4
Data sheet Fibershield ® -HC Fibershield ® -HC The horizontal fire protection curtain without inconvenient support ropes in the opening Product description In the event of an alarm, a room-enclosing or radiation-reducing textile fire protection closure that closes by means of an electric motor in a horizontal installation position and closing direction. Type radiation-reducing, room-enclosing fire protection closure of textile design Verification CE marking according to hEN 16034 : 2014 in conjunction with hEN 13241 : 2003+A2 : 2016 Closing direction horizontal Fire resistance E 120 • EW 90 • tested according to EN 1634-1 : 2014-03 • classified according to EN 13501-2 : 2016-12 Closing cycles C • C1 • tested according to EN 12605 : 2000-08 • classified according to EN 13501-2 : 2016-12 Durability C1 for 1-part systems up to size 5000 x 5000 mm for EW60 or 6000 x 6500 mm for E120 and EW30 • C for 2-part systems up to size 9400 x 18800 mm for E120 and EW60 or 6800 x 4270 mm for EW90 Environmental conditions In the event of a fire, the falling of ceiling parts in the area of the the area of the soffit by suitable on-site measures on the part of the customer. Not taken into account are special environmental conditions (for example Humidity >80%, ambient t • Special environmental conditions are not taken into account (e.g. humidity > 80 %, ambient temperature < 5 °C and > 45 °C, wind loads etc.). V EN-20211218 1 stoebich.com

Fibershield -HC

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Data sheetFibershield®-HC

Fibershield®-HCThe horizontal fire protection curtain without inconvenient support ropes in the

opening

Product description In the event of an alarm, a room-enclosing or radiation-reducingtextile fire protection closure that closes by means of an electricmotor in a horizontal installation position and closing direction.

Type radiation-reducing, room-enclosingfire protection closure of textiledesign

Verification CE marking according to hEN16034 : 2014 in conjunction withhEN 13241 : 2003+A2 : 2016

Closing direction horizontal

Fire resistance E 120 • EW 90 • tested accordingto EN 1634-1 : 2014-03 • classifiedaccording to EN 13501-2 : 2016-12

Closing cycles C • C1 • tested according to EN12605 : 2000-08 • classifiedaccording to EN 13501-2 : 2016-12

Durability C1 for 1-part systems up to size5000 x 5000 mm for EW60 or 6000x 6500 mm for E120 and EW30 • Cfor 2-part systems up to size 9400x 18800 mm for E120 and EW60 or6800 x 4270 mm for EW90

Environmental conditions In the event of a fire, the falling ofceiling parts in the area of the thearea of the soffit by suitableon-site measures on the part ofthe customer. Not taken intoaccount are special environmentalconditions (for example Humidity>80%, ambient t • Specialenvironmental conditions are nottaken into account (e.g. humidity> 80 %, ambient temperature < 5°C and > 45 °C, wind loads etc.).

V EN-20211218 1 stoebich.com

Data sheetFibershield®-HC

Constructive system design (System drawing)

1 = Smoke detector 2 = Housing 3 = Guide rails 4 = Textile5 = End element 6 = Tubular motor 7 = Control module 8 = Control with operating unit9 = Manual release

Classification Size Type Fabric Wall Thickness Housing (d x h) Guide Rail

E 120 6000 x 6500 1-tlg Heliotex 120 300 235 x 320 200 x 80EW 30 6000 x 6500 1-tlg Heliotex 120 300 235 x 320 200 x 80EW 60 5000 x 5000 1-tlg Heliotex 120 300 235 x 320 200 x 80E 120 9400 x 18800 2-tlg Heliotex 120 300 400 x 610 300 x 150EW 60 9400 x 18800 2-tlg Heliotex 120 300 400 x 610 300 x 150EW 90 6800 x 4270 2-tlg Heliotex 120 300 400 x 610 300 x 150

V EN-20211218 2 stoebich.com

Data sheetFibershield®-HC

Casing installation options

Below the ceiling

Casing

Open state Closed state

V EN-20211218 3 stoebich.com

Data sheetFibershield®-HC

Guide rails

Below the ceiling

V EN-20211218 4 stoebich.com