10
1651B 1652B 1653B Fluke 1650B Series Multifunction Installation Testers The installation testing solution for demanding environments The Fluke 1650B Series testers, with new advanced features, are the perfect instal- lation testing tool for verifying the safety of electrical installations in domestic, com- mercial, and industrial applications. Ensure that fixed wiring is correctly installed and compliant with IEC 60364, HD 384 require- ments, and all relevant local standards. The 1650B Series is efficient to use by allowing the user to measure loop impedance with- out tripping RCD’s, eliminating the need to bypass them. Slim reach probes allow you to keep your eyes on the panel while probing hard to reach areas. With easy-to-operate controls, a large display with a wide viewing angle, padded neck strap, and a compact, ergonomic design, these testers are com- fortable enough to use for all day testing. Extended Specifications Compact, lightweight and com- fortable to wear Simple operation for fast, easy testing Fast high current loop test (high current mode) Advanced loop testing prevents RCDs from tripping Variable RCD current mode for customized settings Zero adapter for easy test lead compensation The PASS/FAIL indicator takes the guesswork out of RCD testing Insulation test voltages (1651: 250 V, 500 V, 1000 V), (1652: 250 V, 500 V, 1000 V), (1653: 50 V, 100 V, 250 V, 500 V, 1000 V) for a variety of applications Select voltage measurement quickly and easily between L-N, L-PE, and N-PE Dual display gives simultaneous readout of mains voltage and frequency Auto discharge allows fast and safe discharge of electrical energy in capacitive circuits Added safety through live cir- cuit detection, to check and inhibit test if circuit under test is live Wiring connection check indi- cation and live circuit detection for added safety Time saving auto-null feature subtracts lead resistance from measurements, and stores it in memory even after powering down High resolution measurements down to 0.01 ohm for a high level of accuracy User selectable safety voltage level of 50 V or 25 V for varied environments Rotary knob labeling available in six versions. English, French, German, Italian, Spanish and a user-friendly symbols version Perform ground tests with aux- iliary earth spikes eliminating the need for multiple instru- ments (1653 only) Download up to 500 stored results with IR port and adapter for professional reporting (1653 only) Detachable leads for easy replacement EN-61557 and VDE 0413 compliant

Fluke 1653 Catalogue

Embed Size (px)

DESCRIPTION

Fluke

Citation preview

  • 1651B 1652B

    1653B

    Fluke 1650B SeriesMultifunction Installation Testers

    The installation testing solution for demanding environmentsThe Fluke 1650B Series testers, with new advanced features, are the perfect instal-lation testing tool for verifying the safety of electrical installations in domestic, com-mercial, and industrial applications. Ensure that fixed wiring is correctly installed and compliant with IEC 60364, HD 384 require-ments, and all relevant local standards. The 1650B Series is efficient to use by allowing

    the user to measure loop impedance with-out tripping RCDs, eliminating the need to bypass them. Slim reach probes allow you to keep your eyes on the panel while probing hard to reach areas. With easy-to-operate controls, a large display with a wide viewing angle, padded neck strap, and a compact, ergonomic design, these testers are com-fortable enough to use for all day testing.

    Extended Specifications

    Compact,lightweightandcom-fortabletowear

    Simpleoperationforfast,easytesting

    Fasthighcurrentlooptest(highcurrentmode)

    AdvancedlooptestingpreventsRCDsfromtripping

    VariableRCDcurrentmodeforcustomizedsettings

    Zeroadapterforeasytestleadcompensation

    ThePASS/FAILindicatortakestheguessworkoutofRCDtesting

    Insulationtestvoltages(1651:250V,500V,1000V),(1652:250V,500V,1000V),(1653:50V,100V,250V,500V,1000V)foravarietyofapplications

    SelectvoltagemeasurementquicklyandeasilybetweenL-N,L-PE,andN-PE

    Dualdisplaygivessimultaneousreadoutofmainsvoltageandfrequency

    Autodischargeallowsfastandsafedischargeofelectricalenergyincapacitivecircuits

    Addedsafetythroughlivecir-cuitdetection,tocheckandinhibittestifcircuitundertestislive

