Upload
lynguyet
View
245
Download
4
Embed Size (px)
Citation preview
©NFPA 2008
Fire Safety Analysis Manual For Conducting the Fire Safety Analysis
Required by NFPA 58
OSINERGMIN Forum
Presented by:
Theodore Lemoff Principal Gases Engineer, NFPA
Lima, Peru December, 2009
Fire Safety Analysis for LP-Gas Storage FacilitiesPresented by Theodore Lemoff, NFPA
OSINERG Forum, Lima
Copyright © 2009, Propane Education and Research Council. All Rights Reserved. 1December, 2009
Fire Safety Analysis Manual Fire Safety Analysis Manual forfor
LPLP--Gas Storage FacilitiesGas Storage Facilities
Copyright © 2005 Propane Education & Research Council.
National Fire Protection AssociationNational Fire Protection AssociationNational Propane Gas AssociationNational Propane Gas Association
Funded by a Funded by a Propane Education & Research Council GrantPropane Education & Research Council Grant
Chapters 1Chapters 1--33•• First 3 chaps. provide history, background, & First 3 chaps. provide history, background, &
general overviewgeneral overview•• IntroductionIntroduction•• Container Safety FeaturesContainer Safety Features
Working together in safety
2Copyright © 2005 Propane Education & Research Council.
•• Container Safety FeaturesContainer Safety Features•• FSA ElementsFSA Elements
•• Develops basic understandingDevelops basic understanding•• Concepts, drivers, & requirementsConcepts, drivers, & requirements
Ch. 1-3
Fire Safety AnalysisFire Safety Analysis•• First required in 1976First required in 1976
•• Plants of 4,000 gal. Total Bulk StoragePlants of 4,000 gal. Total Bulk Storage•• Can be required by officialsCan be required by officials
•• Change in 2001Change in 2001
Working together in safety
3Copyright © 2005 Propane Education & Research Council.
Change in 2001Change in 2001•• Required to be written for all plants, 4000 gal. Required to be written for all plants, 4000 gal.
Total StorageTotal Storage•• 3 Years3 Years
•• Manual developed by NFPA & NPGAManual developed by NFPA & NPGA•• PERC fundingPERC funding
Ch. 1.1
What is an FSA?What is an FSA?An audit of a propane plant’s safety features: An audit of a propane plant’s safety features: •• Assessment of means to minimize Assessment of means to minimize
inadvertent propane releasesinadvertent propane releasesF t t iF t t i
Working together in safety
4Copyright © 2005 Propane Education & Research Council.
•• From storage containersFrom storage containers•• During transfer operationsDuring transfer operations
•• Evaluates local emergency response Evaluates local emergency response •• Analysis of potential hazard exposures from Analysis of potential hazard exposures from
and to neighboring propertiesand to neighboring properties
Ch. 1.1
The NeedThe Need•• First required in the 1976 Edition of NFPA 58First required in the 1976 Edition of NFPA 58
•• For plants with > 4,000 gal. propane storageFor plants with > 4,000 gal. propane storage•• “Pullaway” incidents occurred prior to 1976“Pullaway” incidents occurred prior to 1976
•• ESV DevelopedESV Developed
Working together in safety
5Copyright © 2005 Propane Education & Research Council.
•• ESV DevelopedESV Developed•• Recognition that equipment could fail led to FSARecognition that equipment could fail led to FSA
•• Derailments had resulted in BLEVE’sDerailments had resulted in BLEVE’s•• Need to increase safety requirementsNeed to increase safety requirements
•• Required for new plants onlyRequired for new plants only
Ch. 1.1
New RequirementsNew Requirements•• NFPA 58, 2001 edition required FSA for all NFPA 58, 2001 edition required FSA for all
propane plants (> 4,000 gal.)propane plants (> 4,000 gal.)•• Existing FSA’s are OKExisting FSA’s are OK•• Need for Manual became apparentNeed for Manual became apparent
Working together in safety
6Copyright © 2005 Propane Education & Research Council.
•• Need for Manual became apparentNeed for Manual became apparent
•• PERC funds manual by NFPA & NPGAPERC funds manual by NFPA & NPGA
Ch. 1.1
Fire Safety Analysis for LP-Gas Storage FacilitiesPresented by Theodore Lemoff, NFPA
OSINERG Forum, Lima
Copyright © 2009, Propane Education and Research Council. All Rights Reserved. 2December, 2009
Incident DataIncident Data•• NFPA data shows few propane plant fires:NFPA data shows few propane plant fires:
•• 19941994--1998: 49 fires/year 1998: 49 fires/year -- all US plantsall US plants•• Average 1 civilian death, 5 civilian injuriesAverage 1 civilian death, 5 civilian injuries•• Annual $754,000 damageAnnual $754,000 damage
Working together in safety
7Copyright © 2005 Propane Education & Research Council.
Annual $754,000 damage Annual $754,000 damage
•• 1999: all US plants1999: all US plants•• 58 fires, 4 injuries58 fires, 4 injuries•• $722,000 damage$722,000 damage
Ch. 1.4
PhilosophyPhilosophy•• Product control prevents accidentsProduct control prevents accidents
•• Excess flow valves: Good, but not perfectExcess flow valves: Good, but not perfect•• Check valves: Good, but not perfectCheck valves: Good, but not perfect
Working together in safety
8Copyright © 2005 Propane Education & Research Council.
Experience: Tanks don’t fail Experience: Tanks don’t fail → → piping systems dopiping systems do•• Vehicle impact & piping system designVehicle impact & piping system design
•• Newark, 1949: Pipe break due to stressNewark, 1949: Pipe break due to stress•• Sanford NC 1997: Hose & check valve failureSanford NC 1997: Hose & check valve failure•• Truth or Consequences NM 2001, pizza truck hit pipingTruth or Consequences NM 2001, pizza truck hit piping
Ch. 2
Kingman, ArizonaKingman, Arizona•• July 3, 1973July 3, 1973
•• Fire at railcar unloading area of a bulk plantFire at railcar unloading area of a bulk plant•• Plant conformed to NFPA 58 reqs., at the timePlant conformed to NFPA 58 reqs., at the time
Working together in safety
9Copyright © 2005 Propane Education & Research Council.
•• BLEVE resulted in 13 deathsBLEVE resulted in 13 deaths•• 12 firefighters12 firefighters•• Plant managerPlant manager
•• The significant event that led to NFPA 58 safety The significant event that led to NFPA 58 safety improvementsimprovements
Ch. 2.1
Product Control EvolutionProduct Control Evolution•• State of the artState of the art
•• 1970 1970 -- Valves, check valves, excess flow valvesValves, check valves, excess flow valves•• 19761976 Emergency shutoff valves (by 1980)Emergency shutoff valves (by 1980)
Working together in safety
10Copyright © 2005 Propane Education & Research Council.
•• 1976 1976 -- Emergency shutoff valves (by 1980)Emergency shutoff valves (by 1980)•• 1992 1992 -- Internal valves (optional)Internal valves (optional)•• 2001 2001 -- Internal valves (mandatory + 10yr retrofit)Internal valves (mandatory + 10yr retrofit)
Ch. 2.1
Rail SolutionsRail Solutions•• By 1980, all liquefied flammable gas railcars By 1980, all liquefied flammable gas railcars
required (by DOT) to have:required (by DOT) to have:•• Thermal protection Thermal protection •• Head shieldsHead shields
Working together in safety
11Copyright © 2005 Propane Education & Research Council.
•• Head shieldsHead shields•• Shelf couplersShelf couplers
•• Railroad maintenance improved Railroad maintenance improved •• Minimize derailmentsMinimize derailments
Ch. 2.1
FSA ElementsFSA Elements•• Effectiveness of product controlEffectiveness of product control•• Site hazards, including congestionSite hazards, including congestion•• Exposure to neighbors & impact of Exposure to neighbors & impact of
i hb i i d t i l ti it l ti hb i i d t i l ti it l t
Working together in safety
12Copyright © 2005 Propane Education & Research Council.
neighboring industrial activity on plantneighboring industrial activity on plant•• Effectiveness of local fire department Effectiveness of local fire department •• Water supply calculations & availabilityWater supply calculations & availability•• Verify compliance with NFPA 58Verify compliance with NFPA 58
•• Corrective actions for any deficienciesCorrective actions for any deficiencies
Ch. 3
Fire Safety Analysis for LP-Gas Storage FacilitiesPresented by Theodore Lemoff, NFPA
OSINERG Forum, Lima
Copyright © 2009, Propane Education and Research Council. All Rights Reserved. 3December, 2009
Performing an FSA:Performing an FSA:How is this done?How is this done?
•• Tables and FormsTables and Forms
•• Tables identify requirements & allow entriesTables identify requirements & allow entries
•• Forms Forms -- different tanks w/ req. appurtenancesdifferent tanks w/ req. appurtenances
Working together in safety
13Copyright © 2005 Propane Education & Research Council.
q ppq pp•• Check off presence or absence of appurtenancesCheck off presence or absence of appurtenances•• Tabulate information on formsTabulate information on forms•• Forms identify dates when newer requirements were Forms identify dates when newer requirements were
added; Older plants are exempt from some itemsadded; Older plants are exempt from some items
•• Forms for other requirementsForms for other requirements
Ch. 3.1
Using the ManualUsing the Manual•• Use Forms in Chapter 4 to:Use Forms in Chapter 4 to:
•• Gather data on volume of LPGather data on volume of LP--Gas stored & other Gas stored & other information pertinent to facilityinformation pertinent to facility
Working together in safety
14Copyright © 2005 Propane Education & Research Council.
information pertinent to facilityinformation pertinent to facility
•• Perform simple calculations & determine whether Perform simple calculations & determine whether facility requires FSAfacility requires FSA
Table 3.1
Using the ManualUsing the Manual•• Use forms in Chapter 5 to:Use forms in Chapter 5 to:
•• Evaluate product control & safety featuresEvaluate product control & safety features•• Verify appurtenance requirementsVerify appurtenance requirements
Working together in safety
15Copyright © 2005 Propane Education & Research Council.
•• Verify appurtenance requirementsVerify appurtenance requirements•• Verify valves on transfer piping per CodeVerify valves on transfer piping per Code•• Verify optional redundant & failVerify optional redundant & fail--safe product controlsafe product control•• Verify optional low emission transfer equipmentVerify optional low emission transfer equipment
Table 3.1
Using the ManualUsing the Manual•• Use Forms in Chapter 6 to:Use Forms in Chapter 6 to:
•• Analyze protection vs. local conditions of hazardAnalyze protection vs. local conditions of hazard•• Physical protection of containers & pipingPhysical protection of containers & piping
•• Verify ignition source control reqsVerify ignition source control reqs
Working together in safety
16Copyright © 2005 Propane Education & Research Council.
