FELZER nordAQUA FCM chillers and heat pumps
Advanced cooling technology BREATH OF THE BALTIC IN YOUR HOME AND OFFICE
2013
The FCM line
The FELZER nordAQUA FCM line consists of 15 machines with capacities ranging from 110 to 520 kW, using scroll compressors. Thanks to the most advanced components and solutions, the entire line combines low-noise and high-performance with maximum reliability.
Machines can be supplied in either “cool only” or “reversible (cooling and heating)” versions. You can choose between energy effi ciency classes, microchannel or copper-aluminium condensers. You can also select among options for low-noise operation, free cooling, partial heat recovery, built-in hydronic pump packages, and other solutions to fi t your needs.
Technology and reliability
When creating our machines, we try to fi nd a balance between nature and technology. That is why we use R410a refrigerant, which is ozone-friendly, and allows to achieve high performance with relatively small refrigerat charge. Felzer’s production facilities are certifi ed to ISO 14001 standard, and you can be sure that you are causing no harm to the environment when buying our products.
Felzer nordAQUA FCM chillers and heat pumpsFOLLOWING THE TRADITIONS OF THE NORTHERN BALTIC REGIONS, FELZER HELPS PEOPLE TO CREATE COMFORT IN THE DISCOMFORT ENVIRONMENT. FELZER’S NORDAQUA FCM MACHINES ARE RELIABLE AND COMPACT, CRAETED WITH THE MOST ADVANCED SOLUTIONS. COOL ONLY CHILLERS QUIETLY AND SMOOTHLY COOL, AND THE HEAT PUMPS WARM YOUR BUILDING. THE WIDE RANGE OF OPTIONS AVAILABLE ALLOWS EXPERTS TO CHOOSE THE RIGHT SOLUTIONS FOR THEIR PROJECT. THAT’S BALTIC COMFORT.
Felzer nordAQUA_FCM410 chiller with built-in hydronic pump package
FCM BLT-001-EN2
www.felzer.lv
Smooth
Always nearby
Quiet
DurableReliable European suppliers
All chiller components are produced in the European Union and have the CE marking. The machines are assembled in Northern Europe. That, in addition to the sturdy construction of the cabinet, eliminates excess noise and prevents breakage.
Energy efficient
Yes, you can use FELZER nordAQUA FCMs if you are looking to cut electricity costs and require a class A machine, if you want to cheaply heat water using heat recovery in your hot water supply or heating system, or if you just don’t see the point in wasting power on compressors in the winter and want to take advantage of free cooling. Yes, you can save you money and buy reliable and high-quality class B or C machine. The FCM line off ers a wide range of possibilities to the profeccionals in managing energy effi ciency.
In contrast to most of our competitors, the compressors used in our chillers do not exceed single capacity of 25 tons. At partial load, which in most areas of Europe is 95% of the time, the chillers ensure the smallest reasonable changes in cooling capacity when shifting between stages, which is regulated by an advanced control algorithm. Our gradually-regulated chillers are as close as you can get to constant regulation.
Felzer is located at the crossroads of Central, Eastern, and Northern Europe, and so we are never far from our clients in these regions. We know their needs, and take them into account when designing our machines. We have solutions for the harsh continental climate of central Russia, with temperatures that range from -40°С in the winter and +45°С in the summer, for the chilly Scandinavian climate where it doesn’t often go above +25°С, and for the moderate climate of Germany and the Alpine countries. And, you can reach us by car.
The noise from the chiller is muted thanks to a set of implemented solutions. Many of these we off er as options, since not all buildings require them. But the eff ectiveness of the option depends on the basic solutions chosen. And it is here that Felzer is one step ahead. Our chillers use one of the best fans in Europe and the latest generation of compressors. The sturdy cabinet and well-planned construction eliminates noise from component vibration that cannot be controlled by other means.
The body of the chiller is made from galvanized steel and coated with a long-lasting powder coating, protecting it from rust in the most diffi cult conditions. The large selection of coatings for the condensers allows you to place our chillers near corrosive agents.
European quality
Scroll compressors We use the most advanced scroll compressors available. They ensure a long and failure-free operational life, maintain a low noise level, and save on energy use.
Axial fans Large axial fans combine a low noise level with high productivity and energy effi ciency. To minimize the noise level and energy consumption, you have the option of choosing fans with EC motors, or installing fan speed regulators with AC motors.
Reliable power componentsThe modern power components ensure reliable and long-term control and protection of the compressor, fans, and pumps.
Electronic expansion valve Allows for precise regulation of the system’s operation. When combined with a modern controller, it ensures low energy consumption and a wide range of work modes.
