Upload
others
View
3
Download
0
Embed Size (px)
Citation preview
Faculty of Electrical Engineering
University of Ljubljana
Distribution and industrial networks
Laboratory for lighting and photometry
Seminar paper
Earth resistance and calculation of earthing
Author: Supervisor:
Amar Bičo prof. dr. Grega Bizjak
Ljubljana, March, 2019.
Contents 1. INTRODUCTION .................................................................................................................................................7
2. EARTH RESISTANCE........................................................................................................................................8
2.1. Earthing materials ................................................................................................................................... 10
2.1.1. Conductors .............................................................................................................................................. 10
2.1.2. Earth electrode ..................................................................................................................................... 10
2.2. Measurements of soil resistivity ..................................................................................................... 10
2.2.1. Wenner method.................................................................................................................................... 11
2.2.2. Sclumberger method.......................................................................................................................... 12
2.3. Types of ground electrodes ................................................................................................................ 13
2.3.1. Driven rod ............................................................................................................................................... 13
2.3.2. Grounding plates.................................................................................................................................. 14
2.3.3. Grounding strip .................................................................................................................................... 15
2.3.4. Mesh grounding.................................................................................................................................... 16
2.3.5. Semi spherical grounding electrode ........................................................................................... 17
2.3.6. Foundation earth electrodes .......................................................................................................... 17
2.3.7. Buried ring .............................................................................................................................................. 18
2.4. Measuring earth resistance on a existing earth electrode ............................................. 19
2.4.1. Earth resistance measurements on installations with a single earth electrode ... 20
2.4.2. 3-pole measurement method (62 % method) ....................................................................... 20
2.4.3. The triangle measurement method ............................................................................................ 21
2.4.4. 4-pole earth resistance measurements method ................................................................... 22
2.4.5. The variant 62 % method (one stake, only on TT or impedant systems) ................ 23
2.4.6. Selective 4-pole earth resistance measurement................................................................... 24
3. Addition ................................................................................................................................................................... 25
3.1. Questions .......................................................................................................................................................... 25
3.2. Example............................................................................................................................................................. 26
List of figures Figure 1. Soil resistivity in function of moisture. ..........................................................................................9
Figure 2. Wenner method...................................................................................................................................... 11
Figure 3. Sclumberger method. .......................................................................................................................... 12
Figure 4. Driven rod. ................................................................................................................................................ 13
Figure 5. Grounding plate. .................................................................................................................................... 14
Figure 6. Grounding strip. .................................................................................................................................... 15
Figure 7. Grounding with mesh. ........................................................................................................................ 16
Figure 8. Semi spherical electrode. ................................................................................................................... 17
Figure 9. Foundation earth electrode. ............................................................................................................. 18
Figure 10. Buried ring around house. ............................................................................................................. 19
Figure 11. Measurements with single earth electrode. ............................................................................ 20
Figure 12. 3-pole measurement method. ........................................................................................................ 21
Figure 13. Triangle measurement method. ................................................................................................... 22
Figure 14. 4-pole measurement method. ........................................................................................................ 22
Figure 15. The variatn 62% method (one stake). ...................................................................................... 23
Figure 16. Selective 4-pole earth resistance measurement. ................................................................... 24
1. INTRODUCTION
Nothing is quite so common or abundantly available throughout the world as the earth’s soil. We
are more apt to think of earth as something to be tilled for planting or to be excavated for a building
foundation. Yet, it also has an electrical property - conductivity (or low resistance) - that is put to
practical use every day in industrial plants and utilities.
Broadly speaking, “earth resistance” is the resistance of soil to the passage of electric current.
Actually, the earth is a relatively poor conductor of electricity compared to normal conductors like
copper wire. But, if the area of a path for current is large enough, resistance can be quite low and
the earth can be a good conductor. It is the earth’s abundance and availability that make it an
indispensable component of a properly functioning electrical system.
2. EARTH RESISTANCE
The resistance offered by the earth electrode to the flow of current into the ground is known as the
earth resistance or resistance to earth. The earth resistance mainly implies the resistance between
the electrode and the point of zero potential. Numerically, it is equal to the ratio of the potential of
the earth electrode to the current dissipated by it.