•• Verify ignition source control reqs.Verify ignition source control reqs.•• Verify tank separation distances are met Verify tank separation distances are met •• Verify separation distancesVerify separation distances
•• Between containers, transfer points & exposuresBetween containers, transfer points & exposures•• Verify requirements for special protectionVerify requirements for special protection
•• Where installedWhere installed
Table 3.1
Using the ManualUsing the Manual•• Ch. 7 evaluates exposure to offCh. 7 evaluates exposure to off--site propertysite property
•• Effects of unanticipated leakageEffects of unanticipated leakage
•• Credible release cases providedCredible release cases provided
Working together in safety
17Copyright © 2005 Propane Education & Research Council.
Credible release cases providedCredible release cases provided•• Bobtail & transport hose failureBobtail & transport hose failure•• Piping failure (breakage & corrosion)Piping failure (breakage & corrosion)•• Pressure relief valvePressure relief valve
•• Evaluate exposure to and from offEvaluate exposure to and from off--site propertiessite properties
Table 3.1
Using the ManualUsing the Manual•• Ch. 8 evaluates: Ch. 8 evaluates:
•• Local fire response & water supplyLocal fire response & water supply
•• Fire Departments Data FormFire Departments Data Form
Working together in safety
18Copyright © 2005 Propane Education & Research Council.
•• Fire Departments Data FormFire Departments Data Form•• Evaluate response timeEvaluate response time•• Evaluate water supply needsEvaluate water supply needs
•• Identify water availabilityIdentify water availability•• Talk to FDTalk to FD
Table 3.1
Fire Safety Analysis for LP-Gas Storage FacilitiesPresented by Theodore Lemoff, NFPA
OSINERG Forum, Lima
Copyright © 2009, Propane Education and Research Council. All Rights Reserved. 4December, 2009
Using the ManualUsing the ManualCompile the results from Ch. 4 Compile the results from Ch. 4 –– 88
•• Existing:Existing: Results to local responders for Results to local responders for inclusion in their emergency planninginclusion in their emergency planning
•• Proposed:Proposed: Refer to Ch 9Refer to Ch 9
Working together in safety
19Copyright © 2005 Propane Education & Research Council.
Proposed:Proposed: Refer to Ch. 9Refer to Ch. 9•• If offIf off--site property exposure is concern site property exposure is concern -- optionsoptions•• If local FD proves inadequate, options are:If local FD proves inadequate, options are:
•• Meet w/ local fire departmentMeet w/ local fire department•• Consider special protection, redundant failConsider special protection, redundant fail--safe, low safe, low
emission transfer, & other alternatives in Table 9.1emission transfer, & other alternatives in Table 9.1•• Provide plant fire equipment or a fire brigadeProvide plant fire equipment or a fire brigade
Table 3.1
Using the ManualUsing the Manual•• Fire Safety Analysis examplesFire Safety Analysis examples
•• Four examples provided:Four examples provided:•• 44 -- 1 800 gal containers at a rural industrial plant1 800 gal containers at a rural industrial plant
Working together in safety
20Copyright © 2005 Propane Education & Research Council.
4 4 -- 1,800 gal containers at a rural industrial plant1,800 gal containers at a rural industrial plant•• 18,000 gal container at a user site18,000 gal container at a user site•• 18,000 gal container at a small urban bulk plant18,000 gal container at a small urban bulk plant•• 4 4 -- 30,000 gal containers at a bulk plant30,000 gal containers at a bulk plant
•• Examples illustrate use of figures & formsExamples illustrate use of figures & forms
Ch. 4-9
Chapter 4Chapter 4Facility InformationFacility Information
•• Basic information on LPBasic information on LP--Gas facility recordedGas facility recorded
Working together in safety
21Copyright © 2005 Propane Education & Research Council.
•• Decision made on whether FSA is neededDecision made on whether FSA is needed•• Perform simple calculations & determine whether Perform simple calculations & determine whether
facility requires FSAfacility requires FSA
•• If so, proceedIf so, proceed
Ch. 4
Form 4.1: Initial Data on the LP-Gas Facility
A B CItem # Information Item Data
1 LP-Gas Plant Owner or Operator
Working together in safety
22Copyright © 2005 Propane Education & Research Council.
p2 Contact Name: 3 Contact Tel. & Fax Numbers
4 Contact Email Address5 Mailing
AddressStreet 1: Street 2:
Form 4.1
Form 4.2: Facility Storage Capacity
A B C D
Item # Individual Container
Water Capacity (wc) (gallons)
Number of containers
Total Water Capacity (wc)
of each container size (gallons)
500
Working together in safety
23Copyright © 2005 Propane Education & Research Council.
1,000 2,000 4,000 10,000 18,000 30,000
1
60,000
2 Aggregate Water Capacity
Form 4.2
Form 4.3 (1 of 3)Add’l Information on LP-Gas FacilityExisting; Built to NFPA 58 Edition____ Proposed
a) Name of Facility: ________________________________ b) Type LP-Gas Plant: Commercial Industrial Bulkc) Facility Location: Rural Area Suburban
City Commercial City Industrial
Working together in safety
24Copyright © 2005 Propane Education & Research Council.
d) Facility neighbors: Agri. fields Commercial Bldgs.Flammable Liquids Storage Industrial Activity (metal fab., cutting & welding, etc)Manufacturing Others (explain) ______________
e) Plant Address: _________________________________f) Landmarks, if any: ______________________________
Form 4.3
Fire Safety Analysis for LP-Gas Storage FacilitiesPresented by Theodore Lemoff, NFPA
OSINERG Forum, Lima
Copyright © 2009, Propane Education and Research Council. All Rights Reserved. 5December, 2009
Form 4.3 (2 of 3)Add’l Information on LP-Gas Facility
g) LP-Gas liquid supply by: (Check all that apply)Bobtail Truck Transport Rail Tank Car Pipeline
h) LP-Gas Distribution by: (Check all that apply) Bobtail Transport Vapor Piping Liquid Piping Dispensing
Working together in safety
25Copyright © 2005 Propane Education & Research Council.
i) Number of vehicle entrances: 1 2 2+
j) Type of access roads to the plant: Rural City or Town Highway
Entrance 1 Dirt road Gravel road PavedEntrance 2 Dirt road Gravel road Paved (One check per line)
Form 4.3
Form 4.3 (3 of 3)Add’l Information on LP-Gas Facility
k) Staff presence:Not staffed Only during transfer ops.Staffed always (24/7) Only during business hrs.Other (Explain) ____________________________
Working together in safety
26Copyright © 2005 Propane Education & Research Council.
l) Location & dist. to Institutional Occupancies, within 250______________________________________________________________________________________________________________________________________________________
m) Overview plot plan of the facility attached? Yes No
Form 4.3
Chapter 5Chapter 5Analysis of Product Control Measures in Analysis of Product Control Measures in
Container and Transfer PipingContainer and Transfer Piping
•• Appurtenance requirements for containerAppurtenance requirements for container
Working together in safety
27Copyright © 2005 Propane Education & Research Council.
•• Appurtenance requirements for container Appurtenance requirements for container based on size & configured service typesbased on size & configured service types
•• Forms provided to document product control Forms provided to document product control equipment for containers & transfer pipingequipment for containers & transfer piping
Ch. 5
Container AppurtenancesContainer Appurtenances
Perform the Perform the analysis specified analysis specified
i S tii S ti
If the LPIf the LP--Gas facility contains individualGas facility contains individualcontainers in the volume range (gallons wc)containers in the volume range (gallons wc)
Table 5.1: Container Size Dependent EvaluationsTable 5.1: Container Size Dependent Evaluations
Working together in safety
28Copyright © 2005 Propane Education & Research Council.
in Sectionin Section
00 2,0002,000 5.1.15.1.12,0002,000 4,0004,000 5.1.25.1.24,0004,000 5.1.35.1.3
Greater thanGreater than And Less than or And Less than or equal toequal to
Table 5.1
Form 5.1: Compliance with Code Requirements for Appurtenances on Containers of 2,000 Gallons Water Capacity or Less
A B C D E
Container #
Service Configuration
Sub Figure (in Figure 5-1)
Number of Product Release Control Appurtenances
NFPA 58 (2008) Section
ReferenceRequired by
NFPA 58 (applicable
Installed on the Container
Working together in safety
29Copyright © 2005 Propane Education & Research Council.
edition)1
5.7.4.1 and Table 5.7.4.1
23456
Form 5.1
Container Appurtenance Container Appurtenance Requirements Requirements ≤≤ 2,000 gal.2,000 gal.
Working together in safety
30Copyright © 2005 Propane Education & Research Council.
Figure 5-1A
Fire Safety Analysis for LP-Gas Storage FacilitiesPresented by Theodore Lemoff, NFPA
OSINERG Forum, Lima
Copyright © 2009, Propane Education and Research Council. All Rights Reserved. 6December, 2009
Container Appurtenance Container Appurtenance Requirements Requirements ≤≤ 2,000 gal.2,000 gal.
Working together in safety
31Copyright © 2005 Propane Education & Research Council.
Figure 5-1B
Container Appurtenance Container Appurtenance Requirements Requirements ≤≤ 2,000 gal.2,000 gal.
Working together in safety
32Copyright © 2005 Propane Education & Research Council.
Figure 5-1C
Container Appurtenance Container Appurtenance Requirements Requirements ≤≤ 2,000 gal.2,000 gal.
Working together in safety
33Copyright © 2005 Propane Education & Research Council.
Figure 5-1D
Container Appurtenance Container Appurtenance Requirements Requirements ≤≤ 2,000 gal.2,000 gal.
Vertical container Vertical container with vapor devicewith vapor device
Working together in safety
34Copyright © 2005 Propane Education & Research Council.
Figure 5-1E
Form 5.2: Compliance with Code Requirements for Appurtenances on Containers of Water Capacity 2,001
Gallons Through 4,000 Gallons Used in Residences and Commercial Facilities
A B C D E
Container #
Service Configuration
Sub Figure (in Figure 5-1)
Number of Product Release Control Appurtenances
NFPA 58 (2008) Section
ReferenceRequired by
NFPA 58 (applicable
Installed on the Container
Working together in safety
35Copyright © 2005 Propane Education & Research Council.
