Upload
others
View
3
Download
0
Embed Size (px)
Citation preview
1 Fire Detection Overview – CFAA Technical Seminar 2019
Fire detection overview and design considerations
Presented by Tim Renaud – Regional Sales Manager for Western Canada Honeywell | Notifier
2 Fire Detection Overview – CFAA Technical Seminar 2019
3 Fire Detection Overview – CFAA Technical Seminar 2019
4 Fire Detection Overview – CFAA Technical Seminar 2019
Course Agenda
Technology overview of smoke and heat detection Design of smoke and heat detection as per CAN/ULC-S524 Information on other advanced detection technologies to
overcome some challenging applications
5 Fire Detection Overview – CFAA Technical Seminar 2019
Automatic Fire Detectors
Spot Detectors provide detection concentration in a particular location - Heat & Smoke Detectors. Line Detectors provide continuous detection along a path - Thermal Cable & Beam Detectors. Air Sampling Systems draw air through pipes to an enclosed chamber for testing. - (VESDA & Duct Detectors.
6 Fire Detection Overview – CFAA Technical Seminar 2019
Technologies used in Automatic Fire Detectors
Photoelectric Light-Scattering (Reflective) Light-Obscuring (Beam)
Ionization- largely discontinued
Thermal (heat) Duct IR
7 Fire Detection Overview – CFAA Technical Seminar 2019
Photoelectric Smoke Detectors
Light Scattering Type These detectors use a Light-Emitting
Diode (LED) that sends a beam of light into a dark chamber. A photo diode sits on the other side of a partition within the chamber.
Smoke particles entering the chamber deflect some of the light rays into the photocell. The photo cell generates a current when exposed to light, and if the current reaches a certain level, the smoke detector alarms.
8 Fire Detection Overview – CFAA Technical Seminar 2019
Light Scattering Principle Sensing Chamber
LightEmitting
Diode
Photo Diode
Partition
9 Fire Detection Overview – CFAA Technical Seminar 2019
Light Scattering Principle
10 Fire Detection Overview – CFAA Technical Seminar 2019
Heat Detectors Heat detectors are the oldest type of automatic fire
detection device. Not considered direct Life Safety devices, these detectors do contribute to the detection of a fire.
11 Fire Detection Overview – CFAA Technical Seminar 2019
Heat Detectors
Exhibit the lowest false alarm rate of all automatic fire detector devices,
Slowest-responding fire detection devices.
Best used in applications where Fast-developing, large fires are expected. Environment won't allow the use of other fire detection
devices.
12 Fire Detection Overview – CFAA Technical Seminar 2019
Heat Detectors Fixed Detectors alarm when the sensing
element reaches a certain set point. Two common setpoints are in the 135 and 195 degree F range. The Fixed element is generally a non-restorable type, and when activated, must be replaced. Rate-of-Rise Detectors respond when the
rate of temperature increase is greater than an allowable limit (eg.15 degrees in 60 secs.) They are ideally placed in stable environments. The Rate-of-Rise element is restorable when conditions return to normal.
13 Fire Detection Overview – CFAA Technical Seminar 2019
Heat Detectors Rate Compensation Type
Detector responds when temperature
of the surrounding air reaches a predetermined level, regardless of the rate of temperature rise.
Compensates for Thermal Lag. During fast rate of increase in air temperature, rate
compensation allows the detectors to operate a few degrees ahead of the setting.
Doesn’t respond to momentary fluctuations below the selected protection level, reducing false alarms
14 Fire Detection Overview – CFAA Technical Seminar 2019
Design and Application
15 Fire Detection Overview – CFAA Technical Seminar 2019
Design Issues
Device Selection Smoke - Spot versus beam versus aspiration, Heat - line versus spot. What is/are the total cost(s) of one type versus
another? How does the environment affect device selection? Does the device meet specifications and code?
Placement of Devices (where do you place smoke detectors, heat detectors)?
