First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value 0.0375 lumens/ft 2 is used the metric equivalent shall be 0.4036 lumens/m 2 . Any place in the body of Chapter 18 or its annex that the value 1 Foot is used the metric equivalent shall be 0.3 m. Any place in the body of Chapter 18 or its annex that the value 15 feet is used the metric equivalent shall be 4.6 m. Any place in the body of Chapter 18 or its annex that the value 16 feet is used the metric equivalent shall be 4.9 m. Any place in the body of Chapter 18 or its annex that the value 16.5 feet is used the metric equivalent shall be 5.0 m. Any place in the body of Chapter 18 or its annex that the value 20 feet is used the metric equivalent shall be 6.1 m. Any place in the body of Chapter 18 or its annex that the value 21 feet is used the metric equivalent shall be 6.4 m. Any place in the body of Chapter 18 or its annex that the value 30 feet is used the metric equivalent shall be 9.1 m. Any place in the body of Chapter 18 or its annex that the value 6 feet is used the metric equivalent shall be 1.8 m. Submitter Information Verification Submitter Full Name: SIG-NAS Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Jul 25 11:31:31 EDT 2016 Committee Statement Committee Statement: The Technical Committee agrees with the metric conversions proposed in the public inputs and makes the change. Response Message: Public Input No. 428-NFPA 72-2016 [Global Input] Public Input No. 697-NFPA 72-2016 [Global Input] Public Input No. 560-NFPA 72-2016 [Global Input] Public Input No. 566-NFPA 72-2016 [Global Input] Public Input No. 567-NFPA 72-2016 [Global Input] Public Input No. 568-NFPA 72-2016 [Global Input] Public Input No. 574-NFPA 72-2016 [Global Input] Public Input No. 575-NFPA 72-2016 [Global Input] National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... 1 of 496 10/20/2016 11:03 AM

First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2501-NFPA 72-2016 [ Global Input ]

Any place in the body of Chapter 18 or its annex that the value 0.0375 lumens/ft2 is used the metric

equivalent shall be 0.4036 lumens/m2.

Any place in the body of Chapter 18 or its annex that the value 1 Foot is used the metric equivalent shall be0.3 m.

Any place in the body of Chapter 18 or its annex that the value 15 feet is used the metric equivalent shall be4.6 m.

Any place in the body of Chapter 18 or its annex that the value 16 feet is used the metric equivalent shall be4.9 m.

Any place in the body of Chapter 18 or its annex that the value 16.5 feet is used the metric equivalent shallbe 5.0 m.

Any place in the body of Chapter 18 or its annex that the value 20 feet is used the metric equivalent shall be6.1 m.

Any place in the body of Chapter 18 or its annex that the value 21 feet is used the metric equivalent shall be6.4 m.

Any place in the body of Chapter 18 or its annex that the value 30 feet is used the metric equivalent shall be9.1 m.

Any place in the body of Chapter 18 or its annex that the value 6 feet is used the metric equivalent shall be1.8 m.

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 11:31:31 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee agrees with the metric conversions proposed in the public inputsand makes the change.

ResponseMessage:

Public Input No. 428-NFPA 72-2016 [Global Input]

Public Input No. 697-NFPA 72-2016 [Global Input]

Public Input No. 560-NFPA 72-2016 [Global Input]

Public Input No. 566-NFPA 72-2016 [Global Input]

Public Input No. 567-NFPA 72-2016 [Global Input]

Public Input No. 568-NFPA 72-2016 [Global Input]

Public Input No. 574-NFPA 72-2016 [Global Input]

Public Input No. 575-NFPA 72-2016 [Global Input]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 496 10/20/2016 11:03 AM

Page 2: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Public Input No. 585-NFPA 72-2016 [Global Input]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 496 10/20/2016 11:03 AM

Page 3: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2502-NFPA 72-2016 [ Global Input ]

Throughout Chapter 18, replace the term “enforcing authority” with the term “authority having jurisdiction.”

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 12:47:46 EDT 2016

Committee Statement

CommitteeStatement:

This first revision is being created because it uses a defined, existing term that is used in thisstandard and others.

The Technical Committee notes to the Correlating Committee that this would also need to bechanged in Chapter 7, 7.5.6.2 and Chapter 26, 26.6.2.3 and 26.6.3.3.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 496 10/20/2016 11:03 AM

Page 4: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2504-NFPA 72-2016 [ Global Input ]

Throughout chapter 18 and its annex, change the term “visible notification appliance” to “visual notificationappliance”

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 13:33:06 EDT 2016

Committee Statement

CommitteeStatement:

This revision is made to correlate with First Revision #2503. The Technical Committee requeststhe Correlating Committee to review use of the word and direct other Technical Committees toreview use in their chapters.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 496 10/20/2016 11:03 AM

Page 5: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3050-NFPA 72-2016 [ Global Input ]

The NFPA 72 Correlating Committee Task Group on Metric Values would like to submitthe following Global Input , Any place in the body of Chapter 23  or its annex that thevalue 3 feet Is used the metric equivalent shall be 0.9 m

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 15:32:00 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises the text to establish an accurate baseline metric value andfor consistency throughout the document.

ResponseMessage:

Public Input No. 581-NFPA 72-2016 [Global Input]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 496 10/20/2016 11:03 AM

Page 6: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4010-NFPA 72-2016 [ Global Input ]

Revise the title of 26.2.2 (add the word "Fire"):

26.2.2* Fire Alarm Signal Verification.

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 15:30:03 EDT 2016

Committee Statement

CommitteeStatement:

This revision is necessary to clarify that alarm verification does not apply to carbonmonoxide signals.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 496 10/20/2016 11:03 AM

Page 7: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4526-NFPA 72-2016 [ Global Input ]

D.3.2 Emergency Communication Communications Equipment.

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jul 29 14:06:21 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits D.3.2 to correlate with task group work by the CorrelatingCommittee, whereby “communication” as used in this particular context should be pluralized.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 496 10/20/2016 11:03 AM

Page 8: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 5028-NFPA 72-2016 [ Global Input ]

The NFPA 72 Correlating Committee Task Group on Metric Values would like to submitthe following Global Input , Any place in the body of Chapter 17 or its annex that thevalue 5 Feet  Is used the metric equivalent shall be 1.5 m

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Thu Aug 11 13:25:33 EDT 2016

Committee Statement

CommitteeStatement:

This Task Group was established to provide conversion values from inch-pound units to Metricunits in a consistent manner throughout the document. This will establish a baseline value for theuse of each unit of measurement to provide consistency.

ResponseMessage:

Public Input No. 662-NFPA 72-2016 [Global Input]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 496 10/20/2016 11:03 AM

Page 9: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 5029-NFPA 72-2016 [ Global Input ]

The NFPA 72 Correlating Committee Task Group on Metric Values would like to submit the followingGlobal Input , Any place in the body of Chapter 27 or its annex that the value 18 inches Is used themetric equivalent shall be 460 mm

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Thu Aug 11 13:27:09 EDT 2016

Committee Statement

CommitteeStatement:

The SIG-PRS Technical Committee changes all instances of “18 inches” or “18 in.” in Chapter 27of NFPA 72 to have the metric equivalent of 460 millimeters. This is a recommendation from theCorrelating Committee and done in order to achieve consistency throughout the Code

ResponseMessage:

Public Input No. 569-NFPA 72-2016 [Global Input]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 496 10/20/2016 11:03 AM

Page 10: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 504-NFPA 72-2016 [ Global Input ]

Any place in the body of Chapter 24 or its annex where the value 10 inches is used the metric equivalentshall be 254 mm.

Any place in the body of Chapter 24 or its annex where the value 24 inches is used the metric equivalentshall be 610 mm.

Any place in the body of Chapter 24 or its annex where the value 28 inches is used the metric equivalentshall be 711 mm.

Any place in the body of Chapter 24 or its annex where the value 36 inches or 3 feet is used the metricequivalent shall be 910 mm.

Any place in the body of Chapter 24 or its annex where the value 40 inches is used the metric equivalentshall be 1.02 m.

Any place in the body of Chapter 24 or its annex where the value 42 inches is used the metric equivalentshall be 1.07 m.

Any place in the body of Chapter 24 or its annex where the value 60 inches is used the metric equivalentshall be 1.52 m.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 12:40:51 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee agrees with the metric conversions proposed in the public inputsand makes the changes.

ResponseMessage:

Public Input No. 687-NFPA 72-2016 [Global Input]

Public Input No. 691-NFPA 72-2016 [Global Input]

Public Input No. 699-NFPA 72-2016 [Global Input]

Public Input No. 561-NFPA 72-2016 [Global Input]

Public Input No. 577-NFPA 72-2016 [Global Input]

Public Input No. 579-NFPA 72-2016 [Global Input]

Public Input No. 587-NFPA 72-2016 [Global Input]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 496 10/20/2016 11:03 AM

Page 11: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1027-NFPA 72-2016 [ Detail ]

7.2.1

(11) Pathway diagrams between the control unit and the supervising station and shared communicationsequipment within the protected premises

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 23:05:51 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee removes the requirement to determine the pathway between theprotected premises and the supervising station as these are often changing.

ResponseMessage:

Public Input No. 514-NFPA 72-2016 [Section No. 7.2.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 496 10/20/2016 11:03 AM

Page 12: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 5048-NFPA 72-2016 [ Detail ]

Move existing 26.4.6.4, including annex material, to 26.4.3.6 and make the following changes:

26.4.6.4* 26.4.3.6* Retransmission Means.

The means of retransmission shall be accepted by the authority having jurisdiction and shall be inaccordance with 26.3.6.6, 26.5.4.4, or Chapter 27.

Exception: Secondary power supply capacity shall be as required in Chapter 10.

A.26.4.6.4 A.26.4.3.6

It is the intent of this Code that the operator within the proprietary supervising station should have a securemeans of immediately retransmitting any signal indicative of a fire to the public fire departmentcommunications center. Automatic retransmission using an approved method installed in accordance withSections 26.3 through 26.5, and Chapter 27 is the best method for proper retransmission. However, amanual means can be permitted to be used, consisting of either a manual connection following therequirements of Section 26.3, Section 26.5, and Chapter 27, or, for proprietary supervising stations servingonly contiguous properties, a means in the form of a municipal fire alarm box installed within 50 ft (15 15.2m) of the proprietary supervising station in accordance with Chapter 27 can be permitted.

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 22 16:02:30 EDT 2016

Committee Statement

CommitteeStatement:

This revision is the result of a task group which was charged with making changes to thedocument to align the organization for central station service, proprietary station, and remotestation. These changes provide clarity and consistency of organizational formatting between thesesections.

In 26.4.6.4 (moved to 26.4.3.6), the exception was deleted because it is no longer required due tocurrent practices and technology.

In A.26.4.6.4 (moved to A.26.4.3.6), the metric conversion for 50 ft was updated to 15.2 m forconsistency with the rest of the document.

ResponseMessage:

Public Input No. 310-NFPA 72-2016 [Section No. 26.4.6.4]

Public Input No. 305-NFPA 72-2016 [New Section after 26.4.3.5]

Public Input No. 306-NFPA 72-2016 [New Section after A.26.4.3.1]

Public Input No. 311-NFPA 72-2016 [Section No. A.26.4.6.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 496 10/20/2016 11:03 AM

Page 13: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 5050-NFPA 72-2016 [ Detail ]

Add new section:

14.4.5.4.2

Carbon monoxide alarms shall be replaced when either the end-of-life signal is activated or themanufacturer’s replacement date is reached.

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 30 13:00:53 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee adds this section in accordance with guidance from the CorrelatingCommittee to incorporate NFPA 720 into NFPA 72.

ResponseMessage:

Public Input No. 358-NFPA 72-2016 [New Section after 14.4.5.4.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 496 10/20/2016 11:03 AM

Page 14: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 5051-NFPA 72-2016 [ Detail ]

Add new section:

29.6.2 Carbon Monoxide Alarm Interconnection.

Unless exempted by applicable laws, codes, or standards, carbon monoxide alarms used to providea warning function, and where two or more alarms are installed within a dwelling unit, suite ofrooms, or similar area, shall be arranged so that the operation of any carbon monoxide alarmcauses all carbon monoxide alarms within these locations to sound.

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 30 13:11:02 EDT 2016

Committee Statement

CommitteeStatement:

The Standards Council approved the consolidation of NFPA 720 and NFPA 72 and directed thecurrent material that is within the existing NFPA 720 to be relocated into the next edition of NFPA 72.The Correlating Committee on Signaling Systems for the Protection of Life and Property appointedthe 720/72 Consolidation Task Group to review and effect the necessary changes. This section isadded to require interconnection of carbon monoxide alarms, and to mirror requirements for smokeand heat alarms in section 29.5.2.1.1.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 496 10/20/2016 11:03 AM

Page 15: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 5052-NFPA 72-2016 [ Detail ]

Add the following reference to Informational References in the annex:

ASTM E2292, Standard Guide for Field Investigation of Carbon Monoxide Poisoning Incidents, 2014

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 11 13:03:16 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee includes ASTM E2292-14 to provide additional information relativeto carbon monoxide.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 496 10/20/2016 11:03 AM

Page 16: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 5055-NFPA 72-2016 [ Detail ]

Add the following section with annex material:

29.13.4  Carbon Monoxide Instructions.

The following information shall be included in the instructions provided with carbon monoxidealarms and detectors:

(1) Installation instructions

(2) Operating instructions

(3) Testing instructions

(4) Maintenance instructions

(5) Replacement and service instructions

(6) Statement indicating that smoke might not be present during a carbon monoxide alarmcondition

(7) *Information on the actions to be taken in case of an alarm

(8) Minimum and recommended distances from fuel-burning appliances

A.29.13.4(7)

Actions that should be considered include opening windows and doors and evacuation. Also, the informationshould provide examples of organizations to be contacted for assistance.

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 18 12:17:30 EDT 2016

Committee Statement

CommitteeStatement:

The Standards Council approved the consolidation of NFPA 720 and NFPA 72 and directed thecurrent material that is within the existing NFPA 720 to be relocated into the next edition of NFPA 72.The Correlating Committee on Signaling Systems for the Protection of Life and Property appointedthe 720/72 Consolidation Task Group to review and effect the necessary changes. This revisionincorporates requirements from NFPA 720.

ResponseMessage:

Public Input No. 361-NFPA 72-2016 [New Section after 29.11.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 496 10/20/2016 11:03 AM

Page 17: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1004-NFPA 72-2016 [ Section No. 1.1.1 ]

1.1.1

NFPA 72 covers the application, installation, location, performance, inspection, testing, and maintenanceof fire alarm systems, supervising station alarm systems, public emergency alarm reporting systems, fireand carbon monoxide detection and warning equipment, and emergency communications systems(ECS), and their components.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 12:08:20 EDT 2016

Committee Statement

Committee Statement: This incorporates information formerly in NFPA 720.

Response Message:

Public Input No. 166-NFPA 72-2016 [Section No. 1.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

17 of 496 10/20/2016 11:03 AM

Page 18: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1003-NFPA 72-2016 [ New Section after 1.1.2 ]

1.1.3

For the purposes of carbon monoxide detection, this standard is primarily concerned with life safety, notproperty protection.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 11:54:25 EDT 2016

Committee Statement

Committee Statement: This incorporates information formerly in NFPA 720.

Response Message:

Public Input No. 167-NFPA 72-2016 [New Section after 1.1.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 496 10/20/2016 11:03 AM

Page 19: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1005-NFPA 72-2016 [ Section No. 1.2.1 ]

1.2.1

The purpose of this Code is to define the means of signal initiation, transmission, notification, andannunciation; the levels of performance; and the reliability of the various types of fire alarm systems,supervising station alarm systems, public emergency alarm reporting systems, fire and carbon monoxidedetection and warning equipment, emergency communications systems, and their components.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 12:17:43 EDT 2016

Committee Statement

Committee Statement: This incorporates information formerly in NFPA 720.

Response Message:

Public Input No. 168-NFPA 72-2016 [Section No. 1.2.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 496 10/20/2016 11:03 AM

Page 20: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1007-NFPA 72-2016 [ Section No. 1.3.1 ]

1.3.1

Alarm systems shall be classified as follows:

(1) Fire alarm systems

(a) Household fire alarm systems

(b) Protected premises (local) fire alarm systems

(2) Carbon monoxide detection equipment and systems

(a) Single and multiple station carbon monoxide alarms

(b) Carbon monoxide detectors and their related systems and components

(3) Supervising station alarm systems

(a) Central station (service) alarm systems

(b) Remote supervising station alarm systems

(c) Proprietary supervising station alarm systems

(4) Public emergency alarm reporting systems

(a) Auxiliary alarm systems — local energy- type

(b) Auxiliary alarm systems — shunt- type

Supplemental Information

File Name Description

2019NFPA72_FR1007_DV.docx**Editorial Only** Numbered list done legislatively correct in word. For staff use

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 17:05:48 EDT 2016

Committee Statement

CommitteeStatement:

This incorporates information formerly in NFPA 720. The Technical Committee revisies the codeto include the hyphen when “type” is included as part of the descriptive compound noun to tie thephrase together.

Revise “shunt type” and "energy type" to be hyphenated to link the descriptive compound nountogether.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 496 10/20/2016 11:03 AM

Page 21: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ResponseMessage:

Public Input No. 169-NFPA 72-2016 [Section No. 1.3.1]

Public Input No. 629-NFPA 72-2016 [Section No. 1.3.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 496 10/20/2016 11:03 AM

Page 22: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1008-NFPA 72-2016 [ Section No. 1.3.2 ]

1.3.2

Emergency communications systems shall be classified as follows:

(1) One-way emergency communications systems

(a) Distributed recipient mass notification systems

(b) In-building fire emergency voice/alarm communications systems

(c) In-building mass notification systems

(d) Wide- area mass notification systems

(2) Two-way emergency communications systems

(a) In-building emergency communications systems

Supplemental Information

File Name Description

2019NFPA72_FR1008_DV.docx**Editorial Only** The only change is the hyphen in "wide-area". For staff use

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 17:18:20 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee makes an editorial revision to align with the common usageelsewhere in the Code regarding hyphenating "wide-area."

ResponseMessage:

Public Input No. 686-NFPA 72-2016 [Section No. 1.3.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 496 10/20/2016 11:03 AM

Page 23: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1001-NFPA 72-2016 [ New Section after 1.3.4 ]

1.3.5

The requirements of Chapters 7 , 10 , 12 , 14 , 17 , 18 , 21 , 23 , 24 , 26 , and 27 shallapply unless otherwise noted in the specific chapter. Chapter 29 is designed to stand alone unless itspecifically references an earlier chapter.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 11:48:16 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee establishes a statement similar to the charging statement of NFPA101. This also allows for the deletion of a section in each chapter stating that every other chapterof the book applies.

ResponseMessage:

Public Input No. 722-NFPA 72-2016 [New Section after 1.3.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

23 of 496 10/20/2016 11:03 AM

Page 24: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4503-NFPA 72-2016 [ New Section after 2.3 ]

2.3.3 IEEE Publications.

Institute of Electrical and Electronics Engineers, 3 Park Avenue, 17th Floor, New York, NY 10016-5997.

IEEE 450, Recommended Practice for Maintenance, Testing, and Replacement of Vented Lead-AcidBatteries for Stationary Applications , 2010.

IEEE 485, Recommended Practice for Sizing Lead-Acid Batteries for Stationary Applications , 2010.

IEEE 1106, Recommended Practice for Installation, Maintenance, Testing, and Replacement of VentedNickel-Cadmium Batteries for Stationary Applications , 2005.

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 13:31:48 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee adds IEEE references in Chapter 2 to correlate with their use in thestandard and to abide by the NFPA Manual of Style.

ResponseMessage:

Public Input No. 138-NFPA 72-2016 [New Section after 2.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

24 of 496 10/20/2016 11:03 AM

Page 25: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1013-NFPA 72-2016 [ Section No. 3.3.3 ]

3.3.3 Accessible, Readily (Readily Accessible).

Capable of being reached quickly for operation, renewal, or inspections without requiring those to whomready access is requisite to take actions such as to use tools (other and keys), to climb over or under, toremove obstacles, or to resort to portable ladders, and so forth. [ 70: 100] (SIG-FUN)

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 17:44:04 EDT 2016

Committee Statement

Committee Statement: The definition of readily accessible is extracted from Article 100 of NFPA 70.

Response Message:

Public Input No. 113-NFPA 72-2016 [Section No. 3.3.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

25 of 496 10/20/2016 11:03 AM

Page 26: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1502-NFPA 72-2016 [ New Section after 3.3.11 ]

3.3.11.1 Carbon Monoxide Alarm.

A single-or multiple-station alarm responsive to carbon monoxide (CO). (SIG-HOU)

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 11:52:34 EDT 2016

Committee Statement

CommitteeStatement:

A new definition is needed as part of the 72/720 consolidation effort. This definition mirrorsthe smoke alarm definition.

ResponseMessage:

Public Input No. 171-NFPA 72-2016 [New Section after 3.3.11]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 496 10/20/2016 11:03 AM

Page 27: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4504-NFPA 72-2016 [ New Section after 3.3.30 ]

3.3.31* Battery.

An energy storage system or a component thereof, consisting of two or more cells connected togetherelectrically. (SIG-TMS)

3.3.31.1 Battery Capacity.

The electrical energy available from a fully charged battery expressed in ampere-hours. (SIG-TMS)

3.3.31.2 Battery Charger.

A device used to restore and maintain the charge of a secondary battery in which electrical energy isconverted to chemical energy. (SIG-TMS)

3.3.31.2.1 Float Charge.

A constant-voltage charge applied to a battery to keep it fully charged. (SIG-TMS)

3.3.31.2.2 Fully Charged.

A condition synonymous with 100 percent state of charge. (See also 3.3.31.2.3 , State of Charge.)(SIG-TMS)

3.3.31.2.3 State of Charge (SOC).

The stored or remaining capacity of a battery at a given time expressed as a percentage of its ratedcapacity. (SIG-TMS)

3.3.31.2.4 Trickle Charge.

A continuous, low-rate, constant-current charge given to a cell or battery to keep the unit fully charged.(See also 3.3.31.2.1 , Float Charge.) (SIG-TMS)

3.3.31.3 Battery Load Test.

A controlled discharge of a battery at a specified rate for a given period of time until a final voltage isachieved to determine battery capacity. (SIG-TMS)

3.3.31.4 Battery Unit.

See 3.3.40.3 3.3.40.3 , Unit (Multi-Cell). (SIG-TMS)

3.3.31.5 Rechargeable Battery.

An electrochemical cell capable of being discharged and then recharged. (SIG-TMS)

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 13:37:16 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee adds battery definitions per the recommendations of the IEEE StationaryBattery Committee and NFPA Battery Task Group to introduce correct battery terminology. The newdefinitions are based on definitions found in published IEEE battery standards, EPRI technical

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

27 of 496 10/20/2016 11:03 AM

Page 28: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

reports, and battery manufacturer's, technical manuals, that have been adapted for the intended usewithin NFPA 72 by the SIG-TMS Battery Task Group. Refer to: IEEE standards 450 and 1188, EPRItechnical reports 1002925 and 1006757, Power-Sonic’s SLA technical manual and Enersys BatteryApplication Manual US-NP-AM-003.

ResponseMessage:

Public Input No. 139-NFPA 72-2016 [New Section after 3.3.30]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

28 of 496 10/20/2016 11:03 AM

Page 29: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 503-NFPA 72-2016 [ Section No. 3.3.33 ]

3.3.34 Building Fire Safety Plan.

Documentation that provides information on the use of alarms, transmission of alarms, response toalarms, evacuation of immediate area, evacuation of smoke compartment, preparation of floors andbuilding for evacuation and extinguishment of fire. (SIG-ECS)

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 11:18:39 EDT 2016

Committee Statement

CommitteeStatement:

Based upon the actions on several other first revisions, this term is no longer used in thedocument and is removed.

ResponseMessage:

Public Input No. 510-NFPA 72-2016 [Section No. 3.3.33]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

29 of 496 10/20/2016 11:03 AM

Page 30: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4529-NFPA 72-2016 [ New Section after 3.3.38.4 ]

3.3.40 Cell.

The basic electrochemical unit, characterized by an anode and a cathode, used to receive, store, anddeliver electrical energy. [ 70: 480] (SIG-TMS)

3.3.40.1 Primary (Dry) Cell.

A nonrechargeable electrochemical cell requiring periodic replacement, such as a 9-volt alkaline cell.(SIG-FUN)

3.3.40.2 Starved Electrolyte Cell.

A cell in which liquid electrolyte is immobilized, also known as an absorbed glass mat (AGM) cell or agelled electrolyte cell (gel cell). (SIG-TMS)

3.3.40.2.1 Absorbed Glass Mat (AGM) Cell.

A cell in which the liquid electrolyte is immobilized in fiberglass or polymeric fiber separators. (SIG-TMS)

3.3.40.2.2 Gelled Electrolyte Cell (Gel Cell).

A cell in which the electrolyte is immobilized by addition of a gelling agent. (SIG-TMS)

3.3.40.3 Unit (Multi-Cell).

Multiple cells in a single container, such as a 12-volt unit composed of six 2-volt cells. (SIG-TMS)

3.3.40.4* Valve-Regulated Lead-Acid (VRLA) Cell.

A sealed lead-acid cell with a valve that opens to the atmosphere when the internal pressure in the cellexceeds atmospheric pressure by a preselected amount. (SIG-TMS)

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jul 29 15:07:49 EDT 2016

Committee Statement

CommitteeStatement:

The Task group added this new section per the recommendations of IEEE Stationary BatteryCommittee and NFPA Battery Task Group to introduce correct battery terminology. The newdefinitions are based on definitions found in published IEEE battery standards, EPRI technicalreports, and battery manufacturer's, technical manuals, that have been adapted for the intended usewithin NFPA 72 by the SIG-TMS Battery Task Group. Refer to: IEEE standards 450 and 1188, EPRItechnical reports 1002925 and 1006757, Power-Sonic’s SLA technical manual and Enersys BatteryApplication Manual US-NP-AM-003.

ResponseMessage:

Public Input No. 140-NFPA 72-2016 [New Section after 3.3.38.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

30 of 496 10/20/2016 11:03 AM

Page 31: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4004-NFPA 72-2016 [ Section No. 3.3.57 ]

3.3.59 Communications Cloud.

The area in the communications path that is supported by providers of communication communicationsservices not governed under the scope of NFPA 72 in which signals travel between a protected propertyand a monitoring station. Depending on the type of transmission that is used, signals can travel on asingle defined route or through various routes depending on what is available when the signal is initiated.(SIG-SSS)

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 12:15:55 EDT 2016

Committee Statement

CommitteeStatement:

As part of the Correlating Committee Task Group on terms, the term "communication(s)” wasreviewed throughout the entire document for proper use regarding reference to singular and pluraluse. The term should be plural use in this context.

ResponseMessage:

Public Input No. 443-NFPA 72-2016 [Section No. 3.3.57]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

31 of 496 10/20/2016 11:03 AM

Page 32: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4003-NFPA 72-2016 [ New Section after 3.3.60.2 ]

3.3.93* Emergency Response Agency (ERA).

Organizations providing law enforcement, emergency medical, fire, rescue, communications, andrelated support services. [ 1221, 2019] (SIG-SSS)

Supplemental Information

File Name Description

A.3.3.X_FR_4003_BC.docx Annex material

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 12:09:43 EDT 2016

Committee Statement

Committee Statement: This term is extracted from NFPA 1221 and is used in the proposed A.26.5.3.

Response Message:

Public Input No. 173-NFPA 72-2016 [New Section after 3.3.60.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

32 of 496 10/20/2016 11:03 AM

Page 33: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2009-NFPA 72-2016 [ Section No. 3.3.66.1 ]

3.3.68.1 Air Sampling–Type Detector.

A detector that consists of a piping or tubing distribution network that runs from the detector to the area(s)to be protected. An aspiration fan in the detector housing draws air from the protected area back to thedetector through air- sampling ports, piping, or tubing. At the detector, the air is analyzed for fire products.(SIG-IDS)

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 17:42:25 EDT 2016

Committee Statement

CommitteeStatement:

A Correlating Committee task group on language/terms reviewed the language of the Code forconsistency and grammar.

Editorial correction. The Term “air sampling” is generally not hyphenated and majority of usagein the code is not hyphenated. Revised to align with other usage in the Code

ResponseMessage:

Public Input No. 643-NFPA 72-2016 [Section No. 3.3.66.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

33 of 496 10/20/2016 11:03 AM

Page 34: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4520-NFPA 72-2016 [ New Section after 3.3.86 ]

3.3.84 Electromechanical Releasing Device.

Mechanical devices, including fusible links, electrically monitored for contact closure to initiate a signalto the FACU.

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jul 29 12:39:13 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee clarifies the limited use of this device and technology and providesa definition for a previously undefined term.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

34 of 496 10/20/2016 11:03 AM

Page 35: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 546-NFPA 72-2016 [ Section No. 3.3.86 ]

3.3.89 Emergency Communications Systems — Combination.

Various emergency communication communications systems such as fire alarm, mass notification, firefighter communications, area of refuge communications, elevator communications, or others that can beserved through a single control system or through an interconnection of several control systems.(SIG-ECS)

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jul 29 12:13:24 EDT 2016

Committee Statement

CommitteeStatement:

As part of the Correlating Committee Task Group on terms, the term "communication(s)” wasreviewed throughout the entire document for proper use regarding reference to singular and pluraluse. The term should be plural use in this context.

ResponseMessage:

Public Input No. 444-NFPA 72-2016 [Section No. 3.3.86]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

35 of 496 10/20/2016 11:03 AM

Page 36: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1051-NFPA 72-2016 [ New Section after 3.3.91 ]

3.3.97* Energy Storage Systems.

Equipment that receives electrical energy and then provides a means to store that energy in some formfor later use in order to supply electrical energy when needed. The energy storage system utilizes thetechnologies defined in 3.3.97.1 through 3.3.97.4 .

3.3.97.1 Electrochemical Energy Storage System.

Consists of a secondary battery, electrochemical capacitor, flow battery, or hybrid battery-capacitorsystem that stores energy and any associated controls or devices that can provide electric energy upondemand.

3.3.97.2 Chemical Energy Storage System.

Consists of hydrogen storage, the hydrogen generator to supply the hydrogen for storage, and a fuelcell power system to provide electric energy upon demand.

3.3.97.3 Mechanical Energy Storage System.

Consists of a mechanical means to store energy such as through compressed air, pumped water or flywheel technologies, and associated controls and systems, which can be used to run an electricgenerator to provide electric energy upon demand.

3.3.97.4 Thermal Energy Storage System.

Consists of a system that uses heated fluids such as air as a means to store energy along withassociated controls and systems, which can be used to run an electric generator to provide electricalenergy upon demand.

Supplemental Information

File Name Description

2019NFPA72_FR1051_Annex_DV.docx This Annex material corresponds to the new definition.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 07:16:48 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee defines what an energy storage system is and type of technology optionavailable to the industry. Definitions are from UL outline 9540 (a)-(d). The definition of the term“Energy storage system integrator” was not included as this term is not used in NFPA 72.

ResponseMessage:

Public Input No. 551-NFPA 72-2016 [New Section after 3.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

36 of 496 10/20/2016 11:03 AM

Page 37: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3040-NFPA 72-2016 [ Section No. 3.3.103.4.1 ]

3.3.109.4.1 Building Fire Alarm System.

A protected premises fire alarm system that includes any of the features identified in 23.3.3.1 and thatserves the general fire alarm needs of a building or buildings and that provides fire department oroccupant notification or both . (SIG-PRO)

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 14:18:38 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text to remove the specific entities being notified, but to alsoindicate that the purpose of a fire alarm system is to provide notification.

ResponseMessage:

Public Input No. 714-NFPA 72-2016 [Section No. 3.3.103.4.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

37 of 496 10/20/2016 11:03 AM

Page 38: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4027-NFPA 72-2016 [ New Section after 3.3.127 ]

3.3.134* Immediately (as used in Chapter 26).

Performed without unreasonable delay. (SIG-SSS)

Supplemental Information

File Name Description

A.3.3.X_FR_4027_BC.docx Annex material

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 13:18:03 EDT 2016

Committee Statement

CommitteeStatement:

The use of "immediately" in multiple places in Chapter 26 requires a definition in the body ofthe Code, rather than the annex.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

38 of 496 10/20/2016 11:03 AM

Page 39: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4509-NFPA 72-2016 [ New Section after 3.3.133 ]

3.3.140* Inspection and Testing Report Recommendation.

A suggestion that is provided within the scope of the report but is not required and does not rise to thelevel of a deficiency. (SIG-TMS)

Supplemental Information

File Name Description

Inspection_and_Testing_Report_Recommendation_Annex.docxAnnex Material for the new definition of Inspection and Testing Report Recommendation.

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 20:14:36 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee adds this new definition to provide additional clarification to both thebuilding owner and service provider that recommendations are permitted but not required to beacted upon by this Code.

Public Input No. 341-NFPA 72-2016 [New Section after 3.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

39 of 496 10/20/2016 11:03 AM

Page 40: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3041-NFPA 72-2016 [ Section No. 3.3.140 ]

3.3.148 Life Safety Network.

A type of combination system that transmits fire safety control data through gateways to other buildingsystem control units and emergency communications system data between devices and systemsthroughout a building(s) . (SIG-PRO)

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 14:21:26 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee agrees the term "Network" in Life Safety Networks has taken on abroader context from the perspective of both MNS and Class N. Realigning the Life Safety Networkwith "emergency communication systems" broadens the definition to include systems that are notnecessarily only concerned with fire safety.

The Technical Committee edits the proposed text, replacing “to” with “between”.

ResponseMessage:

Public Input No. 410-NFPA 72-2016 [Section No. 3.3.140]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

40 of 496 10/20/2016 11:03 AM

Page 41: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3505-NFPA 72-2016 [ Section No. 3.3.144 ]

3.3.152 Local Energy–Type Auxiliary Alarm System.

See 3.3.2193.3.211 , Public Emergency Alarm Reporting System.

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 12:09:54 EDT 2016

Committee Statement

CommitteeStatement:

A Correlating Committee task group on language/terms reviewed the language of the Code forconsistency and grammar.

Both the “local energy-type” and “local energy type” terms are used in the Code. The former hashistorically (past editions a least to 1979) been used most extensively when including the “type”phrase. Recommend revising the code to include the hyphen when “type” is included as part of thedescriptive compound noun to tie the phrase together.

The Technical Committee adds a hyphen between Energy-Type for consistency.

ResponseMessage:

Public Input No. 631-NFPA 72-2016 [Section No. 3.3.144]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

41 of 496 10/20/2016 11:03 AM

Page 42: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4032-NFPA 72-2016 [ Section No. 3.3.151 ]

3.3.159* Managed Facilities-Based Voice Network (MFVN).

A physical facilities-based network capable of transmitting real-time signals with formats unchanged that ismanaged, operated, and maintained by the service provider to ensure service quality and reliability fromthe subscriber location to public-switched telephone network (PSTN) interconnection points or theinterconnection point with other MFVN peer networks or the supervising station . (SIG-SSS)

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 17:51:08 EDT 2016

Committee Statement

CommitteeStatement:

The definition was revised to remove the circular reference to PSTN, in order to clarify that aPSTN is a MFVN.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

42 of 496 10/20/2016 11:03 AM

Page 43: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4007-NFPA 72-2016 [ New Section after 3.3.158 ]

3.3.324* Wireless Mesh Network (WMN) .

A decentralized communications network made up of radio nodes, organized in a mesh topology thatdoes not rely on a pre-existing infrastructure. (SIG-SSS)

Supplemental Information

File Name Description

A.3.3.X_FR_4007_BC.docx Annex material.

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 12:22:39 EDT 2016

Committee Statement

CommitteeStatement:

The definition of "Wireless Mesh Network (WMN)" does not appear currently in Chapter 3,Definitions. The term is used in the Annex for Chapter 26 as a method of creating a PrivateOne-Way Radio Alarm System and is proposed as an addition to the main text of Chapter 26.

Mesh systems have been listed and used for years as a method of implementing a PrivateOne-Way Radio Alarm System and literally hundreds of thousands of such units exist incommercial fire alarm service.

ResponseMessage:

Public Input No. 468-NFPA 72-2016 [New Section after 3.3.158]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

43 of 496 10/20/2016 11:03 AM

Page 44: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2503-NFPA 72-2016 [ Section No. 3.3.172.3 ]

3.3.180.3 Visible Visual Notification Appliance.

A notification appliance that alerts by the sense of sight. (SIG-NAS)

3.3.180.3.1* Textual Visible Notification Appliance.

A notification appliance that conveys a stream of visible information that displays an alphanumeric orpictorial message. (SIG-NAS)

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 13:17:59 EDT 2016

Committee Statement

CommitteeStatement:

These appliances provide a visual stimulus. The term “visual” more accurately describes theappliance as being a stimulus to the eye rather than simply being visible to the eye. The TechnicalCommittee notes to the Correlating Committee that the word "visible" would also need to bechanged in other chapters.

ResponseMessage:

Public Input No. 624-NFPA 72-2016 [Section No. 3.3.172.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

44 of 496 10/20/2016 11:03 AM

Page 45: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3506-NFPA 72-2016 [ Section No. 3.3.211 [Excluding any

Sub-Sections] ]

A system of alarm-initiating devices, transmitting and receiving equipment, and communicationsinfrastructure ( — other than a public telephone network) — used to communicate with thecommunications center to provide any combination of manual or auxiliary alarm service. (SIG-PRS)

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 12:12:27 EDT 2016

Committee Statement

CommitteeStatement:

As part of the CC TG on terms, the term "communication(s)” was reviewed throughout the entiredocument for proper use regarding reference to singular and plural use. The term should be pluraluse in this context.

The Technical Committee changes communication to communications for consistency and properuse.

ResponseMessage:

Public Input No. 445-NFPA 72-2016 [Section No. 3.3.211 [Excluding any Sub-Sections]]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

45 of 496 10/20/2016 11:03 AM

Page 46: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3521-NFPA 72-2016 [ Section No. 3.3.211.1.1 ]

3.3.219.1.1 Local Energy– Type Auxiliary Alarm System.

An auxiliary system that employs a locally complete arrangement of parts, initiating devices, relays, powersupply, and associated components to automatically activate a master box or auxiliary box over circuitsthat are electrically isolated from the public emergency alarm reporting system circuits. (SIG-PRS)

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 18:06:48 EDT 2016

Committee Statement

CommitteeStatement:

Both the “local energy-type” and “local energy type” terms are used in the Code. The former hashistorically (past editions a least to 1979) been used most extensively when including the “type”phrase. The Technical Committee revises the code to include the hyphen when “type” is included aspart of the descriptive compound noun to tie the phrase together.

ResponseMessage:

Public Input No. 632-NFPA 72-2016 [Section No. 3.3.211.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

46 of 496 10/20/2016 11:03 AM

Page 47: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3042-NFPA 72-2016 [ Section No. 3.3.232 ]

3.3.240 Relocation.

The directed movement of occupants from a fire zone to a safe one area to another area within the samebuilding. (SIG-PRO)

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 14:58:48 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revised the text because the definition referred to fire specifically.The definition is now broadened to include other life safety systems.

ResponseMessage:

Public Input No. 126-NFPA 72-2016 [Section No. 3.3.232]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

47 of 496 10/20/2016 11:03 AM

Page 48: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1503-NFPA 72-2016 [ Section No. 3.3.248 ]

3.3.256* Separate Sleeping Area.

The area of a dwelling unit where the bedrooms or sleeping rooms are located. [ 720, 2015] (SIG-HOU)

Supplemental Information

File Name Description

FR_1503_A.3.3.248.docx new annex

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 12:36:37 EDT 2016

Committee Statement

CommitteeStatement:

This is a product of the 72/720 consolidation Task Group. The Technical Committee removesreference to 720 because NFPA 720 is being incorporated into NFPA 72.

Addition of annex material clarifies where separate sleeping areas may be located in a dwellingunit.

ResponseMessage:

Public Input No. 178-NFPA 72-2016 [Section No. 3.3.248]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

48 of 496 10/20/2016 11:03 AM

Page 49: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 505-NFPA 72-2016 [ New Section after 3.3.275 ]

3.3.283 Speaker.

A person who delivers specific instructions or information to occupants in a building or to those that arein areas outside of the building.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 12:45:22 EDT 2016

Committee Statement

CommitteeStatement:

As part of the Correlating Committee Task Group on terms, the term "Speaker" was reviewedthroughout the entire document for proper use. In some cases it refers to a physical appliance whileother sections use it to refer to a person. There needs to be a definition as to what a speaker iswhen referring to a person who is delivering instructions and or information to occupants. It isunderstood that this will correlate with the actions taken in Chapter 18.

ResponseMessage:

Public Input No. 207-NFPA 72-2016 [New Section after 3.3.275]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

49 of 496 10/20/2016 11:03 AM

Page 50: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3043-NFPA 72-2016 [ Section No. 3.3.317.1 ]

3.3.327.1 Notification Zone.

A discrete area of a building, bounded by building outer walls, fire or smoke compartment boundaries,floor separations, or other fire safety subdivisions, in which occupants or defined area outside a building,in which people are intended to receive common notification. (SIG-PRO)

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 15:01:58 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises the current definition of notification zone to include requirementsfor the zone that are also given in section 23.8.6.3.2. This change eliminates the redundancy and itexpands the definition to include areas outside the building. Areas outside the building are relevantdue to the expansion of NFPA 72 to include mass notification.

ResponseMessage:

Public Input No. 127-NFPA 72-2016 [Section No. 3.3.317.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

50 of 496 10/20/2016 11:03 AM

Page 51: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3039-NFPA 72-2016 [ New Section after 3.3.317.2 ]

3.3.34 Building System Information Unit (BSIU).

A computer-based electronic device that is intended to display building information and execute systemcontrol functions, including fire system information display and control.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 14:14:56 EDT 2016

Committee Statement

Committee Statement: The Technical Committee adds this definition as BSIU is added to Chapter 23.

Response Message:

Public Input No. 536-NFPA 72-2016 [New Section after 3.3.34]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

51 of 496 10/20/2016 11:03 AM

Page 52: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3063-NFPA 72-2016 [ New Section after 3.3.317.2 ]

3.3.102 FACP.

Fire Alarm Control Panel. See 3.3.106 Fire Alarm Control Unit (FACU).

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Sun Aug 07 11:05:04 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee adds the text as the term FACP is still widely used in theindustry.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

52 of 496 10/20/2016 11:03 AM

Page 53: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 545-NFPA 72-2016 [ Section No. 3.3.317.2 ]

3.3.327.2* Signaling Zone.

An area consisting of one or more notification zones where identical signals are actuated simultaneously.(SIG-ECS)

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jul 29 12:10:56 EDT 2016

Committee Statement

CommitteeStatement:

As currently written the floors of a high rise that are playing the evacuation message and the "waitin place" message would be in the same notification zone, as they are activated simultaneously.The addition of the word "identical" clarifies that the notification zone is communicating a commonmessage.

ResponseMessage:

Public Input No. 128-NFPA 72-2016 [Section No. 3.3.317.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

53 of 496 10/20/2016 11:03 AM

Page 54: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1028-NFPA 72-2016 [ Section No. 7.2.1 ]

Detail FR-1027

7.2.1*

Where documentation is required by the authority having jurisdiction, the following list shall represent theminimum documentation required for new fire alarm systems, supervising station and sharedcommunication equipment, and emergency communications systems, including new systems andadditions or alterations to existing systems:

(1)

(2) Riser diagram

(3) Floor plan layout showing locations of all devices, control equipment, and supervising station andshared communications equipment with each sheet showing the following:

(a) Point of compass (north arrow)

(b) A graphic representation of the scale used

(c) Room use identification

(d) Building features that will affect the placement of initiating devices and notification appliances

(4) Sequence of operation in either an input/output matrix or narrative form

(5) Equipment technical data sheets

(6) Manufacturers’ published instructions, including operation and maintenance instructions

(7) Battery capacity and de-rating (safety margin) calculations (where batteries are provided)

(8) Voltage drop calculations for notification appliance circuits

(9) Mounting height elevation for wall-mounted devices and appliances

(10) Where occupant notification is required, minimum sound pressure levels that must be produced bythe audible notification appliances in applicable covered areas

(11) Locations of alarm notification appliances, including candela ratings for visible alarm notificationappliances

(12)

(13) Completed record of completion in accordance with 7.5.6 and 7.8.2

(14) For software-based systems, a copy of site-specific software, including specific instructions on howto obtain the means of system and software access (password)

(15) Record (as-built) drawings

(16) Records, record retention, and record maintenance in accordance with Section 7.7

(17) Completed record of inspection and testing in accordance with 7.6.6 and 7.8.2

Supplemental Information

File Name Description

2019NFPA72_FR1028_Annex_DV.docx This is Annex material for item number (12) only

2019NFPA72_FR1028_DV.docx This is the legislatively correct numbered list. For staff use

* Written narrative providing intent and system description

* Pathway diagrams between the control unit and the supervising station and sharedcommunications equipment within the protected premises

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

54 of 496 10/20/2016 11:03 AM

Page 55: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 23:23:13 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee has revised the text to make reference to the term “safety margin” asused in the Chapter 10. Additional item (11) was added to match what is currently in the IFC. Theterm areas was not deleted from the end of item (10).

ResponseMessage:

Public Input No. 475-NFPA 72-2016 [Section No. 7.2.1]

Public Input No. 578-NFPA 72-2016 [New Section after A.7.2.1(1)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

55 of 496 10/20/2016 11:03 AM

Page 56: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 547-NFPA 72-2016 [ Section No. 7.3.2 ]

7.3.2*

Where required by governing laws, codes, or standards, or other parts of this Code, design (layout)documents shall be prepared prior to installing new systems and additions or alterations to existingsystems . (SIG-ECS)

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jul 29 12:15:40 EDT 2016

Committee Statement

CommitteeStatement:

The existing text only applies to new installations. Layout documents should be required priorto altering existing systems.

ResponseMessage:

Public Input No. 72-NFPA 72-2016 [Section No. 7.3.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

56 of 496 10/20/2016 11:03 AM

Page 57: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 548-NFPA 72-2016 [ Section No. 7.3.3 ]

7.3.3*

Where required by governing laws, codes, or standards, or other parts of this Code, preliminary plansshall be created. (SIG-ECS)

7.3.3.1

When an architect/engineer is preparing bid documents that will incorporate new or modifications to afire alarm or emergency communication system covered by this Code, preliminary bid documents shallbe prepared in accordance with Section 7.3 .

7.3.3.2

The architect/engineer shall be qualified to prepare fire alarm bid documents in accordance with10.5.1 .

7.3.3.3

Bid documents shall incorporate performance criteria to ensure that the system will provide a beneficialcomponent to the fire and life safety needs of the owner, occupants, and authority having jurisdiction.

7.3.3.4

Bid documents shall clearly communicate the intended performance and functionality expected by allbidding/installing contractors.

7.3.3.5

The architect/engineer shall ensure that areas incorporating voice communications will be finished out ina manner that intelligibility of messages can be achieved utilizing the emergency communicationsequipment as specified in bid documents and available to bidding contractors/installers.

Supplemental Information

File Name Description

A.7.3.3.docx Shows addition to annex material as part of FR

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jul 29 12:17:48 EDT 2016

Committee Statement

CommitteeStatement:

Engineers who are not qualified to call out, specify, or review shop drawings related to fire alarmsystems or suppression systems such as clean agent systems incorporating releasing panelsfrequently put a statement on drawings telling the contractor to install a system to Code and thatvoice systems shall be intelligible. However, the purpose of an owner hiring an engineer is to preparedesign bid documents that will benefit the owner, occupants, and the AHJ. The language is wordedto include fire alarm and voice systems such as MNS, area of refuge, stairway communications, etc.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

57 of 496 10/20/2016 11:03 AM

Page 58: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ResponseMessage:

Public Input No. 393-NFPA 72-2016 [Section No. 7.3.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

58 of 496 10/20/2016 11:03 AM

Page 59: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2508-NFPA 72-2016 [ Section No. 7.3.4.6 ]

7.3.4.6

Performance-based design alternatives for strobe visual notification appliance design shall be inaccordance with 18.5.5.6.2.

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 15:18:47 EDT 2016

Committee Statement

CommitteeStatement:

The term “strobe” is being changed to “visual notification appliance” to be consistent with theterminology used throughout the chapter and to coordinate with First Revision #2503.

ResponseMessage:

Public Input No. 263-NFPA 72-2016 [Section No. 7.3.4.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

59 of 496 10/20/2016 11:03 AM

Page 60: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2509-NFPA 72-2016 [ Section No. 7.3.7.2 ]

7.3.7.2

Performance-based design documentation for strobes visual notification appliances shall be inaccordance with 18.5.5.6.2. (SIG-NAS)

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 15:21:45 EDT 2016

Committee Statement

CommitteeStatement:

The term “strobe” is being changed to “visual notification appliance” to be consistent with theterminology used throughout the chapter and to coordinate with First Revision #2503.

ResponseMessage:

Public Input No. 264-NFPA 72-2016 [Section No. 7.3.7.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

60 of 496 10/20/2016 11:03 AM

Page 61: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1029-NFPA 72-2016 [ New Section after 7.3.7.3 ]

7.3.7.4

Performance-based design documentation for mass notification systems shall be in accordance withSection 24.14 .

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 23:27:17 EDT 2016

Committee Statement

CommitteeStatement:

Section 7.3.7 lists requirements for Performance-Based Design Documentation. Section 24.14 forEmergency Communication Systems has requirements for using performance-based designpractices on Mass Notification Systems; however, the requirement for Mass Notification Systemperformance-based design documentation is not listed in Section 7.3.7. Documentation requirementsfor Performance-Based Design in accordance with 24.14 should be listed in 7.3.7. The CorrelatingCommittee should determine which committee has purview over this new section.

ResponseMessage:

Public Input No. 81-NFPA 72-2016 [New Section after 7.3.7.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

61 of 496 10/20/2016 11:03 AM

Page 62: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1006-NFPA 72-2016 [ Section No. 7.5.6.2 ]

7.5.6.2*

The record of completion documentation shall be completed by the installing contractor and submitted tothe enforcing authority having jurisdiction and the owner at the conclusion of the job. The record ofcompletion documentation shall be permitted to be part of the written statement required in 7.5.2 and partof the documents that support the requirements of 7.5.8. When more than one contractor has beenresponsible for the installation, each contractor shall complete the portions of the documentation for whichthat contractor has responsibility.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 16:10:56 EDT 2016

Committee Statement

CommitteeStatement:

The term "enforcing authority" is not defined as is "authority having jurisdiction". AHJ is usedthroughout the Code as the term for the enforcing authority.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

62 of 496 10/20/2016 11:03 AM

Page 63: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1030-NFPA 72-2016 [ Section No. 7.5.6.4 ]

7.5.6.4

The record of completion documentation shall be updated in accordance with 7.5.6.6 to reflect all systemadditions or modifications.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 23:32:09 EDT 2016

Committee Statement

CommitteeStatement:

This Technical Committee revises this language to specifically call out the relevantsection.

Response Message:

Public Input No. 33-NFPA 72-2015 [Section No. 7.5.6.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

63 of 496 10/20/2016 11:03 AM

Page 64: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1031-NFPA 72-2016 [ Section No. 7.7.2.3 ]

7.7.2.3*

All record documentation shall be stored in the documentation cabinet. No record documentation shall bestored in the control unit.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 23:35:12 EDT 2016

Committee Statement

CommitteeStatement:

Currently, this is only a recommendation in the Annex. This FR will make the language mandatorywhile still tying it to the explanatory Annex text. The storage of paperwork, manuals, software, etc.in the control unit is commonplace and presents a very real fire hazard.

ResponseMessage:

Public Input No. 302-NFPA 72-2016 [Section No. 7.7.2.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

64 of 496 10/20/2016 11:03 AM

Page 65: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1002-NFPA 72-2016 [ Section No. 10.1.2 ]

10.1.2

The requirements of this chapter shall apply to systems, equipment, and components addressed inChapters 12 , 14 , 17 , 18 , 21 , 23 , 24 , 26 , and 27 .

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 11:50:49 EDT 2016

Committee Statement

CommitteeStatement:

This is redundant information because of a revision made to Chapter 1. See FR-1001 aftersection 1.3.4.

Response Message:

Public Input No. 727-NFPA 72-2016 [Section No. 10.1.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

65 of 496 10/20/2016 11:03 AM

Page 66: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1016-NFPA 72-2016 [ Section No. 10.3.4 ]

10.3.4

All apparatus requiring rewinding or resetting to maintain normal operation shall be restored to normalafter each abnormal condition and maintained in normal condition for operation .

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 22:12:38 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises the text to remove the redundant references to normaloperation.

Response Message:

Public Input No. 118-NFPA 72-2016 [Section No. 10.3.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

66 of 496 10/20/2016 11:03 AM

Page 67: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1017-NFPA 72-2016 [ New Section after 10.4.3 ]

10.4.4*

Fire alarm control unit displays and controls, which includes visible indicators, shall be mounted suchthat the distance to the highest switch, lamp, or textual display does not exceed 5.5 ft (1.7 m) above thefinished floor, and the lowest switch, lamp, or textual display shall not be less than 1.5 ft (0.4 m) abovethe finished floor.

Supplemental Information

File Name Description

2019NFPA72_FR1017_Annex_DV.docx Add this Annex material for this new section.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 22:14:02 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee adds a new section to include maximum and minimum mountingheight requirements for fire alarm control unit displays.

ResponseMessage:

Public Input No. 114-NFPA 72-2016 [New Section after 10.4.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

67 of 496 10/20/2016 11:03 AM

Page 68: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1018-NFPA 72-2016 [ Section No. 10.4.4 ]

10.4.5*

In Unless otherwise permitted by 10.4.5.1 , in areas that are not continuously occupied, early warningfire detection an automatic smoke detector shall be provided at the location of each control unit(s),notification appliance circuit power extender(s), and supervising station transmitting equipment to providenotification of fire at that location. by one of the following means:

(1) An automatic smoke detector provided at the location of each control unit(s), notification appliancecircuit power extender(s), and supervising station transmitting equipment

(2) Where ambient conditions prohibit installation of an automatic smoke detector, an automatic heatdetector shall be permitted.

Exception: Where ambient conditions prohibit installation of an automatic smoke detector, an automaticheat detector shall be permitted.

10.4.5.1

Smoke or heat detector(s) shall not be required to be installed at the location of dedicated function(s)fire alarm control unit(s) that are not required to provide local or supervising station notification signals.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 22:18:58 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text to maintain the requirement to provide early warningdetection for control unit(s), etc. but adds text to eliminate the requirement for dedicated functionsystems that do not provide notification.

ResponseMessage:

Public Input No. 696-NFPA 72-2016 [New Section after 10.4.4]

Public Input No. 293-NFPA 72-2016 [Section No. 10.4.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

68 of 496 10/20/2016 11:03 AM

Page 69: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1019-NFPA 72-2016 [ Section No. 10.5.1.1 ]

10.5.1.1

Fire alarm system, carbon monoxide detection systems, and emergency communications system plansand specifications shall be developed in accordance with this Code by persons who are experienced inthe design, application, installation, and testing of the systems.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 22:28:19 EDT 2016

Committee Statement

Committee Statement: The Technical Committee edits the text to include carbon monoxide detection systems.

Response Message:

Public Input No. 346-NFPA 72-2016 [Section No. 10.5.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

69 of 496 10/20/2016 11:03 AM

Page 70: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1020-NFPA 72-2016 [ Section No. 10.5.2.1 ]

10.5.2.1

Fire alarm systems , carbon monoxide detection systems, and emergency communications systemsinstallation personnel shall be qualified or shall be supervised by persons who are qualified in theinstallation, inspection, and testing of the systems.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 22:29:52 EDT 2016

Committee Statement

Committee Statement: The Technical Committee edits the text to include carbon monoxide detection systems.

Response Message:

Public Input No. 347-NFPA 72-2016 [Section No. 10.5.2.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

70 of 496 10/20/2016 11:03 AM

Page 71: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1035-NFPA 72-2016 [ Section No. 10.6.1 ]

10.6.1* Scope.

The provisions of this section shall apply to power supplies used for protected premises fire alarmsystems, supervising station alarm systems, public emergency alarm reporting systems, and emergencycommunications systems and equipment complying with this Code unless otherwise specified .

Exception: Low-power radio (wireless) systems that comply with the requirements of 23.16 .

Supplemental Information

File Name Description

A.10.6.1_DV.docx New annex text

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 16:18:11 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises the text to remove a growing list and exception. Whereexceptions are made, the system or component has text identifying specific power requirements[section 23.16 low-power radio (wireless) and section 29 household] Annex material is added toexplain where these exceptions are made.

ResponseMessage:

Public Input No. 348-NFPA 72-2016 [Section No. 10.6.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

71 of 496 10/20/2016 11:03 AM

Page 72: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1036-NFPA 72-2016 [ Section No. 10.6.4 ]

10.6.4 Uninterruptible Power Supplies (UPS).

Energy storage systems (ESS), including electrochemical energy storage systems, chemical energystorage systems, mechanical energy storage systems, and thermal energy storage systems.

10.6.4.1

The UPS ESS device shall be configured in compliance with NFPA 111 for a Type O 0 , Class 24, Level 1system.

10.6.4.2

Where connected to an engine-driven generator arranged in accordance with 10.6.11.3.1 , the ESSdevice shall be permitted to be configured in compliance with NFPA 111 for a Type 0, Class 4, Level 1system.

10.6.4.3

The UPS ESS device shall comply with the requirements of 10.6.5.

10.6.4.4

Failure of the UPS ESS shall result in the initiation of a trouble signal in accordance with Section 10.14.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 16:40:48 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises the text to reflect that UPS systems are a form of Energy StorageSystems (ESS) addressed by Article 706 of the 2017 NEC. Chapter 10 has not classified UPSpower as either primary or secondary, but has addressed it separately. The revised languageacknowledges the term ESS and allows for reduced energy storage capacity when used inconjunction with an Article 700 Legally Required Standby System.

ResponseMessage:

Public Input No. 110-NFPA 72-2016 [Section No. 10.6.4.1]

Public Input No. 109-NFPA 72-2016 [Section No. 10.6.7.3.1]

Public Input No. 572-NFPA 72-2016 [Section No. 10.6.7.3.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

72 of 496 10/20/2016 11:03 AM

Page 73: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1038-NFPA 72-2016 [ Section No. 10.6.5.1.2 ]

10.6.5.1.2

The branch circuit supplying the fire alarm equipment system component(s), carbon monoxide systemcomponent(s), or emergency communication system component(s) shall supply no other loads.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 16:54:59 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text to clarify that multiple pieces of equipment may beconnected to a single circuit.

ResponseMessage:

Public Input No. 349-NFPA 72-2016 [Section No. 10.6.5.1.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

73 of 496 10/20/2016 11:03 AM

Page 74: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1039-NFPA 72-2016 [ Section No. 10.6.5.2.2 ]

10.6.5.2.2*

The system circuit disconnecting means shall be permanently identified as to its purpose. Methods formarking shall be permitted to include, but not be limited to, one of the following: and marked as a firealarm system and/or a signaling system.

“FIRE ALARM” for fire alarm systems

“EMERGENCY COMMUNICATIONS” for emergency communications systems

“FIRE ALARM/ECS” for combination fire alarm and emergency communications systems

Supplemental Information

File Name Description

72_FR-1039_A.10.6.5.2.2_FUN.docx

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 17:00:28 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises this section to clarify how the branch circuit disconnecting meansmust be identified and removes examples in order to comply with the Manual of Style. In the annex,the Technical Committee edits the text to include "CARBON MONOXIDE" systems and movesexamples into the annex in accordance with the Manual of Style.

ResponseMessage:

Public Input No. 120-NFPA 72-2016 [Section No. 10.6.5.2.2]

Public Input No. 350-NFPA 72-2016 [Section No. 10.6.5.2.2]

Public Input No. 119-NFPA 72-2016 [Section No. A.10.6.5.2.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

74 of 496 10/20/2016 11:03 AM

Page 75: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1037-NFPA 72-2016 [ Sections 10.6.6.3.1, 10.6.6.3.2 ]

10.6.6.3.1

Storage batteries dedicated to the system or UPS ESS arranged in accordance with the provisions ofNFPA 111 shall be permitted to supplement the secondary power supply to ensure required operationduring the transfer period.

10.6.6.3.2

Where a UPS an ESS is employed in 10.6.6.3.1, a positive means for disconnecting the input and outputof the UPS ESS system while maintaining continuity of power supply to the load shall be provided.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 16:49:03 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises the text to reflect that UPS systems are a form of EnergyStorage Systems (ESS) addressed by Article 706 of the 2017 NEC.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

75 of 496 10/20/2016 11:03 AM

Page 76: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1040-NFPA 72-2016 [ Section No. 10.6.7.2.1 [Excluding any

Sub-Sections] ]

The secondary power supply shall have sufficient capacity to operate the system under quiescent load(system operating in a nonalarm condition) for a minimum of 24 hours and, at the end of that period, shallbe capable of operating all alarm notification appliances used for evacuation or to direct aid to the locationof an emergency for 5 minutes, unless otherwise permitted or required by 10.6.7.2.1.1 through10.6.7.2.2: .

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 17:02:58 EDT 2016

Committee Statement

Committee Statement: The Technical Committee revises the text to provide proper punctuation.

Response Message:

Public Input No. 657-NFPA 72-2016 [Section No. 10.6.7.2.1 [Excluding any Sub-Sections]]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

76 of 496 10/20/2016 11:03 AM

Page 77: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1041-NFPA 72-2016 [ New Section after 10.6.7.2.2 ]

10.6.7.2.3

Where carbon monoxide detection is not monitored by a supervising station, the secondary powersupply shall have sufficient capacity to operate the carbon monoxide detection system under quiescentload (system operating in a nonalarm condition) for a minimum of 24 hours and, at the end of thatperiod, shall be capable of operating the carbon monoxide detection system and all notificationappliances for 12 hours.

10.6.7.2.4

Where carbon monoxide detection is monitored by a supervising station, the secondary power supplyshall have sufficient capacity to operate the carbon monoxide detection system under quiescent load(system operating in a nonalarm condition) for a minimum of 24 hours and, at the end of that period,shall be capable of operating the carbon monoxide detection system and all notification appliances for 5minutes.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 17:07:43 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee incorporates the secondary power supply requirements formerly in NFPA720. The exception was revised into positive language to comply with the Manual of Style.Reference to 5.8.6.5 was removed as there is no Chapter 5 in NFPA 72, and it appears to involve arequirement other than secondary capacity. Reference to emergency response in accordance with7.2.2 was removed as it appears to relate to an NFPA 720 requirement not related to secondarycapacity.

ResponseMessage:

Public Input No. 351-NFPA 72-2016 [New Section after 10.6.7.2.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

77 of 496 10/20/2016 11:03 AM

Page 78: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1042-NFPA 72-2016 [ Section No. 10.6.10.2.3 ]

10.6.10.2.3

Battery cells Batteries shall be insulated against ground faults.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 17:11:14 EDT 2016

Committee Statement

Committee Statement: The Technical Committee revises this section to provide the correct terminology.

Response Message:

Public Input No. 145-NFPA 72-2016 [Section No. 10.6.10.2.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

78 of 496 10/20/2016 11:03 AM

Page 79: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1043-NFPA 72-2016 [ Section No. 10.6.10.2.5 ]

10.6.10.2.5

Battery cells Batteries shall be protected from physical damage.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 17:13:47 EDT 2016

Committee Statement

Committee Statement: The Technical Committee revises this section to provide the correct terminology.

Response Message:

Public Input No. 147-NFPA 72-2016 [Section No. 10.6.10.2.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

79 of 496 10/20/2016 11:03 AM

Page 80: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1049-NFPA 72-2016 [ Section No. 10.6.10.3.4 ]

10.6.10.3.4*

Batteries shall be either trickle-charged or float-charged charged by listed means .

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 06:43:36 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises this section to clarify that the means for charging batteriesmust be evaluated by a nationally recognized testing laboratory.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

80 of 496 10/20/2016 11:03 AM

Page 81: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1044-NFPA 72-2016 [ Section No. 10.6.11.7 ]

10.6.11.7 Battery and Charger.

10.6.11.7.1

A separate storage battery and separate automatic charger shall be provided for starting the engine-driven generator and shall not be used for any other purpose.

10.6.11.7.2

The battery shall be sized in accordance with 5.6.4 of NFPA 110 .

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 17:18:24 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text to provide subsections for multiple requirements per theManual of Style 1.8.3, and edits the reference to NFPA 110 to comply with the Manual of Style2.3.9.

ResponseMessage:

Public Input No. 148-NFPA 72-2016 [Section No. 10.6.11.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

81 of 496 10/20/2016 11:03 AM

Page 82: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1021-NFPA 72-2016 [ Section No. 10.10.1 ]

10.10.1

Priority alarms alarm signals , fire alarms, alarm signals, carbon monoxide alarm signals, supervisorysignals, pre-alarm signals, and trouble signals shall be distinctively and descriptively annunciated.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 22:32:20 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text to include carbon monoxide detection systems andinclude the use of the term “signal” after priority and fire alarms.

ResponseMessage:

Public Input No. 352-NFPA 72-2016 [Section No. 10.10.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

82 of 496 10/20/2016 11:03 AM

Page 83: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1034-NFPA 72-2016 [ New Section after 10.10.8 ]

10.10.9

Carbon monoxide alarm signals shall comply with 18.4.4.2 .

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 13:03:10 EDT 2016

Committee Statement

Committee Statement: The Technical Committee incorporates information formerly in NFPA 720 into NFPA 72.

Response Message:

Public Input No. 353-NFPA 72-2016 [New Section after 10.10.8]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

83 of 496 10/20/2016 11:03 AM

Page 84: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 551-NFPA 72-2016 [ Section No. 10.11.3 ]

10.11.3

Visible alarm strobe notification appliances shall not be activated when speaker notification appliancesare used as permitted by 24.3.5 for non-emergency paging. (SIG-ECS)

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jul 29 12:41:00 EDT 2016

Committee Statement

CommitteeStatement:

For uniformity throughout the document, the term “strobe” is deleted. Further it is understood thatSIG-NAS is reviewing the terms “visual” and “visible” and SIG-ECS requests the CorrelatingCommittee to review and take appropriate actions. The proposal to change the term speaker is notmade in order to keep in current alignment with the terms loudspeaker/speaker. The TechnicalCommittee requests the Correlating Committee review this action across all Technical Committees.

ResponseMessage:

Public Input No. 187-NFPA 72-2016 [Section No. 10.11.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

84 of 496 10/20/2016 11:03 AM

Page 85: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1023-NFPA 72-2016 [ Section No. 10.18.1 ]

10.18.1* Speaker Audio Amplifier and Tone-Generating Equipment.

If speakers loudspeakers are used to produce audible fire alarm signals, the required trouble signal for10.18.1.1 through 10.18.1.3 shall be in accordance with Section 10.14.