(in Figure 5-1) (applicable edition)
the Container
1
5.7.4.1 and Table 5.7.4.1
23456
Form 5.2
Form 5.3:Compliance with Code Requirements for Appurtenances on Containers of Water Capacity
2,001 Gallons Through 4,000 Gallons Used in Bulk Plants and Industrial Plants
A B C D E F G
Container#
LP-Gas inlet to and outlet from the container**
Fig #
Total Number of Product Release
Control Appurtenances
NFPA 58 (2008)
Section Req’ by
Working together in safety
36Copyright © 2005 Propane Education & Research Council.
Form 5.3
the container ReferenceReq by NFPA 58
Installed
1 Vapor
Inlet 5-2 See Table
5.7.4.2 Outlet 5-3
Liquid Inlet 5-4 Outlet 5-5
Fire Safety Analysis for LP-Gas Storage FacilitiesPresented by Theodore Lemoff, NFPA
OSINERG Forum, Lima
Copyright © 2009, Propane Education and Research Council. All Rights Reserved. 7December, 2009
Container Appurtenance Requirements Container Appurtenance Requirements 2,001 through 4,000 gal.2,001 through 4,000 gal.
Vapor InletVapor InletConfigurationsConfigurations
3 Configurations3 Configurations
Working together in safety
37Copyright © 2005 Propane Education & Research Council.
Figure 5-2
gg
Container Appurtenance Requirements Container Appurtenance Requirements 2,001 through 4,000 gal.2,001 through 4,000 gal.
Vapor InletVapor InletConfigurationsConfigurations
Working together in safety
38Copyright © 2005 Propane Education & Research Council.
Figure 5-2
Container Appurtenance Requirements Container Appurtenance Requirements 2,001 through 4,000 gal.2,001 through 4,000 gal.
Vapor OutletVapor OutletConfigurationsConfigurations
Working together in safety
39Copyright © 2005 Propane Education & Research Council.
Figure 5-3
Container Appurtenance Requirements Container Appurtenance Requirements 2,001 through 4,000 gal.2,001 through 4,000 gal.
Liquid InletLiquid InletConfigurationsConfigurations
Working together in safety
40Copyright © 2005 Propane Education & Research Council.
Figure 5-4
Container Appurtenance Requirements Container Appurtenance Requirements 2,001 through 4,000 gal.2,001 through 4,000 gal.
Liquid InletLiquid InletConfigurationsConfigurations
Working together in safety
41Copyright © 2005 Propane Education & Research Council.
Figure 5-4
Container Appurtenance Requirements Container Appurtenance Requirements 2,001 through 4,000 gal.2,001 through 4,000 gal.
Liquid OutletLiquid OutletConfigurationsConfigurations
Working together in safety
42Copyright © 2005 Propane Education & Research Council.
Figure 5-5
Fire Safety Analysis for LP-Gas Storage FacilitiesPresented by Theodore Lemoff, NFPA
OSINERG Forum, Lima
Copyright © 2009, Propane Education and Research Council. All Rights Reserved. 8December, 2009
Form 5.4: Compliance with Code Requirements for Appurtenances on Containers Having a Water Capacity
Greater Than 4,000 Gallons Used inBulk Plants and Industrial Plants
AA BB CC DD EE FF GG
ContainerContainer
##
LPLP--Gas inlet to and Gas inlet to and outlet from the outlet from the
container**container**
Figure Figure
##
Total Number of Product Total Number of Product Release Control Release Control AppurtenancesAppurtenances
NFPA 58 NFPA 58 Section Section
Reference Reference
(2008 (2008 edition)edition)
Required by Required by NFPA 58 NFPA 58
(Applicable (Applicable Edition)Edition)
Installed Installed on the on the
ContainerContainer
Working together in safety
43Copyright © 2005 Propane Education & Research Council.
Form 5.4
Edition)Edition)
11
VaporVaporInletInlet 55--22
See Table See Table
5.7.4.25.7.4.2
OutletOutlet 55--33
LiquidLiquidInletInlet 55--66
OutletOutlet 55--77
22
VaporVaporInletInlet 55--22
OutletOutlet 55--33
LiquidLiquidInletInlet 55--66
OutletOutlet 55--77
Container Appurtenance Container Appurtenance Requirements > 4,000 gal.Requirements > 4,000 gal.
Liquid InletLiquid InletConfigurationsConfigurations
C fi tiC fi ti
Working together in safety
44Copyright © 2005 Propane Education & Research Council.
Configuration Configuration # 1, # 2, #4, or # 5# 1, # 2, #4, or # 5
Required After Required After July 1, 2011July 1, 2011
Figure 5-6A
Container Appurtenance Container Appurtenance Requirements > 4,000 gal.Requirements > 4,000 gal.
Questions to ask?Questions to ask?
1. Does the internal valve have thermal shutoff feature 1. Does the internal valve have thermal shutoff feature within 5 ft of the valve?within 5 ft of the valve?
Working together in safety
45Copyright © 2005 Propane Education & Research Council.
YesYes NoNo
2. Is a remote shutdown station for the internal valve 2. Is a remote shutdown station for the internal valve located not less than 25 ft and not more than 100 ft from located not less than 25 ft and not more than 100 ft from the liquid transfer point?the liquid transfer point?
YesYes NoNo
Figure 5-6A
Container Appurtenance Container Appurtenance Requirements > 4,000 gal.Requirements > 4,000 gal.
Liquid InletLiquid InletConfigurationsConfigurations
Working together in safety
46Copyright © 2005 Propane Education & Research Council.
Figure 5-6B
Container Appurtenance Container Appurtenance Requirements > 4,000 gal.Requirements > 4,000 gal.
Liquid InletLiquid InletConfigurationsConfigurations
ConfigurationConfiguration
Working together in safety
47Copyright © 2005 Propane Education & Research Council.
Configuration Configuration # 1, # 2, #4, or # 5# 1, # 2, #4, or # 5
Required After Required After July 1, 2011July 1, 2011
Figure 5-6B
Container Appurtenance Container Appurtenance Requirements > 4,000 gal.Requirements > 4,000 gal.
Liquid OutletLiquid OutletConfigurationsConfigurations
Working together in safety
48Copyright © 2005 Propane Education & Research Council.
1.1. Does the internal valve have thermal shutoff feature within 5 ft of Does the internal valve have thermal shutoff feature within 5 ft of the valve?the valve? YesYes NoNo
2.2. Is a remote shutdown station for the internal valve located not less Is a remote shutdown station for the internal valve located not less than 25 ft and not more than 100 ft from the liquid transfer point?than 25 ft and not more than 100 ft from the liquid transfer point?
YesYes NoNo
Figure 5-7A
Fire Safety Analysis for LP-Gas Storage FacilitiesPresented by Theodore Lemoff, NFPA
OSINERG Forum, Lima
Copyright © 2009, Propane Education and Research Council. All Rights Reserved. 9December, 2009
Container Appurtenance Container Appurtenance Requirements > 4,000 gal.Requirements > 4,000 gal.
Liquid OutletLiquid OutletConfigurationsConfigurations
Configurations Configurations #1 #3#1 #3
Working together in safety
49Copyright © 2005 Propane Education & Research Council.
#1 or #3 #1 or #3 Required for new Required for new
installations & for all installations & for all installations after installations after
July 1, 2011July 1, 2011
Figure 5-7B
Transfer PipingTransfer PipingPrevent gas release following piping failurePrevent gas release following piping failure
Emergency shutoff valves; Check valves; Emergency shutoff valves; Check valves; Remote operating locations; Breakaway provisionsRemote operating locations; Breakaway provisions
Working together in safety
50Copyright © 2005 Propane Education & Research Council.
Section 5.2
Form 5.5:Requirements for Transfer Lines of 1½ inch Diameter or Larger,
Liquid-into-ContainersA B C D E F
# Appurtenance Appurtenance
Provided with the Feature
Installed in the
facility?
NFPA 58 (2008)
Section ReferenceYes No
Within 20 ft of the nearest end of the hose or swivel-type
6.12.2
Working together in safety
51Copyright © 2005 Propane Education & Research Council.
Form 5.5
1 Emergency
Shutoff Valve (ESV)
hose or swivel type connections Automatic shutoff through thermal (fire) actuation, melting point < 250 oF
6.12.6
Temperature sensitive element (fusible link) 5 ft from the nearest end of the hose or swivel type piping
6.12.6
Form 5.5:Requirements for Transfer Lines of 1½ inch Diameter or Larger,
Liquid-into-Containers
# Appurtenance Appurtenance Provided with the Feature
Installed in the
facility? NFPA 58
(2008) Section
Reference Yes No
1Emergency
Shutoff Valve
Manual shutoff at ESV location. 6.12.10(1)
Manual shutoff - remote, 25 – 100’. from ESV 6.12.10(2)
ESV on each leg of multi leg piping, each connected to a hose or a swivel on one side and
6.12.5
6 18 2 6(1)
Working together in safety
52Copyright © 2005 Propane Education & Research Council.
Form 5.5
(ESV) connected to a hose or a swivel on one side and to a header > 1½ inch in diameter on the other.
6.18.2.6(1)
Breakaway stanchion is provided so pull-away break on the hose or swivel side & retain intact the valves & piping on plant side
6.12.8
2 Back flow
Check Valve (BCK)**
Downstream of the hose or swivel connection
6.12.8
BCK is designed for this specific application 6.12.4
A BCK is installed on each leg of a multi leg piping connected to a hose or a swivel on one side & to a header of >1½” on the other
6.12.5
Breakaway stanchion so that in a pull-away break will occur on the hose or swivel side & retain the valves and piping on the plant side
6.12.8
Form 5.6:Requirements for Transfer Lines of 1½ inch Diameter or Larger,
Liquid Withdrawal from ContainersA B C D E F
# Appurtenance Appurtenance Provided with the Feature
Installed in the
facility?
NFPA 58 (2008)
Section Reference Yes No
20’ from the end of the hose or swivel. 6.12.2 Automatic shutoff thorough thermal (fire) actuation, melting point < 250 oF 6.12.6
Temperature sensitive element (fusible link) 5 ft from the end of the hose or 6 12 6
Working together in safety
53Copyright © 2005 Propane Education & Research Council.
Form 5.6
1 Emergency Shutoff Valve (ESV)
link) 5 ft from the end of the hose or swivel
6.12.6
Manual shutoff at E SV location. 6.12.10(1) Manual shutoff 25’ – 100’ from the ESV. 6.12.10(2) ESV on each leg of multi leg piping, connected to a hose or a swivel on one side and to a header > 1½” diam. on the other.
6.12.5 6.12.2.6(1)
Breakaway stanchion so that in a pull-away break will occur on the hose or swivel side & retain valves and piping on the plant side.