© 2013 SIA Felzer 3
Technical specifications
nordAQUA_FCM110-520 FCM-110 FCM-125 FCM-135 FCM-160 FCM-180 FCM-200 FCM-230 FCM-260
CuAl* condenser/Cool only
Nominal cooling capacity 1, kW 108 123 133 167 181 208 226 265
Power input in cooling mode, kW 37 44 50 57 61 74 72 97
EER 2.92 2.83 2.66 2.93 2.96 2.80 3.14 2.73
Eurovent energy effi ciency class B C D B B C A C
MCHE** condenser/Cool only
Nominal cooling capacity 1, kW 110 125 135 173 184 212 230 270
Power input in cooling mode, kW 36 42 48 53 59 72 70 94
EER 3.05 2.89 2.73 3.26 3.12 2.94 3.28 2.87
Eurovent energy effi ciency class B C C A A B C C
CuAl* condenser/Reversible
Nominal cooling capacity 1, kW 108 123 133 167 181 208 226 265
Power input in cooling mode, kW 37 44 50 57 61 74 72 97
EER 2.92 2.83 2.66 2.93 2.96 2.80 3.14 2.73
Eurovent energy effi ciency class B C D B B C A C
НNominal heating capacity2, kW 116 137 151 175 197 224 243 298
Power input in heat pump mode, kW 36 41 46 54 58 68 71 90
COP 3.2 3.3 3.3 3.3 3.4 3.3 3.4 3.3
Eurovent energy effi ciency class A A A A A A A A
Minimum capacity level, % 50 50 50 35 30 35 25 25
Sound power/Pressure***, dB(A) 85 85 85 87 87 87 88 88
Number of compressors in circuit А 2 2 2 1 1 1 2 2
Number of compressors in circuit B 0 0 0 2 2 2 2 2
Number of fans 2 2 2 3 3 3 4 4
Number of evaporators 1 1 1 1 1 1 1 1
Number of condensers in circuit A 1 2 2 1 1 1 2 2
Number of condensers in circuit B 0 0 0 2 2 2 2 2
Dimensions (WxH), mm 2220x2300
Length, mm 1210 2420
Transport weight, kg 643 748 793 1148 1193 1295 1357 1537
Water volume in evaporator, l 7.5 9.16 9.16 13 13 16.8 16.8 16.8
Oil charge in circuit А, kg 13.4 13.4 13.4 6.7 6.7 6.7 13.4 13.4
Oil charge in circuit B, kg 0 0 0 13.4 13.4 13.4 13.4 13.4
Refrigerant type R410a
Refrigerant charge in circuit A, kg 8.5 12.5 12.5 7.5 7.5 8 13 13
Refrigerant charge in circuit B, kg 0 0 0 11.5 11.5 12 13 13
Evaporators: brazed plate
Water fl ow, m3/h 18.86 21.43 23.14 29.66 31.54 36.34 39.43 46.29
Pressure drop in evaporator, kPa 67 40 47 31 35 30 36 51
Maximum pressure in the circuit, bars 10 10 10 10 10 10 10 10
Pipe connections, mm 65 65 65 80 80 80 80 80
Condensers CuAl:
Air fl ow, m3/h 40000 40000 40000 60000 60000 60000 80000 80000
Air pressure drop, Pa 70 70 70 70 70 70 70 70
Clearance, m 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
MCHE condensers:
Air fl ow, m3/h 42000 42000 42000 63000 63000 63000 84000 84000
Air pressure drop, Pa 53 53 53 53 53 53 53 53
Clearance, m 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
Fans:
Fan diameter, mm 800 800 800 800 800 800 800 800
Capacity per fan, kW 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
Nominal data for power source, V/phase/Hz 380-400/3/50
1 For Eurovent standard LCP/A/P/С/AC, water temperature at inlet/outlet is 12/7°C, and ambient air temperature is 35°С.
2 For Eurovent standard LCP/A/P/R/AC, water temperature at inlet/outlet is 40/45°C, ambient air temperature is 7°С, humidity is 87%
* CuAl (Copper-aluminium) heat exchanger
** MCHE (Microchannel Heat Exchanger)
*** At a distance of 1 m
The nordAQUA_FCM line off ers a broad selection of functional capabilities, the best price of installed cooling capacity and high quality.
