70
First Revision No. 8241-NFPA 70-2018 [ Global Input ] Revise the title of Article 406: Receptacles, Cord Connectors, and Attachment Plugs (Caps) , and Attachment Fittings Submitter Information Verification Submitter Full Name: NEC-CMP Panel 18 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Jan 15 15:51:39 EST 2018 Committee Statement and Meeting Notes Committee Statement: Title of Article 406 has been updated to reflect the term “attachment fitting” which is already identified. See Article 422.33 for correlation purposes. Response Message: Public Input No. 2012-NFPA 70-2017 [Global Input] Public Input No. 3973-NFPA 70-2017 [Global Input] Public Input No. 3951-NFPA 70-2017 [Global Input] National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/... 1 of 1 3/7/2018 12:52 PM

First Revision No. 8241-NFPA 70-2018 [ Global Input ]

  • Upload
    others

  • View
    11

  • Download
    0

Embed Size (px)

Citation preview

Page 1: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8241-NFPA 70-2018 [ Global Input ]

Revise the title of Article 406:

Receptacles, Cord Connectors, and Attachment Plugs (Caps), and Attachment Fittings

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 15:51:39 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

Title of Article 406 has been updated to reflect the term “attachment fitting” which isalready identified. See Article 422.33 for correlation purposes.

ResponseMessage:

Public Input No. 2012-NFPA 70-2017 [Global Input]

Public Input No. 3973-NFPA 70-2017 [Global Input]

Public Input No. 3951-NFPA 70-2017 [Global Input]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 12:52 PM

Page 2: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8133-NFPA 70-2018 [ Detail ]

393.2 Definitions. The definitions in this section shall apply only within this article.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 08:30:59 EST 2018

Committee Statement and Meeting Notes

Committee Statement: The additional statement adds clarity and complies with the NEC Style Manual.

Response Message:

Public Input No. 1211-NFPA 70-2017 [Section No. 393.2]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 12:55 PM

Page 3: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8140-NFPA 70-2018 [ Detail ]

605.2 Definitions.

The definition in this section shall apply within this article and throughout the Code.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 09:17:15 EST 2018

Committee Statement and Meeting Notes

Committee Statement: The additional statement adds clarity and complies with the NEC Style Manual.

Response Message:

Public Input No. 2231-NFPA 70-2017 [Section No. 605.2]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 12:56 PM

Page 4: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8141-NFPA 70-2018 [ Detail ]

600.2 Definitions. The definitions in this section shall apply only within this article.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 09:29:29 EST 2018

Committee Statement and Meeting Notes

Committee Statement: The additional statement adds clarity and complies with the NEC Style Manual.

Response Message:

Public Input No. 1911-NFPA 70-2017 [Section No. 600.2]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 12:56 PM

Page 5: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8254-NFPA 70-2018 [ Detail ]

406.2 Definitions.

The definitions in this section shall apply only within this article.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 16:23:43 EST 2018

Committee Statement and Meeting Notes

Committee Statement: Provides clarity. Meets the requirements of the style manual.

Response Message:

Public Input No. 1213-NFPA 70-2017 [Section No. 406.2]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 12:58 PM

Page 6: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8388-NFPA 70-2018 [ Detail ]

410.2 Definition. The definitions in this section shall apply only within this article.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 16 14:42:29 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

410.2 was edited to clarify that the definitions are only applicable within Article410.

Response Message:

Public Input No. 1214-NFPA 70-2017 [Section No. 410.2]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:05 PM

Page 7: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8246-NFPA 70-2018 [ Definition: Receptacle. ]

Receptacle.

A contact device installed at the outlet for the connection of an attachment plug, or for the directconnection of electrical utilization equipment designed to mate with the corresponding contactdevice. A single receptacle is a single contact device with no other contact device on the sameyoke. A multiple receptacle is two or more contact devices on the same yoke. (CMP-18)

Informational Note: A duplex receptacle is an example of a multiple receptacle that has tworeceptacles on the same yoke.

Supplemental Information

File Name Description Approved

70_FR8246_100_Receptacle.docx For staff use ✓

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 16:00:14 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

It has been reported that there is confusion and debate among electricians and inspectorsas to whether a typical duplex receptacle is actually 2 receptacles or just 1 receptacle. Theinformational note explains that a duplex receptacle is two receptacles on the same yoke.

ResponseMessage:

Public Input No. 1435-NFPA 70-2017 [Definition: Receptacle.]

Public Input No. 1436-NFPA 70-2017 [Definition: Receptacle.]

Public Input No. 1483-NFPA 70-2017 [Definition: Receptacle.]

Public Input No. 1481-NFPA 70-2017 [Definition: Receptacle.]

Public Input No. 1482-NFPA 70-2017 [New Definition after Definition: Receptacle.]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:05 PM

Page 8: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8134-NFPA 70-2018 [ Section No. 393.10 ]

393.10 Uses Permitted.

Low-voltage suspended ceiling power distribution systems shall be permanently connected andshall be permitted as follows:

(1) For listed utilization equipment capable of operation at a maximum of 30 volts ac (42.4 voltspeak) or 60 volts dc (24.8 volts peak for dc interrupted at a rate of 10 Hz to 200 Hz) andlimited to Class 2 power levels in Chapter 9, Table 11(A) and Table 11(B) for lighting, control,and signaling circuits.

(2) In indoor dry locations.

(3) For residential, commercial, and industrial installations.

(4) In other spaces used for environmental air in accordance with 300.22(C), electrical equipmenthaving a metal enclosure, or with a nonmetallic enclosure and fittings, shall be listed for usewithin an air-handling space and shall have adequate fire-resistant and low-smoke-producingcharacteristics and associated wiring material suitable for the ambient temperature.

Informational Note: One method of defining adequate fire-resistant and low-smoke-producing characteristics for electrical equipment with a nonmetallic enclosure is inANSI/ UL 2043-2008 2013 , Fire Test for Heat and Visible Smoke Release for DiscreteProducts and Their Accessories Installed in Air-Handling Spaces.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 08:41:35 EST 2018

Committee Statement and Meeting Notes

Committee Statement: The referenced standard was updated to the current edition.

Response Message:

Public Input No. 827-NFPA 70-2017 [Section No. 393.10]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:05 PM

Page 9: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8135-NFPA 70-2018 [ Section No. 393.14(A) ]

(A) General Requirements.

Support wiring shall be installed in a neat and workmanlike manner. Cables and conductorsinstalled exposed on the surface of ceilings and sidewalls shall be supported by the buildingstructure in such a manner that the cable is not damaged by normal building use. Such cablesshall be supported by straps, staples, hangers, cable ties listed and identified for securement andsupport , or similar fittings designed and installed so as not to damage the cable.

Informational Note: Suspended ceiling low-voltage power grid distribution systems shouldbe installed by qualified persons in accordance with the manufacturer’s installationinstructions.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 08:43:00 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The listing requirement was added to comply with installations in other spaces inaccordance with 300.22(C) and to assure proper securement.

ResponseMessage:

Public Input No. 4357-NFPA 70-2017 [Section No. 393.14(A)]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:06 PM

Page 10: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8136-NFPA 70-2018 [ Section No. 393.40(A) ]

(A) Connectors.

Connections to busbar grid rails, cables, and conductors shall be made with listed insulatingdevices, and these connections shall be accessible after installation. A soldered connection shallbe made mechanically secure before being soldered. Other means of securing leads, such aspush-on terminals and spade-type connectors, shall provide a secure mechanical connection. Thefollowing connectors shall be permitted to be used as connection or interconnection devices:

(1) Load connectors shall be used for power from the busbar to listed utilization equipment.

(2) A pendant connector shall be permitted to suspend low-voltage luminaires or utilizationequipment below the grid rail and to supply power from the busbar to the utilizationequipment.

(3) A power feed connector shall be permitted to connect the power supply directly to a powerdistribution cable and to the busbar.

(4) Rail-to-rail connectors shall be permitted to interconnect busbars from one ceiling grid rail toanother grid rail.

Informational Note: For quick-connect terminals, see UL 310, Standard for Electrical Quick-Connect, and for mechanical splicing devices, see UL 486A-486B , Standard for WireConnectors and Soldering Lugs for Use with Copper Conductors , and 486B, Standard forWire Connector s .

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 08:46:40 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The referenced standards UL486A and UL486B have been combined intoUL486A-486B.

Response Message:

Public Input No. 2920-NFPA 70-2017 [Section No. 393.40(A)]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:06 PM

Page 11: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8250-NFPA 70-2018 [ Section No. 406.1 ]

406.1 Scope.

This article covers the rating, type, and installation of receptacles, cord connectors, andattachment plugs (cord caps), and attachment fittings .

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 16:15:59 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The requirements in the article also apply to attachment fittings. The attachment fitting isanalogous to the cord connector and the attachment plug (cap). Requirements forattachment fittings were added in the 2017 NEC, § 314.27(E), 422.118, and 422.33.

"Cord" was deleted to be consistent with the article title.

ResponseMessage:

Public Input No. 2014-NFPA 70-2017 [Section No. 406.1]

Public Input No. 3955-NFPA 70-2017 [Section No. 406.1]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:07 PM

Page 12: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8257-NFPA 70-2018 [ Section No. 406.3(D) ]

(D) Isolated Ground Receptacles.

