FAIRA TRANSPARENCY REPORTS
808 Woodland Way, Kent, WA 98030
April 4th, 2017 Thank you for your interest in this Faira Certified home. We have coordinated the efforts of certified and licensed inspection and title professionals to create the Faira Transparency Reports for this home. The Faira Transparency Reports are a detailed portfolio of information that is prepared on behalf of buyers in preparation for making an informed offer on the property.
You may view more detailed information for this home and can make an offer at
http://www.faira.com/listings/10939 All of the information in the Faira Transparency Reports was gathered and compiled without any bias or influence from the seller(s). In fact, these reports are materially identical had you as the buyer(s) ordered the same professionals to perform the evaluations on the same date. Nevertheless, Faira takes no obligation of the reports being complete or accurate. The buyers are recommended to conduct their own due-diligence to their satisfaction. Please contact us if you have any questions or would like more information. We’re happy you’ve chosen a Faira Certified home and look forward to the opportunity of working with you! The Faira Team
RW West Consultants IncProperty Inspection Report
Cover Page
808 Woodland Way, Kent, WA 98030Inspection prepared for: Christopher Ellis
Real Estate Agent: -
Date of Inspection: 4/7/2017 Time: 1:30 PM Age of Home: 1965 Size: 2500
Order ID: 1686
Inspector: Robert PickeringLicense 1807
Email: [email protected]
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 1 of 74
General Exterior Note 1. Exterior NoteObservations:• North Elevation• South Elevation• East Elevation• West Elevation
||2||West Elevation ||2||South Elevation
||2||North Elevation ||2||East Elevation
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 2 of 74
Exterior Areas 1. Siding ConditionSiding appeared in good condition overall. • Wood siding.Observations:• Paint flaking at the siding, recommend loose paint is removed, barewood areas primed andrepainted.• Vent is not flush with siding and does not have flashing to resist water penetration. Recommendconditions are corrected to prevent moisture from entering.• Decay to base if trim, recommend conditions are repaired• Cracked siding, recommend caulking or repair
West near garage West near entry
Northwest corner North
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 3 of 74
South garage entry South
South
East side Siding cracked near chimney
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 4 of 74
2. GuttersGutters and downspouts appeared in good condition overall.Observations:• Recommend installing splashblocks or extensions to divert water minimum 3 feet away from thefoundation. Extensions longer than 3 feet may be required if grade slopes toward the house whereslpash blocks or extension end.
Southeast3. Driveway and Walkway ConditionConcrete sidewalks appeared in good condition overall.Observations:• Uneven surfaces at sidewalks or, driveways/patios are potential tripping hazards, recommendconditions are corrected.
Temporary decking4. SoffitSoffits and eaves appeared in good condition overall.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 5 of 74
5. Door/WindowExterior doors appeared in operable condition, at time of inspection.Observations:• There was no visible flashing above the window. Windows and or doors without flashing requireperiodic maintenance of caulking material.
Flashing east side6. GradingGrading appeared in good condition overall.Observations:• Grade Slopes towards the house from South to north.
||1||Grade Slopes towards the house from South to north.7. ElectricalObservations:• Exterior covers missing/damaged, recommend conditions are repaired as a safety precaution• No power to outlet, recommend further investigation and correction.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 6 of 74
East side8. Cable FeedsMaterials: Primary Service is Overhead Service Drop
9. Gas ConditionMeter located at North side. Main Gas shutoff is located to the lower left of the meter.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 7 of 74
10. Exterior Faucet ConditionExterior faucets were in operable condition overall.Observations:• Loose handle recommend securing
11. Pressure75
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 8 of 74
12. Retaining WallRockery retaining wall.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 9 of 74
Decks 1. Deck1East • Upper
2. DeckDecking and Visible framing appeared in good condition overall. • Guardrail appeared secure. •Handrail appeared secure.Observations:• Handrail not graspable. By today's standards, rails should be configured so that a hand maygrasp around a rail for safety.• Lag bolt sizing should be a minimum 5/8th inch diameter, recommend further investigation andcorrection• Recommend resealing some areas of the deck to extend deck life.• Previous deck was a cantilever type deck and joists were cut back and new header attached toprior deck joists. Type of connection of new header to old joists not visible an could not be verified.