    Wiringconnectioncheckindi-cationandlivecircuitdetectionforaddedsafety

    Timesavingauto-nullfeaturesubtractsleadresistancefrommeasurements,andstoresitinmemoryevenafterpoweringdown

    Highresolutionmeasurementsdownto0.01ohmforahighlevelofaccuracy

    Userselectablesafetyvoltagelevelof50Vor25Vforvariedenvironments

    Rotaryknoblabelingavailableinsixversions.English,French,German,Italian,Spanishandauser-friendlysymbolsversion

    Performgroundtestswithaux-iliaryearthspikeseliminatingtheneedformultipleinstru-ments(1653only)

    Downloadupto500storedresultswithIRportandadapterforprofessionalreporting(1653only)

    Detachableleadsforeasyreplacement

    EN-61557andVDE0413compliant

  • Measurement Function 1651B 1652B 1653B Voltage&Frequency Wiringpolaritychecker InsulationResistance Continuity&Resistance Loop&LineResistance ProspectiveEarthFaultCurrent(PEFC/IK)ProspectiveShort-Circuitcurrent(PSC/IK)

    RCDswitchingtime RCDtrippinglevel ramptest ramptestRCDvariablecurrent AutomaticRCDtestsequence TestpulsecurrentsensitiveRCDs(TypeA) EarthResistance PhaseSequenceIndicator

    Other Features Self-test IlluminatedDisplay

    Memory, Interface Memory ComputerInterface Timeanddate(WhenusedwithFlukeViewsoftware) Software Optional

    Included Accessories Hardcase Remotecontrolprobe[1] ZeroAdapter Note[1]Includedwithall165XBversionsexcept1651BUKVersion.

    Specifications

    Specification Characteristic Size 10cm(L)x25cm(W)x12.5cm(H)Weight(withbatteries) 1.5kgBatterysize,quantity TypeAA,6ea.Batterytype Alkalinesupplied.Usablewith1.2VNiCdorNiMHbatteries(not

    supplied)Batterylife(typical) 200hoursidlingFuse T3.15A,500V,1.5kA6.3x32mm(PN2030852)OperatingTemperature -10Cto40CStorageTemperature -10Cto60Cindefinitely(to-40Cfor100hrs)RelativeHumidity Noncondensing

  • Electrical Measurement SpecificationsTheaccuracyspecificationisdefinedas(%reading+digitcounts)at23C5C,80%RH.Between-10Cand18Candbetween28Cand40C,accuracyspecificationsmaydegradeby0,1x(accuracyspecification)perC.Thefollowingtablescanbeusedforthedeterminationofmaximumorminimumdisplayvaluesconsideringmaximuminstrumentoperatinguncer-taintyperEN61557-1,5.2.4.

    Insulation Resistance (RISO)

    50 V 100 V 250 V 500 V 1000 V

    Lim

    it V

    alue

    Max

    imum

    D

    ispl

    ay V

    alue

    Lim

    it V

    alue

    Max

    imum

    D

    ispl

    ay V

    alue

    Lim

    it V

    alue

    Max

    imum

    D

    ispl

    ay V

    alue

    Lim

    it V

    alue

    Max

    imum

    D

    ispl

    ay V

    alue

    Lim

    it V

    alue

    Max

    imum

    D

    ispl

    ay V

    alue

    1 1.12 1 1.12 1 1.3 1 1.3 1 1.32 2.22 2 2.22 2 2.4 2 2.4 2 2.43 3.32 3 3.32 3 3.5 3 3.5 3 3.54 4.42 4 4.42 4 4.6 4 4.6 4 4.65 5.52 5 5.52 5 5.7 5 5.7 5 5.76 6.62 6 6.62 6 6.8 6 6.8 6 6.87 7.72 7 7.72 7 7.9 7 7.9 7 7.98 8.82 8 8.82 8 9.0 8 9.0 8 9.09 9.92 9 9.92 9 10.1 9 10.1 9 10.110 11.02 10 11.02 10 11.2 10 11.2 10 11.220 22.02 20 22.02 20 22.2 20 22.2 20 22.230 33.02 30 33.2 30 33.2 30 33.2 30 33.240 44.02 40 44.2 40 44.2 40 44.2 40 44.250 55.02 50 55.2 50 55.2 50 55.2 50 55.2