The resistance of the earthing electrode is not concentrated at one point, but it is distributed over
the soil around the electrode. Mathematically, the earth resistance is given as the ratio of the
voltage and the current shown below at (1) and (2):
𝐸𝐴𝑅𝑇𝐻 𝑅𝐸𝑆𝐼𝑆𝑇𝐴𝑁𝐶𝐸 =𝑃𝑜𝑡𝑒𝑛𝑡𝑖𝑎𝑙 𝑡𝑜 𝑒𝑎𝑟𝑡ℎ 𝑒𝑙𝑒𝑐𝑡𝑟𝑜𝑑𝑒
𝐶𝑢𝑟𝑟𝑒𝑛𝑡
(1)
𝑅𝐸𝑎𝑟𝑡ℎ(𝛺) =𝑉 (𝑉)
𝐼 (𝐴)
(2)
For correct design and construction of a grounding system it is necessary to know the properties
of soil on which is a protected substation or device.
The value of earth resistance for different power stations is shown below in Table 1:
Table 1. Value of earth resistance for different power station.
Large Power Station 0,5 (𝛺)
Major Power Station 1,0 (𝛺)
Small Substation 2,0 (𝛺)
The region around the earth in which the electrode is driven is known as the resistance area or
potential area of the ground. The fault current which is injected from the earth electrode is passing
away from the electrode in all directions shown below in the figure. The flow of current into the
grounds depends on the resistivity of the soil in which the earth electrode is placed. The resistivity
of the soil may vary from 1 to 1000 𝛺𝑚 depends on the nature of the soil. Specific soil resistivity
𝜌 is in function of geological properties of soil (moisture, chemical composition of soil). The
specific soil resistivity in function of moisture is shown below on Figure 1.
Figure 1. Soil resistivity in function of moisture.
Conduct of soil is changing for months, if temperature drops below the 0°C there is a chance of
freezing. In that case when the soil is frozen then the soil resistance will increasing. If we go deeper
with ground electrode in earth the changes of soil resistivity are less. Problem is there because the
soil is not uniform in all direction. Soil resistivity for different ground type is given below in Table
2:
Table 2. Typical ground resistivity values.
Ground type Resistivity (𝜴𝒎)
Loams, garden soils, etc. 5-50
Clays 10-100
Chalk 30-100
Clay, sand and gravel mixture 40-250
Marsh, peat 150-300
Sand 250-500
Slates and shales 300-3000
Rock 1000-10 000
Soil resistivity (ρ) is expressed in Ohm metres (Ω.m). This corresponds to the theoretical resistance
in Ohms of a cylinder of earth with a cross-section area of 1 m2 and a length of 1 m. By measuring
it, you can find out how well the soil conducts electric currents. So the lower the resistivity, the
lower the earth electrode resistance required at that location. Resistivity varies significantly
according to the region and the type of soil because it depends on the level of humidity and the
temperature (frost or drought increase it). This is why earth resistance may vary according to the
season or the measurement conditions. As temperature and humidity levels become more stable
the further you go from the ground surface, the deeper the earthing system, the less sensitive it is
to environmental variations. It is advisable to bury your earth electrode as deep as possible.
2.1. Earthing materials
2.1.1. Conductors
The conductors used must be capable of carrying the anticipated fault current and cope with
corrosion over the lifetime of the installation. Bare copper is normally used for a substation
earthing grid, being buried at depths between 0.6 and 1.0 m in rectangles of between 3 and 7 m
side length. Equipment connections are generally laid at a shallower depth of about 0.2 m. Because
of mechanical and thermal criteria, it is unusual for copper of less than 70mm2 to be used.
Aluminium is often used for above ground connections and could be used below ground if it is
certain that the soil will not cause corrosion problems, but most standards prohibit this. Some
protection, such as painting with bitumastic paint, is recommended in the area where the conductor
emerges from the ground, as corrosion may occur here and just below. Where not connected
directly to the electrode, all metallic substation plant is bonded via above ground conductors.
2.1.2. Earth electrode
The earth grid’s horizontal electrodes may be supplemented by vertical rods to assist the
dissipation of earth fault current, further reduce the overall substation earthing resistance and
provide some stability against seasonal changes. This is especially useful for small area substation
sites (such as GIS substations) or where the rod is of sufficient length to enter the water table. Rods
may be of solid copper or copper clad steel and are usually of 1.2 m length with screw threads and
joints for connecting together in order to obtain the required length for installation in the soil. The
formula for the effective resistance, 𝑅𝑟𝑜𝑑𝑠(𝛺) of a single earth rod is shown below (3):
𝑅𝑟𝑜𝑑𝑠 =𝜌
2𝜋𝑙· [ln (
8𝑙
𝑑) − 1]
(3)
Where is:
𝑅𝑟𝑜𝑑𝑠 – vertical earthing rod effective resistance (𝛺)
𝜌 – resistivity of soil (𝛺𝑚)
𝑙 – length of earthing rods (𝑚)
𝑑 −diameter of earthing rods (𝑚)
2.2. Measurements of soil resistivity
Because soil quality may vary greatly with depth and over a wide lateral area, estimation of soil
resistivity based on soil classification provide only a rough approximation. Actual resistivity
measurements are required to fully qualify the resistivity and its effects on the overall transmission
system.
