First Revision No. 17-NFPA 170-2013 [ Global Input ] Alphabetize tables within Chapter 8 NFPA 170 as follows: Table 8.2 Symbols for Control Units (Panels) - alphabetize all symbols according to description adding "Fire Suppression/Releasing Service Control Unit Types" at the end alphabetizing all according to description. Keep i.e "manual Station - basic shape" symbol "as-is" and alphabetize all else following this base symbol. Table 8.3 Symbols for Signal Initiating Devices and Activation Switches - alphabetize all symbols according to description and incorporating the titles alphabetically for (Manual Station Types, Abort Switch Types, Heat Detection Types, Gas Detection Types, Flame Detection Types). Keep i.e "manual Station - basic shape" symbol "as-is" and alphabetize all else following this base symbol. Table 8.4.1 Notification Appliances - alphabetize all symbols according to description Table 8.4.2 Symbols for Notification Appliances - alphabetize all symbols according to description Table 8.4.3 Symbols for Emergency Communications Notification Appliances - alphabetize all symbols according to description Table 8.5 Symbols for Related Equipment - alphabetize all symbols according to description Table 8.6 Symbols for Smoke/Pressurization Controls - alphabetize all symbols according to description Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Submittal Date: Wed May 15 12:20:10 EDT 2013 Committee Statement and Meeting Notes Committee Statement: The technical committee recognizes the advantages for alphabetization in Chapter 8 Tables for ease of use. Response Message: Print Reload Page Close Show Cart Page 1 of 55 National Fire Protection Association Report 7/15/2013 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

First Revision No. 17-NFPA 170-2013 [ Global Input ]First Revision No. 17-NFPA 170-2013 [ Global Input ] Alphabetize tables within Chapter 8 NFPA 170 as follows: Table 8.2 Symbols

  • Upload
    others

  • View
    22

  • Download
    0

Embed Size (px)

Citation preview

First Revision No. 17-NFPA 170-2013 [ Global Input ]

Alphabetize tables within Chapter 8 NFPA 170 as follows:

Table 8.2 Symbols for Control Units (Panels) - alphabetize all symbols according to description adding "Fire Suppression/Releasing Service Control Unit Types" at the end alphabetizing all according to description.

Keep i.e "manual Station - basic shape" symbol "as-is" and alphabetize all else following this base symbol.

Table 8.3 Symbols for Signal Initiating Devices and Activation Switches - alphabetize all symbols according to description and incorporating the titles alphabetically for (Manual Station Types, Abort Switch Types, Heat Detection Types, Gas Detection Types, Flame Detection Types).

Keep i.e "manual Station - basic shape" symbol "as-is" and alphabetize all else following this base symbol.

Table 8.4.1 Notification Appliances - alphabetize all symbols according to description

Table 8.4.2 Symbols for Notification Appliances - alphabetize all symbols according todescription

Table 8.4.3 Symbols for Emergency Communications Notification Appliances -alphabetize all symbols according to description

Table 8.5 Symbols for Related Equipment - alphabetize all symbols according to description

Table 8.6 Symbols for Smoke/Pressurization Controls - alphabetize all symbols according to description

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Wed May 15 12:20:10 EDT 2013

Committee Statement and Meeting Notes

Committee Statement:

The technical committee recognizes the advantages for alphabetization in Chapter 8 Tables for ease of use.

Response Message:

Print Reload Page Close Show Cart

Page 1 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

First Revision No. 22-NFPA 170-2013 [ Sections 2.3.1, 2.3.2, 2.3.3 ]

Original Committee Hide Deleted

2.3.1 ANSI Publications.American National Standards Institute, Inc., 25 West 43rd Street, 4th Floor, New York, NY 10036.

ANSI A117.1, Accessible and Usable Buildings and Facilities,2003 2009 .

ANSI Z535.1, Safety Color Code,2002 2011 .

2.3.2 NECA Publications.National Electrical Contractors Association, 3 Bethesda Metro Center, Suite 1100, Bethesda, MD 20814.

NECA 100, Symbols for Electrical Construction Drawings, 1999 2006 .

2.3.3 Other Publications.Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Fri May 17 14:34:58 EDT 2013

Committee Statement and Meeting Notes

Committee Statement: Editorial update of referenced sectionsResponse Message:

Print Reload Page Close Show Cart

Page 2 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

First Revision No. 23-NFPA 170-2013 [ Section No. 2.4 ]

Original Committee Hide Deleted

2.4 References for Extracts in Mandatory Sections.NFPA 10, Standard for Portable Fire Extinguishers, 2010 2013 edition.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Fri May 17 14:47:24 EDT 2013

Committee Statement and Meeting Notes

Committee Statement: editorial update of referenced sectionsResponse Message:

Print Reload Page Close Show Cart

Page 3 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

First Revision No. 28-NFPA 170-2013 [ Section No. 3.3.3 ]

Original Committee Hide Deleted

3.3.3 Self-Luminous (Emergency Symbols) .A type of sign that is self-energized with respect to luminosity used for an emergency symbol with respect to luminosity and requires no external power source, or photoluminescent materials having the ability to store incident electromagnetic radiation typically from ambient light sources, and release it in the form of visiblelight .

