work group supervisors review or assign a staff member to review each shift log and record

their awareness of responsibilities in the daily log.

2. Reviewers edit lines in Daily Issues to record work orders generated or transferred and de-select

the ATTN box. Include your name when updating an original line.

3. Staff records all significant issues or items with historic value in Daily Issues section.

Staff records items requiring actions by successive shifts in the On Going Issues Section.

Page 70: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

64 3/21/2016

BMO Emergency Response Manual

Emergency Definitions:

1. An emergency must be acted upon immediately, utilizing sound judgment by the First Responder 2. All inquiries from the media or press are to be referred to the vice chancellor for university

communications with no exceptions (303)982-9093, pager (303)266-2608. Do not answer any questions from the media.

3. In general, emergencies can be classified as follows a. Danger to Life or Health - call University Police or 911

i. Fire

ii. Radioactive or chemical spills

iii. Police emergencies

iv. Bomb threats

v. Elevator entrapment b. Property Damage

i. Fire

ii. Flooding

iii. Wind damage

iv. Vandalism (determined by UCPD) c. Disruptions of Operations

i. Temperature Control or Ventilation for Research

ii. Utility outages including electricity, steam, chilled water and potable water

iii. Alarms systems

iv. Elevator or other mechanical failures

v. Environmental and fan systems

vi. Electrical Load Shed (Appendix 7)

vii. Trauma cleanup procedures (Appendix 9 - In progress) d. Loss of Resources

i. Potable water

ii. Chilled water

iii. Steam

iv. Natural gas

v. Electricity

vi. Storm drainage

vii. Sewer drainage

Page 71: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

65 3/21/2016

Guidelines:

The purpose of the BMO Emergency Guidelines Manual is to provide step-by-step guidelines for Building Maintenance & Operations (BMO) personnel to respond in case of an emergency to protect campus customers, research, animals, and equipment. Supervisors and Managers are to use the new employee check-in (Appendix 6) and determine personnel who are going to be an OOM (Operator of the Month) and schedule them to complete the OOM training (Appendix 8) before being placed on the OOM schedule. The following departmental personnel must be notified in the event of flooding, damage to property, fire, or disruptions of operations. If an emergency occurs after hours, you must call the cell phone of these individuals. Normal business hours are Monday-Friday 7:30 AM - 4:00 PM. Keep calling until you contact them.

1. Supervisor of the Month (SOM) 2. Facilities Management Director 3. Facilities Management Vice Chancellor

Responsibilities:

4. Shift personnel a. First responder to all emergencies after hours

b. If RAVE Text or Page is received respond to emergency and contact SOM immediately

c. Contact SOM for assistance

d. Provide initial National Incident Management System (NIMS) incident commander

services for non-business hours

1. Zones a. First responder to all emergencies during normal working hours

2. Trades a. First responder to all emergencies during normal working hours

3. Supervisor of the month (SOM) a. Provides supervisory support to shift

b. Provide NIMS incident commander services during emergencies

c. Must respond to scene for all floods

d. If RAVE text or page is received respond to emergency and conduct assessment

e. After site assessment contact another SOM to serve as NIMS communication officer during

emergencies when SOM is mobile if it needs to be escalated

f. After site assessment send out text\email to Asst. Director, Director and AVC to notify them

of emergency and actions taken

g. Contact Risk Management if there is a potential for property loss

Page 72: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

66 3/21/2016

Flood Procedure (Interior)

NOTE: It is extremely important to address ANY flood concern with the utmost urgency.

Definitions:

Minor Flood - A small area that is easy to contain after isolation of the source and can be remediated

quickly. There are no associated damages or operational impacts. Log the event in the daily log to include

building, room and cause of flood.

Major Flood - A large area that cannot be easily contained after isolation of the source and will require

additional help in order to remediate. If two shift people are on duty, one needs to investigate the source

of the leak while the other contacts the SOM. Be prepared to give an accurate description to the SOM

including building, floor, room, type of flood, and whether it is isolated or not. SOM will be contacted for all

floods. Contact University of Colorado Denver Police Department to notify tenants of the emergency. For

any flood that contains oils, solvents, fuels or other unknown chemicals, do not attempt to

remediate. Try to isolate the source and contact the SOM right away. The SOM will then contact

UCPD to contact the Environmental Health & Safety (EH&S) for support and direction on how best

to deal with this type of flood.

First Responder

1. Report to location of occurrence a. Has the source of the flood been isolated (valves shut off or redirected in some cases?)

b. Call SOM immediately after source has been identified and/or secured. If two personnel

are responding to the flood, one should isolate the other should call SOM. After SOM has

been contacted, remove water using flood vacuum and wear PPE (rubber boots, gloves

and safety glasses.)

c. Whenever possible, turn off the electrical power to the flooded rooms and disconnect the

electrical power cords in contact with the floor (computers, centrifuges, etc.). Keep in mind

that turning off the electrical power may affect experiments and other equipment in the

surrounding areas. Inform the SOM of all equipment that is turned off or unplugged for

safety.

d. Discard the water vacuumed up into the sanitary sewer. Do not discard collected water

outside.

Page 73: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

67 3/21/2016

SOM Checklist

1. SOM is notified of flood, and briefed on contents/make-up of flood (i.e., water based, etc.) 2. The SOM shall respond to site of floods that affect more than one room, affect more than one floor,

involve any research building or have the potential for asbestos, any hazard such as lab space, radioactive material, biohazard, biosafety hoods, chemicals, etc.

3. When the SOM is contacted, the SOM shall assess the need for additional staff for cleanup 4. SOM should contact one of the designated remediation crews to mitigate mold. In the event the

flooded area involves chemicals, radioactive materials, fuel, oil, or other biohazard, SOM shall call UCPD to contact the EH&S pager

5. If the flood area has damaged property, equipment, research, animal health, or created a safety issue, the SOM will report to the site and contact EH&S, UCPD and a third party remediation crew as needed.

6. Once the flood issue has been deemed under control the SOM will file a claim with the University’s Risk Management Department. Once filed, the SOM will then contact the zone supervisor the next business day with all the details of the event and shift responsibility to the zone supervisor.

7. If the SOM was notified of the incident via RAVE please send out text\email to Asst. Director, Director and AVC to notify them of emergency and actions taken.

Page 74: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

68 3/21/2016

Major Water Main or Sewer Line Break Emergency Procedure (Exterior)

Definition

Major water main or sewer line breaks are described as large pipe breaks exterior to the building. Both

systems are located underground (min-4 feet). Water main break outside would require City of Aurora

assistance to shut down main valve locate in the street. Sewer line breaks underground are not very

noticeable and would require fluid group on site ASAP.

First Responder

1. Identify source of break and call SOM 2. Need to identify if break is between meter and building or City of Aurora side 3. Brief the SOM on extent of damage including building, location in building, areas affected, and

what type of support is necessary to secure break

SOM Checklist

1. SOM should contact fluid group 2. If break is outside the meter SOM should contact City of Aurora 3. SOM should contact University Police to send out a Rave message to inform customers of the

emergency 4. SOM should contact UCPD to contact EH&S to inform them of the emergency 5. SOM should contact the Facilities Management Grounds supervisor to inform them of the

emergency 6. The SOM shall respond to all main line breaks to determine what needs to be done to bring the

system back online 7. SOM shall assess if additional staff should be contacted for assistance in the cleanup and repair 8. Once the situation is stabilized, the SOM shall file a claim with University Risk Management and

turn over the control of the repair to the fluid group supervisor 9. The following business day, the supervisor for the fluid group will take over the follow up process 10. If the SOM was notified of the incident via RAVE please send out text\email to Asst. Director,

Director and AVC to notify them of emergency and actions taken.

Page 75: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

69 3/21/2016

Electrical Reset for Power Loss & Power Bumps

Definition

The University of Colorado Denver / Anschutz Medical Campus electrical system serves all UC and UCH

buildings. Children’s Hospital of Colorado is not connected to our Electrical Distribution system.

Electrical power to the Campus is supplied by Xcel Energy through 5 - 13,800 Volt feeders connected to 3

distribution busses in the Campus Substation located to Central Utility Plant. The “2A” Buss feeds all

University of Colorado Hospital Buildings. All UC buildings are fed from the “1A” and "B” Busses. Each of

the 3 distribution Busses have 3 loop feeders going out to feed groups of individual buildings through switch

cabinets located in close proximity to each building. In the event power is lost from Xcel Energy, most all of

the buildings are equipped with a Standby Generator which will automatically start and pick up the critical

electrical load that is connected to it. Not all circuits in a building will be powered by the generator during a

power outage. A Power Bump/ Electrical outage on Campus will manifest itself by alarms through Siemens

Building Automation System (BAS) and the fire panels

First Responder

1. Identify size of outage, one building, several rooms, or several buildings

2. If any building is without power, contact SOM and CUP

3. If the campus experiences a power bump, the BAS system will slowly turn on building systems.

This can take some time (up to 30 minutes) for the building to stage and equalize the load

4. Monitor BAS alarm screen to determine systems that might need to be manually controlled

5. Review zone critical list (see below) to ensure all critical equipment is back on line

6. After review of critical systems has been completed and there are still ongoing issues requiring

assistance from trades or zone, the SOM should be contacted

7. Once the emergency has passed and all systems are restored (verified) initiate freezer walk

8. Fire and Jockey Pump – Check to ensure that the fire pump is not operating

Page 76: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

70 3/21/2016

Zone 1

1. Building 400 (Q09)

a. Building 400 MRI (Q09)and PET/SCAN area

b. Building 401 (R09)1st floor freezers and back-up generator

2. AO1 (L15) verify all systems are back on line, including fire system and elevators

Zone 2

1. Education 2 South (L28)

a. First Floor

i. Verify that the elevators are operational

ii. L28-1306B – check the fire alarm (1st floor hallway south end on west side and

pump.)

iii. L28-1306 – verify that the heating water exchangers and pumps are online

iv. Verify that the air compressor (1306) is operational

v. Verify that the chilled water pumps (1306) are online

b. Roof

i. Verify that the air handling units (AHUs) are online

ii. Verify that the general exhaust fans are online

2. Education 2 North (P28)

a. First Floor

i. Verify that the elevators are operational

ii. P28-1101A – check the fire alarm (1st floor hallway north end on east side) and

pump.

b. Roof

i. Verify that the AHUs are online

ii. Verify that the general exhaust fans are online

3. Library (V23)

a. First Floor

i. Verify that the elevators are operational

ii. Stairwell #5 – Check the fire alarm

iii. V23-0100M – verify that the heating water exchangers and pumps are online

iv. V23-0100M – verify that the chilled water pumps are online

b. Second Floor

i. Verify that CRAC units are functioning

c. Third Floor

i. Verify that CRAC units are functioning

d. Roof

i. Verify that the AHUs are online

ii. Verify that the general exhaust fans are online

4. Dental (L26)

a. First Floor

i. Verify that the elevators are operational

ii. L26-022E – check the fire alarm panel (SW entrance) for alarms.

iii. L26-018AM – check the fire pump.

iv. L26-018M – verify that the vacuum pump control system is online.

v. L26-018M – verify that the building air compressors are operational.

vi. L26-018M – verify that the medical air compressors are operational.

vii. L26-018M – verify that the heating water exchangers and pumps are online.

viii. L26-018M – Verify that the chilled water pumps are online

b. Roof

Page 77: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

71 3/21/2016

i. Verify that the AHUs are online

ii. Verify that the general exhaust fans are online

Zone 3

1. Barbara Davis Center (M20)

a. Basement mechanical room (M20-0111m)

i. Chilled Water Pumps – Three (3) chilled water pumps are located in this mechanical room. One pump must operate at all times as it supplies the cooling for the freezer park located in the basement. The freezer park houses millions of dollars in research material for the Barbara Davis Center (BDC) and without cooling the freezers will fail in a short period of time. Hot Water Heating Pumps – Power bumps can change the status of the hot water heating system from OCC1 to vac. This shuts down the pumps and heat exchangers. If found in this condition, simply change the status of the system back to OCC1 and the system should restore itself.

ii. Vacuum Pumps – These aren’t as critical, but if you are running on the number three chilled water pump it is best to shut the vacuum pumps off.

iii. High and Low Steam Valves – On occasion a power has closed both of these valves, leaving the building without steam. Verify that one of the valves is open and if neither is, open the high flow valve. This protects the low flow steam valve from damage

b. Fire Pump Room (M20-0109)

i. Fire and Jockey Pump – Check to ensure that the fire pump is not operating c. Rooftop Equipment

i. Exhaust Fans – Check to ensure that at least one of the EHU fans (a, b, c, or d) is operating. These fans exhaust the research areas and ALL of the fume hoods. One of these fans should be in operation at all times even if it is only operating at less than capacity

ii. Medical Air Unit (MAU) Fans – Check to ensure that both of these fans (1 and 2) are online

iii. AHU 1 – Check to ensure that this fan is operating iv. Elevators – Ensure that both of the elevators are functioning

2. Ben Nighthorse Campbell Building (M24)

a. First floor mechanical room (M24-153Bm)

b. Hot Water Heating System – During cold weather make sure that the heat exchangers and

hot water heating pump are online

c. Elevators – Ensure both passenger elevators are functioning

3. ED1 Building (P26)

a. First Floor Mechanical Room (P26-1502Bm)

b. Hot Water Heating System – During cold weather make sure that the heat exchangers and

hot water heating pump are online

c. Fire Pump and Jockey Pump – Check to ensure that the fire pump is NOT running

d. Elevators – Ensure that ALL four passenger elevators are functioning

e. Morgue Coolers – Check to see that the morgue coolers are functioning. The condensing

units are located on the roof just south of the penthouse

f. Air Handling Units and Exhaust Fans – AHU-P-3 feeds the gross anatomy area, and if

possible, should be placed back in service

4. Fulginiti Building (R27)

a. Basement Mechanical Room (R27-005m)

b. Hot Water Heating System – Hot water heating and chilled water are supplied to this

building from ED1. During cold weather make sure that the heat exchangers and hot water

heating pumps located in ED1 are online

c. Elevators – Ensure that the passenger elevator is functioning

d. Verify that domestic hot water heater is operating

Page 78: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

72 3/21/2016

Zone 4

1. PRF (AK32) – Verify that all systems have returned to normal on BAS system and physically check

all boilers; reset if needed

2. Pascal Library (P30) – Verify on BAS system that all systems have returned to normal

3. Environmental Health and Safety (R30) – Verify on BAS system that all systems have returned to

normal

4. Henderson Parking Garage (V17) – Verify that all elevators are operational and reset if needed;

check lights and auto doors

5. Campus Services (T36) – Verify on BAS system that all systems have returned to normal; check

elevators and reset if needed.

Page 79: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

73 3/21/2016

Zone 5

Priority 1, Priority 2

1. Building 500 (Q20)

a. Basement

i. Q20-CB001 – check the main air compressors and alternate if necessary.

ii. Q20-CB005T – check telecom room cooling

iii. Q20-CB003 – check that 2 CHW pumps are on. #1 should be on at all times.

iv. Q20-CB003 – (during power outage at RC1 or R2) check the RC1 and R2

emergency CHW pump is operating.

v. Q20-CB011 – check that the condensate mover is operating

vi. Q20-CB010 – check air compressors are operating and maintaining 20 PSI. They

provide motive air for the CHW and condenser water valves for the backup

chillers.

b. Ground Floor

i. Q20-CG002 – check main fire alarm panel for operability and alarms, Call the fire

alarm techs to clear alarms or correct problems.

ii. Ground floor center, west, east, north, west dock – check elevators 1, 2 and 3, 4,

5, 6, and 7 respectively for entrapments and operability.

iii. Q20-EG330C and Q20-EG331 (IT servers) – check Liebert or fan coil cooling

iv. Q20-WG102T, EG302T, EG330C – check telecom room cooling

c. First Floor

i. Q20-N1202T, Q20-W1102T, Q20-E1302T – check telecom room cooling

d. Second Floor

i. Q20-N2401P-SA-Q20-03-004 Serves third floor north and center – ensure AHU

is online

ii. Q20-W2133T, Q20-E2302T – check telecom room cooling

e. Third Floor

i. Q20-W3101T, Q20-W3162, Q20-C3001T – check telecom room cooling

f. Fourth Floor

i. Q20-E4327 and Q20-E4328 – check freezers (medicine) for high temp and

alarms.

ii. W4131, W4132, W4109 (IT servers) – check Liebert or fan coil cooling

iii. W4109, W4131, W4132, W4101T, E4302T – check telecom room cooling

g. Fifth Floor

iv. Q20-C5001 and Q20-C5002 – check freezers (medicine) for high temp and

alarms.

v. Q20-E5334 and Q20-E5335 – check freezers (medicine) for high temp and

alarms.

i. Q20-E5325P check SA-Q20-05-005 Serves fourth floor east – ensure AHU is

online

ii. Q20-E5307M check SA-Q20-05-004 Serves fifth floor east – ensure AHU is

online

iii. Q20-W5114, Q20-W5114B (UH Med Rec) – check Liebert or fan coil cooling

iv. Q20-N5217M check SA-Q20-05-002 Serves fifth north and center – ensure AHU

is online

v. Q20-N5204T, Q20-E5300T, Q20-W5102T, Q20-W5114B – check telecom room

cooling

h. Sixth Floor

i. Q20-E6302T, Q20-6102T– check telecom room cooling

Page 80: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

74 3/21/2016

i. Seventh Floor

i. Q20-W7002T, Q20-W7001T – check telecom room cooling

2. R24 (533)

a. First Floor

i. Q20-R24-005 – check telecom room cooling

Page 81: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

75 3/21/2016

Zone 6

Priority 1

1. RC1 North (P18)

a. Interstitial

i. P18-0V01 – verify fire pump JP-1 and fire alarms

ii. P18-0V01 – check condensate pumps CRP – NV1-101 and 102 alternate as

needed

iii. P18-0V01 – check domestic water pumps - HBP-1 thru 3 one online at all times.

iv. P18-MS04 – check vacuum pumps V-1 thru V-3 all 3 pumps alternate as needed.

v. P18-MS04 – check domestic water heat exchangers – HXG 1 and 2 alternate.

Booster pump CP1 should be online at all times.

vi. P18-0V01 – check sewage ejection pumps – alternate as needed.

b. Second Floor

i. P18-2207M – Check AHUs SA-P18-02-005 and SA-P18-02-006 both units are to

be online at all times

ii. P18-2207M – Chilled Water Pumps CHW-N-201 thru 203 one pump is to be

online at all times

iii. Verify that there are adequate air handlers online to maintain duct static set point

at 1.9”

iv. Tertiary Chilled Water Pumps- CHP-N-204 and 205 both pumps are to be online

at all times

v. P18-2207M – Heat Exchangers- (HHX-1 and 2) Pumps HWP-N201 and N202

one pump online at all times

c. Ninth Floor

i. P18-9404H – check supply damper for P18-9405 BSL-3 lab in the linear hallway

outside of 9404H. The damper should be open at all times.

d. Roof

i. Check exhaust GE-P18-R-006 and 007, both fans should be online at all times

ii. Check exhaust fans FE-P18-R-008 and 009, they should be online at all times

Serves ABSL.

iii. Check exhaust FE-P18-R-013 and 014 they are to be online at all times. Serves

iodination lab (P18-9208) BIO safety cabinets

iv. Check exhaust fans FE-P18-R-016 and 017 fans should be online at all times

v. Check exhaust FE-P18-R-015 this fan should be online at all times

vi. Check exhaust fans FE-P18-R-001 thru 005 they should be online at all times

with duct static pressure of 1.91.

vii. 10103E penthouse – BSL-3 UPS - During a power outage the UPS must be

checked to ensure the UPS has engaged. After power is restored recheck the

UPS to verify that it has switched back to normal power.

viii. Check vivarium rack wash exhaust – FE-P18-R-010 and 10A both fans should be

online at all times.

ix. Check glass wash exhaust GE-P18-R-012, it should be online at all times.