6.12.8
Number of ESV’s in liquid service
Form 5.7: Requirements for Vapor Transfer Lines 1¼-inch Diameter or Larger
A B C D E F
# Appurtenance Appurtenance Provided with the Feature
Installed in the
facility?
NFPA 58 (2008)
Section Reference Yes No
20’ from the end of the hose or swivel. 6.12.2 Automatic shutoff thorough thermal (fire) actuation, melting point < 250 oF 6.12.6
Temperature sensitive element (fusible
Working together in safety
54Copyright © 2005 Propane Education & Research Council.
Form 5.7
1Emergency Shutoff Valve (ESV)
link) 5 ft from the end of the hose or swivel
6.12.6
Manual shutoff at ESV location. 6.12.10(1) Manual shutoff 25’ – 100’ from the ESV 6.12.10(2) ESV on each leg of multi leg piping, connected to a hose or a swivel on one side and to a header > 1½” diam. on the other
6.12.5 6.18.2.6(1)
Breakaway stanchion so that in a pull-away break will occur on the hose or swivel side & retain valves and piping on the plant side
6.12.8
Fire Safety Analysis for LP-Gas Storage FacilitiesPresented by Theodore Lemoff, NFPA
OSINERG Forum, Lima
Copyright © 2009, Propane Education and Research Council. All Rights Reserved. 10December, 2009
Form 5.8: Evaluation of Redundant Fail-Safe Design (1 of 2)
A B C D E F
# Description FeaturesInstalled in the facility? NFPA 58 (2008)
Section ReferenceYes No
1 Container Sizes for which the appurtenances are provided
Redundant Fail-Safe equipment and Low Emission transfer lines are provided for each container of water capacity 2,001 gal through 30,000 gal
6.26.3 and 6.26.4
2 LIQUID OR VAPOR WITHDRAWAL
Internal Valve with integral excess flow valve or excess flow protection 6.26.3.1
Working together in safety
55Copyright © 2005 Propane Education & Research Council.
Form 5.8
2 (1-1/4 in. or larger)Positive Shutoff Valve installed as close as possible to the Internal Valve 6.26.3.4
3 LIQUID OR VAPOR INLET
Internal Valve with integral excess flow valve or excess flow protection or Back Flow Check valve 6.26.3.5
Positive Shutoff Valve installed as close as possible to the Internal Valve or the back flow check valve 6.26.3.5
4 Railcar Transfer
Flow Into or Out of Railroad tank car
Internal Valve installed in the transfer hose or the swivel-type piping at the tank car end
6.18.2.6 (1)and 6.26.4.1
Flow Only into railroad tank car
Internal valve or backflow check valve installed in the transfer hose or the swivel-type piping at the tank car end
6.18.2.6 (2) and 6.26.4.1
Form 5.8: Evaluation of Redundant Fail-Safe Design (2 of 2)
A B C D E F
# Description FeaturesInstalled in the facility? NFPA 58 (2008)
Section ReferenceYes No
5 Cargo Tank Transfer Protection provided in accordance with 6.24.4.1 6.26.4.1
6 Automatic closure of all primary valves Actuated by Fire Detection 6.26.4.2
Working together in safety
56Copyright © 2005 Propane Education & Research Council.
Form 5.8
6 p y(IV & ESV) in an Emergency
Actuated by a hose pull-away due to vehicle motion 6.26.4.2
7 Manually operated remote shutdown of IV and ESV
Remote shutdown station within 15 ft of the point of transfer? 6.26.4.3 (A)
Another remote shutdown station between 25 ft and 100 ft ofthe transfer point? 6.26.4.3 (B)
Shutdown stations will shut down electrical power supply, ifany, to the transfer equipment and primary valves? 6.26.4.3
Signs complying with the requirements of 6.24.4.3 (C)provided? 6.26.4.3 (C)
Form 5.9: Evaluation of Low Emission Transfer Equipment
A B C D E F
# Description FeaturesInstalled in the
facility?NFPA 58 (2008)
SectionReferenceYes No
1Transfer into Cylinders or ASME Containers on Vehicles
Delivery Nozzle and Filler Valve- Max. Liquid Release after transfer of 4 cc.
Fixed Maximum Liquid Level Gage not used during transfer operations
6.26.5.1 (B)
does not exceed 4 cc (0.24 in3)
Working together in safety
57Copyright © 2005 Propane Education & Research Council.
Form 5.9
2
Transfer into Stationary ASME Containers. Delivery valve and nozzle combination
During product transfer or post transfer uncoupling of the hose, liquid product volume released to the atmosphere
from a hose of nominal size 1 in or smaller
6.26.5.1 (A)
does not exceed 15 cc (0.91 in3) from a hose of nominal size larger than 1 in.
6.26.5.2 (B)
3Transfer into Stationary ASME Containers Maximum filling limit
Do containers of less than 2,001 gal (w.c.) have an overfilling prevention device or an other approved device? 6.26.5.2 (F)
Do containers of greater than 2,000 gal (w.c.) have a float gage or other non-venting device? 6.26.5.2 (E)
4
Transfer into Stationary ASME ContainersFixed Maximum Liquid Level gage
Not used during routine transfer operations but used to calibrate other non-venting liquid level gages in the container 6.26.5.2 (C,D)
Chapter 6Chapter 6
Analysis of Local Conditions of HazardAnalysis of Local Conditions of Hazard
•• Prevent tampering & provide accident Prevent tampering & provide accident protection for containers & transfer linesprotection for containers & transfer lines
Working together in safety
58Copyright © 2005 Propane Education & Research Council.
protection for containers & transfer linesprotection for containers & transfer lines
•• Physical protection; Ignition source control; Physical protection; Ignition source control; Separation distances; Special protectionSeparation distances; Special protection
Ch. 6
Form 6.1 (1 of 2)Evaluation of Physical Protection and Other
MeasuresA B C D E F
# Item Features Installed
in the facility?
NFPA 58 (2008)
Section ReferenceYes No
1 Lighting‡ Night operations have adequate lighting 6.18.5
Working together in safety
59Copyright © 2005 Propane Education & Research Council.
Form 6.1
g g
2 Vehicle impact protection
Protection against vehicular (traffic) on containers, transfer piping and other appurtenances is designed for the size of vehicles & traffic.
6.9.3.10 6.19.3.2
3 Protection against corrosion
Is above ground piping in contact with a support, etc., protected against corrosion?
6.9.3.11
Form 6.1 (2 of 2)Evaluation of Physical Protection and Other
MeasuresComplete only 4A or 4B
Perimeter Fence
Does 6 ft industrial type or chain link fence or equivalent enclose (all around) container, appurtenances, equipment, loading and unloading and container filling facilities?
6.18.4.2
Do two means of egress from the enclosure exist? NOTE: Second gate is not required 6 18 4 2(A)
Working together in safety
60Copyright © 2005 Propane Education & Research Council.
Form 6.1
4A g q
when area < 100 ft2, or the point of transfer < 3 ft of gate, or containers not filled
6.18.4.2(A)
Emergency access clearance of 3 ft all around provided? 6.18.4.2(B)
Guard Service
If a guard service, does service cover LP-Gas plant and are the guard personnel trained, per 4.4 of NFPA 58?
6.18.4.3
4B Lock-in-Place devices
Are Lock-in-Place devices provided in lieu of the fence requirements above?
6.18.4.2(C)
Fire Safety Analysis for LP-Gas Storage FacilitiesPresented by Theodore Lemoff, NFPA
OSINERG Forum, Lima
Copyright © 2009, Propane Education and Research Council. All Rights Reserved. 11December, 2009
Form 6.2: Ignition Source Control Assessment
A B C D E
# Ignition Control Requirement
Is the Facility
compliant? NFPA 58
(2008) SectionReference Yes No
1 Are combustible materials, weeds and tall grass not closer than 10 ft. from each container? 6.4.5.2
2 Is a distance at least 20 ft. provided between containers and tanks containing flammable liquids with flash point less than 200 oF (ex., gasoline, diesel)?
6.4.5.5
Working together in safety
61Copyright © 2005 Propane Education & Research Council.
Form 6.2
3 Are electrical equipment and wiring installed per Code requirements? 6.22.2
4 Is open flame equipment located and used according to Code? 6.22.3.1
5 Are ignition control procedures and requirements during liquid transfer operations complied with.? 7.2.3.2
6 Is an approved, portable, dry chemical fire extinguisher of minimum capacity 18 Lbs. and having a B:C rating provided in the facility?
6.25.4.2
7 Is an approved, portable, dry chemical fire extinguisher of minimum capacity 18 Lbs. and having a B:C rating provided on each truck or trailer used to transport portable containers?
9.4.7
8 Is the prohibition on smoking within the facility premises strictly enforced? 7.2.3.2(B) &
9.4.10
Form 6.3 (1 of 2)Separation Distances between Containers
and Buildings, Property Line, etc.
A B C D E F G
#
Container Size
Range in gallons (W C )
Separation Between A property line,
important building or other property & the
nearest container
Minimum Distance
(ft)
Is the Facility
compliant?
NFPA 58 (2004)
Section ReferenceYes No
Working together in safety
62Copyright © 2005 Propane Education & Research Council.
(W.C.) nearest container
1
501 to 2,000
Above Ground 25
6.3.1 and Table 6.3.1
Underground or Mounded 10
Between containers 3
2 2,001 to 30,000
Above Ground 50 Underground or Mounded 50
Between containers 5
Form 6.3
Form 6.3 (2 of 2)Separation Distances between Containers
and Buildings, Property Line, etc.
3 30,001
to 70,000
Above Ground 75
6.3.1 and Table 6 3 1
Underground or Mounded 50
Between containers ¼ sum of diameters
of adjacent containers
Above Ground 100
Working together in safety
63Copyright © 2005 Propane Education & Research Council.
Form 6.3
6.3.1
4 70,001
to 90,000
Above Ground 100 Underground or Mounded 50
Between containers
¼ sum of diameters
of adjacent containers
5 All
sizes > 125g
Distance between a LP-Gas container & an A/G tank with flam. or combust. liquids tank.
20 6.4.5.4
and 6.4.5.5
Form 6.4 (1 of 2)Separation Distances between Points of
Transfer and Other ExposuresA B C D E F G
# Type of Exposure within or outside the facility boundary Check if exposure is present
Minimum
Distance (ft)
Is the Facility compliant?
NFPA 58 (2008) Section Reference
Yes No
1Buildings, mobile homes, recreational vehicles, and modular homes with fire-resistive walls 10
Buildings with other than fire resistive walls
Working together in safety
64Copyright © 2005 Propane Education & Research Council.