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Wed May 29 13:14:44 EDT 2013

Committee Statement and Meeting Notes

CommitteeStatement:

The TC has changed the definition of self luminous to better address the concerns of the submitter. Wherever the wording "self luminous" exisits within the standard, this new definition will now include photoluminescent materials. The annex information for A.4.1.3 and A.5.1.3 will now allow photluminescent materials.

ResponseMessage:Public Input No. 13-NFPA 170-2012 [Global Input]

Print Reload Page Close Show Cart

Page 4 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

First Revision No. 2-NFPA 170-2013 [ Section No. 4.2 ]

Original Committee Hide Deleted

4.2* Symbols for General Use.The symbols for general use shall be as given in Table 4.2.Table 4.2 Symbols for General Use

Print Reload Page Close Show Cart

Page 5 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Not an Exit

Circular Field Square field Red prohibition symbol Background white Door frame green Door opening white Image in black Red circle and diagonal slash

The identification of doors that do NOT lead to an exit

The location of an interior door such as one leading to a closet, an interior courtyard, or a basement

Manual Station — Pull Station/Fire Alarm Box

Rectangular field Red background White flame White hand White box White horn White wave

An instruction to actuate an alarm-initiating device in a fire emergency

Posted above a manually activated initiating device

CommitteeStatement:

The TC agrees with the submitter for the edits, additional information and clarification for the "Not an Exit" symbol and "Manual Station-Pull Station/Fire Alarm Box"

Response Message:Committee Notes:

Date Submitted By

Jun 10, 2013

[ NotSpecified ]

See word attachment for Table edits

Public Input No. 15-NFPA 170-2012 [Section No. 4.2]

Print Reload Page Close Show Cart

Page 13 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

First Revision No. 3-NFPA 170-2013 [ Section No. 5.2 ]

Original Committee Hide Deleted

5.2* Symbols for Use by the Fire Service.The symbols for use by the fire service shall be as given in Table 5.2.Table 5.2 Symbols for Use by the Fire Service

Print Reload Page Close Show Cart

Page 14 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Fire Department Automatic Sprinkler Connection — Siamese

Square field Red background White symbol

The identification and location of a fire department automatic sprinkler connection

The location of a single automatic siamese automatic sprinkler connections on buildings The location of siamese freestanding automatic sprinkler connections

Emergency Telephone

Square field Red background White phone

The identification and location of fire service or emergency telephone system

No Fire Fighting

Circular field Octagonal field Red prohibition symbol White background Black truck within Black octagonal outline Red prohibition symbol

To be posted on, near, or on the approach to buildings where fire fighting is not to occur

Explosives bunkers, frangible buildings, or contaminated buildings

Self-Contained Breathing Apparatus (SCBA)

Square field Rectangular field White symbol Green background

To indicate the location of SCBA, breathing air connections, or refill location

For SCBA fill locations in high-rise buildings

Symbol Characteristics ExamplesSelf-Contained Breathing Apparatus (SCBA)

Square Rectangularfield White symbol Green background

To indicate the location of SCBA, breathing air connections, orrefill location

For SCBA fill locations in high-rise buildings

Supplemental Information

File Name DescriptionOpen FR3_P12_Table_5.2_word_attachment.G1370872684414.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Mon May 13 13:55:26 EDT 2013

Committee Statement and Meeting Notes

CommitteeStatement:

Fire Department Automatic Sprinkler Connection - Siamese The proposed change will prevent confusion with the first example of Fire Department Automatic Sprinkler Connection - Single. Emergency Telephone The proposed change will identify the standard field of the symbol. A rectangular field can also be used alternatively. Whichever the shape will be used, it must be included in the corresponding characteristics column of the symbol. The chosen shape or field should be the first characteristic to achieve consistency with other symbols'characteristics. No Fire Fighting Having the octagonal field as the firstcharacteristic in the column can result in a little bit of confusion until one can analyze the symbol and its characteristics more closely. Since the first characteristic of the preceding symbols (except for Emergency Telephone) describes the overall shape of these symbols, the "No Fire Fighting" symbol should follow also this format. Hence, the proposed change. The TC changed the outer field to circular to represent the actual symbol. SCBA symbol The symbol should have a rectangular field to achieve consistency with the corresponding characteristic. Firefighting Hose or Standpipe Outlet Symbol No demonstrated need to add classifications of standpipe. Hoses are connected via couplings for either type.