10.18.1.1

When primary power is available, failure of any audio amplifier shall result in a trouble signal.

10.18.1.2

When an alarm is present and primary power is not available (i.e., system is operating from the secondarypower source), failure of any audio amplifier shall result in a trouble signal.

10.18.1.3

Failure of any tone-generating equipment shall result in a trouble signal, unless the tone-generating andamplifying equipment are enclosed as integral parts and serve only a single, listed loudspeaker.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 22:43:14 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises the text from “speaker” in the heading to “audio” to match10.18.1.1 and 10.18.1.2 and replaces “speakers” with “loudspeakers” in the requirement.

ResponseMessage:

Public Input No. 188-NFPA 72-2016 [Section No. 10.18.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

85 of 496 10/20/2016 11:03 AM

Page 86: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3069-NFPA 72-2016 [ Section No. 12.2.3.3 ]

12.2.3.3*

Wiring methods permitted by other sections of this Code to resist attack by fire shall be installed inaccordance with manufacturer’s published instructions and the requirements of NFPA 70 Article 760 andArticle 728 .

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Sun Aug 07 13:56:22 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text of Section 12.2.3.3 to incorporate the reference to therequirements of NFPA 70 Article 728: Fire Resistive Cable Systems in addition to the existingreferenced requirements of Article 760: Fire Alarm Systems as both contain requirements relatingto the installation of wiring methods that resist attack by fire.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

86 of 496 10/20/2016 11:03 AM

Page 87: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 5003-NFPA 72-2016 [ Section No. 12.2.4 ]

12.2.4 Ground Connections.

12.2.4.1

All fire alarm systems shall test free of grounds.

Exception: Parts of circuits or equipment that are intentionally and permanently grounded to provideground-fault detection, noise suppression, emergency ground signaling, and circuit protection groundingshall be permitted.

12.2.4.2

The requirements of 12.2.4.1 shall not be required where parts of circuits or equipment areintentionally and permanently grounded in order to provide ground fault detection, noise suppression,emergency ground signals, and circuit protection grounding.

12.2.4.3*

On conductive pathways, operational capability shall be maintained during the application of a singleground connection.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Thu Aug 11 10:47:09 EDT 2016

Committee Statement

CommitteeStatement:

SIG-PRO eliminates specific exceptions to comply with Manual of Style. Some exceptionscannot be eliminated because they would result in a single subsection, which is not permitted in1.8 of the Manual of Style.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

87 of 496 10/20/2016 11:03 AM

Page 88: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3002-NFPA 72-2016 [ Section No. 12.3.8 ]

12.3.8* Class A, Class N, and Class X Pathway Separation.

Class A, Class N, and Class X circuits using physical conductors (e.g., metallic, optical fiber) shall beinstalled so that the primary and redundant, or outgoing and return, conductors, exiting from andreturning to the control unit, respectively, are routed separately.

12.3.8.1

The outgoing and return (redundant) circuit conductors shall be permitted in the same cable assembly(i.e., multiconductor cable), enclosure, or raceway only under the following conditions:

(1) For a distance not to exceed 10 ft (3.0 m) where the outgoing and return conductors enter or exit theinitiating device, notification appliance, or control unit enclosures

(2) Single drops installed in the raceway to individual devices or appliances

(3)

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Aug 03 11:26:23 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises 12.3.8 to extend pathway separation requirements to theredundant portions of Class N circuits. Major portions of Class N Circuits include two or morepathways where primary and redundant paths are to be utilized to maintain operational capabilitysimilar in concept to Class A and Class X circuits. Pathway separation of physical conductors needsto be implemented to reduce the likelihood of a single event affecting both paths.

ResponseMessage:

Public Input No. 650-NFPA 72-2016 [Section No. 12.3.8]

* In a single room not exceeding 1000 ft2 (93 m2) in area, a drop installed in the raceway to multipledevices or appliances that does not include any emergency control function devices

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

88 of 496 10/20/2016 11:03 AM

Page 89: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3001-NFPA 72-2016 [ Section No. 12.4.2 ]

12.4.2 Pathway Survivability Level 1.

Pathway survivability Level 1 shall consist of pathways in buildings that are fully protected by an automaticsprinkler system in accordance with NFPA 13 with any interconnecting conductors, cables, or otherphysical pathways installed in protected by metal raceways or metal armored cables .

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Aug 03 11:23:38 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text of 12.4.2 to permit the use of cables with a metallicarmor as an acceptable method of mechanical protection for conductors to achieve Level Isurvivability.

ResponseMessage:

Public Input No. 518-NFPA 72-2016 [Section No. 12.4.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

89 of 496 10/20/2016 11:03 AM

Page 90: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4507-NFPA 72-2016 [ New Section after 14.1.5 ]

14.1.6

The inspection, testing, and maintenance required by this chapter and NFPA 25 shall be coordinatedso that the system operates as intended.

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 20:08:21 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee adds this new section to clarify this coordinated effort, namely thatthe functions common to both systems operate as intended.

ResponseMessage:

Public Input No. 343-NFPA 72-2016 [New Section after 14.1.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

90 of 496 10/20/2016 11:03 AM

Page 91: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4508-NFPA 72-2016 [ New Section after 14.2.2.2.2 ]

14.2.2.2.3

During required testing, service, or maintenance of fire alarm systems, inspection, service, or testingpersonnel shall be permitted to make note of opportunities to improve or enhance existing systemperformance.

14.2.2.2.3.1

If opportunities to improve or enhance existing system performance are noted, such observations shallbe communicated to the system owner via official correspondence in the inspection and testing report orin a separate document.

14.2.2.2.3.2

The system owner shall only be required to consider, but shall not be required to authorize,implementation of any recommendations.

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 20:12:00 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee adds this new section to provide additional clarification to both thebuilding owner and service provider that recommendations are permitted but not required to beacted upon by this Code.

ResponseMessage:

Public Input No. 342-NFPA 72-2016 [New Section after 14.2.2.2.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

91 of 496 10/20/2016 11:03 AM

Page 92: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4522-NFPA 72-2016 [ Section No. 14.2.2.2.3 ]

14.2.2.2.4

If a deficiency is not corrected at the conclusion of system inspection, testing, or maintenance, the systemowner or the owner’s designated representative shall be informed of the impairment in writing deficiencyby official correspondence within 24 hours.

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jul 29 13:33:17 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text to be consistent with the new proposed definition ofofficial correspondence and adds the word deficiency to be consistent throughout the section.

ResponseMessage:

Public Input No. 15-NFPA 72-2015 [Section No. 14.2.2.2.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

92 of 496 10/20/2016 11:03 AM

Page 93: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4523-NFPA 72-2016 [ Section No. 14.2.2.2.4 ]

14.2.2.2.5

In the event that any equipment is observed to be part of a recall program, the system owner or thesystem owner's designated representative shall be notified in writing by official correspondence .

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jul 29 13:37:11 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text to be consistent with the new proposed definition ofofficial correspondence.

ResponseMessage:

Public Input No. 16-NFPA 72-2015 [Section No. 14.2.2.2.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

93 of 496 10/20/2016 11:03 AM

Page 94: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4521-NFPA 72-2016 [ Section No. 14.2.10.1 ]

14.2.10.1

A test plan shall be written developed to clearly establish the scope of the testing for the fire alarm orsignaling system.

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jul 29 13:30:42 EDT 2016

Committee Statement

Committee Statement: The Technical Committee edits the text to clarify that this section is to develop a test plan.

Response Message:

Public Input No. 31-NFPA 72-2015 [Section No. 14.2.10.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

94 of 496 10/20/2016 11:03 AM

Page 95: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4533-NFPA 72-2016 [ Section No. 14.3.1 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

95 of 496 10/20/2016 11:03 AM

Page 96: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

14.3.1*

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

96 of 496 10/20/2016 11:03 AM

Page 97: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Unless otherwise permitted by 14.3.2, visual inspections shall be performed in accordance with theschedules in Table 14.3.1 or more often if required by the authority having jurisdiction.

Table 14.3.1 Visual Inspection

ComponentInitial

AcceptancePeriodic

FrequencyMethod Reference

1. All equipment X Annual

Ensure there are nochanges that affectequipment performance.Inspect for buildingmodifications, occupancychanges, changes inenvironmental conditions,device location, physicalobstructions, deviceorientation, physicaldamage, and degree ofcleanliness.

14.3.4

2. Control equipment:

 (a 1 ) Fire alarm systemsmonitored for alarm,supervisory, and troublesignals

Verify a system normalcondition.

  (1 a ) Fuses X Annual

  (2 b ) Interfacedequipment

X Annual

  (3 c ) Lamps and LEDs X Annual

  (4 d ) Primary (main)power supply

X Annual

  (5 e ) Trouble signals X Semiannual

 (b 2 ) Fire alarm systemsunmonitored for alarm,supervisory, and troublesignals

Verify a system normalcondition.

  (1 a ) Fuses X Weekly

  (2 b ) Interfacedequipment

X Weekly

  (3 c ) Lamps and LEDs X Weekly

  (4 d ) Primary (main)power supply

X Weekly

  (5 e ) Trouble signals X Weekly

3. Reserved

4.Supervising station alarmsystems — transmitters

Verify location, physicalcondition, and a systemnormal condition.

 (a 1 ) Digital alarmcommunicator transmitter(DACT)

X Annual

 (b 2 ) Digital alarm radiotransmitter (DART)

X Annual

 (c 3 ) McCulloh X Annual

 (d 4 ) Radio alarmtransmitter (RAT)

X Annual

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

97 of 496 10/20/2016 11:03 AM

Page 98: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

AcceptancePeriodic

FrequencyMethod Reference

 (e 5 ) All other types ofcommunicators

X Annual

5.In-building fire emergencyvoice/alarmcommunications equipment

X SemiannualVerify location andcondition.

6. Reserved

7. Reserved

8. Reserved

9.* Batteries

Inspect for corrosion orleakage. Verify tightnessof connections. Verifymarking of themonth/year ofmanufacture (alltypes). Ensure monthand year of manufactureis marked in themonth/year format oneach battery cell/unit.

10.6.10

 (a 1 ) Lead-acid Valve-regulated lead-acid(VRLA) batteries

X Monthly Semiannual

Visually inspectelectrolyte level. Verifymarking of themonth/year ofmanufacture on eachbattery cell/unit. Replaceany cell/unit if alarmequipmentmanufacturer’sreplacement date hasbeen exceeded.

 (b) Nickel-cadmium X Semiannual

Verify tightness of batteryconnections. Inspectterminals for corrosion,excessivecontainer/coverdistortion, cracks incell/unit or leakage ofelectrolyte. Replace anybattery cell/unit ifcorrosion, distortion, orleakage is observed.

 (c 2 ) Primary (dry cell) X Monthly Semiannual

Verify marking of themonth/year ofmanufacture. Replace ifalarm equipment/batterymanufacturer’sreplacement date hasbeen exceeded.Replacement date not toexceed 12 months. Verifytightness of connections.Inspect for corrosion orleakage. Replace anybattery cell/unit ifcorrosion or leakage isobserved.

 (d) Sealed lead-acid X Semiannual

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

98 of 496 10/20/2016 11:03 AM

Page 99: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

AcceptancePeriodic

FrequencyMethod Reference

10. Reserved

11. Remote annunciators X SemiannualVerify location andcondition.

12.Notification appliancecircuit power extenders

X Annual

Verify proper fuse ratings,if any. Verify that lampsand LEDs indicate normaloperating status of theequipment.

10.6

13. Remote power supplies X Annual

Verify proper fuse ratings,if any. Verify that lampsand LEDs indicate normaloperating status of theequipment.

10.6

14. Transient suppressors X SemiannualVerify location andcondition.

15. Reserved

16.Fiber-optic cableconnections

X AnnualVerify location andcondition.

17. Initiating devicesVerify location andcondition (all devices).

 (a 1 ) Air sampling

  (1 a ) General X SemiannualVerify that in-line filters, ifany, are clean.

17.7.3.6

  (2 b ) Sampling systempiping and sampling ports

X N/A

Verify that samplingsystem piping and fittingsare installed properly,appear airtight, and arepermanently fixed.Confirm that samplingpipe is conspicuouslyidentified. Verify thatsample ports or pointsare not obstructed.

17.7.3.6

 (b 2 ) Duct detectors

  (1 a ) General X Semiannual

Verify that detector isrigidly mounted. Confirmthat no penetrations in areturn air duct exist in thevicinity of the detector.Confirm the detector isinstalled so as to samplethe airstream at theproper location in theduct.

17.7.5.5

  (2 b ) Sampling tube X Annual

Verify proper orientation.Confirm the samplingtube protrudes into theduct in accordance withsystem design.

17.7.5.5

 (c 3 ) Electromechanicalreleasing devices

X Semiannual

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

99 of 496 10/20/2016 11:03 AM

Page 100: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

AcceptancePeriodic

FrequencyMethod Reference

 (d 4 ) Fire extinguishingsystem(s) or suppressionsystem(s) switches

X Semiannual

 (e 5 ) Manual fire alarmboxes

X Semiannual

 (f 6 ) Heat detectors X Semiannual

 (g 7 ) Radiant energy firedetectors

X Quarterly

Verify no point requiringdetection is obstructed oroutside the detector’sfield of view.

17.8

 (h 8 ) Video imagesmoke and fire detectors

X Quarterly

Verify no point requiringdetection is obstructed oroutside the detector’sfield of view.

17.7.7;17.11.5

 (i) 9 ) Smoke detectors(excluding one- andtwo-family dwellings)

X Semiannual

 (j 10 ) Projected beamsmoke detectors

X SemiannualVerify beam path isunobstructed.

 (k 11 ) Supervisory signaldevices

X Quarterly

 (l 12 ) Waterflow devices X Quarterly

18. Reserved

19. Combination systemsVerify location andcondition (all types).

 (a 1 ) Fire extinguisherelectronic monitoringdevice devices /systems

X Semiannual

 (b 2 ) Carbon monoxidedetectors/systems

X Semiannual

20.Fire alarm control interfaceand emergency controlfunction interface

X SemiannualVerify location andcondition.

21. Guard’s tour equipment X SemiannualVerify location andcondition.

22. Notification appliancesVerify location andcondition (all appliances).

 (a 1 ) Audible appliances X Semiannual

 (b 2 ) Audible textualnotificationappliances Loudspeakers

X Semiannual

 (c 3 ) Visible appliances

  (1 a ) General X Semiannual 18.5.5

  (2 b ) Candela rating X N/A

Verify that the appliancecandela rating marking orthe FACU controlledcandela rating agreeswith the approveddrawings.

18.5.5

23.Exit marking audiblenotification appliances

X SemiannualVerify location andcondition.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

100 of 496 10/20/2016 11:03 AM

Page 101: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

AcceptancePeriodic

FrequencyMethod Reference

24. Reserved

25.

Area of refugetwo-way Two-wayemergencycommunications systems

X AnnualVerify location andcondition.

26. Reserved

27.Supervising station alarmsystems — receivers

 (a 1 ) Signal receipt X Daily Verify receipt of signal.

 (b 2 ) Receivers X AnnualVerify location and normalcondition.

28.Public emergency alarmreporting systemtransmission equipment

Verify location andcondition.

 (a 1 ) Publicly accessiblealarm box

X Semiannual

 (b 2 ) Auxiliary box X Annual

 (c 3 ) Master box

  (1 a ) Manualoperation

X Semiannual

  (2 b ) Auxiliaryoperation

X Annual

29. Reserved

30. Mass notification system

 (a 1 ) Monitored forintegrity

Verify a system normalcondition.

  (1 a ) Controlequipment

   (i) Fuses X Annual

   (ii) Interfaces X Annual

   (iii) Lamps/LED X Annual

   (iv) Primary (main)power supply

X Annual

  (2 b ) Secondarypower batteries

X Annual

  (3 c ) Initiating devices X Annual

  (4 d ) Notificationappliances

X Annual

 (b 2 ) Not monitored forintegrity; installed prior toadoption of the 2010edition

Verify a system normalcondition.

  (1 a ) Controlequipment

   (i) Fuses X Semiannual

   (ii) Interfaces X Semiannual

   (iii) Lamps/LED X Semiannual

   (iv) Primary (main)power supply

X Semiannual

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

101 of 496 10/20/2016 11:03 AM

Page 102: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

AcceptancePeriodic

FrequencyMethod Reference

  (2 b ) Secondarypower batteries

X Semiannual

  (3 c ) Initiating devices X Semiannual

  (4 d ) Notificationappliances

X Semiannual

 (c 3 ) Antenna X AnnualVerify location andcondition.

 (d 4 ) Transceivers X AnnualVerify location andcondition.

Note: N/A = not applicable, no minimum requirement established.

* For other than VRLA or primary (dry) cell batteries, refer to the battery manufacturer’s instructions orIEEE 450, Recommended Practice for Maintenance, Testing, and Replacement of Vented Lead-AcidBatteries for Stationary Applications , for vented lead-acid batteries, and IEEE 1106, RecommendedPractice for Installation, Maintenance, Testing, and Replacement of Vented Nickel-Cadmium Batteries forStationary Applications , for nickel-cadmium batteries.

Supplemental Information

File Name Description

72-2016_Table_14_3_1_from_Sonia.docxAll of the requested changes are attached in this word file. For staff use

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 08:14:16 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee made multiple changes throughout the table to adhere to guidancefrom the Correlating Committee, to increase clarity of requirements and to include new batterytechnologies.

ResponseMessage:

Public Input No. 522-NFPA 72-2016 [Chapter 14]

Public Input No. 649-NFPA 72-2016 [Section No. 14.3.1]

Public Input No. 134-NFPA 72-2016 [Section No. 14.4.3.2]

Public Input No. 149-NFPA 72-2016 [New Section after 14.3.1]

Public Input No. 519-NFPA 72-2016 [Section No. 14.3.1]

Public Input No. 131-NFPA 72-2016 [Section No. 14.3.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

102 of 496 10/20/2016 11:03 AM

Page 103: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4534-NFPA 72-2016 [ Section No. 14.4.3.2 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

103 of 496 10/20/2016 11:03 AM

Page 104: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

14.4.3.2*

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

104 of 496 10/20/2016 11:03 AM

Page 105: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Systems and associated equipment shall be tested according to Table 14.4.3.2.

Table 14.4.3.2 Testing

ComponentInitial

Acceptance

Periodic

FrequencyMethod

1. All equipment X See Table 14.3.1.

2.Control equipment andtransponder

 (a 1 ) Functions X Annually

Verify correct receipt of alarm, supervisory,and trouble signals (inputs); operation ofevacuation signals and auxiliary functions(outputs); circuit supervision, includingdetection of open circuits and ground faults;and power supply supervision for detectionof loss of ac power and disconnection ofsecondary batteries.

 (b 2 ) Fuses X Annually Verify rating and supervision.

 (c 3 ) Interfacedequipment

X Annually

Verify integrity of single or multiple circuitsproviding interface between two or morecontrol units. Test interfaced equipmentconnections by operating or simulatingoperation of the equipment beingsupervised. Verify signals required to betransmitted at the control unit.

 (d 4 ) Lamps and LEDs X Annually Illuminate lamps and LEDs.

 (e 5 ) Primary (main)power supply

X Annually

Test under maximum load, including allalarm appliances requiring simultaneousoperation. Test redundant power suppliesseparately.

3.Fire alarm control unittrouble signals

 (a 1 ) Audible and visual X Annually

Verify operation of control unit troublesignals. Verify ring-back feature for systemsusing a trouble-silencing switch that requiresresetting.

 (b 2 ) Disconnect switches X Annually

If control unit has disconnect or isolatingswitches, verify performance of intendedfunction of each switch. Verify receipt oftrouble signal when a supervised function isdisconnected.

 (c 3 ) Ground-faultmonitoring circuit

X Annually

If the system has a ground detection feature,verify the occurrence of ground-faultindication whenever any installationconductor is grounded.

 (d 4 ) Transmission ofsignals to off-premiseslocation

X AnnuallyActuate an initiating device and verify receiptof alarm signal at the off-premises location.

Create a trouble condition and verify receiptof a trouble signal at the off-premiseslocation.

Actuate a supervisory device and verifyreceipt of a supervisory signal at theoff-premises location. If a transmissioncarrier is capable of operation under asingle- or multiple-fault condition, activate aninitiating device during such fault condition

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

105 of 496 10/20/2016 11:03 AM

Page 106: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

Acceptance

Periodic

FrequencyMethod

and verify receipt of an alarm signal and atrouble signal at the off-premises location.

4.Supervising station alarmsystems — transmissionequipment

 (a 1 ) All equipment X Annually

aTest all system functions and features inaccordance with the equipmentmanufacturer’s published instructions forcorrect operation in conformance with theapplicable sections of Chapter 26.

Except for DACT, actuate initiating deviceand verify receipt of the correct initiatingdevice signal at the supervising station within90 seconds. Upon completion of the test,restore the system to its functional operatingcondition.

If test jacks are used, conduct the first andlast tests without the use of the test jack.

 (b 2 ) Digital alarmcommunicator transmitter(DACT)

X Annually

Except for DACTs installed prior to adoptionof the 2013 edition of NFPA 72 that areconnected to a telephone line (number) thatis also supervised for adverse conditions bya derived local channel, ensure connectionof the DACT to two separate means oftransmission.

Test DACT for line seizure capability byinitiating a signal while using the telephoneline (primary line for DACTs using twotelephone lines) for a telephone call. Ensurethat the call is interrupted and that thecommunicator connects to the digital alarmreceiver. Verify receipt of the correct signal atthe supervising station. Verify eachtransmission attempt is completed within90 seconds from going off-hook to on-hook.

Disconnect the telephone line (primary linefor DACTs using two telephone lines) fromthe DACT. Verify indication of the DACTtrouble signal occurs at the premises firealarm control unit within 4 minutes ofdetection of the fault. Verify receipt of thetelephone line trouble signal at thesupervising station. Restore the telephoneline (primary line for DACTs using twotelephone lines), reset the fire alarm controlunit, and verify that the telephone line faulttrouble signal returns to normal. Verify thatthe supervising station receives the restoralsignal from the DACT.

Disconnect the secondary means oftransmission from the DACT. Verifyindication of the DACT trouble signal occursat the premises fire alarm control unit within4 minutes of detection of the fault. Verifyreceipt of the secondary means trouble

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

106 of 496 10/20/2016 11:03 AM

Page 107: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

Acceptance

Periodic

FrequencyMethod

signal at the supervising station. Restore thesecondary means of transmission, reset thefire alarm control unit, and verify that thetrouble signal returns to normal. Verify thatthe supervising station receives the restoralsignal from the secondary transmitter.

Cause the DACT to transmit a signal to theDACR while a fault in the telephone line(number) (primary line for DACTs using twotelephone lines) is simulated. Verifyutilization of the secondary communicationspath by the DACT to complete thetransmission to the DACR.

 (c 3 ) Digital alarm radiotransmitter (DART)

X Annually

Disconnect the primary telephone line. Verifytransmission of a trouble signal to thesupervising station by the DART occurswithin 4 minutes.

 (d 4 ) McCullohtransmitter

X Annually

Actuate initiating device. Verify production ofnot less than three complete rounds of notless than three signal impulses each by theMcCulloh transmitter.

If end-to-end metallic continuity is presentand with a balanced circuit, cause each ofthe following four transmission channel faultconditions in turn, and verify receipt ofcorrect signals at the supervising station:

(1) Open

(2) Ground

(3) Wire-to-wire short

(4) Open and ground

If end-to-end metallic continuity is notpresent and with a properly balanced circuit,cause each of the following threetransmission channel fault conditions in turn,and verify receipt of correct signals at thesupervising station:

(1) Open

(2) Ground

(3) Wire-to-wire short

 (e 5 ) Radio alarmtransmitter (RAT)

X Annually

Cause a fault between elements of thetransmitting equipment. Verify indication ofthe fault at the protected premises, ortransmission of trouble signal to thesupervising station.

 (f 6 ) Performance-basedtechnologies

X Annually

Perform tests to ensure the monitoring ofintegrity of the transmission technology andtechnology path.

Where shared communications equipment isused as permitted by 26.6.3.1.14, providedsecondary (standby) power sources shall betested in accordance with Table 14.4.3.2,item 7, 8, or 9, as applicable.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

107 of 496 10/20/2016 11:03 AM

Page 108: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

Acceptance

Periodic

FrequencyMethod

Where a single communications path isused, disconnect the communication path.Manually initiate an alarm signaltransmission or allow the check-in(handshake) signal to be transmitted

automatically.b Verify the premises unitannunciates the failure within 200 seconds ofthe transmission failure. Restore thecommunication path.

Where multiple communication paths areused, disconnect both communication paths.Manually initiate an alarm signaltransmission. Verify the premises control unitannunciates the failure within 200 seconds ofthe transmission failure. Restore bothcommunication paths.

5.Emergency communicationsequipment

 (a 1 ) Amplifier/tonegenerators

X AnnuallyVerify correct switching and operation ofbackup equipment.

 (b 2 ) Call-in signalsilence

X AnnuallyOperate/function and verify receipt of correctvisual and audible signals at control unit.

 (c 3 ) Off-hook indicator(ring down)

X AnnuallyInstall phone set or remove phone from hookand verify receipt of signal at control unit.

 (d 4 ) Phone jacks X AnnuallyVisually inspect phone jack and initiatecommunications path through jack.

 (e 5 ) Phone set X AnnuallyActivate each phone set and verify correctoperation.

 (f 6 ) System performance X AnnuallyOperate the system with a minimum of anyfive handsets simultaneously. Verify voicequality and clarity.

6. Engine-driven generator X Monthly

If an engine-driven generator dedicated tothe system is used as a required powersource, verify operation of the generator andtransfer switch in accordance with NFPA 110by the building owner.

7.Secondary (standby) power

supplyc X Annually

Disconnect all primary (main) power suppliesand verify the occurrence of required troubleindication for loss of primary power. Measureor verify the system’s standby and alarmcurrent demand using the equipmentmanufacturer’s data and verify the ability ofbatteries to meet standby and alarmrequirements using manufacturer’sdata battery’s rated capacity exceeds thesystem’s power demand, including thesafety margin . Operate general alarmsystems a minimum of 5 minutes andemergency voice communications systemsfor a minimum of 15 minutes. Reconnectprimary (main) power supply at end of test.

8.Uninterruptible powersupply (UPS)

X Annually

If a UPS system dedicated to the system isused as a required power source, verify bythe building owner operation of the UPS

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

108 of 496 10/20/2016 11:03 AM

Page 109: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

Acceptance

Periodic

FrequencyMethod

system in accordance with NFPA 111.

9. Battery testsd

Prior to conducting any battery testing, verifyby the person conducting the test that allsystem software stored in volatile memory isprotected from loss.

 (a 1 ) Lead-acid type

  (1 a ) Batteryreplacement

X Annually

Replace batteries in accordance with therecommendations of the alarm equipmentmanufacturer or when the recharged batteryvoltage or current falls below themanufacturer’s recommendations.

  (2 b ) Charger test X Annually

With the batteries fully charged andconnected to the charger, measure thevoltage across the batteries with a voltmeter.Verify the voltage is 2.30 volts per cell±0.02 volts at 77°F (25°C) or as specified bythe equipment manufacturer.

  (3 c ) Discharge test X Annually

With the battery charger disconnected, loadtest the batteries following themanufacturer’s recommendations. Verify thevoltage level does not fall below the levelsspecified. Load testing can be by means ofan artificial load equal to the full fire alarmload connected to the battery.

  (4 d ) Load voltage test X Semiannually

With the battery charger disconnected, loadtest the batteries following themanufacturer’s recommendations. Verify thevoltage level does not fall below the levelsspecified. Load testing can be by means ofan artificial load equal to the full fire alarmload connected to the battery. Verify thebattery does not fall below 2.05 volts per cellunder load.

  (5 e ) Specific gravity X Semiannually

Measure as required the specific gravity ofthe liquid in the pilot cell or all of the cells.Verify the specific gravity is within the rangespecified by the manufacturer. Although thespecified specific gravity varies frommanufacturer to manufacturer, a range of1.205–1.220 is typical for regular lead-acidbatteries, while 1.240–1.260 is typical forhigh-performance batteries. Do not use ahydrometer that shows only a pass or failcondition of the battery and does not indicatethe specific gravity, because such a readingdoes not give a true indication of the batterycondition.

 (b 2 ) Nickel-cadmiumtype

  (1 a ) Batteryreplacement

X Annually

Replace batteries in accordance with therecommendations of the alarm equipmentmanufacturer or when the recharged batteryvoltage or current falls below themanufacturer’s recommendations.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

109 of 496 10/20/2016 11:03 AM

Page 110: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

Acceptance

Periodic

FrequencyMethod

  (2 b ) Charger testd e X Annually

With the batteries fully charged andconnected to the charger, place an amperemeter in series with the battery undercharge. Verify the charging current is inaccordance with the manufacturer’srecommendations for the type of batteryused. In the absence of specific information,use 1⁄30 to 1⁄25 of the battery rating.

  (3 c ) Discharge test X Annually

With the battery charger disconnected, loadtest the batteries following themanufacturer’s recommendations. Verify thevoltage level does not fall below the levelsspecified. Load testing can be by means ofan artificial load equal to the full fire alarmload connected to the battery.

  (4 d ) Load voltage test X Semiannually

With the battery charger disconnected, loadtest the batteries following themanufacturer’s recommendations. Verify thevoltage level does not fall below the levelsspecified. Load testing can be by means ofan artificial load equal to the full fire alarmload connected to the battery. Verify the floatvoltage for the entire battery is 1.42 volts percell, nominal, under load. If possible,measure cells individually.

 (c 3 ) Sealed lead-acidtype

  (1 a ) Batteryreplacement

X Annually

Replace batteries in accordance with therecommendations of the alarm equipmentmanufacturer or when the recharged batteryvoltage or current falls below themanufacturer’s recommendations.

  (2 b ) Charger test X Annually

With the batteries fully charged andconnected to the charger, measure thevoltage across the batteries with a voltmeter.Verify the voltage is 2.30 volts per cell±0.02 volts at 77°F (25°C) or as specified bythe equipment manufacturer.

  (3 c ) Discharge test X Annually

With the battery charger disconnected, loadtest the batteries following themanufacturer’s recommendations. Verify thevoltage level does not fall below the levelsspecified. Load testing can be by means ofan artificial load equal to the full fire alarmload connected to the battery.

  (4 d ) Load voltage test X SemiannuallyVerify the battery performs under load, inaccordance with the battery manufacturer’sspecifications.

(4) Alternate batteries suchas lithium-ion

(a) Battery replacement

Replace batteries in accordance with therecommendations of the alarm equipmentmanufacturer or when the recharged batteryvoltage or current falls below themanufacturer’s recommendations.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

110 of 496 10/20/2016 11:03 AM

Page 111: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

Acceptance

Periodic

FrequencyMethod

(b) Charger test f

With the batteries fully charged andconnected to the charger, measure thevoltage across the batteries with a voltmeter.Verify the voltage is a specified by theequipment manufacturer.

(c) Discharge test g

With the battery charger disconnected, loadtest the batteries following themanufacturer’s recommendations. Verify thevoltage level does not fall below the levelsspecified. Load testing can be by means ofan artificial load equal to the full fire alarmload connected to the battery.

(d) Load voltage test hVerify the battery performs under load, inaccordance with the battery manufacturer’sspecifications.

10.Public emergency alarmreporting system — wiredsystem

X Daily

Manual tests of the power supply for publicreporting circuits shall be made andrecorded at least once during each 24-hourperiod. Such tests shall include the following:

(1) Current strength of each circuit. Changesin current of any circuit exceeding 10 percentshall be investigated immediately.

(2) Voltage across terminals of each circuitinside of terminals of protective devices.Changes in voltage of any circuit exceeding10 percent shall be investigated immediately.

(3)e i Voltage between ground and circuits. Ifthis test shows a reading in excess of50 percent of that shown in the test specifiedin (2), the trouble shall be immediatelylocated and cleared. Readings in excess of25 percent shall be given early attention.These readings shall be taken with acalibrated voltmeter of not more than100 ohms resistance per volt. Systems inwhich each circuit is supplied by anindependent current source (Forms 3 and 4)require tests between ground and each sideof each circuit. Common current sourcesystems (Form 2) require voltage testsbetween ground and each terminal of eachbattery and other current source.

(4) Ground current reading shall bepermitted in lieu of (3). If this method oftesting is used, all grounds showing acurrent reading in excess of 5 percent of thesupplied line current shall be givenimmediate attention.

(5) Voltage across terminals of commonbattery on switchboard side of fuses.

(6) Voltage between common batteryterminals and ground. Abnormal groundreadings shall be investigated immediately.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

111 of 496 10/20/2016 11:03 AM

Page 112: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

Acceptance

Periodic

FrequencyMethod

Tests specified in (5) and (6) shall apply onlyto those systems using a common battery. Ifmore than one common battery is used,each common battery shall be tested.

11. Remote annunciators X Annually

Verify the correct operation and identificationof annunciators. If provided, verify thecorrect operation of annunciator under a faultcondition.

12. Reserved

13. Reserved

14. Reserved

15. Conductors — metallic

 (a 1 ) Stray voltage X N/A

Test all installation conductors with avolt/ohmmeter to verify that there are nostray (unwanted) voltages betweeninstallation conductors or betweeninstallation conductors and ground. Verify themaximum allowable stray voltage does notexceed 1 volt ac/dc, unless a differentthreshold is specified in the publishedmanufacturer's instructions for the installedequipment.

 (b 2 ) Ground faults X N/A

Test all installation conductors, other thanthose intentionally and permanentlygrounded, for isolation from ground per theinstalled equipment manufacturer’spublished instructions.

 (c 3 ) Short-circuit faults X N/A

Test all installation conductors, other thanthose intentionally connected together, forconductor-to-conductor isolation per thepublished manufacturer's instructions for theinstalled equipment. Also test these samecircuits conductor-to-ground.

 (d 4 ) Loop resistance X N/A

With each initiating and indicating circuitinstallation conductor pair short-circuited atthe far end, measure and record theresistance of each circuit. Verify that the loopresistance does not exceed the limitsspecified in the published manufacturer'sinstructions for the installed equipment.

 (e 5 ) Circuit integrity X N/A

For initial and reacceptance testing, confirmthe introduction of a fault in any circuitmonitored for integrity results in a troubleindication at the fire alarm control unit. Openone connection at not less than 10 percent ofthe initiating devices, notification appliancesand controlled devices on every initiatingdevice circuit, notification appliance circuit,and signaling line circuit. Confirm all circuitsperform as indicated in Sections 23.5, 23.6,and 23.7.

N/A Annually

For periodic testing, test each initiatingdevice circuit, notification appliance circuit,and signaling line circuit for correct indication

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

112 of 496 10/20/2016 11:03 AM

Page 113: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

Acceptance

Periodic

FrequencyMethod

at the control unit. Confirm all circuitsperform as indicated in Sections 23.5, 23.6,and 23.7.

16. Conductors — nonmetallic

 (a 1 ) Fiber optics X N/A

Test the fiber-optic transmission line by theuse of an optical power meter or by anoptical time domain reflectometer used tomeasure the relative power loss of the line.Test result data must meet or exceedANSI/TIA 568-C.3, Optical Fiber CablingComponents Standard, related to fiber-opticlines and connection/splice losses and thecontrol unit manufacturer’s publishedspecifications.

 (b 2 ) Circuit integrity X N/A

For initial and reacceptance testing, confirmthe introduction of a fault in any circuitmonitored for integrity results in a troubleindication at the fire alarm control unit. Openone connection at not less than 10 percent ofthe initiating devices, notification appliances,and controlled devices on every initiatingdevice circuit, notification appliance circuit,and signaling line circuit. Confirm all circuitsperform as indicated in Sections 23.5, 23.6,and 23.7.

N/A Annually

For periodic testing, test each initiatingdevice circuit, notification appliance circuit,and signaling line circuit for correct indicationat the control unit. Confirm all circuitsperform as indicated in Sections 23.5, 23.6,and 23.7.

17. Initiating devicesf j

 (a 1 ) Electromechanicalreleasing device

  (1 a )Nonrestorable-type link

X Annually

Verify correct operation by removal of thefusible link and operation of the associateddevice. Lubricate any moving parts asnecessary.

  (2 b ) Restorable-type

linkg k X Annually

Verify correct operation by removal of thefusible link and operation of the associateddevice. Lubricate any moving parts asnecessary.

 (b 2 ) Fire extinguishingsystem(s) or suppressionsystem(s) alarm switch

X AnnuallyOperate the switch mechanically orelectrically and verify receipt of signal by thefire alarm control unit.

 (c 3 ) Fire–gas and otherdetectors

X AnnuallyTest fire–gas detectors and other firedetectors as prescribed by the manufacturerand as necessary for the application.

 (d 4 ) Heat detectors

  (1 a ) Fixed-temperature, rate-of-rise,rate of compensation,restorable line, spot type(excluding pneumatic tube

X

Annually

(see14.4.4.5)

Perform heat test with a listed and labeledheat source or in accordance with themanufacturer’s published instructions.Assure that the test method for the installedequipment does not damage the

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

113 of 496 10/20/2016 11:03 AM

Page 114: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

Acceptance

Periodic

FrequencyMethod

type)nonrestorable fixed-temperature element ofa combination rate-of-rise/fixed-temperatureelement detector.

  (2 b ) Fixed-temperature, nonrestorableline type

X Annually

Do not perform heat test. Test functionalitymechanically and electrically. Measure andrecord loop resistance. Investigate changesfrom acceptance test.

  (3 c ) Fixed-temperature, nonrestorablespot type

X See Method

After 15 years from initial installation, replaceall devices or have 2 detectors per 100laboratory tested. Replace the 2 detectorswith new devices. If a failure occurs on anyof the detectors removed, remove and testadditional detectors to determine either ageneral problem involving faulty detectors ora localized problem involving 1 or 2 defectivedetectors.

If detectors are tested instead of replaced,repeat tests at intervals of 5 years.

  (4 d ) Nonrestorable(general)

X AnnuallyDo not perform heat tests. Test functionalitymechanically and electrically.

  (5 e ) Restorable linetype, pneumatic tube only

X Annually

Perform heat tests (where test chambers arein circuit), with a listed and labeled heatsource or in accordance with themanufacturer's published instructions of thedetector or conduct a test with pressurepump.

  (6 f ) Single- andmultiple-station heat alarms

X Annually

Conduct functional tests according tomanufacturer’s published instructions. Donot test nonrestorable heat detectors withheat.

 (e 5 ) Manual fire alarmboxes

X Annually

Operate manual fire alarm boxes per themanufacturer’s published instructions. Testboth key-operated presignal and generalalarm manual fire alarm boxes.

 (f 6 ) Radiant energy firedetectors

X Semiannually

Test flame detectors and spark/emberdetectors in accordance with themanufacturer’s published instructions todetermine that each detector is operative.

Determine flame detector and spark/emberdetector sensitivity using any of thefollowing:

(1) Calibrated test method

(2) Manufacturer’s calibrated sensitivity testinstrument

(3) Listed control unit arranged for thepurpose

(4) Other approved calibrated sensitivity testmethod that is directly proportional to theinput signal from a fire, consistent with thedetector listing or approval

If designed to be field adjustable, replacedetectors found to be outside of theapproved range of sensitivity or adjust tobring them into the approved range.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

114 of 496 10/20/2016 11:03 AM

Page 115: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

Acceptance

Periodic

FrequencyMethod

Do not determine flame detector andspark/ember detector sensitivity using a lightsource that administers an unmeasuredquantity of radiation at an undefined distancefrom the detector.

 (g 7 ) Smoke detectors —functional test

  (1 a ) In other than one-and two-family dwellings,system detectors

X Annually

h I Test smoke detectors in place to ensuresmoke entry into the sensing chamber andan alarm response. Use smoke or a listedand labeled product acceptable to themanufacturer or in accordance with theirpublished instructions. Other methods listedin the manufacturer's published instructionsthat ensure smoke entry from the protectedarea, through the vents, into the sensingchamber can be used.

  (2 b ) Single- andmultiple-station smokealarms connected toprotected premises systems

X Annually

Perform a functional test on all single- andmultiple-station smoke alarms connected toa protected premises fire alarm system byputting the smoke alarm into an alarmcondition and verifying that the protectedpremises system receives a supervisorysignal and does not cause a fire alarmsignal .

  (3 c ) System smokedetectors used in one- andtwo-family dwellings

X AnnuallyConduct functional tests according tomanufacturer’s published instructions.

  (4 d ) Air sampling X Annually

Test with smoke or a listed and labeledproduct acceptable to the manufacturer or inaccordance with their published instructions.Test from the end sampling port or point oneach pipe run. Verify airflow through all otherports or points.

  (5 e ) Duct type X Annually

In addition to the testing required in Table14.4.3.2(g)(1) and Table 14.4.3.2(h), testduct smoke detectors that use samplingtubes to ensure that they will properlysample the airstream in the duct using amethod acceptable to the manufacturer or inaccordance with their published instructions.

  (6 f ) Projected beamtype

X AnnuallyTest the detector by introducing smoke, otheraerosol, or an optical filter into the beampath.

  (7 g ) Smoke detectorwith built-in thermal element

X AnnuallyOperate both portions of the detectorindependently as described for therespective devices.

  (8 h ) Smoke detectorswith control output functions

X Annually

Verify that the control capability remainsoperable even if all of the initiating devicesconnected to the same initiating devicecircuit or signaling line circuit are in an alarmstate.

 (h 8 ) Smoke detectors —sensitivity testing

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

115 of 496 10/20/2016 11:03 AM

Page 116: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

Acceptance

Periodic

FrequencyMethod

  In other than one- andtwo-family dwellings, systemdetectors

N/A See 14.4.4.3

i m Perform any of the following tests toensure that each smoke detector is within itslisted and marked sensitivity range:

(1) Calibrated test method

(2) Manufacturer’s calibrated sensitivity testinstrument

(3) Listed control equipment arranged for thepurpose

(4) Smoke detector/control unit arrangementwhereby the detector causes a signal at thecontrol unit when its sensitivity is outside itslisted sensitivity range

(5) Other calibrated sensitivity test methodapproved by the authority having jurisdiction

 (i 9 ) Carbon monoxidedetectors/carbon monoxidealarms for the purposes offire detection

X Annually

Test the devices in place to ensure CO entryto the sensing chamber by introductionthrough the vents, to the sensing chamber oflisted and labeled product acceptable to themanufacturer or in accordance with theirpublished instructions.

 (j 10 ) Initiating devices,supervisory

  (1 a ) Control valveswitch

X Semiannual

Operate valve and verify signal receipt to bewithin the first two revolutions of thehandwheel or within one-fifth of the traveldistance, or per the manufacturer’spublished instructions. Continue to cycleoutside stem and yoke valves and verifyswitch does not reset during full travel of thevalve stem.

  (2 b ) High- or low-airpressure switch

X Annually

Operate switch and verify receipt of signal isobtained where the required pressure isincreased or decreased a maximum 10 psi(70 kPa) from the required pressure level.

  (c) Steam pressure X Annually

Operate switch and verify receipt of signal isobtained before pressure decreases to 110percent of the minimum operating pressureof the steam-operated equipment.

  (d) Pressuresupervisory devices forother sources

X Annually

Operate switch and verify receipt of signal isobtained where the required pressure isincreased or decreased from the normaloperating pressure by an amount specifiedin approved design documents.

  (3 e ) Roomtemperature switch

X Annually

Operate switch and verify receipt of signal toindicate the decrease in room temperature to40°F (4.4°C) and its restoration to above40°F (4.4°C).

  (4 f ) Water level switch X Annually

Operate switch and verify receipt of signalindicating the water level raised or lowered amaximum 3 in. (70 mm) from the requiredlevel within a pressure tank, or a maximum12 in. (300 mm) from the required level of anonpressure tank. Also verify its restoral torequired level.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

116 of 496 10/20/2016 11:03 AM

Page 117: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

Acceptance

Periodic

FrequencyMethod

  (5 g ) Watertemperature switch

X Annually

Operate switch and verify receipt of signal toindicate the decrease in water temperatureto 40°F (4.4°C) and its restoration to above40°F (4.4°C).

 (k 11 ) Mechanical,electrosonic, orpressure-type waterflowdevice 

X Semiannually

Water shall be flowed through an inspector'stest connection indicating the flow of waterequal to that from a single sprinkler of thesmallest orifice size installed in the systemor other listed and approved waterflowswitch test methods for wet-pipe systems, oran alarm test bypass connection for dry-pipe,pre-action, or deluge systems in accordancewith NFPA 25.

 (l 12 ) Multi-sensor firedetector or multi-criteria firedetector or combination firedetector

X Annually

Test each of the detection principles presentwithin the detector (e.g., smoke/heat/CO,etc.) independently for the specific detectionprinciple, regardless of the configurationstatus at the time of testing. Also test eachdetector in accordance with the publishedmanufacturer's instructions.

  Test individual sensors together if thetechnology allows individual sensorresponses to be verified.

  

Perform tests as described for the respectivedevices by introduction of the physicalphenomena to the sensing chamber ofelement. An electronic check (magnets,analog values, etc.) is not sufficient tocomply with this requirement.

Verify by using the detector manufacturer'spublished instructions that the test gas usedwill not impair the operation of either sensingchamber of a multisensor, multicriteria, orcombination fire detector.

  Confirm the result of each sensor testthrough indication at the detector or controlunit.

  Where individual sensors cannot be tested

individually, test the primary sensor.j n

   Record all tests and results.

18. Special hazard equipment

 (a 1 ) Abort switch(dead-man type)

X AnnuallyOperate abort switch and verify correctsequence and operation.

 (b 2 ) Abort switch(recycle type)

X AnnuallyOperate abort switch and verify developmentof correct matrix with each sensor operated.

 (c 3 ) Abort switch(special type)

X Annually

Operate abort switch and verify correctsequence and operation in accordance withauthority having jurisdiction. Observesequencing as specified on as-built drawingsor in system owner’s manual.

 (d 4 ) Cross-zonedetection circuit

X Annually

Operate one sensor or detector on eachzone. Verify occurrence of correct sequencewith operation of first zone and then withoperation of second zone.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

117 of 496 10/20/2016 11:03 AM

Page 118: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

Acceptance

Periodic

FrequencyMethod

 (e 5 ) Matrix-type circuit X AnnuallyOperate all sensors in system. Verifydevelopment of correct matrix with eachsensor operated.

 (f 6 ) Release solenoid

circuitk o X Annually Verify operation of solenoid.

 (g 7 ) Squibb releasecircuit

X AnnuallyUse AGI flashbulb or other test lightapproved by the manufacturer. Verifyoperation of flashbulb or light.

 (h 8 ) Verified, sequential,or counting zone circuit

X Annually

Operate required sensors at a minimum offour locations in circuit. Verify correctsequence with both the first and seconddetector in alarm.

 (i 9 ) All above devices orcircuits or combinationsthereof

X AnnuallyVerify supervision of circuits by creating anopen circuit.

19. Combination systems

 (a 1 ) Fire extinguisherelectronic monitoringdevice/system

X Annually

Test communication between the deviceconnecting the fire extinguisher electronicmonitoring device/system and the fire alarmcontrol unit to ensure proper signals arereceived at the fire alarm control unit andremote annunciator(s) if applicable.

 (b 2 ) Carbon

monoxidel device/systemX Annually

Test communication between the deviceconnecting the carbon monoxidedevice/system and the fire alarm control unitto ensure proper signals are received at thefire alarm control unit and remoteannunciator(s) if applicable.

20. Interface equipmentm p X See 14.4.4.4

Test interface equipment connections byoperating or simulating the equipment beingsupervised. Verify signals required to betransmitted are received at the control unit.Test frequency for interface equipment is thesame as the frequency required by theapplicable NFPA standard(s) for theequipment being supervised.

21. Guard’s tour equipment X AnnuallyTest the device in accordance with themanufacturer’s published instructions.

22.Alarm notificationappliances

 (a 1 ) Audiblen q X N/A

For initial and reacceptance testing, measuresound pressure levels for signals with asound level meter meeting ANSI S1.4a,Specifications for Sound Level Meters, Type2 requirements. Measure sound pressurelevels throughout the protected area toconfirm that they are in compliance withChapter 18. Set the sound level meter inaccordance with ANSI/ASA S3.41,American National Standard AudibleEmergency Evacuation Signal, using thetime-weighted characteristic F (FAST).

N/A Annuallyo r For periodic testing, verify the operationof the notification appliances.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

118 of 496 10/20/2016 11:03 AM

Page 119: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

Acceptance

Periodic

FrequencyMethod

 (b 2 ) Audible textualnotification appliances(speakers and otherappliances to convey voicemessages)

X N/A

For initial and reacceptance testing, measuresound pressure levels for signals with asound level meter meeting ANSI S1.4a,Specifications for Sound Level Meters, Type2 requirements. Measure sound pressurelevels throughout the protected area toconfirm that they are in compliance withChapter 18. Set the sound level meter inaccordance with ANSI/ASA S3.41,American National Standard AudibleEmergency Evacuation Signal, using thetime-weighted characteristic F (FAST).

Verify audible information to bedistinguishable andunderstandable intelligible and incompliance with 14.4.11 14.4.10 .

N/A Annuallyo r For periodic testing, verify the operationof the notification appliances.

 (c 3 ) Visible X N/A

Perform initial and reacceptance testing inaccordance with the manufacturer’spublished instructions. Verify appliancelocations to be per approved layout andconfirm that no floor plan changes affect theapproved layout. Verify that the candelarating or method of candela control markingon each visible appliance and rating whenreported by the FACU agrees with theapproved drawings . Confirm that eachappliance flashes.

N/A AnnuallyFor periodic testing, verify that eachappliance flashes.

23.Exit marking audiblenotification appliance

X AnnuallyPerform tests in accordance withmanufacturer's published instructions.

24.Emergency control

functionsp s X Annually

For initial, reacceptance, and periodictesting, verify emergency control functioninterface device activation. Where anemergency control function interface deviceis disabled or disconnected during initiatingdevice testing, verify that the disabled ordisconnected emergency control functioninterface device has been properly restored,including electromagnetic devices used fordoor releasing services as part of a firealarm system .

25.

Area of refugetwo-way Two-wayemergencycommunications systems

X Annually

Use the manufacturer’s publishedinstructions and the as-built drawingsprovided by the system supplier to verifycorrect operation after the initial testingphase has been performed by the supplier orby the supplier’s designated representative.

Test the two-way communication system toverify operation and receipt of visual andaudible signals at the transmitting unit andthe receiving unit, respectively.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

119 of 496 10/20/2016 11:03 AM

Page 120: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

Acceptance

Periodic

FrequencyMethod

Operate systems with more than five stationswith a minimum of five stations operatingsimultaneously.

Verify voice quality and clarity.

Verify directions for the use of the two-waycommunication system, instructions forsummoning assistance via the two-waycommunication system, and writtenidentification of the location is postedadjacent to the two-way communicationsystem.

Verify that all remote stations are readilyaccessible.

Verify the timed automatic communicationscapability to connect with a constantlyattended monitoring location per 24.5.3.4.

26. Special procedures

 (a 1 ) Alarm verification X AnnuallyVerify time delay and alarm response forsmoke detector circuits identified as havingalarm verification.

 (b 2 ) Multiplex systems X AnnuallyVerify communications between sending andreceiving units under both primary andsecondary power.

Verify communications between sending andreceiving units under open-circuit and short-circuit trouble conditions.

Verify communications between sending andreceiving units in all directions wheremultiple communications pathways areprovided.

If redundant central control equipment isprovided, verify switchover and all requiredfunctions and operations of secondarycontrol equipment.

Verify all system functions and features inaccordance with manufacturer’s publishedinstructions.

27.Supervising station alarmsystems — receivingequipment

 (a 1 ) All equipment X Monthly

Perform tests on all system functions andfeatures in accordance with the equipmentmanufacturer’s published instructions forcorrect operation in conformance with theapplicable sections of Chapter 26.

Actuate initiating device and verify receipt ofthe correct initiating device signal at thesupervising station within 90 seconds. Uponcompletion of the test, restore the system toits functional operating condition.

If test jacks are used, perform the first andlast tests without the use of the test jack.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

120 of 496 10/20/2016 11:03 AM

Page 121: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

Acceptance

Periodic

FrequencyMethod

 (b 2 ) Digital alarmcommunicator receiver(DACR)

X Monthly

Disconnect each transmission means in turnfrom the DACR, and verify audible and visualannunciation of a trouble signal in thesupervising station.

Cause a signal to be transmitted on eachindividual incoming DACR line (path) at leastonce every 6 hours (24 hours for DACTsinstalled prior to adoption of the 2013 editionof NFPA 72). Verify receipt of these signals.

 (c 3 ) Digital alarm radioreceiver (DARR)

X Monthly

Cause the following conditions of all DARRson all subsidiary and repeater stationreceiving equipment. Verify receipt at thesupervising station of correct signals foreach of the following conditions:

(1) AC power failure of the radio equipment

(2) Receiver malfunction

(3) Antenna and interconnecting cable failure

(4) Indication of automatic switchover of theDARR

(5) Data transmission line failure betweenthe DARR and the supervising or subsidiarystation

 (d 4 ) McCulloh systems X MonthlyTest and record the current on each circuit ateach supervising and subsidiary stationunder the following conditions:

(1) During functional operation

(2) On each side of the circuit with thereceiving equipment conditioned for an opencircuit

Cause a single break or ground condition oneach transmission channel. If such a faultprevents the functioning of the circuit, verifyreceipt of a trouble signal.

Cause each of the following conditions ateach of the supervising or subsidiary stationsand all repeater station radio transmittingand receiving equipment; verify receipt ofcorrect signals at the supervising station:

(1) RF transmitter in use (radiating)

(2) AC power failure supplying the radioequipment

(3) RF receiver malfunction

(4) Indication of automatic switchover

 (e 5 ) Radio alarmsupervising station receiver(RASSR) and radio alarmrepeater station receiver(RARSR)

X Monthly

Cause each of the following conditions ateach of the supervising or subsidiary stationsand all repeater station radio transmittingand receiving equipment; verify receipt ofcorrect signals at the supervising station:

(1) AC power failure supplying the radioequipment

(2) RF receiver malfunction

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

121 of 496 10/20/2016 11:03 AM

Page 122: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

Acceptance

Periodic

FrequencyMethod

(3) Indication of automatic switchover, ifapplicable

 (f 6 ) Private microwaveradio systems

X Monthly

Cause each of the following conditions ateach of the supervising or subsidiary stationsand all repeater station radio transmittingand receiving equipment; verify receipt ofcorrect signals at the supervising station:

(1) RF transmitter in use (radiating)

(2) AC power failure supplying the radioequipment

(3) RF receiver malfunction

(4) Indication of automatic switchover

 (g 7 ) Performance-basedtechnologies

X Monthly

Perform tests to ensure the monitoring ofintegrity of the transmission technology andtechnology path.

Where a single communications path isused, disconnect the communication path.Verify that failure of the path is annunciatedat the supervising station within 60 minutesof the failure (within 5 minutes forcommunication equipment installed prior toadoption of the 2013 edition of NFPA 72).Restore the communication path.

Where multiple communication paths areused, disconnect both communication pathsand confirm that failure of the path isannunciated at the supervising station withinnot more than 6 hours of the failure (within24 hours for communication equipmentinstalled prior to adoption of the 2013 editionof NFPA 72). Restore both communicationpaths.

28.Public emergency alarmreporting systemtransmission equipment

 (a 1 ) Publicly accessiblealarm box

X Semiannually

Actuate publicly accessible initiatingdevice(s) and verify receipt of not less thanthree complete rounds of signal impulses.Perform this test under normal circuitconditions. If the device is equipped for opencircuit operation (ground return), test it in thiscondition as one of the semiannual tests.

 (b 2 ) Auxiliary box X Annually

Test each initiating circuit of the auxiliary boxby actuation of a protected premisesinitiating device connected to that circuit.Verify receipt of not less than three completerounds of signal impulses.

 (c 3 ) Master box

  (1 a ) Manual operation X Semiannually Perform the tests prescribed for 28(a).

  (2 b ) Auxiliaryoperation

X Annually Perform the tests prescribed for 28(b).

29.Low-power radio (wirelesssystems)

X N/AThe following procedures describe additionalacceptance and reacceptance test methods

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

122 of 496 10/20/2016 11:03 AM

Page 123: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

Acceptance

Periodic

FrequencyMethod

to verify wireless protection systemoperation:

(1) Use the manufacturer’s publishedinstructions and the as-built drawingsprovided by the system supplier to verifycorrect operation after the initial testingphase has been performed by the supplier orby the supplier’s designated representative.

(2) Starting from the functional operatingcondition, initialize the system in accordancewith the manufacturer’s publishedinstructions. Confirm the alternativecommunications path exists between thewireless control unit and peripheral devicesused to establish initiation, indication,control, and annunciation. Test the systemfor both alarm and trouble conditions.

(3) Check batteries for all components in thesystem monthly unless the control unitchecks all batteries and all componentsdaily.

30. Mass notification systems

(a 1 ) Functions X Annually

At a minimum, test control equipment toverify correct receipt of alarm, supervisory,and trouble signals (inputs); operation ofevacuation signals and auxiliary functions(outputs); circuit supervision, includingdetection of open circuits and ground faults;and power supply supervision for detectionof loss of ac power and disconnection ofsecondary batteries.

(b 2 ) Fuses X Annually Verify the rating and supervision.

(c 3 ) Interfaced equipment X Annually

Verify integrity of single or multiple circuitsproviding interface between two or morecontrol units. Test interfaced equipmentconnections by operating or simulatingoperation of the equipment beingsupervised. Verify signals required to betransmitted at the control unit.

(d 4 ) Lamps and LEDs X Annually Illuminate lamps and LEDs.

(e 5 ) Primary (main) powersupply

X Annually

Disconnect all secondary (standby) powerand test under maximum load, including allalarm appliances requiring simultaneousoperation. Reconnect all secondary(standby) power at end of test. Forredundant power supplies, test eachseparately.

(f 6 ) Audible textualnotification appliances(speakers and otherappliances to convey voicemessages)

X Annually

Measure sound pressure level with a soundlevel meter meeting ANSI S1.4a,Specifications for Sound Level Meters, Type2 requirements. Measure and record levelsthroughout protected area. Set the soundlevel meter in accordance with ANSI/ASAS3.41, American National Standard AudibleEmergency Evacuation Signal, using the

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

123 of 496 10/20/2016 11:03 AM

Page 124: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ComponentInitial

Acceptance

Periodic

FrequencyMethod

time-weighted characteristic F (FAST).Record the maximum output when theaudible emergency evacuation signal is on.

Verify audible information to bedistinguishable and understandable.

(g 7 ) Visible X Annually

Perform test in accordance withmanufacturer’s published instructions. Verifyappliance locations to be per approvedlayout and confirm that no floor plan changesaffect the approved layout. Verify that thecandela rating or method of candela controlmarking on each visible appliance and ratingwhen reported by the FACU agrees with theapproved drawings . Confirm that eachappliance flashes.

(h 8 ) Control unit functionsand no diagnostic failuresare indicated

X Annually

Review event log file and verify that thecorrect events were logged. Review systemdiagnostic log file; correct deficiencies notedin file. Delete unneeded log files. Deleteunneeded error files. Verify that sufficientfree disk space is available. Verifyunobstructed flow of cooling air is available.Change/clean filters, cooling fans, and intakevents.

(i 9 ) Control unit reset X AnnuallyPower down the central control unitcomputer and restart it.

(j 10 ) Control unit security X AnnuallyIf remote control software is loaded onto thesystem, verify that it is disabled to preventunauthorized system access.

(k 11 ) Audible/visiblefunctional test

X Annually

Send out an alert to a diverse set ofpredesignated receiving devices and confirmreceipt. Include at least one of each type ofreceiving device.

(l 12 ) Software backup X AnnuallyMake full system software backup. Rotatebackups based on accepted practice at site.

(m 13 ) Secondary powertest

X Annually

Disconnect ac power. Verify the ac powerfailure alarm status on central controlequipment. With ac power disconnected,verify battery voltage under load.

(n 14 ) Wireless signals X AnnuallyCheck forward/reflected radio power is withinspecifications.

(o 15 ) Antenna X AnnuallyCheck forward/reflected radio power is withinspecifications. Verify solid electricalconnections with no observable corrosion.

(p 16 ) Transceivers X AnnuallyVerify proper operation and mounting is notcompromised.

aSome transmission equipment (such as, but not limited to, cable modems, fiber-optic interface nodes,and VoIP interfaces) are typically powered by the building's electrical system using a secondary (standby)power supply that does not meet the requirements of this Code. This is intended to ensure that the testingauthority verifies full secondary (standby) power as required by Chapter 10. Additionally, refer to Table14.4.3.2, items 7 through 9, for secondary (standby) power supply testing.

bThe automatic transmission of the check-in (handshake) signal can take up to 60 minutes to occur.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

124 of 496 10/20/2016 11:03 AM

Page 125: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

cSee Table 14.4.3.2, Item 4(a 1 ) for the testing of transmission equipment.

d The battery tests in Table 14.4.3.2 Item 9 are based on VRLA batteries and it the intent that the testsspecified in (1) through (4) be performed in order. For other secondary battery types, refer to the batterymanufacturer’s instructions or IEEE 450, Recommended Practice for Maintenance, Testing, andReplacement of Vented Lead-Acid Batteries for Stationary Applications , for vented lead-acid batteries,and IEEE 1106, Recommended Practice for Installation, Maintenance, Testing, and Replacement ofVented Nickel-Cadmium Batteries for Stationary Applications , for nickel-cadmium batteries.

eExample: 4000 mAh × 1⁄25 = 160 mA charging current at 77°F (25°C).

f If the charger is adjustable, adjust the output voltage to 2.265 volts per cell ±0.015 v olts at 77°F (25°C)or as specified by the alarm equipment manufacturer.

g See A.14.4.3.2 Item 9(4). A load test per Item 9(5) is permitted in lieu of an ohmic test. [Annex materialto follow]

h See A.14.4.3.2 Item 9(5). [Annex material to follow]

e i The voltmeter sensitivity has been changed from 1000 ohms per volt to 100 ohms per volt so that thefalse ground readings (caused by induced voltages) are minimized.

f j Initiating devices such as smoke detectors used for elevator recall, closing dampers, or releasing doorsheld in the open position that are permitted by the Code (seeNFPA 101 9.6.3 of NFPA 101 ) to initiatesupervisory signals at the fire alarm control unit (FACU) should be tested at the same frequency (annual)as those devices when they are generating an alarm signal. They are not supervisory devices, but theyinitiate a supervisory signal at the FACU.

g k Fusible thermal link detectors are commonly used to close fire doors and fire dampers electricallyconnected to the fire alarm control unit . They are actuated by the presence of external heat, which causesa solder element in the link to fuse, or by an electric thermal device, which, when energized, generatesheat within the body of the link, causing the link to fuse and separate.

h l Note, it is customary for the manufacturer of the smoke detector to test a particular product from anaerosol provider to determine acceptability for use in smoke entry testing of their smoke detector/ smokealarm. Magnets are not acceptable for smoke entry tests.

i m There are some detectors that use magnets as a manufacturer's calibrated sensitivity test instrument.

j n For example, it might not be possible to individually test the heat sensor in a thermally enhancedsmoke detector.

k o Manufacturer's instructions should be consulted to ensure a proper operational test. No suppressiongas or agent is expected to be discharged during the test of the solenoid. See Test Plan of 14.2.10.

l Testing of CO device should be done to the requirements of NFPA 720 .

m p A monitor module installed on an interface device is not considered a supervisory device andtherefore not subject to the quarterly testing frequency requirement. Test frequencies for interface devicesshould be in accordance with the applicable standard. For example, fire pump controller alarms such asphase reversal are required to be tested annually. If a monitor module is installed to identify phasereversal on the fire alarm control panel, it is not necessary to test for phase reversal four times a year.

n q Chapter 18 would require 15 dB over average ambient sound for public mode spaces. Sometimes theambient sound levels are different from what the design was based upon. Private operating mode wouldrequire 10 dB over average ambient at the location of the device.

o r Where building, system, or occupancy changes have been observed, the owner should be notified ofthe changes. New devices might need to be installed and tested per the initial acceptance testing criteria.

p s See A.14.4.3.2, and Table 14.4.3.2, Item 24.

Supplemental Information

File Name Description

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

125 of 496 10/20/2016 11:03 AM

Page 126: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

72-2016_Table_14_4_3_2_from_Sonia.docxAll of the requested changes to this table are included in this word document. For staff use

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 08:23:00 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee makes multiple changes to this table under guidance from theCorrelating Committee, to increase clarity of requirements and to include new batterytechnologies.

ResponseMessage:

Public Input No. 630-NFPA 72-2016 [Section No. 14.4.3.2]

Public Input No. 451-NFPA 72-2016 [Section No. 14.4.3.2]

Public Input No. 547-NFPA 72-2016 [Section No. 14.4.3.2]

Public Input No. 301-NFPA 72-2016 [Section No. 14.4.3.2]

Public Input No. 180-NFPA 72-2016 [Section No. 14.4.3.2]

Public Input No. 7-NFPA 72-2015 [Section No. 14.4.3.2]

Public Input No. 133-NFPA 72-2016 [New Section after 14.4.3.2]

Public Input No. 338-NFPA 72-2016 [Section No. 14.4.3.2]

Public Input No. 254-NFPA 72-2016 [Section No. 14.4.3.2]

Public Input No. 672-NFPA 72-2016 [Section No. 14.4.3.2]

Public Input No. 739-NFPA 72-2016 [Section No. 14.4.3.2]

Public Input No. 135-NFPA 72-2016 [Section No. 14.4.3.2]

Public Input No. 520-NFPA 72-2016 [Section No. 14.4.3.2]

Public Input No. 521-NFPA 72-2016 [Section No. 14.4.3.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

126 of 496 10/20/2016 11:03 AM

Page 127: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4510-NFPA 72-2016 [ New Section after 14.4.3.4 ]

14.4.3.5 Testing of CO System Detectors.

For all carbon monoxide system detectors installed after January 1, 2012, carbon monoxide tests shallbe performed at initial acceptance and annually by the introduction of carbon monoxide into the sensingchamber or element.

14.4.3.5.1

An electronic check (e.g., magnets, analog values, and so on) shall comply with the requirements of14.4.3.5.1.

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 23:07:56 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee provides new language to incorporate NFPA 720 requirements intoChapter 14 in accordance with the guidance of the Correlating Committee.

ResponseMessage:

Public Input No. 356-NFPA 72-2016 [New Section after 14.4.3.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

127 of 496 10/20/2016 11:03 AM

Page 128: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4511-NFPA 72-2016 [ Section No. 14.4.4.5.4 ]

14.4.4.5.5

Carbon monoxide apparatus that require resetting to maintain normal operation shall be restored tonormal as promptly as possible after each test and alarm and kept in normal condition for operation. Alltest signals received shall be recorded to indicate date and time.