2.2.1. Wenner method
This method known as Wenner four-pin method, developed by Dr. Frank Wenner. On these
methods used four electrodes, two for current injection and two for voltage measurement. The
four electrodes embedded to the ground in straight line, the two outer electrodes are current
electrode and two inner electrodes to measure voltage drop due to resistance of soil path when
current passed between the outer electrodes. The arrangement of Wenner method is shown on
Figure 2.
Figure 2. Wenner method.
The Wenner four-pin method, as shown in figure above, is the most commonly used
technique for soil resistivity measurements. Using the Wenner method, the apparent soil
resistivity value is:
𝜌 =4 · 𝜋 · 𝑎 · 𝑅𝑤
1 +2 · 𝑎
√𝑎2 + 4 · 𝑏2−
𝑎
√𝑎2 + 𝑏2
(4)
Where is:
𝜌 = measured apparent soil resistivity (𝛺𝑚)
𝑎 = electrode spacing (𝑚)
𝑏 = depth of the electrodes (𝑚)
𝑅𝑤 = Wenner resistance measures as (“𝑉
𝐼”) in figure 2, if b is small compared to a, the
previous equation can be reduced to (5):
𝜌 = 2 · 𝜋 · 𝑎 · 𝑅𝑤 (5)
2.2.2. Sclumberger method
In the Schlumberger method the distance between the voltages probe is a and the distances
from voltages probe and currents probe are c (Figure 3.), that’s the difference between this
method and Wanner method.
Figure 3. Sclumberger method.
Using the Schlumberger method, if b is small compered to a and c, and c>2a, the apparent
soil resistivity value is (6):
𝜌 =𝜋 · 𝑐 · (𝑐 + 𝑎)
𝑎· 𝑅𝑠
(6)
Where is:
𝜌 = measured apparent soil resistance (𝛺𝑚)
𝑎 = electrode spacing (𝑚)
𝑏 = depth of the electrodes (𝑚)
𝑐 = electrode spacing (𝑚)
𝑅𝑠 = Schlumberger resistance measures as (“𝑉
𝐼”), (𝛺)
2.3. Types of ground electrodes
2.3.1. Driven rod
This is by far the most common grounding device used in the field today. Driven rods
are vertically buried into the ground, their length is form 1 up to 3 meters. The top of
the driven rods must be buried under the surface of earth as much how soil is freezing
because the temperature has big impact on earth resistance. Driven rods also have a very small surface area, which is not always conducive to good contact with the soil.
This is especially true in rocky soils, in which the rod will only make contact on the
edges of the surrounding rock.
Figure 4. Driven rod.
The resistance of driven rod we can calculate using formula (7):
𝑅𝑑𝑟 =𝜌
2𝜋𝑙[𝑙𝑛
2𝑙
𝑑+
1
2ln (
4𝑡 + 1
4𝑡 − 1)]
(7)
Where is:
𝑅𝑑𝑟 = earth resistance of driven rod (Ω)
𝑙 = length of driven rod (𝑚)
𝑑 = diameter of driven rod (𝑚)
𝜌 = soil resistance (Ω𝑚)
𝑡 = depth from surface to middle driven rod (𝑚)
2.3.2. Grounding plates
Grounding plates are typically thin copper plates buried in direct contact with the earth
(Figure 5).
Figure 5. Grounding plate.