Handrail Handrail
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 10 of 74
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 11 of 74
Roof 1. Roof ConditionArchitectural Composition shingle. • Walked on roof surface.Type Average life span 30 years for this type surface with proper maintenance and care.
Southwest Southeast
West upper East upper
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 12 of 74
Ridge north to south2. Flashing
3. SkylightsSkylights appeared sealed, no visible indications of leakage.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 13 of 74
4. Spark Arrestor
5. Vent Caps
6. ChimneyObservations:• Moss on chimney recommend alleviating to prevent spalling• Recommend re pointing in some areas voids in masonry can lead to spauling of the chimney,recommend resealing.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 14 of 74
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 15 of 74
Attic 1 1. AtticAttic access is located in the hallway
2. FramingVisible framing appeared in good condition overall, no visible indications of decay or waterpenetration presently.
North South
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 16 of 74
East West3. Ventilation
South West4. Fan/DuctBathroom fans appeared to exhaust to the exterior overall. • Kitchen fan appeared to exhaust tothe exterior overall.Observations:• Bathroom fans do not exhaust completely to the exterior, recommend correction. This conditioncan result in mold/fungal growth.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 17 of 74
5. Insulation ConditionBlown in fiberglass insulation noted.Depth: Insulation averages about 12-14 inches in depth, estimated R value 38
6. RodentNo visible indications of Rodent Activity.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 18 of 74
Attic 2 1. AtticGarage is location of access.
2. FramingVisible framing appeared in good condition overall, no visible indications of decay or waterpenetration presently.
South East
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 19 of 74
West North3. VentilationVentilation appeared adequate overall.
4. Insulation ConditionObservations:• No insulation present. Area attic was over garage.
5. RodentNo visible indications of Rodent Activity.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 20 of 74
General Interior Note 1. General NotesMaterials: Windows in the home are Double panel insulated glass windows. Any deficiencies arenoted in each room section for accessible windows • Doors in the home are considered operationalunless otherwise noted in each room section • Cabinet doors and in the home are consideredoperational unless otherwise noted in each room section
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 21 of 74
Entryway 1. ConditionsCeiling and walls are in good condition overall. Light fixture operates. Entry door operates andlocks overall. • Tile floor is in good condition.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 22 of 74
Living Room 1. LocationLocation 1st Right • Southwest
2. Living RoomWalls and ceilings appear in good condition overall. Flooring is carpet. Heat register present.Accessible outlets operate. • Light fixture operates.Observations:• Cracking at the ceiling and or walls does not appear unusual.
West to right of window
Ceiling entering the dining room.3. Window-Wall AC or Heat
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 23 of 74
4. FloorObservations:• Carpet Wrinkled, recommend restretching.
5. FireplaceFireplace was wood burning type.Observations:• Tiles on the hearth are cracked.• Creosote buildup in the fireplace, recommend cleaning by licensed chimney sweep before using.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 24 of 74
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 25 of 74
Dining Room 1. LocationLocation Southeast
2. Dining RoomWalls and ceilings appear in good condition overall. Flooring is carpet. Heat register present.Accessible outlets operate. • Light fixture operates. • Ceiling fan operates.Observations:• Cosmetic cracked trim near patio door
3. Window-Wall AC or Heat
4. Ceiling FanMaterials: Ceiling Fan was in operable condition overall
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 26 of 74
Kitchen 1. Kitchen RoomWalls and ceilings appear in good condition overall. Flooring is Tile. Heat register present.Accessible outlets operate. Light fixture operates. Sink and faucets are in operable conditionoverall. Cabinet doors and drawers are in operable condition overall.Cabinet doors and drawers are in operable condition overall.
2. Counter ConditionStile Stone counter tops are in good condition.
3. CabinetCabinet doors and drawers are in operable condition overall.
4. DisposalDisposal operates overall.
5. DishwasherDishwasher was in operable condition.
6. MicrowaveObservations:• Built-in microwave ovens are tested using normal operating controls. Unit was tested andappeared to be serviceable at time of inspection. Leak and/or efficiency testing is beyond the scopeof this inspection. If concerned, client should seek further review by qualified technician prior toclosing.
