ilt{ovAlt0t{s FoR LrvrilG" Description OwensCorning QuietR@ AcousticR" Duct Linerisa bondedblanket of glass fibers designed to be installed inside sheet metalductworkand plenums with metalfasteners and adhesives. The smooth, fire- resistant airstream surfaces resist damage during installation and in service. Q uietR@ AcousticR* Duct Liner complies with requirements of National Fire Protection Association Standards NFPA 90A and 908, qualifying it underother model codes. QuietR@ AcousticR- Duct Liner is available in a selection of thicknesses to meet specific system thermal and acoustical performance requ irements (see Availability table).Rolls are sized to run efficiently on modern automatic coil lines. QuietR@ AcousticR* Duct Linernas a tough,flame-retardant airstream surface with an EPAregistered biocide that stands up to gouging andother abuse in the shoo and on the way to the job-site. lt also contributes to reliable long-term service at internal air velocities up to 6,000fpm (30,5mA). The factoryapplied edge coating complies with industry standards requiring treated transverse joints. ,Produ.ct Dbta,Sh'ebt Availability and Thermal Performance QuietR@ AcousticR- Duct Liner is available in the follo'rvins combinationsofthicknesses and tyoes. ,. ThtCkr,ress ::: . il . l ,,, R;VXue "' :' : . . r: : . l. : ih, 'mrn ,i ',(hilft'?."F)/Btu','i (mr.'.CllW '/z 13 ).2 0.38 QuietR@ AcousticR' Duct Liner Roll Length ..ft.. r00 ffi m 3l 4.7 4.74 3l t00 6.3 8.0 t5 Typical Physical Pit$e$ri$wiiiriiiiiiiliiiii:i Operating Temperature Properties i;1i,i'iir.;iil1iii,'*1..;;'#**ifildifi *A ASTM C +I I ii::::'rV$lHEriii:::: 250'F il2r'C) Maximum Air Velocity UL l8l Erosion Test ,ASTM C IOTI 6,000 fpm (30.5 m/sec) Water Vapor Sorption (by weight) ASTM C IIO4 <3% at I)O"F (49'C1, o57" q.Fl. Fungi Resistance ASTI.,1 C r338 l{eets requirements Fungi Resistance ASTI"1 G 2l Meets requirements Bacteria Resistance ASTM G 22 lYeets rcquirements Corrosiveness ASTM C 565 (Corrosiveness Test) Will not cause corrosion greater than caused by sterile cotton on aluminumor steelx ThermalConductivity k at 75"F(1. at 24'C mean) Type200 R-4.2 P.-6.3 R-8 ASTI'1 C 5I8 Btu.in/hr.ttr." F 0.23 0.24 0.24 0.24 Wm."C 0.034 0.0-?5 0.035 0.035 Surface Burning Characteristics Flame Spread Smoke Developed ASTM E 84,UL 723 <25 <50 Uses QuietR@ AcousticR* Duct Liner enhances indoor environmental quality by absorbing noise within sheetmetalducts, and contributes to indoor comfort by lowedngheatloss or gain through duct walls. Product Attributes Bacterial and Fungal Growth Resistance An EPAregistered biocidein the air stream surface orotects QuietR@ AcousticR- Duct Liner from microbial growth and meets requirements of ASTM C 1338, ASTM G2l (fungitest), and ASTM G22 (bacteria test), Tips to Avoid Mold Growth in Ducts Mold in duct systems occurs when moisture comes into contact with dirt or dustcollection on the duct system surfaces. Proper filters will minimize the collection of dusts and dirt, but careneeds to be exercised to oreventwater formation in the duct,A properly sized andoperated air conditioning unitwill minimize the likelihood of water formation, The system must be maintained and ooerated to insure that sufficient dehumidification is occurring and that filtersare installed and changed asrecommended by the equipment manufacturen

ffi QuietR@ AcousticR' - General Metals · PDF fileWater Vapor Sorption (by weight) ASTM C IIO4

Embed Size (px)

Citation preview

Page 1: ffi QuietR@ AcousticR' - General Metals · PDF fileWater Vapor Sorption (by weight) ASTM C IIO4

ilt{ovAlt0t{s FoR LrvrilG"

Description

Owens Corning QuietR@AcousticR" Duct Liner is abonded blanket of glass fibersdesigned to be installed insidesheet metal ductwork andplenums with metal fasteners andadhesives. The smooth, fire-resistant airstream surfaces resistdamage during installation and inservice. Q uietR@ AcousticR*Duct Liner complies withrequirements of National FireProtection Association StandardsNFPA 90A and 908, qualifying itunder other model codes.