FCM BLT-001-EN4
www.felzer.lv
nordAQUA_FCM110-520 FCM-300 FCM-350 FCM-380 FCM-410 FCM-450 FCM-480 FCM-520
CuAl* condenser/Cool only
Nominal cooling capacity 1, kW 301 330 369 398 441 471 526
Power input in cooling mode, kW 102 121 127 146 151 170 192
EER 2.9 2.7 2.9 2.7 2.9 2.8 2.7
Eurovent energy effi ciency class B C B C B C C
MCHE** condenser/Cool only
Nominal cooling capacity 1, kW 306 337 375 405 449 479 539
ower input in cooling mode, kW 100 117 123 141 146 165 188
EER 3.18 2.99 3.11 2.93 3.10 2.94 2.89
Eurovent energy effi ciency class A B A B A B C
CuAl* condenser/Reversible
Nominal cooling capacity 1, kW 301 330 369 398 441 471 526
Power input in cooling mode, kW 102 121 127 146 151 170 192
EER 2.9 2.7 2.9 2.7 2.9 2.8 2.7
Eurovent energy effi ciency class B C B C B C C
Nominal heating capacity2, kW 332 372 407 448 482 522 597
Power input in heat pump mode, kW 97 111 120 134 141 156 179
COP 3.4 3.4 3.4 3.3 3.4 3.3 3.3
Eurovent energy effi ciency class A A A A A A A
Minimum capacity level, % 20 20 15 15 13 13 13
Sound power/Pressure***, dB(A) 89 89 90 90 91 91 91
Number of compressors in circuit А 3 3 3 3 4 4 4
Number of compressors in circuit B 2 2 3 3 3 3 4
Number of fans 5 5 6 6 7 7 8
Number of evaporators 1 1 1 1 1 1 1
Number of condensers in circuit A 3 3 3 3 4 4 4
Number of condensers in circuit B 2 2 3 3 3 3 4
Dimensions (WxH), mm 2220x2300
Length, mm 3630 4840
Transport weight, kg 2038 2173 2280 2600 2889 3024 3267
Water volume in evaporator, l 76 100 100 100 111 111 111
Oil charge in circuit А, kg 20.1 20.1 20.1 20.1 26.8 26.8 26.8
Oil charge in circuit B, kg 13.4 13.4 20.1 20.1 20.1 20.1 26.8
Refrigerant type R410a
Refrigerant charge in circuit A, kg 30 30 30 30 36 36 36
Refrigerant charge in circuit B, kg 26 26 30 30 32 32 36
Evaporators: shell-and-tube
Water fl ow, m3/h 52.46 57.77 64.29 69.43 76.97 82.11 92.40
Pressure drop in evaporator, kPa 29 35 41 48 49 56 70
Maximum pressure in the circuit, bars 10 10 10 10 10 10 10
Pipe connections, mm 100 100 100 100 150 150 150
Condensers CuAl:
Air fl ow, m3/h 100000 100000 120000 120000 140000 140000 160000
Air pressure drop, Pa 70 70 70 70 70 70 70
Clearance, m 2.0 2.0 2.0 2.0 2.0 2.0 2.0
MCHE condensers:
Air fl ow, m3/h 105000 105000 126000 126000 147000 147000 168000
Air pressure drop, Pa 53 53 53 53 53 53 53
Clearance, m 2.0 2.0 2.0 2.0 2.0 2.0 2.0
Fans:
Fan diameter, mm 800 800 800 800 800 800 800
Capacity per fan, kW 1.6 1.6 1.6 1.6 1.6 1.6 1.6
Nominal data for power source, V/phase/Hz 380-400/3/50
1 For Eurovent standard LCP/A/P/С/AC, water temperature at inlet/outlet is 12/7°C, and ambient air temperature is 35°С.
2 For Eurovent standard LCP/A/P/R/AC, water temperature at inlet/outlet is 40/45°C, ambient air temperature is 7°С, humidity is 87%
* CuAl (Copper-aluminium) heat exchanger
** MCHE (Microchannel Heat Exchanger)
*** At a distance of 1 m
© 2013 SIA Felzer 5
Options № Factory installation On-site installation
Options for condenser and fan:
MIcrochannel condenser 130 X
Corrosion-resistant e-coating for microchannel condenser 131A Х
Corrosion-resistant BlyGold coating for microchannel condenser 131B X
Corrosion-resistant BlyGold coating for copper and aluminium condenser 131С X
Protective side panels on pipes and condenser cooling towers sides 132D X
Protective grille 132A Х
Mesh strainer on the condenser 132C X
EC motors fans 133A Х
Indoor installation (fans with available pressure and fi xed air conduits) 134 X
Sound options:
Sound shells on the compressors (low-noise) 231 Х
Sound casing on the compressors 232A Х
Low speed fans (extra-quiet) 232B Х
Hydronic pump packages:
Hydronic pump package with one low pressure pump 331A Х
Hydronic pump package with one high pressure pump 331B Х
Hydronic pump package with two low pressure pumps 331C Х
Hydronic pump package with two high pressure pumps 331D Х
Storage tank 339A Х
Work at low temperatures and with a light load:
Work at low temperatures (below +12°С , to -20°С): regulating fan speed with thyristor regulator (with a standard AC fan). 431A Х
Work at low temperatures (below +12°С , to -20°С): regulating fan speed with frequency regulator (with a standard AC fan). 431B Х
Work at low temperatures (below +5°С , to -20°С): electric heater on the evaporator 432A Х
Work at low temperatures (below +5°С , to -20°С): electric heater on the hydronic pump package (if hydronic pump package is installed) 432B Х
External evaporator 433A Х
Hot gas bypass 434A Х
Evaporator with aluminium jacket (thermal insulation) 435А Х
Evaporator and hydronic pump package with aluminium jacket (thermal insulation) 436А Х
Electric and control/instrumentation options:
Soft starter for compressors 531A Х
Phase control relay 531B X
Unit with electronic starter 532 Х
Other options:
Shock mounts 631A X
Adapters for grooved couplings (threaded) 632B Х
Painted in color of client’s choice (in RAL palette) 633A X
Storage at temperatures above 48°С – storage of refrigerant in the condenser. Mandatory for transport in shipping containers. Not compatible with microchannel condenser.
634A X
Energy effi ciency
Partial heat recovery by cooling the discharge pipe 731А Х
Full heat recovery (with copper and aluminium condensers) 732А Х
Reversible chiller – possibility of switching to heat pump mode (with copper and aluminium condensers) 733А Х
Free-cooling 734А X
Ease of maintenance
Ball valve on the compressor’s suction line (on the discharge line in the standard version) 831А X
Ball valve before the safety valve on the discharge line (for servicing without removing the refrigerant from the circuit) 831B X
Options and accessories
FCM BLT-001-EN6
www.felzer.lv
Options № Factory installation On-site installation
Options for condenser and fan:
MIcrochannel condenser 130 X
Corrosion-resistant e-coating for microchannel condenser 131A Х
Corrosion-resistant BlyGold coating for microchannel condenser 131B X
Corrosion-resistant BlyGold coating for copper and aluminium condenser 131С X
Protective side panels on pipes and condenser cooling towers sides 132D X
Protective grille 132A Х
Mesh strainer on the condenser 132C X
EC motors fans 133A Х
Indoor installation (fans with available pressure and fi xed air conduits) 134 X
Sound options:
Sound shells on the compressors (low-noise) 231 Х
Sound casing on the compressors 232A Х
Low speed fans (extra-quiet) 232B Х
Hydronic pump packages:
Hydronic pump package with one low pressure pump 331A Х
Hydronic pump package with one high pressure pump 331B Х
Hydronic pump package with two low pressure pumps 331C Х
Hydronic pump package with two high pressure pumps 331D Х
Storage tank 339A Х
Work at low temperatures and with a light load:
Work at low temperatures (below +12°С , to -20°С): regulating fan speed with thyristor regulator (with a standard AC fan). 431A Х
Work at low temperatures (below +12°С , to -20°С): regulating fan speed with frequency regulator (with a standard AC fan). 431B Х
Work at low temperatures (below +5°С , to -20°С): electric heater on the evaporator 432A Х
Work at low temperatures (below +5°С , to -20°С): electric heater on the hydronic pump package (if hydronic pump package is installed) 432B Х
External evaporator 433A Х
Hot gas bypass 434A Х
Evaporator with aluminium jacket (thermal insulation) 435А Х
Evaporator and hydronic pump package with aluminium jacket (thermal insulation) 436А Х
Electric and control/instrumentation options:
Soft starter for compressors 531A Х
Phase control relay 531B X
Unit with electronic starter 532 Х
Other options:
Shock mounts 631A X
Adapters for grooved couplings (threaded) 632B Х
Painted in color of client’s choice (in RAL palette) 633A X
Storage at temperatures above 48°С – storage of refrigerant in the condenser. Mandatory for transport in shipping containers. Not compatible with microchannel condenser.
