Date: Job Name/Location: PO No.: Architect: Engr: GC: Rep: For: File Approval Mech: Resubmit Other Tag #: (Company) (Project Manager) Multi F Inverter Heat Pump Outdoor Unit DFSSBAD019US 013A08 Performance: LMU187HV Capacity (Btu/h) 18,000 Cooling Power Input (kW) 1.12 Heating Power Input (kW) 1.29 Cooling Nominal Test Conditions: Heating Nominal Test Conditions: Indoor: 80°F DB/67°F WB Indoor: 70°F DB/60°F WB Outdoor: 95°F DB/75°F WB Outdoor: 47°F DB/43°F WB Electrical: Power Supply (V¹/Hz/Ø) 208230/60/1 MOP (A) 15 MCA (A) 11.0 Cooling Rated Amps (A) 11.4 Heating Rated Amps (A) 11.9 Compressor (A) 8.2 Fan Motor (A) 0.40 Piping: Refrigerant Charge (lbs) 4.19 Liquid Line (in, OD) 1/4 (2 Each) Vapor Line (in, OD) 3/8 (2 Each) Max Total Piping (ft)² 164.0 Max Elevation between ODU and IDU (ft) 49.2 Max Elevation between IDU and IDU (ft) 24.6 Controls Features: •Auto operaƟon •Auto restart operaƟon •Defrost/Deicing •Inverter (variable speed compressor) •Low ambient operaƟon to 14F (cooling mode) •Restart delay (3minutes) •Self diagnosis •SoŌ start Operating Range: Cooling (°F DB) 14118 Heating (°F WB) 064 Unit Data: Refrigerant Type R410A Refrigerant Control EEV Sound Pressure (±3 dB(A))³ 51 Net Unit Weight (lbs) 123.5 Shipping Weight (lbs) 132.2 Heat Exchanger Coating GoldFin™ Max Number of Indoor Units 2 Compressor: Quantity 1 Type TwinRotary Inverter Oil/Type FVC68D Fan: Type Propeller Quantity 1 Fan Motor/Drive Brushless Digitally Controlled/Direct Airflow Rate (CFM) 2,119 Standard Features: •Limited Five Year Compressor Warranty •Limited Two Year Functional Parts Warranty Notes: 1.Acceptable operaƟng voltage: 187V253V. 2.Piping lengths are equivalent. 3.Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996. 4.All communicaƟon cable to be minimum 18 AWG, 2conductor, stranded, shielded and must comply with applicable local and national code. 5.See Engineering Manual for sensible and latent capaciƟes. 6.Power wiring cable size must comply with the applicable local and naƟonal code. 7.This data is rated 0 Ō above sea level, with 24.6 Ō of refrigerant line and a 0 Ō level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95 – 105%. 8.Must follow installaƟon instrucƟons in the applicable LG installaƟon manual. 1 of 4 Max ODU to IDU Piping (ft) 82.0 Piping Length (no add'l refrigerant, ft) 49.2 Communication Cable (No. x AWG)³ 4 x 18 Min Number of Indoor Units 2 For continual product development, LG reserves the right to change specifications without notice. LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com Optional Accessories: PI485 Integration Board (PMNFP14A0) AC Smart II (PQCSW320A1E) AC Ez (PQCSZ250S0) MOP Maximum Overcurrent Protection MCA Minimum Circuit Ampacity ODU Outdoor Unit IDU Indoor Unit AWG American Wire Gage

Flex Multi-Split Inverted Heat Pump Outdoor Unit · 2015. 9. 30. · Max Elevation between ODU and IDU (ft) 49.2 Max Elevation between IDU and IDU (ft) 24.6 Controls Features: •Auto

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

  • Date:

    Job Name/Location:

    PO No.:

    Architect:Engr:

    GC:

    Rep:

    For: File

    Approval

    Mech:

    Resubmit

    Other

    Tag #:

    (Company) (Project Manager)

    Multi F Inverter Heat Pump Outdoor Unit

    DFS‐SB‐AD‐019‐US 013A08

    Performance:

    LMU187HV

    Capacity (Btu/h) 18,000Cooling Power Input (kW) 1.12Heating Power Input (kW) 1.29Cooling Nominal Test Conditions: Heating Nominal Test Conditions:Indoor: 80°F DB/67°F WB Indoor: 70°F DB/60°F WBOutdoor: 95°F DB/75°F WB Outdoor: 47°F DB/43°F WB

    Electrical:Power Supply (V¹/Hz/Ø) 208‐230/60/1MOP (A) 15MCA (A) 11.0Cooling Rated Amps (A) 11.4Heating Rated Amps (A) 11.9Compressor (A) 8.2Fan Motor (A) 0.40

