Upload
flyman
View
214
Download
0
Embed Size (px)
Citation preview
158 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 1, JANUARY 2003
Fast Ferroresonance Suppression of CouplingCapacitor Voltage Transformers
Milan Graovac, Reza Iravani , Senior Member, IEEE , Xiaolin Wang, and Ross D. McTaggart , Member, IEEE
Abstract—This paper describes a procedure for fast suppres-sion of the phenomenon of ferroresosnance in coupling capacitorvoltage transformers (CCVT) without major change in the CCVTdesign. It will be shown that it is possible to adjust parameters of the secondary overvoltage protection and the filter circuit so thatthe ferroresonance can be cleared in a very short time interval.The study cases reported in this paper show that ferroresonance iseffectively cleared within two cycles. An implementation of metaloxide varistors (MOV) as part of passive ferroresonance protec-tion is also addressed. The Electromagnetic Transients Program(EMTP) is used for modeling transients and fine-tuning the fer-roresonance suppressing circuit. The studies are conducted on theTrench TEHMP161A CCVT.
Index Terms—CCVT, CVT, electromagnetic transients, EMTP,ferroresonance.
I. INTRODUCTION
CCVT is a widely used apparatus for voltage measurement
at transmission and subtransmission voltage levels. The
output voltage of a CCVT is used for monitoring, protection
relays and control applications. Proper design and tuning of
CCVT components guarantee that its output is the required
replica of the input (system voltage) under steady-state con-
ditions. However, due to the CCVT energy storage elements
and magnetic saturation nonlinearity, its output waveform
deviates from the input waveform during transients [ 1], [2].
The phenomenon of ferroresonance is of particular concern
during CCVT transients, and can cause noticeable deviation of
CCVT response from the actual input waveform.
CCVTs are equipped with overvoltage protection schemes
and suppression circuitries to mitigate the phenomenon of fer-
roresonance. The required time to fully mitigate ferroresonance
can be up to several cycles (of 60 Hz). The phenomenon of
ferroresonance highly distorts the CCVT response during the
first three to five cycles, and results in relatively mild distortion
during the next four to six cycles. This characteristic behavior
of CCVT is well understood and imposes no major difficulty in
conventional applications.
Rapid proliferation of 1) digital protection relays and 2)
power electronic apparatus which require accurate voltage
monitoring for their controls, indicates ever increasing fidelity
Manuscript received September 10, 2001; revised February 27, 2002.M. Graovac, R. Iravani, and X. Wang are with the Center for Applied
Power Electronics (CAPE), Electrical and Computer Engineering Depart-ment, University of Toronto, Toronto, ON M5S 3G4, Canada (e-mail:[email protected]; [email protected]; [email protected]).
R. D. McTaggart is with the Instrument Transformer Division, Trench Group,Scarborough, ON M1P 3B5, Canada (e-mail: [email protected]).
Digital Object Identifier 10.1109/TPWRD.2002.803837
Fig. 1. CCVT circuit diagram for EMTP simulation.
of CCVT response during transient regimes. This paper demon-
strates that by means of fine-tuning of overvoltage protection
and suppression circuits, the phenomenon of ferroresonance
can be effectively mitigated within two cycles for the study
system. The objective is to achieve this improvement without
major change in the design and circuit topology of the CCVT.
II. STUDY SYSTEM
Fig. 1 shows schematic diagram of the Trench TEHMP161A
CCVT used for the studies. The CCVT parameters are given in
the Appendix.
The CCVT is composed of 1) capacitive voltage divider (
and ), 2) Step-down transformer (SDT), 3) compensating re-
actor (CR), 4) overvoltageprotection device and its seriesre-
sistor , and 5) ferroresonance suppressing circuit consisting
ofsaturablereactor( and ) inparallel withpermanentload
. In some designs, the burden side can also be equipped with
overvoltage protection device and its loading resistor
as part of the ferroresonance suppressing circuit. However, this
is not a necessary part for TEHMP161A CCVT. Switch in
series with is only introduced in the simulated circuit to im-
pose transients, otherwise it is not part of the CCVT system.
is the lumped resistance of the CCVT high voltage capacitive
branch.