Grounding plate are buried vertically into the ground to achieve better contact with the soil,
because soil can be frizzed grounding plates are buried into the soil on depth of 0,5 m. The
earth resistance of grounding plates we can calculate using (8):
𝑅 =𝜌
4√
𝜋
𝐴
(8)
Where is:
𝑅 = earth resistance of ground plate (Ω)
𝐴 = surface of grounding plate (𝑚2)
𝜌 = soil resistance (Ω𝑚)
In case that we using more then one grounding plate, it is recommending that the space
between grounding plates are 3 m, in that case the earth resistance we can calculate using
(9):
𝑅𝑡 = 0.23 ·𝜌
𝑎 · 𝑛· 𝑘 · µ
(9)
Where is:
𝑅𝑡 = total earth resistance of grounding plates (Ω)
𝑎 = page length of grounding plate (𝑚)
𝑘 = correction factor (depth of soil)
𝜌 = soil resistance (Ω𝑚)
𝑛 = number of grounding plates
µ = coefficient of interaction between the grounding plates
2.3.3. Grounding strip
The grounding strips are horizontally buried into the ground in depth of 0,5 m up to 1 m,
the strip is shown on Figure 6:
Figure 6. Grounding strip.
The resistance of grounding strip with condition that is length of strip is much longer then
the depth on which is buried grounding strip (L >> h) is shown below (10):
𝑅 =𝐾 · 𝜌
2 · 𝜋 · 𝑙ln (
𝐿2
𝑑 · ℎ)
(10)
Where is:
𝑅 = earth resistance of grounding strip (Ω)
𝐿 = length of grounding strip (𝑚)
𝑑 = diameter of grounding strip (𝑚)
𝜌 = soil resistance (Ω𝑚)
ℎ = depth of grounding strip (𝑚)
𝐾 = correction factor (1 – 1,5)
In case that is non circular it is necessary to calculate the value of diameter using formula
(11):
𝑑 = √4 · 𝐴
𝜋
(11)
𝐴 = cross section area of grounding strip (𝑚2)
2.3.4. Mesh grounding
Mesh type of grounding is most commonly using for protection of transformer stations with high voltage with directly grounded neutral point (Figure 7).
Figure 7. Grounding with mesh.
Simplified formula for calculation earth resistance in this case (12):
𝑅 =0,55 · 𝜌
√𝐴
(12)
A = area of mesh (𝑚2); 𝜌 = soil resistivity (Ω𝑚)
2.3.5. Semi spherical grounding electrode
Semi spherical type of grounding electrode is rarely used (Figure 8), but we can use
them for describing foundation earth electrodes like most commonly used type of
grounding electrode.
Figure 8. Semi spherical electrode.
The resistance for semi spherical grounding electrode is (13):
𝑅 =𝜌
2 · 𝜋 · 𝑟0 (13)
2.3.6. Foundation earth electrodes
With a foundation earth electrode, a functioning and maintenance-free earth-termination
system is installed throughout the building’s lifecycle. Foundation earth electrodes are
embedded in the concrete foundation and covered by a concrete layer of at least 5 cm.
Consequently, two requirements are fulfilled:
The concrete conserves the earthing material, corrosion effects are not to be expected
The typically moist concrete on the outside of the foundation establishes a
conductive connection between the systems mentioned above and the ground
Figure 9. Foundation earth electrode.
Earth resistance of foundation earth electrode is (14):
𝑅 =𝜌
𝜋 · 𝑑 (14)
Where is:
𝜌 = soil resistivity (Ω𝑚), diameter d we can calculate 𝑑 = 1,57 · √𝑉3
, here V is volume of foundation (𝑚3).
2.3.7. Buried ring
This solution is strongly recommended, particularly in the case of a new building.
The electrode should be buried around the perimeter of the excavation made for the foundations.
It is important that the bare conductor be in intimate contact with the soil (and not placed in the
gravel or aggregate hard-core, often forming a base for concrete). At least four (widely-spaced)
vertically arranged conductors from the electrode should be provided for the installation
connections and, where possible, any reinforcing rods in concrete work should be connected to the
electrode. The conductor forming the earth electrode, particularly when it is laid in an excavation
for foundations, must be in the earth, at least 50 cm below the hard-core or aggregate base for the
concrete foundation. Neither the electrode nor the vertical rising conductors to the ground floor,
should ever be in contact with the foundation concrete.
Figure 10. Buried ring around house.
The approximate resistance R of the electrode (15):
𝑅 =2 · 𝜌
𝐿
(15)
Where is:
L = length of conductors (𝑚)
𝜌 = resistivity of soil (Ω𝑚)
2.4. Measuring earth resistance on a existing earth electrode
The soil resistivity measurement methods presented so far can only be used when installing a new
earth electrode: they can be used to check the resistance value in advance and adjust the electrode
according to the earth value required. For existing earth electrodes, the method involves checking
that they comply with the safety standards in terms of their construction and resistance value.