QuietR@ AcousticR- Duct Lineris available in a selection ofthicknesses to meet specificsystem thermal and acousticalperformance requ irements (seeAvailability table). Rolls are sizedto run efficiently on modernautomatic coil lines. QuietR@AcousticR* Duct Liner nas atough, flame-retardant airstreamsurface with an EPA registeredbiocide that stands up to gougingand other abuse in the shoo andon the way to the job-site. lt alsocontributes to reliable long-termservice at internal air velocities upto 6,000 fpm (30,5 mA).

The factory applied edge coatingcomplies with industry standardsrequiring treated transverse joints.

,Produ.ct Dbta,Sh'ebtAvailability and Thermal PerformanceQuietR@ AcousticR- Duct Liner is available in the follo'rvins combinations ofthicknesses and tyoes.

,. ThtCkr,ress ::: . il . l ,,, R;VXue" ' : ' : . . r : : . l . :

ih, 'mrn ,i ',(hilft'?."F)/Btu','i (mr.'.CllW'/z 13 ).2 0.38

QuietR@ AcousticR'Duct Liner

Roll Length

..ft..r00

ffi

m3 l

4.7 4.74 3 lt 00

6.3

8.0 t 5

Typical PhysicalPit$e$ri$wiiiriiiiiiiliiiii:iOperating Temperature

Propertiesi;1i,i'iir.;iil1iii,'*1..;;'#**ifildifi *A

ASTM C +I Iii::::'rV$lHEriii::::250'F i l2r 'C)

Maximum Air Velocity UL l8l Erosion Test,ASTM C IOTI

6,000 fpm (30.5 m/sec)

Water Vapor Sorption (by weight) ASTM C I IO4 <3% at I )O"F (49 'C1, o57" q .F l .

Fungi Resistance ASTI.,1 C r338 l{eets requirements

Fungi Resistance ASTI"1 G 2l Meets requirements

Bacteria Resistance ASTM G 22 lYeets rcquirements

Corrosiveness ASTM C 565(Corrosiveness Test)

Will not cause corrosion greater than causedby steri le cotton on aluminum or steelx

Thermal Conductivityk at 75"F (1. at 24'C mean)Type 200R-4.2P.-6.3R-8

ASTI'1 C 5I8 Btu.in/hr.ttr." F

0.230.240.240.24

Wm."C

0.0340.0-?50.0350.035

Surface Burning CharacteristicsFlame SpreadSmoke Developed

ASTM E 84, UL 723<25<50

Uses

QuietR@ AcousticR* Duct Linerenhances indoor environmentalquality by absorbing noise withinsheet metal ducts, andcontributes to indoor comfort bylowedng heat loss or gain throughduct walls.

Product Attributes

Bacterial and Fungal GrowthResistanceAn EPA registered biocide in theair stream surface orotectsQuietR@ AcousticR- Duct Linerfrom microbial growth and meetsrequirements of ASTM C 1338,ASTM G2l (fungitest), andASTM G22 (bacteria test),

Tips to Avoid Mold Growthin DuctsMold in duct systems occurs whenmoisture comes into contact withdirt or dust collection on the ductsystem surfaces. Proper filters willminimize the collection of dustsand dirt, but care needs to beexercised to orevent waterformation in the duct, A properlysized and operated air conditioningunit will minimize the likelihood ofwater formation, The system mustbe maintained and ooerated toinsure that sufficientdehumidification is occurring andthat filters are installed andchanged as recommended by theequipment manufacturen

Page 2: ffi QuietR@ AcousticR' - General Metals · PDF fileWater Vapor Sorption (by weight) ASTM C IIO4

m.il{t{0YATt0}lt r0[ Ltvtl{G*

Assured Thermal PerformanceWhen installed in accordancewith instructions so thatcompression is controlled,QuietR@ AcousticR" Duct Linerprovides specifi ed thermalperformance. See R-value tablebelow. Operating costs arecontrolled due to reduction ofheat loss or gain through ductwdls.