7. Stove/OvenStove/oven were in operable condition overall.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 27 of 74
8. RefrigeratorRefrigerator was in operable condition.
9. SinksSinks are in operable condition overall.
10. ElectricalOutlets are GFCI protected at the counters.
11. Vent ConditionVent fan appears to exhaust to the exterior, part of microwave.
12. HeatingHeat register operates.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 28 of 74
Laundry 1. ConditionCeiling and walls are in good condition overall. Accessible outlets operate.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 29 of 74
Stairs Leading to 2nd Floor 1. StairSteps appeared uniform. • Handrail appeared secure.Observations:• Guardrail balusters are spaced further than newer required 4 inches. 4 inch requirement is sosmall children cannot fit through the guardrail.• Handrail present is less than 36 inches tall, recommend correction as a safety precaution.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 30 of 74
Upstairs Hallway 1. ConditionsCeiling and walls are in good condition overall. Light fixture operates.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 31 of 74
Master Bedroom 1. BedroomWalls and ceilings appear in good condition overall. Flooring is wood in good condition overall.Heat register present. Accessible outlets operate.
2. FloorObservations:• Water damage to flooring.• Wood stained.
3. DoorsObservations:• Entry door sticks, recommend adjustment.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 32 of 74
4. HeatingHeat register operates.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 33 of 74
Master Bathroom 1. RoomCeiling and walls are in good condition overall. Accessible outlets operate. Light fixture operates. •Windows are thermal pane, appeared sealed overall • Entry door is in operable condition overall. •There were no visible indications of plumbing deficiencies overall.
2. ElectricalObservations:• GFCI protected receptacles may not have been required when the house was built. Recommendupgrading with GFCI's at all receptacles near water sources as a safety precaution
3. CountersFormica counter tops are in good condition overall.
4. CabinetsCabinet doors are in operable condition overall.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 34 of 74
5. SinksSinks are in operable condition overall.Observations:• Corroded trap. Monitor for developing leaks (none found during inspection).
6. Exhaust FansVent fan operates overall.
7. FloorsLinoleum Flooring is in good condition overall.
8. ShowerShower door is in operable condition overall.Observations:• Voids in the grout between some of the tile, recommend resealing.• Faucet handle are difficult to operate. Recommend repair by a qualified contractor.• Voids in the caulking/grout where shower walls rest on pan.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 35 of 74
9. ToiletToilet was in operable condition overall.
10. HeatingHeat register operates.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 36 of 74
Hall Bathroom1 1. LocationMaterials: 1st Floor
2. RoomCeiling and walls are in good condition overall. Accessible outlets operate. Light fixture operates.
3. ElectricalObservations:• GFCI protected receptacles may not have been required when the house was built. Recommendupgrading with GFCI's at all receptacles near water sources as a safety precaution
4. CountersFormica counter tops are in good condition overall.
5. CabinetsCabinet doors and drawers are in operable condition overall.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 37 of 74
6. Exhaust FansVent fan operates overall.Observations:• Fan Starts slow, recommend cleaning.
7. FloorsLinoleum Flooring is in good condition overall.
Bubble in linoleum8. TubTub was in good condition overall.
9. ShowerShower is in good condition overall.
10. SinksSinks are in operable condition overall.Observations:• Stopper is missing• Stains from presumed past leaks noted.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 38 of 74
11. ToiletToilet was in operable condition overall.Observations:• Moisture meter indicated abnormal moisture content at the floor base of toilet. This is typicallyindication of defective wax seal, recommend conditions are investigated further and corrected bylicensed plumbing contractor.
Right Normal
Left12. HeatingHeat register operates.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 39 of 74
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 40 of 74
Bedroom 1 1. LocationLocation Northwest
2. Bedroom RoomWalls and ceilings appear in good condition overall. Flooring is wood. Heat register present.Accessible outlets operate. • Light fixture operates.
3. FloorObservations:• Wood floor finish faded/worn
4. HeatingHeat register operates.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 41 of 74
Bedroom 2 1. LocationLocation West • 1st Left
2. Bedroom RoomWalls and ceilings appear in good condition overall. Flooring is wood. Heat register present.Accessible outlets operate. • Light fixture operates.