2. RC1 South (L18) Priority 1

e. First Floor

x. L18-1208AM – check condensation pump CRP-S101 for proper operation, inside

main electrical room (L18-1208E)

a) Second Floor

Page 82: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

76 3/21/2016

xi. L18-2200M – check building supply air, AHUs L18-02-001 thru L18-02-004 all

AHUs are to be online at all times with duct static pressure of 1.71.

xii. L18-2200M – check tertiary loop pumps CHP-S201 and S202, both pumps

should be online at all times

b) Roof

xiii. Check exhaust fan FE-L18-R-009, fan should be online at all times. Serves

iodination lab.

xiv. Check building exhaust, exhaust fans FE-L18-R-001 thru FE-L18-R-005 should

be online at all times with a duct static pressure of 1.91.

xv. Check glass wash exhaust L18-R-007 fan should be online at all times.

Page 83: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

77 3/21/2016

Zone 7

1. Research 2 (P15) Priority 1 a. Vivarium

xvi. P15-0403M – check animal drinking water station should be online at all times.

i. Stairwell Pressurization Fans: SA-P15-R-005 and SA-P15-R-006 (P15-Roof) only online when needed Condensate Pumps: SM-P15-00-001 thru SM-P15-00-003 (P15-0403M) Pumps alternate as needed; ensure system is not in alarm.

ii. Heating Water Pumps: HX-P15-01-001 and HX-P15-01-002 (P15-1300M) Pumps alternate as needed; ensure system is not in alarm.

b. Interstitial xvii. (Location) check fire alarm/pump Demands an immediate review of the fire alarm

and pumps station after a power bump or power loss.

xviii. P15-M300DM – check air compressors CA-P15-M-001 it should be online at all

times.

xix. P15-M300DM – check vacuum pumps: VAC-P15-M-001 thru VAC-P15-M-003

three pumps alternate as needed, ensure system is not in alarm.

c. First Floor i. P15-1500A2 – Vivarium freight elevator #7 should be online at all times.

ii. P15-1400 – check freezer farm for alarming or inoperative units.

iii. P15-1400 – check fan coil units FCU-P15-01-013 thru FCU-P15-01-22 all ten

FCUs should be online at all times.

iv. P15-1300M – check primary chilled water pumps CH-P15-01-001 thru CH-P15-

01-004 one should be online at all times.

v. P15-1300M – check tertiary chilled water loop pumps CH-P15-01-005 and CH-

P15-01-006 both should be online at all times.

vi. P15-1300M – check booster pumps DW-P15-01-001 thru DW-P15-01-003) one

should be online at all times.

vii. P15-1300M – check heat exchangers DHW-P15-01-001 thru DHW-P15-01-004

all should be online at all times.

i. Heating Water Exchangers: HX-P15-01-001 and HX-P15-01-002 (P15-1300M) Exchangers rotate on a lead/lag schedule

d. Second Floor i. P15-2300M – check air handling units SA-P15-02-001 and SA-P15-02-002 they

should be online at all times (serve vivarium.)

ii. P15-2300M – check emergency chilled water valves should be in normal (closed)

position when not needed. If needed, verify the valves are open.

iii. P15-2300M – check clean steam generator HX-P15-02-001 it should be online at

all times

iv. P15-2300M – check air handling units SA-P15-02-003 thru SA-P15-02-010

typically 6 of the 8 fans are online at all times. The system should maintain a

duct static set point of 2” WC.

v. P15-2300M – check return air units RA-P15-02-001 and RA-P15-02-001 both

should be online at all times.

vi. P15-2300M – check AHU controls air compressor CA-P15-01-001 it should be

online at all times.

e. Eleventh Floor vii. P15-11291 – Check Iodination Lab - Demands an immediate review of

associated critical systems after power bumps or power loss.

Page 84: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

78 3/21/2016

f. Roof viii. Check general exhaust fans FE-P15-R-008 and FE-P15-R-009 both fans should

be online at all times.

ix. Check BSL-3 exhaust fans FE-P15-R-015 and FE-P15-R-015 both should be

online at all times

x. Check supply air fan SA-P15-R-001 it should be online at all times (serves BSL-

3.)

xi. Check exhaust fan FE-P15-R-014 it should be online at all times. (serves

Iodination Lab)

xii. Check exhaust air fans FE-P15-R-001 thru FE-P15-R-007 6 of the 7 should be

online at all times.

i. Check the vivarium rack wash exhaust FE-P15-R-012 it should be online at all times.

ii. Check the glass wash exhaust FE-P15-R-013 it should be online at all times.

iii. Check the stairwell pressurization fans SA-P15-R-005 and SA-P15-R-006 they should be online only when needed.

Page 85: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

79 3/21/2016

Zone 8

1. Pharmacy Building (V20) a. First Floor

i. Verify all three elevator are functional b. Basement Mechanical Room

i. Verify fire alarm/fire pump system is normal. ii. Verify heating water pump is running, pumps alternate as needed iii. Verify 550 GPM heating water flow is present. iv. Verify heat exchanger is online, if not; startup/switchover procedure is located on

the bottom left corner of the HX Graphics. v. Verify liquid movers are on vi. Verify chilled water pump is running, pumps alternate as needed. vii. Verify vacuum system is on, pumps alternate as needed.

c. Penthouse/Roof i. Verify at least 3 Exhaust Fans are running ii. Verify at least Supply Fans are running iii. Return fans both run all the time. iv. Verify air compressor is on

d. Cold Rooms i. 2nd floor, 3rd floor, 4th floor ii. Check freezers in LER floors 2, 3, and 4

2. Health and Wellness Center (V08) a. First floor

i. Check all elevators are operational b. Basement mechanical room 0109M

i. Verify AHU’s are on. ii. Verify heating water pumps are on iii. Verify chilled water pumps are on iv. Verify heat exchangers (heating/domestic) are on v. Verify liquid mover is on. vi. Verify domestic water system is on

c. Basement mechanical room 0108 i. Verify heat exchanger is on. ii. Verify liquid mover is on iii. For critical shut offs BAS roomV08-002m

d. Penthouse/Roof i. Verify all AHU’s are on ii. Mechanical room V08-1220M; verify AHU is on

SOM Checklist

1. Once the emergency has passed and all systems are restored and verified initiate freezer walk

2. Maintain SOM log

a. SOM should contact University Police to send out a Rave message to inform customers of

the emergency.

b. SOM should contact Electrical group to determine what needs to be done to bring the

system back on line.

c. SOM shall assess if additional staff should be contacted for assistance to bring systems

back on line.

d. Once things are under control, if required the SOM shall file a claim with University Risk

Management and turn over the control of the repair to the proper supervisor

e. If the SOM was notified of the incident via RAVE please send out text\email to Asst.

Director, Director and AVC to notify them of emergency and actions taken.

f. The following business day, the supervisor for the zone will take over the process

Page 86: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

80 3/21/2016

Loss of Chilled Water

Definition

The university chilled water (primary loop) is supplied from the Central Utility Plant (CUP). If you receive a

Siemens alarm, or are contacted by the CUP, that chilled water supply temperature is too high, you must

contact SOM immediately.

First Responder

1. Below is a checklist of the items to cover in the event of chilled water loss. If you receive an alarm

indicating that the chilled water temperature is too high; first determine if the problem is a local

problem or a global problem.

2. If it is a campus wide problem contact the CUP and/the SOM

3. If it is a single building problem determine if it is a problem with the primary loop or the secondary

loop and contact the CUP.

a. If the problem is with the secondary or tertiary loop

i. Check flow, pressure, supply and return temperatures and system piping integrity

ii. Take initial corrective action

iii. Notify the CUP to communicate the problem.

iv. Contact SOM, make them aware of the problem and advise them to call for help if

needed.

v. Coordinate emergency repairs.

b. If the problem is with the primary loop

i. Check flow, pressure, supply and return temperatures and system piping integrity.

ii. Contact the CUP to communicate the emergency and document the problem.

iii. Get the operators name and record date and time for the log.

iv. If the problem originates in the CUP get the operator’s ETA for repair ETA.

v. Contact SOM, make them aware of the problem and advise them to call for help

or to institute the Chilled Water Load Shedding Procedure (Appendix 8).

4. Complete zone check list below:

Page 87: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

81 3/21/2016

Zone 1

1. Academic Office Building (L15) the critical equipment are telecom rooms located in the center of

the building on each floor between the main break rooms and work rooms.

a. First floor – check temp in 1316T, Monitor systems on the BAS. Monitor VFDs running the

pumps in the 1008M (pump room). Chilled water pumps 3, 4, and 5 are on emergency

power 1 & 2 are strictly on utility power.

b. Second floor – check temp in 2316T & 2110 IT server rooms

c. Third floor – check temp in 3316T & 3216 IT server rooms d. Fourth floor – check temp in 4316T e. Fifth floor – check temp in 5316T f. Sixth floor – check temp in 6316T g. Seventh floor – check temp in 7316T h. Eighth floor – check temp in 8316T i. Ninth floor- check temp in 9000M elevator mechanical room j. Rooftop penthouse - shut off the chilled water to the air handlers (if OAT is above 55

degrees) to conserve the chilled water in the closed loop system.

2. When cooling is not achieved because the loops temp is too high start opening doors to all the

critical equipment in the above rooms.

Page 88: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

82 3/21/2016

Zone 2

1. School of Dental Medicine (L26)

a. The vacuum pumps (basement mechanical room; L26-018m) use chilled water for cooling,

therefore they will need to be turned off and the occupants notified that there will be no

vacuum for the duration of the outage.

b. If not already on, and conditions warrant it, you may want to consider activating the

evaporative cooling system for AHU-3.

2. Library (V23)

a. Check the room temperatures in the library server room (V23-2102F), if above 85-degrees

notify UP to contact the library staff and if available provide a move-n-cool to this area or

prop the door open and place a fan to circulate air.

b. Check the room temperatures in the library server room (V23-3103) equipment locate in

room 3104, if above 85-degrees notify UP to contact the library staff and if available provide

a Move-N-Cool to this area or prop the door open and place a fan to circulate air.

3. ED II (L28 / P28) – no special response required

General Note: If the outside air temperature is favorable, AHUs could be operated using outside air to

minimize heat load within buildings. During warmer weather, be sure to minimize cooling requirements by

turning off or down unnecessary heat sources such as lighting, autoclaves, glass washers, or excessive

outside air.

Page 89: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

83 3/21/2016

Zone 3

1. Ben Nighthorse Campbell Building (M24)

a. There is a FCU on the second floor (Room 233) that is important but NOT critical. If time

permits, space temperatures should be checked

2. Barbara Davis Center (M20)

a. The freezer park. Room M20-0117: The freezer park that is located in the basement of

the Barbara Davis Center is probably the most important room in the zone. There are

millions of dollars of research stored there in 60+ freezers. Room cooling is accomplished

by the five (5) fan coil units that are located in the room. Loss of chilled water will cause a

rapid temperature rise in the room and if the outage is for an extended period of time, the

following steps should be followed.

i. The damper for terminal box CAV-M20-B-007 should be set at 100% (this assumes

an OAT of 80 degrees or less)

ii. The exhaust fan FE-M20-R-010 should be started manually.

iii. The doors to the hallway and stairs should be opened

iv. If it has been determined that this outage will be for an extended period of time the

owners of the freezers will need to be contacted and actions initiated to protect the

contents of the freezers.

v. Set up portable fans to help move the air around.

vi. There are several corridors on the third and fourth floor where freezers are located

but as long as there is a sufficient air supply to the space (even though the DAT of

the terminal boxes may be higher than normal, the freezers should be alright.

vii. The vacuum pumps use chilled water to cool the sealant water. In order to protect

the vacuum pumps, they should be shut down.

3. Education 1 (P26)

a. Loss of chilled water may cause comfort issues but little else

b. If not already on, and conditions warranty it, you may want to consider activating the

evaporative cooling system for AHU-3.

4. The Fulginiti Building (R27)

a. Loss of chilled water may cause comfort issues but little else

b. If not already on, and conditions warrant it, you may want to consider activating the

evaporative cooling system.

Page 90: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

84 3/21/2016

Zone 4

Priority 1, Priority 2

1. PRF (AK32) AHU-1 and AHU-2 no critical equipment, standalone system

a. 1-A-114 mechanical room

i. Air drier # 1, turn off / notify occupants

b. 130 mechanical room

i. FCU-1-001, move-n-cool, open door / box fan

c. 144 IT room

i. FCU-1-002, move-n-cool, open door / box fan

d. Roof

i. PH1, turn off / notify occupants

ii. PH2, turn off / notify occupants

iii. AHU-1, turn off / notify occupants

2. PASCAL (P30) SA-P30-02-002 and SA-P30-02-002 no critical equipment

a. 101, office

i. FCU-01-003

b. 102 processing

ii. FCU-01-001

iii. FCU-01-002

c. 102D IT room

i. FCU-01-009, move-n-cool, open door / box fan

d. 103 reading room

i. FCU-01-004

e. 104 reading room

i. FCU-01-005

ii. FCU-01-006

f. 104F reading room

i. FCU-01-007

g. 104D lounge

i. FCU-01-008

h. 201-C-M mechanical room

i. AHU-02-001, turn off / notify occupants

i. 201-1C-1M mechanical room

i. AHU-02-002, turn off / notify occupants

3. EH&S (R30 and R31) AHU-1 and AHU-2 no critical equipment

a. 100DT IT room

i. FCU-01-001, move-n-cool, open door / box fan

b. PH-200 mechanical room

i. AHU-P-001, turn off / notify occupants

ii. AHU-P-002, turn off / notify occupants

iii. AHU-P-003, turn off / notify occupants

iv. FCU-P-001, move-n-cool, open door / box fan

v. FCU-P-002, move-n-cool, open door / box fan

4. T36 SA-T36-01-003, T36-P-001 and SA-T36-01-002 no critical equipment

a. 118T, IT room

i. FCU-01-001, move-n-cool, open door / box fan

b. 120 conference room

Page 91: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

85 3/21/2016

i. AHU-01-001, turn off / notify occupants

c. 130 mail room

i. AHU-01-004, turn off / notify occupants

d. 141F2 shops

i. AHU-01-002, turn off / notify occupants

e. 141GT IT room

i. FCU-01-002, 141GT, 1, IT room, move-n-cool, open door / box fan

f. 151 paint shop

i. AHU-01-003, 151, 3, paint shop, turn off / notify occupants

g. 151A

i. Air dryer # 1, 151A

ii. Air comp. # 1, 151A

h. Pent House

i. AHU-P-001 turn off / notify occupants

i. 259T IT room

i. FCU-02-001, 259T, open door / box fan

j. 358T IT room

i. FCU-03-001, 358T, move-n-cool, open door / box fan

Page 92: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

86 3/21/2016

Zone 5

1. Building 500 (Q-20)

a. In the event of a Cup loss flag/flow to Building 500, Verify that the backup chiller system is

online. The system has a ten minute time out time delay before bringing chillers on, chillers

will be added according to demand. If the chillers did not come on, go to the BAS chiller

wed page. Verify chiller status is in enable. Then go to the BAS CUP-CHW FLOW page to

the bottom left hand corner, double click on the PM-CHILLER RUN icon to start chillers.

b. In the event of a Cup loss flag/flow to Building 500 only the chiller plant has enough

capacity to handle the entire cooling load of Building 500. In the event of a Cup loss

flag/flow to RC1 and R2 the Tyco valve CHWP 1 ISO VLV located in basement

mechanical room CB003 needs to be closed isolating non-critical areas, and serves the

building critical loop (IT areas) also sending chilled water to RC1 and R2 Vivarium’s.

Verify the valve status on the BAS Q20 secondary CHW SYS graphics page.

Page 93: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

87 3/21/2016

Zone 6

1. RC1 (L18,P18)

Priority 1, Priority 2

a. Reduce the chilled water demand in RC1 (L18,P18)

i. Allow the Building 500 chilled water system to activate and serve RC1 and RC2.

Building 500 non-critical areas will not be feed by the chillers.

ii. Command the chilled water valves closed for the non-critical AHUs and allow the

water to serve the critical loads such as environmental chambers, and coolers.

iii. If the environmental chambers begin to fail, notify the occupants of the issue.

There may be a need to get dry ice or move research to other areas to maintain

a refrigerated environment.

iv. If it is cold out and there is no chilled water flow at all, it may be possible to make

cold water by using the AHUs as heat exchangers. This can be done by

commanding all the chilled water valves open and allowing the 55ᵒ air to transfer

to coils.

b. Reduce the chilled water usage of office spaces

i. Command the chilled water valves closed for mixed air units serving office

spaces. If there are no CUP chillers, but chilled water flow, the chilled water

system can remain cold for a period of time due to the large mass of water in the

underground piping.

ii. Determine if the mixed air units would be better to operate with 100% outside air

or 100% return air.

iii. It is possible to pre-cool office spaces by operating mixed air units when the

outside air temperature is low during the periods of 2:00 am to 6:00 am.

c. Returning from a chilled water outage

i. Release all overrides and return the systems to normal operation.