Acoustically EfficientDuct systems built with this linerabsorb fan and air turbulencenoise and reduce popping noisescaused by sheet metal expansion,contraction and vibration.

ApplicationRecommendations

All portions of duct designated toreceive QuietR@ AcousticR' DuctLiner shall be completely coveredwith duct liner: adhered to thesheet metal with 90% coverage ofadhesive complying with ASTM C915. Transverse joints shall beneatly butted and there shall beno interruptions or gaps. Alltransverse joints shall be edge-coated. Metal nosing on leadingedges must be used where ductliner is preceded by unlined metal,and on all upstream edges whenvelocity exceeds 4,000 fpm (20,3m/s). The black mat faced surfaceof the duct liner shall face theairstream.

QuietR@ AcousticR- Duct Linershall also be secured withmechanical fasteners, eitherimpact-driven or weld-secu red,which shall comoress the ductliner sufficiently to hold it firmly inplace. For fastener spacing, seeillustration.

,:,::r:F#d $ffi iiil ffi $il$H6iBtii:,i,i

Duct Liner shall be cut to assureoverlapped and compressedlongitudinal corner joints. Fordetails, referto NAIMAPublication AHl24, Fibrous GlassDuct Liner Standard,

Minor damage and small tearsmay be repaired by coating withadhesive.

After,installation, and prior tooccupancy blow out duct systemto remove any cuttrng scraps orforeign material remaining in theduct.

Installing two layers of material tomeet a soecific linerthickness isnot recommended. lf thesoecif rcation forces the use ofmultiple layers, the following stepsmust be taken:

l. Adhere bottom layer of ductl inerto duct in normal mannen

2. Adhere top layer to bottomlayer of l iner using a minimumof 90% adhesive coverage.

3. Treat all leading edges withmetal nosings to preventseparation of the two layers.

4. Use mechanical fasteners of theproper length for double layer:

Specification Com pliance. ASTM C l07 l ,Type l , F lex ib le

(replaces obsolete FederalSpecification H H- | -545B.)

. NFPA 9OA/9OB

. ICC Compliant

. California Title 74

. SMACNA Application Standardfor Duct Liners

QuietR@ AcousticR'Duct Liner

. NAIMA Fibrous Glass DuctLiner I nstallation Standard

. Conforms to ASHRAE 67-2001

Application Limitations

Use of QuietR@ AcousticR* DuctLiner is not recommended for thefollowing applications:

. With wood or coal firedequipment, or equipment ofany type which does notinclude automatic maximumtemperature controls andwhere operati ng tem peratu resof 250'F ( l2l "C) may beexceeded.

' ln kitchen or fume exhaustducts, or ducts conveying solidsor corrosive gases

. In any application where theduct liner may come in directcontact with liquid water (suchas cooling coils, humidifiers, andevaporative coolers) unlessorotected from the watersource.

. Inside fire damper sleeves.

. immediately adjacent to hightemperature heating coilswithout radiation protection.

{t

Page 3: ffi QuietR@ AcousticR' - General Metals · PDF fileWater Vapor Sorption (by weight) ASTM C IIO4

QuietR@ Acoustict.Duct Linerm.

