Data Sheet 11.26 Issue A Foam Concentrate Control Valve Rapidrop Limited Rutland Business Park, Newark Road, Peterborough, PE1 5WA, United Kingdom Tel: +44 (0) 1733 847 510 Fax: +44 (0) 1733 553 958 e-mail: [email protected] web: www.rapidrop.com © 2009 Rapidrop Rapidrop® is a registered trade mark. Rapidrop Limited Registered in England No. 4936424 Page 1 of 2 Continued Overleaf TECHNICAL D ATA : MODEL CV SIZE 40NB, 50NB, & 65NB RATED PRESSURE 14 Kg./sq.cm. (200 PSI) END CONNECTION Flanged end to ANSI B 16.5 Class 150# PRESSURE SENSING Teflon tube with stainless HOSE steel braided cover. TRIM CONNECTION Brass / S.S. FACTORY 25 Kg./sq.cm. (365 PSI) HYDROTESTED FINISH Epoxy Red Painted. ORDERING Please specify Model, Size INFORMATION of valve. APPLICATION Foam concentrate control valve is designed for use in bladder tank foam system or inline balance pressure proportioning system. The valve opens automatically when water supply is established through the inlet pipe of ratio controller of bladder tank or in the inline balance pressure proportioning system. The valve opens at minimum of 3 Kg. ( 42.8 psi ) water pressure. No electric power is required to operate the valve. SPECIFICATION The foam concentrate control valve utilizes water as the medium to open the valve. A manual override facility is provided to open the valve. In normal condition the valve remain in closed position. When, a minimum water pressure of 3 Kg./sq.cm. ( 42.8 psi ) is established the valve opens and closing of the valve is manual. INSPECTION AND MAINTENANCE A qualified and trained person must commission the system. After few initial successful tests, an authorised person must be trained to perform the inspection and testing of the system at lest once in a week. The inspection should verify that all the control valves are in their proper position as per the system requirement and no damage has taken place to any component. The foam concentrate control valve / system must be operated at least once in six weeks. The total system should be fully tested at lest once in a year as per NFPA / TAC manual or in accordance to the guidelines of the organisation having local jurisdiction. RD Proportioner Foam Concentrate Control Size Valve Size 80 NB 40NB 100 NB 40NB 150 NB 50NB 200 NB 65NB SELECTION OF FOAM CONCENTRATE CONTROL VALVE SRNO DESCRIPTION MATERIAL SPECIFICATION 1 Valve Stainless Steel 2 Pipe Stainless Steel 3 Cylinder Stainless Steel 4 Hose Stainless Steel 5 Flange Stainless Steel 5 1 4 3 2 5 SOLUTION INLET SOLUTION OUTLET CLOSED O P E N WATER PRESSURE SENSING FROM INLET SIDE OF RATIO CONTROLLER

Foam Concentrate Control Valve - Sariak Co. · PDF fileFoam Concentrate Control Valve Rapidrop Limited Rutland Business Park, ... ALARM WATER CONTROL VALVE ALARM BLADDER TANK RATI

  • Upload
    leanh

  • View
    233

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Foam Concentrate Control Valve - Sariak Co. · PDF fileFoam Concentrate Control Valve Rapidrop Limited Rutland Business Park, ... ALARM WATER CONTROL VALVE ALARM BLADDER TANK RATI

Data Sheet 11.26Issue A

Foam Concentrate Control Valve

Rapidrop LimitedRutland Business Park, Newark Road, Peterborough, PE1 5WA, United Kingdom

Tel: +44 (0) 1733 847 510 Fax: +44 (0) 1733 553 958e-mail: [email protected] web: www.rapidrop.com

© 2009 RapidropRapidrop® is a registered trade mark.Rapidrop LimitedRegistered in England No. 4936424 Page 1 of 2

Continued Overleaf

TECHNICAL DATA :

MODEL CV

SIZE 40NB, 50NB, & 65NB

RATED PRESSURE 14 Kg./sq.cm. (200 PSI)

END CONNECTION Flanged end to ANSI B 16.5Class 150#

PRESSURE SENSING Teflon tube with stainlessHOSE steel braided cover.

TRIM CONNECTION Brass / S.S.

FACTORY 25 Kg./sq.cm. (365 PSI)HYDROTESTED

FINISH Epoxy Red Painted.

ORDERING Please specify Model, SizeINFORMATION of valve.

APPLICATIONFoam concentrate control valve is designed for use inbladder tank foam system or inline balance pressureproportioning system. The valve opens automaticallywhen water supply is established through the inlet pipeof ratio controller of bladder tank or in the inlinebalance pressure proportioning system. The valveopens at minimum of 3 Kg. ( 42.8 psi ) water pressure.No electric power is required to operate the valve.