16 Fire Detection Overview – CFAA Technical Seminar 2019
Design Issues – Smoke Detectors Smoke detector spacing does not need to be
reduced based on ceiling height, but may be affected by beam construction.
Ceilings above 3600mm in room height shall be assessed for spacing based on fire type, growth rate, engineering judgement and mfg. recommendations.
Smoke detectors shall not exceed 83 sq. m
17 Fire Detection Overview – CFAA Technical Seminar 2019
Spot Fire Detector Placement
Smoke Detector
30’
21’
Typical areaof room protection
Maximumradius of protection
Spot detector placement is based on central mounting of a detector in a 30’X 30’ room. No area may be more than 21’from the detector.
21’
30’
70% of detector spacing by ULC
18 Fire Detection Overview – CFAA Technical Seminar 2019
Spot Detector Placement
Smoke Detector
10’
21’
Room Maximumradius of protection
Note that in this application, two detectors are not required because all areas within the room are within 21 feet of the detector.
41’
70% of detector spacing by ULC
19 Fire Detection Overview – CFAA Technical Seminar 2019
Spot Detector Placement
15’ 15’
15’ 15’
15’ 15’
15’ 15’
30’
30’
30’
30’
20 Fire Detection Overview – CFAA Technical Seminar 2019
Spot Detector Placement
Maximum distance from detector to furthest point of sidewall or corner shall not exceed 70% of detector spacing
21 Fire Detection Overview – CFAA Technical Seminar 2019
Spot Detector Placement
Maximum distance between detectors is 12.8 m
22 Fire Detection Overview – CFAA Technical Seminar 2019
Spot Detector Placement
23 Fire Detection Overview – CFAA Technical Seminar 2019
Spot Detector Placement
24 Fire Detection Overview – CFAA Technical Seminar 2019
Spot Detector Placement
A clear space of at least 450 mm shall be maintained between a spot type fire detector and any obstruction, except as specified in Clause 5.7.2.3. (Refer to Figure 4). Obstructions and protrusions not exceeding 100 mm from the ceiling need not be considered as impinging on this clear space.
25 Fire Detection Overview – CFAA Technical Seminar 2019
Spot Fire Detector Placement
Shall not be located closer than 1000mm from the blade tip of a ceiling fan or a unit heater; measured to the edge of the detector. Shall be no closer than 450mm from an air supply or exhaust outlet. Also shall not be in direct air flow.
28 Fire Detection Overview – CFAA Technical Seminar 2019
Smoke Detector placement for beams
This figure applies when both of these conditions are met
29 Fire Detection Overview – CFAA Technical Seminar 2019
Smoke Detector placement for beams
This figure applies if either of these conditions are met
30 Fire Detection Overview – CFAA Technical Seminar 2019
Smoke Detector placement for beams – NEW FOR 2014 standard
If ceiling is level and beam is <10% of ceiling height, then we use smooth ceiling spacing and detectors can be placed on ceiling or under beams.
We can now mount smoke detectors under beams in some conditions. This is new for 2014.
31 Fire Detection Overview – CFAA Technical Seminar 2019
Smoke Detector placement for beams – NEW FOR 2014 standard
If ceiling is level and beam is >10% of ceiling height, then we need to look at the width between beams.
If the width of the beams at centers is <40% of the ceiling height, we half the spacing across and smooth ceiling spacing along.
32 Fire Detection Overview – CFAA Technical Seminar 2019
Smoke Detector placement for beams – NEW FOR 2014 standard
If ceiling is level and beam is >10% of ceiling height, then we need to look at the width between beams.
If the width of the beams at centers is >40% of the ceiling height, we mount one detector in each pocket at the ceiling; not allowed under beams.
35 Fire Detection Overview – CFAA Technical Seminar 2019
Design Issues – Heat Detectors
On 3000 to 9000mm high ceilings, heat detector spacing must be reduced based on ceiling height tables as per CAN ULC S-524.
Spacing will be FURTHER reduced by beam construction.