Receptacles incorporating an isolated equipment grounding conductor connection intended for thereduction of electrical noise ( electromagnetic interference) as permitted in 250.146(D) shall beidentified by an orange triangle located on the face of the receptacle.

(1) Isolated Equipment Grounding Conductor Required.

Receptacles so identified shall be used only with equipment grounding conductors that areisolated in accordance with 250.146(D).

(2) Installation in Nonmetallic Boxes.

Isolated ground receptacles installed in nonmetallic boxes shall be covered with a nonmetallicfaceplate.

Exception: Where an isolated ground receptacle is installed in a nonmetallic box, a metalfaceplate shall be permitted if the box contains a feature or accessory that permits the effectivegrounding connection of the faceplate to the equipment grounding conductor .

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 16:32:06 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The word "equipment" is added to be consistent with current terminology.

The term "electrical noise" is removed because "electromagnetic interference" betterdescribes the condition.

The revised exception in (2) removes the ambiguity of “effective grounding.”

ResponseMessage:

Public Input No. 1512-NFPA 70-2017 [Section No. 406.3(D) [Excluding any Sub-Sections]]

Public Input No. 2397-NFPA 70-2017 [Section No. 406.3(D)]

Public Input No. 1714-NFPA 70-2017 [Section No. 406.3(D)(2)]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:07 PM

Page 13: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8297-NFPA 70-2018 [ Section No. 406.4(C) ]

(C) Methods of Grounding.

The equipment grounding conductor contacts of receptacles and cord connectors shall begrounded by connection connected to the equipment grounding conductor of the circuit supplyingthe receptacle or cord connector.

Informational Note: For installation requirements for the reduction of electricalnoise electromagnetic interference , see 250.146(D).

The branch-circuit wiring method shall include or provide an equipment grounding conductor towhich the equipment grounding conductor contacts of the receptacle or cord connector areconnected.

Informational Note No. 1: See 250.118 for acceptable grounding means.

Informational Note No. 2: For extensions of existing branch circuits, see 250.130.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 16 08:26:40 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The phrase "grounded by connection" is replaced with "connected" to use standardterminology.

Changed the term "electrical noise" to "electromagnetic interference," as it is a moreaccurate term.

Response Message:

Public Input No. 1513-NFPA 70-2017 [Section No. 406.4(C)]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:10 PM

Page 14: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8314-NFPA 70-2018 [ Section No. 406.4(D)(3) ]

(3) Ground-Fault Circuit-Interrupters Interrupter Protection .

Ground-fault circuit-interrupter protected receptacles shall be provided where replacements aremade at receptacle outlets that are required to be so protected elsewhere in this Code.

Exception: Where replacement of the receptacle type is impracticable, such as where the outletbox size will not permit the installation of the GFCI receptacle, the receptacle shall be permittedto be replaced with a new receptacle of the existing type, where GFCI protection is provided andthe receptacle is marked “GFCI Protected” and “No Equipment Ground,” in accordance with406.4(D)(2)(a), (b) (D)(2)(b) , or (c) (D)(2)(c) , as applicable.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 16 09:16:45 EST 2018

Committee Statement and Meeting Notes

Committee Statement: The title is revised for clarity.

Response Message:

Public Input No. 1870-NFPA 70-2017 [Section No. 406.4(D)(3)]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:11 PM

Page 15: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8302-NFPA 70-2018 [ Section No. 406.4(D)(4) ]

(4) Arc-Fault Circuit-Interrupter Protection.

Where If a receptacle outlet is located in any areas specified in 210.12(A) or , (B), or (C) is replaced , areplacement receptacle at this outlet shall be one of the following:

(1) A listed outlet branch-circuit type arc-fault circuit-interrupter receptacle

(2) A receptacle protected by a listed outlet branch-circuit type arc-fault circuit-interrupter type receptacle

(3) A receptacle protected by a listed combination type arc-fault circuit-interrupter type circuit breaker

Exception No. 1: Arc-fault circuit-interrupter protection shall not be required where all of the following apply:

(0) The replacement complies with 406.4(D)(2) (b).

(0) It is impracticable to provide an equipment grounding conductor as provided by 250.130(C) .

(0) A listed combination type arc-fault circuit-interrupter circuit breaker is not commercially available.

(0) GFCI/AFCI dual function receptacles are not commercially available.

Exception: Section 210.12(D), Exception, shall not apply to replacement of receptacles.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 16 08:40:47 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

Exception No. 1 is deleted as it is no longer relevant. Product that complies with the mainrequirement is now available. Section 210.12(C) was added to address guest rooms and guest suites,which were added in the last edition.

The remainder of the revisions are editorial in nature and add clarity.

ResponseMessage:

Public Input No. 855-NFPA 70-2017 [Section No. 406.4(D)(4)]

Public Input No. 233-NFPA 70-2017 [Section No. 406.4(D)(4)]

Public Input No. 431-NFPA 70-2017 [Section No. 406.4(D)(4)]

Public Input No. 3354-NFPA 70-2017 [Section No. 406.4(D)(4)]

Public Input No. 469-NFPA 70-2017 [Section No. 406.4(D)(4)]

Public Input No. 2724-NFPA 70-2017 [Section No. 406.4(D)(4)]

Public Input No. 1606-NFPA 70-2017 [Section No. 406.4(D)(4)]

Public Input No. 232-NFPA 70-2017 [Section No. 406.4(D)(4)]

Public Input No. 887-NFPA 70-2017 [Section No. 406.4(D)(4)]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 2 3/7/2018 1:11 PM

Page 16: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

Public Input No. 1678-NFPA 70-2017 [Section No. 406.4(D)]

Public Input No. 184-NFPA 70-2017 [Section No. 406.4(D)(4)]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

2 of 2 3/7/2018 1:11 PM

Page 17: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8319-NFPA 70-2018 [ New Section after 406.4(D)(6) ]

(7) Controlled Receptacles.

Automatically controlled receptacles shall be replaced with equivalently controlled receptacles. Ifautomatic control is no longer required, the receptacle and any associated receptacles markedper 406.3(E) shall be replaced with a receptacle and faceplate not marked per 406.3(E) .

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 16 09:25:55 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The new text addresses the replacement of controlled receptacles. It addresses safetyconcerns related to the removal of the control feature.

ResponseMessage:

Committee Notes:

Date Submitted By

Jan 16,2018

NEC-CMPPanel 18

Please add an Editorial Comment to update the charging paragraph in 406.4(D), so that the cross-reference range includes this new section.

Public Input No. 229-NFPA 70-2017 [New Section after 406.4(D)(6)]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:12 PM

Page 18: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8336-NFPA 70-2018 [ Section No. 406.5(G) ]

(G) Receptacle Orientation.

(1) Countertop and Work Surfaces.

Receptacles shall not be installed in a face-up position in or on countertop surfaces or worksurfaces unless listed for countertop or work surface applications.

(2) Under Sinks.

Receptacles shall not be installed in a face-up position in the area below a sink.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 16 10:26:45 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

A receptacle outlet installed in the area beneath a sink should not be installed in aface-up position, which could allow water or other objects to enter the receptacle.

ResponseMessage:

Public Input No. 642-NFPA 70-2017 [Section No. 406.5(G)]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:12 PM

Page 19: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8350-NFPA 70-2018 [ Section No. 406.9(C) ]

(C) Bathtub and Shower Space.

Receptacles shall not be installed within a zone measured 900 mm (3 ft) horizontally and 2.5 m (8ft) vertically from the top of the bathtub rim or directly over a bathtub or shower stall shower stallthreshold .

Informational Note: The identified zone is all-encompassing and includes the space directlyover the tub or shower stall.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 16 11:19:55 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The revised language is taken from Section 410.10(D), which provides specific dimensionsfor electrical installations near bathtubs and shower stalls. NEC Section 552.41(F) requiresthat a receptacle “shall not be installed in or within reach [750 mm (30 in.)] of a shower orbathtub space.”

ResponseMessage:

Public Input No. 3693-NFPA 70-2017 [Section No. 406.9(C)]

Public Input No. 3725-NFPA 70-2017 [Section No. 406.9(C)]

Public Input No. 3625-NFPA 70-2017 [Section No. 406.9(C)]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:15 PM

Page 20: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8357-NFPA 70-2018 [ Section No. 406.10 ]

406.10 Grounding-Type Receptacles, Adapters, Cord Connectors, and Attachment Plugs.

(A) Grounding Poles (Connections) .

Grounding-type receptacles, cord connectors, and attachment plugs shall be provided with one fixedgrounding pole in addition to the circuit poles. The grounding contacting pole of grounding-type plug-inground-fault circuit interrupters shall be permitted to be of the movable, self-restoring type on circuits operatingat not over 150 volts between any two conductors or any conductor and ground.

(B) Grounding-Pole (Connection) Identification.

Grounding-type receptacles, adapters, cord connections, and attachment plugs shall have a means forconnection of an equipment grounding conductor to the grounding pole.

A terminal for connection to the grounding pole shall be designated by one of the following:

(1) A green-colored hexagonal-headed or -shaped terminal screw or nut, not readily removable.

(2) A green-colored pressure wire connector body (a wire barrel).