2. Vivarium

a. V-1001M mechanical room

i. FCU-V-001, Move-N-Cool open doors/box fan

b. V-M100A cage wash

i. FCU-V-002, turn off / notify occupants

c. V-102 autoclave room

i. FCU-V-003, turn off / notify occupants

3. Interstitial

a. IN-001

i. FCU-IN-001, Move-N-Cool open doors/box fan

b. IN-001EM electrical room

i. FCU-IN-002, Move-N-Cool open doors/box fan

c. IN-M001T telecom room

i. FCU-IN-003, Move-N-Cool open doors/box fan

d. IN-M002T telecom room

i. FCU-IN-004, Move-N-Cool open doors/box fan

e. IN-001M mechanical room

i. Vac. Pump 1, turn off / notify occupants

ii. Vac. Pump 2, turn off / notify occupants

iii. Vac. Pump 3, turn off / notify occupants

Page 94: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

88 3/21/2016

iv. Air dryer 1, turn off / notify occupants

v. Air dryer 2, turn off / notify occupants

vi. Air comp 1, turn off / notify occupants

vii. Air comp 2, turn off / notify occupants

4. 1ST floor

a. 11303M elect room

i. AHU-01-101, building air

b. 1300E elec. room

i. AHU-01-102, Move-N-Cool open doors/box fan

c. 1204T IT room

i. FCU-01-001, Move-N-Cool open doors/box fan

d. 1106T IT room

i. FCU-01-003, Move-N-Cool open doors/box fan

e. 1006AE, IT room

i. FCU-01-A01, Move-N-Cool open doors/box fan

5. Second floor

a. 2200T, IT room

i. FCU-02-001, Move-N-Cool, open doors/box fan

b. 2207M mech. room

i. AHU-N201, building air, see loss of chilled water, first responder list

ii. AHU-N202, building air, see loss of chilled water, first responder list

iii. AHU-N203, building air, see loss of chilled water, first responder list

iv. AHU-N204, building air, see loss of chilled water, first responder list

v. AHU-N205, vivarium air, see loss of chilled water, first responder list

vi. AHU-N206, vivarium air, see loss of chilled water, first responder list

vii. AHU-N207, building air, see loss of chilled water, first responder list

c. 2207T, IT room

i. FCU-02-002, Move-N-Cool, open doors/box fan

6. Third floor

a. 3500M mechanical room

i. AHU-N301, building air, see loss of chilled water, first responder list

ii. AHU-N302, building air, see loss of chilled water, first responder list

iii. AHU-N303, building air, see loss of chilled water, first responder list

iv. AHU-N304, building air, see loss of chilled water, first responder list

v. FCU-03-A01, 3500M, 2, IT room, Move-N-Cool, open doors/box fan

7. Fourth floor

a. 4113E electrical room

i. FCU-04-002, Move-N-Cool, open doors/box fan

b. 4200T IT room

i. FCU-04-001, Move-N-Cool, open doors/box fan

c. 4201 cold room

i. EVR-04-001, notify tenant, ensure doors are kept closed

d. 4211 cold room

i. EVR-04-002, notify tenant, ensure doors are kept closed

Page 95: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

89 3/21/2016

e. 4217T IT room

i. FCU-04-003, Move-N-Cool, open doors/box fan

f. 4219 cold room

i. EVR-04-003, notify tenant, ensure doors are kept closed

8. Fifth floor

a. 5113 elec. room

i. FCU-05-002, Move-N-Cool, open doors/box fan

b. 5200T IT room

i. FCU-05-001, Move-N-Cool, opening doors/box fan

c. 5210 cold room

i. EVR-05-001, notify tenant, and ensure doors are kept closed

d. 5211, cold room

i. EVR-05-002, notify tenant, and ensure doors are kept closed

e. 5217T, IT room

i. FCU-05-003, Move-N-Cool, open doors/box fan

f. 5218 cold room

i. EVR-05-003, notify tenant, and ensure doors are kept closed

g. 5219 cold room

i. EVR-05-004, notify tenant, and ensure doors are kept closed

9. Sixth floor

a. 6111E elec. room

i. FCU-06-002, Move-N-Cool, open doors/box fan

b. 6200T IT room

i. FCU-06-001, Move-N-Cool, open doors/box fan

c. 6201 cold room

i. EVR-06-001, notify tenant, and ensure doors are kept closed

d. 6210 cold room

i. EVR-06-002, notify tenant, and ensure doors are kept closed

e. 6211 cold room

i. EVR-06-003, notify tenant, and ensure doors are kept closed

f. 6217T IT room

i. FCU-06-003, Move-N-Cool, open doors/box fan

g. 6219 cold room

i. EVR-06-004, notify tenant, and ensure doors are kept closed

10. Seventh floor

a. 7112E, elec. room

i. FCU-07-002, Move-N-Cool, open doors/box fan

b. 7200T IT room

i. FCU-07-001, Move-N-Cool, open doors/box fan

c. 7210 cold room

i. EVR-07-001, notify tenant, ensure doors are kept closed

d. 7216T IT room

i. FCU-07-003, Move-N-Cool, open doors/box fan

e. 7218 cold room

i. EVR-07-002, notify tenant, ensure doors are kept closed

Page 96: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

90 3/21/2016

11. Eighth floor

a. 8112E electrical room

i. FCU-08-002, Move-N-Cool, open doors/box fan

a. 8200T IT room

ii. FCU-08-001, Move-N-Cool, open doors/box fan

b. 8201 cold room

i. EVR-08-001, notify tenant, and ensure doors are kept closed

c. 8217T IT room

iii. FCU-08-003, Move-N-Cool, open doors/box fan

d. 8219 cold room

iv. EVR-08-004, 8219, notify tenant, and ensure doors are kept closed

12. Ninth floor

a. 9111E elec. room

i. FCU-09-002, Move-N-Cool, open doors/box fan

b. 9200T IT room

i. FCU-09-001, Move-N-Cool, open doors/box fan

c. 9201 cold room

i. EVR-09-001, notify tenant, and ensure doors are kept closed

d. 9210 cold room

i. EVR-09-002, notify tenant, and ensure doors are kept closed

e. 9215 cold room

i. EVR-09-003, notify tenant, and ensure doors are kept closed

f. 9216 cold room

i. EVR-09-004, notify tenant, and ensure doors are kept closed

g. 9217T IT room

i. FCU-09-003, Move-N-Cool, open doors/box fan

13. Penthouse

a. 10102M elevator room

i. AHU-P-101

b. 10102M elevator room

i. AHU-P-102

c. 10103E elec. room

i. FCU-P-002, Move-N-Cool, open doors/box fan

d. 10104E elec. room

i. FCU-P-001, Move-N-Cool, open doors/box fan

e. 10201M mech. room

i. FCU-P-003, Move-N-Cool, open doors/box fan

Page 97: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

91 3/21/2016

Zone 7

1. R-2 (P15) Priority 1, Priority 2

2. Interstitial

a. M300AM, vault

i. FCU-3, open doors/box fan

b. M300BE, electrical room

i. FCU-5, open doors/box fan

c. M300DM, mech. room

i. Air dryer #1, turn off/notify occupants

ii. Air dryer #2, turn off/notify occupants

iii. Air comp #1, turn off/notify occupants

iv. Air comp #2, turn off/notify occupants

v. FCU-1, open doors/box fan

vi. VAC Pump #1, turn off/notify occupants/re-pipe domestic water to one-pass

vii. VAC Pump #2, turn off notify occupants re-pipe domestic water to one-pass

viii. VAC Pump #3, turn off notify occupants re-pipe domestic water to one-pass

a. M300D1M elevator room

i. FCU-2, open doors/box fan

b. M300ET electrical/IT room

i. FCU-6, open doors/box fan

c. M300FE IT room

i. FCU-7, open doors/box fan

3. First floor

a. 1C02 corridor

i. FCU-8, open doors/box fan

ii. FCU-9, 1C02, corridor, open doors/box fan

b. 1099F fire command

i. FCU-11, open doors/box fan

c. 1105T elec./IT room

i. FCU-5, open doors/box fan

d. 1108 security

i. FCU-10, Move-N-Cool, open doors/box fan

e. 1112T server room

i. FCU-23, Move-N-Cool, open doors/box fan

f. 1202 server room

i. FCU-12, Move-N-Cool, open doors/box fan

g. 1300M mech. room

i. FCU-6, open doors/box fan

ii. FCU-7, open doors/box fan

h. 1301T it room

iii. FCU-1, open doors/box fan

i. 1309 elec. room

i. FCU-2 open doors/box fan

j. 1310AE elec. room

i. FCU-4 open doors/box fan

k. 1310E elec. room

Page 98: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

92 3/21/2016

i. FCU-3 open doors/box fan

l. 1400 freezer farm

i. FCU-13, Move-N-Cool, open doors/box fan

ii. FCU-14, Move-N-Cool, open doors/box fan

iii. FCU-15, Move-N-Cool, open doors/box fan

iv. FCU-16 , Move-N-Cool, open doors/box fan

v. FCU-17, Move-N-Cool, open doors/box fan

vi. FCU-18, Move-N-Cool, open doors/box fan

vii. FCU-19, Move-N-Cool, open doors/box fan

viii. FCU-20, Move-N-Cool, open doors/box fan

ix. FCU-21, Move-N-Cool, open doors/box fan

x. FCU-22, Move-N-Cool, open doors/box fan

4. Second Floor

a. 2100A, IT room

i. FCU-2, open doors/box fan

b. 2300BT, IT room

i. FCU-1, open doors/box fan

c. 2300M mech. room

i. AHU-1 vivarium air supply, bldg. 500 chillers to provide chilled water

ii. AHU-2, vivarium air supply, bldg. 500 chillers to provide chilled water

iii. AHU-3, building air supply, enable evap. cooling

iv. AHU-4, building air supply, enable evap. cooling

v. AHU-5, building air supply, enable evap. cooling

vi. AHU-6, building air supply, enable evap. cooling

vii. AHU-7, building air supply, enable evap. cooling

viii. AHU-8, building air supply, enable evap. cooling

ix. AHU-9, building air supply, enable evap. cooling

x. AHU-10, building air supply, enable evap. cooling

5. Third Floor

a. 3115T elec./IT room

i. FCU-2, open doors/box fan

b. 3201T elec./IT room

i. FCU-1, open doors/box fan

c. 3233 cold room

i. EVR-1, ensure doors are kept closed

d. 3234 cold room

i. EVR-2, ensure doors are kept closed

6. Fourth Floor

a. 4115T elec./IT room

i. FCU-2 open doors/box fan

b. 4201T elec./IT room

i. FCU-1, open doors/box fan

c. 4256 cold room

i. EVR-1, ensure doors are kept closed

d. 4257 cold room

i. EVR-2, ensure doors are kept closed

Page 99: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

93 3/21/2016

7. Fifth Floor

a. 5115T elec./IT room

i. FCU-2, open doors/box fan

b. 5201T elec./IT room

i. FCU-1, open doors/box fan

c. 5233 cold room

i. EVR-1, ensure doors are kept closed

d. 5234 cold room

i. EVR-2, ensure doors are kept closed

e. 5256 cold room

i. EVR-3, ensure doors are kept closed

8. Sixth Floor

a. 6201T elec./IT room

i. FCU-1, open doors/box fan

b. 6115T elec./IT room

i. FCU-2, open doors/box fan

c. 6233 cold room

i. EVR-1, ensure doors are kept closed

d. 6234 cold room

i. EVR-2, ensure doors are kept closed

e. 6256 cold room

i. EVR-3, ensure doors are kept closed

9. Seventh Floor

a. 7115T, elec./IT room

i. FCU-2, open doors/box fan

b. 7201T, elec./IT room

i. FCU-1, open doors/box fan

c. 7233, cold room

i. EVR-1, ensure doors are kept closed

d. 7234, cold room

i. EVR-2, ensure doors are kept closed

e. 7256, cold room

i. EVR-3, ensure doors are kept closed

f. 7257, cold room

i. EVR-4, ensure doors are kept closed

10. Eighth Floor

a. 8115T, elec./IT room

i. FCU-2, open doors/box fan

b. 8201T, elec./IT room

i. FCU-1, open doors/box fan

c. 8233, cold room

i. EVR-1, ensure doors are kept closed

d. 8234, cold room

i. EVR-2, ensure doors are kept closed

e. 8257, cold room

i. EVR-3, ensure doors are kept closed

Page 100: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

94 3/21/2016

11. Ninth Floor

a. 9115T, elec./IT room

i. FCU-2, open doors/box fan

b. 9201T, elec./IT room

i. FCU-1, open doors/box fan

c. 9233, cold room

i. EVR-1, ensure doors are kept closed

d. 9234, cold room

i. EVR-2, ensure doors are kept closed

e. 9256, cold room

i. EVR-3, ensure doors are kept closed

f. 9257, cold room

i. EVR-4, ensure doors are kept closed

12. Tenth Floor

a. 10115T elec./IT room

i. FCU-2, open doors/box fan

b. 10201T elec./IT room

i. FCU-1, open doors/box fan

c. 10115T elec./IT room

i. FCU-2, open doors/box fan

d. 10233 cold room

i. EVR-1, ensure doors are kept closed

e. 10234 cold room

i. EVR-2, ensure doors are kept closed

f. 10256 cold room

i. EVR-3, ensure doors are kept closed

g. 10257 cold room

i. EVR-4, ensure doors are kept closed

13. Eleventh Floor

a. 11115T elec./IT room

i. FCU-2, open doors/box fan

b. 11201T elec./IT room

i. FCU-1, open doors/box fan

c. 11234 cold room

i. EVR-1, ensure doors are kept closed

d. 11257 cold room

i. EVR-2, ensure doors are kept closed

14. Roof

a. 1105T elec./IT room

i. FCU-5, open doors/box fan

b. 12C01, corridor

i. FCU-6, open doors/box fan

c. 12301T elec. room

i. FCU-3, open doors/box fan

d. 12302 elec. room

i. FCU-1, open doors/box fan

e. 12302AE elec. room

Page 101: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

95 3/21/2016

i. FCU-2, open doors/box fan

f. 12303, storage

i. FCU-4, open doors/box fan

g. 12304 elev. room

i. FCU-7, open doors/box fan

ii. FCU-8, open doors/box fan

h. 12305, storage

i. FCU-9, open doors/box fan

i. 12306E, elec. room

i. FCU-10, open doors/box fan

15. Penthouse

a. 13301M, elec. room

i. FCU-5, open doors/box fan

ii. FCU-5A, open doors/box fan

Page 102: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

96 3/21/2016

Zone 8

1. Chilled water loss School of Pharmacy (V20)

NOTE: Depending on the outside temperatures:

Below 60 degrees:

a. Open chilled water coils, make sure circulating pumps are on to produce chilled water.

Above 60 degrees:

a. Activate EVAP. System: on AHU’s I, 2, 3, and 4 located in the penthouse V20-5000

2. In the event of chilled water loss, check the following Cold Rooms:

a. EVR V20-02-001 (Cold Room V20-2252) ensure door is kept close b. EVR-V20-03-001 (Cold Room V20-3262) ensure door is kept close

c. EVR V20-04-001 (Cold room V20-4262) ensure door is kept close

3. In the event of chilled water loss, check the following Mass SPEC Rooms, Critical equipment

a. FCU-V20-02-005, Serves mass spec room V20-2260 Utilize Move N Cool

b. FCU-V20-02-006, Serves mass spec room V20-2260 Utilize Move N Cool

c. FCU-V20-04-004, Serves mass spec room V20-4210 Utilize Move N Cool

4. In the event of chilled water loss, check the following IT rooms:

a. FCU-V20-01-001 Serves V20-1115t IT Room: Open door, circulate air with box fan, as

needed to keep room below 85 degrees.

b. FCU-V20-02-001 Serves V20-2230t IT Room: Open door, circulate air with box fan, as

needed to keep room below 85 degrees.

c. FCU-V20-03-001 Severs V20-3230t IT Room: Open door, circulate air with box fan, as

needed to keep room below 85 degrees.

d. FCU-V20-04-001 Serves V20-4230t IT Room: Open door, circulate air with box fan, as

needed to keep room below 85 degrees.

e. FCU-V20-B-006 Serves V20-0106t IT Room: Open door, circulate air with box fan, as

needed to keep room below 85 degrees.

5. In the event of chilled water loss check the following Electrical Rooms:

a. First floor: V20-1115E: Open door, circulate air with box fan, as needed to keep room

below 90 degrees.

b. Second floor: V20-2253E and 2331E: Open door, circulate air with box fan, as needed

to keep room below 90 degrees.

c. Third floor: V20-321E and V20-3005E: Open door, circulate air with box fan, as needed

to keep room below 90 degrees.

d. Fourth Floor: V204231E, and V20-4253E: Open door, circulate air with box fan, as

needed to keep room below 90 degrees.

e. Basement: V20-0102E and V20-0101E: Open door, circulate air with box fan, as

needed to keep room below 90 degrees.

6. In the event of chilled water loss check the following Cold Rooms:

a. EVR V20-02-001 (Cold Room V20-2252) ensure door is kept close

b. EVR-V20-03-001 (Cold Room V20-3262) ensure door is kept close

c. EVR V20-04-001 (Cold room V20-4262) ensure door is kept close

7. In the event of chilled water loss check the following Elevator Machine Rooms:

a. V20-P-5000A, open door circulates air with box fan

b. V20-B-0107, open door circulates air with box fan

8. Chilled water loss Health and Wellness Center (V08)

a. In the event of chilled water loss, check Freezer Room

Page 103: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

97 3/21/2016

b. FCU-V08-02-002 Room V20-2209, Utilize Move N Cool

9. In the event of chilled water loss, check Walking Cooler

a. Room V08-1204B ensure door is kept close

10. In the event of chilled water loss check the following IT Rooms

a. V08-1000T: Open door, circulate air with box fan, as needed to keep room below 85

degrees.

b. V08-210T: Open door, circulate air with box fan, as needed to keep room below 85

degrees.

c. V08-3000T: Open door, circulate air with box fan, as needed to keep room below 85

degrees.

d. V08-4000T: Open door, circulate air with box fan, as needed to keep room below 85

degrees.

e. V08-0001T: Open door, circulate air with box fan, as needed to keep room below 85

degrees.

11. In the event of chilled water loss, check the following: Electrical Rooms

a. V08-1003E: Open door, circulate air with box fan, as needed to keep room below 90

degrees.

b. V08-1103Ae: Open door, circulate air with box fan, as needed to keep room below 90

degrees.

c. V08-1103Be: Open door, circulate air with box fan, as needed to keep room below 90

degrees.

d. V08-2106E: Open door, circulate air with box fan, as needed to keep room below 90

degrees.

e. V08-3006E: Open door, circulate air with box fan, as needed to keep room below 90

degrees.

f. V08-4006E: Open door, circulate air with box fan, as needed to keep room below 90

degrees.

g. V08-5000E: Open door, circulate air with box fan, as needed to keep room below 90

degrees.

12. In the event of chilled water loss check Elevator Machine Room

a. FCU-V08-P-001 Room V08-5000E: Open door, circulate air with box fan, as needed

to keep room below 90 degrees.

SOM Checklist

1. If chilled water loss, contact Assistant Director 2. Contact CUP to notify customers (UC Hospital and Children Hospital) 3. Describe the problem and estimated time of repair 4. List the buildings that are affected

5. List the names of the people who were contacted and any other pertinent information.

6. Once the emergency has passed, all systems are restored and verified with building walk thru

7. If the SOM was notified of the incident via RAVE please send out text\email to Asst. Director,

Director and AVC to notify them of emergency and actions taken.

8. Maintain SOM log

Page 104: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

98 3/21/2016

Elevator Emergencies

Definition

Types of elevator emergencies include

1. Persons stuck in stalled elevators (entrapments)

2. Elevator doors open on any floor without the elevator in correct position or any elevator condition

or situation that could lead to injury (elevator failures)

First Responder

1. Entrapments a. Elevator phones call the UPD Dispatch. UPD will call Facilities Dispatch when they receive

an entrapment call during business hours and shift during non-business hours. In either event, the UPD starts a 30 minute call Aurora-Fire timer

b. Dispatch will send a page to Zone and call ThyssenKrupp for extraction

c. Shift’s or Zone’s primary responsibility is to establish and maintain communication with the passengers and UP. This requires going from floor to floor to find the car by yelling through the door. Once the car is located the responders must calm and assure the passengers. If the passengers are experiencing a medical emergency ask the UP to call Aurora Fire immediately

d. If unable to safely extract the passengers, call the SOM and have them call ThyssenKrupp immediately

2. Elevator Failures a. CSC Dispatch during business hours will page the Zone for a confirmation that all doors

are checked for complete closure. Upon receipt of confirmation CSC will call ThyssenKrupp for service

b. Service is provided by ThyssenKrupp Elevator Co. 303-790-8566

c. Calls during business hours are answered by the local dispatch

d. Calls during non-business hours (see SOM procedure below) are answered by the regional dispatch in Dallas, TX

e. The dispatchers need addresses (page 12) and elevator number to process the call.