3. ElectricalObservations:• Open low voltage wiring observed in closet, recommend securing and capping.
Right in closet4. FloorObservations:• Wood floor finish faded/worn
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 42 of 74
5. HeatingHeat register operates.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 43 of 74
Bonus Room 1. LocationLocation North • Basement
2. Bonus RoomWalls and ceilings appear in good condition overall. Flooring is carpet. Heat register present.Accessible outlets operate.
3. Electrical
North wall second from right North wall near sliding door
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 44 of 74
Middle switch outside light did not operate Light did not operate4. Window-Wall AC or Heat
5. DoorsObservations:• Entry door sticks, recommend adjustment. Bend adjustment cannot open or close•
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 45 of 74
Fan does not operate
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 46 of 74
Stairs Leading to Basement 1. StairSteps appeared uniform.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 47 of 74
Basement Hallway 1. ConditionsCeiling and walls are in good condition overall. Light fixture operates.
2. FloorObservations:• Carpet Wrinkled, recommend restretching.• Carpet transition from on style of carpet to another may present a trip hazard recommendcorrection.
3. ElectricalObservations:• Outlet cover plates missing, recommend cover plates are installed. (Owner states electricity willbe run to box for lights in utility room)
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 48 of 74
Near bonus entry4. DoorsObservations:• Entry door sticks, recommend adjustment.• Closet door difficult to operate, recommend adjustment.
Closet door drags carpet
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 49 of 74
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 50 of 74
Basement Family Room 1. LocationLocation West • South • 3rd Left
2. Family RoomWalls and ceilings appear in good condition overall. Flooring is carpet in good condition. Heatregister present. Accessible outlets operate. • Light fixture operates. • Sliding glass door operatesoverall.
3. Window-Wall AC or Heat
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 51 of 74
4. FloorObservations:• Carpet Wrinkled, recommend restretching.
5. FireplaceFireplace is a gas unit.Observations:• Clamp missing on damper, recommend installing clamp to prevent damper from being closedcompletely in case of gas leak.• Fireplace did not operate, recommend conditions are investigated further by licensed HVACcontractor.• Recommend fireplace be serviced by licensed HVAC contractor
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 52 of 74
No clamp
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 53 of 74
Basement Bedroom 1 1. LocationLocation 1st Left • Northwest
2. Bedroom RoomWalls and ceilings appear in good condition overall. Flooring is carpet. Heat register present.Accessible outlets operate.
Closet ceiling3. DoorsObservations:• Entry door sticks, recommend adjustment.• Closet doors not installed.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 54 of 74
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 55 of 74
Basement Laundry Room 1. ConditionCeiling and walls are in good condition overall. Accessible outlets operate. • Light fixture operates.
2. ElectricalGFI outlets within 6 feet of water sources
3. Exhaust FansWindow only, no vent fan.
4. DryerDryer appeared to exhaust to the exterior. • There is a place for dryer to exhaust to the exterior. •220 volt electrical service for electric dryer.
5. Floor ConditionLaminate wood grain material is in good condition overall.
6. Sink
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 56 of 74
7. Heating
8. Washer
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 57 of 74
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 58 of 74
Utility Room 1. Utility RoomLight fixture operates. • Walls and ceiling were wood frame, appeared in good condition. Floor wasconcrete appeared in good condition
2. Electrical
Junction box for lights.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 59 of 74
Garage 1. ConditionWalls and ceilings appeared in good condition overall. Accessible outlets operate. Light fixturesoperate overall. Flooring is concrete, visible portions in good condition overall.
2. Floor ConditionMaterials: Flooring is concrete, appeared in good condition overall.
3. ElectricalObservations:• Improper use of extension cord observed. Extension cords should not be permanently installed orbe routed through walls, floors or partitions.• Outlets are not GFCI protected, recommend GFCI protecting outlets as a safety precaution
4. DoorsEntry door is in operable condition overall.
5. Garage DoorsSafety return sensors operate overall.
Observations:• Tension safety return did not operate on the garage doors, recommend adjustment.
6. Window DeficienciesObservations:• Window is single pane with Aluminum framing.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 60 of 74
Heat/AC 1. Heating TypeGas forced air furnace. There was good air flow at the heat registers and cold air returns overall. •Heat Pump with gas forced air furnace backup.