Spacing is not required to be reduced to less than 0.4 times the spacing.
Recommend other detection method for high ceilings. Look at beam or aspiration detection.
36 Fire Detection Overview – CFAA Technical Seminar 2019
Design Issues – Heat Detectors
For Sloped Ceilings with a slope of less than 30 degrees, all spot type heat detectors shall be spaced using the spacing for the peak ceiling height.
For sloped ceilings with a slope greater than 30 degrees, the average height of all detectors shall be used other than just the peak height to determine the spacing.
*Note – Heat detectors can have different spacing ratings (ex. System Sensor has 50 feet by UL and 25 feet by FM)
37 Fire Detection Overview – CFAA Technical Seminar 2019
Heat Detector Coverage reduced by ceiling height
38 Fire Detection Overview – CFAA Technical Seminar 2019
Heat Detector Spacing Ceiling Height
(feet) Percent (%) of Listed Spacing
0 -10 10-12 12-14 14-16 16-18 18-20 20-22 22-24 24-26 26-28 28-30
100 91 84 77 71 64 58 52 46 40 34
39 Fire Detection Overview – CFAA Technical Seminar 2019
Heat Detector Temperature Ranges
Temp. Classification Detector temp range Maximum ceiling temp
Low Ordinary Intermediate High Extra High
39-57 58-79 80-121 122-162 163-204
102-134 135-174 175-250 251-324 325-400
Celsius Fahrenheit
28 47 69 111 152
82 117 156 232 306
Celsius Fahrenheit
40 Fire Detection Overview – CFAA Technical Seminar 2019
Heat Detector Spacing – Beam Contruction Ceiling
New for 2014 – If there are multiple intersecting beams, mount heats under beam at cross point of beams
41 Fire Detection Overview – CFAA Technical Seminar 2019
Heat Detector Spacing – Beam Contruction Ceiling
New in 2014 – 8.10.3.5 – Where beams are less than 300mm depth and less than 2400mm on centre, heat detectors shall be installed on the bottom of beams.
42 Fire Detection Overview – CFAA Technical Seminar 2019
Heat Detector Spacing – Beam Contruction Ceiling
This figure only applies if BOTH conditions are met
43 Fire Detection Overview – CFAA Technical Seminar 2019
Alternative Heat Detector Placement Or if beams are less than 2.4m apart and project 450mm below the ceiling
If D: H > 0.1 and W : H > 0.4, spot type heat shall be located in each beam pocket
If D : H ≤ 0.1 or W : H ≤ 0.4, spot type heat detectors shall be installed on the bottom of the beams
44 Fire Detection Overview – CFAA Technical Seminar 2019
Detector Spacing – Beam Contruction Ceiling
Summary
- If beams project no more than 100mm below the ceiling, ceiling shall be treated as smooth.
FOR HEAT and SMOKE DETECTORS
FOR SMOKE DETECTORS
- If beams project more than 100mm below the ceiling and less than 300mm and the ceiling height is less than 3600mm, 50% spacing. - If beams project more than 300mm below the ceiling, or the ceiling height is more than 3600mm - one detector in each pocket.
45 Fire Detection Overview – CFAA Technical Seminar 2019
Detector Spacing – Beam Contruction Ceiling
2014 additions FOR SMOKE DETECTORS
- If ceiling is level, beam is <10% of ceiling height = smooth ceili ng spacing and can be placed on ceiling or under beams.
- If ceiling is level, beam >10% of ceiling height AND - A. Beam spacing is >.4 Ceiling Height = On Ceiling in
each pocket - B. Beam spacing is <.4 Ceiling Height = Smooth ceiling
spacing parallel and 50% perpendicular to beams, mounted on ceiling or under beams.
46 Fire Detection Overview – CFAA Technical Seminar 2019
Detector Spacing – Beam Contruction Ceiling
Summary
FOR HEAT DETECTORS
-If beams project more than 100mm below the ceiling- 66% spacing. OR follow alternative calculation of beam depth, ceiling height ratio To calculate whether the heat detectors should be in each beam pocket OR under each beam.
-If beams project more than 450mm below the ceiling, or the beam centers are further apart than 2400mm - one detector in each pocket. -Refer to section 8.3 of CAN/ULC-S524-14 for further info on placement for detectors in many irregular ceiling spaces.
47 Fire Detection Overview – CFAA Technical Seminar 2019
Smoke Detector placement in stairs
49 Fire Detection Overview – CFAA Technical Seminar 2019
Photoelectric Beam Smoke Detectors
Light Obscuration Type
In a projected Beam Detector, alarms are generated by diffusing the projected light beam by a specified percentage of obscuration. Total beam blockage generally results in a trouble signal.
50 Fire Detection Overview – CFAA Technical Seminar 2019
Photoelectric Beam Smoke Detectors Ideally suited for high ceilings dusty and dirty environments environments that experience temperature
extremes. WATCH FOR SUNLIGHT: There should be a
minimum of 10° between the pathway of the light source and detector and the line of sight between detector and reflector.
51 Fire Detection Overview – CFAA Technical Seminar 2019
Projected Beam Principle
Smoke from the fire in the protected area diffuses the intensity of the beam at the receiver
Transmitter Receiver
52 Fire Detection Overview – CFAA Technical Seminar 2019
Single Ended Beam Detector
OSID-R by Xtralis
53 Fire Detection Overview – CFAA Technical Seminar 2019
Beam Detector
Typically, S = 60 feet (18.3 m) maximum
Install at 60cm- 90cm below ceiling
55 Fire Detection Overview – CFAA Technical Seminar 2019
Beam Detector
56 Fire Detection Overview – CFAA Technical Seminar 2019
OSID-DE Detector Open Area Smoke Imaging Detection
57 Fire Detection Overview – CFAA Technical Seminar 2019
OSID Detector
An active Emitter with wide beam LEDs transmit 2 different wavelengths IR and UV to the Imager
Intelligent software locates the specific pixels on the multi pixel CMOS Imager illuminated by the uniquely coded Emitter
Relative strengths of the 2 wavelength
signals are compared to detect smoke and discriminate against nuisance alarm particulates
Building movement and alignment is managed by Imager software without any need for controlled motor drives
58 Fire Detection Overview – CFAA Technical Seminar 2019
OSID Detector Placement and Design
59 Fire Detection Overview – CFAA Technical Seminar 2019
OSID Detector Placement and Design
60 Fire Detection Overview – CFAA Technical Seminar 2019
OSID Detector Placement and Design
Typically, S = 60 feet (18.3 m) maximum but design at 49 feet (15m)
61 Fire Detection Overview – CFAA Technical Seminar 2019
OSID Detector Placement and Design
•Unique solution with Imagers in center serving battery powered Emitters along the perimeter •Power only to the centre units
62 Fire Detection Overview – CFAA Technical Seminar 2019
Aspiration Detector Placement and Design
63 Fire Detection Overview – CFAA Technical Seminar 2019
Aspiration Detector Placement and Design
64 Fire Detection Overview – CFAA Technical Seminar 2019
Standard Detection to Very Early Warning Detection – Solutions for All Environments
ECO Gas Detection
OSID-DE - Open-area Smoke Detection
ECO
ECO-Ex
OSI-10
OSI-90
OSE-SP
OSE--SPW
OSE-HPW
VESDA — World’s Leading ASD Brand
VLC-EX VLC VLF
VLS VFT-15 VLI VLP
VLC Marine
Sensepoint XCL on VEA CO Detection on 40
addressable aspiration points!
Xtralis ASD
XAS-1 XAS-2
VESDA-E Next Generation ASD
VEU-A00-NTF VEU-A10-NTF
VEA-040-A10-NTF VEA-040-A00-NTF
VEP-A00-P-NTF
VEP-A10-P-NTF
VEP-A00-1P-NTF
Analytics
iVESDA
Direct connection to the Notifier SLC
OSID-R – Single Ended Open-area Smoke Detection
65 Fire Detection Overview – CFAA Technical Seminar 2019
Aspiration Detector – When to use?