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 23:08:40 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee provides new language to incorporate NFPA 720 requirements intoChapter 14 in accordance with the guidance of the Correlating Committee.

ResponseMessage:

Public Input No. 357-NFPA 72-2016 [Section No. 14.4.4.5.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

128 of 496 10/20/2016 11:03 AM

Page 129: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1533-NFPA 72-2016 [ Section No. 14.4.5 ]

14.4.5 Single- and Multiple-Station Smoke Alarms. (SIG-HOU)

14.4.5.1

Single- and multiple-station smoke alarms and connected appliances shall be inspected, tested, andmaintained in accordance with 14.4.5 and the manufacturer's published instructions.

14.4.5.2

Smoke alarms Alarms and connected appliances shall be inspected and tested at least monthly.

14.4.5.3*

The responsibility for inspection, testing, and maintenance of smoke alarms and connected appliancesshall be in accordance with 14.2.3.

14.4.5.4

Smoke alarms Alarms shall be replaced when they fail to respond to operability tests.

14.4.5.4.1

Smoke alarms shall not remain in service longer than 10 years from the date of manufacture, unlessotherwise provided by the manufacturer’s published instructions.

Detail FR-5050

14.4.5.4.2

Carbon monoxide alarms shall be replaced when either the end-of-life signal is activated or themanufacturer’s replacement date is reached.

14.4.5.5

Combination smoke/carbon monoxide alarms shall be replaced when the end-of-life signal activates or 10years from the date of manufacture, whichever comes first, unless otherwise provided by themanufacturer's published instructions.

14.4.5.6

Where batteries are used as a source of energy for smoke alarms or combination smoke/carbonmonoxide alarms or single- and multiple-station smoke alarms , the batteries shall be replaced inaccordance with the alarm equipment manufacturer’s published instructions.

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 11:17:46 EDT 2016

Committee Statement

CommitteeStatement:

The Standards Council approved the consolidation of NFPA 720 and NFPA 72 and directed thecurrent material that is within the existing NFPA 720 to be relocated into the next edition of NFPA 72.The Correlating Committee on Signaling Systems for the Protection of Life and Property appointedthe 720/72 Consolidation Task Group to review and effect the necessary changes. Requirements for

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

129 of 496 10/20/2016 11:03 AM

Page 130: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

carbon monoxide are being incorporated into this section.

ResponseMessage:

Public Input No. 358-NFPA 72-2016 [New Section after 14.4.5.4.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

130 of 496 10/20/2016 11:03 AM

Page 131: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1534-NFPA 72-2016 [ Section No. 14.4.6 ]

14.4.6 Household Fire Alarm Systems.

14.4.6.1 Testing.

Household fire alarm systems shall be tested by a qualified service technician at least annually accordingto the methods of Table 14.4.3.2. The installing contractor shall be required to provide this information inwriting to the customer upon completion of the system installation. To the extent that the fire alarm systemis monitored offsite, the supervising station contractor shall provide notice of this requirement to thecustomer on a yearly basis. (SIG-HOU)

14.4.6.2 Maintenance.

Maintenance of household fire alarm systems shall be conducted according to the manufacturer’spublished instructions. (SIG-HOU)

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 11:29:17 EDT 2016

Committee Statement

CommitteeStatement:

Requiring a qualified technician to conduct an annual test in Household is not enforceable.Maintaining a household system is the responsibility of the protected premise's owner not theinstalling company or supervising station.

ResponseMessage:

Public Input No. 627-NFPA 72-2016 [Section No. 14.4.6.1]

Public Input No. 760-NFPA 72-2016 [Section No. 14.4.6.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

131 of 496 10/20/2016 11:03 AM

Page 132: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4513-NFPA 72-2016 [ New Section after 14.4.7 ]

14.4.8 Household Carbon Monoxide Detection Systems.

14.4.8.1 Testing of Household Carbon Monoxide Detection Systems.

14.4.8.1.1

Household carbon monoxide detection systems shall be tested by a qualified service technician at leastevery 3 years according to the methods in line 1 of Table 14.4.3.2 .

14.4.8.1.2

Carbon monoxide detectors shall be replaced when the end-of-life signal is activated, themanufacturer’s replacement date is reached, or when they fail to respond to operability tests.

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 23:10:18 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee provides new language to incorporate NFPA 720 requirements intoChapter 14 in accordance with the guidance of the Correlating Committee.

ResponseMessage:

Public Input No. 359-NFPA 72-2016 [New Section after 14.4.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

132 of 496 10/20/2016 11:03 AM

Page 133: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4514-NFPA 72-2016 [ New Section after 14.6.2.4 ]

14.6.2.5

The system shall be clearly identified by a placard, sticker, or other means to indicate the next regularlyscheduled inspection, test, or maintenance.

Exception: If the devices have been tested as part of the normal carbon monoxide alarm testing, theexisting means of indicating the next regularly scheduled inspection period shall be permitted.

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 23:11:04 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee provides new language to incorporate NFPA 720 requirements intoChapter 14 in accordance with the guidance of the Correlating Committee.

ResponseMessage:

Public Input No. 360-NFPA 72-2016 [New Section after 14.6.2.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

133 of 496 10/20/2016 11:03 AM

Page 134: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2010-NFPA 72-2016 [ Section No. 17.1.1 ]

17.1.1

The performance, selection, use, and location of automatic or manual initiating devices, including but notlimited to fire detection devices, carbon monoxide or other gas detection devices, devices that detect theoperation of fire suppression and extinguishing systems, waterflow detectors, pressure switches, manualfire alarm boxes, and other supervisory signal–initiating devices (including guard tour reporting) used toensure timely warning for the purposes of life safety and the protection of a building, a space, a structure,an area, or an object shall comply with the minimum requirements of this chapter.

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 18:15:56 EDT 2016

Committee Statement

CommitteeStatement:

This change is made as one of numerous changes needed to incorporate and integrate the NFPA720 requirements for carbon monoxide detection into NFPA 72. This change identifies that CO andother gas detectors will be in the scope of Chapter 17 which addresses various initiating devices.

ResponseMessage:

Public Input No. 591-NFPA 72-2016 [Section No. 17.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

134 of 496 10/20/2016 11:03 AM

Page 135: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2011-NFPA 72-2016 [ Section No. 17.4.2 ]

17.4.2

Where subject to mechanical damage, an initiating device shall be protected. A mechanical guard used toprotect a smoke, heat, or radiant energy–sensing detector an initiating device shall be listed for use withthe detector device .

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 18:40:39 EDT 2016

Committee Statement

CommitteeStatement:

This revision is one of numerous revisions proposed as part of the integration of NFPA 720 carbonmonoxide detection requirements into the NFPA 72 Fire Alarm and Signaling Code. This changeprovides recognition of use, application and/or installation requirements consistent with otherdevice requirements in Chapter 17.

ResponseMessage:

Public Input No. 592-NFPA 72-2016 [Section No. 17.4.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

135 of 496 10/20/2016 11:03 AM

Page 136: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2004-NFPA 72-2016 [ Section No. 17.4.6 ]

17.4.6*

Duplicate terminals, leads, or connectors that provide for the connection of installation wiring shall beprovided on each initiating device for the express purpose of connecting into the fire alarm system tomonitor the integrity of the signaling and power wiring.

Exception: Initiating devices connected to a system that provides the required monitoring.

17.4.6.1

Where initiating devices are connected to a system that provides the required monitoring, duplicateterminals, leads, or connectors shall not be required.

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 12:44:58 EDT 2016

Committee Statement

Committee Statement: Exception language is revised to comply with the Manual of Style.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

136 of 496 10/20/2016 11:03 AM

Page 137: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2012-NFPA 72-2016 [ Section No. 17.4.7 [Excluding any

Sub-Sections] ]

Where fire detectors are installed in concealed locations more than 10 ft (3.0 m) above the finished flooror in arrangements where the detector’s alarm or supervisory indicator is not visible to respondingpersonnel, the detectors shall be provided with remote alarm or supervisory indication in a locationacceptable to the authority having jurisdiction.

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 18:44:55 EDT 2016

Committee Statement

CommitteeStatement:

This revision is one of numerous revisions proposed as part of the integration of NFPA 720 carbonmonoxide detection requirements into the NFPA 72 Fire Alarm and Signaling Code. This changeprovides recognition of use, application and/or installation requirements consistent with other devicerequirements in Chapter 17 and where such requirements are applicable to carbon monoxidedetection devices and other detectors.

ResponseMessage:

Public Input No. 605-NFPA 72-2016 [Section No. 17.4.7 [Excluding any Sub-Sections]]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

137 of 496 10/20/2016 11:03 AM

Page 138: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2013-NFPA 72-2016 [ Section No. 17.4.7.3 ]

17.4.7.3

Fire detectors Detectors installed in concealed locations where the specific detector alarm or supervisorysignal is indicated at the control unit (and on the drawings with its specific location and functions) shall notbe required to be provided with remote alarm indicators as specified in 17.4.7.

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 18:46:56 EDT 2016

Committee Statement

CommitteeStatement:

This revision is one of numerous revisions proposed as part of the integration of NFPA 720 carbonmonoxide detection requirements into the NFPA 72 Fire Alarm and Signaling Code. This changeprovides recognition of use, application and/or installation requirements consistent with other devicerequirements in Chapter 17 and where such requirements are applicable to carbon monoxidedetection devices and other detectors.

ResponseMessage:

Public Input No. 606-NFPA 72-2016 [Section No. 17.4.7.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

138 of 496 10/20/2016 11:03 AM

Page 139: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2014-NFPA 72-2016 [ New Section after 17.6.1.3 ]

17.6.1.4

Heat sensing fire detectors shall be listed in accordance with applicable standards such as ANSI/UL521, Standard for Heat Detectors for Fire Protective Signaling Systems , and installed in accordancewith their listing.

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 18:59:16 EDT 2016

Committee Statement

CommitteeStatement:

Sections 17.6.1.4 and 17.6.2.2.2.1 include requirements related to heat detector listings. Thisrevision clarifies that heat detectors are required to be listed, and identifies as an example theANSI/UL standard used to list these detectors. This does not preclude FM 3210 or otherstandards.

ResponseMessage:

Public Input No. 682-NFPA 72-2016 [New Section after 17.6.1.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

139 of 496 10/20/2016 11:03 AM

Page 140: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2001-NFPA 72-2016 [ Section No. 17.6.2.1 ]

17.6.2.1 Classification.

Heat-sensing fire detectors of the fixed-temperature or rate-compensated, spot type shall be classified asto the temperature of operation in accordance with Table 17.6.2.1.

Table 17.6.2.1 Temperature Classification and Color Code for Heat-Sensing Fire Detectors

TemperatureClassification

Temperature RatingRange

Maximum CeilingTemperature Color

Code°F °C °F °C

Low* 100–134 39–57 38–57 80 28 Uncolored

Ordinary 135–174 58–79 115 47 Uncolored

Intermediate 175–249 80–121 155 69 White

High 250–324 122–162 230 111 Blue

Extra high 325–399 163–204 305 152 Red

Very extra high 400–499 205–259 380 194 Green

Ultra high 500–575 260–302 480 249 Orange

*Intended only for installation in controlled ambient areas. Units shall be marked to indicate maximumambient installation temperature.

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 11:06:41 EDT 2016

Committee Statement

CommitteeStatement:

Based on the recommendation from the Metric Values Task Group, SIG-IDS is correlating themetric value of 100 degrees F to be 38 degrees C.

ResponseMessage:

Public Input No. 565-NFPA 72-2016 [Global Input]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

140 of 496 10/20/2016 11:03 AM

Page 141: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2005-NFPA 72-2016 [ Section No. 17.6.3.5.1 ]

17.6.3.5.1*

On ceilings 10 ft to 30 ft (3.0 m to 9.1 m) high, heat detector spacing shall be reduced in accordance withTable 17.6.3.5.1 prior to any additional reductions for beams, joists, or slope, where applicable.

Table 17.6.3.5.1 Heat Detector Spacing Reduction Based on Ceiling Height

Ceiling Height

Greater than (>)

Up to

and IncludingMultiply

Listed

Spacing byft m ft m

0 0 10 3.0 1.00

10 3.0 12 3.7 0.91

12 3.7 14 4.3 0.84

14 4.3 16 4.9 0.77

16 4.9 18 5.5 0.71

18 5.5 20 6.1 0.64

20 6.1 22 6.7 0.58

22 6.7 24 7.3 0.52

24 7.3 26 7.9 0.46

26 7.9 28 8.5 0.40

28 8.5 30 9.1 0.34

Exception: Table 17.6.3.5.1 shall not apply to the following detectors, which rely on the integrationeffect:

Line-type electrical conductivity detectors (see 3.3.66.11 )

Pneumatic rate-of-rise tubing heat detectors (see 3.3.66.15 )

In these cases, the manufacturer’s published instructions shall be followed for appropriate alarm pointand spacing.

17.6.3.5.1.1

For line-type electrical conductivity detectors (see 3.3.68.11 ) and pneumatic rate-of-rise tubing heatdetectors ( see 3.3.68.15 ) , which rely on the integration effect, the derating required by Table17.6.3.5.1 shall not apply, and the manufacturer’s published instructions shall be followed forappropriate alarm point and spacing.

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 12:47:59 EDT 2016

Committee Statement

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

141 of 496 10/20/2016 11:03 AM

Page 142: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Committee Statement: Exception language is revised to comply with the Manual of Style.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

142 of 496 10/20/2016 11:03 AM

Page 143: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2015-NFPA 72-2016 [ New Section after 17.7.1.8 ]

17.7.1.9*

Smoke detectors installed in ducts and other locations with air velocities greater than 300 ft/min (1.5m/sec) shall be listed for the velocity conditions anticipated and installed in accordance with themanufacturer’s instructions.

Supplemental Information

File Name Description

FR_2015_A.17.7.1.9.docx New annex material

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 19:32:29 EDT 2016

Committee Statement

CommitteeStatement:

This revision identifies the fact that smoke detectors installed in ducts and other locations with airvelocities > 300 ft/min. need to be listed for those air velocity environments. The annex item cites,as an example, ANSI/UL 268A. Another example is FM 3230.

ResponseMessage:

Public Input No. 677-NFPA 72-2016 [New Section after 17.7.1.8]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

143 of 496 10/20/2016 11:03 AM

Page 144: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2016-NFPA 72-2016 [ Section No. 17.7.2.2 ]

17.7.2.2

Smoke Spot-type smoke detectors that have provision for field adjustment of sensitivity via a mechanicalmeans shall have an adjustment range of not less than 0.6 percent per foot (1.95 percent per meter)obscuration.

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 19:51:55 EDT 2016

Committee Statement

CommitteeStatement:

The existing text dates back to the days when smoke alarms had mechanical adjustments forsensitivity. In looking at UL 217, the requirement is interpreted as a mechanical adjustment inSection 17.2.1 of the eighth edition. As currently written in NFPA 72 2016, the requirement maycreate confusion if it is viewed within the context of high sensitivity aspirated detectors, which havesensitivity settings outside of the normal UL range of 0.5 to 4%/ft. Aspirated detectors have a numberof very high sensitivity threshold settings that may not differ by the amount required in 17.7.2.2.

ResponseMessage:

Public Input No. 373-NFPA 72-2016 [Section No. 17.7.2.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

144 of 496 10/20/2016 11:03 AM

Page 145: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2008-NFPA 72-2016 [ Section No. 17.7.3.6 ]

17.7.3.6 Air Sampling–Type Smoke Detector.

17.7.3.6.1 General.

17.7.3.6.1.1*

In the absence of specific performance-based design criteria, each sampling port of an airsampling–type smoke detector shall be treated as a spot-type smoke detector for the purpose oflocation and spacing in accordance with 17.7.3 , sensitivity, and the manufacturer’s publishedinstructions.

17.7.3.6.1.2

Air sampling–type smoke detectors shall produce trouble signals if the airflow is outside themanufacturer’s specified range.

17.7.3.6.1.3

If provided, atmospheric contaminant filtration shall be listed for use with the detector and installed andmaintained in accordance with the air sampling–type smoke detector manufacturer’s publishedinstructions.

17.7.3.6.2 Pipe Network.

17.7.3.6.2.1

Maximum air sample transport time from the farthest sampling port to the detector shall not exceed 120seconds.

17.7.3.6.2.2

Sampling pipe networks shall be designed on the basis of, and shall be supported by, computer-basedfluid dynamics design calculations to ensure required performance.

17.7.3.6.2.3

The sampling pipe network design calculations shall include pressure, volumetric flow, and alarmsensitivity at each sampling port.

17.7.3.6.2.4

Software applications for the design of pipe networks shall be listed for use with the manufacturer’sequipment.

17.7.3.6.2.5

Sampling system piping shall be conspicuously identified as “SMOKE DETECTOR SAMPLING TUBE— DO NOT DISTURB,” as follows:

(1) At changes in direction or branches of piping

(2) At each side of penetrations of walls, floors, or other barriers

(3) At intervals on piping that provide visibility within the space, but no greater than 20 ft (6.1 m)

17.7.3.6.2.6*

Sampling ports shall be identified as such.

17.7.3.6.2.7*

If provided, test ports at the end (most remote location) of a pipe run installed in the pipe network solelyfor the purpose of validating consistency in performance (also referred to as benchmark test points)shall be included in the design calculations and allowed, but not required, to comply with therequirements of 17.7.3.6.2 .

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

145 of 496 10/20/2016 11:03 AM

Page 146: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

17.7.3.6.2.8

If the piping and fittings are painted, the painting shall be performed in accordance with the airsampling–type smoke detector manufacturer’s published instructions.

17.7.3.6.2.9*

Pipe network materials, sizing, and installation shall be in accordance with the manufacturer’s publishedrequirements and suitable for use in the environment in which they are installed.

17.7.3.6.2.10

Where used, capillary tubing shall be sized and affixed in accordance with the manufacturer’s publishedinstructions and computer-based design calculations.

17.7.3.6.3 Installation and Spacing.

17.7.3.6.3.1*

Air sampling pipe network fittings shall be installed air-tight and permanently affixed.

17.7.3.6.3.2

Sampled air shall be exhausted to a lessor or equal pressure zone. The pressure differential betweenthe sampled air and detector exhaust shall not exceed the manufacturer’s published instructions.

17.7.3.6.3.3*

Supports for sampling pipe shall be in accordance with the air sampling–type smoke detectormanufacturer’s published instructions.

17.7.3.6.4 Special Applications.

17.7.3.6.4.1 Air Duct Applications.

(A)

The air sampling system shall be listed for air duct applications and shall be installed in accordance withthe manufacturer’s published instructions.

(B)

The inlet and exhaust sections of pipe that are installed inside the air duct shall be air-tight and shallexhaust the sampled air in accordance with the manufacturer’s published instructions.

17.7.3.6.4.2* Electrical Cabinet Applications.

For protection of cabinets containing electrical equipment, the air sampling ports shall be located in themain airflow at the exhaust vents, downstream of the airflow distribution path, or in accordance with themanufacturer’s published instructions.

17.7.3.6.1

Each sampling port of an air sampling–type smoke detector shall be treated as a spot-type detector forthe purpose of location and spacing.

17.7.3.6.2

Maximum air sample transport time from the farthest sampling port to the detector shall not exceed120 seconds.

17.7.3.6.3*

Sampling pipe networks shall be designed on the basis of, and shall be supported by, sound fluiddynamic principles to ensure required performance.

17.7.3.6.4

Sampling pipe network design details shall include calculations showing the flow characteristics of thepipe network and each sample port.

17.7.3.6.5

Air-sampling detectors shall give a trouble signal if the airflow is outside the manufacturer’s specifiedrange.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

146 of 496 10/20/2016 11:03 AM

Page 147: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

17.7.3.6.6*

The sampling ports and in-line filter, if used, shall be kept clear in accordance with the manufacturer’spublished instructions.

17.7.3.6.7

Air-sampling network piping and fittings shall be airtight and permanently fixed.

17.7.3.6.8

Sampling system piping shall be conspicuously identified as “SMOKE DETECTOR SAMPLING TUBE— DO NOT DISTURB,” as follows:

At changes in direction or branches of piping

At each side of penetrations of walls, floors, or other barriers

At intervals on piping that provide visibility within the space, but no greater than 20 ft (6.1 m)

Supplemental Information

File Name Description

FR_2008_17.7.3.6.docx For staff use

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 17:38:57 EDT 2016

Committee Statement

CommitteeStatement:

The SIG-IDS Chair had formed a task group to propose changes that would assist the fire protectioncommunity with the application, installation, inspection, testing, and maintenance of airsampling-type smoke detection systems. This change is a result of that task group's efforts.Additionally, the task group proposed a complete re-write of section 17.7.3.6 which the TechnicalCommittee accepted with revisions. The SIG-IDS Technical Committee provides additional guidancefor air sampling-type smoke detection systems in NFPA 72.

New subsections are introduced to categorize the different sections that apply to an installation orapplication.

17.7.3.6.1.1: Adds criteria for performance based design, ties back to 17.7.3 and manufacturer’spublished instructions. In absence, application would otherwise be limiting.

17.7.3.6.1.2: Relocate 17.7.3.6.5 under new general subsection, edited to include the word “smoke”after Air Sampling for consistency with the section title.

17.7.3.6.1.3: New language intended to prevent use of improper filtration media that may hindersystem performance.

17.7.3.6.2.1: Relocate 17.7.3.6.2 to new subsection for proper categorization.

17.7.3.6.2.2: Relocate 17.7.3.6.3 to new subsection for proper categorization, edit language forclarity. “Sound” / “principles” not specific.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

147 of 496 10/20/2016 11:03 AM

Page 148: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

17.7.3.6.2.3: Relocate 17.7.3.6.4 for proper categorization, additional requirements are added forclarity of calculated performance verification.

17.7.3.6.2.4: New language to ensure modelling programs be specific to the manufacturer’sequipment and set criteria that the program be listed.

17.7.3.6.2.5: Relocate 17.7.3.6.8 to new subsection for proper categorization.

17.7.3.6.2.6: New language to avoid challenges with respect to identifying sampling ports to avoiddamage, non-engineered alterations, and points where maintenance may be required.

17.7.3.6.2.7: New language to not unnecessarily burden system capacity or performance by placinga test point at accessible locations. This does not remove the requirement to meet 120 sec from lastsampling port in fire zone.

A.17.7.3.6.2.7: Add appendix material to provide additional guidance with respect to benchmark testpoint.

17.7.3.6.2.8: New material to prevent damage to pipe from non-compatible chemistries and/orblockage of sampling ports as a result of painting in the field.

17.7.3.6.2.9 New language to address suitability of sampling pipe network with respect to theenvironment in which they are installed.

17.7.3.6.2.10: New language extending requirements to capillary tubes, also, acknowledgespermissible use of capillaries and requires that they be included in calculations.

17.7.3.6.3.1: Relocate 17.7.3.6.7 to new subsection.

17.7.3.6.3.2: New language to prevent systems from not performing their intended function. Pressuredifferentials, if not within manufacture's published guidelines results in systems performingunpredictably.

17.7.3.6.3.3: New language to assure proper methods and materials are used as it relates to supportof air sampling pipe distribution networks.

17.7.3.6.4.1: New language to ensure that the detector selected is suitable and listed for ductapplication and to improve clarity of installation for intent of performance.

17.7.3.6.4.2: New language to provide guidance for application in electrical cabinets notingrequirements for placement of ports for interception of smoke.

ResponseMessage:

Public Input No. 644-NFPA 72-2016 [Section No. 17.7.3.6.5]

Public Input No. 645-NFPA 72-2016 [Section No. 17.7.3.6.7]

Public Input No. 531-NFPA 72-2016 [Section No. 17.7.3.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

148 of 496 10/20/2016 11:03 AM

Page 149: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2006-NFPA 72-2016 [ Section No. 17.7.5.4.2.1 ]

17.7.5.4.2.1 Supply Air System.

Where the detection of smoke in the supply air system is required by other NFPA standards, a detector(s)listed for the air velocity present and that is located in the supply air duct downstream of both the fan andthe filters shall be installed.

Exception: Additional smoke detectors shall not be required to be installed in ducts where the air ductsystem passes through other smoke compartments not served by the duct.

(A)

Where the detection of smoke in the supply air system is required by other NFPA standards, a detector(s)listed for the air velocity present and that is located in the supply air duct downstream of both the fan andthe filters shall be installed.

(B)

Where the air duct system passes through other smoke compartments not served by the duct, additionalsmoke detectors shall not be required to be installed.

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 12:50:20 EDT 2016

Committee Statement

Committee Statement: Exception language is revised to comply with the Manual of Style.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

149 of 496 10/20/2016 11:03 AM

Page 150: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2002-NFPA 72-2016 [ Sections 17.7.5.6.5.3(B), 17.7.5.6.5.3(C) ]

(B)

Each group of three or more doorway openings shall be treated separately. Figure 17.7.5.6.5.3(B) shallapply.

Figure 17.7.5.6.5.3(B) Detector(s) Location +/−24 in. ±24 in. (0.6 m) (610 mm) Requirements forGroup Doorways.

(C)

Each group of doorway openings that exceeds 20 ft (6.1 m) in width, measured at its overall extremes,shall be treated separately. Figure 17.7.5.6.5.3(C) shall apply.

Figure 17.7.5.6.5.3(C) Detector(s) Location +/−24 in. ±24 in. (0.6 m) (610 mm) Requirements forGroup Doorways over 20 ft (6.1 m) in Width.

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 11:10:45 EDT 2016

Committee Statement

CommitteeStatement:

Based on the recommendation from the Metric Values Task Group, SIG-IDS is correlating themetric value of 24 inches to be 610 mm.

ResponseMessage:

Public Input No. 576-NFPA 72-2016 [Global Input]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

150 of 496 10/20/2016 11:03 AM

Page 151: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2025-NFPA 72-2016 [ Section No. 17.7.6.3.3.3 ]

17.7.6.3.3.3

Air- sampling or projected beam smoke detectors shall be installed in accordance with the manufacturer’spublished instructions.

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jul 29 14:58:35 EDT 2016

Committee Statement

CommitteeStatement:

A Correlating Committee task group on language/terms reviewed the language of the Code forconsistency and grammar.

Editorial correction. The Term “air sampling” is generally not hyphenated and the majority ofusage in the code is not hyphenated. The Technical Committee revises to align with other usagein the Code

ResponseMessage:

Public Input No. 646-NFPA 72-2016 [Section No. 17.7.6.3.3.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

151 of 496 10/20/2016 11:03 AM

Page 152: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2021-NFPA 72-2016 [ Section No. 17.10.1 ]

17.10.1 General.

The purpose and scope of Section 17.10 shall be to provide requirements for the selection, installation,and operation of gas detectors other than carbon monoxide detectors .

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 20:44:41 EDT 2016

Committee Statement

CommitteeStatement:

Carbon monoxide detection requirements are separate and distinct from the gas detectionrequirements of 17.10. A new section is added to cover CO detection (17.12).

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

152 of 496 10/20/2016 11:03 AM

Page 153: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2017-NFPA 72-2016 [ Section No. 17.10.2.1 ]

17.10.2.1

Gas detection equipment shall be listed in accordance with applicable standards such as ANSI/UL 1484,Standard for Residential Gas Detectors , or ANSI/UL 2075, Standard for Gas and Vapor Detectors andSensors , for the specific gas or vapor it is intended to detect.

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 20:01:03 EDT 2016

Committee Statement

CommitteeStatement:

The text identifies representative applicable standards for gas and vapor detectors. Devicesmay also be listed to other applicable standards such as FM 6320, 6325, or 6340.

ResponseMessage:

Public Input No. 407-NFPA 72-2016 [Section No. 17.10.2.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

153 of 496 10/20/2016 11:03 AM

Page 154: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2018-NFPA 72-2016 [ New Section after 17.11 ]

17.12 Carbon Monoxide Detectors.

17.12.1

Carbon monoxide detectors shall not be located in areas where environmental conditions cause anadverse effect on the detectors’ ability to detect the targeted hazardous gas.

17.12.2

Carbon monoxide detectors shall be installed as specified in the manufacturer’s published instructions inaccordance with 17.12.2(1) and 17.12.2(2), or 17.12.2(3):

(1)

(2)

(3) A performance-based design in accordance with Section17.3

17.12.3

Carbon monoxide detectors shall be marked in accordance with their listing. Detector thresholds shallbe set to respond at the levels specified by ANSI/UL 2034, Standard for Single and Multiple StationCarbon Monoxide Alarms .

17.12.4

All carbon monoxide detectors shall be located and mounted so that accidental operation will not becaused by jarring or vibration.

17.12.5

The location of carbon monoxide detectors shall be based on an evaluation of potential ambient sourcesand flows of carbon monoxide, moisture, temperature, dust, or fumes and of electrical or mechanicalinfluences to minimize nuisance alarms.

17.12.6

The selection and placement of carbon monoxide detectors shall take into account both theperformance characteristics of the detector and the areas into which the detectors are to be installed toprevent nuisance and unintentional alarms or improper operation after installation.

17.12.7

Unless specifically designed and listed for the expected conditions, carbon monoxide detectors shall notbe installed where any of the following ambient conditions exist:

(1) Temperature below 32°F (0°C)

(2) Temperature above 100°F (38°C)

(3) Relative humidity outside the range of 10 percent to 95 percent

17.12.8

Unless tested and listed for recessed mounting, carbon monoxide detectors shall not be recessed intothe mounting surface.

17.12.9 Protection During Construction.

17.12.9.1

Where detectors are installed for signal initiation during construction, they shall be replaced prior to thefinal commissioning of the system.

17.12.9.2

Where detection is not required during construction, detectors shall not be installed until after all otherconstruction trades have completed cleanup.

* On the ceiling in the same room as permanently installed fuel-burning appliances

* Centrally located on every habitable level and in every HVAC zone of the building

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

154 of 496 10/20/2016 11:03 AM

Page 155: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

17.12.10 Carbon Monoxide Detectors for Control of Carbon Monoxide Spread.

17.12.10.1

System designers shall consider the spread of carbon monoxide through an occupancy through theHVAC system.

17.12.10.2

Interaction with smoke control systems, if such is provided, shall be coordinated.

Supplemental Information

File Name Description

FR_2018_A.17.12.2_1_and_2_.docx New annex material

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 20:10:57 EDT 2016

Committee Statement

CommitteeStatement:

This revision is one of numerous revisions proposed as part of the integration of NFPA 720 carbonmonoxide detection requirements into the NFPA 72 Fire Alarm and Signaling Code. This changeprovides recognition of use, application and/or installation requirements consistent with other devicerequirements in Chapter 17 and where such requirements are applicable to carbon monoxidedetection devices.

ResponseMessage:

Public Input No. 607-NFPA 72-2016 [New Section after 17.11.5.3]

Public Input No. 608-NFPA 72-2016 [New Section after A.17.11.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

155 of 496 10/20/2016 11:03 AM

Page 156: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2022-NFPA 72-2016 [ Section No. 17.14.1 ]

17.15.1

Manually actuated alarm-initiating devices shall be listed in accordance with applicable standards such asANSI/UL 38, Standard for Manual Signaling Boxes for Fire Alarm Systems . for initiating signals otherthan for fire alarm shall be permitted if the devices are differentiated from manual fire alarm boxes by acolor other than red and labeling.

17.15.2

Manually actuated alarm-initiating devices for initiating signals other than for fire alarm shall bepermitted if the devices are differentiated from manual fire alarm boxes by a color other than red andlabeling.

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 20:52:45 EDT 2016

Committee Statement

CommitteeStatement:

This revision provides an example of an applicable listing standard for manual fire alarmboxes.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

156 of 496 10/20/2016 11:03 AM

Page 157: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2023-NFPA 72-2016 [ Section No. 17.16.2.2.2 ]

17.17.2.2.2* Dry Pipe Sprinkler System.

(A)

A pressure supervisory signal–initiating device for a dry-pipe sprinkler system shall indicate both high- andlow-pressure conditions.

(B)

The For dry pipe valves, the off-normal signal shall be initiated when the pressure increases ordecreases by 10 psi (70 kPa).

(C)

For low air pressure dry pipe valves, the high- and low-pressure values shall be set in accordance withthe manufacturer's installation instructions.

Supplemental Information

File Name Description

FR_2023_A.17.16.2.2.2.1469816623923-4_RJR.docx

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jul 29 14:21:48 EDT 2016

Committee Statement

CommitteeStatement:

Some dry pipe valves use lower air pressures in the area of 14-15 PSI, instead of the traditional40 PSI range. A plus or minus value of 10 PSI is not appropriate for these valves and may result insystem discharge prior to the low air pressure supervisory signal.

ResponseMessage:

Public Input No. 371-NFPA 72-2016 [Section No. 17.16.2.2.2(B)]

Public Input No. 429-NFPA 72-2016 [New Section after 17.16.2.2.2(B)]

Public Input No. 74-NFPA 72-2016 [Section No. 17.16.2.2.2(B)]

Public Input No. 67-NFPA 72-2016 [Section No. 17.16.2.2.2(B)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

157 of 496 10/20/2016 11:03 AM

Page 158: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2003-NFPA 72-2016 [ Section No. 17.16.3.2.1 ]

17.17.3.2.1

The off-normal signal shall be initiated when the water level falls 3 in. (70 mm) (76 mm) or rises 3 in.(70 mm) (76 mm) .

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 11:13:37 EDT 2016

Committee Statement

CommitteeStatement:

Based on the recommendation from the Metric Values Task Group, SIG-IDS is correlating themetric value of 3 inches to be 76 mm.

It is the opinion of the SIG-IDS Technical Committee that the correct conversion is 76 mmrather than the 75 mm proposed by PI 583.

ResponseMessage:

Public Input No. 583-NFPA 72-2016 [Global Input]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

158 of 496 10/20/2016 11:03 AM

Page 159: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2512-NFPA 72-2016 [ Section No. 18.1.6 ]

18.1.6

The requirements of Chapters 10 , 14 , 23 , and 24 shall apply to the interconnection of notificationappliances, the control configurations, the power supplies, and the use of the information provided bynotification appliances.

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 16:24:01 EDT 2016

Committee Statement

CommitteeStatement:

This revision is being made to coordinate with the First Revision made by SIG-FUN (PI722).

Response Message:

Public Input No. 729-NFPA 72-2016 [Section No. 18.1.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

159 of 496 10/20/2016 11:03 AM

Page 160: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2513-NFPA 72-2016 [ Section No. 18.4.1.3 ]

18.4.1.3*

Sound from normal or permanent sources, having a duration greater than of at least 60 seconds, shall beincluded when measuring maximum ambient sound level. Sound from temporary or abnormal sourcesshall not be required to be included when measuring maximum ambient sound level.

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 16:28:55 EDT 2016

Committee Statement

CommitteeStatement:

This revision is being made to make the language consistent with other sections inChapter 18.

Response Message:

Public Input No. 123-NFPA 72-2016 [Section No. 18.4.1.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

160 of 496 10/20/2016 11:03 AM

Page 161: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2515-NFPA 72-2016 [ New Section after 18.4.2 ]

18.4.3 Distinctive Carbon Monoxide Signal.

18.4.3.1

When a carbon monoxide sensor or alarm is required by other codes or standards or by the authorityhaving jurisdiction, a distinctive signal pattern shall be required that is different from a fire evacuationsignal.

18.4.3.2

The carbon monoxide signal shall be a four-pulse temporal pattern and comply with the following:

(1) Signals shall be a pattern consisting of four cycles of 100 milliseconds ± 10 percent “on” and 100milliseconds ± 10 percent “off,” followed by 5 seconds ± 10 percent “off.”

(2) After the initial 4 minutes of the carbon monoxide signal, the 5-second “off” time shall be permittedto be changed to 60 seconds ± 10 percent.

Figure 18.4.3.2 Temporal Pattern Parameters — Carbon Monoxide Signal.

18.4.3.3

The signal shall be synchronized within a notification zone.

Supplemental Information

File Name Description

Figure_18.4.3.2_Temporal_Pattern_Parameters_-_Carbon_Monoxide_Signal.docx Shows Figure 18.4.3.2

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 17:23:17 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee includes a distinct audible signal for carbon monoxide. TheTechnical Committee adds new 18.4.3 and Figure 18.4.3.2.

ResponseMessage:

Public Input No. 477-NFPA 72-2016 [New Section after 18.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

161 of 496 10/20/2016 11:03 AM

Page 162: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Public Input No. 609-NFPA 72-2016 [Section No. 18.4.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

162 of 496 10/20/2016 11:03 AM

Page 163: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2514-NFPA 72-2016 [ Section No. 18.4.2 ]

18.4.2 Distinctive Evacuation Signal.

18.4.2.1*

To meet the requirements of Section 10.10, the alarm audible signal pattern used to notify buildingoccupants of the need to evacuate (leave the building) or relocate (from one area to another) shall be thestandard alarm evacuation signal consisting of a three-pulse temporal pattern. The pattern shall be inaccordance with ANSI/ASA S3.41. Figure 18.4.2.1 and shall consist of the following in this order:

“On” phase lasting 0.5 second ±10 percent

“Off” phase lasting 0.5 second ±10 percent for three successive “on” periods

“Off” phase lasting 1.5 seconds ±10 percent

Figure 18.4.2.1 Temporal Pattern Parameters.

Exception: Where approved by the authority having jurisdiction, continued use of the existing consistentevacuation signaling scheme shall be permitted.

18.4.2.2

A single-stroke bell or chime sounded at “on” intervals lasting 1 second ±10 percent, with a 2-second±10 percent “off” interval after each third “on” stroke, shall be permitted.

18.4.2.2

The signal shall be repeated for a period appropriate for the purposes of evacuation of the building, but fornot less than 180 seconds.

18.4.2.2.1

The minimum repetition time shall be permitted to be manually interrupted.

18.4.2.2.2

The minimum repetition time shall be permitted to be automatically interrupted for the transmission ofmass notification messages in accordance with Chapter 24.

18.4.2.3*

The standard evacuation signal shall be synchronized within a notification zone.

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

163 of 496 10/20/2016 11:03 AM

Page 164: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Submittal Date: Mon Jul 25 16:54:58 EDT 2016

Committee Statement

CommitteeStatement:

Because of the many additional changes in the referenced ANSI standard, it is best that thetechnical requirements not be repeated in the body of NFPA 72. Compliance with appropriateANSI standards will be handled by manufacturers and listing agencies.

ResponseMessage:

Public Input No. 121-NFPA 72-2016 [Section No. 18.4.2]

Public Input No. 562-NFPA 72-2016 [Section No. 18.4.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

164 of 496 10/20/2016 11:03 AM

Page 165: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2516-NFPA 72-2016 [ Section No. 18.4.8.4 ]

18.4.9.4

Appliances that are an integral part of a smoke detector, carbon monoxide sensor, smoke alarm, carbonmonoxide alarm, or other initiating device shall be located in accordance with the requirements for thatdevice.

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 18:25:13 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee agrees with the integration of NFPA 720 into NFPA 72 and has addedlanguage for carbon monoxide in an existing section. The word “sensor” is used instead of“detector” to be consistent with FR #2515.

ResponseMessage:

Public Input No. 610-NFPA 72-2016 [Section No. 18.4.8.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

165 of 496 10/20/2016 11:03 AM

Page 166: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2517-NFPA 72-2016 [ Section No. 18.4.10.2 ]

18.4.11.2

Each ADS that does not require voice intelligibility shall be identified as requiring or not requiring voiceintelligibility .

18.4.11.2.1*

Unless specifically required by other governing laws, codes, or standards, or by other parts of this Code,intelligibility shall not be required in all ADSs.

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 18:41:59 EDT 2016

Committee Statement

Committee Statement: The Technical Committee edits the text defining ADS’s that do not require intelligibility.

Response Message:

Public Input No. 479-NFPA 72-2016 [Section No. 18.4.10.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

166 of 496 10/20/2016 11:03 AM

Page 167: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2518-NFPA 72-2016 [ Sections 18.4.10.4, 18.4.10.5 ]

18.4.11.4

Intelligibility shall not be required be permitted to be determined through quantitative measurements asdescribed in D.2.4shall be permitted but are is not required to be determined through quantitativemeasurements .

18.4.11.5

Quantitative measurements as described in D.2.4 shall be permitted but are not required.

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 18:52:16 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee is accepting the proposals in PIs 62 and 63 in order to clarify therequirements for measuring intelligibility. The proposals in PI 744 were not accepted because theTechnical Committee concluded that the basic requirement of qualitative measurement consistentwith the definition of intelligibility is permitted.

ResponseMessage:

Public Input No. 63-NFPA 72-2016 [Section No. 18.4.10.5]

Public Input No. 62-NFPA 72-2016 [Section No. 18.4.10.4]

Public Input No. 744-NFPA 72-2016 [Sections 18.4.10.4, 18.4.10.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

167 of 496 10/20/2016 11:03 AM

Page 168: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2519-NFPA 72-2016 [ Section No. 18.5.3.2 ]

18.5.3.2*

The maximum light pulse duration shall be 20 milliseconds with a maximum duty cycle of 40 percent .

Exception: Lights used to meet the requirements of 18.5.5.5 shall be permitted to be listed andlabeled to have pulse durations up to 100 milliseconds.

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 15:05:15 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee agrees that duty cycle is no longer necessary because it is redundant.The exception is being deleted to eliminate confusion and complications in installation designs.

ResponseMessage:

Public Input No. 247-NFPA 72-2016 [Section No. 18.5.3.2]

Public Input No. 480-NFPA 72-2016 [Section No. 18.5.3.2]

Public Input No. 481-NFPA 72-2016 [Section No. 18.5.3.2]

Public Input No. 100-NFPA 72-2016 [Section No. 18.5.3.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

168 of 496 10/20/2016 11:03 AM

Page 169: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2520-NFPA 72-2016 [ Section No. 18.5.3.4 ]

18.5.3.4*

Lights Visual notification appliances used for fire alarm signaling only or to signal the intent for completeevacuation shall be clear or nominal white and shall not exceed 1000 cd (effective intensity).

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 15:18:50 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee agrees with the work that the Correlating Committee Task Group didand agrees that “light” is not applicable. The term “visual notification appliance” is the properterm.

ResponseMessage:

Public Input No. 248-NFPA 72-2016 [Section No. 18.5.3.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

169 of 496 10/20/2016 11:03 AM

Page 170: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2521-NFPA 72-2016 [ New Section after 18.5.3.5 ]

18.5.3.7

Visual notification appliances used for carbon monoxide signaling shall be as required by theemergency plan and the authority having jurisdiction for the area or building and shall not exceed 1000cd (effective intensity).

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 15:23:05 EDT 2016

Committee Statement

CommitteeStatement:

This revision is made to add code language for carbon monoxide signaling as a result of theintegration of NFPA 720 into NFPA 72. The term “visual notification appliance” was used instead of“light” because it is a more appropriate term. The term “alarm” was not included to coordinate withother first revisions.

ResponseMessage:

Public Input No. 611-NFPA 72-2016 [New Section after 18.5.3.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

170 of 496 10/20/2016 11:03 AM

Page 171: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2522-NFPA 72-2016 [ Sections 18.5.3.5, 18.5.3.6 ]

18.5.3.5

Lights Visual notification appliances used to signal occupants to seek information or instructions shall beclear, nominal white, or other color as required by the emergency plan and the authority having jurisdictionfor the area or building.

18.5.3.6*

The strobe visual synchronization requirements of this chapter shall not apply where the visible visualnotification appliances located inside the building are viewed from outside of the building.

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 15:28:37 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee agrees with the work that the Correlating Committee Task Group didand agrees that “light” and “strobe” are not applicable. The term “visual notification appliance” isthe proper term.

ResponseMessage:

Public Input No. 265-NFPA 72-2016 [Section No. 18.5.3.6]

Public Input No. 249-NFPA 72-2016 [Section No. 18.5.3.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

171 of 496 10/20/2016 11:03 AM

Page 172: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2523-NFPA 72-2016 [ Section No. 18.5.4 ]

18.5.4* Appliance Photometrics.

The light output shall comply with the polar dispersion requirements of ANSI/UL 1971, Standard forSignaling Devices for the Hearing Impaired , or equivalent. for public mode signaling as described inANSI/UL 1971, Standard for Signaling Devices for the Hearing Impaired , ANSI/UL 1638, Standard forVisible Signaling Devices for Fire Alarm and Signaling Systems, Including Accessories , or equivalent.

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 15:35:21 EDT 2016

Committee Statement

Committee Statement: The Technical Committee edits the text to include UL 1638.

Response Message:

Public Input No. 450-NFPA 72-2016 [Section No. 18.5.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

172 of 496 10/20/2016 11:03 AM

Page 173: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2524-NFPA 72-2016 [ Section No. 18.5.5.2 ]

18.5.5.2

Where low ceiling heights do not permit wall mounting at a minimum of 80 in. (2.03 m), wall mountedvisible visual notification appliances shall be mounted within 6 in. (150 mm) of the ceiling. The room sizecovered by a strobe visual notification appliance of a given value shall be reduced by twice the differencebetween the minimum mounting height of 80 in. (2.03 m) and the actual lower mounting height.

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 15:40:22 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee agrees with the work that the Correlating Committee Task Group didand agrees that “strobe” is not applicable. The term “visual notification appliance” is the properterm.

ResponseMessage:

Public Input No. 266-NFPA 72-2016 [Section No. 18.5.5.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

173 of 496 10/20/2016 11:03 AM

Page 174: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2525-NFPA 72-2016 [ Section No. 18.5.5.4.1 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

174 of 496 10/20/2016 11:03 AM

Page 175: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

18.5.5.4.1

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

175 of 496 10/20/2016 11:03 AM

Page 176: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Spacing shall be in accordance with either Table 18.5.5.4.1(a) and Figure 18.5.5.4.1 or Table18.5.5.4.1(b).

Table 18.5.5.4.1(a) Room Spacing for Wall-Mounted Visible Visual Notification Appliances

MaximumRoom Size

Minimum Required Light Output [Effective Intensity (cd)]

One Light Visual NotificationAppliance per Room

Four Lights Visual Notification Appliancesper Room (One Light per Wall)ft m

20 × 206.10 ×6.10

15 NA

28 × 288.53 ×8.53

30 NA

30 × 309.14 ×9.14

34 NA

40 × 4012.2 ×12.2

60 15

45 × 4513.7 ×13.7

75 19

50 × 5015.2 ×15.2

94 30

54 × 5416.5 ×16.5

110 30

55 × 5516.8 ×16.8

115 30

60 × 6018.3 ×18.3

135 30

63 × 6319.2 ×19.2

150 37

68 × 6820.7 ×20.7

177 43

70 × 7021.3 ×21.3

184 60

80 × 8024.4 ×24.4

240 60

90 × 9027.4 ×27.4

304 95

100 ×100

30.5 ×30.5

375 95

110 ×110

33.5 ×33.5

455 135

120 ×120

36.6 ×36.6

540 135

130 ×130

39.6 ×39.6

635 185

NA: Not allowable.

Table 18.5.5.4.1(b) Room Spacing for Ceiling-Mounted Visible Visual Notification Appliances

Maximum

Room SizeMaximum Lens Height*

Minimum Required

Light Output

(Effective Intensity);

One Light Visual Notification Appliance (cd)ft m ft m

20 × 20 6.1 × 6.1 10 3.0 15

30 × 30 9.1 × 9.1 10 3.0 30

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

176 of 496 10/20/2016 11:03 AM

Page 177: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Maximum

Room SizeMaximum Lens Height*

Minimum Required

Light Output

(Effective Intensity);

One Light Visual Notification Appliance (cd)ft m ft m

40 × 40 12.2 × 12.2 10 3.0 60

44 × 44 13.4 × 13.4 10 3.0 75

20 × 20 6.1 × 6.1 20 6.1 30

30 × 30 9.1 × 9.1 20 6.1 45

44 × 44 13.4 × 13.4 20 6.1 75

46 × 46 14.0 × 14.0 20 6.1 80

20 × 20 6.1 × 6.1 30 9.1 55

30 × 30 9.1 × 9.1 30 9.1 75

50 × 50 15.2 × 15.2 30 9.1 95

53 × 53 16.2 × 16.2 30 9.1 110

55 × 55 16.8 × 16.8 30 9.1 115

59 × 59 18.0 × 18.0 30 9.1 135

63 × 63 19.2 × 19.2 30 9.1 150

68 × 68 20.7 × 20.7 30 9.1 177

70 × 70 21.3 × 21.3 30 9.1 185

*This does not preclude mounting lens at lower heights.

Figure 18.5.5.4.1 Room Spacing for Wall-Mounted Visible Visual Notification Appliances.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

177 of 496 10/20/2016 11:03 AM

Page 178: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 15:45:46 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee agrees with the work that the Correlating Committee Task Group didand agrees that “light” is not applicable. The term “visual notification appliance” is the properterm.

ResponseMessage:

Public Input No. 250-NFPA 72-2016 [Section No. 18.5.5.4.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

178 of 496 10/20/2016 11:03 AM

Page 179: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2526-NFPA 72-2016 [ Section No. 18.5.5.4.2 ]

18.5.5.4.2

Visible Visual notification appliances shall be installed in accordance with Table 18.5.5.4.1(a) or Table18.5.5.4.1(b) using one of the following:

(1) A single visible visual notification appliance.

(2)

(3) More than two visible visual notification appliances or groups of synchronized appliances in the sameroom or adjacent space within the field of view that flash in synchronization.

Supplemental Information

File Name Description

72_FR-2526_A.18.5.5.4.2_2_NAS.docx

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 15:59:53 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee agrees with the work that the Correlating Committee Task Group did andagrees that “strobe” is not applicable. The term “visual notification appliance” is the proper term. Forthe annex, The Technical Committee agrees with the work that the Correlating Committee TaskGroup did and agrees that “light” and “strobe” are not applicable. The term “visual notificationappliance” is the proper term.

ResponseMessage:

Public Input No. 267-NFPA 72-2016 [Section No. 18.5.5.4.2]

Public Input No. 258-NFPA 72-2016 [Section No. A.18.5.5.4.2(2)]

* Two groups of visible visual notification appliances, where visual notification appliances of eachgroup are synchronized, in the same room or adjacent space within the field of view. This shallinclude synchronization of strobes visual appliances operated by separate systems.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

179 of 496 10/20/2016 11:03 AM

Page 180: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2527-NFPA 72-2016 [ Section No. 18.5.5.6.1 ]

Global FR-2501

18.5.5.6.1

Any design that provides a minimum of 0.0375 lumens/ft2 (0.4036 lumens/m2 ) of illumination at anypoint within the covered area at all angles specified by the polar dispersion planes for wall- or ceiling-mounted public mode visual notification appliances in ANSI/UL 1971, Standard for Signaling Devices forthe Hearing Impaired ,ANSI/UL 1638, Standard for Visible Signaling Devices for Fire Alarm and SignalingSystems, Including Accessories, or equivalent, as calculated for the maximum distance from the nearestvisual notification appliance, shall be permitted in lieu of the requirements of 18.5.5 , excluding 18.5.5.7 .

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 16:19:19 EDT 2016

Committee Statement

Committee Statement: The Technical Committee edits the text to include ANSI/UL 1638.

Response Message:

Public Input No. 457-NFPA 72-2016 [Section No. 18.5.5.6.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

180 of 496 10/20/2016 11:03 AM

Page 181: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2528-NFPA 72-2016 [ Section No. 18.5.5.7 ]

18.5.5.7 Sleeping Areas.

18.5.5.7.1

Combination smoke detectors and visible visual notification appliances or combination smoke alarms andvisible visual notification appliances shall be installed in accordance with the applicable requirements ofChapters 17, 18, and 29.

18.5.5.7.2

Combination carbon monoxide sensors and visual notification appliances or combination carbonmonoxide alarms and visual notification appliances shall be installed in accordance with the applicablerequirements of Chapters 17 , 18 , and 29 .

18.5.5.7.3*

Table 18.5.5.7.3Table 18.5.5.7.3Table 18.5.5.7.2 shall apply to sleeping areas.

Table 18.5.5.7.3 Effective Intensity Requirements for Sleeping Area Visible Visual Notification Appliances

Distance from Ceiling

to Top of LensMinimum Intensity

(cd)in. mm

≥24 ≥610 110

<24 <610 177

18.5.5.7.4

For rooms with a linear dimension greater than 16 ft (4.87 m 4.9 m ), the visible visual notificationappliance shall be located within 16 ft (4.87 m 4.9 m ) of the pillow.

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 16:25:32 EDT 2016

Committee Statement

CommitteeStatement:

This revision is made to add code language for carbon monoxide signaling as a result of theintegration of NFPA 720 into NFPA 72. The term “visual” was used instead of “visible” because it is amore appropriate term. The proposed exception was not included because the Technical Committeeconcluded that it was not necessary to have a separate exception for carbon monoxide devices. Theproposed revisions in PI 64 were not included. Mounting height for notification appliances areaddressed elsewhere in 18.5.5.1. Once mounting height is established, then table 18.5.5.7.2 wouldbe applied to determine cd.

ResponseMessage:

Public Input No. 612-NFPA 72-2016 [Section No. 18.5.5.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

181 of 496 10/20/2016 11:03 AM

Page 182: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Public Input No. 64-NFPA 72-2016 [Section No. 18.5.5.7.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

182 of 496 10/20/2016 11:03 AM

Page 183: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2529-NFPA 72-2016 [ Section No. 18.5.6 ]

18.5.6 Location of Visible Visual Notification Appliances for Wide- Area Signaling.

Visible Visual notification appliances for wide- area signaling shall be installed in accordance with therequirements of the authority having jurisdiction, approved design documents, and the manufacturer’sinstructions to achieve the required performance.

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 16:45:17 EDT 2016

Committee Statement

CommitteeStatement:

This is an editorial revision to remain consistent with the hyphenated term “wide-area” usedelsewhere in the document. The term “visual” was used instead of “visible” because it is a moreappropriate term.

ResponseMessage:

Public Input No. 688-NFPA 72-2016 [Section No. 18.5.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

183 of 496 10/20/2016 11:03 AM

Page 184: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3016-NFPA 72-2016 [ Sections 21.1.1, 21.1.2 ]

21.1.1

The requirements of Chapters 7, 10, 14 , 17, 18, 23, 24, and 26 shall apply, unless otherwise noted inthis chapter.

21.1.2

The requirements of Chapter 14 shall apply.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 10:51:45 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee combines text to remove repetitive requirements and redundanttext.

Response Message:

Public Input No. 730-NFPA 72-2016 [Section No. 21.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

184 of 496 10/20/2016 11:03 AM

Page 185: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3017-NFPA 72-2016 [ Section No. 21.2.4 ]

21.2.4*

Emergency control function interface devices shall be located within 3 ft (1m 910 mm ) of the componentcontrolling the emergency control function where the control circuit is not configured as a Class D circuit .

Supplemental Information

File Name Description

72_FR-3017_A.21.2.4_PRO.docx

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 10:54:40 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises the text by correcting the existing reference of 1 m to 0.9 m.Annex material was added with FR 3018 to clarify the distinction between supervised circuits andcontrol functions circuits.

ResponseMessage:

Public Input No. 483-NFPA 72-2016 [Section No. 21.2.4]

Public Input No. 580-NFPA 72-2016 [Section No. 21.2.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

185 of 496 10/20/2016 11:03 AM

Page 186: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3019-NFPA 72-2016 [ Section No. 21.2.11 ]

21.2.11

If a fire alarm system is a component of a life safety network and it communicates data to other systemsproviding life safety functions, or it receives data from such systems, the following shall apply:

(1) The path used for communicating data shall be monitored for integrity. This shall include monitoringthe physical communication communications media and the ability to maintain intelligiblecommunications.

(2) Data received from the network shall not affect the operation of the fire alarm system in any way otherthan to display the status of life safety network components.

(3) Where non-fire alarm systems are interconnected to the fire alarm system using a network or otherdigital communication communications technique, a signal (e.g., heartbeat, poll, ping, query) shall begenerated between the fire alarm system and the non-fire alarm system. Failure of the fire alarmsystem to receive confirmation of the transmission shall cause a trouble signal to indicate within200 seconds.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 11:41:45 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text by replacing the term “communication” with“communications.” The term "communication(s)” was reviewed throughout the entire document forproper use regarding reference to singular and plural use. The term should be plural as used in thiscontext. This change is editorial only.

ResponseMessage:

Public Input No. 446-NFPA 72-2016 [Section No. 21.2.11]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

186 of 496 10/20/2016 11:03 AM

Page 187: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3021-NFPA 72-2016 [ Section No. 21.3.2 ]

21.3.2*

In facilities without a required building fire alarm system, fire alarm initiating devices used to initiateelevator Phase 1 I Emergency Recall Operation shall be connected to either a nonrequired building firealarm system or a dedicated function fire alarm control unit that shall be designated as “elevator recallcontrol and supervisory control unit,” permanently identified on the dedicated function fire alarm controlunit and on the record drawings.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 11:44:46 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee changes from the number “1” to Roman numeral I for consistencywith other areas of NFPA 72.

ResponseMessage:

Public Input No. 286-NFPA 72-2016 [Section No. 21.3.2]

Public Input No. 616-NFPA 72-2016 [Section No. 21.3.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

187 of 496 10/20/2016 11:03 AM

Page 188: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3025-NFPA 72-2016 [ Section No. 21.3.3 ]

21.3.3

Unless otherwise required by the authority having jurisdiction, only the elevator lobby, elevator hoistway,elevator machine room, elevator machinery space, elevator control room, and elevator control spacesmoke detectors or other automatic fire detection as permitted by 21.3.10 21.3.9 shall be used to initiateelevator Phase I Emergency Recall Operation.

Exception: A waterflow switch shall be permitted to initiate elevator Phase I Emergency Recall Operationupon activation of a sprinkler installed at the bottom of the elevator hoistway (the elevator pit), providedthe waterflow switch and pit sprinkler are installed on a separately valved sprinkler line dedicated solelyfor protecting the elevator pit, and the waterflow switch is provided without time-delay capability.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 11:59:54 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee adds the terms “machinery space, elevator” to be consistent withANSI/ASME A.17.1.

ResponseMessage:

Public Input No. 287-NFPA 72-2016 [Section No. 21.3.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

188 of 496 10/20/2016 11:03 AM

Page 189: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3026-NFPA 72-2016 [ Section No. 21.3.4 ]

21.3.4

Each fire alarm initiating device used to initiate elevator Phase I Emergency Recall Operation shall becapable of initiating the elevator recall function when all other devices on the same initiating device circuithave been manually or automatically placed in the alarm condition.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 12:06:12 EDT 2016

Committee Statement

CommitteeStatement:

The word “elevator” is added before Phase I and the word “function” is added after elevatorrecall to be more consistent with ANSI/ASME A.17.1.

ResponseMessage:

Public Input No. 288-NFPA 72-2016 [Section No. 21.3.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

189 of 496 10/20/2016 11:03 AM

Page 190: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3014-NFPA 72-2016 [ New Section after 21.3.6 ]

21.3.7* Fire Alarm Initiating Device(s) Inside Elevator Hoistways.

Fire alarm initiating device(s) required to be installed inside an elevator hoistway by other sections ofthis code or by other governing laws, codes, or standards shall be required to be accessible for service,testing, and maintenance from outside the elevator hoistway.

Supplemental Information

File Name Description

72_FR-3014_A.21.3.7_PRO.docx

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 09:42:29 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee includes this new section and associated annex in Ch. 21 to beconsistent with NFPA 72 requirements for access to fire alarm initiating devices (Sections 3.3.4and 17.4.4) and enhancing the safety of workers performing testing and maintenance.

ResponseMessage:

Public Input No. 337-NFPA 72-2016 [New Section after 21.3.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

190 of 496 10/20/2016 11:03 AM

Page 191: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3027-NFPA 72-2016 [ Section No. 21.3.6 ]

21.3.6

Smoke detectors or other automatic fire detection as specified in 21.3.9 shall not be installed inunsprinklered elevator hoistways unless they are installed to activate the elevator hoistway smoke reliefequipment or to initiate elevator Phase I Emergency Recall Operation as required specified in21.3.14.1(2) 21.3.13.1 and 21.3.14.2(2) 21.3.13.2 .

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 12:55:25 EDT 2016

Committee Statement

CommitteeStatement:

The term “as permitted by” 21.3.9 was changed to “as specified in”, the word “elevator” wasadded before Phase I, and the references to sections 21.3.13.1 (2) and 21.3.13.2(2) werechanged to indicate (3) as this section applies to hoistways detection.

ResponseMessage:

Public Input No. 290-NFPA 72-2016 [Section No. 21.3.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

191 of 496 10/20/2016 11:03 AM

Page 192: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3028-NFPA 72-2016 [ Section No. 21.3.7 ]

21.3.8*

When sprinklers are required in elevator hoistways by other codes or standards NFPA 13 , fire alarminitiating devices shall be installed to initiate elevator recall Phase I Emergency Recall Operation inaccordance with 2.27.3.2.1(c) of ANSI/ASME A17.1/CSA B44, Safety Code for Elevators and Escalators,and the following shall apply:

(1) Where sprinklers are located above at the lowest level top of recall the hoistway , the fire detectiondevice(s) shall be located at the top of the hoistway.

(2) Where sprinklers are located in at the bottom of the hoistway (the pit), fire detection device(s) shallbe installed in the pit in accordance with Chapter 17.

(3) Outputs from the fire alarm system to the elevator controller(s) system shall comply with21.3.14 21.3.13 .

(4) The fire alarm initiating device(s) shall be installed in accordance with Chapter 17 .

Supplemental Information

File Name Description

FR_3028_21.3.7_CJF.docx For staff use

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 13:00:21 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee changes the text to be consistent with the ANSI/ASME A.17.1terminology and to specify the locations of fire detection inside a hoistway.

ResponseMessage:

Public Input No. 292-NFPA 72-2016 [Section No. 21.3.7]

Public Input No. 291-NFPA 72-2016 [Section No. 21.3.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

192 of 496 10/20/2016 11:03 AM

Page 193: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3029-NFPA 72-2016 [ Section No. 21.3.8 ]

21.3.9*

Smoke detectors shall not be installed in elevator hoistways to initiate elevator Phase I emergency recalloperation unless the smoke detector is listed for the environment environmental conditions .

Supplemental Information

File Name Description

72_FR-3029_A.21.3.8_PRO.docx

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 13:17:00 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises the text for consistency of terms (elevator Phase I EmergencyRecall Operation). The Technical Committee edits the annex text for clarity.

ResponseMessage:

Public Input No. 321-NFPA 72-2016 [Section No. 21.3.8]

Public Input No. 322-NFPA 72-2016 [Section No. A.21.3.8]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

193 of 496 10/20/2016 11:03 AM

Page 194: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3020-NFPA 72-2016 [ Section No. 21.3.10 ]

21.3.11

When actuated, any fire alarm initiating device that is used to initiate elevator Phase 1 Emergency RecallOperation shall be annunciated at the building fire alarm control unit or at the fire alarm control unitdescribed in 21.3.2.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 11:43:08 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee changes from the number “1” to Roman numeral I for consistencywith other areas of NFPA 72.

ResponseMessage:

Public Input No. 617-NFPA 72-2016 [Section No. 21.3.10]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

194 of 496 10/20/2016 11:03 AM

Page 195: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3022-NFPA 72-2016 [ Section No. 21.3.13.1 ]

21.3.14.1* Elevator Phase I Emergency Recall Operation to Designated Level Recall .

For each elevator or group of elevators operating in a group automatic operation , an output shall beprovided to signal from the fire alarm system to the elevator recall to the designated level system inresponse to the following:

(1) Activation of smoke detectors detector(s) or other automatic fire detection as permitted by21.3.10 21.3.9 located at any associated elevator(s) lobby served by the elevator(s) other than thelobby at the designated level

(2) Activation of smoke detectors detector(s) or other automatic fire detection as permitted by21.3.10 21.3.9 located at any associated elevator(s) machine room, elevator machinery spacecontaining a motor controller or driving machine , elevator control space, or elevator control roomserving the elevator(s) , except where such rooms or spaces are located at the designated level

(3) Activation of smoke detectors detector(s) or other automatic fire detection as permitted by21.3.10 21.3.9 located in the at any associated elevator(s) hoistway serving the elevatorwhere when sprinklers or elevator control spaces or elevator machinery spaces are located in thehoistway those hoistways , unless otherwise specified in 21.3.14.2(3) 21.3.13.2

Supplemental Information

File Name Description

FR_3022_21.3.13.1_CJF.docx Includes annex

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 11:50:30 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text to be consistent with the ANSI/ASME A.17.1 and addsnew annex material for clarifying the source of the “Group Automatic Operation” definition andclarifies the operation of the elevator car visual signal (by the elevator system) was added.

ResponseMessage:

Public Input No. 324-NFPA 72-2016 [Section No. 21.3.13.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

195 of 496 10/20/2016 11:03 AM

Page 196: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3023-NFPA 72-2016 [ Section No. 21.3.13.2 ]

21.3.14.2* Elevator Phase I Emergency Recall Operation to Alternate Level Recall .

For each elevator or group of elevators operating in a group automatic operation , an output shall beprovided to signal from the fire alarm system to the elevator recall to the alternate level in systemin response to the following:

(1) Activation of smoke detectors detector(s) , or other automatic fire detection as permitted by21.3.10 21.3.9 , located at the designated level lobby served by the elevator(s)

(2) Activation of smoke detectors detector(s), , or other automatic fire detection as permitted by21.3.10 21.3.9 , located in the elevator machine room, elevator machinery space containing a motorcontroller or driving machine , elevator control space, or elevator control room serving the elevator(s)if such rooms or spaces are located at the designated level

(3)

Supplemental Information

File Name Description

FR_3023_21.3.13.2_CJF.docx includes annex

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 11:53:54 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text to be consistent with the ANSI/ASME A.17.1 and addsnew annex material for clarifying the source of the “Group Automatic Operation” definition andclarifies the operation of the elevator car visual signal (by the elevator system) was added.

ResponseMessage:

Public Input No. 325-NFPA 72-2016 [Section No. 21.3.13.2]

* Activation of the fire alarm initiating devices device(s) identified in 21.3.14.1(3) 21.3.13.1 if they areinstalled at or below the lowest level of recall in the elevator hoistway and the alternate level islocated above the designated level

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

196 of 496 10/20/2016 11:03 AM

Page 197: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3024-NFPA 72-2016 [ Section No. 21.3.13.3 ]

21.3.14.3* Elevator Warning Signal.

For each elevator or group of elevators, an output shall be provided to the elevator controller inresponse to any of the following:

Activation of the elevator machine room, elevator machinery space, elevator control space, orelevator control room initiating devices identified in 21.3.14.1 (2) or 21.3.14.2 (2)

Activation of the elevator hoistway initiating devices identified in 21.3.14.1 (3) or 21.3.14.2 (3)

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 11:56:56 EDT 2016

Committee Statement

CommitteeStatement:

This section is unnecessary, redundant and confusing.

The reason is that "Elevator Warning Signal" is not a defined term in ASME A17.1 and there is noneed to provide additional output signals from the fire alarm system to the elevator system inaddition to the signals specified in 21.3.13.1 and 21.3.13.2

The visual signal (firefighter's hat symbol) described in ASME A17.1 is activated solely by theelevator system (solid or flashing) upon a specific defined priority described in A17.1.

New annex material is added to 21.3.13.1 and 21.3.13.2 to specify this operation

The existing annex material for A.21.3.13.3 is unnecessary and confusing and is deleted.

ResponseMessage:

Public Input No. 326-NFPA 72-2016 [Section No. 21.3.13.3]

Public Input No. 327-NFPA 72-2016 [Section No. 21.3.13.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

197 of 496 10/20/2016 11:03 AM

Page 198: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3030-NFPA 72-2016 [ Section No. 21.4 ]

21.4 Elevator Power Shutdown.

21.4.1*

Where When heat detectors detector(s) are used to shut down activate the disconnecting meansdescribed in 2.8 of ANSI/ASME A17.1/CSA B44, Safety Code for Elevators and Escalators , todisconnect the main line power supply to the affected elevator and any other power supplies used tomove the elevator, upon or prior the activation of to sprinkler(s) operation , the detector(s) shall haveboth a lower temperature rating and a higher sensitivity lower response time index (RTI) as compared tothe sprinkler(s) .

21.4.2*

If The heat detectors detector(s) specified in 21.4.1 are used to shut down elevator power prior tosprinkler operation, they shall be placed within 24 in. (610 mm) of each sprinkler and be installed inaccordance with the requirements of Chapter 17.

21.4.2.1

Engineering methods, such as those specified in Annex B, shall be permitted to be used to select andplace heat detectors to ensure response prior to any sprinkler operation under a variety of fire growth ratescenarios.

21.4.3*

If pressure or waterflow switches are used to shut down elevator power immediately upon, or prior to, thedischarge of water from sprinklers activate the disconnecting means specified in 21.4.1 , the use ofdevices with time-delay switches or time-delay capability shall not be permitted.

21.4.4*

Control circuits to shut down elevator power circuit(s) of the disconnecting means specified in 21.4.1shall be monitored for the presence of operating voltage. Loss of voltage to the control circuit(s) for thedisconnecting means shall cause a supervisory signal to be indicated at the building fire alarm control unitor at the control unit described specified in 21.3.2.

21.4.5

The initiating devices described specified in 21.4.2 and 21.4.3 shall be monitored for integrity by the firealarm control unit required specified in 21.3.1and or 21.3.2.

Supplemental Information

File Name Description

FR_3030_21.4_CJF.docx For staff use

FR_3030_A.21.4_CJF.docx

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 13:22:50 EDT 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

198 of 496 10/20/2016 11:03 AM

Page 199: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Committee Statement

CommitteeStatement:

The Technical Committee revises the text including the annex material for consistency ofterms between NFPA 72 and ANSI/ASME A.17.1.

ResponseMessage:

Public Input No. 328-NFPA 72-2016 [Section No. 21.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

199 of 496 10/20/2016 11:03 AM

Page 200: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3031-NFPA 72-2016 [ Section No. 21.5.1 ]

21.5.1*

Status of elevator(s), including location within the hoistway, direction of travel, and whether theelevator(s) are occupied, shall be permitted to be displayed on a building fire alarm system annunciatorlocated at the fire command center.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 13:29:45 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee deletes existing 21.5.1 and A.21.5.1 because the fire alarm system doesnot monitor elevator position, direction of travel, or location. A task group has been assigned toreview the language regarding temperature and presence of smoke and how such shall bedisplayed and defined in 21.5.

ResponseMessage:

Public Input No. 775-NFPA 72-2016 [Section No. 21.5.3]

Public Input No. 442-NFPA 72-2016 [Section No. 21.5.3]

Public Input No. 665-NFPA 72-2016 [Section No. 21.5]

Public Input No. 441-NFPA 72-2016 [Section No. 21.5.2]

Public Input No. 774-NFPA 72-2016 [Section No. A.21.5.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

200 of 496 10/20/2016 11:03 AM

Page 201: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3012-NFPA 72-2016 [ Section No. 21.6 ]

21.6* Occupant Evacuation Elevators.

21.6.1 Elevator Status.

Where one or more elevators are specifically designated and marked for use by occupants for to be usedfor occupant self- evacuation during fires and non-fire emergencies , they shall comply with all of theprovisions of Sections 21.5 and 21.6.

21.6.2 Elevator Occupant Evacuation Operation (OEO).

Outputs from the fire alarm system to the elevator controller(s) system shall be provided to implementelevator occupant evacuation operation in accordance with Section 2.27 of ANSI/ ASME A17.1/CSA B44(2013 2016 ), Safety Code for Elevators and Escalators, as required in21.6.2.1 21.6.2.2 and through 21.6.2.5 21.6.2.7 .

21.6.2.1 Applicability.

OEO shall only be initiated upon an automatic or manual signal from the fire alarm system to theelevator system.

21.6.2.1.1*

OEO shall apply separately to each individual elevator and to elevators having group automaticoperation or designated as an elevator group or group of elevators .

21.6.2.1.2*

OEO shall function per 21.6.2.1.1 only prior to Phase I Emergency Recall Operation.

21.6.2.2 Partial Building Evacuation.

Where an elevator or group of elevators is designated for use by occupants for self- evacuation, theprovisions of 21.6.2.3 through 21.6.2.6 shall apply for partial building evacuation.

21.6.2.3 Initiation.

Output signal(s) shall be provided to initiate elevator occupant evacuation operation upon automatic ormanual detection of a fire on a specific floor or floors as a result of OEO shall be initiated by either manualmeans from the Fire Command Center (FCC) in accordance with 21.6.2.4 or by actuation of anautomatic fire alarm initiating device in accordance with 21.6.2.3.1 .

Activation of any automatic fire alarm initiating device used in the building, other than an initiatingdevice used for elevator Phase I Emergency Recall Operation in accordance with 21.3.13

21.6.2.3.1*

An active automatic fire alarm initiating device that does not initiate Phase I Emergency RecallOperation shall cause the fire alarm system to provide a signal to the elevator system indicating the floorof an active alarm.

21.6.2.3.2*

The floors to be evacuated shall be a contiguous block of floors designated as “the elevator evacuationzone” consisting of at least the floor with an active alarm, two floors above the floor with the activealarm, and two floors below the floor with the active alarm.

21.6.2.3.3*

When the floor designated as the elevator discharge level falls within the elevator evacuation zone, it isnot to be evacuated by the elevator(s), and the fire alarm system shall initiate a voice message toinstruct the occupants on that level to exit the building.

* Activation of manual means at the fire command center by authorized or emergency personnel

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

201 of 496 10/20/2016 11:03 AM

Page 202: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

21.6.2.3.4

If activation of an automatic fire alarm initiating device that does not initiate Phase I Emergency RecallOperation occurs on an additional floor(s), including the elevator discharge level at any time while OEOis in effect, the elevator evacuation zone shall be expanded to include all floors with an active alarm, allfloors between the highest and lowest floor with an active alarm, plus two floors above the highest floorwith an active alarm and two floors below the lowest floor with an active alarm.

21.6.2.3.5

If the first active alarm is on the elevator discharge level, automatic initiation of OEO shall not bepermitted for all elevators having that same elevator discharge level.

21.6.2.3.6*

When the first automatic fire alarm initiating device is activated on an elevator discharge level, the firealarm system shall send a signal to the elevator system indicating that level as being an elevatordischarge level.

21.6.2.4* Floor Identification.

(A)

The output signal(s) shall identify each floor to be evacuated.

(B)

The identified floors shall be a contiguous block of floors including the following:

The floor with the first activated automatic initiating device.

Floors with any subsequently activated automatic initiating device(s).

Floors identified by manual means from the fire command center.

Two floors above the highest floor identified by 21.6.2.4(B) (1) through 21.6.2.4(B) (3).

Two floors below the lowest floor identified by 21.6.2.4(B) (1) through 21.6.2.4(B) (3).

(C)

The identified floors shall be displayed on a standard emergency services interface along with the otherelevator status information required by 21.6.1 .

21.6.2.4* Manual Floor Selection.

(A)

A means shall be provided at the fire command center to allow the manual selection of floors.

(B)

The floors shall be selected on the basis of information from authorized or emergency personnel.

21.6.2.4.1

A means shall be furnished at the FCC to provide for the manual selection of each floor in the building

21.6.2.4.2

The manual floor selection shall be activated only by authorized or emergency personnel.

21.6.2.4.3

When OEO is not yet in effect and a manual floor selection is made to initiate OEO, a signal shall besent to the elevator system simulating an active alarm.

21.6.2.4.4

When OEO is in effect and a manual floor selection is made, the elevator evacuation zone shall beexpanded as described in 21.6.2.3.3 .

21.6.2.4.5

The manual selection shall provide a non-latching output(s).

21.6.2.5* Fire Alarm Output Signals to Elevator System.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

202 of 496 10/20/2016 11:03 AM

Page 203: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

21.6.2.5.1

Output from the fire alarm system to the elevator system shall identify each floor with an activatedautomatic fire alarm initiating device.

21.6.2.5.2

Output from the fire alarm system to the elevator system shall include the following:

(1) The floor with the first activated automatic fire alarm initiating device

(2) Floor(s) with any subsequently activated automatic fire alarm initiating device(s)

(3) Floor(s) selected by manual means from the FCC

21.6.2.5.3

The identified floor(s) shall be displayed on the building fire alarm system annunciator at the FCC or ona listed non-fire alarm system annunciator or other annunciator as approved by the authority havingjurisdiction.

21.6.2.6* Occupant Notification.

The in-building fire emergency voice/alarm communications system shall transmit messages coordinatedmessages throughout the building with the elevator system’s text displays in all elevator lobbies. .

21.6.2.6.1

Automatic voice evacuation messages shall be transmitted to the floors identified in 21.6.2.4 elevatorevacuation zone to indicate the need to evacuate and that elevator service is available.

21.6.2.6.2

Automatic voice messages shall be transmitted to the floors not being evacuated to inform occupants ofevacuation status and shall include an indication within the specific group of elevator(s) performing OEO,to inform occupants that elevator service is not available.

21.6.2.6.3*

Automatic voice messages shall be transmitted to the floors identified in 21.6.2.4 elevator evacuationzone to indicate that elevator service is not available when all elevators have been recalled on Phase IEmergency Recall Operation serving that elevator evacuation zone are out of service. .

21.6.2.6.4

All automatic voice messages shall be coordinated so as not to be in conflict with the text displaysprovided separately by the elevator management system.

21.6.2.6.5*

When required by the building code, the emergency voice/alarm communications system’s speaker(s)located in each OEE lobby shall be connected to a separate notification zone for manual paging only.Individual paging zones per each OEE lobby on each floor, a grouped paging zone for all OEE lobbieson a floor, or a vertical paging zone for each elevator group shall be permitted as approved by theauthority having jurisdiction.

21.6.2.6.6

Visible notification appliances (strobes) shall comply with 24.5.17.3(1) , 24.5.17.3(2) , and24.5.17.3(3) .

21.6.2.7 Total Evacuation.

Where an elevator or group of elevators is designated for use by occupants for evacuation, the provisionsof 21.6.2.7.1 through 21.6.2.7.3 shall apply for total evacuation. A means to initiate total buildingevacuation labeled “ELEVATOR TOTAL BUILDING EVACUATION” shall be provided at the FCC.

21.6.2.7.1

Output(s) to signal elevator occupant evacuation operation for total evacuation shall be manuallyactivated from the fire command center by a means labeled “ELEVATOR TOTAL BUILDINGEVACUATION.” When this means is actuated, the fire alarm system shall provide a signal to the elevatorsystem indicating that all floors in the building are to be evacuated.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

203 of 496 10/20/2016 11:03 AM

Page 204: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

21.6.2.7.2

The output(s) shall identify that all floors are to be evacuated.

21.6.2.7.2

The in-building fire emergency voice/alarm communications system shall transmit an evacuation messagethroughout the building to indicate the need to evacuate.

21.6.2.8* Suspension of OEO for an Individual Elevator or Group of Elevators.

21.6.2.8.1

OEO shall be suspended for an individual elevator or group of elevators when an individual elevator or agroup of elevators have been manually recalled via an elevator system designated key operatedswitch(s) labeled “Car Fire Recall” or “Group Fire Recall”.

21.6.2.8.2

When OEO has been suspended as in 21.6.2.8.1 , the in-building fire emergency voice/alarmcommunications system shall transmit messages coordinated with the elevator system’s text displays incompliance with 21.6.2.6 .

21.6.2.9* Partial Termination of OEO.

21.6.2.9.1

OEO shall be terminated for a specific group of elevator(s) when the signal(s) provided in 21.3.14.1and 21.3.14.2 associated with this group of elevator(s) has initiated Phase I Emergency RecallOperation for this group of elevator(s).

21.6.2.9.2

When OEO has been partially terminated, the in-building fire emergency voice/alarm communicationssystem shall transmit messages coordinated with the elevator system’s text displays in compliance with21.6.2.6 .

21.6.2.10 Total Termination of OEO.

21.6.2.10.1

OEO shall be terminated for all elevators in the building upon reset of the fire alarm system.

21.6.2.10.2*

OEO shall be terminated when there are no elevators available for self-evacuation.

Supplemental Information

File Name Description

FR_3012_21.6_CJF.docx For staff use

FR_3012_A.21.6_CJF.docx

Flowchart_for_PI_740.pdf For staff use

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 09:25:35 EDT 2016

Committee Statement

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

204 of 496 10/20/2016 11:03 AM

Page 205: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Committee Statement: The Technical Committee revises the text to be consistent with ANSI/ASME A.17.1.

Public Input No. 740-NFPA 72-2016 [Sections A.21.6.2.1.1(2), A.21.6.2.1.2, A.21.6.2.1.4, A.21....]

Public Input No. 745-NFPA 72-2016 [New Section after 21.6]

Public Input No. 666-NFPA 72-2016 [Section No. 21.6]

Public Input No. 667-NFPA 72-2016 [Sections A.21.6.2.1.1(2), A.21.6.2.1.2, A.21.6.2.1.4, A.21....]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

205 of 496 10/20/2016 11:03 AM

Page 206: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3013-NFPA 72-2016 [ New Section after 21.7 ]

21.8 High Volume Low Speed (HVLS) Fans.

Where required by NFPA 13 , all HVLS fans shall be interlocked to shut down upon activation of asprinkler waterflow switch.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 09:35:50 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee provides this new Section 21.8 to correlate with NFPA 13. Also theterm “LSHV” is changed to “HVLS” to be consistent with NFPA 13 language.

ResponseMessage:

Public Input No. 316-NFPA 72-2016 [New Section after 21.10.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

206 of 496 10/20/2016 11:03 AM

Page 207: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3034-NFPA 72-2016 [ Section No. 23.1.1 ]

23.1.1*

The application, installation, and performance of fire alarm systems within protected premises, includingfire alarm and supervisory signals, shall comply with the requirements of this chapter.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 13:53:40 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee acknowledges the inclusion of carbon monoxide however, the existingtext was not inclusive of all signals and therefore the examples are removed following the Manualof Style.

ResponseMessage:

Public Input No. 221-NFPA 72-2016 [Section No. 23.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

207 of 496 10/20/2016 11:03 AM

Page 208: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3059-NFPA 72-2016 [ Sections 23.1.2, 23.1.3, 23.1.4, 23.1.5 ]

23.1.2

The requirements of Chapters 7, 10, 12, 14 , 17, 18, 21, 24, and 26 shall apply unless otherwise notedin this chapter.

23.1.3

The requirements of Chapter 14 shall apply.

23.1.3

The requirements of this chapter shall not apply to Chapter 29 unless otherwise noted.

23.1.5

The requirements of Section 24.4 shall apply where in-building fire emergency voice/alarmcommunications systems are used.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Sun Aug 07 10:49:17 EDT 2016

Committee Statement

Committee Statement: Combining text to remove repetitive requirements and removing redundant text.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

208 of 496 10/20/2016 11:03 AM

Page 209: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3035-NFPA 72-2016 [ Section No. 23.2.1 ]

23.2.1* Purpose.

The systems covered in Chapter 23 shall be for the protection of life or property, or both, by indicating theexistence of heat, fire, smoke, carbon monoxide, or other emergencies impacting the protected premises.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 13:57:54 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text and acknowledges the inclusion of carbon monoxideinto this standard.

ResponseMessage:

Public Input No. 222-NFPA 72-2016 [Section No. 23.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

209 of 496 10/20/2016 11:03 AM

Page 210: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3036-NFPA 72-2016 [ Section No. 23.3.3.1 ]

23.3.3.1* Building Fire Alarm Systems.

Protected premises fire alarm systems that serve the general fire alarm needs of a building or buildingsshall include one or more of the following systems or functions:

(1) Manual fire alarm signal initiation

(2) Automatic fire alarm and supervisory signal initiation

(3) Monitoring of abnormal conditions in fire suppression systems

(4) Activation of fire suppression systems

(5) Activation of emergency control functions

(6) Activation of fire alarm notification appliances

(7) In-building fire emergency voice/alarm communications

(8) Automatic carbon monoxide alarm initiation

(9) Guard’s tour supervisory service

(10) Process monitoring supervisory systems

(11) Activation of off-premises signals

(12) Combination systems

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 14:00:04 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee acknowledges the inclusion of carbon monoxide however, the mainfocus is that this is still a fire alarm system. Standalone carbon monoxide systems are considered adedicated function system which would be permitted and required to follow the installationrequirements.

ResponseMessage:

Public Input No. 298-NFPA 72-2016 [Section No. 23.3.3.1]

Public Input No. 299-NFPA 72-2016 [Section No. 23.3.3.2]

Public Input No. 297-NFPA 72-2016 [Section No. 23.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

210 of 496 10/20/2016 11:03 AM

Page 211: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 5049-NFPA 72-2016 [ Section No. 23.6.1.3 ]

Global FR-3050

23.6.1.3*

The requirements in 23.6.1 shall not apply to the following:

(1) Circuits between enclosures containing transponders and control units regardless of the number ofinitiating devices, notification appliances, or control relays that might be connected to those controlunits.

(2) Circuits connecting short-circuit fault isolation modules to enclosures containing transponders andcontrol units where the conductors are installed in metallic raceway or equivalently protected againstmechanical injury and where the circuit does not exceed 3 ft (1 m0.9 m) in length.

(3)

Supplemental Information

File Name Description

72_FR-5049_A.23.6.1.3_3_PRO.docx

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 23 12:42:06 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee provides new text because expansion of the SLC circuits should beallowed when the original design did not require the limitations of 23.6.1.

ResponseMessage:

Public Input No. 590-NFPA 72-2016 [New Section after A.23.6.1.3]

Public Input No. 589-NFPA 72-2016 [New Section after 23.6.1.3]

* When alterations or modifications are made to an existing SLC that was not required to meet therequirements of 23.6.1 when it was originally installed, the provisions of 23.6.1 shall not berequired.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

211 of 496 10/20/2016 11:03 AM

Page 212: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 5054-NFPA 72-2016 [ Section No. 23.6.2 ]

23.6.2 Class N Devices.

No area or zone shall be serviced solely by a single device where Class N Class N pathways aredeployed, such that a single device failure would render an area or zone incapable of initiating inputsignals or receiving output signals.

Exception: When a risk analysis is performed to determine areas where a single device is sufficient andacceptable to the authority having jurisdiction.

23.6.2.1

Where a device as referenced by a risk analysis shows that only one device is required and whereacceptable to the authority having jurisdiction, the requirements of 23.6.2 shall not apply. is serviced byonly a single pathway, it shall terminate that pathway with no capability to connect additional endpointdevices to the pathway.

23.6.2.2

.A single fault on a Class N pathway connected to the addressable devices shall not cause the loss ofmore than one addressable device.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 18 12:07:14 EDT 2016

Committee Statement

CommitteeStatement:

SIG-PRO eliminates specific exceptions to comply with Manual of Style. Some exceptionscannot be eliminated because they would result in a single subsection, which is not permitted in1.8 of the Manual of Style.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

212 of 496 10/20/2016 11:03 AM

Page 213: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3003-NFPA 72-2016 [ Section No. 23.6.3 ]

23.6.3 Class N Shared Pathways.

Class N pathways shall be required to use shared pathway Level 3 as specified in 12.5.4 except aspermitted by 23.6.3.2 through 23.6.3.8 .

23.6.3.1 Accessibility.

Class N pathways shall not be accessible to the general public for any purpose or building occupants forany purpose other than specified in the analysis, maintenance, and deployment plans.

23.6.3.2 Level 1 and Level 2.

Shared pathways Levels 1 and 2 shall be permitted subject to a thorough written analysis of the risks, themaintenance plans, roles and responsibilities, and a deployment plan as identified in and subjectto 23.6.3.3and when approved by an AHJ in consideration of the analysis, maintenance, and deploymentplans through 23.6.3.8 .

23.6.3.3 Deployment Plan.

23.6.3.3.1

All equipment connected to shared pathways shall be documented in the deployment plan.

23.6.3.3.1.1

The documentation shall include manufacturer, model, listings, and intended purpose and reason forinclusion on the shared network.

23.6.3.3.1.2

The deployment plan shall identify how and where each piece of equipment is connected.

23.6.3.3.2

All connection ports, used or spare, where any unauthorized or unintended equipment may be added tothe shared network, shall be identified as for use only by equipment consistent with the deployment plan.

23.6.3.4 Change Control Plan.

Configuration upgrades and updates shall be governed by a change control plan, which that determinesthe policy and procedure of the change and ensures that all documentation is correspondingly updated.

23.6.3.5 Management Organization.

23.6.3.5.1

An organization shall be established and maintained to manage the life safety network and shall performthe following tasks:

(1) Contain members appropriately certified by each manufacturer of the equipment and devicesdeployed on shared pathways to maintain such a network

(2) Service and maintain all shared Class N pathways

(3) Maintain the deployment and shared pathways plan for the lifetime of the shared pathways

23.6.3.5.2

Other service personnel, even when certified to service a specific system (i.e., fire alarm or MNS), shallbe authorized and managed by this organization to ensure any outages of any system are planned,managed, and documented and appropriate steps are taken during outages to provide alternate protectionof life and property.

23.6.3.6 Analysis.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

213 of 496 10/20/2016 11:03 AM

Page 214: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

23.6.3.6.1

The analysis shall be performed to determine and document communications capability as follows:

(1) Calculation of minimum required bandwidth such that all life safety systems can be guaranteed tooperate simultaneously and within required time limits

(2) Total bandwidth provided by the network

(3) Future bandwidth requirements

(4) Method of providing and maintaining the prioritization of life safety traffic over non–life safety traffic

23.6.3.6.2

The analysis shall determine and document the power distribution capability as follows:

(1) The methods provided to maintain power to all shared pathway equipment

(2) A calculation of power requirements of all connected equipment

(3) Secondary power capacities provided to maintain all life safety equipment with minimum operationalcapacity in accordance with 10.6.7.2.1.2

(4) Methods to disengage any non–life safety equipment in the event of emergency operation if requiredto support the minimum operational capacity requirements

23.6.3.7 Maintenance Plan.

23.6.3.7.1

The maintenance plan shall identify policy and procedures to monitor, maintain, test, and control changeof the shared pathways.

23.6.3.7.2

Written procedures shall be presented in maintenance plans to govern the following:

(1) Physical access to all parts of the Class N network equipment (i.e., switches, ports, server,controllers, devices, or components)

(2) Electronic access to all parts of the Class N network (i.e., passwords, addresses)

(3)

(4) Upgrade procedures

(5) Change control procedures, with consideration given to require an updated risk analysis if necessary

(6) Prioritization and/or segregation configuration information for life safety traffic

(7) Maintenance and testing plans to ensure the minimum operational capacity with respect to secondarypower is maintained

(8) Other service, maintenance, or reconfiguration plans for any connected equipment

23.6.3.8 Other Risks.

Any other identifiable risk as required by the AHJ shall be discussed and addressed in the analysis andmaintenance plans.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Aug 03 12:41:40 EDT 2016

* Service outage impairment process with notices of impairment and contingency plans for affectedsystems

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

214 of 496 10/20/2016 11:03 AM

Page 215: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Committee Statement

CommitteeStatement:

The Technical Committee revises the text and clarifies that the accessibility requirements apply toall Class N pathways. The use of Level 1 or 2 require a risk analysis including the additional itemsoutlined in 23.6.3.3 through 23.6.3.8. Also changed 23.6.3.3.2 to conform to Manual of Style.

ResponseMessage:

Public Input No. 421-NFPA 72-2016 [Section No. 23.6.3 [Excluding any Sub-Sections]]

Public Input No. 422-NFPA 72-2016 [Section No. 23.6.3.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

215 of 496 10/20/2016 11:03 AM

Page 216: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3008-NFPA 72-2016 [ Section No. 23.8.3 ]

23.8.3 Protected Premises Fire Alarm Systems Interconnected with Dwelling Unit Fire and CarbonMonoxide Warning Equipment.

23.8.3.1

A protected premises fire alarm system shall be permitted to be interconnected to a the household firealarm system(s) warning equipment for the purpose of activating the notification appliances connected tothe household fire alarm system(s) warning equipment .

23.8.3.2

The activation of dwelling unit smoke alarms warning equipment shall only be permitted to be displayed atthe protected premises control unit and annunciators as supervisory signals.

23.8.3.3

If interconnected, an alarm condition at the protected premises fire alarm system shall cause the firealarm notification appliance(s) within the family living unit of the dwelling unit fire warningsystem equipment to become energized. The notification appliances shall remain energized until theprotected premises fire alarm system is silenced or reset.

23.8.3.4

The interconnection circuit or path from the protected premises fire alarm system to the dwelling unit firewarning system equipment shall be monitored for integrity by the protected premises fire alarm system inaccordance with Section 12.6.

23.8.3.5

An alarm condition occurring at the dwelling unit fire warning system equipment or the operation of anytest switches provided as part of the dwelling unit fire warning equipment shall not cause an alarmcondition at the protected premises fire alarm system.

Supplemental Information

File Name Description

FR_3008_23.8.3_CJF.docx For staff use

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Aug 04 09:33:02 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text and acknowledges the inclusion of household carbonmonoxide into NFPA 72. The text is changed for consistency with terminology.

ResponseMessage:

Public Input No. 227-NFPA 72-2016 [Section No. 23.8.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

216 of 496 10/20/2016 11:03 AM

Page 217: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

217 of 496 10/20/2016 11:03 AM

Page 218: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3010-NFPA 72-2016 [ New Section after 23.8.4.1 ]

23.8.4.2 Building System Information Unit (BSIU).

23.8.4.2.1*

A building system information unit (BSIU) shall be listed to product safety standard ANSI/UL 60950,Information Technology Equipment — Part 1: General Requirements , or ANSI/UL 62368-1Audio/Video, Information and Communication Technology Equipment — Part 1: Safety Requirements,or equivalent.

23.8.4.2.2

Where a BSIU provides control of the fire alarm system, the requirements in 23.8.4.2.2.1 through23.8.4.2.2.4 shall also apply.

23.8.4.2.2.1

A fire alarm control unit (FACU) controlling the fire alarm system shall be located within the same roomas the BSIU.

23.8.4.2.2.2*

The BSIU shall not be permitted to perform fire alarm system control features that cannot beaccomplished by the FACU within the room.

23.8.4.2.2.3

The communication path from the FACU and the BSIU shall meet the requirements of 23.8.4.4.1through 23.8.4.4.3

23.8.4.2.2.4

The application software for the BSIU shall be listed to ANSI/UL 864, Control Units and Accessories forFire Alarm Systems

Supplemental Information

File Name Description

72_FR-3010_A.23.8.4.1_PRO.docx

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Aug 04 09:51:40 EDT 2016

Committee Statement

Committee Statement: The Technical Committee adds text to introduce the concept of the BSIU.

Response Message:

Public Input No. 538-NFPA 72-2016 [New Section after 23.8.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

218 of 496 10/20/2016 11:03 AM

Page 219: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3067-NFPA 72-2016 [ Section No. 23.8.4.5 ]

23.8.4.6

Speakers Loudspeakers used as alarm notification appliances on fire alarm systems shall also bepermitted to be used for emergency communications systems when installed in accordance withChapter 24.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Sun Aug 07 13:52:03 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee replaces the term “speakers” with “loudspeakers” forconsistency.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

219 of 496 10/20/2016 11:03 AM

Page 220: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3057-NFPA 72-2016 [ Section No. 23.8.4.8 ]

23.8.4.9*

Signals from carbon monoxide detectors and carbon monoxide detection systems transmitted to a firealarm system shall be indicated as a carbon monoxide alarm signal.

Exception: When in accordance with the building’s emergency response plan, evacuation plan, firesafety plan, or similar documentation, signals from carbon monoxide detectors and carbon monoxidedetection systems transmitted to a fire alarm system shall be permitted to be supervisory signals.

23.8.4.9.1

Signals from carbon monoxide detectors and carbon monoxide detection systems transmitted to a firealarm system shall be indicated as “Carbon Monoxide Alarm” on the fire alarm system control unit orannunciator.

23.8.4.9.2*

Fire alarm system processing for and occupant response to carbon monoxide alarm signals shall be inaccordance with the building’s emergency response plan, evacuation plan, fire safety plan, or similardocumentation.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Sun Aug 07 10:40:19 EDT 2016

Committee Statement

CommitteeStatement:

Revised text to be consistent with changes in NFPA 72. The Technical Committee deletes theannex text to 23.8.4.8 as NFPA 720 has been incorporated into NFPA 72 and is no longer astandalone document.

ResponseMessage:

Public Input No. 752-NFPA 72-2016 [Section No. A.23.8.4.8]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

220 of 496 10/20/2016 11:03 AM

Page 221: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 5005-NFPA 72-2016 [ Section No. 23.8.5.1.2 ]

23.8.5.1.2*

Where connected to a supervising station, fire alarm systems employing automatic fire detectors orwaterflow detection devices shall include a manual fire alarm box to initiate a signal to the supervisingstation.

23.8.5.1.3

Fire alarm systems dedicated to elevator recall control and supervisory service as permitted inSection 21.3 shall not be required to meet 23.5.1.2 .

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Thu Aug 11 10:55:35 EDT 2016

Committee Statement

CommitteeStatement:

SIG-PRO eliminates specific exceptions to comply with Manual of Style. Some exceptionscannot be eliminated because they would result in a single subsection, which is not permitted in1.8 of the Manual of Style.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

221 of 496 10/20/2016 11:03 AM

Page 222: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 5006-NFPA 72-2016 [ Section No. 23.8.5.5.1 ]

23.8.5.5.1

Where required by other governing laws, codes, or standards to be electronically monitored, waterflowalarm-initiating devices shall be connected to a dedicated function fire alarm control unit designated as“sprinkler waterflow and supervisory system” and permanently identified on the control unit and recorddrawings.

23.8.5.5.2

Where waterflow Waterflow alarm-initiating devices are connected to a building fire alarm system, adedicated function fire alarm control unit shall not be required to meet the requirements of 23.8.5.5.1 .

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Thu Aug 11 10:56:40 EDT 2016

Committee Statement

CommitteeStatement:

SIG-PRO eliminates specific exceptions to comply with Manual of Style. Some exceptionscannot be eliminated because they would result in a single subsection, which is not permitted in1.8 of the Manual of Style.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

222 of 496 10/20/2016 11:03 AM

Page 223: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 5007-NFPA 72-2016 [ Section No. 23.8.5.6.1 ]

23.8.5.6.1

Where required by other governing laws, codes, or standards to be electronically monitored, supervisorysignal–initiating devices shall be connected to a dedicated function fire alarm control unit designated as“sprinkler waterflow and supervisory system” and permanently identified on the control unit and recorddrawings.

23.8.5.6.2

Where supervisory Supervisory signal–initiating devices are connected to a building fire alarm system, adedicated function fire alarm control unit shall not be required to meet the requirements of 23.8.5.6.1 .

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Thu Aug 11 10:57:57 EDT 2016

Committee Statement

CommitteeStatement:

SIG-PRO eliminates specific exceptions to comply with Manual of Style. Some exceptionscannot be eliminated because they would result in a single subsection, which is not permitted in1.8 of the Manual of Style.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

223 of 496 10/20/2016 11:03 AM

Page 224: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3038-NFPA 72-2016 [ Section No. 23.8.5.6.3 ]

23.8.5.6.4*

If a valve is installed in the connection between a sprinkler system and an initiating device, the valve shallbe supervised in accordance with 17.17.1 unless the valve is arranged to cause operation of thesupervisory signal initiating device when it is in its non off -normal position.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 14:08:47 EDT 2016

Committee Statement

Committee Statement: The Technical Committee edits the text for clarity.

Response Message:

Public Input No. 642-NFPA 72-2016 [Section No. 23.8.5.6.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

224 of 496 10/20/2016 11:03 AM

Page 225: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3015-NFPA 72-2016 [ New Section after 23.8.5.11 ]

23.8.5.12 Disconnect Switches and Disable Functions.

Operation of any disconnect switch or disable function associated with the fire alarm system, when inthe off-normal condition, shall be indicated at the building fire alarm control unit or at a dedicatedfunction(s) fire alarm control unit if provided.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 10:06:38 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee includes this section within the Fire Alarm Inputs Section 23.8.5 with anew proposed section title and wording.The new section is consistent with 23.11.5.1 but is notlimited to suppression systems only.

ResponseMessage:

Public Input No. 482-NFPA 72-2016 [New Section after 21.8]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

225 of 496 10/20/2016 11:03 AM

Page 226: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 5008-NFPA 72-2016 [ Section No. 23.8.5.11.1 ]

23.8.5.11.1

Automatic fire suppression system alarm–initiating alarm-initiating devices and supervisory signal-initiating signal–initiating devices and their circuits shall be designed and installed so that they cannot besubject to tampering, opening, or removal without initiating a signal. This provision shall include junctionboxes installed outside of buildings to facilitate access to the initiating device circuit.

Note Covers of junction boxes inside of buildings.

Note Tamper–resistant screws or other approved mechanical means shall be permitted for preventingaccess to junction boxes and devices covers installed outside of buildings.

23.8.5.11.2

Covers of junction boxes inside of buildings shall not be required to meet the requirements of23.8.5.11.1 .

23.8.5.11.3

Tamper–resistant Tamper-resistant screws or other approved mechanical means shall be permitted inlieu of the requirements of 23.8.5.11.1 for preventing access to junction boxes and device covers installedoutside of buildings.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Thu Aug 11 10:59:21 EDT 2016

Committee Statement

CommitteeStatement:

SIG-PRO eliminates specific exceptions to comply with Manual of Style. Some exceptionscannot be eliminated because they would result in a single subsection, which is not permitted in1.8 of the Manual of Style.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

226 of 496 10/20/2016 11:03 AM

Page 227: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3060-NFPA 72-2016 [ Sections 23.8.6.2.3, 23.8.6.2.4 ]

23.8.6.2.3

The emergency evacuation signal specified in 18.4.2 shall not be required to operate in exit stairenclosures and exit passageways.

23.8.6.2.4

The emergency evacuation signal specified in 18.4.2 shall not be required to operate in elevator cars.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Sun Aug 07 10:51:18 EDT 2016

Committee Statement

CommitteeStatement:

To be consistent with other sections in the code referencing the automatic evacuationsignal.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

227 of 496 10/20/2016 11:03 AM

Page 228: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3051-NFPA 72-2016 [ Section No. 23.10.2 ]

23.10.2*

Fire alarm systems used for partial evacuation and relocation shall be designed and installed such thatattack by fire within an evacuation a signaling zone shall not impair control and operation of thenotification appliances outside the evacuation signaling zone. Performance features provided to ensuresurvivability shall be described and technical justification provided in the documentation submitted to theauthority having jurisdiction with the evaluation required in 23.4.3.1.

Supplemental Information

File Name Description

72_FR-3051_A.23.10.2_PRO.docx

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 15:33:56 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises the text (including the annex) in order to align the terms tobe consistent with the definition of “signaling zone”.

ResponseMessage:

Public Input No. 700-NFPA 72-2016 [Section No. 23.10.2]

Public Input No. 703-NFPA 72-2016 [Section No. A.23.10.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

228 of 496 10/20/2016 11:03 AM

Page 229: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3068-NFPA 72-2016 [ Section No. 23.10.3 ]

23.10.3

Speakers Loudspeakers that transmit tone signals shall be permitted to be used as fire alarm notificationappliances.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Sun Aug 07 13:53:29 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee replaces the term “speakers” with “loudspeakers” forconsistency.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

229 of 496 10/20/2016 11:03 AM

Page 230: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3009-NFPA 72-2016 [ Section No. 23.16.2 ]

23.16.2* Power Supplies.

A primary battery(s) (dry cell) that meet the requirements of 23.16.2.1 or 23.16.2.2 shall be permitted tobe used as the sole power source for devices incorporating a low-power radio transmitter/transceiverwhere all of the following conditions are met: .

23.16.2.1

The following conditions shall be met when one or more primary batteries are utilized and a catastrophic(open or short) single battery failure affects the alarm operation of the device:

(1) Each transmitter/transceiver shall serve only one device and shall be individually identified at thesystem control unit.

(2) The battery(s) shall be capable of operating the low-power radio transmitter/transceiver and itsassociated device for not less than 1 year before the battery depletion threshold is reached.

(3) A low battery signal shall be transmitted before the device is no longer capable of providing 7 days oftrouble signal operation followed by the signaling of a single non-trouble response.

(4) The low battery signal shall be distinctive from alarm, supervisory, tamper, and trouble signals, shallvisibly identify the affected low-power radio transmitter/transceiver, and, when silenced, shallautomatically re-sound at least once every 4 hours.

(5) Catastrophic (open or short) battery failure shall cause a trouble signal identifying the affectedlow-power radio transmitter/transceiver at the system control unit. When silenced, the trouble signalshall automatically re-sound at least once every 4 hours.

(6) Any mode of failure of a primary battery in a low-power radio transmitter/transceiver shall not affectany other low-power radio transmitter/transceiver.

23.16.2.2

The following conditions shall be met when multiple batteries are utilized and a catastrophic (open orshort) single battery failure does not affect the alarm operation of the device:

(1) Two or more batteries shall be provided.

(2) The combined batteries shall be capable of operating the low-power radio transmitter/transceiverand its associated device for not less than 1 year before the battery depletion threshold in23.16.2.2(3) is reached.

(3) A low battery signal shall be transmitted before the device is no longer capable of providing 7 daysof trouble signal operation followed by the signaling of a single non-trouble response.

(4) Each individual battery, primary and secondary, shall be separately monitored for the batterydepletion threshold, and a low battery signal shall be transmitted when an individual battery hasreached the battery depletion threshold.

(5) Following the failure of a single battery, the remaining battery(s) shall be capable of operating thelow-power radio transmitter/transceiver and its associated device for not less than 7 days when thebattery depletion threshold in 23.16.2.2(3) is reached.

(6) The low battery signal shall be distinctive from alarm, supervisory, tamper, and trouble signals,shall visibly identify the affected low-power radio transmitter/transceiver, and, when silenced, shallautomatically re-sound at least once every 4 hours.

(7) Catastrophic (open or short) failure of any individual battery shall cause a trouble signal identifyingthe affected low-power radio transmitter/transceiver at the system control unit. When silenced, thetrouble signal shall automatically re-sound at least once every 4 hours.

(8) Each transmitter/transceiver shall be permitted to serve more than one device and shall beindividually identified at the system control unit.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

230 of 496 10/20/2016 11:03 AM

Page 231: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Supplemental Information

File Name Description

FR_3009_23.16.2_CJF.docx For staff use

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Aug 04 09:39:40 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises the text as the existing requirements limit the number of devicesand the effect on any other low-power transmitter that can be served by a low-power radiotransmitter/transceiver because it may be operating from a single primary battery as the sole powersource and due to maintenance and battery failure. If at least two independent primary batterysources are provided and are both monitored for integrity and each is capable of serving the load,then the number of devices served should not be restricted.

ResponseMessage:

Public Input No. 474-NFPA 72-2016 [Section No. 23.16.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

231 of 496 10/20/2016 11:03 AM

Page 232: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3011-NFPA 72-2016 [ Section No. 23.16.3 ]

23.16.3 Alarm Signals.

23.16.3.1*

When a wireless initiating device is actuated, its low-power radio transmitter/transceiver shallautomatically transmit an alarm signal comply with 23.16.3.1.1 through 23.16.3.1.4 .

23.16.3.1.1

It shall automatically transmit an alarm signal and be identified at the fire alarm system.

23.16.3.1.2

To ensure the receipt of an alarm signal by the control unit, the low-power radio transmitter/transceivershall automatically repeat alarm transmissions at intervals not exceeding 60 seconds until thetransmitter/transceiver receives a signal confirming receipt of the alarm signal by the control unit .

23.16.3.1.3*

Signals shall have priority in accordance with 23.8.4.7.

23.16.3.1.4

Response time shall be in accordance with 10.11.1.

23.16.3.1.5*

A An fire alarm signal from a low-power radio transmitter/transceiver shall latch at its system the firealarm control unit system until manually reset and shall identify the particular initiating device in alarm.

23.16.3.1.6

Sixty seconds after the conclusion of resetting the fire alarm system, a non-restored actuated low-powerradio transmitter/transceiver shall be identified at the fire alarm systems.

23.16.3.2

Each low-power radio transmitter/transceiver shall automatically repeat alarm transmissions at intervalsnot exceeding 60 seconds until the initiating device is returned to its non-alarm condition.

Supplemental Information

File Name Description

72_FR-3011_A.23.16.3.1.5_PRO.docx

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 09:02:19 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text to clarify there is no need to continue to transmit an alarmsignal once it has been received by the control unit since alarm signals must be latched at the

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

232 of 496 10/20/2016 11:03 AM

Page 233: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

control unit. This will help to reduce the power consumption from battery operated devices duringsystem testing and increase battery life.

ResponseMessage:

Public Input No. 540-NFPA 72-2016 [Section No. 23.16.3]

Public Input No. 295-NFPA 72-2016 [Section No. 23.16]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

233 of 496 10/20/2016 11:03 AM

Page 234: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 506-NFPA 72-2016 [ Section No. 24.3.1.2 ]

24.3.1.2*

Where no listed loudspeaker exists to listed loudspeakers do not achieve the intelligibility requirements ofthe Code for a notification zone, nonlisted loudspeakers shall be permitted to be installed to achieve theintelligibility for that notification zone.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 12:48:31 EDT 2016

Committee Statement

CommitteeStatement:

A listed loudspeaker might exist but not be appropriate for a given application. The otherchanges in this section are editorial.

ResponseMessage:

Public Input No. 779-NFPA 72-2016 [Section No. 24.3.1.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

234 of 496 10/20/2016 11:03 AM

Page 235: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 541-NFPA 72-2016 [ Section No. 24.3.7.1 ]

24.3.7.1*

One-way emergency communications systems shall consist of one or more of the following:

(1) In-building fire emergency voice/alarm communications systems (EVACS) (see Section 24.4)

(2) In-building mass notification systems (see Section 24.5)

(3) Wide-area mass notification systems (see Section 24.6)

(4) Distributed recipient mass notification systems (DRMNS) (see Section 24.7)

Supplemental Information

File Name Description

FR_541_A.24.3.7.1.docx Annex material being added in the FR

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 23:39:03 EDT 2016

Committee Statement

CommitteeStatement:

Other codes reference NFPA 72 for EVAC design and installation. Given that when EVAC isrequired by the building code in consideration of fire risk, this FR seeks to provide guidance to AHJsthat other risks might also be considered that require a risk analysis, and lead to MNS equipmentalso being required in addition to the EVACS. And that there is opportunity to interface MNSequipment to the EVACS.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

235 of 496 10/20/2016 11:03 AM

Page 236: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 507-NFPA 72-2016 [ New Section after 24.3.10 ]

24.3.11 Building System Information Unit.

A building system information unit that displays information and events from the mass notificationsystem shall comply with 23.8.4.4.1 through 23.8.4.4.3 .

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 13:00:17 EDT 2016

Committee Statement

CommitteeStatement:

This FR supports the Code change proposals in Chapter 23 for the BSIU. This allows the inclusionof MNS in the BSIU and follows the requirements in 23.8.4.2.1 and 23.8.4.2.2. Buildings areadvancing with technologies in HVAC, Security, Elevators, Energy Controls, and Lighting.

There are integration and human interfaces that the building operators and designers areexpecting. First responders are embracing new technologies and the fire life safety industry needsto do so as well without affecting reliability and performance. This FR is the first step in taking thefire life safety system into the technology flow.

ResponseMessage:

Public Input No. 539-NFPA 72-2016 [New Section after 24.3.10]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

236 of 496 10/20/2016 11:03 AM

Page 237: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 508-NFPA 72-2016 [ Section No. 24.3.10 ]

24.3.10* Control Unit Listing for Mass Notification Systems.

Control units installed as part of a mass notification system shall be in compliance with this Code and atleast one of the following applicable standards:

(1) ANSI/UL 864, Standard for Control Units and Accessories for Fire Alarm Systems

ANSI/UL 2017, Standard for General-Purpose Signaling Devices and Systems

(2) ANSI/UL 2572, Mass Notification Systems.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 13:03:07 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee retains the reference to ANSI/UL 864 as new systems are beingintegrated into existing systems. The associated annex material in A.24.3.10 addresses theperformance requirements when using an 864 unit. ANSI/UL 2017 includes both emergency andnon-emergency systems so its scope is too broad for mass notification systems.

ResponseMessage:

Public Input No. 681-NFPA 72-2016 [Section No. 24.3.10]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

237 of 496 10/20/2016 11:03 AM

Page 238: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 525-NFPA 72-2016 [ New Section after 24.3.11.1 ]

24.3.12.1.1

When an owner has developed a risk analysis in accordance with 24.3.12 , such risk analysis shall bepermitted to be used as a baseline in preparing the risk analysis for new or renovated facilities that aresimilar in nature.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 22:34:41 EDT 2016

Committee Statement

CommitteeStatement:

This revision permits the use of the existing risk analysis as the framework for thedevelopment of a new risk analysis when a facility is added.

ResponseMessage:

Public Input No. 508-NFPA 72-2016 [New Section after 24.3.11.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

238 of 496 10/20/2016 11:03 AM

Page 239: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 522-NFPA 72-2016 [ Section No. 24.3.13.4.1 ]

24.3.14.4.1

For systems employing relocation or partial evacuation, a Level 2 or Level 3 pathway survivability shall berequired , unless otherwise permitted in 24.3.14.4.1.1 or 24.3.14.4.1.2 .

Exception No. 1: Level 1 shall be permitted where notification zones are separated by less than 2-hourfire-rated construction.

Exception No. 2: Level 1 shall be permitted where there are at least two pathways that are separatedby at least one-third the maximum diagonal of the notification or signaling zones that the pathways arepassing through and the pathway is Class X or Class N.

24.3.14.4.1.1

Where notification zones are separated by less than 2-hour fire-rated construction, a pathwaysurvivability of Level 1, 2 or 3 shall be permitted.

24.3.14.4.1.2

Where Class X or Class N system pathways are installed and the incoming and outgoing pathways areseparated by at least one-third the maximum diagonal of the notification zone, a pathway survivability ofLevel 1, 2 or 3 shall be permitted.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 22:13:37 EDT 2016

Committee Statement

CommitteeStatement:

This revision is made based on the proposal in Public Input 210 to remove all exceptions fromthe document to comply with the Manual of Style.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

239 of 496 10/20/2016 11:03 AM

Page 240: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 510-NFPA 72-2016 [ Section No. 24.3.13.6 ]

24.3.14.6

Pathway survivability levels for wide- area mass notification systems shall be determined by the riskanalysis.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 14:02:34 EDT 2016

Committee Statement

Committee Statement: This is an editorial revision to maintain consistency.

Response Message:

Public Input No. 689-NFPA 72-2016 [Section No. 24.3.13.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

240 of 496 10/20/2016 11:03 AM

Page 241: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 523-NFPA 72-2016 [ Section No. 24.3.13.7 ]

24.3.14.7

Two-way in-building wired emergency communications systems that are installed where the building hasless than 2-hour fire-rated construction shall have a pathway survivability of Level 1, 2, or Level 3.

Exception: Level 1 shall be permitted where the building is less than 2-hour fire-rated construction.

24.3.14.8

Two-way in-building wired emergency communication systems that are installed where the building has2-hour fire-rated construction or greater shall have a pathway survivability of Level 2 or 3.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 22:19:38 EDT 2016

Committee Statement

CommitteeStatement:

This revision is based on the proposal in Public Input 210 to remove all exceptions from thedocument to comply with the Manual of Style.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

241 of 496 10/20/2016 11:03 AM

Page 242: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 511-NFPA 72-2016 [ Section No. 24.3.13.8 ]

24.3.14.9

Two-way radio communications enhancement systems shall comply with 24.3.14.9.1 through24.3.14.9.4 .

24.3.14.9.1*

Where a two-way radio communications enhancement system is used in lieu of a two-way in-buildingwired emergency communications system, it shall have a pathway survivability of Level 1, Level 2, orLevel 3.

Exception: Where leaky feeder cable is utilized as the antenna, it shall not be required to be installedin metal raceway.

24.3.14.9.1.1

The feeder and riser coaxial cables shall be rated as plenum cables.

24.3.14.9.1.2

The feeder coaxial cables shall be connected to the riser coaxial cable using hybrid coupler devices of avalue determined by the overall design.

24.3.14.9.2

Where a two-way radio communications enhancement system is used in lieu of a two-way in-buildingwired emergency communications system, the design of the system shall be approved by the authorityhaving jurisdiction.

24.3.14.9.3*

Riser coaxial cables shall be rated as riser cables and routed through a 2-hour-rated enclosure.

24.3.14.9.4

The connection between the riser and feeder coaxial cables shall be made within the 2-hour-ratedenclosure, and passage of the feeder cable in and out of the 2-hour-rated enclosure shall be firestoppedto 2-hour ratings.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 14:04:14 EDT 2016

Committee Statement

CommitteeStatement:

Section 24.9.2 requires two-way radio communication enhancement systems to be in accordancewith NFPA 1221. NFPA 1221 addresses pathway survivability, although it currently is extracted textfrom NFPA 72. The Technical Committee deletes the text in NFPA 72 as it is also in NFPA 1221.The text need not be in both documents. Delete associated annex material.

ResponseMessage:

Public Input No. 430-NFPA 72-2016 [Section No. 24.3.13.8.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

242 of 496 10/20/2016 11:03 AM

Page 243: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Public Input No. 431-NFPA 72-2016 [Section No. 24.3.13.8.4]

Public Input No. 435-NFPA 72-2016 [Section No. 24.3.13.8.1]

Public Input No. 437-NFPA 72-2016 [Section No. 24.3.13.8.2]

Public Input No. 438-NFPA 72-2016 [Section No. 24.3.13.8.3]

Public Input No. 439-NFPA 72-2016 [Section No. 24.3.13.8.4]

Public Input No. 659-NFPA 72-2016 [Section No. 24.3.13.8.3]

Public Input No. 658-NFPA 72-2016 [Section No. 24.3.13.8.4]

Public Input No. 670-NFPA 72-2016 [Sections A.24.3.13.8.1, A.24.3.13.8.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

243 of 496 10/20/2016 11:03 AM

Page 244: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 524-NFPA 72-2016 [ Section No. 24.3.13.9.1 ]

24.3.14.9.1

Area of refuge wired emergency communications systems that are installed where the building has lessthan 2-hour fire-rated construction shall have a pathway survivability of Level 1, 2, or Level 3.

Exception: Level 1 shall be permitted where the building is less than 2-hour fire-rated construction.

24.3.14.9.2

Area of refuge wired emergency communication systems that are installed where the building has2-hour fire-rated construction or greater shall have a pathway survivability of Level 2 or 3.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 22:22:54 EDT 2016

Committee Statement

CommitteeStatement:

This revision is made based on the proposal in Public Input 210 to remove all exceptions fromthe document to comply with the Manual of Style.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

244 of 496 10/20/2016 11:03 AM

Page 245: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 513-NFPA 72-2016 [ Section No. 24.4.4.2 ]

24.4.4.2*

Except as specified in 24.4.4.3, in occupancies where sleeping accommodations are provided and thevoice message is intended to communicate information to those who could be asleep, a low frequencytone that complies with 18.4.6 18.4.5 shall be used.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 16:03:41 EDT 2016

Committee Statement

Committee Statement: This is an editorial revision to maintain consistency.

Response Message:

Public Input No. 636-NFPA 72-2016 [Section No. 24.4.4.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

245 of 496 10/20/2016 11:03 AM

Page 246: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 514-NFPA 72-2016 [ Section No. 24.4.4.3 ]

24.4.4.3*

In areas where sleeping accommodation are provided, but the voice communication system is used tocommunicate to occupants who are awake, the low frequency tone shall not be required.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 16:05:10 EDT 2016

Committee Statement

Committee Statement: This is an editorial revision to maintain consistency.

Response Message:

Public Input No. 637-NFPA 72-2016 [Section No. 24.4.4.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

246 of 496 10/20/2016 11:03 AM

Page 247: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 516-NFPA 72-2016 [ Section No. 24.4.8.3 [Excluding any

Sub-Sections] ]

Under a fire condition, where Where the system is used to transmit relocation instructions or other fireemergency non-evacuation messages, a 1-second to 3-second alert tone followed by a message (ormessages where multi-channel capability is used) shall be provided.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 16:09:03 EDT 2016

Committee Statement

Committee Statement: This revision is made to coordinate with the revision made to 24.4.8.4.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

247 of 496 10/20/2016 11:03 AM

Page 248: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 501-NFPA 72-2016 [ Section No. 24.4.8.3.1 ]

24.4.8.3.1

The sequence [the alert tone followed by the message(s)] shall be repeated at least three times to informand direct occupants in the signaling zone where the alarm initiation originated, as well as other signalingzones in accordance with the building fire safety emergency response plan.

24.4.8.3.2

Approved alternative fire alarm notification schemes shall be permitted as long as the occupants areeffectively notified and are provided instructions in a timely and safe manner in accordance with thebuilding fire safety emergency response plan.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 11:15:56 EDT 2016

Committee Statement

CommitteeStatement:

For consistency, the Technical Committee changes building fire safety plan to emergency responseplan. Emergency response plan is a defined term in chapter 3 and in NFPA 1600. Emergencyoperations plan is not currently used in NFPA 72. The Technical Committee recommends to theCorrelating Committee that an inter-committee task group be formed to look at this issue further.

ResponseMessage:

Public Input No. 509-NFPA 72-2016 [Sections 24.4.8.3.1, 24.4.8.3.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

248 of 496 10/20/2016 11:03 AM

Page 249: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 515-NFPA 72-2016 [ New Section after 24.4.8.3.2 ]

24.4.8.4

Where the system is used to transmit partial evacuation instructions, the alert tone specified in 24.4.2.1followed by a message (or messages where multi-channel capability is used) shall be provided.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 16:08:00 EDT 2016

Committee Statement

Committee Statement: This revision provides alert tones for partial evacuation.

Response Message:

Public Input No. 778-NFPA 72-2016 [New Section after 24.4.8.3.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

249 of 496 10/20/2016 11:03 AM

Page 250: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 517-NFPA 72-2016 [ Section No. 24.4.8.4 [Excluding any

Sub-Sections] ]

Where provided, loudspeakers in each enclosed stairway, each exit passageway, each occupantevacuation elevator lobby, and each group of elevator cars within a common hoistway shall be connectedto separate notification zones for manual paging only.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 16:11:57 EDT 2016

Committee Statement

CommitteeStatement:

This change brings this section in line with the requirements for OEE and OEO in both NFPA72 and building codes.

ResponseMessage:

Public Input No. 776-NFPA 72-2016 [Section No. 24.4.8.4 [Excluding any Sub-Sections]]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

250 of 496 10/20/2016 11:03 AM

Page 251: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 518-NFPA 72-2016 [ Section No. 24.4.8.4.1 ]

24.4.8.5.1

The evacuation signal specified in 18.4.2 shall not operate in elevator cars, exit stair enclosures, and exitpassageways.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 16:12:54 EDT 2016

Committee Statement

Committee Statement: This revision clarifies the "evacuation signal" mentioned in this section.

Response Message:

Public Input No. 777-NFPA 72-2016 [Section No. 24.4.8.4.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

251 of 496 10/20/2016 11:03 AM

Page 252: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 519-NFPA 72-2016 [ Sections 24.5.16.2, 24.5.16.3 ]

24.5.16.2

The visible notification required by 24.5.16.1 shall be accomplished using strobes visible notificationappliance s .

24.5.16.3

In addition to the strobes visible notification appliances required by 24.5.16.1, textual, graphic, or videodisplays shall be permitted.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 17:25:16 EDT 2016

Committee Statement

CommitteeStatement:

For uniformity throughout the document, the term “strobe” is replaced with “visible notificationappliance”. Further it is understood that SIG-NAS is reviewing the terms “visual” and “visible” andSIG-ECS requests the Correlating Committee to review and take appropriate actions.

ResponseMessage:

Public Input No. 268-NFPA 72-2016 [Section No. 24.5.16.2]

Public Input No. 269-NFPA 72-2016 [Section No. 24.5.16.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

252 of 496 10/20/2016 11:03 AM

Page 253: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 521-NFPA 72-2016 [ Section No. 24.5.17 ]

24.5.17 Visible Appliances.

24.5.17.1

Where strobes visible notification appliances are used as visible appliances , they shall meet therequirements of 24.5.17.2 through 24.5.17.10.

24.5.17.2

Visible notification appliances shall be of a sufficient quantity and intensity and located so as to meet theintent of the design and be in compliance with Section 18.5.

24.5.17.3

Strobes Visible notification appliances used in combination systems where the same strobe visiblenotification appliance is used for both mass notification and fire notification shall comply with thefollowing:

(1) Be clear or nominal white, meeting the listing requirements of ANSI/UL 1971, Standard for SignalingDevices for the Hearing Impaired

(2) Have no marking or be marked with the word “ALERT” stamped or imprinted on the appliance

(3) Be visible to the public

24.5.17.4

In situations where existing notification appliances previously used exclusively for fire alarm applications,and are marked with the word “FIRE,” and are to be used for other emergency notification purposes, fieldmodification to the marking shall be permitted, provided that it is accomplished by one of the followingmethods:

(1) Replacement of the manufacturer’s approved escutcheon or trim plate

(2) Covering of, or removal of, the word “FIRE” using a manufacturer's approved method

(3) Installation of a permanent sign directly adjacent or below the notification appliance indicating that it ismultipurpose and will operate for fire and other emergency conditions

24.5.17.5

Strobes Visible notification appliances with colored lenses shall be marked with the listed effectiveintensity using the lens color installed.

24.5.17.6

The spacing of colored strobes visible notification appliances shall be in accordance with public modespacing requirements of Section 18.5 using the effective intensity as the basis for spacing.

24.5.17.7

Where strobes visible notification appliances are used solely for mass notification, the word “ALERT” shallbe stamped or imprinted on the appliance and be visible to the public.

24.5.17.8

Where colored strobes visible notification appliances are used solely for mass notification, they shall belisted to an applicable standard such as ANSI/UL 1638, Visual Signaling Appliances — Private ModeEmergency and General Utility Signaling.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

253 of 496 10/20/2016 11:03 AM

Page 254: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

24.5.17.9

Strobe appliances listed Visible notification appliances with nominal white light output that are listed toANSI/UL 1971, Standard for Signaling Devices for the Hearing Impaired , and visible notificationappliances with other than nominal white light output that are listed to ANSI/UL 1638, Visual SignalingAppliances—Private Mode Emergency and General Utility Signaling , shall be considered as meeting theintent of this Code. Standard for Signaling Devices for the Hearing Impaired , shall be considered asmeeting the intent of this Code.

Exception: Color lens strobes shall meet the requirements of 24.5.17.8 .

24.5.17.10

Strobes Visible notification appliances used for mass notification shall meet the synchronizationrequirements of Section 18.5.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 17:30:29 EDT 2016

Committee Statement

CommitteeStatement:

For uniformity throughout the document, the term “strobe” is replaced with “visible notificationappliance”. Further it is understood that SIG-NAS is reviewing the terms “visual” and “visible” andSIG-ECS requests the Correlating Committee to review and take appropriate actions. Section24.5.17.9 is further revised based on the proposal in Public Input 210 to remove all exceptions fromthe document to comply with the Manual of Style.

ResponseMessage:

Public Input No. 270-NFPA 72-2016 [Section No. 24.5.17.1]

Public Input No. 271-NFPA 72-2016 [Section No. 24.5.17.3]

Public Input No. 272-NFPA 72-2016 [Section No. 24.5.17.5]

Public Input No. 273-NFPA 72-2016 [Section No. 24.5.17.6]

Public Input No. 274-NFPA 72-2016 [Section No. 24.5.17.7]

Public Input No. 275-NFPA 72-2016 [Section No. 24.5.17.8]

Public Input No. 276-NFPA 72-2016 [Section No. 24.5.17.9]

Public Input No. 277-NFPA 72-2016 [Section No. 24.5.17.10]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

254 of 496 10/20/2016 11:03 AM

Page 255: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 543-NFPA 72-2016 [ Section No. 24.5.24.2 ]

24.5.24.2*

Evaluation documentation in accordance with 7.3.9 shall be provided by the emergency communicationssystem designer attesting to the fact that the public address system has been evaluated and meets theperformance requirements needs of Chapter 24 and the emergency response plan and, where notcompliant with the prescriptive requirements of Chapter 24 , shall provide equivalent systemperformance requirements.

Supplemental Information

File Name Description

A.24.5.24.2.docx New annex material added in FR

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jul 29 11:55:03 EDT 2016

Committee Statement

CommitteeStatement:

This revision clarifies that PA systems will not meet the performance requirements of Chapter 24, ascurrently stated in 24.5.24.2. The revised language states that deficiencies to the performancerequirements of Chapter 24 must be documented and equivalency be provided as permitted anddefined by 1.5. The new annex material provides examples of Public Address Systems that can beproperly evaluated for equivalency requirements to Chapter 24 through the use of a risk analysis.

ResponseMessage:

Public Input No. 427-NFPA 72-2016 [Section No. 24.5.24.2]

Public Input No. 426-NFPA 72-2016 [Section No. 24.5.24.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

255 of 496 10/20/2016 11:03 AM

Page 256: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 520-NFPA 72-2016 [ Section No. 24.6.7.2 ]

24.6.7.2*

HPSAs shall be installed at a height and orientation to prevent hearing damage to anyone in theimmediate vicinity of the speakers appliances .

Supplemental Information

File Name Description

72_FR-520_A.24.6.7.2_ECS.docx

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 17:27:40 EDT 2016

Committee Statement

CommitteeStatement:

As part of the Correlating Committee Task Group the term “speaker” was reviewed throughoutthe document. "Appliance” is the appropriate term. The revision made to the annex material is tomaintain consistency with other revisions.

ResponseMessage:

Public Input No. 194-NFPA 72-2016 [Section No. 24.6.7.2]

Public Input No. 232-NFPA 72-2016 [Section No. A.24.6.7.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

256 of 496 10/20/2016 11:03 AM

Page 257: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 512-NFPA 72-2016 [ Section No. 24.9.1.2 ]

24.9.1.2 Approval and Permit.

Plans shall be submitted for approval prior to installation. At the conclusion of successful acceptancetesting, a renewable permit shall be issued for the public safety radio enhancement system whererequired by the authority having jurisdiction.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 14:07:34 EDT 2016

Committee Statement

CommitteeStatement:

NFPA 1221 has jurisdiction over two-way radio communication enhancement systems andcurrently contains the appropriate approval language.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

257 of 496 10/20/2016 11:03 AM

Page 258: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4008-NFPA 72-2016 [ Sections 26.2.1.3, 26.2.1.4 ]

26.2.1.3

Fire alarm signals received at the supervising station by a zone or zones shall be retransmitted by zoneto the communications center. by one of the following methods:

(1) Signals that are identified by zone at the supervising station shall be retransmitted by zone to thecommunications center.

(2) Signals that are identified as an individual point or points at the supervising station shall beretransmitted by point or points to the communications center.

(3)

26.2.1.4

Fire alarm signals received at the supervising station that are identified as an individual point or pointsshall be retransmitted by point identifier to the communications center.

Supplemental Information

File Name Description

26.2.1.3_FR_4008_BC.docx Revisions. For staff use

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 13:22:52 EDT 2016

Committee Statement

CommitteeStatement:

The revised text clarifies the Technical Committee's intent to permit non-specific signalprocessing (events).

Response Message:

Public Input No. 532-NFPA 72-2016 [Section No. 26.2.1]

* Signals that are received at the supervising station as events shall be retransmitted by event tothe communications center.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

258 of 496 10/20/2016 11:03 AM

Page 259: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4006-NFPA 72-2016 [ Section No. 26.2.2.1 ]

26.2.2.1

For applications other than those addressed under the scope of 29.9.9.2, supervising station personnelshall attempt to verify alarm signals prior to reporting them to the communications center where all thefollowing conditions exist:

(1)

(2) Documentation of the requirement for alarm signal verification is provided by the responsible firedepartment to the supervising station and the protected premises.

(3) If the requirement for verification changes, the responsible fire department shall notify the supervisingstation and the protected premises.

(4)

(5) Verification of a true fire is received from anyone on premises or verification of an unwanted alarmsignal is received only from a pre-assigned list of authorized personnel within the protected premises.

(6)

(7)

(8)

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 12:19:36 EDT 2016

Committee Statement

CommitteeStatement:

As part of the Correlating Committee Task Group on terms, the term "communication(s)” wasreviewed throughout the entire document for proper use regarding reference to singular and pluraluse. The term should be plural use in this context.

ResponseMessage:

Public Input No. 447-NFPA 72-2016 [Section No. 26.2.2.1]

* Alarm signal verification is required by the responsible fire department for a specific protectedpremises.

* The verification process does not take longer than 90 seconds from the time the alarm signal isreceived at the supervising station until the time that retransmission of the verified alarm signal isinitiated.

* Verified alarm signals are immediately retransmitted to the communications center and includeinformation that the signal was verified at the protected premises to be an emergency.

* Alarm signals where verification is not conclusive are immediately retransmitted to thecommunications center.

* Alarm signals that are verified as unwanted alarms shall be reported to the responsible firedepartment in a manner and at a frequency specified by the responsible fire department.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

259 of 496 10/20/2016 11:03 AM

Page 260: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4009-NFPA 72-2016 [ New Section after 26.2.3 ]

26.2.4 Carbon Monoxide Signal Disposition.

26.2.4.1 Carbon Monoxide Alarm Signal Disposition.

26.2.4.1.1

A carbon monoxide alarm signal shall take precedence over supervisory or trouble signals.

26.2.4.1.2

The actuation of a carbon monoxide detector or system shall be distinctively indicated as a carbonmonoxide alarm signal.

