Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
Iowa Electric Light and Power Company
October 17, 1980 LDR-80-284
Mr. James G. Keppler, Director Office of Inspection and Enforcement Region III U.S. Nuclear Regulatory Commission 799 Roosevelt Road ien Ellyn, IL 60137
Dear Mr. Keppler:
This letter and enclosure are Iowa Electric Light and Power Company's final response to IE Bulletin No. 79-14 concerning seismic analyses for as-built safety-related piping systems.
Your recent Bulletins have requested cost information. As a result of Bulletin 79-14, Iowa Electric expended approximately three million dollars in preparation of the report and corrective action.
Very truly yours
Larry D. Root Assistant Vice President Nuclear Generation
LDR/lb cc: w/o
R. Salmon D. Arnold L. Liu S. Tuthill K. Meyer w/a D. Mineck J. Van Sickel K. Eccleston (NRC) NRC Resident Office W/ File: A-101a, BN 79-14 Director Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C. 20555 Director Division of Operating Reactors U.S. Nuclear Regulatory Commission Washington, D.C. 20555
7~ ZV-0Demont 9 W..7
/
(;I1ItralIflcqi * MN. lih.\ .1.51 - U~fl ir u~ Iov%.i 5:!40(; * 319/31%441
LAR9\ D HOOT
v i ( FAR iJ b i wivr
FINAL REPORT
SEISMIC ANALYSIS OF
AS-BUILT SAFETY-RELATED PIPING SYSTEMS FOR
DUANE ARNOLD ENERGY CENTER IOWA ELECTRIC LIGHT AND POWER COMPANY
1.0 INTRODUCTION
U.S. NRC IE Bulletin 79-14, Seismic Analysis for As-Built Safety-Related Piping Systems, was issued on July 2, 1979, revised on July 18, 1979, and supplemented on August 15, 1979, and September 7, 1979.
The bulletin requested licensees to take certain actions to verify that seismic analyses are applicable to as-built plants.
This is a final report and contains the actions taken and the results of those actions.
2.0 ACTIONS TO BE TAKEN BY LICENSEES AND PERMIT HOLDERS
All power reactor facility licensees and construction permit holders are requested to verify, unless verified to an equivalent degree within the last 12 months, that the seismic analysis applies to the actual configuration of safety-related piping systems. The safetyrelated piping includes Seismic Category I systems as defined by Regulatory Guide 1.29, Seismic Design Classification, Revision 1, dated August 1, 1973, or as defined in the applicable FSAR. The action items that follow apply to all safety-related piping 2-1/2 inches in diameter and greater and to Seismic Category I piping, regardless of size, which was dynamically analyzed by computer. For older plants, where Seismic Category I requirements did not exist at the time of licensing, it must be shown that the actual configuration of safety-related systems utilizing piping 2-1/2 inches in diameter and greater meets design requirements.
2.1 SPECIFICS
Specifically, each licensee was requested to perform the following tasks:
2.1.1 Item 1
a. Identify inspection elements to be used in verifying that the seismic analysis input information conforms to the actual configuration of safety-related systems.
Response: Attachment 1, Procedure for Verifying Conformance of Seismic Analysis to Actual Configuration of Safety-Related Piping Systems in Response to IE Bulletin 79-14, identifies the inspection elements used.
b. For each safety-related system, submit a list of design documents, including title, identification number, revision, and date, which were sources of input information for the seismic analyses.
Response: Attachment 2 lists the design documents for each safety-related system.
c. Also submit a description of the seismic analysis input information which is contained in each document.
Response: Attachment 1 (Sections III through IX) describes the input information.
d. Identify systems or portions of systems which are planned to be inspected during each sequential inspection identified in Items 2 and 3 (Sections 2.1.2 and 2.1.3, respectively).
Response: Attachment 4, Results of Inspection,identifies the systems which were inspected and the inspection group in which each system was inspected.
2.1.2 Item 2
For portions of systems which are normally accessible*, inspect one system in each set of redundant systems and all nonredundant systems for conformance to the seismic analysis input information set forth in design documents. In the inspection, include pipe run geometry; support and restraint design, locations, function, and clearance (including floor and wall penetration); embedments (excluding those covered in IE Bulletin 79-02); pipe attachments; and valve and valve operator locations and weights (excluding those covered in IE Bulletin 79-04). Within 60 days of the date of this bulletin, submit a description of the results of this inspection. Where nonconformances are found which affect operability of any system, the licensee will expedite completion of the inspection described in Item 3.
*Note: "Normally accessible" refers to those areas of the plant which can be entered during reactor operation.
Response: See the response to Item 3.
2.1.3 Item 3
In accordance with Item 2, inspect all other normally accessible safety-related systems and all normally inaccessible safetyrelated systems. Within 120 days of the date of this bulletin, submit a description of the results of this inspection.
Response to Items 2 and 3: The inspections described in Bulletin 79-14, Items 2 and 3 were conducted for Iowa Electric Light and Power by Bechtel Associates Professional Corporation of Ann Arbor, Michigan, using its Procedure for Verifying Conformance of Seismic Analysis to Actual Configuration of Safety-Related Piping Systems. (Revision 3 of this procedure is Attachment 1 to this report.)
The inspection reported herein is specifically addressed by Sections III through IX of the procedure. The field inspection was conducted at the Duane Arnold Energy Center. The comparison addressed in Section VIII was performed at Bechtel's Ann Arbor office. The responses for normally accessible lines were submitted via Letters LDR-79-177 dated August 31, 1979, and LDR-79-274 dated October 30, 1979. Normally inaccessible lines were inspected during the February, March, and April 1980 refueling outage. The results of all ihspections and comparisons are tabulated in Attachment 4, Results of Inspection.
In summary, inspection groups are classified as follows:
a. Inspection Group 1 lines include all accessible portions of nonredundant systems and accessible portions of one of two nonredundant systems.
b. Inspection Group 2 lines include accessible portions of redundant systems not included in Group 1.
c. Inspection Group 3 lines include all inaccessible piping. (A chilled water line was covered completely by a metal box enclosure and was not inspected.)
d. Computer-analyzed safety-related small pipe was inspected along with Group 3 lines.
2.1.4 Item 4
If nonconformances are identified:
a. Evaluate the effect of the nonconformance upon system operability under specified earthquake loadings and comply with applicable action statements in your technical specifications, including prompt reporting.
b. Submit an evaluation of identified nonconformances on the validity of piping and support analyses as described in the Final Safety Analysis Report (FSAR) or other NRC-approved documents. Where you determine that reanalysis is necessary, submit your schedule for 1) completing the reanalysis, 2) comparisons of the results to the FSAR or other NRC-approved acceptance criteria, and 3) submitting descriptions of the results of reanalysis.
c. In lieu of Item b, submit a schedule for correcting nonconforming systems so they conform to the design documents. Also, submit a description of the work required to establish conformance.
d. Revise documents to reflect the as-built conditions in the plant, and describe measures which are in effect which provide assurance that future modifications of piping systems, including their supports, will be reflected in a timely manner in design documents and the seismic analysis.
Response to Item 4: The results tabulated in Attachment 4 show that no nonconformances exist.
ATTACHMENTS
1. Procedure for Verifying Conformance of Seismic Analysis to Actual Configuration of Safety-Related Piping Systems in Response to IE Bulletin 79-14, Revision 3.
2. Listing of Design Documents for Seismic Analysis of Lines in Various Inspection Groups
a. Group 1 Lines
b. Group 2 Lines
c. Group 3 Lines
d. Computer-Analyzed Safety-Related Small Pipe
3. Seismic Category I Systems, Associated Piping Line Numbers, and Inspection Group
(This list, included in the previously submitted response for normally accessible lines, is omitted from this response. Attachment 4 lists all lines inspected.)
4. Results of Inspection
a. Group 1 Lines
b. Group 2 Lines
c. Group 3 Lines
d. Computer-Analyzed Safety-Related Small Pipe
Attachment 1
PROCEDURE
FOR
VERIFYING CONFORMANCE OF SEISMIC
ANALYSIS TO ACTUAL CONFIGURATION
OF SAFETY-RELATED PIPING SYSTEMS IN
RESPONSE TO IE BULLETIN 79-14
FOR
DUANE ARNOLD ENERGY CENTER UNIT 1
IOWA ELECTRIC LIGHT AND POWER COMPANY
CEDAR RAPIDS, IOWA
BY
BECHTEL ASSOCIATES PROFESSIONAL CORPORATION
ANN ARBOR, MICHIGAN
REV. 2
APPROVED BY
DATE
REV. 3 B. APPROVED BY
DATE_ J-/ </81,
REV. 0
APPROVED BY> /
DATE
REV. 1
APPROVED BY <_ 6 -e DATE 6 I-/- -?
TABLE OF CONTENTS
I. PURPOSE
II. GENERAL DISCUSSION
III. IDENTIFYING SAFETY-RELATED LINES
IV. INSPECTION PLAN
V. DEVELOP AS-BUILT INSPECTION DOCUMENTS
VI. DEVELOP AS-DESIGNED DOCUMENTS
VII. FIELD INSPECTION
VIII. COMPARISON OF THE AS-BUILT AND AS-DESIGNED CONFIGURATIONS
IX. EVALUATION OF DISCREPANCIES
ATTACHMENTS
1 Piping System Walkdown Data Sheet
2 Piping System Design Conformance Data Sheet
3 Spool Checklist
4 Piping System Nonconformance Resolution Sheet
I. PURPOSE
This procedure describes the method and steps to be taken to verify that the seismic analyses of safety-related piping systems conform to the actual configurations of the installed piping systems at Duane Arnold Energy Center (DAEC). The procedure is intended to be responsive to the requirements of NRC IE Bulletin 79-14 dated July 2, 1979.
II. GENERAL DISCUSSION
This section describes the overall approach to be taken to provide the verification that the seismic analyses performed conform to the actual configuration of the piping systems installed. The general steps are listed below and the detailed description of procedures required to accomplish each step are provided in subsequent sections.
A. Identify all 2-1/2-inch and larger piping and all 2-inch and smaller piping lines which were computer-analyzed and safetyrelated.
B. Separate these lines into four inspection groups:
1. Inspection Group 1 lines include all accessible portions of nonredundant systems and accessible portions of one of two redundant system
2. Inspection Group 2 lines include accessible portions of redundant systems not included in Group 1 lines.
3. Inspection Group 3 lines include all inaccessible lines.
4. Computer-analyzed, safety-related small pipe
C. Develop as-built inspection documents for the field surveys of the piping systems. The inspection documents are to contain all information required to be verified by the field inspection.
D. Develop as-designed documents which reflect the piping configuration which was used as input to the seismic analysis.
E. Perform field inspection of actual piping system configurations using the as-built inspection documents described above. Document any deviations from the inspection documents as a result of the inspection.
F. Compare the verified as-built documents with the completed as-designed documents for agreement with the seismic analysis input.
G. Evaluate the significance of any discrepancies between the verified as-built documents and the as-designed documents.
H. Evaluate the results of the field inspections and any reanalyses to determine whether verification inspections beyond the initial phase are warranted.
III. IDENTIFY SAFETY-RELATED LINES
To identify the safety-related piping lines 2-1/2 inches and larger which have been seismically analyzed, use the DAEC Piping Summary Sheets, Drawing M-190 (current revision). The seismic classification of each line is noted in the summary sheets. Use applicable piping and instrument diagrams (P&IDs) to identify computer-analyzed, safety-related small piping. Where the small pipe is not identified by line number or the P&IDs, assign a 500 series line number to line. Once identified, a list of all Seismic Category I (SCI) lines is to be prepared.
IV. INSPECTION PLAN
The nonredundant and redundant safety systems are to be identified using the DAEC FSAR. One train of the redundant systems is to be selected for inspection. Area piping drawings and system P&IDs are to be used to identify accessible portions of these systems. A list of the lines associated with nonredundant systems and the selected trains of redundant systems in accessible areas is to be prepared for the initial field inspection phase. Lists of the remaining lines to be inspected in subsequent inspection phases are also to be prepared.
V. DEVELOP AS-BUILT INSPECTION DOCUMENT
For each line in the field inspection effort, an inspection package is to be developed. The basic documents in the package for each line are the hanger isometric(s) and the hanger detail drawings. This package is assembled as follows:
A. An inspection data sheet for each line to be inspected is prepared. The data sheet lists the line identification number and the DAEC system startup number for the system containing the line.
B. The system P&ID which contains the selected line is checked to determine the seismic boundaries of the line. All hanger isometrics which show the line or portions of the line will be listed in the inspection data sheet. If the line connects to a non-Seismic Category I (non-SCI) line, the SCI line ends at the first rigid anchor after the seismic boundary. The hanger isometric for this portion of the non-SCI line will also be listed.
C. Copies of all hanger isometrics associated with a line will be collected for the inspection package.
D. The hanger isometrics will be reviewed to identify all seismic supports or restraints. The list of supports/restraints and the hanger detail drawing number for each will be listed on the data sheet.
E. Copies of all hanger detail drawings will be collected for inclusion in the package.
F. The dimensions of the hanger locations are to be extracted from the seismic calculation input and added to the hanger isometric. If, because of the availability of inspection packages required to support the inspection teams, there is not ample time to extract these dimensions, then the dimensions are to be added from the field measurements to the hanger isometric and compared to the calculation dimensions after the inspection.
G. The function of the hanger, that is the restriction or loadcarrying direction, is to be extracted from the calculation input and checked against the function indicated on the hanger detail drawing. Conformance is to be noted on the inspection data sheet. Because of schedule reasons, the check on the hanger function may be made following the field inspection when the verified as-built isometrics and hanger drawings are compared to the stress isometric and calculation input.
H. Valve mark numbers are to be extracted from the system P&IDs and marked in the inspection data sheet and the hanger isometrics. The inspection data sheet, the hanger isometric(s), and the hanger detail drawing(s) will comprise the field inspection package.
I. Spool checklist
VI. DEVELOP AS-DESIGNED DOCUMENTS
For lines 2-1/2-inches and larger, the stress isometric represents the as-designed configuration which was used as input to the seismic calculation. Copies of the stress isometric will be obtained for each line identified in the inspection effort. If the stress isometric does not contain the location dimensions of the hangers, then the calculation input will be reviewed to extract the dimensions from the input data. Should the stress isometric be unavailable, data from existing isometrics and original stress calculations may be used to reconstruct a stress isometric. For safety-related, computer-analyzed piping 2 inches and smaller, the field isometric represents the as-designed configuration.
VII. FIELD INSPECTION
The actual configuration of the piping systems included in this procedure are to be verified by field inspections or walkdowns of each safety-related line. The inspections are to be conducted using the guidelines listed below. The personnel involved in the field inspections are to receive qualifications training prior to conducting the inspections. Documentation of the qualification training for the individuals is to be provided. The inspection package described in Section V is to be provided to the inspection team assigned to a given line.
The inspection teams are to verify that:
A. Piping geometry conforms to the as-built hanger isometric. The dimensions of the piping configuration are to be checked.
B. Branch connection locations conform to the hanger isometric. The dimensions to the connections are to be checked.
C. Valve locations and valve identification numbers conform to the hanger isometric. The dimensions of the valve location within the piping run are to be checked.
D. Support/restraint locations conform to the hanger isometric. The dimensions of the support/restraint within the piping run are to be checked. Those supports/restraints with concrete expansion bolts are being inspected under Bulletin 79-02, and only the locations of these support/restraints are to be verified under this procedure.
For dimensional checks on the pipe geometry, branch connections, and valve location, a tolerance of + 6 inches or + 5% of the total length of any individual piping run between changes of direction, whichever is larger, is acceptable. For dimensional checks on support/restraint locations, a tolerance of + 6 inches for pipe sizes 4 inches and smaller and + 2 pipe diameters with a maximum of + 24 inches for all other sizes is acceptable. For checks on support/restraint orientation, a tolerance of + 15 degrees is acceptable. It is expected that verification of the majority of the location dimensions will be performed by the use of a measuring device. However, visual verification is acceptable in those situations where the inspector is assured that the dimension can be judged within the above tolerances. For example, when the piping is a larger diameter and the runs are fairly short, the distance can usually be visually determined to be within the established tolerances, or a pipe run may cross two column lines which have a known spacing.
E. Valve operator orientation conforms to the hanger isometric. The orientation of the valve operator in the plane normal to the piping run is to be checked. A tolerance of + 10 degrees from the drawing orientation is acceptable.
F. The support/restraint function conforms to the function indicated on the hanger detail drawing. This relates to the type and load direction. The type is one of the following: spring, rod, strut, or snubber. The loading direction is to be checked against the hanger design shown in the hanger detail drawing.
G. Support/restraint assembly details conform to the hanger detail drawings. Items to be checked are the existence and size of structural members, existence of reinforcing members, existence of attachment welds (exact size need not be measured), and orientation.
H. Clearances specified for restraints are no larger than 1/8 inch and clearances for floor and wall penetrations which are not designed to act as restraints are no smaller than 1/8 inch.
I. Anchor assembly details are in general compliance with the detail drawing. Visual inspection of anchors is acceptable.
It is not necessary to remove insulation for inspections, except for inspections of clearances specified in Item VII.H. A random sample of approximately 20% of those restraints which are insulated and require checking of clearances shall be selected and the insulation removed for the check to be made. A high incidence of clearances found out of tolerance shall be cause for further inspection of insulated restraints. In the conduct of the field inspections, the information on the inspection drawings which is in conformance with the actual installation will be yellowed out for accessible lines and a green check will be used for inaccessible lines. Inspection information which is added during the inspection will be documented with a green pen. Any information added to the inspection documents from any source other than the field inspection will be added with a red pen. Information added to inspection documents in any other color will be ignored.
VIII. COMPARISON OF THE AS-BUILT AND AS-DESIGNED CONFIGURATIONS
A. A completed inspection package for each line will contain:
.1. The completed inspection data sheet signed and dated by the field inspector
2. The verified hanger isometric marked to indicate the measured dimensions which conform to the hanger isometric. Any deviation of the dimensions, piping geometry, or valve orientation will also be marked on the verified hanger isometric.
3. The hanger detail drawings marked to show any deviations of the actual installation from the detail drawing
4. The spool checklist
B. The verified hanger isometric is to be compared to the stress isometric for conformance. A Piping System Design Conformance Data Sheet is to be prepared to document the comparison. Any discrepancies are to be noted on the data sheet. If the hanger location dimensions were not added to the hanger isometric before the field walkdown, the dimensions measured in the field (green pen) will be yellowed out during the conformance comparison unless otherwise approved by the Bechtel project engineer. For inaccessible lines, no marks will be made on the inspection documents. The hanger detail drawings which indicate discrepancies will also be listed on the data sheet. The completed verification package will include:
1. Completed Inspection Package
a. Inspection data sheet
b. Hanger isometric
c. Spool checklist
d. Hanger detail drawings
2. Completed Comparison Package
a. Stress isometric
b. Design conformance data sheet
IX. EVALUATION OF DISCREPANCIES
Following the comparison of the as-built and as-designed configurations, the completed verification package, with discrepancies noted on the Design Conformance Data Sheet, will be turned over to a stress analyst for evaluation. The stress analyst will determine if the noted discrepancies will significantly affect the seismic analysis originally performed. If it is determined that a nonconformance exists, then the line will be reanalyzed. For purposes of this effort, a nonconformance is defined as a discrepancy which the stress evaluation finds invalidates the conclusions of the seismic analysis of record.
PIPING SYSTEM WALKDOWN DATA SHEET
Spool identification:
Hanger isometric used for inspection:
Stress isometric:
Pipe geometry: This includes spool dimensions, valve locations, and clearances
Meets isometric
Differs from isometric (attach sketch or description)
VALVES (INCLUDING OPERATORS)
Valve Weight Analyzed Weight from Vendor Print Ven
SUS number
Rev: Date
Rev: Date
dor Print Number
SUPPORTS/RESTRAIMPS
Calculation As-Built Location Configuration Function Function Clearance
Identification Number Drawing/Revision T Per Isometric Per Detail Matches Detail Matches Detail Acceptable
Pipe attachments per spool drawing:
Clearances required around pipe:
Tolerances: Pipe location:
Inspection by:
Yes No (explain)
Hanger location:
Signature: Date
PIPING SYSTEM DESIGN CONFORMANCE DATA SHEET
1.
2.
3.
4.
5.
6. Hanger details: List hanger detail drawings which have discrepancies:
7. Valves: List valves in which the vendor weight different from the analyzed weight:
By D t_
Spool identification: SUS number:
Verified hanger isometric: Rev: Date
Stress isometric Rev: Date
Calculation number:
Pipe geometry
Stress isometric conforms to verified inspection isometric
Does not conform
List discrepancies:
a
e
SPOOL CHECKLIST
1. Spool number:
2. Complete set of isometrics to boundaries list missing drawings.
3. Complete set of hanger drawings yes drawings.
yes no. If no,
no. If no, list missing
4. Hanger locations and function extracted from stress input -yes no
5. Items 1, 2, and 3 and the proper columns of Items 5 and 6 completed on data sheet
by Date
6. Hanger list sent for 79-02 check
7.
8.
9.