(3) A similar green-colored connection device, in the case of adapters. The grounding terminal of a groundingadapter shall be a green-colored rigid ear, lug, or similar device. The equipment grounding connectionshall be so designed that it cannot make contact with current-carrying parts of the receptacle, adapter, orattachment plug. The adapter shall be polarized.

(4) If the terminal for the equipment grounding conductor is not visible, the conductor entrance hole shall bemarked with the word green or ground, the letters G or GR, a grounding symbol, or otherwise identified bya distinctive green color. If the terminal for the equipment grounding conductor is readily removable, thearea adjacent to the terminal shall be similarly marked.

Informational Note: See Informational Note Figure 406.10(B)(4).

Figure Informational Note Figure 406.10(B)(4) One Example of a Symbol Used to Identify theTermination Point for an Equipment Grounding Conductor.

(C) Grounding Terminal Use.

A grounding terminal shall not be used for purposes other than connection to the equipment groundingconductor .

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 2 3/7/2018 1:15 PM

Page 21: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

(D) Grounding-Pole (Connection) Requirements.

Grounding-type attachment plugs and mating cord connectors and receptacles shall be designed such that theequipment grounding connection is made before the current-carrying connections. Grounding-type devicesshall be so designed that grounding poles of attachment plugs cannot be brought into contact with current-carrying parts of receptacles or cord connectors.

(E) Use.

Grounding-type attachment plugs shall be used only with a cord having an equipment grounding conductor.

Informational Note: See 250.126 for identification of equipment grounding conductor terminals.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 16 11:39:12 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The term pole or poles has been misunderstood by some readers of the Code. Adding theparenthetical (connection) to the titles of (A), (B), and (D) adds clarity.

The phrase "connection to the equipment grounding conductor" is more precise.

ResponseMessage:

Public Input No. 1717-NFPA 70-2017 [Section No. 406.10(C)]

Public Input No. 2130-NFPA 70-2017 [Section No. 406.10]

Public Input No. 2398-NFPA 70-2017 [Section No. 406.10(E)]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

2 of 2 3/7/2018 1:15 PM

Page 22: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8394-NFPA 70-2018 [ Section No. 410.10(D) ]

(D) Bathtub and Shower Areas.

A luminaire installed in a bathtub or shower area shall meet all of the following requirements:

(1)

No parts of cord-connected luminaires, chain-, cable-, or cord-suspended luminaires, lighting track,pendants, or ceiling-suspended (paddle) fans shall be located within a zone measured 900 mm(3 ft) horizontally and 2.5 m (8 ft) vertically from the top of the bathtub rim or shower stallthreshold. This zone is all-encompassing and includes the space directly over the tub or showerstall.

(2)

Luminaires located within the actual outside dimension of the bathtub or shower to a height of2.5 m (8 ft) vertically from the top of the bathtub rim or shower threshold shall be marked suitablefor damp locations or marked suitable for wet locations. Luminaires located where subject toshower spray shall be marked suitable for wet locations .

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 16 15:05:42 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The section was changed to a list format to improve usability. To match the format of othersubdivision lists in Article 410, an introductory statement was added. As defined in Article100, a damp location is protected from saturation with liquids, therefore it is not appropriateto allow a product marked as suitable for damp locations to be subject to a shower spray.The panel has clarified that the use of a wet location marked luminaire is allowed in locationswhere the luminaire is not subject to shower spray.

ResponseMessage:

Public Input No. 3141-NFPA 70-2017 [Section No. 410.10(D)]

Public Input No. 88-NFPA 70-2017 [Section No. 410.10(D)]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:15 PM

Page 23: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8406-NFPA 70-2018 [ Section No. 410.22 ]

410.22 Outlet Boxes to Be Covered.

In a completed installation, each outlet box shall be provided with a cover unless covered bymeans of a luminaire canopy, lampholder, receptacle that covers the box or is provided with afaceplate , or similar device.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 16 15:51:57 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

A faceplate is needed in conjunction with a receptacle to cover a box. However, somereceptacles are constructed in a way that provides a box cover without a faceplate.

ResponseMessage:

Public Input No. 4027-NFPA 70-2017 [Section No. 410.22]

Public Input No. 2075-NFPA 70-2017 [Section No. 410.22]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:16 PM

Page 24: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8418-NFPA 70-2018 [ Section No. 410.36(A) ]

(A) Luminaires Supported By Outlet Boxes.

Outlet Luminaires shall be permitted to be supported by outlet boxes or fittings installed asrequired by 314.23and complying with the . The installation shall comply with the followingrequirements:

(1) The outlet boxes or fittings shall comply with 314.27(A)(1) and 314.27(A)(2)

(2) Luminaires shall be permitted to support luminaires. be supported in accordance with314.27(E).

Supplemental Information

File Name Description Approved

Panel_18_FR-8418_410.36_A_leg_changes.docx For staff use ✓

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 16 16:13:52 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

This revision is being made to coordinate with section 314.27(E), which was added to the2017 NEC. The section was reorganized as a list to clarify that compliance with314.27(A)(1) and 314.27(A)(2) is always required.

ResponseMessage:

Public Input No. 2079-NFPA 70-2017 [Section No. 410.36(A)]

Public Input No. 4043-NFPA 70-2017 [Section No. 410.36(A)]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:16 PM

Page 25: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8426-NFPA 70-2018 [ Section No. 410.42 ]

410.42 Luminaire(s) with Exposed Conductive Parts.

Exposed metal parts conductive parts that are accessible to unqualified persons shall beconnected to an equipment grounding conductor or insulated from the equipment groundingconductor be separated from all live parts and other conducting surfaces or be inaccessible tounqualified personnel. Lamp tie wires, by a listed system of double insulation.

Exception No. 1: Small isolated parts, such as mounting screws, clips, and decorative bands onglass spaced at least 38 mm (11⁄2 in.) from lamp terminals shall not be required to be grounded .

Exception No. 2: Portable luminaires with a polarized attachment plug.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 16 16:31:37 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The panel has simplified the requirements for protection against electric shock injuryassociated with luminaires with accessible conductive surfaces and added an exceptionfor the polarized plug connection of portable luminaires permitted by 410.82.

ResponseMessage:

Public Input No. 2473-NFPA 70-2017 [Section No. 410.42]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:17 PM

Page 26: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8430-NFPA 70-2018 [ Section No. 410.44 ]

410.44 Methods of Grounding.

Luminaires and equipment shall be mechanically connected to an equipment grounding conductoras specified in 250.118 and sized in accordance with 250.122.

Exception No. 1: Luminaires made of insulating material that is directly wired or attached tooutlets supplied by a wiring method that does not provide a ready means for groundingattachment to an equipment grounding conductor shall be made of insulating material and shallhave no exposed conductive parts.

Exception No. 1: Replacement luminaires shall be permitted to connect an equipment groundingconductor from the outlet in the same manner as replacement receptacles in compliance with250.130(C). The luminaire shall then comply with 410.42.

Exception No. 2: Where no equipment grounding conductor exists at the outlet, replacementluminaires that are GFCI protected or do not have exposed conductive parts shall not berequired to be connected to an equipment grounding conductor.

Supplemental Information

File Name Description Approved

70_FR8430_410.44.docx For staff use ✓

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 16 16:49:18 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The panel has simplified the requirements for protection against electric shock injuryassociated with luminaires with accessible conductive surfaces. Exception #1 was deleted,since there is no requirement for a luminaire with no accessible conductive parts, or ‘madeof insulating material’, to be grounded. Hence, there is no need to exempt it from thegrounding requirement.

ResponseMessage:

Public Input No. 2475-NFPA 70-2017 [Section No. 410.44]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:17 PM

Page 27: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8433-NFPA 70-2018 [ Section No. 410.46 ]

410.46 Equipment Grounding Conductor Attachment.

Luminaires with exposed metal parts shall be provided with a means for connecting anequipment grounding conductor for such luminaires.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 16 17:00:25 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The panel has eliminated 410.46. This is a product (luminaire) requirement that isaddressed by the Listing requirement of 410.6.

ResponseMessage:

Public Input No. 2478-NFPA 70-2017 [Section No. 410.46]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:20 PM

Page 28: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8479-NFPA 70-2018 [ Section No. 410.52 ]

410.52 Conductor Insulation.

Luminaires shall be wired with conductors having insulation suitable for the environmentalconditions, current, voltage, and temperature to which the conductors will be subjected.

Informational Note: For ampacity of fixture wire, maximum operating temperature,voltage limitations, minimum wire size, and other information, see Article 402 .

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 17 07:36:30 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The content of 410.52 is fully addressed by the Listing requirement of 410.6; therefore,the panel is eliminating this section. This requirement is contained within the applicableproduct standards (e.g., UL 1598, UL 153, and others).

ResponseMessage:

Public Input No. 2588-NFPA 70-2017 [Section No. 410.52]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:21 PM

Page 29: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8480-NFPA 70-2018 [ Section No. 410.54 ]

410.54 Pendant Conductors for Incandescent Filament Lamps.

(A) Support.

Pendant lampholders with permanently attached leads, where used for other than festoonwiring, shall be hung from separate stranded rubber-covered conductors that are soldereddirectly to the circuit conductors but supported independently thereof.

(B) Size.

Unless part of listed decorative lighting assemblies, pendant conductors shall not be smallerthan 14 AWG for mogul-base or medium-base screw shell lampholders or smaller than 18 AWGfor intermediate or candelabra-base lampholders.