2. Heater Location Furnace is located in the utility room
3. Heating conditionObservations:• Last service date is over one year ago, or is unable to be determined. Unit appears to beoperating properly from controls, there are areas which cannot be seen without specializedequipment and training. One such area is the combustion chamber / heat exchanger where cold airblows across the "fire box", becoming the hot air that circulates throughout your home. During thelife span of any furnace, this metal wall may develop a crack or a broken weld, allowing carbonmonoxide to circulate throughout the home. Recommend service and inspection by licensed HVACcontractor prior to closing
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 61 of 74
4. VentingObservations:• Combustion air venting in furnace room: There are two gas fuel-burning appliances in thebasement utility/furnace room: water heater and furnace. All fuel-burning appliances must beprovided with enough fresh air for proper combustion and ventilation of flue gases. In this home,these appliances are using indoor air for ventilation and combustion. Other than the door--there isno visible venting into the utility/furnace room. With the door closed--there may be a lack ofcombustion air resulting in hazardous Carbon Monoxide (CO) into the dwelling living areas.Recommend conditions are investigated further by licensed HVAC contractor.
5. FiltersLocation: Left side of furnace filter location
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 62 of 74
Left side
Right6. AC ConditionLocation: The compressor is located on the exterior east.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 63 of 74
Plumbing/Water Heater1 1. PlumbingWater lines were copper. • Water lines were Galvanized water lines rust from the inside out andrestrict water flow. Average life span for galvanized water lines and 50 years. • Drain and wastelines are cast iron and plastic
2. Water Heater ConditionHeater Type: Gas Water heater.
3. AgeObservations:• Approximately 17 years of age, average life span is 10 to 12 years.
4. ConditionSeismic straps are in place. • Expansion tank is in place.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 64 of 74
5. TPRV Condition
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 65 of 74
Electrical 1 1. LocationMaterials: Located in the Bonus room
2. Electrical125 AMP service, 1/0 Aluminum service entrance wires.Observations:• Wiring not terminated (unattached & without wire nut) in panel box. Possible shock /electrocution hazard, as it can come into contact with panel dead front cover, thereby energizingthe cover.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 66 of 74
3. GroundingElectrical service is grounded and bonded.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 67 of 74
4. Wiring TypeBreaker system present. Wiring sizes conform to breaker sizes overall. Smaller branch circuit wiringis copper.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 68 of 74
Foundation/Crawlspaces 1. FoundationContinuous concrete foundation visible portion appeared in good condition overall. • Basement andconcrete slab foundation.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 69 of 74
Shutoffs 1. Shutoff LocationsMaterials: Main Water
Main gas shutoff Air Conditioner disconnect is located adjacent toexterior portion of the air conditioner.
Water heater water line shutoff is located abovethe water heater.
Furnace gas shutoff is located to the left of thefurnace.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 70 of 74
Furnace disconnect is located to the left of thefurnace.
Basement bedroom
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 71 of 74
Equipment 1. Appliances/EquipmentObservations:• Refrigerator• Dishwasher• Microwave• Stove• Furnace• Water Heater
Water Heater Furnace
||2||Dishwasher ||2||Dishwasher
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 72 of 74
||2||Stove ||2||Refrigerator
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 73 of 74
GlossaryGlossary
Term DefinitionCombustion Air The ductwork installed to bring fresh outside air to the furnace
and/or hot water heater. Normally, two separate supplies of airare brought in: one high and one low.
Expansion Tank An expansion tank or expansion vessel is a small tank used toprotect closed (not open to atmospheric pressure) water heatingsystems and domestic hot water systems from excessivepressure. The tank is partially filled with air, whosecompressibility cushions shock caused by water hammer andabsorbs excess water pressure caused by thermal expansion.
GFCI A special device that is intended for the protection of personnelby de-energizing a circuit, capable of opening the circuit wheneven a small amount of current is flowing through the groundingsystem.