Under normal conditions, the suppression circuit provides a
constant burden of . A salient feature of a CCVT equipped
with this kind of ferroresonance suppression circuitry is its flat
frequency response up to several hundred Hz. To the contrary,
a CCVT with tuned RLC filter based ferroresonance protection
circuit does not exhibit flat frequency response [ 3], [4].
0885-8977/02$17.00 © 2003 IEEE
Authorized licensed use limited to: Universidad de chile. Downloaded on November 19, 2008 at 12:26 from IEEE Xplore. Restrictions apply.
GRAOVAC et al.: FAST FERRORESONANCE SUPPRESSION OF COUPLING CAPACITOR VOLTAGE TRANSFORMERS 159
Fig. 2. Magnetization curve of .
Studies also show that ferroresonance suppression RL circuit
with saturable reactor has little effect on the CCVT transients.
The current through the reactor is negligible unless the ferrores-
onance is present so the only ferroresonance suppression circuit
component affecting the transient response is loading resistor
[1]. Therefore, the CCVT transient response to a primary
voltage collapse is less distorted when ferroresonance suppres-
sion RL circuit, with saturable reactor, is used. This results in
significantly smaller distance relay overreach [ 2].
has a knee point at about 150% of the rated voltage, Fig. 2,
and unless saturated has no effect on the CCVT response. Fer-
roresonance is accompanied with secondary side overvoltage
which saturates and triggers conduction of (if it exists in
the system). Consequently, the accumulated energy dissipates
in and .
It should be noted that ( ) represents either a spark-gap
with pre-specified break-down voltage or a semiconductor
switch (e.g., triac) which is triggered at a pre-specified voltage
level. TEHMP161A CCVT utilizes a spark-gap.
III. STUDY RESULTS
The CCVT ferroresonance response is investigated under the
following conditions. Initially switch is open and burden is a
series RL branch which consumes 1 VA at 115 and lag-
ging power factor of 0.85. Switch is closed ( m )
and after approximately seven cycles opened. Opening satu-
rates SDT and results in ferroresonance. DCG EMTP [5] isused
for modeling the CCVT ferroresonance test.
A. Case 1
This case investigates the effect of suppressing filter on the
CCVT ferroresonance phenomenon when and are not
included in the CCVT circuit. The ferroresonance suppressing
circuit consists of resistor in parallel with the sat-
urable reactor. Filter reactor has the magnetization curve shown
in Fig. 2 and the internal resistance of . is set
to fire at 250 V.
Fig. 3 shows the CCVT ferroresonance behavior. The first
diagram shows voltage during the test. The second dia-
gram shows RMS values of the same voltage calculated from
zero crossing to zero crossing. The third diagram is the enlarged
version of the second one (around the rated RMS value). It is
assumed that the ferroresonance is cleared if the RMS voltage
value deviates less than 5% from the rated value of 115 V. It
should be noted that half-cycle RMS results in higher deviation
as compared with full-cycle RMS.
Fig. 3. CCVT response to the ferroresonance test when and are notincluded in the system.
Fig. 4. Measured CCVT secondary voltage during the ferroresonance testwhen and are not included in the system. Time scale is 100 ms/div.
Fig. 3 indicates that ferroresonance is cleared after nearly
ten cycles. Overvoltage during the first cycle is very high. The
reason is that current through lags voltage by almost
90 . Therefore, reactor saturates only after the voltage has al-
ready reached the peak value. The CCVT ferroresonance re-
sponse of Fig. 3 closely agrees with the laboratory test result
shown on Fig. 4 and satisfies ANSI C93.1 standard [6]. Figs. 3
and 4 clearly illustrate that CCVT output voltage is highly dis-
torted during the first 4 cycles, and mildly distorted during the
next several cycles.