]{O',ATIOi{S TOR LIYII{G*Iti

NRC

0,05 0,87 0.98 r .05 0.70

I r, (38) 0.05 u . i 1 0,Bs t . 0 l t .85

Octave band center frequencies, Hz

t25 250 500 t000 2000 4000

8 0,6 r .5 ) .7 5.8 7.4 +.3 0.8 2.9 1.9 7.2 7.4 4.3

0.5 | .7 7.3 5.0 5.8 3 .6 0.5 ) .3 +.2 6.7 5.8 3.6

0.+ 0.8 | .9 4.0 1.1 2 .8 0 .5 t . 6 3 .5 5 .0 4 . t ) . 8

0.2 0.5 r . .1 7.8 ) .? r . 8 0.1 0.8 2.3 i .3 2.0 1.7

0.1 0 . r r .0 2 .0 r .2 i . 2 0.2 0 .5 t .8 ) .3 r . r r . l

Duct Liner inserlion Loss - Data extracted frcm ASHRAE Handbook, HVAC Appiications, Chapter 43, 1999P/A = duct perirneten ft iduct cross sectional area (ft2). Example: 12" x 12", PiA = 4 t l/ft). For more information, call,our Orens Cor n ing Representa t i 'e .

Figure I

ProduCt Data Sheet

Acoustic Performance,,,,:,,, ::,:,::1, T€ited V:tl i j*s'r.quietR9 Duet iher::::, r i:: : :::

Sound Absorption coefflcients at octave band center frequencies (Hz)

Thickness in imm) 125 250 500 1000 2000 4000' : ( l3) 0.01 0 . t 2 0.39 o.64 0.78 0.74 0.50

| (25)

2 ( 5 r ) 0 . 1 7 0.66 t . 04 r .08 | . 07 0.9s

These data'rere collected using a l imited sample size and are not absolute vaiues. Reasonabie tolerances musttherefore be applied. All tests,rere conducted in accordance with ASTIY C'i23, l"lounting A (materiai piaced against asolid backing such as a block wall). For more information, call y-our Owens Corning Representative.

::,:::,,,i, i:::!ns€htion,rlrrs$' xB - r:ft::of:uin:ed,::Strct:,::,,,,,:::: ii;l " L iner 2" L iner

Octave band center frequencies, Hz

PlA,ftlft'z 125 250 500 1000 2000 4000

0.30 0.60

legsed md hfiEdcomtr

ilAXtUUil f;As}Ef,tn SFlfiilS ::{lt|.linlrndr,ail ry!|i|dt0 to 2500 fpm'rebcitv

,,,,, , ,,, ' , ,, ,,,,,, :: ' t0ridl2;;: lr l/*gelg , , , , , , , , , : , : : : : : : ' A

' , , , ' , , , , , U " ' : " f , : : : : : , ' f tfnn*.

I l*- {180m} {i5mm} l300sml {460nm}

:: :,:: U5111'10:6000:&rn $l6riB ,: ,, ,,:::,: :*1L?10,30;5ro/recJ' : ,,,:. : . . A: ' , : :g , , : c,: , : ' B ::':::.'fi: i ..:3lf :tr :8r:1:::, lBlf::;{l0uftmf {}srlft} {rl50mml.1'l&5mm}

.-,I- >' :&' ru*l n*u t,r,**r r ruui **t i. *uo,t',,,F.rd'd* finer rs prece#d by urdined metui.0tlwrunse,wlpnoir v*crlv exteeb 4000 lpm (20.3 mls). u* mefnlmehl nosiftg 0n 0ll up$reom edges of dutt liner.

Page 4: ffi QuietR@ AcousticR' - General Metals · PDF fileWater Vapor Sorption (by weight) ASTM C IIO4

QuietR@ AcousticR.Duct Linerm.

t{ovATt0t{l roR LtYtl{G*

OWENS OORNING INSULATING SYSTEMS, LLCONE OWENS COFNING PARKWAYTOLEDO, OHIO, USA43659

1.800-GET-PINK*ilrofiflo$filUflXC www.owenscornlng.com

Pub. No. 10004451-A. Printed in U.S.A. August 2007. THE PINKPANTHER" &@1964-2007 MetreGoldwyn-Mayer Studios Inc. All RightsBeserved. The color PINK is a registered trademark of Owens Corning.@2007 Owens Corning.