by Date
79-02 check complete, record attached Date
Released to field by Date
Number of data sheets in complete spool package
PIPING SYSTEM NONCONFORMANCE RESOLUTION SHEET
1. Spool identification:
Resolution of nonconformances:
SUS number:
By DateDateBy
Attachment 2
LIST OF DESIGN DOCUMENTS FOR
ANALYSIS OF LINES IN VARIOUS INSPECTION GROUPS
TABLE OF CONTENTS
2-1 List of Design Documents for Seismic Analysis of Group 1 Lines
2-41 List of Design Documents for Seismic Analysis of Group 2 Lines
2-58 List of Design Documents for Seismic Analysis of Group 3 Lines
2-87 List of Design Documents for Seismic Analysis of Computer-Analyzed Safety-Related Small Pipe
Attachment 2 (229 pages)
List of Design Documents for Seismic Analysis of Group 1 Lines
Line #: DBB-1 Service: RHR pump discharge from MO-2004 to MO-2003
Design Input Documents:
Piping Class/Summary Sheet: DBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-20 A BP-9172, R1
2) Valve Vendor Print Numbers
MO-2004 M133C-2(l)-ll MO-2003 M152A-4-4
Line #: EBB-4 Service: RCIC test line
Design Input Documents:
Piping Class/Summary Sheet: EBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric cannot be found
1) Hanger Drawing Number
H-15 BP-1651, Rl SR-12 BP-1672, R3 H-16 BP-1652, RI &
BP-1652A, RI & BP-1652B, RI
H-17 BP-1653, R1 H-18 BP-1654 H-19 BP-1655
2) Valve Vendor Print Numbers
MO-2515 M133A-004-6 V-25-07 M133A-047-4
2-1
Line #: EBB-6 Service: HPCI pump recirculation to MO-2318
Design Input Documents:
Piping Class/Summary Sheet: EBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric cannot be found
1) Hanger Drawing Numbers
H-21 BP-1657, Ri H-20 BP-1656, R2
2) Valve Vendor Print Numbers
MO-2318 M133A-012-5 V-23-14 M133A-017-4
Line #: EBB-17 Service: Core spray from MO-2115 to MO-2117
Design Input Documents:
Piping Class/Summary Sheet: EBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-12 BP-1726 H-13 BP-1727 SR-17 BP-1793
2) Valve Vendor Print Numbers
MO-2115 M133A-040-3
2-2
Line #: GBB-3 Service: RHR pumps P-229 B, D discharge to MO-1903
Design Input Documents:
Piping Class/Summary Sheet: GBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-1 BP-1846/3 BP-1846A/1
H-2 BP-1847/2 H-3 BP-1848/1 H-4 BP-1849/2
BP-1849A/1 H-5 BP-1850/2 H-6 BP-1851/1
BP-1851A/1 H-30 BP-1882, RI SS-235 BP-2088, R1, Sh. A H-31 BP-1883, RI H-32 BP-1884, R2 H-33 BP-1885, R2 H-34 BP-1886, R2 SS-236 BP-2089, Ri, Sh. A H-35 BP-1887, R2 H-36 BP-1888, R2
BP-1888A, Ri H-20C BP-9715, Ri
BP-9715A, RI SS-237 BP-2090, Ri SS-238 BP-2091, R2 SA-78 BP-1930/2 H-79 BP-1931/2 H-80 BP-1932/2 H-81 BP-1933/2 H-82 BP-1934/1 H-83 BP-1935/2 H-84 BP-1936/1 H-85 BP-1937/1
2) Valve Vendor Print Numbers
V-19-2 M137A-Ol0-4 V-19-3 M137A-001-4 V-19-4 M137A-010-4 MO-1940 MI37A-009-6 V-19-12 M137B-4-3 V-19-13 M137B-4-3
2-3
Line #: GBB-5Service: Discharge crossover from pumps P-229 B, D to P-229 A, C
Design Input Documents:
Piping Class/Summary Sheet: GBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
SR-230 H-18 H-19 SS-215 H-20
BP-2083RI BP-1870R3 BP-1871R2 BP-2068/ARlRI BP-1872R3
2) Valve Vendor Print Numbers
MO-2010 MO-1937 MO-1936 V-19-48
M137A-8-3 M137B-11-3 M137A-16-4 M137A-56-1
Line 4: Service:
GBB-6 RHR pumps P-229B, D discharge to RHR heat exchanger IE-201B
Design Input Documents:
Piping Class/Summary Sheet: GBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1). Hanger Drawing Numbers
BP-1852/1 & BP-2078/1 BP-2079/2
BP-1852A/1
2) Valve Vendor Print Numbers
MO-1939 M137-17-7.2
2-4
H-7 SS-225 SS-226
Line #: GBB-8 Service: RHR pumps discharge from RHR heat exchanger IE-201B to header
Design Input Documents:
Piping Class/Summary Sheet: GBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Sketch-735
1) Hanger Drawing Numbers
H-29 BP-1881/2 & BP-1881A/1 & BP-1881B/2
2) Valve Vendor Print Number
MO-1941 M137A-13-4
Line #: GBB-10 Service: RHR pump discharge from header to MO-1901
Design Input Documents:
Piping Class/Summary Sheet: GBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Sketch-735
1) Hanger Drawing Numbers
H-25 BP-1877, R1 SS-241 BP-2094 H-26 BP-1878, R2 &
BP-1878A, R1 SS-243 BP-2096, RI SR-244 BP-2097 &
BP-2097A SS-242 BP-2095, R2 H-27 BP-1879, R2 H-28 BP-1880, R2
2) Valve Vendor Print Numbers
None
2-5
Line #: GBB-13 Service: Core spray pump IP-211A discharge
Design Input Documents:
Piping Class/Summary Sheet: GBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-1 BP-1715, R1 & BP-1715 A, RI SR-13 BP-1789, RI SR-14 BP-1790, RI H-2 BP-1716, Ri H-3 BP-1717, RI H-4 BP-1718, Ri & BP-1718A, Ri H-5 BP-1719A-C, R2 & BP-1719 H-6 BP-1720, R2 H-7 BP-1721, R2 SR-15 BP-1791, Ri SS-16 BP-1792, RI H-8 BP-1722, R2 H-9 BP-1723, R2 H-10 BP-1724, R2 H-11 BP-1725, Ri
2) Valve Vendor Print Number
V-21-7 M137A-002-4
2-6
Line#: GBB-15 Service: RHR pumps P-229 B, D discharge to test line upstream
of MO-1935, MO-1970
Design Input Documents:
Piping Class/Summary Sheet: GBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
BP-1960, BP-1961, BP-1962, BP-1963, BP-1964, BP-1964A, BP-1965, BP-1966, BP-1967, BP-1968, BP-1969, BP-1970, BP-1971, BP-1972,
R2 R1 Ri Ri Ri R1
Ri Ri R1 Ri Ri Ri Ri R2
2) Valve Vendor Print Numbers
V-19-14 V-19-15 CV-1966 V-19-6 MO-1967
Mi37A-4-4 Mi37B-5-3 Mi44A-8-28 MI37A-3-4 M137B-10-3
2-7
H-108 H-109 H-110 H-111 H-112
H-113 H-114 H-115 H-116 H-117 H-118 H-119 H-120
Line #: GBB-18 Service: Condensate supply to RHR discharge to reactor
Design Input Documents:
Piping Class/Summary Sheet: GBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric cannot be found
1) Hanger Drawing Numbers
H-156 BP-2009, RI H-79 BP-4730/1 H-80 BP-4731/1 H-81 BP-4732/1 H-82 BP-4733/1 H-126 BP-4777/1 H-125 BP-4776/1 H-84 BP-4735/1 H-85 BP-4736/1 H-86 BP-4737 H-96 BP-4747/2 H-95 BP-4746/2 H-94 BP-4745/1 H-93 BP-4744/1 H-92 BP-4743/1 H-91 BP-4742/1 H-118 BP-4769/1 H-119 BP-4770/1 H-120 BP-4771/1 H-121 BP-4772/1 H-122 BP-4773/2
2) Valve Vendor Print Numbers
V-34-20 M137B-9-3 V-34-21 M137A-41-3 V-36-13 M137A-40-4 V-19-30 M137B-4-3 V-19-31 M137B-4-3
2-8
Line #: GBB-22 Service: RHR service water discharge to RHR system downstream of MO-1942
Design Input Documents:
Piping Class/Summary Sheet: GBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Number
H-28 BP-2528, R1
2) Valve Vendor Print Numbers
V-20-lO M137A-051-2 MO-1942 M137A-013-4
Line #: GBB-23 Service: RHR discharge to fuel pool storage
Design Input Documents:
Piping Class/Summary Sheet: GBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SK-M-338
1) Hanger Drawing Numbers
H-153 BP-2006, R2 SR-160 BP-2013, R1 H-155 BP-2008, R2 H-148 BP-2001, R1 SA-157 BP-2010, R2 H-150 BP-2003, Ri SR-158 BP-2011, Rl H-152 BP-2005, R2 SR-159 BP-2012, Ri SR-161 BP-2014, Ri
2) Valve Vendor Print Numbers
V-34-48 M137A-48-2
2-9
Line #: GBC-2 Service: RHR service water discharge to RHR heat exchanger IE-201B
Design Input Documents:
Piping Class/Summary Sheet: GBC/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-66 BP-2566, RI H-67 BP-2567, R2 SR-157 BP-6257, RI H-68 BP-2568, Ri SA-90 BP-6190, Ri H-60 BP-2560, Ri H-61 BP-2561, Ri H-62 BP-2562, R2 H-63 BP-2563, R2 H-64 BP-2564, Ri H-65 BP-2565, Ri H-7 BP-2507, Ri H-8 BP-2508, Ri H-9 BP-2509, Ri H-10 BP-2510, R2 SR-60 BP-6160B, Ri
BP-6160, Ri BP-6160A, RI
H-li BP-2511, Ri BP-2511A, Ri
H-12 BP-2512, Ri H-13 BP-2513, Ri SR-61 BP-6161, Ri H-14 BP-2514, Ri H-15 BP-2515, Ri SS-62 BP-6162, Ri SR-64 BP-6164, Ri H-16 BP-2516, Ri
BP-2516A, Ri H-17 BP-2517, Ri
2) Valve Vendor Print Numbers
V-46-16 V-46-17 V-46-13 V-46-11 V-46-12 V-46-14 V-13-1 V-13-2
M137A-44-2 M137A-44-2 M137-035-3 MI37-035-3 MI37-045-2 M137-045-2 M137A-44-2 MI37-44-2
2-10
Line #: GBC-4 SErvice: RHR service water from RHR heat exchanger IE-201B to
MO-1946
Design Input Documents:
Piping Class/Summary Sheet: GBC/M-190 Seismic Response Spectra: See FSAR Piping SEress Isometric Drawings: SK-0217884-149
1) Hanger Drawing Numbers
H-36 BP-2536/1 BP-2536A/1 BP-2530A/2
H-37 BP-2537/3 SR-74 BP-6174/1 SR-73 BP-6173/1
BP-6173A/1
2) Valve Vendor Print Number
MO-1947 MI44A-120-4 V-13-3 M137A-44-2
Line #: GBC-5 Service: RHR service water discharge to RHR heat exchanger discharge
upstream of MO-1942
Design Input Documents:
Piping Class/Summary Sheet: GBC/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger DrAwing Numbers
SA-59 BP-6159, R2 H-24 BP-2524, RI H-25 BP-2525, Ri H-26 BP-2526, R2 H-27 BP-2527, Ri
BP-2527A, Ri H-18 BP-2518, R1 H-19 BP-2519, R1 H-20 BP-2520, Ri H-21 BP-2521, Ri H-22 BP-2522, Ri
2) Valve Vendor Print Numbers
12" Check M137A-35-3 MO-1943-B M137-34-5 MO-1943-A M137A-34-5 V-13-15 M137A-35-3
2-11
Line #: GLE-5 Service: RHR pump discharge and test line to torus spray
between MO-1932 and MO-1933 and MO-1934
Design Input Documents:
Piping Class/Summary Sheet: Seismic Response Spectra: Piping Stress Isometric Drawir
1) Hanger Drawing Numbers
H-23 H-24
GLE/M-190 See FSAR igs: Isometric Reconstructed
BP-1737 BP-1738
2) Valve Vendor Print Numbers
MO-1934 MO-1932 MO-1933
MI51A-007-4 MI51A-006-4 M137A-17-4
Line #: HBB-2 Service: Core Spray Pump IP-211A Suction
Design Input Documents:
Piping Class/Summary Sheet: HBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SK 75-396-30
1) Hanger Drawing Numbers
BP-1701 RO BP-1701A Rl BP-1702 Rl BP-1702 A R1 BP-1703 Rl BP-1703A Rl BP-1704 RO BPl704A Ri BP-1705 R1 BP-1705A Ri BP-1783 R2 BP-1785 R1 BP-1706 Ri BP-1706A R1 BP-1707 R3 BP-1771 R1
2) Valve Vendor Print Numbers
MO-2100 V-21-1
M137A-15-3 M137A-011-4
2-12
H-1
H-2
H-3
H-4
H-5
SS-7 SS-8 H-6
H-7
Line #: HBB-6 Service: HPCI turbine exhaust to torus isolation valve
Design Input Documents:
Piping Class/Summary Sheet: HBB Seismic Response Spectra: See Piping Stress Isometric Drawings:
1) Hanger Drawing Numbers
SR-1 BP-1585 Ri BP-1585A Ri
H-1 BP-1501 R2 BP-1501 Ri
SS-20 BP-1586 R2 H-2 BP-1502 R2
BP-1502A RI SR-21 BP-1587 R3 H-3 BP-1503 Ri
BP-1503A R1 H-4 BP-1504 R2 H-5 BP-1505 Ri SS-22 BP-1588 Ri H-6 BP-1506 R2
2) Valve Vendor Print Number
V-22-16
/M-190 FSAR Isometric Reconstructed
M137A-005-5
2-13
Line #: HBB-7 Service: RCIC turbine exhaust to torus isolation valve
Design Input Documents:
Piping Class/Summary Sheet: HBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SK TS-395-51
1) Hanger Drawing Numbers
H-1 BP-1601 R2 BP-1601A Ri
H-2 BP-1602 R1 SS-17 BP-1677 R2 H-3 BP-1603 Ri H-4 BP-1604 R2 SS-18 BP-1678 R2 H-5 BP-1605 R3 SS-1 BP-1680 RI
BP-1680A RI H-6 BP-1606 R5 H-7 BP-9725 R3
BP-9725A R2
2) Valve Vendor Print Numbers
V-24-23 M137A-007-5
2-14
I
Line #: HBB-8 Service: HPCI pump suction from MO-2321 to MO-2322
Design Input Documents:
Piping Class/Summary*Sheet: HBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-1 BP-1524, Ri SR-1 BP-6105, RI SR-2 BP-6106, Ri
BP-6106A, RI H-3 BP-1526, Ri H-4 BP-1527, R2 SR-3 BP-6107, Ri
BP-6107A, R2 H-5 BP-1528, R2 SR-4 BP-6108, RI H-6 BP-1529, Ri
BP-1529A, Ri H-7 BP-1530, Ri H-8 BP-1531, R2
2) Valve Vendor Print Numbers
V-23-1 MI37A-012-4 MO-2322 MI37A-014-4
Line #: HBB-9 Service: HPCI pump suction from condensate line
Design Input Documents:
Piping Class/Summary Sheet: HBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-9 BP-9727 Ri
2) Valve Vendor Print Numbers
MO-2300 M137A-014-4 V-23-4 MI37A-012-4
2-15
Line #: HBB-14 Service: RCIC pump suction from MO-2516 to MO-2517
Design Input Documents:
Piping Class/Summary Sheet: HBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-1 BP-1617 R2 H-2 BP-1618 RI SR-5 BP-1665 Ri H-3 BP-1619 R2
BP-1619A R2 H-4 BP-1620 R2 H-5 BP-1621 RI SR-4 BP-1664 RI H-6 BP-1622 RI
2) Valve Vendor Print Numbers
V-25-01 MO-2517
M137A-6-4 MI37B-14-3
Line#: Service:
HBB-15 RCIC pump suction from condensate storage tank
Design Input Documents:
Piping Class/Summary Sheet: HBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-l BP-1627 R2 H-7 BP-1623 RI H-8 BP-1624 R2
2) Valve Vendor Print Numbers
V-25-03 MO-2500 V-25-02 V-25-04 MO-2517 V-25-05 V-25-01
M137A-6-3 M137B-14-3 M137B-6-3 M137B-6-3 M137B-14-3 M137A-6-4 M137A-6-4
2-16
Line#: HBB-21 Service: RCIC pump suction from RHR heat exchanger
Design Input Documents:
Piping Class/Summary Sheet: HBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-10 H-9 H-49 H-50 H-51 H-52 H-53
H-54 SS-218 H-48 H-47 H-46 H-45 H-44 H-37
BP-1626, RI BP-1625, RI BP-1901, R2 BP-1902, R2 BP-1903, R2 BP-1904, R3 BP-1905, R2 BP-1905A, R2 BP-1906, Ri BP-2071, RI BP-1900, R2 BP-1899, R2 BP-1898, R3 BP-1897, R2 BP-1896, R2 BP-1889, RI
2) Valve Vendor Print Numbers
V-25-04 V-25-05
M137B-6-3 MI37A-6-4
2-17
Line#: HBB-23 Service: RHR pumps P-229 B,D, suction downstream of MO-1909
Design Input Documents:
Piping Class/Summary Sheet: HBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-1 BP-1821 RI H-2 BP-1822 Ri H-3 BP-1823 Ri H-4 BP-1824
BP-1824A BP-1824B
H-5 BP-1825 R2 H-20 BP-1820 R3 H-19 BP-1819 Ri H-18 BP-1818 R2
BP-1818A Ri H-15 BP-1815 R2
BPl815A Ri SS-220 BP-2073 Ri H-16 BP-1816 R2 H-17 BP-1817 R3
BP-1817A R2 SS-219 BP-2072 Ri H-14 BP-1814 Ri
BP-1814A Ri H-13 BP-1813 R3 H-12 BP-1812 R4
BP-1812A Ri H-llA BP-9711A Ri
BP-9711 RI H-l BP-1811 R2
BP-1811A R2
2) Valve Vendor Print Numbers
MO-1911 Mi37A-14-4 MO-1913 M137A-1.4-4 V-19-10 MI37B-4-3 V-19-12 M137B-4-3 MO-1912 MI37A-14-4 MO-1920 MI37A-14-4 MO-1909 MI52A-30-3
2-18
Line #: HBB-25 Service: Drain from fuel pool skimmer tanks
Design Input Documents:
Piping Class/Summary Sheet: HBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-163 BP-2016 R2 H-164 BP-2017 R2 H-165 BP-2018 R2 SS-178 BP-2031 RI
BP-2031A R1 SR-177 BP-2030 R2 H-166 BP-2019 R2
BP-2019A Ri H-167 BP-2020 R2 H-168 BP-2021 R2 SA-179 BP-2032 RI H-170 BP-2032 R2 H-171 BP-2024 R2 H-172 BP-2025 R2 SR-180 BP-2033 Ri
BP-2033a Ri SR-174 BP-2027 R2 H-175 BP-2028 R2 H-176 BP-2029 R2 H-173 BP-2026 R2
2) Valve Vendor Print Numbers
None
2-19
Line #: HBB-29 Service: RHR relief valve PSV-1952 to suppression pool
Design Input Documents:
Piping Class/Summary Sheet: HBB Seismic Response Spectra: See Piping Stress Isometric Drawings:
1) Hanger Drawing Numbers
H-195 H-196 H-197 H-198 SS-199 H-200 H-201 H-191 SR-192 H-193. SR-194
BP-2048, BP-2049, BP-2050, BP-2051, BP-2052, BP-2053, BP-2054, BP-2044, BP-2045, BP-2046, BP-2047,
/M-190 FSAR Isometric Reconstructed
R2 R2 R2 R2 & BP-2051A, R1 RI & BP-2052A, R1 R2 R2 R2 R2 R2 R2
2) Valve Vendor Print Numbers
None
2-20
Line #: HBD-24 Service: Emergency service water pump IP-99A discharge
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
BP-6193/1 BP-2607/1 BP-2608/1 BP-2609/1 BP-2610/1 BP-2611/1 BP-2612/1 BP-2613/1 BP-2614/1 BP-2515/1 BP-2669/1 BP-2670/1 BP-6260/1 BP-2671/1 BP-8009/1 BP-6246/1 BP-7061/1 BP-9657/1 BP-2682/2 BP-7057/1 BP-7058/1 BP-6249/1 BP7059/1 BP-2675/2 BP-2675A/2 BP-2676/2 BP-2677/2 BP-2678/2 BP2674/1 & BP-2674A/1 BP-2675B/2
SR-150 SA-162 H-42 H-43 H-44 SA-92 H-157 H-158 H-35
H-36 SA-91 H-1 H-2 H-3 H-4 H-5 SR-155 H-6 H-20 H-21 H-22 SA-161 H-12 H-13 H-14 H-15 H-16 H-17 H-18 H-19
&
BP-6250/1 & BP-6262/1 BP-2679/2 BP-2680/2 BP-2681/2 BP-6192/2 BP-7094/1 BP-7095/1 BP-2672/3 & BP-2672B/2 BP-2673/1 & BP-6191/2 BP-2585/2 BP-2586/2 & BP-2587/2 BP-2588/1 BP-2589/2 BP-6255/1 BP-2590/2 BP-2604/1 BP-2605/1 BP-2606/2 BP6261/1 BP-2596/1 BP-2597/1 BP-2598/1 BP-2599/1 BP-2600/1 BP-2601/1 BP-2602/1 BP-2603/1 &
BP-6250A/1
BP-2672A/1
BP-2672A/1
BP-2586A/1
BP-2603A/1
2) Valve Vendor Print Numbers
M135A-31-2 M135A-4-8 M135A-6-5 M135-31-2
V-46-21 V-46-22 V-46-24 V-46-25
M135A-33-3 MI35A-4-8 MI35A-31-2 MI35A-31-2
2-21
SA-93 H-23 H-24 H-25 H-26 H-27 H-28 H-29 H-30 H-31 H-32 H-33 SA-160 H-34 H-123 SA-146 H-124 FH-3 H-45 H-120 H-121 SR-149 H-122 H-38
H-39 H-40 H-41 H-37
V-13-53 V-69-66 V-69-67 V-13-61
Line #: HBD-26 Service: Emergency service water to diesel generator IE-53A
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Seismic REsponse Spectra: See FSAR Piping Stress Isometric Drawings: 0217884-122
1) Hanger Drawing Numbers
SR-103 BP-6203, RI BP-6203A, Ri
SR-5 BP-6117, R2 BP-6117A, R2 BP-6117B, R2
H-1 BP-2654, RI SG-104 BP-6204, RI
BP-2655, RI
2) Valve Vendor Print Numbers
CV-2080 M135A-68-1 V-13-35 M135A-32-3
2-22
Line #: HBD-28 Service: Emergency service water returns from safeguard equipment
serviced by pump IP-99A
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Sesmic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
BP-6196/1 BP-2637/1 BP-2638/1 BP-2639/1 BP-2640/1 BP-2641/1 BP-2642/1 BP-2643/1 BP-2644/1 BP-2645/1 BP-6198/1 BP-2646/1 BP-2647/1 BP-2648/1 BP-2649/1 BP-2683/1 BP-2684/1 BP-2685/1 BP-2650/2 BP-2650A/2 BP-7096/1 BP-7097/1
H-15 SA-99 H-16 H-17 H-49 H-50 SA-94 SR-152 H-51 H-128 H-52 H-53 H-54 H-55 H-56 H-57 SA-95 H-59 H-125 H-126 H-127
BP-2651/2 BP-6199/2 BP-2652/1 BP-2653/1 BP-2686/2 BP-2687/1 BP-6194/1 BP-9748/1 BP-2688/1 BP-7065/1 BP-2689/2 BP-2690/2 BP-2691/2 BP-2692/2 BP-2693/2 BP-2694/2 BP-6195/2 BP-2696/1 BP-7062/1 BP-7063/1 BP-7064/1
2) Valve Vendor Print Numbers
TCV-6924B V-13-122 CV-1956A MO-2077 V-13-54 TCV-6924A V-13-62
M90-1-2 MI35A-4-8 M135A-67-1 M135A-34-2 M135-31-2 M90-1-2 M135-32-3
SA-96 H-1 H-2 H-3 H-4 H-5 H-6 H-7 H-8 H-9 SA-98 H-10 H-11 H-12 H-13 H-46 H-47 H-48 H-14
H-159 H-160
2-23
Line #: HBD-31 Service: Service water return from RHR heat exchanger IE-201B to
downstream of MO-1947 to MO-1998B
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SK 0217884-149
1) Hanger Drawing Numbers
SS-71 BP-6171 R1 H-38 BP-2538 R1 H-39 BP-2539 R1 H-40 BP-2540 Ri SR-70 BP-6170 R1
BP-6160A Ri H-42 BP-2542 R1 H-43 BP-2543 R1 H-44 BP-2544 R1 H-45 BP-2545 Ri SS-l1 BP-6201.Ri H-46 BP-2546 R1 H-47 BP-2547 RI H-48 BP-2548 Ri H-49 BP-2549 Ri H-50 BP-2550 R1
2) Valve Vendor Print Numbers
MO-1998 B Mi44C-49-1
Line #: HBD-32 Service: RHR service water return from RHR heat exchanger to cooling
tower via CW discharge downstream of MO-1998 A,B
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Sketch-710
1) Hanger Drawing Numbers
H-35 BP-2353, R2
2) Valve Vendor Print Numbers
None
2-24
Line #: HBD-67 Service: River water pumps IP-117 B,D discharge
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SK-M-401, SK-M-399, SK-M-403
1) Hanger Drawing Numbers
H-10 H-9 H-8 SA-28 H-29 H-28 SA-29 H-27 H-26 H-30 FH-20 H-21 FH-21 H-23 H-24 SA-2 7 SA-39 H-3 H-4 SA-37 SA-46 H-2 H-1 SA-44 SA-45 H-13 H-14 SA-30
BP-2578 BP2577 BP-2576 BP-6128, BP-5229, BP-5 228, BP-6129, BP-5227, BP-5226, BP-5220, BP-9501, BP-9502, BP-5223, BP-5224, BP-6127, BP-6139, BP-2571, BP-2573, BP-6137, BP-6246, BP-6146A, BP-2 570, BP-2569, BP-6144, BP-6145, BP-2581, BP-2 582, BP-6130,
Fl
Fl
2) Valve Vendor Print Numbers
AV-2902B AV-2909D V-29-6 V-29-8 V-29-5 V-29-7 V-39-17 V-29-25 AV-2909F CV-4910A CV-4909 CV-4914 V-46-43 V-46-46
Multiplex (Model A-32) Multiplex (Model A-32) M144C-014-4 M144C-014-4 M132A-002-4 M132A-002-4 M135A-004-8 M135A-004-8 Multiplex (Model A-32) M144C-024-5 M144C-024-5 M144C-028-1 M135A-032-3 M135A-004-8
2-26
R2, R2 R2 R2, RI R2 R2 RI RI R2 RI R2 RI R1 Ri R2 R2 R1
R2 R2 R3 R3 R1 R2 R4
Line #: HBD-80 Service: Emergency service water from diesel generator IE-53A to
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
SR-1
H-7 H-8 SG-108 H-9 H-10
BP-6113 R3 BP-6113A R2 BP-2660 R2 BP-2661 R2 BP-6208 Ri BP-2662 R2 BP-2663 R2
2) Valve Vendor Print Numbers
None
Line #: HBD-82 Service: Discharge from PSE to 2079 A, B to radwaste dilution
line and deicing
Design Input Documents:
Piping Class/Summary Sheet: HBD Seismic Response Spectra: See Piping Stress Isometric Drawings:
1) Hanger Drawing Numbers
/M-190 FSAR 75.396-48 & Reconstructed Isometric
BP-1002, R2 BP-1003. R2 BP-1004, R2 BP-7022, Ri BP-7023, Ri BP-7024, RI BP-5240 BP-5241 & BP-5241 A BP-5244 BP-5242, R2 BP-5243, R2 BP-5245, R2 BP-5246, R2 BP-1000, R3 BP-1001, R2
2) Valve Vendor Print Numbers
M144C-053-3 M144C-36-3, 51-1, 54-2 M144C-56-1, 61-1, 63-2 M144C-74-2 M144C-75-2
2-27
H-202 H-203 H-204 H-85 H-86 H-87 H-40 H-41 H-44 H-42 H-43 H-45 H-46 H-200 H-201
V-42-10 V-42-11 V-42-12 V-29-37 V-29-32
Line #: HBD-97 Service: Well water pump discharge
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: 75.396-9 and 75.396-10
1) Hanger Drawing Numbers
H-79 H-80 H-81 FH-3 FH-2 H-82 H-83
BP-5079, R1 BP-5080, R1 BP-5081, R1 BP-9554 BP-9553 BP-5082 BP-5083
2) Valve Vendor Print Numbers
V-44-20 V-44-23 CV-5701 V-44-24
M135A-3-4 MI35A-3-4 M135A-78-2 M135A-31-2
Line #: HBD-122 Service: Diesel exhaust
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers *
BP-6115, BP-3868, BP-3869, BP-3870, BP-3871, BP-6116, BP-3872, BP-3873, BP-3874, BP-3875,
R2 & BP-6115A, R2 RI R2 RI R1 R2 & BP-6116A, R2 R3 R2 RI RI
2) Valve Vendor Print Number
None
2-28
SR-3 H-68 H-69 H-70 H-71 SR-4 H-72 H-73 H-74 H-75
Line #: HBD-159 Service: Cooling water P/P IV-CP-30B discharge through chiller to
control room air
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings:
1) Hanger Drawing Numbers:
SA-1 .BP-8001, R1 H-6 BP-8006, Rl H-7 BP-8007, Rl H-18 BP-8018-1, RI H-23 BP-8023-1, Rl H-22 BP-8022-1, Rl H-21 BP-8021-1, RI
2) Valve Vendor Print Numbers:
V-69-68 M135BC-1-1 V-69-83 M135BC-1-1
2-29
Line #: HBD-161 Service: Control room air CCW to p/p IV-CP-30B
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-19 BP-8019, R2 H-18 BP-8018-2, RI H-23 BP-8023-3, Ri H-22 BP-8022-3, Ri H-15 BP-8015, RI SA-14 BP-8014, RI
2) Valve Vendor Print Numbers
V-69-22 M-135A-4-8 V-69-135 M135A-4-8
Line #: HCB-2 Service: Standby liquid control pump suction
Design Input Documents:
Piping Class/Summary Sheet: HCB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-50 BP-4871, Ri H-51 BP-4872, R2 H-52 BP-4873, R2 H-53 BP-4874, R2
2) Valve Vendor Print Numbers
V-26-2 M-143B-001 V-26-3 M-143B-001 V-26-1 M-143B-003 V-26-18 M-143B-003
2-30
Line #: HCC-6 Service: HPCI suction from condensate storage tank
Design Input Documents:
Piping Class/Summary Sheet: HCC/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
SR-5 BP-6109, R2 BP-6109A, RI BP-6109B, RI
SR-6 BP-6110, RI BP-6110A, Ri
SR-7 BP-6111, R2 BP-6111A, RI BP-6111B, RI
H-10 BP-6112, R2 BP-6112A, R2
H-11 BP-9729, RI H-12 BP-9730, RI
BP-9730A, R2 BP-9730B, R2
2) Valve Vendor Print Numbers
None
Line #: HCC-7 Service: RCIC suction from condensate storage tank
Design Input Documents:
Piping Class/Summary Sheet: HCC/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-14 BP-1630 R2 H-13 BP-1629 R2 SR-6 BP-1666 RI H-12 BP-1628 R2
BP-1628A R2
2) Valve Vendor Print Numbers
None
2-31
Line #: HCC-8 Service: Core spray pump suction from condensate storage tank
Design Input Documents:
Piping Class/Summary Sheet: HCC/M-190 Seismic Response Spectra: See FSAR Piping St-ress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-6 BP-1761, R3 BP-1761A, R3 BP-1761B, R2
H-7 BP-1762, R2 H-14 BP-1769, R2 H-13 BP-1768, R2 H-12 BP-1767, R3 H-11 BP-1766, R2 H-10 BP-1765, R2 H-9 BP-1754, R3 H-17 BP-1772, R2
BP-1772A, R2 SS-11 BP-1787, R1 SS-12 BP-1788, R2 H-16 BP-1771, R2 SA-23 BP-1799, R1 H-8 BP-1763, R2 H-2 BP-1757, R3 H-1 BP-1756, R3 H-3 BP-1758, R3 H-4 BP-1759, R2 H-5 BP-1760, R3
2) Valve Vendor Print Numbers
None
2-32
Line #: HLE-1 Service: HPCI pump suction from torus to MO-2321
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
None
2) Valve Vendor Print Numbers
MO-2321 MI51A-002-4
Line #: HLE-2 Service: RCIC pump suction from torus to MO-2516
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
None
2) Valve Vendor Print Numbers
MO-2516 M137-34-2
2-33
Line #: HLE-4 Service: Core spray pump IP-211A suction from torus through MO-2147
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
None
2) Valve Vendor Print Numbers
None
Line #: HLE-5 Service: RCIC turbine exhaust to torus
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: 75-395-51
1) Hanger Drawing Numbers
None
2) Valve Vendor Print Numbers
V-24-8 MI51A-005-4
Line #: HLE-6 Service: HPCI turbine exhaust to torus
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-7 BP-1507 R2 H-7A BP-9656 R2
2) Valve Vendor Print Number
V-22-17 MI51A-008-4
2-34
Line #: HLE-12 Service: RHR pump discharge to torus spray from MO-1933
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-17 H-18
BP-1731 BP-1732
2) Valve Vendor Print Numbers
None
Line #: Service:
HLE-13 RHR test line to torus from MO-1934 and MO-2038 and MO-2009
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
BP-1730 BP-1733 BP-1734 BP-1735 BP-1736 BP-9644, BP-6710, BP-6711, BP-6712, BP-6713, BP-6715, BP-6714,
H-157 H-158 H-159H H-160 H-161
R1 Ri Ri Ri R1 Ri R1
BP-4157, RI BP-4158, Ri BP-4159, R2 BP-4160, RI BP-4161, R1
2) Valve Vendor Print Numbers
M137B-33-1 M137B-33-1 MI37B-9-3 Mi37A-41-3 M137B-9-3 M137A-41-3 MI37B-9-3
2-35
H-1 6 H-19 H-20 H-21 H-22 FH-1 H-210 H-211 H-212 H-213 H-215 H-214
V-19-28 V-19-29 V-37-23 V-37-21 V-37-22 V-37-24 V-37-25
Line # Service:
HLE-15 RHR pump discharge to containment coil from MO-200 through penetration
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-14 H-15
BP-1728,R2 BP-1729
2) Valve Vendor Print Numbers
MO-2112 MI51A-25-1
Line #: Service:
HLE-16 Core Spray Test Line
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-11 H-12
BP-1749 R2 BP-1750 R2
2) Valve Vendor Print Numbers
None
Line #: Service:
HLE-18 RHR pump discharge to containment coil from MO-1902 through penetration
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric cannot be found
1) Hanger Drawing Number
None
2) Valve Vendor Print Number
None
2-36
I
Line #: HLE-19 Service: HPCI minimum flow line downstream of MO-2318
Design Input Documents:
Piping Class/Summary sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric cannot be found
1) Hanger Drawing Numbers
H-24 BP-1660, R1 H-23 BP-1659, R2 & BP-1659A, R1 H-22 BP-1658, Ri H-1 BP-1773, Ri H-2 BP-1774, R2 & BP-1774A, RI H-3 BP-1775, RI H-4 Bp-1776, Ri
2) Valve Vendor Print Numbers
None
Line #: HLE-23 Service: Containment vent purge exhaust
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric can not be found
1) Hanger Drawing Numbers
H-1l BP-4511 R2 SR-47 BP-4547 R2
2) Valve Vendor Print Numbers
CV-4302 Mi44D-2(3)-3 CV-4303 M144D-2(4)-3
2-37
Line #: HLE-24 Service: Torus vent purge exhaust
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Reponse Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-1 H-2 H-3
H-4
BP-4501, R2 BP-4502, R2 BP-4503, RI BP-4503A, RI BP-4504, R2
2) Valve Vendor Print Numbers
CV-4300 CV-4301
M144D-2(1)-3 M144D-2(2)-3
Line #: HLE-25 Service: Containment purge (supply)
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Reponse Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-5 H-6 H-7
4505/0 4506/1 4507
2) Valve Vendor Print Numbers
M144D-2 (6)-3 M144D-9-4
CV-4306 CV-4307
2-38
Line #: HLE-26 Service: Torus purge (supply)
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-l90 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-8 4508/2 & 4508A/1
2) Valve Vendor Print Number
CV-4308 M144D-9-4 & M144D-2(7)-3
Line #: HLE-27 Service: Torus Vacuum breaker line
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric cannot be found
1) Hanger Drawing Numbers
H-9 BP-4509 R2 BP-4509A Rl
H-10 BP-4510 R2 BP-4510A RI
2) Valve Vendor Print Numbers
CV-4304 M144D-2(9)-3 CV-4305 M144D-2(8)-3
2-39
Line #: HLE-28 Service: Reactor building cooling water penetration supply
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
None
2) Valve Vendor Print Number
MO-4841 B M137B-15-6
Line #: HLE-29 Service: Reactor building cooling water penetration return
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
None
2) Valve Vendor Print Number
MO-4841 A M137B-16-4
2-40
List of Design Documents for Seismic Analysis of Group 2 Lines
Line #: DBB-2 Service: RHR heat exchange discharge
Design Input Documents:
Piping Class/Summary Sheet: DBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-20B BP 9714, Rl
2) Valve Vendor Print Numbers
MO-1904 M133C-2(l)-1l
Line #: EBB-18 Service: Core spray pump discharge
Design Input Documents:
Piping Class/Summary Sheet: EBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-lOA BP 9726, R3 BP 9726A, RI
2) Valve Vendor Print Numbers
MO-2135 M133A-40-3
2-41
Line #: GBB-4 Service: RHR pump discharge
Design Input Documents:
Piping Class/Summary Sheet: GBB Seismic Response Spectra: See Piping Stress Isometric Drawings:
/M-190 FSAR Isometric Reconstructed
1) Hanger Drawing Numbers
BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP
1839, Ri 1839A, Ri 1839B, Ri 1840, Ri 1841, Ri 1842, R2 1842A, RI 1843, R2 1844, Ri 1854, R2 1854A, Ri 2063, Ri 1855, R2 1856, R2 1857, Ri 1858, Ri 2070, R2 1859, R2 1860, Ri 1861, R3 2064, Ri 1862, R2 1864, R3 1864, R3 1865, R3 2069, Ri 9713, Ri 9713, Ri 2066, Ri 2065, Ri
2) Valve Vendor Print Numbers
M137A-1-4 M137A-10-4 MI37A-1-4 MI37A-10-4 M137B-4-3 M137B-4-3 MI37A-9-6
2-42
H-1
H-2 H-3 H-4.