Form 6.4
Section 6.5.3 &Table 6.5.3
2Buildings with other than fire resistive walls
25
3Building wall openings or pits at or below the level of the point of transfer 25
4Line of adjoining property that can be built upon
25
5Outdoor places of public assembly, including school yards, athletic fields, and playgrounds 50
6
Public ways, including public streets, highways, thoroughfares, and sidewalks
From points of transfer in LP-Gas dispensing stations and at vehicle fuel dispensers.
10
From other points of transfer 25
Form 6.4 (2 of 2)Separation Distances between Points of
Transfer and Other ExposuresA B C D E F G
# Type of Exposure within or outside the facility boundary Check if
exposure is present
Minimum Distance
(ft)
Is the Facility compliant?
NFPA 58 (2008) Section Reference
Yes No
7Driveways
5
Working together in safety
65Copyright © 2005 Propane Education & Research Council.
Form 6.4
Section 6.5.3 &Table 6.5.3
8Mainline railroad track centerlines
25
9Containers other than those being filled
10
10Flammable and Class II combustible liquid dispensers and aboveground and underground containers 20
11Flammable and Class II combustible liquid dispensers and the fill connections of LPG containers 10
12LP-Gas dispensing device located close to aClass I liquid dispensing device. 10 6.22.4.3
Form 6.5: Special Protection Measures, Requirements for Passive
SystemsA B C D E
# Special Protection Option QuestionIs the Facility
compliant? NFPA 58 (2008) Section
ReferenceYes No
1 Container Insulation
Insulation provided on each of the containers? 6.25.5.1
Insulation material complies with the requirements of section 6.25.5.1 and
Working together in safety
66Copyright © 2005 Propane Education & Research Council.
Form 6.5
6.23.5.1of NFPA 58? 6.25.5.2
2 Mounding of containers
Each container in the facility is mounded? 6.25.5.3
Mounding complies with each requirement under section 6.23.5.3 of NFPA 58. 6.25.5.3
3 Burying of containers
Each container in the facility is buried? 6.25.5.4
Buried containers comply with each requirement under section 6.6.6.1 of NFPA 58. 6.6.6.1 &
6.25.5.4
Fire Safety Analysis for LP-Gas Storage FacilitiesPresented by Theodore Lemoff, NFPA
OSINERG Forum, Lima
Copyright © 2009, Propane Education and Research Council. All Rights Reserved. 12December, 2009
Form 6.6: Special Protection Measures, Requirements for Active Systems
# Special
Protection Option
Question
Is the facility
compliant?
NFPA58 (2004)
Section ReferenceYes No
1 Water Spray
Are fixed Spray systems complying with NFPA 15, used for each container in facility?
6.25.6.1
Do fire responsive devices actuate water spray systems automatically?
6.25.6.2
Can water spray systems be actuated manually also?
6.25.6.2
Working together in safety
67Copyright © 2005 Propane Education & Research Council.
Form 6.6
manually also?
2 Monitor Nozzles
Are the monitor nozzles located & arranged so that the water stream can wet the surfaces of all containers exposed to a fire?
6.25.6.3
Can the water stream from a monitor nozzle reach & wet the entire surface of, at least, one half of a length from one end of each of the containers it is designed to protect?
6.25.6.3
Do fixed monitor nozzles comply with NFPA 15 requirements?
6.25.6.3
Do fire responsive devices actuate the monitor nozzles?
6.25.6.3
Can the monitor nozzles be actuated manually also?
6.25.6.3
Form 6.7: Protection Against Vehicular Impact
Is physical protection provided? # System Protected
Yes No
Type of physical protection installed
1 St t i
Working together in safety
68Copyright © 2005 Propane Education & Research Council.
1 Storage containers 2 Transfer stations
3 Entry way into the plant
Form 6.7
Chapter 7Chapter 7
Exposures to and from Other Properties, Exposures to and from Other Properties, Population DensityPopulation Density
•• Exposure to nearby propertiesExposure to nearby properties
Working together in safety
69Copyright © 2005 Propane Education & Research Council.
•• Exposure to nearby propertiesExposure to nearby properties•• Reasonable “worst case” examplesReasonable “worst case” examples
•• Exposure from external threatsExposure from external threats•• From industrial neighborsFrom industrial neighbors
Ch. 7
Table 7.1 (1 of 2)Table 7.1 (1 of 2)Hazards DistancesHazards Distances
ScenarioDetails of the
Propane Release
Vapor Dispersion Distance
to LFL (ft)
Explosion Hazard
Distance (ft)
Pool Fire Radiation Distance
(ft)
Fire Ball Radiation Distance
(ft)
1A Bobtail hose failure.
1” ID x 150 ft hose length
250 110 30 50
1” ID x 120
Working together in safety
70Copyright © 2005 Propane Education & Research Council.
Table 7.1
failure. Release of LP-Gas, quickly
1B 1 ID x 120 ft hose length
230 103 25 45
1C 1” ID x 75 ft hose length
190 90 20 40
2
Release of transfer piping 1" x 30 ft + @ 20 gpm for 10 min., due to failed excess flow valve
135 120 50 25
3 Release from Pressure Relief Valve
No ignitable vapor concentration at ground level.
Table 7.1 (2 of 2)Table 7.1 (2 of 2)Hazards DistancesHazards Distances
Scenario
Details of the Propane Release
Vapor Dispersion Distance to LFL
(ft)
Explosion Hazard
Distance (ft)
Pool Fire Radiation Distance
(ft)
Fire Ball Radiation Distance
(ft)
4
Release from a 1” ID x 150 ft length transfer piping to a vaporizer & reduced flow from partially open XS flow
250 120 50 50
Working together in safety
71Copyright © 2005 Propane Education & Research Council.
Table 7.1
from partially open XS flow valve @ 20 gpm for 10 min
5
Corrosion hole leak in a transfer pipe at a pressure of 130 psig (corresponding to 80oF) for 60 min. Hole size is ¼” ID
110 120 50 5
6 Release of a 2” ID x 10 ft transfer hose 195 90 20 40
7 Transport hose blowdown: Hose size 2" ID, 20 ft length release for 3 min., from a Transport
75 30 10 < 5
Hazard DistancesHazard Distances•• Hazard distances of threats to adjoining Hazard distances of threats to adjoining
exposures are calculated using EPA modelexposures are calculated using EPA model•• Annex B includes details of calculationsAnnex B includes details of calculations•• Distances for other cases can be calculatedDistances for other cases can be calculated
Working together in safety
72Copyright © 2005 Propane Education & Research Council.
•• Distances for other cases can be calculated Distances for other cases can be calculated using models in literatureusing models in literature
•• Hazard distances of threats to containers are Hazard distances of threats to containers are calculated using accepted modelscalculated using accepted models
Ch. 7.1
Fire Safety Analysis for LP-Gas Storage FacilitiesPresented by Theodore Lemoff, NFPA
OSINERG Forum, Lima
Copyright © 2009, Propane Education and Research Council. All Rights Reserved. 13December, 2009
Form 7.1:Types of Occupancies Near or Surrounding the LP-Gas Plant
Is an Occupancy
located within the
hazard distance from the Facility?
Type of Occupancies Case From Table
7.1
Yes No
Working together in safety
73Copyright © 2005 Propane Education & Research Council.
Yes No Assembly Occupancies (Places of worship, Libraries, Theaters and Auditoriums, Food or Drink Bars, Sports Stadiums, Amusement Parks, Transportation Centers, etc.)
Institutional Occupancies (Elderly Persons Home or Nursing Home, Hospitals, Alcohol & Drug Rehabilitation Centers, Prisons,
Educational Occupancies (Elementary Schools, Day Care facilities, etc)
Form 7.1
Threat to Containers from Threat to Containers from ExposuresExposures
•• Quality concerns over threat to containersQuality concerns over threat to containers
•• Thermal radiation from outside boundaryThermal radiation from outside boundary•• Explosion or large fireExplosion or large fire
Working together in safety
74Copyright © 2005 Propane Education & Research Council.
p gp g•• Softening point of propane tank steel Softening point of propane tank steel -- 800800ooFF
•• Note types of surrounding occupanciesNote types of surrounding occupancies•• Determine potential hazards & effectsDetermine potential hazards & effects•• Coordinate precautions & actions w/ neighborsCoordinate precautions & actions w/ neighbors
Ch. 7.2
Threat to Containers from Threat to Containers from ExposuresExposures
Container SizeContainer Sizegallons wcgallons wc
Maximum Maximum TemperatureTemperature
1,0001,000 478 ºF478 ºF2,0002,000 346 ºF346 ºF
Temperatures identified Temperatures identified in the chart are less than in the chart are less than the yield temperature of the yield temperature of the containers the containers ––
Working together in safety
75Copyright © 2005 Propane Education & Research Council.
4,0004,000 345 ºF345 ºF12,00012,000 345 ºF345 ºF18,00018,000 339 ºF339 ºF30,00030,000 329 ºF329 ºF60,00060,000 269 ºF269 ºF
Ch. 7.2
meaning current “set meaning current “set back” distances will back” distances will provide adequate provide adequate protection from protection from external exposure. external exposure.
Form 7.2: Exposure to LP-Gas Plant from External Hazards
A B C D Hazard
DOES exist to LP-Gas
Plant Item # Type of Neighboring Operation
YES NO
1 Petroleum and other hazardous material storage wholesale dispensing etc
Working together in safety
76Copyright © 2005 Propane Education & Research Council.
storage, wholesale dispensing, etc.
2 Metal cutting, welding , and metal fabrication
3 Industrial Manufacturing that can pose external hazards
4 Ports, rail yards and trans-shipment terminals handling flammable and explosive materials
5 Other operations that may pose hazards (gasoline and other hazardous material dispensing stations, fertilizer storage, etc)
Form 7.2
Chapter 8Chapter 8
Evaluation of Fire Services & Water SupplyEvaluation of Fire Services & Water Supply
•• Details of local Fire Service(s)Details of local Fire Service(s)•• Capabilities & resourcesCapabilities & resources
Working together in safety
77Copyright © 2005 Propane Education & Research Council.
•• Capabilities & resourcesCapabilities & resources•• Staffing, response time, training, etc.Staffing, response time, training, etc.
•• Water needs and availabilityWater needs and availability
Ch. 8.1-8.2
Form 8.1: Data on the Responding Fire Department (1 of 3)
Name of the person in the FD assisting 2A
Name of the Fire Department (FD)1
Data EntryData ItemItem #CBA
Working together in safety
78Copyright © 2005 Propane Education & Research Council.