SOM Checklist

SOM should be notified whenever an elevator emergency arises. SOM will call ThyssenKrupp immediately

for elevator entrapments and keep the shift crew informed about their estimated arrival time. SOM will

make the determination on all other elevator calls regarding whether ThyssenKrupp needs to be called in

or if it can wait until the following business day. If the SOM was notified of the incident via RAVE please

send out text\email to Asst. Director, Director and AVC to notify them of emergency and actions taken.

Page 105: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

99 3/21/2016

Fire Alarm Response

Definition

All fire alarms come into UCPD. UCPD then calls the Aurora Fire Department (AFD) and puts a page out

to facilities staff.

First Responder

1. After receiving a fire alarm page, respond to the fire alarm control panel location of the building in

alarm. Some buildings have a room; others have a panel in an open location in the hallway

2. If there’s one person on shift, stay at the fire alarm control panel location and let UP escort AFD to

the alarmed location. There are elevator keys in each building’s fire alarm control panel location

for the AFD to use

3. If two people are on shift, one will stay at the fire alarm control panel location and the other may

assist in escorting AFD. Remember, if it’s a true fire, AFD staff is protected and you are not

4. Do not silence or reset anything unless told to do so by AFD. Some AFD staff like to do the resetting

themselves. Some will direct you to do it. Once everything is silenced and/or cleared, make sure

the fire alarm control panel location is locked up and the elevator keys are back

5. If the system can’t be reset, see SOM section below

SOM Checklist

If shift calls with a fire alarm that can’t be reset, call one of the fire alarm technicians or the electrical

supervisor to have the particular location disabled from the fire system. When a zone is disabled, a fire

watch will have to be implemented and the fire and life safety officer shall be notified. The safety,

regulatory, and training specialist will act as the fire and life safety officer. If the SOM was notified of the

incident via RAVE please send out text\email to Asst. Director, Director and AVC to notify them of

emergency and actions taken. See UC Facilities Management Business Rules for Fire Watch Protocols

Page 106: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

100 3/21/2016

Loss of Building HVAC

Definition

Loss of building heating, ventilation, and air conditioning to certain areas may cause major damage to

equipment, loss of animals, and have a negative impact on human comfort. Critical AHUs that serve

research areas, animals, and patients must be returned to normal status as soon as possible.

First Responder

1. Check alarms in Siemens to determine which AHU is in alarm 2. May not be an air handling unit. The problem could be something as simple as a failure of a

terminal box 3. After determining the alarms physically inspect equipment 4. If the issues are dampers inspect whisker switches, actuators and linkages for damage or failure 5. Check the low pressure switch and the high pressure switch and reset if needed. If switches will

not reset check filters for loading, snow and debris also check the heating and cooling coils for the same

6. Check freeze stats, if tripped verify there are no leaks before re-setting; if the freeze trips again, check for steam and or ensure steam valves are open, operation of face & bypass to verify it is working. If using heating water check pumps, valves and heat exchangers for operation

7. If you have a fault at the VFD it will be necessary to manually reset it. Turn power off at VFD and let the VFD screen black out completely and wait a few seconds the turn power back on

8. If you have any issues where the AHU is running but you have little or no CFM you need to shut down the unit and check damper operations, check belts for slippage or broken belts

Page 107: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

101 3/21/2016

Zone 1

1. AO1 (L15)

a. L15- All Telecom rooms, floors 1 through 8 (found in Apogee)

b. L15-2nd floor server room L15-2100

c. L15-3rd floor server room L15-3213

2. Building 400 (Q09)

a. Q09- 1st Floor MRI FCU’s in corridor ceiling of 101

b. Q09- 1st Floor PET/CT FCU’s and Condensing Units- FCU’s located in room ceilings

in 114, 114a and 118. Condensing units located outside on the West side of PET/CT

building

c. Q09- 2nd Floor FCU- located in room ceiling 214

d. R09- Swamp Coolers- located outside of the building on the West end, North side

and East end

3. Building 407 (U09)

a. U09- Trane Unit- located South side of building. Resets are local to the unit.

b. U09- Dispatch AC unit- reset is in the ceiling next to the unit (regular breaker)

typically trips during power bumps

Page 108: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

102 3/21/2016

Zone 2

1. School of Dental Medicine (L26)

a. If exhaust fan EF2 on the roof fails, the occupants will need to be notified so that they

can cease hazardous operations turn off the autoclaves

b. AHU3 has evaporative cooling which can be commanded on if appropriate for cooling

purposes

2. ED II (L28 / P28)

a. No special needs on these units

3. Library (V23)

a. Units have evaporative cooling and can be commanded on if appropriate for cooling

purposes

Page 109: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

103 3/21/2016

Zone 3

1. Ben Nighthorse Campbell (M24)

a. No critical air handling units

2. Barbara Davis Center (M20)

a. MAU-1 feeds the research areas on the third floor

b. AHU-1 feeds the freezer park in the basement and the rest of the non-lab areas in the

building

c. MAU-2 feeds the animal holding room in the basement and the fourth floor research

area.

3. ED1 (P26)

a. AHU-P-3 feeds the 5th floor gross anatomy labs

4. Fulginiti Building (R27)

a. No critical air handling unit

Zone 4

1. PRF (AK-32)

2. Asset, room #, priority, usage, and emergency action

a. ph1, roof, 1, building, turn off / notify occupants

b. ph2, roof, 1, building, turn off / notify occupants

c. AHU-1, roof, 1, office air, turn off / notify occupants

d. FCU-1 130, 3, mechanical room, and move-n-cool/opening door / box fan

e. FE-R-001, roof, 1, fume hoods, turn off / notify occupants

f. FE-R-002, roof, 1, fume hoods, turn off / notify occupants

g. FE-R-003, roof, 1, fume hoods, turn off / notify occupants

h. FE-R-004, roof, 1, fume hoods, turn off / notify occupants

i. FE-R-005, roof, 1, fume hoods, turn off / notify occupants

j. FE-R-006, roof, 1, fume hoods, turn off / notify occupants

k. FE-R-007, roof, 1, fume hoods, turn off / notify occupants

l. TE-R-001, roof, 3, toilet exhaust

m. TE-R-002, roof, 3, toilet exhaust

3. Pascal Library (P-30)

4. Asset, room #, priority, usage, and emergency action

a. AHU-02-001, 201-1c-1m, 3, building air, turn off / notify occupants

b. FCU-01-001, 102, 3, processing

c. FCU-01-002, 102, 3, processing

d. FCU-01-003, 101, 3, office

e. FCU-01-004, 104, 3, reading

f. FCU-01-005, 104, 3, reading

g. FCU-01-006, 104, 3, reading

h. FCU-01-007, 104F, 3, reading

i. FCU-01-008, 104D, 3, lounge

j. FCU-01-009, 102D, 1, IT room, move-n-cool , open door / box fan

k. GE-R-001, ROOF, 3, garage exhaust

l. GE-R-002, ROOF, 3, garage exhaust

m. GE-R-003, ROOF, 3, toilet exhaust

n. GE-R-005, ROOF, 3, garage exhaust

Page 110: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

104 3/21/2016

o. GE-R-006, ROOF, 3, garage exhaust

5. Health and Safety (R-30/31)

6. Asset, room #, priority, usage, and emergency action

a. AHU-P-001, PH-200, 3, building air, turn off / notify occupants

b. AHU-P-002, PH-200, 3, building air, turn off / notify occupants

c. AHU-P-003, PH-200, 3, building air, turn off / notify occupants

d. FCU-01-001, 100DT, 1, IT room, and move-n-cool/opening door / box fan

e. FCU-P-001, PH-200M, 2, mechanical room, and move-n-cool/opening door / box fan

f. FCU-P-002, PH-200M, 2, mechanical room, and move-n-cool/opening door / box fan

g. EVR-01, 101K1A, 1, walk-in freezer, and notify tenant/keep door close

h. ROOF, DEF-01, 1, hazmat exhaust, and see 1st responder list

i. Roof, DEF-02, 1, hazmat exhaust, and see 1st responder list

j. Roof, FE-01, 1, fume exhaust, and see 1st responder list

k. Roof, TE-01, 3, toilet exhaust

l. Roof, GE-01, 1, hazmat exhaust, and see 1st responder LIST

m. Roof, GE-02, 1, hazmat exhaust, and see 1st responder list

n. Roof, GE-03, 1, hazmat exhaust, and see 1st responder list

o. Roof, GE-05, 3, general exhaust

p. Roof, GE-06, 1, hazmat exhaust, and see 1st responder list

q. Roof, GE-07, 1, hazmat exhaust, and see 1st responder list

r. Roof, GE-08, 3, general exhaust

7. Campus Services (T-36)

8. Asset, room #, priority, usage, emergency action

a. AHU-01-001, 120, 3, conference, turn off / notify occupants

b. AHU-01-002, 141F2 3, shops, turn off / notify occupants

c. AHU-01-003, 151, 3, paint shop, turn off / notify occupants

d. AHU-01-004, 130, 3, mail room, turn off / notify occupants

e. AHU-P-001, PH, 3, offices, turn off / notify occupants

f. FCU-01-001, 118T, 1, IT room, move-n-cool, open door / box fan

g. FCU-01-004, 141GT, 1, IT room, move-n-cool, open door / box fan

h. FCU-01-003, 111M, 1, elev. room, move-n-cool, open door / box fan

i. FCU-02-001, 259T, 1, IT room, move-n-cool, open door / box fan

j. FCU-03-001, 258T, 1, IT room, move-n-cool, open door / box fan

k. GE-01-001, 141D5 3, toilet exhaust

l. GE-01-002, 112, 3, toilet exhaust

m. GE-01-003, 141F2, 3, toilet exhaust

n. GE-01-004, 151J, 3, toilet exhaust

o. GE-01-005, 130, 3, toilet exhaust

p. GE-01-006, 130C, 3, toilet exhaust

q. FE-01-001, 150, 3, welding shop

r. FE-01-002, 160, 3, paint shop

s. FE-01-003, 151, 3, grounds shop

t. FE-01-004, 151, 3, grounds shop

u. FE-01-005, 117M, 3, mechanical room

v. FE-01-006, 130, 3, print shop

w. FE-01-007, 130, 3, print shop

x. GE-02-001, 220E, 3, electrical room

y. GE-03-001, 331, 3, copy room

Page 111: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

105 3/21/2016

Zone 5

1. Building 500 (Q20) has several AHU’s; each floor/wing is serves by an individual unit and may

or may not deem critical. In the event of HVAC loss to the following areas mention below are

deemed critical and requires action.

a. Freezer Room: 3rd floor C3002 serves by SA-Q20-03-004, Notify customer, Utilize

Move N Cool to keep room below 85 degrees.

b. Freezer Room: 5th floor C5002 and C5001 serves by SA-Q20-05-002, Notify customer,

Utilize Move N Cool to keep room below 85 degrees.

c. Freezer Room: 5th floor E5334 and E5335 serves by SA-Q20-05-004, Notify customer,

Utilize Move N Cool to keep room below 85 degrees.

d. Medical Refrigerators: 4th floor E4308, E4327, and E4328 serves by SA-Q20-05-005,

Notify customer, Utilize Move N Cool to keep room below 85 degrees.

e. Server Room: 4th floor W4109, W4131, and W4132 serves by FCU’s located inside

room, Notify customer, Utilize Move N Cool to keep room below 85 degrees.

f. Server Room: 5th floor W5114 and W5114B serves by Liebert located inside room,

Notify customer, Utilize Move N Cool to keep room below 85 degrees.

g. Server Room: ground floor EG330C and EG331 serves by Liebert located inside room,

Notify customer, Utilize Move N Cool to keep room below 85 degrees.

h. IT Room: 3rd floor W3162 serves by Liebert located inside room, Notify customer,

Utilize Move N Cool to keep room below 85 Degrees.

2. In the event of HVAC loss to one of the IT rooms mention below open door, circulate air with

box fan, as needed to keep room below 85 degrees.

a. W7002T , W3101T, W7001T, E6302T, W6102T, N5204T, E5300T, W5102T,

W5114B, W4109, W4131, W4132, W4101T, E4302T, C3001T, W2133T,

C3001T, W2133T, E2302T, N1202T, W1102T, E1302T, WG102T, EG302T,

R24005, CB005T, and E4302T.

Zone 6

1. RC1 (P18) North

2. Asset, room #, priority, usage, and emergency action

3. VIVARIUM

a. FCU-V-001, V-1001M, 2, mechanical room, move - n - cool, open doors/box fan

b. FCU-V-002, V-100A, 3, cage wash, turn off / notify occupants

c. FCU-V-003, V-102, 3, autoclave, turn off / notify occupants

4. INTERSTATAL

Page 112: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

106 3/21/2016

a. FCU-IN-001, IN-001M, 2, mechanical room, move - n - cool, open doors/box fan

b. FCU-IN-002, IN-001EM, 2, mechanical room, move - n - cool, open doors/box fan

c. FCU-IN-003, IN-M001T, 1, IT room, move - n – cool, open doors/box fan

d. FCU-IN-004, IN-M002T, 1, IT room, move - n – cool, open doors/box fan

5. RC1 (P-18) South

1. First floor

a. AHU-01-101, 1208E, 2, electrical room, move - n – cool, open doors/box fan

b. FCU-01-001, 1204T1, IT room, move - n – cool, open doors/box fan

2. Second floor

a. AHU-S201, 2200BM, 1, BUILDING AIR, and SEE 1ST RESPONDER LIST

b. AHU-S202, 2200BM, 1, BUILDING AIR, and SEE 1ST RESPONDER LIST

c. AHU-S203, 2200BM, 1, BUILDING AIR, and SEE 1ST RESPONDER LIST

d. AHU-S204, 2200BM, 1, BUILDING AIR, and SEE 1ST RESPONDER LIST

e. FCU-02-001, 2200AT, 1, IT ROOM

3. Fourth floor

a. FCU-04-001, 4200E1, electrical room, move - n – cool, open doors/box fan

b. FCU-04-002, 4211T1, IT room, move - n – cool, open doors/box fan

c. FCU-04-003, 4212E1, electrical room, move - n - cool, open doors/box fan

d. EVR-04-001, 4202, 1, cold room, notify tenant, and ensure doors are kept closed

e. EVR-04-002, 4214, 1, cold room, notify tenant, and ensure doors are kept closed

f. EVR-04-003, 4213, 1, cold room, notify tenant, and ensure doors are kept closed

4. Fifth floor

a. FCU-05-001, 5200E1, electrical room, move - n – cool, open doors/box fan

b. FCU-05-002, 5210T1, It room, move - n – cool, open doors/box fan

c. FCU-05-003, 5211E1, electrical room, move - n – cool, open doors/box fan

d. EVR-05-001, 5202, 1, cold room, notify tenant, and ensure doors are kept closed

e. EVR-05-002, 5212, 1, cold room, notify tenant, and ensure doors are kept closed

f. EVR-05-003, 5213, 1, cold room, notify tenant, and ensure doors are kept closed

Page 113: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

107 3/21/2016

5. Sixth floor

a. FCU-06-001, 6200E, 1, electrical room, move - n – cool, open doors/box fan

b. FCU-06-002, 6208T, 1, IT room, move - n – cool, open doors/box fan

c. FCU-06-003, 6209E, 1, electrical room, move - n – cool, open doors/box fan

6. Seventh floor

a. FCU-07-001, 7200E, 1, electrical room, move - n – cool, open doors/box fan

b. FCU-07-002, 7208T, 1, IT room, move - n – cool, open doors/box fan

c. FCU-07-003, 7209E, 1, electrical room, move - n – cool, opening doors/box fan

d. EVR-07-001, 7202, 1, cold room, notify tenant, and ensure doors are kept closed

e. EVR-07-002, 7210, 1, cold room, notify tenant, and ensure doors are kept closed

f. EVR-07-003, 7211, 1, cold room, notify tenant, and ensure doors are kept closed

7. Eighth floor

a. FCU-08-001, 8200E1, electrical room, move - n – cool, open doors/box fan

b. FCU-08-002, 8211T, 1, IT room, move - n – cool, open doors/box fan

c. FCU-08-003, 8212E, 1, electrical room, move - n – cool, open doors/box fan

d. EVR-08-001, 8201, 1, cold room, notify tenant, and ensure doors are kept closed

e. EVR-08-002, 8214, 1, cold room, notify tenant, and ensure doors are kept closed

8. Ninth floor

a. FCU-09-001, 9200E, 1, electrical room, move - n – cool, open doors/box fan

b. FCU-09-002, 9211T, 1, IT room, move - n – cool, open doors/box fan

c. FCU-09-003, 9212E, 1, electrical room, move - n – cool, open doors/box fan

d. EVR-09-001, 9201, 1, cold room, notify tenant, and ensure doors are kept closed

e. EVR-09-002, 9202, 1, cold room, notify tenant, and ensure doors are kept closed

f. EVR-09-003, 9206, 1, cold room, notify tenant, and ensure doors are kept closed

g. EVR-09-004, 9210, 1, cold room, notify tenant, and ensure doors are kept closed

h. EVR-09-005, 9213, 1, cold room, notify tenant, and ensure doors are kept closed

i. EVR-09-006, 9214, 1, cold room, notify tenant, and ensure doors are kept closed

Page 114: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

108 3/21/2016

9. Tenth floor

a. FCU-10-001, 10200E, 1, electrical room, move - n – cool, open doors/box fan

b. FCU-10-002, 10211T, 1, IT room, move - n – cool, open doors/box fan

c. FCU-10-003, 10212E, 1, electrical room, move - n – cool, open doors/box fan

d. EVR-10-001, 10201, 1, cold room, notify tenant, and ensure doors are kept closed

e. EVR-10-002, 10202, 1, cold room, notify tenant, and ensure doors are kept closed

f. EVR-10-003, 10206, 1, cold room, notify tenant, and ensure doors are kept closed

g. EVR-10-004, 10210, 1, cold room, notify tenant, and ensure doors are kept closed

h. EVR-10-005, 10213, 1, cold room, notify tenant, and ensure doors are kept closed

i. EVR-10-006, 10214, 1, cold room, notify tenant, and ensure doors are kept closed

10. Eleventh floor

a. FCU-11-001, 11200E, 1, electrical room, move - n – cool, open doors/box fan

b. FCU-11-002, 11211T, 1, IT room, move - n – cool, open doors/box fan

c. FCU-11-003, 11212E, 1, electrical room, move - n – cool, open doors/box fan

d. EVR-11-001, 11202, 1, cold room, notify tenant, and ensure doors are kept closed

e. EVR-11-002, 11214, 1, cold room, notify tenant, and ensure doors are kept closed