(C) Twisted or Cabled.

Pendant conductors longer than 900 mm (3 ft) shall be twisted together where not cabled in alisted assembly.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 17 07:38:51 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The content of 410.54 is fully addressed by the Listing requirement of 410.6;therefore, the panel is eliminating this section.

ResponseMessage:

Public Input No. 2589-NFPA 70-2017 [Section No. 410.54]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:21 PM

Page 30: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8482-NFPA 70-2018 [ Section No. 410.62(C)(1) ]

(1) Cord-Connected Installation.

A luminaire or a listed assembly in compliance with any of the conditions in 410.62(C)(1) (a)through (C)(1) (c) shall be permitted to be cord connected provided the luminaire is located directlybelow the outlet or busway, the cord is not subject to strain or physical damage, and the cord isvisible over its entire length except at terminations.

(a) A luminaire shall be permitted to be connected with a cord terminating in a grounding-typeattachment plug or busway plug. If grounding is not required in accordance with 410.42 , apolarized-type plug shall be permitted.

(b) A luminaire assembly equipped with a strain relief and canopy shall be permitted to use acord connection between the luminaire assembly and the canopy. The canopy shall be permitted toinclude a section of raceway not over 150 mm (6 in.) in length and intended to facilitate theconnection to an outlet box mounted above a suspended ceiling.

(c) Listed luminaires connected using listed assemblies that incorporate manufactured wiringsystem connectors in accordance with 604.100(C) shall be permitted to be cord connected.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 17 07:59:11 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The panel added provisions for cord connection using polarized attachment plugs inaccordance with revision being made to section 410.42. The UL 153 standard (portableluminaires) allows the use of polarized plugs and they are frequently used on shop lights.

ResponseMessage:

Committee Notes:

Date Submitted By

Jan 17,2018

NEC-CMPPanel 18

This revision only adds the second sentence in list item (a). Remainder is existing text.

Public Input No. 2599-NFPA 70-2017 [Section No. 410.62(C)(1)]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:22 PM

Page 31: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8512-NFPA 70-2018 [ New Section after 410.68 ]

410.69 Identification of Control Conductor Insulation.

Where control conductors are spliced, terminated, or connected in the same luminaire orenclosure as the branch-circuit conductors, the control conductor shall not be of a color reservedfor the grounded branch-circuit conductor or the equipment grounding conductor.

Informational Note: Refer to 200.6 and 250.119.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 17 09:41:37 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The panel has created a new section 410.69 to prevent lighting control conductors frombeing installed using the same color as the branch circuit conductors. One common controlconductor scheme is to use "purple and gray" colored control conductors. 200.6(A)specifically permits white and gray to be used in the identification of grounded conductors. Ashock incident could occur when "gray control" conductors are inadvertently spliced to thegrounded conductor. The panel concludes that wire colors reserved for grounded branchcircuit conductor or equipment grounding conductor should not be used for controlconductors. Ungrounded conductors can be any color.

ResponseMessage:

Public Input No. 2688-NFPA 70-2017 [New Section after 410.68]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:22 PM

Page 32: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8390-NFPA 70-2018 [ Section No. 410.70 ]

410.70 Combustible Shades and Enclosures.

Adequate airspace shall be provided between lamps and shades or other enclosures ofcombustible material.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 16 14:52:51 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

Section 410.70 was eliminated because the content of this section is fully addressed byANSI/UL 153, Standard for Portable Electric Lamps, and applied by the Listing requirementof 410.6. Eliminating this content relieves AHJs from any burden to evaluate the materialsand construction of these otherwise listed products.

ResponseMessage:

Public Input No. 2606-NFPA 70-2017 [Section No. 410.70]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:23 PM

Page 33: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8505-NFPA 70-2018 [ Section No. 410.82 ]

410.82 Portable Luminaires.

(A) General.

Portable luminaires shall be wired with flexible cord recognized by 400.4 and an attachmentplug of the polarized or grounding type. Where used with Edison-base lampholders, thegrounded conductor shall be identified and attached to the screw shell and the identified blade ofthe attachment plug.

(B) Portable Handlamps.

In addition to the provisions of 410.82(A) , portable handlamps shall comply with the following:

(0) Metal shell, paper-lined lampholders shall not be used.

(0) Handlamps shall be equipped with a handle of molded composition or other insulatingmaterial.

(0) Handlamps shall be equipped with a substantial guard attached to the lampholder orhandle.

(0) Metallic guards shall be grounded by means of an equipment grounding conductor runwith circuit conductors within the power-supply cord.

(0) Portable handlamps shall not be required to be grounded where supplied through anisolating transformer with an ungrounded secondary of not over 50 volts.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 17 09:23:00 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The panel has removed all of the portable luminaire construction requirements from PartVII because they are contained in the product standards and applied by the Listingrequirement of 410.6.

ResponseMessage:

Public Input No. 1724-NFPA 70-2017 [Section No. 410.82(B)]

Public Input No. 2613-NFPA 70-2017 [Section No. 410.82]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:23 PM

Page 34: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8515-NFPA 70-2018 [ Section No. 410.115(B) ]

(C) Installation in Fire-Resistant Construction.

Luminaires marked “FOR USE IN NON-FIRE-RATED INSTALLATIONS” shall not be used infire-rated installations. Where a luminaire is recessed in fire-resistant material in a building offire-resistant construction, a temperature higher than 90°C (194°F) but not higher than 150°C(302°F) shall be considered acceptable if the luminaire is plainly marked for that service. therecessed luminaire shall satisfy one of the following:

(1) The recessed luminaire shall be listed for use in a fire resistance–rated construction.

(2) The recessed luminaire shall be installed in or used with a luminaire enclosure that is listedfor use in a fire resistance–rated construction.

(3) The recessed luminaire shall be listed and shall be installed in accordance with a tested fireresistance–rated assembly. When a tested fire resistance–rated assembly allows theinstallation of a recessed fluorescent luminaire, a recessed LED luminaire of comparableconstruction shall be permitted.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 17 10:15:48 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The existing code text of 410.115(B) with only temperature requirements and with no meansof verification is insufficient. Testing that includes all the applicable considerations andsubsequent listing of a fire resistance rated assembly and luminaire by an NRTL takes awaythe guesswork for the installer, contractor, and electrical inspector in the field. The panel hasrevised the requirements for installation in Fire-Resistance Construction to be consistent withcurrent listing options and relocated the requirement to section 410.116 since it no longerreferences temperature requirements. The panel additionally updated the requirement withprovisions that address the use of LED luminaires.

ResponseMessage:

Public Input No. 3536-NFPA 70-2017 [Section No. 410.115(B)]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:24 PM

Page 35: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8529-NFPA 70-2018 [ Section No. 410.136(B) ]

(B) Combustible Low-Density Cellulose Fiberboard.

Where a surface-mounted luminaire containing a ballast, transformer, LED driver, or power supplyis to be installed on combustible low-density cellulose fiberboard, it shall be marked for thiscondition or shall be spaced not less than 38 mm (11⁄2 in.) from the surface of the fiberboard.Where such luminaires are partially or wholly recessed, the provisions of 410.110 through 410.122shall apply.

Informational Note: Combustible low-density cellulose fiberboard includes sheets, panels,

and tiles that have a density of 320 kg/m3 (20 lb/ft3) or less and that are formed of bondedplant fiber material but does not include solid or laminated wood or fiberboard that has a

density in excess of 320 kg/m3 (20 lb/ft3) or is a material that has been integrally treatedwith fire-retarding chemicals to the degree that the flame spread index in any plane of thematerial will not exceed 25, determined in accordance with tests for surface burningcharacteristics of building materials. See ANSI/ ASTM E84–2015a –17a , Standard TestMethod for Surface Burning Characteristics of Building Materials, or ANSI/UL 723–2013 UL723–2017 , Standard for Test for Surface Burning Characteristics of Building Materials.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 17 11:09:51 EST 2018

Committee Statement and Meeting Notes

Committee Statement: The references in the informational note are updated to the current editions.

Response Message:

Public Input No. 829-NFPA 70-2017 [Section No. 410.136(B)]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:25 PM

Page 36: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8530-NFPA 70-2018 [ Section No. 410.141(B) ]

(B) Within Sight or Locked Type.

The switch or circuit breaker shall be located within sight from the luminaires or lamps, or it shallbe permitted to be located elsewhere if it is lockable open in accordance with 110.25.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 17 11:13:42 EST 2018

Committee Statement and Meeting Notes

Committee Statement: The word “open” was added to align the text with 110.25.

Response Message:

Public Input No. 1589-NFPA 70-2017 [Section No. 410.141(B)]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:25 PM

Page 37: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8138-NFPA 70-2018 [ Section No. 411.6(D) ]

(D) Insulated Conductors.

Insulated secondary circuit conductors shall be of the type, and installed as, described in (1), (2),or (3):

(0) Class 2 cable supplied by a Class 2 power source and installed in accordance with Parts Iand III of Article 725 .

(0) Conductors, cord, or cable of the listed system and installed not less than 2.1 m (7 ft)above the finished floor unless the system is specifically listed for a lower installationheight.

(0) Wiring methods described in Chapter 3 .