Name of the person collecting the data3B
Date on which FD data was collected3A
Position of the person in the FD assisting with the data acquisition2B
with the data acquisition2A
Form 8.1
Fire Safety Analysis for LP-Gas Storage FacilitiesPresented by Theodore Lemoff, NFPA
OSINERG Forum, Lima
Copyright © 2009, Propane Education and Research Council. All Rights Reserved. 14December, 2009
Form 8.1: Data on the Responding Fire Department (2 of 3)
4 Number of firefighters on duty at any time
5 Average number of firefighters available for response
6A Number of firefighters
“Firefighter I” level
Working together in safety
79Copyright © 2005 Propane Education & Research Council.
qualified to 6B “Firefighter II” level
7A
Number of firefighters who would
respond on the first alarm
7B respond on the first alarm, qualified NFPA 472 or local requirements
7Crespond on the first alarm with knowledge & training on LP-Gas properties and LP-Gas fires
Form 8.1
Form 8.1 Data on the Responding Fire Department (3 of 3)
8ANumber of fire apparatus that can deploy a 125 gpm hose line supplied by onboard water
that are in service in the department
Working together in safety
80Copyright © 2005 Propane Education & Research Council.
by onboard water for at least 4 minutes, and
8B that would respond on a first alarm
Form 8.1
Form 8.2:Response Time Data for the Fire Departments
A B C D ECompany or Department Time in Minutes for
Alarm Receipt & Handling Turnout Travel Total
Time
Working together in safety
81Copyright © 2005 Propane Education & Research Council.
& Handling Time
Form 8.2
Form 8.3: Water Flow Rate and Total Water Volume Required to
Cool Containers Exposed to a FireA B C D E F G H
Item#
ASME Container
Size
Total Surface Area of
each
Surface Area of
each container
to be
Water flow rate
required per
Number of containers of the size
Total Water flow rate required
Total volume of
water required
Working together in safety
82Copyright © 2005 Propane Education & Research Council.
(gallons) Container(ft2)
to be Cooled
(ft2)
container(gpm)
indicated (gpm) for 10 min(gal)
1500 86 43 10.8
1,000 172 86 21.5
2,000 290 145 36.3
Note: Consider only the largest container and two adjacent containers.
Form 8.3
Form 8.4: Evaluation of Water Availability in or Near the LP-Gas
Facility (1 of 2)A B C D
Item # Water from Available? Quantitative information
Public supply orDistance
fromAvailable
water flow
Working together in safety
83Copyright © 2005 Propane Education & Research Council.
1
Public supply or from another piped-in supply through one or more fire hydrants in or near the facility
□ Yes
□ No
Hydrant data
from Facility
gate(feet)
water flow rate from
hydrants(1)
(gpm)Hydrant 1Hydrant 2Hydrant 3
(1) Obtain hydrant flow rates from supplier or conduct test
Form 8.4
Form 8.4: Evaluation of Water Availability in or Near the LP-Gas
Facility (2 of 2)A B C D
Item # Water from Available? Quantitative information
A nearby static water source □ Yes Distance to water = ___ Feet
Working together in safety
84Copyright © 2005 Propane Education & Research Council.
2 water source (stream, pond, lake, etc)
□ Yes □ No Time to set up relay = min.
Rate of delivery = ____ gpm
3Only through mobile water tanker shuttle
□ Yes □ No
Time to set up shuttle = ____ min. Sustainable flow rate = ____ gpm
Form 8.4
Fire Safety Analysis for LP-Gas Storage FacilitiesPresented by Theodore Lemoff, NFPA
OSINERG Forum, Lima
Copyright © 2009, Propane Education and Research Council. All Rights Reserved. 15December, 2009
Existing Facility?Existing Facility?•• Yes?Yes?
Communicate informationCommunicate informationto local responders for to local responders for inclusion in theirinclusion in their
Working together in safety
85Copyright © 2005 Propane Education & Research Council.
inclusion in their inclusion in their emergency planningemergency planning
•• No?No?ContinueContinue
General
Chapter 9Chapter 9Evaluation Summary of a ProposedEvaluation Summary of a Proposed
New LPNew LP--Gas FacilityGas Facility
S i Ch 4S i Ch 4 8 f d f ilit8 f d f ilit
Working together in safety
86Copyright © 2005 Propane Education & Research Council.
•• Summarize Ch. 4Summarize Ch. 4--8 for new proposed facility8 for new proposed facility•• Check compliance with NFPA 58Check compliance with NFPA 58•• Alter design for nonAlter design for non--compliancecompliance
•• Modifications and/or alternativesModifications and/or alternatives
Ch. 9
Evaluation of New PlantsEvaluation of New Plants•• Summarize Summarize
•• Product control featuresProduct control features•• Analysis of local hazardsAnalysis of local hazards
Working together in safety
87Copyright © 2005 Propane Education & Research Council.
•• If any deficiencies in the If any deficiencies in the design, correct themdesign, correct them
Form 9.1
Evaluation of New PlantsEvaluation of New Plants•• Summarize exposure to & from plantSummarize exposure to & from plant
•• If potential hazards exist, consider:If potential hazards exist, consider:•• Moving containersMoving containers
Working together in safety
88Copyright © 2005 Propane Education & Research Council.
Moving containersMoving containers•• Redundant & failRedundant & fail--safe product controlsafe product control•• Install automated shutdown systemsInstall automated shutdown systems•• Administrative controls (hose replacement, Administrative controls (hose replacement,
inspection, training, frequent inspections)inspection, training, frequent inspections)
Form 9.2
Evaluation of New PlantsEvaluation of New Plants•• Summarize fire department evaluationsSummarize fire department evaluations
•• If deficiencies are identified,If deficiencies are identified,•• Collaborate with fire departmentCollaborate with fire department•• Consider plant fire brigade; mutual aid with otherConsider plant fire brigade; mutual aid with other
Working together in safety
89Copyright © 2005 Propane Education & Research Council.
Consider plant fire brigade; mutual aid with other Consider plant fire brigade; mutual aid with other industrial plants; special protectionindustrial plants; special protection
•• Forms provided for these optionsForms provided for these options
•• Is adequate water provided? ... available?Is adequate water provided? ... available?•• If not, consider product control or other featuresIf not, consider product control or other features
Forms 9.3-9.7
Evaluation of New PlantsEvaluation of New Plants•• Additional considerations:Additional considerations:
•• Reduce service life of hosesReduce service life of hoses•• Increase frequency of equipment inspection Increase frequency of equipment inspection
Working together in safety
90Copyright © 2005 Propane Education & Research Council.
•• Periodic inspection of container PRVsPeriodic inspection of container PRVs•• Increase strength of piping systems Increase strength of piping systems •• Install ESVs & container internal valvesInstall ESVs & container internal valves•• Install ESVs downstream of pump outlets, & Install ESVs downstream of pump outlets, &
upstream of bulkhead valves upstream of bulkhead valves
Table 9.1
Fire Safety Analysis for LP-Gas Storage FacilitiesPresented by Theodore Lemoff, NFPA
OSINERG Forum, Lima
Copyright © 2009, Propane Education and Research Council. All Rights Reserved. 16December, 2009
Evaluation of New PlantsEvaluation of New Plants•• Additional Considerations:Additional Considerations:
•• Install pneumatic tubing fire detection system Install pneumatic tubing fire detection system along facility boundaryalong facility boundary
Working together in safety
91Copyright © 2005 Propane Education & Research Council.
•• Flame or gas detection systems connected to Flame or gas detection systems connected to close container valves w/ signal to FDclose container valves w/ signal to FD
•• Increase separation distances of internal facility Increase separation distances of internal facility exposures to container exposures to container •• For example, site buildings & vehicle parking areasFor example, site buildings & vehicle parking areas
Table 9.1
Evaluation of New PlantsEvaluation of New Plants•• Additional Considerations:Additional Considerations:
•• Relocate overhead power lines away from all Relocate overhead power lines away from all container & cylinder storage areascontainer & cylinder storage areas
Working together in safety
92Copyright © 2005 Propane Education & Research Council.
•• Eliminate all combustible vegetation within 30 ft Eliminate all combustible vegetation within 30 ft of LPof LP--Gas container Gas container -- use paving or graveluse paving or gravel
•• Mound or bury containers Mound or bury containers
Table 9.1
AppendicesAppendices•• Appendix A: FillAppendix A: Fill--in Formsin Forms
•• Appendix B: Hazard Distance and Hazard Appendix B: Hazard Distance and Hazard Area CalculationsArea Calculations
Working together in safety
93Copyright © 2005 Propane Education & Research Council.
Area CalculationsArea Calculations
•• Appendix C: Propane Property Values Used Appendix C: Propane Property Values Used in FSA Calculationsin FSA Calculations
Appendices
SummarySummary•• We have reviewed how to use the Fire We have reviewed how to use the Fire
Safety Analysis Manual to prepare a Fire Safety Analysis Manual to prepare a Fire Safety Analysis.Safety Analysis.
•• An example using a small installationAn example using a small installation
Working together in safety
94Copyright © 2005 Propane Education & Research Council.
•• An example, using a small installationAn example, using a small installation
Summary
•• Four 1,800 gal containersFour 1,800 gal containers
•• Small rural industrial area Small rural industrial area •• Small rural manufacturing within facility boundarySmall rural manufacturing within facility boundary
FSA Example #1FSA Example #1
Working together in safety
95Copyright © 2005 Propane Education & Research Council.
•• No separate vaporizer, but containers used for No separate vaporizer, but containers used for vapor service to the customervapor service to the customer
•• Vapor withdrawal only Vapor withdrawal only -- from top of containersfrom top of containers•• Vapor service line Vapor service line -- manifoldedmanifolded•• Vapor line Vapor line -- underground w/ cathodic protectionunderground w/ cathodic protection
Ch. 10
Plant Information Ex. #1Plant Information Ex. #1•• Located in rural (lowLocated in rural (low--density) population area density) population area •• Containers 130 ft from manufacturing plantContainers 130 ft from manufacturing plant•• Parking area Parking area -- extends 150’ N & 25’ Eextends 150’ N & 25’ E•• Main roadMain road 70’ S of containers70’ S of containers
Working together in safety
96Copyright © 2005 Propane Education & Research Council.
