Page 1 1/24/2018 FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE APPLICATIONS Volker Bergmann, Reinhausen Power Composites GmbH

FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

  • Upload
    others

  • View
    12

  • Download
    0

Embed Size (px)

Citation preview

Page 1: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 11/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

FIBRE REINFORCED PLASTICS

IN HIGH VOLTAGE APPLICATIONS

Volker Bergmann, Reinhausen Power Composites GmbH

Page 2: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 21/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

OVERVIEW

1. Introduction

2. Hollow core composite insulators and their application

3. Dielectric and mechanic requirements

4. FRP material solution

5. Product testing: design, sample and routine tests

Page 3: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 31/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

INTRODUCTION

Dipl.-Ing. Volker Bergmann

I Technology & Development, Electrical Applications

I Reinhausen Power Composites GmbH, Regensburg

Curriculum Vitae

I Study of Electrical Engineering, TU Berlin

I Research Scientist, High Voltage Engineering, TU Berlin

I R&D Engineer, HV Circuit Breaker, Siemens AG, Berlin

I Area Sales Manager Asia, Reinhausen Power Composites GmbH,

Regensburg

Committees

I Member of DKE/K 451: Isolatoren

I Member of IEC TC 112: Evaluation and qualification of electrical

insulating materials and systems, WG 3: Electrical Strength

I Guest in IEC TC 36, DKE/K 183

Page 4: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 41/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

TRANSMISSION AND DISTRIBUTION

Page 5: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 51/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

Structure:FRP tube: mechanical strength

Aluminum end fittings: interface

Shed profile of silicone rubber: protection andelectrical performance

Applications:Transformers-, Wall- & GIS-Bushing

Circuit Breaker – Dead Tank & Live Tank

Cable Termination

Instrument Transformer – CT, VT & CVT

Arrestor

Disconnecting Switch

Post Insulator

Capacitor

Wind Coupling

HOLLOW CORE COMPOSITE INSULATORS

Page 6: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 61/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

WHY HOLLOW CORE COMPOSITE INSULATORS?

DIMENSIONS

I Porcelain insulators available up to a length of 3 m

I For larger porcelain insulators:

I Only a few producers with sufficient capability

I Brittleness damages during production

I Broad tolerances (> 1 cm) large number of rejections

I For composites almost no limitation in length

12m

3m

[http://www.hnhddc.com/encp.htm]

Page 7: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 71/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

Porcelain-Insulator: Explosion

[Dan Windmar, Anders Holmberg, Mattias

Lundborg: Production & Application of Hollow

Composite Insulators on HV Apparatus; in 2009

World Congress on Insulators, Arresters and

Bushings]

WHY HOLLOW CORE COMPOSITE INSULATORS?

SAFETY

Page 8: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 81/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

Composite Insulator: Bullet hole

[Dan Windmar, Anders

Holmberg, Mattias

Lundborg: Production &

Application of Hollow

Composite Insulators on

HV Apparatus, in 2009

World Congress on

Insulators, Arresters and

Bushings]

WHY HOLLOW CORE COMPOSITE INSULATORS?

SAFETY

Page 9: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 91/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

WHY HOLLOW CORE COMPOSITE INSULATORS?

SEISMIC WITHSTAND

Seismic test of transformer bushing

Page 10: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 101/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

I Large dimensions

I Improved seismic withstand

I No shivers (safety)

I Adjustable material characteristics

I Weight: about 40% less than porcelain

WHY HOLLOW CORE COMPOSITE INSULATORS?

ADVANTAGES

Page 11: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 111/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

Wall Bushing for 800kV HVDC

I Horizontal

I Connects indoor and outdoor side in an

HVDC yard, e.g. valve hall.

I Operation in high polluted areas results in

long creepage distances

I Outdoor side:

I Length: 9 m

I Weight: 850 kg (insulator)

I Specified bending moment: 500 kNm

APPLICATIONS

Page 12: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 121/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

Tapered bushing on 500kV SF6 circuit breaker

Arcs in breaking chamber produce hot gases and aggressive byproducts

Short circuit currents result in high dynamic forces

Tapered design to save insulation media SF6 up to 45%

Expected life time: 30 years and more, minimum service (e.g. no cleaning)

Length: 4,5 m, weight 200 kg, specified bending moment 150 kNm

APPLICATIONS

Page 13: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 131/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