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 09:06:34 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

411.6 (D) is redundant since Class-2 insulated conductors may be powered by a Class-2power supply in accordance with Article 725, Chapter 3 wiring is obviously allowed, and forcable/trapeze systems, since uninsulated conductors are allowed above 7 ft, it is obviousthat insulated conductors would also be allowed.

ResponseMessage:

Public Input No. 2735-NFPA 70-2017 [Section No. 411.6(D)]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:26 PM

Page 38: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8156-NFPA 70-2018 [ New Definition after Definition:

Photovoltaic (PV) Powered... ]

Retrofit Kit, Sign Specific.

A kit consisting of the necessary parts and hardware to allow for field installation in a host sign,based on the included installation instructions.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 10:16:04 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

These kits will include all parts and hardware to complete the retrofit in the field. The kit isintended to be installed in a specific host sign or sign type. The major kit component(s)and/or the installation instructions must carry the listing labeling, as required in 600.3.

ResponseMessage:

Public Input No. 3630-NFPA 70-2017 [New Definition after Definition: Photovoltaic (PV) Powered...]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:27 PM

Page 39: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8153-NFPA 70-2018 [ New Definition after Definition: LED Sign

Illumination Syst... ]

Host Sign.

A sign or outline lighting system already installed in the field that is designated for fieldconversion of the illumination system with a retrofit kit.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 10:05:31 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

An existing specific sign or sign type that is being considered for upgrade with theinstallation of a complete sign specific retrofit kit can best be identified in the installationinstructions as a host sign.

This term has also been used in the product safety standard for sign LED retrofit kits inUL879A.

ResponseMessage:

Public Input No. 3900-NFPA 70-2017 [New Definition after Definition: LED Sign Illumination Syst...]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:28 PM

Page 40: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8154-NFPA 70-2018 [ New Definition after Definition: Skeleton

Tubing. ]

Subassembly.

Component parts or a segment of a sign, retrofit kit, or outline lighting system that, whenassembled, forms a complete unit or product.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 10:07:39 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

This definition is similar to the UL48 definition. The term 'subassembly' is intended to beused for components that are used for field installed retrofit kits, signs, and outline lightingsystems. These systems are sign specific and outline the parts and components required toinstall a safe and code compliant installation outlined in the installation instructions.

ResponseMessage:

Public Input No. 3633-NFPA 70-2017 [New Definition after Definition: Skeleton Tubing.]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:28 PM

Page 41: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8157-NFPA 70-2018 [ Section No. 600.3 [Excluding any

Sub-Sections] ]

Fixed, mobile, or portable electric signs, section signs, outline lighting, photovoltaic (PV) poweredsigns, and retrofit kits, regardless of voltage, shall be listed and labeled , provided with installationinstructions, and installed in conformance with that listing, unless otherwise approved by specialpermission.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 10:26:56 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

Listed electric signs need to be shipped with a listing label to identify that the product issafe and can be connected to the grid safely. The local electrical inspector will depend onthe label and not require his/her inspection other than the primary connection. The label isalso a tracking device if, for any reason, the sign fails or is found to be unsafe.

ResponseMessage:

Public Input No. 3904-NFPA 70-2017 [Section No. 600.3 [Excluding any Sub-Sections]]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:29 PM

Page 42: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8159-NFPA 70-2018 [ Section No. 600.4 ]

600.4 Markings.

(A) Signs and Outline Lighting Systems.

Signs and outline lighting systems shall be listed and labeled ; marked with the manufacturer’s name,trademark, or other means of identification; and input voltage and current rating.

(B) Signs with a Retrofitted Illumination System.

(1) The retrofitted sign shall be marked that the illumination system has been replaced.

(2) The marking shall include the kit providers and installer’s name, logo, or unique identifier.

(3) Signs equipped with tubular light-emitting diode lamps powered by the existing sign sockets shall includea label alerting the service personnel that the sign has been modified. The label shall meet therequirements of 110.21(B). The label shall also include a warning not to install fluorescent lamps and shallalso be visible during relamping.

(C) Signs with Lampholders for Incandescent Lamps.

Signs and outline lighting systems with lampholders for incandescent lamps shall be marked to indicate themaximum allowable lamp wattage per lampholder. The markings shall be permanently installed, in letters atleast 6 mm (1⁄4 in.) high, and shall be located where visible during relamping.

(D) Visibility.

The markings required in 600.4(A) and listing labels shall not be required to be readily visible after installationbut and shall be permanently applied in a location visible during prior to servicing. The marking shall bepermitted to be installed in a location not readily viewed by the public.

(E) Durability.

Marking labels shall be permanent, durable and, when in wet locations, shall be weatherproof.

(F) Installation Instructions.

All signs, outline lighting, skeleton tubing systems, and retrofit kits shall be marked to indicate that field wiringand installation instructions are required.

Exception: Portable, cord-connected signs are not required to be marked.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 10:32:44 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The section is revised to provide visibility of markings at the time of installation and service, as wellas the electrical inspection. The markings are intended for the safety of inspection personnel.

ResponseMessage:

Public Input No. 878-NFPA 70-2017 [Section No. 600.4]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 2 3/7/2018 1:30 PM

Page 43: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

Public Input No. 3905-NFPA 70-2017 [Section No. 600.4(A)]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

2 of 2 3/7/2018 1:30 PM

Page 44: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8171-NFPA 70-2018 [ Section No. 600.5(A) ]

(A) Required Branch Circuit.

Each commercial building and each commercial occupancy accessible to pedestrians shall beprovided with at least one outlet in an accessible location at each entrance to each tenant spacefor sign or outline lighting system use. The outlet(s) shall be supplied by a branch circuit rated atleast 20 amperes that supplies no other load. Service locations, such as hallways, entrances, orcorridors, shall not be considered accessible to pedestrians.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 11:04:24 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

This section is clarified to state that entrances not accessible to customers, such asdelivery doors, do not require a sign outlet.

ResponseMessage:

Public Input No. 3140-NFPA 70-2017 [Section No. 600.5(A)]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:31 PM

Page 45: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8180-NFPA 70-2018 [ Section No. 600.5(C)(1) ]

(1) Supply.

The wiring method used to supply signs and outline lighting systems shall terminate within a sign,an outline lighting system enclosure, a suitable box, or a conduit body, or panelboard .

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 11:27:37 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The wiring methods for signs includes feeder conductors that terminate in panelboardswithin a sign body or sign enclosure. While it may be deemed a “suitable box”, thepanelboard serves as the landing point for energized feeders for distribution to branchcircuits with overcurrent devices.

ResponseMessage:

Public Input No. 3915-NFPA 70-2017 [Section No. 600.5(C)(1)]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:32 PM

Page 46: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8186-NFPA 70-2018 [ Section No. 600.5(C)(2) ]

(2) Enclosures as Pull Boxes.

Signs and transformer Transformer enclosures shall be permitted to be used as pull or junctionboxes for conductors supplying other adjacent signs, outline lighting systems, or floodlights thatare part of a sign and shall be permitted to contain both branch and secondary circuit conductors,provided the sign disconnecting means de-energizes all current-carrying conductors in theseenclosures .

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 11:38:22 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

This section was originally added to allow transformer boxes (enclosures) used to housetransformers to include primary and secondary conductors. The first word implied to someAHJs and installers that the sign body was an enclosure by default, which is not correctunless the sign is marked to require the use of a recognized component sign face. The signbody should not include these high voltage conductors. Removing the word signs will clarifythe intent of this section for transformer boxes and should eliminate the confusion.

This revision adds clarity to the requirement for the disconnecting means to ensure allconductors inside the box are de-energized prior to servicing.

ResponseMessage:

Public Input No. 3917-NFPA 70-2017 [Section No. 600.5(C)(2)]

Public Input No. 3645-NFPA 70-2017 [Section No. 600.5(C)(2)]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:32 PM

Page 47: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8200-NFPA 70-2018 [ Section No. 600.6 [Excluding any

Sub-Sections] ]

Each sign and outline lighting system, feeder conductor(s), or branch circuit(s) supplying a sign,outline lighting system, or skeleton tubing shall be controlled by an externally operable switch orcircuit breaker that opens all ungrounded conductors and controls no other load. The switch orcircuit breaker shall open all ungrounded conductors simultaneously on multi-wire branch circuits inaccordance with 210.4(B). Signs and outline lighting systems located within fountains shall havethe disconnect located in accordance with 680.13.

Exception No. 1: A disconnecting means shall not be required for an exit directional sign locatedwithin a building.

Exception No. 2: A disconnecting means shall not be required for cord-connected signs with anattachment plug.

Informational Note: The location of the disconnect is intended to allow service ormaintenance personnel and first responders complete and local control of the disconnectingmeans.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 12:59:05 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The informational note does not recognize that others than service and maintenanceelectricians have a risk associated with an energized sign or outline lighting system. Firstresponders are exposed to the same hazards and have a need to know the location ofenergized conductors and the disconnecting means.

ResponseMessage:

Public Input No. 3918-NFPA 70-2017 [Section No. 600.6 [Excluding any Sub-Sections]]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:33 PM

Page 48: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8216-NFPA 70-2018 [ Section No. 600.30 ]

600.30 Applicability.

Part II of this article shall apply to all of the following:

(1) Field-installed skeleton tubing

(2) Field-installed secondary circuits

(3) Outline lighting

(4) Field-installed retrofit kits

These requirements shall be in addition to the requirements of Part I.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 13:51:15 EST 2018

Committee Statement and Meeting Notes

Committee Statement: This clarifies that retrofit kits are suitable for field installation.