634A X
Energy effi ciency
Partial heat recovery by cooling the discharge pipe 731А Х
Full heat recovery (with copper and aluminium condensers) 732А Х
Reversible chiller – possibility of switching to heat pump mode (with copper and aluminium condensers) 733А Х
Free-cooling 734А X
Ease of maintenance
Ball valve on the compressor’s suction line (on the discharge line in the standard version) 831А X
Ball valve before the safety valve on the discharge line (for servicing without removing the refrigerant from the circuit) 831B X
MICROCHANNEL CONDENSER OPTION 130
At the core of FELZER nordAQUA FCM machines are the copper-aluminium condensers. They have been thoroughly tested on the market, and are an excellent and reliable solution. Microchannel all-aluminium condensers have been widely used on “cool only” machines since the end of the 1990s. They can be included in the FELZER nordAQUA FCM as well (you can fi nd the specifi cations for the two versions of the machine in the specifi cations table. Microchannel condensers have a number of advantages over copper and aluminium condensers. First, they are lighter and more compact; the machines in which they are installed require up to 60% less refrigerant charge. Second, they are made from a single metal, which protects them from galvanic corrosion. Third, they are easier to clean – just run them under a stream of highly pressurized water. And fourth, all of these advantages together make this solution more capital-intensive. Microchannel condensers cannot be used in heat pumps, since they cannot also function as evaporators. The copper and aluminium condensers have their advantages as well. First, the air-cooled fi ns of microchannel condensers are more aff ected by contamination. Therefore, if the condenser is not regularly cleaned, with time the fi ns become plugged up and the machine’s performance level drops. Second, copper and aluminum condensers can be repaired, while repairing microchannel condensers is quite diffi cult. If there is a high risk that the condenser will be mechanically damaged, it is best to choose a copper and aluminum condenser. In particularly aggressive environments, either option may be better, depending on other factors. See option 131A/B/C and consult with Felzer specialists.
CONDENSER COATINGS OPTION 131A/B/C
In highly aggressive environments (the seaside, chemical production, etc.), it is recommended that you use either copper and aluminium condensers with Blygold coating or microchannel compressors with either e-coating or Blygold coating. Which one is best depends on the specifi c situation. More information on each type of coating can be provided upon request. Please contact Felzer’s specialists for assistance.
PROTECTIVE OPTIONS OPTIONS 132A/B/C/D• Protective side panels on the cooling towers (option 132D) protect the pipes
from the condenser from physical damage, and also serve a decorative purpose.
• The security grille (option 132A) protects the chiller from infi ltration by people and large animals.
• The mesh strainer on the condenser (option 132С) protects the condenser from large contaminants (poplar fl uff , insects, large stones, etc.).
FANS WITH EC MOTORS OPTION 133AAllows for smooth control of the condensation pressure and decreases energy consumption.
INDOOR INSTALLATION FANS WITH AVAILABLE PRESSURE AND DISCHARGE DUCTS OPTION 134Installation of fans that allow heated air to be expelled from the chiller’s condensers through air ducts allows you to install the chiller indoors.
SOUND OPTIONS
• Sound shells on the compressors (low-noise option) (option 231).• Sound casing on the compressor and low-speed fans (extra-quiet option)
(options 232A and 232B).
© 2013 SIA Felzer 7
Range of performancefor nordAQUA_FCM chillers
LWT – leaving water temperatureAT – ambient temperature
Operational zones I – standard chillerII – chiller with low temperature settingsIII – chiller with options for work in a low temperature environmentIV – chiller with low temperature settings and options for work in a low temperature environment
E-28
E-12
1
TE
11
PE
129
3
LPS
101314
PE TE HPS
2
6
ATTE
4 5
15
E-19 E-18
1
TE
11
PE
129
LPS
101314
PE TE HPS
2
6
ATTE
4 5
15
3
E-34 E-31
1
TE
11
PE
129
8
EWTTE
16
LPS
LWTTE
17
101314
PE TE HPS
6
ATTE
4 5
15
7
1,5 м 3,0 м
-15 -10 -5 0 +5 +10 +15 +20 +25
LWT ºC
0
-10
-20
+10
+20
+30
+40
+50
AT ºC
III
IIIIV
8
EWTTE
16
LWTTE
17
7
2
3E-11 E-8 E-14
1
TE
11
PE
129
LPS
101314
PE TE HPS
6
ATTE
4 5
15
33
8
EWTTE
16
LWTTE
17
7
2
E-21
2
3
8
EWTTE
16
WATERINLET
WATEROUTLET
WATERINLET
WATEROUTLET
WATERINLET
WATEROUTLET
WATERINLET
WATEROUTLET
LWTTE
17
7
2
2 м 2 м3 м
FCM 160-200 – контур A FCM 450-520 – контур A FCM 520 – контур B
FCM 110-135, 230, 260 – контур A FCM 160-350 – контур B
FCM 300-410 – контур AFCM 380-480 – контур B
Key
WORK AT LOW TEMPERATURES AND WITH A LIGHT LOAD: REGULATING FAN SPEED OPTION 431A/BAt a low ambient temperature (below +12°С, to -20°С), a condensation pressure necessary for the compressor to operate must be maintained. If there is no EC motor, this can be done using other methods of regulating fan speed. We propose two options:
• Operation at low temperatures (below +12°С, to -20°С): regulating fan speed using a thyristor regulator (when using a standard AC fan).