26.2.4.1.3*

Servicing of a system in alarm that cannot be reset shall be in accordance with Chapter 14 and shalloccur within 4 hours of the carbon monoxide alarm signal.

26.2.4.1.4*

Upon receipt of a carbon monoxide alarm signal, supervising station personnel shall perform thefollowing actions in the order listed:

(1) Where required by the emergency response agency, immediately retransmit indication of thecarbon monoxide alarm signal to the communications center.

(2) Contact the responsible party(s) in accordance with the notification plan.

26.2.4.1.5*

Where a carbon monoxide alarm signal is transmitted directly to a communications center,communications center personnel shall perform the following actions in the order listed:

(1) Follow standard operating procedures.

(2) Contact the responsible party(s) in accordance with the notification plan.

26.2.4.2 Carbon Monoxide Trouble Signal Disposition.

26.2.4.2.1

Upon receipt of a carbon monoxide trouble signal, the responsible party(s) shall be notified.

26.2.4.2.2

Servicing of a system in trouble shall be in accordance with Chapter 14 and shall occur within 4 hoursof the trouble indication.

26.2.4.2.3

Carbon monoxide end-of-life signals, if provided, shall be treated as trouble signals.

Supplemental Information

File Name Description

26.2.4_FR_4009_BC.docx New text. Includes Annex

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

260 of 496 10/20/2016 11:03 AM

Page 261: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

State:

Zip:

Submittal Date: Wed Jul 27 14:10:54 EDT 2016

Committee Statement

CommitteeStatement:

CO alarm and trouble signals need to be treated differently than fire alarm and trouble signals.Requirements for handling of CO signals are relocated from the 2015 edition of NFPA 720unchanged into new sections in this chapter.

26.2.4.2.3 was added to provide guidance on end-of-life signaling.

ResponseMessage:

Public Input No. 756-NFPA 72-2016 [New Section after 26.4.6.6.4]

Public Input No. 754-NFPA 72-2016 [New Section after 26.3.8.4]

Public Input No. 218-NFPA 72-2016 [New Section after 26.2.1.4]

Public Input No. 220-NFPA 72-2016 [Section No. 26.2.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

261 of 496 10/20/2016 11:03 AM

Page 262: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4012-NFPA 72-2016 [ Section No. 26.3.4.1 ]

26.3.4.1*

Documentation indicating Code compliance of the alarm system shall be issued by the organization thathas listed the prime contractor.

Supplemental Information

File Name Description

A.26.3.4.1_FR_4012_BC.docx New annex material.

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 16:07:50 EDT 2016

Committee Statement

CommitteeStatement:

Add new annex material.

The new text clarifies that this section does not cover the Chapter 7 documentation, which issometimes misunderstood by code users.

ResponseMessage:

Public Input No. 604-NFPA 72-2016 [New Section after A.26.3.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

262 of 496 10/20/2016 11:03 AM

Page 263: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4013-NFPA 72-2016 [ Section No. 26.3.5.2.2 ]

26.3.5.2.2

The subsidiary facility shall be inspected at least monthly by central station personnel for the purpose ofverifying the operation and condition of all supervised equipment, all telephones, all battery conditions,and all fluid levels of batteries and generators energy storage systems, batteries, and generators, inaccordance with the manufacturer's instructions .

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 16:26:51 EDT 2016

Committee Statement

CommitteeStatement:

The revision adds inspection requirements for energy storage systems in a subsidiary station. Theinspection includes the physical condition of the equipment, as well as the operation. Details ofthese inspections are outside the scope of NFPA 72, so a reference to the manufacturer'sinstructions was added.

ResponseMessage:

Public Input No. 545-NFPA 72-2016 [Section No. 26.3.5.2.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

263 of 496 10/20/2016 11:03 AM

Page 264: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4014-NFPA 72-2016 [ Section No. 26.3.5.2.6 ]

26.3.5.2.6

When the communications channel between the subsidiary station and the supervising station fails, thecommunications shall be switched to an alternate path. Public The public switched telephone network ora managed facilities-based voice network shall be used only as an alternate path.

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 17:07:38 EDT 2016

Committee Statement

CommitteeStatement:

Adding the MFVN, along with the PSTN, clarifies equivalency between the two, in anticipationof the discontinuance of the PSTN.

ResponseMessage:

Public Input No. 593-NFPA 72-2016 [Section No. 26.3.5.2.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

264 of 496 10/20/2016 11:03 AM

Page 265: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4020-NFPA 72-2016 [ Section No. 26.3.8 ]

26.3.8 Procedures.

26.3.8.1

The procedural requirements outlined in Section 26.2 shall be followed.

26.3.8.2

The additional procedural requirements outlined in 26.3.8 shall also be followed.

26.3.8.3 Disposition of Signals.

26.3.8.3.1 Alarm Signals.

26.3.8.3.1.1

The central station shall perform the following actions:

(1)

(2) Dispatch a runner or technician to the protected premises to arrive within 2 hours after receipt of asignal if equipment needs to be manually reset by the prime contractor. Except where prohibited bythe authority having jurisdiction, the runner or technician shall be permitted to be recalled prior toarrival at the premises if a qualified representative of the subscriber at the premises can provide thenecessary resetting of the equipment and is able to place the system back in operating condition.

(3) Immediately notify the subscriber.

(4) Provide notice to the subscriber or authority having jurisdiction, or both, if required.

Exception: If the alarm signal results from a prearranged test, the actions specified by26.3.8.3.1.1(1)26.3.9.1.1 and 26.3.8.3.1.1(3) shall not be required.

26.3.8.3.2 Guard’s Tour Supervisory Signal.

26.3.8.3.2.1

Upon failure to receive a guard’s tour supervisory signal within a 15-minute maximum grace period, thecentral station shall perform the following actions:

(1) Communicate without unreasonable delay with personnel at the protected premises

(2) Dispatch a runner to the protected premises to arrive within 30 minutes of the delinquency ifcommunications cannot be established

(3) Report all delinquencies to the subscriber or authority having jurisdiction, or both, if required

26.3.8.3.2.2

Failure of the guard to follow a prescribed route in transmitting signals shall be handled as a delinquency.

* Retransmit the alarm to the communications center in accordance with 26.2.1.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

265 of 496 10/20/2016 11:03 AM

Page 266: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

26.3.8.3.3* Supervisory Signals.

Upon receipt of a supervisory signal that is not prearranged, the central station shall perform the followingactions:

(1)

(2) Dispatch a runner or maintenance person to arrive within 2 hours to investigate unless thesupervisory signal is cleared in accordance with a scheduled procedure determined by26.3.8.3.3(1)26.3.9.3

(3) Notify the authority having jurisdiction and the subscriber when sprinkler systems or other firesuppression systems or equipment have been wholly or partially out of service for 8 hours

(4) When service has been restored, provide notice to the subscriber and the authority having jurisdictionof the nature of the signal, the time of occurrence, and the restoration of service when equipment hasbeen out of service for 8 hours or more

26.3.8.3.4 Trouble Signals.

Upon receipt of trouble signals or other signals pertaining solely to matters of equipment maintenance ofthe alarm systems, the central station shall perform the following actions:

(1)

(2) Dispatch personnel to arrive within 4 hours to initiate maintenance, if necessary

(3) When the interruption is more than 8 hours, provide notice to the subscriber and the fire department ifso required by the authority having jurisdiction as to the nature of the interruption, the time ofoccurrence, and the restoration of service

26.3.8.3.5 Test Signals.

26.3.8.3.5.1

All test signals received shall be recorded to indicate date, time, and type.

26.3.8.3.5.2

Test signals initiated by the subscriber, including those for the benefit of an authority having jurisdiction,shall be acknowledged by central station personnel whenever the subscriber or authority inquires.

26.3.8.3.5.3*

Any test signal not received by the central station shall be investigated immediately, and action shall betaken to reestablish system integrity.

26.3.8.3.5.4

The central station shall dispatch personnel to arrive within 2 hours if protected premises equipmentneeds to be manually reset after testing.

26.3.8.3.5.5

The prime contractor shall provide each of its representatives and each alarm system user with a uniquepersonal identification code.

26.3.8.3.5.6

In order to authorize the placing of an alarm system into test status, a representative of the primecontractor or an alarm system user shall first provide the central station with his or her personalidentification code.

Supplemental Information

File Name Description

26.3.8_FR_4020_BC.docx Revisions. Includes Annex

Submitter Information Verification

* Communicate immediately with the persons designated by the subscriber and notify the firedepartment, law enforcement agency, or both when required by the authority having jurisdiction

* If a received trouble signal does not restore within 15 minutes, communicate immediately withpersons designated by the subscriber

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

266 of 496 10/20/2016 11:03 AM

Page 267: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 19:20:12 EDT 2016

Committee Statement

CommitteeStatement:

This revision is the result of a task group which was charged with making changes to the documentto align the organization for central station service, proprietary station, and remote station. Thesechanges provide clarity and consistency of organizational formatting between these sections.

26.3.8.4 - Immediate communication on receipt of a trouble signal creates unnecessary nuisancenotifications of the owner or owner's representative. Some signals, such as a communication pathfailure on IP, will self restore and do not require intervention by the owner or owner's representative.Nuisance notifications of the owner or owners representative could encourage the owner todisregard notifications. Annex material was added to clarify that it is not the intent to require aminimum 15-minute delay before communication is initiated.

ResponseMessage:

Public Input No. 303-NFPA 72-2016 [New Section after 26.3.7]

Public Input No. 213-NFPA 72-2016 [Section No. 26.3.8.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

267 of 496 10/20/2016 11:03 AM

Page 268: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4026-NFPA 72-2016 [ Section No. 26.4.3.5 ]

26.4.3.5

If 25 or more protected buildings or premises are connected to a subsidiary station, both of the followingshall be provided at the subsidiary station:

(1) Automatic means for receiving and recording signals under emergency staffing conditions

(2) A telephone

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 12:51:16 EDT 2016

Committee Statement

CommitteeStatement:

The term "emergency staffing conditions" is undefined and ambiguous. This changeremoves the ambiguous term.

ResponseMessage:

Public Input No. 543-NFPA 72-2016 [Section No. 26.4.3.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

268 of 496 10/20/2016 11:03 AM

Page 269: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4022-NFPA 72-2016 [ Section No. 26.4.6 ]

26.4.6 Operations.

26.4.6.1 Procedures

26.4.6.1.1

The procedural requirements outlined in Section 26.2 shall be followed.

26.4.6.1.2

The additional procedural requirements outlined in 26.4.6.1 shall also be followed.

26.4.6.1.3 Communications and Transmission Channels.

26.4.6.1.3.1

All communications and transmission channels used to receive signals between the proprietarysupervising station and the protected premises control unit shall be operated manually or automaticallyonce every 24 hours to verify operation.

26.4.6.1.3.2

If a communications or transmission channel fails to operate, the operator shall immediately notify theperson(s) identified by the owner or authority having jurisdiction.

26.4.6.1.3.3* Coded Retransmission.

Retransmission by coded signals shall be confirmed by two-way voice communications indicating thenature of the alarm.

26.4.6.1.4 Operator Controls.

26.4.6.1.4.1

All operator controls at the proprietary supervising station(s) designated by the authority having jurisdictionshall be operated at each change of shift.

26.4.6.1.4.2

If operator controls fail, the operator shall immediately notify the person(s) identified by the owner orauthority having jurisdiction.

26.4.6.1.5 Retransmission.

Indication of a fire shall be promptly immediately retransmitted to the communications center or otherlocations accepted by the authority having jurisdiction, indicating the building or group of buildings fromwhich the alarm has been received.

Detail FR-5048

26.4.6.4* Retransmission Means.

The means of retransmission shall be accepted by the authority having jurisdiction and shall be inaccordance with 26.3.6.6 , 26.5.4.4 , or Chapter 27 .

Exception: Secondary power supply capacity shall be as required in Chapter 10 .

26.4.6.1.6 Dispositions of Signals.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

269 of 496 10/20/2016 11:03 AM

Page 270: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

26.4.6.1.6.1 Alarms.

Upon receipt of an alarm signal, the proprietary supervising station operator shall initiate action to performthe following:

(1) Notify the communications center, the emergency response team, and such other parties as theauthority having jurisdiction requires in accordance with 26.2.1

(2) Dispatch a runner or technician to the alarm location to arrive within 2 hours after receipt of a signal

(3) Restore the system as soon as possible after disposition of the cause of the alarm signal

26.4.6.1.6.2 Guard’s Tour Supervisory Signal.

If a guard’s tour supervisory signal is not received from a guard within a 15-minute maximum grace period,or if a guard fails to follow a prescribed route in transmitting the signals (where a prescribed route hasbeen established), the proprietary supervising station operator shall initiate action to perform the following:

(1) Communicate at once with the protected areas or premises by telephone, radio, calling back over thesystem circuit, or other means accepted by the authority having jurisdiction

(2) Dispatch a runner to arrive within 30 minutes to investigate the delinquency if communications withthe guard cannot be promptly immediately established

26.4.6.1.6.3 Supervisory Signals.

Upon receipt of sprinkler system and other supervisory signals, the proprietary supervising stationoperator shall initiate action to perform the following, if required:

(1) Communicate immediately with the designated person(s) to ascertain the reason for the signal

(2) Dispatch personnel to arrive within 2 hours to investigate, unless supervisory conditions arepromptly immediately restored

(3) Notify the fire department if required by the authority having jurisdiction

(4) Notify the authority having jurisdiction when sprinkler systems are wholly or partially out of service for8 hours or more

(5)

26.4.6.1.6.4 Trouble Signals.

Upon receipt of trouble signals or other signals pertaining solely to matters of equipment maintenance ofthe alarm system, the proprietary supervising station operator shall initiate action to perform the following,if required:

(1) Communicate immediately with the designated person(s) to ascertain reason for the signal

(2) Dispatch personnel to arrive within 4 hours to initiate maintenance, if necessary

(3) Notify the fire department if required by the authority having jurisdiction

(4) Notify the authority having jurisdiction when interruption of service exists for 4 hours or more

(5) When equipment has been out of service for 8 hours or more, provide written notice to the authorityhaving jurisdiction as to the nature of the signal, time of occurrence, and restoration of service

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 00:04:03 EDT 2016

* Provide written notice to the authority having jurisdiction as to the nature of the signal, time ofoccurrence, and restoration of service when equipment has been out of service for 8 hours or more

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

270 of 496 10/20/2016 11:03 AM

Page 271: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Committee Statement

CommitteeStatement:

This revision is the result of a task group which was charged with making changes to thedocument to align the organization for central station service, proprietary station, and remotestation. These changes provide clarity and consistency of organizational formatting between thesesections.

In 26.4.6.4 (moved to 26.4.3.6), the exception was deleted because it is no longer required due tocurrent practices and technology.

In A.26.4.6.4 (moved to A.26.4.3.6), the metric conversion for 50 ft was updated to 15.2 m forconsistency with the rest of the document.

The term "promptly" was replaced with "immediately" throughout the section for consistency.

ResponseMessage:

Public Input No. 307-NFPA 72-2016 [Section No. 26.4.6]

Public Input No. 312-NFPA 72-2016 [New Section after A.26.4.4.3]

Public Input No. 313-NFPA 72-2016 [Section No. A.26.4.6.5]

Public Input No. 314-NFPA 72-2016 [New Section after 26.4.6.1.2]

Public Input No. 315-NFPA 72-2016 [Section No. A.26.4.6.5]

Public Input No. 162-NFPA 72-2016 [Section No. 26.4.6.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

271 of 496 10/20/2016 11:03 AM

Page 272: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4015-NFPA 72-2016 [ Section No. 26.5.4.4 ]

26.5.4.4

Retransmission of an alarm signal, if required, shall be by one of the following methods, which appear indescending order of preference as follows:

(1) A dedicated circuit that is independent of any switched telephone network. This circuit shall bepermitted to be used for voice or data communications.

(2) A one-way (outgoing only) telephone at the remote supervising station that utilizes the public-switched telephone network or a managed facilities-based voice network . This telephone shall beused primarily for voice transmission of alarms to a telephone at the communications center thatcannot be used for outgoing calls.

(3) A private radio system using the fire department frequency, where permitted by the fire department.

(4) Other methods accepted by the authority having jurisdiction.

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 17:18:00 EDT 2016

Committee Statement

CommitteeStatement:

Adding the MFVN, along with the PSTN, clarifies equivalency between the two, in anticipationof the discontinuance of the PSTN.

ResponseMessage:

Public Input No. 594-NFPA 72-2016 [Section No. 26.5.4.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

272 of 496 10/20/2016 11:03 AM

Page 273: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4024-NFPA 72-2016 [ Section No. 26.5.6 ]

26.5.6 Disposition of Signals Procedures .

26.5.6.1

If the remote supervising station is at a location other than the communications center, alarm signals shallbe retransmitted to the communications center in accordance with 26.2.1 The procedural requirementsoutlined in Section 26.2 shall be followed .

26.5.6.2

Upon receipt of an alarm, supervisory, or trouble signal by the remote supervising station, the operator onduty shall be responsible for immediately notifying the owner or the owner’s designated representativeand, where required, the authority having jurisdiction. The additional procedural requirements outlined in26.5.6 shall also be followed.

26.5.6.3 Disposition of Signals.

26.5.6.3.1 Alarm Signals.

The remote station shall perform the following actions:

(1) If the remote station is at a location other than the communications center, retransmit alarm signalsto the communications center in accordance with 26.2.1 .

(2) Immediately notify the owner or the owner's designated representative.

26.5.6.3.2 Supervisory Signals.

Upon receipt of a supervisory signal that is not prearranged, the remote station shall perform thefollowing actions:

(1) Immediately notify the owner or the owner’s designated representative.

(2) Where required, notify the authority having jurisdiction.

26.5.6.3.3 Trouble Signals.

26.5.6.3.3.1

Upon receipt of a trouble signal that is not prearranged, the remote station shall perform the followingaction:

(1) Immediately notify the owner or the owner's designated representative.

(2) Where required, notify the authority having jurisdiction.

26.5.6.3.3.2

For trouble signals, the remote station operator shall be permitted to delay transmission for 15 minutesto allow for a status change in the signal that would resolve the trouble signal.

26.5.6.3.3.3

If a trouble restoral signal is received within 15 minutes, the operator shall not be required to notify theowner or the owner's designated representative or the authority having jurisdiction.

Supplemental Information

File Name Description

26.5.6_FR_4024_BC.txt Final revised text. For staff use

Submitter Information Verification

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

273 of 496 10/20/2016 11:03 AM

Page 274: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 00:38:28 EDT 2016

Committee Statement

CommitteeStatement:

This revision is the result of a task group which was charged with making changes to the documentto align the organization for central station service, proprietary station, and remote station. Thesechanges provide clarity and consistency of organizational formatting between these sections.

26.5.6.3.2.1 and 26.5.6.3.2.2 - Immediate communication on receipt of a trouble signal createsunnecessary nuisance notifications of the owner or owner's representative. Some signals, such as acommunication path failure on IP, will self restore and do not require intervention by the owner orowner's representative. Nuisance notifications of the owner or owners representative couldencourage the owner to disregard notifications. Supervisory signals were not included in thisallowance because they are positive signals that indicate important changes of status on monitoredsystems.

ResponseMessage:

Public Input No. 309-NFPA 72-2016 [New Section after 26.5.5.2]

Public Input No. 214-NFPA 72-2016 [Section No. 26.5.6]

Public Input No. 212-NFPA 72-2016 [New Section after A.26.5.3.2]

Public Input No. 211-NFPA 72-2016 [New Section after 26.5.6.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

274 of 496 10/20/2016 11:03 AM

Page 275: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4028-NFPA 72-2016 [ Section No. 26.6.3.13.1 ]

26.6.3.13.1* Premises Equipment.

The secondary power capacity for all transmitters and shared equipment necessary for the transmission ofalarm, supervisory, trouble, and other signals located at the protected premises shall be a minimum of24 hours or as permitted by 10.6.7.3.1(2)10.6.7.3.1(2)10.6.7.3.1 .

Exception No. 1: Secondary power capacity for shared equipment shall be permitted to have a capacityof 8 hours where acceptable to the authority having jurisdiction and where a risk analysis is performed toensure acceptable availability is provided.

Exception No. 2: Secondary power capacity for shared and premises equipment used in additionalcommunications paths shall not be required where the first communications path meets theperformance requirements of 26.6.3.3

Supplemental Information

File Name Description

26.6.3.13.1_FR_4028_BC.docx Revisions. Includes Annex

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 16:38:01 EDT 2016

Committee Statement

CommitteeStatement:

If the subscriber elects to install a secondary path, then placing a 24-hour backup requirement isan unnecessary burden on the secondary path when single path communication is permitted bycode.

ResponseMessage:

Public Input No. 556-NFPA 72-2016 [Section No. 26.6.3.13]

Public Input No. 487-NFPA 72-2016 [Section No. 26.6.3.13]

Public Input No. 557-NFPA 72-2016 [New Section after A.26.6.3.13]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

275 of 496 10/20/2016 11:03 AM

Page 276: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4016-NFPA 72-2016 [ Section No. 26.6.4.1.1 ]

26.6.4.1.1* Public Switched Telephone Network.

A DACT shall be connected to the public switched telephone network or a managed facilities-based voicenetwork upstream of any private telephone system at the protected premises.

(A)

The connections to the public switched telephone network or a managed facilities-based voice networkshall be under the control of the subscriber for whom service is being provided by the supervising stationalarm system.

(B)

Special attention shall be required to ensure that this connection is made only to a loop start telephonecircuit and not to a ground start telephone circuit.

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 17:21:05 EDT 2016

Committee Statement

CommitteeStatement:

Adding the MFVN, along with the PSTN, clarifies equivalency between the two, in anticipationof the discontinuance of the PSTN.

ResponseMessage:

Public Input No. 595-NFPA 72-2016 [Section No. 26.6.4.1.1 [Excluding any Sub-Sections]]

Public Input No. 598-NFPA 72-2016 [Section No. 26.6.4.1.1(A)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

276 of 496 10/20/2016 11:03 AM

Page 277: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4017-NFPA 72-2016 [ Section No. 26.6.4.1.5 ]

26.6.4.1.5 DACT Transmission Means.

The following requirements shall apply to all DACTs:

(1) A DACT shall be connected to two separate means of transmission at the protected premises so thata single point of failure on one means of transmission shall not affect the second means oftransmission.

(2) The DACT shall be capable of selecting the operable means of transmission in the event of failure ofthe other means.

(3) The primary means of transmission shall be a telephone line (number) connected to the publicswitched network or a managed facilities-based voice network .

(4)

(5) Each DACT shall be programmed to call a second receiver when the signal transmission sequence tothe first called line (number) is unsuccessful.

(6) Each transmission means shall automatically initiate and complete a test signal transmissionsequence to its associated receiver at least once every 6 hours. A successful signal transmissionsequence of any other type, within the same 6-hour period, shall fulfill the requirement to verify theintegrity of the reporting system, provided that signal processing is automated so that 6-hourdelinquencies are individually acknowledged by supervising station personnel.

(7)

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 17:25:30 EDT 2016

Committee Statement

CommitteeStatement:

Adding the MFVN, along with the PSTN, clarifies equivalency between the two, in anticipationof the discontinuance of the PSTN.

ResponseMessage:

Public Input No. 600-NFPA 72-2016 [Section No. 26.6.4.1.5]

* The first transmission attempt shall utilize the primary means of transmission.

* If a DACT is programmed to call a telephone line (number) that is call forwarded to the line (number)of the DACR, a means shall be implemented to verify the integrity of the call forwarding feature every4 hours.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

277 of 496 10/20/2016 11:03 AM

Page 278: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4025-NFPA 72-2016 [ Section No. 26.6.5.2.6(A) ]

(A)

Allowable loading capacities shall be in accordance with Table 26.6.5.2.6(A), except as modified by thefollowing:

(1) Each guard’s tour transmitter shall reduce the allowable RATs by 15.

Each two-way protected premises radio transmitter shall reduce the allowable RATs by two.

(2) Each supervised burglar alarm (open/close) or each suppressed guard’s tour transmitter shall reducethe allowable RATs by five.

Table 26.6.5.2.6(A) Loading Capacities of One-Way Radio Alarm Systems

Radio Alarm Repeater Station Receiver (RARSR)

System Type

Type6

Type7

Maximum number of fire alarm service initiating device circuits per RARSR 5,120 5,120

Maximum number of RATs for fire 512 512

Maximum number of all types of initiating device circuits per RARSR in any combination* 10,240 10,240

Maximum number of RATs for all types of fire alarm service per RARSR in anycombination*

1,024 1,024

System Units at the Supervising Station

Maximum number of all types of initiating device circuits per system unit* 10,240 10,240

Maximum number of fire-protected buildings and premises per system unit 512 512

Maximum number of fire alarm service initiating device circuits per system unit 5,120 5,120

*Includes every initiating device circuit (e.g., waterflow, fire alarm, supervisory, guard, burglary, hold-up).

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 12:12:54 EDT 2016

Committee Statement

CommitteeStatement:

List item (2) discusses the operation of a two-way RAT, which is not compatible with aone-way system, and thus does not belong in this location.

ResponseMessage:

Public Input No. 382-NFPA 72-2016 [Section No. 26.6.5.2.6(A)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

278 of 496 10/20/2016 11:03 AM

Page 279: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4029-NFPA 72-2016 [ New Section after 26.6.5.2.7 ]

26.6.5.2.8 Wireless Mesh Networks (WMN).

A wireless mesh network utilizing listed components satisfies the requirements of 26.6.5.2 .

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 17:05:39 EDT 2016

Committee Statement

CommitteeStatement:

Wireless mesh networks have long been used to satisfy the requirements of a One-Way PrivateRadio Alarm System. There are many hundreds of thousands of such units in use in commercial firesystems. UL has recognized the performance of a wireless mesh network as satisfying therequirements of 26.6.5.2. This addition makes it clear and creates an unambiguous code sectionreference point for AHJs.

ResponseMessage:

Public Input No. 473-NFPA 72-2016 [New Section after 26.6.5.2.1(C)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

279 of 496 10/20/2016 11:03 AM

Page 280: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3507-NFPA 72-2016 [ Section No. 27.1.6 ]

27.1.6

The requirements of this chapter shall not apply to Chapter 29 unless otherwise noted.

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 12:17:36 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee deletes the clause as reference to CH 29 is not included in thissection, so this would never apply.

ResponseMessage:

Public Input No. 735-NFPA 72-2016 [Section No. 27.1.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

280 of 496 10/20/2016 11:03 AM

Page 281: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3508-NFPA 72-2016 [ Section No. 27.2 ]

27.2 General Fundamentals .

27.2.1*

Public emergency alarm reporting systems shall be designed, installed, operated, and maintained inaccordance with this chapter to provide reliable transmission and receipt of alarms in a manneracceptable to the authority having jurisdiction.

27.2.2

A public emergency alarm reporting system, as described herein, shall be permitted to be used for thetransmission of other signals or calls of a public emergency nature, provided that such transmission doesnot interfere with the transmission and receipt of fire alarms.

27.2.3*

All devices shall be designed to function satisfactorily under the climatic and environmental conditions towhich they could be exposed.

27.2.3.1

All devices shall be identified as suitable for the location and conditions for which they are installed.

27.2.4

All circuits, paths, and equipment necessary for the receipt of signals from a protected premises shall bemonitored for integrity.

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 12:20:15 EDT 2016

Committee Statement

CommitteeStatement:

The term "General Fundamentals" is considered redundant. The Technical Committeedeletes the word "Fundamentals."

ResponseMessage:

Public Input No. 651-NFPA 72-2016 [Section No. 27.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

281 of 496 10/20/2016 11:03 AM

Page 282: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3510-NFPA 72-2016 [ Section No. 27.5.2.2.7 ]

27.5.2.2.7

Facilities shall be provided with a device that automatically records the date and time of receipt of eachalarm.

Exception: Only the time shall be required to be automatically recorded for voice recordings.

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 14:02:07 EDT 2016

Committee Statement

Committee Statement: The exception is removed because it referres to outdated equipment and procedures.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

282 of 496 10/20/2016 11:03 AM

Page 283: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3509-NFPA 72-2016 [ Section No. 27.5.2.8.1 ]

27.5.2.8.1

Float-charged batteries shall be of the storage type. Primary batteries (i.e., dry cells) shall not be used.

27.5.2.8.1.1

Lead Vented lead -acid batteries shall be in jars of glass or other identified or approved transparentmaterials. ;

27.5.2.8.1.2

Other types of batteries shall be in containers identified or approved for the purpose.

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 12:42:00 EDT 2016

Committee Statement

CommitteeStatement:

Change to 27.5.2.8.1 is made to clarify that the installation requirement for public alarm reportingsystem float charged batteries applies to vented lead-acid batteries, not VRLA batteries and that“approved transparent container” should be terminology used as newer technologies are more oftenused than glass jars.

This PI addresses the SIG-TMS Battery Task Group recommendations concerning the battery testmethods of Item 9 and other necessary changes within NFPA 72 in support of theserecommendations. The recommendations are made with support from the IEEE Stationary BatteryCommittee project team dedicated to this effort and are based on battery manufacturer’sspecifications, IEEE standards, and studies performed by various entities including the ElectricPower Research Institute (EPRI), North American Electric Research Corporation (NERC), andAlbercorp.

Task Group 1 - Battery Testing: Herb Hurst (Chair), Scott Carlson, Richard Carter, Lou Chavez, VicHumm, James Lugar, Stan Maciaszek

ResponseMessage:

Public Input No. 150-NFPA 72-2016 [Section No. 27.5.2.8.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

283 of 496 10/20/2016 11:03 AM

Page 284: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3525-NFPA 72-2016 [ Section No. 27.5.3.4 [Excluding any

Sub-Sections] ]

Wired or wireless alarm repeating systems used to repeat signals between a remote communicationscenter and the alarm processing equipment location shall meet the requirements of 27.5.3.4.1 through27.5.3.4.7.

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 18:16:56 EDT 2016

Committee Statement

CommitteeStatement:

As part of the Correlating Committee Task Gorup on terms, the term "communication(s)” wasreviewed throughout the entire document for proper use regarding reference to singular and pluraluse. The term should be plural use in this context.

The Technical Committee changes communication to communications for consistency and properuse.

ResponseMessage:

Public Input No. 448-NFPA 72-2016 [Section No. 27.5.3.4 [Excluding any Sub-Sections]]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

284 of 496 10/20/2016 11:03 AM

Page 285: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3526-NFPA 72-2016 [ Section No. 27.5.3.6.1 ]

27.5.3.6.1

A pathway or communications trouble condition shall be detected and annunciated at both thecommunications center and the alarm processing equipment location within 200 seconds and shall meetthe requirements of 27.5.2.4.

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 18:17:30 EDT 2016

Committee Statement

CommitteeStatement:

As part of the Correlating Committee Task Group on terms, the term "communication(s)” wasreviewed throughout the entire document for proper use regarding reference to singular and pluraluse. The term should be plural use in this context.

The Technical Committee changes communication to communications for consistency and properuse.

ResponseMessage:

Public Input No. 449-NFPA 72-2016 [Section No. 27.5.3.6.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

285 of 496 10/20/2016 11:03 AM

Page 286: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3511-NFPA 72-2016 [ Section No. 27.5.5.3.5 ]

27.5.5.3.5

Radio repeaters upon which receipt of alarms depend shall be provided with dual receivers, transmitters,and power supplies. Failure of the primary receiver, transmitter, or power supply shall cause an automaticswitchover to the secondary receiver, transmitter, or power supply.

27.5.5.3.5.1

Manual switchover shall be permitted, provided that it is completed within 30 seconds.

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 14:14:56 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee removes the exception in accordance with guidance from theCorrelating Committee to remove Exceptions from NFPA 72.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

286 of 496 10/20/2016 11:03 AM

Page 287: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3512-NFPA 72-2016 [ Section No. 27.6.2.1.11.2 ]

27.6.2.1.11.2*

Outside plant cables entering buildings or other structures shall be installed in rigid metal conduit,intermediate metal conduit, or electrical metallic tubing. The installation shall comply with the requirementsof the applicable raceway article of NFPA 70.

27.6.2.1.11.3

Schedule 80 PVC or RTRC rigid nonmetallic conduit shall be permitted for the underground portions ofthe installations installation , provided that all elbows used are rigid or intermediate metal conduit.

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 14:18:23 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee removes the exception in accordance with guidance from theCorrelating Committee to remove Exceptions from NFPA 72.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

287 of 496 10/20/2016 11:03 AM

Page 288: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3513-NFPA 72-2016 [ Section No. 27.6.3.1.2 ]

27.6.3.1.2*

Outside plant cables entering buildings or other structures shall be installed in rigid metal conduit,intermediate metal conduit, or electrical metallic tubing. The installation shall comply with the requirementsof the applicable raceway article of NFPA 70.

Exception:

27.6.3.1.3

Schedule 80 PVC or RTRC rigid nonmetallic conduit shall be permitted for the underground portions ofthe installations installation , provided that all elbows used are rigid or intermediate metal conduit.

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 14:26:51 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee removes the exception in accordance with guidance from theCorrelating Committee to remove Exceptions from NFPA 72.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

288 of 496 10/20/2016 11:03 AM

Page 289: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3522-NFPA 72-2016 [ Section No. 27.6.3.2.2.1 ]

27.6.3.2.2.1

Auxiliary alarm systems shall be one of the following types:

(1)

(2)

Supplemental Information

File Name Description

PI_633.docx The list is misrepresented when entered into terra. It is corrected in this word file. For staff use

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 18:08:47 EDT 2016

Committee Statement

CommitteeStatement:

Both the “local energy-type” and “local energy type” terms are used in the Code. The former hashistorically (past editions a least to 1979) been used most extensively when including the “type”phrase. The Technical Committee revises the code to include the hyphen when “type” is included aspart of the descriptive compound noun to tie the phrase together.

* Local– energy-type

(a) Local energy– type systems shall be permitted to be of the coded or noncoded type.

(b) Power supply sources for local energy–type systems shall conform to Chapter 10.

(c) Transmitter trouble signals shall be indicated at the control unit and the building fire commandcenter in accordance with 10.14.7.

* Shunt- type

(a) Shunt– type systems shall be noncoded with respect to any remote electrical tripping oractuating devices.

(b) All conductors of the shunt circuit shall be installed in accordance with NFPA 70, Article 344, forrigid metal conduit, or Article 358, for electrical metallic tubing.

(c) Both sides of the shunt circuit shall be in the same conduit.

(d) Where a shunt loop is used, it shall not exceed a length of 750 ft (230 m) and shall be in conduit.

(e) Conductors of the shunt circuits shall not be smaller than 14 AWG and shall be insulated asprescribed in NFPA 70, Article 310.

(f) The power for shunt-type systems shall be provided by the public emergency alarm reportingsystem.

(g)* A local system made to an auxiliary alarm system by the addition of a relay whose coil isenergized by a local power supply and whose normally closed contacts trip a shunt-type masterbox shall not be permitted.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

289 of 496 10/20/2016 11:03 AM

Page 290: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

The Technical Committee revises “shunt-type” and "local energy-type" to be hyphenated to link thedescriptive compound noun together and to be consistent with other occurrences in the Code.

ResponseMessage:

Public Input No. 633-NFPA 72-2016 [Section No. 27.6.3.2.2.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

290 of 496 10/20/2016 11:03 AM

Page 291: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3523-NFPA 72-2016 [ Section No. 27.6.3.2.2.2 ]

27.6.3.2.2.2

The interface of the two types of auxiliary alarm systems with the three types of public emergency alarmreporting systems shall be in accordance with Table 27.6.3.2.2.2.

Table 27.6.3.2.2.2 Application of Public Emergency Alarm Reporting Systems with Auxiliary AlarmSystems

Reporting

Systems

Local Energy-

TypeShunt-Type

Wired Yes Yes

Wireless Yes No

Telephone series Yes No

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 18:12:40 EDT 2016

Committee Statement

CommitteeStatement:

A Correlating Committee Task Group on language/terms reviewed the language of the Code forconsistency and grammar.

Both the “local energy-type” and “local energy type” terms are used in the Code. The former hashistorically (past editions a least to 1979) been used most extensively when including the “type”phrase. The Technical Committee revises the Code to include the hyphen when “type” is includedas part of the descriptive compound noun to tie the phrase together.

The Technical Committee revises “shunt-type” and "local energy-type" to be hyphenated to link thedescriptive compound noun together and to be consistent with other occurrences in the Code.

ResponseMessage:

Public Input No. 634-NFPA 72-2016 [Section No. 27.6.3.2.2.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

291 of 496 10/20/2016 11:03 AM

Page 292: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3524-NFPA 72-2016 [ Section No. 27.6.3.2.2.3 ]

27.6.3.2.2.3

The application of the two types of auxiliary alarm systems shall be limited to the initiating devicesspecified in Table 27.6.3.2.2.3.

Table 27.6.3.2.2.3 Application of Initiating Devices with Auxiliary Alarm Systems

Initiating

Devices

LocalEnergy-

Type

Shunt-Type

Manually actuated alarm-initiating device Yes Yes

Waterflow or actuation of the fire extinguishing system(s) or suppressionsystem(s)

Yes Yes

Automatic detection devices Yes No

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 18:14:05 EDT 2016

Committee Statement

CommitteeStatement:

Both the “local energy-type” and “local energy type” terms are used in the Code. The former hashistorically (past editions a least to 1979) been used most extensively when including the “type”phrase. The Technical Committee revises the Code to include the hyphen when “type” is includedas part of the descriptive compound noun to tie the phrase together.

The Technical Committee revises “shunt-type” and "local energy-type" to be hyphenated to link thedescriptive compound noun together and to be consistent with other occurrences in the Code.

ResponseMessage:

Public Input No. 635-NFPA 72-2016 [Section No. 27.6.3.2.2.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

292 of 496 10/20/2016 11:03 AM

Page 293: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3514-NFPA 72-2016 [ Section No. 27.6.3.2.3.1 ]

27.6.3.2.3.1

Shunt-type auxiliary alarm systems shall be arranged so that one auxiliary transmitter does not serve

more than 100,000 ft2 (9290 m2) total area. Where or as otherwise permitted by the authority havingjurisdiction.

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 14:30:29 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee removes the exception in accordance with guidance from theCorrelating Committee to remove Exceptions from NFPA 72.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

293 of 496 10/20/2016 11:03 AM

Page 294: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3515-NFPA 72-2016 [ Section No. 27.6.3.2.3.6 ]

27.6.3.2.3.6

The system shall be designed and arranged so that a single fault on the auxiliary alarm system shall notjeopardize operation of the public emergency alarm reporting system and shall not, in case of a singlefault on either the auxiliary or public emergency alarm reporting system, transmit a false alarm on eithersystem.

27.6.3.2.3.7

Shunt The requirements of 27.6.3.2.3.6 shall not apply to shunt systems complying with27.6.3.2.2.1(2) .

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 14:32:54 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee removes the exception in accordance with guidance from theCorrelating Committee to remove Exceptions from NFPA 72.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

294 of 496 10/20/2016 11:03 AM

Page 295: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3516-NFPA 72-2016 [ Section No. 27.7.1.1.1 ]

27.7.1.1.1

Exterior metallic, fiber-optic cable and wire shall conform to International Municipal Signal Association(IMSA) specifications or an approved equivalent.

27.7.1.1.2

Where circuit conductors or fiber-optic strands are provided by a public utility on a lease basis, IMSAspecifications shall not apply.

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 14:39:43 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee removes the exception in accordance with guidance from theCorrelating Committee to remove Exceptions from NFPA 72.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

295 of 496 10/20/2016 11:03 AM

Page 296: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3517-NFPA 72-2016 [ Section No. 27.7.1.1.2 ]

27.7.1.1.3

Where a public box is installed inside a building, the circuit from the point of entrance to the public boxshall be installed in rigid metal conduit, intermediate metal conduit, or electrical metallic tubing inaccordance with NFPA 70.

Exception: This requirement shall not apply to wireless box systems.

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 14:41:59 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee removes the exception in accordance with guidance from theCorrelating Committee to remove Exceptions from NFPA 72. The exception was determined to becommon sense and not needed to be in the standard.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

296 of 496 10/20/2016 11:03 AM

Page 297: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3518-NFPA 72-2016 [ Section No. 27.7.1.4.1.2 ]

27.7.1.4.1.2

Conductors and cables for public emergency alarm reporting system use shall not be attached to acrossarm that carries electric light and power conductors.

27.7.1.4.1.3

Power conductors for Conductors that operate at 250 volts or less and are part of the public emergencyalarm reporting system use, operating at 250 volts or less, shall be permitted to share the crossarm withthe conductors and cables and shall be tagged for public emergency alarm reporting systems .

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 14:44:11 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee removes the exception in accordance with guidance from theCorrelating Committee to remove Exceptions from NFPA 72.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

297 of 496 10/20/2016 11:03 AM

Page 298: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3519-NFPA 72-2016 [ Section No. 27.7.1.6.2 ]

27.7.1.6.2*

Where installed in buildings, conductors and fiber-optic cables shall be installed in any of the followingwiring methods:

(1) Electrical metallic tubing

(2) Intermediate metal conduit

(3) Rigid metal conduit

27.7.1.6.2.1

Rigid nonmetallic conduit Where installed in buildings, conductors and fiber-optic cables shall bepermitted to be installed in rigid nonmetallic conduit where approved by the authority having jurisdiction.

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 14:56:22 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee removes the exception in accordance with guidance from theCorrelating Committee to remove Exceptions from NFPA 72.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

298 of 496 10/20/2016 11:03 AM

Page 299: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3520-NFPA 72-2016 [ Section No. 27.7.2.1.5 ]

27.7.2.1.5

Circuits shall not pass over, under, through, or be attached to buildings or property not owned by or underthe control of the authority having jurisdiction or the agency responsible for maintaining the system.

27.7.2.1.6

Where The requirements of 27.7.2.1.5 shall not apply where the circuit is terminated at a publicemergency alarm reporting system initiating device on the premises and where a means, approved bythe authority having jurisdiction, is provided to disconnect the circuit from the building or property.

Submitter Information Verification

Submitter Full Name: SIG-PRS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 15:01:19 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee removes the exception in accordance with guidance from theCorrelating Committee to remove Exceptions from NFPA 72.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

299 of 496 10/20/2016 11:03 AM

Page 300: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1504-NFPA 72-2016 [ Section No. 29.2 ]

29.2* Purpose.

29.2.1

Fire-warning equipment for residential occupancies shall provide a reliable means to notify the occupantsof the presence of a threatening fire and the need to escape to a place of safety before such escape mightbe impeded by untenable conditions in the normal path of egress.

29.2.2*

Carbon monoxide warning equipment for residential occupancies shall provide a reliable means to notifythe occupants of the presence of carbon monoxide levels that constitute a potential life safety risk andthe need for action as a consequence of those levels.

Supplemental Information

File Name Description

72_FR-1504_A.29.2.2_HOU.docx

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 13:12:58 EDT 2016

Committee Statement

CommitteeStatement:

The Standards Council approved the consolidation of NFPA 720 and NFPA 72 and directed thecurrent material that is within the existing NFPA 720 to be relocated into the next edition of NFPA72. The Correlating Committee on Signaling Systems for the Protection of Life and Propertyappointed the 720/72 Consolidation Task Group to review and effect the necessary changes. TheSIG-HOU committee accepts this addition.

Annex: By favorable ballot of the NFPA 72 Technical Committees, the Correlating Committee onSignaling Systems for the Protection of Life and Property and approval by the NFPA StandardsCouncil (August 17-19, 2015) the current material within the existing NFPA 720 is to be incorporatedinto the next edition of NFPA 72.

Text has been modified to avoid specific occupancy references. (SIG-HOU)

The Technical Committee adds a new last sentence to recommend a potential personal safetymeasure.

This is an installation standard. Requirements for when and where to install carbon monoxidewarning equipment belong in occupancy standards and building and fire codes, not this document.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

300 of 496 10/20/2016 11:03 AM

Page 301: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Public Input No. 367-NFPA 72-2016 [Section No. 29.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

301 of 496 10/20/2016 11:03 AM

Page 302: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1505-NFPA 72-2016 [ Sections 29.3.5, 29.3.6, 29.3.7, 29.3.8, 29.3.9 ]

29.4 Notification.

29.4.1*

Fire-warning equipment to be installed in residential occupancies shall produce the audible emergencyevacuation signal described in ANSI/ASA S3.41, American National Standard Audible EmergencyEvacuation Signal, whenever the intended response is to evacuate the building.

Exception: Where mechanically powered single-station heat alarms are used as supplementarydevices, unless required by applicable laws, codes, or standards, such devices shall not be required toproduce the emergency evacuation signal described in ANSI S3.41.

29.4.2

Where mechanically powered single-station heat alarms are used as supplementary devices, unlessrequired by applicable laws, codes, or standards, such devices shall not be required to produce theemergency evacuation signal described in ANSI/ASA S3.41.

29.4.3*

Carbon monoxide warning equipment to be installed in residential occupancies shall produce the T-4signal. After the initial 4 minutes of alarm, the 5-second “off” time of the alarm signal shall be permittedto be changed to 60 seconds ± 10 percent.

29.4.4

The audible emergency evacuation signal shall be permitted to be used for other devices as long as thedesired response is immediate evacuation.

29.4.5*

Fire-warning equipment producing the audible emergency evacuation signal shall be permitted toincorporate voice notification under either or both of the following conditions:

(1) Where the voice message is contained completely within the 1.5-second pause period of the audibleemergency evacuation signal

(2) Where the voice message complies with 29.4.5(2)(a) and 29.4.5(2)(b) as follows:

(a) The voice message is first preceded by a minimum of eight cycles of the audible emergencyevacuation signal.

(b) The voice message periodically interrupts the signal for no longer than 10 seconds, followed by aminimum of two cycles of the audible emergency evacuation signal between each voicemessage. The initial eight-cycle period shall not be required to be repeated.

29.4.6*

Carbon monoxide warning equipment producing the audible alarm signal shall be permitted toincorporate voice notification under either or both of the following:

(1) Where the voice message is contained completely within the 5-second pause period of the audiblealarm signal

(2) Where the voice message complies with 29.4.6(2)(a) and 29.4.6(2)(b) as follows:

(a) The voice message is first preceded by a minimum of 6 cycles of the audible alarm signal.

(b) The voice message periodically interrupts the signal for no longer than 10 seconds, followedby a minimum of two cycles of the audible alarm signal between each voice message. Theinitial 6-cycle period shall not be required to be repeated.

29.4.7

All audible fire alarm signals installed shall meet the performance requirements of 18.4.4, 18.4.6.1,18.4.6.2, and 29.4.9.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

302 of 496 10/20/2016 11:03 AM

Page 303: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

29.4.8*

When Where visible appliances are provided, they shall meet the requirements of Section 18.5. Sincehearing deficits are often not apparent, the responsibility for advising the appropriate person(s) of theexistence of this deficit shall be that of the party with hearing loss.

29.4.9

Notification appliances provided in sleeping rooms and guest rooms for those with hearing loss shallcomply with 29.4.9.1 and 29.4.9.2, as applicable.

29.4.9.1* Mild to Severe Hearing Loss.

Notification appliances provided for those with mild to severe hearing loss shall comply with the following:

(1) An audible notification appliance producing a low frequency alarm signal shall be installed in thefollowing situations:

(a) Where required by governing laws, codes, or standards for people with hearing loss

(b) Where provided voluntarily for those with hearing loss

(2)

29.4.9.2* Moderately Severe to Profound Hearing Loss.

Visible notification appliances in accordance with the requirements of 18.5.5.7 and tactile notificationappliances in accordance with the requirements of Section 18.10 shall be required for those withmoderately severe to profound hearing loss in the following situations:

(1)

(2) Where provided voluntarily for those with hearing loss

29.4.10

Signals from notification appliances shall not be required to be synchronized.

Supplemental Information

File Name Description

FR_1505_Figure_A.29.4.3.png New annex image

FR_1505_Figure_A.29.4.6_T4_drawing_Model.pdf new annex image

FR_1505_A.29.4.docx New annex text

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 16:06:39 EDT 2016

Committee Statement

Committee The Standards Council approved the consolidation of NFPA 720 and NFPA 72 and directed the

* The low frequency alarm signal output shall comply with the following:

(a) The waveform shall have a fundamental frequency of 520 Hz ±10 percent.

(b) The minimum sound level at the pillow shall be 75 dBA, or 15 dB above the average ambientsound level, or 5 dB above the maximum sound level having a duration of at least 60 seconds,whichever is greater.

* Where required by governing laws, codes, or standards for people with hearing loss

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

303 of 496 10/20/2016 11:03 AM

Page 304: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Statement: current material that is within the existing NFPA 720 to be relocated into the next edition of NFPA 72.The Correlating Committee on Signaling Systems for the Protection of Life and Property appointedthe 720/72 Consolidation Task Group to review and effect the necessary changes. The SIG-HOUcommittee accepts the addition of 29.4.3.

This revision removes the exception to comply with the Manual of Style.

This revision adds the voice allowance for CO which was proposed to be added to NFPA 720.

Note to Correlating Committee: The annex material in A.29.4.3 should not be repeated if it is beingincluded in Chapter 18.

ResponseMessage:

Public Input No. 388-NFPA 72-2016 [Section No. 29.3.5 [Excluding any Sub-Sections]]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

304 of 496 10/20/2016 11:03 AM

Page 305: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1507-NFPA 72-2016 [ New Section after 29.5 ]

29.6* Carbon Monoxide Detection.

The warning functions intended in this standard shall be performed by single or multiple-station alarmsor by detectors connected to a control unit and associated equipment.

29.6.1 Required Detection.

29.6.1.1*

Where required by other governing laws, codes, or standards for a specific type of occupancy, listedcarbon monoxide alarms or detectors shall be installed as follows:

(1) Outside of each separate dwelling unit sleeping area, within 21 ft (6.4 m) of any door to a sleepingroom, with the distance measured along a path of travel

(2) On every occupiable level of a dwelling unit, including basements, excluding attics and crawlspaces

(3) In all sleeping rooms and guest rooms containing installed fuel-burning appliances

(4) Other locations where required by applicable laws, codes, or standards

29.6.1.2*

Each alarm or detector shall be located on the wall, ceiling, or other location as specified in themanufacturer’s published instructions that accompany the unit.

Detail FR-5051

29.6.2 Carbon Monoxide Alarm Interconnection.

Unless exempted by applicable laws, codes, or standards, carbon monoxide alarms used to provide awarning function, and where two or more alarms are installed within a dwelling unit, suite of rooms, orsimilar area, shall be arranged so that the operation of any carbon monoxide alarm causes all carbonmonoxide alarms within these locations to sound.

Supplemental Information

File Name Description

FR_1507_A.29.6.docx New annexes

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 16:44:37 EDT 2016

Committee Statement

CommitteeStatement:

The Standards Council approved the consolidation of NFPA 720 and NFPA 72 and directed thecurrent material that is within the existing NFPA 720 to be relocated into the next edition of NFPA 72.The Correlating Committee on Signaling Systems for the Protection of Life and Property appointedthe 720/72 Consolidation Task Group to review and effect the necessary changes. Carbon monoxide

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

305 of 496 10/20/2016 11:03 AM

Page 306: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

detection requirements have been moved here for this purpose.

Besides the language that was moved from NFPA 720, the requirement for detection in sleepingrooms containing fuel-burning appliances was added to address the hazard of incompletecombustion from fuel-burning appliances.

A dimension of 21 feet was added to improve the usability and provide clear direction.

ResponseMessage:

Public Input No. 401-NFPA 72-2016 [New Section after A.29.5.1.3.1]

Public Input No. 369-NFPA 72-2016 [New Section after 29.5.1]

Public Input No. 402-NFPA 72-2016 [New Section after A.29.5.1.3.1]

Public Input No. 403-NFPA 72-2016 [New Section after A.29.5.1.3.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

306 of 496 10/20/2016 11:03 AM

Page 307: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1506-NFPA 72-2016 [ Section No. 29.5.1 ]

29.7.1* Required Smoke Detection.

29.7.1.1*

Where required by other governing laws, codes, or standards for a specific type of occupancy,approved listed single- and multiple-station smoke alarms shall be installed as follows:

(1)

(2)

(3) On every level of a dwelling unit, including basements

(4) On every level of a residential board and care occupancy (small facility), including basements andexcluding crawl spaces and unfinished attics

(5)

(6) In the living area(s) of a residential board and care occupancy (small facility)

29.7.1.2

Where the area addressed in 29.7.1.1(2) is separated from the adjacent living areas by a door, a smokealarm shall be installed in the area between the door and the sleeping rooms, and additional alarms shallbe installed on the living area side of the door as specified by 29.7.1.1 and 29.7.1.3.

29.7.1.3

In addition to the requirements of 29.7.1.1(1) through (3), where the interior floor area for a given level of

a dwelling unit, excluding garage areas, is greater than 1000 ft2 (93 m2), smoke alarms shall be installedper 29.7.1.3.1 and 29.7.1.3.2.

29.7.1.3.1*

All points on the ceiling shall have a smoke alarm within a distance of 30 ft (9.1 m) travel distance or shall

have an equivalent of one smoke alarm per 500 ft2 (46 m2) of floor area. One smoke alarm per 500 ft2

(46 m2) is evaluated by dividing the total interior square footage of floor area per level by 500 ft2 (46 m2).

29.7.1.3.2

Where dwelling units include great rooms or vaulted/cathedral ceilings extending over multiple floors,smoke alarms located on the upper floor that are intended to protect the aforementioned area shall bepermitted to be considered as part of the lower floor(s) protection scheme used to meet the requirementsof 29.7.1.3.1.

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 16:14:33 EDT 2016

Committee Statement

* In all sleeping rooms and guest rooms

* Outside of each separate dwelling unit sleeping area, within 21 ft (6.4 m) of any door to a sleepingroom, with the distance measured along a path of travel

* In the living area(s) of a guest suite

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

307 of 496 10/20/2016 11:03 AM

Page 308: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

CommitteeStatement:

The Standards Council approved the consolidation of NFPA 720 and NFPA 72 and directed thecurrent material that is within the existing NFPA 720 to be relocated into the next edition of NFPA 72.The Correlating Committee on Signaling Systems for the Protection of Life and Property appointedthe 720/72 Consolidation Task Group to review and effect the necessary changes. This sectionapplies to smoke detection, not CO detection.

"Approved" is changed to "listed" because it eliminates the confusion of whether it is the localauthority who is approving the equipment.

ResponseMessage:

Public Input No. 368-NFPA 72-2016 [Section No. 29.5.1]

Public Input No. 694-NFPA 72-2016 [Section No. 29.5.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

308 of 496 10/20/2016 11:03 AM

Page 309: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1509-NFPA 72-2016 [ Section No. 29.5.2.1.1 ]

29.7.2.1.1* Interconnected Smoke and Heat Alarms.

Unless exempted by applicable laws, codes, or standards, smoke or heat alarms used to provide afire-warning function, and when where two or more alarms are installed within a dwelling unit, suite ofrooms, or similar area, shall be arranged so that the operation of any smoke or heat alarm causes allalarms within these locations to sound.

Exception: The arrangment for all alarms to sound shall not be required for mechanically poweredsingle-station heat alarms.

29.7.2.1.1.1

The arrangement for all alarms to sound shall not be required for mechanically powered single-stationheat alarms.

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 18:06:32 EDT 2016

Committee Statement

CommitteeStatement:

The word "exception" is removed to comply with the Manual of Style. The title is revised toclarify that this section applies to the interconnection of the sounding of smoke and heat alarms.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

309 of 496 10/20/2016 11:03 AM

Page 310: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1513-NFPA 72-2016 [ New Section after 29.6.1 ]

29.8.2 Primary Power Source Nonreplaceable Primary Battery.

If alarms are powered by a nonrechargeable, nonreplaceable primary battery, the battery shall bemonitored to ensure the following conditions are met:

(1) All power requirements are met for at least 10 years of battery life, including required periodictesting.

(2) A distinctive audible trouble signal occurs before the battery is incapable of operating the device(s)for alarm purposes.

(3) At the battery voltage at which a trouble signal is obtained, the unit is capable of producing a firealarm signal for at least 4 minutes, or a carbon monoxide alarm signal for at least 12 continuoushours, followed by not less than 7 days of trouble signal operation.

(4) The audible trouble signal is produced at least once every minute for 7 consecutive days.

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 11:19:02 EDT 2016

Committee Statement

CommitteeStatement:

Performance requirements for a device powered by a 10-year battery should not be lessstringent than those powered by a 1-year battery.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

310 of 496 10/20/2016 11:03 AM

Page 311: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1514-NFPA 72-2016 [ Section No. 29.6.1 ]

29.8.1 Smoke and Heat and Carbon Monoxide Alarms.

Smoke and heat and carbon monoxide alarms shall meet the requirements of 29.7.2.1.1 and be poweredby one of the following means:

(1) A commercial light and power source along with a secondary power source that is capable ofoperating the device for at least 7 days in the normal condition, followed by 4 minutes of alarm.Carbon monoxide alarms shall have sufficient capacity to operate the alarm signal(s) for at least 12continuous hours.

(2) If a commercial light and power source is not normally available, a noncommercial ac power sourcealong with a secondary power source that is capable of operating the device for at least 7 days in thenormal condition, followed by 4 minutes of alarm for smoke and heat alarms or 12 hours of alarm forcarbon monoxide alarms.

(3) A nonrechargeable, nonreplaceable nonrechargeable, nonreplaceable primary battery that iscapable of operating the device for at least 10 years in the normal condition, followed by 4 minutes ofalarm, followed by 7 days of trouble meets the requirements of 29.8.2 .

(4) If a battery primary power supply is specifically permitted, a battery meeting the requirements of29.8.7 29.8.729.8.6 29.8.7 (nonrechargeable primary battery) or the requirements of29.8.2 29.8.229.8.7 29.8.2 (rechargeable primary battery) .

(5) A suitable spring-wound mechanism for the nonelectrical portion of a listed single-station alarm with avisible indication to show that sufficient operating power is not available.

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 11:23:37 EDT 2016

Committee Statement

CommitteeStatement:

The Standards Council approved the consolidation of NFPA 720 and NFPA 72 and directed thecurrent material that is within the existing NFPA 720 to be relocated into the next edition of NFPA72. The Correlating Committee on Signaling Systems for the Protection of Life and Propertyappointed the 720/72 Consolidation Task Group to review and effect the necessary changes.

Carbon monoxide alarms are required to be able to sound for 12 continuous hours. This adds thatrequirement to this section.

ResponseMessage:

Public Input No. 384-NFPA 72-2016 [Section No. 29.6.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

311 of 496 10/20/2016 11:03 AM

Page 312: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1510-NFPA 72-2016 [ Section No. 29.6.2 ]

29.8.3 Household Fire Fire and Carbon Monoxide Alarm Systems.

Power for household fire alarm systems shall comply with the following requirements:

(1) Household fire and carbon monoxide alarm systems shall have two independent power sourcesconsisting of a primary source that uses commercial light and power and a secondary source thatconsists of a rechargeable battery.

(2) The secondary source shall be capable of operating the system for at least 24 hours in the normalcondition, followed by 4 minutes of fire alarm or 12 hours of carbon monoxide alarm .

(3) The secondary power source shall be supervised and shall cause a distinctive audible and visibletrouble signal upon removal or disconnection of a battery or a low-battery condition.

(4) A rechargeable battery used as a secondary power source shall meet the following criteria:

(a) Be automatically recharged by an ac circuit of the commercial light and power source

(b) Be recharged within 48 hours

(c) Provide a distinctive audible trouble signal before the battery is incapable of operating thedevice(s) for alarm purposes

(5) Low-power wireless systems shall comply with the performance criteria of Section 23.16.

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 18:30:53 EDT 2016

Committee Statement

CommitteeStatement:

The Standards Council approved the consolidation of NFPA 720 and NFPA 72 and directed thecurrent material that is within the existing NFPA 720 to be relocated into the next edition of NFPA72. The Correlating Committee on Signaling Systems for the Protection of Life and Propertyappointed the 720/72 Consolidation Task Group to review and effect the necessary changes.

The carbon monoxide audible alarm signal must sound for 12 continuous hours. This revisionincorporates that requirement into the household alarm system power requirements.

ResponseMessage:

Public Input No. 385-NFPA 72-2016 [Section No. 29.6.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

312 of 496 10/20/2016 11:03 AM

Page 313: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1515-NFPA 72-2016 [ Section No. 29.6.3 ]

29.8.4 AC Primary Power Source.

The ac power source specified in 29.8.1 and 29.8.3 29.8.329.8.2 29.8.3 shall comply with the followingconditions:

(1) A visible “power on” indicator shall be provided.

(2) All electrical systems designed to be installed by other than a qualified electrician shall be poweredfrom a source not in excess of 30 volts that meets the requirements for power-limited fire alarmcircuits as defined in NFPA 70, Article 760.

(3)

(4) AC primary (main) power shall be supplied either from a dedicated branch circuit or the unswitchedportion of a branch circuit also used for power and lighting.

(5) Operation of a switch (other than a circuit breaker) shall not cause loss of primary (main) power.Operation of a ground-fault circuit-interrupter (GFCI) receptacle shall not cause loss of primary (main)power. Smoke alarms Alarms powered by branch circuits protected by arc-fault circuit-interrupters(AFCI) or GFCI circuit breakers ground-fault circuit-interrupters (GFCI) shall have a secondary powersource.

(6) Neither loss nor restoration of primary (main) power shall cause an alarm signal that exceeds 2seconds .

Exception: An alarm signal shall be permitted but shall not exceed 2 seconds.

(7) Where a secondary (standby) battery is provided, the primary (main) power supply shall be ofsufficient capacity to operate the system under all conditions of loading with any secondary (standby)battery disconnected or fully discharged.

Supplemental Information

File Name Description

FR_1515_A.29.6.3_3_.docx New annex material

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 11:42:04 EDT 2016

Committee Statement

CommitteeStatement:

The Standards Council approved the consolidation of NFPA 720 and NFPA 72 and directed thecurrent material that is within the existing NFPA 720 to be relocated into the next edition of NFPA 72.The Correlating Committee on Signaling Systems for the Protection of Life and Property appointedthe 720/72 Consolidation Task Group to review and effect the necessary changes. “Smoke” wasremoved from list item 5 because this now applies to CO alarms as well.

* A restraining means shall be used at the plug-in of any cord-connected installation, unless the unitutilizes a secondary (standby) power source meeting the requirements of Section 29.6 and loss ofthe ac primary power source results in annunciation of an audible trouble signal meeting 29.7.6.4 .

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

313 of 496 10/20/2016 11:03 AM

Page 314: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

The exception was rewritten to comply with the Manual of Style.

List item (3): The annunciation of an audible trouble signal meeting 29.7.6.4 to alert the user whenthe plug has been dislodged or disconnected provides warning to reattach the plug to thereceptacle. This option also addresses newer receptacles which do not have a center screw forattachment of the receptacle cover. Marking has not been added as an alternate method because itwould provide a lower level of protection than this revision.

List item (5): This section is clarified to apply to all GFCI and AFCI protection.

ResponseMessage:

Public Input No. 386-NFPA 72-2016 [Section No. 29.6.3]

Public Input No. 404-NFPA 72-2016 [New Section after A.29.5.2.2]

Public Input No. 764-NFPA 72-2016 [Section No. 29.6.3]

Public Input No. 663-NFPA 72-2016 [Section No. 29.6.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

314 of 496 10/20/2016 11:03 AM

Page 315: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1516-NFPA 72-2016 [ Section No. 29.6.4 ]

29.8.5 Secondary (Standby) Power Source.

Where alarms include a battery that is used as a secondary power source, the following conditions shallbe met:

(1) The secondary power source shall be supervised and shall cause a distinctive audible or visibletrouble signal upon removal or disconnection of a battery or a low-battery condition.

(2) Acceptable replacement batteries shall be clearly identified by the manufacturer’s name and modelnumber on the unit near the battery compartment.

(3) A rechargeable battery used as a secondary power source shall meet the following criteria:

(a) Be automatically recharged by the primary power source

(b) Be recharged within 4 hours where power is provided from a circuit that can be switched on or offby means other than a circuit breaker, or within 48 hours where power is provided from a circuitthat cannot be switched on or off by means other than a circuit breaker

(c) Provide a distinctive audible trouble signal before the battery is incapable of operating thedevice(s) for alarm purposes

(d) At the battery condition at which a trouble signal is obtained, be capable of producing an a firealarm signal for at least 4 minutes or the carbon monoxide signal for 12 continuous hours, ,followed by not less than 7 days of trouble signal operation

(e) Produce an audible trouble signal at least once every minute for 7 consecutive days

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 11:54:15 EDT 2016

Committee Statement

CommitteeStatement:

The Standards Council approved the consolidation of NFPA 720 and NFPA 72 and directed thecurrent material that is within the existing NFPA 720 to be relocated into the next edition of NFPA72. The Correlating Committee on Signaling Systems for the Protection of Life and Propertyappointed the 720/72 Consolidation Task Group to review and effect the necessary changes.

This adds the 12 hour alarm signal requirement for carbon monoxide alarms.

ResponseMessage:

Public Input No. 387-NFPA 72-2016 [Section No. 29.6.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

315 of 496 10/20/2016 11:03 AM

Page 316: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1511-NFPA 72-2016 [ Section No. 29.6.5 ]

29.8.6 Visible Notification Appliance (with Smoke or Heat Single- or Multiple-Station Alarm).

If a visible notification appliance is used in conjunction with a smoke or heat alarm application single- ormultiple-station alarm for compliance with 29.4.8, the notification appliance shall not be required to besupplied with a secondary power source.

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 18:38:56 EDT 2016

Committee Statement

CommitteeStatement:

The Standards Council approved the consolidation of NFPA 720 and NFPA 72 and directed thecurrent material that is within the existing NFPA 720 to be relocated into the next edition of NFPA72. The Correlating Committee on Signaling Systems for the Protection of Life and Propertyappointed the 720/72 Consolidation Task Group to review and effect the necessary changes.

This incorporates all single- and multiple-station alarms, including carbon monoxide alarms, into thisrequirement.

ResponseMessage:

Public Input No. 392-NFPA 72-2016 [Section No. 29.6.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

316 of 496 10/20/2016 11:03 AM

Page 317: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1517-NFPA 72-2016 [ Section No. 29.6.6 ]

29.8.7 Primary Replaceable Battery, Sole Power Source (Nonrechargeable Battery ).

If smoke alarms are powered solely by a replaceable primary battery, the battery shall be monitored toensure the following conditions are met:

(1) All power requirements are met for at least 1 year of battery life, including weekly required periodictesting.

(2) A distinctive audible trouble signal before the battery is incapable of operating (from causes such asaging or terminal corrosion) operating the device(s) for alarm purposes.

(3) For a system - connected unit employing a lock-in alarm feature, automatic transfer is provided fromalarm to a trouble condition when the unit has insufficient power to support an alarm condition .