RW West Consultants Inc 808 Woodland Way, Kent, WA
Page 74 of 74
Report SummaryReport Summary
The summary below consists of potentially significant findings. These findings can be a safetyhazard, a deficiency requiring a major expense to correct or items I would like to draw extra attentionto. The summary is not a complete listing of all the findings in the report, and reflects the opinion ofthe inspector. Please review all pages of the report as the summary alone does not explain all of theissues. All repairs should be done by a licensed & bonded tradesman or qualified professional. Irecommend obtaining a copy of all receipts, warranties and permits for the work done.Stairs Leading to 2nd FloorPage 29 Item: 1 Stair • Guardrail balusters are spaced further than newer required 4
inches. 4 inch requirement is so small children cannot fitthrough the guardrail.• Handrail present is less than 36 inches tall, recommendcorrection as a safety precaution.
Hall Bathroom1Page 38 Item: 11 Toilet • Moisture meter indicated abnormal moisture content at the
floor base of toilet. This is typically indication of defective waxseal, recommend conditions are investigated further andcorrected by licensed plumbing contractor.
Basement Family RoomPage 51 Item: 5 Fireplace • Clamp missing on damper, recommend installing clamp to
prevent damper from being closed completely in case of gasleak.• Fireplace did not operate, recommend conditions areinvestigated further by licensed HVAC contractor.• Recommend fireplace be serviced by licensed HVACcontractor
GaragePage 59 Item: 3 Electrical • Outlets are not GFCI protected, recommend GFCI protecting
outlets as a safety precautionPage 59 Item: 5 Garage Doors • Tension safety return did not operate on the garage doors,
recommend adjustment.Heat/ACPage 60 Item: 3 Heating condition • Last service date is over one year ago, or is unable to be
determined. Unit appears to be operating properly fromcontrols, there are areas which cannot be seen withoutspecialized equipment and training. One such area is thecombustion chamber / heat exchanger where cold air blowsacross the "fire box", becoming the hot air that circulatesthroughout your home. During the life span of any furnace,this metal wall may develop a crack or a broken weld, allowingcarbon monoxide to circulate throughout the home.Recommend service and inspection by licensed HVACcontractor prior to closing
Electrical 1Page 65 Item: 2 Electrical • Wiring not terminated (unattached & without wire nut) in
panel box. Possible shock / electrocution hazard, as it cancome into contact with panel dead front cover, therebyenergizing the cover.
Item Page Issue Description Corrective Action Taken
15 of 746 of 74
- Exterior covers missing/damaged, recommend conditions are repaired as a safety precaution- No power to outlet, recommend further investigation and correction.
- Damaged exterior cover replaced at deck outlet.- Electrical power restored to both outlets.
2 27 of 74 - Cosmetic trim cracked near patio door. - Trim replaced.
3 35 of 74
- GFCI protected receptacles may not have been required when the house was built. Recommend upgrading with GFCI's at all receptacles near water sources as a safety precaution. - GFCI outlet installed in Master Bathroom.
4 36 of 74
- GFCI protected receptacles may not have been required when the house was built. Recommend upgrading with GFCI's at all receptacles near water sources as a safety precaution. - GFCI outlet installed in Hall Bathroom.
5 37 of 74 - Stopper is missing from hall bathroom sink. - Installed stopper.
6 38 of 74
- Moisture meter indicated abnormal moisture content at the floor base of toilet. This is typically indication of defective wax seal, recommend conditions are investigated and corrected. - Installed new wax seal.
7 44 of 74 - Middle switch outside light did not operate.- Closed the circuit breaker for lights: Switch and lights operate.
8 44 of 74 - Entry door sticks, recommend adjustment. Bend adjustment cannot open or close.- Door hinges adjusted and secured. Door operates smoothly.
9 47 of 74 - Outlet cover plates missing, recommend cover plates are installed. - Installed outlet cover plates.
10 59 of 74 - Tension safety return did not operate on the garage door, recommend adjustment.- Installed new garage door opener. Tension safety return now functions.
11 60 of 74
- Last service date is over one year ago, or is unable to be determined. Unit appears to be operating properly from controls. Recommend service and inspection by licensed HVAC contractor prior to closing.
East Hill Heating & Cooling inspected and serviced HVAC on 21-Apr-2017.
12 65 of 74Wiring not terminated (unattached & without wire nut) in panel box. Possible shock / electrocution hazard.
Confirmed no power to wiring. Installed wire nuts to unterminated wire ends.