• Operation at low temperatures (below +12°С, to -20°С): regulating fan speed using a frequency regulator (when using a standard AC fan).
WORK AT LOW TEMPERATURES AND WITH A LIGHT LOAD: PROTECTING THE EVAPORATOR AND HYDRONIC PUMP PACKAGE FROM FREEZING OPTION 432A/B, 433 If it is necessary to work in freezing ambient temperatures (below +5°С, to -20°С), or when chilling liquids to temperatures close to freezing, you must also prevent the liquid in the evaporator from freezing (since this may damage it). At low temperatures, a glycol solution must therefore be used. However, if freezing is a possibility, we suggest the following options for work at these temperatures:
• An electric heating element on the evaporator (option 432A) will protect the evaporator from freezing during the short-term liquid temperature decreasing (closing to the freezing point).
• Set for external placement of the evaporator outside of the chiller (external evaporator) (option 433А) – allows you to place the evaporator indoors and not use glycol in the system. Requires installation by a certifi ed specialist.
WORK AT LOW TEMPERATURES AND WITH A LIGHT LOAD:• Hot gas bypass (option 434A) – allows you to create additional steps of work
for compressors.
• Thermal insulation of the evaporator with aluminum jacket (option 435А) – protects the insulation from damage.
• Thermal insulation of the hydronic pump package with aluminum jacket (option 436А) – protects the insulation from damage.
• Free-cooling (option 437A) – signifi cantly lowers the cost of operation by saving energy.
ELECTRIC AND CONTROL/INSTRUMENTATION OPTIONS:• Compressor soft starter (option 531A) – lowers the start-up currents.
• Phase control relay (option 531B) – protects the electric and control/instrumentation equipment during a faulty or incorrect launch.
• Unit with electronic starter (option 532) – longer service life than the standard automatic switches.
Options and accessories
FCM BLT-001-EN8
www.felzer.lv
HYDRONIC PUMP PACKAGES OPTIONS 331A/B/C/D AND 339AFELZER nordAQUA FCM chillers can come with hydronic pump packages that allow you to save space and cut installation expenses. There are 4 versions of hydronic pump package available: with one or two pumps, and high or low pressure. The storage tank is installed separately from the chiller, but can be shipped together with it. The thermal insulation is done in-factory, and the tanks are well protected from corrosion.
OTHER OPTIONS:• Shock mounts (option 631A) – protects the building from vibrations.
• Adapters for grooved couplings (threaded) (option 632B) – if you do not have adapters for connecting the chiller pipes to the system pipes.
• Painted in the color of the client’s choice on the RAL palette (option 633A).
• Storage at temperatures higher than 48°С – storage of refrigerant in the condenser. This option is required for transportation in shipping containers. Not compatible with microchannel condensers (option 634A).
ENERGY EFFICIENCY • Partial heat recovery by cooling the discharge line (option 731А) – part of the
heat given off by the chiller can be recovered for a water system (hot water, heating).
• Full heat recovery (with copper and aluminium condensers (option 732А) – most of the heat given off by the chiller can be recovered for a water system (hot water, heating).
• Reversible chiller – the ability to switch to heat pump mode (with copper and aluminium condensers) (option 733А) – the chiller can work in the “cooling only” mode and in the “cooling and heating” mode).
• Free-cooling (option 734А) – direct cooling of the liquid (without using the compressors) using the machine’s cooling towers.
EASE OF MAINTENANCE• Ball valve on the compressor’s suction line) (on the discharge line in the
standard version) (option 831А) – allows the compressor to be repaired with removing the refrigerant.
• Ball valve before the safety valve on the discharge line (for servicing without removing the refrigerant from the circuit) (option 831B).