H-5 H-6 H-2
SS-210 H-3 H-4 SR-5 SR-6 SS-217 H-7 H-8 H-9 SS-211 H-10 H-ll1 H-12 H-13 SS-216 H-200
SS-213 SS-212
V-20-1 V-20-2 V-20-3 V-20-4 V-20-14 V-20-12 MO 2030
Line #: GBB-7 Service: RHR pump discharge
Design Input Documents:
Piping Class/Summary Sheet: GBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-7 BP 1845, Ri SS-223 BP 2076, Ri SS-224 BP 2077, Ri
BP 2077A, RI BP 2077B, RI
2) Valve Vendor Print Numbers
MO 2029 M137A-13-4
Line #: GBB-9 Service: RHR heat exchange discharge
Design Input Documents:
Piping Class/Summary Sheet: GBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-1 BP 1853, Ri BP 1853A, Ri
2) Valve Vendor Print Numbers
MO 2031 M137A-13-4
2-43.
Line #: GBB-14 Service: Core spray pump discharge
Design Input Documents:
Piping Class/Summary Sheet: GBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
SR-18 BP 1794, Rl H-1 BP 1739, Ri H-2 BP 1740, Ri H-3 BP 1741, R2 H-4 BP 1742, R2
BP 1742A, Ri SS-20 BP 1796, Ri
BP 1796A, R2 H-5 BP 1743, Ri H-6 BP 1744, R3 SR-21 BP 1797, Ri H-7 BP 1745, Ri
BP 1745A, R2 H-8 BP 1746, R2 H-9 BP 1747, R2
BP 1747A, Ri SS-22 BP 1798, Ri
BP 1798A, Ri H-10 BP 1748, R2
2) Valve Vendor Print Numbers
V-21-10 MI37A-2-4 MO 2132 MI51A-3-4
2-44
Line #: GBB-16 Service: RHR pumps - test line; RHR heat exchange
discharge
Design Input Documents:
Piping Class/Summary Sheet: GBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
SS-214 BP 2067, R2 H-29 BP 1944, Ri H-93 BP 1945, Ri H-94 BP 1946, Ri H-95 BP 1947, R1 H-96 BP 1948, Ri H-97 BP 1949, Ri H-98 BP 1950, Ri H-99 BP 1951, Ri H-100 BP 1952, Ri H-101 BP 1953, Ri H-102 BP 1954, Ri H-103 BP 1955, Ri H-104 BP 1956, Ri H-105 BP 1957, Ri H-106 BP 1958, Ri H-107 BP 1959, Ri H-91 BP 1943, Ri H-90 BP 1942, Ri H-88 BP 1941, Ri H-89 BP 1940, Ri
BP 1940A, Ri H-87 BP 1939, Ri H-86 BP 1938, Ri
2) Valve Vendor Print Numbers
V-20-5 MI37A-3-4 MO-2036 MI37B-10-3 CV-2037 MI44A-126-2 MO-2009 MI37B-013-4 MO-2038 MI37B-012-4 V-20-7 MI37B-5-3 V-20-8 M137A-4-4 V-20-9 MI37B-5-3 V-20-6 MI37A-4-4
2-45.
Line #: GBC-1 Service: Pumphouse RHR SW
Design Input Documents:
Piping Class/Summary Sheet: GBC/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-57 BP 2557, Ri H-58 BP 2558, R2 H-59 BP 2559, Ri SS-56 BP 6156, Ri
BP 6156A, RI SS-57 BP 6157, Ri H-51 BP 2551, RO H-52 BP 2552, Ri H-53 BP 2553, R2 H-54 BP 2554, Ri H-55 BP 2555, Ri H-56 BP 2556, Ri H-6 BP 2506, R2
BP 2506A, R2 SR-85 BP 6185, Ri H-5 BP 2505, Ri SR-58 BP 6158, Ri H-4 BP 2504, Ri
BP 2504A, Ri H-3 BP 2503, RI H-2 BP 2502, Ri H-1 BP 2501, Ri
BP 2501A, Ri SR-84 BP 6184, Ri
2) Valve Vendor Print Numbers
V-46-28 Mi37A-44-2 V-46-29 MI37A-44-2 V-46-30 MI37-35-3 V-46-26 M137-35-3 V-46-31 M137-45-2 V-46-27 MI37-45-2 V-13-24 M137A-44-2 V-13-23 MI37A-44-2
2-46
Line #: Service:
GBC-3 RHR SW return
Design Input Documents:
Piping Class/Summary Sheet: GBC/M-190 Seismic Pesponse Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-29 SR-67 SR-65 H-30
SR-6 6
BP 2529, Ri BP 6167, Ri BP 6165, Ri BP 2530, Ri BP 2530A, R2 BP 6166, Ri
2) Valve Vendor Print Numbers
V-13-25 MO-2046
MI37A-44-2 M144A-120-4
Line #: Service:
GLE-6 Core spray pump discharge
Design Input Documents:
Piping Class/Summary Sheet: GLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-16 BP 1754, Ri
2) Valve Vendor Print Numbers
MO-2005 MO-2006 MO-2007
MI51A-006-4 M137A-017-4 MI51A-007-4
2-47
Line #: HBB-1 Service: Core spray pump suction
Design Input Documents:
Piping Class/Summary Sheet: Seismic Response Spectra: Piping Stress Isometric Dra
1) Hanger Drawing Numbers
H-1 BP 1708, R2 H-2 BP 1709, R2 H-3 BP 1710, Ri H-4 BP 1711, Ri H-5 BP 1712, R2 SS-9 BP 1785, R2 SS-10 BP 1786, Ri H-6 BP 1713, R3
BP 1713A, R2 H-7 BP 1714, R2
BP 1714A, R2
2) Valve Vendor Print Numbers
MO-2120 V-21-2
HBB/M-190 See FSAR
wings: Isometric Reconstructed
M137A-015-3 M137A-011-4
- 2-48 ,
Line #: HBB-24 Service: RHR pump suction
Design Input Documents:
Piping Class/Summary Sheet: Seismic Response Spectra: Piping Stress Isometric Dra
1) Hanger Drawing Numbers
BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP
2082, Ri 1826, R2 1827, R2 2081, Ri 1828, R2 1828A, Ri 1828B, Ri 1801, R3 1801A, R2 9660, R3 9660A, R2 1802, R3 1802A, R2 1803, R3 1829, R2 1830, R2 1831, R2 1832, R2 1833, R2 2080, Ri
HBB/M-190 See FSAR
wings:
H-14 H-15 H-16 H-17 H-18 H-4
SS-221
H-5
SS-222 H-6-1 H-7-1
H-8-1
H-9-1 H-10-1
Isometric Reconstructed
BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP
1834, R2 1835, R2 1836, R2 1837, R2 1838, R2 1804, R2 1804A, Ri 2074, Ri 2074A, Ri 1805, R2 1805A, R1 2075, Ri 1806, R2 1807, R3 1807A, RI 1808, R2 1808A, R2 1809, R2 1810, R3 1810A, Ri
2) Valve Vendor Print Numbers
MI51A-ll-3 MI37A-18-4 M137A-18-4
MO-2015 MO-2016
MI37A-18-4 MI37A-18-4
2-49.
SS-229 H-6 H-7 SS-228 H-8
H-1
H-lA
H-2
H-3 H-9 H-10 H-11 H-12 H-13 SS-227
MO-2069 MO-2012 MO-2011
Line #: HBB-30 Service: Residual heat removal (reactor building)
Design Input Documents:
Piping Class/Summary Sheet: HBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-202 H-203 H-204 SS-205 SS-206 H-207 SR-208 H-209 SS-245
BP BP BP BP BP BP BP BP BP
2055, 2056, 2057, 2058, 2059, 2060, 2061, 2062, 2098,
2) Valve Vendor Print
Rl R3 R2 Rl Rl R3 R2 R2 Rl
Numbers
None
2-50.
Line #: HBD-25 Service: Emergency service water
Design Input Documents:
Piping Class/Summary Sheet: Seismic Response Spectra: Piping Stress Isometric Dra
1) Hanger Drawing Numbers
BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP
2591, Ri 2592, R2 2593, R3 2594, R2 2595, R3 2616, Ri 2617, Ri 2618, Ri 6245, Ri 2619, Ri 2620, Ri 2621, RI 2622, Ri 2623, Ri 2624, Ri 2625, Ri 2626, Ri 2627, Ri 2628, RI 2629, R2 2630, R2 2631, Ri 2631A, Ri
HBD/M-190 See FSAR
wings: Isometric Reconstructed
H-114 H-ll5 SA-148 H-i16 H-117 H-ll8 FH-4 H-62
H-63
H-64 H-65 H-66 H-67 FH-1 H-68 H-69 H-70 H-71 H-71 H-72
H-119
BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP
7051, Ri 7052, Ri 6248, Ri 7053, Ri 7054, R2 7055, R2 9659, Ri 2699, R2 2699A, Ri 2699B, Ri 7000, Ri 7000A, Ri 7001, Ri 7002, Ri 7003, Ri 7004, Ri 7093, Ri 7005, Ri 7006, Ri 7007, R2 7008, R2 7008, R2 7009, R3 7009A, R1 7056, Ri
2) Valve Vendor Print Numbers
MI35A-033-3 Mi35A-031-2 M135A-031-2 M135A-004-8 M135A-033-3 MI35A-033-3
V-13-38 V-69-70 V-69-71 MO-2039B V-13-45
MI35A-031-2 M135A-004-8 MI35A-006-5 M135A-034-2 MI35A-31-2
2-51
H-7 H-8 H-9 H-10 H-ll H-1 H-2 H-3 SG-145 H-4 H-5 H-6 H-7-1 H-8-1 H-9-1 H-10-1 H-11-1 H-12 H-13 H-14 H-15 H-16
V-46-18 V-46-19 V-46-20 V-46-23 V-13-37 V-13-36
Line #: HBD-27 Service: Emergency service water
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
BP 6205, Ri BP 6205A, Ri BP 6118, R2 BP 6118A, R2 BP 6118B, R2 BP 2656, Ri
SG-106
H-4 SR-107 H-5 H-6
BP 6206, Ri BP 6206A, R1 BP 2657, Ri BP 6207, Ri BP 2658, Ri BP 2659, Ri
2) Valve Vendor Print Numbers
M135A-68-1 M135A-32-3
Line #: HBD-29 Service: Emergency service water
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
BP 2632, Ri BP 2632A, Ri BP 2633, Ri BP 2634, R2 BP 2635, R2 BP 2636, Ri BP 7010, Ri BP 7011, Ri BP 6251, Ri BP 7012, Ri BP 7013, Ri BP 7014, Ri BP 7015, Ri
FR -2 H-79 H-80 H-81 H-82 H-83 SA-100 H-109 H-1 10 H-111 H-1 12 H-1 13
BP BP BP BP BP BP BP BP BP BP BP BP
7092, 7016, 7017, 7018, 7019, 7020, 6200, 7046, 7047, 7048, 7049, 7050,
Ri Ri Ri Ri R2 R2 R2 Ri Ri Ri Ri Ri
2) Valve Vendor Print Numbers
V-13-125 MI35C-1-1 V-13-39 M135A-31-2 TCV-6924B M90-4-1
MO-2078 CV-1956 V-1 3-46
M135A-34-2 MI35A-67-1 M135A-32-3
2-52
SR-105
SR-6
H-3
CV-2081 V-1 3-34
H-1
H-2 H-3 H-4 H-5 H-73 H-74 SA-151 H-75 H-76 H-77 H-78
Line #: HBD-162 Service: Chilled water
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
SA-20 BP 8020, RI H-21 BP 8021-3, Ri H-22 BP 8022-4, Ri H-23 BP 8023-4, Ri H-24 BP 8024, Ri
2) Valve Vendor Print Numbers
V-69-49 MI35A-4-8 V-69-51 M135A-4-8
Line #: HLE-3 Service: Core spray pump
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
None
2) Valve Vendor Print Numbers
MO-2146 MI51A-010-3
2-55
Line #: HLE-8 * Service: RHR pump suction
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
None
2) Valve Vendor Print Numbers
None
Line #: HLE-11 Service: Core spray pump discharge
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-17 BP 1755, Ri
2) Valve Vendor Print Numbers
None
Line #: HLE-14 Service: Core spray pump discharge
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
H-13 BP 1751, Ri H-14 BP 1752, Rl H-15 BP 1753, R3
2) Valve Vendor Print Numbers
None
.2-56
Line #: HLE-17 Service: RHR heat exchange discharge
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
None
2) Valve Vendor Print Numbers
None
Line #: HBD-192 Service: HPCI lube oil piping
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Isometric Reconstructed
1) Hanger Drawing Numbers
FH-l BP 9761, R1 FH-2 BP 9762, R1
2) Valve Vendor Print Numbers
None
2-57
List of Design Documents for Seismic Analysis of Group 3 Lines
Line #: DBA-2 Service: Turbine main steam
Design Input Documents:
Piping Class/Summary Sheet: DBA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-266
1) Hanger Drawing Numbers
H-40 BP 160, Ri H-41 BP 161, R2 H-42 BP 162, Ri
BP 162A, Ri H-43 BP 163, Ri H-44 BP 164, Ri H-45 BP 165, Ri H-46 BP 166, Ri H-55 BP 175, R2 SS-137 BP 7857, Ri H-54 BP 174, R1 H-53 BP 173, Ri H-52 BP 172, Ri H-51 BP 171, Ri H-50 BP 170, Ri H-49 BP 169, Ri H-48 BP 168, Ri
BP 168A, Ri H-47 BP 167, Ri H-56 BP 176, Ri H-57 BP 177, Ri
2) Valve Vendor Print Numbers
MO-1044 M150-3-5 V-03-01 M1504-2-1 MO-1043 M150-3-5
2-58
Line #: DBA-3 Service: Steam to HPCI turbine
Design Input Documents:
Piping Class/Summary Sheet: DBA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-344
1) Hanger Drawing Numbers
H-5 BP-1571 BP-1571A BP-1571B
2) Valve Vendor Print Numbers
MO-2238 MI52A-31-2
Line #: DBA-4 Service: Steam to RCIC turbine from main steam
Design Input Documents:
Piping Class/Summary Sheet: DBA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: M-706, SA-7222
1) Hanger Drawing Numbers
H-1 BP 1661, R4 BP 1661A, R3
H-2 BP 1662, R4 BP 1662A, RI BP 1662B, R3
H-3 BP 1663, R2 BP 1663A, R3
SS-34 BP 6034, R2 BP 6034A, RI BP 6034B, RI
SS-35 BP 6035, R2 BP 6035A, R2 BP 6035B, R2 BP 6035C, R2
SS-36 BP 6036, R2
2) Valve Vendor Print Numbers
MO-2400 M133A-6-5 MO-2401 M133A-13-4
2-59
I
Line #: DBA-5 Service: RHR pump discharge from MO-1901 to reactor
head spray
Design Input Documents:
Piping Class/Summary Sheet: DBA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-353
1) Hanger Drawing Numbers
H-1 BP 2120, R2 BP 2120A, Ri BP 2120B, RI
H-2 BP 2121, R2 BP 2121A, Ri BP 2121B, Ri
H-3 BP 2122, R2 H-4 BP 2123, R2
BP 2123A, RI H-5 BP 2124, R2
BP 2124A, Ri H-6 BP 2125, R2
BP 2125, Ri H-7 BP 2126, R2
BP 2126A, Ri SS-31 BP 6031, R3
BP 6031A, R2 BP 6031B, R2
SS-37 BP 6037, R3 BP 6037A, R2
SS-38 BP 6038, R4 BP 6038A, RI
SS-47 BP 6047, R3
2) Valve Vendor Print Numbers
V-19-5 M133A-1-5 MO-1901 M133A-3-7
2-60
Line #: DBA-6 Service: Control rod hydraulic from reactor isolation
valve to line DCA-16
Design Input Documents:
Piping Class/Summary Sheet: DBA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-355
1) Hanger Drawing Numbers
H-1 BP 4410, Ri BP 4410A, Ri BP 4410B, R1
H-2 BP 4411, Ri BP 4411A, RI
H-3 BP 4412, Ri BP 4412A, R1 BP 4412B, Ri
H-4 BP 4413, Ri BP 4413A, Ri
SR-28 BP 6028, Ri BP 6028A, Ri BP 6028B, Ri
SS-29 BP 6029, R2 BP 6029A, R2
SS-30 BP 6030, Ri BP 6030A, Ri BP 6030B, Ri
H-30 BP 4430, Ri H-31 BP 4431, Ri H-32 BP 4432, Ri H-33 BP 4433, R2 SA-34 BP 4434, R2
2) Valve Vendor Print Numbers
V-17-51 M133A-11-3 V-17-52 M133A-8-4 V-17-53 M133A-8-4 V-17-54 M133A-53-3
2-61
Line #: DCA-2 Service: RHR pump discharge from isolation valve 2008
Design Input Documents:
Piping Class/Summary Sheet: DCA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-331
1) Hanger Drawing Numbers
None
2) Valve Vendor Print Numbers
None
Line #: DCA-6 Service: Cleanup pump suction from reactor recirculation
pump suction line
Design Input Documents:
Piping Class/Summary Sheet: DCA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-337
1) Hanger Drawing Numbers
H-1 BP 3642, R2 BP 3642A, R1
H-2 BP 3643, R2 BP 3643A, R1
H-4 BP 3645, R2 SR-51 BP 6051, R1
BP 6051A, Rl SG-52 BP 6052, R1
BP 6052, R1 SS-48 BP 6048, R2 SS-49 BP 6049, R1 SS-50 BP 6050, Ri
BP 6050A, R1
2) Valve Vendor Print Numbers
V-2701 M134A-1-5 MO-2700 M134A-12-1
.2-62
Line #: Service:
DCA-8 (see DLA-7) Core spray discharge from stop valve 2142 to upper reactor spray
Design Input Documents:
Piping Class/Summary Sheet: DCA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-334
1) Hanger Drawing Numbers
None
2) Valve Vendor Print Numbers
None
Line #: Service:
DCA-9 (part of DLA-8) Core spray discharge from stop valve 2143 to lower reactor spray
Design Input Documents:
Piping Class/Summary Sheet: DCA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-334
1) Hanger Drawing Numbers
None
2) Valve Vendor Print Numbers
None
.2-63
Line #: DLA-1 Service: HPCI discharge to FW line upstream of MO-2312
Design Input Documents:
Piping Class/Summary Sheet: DLA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: M-701
1) Hanger Drawing Numbers
SR-10 BP 1576, Ri H-12A BP 1561, R2 H-12 BP 1560, Ri
BP 1560A, Ri BP 1560B, Ri
SR-8 BP 1574, Ri SR-9 BP 1575, R2
2) Valve Vendor Print Numbers
CV-2313 M152B-1-2 MO-2312 MI52A-9-3
Line #: DLA-3 Service: Steam to HPCI turbine
Design Input Documents:
Piping Class/Summary Sheet: DLA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-344
1) Hanger Drawing Numbers
H-1 BP 1567, R3 BP 1567A, Ri BP 1567B, Ri
H-2 BP 1568, R4 BP 1568A, Ri
H-3 BP 1569, R4 BP 1569A, Ri
SS-1 BP 6001, R1 BP 6001A, RO
SS-2 BP 6002, R3 BP 6002A, R2
SS-3 BP 6003, R2 BP 6003A, RI BP 6003B, R1
SR-23 BP 1589, R1 BP 1589A, Ri
2) Valve Vendor Print Numbers
None
2-64
Line #: DLA-4 (see DCA-5) Service: RHR pump suction from reactor recirculation
line to MO-1909
Design Input Documents:
Piping Class/Summary Sheet: DLA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-330
1) Hanger Drawing Numbers
H-9 BP 2109, R2 BP 2109A, RI
H-10 BP 2110, R3 BP 2110A, R1
H-ll BP 2111, R2 BP 2111A, Ri BP 2111B, R2 BP 2111C, R2
H-12 BP 2112, R2 BP 2112A, Ri BP 2112B, R1 BP 2112C, R2
H-13 BP 2113, R2 BP 2113A, RiBP 2113B, Ri BP 2113C, Ri
SS-14 BP 6014, R4 BP 6014A, Ri BP 6014B, Ri
SS-15 BP 6015, R3 BP 6015A, R2
2) Valve Vendor Print Numbers
MO-1908 M152A-30-3 ZS-1993 M152A-2-4 MO-1909 M152A-30-3
Line #: DCA-5 (part of DLA-4) Service: RHR pump suction from reactor recirculation
pump suction line to stop valve
Design Input Documents:
Piping Class/Summary Sheet: DCA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-330
1) Hanger Drawing Numbers
None
2) Valve Vendor Print Numbers
None 2-65
Line #: DLA-5 Service: RHR discharge from MO-2003 through penetration
to valve ZS-2008
Design Input Documents:
Piping Class/Summary Sheet: DLA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-331
1) Hanger Drawing Numbers
BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP
2101, R2 2101A, R2 2102, R3 2102A, Rl 2103, R2 2103A, Ri 2104, R3 2104A, RI 2114, Ri 2114A, RI 2114B, RI 6010, R3 6010A, R2 6010B, R2 6010C, R2 6011, R2 6011A, R2 6011B, R2 6011C, R2 6011D, Ri
2) Valve Vendor Print Numbers
CV-2002 ZS-2008
M152B-27-1-2 M152A-1-5
2-66
H-1
H-2
H-3
H-4
H-14
SS-10
SS-11
Line #: DLA-6 Service: RHR discharge from MO-1905 through penetration
to valve ZS-1907
Design Input Documents:
Piping Class/Summary Sheet: DLA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: M-332
1) Hanger Drawing Numbers
H-5 BP 2105, R3 BP 2105A, R3
H-6 BP 2106, R3 BP 2106A, R2
H-7 BP 2107, R3 H-8 BP 2108, R3 H-15 BP 2115, Ri
BP 2115A, R1 SS-12 BP 6012, R2
BP 6012A, R2 SS-13 BP 6013, R3
BP 6013A, R2 BP 6013B, R2
2) Valve Vendor Print Numbers
CV-1906 ZS-1907
M152B-27(l)-2 M152A-1-5
2-67
Service: Core spray discharge from CV-2117 to reactor spray valve
Design Input Documents:
Piping Class/Summary Sheet: DLA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-334
1) Hanger Drawing Numbers
H-1 BP 1777, R3 BP 1777A, R1 BP 1777B, R1 BP 1777C, R1
H-2 BP 1778, Ri BP 1778A, R2 BP 1778B, Ri BP 1778C, Ri
H-3 BP 1779, Ri
2) Valve Vendor Print Numbers
CV-2118 M152B-6-(1)5 ZS-2142 M152A-3-3 MO-2117 M152A-5-4 V-21-64 M141-55(1)-1 V-21-65 M141-55(1)-l V-21-62 M141-55(1)-l V-21-63 M141-55(1)-1
Line #: DLA-8 (see DCA-9) Service: Core spray discharge from CV-2137 to reactor
spray valve
Design Input Documents:
Piping Class/Summary Sheet: DLA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-334
1) Hanger Drawing Numbers
H-4 BP 1780, R3 H-5 BP 1781, R2 H-6 BP 1782, R2
2) Valve Vendor Print Numbers
ZS-2143 M152A-3-3 CV-2138 M152B-6-1-5 MO-2137 M152A-5-4
2-68
Line #: DLA-7 (part of DCA-8)
Line #: EBB-14 Service: HPCI, RCIC
Design Input Documents:
Piping Class/Summary Sheet: EBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: M-702
1) Hanger Drawing Numbers