    60 66.2 60 66.2 60 66.2 60 66.2

    70 77.2 70 77.2 70 77.2 70 77.2

    80 88.2 80 88.2 80 88.2 80 88.2

    90 99.2 90 99.2 90 99.2 90 99.2

    100 110.2 100 110.2 100 110.2 100 110.2

    200 220.2 200 220.2 200 220.2

    300 347 300 345400 462 400 460

    500 577 500 575

    600 690

    700 805

    800 920

    900 1035

    1000 1150

    3FlukeCorporationFluke1650BSeriesMultifunctionInstallationTesters

  • Continuity (RLO)

    Loop Tests (ZI)

    Limit Value Maximum Display Value 0.2 0.160.3 0.250.4 0.340.5 0.430.6 0.520.7 0.610.8 0.70.9 0.791 0.882 1.783 2.684 3.585 4.486 5.387 6.288 7.189 8.0810 8.9820 17.9830 26.8

    Loop ZI Hi Current Loop ZI No Trip Loop ZI Loop RE

    Limit Value Maximum Display Value

    Limit Value Maximum Display Value

    Limit Value Maximum Display Value

    Limit Value Maximum Display Value

    0.20 0.14 - - 3 2.53 3 2.720.30 0.23 - - 4 3.38 4 3.620.40 0.32 0.40 0.28 5 4.23 5 4.520.50 0.41 0.50 0.37 6 5.08 6 5.420.60 0.50 0.60 0.45 7 5.93 7 6.320.70 0.59 0.70 0.54 8 6.78 8 7.220.80 0.68 0.80 0.62 9 7.63 9 8.120.90 0.77 0.90 0.71 10 8.48 10 9.021.00 0.86 1.00 0.79 20 16.98 20 18.021.10 0.95 1.10 0.88 30 25.3 30 27.21.20 1.04 1.20 0.96 40 33.8 40 36.21.30 1.13 1.30 1.05 50 42.3 50 45.21.40 1.22 1.40 1.13 60 50.8 60 54.21.50 1.31 1.50 1.22 70 59.3 70 63.21.60 1.40 1.60 1.30 80 67.8 80 72.21.70 1.49 1.70 1.39 90 76.3 90 81.21.80 1.58 1.80 1.47 100 84.8 100 90.21.90 1.67 1.90 1.56 200 169.8 200 180.22.00 1.76 2.00 1.64 300 253 300 272- - - - 400 338 400 362- - - - 500 423 500 452- - - - 600 508 600 542- - - - 700 593 700 632- - - - 800 678 800 722- - - - 900 763 900 812- - - - 1000 848 1000 902

    4FlukeCorporationFluke1650BSeriesMultifunctionInstallationTesters

  • RCD/FI Tests (T, IN)

    Earth Tests (RE)

    RCD/FI Time RCD/FI Current

    Limit Value Maximum Display

    Value Limit Value

    Maximum Display Value

    20 18.1 0.5 0.4330 27.1 0.6 0.5240 36.1 0.7 0.6150 45.1 0.8 0.760 54.1 0.9 0.7970 63.1 1 0.8880 72.1 2 1.7890 81.1 3 2.68100 90.1 4 3.58200 180.1 5 4.48300 271 6 5.38400 361 7 6.28500 451 8 7.18600 541 9 8.08700 631 10 8.98800 721 20 17.98900 811 30 26.81000 901 40 35.82000 1801 50 44.8

    60 53.8

    70 62.8

    80 71.8

    90 80.8

    100 89.8

    200 179.8

    300 268

    400 358

    500 448

    Limit Value Maximum Display Value 10 8.820 17.830 26.840 35.850 44.860 53.870 62.880 71.890 80.8100 89.8200 179.8300 268.0400 358.0500 448.0600 538.0700 628.0800 718.0900 808.01000 898.02000 1798.0