(4) At the battery voltage at which a trouble signal is obtained, the unit is capable of producing an a firealarm signal for at least 4 minutes or a carbon monoxide alarm signal for at least 12 continuoushours , followed by not less than 7 days of trouble signal operation.

(5) The audible trouble signal is produced at least once every minute for 7 consecutive days.

(6) Acceptable replacement batteries are clearly identified by the manufacturer’s name and modelnumber on the unit near the battery compartment.

(7) A noticeable, visible indication is displayed when a primary battery is removed from the unit.

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 11:57:20 EDT 2016

Committee Statement

CommitteeStatement:

The Standards Council approved the consolidation of NFPA 720 and NFPA 72 and directed thecurrent material that is within the existing NFPA 720 to be relocated into the next edition of NFPA 72.The Correlating Committee on Signaling Systems for the Protection of Life and Property appointedthe 720/72 Consolidation Task Group to review and effect the necessary changes. This revisionincorporates the 12 hour carbon monoxide alarm requirement.

List item (2) is revised to remove explanatory language.

List item (3) is revised for clarity.

ResponseMessage:

Public Input No. 389-NFPA 72-2016 [Section No. 29.6.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

317 of 496 10/20/2016 11:03 AM

Page 318: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1518-NFPA 72-2016 [ Section No. 29.6.7 ]

29.8.8 Primary Power Source (Rechargeable Battery).

If smoke alarms are powered by a rechargeable battery, the following conditions shall be met:

(1) The battery shall, with proper charging, be able to power the alarm for a life of 1 year.

(2) The battery shall be automatically recharged by an a circuit of the commercial light and powersource.

(3) The battery shall be recharged within 4 hours where power is provided from a circuit that can beswitched on or off by means other than a circuit breaker, or within 48 hours where power is providedfrom a circuit that cannot be switched on or off by means other than a circuit breaker.

(4) A distinctive audible trouble signal shall sound before the battery is incapable of operating thedevice(s) for alarm purposes.

(5) For a unit employing a lock-in alarm feature, automatic transfer shall be provided from alarm to atrouble condition.

(6) At the battery condition at which a trouble signal is obtained, the unit shall be capable of producingan a fire alarm signal for at least 4 minutes or a carbon monoxide alarm signal for 12 continuoushours , followed by not less than 7 days of trouble signal operation.

(7) The audible trouble signal shall be produced at least once every minute for 7 consecutive days.

(8) The battery shall be nonremoveable , or a noticeable and visible indication shall be displayed whenthe battery is removed from the unit.

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 12:10:21 EDT 2016

Committee Statement

CommitteeStatement:

The Standards Council approved the consolidation of NFPA 720 and NFPA 72 and directed thecurrent material that is within the existing NFPA 720 to be relocated into the next edition of NFPA 72.The Correlating Committee on Signaling Systems for the Protection of Life and Property appointedthe 720/72 Consolidation Task Group to review and effect the necessary changes. This incorporatesthe 12 hour carbon monoxide alarm requirement.

List item (8) is added to ensure that there is notice to the occupant if the battery is removed.

ResponseMessage:

Public Input No. 390-NFPA 72-2016 [Section No. 29.6.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

318 of 496 10/20/2016 11:03 AM

Page 319: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1512-NFPA 72-2016 [ Section No. 29.6.8 ]

29.8.9 Secondary (Standby) Non-Battery Power Source.

Where alarms include a secondary power source (non-battery), the following conditions shall be met:

(1) The secondary power source shall be supervised and shall cause a distinctive audible or visibletrouble signal upon depletion or failure.

(2) A distinctive audible trouble signal shall be provided before the power source is incapable ofoperating the device(s) for alarm purposes.

(3) At a power source condition at which a trouble signal is obtained, the power source shall be capableof producing an a fire alarm signal for at least 4 minutes or a carbon monoxide alarm signal for atleast 12 continuous hours , followed by not less than 7 days of trouble signal operation.

(4) The audible trouble signal shall be produced at least once every minute for 7 consecutive days.

(5) A rechargeable secondary power source shall meet the following criteria:

(a) Be automatically recharged.

(b) Be recharged within 4 hours where power is provided from a circuit that can be switched on or offby means other than a circuit breaker, or within 48 hours where power is provided from a circuitthat cannot be switched on or off by means other than a circuit breaker.

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 18:49:27 EDT 2016

Committee Statement

CommitteeStatement:

The Standards Council approved the consolidation of NFPA 720 and NFPA 72 and directed thecurrent material that is within the existing NFPA 720 to be relocated into the next edition of NFPA72. The Correlating Committee on Signaling Systems for the Protection of Life and Propertyappointed the 720/72 Consolidation Task Group to review and effect the necessary changes.

This incorporates the 12 hour alarm requirement for carbon monoxide devices.

ResponseMessage:

Public Input No. 391-NFPA 72-2016 [Section No. 29.6.8]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

319 of 496 10/20/2016 11:03 AM

Page 320: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1521-NFPA 72-2016 [ New Section after 29.7.2 ]

29.9.3 Carbon Monoxide Alarms and Detectors.

29.9.3.1*

Each carbon monoxide alarm shall be in compliance with ANSI/UL 2034, Standard for Single andMultiple Station Carbon Monoxide Alarms .

29.9.3.2

Each carbon monoxide detector shall be in compliance with ANSI/UL 2075, Standard for Gas andVapor Detectors and Sensors , and shall meet the sensitivity testing and alarm thresholds of ANSI/UL2034, Standard for Single and Multiple Station Carbon Monoxide Alarms .

29.9.3.3

All signals produced from periodic testing of carbon monoxide alarms or detectors shall be identical tothe signal produced when the unit is in alarm.

29.9.3.4

Trouble signals shall be distinctive from alarm signals.

29.9.3.5

Unless otherwise recommended by the manufacturer’s published instructions, carbon monoxide alarmsand detectors shall be replaced when they fail to respond to tests.

Supplemental Information

File Name Description

FR_1521_A.29.7.3.1.docx New annex

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 15:13:27 EDT 2016

Committee Statement

CommitteeStatement:

The Standards Council approved the consolidation of NFPA 720 and NFPA 72 and directed thecurrent material that is within the existing NFPA 720 to be relocated into the next edition of NFPA 72.The Correlating Committee on Signaling Systems for the Protection of Life and Property appointedthe 720/72 Consolidation Task Group to review and effect the necessary changes. This incorporatesNFPA 720 requirements into NFPA 72.

ResponseMessage:

Public Input No. 405-NFPA 72-2016 [New Section after A.29.7.2]

Public Input No. 366-NFPA 72-2016 [New Section after 29.7.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

320 of 496 10/20/2016 11:03 AM

Page 321: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1520-NFPA 72-2016 [ Section No. 29.7.3 ]

29.9.4 Resistance to Nuisance Source.

Effective January 1, 2019, smoke alarms and smoke detectors used in household fire alarm systemsshall be listed for resistance to common nuisance sources.

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 13:52:06 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee deletes the text. Cooking is the most common nuisance sourceand is addressed in 29.8.3.4 (6).

ResponseMessage:

Public Input No. 755-NFPA 72-2016 [Section No. 29.7.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

321 of 496 10/20/2016 11:03 AM

Page 322: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1501-NFPA 72-2016 [ Section No. 29.7.4.1 ]

29.9.4.1

Each heat detector and heat alarm, including a heat detector or heat alarm integrally mounted on a smokedetector or smoke alarm, shall detect abnormally high temperature or rate-of-temperature rise, and allsuch detectors shall be listed for not less than 50 ft (15 15.2 m) spacing.

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 11:15:17 EDT 2016

Committee Statement

CommitteeStatement:

This revision is made to align with the work of NFPA 72 Correlating Committee Task Group onMetric Values for consistency throughout the document. (PI 692)

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

322 of 496 10/20/2016 11:03 AM

Page 323: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1522-NFPA 72-2016 [ Section No. 29.7.6.5 ]

29.9.6.5

A means for turning off activated alarm notification appliances shall be permitted only if the followingconditions are satisfied:

(1) The means is key-operated or located within a locked cabinet, or arranged to provide equivalentprotection against unauthorized use.

(2) The means includes the provision of a visible alarm silence indication.

(3) The silenced position is indicated by a distinctive signal.

(4) The switch is a momentary or self-restoring switch.

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 15:40:40 EDT 2016

Committee Statement

CommitteeStatement:

The Standards Council approved the consolidation of NFPA 720 and NFPA 72 and directed thecurrent material that is within the existing NFPA 720 to be relocated into the next edition of NFPA 72.The Correlating Committee on Signaling Systems for the Protection of Life and Property appointedthe 720/72 Consolidation Task Group to review and effect the necessary changes. This incorporatesNFPA 720 requirements into NFPA 72.

ResponseMessage:

Public Input No. 365-NFPA 72-2016 [Section No. 29.7.6.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

323 of 496 10/20/2016 11:03 AM

Page 324: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1523-NFPA 72-2016 [ Section No. 29.7.7.6 ]

29.9.7.6

In a fire/burglar system, the operation shall be as follows: Audible alarm signals shall be provided in thefollowing priority order:

(1) A fire alarm signal shall take precedence or be clearly recognizable over any other signal, even whenthe non-fire alarm signal is initiated first. Fire alarm

(2) Distinctive alarm signals shall be used so that fire alarms can be distinguished from other functions,such as burglar alarms. The use of a common-sounding appliance for fire and burglar alarms shall bepermitted where distinctive signals are used. Carbon monoxide

(3) Other

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 16:31:58 EDT 2016

Committee Statement

CommitteeStatement:

The previous language in 29.7.7.6 is removed because it was redundant (see 29.7.7.2 and29.7.7.3). New language is added to require fire and carbon monoxide alarms to take precedenceover less critical alarms, such as burglar.

ResponseMessage:

Public Input No. 363-NFPA 72-2016 [Section No. 29.7.7.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

324 of 496 10/20/2016 11:03 AM

Page 325: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1538-NFPA 72-2016 [ Section No. 29.7.9.1 [Excluding any

Sub-Sections] ]

Means to transmit alarm signals to a constantly attended, remote monitoring location shall be processedby a household fire alarm system and shall perform as described in Chapter 26, except as modified by29.9.9.1.1 through 29.9.9.1.6 29.9.9.1.7 .

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 00:28:01 EDT 2016

Committee Statement

Committee Statement: A new requirement was added (section 29.7.9.1.7) by FR 1532.

Response Message:

Public Input No. 655-NFPA 72-2016 [Section No. 29.7.9.1 [Excluding any Sub-Sections]]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

325 of 496 10/20/2016 11:03 AM

Page 326: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1532-NFPA 72-2016 [ New Section after 29.7.9.1.6 ]

29.9.9.1.7

Alarm, supervisory, and trouble signals shall be permitted to be received at a listed central supervisingstation.

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 10:37:48 EDT 2016

Committee Statement

CommitteeStatement:

Provides clarity for signal transmission in household alarm systems. Section 26.5.3 contains arestrictive clause requiring listed stations to exceed the current supervising station requirements.

ResponseMessage:

Public Input No. 656-NFPA 72-2016 [Section No. 29.7.9.1.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

326 of 496 10/20/2016 11:03 AM

Page 327: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1524-NFPA 72-2016 [ Section No. 29.7.9.2 ]

29.9.9.2*

Remote monitoring stations shall be permitted to verify fire alarm signals prior to reporting them to the fireservice, provided that the verification process does not delay the reporting by more than 90 seconds.

29.9.9.3

Verification shall not be permitted for signals from carbon monoxide detectors and carbon monoxidedetection systems transmitted to a fire alarm system.

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 17:22:20 EDT 2016

Committee Statement

CommitteeStatement:

Verification is extremely difficult and possibly unsafe because carbon monoxide is odorless,tasteless, and colorless. Its presence is undetectable by smell, taste, or sight, but can bedetermined only with special equipment for the purpose of measuring levels of Carbon Monoxide.

ResponseMessage:

Public Input No. 757-NFPA 72-2016 [Section No. 29.7.9.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

327 of 496 10/20/2016 11:03 AM

Page 328: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1525-NFPA 72-2016 [ Section No. 29.8.1.4 ]

29.10.1.4

The supplier or installing contractor shall provide the system owner or other responsible parties with thefollowing:

(1) An instruction booklet illustrating typical installation layouts

(2) Instruction charts describing the operation, method, and frequency of testing and maintenance offire-warning equipment

(3) Printed information for establishing an emergency evacuation plan

(4) Printed information to inform system owners where they can obtain repair or replacement service,and where and how parts requiring regular replacement, such as batteries or bulbs, can be obtainedwithin 2 weeks

(5) Information noting both of the following:

(a) Unless otherwise recommended by the manufacturer's published instructions, smoke alarmsshall be replaced when they fail to respond to tests.

(b) Smoke alarms installed in one- and two-family dwellings shall not remain in service longer than10 years from the date of manufacture shall not remain in service longer than 10 years from thedate of manufacture unless otherwise provided by manufacturer's published instructions .

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 17:33:05 EDT 2016

Committee Statement

CommitteeStatement:

This chapter is meant to be equipment specific, not occupancy specific. From a life safetyperspective, it does not matter whether the smoke alarm is located in a home, apartment or hotel,it needs to be replaced within 10 years or when the device fails an operability test.

ResponseMessage:

Public Input No. 319-NFPA 72-2016 [Section No. 29.8.1.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

328 of 496 10/20/2016 11:03 AM

Page 329: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1519-NFPA 72-2016 [ Section No. 29.8.3.4 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

329 of 496 10/20/2016 11:03 AM

Page 330: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

29.10.3.4 Specific Location Requirements.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

330 of 496 10/20/2016 11:03 AM

Page 331: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

The installation of smoke alarms and smoke detectors shall comply with the following requirements:

(1) Smoke alarms and smoke detectors shall not be located where ambient conditions, including humidityand temperature, are outside the limits specified by the manufacturer's published instructions.

(2) Smoke alarms and smoke detectors shall not be located within unfinished attics or garages or in otherspaces where temperatures can fall below 40ºF (4 4.4 ºC) or exceed 100ºF (38ºC).

(3)

(4)

(5) Smoke alarms or smoke detectors that use photoelectric detection shall be permitted for installationat a radial distance greater than 6 ft (1.8 m) from any stationary or fixed cooking appliance when bothof the following conditions are met:

(a) The kitchen or cooking area and adjacent spaces have no clear interior partitions or headers.

(b) The 10 ft (3.0 m) area of exclusion would prohibit the placement of a smoke alarm or smokedetector required by other sections of this code.

Exception: Smoke alarms or smoke detectors that use photoelectric detection shall be permittedfor installation at a radial distance greater than 6 ft (1.8 m) from any stationary or fixed cookingappliance when the following conditions are met:

  (a) The kitchen or cooking area and adjacent spaces have no clear interior partitions orheaders and

  (b) The 10 ft (3.0 m) area of exclusion would prohibit the placement of a smoke alarm orsmoke detector required by other sections of this code.

(6) Effective January 1, 2019 May 29, 2020 , smoke alarms and smoke detectors used in household firealarm systems installed between 6 ft (1.8 m) and 20 ft (6.1 m) along a horizontal flow path from astationary or fixed cooking appliance shall be listed for resistance to common nuisance sources fromcooking.

(7)

(8) Smoke alarms and smoke detectors shall not be installed within a 36 in. (910 mm) horizontal pathfrom the supply registers of a forced air heating or cooling system and shall be installed outside of thedirect airflow from those registers.

(9)

(10) Where stairs lead to other occupiable levels, a smoke alarm or smoke detector shall be located sothat smoke rising in the stairway cannot be prevented from reaching the smoke alarm or smokedetector by an intervening door or obstruction.

(11) For stairways leading up from a basement, smoke alarms or smoke detectors shall be located on thebasement ceiling near the entry to the stairs.

(12)

(13) Smoke alarms and detectors installed in rooms with joists or beams shall comply with therequirements of 17.7.3.2.4.

(14) Heat alarms and detectors installed in rooms with joists or beams shall comply with the requirementsof 17.6.3.

* Where the mounting surface could become considerably warmer or cooler than the room, such as apoorly insulated ceiling below an unfinished attic or an exterior wall, smoke alarms and smokedetectors shall be mounted on an inside wall.

* Smoke alarms and smoke detectors shall not be installed within an area of exclusion determined bya 10 ft (3.0 m) radial distance along a horizontal flow path from a stationary or fixed cookingappliance, unless listed for installation in close proximity to cooking appliances. Smoke alarms andsmoke detectors installed between 10 ft (3.0 m) and 20 ft (6.1 m) along a horizontal flow path from astationary or fixed cooking appliance shall be equipped with an alarm-silencing means or usephotoelectric detection.

* Smoke alarms and smoke detectors shall not be installed within a 36 in. (910 mm) horizontal pathfrom a door to a bathroom containing a shower or tub unless listed for installation in close proximity tosuch locations.

* Smoke alarms and smoke detectors shall not be installed within a 36 in. (910 mm) horizontal pathfrom the tip of the blade of a ceiling-suspended (paddle) fan unless the room configuration restrictsmeeting this requirement .

* For tray-shaped ceilings (coffered ceilings), smoke alarms and smoke detectors shall be installed onthe highest portion of the ceiling or on the sloped portion of the ceiling within 12 in. (300 mm)vertically down from the highest point.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

331 of 496 10/20/2016 11:03 AM

Page 332: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Supplemental Information

File Name Description

FR_1519_A.29.8.3.4_8_.docxNew annex material

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 13:22:50 EDT 2016

Committee Statement

CommitteeStatement:

List item (2) is revised to provide metric conversions consistently throughout the document.

The exception is revised to comply with the Manual of Style.

List item (5) Compliant products might not be available by January 1, 2019. The compliance dateis changed to May 29, 2020, which is the date that listing agencies have stated that products mustcomply with this requirement.

The change to list item (8) provides a means to be code compliant where it is physicallyimpossible to locate smoke alarms and detectors 36 inches or more from the tip of a fan blade.

ResponseMessage:

Public Input No. 685-NFPA 72-2016 [Section No. 29.8.3.4]

Public Input No. 759-NFPA 72-2016 [Section No. 29.8.3.4]

Public Input No. 675-NFPA 72-2016 [Section No. 29.8.3.4]

Public Input No. 550-NFPA 72-2016 [Section No. 29.8.3.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

332 of 496 10/20/2016 11:03 AM

Page 333: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1535-NFPA 72-2016 [ Section No. 29.8.4.3 ]

29.10.4.3*

Heat detectors or alarms shall be mounted on the ceiling at least 4 in. (100 mm) from a wall or on a wallwith the top of the detector or alarm not less than 4 in. (100 mm), nor more than 12 in. (300 mm), belowthe ceiling.

Exception: Where the mounting surface could become considerably warmer or cooler than the room,such as a poorly insulated ceiling below an unfinished attic or an exterior wall, the detectors or alarmsshall be mounted on an inside wall.

29.10.4.4

Where the mounting surface could become considerably warmer or cooler than the room, such as apoorly insulated ceiling below an unfinished attic or an exterior wall, the detectors or alarms shall bemounted on an inside wall.

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 12:02:42 EDT 2016

Committee Statement

Committee Statement: Exception language is revised to comply with the Manual of Style.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

333 of 496 10/20/2016 11:03 AM

Page 334: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1526-NFPA 72-2016 [ New Section after 29.8.5 ]

29.10.6 Installation and Inspection Record.

Where a form is required by the AHJ to document the installation and inspection of a household firealarm system or single- or multiple-station alarms, 7.8.2(3) shall be used to document the record ofcompletion and inspection.

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 18:11:45 EDT 2016

Committee Statement

CommitteeStatement:

The form is being moved from A.29.8.1.4 to Chapter 7 to allow for required use and to beenforceable by the AHJ.

See FR 1529.

ResponseMessage:

Public Input No. 419-NFPA 72-2016 [New Section after 29.10]

Public Input No. 400-NFPA 72-2016 [Section No. 29.10]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

334 of 496 10/20/2016 11:03 AM

Page 335: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1527-NFPA 72-2016 [ Section No. 29.11 ]

29.13 Markings and Instructions.

29.13.1 Alarms.

All alarms shall be plainly marked with the following information on the unit:

(1) Manufacturer’s or listee’s name, address, and model number

(2) A mark or certification that the unit has been approved or listed by a testing laboratory

(3) Electrical rating (where applicable)

(4) Manufacturer's published operating and maintenance instructions

(5) Test instructions

(6) Replacement and service instructions

(7) Identification Explanation of signal indicators, including identification of lights, switches, meters, andsimilar devices, regarding their function, unless their function is obvious

(8) Distinction between alarm and trouble signals on units employing both

(9) The sensitivity setting for an alarm having a fixed setting (For an alarm that is intended to be adjustedin the field, the range of sensitivity shall be indicated. The marked sensitivity shall be indicated as apercent per foot obscuration level. The marking shall include a nominal value plus tolerance.)

(10) Reference to an installation diagram and system owner’s manual

(11) Date of manufacture in the format YEAR (in four digits), MONTH (in letters), and DAY (in two digits)located on the outside of the alarm

29.13.1.1

Where space limitations prohibit inclusion of 29.13.1(4) and (6), it is not prohibited for this information tobe shall be permitted to include this information in the installation instructions instead.

29.13.2 Carbon Monoxide Alarms.

In addition to 29.13.1 , carbon monoxide alarms or detectors shall be provided with the followinginformation:

(1) Statement that indicates the unit is not suitable as a fire detector

(2) Electrical rating (if applicable)

(3) Warning that carbon monoxide is odorless, colorless, and tasteless

(4) Emergency actions to be taken

(5) Recommended replacement date

29.13.3 Fire Alarm Control Unit.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

335 of 496 10/20/2016 11:03 AM

Page 336: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

All household fire-warning equipment or systems shall be plainly marked with the following information onthe unit:

(1) Manufacturer’s or listee’s name, address, and model number

(2) A mark or certification that the unit has been approved or listed by a testing laboratory

(3) Electrical rating (where applicable)

(4) Identification of all user interface components and their functions (such as, but not limited to, lights,switches, and meters) located adjacent to the component

(5) Manufacturer's published operating and maintenance instructions

(6) Test instructions

(7) Replacement and service instructions

(8) Reference to an installation wiring diagram and homeowner’s manual, if not attached to control unit,by drawing number and issue number and/or date

Exception: Where space limitations prohibit inclusion of 29.13.3 (5) and (7), it is not prohibited forthis information to be in the installation instructions instead.

29.13.3.1

Where space limitations prohibit inclusion of 29.13.3(5) and 29.13.3(7) , it is not prohibited for thisinformation to be shall be permitted to include this information in the installation instructions instead.

Detail FR-5055

29.13.4 Carbon Monoxide Instructions.

The following information shall be included in the instructions provided with carbon monoxide alarms anddetectors:

(1) Installation instructions

(2) Operating instructions

(3) Testing instructions

(4) Maintenance instructions

(5) Replacement and service instructions

(6) Statement indicating that smoke might not be present during a carbon monoxide alarm condition

(7)

(8) Minimum and recommended distances from fuel-burning appliances

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 18:21:00 EDT 2016

Committee Statement

CommitteeStatement:

"Listing" is a defined term in the Code that covers listings (or approvals) provided by a wide rangeof certification organizations that may or may not include the word "Listed" in their certificationmark. The use of "approved" in this context is not correct, since it is defined as being acceptable tothe AHJ.

* Information on the actions to be taken in case of an alarm

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

336 of 496 10/20/2016 11:03 AM

Page 337: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Exceptions were rewritten to comply with the Manual of Style.

Requirements for carbon monoxide have been added from NFPA 720.

ResponseMessage:

Public Input No. 698-NFPA 72-2016 [Section No. 29.11]

Public Input No. 362-NFPA 72-2016 [Section No. 29.11.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

337 of 496 10/20/2016 11:03 AM

Page 338: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2506-NFPA 72-2016 [ Section No. A.3.3.6 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

338 of 496 10/20/2016 11:03 AM

Page 339: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

A.3.3.6 Acoustically Distinguishable Space (ADS).

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

339 of 496 10/20/2016 11:03 AM

Page 340: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

All parts of a building or area intended to have occupant notification are subdivided into ADSs as defined.Some ADSs might be designated to have voice communication communications capability and requirethat those communications be intelligible. Other spaces might not require voice intelligibility or might notbe capable of reliable voice intelligibility. An ADS might have acoustical design features that are conducivefor voice intelligibility, or it might be a space where voice intelligibility could be difficult or impossible toachieve. Each is still referred to as an ADS.

In smaller areas, such as those under 400 ft2 (40 m2), walls alone will define the ADS. In larger areas,other factors might have to be considered. In spaces that might be subdivided by temporary or movablepartitions, such as ballrooms and meeting rooms, each individual configuration should be considered aseparate ADS. Physical characteristics, such as a change in ceiling height of more than 20 percent, or achange in acoustical finish, such as carpet in one area and tile in another, would require those areas to betreated as separate ADSs. In larger areas, there might be noise sources that require a section to betreated as a separate ADS. Any significant change in ambient noise level or frequency might necessitatean area be considered a separate ADS.

In areas of 85 dBA or greater ambient sound pressure level, meeting the pass/fail criteria for intelligibilitymight not be possible, and other means of communication communications might be necessary. So, forexample, the space immediately surrounding a printing press or other high-noise machine might bedesignated as a separate ADS, and the design might call for some form of effective notification but notnecessarily require the ability to have intelligible voice communication communications . The aisles oroperator’s control stations might be separate ADSs where intelligible voice communication might bedesired.

Significant differences in furnishings — for example, an area with tables, desks, or low dividers, adjacentto an area with high shelving — would require separate consideration. The entire desk area could be asingle acoustic zone, whereas each area between shelving could be a unique zone. Essentially, anynoteworthy change in the acoustical environment within an area will mandate consideration of that portionof the area to be treated as an acoustic zone. Hallways and stairwells will typically be considered asindividual acoustic zones.

Spaces confined by walls with carpeting and acoustical ceilings can be deemed to be one ADS. An ADSshould be an area of consistent size and material. A change of materials from carpet to hard tile, theexistence of sound sources, such as decorative waterfalls, large expanses of glass, and changes inceiling height, are all factors that might separate one ADS from another.

Each ADS might require different components and design features to achieve intelligible voicecommunication. For example, two ADSs with similar acoustical treatments and noise levels might havedifferent ceiling heights. The ADS with the lower ceiling height might require more ceiling-mountedspeakers to ensure that all listeners are in a direct sound field (see Figure A.3.3.6). Other ADSs mightbenefit from the use of alternate speaker technologies, such as line arrays, to achieve intelligibility.

An ADS that differs from another because of the frequency and level of ambient noise might require theuse of speakers and system components that have a wider frequency bandwidth than conventionalemergency communications equipment. However, designers should not use higher bandwidth speakers inall locations, unless needed to overcome certain acoustic and ambient conditions. This is because thehigher bandwidth appliance will require more energy to perform properly. This increases amplifier and wiresize and power supply requirements.

In some spaces, it might be impractical to achieve intelligibility, and, in such a case, alternatives to voiceevacuation might be required within such areas.

Figure A.3.3.6 Illustration Demonstrating the Effect of Ceiling Height. (Source: R. P. SchifilitiAssociates, Inc.)

There might be some areas of a facility where there are several spaces of the same approximate size andthe same acoustic properties. For example, there might be an office space with multiple individual offices,each with one speaker. If one or two are satisfactorily tested, there is no need to test all of them forspeech intelligibility.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

340 of 496 10/20/2016 11:03 AM

Page 341: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 13:43:08 EDT 2016

Committee Statement

CommitteeStatement:

The word “communication” is being changed to "communications" because the plural is the properuse in this context. The term “speaker” does not need to be replaced with “Textual AudibleNotification Appliance” because this is already a sub-definition in section 3.3.172.1.2.

ResponseMessage:

Public Input No. 195-NFPA 72-2016 [Section No. A.3.3.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

341 of 496 10/20/2016 11:03 AM

Page 342: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3046-NFPA 72-2016 [ Section No. A.3.3.67 ]

A.3.3.69 Device (Class N).

Class N devices include components connected to a Class N network that monitor the environment (e.g.,smoke, heat, contact closure, manual “in case of fire” pull) and/or provide some output(s) (e.g., drycontact, audible/visual alert/notification, addressable speaker loudspeaker ) that are required to providethe real-time functionality necessary for the protection of life and property. In this way, a componentconnected to the network used for noncritical functions (i.e., maintenance) can be differentiated andexcluded from the monitoring for integrity requirements of Class N.

Also in this way, transport equipment (e.g., switches, routers, hubs, media converters) and otherequipment (e.g., printers, storage devices) can be differentiated from the requirements applied to Class Ndevices if they do not provide life safety–specific environmental monitoring, inputs, or outputs for the lifesafety system. This is not to say that this equipment is not important to the overall operation of the system,just that this equipment is not considered a “device” in the context of Class N. Equipment that does notmeet the definition of a device cannot be specifically supervised but rather generally supervised as theyare part of the supervised pathways that service the Class N devices themselves.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 15:08:06 EDT 2016

Committee Statement

Committee Statement: The Technical Committee replaces the term speaker with loudspeaker for consistency.

Response Message:

Public Input No. 196-NFPA 72-2016 [Section No. A.3.3.67]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

342 of 496 10/20/2016 11:03 AM

Page 343: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3047-NFPA 72-2016 [ Section No. A.3.3.92 ]

A.3.3.96 Endpoint (Class N).

An endpoint device originates and/or terminates a communication stream and does not forward it to otherdevices.

An FACU, ACU, ECCU endpoint originates and/or terminates a communication stream with autonomy. Ifdata is sent to or received from other locations, that communications stream forms a new path. The newpath could even employ a different communications protocol and, where permitted, have a differentpathway class designation as defined in Section 12.3.

The exception in 12.3.6(1) shows Class N communication paths do not require redundant paths whenconnected to a single endpoint device. However, a connection to an FACU, ACU, or ECCU must beredundant even when those elements are an endpoint on a Class N communication path, with theexcepted allowance of 20 ft (6 6.1 m) inside a raceway or enclosure defined in 12.6.9.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 15:25:27 EDT 2016

Committee Statement

Committee Statement: The Technical Committee edits the text to correct the conversion of 20 ft to 6.1m.

Response Message:

Public Input No. 573-NFPA 72-2016 [Section No. A.3.3.92]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

343 of 496 10/20/2016 11:03 AM

Page 344: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3044-NFPA 72-2016 [ Section No. A.3.3.103.4 ]

A.3.3.109.4 Protected Premises (Local) Fire Alarm System.

A protected premises fire alarm system is any fire alarm system located at the protected premises. It caninclude any of the functions identified in Section 23.3. Where signals are transmitted to acommunication communications center or supervising station, the protected premises fire alarm systemalso falls under the definition of one of the following systems: central station service alarm system, remotesupervising station alarm system, proprietary supervising station alarm system, or auxiliary alarm system.The requirements that pertain to these systems apply in addition to the requirements for the protectedpremises fire alarm systems.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 15:03:43 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text by replacing the term “communication” with“communications.” The term "communication(s)” was reviewed throughout the entire document forproper use regarding reference to singular and plural use. The term should be plural as used in thiscontext. This change is editorial only.

ResponseMessage:

Public Input No. 452-NFPA 72-2016 [Section No. A.3.3.103.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

344 of 496 10/20/2016 11:03 AM

Page 345: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 549-NFPA 72-2016 [ Section No. A.3.3.104 ]

A.3.3.110 Fire Command Center.

The fire command center should contain the following features as applicable to the specific facility:

(1) Emergency voice/alarm communication communications system unit

(2) Fire department communications unit

(3) Fire detection and alarm system annunciator unit

(4) Annunciator unit visually indicating the location of the elevators and whether they are operational

(5) Status indicators and controls for air-handling systems

(6) The required fire-fighter’s control panel for smoke control systems installed in the building

(7) Controls for unlocking stairway doors simultaneously

(8) Sprinkler valve and waterflow detector display panels

(9) Emergency and standby power status indicators

(10) Telephone for fire department use with controlled access to the public telephone system

(11) Fire pump status indicators

(12) Schematic building plans indicating the typical floor plan and detailing the building core, means ofegress, fire protection systems, fire-fighting equipment, and fire department access

(13) Worktable

(14) Generator supervision devices, manual start, and transfer features

(15) Public address system

(16) Other emergency systems identified in emergency response plan

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jul 29 12:28:34 EDT 2016

Committee Statement

CommitteeStatement:

As part of the Correlating Committee Task Group on terms, the term "communication(s)” wasreviewed throughout the entire document for proper use regarding reference to singular and pluraluse. The term should be plural use in this context.

ResponseMessage:

Public Input No. 453-NFPA 72-2016 [Section No. A.3.3.104]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

345 of 496 10/20/2016 11:03 AM

Page 346: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3045-NFPA 72-2016 [ Section No. A.3.3.136.1.1 ]

A.3.3.144.1.1 Emergency Control Function Interface.

See Figure A.3.3.144.1.1.

Figure A.3.3.144.1.1 Emergency Control Function Interface.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 15:05:19 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee changes the term from FACP to FACU for consistency with otherareas of NFPA 72.

Response Message:

Public Input No. 618-NFPA 72-2016 [Section No. A.3.3.136.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

346 of 496 10/20/2016 11:03 AM

Page 347: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4005-NFPA 72-2016 [ Section No. A.3.3.151 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

347 of 496 10/20/2016 11:03 AM

Page 348: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

A.3.3.159 Managed Facilities-Based Voice Network (MFVN).

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

348 of 496 10/20/2016 11:03 AM

Page 349: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Managed facilities-based voice network service is functionally equivalent to traditional PSTN-basedservices provided by authorized common carriers (public utility telephone companies) with respect todialing, dial plan, call completion, carriage of signals and protocols, and loop voltage treatment andprovides all of the following features:

(1) A loop start telephone circuit service interface.

(2) Pathway reliability that is assured by proactive management, operation, and maintenance by theMFVN provider.

(3) 8 hours of standby power supply capacity for MFVN communications equipment either located at theprotected premises or field deployed. Industry standards followed by the authorized common carriers(public utility telephone companies), and the other communications service providers that operateMFVNs, specifically engineer the selection of the size of the batteries, or other permanently locatedstandby power source, in order to provide 8 hours of standby power with a reasonable degree ofaccuracy. Of course, over time, abnormal ambient conditions and battery aging can always have apotentially adverse effect on battery capacity. The MFVN field-deployed equipment typically monitorsthe condition of the standby battery and signals potential battery failure to permit the communicationsservice provider to take appropriate action.

(4) 24 hours of standby power supply capacity for MFVN communications equipment located at thecommunication communications service provider’s central office.

(5) Installation of network equipment at the protected premises with safeguards to prevent unauthorizedaccess to the equipment and its connections.

When providing telephone service to a new customer, MFVN providers give notice to the telephoneservice subscriber of the need to have any connected alarm system tested by authorized fire alarmservice personnel in accordance with Chapter 14 to make certain that all signal transmission featureshave remained operational. These features include the proper functioning of line seizure and thesuccessful transmission of signals to the supervising station. In this way, the MFVN providers assist theirnew customers in complying with a testing procedure similar to that outlined in 26.2.7 for changes toproviders of supervising station service.

The evolution of the deployment of telephone service has moved beyond the sole use of metallicconductors connecting a telephone subscriber’s premises with the nearest telephone service provider’scontrol and routing point (wire center). In the last 25 years, telephone service providers have introduced avariety of technologies to transport multiple, simultaneous telephone calls over sharedcommunication’s communication pathways. In order to facilitate the further development of themodernization of the telephone network, the authorized common carriers (public utility telephonecompanies) have transitioned their equipment into a managed facilities-based voice network (MFVN)capable of providing a variety of communications services in addition to the provision of traditionaltelephone service.

Similarly, the evolution of digital communications technology has permitted entities other than theauthorized common carriers (public utility telephone companies) to deploy robust communicationsnetworks and offer a variety of communications services, including telephone service.

These alternate service providers fall into two broad categories. The first category includes those entitiesthat have emulated the MFVN provided by the authorized common carriers. The second category includesthose entities that offer telephone service using means that do not offer the rigorous quality assurance,operational stability, and consistent features provided by an MFVN.

The Code intends to only recognize the use of the telephone network transmission of alarm, supervisory,trouble, and other emergency signals by means of MFVNs.

For example, the Code intends to permit an MFVN to provide facilities-based telephone (voice) servicethat interfaces with the premises fire alarm or emergency signal control unit through a digital alarmcommunicator transmitter (DACT) using a loop start telephone circuit and signaling protocols fullycompatible with and equivalent to those used in public switched telephone networks. The loop starttelephone circuit and associated signaling can be provided through traditional copper wire telephoneservice (POTS — “plain old telephone service”) or by means of equipment that emulates the loop starttelephone circuit and associated signaling and then transmits the signals over a pathway using packetswitched (IP) networks or other communications methods that are part of an MFVN.

Providers of MFVNs have disaster recovery plans to address both individual customer outages andwidespread events such as tornados, ice storms, or other natural disasters, which include specific network

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

349 of 496 10/20/2016 11:03 AM

Page 350: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

power restoration procedures equivalent to those of traditional landline telephone services.

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 12:18:33 EDT 2016

Committee Statement

CommitteeStatement:

As part of the Correlating Committee Task Group on terms, the term "communication(s)” wasreviewed throughout the entire document for proper use regarding reference to singular and pluraluse. The term should be plural use in this context.

ResponseMessage:

Public Input No. 454-NFPA 72-2016 [Section No. A.3.3.151]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

350 of 496 10/20/2016 11:03 AM

Page 351: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2507-NFPA 72-2016 [ Section No. A.3.3.172.1.2 ]

A.3.3.180.1.2 Textual Audible Notification Appliance.

An example of a textual audible notification appliance is a speaker an electrical acoustic transducer thatreproduces a voice message or tone signal, such as a speaker .

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 13:52:52 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee does not want to describe an appliance with the term “appliance” assuggested in the PI. The revision is being made to provide a more accurate description of theterm.

ResponseMessage:

Public Input No. 197-NFPA 72-2016 [Section No. A.3.3.172.1.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

351 of 496 10/20/2016 11:03 AM

Page 352: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1014-NFPA 72-2016 [ Section No. A.3.3.240.1 ]

A.3.3.248.1 Alarm Response.

Examples include the actuation of alarm notification appliances, elevator recall, smoke control measures,emergency responder dispatch, and deployment of resources in accordance with a risk analysis and theassociated emergency response action plan, and so forth .

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 21:48:39 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee modifies the existing language to utilize the term "emergencyresponse plan" as currently defined in NFPA 72.

ResponseMessage:

Public Input No. 489-NFPA 72-2016 [Section No. A.3.3.240.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

352 of 496 10/20/2016 11:03 AM

Page 353: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 550-NFPA 72-2016 [ Section No. A.7.3.2 ]

A.7.3.2

Design (layout) documents should contain information related to the system that could includespecifications, shop drawings, input/output matrix, battery calculations, notification appliance voltage dropcalculations for strobes visible notification appliances and speakers, and product technical data sheets.

Design (layout) documents could include such items as preliminary plans issued as guidance anddirection, risk analysis, emergency response plan, or a combination of these.

Deviations from requirements of governing laws, codes, standards, or preliminary plan requirementsspecified by an engineer should be clearly identified and documented as such.

Documentation of equivalency, where applicable, should be provided in accordance with Section 1.5 andbe included with the record drawings.

It is the intent that existing systems that are altered should have design (layout) documents prepared thatare applicable only to the portion(s) of the system being altered.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jul 29 12:31:52 EDT 2016

Committee Statement

CommitteeStatement:

For uniformity throughout the document, the term “strobe” is replaced with “visible notificationappliance”. Further it is understood that SIG-NAS is reviewing the terms “visual” and “visible” andSIG-ECS requests the Correlating Committee to review and take appropriate actions. The proposalto change the term speaker was not made in order to keep in current alignment with the termsloudspeaker/speaker. The Technical Committee requests the Correlating Committee review thisaction across all Technical Committees.

ResponseMessage:

Public Input No. 198-NFPA 72-2016 [Section No. A.7.3.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

353 of 496 10/20/2016 11:03 AM

Page 354: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1032-NFPA 72-2016 [ Section No. A.7.7.2.3 ]

A.7.7.2.3

The intent is that paper and/or electronic documents should not be stored inside the control unit becausecontrol units are not typically approved for the storage of combustible material.

Examples of system documents include the following:

(1) Record drawings (as-builts)

(2) Equipment technical data sheets

(3) Alternative means and methods, variances, appeals, and approvals, and so forth

(4) Performance-based design documentation in accordance with 7.3.7

(5) Risk analysis documentation in accordance with 7.3.6

(6) Emergency response plan in accordance with 7.3.8

(7) Evaluation documentation in accordance with 7.3.9

(8) Software and firmware control documentation in accordance with 23.2.2

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 23:38:11 EDT 2016

Committee Statement

CommitteeStatement:

The storage of paperwork, manuals, software, etc. within control unit cabinets is stillcommonplace and presents a very real fire hazard. Documents must not be stored within thesecabinets regardless of whether they are paper or electronic format.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

354 of 496 10/20/2016 11:03 AM

Page 355: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1025-NFPA 72-2016 [ Section No. A.10.4.1 ]

A.10.4.1

Fire alarm specifications can include some or all of the following:

(1) Address of the protected premises

(2) Owner of the protected premises

(3) Authority having jurisdiction

(4) Applicable codes, standards, and other design criteria to which the system is required to comply

(5) Type of building construction and occupancy

(6) Fire department response point(s) and annunciator location(s)

(7) Type of fire alarm system to be provided

(8) Calculations (e.g., secondary supply and voltage drop calculations)

(9) Type(s) of fire alarm initiating devices, supervisory alarm initiating devices, and evacuation notificationappliances to be provided

(10) Intended area(s) of coverage

(11) Complete list of detection, evacuation signaling, and annunciator zones

(12) Complete list of emergency control functions

(13) Complete sequence of operations detailing all inputs and outputs

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 22:48:50 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee removes the term “evacuation” to include all signaling and toimprove consistency and grammar.

ResponseMessage:

Public Input No. 705-NFPA 72-2016 [Section No. A.10.4.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

355 of 496 10/20/2016 11:03 AM

Page 356: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1046-NFPA 72-2016 [ Section No. A.10.6.7.2.1.1 ]

A.10.6.7.2.1.1

The 20-percent minimum reserved capacity safety margin is intended to address both normal aging andeffects of on battery loading. Some systems with a high rate of alarm signaling battery discharge mightrequire a greater safety margin. Battery calculations should take into account a discharge factor resultingfrom the discharge of batteries at a greater rate than the one specified in the battery data provided by themanufacturer. For example, valve-regulated lead-acid (VRLA) batteries are typically assigned a 20-hourdischarge rate (C/20). Any rate greater than C/20 requires using the manufacturer's formula or dischargefactor table. capacity. As a battery ages, rated capacity will decrease to 80 percent, which is consideredthe end of service life. As a minimum, a 20 percent correction factor should be applied for aging to ensurethe battery can meet its current demand at the end of service life. At initial installation, battery capacitycould be as low as 90 percent and should gradually increase when subjected to several deepdischarge/charging cycles or remaining on float-charge for several weeks. For additional information onbattery sizing considerations, refer to IEEE 485 , Recommended Practice for Sizing Lead-Acid Batteriesfor Stationary Applications.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 17:25:47 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises the text to clarify terminology and includes reference toIEEE 485 for additional information.

ResponseMessage:

Public Input No. 144-NFPA 72-2016 [Section No. A.10.6.7.2.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

356 of 496 10/20/2016 11:03 AM

Page 357: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1048-NFPA 72-2016 [ Section No. A.10.6.10 ]

A.10.6.10

The following newer types valve-regulated lead-acid (VRLA) battery type of rechargeable batteries arenormally battery is currently used in protected premises applications.:

Vented Lead-Acid, Gelled, or Starved Electrolyte Battery. This rechargeable-type battery isgenerally used in place of primary batteries in applications that have a relatively high current drainor that require the extended standby capability of much lower currents. The nominal voltage of asingle cell is 2 volts, and the battery is available in multiples of 2 volts (e.g., 2, 4, 6, 12). Batteriesshould be stored according to the manufacturer’s published instructions.

Nickel-Cadmium Battery. The sealed-type nickel-cadmium battery generally used in applicationswhere the battery current drain during a power outage is low to moderate (typically up to a fewhundred milliamperes) and is fairly constant. Nickel-cadmium batteries are also available in muchlarger capacities for other applications. The nominal voltage per cell is 1.42 volts, with batteriesavailable in multiples of 1.42 (e.g., 12.78, 25.56). Batteries in storage can be stored in any state ofcharge for indefinite periods. However, a battery in storage will lose capacity (will self-discharge),depending on storage time and temperature. Typically, batteries stored for more than 1 monthrequire an 8-hour to 14-hour charge period to restore capacity. In service, the battery should receivea continuous, constant-charging current that is sufficient to keep it fully charged. (Typically, thecharge rate equals 1 ⁄10 to 1 ⁄20 of the ampere-hour rating of the battery.) Because batteries aremade up of individual cells connected in series, the possibility exists that, during deep discharge,one or more cells that are low in capacity will reach complete discharge prior to other cells. Thecells with remaining life tend to charge the depleted cells, causing a polarity reversal resulting inpermanent battery damage. This condition can be determined by measuring the open cell voltageof a fully charged battery (voltage should be a minimum of 1.28 volts per cell multiplied by thenumber of cells). Voltage depression effect is a minor change in discharge voltage level caused byconstant current charging below the system discharge rate. In some applications of nickel-cadmiumbatteries (e.g., battery-powered shavers), a memory characteristic also exists. Specifically, if thebattery is discharged daily for 1 minute, followed by a recharge, operation for 5 minutes will notresult in the rated ampere-hour output because the battery has developed a 1-minute dischargememory.

Sealed Lead-Acid Battery. In a sealed lead-acid battery, the electrolyte is totally absorbed by theseparators, and no venting normally occurs. Gas evolved during recharge is internally recombined,resulting in minimal loss of capacity life. A high-pressure vent, however, is provided to avoiddamage under abnormal conditions.

This rechargeable-type battery is generally used in place of primary batteries in applications that have arelatively high current drain or that require the extended standby capability of much lower currents. Thenominal voltage of a single starved electrolyte cell is 2 volts, and the battery is available in multiples of2 volts (e.g., 2, 4, 6, 12). Batteries should be stored according to the battery manufacturer’s publishedinstructions. These batteries are often incorrectly referred to as “sealed lead-acid,” “gel” or“maintenance-free batteries.”

There are two technologies available. The most common type is referred to as “absorbed glass mat” orAGM. In this technology, the electrolyte is immobilized by being absorbed into fiberglass mats thatsurround the plates. Nearly all VRLA batteries in use in U.S. fire protection applications are AGM.

The second technology is referred to as gelled electrolyte. In this technology, the electrolyte isimmobilized in a silica gel. This technology is predominately seen in European applications. While somemanufacturers refer to the battery as a gel battery in the literature, this needs to be confirmed by thetechnician. Gel batteries require higher float voltages than AGM, and floating an AGM battery at gelvoltages will shorten the battery life.

Submitter Information Verification

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

357 of 496 10/20/2016 11:03 AM

Page 358: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 17:33:26 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises the annex text to utilize the correct terminology for batterytechnology.

Response Message:

Public Input No. 151-NFPA 72-2016 [Section No. A.10.6.10]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

358 of 496 10/20/2016 11:03 AM

Page 359: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1050-NFPA 72-2016 [ Section No. A.10.6.10.3.4 ]

A.10.6.10.3.4

Batteries The circuitry and methods for charging batteries of various types are to be evaluated by anationally recognized testing laboratory to ensure they are appropriate for the purpose. During primarypower use, batteries are trickle-charged if they are off-line and waiting to be put under load in the event ofa loss of power.

Float-charged batteries are fully charged and connected across the output of the rectifiers to smooth theoutput and to serve as a standby source of power in the event of a loss of line power. Other chargingmethods are used to restore capacity to a battery after it has been utilized during a loss of primary power.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 06:48:16 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises the annex text to better reflect actual practice forcharging batteries.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

359 of 496 10/20/2016 11:03 AM

Page 360: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1024-NFPA 72-2016 [ Section No. A.10.11.2 ]

A.10.11.2

The intent of this requirement is to ensure that hearing-impaired persons who are deaf or hard of hearingare alerted to seek additional information regarding an emergency situation. Hearing-impaired personsmight not be Persons who are deaf or hard of hearing are not always alerted by the speaker notificationappliances loudspeakers that provide evacuation tones or voice instructions. It is intended that thespeakers loudspeakers and visible devices notification appliances located in the same area be activatedtogether whenever tones, recorded voice instructions, or live voice instructions are being provided.

Submitter Information Verification

Submitter Full Name: SIG-FUN

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 25 22:45:10 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises the text to replace the term “speakers” with “loudspeakers”.Also, “hearing-impaired person” is replaced by “person who is deaf or hard of hearing” forconsistency throughout the Code.

ResponseMessage:

Public Input No. 200-NFPA 72-2016 [Section No. A.10.11.2]

Public Input No. 647-NFPA 72-2016 [Section No. A.10.11.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

360 of 496 10/20/2016 11:03 AM

Page 361: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3053-NFPA 72-2016 [ Section No. A.12.2.1 ]

A.12.2.1

In the 2007 edition of NFPA 72, initiating device circuit, signaling line circuit, and notification appliancecircuit performance class/style tables were rooted in “copper” wiring methods. Fire alarm control units usenew communication communications technologies, such as Ethernet, fiber optics, and wireless, which donot fit in the “copper” wiring methods.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 15:41:04 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text by replacing the term “communication” with“communications.” The term "communication(s)” was reviewed throughout the entire document forproper use regarding reference to singular and plural use. The term should be plural as used in thiscontext. This change is editorial only.

ResponseMessage:

Public Input No. 455-NFPA 72-2016 [Section No. A.12.2.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

361 of 496 10/20/2016 11:03 AM

Page 362: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3007-NFPA 72-2016 [ Section No. A.12.3.6(1) ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

362 of 496 10/20/2016 11:03 AM

Page 363: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

A.12.3.6(1)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

363 of 496 10/20/2016 11:03 AM

Page 364: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

The Class N pathway designation is added to specifically address the use of modern networkinfrastructure when used in fire alarm and emergency communication systems.

Class N networks can be specified for ancillary functions but are not required for supplemental reportingdescribed in 23.12.4. [See Figure A.23.12.4].

Ethernet network devices are addressable but with an important distinction from device addresses on atraditional SLC multi-drop loop. A device with an Ethernet address is, in most cases, a physical endpointconnected to a dedicated cable. Traditional SLC devices are all wired on the same communication line (inparallel), similar to an old party-line telephone system. By comparison, Ethernet’s network switches directeach data packet to its intended recipient device like our modern phone systems.

Class N uses redundant paths as a means to compensate for Ethernet wiring that does not report a singleconnection to ground, a basic requirement of Class B. Thus, the physical separation of Class A andClass X, and equipment redundancy described in 12.3.7, is not inherently required of Class N. In otherwords, failure of a single switch is permitted take down a class N segment and is only required to reportthe loss of communication. Where redundant path segments are intended to have survivability similar toClass A or Class X, the physical separation requirements and overall equipment redundancy must bespecified in addition to the Class N designation.

As a visual model, Class N could be likened to a redundant pathway backbone, allowed to have Class Cbranch paths to single endpoint devices. Therefore, every effort is made in this section to clearlydistinguish the single endpoint device from the transport equipment required to have redundant paths.

Class N requires redundant, monitored pathway segments to and from control equipment (fire alarmcontrol units, ACUs, or ECCUs) where any interruption in communications could potentially affect multipleendpoint devices. Typically, interconnected communications equipment such as Ethernet switches,wireless repeaters, or media converters are used in combination to create pathways. Chapter 12describes the required behavior of Class N pathways. All equipment must meet the requirements of otherchapters in NFPA 72 (such as, but not limited to, requirements pertaining to secondary power supplies,equipment listings, and environment conditions).

Redundant pathways, isolated from ground, are actually common practice in robust Ethernet designs.Managed network switches commonly have specific uplink ports that are intended for load sharing andallow two parallel connections. For compliance with Class N, a trouble must be reported if either of theseconnections fails. [See Figure A.12.3.6(1)(a) and Figure A.12.3.6(1)(b).]

Class N pathways can use metallic conductor communications cable, such as a 100 ohm balancedtwisted pair (e.g., Category 5E), including single-pair or multi-pair cable, or other communications media,such as optical fiber cable or wireless transmission, or a combination of two or more such transportmediums.

Where a conductor-based media is used for Class N, the intention is not to monitor faults on individualconductors but rather to monitor the operational capability and performance of the pathway as a whole.Similar to Class C, end-to-end verification is used in Class N.

Primary and required redundant pathways are independently and continuously verified for their ability tosupport end-to-end communications to and from each endpoint device and its associated controlequipment. Pathway segments that service more than one device must have at least one verifiedredundant pathway segment. Should any primary pathway segment fail, communication is supported bythe redundant pathway segment(s.) Failure of either a primary or redundant pathway will indicate atrouble.

Redundant pathway segments are generally independent and do not normally share media with theprimary pathways. However, there are exceptions, such as different frequencies for wireless components,or ring topologies. [See Figure A.12.3.6(5).]

A Class N network can be made more reliable with physically distinct pathway segments (i.e., an alternateconduit, or cable tray route, or wireless transmission frequency range, or a combination of distinct media).In addition to the required primary segments and redundant segments, a Class N pathway is permitted tohave nonrequired segments. [See Figure A.12.3.6(1)(c).] Additional nonrequired pathway segments areallowed to be connected and not independently monitored for integrity as long as two paths are monitoredto meet the redundancy requirement of Class N.

Figure A.12.3.6(1)(a) Class N Pathway Block Diagram – Example 1.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

364 of 496 10/20/2016 11:03 AM

Page 365: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Figure A.12.3.6(1)(b) Class N Pathway Block Diagram – Example 2.

Traditionally, NFPA has used the word device for input components and the term appliance forcomponents used in notification. With respect to Class N, the term device includes appliances and otherintelligent, addressable components that perform a programmable input or output function. Examples ofClass N devices include the following:

(1) Input components such as alarm initiating modules switches and sensors

(2) Output components such as output modules, Ethernet speakers (i.e., IEEE 802.3af PoEspeakers loudspeakers ), intelligent strobes, textual signage, and intelligent audio amplifiers

Transmission equipment components (e.g., media converters, Ethernet switches, patch panels, cross-connects) are connected to the Class N pathway merely to transport instructions between otherequipment. As such, they are not considered devices with respect to Class N pathways.

The audio amplifier listed above is an example of an addressable device that can receive a digital audioinput from the Class N pathway and then provide a notification appliance circuit (NAC) output withClass A, B, or X pathways. Other endpoint devices can similarly provide alternate class pathways forstrobes (NACs) or initiating devices (IDCs). From the perspective of the Class N pathway, communicationsterminates terminate at this endpoint device. However, since these types of endpoints can supportmultiple notification appliance devices or initiating devices, path segments are subject to the redundantpathway requirement unless protected in an enclosure or raceway less than 20 ft (6 m) in length. [SeeFigure A.12.3.6(1)(c) .]

Figure A.12.3.6(1)(c) Class N Pathway to Endpoint with Multiple Devices.

Class N connections between control equipment are required to have redundant monitored pathwaysegments if a failure of a primary pathway segment in between control equipment could impair theoperation of the control equipment. [See Figure A.12.3.6(1)(d).]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

365 of 496 10/20/2016 11:03 AM

Page 366: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Figure A.12.3.6(1)(d) Class N Pathway Block Diagram with Multiple Control Units.

Class N is also permitted to include dual port devices that provide both transmission and input/outputfunctions. Endpoint devices can have multiple connection ports and support dual pathway segmentconnections; thus the term endpoint device is not intended to prohibit more than one connection to adevice. Even with dual connections, where other devices depend on the path, primary and redundantpaths are required. But, where an endpoint device has two connection ports, and when a secondarynonrequired connection is added, there is no requirement to separately supervise the nonrequiredredundant pathway segment. [See Figure A.12.3.6(1)(e).]

Figure A.12.3.6(1)(e) Class N Pathway Block Diagram with Device with Dual Pathway Connection.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Aug 04 09:28:19 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee replaces the term “terminates” in the third to last paragraph to “terminate”for grammatical correctness. The Technical Committee does not replace the term “speaker” with“textual audible notification appliance” nor the term “strobe” with “visible notification appliance” as theintended use of both terms is clear. However, the term “speaker” is replaced by the term“loudspeaker” as this is the preferred terminology. The Technical Committee also directs NFPA staffto replace the term “speaker” in Figure A.12.3.6(1)(c) with the preferred term “loudspeaker.”

ResponseMessage:

Public Input No. 201-NFPA 72-2016 [Section No. A.12.3.6(1)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

366 of 496 10/20/2016 11:03 AM

Page 367: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3066-NFPA 72-2016 [ Section No. A.12.4.3 ]

A.12.4.3

Methods of survivability protection might alternate within a protected premise. For example, 2-hourresistive fire-resistive cable might extend from a 2-hour fire-rated fire-resistance-rated enclosure.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Sun Aug 07 13:45:14 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text to incorporate consistent terminology forconsistency and clarity.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

367 of 496 10/20/2016 11:03 AM

Page 368: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3054-NFPA 72-2016 [ Section No. A.12.4.3(4) ]

A.12.4.3(4)

A performance-based alternative is needed because it is possible to construct a nonsprinklered, TypeV(000) building that employs relocation or partial evacuation (e.g., a single-story ambulatory health careoccupancy) that would not warrant either a 2-hour fire resistance–rated fire-resistive-rated enclosure or a2-hour cable. Examples of performance alternatives that might be considered in a design for survivabilityare a strategic application of Class A, Class X, or Class N segments and also wirelesscommunication communications pathways.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 15:46:31 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text by replacing the term “communication” with“communications.” The term "communication(s)” was reviewed throughout the entire document forproper use regarding reference to singular and plural use. The term should be plural as used in thiscontext. This change is editorial only. The Technical Committee aligns the different references torated cables and enclosures. These changes are editorial only.

ResponseMessage:

Public Input No. 668-NFPA 72-2016 [Sections A.12.4.3, A.12.4.3(4), A.12.4.4(4)]

Public Input No. 458-NFPA 72-2016 [Section No. A.12.4.3(4)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

368 of 496 10/20/2016 11:03 AM

Page 369: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3055-NFPA 72-2016 [ Section No. A.12.4.4(4) ]

A.12.4.4(4)

A performance-based alternative is needed because it is possible to construct a sprinklered single-storyType V(111) or multistory Type II(111) building that employs relocation or partial evacuation (e.g., a healthcare occupancy) that would not warrant either a 2-hour fire resistance–rated fire-resistive-rated enclosureor a 2-hour cable (a 1-hour enclosure would suffice). Examples of performance alternatives that might beconsidered in a design for survivability are a strategic application of Class A, Class X, or Class Nsegments and also wireless communication communications pathways.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 15:49:27 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text by replacing the term “communication” with“communications.” The term "communication(s)” was reviewed throughout the entire document forproper use regarding reference to singular and plural use. The term should be plural as used in thiscontext. This change is editorial only. The Technical Committee aligns the different references torated cables and enclosures. These changes are editorial only.

ResponseMessage:

Public Input No. 459-NFPA 72-2016 [Section No. A.12.4.4(4)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

369 of 496 10/20/2016 11:03 AM

Page 370: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3056-NFPA 72-2016 [ Section No. A.12.5 ]

A.12.5

Shared pathway designations propose a list of shared pathways, some of which are only allowable fornonrequired functions. Other sections of this Code determine which of the shared pathways are allowed tobe used as paths for required fire alarm signaling. Refer to 23.8.2.6 for sharedcommunication communications requirements.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 15:55:04 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text by replacing the term “communication” with“communications.” The term "communication(s)” was reviewed throughout the entire document forproper use regarding reference to singular and plural use. The term should be plural as used in thiscontext. This change is editorial only.

ResponseMessage:

Public Input No. 460-NFPA 72-2016 [Section No. A.12.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

370 of 496 10/20/2016 11:03 AM

Page 371: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4524-NFPA 72-2016 [ Section No. A.14.4.3.2 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

371 of 496 10/20/2016 11:03 AM

Page 372: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

A.14.4.3.2

Table 14.4.3.2, Item 17. Where the manufacturer publishes limits of accuracy for the operation of aninitiating device, the test method should verify actuation is within the tolerances provided.

Table 14.4.3.2 Item 22(a 1 ) and 22(b 2 ). If, during the course of the periodic test of audible appliances,it is suspected that alarm sound levels could be lower than the required minimum, the system owner orthe system owner's designated representative should be notified in writing by official correspondence .Such notification will allow the building owner or designated building representative to determine whethersound pressure level readings should be taken for the area(s) in question.

Table 14.4.3.2, Item 24. The extent of testing of a fire alarm or signaling system, including devices thatwere not tested, should be documented in accordance with the Test Plan test plan in 14.2.10. NFPA 72does not require testing of an emergency control function, such as elevator recall, but does require testingof the emergency control function interface device, such as the relay powered by the fire alarm orsignaling system. Where the emergency control function is not being tested concurrent with the fire alarmor signaling system testing, measurement of the emergency control function interface device outputshould be verified using the proper test devices. This might require reading or observing the condition of arelay, a voltage measurement, or the use of another type of test instrument. Once testing is complete,verification that any disabled or disconnected interface devices have been restored to normal is essential,and this verification should be documented in the testing results.

Testing of the emergency control functions themselves is outside of the scope of NFPA 72. A completeend-to-end test that demonstrates the performance of emergency control functions activated by the firealarm or signaling system might be required by some other governing laws, codes, or standards, or theauthority having jurisdiction. In that situation, other applicable installation standards and designdocuments, not NFPA 72, would address testing and performance of the emergency control functions.NFPA 4 provides requirements for integrated (end-to-end) system testing.

It is important to note that the appropriate NFPA standard would provide the acceptance criteria for theoverall emergency control function operation requirements, including performance and test methods, whileNFPA 72 covers the required performance and testing of the emergency function interface device.

For instance, if an end-to-end test for a building with an engineered smoke control system is required bysome other governing laws, codes, standards, or the authority having jurisdiction, the test protocol wouldhave unique criteria for the smoke control system design, and a special inspector would be responsible forthe overall operation and performance of the smoke control system in accordance with the appropriatestandard (NFPA 92 and NFPA 101) during the testing, including measuring pressure differentials andensuring proper fan and damper operation. Refer to the following extract from NFPA 101 on smokecontrol:

9.3.2 System Designer. The engineer of record shall clearly identify the intent of the system, the designmethod used, the appropriateness of the method used, and the required means of inspecting, testing, andmaintaining the system. [101: 9.3.2]

9.3.3 Acceptance Testing. Acceptance testing shall be performed by a special inspector in accordancewith Section 9.13. [101: 9.3.3]

Even though the fire alarm or signaling system initiating device might activate the smoke control system,the actual testing of the dampers and fan operation would be as required by the smoke control design andnot part of the fire alarm or signaling system.

Other emergency control operation requirements might be as follows: For fan shutdown and smokedamper operation, the fan and damper operations would be in accordance with NFPA 90A and NFPA 105respectively, and those equipment operations would be verified by those responsible for HVAC systems incombination with the fire alarm system personnel. Guidance for elevator inspection and testing can befound in ASME A.17.2, Guide for Inspection of Elevators, Escalators and Moving Walks. For elevatorsystems, the recall function, elevator power shutdown, and hat illumination would be done with theelevator mechanics present during the test. This operational test is often accomplished during routineperiodic fire alarm testing. For fire door holder and fire shutter release, it would be expected that theemergency control function operation of the doors/shutters would be verified in accordance with NFPA 80and NFPA 101 during the test. In some cases, the door manufacturer representative might need to bepresent to reset the equipment.

Submitter Information Verification

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

372 of 496 10/20/2016 11:03 AM

Page 373: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jul 29 13:38:20 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits text to be consistent with the new proposed definition of officialcorrespondence.

The Technical Committee provides new language in the Annex to address the need to take intoaccount manufacturer tolerances for equipment operability, especially where environmentalconditions are not optimal.

ResponseMessage:

Public Input No. 26-NFPA 72-2015 [Section No. A.14.4.3.2]

Public Input No. 209-NFPA 72-2016 [Section No. A.14.4.3.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

373 of 496 10/20/2016 11:03 AM

Page 374: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4519-NFPA 72-2016 [ Section No. A.14.4.5.5 ]

A.14.4.5.5

Carbon monoxide alarm replacement is covered under NFPA 720 .

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jul 29 12:27:19 EDT 2016

Committee Statement

CommitteeStatement:

Annex material was removed due to NFPA 720 being withdrawn. The Correlating Committee isrequested to forward to SIG-HOU for concurrence.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

374 of 496 10/20/2016 11:03 AM

Page 375: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4531-NFPA 72-2016 [ Section No. A.14.6.2.4 ]

A.14.6.2.4

One method used to define the required sequence of operations and to document the actual sequence ofoperations is an input/output matrix (see Figure A.14.6.2.4).

Figure A.14.6.2.4 Typical Input/Output Matrix.

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 02 21:50:39 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee modifies column GG and replaces "exterior strobe" with "exterior visiblenotification appliance".

This is done as part of the Correlating Committee Task Group on terms, the term "light" and “strobe”was reviewed throughout the entire document for proper use. In some cases it refers to a physicalappliance while other sections use it to refer to the output of an appliance. In this section the term isfor an appliance and the proper term "visible notification appliance" should be used.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

375 of 496 10/20/2016 11:03 AM

Page 376: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ResponseMessage:

Public Input No. 279-NFPA 72-2016 [Section No. A.14.6.2.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

376 of 496 10/20/2016 11:03 AM

Page 377: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2019-NFPA 72-2016 [ Section No. A.17.5.3.1.4 ]

A.17.5.3.1.4

Total coverage requires that a fire above the suspended ceiling be detected. Detector spacing andlocation for above ceiling spaces are addressed in 17.7.3.5.2. If that above-ceiling space is used as an airreturn plenum, this detection can be provided either by smoke detectors placed in accordance with17.7.4.2 or where the air leaves the smoke compartment in accordance with 17.7.5.4.2.2.

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 20:21:52 EDT 2016

Committee Statement

CommitteeStatement:

A Correlating Committee Task Group on language/terms reviewed the language of the Code forconsistency and grammar.

The Technical Committee revises the “above ceiling" phrase to add a hyphen to clarify the intentbecause the term comes before a noun and intends to modify and act as a single idea.Additionally, to be consistent with usage elsewhere in the same clause.

ResponseMessage:

Public Input No. 639-NFPA 72-2016 [Section No. A.17.5.3.1.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

377 of 496 10/20/2016 11:03 AM

Page 378: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2537-NFPA 72-2016 [ Section No. A.18.3.3.2 ]

A.18.3.3.2

The intent is to prohibit labeling that could give an incorrect message. Wording such as “Emergency”would be acceptable for labeling because it is generic enough not to cause confusion. Fire alarm systemsare often used as emergency notification systems, and therefore attention should be given to this detail.

Combination audible and visible units may have several visible appliances, visual notification appliancesare permitted to have multiple visual elements each labeled differently or not labeled at all.

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 18:21:38 EDT 2016

Committee Statement

CommitteeStatement:

The term “may” is removed in order to comply with the Manual of Style. The term “visual” wasused instead of “visible” because it is a more appropriate term.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

378 of 496 10/20/2016 11:03 AM

Page 379: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2540-NFPA 72-2016 [ Section No. A.18.4.1.2 ]

A.18.4.1.2

The maximum sound pressure level permitted in a space is 110 dBA, reduced from 120 dBA in previouseditions. The change from 120 dBA to 110 dBA is to coordinate with other laws, codes, and standards.

In addition to the danger of exposure to a high sound level, long-term exposure to lower levels may alsobe a problem when, for example, occupants must traverse long egress paths to exit or technicians testlarge systems over extended time periods.

This Code does not presume to know how long a person will be exposed to an audible notificationsystem. The limit of 110 dBA has been set as a reasonable upper limit for the performance of a system.For workers who may be exposed to high sound levels over the course of a 40-year employment history,OSHA (Occupational, Health and Safety Administration) has established a maximum permitted dosebefore a hearing conservation program must be implemented. A worker exposed to 120 dBA for7.5 minutes a day for 40 years might be in danger of suffering a hearing impairment. The OSHAregulation includes a formula to calculate a dose for situations where a person is exposed to differentsound levels for different periods of time. The maximum permitted by the regulation is an 8-hourequivalent dose of 90 dBA. It is possible to calculate the dose a person experiences when traversing anegress path where the sound pressure level varies as he/she passes close to, then away from, audibleappliances. Table A.18.4.1.2 depicts OSHA permissible noise exposures.

Table A.18.4.1.2 Permissible Noise Exposures

Duration

(hr)

L A

(dBA)

8 90

6 92

4 95

3 97

2 100

1.5 102

1 105

0.5 110

0.25 115

0.125 (7.5 minutes) 120

Source: OSHA, 29 CFR 1910.5, Table G-16, Occupational Noise Exposure.

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 19:15:46 EDT 2016

Committee Statement

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

379 of 496 10/20/2016 11:03 AM

Page 380: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

CommitteeStatement:

The Technical Committee believes that explaining the change from 120 to 110 dBA is nolonger necessary.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

380 of 496 10/20/2016 11:03 AM

Page 381: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2530-NFPA 72-2016 [ Section No. A.18.4.3 ]

A.18.4.4

The typical average ambient sound level for the occupancies specified in Table A.18.4.4 are intended onlyfor design guidance purposes. The typical average ambient sound levels specified should not be used inlieu of actual sound level measurements.

Table A.18.4.4 Average Ambient Sound Level According to Location

LocationAverage Ambient

Sound Level (dBA)

Business occupancies 55 54

Educational occupancies 45

Industrial occupancies 80 88

Institutional occupancies 50

Mercantile occupancies 40

Mechanical rooms 85 91

Piers and water-surrounded structures 40

Places of assembly 55 60

Residential occupancies 35

Storage occupancies 30

Thoroughfares, high-density urban 70

Thoroughfares, medium-density urban 55

Thoroughfares, rural and suburban 40

Tower occupancies 35

Underground structures and windowless buildings 40

Vehicles and vessels 50

Sound levels can be significantly reduced due to distance and losses through building elements. Everytime the distance from the source doubles, the sound level decreases by about 6 decibels (dB). Audiblenotification appliances are typically rated by manufacturers' and testing agencies at 10 ft (3 m) from theappliance. Subsequently, at a distance of 20 ft (6.1 m) from an audible appliance rated at 84 dBA, thesound level might be reduced to 78 dBA. At a closed door, the loss might be about 10 dB to 24 dB or moredepending on construction. If the opening around the door is sealed, this might result in a loss of 22 dB to34 dB or more.

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 17:08:34 EDT 2016

Committee Statement

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

381 of 496 10/20/2016 11:03 AM

Page 382: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

CommitteeStatement:

The Technical Committee recognizes the documentation from the Department of Health andHuman Services and agrees with the proposed sound levels. The Technical Committee edits thedBA values pertaining to business occupancies, industrial occupanices, mechanical rooms, andplaces of assembly

ResponseMessage:

Public Input No. 478-NFPA 72-2016 [Section No. A.18.4.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

382 of 496 10/20/2016 11:03 AM

Page 383: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2531-NFPA 72-2016 [ Section No. A.18.5 ]

A.18.5

The mounting height of the appliances affects the distribution pattern and level of illumination produced byan appliance on adjacent surfaces. It is this pattern, or effect, that provides occupant notification byvisible visual appliances. If mounted too high, the pattern is larger but at a lower level of illumination(measured in lumens per square foot or foot-candles). If mounted too low, the illumination is greater(brighter) but the pattern is smaller and might not overlap correctly with that of adjacent appliances.

A qualified designer could choose to present calculations to an authority having jurisdiction showing that itis possible to use a mounting height greater than 96 in. (2.44 m) or less than 80 in. (2.03 m), provided thatan equivalent level of illumination is achieved on the adjacent surfaces. This can be accomplished byusing listed higher intensity appliances or closer spacing, or both.

Engineering calculations should be prepared by qualified persons and should be submitted to the authorityhaving jurisdiction, showing how the proposed variation achieves the same or greater level of illuminationprovided by the prescriptive requirements of Section 18.5.

The calculations require knowledge of calculation methods for high-intensity strobes visual notificationappliances . In addition, the calculations require knowledge of the test standards used to evaluate and listthe appliance.

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 17:39:33 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee agrees with the work that the CC TG did and agrees that “strobe” isnot applicable. The term “visual notification appliance” is the proper term.

ResponseMessage:

Public Input No. 280-NFPA 72-2016 [Section No. A.18.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

383 of 496 10/20/2016 11:03 AM

Page 384: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2532-NFPA 72-2016 [ Section No. A.18.5.3.2 ]

A.18.5.3.2

New research using lights visual notification appliances with longer pulse durations shows that theexisting tables for indirect signaling [Table 18.5.5.4.1(a) and Table 18.5.5.4.1(b)] are inadequate to assurereliable notification. Until additional work is done and incorporated into this Code, lights visual notificationappliances used for indirect signaling and having effective intensities specified in Table 18.5.5.4.1(a) orTable 18.5.5.4.1(b) need to be short duration, high intensity to be effective for the specified area ofcoverage. This limitation does not apply to direct signaling such as that used in corridors in accordancewith 18.5.5.5 . For direct signaling in corridors ( 18.5.5.5 ), longer pulse appliances (up to 100 ms), suchas LED lights, have been shown to be effective. Longer pulse durations might also be effective in largevolume spaces that use direct signaling, as discussed in A.18.5.4 .

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 17:41:55 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee agrees with the work that the Correlating Committee Task Group did andagrees that “light” is not applicable. The term “visual notification appliance” is the proper term. Thelast three sentences were deleted because the exception for direct signaling was removed in thebody of the code.

ResponseMessage:

Public Input No. 253-NFPA 72-2016 [Section No. A.18.5.3.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

384 of 496 10/20/2016 11:03 AM

Page 385: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2533-NFPA 72-2016 [ Section No. A.18.5.4 ]

Global FR-2504

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

385 of 496 10/20/2016 11:03 AM

Page 386: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

A.18.5.4

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

386 of 496 10/20/2016 11:03 AM

Page 387: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

The prescriptive requirements of Section 18.5 assume the use of appliances having very specificcharacteristics of light color, intensity, distribution, and so on. The appliance and application requirementsare based on extensive research. However, the research was limited to typical residential and commercialapplications such as school classrooms, offices, hallways, and hotel rooms. While these specificappliances and applications will likely work in other spaces, their use might not be the most effectivesolution and might not be as reliable as other visible notification methods.

For example, in large warehouse spaces and large distribution spaces such as super stores, it is possibleto provide visible signaling using the appliances and applications of this chapter. However, mountingstrobe lights visual notification appliances at a height of 80 in. to 96 in. (2.03 m to 2.44 m) along aisleswith rack storage subjects the lights visual notification appliances to frequent mechanical damage byforklift trucks and stock. Also, the number of appliances required would be very high. It might be possibleto use other appliances and applications not specifically addressed by this chapter at this time. Alternativeapplications must be carefully engineered for reliability and function and would require permission of theauthority having jurisdiction.

Tests of a system in large warehouse/super stores designed using the prescriptive approach of 18.5.5.4showed that high ambient light levels resulted in both indirect and direct signaling effects. The signal-to-noise ratio produced by the operating visible notification appliances visual notification appliances waslow in many locations. However, with visible notification appliances visual notification appliances locatedover the aisles or unobstructed by stock, indirect and some direct notification was sometimes achieved.Direct notification occurs even when occupants do not look up toward the ceiling-mounted visiblenotification appliances visual notification appliances due to the extended cone of vision shown in FigureA.18.5.4(a). The visible notification appliance visual notification appliance intensity and spacing resultingfrom the prescriptive design was generally sufficient for occupant notification by a combination of directand indirect signaling. Testing showed that the best performance was achieved where visible notificationappliances visual notification appliances were directly over aisles or where visible notificationappliances visual notification appliances in adjacent aisles were not obstructed by stock. Theperformance-based design method will almost always result in aisles not having a line of visiblenotification appliances visual notification appliances in them, because the spacing of visible notificationappliances visual notification appliances can be greater than the spacing of aisles. Also, it is recognizedthat aisles might be relocated after installation of the system. Good design practice is to place visiblenotification appliances visual notification appliances over aisles, especially those that are likely to remainunchanged such as main aisles, and over checkout areas. Where reorganization of aisles results invisible notification appliances visual notification appliances not in or over an aisle, or where that is thebase design, it is important to have a clear view from that aisle to a nearby visible notificationappliance visual notification appliance . See Figure A.18.5.4(b). Some spaces might have marginal visiblenotification appliance visual notification appliance effect (direct or indirect). However, occupants in theselarge stores and storage occupancies move frequently and place themselves in a position where theyreceive notification via the visible notification appliances visual notification appliances . In addition,complete synchronization of the visible notification appliances visual notification appliances in the spaceproduced a desirable effect.

Visible notification using the methods contained in 18.5.5.4 is achieved by indirect signaling. This meansthe viewer need not actually see the appliance, just the effect of the appliance. This can be achieved byproducing minimum illumination on surfaces near the appliance, such as the floor, walls, and desks. Theremust be a sufficient change in illumination to be noticeable. The tables and charts in Section 18.5 specifya certain candela-effective light intensity for certain size spaces. The data were based on extensiveresearch and testing. Appliances do not typically produce the same light intensity when measured off-axis.To ensure that the appliance produces the desired illumination (effect), it must have some distribution oflight intensity to the areas surrounding the appliance. ANSI/UL 1971, Standard for Signaling Devices forthe Hearing Impaired, specifies the distribution of light shown to provide effective notification by indirectvisible signaling.

Figure A.18.5.4(a) Extended Cone of Vision. (Courtesy of R. P. Schifiliti Associates, Inc.)

Figure A.18.5.4(b) Visible Notification AppliancesVisual Notification Appliances in Stores.(Courtesy of R. P. Schifiliti Associates, Inc.)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

387 of 496 10/20/2016 11:03 AM

Page 388: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 17:48:47 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee agrees with the work that the Correlating Committee Task Group did andagrees that “light” is not applicable. The term “visual notification appliance” is the proper term. Theother occurrences of “visible” in this section will be referred to the Task Group established to reviewChapter 18 and related annex material for the use of the term “visible” and determine where it isappropriate to change the term to “visual”.

ResponseMessage:

Public Input No. 256-NFPA 72-2016 [Section No. A.18.5.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

388 of 496 10/20/2016 11:03 AM

Page 389: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2534-NFPA 72-2016 [ Section No. A.18.5.5.1 ]

A.18.5.5.1

The requirements for the location of appliances within a building or structure are intended to apply tostrobe lights visual notification appliances applied in accordance with 18.5.5.4, 18.5.5.5, and 18.5.5.7.The mounting and location of appliances installed using the performance-based alternative of 18.5.5.6can be located differently, provided they meet the intended performance requirements. Other appliances,such as graphic displays, video screens, and so on, should be located so that they meet their intendedperformance.

Where low ceiling heights or other conditions do not permit mounting at a minimum of 80 in. (2.03 m),visible visual notification appliances can be mounted at a lower height. However, lowering the mountingheight reduces the area of coverage for that strobe visual notification appliance . The performance-basedmethods of 18.5.5.6 can be used to determine the area of coverage. Strobe light Visual notificationappliance mounting height should not be lowered below the plane of normal human viewing[approximately 5 ft (1.5 m)] except where ceiling heights limit the mounting position.

The mounting height requirement of 80 in. to 96 in. (2.03 m to 2.44 m) does not address the possibility ofconditions where ceiling heights are less than 80 in. (2.03 m). The range that is permitted [80 in. to 96 in.(2.03 m to 2.44 m)] ensures that strobes visual notification appliances are not mounted too high, whichwould result in lower levels of illumination on surrounding walls and on the floor. The lower limit of therange ensures that a minimum percentage of the surrounding surfaces is illuminated and that the top ofthe illuminated pattern is at or above the plane of normal human viewing [approximately 5 ft (1.5 m)]. Wallmounting of strobe lights visual notification appliances , which are listed only for wall mounting, can resultin little or no illumination above the plane of the strobe light visual notification appliance . In the case oflower ceiling heights and mounting close to the ceiling, the level of illumination on the floor andsurrounding walls is not reduced but the walls have a near 100 percent illuminated or “painted” areabecause the strobe visual notification appliance is close to the ceiling. That is, there is little or no wallsurface above the plane of the strobe visual notification appliance that is not illuminated when thestrobe visual notification appliance is mounted close to the ceiling. Thus, when a strobe visual notificationappliance is mounted lower than the minimum [80 in. (2.03 m)] but still close to the ceiling, the only loss ofsignal is the smaller pattern produced on the horizontal plane (floor).

In the case where the only change is a lower mounting height due to a lower ceiling height, the room sizecovered by a strobe visual notification appliance of a given value should be reduced by twice thedifference between the minimum mounting height of 80 in. (2.03 m) and the actual, lower mounting height.For example, if a 15 cd effective strobe visual notification appliance that normally covers a 20 ft (6.1 m)square space is being used and the height of the space is 63 in. (1.6 m) and the strobe visual notificationappliance is mounted at 59 in. (1.5 m), the strobe visual notification appliance can only cover a 16.5 ft(5.03 5.0 m) square space: 20 ft - 2 (80 in. - 59 in.) (1 ft/12 in.) = 16.5 ft (5.03 5.0 m).

The room size reduction assumes that the horizontal pattern on each side of the strobe visual notificationappliance is reduced by the same amount that the strobe visual notification appliance height is reduced.

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 17:51:08 EDT 2016

Committee Statement

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

389 of 496 10/20/2016 11:03 AM

Page 390: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

CommitteeStatement:

The Technical Committee agrees with the work that the Correlating Committee Task Group didand agrees that “light” and “strobe” are not applicable. The term “visual notification appliance” isthe proper term.

ResponseMessage:

Public Input No. 257-NFPA 72-2016 [Section No. A.18.5.5.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

390 of 496 10/20/2016 11:03 AM

Page 391: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2536-NFPA 72-2016 [ Section No. A.18.5.5.7.2 ]

A.18.5.5.7.3

For sleeping areas, the use of lights visual notification appliances with other intensities at distancesdifferent greater than within 16 ft (4.9 m) has not been researched and is not addressed in this Code.

This section on strobes visual notification appliances for alerting sleeping persons intends thatstand-alone strobes visual notification appliances be located in accordance with 18.5.5. If thestrobe visual notification appliance is an integral part of a smoke detector or smoke alarm, the unit mustbe mounted in accordance with the requirements for the smoke detector or smoke alarm. In either case(stand-alone or combination), Table 18.5.5.7.3 is then consulted to determine the minimum requiredintensity. Where the appliance is mounted less than 24 in. (610 mm) from the ceiling, it must have aminimum 177 cd effective rating because it might be in a smoke layer at the time it is called upon tooperate. If the appliance is 24 in. (610 mm) or more from the ceiling, it is permitted to be rated 110 cdeffective or more. Note that the requirement for increasing the intensity when mounted close to the ceilingapplies only to strobes visual notification appliances used in sleeping areas to awaken sleeping people. Itis assumed that in nonsleeping situations, a strobe visual notification appliance is not needed to alertsomeone if there is a developing smoke layer.

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 26 17:58:58 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee agrees with the work that the Correlating Committee Task Group didand agrees that “light” and “strobe” are not applicable. The term “visual notification appliance” isthe proper term. The first sentence was modified for clarification.

ResponseMessage:

Public Input No. 259-NFPA 72-2016 [Section No. A.18.5.5.7.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

391 of 496 10/20/2016 11:03 AM

Page 392: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3070-NFPA 72-2016 [ Section No. A.21.1 ]

A.21.1

Fire alarm systems, signaling systems, and emergency communications systems are often part of a large,integrated system serving a building or area. Figure A.21.1 shows examples of individual systems thatmight be part of an integrated system.

A fire alarm system might monitor the status of one of the other individual systems or provide a form ofoutput to control another individual system, such as a smoke control system or an elevator controller.

In some cases, the fire alarm system shares information and control in two directions with anotherindividual system. NFPA 72 covers only the fire alarm or signaling system in the circuits powered by it, notany part of the other individual systems.

See NFPA 3 and NFPA 4 for additional information on integrated systems.

Figure A.21.1 Integrated Systems. (Courtesy of R.P. Schifiliti Associates, Inc.)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

392 of 496 10/20/2016 11:03 AM

Page 393: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Sun Aug 07 14:05:54 EDT 2016

Committee Statement

Committee Statement: Text changed to conform to Manual of Style

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

393 of 496 10/20/2016 11:03 AM

Page 394: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3033-NFPA 72-2016 [ Section No. A.21.3.9 ]

A.21.3.10

The objective of elevator Phase I Emergency Recall Operation is to have the elevator automatically returnto the recall level before fire can affect the safe operation of the elevator. This includes both the safemechanical operation of the elevator, as well as the delivery of passengers to a safe lobby location. WhereANSI/ASME A17.1/CSA B44, Safety Code for Elevators and Escalators, specifies the use of smokedetectors fire alarm initiating devices used to initiate Phase I Emergency Recall Operation , these devicesare expected to provide the earliest response to situations that would require Phase I Emergency RecallOperations. The use of other automatic fire detection is only intended where smoke detection would notbe appropriate due to the environment. Where ambient conditions prohibit the installation of smokedetectors, the selection and location of other automatic fire detection should be evaluated to ensure thebest response is achieved. When heat detectors are used, consideration should be given to both detectortemperature and time lag characteristics ( Response Time Index ) . The consideration of a low temperaturerating alone might not provide the earliest response. It should be noted that smoke detectors installed inhoistways can be a source of nuisance activation. Therefore, hoistways need smoke detectors specificallyintended for those types of spaces (environments). Performance-based selection of specific automatic firedetection suitable for elevator hoistways can be based on Annex B as acceptable to the authority havingjurisdiction.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 13:50:59 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises the text to be consistent with ANSI/ASME A.17.1 and addsthe term “response time index”.

ResponseMessage:

Public Input No. 323-NFPA 72-2016 [Section No. A.21.3.9]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

394 of 496 10/20/2016 11:03 AM

Page 395: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3006-NFPA 72-2016 [ Section No. A.23.6.1 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

395 of 496 10/20/2016 11:03 AM

Page 396: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

A.23.6.1

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

396 of 496 10/20/2016 11:03 AM

Page 397: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

The intent of 23.6.1 applies to both short-circuit faults and open-circuit faults.

Fire alarm and signaling system communications technologies have evolved to the point that SLCs arenow the prevalent means of monitoring initiation devices, controlling output devices, and communicatingbetween panels, annunciators, and controllers.

The extent of coverage of traditional IDCs is inherently limited based on the quantity of powered initiationdevices or code limitations. Similarly, the extent and coverage of NACs also are limited by the powerrequired to operate the devices. SLCs, unlike IDCs and NACs, have few limitations, and it is now commonthat a single SLC can monitor and control more than 250 devices. In addition, a single SLC can be theonly pathway by which alarms are initiated, emergency control functions are controlled, and audible andvisual notification appliances are activated.

A total catastrophic failure of a fire alarm and life safety system due to a single open or short on an SLCcan negate most, if not all, of this Code’s requirements for specifying an acceptable minimum level ofperformance and reliability for the protection of life and property from fire.

Designers should carefully consider the potential that a single SLC short or open caused by a fire orinadvertent damage to the SLC could disable an entire SLC prior to the activation of an alarm conditionalong with the subsequent alarm signaling and emergency control functions.

With traditional IDCs and NACs, a single open, ground, or short fault on one circuit could not affect theperformance of other IDCs, NACs, and emergency control circuits. As such, the occurrence of a singleshort or open could limit the extent of the failure to a particular zone or area.

One method for providing an acceptable level of performance and reliability of SLCs is to limit the potentialcatastrophic failure to one zone, in a way similar to how traditional IDCs and NACs have been and arenow required to do.

A single zone could be designated in the following ways:

(1) By floor where an SLC would not span multiple floors

(2) By floor area, where a large floor would be split into multiple zones based on a maximum floor area

size (e.g., 22,500 ft2)

(3) By fire barrier or smoke barrier compartment boundaries, which an SLC would not cross

(4) By maximum length or circuit, where an SLC would not be longer than a predetermined length (e.g.,300 ft)

See the definition of zone (3.3.323) and Figure A.23.6.1(a) through Figure A.23.6.1(d) for additionalclarification.

Figure A.23.6.1(a) depicts a Class B SLC with four zones. Wiring of more zones would require oneisolator for each additional zone. The isolator can be integrated into the device or a separate component.If a single short or open occurs beyond the isolators, only one zone will be affected.

Figure A.23.6.1(a) Class B Isolation Method.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

397 of 496 10/20/2016 11:03 AM

Page 398: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Figure A.23.6.1(b) depicts a Class A SLC with four zones. Wiring of more zones would require oneisolator for each additional zone. The isolator can be integrated into the device or a separate component.If a single short or open occurs, only one zone will be affected. If a single open occurs, no devices will beaffected.

Figure A.23.6.1(b) Class A Isolation Method.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

398 of 496 10/20/2016 11:03 AM

Page 399: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Figure A.23.6.1(c) depicts a hybrid Class A SLC loop with Class B SLC branches serving four zones thatis designated as a Class B SLC. Wiring of more zones would require one isolator for each additional zone.The isolator can be integrated into the device or a separate component. If a single short occurs, only onezone will be affected. If a single open occurs, it might affect only one zone.

Figure A.23.6.1(c) Hybrid Isolation Method.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

399 of 496 10/20/2016 11:03 AM

Page 400: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Figure A.23.6.1(d) depicts an incorrect Class B SLC configuration with four zones. If a single short oropen occurs, one or more zones could be affected depending on the location of the single short.

Figure A.23.6.1(d) Incorrect Use of Isolators on an SLC.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Aug 03 12:54:05 EDT 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

400 of 496 10/20/2016 11:03 AM

Page 401: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Committee Statement

Committee Statement: The Technical Committee changes the term from FACP to FACU.

Response Message:

Public Input No. 620-NFPA 72-2016 [Section No. A.23.6.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

401 of 496 10/20/2016 11:03 AM

Page 402: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3004-NFPA 72-2016 [ Section No. A.23.8.4.3 ]

A.23.8.4.4

For systems such as carbon monoxide detection, fire extinguisher electronic monitoring device,emergency communication communications (mass notification), or intrusion, much of the benefit of acombination system comes from being able to use common wiring. If the equipment in the combinationsystem is of equivalent quality to fire alarm equipment, and the system monitors the wiring and equipmentin the same way as fire alarm equipment, then sharing of wiring is permitted. If the equipment is not ofequivalent quality, isolation between the systems would be required.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Aug 03 12:48:20 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text by replacing the term “communication” with“communications.” The term "communication(s)” was reviewed throughout the entire document forproper use regarding reference to singular and plural use. The term should be plural as used in thiscontext. This change is editorial only.

ResponseMessage:

Public Input No. 461-NFPA 72-2016 [Section No. A.23.8.4.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

402 of 496 10/20/2016 11:03 AM

Page 403: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3058-NFPA 72-2016 [ Section No. A.23.8.4.6 ]

A.23.8.4.7

Examples of signal classification are provided in Table A.23.8.4.7. This is not all-inclusive or prescriptivebut is meant to illustrate a potential classification scheme. Actual schemes may might vary dependingupon the emergency response plan and/or requirements of the authority having jurisdiction. Massnotification systems are allowed to take priority over the fire alarm audible notification message or signal.This is intended to allow the mass notification system to prioritize emergency signals on the basis of riskto building occupants. The designer should specify the desired operation, in particular, as to what shouldoccur immediately after the mass notification message has completed.

Table A.23.8.4.7 Examples of Signal Classification

Life Safety Property Protection Trouble Other

Fire alarm signals Security signals Battery fault HVAC signals

Carbon monoxide alarm signals Supervisory signals AC power failure Occupancy

Code blue signals Access control IDC faults

Panic alarms NAC faults

Hazmat signals SLC faults

Severe weather warnings

Flood alarms

Mass notification signals

Holdup alarm signals

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Sun Aug 07 10:46:47 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text by replacing “response plan” with “emergencyresponse plan” as this is the terminology defined within NFPA 72.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

403 of 496 10/20/2016 11:03 AM

Page 404: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3064-NFPA 72-2016 [ Section No. A.24.3.2 ]

A.24.3.2

Users who speak too softly, too loudly, or who hold a microphone too close, too far, or at an incorrectangle can introduce distortion or cause reduced intelligibility of the spoken message. The characteristicsof the system microphone are important ergonomic factors that affect voice intelligibility. Somemicrophones need to be held close to the mouth, perhaps an inch or less. Others need to be three or fourinches away. How is the user to know what’s ideal? A simple diagram next to the microphone can help.Some microphones are very directional and must be held flat in front of the speaker’s mouth. Thesemicrophones are useful in small command centers, since they are less likely to pick up conversations offto the sides. On the other hand, microphones with a wider polar sensitivity are more forgiving for a user tohold comfortably while moving and doing other tasks. Their downside is that they will pick up extraneousnoise in poorly designed command centers introduced into the microphone.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Sun Aug 07 11:17:07 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises the Annex section to solve the issue proposed, where in somecases the word “speaker” refers to a physical appliance while other sections use it to refer to aperson.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

404 of 496 10/20/2016 11:03 AM

Page 405: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 527-NFPA 72-2016 [ Section No. A.24.3.7 ]

A.24.3.7

One-way emergency communications systems are intended to broadcast information, in an emergency, topersonnel in one or more specified indoor or outdoor areas. It is intended that emergency messages beconveyed either by audible or visible textual means or both. This section does not apply to bells, horns, orother sounders and lights visible notification appliances , except where used in conjunction with thedesired operation of emergency messages and signaling.

Two-way emergency communications systems are divided into two categories, those systems that areanticipated to be used by building occupants and those systems that are to be used by fire fighters, police,and other emergency services personnel. Two-way emergency communications systems are used both toexchange information and to communicate information, such as, but not limited to, instructions,acknowledgement of receipt of messages, condition of local environment, and condition of persons, and togive assurance that help is on its way.

NFPA 72 contains requirements that can impact the application of emergency communications systems.For instance, coordination of the functions of an emergency communications system with other systemsthat communicate audibly and/or visibly [such as fire alarm systems, security systems, public address (PA)systems] is essential in order to provide effective communication in an emergency situation. Conflicting orcompeting signals or messages from different systems could be very confusing to occupants and have anegative impact on the intended occupant response. Where independent systems using audible and/orvisible notification are present, the emergency communications system needs to interface with thosesystems to effect related control actions such as deactivating both audible and visible notificationappliances. The use of a single integrated combination system might offer both economic and technicaladvantages. In any case, coordination between system functions is essential. The coordination ofemergency communications systems with other systems should be considered part of the risk analysis forthe emergency communications system. (See Figure A.24.3.7.)

Additional documents such as NEMA Standard SB 40, Communications Systems for Life Safety inSchools, can also be used as supplemental resources to provide help with risk assessment andapplication considerations.

Figure A.24.3.7 Emergency Communications Systems.

Supplemental Information

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

405 of 496 10/20/2016 11:03 AM

Page 406: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

File Name Description

Figure_A.24.3.7.docx Shows correction to Figure A.24.3.7

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 22:55:17 EDT 2016

Committee Statement

CommitteeStatement:

For uniformity throughout the document, the term “light” was replaced with “visible notificationappliance”. Further it is understood that SIG-NAS is reviewing the terms “visual” and “visible” andSIG-ECS requests the Correlating Committee to review and take appropriate actions. The changeto the figure is to correct a typo.

ResponseMessage:

Public Input No. 260-NFPA 72-2016 [Section No. A.24.3.7]

Public Input No. 771-NFPA 72-2016 [Section No. A.24.3.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

406 of 496 10/20/2016 11:03 AM

Page 407: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 528-NFPA 72-2016 [ Section No. A.24.3.8 ]

A.24.3.8

The layers can be used in combination. In all cases, the system design needs to follow the risk analysisand be integrated into the emergency response plan. Research has shown that more than one layer hasbeen used to be effective. Multiple layers provide an extra level of notification (a safety net). The overallMNS application is likely to exploit a number of public and individual systems or components that combineto produce a reliable and robust solution to achieve emergency notification objectives.

Layer 1 could consist of elements such as the following:

(1) Emergency voice/alarm communications systems (EVACS)

(2) In-building mass notification system (MNS)

(3) One-way voice communication systems (PA)

(4) Two-way voice communication systems

(5) Visible notification appliances

(6) Textual/digital signage/displays

Layer 2 could consist of elements such as the following:

(1) Wide-area outdoor mass notification systems (MNS) MNS

(2) High power speaker arrays (HPSA)

Layer 3 could consist of elements such as the following:

(1) Short message service (SMS)

(2) Email

(3) Computer pop-ups

(4) Smartphone applications (Apps apps )

(5) Reverse 911/automated dialing

Layer 4 could consist of elements such as the following:

(1) Radio broadcast (satellite, AM/FM)

(2) Television broadcast (satellite, digital)

(3) Location specific messages/notifications

(4) Weather radios

(5) Social networks

Also see Optimizing Fire Alarm Notification for High Risk Groups research project.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 22:59:21 EDT 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

407 of 496 10/20/2016 11:03 AM

Page 408: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Committee Statement

CommitteeStatement:

In-building mass notification systems is added to the list specifically so as not to inadvertentlyimply to a casual reader that MNS and Emergency Voice Alarm Communication System are thesame thing.

ResponseMessage:

Public Input No. 471-NFPA 72-2016 [Section No. A.24.3.8]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

408 of 496 10/20/2016 11:03 AM

Page 409: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 526-NFPA 72-2016 [ Section No. A.24.3.9 ]

A.24.3.9

The design documents might include, but are not limited to, shop drawings, input/output matrix, batterycalculations, notification appliance voltage drop and wattage calculations for strobes visible notificationappliances and speakers, and product data sheets.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 22:51:01 EDT 2016

Committee Statement

CommitteeStatement:

Wattage calculations are required for audio systems. Voltage comes into play for audio but many donot provide calculations for wattage and use the inverse square law and this causes many audiosystems to not function as intended. The proposed change to the term “speaker” was not made inorder to keep in current alignment with the terms loudspeaker/speaker. The Technical Committeerequests the Correlating Committee review this action across all Technical Committees.

ResponseMessage:

Public Input No. 208-NFPA 72-2016 [Section No. A.24.3.9]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

409 of 496 10/20/2016 11:03 AM

Page 410: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 509-NFPA 72-2016 [ Section No. A.24.3.10 ]

A.24.3.10

A fire alarm control unit that is listed in accordance with ANSI/UL 864 or ANSI/UL 2017 can be used forMNS. A control unit only listed in accordance with ANSI/UL 2572 or ANSI/UL 2017 cannot be used as afire alarm control unit. A fire emergency voice/ alarm communications systems (EVACS) control unit thatis listed in accordance with ANSI/UL 864, Standard for Control Units and Accessories for Fire AlarmSystems , or an emergency alarm system control unit listed to ANSI/UL 2017, Standard for General-Purpose Signaling Devices and Systems , can be used for MNS as long as the control unit has also beenevaluated to ANSI/UL 2572, Mass Notification Systems . The unique requirements in Chapter 24 formass notification systems are included in ANSI/UL 2572. A control unit is permitted to provide multiple lifesafety services when evaluated to the respective requirements. A control unit only listed in accordancewith ANSI/UL 2572 or ANSI/UL 2017 cannot be used as a fire alarm control unit.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 13:58:49 EDT 2016

Committee Statement

CommitteeStatement:

“Fire alarm” is revised to “fire emergency voice/alarm communication systems (EVACS)” because notall fire alarm control units have voice capability which is required for mass notification systems. Theadditional revisions are intended to clarify that control units can be evaluated to multiple standardssuch as such as ANSI/UL864 and ANSI/UL2017 to provide a combination of life safety signaling, andin order to provide mass notification services, the control unit must also be evaluated toANSI/UL2572. ANSI/UL2572 includes unique requirements for mass notification systems which arederived from Chapter 24. Examples of unique requirements are: priority of signaling, overriding andrelinquishing control of the fire alarm signaling, not overriding special notification releasing signaling,activating notification appliances that have completed the minimum number of required cycles onceevery 30 seconds. These requirements only reside in ANSI/UL2572. This revision clarifies anyconfusion for AHJs and customers.

ResponseMessage:

Public Input No. 693-NFPA 72-2016 [Section No. A.24.3.10]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

410 of 496 10/20/2016 11:03 AM

Page 411: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 529-NFPA 72-2016 [ Section No. A.24.3.13.3 ]

A.24.3.14.3

This section is not meant to preclude a performance-based pathway survivability approach. As with mostperformance-based approaches, documentation should be provided by the designer and maintained withsystem documentation for the life of the system. Written documentation of the approval from the authorityhaving jurisdiction should also be maintained. A performance-based approach to pathway survivabilitycould be equivalent to, less stringent than, or more stringent than the prescriptive approach in 24.3.14.Often a performance-based approach will result from a risk analysis.

This section is also not meant to preclude less stringent pathway survivability requirements supported bya risk analysis for those unique occupancies that employ emergency voice alarm/emergencycommunication systems for relocation or partial evacuation as part of their fire safety plan whererelocation or partial evacuation could be readily superseded by total evacuation and where buildings areof a type other than Type I or Type II (222) construction where the pathway survivability performancerequirement does not need to be for two hours. Examples include low rise education and day careoccupancies, nursing homes, ambulatory health care occupancies, hotel and dormitory occupancies, andresidential board and care occupancies.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 23:02:13 EDT 2016

Committee Statement

Committee Statement: This is an editorial revision to maintain consistency.

Response Message:

Public Input No. 683-NFPA 72-2016 [Section No. A.24.3.13.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

411 of 496 10/20/2016 11:03 AM

Page 412: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 531-NFPA 72-2016 [ Section No. A.24.4.6.1 ]

A.24.4.6.1

Speakers Loudspeakers located in the vicinity of the in-building fire emergency voice/alarmcommunications control equipment or MNS equipment should be arranged so they do not cause audiofeedback when the system microphone is used. Speakers Loudspeakers installed in the area of two-waytelephone stations should be arranged so that the sound pressure level emitted does not preclude theeffective use of the two-way telephone system. Circuits for speakers loudspeakers and telephones shouldbe separated, shielded, or otherwise arranged to prevent audio cross-talk between circuits.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 23:06:08 EDT 2016

Committee Statement

CommitteeStatement:

The term “speaker” is changed to “loudspeaker” in order to keep in current alignment with theterms loudspeaker/speaker, to be reviewed by the Correlating Committee. MNS is added toinclude similar equipment.

ResponseMessage:

Public Input No. 229-NFPA 72-2016 [Section No. A.24.4.6.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

412 of 496 10/20/2016 11:03 AM

Page 413: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 502-NFPA 72-2016 [ Section No. A.24.4.8 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

413 of 496 10/20/2016 11:03 AM

Page 414: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

A.24.4.8

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

414 of 496 10/20/2016 11:03 AM

Page 415: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

When a fire or other emergency occurs in a building, the usual goal is to evacuate the occupants orrelocate them so that they are not exposed to hazardous conditions. The exception occurs in occupanciesusing stay-in-place/defend-in-place (SIP/DIP) [1] strategies. It might also be necessary to alert andprovide information to trained staff responsible for assisting evacuation or relocation. Figure A.24.4.8shows several key steps in a person’s reaction and decision-making process [2].

Occupants rarely panic in fire situations [3,4]. The behavior that they adopt is based on the informationthey have, the perceived threat, and the decisions they make. The entire decision path is full of thoughtand decisions on the part of the occupant, all of which take time before leading to the development ofadaptive behavior. In hindsight, the actions of many occupants in real fires are sometimes less thanoptimal. However, their decisions might have been the best choices given the information they had. Firealarm systems that only use audible tones and/or flashing strobe lights visible notification appliancesimpart only one bit of information: fire alarm. It has long been recognized that environments havingcomplex egress situations or high hazard potentials require occupant notification systems that providemore than one bit of information [5]. To reduce the response time of the occupants and to effect thedesired behavior, the message should contain several key elements [3,6].

Figure A.24.4.8 Key Steps in Person’s Reaction.

The key elements include the following:

(1) Tell occupants what has happened and where

(2) Tell occupants what they should do

(3) Tell occupants why they should do it

There does not seem to be any research that has tested actual message content to determine the bestway to inform occupants. The problem is that each building and each fire is unique. Messaging is furthercomplicated by the need to give different information to different people, depending on their locationrelative to the fire, their training, and their physical/mental capabilities.

Messages should use positive language and avoid negative instructions that could be misinterpreted dueto unintelligible communications. For example, if you want people to leave an area, say so: “A fire hasbeen reported in the area. For your safety, use the stairs to evacuate the area immediately.” A badexample is: “The signal tone you have just heard indicated a report of an emergency. If your floorevacuation signal sounds after this message, do not use the elevator, walk to the nearest stairway andleave the floor. While the report is being verified, occupants on other floors should await furtherinstructions.” This message is too long, ambiguous, and subject to misunderstanding if not heard clearly.The word “not” might not be heard clearly, or it might be heard to apply to the entire remaining sentence.Similarly, care should be used in selecting and clearly enunciating words such as “fifth” and “sixth,” whichcan sound the same if the system and environment lead to low intelligibility.

See A.24.3.6.1 for more information on methodology for improved message content, structure, and

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

415 of 496 10/20/2016 11:03 AM

Page 416: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

intelligibility. Refer to Annex D for more information on speech intelligibility and how it is predicted.

Content of the message should be predicated on the building fire safety emergency response plan, thenature of the building and its occupants, the design of the fire alarm system, and testing of the occupantreaction to the message. Caution is advised that the fire alarm system operation and message actuationmight be initiated by a manual pull station or detector remote from the fire.

[1] Schifiliti, R. P., “To Leave or Not to Leave — That is the Question!”, National Fire ProtectionAssociation, World Fire Safety Congress & Exposition, May 16, 2000, Denver, CO.

[2] Ramachandran, G., “Informative Fire Warning Systems,” Fire Technology, vol. 47, no. 1, February1991, National Fire Protection Association, 66–81.

[3] J., Bryan, “Psychological Variables That May Affect Fire Alarm Design,” Fire Protection Engineering,Society of Fire Protection Engineers, Issue No. 11, Fall 2001.

[4] Proulx, G., “Cool Under Fire,” Fire Protection Engineering, Society of Fire Protection Engineers, IssueNo. 16, Fall 2002.

[5] General Services Administration, Proceedings of the Reconvened International Conference on FireSafety in High Rise Buildings, Washington, D.C., October 1971.

[6] Proulx, G., “Strategies for Ensuring Appropriate Occupant Response to Fire Alarm Signals,” NationalResearch Council of Canada, Ottawa, Ontario, Construction Technology Update, No. 43, 1–6, December2000.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 11:17:30 EDT 2016

Committee Statement

CommitteeStatement:

For consistency, the Technical Committee changes building fire safety plan to emergency responseplan. Additionally, for uniformity throughout the document, the term “strobe” is replaced with “visiblenotification appliance”. Further it is understood that SIG-NAS is reviewing the terms “visual” and“visible” and SIG-ECS requests the Correlating Committee to review and take appropriate actions.

ResponseMessage:

Public Input No. 261-NFPA 72-2016 [Section No. A.24.4.8]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

416 of 496 10/20/2016 11:03 AM

Page 417: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 532-NFPA 72-2016 [ Section No. A.24.5.2.2 ]

A.24.5.2.2

Authorized personnel could effect initiate message initiation signaling over the mass notification systemfrom either a an emergency command center or a secondary (backup) control station(s). In cases whereclusters of facilities within the same geographical region exist, one or more regional control stations couldeffect initiate message initiation signaling . The mass notification system could permit activation ofmessages originated by mobile sentries and roving patrols using wireless activation devices. Since it iscommon practice to allow mass notification systems to be utilized for “nonemergency” messages, theemergency command center should incorporate a clearly marked and easy to operate means todistinguish between emergency and non-emergency nonemergency use. Comprehensive training and afail-safe default to the emergency mode of operation should be employed to ensure that no actualemergency message gets transmitted as a non-emergency nonemergency broadcast.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 23:22:04 EDT 2016

Committee Statement

Committee Statement: This is an editorial revision to maintain consistency.

Response Message:

Public Input No. 621-NFPA 72-2016 [Section No. A.24.5.2.2]

Public Input No. 112-NFPA 72-2016 [Section No. A.24.5.2.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

417 of 496 10/20/2016 11:03 AM

Page 418: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 544-NFPA 72-2016 [ Section No. A.24.5.4.1 ]

A.24.5.4.1

Alternate methods that achieve the desired statistical availability could be deemed acceptable in lieu ofmonitoring the integrity of circuits, signaling channels, or communication pathways where consistent withthe risk analysis and emergency response plan.

An example of an alternate method could include an attendant monitored system listed to UL 2017,Standard for General-Purpose Signaling Devices and Systems . As defined by Section 1.2 of UL 2017 ,“Type AM (Attendant Monitored) devices or systems are intended to be constantly operated andmaintained by competent and experienced personnel, either locally or at a remote station”. Such aconstantly operated system could demonstrate a statistically significant availability to satisfy an AHJ.Additionally, ANSI/NEMA SB 40, Communications Systems for Life Safety in Schools , references“operational integrity” in relation to systems that are used regularly for routine purposes and suggests thatsuch systems would be statistically more available due to a lower risk of falling into a state of disrepair.SB 40 also addresses system readiness in relation to constant use , and recommends that, to thegreatest extent possible, equipment used in emergency communication should be used daily in routinesituations. Therefore, it is important to consider the level to which a system is constantly operated and thelevel of operator training when preparing a risk analysis. Based on the occupancy of the premise, the riskanalysis, and the emergency response plan, the designer and AHJ can more easily determine whether itis appropriate for loudspeaker circuits to utilize this alternate method for equivalency.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jul 29 12:08:04 EDT 2016

Committee Statement

CommitteeStatement:

Section 24.5.4.1 creates circumstances for alternate methods to be used, and the existing annexmaterial elaborates on the criteria for the exemption, but no examples are provided for the contextof this criteria. This addition to the annex seeks to provide additional clarity by providing an exampleof an alternate method with cited justification from other referenced standards.

ResponseMessage:

Public Input No. 423-NFPA 72-2016 [Section No. A.24.5.4.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

418 of 496 10/20/2016 11:03 AM

Page 419: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 533-NFPA 72-2016 [ Section No. A.24.5.18.2 ]

A.24.5.18.2

The requirement of 24.5.18.2 does not imply that multiple primary methods of visible appliances cannotexist in a common area. Both strobes and graphical or textual appliances are designated as primarywhere the authority having jurisdiction declares both to be required. When textual audible notification isrequired, consideration is warranted for high-noise areas and for a hearing- impaired person’s capability ofclearly receiving instructions.

As mass notification systems are deployed, the more complex emergency management communicationrequirements that go beyond what can be indicated by a strobe and a tone are being addressed. Theintelligibility requirements of a MNS/ECS are a direct reflection of this reality. However, for a hearing-impaired person, no degree of intelligibility might be sufficient. Additionally, there are physical spaceswhere intelligibility is impossible or impractical to provide. In designating a primary visual notificationappliance, it is easy to assume that a strobe is sufficient and all other visual notification is automaticallysupplemental.

However, where the risk analysis and an emergency response plan require the communication of MNStextual audible instructions for occupants, a strobe should not be considered a sufficient primarynotification appliance where intelligibly cannot be achieved or where consideration for lone individuals orgroups of individuals with hearing impairments might prevent them from responding appropriately toemergency instructions.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 23:24:47 EDT 2016

Committee Statement

Committee Statement: This is an editorial revision to maintain consistency.

Response Message:

Public Input No. 648-NFPA 72-2016 [Section No. A.24.5.18.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

419 of 496 10/20/2016 11:03 AM

Page 420: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 535-NFPA 72-2016 [ Section No. A.24.7 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

420 of 496 10/20/2016 11:03 AM

Page 421: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

A.24.7

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

421 of 496 10/20/2016 11:03 AM

Page 422: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Distributed recipient mass notification systems are enterprise-class systems for the management of, andmass distribution of, emergency notification messages within buildings, throughout installations, acrossentire geographical regions, or throughout a worldwide military command. Using distributed recipient massnotification systems, designated system operators would be able to rapidly and reliably inform appropriatepersonnel of homeland security levels (including chemical, biological, radiological, and nuclear threats;hazardous weather conditions; and many other critical events), possibly with near real-time responsecapability.

A distributed recipient mass notification system is meant to communicate to a wide range of targetedindividuals and groups. These systems might use mass dialing systems, including reverse 911, email,SMS, or other directed communications methods to broadcast information. They might also use wired orwireless networks for one- or two-way communications and/or control between a building or area and anemergency services organization (information, command, and control).

Distributed Through classified as one-way ECS, distributed recipient mass notification systems could becapable of centrally tracking, in real time, all alerting activities for each individual recipient, includingsending, receiving, and responding to alerts, and be able to generate reports based on trackedinformation. Distributed recipient mass notification systems could be able to provide ability to collect andreport user responses to alerts, such as "I am safe," "I need assistance," and "I am not in affected area."

Distributed recipient mass notification systems could incorporate a predefined library of signals andmessaging appropriate for, but not limited to, the following:

(1) Presidential alert message

(2) Homeland security levels

(3) Terrorism threats, watches, or warnings

(4) Evacuation routes

(5) Emergency directives

(6) Personnel recall requirements

(7) Federal, DOD, police, fire, or locally /installation-specific warning and notification requirements

(8) Amber alerts

The distributed recipient mass notification system could be capable of monitoring emergency notificationsfrom multiple data sources [Commercial Mobile Alert System (CMAS) such as Wireless Emergency Alert(WEA) , National Weather Service, Emergency Managers Weather Information Network (EMWIN), NavalMeteorology and Oceanography (METOC), and others as determined locally] and automatically sendingout notifications to designated facilities and personnel based on predefined rules.

A mass notification system could also be capable of reaching out to all online personnel by leveraging ahighly secure, redundant, Web-based IP network architecture to manage the entire mass notificationprocess. Agencies and organizations can create role-based uses such as operators, administrators, andrecipients, based on their access rights across multiple facilities, campuses, and installations. Systemrules could be established to determine operator permissions and actions such as creating and activatingscenarios, as well as the extent and geography of alerts and delivery systems and devices that should beused. Such a Web-based mass notification system would employ an open, standards-based architecture.The system could be integrated with existing user directories to support organizational hierarchy andemergency response groups. It could be structured to allow emergency criteria–based targeting ofemergency alerts.

Additionally, this annex material provides information on ongoing development of system requirements fornet-centric alerting systems (NCAS) that will be based on IP technologies. This annex is not mandatory,but is provided to stimulate development of suitable requirements and standards. Consequently, usersuggestions and feedback on this annex are highly encouraged and requested. Methods to ensurereliability and robustness in off-normal or emergency conditions are of particular concern. The requiredamount of and method for isolating alerting functions from normal, non-alerting system functions needsdevelopment.

NCAS leverage the IP network infrastructure to instantly reach those personnel who have access to nearlyany IP-connected devices [such as pop-up alerts on personal computers (PC), text messages to personaldata assistants (PDA) and cellular telephones, electronic mail to IP-capable cellulartelephones messages , and voice messages to voiceover-IP (VoIP) telephones and PCs]. Additionally,NCAS could be used to activate, through a single user interface, other (IP based and non-IP based)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

422 of 496 10/20/2016 11:03 AM

Page 423: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

alerting systems, such as wide-area alerting systems and traditional dial-up telephone alerting systems.

NCAS can be installed independently or at a central location. In a centrally managed NCAS configuration,personnel and facilities in the regional operations center’s particular area of coverage could be alertedinstantly by events, either from any individual installation, or centrally from the regional operations center.Using management tools, designated operators from each installation in the region could log in via a webbrowser and have complete access to their own portion of the NCAS. The regional operations centerwould retain the ability to centrally monitor and manage all portions of the system, including supervisoryand trouble conditions of the different system components and integrated components.

The NCAS would incorporate a Web-based management and alert activation application through which alloperators and administrators could gain access to the system’s capabilities, based on the users’permissions and the defined access policy. Such a management application would incorporatemanagement of the alert activation flow through all delivery methods, as well as end-user management,operators’ permission and access, tracking and reporting, and all administrative aspects of the system.

Distributed recipient mass notification systems could interface and interoperate with other types of massnotification capabilities, including wide-area and in-building mass notification systems. Duringemergencies, systems operators should not need to send notifications using multiple alerting systems.The distributed recipient mass notification system, particularly NCAS, might be able to provide thecapability to integrate user interfaces and consolidate access to multiple mass notification and alertingsystems.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 23:28:32 EDT 2016

Committee Statement

CommitteeStatement:

This revision provides clarification on capability to track and report progress and responsesthough DRMNS. This revision also updates CMAS with WEA, and updates to current industryterms and capabilities.

ResponseMessage:

Public Input No. 770-NFPA 72-2016 [Section No. A.24.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

423 of 496 10/20/2016 11:03 AM

Page 424: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 537-NFPA 72-2016 [ Section No. A.24.7.3 ]

A.24.7.2

Distributed recipient mass notification systems could be capable of sending alert messages in a prioritizedmethod to target recipients according to the following:

(1) Hierarchical organizational structure (as would be imported from an active directory)

(2) Organizational roles

(3) Specific distribution lists [e.g., hazardous materials (HAZMAT) response teams]

(4) Specific distribution (e.g., hearing impaired or others with impairments that warrant prioritizednotification)

(5) Dynamic groups created through on-the-fly queries of the user directory

(6) Geographical locations (e.g., entire bases, zones within bases)

(7) IP addresses (required for targeting devices in specific physical locations)

Distributed recipient mass notification systems should provide mechanisms to update user and targetingdata; for example, user data import, integration with personnel directories, and self-user registration.

Distributed recipient mass notification systems could use a Web-based user interface, support locallydesignated standard network ports and protocols, and provide open interfaces to support interoperability,such as eXtensible markup language (XML) and common alerting protocol (CAP) based emergencymessages. (See OASIS Standard CAP-V1.2, OASIS Common Alerting Protocol version 1.2.)

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 23:31:41 EDT 2016

Committee Statement

CommitteeStatement:

This revision attaches existing annex material to the correct section. The annex text ofA.24.7.3 is relocated at the end of A.24.7.2.

ResponseMessage:

Public Input No. 769-NFPA 72-2016 [Section No. A.24.7.3]

Public Input No. 762-NFPA 72-2016 [Section No. A.24.7.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

424 of 496 10/20/2016 11:03 AM

Page 425: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 538-NFPA 72-2016 [ Section No. A.24.7.5 ]

A.24.7.5

Distributed recipient mass notification systems would be capable of sending alert messages to end-users(recipients) via multiple delivery methods, including the following:

(1) Audio-visual network alerts to desktops and laptops via desktop pop-up

(2) Text alerts to mobile phones and pagers

(3) Text alerts to electronic mail (e-mail) clients

(4) Text alerts to social networks

(5) Audio alerts to phones

(6) Audio alerts to existing wide-area or building voice and or mass notification systems

(7) Network alerts to any other IP-connected devices via standard XML and CAP protocols

The system could be extendable to support additional delivery methods in the future as this technologydevelops.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 23:33:08 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee makes this revision to keep up with the industry by adding socialnetworks as means to distribute notifications.

ResponseMessage:

Public Input No. 767-NFPA 72-2016 [Section No. A.24.7.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

425 of 496 10/20/2016 11:03 AM

Page 426: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 539-NFPA 72-2016 [ Section No. A.24.13 ]

A.24.13

An emergency communications system information, command, and control is intended to include wired orwireless networks for one- or two-way communications and/or control between a building or area and anemergency command center and could include an emergency services organization or public alarmreporting system. In a very basic configuration, a system and the receiving facility could be a supervisingstation system. However, there can be more complex systems that allow control of building systems andcommunication communications to building occupants from a remote location, including a municipal orother public alarm reporting command center or possibly even from a mobile command vehicle usingsecure communications.

Submitter Information Verification

Submitter Full Name: SIG-ECS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 23:34:15 EDT 2016

Committee Statement

CommitteeStatement:

As part of the Correlating Committee Task Group on terms, the term "communication(s)” wasreviewed throughout the entire document for proper use regarding reference to singular and pluraluse. The term should be plural use in this context.

ResponseMessage:

Public Input No. 463-NFPA 72-2016 [Section No. A.24.13]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

426 of 496 10/20/2016 11:03 AM

Page 427: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 540-NFPA 72-2016 [ Section No. A.24.14 ]

A.24.14

The risk analysis forms the basis for the emergency response plan.

Ensuring accurate information dissemination to the right people, at the right place, and at the right time isessential to the mitigation of threat actions and consequences. Trained personnel are charged withmaking such decisions in real time. Quite often, the instructions provided to personnel in affected areaspertain to acting in specific defensive ways so as not to expose them to danger. A typical example is thecase of a chemical or biological agent attack wherein the right response is to relocate to secure areaswithin the building while sealing doors and windows and shutting down air intakes, rather than to leave thebuilding and be exposed to the attacking agent.

In cases of bomb threats, where specific information is available, directions for evacuation are to be given;these directions require more specificity than simply the instruction “Evacuate the building.” In most cases,the evacuation route might depend on threat intelligence and is likely to be different from that specified inan emergency response plan. Most people can tell where the fire comes from but do not always knowwhere the bomb is. Automatic evacuation of a building, a common procedure in cases of a fire, is to beavoided, since it might expose personnel to even greater danger.

One of the reasons for implementing a mass notification system is the threat of terrorism. Terrorismattacks tend to be well organized and are often planned with details to inflict the widest degree of damagethat is possible. The mass notification system must be designed to withstand various attack scenarios andsurvive even if some damage has already occurred.

Each design of a mass notification system should be specific to the nature and anticipated risks of eachfacility for which it is designed. Although this chapter outlines some specific criteria and/or limitations,each design should be based on recognized performance-based design practices.

The mass notification system should take into account various considerations, such as those indicated inthis chapter. The particular design might or might not incorporate these provisions.

Considerations for developing a mass notification system are as follows:

(1) Specific design for the facility

(2) Account for anticipated risks

(3) Use of live and/or prerecorded messaging

(4) Interfacing with other building emergency communications systems

(5) Interfacing with wide-area notification systems

(6) Ability to control the HVAC and access control systems

(7) Access to system components

(8) Survivability of the system

(9) Communication Communications link redundancy and security

(10) Redundancy and security of the emergency command center

(11) Ability to customize and add to prerecorded message library

(12) Messages should be tailored to the situation and audience

(13) Scripted messages for live voice messages

(14) Proper training of individuals that operate the system

Submitter Information Verification

Submitter Full Name: SIG-ECS

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

427 of 496 10/20/2016 11:03 AM

Page 428: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 23:35:19 EDT 2016

Committee Statement

CommitteeStatement:

As part of the Correlating Committee Task Group on terms, the term "communication(s)” wasreviewed throughout the entire document for proper use regarding reference to singular and pluraluse. The term should be plural use in this context.

ResponseMessage:

Public Input No. 464-NFPA 72-2016 [Section No. A.24.14]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

428 of 496 10/20/2016 11:03 AM

Page 429: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4011-NFPA 72-2016 [ Section No. A.26.3.4 ]

A.26.3.4

The terms certificated and placarded, which appeared in previous editions of NFPA 72, were consideredby some to be too specific to two listing organizations and were replaced with more generic wording. Theconcept of providing documentation to indicate ongoing compliance of an installed system continues to bereflected by the current language.

There are two distinct services offered by organizations that list fire alarm service provided by primecontractors and central stations. The first is the listing of these alarm services, which requires thecompanies to demonstrate they have the knowledge and ability to install, test, service, and maintaincentral station alarm systems and/or monitor and appropriately retransmit on receipt of various signalsfrom protected premises alarm systems.

The second part of the service provided by listing organizations is the certification of individual protectedpremises fire alarm systems to bring the alarm systems under their ongoing audit inspection program orsystematic follow-up program. Under this program, systems are certified by the listing organization, anddocumentation of this is to be provided, posted, and handled as described in 26.3.4 through 26.3.4.8 .The method used to document compliance with this portion of the program varies among listingorganizations and includes the issuance of certificates, placards, or other documentation.

There is nothing in this Code that requires all protected premises alarm systems monitored by a listedcentral station to be tested, maintained, serviced, monitored, and responded to in accordance withSection 26.3 . This is often misunderstood by code users, owners, and AHJs, who think that merelyspecifying that these systems be monitored by a central station with a fire alarm listing gets them fullcentral station service. Full compliance with central station alarm system requirements involves usingalarm companies with fire alarm listings and having the listing organization certify the protected premisesalarm system.

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 16:03:36 EDT 2016

Committee Statement

CommitteeStatement:

The additional text better explains the requirements related to listed companies andcode-compliant protected premises alarm systems.

ResponseMessage:

Public Input No. 602-NFPA 72-2016 [Section No. A.26.3.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

429 of 496 10/20/2016 11:03 AM

Page 430: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4018-NFPA 72-2016 [ Section No. A.26.3.6.6 ]

A.26.3.6.6

Two telephone lines (numbers) at the central station connected to the public switched telephone networkor a managed facilities-based voice network , each having its own telephone instrument connected, andtwo telephone lines (numbers) available at the communications center to which a central station operatorcan retransmit an alarm meet the intent of this requirement.

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 17:27:21 EDT 2016

Committee Statement

CommitteeStatement:

Adding the MFVN, along with the PSTN, clarifies equivalency between the two, in anticipationof the discontinuance of the PSTN.

ResponseMessage:

Public Input No. 603-NFPA 72-2016 [Section No. A.26.3.6.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

430 of 496 10/20/2016 11:03 AM

Page 431: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4021-NFPA 72-2016 [ Section No. A.26.4.3.1 ]

A.26.4.3.1

Consideration should be given to providing the following features for a proprietary supervising stationlocation:

(1) Fire resistive construction meeting the requirements of adopted building codes

(2) Air handling systems isolated from common building systems

As a useful guide for determining the nature of the design and integrity necessary to achieve properprotection, the proprietary supervising station building or that portion of a building occupied by aproprietary supervising station should compare the construction, fire protection, restricted access,emergency lighting, and power facilities to the requirements stated in the latest edition of ANSI/UL 827,Standard for Central- Station Alarm Services .

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 19:34:01 EDT 2016

Committee Statement

CommitteeStatement:

This revision is the result of a task group which was charged with making changes to thedocument to align the organization for central station service, proprietary station, and remotestation. These changes provide clarity and consistency of organizational formatting between thesesections.

ResponseMessage:

Public Input No. 304-NFPA 72-2016 [New Section after A.26.4.3.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

431 of 496 10/20/2016 11:03 AM

Page 432: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4023-NFPA 72-2016 [ Section No. A.26.5.3 ]

A.26.5.3

As a minimum, the room or rooms containing the remote supervising station equipment should have a1-hour fire rating, and the entire structure should be protected by an alarm system complying withChapter 23.

As a useful guide for determining the nature of the design and integrity necessary to achieve properprotection, the remote supervising station building or that portion of a building occupied by a remotesupervising station should compare the construction, fire protection, restricted access, emergencylighting, and power facilities to the requirements stated in the latest edition of ANSI/UL 827, Standard forCentral-Station Alarm Services .

If the remote supervising station is located within an emergency response agency (ERA), the ERA shouldconsider meeting the requirements of Chapter 4 of NFPA 1221 .

Submitter Information Verification

Submitter Full Name: SIG-SSS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 00:33:45 EDT 2016

Committee Statement

CommitteeStatement:

This revision is the result of a task group which was charged with making changes to thedocument to align the organization for central station service, proprietary station, and remotestation. These changes provide clarity and consistency of organizational formatting between thesesections.

ResponseMessage:

Public Input No. 308-NFPA 72-2016 [Section No. A.26.5.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

432 of 496 10/20/2016 11:03 AM

Page 433: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1531-NFPA 72-2016 [ Section No. A.29.3.5 ]

A.29.4.1

The use of the distinctive three-pulse temporal pattern fire alarm evacuation signal has beenrecommended by this Code since 1979. It has since been adopted as both an American NationalStandard (ANSI/ASA S3.41, American National Standard Audible Emergency Evacuation Signal) and anInternational Standard (ISO 8201, Audible Emergency Evacuation Signal).

Copies of both of these standards are available from either of the following:

The web at asa.aip.org/map_publications.html

Standards Publication Fulfillment, P.O., Box 1020, Sewickly, PA 15143-9998, Tel. 412-741-1979.

For information about the Acoustical Society of America, or for how and why the three-pulse temporalpattern signal was chosen as the international standard evacuation signal, contact Standards Secretariat,Acoustical Society of America, 35 Pinelawn Road, Suite 114E, Melville, NY 11747, Tel. 531-490-0215,Email: [email protected].

The standard fire alarm evacuation signal is a three-pulse temporal pattern using any appropriate sound.The pattern consists of the following in this order:

(1) An “on” phase lasting 0.5 second ±10 percent.

(2) An “off” phase lasting 0.5 second ±10 percent for three successive “on” periods.

(3) An “off” phase lasting 1.5 seconds ±10 percent [see Figure A.29.4.1(a) and Figure A.29.4.1(b)]. Thesignal should be repeated for a period appropriate for the purposes of evacuation of the building, butfor not less than 180 seconds. A single-stroke bell or chime sounded at “on” intervals lasting 1 second±10 percent, with a 2-second ±10 percent “off” interval after each third “on” stroke, is permitted [seeFigure A.29.4.1(c) ].

The minimum repetition time is permitted to be manually interrupted.

Figure A.29.4.1(a) Temporal Pattern Parameters.

Figure A.29.4.1(b) Temporal Pattern Imposed on Signaling Appliances That Emit ContinuousSignal While Energized.

Figure A.29.4.1(c) Temporal Pattern Imposed on Single-Stroke Bell or Chime.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

433 of 496 10/20/2016 11:03 AM

Page 434: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 10:33:10 EDT 2016

Committee Statement

CommitteeStatement:

A Correlating Committee task group on process reviewed the Code for consistency. Thereference to the web page is deleted because the referenced documents are not available on thesite.

ResponseMessage:

Public Input No. 622-NFPA 72-2016 [Section No. A.29.3.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

434 of 496 10/20/2016 11:03 AM

Page 435: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1536-NFPA 72-2016 [ Section No. A.29.7.8.2.1 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

435 of 496 10/20/2016 11:03 AM

Page 436: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

A.29.9.8.2.1

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

436 of 496 10/20/2016 11:03 AM

Page 437: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

For RF waves traveling along the earth surface, the signal power loss (in dB), Lp, can be calculated using

the following plane-earth propagation loss model:

[A.29.7.8.2.1a

where Dp represents the distance between the transmitter and receiver and hTX and hRX are the heights

of the transmitter and receiver, respectively, above the earth.

The plane earth propagation model is a practical simplification and requires that hTX, hRX << Dp. It

reflects the average expected attenuation due to distance of the RF carrier for a stationary set of radioswith an essentially clear line of sight. It predicts maximum communications range only in the UHF band(300 MHz to 3 GHz) and is not dependent on frequency.

Inside a building, the model can be expanded to determine the total path loss, LT, which includes the

plane earth loss, Lp (equation A.29.7.8.2.1a A.29.7.9.2.1a ), and the loss due to the building materials in

the propagation path, Lb, as follows:

[A.29.7.8.2.1b

If an equivalent open area test distance DEOAT is defined as follows:

[A.29.7.8.2.1c

then DEOAT can be shown to be:

[A.29.7.8.2.1d

The DEOAT function is used to calculate a test distance required to verify the functional range of wireless

alarm products. As noted above in the right side of equation A.29.7.8.2.1d A.29.7.9.2.1d , the functionrepresents two factors — one that describes the attenuation of a radio frequency signal due to plane earthpropagation path loss (Dp), and one that describes the dwelling material losses (Lb) in the signal’s

propagation path. It is the combination of dwelling loss and propagation path loss that is used in thecalculation of the test distance DEOAT. The losses are expressed in dB, and the unit for distances is

meter.

In reviewing average home sizes, a reliable (indoor) communication of 100 ft (30.5 m) is adequate for a

majority of dwellings, based on an average house size of 2200 ft2 (204 m2) [National Association of HomeBuilders]. Construction materials of a home (walls and floors) can attenuate an RF signal, with the RFsignal being attenuated more at higher frequencies [Stone, 1997]. Communication specifications fordevices of this type are typically specified as open field (no obstructions) test distances, and not in termsof attenuation. Therefore, the standard specifies a minimum open area test distance, DEOAT, that the RF

products must communicate. This distance is equal to 100 ft (30.5 m) (the longest straight line distancewithin a majority of homes) plus an additional distance that is equivalent to the attenuation of four wallsand two floors (the most straight line obstructions in a majority of homes). The additional distance variesdepending on the operating frequency of the product. Formulas for calculating DEOAT are included below,

along with examples for a number of different frequencies. These criteria are expected to yield reliableindoor communications at 100 ft (30.5 m) when used inside a majority of dwellings.

The building attenuation factor, Lb, represents the maximum attenuation value of typical floors and walls

within a majority of structures. Lb is calculated using attenuation values of different materials. The

following method is used to calculate Lb. The building materials attenuation coefficients specified in this

application are taken from Stone, 1977. Other sources of appropriate building material attenuationcoefficients may can be used; however, testing organizations should apply values consistently for allproducts tested.