Hydronic pump package with two pumps (optional)
9
4
6
5 3
3
Two pumps
43 6
One pump
EWT
LWT
TE
TE
8
811F
10
3
3
Hydronic pump package(included in the optional chiller set)
3
3
1
2
2
12 1212
12
PI
12 13
12 Шаровый кран
13 Манометр
Component speci� cations1 – Storage tank with air separator (Option. Not included with the chiller and hydronic pump package)2 – Flex connections (Not included with the chiller and hydronic pump package)3 – Ball valves4 – Expansion tank5 – Mesh strainer6 – In-line pump7 – Check valve8 – Temperature sensors (entering and leaving water)9 – Chiller’s brazed plate heat exchanger 10 – Flow switch11 – Balancing valve12 – Ball valve 13 – Pressure gauge
© 2013 SIA Felzer 9
1
1
1
6
2
2
2
3
57
4
1 Condensers in V-shaped cooling towers
2 Axial fans
3 Hydronic pumps
5
Evaporator
6
Scroll compressors
7
Filter-drier
4
Electronic expansion valve
FCM BLT-001-EN10
Main components
www.felzer.lv
1 1
1
2
2
2
55
5
5
5
5
4
Felzer nordAQUA_FCM410 chiller with built-in hydronic pump package
© 2013 SIA Felzer 11
FCM-110 FCM-125 FCM-135 FCM-160 FCM-180 FCM-200 FCM-230 FCM-260 FCM-300 FCM-350 FCM-380 FCM-410 FCM-450 FCM-480 FCM-520
L (length) 1210 2420 3630 4840
B (breadth) 2220
H (height) 2300
FCM BLT-001-EN12
Dimensions
Dimensions
www.felzer.lv
2140
3633
3633
2300
2220
2220
940
540
362
L
XD2
Z
D1
L
WATER INLETWITHOUT HYDRONIC PUMP PACKAGE5" VICTAULIC
WATER OUTLET5" VICTAULIC
WATER INLETWITH HYDRONIC PUMP PACKAGE5" VICTAULIC
2140
3633
3633
2300
2220
2220
940
540
362
L
XD2
Z
D1
L
WATER INLETWITHOUT HYDRONIC PUMP PACKAGE5" VICTAULIC
WATER OUTLET5" VICTAULIC
WATER INLETWITH HYDRONIC PUMP PACKAGE5" VICTAULIC
2140
3633
3633
2300
2220
2220
940
540
362
L
XD2
Z
D1
L
WATER INLETWITHOUT HYDRONIC PUMP PACKAGE5" VICTAULIC
WATER OUTLET5" VICTAULIC
WATER INLETWITH HYDRONIC PUMP PACKAGE5" VICTAULIC
L=Vx1210 mmV= number of V-shaped cooling towers
© 2013 SIA Felzer 13
NordAQUA FCMs
E-28
E-12
1
TE
11
PE
129
3
LPS
101314
PE TE HPS
2
6
ATTE
4 5
15
E-19 E-18
1
TE
11
PE
129
LPS
101314
PE TE HPS
2
6
ATTE
4 5
15
3
E-34 E-31
1
TE
11
PE
129
8
EWTTE
16
LPS
LWTTE
17
101314
PE TE HPS
6
ATTE
4 5
15
7
1,5 м 3,0 м
-15 -10 -5 0 +5 +10 +15 +20 +25
LWT ºC
0
-10
-20
+10
+20
+30
+40
+50
AT ºC
III
IIIIV
8
EWTTE
16
LWTTE
17
7
2
3E-11 E-8 E-14
1
TE
11
PE
129
LPS
101314
PE TE HPS
6
ATTE
4 5
15
33
8
EWTTE
16
LWTTE
17
7
2
E-21
2
3
8
EWTTE
16
WATERINLET
WATEROUTLET
WATERINLET
WATEROUTLET
WATERINLET
WATEROUTLET
WATERINLET
WATEROUTLET
LWTTE
17
7
2
2 м 2 м3 м
FCM 160-200 – контур A FCM 450-520 – контур A FCM 520 – контур B
FCM 110-135, 230, 260 – контур A FCM 160-350 – контур B
FCM 300-410 – контур AFCM 380-480 – контур B
E-28
E-12
1
TE
11
PE
129
3
LPS
101314
PE TE HPS
2
6
ATTE
4 5
15
E-19 E-18
1
TE
11
PE
129
LPS
101314
PE TE HPS
2
6
ATTE
4 5
15
3
E-34 E-31
1
TE
11
PE
129
8
EWTTE
16
LPS
LWTTE
17
101314
PE TE HPS
6
ATTE
4 5
15
7
1,5 м 3,0 м
-15 -10 -5 0 +5 +10 +15 +20 +25
LWT ºC
0
-10
-20
+10
+20
+30
+40
+50
AT ºC
III
IIIIV
8
EWTTE
16
LWTTE
17
7
2
3E-11 E-8 E-14
1
TE
11
PE
129
LPS
101314
PE TE HPS
6
ATTE
4 5
15
33
8
EWTTE
16
LWTTE
17
7
2
E-21
2
3
8
EWTTE
16
WATERINLET
WATEROUTLET
WATERINLET
WATEROUTLET
WATERINLET
WATEROUTLET