Response Message:

Public Input No. 3934-NFPA 70-2017 [Section No. 600.30]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:33 PM

Page 49: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8223-NFPA 70-2018 [ Section No. 600.33(C) ]

(C) Protection Against Physical Damage.

Where If subject to physical damage, the conductors shall be protected and installed inaccordance with 300.4. All through-wall penetrations shall be protected by a listed bushing orraceway.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 14:26:45 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The additional requirement to protect this type of wiring will only apply to section signinstallations. This type of installation requires many wall penetrations between letters andother signage, which necessitates a listed bushing or raceway for physical protection ofconductors passing through a wall.

ResponseMessage:

Public Input No. 3936-NFPA 70-2017 [Section No. 600.33(C)]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:34 PM

Page 50: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8227-NFPA 70-2018 [ New Section after 600.34 ]

600.35 Retrofit Kits.

(A) General.

A general-use or sign-specific retrofit kit for a sign or outline lighting system shall includeinstallation instructions and requirements for field conversion of a host sign. The retrofit kit shallbe listed and labeled.

(B) Installation.

The retrofit kit shall be installed in accordance with the installation instructions.

(1) Wiring Methods.

Wiring methods shall be in accordance with Chapter 3.

Exception: If powered from a Class 2 source, wiring methods shall be in accordance with600.12(C)(1)(2), 600.24 , and 600.33 .

(2) Damaged Parts .

All parts that are not replaced by a retrofit kit shall be inspected for damage. Any part found tobe damaged or damaged during conversion of the sign shall be replaced or repaired to maintainthe sign or outline lighting system’s dry, damp, or wet location rating.

(3) Workmanship.

Field conversion workmanship shall be in accordance with 110.12.

(4) Marking.

The retrofitted sign shall be marked in accordance with 600.4(B) .

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 14:44:15 EST 2018

Committee Statement and Meeting Notes

Committee Statement: Retrofit kits needed to be added to the article with the installation requirements.

Response Message:

Public Input No. 3939-NFPA 70-2017 [New Section after 600.34]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:34 PM

Page 51: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8386-NFPA 70-2018 [ Section No. 406.4(A) ]

(A) Grounding Type.

Except as provided in 406.4(D), receptacles installed on 15- and 20-ampere branch circuits shallbe of the grounding type. Grounding-type receptacles shall be installed only on circuits of thevoltage class and current for which they are rated, except as provided in 210.21(B)(1) for singlereceptacles or Table 210.21(B)(2) and Table 210.21(B)(3) for two or more receptacles .

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 16 13:58:52 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

This revision correlates the requirements with Article 210 for single receptacles installedon a lower-rated branch circuit. The referenced tables are only applicable to two or morereceptacles.

ResponseMessage:

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:35 PM

Page 52: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8345-NFPA 70-2018 [ Sections 406.9(A), 406.9(B) ]

(A) Damp Locations.

A receptacle installed outdoors in a location protected from the weather or in other damp locations shall havean enclosure for the receptacle that is weatherproof when the receptacle is covered (attachment plug cap notinserted and receptacle covers closed).

An installation suitable for wet locations shall also be considered suitable for damp locations.

A receptacle shall be considered to be in a location protected from the weather where located under roofedopen porches, canopies, marquees, and the like, and will not be subjected to a beating rain or water runoff. All15- and 20-ampere, 125- and 250-volt nonlocking receptacles shall be a listed weather-resistant type.

Informational Note: The types of receptacles covered by this requirement are identified as 5-15, 5-20,6-15, and 6-20 in ANSI/NEMA WD 6–2012 6–2016 , Wiring Devices — Dimensional Specifications.

(B) Wet Locations.

(1) Receptacles of 15 and 20 Amperes in a Wet Location.

Receptacles of 15 and 20 amperes, 125 and 250 volts installed in a wet location shall have an enclosure thatis weatherproof whether or not the attachment plug cap is inserted. An outlet box hood installed for thispurpose shall be listed and shall be identified as “extra-duty.” Other listed products, enclosures, or assembliesproviding weatherproof protection that do not utilize an outlet box hood need not be marked “extra duty.”

Informational Note No. 1: Requirements for extra-duty outlet box hoods are found inANSI/UL 514D–2013 UL 514D–2016 , Cover Plates for Flush-Mounted Wiring Devices. “Extra duty”identification and requirements are not applicable to listed receptacles, faceplates, outlet boxes,enclosures, or assemblies that are identified as either being suitable for wet locations or rated as one ofthe outdoor enclosure–type numbers of Table 110.28 that does not utilize an outlet box hood.

Exception: 15- and 20-ampere, 125- through 250-volt receptacles installed in a wet location and subject toroutine high-pressure spray washing shall be permitted to have an enclosure that is weatherproof when theattachment plug is removed.

All 15- and 20-ampere, 125- and 250-volt nonlocking-type receptacles shall be listed and so identified as theweather-resistant type.

Informational Note No. 2: The configuration of weather-resistant receptacles covered by thisrequirement are identified as 5-15, 5-20, 6-15, and 6-20 in ANSI/NEMA WD 6–2012 6–2016 , WiringDevices — Dimensional Specifications.

(2) Other Receptacles.

All other receptacles installed in a wet location shall comply with 406.9(B)(2) (a) or (B)(2)(b).

(a) A receptacle installed in a wet location, where the product intended to be plugged into it is notattended while in use, shall have an enclosure that is weatherproof with the attachment plug cap inserted orremoved.

(b) A receptacle installed in a wet location where the product intended to be plugged into it will beattended while in use (e.g., portable tools) shall have an enclosure that is weatherproof when the attachmentplug is removed.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 2 3/7/2018 1:35 PM

Page 53: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

Zip:

Submittal Date: Tue Jan 16 10:55:35 EST 2018

Committee Statement and Meeting Notes

Committee Statement: The references have been updated to the current editions.

Response Message:

Public Input No. 739-NFPA 70-2017 [Section No. 406.9]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

2 of 2 3/7/2018 1:35 PM

Page 54: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8378-NFPA 70-2018 [ New Section after 406.12 ]

406.13 Single-Pole Separable-Connector Type.

Single-pole separable connectors shall be listed and labeled and shall comply with 406.13(A) through (D).

(A) Locking or Latching Type.

Single-pole separable connectors shall be of either the locking or latching type and marked with themanufacturer’s name or identification and voltage and ampere ratings.

(B) Identification.

Connectors designated for connection to the grounded circuit conductor shall be identified by a white-colored housing; connectors designated for connection to the grounding circuit conductor shall be identifiedby a green-colored housing.

(C) Interchangeability.

Single-pole separable connectors shall be permitted to be interchangeable for ac or dc use or for differentcurrent ratings or voltages on the same premises, provided they are listed for ac/dc use and marked in asuitable manner to identify the system to which they are intended to be connected.

(D) Connecting and Disconnecting.

The use of single-pole separable connectors shall be performed by a qualified person and shall comply withat least one of the following conditions:

(1) Connection and disconnection of connectors are only possible where the supply connectors areinterlocked to the source, and it is not possible to connect or disconnect connectors when the supplyis energized.

(2) Line connectors are of the listed sequential-interlocking type so that load connectors are connected inthe following sequence and that disconnection is in the reverse sequence:

(a) Equipment grounding conductor connection

(b) Grounded circuit conductor connection, if provided

(c) Ungrounded conductor connection

(3) A caution notice that complies with 110.21(B) is provided on the equipment employing single-poleseparable connectors, adjacent to the line connectors, indicating that connections are to be performedin the following sequence and that disconnection is in the reverse sequence:

(a) Equipment grounding conductor connectors

(b) Grounded circuit-conductor connectors, if provided

(c) Ungrounded conductor connectors

Informational Note: A single-pole locking-type separable connector is investigated in accordancewith ANSI/UL 1691-2014, Single Pole Locking-Type Separable Connectors .

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 2 3/7/2018 1:36 PM

Page 55: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

City:

State:

Zip:

Submittal Date: Tue Jan 16 13:28:39 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

Article 406 does not address single pole separable connectors nor does it require a single pole separableconnector to be listed. Single-pole separable connectors are widely available in the market place and areused in a variety of applications, including land transportation, non-hazardous refinery and miningoperations. The nationally recognized product standard for single pole separable connectors, ANSI/UL1691 contains requirements that correspond to the required construction as well as the performance andmarking requirements to evaluate the suitability of a single pole separable connector. Requiring the use ofa listed single pole separable connector will confirm that the installed device complies with the requiredcharacteristics of 406.13. Sections 520.53(C) and 530.22 are the source of these requirements.

Article 406 contains requirements for a variety of different types of plugs and receptacles such asreceptacle with USB charger, tamper resistant receptacles and weather-resistant receptacles. However,the Article does not address single pole separable connectors, which are widely available in the marketplace. The proposed text identifies their proper connection and disconnection sequence, necessary forthe safe use of these devices. Sections 520.53(C) and 530.22 are the source of these requirements.

ResponseMessage:

Committee Notes:

Date Submitted By

Jan 16,2018

NEC-CMP Panel18

A reference to ANSI/UL 1691 needs to added in Annex A.