    5FlukeCorporationFluke1650BSeriesMultifunctionInstallationTesters

  • Range Resolution Accuracy

    50Hz - 60Hz Input Impedance

    Overload Protection

    500V 0.1V 0.8%+3 3.3M 660Vrms

    AC Voltage Measurement (V)

    Continuity Testing (RLO)

    Insulation Resistance Measurement (RISO)

    Range (Autoranging) Resolution Open Circuit Voltage Accuracy 20 0.01 >4V (1.5%+3digits)200 0.1 >4V (1.5%+3digits)2000 1 >4V (1.5%+3digits)

    NoteThenumberofpossiblecontinuitytestswithafreshsetofbatteriesis3000.

    Range RLO Test Current 7.5 210mA35 100mA240 20mA2000 2mA

    Test Probe Zeroing Pressthe tozerothetestprobe.Cansubtractupto2ofleadresistance.Errormessagefor>2.

    Live Circuit Detection Inhibitstestifterminalvoltage>10Vacdetectedpriortoinitiationoftest.

    Test Voltages Accuracy of Test Voltage (at rated test

    current) Model 1651B Model 1652B Model 1653B

    250-500-1000V 250-500-1000V 50-100-250-500-1000V +10%,-0%

    Test Voltage Insulation Resistance

    Range Resolution Test Current Accuracy

    50V 10kto50M 0.01M 1mA@50k (3%+3digits)

    100V100kto20M 0.01M

    1mA@100k (3%+3digits)20Mto100M 0.1M (3%+3digits)

    250V10kto20M 0.01M

    1mA@250k (1.5%+3digits)20Mto200M 0.1M (1.5%+3digits)

    500V10kto20M 0.01M

    1mA@500k(1.5%+3digits)

    20Mto200M 0.1M (1.5%+3digits)200Mto500M 1M 10%

    1000V100kto200M 0.1M

    1mA@1M (1.5%+3digits)200Mto1000M 1M 10%

    NoteThenumberofpossibleinsulationtestswithafreshsetofbatteriesis2000.

    Auto Discharge Dischargetimeconstant30Vpriortoinitiationoftest.Maximum Capacitive Load: Operablewithupthe5Fload.

    6FlukeCorporationFluke1650BSeriesMultifunctionInstallationTesters

  • 7FlukeCorporationFluke1650BSeriesMultifunctionInstallationTesters

    Loop and Line Impedance (ZI)No Trip and Hi Current Modes RCD/FI

    Prospective Earth Fault Current Test (PSC/IK)

    RCD Testing RCD Types Tested

    Test Signals

    Mains Input Voltage Range 100-500Vac(50/60Hz)Input Connection (soft key selection)

    LoopImpedance:phasetoearthLineimpedance:phasetoneutral

    Limit on Consecutive Tests Automaticshutdownwheninternalcomponentsaretoohot.ThereisalsoathermalshutdownforRCDtests.

    Maximum Test Current @ 400 V 20Asinusoidalfor10msMaximum Test Current @ 230 V 12Asinusoidalfor10ms

    Range Resolution Accuracy*

    20 0.01 NoTripmode:(3%+6digits)HiCurrentmode:(2%4digits)

    200 0.1 NoTripmode:(3%)HiCurrentmode:(2%)2000 1 6%**Notes* Validforresistanceofneutralcircuit200V.

    Computation ProspectiveEarthFaultCurrent(PEFC/IK)orProspectiveShortCircuitCurrent(PSC/IK)determinedbydividingmeasuredmainsvoltagebymeasuredloop(L-PE)resistanceorline(L-N)resistance,respectively.

    Range 0to10kAor0to50kA(SeePower-OnOptionsearlierinthismanual)Resolution and Units Resolution Units

    IK1000A 0.1kA

    Accuracy Determinedbyaccuracyofloopresistanceandmainsvoltagemeasurements.