•• Main road Main road -- 70 S of containers70 S of containers•• No property hazard within 250’No property hazard within 250’•• Containers protected:Containers protected:
•• Commercial grade galvanized guardrailCommercial grade galvanized guardrail•• 3 ft clearance all around3 ft clearance all around
Example
Fire Safety Analysis for LP-Gas Storage FacilitiesPresented by Theodore Lemoff, NFPA
OSINERG Forum, Lima
Copyright © 2009, Propane Education and Research Council. All Rights Reserved. 17December, 2009
Plant Information Ex. #1Plant Information Ex. #1•• Manifolded liquid fill 2” line (no liq.withdrawal)Manifolded liquid fill 2” line (no liq.withdrawal)•• Built to NFPA 58, 1992 edition Built to NFPA 58, 1992 edition
•• No special protection No special protection •• No redundant & failNo redundant & fail--safe systemsafe system
Working together in safety
97Copyright © 2005 Propane Education & Research Council.
No redundant & failNo redundant & fail safe system safe system •• All appurtenance requirements presentAll appurtenance requirements present
•• No public water supply/hydrants on/near site No public water supply/hydrants on/near site •• Pond 5 miles from facilityPond 5 miles from facility•• Nearest FD 3 miles (next 15 miles) Nearest FD 3 miles (next 15 miles) -- both both
volunteer w/ no 24 hr presence volunteer w/ no 24 hr presence -- horn notificationhorn notification
Example
Plant Information Ex. #1Plant Information Ex. #1
Manufacturing
4 4 -- 1,800 wc LP Storage Vessels1,800 wc LP Storage Vessels
Property LineProperty Line
150 ft.150 ft.Parking
30 ft.30 ft.
Working together in safety
98Copyright © 2005 Propane Education & Research Council.
Manufacturing Plant
RoadRoad
250 ft.250 ft. 130 ft.130 ft.
70 ft.70 ft.
Example
Ex. #1 - Form 4.2: Facility Storage Capacity
A B C D
Item # Individual Container
Water Capacity (wc) (gallons)
Number of containers
Total Water Capacity (wc)
of each container size (gallons)
500 1 000
Working together in safety
99Copyright © 2005 Propane Education & Research Council.
1,000 2,000 4,000 10,000 18,000 30,000
1
Other: 1,800
2 Aggregate Water Capacity
4
4 7,200
7,200
Example
Ex. #1 - Form 4.3 (1 of 3)Add’l Information on LP-Gas FacilityExisting; Built to NFPA 58 Edition Proposed
a) Name of Facility: b) Type LP-Gas Plant: Commercial Industrial Bulkc) Facility Location: Rural Area Suburban
City Commercial City Industrial
X 1992ABC Propane Co., Inc. Div 1
XX
Working together in safety
100Copyright © 2005 Propane Education & Research Council.
y yd) Facility neighbors:
Agri. fields Commercial Bldgs.Flammable Liquids Storage Industrial Activity (metal fab., cutting & welding, etc)Manufacturing Others (explain) _______________
e) Plant Address: f) Landmarks, if any: _______________________________
523 Main Street, Central City, MA 02222
X
Example
Ex. #1 - Form 4.3 (2 of 3)Add’l Information on LP-Gas Facility
g) LP-Gas liquid supply by: (Check all that apply) Bobtail Truck Transport Rail Tank Car Pipeline
h) LP-Gas Distribution by: (Check all that apply) Bobtail Transport Vapor Piping Liquid Piping Dispensing
X
X
Working together in safety
101Copyright © 2005 Propane Education & Research Council.
i) Number of vehicle entrances: 1 2 2+
j) Type of access roads to the plant: Rural City or Town Highway
Entrance 1 Dirt road Gravel road PavedEntrance 2 Dirt road Gravel road Paved (One check per line)
XX
X
Example
Ex. #1 - Form 4.3 (3 of 3)Add’l Information on LP-Gas Facility
k) Staff presence:Not staffed Only during transfer ops.Staffed always (24/7) Only during business hrs.Other (Explain) ___________________________
X
Working together in safety
102Copyright © 2005 Propane Education & Research Council.
l) Location & dist. to Institutional Occupancies, within 250 ft
______________________________________________________________________________________________________________
m) Overview plot plan of the facility attached? Yes No
No Institutional or other occupancies within 250 ft of facility.
X
Example
Fire Safety Analysis for LP-Gas Storage FacilitiesPresented by Theodore Lemoff, NFPA
OSINERG Forum, Lima
Copyright © 2009, Propane Education and Research Council. All Rights Reserved. 18December, 2009
Container Appurtenance Container Appurtenance Requirements < 2,000 gal.Requirements < 2,000 gal.
Working together in safety
103Copyright © 2005 Propane Education & Research Council.
Fig. 5-1A
Example
Ex. #1 - Form 5.1: Container Appurtenance Requirements
A B C D E
Container #
Service Configuration
Sub Figure (in Figure 5-1)
Number of Product Release Control Appurtenances
NFPA 58 (2008) Section
ReferenceRequired by
NFPA 58 (applicable
Installed on the Container
Working together in safety
104Copyright © 2005 Propane Education & Research Council.
edition)1
5.7.4.1 and Table 5.7.4.1
23456
5.1-A5.1-A5.1-A5.1-A
5 5555
555
Example
Ex. #1 - Form 5.5: Manifolded Liquid-in Transfer Lines > 1½”
A B C D E F
# Appurtenance Appurtenance
Provided with the Feature
Installed in the
facility?
NFPA 58 (2004)
Section Reference Yes No
Within 20 ft of the nearest end of the h i l t
6.12.2 X
Working together in safety
105Copyright © 2005 Propane Education & Research Council.
1 Emergency
Shutoff Valve (ESV)
hose or swivel-type connections Automatic shutoff through thermal (fire) actuation, melting point < 250 oF
6.12.6
Temperature sensitive element (fusible link) 5 ft from the nearest end of the hose or swivel type piping
6.12.6
X
X
X
Example
Ex. #1 - Form 5.5: Manifolded Liquid-in Transfer Lines > 1½”
# Appurtenance Appurtenance Provided with the Feature
Installed in the
facility? NFPA 58
(2004) Section
Reference Yes No
1Emergency
Shutoff Valve
Manual shutoff at ESV location. 6.12.10(1)
Manual shutoff - remote, 25 – 100’. from ESV 6.12.10(2)
ESV on each leg of multi leg piping, each connected to a hose or a swivel on one side and
6.12.5
6 18 2 6(1)
XX
X
Working together in safety
106Copyright © 2005 Propane Education & Research Council.
(ESV) to a header > 1½ inch in diameter on the other. 6.18.2.6(1)
Breakaway stanchion is provided so pull-away break on the hose or swivel side & retain intact the valves & piping on plant side
6.12.8
2 Back flow
Check Valve (BCK)**
Downstream of the hose or swivel connection
6.12.8
BCK is designed for this specific application 6.12.4
A BCK is installed on each leg of a multi leg piping connected to a hose or a swivel on one side & to a header of >1½” on the other
6.12.5
Breakaway stanchion so that in a pull-away break will occur on the hose or swivel side & retain the valves and piping on the plant side
6.12.8
X
X
XX
X
X
X
Example
Ex. #1. - Form 5.7: Vapor Transfer Lines > 1¼”
A B C D E F
# Appurtenance Appurtenance Provided with the Feature
Installed in the
facility?
NFPA 58 (2004)
Section Reference Yes No
20’ from the end of the hose or swivel. 6.12.2 Automatic shutoff thorough thermal (fire) actuation, melting point < 250 oF 6.12.6
Temperature sensitive element (fusible
X
X
Working together in safety
107Copyright © 2005 Propane Education & Research Council.
1 Emergency Shutoff Valve (ESV)
p (link) 5 ft from the end of the hose or swivel
6.12.6
Manual shutoff at ESV location. 6.12.10(1) Manual shutoff 25’ – 100’ from the ESV 6.12.10(2) ESV on each leg of multi leg piping, connected to a hose or a swivel on one side and to a header > 1½” diam. on the other
6.12.5 6.18.2.6(1)
Breakaway stanchion so that in a pull-away break will occur on the hose or swivel side & retain valves and piping on the plant side
6.12.8
X
XX
X
X
Example
A B C D E F
# Item Features
Installed in the
facility?
NFPA 58 (2004)
Section ReferenceYes No
1 Lighting‡ Night operations have adequate lighting 6.18.5
Ex. #1 - Form 6.1 (1 of 2) Physical Protection & Other Measures
X
Working together in safety
108Copyright © 2005 Propane Education & Research Council.
lighting
2 Vehicle impact protection
Protection against vehicular (traffic) on containers, transfer piping and other appurtenances is designed for the size of vehicles & traffic.
6.9.3.10
and 6.19.3.2
3 Protection against corrosion
Is above ground piping in contact with a support, etc., protected against corrosion?
6.9.3.11
X
X
Example
Fire Safety Analysis for LP-Gas Storage FacilitiesPresented by Theodore Lemoff, NFPA
OSINERG Forum, Lima
Copyright © 2009, Propane Education and Research Council. All Rights Reserved. 19December, 2009
Ex. #1 - Form 6.1 (2 of 2) Physical Protection & Other Measures
Complete only 4A or 4B
Perimeter Fence
Does 6 ft industrial type or chain link fence or equivalent enclose (all around) container, appurtenances, equipment, loading and unloading and dispensing facilities?
6.18.4.2
Do two means of enclosure emergency accesses exist? NOTE: Second gate is not required 6 18 4 2(A)
X
X
Working together in safety
109Copyright © 2005 Propane Education & Research Council.
4A NOTE: Second gate is not required when area < 100 ft2, or the point of transfer < 3 ft of gate, or containers not filled
6.18.4.2(A)
Emergency access clearance of 3 ft all around provided? 6.18.4.2(B)
Guard Service
If a guard service, does service cover LP-Gas plant and are the guard personnel trained, per 4.4 of NFPA 58?
6.18.4.3
4B Lock-in-Place devices
Are Lock-in-Place devices provided in lieu of the fence requirements above?
6.18.4.2(C)
X
X
NA
NA
Example
A B C D E
# Ignition Control Requirement
Is the Facility
compliant? NFPA 58
(2004) SectionReference Yes No
1 Are combustible materials, weeds and tall grass not closer than 10 ft. from each container?
6.4.5.2
2 Is a distance at least 20 ft. provided between containers and tanks containing flammable liquids with flash point less than 6.4.5.5
Ex. #1 - Form 6.2: Ignition Source Control Assessment
X
X
Working together in safety
110Copyright © 2005 Propane Education & Research Council.
200 oF (ex., gasoline, diesel)?
3 Are electrical equipment and wiring installed per Code requirements? 6.22.2
4 Is open flame equipment located and used according to Code? 6.22.3.1
5 Are ignition control procedures and requirements during liquid transfer operations complied with.?
7.2.3.2
6 Is an approved, portable, dry chemical fire extinguisher of minimum capacity 18 Lbs. and having a B:C rating provided in the facility?