H-1 BP 1508, Ri SR-18 BP 1584, Ri H-2 BP 1509, R2 SR-17 BP 1583, Ri SS-16 BP 1582, Ri
BP 1582A, Ri BP 1582B, Ri
H-3 BP 1510, Ri BP 1510A, R1
H-4 BP 1511, R3 SS-16A BP 9654, Ri H-5 BP 1512, R3 H-6 BP 1513, R3 H-7 BP 1514, R4 SS-15 BP 1581, R2 H-8 BP 1515, R3 H-9 BP 1516, R2 H-10 BP 1517, R3 H-11 BP 1518, R3 H-12 BP 1519, R3 H-13 BP 1520, R3 SS-14 BP 1580, R2 H-14 BP 1521, Ri
BP 1521A, Ri SS-13 BP 1579, R3
BP 1579A, Ri H-15 BP 1522, Ri H-16 BP 1523, R2
2) Valve Vendor Print Numbers
MO-2202 M133A-9-5 MO-2239 MI52A-8-3
2-69
Line #: EBB-15 Service: RCIC turbine steam
Design Input Documents:
Piping Class/Summary Sheet: EBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: M-706-H
1) Hanger Drawing Numbers
BP BP BP BP BP BP BP BP BP BP BP BP BP BP
1607, R2 1608, R2 1609, R2 9724, Ri 1610, R2 1610A, Ri 1611, R2 1611A, Ri 1612, R2 1612A, Ri 1613, R2 1613A, R2 1614, R2 1615, R2
H-10 H-11
H-12
H-13 H-14
H-15 H-16 SR-13 SR-14
BP 1616, R2 BP 1644, R2 BP 1644A, R2 BP 1645, R2 BP 1645A, RI BP 1645B, Ri BP 1646, Ri BP 1647, Ri BP 1647A, Ri BP 1648, Ri BP 1679, R2 BP 1673, R2 BP 1674, R4 BP 1674A, R2
2) Valve Vendor Print Numbers
MI33A-13-14 MI33A-4-6
.2-70
H-1 H-2 H-3 H-3A H-4
H-5
H-6
H-7
H-8 H-9
MO-2401 MO-2404
Line #: EBD-2 Service: Main steam
Design Input Documents:
Piping Class/Summary Sheet: EBD/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-267
1) Hanger Drawing Numbers
H-98 SR-159 SS-160
H-34 SA-161
H-100
H-101 H-102 H-103 H-67 H-70 H-71 H-72 H-73 H-74 H-75
H-76 H-77 H-78
H-79 H-80 H-81 H-82 H-83 H-84 SA-85 H-17 H-18 H-19 H-20 SR-148 SR-149 H-22
BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP
7818, Ri 7879, Ri 7880, Ri 7880A, Ri 150, R2 7881, R2 7881A, Ri 7820, Ri 7820A, Ri 7820B, Ri 7821, Ri 7822, Ri 7823, Ri 189, Ri 190, Ri 191, Ri 192, R2 193, Ri 194, Ri 195, Ri 195A, Ri 196, Ri 197, Ri 198, R2 198A, Ri 199, R2 7800, Ri 7801, Ri 7802, Ri 7803, Ri 7804, Ri 7805, R3 133, R3 134, R3 135, R2 136, R2 7868, Ri 7869, Ri 138, Ri
2-71
SR-150 SS-151 SR-155 H-25 H-24 SS-153 SS-154
H-95 SG-156
SG-157 SA-158
FH-1 FH-2 SR-138 SR-139 SR-ll0
SR-134 H-8 H-23 SS-2
H-18 SS-114 H-5 H-6 H-19 SS-115
SS-116 H-9 H-10 SR-111
BP 7870, Ri BP 7871, Ri BP 7875, Ri BP 141, R3 BP 140, R3 BP 7873, Ri BP 7874, Ri BP 7874A, Ri BP 7815, Ri BP 7876, R2 BP 7876A, Ri BP 7877, R2 BP 7878, R2 BP 7878A, Ri BP 9696, Ri BP 9697, Ri BP 7858, Ri BP 7859, Ri BP 7830, R2 BP 7830A, R1 BP 7854, R2 BP 108, R3 BP 9735, R2 BP 6102, R3 BP 6102A, Ri BP 157, R3 BP 7834, R2 BP 105, R3 BP 106, R3 BP 158, R3 BP 7835, R3 BP 7835A, R2 BP 7835B, R2 BP 7836, R3 BP 109, R3 BP 110, R3 BP 7831, R2 BP 7831A, Ri
Line #: EBD-2 (page 2 of 2) Service: Main steam
1) Hanger Drawing Numbers (continued)
SR-135 BP 7855, R2 H-12 BP 112, R3 H-22 - BP 9734, R2 SS-1 BP 6101, R3
BP 6101A, R3 BP 6101B, R2
H-20 BP 159, R3 SS-117 BP 7837, R2 SS-118 BP 7838, R2 H-13 BP 113, R3 SR-112 BP 7832, R2
BP 7832A, R1 H-14 BP 114, R4 SR-136 BP 7856, R2 H-16 BP 116, R3 H-21 BP 9733, R2 SS-3 BP 6103, Ri
BP 6103A, RI BP 6103B, R1
SS-4 BP 6103A, Ri BP 6103B, RI BP 6103, Ri
H-17 BP 156, R3 SS-113 BP 7833, R3
BP 7833A, R2 H-1 BP 101, R3 H-2 BP 102, R3 SR-109 BP 7829, R2
BP 7829A, R1 BP 7829B, R1
SR-133 BP 7853, R2 H-4 BP 104, R4 H-24 BP 9736, R2
2) Valve Vendor Print Numbers
MO-1054 M150A-4-5 MO-1055 M150A-4-5 MO-9148 M1-N35-36-2 CV-1097B M1-N35-43 V-03-04 MI50A-1-4 V-03-05 M150A-1-4
2-72
Line #: GBC-6 Service: Steam line relief valve PS-4402 discharge
to torus
Design Input Documents:
Piping Class/Summary Sheet: GBC/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-346
1) Hanger Drawing Numbers
BP 3529, R2 BP 3529A, Rl BP 3529B, RI BP 3529C, R2 BP 6053, R2 BP 6053A, Rl BP 6053B, Rl BP 6053C, R1
SS-16
SS-17
BP 6016, R2 BP 6016A, R1 BP 6017, Ri BP 6017A, R1 BP 3531, R2 BP 3531A, R1
2) Valve Vendor Print Numbers
PSV-4439C M14-6-66-3
Line #: GBC-7 Service: Steam line relief from PSV-4407
Design Input Documents:
Piping Class/Summary Sheet: GBC/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-347
1) Hanger Drawing Numbers
BP 3532, R3 BP 3532A, Rl BP 3532B, Rl BP 3532C, RI BP 3533, R3 BP 3533A, R1 BP 3533B, Rl
H-6
SS-18
SS-19
BP 3534, R3 BP 3534A, RI BP 3534B, R1 BP 6018, R2 BP 6018A, R1 BP 6019, R2
2) Valve Vendor Print Numbers
PSV-4439E M14-6-66-3
H-1
SR-5 3
H-4
H-5
2-73
Line #: GBC-8 Service: Steam line relief from PSV-4406
Design Input Documents:
Piping Class/Summary Sheet: GBC/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-348
1) Hanger Drawing Numbers
H-7 BP 3535, R2 BP 3535A, RI BP 3535B, Rl BP 3535C, R2
H-8 BP 3536, R2 BP 3536A, R1
H-9 BP 3537, R2 BP 3537A, Ri BP 3537B, R1
H-10 BP 3538, R2 BP 3538A, RI
SS-20 BP 6020, R2 BP 6020A, RI
SS-21 BP 6021, R2 SS-44 BP 6044, RI
BP 6044A, RI SS-45 BP 6045, Ri
BP 6045A, Ri BP 6045B, R1
SS-46 BP 6046, Ri BP 6046A, Ri
2) Valve Vendor Print Numbers
PSV-4439F M146-66-3
2-74
Line #: GBC-9 Service: Steam line relief from PSV-4400
Design Input Documents:
Piping Class/Summary Sheet: GBC/M-190 Seismic Response Spectra: See FSAR Piping Sfress Isometric Drawings: SKM-349
1) Hanger Drawing Numbers
H-11 BP 3539, R2 BP 3539A, Ri BP 3539B, RI
H-12 BP 3540, R2 BP 3540A, Ri
H-13 BP 3541, R2 BP 3541A, RI
H-14 BP 3542, R2 BP 3542A, Ri
SS-22 BP 6022, Ri BP 6022A, Ri BP 6022B, Ri
SS-23 BP 6023, Ri BP 6023A, Ri
SS-41 BP 6041, Ri BP 6041A, Ri
SS-42 BP 6042, R2 BP 6042A, Ri
SS-43 BP 6043, R2 BP 6043A, Ri BP 6043B, Ri
2) Valve Vendor Print Numbers
PSV-4439A M146-66-3
2-75
Line #: GBC-10 Service: Steam line relief from PSV-4401
Design Input Documents:
Piping Class/Summary Sheet: GBC/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-350
1) Hanger Drawing Numbers
BP 3543, R2 BP 3543A, Rl BP 3543B, RI BP 3544, R2 BP 3544A, R2 BP 6024, R2 BP 6024A, RI
SS-25
SS-39
SS-40
BP 6025, R2 BP 6025A, RI BP 6039, Ri BP 6039A, RI BP 6040, R2 BP 6040A, Ri BP 6040B, Ri BP 6040C, R2
2) Valve Vendor Print Numbers
PSV-4439B M146-66-3
Line #: GBC-ll Service: Steam line relief from PSV-4405
Design Input Documents:
Piping Class/Summary Sheet: GBC/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-351
1) Hanger Drawing Numbers
BP 3545, R2 BP 3545A, Ri BP 3545B, Ri BP 3546, R2 BP 3546A, R1 BP 3547, R2 BP 3547A, R1 BP 3548, R2 BP 3548A, RI BP 3548B, Ri
SS-26
SS-27 SS-32
SS-33
BP 6026, Ri BP 6026A, Ri BP 6027, Ri BP 6032, R3 BP 6032A, R3 BP 6032B, Ri BP 6033, Ri BP 6033A, R1 BP 6033B, R1 BP 6033C, RI
2) Valve Vendor Print Numbers
PSV-4439D M146-66-3
H-15
H-16
SS-24
H-17
H-18
H-19
H-20
2-76
Line #: GLE-7 Service: RHR pump discharge to containment coil from MO-2001
through MO-2000
Design Input Documents:
Piping Class/Summary Sheet: GLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: M-720
1) Hanger Drawing Numbers
H-14 BP 1866, Ri H-15 BP 1867, Ri H-16 BP 1868, R3
BP 1868A, Ri H-17 BP 1869, R3
2) Valve Vendor Print Numbers
MO-2001 MI51A-1-5 MO-2000 MI51A-4-4
Line #: GLE-8 Service: RHR pump discharge to containment coil from MO-1903
through MO-1902
Design Input Documents:
Piping Class/Summary Sheet: GLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: M-721 reconstructed
1) Hanger Drawing Numbers
H-21 BP 1873, Ri H-22 BP 1874, R3
BP 1874A, Ri BP 1874B, R1
SS-239 BP 2092, Ri BP 2092A, RI BP 2092B, R1
SS-240 BP 2093, Ri H-23 BP 1875, R3 H-24 BP 1876, Ri
2) Valve Vendor Print Numbers
MO-1902 M151A-1-5 MO-1903 MI51A-4-4
.2-77
Line #: HBD-94 Service: Well water supply inside drywell loop A
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Reconstructed
1) Hanger Drawing Numbers
BP 5318, R2 BP 5318A, R2 BP 5319, R2 BP 5319A, R2 BP 5320, R2 BP 5320A, R2 BP 6242, Ri BP 6240, Ri BP 5321, R2 BP 5321A, R2 BP 6241, Ri BP 5305, R3 BP 5305A, R2 BP 5305B, R2 BP 5306, R2 BP 6119, R2 BP 6119A, RI BP 5307, R2
H-208
H-209
H-210 H-211
SG-138 SA-139 H-213
H-214
H-215
H-216
H-217
BP 5308, R2 BP 5308A, R2 BP 5309, R2 BP 5309A, R3 BP 5310, R2 BP 5311, R2 BP 5311A, R2 BP 6238, RI BP 6239, Ri BP 5313, R2 BP 5313A, R2 BP 5314, R2 BP 5314A, R2 BP 5315, R2 BP 5315A, R2 BP 5316, R2 BP 5315A, R2 BP 5317, R2
2) Valve Vendor Print Numbers
MI53-4-8
2-78
H-218
H-219
H-220
SA-142 SA-140 H-221
SA-141 H-205
H-206 SA-19
H-207
V-57-62
Line #: HBD-95 Service: Well water supply inside drywell loop B
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-668 also
reconstructed
1) Hanger Drawing Numbers
BP 5330, Ri BP 5330A, R2 BP 5331, R2 BP 5332, R2 BP 5333, R2 BP 5333A, R2 BP 5334, R2 BP 5334A, R2 BP 6237, Ri BP 6236, Ri BP 5335, R2 BP 5335A, R2 BP 6126, R2 BP 6126A, R2 BP 5336, R2 BP 5336A, R2
SA-135 H-222
H-223
H-224
SA-25
SG-134 H-227
H-228 H-229
BP BP BP BP BP BP BP BP BP BP BP BP BP BP
6235, Ri 5322, Ri 5322A, R2 5323, R2 5323A, R2 5324, R2 5324A, R2 6125, R3 6125A, R1 6234, Ri 5327, R2 5327A, R2 5328, R2 5329, R2
2) Valve Vendor Print Numbers
V-57-61 PSV-57-18B MO-5707B MO-5714B MO-5716B
M-135-4 M146-67-3 M144F-30-3 M144F-30-3 M144F-30-3
H-230
H-231 H-232 H-233
H-234
SA-137 SA-136, H-235
SA-26
H-236
2-79
Line #: HBD-115 Service: Drywell well water
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: EDS-0207884-115
1) Hanger Drawing Numbers
5187, R3 5187A, R2 5187B, Ri 5189, R2 5190, R2 5190A, R2 5191, R2 5192, R2 5192A, R2 5193, R2 5194, R2 5194, R2 5195, R2 5195A, R2 5196, R2 5196A, R2 5197, R3 5197A, R2 5198, R3 6152, R3 6152A, R1 6230 6229, Ri
H-199 H-200
H-201
FH-201A SA-1 31 SA-1 32 H-203
H-204
SA-133
BP 5199, R2 BP 5300, R2 BP 5300A, R2 BP 5301, R2 BP 5301A, R2 BP 9658, Ri BP 6231, Ri BP 6232, Ri BP 5303, R2 BP 5303A, R3 BP 5304, R3 BP 5304A, R3 BP 5304B, R3 BP 6233, Ri
2) Valve Vendor Print Numbers
MI35A-31-2
2-80
H-187
H-189 H-190
H-191 H-192
H-193 H-194
H-194
H-196
H-197
H-198 SA-52
SA-1 30 SR-1 29
BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP
V-5 7-6 6
Line #: HBD-116 Service: Well water return inside drywell loop B
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-670
1) Hanger Drawing Numbers
BP 5337, R2 BP 5337A, R2 BP 5338, R2 BP 5338A, R2 BP 5339, R2 BP 5339A, R2 BP 6180, Ri BP 5340, R2 BP 5341, R2 BP 5341A, R2 BP 5342, R2 BP 5343, R2 BP 5343A, R2BP 5344, R2 BP 5345, R2 BP 5345A, R2
H-246 H-247
H-248
SA-125 SA-126 H-250 H-251
H-252
H-253
SA-128 SA-127
BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP
5346, R2 5347, R2 5347A, R2 5348, R2 5348A, R2 5348B, R2 6225, Ri 6226, Ri 5350, R2 5351, R2 5399A, R2 5352, R2 5352A, R2 5353, R2 5353A, R2 6228, Ri 6227, Ri
2) Valve Vendor Print Numbers
M135A-67-1
.2-81
H-237
H-238
H-239
SA-80 H-240 H-241
H-242 H-243
H-244 H-245
V-57-65
Line #: HBD-64 Service: Drywell cooling water
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-673
1) Hanger Drawing Numbers
H-254 BP 5354, R2 BP 5354A, RI
H-255 BP 5355, R2 H-256 BP 5356, R3
BP 5356A, RI
2) Valve Vendor Print Numbers
None
-2-82
Line #: HBD-65 Service: Drywell cooling water
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-612
1) Hanger Drawing Numbers
H-257 BP 5357, R2 H-258 BP 5358, R2
BP 5358A, R2 H-259 BP 5359, R2 SA-76 BP 6176, R2
2) Valve Vendor Print Numbers
None
Line #: HLE-21 Service: Nitrogen to drywell valves
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: None
1) Hanger Drawing Numbers
None
2) Valve Vendor Print Numbers
None
2-83
Line #: HLE-30 Service: Drywell floor drains sump pump discharge
containment penetration
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-666
1) Hanger Drawing Numbers
H-200 BP 6700, Ri BP 6700A, R1
H-201 BP 6701, Ri H-156 BP 4156, Ri H-155 BP 4155, Ri H-154 BP 4154, Ri H-153 BP 4153, Ri SA-78 BP 6178, R2
2) Valve Vendor Print Numbers
CV-3704 M137B-24-5 CV-3705 M137B-22-4
Line #: HLE-31 Service: Drywell equipment drain sump pump discharge
containment penetration
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-671
1) Hanger Drawing Numbers
H-140 BP 4140, Ri SR-35 BP 6135, R2 H-139 BP 4139, Ri H-138 BP 4138, R2 H-137 BP 4137, R2 SA-36 BP 6136, R2
2) Valve Vendor Print Numbers
CV-3729 M137B-22-4 CV-3728 M137B-24-5
2-84
Line #: HLE-32 (see HLE-33) Service: Drywell cooling water well water supply penetration
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-667
1) Hanger Drawing Numbers
BP 5378, Ri BP 5379, Ri BP 5380, Ri BP 5381, Ri BP 5382, Ri BP 5383, Ri
H-284 H-285 SA-20 SA-21 H-362
BP 5384, Ri BP 5385, Ri BP 6120, R2 BP 6121, Ri BP 5462, Ri BP 5462A, R1
2) Valve Vendor Print Numbers
CV-5718A M137B-26-3 V-57-59 M137A-36-3 CV-5719A M137A-40-4
Line #: HLE-33 (part of HLE-32) Service: Drywell cooling water well water supply penetration
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-668
1) Hanger Drawing Numbers
BP 5376, R2 BP 5377, Ri BP 6123, Ri
H-361
SR-97
BP 5461, R2 BP 5461A, R2 BP 6197, Ri BP 6197A, Ri BP 6197B, Ri
2) Valve Vendor Print Numbers
CV-5718B M137A-62-1 V-57-58 M137A-36-3
CV-5719B M-137-24-1516-3 V-44-30 MI35A-67-1
2-85
H-278 H-279 H-280 H-281 H-282 H-283
H-276 H-277 SR-23
Line #: HLE-34 Service: Drywell cooling water well water return penetration
Design Input Documents:
Piping Class/Summary Sheet: Seismic Response Spectra:
HLE/M-190 See FSAR
Piping Stress Isometric Drawings:
1) Hanger Drawing Numbers
H-12 SA-49 SA-50
BP 5012, Ri - BP 6149, R2
BP 6150, Ri
H-260 H-6 SA-51
Reconstructed
BP 5360, Ri BP 5006, R2 BP 6181, Ri
2) Valve Vendor Print Numbers
M137B-24-5 MI35A-4-8 M137BC
CV-5704A CV-5703A
M137A-4-8 M137A-67-2
Line #: HLE-35 Service: Well water drywell
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: SKM-670
1) Hanger Drawing Numbers
BP 5031, Ri BP 5032, R3 BP 6179, Ri BP 6179A, Ri
H-33 SA-82 SA-83
BP 5033, BP 6182, BP 6183,
2) Valve Vendor Print Numbers
V-57-70 MI35A-4-8 CV-5703B M137B-24-5 CV-5704B M137A-62-1
V-57-60 V-44-31
M137A-67-2 M138-9-1
Line #: HLE-36 Service: Nitrogen purge supply to containment downstream
of FCI valves
Design Input Documents:
Piping Class/Summary Sheet: HLE/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: Reconstructed
1) Hanger Drawing Numbers
H-44 BP 4544, Ri H-45 BP 4545, Ri H-46 BP 4546, Ri
2) Valve Vendor Print Numbers
M137B-41-3 M137B-41-3
CV-4311 M137B-41-3
2-86
V-44-3 3 V-5 7-6 9 V-5 7-61
SA-31 H-32 SR-79
RI RI Ri
CV-4 312 CV-4 313
I
List of Design Documents for Seismic Analysis of Computer-Analyzed Safety-Related Small Pipe
Line #: CRD-524 Service: CRD scram discharge system
Design Input Documents:
Piping Class/Summary Sheet: -/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: DA-007
DA-009
1) Hanger Drawing Numbers
1 RCI DA-9, Sh 10-7884-M115 40-(10)-1 2 RCI DA-9, Sh 10-7884-M115 40-(10)-1 3 RCI DA-9, Sh 10-7884-M115 40-(10)-l 4 RCI DA-9, Sh lO-7884-M115 40-(10)-1 5 RCI DA-9, Sh lO-7884-M115 40-(10)-l 6 RCI DA-9, Sh l0-7884-M115 40-(10)-l 7 RCI DA-7, Sh 1-7884-M115-46-(l)-8 8 RCI DA-7, Sh 1-7884-M115-46-(l)-8 9 RCI DA-7, Sh 1-7884-M115-46-(l)-8 10 RCI DA-7, Sh 1-7884-M115-46-(l)-8 11 RCI DA-7, Sh 1-7884-M115-46-(1)-8 12 RCI DA-7, Sh 1-7884-M115-46-(l)-8 13 RCI DA-7, Sh 1-7884-M115-46-(l)-8
2) Valve Vendor Print Numbers
V-18-3 M115-46(l)-6 V-18-4 M115-46(1)-6 V-18-5 M115-46(1)-6
2-87
Line #: CRD-526 Service: CRD scram
Design Input Documents:
Piping Class/Summary Sheet: -/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: DA-007
1) Hanger Drawing Numbers
Hi H2 H3 H4 H5 H6 H7 H8 H9 HIO Hl H12 H13
PS3 PS3 PSI PSI PSI PSI PSI PSI PSI PSI PSI PSI PSI
DET DET DET DET DET DET DT DE T DE T DET DET DET DET
U U U U U U U U U U U U U
DA-007 DA-007 DA-007 DA-007 DA-007 DA-007 DA-007 DA-007 DA-007 DA-007 DA-007 DA-007 DA-007
2) Valve Vendor Print Numbers
None
Line #: DBA-1 Service: Drains from steam lines inside containment
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: 4043B
1) Hanger Drawing Numbers
Hi DETI FSK 4043, R6 DETC SKM 1607, RO PSI SKM 602, RO
H2 PSI SKM 602, RO DETC SKM 1607, RO
H3 PS2 SKM 602, RO SNUB 16A
H4 PS 2 SKM 602, RO Sh 107, SKM 1611, RO
2) Valve Vendor Print Numbers
V-14-7 MI23A-6-7
2-89
Line #: DBA-2(A) Service: Drains from steam lines
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-3939B, FSK-3973B,
FSK-3994B
1) Hanger Drawing Numbers
FSK-3973B FSK-3994B
Sh 46 Hi
Sh 47 H2
FSK-3994B
Hi
Sh 1
H13
H2
H3
H4
H5
DET B SKM 1609, Ri PS 1 SKM 602, RO DET C SKM 1607, RO
SKM 1611, RO PS 2 SKM 602, RO DET A SKM 1601, RO
PS 6 SKM 602, RO DET A SKM 1606, RO PS 1 SKM 602, RO DET B SKM 1609, Ri PS 2 SKM 602, RO SNUB 15A PS 2 SKM 602, RO DET C SKM 1607, RO PS 1 SKM 602, RO DET C SKM 1607, RO PS 1 SKM 602,RO DET A SKM 1606, RO PS 1 SKM 602, RO DET A SKM 1606, RO
H6 PS 1 SKM DET B SKM
H7 PS 1 SKM DET A SKM
H8 PS 1 SKM DET A SKM
H9 PS 1 SKM DET A SKM
H10 PS 2 SKM Hl PS 2 SKM
DET C SKM H12 PS 2 SKM
DET A SKM
602, RO 1609, RI 602, RO 1606, RO 602, RO 1606, RO 602, RO 1606, RO 1609, Ri 602, RO 1607, RO 602, RO 1606, RO
FSK-3939B
Hi PS 1 SKM DET A SKM
H2 PSi SKM DET A SKM
H3 DET 1 FSK Sh 40 SKM H4 DET 1 FSK
602, RO 1606, RO 602, RO 1606, RO 3939B, R4 1611, RO 3939B, R4
2) Valve Vendor Print Numbers
None
2-90.
