Distance (m) Temperature °C 70 60 50 40 30 20 10 0 Exceeding a maximum Temperature > 60° C Time (s) Temperature °C 70 60 50 40 30 20 10 0 Exceeding a Temperature Increase Within A Certain Time > 13° C/40 s Alarm Distance (m) > 15° C > 15° C Avg. Temp. Temperature °C 70 60 50 40 30 20 10 0 Exceeding the Average Temperature by > 15° C Alarm Alarm Applications: Road and railway tunnels Cable routes, bus ducts, and data centers Storage and warehouse facilities including conveyor systems Nuclear and other special hazard facilities Commercial Buildings and Parking Garage Features: Cost-effective gathering of thousands of measurements over long distances with a single fiber optic sensing cable Pinpoints exact location, size, and spread of fire events Installs and integrates easily into fire management systems Eliminates need for maintenance or individual calibration for each sensing point Intrinsically safe and immune to electromagnetic noise (EMI), dirt, dust and humidity Eliminates requirement for separate power and communication cabling Customizable packaging techniques for harsh environments Allows stand-alone operation Marmon Engineered Solutions’ FOSS lets you configure the appropriate alarm criteria in hundreds of zones along the same sensor cable to prevent false alarms or false positives in environments with dynamic temperature ranges. Software can also be programmed to interact with surveillance and suppression systems to ensure an accurate and effective response. Marmon Engineered Solutions’ FOSS for Fire Detection, using Distributed Temperature Sensing (DTS), minimizes total installation and operational costs while maximizing reliability for asset pro- tection in areas with extreme environmental conditions and high safety risks. Alarm Types: - Max/Min. - Temp Average - Temp Differential - Temp Gradient/Increase 280 Trumbull Street • 23rd Floor • Hartford, CT 06103 USA • Telephone: 832-813-8674 • Fax: 860-653-8301 • www.marmonewc.com © 2017 Marmon Wire & Cable, LLC Fiber Optic Sensing Systems Fire Detection

Fiber Optic Sensing Systems Fire Detection - Marmon EWCmarmonewc.com/wp-content/uploads/2017/03/FOSS-Fire-Safety-Tech...• Passes API 2218 flame test and ASTM 119 curve Fiber Optic

Embed Size (px)

Citation preview

Page 1: Fiber Optic Sensing Systems Fire Detection - Marmon EWCmarmonewc.com/wp-content/uploads/2017/03/FOSS-Fire-Safety-Tech...• Passes API 2218 flame test and ASTM 119 curve Fiber Optic

Distance (m)

Tem

pera

ture

°C

70

60

50

40

30

20

10

0

Exceeding a maximum Temperature > 60° CTime (s)

Tem

pera

ture

°C

70

60

50

40

30

20

10

0

Exceeding a Temperature Increase WithinA Certain Time > 13° C/40 s

Alarm

Distance (m)

> 15° C> 15° CAvg. Temp.

Tem

pera

ture

°C

70

60

50

40

30

20

10

0

Exceeding the Average Temperature by > 15° C

AlarmAlarm

Applications:• Road and railway tunnels• Cable routes, bus ducts, and data centers• Storage and warehouse facilities includingconveyor systems

• Nuclear and other special hazard facilities• Commercial Buildings and Parking Garage

Features:• Cost-effective gathering of thousands ofmeasurements over long distances with asingle fiber optic sensing cable

• Pinpoints exact location, size, and spread offire events

• Installs and integrates easily into fire management systems• Eliminates need for maintenance or individual calibration for each sensing point• Intrinsically safe and immune to electromagnetic noise (EMI), dirt, dust and humidity• Eliminates requirement for separate power and communication cabling• Customizable packaging techniques for harsh environments• Allows stand-alone operationMarmon Engineered Solutions’ FOSS lets you configure the appropriate alarm criteria inhundreds of zones along the same sensor cable to prevent false alarms or false positives inenvironments with dynamic temperature ranges. Software can also be programmed to interact withsurveillance and suppression systems to ensure an accurate and effective response.

Marmon Engineered Solutions’ FOSS for Fire Detection, using Distributed Temperature Sensing(DTS), minimizes total installation and operational costs while maximizing reliability for asset pro-tection in areas with extreme environmental conditions and high safety risks.

Alarm Types: - Max/Min. - Temp Average - Temp Differential - Temp Gradient/Increase

280 Trumbull Street • 23rd Floor • Hartford, CT 06103 USA • Telephone: 832-813-8674 • Fax: 860-653-8301 • www.marmonewc.com© 2017 Marmon Wire & Cable, LLC

Fiber Optic Sensing SystemsFire Detection

Page 2: Fiber Optic Sensing Systems Fire Detection - Marmon EWCmarmonewc.com/wp-content/uploads/2017/03/FOSS-Fire-Safety-Tech...• Passes API 2218 flame test and ASTM 119 curve Fiber Optic

VITALink® 2000:The proper cable design also allows our sensing system to withstand temperatures up to 1000°C(1832°F). This includes Marmon’s Fire Resistive Instrumentation Cable, VITALink® 2000 600 Volt(Pairs or Triads). Size: 16 AWG – 19/29 nickel-coated copper, thermal barrier layer, .045”low-smoke zero-halogen thermoset ceramifiable insulation and .015” black low-smoke zero-halogenthermoset conductor jacket (nominal diameter 0.235”, 5.97 mm).

Features and Performance• Patented VITALink® 2000 Fire-Rated cable • Flexible for installation ease• Easy stripability, no special tools/connectors• In accordance with UL/CUL Listed standards

• Low Smoke, Halogen free design• Moisture Resistant • Installs in steel raceway/conduit with steel fittings• Passes API 2218 flame test and ASTM 119 curve

Fiber Optic Sensing Systems (FOSS)for Fire Detection systems have a lifeexpectancy of 30 years or more based offmean-time-between-failures (MTBF) statisticalfield analysis.

280 Trumbull Street • 23rd Floor • Hartford, CT 06103 USA • Telephone: 832-813-8674 • Fax: 860-653-8301 • www.marmonewc.com© 2017 Marmon Wire & Cable, LLC

Fiber Optic Sensing SystemsFire Detection

International Quality Standards as recognized by:• VdS (Association of German Property Insurers)• CE (Electromagnetic Compliance, Europe)• prEN 54-22 Class A1N• UL 521, ULC S530 spacing up to 50ft

• ISO 9001 and ISO 14001• TÜV Rheinland• ATEX certified

Optical Fiber

Backscattered Light ReturningTo The Temperature Sensor

Laser Pulse PropagatingThrough The Fiber

Technical Performance• Temperature accuracy: < 1.0°C• Temperature resolution: < 0.5°C• Spatial Resolution: up to 0.25m• Measurement Time: 10s to 30s (adjustable)

• Unit Operating Temperature: -10°C to+60°C

• Available with 1, 2, and 4 channels • Suitable for wind speeds up to 10m/s• Full sensor system redundancy available

• Operating temperature range: -180°C to +1000°C(depending on sensor cable design)

• Measurement Range: up to 10km per channel / 20kmwith one unit (10km in either direction)

• Crucial information determining the magnitude and directionof the fire spread

• Localization of fire source without false alarms• Alarm as well as pre-alarm criteria selectable for each zone • Over 250 individually programmable zones per channel(overlapping zones, distinct alarm types)