Public Input No. 1458-NFPA 70-2017 [New Article after 406]

Public Input No. 1457-NFPA 70-2017 [New Article after 406]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

2 of 2 3/7/2018 1:36 PM

Page 56: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8368-NFPA 70-2018 [ Section No. 406.12 ]

406.12 Tamper-Resistant Receptacles.

All 15- and 20-ampere, 125- and 250-volt nonlocking-type receptacles in the areas specified in 406.12(1)through (7) (8) shall be listed tamper-resistant receptacles.

(1) Dwelling units, in all areas including attached and detached garages and accessory buildings to dwellingunits, and common areas of multifamily dwellings specified in 210.52 and 550.13

(2) Guest rooms and guest suites of hotels and motels , motels, and their common areas

(3) Child care facilities

(4) Preschools and elementary education facilities

(5) Business offices, corridors, waiting rooms and the like in clinics, medical and dental offices, andoutpatient facilities

(6) Subset of assembly occupancies described in 518.2 to include places of waiting awaiting transportation,gymnasiums, skating rinks, and auditoriums

(7) Dormitories Dormitory units

(8) Assisted living facilities

Informational Note No. 1: This requirement would include receptacles identified as 5-15, 5-20, 6-15,and 6-20 in ANSI/NEMA WD 6-2016, Wiring Devices — Dimensional Specifications.

Informational Note No. 2: Assisted living facilities are Institutional Use Group I-1 per IBC 2015.

Exception to (1), (2), (3), (4), (5), (6), (7) and (8): Receptacles in the following locations shall not be requiredto be tamper resistant:

(1) Receptacles located more than 1.7 m (5 1⁄2 ft) above the floor

(2) Receptacles that are part of a luminaire or appliance

(3) A single receptacle, or a duplex receptacle for two appliances, located within the dedicated space foreach appliance that, in normal use, is not easily moved from one place to another and that is cord-and-plug-connected in accordance with 400.10(A)(6), (A)(7), or (A)(8)

(4) Nongrounding receptacles used for replacements as permitted in 406.4(D)(2)(a)

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 16 12:50:23 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The text in item (1) has been modified to improve clarity that a “dwelling unit includes attached anddetached garages and accessory buildings to a dwelling unit." It also clarifies that common areas ofmultifamily dwelling units are included.

The text in item (2) has been modified to clarify that guest rooms and guest suites of hotels andmotels includes their common area.

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 2 3/7/2018 1:36 PM

Page 57: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

In item (4), “elementary“ was deleted to remove ambiguity as to what age group of children will occupythe space.

In item (6), “waiting” was changed to “awaiting” because it is the correct verb.

In item (7), “dormitories” was changed to “dormitory unit” to use a more accurate term.

In item (8), "assisted living facilities" was added because children are present in these facilities.

In the Exception, commas were added to list item (3) to remove ambiguity that "for two appliances"applies only to duplex receptacles.

ResponseMessage:

Public Input No. 2083-NFPA 70-2017 [Section No. 406.12]

Public Input No. 2809-NFPA 70-2017 [Section No. 406.12]

Public Input No. 2297-NFPA 70-2017 [Section No. 406.12]

Public Input No. 2152-NFPA 70-2017 [Section No. 406.12]

Public Input No. 3128-NFPA 70-2017 [Section No. 406.12]

Public Input No. 2863-NFPA 70-2017 [Section No. 406.12]

Public Input No. 3755-NFPA 70-2017 [Section No. 406.12]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

2 of 2 3/7/2018 1:36 PM

Page 58: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8403-NFPA 70-2018 [ Definition: Closet Storage Space. ]

Clothes Closet Storage Space.

The volume bounded by the sides and back closet walls and planes extending from the closet floor verticallyto a height of 1.8 m (6 ft) or to the highest clothes-hanging rod and parallel to the walls at a horizontal distanceof 600 mm (24 in.) from the sides and back of the closet walls, respectively, and continuing vertically to thecloset ceiling parallel to the walls at a horizontal distance of 300 mm (12 in.) or the width of the shelf,whichever is greater; for a closet that permits access to both sides of a hanging rod, this space includes thevolume below the highest rod extending 300 mm (12 in.) on either side of the rod on a plane horizontal to thefloor extending the entire length of the rod. See Figure 410.2.

Figure 410.2 Clothes Closet Storage Space.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 16 15:44:11 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The provisions of section 410.16 were responsive to field incident data that involved clothes closets.The definition in section 410.2 and Fig. 410.2 has been revised to specify the storage space as aclothes closet.

This revision could necessitate research into other types of closet storage.

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 2 3/7/2018 1:36 PM

Page 59: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

ResponseMessage:

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

2 of 2 3/7/2018 1:36 PM

Page 60: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8400-NFPA 70-2018 [ Section No. 410.16 ]

410.16 Luminaires in Clothes Closets.

(A) Luminaire Types Permitted.

Only luminaires of the following types shall be permitted in a clothes closet:

(1) Surface-mounted or recessed incandescent or LED luminaires with completely enclosed light sources

(2) Surface-mounted or recessed fluorescent luminaires

(3) Surface-mounted fluorescent or LED luminaires identified as suitable for installation within the clothescloset storage space

(B) Luminaire Types Not Permitted.

Incandescent luminaires with open or partially enclosed lamps and pendant luminaires or lampholders shallnot be permitted.

(C) Location.

The minimum clearance between luminaires installed in clothes closets and the nearest point of a clothescloset storage space shall be as follows:

(1) 300 mm (12 in.) for surface-mounted incandescent or LED luminaires with a completely enclosed lightsource installed on the wall above the door or on the ceiling.

(2) 150 mm (6 in.) for surface-mounted fluorescent luminaires installed on the wall above the door or on theceiling.

(3) 150 mm (6 in.) for recessed incandescent or LED luminaires with a completely enclosed light sourceinstalled in the wall or the ceiling.

(4) 150 mm (6 in.) for recessed fluorescent luminaires installed in the wall or the ceiling.

(5) Surface-mounted fluorescent or LED luminaires shall be permitted to be installed within the clothes closetstorage space where identified for this use.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 16 15:27:28 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The provisions of section 410.16 were responsive to field incident data that involved clothes closets.This revision clarifies that the requirement is applicable only to clothes closets, as previouslyindicated by the title.

ResponseMessage:

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:41 PM

Page 61: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8412-NFPA 70-2018 [ New Section after 410.117 ]

410.118 Access to Other Boxes.

Luminaires recessed in ceilings, floors, or walls shall not be used to access outlet, pull, orjunction boxes or conduit bodies, unless the box or conduit body is an integral part of the listedluminaire.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 16 16:00:11 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The new text clarifies that a luminaire cannot be used to access junction boxes thatare not associated with wiring for the luminaire.

ResponseMessage:

Committee Notes:

Date Submitted By

Jan 16,2018

NEC-CMPPanel 18

This new section is intended to be located in Part X. The existing 410.118 in Part XI should be renumbered as 410.119.

Public Input No. 1805-NFPA 70-2017 [Section No. 410.24(B)]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:41 PM

Page 62: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8542-NFPA 70-2018 [ Section No. 410.137(C) ]

(C) Wired Luminaire Sections.

Wired luminaire sections are paired, with a ballast(s) or LED driver(s) supplying a lamp lightsource or lamps light sources in both. For interconnection between paired units, it shall bepermissible to use metric designator 12 (trade size 3⁄8) flexible metal conduit in lengths notexceeding 7.5 m (25 ft), in conformance with Article 348. Luminaire wire operating at line voltage,supplying only the ballast(s) or LED driver(s) of one of the paired luminaires, shall be permitted inthe same raceway as the lamp light source supply wires of the paired luminaires where thevoltage rating of the light source supply wires is greater than the line voltage .

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 17 11:42:26 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The section has been updated to include provisions for LED light sources. Since someLED drivers operate with a Class 2 output, the last sentence of the section was updated toclarify that Class 2 wiring cannot be run in the same conduit as conductors operating at linevoltage.

ResponseMessage:

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:41 PM

Page 63: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8537-NFPA 70-2018 [ New Section after 410.160 ]

Part XVI. Special Provisions for Horticultural Lighting Equipment

410.170 General.

Luminaires complying with Parts, I. II, III, IV, V, VI, VII, IX, X, XI, and XII of this article shall be permitted tobe used for horticultural lighting. Part XVI shall additionally apply to lighting equipment specifically identifiedfor horticultural use.

Informational Note: Lighting equipment identified for horticultural use is designed to provide aspectral characteristic needed for the growth of plants and can also provide supplemental generalillumination within the growing environment.

410.172 Listing.

Lighting equipment identified for horticultural use shall be listed.

410.174 Installation and Use.

Lighting equipment identified for horticultural use shall be installed and used in accordance with themanufacturer’s installation instructions and installation markings on the equipment as required by thatlisting.

410.176 Locations Not Permitted.

(A) General Lighting.

Lighting equipment identified for horticultural use shall not be installed as lighting for general illuminationunless such use is indicated in the manufacturer’s instructions.

(B) Installed Location.

Lighting equipment identified for horticultural use shall not be installed where it is likely to be subject tophysical damage or where concealed.