Post insulator for 800 kV HVDC coils

Coils weigh up to 40 t

Withstand to earthquakes

Length: >10 m, weight: 1100 kg, specified bending moment: 400 kNm

APPLICATIONS

Page 14: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 141/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

Oil-gas bushing insert for 800 kV power transformer

Barrier between inner oil side and outer SF6 bushing side

Immersed in SF6 results in high electric stresses and temperatures

Protection of the surface against used insulating gases and liquids

Length about 2 m, weight about 50 kg

APPLICATIONS

Page 15: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 151/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

Dielectric requirements for FRP:

I Resistance to chemical and physical degradation by water

I Volume resistivity > 1010Ωm

I Breakdown field strength ≈ 30kV/cm

Mechanic requirements for FRP:

I Glass transition temperature

Tg > Tmax + 15K

I Temperature -60°C .. +110°C (typical)

I Pressure

I Bending

REQUIREMENTS

Page 16: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 161/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

REQUIREMENTS

Further criteria for resin systems in high voltage application

I Ageing behaviour

I Compatibility to insulating media (e.g. oil, SF6)

I Moisture absorption

I Gas permability

I Tracking resistance

I Arc resistance

I Dielectric characteristics (e.g. R, loss factor)

I conductivity κ (important for DC) …

Page 17: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 171/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

SOLUTION

I Reinforcement: E-glass

I Matrix system: epoxy resin

I Superior electrical properties

I Good chemical resistance

Page 18: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 181/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

SOLUTION

Page 19: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 191/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

SOLUTION

Housing material: silicone rubber SiR

I Chemical structure: – Si – O – Si – O –

I High bonding energy: 444 kJ/mole

I High resistance against:

I UV-radiation

I Chemical attack

I High temperatures

I Hydrophobicity[http://en.wikipedia.org/wiki/Silicone_rubber]

Shed material Chemical structure Bonding energy

SiR – Si – O – Si – O – 444 kJ/mol

EVM/EPR – C – C – 345 kJ/mol

Page 20: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 201/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

PRODUCT TESTS ACCORDING IEC 61462

Design Tests

I Excessive material, electrical and mechanical tests on samples and

sample insulators to ensure suitability of design, materials and

manufacturing technology

Type Tests

I Mechanical tests to validate the customized insulator type properties

Sample Tests

I Tests on samples from the batch to verify characteristics, which depend

on manufacturing quality and materials used

Routine Tests

I Eliminate insulators with manufacturing defects

Page 21: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 211/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

MATERIAL TEST

Performed tests on cutted samples of winding tube

I High voltage test (IEC 60243-1)

I Immersed in insulating tempered mineral oil

I Short term electrical withstand and thermal breakdown

I Dye Penetration Test (IEC 62217)

I Put in colourant bath

I Color penetrates through capillars and other imperfections

I Water Diffusion Test (IEC 62217)

I Boiled in water with defined salinity (100 h)

I Current and electrical withstand

I Withstand against degradation by water [IEC 62217:2012]

Page 22: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 221/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

DESIGN TEST

IEC 61462 §7.2Thermal mechanical prestress (bending at low and high temperature)

Water immersion pre-stressing

Verification of performance byAC flashover test

Steep-front impulse voltage test

30 min AC withstand test

Visual examination

[IEC 61462:2007]

Page 23: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 231/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

BENDING, PRESSURE AND TIGHTNESS TEST

Design is mechanically specified by

I MML: maximum mechanical load in service

I MSP: maximum service pressure

Bending of insulator: force applied to top fitting

I Type test: up to 2.5 x MML

I Sample test: up to 1.5 x MML

I Routine test: 1 x MML

Inner pressure test of insulator:

I Type test: up to 4 x MSP

I Sample test: 2 x MSP

I Routine test: 2 x MSP

Tightness test of insulator:

I Pressure loss test with air or

I Accumulation bag test with helium at 1 x MSP

Acceptance criteria:

I No permanent deformation

after 1.5 x MML and 2 x MSP

I No visible damage

after 2.5 x MML and 4 x MSP

I Tightness according customer agreement

Page 24: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 241/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I

CONCLUSION

Hollow core composite insulators

I Have advantages against porcelain

I Performance / safety / dimension

I Have mechanical and dielectric requirements

I Expected lifetime >30 years, also in harsh environment

I High testing requirements (100% mechanical routine tests)

Page 25: FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE …

Page 251/24/2018FRP in high voltage application, Volker Bergmann, GFK unlimited 2018 I I