WATERINLET
WATEROUTLET
LWTTE
17
7
2
2 м 2 м3 м
FCM 160-200 – контур A FCM 450-520 – контур A FCM 520 – контур B
FCM 110-135, 230, 260 – контур A FCM 160-350 – контур B
FCM 300-410 – контур AFCM 380-480 – контур B
Component specifi cations1 – Scroll compressors2 – Condenser fans3 – Condenser (microchannel aluminium)4 – Filter-drier5 – Sight glass6 – Electronic expansion valve (EEV)7 – Brazed plate heat exchanger (BPHE)8 – Mesh strainer protecting the evaporator from large particles in the circuit water9 – Low pressure switch10 – High pressure switch
11 – Suction temperature sensor (overheating)12 – Suction pressure sensor (evaporation)13 – Discharge temperature sensor 14 – Discharge pressure sensor 15 – Ambient temperature sensor 16 – Entering water temperature sensor 17 – Leaving water temperature sensor
FCM 160-200 – circuit А
FCM 450-520 – circuit АFCM 520 – circuit В
FCM BLT-001-EN14
www.felzer.lv
E-28
E-12
1
TE
11
PE
129
3
LPS
101314
PE TE HPS
2
6
ATTE
4 5
15
E-19 E-18
1
TE
11
PE
129
LPS
101314
PE TE HPS
2
6
ATTE
4 5
15
3
E-34 E-31
1
TE
11
PE
129
8
EWTTE
16
LPS
LWTTE
17
101314
PE TE HPS
6
ATTE
4 5
15
7
1,5 м 3,0 м
-15 -10 -5 0 +5 +10 +15 +20 +25
LWT ºC
0
-10
-20
+10
+20
+30
+40
+50
AT ºC
III
IIIIV
8
EWTTE
16
LWTTE
17
7
2
3E-11 E-8 E-14
1
TE
11
PE
129
LPS
101314
PE TE HPS
6
ATTE
4 5
15
33
8
EWTTE
16
LWTTE
17
7
2
E-21
2
3
8
EWTTE
16
WATERINLET
WATEROUTLET
WATERINLET
WATEROUTLET
WATERINLET
WATEROUTLET
WATERINLET
WATEROUTLET
LWTTE
17
7
2
2 м 2 м3 м
FCM 160-200 – контур A FCM 450-520 – контур A FCM 520 – контур B
FCM 110-135, 230, 260 – контур A FCM 160-350 – контур B
FCM 300-410 – контур AFCM 380-480 – контур BE-28
E-12
1
TE
11
PE
129
3
LPS
101314
PE TE HPS
2
6
ATTE
4 5
15
E-19 E-18
1
TE
11
PE
129
LPS
101314
PE TE HPS
2
6
ATTE
4 5
15
3
E-34 E-31
1
TE
11
PE
129
8
EWTTE
16
LPS
LWTTE
17
101314
PE TE HPS
6
ATTE
4 5
15
7
1,5 м 3,0 м
-15 -10 -5 0 +5 +10 +15 +20 +25
LWT ºC
0
-10
-20
+10
+20
+30
+40
+50
AT ºC
III
IIIIV
8
EWTTE
16
LWTTE
17
7
2
3E-11 E-8 E-14
1
TE
11
PE
129
LPS
101314
PE TE HPS
6
ATTE
4 5
15
33
8
EWTTE
16
LWTTE
17
7
2
E-21
2
3
8
EWTTE
16
WATERINLET
WATEROUTLET
WATERINLET
WATEROUTLET
WATERINLET
WATEROUTLET
WATERINLET
WATEROUTLET
LWTTE
17
7
2
2 м 2 м3 м
FCM 160-200 – контур A FCM 450-520 – контур A FCM 520 – контур B
FCM 110-135, 230, 260 – контур A FCM 160-350 – контур B
FCM 300-410 – контур AFCM 380-480 – контур B
Component specifi cations1 – Tandem scroll compressors*2 – Condenser fans (one – FCC 055, 060, 070; two – FCC 080)3 – Condenser (microchannel aluminium)4 – Filter-drier5 – Sight glass6 – Electronic expansion valve (EEV)7 – Brazed plate heat exchanger (BPHE)8 – Mesh strainer protecting the evaporator from large particles in the circuit water9 – Low pressure switch
10 – High pressure switch11 – Suction temperature sensor (overheating)12 – Suction pressure sensor (evaporation)13 – Discharge temperature sensor 14 – Discharge pressure sensor 15 – Ambient temperature sensor 16 – Entering water temperature sensor 17 – Leaving water temperature sensor
FCM 110-135, 230, 260 – circuit АFCM 160-350 – circuit В
FCM 300-410 – circuit АFCM 380-480 – circuit В
© 2013 SIA Felzer 15