B. Case 2
This case investigates the phenomenon of ferroresonance
when gap and are also included in the CCVT
model. Breakdown voltage of is set to 250 V. Fig. 5 shows
that ferroresonance is cleared in 13 cycles.
Comparison of Figs. 3 and 5 indicates that presence of
and has a detrimental effect on the CCVT response. The
reason can be explained using Fig. 6.
Authorized licensed use limited to: Universidad de chile. Downloaded on November 19, 2008 at 12:26 from IEEE Xplore. Restrictions apply.
160 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 1, JANUARY 2003
Fig. 5. CCVT response to the ferroresonance test when and areincluded in the system.
Fig. 6. Current components through and saturable reactor duringferroresonance.
Fig. 6 shows distribution of current between the saturable re-
actor branch and branch during ferroresonance. Secondary
voltage experiences a steep rise when the short-circuit cur-
rent is interrupted by switch . Saturable reactor saturates be-
fore voltage reaches to the voltage breakdown level of . Thus
reactor stores some energy during the first half-cycle of tran-
sient and returns a portion of this energy to the CCVT system
during the next half-cycle. If branch – is not included in
the system, this energy will result in the peak voltage of about
500 V in the second half-cycle as shown in Fig. 3. Presence
of – branch limits this peak voltage to about 400 V as
shown in Fig. 6. Reactor once again saturates during the
second half-cycle and also returns some of its stored energy to
the system in the third half-cycle. This in turn results in over-
Fig. 7. CCVT response to ferroresonance test for .
Fig. 8. CCVT response to ferroresonance test for .
voltage in the third half-cycle, but with a noticeably smaller
peak value as compared with the previous half-cycle. After the
second half-cycle, the SDT core is not saturated, but the tran-
sient will be experienced during the next few cycles. Duration
of this transient behavior primary depends on the overvoltage
during the second half-cycle.
Fig. 6 also indicates that the ferroresonance can be more ef-
fectively mitigated if we have the following.
• Phase shift between and the current through is
reduced.
• Dissipated energy in is increased to improve distribu-
tion of dissipated energy between and .
Both issues are addressed by increasing . Fig. 7 shows the
effect of different values of on the CCVT response to the
ferroresonance test when . It should be noted that
increasing beyond a certain value reduces the effectiveness
of since it can limit to a value below the breakdown
voltage of .
Fig. 8 shows that the CCVT response can be further improved
by fine-tuning .
Fig. 9 shows that the phenomenon of ferroresonance is effec-
tively damped out in one cycle when and
.
Authorized licensed use limited to: Universidad de chile. Downloaded on November 19, 2008 at 12:26 from IEEE Xplore. Restrictions apply.
GRAOVAC et al.: FAST FERRORESONANCE SUPPRESSION OF COUPLING CAPACITOR VOLTAGE TRANSFORMERS 161
Fig. 9. CCVT response to ferroresonance test when and
.
Overvoltage protection device can be realized either by a
spark-gap or a triac. In any case must conduct only during
ferroresonance conditions and not as a result of systemovervolt-
ages which are reflected to the CCVT burden side. In this re-
spect, triac is more advantageous as its firing instant and firing
voltage can be more accurately controlled. Furthermore, triac
has capability for large transient overcurrents without reaching
to its thermal limit.
Fig. 10 shows the CCVT response to the hypothetical sce-
nario in which malfunctions andpre-maturely conducts. Pre-
mature conduction of initiates a transient process which re-
sults in brief saturation of SDT after a few cycles. The transientis promptly cleared by the saturable reactor . Fig. 10 indi-
cates that saturable reactor also provides an inherent self-pro-
tection against internal failures. Tuned RLC ferroresonance sup-
pression circuits do not have such a capability.
C. Case 3
An alternative to overvoltage protection device (either
spark-gap or triac) and is a Metal Oxide Varistor (MOV).