Line #: Service:
DBA-2(B) Test connection and MSIV-LC system
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-487B
1) Hanger Drawing Numbers
SKM PS 2 SKM PS 2 SKM DET C SKM
SKM PS 2 SKM
SKM PS 2 SKM PS 2 SKM DET C SKM
SKM PS 2 SKM
SKM PS 2 SKM
SKM PS 2 SKM
SKM PS 2 SKM PS 2 SKM DET C SKM SNUB 15
SKM PS 2 SKM
1611, RO 602, RO 602, RO 1607, RO 1611, RO 602, RO 1611, RO 602, RO 602, RO 1607, RO 1611, RO 602, RO 1611, RO 602, RO 1611, RO 602, RO 1611, RO 602, RO 602,RO 1607, RO
1611, RO 602, RO
2) Valve Vendor Print Numbers
V-14-39 V-14-40 V-14-136 V-84-41 V-84-01 V-84-42 V-84-08 V-14-45 V-14-48 V-14-137
M-123A-6-7 M-123A-6-7 M141D-1-2 M141-55-(l)-2 M141D-21-1 M141D-21-1 M141D-21-1 M-123A-6 M123A-6-7 M141-55(1)-i
V-14-46 V-84-43 V-84-15 V-14-49 V-14-135 V-84-22 V-14-42 V-14-138 V-14-43 V-84-44
M-123A-6 MI41D-21-1 M141D-21-1 M123A-6-7 M141-55(1)-i M141D-21-1 M141-55(1)-i M141-55(1)-i M141-55(1)-i M141D-21-1
2-91
Sh 120
Hi
Sh 127
Sh 121
H2
Sh 126
Sh 122
Sh 125
Sh 124
H3
Sh 123
Line #: DBA-2(B) Service: Test connection and MSIV-LV system
Design Input Documents:
Piping Class/Summary She Seismic Response Spectra Piping Stress Isometric
1) Hanger Drawing Numbers
Hi PS 2 SKM 602, RO DET A SKM 1606, RO
H2 PS 2 SKM 602, RO DET C SKM 1607, RO SNUB-009800 FSK
H3 PS 2 SKM 602, RO DET C SKM 1607, RO
H4 PS 2 SKM 602, RO DET C SKM 1607, RO
H5 PS 2 SKM 602, RO DET A SKM 1606, RO
H8 PS 2 SKM 602, RO DET A SKM 1606, RO
H6 PS 2 SKM 602, RO DET C SKM 1607, RO
H7 PS 4 SKM 602, RO DET B SKM 1609, Ri
et: DBA/M190 See FSAR
Drawings: FSK-10026B
10026B
2) Valve Vendor Print Numbers
V-84-25 V-84-24 V-84-23 MO-8401B MO-8402B
M141D-20-1 M141D-20-1 M141D-21-1 B-21-3238 B-21-3238
2-92
I
Line #: Service:
DBA-2(B) Test connection and MSIV-LC system
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-10027B
1) Hanger Drawing Numbers
Hi PS 2 DET A
H2 PS 2 DET C
H3 PS 2 DET C
H4 PS 2 DET C
H5 PS 2 DET C
H6 PS 2 DET C
H7 PS 2 DET C
H8 PS 2 DET B
SKM SKM SKM SKM SKM SKM SKM SKM SKM SKM SKM SKM SKM SKM SKM SKM
602, RO 1606, RO 602, RO 1607, RO 602, RO 1607, RO 602, RO 1607, RO 602, RO 1607, RO 602, RO 1607, RO 602, RO 1607, RO 602, RO 1609, Ri
2) Valve Vendor Print Numbers
M141D-20-1 M141D-20-1 M141D-21-1
V-84-03 V-84-04 V-84-02
2-93
Line #: DBA-2(B) Service: Test connection and MSIV-LC system
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4187B
1) Hanger Drawing Numbers
Hi PS 2 SKM 602, RO DET C SKM 1607,RO SNUBBER-000272
-00921 H2 PS 2 SKM 602, RO
DET C SKM 1607, RO H3 PS 2 SKM 602, RO
DET C SKM 1607, RO H4 PS 2 SKM 602, RO
DET C SKM 1607, rO H5 PS 2 SKM 602, RO
DET C SKM 1607, RO H6 PS 4 SKM 602, RO
DET B SKM 1609, Ri H7 PS 4 SKM 602, RO
DET B SKM 1609, Ri
2) Valve Vendor Print Numbers
V-84-18 V-84-17 V-84-16 MO-8401D MO-8402D
M141D-20-1 M141D-20-1 MI41D-21-1 B-21-3238 B-21-3238
2-94
Line #: DBA-2(A) Service: Test connection and MSIV-LC system
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-10029B
1) Hanger Drawing
H1 PS 2 DET C
H2 PS 2 DET C
H3 PS 2 DET A
H4 PS 2 DET A
H5 PS 2 DET C
H6 PS 2 DET A
H7 PS 2 DET A
H8 PS 4 DET B
Numbers
SKM SKM SKM SKM SKM SKM SKM SKM SKM SKM SKM SKM SKM SKM SKM SKM
602, RO 1607, RO 602, -RO 1607, RO 602, RO 1606, RO 602, RO 1606, RO 602, $0 1607, RO 602, RO 1606, RO 602, RO 1606, RO 602, RO 1609, R1
2) Valve Vendor Print Numbers
V-84-11 V-84-10 V-84-9 MO-8402C MO-8401C
M141D-20-1 M141D-20-1 M141D-21-1 B-21-3238 B-21-3238
2-95
Line #: DBA-2(B) Service: Test connection and MSIV-LC system
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-10030B
1) Hanger Drawing Numbers
Ji PS 4 DET C
H2 PS 4 DET C
H3 PS 4 DET A
H4 PS 4 DET B
H5 PS 4 DET A
H6 PS 1 DET C
H7 PS 2 DET A
2) Valve Vendor
MO-8403B
SKM SKM SKM SKM SKM SKM SKM SKM SKM SKM SKM SKM SKM SKM
602, RO 1607, RO 602, RO 1607, RO 602, RO 1606, RO 602, RO 1609, Ri 602, RO 1606, RO 602, RO 1607, RO 602, RO 1606, RO
Print Numbers
B-21-3238
2-96
Line #: DBA-2(B) Service: Test connection and MSIV-LC system
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-10031B
1) Hanger Drawing
Hi PS 4 DET C
H2 PS 4 DET C
H3 PS 4 DET A
H4 PS 4 DET B
H5 PS 4 DET A
H6 PS 1 DET C
H7 PS 2 DET A
Numbers
SKM 602, RO SKM 1607, RO SKM 602, RO SKM 1607, RO SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1609, Ri SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1607, rO SKM 602, RO SKM 1606, RO
2) Valve Vendor Print Numbers
MO-8403A B-21-3238
Line #: DBA-2(B) Service: Test connection and MSIV-LC system
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-10032B
1) Hanger Drawing Numbers
Hi PS 4 DET C
H2 PS 4 DET C
H3 PS 4 DET A
H5 PS 4 DET A
H6 PS 2 DET A
H4 PS 4 DET B
SKM 602, RO SKM 1607, RO SKM 602, RO SKM 1607, RO SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1609, Ri
2) Valve Vendor Print Numbers
MO-8403D B-21-3238
2-97
Line #: DBA-2(B) Service: Test connection and MSIV-LC system
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-10033B
1) Hanger Drawing Numbers
Hi PS 4 DET C
H2 PS 4 DET C
H3 PS 4 DET A
H4 PS 4 DET A
H5 PS 4 DET A
H6 PS 2 DET A
SKM 602, RO SKM 1607, RO SKM 602, RO SKM 1607, RO SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1606, RO
2) Valve Vendor Print Numbers
MO-8403C B-21-3238
2-98
Line #: DBA-2(B) Service: Test connection and MSIV-LC system
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping St-ress Isometric Drawings: FSK-10034B
1) Hanger Drawing Numbers
Hi PS DET A
H2 PS 6 DET A
H3 PS 6 DET A
H4 S 6 DET 6
H5 PS 4 DET A
H6 PS 4 DET A
H7 PS 4 DET A
SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1606, RO
2) Valve Vendor Print Numbers
M141D-21-1 M141D-20-1 M141D-20-1 M141D-21-1 M141D-20-1 M141D-20-1 M141D-21-1 M141D-20-1 M141D-20-1 M141D-21-1 M141D-20-1 M141D-20-1
V-84-48 V-84-12 V-84-13 V-84-45 V-84-19 V-84-20 V-84-47 V-84-05 V-84-06 V-84-46 V-84-26 V-85-27
2-99
Line #: DBA-2(B) Service: Test connection and MSIV-LC system
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-10035B
1) Hanger Drawing Numbers
Hi DET 1 DET A
H2 PS 2 DET B
H3 PS 2 DET A
H4 PS 2 DET A
H5 PS 1 DET B
FSK-10035 SKM 1606, RO SKM 602, RO SKM 1609, Ri SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1609, Ri
2) Valve Vendor Print Numbers
V-84-47 M141D-21-1
2-100
Line #: DBA-2(B) Service: Test connection and MSIV-LC system
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-10036B
1) Hanger Drawing Numbers
Hi PS 2 DET A
H2 PS DET C
H3 PS 2 DET A
H4 PS 2 DET A
H5 PS 2 DET A
H6 PS 5 DET A
H7 PS 5 DET C
H8 PS 5 DET C
H9 PS 5 DET C
SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1607, RO SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1607, RO SKM 602, RO SKM 1607, RO SKM 602, RO SKM 1607, RO
2) Valve Vendor Print Numbers
None
.2-101.
Line #: DBA-2(B) Service: Test connection and MSIV-LC system
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-10037B
1) Hanger Drawing Numbers
Hi PS 4 DET C
H2 PS 4 DET A
H3 PS 4 DET B
H4 PS 4 DET A
H5 PS 4 DET A
SKM SKM SKM SKM SKM SKM SKM SKM SKM SKM
602, RO 1607, RO 602, RO 1606, RO 602, RO 1609, Ri 602, RO 1606, RO 602, RO .1606, RO
2) Valve Vendor Print Numbers
None
Line #: Service:
DBA-2 (B) Test connection and MSIV-LC system
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-10038B
1) Hanger Drawing Numbers
Hi PS DET C
H2 PS 4 DET A
H3 PS 4 DET B
H4 PS 4 DET A
H4 PS 4 DET A
SKM SKM SKM SKM SKM SKM SKM SKM SKM SKM
602, RO 1607, RO 602, RO 1606, RO 602, RO 1609, Ri 602, RO 1606, RO 602, RO 1606, RO
2) Valve Vendor Print Numbers
None
2-102
Line #: DBA-2(B) Service: Test connectionand MSIV-LC system
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-10039B
1) Hanger Drawing Numbers
Hi PS 1 DET C
H2 PS 4 DET A
H3 PS 4 DET B
H4 PS 4 DET A
H5 PS 4 DET A
SKM 602, RO SKM 1607, RO SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1609, Ri SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1606, RO
2) Valve Vendor Print Numbers None
Line #: DBA-2(B) Service: Test connection and MSIV-LC system
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-10040B
1) Hanger Drawing Numbers
Hi PS 4 DET A
H2 PS 4 DET A
H3 PS 4 DET B
H4 PS 4 DET A
H5 PS 4 DET C
SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1609, Ri SKM 602, RO SKM 1606, RO SKM 602, RO SKM 1607, RO
2) Valve Vendor Print Numbers
None
2-103
Line #: DBA-2(B) Service: Test connection and MSIV-LC system
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-10041B
1) Hanger Drawing Numbers
H-1 PS4 DET B
H-2 PS 4 DET A
H-3 PS 5 DET A
SKM-602, RO SKM-1609, Ri SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-84-33 V-84-32 V-84-34
Line #: Service:
M141D-20-1 M141D-20-1 M141A-56-4
DBA-2(B) Test connection and JSIB-LC system
esign Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-10042B
1) Hanger Drawing Numbers
H-1 PS 4 DET B
H-2 PS 4 DET A
H-3 PS 4 DET A
SKM-602, RO SKM-1609, Rl SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1602, RO
2) Valve Vendor Print Numbers
M141A-56-4 MI41D-20-1 M141D-20-1
V-84-35 V-84-36 V-84-37
2-104
Line #: Service:
DBA-2(B) Test connection and MSIV-LC system
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-10046B
1) Hanger Drawing Numbers
H-1 PS 1 DET B
H-2 PS 1 DET A
H-3 PS 1 DET A
SKM-602, RO SKM-1609, RI SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
None
Line #: Service:
DBA-2(C) Drains from steam lines inside containment
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4220B
1) Hanger Drawing Numbers
H-1 PS 6 DET A
SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-14-37 M-123-A-6-7 V-14-38 M-123-A-6-7
2-107
Line #: DBA-4 Service: Steam to RCIC turbine from main steam line to MO-2401
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4325B, FSK-4026B
1) Hanger Drawing Numbers
FSK-4325
H-2 PS 6 DET A
FSK-4026
H-1 PS 1 DET A
H-2 PS 1 DET A
H-3 PS 1 DET B
H-4 DET 1 DET C
SKM-602, RO SKM-1606, RO
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, Ri FSK-4026, R4 SKM-1607, RO
2) Valve Vendor Print Numbers
M141-55(1)-1 M141-55(1)-1 M141-55(1)-1 M141-55(1)-1
V-23-33 V-24-27 V-24-27 V-24-26
2-108
Line #: DBA-5 Service: RHR pump discharge from MO-1901 to reactor head spray
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-3934B
1) Hanger Drawing Numbers
H-1 PS-1 DET B
H-2 PS 1 DET A
H-3 PS 1 DET A
H-4 PS 6 DET C
SKM-602, RO SKM-1609, R1 SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO
2) Valve Vendor Print Numbers
V-19-34 V-19-3 3
M-141-55(l)-1 M-141-55(1)-i
Line #: DBA-7 Service: Drain test connection
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4130B
1) Hanger Drawing Numbers
Sh 35 DET 1
H-1 PS 1 DET B
SKM-1611, RO FSK-4130 SKM-602, RO SKM-1609, Rl
2) Valve Vendor Print Numbers
M-141-A-56-4 M-141-A-56-4 M-141-A-55-1-1 M-141-A-55-1-1
V-25-25 V-25-26 V-25-16 V-25-17
2-109
Line #: DBA-9 Service: Reactor vessel vent to drywell equipment drain sump
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4041B, FSK-4042B,
FSK-4239B, FSK-5593B
1) Hanger Drawing Numbers
FSK-5593B FSK-4042B
H-1 PS 2 DET B
H-2 PS 1 DET A
H-3 H-4 PS 2
DET C H-5 PS 1
DET A H-6 PS 2
SNUB 13 H-7 PS 1
DET A Sh 106
PS 1-2
SKM-602, RO SKM-1609, Rl SKM-602, RO SKM-1606, RO SKM-1601, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO
SKM-602, RO SKM-1606, RO SKM-1611, RO SKM-602, RO
FSK-4239B
H-1 PS 2 SNUB 17A
H-2 H-3 H-4 PS 2
SNUB 18A H-5 PS 1
DET C
PS 2 SNUB 19A
H-6 H-4 H-8
H-9 H-10 PS 1
DET A H-11 PS 1
DET B
SKM-602, RO
SKM-1601, RO SKM-1601, RO SKM-602, RO
SKM-602, RO SKM-1607, RO SKM-1601, RO SKM-1601, RO SKM-602, RO
SKM-1601, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, Ri
H-1 DET C Sh 2C
DET B Sh 2B DET B H-2 PS 1
DET C H-3 PS 1
DET A H-4 PS 1
DET B H-5 PS 2
DET A H-6 PS 1
DET B H-7 PS 2
DET A H-8 PS 2
SNUB 2B Sh 103 PS 1 H-9 PS 2
DET A H-10 PS 2
DET A Sh 104 PS 2 H-ll DET 4 H-12 DET 4 Sh 105 PS 2 H-13 PS 1
DET C
FSK-5593B
H-1 PS 2 DET U
Sh 93 Sh 94
SKM-1607, RO
SKM-1609, RI SKM-1609, R1 SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, Ri SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, Ri SKM-602, RO SKM-1606, RO SKM-602, RO
SKM-602, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO FSK-4042B FSK-4042B SKM-602, RO SKM-602, RO SKM-1607, RO
SKM-602, RO SKM-1608, RO SKM-1611, RO SKM-1611, RO
. 2-110
Sheet 2 of 2
FSK-5593B
H-2 PS 2 DET B
H-3 PS 2 DET A
H-4 PS-2 DET A
H-5 PS 2 DET A
H-6 PS 2 DET A
H-7 PS 1 DET A
H-8 PS 1 DET A
H-9 PS 2 DET A
H-10 PS 1 DET A
H-ll PS 2 DET A
H-12 PS 2 DET A
H-13 PS 1 DET A
SKM-602, RO SKM-1609, RI SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-15-01 CV-4429 V-14-6 V-14-5 CV-4428
M-123A-6-7 M-141-35-1 M-123A-6-7 M-123A-6-7 M-141-35-1
.2-111
Line #: DBA-9
Line #: DBA-10 Service: High pressure flange leak-off reactor vessel
Design Input Documents:
Piping Class/Summary Sheet: DBA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-3352B,
FSK-4239B,FSK-5591B, FSK-4238B
1) Hanger Drawing
FSK-4238B
H-1 PS 2 DET A
H-2 PS 2 DET A
H-3 PS 2 DET C
Sh 66 H-4 PS 2
DET A Sh 67 H-6 PS 2
DET A H-7 PS 2
DET A H-5 PS 1
DET C Sh 11
FSK-5591B
Sh 64 PS 1
H-1 PS 1 DET C
H-2 PS 1 DET A
H-3 DET B H-4 PS 1
DET A H-5 PS 1
DET A H-6 PS 3
DET A H-7 PS 1
DET A
Numbers
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-1611, RO SKM-602, RO SKM-1606, RO SKM-1611, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-1611, RO
SKM-1611, RO SKM-602, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-1609, R1 SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
FSK-5591B
H-8 PS 2 DET A
H-9 PS 1 DET C
H-10-PS-2 DET A
H-11 PS, 3 DET A
H-12 PS 1 DET A
H-13 PS 2 DET A
H-14 PS 1 DET A
H-15 PS 1 DET A
H-16 PS 1 DET A
FSK-4239B
H-1 PS 1 DET B
FSK-3352B
H-1 PS 1 DET A
H-2 PS 1 DET B
H-3 PS 2 DET C
H-4 PS 2 DET C
H-5 PS 1 DET A
H-6 PS 1 DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
SKM-602, RO SKM-1609, RO
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
,2-112
2) Valve Vendor Print Numbers
V-14-126 V-14-125 V-14-127 V-16-79 V-16-78
M141D-1-2 M141D-1-2 M141D-1-2 Mi41-55(1)-i M141-55(1)-i
Line #: DCA 1/4 Service: Recirculation system Loop A
Design Input Documents:
Piping Class/Summary Sheet: DCA Seismic Response Spectra: See Piping Stress Isometric Drawings:
/M190 FSAR 761E584, 761E344
1) Hanger Drawing Numbers
GE 761E344, Sh 1
SS A8
SSA9
HAl
SSAl
SSA2
SSA3
HA5
HA6
HA7
SSA4
SSA 5
SSA 10
GE 761E344, Sh 1
BP 215, RO BP 215A, Ri BP 215A, R1 BP 217, RO BP 101, Ri BP 101A, R1 BP 101B, RO BP 101C, Ri BP 201, RO BP 201A. R1 BP 203A, RI BP 203, Ri BP 205A, Ri BP 205, Ri BP 105A, R1 BP 105, Ri BP 105B, RO BP 105A, R1 BP 106A, R1 BP 105B, RO BP 107, Ri BP 107A, R1 BP 107B, RO BP 207A, Ri BP 207, RO BP 209A, Ri BP 209, RO BP 219A, R2 BP 219A, Ri BP 219B, RO
SSAll
HA9 HA2
BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP BP
SSA6
SSA 7
HA3
HA4
221A, R1 221, Ri 221B, RI 109, RO 101A, RI 101C, Ri 102, Ri 102A, RO 211A, Ri 211, RO 211A, R1 213, RO 103, Ri 103A, RI 103A, $1 104, Ri
GE 761E584, Sh 1
RR1 RR2 RR3 RR4 RR5 RR6 RR7 RR8 RR9 RR1O RRl 1 RRI2 RR1 3 RR14
GE 761E584, GE 761E584, GE 761E584, GE 761E584, GE 761E584, GE 761E584, GE 761E584, GE 761E584, GE 761E584, GE 761E584, GE 761E584, GE 761E584, GE 761E584, GE 761E584,
Sh Sh Sh Sh Sh Sh Sh Sh Sh Sh Sh Sh Sh Sh
2-113
2 2 2 2 2 2 2 2 2 2 2 2 2 2
Line #: DCA-10 Service: Test loop from core spray line inside containment
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5589B
1) Hanger Drawing Numbers
H-1 PS 1 DET C
H-2 PS 1 DET A
H-3 PS 1 DET C
H-4 PS 1 DET C
SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1607, RO
2) Valve Vendor Print Numbers
V-21-35 M123A-6-7
Line #: DCA-1l Service: HPCI steam
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5581B
1) Hanger Drawing Numbers
H-1 PS 6 DET U
Sh 49 Sh 50 H-2 PS 2
DET B H-3 PS 2
DET A H-4 PS 2
DET A H-5 PS 2
DET A H-6 PS 1
DET A H-7 PS 2
DET C H-8 PS 5
DET A H-9 PS 2
DET C
2) Valve Vendor
None
SKM-602, RO SKM-1608, RO SKM-1611, RO SKM-1611, rO SKM-602, RO SKM-1609, RI SKM-602, rO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, rO SKM-602, rO SKM-1606, rO SKM-602, RO SKM-1607, RO
Print Numbers
2-115
Line #: DCA-11 Service: HPCI steam
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5582B
1) Hanger Drawing Numbers
H-1 PS 6 DET U
Sh 52 Sh 51 H-2 PS 2
DET B H-3 PS-2
DET A H-4 PS 2
DET A H-5 PS 2
DET A H-6 PS 2
DET A H-7 PS 2
DET C DET 1
H-8 PS 5 DET A
H-9 PS 2 DET C DET 1
SKM-602, RO SKM-1608, RO SKM-1611, RO SKM-1611, RO SKM-602, RO SKM-1609, RI SKM-602, RO SKM-1606, RO SKM-602, rO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO FSK-5581B SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO FSK-5581B
2) Valve Vendor Print Numbers
V-22-3 M-123A-6-7
2-116
Line #: DCA-11 Service: HPCI steam
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5583B
1) Hanger Drawing Numbers
H-1 PS 6 DET A
H-3 DET C H-4 PS 2
DET A H-5 PS 2
DET A H-6 PS 2
DET A H-7 PS 2
DET U Sh 18
SKM-602, RO SKM-1606, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1608, RO SKM-1611, RO
2) Valve Vendor Print Numbers
V-22-4 M-123A-6-7
Line #: DCA-11 Service: HPCI steam
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5584B
1) Hanger Drawing
H-1 PS 6 DET A
H-2 PS 6 DET A
H-3 PS 6 DET A
H-4 PS 6 DET A
H-5 DET C SH 19 H-8 PS 2
DET A H-9 PS 2
DET A H-10 PS 2
DET A
Numbers
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-1607, RO SKM-1611, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2-117
H-11 PS-2 DET A
H-12 PS 2 DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-21-1 M137A-2-4
Line #: Service:
DCA-3 Standby liquid control test connection
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-3992B, FSK-3993B
1) Hanger Drawing Numbers
FSK-3992B**
H-1 SH 96 DET B
FSK-3993B*
H-1 Sh 45 DET A
H-2 PS 1 DET C
H-3 PS 1 DET A
H-4 PS 1 DET A
SKM-1611, SKM-1609,
RO Rl
SKM-1611, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-26-8** V-26-24* V-26-23*
M123-4-3 M123A-6-7 M123A-6-7
2-118
,
Line #: Service:
DCA-13 Standby liquid control test connection
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping St-ress Isometric Drawings: FSK-3734B
1) Hanger Drawing Numbers
H-1 PS 2 DET A
H-2 PS 2 DET C
H-3 PS 3 DET C
H-4 PS 2 DET A
H-5 PS 1 DET A
H-6 PS 1 DET A
H-7 PS 1 DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
Valve Vendor Print Numbers
M123-4-3 M123A-5-10 M123A-6-7 M123A-6-7
2-119
2)
V-26-9 ZS-2615 V-26-26 V-26-27
Line #: DCA-13 Service: Standby liquid control test connection
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5507B
1) Hanger Drawing Numbers
H-1 DET C H-2 PS 1
DET A H-3 DET C H-4 DET C H-5 DET C H-6 PS 4
DET A H-7 PS 4
DET A H-8 PS 4
DET A
SKM-1607, RO SKM-602, RO SKM-1607, RO SKM-1607, RO SKM-1607, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-15-19 M-123A-6-7
Line #: DCA-13 Service: Standby liquid control test connection
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5513B
1) Hanger Drawing
H-1 PS 1 DET C
H-2 PS'1 DET B
H-3 PS 1 DET A
H-4 PS 1 DET A
H-5 PS 1 DET A
H-6 PS 1 DET A
H-7 PS 1 DET C
Numbers
SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1609, RI SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO
2-120
H-8 PS 4 DET C
H-9 PS 4 DET A
H-10 PS 4 DET A
SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vebdor Print Numbers
V-15-18 M-123A-6-7
Line #: Service:
DCA-1 3 Standby liquid control test connection
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5520B
1) Hanger Drawing
H-1 DET C H-2 PS 1
DET A H-3 DET C H-4 DET C H-5 DET C H-6 PS 4
DET A H-7 PS 4
DET A H-8 DET C
Numbers
SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-1607, RO SKM-1607, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-1607, RO
2) Valve Vendor Print Numbers
V-15-37 MI23A-6-7
2-121
Line #: DCA 17/18 Service: CRDs
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: DA-003
1) Hanger Drawing Numbers
41 RCI DA-9, Sh 2 46 RCI DA-9, Sh 1 7884-M115-40(2)-2 78840N115-40(1)-2
42 RCI DA-9, Sh2 47 RCI DA-9, Sh 1 7884-M115-40(2)-2 7884-M115-40(1)-2
43 RCI DA-9, Sh 4 48 RCI DA-9, Sh 4 7884-Mll5-40(4)-2 7884-M115-40-(4)-2
44 RCI DA-9, Sh 3 49 RCI DA-9, Sh 3 7884-M115-40(3)-2 7884-M115-40(3)-2
45 RCI DA-9, Sh 3 50 RCI DA-9, Sh 3 7884-M115-40(3)-2 7884-Mll5-40(3)-2
Piping Stress Isometric Drawings: DA-004
16 RCI DA-9, Sh 8 20 RCI DA-9, Sh 9 7884-M115-40(8)-1 7884-M-115-40(9)-1
17 RCI DA-9, Sh 8 21 RCI DA-9, Sh 9 7884-Mll5-40(8)-i 7884-M115-40(9)-i
18 RCI DA-9, Sh 4 22 RCI DA-9, Sh 4 7884-Mll5-40(4)-1 7884-M115-40(4)-1
19 RCI DA-9, Sh 3 23 RCI DA-9, Sh 3 7884-M115-40-(3)-1 7884-M115-40(3)-i
39 RCI DA-9, Sh 3 40 RCI DA-9, Sh 3 7884-Mll5-40-(3)-1 7884-M115-40(3)-1
2-122
i
Service: CRDs
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: DA-005
1) Hanger Drawing Numbers
24 RCI DA-9, Sh 5 7884-M115-40(5)-2 RIC DA-9, Sh 7 7884-Mll5-40(7)-1
25 RCI DA-9, Sh 5 7884-Mll5-40(5)-2 RCI DA-9, Sh 7 7884-Mll5-40(7)-i
26 RCI DA-9, Sh 5 7884-Mll5-40(5)-2 RCI DA 9, Sh 7 7884-Mll5-40(7)-1
27 RCI DA-9, Sh 7 7884-M115-40(7)-1
28 RCI DA-9, Sh 5 7884-Mll5-40(5)-2 RCI DA-9, Sh 7 7884-Mll5-40(7)-i
29 RCI DA-9, Sh 5 7884-Mll5-40(5)-2 RCI DA-9, Sh 7 7884-M115-40(7)-i
30 RCI DA-9, Sh 7 7884-M115-40(7)-1
31 RCI DA-9, Sh 7 7884-M115-40(7)-1
32 RCI DA-9, Sh 5 7884-M115-40(5)-2 RCI DA-9, Sh 7 7884-Mll5-40(7)-i
33 RCI DA-9, Sh 5 7884-Mi15-40(5)-2 RCI DA-9, Sh 7 7884-Mll5-40(7)-1
34 RCI DA-9, Sh 7 7884-Mll5-40(7)-1
35 RCI DA-9, Sh 5 7884-Mll5-40(5)-2 RCI DA-9, Sh 7 7884-Mll5-40(7)-1
36 RCI DA-9, Sh 5 7884-Mll5-40(5)-2
2-123
Line #: DCA-17/18 Sheet 2
Line #: DCA-17/18 Service: CRDs
Design Input Documents:
Sheet 2
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: DA-005
1) Hanger Drawing Numbers
24 RCI DA-9, Sh 5 7884-Mll5-40(5)-2 RIC DA-9, Sh 7 7884-M115-40(7)-1
25 RCI DA-9, Sh 5 7884-M115-40(5)-2 RCI DA-9, Sh 7 7884-Mll5-40(7)-1
26 RCI DA-9, Sh 5 7884-Ml5-40(5)-2 RCI DA 9, Sh 7 7884-M1T5-40(7)-i
27 RCI DA-9, Sh 7 7884-M115-40(7)-1
28 RCI DA-9, Sh 5 7884-M115-40(5)-2 RCI DA-9, Sh 7 7884-Ml15-40(7)-i
29 RCI DA-9, Sh 5 7884-MllS-40(5)-2 RCI DA-9, Sh 7 7884-M115-40(7)-1
30 RCI DA-9, Sh 7 7884-M115-40(7)-1
2) Valve Vendor Print Numbers
V-18-1364 through V-18-1452 V-18-1097 through V-18-1185
31 RCI DA-9, Sh 7 7884-M115-40(7)-1
32 RCI DA-9, Sh 5 7884-Mll5-40(5)-2 RCI DA-9, Sh 7 7884-Ml15-40(7)-1
33 RCI DA-9, Sh 5 7884-M115-40(5)-2 RCI DA-9, Sh 7 7884-Ml5-40(7)-i
34 RCI DA-9, Sh 7 7884-M115-40(7)-1
35 RCI DA-9, Sh 5 7884-M115-40(5)-2 RCI DA-9,Sh 7 7884-M115-40(7)-i
36 RCI DA-9, Sh 5 7884-M115-40(5)-2 RCI DA-9, Sh 7 7884-M115-40(7)-1
37 RCI DA-9, Sh 7 7884-M115-40(7)-1
38 RCI DA-9, Sh 7 7884-M115-40(7)-1
M115-17-1 M115-17-1
2-124
PSA-1 H-7 SNUB 17
PSA-1 H-8 PS.1
DET ASKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
None
Line #: DCA-19A Sheet 2 Service: Recircualtion system
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4166B
1) Hanger Drawing Numbers
H-1 SNUB 18 PSA-1
H-2 PS 1 Sh 5
SKM-602, RO SKM-1611, RO
2) Valve Vendor Print Numbers
V-15-43 V-16-45
M123A-6-7 M123A-6-7
Line #: DCA-19A Sheet 2 Service: Recirculation system
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4167B
1) Hanger Drawing Numbers
H-1 PS 1 DET C
H-2 PS 2 SNUB 9A PSA-1
H-3 DET 2 Sh 108
SKM-602, RO SKM-1607, RO SKM-602, RO
FSK-4167B SKM-1611, RO
2-126
2) Valve Vendor Print Numbers
V-16-46 V-16-47
M-123A-6-7 M-123A-6-7
Line #: DCA-19A Sheet 4 Service: Recirculation system
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4170B
1) Hanger Drawing
H-1 PS 2 SNUB 10A PSA-1
H-2 PS 2 SNUB 1lA PSA-1
H-3 PS 2 Sh 111
H-4 PS 1 DET C
Numbers
SKM-602,
SKM-602,
RO
RO
SKM-602, RO SKM-1611, RO SKM-602, RO SKM-1607, RO
2) Valve Vendor Print Numbers
V-16-35 V-16-36
M-123A-6-7 M-123A-6-7
2-127
Line #: Service:
DCA-19A Sheet 5 Recirculation system
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4172B
1) Hanger Drawing Numbers
H-1 PS 2 Sh 76
H-2 PS 1 DET C
SKM-602, RO SKM-1611, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-16-38 V-16-39
M-123A-6-7 M-123A-6-7
2-128
Line #: Service:
DCA-19A Sheet 6 Recirculation system
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic-Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4173B
1) Hanger Drawing Numbers
H-1 Sh 7E H-2 SNUB
PSA-1 H-3 PS 2
DET I H-4 PS 2
DET 1
2) Valve Vend
V-16-42 V-16-41
SKM-1611, RO
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
or Print Numbers
M-123A-6-7 M-123A-6-7
.2-129
Line #: DCA-19B Service: Recirculation system
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4168, FSK-4171B,
FSK-4174
1) Hanger Drawing Numbers
FSK-4168*
S-1 Sh 86 DET B
H-2 PS 2 SNUB 13 PSA-1
FSK-4171B**
H-1 Sh 74 PS 2
FSK-4174***
H-1 Sh 73 DET B
H-2 PS 1 DET A
SKM-1611, RO SKM-1609, Ri SKM-602, RO
SKM-1611, RO SKM-602, RO
SKM-1611, RO SKM-1609, Ri SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-16-44* V-16-37** V-16-40***
M123A-6-7 M123A-6-7 M123A-6-7
2-130
Line #: DCA-19C Service: Recirculation system
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4201B, FSK-4204B,
FSK-4207
1) Hanger Drawing Numbers
FSK-4201B*
H-1 SH 83 H-2 Sh 84
FSK-4204B**
H-1 Sh 78 H-2 Sh 82
PS 2
FSK-4207B***
H-1 Sh 68
2) Valve Vendor
*V-16-29 **V-16-23
***V-16-20
SKM-1611, SKM-1611,
RO RO
SKM-1611, RO SKM-1611, RO SKM-602, RO
SKM-1611, RO
Print Numbers
M-123A-6-7 M-123A-6-7 M-123A-6-7
2-131
Line #: Service:
DCA-19D Recirculation system
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4198B
1) Hanger Drawing
H-6 Sh 110 PS 2
H-5 SNUB 14A PSA-1
H-2 Sh 114 PS 1
H-4 Sh 115 PS 2
H-3 SNUB 12A PS 2 PSA-1
H-1 SNUB 13A PS 2 PSA-1
H-7 PS 1 DET A
Numbers
SKM-1611, RO SKM-602, RO
SKM-1611, RO SKM-602, RO SKM-1611, RO SKM-602, RO
SKM-602, RO
SKM-602, RO
SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
None
2-132
Line #: DCA-19DService: Recirculation system
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4199B, FSK-4200B
1) Hanger Drawing Numbers
H-1 PS 1 Sh 6
FSK-42000
H-1 Sh 81 PS 1
H-2 SNUB BA PS 2 PSA-1
H-3 PS 1 DET C
H-4 Sh 80
SKM-602, RO SKM-1611, RO
SKM-1611, RO SKM-602, RO
SKM-602, RO
SKM-602, RO SKM-1607, RO SKM-1611, RO
2) Valve Vendor Print Numbers
V-16-27 V-16-28 V-16-86 V-16-26
M-123A-6-7 M-123A-6-7 M-123A-6-7 M-123A-6-7
2-133
Sheet 2
Line #: DCA-19D Sheet 3 Service: Recirculation system
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4202B, FSK-4203B
1) Hanger Drawing Numbers
FSK-4202B
H-1 Sh 117 H-2 Sh 4
PS 2 H-3 Sh 116
FSK-5203B
H-1 Sh 79 PS 1
H-2 SNUB 19 PS 2
H-3 PS 1 DET C
H-4 PS 1 DET A
SKM-1611, RO SKM-1611, RO SKM-602, RO SKM-1611, RO
SKM-1611, RO SKM-602, RO
SKM-602, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
M-123A-6-7 M-123A-6-7 M-123A-6-7 M-123A-6-7
V-16-30 V-16-85 V-16-21 V-16-22
2-134
Line #: DCA-19D Sheet 4 Service: Recirculation system
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4205B, FSK-4206B
1) Hanger Drawing Numbers
FSK-4205B
H-1 PS 2 Sh 72
FSK-4206B
H-1 Sh 85 DET B
H-2 SNUB 7A PS-2 PSA-1
H-3 PS 2 DET A
H-4 PS 2 DET A
SKM-602, RO SKM-1611, RO
SKM-1611, RO SKM-1609, R1
SKM-602, RO
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
M-123A-6-7 M-123A-6-7 M-123A-6-7 M-123A-6-7
V-16-18 V-16-19 V-16-29 V-16-25
2-135
Line #: DCA-20 Service: Seal purge from CRD system
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4480B
1) Hanger Drawing Numbers
Sh 100 DET B Sh 100 PS 2
H-1 PS 1 DET A
H-2 H-3 PS 2
DET U H-4 PS 1
DET B H-5 PS 1
DET A H-6 PS 1
DET A H-7 PS 1
DET A H-8 PS 1
DET A H-9 PS 1
DET A H-10 PS 1
DET A H-11 PS 1
DET A H-12 PS 1
DET A H-13 PS 1
DET A H-14 PS 1
DET A H-15 PS 1
DET A
SKM-1611, RO SKM-1609, Ri SKM-1611, RO SKM-602, RO SKM-602, RO SKM-1606, RO FSK-4480B SKM-602, RO SKM-1608, RO SKM-602, RO SKM-1609, Ri SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-2606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-17-87 V-17-88 CV-1804A
M123A-6 M123A-6 M123D-13
2-136
Line #: DCA-20 Sheet 2 Service: Seal purge from CRD system
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4871B
1) Hanger Drawing Numbers
Sh 97 PS 2 Sh 98 PS 2
H-1 PS 1 DET A
H-2 PS 2 DET U
Sh 99 DET 2 H-3 PS 1
DET B H-4 PS 1
DET A H-5 PS 1
DET A
SKM-1611, RO SKM-602, RO SKM-1611, RO SKM-602, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1608, RO FSK-4480B SKM-602, RO SKM-1609, Rl SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-17-91 V-17-92 CV-1804B
M123A-6-7 M123A-6-7 M123D-13
2-137
Line #: DCA-503 Service: Main steam Loop A
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic-Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5565B
1) Hanger Drawing Numbers
H-1 DET X DET U
H-2 DET C H-3 PS 2 H-4 PS 2
DET A H-5 PS 2
DET A H-6 PS 2
DET B H-7 PS 2
DET C H-8 PS 2 H-9 PS 2
DET A
FSK-4471B, R2 SKM-1608, RO SKM-1607, RO SKM-602, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM 1606, RO SKM-602, RO SKM-1609, R1 SKM-602, RO SKM-1607, RO SKM-602, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-14-20 M-123A-6-7
.2-138
Line #: DCA-504 Service: Riciruclation system discharge
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5529B, 0207884-100
1) Hanger Drawing Numbers
H-1 PS 5 DET A
H-2 PS 1 DET C
H-3 PS 5 DET C DET 2
H-4 PS 2 DET A
H-5 PS 1 DET A
H-6 PS 1 DET A
H-7 PS 1 DET A
H-8 PS 1 DET A
H-9 PS 1 DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1607, RO FSK-5536B SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, $0 SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-16-17 M-123A-6-7
2-139
Line #: DCA-505 Service: Recirculation system riser differential pressure
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5531B, EDS 0207884-096
1) Hanger Drawing Numbers
H-1 PS 1 DET C
H-2 PS 1 DET B
H-3 PS 1 DET A
H-4 PS 1 DET A
H-5 PS 1 DET A
H-6 PS 1 DET A
H-7 PS 2 DET A
H-8 PS 1 DET C DET 3
H-9 PS 5 DET A
SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1609, RI SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO 1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKm-1607, RO FSK-5529B SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-16-73 M-123A-6-7
2-140
Line #: DCA-506 Service: Recirculation system riser differntial pressure
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5530B
1) Hanger Drawing Numbers
H-1 PS 5 DET C DET 2
H-2 PS 5 DET B
H-3 PS 4 DET A
H-4 PS 4 DET A
H-5 PS 2 DET C DET 1
H-6 PS 2 DET B
H-7 PS 1 DET A
H-8 PS 2 DET A
H-9 PS 1 DET A
H-10 PS 2 DET A
H-l PS 2 DET A
H-12 PS 1 DET A
H-13 PS 1 DET A
H-14 PS 1 DET A
H-15 PS 5 DET A
Sh 54
SKM-602, RO SKM-1607, RO FSK-5533B SKM-602, RO SKM-1609, Rl SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO FSK-5533B SKM-602, RO SKM-1609, Rl SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-1611, RO
2) Valve Vendor Print Numbers
None
.2-141,
Line #: DCA-507 Service: Recirculation system riser differential pressure
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4432B, 0207884-097
1) Hanger Drawing Numbers
H-1 PS 2 DET C DET 1
H-2 PS 2 DET B
H-3 PS 2 DET A
H-4 PS 1 DET A
H-5 PS 1 DET A
H-6 PS 1 DET A
H-7 PS 2 DET B
H-8 PS 2 DET C DET 1
H-9 PS 5 DET A
H-10 PS 4 DET A
H-11 PS 4 DET A
H-12 PS 5 DET B
H-13 PS 5 DET C DET 2
SKM-602, RO SKM-1607, RO FSK-5533B, R2 SKM-602, RO SKM-1609, Rb SKM 602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, RI SKM-602, RO SKM-1607, RO FSK-5533B SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, Ri SKM-602, RO SKM-1607, RO FSK-5533B
2) Valve Vendor Print Numbers
V-16-74 M-123A-6-7
2-142
Line *: DCA-508Service: Instrument piping from drywell water level temperature
Column B
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5627B, FSK-5663
1) Hanger Drawing Numbers
FSK-5627B
H-1 PS 1 DET C
H-2 PS 1 DET B
H-3 PS 1 DET A
H-4 PS 1 DET A
H-5 PS 1 DET A
H-6 PS 1 DET A
FSK-5663B
H-1 PS 5 DET A
H-2 PS 5 DET A
H-3 PS 2 DET A
H-4 PS 2 DET A
H-5 PS 2 DET A
H-6 PS 2 DET A
H-7 PS 2 DET A
SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1609, R1 SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
None
2-143
Line #: DCA-508 Sheet 2 Service: Instrument piping from drywell water level temperature
Column B
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic -Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5533B, FSK-5556B
1) Hanger Drawing Numbers
FSK-5533B
H-1 PS 1 DET C
H-2 PS 1 DET B
H-3 PS 2 DET C
H-4 PS 5 DET A
H-5 PS 4 DET.A
H-6 PS 4 DET A
H-7 PS 5 DET B
H-8 PS 5 DET C
SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1609, R1 SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, RI SKM-602, RO SKM-1607, RO
FSK-5556B
Sh 55 Sh 8
PS 2 H-1 PS 2
DET C H-2 SNUB 2 PSA-1 H-3 SNUB 3 PSA-1 Sh 44
PS 1
SKM-1611, RO SKM-1611, RO SKM-602, RO SKM-602, RO SKM-1607, RO
SKM-1611, RO SKM-602, RO
2) Valve Vendor Print Numbers
V-16-70 M-123A-6-7
.2-144.
Line #: DCA-508Service: Instrument piping from drywell water level temperature
Column B
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5563B
1) Hanger Drawing Numbers
H-1 PS 2 DET A
H-2 PS 2 DET A
H-3 PS 4 DET B
H-4 PS 1 DET A
H-5 PS 1 DET A
H-6 PS 1 DET A
H-7 PS 1 DET B
H-8 PS 1 DET A
H-9 PS 1 DET A
H-10 PS 2 DET A
H-li PS 1 DET C DET 3
SH 22
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, RI SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, Ri SKM-602, RO SKM-1606, RO SKM-602,RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO FSK-5564B SKM-1611, RI
2) Valve Vendor Print Numbers
V-15-25 M123A-6-7
2-145
Sheet 3
Line #: DCA-509 Service: Main steam A piping
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5566B, EDS 0267884-023
1) Hanger Drawing Numbers
H-1 DEX X DET U
H-7 PS 6 DET A
H-2 PS 2 DET 6
H-3 PS 2 DET A
H-4 PS 2 DET A
H-5 PS 5 DET B
H-6 PS 2 DET C DET 7
FSK-5571B, R2 SKM-1608, RO SKM-602, RO SKM-1606, RO SKM-602, RO FSK-5565B, R6 SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, Ri SKM-602, RO SKM-1607, RO FSK-5565B, R3
2) Valve Vendor Print Numbers
V-14-17 M-123A-6-7
.2-146
I
Line #: DCA 510 Service: Main steam D piping
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5579
1) Hanger Drawing
H-1 DET X DET U
H-7 PS 6 DET A
H-2 PS 2 DET A
H-3 PS 2 DET A
H-4 SNUB 5 PSA-1
H-5 PS 2 DET C DET 5
H-6 PS 2 DET B
Numbers
FSK-5571B, R2 SKM-1608, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
FSK-5575B, R6 SKM-602, RO SKM-1607, RO FSK-5575B, R6 SKM-602, RO SKM-1609, Ri
2) Valve Vendor Print Numbers
V-14-12 M-123A-6-7
.2-147
Line #: Service:
DCA 511 Main steam D piping
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5578
1) Hanger Drawing Numbers
H-1 DET X DET U
H-2 PS 2 DET A
H-3 PS 2 DET A
H-4 PS 2 DET A
H-5 PS 2 DET A
H-6 PS 2 DET A
H-7 PS 2 DET A
FSK-5571, R2 SKM-1608, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-14-13 M-123A-6-7
Line #: DCA 512 Service: Recirculation loop B seal cavity upper IP-201B
Design Input Documents:
Piping Class/Summary Sheet: DCA/MI90 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5548B
1) Hanger Drawing Numbers
H-1 PS 1 DET B
SH-16 SNUB 5A SNUB 6A
H-2 PS 2 DET A
SKM-602, RO SKM-1609, Ri SKM-1611, RO
SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
None
2-148
Line #: DCA 513 Service: Recirculation loop A seal cavity lower IP201A
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5539B
1) Hanger Drawing Numbers
H-1 PS 2 DET C
Sh 133 SH 132 H-2 PS 2
DET u Sh 15 H-3 PS 1
DET B
SKM-602, RO SKM-1607, RO FSK-5539B FSK-5539B SKM-602, RO SKM-1608, RO FSK-5540B, R5 SKM 602, RO SKM-1609, RI
2) Valve Vendor Print Numbers
V-16-70 V-16-51 V-16-58
M-123A-6-7 M-123A-6-7 M-123A-6-7
2-149
Line #: DCA-514 Service: Reactor water level
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping SEress Isometric Drawings: FSK-5564B
1) Hanger Drawing Numbers
Sh 37 Sh 38 H-9 PS 2
DET A H-8 PS 1
DET A H-7 PS 1
DET B H-6 PS 1
DET A H-5 PS 1
DET A H-4 PS 4
DET A H-3 PS 4
DET C DET 1
H-2 PS 2 DET A
H-1 PS 2 DET A
FSK-5564B, R5 FSK-5564B, R5 SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, R1 SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO FSK-5561B, R6 SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
None
2-150
Line #: DCA-515 Service: Temperature equivalent column B
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5561B, FSK-5556B
1) Hanger Drawing Numbers
FSK-5561B
H-1 PS 2 DET A
H-2 PS 2 DET A
H-3 PS 2 DET B
H-4 PS 4 DET A
H-5 PS 1 DET A
H-6 PS 1 DET B
H-8 PS 2 DET C
H-7 DET C Sh 20 Sh 57
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, RI SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, Ri SKM-602, RO SKM-1607, RO FSK-5561B SKM-1611, RO SKM-1611, RO
FSK-5556B
Sh 55 Sh 8 H-1 PS 2
DET C H-2 SNUB 2
PSA-1 H-3 SNUB 3
PSA-1 Sh 44
SKM-1611, RO SKM-1611, RO SKM-602, RO SKM-1607, RO
SKM-1611, RO
2) Valve Vendor Print Numbers
V-15-21 M-123A-6-7
2-151
Line #: DCA-516 Service: Reactor water temperature column B
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5556B,
FSK-5562B
1) Hanger Drawing Numbers
FSK-5556B
Sh 55 Sh 8 H-1 PS 2
DET C H-2 SNUB 2
PSA-1 H-3 SNUB 3
PSA-1 Sh 44
PS 1
FSK-5662B
H-1 PS 5 DET A
H-2 PS 5 DET A
H-3 PS 2 DET A
H-4 PS 2 DET A
H-5 PS 2 DET A
H-6 PS 2 DET A
FSK-5662B,
FSK-5562
SKM-1611, RO SKM-1611,, RO SKM-602, RO SKM-1607, RO SKM-602, RO
SKM-602, RO
SKM-1611, RO SKM-602, RO
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
H-1 PS 2 DET A
H-2 PS 2 DET A
H-3 PS 4 DET A DET 1
H-4 PS 4 DET A
H-5 PS 4 DET A
H-6 PS 1 DET B
H-7 PS 1 DET C DET 1
H-8 PS 2 DET A
Sh 20 Sh 56
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO FSK-5661B SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, RI SKM, 602, RO SKM-1607, RO FSK-5561B SKM-602, RO SKM-1606, RO SKM-1611, RO SKM-1611, RO
2) Valve Vendor Print Numbers
V-15-22 M-123A-6-7
2-152
Line #: DCA-519C Service: Recirculation loop A
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic .Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5541B
1) Hanger Drawing Numbers
H-1 PS 2 DET C DET 1
H-2 PS 1 DET A
H-3 PS 1 DET B
H-4 PS 2 DET C
SKM-602, RO SKM-1607, RO FSK-5541B SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, Rl SKM-602, RO SKM-1607, RO
2) Valve Vendor Print Numbers
V-16-4 M-123A-6-7
Line #: DCA-519D Service: Recirculation loop A
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5542B
1) Hanger Drawing Numbers
DET 1 H-1 PS 2
DET C H-2 PS 1
DET A H-3 PS 1
DET B H-4 PS 2
DET C DET 1
FSK-5541B SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, Rl SKM-602, RO SKM-1607, RO FSK-5541B
2) Valve Vendor Print Numbers
V-16-17 M-123A-6-7
.2-153
Line #: DCA-520 Service: Recirculation loop A lP-21-A
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5537B
1) Hanger Drawing Numbers
H-1 PS 2 DET A
H-2 PS 2 DET A
H-3 PS 2 DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-16-60 M-123A-6-7
Line #: DCA-521 Service: Recirculation loop A 1P-210A
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5538B
1) Hanger Drawing Numbers
J=1 PS 2 DET C DET 1
H-2 PS 2 DET A
Sh 13 Sh 60
SKM-602, RO SKM-1607, RO FSK-5546B SKM-602, RO SKM-1606, RO SKM-1611, RO SKM-1611, RO
2) Valve Vendor Print Numbers
V-16-59 M-123A-6-7
2-154
Service: Recirculation loop B
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5554B
1) Hanger Drawing Numbers
H-1 PS 6 DET A
H-2 PS 2 DET C DET 1
Sh 48 DET 2 H-3 PS 5
DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO FSK-5553B FSK-5553B SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-16-81 M-123A-6-7
Line #: DCA-553 Service: Reactor water level
Design Input Documents:
Piping Class/Summary Sheet: DCA/MI90 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: EDS 027884-087
1) Hanger Drawing Numbers
SNUB 4 PSA-1
SH 58 H-1 PS 1
DET A H-2 PS 1
DET A H-3 PS 1
DET 2 Sh 9
PS 2
SKM-1611, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO FSK-5560B, R6 SKM-1611, RO FSK-5558B, R2 SKM-602, RO
2) Valve Vendor Print Numbers
None
2-155
Line #: DCA-522
Line #: DCA-534 Service: Temperature equalizing column A
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5555, FSK-5559B
1) Hanger Drawing Numbers
FSK-5555B
H-2 PS 2 DET C DET 2
H-1 Sh 7 PS 2
H-3 DET 3
FSK-5559B
Sh 9 PS 2
H-1 PS 1 DET 2
H-2 PS 1 DET A
H-3 PS 1 DET A
H-4 PS 1 DET A
H-5 PS 1 DET A
Sh 89
SKM-602, RO SKM-1607, RO FSK-5556B SKM-1611, RO SKM-602, RO FSK-5555B
SKM-1611, RO SKM-602, RO SKM-602, RO FSK-5560 SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606,RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-1611, RO
2) Valve Vendor Print Numbers
None
2-156
Line #: DCA-535 Service: Temperature Equalizing column A
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5555B,
FSK-5657BFSk-5558B,
1) Hanger Drawing Numbers
FSK-5555B
H-1 PS 2 DET C DET 2
H-2 SH 7 PS 2
H-3 DET 3
FSK-5558B
Sh 9 PS 2
H-1 PS 2 DET C
H-2 PS 2 *DET A
SKM-602, RO SKM-1607, RO FSK-5556B SKM-1611, RO SKM-602, RO FSK-5555B
SKM-1611, RO SKM-602, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO
FSK-5657B*
H-1 PS 2 DET B
H-2 PS 2 DET A
H-3 PS 1 DET A DET 1
H-4 PS 1 H-5 PS 1
DET A H-6 PS 1
DET A H-7 PS 2
DET A
SKM-602, RO SKM-1609, RI SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO FSK-5656B SKM-602, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
*V...15-03 M-123A-6-7
2-157e
Line #: DCA-536 Service: Instrument piping from X-14 to 1C-56
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5656B
1) Hanger Drawing Numbers
H-1 PS 2 DET A
H-2 PS 2 DET B
H-3 PS 2 DET A
H-4 DET PS 1 DET A
H-5 PS 1 DET A
H-6 PS 1 DET A
H-7 DET 2 PS 1
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, RI SKM-602, RO SKM-1606, RO FSK-5656B, R2 SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO FSK-5657 SKM-602, RO
2) Valve Vendor Print Numbers
None
2-158
Line #: Service:
DCA-536 Sheet 2 Temperature equalizing column A reference leg piping
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5557B
1) Hanger Drawing Numbers
Sh 9 PS 2
H-1 DET 1 PS 2
Sh 88 H-2 PS 1
DET A
FSK-1063 SKM-602, RO FSk-5558B SKM-602, RO SKM-1611, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-15-02 M-123A-6-7
Line #: Service:
DCA-536 Temperature equalizing column A
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5555B
1) Hanger Drawing Numbers
H-1 PS 2 H-2 SET 2
DET C PS 2
H-3 DET 3
SKM-602, RO FSK-5556B SKM-1607, RO SKM-602, RO FSK-5555B
2) Valve Vendor Print Numbers
None
-2-159
I
Line #: Service:
DCA-537 Recirculation system riser differential pressurizer N2G
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5535B
1) Hanger Drawing Numbers
H-1 DET 2 DET C PS 5
H-2 DET B PS 5
H-3 PS 4 DET A
H-4 PS 4 DET A
H-5 PS 5 DET A
H-6 DET 1 DET C PS 2
H-7 PS 2 DET S
H-8 PS 2 DET A
H-9 PS 2 DET A
H-10 PS 1 . DET A
FSK-5533B SKM-1607, RO SKM-602, RO SKM-1609, Rl SKM-602, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM 1606, RO FSK-5533B SKM-1607, RO SKM-602, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-16-68 M-123A-6-7
.2-160
Line #: DCA-538 Service: Recirculation system riser differential pressurizer N2F
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5534
1) Hanger Drawing Numbers
H-1 PS 5 DET A
H-2 PS 2 DET A
H-3 DET 2 DEC C PS 2
H-4 PS 2 DET A
H-5 PS 1 DET A
H-6 PS 1 DET A
H-7 PS 2 DET B
H-8 DET 1 PS 1 DEC C
H-9 PS 2 DET A
H-10 PS 1 DET A
H-11 PS 1 DET A
H-12 PS 1 DET A
H-13 PS 1 DET A
H-14 PS 1 DET 3
H-15 DET 5 DET C PS 1
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO FSK-5536B SKM-1607, RO SKM-602, RO SKM-602, RO SKM-1602, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, R1 FSK-5536B SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, RI FSK-5534B SKM-1607, RO SKM-602, RO
2) Valve Vendor Print Numbers
None
2-161
Line #: DCA-539 Service: Recirculation system riser differential pressure N2H
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping 9tress Isometric Drawings: FSK-5536B
1) Hanger Drawing Numbers
H-1 PS 5 DET A
H-2 PS 2 DET A
H-3 DET 2 DET 2 DEC C
H-4 PS 2 DET A
H-5 PS 1 DET A
H-6 PS 4 DET A
H-7 PS 2 DET B
H-8 DET 1 PS 1 DET C
H-9 PS 1 DET B
H-10 PS 1 DET A
H-11 PS 1 DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO FSK-5536B SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, R1 FSK-5536B SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1609, Ri SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-16-67 M-123A-6-7
2-162
Line #: DCA-540 Service: Main steam A piping X-102 (low pressure)
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic-Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5567B
1) Hanger Drawing Numbers.
H-1 DET X DET U
H-2 SNUB 4A PS 1
H-3 DET C PS 6
H-4 PS 2 DET A
H-5 PS 1 DET A
H-6 SNUB 3A PS 1
H-7 PS 1 DET A
H-8 PS 1 DET A
H-9 PS 2 DET A
FSK-5571B SKM-1608, RO
FSK-5567B, R6 SKM-1607, RO SKM-602, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
FSK-5567B, R6 SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO FSK-1063
2) Valve Vendor Print Numbers
V-14-18 M-123A-6-7
.2-163
Line #: DCA-541 Service: Main steam A piping X-102 (high pressure)
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5568B
1) Hanger Drawing Numbers
H-1 DET Z DET U
H-2 SNUB 2A PSA-1
H-3 DET C PS 6
H-4 PS 2 DET Z
H-5 PS 1 DET A
H-6 SNUB lA H-7 PS 1
DET A H-8 PS 1
DET A H-9 PS 2
DET A
FSK-5571B, R2 SKM-1608, RO
FSK-5568B, R5 SKM-1607, RO SKM-602, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO FSK-5568B, R5 SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO FSK-1063
2) Valve Vendor Print Numbers
V-15-19 M-123A-6-7
2-164
Line #: DCA-542 Service: Main steam B piping X-102C (low pressure)
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5571B
1) Hanger Drawing Numbers
H-1 DET X H-2 PS 2
DET A H-3 PS 2
DET A H-4 PS 2
DET A H-5 PS 2
DET A H-6 PS 2
DET A H-7 PS 2
DET A
FSK-5571B, R2 SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO FSK-1063
2) Valve Vendor Print Numbers
V-14-25 M-123A-6-7
2-165.