410.178 Flexible Cord.

Flexible cord shall only be permitted when provided as part of listed lighting equipment identified forhorticultural use for any of the following uses:

(1) Connecting a horticultural lighting luminaire directly to a branch circuit outlet

(2) Interconnecting horticultural lighting luminaires

(3) Connecting a horticultural lighting luminaire to a remote power source

Informational Note: Remote power sources include LED drivers, fluorescent ballasts, or HIDballasts.

410.180 Fittings and Connectors.

Fittings and connectors attached to flexible cords shall be provided as part of a listed horticultural lightingequipment device or system and installed in accordance with the instructions provided as part of that listing.

410.182 Grounding.

Lighting equipment identified for horticultural use shall be grounded as required in Article 250 and Part V ofthis article.

410.184 Ground-Fault Circuit-Interrupter Protection.

Lighting equipment identified for horticultural use employing flexible cord(s) with one or more connectorsshall be supplied by lighting outlets with ground-fault circuit-interrupter protection.

410.186 Support.

Special fittings identified for support of horticultural lighting equipment shall be designed specifically for thehorticultural lighting equipment on which they are installed and shall be used in accordance with theinstallation instructions provided and shall be securely fastened.

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 2 3/7/2018 1:42 PM

Page 64: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

410.188 Hazardous (Classified) Locations.

Where installed in hazardous (classified) locations, horticultural lighting equipment shall conform to Articles500 through 517 in addition to this article.

Supplemental Information

File Name Description Approved

70_FR8537_410_PartXVI.docx For staff use ✓

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 17 11:28:11 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

With the increasing numbers of indoor plant growing facilities being established, horticultural lightingequipment providing a wavelength(s) of light necessary for plant growth has become a rapidly expandingtechnology. While the Code has provisions for agricultural buildings in Article 547, the newer indoorhorticultural lighting installations demand different considerations. For example, since horticultural lightingequipment needs to be adjustable to accommodate seasonal plant diversity and growth, flexibleconnection to branch circuits and between luminaires is provided. Also, horticultural lighting equipment istypically installed in close proximity to each other, and can have unique support from structures in theenvironment.

Code requirements are needed to ensure safe installations and to facilitate inspection; therefore, thepanel has created new Part XVI for Horticultural Lighting Equipment.

ResponseMessage:

Public Input No. 3448-NFPA 70-2017 [New Section after 410.160]

Public Input No. 2741-NFPA 70-2017 [New Part after XV.]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

2 of 2 3/7/2018 1:42 PM

Page 65: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8148-NFPA 70-2018 [ New Definition after Definition:

Photovoltaic (PV) Powered... ]

Retrofit Kit, General Use.

A kit consisting of primary parts, which does not include all the parts for a complete subassemblybut includes a list of required parts and installation instructions to complete the subassembly inthe field.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 09:56:48 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

These kits, which can comprise only the major components, might not include all of theparts and pieces required to complete the retrofit. Specific installation instructions will needto outline the other items required for the completion of the retrofit to be assembled in thefield. The major kit component(s) and/or the installation instructions must carry the listinglabeling.

ResponseMessage:

Public Input No. 3624-NFPA 70-2017 [New Definition after Definition: LED Sign Illumination Syst...]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:42 PM

Page 66: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8174-NFPA 70-2018 [ New Section after 600.5(A) ]

(B) Marking.

A disconnecting means for a sign, outline lighting system, or controller shall be marked with theidentity of the sign, outline lighting system, or controller it controls.

Exception: An external disconnecting means that is mounted on the sign body, signenclosure, sign pole, or controller shall not be required to identify the sign or outline lightingsystem it controls.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 11:13:42 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

External disconnecting means in a remote location from the sign, outline lighting system, orcontroller might not be readily associated with the sign, outline lighting system, or controllerthey control. Anecdotal evidence points to situations where a disconnect technically withinsight of the sign (that is, not exceeding 50 feet and visible to the service technician) wouldnot be recognized or identified as controlling the sign, outline lighting system, or controller byanyone other than the service technician.

Sign service and maintenance personnel, as well as first responders, have a need to knowwhat utilization equipment the disconnect(s) is designated for where it is not mounted on thesign, outline lighting system, or controller.

ResponseMessage:

Public Input No. 3931-NFPA 70-2017 [Section No. 600.5(B)]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:43 PM

Page 67: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8289-NFPA 70-2018 [ New Section after 600.6(A)(3) ]

(4) Remote Location.

The disconnecting means, if located remote from the sign, sign body, or pole, shall be mountedat an accessible location available to first responders and service personnel. The location of thedisconnect shall be marked with a label at the sign location and marked as the disconnect forthe sign or outline lighting system. The label shall comply with 110.21(B).

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 16 08:00:19 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

This revision will allow access to and identify the location of the disconnect for firstresponders and service personnel.

ResponseMessage:

Public Input No. 215-NFPA 70-2017 [New Section after 600.6(A)(2)]

Public Input No. 3924-NFPA 70-2017 [Section No. 600.6(A)(2)]

Public Input No. 3927-NFPA 70-2017 [Section No. 600.6(A)(3)]

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:43 PM

Page 68: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8217-NFPA 70-2018 [ Section No. 600.33(A) ]

(A) Insulation and Sizing of Class 2 Conductors.

Class 2 cable listed for the application that complies with Table 600.33(A)(a) or Table 600.33(A)(b) forsubstitutions shall be installed on the load side of the Class 2 power source. The conductors shall have anampacity not less than the load to be supplied and shall not be sized smaller than 18 AWG.

Table 600.33(A)(a) Applications of Power Limited Cable in Signs and Outline Lighting

Location CL2 CL3 CL2R CL3R CL2P CL3P PLTC

Nonconcealed spaces inside buildings Y Y Y Y Y Y Y

Concealed spaces inside buildings that are not used asplenums or risers

Y Y Y Y Y Y Y

Environmental air spaces plenums or risers N N N N Y Y N

Environmental air spaces risers N N Y Y Y Y N

Wet locations N N N N N N Y

Y = Permitted. N = Not Permitted.

Table 600.33(A)(b) Class 2 Cable Substitutions

Cable Type Permitted Substitutions

CL3P CMP

CL2P CMP, CL3P

CL3R CMP, CL3P, CMR

CL2R CMP, CL3P, CL2P, CMR, CL3R

CL3 CMP, CL3P, CMR, CL3R, CMG, CM, PLTC

CL2 CMP, CL3P, CL2P, CMR, CL3R, CL2R, CMG, CM, PLTC, CL3

CL3X CMP, CL3P, CMR, CL3R, CMG, CM, PLTC, CL3, CMX

CL2X CMP, CL3P, CL2P, CMR, CL3R, CL2R, CMG, CM, PLTC, CL3, CL2, CMX,CL3X

PLTC None

(1) General Use.

CL2 or CL3, PLTC, or any listed applicable cable for general use shall be installed within and on buildings orstructures.

(2) Other Building Locations.

In other locations, any listed applicable cable permitted in 600.33(A)(1), (A)(2), (A)(3), and (A)(4) and Table600.33(A)(a) and (A)(2) (b) shall be permitted to be used as follows:

(1) CL2P or CL3P — Ducts, plenums, or other spaces used for environmental air

(2) CL2R or CL3R — Vertical shafts and risers

(3) Substitutions from Table 600.33(A)(b)

(3) Wet Locations.

Class 2 cable used in a wet location shall be listed and marked suitable for use in a wet location.

(4) Other Locations.

Class 2 cable exposed to sunlight shall be listed and marked “ sunlight resistant — suitable for outdoor use.”

Exception: Listed PLTC not marked as sunlight resistant shall be permitted.

Informational Note: PLTC is tested for exposure to sunlight but might not be so marked.

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 2 3/7/2018 1:44 PM

Page 69: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

Supplemental Information

File Name Description Approved

70_FR8217_600.33_A_.docx For staff use ✓

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 14:05:37 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

Riser cables are not allowed in a plenum. To correct this inaccuracy, this revision adds separatelines for Risers and Plenums.

PLTC is added to the Table 600.33(A)(2) to reinforce that there is no substitution for this cabletype.

A new exception and informational note are added to 600.33(A)(4) to address the applicability ofPLTC where sunlight resistance is required.

ResponseMessage:

Public Input No. 2657-NFPA 70-2017 [Section No. 600.33(A) [Excluding any Sub-Sections]]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

2 of 2 3/7/2018 1:44 PM

Page 70: First Revision No. 8241-NFPA 70-2018 [ Global Input ]

First Revision No. 8139-NFPA 70-2018 [ Section No. 605.1 ]

605.1 Scope.

(A) Covered.

This article covers electrical equipment, lighting accessories, and wiring systems used to connect,contained within, or installed on office furnishings.

(B) Not Covered.

This article does not apply to individual office furnishings not connected to a system, such aschairs, freestanding desks, tables, storage units, and shelving units.

Submitter Information Verification

Submitter Full Name: NEC-CMP Panel 18

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 15 09:10:21 EST 2018

Committee Statement and Meeting Notes

CommitteeStatement:

The scope was broken down into first level subdivisions. The scope was clarified tospecify items that are not covered by the article.

ResponseMessage:

Public Input No. 2644-NFPA 70-2017 [Sections 605.1, 605.2]

Editorial Comment

Click here

National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/...

1 of 1 3/7/2018 1:44 PM