Advantages of MOV are 1) stable characteristic, 2) simple de-
sign and robust structure, and 3) high performance reliability.
However, the concern is the limited amount of energy that MOV
can dissipate.
To examine the effectiveness of the MOV in the CCVT sys-
tems, and its series resistance were replaced by a 130
MOV. The energy rating of MOV is 210 J within 2 ms.
is changed within the acceptable range to fine-tune the CCVT
system. Fig. 11 shows the CCVT response to the ferroresonance
Fig. 10. CCVT response to premature conduction of .
Fig. 11. CCVT response to ferroresonance testwhen and are replacedby MOV.
test when . Fig. 11 shows that ferroresonance is
cleared in four cycles. The total dissipated energy in MOV is 93
J which is significantly less than the rated value of 210 J.
Authorized licensed use limited to: Universidad de chile. Downloaded on November 19, 2008 at 12:26 from IEEE Xplore. Restrictions apply.
162 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 1, JANUARY 2003
Fig. 12. Sharing theburden between theMOVand thesaturable reactor duringthe ferroresonance test.
Fig. 13. CCVT response to the ferroresonance test for V,
, and .
Fig. 12 shows current components of MOV and saturable re-
actor during ferroresonance. MOV conducts when is
larger then 280 V. Therefore, it dissipates energy only during
part of the second half-cycle. Fig. 12 also illustrates that the sat-
urable reactor remains active and provides protection during the
rest of the transient period.
IV. DISCUSSION
For conventional applications where the CCVT ferroreso-
nance mitigation is acceptable within several cycles, e.g., 10
cycles, the suppression circuit of Case 1 (i.e., , and
) provides the desired solution. This approach is currently
adopted in the Trench TEHMP161A CCVT. If high-speed (e.g.,
two-cycle) ferroresonance clearing is required, the suppression
circuit can be augmented with the branch composed of
and ; see Fig. 1. represents either a spark-gap or a
triac. Theoretically, both triac and spark-gap provide the same
performance when fired at the same voltage level. However,
firing of the triac can be precisely controlled and practically the
required performance can be achieved with a higher degree of
precision. One solution to assure that spark-gap does not fire
prematurely is to utilize a gap with a higher breakdown voltage.
However, increasing the breakdown voltage will reduce ef-
fectiveness of the overall ferroresonance mitigation system.
Fig. 13 shows the CCVT response to the ferroresonance test
when the gap breakdown voltage is increased from 250 (Fig. 9)
to 350 V. Comparison of Figs. 9 and 13 indicates that increasing
breakdown voltage has increased the required time for clearing
ferroresonance from one to five cycles, respectively.
The studies also indicate that the combination of and
can be replaced by a MOV. Although MOV is not as effec-
tive as a triac/spark-gap in clearing ferroresonance, it can be
used in combination with the suppression filter for ferroreso-
nance mitigation within two cycles. An advantage of MOV over
triac/spark-gap is that it has a more stable – characteristic,
and it is easier to install, operate, and maintain.
V. CONCLUSIONS
The study results presented in this paper demonstrate that
the CCVT ferroresonance protection can be improved, without
a major change in the design, to mitigate the phenomenon of
ferroresonance within a prespecified time period. It is shown
that the well-tuned triac/spark-gap overvoltage protection can
clear the ferroresonance within two cycles. For cases when
pre-mature breakdown failure of the burden-side overvoltage
protection device is a concern, the MOV may be used. MOV
based ferroresonance mitigation may not be as effective as
triac/spark-gap protection, however it noticeably improves the
CCVT ferroresonance response. In all the studied cases, the
suppression circuit, i.e., – – , is the primary counter-
measure to the phenomenon of ferroresonance and either triac,
spark-gap or MOV augments its ferroresonance damping effect.
APPENDIX
Tables I-IV contain technical data for use throughout this
paper.
TABLE ITRENCH TEHMP161A CCVT TECHNICAL DATA
Authorized licensed use limited to: Universidad de chile. Downloaded on November 19, 2008 at 12:26 from IEEE Xplore. Restrictions apply.
GRAOVAC et al.: FAST FERRORESONANCE SUPPRESSION OF COUPLING CAPACITOR VOLTAGE TRANSFORMERS 163
TABLE IICCVT CIRCUIT PARAMETERS
TABLE IIISDT MAGNETIZATION CURVE DATA
TABLE IV MAGNETIZATION CURVE DATA
REFERENCES
[1] M. A. Hudges, “Distance relay performance as affected by capacitorvoltage transformers,” Proc. Inst. Elect. Eng., vol. 121, no. 12, pp.1557–1566, December 1974.
[2] D. Hou and J. Roberts, “Capacitive voltage transformers—Transientoverreach concerns and solution for distance relaying,” in Proc. 22nd
Annu. Western Protective Relay Conf..[3] M. Kezunovic, Lj. Kojovic, V. Skendzic, C. W. Fromen, D. R. Sevcik,
and S. L. Nilsson, “Digital models of coupling capacitor voltage trans-formers for protective relay transient studies,” IEEE Trans. Power De-livery, vol. 7, pp. 1927–1935, Oct. 1992.
[4] H. J. Vermeulen, L. R. Dann, and J. van Roojen, “Equivalent circuitmodeling of a capacitivevoltage transformer for power system harmonicfrequencies,” IEEE Trans. Power Delivery, vol. 10, pp. 1743–1749, Oct.1995.
[5] DCG/EPRI, “Electromagnetic Transients Program (EMTP), Version3.0,” in Rule Book . Palo Alto, CA: Main Program, Nov. 1996, vol. 1.
[6] Power-line carrier coupling capacitors and coupling capacitor voltagetransformers (CCVT)—requirements, ANSI C93.1-1999, May 1999.
Milan Graovac received the B.Sc., M.Sc., and Ph.D. degrees from the Univer-sity of Belgrade, Yugoslavia, all in electrical engineering in 1980, 1987, and1992, respectively.
From 1981 to 1993, he was with Electrical Engineering Department, Univer-sity of Belgrade. He is now a Senior Research Associate at the University of Toronto, Toronto, ON, Canada. His research interests include power system re-liability, dynamics and control, FE modeling, and power electronics.
Reza Iravani (M’85–SM’00)received the B.Sc.degree in electrical engineeringin 1976 from Tehran Polytechnique University and started his career as a con-sulting engineer. He received the M.Sc. and Ph.D. degrees in electrical engi-neering from the University of Manitoba, Canada, in 1981 and 1985, respec-tively.
He is a Professor at the University of Toronto. His research interests includepower electronics and power system dynamics and control.
Xiaolin Wang received his B.Sc. and M.Sc. degrees from Xi’an Jiaotong Uni-versity, China, in electrical engineering in 1982 and 1988. From 1982 to 1994,he was with Electrical Engineering Department at Xi’an Jiaotong University.
He is a Senior Research Associate in the Department of Electrical and Com-puter Engineering, University of Toronto, Canada. His research interests areelectromagnetic transients and control/protection in power system.
Ross D. McTaggart (M’85) was born in Oshawa, ON, Canada, in 1952. Hestudied electrical engineering at the Universityof Toronto and receivedthe B.Sc.degree in 1976.
He becamea ProfessionalEngineerin 1979. He worked as an Engineer at sev-eral electrical manufacturers before joining Trench Electric in 1986 to developan SF6 current transformer product line up to 800 kV. When this was complete,he became the Engineering Manager and is now the R&D Manager at the In-strument Transformer Division.
Mr. McTaggart is an active member of the IEEE and IEC instrument trans-former standards committees and working groups.
Authorized licensed use limited to: Universidad de chile. Downloaded on November 19, 2008 at 12:26 from IEEE Xplore. Restrictions apply.