ResponseMessage:Public Input No. 12-NFPA 170-2012 [Section No. 5.2]

Print Reload Page Close Show Cart

Page 19 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

First Revision No. 4-NFPA 170-2013 [ Section No. 6.3.3 ]

Original Committee Hide Deleted

6.3.3* Symbols for Walls and Parapets.Symbols for walls and parapets shall be as given in Table 6.3.3.Table 6.3.3 Symbols for Walls and Parapets

Symbol DescriptionWall — basic shape

Smoke barrier wall

1⁄2-hour fire-rated fire wall

1⁄2-hour fire-rated fire /smoke barrier wall

3⁄4-hour fire-rated fire wall

3⁄4-hour fire-rated fire /smoke barrier wall

1-hour fire-rated fire wall

1-hour fire-rated fire /smoke barrier wall

2-hour fire-rated fire wall

2-hour fire-rated fire /smoke barrier wall

3-hour fire-rated fire wall

3-hour fire-rated fire /smoke barrier wall

4-hour fire-rated fire wall

4-hour fire-rated fire /smoke barrier wall

Parapet — One cross for each 150 mm (6 in.) parapet that extends above roof (Shown is plan view of symbol.)

Supplemental Information

Print Reload Page Close Show Cart

Page 20 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

First Revision No. 4

Table 6.3.3 Symbols for Walls and Parapets

Symbol Description

Wall — basic shape

Smoke barrier wall

½-hour fire-ratedwall

½-hour fire-rated /smoke barrier wall

¾-hour fire-rated wall

¾-hour fire-rated/smoke barrier wall

1-hour fire-rated wall

1-hour fire-rated/smoke barrier wall

2-hour fire-rated wall

2-hour fire-rated/smoke barrier wall

3-hour fire-rated wall

3-hour fire-rated/smoke barrier wall

4-hour fire-rated wall

4-hour fire-rated/smoke barrier wall

Parapet — One cross for each 150 mm (6 in.) parapet that extends above roof (shown is plan view of symbol.)

SEE ATTACHMENT FOR NEW ARTWORK CHANGES

FileName Description

Open artwork_attachment_for_FR4_Table_6.3.3.pdf

Open FR4_PI17_Table_6_3_3_word_attachment_edited_with_SLS_review1.docx

Open 170FCfT06-3-3_9.jpg

Open 170FCfT06-3-3_11.jpg

Open 170FCfT06-3-3_13.jpg

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Mon May 13 14:44:31 EDT 2013

Committee Statement and Meeting Notes

CommitteeStatement:

The basic shape for "wall" does not need designation therefore we are not adding other verbiage. The symbol SP is a smoke partition and special terms are not necessary. The submitter's "barrier wall'' designation is not changed by the Technical Committee because there is varied terminology for fire rated construction and we are not removing 3/4 fire rated wall because there may be situations where it could be used by a designer. The technical committee is adding the new designation "F" to denote a firewall to the "2 hour", "3 hour", 4 hour" symbols. See attachment for new artwork

Response Message:Committee Notes:

Date Submitted By

May 29, 2013

[ NotSpecified ]

See attachment for artwork and locate these symbols before the "parapet sysmbol"

Public Input No. 17-NFPA 170-2012 [Section No. 6.3.3]

Print Reload Page Close Show Cart

Page 21 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

First Revision No. 5-NFPA 170-2013 [ Section No. 7.2 ]

Original Committee Hide Deleted

7.2* Water Supply and Distribution Symbols.Water supply and distribution symbols shall be as given in Table 7.2.Table 7.2 Water Supply and Distribution Symbols

Print Reload Page Close Show Cart

Page 22 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Symbol Comments

Public water main Indicate pipe size and material

Private water main Indicate pipe size and material

Water main underbuilding

Indicate pipe size andmaterial

Suction pipe Indicate pipe size and material

Thrust block

Riser

Pipe elbow up or downHeight on either side indicated by pipe height tags

Pipe tee up or downHeight of crossed pipes indicated by pipe height tags

Valves (general) Basic shape; indicate valve size

Valve in pit Indicate valve size

Post-indicator valve Indicate valve size

Key-operated valve Indicate valve size

OS&Y valve (outside screw and yoke, rising stem)

Indicate valve size

Indicating butterflyvalve Indicate valve size

Nonindicating valve(nonrising-stem valve) Indicate valve size

Check valveBasic shape; indicate valve size, direction of flow

Backflow preventer —double check type

Also referred to as a double check valve assembly

Print Reload Page Close Show Cart

Page 23 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Symbol Comments

Backflow preventer —reduced pressure zone (RPZ) type

Pressure-regulatingvalve

Pressure relief valve

Float valve

Meter Indicate type

Private hydrant, one hose outlet

Indicate size, type of thread, or connection

Public hydrant, two hose outlets

Indicate size, type of thread, or connection

Public hydrant, two hose outlets and pumper connection

Indicate size, type of thread, or connection

Wall hydrant, two hoseoutlets

Indicate size, type of thread, or connection

Private housed hydrant, two hose outlets

Indicate size, type of thread, or connection

Siamese fire department connection

Specify type, size, and angle

Freestanding siamese fire department connection

Sidewalk or pit type; specify size

Print Reload Page Close Show Cart

Page 24 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Symbol Comments

Single fire departmentconnection

Specify type, size, thread, and angle

Fire pump with driver Specify driver type and rated capacity

Freestanding testheader

Freestanding; specify number and sizes of outlets

Wall-mounted testheader

Wall; specify number and sizes of outlets

Screen/strainer

Supplemental Information

File Name DescriptionOpen Artwork_attachement_got_FR5_Table_7.2.pdf

Open 170FCfT07-2_7.jpg

Open 170FCfT07-2_8.jpg

Open FR5_PI19_Table_7.2.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Mon May 13 15:40:13 EDT 2013