When to use Aspiration versus regular Spot detection?
Spot detectors offer a good solution to standard spaces requiring detection between 0.5% obs/ft to 2% obs/ft. Aspiration is a better solution when: •EWFD or VEWFD is required •Accessibility to the area is limited to restricted after installation for testing and maintenance •Aesthetics are a concern •Challenging or harsh environments •Temperature extremes
67 Fire Detection Overview – CFAA Technical Seminar 2019
When to use Aspiration versus Beam detection?
•Tighter spaces between warehousing shelves •Building Shift •In rack protection possible •Higher sensitivity required in very high rooms (may compensate for dilution caused by height) •Quicker response times required •Wider range of temperatures •Sunlight issues
Aspiration Detector – When to use?
68 Fire Detection Overview – CFAA Technical Seminar 2019
Aspiration Detector – Code reference CAN/ULC-S524-14 5.10 AIR SAMPLING TYPE DETECTORS 5.10.1 Location and detector spacing of air sampling type detectors shall be in accordance with the manufacturer's documented installation instructions. 5.10.2 Air sampling type networks shall be designed on the basis of and be supported by sound dynamic fluid principles to ensure proper performance. Network design details shall include calculations showing the flow characteristics of the piping network and for each sampling point. 5.10.3 Air sampling detectors shall give a trouble signal where the airflow is outside the manufacturer's specified range. The sampling ports and in-line filter (where used) shall be kept clear in accordance with the manufacturer's documented instructions.
69 Fire Detection Overview – CFAA Technical Seminar 2019
Aspiration Detector – Code References 5.10.4 Air sampling pipe networks shall: - A Be airtight; - B Be permanently fixed; - C Be conspicuously labelled as smoke detector sampling pipe; - D Have warning signs not to disturb or alter the sampling pipe affixed at direction changes, each side of wall, floors or similar barriers and at intervals on piping not more than 6000 mm apart; and - E Have inlet ports not less than 100 mm from the wall or ceiling.
70 Fire Detection Overview – CFAA Technical Seminar 2019
Aspiration Detector Placement and Design
71 Fire Detection Overview – CFAA Technical Seminar 2019
Aspiration Detector Placement and Design
Aspiration detection can be designed to sense smoke even when stratification occurs in a large space. Recommended to provide ports for stratification when ceiling height > 30ft.
By designing the piping network with sensing holes down the walls, detection is now able to sense smoke at multiple heights.
72 Fire Detection Overview – CFAA Technical Seminar 2019
Aspiration Detector Placement and Design
Aspiration detection in smooth ceiling / pockets formed by beam depths < OR =300mm
73 Fire Detection Overview – CFAA Technical Seminar 2019
Aspiration Detector Placement and Design
Aspiration detection in ceiling pockets formed by beam depths >300mm or ceiling heights >3.6m
74 Fire Detection Overview – CFAA Technical Seminar 2019
Detection Coverage in Data Centres
NFPA Regulatory Requirements
VEWFD EWFD SFD
Sample Port Spacing
200 sq. ft. (18.5 sq. m)
400 sq. ft. (37 sq. m)
900 sq. ft. (84 sq. m)
Transport Time 60 Seconds 90 Seconds 120 Seconds
Pre-Alarm 0.2%obs/ft. (0.6 obs/m)
N/A N/A
Alarm 1.0% obs/ft.
(3.1% obs/m)
1.5% obs/ft. (4.6% obs/m)
3.2% obs/ft. (10% obs/m)
76 Fire Detection Overview – CFAA Technical Seminar 2019
QUESTIONS?
Tim Renaud – Regional Sales Manager Notifier – Western Canada
Leaders in Life. Safety. Technology. Leaders in Life. Safety. Technology.
Thank You for Attending!