Line #: DCA-543 Service: Main steam line B X-34E (high pressure)
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: 0207884-009, Rev A
1) Hanger Drawing Numbers
H-1 DET 3 DET C PS 2
H-2 DET 4 DET C PS 2
H-3 PS 2 DET A
H-4 PS 2 DET A
FSK-5569B SKM-1607, RO SKM-602, RO FSK-5569B SKM-1607, RO SKM-602, RO SKM-602, RO SKM-1606, RO SKM 602, RO SKM-1606, RO FSK-1063
2) Valve Vendor Print Numbers
V-14-26 M-123A-6-7
2-166
Line #: DCA-545 Service: Main steam B piping X-102 (high pressure)
Design Input Documents:
Piping Class/Summary Sheet: DCA/MI90 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5572B
1) Hanger Drawing Numbers
(Special) DET C
H-1 PS 2 DET A
H-2 PS 2 DET A
H-3 PS 2 DET A
H-4 PS 2 DET A
H-5 PS 2 DET A
H-6 -PS 2 DET A
FSK-5571B SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-606, RO SKM-1606, RO FSK-1063
2) Valve Vendor Print Numbers
V-14-28 M-123A-6-7
2-167
Line #: DCA-546 Service: Main steam C piping X-30 (low pressure)
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5576B
1) Hanger Drawing Numbers
H-1 DET 4 H-2 DET A
PS 6 H-3 PS 2
DET A H-4 PS 2
DET A H-5 DET 5
DET C PS 2
H-6 PS 2 DET A
FSK-5575B SKM-1606, RO SKM-602, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO FSK-5575B SKM-1607, RO SKM-602, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-14-22 M-123A-6-7
2-168
Line #: Service:
DCA-547 Main steam C piping
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5573B
1) Hanger Drawing Numbers
DET Y H-1 PS 2
DET A H-2 PS 2
DET A H-3 PS 2
DET A H-4 PS 2
DET A H-5 PS 2
DET A H-6 PS 2
DET A H-7 PS 2
DET A H-8 PS 2
DET A
FSK-5575B SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-14-24 M-123A-6-7
2-169
Line #: DCA-548 Service: Main steam C piping X-34B (low pressure)
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5574B
1) Hanger Drawing Numbers
Special DET Y
H-1 PS 2 DET A
H-2 PS 2 DET A
H-3 PS 2 DET A
H-4 PS 2 DET A
H-5 PS 2 DET A
H-6 PS 2 DET A
H-7 PS 2 DET A
H-8 PS 2 DET A
FSK-5575 SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-14-21 M-123A-6-7
2-170
Line #: DCA-549 Service: Main steam C piping X-30 (high pressure)
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5575B
EDS ISO-0217884-013, RO
1) Hanger Drawing Numbers
H-1 DET Y H-2 PS 2
DET A H-3 PS 2
DET A H-4 DET 5
DET C PS 2
H-5 PS 2 DET B
DSK-5575B SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO FSK-5575B SKM-1607, RO SKM-602, RO SKM-602, RO SKM-1609, RI
2) Valve Vendor Print Numbers
V-14-23 M-123A-6-7
2-171
Line #: DCA-550 Service: Main steam D piping X-30D (low pressure)
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5580B
1) Hanger Drawing Numbers
H-1 DET A PS 6
H-2 DET A PS 2
H-3 DET A PS 2
H-4 SNUB-6 PSA-1
H-5 DET 5 DET C PS 2
H-6 DET A PS 2
SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO
FSK-5575B SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO
2) Valve Vendor Print Numbers
V-14-11 M-123A-6-7
2-172
Line #: Service:
DCA-551 Main steam D piping
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5577B
0207884-015RB
1) Hanger Drawing Numbers
H-1 DET X H-2 PS 6
DET A H-3 PS 2
DET A H-4 PS 2
DET A H-5 PS 2
DET A H-6 PS 2
DET A H-7 PS 2
DET A H-8 PS 2
DET A Ref
FSK-5571B SKM-602, RO SKM-1606, RO SKM-602, RO SKm-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-16067, RO SKM-602, RO SKM-1606, RO FSK-1063
2) Valve Vendor Print Numbers
V-14-10 M-123A-6-7
.2-173
Line #: Service:
DCA-552 Recirculation loop A piping at FE 4631 to X-56 (low pressure)
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5544B
1) Hanger Drawing Numbers
H-1 DET 1 DET C PS 2
H-2 PS 2 DET A
H-3 PS 2 DET A
H-4 DET C H-5 DET C
FSK-5552B, R4 SKM-1607, RO SKM-602, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-1607, RO SKM-1609, Ri
2) Valve Vendor Print Numbers
V-16-16 M-123A-6-7
2-174
Line #: Service:
DCA-553 Recirculation loop A piping at FE 4631 to X-56 (high pressure)
Design Input Documents:
Piping Class/Summary Sheet: DCA/MI90 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5543B
1) Hanger Drawing Numbers
H-1 DET 1 PS 2 DET C
H-2 PS 2 DET A
H-3 PS 2 DET A
H-4 DET C H-5 PS 6
DET A H-6 PS 6
DET A H-7 PS 2
DET C H-8 PS 2
DET C
FSK-5552B, R4 SKM-602, RO SKM-1609, RI SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-1609, R1 SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, RI SKM-602, RO SKM-1609, RI
2) Valve Vendor Print Numbers
V-16-15 M-123A-6-7
2-175
Line #: DCA-554 Service: Recirculation loop A, seal cavity
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5540B
1) Hanger Drawing Numbers
H-1 PS 1 DET B
SH 15 PS 1 H-2 PSA-1
SNUB 8 H-3 PSA-1
SNUB 9 H-4 SNUB 7
SPA-1
SKM-602, RO SKM-1609, Ri SKM-602, RO FSK-5540, R5
FSK-5540, R5 FSK-5540, R5 FSK-5540, R5 FSK-5540, R5
2) Valve Vendor Print Numbers
V-16-34 MI23A-6-7
2-176
Line #: Service:
DCA-554 Sheet 2 Main steam B piping
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5569B
0207884-009
1) Hanger Drawing Numbers
H-1 DET 3 DET C PS 2
H-2 DET $ DET C PS 2
H-3 PS 2 DET A
H-4 PS 2 DET A
Detail X
FSK-5569B, R3 SKM-1607, RO SKM-602, RO FSK-5569B, R3 SKM-1607, RO SKM-602, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO FSK-5571B
2) Valve Vendor Print Numbers
V-14-27 M-123A-6-7
2-177
Line #: DCA-555 Service: Recirculation loop B piping seal cavity (1) lower IP-201B
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5547B
1) Hanger Drawing Numbers
Sh 16 H-1 PS 1
DET B H-2 PS 2
DET A
FSK-5540B SKM-602, RO SKM-1609, R1 SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-16-52 V-16-53
M-123A-6-7 M-123A-6-7
2-178
Line #: DCA-555 Sheet 2 Service: Reactor building below 757'-6" drywell recirculation
loop B water purge to pump IP-201B
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4467B
1) Hanger Drawing Numbers
Sh 119 PS 1 Sh 118 PS 2 Sh 32 H-1 DET 2
PS 2 DET C
H-2 DET A PS 2
H-3 PS 2 DET 3
H-4 DET 1 PS 2
H-5 PS 1 DET A
H-6 PS 2 DET A
SKM-602, RO SKM-602, RO SKM-1611, RO FSK-4467B SKM-602, RO SKM-1607, RO SKM-1606, RO SKM-602, RO SKM-602, RO SKM-1609, RI FSK-4467B SKM-602, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
M-123A-6-7 M-123-6-7 M-123A-3-6 M-123A-6-7 M-123A-6-7 M-123D-12-1
V-17-78 V-17-79 V-17-80 V-17-81 V-17-82 V-17-83
2-179
Line #: Service:
DCA-555 Sheet 3 Reactor bulding below 757'-6" drywell minipurge
drain line off feed line to 4" HBC-80
Design Input Documents:
Piping C-lass/Summary Sheet: DCA/MI90 Seismic Response Spectra: See FSAR
Piping Stress Isometric Drawings: FSK-4466B
1) Hanger Drawing Numbers
H-1 PS 6 DET A
H-2 PS 2 DET A
H-3 PS 2 DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
None
2-180
Line #: DCA-556 Service: Recirculation loop B piping for P-5-4637 (X-31)
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5553B
1) Hanger Drawing Numbers
H-1 PS 5 DET A
H-2 DET 1 PS 2 DET C
H-3 DET 2 Sh 48 PS 1
H-4 PS 6 DET A
SKM-602, RO SKM-1606, RO FSK-5553B, R4 SKM-602, RO SKM-1607, RO FSK-5553B, R4 FSK-5553B, R4 SKM-602, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-16-80 M-123A-6-7
2-181
Line #: DCA-557 Service: Recirculation loop B
Design Input Documents:
Piping C_1ass/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings:' FSK-5545B
1) Hanger Drawing Numbers
Sh 36 H-1 PS 5
DET A H-2 PS 2
DET C DET 1
SKM-1611, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO FSK-5553B
2) Valve Vendor Print Numbers
V-16-55 M-123A-6-7
2-182
IEM
Line #: DCA-558 Service: Recirculation loop B piping IP-201B
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190
Seismic Response Spectra: See FSAR
Piping Stress Isometric Drawings: FSK-5546B
1) Hanger Drawing Numbers
H-1 PS 2 DET A
H-2 DET 1 PS 2 DET C
Sh 12 DET B
Sh 61
SKM-602, RO SKM-1606, RO FSK-5546B, R5 SKM-602, RO SKM-1607, RO FSK-5546B, R5 SKM-1609, RI FSK-5546B, R5
2) Valve Vendor Print Numbers
V-16-54 M-123-17-6-7
2-183
Service: Recirculation loop B
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5550B
1) Hanger Drawing Numbers
H-1 PS 2 DET C DET 2
H-2 PS 1 DET A
H-3 PS 1 DET B
H-4 PS 1 DET A
H-5 PS 1 DET C DET 1
H-6 PS 2 DET A
SKM-602, RO SKM-1607, RO FSK-5549B, Ri SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, RI SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO FSK-5549B, R1 SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-16-31 M123A-6-7
2-184
DCA-5 59Line #:
Line #: DCA-560 Service: Recirculation loop B
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic-Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5549
1) Hanger Drawing Numbers
H-1 PS 2 DET C DET 2
H-2 PS 1 DET A
H-3 PS 1 DET B
H-4 PS 1 DET A
H-5 PS 1 DET C
H-6 PS 2 DET A
SKM-602, RO SKM-1607, RO FSK-5549 SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, R1 SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-16-32 M-123A-6-7
2-185
Line #: Service:
DCA-561 Recircualtion loop B
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5552B
1) Hanger Drawing Numbers
H-1 PS 2 DET C
H-2 PS 2 DET A
H-3 PS 3 DET A
H-4 DET C H-5 DET C
SKM-602, RO SKM-1607, RO SKM-602, RO SKM-106, RO SKM-602, RO SKM1606, RO SKm-1607, RO SKM-1607, RO
2) Valve Vendor Print Numbers
V-16-34 M-123A-6-7
2-186
Line #: DCA-562 Service: Recirculation loop B
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190
Seismic Response Spectra: See FSAR
Piping Stress Isometric Drawings: FSK-5551
1) Hanger Drawing Numbers
H- 1 PS 6 DET A
H-2 PS 6 DET A
H-3 PS 2 DET A
H-4 PS 2 DET A
H-5 PS 2 DET C
H-6 PS 2 DET C
H-7 PS 2 DET C DET 1
H-8 DET C
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1607, RO FSK-5552B SKM-1607, RO
2) Valve Vendor Print Numbers
V-16-3 3 M-123A-6-7
2-187
Line #: Service:
DCA-563 Recirculation sample pipe
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5593B, FSK-5693B
1) Hanger Drawing Numbers
FSK-5592B
Sh 53 SNUB PSA-1
H-1 PS 1 DET C
H-2 PS 1 DET A
H-3 PS 1 DET C
H-4 PS 1 DET C
H-5 PS 1 DET A
Sh 14 H-6 PS 1
DET C H-7 PS 1
DET A H-8 PS 1
DET C H-9 PS 2
DET A H-10 PS 2
FSK-5692B
Sh 135 Sh 136 H-1 PS 1
DET C H-2 PS 2
DET C
SKM-1611, RO
SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-1611, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO
SKM-1611, RO SKM-1611, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1607, RO
2) Valve Vendor Print Numbers
V-16-73 CV-4639
M-123A-6-7 M-123A-6-7
2-188
Line #: DCA-569 Service: Recirculation steam piping
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic -Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5587B
1) Hanger Drawing Numbers
H-1 PS 2 DET V
Sh 128 H-2 PS 2
DET A H-3 PS 2
DET A H-4 PS 1
DET A H-5 PS 1
DET A H-6 PS 1
DET A H-7 PS 1
DET A H-8 PS 1
DET B H-9 SNUB 10
PSA-1 H-10 SNUB 12
PSA-1 Sh 25 Sh 63 Sh 128 H-li PS 1
DET C H-12 SNUB 11
SKM-602, RO SKM-1606, RO SKM-1611, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, Ri
SKM-1611, RO SKM-1611, RO SKM-1611, RO SKM-602, RO SKM-1607, RO
2) Valve Vendor Print Numbers
V-24-7 M-123A-6-7
2-189
Line #: DCA-570 Service: Recirculation steam piping
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic 'Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5585B
1) Hanger Drawing
H-1 SNUB 6B PSA-1
H-2 PS 6 DET C
H-3 PS 6 DET U
Sh 24 PS 2 DET A
H-4 PS 6 DET A
H-5 PS 2 DET V
H-6 PS 2 DET A
H-7 DET C H-8 PS 5
DET A H-9 PS 4
DET B H-10 PS 4
DET A H-11 PS 4
DET A H-12 PS 5
DET C H-13 PS 5
DET A H-14 PS 2
DET A
Numbers
SKM-602, RO SKM-1609, RI SKM-602, RO SKM-1608, RO SKM-1611, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, Ri SKM-602, RO SKM-1606, RO SKM-1609, RI SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, R1 SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1608, RO
2) Valve Vendor Print Numbers
V-24-5 M-123A-6-7
2-190
Line #: DCA-571 Service: Steam piping (RCIC)
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5588B
1) Hanger Drawing Numbers
H-1 PS 2 DET C DET 4
H-2 PS 1 DET A
H-3 PS 1 DET A
H-4 PS 1 DET A
H-5 PS 1 DET A
H-6 PS 1 DET A
H-7 PS 1 DET C DET 3
Sh 91 H-8 PS 6
DET C Sh 90 Sh 92 H-9 SNUB 28A
PSA-1 H-10 PS 2
DET A H-1l PS 2
DET A Sh 90 Sh 91 Sh 92
SKM-602, RO SKM-1607, RO FSK-5587B, R6 SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO FSK-5587B, R6 SKM-1611, RO SKM-602, RO SKM-1607, RO SKM-1611, RO SKM-1611, RO
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-1611, RO SKM-1611, RO SKM-1611, RO
2) Valve Vendor Print Numbers
V-24-4 M-123A-6-7
2-192
Line #: DCA-574 Service: Jet pump instrumentation
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5502B, FSK-5503.
FSK-5504B, FSK-5505B
1) Hanger Drawing Numbers
FSK-5502B
H-1 PS 5 DET A
H-2 PS 4 DET C
H-3 PS 4 DET A
H-4 PS 4 DET A
FSK-5503B**
H-1 PS 5 DET A
H-2 PS 4 DET C
H-3 PS 4 DET A
H-4 PS 4 DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
FSK-5504B***
H-1 PS 5 DET A
H-2 PS 4 DET C
H-3 PS 4 DET A
H-4 PS 4 DET A
FSK-5505B****
H-1 PS 5 DET A
H-2 PS 4 DET C
H-3 PS 4 DET C
H-4 PS 4 DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
*V-15-7 **V-15-12
***V-15-13 ****V-15-15
M-123A-6-7 M-123A-6-7 M-123A-6-7 M-123A-6-7
2-193
Service: Jet pump instrumentation
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic_-Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5506B
1) Hanger Drawing Numbers
FSK-5506B*****
H-1 PS 5 DET A
H-2 PS 4 DET C
H-3 PS 4 DET A
H-4 PS 4 DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
*****V-15-15 M-123A-6-7
2-194 j
Line #: DCA-574 Sheet 2
Line #: DCA-578 Service: Jet pump instrumentation
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5521B, FSK-5618
1) Hanger Drawing Numbers
FSK-5521B*
H-1 PS 4 DET A
H-2 PS 4 DET A
H-3 PS 4 DET C
H-4 PS 5 DET A
FSK-5618B**
H-1 PS 1 DET A
H-2 PS 2 DET B
H-3 PS 1 DET C
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, Ri SKM-602, RO SKM-1607, RO
2) Valve Vendor Print Numbers
*V-15-34 M-123A-6-7
2-195
Line #: Service:
DCA-579 Jet pump instrumentation
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic-,Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5519B
1) Hanger Drawing
H-1 PS 4 DET A
H-2 PS 4 DET A
H-3 PS 4 DET C
H-4 PS 5 DET A
Numbers
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-15-30 M-123A-6-7
2-196
Line #: Service:
DCA-580 Jet pump instrumentation pipe detail nozzle N8B
Design Input Documents:
Piping _Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5515
1) Hanger Drawing Numbers
H-1 PS 4 DET A
H-2 PS 4 DET A
H-3 PS 4 DET C
H-4 PS 5 DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKm-1606, RO
2) Valve Vendor Print Numbers
V-15-29 M-123A-6-7
.2-197.
Line #: DCA-581 Service: Jet pump instrumentation piping flow transmission FT 4503
Design Input Documents:
Piping Class/Summary Sheet: . DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5517B
1) Hanger Drawing Numbers
H-1 PS 4 DET A
H-2 PS 4 DET A
H-3 PS 4 DET C
H-4 PS 5 DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-15-28 M-123A-6-7
2-198
Line #: DCA-582 Service: Jet pump instrumentation piping flow transmission
FT 4517, 4501 (low pressure)
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5516B
Hanger Drawing
H-1 PS 4 DET A
H-2 PS 4 DET A
H-3 PS 4 DET C
H-4 PS 5 DET A
Numbers
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKm-602, RO SKM-1607, RO SKM-602, RO SKM-1606,RO
2) Valve Vendor Print Numbers
V-1 5-26 M-123A-6-7
2-199
Line #: DCA-584 )Service: Jet pump instrumentation piping flow transmission
FT 4509, 4519 (low pressure)
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5523B
.1) Hanger Drawing Numbers
H-1 PS 5 DET A
H-2 PS 4 DET C
H-3 PS 4 DET A
H-4 PS 4 DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-15-28 M-123A-6-7
2-200
Line 4: Service:
DCA-585 Jet pump instrumentation piping flow transmission FT 4511
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5524B
1) Hanger Drawing
H-1 PS 5 DET A
H-2 PS 4 DET C
H-3 PS 4 DET A
H-4 PS 4 DET A
Numbers
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-1531 M-123A-6-7
2-201
Line #: DCA-586 Service: Jet pump instrumentation piping flow transmission
FT 4513
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5525B
1) Hanger Drawing Numbers
H-1 PS 5 DET A
H-2 PS 4 DET C
H-3 PS 4 DET A
H-4 PS 4 DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-1 5-3 2 M-123A-6-7
2-202
Line #: DCA-588 Service: Jet pump instrumentation piping flow transmission
FT 4515
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5526B
1) Hanger Drawing Numbers
H-1 PS 5 DET A
H-2 PS 4 DET C
H-3 PS 4 DET A
H-4 PS 4 DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-15-33 M-123A-6-7
2-203
Line #: DCA-589 Service: Jet pump instrumentation piping flow transmission
FT 4519 (high pressure)
Design Input Documents:
Piping Class/Summary Sheet: DCA/MI90 Seismic Re-sponse Spectra: See FSAR .Piping Stress Isometric Drawings: FSK-5527B
1) Hanger Drawing Numbers
H-1 PS 5 DET A
H-2 PS 4 DET C
H-3 PS 4 DET A
H-4 PS 4 DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-15-30 M123A-6-7
2-204
Line #: Service:
DCA-590 Jet pump instrumentation piping flow transmission FT 4509
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Reqponse Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5512B
1) Hanger Drawing
H-1 PS 5 DET A
H-2 PS 4 DET C
H-3 PS 4 DET A
H-4 PS 4 DET A
2) Valve Vendf
V-15-1 1
Numbers
SKM-602, RD SKM-1606, RD SKM-602, RD SKM-1607, RD SKM-602, RD SKM-1606, RD SKM-602, RD SKM-1606, RD
or Print Numbers
M-123A-6-7
2-205
Line *: Service:
DCA-591 Instrumentation piping from X-40A to 1C-122 (tube F)
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5612B
1) Hanger Drawing Numbers
H-1 PS 1 DET A
H-2 PS 1 DET A
H-3 PS 1 DET A
H-4 PS 1 DET A
H-5 PS 1 DET A
H-6 PS 1
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
None
2-206
Line #: DCA-591Service: Jet pump instrumentation piping flow transmission
FT 4518, LITS 4565
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR .Piping Stress Isometric Drawings: FSK-5514B
1) Hanger Drawing Numbers
H-1 PS 5 DET A
H-2 PS 4 DET C
H-3 PS 4 DET A
H-4 PS 4 DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-15-17 M-123A-6-7
2-207
Sheet 2
Line #: Service:
DCA-592 Jet pump instrumentation low pressure piping flow transmission FT 4518, 4502
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Re-sponse Spectra: See FSAR .Piping Stress Isometric Drawings: FSK-5509B
1) Hanger Drawing Numbers
H-1 PS 4 DET A
H-2 PS 4 DET C
H-3 PS 4 DET A
H-4 PS 4 DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-15-20 M-123A-6-7
2-208
Line #: DCA-593 Service: Jet pump instrumentation to X-40A
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5510B
1) Hanger Drawing Numbers
H-1 PS 5 DET A
H-2 PS 4 DET C
H-3 PS 4 DET A
H-4 PS 4 DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
None
2-209
Line #: Service:
DCA-594 Jet pump instrumentatio to X-40A
Design Input Documents:
Piping Class/Summary Sheet: DCA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-5511B
1) Hanger Drawing Numbers
H-1 PS 5 DET A
H-2 PS 4 DET C
H-3 PS 4 DET A
H-4 PS 4 DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
V-15-10 M-123A-6-7
2-210
Line *: Service:
DLA-1 HPCI discharge to FW line
Design Input Documents:
Piping Class/Summary Sheet: DLA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4162B
1) Hanger Drawing Numbers
H-1 PS 6 DET U
SKM-602, RO SKM-1608, RO
2) Valve Vendor Print Numbers
V-23-17 V-23-18
M-141-55-1-1 M-141-55-1-1
Line #: Service:
DLA-2 FW discharge from isolation stop check valve to reactor
Design Input Documents:
Piping Class/Summary Sheet: DLA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4309
1) Hanger Drawing Numbers
H-2 PS 1 DET B
H-2 PS 1 DET B
SKM-602, RO SKM-1609, Ri SKM-602, RO SKM-1609, R1
2) Valve Vendor Print Numbers
M141-55(l)-l M141-55(1)-i M141-55(1)-i M141-55(1)-1 M141-55(1)-i M141-55(1)-1
2-211
V-14-59 V-14-94 V-14-60 V-14-56 V-14-95 V-14-57
Line #: Service:
DLA-2 FW discharge from isolation stop check valve to reactor
Design Input Documents:
Piping Class/Summary Sheet: DLA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4145B
1) Hanger Drawing Numbers
H-1 PS 1 DET A
H-2 DET A SH 43 PS 6 DET B
H-3 PS-6 DET A
H-4 PS 2 DET A
H-5 DET A SB 42 PS 6 DET B
H-6 PS 6 DET A
SKM-602, RO SKM-1606, RO FSK-4145B, R6 SKM-1611, RO SKM-602, RO SKM-1609, Ri SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO FSK-4145B, R6 SKM-1611, RO SKM-602, RO SKM-1609, Ri SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
M-123-A-6-7 M-123-A-6-7 M-123-A-6-7 M-123-A-6-7
V-14-35 V-14-36 V-14-33 V-14-34
2-212
Line #: Service:
DLA- 3 Steam to HPCI turbine
Design Input Documents:
Piping Class/Summary Sheet: DLA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4074B
1) Hanger Drawing Numbers
H-1 PS 1 DET B
H-2 PS 1 DET A
H-3 PS 1 DET A
H-4 PS 1 DET A
H-5 DET 1 8-6 PS 1
DET B
SKM-602, RO SKM-1609, RI SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO FSK-4074, R5 SKM-602, RO SKM-1609, Ri
2) Valve Vendor Print Numbers
V-22-5 M-123-A-6-7 V-22-6 M-123-A-6-7
2-213
Line #: DLA-4 Service: RHR pump suction from reactor recirculating line
valve drains
Design Input Documents:
Piping Class/Summary Sheet: DLA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-3922, FSK-4308
1) Hanger Drawing Numbers
FSK 3922
H-1 DET A SKM-1606, RO
FSK 4308
None
2) Valve Vendor Print Numbers
FSK 3922
V-19-54 V-19-53
FSK 4308
V-19-94 V-19-95 V-19-96 V-19-97
M-141-55-1-1 M-141-55-1-1
M-141A-56-4 M-141A-56-4 M-141A-56-4 M-141A-56-4
Line #: DLA-5 Service: RHR discharge
Design Input Documents:
Piping Class/Summary Sheet: DLA/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4575B
1) Hanger Drawing Numbers
None
2) Valve Vendor Print Numbers
V-20-73 V-20-74
M-141A-56-4 M-141A-56-4
2-214
Line #: DLA-6 Service: RHR discharge
Design Input Documents:
Piping Class/Summary Sheet: DLA/M-190 Seismic Response Spectra: See FSAR Piping Streds Isometric Drawings: FSK-4575B, FSK-4947B,
FSK-3946B
1) Hanger Drawing Numbers
FSK 4575B
None
FSK 3947B
H-1 DET 1
FSK 3946B
H-1 DET 1
2) Valve Vendor
FSK-3947B, R6
FSK-3946B, R6
Print Numbers
FSK 4575B
V-19-35 V-19-38
FSK 3947B
V-20-38 V-20-39
FSK 3946B
V-19-49 V-19-50
M141A-53-2 M141A-53-2
M141-55(1)-1 M141-55(1)-i
M141-55(1)-i M141-55(1)-1
2-215
Line #: EBB-2 Service: RCIC pump discharge
Design Input Documents:
Piping Class/Summary Sheet: EBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4230B
1) Hanger Drawing Numbers
FSK 4230B
H-1 PS 1 DET B
SKM-602, RO SKM-1609, RI
2) Valve Vendor Print Numbers
MO-2426 V-24-41
M141-55(1)-i M141A-53-2
Line #: EBB-3 Service: RCIC pump recirculation line
Design Input Documents:
Piping Class/Summary Sheet: EBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4139B, FSK-4147B
1) Hanger Drawing Numbers
FSK-4139B
H-1 PS 6 DET A
H-2 PS 1 DET C
H-3 PS 1 DET A
H-4 PS 1
FSK-4147B
H-1 PS 1 DET B
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO SKM-602, RO
SKM-602, RO SKM-1609, RI
2) Valve Vendor Print Numbers
FSK-4139B