6.25.4.2
7
Is an approved, portable, dry chemical fire extinguisher of minimum capacity 18 Lbs. and having a B:C rating provided on each truck or trailer used to transport portable containers?
9.4.7
8 Is the prohibition on smoking within the facility premises strictly enforced? 7.2.3.2(B)
& 9.4.10
XXX
X
X
X
Example
Ex. #1 - Form 6.3 (1 of 2)Separation Distances
A B C D E F G
#
Container Size
Range in gallons (W C )
Separation Between A property line,
important building or other property & the
nearest container
Minimum Distance
(ft)
Is the Facility
compliant? NFPA 58
(2004) Section
ReferenceYes No
Working together in safety
111Copyright © 2005 Propane Education & Research Council.
(W.C.) nearest container
1
501 to 2,000
Above Ground 25
6.3.1 and Table 6.3.1
Underground or Mounded 10
Between containers 3
2 2,001 to 30,000
Above Ground 50 Underground or Mounded 50
Between containers 5
XNA NA
XNA NA
NA NA
NA NA
Example
Ex. #1 - Form 6.3 (2 of 2)Separation Distances
330,001
to 70,000
Above Ground 75
6.3.1 and
Underground or Mounded 50
Between containers ¼ sum of diameters
of adjacent containers
NA NANA NA
NA NA
Working together in safety
112Copyright © 2005 Propane Education & Research Council.
Table6.3.1
470,001
to 90,000
Above Ground 100 Underground or Mounded 50
Between containers ¼ sum of diameters
of adjacent containers
5All
sizes > 125g
Distance between a LP-Gas container & an A/G tank with flam. or combust. liquids tank.
20 6.4.5.4
and 6.4.5.5
NA NANA NA
NA NA
X
Example
A B C D E F G
# Type of Exposure within or outside the facility boundary Check if
exposure is present
Minimum Distance
(ft)
Is the Facility compliant?
NFPA 58 (2008) Section Reference
Yes No
1Buildings, mobile homes, recreational vehicles, and modular homes with fire-resistive walls 10
2Buildings with other than fire resistive walls
25
Ex. #1 - Form 6.4 (1 of 2)Points of Transfer & Exposures
NA NA
NA NA
Working together in safety
113Copyright © 2005 Propane Education & Research Council.
Section 6.5.3 &Table 6.5.3
3Building wall openings or pits at or below the level of the point of transfer
25
4Line of adjoining property that can be built upon
25
5Outdoor places of public assembly, including school yards, athletic fields, and playgrounds 50
6Public ways, including public streets, highways, thoroughfares, and sidewalks
From points of transfer in LP-Gas dispensing stations and at vehicle fuel dispensers.
10
From other points of transfer 25
NA NA
NA NA
NA NA
Ch. 10
X
X
X
X
A B C D E F G
# Type of Exposure within or outside the facility boundary Check if
exposure is present
Minimum Distance
(ft)
Is the Facility compliant?
NFPA 58 (2008) Section Reference
Yes No
7Driveways
5
M i li il d k li
Ex. #1 - Form 6.4 (2 of 2)Points of Transfer & Exposures
NA NA
Working together in safety
114Copyright © 2005 Propane Education & Research Council.
Section 6.5.3 &Table 6.5.3
8Mainline railroad track centerlines
25
9Containers other than those being filled
10
10Flammable and Class II combustible liquid dispensers and aboveground and underground containers 20
11Flammable and Class II combustible liquid dispensers and the fill connections of LPG containers 10
12LP-Gas dispensing device located close to aClass I liquid dispensing device. 10 6.22.4.3
NA NA
NA NA
NA NA
NA NA
NA NA
Ch. 10
Fire Safety Analysis for LP-Gas Storage FacilitiesPresented by Theodore Lemoff, NFPA
OSINERG Forum, Lima
Copyright © 2009, Propane Education and Research Council. All Rights Reserved. 20December, 2009
Ex. #1 - Form 6.5: Special Protection - Passive Systems
A B C D E
# Special Protection Option QuestionIs the Facility
compliant? NFPA 58 (2008) Section
ReferenceYes No
1 Container Insulation
Insulation provided on each of the containers? 6.25.5.1
Insulation material complies with the requirements of section 6.25.5.1 and
NA
NA
Working together in safety
115Copyright © 2005 Propane Education & Research Council.
6.23.5.1of NFPA 58? 6.25.5.2
2 Mounding of containers
Each container in the facility is mounded? 6.25.5.3
Mounding complies with each requirement under section 6.23.5.3 of NFPA 58. 6.25.5.3
3 Burying of containers
Each container in the facility is buried? 6.25.5.4
Buried containers comply with each requirement under section 6.6.6.1 of NFPA 58. 6.6.6.1 &
6.25.5.4
NA
NA
NA
NA
NA
Ch. 10
Ex. #1 – Add’l Form 6.7: Protection Against Vehicular Impact
Is physical protection provided? # System Protected
Yes No
Type of physical protection installed
1 St t i X
Working together in safety
116Copyright © 2005 Propane Education & Research Council.
1 Storage containers 2 Transfer stations
3 Entry way into the plant
XX
NA
Ch. 10
Table 7.1 (1 of 2)Table 7.1 (1 of 2)Hazards DistancesHazards Distances
Scenario Details of the
Propane Release
Vapor DispersionDistance
to LFL (ft)
Explosion Hazard
Distance (ft)
Pool Fire Radiation Distance
(ft)
Fire Ball Radiation Distance
(ft)
1A Bobtail hose failure.
1” ID x 150 ft hose length
250 110 30 50
1” ID x 120
Working together in safety
117Copyright © 2005 Propane Education & Research Council.
Ch. 10
failure. Release of LP-Gas, quickly
1B 1 ID x 120 ft hose length
230 103 25 45
1C 1” ID x 75 ft hose length
190 90 20 40
2
Release of transfer piping 1" x 30 ft + @ 20 gpm for 10 min., due to failed excess flow valve
135 120 50 25
3 Release from Pressure Relief Valve
No ignitable vapor concentration at ground level.
Table 7.1 (2 of 2)Table 7.1 (2 of 2)Hazards DistancesHazards Distances
Scenario
Details of the Propane Release
Vapor Dispersion Distance
to LFL (ft)
Explosion Hazard
Distance (ft)
Pool Fire Radiation Distance
(ft)
Fire Ball Radiation Distance
(ft)
4
Release from a 1” ID x 150 ft length transfer piping to a vaporizer & reduced flow from partially open XS flow
250 120 50 50
Working together in safety
118Copyright © 2005 Propane Education & Research Council.
Ch. 10
from partially open XS flow valve @ 20 gpm for 10 min
5
Corrosion hole leak in a transfer pipe at a pressure of 130 psig (corresponding to 80oF) for 60 min. Hole size is ¼” ID
110 120 50 5
6 Release of a 2” ID x 10 ft transfer hose 195 90 20 40
7 Transport hose blowdown: Hose size 2" ID, 20 ft length release for 3 min., from a Transport
75 30 10 < 5
Ex. #1 - Form 7.1: Nearby Occupancies
Is an Occupancy
located within the
hazard distance from the Facility?
Type of Occupancies Case From Table
7.1
Yes No
Working together in safety
119Copyright © 2005 Propane Education & Research Council.
Yes No Assembly Occupancies (Places of worship, Libraries, Theaters and Auditoriums, Food or Drink Bars, Sports Stadiums, Amusement Parks, Transportation Centers, etc.)
Institutional Occupancies (Elderly Persons Home or Nursing Home, Hospitals, Alcohol & Drug Rehabilitation Centers, Prisons,
Educational Occupancies (Elementary Schools, Day Care facilities, etc)
X
X
X
Ch. 10
Ex. #1 - Form 7.2: Exposure from External Hazards
A B C D Hazard
DOES exist to LP-Gas
Plant Item # Type of Neighboring Operation
YES NO
1 Petroleum and other hazardous material storage, wholesale dispensing, etc. X
Working together in safety
120Copyright © 2005 Propane Education & Research Council.
storage, wholesale dispensing, etc.
2 Metal cutting, welding , and metal fabrication
3 Industrial Manufacturing that can pose external hazards
4 Ports, rail yards and trans-shipment terminals handling flammable and explosive materials
5 Other operations that may pose hazards (gasoline and other hazardous material dispensing stations, fertilizer storage, etc)
XX
X
X
Ch. 10
Fire Safety Analysis for LP-Gas Storage FacilitiesPresented by Theodore Lemoff, NFPA
OSINERG Forum, Lima
Copyright © 2009, Propane Education and Research Council. All Rights Reserved. 21December, 2009
Ex. #1 - Form 8.3: Water Flow Rate & Volume
A B C D E F G H
Item#
ASME Container
Size
Total Surface Area of
each
Surface Area of
each container
to be
Water flow rate
required per
Number of containers of the size
Total Water flow rate required
Total volume of water required
for 10
Working together in safety
121Copyright © 2005 Propane Education & Research Council.
(gallons) Container(ft2)
to be Cooled
(ft2)
container(gpm)
indicated (gpm) for 10 min(gal)
1
500 86 43 10.8
1,000 172 86 21.5
2,000 290 145 36.3 4 3(36.3)=109 1,090
Ch. 10
Ex. #1 - Form 8.4: Water Availability (1 of 2)
A B C D
Item # Water from Available? Quantitative information
Public supply orDistance
fromAvailable
water flow
Working together in safety
122Copyright © 2005 Propane Education & Research Council.
1
Public supply or from another piped-in supply through one or more fire hydrants in or near the facility
□ Yes
□ No
Hydrant data
from Facility
gate(feet)
water flow rate from
hydrants(1)
(gpm)Hydrant 1Hydrant 2Hydrant 3
(1) Obtain hydrant flow rates from supplier or conduct test
X
Ch. 10
Ex. #1 - Form 8.4:Water Availability (2 of 2)
A B C D
Item # Water from Available? Quantitative information
A nearby static water source □ Yes Distance to water = ___ Feet
Working together in safety
123Copyright © 2005 Propane Education & Research Council.
2 water source (stream, pond, lake, etc)
□ Yes □ No Time to set up relay = min.
Rate of delivery = ____ gpm
3Only through mobile water tanker shuttle
□ Yes □ No
Time to set up shuttle = ____ min. Sustainable flow rate = ____ gpm
XX
XX*Pond 5 miles from facility.*Pond 5 miles from facility.
**
Ch. 10