    RCD Type* Model 1651B Model 1652B Model 1653B AC1 G2 AC S3 A4 G A S

    Notes1ACRespondstoAC2GGeneral,nodelay3STimedelay4ARespondstopulsedsignal*RCDtestinhibitedforV>265acRCDtestspermittedonlyifselectedcurrentxearthingresistanceis

  • 8FlukeCorporationFluke1650BSeriesMultifunctionInstallationTesters

    Tripping Speed Test (T)

    Maximum Trip TimeTheRCDsymbolswitchesonwhentestingtheRCDtriptimeifthetriptimemeetsthefollowingconditions:

    RCD/FI-Tripping Current Measurement/Ramp Test (IN)Models1652Band1653B

    Earth Resistance Test (RE) Model1653BOnly.Thisproductisintendedtobeusedtomeasureinstallationsinprocessplants,industrialinstallations,andresidentialapplications.

    Current Settings[1] Multiplier Current Accuracy 10301003005001000mA-VAR x1/2 +0%,-10%oftestcurrent10301003005001000mA-VAR x1 +10%,-0%1030100mA x5 +10%,-0%Note[1]1000mAtypeAConly.700mAmaximumtypeAinVARmode.

    Current Multiplier *RCD Type Measurement Range

    Trip Time Accuracy Europe UKx1/2 G 310ms 2000ms (1%Reading+1ms)x1/2 S 510ms 2000ms (1%Reading+1ms)x1 G 310ms 310ms (1%Reading+1ms)x1 S 510ms 510ms (1%Reading+1ms)x5 G 50ms 50ms (1%Reading+1ms)x5 S 160ms 160ms (1%Reading+1ms)Notes*GGeneral,nodelay*STimedelay

    RCD I N Trip time limitsAC,G x1 Lessthan300msAC,G-Stype x1 Between130msand500msA x1 Lessthan300msA-Stype x1 Between130msand500msAC,G x5 Lessthan40msAC,G-Stype x5 Between50msand150msA x5 Lessthan40msA-Stype x5 Between50msand150ms

    Current Range Step Size Dwell Time Measurement

    Accuracy Type G Type S*30%to110%ofRCDratedcurrent

    10%ofIN 300ms/step 500ms/step 5%

    Note30%to150%forTypeAIN>10mA,30%to210%forTypeAIN=10mASpecifiedtripcurrentrange:50%to100%forTypeAC,35%to140%forTypeA(>10mA),35%to200%forTypeA(10mA)

    Range Resolution Accuracy 200 0.1 (2%+5digits)2000 1 (3.5%+10digits)

    Range: RE + RPROBE Test Current 160 50mA1600 5mA16000 500A52000 150A

    Frequency Output Voltage128Hz 25V

    Live Circuit Detection Inhibitstestifterminalvoltage>10Vacisdetectedpriortostartoftest.

  • Phase Sequence IndicationModel1653BOnly

    Mains Wiring TestIcons( )indicateifL-PEorL-Nterminalsarereversed.Instrumentoperationisinhib-itedandanerrorcodeisgeneratediftheinputvoltageisnotbetween100Vand500V.TheUKLoopandRCDtestsareinhibitediftheL-PEortheL-Nterminalsarereversed.

    Operating Ranges and Uncertainties per EN 61557

    Icon iconPhaseSequenceindicatorisactive.Display of Phase Sequence Displays1-2-3indigitaldisplayfieldforcorrect

    sequence.Displays3-2-1forincorrectphase.Dashesinplaceofanumberindicateavaliddeterminationcouldnotbemade.

    Mains Input Voltage Range (phase-to phase) 100to500V

    Function Display Range EN 61557 Measurement

    Range Operating Uncertainty

    Nominal Values

    VEN61557-1 0.0Vac500Vac 50Vac500Vac(2%+2dgt)UN=230/400Vacf=50/60Hz

    RLOEN61557-4 0.00-2000 0.2-2000(10%+2dgt)4.0Vdc24VdcRLO2.00IN200mA

    RISOEN61557-2 0.00M-1000M1M-200M(10%+2dgt)200M-1000M(15%+2dgt)

    UN=50/100/250/500/1000VdcIN=1.0mA

    ZIEN61557-3

    ZI0.00-2000

    2-1000(15%+2dgt)

    UN=230/400Vacf=50/60HzIK=0A10.0kA

    ZI(NoTrip)0.00-2000

    0.4-2(15%+6dgt)

    ZI(HiCurrent)0.00-2000

    0.2-2(10%+4dgt)

    RE0.00-2000

    10-1000(10%+2dgt)

    T,INEN61557-6

    T0.0ms2000ms 25ms2000ms(10%+1dgt)T=10/30/100/300/500/1000mA

    IN0.5mA550mA 0.5mA550mA(10%+1dgt)IN=10/30/100/300/500mA

    REEN61557-5 0.0-2000 10-2000(10%+2dgt) f=128Hz

    PhaseEN61557-7 1:2:3

    9FlukeCorporationFluke1650BSeriesMultifunctionInstallationTesters

  • Influence Quantity

    Volt

    s

    RLo

    EN

    615

    57-4

    RIS

    O

    EN

    615

    57-2

    Z I

    EN

    615

    57-3

    TE

    N 6

    1557

    -6

    IN

    EN

    615

    57-6

    RE

    EN

    615

    57-5

    E1-Position 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00%E2-SupplyVoltage 0.50% 3.00% 3.00% 3.00% 3.00% 2.75% 2.25%E3-Temperature 0.50% 3.00% 3.00% 3.00% 3.00% 2.25% 2.75%E4-SeriesInterferencesVoltage - - - - - - 1.50%E5-Resistanceoftheprobesandauxiliaryearthelectrodes - - - - - - 4.00%

    E6.2-Systemphaseangle - - - 1.00% - - -E7-Systemfrequency 0.50% - - 2.50% - - 0.00%E8-Systemvoltage - - - 2.50% 2.50% 2.50% 0.00%E9-Harmonics - - - 2.00% - - -E10-D.C.Quantity - - - 2.50% - - -

    Fluke CorporationPOBox9090,Everett,WA98206U.S.A.

    Fluke Europe B.V.POBox1186,5602BDEindhoven,TheNetherlands

    For more information call:IntheU.S.A.(800)443-5853orFax(425)446-5116InEurope/M-East/Africa+31(0)402675200orFax+31(0)402675222InCanada(800)-36-FLUKEorFax(905)890-6866Fromothercountries+1(425)446-5500orFax+1(425)446-5116Webaccess:http://www.fluke.com

    2008FlukeCorporation.Specificationssubjecttochangewithoutnotice.PrintedinU.S.A.11/20083367586D-EN-NRevAPub_ID:11518-eng

    Modification of this document is not permitted without written permission from Fluke Corporation.

    Fluke. Keeping your world up and running.

    10FlukeCorporationFluke1650BSeriesMultifunctionInstallationTesters

    Ordering information

    1653B MultifunctionInstallationTester

    1652B MultifunctionInstallationTester

    1651B MultifunctionInstallationTester

    Optional accessoriesMTC1363MainsTestCordMTC77MainsTestCordES165XEarthSpikeTestKit(1653only)

    FVF-SC2FlukeViewSoftware(1653only)

    Included with 1650B:TP165XRemoteControlProbe(1652Band1653Bonly)TL165/UKFusedtestleadsetTD07FPARTPtestcertificates(1651Bonly)C1600HardCarryingCaseMainstestcordZeroadapterPaddedcarryingstrapQuickreferenceguide6AAbatteries

    Operating Uncertainties per EN 61557 TheOperatingUncertaintyshowsthemaximumpossibleuncertaintywhenallinfluencefactorsE1-E10arecounted.

    Volt

    s

    RLo

    EN

    615

    57-4

    RIS

    O

    EN

    615

    57-2

    Z I

    EN

    615

    57-3

    TE

    N 6

    1557

    -6

    IN

    EN

    615

    57-6

    RE

    EN

    615

    57-5

    IntrinsicUncertaintyA 0.80% 1.50% 10.00% 6.00% 1.00% 5.00% 3.50%