V-25-06 V-25-20 V-25-21 V-25-29 MO-2510
PSK-4147B
M141-057-3 M141A-53-2 M141A-53-2 M141A-54(1)-4 M141A-54(1)-4
2-217
None
Line #: Service:
EBB-14 HPCI steam side
Design Input Documents:
Piping Class/Summary Sheet: EBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-3559B
1) Hanger Drawing Numbers
H-1 PS 1 DET B
H-2 PS 2 DET U
H-3 PS 2 DET U
H-4 PS 1 DET A
H-5 PS 1 DET A
H-6 PS 2 DET B
SKM-602, RO SKM-1609, RI SKM-602, RO SKM-1608, RO SKM-602, RO SKM-1608, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, RI
2) Valve Vendor Print Numbers
MI41A-55-1-1 M141A-55-1-1 M141-56-4 M141-56-4 M141D-1-2 M141-55-1-2 M141-56-4 M141-56-4 MI41A-38-1
2-218
V-25-10 V-22-9 CV-2 212 CV-2 211 V-22-52 V-22-53 V-22-7 V-22-8 CV-2 206
Line #: EBB-15 Service: Drain pot to main condenser RCIC steam side
Design Input Documents:
Piping Class/Summary Sheet: EBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-3558B
1) Hanger Drawing Numbers
H-1 PS 1 DET A
H-2 PS 2 DET U
H-3 PS 2 DET B
H-4 PS 1 DET A
H-5 PS 5 DET U
H-6 PS 5 DET U
H-7 PS 1 DET B
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1608, RO SKM-602, RO SKM-1609, R1 SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1608, RO SKM-602, RO SKM-1608, RO SKM-602, RO SKM-1608, RO
2) Valve Vendor Print Numbers
V-24-39 V-24-40- V-2 4-1 V-24-2 CV-2 409 CV-2 410 CV-2411 V-24-28 V-24-29
M141-54-14 M141-54-14 M141A-56-4 MI41A-56-4 M141A-38-1 M141A-38-1 M141A-38-1 M141-55-1-1 M141-55-1-1
2-219
Line #: EBB-16 Service: Steam to RHR heat exchanger to CV-2033, CV-1963
Design Input Documents:
Piping Class/Summary Sheet: EBB/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4392B
1) Hanger Drawing Numbers
H-1 PS 1 DET A
H-2 PS 1 DET A
H-3 PS 1 DET B
H-4 PS 1 DET C
H-5 PS 6 DET A
SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1606, RO SKM-602, RO SKM-1609, R1 SKM-602, RO SKM-1607, RO SKM-602, RO SKM-1606, RO
2) Valve Vendor Print Numbers
M141-55(1)-i MI41-55(1)-1 M144A-118-3 M144A-l18-3
V-19-78 V-19-79 CV-1964 CV-2034
2-220
Line #: Service:
GE main steam Loop A Main Steam
Design Input Documents:
Piping Class/Summary Sheet: Seismic Response Spectra: Piping Stress Isometric Dra
1) Hanger Drawing Numbers
MS-1-1
HA-1
MS-1-2
MS-1-3
MS-1-4
C-516R5 C-518R5 M-352R5 BP301R4 301ARO 301BR2 301CRO C-516R5 C-518R5 M-352R5 C-516R5 C-518R5 M-352R5 C-516R5 C-518R5 M-352R5
wir
SSAI
SSA2
MS-1-5
HA-2
MS-1-6
MS-1-7
MS-1-8
MS-1-9
AAl
Loop A/M-190 See FSAR gs: BEC-01-13(3-5-73)
BP401AR1 401R1 BP401ARI 402RO C524R4 M-352R5 B03R4 303AR2 303BR4 C-524R4 M-352 R5 M-359 R3 M-352 R5 C-533 R3 M-332 R5 C-531 R5 M-352 R5 GE-731E 782 SHTS 1 & 3
2) Valve Vendor Print Numbers
PSV-4400
PSV-4401
CV-4412 CV-4413
B-21-12-13 B-21-3379-1-1-2 B-21-12-13 B-21-3379-1-1-2 B-21-4-3 B-21-4-3
2-221
Line #: GE main steam Loop B Sheet 1 of 2 r ervice: Main Steam
Design Input Documents:
Piping Class/Summary Sheet: Loop B/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: BEC-01-14(3-5-73)
1) Hanger Drawing Numbers
C516 R5 C518 R5 M352 R5 BPBO1A RO 302A R2 302 R4 C516 R5 C518 R5 M-352 R5 C-516 R5 C-518 R5 M 352 R5 BP405 RO 405A R3 405B R2 BP405A R3 405B R2 406 RO
MS-2-4
MS-2-5
MS-2-6
HB-2
MS-2-9
HB-3
C-516 R5 C-532 R4 M-352 R5 C-524 R4 M-352 R3 C-524 R4 M-352 R5 M-357 R3 BP-304 R4 304A RO 304B R4 C-524 R4 M-352 R5 BP-304A RO 305 R4 305A R4
2) Valve Vendor Print Numbers
PSV 4403 PSV 4402 PSV-4401 CV 4415 CV 4316
B-21-2831-53-9 B-21-13-2 B-21-3379-1-12 B-21-4-3 B-21-4-3
MS-2-1
HB-1
MS-2-2
MS-2-3
SSB1
SSB2
2-222
Line #: GE main steam Loop B Sheet 1 of 2 Service: Main Steam
Design Input Documents:
Piping Class/Summary Sheet: Loop B/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: BEC-01-14(3-5-73)
1) Hanger Drawing Numbers
MS-2-1 C-516 R5 C-518 R5 M-352 R5
HB-1 BPBO1A RO 302A R2 302 R4
MS-2-2 C-516 R5 C-518 R5 M-352 R5
MS-2-3 C-516 R5 C-518 R5 M-352 R5
SSB1 BP-405 RO 405A R3 405B R2
SSB2 BP-405A R3 405B R2 406 RO
MS-2-4 C-516 R5 C-534 R4 M-352 R5
MS-2-5 C-524 R4 M-352 R3
MS-2-6 C-524 R4 M-352 R5 M-357 R3
HB-2 BP-304 R4 304A RO 304B R4
MS-2-7 C-524 R4 M-352 R5
MS-2-0 C-524 R4 M-352 R5
HB-3 BP-304A RO 305 R4 305A R4
2) Valve Vendor Print Numbers
PSV 4403 B-21-2831-53-9 PSV 4402 B-21-13-2 PSV 4401 B-21-3379-1-12 CV 4415 B-21-4-3 CV 4316 B-21-4-3
2-224
Line #: GE main steam Loop C Sheet 1 of 2 Service: Main Steam
Design Input Documents:
Piping Class/Summary Sheet: Loop C/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: BEC-01-15(3-5-73)
1) Hanger Drawing Numbers
C-516 R5 C-518 R5 M-352 R5 BP301A RO 302A R3 302 R4 C-516 R5 C-518 R5 C-516 R5 C-518 R5 M-352 R5 BP407 RO 407A R4 407B RI 408 RO 408 R4 407A R4 407B RI
MS-3-34
MS-3-5
MS-3-6
HC 2
MS-3-7
MS-3-9
HC3
C-534 R4 M-352 R5 C-524 R4 M-352 R5 C-524 R4 M-352 R5 M-357 R3 BP 304 R4 304A RO 304B R4 C-524 R4 M-352 R5 C-524 R4 M-352 R5 BP305 R4 305A R4 304A RO
2) Valve Vendor Print Numbers
B-21-4-3 B-21-4-3
2-225
MS-3-1
HC1
MS-3-2
MS-3-3
SSC1
SSC2
CV-4418 CV-4419
Line #: Service:
GE main steam Loop C Sheet 2 of 2 Main Steam
Design Input Documents:
Piping Class/Summary Sheet: Loop C/M-190 Seismic Response Spectra: See FSAR Piping St-ress Isometric Drawings: BEC-01-15(3-5-73)
1) Hanger Drawing Numbers
MS-3-ll
MS-3-12
MS-3-13
MS-3-14
AC-1
C-524 R4 M-352 R5 M-359 R3 M-352 R5 C-533 R3 M-352 R5 C-531 R5 M-352 R5 GE-731E782 Sheets 1 & 3
2) Valve Vendor Print Numbers
None
2-226
Line #: GE Main steam Loop D Service: Main Steam
Design Input Documents:
Piping Class/Summary Sheet: Loop D/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: BEC-01-16(3-5-73)
1) Hanger Drawing Numbers
C-516 R5 C-518 R5 M-357 R5 BP-301 R4 301A RO 301B R2 301C RO C-516 R5 C-518 R5 M-352 R5 C-516 R5 C-518 R5 M-352 R5 C-516 R5 C-518 R5 M-352 R5 BP401A R1 403 Ri
SSD2
MS-4-5
HD-2
MS-4-6
MS-4-7
MS-4-8
MS -4-9
AD-1
BP401A R1 BP404 RO C-524 R4 M-352 R5 BP303A R2 303 R4 303B R4 C-524 R4 M-352 R5 M-359 R3 M-352 R5 C 533 R3 M-352 R5 C-531 R5 M-352 R5 GE731E782 Sheet 1 & 3
2) Valve Vendor Print Numbers
PSV 4406 PSV 4401 PSV 4407 CV 4420 CV4421
B21-73-2 B21-3379-1-1-2 B21-13-2 B21-4-3 B21-4-3
MS -4-1
HD-l
MS-4-2
MS-4-3
M5-4-4
SSOl
2-227
Line #: Service:
HBC-21 Discharqe from sump pumps
Desiqn Input Documents:
Piping Class/Summary Sheet: HBC/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-3530B
1) Hanger Drawing Numbers
H-1 PSI SKM-602 RO DET A SKM-1606 RO
2) Valve Vendor Print Numbers
V-37-1 V-37-2 V-37-3 V-37-4
M141-52-2 M141-54(1)-4 M141-52-3 M141-54(1)-4
Line #: Service:
HBD-34 Diesel oil piping
Design Input Documents:
Piping Class/Summary Sheet: HBD/M-190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-3437
1) Hanger Drawing Numbers
H-1 PS 1 DET U
H-2 PS 1 DET U
H-3 PS 1 DET U
H-4 PS 1 DET U
H-5 PS 1 DET U
H-6 FSK-343
SKM-602, RO SKM-1608, RO SKM-602, RO SKM-1608, RO SKM-602, RO SKM-1608, RO SKM-602, RO SKM-1608, RO SKM-602, RO SKM-1608, RO
7B, Rev 1
2) Valve Vendor Print Numbers
None
2-228
Line #: Service:
DLA-2 Feedwater discharge from isolation stop check valve to reactor
Design Input Documents:
Piping Class/Summary Sheet: DLA/M190 Seismic Response Spectra: See FSAR Piping Stress Isometric Drawings: FSK-4345
1) Hanger Drawing Numbers
None
2) Valve Vendor Print Numbers
V-14-58 V-14-61
M141-55(1)-i M141-55(1)-1
2-229
Attachment 4
RESULTS OF INSPECTION
TABLE OF CONTENTS
4-1 Group 1 Lines
4-6 Group 2 Lines
4-8 Group 3 Lines
4-11 Computer-Analyzed, Safety-Related Small Pipe
4-18 General Electric Piping
Notes:
1. "Note 1" is shown in the tables where original seismic calculations were not available to determine the number of discrepancies.
2. Discrepancies are defined as anomalies found during comparison of as-built configurations with as-designed configurations.
3. "No nonconformances" is defined as follows:
* Lines in which comparison found no discrepancies
* Lines for which stress evaluation found that discrepancies did not invalidate original analysis.
Attachme (10 page
RESULTS OF INSPECTION OF ACCESSIBLE LINES
Line Number
DBB-1
EBB-4 includes EBB-1
EBB-6
EBB-17
GBB-3
GBB-5
GBB-6
GBB-8
GBB-10
GBB-13
GBB-15
GBB-18
GBB-22
GBB-23
GRC-2
System
RHR heat exchanger discharge
RCIC
HPCI
Core spray
RHR pump discharge
RHR pump discharge
RHR pump discharge
RHR pump discharge
RHR
Core spray
RHR pump discharge to test line
RHR
RHR
RHR
RHR service water
Group 1 Lines
Number of Discrepancies
None
Note 1
Note 1
3
1
4
2
3
3
4
4
2
2
2
7
4-1
Evaluation Status
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Remarks
Seismic analysis of as-built performed 4
Seismic analysis of as-built performed
Seismic analysis of as-built performed
Seismic analysis of as-built performed
Seismic analysis of as-built performed
Seismic analysis of as-built performed
Seismic analysis of as-built performed
Seismic analysis of as-built performed
Seismic analysis of as-built performed
rrr."- ? I
Gr~ou Line
Number
GBC-4
GBC-5
GLE-5
HBB-2
HBB-6
HBB-7
H813-8
HBB-9
HBB-14
HBB-15
HBB-21
HBB-23
HBB-24
HBB-25
HBB-29
HBD-24
HBD-26
Lnes (continued)
System
RHR cooling water
RHR service water
RHR pump test lines to torus
Core spray pump suction
HPCI turbine exhaust
Turbine steam exhaust
HPCI pump suction
IIPCI pump suction from condensate
RCIC pump suction
RCIC pump suction from condensate storage tank
RCIC from RHR heat exchanger
RHR pump suction
RHR pump suction
Drain from fuel pool skimmer
RHR
Emergency service water
Emergency service water
Number of Discrepancies
1
7
None
2
2
1
1
18 2 8 8 1
3
1
28
2
Evaluation Status
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete for accessible portions, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
4-2
Remarks
Seismic analysis of as-built performed
Seismic analysis of as-built performed
Portions inaccessible, pipeway entrance sealed
Seismic analysis of as-built performed
GroulM Lines (continued)
Line Number Systen
HBD-28 Emergency service water
HBD-31 RHR cooling water
HBD-32 RHR service water
HBD-34 Diesel oil
HBD-61 Diesel-air supply
HBD-67 River water pump discharge
HBD-80 Emergency Service water
HBD-82 Circulating water
HBD-97 Well water
HBD-122 Standby diesel generator
HBD-159 Reactor building chill water
HBD-161 HVAC control building
HCB-2 Standby liquid control
HCC-6 HPCI pump suctions
HCC-7 Condenser and demineralized water
HCC-8 Core spray pump suction
Number of Discrepancies
6
6
2
2
2
15
6
4
2
7
7
7
4
1
3
3
Evaluation Status
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
4-3
Remarks
GrA'1 Lines (continued)
Line Number System
HLE-1 HPCI suction
HLE-2 RCIC pump suction from torus
HLE-4 Core spray
HLE-5 Turbine steam exhaust
HLE-6 HPCI turbine exhaust
HLE-7 RHR pump suction
HLE-12 Core spray pump discharge
HLE-13 Core spray pump discharge
HLE-15 Core spray pump discharge
HLE-16 Core spray test lines
HLE-18 Core spray test lines
HLE-19 Core spray pump discharge
HLE-23 Containment vent purge exhaust
HLE-24
HLE-25
HLE-26
Torus vent purge exhaust
Containment atmospheric control
Containment atmospheric control
Number of Discrepancies
None
None
None
3
None
1
None
None
None
1
None
Note 1
Note 1
5
2
None
Evaluation Status
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete for accessible portion, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Remarks
Seismic analysis of as-built performed
Seismic analysis of as-built performed; portion sealed in duct chase inaccessible
4-4
Group 1 Lines (continued)
Number of Discrepancies
I
System
Torus vacuum breaker
Drywell cooling water
Drywell cooling water
Line Number
HLE-27
HLE-28
HLE-29
Evaluation Status
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
None
None
Remarks
Line Number
DBB-2
EBB-18
GRB3-4
GBB-7'
GBB-9
GBB-14
GBB-16
GBC-1
GBC-3
GLE-6
HBB-1
HBB-24
HBB-30
IIBD-25
System
RHR heat exchanger discharge
Core spray pump discharge
RHR pump discharge
RHR pump discharge'
RHR heat exchanger discharge
Core spray pump discharge
RHR pumps-test liner RHR heat exchanger discharge
Pumphouse RHR service water
RHR service water return
Core spray pump discharge
Core spray pump suction
RHR pump suction
RHR reactor building
Emergency service water
ULTS OF INSPECTION OF ACCESSIBLE LINES
Group 2 Lines
Number of Discrepancies Evaluation Status
None Evaluation complete, no nonconformance
3 Evaluation complete, no nonconformance
5 Evaluation .complete, no nonconformance
See GBB-5 Evaluation complete, no nonconformance
See GBB-4 Evaluation complete, no nonconformance
6 Evaluation complete, no nonconformance
8 Evaluation complete, no nonconformance
10 Evaluation complete, no nonconformance
1 Evaluation complete, no nonconformance
See GBB-14 Evaluation complete, no nonconformance
8 Evaluation complete, no nonconformance
2 Evaluatidn complete, no nonconformance
4 / Evaluati'on complete, no nonconformance
11 Evaldation complete, no onconformance
4-6
Remarks
Analysis of as-built configuration performed
Analysis of as-built configuration performed
Analysis of as-built configuration performed
Analysis of as-built configuration performed
Analysis of as-built configuration performed
Analysis of as-built configuration performed
Analysis of as-built configuration performed
I . , t I
Group 2 Lines (continued)
Line Number
HBD-27
HBD-29
HBD-30
HBD-68
HBD-81
HBD-160
HBD-162
HBD-192
HLE-3
HLE-8
HLE-11
HLE-14
HLE-17
System
Emergency service water
Emergency service water
RHR service water return
River water supply
Emergency service water
Chilled water
Chilled water
Lube oil
Core spray pump discharge
RHR pump suction
Core spray pump discharge
Core spray pump discharge
RHR heat exchanger discharge
Number of Discrepancies
3
24
3
13
None
5
4
Note 1
See HBB-1
None
See GBB-14
See GBB-14
See GBB-4
Evaluation Status
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
4-7
Remarks
Analysis of as-built configuration performed
Analysis of as-built configuration performed
Analysis of as-built configuration performed
Analysis of as-built configuration performed
Analysis of as-built configuration performed
Analysis of as-built configuration performed
Analysis of as-built configuration performed
Analysis of as-built configuration performed
Analysis of as-built configuration performed
I OF ACCESSIBLE LINES
Line Number System
DBA-002 Turbine main steam 0
DBA-003 HPCI
Group 3 Lines
Number of Discrepancies
3
1
1DBA-004 Steam to RCIC turbine
DBA-005 RHR
DBA-006 (includes DCA-16)
0
Control rod 4
1DBA-7/8 Drain test connection
DCA-2 RHR 0
DCA-006 Cleanup pump suction
DCA-008 (includes DLA-7)
DCA-009 ( includes DLA-8)
DLA-00d (includes EBB-5)
2
Core spray discharge
Core spray discharge
2
1
HPCI discharge 1
1DLA-002 Feedwater discharge
DLA-003 HPCI
DLA-004 RHR (includes DCA-5)
6
1
Evaluation Status
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Remarks
None
None
None
Portion inaccessible due to submergence in spent fuel pool
None
None
None
None
None
None
None
None
None
None
4-8
rr"."" '". 1, 1
RESULTS OF INS
Number of Discrepancies
7
6
3
Note 1
1
25
0
0
0
0
0
0
2
4
5
3
Evaluation Status
Evaluation copmlete, no nonconformance
Evaluation complete no nonconformance
Evaluation complete
Evaluation complete
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Remarks
None
None
See DCA-008
See DCA-009
None
Seismic analysis of as-built performed
Seismic analysis of as-built performed
None
None
None
None
None
None
None
None
None
None
None
4-9
3 Lines (continued)
Line Number System
HBD-115 Drywell well water
HBD-116 Well water return
HBD-64/65 Drywell cooling water
HLE-006 HPCI turbine exhaust to torus
HLE-021 Nitrogen
HLE-030 Drywell floor drains
HLE-031 Drywell equipment drain
HLE-032/ Drywell cooling water HLE-033
HLE-034 Cooling water
HLE-035 Well water
HLE-036 Nitrogen purge supply
HBD-159 Chilled water
HBD-160 Chilled water
HBD-161 Chilled water
IBD-162 Chilled water
Number of Discrepancies
6
8
2
2
0
3
3
7
6
4
1
1
2
6
0
Evaluation Status
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation not performed
4-10
Remarks
None
None
None
None
None
None
None
None
None
None
None
Portion is enclosed in metal box and inaccessible.
Portion is enclosed in metal box and inaccessible.
Portion is enclosed in metal box and inaccessible.
Line is enclosed in metal box and inaccessible.
COMPUTER-ANAL)
Line Number
CRD-524
CRD-525
CRD-526
DBA-001
DBA-02A
DBA-02B
DBA-02C
DBA-004
DBA-005
DBA-007
DBA-009
DRA-010 High-pressure leakoff
DCA-1/4A Recirculating loop A (includes large pipe)
DCA-1/48 Recirculating loop B (includes large pipe)
DCA-006 Cleanup pump
System
CRD scram
CRD scram
CRD scram
Steam line drains containment
Steam line drains containment
Test connection - MSIV LC system
Steam line drains containment
Steam to RCIC turbine
RHR pump discharge
Drain test connection
Reactor vessel vent
9
0
2
1
no nonconfoi
Evaluation no nonconfor
Evaluation no nonconfor
Evaluation no nonconfor
Evaluation ( no nonconfor
Bj RTY-RELATED SMALL PIPE
Number of Discrepancies Evaluation
1 Evaluation no nonconfo
3 Evaluation no nonconfo
1 Evaluation no nonconfo
3 Evaluation no nonconfo
3 Evaluation no nonconfo
94 Evaluation no nonconfo
0 Evaluation no nonconfo
1 Evaluation no nonconfo
3 Evaluation no nonconfo
3 Evaluation no nonconfoi
11 Evaluation
Status
complete, rmance
complete, rmance
complete, rmance
complete, rmance
complete, rmance
complete, rmance
complete, rmance
complete, rmance
complete, rmance
complete, rmance
complete, rmance
complete, rmance
complete, rmance
complete, mance
complete, mance
4-11
Remarks
None
None
None
None
None
Includes 22 isometrics
None
None
None
None
Portions of piping inaccessible due to submergence in fuel storage pool
Portions of piping inaccessible due to high conjestion of piping in area
None
None
None
yvf - ': t
Computer-Analyzed Safety-Related Small P pe (continued)
System
Test loop for core spray
HPCI steam
Number of Discrepancies
2
6
DCA-013
DCA-17/18
DCA-19A
DCA-19B
DCA-19C
DCA-19D
DCA-020
DCA-503
DCA-504
DCA-505
DCA-506
DCA-507
DCA-508
DCA-509
DCA-510
Standby liquid control
CRDs
Recirculation system
Recirculation system
Recirculation system
Recirculation system
Recirculation system
Main steam A
Recirculating system riser
Recirculating system riser
Recirculating system riser
Recirculatinq system riser
Temperature column B
Main steam A
Main steam D
Line Number
DCA-010
DCA-0 11
Evaluation Status
Evaluation complete no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Remarks
None
Portions of line inaccessible due to conjestion of piping in area
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
13
8
3
2
2
18
2
3
3
4
3
3
8
5
4
!I
-r." . " I
Computer-Analyzed Safety-Related Small Pipe (continued)
Line Number System
DCA-511 Main steam D
DCA-512 Recirculating loop B
DCA-513 Recirculating loop A
DCA-514 Reactor water level
DCA-515 Temperature column B
DCA-516 Temperature column B
DCA-519C Recirculating loop A
DCA-519D Recirculating loop A
DCA-520 Recirculating loop A
DCA-521 Recirculating loop A
DCA-522 Recirculating loop A
DCA-534 Temperature column A
DCA-535 Temperature golumn A
DCA-536 Temperature equalization column A
DCA-537 Recirculating system riser differential pressure N2G
DCA-538 Recirculating system riser differential pressure N2F
DCA-539 Recirculating system riser differential pressure N2H
Number of Discrepancies
3
2
3
4
2
3
1
3
2
1
3
5
6
3
2
0
3
Evaluation Status
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Remarks
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
~* ~': ~"i
Computer-Analyzed Safety-Related Small Pipe (continued)
Line Number System
DCA-540 Main steam A piping X-102 (low-pressure)
DCA-541 Main steam A piping X-102 (high-pressure)
DCA-542 Main steam B piping X-102C (low-pressure)
DCA-543 Main steam line B X-34E (high-pressure)
DCA-545 Main steam B piping X-102 (high-pressure)
DCA-546 Main steam C piping X-30 (low-pressure)
DCA-547 Main steam C
DCA-548 Main steam C piping X-34B (low-pressure)
DCA-549 Main steam C piping X-30 (high-pressure)
DCA-550 Main steam D piping
DCA-551 Main steam B piping
DCA-552 Recirculation loop A piping
DCA-553 Recirculation loop A piping
DCA-554 Recirculating loop A
DCA-554 Recirculating loop B
DCA-555 Recirculating loop B piping
DCA-556 Recirculating loop B
Number of Discrepancies
1
4
2
2
2
2
1
0
2
1
2
3
2
6
5
2
Evaluation Status
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Remarks
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
Computer-Analyzed Safety-Related Small Pipe (continued)
Line Number System
DCA-557 Recirculating loop B
DCA-558 Recirculating loop B
DCA-559 Recirculating loop A
DCA-560 Recirculating loop B
DCA-561 Recirculating loop B
DCA-562 Recirculating loop B
DCA-563 Recirculation sample
DCA-569 RCIC steam
DCA-570 RCIC steam
DCA-571 RCIC steam
DCA-574 Jet pump instrumentation
DCA-578 Jet pump instrumentation
DCA-579 Jet pump instrumentation
DCA-580 Jet pump instrumentation
DCA-581 Jet pump instrumentation
DCA-582 Jet pump instrumentation
DCA-584 Jet pump instrumentation
Number of Discrepancies
2
4
4
3
5
3
5
1
2
3
10
3
1
1
2
2
1
Evaluation Status
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Remarks
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
Computer-Analyzed Safety-Related Small Pipe (continued)
Line Number of Number System Discrepancies
DCA-585 Jet pump instrumentation 1
DCA-586 Jet pump instrumentation I
DCA-588 Jet pump instrumentation 2
DCA-589 Jet pump instrumentation I
DCA-590 Jet pump instrumentation I
DCA-591 Instrument piping 3
DCA-592 Jet pump instrumentation 2
DCA-593 Jet pump instrumentation to X-40A 1
DCA-594 Jet pump instrumentation to X-40A I
DLA-001 HPCI discharge to feedwater line 0
DLA-002 Feedwater discharge from isolation stop check valve 5 to reactor
DLA-003 Steam to HPCI turbine 0
DLA-004 RHR pump suction from reactor recirculating line 0 valve draing
DLA-5/6 RHR discharge 0
EBB-001 RCIC pump discharge 1
EBB-002 RCIC pump discharge 0
EBB-003 RCIC pump recirculation 2
Evaluation Status
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
4-16
Remarks
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
Computer-Analyzed Safety-Related Small Pipe (continued)
Line Number System
EBB-014 HPCI steam side
EBB-015 Drain pot to main condenser RCIC steam side
EBB-015 Steam to RHR heat exchanger to CV-2033, CV-1963
HBC-021 Sump discharge
HBD-034 Diesel oil piping
DCA-533 Reactor water level
DCA-007 RCIC discharge to feedwater line
HLE-564 Test connection for expansion joint XJ-2400
Number of Discrepancies
3
2
6
5
1
3
3
0
Evaluation Status
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
4-17
Remarks
None
None
None
None
None
None
None
None
-W
General Electric Piping
Line Number mystem
Loop A GE main steam
Loop B GE main steam
Loop C GE main steam
Loop D GE main steam
Number of Disc repanc ies
7
1
5
4
Evaluation Status
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Evaluation complete, no nonconformance
Remarks
None
None
None
None