Committee Statement and Meeting Notes

CommitteeStatement:

The technical Committee agrees with the submitter as there is no standard symbol to indicate fittings vertically within the page. This additional information provides a means of doing so. Without the pipe height tags there is no way to tell if an elbow goes up or down.

ResponseMessage:Committee Notes:

Date Submitted By

Jun 10, 2013

[ Not Specified ]

See word attachment & artwork attachment

Public Input No. 19-NFPA 170-2013 [Section No. 7.2]

Print Reload Page Close Show Cart

Page 25 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

First Revision No. 16-NFPA 170-2013 [ Section No. 7.8 ]

Original Committee Hide Deleted

7.8 Symbols for Fire-Fighting Equipment.Symbols for fire-fighting equipment shall be as given in Table 7.8.Table 7.8 Symbols for Fire-Fighting Equipment

Symbol Description Comments

Fire-fighting equipment Basic shape

CO2 reel station

Dry chemical reel station

Fire hose valve connection Specify thread size

Foam reel station

Hose station, dry standpipe

Hose station, wet standpipe

Monitor nozzle, dry Specify orifice size

Monitor nozzle, charged Specify orifice size

Supplemental Information

File Name DescriptionOpen Artwork_attachment_for_FR_16_Table_7.8.pdf

Open Table_FR16_PI_18_Table_7.8_word_attachment.docx

Open 170FCfT07-8_9.jpg

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Wed May 15 11:05:53 EDT 2013

Committee Statement and Meeting Notes

Print Reload Page Close Show Cart

Page 26 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

CommitteeStatement:

This additional information broadens the use of these symbols to include hose connections.

Response Message:Committee Notes:

Date Submitted By

Jun 10, 2013

[ NotSpecified ]

See word attachement and artwork attachment

Print Reload Page Close Show Cart

Page 27 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Table 7.8 Symbols for Fire-Fighting Equipment

Symbol Description Comments ADD NEW SYMBOL Fire Hose Valve Connection Specify thread size

First Revision No. 30-NFPA 170-2013 [ Section No. 7.9 ]

Original Committee Hide Deleted

7.9* Miscellaneous Symbols.Miscellaneous symbols shall be as given in Table 7.9.Table 7.9 Miscellaneous Symbols

Print Reload Page Close Show Cart

Page 28 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Description Comments

Agent storage container Specify type of agent and mounting

Agent storage container —foam

Agent storage container —Halon

Agent storage container —carbon dioxide

Agent storage container —clean agent

Agent storage container —dry chemical

Agent storage container —water mist

Agent storage container —wet chemical

Special spray nozzle Specify type, orifice, size, other required data (shown here on pipe)

Fusible link Specify degrees

Fusible link with electrothermal feature Specify degrees

Solenoid valve

End of line device —resistor

End of line device — relay

End of line device —capacitor

End of line device —diode

Print Reload Page Close Show Cart

Page 29 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Description Comments

Transfer switch —automatic with handle

Transfer switch — manual with handle

Supplemental Information

File Name DescriptionOpen FR-30.docx

Submitter Information Verification

Submitter Full Name: Sandra StanekOrganization: National Fire Protection AssocSubmittal Date: Wed Jul 10 11:20:04 EDT 2013

Committee Statement and Meeting Notes

Committee Statement:

The TC has moved the following symbols to Table 8.3 ( see FR8 ): EOL re -End of line device-resistor; EOL ri - End of line device-relay; EOL c - End of Line device-capacitor; EOL D - End of Line device-diode; ATS -TransferSwitch-automatic with handle; MTS - Transfer switch manual with handle;SOV - Solenoid Valve

ResponseMessage:Committee Notes:

Date Submitted By

Jul 10, 2013

Sandra Stanek

Delete entries from Table 7.9 and move to Table 8.3; FR-8

Print Reload Page Close Show Cart

Page 30 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Move the following to Table 8.3 in FR-8:

Solenoid valve

End of line device — resistor

End of line device — relay

End of line device — capacitor

End of line device — diode

Transfer switch — automatic with handle

Transfer switch — manual with handle

First Revision No. 7-NFPA 170-2013 [ Section No. 8.2 ]

Original Committee Hide Deleted

8.2 Symbols for Control Panels.Global FR-17 Hide Deleted

Symbols for control panels shall be as given in Table 8.2 .Table 8.2 Symbols for Control Units (Panels)

Print Reload Page Close Show Cart

Page 31 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Basic shape

Amplifier rack

Area of refuge emergency communication system — master unit

Area of refuge emergency communication system — remote unit

Autonomous control unit

Battery cabinet

Cathode ray tube

Control panel for heating (H) , ventilation (V) , , air conditioning (AC), exhaust (E) , stairwell pressurization (P)

Dedicated function fire alarm control unit

Digital alarm communicator receiver

Digital alarm communicator transmitter

Elevator status/recall

Emergency communications control unit

Fire alarm annunciator

Fire alarm communicator

Fire alarm control panel

Fire alarm control unit (dedicated)

Fire alarm terminal cabinet

Fire alarm transponder n = transponder number

Fire suppression control panel xx denotes suppression typeFire suppression control unit xx denotes suppression type

Print Reload Page Close Show Cart

Page 32 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Graphic annunciator panel

LCD annunciator/display

Master fire alarm control unit

Notification circuit power booster, extender panel n = unit number

Power panel

Pre-action system/control unit

Printer

Protected premises control unit (local)

Purge panel

Relay panel

Releasing service fire alarm control unit

Remote voice evacuation microphone

Remotely located evacuation amplifier cabiner

Sprinkler alarm panel

Uninterruptible power supply

Voice evacuation control unit

Wireless control unit

Fire Suppression/Releasing Service Control Unit Types:

Carbon dioxide

Clean agent

Deluge fire sprinkler

Dry chemical

Fire fighter interface

Print Reload Page Close Show Cart

Page 33 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Fire pump controller

Foam

Halon

Water mist

Wet chemical

Supplemental Information

FileName Description

Open artwork_attachment_for_FR7_Table_8.2.pdf

Open FR7_PI_3_Table_8_2_word_attachment_edited_with_SLS_review1.docx

Open 170FCfT08-2_3.jpg

Open 170FCfT08-2_4.jpg

Open 170FCfT08-2_29.jpg

Open 170FCfT08-2_47.jpg

Open 170FCfT08-2_48.jpg

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Mon May 13 16:36:03 EDT 2013

Committee Statement and Meeting Notes

CommitteeStatement:

The TC recognizes the need for adding the following new symbols: #1 add subscript to FACU as dedicated #2 add italisized "n" to Fire Alarm transponder #3 revise HVA symbol to HVAC for industry standard #4 add subscript to FACU for "dedicated" #5 connection that indicates fire pump status. The disconnect is integral to the fire pump controller. See attachment for new symbols

Response Message:

Print Reload Page Close Show Cart

Page 34 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Date Submitted By

Jun 10, 2013

[ NotSpecified ]

See word attachemnt and artwork attachment

Public Input No. 3-NFPA 170-2012 [Section No. 8.2]

Print Reload Page Close Show Cart

Page 35 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Table 8.2 Symbols for Control Units (Panels)

Symbol Description

Basic shape

Fire alarm control panel

D Fire alarm control unit (dedicated)

SEE ARTWORK

Fire alarm transponder n = transponder number

Fire alarm annunciator

LCD annunciator/display

Notification circuit power booster, extender panel n = unit number

Fire alarm terminal cabinet

Battery cabinet

Voice evacuation control unit

Remote voice evacuation microphone

Graphic annunciator panel

Uninterruptible power supply

Power panel

Cathode ray tube

Printer

Emergency communications control unit

Fire suppression control panel xx denotes suppression type

Fire suppression control unit xx denotes suppression type

Amplifier rack

Area of refuge emergency communication system — master unit

Area of refuge emergency communication system — remote unit

Autonomous control unit

Remotely located evacuation amplifier cabiner

Elevator status/recall

Digital alarm communicator receiver

Digital alarm communicator transmitter

Fire alarm communicator

HVAC Control panel for heating (H), ventilation (V), exhaust, stairwell pressurization, air conditioning (AC)

Purge panel

Pre-action system

Relay panel

Sprinkler alarm panel

Wireless control unit

Master fire alarm control unit

Protected premises control unit (local)

Dedicated function fire alarm control unit

Releasing service fire alarm control unit

Fire Suppression/Releasing Service Control Unit Types:

Carbon dioxide

Dry chemical

Halon

Foam

Wet chemical

Clean agent

Water mist

Deluge fire sprinkler

SEE ARTWORK Fire pump controller SEE ARTWORK Fire fighter interface

Formatted: Font: Bold

First Revision No. 8-NFPA 170-2013 [ Section No. 8.3 ]

Original Committee Hide Deleted

8.3* Symbols for Fire Alarms, Detection, and Related Equipment — Signal Initiating Devices and Activation Switches.

Global FR-17 Hide Deleted

Symbols for signal initiating devices and activation switches shall be as given in Table 8.3 . Table 8.3 Symbols for Signal Initiating Devices and Activation Switches

Print Reload Page Close Show Cart

Page 36 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Abort Switch Types:

Abort switch — basic shape

Abort switch

Abort switch — Carbon dioxide

Abort switch — Clean agent

Abort switch — Deluge fire sprinkler

Abort switch — Dry chemical

Abort switch — Foam

Abort switch — Halon

Manual releasing station

Abort switch — Preaction

Abort switch — Water mist

Abort switch — Wet chemical

Addressable Modules:

Addressable input monitor module

Addressable input/output module; # denotes number of inputs and outputs

Addressable output control module

Print Reload Page Close Show Cart

Page 37 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Automatic Detection Type:

Automatic detection and supervisory devices — basic shape

Flame Detector/Sensor Detection Types:

Flame detector basic shapeXX = detection type

Combination ultraviolet/infrared

Infrared detector

Ultraviolet detector

Visible radiation detector

Gas Detector/Sensor Subscript Examples Detection Types:

Gas detector/sensor basic shapeXX = gas type

Carbon dioxide detector

Carbon monoxide detector

Hydrogen chloride detector

Methane detector

Heat Detector/Sensor Detection Types:

Heat detector/sensor — XX = type basic shape

Print Reload Page Close Show Cart

Page 38 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Combination rate of rise/fixed temperature

Fixed temperature

Heat detector — line type

Heat detector/sensor (thermal detection) orientation not to be changed

Rate compensation

Rate of rise only

Interface and Supervisory Devices:

End of line device — capacitor

End of line device — diode

End of line device — relay

End of line device — resistor

Flow detector/switch

High temperature switch

Level detector/switch

Low temperature switch

Non-addressable output relay

Pressure detector/switch

Solenoid valve

Temperature supervisory switch

Print Reload Page Close Show Cart

Page 39 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Transfer switch — automatic with handle

Transfer switch — manual with handle

Valve supervisory switch

Valve with valve integral supervisory switch

Water detector

Manual Station Fire Alarm Box Types:

Manual station — basic shape

Manual station — carbon Carbon dioxide

Manual station — clean Clean agent

Manual station — deluge Deluge fire sprinkler

Drill key

Manual station — dry Dry chemical

Fire alarm master box

Manual station — foam Foam

Manual station — Halon

Manual station — preaction Preaction

Manual station — pull Pull station/fire alarm box

Manual station — water Water mist

Manual station — wet Wet chemical

Smoke Detector Detection /Sensor Types:

Smoke detector/sensor — basic shape orientation not to bechanged

Print Reload Page Close Show Cart

Page 40 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Air sampling

In duct

Ionization

Photoelectric

Relay base

Single station

Smoke/heat detector/carbon monoxide detector

Smoke/heat detector/sensor combination

Smoke detector/sensor— beam receiver

Smoke detector/sensor — beam transmitter

Smoke detector/sensor — XX = type

Smoke detector/sensor for duct

Sounder base

Supplemental Information

Print Reload Page Close Show Cart

Page 41 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

File Name DescriptionOpen artwork_attachment_for_FR8_Table_8.3.pdf

Open FR8_table_8_3_word_attachment_edited_with_SLS_review1.docx

Open 170FCfT08-3_10.jpg

Open 170FCfT08-3_14.jpg

Open 170FCfT08-3_15.jpg

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Mon May 13 17:08:32 EDT 2013

Committee Statement and Meeting Notes

CommitteeStatement:

1. Combined combination heat detector/smoke detector into one symbol. The TC is changing the shape of symbol only. By combining this into one symbol, it allows for easier delineation between the two meanings. 2. The TC is not adding the smoke detector sensor for the duct as it adds confusion and could cause designer errors. 3. This symbol already exists in Table 8.5 therefore the TC is not adding it. 4. Adding new symbol to "Gas Detector/Sensor Subscript Examples" (changing name to Gas Detection Types) for designation of smoke/heat detector/carbon monoxide detector does exist, and a symbol is required. 5. Moving symbols within Table for ease of use

Response Message:Committee Notes:

Date Submitted By

Jun 10, 2013

[ NotSpecified ]

see word attachment and artwork attachment

Public Input No. 4-NFPA 170-2012 [Section No. 8.3]

Print Reload Page Close Show Cart

Page 42 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Table 8.3 Symbols for Signal Initiating Devices and Activation Switches

Symbol Description

Manual station — basic shape

Manual station — Pull station/fire alarm box

Fire alarm master box

Drill key

Abort switch — basic shape

Abort switch

Manual releasing station

Automatic detection and supervisory devices — basic shape

Heat detector/sensor (thermal detection) orientation not to be changed

Heat detector/sensor — XX = type basic shape

Heat detector — line type

Smoke detector/sensor — basic shape orientation not to be changed

Smoke detector/sensor — XX = type

Smoke/heat detector/sensor combination

SEE ATTACHED Smoke/heat detector/carbon monoxide detector

Smoke detector/sensor — beam transmitter

Smoke detector/sensor— beam receiver

Smoke detector/sensor for duct

Gas detector/sensor basic shape XX = gas type

Flame detector basic shape XX = detection type

Water detector

Manual Fire Alarm Box Types:

Manual station — Carbon dioxide

Manual station — Dry chemical

Manual station — Halon

Manual station — Foam

Manual station — Wet chemical

Manual station — Clean agent

Manual station — Water mist

Manual station — Deluge fire sprinkler

Manual station — Preaction

Abort Switch Types:

Abort switch — carbon dioxide

Abort switch — dry chemical

Abort switch — Halon

Abort switch — foam

Abort switch — wet chemical

Abort switch — clean agent

Abort switch — water mist

Abort switch — deluge fire sprinkler

Abort switch — preaction

Heat Detection/Sensor Types:

Combination rate of rise/fixed temperature

Formatted: Font: Bold

Formatted: Font: Bold

Formatted: Font: Bold

Formatted: Font: Bold

Formatted: Font: Bold

Rate compensation

Fixed temperature

Rate of rise only

Smoke Detection/Sensor Types:

Air sampling

Photoelectric

Ionization

Relay base

Single station

Sounder base

In duct

Gas Detection Types:

Carbon monoxide detector

Carbon dioxide detector

Hydrogen chloride detector

Methane detector

Flame Detection Types:

Ultraviolet

Infrared

Combination ultraviolet/infrared

Formatted: Font: Bold

Formatted: Font: Bold

Formatted: Font: Bold

Formatted: Font: Bold

Formatted: Font: Bold

Formatted: Font: Bold

Visible radiation

Flow detector/switch

Pressure detector/switch

Valve supervisory switch

Valve with valve integral supervisory switch

Level detector/switch

Temperature supervisory switch

High temperature switch

Low temperature switch

Addressable input monitor module

Addressable output control module

Addressable input/output module; # denotes number of inputs and outputs

Non-addressable output relay

First Revision No. 24-NFPA 170-2013 [ Section No. 8.5 ]

Original Committee Hide Deleted

8.5 Related Equipment.Global FR-17 Hide Deleted

Symbols for related equipment shall be as given in Table 8.5 . Table 8.5 Symbols for Related Equipment

Print Reload Page Close Show Cart

Page 43 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Air sampling detector piping

Door closer

Door holder

End of line resistor

Fire service or emergency phone station — accessible

Fire service or emergency phone station — basic shape

Fire service or emergency phone station — handset

Fire service or emergency phone station — jack

Floor Warden Station

Integrated smoke sensor and door closer

Isolator module (Style 6 or 7 fault protection)

Junction box

Mass notification system

Sync adapter module (strobe synchronization)

Print Reload Page Close Show Cart

Page 44 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Watchman's tour station

Supplemental Information

File Name DescriptionOpen Changes_to_Table_8.5.pdf

Open 170FCfT08-5_6.jpg

Open 170FCfT08-5_7.jpg

Open 170FCfT08-5_8.jpg

Open 170FCfT08-5_9.jpg

Open 170FCfT08-5_12.jpg

Open 170FCfT08-5_13.jpg

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Fri May 24 14:32:40 EDT 2013

Committee Statement and Meeting Notes

CommitteeStatement:

The TC changed the location of the subscript for the phone stations, added "Floor Warden Station" and "Mass Notification System", and edited the "junction box" symbol. See attachment for more information.

ResponseMessage:Committee Notes:

Date Submitted By

May 29, 2013

[ Not Specified ]

See attachment for more information

Print Reload Page Close Show Cart

Page 45 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

First Revision No. 27-NFPA 170-2013 [ Section No. 8.6 ]

Original Committee Hide Deleted

8.6 Symbols for Smoke/Pressurization Control.Global FR-17 Hide Deleted

Symbols for smoke/pressurization controls shall be as given in Table 8.6 . Table 8.6 Symbols for Smoke/Pressurization Controls

Print Reload Page Close Show Cart

Page 46 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Description Comments

Dampers — barometric

Dampers — fire

Dampers — fire/smoke

Dampers — motorizedfire/smoke

Dampers — smoke

Fans — duct Arrow indicates direction of flow

Fans — general Arrow indicates direction of flow

Print Reload Page Close Show Cart

Page 47 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Description Comments

Fans — roof Arrow indicates direction of flow

Fans — wall Arrow indicates direction of flow

Hand (manual)/ off-automatic

Pressurized stairwell Orient as required for base or headinjection

Purge controls — manualcontrol

Ventilation openings Orient as required for intake orexhaust

Supplemental Information

File Name DescriptionOpen Changes_to_Table_8.6.pdf

Open 170FCfT08-6_8.jpg

Open 170FCfT08-6_9.jpg

Open 170FCfT08-6_10.jpg

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Wed May 29 11:32:17 EDT 2013

Committee Statement and Meeting Notes

CommitteeStatement:

The TC has removed the circle with the wisp and changed the symbol to a polygon for Dampers - smoke, Dampers - fire/smoke, Damopers - motorized fire/smoke. See attachment for symbol changes