11. Twelfth floor

a. FCU-12-001, 12200E, 1, electrical room, move - n – cool, open doors/box fan

b. FCU-12-002, 12211T, 1, IT room, move - n – cool, open doors/box fan

c. FCU-12-003, 12212E, 1, electrical room, move - n – cool, open doors/box fan

12. Penthouse

a. SA-R-003, 1, elevator room, see 1st responder list, move - n - cool

b. FCU-P-001, 1, VFD room, move - n – cool, opening doors/box fan

c. FCU-P-002, 1, electrical room, move - n – cool, opening doors/box fan

d. FCU-P-003, 1, elevator room, move - n – cool, opening doors/box fan

13. Roof

a. FE-R-001, 3, building exhaust, see 1st responder list

b. FE-R-002, 3, building exhaust, see 1st responder list

Page 115: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

109 3/21/2016

c. FE-R-003, 3, building exhaust, see 1st responder list

d. FE-R-004, 3, building exhaust, see 1st responder list

e. FE-R-005, 3, building exhaust, see 1st responder list

f. FE-R-006, 3, toilet exhaust, see 1st responder list

g. FE-R-007, 3, glass wash exhaust, see 1st responder list

h. FE-R-008, 3, general exhaust, see 1st responder list

Page 116: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

110 3/21/2016

Zone 7

1. RC2 (P15) Interstitial Priority 1

a. Identify by room number, usage and emergency action

i. FCU-5 M300BE electrical room open doors/box fan

ii. FCU-6 M300ET electrical/IT room utilize move and cool if available, opening

doors and box fan

iii. FCU-7 M300FE IT room utilize move and cool if available open doors/box fan

2. Interstitial Priority 2

a. Identify by room number, usage and emergency action

b. FCU-2 M300D1M, elevator room, utilize move -n- cool if available, open doors/box fan

3. Interstitial Priority 3

a. Identify by room number, usage and emergency action

i. FCU-1 M300DM, mechanical room, open doors/box fan

ii. FCU-3 M300AM, vault, open doors/box fan

4. 1st Floor Priority 1

a. Identify by room number, usage and emergency action

i. FCU-1 1301T, IT room, utilize move -n- cool if available, and opening

doors/box fan

ii. FCU-5 1105T, elec./IT room, utilize move -n- cool if available, open doors/box

fan

iii. FCU-10 1108, security, utilize move -n- cool if available, open doors/box fan

iv. FCU-13 1400, freezer farm, utilize move -n- cool if available, open doors/box

fan

v. FCU-14 1400, freezer farm, utilize move -n- cool if available, open doors/box

fan

vi. FCU-15 1400, freezer farm, utilize move -n- cool if available, open doors/box

fan

vii. FCU-16 1400, freezer farm, utilize move -n- cool if available, open doors/box

fan

viii. FCU-17 1400, freezer farm, utilize move -n- cool if available, open doors/box

fan

ix. FCU-18 1400, freezer farm, utilize move -n- cool if available, open doors/box

fan

x. FCU-19 1400, freezer farm, utilize move -n- cool if available, open doors/box

fan

xi. FCU-20 1400, freezer farm, utilize move -n- cool if available, opening

doors/box fan

xii. FCU-21 1400, freezer farm, utilize move -n- cool if available, open doors/box

fan

Page 117: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

111 3/21/2016

xiii. FCU-22 1400, freezer farm, utilize move -n- cool if available, open doors/box

fan

xiv. FCU-23 1112T, server room, utilize move -n- cool if available, open doors/box

fan

5. 1st Floor Priority 2

a. Identify by room number, usage and emergency action

i. FCU-2 1309, electrical room, open doors/box fan

ii. FCU-3 1310E, electrical room, open doors/box fan

iii. FCU-4 1310AE, electrical room, open doors/box fan

iv. FCU-111099F, fire command, open doors/box fan

6. 1st Floor Priority 3

a. Identify by room number, usage and emergency action

i. FCU-6 1300M, mechanical room, open doors/box fan

ii. FCU-7 1300M, mechanical room, open doors/box fan

iii. FCU-8 1C02, corridor, open doors/box fan

iv. FCU-9 1C02, corridor, open doors/box fan

7. 2nd Floor Priority 1

a. Identify by room number, usage and emergency action

i. AHU-1, 2300M, vivarium air supply, and make sure AHU # 2 is running

ii. AHU-2, 2300M, vivarium air supply, and make sure AHU # 1 is running

iii. AHU-3, 2300M, building air supply, and building can survive with 4 AHU's

running

iv. AHU-4, 2300M, building air supply, and building can survive with 4 AHU's

running

v. AHU-5, 2300M, building air supply, and building can survive with 4 AHU's

running

vi. AHU-6, 2300M, building air supply, and building can survive with 4 AHU's

running

vii. AHU-7, 2300M, building air supply, and building can survive with 4 AHU's

running

viii. AHU-8, 2300M, building air supply, and building can survive with 4 AHU's

running

ix. AHU-9, 2300M, building air supply, and building can survive with 4 AHU's

running

x. AHU-10, 2300M, building air supply, and building can survive with 4 AHU's

running

xi. FCU-1 2300BT, IT room, utilize move -n- cool if available, open doors/box fan

xii. FCU-2 2100A, IT room, utilize move -n- cool if available, open doors/box fan

8. 3rd Floor Priority 1

a. Identify by room number, usage and emergency action

i. FCU-1 3201T, elec./IT room, utilize move -n- cool if available, open doors/box

fan

ii. FCU-2 3115T, elec./IT room, utilize move -n- cool if available, open doors/box

fan

iii. EVR-1 3233, cold room, ensure doors are kept closed

iv. EVR-2 3234, cold room, ensure doors are kept closed

9. 3rd Floor Priority 3

a. Identify by room number, usage and emergency action

i. LER, freezer storage walk area, and to ensure -80 are not in alarm

Page 118: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

112 3/21/2016

10. 4th Floor Priority 1

a. Identify by room number, usage and emergency action

i. FCU-1 4201T, elec./IT room, utilize move -n- cool if available, open doors/box

fan

ii. FCU-2 4115T, elec./IT room, utilize move -n- cool if available, open doors/box

fan

iii. EVR-1 4256, cold room, ensure doors are kept closed

iv. EVR-2 4257, cold room, ensure doors are kept closed

11. 4th Floor Priority 2

a. Identify by room number, usage and emergency action

i. LER, freezer storage walk area, and to ensure -80 are not in alarm

12. 5th Floor Priority 1

a. Identify by room number, usage and emergency action

i. FCU-1 5201T, elec./IT room, utilize move -n- cool if available, open doors/box

fan

ii. FCU-2 5115T, elec./IT room, utilize move -n- cool if available, open doors/box

fan

iii. EVR-1 5233, cold room, ensure doors are kept closed

iv. EVR-2 5234, cold room, ensure doors are kept closed

v. EVR-3 5256, cold room, ensure doors are kept closed

13. 5th Floor Priority 2

a. Identify by room number, usage and emergency action

i. LER, freezer storage walk area, and to ensure -80 are not in alarm

14. 6th Floor Priority 1

a. Identify by room number, usage and emergency action

i. FCU-1 6201T, elec./IT room, utilize move -n- cool if available, and opening

doors/box fan

ii. FCU-2 6115T, elec./IT room, utilize move -n- cool if available, open doors/box

fan

iii. EVR-1 6233, cold room, ensure doors are kept closed

iv. EVR-2 6234, cold room, ensure doors are kept closed

v. EVR-3 6256, cold room, ensure doors are kept closed

15. 6th Floor Priority 2

a. Identify by room number, usage and emergency action

i. LER, freezer storage walk area, and to ensure -80 are not in alarm

16. 7th Floor Priority 1

a. Identify by room number, usage and emergency action

i. FCU-1 7201T, elec./IT room, utilize move -n- cool if available, open doors/box

fan

ii. FCU-2 7115T, elec./IT room, utilize move -n- cool if available, open doors/box

fan

iii. EVR-1 7233, cold room, ensure doors are kept closed

iv. EVR-2 7234, cold room, ensure doors are kept closed

v. EVR-3 7256, cold room, ensure doors are kept closed

vi. EVR-4 7257, cold room, ensure doors are kept closed

Page 119: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

113 3/21/2016

17. 7th Floor Priority 2

a. Identify by room #, usage and emergency action

i. LER, freezer storage walk area, and to ensure -80 are not in alarm

18. 8th Floor Priority 1

a. Identify by room number, usage and emergency action

i. FCU-1 8201T, elec./IT room, utilize move -n- cool if available, open doors/box

fan

ii. FCU-2 8115T, elec./IT room, utilize move -n- cool if available, open doors/box

fan

iii. EVR-1 8233, cold room, ensure doors are kept closed

iv. EVR-2 8234, cold room, ensure doors are kept closed

v. EVR-3 8257, cold room, ensure doors are kept closed

19. 8th Floor Priority 2

a. Identify by room number, usage and emergency action

i. LER, freezer storage walk area, and to ensure -80 are not in alarm

20. 9th Floor Priority 1

a. Identify by room number, usage and emergency action

i. FCU-1 9201T, elec./IT room, utilize move -n- cool if available, open doors/box

fan

ii. FCU-2 9115T, elec./IT room, utilize move -n- cool if available, open doors/box

fan

iii. EVR-1 9233, cold room, ensure doors are kept closed

iv. EVR-2 9234, cold room, ensure doors are kept closed

v. EVR-3 9256, cold room, ensure doors are kept closed

vi. EVR-4 9257, cold room, ensure doors are kept closed

21. 9th Floor Priority 2

a. Identify by room number, usage, and emergency action

i. LER, freezer storage walk area, and to ensure -80 are not in alarm

22. 10th Floor Priority 1

a. Identify by room number, usage and emergency action

i. FCU-1 10201T, elec./IT room, utilize move -n- cool if available, open

doors/box fan

ii. FCU-2 10115T, elec./IT room, utilize move -n- cool if available, open

doors/box fan

iii. EVR-1 10233, cold room, ensure doors are kept closed

iv. EVR-2 10234, cold room, ensure doors are kept closed

v. EVR-3 10256, cold room, ensure doors are kept closed

vi. EVR-4 10257, cold room, ensure doors are kept closed

23. 10th Floor Priority 2

a. Identify by room number, usage and emergency action

i. LER, freezer storage walk area, and to ensure -80 are not in alarm

24. 11th Floor Priority 1

Page 120: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

114 3/21/2016

a. Identify by room number, usage and emergency action

i. FCU-1, 11201T, elec./IT room, utilize move -n- cool if available, open

doors/box fan

ii. FCU-2, 11115T, elec./IT room, utilize move -n- cool if available, open

doors/box fan

iii. EVR-1, 11234, cold room, ensure doors are kept closed

iv. EVR-2, 11257, cold room, ensure doors are kept closed

25. 11th Floor Priority 2

a. Identify by room number, usage and emergency action

i. LER, freezer storage walk area, and to ensure -80 are not in alarm

26. Roof Priority 1

a. Identify by room number, usage and emergency action

i. FCU-1, 12302E, electrical room, open doors/box fan

ii. FCU-2, 12302AE, electrical room, open doors/box fan

iii. FCU-3, 12301T, electrical room, open doors/box fan

iv. FE-1, roof lab exhaust, and building can survive with 4 FE's running

v. FE-2, roof lab exhaust, and building can survive with 4 FE's running

vi. FE-3, roof lab exhaust, and building can survive with 4 FE's running

vii. FE-4, roof lab exhaust, and building can survive with 4 FE's running

viii. FE-5, ROOF LAB EXHAUST, and BUILDING CAN SURVIVE WITH 4 FE's

RUNNING

ix. FE-6, roof lab exhaust, and building can survive with 4 FE's running

x. FE-7, roof lab exhaust, and building can survive with 4 FE's running

xi. FE-8, roof animal exhaust, and make sure FE # 9 is running

xii. FE-9, roof animal exhaust, and make sure FE # 8 is running

xiii. FE-14, roof, 11291 iodination ex., and close lab no work in lab. contact EHS

xiv. FE-15, roof bsl-3, and shut down fe-16 and sa-r-001, close lab no work in lab.

contact EHS

xv. FE-16, roof bsl-3, and shut down fe-15 and sa-r-001, close lab no work in lab.

contact EHS

Page 121: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

115 3/21/2016

xvi. SA-001, roof BSL-3, and set FE-15 and FE-16 VFD to 10 hertz, close lab

no work in lab. contact EHS

27. Roof Priority 2

a. Identify by room number, usage, and emergency action

i. FCU-5, 1105T, elec./IT room, utilize move -n- cool if available, open doors/box

fan

ii. FCU-7, 12304, elevator room, open doors/box fan

iii. FCU-8, 12304, elevator room, open doors/box fan

iv. FCU-10, 12306E, electrical room, open doors/box fan

28. Roof Priority 3

a. Identify by room number, usage and emergency action

i. FCU-4,12303, storage, open doors/box fan

ii. FCU-6, 12C01, corridor, open doors/box fan

iii. FCU-9, 12305, storage, open doors/box fan

iv. FE-10, roof ABSL-3, and not in use

v. FE-11, roof ABSL-3, and not in use

vi. FE-12, roof cage wash, and repair asap, not critical

vii. FE-13, roof cage wash, and repair asap, not critical

viii. FE-17, roof storage room, and repair asap, not critical

ix. SA-005, roof stair pressure, and not in use

x. SA-006, roof stair pressure, and not in use

29. Penthouse Priority 1

a. Identify by room number, usage and emergency action

i. FCU-5, 13301M electrical room, open doors/box fan

ii. FCU-5A, 13301M electrical room, open doors/box fan

30. AHU 02-001 and AHU 02-002 Vivarium Supply Air Units

31. AHU 02-003 through AHU 02-010 Lab Supply Air Units

Page 122: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

116 3/21/2016

Zone 8

1. Loss of HVAC Pharmacy Building V20:

a. Notify customers of Fume Hood safety, preventing use.

b. Slow down exhaust fans, to prevent extreme negative building pressures.

c. Check LER for alarming freezers, notify customers.

2. In the event of HVAC loss, check the following Cold Rooms:

a. EVR V20-02-001 (Cold Room V20-2252) ensure door is kept close

b. EVR-V20-03-001 (Cold Room V20-3262) ensure door is kept close

c. EVR V20-04-001 (Cold room V20-4262) ensure door is kept close

3. In the event of HVAC loss, check the following Mass SPEC Rooms, Critical equipment

a. FCU-V20-02-005, Serves mass spec room V20-2260 Utilize Move N Cool

b. FCU-V20-02-006, Serves mass spec room V20-2260 Utilize Move N Cool

c. FCU-V20-04-004, Serves mass spec room V20-4210 Utilize Move N Cool

4. In the event of HVAC loss, check the following IT rooms:

a. FCU-V20-01-001 Serves V20-1115t IT Room: Open door, circulate air with box fan, as

needed to keep room below 85 degrees.

b. FCU-V20-02-001 Serves V20-2230t IT Room: Open door, circulate air with box fan, as

needed to keep room below 85 degrees.

c. FCU-V20-03-001 Severs V20-3230t IT Room: Open door, circulate air with box fan, as

needed to keep room below 85 degrees.

d. FCU-V20-04-001 Serves V20-4230t IT Room: Open door, circulate air with box fan, as

needed to keep room below 85 degrees.

e. FCU-V20-B-006 Serves V20-0106t IT Room: Open door, circulate air with box fan, as

needed to keep room below 85 degrees.

5. In the event of HVAC loss, check the following Electrical Rooms:

a. First floor: V20-1115E: Open door, circulate air with box fan, as needed to keep room

below 90 degrees.

b. Second floor: V20-2253E and 2331E: Open door, circulate air with box fan, as needed

to keep room below 90 degrees.

c. Third floor: V20-321E and V20-3005E: Open door, circulate air with box fan, as needed

to keep room below 90 degrees.

d. Fourth floor: V204231E, and V20-4253E: Open door, circulate air with box fan, as

needed to keep room below 90 degrees.

e. Basement: V20-0102E and V20-0101E: Open door, circulate air with box fan, as

needed to keep room below 90 degrees.

6. In the event of HVAC loss, check the following Elevator Machine Rooms:

a. V20-P-5000A, open door circulates air with box fan

b. V20-B-0107, open door circulates air with box fan

Page 123: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

117 3/21/2016

Loss of HVAC Building Health and Wellness Center (V08)

1. In the event of HVAC loss to critical area V08-2209 (freezer Room) Notify customer, Utilize

Move N Cool to keep room below 85 degrees.

2. In the event of HVAC loss to one of the following IT Rooms check and ensure actions below are

taken.

a. V08-1000T: Open door, circulate air with box fan, as needed to keep room below 85

degrees.

b. V08-210T: Open door, circulate air with box fan, as needed to keep room below 85

degrees.

c. V08-3000T: Open door, circulate air with box fan, as needed to keep room below 85

degrees.

d. V08-4000T: Open door, circulate air with box fan, as needed to keep room below 85

degrees.

e. V08-0001T: Open door, circulate air with box fan, as needed to keep room below 85

degrees.

3. In the event of HVAC loss to one the following: Electrical Rooms ensure actions below are taken.

a. V08-1003E: Open door, circulate air with box fan, as needed to keep room below 90

degrees.

b. V08-1103Ae: Open door, circulate air with box fan, as needed to keep room below 90

degrees.

c. V08-1103Be: Open door, circulate air with box fan, as needed to keep room below 90

degrees.

d. V08-2106E: Open door, circulate air with box fan, as needed to keep room below 90

degrees.

e. V08-3006E: Open door, circulate air with box fan, as needed to keep room below 90

degrees.

f. V08-4006E: Open door, circulate air with box fan, as needed to keep room below 90

degrees.

g. V08-5000E: Open door, circulate air with box fan, as needed to keep room below 90

degrees.

4. In the event of HVAC loss to the Elevator Machine Room

a. FCU-V08-P-001 Room V08-5000E: Open door, circulate air with box fan, as needed to

keep room below 90 degrees.

SOM Checklist

1. Contact zone leads to respond

2. Major loss contact Assistant Director or Director and provide the following information

a. Problem and estimated time of repair

b. Building affected

c. Names of people contacted and other pertinent information.

3. Once the emergency has resolved and all systems are restored, verify with building walk thru

4. If the SOM was notified of the incident via RAVE please send out text\email to Asst. Director,

Director and AVC to notify them of emergency and actions taken.

5. Maintain SOM log

Page 124: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

118 3/21/2016

Natural Gas Line Leak

Definition

NOTE: It is very common to smell some gas while cooking or utilizing devices that burn natural

gas. Natural gas has an added odorant that smells like rotten eggs, in order to give early warning

of a leak. ALMOST ALL LEAKS ARE MINOR. Unless there is a broken pipe, smells are typically

not dangerous.

First Responder

Shift will be notified by University Police or the after-hour’s page from the Customer Service Center

(CSC). Shift will investigate and escalate if needed.