Various measurement methods may be used, however, depending on the installation's
characteristics: whether it is possible to cut off the installation's power supply or disconnect the
earth electrode, whether the electrode to be tested is the only one or is connected to others, what
level of measurement accuracy is required, where the installation is located (urban or rural
environment).
The region around the earth in which the electrode is driven is known as the resistance area or
potential area of the ground. The fault current which is injected from the earth electrode is passing
away from the electrode in all directions. The flow of current into the grounds depends on the
resistivity of the soil in which the earth electrode is placed. The resistivity of the soil may vary
from 1 to 1000 𝛺𝑚 depends on the nature of the soil. Specific soil resistivity 𝜌 is in function of
geological properties of soil (moisture, chemical composition of soil). Characteristic values of
earth resistance are: 0.5𝛺 (Larger station), 1,0𝛺 (Major station), 2,0𝛺 (Small station).
2.4.1. Earth resistance measurements on installations with a single earth electrode
It is important to point out that the earth resistance measurement of reference is the 2-stake method.
This method is referenced in all the electrical installation testing standards and can be used to
measure the earth resistance both accurately and safely. The measurement principle involves using
an appropriate generator G to inject an alternating current (i) through the auxiliary electrode H and
back through the earth electrode E.
The voltage V between the earth electrode E and the point in the earth where the potential is zero
is measured using another auxiliary electrode S. The resistance can then be calculated by dividing
the voltage measured by the constant current injected (i), thus (16):
𝑅𝐸 =𝑈𝐸𝑆
𝐼𝐸𝐻
(16)
Figure 11. Measurements with single earth electrode.
2.4.2. 3-pole measurement method (62 % method)
This method requires the use of two auxiliary electrodes (or "stakes") to inject the current and to
provide the 0 V potential reference. The positioning of the two auxiliary electrodes in relation to
the earth electrode to be measured E(X) is crucial.
For correct measurement, the "0 V potential auxiliary electrode" must not be set up in the zones of
influence of the earths E & H caused by the current (i) flowing.
Statistics from the field have shown that the best method for ensuring high measurement accuracy
is to place stake S at a position 62 % of the distance from E on the straight line EH. You then need
to make sure that the measurement does not vary or only varies slightly when stake S is moved by
± 10 % (S’ and S”) on either side of its initial position on the line EH. If the measurement does
vary, it means that (S) is in an influence zone, so you must increase the distances and then repeat
the measurements.
Figure 12. 3-pole measurement method.
2.4.3. The triangle measurement method
This method requires two auxiliary electrodes (stakes). It is used when the method described above
(Figure 11) is not suitable (alignment not possible or obstacle preventing a sufficient distance from
H).
It involves:
Setting up the stakes S and H so that the earth electrode E and the stakes S and H form an
equilateral triangle
First measuring with S on one side and then measuring with S on the other side.
If the values found differ significantly, it means stake S is in a zone of influence. You must then
increase the distances and repeat the measurements. If the values obtained are within a few percent
of one another, the measurement can be considered valid. The results of this method may be
uncertain, however, because even when the values found are similar, the zones of influence may
overlap. To make sure, repeat the measurements after increasing the distances.
Figure 13. Triangle measurement method.
2.4.4. 4-pole earth resistance measurements method
The 4-pole earth resistance measurement method is based on the same principle as 3-pole
measurement, but with an additional connection between the earth to be measured E and the
measurement instrument. This method offers better resolution (10 times better than the 3-pole
method) and means that the resistance of the measurement leads no longer needs to be taken into
account. This function is ideal for measuring very low earth resistance values, so it is particularly
prized by power transmission and distribution companies who need to measure earth resistance
values of just a few Ohms.
Figure 14. 4-pole measurement method.
The advantage of 3-pole and 4-pole earth resistance measurements is that they can be performed
on an installation with the power off, so the earth can be tested even if the house or building
involved has not yet been connected to the power distribution network or has been disconnected
from it.
For these two types of measurement, you are advised to open the earth bar in order to isolate the
earth electrode to be measured, thus making sure that the earth resistance measured really is the
resistance of the earth electrode. Otherwise, there may be a de facto bond between the earthing
installation and an earth electrode due, for example, to the metal ducts of a water or gas distribution
network. Earth resistance measurements with the bar closed will then be incorrect due to the
presence of this de facto earth electrode. This may lead to an excessively high earth resistance
value later on (if a metal duct is replaced with an insulating material, for example). Consequently,
unless you are sure that there is no de facto earth electrode, you must open the earth bar for any
earth resistance measurements. To detect any de facto earth electrodes, it may be useful to measure
the earth electrodes with the bar open and with the bar closed so that you can check whether the
"closed-bar" value is due to the installed earth electrode or to de facto
earth electrodes.