    Piping:

    Refrigerant Charge (lbs) 4.19Liquid Line (in, OD) 1/4 (2 Each)Vapor Line  (in, OD) 3/8 (2 Each)Max Total Piping (ft)² 164.0

    Max Elevation between ODU and IDU (ft) 49.2Max Elevation between IDU and IDU (ft) 24.6

    Controls Features: •Auto opera on  •Auto restart opera on •Defrost/Deicing •Inverter (variable speed compressor)

    •Low ambient opera on to 14F (cooling mode) •Restart delay (3‐minutes) •Self diagnosis •So  start

    Operating Range:Cooling (°F DB) 14‐118Heating (°F WB) 0‐64

    Unit Data:

    Refrigerant Type R410ARefrigerant Control EEVSound Pressure (±3 dB(A))³ 51Net Unit Weight (lbs) 123.5Shipping Weight (lbs) 132.2Heat Exchanger Coating GoldFin™

    Max Number of Indoor Units 2

    Compressor:

    Quantity 1Type Twin‐Rotary InverterOil/Type FVC68D

    Fan:

    Type PropellerQuantity 1Fan Motor/Drive Brushless Digitally Controlled/DirectAirflow Rate (CFM) 2,119

    Standard Features: •Limited Five Year Compressor Warranty•Limited Two Year Functional Parts Warranty

    Notes: 1.Acceptable opera ng voltage: 187V‐253V. 2.Piping lengths are equivalent. 3.Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996. 4.All communica on cable to be minimum 18 AWG, 2‐conductor, stranded, shielded and 

    must comply with applicable local and national code. 5.See Engineering Manual for sensible and latent capaci es. 6.Power wiring cable size must comply with the applicable local and na onal code. 7.This data is rated 0   above sea level, with 24.6   of refrigerant line and a 0   level 

    difference between outdoor and indoor units.  All capacities are net with a combination ratio between 95 – 105%.

    8.Must follow installa on instruc ons in the applicable LG installa on manual.

    1 of 4

    Max ODU to IDU Piping (ft) 82.0Piping Length (no add'l refrigerant, ft) 49.2

    Communication Cable (No. x AWG)³ 4 x 18

    Min Number of Indoor Units 2

    For continual product development, LG reserves the right to change specifications without notice.LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com

    Optional Accessories:PI‐485 Integration Board (PMNFP14A0)AC Smart II (PQCSW320A1E)AC Ez (PQCSZ250S0)

    MOP ‐ Maximum Overcurrent Protection MCA ‐ Minimum Circuit Ampacity

    ODU ‐ Outdoor Unit IDU ‐ Indoor Unit

    AWG ‐ American Wire Gage

  • Job Name/Location:

    Tag #:Date:PO No.:

    Multi F Inverter Heat Pump Outdoor Unit

    DFS‐SB‐AD‐019‐US 013A08

    LMU187HV

    2 of 4For continual product development, LG reserves the right to change specifications without notice.LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com

  • Job Name/Location:

    Tag #:Date:PO No.:

    Flex Multi Inverter Heat Pump Outdoor UnitLMU187HV

    Capacity  data is based on the following conditions – Cooling Nominal Test Conditions: Heating Nominal Test Conditions:Indoor: 80°F DB/67°F WB Indoor: 70°F DB/60°F WBOutdoor: 95°F DB/75°F WB Outdoor: 47°F DB/43°F WB

    Refer to the EPDB Capacity Tables for capacities at other temperatures.

    Page 3 of 4DFS‐SB‐AD‐019‐US 013A08For continual product development, LG reserves the right to change specifications without notice.LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com

  • Job Name/Location:

    Tag #:Date:PO No.:

    Flex Multi Inverter Heat Pump Outdoor UnitLMU187HV

    Page 4 of 4DFS‐SB‐AD‐019‐US 013A08For continual product development, LG reserves the right to change specifications without notice.LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com

    Capacity  data is based on the following conditions – Cooling Nominal Test Conditions: Heating Nominal Test Conditions:Indoor: 80°F DB/67°F WB Indoor: 70°F DB/60°F WBOutdoor: 95°F DB/75°F WB Outdoor: 47°F DB/43°F WB

    Refer to the EPDB Capacity Tables for capacities at other temperatures.

    File: OffApproval: OffResubmit: OffOther: OffPI485 Integration Board PMNFP14A0: OffAC Smart II PQCSW320A1E: OffAC Ez PQCSZ250S0: OffOther Field: Architect: GC: Engr: Mech: Company: Project Manager: Job Name/Location: Tag #: Date: PO No: Remarks7: Remarks6: Remarks5: Remarks4: Remarks3: Remarks2: Remarks1: