FLUX를활용한몰드변압기의전기적손실계산과열해석을통한 Hot-spot 확인
산일전기김선영선임연구원
Finding hotspot of Molded transformer through the electric losses and thermal analysis
목적및모델선정
TECHNICAL DATA
No. of phase (Ph) 3
Rated power (kVA) 7,000
Rated frequency (Hz) 60
Rated Voltage (No-load)
Pri.Winding (V) 11,000
Sec.Winding (V) 2 x 1,850
Winding material Pri.Winding Aluminum
Sec.Winding Aluminum
▪ 해석대상변압기사양
▪ 목적
➢ 코일외에주변도체의전기적손실계산필요
➢ 변압기개발시온도특성검토필요
해석과정
FLUX 2D (자계)winding eddy current
FLUX 3D (자계)structure
Acusolve(CFD)Convection coefficient
FLUX(열계)Hot-spot 확인
전기적손실합계
Heated Air Outlets
Cooling Air Inlets
Joule Special Short Circuit
Losses
HV 13917 3111 17028
LV delta 10743 3897 14640
LV star 10683 3291 13974
Connections HV 159 1 160
Connections LV delta 280 38 318
Connections LV star 808 105 913
Steel 0 35 35
Tank 0 40 40
Total 36590 10518 47108
Enclosure
FLUX 2D(자계)-Eddy Current Losses analysis
Unit |W] JOULE EDDY
HV LOSSES 1 296 194
HV LOSSES 2 296 70
HV LOSSES 3 303 31
HV LOSSES 4 239 17
HV LOSSES 5 249 25
HV LOSSES 6 312 41
HV LOSSES 7 312 34
HV LOSSES 8 312 105
HV TOP TOTAL 2320 518
HV LOSSES 8 312 105
HV LOSSES 7 312 35
HV LOSSES 6 312 41
HV LOSSES 5 249 25
HV LOSSES 4 239 17
HV LOSSES 3 303 31
HV LOSSES 2 296 70
HV LOSSES 1 296 195
HV BOTTOM TOTAL 2320 519
LV TOP TOTAL 3581 1299
LV BOTTOM TOTAL 3561 1097
HV 1Phase 5677
LV 1Phase 9538
1Phase Tot. 15215
HV 3Phase 17031
LV 3Phase 28614
3Phase TOTAL 45645
▪ Current density in connection and structure [A/cm2]
JouleEddy current
losses
Short Circuit
Losses
Connections
HV159 1 160
Connections
LV delta280 38 318
Connections
LV star808 105 913
Steel 0 35 35
Tank 0 40 40
Total 1247 219 1466
FLUX 3D(자계)-Stray Losses analysis
Acusolve(CFD)-convection coefficient contours
Acusolve(CFD)-convection coefficient analysis
A Phase B Phase
1HV_top
Outer 23.55 16.67
Inner 59.51 59.16
2HV_bot
Outer 30.55 24.9
Inner 32.94 34.10
3LV_top
Outer 58.77 61.63
Inner 49.94 47.71
4LV_bot
Outer 32.65 34.48
Inner 45.57 42.39
[W/m2K]
FLUX 2D(열계) – Hot-spot Analysis
▪ AFWF type
Hot point
Winding Temperature
HV_top 78.0 ℃
HV_bottom 80.3 ℃
LV_top 73.5 ℃
LV_bottom 73.4 ℃
SUMMARY
▪ 전기적손실계산(Eddy current losses + Stray losses)
- FLUX2D를활용하여 axisymmetry model로권선도체각각의손실을계산하고 FLUX3D를활용하여부스바와코어지지
대, 탱크에서발생하는 stray loss를계산하였다.
Joule Special Short Circuit
Losses
2D eddy current losses
HV 13920 3111 17031
LV delta 10743 3897 14640
LV star 10683 3291 13974
3D stray losses
Connections HV 159 1 160
Connections LV delta 280 38 318
Connections LV star 808 105 913
Steel 0 35 35
Tank 0 40 40
Total 36593 10518 47111
▪ Hot-spot 확인(Winding losses + CFD + Thermal)
- FLUX2D 자계해석으로권선도체각각의단위면적당손실을계산하고 Acusolve를활용하여코일표면에발생하는대류
상수를계산하였다.
- FLUX2D 열계해석을사용하여자계해석으로얻은 Heat source와 CFD로얻은대류상수를사용하여코일내부의 hot-spot
이하부 HV코일에서 80℃의 최고온도를보이는것을확인하였다.