ResponseMessage:Committee Notes:

Date Submitted By

May 29, 2013

[ Not Specified ]

There are no text changes to this table, only symbol changes. See attachment

Print Reload Page Close Show Cart

Page 48 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

First Revision No. 14-NFPA 170-2013 [ Section No. 11.1 ]

Original Committee Hide Deleted

11.1 Introduction.This chapter shall provide requirements on the preparation of floor diagrams and plans, posted within a building, to show the egress evacuation paths and locations of equipment used during an emergency. Building emergency information shall be provided to instruct or guide occupants in how to report an emergency; when to evacuate to the outside evacuation assembly area, to a designated area of refuge, to an area of rescue assistance, or to a designated shelter area; when to remain in place; or when to employ any combination of these options.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Tue May 14 08:39:46 EDT 2013

Committee Statement and Meeting Notes

CommitteeStatement:

The Technical Committee is adding the word "evacuation" following consistency with Sec. 11.4.1.1

Response Message:

Print Reload Page Close Show Cart

Page 49 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

First Revision No. 18-NFPA 170-2013 [ Section No. 11.2.2 ]

Original Committee Hide Deleted

11.2.2*A basic floor plan shall show a minimum of two ways to exit from the location of where the diagram/plan is posted, when possible, show the entire floor plan, but when unable to provide a key plan highlighting the area shown in accordance with NFPA 101, Life Safety Code. A plan shall show a minimum of two ways to exit from the location of where the diagram/plan is posted, showing the entire floor plan in accordance with NFPA 101 , Life Safety Code . When unable to show the entire floor plan, provide a key plan highlighting the area.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Thu May 16 07:29:13 EDT 2013

Committee Statement and Meeting Notes

CommitteeStatement:

The technical Committee recognizes the shape of the entire plan is much easier to recognize than small sections. But, if necessary, the key plan gives the viewer a full understanding of the building.

ResponseMessage:

Print Reload Page Close Show Cart

Page 50 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

First Revision No. 19-NFPA 170-2013 [ Section No. 11.3.2 ]

Original Committee Hide Deleted

11.3.2There shall be a notation showing the location of the viewer and their orientation withthe "you are here" notation pointing up to the sign location . This shall be the most dominant graphic on the diagram.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Thu May 16 09:21:55 EDT 2013

Committee Statement and Meeting Notes

CommitteeStatement:

The technical committee clarifies the confusion in sometimes the "you are here" notation giving the impression that the sign is on the other side of the wall.

Response Message:

Print Reload Page Close Show Cart

Page 51 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

First Revision No. 20-NFPA 170-2013 [ Section No. 11.4.3 ]

Original Committee Hide Deleted

11.4.3The diagram or plan shall provide emergency evacuation guidelines describing the different emergency alert signals and of when and what to do when the signals are sounded. If there are not any signals, the guidelines shall describe how the occupants will be instructed what to do in case of an emergency.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Thu May 16 09:27:05 EDT 2013

Committee Statement and Meeting Notes

CommitteeStatement:

The Technical Committee recognizes there are several types of emergency conditions that require different emergency alerts and instructions.

ResponseMessage:

Print Reload Page Close Show Cart

Page 52 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

First Revision No. 29-NFPA 170-2013 [ New Section after B.5.3.2 ]

Committee Hide Deleted

Annex C Emergency Responder MapThis annex is not a part of the requirements of this NFPA document but is intendedfor informational purposes only.C.1 Emergency Responder Plan.The plan shown in Figure C.1(a) and Figure C.1(b) provides emergency responders an example of maps showing the interior and exterior locations of the building using the symbols from Table 5.2 and information from Chapter 9 . See Figure C.1(a)and Figure C.1(b) .Figure C.1(a) Emergency Response Map First Floor, Interior.

Figure C.1(b) Emergency Response Map Exterior.

Print Reload Page Close Show Cart

Page 53 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

Supplemental Information

FileName Description

Open Artwork_attachment_for_Emer_Response_Map_interior_Annex_C.1a.pdf

Open Artwork_for_Emer_Response_Map_exterior_Annex_C.1b.pdf

Open 170FCfC-01_a_.jpg

Open 170FCfC-01_b_.jpg

Submitter Information Verification

Submitter Full Name: Sandra StanekOrganization: National Fire Protection AssocSubmittal Date: Tue Jul 02 08:47:45 EDT 2013

Committee Statement and Meeting Notes

Committee Statement:

The technical committee has provided emergency responders an informational plan showing property and building access, fire hose connections, utility shut off locations, fire alarm panel locations, fire protection features, evacuation assembly areas and other information. This plan shows an example of utilization of NFPA 170 symbols for emergency response.

Response Message:Committee Notes:

Date Submitted By

Jul 2, 2013

SandraStanek

Editorial: move existing Annex C Informational References to new Annex D

Print Reload Page Close Show Cart

Page 54 of 55National Fire Protection Association Report

7/15/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...