SPECIFICATIONThe foam concentrate control valve utilizes water asthe medium to open the valve. A manual override facilityis provided to open the valve. In normal condition thevalve remain in closed position. When, a minimum waterpressure of 3 Kg./sq.cm. ( 42.8 psi ) is established thevalve opens and closing of the valve is manual.

INSPECTION AND MAINTENANCEA qualified and trained person must commission thesystem. After few initial successful tests, anauthorised person must be trained to perform theinspection and testing of the system at lest once in aweek. The inspection should verify that all the controlvalves are in their proper position as per the systemrequirement and no damage has taken place to anycomponent. The foam concentrate control valve /system must be operated at least once in six weeks.The total system should be fully tested at lest once ina year as per NFPA / TAC manual or in accordance tothe guidelines of the organisation having localjurisdiction.

RD Proportioner Foam Concentrate ControlSize Valve Size

80 NB 40NB

100 NB 40NB

150 NB 50NB

200 NB 65NB

SELECTION OF FOAM CONCENTRATE CONTROL VALVE

SRNO DESCRIPTION MATERIAL SPECIFICATION1 Valve Stainless Steel2 Pipe Stainless Steel3 Cylinder Stainless Steel4 Hose Stainless Steel5 Flange Stainless Steel

5

1

4

3

2

5

SOLUTION INLET

SOLUTIONOUTLET

CLOSE

D

OPE

N

WATER PRESSURE SENSING FROM INLET SIDE OFRATIO CONTROLLER

Page 2: Foam Concentrate Control Valve - Sariak Co. · PDF fileFoam Concentrate Control Valve Rapidrop Limited Rutland Business Park, ... ALARM WATER CONTROL VALVE ALARM BLADDER TANK RATI

Data Sheet 11.26Issue A

Foam Concentrate Control Valve

Rapidrop LimitedRutland Business Park, Newark Road, Peterborough, PE1 5WA, United Kingdom

Tel: +44 (0) 1733 847 510 Fax: +44 (0) 1733 553 958e-mail: [email protected] web: www.rapidrop.com

© 2009 RapidropRapidrop® is a registered trade mark.Rapidrop LimitedRegistered in England No. 4936424

Page 2 of 2

TYPICAL INSTALLATION OF FOAM CONCENTRATE CONTROL VALVE

ETA

RTN

EC

NO

C M

AOF

RET

AW

FOAM CONCENTRATE CONTROL VALVE

WATER INLET

SWINGCHECK VALVE

NETWORKTO SPRINKLER

SPRINKLERALARM

WATERCONTROL

VALVE

ALARM

BLADDER TANK

RATIOCONTROLLER

VALVE

WATER INLET

ETA

RTN

EC

NO

C M

AOF

WATER

CONTROL VALVEFOAM CONCENTRATE

FOAM SOLUTION OUTLET

BLADDER TANK

RATIO CONTROLLER

DELUGEVALVE

LIMITED WARRANTYProducts supplied by RAPIDROP.LTD.. are warranted against defects in material and workmanship for a period of Two (2) years from the date of shipment.RD's obligation under this warranty is limited to replace or repair the products or its parts, which are shown to RD's examination to be in a defective conditionattributable to RD. No warranty is given for products or components which have been subject, to misuse, improper installation, corrosion, wear and tear,improper storage, modification or repaired. If the defect attributable to RD cannot be rectified by repair or replacement, then RD may elect to refund thepurchase price of the equipment in complete discharge of its obligation under this Limited Warranty.

IN NO EVENT SHALL RAPIDROP. LTD. BE LIABLE IN CONTRACT, STRICT LIABILITY OR ANY OTHER LEGAL THEORY, FOR INCIDENTAL, IN-DIRECT, SPECIAL ORCONSEQUENTIAL DAMAGES, INCLUDING DAMAGES. FOR INJURY TO PERSON OR DEATH OR DAMAGE TO PROPERTY AND OR PENALTIES RESULTING FROM ANY PRODUCTS OR COMPONENT MANUFACTURED OR ASSEMBLED BY RD. THIS IS LIMITED WARRANTY ONLY. RD DISCLAIMS WITH RESPECT TO THE PRODUCTS ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND ALL IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE. THERE IS NO WARRANTY OF ANY NATURE MADE BY RD BEYOND AS STATED ABOVE.

NOTICE :The equipment presented in this bulletin is to be installed in accordance with the latest publication standards of NFPA or other similar organisations and alsowith the provision of government codes or ordinances wherever applicable. The information provided by us are to the best of our knowledge and belief, and are general guidelines only. Site handling and installation control is beyond ourreach. Hence we give no guarantee for result and take no liability for damages, loss or penalties whatsoever, resulting from our suggestion, information,recommendation or damages due to our product.Product development is a continuous programme of RAPIDROP. LTD. and hence the right to modify any specification without prior notice is reservedwith the company.