1. If possible, shut off the source of the gas

2. Leave the area, and ask others in the vicinity to do so

3. Open outside doors to allow for cross-ventilation

4. If there is a broken gas pipe, sound the fire alarm as you leave the building (using fire alarm

pull stations at exits)

5. Leave the building via the shortest and safest exit route. Do not use elevators; always use

stairs

6. Go to a safe area or to a pre-assigned exterior assembly location (Muster Area) for your

building

7. Call 911 (and University Police at 303-724-4444) from the nearest phone in safe area to ensure

an emergency response. Await response personnel at safe location. If you know or suspect

that someone is missing or trapped, contact the emergency personnel outside the

building. Only emergency personnel are to use the building’s P.A. system to notify occupants

8. Call SOM to inform

SOM Checklist

SOM shall call Fire and Life Safety crew to inform them of leak. SOM should also call the fluid group for

follow up repair as needed. If the SOM was notified of the incident via RAVE please send out text\email

to Asst. Director, Director and AVC to notify them of emergency and actions taken.

Page 125: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

119 3/21/2016

Storm Water/Sewer Line Break (Interior)

Definition

Common issues that may arise with interior storm and sewer systems which will require attention are backups/stoppages, or leaks. It’s more likely to have a band that has a leak or a backup due to something in the line.

First Responder

Determine the source of leak/identify which system, the approximate size of the line and describe the leak. Place a barrel underneath if possible. Call the SOM unless the leak is so small that it can be contained until the next working day.

SOM Checklist

Once the SOM is called, the fluid group should be contacted. They will come in and isolate any supply that leads to the leaking line. After isolating, repairs will be made. Depending on how much there is to clean up, contact UCPD to contact EH&S for direction. If the SOM was notified of the incident via RAVE please send out text\email to Asst. Director, Director and AVC to notify them of emergency and actions taken.

Page 126: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

120 3/21/2016

Cold Room Notification Process

First Responder

Time is critical; we need to determine if there is any temperature sensitive research that needs to be relocated. Should it not be possible to make repairs the following procedures must be followed.

First Responder will contact University Police to contact the client. 1. Check temperature on cold room display and determine if cold room is above 6 degrees or

below 2 degrees Celsius

a. Check to see if cold room has power and evaporator fans are running

b. Look and listen to determine if compressor is running. If compressor is not running push reset button next to compressor on top of cold room.

c. If compressors trips again after resetting contact SOM and inform them of what was done

Page 127: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

121 3/21/2016

d. If laboratory employees are present, inform client of status and advise them whether or not they should move the items in the cold room to another cold room location

e. If first responder cannot make direct contact with a client, University Police should be notified (303-724-4444) with the names of the people listed on the cold room call down list and cold room location. If UP cannot reach the client, then UP is to call EH&S to remove any temperature sensitive materials

f. Shift personnel post a “Cold Room Out of Service” tag on the cold room door or control panel

g. University Police will make every effort to contact the personnel responsible for the cold room. If they report back to shift personnel that no one was reached, shift personnel will contact SOM and inform them of the situation and what has been done to contact parties

h. Daily logs must be kept up to date during the process and pertinent information passed on to the next shift

SOM Checklist

1. Upon notification from shift personnel that the cold room is down and will not be operational, collect the following data

a. Bldg. and cold room number and location. b. Department affected. c. Contact information given to University Police. d. Problem and estimated time of repair (if known). e. Names of people contacted.

2. Check to make sure status information is entered in the Daily Log and that shift personnel know the current status

3. If the SOM was notified of the incident via RAVE please send out text\email to Asst. Director, Director and AVC to notify them of emergency and actions taken.

Page 128: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

122 3/21/2016

Emergency Steam Outage

First Responder

1. Any steam pipe two inches or larger (either in the distribution loop or in a building) that has a significant leak and requires isolation requires coordination with the staff at the Central Utility Plant (CUP)

2. Prior to isolation call the CUP at X41500, this will allow them to respond and prepare for the shut down so that equipment in the CUP is not damaged. Calls to the SOM are also required

3. CUP will contact (UC Hospital and Children Hospital) if affected

4. Once the system has been isolated, coordinate with the SOM and the Outage coordinator to send out notification to the occupants if normal occupant activities are affected by the shutdown, i.e. fume hood operation, environmental chambers, etc...

5. If controls need to be overridden to a manual condition to keep building systems operational, make sure to record all set points before they are changed and any equipment that is in operation to document what has been shut down. As needed, request additional resources from the SOM

6. Per the response from the CUP as to the viability of the plant systems, an assessment should be made if buildings systems should be shut down or allowed to operate to maintain building pressurization and exhaust

7. Reduction of the steam usage (refer to steam load shed document) a. The condensate pumps will not operate if there is limited steam. Plan on taking the

condensate to drain. Prior to draining the condensate call the CUP at X41500. If condensate does back-up in the systems this can cause water hammer and banging of the pipes

8. Reduce the airflow (refer to steam load shed document) 9. Increase the heat load

a. Gain additional heat by turning on all the lights b. Open interior doors to areas that may freeze

10. Returning from a steam outage a. Any steam pipe two inches or over (either in the distribution loop or in a building) that

has a significant leak and requires opening back to service requires coordination with the staff at the Central Utility Plant (CUP)

b. Prior to turning on the valve call the CUP at X41500, this will allow them to respond and prepare for the opening of the valve so that equipment in the CUP is not damaged. Calls to the SOM are also required

11. Increase the steam usage a. Slowly open the valve to warm up and pressurize the system (this may take some time

dependent on the size of the system). Once the system is up to pressure one can start to release command of the system valves on the heat exchangers and air-handlers until the system is at set point and release the valves to program control

b. If there was no steam, slowly open the valve to warm up and pressurize the system (this may take some time dependent on the size of the system). Very slowly, bring all the piping and system to set point. Failure to slowly bring up the system can result in damage to the heat exchanger and the piping system

c. Prior to returning the condensate to the CUP, call the CUP at X41500, so that they know to expect additional condensate back. Return the condensate to the CUP

d. Release all overrides 12. Increase the airflow

a. Slowly release all set point overrides to the previously recorded values b. Turn on all exhaust fans c. Make sure everything has been returned to moral

13. Return the heat load to normal a. Return the lights to normal operation b. Close any doors that have been propped open c. Double check everything is returned to normal on all systems.

Page 129: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

123 3/21/2016

-80 C Freezers

Definition

A -80 freezer is a Cascade Refrigeration System use by the research community to store specimens and samples. -20 freezers serve the same purpose but at a warmer temperature.

1. Time is Critical-During working hours every effort will be made to locate the owner of the

freezer using call down list post on freezer. After hours, contact University Police.

2. If we cannot make direct contact with a client, contact University Police (303-724-4444) with the names of people listed on freezer call down list and contact Circuit Management Supervisor who can assist in finding the owner of the freezer. If no information is posted on freezer go to the lab space directly behind freezer and collect information off three surrounding lab placards and submit to university police

3. Once contact with the client is made we must determine if there is a backup freezer available. For the most up to date spare freezer and in use list can be found at G:\common\circMang\spare units in use.docx and please use the guidelines on page 124.

Page 130: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

124 3/21/2016

4. If University Police cannot contact anyone concerning the freezer, Supervisor will contact University Police (303-724-4444) and request assistance from Environmental Health and Safety to remove any temperature sensitive research

5. Shift person will contact the SOM inform them of freezer failure and what has been done to contact parties

6. All operation information must be entered in the Daily Log. Pertinent information passed on to the next shift

SOM Checklist

1. Upon notification from shift personnel that the freezer is down and will not be operational, collect the following data

a. Bldg. and freezer number and location

b. Department affected

c. Contact information given to University Police

d. Problem (if known)

e. Names of people contacted

f. Location of emergency freezer. G:\common\circ Mang\spare units in use.docx 2. Check to make sure status information is entered in the Daily Log and that shift personal

know the current status 3. If the SOM was notified of the incident via RAVE please send out text\email to Asst. Director,

Director and AVC to notify them of emergency and actions taken.

Spare Refrigeration Equipment Usage

Please see the list below to identify the location and type of unit you may be interested in

using and then follow the instruction below to gain access.

These are the locations and type of unit:

P18 9th fl. area “C” -20 labeled UCD SPARE -20 #02 P18 9LER 26

P18 9th fl. area “B” -80 labeled UCD SPARE -80 #15 P18 9LER 21

P18 8th fl. area “C” -80 labeled UCD SPARE -80 #01 P18 8LER 10

P18 8th fl. area “B” -20 labeled UCD SPARE -20 #07 P18 8LER 21

P18 6th fl. area “A” -80 labeled UCD SPARE -80 #14 P18 6LER 09

P18 5th fl. area “D” -80 labeled UCD SPARE -80 #04 P18 5LER 26

P18 3rd fl. area “A” -80 labeled UCD SPARE -80 #12 P18 3LER 03

L18 12th fl. area “C” -20 labeled UCD SPARE -20 #01 L18 12LER 15

L18 11th fl. area “C” -80 labeled UCD SPARE -80 #13 L18 11LER 15

L18 9th fl. area “C” -80 labeled UCD SPARE -80 #02 L18 9LER 12

L18 9th fl. area “C” -20 labeled UCD SPARE -20 #08 L18 9LER 13

L18 4th fl. area “C” -80 labeled UCD SPARE -80 #07 L18 4LER 15

P15 9th fl. area “C” -80 labeled UCD SPARE -80 #05 P15 9LER 05

P15 9th fl. area “C” -20 labeled UCD SPARE -20 #05 P15 9LER 16

P15 8th fl. area “C” -20 labeled UCD SPARE -20 #04 P15 8LER 22

P15 8th fl. area “D” -80 labeled UCD SPARE -80 #10 P15 8LER 21

P15 5th fl. area “B” -20 labeled UCD SPARE -20 #06 P15 5LER 28

P15 5th fl. area “B” -80 labeled UCD SPARE -80 #03 P15 5LER 15

P15 4th fl. area “C” -80 labeled UCD SPARE -80 #15 P15 4LER 07

V20 2nd fl. area “D” -20 labeled UCD SPARE -20 #03 V20 2LER 13

V20 2nd fl. area “D” -80 labeled UCD SPARE -80 #09 V20 2LER 01

Page 131: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

125 3/21/2016

V20 4th fl. area “C” -80 labeled UCD SPARE -80 #06 V20 4LER 07

V20 4th fl. area “C” -20 labeled UCD SPARE -20 #09 V20 4LER 08

M20 3rd fl. 3202T -80 labeled UCD SPARE -80 #08 M20 3202T 04

V08 room 2209 -20 labeled UCD SPARE -20 #10 V08 2209 05

AK32 room 111 -20 labeled UCD SPARE -20 #11 AK32 111 03

AK32 room 143 -80 labeled UCD SPARE -80 #11 AK32 143 13

Each unit is identified at the upper right hand corner with a unit number and 1 contact

numbers. During normal work hours the customer service number (X41777) is listed.

Each unit will be locked with a facilities ladder key lock to prevent uncoordinated use of

the equipment.

When contacted to coordinate use of this equipment the following information must be

gathered:

Purpose of use (emergency due to equipment failure, defrost ect.).

Lab contact information (NOT A LAB EXTENTION) must be posted on the spare

unit they are using in case of an emergency. Please list at least 2.

A brief inventory of the contents and hazards must be posted on the unit they are

using.

How long does the lab anticipate the use of this equipment?

The lock will be removed during the labs use of the equipment. Please place the lock on the

unit’s power cord. If contacted for use after hours, the lab will need to be escorted to the

location of the equipment as they will not have floor to floor access. If no one from the lab

is available to transport the contents of the freezer then call the EH&S on call pager at

(303-266-3262) for assistance.

After use, Zachary Wilson (X45945) will need to be notified to GREEN TAG the

equipment so that it is ready for the next coordinated usage. Once the unit has been

GREEN TAGGED the lock will need to be replaced. If Zachary Wilson is not available,

please contact the Main EH&S number at X40345 for assistance.

Page 132: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

126 3/21/2016

Appendix 1: Continuity of operations (COOP) (Currently undergoing revision)

Appendix 2: Environmental Health and Safety Emergency Procedure/Policy:

http://www.ucdenver.edu/academics/research/AboutUs/health-safety/polices-procedures/Pages/policies-procedures.aspx

Appendix 3: Gasoline Spill and SPCC Response Procedure:

Gasoline Spill Response Procedure Revision 2

University of Colorado Denver 11/18/2015

In the event that a gasoline spill occurs, employees will implement the following procedures.

Safety is always the first priority. Gasoline is an extremely flammable liquid and vapor; increasing the risk of fire. It can kill aquatic life and wildlife if it gets in the storm sewer. Gasoline in the sanitary sewer can cause an explosion. It is an eye, skin and respiratory irritant and can cause falling hazards due to slipping.

Small Gasoline Fuel Spills of One Gallon or Less -

Step 1. Stop the spill, if it is safe to do so. Do not step in the spill. A fire extinguisher should be present prior to containment and clean-up. The Remote Yard has one gas pump. There are three fire extinguishers mounted on the exterior wall of a garage and two sheds in the Remote Yard.

Step 2. Contain the spill. Eliminate all ignition and energy sources. If the spill or leak cannot be stopped, use a pan, pail or whatever is available to catch the flow. If you are unable to prevent spilled material from entering storm drains, waterways or the sanitary sewer, follow the telephone escalation list below:

Facilities Management Department, Spill Notification Telephone Escalation List:

Customer Service Center (normal business hours) (303) 724-1777

Nancy Hostetler, Environmental Specialist (emergency after hours) (720) 641-4491

Scott Roen, Manager of Engineering (emergency after hours) (720) 252-8574

All types of spill containment material (Universal, Oil Only, Chemical or Organic) effectively absorbs gasoline. The absorbent material does not change the flammable properties of gasoline. Spill kits, goggles, face shields, gloves, caution tape and cones are in the Remote Yard (V34), at the CUP (S34), and in the Q20 Generator Building (S21). For specific spill containment material locations, see the next page. Use cones and caution tape to barricade the area. Wear personal protective equipment (chemical goggles, face shield and chemical resistant nitrile gloves). Contain the spill by putting absorbent material (spill pillows, loose absorbent, kitty litter, wood mulch, sand or dirt) around the spill to stop the flow. Then, use absorbent material to soak up the gasoline.

Step 3. Collect the contaminated absorbent. Pick up or sweep up the absorbent material using non-sparking tools (broom and rubber or plastic dustpan). Put the absorbent material in a closed container or inside tied heavy garbage bags to trap the gasoline vapors. Ensure the area is clear of any possible ignition

Page 133: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

127 3/21/2016

or energy sources. Spilled gasoline is slippery; spread fresh sand or kitty litter to reduce slipping on walkways and/or roadways.

Step 4. Immediately call Environmental Health and Safety (EH&S) to request proper storage and disposal of the waste at (303) 724-0345. If after hours, call University Police to page the on-call EH&S emergency responder.

A Gasoline Spill Greater than One Gallon Requires an Immediate Response from the Fire Department

1. Immediately call University Police to contact the Aurora Fire Department for an emergency response.

2. Tell University Police to establish an exclusion zone at the spill site. 3. Keep yourself and others upwind/uphill and away from the area. 4. Follow the telephone escalation list above. 5. Meet arriving Fire Department/HAZMAT team to provide them information.

Anschutz Medical Campus - SPILL CONTAINMENT MATERIAL LOCATIONS, TYPES, AND SUPPLIES

Locations Absorbent Type For Absorbing PPE

Face Shield Gloves

Caution Tape Traffic Cones

Remote Yard (V34) by gas pump

Oil Only Spill Kit

Diesel, repels water*. Gasoline

Yes Yes Yes Yes East side, two bay shed

Fire extinguishers mounted on the exterior wall of a garage and 2 sheds at V34.

Q20 Generator Bldg. (S21), 2nd Rm

Oil Only Spill Kit

Diesel, repels water*. Gasoline

Yes Yes Yes Yes Yes

CUP Locations 2nd fl Generator Rm

Universal Spill Kit

All fluids including water

Yes Yes Yes Yes Tool Crib & Supply Rm,

1st floor dock area

2nd fl Electrical Rm

Unknown kit type

------------- Yes Yes Yes Yes Tool Crib & Supply Rm,

1st floor dock area

1st fl Boiler Rm, South

Universal Spill Kit

All fluids including water

Yes Yes Yes Yes Tool Crib & Supply Rm,

1st floor dock area

1st fl Boiler Rm, East

Oil & Water absorbent

All fluids including water

Yes Yes Yes Tool Crib & Supply Rm,

1st floor dock area

Basement Fuel Oil Day Hallway

Oil Only Spill Kit &

Diesel, repels water*. Gasoline

Yes Yes Yes Yes Tool Crib & Supply Rm,

Page 134: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

128 3/21/2016

Oil absorbent

1st floor dock area

Basement Water Analysis Room

Universal Spill Kit

All fluids including water

Yes Yes Yes Yes Tool Crib & Supply RM, 1st floor dock area

Fuel Oil Tank Farm Storage Rm

Oil Only Spill Kit

Diesel, repels water*. Gasoline

Yes Yes Yes Yes Tool Crib & Supply Rm,

1st floor dock area

Fuel Oil Tank Farm Pump Rm

Oil absorbent

Diesel, repels water*. Gasoline

Yes Yes Yes Tool Crib & Supply Rm,

1st floor dock area

* Best to use Oil Only for diesel outside. Because Oil Only repels water, we won't pay hazardous waste disposal costs for absorbed water. All types of spill containment material effectively absorbs gasoline.

SPCC Spill Response Procedure In the event that a diesel spill occurs, employees will implement the

following procedures.

1. Safety is always the first priority. Assess and respond to imminent safety hazards first.

a) The first person to discover a spill must alert any nearby persons that a spill has occurred and

warn them away from the site. With cones and caution tape, barricade the area. If needed,

request help from University Police.

b) This employee must then immediately notify the Facilities Management Department

Environmental Compliance staff and provide initial information regarding the location, type and

approximate size of the spill. (See Spill Notification Telephone Escalation List below.)

c) If the fire risk is minimal, the Incident Commander shall direct area ignition and energy sources

be eliminated and assign retrieval of fire extinguishers to accompany a fire watch for the site

while the small spill response (less than 25 gallons) is in progress. A small spill response and

cleanup by university staff may be appropriate. For specific spill containment material

locations, see prior page.

d) The Environmental Specialist, or designated representative, shall serve as Incident

Commander and must promptly inspect the spill site and conduct an initial assessment to

determine the severity and urgency of potential hazards.

e) The Incident Commander shall promptly report spill assessment information to other Facilities

Management Department Environmental Compliance staff, as necessary to ensure a safe and

effective response.

f) The spill may be judged as a major spill event: 1) if the quantity of diesel fuel release is over 25

gallons (approximately 100 square feet), or 2) if the spill may escape the local area, or 3) if an

imminent and acute safety hazard may exist. In the event of a major spill event, an emergency

Page 135: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

129 3/21/2016

response may be initiated in consultation with the Facilities Management Department,

Environmental Health & Safety Department, and/or University Police.

g) For major spill events in which an emergency response is initiated and public authorities are

notified, the on-site manager shall undertake the following actions:

Contact University Police to establish an exclusion zone at the spill site.

If a significant fire hazard exists or the spill is 25 gallons or greater, inform University

Police to call the Aurora Fire Department for emergency response.

Facilities employees to cover or blockade nearby storm sewer inlets.

During regular business hours, notify the Environmental Health & Safety (EH&S)

Department at

(303) 724-0345. After hours, inform University Police call the EH&S emergency-on-call

pager.

Meet arriving Fire Department/HAZMAT team and provide information.

Assist in area evacuation actions, if so directed.

Facilities Management Department, Spill Notification Telephone Escalation List:

Customer Service Center (normal business hours) (303) 724-1777

Nancy Hostetler, Environmental Specialist (emergency after hours) (720) 641-4491

Scott Roen, Manager of Engineering (emergency after hours) (720) 252-8574

Appendix 4: Zone building emergency manual locations:

Zone 1:

a. BAS room in AO1… L15 1008.

b. All 400 buildings – behind basement entry doors

Zone 2:

a. L28-1306A (for both L28 & P28)

b. L26-022e

c. V23-0100M

Zone 3:

a. P26-1502Bm

b. R27-005m

c. M24-153A

d. M20-0113

Page 136: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

130 3/21/2016

Zone 4:

a. T-36-BAS room 141F

b. AK-32-130

c. P30-201C

d. R30-1S01 Zone 5:

a. Building 500 NG009

Zone 6:

a. R-1 North BAS office 2207 and R-1 South BAS office 2106 Zone 7:

a. BAS room in R2… P15 2300A.

Zone 8:

a. Health and wellness V08-0002m

b. Pharmacy: V20-0108

Appendix 5: Move-N-Cooler locations:

Zone 1: None Zone 2: None Zone 3: None Zone 4: None Zone 5:

a. Two in N3206 Zone 6: None Zone 7:

a. One in R2, 1st floor mechanical room… P15 1300M

Zone 8:

a. One Pharmacy-V20-0124

b. One Health and Wellness V08-0100E

Page 137: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

131 3/21/2016

Appendix 6: New Employee check-in procedures:

Page 138: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

132 3/21/2016

Updated: 2/1/2013

New Hire Checklist for Facilities Management

Employee Name: _____________________________ Hire Date: _________________

Job Title: ___________________________________

INITIALDATE

COMPLETE

HR

Dept

FM

Director

Interview

LeadFM Supv

FM

HR/Payroll

http://www.ucdenver.edu/faculty_staff/employees/policies/Pages/default.aspx

BEFORE HIRING DECISION IS FINALIZED

•X

• Exempt Professional Salary approved by HR Director X

• X X

•X

AFTER HIRING DECISION IS FINALIZED

X

• X

• X

Make verbal offer to candidate and schedule time to come in and complete paperwork. X

•X

• X

X

• X

X

• If applicable, submit Department Uniform Request Form (G:\Common\BOM&R\Forms\Personnel Forms) X

• X

• X

• X

Submit Background Authorization form to HR for processing. Coordinate with applicant (form completion

and submittal). This step includes driving record check.

Consent and Request for Drug/Alcohol Testing form. Direct candidate on how/where to get test completed.

RESPONSIBILITY

At close of signature meeting, direct the candidate to FM HR/Payroll for remaining forms completion.

Complete Background Check. (Release form completed during Search period)

If, based on information provided on I-9, a candidate is not a US.citizen or a permanent resident, contact

International Student and Scholar Services (ISSS) to discuss visa options.

Draft Letter of Offer (LoO) with scheduled New Employee Orientation and other training info. Submit to HR

with PDQ and Physical Requirements Assessment Sheet for approval (If Physical Requirements Assessment

wasn't already been completed at oral exam).

Obtain signatures from Appointing Authority on Letter of Offer package (include Key Request form)

Provide recommendation package to Director for review. Should include the chosen candidate's

application, the high-level scoring matrix from the interview process as compared to the other candidates,

and the questions used in the interview process.

Provide proposed salary and any specific details to Diana Taipalus for Offer Letter drafting.

Diana forwards appropriate salary information to FM HR for inclusion in Offer Letter

If applicable, request cell phone (Leslie Miller)

Provide Original of the signed Letter of Offer to FM HR/Payroll.

Exempt Professional Positions Only: Search or Search Waiver approval by Human Resources (HR Dept) and

Chancellor. PMR Helpful Tips e-mailed to [email protected]

ITEM

Hiring Process

Use current hiring process for either Classified or Non/Classified as found in the HR section of the policies website:

Meet with Candidate to obtain signature on LoO (Inform candidate to bring social security card, driver's

license and a voided check). --This step may be delegated to a Manager, but is not to be completed at a

supervisor level-- Provide copies of, or web link to, handbook, policy manuals, office procedures, University

policies, and departmental policies and procedures. Go over institutional and departmental policies and

procedures. Have employee sign statement of understanding.

Page 139: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

133 3/21/2016

X

- X

-X

- X

- X

- X

- X

- X

- Ensure that the fiscal code of ethics has been signed (if applicable) X

-X

- X

- X

• X

•X

X

• X

• Request e-mail account access X

SCHEDULE EMPLOYEE FOR REQUIRED TRAINING/IMMUNIZATIONS

- X

- X

- X

•X

- X

-X

-X

- X

- X

• X

• X

-

For Supervisors of Classified Staff (within 90 days of hire or promotion date): Overview of State Personnel

Rules

New Employee Orientation/Benefits Orientation

Preventing Sexual Harassment (noted in LoO as On-Line Training)

Personal data worksheet complete/HR liaison enters info into HRMS

Q-Fever, if employee has regular duties in the Restricted Animal Area of the PRF

Required for cell phone assignment: Responsibility Form (https://www.cu.edu/psc/cert.html)

Provide Immunization Needs to FM HR/Payroll:

Immunizations

Complete Fiscal Certification Process if Officer or if designated by Officer

Optional based on position:

Human Resources Management System (HRMS), Finance training, PeopleAdmin training, A Card

Training (training is required before access is granted)

Jobs at CU Training - https://www.cu.edu/jobs/access.html. Must complete on-line tutorial before

faxing access form to PBS.

I-9 completed/certified by department and sent to Human Resources within 3 days of hire

Emergency contact form complete/HR liaison enters info into HRMS

Social security Form 1945 complete for Classified staff with copy to personnel file (part of

classified staff offer letter)

Classified Staff PERA form

Direct deposit form complete/sent to PBS

W-4 form complete/sent to PBS

Complete ID Badge Form and submit to Appointing Authority (Division Director for approval and electronic

submission to ID Access). (G:\Common\BOM&R\Forms\Personnel Forms\Access Applications); cc: to S

Lemieux, S Segerstedt, M Whipple, N Hostetler, S Frank, A Downing, L Breyare, & L Miller)

Employee Self ID Form (submit electronically or send to HR)

Employment Verification Affirmation complete (verification of legal work status) complete

within 3 days of hire

Social security card reviewed for name match

Appropriate hiring paperwork includes:

Enter appointment into HRMS (Peoplesoft). Request handdrawn check for any retro-active pay if payroll cut-

off is missed or no system generated pay available.

Review parking option for the first day of work (ID badge not yet available)

Schedule and track immunizations taken (Nancy Hostetler coordinate scheduling w/Supervisor)

Already scheduled per dates in Offer Letter

Performance Management (noted in LoO as On-Line Training)

Enter employee in Kronos system.

Hepatitis B series (recommended), if employee is part of the Fluid Group

Page 140: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

134 3/21/2016

PREPARE THE DEPARTMENT

•X

• X

• X

• X

• X

• X

•X

X

•X

• X

• X

• X

• X

• X

• X

•X

• X

• X

• X

•X

• X

• X

•X

• X

• X

X

• X

• X

• X

If applicable, assign a locker

Describe lunch options.

Provide University smoking policy

DURING EMPLOYEE'S FIRST DAY

PREPARE THE WORK AREA

If applicable, provide cell phone and provide cell phone policy for employee's signature. Be sure employee

has completed any required training. Employee must also complete the Personal Technology Responsibility

(PT) Form located at https://www.cu.edu/psc/cert.html.

Introduce the key contact within the department who will be available to answer questions if you are not

available.

Send e-mail or post an announcement for other work groups about the new employee's arrival and include

individuals in other departments who will be working with the new employee

Update organizational chart

If applicable, order telephone service or if employee will be using an existing telephone extension re-set

password (Leslie Miller)

Talk with current team members about the new employee’s role and responsibilities

Identify at least one individual who will act as the employee's key contact within the department

Provide a campus map to the new employee

Personally welcome the new staff member when they arrive and show the employee his/her work area

If applicable, order name plate or name tag

Give a simple initial work assignment

Request Maximo access (send name, ID #, Position, Supervisor, Work Group, Pager # and Cell Phone # to

Shane Lemieux, Stephen Segerstedt and Alicia Downing)

If applicable, order business cards

If applicable, request an EZA card

Introduce co-workers/have a short welcome meeting with the department at the (weekly crew meeting)

Request keys (main door, office, desk, filing cabinets)

http://www.ucdenver.edu/about/departments/FacilitiesManagement/Documents/FM_Forms/KeyRequestForm.

pdf

Provide telephone directory and directions for telephone system

If applicable, order a computer. If a new computer is not needed, make sure current computer is functional;

all software is installed, etc.

Update Facilities Ops database with employee information

Give a tour including restrooms, kitchen, emergency exits, etc.

Provide a staff list with telephone numbers, e-mail addresses, etc., that includes a list of main contacts

Have employee sign any forms required to obtain the tools for their job.

Describe or have a list of regular meetings and other regularly scheduled items that the employee should

place on their calendar

Describe the orientation plan for the first few days

Remind team to update e-mail groups

If applicable, request Pager

Update pager lists and telephone contact lists (currently with Leslie Miller)

Page 141: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

135 3/21/2016

• X

• X

• X

X

• X

• X

WITHIN FIRST WEEK OF HIRE DATE

• X

•X

•X

• X

•X

•X

• X

• X

• X

•X

• X

• X

• X

•X

• X

• X

• X

• If applicable, have Siemens account assigned by Dave Thorson. X

• If applicable, provide OOM training sheets X

• X

• X

• X

WITHIN FIRST MONTH OF HIRE

• X

• X X

• X

- X

- X

Finalize the performance plan

Provide copy of NHDS agreement to FM HR for inclusion in employee's personnel file/reminders for increase

Facilities Management orientation.

Provide Institutional mission statement / goals

Provide Departmental mission statement / goals

Send the employee to FM IT Staff to complete Kronos activation once ID Badge has been issued.

Review ITS policies (security, proper and improper use, etc.) Review work schedule, meal periods and breaks

Review overtime with non-exempt classified staff - discuss overtime needs, approvals required, department

standards for overtime and comp time, and essential personnel application

Show employee how to access the UCD web site and on-line telephone directory

After the new employee's first week, set a regular schedule to meet

If position requires a respirator, please contact Nancy Hostetler

Review how to handle confidential information based on employee's position

Review work schedule, meal periods and breaks

Review required training for all employees and position specific training. Have employee entered into

Primedia data base

If employee is PMT I - finalize New Hire Delayed Salary (NHDS) increase agreement

Show how to send and where to receive US and campus mail and locations of US mail boxes for personal

Provide training and materials for Lock out / tag out

Provide directions on how to use telephone system, access computer, etc.

Review building and workplace security procedures, safety/accident procedures, location of first aid

supplies, how to report hazards, location of emergency assembly point, fire alarms, extinguishers, etc.

Review job description and performance expectations and explain why the job is important and how it

relates to unit and university goals/begin drafting the performance plan.Review process for requesting leave and documenting time off/policies about requesting vacation and

review process for completing work record

Review e-mail policy and sign. Have employee attend e-mail etiquette training

Review organizational charts and define department's function and interrelationships with other

departments

Review how often to check in about assignments and when and how to ask for help between trades

Review policies regarding visitors, personal phone calls, copies, faxes, etc.

Order uniforms, if applicable.

If applicable, provide long distance calling code

Allow time for employee to set up work space, voicemail, e-mail, get ID/access card and check into parking

options (check with FM HR to be sure employee info is available in Peoplesoft and viewable by ID Badge

access group before sending them to acquire badge)

Meet with the new employee at the end of the day to answer questions and find out how the day went

Show where to get or how to request supplies

Employee must take Information Privacy and Security Training in SkillPort-See Diana Taipalus if you need help

Issue Work Request to schedule specific time for training or meeting activities (BMO/Const Svcs)

Remind employee of the 30 day requirement for submitting benefit elections to Payroll and Benefit Services

Page 142: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

136 3/21/2016

• X

• Employee completes Job Hazard Assessment Questionnaire with supervisor discussion. Submit to N Hostetler X

• X

• X

•X

• X

• X

• X

• X

• X

• X

• If applicable, send to ROCIP training for project access (Risk Mgmt/Mike Barden) X

• X

Discuss access to vivariums, BSL-3 and ABSL-3 labs, R30/R31 Radioisotope storage rooms, SAB cooler and

PRF Restricted Animal Area.

Tools: list personal tools & explain access to departmental tools and shops

Go over safety / building access / PPE

Describe work flow

Go over issues related to research response to floods and disasters

If applicable, provide or sign employee up for confined space training

Meet regularly to answer questions or provide coaching

If required, start training on Siemens

Review elevator extraction policy

Provide training and materials for Lock out / tag out

Review Vehicle policy, inter-campus commutes & state driving conduct

Page 143: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

137 3/21/2016

Appendix 7: Load Shed Procedures:

Electrical Load Shedding Procedure Anschutz Medical Campus - October 1, 2013

The following is an electrical load shedding procedure that may be implemented by Facilities Management staff as necessary to maintain electrical power distribution to all or most areas on Campus while reducing our demand on Xcel Energy, our utility power provider. The procedure includes a brief description of the Electrical Distribution to the Campus from Xcel Energy, a description of the Electrical Distribution on Campus, and Load Shedding procedures to reduce our demand on Xcel Energy. Xcel Energy Distribution to the Campus:

Utility power is delivered to the Campus through 5- 13,800 volt underground feeders from 2 substations. The substations are located at 23rd and Victor (Fitz sub) and 13th and Potomac (East sub). 4 feeders originate at the Fitz sub and 1 feeder originates at the East sub. The feeders each have a number designation to identify them and they are as follows, 1510, 1513, 1515, and 1519 from the Fitz sub and 1577 from the East sub. How the feeders are connected to the Campus switchgear will be covered in the Campus distribution section. All of the feeders are 18 Mega Watt feeders. Each can carry a sustained load of 18 Mega Watts and can carry an increased load of up 22 Mega Watts for short periods during emergencies. The feeders are routed through a series of switch cabinets including the 8 switches located south of the Campus switchgear which allow power to be distributed from these feeders. All of the switches in the Xcel Distribution are controlled by Xcel Energy and are switched and maintained by Xcel. There are also other non-UC Campus loads connected to these feeders outside of the Campus. Campus Electrical Distribution System: The 5 feeders from Xcel terminate at the main Campus switchgear located south of the Central Utility Plant. The main Campus switchgear consists of 2- ATO (automatic throw over) distribution busses and 1- MTO (manual throw over) distribution buss. Each buss is connected to 2 of the 5 Xcel feeders. Each buss is a Main Tie Main configuration with a feeder connected to each end with a Tie Breaker in the center allowing each buss to be fed from either feeder entirely with one Main Breaker closed and the Tie closed (single source) or fed from both ends with both Mains closed and the Tie Breaker open (split buss). Each buss has a letter number designation and they are: S1A buss- UC Critical Loads S2A buss- All UCH buildings SB buss- CUP and all other non-critical UC Loads. The feeder buss connections are as follow: 1513- Connected to the S2A buss “B” Main Breaker. 1515- Connected to the S2A buss “A” Main Breaker and the S1A buss “A” Main Breaker. 1577- Connected to the S1A buss “B” Main Breaker. 1510- Connected to the SB buss “B” Main Breaker. 1519- Connected to the SB Buss “A” Main Breaker. The 1515 feeder is the only shared feeder and connected to more than one buss in the switchgear. Along with the 2 Main Breakers and the Tie Breaker in each buss, there are Feeder Breakers that are connected to each Main Breaker on either side of the Tie. These Feeder Breakers feed 9 distribution loops that go out through the Campus. Each loop has an “A” and “B” Feeder Breaker on opposite ends of the Buss where they are located. The distribution loops and buildings fed by each will be addressed here but not the individual switches that feed to each building. S2A Buss S2A-1 Loop- AOP, Cancer Center, and RMLEI S2A-2 Loop- AIP and CCW S2A-3 Loop- AIP Tower 2 S1A Buss S1A-1 Loop- Research 1 and Pharmacy and Pharmaceutical Sciences S1A-2 Loop- PASACAL, EH/S, Barbara Davis Center, Nighthorse Campbell, Building 500, and F610

Page 144: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

138 3/21/2016

S1A-3 Loop- Research 2, Red Cross, Henderson Structure, 400 Series, Parking Lot and Street Lighting, and Health and Wellness. SB Buss SB-1 Loop- Spare SB-2 Loop- Education 2 North and South, AO1, Leprino, UCH Staff Structure, UCH Visitors Structure, School of Dental Medicine, Campus Services Building, and Parking Lot and Street Lighting. SB-3 Loop- Education 1, Library, Parking Lot and Street Lighting. SB-4 Loop- Central Utility Plant Load Shedding Guidelines and Procedures: Load shedding will have to more than likely occur from an issue with Xcel Energy’s ability to provide power to the Campus in one way or another. Xcel could possibly need load reduced or dropped completely from one or more Campus feeders or the Campus could experience reduced capacity from all Xcel feeders and the need for load shedding across the Campus. If an individual feeder is in need of load reduction, the load can simply be moved over to the other feeder for the buss with the impacted feeder. This can be done manually with all three busses by moving the open in the loops to the end of the loops fed from the feeder that needs load reduction or opening the buss main breaker that is fed from the feeder needing reduction and closing the tie breaker in the buss. In the event that load reduction across the Campus must occur to lessen the load on Xcel and cannot be accomplished by moving loads from one feeder to another, Loads will be reduced by placing load on Stand-By Generators. Most all buildings are equipped with a genset and a significant amount of load can be placed on generator while maintaining normal utility power to the buildings. If this reduction is not sufficient for Xcel, normal utility loads will have to be shut down on a prioritized basis leaving generator backed emergency loads being the only loads powered until the issue can be resolved. Extensive documentation must occur of all actions taken during this procedure to insure nothing is missed and also allow for a comprehensive transition back to normal conditions. It is assumed that in this situation the NIMS model will be utilized and a contact person established to gather all load shed information from the field and compile into one document for reference during the event. The following is a representation of the total utility load on each Buss and the reduction that can be achieved by placing as much load on generator as possible. 2A Buss Total Load Load that can be placed on Generator 8.047 Megawatt 4.132 Megawatt 1A Buss total Load Load that can be placed on Generator 10.057 Megawatt 4.053 Megawatt B Buss Total Load Load that can be placed on Generator 12.966 Megawatt 1.053 Megawatt Total Campus Substation Load Total Generator Load 31.07 Megawatt 9.238 Megawatt Significant load reduction can occur for the 1A and 2A busses with generator power reducing those loads on Xcel by 40 - 50%. The load on the B Buss can be reduced slightly but not a lot can be gained due to the fact that the CUP chilled water production is on the B Buss with no Generator back up. Significant load could be reduced in this area with the implementation of the Chilled Water Load Shedding plan which will be discussed separately from this plan. By placing all the loads on Generator we can get a 29.7% total load reduction on the utility supply. If Xcel needs more of a reduction than this will offer building utility loads will need to be shut down. The following is a prioritization of how those loads will be shut down. 1st loads to be shut down- Education and Teaching space 2nd loads to be shut down- Administrative space

Page 145: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

139 3/21/2016

3rd loads to be shut down- Research space 4th loads to be shut down- Clinical space 5th loads to be shut down- Animal Care space 6th loads to be shut down- Patient Care space As space is shut down, the load on the CUP chilled water production will drop which will drop the electrical loads on the B Buss as well as the loads on the 1A and 2A busses. Loading will depend on Xcel’s ability to supply power during an event and loads will have to be monitored during the entire time load shedding is taking place. It should be noted that if this plan is implemented it will take extensive involvement of the Electrical Group and the Outage Coordinator with direction from the Executive leadership. It should also be noted that provisions for fuel delivery must be put in place immediately upon the start of this procedure and depending on what the expected duration of the load shedding will be. All of the Generators have varying fuel supply amounts and durations of run time on each fuel source. With current loading it will require 10,190 gallon of fuel per 24 hr. period and it should be assumed that we will need fuel delivered daily. Fuel tank levels should be monitored every 2-3 hours during run time and consumption tracked to determine when individual units will require refueling. If units are running close to being out of fuel before refueling can occur, these units should be shut down and left off until refueling can occur. They must not be allowed to run out of fuel as this will cause serious issues with the fuel systems on the units and require vendor support to get the units back on line due to air in the fuel system. A staffing plan should be set up at the beginning of this procedure depending on duration to allow 24 hr. monitoring of the generator systems and electrical loads.