L1 = Frequency dependent attenuation value for 1⁄2 in. (13 mm) drywall

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

437 of 496 10/20/2016 11:03 AM

Page 438: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

L2 = Frequency dependent attenuation value for 11⁄2 in. (38 mm) structural lumber

L3 = Frequency dependent attenuation value for 3⁄4 in. (19 mm) plywood

L4 = Frequency dependent attenuation value for 1⁄2 in. (13 mm) glass/tile floor

Lw = Attenuation value of a wall = 2 × L1 + L2

Lf = Attenuation value of a floor = L1 + L2 + L3 + L4

Assuming four walls and two floors,

[A.29.7.8.2.1e

The source for the equation in 29.9.8.2.1 is Stone, W. “Electromagnetic Attenuation in ConstructionMaterials,” National Institute of Standards and Technology, NISTIR 6055, 1997.

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 12:15:01 EDT 2016

Committee Statement

CommitteeStatement:

The term "may" shall not be used in any portion of the code in accordance with the Manualof Style.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

438 of 496 10/20/2016 11:03 AM

Page 439: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 1529-NFPA 72-2016 [ Section No. A.29.8.1.4 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

439 of 496 10/20/2016 11:03 AM

Page 440: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

7.8.2 Forms for Documentation.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

440 of 496 10/20/2016 11:03 AM

Page 441: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Forms for documentation shall be as follows:

(1)

(2)

(3) Where a form is required by the AHJ to document the installation and inspection of a household firealarm system or single- or multiple-station alarms, Figure 7.8.2(m) can be used to document therecord of completion and inspection .

Figure 7.8.2(a) System Record of Completion. (SIG-FUN)

* Unless otherwise permitted or required in 7.5.6 or 7.8.1.2, Figure 7.8.2(a) through Figure 7.8.2(f)shall be used to document the record of completion and inspection . (SIG-FUN)

* Unless otherwise permitted or required in 7.6.6 or 7.8.1.2, Figure 7.8.2(g) through Figure 7.8.2(l)shall be used to document the record of inspection and testing. (SIG-TMS)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

441 of 496 10/20/2016 11:03 AM

Page 442: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Figure 7.8.2(b) Emergency Communications System Supplementary Record of Completion.(SIG-FUN)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

442 of 496 10/20/2016 11:03 AM

Page 443: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Figure 7.8.2(c) Power Systems Supplementary Record of Completion. (SIG-FUN)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

443 of 496 10/20/2016 11:03 AM

Page 444: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

444 of 496 10/20/2016 11:03 AM

Page 445: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Figure 7.8.2(d) Notification Appliance Power Panel Supplementary Record of Completion.(SIG-FUN)

Figure 7.8.2(e) Interconnected Systems Supplementary Record of Completion. (SIG-FUN)

Figure 7.8.2(f) Deviations from Adopted Codes and Standards Supplementary Record ofCompletion. (SIG-FUN)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

445 of 496 10/20/2016 11:03 AM

Page 446: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Figure 7.8.2(g) System Record of Inspection and Testing. (SIG-TMS)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

446 of 496 10/20/2016 11:03 AM

Page 447: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

447 of 496 10/20/2016 11:03 AM

Page 448: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Figure 7.8.2(h) Notification Appliance Supplementary Record of Inspection and Testing.(SIG-TMS)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

448 of 496 10/20/2016 11:03 AM

Page 449: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Figure 7.8.2(i) Initiating Device Supplementary Record of Inspection and Testing. (SIG-TMS)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

449 of 496 10/20/2016 11:03 AM

Page 450: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Figure 7.8.2(j) Mass Notification System Supplementary Record of Inspection and Testing.(SIG-TMS)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

450 of 496 10/20/2016 11:03 AM

Page 451: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Figure 7.8.2(k) Emergency Communications Systems Supplementary Record of Inspection andTesting. (SIG-TMS)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

451 of 496 10/20/2016 11:03 AM

Page 452: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

452 of 496 10/20/2016 11:03 AM

Page 453: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Figure 7.8.2(l) Interface Component Supplementary Record of Inspection and Testing. (SIG-TMS)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

453 of 496 10/20/2016 11:03 AM

Page 454: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

454 of 496 10/20/2016 11:03 AM

Page 455: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Figure 7.8.2(m) Installation and Inspection Form Single- and Multiple-Station Smoke Alarms andHousehold Fire Alarm Systems.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

455 of 496 10/20/2016 11:03 AM

Page 456: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Supplemental Information

File Name Description

FR_1529_A.29.8.1.4_to_7.8.2_3_form_changes.docx Changes to form

FR-1529.pdf Marked-up form

Submitter Information Verification

Submitter Full Name: SIG-HOU

Organization: [ Not Specified ]

Street Address:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

456 of 496 10/20/2016 11:03 AM

Page 457: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

City:

State:

Zip:

Submittal Date: Wed Jul 27 00:27:16 EDT 2016

Committee Statement

CommitteeStatement:

The form is being relocated from A.29.8.1.4 to Chapter 7 to allow for required use and to beenforceable by the AHJ. See FR 1526 which points users from Chapter 29 to this form.

ResponseMessage:

Public Input No. 417-NFPA 72-2016 [Section No. A.29.8.1.4]

Public Input No. 336-NFPA 72-2016 [Section No. A.29.8.1.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

457 of 496 10/20/2016 11:03 AM

Page 458: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2020-NFPA 72-2016 [ Section No. B.2.3.1.4.2 ]

B.2.3.1.4.2

An example of a fire scenario in a computer room might be as follows.

The computer room is 9.1 m × 6 m (30 ft × 20 ft) and 2.8 m (8 ft) high. It is occupied 12 hours a day, 5days a week. The occupants are mobile and familiar with the building. There are no fixed fire suppressionsystems protecting this location. The fire department is capable of responding to the scene in 6 minutes,and an additional 15 minutes for fire ground evolution is needed.

Overheating of a resistor leads to the ignition of a printed circuit board and interconnecting cabling. Thisleads to a fire that quickly extends up into the above- ceiling space containing power and communicationscabling. The burning of this cabling produces large quantities of dense, acrid smoke and corrosiveproducts of combustion that spread throughout the computer suite. This causes the loss of essentialcomputer and telecommunications services for 2 months.

Submitter Information Verification

Submitter Full Name: SIG-IDS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 20:22:58 EDT 2016

Committee Statement

CommitteeStatement:

A Correlating Committee Task Group on language/terms reviewed the language of the Code forconsistency and grammar.

The Technical Committee revises the “above ceiling" phrase to add a hyphen to clarify the intentbecause the term comes before a noun and intends to modify and act as a single idea.Additionally, to be consistent with usage elsewhere in the same clause.

ResponseMessage:

Public Input No. 640-NFPA 72-2016 [Section No. B.2.3.1.4.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

458 of 496 10/20/2016 11:03 AM

Page 459: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3061-NFPA 72-2016 [ Section No. C.2.2.1 [Excluding any

Sub-Sections] ]

Determine an alarm emergency response plan considering the requirements of NFAC, local codes andregulations, the availability and responsibility of building operating personnel, and the mobility ofoccupants.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Sun Aug 07 11:01:39 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text by replacing the term “alarm response plan” with theterm defined by NFPA 72, “emergency response plan.”

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

459 of 496 10/20/2016 11:03 AM

Page 460: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3062-NFPA 72-2016 [ Section No. C.2.2.1.1 ]

C.2.2.1.1 Investigation.

Building security or operating personnel should investigate every alarm signal, and the alarm emergencyresponse plan might include investigation of initial alarm signals prior to activating a general alarm or theevacuation or relocation of occupants.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Sun Aug 07 11:02:28 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text by replacing the term “alarm response plan” with theterm defined by NFPA 72, “emergency response plan.”

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

460 of 496 10/20/2016 11:03 AM

Page 461: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3048-NFPA 72-2016 [ Section No. C.2.2.1.7 ]

C.2.2.1.7 Fire Scene Operations.

Compartmentation, water supply, fire fighter access, and communication links are important for manualfire-fighting operations. Fire alarm system monitoring, reporting, display, and control functions thatenhance the maintenance and operation of these elements that enhance fire scene operations should beconsidered in the design, installation, and maintenance of protected premises fire alarm systems. Anexample would be a flashing light visible notification appliance over the fire department connection.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 15:27:11 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text to be more consistent with terminology usedthroughout NFPA 72.

Response Message:

Public Input No. 262-NFPA 72-2016 [Section No. C.2.2.1.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

461 of 496 10/20/2016 11:03 AM

Page 462: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3049-NFPA 72-2016 [ Section No. C.3 ]

C.3 Premises Mission/Use/Property Protection.

The loss of use or mission of a facility to the effects of accidental fire can have a very significant impact onthe community or organization served by the facility. In such a case, it is appropriate to enhance functionalcharacteristics of the protected premises system. Considerations include the following:

(1) Criticality/Mission Continuity

(a) Community — Loss of operations of the facility might affect the community beyond the facility.Consider the sensitivity of fire detection and the effectiveness of alarm processing, emergencyresponse, and fire suppression to minimize effects on the community served due to facilityimpairment by fire.

(b) Operations

i. On-premises — Fire might result in business interruption or reduced effectiveness.

ii. Elsewhere — Services provided by the facility to remote locations might cease or bereduced.

(2) Life Safety

(a) Evacuation/Relocation — Size, distribution, and mobility of the occupant population should beconsidered with knowledge of facility emergency planning and availability of emergencyresponse resources to determine the extent to which people movement might be managedduring a fire incident.

(b) Defend- In- Place — A protected premises system might be used to activate facility fire safetyelements necessary to defend occupants in place or to enhance rescue assistance.

(3) Property

(a) Value — Cost, availability, and time required to reestablish facility contents should be consideredwhen determining the sensitivity of fire detection and the effectiveness of alarm processing,emergency response, and fire suppression.

(b) Replacement — Availability and time required to replace damaged facility contents should beconsidered when determining the sensitivity of fire detection and the effectiveness of alarmprocessing emergency response and fire suppression.

(c) Redundancy — Duplication of facility contents in separate locations might reduce the need forsensitivity of fire detection or other property protection system capabilities.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 05 15:29:42 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises the text to be consistent with the use of the term defend-in-place as used in NFPA 72.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

462 of 496 10/20/2016 11:03 AM

Page 463: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

ResponseMessage:

Public Input No. 626-NFPA 72-2016 [Section No. C.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

463 of 496 10/20/2016 11:03 AM

Page 464: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4525-NFPA 72-2016 [ Section No. D.2.3.1.2 ]

D.2.3.1.2

All parts of a building or area intended to have occupant notification are subdivided into ADSs as defined.Some ADSs might be designated to have voice communication communications capability and requirethat those communications be intelligible. Other spaces might not require voice intelligibility or might notbe capable of reliable voice intelligibility. Each is still referred to as an ADS.

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jul 29 13:55:48 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text to correlate with task group work by the CorrelatingCommittee, whereby “communication” as used in this particular context should be pluralized.

ResponseMessage:

Public Input No. 465-NFPA 72-2016 [Section No. D.2.3.1.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

464 of 496 10/20/2016 11:03 AM

Page 465: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4527-NFPA 72-2016 [ Section No. D.2.5.4 ]

D.2.5.4

In areas where the ambient sound pressure level exceeds 90 dBA, speech satisfactory speechintelligibility is difficult to achieve with conventional communications equipment and design practice. Abetter system design might include alternate communications methods, such as signs and displays, ormight involve providing occupant notification but not voice alarm communication at that location.

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jul 29 14:12:03 EDT 2016

Committee Statement

CommitteeStatement:

The redundant language has been removed but voice alarm has been left the way it isbecause it already conveys dual capability.

ResponseMessage:

Public Input No. 466-NFPA 72-2016 [Section No. D.2.5.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

465 of 496 10/20/2016 11:03 AM

Page 466: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4505-NFPA 72-2016 [ Section No. D.3.2.3 ]

D.3.2.3 Emergency Communications System Control Panel Unit .

The system under test for the emergency communications system should be located and identified prior totesting, and its operation features necessary for the testing clarified. Personnel who are authorized toaccess and service the control panel unit are necessary for the testing and should be included within theteam performing the tests. If necessary, notification to locations beyond the facility that is being tested(e.g., fire department or a supervising station) should be notified of the tests, and if appropriate, theirautomatic notification feature disabled. Upon completion of the tests the emergency communicationssystem should be returned to its normal operating condition.

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 19:41:49 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises the text to replace “panel” with “unit” and thereby correlatewith the definition of an Emergency Communications System Control Unit in Chapter 3.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

466 of 496 10/20/2016 11:03 AM

Page 467: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4506-NFPA 72-2016 [ Section No. D.6.5 ]

D.6.5 Unoccupied Testing.

D.6.5.1 General.

Testing of speech intelligibility in the presence of the occupied ambient sound pressure level is thepreferred method. However, for various reasons, including disruption of normal work, it might be desirableto only do “silent” testing during occupied periods and to do testing with the STI or STIPA test signalduring unoccupied or less occupied conditions.

D.6.5.2 Number of Tests.

This test method requires three different measurements at each measurement point, typically made duringtwo site visits. The data for each measurement is saved in a format in accordance with the instrumentmanufacturer’s requirements. The three data files are then post-processed to arrive at the final correctedSTI.

D.6.5.3 Occupied Ambient Sound Pressure Level Measurement.

D.6.5.3.1

At each measurement point in each ADS measure the occupied ambient sound pressure level.

D.6.5.3.2

Save the measurement data in accordance with the instrument manufacturer’s requirements to permitpost-processing of the data.

D.6.5.3.3

Document the results in writing on plans or forms in a way that accurately describes the measurementpoint and that permits future testing at the same locations.

D.6.5.4 Unoccupied Ambient Sound Pressure Level Measurement.

D.6.5.4.1

At each measurement point in each ADS measure the unoccupied ambient sound pressure level.

D.6.5.4.2

Save the measurement data in accordance with the instrument manufacturer’s requirements to permitpost-processing of the data.

D.6.5.4.3

Document the results in writing on plans or forms in a way that accurately describes the measurementpoint and that permits future testing at the same locations.

D.6.5.5 Unoccupied STI Measurement.

D.6.5.5.1

Set up the talkbox in accordance with Section D.4 and start the STI or STIPA test signal.

D.6.5.5.2

At each measurement point in each ADS measure the uncorrected STI.

D.6.5.5.3

Save the measurement data in accordance with the instrument manufacturer’s requirements to permitpost-processing of the data.

D.6.5.5.4

Document the results in writing on plans or forms in a way that accurately describes the measurementpoint and that permits future testing at the same locations.

D.6.5.6 Post- Processing.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

467 of 496 10/20/2016 11:03 AM

Page 468: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

D.6.5.6.1

The corrected STI is arrived at by post-processing of the occupied ambient sound pressure levelmeasurement, the unoccupied ambient sound pressure level measurement, and the unoccupied STImeasurement. In effect, the measured STI (uncorrected) is being corrected by adding in the effects of theactual expected (occupied) ambient sound pressure level.

D.6.5.6.2

The post- processing procedure or software provided by the instrument manufacturer should be used tocalculate the final corrected STI for each measurement point.

D.6.5.6.3

Document the results in writing on plans or forms in a way that accurately describes the measurementpoint and that permits future testing at the same locations.

D.6.5.6.4

Documentation of the final results for each point should include the results of all three measurements andthe final corrected STI value. The manufacturer’s software revision should also be included in the resultsdocumentation.

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 20:00:30 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee removed the words "in writing" because they were found to beunnecessary.

Response Message:

Public Input No. 340-NFPA 72-2016 [Sections 14.2.2.2.3, 14.2.2.2.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

468 of 496 10/20/2016 11:03 AM

Page 469: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3071-NFPA 72-2016 [ Section No. F.1 ]

F.1

Circuit class designations in this edition of the Code are Class A, B, C, D, E, R, S, N, and X. Definitionscan be found in Chapter 12. Additionally, special circuits unique to supervising stations are designated asTypes 4, 5, 6, and 7, and definitions can be found in Chapter 26.

The wiring diagrams depicted in Figure F.2.1.1 through Figure F.3.14(k) are representative of typicalcircuits encountered in the field and are not intended to be all-inclusive.

The noted symbols are as indicated in NFPA 170.

An individual point-identifying (i.e., addressable) fire alarm initiating device operates on a signaling linecircuit and is designated as a Class A, Class B, or Class X initiating device circuit. All fire alarm circuitsmust test free of grounds because metallic conductors will cause failure of the circuit when a secondground condition occurs on the same power source.

Nonmetallic circuit paths, such as wireless and fiber-optic, may might still be designated as Class A, B, orX if they meet the other performance requirements of those pathways.

Ground-fault detection is not required for all circuits that might be interconnected with the fire alarmsystem. Therefore, tests for ground-fault detection should be limited to those circuits equipped withground-fault detection. The Class R designation is for a redundant circuit that can use metallicconductors, but is not concerned with ground fault detection. Class S is a single path supervised circuitthat can use metallic conductors, but is not concerned with ground fault detection.

The following initiating device circuits are illustrative of either alarm or supervisory signaling. Alarm-initiating devices and supervisory initiating devices are not permitted to have identical annunciation at thefire alarm control unit.

Directly connected system smoke detectors, commonly referred to as two-wire detectors, should be listedas being electrically and functionally compatible with the fire alarm control unit and the specific subunit ormodule to which they are connected. If the detectors and the units or modules are not compatible, it ispossible that, during an alarm condition, the detector's visible indicator will illuminate, but no change ofstate to the alarm condition will occur at the fire alarm control unit. Incompatibility can also prevent propersystem operation at extremes of operating voltage, temperature, and other environmental conditions.

Where two or more two-wire detectors with integral relays are connected to a single initiating devicecircuit, and their relay contacts are used to control essential building functions (e.g., fan shutdown,elevator recall), it should be clearly noted that the circuit might be capable of supplying only enoughenergy to support one detector/relay combination in an alarm mode. If control of more than one buildingfunction is required, each detector/relay combination used to control separate functions should beconnected to separate initiating device circuits, or they should be connected to an initiating device circuitthat provides adequate power to allow all the detectors connected to the circuit to be in the alarm modesimultaneously. During acceptance and reacceptance testing, this feature should always be tested andverified.

A speaker is an alarm notification appliance, and, if used as shown in the diagrams in Section F.2, theprinciple of operation and supervision is the same as for other audible alarm notification appliances (e.g.,bells and horns).

The testing of supervised remote relays is to be conducted in the same manner as for notificationappliances.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

469 of 496 10/20/2016 11:03 AM

Page 470: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

City:

State:

Zip:

Submittal Date: Sun Aug 07 14:08:23 EDT 2016

Committee Statement

Committee Statement: Changed text to conform to manual of style and added Class N circuit designation.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

470 of 496 10/20/2016 11:03 AM

Page 471: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4528-NFPA 72-2016 [ Section No. F.1 ]

F.1

Circuit class designations in this edition of the Code are Class A, B, C, D, E, R, S, N, and X. Definitionscan be found in Chapter 12. Additionally, special circuits unique to supervising stations are designated asTypes 4, 5, 6, and 7, and definitions can be found in Chapter 26.

The wiring diagrams depicted in Figure F.2.1.1 through Figure F.3.14(k) are representative of typicalcircuits encountered in the field and are not intended to be all-inclusive.

The noted symbols are as indicated in NFPA 170.

An individual point-identifying (i.e., addressable) fire alarm initiating device operates on a signaling linecircuit and is designated as a Class A, Class B, or Class X initiating device circuit. All fire alarm circuitsmust test free of grounds because metallic conductors will cause failure of the circuit when a secondground condition occurs on the same power source.

Nonmetallic circuit paths, such as wireless and fiber-optic, may might still be designated as Class A, B, orX if they meet the other performance requirements of those pathways.

Ground-fault detection is not required for all circuits that might be interconnected with the fire alarmsystem. Therefore, tests for ground-fault detection should be limited to those circuits equipped withground-fault detection. The Class R designation is for a redundant circuit that can use metallicconductors, but is not concerned with ground fault detection. Class S is a single path supervised circuitthat can use metallic conductors, but is not concerned with ground fault detection.

The following initiating device circuits are illustrative of either alarm or supervisory signaling. Alarm-initiating devices and supervisory initiating devices are not permitted to have identical annunciation at thefire alarm control unit.

Directly connected system smoke detectors, commonly referred to as two-wire detectors, should be listedas being electrically and functionally compatible with the fire alarm control unit and the specific subunit ormodule to which they are connected. If the detectors and the units or modules are not compatible, it ispossible that, during an alarm condition, the detector's visible indicator will illuminate, but no change ofstate to the alarm condition will occur at the fire alarm control unit. Incompatibility can also prevent propersystem operation at extremes of operating voltage, temperature, and other environmental conditions.

Where two or more two-wire detectors with integral relays are connected to a single initiating devicecircuit, and their relay contacts are used to control essential building functions (e.g., fan shutdown,elevator recall), it should be clearly noted that the circuit might be capable of supplying only enoughenergy to support one detector/relay combination in an alarm mode. If control of more than one buildingfunction is required, each detector/relay combination used to control separate functions should beconnected to separate initiating device circuits, or they should be connected to an initiating device circuitthat provides adequate power to allow all the detectors connected to the circuit to be in the alarm modesimultaneously. During acceptance and reacceptance testing, this feature should always be tested andverified.

A speaker is an alarm notification appliance, and, if used as shown in the diagrams in Section F.2, theprinciple of operation and supervision is the same as for other audible alarm notification appliances (e.g.,bells and horns).

The testing of supervised remote relays is to be conducted in the same manner as for notificationappliances.

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

471 of 496 10/20/2016 11:03 AM

Page 472: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

City:

State:

Zip:

Submittal Date: Fri Jul 29 14:14:38 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee edits the text in line with a review conducted by the CorrelatingCommittee and for consistency with Chapter 12. Class R and Class S have been removed fromChapter 12 and Class N has been added. The above text will harmonize accordingly.

ResponseMessage:

Public Input No. 717-NFPA 72-2016 [Section No. F.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

472 of 496 10/20/2016 11:03 AM

Page 473: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4530-NFPA 72-2016 [ Section No. F.4 ]

F.4 Batteries.

To maximize battery life, nickel-cadmium batteries should be charged as in Table F.4(a) .

To maximize battery life, the battery voltage for lead-acid cells should be maintained within the limitsshown in Table F.4(b) .

The following procedure is recommended for checking the state of charge for nickel-cadmium batteries:

The battery charger should be switched from float to high-rate mode.

The current, as indicated on the charger ammeter, will immediately rise to the maximum output ofthe charger, and the battery voltage, as shown on the charger voltmeter, will start to rise at thesame time.

The actual value of the voltage rise is unimportant, because it depends on many variables. Thelength of time it takes for the voltage to rise is the important factor.

If, for example, the voltage rises rapidly in a few minutes, then holds steady at the new value, thebattery is fully charged. At the same time, the current will drop to slightly above its original value.

In contrast, if the voltage rises slowly and the output current remains high, the high-rate chargeshould be continued until the voltage remains constant. Such a condition is an indication that thebattery is not fully charged, and the float voltage should be increased slightly.

Table F.4(a) Voltage for Nickel-Cadmium Batteries

Float voltage 1.42 volts/cell +0.01 volt

High-rate voltage 1.58 volts/cell +0.07 volt −0.00 volt

Note: High- and low-gravity voltages are (+) 0.07 volt and (−) 0.03 volt respectively.

Table F.4(b) Voltage for Lead-Acid Batteries

Float

Voltage

High-Gravity Battery (Lead Calcium) Low-Gravity Battery (Lead Antimony)

Maximum 2.25 volts/cell 2.17 volts/cell

Minimum 2.20 volts/cell 2.13 volts/cell

High-rate voltage — 2.33 volts/cell

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 02 21:35:56 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee makes the change to delete battery types not used, (i.e., ventedlead-acid and Nickel-cadmium) as the test methods do not align with IEEE standards and containtechnical errors. Associated PI-133 refers to IEEE standards 450 and 1106 in Table 14.4.3.2

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

473 of 496 10/20/2016 11:03 AM

Page 474: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

footnote d) for proper maintenance, testing, and replacement of other battery types.

ResponseMessage:

Public Input No. 152-NFPA 72-2016 [Section No. F.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

474 of 496 10/20/2016 11:03 AM

Page 475: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 3065-NFPA 72-2016 [ Section No. G.2.2.1 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

475 of 496 10/20/2016 11:03 AM

Page 476: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

G.2.2.1 The Message.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

476 of 496 10/20/2016 11:03 AM

Page 477: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Regardless of the method used to disseminate the warning message, there are certain characteristics thatare required of an effective warning message. These are included here:

(1) Message Content.

(a) A warning message should contain five important topics to ensure that occupants have sufficientinformation to respond.

i. Who is providing the message? (i.e., the source of the message)

ii. What should people do? (i.e., what actions occupants should take in response to theemergency and, if necessary, how to take these actions)

iii. When do people need to act? (In rapid-onset events, the “when” is likely to be“immediately.”)

iv. Where is the emergency taking place? (i.e., who needs to act and who does not)

v. Why do people need to act? (including a description of the hazard and itsdangers/consequences)

(b) The source of the message should be someone who is perceived as credible by the occupants

(c) Building managers, campus managers, and emergency personnel should understand theaffected population and, from this understanding, develop a database of possible trusted sources(as well as backup sources).

(2) Message Structure.

(a) Message order for short messages (e.g., 90-characters) should be the following:

i. Source

ii. Guidance on what people should do

iii. Hazard (why)

iv. Location (where)

v. Time.

(b) Message order for longer messages should be the following:

i. Source

ii. Hazard

iii. Location

iv. Guidance

v. Time

(c) Numbered lists can help to chronologically organize multiple steps in a process

(d) For limited message length, message writers could draft the message in a bulleted form; each ofthe five topics in the warning should be separated as its own bullet point

(e) Distinct audiences should be addressed separately in the message (or in multiple messages)

(3) Message Language (or Wording).

(a) Messages should be written using short, simple words, omitting unnecessary words or phrases.

(b) Messages should be written using active voice, present tense, avoiding hidden verbs.

(c) Messages should be written using short, simple, and clear sentences, avoiding double negativesand exceptions to exceptions; main ideas should be placed before exceptions and conditions.

(d) Emergency messages should be written at a sixth grade reading level or lower. An emergencymessage can be evaluated for its reading level using computer software and/or a simplecalculation.

(e) Emergency messages should be written without the use of jargon and false cognates.

(f) Emergency messages should be provided in the language of the predominant affected populace.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

477 of 496 10/20/2016 11:03 AM

Page 478: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

If there is a possibility of isolated groups that do not speak the predominant language,multilingual messages should be provided. It is expected that small groups of transientsunfamiliar with the predominant language will be picked up in the traffic flow in the event of anemergency and are not likely to be in an isolated situation.

(4) Multiple Messages.

(a) Building managers, campus managers, and emergency personnel should anticipate the need towrite more than one emergency message throughout a disaster, including feedback messages orupdates.

(b) In update messages, occupants should be told why the information has changed, to ensure thatthe new message is viewed as credible.

(c) Provide feedback messages after a “non-event” to inform occupants that the alert signal andwarning system operated and worked as planned and the reasons why the event did not occur.

(d) Building managers, campus managers, and emergency personnel should test emergencymessages with the affected population.

(5) Visual Warnings.

(a) Messages that are displayed visually will have different capabilities and limitations than thosedisseminated audibly. Message creators should consider different factors and make differenttypes of decisions based upon the dissemination method. The first consideration is the type ofvisual technology that will be used to disseminate the messages, which can include textual visualdisplays, SMS text messages, computer pop-ups, email, Internet websites, news (TV broadcast),or streaming broadcast over the web. Depending upon the technology chosen to display visualwarning messages, guidance is provided here on message displays to enable occupants to seeor notice the displayed warning, understand the warning, perceive warning credibility and risk,and respond appropriately.

(6) Noticing and Reading the Warning.

(a) Place the emergency sign in a location where people will notice it and be able to read it from theiroriginal (pre-emergency) location.

(b) Signs will be reliably conspicuous within 15 degrees of the direct line of sight.

(c) Text is easier to read when written with a mixture of upper and lower case letters rather than theuse of all capitals.

(d) The recommended relationship for older adults with lower visual acuity is D = 100 * h, providing amore conservative result, and ensuring that a larger population will be able to read theemergency message.

(e) A stroke-to-width ratio of the letters is suggested as 1:5 (generally), with a ratio of 1:7 suggestedfor lighter letters on a darker background.

(f) Building managers, campus managers, or emergency personnel should consult the ADAStandards for Accessible Design (U.S. Department of Justice 2010) for additional requirementson signage.

(g) Contrast between the text and the background should be at least 30 percent, althoughrecommended values could be as high as 60 percent.

(h) The use of pictorials (in lieu of or in addition to text) can also bring attention to the sign.

(i) Message providers should ensure that emergency information is not blocked by other signs orinformation.

(7) Comprehending, Believing, and Personalizing the Warning.

(a) Printed text should accompany symbols or pictorials used in visual warnings; a minimum numberof words should be used to accompany graphics.

(b) Diagrams that display a series of sequential steps are more successful for comprehension of aprocess than one single graphic.

(c) A color-contrasted word or statement should be used for text that should be read first and/or beperceived as more urgent than the rest, unless color is used for other reasons (e.g. bilingual

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

478 of 496 10/20/2016 11:03 AM

Page 479: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

text).

(d) A warning message can increase in perceived credibility and risk if occupants are shown thatothers are also responding.

(e) Simultaneously displayed text (discrete messages) is preferred rather than a sequentiallydisplayed message.

(f) Simultaneously displayed text can also be used for bilingual messages, especially if care is takento differentiate the text of one language from the text of the other language.

(g) Limit the use of flashing words on visual message displays.

(8) Audible Warnings.

(a) There are specific warning technologies that only (or primarily) affect the aural sense, includingpublic address systems (voice notification systems), automated voice dialing, satellite/AM/FMradio broadcasts, satellite/off-air television broadcasts, and tone alert radios. Whereas visualtechnologies can limit message length, audible warnings are often limited only by the attentioncapabilities of the audience. In other words, an audible message can play for long periods of timewith these technology types, and the message creator and source must be careful to provide allimportant information in an appropriate length of time.

(b) In this section, guidance will be given for methods to increase the likelihood that an individual willperceive, or hear, the message. Following this, guidance will be provided that can increasecomprehension of the message for audible messages, as well as the ways in which to increasecredibility and risk assessment of the event when the warning is presented audibly.

(9) Perception.

(a) Other, non-alert/warning voices in the background should be reduced or eliminated.

(b) Any voice announcements should also be accompanied by simultaneous visual text.

(10) Comprehending, Believing, and Personalizing the Warning.

(a) Letters are more difficult to identify in speech than numbers, which are more difficult than colors.

(b) Message speakers People making announcements (or other message sources) should not beheavily accented and should speak with a rate of approximately 175 words per minute.

(c) Audible warnings can be delivered using a live voice, dynamic voice (generated by text-to-speech software), or using pre-recorded voice.

(d) The live voice and dynamic voice methods provide the benefit of messages that can be updatedwith new information while also conveying an appropriate level of urgency, if necessary.

(e) Dynamic and pre-recoded voice methods provide the benefits of easily repeating the playedmessages for longer periods of time and not relying on the voice announcer training or stresslevel while delivering the message.

(f) For the voice itself, best results will vary, depending on the specific location — for example, inoutdoor applications, it has been shown that a male voice will provide better intelligibility, as thenaturally lower frequency of the male voice travels better. Inversely, in an interior application,where the background ambient noise is typically in the same lower frequencies, a female voicetends to penetrate better, as it is more distinct from the ambient.

(g) Urgency measures should be used selectively to emphasize the more dangerous, immediate,life-threatening situations (since overuse can lead to non-response in future disasters).

(11) Dissemination of the Warning Message.

(a) Use multiple channels to disseminate the warning message, including visual, audible, and tactilemeans.

(b) A warning message should be repeated at least once, with some research advocating formessage repetition of at least three times.

(c) Messages should be stated in full, and then repeated in full, rather than repeating statementswithin the same message.

(d) Warning messages should be repeated at intervals, rather than consecutively.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

479 of 496 10/20/2016 11:03 AM

Page 480: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

(e) Warning messages should be disseminated as early as possible.

(f) Face-to-face communication should accompany other audible or visual technologies.

(g) Messages should be disseminated using a combination of both push and pull technologies.

(h) Push communication2 is most important to use for alert signals as well as initial warningmessages.

Submitter Information Verification

Submitter Full Name: SIG-PRO

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Sun Aug 07 11:19:15 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee revises the Annex section to solve the issue proposed, where in somecases the word “speaker” refers to a physical appliance while other sections use it to refer to aperson.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

480 of 496 10/20/2016 11:03 AM

Page 481: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 4515-NFPA 72-2016 [ New Section after G.6 ]

Annex H Dangers of Carbon Monoxide

This annex is not a part of the requirements of this NFPA document but is included for informationalpurposes only.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

481 of 496 10/20/2016 11:03 AM

Page 482: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

H.1 Carbon Monoxide.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

482 of 496 10/20/2016 11:03 AM

Page 483: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Carbon monoxide is an odorless, tasteless, colorless gas produced by incomplete combustion. Solid,liquid, or gaseous fuels can each, under certain conditions, produce lethal concentrations in the home.(See Table H.1 and Figure H.1 .)

Table H.1 Symptoms of Carbon Monoxide Exposure Based on Concentration

Concentration(ppm CO)

Symptoms

50 No adverse effects with 8 hours of exposure

200 Mild headache after 2–3 hours of exposure

400 Headache and nausea after 1–2 hours of exposure

800Headache, nausea, and dizziness after 45 minutes of exposure; collapse andunconsciousness after 2 hours of exposure

1,000 Loss of consciousness after 1 hour of exposure

1,600 Headache, nausea, and dizziness after 20 minutes of exposure

3,200Headache, nausea, and dizziness after 5–10 minutes of exposure; collapse andunconsciousness after 30 minutes of exposure

6,400Headache and dizziness after 1–2 minutes of exposure; unconsciousness anddanger of death after 10–15 minutes of exposure

12,800 (1.28% byvolume)

Immediate physiological effects; unconsciousness and danger of death after 1–3minutes of exposure

Figure H.1 Carbon Monoxide Concentration (ppm CO) Versus Time (Minutes).

The values in Table H.1 are approximate values for healthy adults. Children, the elderly, and personswith preexisting physical conditions might be more susceptible to the effects of carbon monoxideexposure. Continued exposure after unconsciousness can cause death. The dangers of carbonmonoxide exposure depend on a number of variables, such as the occupant’s health, activity level, timeof exposure, and initial carboxyhemoglobin (COHb) level. Due to these variables, Table H.1 andFigure H.1 are to be used as general guidelines and might not appear quantitatively consistent.

The following equation for determining the estimated percent of COHb in the blood is from “A proposalfor evaluating human exposure to carbon monoxide contamination in military vehicles,” by Steinbergand Nielson and “Considerations for the physiological variables that determine the bloodcarboxyhemoglobin concentration in man” by Coburn, Forster, and Kane.

[H.1]

where:

% COHb t = percentage of COHb at time t

% COHb 0 = percentage of COHb in the blood at time 0

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

483 of 496 10/20/2016 11:03 AM

Page 484: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

t = time (minutes)

B = 0.0404 (work effort)

ppm CO = parts per million carbon monoxide

Supplemental Information

File Name Description

Annex_Equation.1466716184475.doc Equation to go in Annex H

Figure_H_1.1466716168212.docx Please relabel as H.1 and put in annex H

Table_H_1.1466535440816.docx Please re-label as Table H.1 and insert into Annex H

Submitter Information Verification

Submitter Full Name: SIG-TMS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 28 23:13:43 EDT 2016

Committee Statement

CommitteeStatement:

The Technical Committee provides new language to incorporate NFPA 720 requirements intoChapter 14 in accordance with the guidance of the 720/72 Consolidation Task Group.

ResponseMessage:

Public Input No. 378-NFPA 72-2016 [New Section after G.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

484 of 496 10/20/2016 11:03 AM

Page 485: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

First Revision No. 2541-NFPA 72-2016 [ Chapter H ]

Annex I Informational References

I.1 Referenced Publications.

The documents or portions thereof listed in this annex are referenced within the informational sections ofthis Code and are not part of the requirements of this document unless also listed in Chapter 2 for otherreasons.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

485 of 496 10/20/2016 11:03 AM

Page 486: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

I.1.1 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 3, Recommended Practice for Commissioning of Fire Protection and Life Safety Systems, 2015edition.

NFPA 4, Standard for Integrated Fire Protection and Life Safety System Testing, 2015 2017 edition.

NFPA 10, Standard for Portable Fire Extinguishers, 2013 2017 edition.

NFPA 11, Standard for Low-, Medium-, and High-Expansion Foam, 2016 edition.

NFPA 12, Standard on Carbon Dioxide Extinguishing Systems, 2015 2018 edition.

NFPA 12A, Standard on Halon 1301 Fire Extinguishing Systems, 2015 2018 edition.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2016 2019 edition.

NFPA 14, Standard for the Installation of Standpipe and Hose Systems, 2013 2019 edition.

NFPA 15, Standard for Water Spray Fixed Systems for Fire Protection, 2012 2017 edition.

NFPA 17, Standard for Dry Chemical Extinguishing Systems, 2013 2017 edition.

NFPA 17A, Standard for Wet Chemical Extinguishing Systems, 2013 2017 edition.

NFPA 70®, National Electrical Code®, 2014 2017 edition.

NFPA 80, Standard for Fire Doors and Other Opening Protectives, 2016 2017 edition.

NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems, 2015 2018 edition.

NFPA 90B, Standard for the Installation of Warm Air Heating and Air-Conditioning Systems, 2015 2018edition.

NFPA 92, Standard for Smoke Control Systems, 2015 2018 edition.

NFPA 101®, Life Safety Code®, 2015 2018 edition.

NFPA 105, Standard for Smoke Door Assemblies and Other Opening Protectives, 2016 2019 edition.

NFPA 170, Standard for Fire Safety and Emergency Symbols, 2015 2018 edition.

NFPA 551, Guide for the Evaluation of Fire Risk Assessments, 2013 2019 edition.

NFPA 720 , Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment ,2015 edition.

NFPA 730, Guide for Premises Security, 2014 2017 edition.

NFPA 731, Standard for the Installation of Electronic Premises Security Systems , 2017 edition.

NFPA 750, Standard on Water Mist Fire Protection Systems, 2015 2019 edition.

NFPA 909, Code for the Protection of Cultural Resource Properties — Museums, Libraries, and Places ofWorship, 2013 2017 edition.

NFPA 914, Code for Fire Protection of Historic Structures, 2015 2019 edition.

NFPA 1221, Standard for the Installation, Maintenance, and Use of Emergency Services CommunicationsSystems, 2016 2019 edition.

NFPA 1600®, Standard on Disaster/Emergency Management and Business Continuity Programs,2013 2019 edition.

NFPA 5000®, Building Construction and Safety Code®, 2015 2018 edition.

Fire Protection Research Foundation, Optimizing Fire Alarm Notification for High Risk Groups, 2007.

I.1.2 Other Publications.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

486 of 496 10/20/2016 11:03 AM

Page 487: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

I.1.2.1 ANSI Publications.

American National Standards Institute, Inc., 25 West 43rd Street, 4th floor, New York, NY 10036.

ANSI/ASME A17.1/CSA B44, Safety Code for Elevators and Escalators, 2013.

ANSI/FM 3260, American National Standard for Energy-Sensing Fire Detectors for Automatic Fire AlarmSignaling,2004 2014 .

ANSI S3.2, Method for Measuring the Intelligibility of Speech Over Communications Systems, 1989,revised 2009.

ANSI/UL 827, Standard for Central-Station Alarm Services, 2014.

ANSI S3.41, American National Standard Audible Emergency Evacuation Signal , 1990, reaffirmed2008.

ANSI/UL 268, Standard for Smoke Detectors for Fire Alarm Systems , 6th edition, 2009.

ANSI/UL 864, Standard for Control Units and Accessories for Fire Alarm Systems , 9th edition, 2003,revised 2012.

ANSI/UL 1638, Standard for Visual Signaling Appliances — Private Mode Emergency and General UtilitySignaling, 4th edition, 2001, revised 2013.

ANSI/UL 1971, Standard for Signaling Devices for the Hearing Impaired , 3rd edition, 2002, revised2013.

I.1.2.2 ASME Publications.

American Society of Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990.

ASME A.17.2, Guide for Inspection of Elevators, Escalators and Moving Walks, 2012 2014 .

I.1.2.3 FEMA Publications.

FEMA Headquarters, 500 C Street, SW, Washington DC, 20472.

FEMA Publication CPG-17, Outdoor Warning Systems Guide, March, 1980.

I.1.2.4 FM Publications.

FM Global, 1301 Atwood Avenue, P.O. Box 7500, Johnston, RI 02919.

FM 3210, Heat Detectors for Automatic Fire Alarm Signaling, 2007.

I.1.2.5 IEC Publications.

International Electrotechnical Commission, 3 rue de Varembé, P.O. Box 131, CH-1211 Geneva 20,Switzerland. IEC documents are available through ANSI.

IEC 60268, Sound system equipment — Part 16: Objective rating of speech intelligibility by speechtransmission index, second edition, 1998 2011 .

I.1.2.6 IEEE Standards Association Publications.

Institute of Electrical and Electronics Engineers, 3 Park Avenue, New York, NY 10016-5997

IEEE Std TM 450, Recommended Practice for Maintenance, Testing, and Replacement of VentedLead-Acid Batteries for Stationary Applications, 2010.

IEEE Std TM 485, Recommended Practice for Sizing Lead-Acid Batteries for Stationary Applications,2010.

IEEE Std TM 1106, Recommended Practice for Installation, Maintenance, Testing, and Replacement ofVented Nickel-Cadmium Batteries for Stationary Applications, 2005.

IEEE Std TM 1188, Recommended Practice for Maintenance, Testing, and Replacement of Valve-Regulated Lead-Acid (VRLA) Batteries for Stationary Applications, 2005.

I.1.2.7 IES Publications.

Illuminating Engineering Society of North America, 120 Wall Street, 17th floor, New York, NY 10005.

Lighting Handbook Reference and Application, 2008.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

487 of 496 10/20/2016 11:03 AM

Page 488: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

I.1.2.8 ISO Publications.

Standards Secretariat, Acoustical Society of America, 335 East 45th Street, New York, NY 10017-3483.

ISO/TR 4870, Acoustics — The Construction and Calibration of Speech Intelligibility Tests, 1991.

ISO 7240-19, Fire Detection and Alarm Systems — Part 19: Design, Installation, Commissioning, andService of Sound Systems for Emergency Purposes, 2007.

ISO 8201, Audible Emergency Evacuation Signal, 1990, revised 2008 2015 .

I.1.2.9 NEMA Publications.

National Electrical Manufacturers Association, 1300 North 17th Street, Suite 1752, Rosslyn, VA 22209.

NEMA SB-40, Communications Systems for Life Safety in Schools, 2008 2015 .

NEMA SB-50, Emergency Communications Audio Intelligibility Applications Guide, 2008 2014 .

I.1.2.10 NIST Publications.

National Institute of Standards and Technology, 100 Bureau Drive, Gaithersburg, MD 20899-1070.

NIST 6055, Electromagnetic Signal Attenuation in Construction Materials, 1997.

NIST Technical Note 1455–1, Performance of Home Smoke Alarms, Analysis of the Response of SeveralAvailable Technologies in Residential Fire Settings, February 2008.

NIST Technical Note 1779, General Guidance on Emergency Communications Strategies for Buildings,February 2013.

I.1.2.11 OASIS Publications.

Organization for the Advancement of Structured Information Standards (OASIS), 25 Corporate Drive,Suite 103, Burlington, MA 01803.

OASIS Standard CAP-V1.2, OASIS Common Alerting Protocol, Version 1.2.

I.1.2.12 SFPE Publications.

Society of Fire Protection Engineers, 7315 Wisconsin Avenue, #620E, Bethesda, MD 20814.

Guide to Performance Based Design.

SFPE Engineering Guide: Evaluation of the Computer Fire Model DETACT QS, 2002.

SFPE Engineering Guide to Human Behavior in Fire, 2003.

SFPE Engineering Guide to Performance Based Fire Protection Analysis and Design of Buildings ,2000 2007 .

SFPE Handbook of Fire Protection Engineering, 3rd Edition 5th Edition , 2002 2016 .

Keating, John P. and Loftus, Elizabeth F., “People Care in Fire Emergencies — Psychological Aspects,1975,” SFPE, 1975.

I.1.2.13 U.S. Government Publications.

U.S. Government Printing Office, Washington, DC 20402.

ADA-ABA-AG, Americans with Disabilities Act and Architectural Barriers Act AccessibilityGuidelines,2004 2010 .

Title 29, Code of Federal Regulations, Part 1910.5.

Title 47, Code of Federal Regulations, Part 15.

I.1.2.14 References Associated with Annex A.

I.1.2.14.1 Reference to A.18.4.7.2.

http://www.aip.org/pt/nov99/locsound.html.

I.1.2.14.2 References to A.24.3.1.

Kuligowski, Erica D., NIST Technical Note 1779: “General Guidance on Emergency CommunicationStrategies for Buildings,” Feb. 2013.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

488 of 496 10/20/2016 11:03 AM

Page 489: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

I.1.2.14.2 References to A.24.3.11.

(1) CARVER — Target Analysis and Vulnerability Assessment Methodology, Washington, DC: U.S.Department of Defense (see Field Manual 34-36, Special Operation Forces Intelligence and ElectronicsWarfare Operation, Sept. 30, 1991), www.defense.gov

(2) General Security Risk Assessment Guidelines. Alexandria, VA: American Society for Industrial SecurityInternational, www.asisonline.org

(3) NFPA 1600, Standard on Disaster/Emergency Management and Business Continuity Programs,Quincy, MA: National Fire Protection Association, www.nfpa.org

(4) NFPA 730, Guide for Premises Security, Quincy, MA: National Fire Protection Association,www.nfpa.org

(5) Responsible Care Code, Washington, DC: American Chemistry Council, www.americanchemistry.com

(6) Risk and Resilience Management of Water & Wastewater Systems, Denver, CO: American WaterWorks Association, www.awwa.org

(7) VAMCAP® Vulnerability Assessment Methodology for Critical Asset Protection, Wilmington, DE:SafePlace Corporation, www.safeplace.com

(8) Vulnerability Assessment Methodologies, Albuquerque, NM: Sandia National Laboratories,www.sandia.gov

I.1.2.14.3 References to A.24.4.8.

(1) Schifiliti, R.P., “To Leave or Not to Leave — That is the Question!”, National Fire ProtectionAssociation, World Fire Safety Congress & Exposition, May 16, 2000, Denver, CO.

(2) Ramachandran, G., “Informative Fire Warning Systems,” Fire Technology, Volume 47, Number 1,February 1991, National Fire Protection Association, 66–81.

(3) J. Bryan, “Psychological Variables That May Affect Fire Alarm Design,” Fire Protection Engineering,Society of Fire Protection Engineers, Issue No. 11, Fall 2001.

(4) Proulx, G., “Cool Under Fire,” Fire Protection Engineering, Society of Fire Protection Engineers, IssueNo. 16, Fall 2002.

(5) General Services Administration, Proceedings of the Reconvened International Conference on FireSafety in High Rise Buildings, Washington, D.C., October 1971.

(6) Proulx, G., “Strategies for Ensuring Appropriate Occupant Response to Fire Alarm Signals,” NationalResearch Council of Canada, Ottawa, Ontario, Construction Technology Update, No. 43, 1–6, December2000.

I.1.2.14.4 References to A.29.2.

(1) “A Few Fire Facts at the Household Level,” NFPA Fire Analysis Division, Fire Journal, May 1986.

(2) “Fire Loss in the United States during 2007,” Michael J. Karter, NFPA Fire Analysis and ResearchDivision.

(3) “Home Structure Fires,” Marty Ahrens, NFPA Fire Analysis and Research Division, February 2007.

I.1.2.14.5 References to A.29.3.7.

CSE NIH report, 2005; Bruck and Thomas, 2009; Bruck, Thomas, and Ball, NFPA RF report, 2007.

I.1.2.14.6 References to A.29.5.1.

(1) NBS GCR 75-51, Detector Sensitivity and Siting Requirements for Dwellings, 1975.

(2) NBS GCR 77-82, Detector Sensitivity and Siting Requirements for Dwellings Phase 2, 1977.

(3) NIST Technical Note 1455-1, Performance of Home Smoke Detectors Analysis of the Response ofSeveral Available Technologies in a Residential Setting, 2007.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

489 of 496 10/20/2016 11:03 AM

Page 490: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

I.1.2.14.7 References to A.29.5.2.1.1

(1) Green, M. A., and Andres, C. “2004-2005 National Sample Survey of Unreported Residential Fires.”CPSC, 2009.

(2) Ahrens, M. “Factors in Smoke Alarm Performance.” National Fire Protection Association. December2009.

(3) Thomas, I., and Bruck, D. “Smoke Alarms in Dwellings: Timely Activation and Effective Notification.”Victoria University. June 2010.

(4) Fabian, T. “…” Report in preparation.

I.1.2.15 Other Publications - Related to Carbon Monoxide Provisions

Ashley, E., DuBois, J., “Waking Effectiveness of Audible, Visual, and Vibratory Emergency AlarmsAcross All Hearing Levels,” Fire Suppression and Detection Research Symposium, Orlando, FL 2005.

Coburn, R. F., Forster, R. E., and Kane, P. G., “Considerations for the physiological variables thatdetermine the blood carboxyhemoglobin concentration in man,” Journal of Clinical Investigation, 1965,November; 44(11):1899–1910.

CSE NIH report, 2005: Bruck and Thomas, 2009; Bruck, Thomas, and Ball, NFPA RF report, 2007.

Fire Protection Research Foundation (FPRF) Report, Development of Technical Basis for CarbonMonoxide Detector Siting , prepared by C. Beyler and D. Gottuk, 2007.

Report of research on emergency signaling devices for use by the hearing impaired (Subject 1971),Underwriters Laboratories, 1991.

Steinberg, S., and Nielson, G. D., “A proposal for evaluating human exposure to carbon monoxidecontamination in military vehicles,” AMCMS Code 672716.H700011, March 1977.

Stone, W. Electromagnetic Attenuation in Construction Materials , National Institute of Standards andTechnology, NISTIR 6055, 1997.

Title 47, Code of Federal Regulations, Part 15.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

490 of 496 10/20/2016 11:03 AM

Page 491: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

I.1.2.16 References Associated with Annex B.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

491 of 496 10/20/2016 11:03 AM

Page 492: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

(1) Alpert, R. “Ceiling Jets,” Fire Technology, Aug. 1972.

(2) “Evaluating Unsprinklered Fire Hazards,” SFPE Technology Report 83-2.

(3) Babrauskas, V., Lawson, J. R., Walton, W. D., and Twilley, W. H. “Upholstered Furniture Heat ReleaseRates Measured with a Furniture Calorimeter,” (NBSIR 82-2604) (Dec. 1982). National Institute ofStandards and Technology (formerly National Bureau of Standards), Center for Fire Research,Gaithersburg, MD 20889.

(4) Beyler, C. “A Design Method for Flaming Fire Detection,” Fire Technology, Vol. 20, No. 4, Nov. 1984.

(5) DiNenno, P., ed. Chapter 31, SFPE Handbook of Fire Protection Engineering, by R. Schifiliti, Sept.1988.

(6) Evans, D. D. and Stroup, D. W. “Methods to Calculate Response Time of Heat and Smoke DetectorsInstalled Below Large Unobstructed Ceilings,” (NBSIR 85-3167) (Feb. 1985, issued Jul. 1986). NationalInstitute of Standards and Technology (formerly National Bureau of Standards), Center for Fire Research,Gaithersburg, MD 20889.

(7) Heskestad, G. “Characterization of Smoke Entry and Response for Products-of-Combustion Detectors”Proceedings, 7th International Conference on Problems of Automatic Fire Detection, Rheinish-Westfalischen Technischen Hochschule Aachen (Mar. 1975).

(8) Heskestad, G. “Investigation of a New Sprinkler Sensitivity Approval Test: The Plunge Test,” FMRCTech. Report 22485, Factory Mutual Research Corporation, 1151 Providence Turnpike, Norwood, MA02062.

(9) Heskestad, G. and Delichatsios, M. A. “The Initial Convective Flow in Fire: Seventeenth Symposiumon Combustion,” The Combustion Institute, Pittsburgh, PA (1979).

(10) Heskestad, G. and Delichatsios, M. A. “Environments of Fire Detectors — Phase 1: Effect of FireSize, Ceiling Height and Material,” Measurements Vol. I (NBS-GCR-77-86), Analysis Vol. II (NBS-GCR-77-95). National Technical Information Service (NTIS), Springfield, VA 22151.

(11) Heskestad, G. and Delichatsios, M. A. “Update: The Initial Convective Flow in Fire,” Fire SafetyJournal, Vol. 15, No. 5, 1989.

(12) International Organization for Standardization, Audible Emergency Evacuation Signal, ISO 8201,1987.

(13) Klote, J. and Milke, J. “Principles of Smoke Management,” American Society of Heating, Refrigeratingand Air Conditioning Engineers, Atlanta, GA, 2002.

(14) Lawson, J. R., Walton, W. D., and Twilley, W. H. “Fire Performance of Furnishings as Measured in theNBS Furniture Calorimeter, Part 1,” (NBSIR 83-2787) (Aug. 1983). National Institute of Standards andTechnology (formerly National Bureau of Standards), Center for Fire Research, Gaithersburg, MD 20889.

(15) Morton, B. R., Taylor, Sir Geoffrey, and Turner, J. S. “Turbulent Gravitational Convection fromMaintained and Instantaneous Sources,” Proc. Royal Society A, 234, 1–23, 1956.

(16) Schifiliti, R. “Use of Fire Plume Theory in the Design and Analysis of Fire Detector and SprinklerResponse,” Master’s Thesis, Worcester Polytechnic Institute, Center for Firesafety Studies, Worcester,MA, 1986.

(17) Title 47, Code of Federal Regulations, Communications Act of 1934 Amended.

(18) Schifiliti, R. and Pucci, W. “Fire Detection Modelling, State of the Art,” 6 May, 1996 sponsored by theFire Detection Institute, Bloomfield, CT.

(19) Forney, G., Bukowski, R., Davis, W. “Field Modelling: Effects of Flat Beamed Ceilings on Detectorand Sprinkler Response,” Technical Report, Year 1. International Fire Detection Research Project,National Fire Protection Research Foundation, Quincy, MA. October, 1993.

(20) Davis, W., Forney, G., Bukowski, R. “Field Modelling: Simulating the Effect of Sloped BeamedCeilings on Detector and Sprinkler Response,” Year 1. International Fire Detection Research ProjectTechnical Report, National Fire Protection Research Foundation, Quincy, MA. October, 1994.

(21) Brozovski, E. “A Preliminary Approach to Siting Smoke Detectors Based on Design Fire Size andDetector Aerosol Entry Lag Time,” Master’s Thesis, Worcester Polytechnic, Worcester, MA, 1989.

(22) Cote, A. NFPA Fire Protection Handbook, 20th edition, National Fire Protection Association, Quincy,MA, 2008.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

492 of 496 10/20/2016 11:03 AM

Page 493: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

(23) Tewarson, A., “Generation of Heat and Chemical Compounds in Fires,” SFPE Handbook of FireProtection Engineering, Second Edition, NFPA and SFPE, 1995.

(24) Hollman, J. P. Heat Transfer, McGraw-Hill, New York, 1976.

(25) Custer, R. L. P., and Meacham, B. “Introduction to Performance Based Fire Safety,” SFPE, 1997.

(26) Schifiliti, R. P., Meacham B., Custer, R. L. P. “Design of Detection Systems,” SFPE Handbook of FireProtection Engineering.

(27) Marrion, C. “Correction Factors for the Heat of Combustion in NFPA 72,” Appendix B, Fire ProtectionEngineering, SFPE, 1998.

(28) Marrion, C. “Designing and Analyzing the Response of Detection Systems: An Update to PreviousCorrelations,” 1988.

(29) Custer, R. and Bright, R. “Fire Detection: The State-of-the-Art,” NBS Tech. Note 839, National Bureauof Standards, Washington, 1974.

(30) Meacham, Brian J. “Characterization of Smoke from Burning Materials for the Evaluation of LightScattering-Type Smoke Detector Response,” MS Thesis, WPI Center for Firesafety Studies, Worcester,MA, 1991.

(31) Delichatsios, M. A. “Categorization of Cable Flammability, Detection of Smoldering, and FlamingCable Fires,” Interim Report, Factory Mutual Research Corporation, Norwood, MA, NP-1630, Nov. 1980.

(32) Heskestad, G. FMRC Serial Number 21017, Factory Mutual Research Corp., Norwood, MA, 1974.

(33) Marrion, C. E. “Lag Time Modeling and Effects of Ceiling Jet Velocity on the Placement of OpticalSmoke Detectors,” MS Thesis, WPI Center for Firesafety Studies, Worcester, MA, 1989.

(34) Kokkala, M. et al. “Measurements of the Characteristic Lengths of Smoke Detectors,” FireTechnology, Vol. 28, No. 2, National Fire Protection Association, Quincy, MA, 1992.

(34a) Yamauchi et al. “A Calculation Method for Predicting Heat and Smoke Detector’s Response.”

(34b) Cleary et al. “Particulate Entry Lag in Spot Type Smoke Detectors,” IAFSS Proceedings, Boston, MA2000.

(34c) Keski-Rahkonen, “Revisiting Modeling of Fluid Penetration into Smoke Detectors,” AUBE 2001.

(34d) Bjoerkman et al. “Determination of Dynamic Model Parameters of Smoke Detectors,” Fire SafetyJournal, No 37, pp. 395–407, 2002.

(34e) Keski-Rahkonen, “A New Model for Time Lag of Smoke Detectors,” International CollaborativeProject to Evaluate Fire Models for Nuclear Power Plant Application, Gaithersburg, MD May 2002.

(35) UL 268, Standard for Smoke Detectors for Fire Alarm Systems, Underwriters Laboratories, Inc.,Northbrook, IL, 2009.

(36) Deal, Scott.“Technical Reference Guide for FPEtool Version 3.2,” NISTIR 5486, National Institute forStandards and Technology, U.S. Department of Commerce, Gaithersburg, MD, Aug. 1994.

(37) Mowrer, F. W. “Lag Times Associated with Detection and Suppression,” Fire Technology, Vol. 26,No. 3, pp. 244–265, 1990.

(38) Newman, J. S. “Principles for Fire Detection,” Fire Technology, Vol. 24, No. 2, pp. 116–127, 1988.

(39) Custer, R., Meacham, B., Wood, C. “Performance Based Design Techniques for Detection andSpecial Suppression Applications,” Proceedings of the SFPE Engineering Seminars on Advances inDetection and Suppression Technology, 1994.

(40) SFPE Engineering Guide to Performance Based Fire Protection Analysis and Design of Buildings,2007, SFPE, Bethesda, MD.

(41) SFPE Handbook of Fire Protection Engineering, Fourth Edition, SFPE, Bethesda, MD, 2008.

(42) Drysdale, Dougal, An Introduction to Fire Dynamics, John Wiley & Sons, New York, NY, 1998, ISBN 0471 90613 1, Second Edition.

(43) Nam S., Donovan L.P. and Kim S.G., Establishing Heat Detectors Thermal Sensitivity Through BenchScale Tests, Fire Safety Journal, Volume 39, Number 3, 191–215, April 2004.

(44) Nam S., Thermal Response Coefficient TRC of Heat Detectors and Its Field Applications, FireDetection and Research Applications Symposium, NFP Research Foundation, January 2003.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

493 of 496 10/20/2016 11:03 AM

Page 494: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

(45) Nam S., Performance-Based Heat Detector Spacing, Interflam 2004, pp 883–892.

(46) Geiman, J. A., “Evaluation of Smoke Detector Response Estimation Methods,” Master of ScienceThesis, University of Maryland, College Park, MD, December 2003.

(47) Projected Beam Smoke Detectors — More Than Just a Substitute for Spot Detectors; Fire ProtectionEngineering, Summer 2004, SFPE.

(48) Geiman, J.A., and Gottuck, D.T., “Alarm Thresholds for Smoke Detector Modeling,” Fire SafetyScience — Proceeding of the Seventh International Symposium, 2003, pp. 197–208.

(49) The SFPE Code Official's Guide to Performance-based Design Review and Analysis of Buildings,Society of Fire Protection Engineers, Bethesda, MD, 2004.

(50) NFPA 101, Life Safety Code, National Fire Protection Association, Quincy, MA, 2009.

(51) NFPA 909, Code for the Protection of Cultural Resource Properties — Museums, Libraries, andPlaces of Worship, National Fire Protection Association, Quincy, MA, 2010.

(52) NFPA 914, Code for Fire Protection of Historic Structures, National Fire Protection Association,Quincy, MA, 2010.

(53) Performance-based Building Design Concepts, International Code Council, Washington DC, 2004.

(54) Extreme Event Mitigation In Buildings—Analysis and Design, Meacham, National Fire ProtectionAssociation, Quincy, MA, 2006.

(55) Geiman, Gottuk, and Milke, “Evaluation of Smoke Detector Response Estimation Methods: OpticalDensity, Temperature Rise and Velocity at Alarm,” Journal of Fire Protection Engineering, 2006.

(56) Su et al., “Kemano Fire Studies—Part 1: Response of Residential Smoke Alarms,” Research Report108, NRCC, April 2003.

(57) Davis, W., The Zone Model Jet, “A Model for the Prediction of Detector Activation and GasTemperature in the Presence of a Smoke Layer,” NISTIR 6324, NIST, May 1999.

(58) SFPE Engineering Guide to Human Behavior in Fire.

I.1.2.17 References Associated with Annex D.

(1) Jacob, K. & Tyson, T., “Computer-Based Prediction of Speech Intelligibility for Mass NotificationSystems,” SUPDET 2008, Fire Protection Research Foundation, Mar 2008.

(2) IEC 60268-16, “Sound system equipment — Part 16: Objective rating of speech intelligibility by speechtransmission index,” 2003.

(3) ANSI/ASA S3.5, “American National Standard Methods for Calculation of the Speech IntelligibilityIndex,” 1997.

(4) Barnett, P.W. and Knight, A.D., “The Common Intelligibility Scale,” Proceedings of the Institute ofAcoustics, Vol. 17, Part 7, 1995.

(5) IEC 60849, Annex B, Sound Systems for Emergency Purposes, Feb 1998.

(6) Sander J. van Wijngaarden and Jan A. Verhave, Past Present and Future of the Speech TransmissionIndex, Chapter 9, Measurement and Prediction of Speech Intelligibility in Traffic Tunnels Using the STI,p113, TNO Human Factors, The Netherlands, 2002.

(7) Mapp, P., “Systematic & Common Errors in Sound System STI and Intelligibility Measurements,”Convention Paper 6271, Audio Engineering Society, 117th Convention, San Fran, CA, 28–31 Oct 2004.

(8) Peter Mapp, Past Present and Future of the Speech Transmission Index, Chapter 8, PracticalApplication of STI to Assessing Public Address and Emergency Sound Systems, TNO Human Factors,The Netherlands, 2002.

I.1.2.18 References Associated with Annex G.

G.1 Kuligowski, Erica D., NIST Technical Note 1779: “General Guidance on Emergency CommunicationStrategies for Buildings,” Feb. 2013.

I.2 Informational References.

The following documents or portions thereof are listed here as informational resources only. They are nota part of the requirements of this document.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

494 of 496 10/20/2016 11:03 AM

Page 495: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

Detail FR-5052

I.2.1 ASTM Publications.

ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959.

ASTM E2292, Standard Guide for Field Investigation of Carbon Monoxide Poisoning Incidents , 2014.

I.2.2 EPRI Publications.

Electric Power Research Institute, 3420 Hillview Avenue, Palo Alto, CA 94304

Technical Report 1002925, Stationary Battery Monitoring by Internal Ohmic Measurement , 2002

Technical Report TR-10067577, Stationary Battery Guide; Design, Application, and Maintenance, 2002

I.2.3 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 1192, Standard on Recreational Vehicles , 2018 edition.

I.2.4 UL Publications.

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

ANSI/ASA S3.41, American National Standard Audible Emergency Evacuation Signal , 2016.

ANSI/UL 268, Standard for Smoke Detectors for Fire Alarm Systems , 6th edition, 2009.

ANSI/UL 864, Standard for Control Units and Accessories for Fire Alarm Systems, 9th edition, 2014.

ANSI/UL 1638, Standard for Visual Signaling Appliances — Private Mode Emergency and General UtilitySignaling , 5th edition, 2016.

ANSI/UL 1971, Standard for Signaling Devices for the Hearing Impaired, 3rd edition, 2002, revised2013.

ANSI/UL 2034, Standard for Single and Multiple Station Carbon Monoxide Alarms, 2008, Revised 2009.

ANSI/UL 2074, Gas and Vapor Detectors and Sensors, 2004.

I.3 References for Extracts in Informational Sections.

NFPA 70®, National Electrical Code®, 2014 2017 edition.

NFPA 92, Standard for Smoke Control Systems, 2012 2018 edition.

NFPA 92B, Smoke Management Systems in Malls, Atria, and Large Spaces, 1995 edition.

NFPA 101®, Life Safety Code®, 2015 2018 edition.

NFPA 1221, Standard for the Installation, Maintenance, and Use of Emergency Services CommunicationsSystems, 2013 2016 edition.

Submitter Information Verification

Submitter Full Name: SIG-NAS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 10:24:43 EDT 2016

Committee Statement

CommitteeStatement:

This first revision is being made to update the reference standards in Annex H.

This is designated to SIG-NAS but SIG-TMS felt it was necessary to act on this as well. SIG-TMS

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

495 of 496 10/20/2016 11:03 AM

Page 496: First Revision No. 2501-NFPA 72-2016 [ Global Input ]€¦ · First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value

agrees with these changes and would like to make a First Revision exactly as submitted. SIG-TMSadds these publications in accordance with the recommendations of the Battery Testing TaskGroup.

Public Input No. 625-NFPA 72-2016 [New Section after H.1.2.15]

Public Input No. 613-NFPA 72-2016 [Section No. H.1.1]

Public Input No. 623-NFPA 72-2016 [Section No. H.1.2.13.2]

Public Input No. 153-NFPA 72-2016 [New Section after H.1.2.5]

Public Input No. 537-NFPA 72-2016 [Section No. H.2.1]

Public Input No. 535-NFPA 72-2016 [Section No. H.1.2.1]

Public Input No. 154-NFPA 72-2016 [New Section after H.2]

Public Input No. 3-NFPA 72-2015 [Chapter H]

Public Input No. 614-NFPA 72-2016 [New Section after H.1.2.11]

Public Input No. 615-NFPA 72-2016 [New Section after H.1.2.12]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

496 of 496 10/20/2016 11:03 AM