INTRODUCTION
PRINCIPLE PURPOSE OF FLAME SAFEGUARDSUPERVISIORY SYSTEM IS TO ENSURE THAT ITIS SAFE TO LIGHT THE BOILER AND CONTINUEBOILER OPERATION.
IT IS ALSO USED FOR BOILER SHUTDOWN. ACCURATE DETECTION OF A FIRE IS ONE OF
THE MOST IMPORTANT TASKS OF FSSS.
FOR THIS PURPOSE THERMOCOUPLES , FLAME
RODS OR FLAME SCANNERS ARE INSTALLED. UV, IR AND MULTIPLE FREQUENCY SENSING
ARE THE DIFFERENT TYPES OF FLAMESCANNERS.
7/31/2019 Flame Scanners1
3/24
7/31/2019 Flame Scanners1
4/24
7/31/2019 Flame Scanners1
5/24
MECHANICAL COMPONENTSMECHANICAL COMPONENTS
Comprises of a stationary part called theflame scanner guide assembly and a removablepart called the flame scanner assembly.
FLAME SCANER GUIDE ASSEMBLY:- SCANNER HEAD HOUSING
FLEXIBLE METAL HOSE :- Adapts scanner to tilting ofwind box nozzles.
RIGID GUIDE PIPE SECTION:- Fixed to the wind boxand serves as a protective cover/packing gland.
COOLING AIR MANIFOLD:- is screwed onto theguide pipe
COVER PLATE: closes the wind box opening when
scanner is removed for maintenance.
7/31/2019 Flame Scanners1
6/24
MECHANICAL COMPONENTSMECHANICAL COMPONENTS
FLAME SCANNER ASSEMBLY:-
SCANNER HEAD ASSEMBLY:- Comprises of ascanner head body with the collimator tube, shield,
collimating lens, barrel, mounting plate,compression spring, one end of fiber optic cableand a plug.
FLEXIBLE METAL HOSE:- Houses the fiber opticcable
RIGID PIPE:- Houses the fiber optic cable SCANNER HOUSING ASSEMBLY:- houses the
scanner head electronics card which convertsvisible light signal to equivalent electrical signal.
7/31/2019 Flame Scanners1
7/24
FLAME SCANNER ASSEMBLY:-
FLEXIBLE
METAL
HOSERIGID PIPE
SCANNER
HOUSING
SCANNER HEAD
ASSEMBLY
7/31/2019 Flame Scanners1
8/24
FLAME SCANNER ASSEMBLY:-
COMPRESSION SPRING FIBER OPTIC CABLE
PLUG
SCANNER HEAD BODYLENSSPACER
7/31/2019 Flame Scanners1
9/24
ELECTRICAL COMPONENETSELECTRICAL COMPONENETS
LOCAL:- SCANNER HOUSING ELECTRONICS
REMOTE :- POWER SUPPLY MODULE:-
INTENSITY & FAULT DETECTION CARD:-
FREQUENCY DETECTION CARD:-
LAMP & METER CARD:-
LAMP DRIVER CARD:-
2/4 FLAME INDICATION & FAULT ALARM:-
7/31/2019 Flame Scanners1
10/24
ELECTRICAL COMPONENTSELECTRICAL COMPONENTS
SCANNER HOUSING ELECTRONICSSCANNER HOUSING ELECTRONICS :- Flame signal (light) transmitted via the fiber
optic cable strikes a photodiode.
Light signal is converted into an small current
signal by the photodiode. Current signal is converted to a voltage signal.
(1.5v for intense brightness and 6.4 v for nolight)
Voltage signal is amplified by an amplifier ofgain 1/3.
Voltage signal is the converted into a currentsignal and sent to remote electronics.
7/31/2019 Flame Scanners1
11/24
SCANNER HOUSING ELECTRONICSSCANNER HOUSING ELECTRONICS
PHOTOCOUPLER
ASSEMBLY
TRIMMING POTS
7/31/2019 Flame Scanners1
12/24
ELECTRICAL COMPONENTSELECTRICAL COMPONENTS
POWER SUPPLY CARD :-
I/P voltage and frequency:- 110V 50 Hz
O/P voltage:- +15v, -15VDC
7/31/2019 Flame Scanners1
13/24
POWER SUPPLY CARDPOWER SUPPLY CARD:-
P/S SWITCH
7/31/2019 Flame Scanners1
14/24
ELECTRICAL COMPONENTSELECTRICAL COMPONENTS
INTENSITY AND FAULT DETECTION CARDINTENSITY AND FAULT DETECTION CARD :-
- Current Signal Converted To Equivalent millivoltsignal.
- Intensity slope is inverted and multiplied by factor
3.
- This active flame signal consists of intensity andfrequency components. The active flame signal istransmitted to the frequency detection cards aswell as the intensity circuitry.
- The ac component is eliminated to obtain anintensity only flame signal.
7/31/2019 Flame Scanners1
15/24
7/31/2019 Flame Scanners1
16/24
INTENSITY AND FAULT DETECTION CARDINTENSITY AND FAULT DETECTION CARD
INTENSITY
INDICATOR
DROP OUT
SWITCH
DROP OUT
POT
PULL IN POT
PULL OUT
SWITCH
7/31/2019 Flame Scanners1
17/24
ELECTRICAL COMPONENTSELECTRICAL COMPONENTS
FREQUENCY DETECTION CARDFREQUENCY DETECTION CARD :-
- Two types of frequency detection cards used. Oneis tuned to frequency 3hz to determine existencefireball flame frequency in the active flame signal
and the other is tuned to 29hz and is used fordetermining oil gun flame frequency.
- Active flame signal from intensity and faultdetection card is ac coupled to block intensityinformation.
- Ac signal is compared with set frequency. A matchgenerates a logic one.
- Delay of 2 secs is provided during frequencypermissive drop out.
7/31/2019 Flame Scanners1
18/24
FREQUENCY DETECTION CARDFREQUENCY DETECTION CARD
FILTER
SWITCH FREQUENCY LED
YELLOW TRIM
7/31/2019 Flame Scanners1
19/24
ELECTRICAL COMPONENTSELECTRICAL COMPONENTS
LAMP AND METER CARDLAMP AND METER CARD :-
- Oil guns flame/no flame and visual intensityFAULT warnings are generated.
- Flame intensity signal is indicated on Flameintensity mA Meter.
- Power supply of +/-15Vdc is provided to thescanner housing electronics.
7/31/2019 Flame Scanners1
20/24
LAMP AND METER CARDLAMP AND METER CARD
FAULT LED
INTENSITY METER
FLAME LED
7/31/2019 Flame Scanners1
21/24
ELECTRICAL COMPONENTSELECTRICAL COMPONENTS
2/4 FAULT INDICATION AND FAULT2/4 FAULT INDICATION AND FAULTALARMALARM:-
- Provides contact closure of relay when at least
2 out of 4 scanners are detecting fireballflame.
- Provides contact closure of relay when fault isdetected on any scanner cable or scannerhead electronics.
- These contact are further used in DCS:
- Fault signal is used to alert operator ofexisting fault is system.
- 2/4 flame scanner in service is used in Boiler
tripping logic.
7/31/2019 Flame Scanners1
22/24
2/4 FAULT INDICATION AND FAULT ALARM2/4 FAULT INDICATION AND FAULT ALARM:-
RELAYS
2/4 FLAME
FAULT
7/31/2019 Flame Scanners1
23/24
7/31/2019 Flame Scanners1
24/24