Appendix 8: Anschutz Medical Campus Chilled Water Load Shedding:

Anschutz Medical Campus - Chilled water load shedding procedure 2/12/2015

In the event that the chilled water system partial failure or failure at the CUP the following are the steps for

load shedding until the CUP is at stable chilled water production:

1. Start Building 500 Chillers – Turn on the point “CH-Q20-G-PM-ENA”.

2. Close all of the AHU chilled water valves for the following buildings and monitor the economizer

sections:

a. Campus Services – (1)

b. Library – (1)

c. Health and Wellness – (1)

d. Fulginiti (1, except for forum AHU)

e. Academic Office

f. Education II

g. Nighthorse Campbell

h. Pascal

i. EH&S

j. Education 1 (1, only for gross anatomy AHU) (Cadavers may need to be returned to the

freezer)

Note 1 - (AHUs have evaporative cooling)

3. Shutdown the primary chilled water system for the following building to stop the process cooling for

telecomm/electrical rooms and other areas:

a. Campus Services

b. Library (May require Move-N-Cool for historic collection in room V23-3102)

c. Health and Wellness (May require Move-N-Cool for Freezers in room V08-2209)

d. Fulginiti

Page 146: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

140 3/21/2016

e. Academic Office

f. Education II

g. Nighthorse Campbell

h. Pascal

i. EH&S

j. Education 1

4. Shutdown the cooling for telecom/electrical rooms in the following areas:

a. Research 1

b. School of Pharmacy

c. Barbara Davis (excluding freezer farm in room M20-0117)

d. Research II (excluding freezer farm in room P15-1400)

e. School of Dentistry

5. Request hospitals start available emergency chillers

1. UCH – Cancer Center

2. UCH – Inpatient Tower 1

3. TCH – Data Center in Gary Pavilion

TCH point of contact = Joe Hart 303 870-7414

UCH point of contact = Mike Martins 80246/ John Morrow 88989

6. Close all of the AHU chilled water valves for the following buildings and monitor the discharge air

temperatures:

a. Research 1 – South tower only (1)

b. School of Pharmacy (1)

c. Barbara Davis (2)

d. Research II (1) (2)

e. Research 1 – North tower only (1, except for tower AHUs) (2) (May require Move-N-Cools for

Pathology Storage (P18-1400A1)

f. School of Dentistry

Note 1 - (AHUs have evaporative cooling)

Note 2 – (Vivarium AHUs may require chilled water due to humidity conditions)

7. Shutdown the primary chilled water system for the following building to stop the process cooling for

environmental rooms and freezer farms:

a. School of Dentistry

b. Barbara Davis

c. School of Pharmacy

d. Research II

e. Research 1

8. Request that hospitals start their chilled water load shedding sequence:

TCH point of contact = Joe Hart 303 870-7414

UCH point of contact = Mike Martins 80246/ John Morrow 88989

Page 147: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

141 3/21/2016

Appendix 9: OOM procedures and sign off sheets: (Currently undergoing revision)

Page 148: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

142 3/21/2016

Appendix 10: Trauma cleanup procedures: (Currently undergoing revision)

Page 149: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

143 3/21/2016

Appendix 11: RAVE Communication:

Registering to receive RAVE texts:

1. Go to the portal log-in page at https://portal.prod.cu.edu/UCDAccessFedAuthLogin.html.

2. Enter your regular network username and password. This will open the welcome page.

3. Click on the ‘My Info and Pay’ tab, next go down to ‘Employee profile’ tab and click on it. Then

under phone numbers update or ensure the cellular number on there is the one that you want to

receive the RAVE information on. You also will receive a verification call when changing any of

the numbers.

4. Once you’ve updated your existing numbers and added any new numbers, don’t forget to click the

“Save” button on the screen. If your changes were successful, you’ll get a confirmation message

“The Save was successful”.

5. Click on ‘OK’ and you’re all done! You can exit the page normally.

Page 150: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

144 3/21/2016

Supervisor of the Month paging instructions:

Instructions for sending Rave Alerts to your department personnel

Log into Rave at: https://www.getrave.com/login/denveralerts

Use your CU Denver Email address as your username. Click the “Forgot your Password” link, if needed.

1. Click the “Admin” button at the top of the page after you log in to your account.

2. Click the green “Create Alert” button.

Page 151: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

145 3/21/2016

3. Enter an Alert Name in this field. The yellow circled #1 will turn green, as seen in next slide.

4. Click on the yellow

and white “Text” box here. This will open the screen shown on the next slide.

Page 152: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

146 3/21/2016

5. Enter an appropriate text message for the alert. The yellow circled #2 will turn green, as seen in next slide.

* Note that most text messages are limited to 140 characters.

6. Click on the gray

“Mail” box here (in order to enter email verbiage). This will open the screen shown on the next slide.

Page 153: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

147 3/21/2016

7. Enter an appropriate email message for the alert here (as shown on the next slide).

Once text has been

entered into the Text

and Mail sections, both

boxes will turn

green.

8. Next, click the yellow

“Add” button in order to choose who will receive the alert.

Page 154: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

148 3/21/2016

Once you have clicked the yellow “Add” button, you can choose your Delivery Targets.

You can choose lists AND/OR Choose individuals

Once you have chosen (clicked on) a list(s) or individual people, they will be highlighted in blue and transferred to the Targeted Recipients box.

9. Click Save.

Once your Delivery Tar-

gets have been chosen,

the #3 circle will turn

green.

The “Continue” button

will also turn green to

allow you to send the

alert.

10. Click the green Con-

tinue button to pre-

view the alert

(before sending).

Page 155: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

149 3/21/2016

This final screen (please review carefully!) will show you:

To how many recipients the alert will be sent

The text message verbiage

The email message verbiage

11. Click the “Send this Alert!” button to send the alert.

You have successfully sent an alert to all of the Targeted Recipients (individuals and/or

lists)! The alert will be sent to cell phones and CU Denver email addresses of each person.

Page 156: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

150 3/21/2016

Appendix 12: Employee phone list: Please use the link below to see the latest employee phone list; \\paradise2\operations\Dispatch\Employee Phone List Appendix 13: Company Contact numbers:

Name Phone Address

Air Systems Inc 303-761-5020 2991 S. Tejon, Englewood Co, 80110

Batteries Plus 303-745-3333 994 S. Abiliene, Aurora CO, 80012

Belfor Environmental Inc. (SCPP) 303-425-7526 5075 Kalamath, Denver CO, 80221

Belfor Property Restoration 303-425-9700 5085 Kalamath St., Denver Co, 80221

BLIND SHINE 303-373-9934 5150 Havana Unit C, Denver Co, 80239

Blue Prints- Copies- Scanning 303-755-8984 8400 E. Iliff Ave Unit 12, Denver CO, 80231

Bob's Electric Motor Service 303-744-3297 1221 South Bannock Street, Denver CO, 80223-3201

Carrier Building Services 303-796-0799 12742 E Caley Ave Ste 2-A, Centennial Co, 80111

CG CONSTRUCTION, INC. (SCPP) 303-421-6434 2775 W. Hampden Ave. Suite 100, Englewood Colorado, 80110

City Lighting Products 303-868-1287 7104 S. Dillon Ct., Englewood CO, 80112

Colorado Doorways 303-291-0900 3333 E 52nd Ave, DENVER CO, 80216

Colorado Electric & Power Systems (SCPP)

303-298-9191 5454 N. Washington Unit 3, Denver CO, 80216

Colorado Piping & Mechanical, Inc. 303-777-7151 525 East Mississippi Ave, Denver CO, 80210

COLORADO TIRE & SE 303-340-1420 1541 Chambers Rd, Aurora CO, 80011

Component Specialties INC 303 341-0160 3202 Nome St, Aurora Co, 80010

Construction Concepts, Inc. (SCPP) 970-535-0600 14125 Mead St., Longmont CO, 80504

Custom Environmental Services, Inc. (SCPP)

303-423-9949 8041 W. I70 Frontage Road Unit #11, Arvada CO., 80002

Denver Valve & Fitting 303-232-8844 9500 W. 49th Ave unit D103, Wheat Ridge Co, 80033

Electrical Distribution 303-825-5011 1661 W. 3rd Avenue, Denver CO, 80223

Electronic Components 877-884-4653 421 West 104 Ave, Northglenn CO, 80234

Electro-Steam 866-617-0764 50 Indel Ave, Rancocas NJ, 08075-0438

Empire Gas & Electric Equipment Co 303-623-7747 1635 W. 13th Ave, Denver Co, 80204-2403

Energy West 303-279-4800 14828 W. 6th Ave 11B, Golden Co, 80401

Excel Environmental Inc. (SCPP) 303-577-9933 1852 Jasper St, Unit E, Aurora CO., 80011

Fastenal Co 303-340-8435 12001 E. 33rd Ave., ,

Fire extinguishers and fire system services

303-534-0661 11411 E. 51 st Ave, Denver CO, 80239

Flow Solutions 1-800-848-1141

720 Geiger Court, Colorado Springs Co, 80916

Page 157: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

151 3/21/2016

Getinge 1-800-950-9912

1777 East Henrietta Road; POB 92640, Rochester New York, 14692-0640

Gilmore Construction Corp. (SCPP) 303-371-5700 4949 Ironton St., Denver CO., 80239

Golden Way Mechanical HVAC 303-935-0520 6333 S Santa Fe Dr. Ste C, Littleton CO, 80120

Golf Cart Company 888-476-4747 5345 Newport St, Commerce City CO, 80022

Grainger Supply 719-598-9500 95 S. Tejon St., Denver Colorado, 80223

Guirys Inc. 303-292-0444 2245 Market St, Denver CO,

H2O filters 303-233-7400 1315 nelson Unit H, Lakewood CO, 80215

Hercules Industries 303-937-1000 1310 W Evans Ave., Denver Co, 80223

Hospital Shared Services Security Systems

303-603-3000 900 S. Broadway, Denver CO, 80209

Howell Construction (SCPP) 303-825-6257 550 Lipan Street, Denver CO, 80204

Hughes Supply Inc 303-534-4293 275 Kalamath St, Denver Co, 0223

Hydraulics 303-333-7442 6800 Stapleton Dr., Denver CO, 80216

JCOR Mechanical, Inc. 303-271-9787 15800 West 5th Ave, Golden CO, 80401

Jim Black Construction 303 452-8710 12279 Pennsylvania St., Thornton CO, 80241

Johnstone Supply 303-573-5626 2701 West 7th Avenue, Denver CO, 80204-4114

Ken Caryl Glass 303-791-3122 12450 Mead Way, Littleton CO, 80125

Kennerly Construction Corp. (SCPP) 303-742-7989 2390 S. Kalamath St., Unit F, Denver CO, 80223

Kimmel Mechanical, Inc. 303-322-8144 4975 Paris Street, Denver CO, 80239

Koch Filter Corp. 303-627-4027 625 W. Hill St, Louisville KY, 40208

KWAL 303-367-0057 1701 Chambers rd # A, Aurora Co, 80011

L.M. Nelson 303-980-8217 468 S Dudley, Lakewood Co, 80226

Long Building Systems 303-975-2119 5001 S. Zuni, Littleton Co., 80120

Louis and Company 888-422-5852 4691 Havana Street, Denver Co, 80238

LUTEK 303-650-6000 5135 W. 58th ave., Arvada Co, 80002

Mac Bestos, Inc. 303-534-2757 1235 Delaware Street, Denver CO., 80204

Magnum Materials of Colorado 303-576-9588 3855 Sable Blvd, Aurora Co, 80011

Mark Young Construction, Inc. (SCPP) 303-776-1449 7200 Miller Place, Frederick CO, 80504

McGee Company 303-777-2615 1140 S Jason St, Denver Co, 80223

Miser Asbestos Removal Inc 303-922-8821 2991 S. Tejon St., Englewood CO, 80110

Motion Industries 318-687-2110 P.O. Box 1655, Birmingham AL, 35201

Mountain States Engineering and Controls

303-548-7603 1520 Iris Street, Lakewood CO, 80215

MW Golden Constructors (SCPP) 303-688-9848 P.O. Box 338, Castle Rock CO, 80104

Nalco Chemical Co 303-369-0138 3033 S Parker Rd, Aurora Co, 80014

Omega Engineering, Inc 203-359-1660 One Omega Drive, Stamford CT, 06907-0047

Parker Hannifin Corporation 805-604-3409 2340 Eastman Ave, Oxnard CA, 93030

Paxton Wood Source 303-399-6810 4837 Jackson, Denver Co, 80216

Red Man Pipe and Supply 303-343-1899 16401 E 33rd Drive #10-A, Aurora Co,

Page 158: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

152 3/21/2016

Rhinotrax Construction (SCPP) 303-682-9906 4161 Mulligan Street, Longmont CO, 80504

RYALL ELECTRIC 303-629-7721 2627 WEST 6TH AVENUE, DENVER CO, 80204

SERVPRO Office > Account Manager - Thomas Gibson >

303-494-2000 720-879-7387

697 S Pierce Ave. Louisville, CO 80027

Sharpening service 303-789-3855 4769 S Broadway, Englewood CO`, 80113

SHERWIN WILLIAMS 303-237-5412 15390 E. Alameda pkwy, Aurora Co, 80017

Sid Harvey Industries, Inc. 303-623-1236 2700 West 6th Avenue, Denver CO, 80204-4107

Siemens Building Technologies Inc. 303-279-8500 7810 Schaffer Parkway, Littleton Co, 80127

SPYCOR Building Products 877-293-0784 , ,

Steris Corporation 303-814-9014 5960 Heisley Rd, Mentor OH, 44060

Strait Lumber Company 303-366-3561 4780 York St, Denver Co, 80216

Sturgeon Electric Company (SCPP) 303-286-8000 12150 East 112th Ave, Henderson CO, 80640

Thyssenkrupp Elevator Company 303-790-8566 7367 S Revere Pkwy, Unit 2-A, Centennial, CO 80112 CO, 80112

ThyssenKrupp onsite technician - Dan Edwards

303-434-6416

Tower Electric, Inc. (SCPP) 303-690-0235 621 Southpark Drive Suite 1500, Littleton CO, 80120

Trane Co 303-228-3300 445 Bryant St., Denver Co, 80204

US Engineering 303-901-3499 729 S.E. 8th Street - P.O. Box 905, Loveland CO, 80537

Water systems 800-748-1837 41801 N. union Blvd, Colorado Springs CO, 80909

Werther International 800-972-4668 8614 Veterans Memorial Drive, Houston TX, 77088

Westco Systems, Inc 303-427-4800 7396 Lowell Blvd., Westminster CO, 80030

WHITE CAP CONST 303-534-0661 70 Santa Fe Dr, Denver Co, 80223

Page 159: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

153 3/21/2016

Appendix 14: Emergency Contact numbers for Bioscience 2 Building:

Emergency Contacts

The numbers listed below are to be used in the event of an after-hours building-related emergency. Brian Young is the first responder; if you are unable to reach him, please proceed down the list. Note: If you need access to the building after business hours, a service fee may be billed to your company. Brian Young: Office (720) 859-4113

Cell (303) 667-2393 Keith Yoshida: Cell (303) 801-7535 Vicki Jenings: Cell (303) 526-6300 For emergencies during office hours (Monday – Friday, 7:30 am to 5:00 pm), call: Front Desk/Main Operator 720-859-4100 Brian Young 720-859-4113 Vicki Jenings 720-859-4108 Brittany Joyce 720-859-4109 University Police Emergency Number – 303-724-4444

2. Building Services & Policies 2.1 Building Access & Security Building Access: The building doors unlock at 7:30 AM and lock at 5:30 PM Monday through Friday. If you need to access the building outside these hours or on holidays, you must have a Badge. Badges are issued by University Security to individuals (not a company) so that security reports adequately track who enters the building. If a card reader is not working or if there are other access issues, call 720-724-0014. Suite/Lab Access: Each Suite and Lab is accessed through Badges provided by University Security. Keys to interior doors will be available through the FRA. Keys are required to be returned to the FRA whenever companies experience a staffing change. To effectively maintain company records and building security, the FRA tenant database and security system must be updated with current key holder information. Keys can be re-issued to a new key holder at no charge to the tenant, or returned.

Page 160: Facility Management – Facility Operations Business Rules ... · service charges associated should be forwarded to Customer Service Center to correct. Time labor entries will be

154 3/21/2016

To request keys, contact [email protected] or [email protected]. To request badges, use the following contact info:

University tenants: contact University Security at: [email protected] Non-university tenants: contact [email protected]

Only authorized personnel may request keys and badges. Please provide the name of authorized personnel on the Company Information Sheet attached to this handbook. Emergency Access: If you are in the building after hours, it is recommended that you carry your Badge on your person to avoid being locked out of your premises or the building. In the event you accidentally lock yourself out of your office or the building, access cannot be granted remotely. You may call University Security at 303-724-4444 to arrange access.