2.4.5. The variant 62 % method (one stake, only on TT or impedant systems)
This method does not require disconnection of the earth bar and only one auxiliary stake (S) is
necessary. With this method, the earthing system of the distribution transformer acts as the H stake
and the PE conductor accessible on the protective conductor (or earth bar) acts as the E stake.
Figure 15. The variatn 62% method (one stake).
The measurement principle is the same as for the normal 62 % method. The S stake will be
positioned so that the distance S-E is equal to 62 % of the total distance (distance between E and
H). As a result, S will normally be located in the neutral "0 V reference earth" zone. The earth
resistance is calculated by dividing the measured voltage by the current injected.
Differences compared with the normal 62 % method:
The power supply for measurement comes from the mains instead of from batteries.
A single auxiliary stake is required (stake S) so the measurement can be set up more
quickly.
It is not necessary to disconnect the building’s earth bar. This also saves time and makes
sure that safety is maintained on the installation during measurement.
2.4.6. Selective 4-pole earth resistance measurement
When a classic 3-pole or 4-pole measurement method is used on a system with parallel earthing,
the measurement current injected into the system is divided between the different earths. This
means it is impossible to determine the amount of current in a given earth electrode, so its
resistance cannot be determined either. In such cases, it is the total current flowing in the earthing
system which is measured, giving the overall earth resistance equivalent to the resistances of all
the earth electrodes set up in parallel.
To neutralize the influence of the parallel earth electrodes, there is a selective variant of the 4-pole
measurement method. The principle is the same except that a current clamp is added to measure
the exact current flowing in the earth to be measured, so that its precise value can be determined.
Due to the use of auxiliary stakes and more particularly the 0 V reference with the S stake, this
method ensures accurate measurement of the earth resistance.
Figure 16. Selective 4-pole earth resistance measurement.
3. Addition
3.1. Questions
1.) What is earth resistance and values for different types of power station ?
The resistance offered by the earth electrode to the flow of current into the ground is known as the
earth resistance or resistance to earth. The earth resistance mainly implies the resistance between
the electrode and the point of zero potential. Numerically, it is equal to the ratio of the potential of
the earth electrode to the current dissipated by it. For correct design and construction of a
grounding system it is necessary to know the properties of soil on which is a protected substation
or device.
2.) Describe earth resistance measurements on installations with a single earth electrode?
It is important to point out that the earth resistance measurement of reference is the 2-stake method.
This method is referenced in all the electrical installation testing standards and can be used to
measure the earth resistance both accurately and safely.
The measurement principle involves using an appropriate generator G to inject an alternating
current (i) through the auxiliary electrode H and back through the earth electrode E.
The voltage V between the earth electrode E and the point in the earth where the potential is zero
is measured using another auxiliary electrode S.
3.) Describe the Wenner method for measuring soil resistivity ?
This method known as Wenner four-pin method, developed by Dr. Frank Wenner. On these
methods used four electrodes, two for current injection and two for voltage measurement. The
four electrodes embedded to the ground in straight line, the two outer electrodes are current
electrode and two inner electrodes to measure voltage drop due to resistance of soil path when
current passed between the outer electrodes.
3.2. Example
Calculate earth resistance for grounding electrodes:
- Length of rod: l = 4,5 m
- Specific earth resistance 𝜌 = 250 Ωm
- Diameter d = 25,4 mm
- n (number of rods)
a) Configuration 1:
𝑅 =𝜌
2𝜋𝑙𝑙𝑛
4𝑙
𝑑=
250
2 · 𝜋 · 4,5𝑙𝑛
4 · 4,5
25,5 · 10−3= 58,03 (Ω)
b) Configuration 2: two rods with space between of 2m
𝑅 =𝜌
2𝜋𝑙𝑙𝑛
4𝑙
𝐴
𝐴 = 2 [𝑑
2· 𝑘𝑛−1]
1𝑛
= 0,7407
𝑅 = 22,9 (Ω)
c) Configuration 3: four rods with space between of 2m
𝑅 =𝜌
2𝜋𝑙𝑙𝑛
4𝑙
𝐴
𝐴 = 2 [𝑑
2· 𝑘𝑛−1]
1𝑛
= 1,129
𝑅 = 24,48 (Ω)